You are on page 1of 1840

Preface

Open Source Software

Table of Contents

SIPROTEC 5 Introduction 1
Overcurrent Protection Basic Structure of the Function 2
7SJ82/7SJ85
System Functions 3
V7.90 and higher Applications 4
Function-Group Types 5
Manual
Protection and Automation Functions 6
Capacitor Bank Protection 7
Control Functions 8
Supervision Functions 9
Measured Values, Energy Values, and
Supervision of the Primary System 10
Functional Tests 11
Technical Data 12
Appendix A
Glossary

Index

C53000-G5040-C017-A
NOTE

i For your own safety, observe the warnings and safety instructions contained in this document, if available.

Disclaimer of Liability Copyright


Subject to changes and errors. The information given in Copyright © Siemens 2019. All rights reserved.
this document only contains general descriptions and/or The disclosure, duplication, distribution and editing of this
performance features which may not always specifically document, or utilization and communication of the content
reflect those described, or which may undergo modifica- are not permitted, unless authorized in writing. All rights,
tion in the course of further development of the products. including rights created by patent grant or registration of a
The requested performance features are binding only when utility model or a design, are reserved.
they are expressly agreed upon in the concluded contract.
Document version: C53000-G5040-C017-A.01 Trademarks
Edition: 06.2019
SIPROTEC™, DIGSI™, SIGRA™, SIGUARD™, SAFIR™, SICAM™,
Version of the product described: V7.90 and higher and MindSphere™ are trademarks of Siemens AG. Any
unauthorized use is prohibited. All other designations in
this document may represent trademarks whose use by
third parties for their own purposes may violate the propri-
etary rights of the owner.
Preface

Purpose of the Manual


This manual describes the protection, automation, control, and monitoring functions of the SIPROTEC 5
devices.

Target Audience
Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-
tenance of automation, selective protection and control equipment, and operational crew in electrical installa-
tions and power plants.

Scope
This manual applies to the SIPROTEC 5 device family.

Further Documentation

[dwprefdm-221012-01.tif, 3, en_US]

• Device manuals
Each Device manual describes the functions and applications of a specific SIPROTEC 5 device. The printed
manual and the online help for the device have the same informational structure.

• Hardware manual
The Hardware manual describes the hardware building blocks and device combinations of the SIPROTEC 5
device family.

• Operating manual
The Operating manual describes the basic principles and procedures for operating and assembling the
devices of the SIPROTEC 5 range.

SIPROTEC 5, 7SJ82/7SJ85, Manual 3


C53000-G5040-C017-A, Edition 06.2019
Preface

• Communication protocol manual


The Communication protocol manual contains a description of the protocols for communication within
the SIPROTEC 5 device family and to higher-level network control centers.

• Product information
The Product information includes general information about device installation, technical data, limiting
values for input and output modules, and conditions when preparing for operation. This document is
provided with each SIPROTEC 5 device.

• Engineering Guide
The Engineering Guide describes the essential steps when engineering with DIGSI 5. In addition, the Engi-
neering Guide shows you how to load a planned configuration to a SIPROTEC 5 device and update the
functionality of the SIPROTEC 5 device.

• DIGSI 5 online help


The DIGSI 5 online help contains a help package for DIGSI 5 and CFC.
The help package for DIGSI 5 includes a description of the basic operation of software, the DIGSI princi-
ples and editors. The help package for CFC includes an introduction to CFC programming, basic examples
of working with CFC, and a reference chapter with all the CFC blocks available for the SIPROTEC 5 range.

• SIPROTEC 5/DIGSI 5 Tutorial


The tutorial on the DVD contains brief information about important product features, more detailed infor-
mation about the individual technical areas, as well as operating sequences with tasks based on practical
operation and a brief explanation.

• SIPROTEC 5 catalog
The SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5.

• Selection guide for SIPROTEC and Reyrolle


The selection guide offers an overview of the device series of the Siemens protection devices, and a
device selection table.

Indication of Conformity

This product complies with the directive of the Council of the European Communities
on harmonization of the laws of the Member States concerning electromagnetic
compatibility (EMC Directive 2014/30/EU), restriction on usage of hazardous
substances in electrical and electronic equipment (RoHS Directive 2011/65/EU), and
electrical equipment for use within specified voltage limits (Low Voltage Directive
2014/35/EU).
This conformity has been proved by tests performed according to the Council Directive
in accordance with the product standard EN 60255-26 (for EMC directive), the standard
EN 50581 (for RoHS directive), and with the product standard EN 60255-27 (for Low
Voltage Directive) by Siemens.
The device is designed and manufactured for application in an industrial environment.
The product conforms with the international standards of IEC 60255 and the German
standard VDE 0435.

Standards
IEEE Std C 37.90
The technical data of the product is approved in accordance with UL.
For more information about the UL database, see ul.com
You can find the product with the UL File Number E194016.

IND. CONT. EQ.


69CA

4 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Preface

Additional Support
For questions about the system, please contact your Siemens sales partner.

Support
Our Customer Support Center provides a 24-hour service.
Siemens AG
Customer Support Center
Humboldtstrasse 59
90459 Nuremberg
Germany
E-mail: support.energy@siemens.com

Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG Phone: +49 (911) 433-7415
Siemens Power Academy TD Fax: +49 (911) 433-7929
Humboldtstrasse 59 E-mail: poweracademy@siemens.com
90459 Nuremberg Internet: www.siemens.com/poweracademy
Germany

Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:

! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.

SIPROTEC 5, 7SJ82/7SJ85, Manual 5


C53000-G5040-C017-A, Edition 06.2019
Preface

NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.

NOTE

i Important information about the product, product handling or a certain section of the documentation
which must be given particular attention.

Qualified Electrical Engineering Personnel


Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.

Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:

• Proper transport

• Proper storage, setup and installation

• Proper operation and maintenance


When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:

• The equipment must be grounded at the grounding terminal before any connections are made.

• All circuit components connected to the power supply may be subject to dangerous voltage.

• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).

• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.

• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.

Used Symbols on Device

No. Symbol Description

1 Direct current, IEC 60417-5031

2 Alternating current, IEC 60417-5032

3 Direct and alternating current, IEC 60417-5033

4 Earth (ground) terminal, IEC 60417-5017

5 Protective conductor terminal, IEC 60417-5019

6 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Preface

No. Symbol Description

6 Caution, risk of electric shock

7 Caution, risk of danger, ISO 7000-0434

8 Protective Insulation, IEC 60417-5172, Safety Class II devices

9 Guideline 2002/96/EC for electrical and electronic devices

10 Guideline for the Eurasian Market

SIPROTEC 5, 7SJ82/7SJ85, Manual 7


C53000-G5040-C017-A, Edition 06.2019
8 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
Open Source Software

The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the soft-
ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years
since purchase of the Product. We are liable for the Product including the Open Source Software contained in
it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software
beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects
resulting from modifications to the Open Source Software by you or third parties is excluded. We do not
provide any technical support for the Product if it has been modified.
When using DIGSI 5 in online mode, you are provided with the option to go to the main menu Show open
source software information and read and display the Readme_OSS file containing the original license text
and copyright information.
To do this, the following steps are necessary:

• Switch to online mode.

• Select the device.

• Select Online in the menu bar.

• Click Show open source software information.

NOTE

i To read the Readme_OSS file, a PDF viewer must be installed on the computer.
In order to operate SIPROTEC 5 devices, a valid DIGSI 5 license is required.

SIPROTEC 5, 7SJ82/7SJ85, Manual 9


C53000-G5040-C017-A, Edition 06.2019
10 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
Table of Contents

Preface.......................................................................................................................................................... 3

Open Source Software..................................................................................................................................9

1 Introduction................................................................................................................................................43
1.1 General.............................................................................................................................44
1.2 Properties of SIPROTEC 5................................................................................................... 46

2 Basic Structure of the Function.................................................................................................................. 47


2.1 Function Embedding in the Device.................................................................................... 48
2.2 Adjustment of Application Templates/Functional Scope..................................................... 55
2.3 Function Control............................................................................................................... 57
2.4 Text Structure and Reference Number for Settings and Indications.....................................61
2.5 Information Lists............................................................................................................... 63

3 System Functions....................................................................................................................................... 65
3.1 Indications........................................................................................................................ 66
3.1.1 General....................................................................................................................... 66
3.1.2 Reading Indications on the On-Site Operation Panel..................................................... 66
3.1.3 Reading Indications from the PC with DIGSI 5............................................................... 68
3.1.4 Displaying Indications.................................................................................................. 69
3.1.5 Logs............................................................................................................................ 72
3.1.5.1 General..................................................................................................................72
3.1.5.2 Operational Log..................................................................................................... 73
3.1.5.3 Fault Log................................................................................................................75
3.1.5.4 Ground-Fault Log................................................................................................... 76
3.1.5.5 User Log................................................................................................................ 78
3.1.5.6 Setting-History Log.................................................................................................80
3.1.5.7 Communication Log............................................................................................... 81
3.1.5.8 Communication-Supervision Log............................................................................ 83
3.1.5.9 Security Log........................................................................................................... 84
3.1.5.10 Device-Diagnosis Log............................................................................................. 85
3.1.6 Saving and Deleting the Logs....................................................................................... 86
3.1.7 Spontaneous Indication Display in DIGSI 5....................................................................88
3.1.8 Spontaneous Fault Display on the On-Site Operation Panel...........................................88
3.1.9 Stored Indications in the SIPROTEC 5 Device.................................................................90
3.1.10 Resetting Stored Indications of the Function Group ..................................................... 91
3.1.11 Test Mode and Influence of Indications on Substation Automation Technology ............91
3.2 Measured-Value Acquisition.............................................................................................. 92
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups...........................................94
3.3.1 Overview.....................................................................................................................94
3.3.2 Sampling-Frequency Tracking...................................................................................... 94

SIPROTEC 5, 7SJ82/7SJ85, Manual 11


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

3.3.3 Frequency Tracking Groups..........................................................................................97


3.3.4 Frequency Tracking Groups – Interpretation of Measured Values................................ 101
3.4 Processing Quality Attributes...........................................................................................103
3.4.1 Overview...................................................................................................................103
3.4.2 Quality Processing/Affected by the User for Received GOOSE Values........................... 105
3.4.3 Quality Processing/Affected by the User in CFC Charts................................................ 111
3.4.4 Quality Processing/Affected by the User in Internal Device Functions.......................... 115
3.5 Fault Recording...............................................................................................................119
3.5.1 Overview of Functions .............................................................................................. 119
3.5.2 Structure of the Function........................................................................................... 119
3.5.3 Function Description..................................................................................................119
3.5.4 Application and Setting Notes....................................................................................122
3.5.5 Settings.....................................................................................................................125
3.5.6 Information List......................................................................................................... 126
3.6 Protection Communication..............................................................................................127
3.6.1 Overview...................................................................................................................127
3.6.2 Protection-Communication Structure ........................................................................ 127
3.6.3 Protection Interface and Protection Topology............................................................. 128
3.6.3.1 Overview of Functions......................................................................................... 128
3.6.3.2 Structure of the Function..................................................................................... 128
3.6.3.3 Function Description............................................................................................ 129
3.6.3.4 Initialization and Configuration of the Protection Interface in DIGSI 5 ................... 138
3.6.3.5 Device-Combination Settings................................................................................139
3.6.3.6 Selecting the Connection..................................................................................... 142
3.6.3.7 Setting Notes for the Protection Interface............................................................. 143
3.6.3.8 Routing Information in DIGSI 5............................................................................. 146
3.6.3.9 Diagnostic Measured Values of the Protection Interface........................................ 151
3.6.3.10 Diagnostic Data for the Protection Interface..........................................................155
3.6.3.11 Settings............................................................................................................... 160
3.6.3.12 Information List................................................................................................... 161
3.7 Date and Time Synchronization....................................................................................... 164
3.7.1 Overview of Functions............................................................................................... 164
3.7.2 Structure of the Function........................................................................................... 164
3.7.3 Function Description..................................................................................................164
3.7.4 Application and Setting Notes....................................................................................167
3.7.5 Settings.....................................................................................................................170
3.7.6 Information List......................................................................................................... 171
3.8 User-Defined Objects...................................................................................................... 172
3.8.1 Overview...................................................................................................................172
3.8.2 Basic Data Types........................................................................................................ 173
3.8.3 Pulse and Energy Metered Values, Transformer Taps.................................................. 176
3.8.4 Additional Data Types................................................................................................ 176
3.8.5 External Signals......................................................................................................... 176
3.9 Other Functions.............................................................................................................. 178
3.9.1 Signal Filtering and Chatter Blocking for Input Signals................................................ 178
3.9.2 Acquisition Blocking and Manual Updating.................................................................182
3.9.3 Persistent Commands................................................................................................ 185
3.9.4 Device Logout........................................................................................................... 185
3.9.4.1 Overview............................................................................................................. 185

12 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

3.9.4.2 Application and Setting Notes.............................................................................. 186


3.9.4.3 Information List................................................................................................... 188
3.10 General Notes for Setting the Threshold Value of Protection Functions.............................189
3.10.1 Overview ..................................................................................................................189
3.10.2 Modifying the Transformer Ratios in DIGSI 5.............................................................. 189
3.10.3 Changing the Transformation Ratios of the Transformer on the Device....................... 196
3.11 Device Settings............................................................................................................... 198
3.11.1 General Device Settings............................................................................................. 198
3.11.1.1 Overview ............................................................................................................ 198
3.11.1.2 Application and Setting Notes.............................................................................. 199
3.11.1.3 Settings............................................................................................................... 200
3.11.1.4 Information List................................................................................................... 200
3.11.2 Settings-Group Switching.......................................................................................... 201
3.11.2.1 Overview of Functions .........................................................................................201
3.11.2.2 Structure of the Function..................................................................................... 201
3.11.2.3 Function Description............................................................................................ 201
3.11.2.4 Application and Setting Notes.............................................................................. 202
3.11.2.5 Settings............................................................................................................... 203
3.11.2.6 Information List................................................................................................... 203

4 Applications.............................................................................................................................................. 205
4.1 Overview........................................................................................................................ 206
4.2 Application Templates and Functional Scope for the Devices 7SJ82/7SJ85........................207

5 Function-Group Types.............................................................................................................................. 213


5.1 Function-Group Type Voltage/current 3-Phase................................................................. 214
5.1.1 Overview...................................................................................................................214
5.1.2 Structure of the Function Group................................................................................ 214
5.1.3 Application and Setting Notes....................................................................................218
5.1.4 Write-Protected Settings............................................................................................ 219
5.1.5 Settings.....................................................................................................................219
5.1.6 Information List......................................................................................................... 220
5.2 Function-Group Type Voltage/current 1-Phase................................................................. 221
5.2.1 Overview...................................................................................................................221
5.2.2 Structure of the Function Group................................................................................ 221
5.2.3 Application and Setting Notes....................................................................................224
5.2.4 Write-Protected Settings............................................................................................ 225
5.2.5 Settings.....................................................................................................................225
5.2.6 Information List......................................................................................................... 226
5.3 Function-Group Type Voltage 3-Phase............................................................................. 227
5.3.1 Overview...................................................................................................................227
5.3.2 Structure of the Function Group................................................................................ 227
5.3.3 Application and Setting Notes....................................................................................228
5.3.4 Settings.....................................................................................................................228
5.3.5 Information List......................................................................................................... 229
5.4 Function-Group Type Capacitor Bank............................................................................... 230
5.4.1 Overview...................................................................................................................230
5.4.2 Structure of the Function Group................................................................................ 231
5.4.3 Application and Setting Notes....................................................................................240

SIPROTEC 5, 7SJ82/7SJ85, Manual 13


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

5.4.4 Write-Protected Settings............................................................................................ 241


