Diseño de Vigas Con alma compacta y ala esbelta


1.1 Eje A-A (Tramo Eje 1-1, Eje 2-2)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm Mu= >
3.230 Tm CUMPLE

1.2 Eje A-A (Tramo Eje 2-2, Eje 3-3)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm Mu= 1.730 Tm CUMPLE
1.3 Eje A-A (Tramo Eje 3-3, Eje 4-4)
>
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm Mu= 2.320 Tm CUMPLE
1.4 Eje B-B (Tramo Eje 1-1, Eje 2-2) >
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm Mu= 7.630 Tm CUMPLE
1.5 Eje B-B (Tramo Eje 2-2, Eje 3-3)
Datos: > I
Perfil Tipo E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm Mu= 7.190 Tm CUMPLE
1.6 Eje B-B (Tramo Eje 3-3, Eje 4-4)
Datos: > I
Perfil Tipo E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm Mu= 5.240 Tm CUMPLE
1.7 Eje C-C (Tramo Eje 1-1, Eje 2-2)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm > Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm Mu= 7.630 Tm CUMPLE
1.8 Eje C-C (Tramo Eje 2-2, Eje 3-3)
Datos: Perfil Tipo
> I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm Mu= 2.810 Tm CUMPLE
1.9 Eje C-C (Tramo Eje 3-3, Eje 4-4)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm
> Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm Mu= 5.280 Tm CUMPLE
1.10 D-D (Tramo Eje 1-1, Eje 2-2)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm > Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm Mu= 3.140 Tm CUMPLE

1.11 Eje D-D (Tramo Eje 2-2, Eje 3-3)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm > Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm Mu= 1.670 Tm CUMPLE
1.12 Eje D-D (Tramo Eje 3-3, Eje 4-4)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
>
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm Mu= 2.300 Tm CUMPLE
1.13 Eje 1-1 (Tramo Eje A-A, Eje B-B)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 27.00 cm Fy= 2500 kg/cm²
tf= 0.35 cm > A= 60.395 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.650 cm
ALA= 10.86 28.588 Ix= 3112.6611 cm⁴
b/t = 38.57 - Sx= 311.266 cm³
Esbelto Zx= 385.906 cm³
ALMA= 108.06 162.95 0.011 0.147533407 Iy= 1149.262 cm⁴
h/tw= 8.98 - Sy= 85.131 cm³
Compacto λ= 38.571 m Zy= 149.879 cm³
Mp= 9.648 Tm λ² 1487.755 m ϒy= 4.362 cm
Mr= 5.447 Tm kc= 1.311 m J= 65.868 cm⁴
Mn= 5.046 Tm Cw= 110834.050 cm⁶ rts= 6.022 cm
ɸMn= 4.54 Tm Mu= 4.150 Tm CUMPLE
1.14 Eje 1-1 (Tramo Eje B-B, Eje C-C)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 27.00 cm Fy= 2500 kg/cm²
>
tf= 0.35 cm A= 60.395 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.650 cm
ALA= 10.86 28.588 Ix= 3112.6611 cm⁴
b/t = 38.57 - Sx= 311.266 cm³
Esbelto Zx= 385.906 cm³
ALMA= 108.06 162.95 0.011 0.147533407 Iy= 1149.262 cm⁴
h/tw= 8.98 - Sy= 85.131 cm³
Compacto λ= 38.571 m Zy= 149.879 cm³
Mp= 9.648 Tm λ² 1487.755 m ϒy= 4.362 cm
Mr= 5.447 Tm kc= 1.311 m J= 65.868 cm⁴
Mn= 5.046 Tm Cw= 110834.050 cm⁶ rts= 6.022 cm
ɸMn= 4.54 Tm Mu= 3.420 Tm CUMPLE

1.15 Eje 1-1 (Tramo Eje C-C, Eje D-D)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 27.00 cm Fy= 2500 kg/cm²
tf= 0.35 cm > A= 60.395 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.650 cm
ALA= 10.86 28.588 Ix= 3112.6611 cm⁴
b/t = 38.57 - Sx= 311.266 cm³
Esbelto Zx= 385.906 cm³
ALMA= 108.06 162.95 0.011 0.147533407 Iy= 1149.262 cm⁴
h/tw= 8.98 - Sy= 85.131 cm³
Compacto λ= 38.571 m Zy= 149.879 cm³
Mp= 9.648 Tm λ² 1487.755 m ϒy= 4.362 cm
Mr= 5.447 Tm kc= 1.311 m J= 65.868 cm⁴
Mn= 5.046 Tm Cw= 110834.050 cm⁶ rts= 6.022 cm
ɸMn= 4.54 Tm Mu= 4.180 Tm CUMPLE
1.16 Eje 2-2 (Tramo Eje A-A, Eje B-B)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 60.88 cm²
>
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3150.7669 cm⁴
b/t = 30.63 - Sx= 315.077 cm³
Esbelto Zx= 390.224 cm³
ALMA= 108.06 162.95 0.01091 0.146957974 Iy= 981.412 cm⁴
h/tw= 8.93 - Sy= 80.115 cm³
Compacto λ= 30.625 m Zy= 142.238 cm³
Mp= 9.756 Tm λ² 937.891 m ϒy= 4.015 cm
Mr= 5.514 Tm kc= 1.311 m J= 65.976 cm⁴
Mn= 8.102 Tm Cw= 94158.416 cm⁶ rts= 5.524 cm
ɸMn= 7.29 Tm Mu= 6.680 Tm CUMPLE
1.17 Eje 2-2 (Tramo Eje B-B, Eje C-C)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm > A= 60.88 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3150.7669 cm⁴
b/t = 30.63 - Sx= 315.077 cm³
Esbelto Zx= 390.224 cm³
ALMA= 108.06 162.95 0.01091 0.146957974 Iy= 981.412 cm⁴
h/tw= 8.93 - Sy= 80.115 cm³
Compacto λ= 30.625 m Zy= 142.238 cm³
Mp= 9.756 Tm λ² 937.891 m ϒy= 4.015 cm
Mr= 5.514 Tm kc= 1.311 m J= 65.976 cm⁴
Mn= 8.102 Tm Cw= 94158.416 cm⁶ rts= 5.524 cm
ɸMn= 7.29 Tm Mu= 3.500 Tm CUMPLE
1.18 Eje 2-2 (Tramo Eje C-C, Eje D-D)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm > A= 60.88 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3150.7669 cm⁴
b/t = 30.63 - Sx= 315.077 cm³
Esbelto Zx= 390.224 cm³
ALMA= 108.06 162.95 0.01091 0.146957974 Iy= 981.412 cm⁴
h/tw= 8.93 - Sy= 80.115 cm³
Compacto λ= 30.625 m Zy= 142.238 cm³
Mp= 9.756 Tm λ² 937.891 m ϒy= 4.015 cm
Mr= 5.514 Tm kc= 1.311 m J= 65.976 cm⁴
Mn= 8.102 Tm Cw= 94158.416 cm⁶ rts= 5.524 cm
ɸMn= 7.29 Tm Mu= 7.040 Tm CUMPLE

1.19 3-3 (Tramo Eje A-A, Eje B-B)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm > A= 58 cm²
tw= 2.00 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3062.2933 cm⁴
b/t = 30.63 - Sx= 306.229 cm³
Esbelto Zx= 376.400 cm³
ALMA= 108.06 162.95 0.00916 0.134310726 Iy= 981.542 cm⁴
h/tw= 9.60 - Sy= 80.126 cm³
Compacto λ= 30.625 m Zy= 139.250 cm³
Mp= 9.410 Tm λ² 937.891 m ϒy= 4.114 cm
Mr= 5.359 Tm kc= 1.265 m J= 53.312 cm⁴
Mn= 7.595 Tm Cw= 94158.416 cm⁶ rts= 5.603 cm
ɸMn= 6.84 Tm Mu= 5.950 Tm CUMPLE

1.20 Eje 3-3 (Tramo Eje B-B, Eje C-C)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 58 cm²
tw= 2.00 cm
> C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3062.2933 cm⁴
b/t = 30.63 - Sx= 306.229 cm³
Esbelto Zx= 376.400 cm³
ALMA= 108.06 162.95 0.00916 0.134310726 Iy= 981.542 cm⁴
h/tw= 9.60 - Sy= 80.126 cm³
Compacto λ= 30.625 m Zy= 139.250 cm³
Mp= 9.410 Tm λ² 937.891 m ϒy= 4.114 cm
Mr= 5.359 Tm kc= 1.265 m J= 53.312 cm⁴
Mn= 7.595 Tm Cw= 94158.416 cm⁶ rts= 5.603 cm
ɸMn= 6.84 Tm Mu= 3.320 Tm CUMPLE

