IIE – ISHRAE INSTITUTE OF EXCELLENCE

ADVANCED DIPLOMA COURSE IN


REFRIGERATION AND AIR CONDITIONING
RAC 002
PSYCHROMETRY, HEAT LOAD ESTIMATION
FOR
AIR-CONDITIONING & REFRIGERATION

RAC 002.01B-PSYCHROMETRY-02 1

Objectives
–Understand various processes.
–How the status point shifts in the psychrometric chart when
thermodynamic processes alter the condition of air
–Mark a process

2
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

1
Processes - Sensible Heating

HOT WATER HEX ELECTRIC HEATER

AIR AIR

SINGLE
STAGE

MULTI
STAGE
COLD WATER

THYRISTOR
HOT WATER IN

CONTROLLED
OUT

3
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes - Sensible Heating


When air undergoes SENSIBLE HEATING (no
change in content of moisture), the status point
shifts to the right of its initial condition
(HORIZONTAL LINE TO THE RIGHT)
For a given volumetric flowrate of air, the
final point depends on the amount of heat
added
The line connecting the initial status
point and the final status point is called
“PROCESS”.
In this example this is
SENSIBLE HEATING

INITIAL STATUS POINT SENSIBLE HEATING PROCESS. AIR


25 OC, DBT, 50% RH IS HEATED FROM 25 OC, TO 35 OC

4
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

2
Processes - Sensible Heating
Identify what are the changes in properties of air
from its initial condition

Sensible Heating
No Moisture Addition (Same Humidity ratio)
Dry bulb Temperature Increases
Wet Bulb Increases
RH Decreases
Enthalpy Increases
No change in Dew Point temperature

INITIAL STATUS POINT SENSIBLE HEATING PROCESS. AIR


25 OC, DBT, 50% RH IS HEATED FROM 25 OC, TO 35 OC

5
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes - Sensible Heating


When air undergoes SENSIBLE HEATING (no
change in content of moisture), the status point
shifts to the right of its initial condition
(HORIZONTAL LINE TO THE RIGHT)
For a given volumetric flowrate of air, the
final point depends on the amount of heat
added
The line connecting the initial status
point and the final status point is called
“PROCESS”.
In this example this is
SENSIBLE HEATING

INITIAL STATUS POINT SENSIBLE HEATING PROCESS. AIR


75F OC, DBT, 50% RH IS HEATED FROM 75 OF, TO 95 OF

6
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

3
Processes Sensible Cooling
(Cooling above dew-point)
When air undergoes SENSIBLE COOLING (no
change in content of moisture), the status point
shifts to the LEFT of its initial condition AND DOES
NOT CROSS SATURATION (HORIZONTAL LINE
TO THE LEFT)
For a given volumetric flowrate of air, the
final point depends on the amount of heat
removed
The line connecting the initial status INITIAL STATUS POINT
25 OC, DBT, 50% RH
point and the final status point is called
“PROCESS”.
In this example this is
SENSIBLE COOLING
SENSIBLE COOLING PROCESS. AIR
IS COOLED FROM 25 OC, TO 15 OC

7
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes Sensible Cooling


(Cooling above dew-point)
Identify what are the changes in properties of air
from its initial condition

Sensible Cooling
No Moisture Addition (No change in Humidity Ratio)
Dry bulb Temperature Decreases
Wet Bulb Decreases INITIAL STATUS POINT
RH Increases 25 OC, DBT, 50% RH
Enthalpy Decreases
No change in Dew Point Temperature

SENSIBLE COOLING PROCESS. AIR


IS COOLED FROM 25 OC, TO 15 OC

8
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

4
Processes Sensible Cooling
(Cooling above dew-point)
When air undergoes SENSIBLE COOLING (no
change in content of moisture), the status point
shifts to the LEFT of its initial condition AND DOES
NOT CROSS SATURATION (HORIZONTAL LINE
TO THE LEFT)
For a given volumetric flowrate of air, the
final point depends on the amount of heat
removed
The line connecting the initial status INITIAL STATUS POINT
75 OF, DBT, 50% RH
point and the final status point is called
“PROCESS”.
In this example this is
SENSIBLE COOLING
SENSIBLE COOLING PROCESS. AIR
IS COOLED FROM 75 OF, TO 60 OF

9
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
Air at 25 OC DBT and 50% RH is heated through an electric heater to final
state of 34 OC DBT
• Final RH is > than initial RH
• Final Humidity Ratio is < than initial Humidity Ratio
• Initial Dew point temperature = Final Dew Point temperature
• Final Enthalpy < than initial Enthalpy