5.4.5 Settings.....................................................................................................................241
5.4.6 Information List......................................................................................................... 242
5.5 Function-Group Type Capacitor Bank Differential Protection ............................................243
5.5.1 Function-Group Types................................................................................................243
5.5.2 Function-Group Type Capacitor Bank Diff................................................................... 244
5.5.2.1 Overview ............................................................................................................ 244
5.5.2.2 Structure of the Function Group........................................................................... 245
5.5.2.3 Information List................................................................................................... 247
5.5.3 Function-Group Type Capacitor-Bank Side.................................................................. 247
5.5.3.1 Overview ............................................................................................................ 247
5.5.3.2 Structure of the Function Group........................................................................... 248
5.5.3.3 Application and Setting Notes.............................................................................. 253
5.5.3.4 Write-Protected Settings.......................................................................................254
5.5.3.5 Settings............................................................................................................... 255
5.5.3.6 Information List................................................................................................... 255
5.6 Function-Group Type Analog Units.................................................................................. 256
5.6.1 Overview...................................................................................................................256
5.6.2 Structure of the Function Group................................................................................ 256
5.6.3 20-mA Unit Ethernet..................................................................................................258
5.6.3.1 Overview ............................................................................................................ 258
5.6.3.2 Structure of the Function..................................................................................... 258
5.6.3.3 Communication with 20-mA Unit Ethernet .......................................................... 259
5.6.3.4 Application and Setting Notes.............................................................................. 260
5.6.3.5 20-mA Channel.................................................................................................... 260
5.6.3.6 Application and Setting Notes.............................................................................. 263
5.6.3.7 Settings............................................................................................................... 264
5.6.3.8 Information List................................................................................................... 266
5.6.4 20-mA Unit Serial...................................................................................................... 266
5.6.4.1 Overview ............................................................................................................ 266
5.6.4.2 Application and Setting Notes.............................................................................. 267
5.6.4.3 Settings............................................................................................................... 268
5.6.4.4 Information List................................................................................................... 270
5.6.5 Communication with 20-mA Unit...............................................................................270
5.6.5.1 Integration of a Serial 20-mA Unit........................................................................ 270
5.6.5.2 Integration of a 20-mA Unit Ethernet....................................................................273
5.6.6 V/I-Measuring-Transducer Unit with Fast Inputs..........................................................275
5.6.6.1 Overview............................................................................................................. 275
5.6.6.2 Structure of the Function..................................................................................... 276
5.6.6.3 Function Description............................................................................................ 276
5.6.6.4 Application and Setting Notes.............................................................................. 277
5.6.6.5 Settings............................................................................................................... 281
5.6.6.6 Information List................................................................................................... 283
5.6.7 RTD Unit Ethernet...................................................................................................... 283
5.6.7.1 Overview............................................................................................................. 283
5.6.7.2 Structure of the Function..................................................................................... 283
5.6.7.3 Communication with an RTD Unit ........................................................................ 284
5.6.7.4 Application and Setting Notes.............................................................................. 285
5.6.7.5 Temperature Sensor.............................................................................................286
5.6.7.6 Application and Setting Notes ............................................................................. 287
5.6.7.7 Settings............................................................................................................... 288
5.6.7.8 Information List................................................................................................... 288
5.6.8 RTD Unit, Serial..........................................................................................................288
5.6.8.1 Overview ............................................................................................................ 288

14 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

5.6.8.2 Application and Setting Notes ............................................................................. 288


5.6.8.3 Settings............................................................................................................... 289
5.6.8.4 Information List................................................................................................... 290
5.6.9 Communication with RTD Unit................................................................................... 291
5.6.9.1 Integration of a Serial RTD Unit (Ziehl TR1200)..................................................... 291
5.6.9.2 Integration of an RTD Unit Ethernet (TR1200 IP)................................................... 294
5.6.9.3 Temperature Simulation without Sensors ............................................................ 296
5.6.10 Temperature Acquisition via Protocols........................................................................296
5.6.10.1 Overview............................................................................................................. 296
5.6.10.2 Structure of the Function..................................................................................... 296
5.6.10.3 Stage Temperature Acquisition via PROFINET IO or IEC 61850............................... 297
5.6.10.4 Stage Temperature Acquisition via GOOSE............................................................304
5.6.10.5 Application and Setting Notes.............................................................................. 317
5.6.10.6 Settings............................................................................................................... 318
5.6.10.7 Information List................................................................................................... 318
5.7 Function-Group Type Circuit Breaker............................................................................... 319
5.7.1 Overview...................................................................................................................319
5.7.2 Structure of the Function Group................................................................................ 320
5.7.3 Application and Setting Notes....................................................................................321
5.7.4 Settings.....................................................................................................................322
5.7.5 Information List......................................................................................................... 323
5.7.6 Trip Logic.................................................................................................................. 324
5.7.6.1 Function Description............................................................................................ 324
5.7.6.2 Application and Setting Notes.............................................................................. 325
5.7.6.3 Settings............................................................................................................... 325
5.7.6.4 Information List................................................................................................... 326
5.7.7 Circuit Breaker........................................................................................................... 326
5.7.7.1 Overview............................................................................................................. 326
5.7.7.2 Tripping, Opening, and Closing the Circuit Breaker............................................... 326
5.7.7.3 Acquisition of Circuit-Breaker Auxiliary Contacts and Further Information..............328
5.7.7.4 Definitive Tripping, Circuit-Breaker Tripping Alarm Suppression.............................329
5.7.7.5 Tripping and Opening Information....................................................................... 330
5.7.7.6 Application and Setting Notes.............................................................................. 331
5.7.7.7 Settings............................................................................................................... 334
5.7.7.8 Information List................................................................................................... 334
5.7.8 Circuit-Breaker Position Recognition for Protection-Related Auxiliary Functions........... 334
5.7.8.1 Overview............................................................................................................. 334
5.7.9 Detection Manual Closure (for AREC and Process Monitor)......................................... 335
5.7.9.1 Function Description............................................................................................ 335
5.7.9.2 Application and Setting Notes.............................................................................. 336
5.7.9.3 Settings............................................................................................................... 337
5.7.9.4 Information List................................................................................................... 337
5.8 Process Monitor.............................................................................................................. 338
5.8.1 Overview of Functions............................................................................................... 338
5.8.2 Structure of the Function........................................................................................... 338
5.8.3 Current-Flow Criterion............................................................................................... 339
5.8.4 Application and Setting Notes (Current-Flow Criterion) ..............................................340
5.8.5 Circuit-Breaker Condition for the Protected Object......................................................340
5.8.6 Closure Detection...................................................................................................... 341
5.8.7 Information List......................................................................................................... 341
5.8.8 Cold-Load Pickup Detection (Optional) ...................................................................... 342
5.8.9 Application and Setting Notes (Cold-Load Pickup Detection) ...................................... 343

SIPROTEC 5, 7SJ82/7SJ85, Manual 15


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

5.8.10 Settings.....................................................................................................................344
5.8.11 Information List......................................................................................................... 344

6 Protection and Automation Functions..................................................................................................... 345


6.1 Power-System Data......................................................................................................... 347
6.1.1 Overview...................................................................................................................347
6.1.2 Structure of the Power-System Data...........................................................................347
6.1.3 Application and Setting Notes – General Settings....................................................... 347
6.1.4 Application and Setting Notes for Measuring-Point Current 3‑Phase (I 3-ph)............... 348
6.1.5 Application and Setting Notes for Measuring-Point Current 1-Phase (I-1ph)................ 351
6.1.6 Application and Setting Notes for Measuring Point Voltage 3‑Phase (V-3ph)............... 352
6.1.7 Application and Setting Notes for Measuring Point Voltage 1-Phase (V-1ph)............... 357
6.1.8 Settings.....................................................................................................................359
6.1.9 Information List......................................................................................................... 366
6.2 Group Indications of Overcurrent Protection Functions.................................................... 369
6.2.1 Description ............................................................................................................... 369
6.3 Overcurrent Protection, Phases........................................................................................370
6.3.1 Overview of Functions .............................................................................................. 370
6.3.2 Structure of the Function .......................................................................................... 370
6.3.3 Filter for RMS Value Gain........................................................................................... 372
6.3.3.1 Description.......................................................................................................... 372
6.3.3.2 Application and Setting Notes.............................................................................. 373
6.3.3.3 Settings............................................................................................................... 374
6.3.3.4 Information List................................................................................................... 374
6.3.4 Stage with Definite-Time Characteristic Curve............................................................ 375
6.3.4.1 Description ......................................................................................................... 375
6.3.4.2 Application and Setting Notes ............................................................................. 379
6.3.4.3 Settings............................................................................................................... 382
6.3.4.4 Information List................................................................................................... 385
6.3.5 Stage with Inverse-Time Characteristic Curve............................................................. 386
6.3.5.1 Description ......................................................................................................... 386
6.3.5.2 Application and Setting Notes ............................................................................. 390
6.3.5.3 Settings............................................................................................................... 393
6.3.5.4 Information List................................................................................................... 396
6.3.6 Stage with User-Defined Characteristic Curve............................................................. 396
6.3.6.1 Description ......................................................................................................... 396
6.3.6.2 Application and Setting Notes ............................................................................. 397
6.3.6.3 Settings............................................................................................................... 399
6.3.6.4 Information List................................................................................................... 401
6.3.7 Blocking of the Tripping by Device-Internal Inrush-Current Detection..........................402
6.3.7.1 Description ......................................................................................................... 402
6.3.7.2 Application and Setting Notes ............................................................................. 402
6.3.8 Influence of Other Functions via Dynamic Settings..................................................... 403
6.3.8.1 Description ......................................................................................................... 403
6.3.8.2 Application and Setting Notes (Advanced Stage) ..................................................407
6.4 Voltage-Dependent Overcurrent Protection, Phases......................................................... 408
6.4.1 Overview of Functions............................................................................................... 408
6.4.2 Structure of the Function........................................................................................... 408
6.4.3 Stage with Inverse-Time Overcurrent Protection, Voltage-Dependent......................... 409
6.4.3.1 Description.......................................................................................................... 409
6.4.3.2 Application and Setting Notes.............................................................................. 411
6.4.3.3 Settings............................................................................................................... 413

16 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.4.3.4 Information List................................................................................................... 413


6.4.4 Stage with Inverse-Time Overcurrent Protection, Voltage-Released.............................414
6.4.4.1 Description.......................................................................................................... 414
6.4.4.2 Application and Setting Notes.............................................................................. 415
6.4.4.3 Settings............................................................................................................... 416
6.4.4.4 Information List................................................................................................... 416
6.4.5 Stage with Definite-Time Overcurrent Protection, Undervoltage Seal-In...................... 418
6.4.5.1 Description.......................................................................................................... 418
6.4.5.2 Application and Setting Notes.............................................................................. 419
6.4.5.3 Settings............................................................................................................... 420
6.4.5.4 Information List................................................................................................... 421
6.4.6 Stage with Definite-Time Overcurrent Protection, Voltage-Released Under-
voltage Seal-In...........................................................................................................422
6.4.6.1 Description.......................................................................................................... 422
6.4.6.2 Application and Setting Notes.............................................................................. 423
6.4.6.3 Settings............................................................................................................... 425
6.4.6.4 Information List................................................................................................... 426
6.5 Overcurrent Protection, Ground...................................................................................... 427
6.5.1 Overview of Functions............................................................................................... 427
6.5.2 Structure of the Function........................................................................................... 427
6.5.3 General Functionality................................................................................................ 428
6.5.3.1 Description.......................................................................................................... 428
6.5.3.2 Application and Setting Notes ............................................................................. 429
6.5.3.3 Settings............................................................................................................... 430
6.5.4 Stage with Definite-Time Characteristic Curve............................................................ 431
6.5.4.1 Description ......................................................................................................... 431
6.5.4.2 Application and Setting Notes ............................................................................. 433
6.5.4.3 Settings............................................................................................................... 435
6.5.4.4 Information List................................................................................................... 438
6.5.5 Stage with Inverse-Time Characteristic Curve............................................................. 439
6.5.5.1 Description ......................................................................................................... 439
6.5.5.2 Application and Setting Notes ............................................................................. 442
6.5.5.3 Settings............................................................................................................... 443
6.5.5.4 Information List................................................................................................... 446
6.5.6 Stage with User-Defined Characteristic Curve............................................................. 446
6.5.6.1 Description ......................................................................................................... 446
6.5.6.2 Application and Setting Notes ............................................................................. 448
6.5.6.3 Settings............................................................................................................... 449
6.5.6.4 Information List................................................................................................... 451
6.5.7 Blocking of the Tripping by Device-Internal Inrush-Current Detection..........................451
6.5.7.1 Description.......................................................................................................... 451
6.5.7.2 Application and Setting Notes ............................................................................. 452
6.5.8 Influence of Other Functions via Dynamic Settings..................................................... 453
6.5.8.1 Description ......................................................................................................... 453
6.5.8.2 Application and Setting Notes (Advanced Stage) ..................................................456
6.6 Directional Overcurrent Protection, Phases...................................................................... 458
6.6.1 Overview of Functions .............................................................................................. 458
6.6.2 Structure of the Function .......................................................................................... 458
6.6.3 Stage Control............................................................................................................ 460
6.6.3.1 Description ......................................................................................................... 460
6.6.3.2 Application and Setting Notes ............................................................................. 460
6.6.4 Stage with Definite-Time Characteristic Curve............................................................ 461
6.6.4.1 Description ......................................................................................................... 461
6.6.4.2 Application and Setting Notes ............................................................................. 464

SIPROTEC 5, 7SJ82/7SJ85, Manual 17


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.6.4.3 Settings............................................................................................................... 466


6.6.4.4 Information List................................................................................................... 468
6.6.5 Stage with Inverse-Time Characteristic Curve............................................................. 470
6.6.5.1 Description ......................................................................................................... 470
6.6.5.2 Application and Setting Notes ............................................................................. 473
6.6.5.3 Settings............................................................................................................... 476
6.6.5.4 Information List................................................................................................... 478
6.6.6 Stage with User-Defined Characteristic Curve............................................................. 479
6.6.6.1 Description ......................................................................................................... 479
6.6.6.2 Application and Setting Notes ............................................................................. 480
6.6.6.3 Settings............................................................................................................... 481
6.6.6.4 Information List................................................................................................... 484
6.6.7 Direction Determination............................................................................................ 484
6.6.7.1 Description ......................................................................................................... 484
6.6.7.2 Application and Setting Notes ............................................................................. 487
6.6.8 Influence of Other Functions via Dynamic Settings .................................................... 488
6.6.9 Application Notes for Parallel Lines and Cable Runs with Infeed at Both Ends ............. 488
6.6.10 Application Notes for Directional Comparison Protection ........................................... 489
6.7 Directional Overcurrent Protection, Ground..................................................................... 491
6.7.1 Overview of Functions............................................................................................... 491
6.7.2 Structure of the Function........................................................................................... 491
6.7.3 General Functionality................................................................................................ 493
6.7.3.1 Measured-Value Selection.................................................................................... 493
6.7.3.2 Direction Determination....................................................................................... 494
6.7.3.3 Application and Setting Notes.............................................................................. 496
6.7.3.4 Settings............................................................................................................... 498
6.7.3.5 Information List................................................................................................... 499
6.7.4 Stage Control............................................................................................................ 499
6.7.4.1 Description.......................................................................................................... 499
6.7.4.2 Application and Setting Notes.............................................................................. 499
6.7.5 Stage with Definite-Time Characteristic Curve............................................................ 501
6.7.5.1 Description.......................................................................................................... 501
6.7.5.2 Application and Setting Notes.............................................................................. 504
6.7.5.3 Settings............................................................................................................... 507
6.7.5.4 Information List................................................................................................... 509
6.7.6 Stage with Inverse-Time Characteristic Curve............................................................. 510
6.7.6.1 Description.......................................................................................................... 510
6.7.6.2 Application and Setting Notes.............................................................................. 514
6.7.6.3 Settings............................................................................................................... 517
6.7.6.4 Information List................................................................................................... 520
6.7.7 Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse Char-
acteristic Curve..........................................................................................................521
6.7.7.1 Description.......................................................................................................... 521
6.7.7.2 Application and Setting Notes.............................................................................. 523
6.7.7.3 Settings............................................................................................................... 524
6.7.7.4 Information List................................................................................................... 526
6.7.8 Stage with Knee-Point Characteristic Curve................................................................ 527
6.7.8.1 Description.......................................................................................................... 527
6.7.8.2 Application and Setting Notes.............................................................................. 528
6.7.8.3 Settings............................................................................................................... 529
6.7.8.4 Information List................................................................................................... 530
6.7.9 Stage with User-Defined Characteristic Curve............................................................. 531
6.7.9.1 Description.......................................................................................................... 531
6.7.9.2 Application and Setting Notes.............................................................................. 532

