Allen Bradley
Adjustable
Frequency AC Drive

Powerflex 4M
400 W
AB Powerflex 4M
Wiring the Drive
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M

Parameter Organization
AB Powerflex 4M

Parameter Organization - Display


d001 – Output Frequency
Output frequency present at T1, T2 & T3 (U, V & W).

d002– Commanded Frequency


Value of the active frequency command. Displays the
commanded frequency even if the drive is not running.

d003 - Output Current


The output current present at T1, T2 & T3 (U, V & W).

d004 - Output Voltage


The output voltage present at T1, T2 & T3 (U, V & W).
d006 – Drive Status
Present operating condition of the
d005 – DC Bus Voltage
drive.
Present DC bus voltage level.
AB Powerflex 4M

Parameter Organization
d010 – Process Display
The output frequency scaled by A440 [Process Factor] or by A438 [Process Time Lo] and
A439 [Process Time Hi].

d012 – Control Source


Displays the active source of the Start
Command and Speed Command.
AB Powerflex 4M

Parameter Organization
d012 – Control In Status
Status of the control terminal block control inputs.
Important: Actual control commands may come from a source other than the control
terminal block.

d018 - Elapsed Run Time


Accumulated time drive is outputting power. Time is displayed in 10-hour increments.
AB Powerflex 4M

Parameter Organization
d020 - Analog In 0-10V
The present value of the voltage at I/O Terminal 13 (100.0% = 10 volts).

d021 - Analog In 4-20mA


The present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA).

d022 - Drive Temperature


Present operating temperature of the drive power section.
AB Powerflex 4M

Parameter Organization - Program


P101 – Motor NP Voltage
Stop drive before changing this parameter.
Set to the motor nameplate rated voltage.

P102 – Motor NP Hertz


Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.

P103 – Motor OL Current


Set to the maximum allowable motor current.

P104 – Minimum Frequency


Sets the lowest frequency the drive will output
continuously. Min/Max: 0.0/400.0 Hz

P105 – Maximum Frequency


Sets the highest frequency the drive will output
continuously. Min/Max: 0.0/400.0 Hz
AB Powerflex 4M

Parameter Organization - Program


P106 – Start Source
Stop drive before changing this parameter.
Sets the control scheme used to start the drive.

P107 – Stop Mode


Active stop mode for all stop sources
0“Ramp, CF”(1) (Default)
Ramp to Stop. “Stop” command clears
active fault.
1“Coast, CF”(1)
Coast to Stop. “Stop” command clears
active fault.
AB Powerflex 4M

Parameter Organization - Program


P108 – Speed Reference
Sets the source of the speed reference to the drive.

P109 – Acc. time


Sets the rate of acceleration for all speed increases.
AB Powerflex 4M

Parameter Organization - Program


P110 – Dec. Time
Sets the rate of deceleration for all speed decreases.

P112 – Reset to Default


Resets all parameter values to factory defaults.
AB Powerflex 4M

Parameter Organization - Terminal


t201 – Digital In1 Sel
(I/O Terminal 5)
T202 – Digital In2 Sel
(I/O Terminal 6)
AB Powerflex 4M

Parameter Organization - Terminal


t201 – Digital In1 Sel
(I/O Terminal 5)
T202 – Digital In2 Sel
(I/O Terminal 6)
AB Powerflex 4M

Parameter Organization - Terminal


t211 – Analog In 0 ~ 10 V Lo
Sets the analog input level that corresponds to P104 [Minimum Freq] if a 0-
10V input is used by P108
Analog inversion can be accomplished by setting this value larger than
t212 [Anlg In 0-10V Hi] or by setting t201 - t202 [Digital Inx Sel] to option
15 “Anlg Invert”.

t212 – Analog In 0 ~ 10 V Hi
Sets the analog input level that corresponds to P105 [Maximum Freq] if a 0-10V input is
used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than t211 [Anlg In 0-
10V Lo] or by setting t201 - t202 [Digital Inx Sel] to option 15 “Anlg Invert”.
AB Powerflex 4M

Parameter Organization - Terminal


t213 – Analog In 4 ~ 20mA Lo
Sets the analog input level that corresponds to P104 [Minimum Freq] if a 4-
20mA input is used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value larger than t214
[Anlg In4-20mA Hi] or by setting t201 - t202 [Digital Inx Sel] to option 15
“Anlg Invert”.

t214 – Analog In 4 ~ 20mA Hi


Sets the analog input level that corresponds to P105 [Maximum Freq] if a 4-
20mA input is used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than
t213 [Anlg In4-20mA Lo] or by setting t201 - t202 [Digital Inx Sel] to option
15 “Anlg Invert”.
AB Powerflex 4M

Parameter Organization - Terminal


t221 – Relay Out Selection
Sets the condition that changes the state of the output relay contacts.
AB Powerflex 4M

Parameter Organization - Terminal


t221 – Relay Out Selection
Sets the condition that changes the state of the output relay contacts.

t222 – Relay Out Level


Sets the trip point for the digital output relay if the value
of t221 [Relay Out Sel] is 6, 7, 8, 10 or 11.
nfi Learn 4 PLC’s in a Day

Learn to Code | Code to Learn


presents
100+ Video Tutorials
Coupon Code
in $99 $49
https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare

Life time Access


Course Outline PLC – Programmable Logic Controller
Delta DVP 14 SS + 16 SP
• 100+ PLC Video Tutorials Allen Bradley M1000
• Doubt Clearing Complementary LIVE Sessions on Team Viewer Siemens S7 200
• Ladder Logic Programming Schneider
• PLC Presentations, PLC Circuits, PLC Codes Analog Cards Programming
• FREE PLC Simulation Software for Practice 04 AD – Analog to Digital
04DA- Digital to Analog
For more courses visit www.nfiautomation.org
PLC & VFD Advanced
Course
4 PLC’s Training
Platforms

$149
Course Link:
Course Highlights: http://www.wiziq.com/course/28882-plc-and-
ac-drives-online-certificate-trainaing-course
• 30 Live Practical Classes on PLC, Analog Cards & AC drives- VFD
• 100+ PLC Video Tutorials with Lifetime Access & FREE PLC Simulator
• FREE Circuits Diagram

For more courses visit www.nfiautomation.org


Thanks
www.nfiautomation.org

nfi

You might also like