You are on page 1of 4

TRANSMISSION AND DISTRIBUTION

Electromagnetic forces in transformers


under short circuit conditions
by Nadim Mahomed, Powertech Transformers

Short circuit events generate high current conditions in transformer windings. These currents in turn induce excessive forces in a transformer.
Electromagnetic forces are important considerations in the design, manufacturing and operation of transformers. These forces can be
subdivided into axial and radial forces each with unique considerations and mitigating measures.

Transformers in general consist of primary of electromagnetic forces are presented i(t) = instantaneous short circuit current
and secondar y windings, across which here to guide toward an appreciation of
Ip = peak short circuit current
a voltage and current transformation the significance of short circuit events in
is induced at constant power. During transformer design. The discussion begins  = angular frequency in rad/s
normal operation the transformer will be with a description of the short circuit
supplied on the primary at rated voltage current, the induced electromagnetic  = voltage angle at which short circuit
and current. Current flowing in the primary forces and finally methods of preventing occurs
windings will induce a magnetic field that transformer failure.  = impedance phase angle
will link the windings of the secondar y,
inducing current flow. Current flow in the Short circuit current Fig. 1 shows that the first current peak is the
secondary will be inversely proportional The most commonly occurring short circuit maximum peak, becoming progressively
to the turn ratio between the primary and event is a single-line to earth fault in which smaller as the unidirectional (green line in
secondary windings. one phase is short circuited to ground. This Fig. 1) component decays. For this reason
type of fault may occur due to lightning the first peak is usually used to calculate
The generation of an electromagnetic maximum occurring forces.
strikes, debris, pollution effects, animals
field inside the transformer is therefore
and vegetation. Other types of faults To aid the understanding of short circuit
intrinsic to transformer operation. This
such as three-phase to ground, double current and its relationship to the power
electromagnetic field will however lead
earth fault are also considered in short transformer, the simplest fault scenario,
to the generation of forces inside the
circuit current calculations. In general the viz. three-phase symmetrical short circuit
transformer windings stipulated by the laws
short circuit current is calculated using fault, is discussed. This allows the use of an
of magnetism viz. Faradays law of induction
symmetrical components for various equivalent single phase circuit model, as
and Lenz's law of electromagnetic force[1].
situations taking into account: all phases remain balanced and nominal
During normal operation, these forces are or rated values of the transformer current
 Tapping arrangement
relatively low and for this condition the can be used. The steady state component
transformer design is based primarily on the  Fault position (e.g. low voltage or high
of short circuit current for this simple case
dielectric and thermal considerations – loss voltage winding)
can be expressed as a multiple of nominal
reduction and insulation integrity. Under  Short circuit power combination current by the overcurrent factor "r" shown
short-circuit fault conditions the current (network and transformer) in Eqn. 2. The steady state current under
excitation increases significantly, possibly  Short circuit type (e.g. single phase to short circuit condition is then r times the
8 – 10 times nominal current, resulting in earth, three phase symmetrical, etc.) nominal current.
extreme forces in the transformer windings.
The short circuit withstand capability of The short circuit current given in (2)
a transformer, is mainly a function of its Eqn 1.consists of two components: a steady
state component at power frequency, and where:
thermal and mechanical performance.
However, due to the speed at which an exponentially decreasing unidirectional Zt = transformer impedance in percentage
these faults occur and are cleared, the component as shown in Fig. 1 [2].
primar y concern is of a mechanical Z s = system impedance in percentage
(1)
nature, and design considerations shift to To account for the initial direct current
control the electromagnetic forces and (DC) offset and therefore the first peak,
prevent mechanical failure. The basics where:
a further factor called the asymmetr y
factor "k" is used [2]. This results in a
more accurate representation of the
current to precisely calculate the peak
electromagnetic force. Values of k are
specified in the applicable standards such
as the IEC 60076-5 [3]. The asymmetry
factor is dependent on the ratio of the
transformer reactance (X) and resistance
(R). Values of k increase for increasing X/R
ratios. Values of 1,8 for transformers up to
100 MVA and 1,9 for transformers in excess
of 100 MVA are indicated when the X/R
ratio is unavailable [3].

Electromagnetic forces
Fig. 1: Short circuit current [2]. The current carr ying conductors of the

energize - March 2011 - Page 36


TRANSMISSION AND DISTRIBUTION

Fig. 2: Current and induced force waveforms.