18 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.7.9.3 Settings............................................................................................................... 533


6.7.9.4 Information List................................................................................................... 536
6.7.10 Influence of Other Functions via Dynamic Settings..................................................... 536
6.8 Inrush-Current Detection.................................................................................................537
6.8.1 Overview of Functions............................................................................................... 537
6.8.2 Structure of the Function .......................................................................................... 537
6.8.3 Function Description..................................................................................................537
6.8.4 Application and Setting Notes....................................................................................541
6.8.5 Settings.....................................................................................................................542
6.8.6 Information List......................................................................................................... 543
6.9 Instantaneous High-Current Tripping...............................................................................544
6.9.1 Overview of Functions .............................................................................................. 544
6.9.2 Structure of the Function .......................................................................................... 544
6.9.3 Standard Release Procedure....................................................................................... 545
6.9.4 Application and Setting Notes ................................................................................... 546
6.9.5 Release Procedure via Protection Interface................................................................. 547
6.9.6 Application and Setting Notes ................................................................................... 549
6.9.7 Settings.....................................................................................................................549
6.9.8 Information List......................................................................................................... 550
6.10 Arc Protection................................................................................................................. 551
6.10.1 Overview of Function ................................................................................................551
6.10.2 Structure of the Function........................................................................................... 551
6.10.3 Function Description..................................................................................................552
6.10.4 Application and Setting Notes – General Settings....................................................... 554
6.10.5 Application and Setting Notes for the Stage............................................................... 555
6.10.6 Settings.....................................................................................................................556
6.10.7 Information List......................................................................................................... 557
6.10.8 Application Example for Arc Protection with Point Sensors in Operating Mode:
Light Only................................................................................................................. 559
6.10.8.1 Description.......................................................................................................... 559
6.10.8.2 Application and Setting Notes.............................................................................. 560
6.10.9 Application Example for Arc Protection with Point Sensors in Operating Mode:
Light and Current...................................................................................................... 561
6.10.9.1 Description.......................................................................................................... 561
6.10.9.2 Application and Setting Notes.............................................................................. 563
6.10.10 Application Example for Arc Protection with Point Sensors via External Trip Initiation..563
6.10.10.1 Description.......................................................................................................... 563
6.10.10.2 Application and Setting Notes.............................................................................. 565
6.10.11 Application Example for Arc Protection with a Line Sensor in Operating Mode:
Light and Current...................................................................................................... 567
6.10.11.1 Description.......................................................................................................... 567
6.10.11.2 Application and Setting Notes.............................................................................. 569
6.11 Instantaneous Tripping at Switch onto Fault.................................................................... 570
6.11.1 Overview of Functions .............................................................................................. 570
6.11.2 Structure of the Function........................................................................................... 570
6.11.3 Stage Description...................................................................................................... 571
6.11.4 Application and Setting Notes....................................................................................571
6.11.5 Settings.....................................................................................................................572
6.11.6 Information List......................................................................................................... 572

SIPROTEC 5, 7SJ82/7SJ85, Manual 19


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.12 Overcurrent Protection, 1-Phase...................................................................................... 573


6.12.1 Function Overview ....................................................................................................573
6.12.2 Structure of the Function .......................................................................................... 573
6.12.3 Stage with Definite-Time Characteristic Curve............................................................ 575
6.12.3.1 Description ......................................................................................................... 575
6.12.3.2 Application and Setting Notes ............................................................................. 576
6.12.3.3 Settings............................................................................................................... 577
6.12.3.4 Information List................................................................................................... 577
6.12.4 Stage with Inverse-Time Characteristic Curve............................................................. 578
6.12.4.1 Description ......................................................................................................... 578
6.12.4.2 Application and Setting Notes ............................................................................. 579
6.12.4.3 Settings............................................................................................................... 580
6.12.4.4 Information List................................................................................................... 581
6.12.5 Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse Char-
acteristic Curve..........................................................................................................582
6.12.5.1 Description.......................................................................................................... 582
6.12.5.2 Application and Setting Notes.............................................................................. 584
6.12.5.3 Settings............................................................................................................... 585
6.12.5.4 Information List................................................................................................... 585
6.12.6 Stage with User-Defined Characteristic Curve............................................................. 586
6.12.6.1 Description ......................................................................................................... 586
6.12.6.2 Application and Setting Notes ............................................................................. 587
6.12.6.3 Settings............................................................................................................... 588
6.12.6.4 Information List................................................................................................... 588
6.12.7 Fast Stage................................................................................................................. 589
6.12.7.1 Description ......................................................................................................... 589
6.12.7.2 Application and Setting Notes ............................................................................. 589
6.12.7.3 Settings............................................................................................................... 590
6.12.7.4 Information List................................................................................................... 590
6.12.8 Application Example: High-Impedance Restricted Ground-Fault Protection..................590
6.12.8.1 Description ......................................................................................................... 590
6.12.8.2 Application and Setting Notes ............................................................................. 592
6.12.9 Application Example: Tank Leakage Protection........................................................... 596
6.12.9.1 Description ......................................................................................................... 596
6.12.9.2 Application and Setting Notes ............................................................................. 597
6.13 Positive-Sequence Overcurrent Protection....................................................................... 598
6.13.1 Overview of Functions .............................................................................................. 598
6.13.2 Structure of the Function .......................................................................................... 598
6.13.3 Stage with Definite-Time Characteristic Curve............................................................ 599
6.13.3.1 Description.......................................................................................................... 599
6.13.3.2 Application and Setting Notes.............................................................................. 600
6.13.3.3 Settings............................................................................................................... 602
6.13.3.4 Information List................................................................................................... 602
6.13.4 Stage with Inverse-Time Characteristic Curve............................................................. 604
6.13.4.1 Description.......................................................................................................... 604
6.13.4.2 Application and Setting Notes ............................................................................. 605
6.13.4.3 Settings............................................................................................................... 606
6.13.4.4 Information List................................................................................................... 606
6.14 Non-Directional Intermittent Ground-Fault Protection......................................................608
6.14.1 Overview of Functions............................................................................................... 608
6.14.2 Structure of the Function........................................................................................... 608
6.14.3 Stage Description...................................................................................................... 609
6.14.4 Application and Setting Notes....................................................................................613

20 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.14.5 Settings.....................................................................................................................615
6.14.6 Information List......................................................................................................... 615
6.15 Directional Intermittent Ground-Fault Protection............................................................. 616
6.15.1 Overview of Functions............................................................................................... 616
6.15.2 Structure of the Function........................................................................................... 616
6.15.3 Stage Description...................................................................................................... 617
6.15.4 Application and Setting Notes....................................................................................623
6.15.5 Settings.....................................................................................................................625
6.15.6 Information List......................................................................................................... 626
6.16 Sensitive Ground-Fault Detection.................................................................................... 627
6.16.1 Overview of Functions............................................................................................... 627
6.16.2 Structure of the Function........................................................................................... 627
6.16.3 General Functionality................................................................................................ 629
6.16.3.1 Description.......................................................................................................... 629
6.16.3.2 Application and Setting Notes.............................................................................. 632
6.16.3.3 Settings............................................................................................................... 633
6.16.3.4 Information List................................................................................................... 634
6.16.4 Directional 3I0 Stage with Cos φ or Sin φ Measurement............................................. 635
6.16.4.1 Description.......................................................................................................... 635
6.16.4.2 Application and Setting Notes.............................................................................. 641
6.16.4.3 Settings............................................................................................................... 643
6.16.4.4 Information List................................................................................................... 644
6.16.5 Directional Transient Ground-Fault Stage................................................................... 644
6.16.5.1 Description ......................................................................................................... 644
6.16.5.2 Application and Setting Notes.............................................................................. 649
6.16.5.3 Settings............................................................................................................... 652
6.16.5.4 Information List................................................................................................... 652
6.16.6 Directional 3I0 Stage with φ(V0,3I0) Measurement.................................................... 653
6.16.6.1 Description ......................................................................................................... 653
6.16.6.2 Application and Setting Notes.............................................................................. 657
6.16.6.3 Settings............................................................................................................... 658
6.16.6.4 Information List................................................................................................... 659
6.16.7 Directional Y0 Stage with G0 or B0 Measurement.......................................................660
6.16.7.1 Description.......................................................................................................... 660
6.16.7.2 Application and Setting Notes.............................................................................. 665
6.16.7.3 Settings............................................................................................................... 669
6.16.7.4 Information List................................................................................................... 670
6.16.8 Directional Stage with Phasor Measurement of a Harmonic........................................ 670
6.16.8.1 Description.......................................................................................................... 670
6.16.8.2 Application and Setting Notes.............................................................................. 675
6.16.8.3 Settings............................................................................................................... 677
6.16.8.4 Information List................................................................................................... 677
6.16.9 Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage..................... 679
6.16.9.1 Description ......................................................................................................... 679
6.16.9.2 Application and Setting Notes.............................................................................. 680
6.16.9.3 Settings............................................................................................................... 683
6.16.9.4 Information List................................................................................................... 683
6.16.10 Non-Directional 3I0 Stage.......................................................................................... 683
6.16.10.1 Description ......................................................................................................... 683
6.16.10.2 Application and Setting Notes ............................................................................. 685
6.16.10.3 Settings............................................................................................................... 686
6.16.10.4 Information List................................................................................................... 686

SIPROTEC 5, 7SJ82/7SJ85, Manual 21


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.16.11 Non-Directional Y0 Stage........................................................................................... 687


6.16.11.1 Description.......................................................................................................... 687
6.16.11.2 Application and Setting Notes.............................................................................. 689
6.16.11.3 Settings............................................................................................................... 690
6.16.11.4 Information List................................................................................................... 690
6.16.12 Non-Directional 3I0 Harmonic Stage.......................................................................... 691
6.16.12.1 Description.......................................................................................................... 691
6.16.12.2 Application and Setting Notes.............................................................................. 692
6.16.12.3 Settings............................................................................................................... 693
6.16.12.4 Information List................................................................................................... 694
6.16.13 Pulse-Pattern Detection Stage.................................................................................... 694
6.16.13.1 Description.......................................................................................................... 694
6.16.13.2 Application and Setting Notes.............................................................................. 699
6.16.13.3 Settings............................................................................................................... 702
6.16.13.4 Information List................................................................................................... 702
6.17 Undercurrent Protection..................................................................................................703
6.17.1 Overview of Functions............................................................................................... 703
6.17.2 Structure of the Function .......................................................................................... 703
6.17.3 Stage Description...................................................................................................... 704
6.17.4 Application and Setting Notes ................................................................................... 705
6.17.5 Settings.....................................................................................................................706
6.17.6 Information List......................................................................................................... 707
6.18 Negative-Sequence Protection.........................................................................................708
6.18.1 Overview of Functions .............................................................................................. 708
6.18.2 Structure of the Function .......................................................................................... 708
6.18.3 General Functionality................................................................................................ 709
6.18.3.1 Description.......................................................................................................... 709
6.18.3.2 Application and Setting Notes.............................................................................. 709
6.18.4 Stage with Definite-Time Characteristic Curve............................................................ 711
6.18.4.1 Stage Description ................................................................................................ 711
6.18.4.2 Application and Setting Notes ............................................................................. 712
6.18.4.3 Settings............................................................................................................... 712
6.18.4.4 Information List................................................................................................... 713
6.18.5 Stage with Inverse-Time Characteristic Curve............................................................. 714
6.18.5.1 Description.......................................................................................................... 714
6.18.5.2 Application and Settings Notes............................................................................. 715
6.18.5.3 Settings............................................................................................................... 716
6.18.5.4 Information List................................................................................................... 716
6.19 Directional Negative-Sequence Protection....................................................................... 717
6.19.1 Overview of Functions............................................................................................... 717
6.19.2 Structure of the Function .......................................................................................... 717
6.19.3 Function Description..................................................................................................717
6.19.4 Application and Setting Notes for Direction Determination ........................................ 722
6.19.5 Application and Setting Notes for Stages ................................................................... 722
6.19.6 Settings.....................................................................................................................724
6.19.7 Information List......................................................................................................... 725
6.20 Thermal Overload Protection, 3-Phase - Advanced........................................................... 727
6.20.1 Overview of Functions............................................................................................... 727
6.20.2 Structure of the Function........................................................................................... 727
6.20.3 Filter for RMS Value Gain........................................................................................... 727
6.20.3.1 Description.......................................................................................................... 727

22 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.20.3.2 Application and Setting Notes.............................................................................. 728


6.20.3.3 Settings............................................................................................................... 729
6.20.3.4 Information List................................................................................................... 730
6.20.4 Stage with Thermal Overload Protection, 3-Phase - Advanced.....................................730
6.20.4.1 Description ......................................................................................................... 730
6.20.4.2 Application and Setting Notes.............................................................................. 735
6.20.4.3 Settings............................................................................................................... 739
6.20.4.4 Information List................................................................................................... 740
6.21 Thermal Overload Protection, User-Defined Characteristic Curve...................................... 741
6.21.1 Overview of Functions............................................................................................... 741
6.21.2 Structure of the Function........................................................................................... 741
6.21.3 Function Description..................................................................................................742
6.21.4 Application and Setting Notes....................................................................................746
6.21.5 Settings.....................................................................................................................749
6.21.6 Information List......................................................................................................... 750
6.22 Thermal Overload Protection, 1-Phase............................................................................. 752
6.22.1 Overview of Functions............................................................................................... 752
6.22.2 Structure of the Function........................................................................................... 752
6.22.3 Function Description..................................................................................................753
6.22.4 Application and Setting Notes....................................................................................757
6.22.5 Settings.....................................................................................................................760
6.22.6 Information List......................................................................................................... 761
6.23 Unbalanced-Load Protection............................................................................................762
6.23.1 Overview of Functions............................................................................................... 762
6.23.2 Structure of the Function........................................................................................... 762
6.23.3 Function Description..................................................................................................763
6.23.4 Application and Setting Notes....................................................................................765
6.23.5 Settings.....................................................................................................................767
6.23.6 Information List......................................................................................................... 767
6.24 Overvoltage Protection with 3-Phase Voltage...................................................................768
6.24.1 Overview of Functions .............................................................................................. 768
6.24.2 Structure of the Function........................................................................................... 768
6.24.3 Stage with Definite-Time Characteristic Curve............................................................ 769
6.24.3.1 Description ......................................................................................................... 769
6.24.3.2 Application and Setting Notes ............................................................................. 770
6.24.3.3 Settings............................................................................................................... 772
6.24.3.4 Information List................................................................................................... 773
6.24.4 Stage with Inverse-Time Characteristic Curve............................................................. 774
6.24.4.1 Description ......................................................................................................... 774
6.24.4.2 Application and Setting Notes ............................................................................. 777
6.24.4.3 Settings............................................................................................................... 779
6.24.4.4 Information List................................................................................................... 779
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage..............................780
6.25.1 Overview of Functions .............................................................................................. 780
6.25.2 Structure of the Function .......................................................................................... 780
6.25.3 Stage Description ......................................................................................................781
6.25.4 Application and Setting Notes....................................................................................782
6.25.5 Settings.....................................................................................................................785
6.25.6 Information List......................................................................................................... 785

SIPROTEC 5, 7SJ82/7SJ85, Manual 23


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.26 Overvoltage Protection with Positive-Sequence Voltage................................................... 787