CLICK HERE FOR


ANSWER
10
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

5
Processes

Quiz Time
Choose the correct / appropriate answers
Air at 25 OC DBT and 50% RH is heated through an electric heater to final
state of 34 OC DBT
• Final RH is > than initial RH
• Final Humidity Ratio is < than initial Humidity Ratio
• Initial Dew point temperature = Final Dew Point temperature
• Final Enthalpy < than initial Enthalpy

11
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
Air at 25 OC DBT and 50% RH is heated through an electric heater to final
state of 34 OC DBT
• Final WBT is > than initial WBT
• Final Specific Humidity is = initial Humidity Ratio
• Initial Dew point temperature < Final Dew Point temperature
• Final Enthalpy = initial Enthalpy

CLICK HERE FOR


ANSWER
12
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

6
Processes

Quiz Time
Choose the correct / appropriate answers
Air at 25 OC DBT and 50% RH is heated through an electric heater to final
state of 34 OC DBT
• Final WBT is > than initial WBT
• Final Specific Humidity is = initial Humidity Ratio
• Initial Dew point temperature < Final Dew Point temperature
• Final Enthalpy = initial Enthalpy

13
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
Air at 25 OC DBT and 50% RH is heated through an electric heater to final
state of 34 OC DBT, 30% RH
• Final WBT is ~~14 OC
• Final Specific Humidity is 0.30 kg/kg
• Final Dew Point temperature = ~~14 OC
• Final Enthalpy ~~ 60 kJ/kg

CLICK HERE FOR


ANSWER
14
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

7
Processes

Quiz Time
Choose the correct / appropriate answers
Air at 25 OC DBT and 50% RH is heated through an electric heater to final
state of 34 OC DBT, 30% RH
• Final WBT is ~~14 OC
• Final Specific Humidity is 0.30 kg/kg
• Final Dew Point temperature = ~~14 OC
• Final Enthalpy ~~ 60 kJ/kg

15
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
Air at 25 OC DBT and 50% RH is heated through an electric heater to final
state of 34 OC DBT, 30% RH
• Final Humidity ratio is 10 grams / kg
• Final Specific Volume ~~ is 0.88 m3/kg
• Final WBT ~~ 21 OC
• All of the above

CLICK HERE FOR


ANSWER
16
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

8
Processes

Quiz Time
Choose the correct / appropriate answers
Air at 25 OC DBT and 50% RH is heated through an electric heater to final
state of 34 OC DBT, 30% RH
• Final Humidity ratio is 10 grams / kg
• Final Specific Volume ~~ is 0.88 m3/kg
• Final WBT ~~ 21 OC
• All of the above

17
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
Air at 77 OF DBT and 50% RH is sensibly cooled to final state of 59 OF DBT,

• Final RH is > than initial RH


• Final Humidity Ratio is < than initial Humidity Ratio
• Initial Dew point temperature = Final Dew Point temperature
• Final Enthalpy < than initial Enthalpy

CLICK HERE FOR


ANSWER
18
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

9
Processes

Quiz Time
Choose the correct / appropriate answers
Air at 77 OF DBT and 50% RH is sensibly cooled to final state of 59 OF DBT,

• Final RH is > than initial RH


• Final Humidity Ratio is < than initial Humidity Ratio
• Initial Dew point temperature = Final Dew Point temperature
• Final Enthalpy < than initial Enthalpy

19
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
Air at 77 OF DBT and 50% RH is sensibly cooled to final state of 59 OF DBT,

• Final WBT is > than initial WBT


• Final Specific Humidity is = initial Humidity Ratio
• Initial Dew point temperature < Final Dew Point temperature
• Final Enthalpy = initial Enthalpy

CLICK HERE FOR


ANSWER
20
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

10
Processes

Quiz Time
Choose the correct / appropriate answers
Air at 77 OF DBT and 50% RH is sensibly cooled to final state of 59 OF DBT,

• Final WBT is > than initial WBT


• Final Specific Humidity is = initial Humidity Ratio
• Initial Dew point temperature < Final Dew Point temperature
• Final Enthalpy = initial Enthalpy

21
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
Air at 77 OF DBT and 50% RH is sensibly cooled to final state of 59 OF DBT
and approximately 93% RH,

• Final WBT is ~~52 OF


• Final Specific Humidity is ~~70 grains/lb
• Final Dew Point temperature = ~~57 OF
• Final Enthalpy ~~ 20 BTU/lb
CLICK HERE FOR
ANSWER
22
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

11
Processes

Quiz Time
Choose the correct / appropriate answers
Air at 77 OF DBT and 50% RH is sensibly cooled to final state of 59 OF DBT
and approximately 93% RH,

