Features
1. Provides maximum coverage areas of 14 ft.
(4,27 m) by 14 ft. (4,27 m) 196 ft2 (18,21 m2).
2. Can be installed recessed below finished ceil-
ings with 1 2² (13 mm) adjustment. Available in
brass, chrome, black plated and white polyester N252 EC Pendent
coated finishes.
3. 165 °F (74 °C) and 212 °F (100 °C) temperature
ratings.
4. Listed by Underwriters’ Laboratories Inc. and by
Underwriters’ Laboratories for use in Canada.
5. cULus Listed for unobstructed or
noncombustible obstructed construction.
The Reliable Automatic Sprinkler Co., Inc. 525NorthMacQuestenParkway, MountVernon, NewYork, 10552
Installation
Model N252 sprinklers are to be installed as N252 EC pendent and recessed pendent sprinklers
shown. Model FP escutcheons, illustrated herewith, use only the Model N wrench (ref. Fig. 3). Use of
are the only recessed escutcheons to be used with wrenches other than that specified may damage these
Model N252 EC Recessed Pendent Sprinklers. Use sprinklers. Sprinklers should be tightened between 22
of any other recessed escutcheon will void all ap- to 30 ft. - lbs. (29,8 - 40,7 Nm) torque. Sprinklers not
provals and warranties. When handling sprinklers, tightened to recommended torque may cause leak-
hold sprinklers only on frame arms and do not apply age or impairment of the sprinklers. Damaged sprin-
any force on the link assembly. For installing Model klers must be replaced immediately.
Link Assembly
Frame Arm
Model N Wrench
2.
Technical Data
Maximum
Temperature Sprinkler
Sprinkler Ambient Nominal Orifice Thread Sprinkler Ht.
Type Rating Identification
Model Ceiling Temp. K-Factor Size Size Inch (mm)
Number (SIN)
°F °C °F °C
Pendent/ 165 74 100 38
1² NPT
N252 EC Recessed 25.2 1 inch 3.6 (91,5) RA0852
212 100 150 66 (R1)
Pendent
Design Criteria
The Models N252 EC Pendent and Recessed Pen- • The minimum clearance between the deflector
dent Sprinklers are cULus Listed control-mode, ex- and the top of storage is 3 ft. (0,92m). For clear-
tended coverage density/area sprinklers for ances of 3 ft. (0,92m) up to 4 ft. (1,21m), the mini-
installation in accordance with the extended cover- mum design pressure is 22 psi (1,52 bar). For
age pendent spray sprinkler criteria of NFPA 13, or clearances of 4 ft. (1,21m) and greater, the mini-
other applicable NFPA standards, when used in com- mum design pressure is established by the mini-
bination with the following guidelines:
mum flow requirement (however, the pressure
• Protection for extra hazard and high-piled stor- can never be less than 7 psi (0,48 bar)).
age occupancies using NFPA 13 density/area
criteria. • Available temperature ratings are Ordinary, 165
°F (74 °C) and Intermediate, 212 °F (100 °C). Se-
• Suitable for use in wet pipe systems, and in lection of temperature rating is based on the ex-
dry-pipe and preaction systems as specifically pected maximum ambient temperature
allowed for pendent sprinklers in NFPA 13. exposure, or in accordance with the high-piled
• cULus Listed for “unobstructed” or storage density/area curve requirements speci-
non-combustible “obstructed” construction. fied in Chapter 12 of the 2002 edition of NFPA 13.
Given that the Model N252 EC sprinklers are spe- In accordance with the listing of the sprinkler, the
cifically listed for noncombustible obstructed density curves normally associated with high
construction, they may be installed within trusses temperature rated sprinklers [286°F (141°C)]
or bar joists having noncombustible web mem- may be used with either the ordinary or intermedi-
bers greater than 1 inch (25.4 mm) when apply- ate temperature rating of the N252 EC sprinklers.
ing the “Four Times Rule” as defined in NFPA 13 • The obstruction criteria in NFPA 13 for Extended
under “Obstructions to Sprinkler Discharge Pat- Coverage Pendent Sprinklers shall be used for
tern Development.” the locating and positioning Model N252 EC
• Maximum area of coverage per sprinklers is 196 sprinklers relative to obstructions.
ft2 (18.2 m2); minimum area of coverage is 100 ft2
Maintenance
(9.3 m2). Maximum spacing between sprinklers
is 14 ft (4.3 m); minimum spacing between sprin- The Models N252 EC Pendent and Recessed Pen-
klers is 8 ft (2.44 m). dent Sprinklers should be inspected quarterly and the
sprinkler system maintained in accordance with
• Minimum flow requirement is based on the de- NFPA 25, and local jurisdictional requirements. Do
sign density applied over the actual area of cov- not clean sprinklers with soap and water, ammonia, or
erage per sprinkler. For example, a design any other cleaning fluids or solvents. Remove dust by
density of 0.43 gpm/ft2 (17.5 mm/min) applied using a soft brush or gentle vacuuming. Remove any
over 14 ft x 14 ft (4.3 m x 4.3 m) spacing, or 196 ft2 sprinkler that has been painted (other than fac-
(18.2 m2), would require a minimum sprinkler de- tory-applied) or otherwise altered after leaving the
factory. A stock of spare sprinklers should be main-
sign flow rate and pressure of 84.3 gpm (319.2
tained to allow quick replacement of damaged or op-
L/min) at 11.2 psi (0.77 bar). erated sprinklers. Prior to installation, sprinklers
• Maximum working pressure - 175 psi (12.1 bar). should be maintained in the original cartons and
packaging until used to minimize the potential for
damage to sprinkler that would cause improper oper-
ation or non-operation.
3.
Reliable...For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
ProductsmanufacturedanddistributedbyReliablehavebeenprotectinglifeandpropertyforover80years,andareinstalledandservicedbythemosthighlyqualifiedandreputa-
ble sprinkler contractors located throughout the United States, Canada and foreign countries.