1.21 Eje 3-3 (Tramo Eje C-C, Eje D-D)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 58 cm²
>
tw= 2.00 cm > C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3062.2933 cm⁴
b/t = 30.63 - Sx= 306.229 cm³
Esbelto Zx= 376.400 cm³
ALMA= 108.06 162.95 0.00916 0.134310726 Iy= 981.542 cm⁴
h/tw= 9.60 - Sy= 80.126 cm³
Compacto λ= 30.625 m Zy= 139.250 cm³
Mp= 9.410 Tm λ² 937.891 m ϒy= 4.114 cm
Mr= 5.359 Tm kc= 1.265 m J= 53.312 cm⁴
Mn= 7.595 Tm Cw= 94158.416 cm⁶ rts= 5.603 cm
ɸMn= 6.84 Tm Mu= 6.320 Tm CUMPLE
1.22 4-4 (Tramo Eje A-A, Eje B-B)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.00 cm Fy= 2500 kg/cm²
tf= 0.37 cm A= 60.132 cm²
tw= 2.20 cm C= 1 -
d= 20.00 cm
> ho= 19.630 cm
ALA= 10.86 28.588 Ix= 3020.9144 cm⁴
b/t = 32.43 - Sx= 302.091 cm³
Esbelto Zx= 378.336 cm³
ALMA= 108.06 162.95 0.01209 0.154850107 Iy= 853.490 cm⁴
h/tw= 8.75 - Sy= 71.124 cm³
Compacto λ= 32.432 m Zy= 129.865 cm³
Mp= 9.458 Tm λ² 1051.863 m ϒy= 3.767 cm
Mr= 5.287 Tm kc= 1.327 m J= 70.484 cm⁴
Mn= 7.006 Tm Cw= 82123.000 cm⁶ rts= 5.264 cm
ɸMn= 6.31 Tm Mu= 5.800 Tm CUMPLE
1.23 Eje 4-4 (Tramo Eje B-B, Eje C-C)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.00 cm Fy= 2500 kg/cm²
tf= 0.37 cm A= 60.132 cm²
tw= 2.20 cm > C= 1 -
d= 20.00 cm ho= 19.630 cm
ALA= 10.86 28.588 Ix= 3020.9144 cm⁴
b/t = 32.43 - Sx= 302.091 cm³
Esbelto Zx= 378.336 cm³
ALMA= 108.06 162.95 0.01209 0.154850107 Iy= 853.490 cm⁴
h/tw= 8.75 - Sy= 71.124 cm³
Compacto λ= 32.432 m Zy= 129.865 cm³
Mp= 9.458 Tm λ² 1051.863 m ϒy= 3.767 cm
Mr= 5.287 Tm kc= 1.327 m J= 70.484 cm⁴
Mn= 7.006 Tm Cw= 82123.000 cm⁶ rts= 5.264 cm
ɸMn= 6.31 Tm Mu= 4.630 Tm CUMPLE
1.24 Eje 4-4 (Tramo Eje C-C, Eje D-D)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.00 cm Fy= 2500 kg/cm²
tf= 0.37 cm A= 60.132 cm²
tw= 2.20 cm > C= 1 -
d= 20.00 cm ho= 19.630 cm
ALA= 10.86 28.588 Ix= 3020.9144 cm⁴
b/t = 32.43 - Sx= 302.091 cm³
Esbelto Zx= 378.336 cm³
ALMA= 108.06 162.95 0.01209 0.154850107 Iy= 853.490 cm⁴
h/tw= 8.75 - Sy= 71.124 cm³
Compacto λ= 32.432 m Zy= 129.865 cm³
Mp= 9.458 Tm λ² 1051.863 m ϒy= 3.767 cm
Mr= 5.287 Tm kc= 1.327 m J= 70.484 cm⁴
Mn= 7.006 Tm Cw= 82123.000 cm⁶ rts= 5.264 cm
ɸMn= 6.31 Tm Mu= 5.820 Tm CUMPLE
2. Diseño de Columnas Tubulares Compactas
2.1 Columna A1 (Piso 1)
Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 30.00 cm fy= 2500 kg/cm²
d= 30.00 cm A= 38.700 cm²
tf= 0.50 cm Ix=Iy= 7137.225 cm⁴
tw= 0.15 cm Sx=Sy= 475.815 cm³
Lb= 2.000 m Pu/ɸc.Pn= 0.299 Zx=Zy= 505.575 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.276 rx=ry= 13.580 cm
Mu= ux/ɸb.Mn= 0.276 J= 6049.245 cm⁴
2.960 2.960
Pu= 24.23 Ton Lp= 13.808 m
Ala= 32.02 40.023206 Mp= 12.639 Tm k= 1.200 -
b/t= 58.00 - Mn= 11.895375 Tm e= 17.673 -
ESBELTO ɸMn= 10.706 Tm λc= 0.197 -
Alma= 69.18 162.95163 % de %(x-x)= 55% fcr= 2.460 Ton/cm²
h/t= 198.00 - Trabajo %(y-y)= 55% ɸc.Pn= 80.915 Ton
ESBELTO CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.2 Columna A2 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 30.00 cm fy= 2500 kg/cm²
d= 30.00 cm A= 38.700 cm²
tf= 0.50 cm Ix=Iy= 7137.225 cm⁴
tw= 0.15 cm Sx=Sy= 475.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.492 Zx=Zy= 505.575 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.279 rx=ry= 13.580 cm
Mu=
2.982 2.982 ux/ɸb.Mn= 0.279 J= 6049.245 cm⁴
Pu= 39.01 Ton Lp= 13.808 m
Ala= 32.02 40.023206 Mp= 12.639 Tm k= 1.200 -
b/t= 58.00 - Mn= 11.895375 Tm e= 26.509 -
esbelta ɸMn= 10.706 Tm λc= 0.295 -
Alma= 69.18 162.95163 % de %(x-x)= 74% fcr= 2.410 Ton/cm²
h/t= 198.00 - Trabajo %(y-y)= 74% ɸc.Pn= 79.293 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.3 Columna A3 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 30.00 cm fy= 2500 kg/cm²
d= 30.00 cm A= 38.700 cm²
tf= 0.50 cm Ix=Iy= 7137.225 cm⁴
tw= 0.15 cm Sx=Sy= 475.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.528 Zx=Zy= 505.575 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.279 rx=ry= 13.580 cm
Mu=
2.986 2.986 ux/ɸb.Mn= 0.279 J= 6049.245 cm⁴
Pu= 41.84 Ton Lp= 13.808 m
Ala= 32.02 40.023206 Mp= 12.639 Tm k= 1.200 -
b/t= 58.00 - Mn= 11.895375 Tm e= 26.509 -
esbelta ɸMn= 10.706 Tm λc= 0.295 -
Alma= 69.18 162.95163 % de %(x-x)= 78% fcr= 2.410 Ton/cm²
h/t= 198.00 - Trabajo %(y-y)= 78% ɸc.Pn= 79.293 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.4 Columna A4 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 30.00 cm fy= 2500 kg/cm²
d= 30.00 cm A= 38.700 cm²
tf= 0.50 cm Ix=Iy= 7137.225 cm⁴
tw= 0.15 cm Sx=Sy= 475.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.191 Zx=Zy= 505.575 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.231 rx=ry= 13.580 cm
Mu=
2.470 2.470 ux/ɸb.Mn= 0.231 J= 6049.245 cm⁴
Pu= 15.11 Ton Lp= 13.808 m
Ala= 32.02 40.023206 Mp= 12.639 Tm k= 1.200 -
b/t= 58.00 - Mn= 11.895375 Tm e= 26.509 -
esbelta ɸMn= 10.706 Tm λc= 0.295 -
Alma= 69.18 162.95163 % de %(x-x)= 33% fcr= 2.410 Ton/cm²
h/t= 198.00 - Trabajo %(y-y)= 33% ɸc.Pn= 79.293 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.5 Columna B1 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 40.00 cm fy= 2500 kg/cm²
d= 40.00 cm A= 51.700 cm²
tf= 0.50 cm Ix=Iy= 17086.308 cm⁴
tw= 0.15 cm Sx=Sy= 854.315 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.434 Zx=Zy= 904.075 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.208 rx=ry= 18.179 cm
Mu=
4.000 4.000 ux/ɸb.Mn= 0.208 J= 14445.897 cm⁴
Pu= 46.77 Ton Lp= 18.463 m
Ala= 32.02 40.023206 Mp= 22.602 Tm k= 1.200 -
b/t= 78.00 - Mn= 21.3578854 Tm e= 19.803 -
esbelta ɸMn= 19.222 Tm λc= 0.220 -
Alma= 69.18 162.95163 % de %(x-x)= 62% fcr= 2.450 Ton/cm²
h/t= 264.67 - Trabajo %(y-y)= 62% ɸc.Pn= 107.650 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.6 Columna B2 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 55.00 cm fy= 2500 kg/cm²
d= 55.00 cm A= 71.200 cm²
tf= 0.50 cm Ix=Iy= 44778.683 cm⁴
tw= 0.15 cm Sx=Sy= 1628.316 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.690 Zx=Zy= 1717.450 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.181 rx=ry= 25.078 cm
Mu=
6.630 6.630 ux/ɸb.Mn= 0.181 J= 37781.963 cm⁴
Pu= 103.27 Ton Lp= 25.445 m
Ala= 32.02 40.023206 Mp= 42.936 Tm k= 1.200 -
b/t= 108.00 - Mn= 40.7078939 Tm e= 14.355 -
esbelta ɸMn= 36.637 Tm λc= 0.160 -
Alma= 69.18 162.95163 % de %(x-x)= 85% fcr= 2.473 Ton/cm²
h/t= 364.67 - Trabajo %(y-y)= 85% ɸc.Pn= 149.691 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.7 Columna B3 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 55.00 cm fy= 2500 kg/cm²
d= 55.00 cm A= 71.200 cm²
tf= 0.50 cm Ix=Iy= 44778.683 cm⁴
tw= 0.15 cm Sx=Sy= 1628.316 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.727 Zx=Zy= 1717.450 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.166 rx=ry= 25.078 cm
Mu=
6.073 6.073 ux/ɸb.Mn= 0.166 J= 37781.963 cm⁴
Pu= 108.78 Ton Lp= 25.445 m
Ala= 32.02 40.023206 Mp= 42.936 Tm k= 1.200 -
b/t= 108.00 - Mn= 40.7078939 Tm e= 14.355 -
esbelta ɸMn= 36.637 Tm λc= 0.160 -
Alma= 69.18 162.95163 % de %(x-x)= 87% fcr= 2.473 Ton/cm²
h/t= 364.67 - Trabajo %(y-y)= 87% ɸc.Pn= 149.691 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.8 Columna B4 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 33.00 cm fy= 2500 kg/cm²
d= 33.00 cm A= 42.600 cm²
tf= 0.50 cm Ix=Iy= 9533.950 cm⁴
tw= 0.15 cm Sx=Sy= 577.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.733 Zx=Zy= 613.050 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.185 rx=ry= 14.960 cm
Mu=
2.400 2.400 ux/ɸb.Mn= 0.185 J= 8073.355 cm⁴
Pu= 64.37 Ton Lp= 15.205 m
Ala= 32.02 40.023206 Mp= 15.326 Tm k= 1.200 -
b/t= 64.00 - Mn= 14.4453788 Tm e= 24.064 -
esbelta ɸMn= 13.001 Tm λc= 0.268 -
Alma= 69.18 162.95163 % de %(x-x)= 90% fcr= 2.426 Ton/cm²
h/t= 218.00 - Trabajo %(y-y)= 90% ɸc.Pn= 87.845 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN
2.9 Columna C1 (Piso 1)
Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 30.00 cm fy= 2500 kg/cm²
d= 30.00 cm A= 38.700 cm²
tf= 0.50 cm Ix=Iy= 7137.225 cm⁴
tw= 0.15 cm Sx=Sy= 475.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.609 Zx=Zy= 505.575 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.374 rx=ry= 13.580 cm
Mu=
4.000 4.000 ux/ɸb.Mn= 0.374 J= 6049.245 cm⁴
Pu= 48.30 Ton Lp= 13.808 m
Ala= 32.02 40.023206 Mp= 12.639 Tm k= 1.200 -
b/t= 58.00 - Mn= 11.895375 Tm e= 26.509 -
esbelta ɸMn= 10.706 Tm λc= 0.295 -
Alma= 69.18 162.95163 % de %(x-x)= 94% fcr= 2.410 Ton/cm²
h/t= 198.00 - Trabajo %(y-y)= 94% ɸc.Pn= 79.293 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.10 Columna C2 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 45.00 cm fy= 2500 kg/cm²
d= 45.00 cm A= 58.200 cm²
tf= 0.50 cm Ix=Iy= 24408.350 cm⁴
tw= 0.15 cm Sx=Sy= 1084.816 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.581 Zx=Zy= 1146.450 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.227 rx=ry= 20.479 cm
Mu=
5.550 5.550 ux/ɸb.Mn= 0.227 J= 20619.364 cm⁴
Pu= 70.70 Ton Lp= 20.790 m
Ala= 32.02 40.023206 Mp= 28.661 Tm k= 1.200 -
b/t= 88.00 - Mn= 27.1203889 Tm e= 17.579 -
esbelta ɸMn= 24.408 Tm λc= 0.196 -
Alma= 69.18 162.95163 % de %(x-x)= 78% fcr= 2.460 Ton/cm²
h/t= 298.00 - Trabajo %(y-y)= 78% ɸc.Pn= 121.708 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.11 Columna C3 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 40.00 cm fy= 2500 kg/cm²
d= 40.00 cm A= 51.700 cm²
tf= 0.50 cm Ix=Iy= 17086.308 cm⁴
tw= 0.15 cm Sx=Sy= 854.315 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.568 Zx=Zy= 904.075 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.203 rx=ry= 18.179 cm
Mu=
3.900 3.900 ux/ɸb.Mn= 0.203 J= 14445.897 cm⁴
Pu= 61.11 Ton Lp= 18.463 m
Ala= 32.02 40.023206 Mp= 22.602 Tm k= 1.200 -
b/t= 78.00 - Mn= 21.3578854 Tm e= 19.803 -
esbelta ɸMn= 19.222 Tm λc= 0.220 -
Alma= 69.18 162.95163 % de %(x-x)= 75% fcr= 2.450 Ton/cm²
h/t= 264.67 - Trabajo %(y-y)= 75% ɸc.Pn= 107.650 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.12 Columna C4 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 33.00 cm fy= 2500 kg/cm²
d= 33.00 cm A= 42.600 cm²
tf= 0.50 cm Ix=Iy= 9533.950 cm⁴
tw= 0.15 cm Sx=Sy= 577.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.641 Zx=Zy= 613.050 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.196 rx=ry= 14.960 cm
Mu=
2.550 2.550 ux/ɸb.Mn= 0.196 J= 8073.355 cm⁴
Pu= 56.28 Ton Lp= 15.205 m
Ala= 32.02 40.023206 Mp= 15.326 Tm k= 1.200 -
b/t= 64.00 - Mn= 14.4453788 Tm e= 24.064 -
esbelta ɸMn= 13.001 Tm λc= 0.268 -
Alma= 69.18 162.95163 % de %(x-x)= 82% fcr= 2.426 Ton/cm²
h/t= 218.00 - Trabajo %(y-y)= 82% ɸc.Pn= 87.845 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.13 Columna D1 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 30.00 cm fy= 2500 kg/cm²
d= 30.00 cm A= 38.700 cm²
tf= 0.50 cm Ix=Iy= 7137.225 cm⁴
tw= 0.15 cm Sx=Sy= 475.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.319 Zx=Zy= 505.575 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.747 rx=ry= 13.580 cm
Mu=
8.000 8.000 ux/ɸb.Mn= 0.747 J= 6049.245 cm⁴
Pu= 25.33 Ton Lp= 13.808 m
Ala= 32.02 40.023206 Mp= 12.639 Tm k= 1.200 -
b/t= 58.00 - Mn= 11.895375 Tm e= 26.509 -
esbelta ɸMn= 10.706 Tm λc= 0.295 -
Alma= 69.18 162.95163 % de %(x-x)= 98% fcr= 2.410 Ton/cm²
h/t= 198.00 - Trabajo %(y-y)= 98% ɸc.Pn= 79.293 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.14 Columna D2 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 33.00 cm fy= 2500 kg/cm²
d= 33.00 cm A= 42.600 cm²
tf= 0.50 cm Ix=Iy= 9533.950 cm⁴
tw= 0.15 cm Sx=Sy= 577.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.459 Zx=Zy= 613.050 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.192 rx=ry= 14.960 cm
Mu=
2.500 2.500 ux/ɸb.Mn= 0.192 J= 8073.355 cm⁴
Pu= 40.28 Ton Lp= 15.205 m
Ala= 32.02 40.023206 Mp= 15.326 Tm k= 1.200 -
b/t= 64.00 - Mn= 14.4453788 Tm e= 24.064 -
esbelta ɸMn= 13.001 Tm λc= 0.268 -
Alma= 69.18 162.95163 % de %(x-x)= 63% fcr= 2.426 Ton/cm²
h/t= 218.00 - Trabajo %(y-y)= 63% ɸc.Pn= 87.845 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.15 Columna D3 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 33.00 cm fy= 2500 kg/cm²
d= 33.00 cm A= 42.600 cm²
tf= 0.50 cm Ix=Iy= 9533.950 cm⁴
tw= 0.15 cm Sx=Sy= 577.815 cm³
Lb= 3.000 m Pu/ɸc.Pn= 0.394 Zx=Zy= 613.050 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.177 rx=ry= 14.960 cm
Mu=
2.300 2.300 ux/ɸb.Mn= 0.177 J= 8073.355 cm⁴
Pu= 34.63 Ton Lp= 15.205 m
Ala= 32.02 40.023206 Mp= 15.326 Tm k= 1.200 -
b/t= 64.00 - Mn= 14.4453788 Tm e= 24.064 -
esbelta ɸMn= 13.001 Tm λc= 0.268 -
Alma= 69.18 162.95163 % de %(x-x)= 55% fcr= 2.426 Ton/cm²
h/t= 218.00 - Trabajo %(y-y)= 55% ɸc.Pn= 87.845 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

