You are on page 1of 25

HDPE TO DUCTILE IRON

A D HDPE TO PCCP

2016-05-12
VERSION DATE
(4 TO 32-INCH ONLY) NO. DESCRIPTION (16 TO 32-INCH ONLY) NO. DESCRIPTION
TRANSITION ASSEMBLY 1. WALL BLOCKING, REFER TO TRANSITION ASSEMBLY 1. WALL BLOCKING, REFER TO
1 MJ D.I. PIPE /
HDPE PIPE 2 DETAIL HD4 OR HD5 DETAIL HD4 OR HD5
VALVE /

HD1
2. IPS x DIPS RESTRAINED MJ 2 PCCP PIPE
FITTING 2. RESTRAINT COUPLER WITH
ADAPTER WITH STEEL PIPE HDPE PIPE
STEEL PIPE STIFFENER

VERSION NO.
STIFFENER AND KIT

1.0
3. WALL ANCHOR OR FLEX
3. WALL ANCHOR OR FLEX RESTRAINT, REFER TO DETAIL
MIN. 1' RESTRAINT, REFER TO DETAIL
MAX. 5' HD4
3 HD4 OR HD5
NOTES: MIN. 1' 4. PCCP DEEP JOINT ADAPTER.
4 INSTALL AT EXISTING JOINT.
A. HIGH DENSITY POLYETHYLENE (HDPE) FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906. 3 MAX. 5'
B. MECHANICAL FITTINGS SHALL BE SPECIFICALLY DESIGNED FOR USE WITH HDPE PIPE. FIELD WELD PER
1
C. INSTALL STAINLESS STEEL INTERNAL STIFFENER IN THE END OF THE HDPE PIPE WHEN HDPE PIPE IS INSERTED INTO NOTES: MANUFACTURERS INSTRUCTIONS,
THE BELL END OF NON-HDPE PIPE, VALVE, FITTING, OR INTO THE HUB OF A MECHANICAL COUPLING. IF PCCP IS RESTRAINED JOINT.

TRANSITION FROM HDPE TO OTHER


A. FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906.
D. INTERNAL STIFFENER CAN BE WEDGE TYPE OR SOLID BODY. STIFFENER WILL BE RATED FOR DR AND ID OF PIPE. FOR
B. MECHANICAL FITTINGS SHALL BE SPECIFICALLY DESIGNED FOR USE WITH HDPE PIPE.
WATER, 304 OR 316 STAINLESS STEEL IS ALLOWED. FOR WASTEWATER, 316 SS IS REQUIRED.

MATERIAL (4-INCH TO 32-INCH)


E. MECHANICAL JOINT ADAPTERS SHALL BE PE4710 AND CAN BE MADE TO ASTM D 3261. IF MACHINED, ADAPTERS MUST
C. STAINLESS STEEL INTERNAL STIFFENERS SHALL BE INSTALLED IN THE END OF THE HDPE PIPE WHEN
MEET THE REQUIREMENTS OF ASTM F 2206. ADAPTERS SHALL HAVE A PRESSURE RATING EQUAL TO THE PIPE. HDPE PIPE IS INSERTED INTO THE BELL END OF NON-HDPE PIPE, VALVE, FITTING, OR INTO THE HUB OF A
F. FIGURE ABOVE SHOWS TRANSITION TO BELL END OF DIP. FOR TRANSITION TO PLAIN END OF DIP, SEE PVC FIGURE. BOLTED COUPLING.
G. EXTERNAL RESTRAINT DEVICES ARE NOT ALLOWED. D. INTERNAL STIFFENER CAN BE WEDGE TYPE OR SOLID BODY. STIFFENER WILL BE RATED FOR DR AND ID
OF PIPE. FOR WATER, 304 OR 316 STAINLESS STEEL IS ALLOWED. FOR WASTEWATER 316 SS IS
REQUIRED.
B HDPE TO PVC OR DI
(4 TO 32-INCH ONLY)
TRANSITION ASSEMBLY
NO. DESCRIPTION
1. WALL BLOCKING, REFER
E. RESTRAINT COUPLER SLEEVE SHALL BE ASTM A513 WITH FUSION BONDED EPOXY. LOW ALLOY STEEL
BOLTS CONFORM TO AWWA C111.4.
PVC OR TO DETAIL HD4 OR HD5
1 2 HDPE TO STEEL
HDPE PIPE DI PIPE 2. BELL MJ ADAPTER WITH
MECHANICAL RESTRAINT
KIT
E (4 TO 32-INCH ONLY)
TRANSITION ASSEMBLY
NO. DESCRIPTION
1. THRUST BLOCK, REFER TO
DETAIL HD4 OR HD5
3. WALL ANCHOR OR FLEX 2. HDPE PLAIN END x STEEL PLAIN
RESTRAINT, REFER TO 4 STEEL END WELD-ON TRANSITION FOR
3 MIN. 1' DETAIL HD4 OR HD5 HDPE PIPE PIPE
2 WATER
MAX. 5'
NOTES: 3. WALL ANCHOR OR FLEX
A. FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906. RESTRAINT, REFER TO DETAIL
B. MECHANICAL FITTINGS USED SHALL BE SPECIFICALLY DESIGNED FOR USE WITH HDPE PIPE. HD4
C. STAINLESS STEEL INTERNAL STIFFENERS SHALL BE INSTALLED IN THE END OF THE HDPE PIPE WHEN 4. BUTT FUSION OR
MIN. 1' 5
HDPE PIPE IS INSERTED INTO THE BELL END OF NON-HDPE PIPE, VALVE, FITTING, OR INTO THE HUB OF A ELECTROFUSION JOINT
3 MAX. 5'
BOLTED COUPLING 5. STEEL WELD
1
D. RESTRAINT COUPLER SLEEVE SHALL BE ASTM A513 WITH FUSION BONDED EPOXY. LOW ALLOY STEEL
BOLTS CONFORM TO AWWA C111.4 NOTES:
E. WHEN PVC BELL END IS ENCOUNTERED, FIELD CUT PVC TO FORM PLAIN END PER MANUFACTURER'S A. FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906.
INSTRUCTIONS. WHEN DI BELL END IS ENCOUNTERED, USE DETAIL HD1 A. B. TRANSITION SHALL BE MANUFACTURED TO ASTM D2513 CATEGORY 1.
C. COAT INTERIOR AND EXTERIOR OF WELD PER MANUFACTURER'S INSTRUCTIONS.

F HDPE TO HDPE ELECTROFUSION TRANSITION


ASSEMBLY (4-INCH TO 24-INCH ONLY)
C 2
HDPE TO HDPE
MECHANICAL TRANSITION ASSEMBLY
2 NO. DESCRIPTION NO. DESCRIPTION
1. MECHANICAL HDPE HDPE PIPE HDPE PIPE 1. ELECTROFUSION
1 1
3 3 COUPLING. COUPLING
2. WALL BLOCKING, REFER
TO DETAIL HD4 OR HD5
3. WALL ANCHOR OR FLEX NOTES:
MIN. 1' MIN. 1' RESTRAINT, REFER TO A. ONLY ALLOWED WHEN BUTT FUSION IS NOT POSSIBLE.
EXISTING MAX. 5' MAX. 5' DETAIL HD4. B. FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906.
HDPE PIPE

A CITY OF CHARLOTTE DEPARTMENT


NEW INSTALLATION HDPE PIPE C. PROVIDE ELECTROFUSION RECORD TO CHARLOTTE WATER INSPECTOR WITHIN ONE HOUR OF FUSION PER
NOTES:
A. ONLY ALLOWED WHEN BUTT FUSION IS NOT POSSIBLE. STANDARD SPECIFICATION.
B. FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906. NOTES TO DESIGNER
C. MECHANICAL FITTINGS SHALL BE SPECIFICALLY DESIGNED FOR USE WITH HDPE PIPE. A. CHARLOTTE WATER PREFERS JOINING HDPE USING BUTT FUSION. IF BUTT FUSION IS NOT POSSIBLE
D. INTERNAL STIFFENER CAN BE WEDGE TYPE OR SOLID BODY. STIFFENER WILL BE RATED FOR DR AND ID THEN ELECTROFUSION FITTNGS ARE ALLOWED. IF ELECTROFUSION FITTINGS ARE NOT POSSIBLE, THEN
OF PIPE. FOR WATER, 304 OR 316 STAINLESS STEEL IS ALLOWED. FOR WASTEWATER 316 SS IS MECHANICAL FITTINGS ARE ALLOWED. CHARLOTTE WATER DOES NOT ALLOW BURIED FLANGED JOINTS.
REQUIRED.
2016-05-12
VERSION DATE
NOTES TO DESIGNER
A. THIS DETAIL APPLIES ONLY TO 4-INCH THROUGH 12-INCH
PIPE TRANSITIONS. LARGER DIAMETER TRANSITIONS

HD2
REQUIRE SPECIFIC DESIGN AND APPROVAL.
B. CHARLOTTE WATER PREFERS JOINING HDPE USING BUTT

VERSION NO.
FUSION JOINING. IF BUTT FUSION IS NOT POSSIBLE THEN

1.0
ELECTROFUSION FITTNGS ARE ALLOWED. IF
ELECTROFUSION FITTINGS ARE NOT POSSIBLE, THEN
MECHANICAL FITTINGS ARE ALLOWED. CHARLOTTE WATER
DOES NOT ALLOW BURIED FLANGED JOINTS.

TO AC PIPE (4-INCH TO 12-INCH)


NO. DESCRIPTION
1. WALL BLOCKING, REFER TO STANDARD

TRANSITION FROM HDPE


2 DETAIL HD4
2. RESTRAINED MECHANICAL COUPLING OR
REDUCING MECHANICAL COUPLING. STEEL
PIPE STIFFENER REQUIRED ON HDPE.
3. WALL ANCHOR OR FLEX RESTRAINT, REFER
TO STANDARD DETAIL HD4

3
1

TRANSITION NOTES:
A. FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906.
B. HIGH DENSITY POLYETHYLENE (HDPE) FITTINGS SHALL BE MOLDED OR FABRICATED BY PIPE MANUFACTURER.
C. MECHANICAL FITTINGS SHALL BE SPECIFICALLY DESIGNED FOR USE WITH HDPE PIPE.
D. STAINLESS STEEL INTERNAL STIFFENERS SHALL BE INSTALLED IN THE END OF THE HDPE PIPE WHEN HDPE PIPE IS INSERTED INTO THE BELL END OF NON-HDPE PIPE, VALVE, FITTING, OR
INTO THE HUB OF A BOLTED COUPLING. INTERNAL STIFFENER CAN BE WEDGE TYPE OR SOLID BODY. STIFFENER WILL BE RATED FOR DR AND ID OF PIPE. FOR WATER, 304 OR 316
STAINLESS STEEL IS ALLOWED. FOR WASTEWATER, 316 IS REQUIRED.
E. MECHANICAL JOINT ADAPTERS SHALL BE PE4710 AND CAN BE MADE TO ASTM D3261. IF MACHINED, ADAPTERS MUST MEET THE REQUIREMENTS OF ASTM F2206. ADAPTERS SHALL HAVE A
PRESSURE RATING EQUAL TO THE PIPE.
F. WHEN BELL END IS ENCOUNTERED, FIELD CUT PIPE TO FORM A PLAIN END.