6.26.1 Overview of Functions............................................................................................... 787
6.26.2 Structure of the Function........................................................................................... 787
6.26.3 Stage Description ......................................................................................................788
6.26.4 Application and Setting Notes....................................................................................788
6.26.5 Settings.....................................................................................................................789
6.26.6 Information List......................................................................................................... 789
6.27 Overvoltage Protection with Negative-Sequence Voltage................................................. 791
6.27.1 Overview of Functions .............................................................................................. 791
6.27.2 Structure of the Function .......................................................................................... 791
6.27.3 General Functionality................................................................................................ 791
6.27.3.1 Description.......................................................................................................... 791
6.27.3.2 Application and Setting Notes.............................................................................. 792
6.27.3.3 Settings............................................................................................................... 793
6.27.3.4 Information List................................................................................................... 793
6.27.4 Stage with Negative-Sequence Voltage...................................................................... 794
6.27.4.1 Description.......................................................................................................... 794
6.27.4.2 Application and Setting Notes.............................................................................. 794
6.27.4.3 Settings............................................................................................................... 796
6.27.4.4 Information List................................................................................................... 797
6.28 Overvoltage Protection with Any Voltage.........................................................................798
6.28.1 Overview of Functions............................................................................................... 798
6.28.2 Structure of the Function........................................................................................... 798
6.28.3 Stage Description...................................................................................................... 799
6.28.4 Application and Setting Notes....................................................................................800
6.28.5 Settings.....................................................................................................................802
6.28.6 Information List......................................................................................................... 803
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage ....... 804
6.29.1 Overview of Functions............................................................................................... 804
6.29.2 Structure of the Function .......................................................................................... 804
6.29.3 General Functionality................................................................................................ 804
6.29.3.1 Description.......................................................................................................... 804
6.29.3.2 Application and Setting Notes.............................................................................. 805
6.29.3.3 Settings............................................................................................................... 806
6.29.3.4 Information List................................................................................................... 806
6.29.4 Stage with Negative-Sequence Voltage/Positive-Sequence Voltage ............................ 807
6.29.4.1 Description.......................................................................................................... 807
6.29.4.2 Application and Setting Notes.............................................................................. 807
6.29.4.3 Settings............................................................................................................... 809
6.29.4.4 Information List................................................................................................... 810
6.30 Undervoltage Protection with 3-Phase Voltage................................................................ 811
6.30.1 Overview of Functions............................................................................................... 811
6.30.2 Structure of the Function .......................................................................................... 811
6.30.3 Stage with Definite-Time Characteristic Curve............................................................ 812
6.30.3.1 Description.......................................................................................................... 812
6.30.3.2 Application and Setting Notes.............................................................................. 814
6.30.3.3 Settings............................................................................................................... 817
6.30.3.4 Information List................................................................................................... 819
6.30.4 Stage with Inverse-Time Characteristic Curve............................................................. 820
6.30.4.1 Description.......................................................................................................... 820
6.30.4.2 Application and Setting Notes.............................................................................. 824

24 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.30.4.3 Settings............................................................................................................... 827


6.30.4.4 Information List................................................................................................... 827
6.31 Undervoltage Protection with Positive-Sequence Voltage.................................................829
6.31.1 Overview of Functions .............................................................................................. 829
6.31.2 Structure of the Function .......................................................................................... 829
6.31.3 Stage Description ......................................................................................................830
6.31.4 Application and Setting Notes ................................................................................... 831
6.31.5 Settings.....................................................................................................................834
6.31.6 Information List......................................................................................................... 835
6.32 Undervoltage Protection with Any Voltage.......................................................................836
6.32.1 Overview of Functions............................................................................................... 836
6.32.2 Structure of the Function........................................................................................... 836
6.32.3 Stage Description...................................................................................................... 837
6.32.4 Application and Setting Notes....................................................................................838
6.32.5 Settings.....................................................................................................................840
6.32.6 Information List......................................................................................................... 841
6.33 Overfrequency Protection................................................................................................842
6.33.1 Overview of Functions............................................................................................... 842
6.33.2 Structure of the Function........................................................................................... 842
6.33.3 Overfrequency-Protection Stage................................................................................ 843
6.33.4 Application and Setting Notes....................................................................................844
6.33.5 Settings.....................................................................................................................845
6.33.6 Information List......................................................................................................... 846
6.34 Underfrequency Protection............................................................................................. 847
6.34.1 Overview of Functions............................................................................................... 847
6.34.2 Structure of the Function........................................................................................... 847
6.34.3 Underfrequency-Protection Stage.............................................................................. 848
6.34.4 Application and Setting Notes....................................................................................849
6.34.5 Settings.....................................................................................................................850
6.34.6 Information List......................................................................................................... 851
6.35 Underfrequency Load Shedding...................................................................................... 853
6.35.1 Overview of Functions............................................................................................... 853
6.35.2 Structure of the Function........................................................................................... 853
6.35.3 General Functionality................................................................................................ 854
6.35.3.1 Description.......................................................................................................... 854
6.35.3.2 Application and Setting Notes.............................................................................. 857
6.35.4 Stage Description...................................................................................................... 860
6.35.4.1 Description.......................................................................................................... 860
6.35.4.2 Application and Setting Notes.............................................................................. 862
6.35.5 Settings.....................................................................................................................863
6.35.6 Information List......................................................................................................... 863
6.36 Rate of Frequency Change Protection.............................................................................. 865
6.36.1 Overview of Functions .............................................................................................. 865
6.36.2 Structure of the Function........................................................................................... 865
6.36.3 General Functions (Undervoltage Test, df/dt Calculation)........................................... 865
6.36.3.1 Description.......................................................................................................... 865
6.36.3.2 Application and Setting Notes.............................................................................. 866

SIPROTEC 5, 7SJ82/7SJ85, Manual 25


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.36.4 Stage Description...................................................................................................... 867


6.36.4.1 Description.......................................................................................................... 867
6.36.4.2 Application and Setting Notes.............................................................................. 868
6.36.5 Settings.....................................................................................................................869
6.36.6 Information List......................................................................................................... 869
6.37 Vector-Jump Protection................................................................................................... 871
6.37.1 Overview of Functions............................................................................................... 871
6.37.2 Structure of the Function........................................................................................... 871
6.37.3 General Functionality................................................................................................ 871
6.37.3.1 Description.......................................................................................................... 871
6.37.3.2 Application and Setting Notes.............................................................................. 874
6.37.3.3 Settings............................................................................................................... 874
6.37.3.4 Information List................................................................................................... 874
6.37.4 Δφ Stage................................................................................................................... 875
6.37.4.1 Description.......................................................................................................... 875
6.37.4.2 Application and Setting Notes.............................................................................. 876
6.37.4.3 Settings............................................................................................................... 877
6.37.4.4 Information List................................................................................................... 877
6.37.5 I1 < Release Stage .....................................................................................................877
6.37.5.1 Description.......................................................................................................... 877
6.37.5.2 Application and Setting Notes.............................................................................. 878
6.37.5.3 Settings............................................................................................................... 878
6.37.5.4 Information List................................................................................................... 878
6.38 Power Protection (P,Q), 3-Phase...................................................................................... 879
6.38.1 Overview of Functions .............................................................................................. 879
6.38.2 Structure of the Function .......................................................................................... 879
6.38.3 Active Power Stage ................................................................................................... 880
6.38.4 Reactive Power Stage ................................................................................................882
6.38.5 Application Example.................................................................................................. 883
6.38.6 Setting Notes for the Active Power Stage................................................................... 884
6.38.7 Setting Notes for the Reactive Power Stage................................................................ 885
6.38.8 Settings.....................................................................................................................886
6.38.9 Information List......................................................................................................... 887
6.39 Reverse-Power Protection................................................................................................889
6.39.1 Overview of Functions............................................................................................... 889
6.39.2 Structure of the Function........................................................................................... 889
6.39.3 General Functionality................................................................................................ 890
6.39.3.1 Description ......................................................................................................... 890
6.39.3.2 Application and Setting Notes.............................................................................. 891
6.39.3.3 Settings............................................................................................................... 893
6.39.3.4 Information List................................................................................................... 893
6.39.4 Stage Description...................................................................................................... 894
6.39.4.1 Description ......................................................................................................... 894
6.39.4.2 Application and Setting Notes.............................................................................. 895
6.39.4.3 Settings............................................................................................................... 895
6.39.4.4 Information List................................................................................................... 896
6.40 Overexcitation Protection................................................................................................897
6.40.1 Overview of Functions .............................................................................................. 897
6.40.2 Structure of the Function .......................................................................................... 897
6.40.3 Stage with Dependent Characteristic Curve (Thermal Stage).......................................898
6.40.3.1 Function Description............................................................................................ 898

26 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.40.3.2 Application and Setting Notes.............................................................................. 901


6.40.3.3 Settings............................................................................................................... 902
6.40.3.4 Information List................................................................................................... 902
6.40.4 Stage with Independent Characteristic Curve............................................................. 904
6.40.4.1 Function Description............................................................................................ 904
6.40.4.2 Application and Setting Notes ............................................................................. 904
6.40.4.3 Settings............................................................................................................... 905
6.40.4.4 Information List................................................................................................... 905
6.41 Undervoltage-Controlled Reactive-Power Protection........................................................ 907
6.41.1 Overview of Functions............................................................................................... 907
6.41.2 Structure of the Function........................................................................................... 907
6.41.3 Protection Stage........................................................................................................ 908
6.41.3.1 Description.......................................................................................................... 908
6.41.3.2 Application and Setting Notes.............................................................................. 909
6.41.3.3 Settings............................................................................................................... 911
6.41.3.4 Information List................................................................................................... 912
6.41.4 Reclosure Stage......................................................................................................... 913
6.41.4.1 Description.......................................................................................................... 913
6.41.4.2 Application and Setting Notes.............................................................................. 914
6.41.4.3 Settings............................................................................................................... 915
6.41.4.4 Information List................................................................................................... 915
6.42 Circuit-Breaker Failure Protection.....................................................................................916
6.42.1 Overview of Functions............................................................................................... 916
6.42.2 Structure of the Function........................................................................................... 916
6.42.3 Function Description..................................................................................................917
6.42.4 Application and Setting Notes....................................................................................924
6.42.5 Settings.....................................................................................................................931
6.42.6 Information List......................................................................................................... 933
6.43 Circuit-Breaker Restrike Protection................................................................................... 934
6.43.1 Overview of Function................................................................................................ 934
6.43.2 Structure of the Function........................................................................................... 934
6.43.3 Function Description..................................................................................................934
6.43.4 Application and Setting Notes....................................................................................938
6.43.5 Settings.....................................................................................................................941
6.43.6 Information List......................................................................................................... 942
6.44 Restricted Ground-Fault Protection.................................................................................. 943
6.44.1 Overview of Functions .............................................................................................. 943
6.44.2 Structure of the Function .......................................................................................... 943
6.44.3 Function Description..................................................................................................944
6.44.4 Application and Setting Notes....................................................................................949
6.44.5 Settings.....................................................................................................................959
6.44.6 Information List......................................................................................................... 960
6.45 External Trip Initiation 3-Pole.......................................................................................... 961
6.45.1 Overview of Functions............................................................................................... 961
6.45.2 Structure of the Function........................................................................................... 961
6.45.3 Stage Description ......................................................................................................962
6.45.4 Application and Setting Notes....................................................................................962
6.45.5 Settings.....................................................................................................................963
6.45.6 Information List......................................................................................................... 963

SIPROTEC 5, 7SJ82/7SJ85, Manual 27


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.46 Automatic Reclosing Function......................................................................................... 964


6.46.1 Overview of Functions............................................................................................... 964
6.46.2 Structure of the Function........................................................................................... 964
6.46.3 Cooperation of the Automatic Reclosing Function and Protection Functions .............. 966
6.46.4 Cyclic Automatic Reclosing Function.......................................................................... 968
6.46.4.1 Operating Modes for Cyclic Automatic Reclosing Function.................................... 968
6.46.4.2 Structure of the Cyclic Automatic Reclosing Function............................................ 971
6.46.4.3 Input Logic for Operating Modes with Tripping .................................................... 972
6.46.4.4 Input Logic for Operating Modes with Pickup........................................................973
6.46.4.5 Start.................................................................................................................... 974
6.46.4.6 Cycle Control with Operating Mode 1: With Tripping/With Action Time..................975
6.46.4.7 Cycle Control with Operating Mode 2: With Pickup/With Action Time.................... 977
6.46.4.8 Cycle Control with Operating Mode 3: With Tripping/Without Action Time.............979
6.46.4.9 Cycle Control with Operating Mode 4: With Pickup/Without Action Time............... 980
6.46.4.10 Stage Release.......................................................................................................981
6.46.4.11 Dead Time for Operating Modes With Tripping......................................................982
6.46.4.12 Dead Time for Operating Modes with Pickup ........................................................983
6.46.4.13 Evolving-Fault Detection During Dead Time.......................................................... 984
6.46.4.14 Closing Indication and Close Command................................................................ 986
6.46.4.15 Reclaim Time....................................................................................................... 989
6.46.4.16 Circuit-Breaker Readiness .................................................................................... 990
6.46.4.17 Blockings............................................................................................................. 991
6.46.4.18 Dead-Line Checking (DLC) and Reduced Dead Time (RDT)..................................... 994
6.46.4.19 Settings............................................................................................................... 996
6.46.4.20 Information List................................................................................................... 998
6.46.5 Automatic Reclosing Function with Adaptive Dead Time (ADT)................................. 1000
6.46.5.1 Description........................................................................................................ 1000
6.46.5.2 Settings ............................................................................................................ 1001
6.46.5.3 Information List................................................................................................. 1002
6.46.6 Cooperation with External Automatic Reclosing Function......................................... 1003
6.46.6.1 Description ....................................................................................................... 1003
6.46.6.2 Information List................................................................................................. 1004
6.46.7 Application and Setting Notes for General Settings...................................................1005
6.46.8 Application and Setting Notes for 1 Cycle of the Cyclic Automatic Reclosing Function 1011
6.47 Fault Locator.................................................................................................................1014
6.47.1 Overview of Functions............................................................................................. 1014
6.47.2 Structure of the Function.........................................................................................1014
6.47.3 Function Description................................................................................................1015
6.47.4 Application and Setting Notes..................................................................................1021
6.47.5 Settings...................................................................................................................1025
6.47.6 Information List....................................................................................................... 1026
6.48 Fault Locator Plus..........................................................................................................1027
6.48.1 Overview of Functions............................................................................................. 1027
6.48.2 Structure of the Function.........................................................................................1027
6.48.3 Function Description................................................................................................1029
6.48.4 Application and Setting Notes..................................................................................1032
6.48.5 Settings...................................................................................................................1037
6.48.6 Information List....................................................................................................... 1038
6.49 Temperature Supervision.............................................................................................. 1040
6.49.1 Overview of Functions ............................................................................................ 1040
6.49.2 Structure of the Function ........................................................................................ 1040

28 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

6.49.3 Function Description ...............................................................................................1041


6.49.4 Application and Setting Notes ................................................................................. 1041
6.49.5 Settings...................................................................................................................1042
6.49.6 Information List....................................................................................................... 1047
6.50 Phase-Sequence Switchover.......................................................................................... 1050
6.50.1 Overview of Functions............................................................................................. 1050
6.50.2 Structure of the Function ........................................................................................ 1050
6.50.3 Function Description................................................................................................1050
6.50.4 Application and Setting Notes..................................................................................1053
6.50.5 Settings...................................................................................................................1054
6.50.6 Information List....................................................................................................... 1055
6.51 Current-Jump Detection................................................................................................ 1056
6.51.1 Overview of Functions............................................................................................. 1056
6.51.2 Structure of the Function ........................................................................................ 1056
6.51.3 Function Description................................................................................................1056
6.51.4 Application and Setting Notes ................................................................................. 1057
6.51.5 Settings...................................................................................................................1058
6.51.6 Information List....................................................................................................... 1058
6.52 Voltage-Jump Detection................................................................................................ 1059
6.52.1 Overview of Functions............................................................................................. 1059
6.52.2 Structure of the Function ........................................................................................ 1059
6.52.3 Function Description................................................................................................1059
6.52.4 Application and Setting Notes ................................................................................. 1060
6.52.5 Settings...................................................................................................................1061
6.52.6 Information List....................................................................................................... 1061
6.53 Voltage Measuring-Point Selection................................................................................ 1062
6.53.1 Overview of Functions............................................................................................. 1062
6.53.2 Function Description................................................................................................1062
6.53.3 Application and Setting Notes..................................................................................1063
6.53.4 Information List....................................................................................................... 1064

7 Capacitor Bank Protection...................................................................................................................... 1065


