Company: Date: 15/10/2019

Anchor Designer™ Engineer: Page: 1/6


Software Project:
Version 2.8.7094.0 Address:
Phone:
E-mail:

1.Project information
Customer company: Project description:
Customer contact name: Location:
Customer e-mail: Fastening description:
Comment:

2. Input Data & Anchor Parameters


General Base Material
Design method:ACI 318-14 Concrete: Normal-weight
Units: SI units (metric) Concrete thickness, h (mm): 1000
State: Uncracked
Anchor Information: Compressive strength, f’c (MPa): 20.68
Anchor type: Cast-in-place Ψc,V: 1.4
Material: F1554 Grade 36 Reinforcement condition: A tension, A shear
Diameter (inch): 0.625 Supplemental reinforcement: No
Effective Embedment depth, hef (mm): 210 Reinforcement provided at corners: No
Anchor category: - Ignore concrete breakout in tension: No
Anchor ductility: Yes Ignore concrete breakout in shear: No
hmin (mm): 244 Ignore 6do requirement: No
Cmin (mm): 95 Build-up grout pad: No
Smin (mm): 95
Base Plate
Length x Width x Thickness (mm): 250 x 250 x 19
Yield stress: 245.00 N/mm²

Profile type/size: W6X20

Recommended Anchor
Anchor Name: Heavy Hex Bolt - 5/8"Ø Heavy Hex Bolt, F1554 Gr. 36

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 15/10/2019
Anchor Designer™ Engineer: Page: 2/6
Software Project:
Version 2.8.7094.0 Address:
Phone:
E-mail:

Load and Geometry


Load factor source: ACI 318 Section 5.3
Load combination: not set
Seismic design: No
Anchors subjected to sustained tension: Not applicable
Apply entire shear load at front row: No
Anchors only resisting wind and/or seismic loads: No

Strength level loads:

Nua [kN]: -34.00


Vuax [kN]: 0.00
Vuay [kN]: 2.00
Mux [kNm]: 0.00
Muy [kNm]: 15.00
Muz [kNm]: 0.00

<Figure 1>

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 15/10/2019
Anchor Designer™ Engineer: Page: 3/6
Software Project:
Version 2.8.7094.0 Address:
Phone:
E-mail:

<Figure 2>

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 15/10/2019
Anchor Designer™ Engineer: Page: 4/6
Software Project:
Version 2.8.7094.0 Address:
Phone:
E-mail:

3. Resulting Anchor Forces


Anchor Tension load, Shear load x, Shear load y, Shear load combined,
Nua (kN) Vuax (kN) Vuay (kN) √(Vuax)²+(Vuay)² (kN)
1 35.7 0.0 0.5 0.5
2 35.7 0.0 0.5 0.5
3 4.0 0.0 0.5 0.5
4 4.0 0.0 0.5 0.5
Sum 79.5 0.0 2.0 2.0
Maximum concrete compression strain (‰): 0.49 <Figure 3>
Maximum concrete compression stress (N/mm²): 14.58
Resultant tension force (kN): 79.49
Resultant compression force (kN): 113.49
Eccentricity of resultant tension forces in x-axis, e'Nx (mm): 40
Eccentricity of resultant tension forces in y-axis, e'Ny (mm): 0
Eccentricity of resultant shear forces in x-axis, e'Vx (mm): 0
Eccentricity of resultant shear forces in y-axis, e'Vy (mm): 0

4. Steel Strength of Anchor in Tension (Sec. 17.4.1)


Nsa (kN) Nsa (kN)
58.27 0.75 43.70

5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.4.2)


Nb = k c a f’chef1.5 (Eq. 17.4.2.2a)
kc a f’c (MPa) hef (mm) Nb (kN)
10.0 1.00 20.68 67 24.86
Ncbg = (ANc / ANco) ec,N ed,N c,N cp,N Nb (Sec. 17.3.1 & Eq. 17.4.2.1b)
ANc (mm2) ANco (mm2) ca,min (mm) ec,N ed,N c,N cp,N Nb (kN) Ncbg (kN)
114000 40000 100 0.715 1.000 1.25 1.000 24.86 0.75 47.50