ASBESTOS NOTES:
A. ASBESTOS CEMENT (AC) PIPE, ALSO KNOWN AS TRANSITE PIPE, IS KNOWN TO CONTAIN ASBESTOS CONTAINING MATERIAL (ACM). SPECIAL WASTE MANAGEMENT PROCEDURES AND HEALTH
AND SAFETY REQUIREMENTS WILL BE APPLICABLE WHEN REMOVAL AND/OR DISTURBANCE OF THIS PIPE OCCURS.
B. WRITTEN NOTIFICATION TO THE NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES OR THE DEPARTMENT OF ENVIRONMENTAL PROTECTION OF MECKLENBURG COUNTY 10
DAYS PRIOR COMMENCING WITH THE REMOVAL OF AC PIPE IS REQUIRED. AT EACH LOCATION SHOWN IN THE PLANS AND/OR IDENTIFIED BY THE CONTRACTOR TO INVOLVE AC PIPE, THE
CONTRACTOR WILL BE REQUIRED TO REMOVE THE NECESSARY AMOUNT OF AC PIPE TO MAKE THE CONNECTION WITHOUT CREATING ANY FRIABLE MATERIAL. THE CONTRACTOR SHALL
REMOVE WHOLE SECTIONS OF AC PIPE AND MAKE THE TIE-IN AT THE NEAREST JOINT. CONTRACTOR WILL UNCOVER NO MORE THAN 20-FEET OF AC PIPE AT ANY TIME. CUTTING OF AC PIPE
SHALL BE MINIMIZED. THE CONTRACTOR SHALL REMOVE ANY CUT AC PIPE AND STORE IT IN A SECURE, ENGINEER APPROVED LOCATION FOR EVENTUAL DISPOSAL BY CONTRACTOR. PRIOR
TO PERFORMING THIS WORK, THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND THE OWNER OF THE UTILITY OF THE WORK SCHEDULE 72 HOURS IN ADVANCE OF BEGINNING THE WORK.
C. WHEN WORKING WITH AC PIPES, CONTRACTOR WILL COMPLY WITH OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) AND NATIONAL EMISSIONS STANDARDS FOR HAZARDOUS
AIR POLLUTANTS (NESHAP) REGULATIONS, INCLUDING BUT NOT LIMITED TO USE OF PERSONAL PROTECTIVE EQUIPMENT, SPECIALIZED TRAINING, ACCREDITATION, USE OF WET WORK

A CITY OF CHARLOTTE DEPARTMENT


PROCEDURES TO CUT AND REMOVE AC PIPE, AND HANDLING AND DISPOSAL OF AC PIPE AND MATERIAL INCLUDING CONTAMINATED SOIL.
D. AC PIPE WILL BE ABANDONED BY REMOVAL OR ABANDON IN PLACE BY GROUTING. ALL AC PIPE AND MATERIALS REMOVED WILL BECOME THE PROPERTY OF THE CONTRACTOR. THE
CONTRACTOR WILL PROVIDE THE OWNER WITH DISPOSAL RECEIPTS SHOWING PROPER DISPOSAL AT AN AUTHORIZED FACILITY.
2016-05-12
VERSION DATE
HD3
NO. DESCRIPTION
1. HDPE EMBEDMENT MATERIAL – FINE AGGREGATE ACCORDING TO

VERSION NO.
ASTM C33 TABLE 1

1.0
2. BACKFILL - COMPACT BACKFILL PER ASTM D 698 AND AASHTO T-99
AS MODIFIED BY NCDOT TO 95% MAXIMUM DENSITY WITHIN A
ROAD RIGHT-OF-WAY. FINAL 6-INCHES OF SUBGRADE SHALL BE
COMPACTED TO 100%. 85% MAXIMUM DRY DENSITY REQUIRED
3 OUTSIDE ROAD RIGHT-OF-WAY.
3. WARNING TAPE - 6-INCH WIDE WARNING TAPE INSTALLED 1 FOOT
MIN. MIN. BELOW GROUND SURFACE AS WELL AS DIRECTLY ABOVE
12" HDPE EMBEDMENT MATERIAL.
4. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER
TRACER WIRE WITH 30 MIL THICK BLUE HDPE INSULATION AT THE

EMBEDMENT AND BACKFILL


2 BOTTOM OF THE EMBEDMENT LAYER. DO NOT ATTACH TRACER
WIRE TO PIPE.
BACKFILL
NOTES:

FOR HDPE PIPE


A. WHERE PIPE IS INSTALLED DEEPER THAN 8 FEET, INSTALL
ADDITIONAL TRACER WIRE AT A DEPTH BETWEEN 4 AND 5-FEET.
3 INSTALL TRACER WIRE IN A PVC CONDUIT.
B. EMBEDMENT SHOULD BE PLACED IN LIFTS, NOT EXCEEDING 6
INCHES IN THICKNESS, AND THEN TAMPED. TAMPING SHOULD
BE ACCOMPLISHED WITH A MECHANICAL TAMPER.
6" MIN. DEPTH
C. A MAXIMUM OF 100 FEET OF OPEN TRENCH WILL BE ALLOWED
AFTER COMPACTION
AT ANY TIME, UNLESS APPROVED BY ENGINEER.
D. PERFORM CONDUCTIVITY TEST ON THE TRACER WIRE AT FINAL
HDPE INSPECTION.
EMBEDMENT
ET LE
ER
M B

MATERIAL
IA IA
D AR
V

6" MIN. (COMPACTED) REQUIRED TRENCH WIDTH


PIPE SIZE MINIMUM TRENCH MAXIMUM TRENCH
(INCHES) WIDTH (INCHES) WIDTH (INCHES)
<18 PIPE OD + 12 PIPE OD + 30

4 18 to 23 PIPE OD + 12 PIPE OD + 36

12" 24 to 32 PIPE OD + 24 PIPE OD + 36


MIN.
MAXIMUM TRENCH WIDTH NOTES:
A. LARGER TRENCH WIDTH ALLOWED TO
ACCOMMODATE BUTT FUSION EQUIPMENT AT FUSION
LOCATIONS.

A CITY OF CHARLOTTE DEPARTMENT


2016-05-12
VERSION DATE
w NO. DESCRIPTION
MINIMUM NUMBER OF FLEX RESTRAINTS 1. HDPE PIPE
ELEVATION VIEW BY PIPE SIZE 2. ELECTROFUSED HDPE FLEX RESTRAINT OR WALL ANCHOR

HD4
HDPE NOMINAL PIPE NUMBER OF FLEX 3. CONCRETE WALL BLOCKING - F'C = MINIMUM 3,600 PSI.

VERSION NO.
SIZE (INCHES) RESTRAINTS 4. FLEX RESTRAINTS FOR HDPE PIPE. SEE TABLE FOR REQUIRED NUMBER OF FLEX

1.0
RESTRAINTS BY PIPE SIZE. COMPLY WITH MANUFACTURERS INSTRUCTIONS
4 THROUGH 8 2 FOR NUMBER OF FLEX RESTRAINTS IF GREATER THAN SHOWN IN TABLE.
10 THROUGH 12 3 5. AWG NO. 12 GAUGE SOLID COPPER TRACER WIRE WITH BLUE 30 MIL HDPE
INSULATION.

NOTES:

FOR HDPE PIPE (4-INCH TO 12-INCH)


A. WHEN DIRECTED BY THE ENGINEER,THE CONCRETE WALL BLOCK SIZE MAY BE
2
1 ADJUSTED, BASED ON ACTUAL SOIL CLASSIFICATION AND PIPE DIAMETER.

CONCRETE WALL BLOCKING


B. FLEX RESTRAINTS MUST BE RATED AT 8,000 LBS OF FORCE OR HIGHER.

REBAR DETAIL: FRONT VIEW REBAR DETAIL: SIDE VIEW

REBAR NOTES:
12" 12" 14" 12" 12" A B C A. FOR 4 TO 10-INCH PIPE, PLACE ONE REBAR MAT AT
5" 5" LOCATION B ON THE REBAR DETAIL: SIDE VIEW.
B. FOR 12-INCH PIPE, PLACE TWO REBAR MATS - ONE AT
5" LOCATION A AND ONE AT LOCATION C ON THE REBAR
DETAIL: SIDE VIEW.
6"

6"

7"
4'
7"

6"

6"

5"

MINIMUM 3-INCH CLEAR


w
6' A. ENGINEER TO CONFIRM ADEQUATE SOIL PRESSURE
BEARING CAPACITY FOR THRUST BLOCK

REBAR DIAMETER SCHEDULE APPROX. DEAD END APPROX.


APPROXIMATE
THRUST AT 200 PSI WATER UNDISTURBED SOIL W CONCRETE VOLUME
PRESSURE SOIL BEARING PRESSURE MINIMUM
HDPE NOMINAL TOTAL TOTAL TOTAL
AREA (SQUARE WIDTH
REBAR SCHEDULE PIPE DIAMETER REBAR REBAR REBAR HDPE NOMINAL TOTAL BEARING (CUBIC (CUBIC
BAR SIZE FEET) (INCHES)
WEIGHT (LB) WEIGHT (LB) PIPE DIAMETER THRUST LOAD FEET) YARD)
NUMBER NUMBER (INCHES) LENGTH (FT)
ONE MAT TWO MATS (INCHES) (POUNDS) (LB/SQ FT)
LENGTH REQUIRED REQUIRED
TYPE
(INCHES) FOR ONE FOR TWO 4 2,130 15 142 10 20 0.74
4 #5 64 67 134
MAT MATS

A CITY OF CHARLOTTE DEPARTMENT


6 #5 64 67 134 6 4,616 15 308 10 20 0.74
VERTICAL 38 6 12

HORIZONTAL 62 6 12 8 #5 64 67 134 8 7,823 15 522 12 24 0.89

DIAGONAL 30 4 8 10 #5 64 67 134 10 12,153 15 810 12 24 0.89

HORIZONTAL 24 2 4 12 #5 64 67 134 12 17,094 15 1,140 14 28 1.04


2016-05-12
VERSION DATE
w NO. DESCRIPTION
MINIMUM NUMBER OF FLEX RESTRAINTS 1. HDPE PIPE
ELEVATION VIEW BY PIPE SIZE 2. ELECTROFUSED HDPE FLEX RESTRAINT OR WALL ANCHOR

HD5
HDPE NOMINAL PIPE NUMBER OF FLEX 3. CONCRETE WALL BLOCKING - F'C = MINIMUM 3,600 PSI.

VERSION NO.
SIZE (INCHES) RESTRAINTS 4. FLEX RESTRAINTS FOR HDPE PIPE. SEE TABLE FOR REQUIRED NUMBER OF FLEX

1.0
RESTRAINTS BY PIPE SIZE. COMPLY WITH MANUFACTURERS INSTRUCTIONS
14 4 FOR NUMBER OF FLEX RESTRAINTS IF GREATER THAN SHOWN IN TABLE.
16 6 5. AWG NO. 12 GAUGE SOLID COPPER TRACER WIRE WITH BLUE 30 MIL HDPE
INSULATION.
18 7
24 10

FOR HDPE PIPE (14-INCH TO 32-INCH)


32 17 NOTES:
A. WHEN DIRECTED BY THE ENGINEER,THE CONCRETE WALL BLOCK SIZE MAY BE
2
1 ADJUSTED, BASED ON ACTUAL SOIL CLASSIFICATION AND PIPE DIAMETER.