• Final WBT is ~~52 OF


• Final Specific Humidity is ~~70 grains/lb
• Final Dew Point temperature = ~~57 OF
• Final Enthalpy ~~ 20 BTU/lb

23
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
Air at 77 OF DBT and 50% RH is sensibly cooled to final state of 59 OF DBT
and approximately 93% RH,
• Final Humidity ratio is ~~ 0.010 lb / lb
• Final Specific Volume ~~ is 13.5 ft3/lb
• Final WBT ~~ 58 OF
• All of the above

CLICK HERE FOR


ANSWER
24
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

12
Processes

Quiz Time
Choose the correct / appropriate answers
Air at 77 OF DBT and 50% RH is sensibly cooled to final state of 59 OF DBT
and approximately 93% RH,
• Final Humidity ratio is ~~ 0.010 lb / lb
• Final Specific Volume ~~ is 13.5 ft3/lb
• Final WBT ~~ 58 OF
• All of the above

25
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes - Cooling & Dehumidification


Also known as Dehumidification by Cooling
The temperature below which further cooling of air causes
condensation is called DEW POINT TEMPERATURE

When air is cooled below its dew point moisture from the air
starts condensing

If we need to remove moisture from air (de-humidify) we


need to cool air below its dew point

Lower the temperature of air, greater is the removal


(condensation) of moisture. Ie, greater is the dehumidification
effect

26
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

13
Processes - Cooling & Dehumidification
Also known as Dehumidification by Cooling
CHW COOLING COIL DX COOLING COIL

AIR AIR
DX

FROM ONDENSER
REFRIGERANT
REFRIGERANT TO
COMPRESSOR

LIQUID
VAPOUR
WATER OUT

WATER IN
CHILLED

CHILLED

27
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes - Cooling & Dehumidification


Also known as Dehumidification by Cooling
When heat is removed from air, initially it undergoes
“sensible cooling” – till it reaches the dew point.
In this case DPT IS ~~14 OC
Air is saturated at this point and at 14 OC, it
is holding the maximum amount of moisture
it can handle at 14 OC
From this point, further heat
removal (cooling) will cause DPT ~~ 14 OC
drop in air temperature INITIAL STATUS POINT
25 OC, DBT, 50% RH
along with reduction in
specific humidity as air will DEHUMIDIFICATION
travel along the saturation
line

SENSIBLE COOLING
COOLING BELOW DPT

28
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

14
Processes - Cooling & Dehumidification
Also known as Dehumidification by Cooling
Identify what are the changes in properties of air
from its initial condition

Cooling & Dehumidification


Moisture is removed (Reduction in Humidity Ratio
- dehumidification)
Dry bulb Temperature Decreases
Wet Bulb Decreases
RH at exit of HEX is almost at saturation
Enthalpy Decreases
INITIAL STATUS POINT AS
AIR ENTERS HEX

FINAL STATUS POINT AS CHANGES TO AIR AS IT


AIR LEAVES HEX MOVES THROUGH HEX

29
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes - Cooling & Dehumidification


Also known as Dehumidification by Cooling
When heat is removed from air, initially it undergoes
“sensible cooling” – till it reaches the dew point.
In this case DPT IS ~~55 OF
Air is saturated at this point and at 55 OF, it is
holding the maximum amount of moisture it
can handle
From this point, further heat
removal (cooling) will cause DPT ~~ 55 OF
drop in air temperature INITIAL STATUS POINT
75 OF, DBT, 50% RH
along with reduction in
specific humidity as air will
travel along the saturation DEHUMIDIFICATION
line

SENSIBLE COOLING
COOLING BELOW DPT

30
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

15
Processes - Cooling & Dehumidification
Also known as Dehumidification by Cooling
Identify what are the changes in properties of air
from its initial condition

Cooling & Dehumidification


Moisture is removed (Reduction in
Humidity Ratio - dehumidification)
Dry bulb Temperature Decreases
Wet Bulb Decreases
RH at exit of HEX is almost at saturation
Enthalpy Decreases
INITIAL STATUS POINT AS
AIR ENTERS HEX

FINAL STATUS POINT AS CHANGES TO AIR AS IT


AIR LEAVES HEX MOVES THROUGH HEX
31
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 50% RH is treated to its final state of
13 OC DBT / 12 OC WBT
• Initial WBT is > Final WBT
• Final Specific Volume > Initial Specific Volume
• Final Enthalpy > Initial Enthalpy
• Initial DPT > Final DPT