2.16 Columna D4 (Piso 1)


Datos: Perfil Tubular O E= 2043185 kg/cm²
bf= 30.00 cm fy= 2500 kg/cm²
d= 30.00 cm A= 38.700 cm²
tf= 0.50 cm Ix=Iy= 7137.225 cm⁴
tw= 0.15 cm Sx=Sy= 475.815 cm³
Lb= 3.00 m Pu/ɸc.Pn= 0.404 Zx=Zy= 505.575 cm³
Eje x-x Eje y-y ux/ɸb.Mn= 0.675 rx=ry= 13.580 cm
Mu=
7.230 7.230 ux/ɸb.Mn= 0.675 J= 6049.245 cm⁴
Pu= 32.04 Ton Lp= 13.808 m
Ala= 32.02 40.023206 Mp= 12.639 Tm k= 1.200 -
b/t= 58.00 - Mn= 11.895375 Tm e= 26.509 -
esbelta ɸMn= 10.706 Tm λc= 0.295 -
Alma= 69.18 162.95163 % de %(x-x)= 100% fcr= 2.410 Ton/cm²
h/t= 198.00 - Trabajo %(y-y)= 100% ɸc.Pn= 79.293 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN
1. Diseño de Vigas Con alma compacta y ala esbelta
1.1 Eje A-A (Tramo Eje 1-1, Eje 2-2)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm > Mu= 3.230 Tm CUMPLE