CONCRETE WALL BLOCKING


B. FLEX RESTRAINTS MUST BE RATED AT 8,000 LBS OF FORCE OR HIGHER.

REBAR DETAIL: FRONT VIEW REBAR DETAIL: SIDE VIEW

4" 12" 12" 12" 12" 16" 12" 12" 12" 12" 4" A C
REBAR NOTES:
4 A. FOR 14 TO 32-INCH PIPE, PLACE REBAR MATS BOTH AT
LOCATION A AND LOCATION C ON THE REBAR DETAIL:
4"
SIDE VIEW.
4"
4"
4"
5 1/2"
5 1/2"
5'
6"

5 1/2"
5 1/2"
4"
4"
4"
4"
MINIMUM 3-INCH CLEAR
5 A. ENGINEER TO CONFIRM ADEQUATE SOIL PRESSURE
10' w BEARING CAPACITY FOR THRUST BLOCK
4"
APPROX. DEAD END APPROX.
APPROXIMATE
THRUST AT 200 PSI WATER SOIL
UNDISTURBED W CONCRETE VOLUME
PRESSURE PRESSURE
REBAR SCHEDULE SOIL BEARING MINIMUM
REBAR DIAMETER SCHEDULE AREA (SQUARE WIDTH
HDPE NOMINAL TOTAL BEARING (CUBIC (CUBIC
NUMBER NUMBER FEET) (INCHES)
HDPE NOMINAL TOTAL TOTAL REBAR TOTAL REBAR PIPE DIAMETER THRUST LOAD FEET) YARD)
LENGTH REQUIRED REQUIRED
TYPE PIPE DIAMETER BAR SIZE LENGTH OF WEIGHT (LB) WEIGHT (LB) (INCHES) (POUNDS) (LB/SQ FT)
(INCHES) FOR ONE FOR TWO
(INCHES) REBAR (FT) ONE MAT TWO MATS
MAT MATS
14 #5 126 131 262 14 20,608 30 687 14 58 2.16
VERTICAL 52 8 16

A CITY OF CHARLOTTE DEPARTMENT


16 #5 126 131 262 16 26,915 30 897 16 67 2.47
VERTICAL 10 4 8 18 #5 126 131 262 18 34,073 30 1,136 16 67 2.47
HORIZONTAL 112 6 12 20 #5 126 131 262 20 42,063 30 1,402 18 75 2.78
24 #5 126 131 262 24 60,566 30 2,019 18 75 2.78
HORIZONTAL 48 4 8
30 #7 126 257 514 30 94,641 30 3,155 22 92 3.40
DIAGONAL 48 4 8 32 #7 126 257 514 32 107,678 30 3,589 22 92 3.40
2016-05-12
VERSION DATE
PLAN VIEW
3
8

HD6
NO. DESCRIPTION
6 1. HDPE PIPE

VERSION NO.
6 2. CONDUIT - 1 INCH PVC CONDUIT TO CONTAIN TRACER WIRE

1.0
12" 3. CONCRETE ENCASEMENT (F'C=3600 PSI MIN).
1
MIN. 4. STONE STABILIZATION MATERIAL AS REQUIRED
5. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER
TRACER WIRE WITH 30 MIL THICK, BLUE HDPE INSULATION AT THE
BOTTOM OF THE UTILITY SAND EMBEDMENT LAYER.

CONCRETE ENCASEMENT FOR HDPE PIPE


6. NEOPRENE FOAM PROTECTIVE WRAPPING, 41 - 34 INCH THICKNESS.
12" 7. HDPE EMBEDMENT MATERIAL - FINE AGGREGATE ACCORDING TO ASTM
MIN. C33 TABLE 1.
6" (TYP.) 8. #5 REBAR LONG (TYP)
24" 9. #4 REBAR TIES - MINIMUM 1.5-INCH CLEARANCE TO PIPE, MINIMUM
(TYP.) 3-INCH COVER

NOTES:
ELEVATION VIEW
A. CONCRETE ENCASEMENT SHALL ONLY BE INSTALLED WHERE SHOWN ON
8 APPROVED PLANS OR WITH PRIOR APPROVAL BY CLT WATER ENGINEER.
6 3 B. THIS RESTRICTION IS IN PLACE DUE TO THE INABILITY TO EASILY
6 MAINTAIN/REPAIR OR TAP A MAIN ENCASED IN CONCRETE.
C. ENGINEER TO CONFIRM TEMPERATURE FROM CONCRETE CURING AT SITE
1 12"
WILL BE LESS THAN THE HDPE VICAT SOFTENING TEMPERATURE OF 260°F.
MIN.
7
7
Concrete Volume per LF
Pipe Diameter
5 min W (in) min H (in)
5 6" MIN. (inches)
FT^3 / LF CY / LF

2 2 4 31 25 5.29 0.20
6 33 27 5.99 0.22
4 8 36 30 7.15 0.26
10 38 32 7.90 0.29
12 40 34 8.66 0.32
14 42 36 9.43 0.35
SECTION VIEW
16 44 38 10.21 0.38
18 46 40 11.01 0.41
W
(MIN) 20 48 42 11.82 0.44
1 22 50 44 12.64 0.47
24 52 46 13.47 0.50
26 54 48 14.31 0.53
H
3 (MIN) 28 56 50 15.17 0.56
30 58 52 16.04 0.59
4
32 60 54 16.91 0.63

A CITY OF CHARLOTTE DEPARTMENT


9
8
5 2
2016-05-12
VERSION DATE
NO. DESCRIPTION
1. HDPE WATER MAIN
2. HDPE PIPE

HD7
3. ELECTROFUSION COUPLING OR RESTRAINED MJ ADAPTER WITH
STAINLESS STEEL STIFFENER AND ACCESSORY KIT. SEE STANDARD

VERSION NO.
DETAIL HD1 FOR TRANSITION DETAIL.

1.0
3' MIN. 6' PREFERRED. 4. CONCRETE BLOCK - 8-INCH BY 16-INCH SOLID CONCRETE BLOCK
5. RESILIENT SEAT GATE VALVE
10 6. FOR CONNECTION TO NEW CONSTRUCTION SEE STANDARD DETAIL
HD8. FOR CONNECTION TO EXISTING MAIN SEE STANDARD DETAIL HD7.
7. VALVE BOX ASSEMBLY - SEE CLT WATER STANDARD DETAIL.
8. CONCRETE HYDRANT COLLAR. CAST IN PLACE. 3-FEET DIAMETER BY
8-INCH THICK.
9. MINIMUM 9 CUBIC FEET OF #57 OR #67 WASHED STONE
PROPORTIONALLY AROUND BASE. DO NOT COVER WEEP HOLE.
18" ± 2" 10. HYDRANT PER CLT WATER SPECIFICATIONS
11. SEE CLT WATER TRACER WIRE STANDARD DETAILS FOR TERMINATION

HYDRANT CONNECTION
METHOD.
12. AWG. NO. 12 GAUGE SOLID COPPER TRACER WIRE WITH BLUE 30 MIL

FOR HDPE PIPE


8" HDPE INSULATION

8
11

7 12
NOTES:
A. HYDRANT LOCATION: ON ROADS WITH CURB AND GUTTER, USE EXISTING
CLT WATER STANDARD DETAIL FOR FIRE HYDRANTS IN ALL CASES UNLESS
6 5 9 6" MIN.
OTHERWISE NOTED BY ENGINEER.
B. BURIAL TO BE MINIMUM 3-FOOT 6-INCHES UNLESS OTHERWISE DIRECTED
BY THE ENGINEER.
C. EXTENSIONS REQUIRED AS DETERMINED BY THE ENGINEER,HOWEVER NO
MORE THAN ONE HYDRANT EXTENSION IS ALLOWED. IF EXTENSION IS
USED, NO NOT CAST HYDRANT COLLAR ON EXTENSION JOINT.
D. ON ROADS WITHOUT SIDE DITCH OR CURB, HYDRANT SHALL BE LOCATED 1
1 3 12 4 2 12 3 4 FOOT INSIDE THE ROAD RIGHT OF WAY
E. ON ROADS WITH SIDE DITCH, FIRE HYDRANT SHALL BE LOCATED A
MINIMUM OF 4-FEET BACK OF SIDE DITCH.

A CITY OF CHARLOTTE DEPARTMENT


NO. DESCRIPTION

2016-05-12
VERSION DATE
1. ELECTROFUSION TAPPING SADDLE OR STAINLESS STEEL
TAPPING SLEEVE WITH OUTLET SEAL GASKET.
2. FLxMJ TAPPING VALVE. REFER TO STANDARD DETAIL HD10 AND

HD8
HD11.
3. HDPE PIPE

VERSION NO.

1.0
7 7 4. STANDARD VALVE BOX ASSEMBLY
5. AWG NO. 12 GAUGE SOLID COPPER TRACER WIRE WITH BLUE
30 MIL HDPE INSULATION.
6. CONCRETE THRUST BLOCK (SEE TABLE FOR SIZING)
7. TRENCH LIMITS
8. EXISTING HDPE WATER MAIN
9. UNDISTURBED NATIVE SOIL
2 1 2 10. HDPE PIPE BUTT FUSION JOINT

FOR HDPE PIPE (4-INCH TO 32-INCH)


6 11 3
11. BUTT FUSED BRANCH SADDLE
10 3

TAPPING SLEEVE AND VALVE


NOTES:
A. BRANCH LARGER THAN THE EXISTING MAIN IS NOT ALLOWED.
B. FOR EXISTING HDPE MAIN, USE ELECTROFUSION TAPPING SADDLE
9 9 OR BUTT FUSED BRANCH SADDLE.

7 7 THRUST BLOCK TABLE


8 6 8

TYPE OF FITTING TEE OR DEAD END


TOTAL REQUIRED BEARING
TAP SIZE (INCHES) AREA (FT²)

4 1.3
6 2.9
8 5.1
10 7.9
12 11.4
14 15.7
4
16 20.1
18 25.8
20 31.4
24 45.3
30 70.7
32 80.4

8 2 THRUST BLOCK NOTES:


A. THRUST BLOCKS TO BE 3,600 PSI CONCRETE.
6 B. THRUST BLOCKS TO BE POURED AGAINST UNDISTURBED SOIL.
C. JOINTS TO BE KEPT FREE OF CONCRETE. ALLOW WORKING ROOM

A CITY OF CHARLOTTE DEPARTMENT


AROUND NUTS AND BOLTS. WRAP FITTING WITH 2 LAYERS HDPE FILM
(HDCLPE PER AWWA C-105). EACH LAYER MINIMUM 4 MILS THICK.
D. AREAS GIVEN ARE FOR DR 9 PIPE AT TEST PRESSURE OF 200 PSI IN
9 SOIL WITH 2,000 PSI BEARING CAPACITY. CHANGES SUBJECT TO FIELD
5
CONDITIONS AND APPROVAL OF THE ENGINEER.
E. TAPPING SLEEVES SHALL HAVE THRUST BLOCKS SIZED BASED ON
TAP SIZE.
2016-05-12
VERSION DATE
NO. DESCRIPTION
1. BUTT FUSED BRANCH SADDLE FITTING
2. HDPE PIPE BUTT FUSION JOINT

HD9
6 6
3. FULL BODY STAINLESS STEEL MJ BRANCH SLEEVE WITH

VERSION NO.
7 OUTLET SEAL GASKET

1.0
4. CONCRETE THRUST BLOCK (SEE TABLE FOR SIZING)
5. UNDISTURBED NATIVE SOIL
6. TRENCH LIMITS
2 7. EXISTING HDPE WATER MAIN
4 1 4 3 8. PROPOSED GROUND SURFACE
2 2
NOTES:

CUT-IN TEE FOR EXISTING HDPE PIPE


A. BRANCH LARGER THAN MAIN IS NOT ALLOWED.
B. IF COMPLETE SHUT OFF IS POSSIBLE ON EXISTING HDPE MAIN, USE
BUTT FUSION MOLDED TEE. IF SHUT OFF IS NOT POSSIBLE,
CONFIRM WITH CHARLOTTE WATER INSPECTOR THAT MECHANICAL
JOINT TEE OPTION IS ALLOWED.