Fig. 4: Magnetic field and associated


Fig. 3: Directional relationship between fields. force directions.

transformer windings are situated in the The direction of the forces are stipulated the full 3-phase transformer on the left is
magnetic leakage field. By the fundamental by the vector product in Eqn. 3 indicating a 360° rotation of the 2D diagrams on the
postulates of electromagnetics these that the force will act perpendicular to right about the axis (dashed line). This is a
conductors will experience a force the plane formed by the magnetic field single phase axi-symmetric simplification
due to the interaction between the intensity and current direction. The force of the transformer geometry that may be
electric (current) and magnetic fields. direction can be determined using the analysed in two dimensions as is the case
This electromagnetic force is calculated in Fig. 4.
left hand rule, as indicated in Fig. 3 which
as the vector product of current density describes the field relationships for the Electromagnetic forces in transformer
and magnetic field intensity as given in
cross-section of a single conductor. windings can be sub-divided into axial and
Eqn. 3 [1].
radial force by means of associated axial
Electromagnetic force tends to minimise
(3) and radial modes of failure. Axial forces
the magnetic energy density in the
occur in a direction parallel to the winding
where: volume. In this way the forces tend to :
height. Radial forces occur perpendicular
F = force in N  Reduce the radius of inner windings to the winding height. Axial and radial
 Increase the radius of outer windings forces, although sharing a common
J = current density in A/m 2 origin, can for the most part, be treated
 Reduce the height of windings – as mutually exclusive modes [2].
B = magnetic flux density in T windings are compressed toward the
Short circuit current will influence both flux median horizontal Radial forces
density B and current density J in Eqn. 3 Viewing the transformer from a cross The flux at mid winding height is for the
implying that force is proportional to the sectional view (Fig. 4), and taking into most part parallel to the winding height.
square of the current. Fig. 2 shows the account the direction of the current According to the left hand rule, the resulting
relationship between current and force as being constant, it is noted that the force therefore acts perpendicular to the
and the nature of electromagnetic forces. force is perpendicular to, and follows the winding height. For windings on the inside
The electromagnetic force pulsates at bending of the flux lines. In the middle of of the main flux field (situated between
approximately twice the power frequency the windings this results in a radial force primary and secondary windings) the force
and is unidirectional. Considering that the pushing outward, and toward the ends of acts inward, and for outside windings,
overcurrent factor is typically between 8 the windings this results in an axial force outward as depicted in Fig. 5.
and 10, the force generated can easily pushing onto the windings.
be in the region of a hundred times the Forces acting on the inside windings result
nominal force magnitude and may reach The explanation of the transformer cross in a compressive stress whereas on the
several thousand kN [2]. section is shown in Fig. 5. The 3D figure of outer winding this force leads to a tensile

energize - March 2011 - Page 38


TRANSMISSION AND DISTRIBUTION

Fig. 5: Transformer 2D diagrammatic representation explained. Fig. 6: Conductor force directions and associated stresses.

stress acting to elongate the winding turn work to increase the displacement i.e. primarily of a mechanical nature, involving
– as shown in Fig. 6 [2]. This is as a result windings are pushed further apart, resulting structural countermeasures whereas
of the cylindrical profile of the windings in iteratively worse displacements and reducing the origin of these forces is
where forces, perpendicular to the winding therefore higher forces [2]. primarily a magnetic field problem and
circumference, create tangential stresses. therefore electrical in nature.
Mitigating the effects of short circuit
As stated earlier, radial and axial short
Axial forces In essence there are two approaches to circuit forces and their associated modes
Axial forces are generated parallel with reducing the destructive effects of short of failure may be considered mutually
the winding height. Due to the pattern of circuit forces. At the outset transformer exclusive for the most part. Preventative
the magnetic leakage field, the windings Designers aim to decrease the occurring measures will involve manipulating the
experience opposing forces at the winding electromagnetic forces by sound design magnetic field, and making choices in the
ends, leading to compressive forces. Axial choices. Electromagnetic forces however design that will lead to a more acceptable
force is generated when the transformer's will always be of significant levels, and field distribution inside the transformer.
magnetic field lines are radially orientated. measures to mitigate the effect of these One way to reduce the magnitude of
Fig. 4. shows that the highest ‘bending' of induced forces must be taken. Measures the magnetic field would be to decrease
the magnetic field occurs at the winding against electromagnetic forces are the short circuit current by increasing the
ends, consequently maximum axial force is
generated here. The local force generation
accumulates toward the middle of the
windings resulting in a maximum occurring
force at mid-winding height. This force is
compressive towards the winding centre as
the circulation direction of the magnetic
field leads to opposing forces at each end
of the winding. A schematic representation
of the axial force distribution, in a typical
transformer winding, is shown in Fig. 7.
In addition to the compressive force
occurring in the winding the effect of
recoil is also considered as transformer
windings are essentially springs from a
mechanical point of view. This spring
action can be explained by noting the
nature of the electromagnetic wave in
Fig. 2. The force magnitude follows
a sinusoidal pattern and therefore
compressive tension stored in the winding
is released as the force approaches zero.
This force will be exerted against the core
yokes and end insulation structures, and
will have a magnitude of less than the
compressive force generating it.
Winding displacement from the centre
line result in excessive axial forces, and
provision for this possibility is necessary –
shown in Fig. 8. This is due to the difference
in the ampere-turns (i.e. mmf) distribution
along the winding heights resulting in more
pronounced bending of the field lines at
the point of missing ampere-turns or where
the displacement occurs. The forces then