7.1 Introduction..................................................................................................................1066
7.2 Overcurrent Protection for Capacitor Banks....................................................................1067
7.2.1 Overview ................................................................................................................1067
7.2.2 Overcurrent Protection, Phases for Protection of RLC Filter-Circuit Elements..............1067
7.2.2.1 Structure of the Function .................................................................................. 1067
7.2.2.2 Function Description ......................................................................................... 1068
7.2.2.3 Application and Setting Notes ........................................................................... 1069
7.2.2.4 Settings............................................................................................................. 1070
7.2.2.5 Information List................................................................................................. 1070
7.3 Thermal Overload Protection for Capacitor Banks...........................................................1071
7.3.1 Overview of Functions ............................................................................................ 1071
7.3.2 Structure of the Function ........................................................................................ 1071
7.3.3 Function Description ...............................................................................................1071
7.3.4 Application and Setting Notes ................................................................................. 1072
7.3.5 Settings...................................................................................................................1073
7.3.6 Information List....................................................................................................... 1074

SIPROTEC 5, 7SJ82/7SJ85, Manual 29


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

7.4 Current-Unbalance Protection for Capacitors, 3-Phase....................................................1075


7.4.1 Overview of Functions............................................................................................. 1075
7.4.2 Structure of the Function.........................................................................................1075
7.4.3 General Functions and Measuring-Point Selection.................................................... 1075
7.4.3.1 Description........................................................................................................ 1075
7.4.3.2 Application and Setting Notes............................................................................ 1082
7.4.3.3 Settings............................................................................................................. 1090
7.4.3.4 Information List................................................................................................. 1091
7.4.4 Overcurrent-Protection Stage I>............................................................................... 1092
7.4.4.1 Description........................................................................................................ 1092
7.4.4.2 Application and Setting Notes............................................................................ 1094
7.4.4.3 Settings............................................................................................................. 1095
7.4.4.4 Information List................................................................................................. 1095
7.4.5 Counter Stage......................................................................................................... 1097
7.4.5.1 Description........................................................................................................ 1097
7.4.5.2 Application and Setting Notes............................................................................ 1098
7.4.5.3 Settings............................................................................................................. 1099
7.4.5.4 Information List................................................................................................. 1099
7.5 Current-Unbalance Protection for Capacitors, 1-Phase....................................................1100
7.5.1 Overview of Functions............................................................................................. 1100
7.5.2 Structure of the Function.........................................................................................1100
7.5.3 General Functions and Measuring-Point Selection.................................................... 1100
7.5.3.1 Description........................................................................................................ 1100
7.5.3.2 Application and Setting Notes............................................................................ 1107
7.5.3.3 Settings............................................................................................................. 1110
7.5.3.4 Information List................................................................................................. 1110
7.5.4 Overcurrent-Protection Stage I>............................................................................... 1111
7.5.4.1 Description........................................................................................................ 1111
7.5.4.2 Application and Setting Notes............................................................................ 1113
7.5.4.3 Settings............................................................................................................. 1113
7.5.4.4 Information List................................................................................................. 1114
7.5.5 Counter Stage......................................................................................................... 1115
7.5.5.1 Description........................................................................................................ 1115
7.5.5.2 Application and Setting Notes............................................................................ 1116
7.5.5.3 Settings............................................................................................................. 1117
7.5.5.4 Information List................................................................................................. 1117
7.6 Peak Overvoltage Protection for Capacitors....................................................................1119
7.6.1 Overview of Functions............................................................................................. 1119
7.6.2 Structure of the Function.........................................................................................1119
7.6.3 Stage with Inverse-Time Characteristic Curve........................................................... 1120
7.6.3.1 Description........................................................................................................ 1120
7.6.3.2 Application and Setting Notes............................................................................ 1122
7.6.3.3 Settings............................................................................................................. 1124
7.6.3.4 Information List................................................................................................. 1124
7.6.4 Stage with Definite-Time Characteristic Curve.......................................................... 1126
7.6.4.1 Description........................................................................................................ 1126
7.6.4.2 Application and Setting Notes............................................................................ 1127
7.6.4.3 Settings............................................................................................................. 1127
7.6.4.4 Information List................................................................................................. 1128
7.6.5 Stage with User-Defined Characteristic Curve........................................................... 1128
7.6.5.1 Description........................................................................................................ 1128
7.6.5.2 Application and Setting Notes............................................................................ 1129
7.6.5.3 Settings............................................................................................................. 1130
7.6.5.4 Information List................................................................................................. 1130

30 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

7.7 Voltage Differential Protection for Capacitors.................................................................1131


7.7.1 Overview of Functions............................................................................................. 1131
7.7.2 Structure of the Function.........................................................................................1131
7.7.3 General Functionality.............................................................................................. 1131
7.7.3.1 Description........................................................................................................ 1131
7.7.3.2 Application and Setting Notes............................................................................ 1137
7.7.4 Protection Stage...................................................................................................... 1139
7.7.4.1 Description........................................................................................................ 1139
7.7.4.2 Application and Setting Notes............................................................................ 1140
7.7.4.3 Settings............................................................................................................. 1141
7.7.4.4 Information List................................................................................................. 1142
7.8 Differential Protection for Capacitor Banks.....................................................................1143
7.8.1 Overview of Functions............................................................................................. 1143
7.8.2 Structure of the Function.........................................................................................1143
7.8.3 Function Description................................................................................................1143
7.8.4 Application and Setting Notes..................................................................................1162
7.8.5 Settings...................................................................................................................1168
7.8.6 Information List....................................................................................................... 1169
7.9 Detuning Supervision for Capacitor Banks......................................................................1171
7.9.1 AC-Filter Detuning Supervision................................................................................ 1171

8 Control Functions................................................................................................................................... 1173


8.1 Introduction..................................................................................................................1174
8.1.1 Overview.................................................................................................................1174
8.1.2 Concept of Controllables..........................................................................................1174
8.2 Switching Devices......................................................................................................... 1177
8.2.1 General Overview.................................................................................................... 1177
8.2.2 Switching Device Circuit Breaker.............................................................................. 1177
8.2.2.1 Structure of the Circuit-Breaker Switching Device................................................1177
8.2.2.2 Application and Setting Notes............................................................................ 1180
8.2.2.3 Connection Variants of the Circuit Breaker.......................................................... 1183
8.2.2.4 Settings............................................................................................................. 1191
8.2.2.5 Information List................................................................................................. 1193
8.2.3 Disconnector Switching Device................................................................................ 1195
8.2.3.1 Structure of the Disconnector Switching Device.................................................. 1195
8.2.3.2 Application and Setting Notes............................................................................ 1198
8.2.3.3 Trigger Variants of the Disconnector...................................................................1200
8.2.3.4 Settings............................................................................................................. 1203
8.2.3.5 Information List................................................................................................. 1204
8.3 Control Functionality.....................................................................................................1205
8.3.1 Command Checks and Switchgear Interlocking Protection........................................ 1205
8.3.2 Command Logging ................................................................................................. 1221
8.3.3 Settings...................................................................................................................1225
8.3.4 Information List....................................................................................................... 1226
8.4 Synchronization Function..............................................................................................1227
8.4.1 Overview of Functions............................................................................................. 1227
8.4.2 Structure of the Function.........................................................................................1227
8.4.3 Connection and Definition....................................................................................... 1228
8.4.4 General Functionality.............................................................................................. 1231
8.4.4.1 Description........................................................................................................ 1231

SIPROTEC 5, 7SJ82/7SJ85, Manual 31


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

8.4.4.2 Application and Setting Notes............................................................................ 1235


8.4.4.3 Settings............................................................................................................. 1238
8.4.5 Dynamic Measuring-Point Switching........................................................................ 1238
8.4.6 Sequence of Functions............................................................................................ 1240
8.4.7 Stage Synchrocheck.................................................................................................1242
8.4.7.1 Description........................................................................................................ 1242
8.4.7.2 Application and Setting Notes............................................................................ 1243
8.4.7.3 Settings............................................................................................................. 1243
8.4.7.4 Information List................................................................................................. 1244
8.4.8 Stage Synchronous/Asynchronous........................................................................... 1245
8.4.8.1 Description........................................................................................................ 1245
8.4.8.2 Application and Setting Notes............................................................................ 1249
8.4.8.3 Settings............................................................................................................. 1251
8.4.8.4 Information List................................................................................................. 1252
8.4.9 Stage Synchronous/Asynchronous with Balancing Commands.................................. 1253
8.4.9.1 Description........................................................................................................ 1253
8.4.9.2 Application and Setting Notes............................................................................ 1260
8.4.9.3 Settings............................................................................................................. 1270
8.4.9.4 Information List................................................................................................. 1272
8.4.10 Expanded Checks (df/dt and Smoothing of Oscillations)........................................... 1273
8.4.11 Closing at De-Energized Line/Busbar.........................................................................1274
8.4.11.1 Description........................................................................................................ 1274
8.4.11.2 Application and Setting Notes............................................................................ 1276
8.4.12 Direct Close Command ............................................................................................1277
8.4.13 Interaction with Control, Automatic Reclosing (AREC), and External Triggering......... 1278
8.4.14 External Synchronization......................................................................................... 1280
8.4.14.1 Description........................................................................................................ 1280
8.4.14.2 Application and Setting Notes (External Synchronization)................................... 1282
8.4.14.3 Settings............................................................................................................. 1283
8.4.14.4 Information List................................................................................................. 1285
8.4.15 Settings...................................................................................................................1285
8.4.16 Information List....................................................................................................... 1288
8.5 Switching Sequences.................................................................................................... 1290
8.5.1 Overview of Functions ............................................................................................ 1290
8.5.2 Function Description................................................................................................1290
8.5.3 Application and Setting Notes..................................................................................1292
8.5.4 Settings...................................................................................................................1296
8.5.5 Information List....................................................................................................... 1296
8.6 User-Defined Function Block [Control]........................................................................... 1297
8.6.1 Overview of Functions............................................................................................. 1297
8.6.2 Function Description................................................................................................1297
8.6.3 Application and Setting Notes..................................................................................1298
8.6.4 Settings...................................................................................................................1300
8.6.5 Information List....................................................................................................... 1300
8.7 CFC-Chart Settings........................................................................................................ 1302
8.7.1 Overview of Functions............................................................................................. 1302
8.7.2 Function Description................................................................................................1302
8.7.3 Application and Setting Notes..................................................................................1302
8.7.4 Settings...................................................................................................................1303
8.7.5 Information List....................................................................................................... 1303

32 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

8.8 Transformer Tap Changers............................................................................................ 1304


8.8.1 Function Description................................................................................................1304
8.8.2 Application and Setting Notes..................................................................................1308
8.8.3 Settings...................................................................................................................1315
8.8.4 Information List....................................................................................................... 1315
8.9 Voltage Controller......................................................................................................... 1316
8.9.1 Overview of Functions............................................................................................. 1316
8.9.2 Structure of the Function.........................................................................................1316
8.9.3 Function Description................................................................................................1317
8.9.3.1 General..............................................................................................................1317
8.9.3.2 Logic of the Function......................................................................................... 1324
8.9.3.3 Control Response............................................................................................... 1325
8.9.3.4 Function Supervision..........................................................................................1328
8.9.3.5 Line Compensation............................................................................................ 1328
8.9.3.6 Limiting Values.................................................................................................. 1330
8.9.3.7 Blockings........................................................................................................... 1330
8.9.3.8 Parallel Operation.............................................................................................. 1331
8.9.3.9 Creating a GOOSE Later Binding for Parallel Control ........................................... 1343
8.9.3.10 Functional Measured Values...............................................................................1351
8.9.4 Application and Setting Notes..................................................................................1355
8.9.4.1 General..............................................................................................................1355
8.9.4.2 Controlling.........................................................................................................1357
8.9.4.3 Voltage Controller.............................................................................................. 1358
8.9.4.4 Line Compensation............................................................................................ 1363
8.9.4.5 Limiting Values.................................................................................................. 1366
8.9.4.6 Blockings........................................................................................................... 1367
8.9.4.7 Parallel Control...................................................................................................1368
8.9.5 Settings...................................................................................................................1369
8.9.6 Information List....................................................................................................... 1379
8.10 Point-on-Wave Switching.............................................................................................. 1383

9 Supervision Functions............................................................................................................................ 1385


9.1 Overview...................................................................................................................... 1386
9.2 Resource-Consumption Supervision...............................................................................1387
9.2.1 Load Model............................................................................................................. 1387
9.2.2 Function Points........................................................................................................1389
9.2.3 CFC Resources......................................................................................................... 1390
9.3 Supervision of the Secondary System............................................................................ 1392
9.3.1 Overview.................................................................................................................1392
9.3.2 Measuring-Voltage Failure....................................................................................... 1392
9.3.2.1 Overview of Functions....................................................................................... 1392
9.3.2.2 Structure of the Function .................................................................................. 1393
9.3.2.3 Unbalanced Measuring-Voltage Failure...............................................................1395
9.3.2.4 3-Phase Measuring-Voltage Failure.....................................................................1396
9.3.2.5 Switching onto a 3-Phase Measuring-Voltage Failure, Low Load..........................1397
9.3.2.6 Application and Setting Notes............................................................................ 1398
9.3.2.7 Settings............................................................................................................. 1399
9.3.2.8 Information List................................................................................................. 1400
9.3.3 Signaling-Voltage Supervision..................................................................................1400
9.3.3.1 Overview of Functions....................................................................................... 1400
9.3.3.2 Structure of the Function................................................................................... 1400
9.3.3.3 Function Description.......................................................................................... 1401
9.3.3.4 Application and Setting Notes............................................................................ 1403

SIPROTEC 5, 7SJ82/7SJ85, Manual 33


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

9.3.3.5 Settings............................................................................................................. 1404


9.3.3.6 Information List................................................................................................. 1405
9.3.4 Voltage-Transformer Circuit Breaker.........................................................................1406
9.3.4.1 Overview of Functions....................................................................................... 1406
9.3.4.2 Structure of the Function .................................................................................. 1406
9.3.4.3 Function Description.......................................................................................... 1406
9.3.4.4 Application and Setting Notes............................................................................ 1406
9.3.4.5 Settings............................................................................................................. 1407
9.3.4.6 Information List................................................................................................. 1407
9.3.5 Voltage-Balance Supervision.................................................................................... 1407
9.3.5.1 Overview of Functions .......................................................................................1407
9.3.5.2 Structure of the Function................................................................................... 1407
9.3.5.3 Function Description.......................................................................................... 1408
9.3.5.4 Application and Setting Notes............................................................................ 1409
9.3.5.5 Settings............................................................................................................. 1409
9.3.5.6 Information List................................................................................................. 1410
9.3.6 Voltage-Sum Supervision......................................................................................... 1410
9.3.6.1 Overview of Functions .......................................................................................1410
9.3.6.2 Structure of the Function .................................................................................. 1410
9.3.6.3 Function Description.......................................................................................... 1410
9.3.6.4 Application and Setting Notes............................................................................ 1412
9.3.6.5 Settings............................................................................................................. 1412
9.3.6.6 Information List................................................................................................. 1412
9.3.7 Voltage Phase-Rotation Supervision......................................................................... 1413
9.3.7.1 Overview of Functions .......................................................................................1413
9.3.7.2 Structure of the Function .................................................................................. 1413
9.3.7.3 Function Description.......................................................................................... 1413
9.3.7.4 Application and Setting Notes ........................................................................... 1414
9.3.7.5 Settings............................................................................................................. 1414
9.3.7.6 Information List................................................................................................. 1414
9.3.8 Voltage-Comparison Supervision..............................................................................1415
9.3.8.1 Overview of Functions....................................................................................... 1415
9.3.8.2 Structure of the Function................................................................................... 1415
9.3.8.3 Description........................................................................................................ 1415
9.3.8.4 Application and Setting Notes............................................................................ 1419
9.3.8.5 Settings............................................................................................................. 1419
9.3.8.6 Information List................................................................................................. 1420
9.3.9 Broken-Wire Detection............................................................................................. 1420
9.3.9.1 Overview of Functions....................................................................................... 1420
9.3.9.2 Structure of the Function................................................................................... 1420
9.3.9.3 Function Description.......................................................................................... 1420
9.3.9.4 Application and Setting Notes............................................................................ 1421
9.3.9.5 Settings............................................................................................................. 1421
9.3.9.6 Information List................................................................................................. 1421
9.3.10 Current-Balance Supervision.................................................................................... 1422
9.3.10.1 Overview of Functions .......................................................................................1422
9.3.10.2 Structure of the Function................................................................................... 1422
9.3.10.3 Function Description.......................................................................................... 1422
9.3.10.4 Application and Setting Notes............................................................................ 1423
9.3.10.5 Settings............................................................................................................. 1424
9.3.10.6 Information List................................................................................................. 1424
9.3.11 Current-Sum Supervision......................................................................................... 1424
9.3.11.1 Overview of Functions .......................................................................................1424
9.3.11.2 Structure of the Function................................................................................... 1425
9.3.11.3 Function Description.......................................................................................... 1425
9.3.11.4 Application and Setting Notes............................................................................ 1427