(4-INCH TO 32-INCH)
6 6 THRUST BLOCK TABLE
7
5 5 TYPE OF FITTING TEE OR DEAD END
2

TYPICAL PLAN VIEW

TOTAL REQUIRED BEARING


MAIN SIZE (INCHES) AREA (FT²)

4 2
6 2.5
8 4.5
8
10 7
12 10
14 14
16 18
18 22
20 27

THRUST BLOCK NOTES:


A. THRUST BLOCKS TO BE 3,600 PSI CONCRETE.
B. THRUST BLOCKS TO BE POURED AGAINST UNDISTURBED SOIL.
C. JOINTS TO BE KEPT FREE OF CONCRETE. ALLOW WORKING ROOM
4 AROUND NUTS AND BOLTS. WRAP FITTING WITH 2 LAYERS HDPE
FILE (HDCLPE PER AWWA C-105). EACH LAYER MINIMUM 4 MILS
THICK.
D. AREAS GIVEN ARE FOR DR 11 PIPE AT TEST PRESSURE OF 200 PSI

A CITY OF CHARLOTTE DEPARTMENT


IN SOIL WITH 2,000 PSI BEARING CAPACITY. CHANGES SUBJECT
TO FIELD CONDITIONS AND APPROVAL OF THE ENGINEER.
E. TAPPING SLEEVES SHALL HAVE THRUST BLOCKS SIZED THE SAME
AS TEES.
2016-05-12
NO. DESCRIPTION

VERSION DATE
1. CONCRETE WALL BLOCKING (REFER TO STANDARD DETAIL HD4)
2. TRANSITION COUPLING IF REQUIRED (REFER TO STANDARD DETAIL

HD10
HD1)
3. TO PREVENT THE OVER-BENDING OF HDPE, A MIN. 1.50 TIMES THE

VERSION NO.
MANUFACTURER SPECIFIED BEND RADIUS IS ALLOWED. IF BEND

1.0
RADIUS REQUIREMENTS CANNOT BE MET, THEN BUTT FUSED LONG
RADIUS BEND FITTINGS ARE ALLOWED.
4. NEW HDPE PIPE - MINIMUM LENGTH IS 10 FEET PLUS DIAMETER OF
STORM PIPE OF STRAIGHT RUN OF PIPE AND CENTERED UNDER
STORM DRAIN PIPE.
7 7
6 5. TRENCH LIMITS
6. STORM DRAIN (OR PROPOSED CONFLICT)
7. ROD BEND TO WALL BLOCK IF TRANSITION IS NOT SELF-RESTRAINED.

LOWERING OF 6-INCH TO 12-INCH


ROD MATERIAL MUST BE CORROSION-RESISTANT AND COVERED IN
CORROSION INHIBITING SUBSTANCE.

WATER MAIN USING HDPE


8. TIE ROD - THE CONNECTING TIE RODS THAT JOIN THE TWO RINGS
5' MIN 5' MIN
2 2 SHALL BE MADE OF LOW ALLOY STEEL THAT CONFORMS TO
18" MIN. ANSI/AWWA C111/A21.11.
9. STEEL CASING PIPE - REQUIRED IF STORM PIPE IS 72-INCHES
1 1 DIAMETER OR LARGER OR IF REQUIRED IF STORM CONFLICT IS A BOX
CULVERT. REFER TO STEEL CASING FOR HDPE PIPE STANDARD
3 3 DETAIL.
9 4
NOTES
A. ALL HDPE PIPE SHALL HAVE BUTT FUSED JOINT OR ELECTROFUSED
FITTINGS.
B. EMBEDMENT OF WATER MAIN SHALL BE PER STANDARD DETAIL HD3.
C. IF THE EXISTING PIPE IS HDPE, CONTRACTOR MAY NOT DEFLECT
PIPE AS-IS TO ACHIEVE LOWERING. HDPE FITTINGS OR NEW HDPE
6 PIPE MUST BE INSTALLED TO PROVIDE THE EXTRA PIPE LENGTH
NEEDED TO ACCOMMODATE A WATER MAIN LOWERING.
D. LOWERED PIPE MUST BE NEW MATERIAL. REUSE OF EXISTING PIPE
2 IS NOT ALLOWED.
5 7 7

5
BEND RADIUS TABLE TIE ROD TABLE
MAIN SIZE MINIMUM BEND MAIN SIZE TIE ROD SIZE
(INCHES) RADIUS (FEET) (INCHES) (COUNT - INCH)
2
1 1 4 90 4 4 - 34 X 13
6 133 6 6 - 43 X 13
3 3
8 173 8 6 - 34 X 13
4 9
10 215 10 8 - 34 X 18
NOTES TO DESIGNER
A. ENGINEER SHALL CONFIRM WATER LINE SEPARATION IS IN 12 255 12 8 - 34 X 18
ACCORDANCE WITH STATE REGULATIONS. MODIFY DETAIL 16 320

A CITY OF CHARLOTTE DEPARTMENT


16 10 - 34 X 18
ACCORDINGLY.
B. ALL BLUE LEADERS AND DIMENSIONS SHOULD BE FILLED IN 20 400 20 12 - 34 X 18
ACCORDING TO PROJECT PARAMETERS AND PLACED ON A 24 480 24 14 - 34 X 18
NON-COLOR PLOTTING LAYER.
C. THIS DETAIL SHOULD BE MODIFIED FOR EACH SPECIFIC 30 600 30 16 - 1 X 18
APPLICATION. IF THERE ARE MULTIPLE WATER LINE LOWERINGS 32 640 32 20 - 1 X 18
REQUIRED, MULTIPLE DETAILS SHOULD BE PREPARED.
2016-05-12
VERSION DATE
NO. DESCRIPTION
1. HDPE WATER MAIN
2. BUTT FUSED JOINT OR RESTRAINED MJ ADAPTER WITH STAINLESS

HD11
STEEL STIFFENER AND ACCESSORY KIT. SEE STANDARD DETAIL HD1
FOR TRANSITION DETAIL.

VERSION NO.
3. GATE VALVE.

1.0
4. VALVE BOX ASSEMBLY. SEE STANDARD DETAIL.
5. TRACER WIRE TERMINATION.
6. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER
TRACER WIRE WITH 30 MIL THICK BLUE HDPE INSULATION
7. CONCRETE BEARING BLOCK FOR 10-INCH AND LARGER GATE VALVES.
POLYETHYLENE WRAP BARRIER SHALL BE PRESENT BETWEEN BEARING
BLOCK AND VALVE. WRAP SHALL BE TWO LAYERS OF 4 MIL THICK
HDCLPE.

GATE VALVE FOR HDPE PIPE


5 NOTES:
A. MJ ADAPTER KIT SHALL INCLUDE BOLTS AND NUTS, GRADE 3 OR HIGHER

(3-INCH TO 12-INCH)
AND LONG ENOUGH TO ACCOMMODATE THE ADDED LENGTH OF HDPE
FITTING TO ATTACH TO VALVES.
B. CHARLOTTE WATER ALLOWS THE INSTALLATION OF DIFFERENT PIPE
MATERIALS ON EITHER SIDE OF THE GATE VALVE. INSTALL TRANSITIONS
PER STANDARD DETAIL HD1 FOR HDPE.
C. IF VALVE OPERATING NUT IS MORE THAN 3 FEET BELOW FINISHED GRADE,
4 PROVIDE EXTENSION STEM WITH STANDARD 2-INCH SQUARE OPERATING
NUT IN TOP SECTION OF VALVE BOX. SEE STANDARD DETAIL.

6
1 3 1

2
2
7

A CITY OF CHARLOTTE DEPARTMENT


PROFILE VIEW SIDE VIEW

2016-05-12
VERSION DATE
NO. DESCRIPTION
1 1. FRAME AND COVER ASSEMBLY. SEE STANDARD DETAIL.
2. TRACER WIRE TERMINATION.

HD12
3. VALVE BOX ASSEMBLY. SEE CLT WATER STANDARD DETAIL.
3 4. GATE VALVE.

VERSION NO.
5. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER

1.0
2
5 6
TRACER WIRE WITH 30 MIL THICK BLUE HDPE INSULATION
6. CONCRETE BEARING BLOCK FOR 10-INCH AND LARGER GATE VALVES.
1 POLYETHYLENE WRAP BARRIER SHALL BE PRESENT BETWEEN BEARING
BLOCK AND VALVE. WRAP SHALL BE TWO LAYERS OF 4 MIL THICK

HORIZONTAL INSTALLATION OF GATE VALVES


3
HDCLPE.
7. CONE BEARING BLOCKS.
8. RESTRAINED MJ ADAPTER WITH STAINLESS STEEL STIFFENER AND

FOR HDPE PIPE (16-INCH TO 32-INCH)


4 ACCESSORY KIT.
9. THRUST BLOCK. REFER TO STANDARD DETAIL.

NOTES:
4
5 A. CONNECT VALVE TO HDPE LINE WITH RESTRAINED MJ ADAPTER WITH
STAINLESS STEEL STIFFENER AND ACCESSORY KIT. SEE STANDARD DETAIL
6 6
HD1 FOR TRANSITION DETAIL.
SIDE B. MJ ADAPTER KIT SHALL INCLUDE BOLTS AND NUTS, GRADE 3 OR HIGHER
6 AND LONG ENOUGH TO ACCOMMODATE THE ADDED LENGTH OF HDPE
FITTING TO ATTACH TO VALVES.
C. CHARLOTTE WATER ALLOWS THE INSTALLATION OF DIFFERENT PIPE
MATERIALS ON EITHER SIDE OF THE GATE VALVE. INSTALL TRANSITIONS
PER STANDARD DETAIL HD1 FOR HDPE.
PLAN VIEW C. IF VALVE OPERATING NUT IS MORE THAN 3 FEET BELOW FINISHED GRADE,
PROVIDE EXTENSION STEM WITH STANDARD 2-INCH SQUARE OPERATING
NUT IN TOP SECTION OF VALVE BOX. SEE STANDARD DETAIL.
D. REFER TO STANDARD DETAIL FOR MANHOLE COVER DETAIL.
9 ELEVATIONS
METHOD A METHOD B

1 FINISHED
FINISHED GRADE
8 MAX. 20' GRADE 4" MIN.
2 18"
18"
MIN. 12'
2"
2"
4" MIN.
3 4
PLAN: PRECAST CONCRETE PAD SECTION
REFER TO STANDARD DETAIL
10"

4'-6" 3"

MAX. 20'
8 2'-3"
MIN. 12' 6"
TYP.
4'-6"

A CITY OF CHARLOTTE DEPARTMENT


2'-3"
3"
TYP.
9
2016-05-12
VERSION DATE
NO. DESCRIPTION
ELEVATIONS PLAN: PRECAST CONCRETE PAD SECTION 1. FRAME AND COVER ASSEMBLY. SEE STANDARD DETAIL.
REFER TO STANDARD DETAIL 2. TRACER WIRE TERMINATION.

