BATTERY SIZING DONE TO IEEE485 STANDARD

CUSTOMER MALAKOFF POWER BHD PERAI PLANT Date 8-9-2019


Sized by: SYED FIAMM MALAYSIA
PROJECT To supply & replace 125VDC battery bank
FIAMM Sizing Tool 2.1.22
DESIGN MINIMUM CELL ELECTROLYTE CELL TYPE:
TEMPERATURE: 20 °C VOLTAGE 1.781 Volt DENSITY 1.22 PLANTE'
(1) (2) (3) (4) (5) (6) (7)
PERIOD LOAD CHANGE IN DURATION TIME TO END (3) / (6)
LOAD (Amperes) LOAD OF PERIOD OF SECTION Ah/pos plate
( minutes ) POSITIVE PLATE FOR SECTION
Pos. Values Neg. Values

Section 1
1 A1 = 600.0 A1-0 = 600.0 M1 = 1 M1= 1 135.01 4.44
Sub total 4.44
Total 1.................... 4.44
Section 2
1 A1 = 600.0 A1-0 = 600.0 M1 = 1 M1+M2= 121 39.06 15.36
2 A2 = 180.0 A2-A1= -420.00 M2 = 120 M2= 120 39.30 -10.69
Sub total 15.36 -10.69
Total 2.................... 4.67

Temperature correction = 1.00 Design Margin = 1.10 Aging Factor = 1.20


Uncorrected Size = 4.67 Positive Plates Number of positive plate x Total Correction Factor (1.32) = 6.17 Positive Plates
Required Size = 7 Positive Plates
Capacity = 770 Ah (C10) Number of cells = 64 Cell Type = SGH 15 D

To supply & replace 125VDC battery bank GROE PLANTE TYPE


Requested Load Profile
700

600
600

500

400
(Amperes)

300

180
200

100

0
0 20 40 60 80 100 120 140

MINUTES

125VDC battery bank

All data printed in this document are preliminary and must be confirmed by Fiamm