34 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

9.3.11.5 Settings............................................................................................................. 1427


9.3.11.6 Information List................................................................................................. 1428
9.3.12 Current Phase-Rotation Supervision......................................................................... 1428
9.3.12.1 Overview of Functions .......................................................................................1428
9.3.12.2 Structure of the Function .................................................................................. 1428
9.3.12.3 Function Description.......................................................................................... 1429
9.3.12.4 Application and Setting Notes ........................................................................... 1430
9.3.12.5 Settings............................................................................................................. 1430
9.3.12.6 Information List................................................................................................. 1430
9.3.13 Trip-Circuit Supervision............................................................................................ 1430
9.3.13.1 Overview of Functions....................................................................................... 1430
9.3.13.2 Structure of the Function .................................................................................. 1430
9.3.13.3 Trip-Circuit Supervision with 2 Binary Inputs....................................................... 1431
9.3.13.4 Trip-Circuit Supervision with 1 Binary Input.........................................................1432
9.3.13.5 Application and Setting Notes ........................................................................... 1435
9.3.13.6 Settings............................................................................................................. 1436
9.3.13.7 Information List................................................................................................. 1436
9.3.14 Closing-Circuit Supervision...................................................................................... 1436
9.3.14.1 Overview of Functions....................................................................................... 1436
9.3.14.2 Structure of the Function................................................................................... 1436
9.3.14.3 Closing-Circuit Supervision with 2 Binary Inputs..................................................1437
9.3.14.4 Closing-Circuit Supervision with 1 Binary Input................................................... 1438
9.3.14.5 Application and Setting Notes............................................................................ 1441
9.3.14.6 Settings............................................................................................................. 1441
9.3.14.7 Information List................................................................................................. 1441
9.4 Supervision of the Device Hardware.............................................................................. 1443
9.4.1 Overview.................................................................................................................1443
9.4.2 Analog-Channel Supervision via Fast Current-Sum....................................................1444
9.4.2.1 Overview of Functions....................................................................................... 1444
9.4.2.2 Structure of the Function................................................................................... 1444
9.4.2.3 Function Description.......................................................................................... 1445
9.5 Supervision of Device Firmware.....................................................................................1448
9.6 Supervision of Hardware Configuration......................................................................... 1449
9.7 Supervision of Communication Connections..................................................................1450
9.8 Error Responses and Corrective Measures...................................................................... 1451
9.8.1 Overview.................................................................................................................1451
9.8.2 Defect Severity 1..................................................................................................... 1452
9.8.3 Defect Severity 2..................................................................................................... 1456
9.8.4 Defect Severity 3..................................................................................................... 1457
9.8.5 Defect Severity 4 (Group Alarm)...............................................................................1458
9.9 Group Indications..........................................................................................................1460

10 Measured Values, Energy Values, and Supervision of the Primary System........................................... 1463
10.1 Overview of Functions.................................................................................................. 1464
10.2 Structure of the Function.............................................................................................. 1465
10.3 Operational Measured Values........................................................................................ 1467
10.4 Fundamental and Symmetrical Components..................................................................1469
10.5 Average Values............................................................................................................. 1470
10.5.1 Function Description of Average Values................................................................... 1470
10.5.2 Application and Setting Notes for Average Values.................................................... 1470

SIPROTEC 5, 7SJ82/7SJ85, Manual 35


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

10.6 Minimum/Maximum Values...........................................................................................1473


10.6.1 Function Description of Minimum/Maximum Values.................................................1473
10.6.2 Application and Setting Notes for Minimum/Maximum Values.................................. 1474
10.7 Energy Values............................................................................................................... 1475
10.7.1 Function Description of Energy Values..................................................................... 1475
10.7.2 Application and Setting Notes for Energy Values...................................................... 1476
10.8 User-Defined Metered Values........................................................................................ 1478
10.8.1 Function Description of Pulse-Metered Values.......................................................... 1478
10.8.2 Application and Setting Notes for Pulse-Metered Values........................................... 1479
10.9 Phasor Measurement Unit (PMU)...................................................................................1482
10.9.1 Overview of Functions............................................................................................. 1482
10.9.2 Structure of the Function Group.............................................................................. 1482
10.9.3 Function Description................................................................................................1482
10.9.4 Transmitted Data..................................................................................................... 1487
10.9.5 PMU Communication (IEEE C37.118)....................................................................... 1487
10.9.6 Parameterizing the PMU with DIGSI..........................................................................1489
10.9.7 Parameterizing the PMU on the Device.....................................................................1496
10.9.8 Application and Setting Notes..................................................................................1498
10.9.9 Settings...................................................................................................................1499
10.9.10 Information List....................................................................................................... 1501
10.10 Measuring Transducers................................................................................................. 1502
10.10.1 Overview of Functions ............................................................................................ 1502
10.10.2 Structure of the Function ........................................................................................ 1502
10.10.3 Function Description................................................................................................1502
10.10.4 Application and Setting Notes..................................................................................1505
10.10.5 Settings...................................................................................................................1506
10.10.6 Information List....................................................................................................... 1508
10.11 Statistical Values of the Primary System......................................................................... 1509
10.12 Circuit-Breaker Wear Monitoring....................................................................................1510
10.12.1 Overview of Functions ............................................................................................ 1510
10.12.2 Structure of the Function.........................................................................................1510
10.12.3 General Functionality.............................................................................................. 1511
10.12.3.1 Description........................................................................................................ 1511
10.12.3.2 Application and Setting Notes............................................................................ 1512
10.12.3.3 Settings............................................................................................................. 1513
10.12.3.4 Information List................................................................................................. 1513
10.12.4 ΣI*-Method Stage.................................................................................................... 1514
10.12.4.1 Description........................................................................................................ 1514
10.12.4.2 Application and Setting Notes............................................................................ 1516
10.12.4.3 Settings............................................................................................................. 1516
10.12.4.4 Information List................................................................................................. 1516
10.12.5 2P-Method Stage..................................................................................................... 1517
10.12.5.1 Description........................................................................................................ 1517
10.12.5.2 Application and Setting Notes............................................................................ 1520
10.12.5.3 Settings............................................................................................................. 1521
10.12.5.4 Information List................................................................................................. 1521
10.12.6 I2t-Method Stage.....................................................................................................1522
10.12.6.1 Description........................................................................................................ 1522
10.12.6.2 Application and Setting Notes............................................................................ 1523

36 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

10.12.6.3 Settings............................................................................................................. 1523


10.12.6.4 Information List................................................................................................. 1523
10.12.7 Supervision CB Make Time Stage..............................................................................1524
10.12.7.1 Description........................................................................................................ 1524
10.12.7.2 Application and Setting Notes............................................................................ 1525
10.12.7.3 Settings............................................................................................................. 1525
10.12.7.4 Information List................................................................................................. 1526

11 Functional Tests......................................................................................................................................1527
11.1 General Notes............................................................................................................... 1528
11.2 Direction Test of the Phase Quantities (Current and Voltage Connection) ...................... 1529
11.3 Direction Test of Ground Quantities for Directional Ground-Fault Functions................... 1530
11.3.1 Overview.................................................................................................................1530
11.3.2 Directional Testing for Solid or Resistive-Grounded Systems..................................... 1530
11.3.3 Directional Testing for Isolated or Resonant-Grounded Systems................................ 1532
11.4 Functional Test of Thermal Overload Protection ............................................................ 1534
11.5 Primary and Secondary Tests of the Circuit-Breaker Failure Protection............................ 1536
11.6 Circuit-Breaker Test....................................................................................................... 1539
11.7 Functional Test of the Inrush-Current Detection ............................................................ 1542
11.8 Functional Test of Transient Ground-Fault Protection .................................................... 1543
11.9 Functional Test of the Trip-Circuit Supervision .............................................................. 1544
11.10 Functional Test for the Phase-Rotation Reversal............................................................. 1545
11.11 Functional Test for Overvoltage Protection with Zero-Sequence Voltage/Residual
Voltage ........................................................................................................................ 1546
11.12 Primary and Secondary Testing of the Synchronization Function.................................... 1548
11.13 Testing the Negative-Sequence Current ........................................................................ 1552
11.14 Reverse-Power Protection..............................................................................................1553
11.14.1 Secondary Test........................................................................................................ 1553
11.14.2 Primary Test............................................................................................................ 1553
11.15 Functional Test Protection Communication....................................................................1556
11.15.1 Checking the Protection-Data Communication......................................................... 1556
11.15.2 Directional Test .......................................................................................................1557
11.16 Functional Test for Overexcitation Protection ................................................................1558
11.17 Functional Test Differential Protection for Capacitor Banks.............................................1559
11.17.1 Secondary Tests.......................................................................................................1559
11.17.2 Primary Tests........................................................................................................... 1560
11.18 Commissioning Hints for Voltage Control...................................................................... 1561
11.18.1 Secondary Tests.......................................................................................................1561
11.18.1.1 General..............................................................................................................1561
11.18.1.2 Checking the Transformer Tap Position...............................................................1561
11.18.1.3 Check of the Voltage-Control Function............................................................... 1564
11.18.1.4 Further Tests......................................................................................................1565
11.18.1.5 Voltage-Control Function for Parallel Transformers............................................. 1568
11.18.2 Primary Tests........................................................................................................... 1573

12 Technical Data........................................................................................................................................ 1577


12.1 General Device Data......................................................................................................1580
12.1.1 Analog Inputs.......................................................................................................... 1580
12.1.2 Supply Voltage........................................................................................................ 1583

SIPROTEC 5, 7SJ82/7SJ85, Manual 37


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

12.1.3 Binary Inputs........................................................................................................... 1584


12.1.4 Relay Outputs.......................................................................................................... 1585
12.1.5 Design Data.............................................................................................................1587
12.2 Protection Interface and Protection Topology................................................................ 1591
12.3 Date and Time Synchronization..................................................................................... 1593
12.4 Analog-Units Function Group........................................................................................ 1594
12.5 Overcurrent Protection, Phases......................................................................................1595
12.5.1 Stage with Definite-Time Characteristic Curve.......................................................... 1595
12.5.2 Stage with Inverse-Time Characteristic Curve........................................................... 1597
12.5.3 Stage with User-Defined Characteristic Curve .......................................................... 1604
12.6 Voltage-Dependent Overcurrent Protection, Phases....................................................... 1607
12.7 Overcurrent Protection, Ground.................................................................................... 1610
12.7.1 Stage with Definite-Time Characteristic Curve ......................................................... 1610
12.7.2 Stage with Inverse-Time Characteristic Curve........................................................... 1611
12.7.3 Stage with User-Defined Characteristic Curve .......................................................... 1618
12.8 Directional Overcurrent Protection, Phases.................................................................... 1620
12.8.1 Stage with Definite-Time Characteristic Curve.......................................................... 1620
12.8.2 Stage with Inverse-Time Characteristic Curve........................................................... 1621
12.8.3 Stage with User-Defined Characteristic Curve........................................................... 1624
12.9 Directional Overcurrent Protection, Ground................................................................... 1626
12.9.1 Stage with Definite-Time Characteristic Curve.......................................................... 1626
12.9.2 Stage with Inverse-Time Characteristic Curve........................................................... 1627
12.9.3 Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse Char-
acteristic Curve........................................................................................................1629
12.9.4 Stage with Knee-Point Characteristic Curve ............................................................. 1631
12.9.5 Stage with User-Defined Characteristic Curve........................................................... 1633
12.10 Inrush-Current Detection...............................................................................................1636
12.11 Arc Protection............................................................................................................... 1637
12.12 Instantaneous High-Current Tripping.............................................................................1638
12.13 Instantaneous Tripping at Switch onto Fault ................................................................. 1639
12.14 Overcurrent Protection, 1-Phase.................................................................................... 1640
12.14.1 Stage with Definite-Time Characteristic Curve.......................................................... 1640
12.14.2 Stage with Inverse-Time Characteristic Curve........................................................... 1641
12.14.3 Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse Char-
acteristic Curve........................................................................................................1643
12.14.4 Stage with User-Defined Characteristic Curve .......................................................... 1645
12.15 Overcurrent Protection, 1-Phase (Fast Stage)................................................................. 1647
12.16 Positive-Sequence Overcurrent Protection..................................................................... 1648
12.16.1 Stage with Definite-Time Characteristic Curve.......................................................... 1648
12.16.2 Stage with Inverse-Time Characteristic Curve........................................................... 1649
12.17 Non-Directional Intermittent Ground-Fault Protection....................................................1651
12.18 Directional Intermittent Ground-Fault Protection........................................................... 1653
12.19 Sensitive Ground-Fault Detection.................................................................................. 1655
12.19.1 General................................................................................................................... 1655
12.19.2 Directional 3I0 Stage with Cos φ or Sin φ Measurement........................................... 1656
12.19.3 Directional Transient Ground-Fault Stage................................................................. 1657

38 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

12.19.4 Directional 3I0 Stage with φ(V0,3I0) Measurement.................................................. 1658


12.19.5 Directional Y0 Stage with G0 or B0 Measurement (Admittance)................................1659
12.19.6 Directional Stage with Phasor Measurement of a Harmonic...................................... 1660
12.19.7 Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage................... 1661
12.19.8 Non-Directional 3I0 Stage........................................................................................ 1662
12.19.9 Non-Directional Y0 Stage......................................................................................... 1662
12.19.10 Non-Directional 3I0 Harmonic Stage........................................................................ 1663
12.19.11 Pulse-Pattern Detection Stage.................................................................................. 1664
12.20 Undercurrent Protection................................................................................................1666
12.21 Negative-Sequence Protection.......................................................................................1668
12.21.1 Stage with Definite-Time Characteristic Curve.......................................................... 1668
12.21.2 Stage with Inverse-Time Characteristic Curve........................................................... 1669
12.22 Directional Negative-Sequence Protection with Definite-Time Delay...............................1672
12.23 Thermal Overload Protection, 3-Phase – Advanced........................................................ 1674
12.24 Thermal Overload Protection, User-Defined Characteristic Curve.................................... 1678
12.25 Thermal Overload Protection, 1-Phase........................................................................... 1679
12.26 Unbalanced-Load Protection..........................................................................................1682
12.27 Overcurrent Protection for Capacitor Banks....................................................................1684
12.27.1 Stage with Definite-Time Characteristic Curve.......................................................... 1684
12.27.2 Stage with Inverse-Time Characteristic Curve........................................................... 1686
12.27.3 Stage with User-Defined Characteristic Curve .......................................................... 1693
12.28 Current-Unbalance Protection for Capacitors, 3-Phase....................................................1696
12.29 Current-Unbalance Protection for Capacitors, 1-Phase....................................................1698
12.30 Voltage-Differential Protection for Capacitors................................................................ 1700
12.31 Differential Protection for Capacitor Banks.....................................................................1701
12.32 Overvoltage Protection with 3-Phase Voltage.................................................................1704
12.33 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage ...........................1706
12.34 Overvoltage Protection with Positive-Sequence Voltage ................................................ 1708
12.35 Overvoltage Protection with Negative-Sequence Voltage .............................................. 1709
12.36 Overvoltage Protection with Any Voltage.......................................................................1710
12.37 Peak Overvoltage Protection for Capacitors....................................................................1712
12.38 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage ..... 1714
12.39 Undervoltage Protection with 3-Phase Voltage.............................................................. 1715
12.40 Undervoltage Protection with Positive-Sequence Voltage...............................................1718
12.41 Undervoltage Protection with Any Voltage ....................................................................1720
12.42 Overfrequency Protection..............................................................................................1722
12.43 Underfrequency Protection........................................................................................... 1723
12.44 Underfrequency Load Shedding.................................................................................... 1724
12.45 Rate of Frequency Change Protection............................................................................ 1726
12.46 Vector-Jump Protection................................................................................................. 1728
12.47 Power Protection (P,Q), 3-Phase.................................................................................... 1729
12.48 Reverse-Power Protection..............................................................................................1730
12.49 Overexcitation Protection..............................................................................................1731
12.50 Undervoltage-Controlled Reactive-Power Protection...................................................... 1733