HD13
METHOD A - IN SHOULDER 10" 3. VALVE BOX ASSEMBLY. SEE STANDARD DETAIL.
4. GATE VALVE - VERTICALLY ORIENTED

VERSION NO.
4'-6" 3"
5. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER

1.0
13 TRACER WIRE WITH 30 MIL THICK BLUE HDPE INSULATION
2 2'-3" 6. BEARING BAR FOR VALVE BOX. POLYETHYLENE WRAP BARRIER SHALL BE
4" MIN. 6"
18" PRESENT BETWEEN BEARING BLOCK AND VALVE.
TYP.
4'-6" 7. BEARING BLOCK FOR VALVE.
2 8. PRECAST CONCRETE BEAM (REINFORCED)

VERTICAL INSTALLATION OF GATE VALVES


2"
2'-3" 9. PRECAST CONCRETE PAD (REINFORCED). SEE STANDARD DETAIL.
3 6 3"
10. 12 INCH (MIN.) DIP OR C900 PVC DR18 RISER PIPE 20 INCH MAXIMUM

FOR HDPE PIPE (16-INCH TO 32-INCH)


TYP.
11. RESTRAINED MJ ADAPTER WITH STAINLESS STEEL STIFFENER AND
ACCESSORY KIT. SEE STANDARD DETAIL HD1 FOR TRANSITION DETAIL.
12. EXTENSION STEM ASSEMBLY. REFER TO STANDARD DETAIL.
13. FINISHED GRADE
METHOD B - IN PAVEMENT 14. RESTRAINED MJ ADAPTER WITH STAINLESS STEEL STIFFENER AND
ACCESSORY KIT.
15. THRUST BLOCK. REFER TO STANDARD DETAIL.
13
2 NOTES:
18" A. CONNECT VALVE TO HDPE LINE WITH RESTRAINED MJ ADAPTER WITH
STAINLESS STEEL STIFFENER AND ACCESSORY KIT. SEE STANDARD DETAIL
HD1 FOR TRANSITION DETAIL.
2"
B. CHARLOTTE WATER ALLOWS THE INSTALLATION OF DIFFERENT PIPE
4" MIN.
3 6 MATERIALS ON EITHER SIDE OF THE GATE VALVE. INSTALL TRANSITIONS
PER STANDARD DETAIL HD1 FOR HDPE.
C. IF VALVE OPERATING NUT IS MORE THAN 3 FEET BELOW FINISHED GRADE,
PROVIDE EXTENSION STEM WITH STANDARD 2-INCH SQUARE OPERATING
NUT IN TOP SECTION OF VALVE BOX. SEE STANDARD DETAIL.
D. REFER TO STANDARD DETAIL FOR MANHOLE COVER DETAIL.
PROFILE VIEW SIDE VIEW

PLAN VIEW
12
3

6 6
MAX. 20' MAX. 20'
MIN. 12' MIN. 12' 15
15

A CITY OF CHARLOTTE DEPARTMENT


14 14

7 7
2016-05-12
VERSION DATE
ELEVATIONS PRECAST CONCRETE PAD PLAN VIEW NO. DESCRIPTION
REFER TO STANDARD DETAIL REFER TO STANDARD DETAIL 1. PRECAST CONCRETE BEAM (REINFORCED)
2. PRECAST CONCRETE PAD (REINFORCED). SEE STANDARD DETAIL.

HD14
3. 12 INCH (MIN.) DIP OR C900 PVC DR18 RISER PIPE 20 INCH MAXIMUM
4. RESTRAINED MJ ADAPTER WITH STAINLESS STEEL STIFFENER AND

VERSION NO.
SECTION ACCESSORY KIT. SEE STANDARD DETAIL HD1 FOR TRANSITION DETAIL.

1.0
METHOD A 5. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER TRACER
10"
WIRE WITH 30 MIL THICK BLUE HDPE INSULATION
3" 6. EXTENSION STEM ASSEMBLY. REFER TO STANDARD DETAIL.
FINISHED 7. WASHED #57 OR #67 STONE-MINIMUM 6 FEET ON EACH SIDE OF VALVE.
GRADE 4" MIN. 8. HDPE WATER MAIN.
18"
2 9. CONCRETE BEARING BLOCK FOR 10-INCH AND LARGER GATE VALVES.
POLYETHYLENE WRAP BARRIER SHALL BE PRESENT BETWEEN BEARING

BUTTERFLY VALVE FOR HDPE PIPE


2" BLOCK AND VALVE. WRAP SHALL BE TWO LAYERS OF 4 MIL THICK HDCLPE.
10. MJ X MJ BUTTERFLY VALVE.
3 6
11. DIPS MJ ADAPTER
METHOD B 2 12. DIP SPOOL PIECE WITH RESTRAINT HARNESS.

(16-INCH TO 32-INCH)
NOTES:
4'-6" A. MJ ADAPTER KIT SHALL INCLUDE BOLTS AND NUTS, GRADE 3 OR HIGHER.
B. PROVIDE REDUCERS PRIOR TO MJ ADAPTER IN NEXT LOWER PIPE SIZE IF
2'-3" IPS PIPE SIZE IS NOT COMPATIBLE WITH AVAILABLE DIPS VALVE SIZES.
18" 6" CHARLOTTE WATER DOES NOT TYPICALLY USE 18-INCH VALVES.
2 TYP.
C. CHARLOTTE WATER ALLOWS THE INSTALLATION OF DIFFERENT PIPE
4'-6"
2" MATERIALS ON EITHER SIDE OF THE BUTTERFLY VALVE. INSTALL
4" MIN. 2'-3" TRANSITIONS PER STANDARD DETAIL HD1 FOR HDPE.
3 6 3" C. IF VALVE OPERATING NUT IS MORE THAN 3 FEET BELOW FINISHED GRADE,
TYP. 2 PROVIDE EXTENSION STEM WITH STANDARD 2-INCH SQUARE OPERATING
NUT IN TOP SECTION OF VALVE BOX. SEE STANDARD DETAIL.
D. REFER TO STANDARD DETAIL FOR MANHOLE COVER DETAIL.

PLAN VIEW

VALVE SIZE TABLE


SIDE VIEW DR 9 IPS
MJ ADAPTER VALVE SIZE
11 HDPE SIZE IPS REDUCER
(IPS X DIPS) (INCH)
(INCH)
1 3 8 N/A 8x8 8
12 6
5 6
2
4 3 10 N/A 10 x 10 10
1 10
10 2" MIN. 12 N/A 12 x 12 12
7
7
3
4
14 N/A 14 x 14 14

12 1' MIN. 16 N/A 16 x 16 16


1 1' MIN. 18 18 x 16 16 x 16 16
11
6" MIN. 20 N/A 20 x 20 20
9

A CITY OF CHARLOTTE DEPARTMENT


9 22 22 x 20 20 x 20 20
24 N/A 24 x 24 24
8 26 26 x 24 24 x 24 24
30 N/A 30 x 30 30
32 32 x 30 30 x 30 30
6"-16" MAIN 20"-32" MAIN

2016-05-12
VERSION DATE
WHEN IN
PAVEMENT 7

HD15
2' MIN. 3'-0"

VERSION NO.
14 14 9
2 3

1.0
1 3 1

6" MIN. 6

14
14
11 2 3
5 5 5
10
3' MIN.
13 13
15 7
9 9
3

AIR RELEASE VALVES


11
12 8
5

FOR HDPE PIPE


4
2 7
6 8
8

1 3 1
1
10 3

6
ITEM LIST FOR 1-INCH AIR RELEASE ITEM LIST FOR 2-INCH AIR RELEASE
NO. DESCRIPTION NO. DESCRIPTION NO. DESCRIPTION NO. DESCRIPTION 5 4 5
1. HDPE WATER MAIN 1. HDPE WATER MAIN
9. 1-INCH RED BRASS NIPPLE LENGTH AS REQUIRED
2. 1-INCH HDPE TAPPING - SCH 40 - (MNPT X MNPT),
2. 2-INCH HDPE TAPPING 10. 2-INCH DUCTILE IRON
7
TEE BY ELECTROFUSION LENGTH AS REQUIRED TEE BY ELECTROFUSION (FUSION BONDED EPOXY
ONLY 10.1-INCH DUCTILE IRON ONLY COATED) THREADED
3. HDPE BUTT FUSION JOINT 3. HDPE BUTT FUSION JOINT
(FUSION BONDED EPOXY COUPLING (FNPT)
4. 1-INCH SDR-9 HDPE COATED) THREADED 4. 2-INCH SDR-9 HDPE 11. 2-INCH NPT CAP (HAND
TUBING (CTS) COUPLING (FNPT) TUBING (CTS) TIGHT)
5. 1-INCH HDPE PLAIN END x 11.1-INCH NPT CAP (HAND5. 2-INCH HDPE PLAIN END x 12. HDPE EMBEDMENT ITEM LIST FOR 6-INCH AIR RELEASE
STEEL PLAIN END TIGHT) STEEL THREADED MATERIAL NO. DESCRIPTION
WELD-ON TRANSITION 12. HDPE EMBEDMENT WELD-ON TRANSITION 13. TRENCH LIMITS 1. 6-INCH GATE VALVE. SEE STANDARD DETAIL.
FITTING FOR WATER MATERIAL FITTING FOR WATER 14. VALVE BOX ASSEMBLY - 2. FIRE HYDRANT ASSEMBLY PER STANDARD DETAIL.
6. 1-INCH BRASS AWWA 13. TRENCH LIMITS 6. 2-INCH THREADED GATE SEE STANDARD DETAIL 3. 6-INCH HDPE PIPE.
CURB STOP BALL VALVE 14. VALVE BOX ASSEMBLY - VALVE (FNPT X FNPT) 15. TRACER WIRE - 4. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID
(CTS) SEE STANDARD DETAIL7. 2-INCH RED BRASS NIPPLE CONTINUOUS AWG NO. 12 COPPER TRACER WIRE WITH 30 MIL THICK BLUE HDPE INSULATION.
7. 1-INCH RED BRASS NIPPLE 15. TRACER WIRE - - SCH 40 - (MNPT X MNPT), GAUGE SOLID COPPER 5. RESTRAINED MJ ADAPTER WITH STAINLESS STEEL STIFFENER AND ACCESSORY KIT. SEE
- SCH 40 - (MNPT X MNPT), CONTINUOUS AWG NO. 12 MINIMUM 30-INCH LONG TRACER WIRE WITH 30 MIL STANDARD DETAIL FOR TRANSITION DETAIL.
MINIMUM 30-INCH LONG GAUGE SOLID COPPER 8. 2-INCH RED BRASS 90° THICK BLUE HDPE 6. HDPE BUTT FUSION TEE
8. 1-INCH RED BRASS 90° TRACER WIRE WITH 30 MIL
BEND (FNPT X FNPT) INSULATION 7. HDPE WATER MAIN
BEND (FNPT X FNPT) THICK BLUE HDPE 9. 2-INCH RED BRASS NIPPLE 8. VALVE BOX ASSEMBLY. SEE STANDARD DETAIL.
INSULATION - SCH 40 - (MNPT X MNPT), 9. 24-INCH DIAMETER REINFORCED CONCRETE PAD.
10. #57 OR #68 WASHED STONE-ENCASEMENT
NOTES: 11. CONCRETE HYDRANT COLLAR. CAST IN PLACE. 3-FEET DIAMETER BY 8-INCH THICK.
A. AIR RELEASE VALVE ASSEMBLIES FOR MAINS 12-INCHES AND SMALLER SHALL BE 1-INCH IN SIZE.
B. AIR RELEASE VALVE ASSEMBLIES FOR 16-INCH MAINS SHALL BE 2-INCHES IN SIZE.
NOTES:
C. AIR RELEASE VALVE ASSEMBLIES FOR 20-INCH AND LARGER MAINS SHALL BE 6-INCH.