1.2 Eje A-A (Tramo Eje 2-2, Eje 3-3)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm > Mu= 1.730 Tm CUMPLE
1.3 Eje A-A (Tramo Eje 3-3, Eje 4-4)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm > Mu= 2.320 Tm CUMPLE
1.4 Eje B-B (Tramo Eje 1-1, Eje 2-2)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm > Mu= 7.630 Tm CUMPLE
1.5 Eje B-B (Tramo Eje 2-2, Eje 3-3)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm > Mu= 7.190 Tm CUMPLE
1.6 Eje B-B (Tramo Eje 3-3, Eje 4-4)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm > Mu= 5.240 Tm CUMPLE
1.7 Eje C-C (Tramo Eje 1-1, Eje 2-2)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm > Mu= 7.630 Tm CUMPLE
1.8 Eje C-C (Tramo Eje 2-2, Eje 3-3)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm > Mu= 2.810 Tm CUMPLE
1.9 Eje C-C (Tramo Eje 3-3, Eje 4-4)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 67.165 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.550 cm
ALA= 10.86 28.588 Ix= 3742.722 cm⁴
b/t = 32.22 - Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
ALMA= 108.06 162.95 0.00936 0.135841359 Iy= 1830.096 cm⁴
h/tw= 8.88 - Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Mp= 11.280 Tm λ² 1038.272 m ϒy= 5.220 cm
Mr= 6.550 Tm kc= 1.311 m J= 66.527 cm⁴
Mn= 8.693 Tm Cw= 174778.814 cm⁶ rts= 6.913 cm
ɸMn= 7.82 Tm > Mu= 5.280 Tm CUMPLE
1.10 D-D (Tramo Eje 1-1, Eje 2-2)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm > Mu= 3.140 Tm CUMPLE

1.11 Eje D-D (Tramo Eje 2-2, Eje 3-3)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm > Mu= 1.670 Tm CUMPLE
1.12 Eje D-D (Tramo Eje 3-3, Eje 4-4)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 29.00 cm Fy= 2500 kg/cm²
tf= 0.45 cm A= 40.2 cm²
tw= 1.00 cm C= 1 -
d= 15.00 cm ho= 14.550 cm
ALA= 10.86 28.588 Ix= 1615.401 cm⁴
b/t = 32.22 - Sx= 215.387 cm³
Esbelto Zx= 239.580 cm³
ALMA= 108.06 162.95 0.00307 0.071954026 Iy= 1830.350 cm⁴
h/tw= 14.10 - Sy= 126.231 cm³
Compacto λ= 32.222 m Zy= 192.750 cm³
Mp= 5.990 Tm λ² 1038.272 m ϒy= 6.748 cm
Mr= 3.769 Tm kc= 1.033 m J= 6.612 cm⁴
Mn= 3.940 Tm Cw= 96810.230 cm⁶ rts= 7.861 cm
ɸMn= 3.55 Tm > Mu= 2.300 Tm CUMPLE
1.13 Eje 1-1 (Tramo Eje A-A, Eje B-B)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 27.00 cm Fy= 2500 kg/cm²
tf= 0.35 cm A= 60.395 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.650 cm
ALA= 10.86 28.588 Ix= 3112.6611 cm⁴
b/t = 38.57 - Sx= 311.266 cm³
Esbelto Zx= 385.906 cm³
ALMA= 108.06 162.95 0.011 0.147533407 Iy= 1149.262 cm⁴
h/tw= 8.98 - Sy= 85.131 cm³
Compacto λ= 38.571 m Zy= 149.879 cm³
Mp= 9.648 Tm λ² 1487.755 m ϒy= 4.362 cm
Mr= 5.447 Tm kc= 1.311 m J= 65.868 cm⁴
Mn= 5.046 Tm Cw= 110834.050 cm⁶ rts= 6.022 cm
ɸMn= 4.54 Tm > Mu= 4.150 Tm CUMPLE
1.14 Eje 1-1 (Tramo Eje B-B, Eje C-C)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 27.00 cm Fy= 2500 kg/cm²
tf= 0.35 cm A= 60.395 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.650 cm
ALA= 10.86 28.588 Ix= 3112.6611 cm⁴
b/t = 38.57 - Sx= 311.266 cm³
Esbelto Zx= 385.906 cm³
ALMA= 108.06 162.95 0.011 0.147533407 Iy= 1149.262 cm⁴
h/tw= 8.98 - Sy= 85.131 cm³
Compacto λ= 38.571 m Zy= 149.879 cm³
Mp= 9.648 Tm λ² 1487.755 m ϒy= 4.362 cm
Mr= 5.447 Tm kc= 1.311 m J= 65.868 cm⁴
Mn= 5.046 Tm Cw= 110834.050 cm⁶ rts= 6.022 cm
ɸMn= 4.54 Tm > Mu= 3.420 Tm CUMPLE

1.15 Eje 1-1 (Tramo Eje C-C, Eje D-D)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 27.00 cm Fy= 2500 kg/cm²
tf= 0.35 cm A= 60.395 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.650 cm
ALA= 10.86 28.588 Ix= 3112.6611 cm⁴
b/t = 38.57 - Sx= 311.266 cm³
Esbelto Zx= 385.906 cm³
ALMA= 108.06 162.95 0.011 0.147533407 Iy= 1149.262 cm⁴
h/tw= 8.98 - Sy= 85.131 cm³
Compacto λ= 38.571 m Zy= 149.879 cm³
Mp= 9.648 Tm λ² 1487.755 m ϒy= 4.362 cm
Mr= 5.447 Tm kc= 1.311 m J= 65.868 cm⁴
Mn= 5.046 Tm Cw= 110834.050 cm⁶ rts= 6.022 cm
ɸMn= 4.54 Tm > Mu= 4.180 Tm CUMPLE
1.16 Eje 2-2 (Tramo Eje A-A, Eje B-B)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 60.88 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3150.7669 cm⁴
b/t = 30.63 - Sx= 315.077 cm³
Esbelto Zx= 390.224 cm³
ALMA= 108.06 162.95 0.01091 0.146957974 Iy= 981.412 cm⁴
h/tw= 8.93 - Sy= 80.115 cm³
Compacto λ= 30.625 m Zy= 142.238 cm³
Mp= 9.756 Tm λ² 937.891 m ϒy= 4.015 cm
Mr= 5.514 Tm kc= 1.311 m J= 65.976 cm⁴
Mn= 8.102 Tm Cw= 94158.416 cm⁶ rts= 5.524 cm
ɸMn= 7.29 Tm > Mu= 6.680 Tm CUMPLE
1.17 Eje 2-2 (Tramo Eje B-B, Eje C-C)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 60.88 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3150.7669 cm⁴
b/t = 30.63 - Sx= 315.077 cm³
Esbelto Zx= 390.224 cm³
ALMA= 108.06 162.95 0.01091 0.146957974 Iy= 981.412 cm⁴
h/tw= 8.93 - Sy= 80.115 cm³
Compacto λ= 30.625 m Zy= 142.238 cm³
Mp= 9.756 Tm λ² 937.891 m ϒy= 4.015 cm
Mr= 5.514 Tm kc= 1.311 m J= 65.976 cm⁴
Mn= 8.102 Tm Cw= 94158.416 cm⁶ rts= 5.524 cm
ɸMn= 7.29 Tm > Mu= 3.500 Tm CUMPLE
1.18 Eje 2-2 (Tramo Eje C-C, Eje D-D)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 60.88 cm²
tw= 2.15 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3150.7669 cm⁴
b/t = 30.63 - Sx= 315.077 cm³
Esbelto Zx= 390.224 cm³
ALMA= 108.06 162.95 0.01091 0.146957974 Iy= 981.412 cm⁴
h/tw= 8.93 - Sy= 80.115 cm³
Compacto λ= 30.625 m Zy= 142.238 cm³
Mp= 9.756 Tm λ² 937.891 m ϒy= 4.015 cm
Mr= 5.514 Tm kc= 1.311 m J= 65.976 cm⁴
Mn= 8.102 Tm Cw= 94158.416 cm⁶ rts= 5.524 cm
ɸMn= 7.29 Tm > Mu= 7.040 Tm CUMPLE

1.19 3-3 (Tramo Eje A-A, Eje B-B)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 58 cm²
tw= 2.00 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3062.2933 cm⁴
b/t = 30.63 - Sx= 306.229 cm³
Esbelto Zx= 376.400 cm³
ALMA= 108.06 162.95 0.00916 0.134310726 Iy= 981.542 cm⁴
h/tw= 9.60 - Sy= 80.126 cm³
Compacto λ= 30.625 m Zy= 139.250 cm³
Mp= 9.410 Tm λ² 937.891 m ϒy= 4.114 cm
Mr= 5.359 Tm kc= 1.265 m J= 53.312 cm⁴
Mn= 7.595 Tm Cw= 94158.416 cm⁶ rts= 5.603 cm
ɸMn= 6.84 Tm > Mu= 5.950 Tm CUMPLE