SIPROTEC 5, 7SJ82/7SJ85, Manual 39


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

12.51 Circuit-Breaker Failure Protection ..................................................................................1735


12.52 Circuit-Breaker Restrike Protection................................................................................. 1737
12.53 Restricted Ground-Fault Protection................................................................................ 1738
12.54 External Trip Initiation .................................................................................................. 1740
12.55 Automatic Reclosing..................................................................................................... 1741
12.56 Fault Locator.................................................................................................................1742
12.57 Fault Locator Plus..........................................................................................................1743
12.58 Temperature Supervision.............................................................................................. 1744
12.59 Current-Jump Detection................................................................................................ 1745
12.60 Voltage-Jump Detection................................................................................................ 1746
12.61 Synchronization Function..............................................................................................1747
12.62 Voltage Controller......................................................................................................... 1750
12.63 Current-Balance Supervision..........................................................................................1754
12.64 Voltage-Balance Supervision .........................................................................................1755
12.65 Current-Sum Supervision...............................................................................................1756
12.66 Voltage-Sum Supervision.............................................................................................. 1757
12.67 Current Phase-Rotation Supervision .............................................................................. 1758
12.68 Voltage Phase-Rotation Supervision .............................................................................. 1759
12.69 Voltage-Comparison Supervision................................................................................... 1760
12.70 Trip-Circuit Supervision ................................................................................................ 1761
12.71 Closing-Circuit Supervision............................................................................................ 1762
12.72 Analog Channel Supervision via Fast Current Sum .........................................................1763
12.73 Measuring-Voltage Failure Detection............................................................................. 1764
12.74 Voltage-Transformer Circuit Breaker ............................................................................. 1766
12.75 Operational Measured Values and Statistical Values....................................................... 1767
12.76 Energy Values............................................................................................................... 1771
12.77 Phasor Measurement Unit............................................................................................. 1772
12.78 Circuit-Breaker Wear Monitoring ...................................................................................1773
12.79 CFC...............................................................................................................................1774
12.80 Point-on-Wave Switching.............................................................................................. 1778

A Appendix................................................................................................................................................ 1779
A.1 Order Configurator and Order Options...........................................................................1780
A.2 Ordering Accessories.....................................................................................................1781
A.3 Typographic and Symbol Conventions........................................................................... 1783
A.4 Standard Variants for 7SJ82.......................................................................................... 1786
A.5 Standard Variants for 7SJ85.......................................................................................... 1789
A.6 Current Transformer Requirements ...............................................................................1793
A.7 Connection Examples for Current Transformers............................................................. 1796
A.8 Connection Examples of Voltage Transformers for Modular Devices............................... 1803
A.9 Connection Examples of Voltage Transformers for Non-Modular Devices........................1809
A.10 Prerouting 7SJ82/85 General......................................................................................... 1813
A.11 Prerouting 7SJ82/85 Capacitor Bank Applications...........................................................1815

Glossary.................................................................................................................................................. 1817

40 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Table of Contents

Index.......................................................................................................................................................1837

SIPROTEC 5, 7SJ82/7SJ85, Manual 41


C53000-G5040-C017-A, Edition 06.2019
42 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
1 Introduction

1.1 General 44
1.2 Properties of SIPROTEC 5 46

SIPROTEC 5, 7SJ82/7SJ85, Manual 43


C53000-G5040-C017-A, Edition 06.2019
Introduction
1.1 General

1.1 General
The digital multifunctional protection and bay controllers of the SIPROTEC 5 device series are equipped with a
powerful microprocessor. As a result, all tasks, from acquiring measurands to entering commands in the
circuit breaker, are processed digitally.

Analog Inputs
The measuring inputs transform the currents and voltages sent by the instrument transformers and adapt
them to the internal processing level of the device. A SIPROTEC 5 device has a current transformer and,
depending on the device type, a voltage transformer. The current inputs are therefore intended for the detec-
tion of phase currents and ground current. The ground current can be detected sensitively using a core
balance current transformer. In addition, phase currents can be detected very sensitively for a particularly
precise measurement. The voltage inputs detect the measuring voltage of device functions requiring current
and voltage measured values.
The analog values are digitized in the internal microcomputer for data processing.

Microcomputer System
All device functions are processed in the microcomputer system.
This includes, for example:

• Filtering and preparation of the measurands

• Constant monitoring of the measurands

• Monitoring of the pickup conditions for the individual protection functions

• Querying of limiting values and time-outs

• Controlling of signals for the logic functions

• Decision about the trip and close commands

• Storage of indications, fault data, and fault values for fault analysis

• Administration of the operating system and its functions, such as data storage, real-time clock, communi-
cation, interfaces, etc.

• External distribution of information

Binary Inputs and Outputs


Using the binary inputs and outputs, the device receives information from the system or from other devices
(such as locking commands). The most important outputs include the commands to the switching devices and
the indications for remote signaling of important events and states.

Front Elements
For devices with an integrated or offset operation panel, LEDs and an LC display on the front provide informa-
tion on the device function and report events, states, and measured values. In conjunction with the LC display,
the integrated keypad enables on-site operation of the device. All device information such as setting parame-
ters, operating and fault indications or measured values can be displayed, and setting parameters changed. In
addition, system equipment can be controlled via the user interface of the device.

Serial Interfaces
The serial interface in the front cover enables communication with a personal computer when using the DIGSI
operating program. As a result, the operation of all device functions is possible. Additional interfaces on the
back are used to realize various communication protocols.

44 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Introduction
1.1 General

Power Supply
The individual functional units of the device are powered by an internal power supply. Brief interruptions in
the supply voltage, which can occur during short circuits in the system auxiliary voltage supply are generally
bridged by capacitor storage (see also the Technical Data).

SIPROTEC 5, 7SJ82/7SJ85, Manual 45


C53000-G5040-C017-A, Edition 06.2019
Introduction
1.2 Properties of SIPROTEC 5

1.2 Properties of SIPROTEC 5


The SIPROTEC 5 devices at the bay level are compact and can be installed directly in medium and high-voltage
switchgear. They are characterized by comprehensive integration of protection and control functions.

General Properties

• Powerful microprocessor

• Fully digital measured-value processing and control, from sampling and digitizing of measurands to
closing and tripping decisions for the circuit breaker

• Complete galvanic and interference-free isolation of the internal processing circuits from the system
measuring, control, and supply circuits through instrument transformers, binary input and output
modules, and DC and AC voltage converters

• Easy operation using an integrated operator and display panel, or using a connected personal computer
with user interface

• Continuous display of measured and metered values at the front

• Storage of min/max measured values (slave pointer function) and storage of long-term average values

• Storage of fault indications for system incidents (faults in system) with real-time assignment and instan-
taneous values for fault recording

• Continuous monitoring of the measurands as well as the device hardware and software

• Communication with central control and storage devices possible via the device interface

• Battery-buffered, synchronizable clock

Modular Concept
The SIPROTEC 5 modular concept ensures the consistency and integrity of all functionalities across the entire
device series. Significant features here include:

• Modular system design in hardware, software, and communication

• Functional integration of various applications, such as protection, control, and fault recorder

• The same expansion and communication modules for all devices in the family

• Innovative terminal technology with easy assembly and interchangeability and the highest possible
degree of safety

• The same functions can be configured individually across the entire family of devices

• Ability to upgrade with innovations possible at all times through libraries

• Open, scalable architecture for IT integration and new functions

• Multi-layered security mechanisms in all links of the security chain

• Self-monitoring routines for reliable localization and indication of device faults

• Automatic logging of access attempts and safety-critical operations on the devices and systems

Redundant Communication
SIPROTEC 5 devices maintain complete communication redundancy:

• Multiple redundant communication interfaces

• Redundant and independent protocols to control centers possible (such as IEC 60870-5-103 and
IEC 61850, either single or redundant)

• Redundant time synchronization (such as IRIG-B, SNTP, or IEEE 1588)

46 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
2 Basic Structure of the Function

2.1 Function Embedding in the Device 48


2.2 Adjustment of Application Templates/Functional Scope 55
2.3 Function Control 57
2.4 Text Structure and Reference Number for Settings and Indications 61
2.5 Information Lists 63

SIPROTEC 5, 7SJ82/7SJ85, Manual 47


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.1 Function Embedding in the Device

2.1 Function Embedding in the Device


General
SIPROTEC 5 devices offer great flexibility in the handling of functions. Functions can be individually loaded
into the device. Additionally, it is possible to copy functions within a device or between devices. The necessary
integration of functions in the device is illustrated by the following example.

NOTE

i The availability of certain settings and setting options depends on the device type and the functions avail-
able on the device!

EXAMPLE
A 1 1/2 circuit-breaker layout of the 7SA86 distance protection device serves as an example. The following
protection functions are required for implementation (simplified and reduced):

• Distance protection (21)

• Overcurrent protection, phases (51)

• Circuit-breaker failure protection (50BF), for circuit breakers 1 and 2

• Basic functionality (handling of tripping, etc.)

Several predefined function packages that are tailored to specific applications exist for each device family. A
predefined functional scope is called an application template. The existing application templates are offered
for selection automatically when you create a new device in DIGSI 5.

EXAMPLE
When creating the device in DIGSI 5, you must select the appropriate application template. In the example,
select the application template DIS overhead line, grounded systems, 1 1/2 circuit-breaker layout. This
application template covers the required functional scope. Selecting this application template determines the
preconfigured functional scope. This can be changed as necessary (see chapter 2.2 Adjustment of Application
Templates/Functional Scope).

Function Groups (FG)


Functions are arranged in function groups. This simplifies handling of functions (adding and copying). The
function groups are assigned to primary objects, such as a line, transformer, or circuit breaker.
The function groups bundle functions with regard to the following basic tasks:

• Assignment of functions to current and/or voltage transformers (assignment of functions to the meas-
uring points and thus to the protected object)

• Exchange of information between function groups


When a function is copied into a function group, it automatically works with the measuring points assigned to
the function group. Their output signals are also automatically included in the configured interfaces of the
function group.
The number and type of function groups differ in the respective application templates, depending on the type
of the device and application. You can add, copy, or even delete function groups for a specific application. You
can also adapt the functional scope within a function group according to the use case. You can find detailed
information on this in the DIGSI 5 Online help.

48 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.1 Function Embedding in the Device

EXAMPLE
The selected application template DIS overhead line, grounded systems, 1 1/2 circuit-breaker layout
comprises 3 function groups:

• Protection function group Line 1

• Circuit-breaker function group QA 1

• Circuit-breaker function group QA 2


The following figure shows the embedding of functions via function groups.

[dweifkfg-021012-01.tif, 1, en_US]

Figure 2-1 Embedding the Functions via Function Groups

Depending on the type of device, there are different types of function groups:

• Protection function groups

• Circuit-breaker function groups


Protection function groups bundle functions that are assigned to one protected object – for example, to the
line. Depending on the device type and nature of the protected object, there are different types of protection
function groups (line, voltage/current 3-phase, transformer, motor, generator, etc.).
Circuit-breaker function groups bundle functions assigned to the local switches – for example, circuit breakers
and disconnectors (such as processing of tripping, circuit-breaker failure protection , automatic reclosing).
The number and type of function groups differ in the respective application templates, depending on the type
of the device and application. You can add, copy, or even delete function groups for a specific application. You
can also adapt the functional scope within a function group according to the use case. You can find detailed
information on this in the DIGSI 5 Online help.

SIPROTEC 5, 7SJ82/7SJ85, Manual 49


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.1 Function Embedding in the Device

Interface Between Function Group and Measuring Point


The function groups receive the measurands of the current and voltage transformers from measuring points.
For this, the function groups are connected to one or more measuring points.
The number of measuring points and the assignment of function groups to the measuring points are preset by
the selected application template in accordance with the specific application. Therefore, this specifies which
measuring point(s) and the corresponding measurands have to be used by which function within the function
group.

EXAMPLE
The measuring points are assigned to the function groups in the application template in Figure 2-1 as follows:

• The protection function group Line is assigned to the measuring points I-3ph 1, I-3ph 2, and V-3ph 1.
The function group therefore receives the measured values from current transformers 1 and 2 and from
voltage transformer 1. The currents of measuring points I-3ph 1 and I-3ph 2 are added geometrically for
feeder-related processing.

• The circuit-breaker function group QA1 is assigned to the measuring point I-3ph 1 and receives the
measured values from current transformer 1.

• The circuit-breaker function group QA2 is assigned to the measuring point I-3ph 2 and receives the
measured values from current transformer 2.

The user can change the assignment as needed, that is, function groups can be assigned to any available
measuring points of the device.
To check or change the assignment of measuring points to the function groups, double-click Function-group
connections in the DIGSI 5 project tree.

[scfgverb-190214-01, 1, en_US]

Figure 2-2 Project Tree in DIGSI 5 (Detail)

The window for routing of the measuring points opens in the working area (see the following Figure, does not
correspond to the example).

50 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.1 Function Embedding in the Device

[scmscofg-180311-01.tif, 1, en_US]

Figure 2-3 Connecting Measuring Points and Function Groups

Interface Between Protection and Circuit-Breaker Function Groups


The protection function group(s) is/are connected to one or several circuit-breaker function groups. This
connection generally determines:

• Which circuit breaker(s) is/are started by the protection functions of the protection FG.

• Starting the Circuit-breaker failure protection function (if available in the Circuit-breaker function
group) through the protection functions of the connected protection function group

• Starting the Automatic reclosing function (AREC, if available in the Circuit-breaker function group)
through the protection functions of the connected Protection function group
Besides the general assignment of the protection function group(s) to the circuit-breaker function groups, you
can also configure the interface for specific functionalities in detail. Further information on this is included
later in the section. Figure 2-6 shows how to reach the detail configuration. Figure 2-7 shows the possible
assignments in detail.
These definitions are also set appropriately for the specific application by the selected application template.
The user can change this linkage as needed, that is, protection function groups can be freely assigned to any
Circuit-breaker function groups.
To check or change the assignment of the protection function groups to the circuit-breaker function groups,
double-click Function group connections in the DIGSI 5 project tree → Name of device (see following
figure).

[scfgverb-190214-01, 1, en_US]

Figure 2-4 Project Tree in DIGSI 5 (Detail)

The window for general routing of the function groups opens in the working area (see following figure).

SIPROTEC 5, 7SJ82/7SJ85, Manual 51


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.1 Function Embedding in the Device

[scfgcols-220211-01.tif, 1, en_US]

Figure 2-5 Connection of Protection Function Group with Circuit-Breaker Function Group

Besides the general assignment of the protection function group(s) to the circuit-breaker function groups, you
can also configure the interface for specific functionalities in detail. Proceed as follows:

• Open the SIPROTEC 5 device folder in the DIGSI 5 project tree.

• Open the function settings folder in the DIGSI 5 project tree.

• Open the respective protection function group in the DIGSI 5 project tree, for example, Line 1 (see the
following figure).

52 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.1 Function Embedding in the Device

[sclsinta-190214-01, 1, en_US]

Figure 2-6 Project Tree in DIGSI 5 (Detail)

• Double-click Circuit-breaker interaction (see Figure 2-6).

• The window for the detailed configuration of the interface between the protection function group and
the Circuit-breaker function group(s) opens in the working area.

• In this view, configure the interface via the context menu (right mouse button), see Figure 2-7.

SIPROTEC 5, 7SJ82/7SJ85, Manual 53


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.1 Function Embedding in the Device

[scdetail-220211-01.tif, 1, en_US]

Figure 2-7 Detail Configuration of the Interface Between the Protection Function Group and the Circuit-
Breaker Function Group(s)

In the detail configuration of the interface, you define:

• Which operate indications of the protection functions go into the generation of the trip command

• Which protection functions start the automatic reclosing function

• Which protection functions block the automatic reclosing function

• Which protection functions start the Circuit-breaker failure protection function

Functions (FN), Tripping Stages/Function Blocks (FB)


As already illustrated in Figure 2-1, functions are assigned to the protected objects or other primary objects via
function groups.
Functions can be further subdivided. For example, protection functions often consist of multiple protection
stages (for example, the Overcurrent-protection function). Other functions can contain one or more function
blocks.
Each stage, each function block, and each function (without stages/function blocks) can be individually
switched into specific operating modes (for example, switch on/off). This is termed function control and is
explained in chapter 2.3 Function Control.
To adjust the functionality to the specific application, functions, tripping stages, and function blocks can be
added, copied, and deleted (see chapter 2.2 Adjustment of Application Templates/Functional Scope).