energize - March 2011 - Page 39


TRANSMISSION AND DISTRIBUTION
stretching of the conductors and may lead
to rupture, if the conductor yield strength
is exceeded. Compressive stresses lead
to buckling of the conductors, in which
the conductors are forced inward and
could potentially bulge outwards at the
elastic limit of the conductor material.
Mitigating radial forces primarily involves
choosing the correct hardness of the
conductor while taking into account
cost and manufacturability. In addition,
a sound winding design methodology
such as self-supporting windings, correct
dr ying and processing, and the use of
appropriate conductors minimises the risk
of radial failure.
Both axial and radial forces often lead
to secondary failure which is dielectric in
nature. Failure of the insulation structures
due to the aforementioned failure modes
is common, leading to arc formation, and
dielectric breakdown.
Fig. 7: Cumulative and local force distribution along winding height.

Conclusion
impedance values of the system and/ as high short circuit forces are inevitable.
or transformer thereby decreasing the The short circuit withstand capability of a Short circuit events that occur in a
overcurrent factor. However this is not transformer is dependent on the occurring network induce high mechanical forces in
always practicable since these parameters stress vs. mechanical withstand ability of transformer windings. The electromagnetic
are usually dependent on a host of other the various structural parts. force is induced in the transformer windings
requirements such as network topology and is due to the interaction of the
Axial allowable stress limits are divided magnetic field of the transformer and
and customer specifications.
into two categories namely limits relating the current density in the transformer
Manipulating the field-winding relation can to the compressive forces in the windings
windings. As such the force is exponentially
be achieved by changing the geometries themselves and those related to axial thrust
proportional to the current resulting
of the transformer active part i.e. core and forces toward the clamping structure. Axial
in excessive force generation for any
windings. The goal of any field manipulation thrust forces are a consequence of winding
increase in current. The radial and axial
would be, primarily, to reduce axial forces displacement (Fig. 8) and the spring
force may be treated independently and
by straightening the field lines in the action of the windings (after compressive
could result in radial and axial modes
region of the winding ends. Less bending forces). Compressive force is a concern
of failure if the withstand capability is
of the field lines equals less axial forces. in the windings themselves whereas thrust
forces affect the end structures (between e x c e e d e d. T h e m a g n i t u d e o f t h e s e
Adjusting winding height, winding duct
width (space between windings), winding the yoke and windings). End thrust forces forces may be reduced by manipulating
inner diameter, distances from winding to can lead to failure of the end insulation the magnetic field by changes in the
core are some of the considerations that structures, which include those structures transformer geometry. However provision
can have a significant impact on the field common to all windings. Since all windings for these forces must be made, consisting
pattern with limited effect to other design in a multiple winding transformer may mainly of the mechanical withstand
considerations. experience simultaneous end thrust forces capabilities and positioning of the various
(all currents in a winding block being in transformer materials. Initially a transformer
In addition to field considerations the phase), the cumulative effect must be design is driven by thermal and dielectric
transformer must be built to mechanically taken into account. Compressive forces properties; however short circuit provisions
withstand all forces generated under a on the other hand can lead to failure of often supersede these design choices
short circuit event. The structural rigidity of the windings themselves. Various modes leading to significant cost increase.
the transformer active part is paramount of failure are taken into account viz. Short circuit withstand is a complicated
conductors bending between spacers, interaction of electrical- and mechanical
conductor tilting, conductor telescoping, engineering and its significance in any
and spacers disintegrating [2]. Also worth electromagnetic machine should not
noting is the pulsating nature of the forces, be underestimated, least of all in power
which can lead to deterioration of the transformers.
insulation structure and demonstrate the
importance of quick fault clearing times. References
The risk of failure from any of these forces [1] D K C h e n : F i e l d a n d W a v e
is directly related to the processing and Electromagnetics,Addison-Wesley Publishing
assembly of the windings. Reducing the risk Company Inc., USA, second edition, November
1992.
of failure due to axial stresses, is concerned
[2] G Bertagnolli: Short-circuit Duty of Power
with minimising winding displacements, Transformers, ABB Ltd., Zurich, third edition, June
c o r r e c t w i n d i n g c l a m p i n g, r e d u c e d 2006.
moisture content due to proper processing [3] IEC standard 60076-5: Power Transformers – Part
and the use of quality materials. 5: “Ability to withstand short circuit”, 2006.

Radial forces lead to tensile and Contact Nico Gunter,


compressive stresses which display distinct Powertech Transformers,
modes of failure. Tensile stresses are due Tel 012 318-9911,
Fig. 8: Winding displacement to forces acting to increase the diameter nico.gunter@pttransformers.co.za 
and induced forces. of the windings. These forces result in

energize - March 2011 - Page 40

You might also like