1.20 Eje 3-3 (Tramo Eje B-B, Eje C-C)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 58 cm²
tw= 2.00 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3062.2933 cm⁴
b/t = 30.63 - Sx= 306.229 cm³
Esbelto Zx= 376.400 cm³
ALMA= 108.06 162.95 0.00916 0.134310726 Iy= 981.542 cm⁴
h/tw= 9.60 - Sy= 80.126 cm³
Compacto λ= 30.625 m Zy= 139.250 cm³
Mp= 9.410 Tm λ² 937.891 m ϒy= 4.114 cm
Mr= 5.359 Tm kc= 1.265 m J= 53.312 cm⁴
Mn= 7.595 Tm Cw= 94158.416 cm⁶ rts= 5.603 cm
ɸMn= 6.84 Tm > Mu= 3.320 Tm CUMPLE

1.21 Eje 3-3 (Tramo Eje C-C, Eje D-D)


Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.50 cm Fy= 2500 kg/cm²
tf= 0.40 cm A= 58 cm²
tw= 2.00 cm C= 1 -
d= 20.00 cm ho= 19.600 cm
ALA= 10.86 28.588 Ix= 3062.2933 cm⁴
b/t = 30.63 - Sx= 306.229 cm³
Esbelto Zx= 376.400 cm³
ALMA= 108.06 162.95 0.00916 0.134310726 Iy= 981.542 cm⁴
h/tw= 9.60 - Sy= 80.126 cm³
Compacto λ= 30.625 m Zy= 139.250 cm³
Mp= 9.410 Tm λ² 937.891 m ϒy= 4.114 cm
Mr= 5.359 Tm kc= 1.265 m J= 53.312 cm⁴
Mn= 7.595 Tm Cw= 94158.416 cm⁶ rts= 5.603 cm
ɸMn= 6.84 Tm > Mu= 6.320 Tm CUMPLE
1.22 4-4 (Tramo Eje A-A, Eje B-B)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.00 cm Fy= 2500 kg/cm²
tf= 0.37 cm A= 60.132 cm²
tw= 2.20 cm C= 1 -
d= 20.00 cm ho= 19.630 cm
ALA= 10.86 28.588 Ix= 3020.9144 cm⁴
b/t = 32.43 - Sx= 302.091 cm³
Esbelto Zx= 378.336 cm³
ALMA= 108.06 162.95 0.01209 0.154850107 Iy= 853.490 cm⁴
h/tw= 8.75 - Sy= 71.124 cm³
Compacto λ= 32.432 m Zy= 129.865 cm³
Mp= 9.458 Tm λ² 1051.863 m ϒy= 3.767 cm
Mr= 5.287 Tm kc= 1.327 m J= 70.484 cm⁴
Mn= 7.006 Tm Cw= 82123.000 cm⁶ rts= 5.264 cm
ɸMn= 6.31 Tm > Mu= 5.800 Tm CUMPLE
1.23 Eje 4-4 (Tramo Eje B-B, Eje C-C)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.00 cm Fy= 2500 kg/cm²
tf= 0.37 cm A= 60.132 cm²
tw= 2.20 cm C= 1 -
d= 20.00 cm ho= 19.630 cm
ALA= 10.86 28.588 Ix= 3020.9144 cm⁴
b/t = 32.43 - Sx= 302.091 cm³
Esbelto Zx= 378.336 cm³
ALMA= 108.06 162.95 0.01209 0.154850107 Iy= 853.490 cm⁴
h/tw= 8.75 - Sy= 71.124 cm³
Compacto λ= 32.432 m Zy= 129.865 cm³
Mp= 9.458 Tm λ² 1051.863 m ϒy= 3.767 cm
Mr= 5.287 Tm kc= 1.327 m J= 70.484 cm⁴
Mn= 7.006 Tm Cw= 82123.000 cm⁶ rts= 5.264 cm
ɸMn= 6.31 Tm > Mu= 4.630 Tm CUMPLE
1.24 Eje 4-4 (Tramo Eje C-C, Eje D-D)
Datos: Perfil Tipo I E= 2043185 kg/cm²
bf= 24.00 cm Fy= 2500 kg/cm²
tf= 0.37 cm A= 60.132 cm²
tw= 2.20 cm C= 1 -
d= 20.00 cm ho= 19.630 cm
ALA= 10.86 28.588 Ix= 3020.9144 cm⁴
b/t = 32.43 - Sx= 302.091 cm³
Esbelto Zx= 378.336 cm³
ALMA= 108.06 162.95 0.01209 0.154850107 Iy= 853.490 cm⁴
h/tw= 8.75 - Sy= 71.124 cm³
Compacto λ= 32.432 m Zy= 129.865 cm³
Mp= 9.458 Tm λ² 1051.863 m ϒy= 3.767 cm
Mr= 5.287 Tm kc= 1.327 m J= 70.484 cm⁴
Mn= 7.006 Tm Cw= 82123.000 cm⁶ rts= 5.264 cm
ɸMn= 6.31 Tm > Mu= 5.820 Tm CUMPLE
3. Diseño de Columnas No Compactas Rellenas de Hormigón
3.1 Columna A1 (Piso 1) Ip= 37307.869 cm⁴ fcr
Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 37.18 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
19.11 19.11 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.2 Columna A2 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 54.17 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
20.00 20.00 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.2 Columna A2 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 48.08 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
19.30 19.30 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.4 Columna A4 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 43.84 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
19.53 19.53 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.5 Columna B1 (Piso 1) Ip= 28702.317 cm⁴ fcr


Datos: Ic= 733849.767 cm⁴ Perfil Relleno O
bf= 55.00 cm Líím.2= 85.764 -
d= 55.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 220.000 esbelto
tw= 0.30 cm Pp=PNO= 125.235 Ton
Lb= 3.000 m C3= 0.640 -
Pu= 60.00 Ton EI= 161384036773 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6398017
Mu=
12.00 12.00 Ap= 28 cm
Es= 2043185 kg/cm² bi= 54 cm
Ec= 218820 kg/cm² C1= 40.800 Ton b1c=
fy= 2500 kg/cm² C2= 20.625 Ton b2c=
f´c= 210 kg/cm² C3= 239.504 Ton b3c=
Ap= 60.200 cm² C4= 0.000 Ton b4c=
Ac= 2964.800 cm² CT= 300.929 Ton b1t=
Euler= 12290097 kg T1= 82.500 Ton b2t=
exp= 0.010 - T2= 40.800 Ton b3t=
Pn= 125.229 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 106.445 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 123.300 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 34.935 T.m % de
ɸMn= 31.442 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.6 Columna B2 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 85.00 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
Mu=
6.38 6.38 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.7 Columna B3 (Piso 1) Ip= 28702.317 cm⁴ fcr


Datos: Ic= 733849.767 cm⁴ Perfil Relleno O
bf= 55.00 cm Líím.2= 85.764 -
d= 55.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 220.000 esbelto
tw= 0.30 cm Pp=PNO= 125.235 Ton
Lb= 3.000 m C3= 0.640 -
Pu= 101.00 Ton EI= 161384036773 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6398017
Mu=
1.25 1.25 Ap= 28 cm
Es= 2043185 kg/cm² bi= 54 cm
Ec= 218820 kg/cm² C1= 40.800 Ton b1c=
fy= 2500 kg/cm² C2= 20.625 Ton b2c=
f´c= 210 kg/cm² C3= 239.504 Ton b3c=
Ap= 60.200 cm² C4= 0.000 Ton b4c=
Ac= 2964.800 cm² CT= 300.929 Ton b1t=
Euler= 12290097 kg T1= 82.500 Ton b2t=
exp= 0.010 - T2= 40.800 Ton b3t=
Pn= 125.229 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 106.445 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 123.300 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 34.935 T.m % de
ɸMn= 31.442 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.8 Columna B4 (Piso 1) Ip= 28702.317 cm⁴ fcr


Datos: Ic= 733849.767 cm⁴ Perfil Relleno O
bf= 55.00 cm Líím.2= 85.764 -
d= 55.00 cm Líím.3= 161.400 -
tf= 0.25 cm λ= 220.000 esbelto
tw= 0.30 cm Pp=PNO= 125.235 Ton
Lb= 3.000 m C3= 0.640 -
Pu= 71.00 Ton EI= 161384036773 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6398017
Mu=
10.54 10.54 Ap= 28 cm
Es= 2043185 kg/cm² bi= 54 cm
Ec= 218820 kg/cm² C1= 40.800 Ton b1c=
fy= 2500 kg/cm² C2= 20.625 Ton b2c=
f´c= 210 kg/cm² C3= 239.504 Ton b3c=
Ap= 60.200 cm² C4= 0.000 Ton b4c=
Ac= 2964.800 cm² CT= 300.929 Ton b1t=
Euler= 12290097 kg T1= 82.500 Ton b2t=
exp= 0.010 - T2= 40.800 Ton b3t=
Pn= 125.229 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 106.445 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 123.300 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 34.935 T.m % de
ɸMn= 31.442 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.9 Columna C1 (Piso 1) Ip= 39063.243 cm⁴ fcr


Datos: Ic= 1040936.757 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.35 cm Pp=PNO= 120.473 Ton
Lb= 3.000 m C3= 0.640 -
Pu= 47.62 Ton EI= 225546780803 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6398056
Mu=
4.24 4.24 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 51.888 Ton b1c=
fy= 2500 kg/cm² C2= 26.250 Ton b2c=
f´c= 210 kg/cm² C3= 310.765 Ton b3c=
Ap= 71.650 cm² C4= 0.000 Ton b4c=
Ac= 3528.350 cm² CT= 388.902 Ton b1t=
Euler= 17176370 kg T1= 105.000 Ton b2t=
exp= 0.007 - T2= 51.888 Ton b3t=
Pn= 120.470 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.400 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 156.888 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 49.025 T.m % de
ɸMn= 44.123 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN
3.10 Columna C2 (Piso 1) Ip= 37307.869 cm⁴ fcr
Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 85.764 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 76.04 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
4.22 4.22 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.11 Columna C3 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 65.04 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
3.23 3.23 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.12 Columna C4 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 161.400 -
tf= 0.25 cm λ= 240.000
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 58.57 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
2.90 2.90 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.13 Columna D1 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 161.400 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 24.17 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
2.11 2.11 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.14 Columna D2 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 161.400 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 43.24 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
2.24 2.24 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.15 Columna D3 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 57.176 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 36.17 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
Mu=
1.78 1.78 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3.16 Columna D4 (Piso 1) Ip= 37307.869 cm⁴ fcr