A CITY OF CHARLOTTE DEPARTMENT


A. ALL PIPE, FITTINGS, ETC. SHALL BE RESTRAINED JOINT OR MJ WITH WEDGE ACTION
D. 2-INCH BALL VALVES MAY NOT BE SUBSTITUTED FOR GATE VALVES.
RESTRAINT. BUTT FUSED AND ELECTROFUSED HDPE IS FULLY RESTRAINED.
B. ALL HARDWARE (BOLT/WASHER/NUT) SHALL BE TYPE 304 STAINLESS STEEL WITH ANTI-SEIZE
COMPOUND
C. SEE CONSTRUCTION PLANS FOR EXACT LOCATIONS OF VALVES AND FIRE HYDRANT.
D. HYDRANT EXTENSIONS SHALL BE LIMITED TO 1 EACH PER FIRE HYDRANT.
NO. DESCRIPTION 6"-32" MAIN 22"-32" MAIN AT CREEK CROSSINGS

2016-05-12
WHEN IN

VERSION DATE
1. NPT CAP (HAND TIGHT) PAVEMENT
2. VALVE BOX (TOP SECTION) - 3'-0" 2' MIN. END PLAN
PLAN 7
ASSEMBLY

HD16
7
3. TRENCH LIMITS 11 2 11 2 5
4. HDPE EMBEDMENT MATERIAL

VERSION NO.
MAY BE ROTATED 90°

1.0
5. HDPE TRANSITION RISER 6" MIN. 15
FOR HORIZONTAL
6. 2-INCH GATE VALVE
10 10 ALIGNMENT
7. HDPE TAPPING TEE BY 9 6
ELECTROFUSION ONLY 1 3
10 15
8. HDPE WATER MAIN 1
9. 2-INCH SDR-9 HDPE PIPE (IPS) 3' MIN.
3 3 14 14
10. VALVE BOX ASSEMBLY. SEE 6
STANDARD DETAIL. 2 1
11. HDPE BUTT FUSION JOINT 12 5
5 15 5
12. TRACER WIRE-CONTINUOUS
AWG NO. 12 GAUGE SOLID END ELEVATION
5 4 ELEVATION

BLOW OFF ASSEMBLIES


COPPER TRACER WIRE WITH
16
30 MIL THICK BLUE HDPE 2 IDENTICAL
INSULATION. 12 8 9 12

FOR HDPE PIPE


13 12

8
5 7 30"
11 11 11 3'-6"
9 4 MIN. 10
11 6
11 8
4 56.25° 7

1
5 3 1
30" CONCRETE PAD DETAIL
6
17
4" 6"
CHARLOTTE
15 14 17
2" WATER 5 4 5 14

30"
3" 6" 6" 6" 6" 3" ACCESS NO. DESCRIPTION
1. 12-INCH GATE VALVE. SEE STANDARD DETAIL.
2. FIRE HYDRANT ASSEMBLY PER STANDARD DETAIL.
3. 6-INCH HDPE PIPE.
4. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER TRACER WIRE WITH 30 MIL
THICK BLUE HDPE INSULATION.
5. RESTRAINED MJ ADAPTER WITH STAINLESS STEEL STIFFENER AND ACCESSORY KIT. SEE
STANDARD DETAIL HD1 FOR TRANSITION DETAIL.
6. HDPE TEE
7. HDPE WATER MAIN
NOTES:
8. VALVE BOX ASSEMBLY. SEE STANDARD DETAIL.
A. ALL PIPE, FITTINGS, ETC. SHALL BE RESTRAINED JOINT OR MJ WITH WEDGE ACTION RESTRAINT. BUTT
9. 30"x 30"x6" REINFORCED CONCRETE VALVE PAD WITH #4 REBAR AT 6 INCH O.C. EACH WAY. SEE
FUSED AND ELECTROFUSED HDPE IS FULLY RESTRAINED.
CONCRETE PAD DETAIL ON THIS SHEET.
B. CLT WATER DISTRIBUTION VALVES OPEN RIGHT (CLOCKWISE).
10. 6-INCH GATE VALVE. SEE STANDARD DETAIL HD10.
C. ALL HARDWARE (BOLT/WASHER/NUT) SHALL BE TYPE 304 STAINLESS STEEL WITH ANTI-SEIZE
11. #57 OR #68 WASHED STONE-ENCASEMENT TO 6" ABOVE BLIND FLANGE.
COMPOUND
12. 24 INCH DIAMETER REINFORCED CONCRETE PAD.
D. SEE CONSTRUCTION PLANS FOR EXACT LOCATIONS OF VALVES, CLT WATER ACCESS POINT, AND FIRE
13. 12" DUCTILE IRON BLIND FLANGE, HDPE FLANGE ADAPTER, AND DUCTILE IRON BACK-UP RING.
HYDRANT.
14. HDPE FITTING BUTT FUSION JOINT.
E. HYDRANT EXTENSIONS SHALL BE LIMITED TO 1 EACH PER FIRE HYDRANT.

A CITY OF CHARLOTTE DEPARTMENT


15. 12-INCH HDPE PIPE.
16. 72-INCH 3-RAIL MARKER POST, BLUE IN COLOR TO SIGNIFY WATER (RHINO OR APPROVED
EQUAL).
17. HDPE EMBEDMENT MATERIAL
NO. DESCRIPTION

2016-05-12
VERSION DATE
1. END OF LINE VALVE-BUTTERFLY OR GATE VALVE
2. HDPE WATER MAIN
3. FLEX RESTRAINTS FOR HDPE PIPE. SEE STANDARD DETAIL

HD17
HD4.
4. CONCRETE WALL BLOCKING - F'C = MINIMUM 3,600 PSI. SEE

VERSION NO.

1.0
STANDARD DETAIL HD4.
5. BUTT FUSED HDPE END CAP
6. MJ ADAPTER WITH STAINLESS STEEL STIFFENER AND 5' 12'
ACCESSORY KIT OR BUTT FUSION JOINT AS APPROPRIATE TO
VALVE. 4

DEAD END WALL BLOCKING FOR HDPE PIPE


7. 2 INCH HDPE PIPE
8. 2 INCH HDPE 90° BEND
3' MIN.
9. 2 INCH HDPE NIPPLE - LENGTH AS REQUIRED.
10. 2-INCH TAPPING TEE OR 4-INCH SADDLE.
6 1 6 3
11. VALVE BOX ASSEMBLY. SEE STANDARD DETAILS HD10, HD11,
HD12, AND HD17.
12. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID
COPPER TRACER WIRE WITH 30 MIL THICK BLUE HDPE 4'
INSULATION. MAX.
13. 1 INCH SCH 40 PVC ELECTRICAL CONDUIT. LENGTH AS TRENCH
5 WIDTH
REQUIRED. 17
14. UNDISTURBED SOIL
15. 5 INCH CAST IRON SOIL PIPE, L=15" OR VALVE BOX BOTTOM 2 7
SECTION.
16. TRENCH LIMITS 17 11
17. CONTROL VALVE 3' MIN. 14
18. CONCRETE BEARING BLOCK

11
11 11
11
5" MIN.
9" MAX.
15
15

14 9
6 4
1 6 1.5 TIMES
3 PIPE DIAMETER
17

8
5
7
1' MIN.
2 18 13 17
18 10 12
14 10

OUTLET SIZE TABLE

A CITY OF CHARLOTTE DEPARTMENT


NOTES: A. ENGINEER TO CONFIRM ADEQUATE SOIL PRESSURE BEARING
A. WHEN DIRECTED BY THE ENGINEER,THE CONCRETE WALL MAIN DIAMETER OUTLET NOMINAL CAPACITY FOR THRUST BLOCK
BLOCK SIZE MAY BE ADJUSTED, BASED ON ACTUAL SOIL CONTROL VALVE
(INCH) DIAMETER (INCH) B. DESIGNATE IN PLANS THE TYPE OF VALVE FOR ITEM 11.
CLASSIFICATION AND PIPE DIAMETER. C. FOR 2-INCH TO 12-INCH MAIN, USE GATE VALVE. FOR 14-INCH TO
B. FOR IN-DITCH FUSION, MINIMUM TRENCH WIDTH TO 2 to 20 2-INCH 2-INCH GATE VALVE 32-INCH MAIN, USE BUTTERFLY VALVE UNLESS OTHERWISE
ACCOMMODATE EQUIPMENT ALLOWED. APPROVED IN WRITING BY CHARLOTTE WATER ENGINEER.
22 to 32 4-INCH 4-INCH GATE VALVE
D. FLUSHING DEVICE MAY BE REQUIRED.
2016-05-12
VERSION DATE
NO. DESCRIPTION
1. HDPE WATER MAIN CARRIER PIPE

HD18
5' 2. STEEL CASING PIPE, MINIMUM 35,000 PSI MINIMUM YIELD
MINIMUM 4 STRENGTH STEEL. SEE TABLE FOR THICKNESS.

VERSION NO.
3. PLUG ENDS OF CASING WITH GROUT (8-INCHES MINIMUM WIDTH).

1.0
4. EDGE OF PAVEMENT OR BACK OF CURB.
5. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER
TRACER WIRE WITH 30 MIL THICK COLOR-CODED HDPE INSULATION
AT THE BOTTOM OF THE EMBEDMENT LAYER.

NOTES:
A. CASING SPACERS ARE NOT ALLOWED FOR USE ON HDPE PIPE IN
3'-6"
STEEL CASING.

STEEL CASING FOR HDPE PIPE


MINIMUM
B. SKIDS ARE ALLOWED FOR LONG INSTALLATIONS WITH APPROVAL OF
DEPTH
ENGINEER.
2 C. ALLOWABLE TENSILE LOAD FOR PIPE MAY NOT BE EXCEEDED WHEN
5 PULLING CARRIER PIPE THROUGH CASING.
D. IF USING UNDER NCDOT ROADWAY, 36-INCH AND 42-INCH CASING IS
REQUIRED.