CLICK HERE FOR


ANSWER
32
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

16
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 50% RH is treated to its final state of
13 OC DBT / 12 OC WBT
• Initial WBT is > Final WBT
• Final Specific Volume > Initial Specific Volume
• Final Enthalpy > Initial Enthalpy
• Initial DPT > Final DPT

33
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 50% RH is treated to its final state of
13 OC DBT / 12 OC WBT
• Initial Specific Humidity = Final Specific Humidity
• Final Specific Humidity = Final Humidity Ratio
• Final RH > Initial RH
• Initial WBT > Final WBT

CLICK HERE FOR


ANSWER
34
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

17
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 50% RH is treated to its final state of
13 OC DBT / 12 OC WBT
• Initial Specific Humidity = Final Specific Humidity
• Final Specific Humidity = Final Humidity Ratio
• Final RH > Initial RH
• Initial WBT > Final WBT

35
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 50% RH is treated to its final state of
13 OC DBT / 12 OC WBT
• Final RH = ~~ 89%
• Initial Wet Bulb = ~~ 11.3 OC
• Final Enthalpy =~~34 kJ/kg
• Initial Enthalpy = ~~ 50 kJ/kg

CLICK HERE FOR


ANSWER
36
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

18
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 50% RH is treated to its final state of
13 OC DBT / 12 OC WBT
• Final RH = ~~ 89%
• Initial Wet Bulb = ~~ 11.3 OC
• Final Enthalpy =~~34 kJ/kg
• Initial Enthalpy = ~~ 50 kJ/kg

37
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 50% RH is treated to its final state of
13 OC DBT / 12 OC WBT
• Final DPT = ~~11.3 OC
• Initial Specific Volume =~~0.86 m3/Kg
• Final DPT = ~~17.8 OC
• All of the above

CLICK HERE FOR


ANSWER
38
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

19
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 50% RH is treated to its final state of
13 OC DBT / 12 OC WBT
• Final DPT = ~~11.3 OC
• Initial Specific Volume =~~0.86 m3/Kg
• Final DPT = ~~17.8 OC
• All of the above

39
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial WBT is < Final WBT
• Final Specific Volume > Initial Specific Volume
• Final Enthalpy < Initial Enthalpy
• Initial DPT > Final DPT

CLICK HERE FOR


ANSWER
40
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

20
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial WBT is < Final WBT
• Final Specific Volume > Initial Specific Volume
• Final Enthalpy < Initial Enthalpy
• Initial DPT > Final DPT

41
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial Specific Humidity = Final Specific Humidity
• Final Specific Humidity > Final Humidity Ratio
• Final RH = Initial RH
• Initial WBT > Final WBT

CLICK HERE FOR


ANSWER
42
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

21
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial Specific Humidity = Final Specific Humidity
• Final Specific Humidity > Final Humidity Ratio
• Final RH = Initial RH
• Initial WBT > Final WBT

43
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial Specific Humidity = ~~0.010 lb / lb
• Final Specific Humidity = ~~0.008 lb / lb
• Final Humidity Ratio = ~~56 grains / lb
• Initial WBT = ~~54 OF

CLICK HERE FOR


ANSWER
44
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

22
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial Specific Humidity = ~~0.010 lb / lb
• Final Specific Humidity = ~~0.008 lb / lb
• Final Humidity Ratio = ~~56 grains / lb
• Initial WBT = ~~54 OF

45
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial Specific Humidity = ~~70 grains / lb
• Final Relative Humidity = ~~88 %
• Final Enthalpy = ~~30 BTU/ lb
• Initial WBT = ~~64 OF

CLICK HERE FOR


ANSWER
46
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

23
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial Specific Humidity = ~~70 grains / lb
• Final Relative Humidity = ~~88 %
• Final Enthalpy = ~~30 BTU/ lb
• Initial WBT = ~~64 OF

47
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial Enthalpy = ~~29 BTU / lb
• Final Enthalpy = ~~ 22.5 BTU / lb
• Final DPT = ~~52 OF
• All of the above

CLICK HERE FOR


ANSWER
48
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

24
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 50% RH is treated to its final state of
56 OF DBT / 54 OF WBT
• Initial Enthalpy = ~~29 BTU / lb
• Final Enthalpy = ~~ 22.5 BTU / lb
• Final DPT = ~~52 OF
• All of the above

49
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes
Adiabatic Humidification or Evaporative Cooling

SPRAY AIR
CHAMBER

50
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

25
Processes
Adiabatic Humidification or Evaporative Cooling
Rapidly flowing air is exposed to either a water
spray or a wet pad allowing direct heat transfer
between air and water
Moisture evaporates. For evaporation to take
place, latent heat is required
This latent heat is taken from the FINAL STATUS POINT
surrounding air thereby cooling the air ~~21.5 OC, WBT, 90% RH

Internal Heat transfer, no addition or INITIAL STATUS POINT


~~21.5 OC, WBT, 30% RH
removal of extraneous heat
Enthalpy of air remains constant as
it travels along the constant
enthalpy / constant WBT line
Final status point depends on the
saturation efficiency of the
equipment.
In this case, saturation
efficiency is 90%
51
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes
Adiabatic Humidification or Evaporative Cooling
Identify what are the changes in properties
of air from its initial condition

FINAL STATUS POINT


~~21.5 OC, WBT, 90% RH

INITIAL STATUS POINT


~~21.5 OC, WBT, 30% RH

EVAPORATIVE COOLING
No change in enthalpy.
WBT remains same
DBT reduced
Specific Humidity increases (moisture added)
RH goes up (air moves towards saturation)
TEMPERATURE MOISTURE ADDITION
REDUCTION (COOLING) (HUMIDIFICATION)
52
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

26
Processes
Adiabatic Humidification or Evaporative Cooling
Identify what are the changes in properties
of air from its initial condition

FINAL STATUS POINT


~~70 OF, WBT, 90% RH

INITIAL STATUS POINT


~~70 OF, WBT, 30% RH

EVAPORATIVE COOLING
No change in enthalpy.
WBT remains same
DBT reduced
Specific Humidity increases (moisture added)
RH goes up (air moves towards saturation)
TEMPERATURE MOISTURE ADDITION
REDUCTION (COOLING) (HUMIDIFICATION)
53
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 40 OC DBT and 25% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final DBT = Initial DBT
• Final DBT < Initial DBT
• Final WBT > Initial WBT
• Final WBT = Initial WBT

CLICK HERE FOR


ANSWER
54
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

27
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 40 OC DBT and 25% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90%
• Final DBT = Initial DBT
• Final DBT < Initial DBT
• Final WBT > Initial WBT
• Final WBT = Initial WBT

55
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 40 OC DBT and 25% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90%
• Final Humidity Ratio > Initial Humidity Ratio
• Final Enthalpy < Initial Enthalpy
• Final Enthalpy = Initial Enthalpy
• Final DPT = Initial DPT

CLICK HERE FOR


ANSWER
56
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

28
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 40 OC DBT and 25% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90%
• Final Humidity Ratio > Initial Humidity Ratio
• Final Enthalpy < Initial Enthalpy
• Final Enthalpy = Initial Enthalpy
• Final DPT = Initial DPT

57
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 40 OC DBT and 25% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90%
• Final Humidity Ratio = ~~0.0178 lb/lb
• Initial Humidity Ratio = ~~0.0115 lb/lb
• Final DPT = ~~ 23 OC
• All of the above

CLICK HERE FOR


ANSWER
58
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

29
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 40 OC DBT and 25% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90%
• Final Humidity Ratio = ~~0.0178 lb/lb
• Initial Humidity Ratio = ~~0.0115 lb/lb
• Final DPT = ~~ 23 OC
• All of the above

59
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 40 OC DBT and 25% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90%
• Initial DPT = ~~16.2 OC
• Final DBT = ~~ 23.4 OC
• Initial Enthalpy = 70 KJ / kg
• Final Enthalpy = 70 kJ / kg

CLICK HERE FOR


ANSWER
60
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

30
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 40 OC DBT and 25% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90%
• Initial DPT = ~~16.2 OC
• Final DBT = ~~ 23.4 OC
• Initial Enthalpy = 70 kJ / kg
• Final Enthalpy = 70 kJ / kg

61
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final DBT < Initial DBT
• Final DBT=Initial DBT
• Final WBT < Initial WBT
• Final Enthalpy = Initial Enthalpy

CLICK HERE FOR


ANSWER
62
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

31
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final DBT < Initial DBT
• Final DBT=Initial DBT
• Final WBT < Initial WBT
• Final Enthalpy = Initial Enthalpy

63
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final WBT = Initial WBT
• Final DPT=Initial DPT
• Final Humidity Ratio > Initial Humidity Ratio
• Final Specific Volume < Initial Specific Volume

CLICK HERE FOR


ANSWER
64
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

32
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final WBT = Initial WBT
• Final DPT=Initial DPT
• Final Humidity Ratio > Initial Humidity Ratio
• Final Specific Volume < Initial Specific Volume

65
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final DPT= ~~ 74 OF
• Initial DPT = ~~ 74 OF
• Final WBT = ~~ 75 OF
• All of the above

CLICK HERE FOR


ANSWER
66
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

33
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final DPT= ~~ 74 OF
• Initial DPT = ~~ 74 OF
• Final WBT = ~~ 75 OF
• All of the above

67
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final DBT= ~~ 77 OF
• Initial DPT = ~~ 64 OF
• Initial WBT = ~~ 75 OF
• All of the above

CLICK HERE FOR


ANSWER
68
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

34
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• Final DBT= ~~ 77 OF
• Initial DPT = ~~ 64 OF
• Initial WBT = ~~ 75 OF
• All of the above

69
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• The moisture reduction in the process is ~~ 0.053 lb/lb
• The moisture reduction in the process is ~~ 0.053 kg/kg
• The temperature reduction in the process is ~~ 24 OF
• All of the above

CLICK HERE FOR


ANSWER
70
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

35
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 101 OF DBT and 30% RH is treated with a spray of
water. The efficiency of the spray chamber is able to saturate the air to 90% .
• The moisture reduction in the process is ~~ 0.053 lb/lb
• The moisture reduction in the process is ~~ 0.053 kg/kg
• The temperature reduction in the process is ~~ 24 OF
• All of the above

71
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes
Adiabatic De-Humidification / Chemical Dehumidification

WET AIR COOLING COIL DESSICANAT DE-HUMIDIFER DRY AIR

72
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

36
Processes
Adiabatic De-Humidification / Chemical Dehumidification
Air passes through a chemical chamber that
has high affinity for moisture
Moisture in the air is removed by chemicals.
The final status point is the process
requirement for which the quantity of chemicals
are added appropriately
INITIAL STATUS POINT
Internal Heat transfer, no addition or removal of ~~20 OC, WBT, 60% RH
extraneous heat
Enthalpy of air remains constant as it travels
along the constant enthalpy / constant WBT
line
In this case, the final status point is 25% RH

FINAL STATUS POINT


~~20 OC, WBT, 25% RH

73
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes
Adiabatic De-Humidification / Chemical Dehumidification
Identify what are the changes in properties
of air from its initial condition

INITIAL STATUS POINT


~~20 OC, WBT, 60% RH

CHEMICAL DEHUMIDIFICATION
No change in enthalpy.
WBT remains same
DBT is increased FINAL STATUS POINT
Specific Humidity decreases (moisture removed) ~~20 OC, WBT, 25% RH
RH goes down (air moves away from saturation)

74
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

37
Processes
Adiabatic De-Humidification / Chemical Dehumidification
Identify what are the changes in properties
of air from its initial condition

INITIAL STATUS POINT


~~68 OF, WBT, 60% RH

CHEMICAL DEHUMIDIFICATION
No change in enthalpy.
WBT remains same
DBT is increased FINAL STATUS POINT
Specific Humidity decreases (moisture removed) ~~68 OF, WBT, 25% RH
RH goes down (air moves away from saturation)

75
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 20 OC WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 20% RH
• Final WBT = Initial WBT
• Final DPT < Initial DPT
• Final DBT > Initial DBT
• All of the above

CLICK HERE FOR


ANSWER
76
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

38
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 20 OC WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 20% RH
• Final WBT = Initial WBT
• Final DPT < Initial DPT
• Final DBT > Initial DBT
• All of the above

77
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 20 OC WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 20% RH
• Final Enthalpy > Initial Enthalpy
• Final Humidity Ratio > Initial Specific Humidity
• Initial Specific Volume > Final Specific Volume
• None of the above

CLICK HERE FOR


ANSWER
78
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

39
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 20 OC WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 20% RH
• Final Enthalpy > Initial Enthalpy
• Final Humidity Ratio > Initial Specific Humidity
• Initial Specific Volume > Final Specific Volume
• None of the above

79
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 20 OC WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 20% RH
• Final Enthalpy = ~~ 57 kJ/kg
• Final Humidity Ratio = 0.0126 kg/kg
• Initial DPT = ~~ 17.6 OC
• Final Specific Volume = ~~ 0.86 m3/kg

CLICK HERE FOR


ANSWER
80
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

40
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 20 OC WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 20% RH
• Final Enthalpy = ~~ 57 kJ/kg
• Final Humidity Ratio = 0.0126 kg/kg
• Initial DPT = ~~ 17.6 OC
• Final Specific Volume = ~~ 0.86 m3/kg

81
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 20 OC WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 20% RH
• Enthalpy Increase through the process = ~~ 0 Btu/lb (zero)
• Humidity Ratio increase through the process = 0.0077 kg/kg
• Final DBT = ~~ 36.8 OC
• Final DPT= ~~ 17.6 OC

CLICK HERE FOR


ANSWER
82
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

41
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 25 OC DBT and 20 OC WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 20% RH
• Enthalpy Increase through the process = ~~ 0 Btu/lb (zero)
• Humidity Ratio increase through the process = 0.0077 kg/kg
• Final DBT = ~~ 36.8 OC
• Final DPT= ~~ 17.6 OC

83
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 68 OF WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 30% RH
• Final WBT > Initial WBT
• Final WBT < Initial WBT
• Final DBT < Initial DBT
• None of the above

CLICK HERE FOR


ANSWER
84
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

42
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 68 OF WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 30% RH
• Final WBT > Initial WBT
• Final WBT < Initial WBT
• Final DBT < Initial DBT
• None of the above

85
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 68 OF WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 30% RH
• Final WBT = Initial WBT
• Final DPT < Initial DPT
• Final Enthalpy = Initial Enthalpy
• All of the above

CLICK HERE FOR


ANSWER
86
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

43
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 68 OF WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 30% RH
• Final WBT = Initial WBT
• Final DPT < Initial DPT
• Final Enthalpy = Initial Enthalpy
• All of the above

87
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 68 OF WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 30% RH
• Final DBT = ~~91.5 OF
• Initial RH = ~~ 63.5%
• Final DPT = ~~ 55.8 OF
• Initial Specific Volume = ~~ 14.1 ft3/lb

CLICK HERE FOR


ANSWER
88
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

44
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 68 OF WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 30% RH
• Final DBT = ~~91.5 OF
• Initial RH = ~~ 63.5%
• Final DPT = ~~ 55.8 OF
• Initial Specific Volume = ~~ 14.1 ft3/lb

89
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 68 OF WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 30% RH
• Temperature decrease through the process is 14.5 OF
• Moisture reduction through the process is 3.2 grams / kg
• Moisture reduction through the process is 22.4 grains / lb
• Final Specific Volume = ~~ 14.1 ft3/lb

CLICK HERE FOR


ANSWER
90
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

45
Processes

Quiz Time
Choose the correct / appropriate answers
The initial state of air at 77 OF DBT and 68 OF WBT is sent through a
desiccant chamber for de-humidification. Air that is let out of the chamber is
at approximately at 30% RH
• Temperature decrease through the process is 14.5 OF
• Moisture reduction through the process is 3.2 grams / kg
• Moisture reduction through the process is 22.4 grains / lb
• Final Specific Volume = ~~ 14.1 ft3/lb
Temperature increase is 14,5 OF

91
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes AIR MIXING

RA (Mass M1, Temperature T1)

FILTER COIL FAN

Conditioned Space
OA
(Mass M2,
Temperature T2

For the mixing of 2 equal substances (Specific Heat being same)

Tmix = (m1T1 + m2T2) / (m1+m2)


92
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

46
Processes AIR MIXING
The Status point of the final mixing condition
will always be on the line connecting the initial
status points of the two air streams
At what point on this line the mixture
status will be depends on the mass /
volumetric flow rate of the two streams 10% OUTSIDE AIR

The mixture condition will be in


inverse proportion to the larger of the
two masses
If RA is 90% of the total air quantity,
the mixture status point will be at
10% away from the RA status point
and vice-versa

90% ROOM AIR

93
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes AIR MIXING


To identify the Mixture conditions:-
Measure linear distance of the line
representing the two air streams
Measure 0.1*X from RA condition or
0.9*X from OA conditions and mark 0.9 “X” 10% OUTSIDE AIR
a point

0.1 “X” 90% ROOM AIR MIXED AIR

94
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

47
Processes

Quiz Time
Choose the correct / appropriate answers
10% of OA at 45 OC DBT and 16 grams /kg mixes with RA @ 25 OC and 50%
RH

• The enthalpy of OA is 86.6 kJ/kg


• The RH of room air is lesser than RH of outside air
• The DPT of OA is greater than DPT of room air
• Specific Humidity of RA is ~~0.01 lb/lb

CLICK HERE FOR


ANSWER

95
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
10% of OA at 45 OC DBT and 16 grams /kg mixes with RA @ 25 OC and 50%
RH

• The enthalpy of OA is 86.6 kJ/kg


• The RH of room air is lesser than RH of outside air
• The DPT of OA is greater than DPT of room air
• Specific Humidity of RA is ~~0.01 lb/lb

96
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

48
Processes

Quiz Time
Choose the correct / appropriate answers
10% of OA at 45 OC DBT and 16 grams /kg mixes with RA @ 25 OC and 50%
RH

• The enthalpy of mixture is ~~ 53.8 kJ/kg


• DPT of mixture is ~~ 14.8 OC
• The DPT of RA is ~~ 13.9 OC
• All of the above

CLICK HERE FOR


ANSWER

97
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
10% of OA at 45 OC DBT and 16 grams /kg mixes with RA @ 25 OC and 50%
RH

• The enthalpy of mixture is ~~ 53.8 kJ/kg


• DPT of mixture is ~~ 14.8 OC
• The DPT of RA is ~~ 13.9 OC
• All of the above

98
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

49
Processes

Quiz Time
Choose the correct / appropriate answers
10% of OA at 45 OC DBT and 16 grams /kg mixes with RA @ 25 OC and 50%
RH

• WBT mixture is ~~ 19 OC
• WBT RA is ~~ 17.8 OC
• The RH of mixture is ~~ 27% OC
• Specific Volume OA is ~~ 0.92 m3/kg

CLICK HERE FOR


ANSWER

99
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
10% of OA at 45 OC DBT and 16 grams /kg mixes with RA @ 25 OC and 50%
RH

• WBT mixture is ~~ 19 OC
• WBT RA is ~~ 17.8 OC
• The RH of mixture is ~~ 27% OC
• Specific Volume OA is ~~ 0.92 m3/kg

100
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

50
Processes

Quiz Time
Choose the correct / appropriate answers
OA at 110 OF DBT and 30% RH mixes with RA @ 77 OF and 50% RH where
the mixture DBT is 92 OF

• The enthalpy of OA is 44.9 BTU/lb


• The RH of room air is greater than RH of outside air
• The DPT of OA is lesser than DPT of room air
• Specific Humidity of RA is ~~0.01 kg/kg

CLICK HERE FOR


ANSWER

101
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
OA at 110 OF DBT and 30% RH mixes with RA @ 77 OF and 50% RH where
the mixture DBT is 92 OF

• The enthalpy of OA is 44.9 BTU/lb


• The RH of room air is greater than RH of outside air
• The DPT of OA is lesser than DPT of room air
• Specific Humidity of RA is ~~0.01 kg/kg

102
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

51
Processes

Quiz Time
Choose the correct / appropriate answers
OA at 110 OF DBT and 30% RH mixes with RA @ 77 OF and 50% RH where
the mixture DBT is 92 OF

• The DPT of RA is ~~57 OF


• The WBT of OA is ~~81.1 OF
• The percentage of OA is ~~ 58.8%
• The percentage of RA is ~~ 54.5%

CLICK HERE FOR


ANSWER

103
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
OA at 110 OF DBT and 30% RH mixes with RA @ 77 OF and 50% RH where
the mixture DBT is 92 OF

• The DPT of RA is ~~57 OF


• The WBT of OA is ~~81.1 OF
• The percentage of OA is ~~ 58.8%
• The percentage of RA is ~~ 54.5%

104
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

52
Processes

Quiz Time
Choose the correct / appropriate answers
OA at 110 OF DBT and 30% RH mixes with RA @ 77 OF and 50% RH where
the mixture DBT is 92 OF

• The DPT of mixture is ~~64 OF


• The WBT of mixture is ~~72.5 OF
• The enthalpy of mixture is ~~ 36.2 BTU/lb
• All of the above

CLICK HERE FOR


ANSWER

105
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

Processes

Quiz Time
Choose the correct / appropriate answers
OA at 110 OF DBT and 30% RH mixes with RA @ 77 OF and 50% RH where
the mixture DBT is 92 OF

• The DPT of mixture is ~~64 OF


• The WBT of mixture is ~~72.5 OF
• The enthalpy of mixture is ~~ 36.2 BTU/lb
• All of the above

106
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

53
Summary :
PSYCHROMETRY – 02 (OF 4)
 How to use the Psychrometric Chart to the extent of
 Marking a process
 Change in properties after air is treated
 Various process with focus on
 Sensible Heating
 Sensible cooling
 Cooling and Dehumidification
 Evaporative Cooling
 Adiabatic Dehumidification
 Air mixing

107
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

References / Acknowledgements
 Various IP & SI Psychrometric Charts
 https://www.google.co.in/
 http://www.sugartech.co.za/psychro/
 Training Notes – Sigma Solutions – Sekar Ram

108
IIE-ICP-DIPLOMA-RAC-002.01B-PSYCHROMETRY, HEAT LOAD ESTIMATION FOR AC & R, TOPIC 02B-PSYCHROMETRY-02 (OF 4)

54
RAC 002.01 B – PSYCHROMETRY - PROCESSES