Datos: Ic= 1042692.131 cm⁴ Perfil Relleno O
bf= 60.00 cm Líím.2= 85.764 -
d= 60.00 cm Líím.3= 142.940 -
tf= 0.25 cm λ= 240.000 esbelto
tw= 0.30 cm Pp=PNO= 120.514 Ton
Lb= 3.000 m C3= 0.637 -
Pu= 31.07 Ton EI= 221451782049 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6365
Mu=
1.16 1.16 Ap= 30 cm
Es= 2043185 kg/cm² bi= 59 cm
Ec= 218820 kg/cm² C1= 44.550 Ton b1c=
fy= 2500 kg/cm² C2= 22.500 Ton b2c=
f´c= 210 kg/cm² C3= 285.530 Ton b3c=
Ap= 65.700 cm² C4= 0.000 Ton b4c=
Ac= 3534.300 cm² CT= 352.580 Ton b1t=
Euler= 16864518 kg T1= 90.000 Ton b2t=
exp= 0.007 - T2= 44.550 Ton b3t=
Pn= 120.512 Ton T3= 0.000 Ton b4t=
ɸc.Pn= 102.435 Ton T4= 0.000 Ton brazo(1)=
CUMPLE A C. AXIAL TT= 134.550 Ton brazo(2)=
CUMPLE A FLEXIÓN Mn= 43.768 T.m % de
ɸMn= 39.392 Tm Trabajo
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN
319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 79%
%(y-y)= 79%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 98%
%(y-y)= 98%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 90%
%(y-y)= 90%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 87%
%(y-y)= 87%
XIAL Y FLEXIÓN

379.9311
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
27.350 cm
0.000 cm
54.850 cm
0.000 cm
0.000 cm
18.300 cm
%(x-x)= 90%
%(y-y)= 90%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O
0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 97%
%(y-y)= 97%
XIAL Y FLEXIÓN

379.9311
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
27.350 cm
0.000 cm
54.850 cm
0.000 cm
0.000 cm
18.300 cm
%(x-x)= 98%
%(y-y)= 98%
XIAL Y FLEXIÓN

379.9311
Perfil Relleno O
0.000 cm
0.000 cm
0.000 cm
0.000 cm
27.350 cm
0.000 cm
54.850 cm
0.000 cm
0.000 cm
18.300 cm
%(x-x)= 96%
%(y-y)= 96%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.825 cm
0.000 cm
59.825 cm
0.000 cm
0.000 cm
19.961 cm
%(x-x)= 55%
%(y-y)= 55%
XIAL Y FLEXIÓN
319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 84%
%(y-y)= 84%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 71%
%(y-y)= 71%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 64%
%(y-y)= 64%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 28%
%(y-y)= 28%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 47%
%(y-y)= 47%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O
0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 39%
%(y-y)= 39%
XIAL Y FLEXIÓN

319.24766
Perfil Relleno O

0.000 cm
0.000 cm
0.000 cm
0.000 cm
29.850 cm
0.000 cm
59.850 cm
0.000 cm
0.000 cm
19.967 cm
%(x-x)= 33%
%(y-y)= 33%
XIAL Y FLEXIÓN
CUADRO COMPARATIVO (ELEMENTOS CRÍTICOS)

Vigas Vigas Vigas No Vigas No Vigas


Compactas Compactas Compactas Compactas Esbeltas (COL Vigas Esbeltas
(COL RELL)
(COL TUB) (COL RELL) (COL TUB) (COL RELL) TUB)
Tramo:EJE B-B, (1-1,2-2)
EJE B-B, (1-1,2-2)
EJE B-B, (1-1,2-2)
EJE B-B, (1-1,2-2)
Ap(cm²): 40.340 40.340 67.165 67.165
VIGAS
Mu(Tm): 8.400 8.600 7.190 7.630
ɸMn(Tm): 8.670 8.670 7.824 7.824
COLUMNA: B2 B2 B3 B2
Ap(cm²): 81.750 58.560 71.200 33.900
Ac(cm²): - 566.440 - 18.900
Mu(Tm): 6.070 6.970 6.073 6.380
COLUMNAS
ɸMn(Tm): 18.801 15.593 36.637 39.392
Pu(T): 107.340 115.760 108.780 85.000
ɸPc(T): 164.540 206.989 149.691 102.435
%.trabajo: 94.00% 96.00% 87.40% 97.38%

VIGAS ASBELTAS - COLUMNAS RELLENAS


VIGA EJE B-B
TRAMO bf tf tw d b/t ALA
Eje 1-1, Eje 2-2 29.00 0.45 2.15 20.00 64.44 Esbelto
Eje 2-2, Eje 3-3 29.00 0.45 2.15 20.00 32.22 Esbelto
Eje 3-3, Eje 4-4 29.00 0.45 2.15 20.00 32.22 Esbelto

COLUMNA bf tf tw d λ Condicion
Columna B1 55.00 0.25 0.30 55.00 220.00 esbelto
Columna B2 60.00 0.30 3.00 0.25 200.00 esbelto
Columna B3 55.00 0.30 3.00 0.25 183.33 esbelto
Columna B4 55.00 0.30 0.30 0.25 183.33 esbelto
VIGAS COMPACTAS - COLUMNAS TUBULARES
VIGA EJE B-B
TRAMO bf tf tw d b/t ALA
Eje 1-1, Eje 2-2 29.00 0.45 2.15 20.00 32.22 esbelta
Eje 2-2, Eje 3-3 29.00 0.45 2.15 20.00 32.22 esbelta
Eje 3-3, Eje 4-4 29.00 0.45 2.15 20.00 32.22 esbelta

COLUMNA bf tf tw d b/t ALA


Columna B1 40.00 0.50 0.15 40.00 78.00 ESBELTA
Columna B2 55.00 0.50 0.15 55.00 108.00 ESBELTA
Columna B3 55.00 0.50 0.15 55.00 108.00 ESBELTA
Columna B4 33.00 0.50 0.15 33.00 64.00 ESBELTA

1.4 Eje B-B (Tramo Eje 1-1, Eje 2-2)


Datos: Perfil Tipo I
bf= 29.00 cm
tf= 0.45 cm
tw= 2.15 cm
d= 20.00 cm
ALA= 10.86 28.5880045
b/t = 32.22 -
Esbelto
ALMA= 108.06 162.95 0.00936081 0.135841359
h/tw= 8.88 -
Compacto λ= 32.222 m
Mp= 11.280 Tm λ² 1038.272 m
Mr= 6.550 Tm kc= 1.311 m
Mn= 8.693 Tm cm⁶
ɸMn= 7.82 Tm
> Cw=Mu=
174778.814
7.630 Tm

2.5 Columna B1 (Piso 1)


Datos: Perfil Tubular O
bf= 40.00 cm
d= 40.00 cm
tf= 0.50 cm
tw= 0.15 cm
Lb= 3.000 m Pu/ɸc.Pn= 0.434
Eje x-x Eje y-y Mux/ɸb.Mn= 0.208
Mu=
4.000 4.000Mux/ɸb.Mn= 0.208
Pu= 46.77 Ton
Ala= 32.02 40.0232063 Mp= 22.602 Tm
b/t= 78.00 - Mn= 21.35788542 Tm
esbelta ɸMn= 19.222 Tm
Alma= 69.18 162.951626 % de %(x-x)= 62%
h/t= 264.67 - Trabajo %(y-y)= 62%
esbelta CUMPLE A FLEXIÓN
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEX
h/tw ALMA A= Lp= Lr= Lb= ɸMn= Condición
8.88 Compacto 67.17 32.22 1038.27 1.31 7.82 >
8.88 Compacto 67.17 32.22 1038.27 1.50 7.82 >
8.88 Compacto 67.17 32.22 1038.27 1.31 7.82 >

Ap Ac Lb ɸMn Condición Mu ɸc.Pn Condición


60.20 2964.80 3.00 31.44 > 12.00 106.44 >
33.90 18.90 3.00 39.39 > 6.38 102.44 >
30.90 17.15 3.00 31.44 > 1.25 106.44 >
32.79 19.04 3.00 31.44 > 10.54 106.44 >
h/tw ALMA A= Lp= Lr= Lb= ɸMn= Condición
8.88 COMPACTA 67.17 32.22 1038.27 1.67 7.82 >
8.88 COMPACTA 67.17 32.22 1038.27 1.50 7.82 >
8.88 COMPACTA 67.17 32.22 1038.27 1.33 7.82 >

h/tw ALMA Ap Lb ɸMn Condición Mu ɸc.Pn


264.67 ESBELTA 51.70 3.00 19.22 > 4.00 107.65
364.67 ESBELTA 71.20 3.00 36.64 > 6.63 149.69
364.67 ESBELTA 71.20 3.00 36.64 > 6.07 149.69
218.00 ESBELTA 42.60 3.00 13.00 > 2.40 87.85