1
3

MINIMUM SIZE AND THICKNESS STANDARDS FOR CASING PIPE

NOMINAL DOT CASING DOT CASING RAILROAD


RAILROAD CASING
CARRIER PIPE DIAMETER THICKNESS THICKNESS
DIAMETER (INCHES)
(INCHES) (INCHES) (INCHES) (INCHES)

2 8 0.250 N/A N/A


3 8 0.250 N/A N/A
4 8 0.250 N/A N/A
6 12.75 0.250 16 0.281
8 16 0.250 18 0.312
10 18 0.250 20 0.344
12 20 0.250 24 0.406
14 20 0.250 30 0.469
16 24 0.250 30 0.469
18 24 0.375 36 0.562
20 36 0.375 36 0.562
36 0.375 36 0.562

A CITY OF CHARLOTTE DEPARTMENT


22
24 36 0.375 36 0.562
26 42 0.500 48 0.750
30 42 0.500 48 0.750
32 42 0.500 48 0.750
2016-05-12
TAPPING SADDLE WITH CAP AND CUTTER

VERSION DATE
NO. DESCRIPTION
1. HDPE WATER MAIN

HD19
2. HDPE SERVICE TAPPING SADDLE WITH CAP AND CUTTER
3. HDPE WATER TUBING (SDR-9 CTS) 8

VERSION NO.
4. BUTT FUSION JOINT

1.0
5. FINISHED GRADE OF STREET
6. 5/8" X 3/4" ANGLE BALL VALVE WITH LOCK WINGS, YOKE STAR NUT X CTS
COMPRESSION
7. WATER METER
8. METER BOX ASSEMBLY. SEE STANDARD DETAIL. 1
4 3 4
9. TRACER WIRE - CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER TRACER 2
WIRE WITH 30 MIL THICK BLUE HDPE INSULATION

HDPE SERVICE CONNECTION TAP ON


10. 5/8-INCH X 3/4-INCH BRASS 90° YOKE STAR NUT X CTS COMPRESSION

HDPE PIPE (3/4-INCH TO 1-INCH)


CONNECTOR
11. TYPE K COPPER TUBING OR HDPE SDR-9 (CTS) TUBING WITH INSERT
STIFFENERS
12. CURB AND GUTTER

1' TYP.

NOTES:
A. METER LOCATION WHERE 8 5
12 11
SIDEWALK AND CURB ARE
INTEGRAL IS AT BACK OF
SIDEWALK INSTEAD OF BACK OF
CURB AS SHOWN. 7
B. ANGLED OPTION IS ONLY ALLOWED
WITH CHARLOTTE WATER 18-INCH MINIMUM
APPROVAL

6 10
11
3-FOOT MINIMUM
1' MINIMUM
OPTION - ANGLED TAPPING SADDLE WITH METER ABOVE MAIN

6 2 4 3
°
90
AX 4
M

2 1 9

A CITY OF CHARLOTTE DEPARTMENT


1 9
NO. DESCRIPTION

2016-05-12
NOTES: G. REBARS SHALL BE GRADE 60 PER ASTM A615.

VERSION DATE
A. ALL FLANGE HARDWARE (BOLT/WASHER/NUT) SHALL BE H. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. 1. HDPE WATER MAIN
STAINLESS STEEL - TYPE 304 WITH ANTI-SEIZE I. DIAGONAL REINFORCING SHALL BE ADDED AT ALL 2. HDPE SERVICE TAPPING SADDLE WITH CAP AND CUTTER
3. HDPE BUTT FUSION JOINT

HD20
COMPOUND. OPENINGS.
B. ALL PIPE SHALL BE RESTRAINED FROM TAP TO J. PIPE PENETRATIONS SHALL BE SEALED WITH FLEXIBLE 4. BUTT FUSION X THREADED (MNPT) ADAPTER
5. STANDARD VALVE BOX ASSEMBLY (TYP) - ALL VALVES (OMIT AT

VERSION NO.
PROPERTY LINE VALVE. CONNECTERS (MANHOLE BOOTS) OR WITH 4-INCHES OF

1.0
C. VAULT SHALL BE RATED FOR NCDOT HS-20 LOADING - BRICK & MORTAR (AND 1/2 INCH THICK CONSTRUCTION CORPORATION STOP ON SHORT SIDE SERVICE)
SUBMIT SHOP DRAWINGS / P.E. SEALED FOR REVIEW. EXPANSION MATERIAL). 6. 1 1/2" SDR-9 IPS HDPE PIPE
D. ALL CONCRETE SHALL BE MINIMUM 4000 PSI K. FRAME TO BE FLUSH WITH GROUND OR CONCRETE 7. 1 1/2" BRASS BALL VALVE (FNPT x FNPT)
COMPRESSIVE STRENGTH. SIDEWALK, GROUND SHALL SLOPE AWAY FROM VAULT. 8. 1 1/2" RED BRASS PIPE NIPPLE (L = 30" )
E. DESIGN SHALL CONFORM TO ASTM C858 - L. ALL JOINTS SHALL BE MADE WATERTIGHT USING 2 9. 1 1/2" BRASS METER SETTER ASSEMBLY - FORD #VB-76-95311-05,
SPECIFICATIONS FOR "UNDERGROUND PRECAST RINGS OF BUTYL RUBBER JOINT MASTIC. MUELLER #098B 242343, CAMBRIDGE #6020-718F6F6-UUBS OR
CONCRETE UTILITY STRUCTURE". MCDONALD #720B618WTFF, NO SOLDER JOINTS PERMITTED
F. STEEL REINFORCING DESIGN SHALL CONFORM TO ASTM 10. 3/4" SCH 40 RED BRASS NIPPLE (L=18") x 2 EACH

HDPE SERVICE CONNECTION TAP


C857. 11. 1 1/2" WATER METER ASSEMBLY WITH AMR ERT TRANSMITTER (BY
CONTRACTOR)
12. BY PASS BALL VALVE WITH LOCK WINGS - LOCK VALVE IN CLOSED

ON HDPE PIPE (1 1/2-INCH)


1
POSITION (SERIAL NUMBERED STUD LOCK - FURNISHED BY
13
36" CHARLOTTE WATER)
14 13. PRECAST CONCRETE SERVICE VAULT (36" x 24" x 31")
19
14. 6" DIAMETER SUMP HOLE
15. 6" COMPACTED #57 OR #67 WASHED STONE
20
16. MINIMUM OF (3) STANDARD SOLID CONCRETE BRICK COURSES
20 6 7
20 22 UNDER ACCESS DOOR FRAME, MAXIMUM 2 FT.
2
17. 24" x 36" ACCESS DOOR - SEE STANDARD DETAIL
18. AMR (ERT) TRANSMITTER
19. 3/8" DIAMETER GALV. STEEL EYE BOLT (ADHESIVE ANCHOR) -
24" TYPICAL
3 4 8
7 8
11 9 17 21 20. AWG #12 GAUGE SOLID COPPER TRACER WIRE 20 MILS HDPE
BLUE INSULATION (THWN) - TERMINATE WITH 24" EXCESS WIRE
(COILED) AT EYE BOLT AND VALVE BOX (TYP)
21. CAST IN PLACE CONCRETE SIDEWALK - BRICK WORK SHALL NOT
10 EXTEND TO SURFACE, ACCESS DOOR SHALL REST ON SIDEWALK
TYPICAL PLAN 22. 1 1/2" TYPE K COPPER TUBING TAIL PIECE - L = 24" MIN. - CAP END

L
18
T AI 16

17
DE 13 ALTERNATE IN 18

CONCRETE SIDEWALK
17
2'
(MAX.)
5

19

5
13.25" 16 16

20 36" MIN. 11 13

20
13 20
31"
9 9 20
11
18"
12
10 4"
MIN.
2

A CITY OF CHARLOTTE DEPARTMENT


7
14
7 22
14 4" MIN.
6 3 4
8 8
1

15
TYPICAL ELEVATION SECTION VIEW 15
NO. DESCRIPTION

2016-05-12
NOTES: G. REBARS SHALL BE GRADE 60 PER ASTM A615.

VERSION DATE
A. ALL FLANGE HARDWARE (BOLT/WASHER/NUT) SHALL BE H. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. 1. HDPE WATER MAIN
STAINLESS STEEL - TYPE 304 WITH ANTI-SEIZE I. DIAGONAL REINFORCING SHALL BE ADDED AT ALL 2. HDPE SERVICE TAPPING SADDLE WITH CAP AND CUTTER

HD21
COMPOUND. OPENINGS. 3. HDPE BUTT FUSION JOINT
B. ALL PIPE SHALL BE RESTRAINED FROM TAP TO J. PIPE PENETRATIONS SHALL BE SEALED WITH FLEXIBLE 4. BUTT FUSION X THREADED (MNPT) ADAPTER

VERSION NO.
PROPERTY LINE VALVE. CONNECTERS (MANHOLE BOOTS) OR WITH 4-INCHES OF 5. STANDARD VALVE BOX ASSEMBLY (TYP) - ALL VALVES

1.0
C. VAULT SHALL BE RATED FOR NCDOT HS-20 LOADING - BRICK & MORTAR (AND 1/2 INCH THICK CONSTRUCTION (OMIT AT CORPORATION STOP ON SHORT SIDE SERVICE)
SUBMIT SHOP DRAWINGS / P.E. SEALED FOR REVIEW. EXPANSION MATERIAL). 6. 2" SDR-9 IPS HDPE PIPE
D. ALL CONCRETE SHALL BE MINIMUM 4000 PSI K. FRAME TO BE FLUSH WITH GROUND OR CONCRETE 7. 2" BRASS BALL VALVE (FNPT x FNPT)
COMPRESSIVE STRENGTH. SIDEWALK, GROUND SHALL SLOPE AWAY FROM VAULT. 8. 2" RED BRASS PIPE NIPPLE (L = 30" )
E. DESIGN SHALL CONFORM TO ASTM C858 - L. ALL JOINTS SHALL BE MADE WATERTIGHT USING 2 9. 2" BRASS METER SETTER ASSEMBLY - FORD
SPECIFICATIONS FOR "UNDERGROUND PRECAST RINGS OF BUTYL RUBBER JOINT MASTIC. #VB-76-95311-05, MUELLER #098B 242343, CAMBRIDGE
CONCRETE UTILITY STRUCTURE". #6020-718F6F6-UUBS OR MCDONALD #720B618WTFF, NO
F. STEEL REINFORCING DESIGN SHALL CONFORM TO ASTM SOLDER JOINTS PERMITTED

HDPE SERVICE CONNECTION TAP


C857. 10. 3/4" SCH 40 RED BRASS NIPPLE (L=18") x 2 EACH
11. 2" WATER METER ASSEMBLY WITH AMR ERT TRANSMITTER
(BY CONTRACTOR)
12. BY PASS BALL VALVE WITH LOCK WINGS - LOCK VALVE IN

ON HDPE PIPE (2-INCH)


36"
13 CLOSED POSITION (SERIAL NUMBERED STUD LOCK -
1 FURNISHED BY CHARLOTTE WATER)
19 19 13. PRECAST CONCRETE SERVICE VAULT (36" x 24" x 31")
14. 6" DIAMETER SUMP HOLE
8 9 14 7 15. 6" COMPACTED #57 OR #67 WASHED STONE
22
16. MINIMUM OF (3) STANDARD SOLID CONCRETE BRICK
2
COURSES UNDER ACCESS DOOR FRAME, MAXIMUM 2 FT.
24" 17. 24" x 36" ACCESS DOOR - SEE STANDARD DETAIL
18. AMR (ERT) TRANSMITTER
20 10
3 6 x 11 7 19. 3/8" DIAMETER GALV. STEEL EYE BOLT (ADHESIVE
21 ANCHOR) - TYPICAL
17
20. AWG #12 GAUGE SOLID COPPER TRACER WIRE 20 MILS
HDPE BLUE INSULATION (THWN) - TERMINATE WITH 24"
10 EXCESS WIRE (COILED) AT EYE BOLT AND VALVE BOX (TYP)
21. CAST IN PLACE CONCRETE SIDEWALK - BRICK WORK SHALL
TYPICAL PLAN NOT EXTEND TO SURFACE, ACCESS DOOR SHALL REST ON
SIDEWALK
18 A IL 16 22. 2" TYPE K COPPER TUBING TAIL PIECE - L = 24" MIN. - CAP
T END.
ALTERNATE IN 18
DE
17 13