6. Pullout Strength of Anchor in Tension (Sec. 17.4.3)


Npn = c,PNp = c,P8A brgf’c (Sec. 17.3.1, Eq. 17.4.3.1 & 17.4.3.4)
c,P Abrg (mm2) f’c (MPa) Npn (kN)
1.4 433 20.68 0.70 70.20

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 15/10/2019
Anchor Designer™ Engineer: Page: 5/6
Software Project:
Version 2.8.7094.0 Address:
Phone:
E-mail:

8. Steel Strength of Anchor in Shear (Sec. 17.5.1)


Vsa (kN) grout grout V sa (kN)

34.99 1.0 0.65 22.74

9. Concrete Breakout Strength of Anchor in Shear (Sec. 17.5.2)


Shear perpendicular to edge in y-direction:
Vby = min|0.6(le / da)0.2 da a f’cca11.5; 9 a f’cca11.5| (Eq. 10.6.5.2.2a & Eq. 10.6.5.2.2b)
le (mm) da (mm) a f’c (MPa) ca1 (mm) Vby (kN)
127 16 1.00 20.68 280 74.80
Vcbgy = (AVc / AVco) ec,V ed,V c,V h,VV by (Sec. 17.3.1 & Eq. 17.5.2.1b)
AVc (mm2) AVco (mm2) ec,V ed,V c,V h,V Vby (kN) Vcbgy (kN)
126000 352800 1.000 0.771 1.400 1.000 74.80 0.75 21.64

Shear parallel to edge in y-direction:


Vbx = min|0.6(le / da)0.2 da a f’cca11.5; 9 a f’cca11.5| (Eq. 10.6.5.2.2a & Eq. 10.6.5.2.2b)
le (mm) da (mm) a f’c (MPa) ca1 (mm) Vbx (kN)
127 16 1.00 20.68 100 15.96
Vcbgy = (2)(AVc / AVco) ec,V ed,V c,V h,VV bx (Sec. 17.3.1, 17.5.2.1(c) & Eq. 17.5.2.1b)
AVc (mm2) AVco (mm2) ec,V ed,V c,V h,V Vbx (kN) Vcbgy (kN)
57000 45000 1.000 1.000 1.400 1.000 15.96 0.75 42.47

10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.5.3)


Vcpg = kcpNcbg = kcp(ANc / ANco) ec,N ed,N c,N cp,N Nb (Sec. 17.3.1 & Eq. 17.5.3.1b)
kcp ANc (mm2) ANco (mm2) ec,N ed,N c,N cp,N Nb (kN) Vcpg (kN)
2.0 114000 40000 1.000 1.000 1.250 1.000 24.86 0.70 124.01

11. Results
Interaction of Tensile and Shear Forces (Sec. 17.6.)
Tension Factored Load, Nua (kN) Design Strength, øNn (kN) Ratio Status
Steel 35.72 43.70 0.82 Pass
Concrete breakout 79.49 47.50 1.67 Fail (Governs)
Pullout 35.72 70.20 0.51 Pass

Shear Factored Load, Vua (kN) Design Strength, øVn (kN) Ratio Status
Steel 0.50 22.74 0.02 Pass
T Concrete breakout y+ 2.00 21.64 0.09 Pass (Governs)
|| Concrete breakout x- 1.00 42.47 0.02 Pass (Governs)
Pryout 2.00 124.01 0.02 Pass

Interaction check Nua/ Nn Vua/ Vn Combined Ratio Permissible Status


Sec. 17.6..1 1.67 0.00 167.4% 1.0 Fail

FAIL! Selected anchor type and embedment do not meet the selected design criteria.

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 15/10/2019
Anchor Designer™ Engineer: Page: 6/6
Software Project:
Version 2.8.7094.0 Address:
Phone:
E-mail:

12. Warnings
- Calculated concrete compression stress exceeds the permissible bearing stress of diameter 0.85f’c per ACI 318 Section 22.8.3.2.

- Designer must exercise own judgement to determine if this design is suitable.

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.