1.5 Eje B-B (Tramo Eje 2-2, Eje 3-3)


E= 2043185 kg/cm² Datos: Perfil Tipo I
Fy= 2500 kg/cm² bf= 29.00 cm
A= 67.165 cm² tf= 0.45 cm
C= 1 - tw= 2.15 cm
ho= 19.550 cm d= 20.00 cm
Ix= 3742.72197 cm⁴ ALA= 10.86 28.5880045
Sx= 374.272 cm³ b/t = 32.22 -
Zx= 451.213 cm³ Esbelto
Iy= 1830.096 cm⁴ ALMA= 108.06 162.95 0.00936081
Sy= 126.214 cm³ h/tw= 8.88 -
Zy= 211.297 cm³ Compacto λ=
ϒy= 5.220 cm Mp= 11.280 Tm λ²
J= 66.527 cm⁴ Mr= 6.550 Tm kc=
rts= 6.913 cm Mn= 8.693 Tm
CUMPLE ɸMn= 7.82 Tm
> Cw= Mu=

2.6 Columna B2 (Piso 1)


E= 2043185 kg/cm² Datos: Perfil Tubular
fy= 2500 kg/cm² bf= 55.00 cm
A= 51.700 cm² d= 55.00 cm
Ix=Iy= 17086.308 cm⁴ tf= 0.50 cm
Sx=Sy= 854.315 cm³ tw= 0.15 cm
Zx=Zy= 904.075 cm³ Lb= 3.000 m Pu/ɸc.Pn=
rx=ry= 18.179 cm Eje x-x Eje y-y Mux/ɸb.Mn=
J= 14445.897 cm⁴
Mu=
6.630 6.630Mux/ɸb.Mn=
Lp= 18.463 m Pu= 103.27 Ton
k= 1.200 - Ala= 32.02 40.0232063 Mp=
e= 19.803 - b/t= 108.00 - Mn=
λc= 0.220 - esbelta ɸMn=
fcr= 2.450 Ton/cm² Alma= 69.18 162.951626 % de
ɸc.Pn= 107.650 Ton h/t= 364.67 - Trabajo
CUMPLE A C. AXIAL esbelta CUMPLE A FLEX
DOS DE C. AXIAL Y FLEXIÓN EL ELEMENTO CUMPLE A ESFUERZOS COMBIN
1.4 Eje B-B (Tramo Eje 1-1, Eje 2-2)
Datos:
bf= 29.00
tf= 0.45
tw= 2.15
d= 20.00
ALA= 10.86
b/t = 32.22
Mu= Condición Esbelto
7.63 CUMPLE ALMA= 108.06
7.19 CUMPLE h/tw= 8.88
5.24 CUMPLE Compacto
Mp= 11.280
Pu % x-x % y-y Mr= 6.550
60.00 0.90 0.90 Mn= 8.693
85.00 0.97 0.97 ɸMn= 7.82
101.00 0.98 0.98
71.00 0.96 0.96 3.5 Columna B1 (Piso 1)
Datos:
bf=
d=
tf=
tw=
Lb=
Pu=

Mu=
Es=
Ec=
fy=
f´c=
Mu= Condición Ap=
7.19 CUMPLE Ac=
4.11 CUMPLE Euler=
5.24 CUMPLE exp=
Pn=
Condición Pu % x-x % y-y ɸc.Pn=
> 46.77 0.62 0.62 CUMPLE A C. AXIA
> 103.27 0.85 0.85 CUMPLE A FLEXIÓ
> 108.78 0.87 0.87
> 64.37 0.90 0.90 EL ELE

1.6 Eje B-B (Tramo Eje 3-3, Eje 4-4)


Perfil Tipo I E= 2043185 kg/cm² Datos:
Fy= 2500 kg/cm² bf= 29.00
A= 67.165 cm² tf= 0.45
C= 1 - tw= 2.15
ho= 19.550 cm d= 20.00
Ix= 3742.72197 cm⁴ ALA= 10.86
Sx= 374.272 cm³ b/t = 32.22
Zx= 451.213 cm³ Esbelto
0.135841359 Iy= 1830.096 cm⁴ ALMA= 108.06
Sy= 126.214 cm³ h/tw= 8.88
32.222 m Zy= 211.297 cm³ Compacto
1038.272 m ϒy= 5.220 cm Mp= 11.280
1.311 m J= 66.527 cm⁴ Mr= 6.550
174778.814 cm⁶ rts= 6.913 cm Mn= 8.693
7.190 Tm CUMPLE ɸMn= 7.82

2.7 Columna B3 (Piso 1)


Perfil Tubular O E= 2043185 kg/cm² Datos:
fy= 2500 kg/cm² bf= 55.00
A= 71.200 cm² d= 55.00
Ix=Iy= 44778.683 cm⁴ tf= 0.50
Sx=Sy= 1628.316 cm³ tw= 0.15
0.690 Zx=Zy= 1717.450 cm³ Lb= 3.000
0.181 rx=ry= 25.078 cm Eje x-x
0.181 J= 37781.963 cm⁴
Mu=
6.073
Lp= 25.445 m Pu= 108.78
42.936 Tm k= 1.200 - Ala= 32.02
40.70789394 Tm e= 14.355 - b/t= 108.00
36.637 Tm λc= 0.160 - esbelta
%(x-x)= 85% fcr= 2.473 Ton/cm² Alma= 69.18
%(y-y)= 85% ɸc.Pn= 149.691 Ton h/t= 364.67
CUMPLE A FLEXIÓN CUMPLE A C. AXIAL esbelta
E A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN EL ELEMENTO CUM

28.588

28.588
1-1, Eje 2-2)
Perfil Tipo I E= 2043185 kg/cm²
cm Fy= 2500 kg/cm²
cm A= 67.165 cm²
cm C= 1 -
cm ho= 19.550 cm
28.5880045 Ix= 3742.72197 cm⁴
- Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
162.95 0.00936081 0.13584136 Iy= 1830.096 cm⁴
- Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Tm λ² 1038.272 m ϒy= 5.220 cm
Tm kc= 1.311 m J= 66.527 cm⁴
Tm cm⁶
> Cw= 174778.814 rts= 6.913 cm
Tm Mu= 7.630 Tm CUMPLE

B1 (Piso 1) Ip= 28702.317 cm⁴ fcr 379.9311


Ic= 733849.767 cm⁴ Perfil Relleno O
55.00 cm Líím.2= 85.764 -
55.00 cm Líím.3= 142.940 -
0.25 cm λ= 220.000 esbelto
0.30 cm Pp=PNO= 125.235 Ton
3.000 m C3= 0.640 -
60.00 Ton EI= 161384036773 kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.63980165
12.00 12.00 Ap= 28 cm
2043185 kg/cm² bi= 54 cm
218820 kg/cm² C1= 40.800 Ton b1c= 0.000
2500 kg/cm² C2= 20.625 Ton b2c= 0.000
210 kg/cm² C3= 239.504 Ton b3c= 0.000
60.200 cm² C4= 0.000 Ton b4c= 0.000
2964.800 cm² CT= 300.929 Ton b1t= 27.350
12290097 kg T1= 82.500 Ton b2t= 0.000
0.010 - T2= 40.800 Ton b3t= 54.850
125.229 Ton T3= 0.000 Ton b4t= 0.000
106.445 Ton T4= 0.000 Ton brazo(1)= 0.000
CUMPLE A C. AXIAL TT= 123.300 Ton brazo(2)= 18.300
CUMPLE A FLEXIÓN Mn= 34.935 T.m % de %(x-x)=
ɸMn= 31.442 Tm Trabajo %(y-y)=
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN

3-3, Eje 4-4)


Perfil Tipo I E= 2043185 kg/cm²
cm Fy= 2500 kg/cm²
cm A= 67.165 cm²
cm C= 1 -
cm ho= 19.550 cm
28.5880045 Ix= 3742.72197 cm⁴
- Sx= 374.272 cm³
Esbelto Zx= 451.213 cm³
162.95 0.00936081 0.13584136 Iy= 1830.096 cm⁴
- Sy= 126.214 cm³
Compacto λ= 32.222 m Zy= 211.297 cm³
Tm λ² 1038.272 m ϒy= 5.220 cm
Tm kc= 1.311 m J= 66.527 cm⁴
Tm cm⁶
Tm
> Cw= Mu=
174778.814
5.240 Tm
rts= 6.913
CUMPLE
cm

)
Perfil Tubular O E= 2043185 kg/cm²
cm fy= 2500 kg/cm²
cm A= 71.200 cm²
cm Ix=Iy= 44778.683 cm⁴
cm Sx=Sy= 1628.316 cm³
m Pu/ɸc.Pn= 0.727 Zx=Zy= 1717.450 cm³
Eje y-y Mux/ɸb.Mn= 0.166 rx=ry= 25.078 cm
6.073 Mux/ɸb.Mn= 0.166 J= 37781.963 cm⁴
Ton Lp= 25.445 m
40.0232063 Mp= 42.936 Tm k= 1.200 -
- Mn= 40.70789394 Tm e= 14.355 -
esbelta ɸMn= 36.637 Tm λc= 0.160 -
162.951626 % de %(x-x)= 87% fcr= 2.473 Ton/cm²
- Trabajo %(y-y)= 87% ɸc.Pn= 149.691 Ton
esbelta CUMPLE A FLEXIÓN CUMPLE A C. AXIAL
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN
1.5 Eje B-B (Tramo Eje 2-2, Eje 3-3)
Datos: Perfil Tipo I
bf= 29.00 cm
tf= 0.45 cm
tw= 2.15 cm
d= 20.00 cm
ALA= 10.86 28.5880045
b/t = 32.22 -
Esbelto
ALMA= 108.06 162.95 0.00936081 0.135841359
h/tw= 8.88 -
Compacto λ= 32.222 m
Mp= 11.280 Tm λ² 1038.272 m
Mr= 6.550 Tm kc= 1.311 m
Mn= 8.693 Tm cm⁶
> Cw= 174778.814
ɸMn= 7.82 Tm Mu= 7.190 Tm