CONCRETE SIDEWALK 17
2-FT
5
MAX.
5
19

5
16 16

18 19
13
11
11 20 31" 13
9 11
9
20 18"
12 10 4" MIN.
2

A CITY OF CHARLOTTE DEPARTMENT


6 22 14
3 4 20 4
20 5
8
14
10
7 MIN. 4"

1
15
15
TYPICAL ELEVATION SECTION VIEW
2016-05-12
NO. DESCRIPTION

VERSION DATE
1. HDPE GRAVITY SEWER PIPE - DR17, BUTT FUSED OR ELECTROFUSED NO. DESCRIPTION
2. CUSTOMER SEWER LATERAL 1. RUBBER COUPLING

HD22
3. ELECTROFUSION COUPLING OR BUTT FUSION JOINT 2. NEW HDPE SEWER LATERAL (DR 17)
4. HDPE LONG RADIUS WYE 3. TRANSITION COUPLING

VERSION NO.
5. FLEXIBLE, SHIELDED, COUPLING WITH SHEAR BAND 4. EPOXY SADDLE

1.0
6. CAST IRON SEWER VALVE BOX TOP SECTION AND LID 5. ELECTROFUSION SADDLE
7. LID 6. STRAPPED RUBBER SADDLE (PVC HUB, RUBBER SADDLE, AND SS
8. FINISH GRADE BAND)
9. TRACER WIRE-CONTINUOUS AWG NO. 12 GAUGE SOLID COPPER TRACER 7. FABRICATED HDPE TEE
WIRE WITH 30 MIL THICK GREEN HDPE INSULATION. 8. EXISTING SEWER LATERAL

LATERAL ON HDPE PIPE BY PIPE BURSTING


4-INCH TO 6-INCH SEWER CLEANOUT AND
10. TRACER WIRE TERMINATION. SEE STANDARD DETAIL. 9. CLEAN OUT
12. BEND - 22.5-DEGREE OR 45-DEGREE
13. ELECTROFUSION SADDLE TEE
14. HDPE SEWER MAIN INSTALLED BY PIPE BURSTING
NOTES:
NOTES:
A. RUBBER COUPLINGS SHALL BE SHIELDED TYPE WITH STAINLESS
A. MINIMUM LATERAL SLOPE SHALL BE 1.0%.
STEEL SERIES 300 BANDSCREW AND HOUSING WITH SHEAR BAND.
B. BASED ON SITE CONDITIONS, CHARLOTTE WATER MAY APPROVE THE
B. RUBBER SADDLES SHALL BE SEALED WITH AN ELASTOMERIC
CLEANOUT INSIDE THE ROAD RIGHT-OF-WAY.
SEALANT. SEE SPECIFICATIONS.
C. SEWER MAIN, SADDLE TEE, AND BEND SHALL BE COMPLETELY EMBEDDED
C. CHANGES IN PIPE TYPE AND CONNECTIONS ARE NOTED ON THE
WITH #57 OR #67 WASHED STONE.
DRAWINGS
D. IF ADDITIONAL COUPLINGS ARE NEEDED TO MAKE A CONNECTION,
THE CONTRACTOR SHALL USE ELECTROFUSION COUPLINGS
E. ELECTROFUSION SADDLES SHALL CONSIST OF A FUSION SADDLE
WITH AN INTEGRAL FUSION COUPLER AT ITS OUTLET.
CHARLOTTE WATER EASEMENT
ROAD RIGHT-OF-WAY OR

CHARLOTTE WATER PROPERTY OWNER / CUSTOMER

7 6 8 NEW HDPE LATERAL INTO NEW HDPE LATERAL INTO EXISTING LATERAL INTO
EXISTING SEWER NEW OR EXISTING HDPE SEWER NEW HDPE OR PVC SEWER

11
1 1
3 1
9 9
10 9
4
10
1
12

13 3 5
14 3 2
2

5
3 3
4 6 7
2-FOOT MINIMUM

A CITY OF CHARLOTTE DEPARTMENT


EXIST. SEWER MAIN NEW OR EXISTING NEW SEWER MAIN
(PVC, DUCTILE, OR VCP) SEWER MAIN (HDPE) (HDPE OR PVC)

1 1
2016-05-12
VERSION DATE
HD23
STRADDLE TYPE SANITARY SEWER MANHOLE WITH HDPE PIPE

VERSION NO.

1.0
7" MIN. 4 6 A
5 2

21" MAX. 7 FORM CHANNEL IN PLACE

SADDLE TYPE MANHOLE CONNECTION


ON HDPE PIPE (8-INCH AND LARGER)
1
24"Ø - 4'Ø
30"Ø - 5'Ø FL
O
W

7" MIN.

FLOW
8 3

TAPERED TOWARDS FLOW


LINE FOR CAMERA ACCESS
A
5" MIN. 48" OR 60"Ø 5" MIN. 6' FOR 4'ØMH
9 7' FOR 5'ØMH
6" MIN.
(TYP.)
3" MIN.
10
6" ± 3" MIN.
(TYP.)

6" MIN. 6" MIN.


2" MIN.
. FLOW (TYP.) 3" MIN.
3" MIN. 3" 11 3" MIN.
N. 12" MIN.
MIN.

11 11
12"

12
3" 13
6' FOR 4'ØMH 6' FOR 4'ØMH
7' FOR 5'ØMH SECTION A-A 7' FOR 5'ØMH

NO. DESCRIPTION
1. PIPE JOINT. SEE STANDARD DETAIL FOR NEW PIPE CONNECTION AT MANHOLE NOTES:
2. POURED IN PLACE CONCRETE BASE - 3600 PSI CONCRETE 7" HOOK 7" HOOK
A. ALL PIPE OPENINGS SHALL BE NO GREATER THAN
3. POLYPROPYLENE SAFETY STEPS INSTALLED ON UPSTREAM SIDE - 4-FOOT Ø MH 3-INCH LARGER THAN THE OUTSIDE DIAMETER OF
OVER WIDEST SHELF - 5-FOOT Ø MH THE PIPE.
4. MANHOLE FRAME AND COVER. SEE STANDARD DETAIL. B. BASE SECTION SHALL BE REINFORCED WITH A
5. CONCRETE COLLAR, POURED IN PLACE. 10-INCH MINIMUM DEPTH (REQUIRED IN ROADWAY) MINIMUM AREA OF 0.20 SQUARE INCHES PER
6. GRADE WITHIN RIGHT-OF-WAY LINEAR FOOT EACH WAY. 5'-6" FOR 4'ØMH
7. PRECAST CONCRETE GRADE RINGS AS REQUIRED C. ALL PRECAST SECTIONS SHALL BE DESIGNED FOR 6'-6" FOR 5'ØMH
8. BUTYL RUBBER ROPE BETWEEN ALL JOINTS AND TAPE OUTSIDE OF BARREL SECTIONS H-20 LOADING + IMPACT + LIVE LOAD + DEAD LOAD. #5 REBAR GRADE 60
AND GRADE RINGS (TYPICAL)
@8-INCH CENTERS EACH WAY
9. PRECAST MANHOLE SECTIONS CONFORMING TO ATSM C-478, AS MODIFIED.

A CITY OF CHARLOTTE DEPARTMENT


10. MINIMUM SHELF SLOPE OF 1:12
11. CONCRETE BASE, 3,600 PSI CONCRETE
12. COMPACTED #57 OR #67 WASHED STONE UNDER CONCRETE BASE
13. #5 REBAR AT 18" O.C. BOTH WAYS. REBAR SHALL HAVE A MINIMUM CLEARANCE OF
3-INCHES WHEN CONCRETE IS NOT FORMED
2016-05-12
VERSION DATE
SMALL PUNCTURE REPAIR

HD24
VERSION NO.

1.0
1

(MAINTENANCE REPAIRS ONLY)


2

EXISTING HDPE PIPE REPAIR


1

NO. DESCRIPTION
1. EXISTING HDPE WATER MAIN
2. WRAP AROUND REPAIR CLAMP
3. SOLID RESTRAINED SLEEVE

SMALL PUNCTURE REPAIR NOTES:


A. SMALL PUNCTURE DAMAGE IS DEFINED AS ONE INCH OR SMALLER
PUNCTURE IN ONE PIPE WALL.
B. PREFFERED REPAIR METHOD FOR SMALL PUNCTURE IS
ELECTROFUSION PATCH. MECHANICAL COUPLING IS ALLOWED
WHEN PIPE CAN NOT BE DRIED, UPON APPROVAL OF CHARLOTTE
WATER INSPECTOR.
C. BEFORE ADDING FITTING, DRILL SMALL HOLE AT EACH END OF
DAMAGE TO PREVENT CRACK PROPAGATING.
D. FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906.
E. MECHANICAL FITTINGS USED WITH HDPE PIPE SHALL BE
SPECIFICALLY DESIGNED FOR USE WITH HDPE PIPE.
F. MINIMUM CLAMP WIDTH IS 12-INCHES. MINIMUM CLAMP WIDTH IS

A CITY OF CHARLOTTE DEPARTMENT


5-INCHES ON EITHER SIDE OF PUNCTURE, FOR 10" NOMINAL
DIAMETER PIPE AND LARGER.
CREEK CROSSING BY DIRECTIONAL DRILL

2016-05-12
VERSION DATE
TOP OF BANK TOP OF BANK

HD25
VERSION NO.

1.0
3 2 3 3 2 3

4-FOOT
MIN.
COVER

HDPE CREEK CROSSING


1 MIN. 10-FT 1 MIN. 10-FT 1

CREEK CROSSING WITH FITTINGS


TOP OF BANK
OPEN CUT OR CONVENTIONAL BORE TOP OF BANK

3 2 3 3 2 3

4-FOOT
MIN.
COVER

1 MIN. 10-FT 1 MIN. 10-FT 1

NO. DESCRIPTION NOTES:


1. HDPE WATER MAIN CARRIER PIPE A. FITTINGS SHALL MEET THE REQUIREMENTS OF AWWA C906.
2. VALVE B. MECHANICAL FITTINGS USED WITH HDPE PIPE SHALL BE
3. HDPE RESTRAINED JOINT ADAPTER WITH SPECIFICALLY DESIGNED FOR USE WITH HDPE PIPE.
STEEL PIPE STIFFENER C. STAINLESS STEEL INTERNAL STIFFENERS SHALL BE INSTALLED IN
THE END OF THE HDPE PIPE WHEN HDPE PIPE IS INSERTED INTO
THE BELL END OF NON-HDPE PIPE, VALVE, FITTING, OR INTO THE
HUB OF A BOLTED COUPLING
D. ALLOWABLE TENSILE LOAD FOR PIPE MAY NOT BE EXCEEDED WHEN
PULLING CARRIER PIPE THROUGH HORIZONTAL DIRECTIONAL DRILL

A CITY OF CHARLOTTE DEPARTMENT


(HDD). PROVIDE SEALED CALCULATIONS.
E. LOCATE VALVES IN ACCESSIBLE LOCATION AT TOP OF BANK WITHIN
100 TO 1,000 LINEAR FEET OF TOP OF BANK ON BOTH SIDES OF
CENTERLINE OF CREEK.

You might also like