The loading from the column to the pile is analyzed by using the software Esteem.
Design data as following:
Beam size = 200mm x 200mm
Column size = 200mm x 600mm
Slab thickness = 300mm
From the result analysis of software Esteem, the axial force applied to each of the column is
tabled as the following:
To easy the works, the loading of the column to the pile with the same applied force will be
categorized together.
C1 (2,B)
P1 76.04 C3 (2,D)
C10 (8,B)
C12 (8,D)
C2 (2,C)
P2 106.82 C11 (8,C)
C4 (4,B)
P3 174.47 C6 (4,D)
C7 (6,B)
C9 (6,D)
C5 (4,C)
P4 202.23 C8 (6,C)
19
Foundation design calculation has been done in the work sheet by manual calculation and attach
at the appendix.
Pile Location Pile Length, l (m) Applied Axial Force, kN Pile Capacity, kN
References