3.6 Columna B2 (Piso 1) Ip= 37307.869


fil Relleno O Datos: Ic= 1042692.131
bf= 60.00 cm Líím.2= 85.764
d= 60.00 cm Líím.3= 142.940
tf= 0.25 cm λ= 240.000
tw= 0.30 cm Pp=PNO= 120.514
Lb= 3.000 m C3= 0.637
Pu= 85.00 Ton EI= 221451782049
Eje x-x Eje y-y k= 1.200
Mu=
6.38 6.38 Ap= 30
Es= 2043185 kg/cm² bi= 59
cm Ec= 218820 kg/cm² C1= 44.550
cm fy= 2500 kg/cm² C2= 22.500
cm f´c= 210 kg/cm² C3= 285.530
cm Ap= 65.700 cm² C4= 0.000
cm Ac= 3534.300 cm² CT= 352.580
cm Euler= 16864518 kg T1= 90.000
cm exp= 0.007 - T2= 44.550
cm Pn= 120.512 Ton T3= 0.000
cm ɸc.Pn= 102.435 Ton T4= 0.000
cm CUMPLE A C. AXIAL TT= 134.550
90% CUMPLE A FLEXIÓN Mn= 43.768
90% ɸMn= 39.392
ÓN EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y F

2.8 Columna B4 (Piso 1)


Datos: Perfil Tubular O
bf= 33.00 cm
d= 33.00 cm
tf= 0.50 cm
tw= 0.15 cm
Lb= 3.000 m Pu/ɸc.Pn= 0.733
Eje x-x Eje y-y Mux/ɸb.Mn= 0.185
Mu=
2.400 2.400Mux/ɸb.Mn= 0.185
Pu= 64.37 Ton
Ala= 32.02 40.0232063 Mp= 15.326 Tm
b/t= 64.00 - Mn= 14.44537879 Tm
esbelta ɸMn= 13.001 Tm
Alma= 69.18 162.951626 % de %(x-x)= 90%
h/t= 218.00 - Trabajo %(y-y)= 90%
esbelta CUMPLE A FLEXIÓN
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN
1.6 Eje B-B (Tramo Eje 3-3, Eje 4-4)
E= 2043185 kg/cm² Datos: Perfil Tipo I
Fy= 2500 kg/cm² bf= 29.00 cm
A= 67.165 cm² tf= 0.45 cm
C= 1 - tw= 2.15 cm
ho= 19.550 cm d= 20.00 cm
Ix= 3742.72197 cm⁴ ALA= 10.86 28.5880045
Sx= 374.272 cm³ b/t = 32.22 -
Zx= 451.213 cm³ Esbelto
Iy= 1830.096 cm⁴ ALMA= 108.06 162.95 0.00936081
Sy= 126.214 cm³ h/tw= 8.88 -
Zy= 211.297 cm³ Compacto λ=
ϒy= 5.220 cm Mp= 11.280 Tm λ²
J= 66.527 cm⁴ Mr= 6.550 Tm kc=
rts= 6.913 cm Mn= 8.693 Tm
> Cw=
CUMPLE ɸMn= 7.82 Tm Mu=

cm⁴ fcr 319.24766 3.7 Columna B3 (Piso 1)


cm⁴ Perfil Relleno O Datos:
- bf= 55.00 cm
- d= 55.00 cm
esbelto tf= 0.25 cm
Ton tw= 0.30 cm
- Lb= 3.000 m
kg*cm² Pu= 101.00 Ton
- 0.6365 Eje x-x Eje y-y
Mu=
cm 1.25 1.25
cm Es= 2043185 kg/cm²
Ton b1c= 0.000 cm Ec= 218820 kg/cm²
Ton b2c= 0.000 cm fy= 2500 kg/cm²
Ton b3c= 0.000 cm f´c= 210 kg/cm²
Ton b4c= 0.000 cm Ap= 60.200 cm²
Ton b1t= 29.850 cm Ac= 2964.800 cm²
Ton b2t= 0.000 cm Euler= 12290097 kg
Ton b3t= 59.850 cm exp= 0.010 -
Ton b4t= 0.000 cm Pn= 125.229 Ton
Ton brazo(1)= 0.000 cm ɸc.Pn= 106.445 Ton
Ton brazo(2)= 19.967 cm CUMPLE A C. AXIAL
T.m % de %(x-x)= 97% CUMPLE A FLEXIÓN
Tm Trabajo %(y-y)= 97%
S COMBINADOS DE C. AXIAL Y FLEXIÓN EL ELEMENTO CUMPLE A ESFU

E= 2043185 kg/cm²
fy= 2500 kg/cm²
A= 42.600 cm²
Ix=Iy= 9533.950 cm⁴
Sx=Sy= 577.815 cm³
Zx=Zy= 613.050 cm³
rx=ry= 14.960 cm
J= 8073.355 cm⁴
Lp= 15.205 m
k= 1.200 -
e= 24.064 -
λc= 0.268 -
fcr= 2.426 Ton/cm²
ɸc.Pn= 87.845 Ton
CUMPLE A C. AXIAL
DOS DE C. AXIAL Y FLEXIÓN
Perfil Tipo I E= 2043185 kg/cm²
Fy= 2500 kg/cm²
A= 67.165 cm²
C= 1 -
ho= 19.550 cm
Ix= 3742.72197 cm⁴
Sx= 374.272 cm³
Zx= 451.213 cm³
0.135841359 Iy= 1830.096 cm⁴
Sy= 126.214 cm³
32.222 m Zy= 211.297 cm³
1038.272 m ϒy= 5.220 cm
1.311 m J= 66.527 cm⁴
174778.814 cm⁶ rts= 6.913 cm
5.240 Tm CUMPLE

Ip= 28702.317 cm⁴ fcr 379.9311 3.8 Columna B4 (Piso 1)


Ic= 733849.767 cm⁴ Perfil Relleno O Datos:
Líím.2= 85.764 - bf=
Líím.3= 142.940 - d=
λ= 220.000 esbelto tf=
Pp=PNO= 125.235 Ton tw=
C3= 0.640 - Lb=
EI= 161384036773 kg*cm² Pu=
k= 1.200 - 0.63980165
Mu=
Ap= 28 cm
bi= 54 cm Es=
C1= 40.800 Ton b1c= 0.000 cm Ec=
C2= 20.625 Ton b2c= 0.000 cm fy=
C3= 239.504 Ton b3c= 0.000 cm f´c=
C4= 0.000 Ton b4c= 0.000 cm Ap=
CT= 300.929 Ton b1t= 27.350 cm Ac=
T1= 82.500 Ton b2t= 0.000 cm Euler=
T2= 40.800 Ton b3t= 54.850 cm exp=
T3= 0.000 Ton b4t= 0.000 cm Pn=
T4= 0.000 Ton brazo(1)= 0.000 cm ɸc.Pn=
TT= 123.300 Ton brazo(2)= 18.300 cm CUMPLE A C. A
Mn= 34.935 T.m % de %(x-x)= 98% CUMPLE A FLE
ɸMn= 31.442 Tm Trabajo %(y-y)= 98%
MENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN EL ELEM
a B4 (Piso 1) Ip= 28702.317 cm⁴ fcr 379.9311
Ic= ### cm⁴ Perfil Relleno O
55.00 cm Líím.2= 85.764 -
55.00 cm Líím.3= 161.400 -
0.25 cm λ= 220.000 esbelto
0.30 cm Pp=PNO= 125.235 Ton
3.000 m C3= 0.640 -
71.00 Ton EI= ### kg*cm²
Eje x-x Eje y-y k= 1.200 - 0.6398017
10.54 10.54 Ap= 28 cm
2043185 kg/cm² bi= 54 cm
218820 kg/cm² C1= 40.800 Ton b1c= 0.000 cm
2500 kg/cm² C2= 20.625 Ton b2c= 0.000 cm
210 kg/cm² C3= 239.504 Ton b3c= 0.000 cm
60.200 cm² C4= 0.000 Ton b4c= 0.000 cm
2964.800 cm² CT= 300.929 Ton b1t= 27.350 cm
12290097 kg T1= 82.500 Ton b2t= 0.000 cm
0.010 - T2= 40.800 Ton b3t= 54.850 cm
125.229 Ton T3= 0.000 Ton b4t= 0.000 cm
106.445 Ton T4= 0.000 Ton brazo(1)= 0.000 cm
CUMPLE A C. AXIAL TT= 123.300 Ton brazo(2)= 18.300 cm
CUMPLE A FLEXIÓN Mn= 34.935 T.m % de %(x-x)= 96%
ɸMn= 31.442 Tm Trabajo %(y-y)= 96%
EL ELEMENTO CUMPLE A ESFUERZOS COMBINADOS DE C. AXIAL Y FLEXIÓN