54 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.2 Adjustment of Application Templates/Functional Scope

2.2 Adjustment of Application Templates/Functional Scope


Application Template
The application template defines the preconfigured functional scope of the device for a specific use case. A
certain number of application templates is predefined for each device type. DIGSI 5 automatically offers the
application templates for selection when a new device is installed. The available application templates with
the respective functional scope are described in more detail in 4 Applications.
The selection of the application template first predefines which function groups and functions are present in
the device (see also Figure 2-1 in chapter 2.1 Function Embedding in the Device).
You can adjust the functional scope to your specific application.

Adjusting the Functional Scope


Adjust the functional scope based on the selected application template. You can add, copy or delete functions,
tripping stages, function blocks, or complete function groups.
In the DIGSI 5 project tree, this can be done via the following Editors:

• Single-line configuration

• Information routing

• Function settings
Siemens recommends the Single-line configuration Editor to adjust the functional scope.
Complete missing functionalities from the Global DIGSI 5 Library. Then, the default settings of the added func-
tionality are active. You can copy within a device and between devices as well. Settings and routings are also
copied when you copy functionalities.

NOTE

i If you delete a parameterized function group, function, or stage from the device, all settings and routings
will be lost. The function group, function, or tripping stage can be added again, but then the default
settings are active.

In most cases, the adjustment of the functional scope consists of adding and deleting functions, tripping
stages, and function blocks. As previously described, the functions, tripping stages, and function blocks auto-
matically connect themselves to the measuring points assigned to the function group.
In few cases, it may be necessary to add a protection or circuit-breaker function group. These newly added
function groups do not contain (protection) functions. You must individually load the (protection) functions
for your specific application. You must also connect the protection or circuit-breaker function group to one or
more measuring points (see chapter 2.1 Function Embedding in the Device). You must connect newly added
protection function groups to a circuit-breaker function group (see chapter 2.1 Function Embedding in the
Device).
Functions, tripping stages, function blocks, and function groups can be added up to a certain maximum
number. The maximum number can be found in the respective function and function-group descriptions.

Function Points
Function points (FP) are assigned to specific functions, but not to other functions. Further information can be
found in the description of application templates, in the chapter 4 Applications.
The device is supplied with the acquired function-point credit. Functions with function points can be loaded
into the device only within the available function-point credit. The functional scope cannot be loaded into the
device if the required number of points of the functional scope is higher than the function-point credit. You
must either delete functions or upgrade the function-point credit of the device.
No function points are required to add additional stages in functions.

Extending the Function-Point Credit


You can reorder function points if the function-point credit for the device is not enough.

SIPROTEC 5, 7SJ82/7SJ85, Manual 55


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.2 Adjustment of Application Templates/Functional Scope

Proceed as follows:

• Determine the function point requirement of certain functions, for example, with DIGSI 5 or the
SIPROTEC 5 Configurator.

• Order the additional function points from your local distributor or at http://www.energy.siemens.com.

• Siemens provides a signed license file for your device, either via e-mail or for downloading.

• Use DIGSI 5 to load the signed license file into your device. The procedure is described in the Online Help
of DIGSI 5.

56 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.3 Function Control

2.3 Function Control


Function control is used for:

• Functions that do not contain stages or function blocks

• Stages within functions

• Function blocks within functions

NOTE

i Simplifying functions and function control will be discussed in the following. The description also applies
to tripping stage control and function block control.

Functions can be switched to different operating modes. You use the parameter Mode to define whether you
want a function to run (On) or not (Off). In addition, you can temporarily block a function or switch it into test
mode for the purpose of commissioning (parameter Mode = Test).
The function shows the current status – such as an Alarm – via the Health signal.
The following explains the different operating modes and mechanisms and how you set the functions into
these modes. The function control is shown in Figure 2-8. It is standardized for all functions. Therefore, this
control is not discussed further in the individual function descriptions.

[losteurg-040411-01.tif, 1, en_US]

Figure 2-8 General Control of a Function

State Control
You can control the state of a function via the parameter Mode and the input Superordinate state.
You set the specified operating state of the function via the parameter Mode. The function mode can be set to
On, Off, and Test. The operating principle is described in Table 2-2. You can set the parameter Mode via:

• DIGSI 5

• On-site operation at the device

• Certain systems control protocols (IEC 61850, IEC 60870-5-103)


The possibility to adjust the superordinate state is limited. For test purposes, the complete device can set into
test mode.

SIPROTEC 5, 7SJ82/7SJ85, Manual 57


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.3 Function Control

The state of the function resulting from the parameter Mode and the superordinate state is shown in the
following table.

Table 2-1 Resulting State of the Function (from Linkage of Parameter Mode and Superordinate State)

Inputs State of the Function


Parameter Mode (of the function) Superordinate State
Off (any) Off
(any) Off Off
On On On
On Test Test
Test On Test
Test Test Test

The following table shows the possible function states:

Table 2-2 Possible States of a Function

Function State Explanation


On The function is activated and operating as defined. The prerequisite is that the health of the
function is OK.
Off The function is turned off. It does not create any information. The health of a disabled func-
tion always has the value OK.

58 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.3 Function Control

Function State Explanation


Test The function is set to test mode. This state supports the commissioning. All outgoing infor-
mation from the function (indications and, if present, measured values) is provided with a
test bit. This test bit significantly influences the further processing of the information,
depending on the target.
For instance, among other things, it is possible to implement the functionality Blocking of
the command relay known from SIPROTEC 4.
Target of the Informa- Processing
tion
Log The indication is labeled Test in the log.
Contact An indication routed to contact is not triggering the contact.
Light-emitting diode (LED) An indication routed to the LED triggers the LED (normal
processing)
CFC Here, the behavior depends on the state of the CFC chart.

• CFC chart itself is not in test state:


The CFC chart is not triggered by a status change of infor-
mation with a set test bit. The initial state of the informa-
tion (state before test bit was set) is not processed during
execution of the CFC chart.
• CFC chart itself is in test state:
The CFC chart continues to process the information (indica-
tion or measured value) normally. The CFC outgoing infor-
mation is provided with a test bit. The definitions in this
table apply to its continued processing.
A CFC chart can be set to the test state only by switching the
entire device to test mode.
Protocol Indication and measured value are transmitted with set test bit,
provided that the protocol supports this functionality.
If an object is transmitted as a GOOSE message, the test bit is set
spontaneously and the GOOSE message is transmitted immedi-
ately. The receiver of the GOOSE message is automatically noti-
fied of transmitter test mode.
If an object is transmitted via the protection interface, the test bit
is not transmitted. The Test state must also be transmitted as
information for this state to be taken into account in the applica-
tion on the receiver end. You must route the Test signal in the
DIGSI 5 project tree → Device → Communication routing.
The test mode of the differential protection will be dealt with
separately in the application.

Health
Health signals if a selected function can perform its designated functionality. If so, the health is OK. In case the
functionality is only possible in a limited way or not at all, due to state or problems within the device, the
health will signal Warning (limited functionality) or Alarm (no functionality).
Internal self-monitoring can cause functions to assume the health Alarm (see chapter 9 Supervision Func-
tions). If a function assumes the health state Alarm, it is no longer active (indication not active is gener-
ated).
Only a few functions can signal the health state Warning. The health state Warning results from function-
specific supervision and - where it occurs - it is explained in the function description. If a function assumes the
Warning status, it will remain active, that is, the function can continue to work in a conditional manner and
trip in the case of a protection function.

SIPROTEC 5, 7SJ82/7SJ85, Manual 59


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.3 Function Control

Not Active
The indication Not active signals that a function is currently not working. The indication Not active is
active in the following cases:

• Function is disabled

• The function is in the health state Alarm

• Function is blocked by an input signal (see Figure 2-8)

• All protection-function steps are disabled via the Enable protection controllable (state = false). The
indication Protection inactive is active.

Blocking of the Operate Indication, No Fault Recording at Pickup


With the Blk. Op. Ind. & Fault Rec. parameter, you define whether a function works as a protection
or a monitoring function. Further, you use this to determine the type and scope of the logging (see following
table)
Parameter Value Description
No The function works as a protection function. It generates an operate indica-
tion and starts fault recording with pickup. During fault recording, a fault is
created and logged as a fault record in the fault log.
Yes The function works as a supervision function. The logic runs normally, but
without creating the operate indication. The time-out indication is still
generated and can be processed further if necessary. No fault recording
starts with pickup.

60 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.4 Text Structure and Reference Number for Settings and Indications

2.4 Text Structure and Reference Number for Settings and Indications
Each parameter and each indication has a unique reference number within every SIPROTEC 5 device. The
reference number gives you a clear reference, for example, between an indication entry in the buffer of the
device and the corresponding description in the manual. You can find the reference numbers in this docu-
ment, for example, in the application and setting notes, in the logic diagrams, and in the parameter and infor-
mation lists.
In order to form unique texts and reference numbers, each function group, function, function block/stage, and
indication or parameter has a text and a number. This means that structured overall texts and numbers are
created.
The structure of the texts and reference numbers follows the already shown in Figure 2-1, hierarchy:

• Function group:Function:Stage/Function Block:Indication

• Function group:Function:Stage/Function Block:Parameter


The colon serves as a structure element to separate the hierarchy levels. Depending on the functionality, not
all hierarchy levels are always available. Function Group and Stage/Function block are optional. Since the func-
tion groups, functions as well as tripping stages/function blocks of the same type can be created multiple
times, a so-called instance number is added to these elements.

EXAMPLE
The structure of the text and reference number is shown in the protection-function group Line as an example
of the parameter Threshold value and the indication Pickup of the 2nd definite time-overcurrent protec-
tion stage of the function Overcurrent protection, phases (see Figure 2-9). Only one function and one func-
tion group exist in the device. The representation of the stage is simplified.

[lostuumz-180311-01.tif, 1, en_US]

Figure 2-9 Stage of the Overcurrent Protection Function, Phases (without Representation of Stage
Control)

The following table shows the texts and numbers of the hierarchy elements concerned:
Name Number of the Type Instance Number
Protection function group Line 2 1
Function Overcurrent 3ph 20 1
Stage Definite time-overcurrent 66 2
protection
Settings Threshold value 3 –
Indication Pickup 55 –

The instance numbers arise as follows:

• Function group: Line 1


1 instance, because only one Line function group exists in the device

• Function: Overcurrent 3ph 1


1 instance, because only one Overcurrent 3ph function exists in the Line function group

SIPROTEC 5, 7SJ82/7SJ85, Manual 61


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.4 Text Structure and Reference Number for Settings and Indications

• Stage: Definite time-overcurrent protection 2


2 instances, because 2 definite time-overcurrent protection stages exist in the Overcurrent 3ph function
(here the 2nd instance as an example)
This results in the following texts and numbers (including the instance numbers):
Parameter: Number
Line 1:Overcurrent 3-ph 1:Definite time-overcurrent 21:201:662:3
protection 2:Threshold value
Indication: Number
Line 1:Overcurrent 3-ph 1:Definite time-overcurrent 21:201:662:55
protection 2:Pickup

The structure is simplified accordingly for parameters and indications with fewer hierarchy levels.

62 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Basic Structure of the Function
2.5 Information Lists

2.5 Information Lists


For the function groups, functions, and function blocks, settings and miscellaneous signals are defined that
are shown in the settings and information lists.
The information lists summarize the signals. The data type of the information may differ. Possible data types
are ENS, ACD, ACT, SPS and MV, etc.
A type is assigned to the individual data types. The following table shows the possible types:
Type Meaning
I Input – input signal
O Output – output signal
C Controllable – control signal

EXAMPLE:
The following table shows the types for some data types as examples:
Data Type Type
ENS O
ACD O
ACT O
SPS I or O
SPC C
MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 63


C53000-G5040-C017-A, Edition 06.2019
64 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
3 System Functions

3.1 Indications 66
3.2 Measured-Value Acquisition 92
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups 94
3.4 Processing Quality Attributes 103
3.5 Fault Recording 119
3.6 Protection Communication 127
3.7 Date and Time Synchronization 164
3.8 User-Defined Objects 172
3.9 Other Functions 178
3.10 General Notes for Setting the Threshold Value of Protection Functions 189
3.11 Device Settings 198

SIPROTEC 5, 7SJ82/7SJ85, Manual 65


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

3.1 Indications

3.1.1 General

During operation, indications deliver information about operational states. These include:

• Measured data

• Power-system data

• Device supervisions

• Device functions

• Function procedures during testing and commissioning of the device


In addition, indications give an overview of important fault events after a failure in the system. All indications
are furnished with a time stamp at the time of their occurrence.
Indications are saved in logs inside the device and are available for later analyses. The following number of
indications are saved at least in the respective buffer (depending on the scope of the indications):

• Ground-fault log 100 indications

• Fault log 1000 indications

• User-defined log 200 indications

• Operational log 2000 indications

• Motor-starting log 200 indications


If the maximum capacity of the user-defined log or of the operational log is exhausted, the oldest entries
disappear before the newest entries. If the maximum capacity of the fault log or of the ground-fault log is
reached, the number of the last fault is output via the signal Fault log is full. You can route this signal in the
information routing. If indications in the information routing of DIGSI 5 are routed to a log, then they are also
saved. During a supply-voltage failure, recorded data are securely held by means of battery buffering or
storage in the flash memory. You can read and analyze the log from the device with DIGSI 5. The device
display and navigation using keys allow you to read and analyze the logs on site.
Indications can be output spontaneously via the communication interfaces of the device and through external
request via general interrogation. In DIGSI 5, indications can be tracked spontaneously during online mode in
a special indication window. Indications can be made accessible to higher-level control systems through
mapping on various communication protocols.

NOTE

i All indications are assigned to certain device functions. The text of each indication contains the corre-
sponding function designation. You will find explanations of the meaning of indications in the corre-
sponding device functions. However, you can also define indications yourself and group them into your
own function blocks. These can be set by binary inputs or CFC logic.

Reading Indications
To read the indications of your SIPROTEC 5 device you can use the on-site operation panel of the device or a PC
on which you have installed DIGSI 5. The subsequent section describes the general procedure.

3.1.2 Reading Indications on the On-Site Operation Panel

Procedure
The menus of the logs begin with a header and 2 numbers at the top right corner of the display. The number
after the slash signifies the number of indications that are available. The number before the slash indicates

66 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

how many indications have just been selected or shown. The end of the indication list is closed with the entry
***END***.

[scoprlog-090413-01.tif, 1, en_US]

Figure 3-1 On-Site Display of an Indication List (Example: Operational Indications)

Menu Path Log


Main menu → Indications → Operational log
Fault log
Ground-fault log
Setting changes
User indications 1
User indications 2
Motor-starting indications
Communication-supervision log
Main Menu → Test & Diagnosis → Log → Device diagnosis
Security indications
Communication indications

To reach the desired log from the main menu, use the navigation keys of the on-site operation panel.
² Navigate inside the log using the navigation keys (top/bottom). You will find the most current indication
at the top of the list. The selected indication is shown with a dark background.
Which indications can be shown in the selected log depends on the assignments in the DIGSI 5 information
routing matrix or is predefined. Every indication contains date, time and its state as additional information.
You will find information about this in chapter 3.1.5.1 General.
In some logs you are given the option of deleting the entire indication list by softkey in the footer of the
display. To learn more about this, read chapter 3.1.6 Saving and Deleting the Logs.

NOTE

i No password entry is necessary to read indications from the device.

SIPROTEC 5, 7SJ82/7SJ85, Manual 67


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

3.1.3 Reading Indications from the PC with DIGSI 5

Procedure

Menu Path (Project) Log


Project → Device → Process data → Log → Operational log
Setting changes
Communication-supervision log
Fault log
User indications 1
User indications 2
Motor-starting log
Ground-fault log
Online access → Device → Device information → Device-diagnosis log
Logs tab → Security indications
Online access → Device → