Table of contents
Ruangan K1 500 LUX
Ruangan K1 500 LUX
Philips Lighting - TBS417 2xTL5-50W HFP C6 (2xTL5-50W/830)...................................................................................................................3
Site 1
Building 1
Storey 1
Room 1
Room summary....................................................................................................................................................................................... 6
Luminaire layout plan.............................................................................................................................................................................. 7
Luminaire parts list.................................................................................................................................................................................. 9
Views..................................................................................................................................................................................................... 10
Workplane 1 / Perpendicular illuminance (adaptive)............................................................................................................................. 12
Page 2
Ruangan K1 500 LUX 4/21/2018
Site 1 / Building 1 / Storey 1 / Philips Lighting TBS417 2xTL5-50W HFP C6 2xTL5-50W/830 / Philips Lighting - TBS417 2xTL5-50W
HFP C6 (2xTL5-50W/830)
90° 90°
75° 75°
60° 60°
160
45° 45°
240
320
cd/klm η = 59%
C0 - C180 C90 - C270
Page 3
Ruangan K1 500 LUX 4/21/2018
Site 1 / Building 1 / Storey 1 / Philips Lighting TBS417 2xTL5-50W HFP C6 2xTL5-50W/830 / Philips Lighting - TBS417 2xTL5-50W
HFP C6 (2xTL5-50W/830)
300
250
200
150
100
50
E(0°) 10200
0.97 E(C90) 44.2° 1881
0.50 0.96 E(C0) 43.8° 1930
E(0°) 2550
1.9 E(C90) 44.2° 470
1.0 1.9 E(C0) 43.8° 483
E(0°) 1133
2.9 E(C90) 44.2° 209
1.5 2.9 E(C0) 43.8° 214
E(0°) 638
3.9 E(C90) 44.2° 118
2.0 3.8 E(C0) 43.8° 121
E(0°) 408
4.9 E(C90) 44.2° 75
2.5 4.8 E(C0) 43.8° 77
E(0°) 283
5.8 E(C90) 44.2° 52
3.0 5.8 E(C0) 43.8° 54
Distance [m] Cone diameter [m] Illuminance [lx]
C0 - C180 (Beam angle: 87.6°)
C90 - C270 (Beam angle: 88.4°)
Page 4
Ruangan K1 500 LUX 4/21/2018
Site 1 / Building 1 / Storey 1 / Philips Lighting TBS417 2xTL5-50W HFP C6 2xTL5-50W/830 / Philips Lighting - TBS417 2xTL5-50W
HFP C6 (2xTL5-50W/830)
C270 C90
300
400
500
C315 C0 C45
cd/m²
g = 65.0° g = 75.0° g = 85.0°
2H 2H 19.1 20.0 19.4 20.2 20.4 19.1 20.0 19.4 20.2 20.4
3H 19.0 19.8 19.3 20.0 20.3 19.0 19.8 19.2 20.0 20.2
4H 18.9 19.7 19.2 19.9 20.2 18.9 19.6 19.2 19.9 20.2
6H 18.8 19.5 19.2 19.8 20.1 18.8 19.5 19.1 19.8 20.1
8H 18.8 19.4 19.1 19.7 20.0 18.8 19.4 19.1 19.7 20.0
12H 18.8 19.4 19.1 19.7 20.0 18.7 19.4 19.1 19.7 20.0
4H 2H 18.9 19.7 19.3 20.0 20.2 18.9 19.7 19.2 19.9 20.2
3H 18.8 19.4 19.2 19.7 20.1 18.8 19.4 19.1 19.7 20.0
4H 18.7 19.3 19.1 19.6 20.0 18.7 19.3 19.1 19.6 19.9
6H 18.7 19.1 19.1 19.5 19.9 18.6 19.1 19.0 19.5 19.9
8H 18.6 19.0 19.0 19.4 19.8 18.6 19.0 19.0 19.4 19.8
12H 18.6 19.0 19.0 19.4 19.8 18.6 18.9 19.0 19.3 19.8
8H 4H 18.6 19.0 19.0 19.4 19.8 18.6 19.0 19.0 19.4 19.8
6H 18.5 18.9 19.0 19.3 19.7 18.5 18.8 19.0 19.3 19.7
8H 18.5 18.8 19.0 19.2 19.7 18.5 18.8 18.9 19.2 19.7
12H 18.4 18.7 18.9 19.2 19.6 18.4 18.7 18.9 19.1 19.6
12H 4H 18.6 19.0 19.0 19.4 19.8 18.6 18.9 19.0 19.3 19.8
6H 18.5 18.8 19.0 19.2 19.7 18.5 18.8 18.9 19.2 19.7
8H 18.4 18.7 18.9 19.2 19.6 18.4 18.7 18.9 19.1 19.6
Variation of the observer position for the luminaire distances S
S = 1.0H +1.8 / -6.6 +2.2 / -7.9
S = 1.5H +3.7 / -19.5 +3.7 / -22.9
S = 2.0H +5.7 / -24.9 +5.7 / -28.0
The UGR values are calculated in acc. with CIE Publ. 117. Spacing-
to-height ratio = 0.25
Page 5
Ruangan K1 500 LUX 4/21/2018
Room 1
Clearance height: 3.100 m to 3.500 m, Reflection factors: Ceiling 70.0%, Walls 44.0%, Floor 63.8%, Light loss factor: 0.80
Workplane
Surface Result Average (Target) Min Max Min/average Min/max
1 Workplane 1 Perpendicular illuminance (adaptive) [lx] 518 (≥ 300) 0.08 654 0.00 0.00
Height: 0.800 m, Wall zone: 0.000 m
Lighting power density: 13.26 W/m² = 2.56 W/m²/100 lx (Floor area of room 207.36 m²)
The energy consumption quantities refer to the lights planned for the room without taking into account light scenes and their dimming levels.
Consumption: 3350 - 5300 kWh/a of maximum 7300 kWh/a
Page 6
Ruangan K1 500 LUX 4/21/2018
Room 1
Page 7
Ruangan K1 500 LUX 4/21/2018
Page 8
Ruangan K1 500 LUX 4/21/2018
Room 1
# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]
Page 9
Ruangan K1 500 LUX 4/21/2018
Room 1
Storey 1 (37)
Storey 1 (34)
Page 10
Ruangan K1 500 LUX 4/21/2018
Storey 1 (35)
Storey 1 (36)
Page 11
Ruangan K1 500 LUX 4/21/2018
Page 12
Ruangan K1 500 LUX 4/21/2018
Isolines [lx]
Scale: 1 : 100
Page 13
Ruangan K1 500 LUX 4/21/2018
Scale: 1 : 100
Page 14
Ruangan K1 500 LUX 4/21/2018
Scale: 1 : 100
Page 15
Alasan Pemilihan Lampu :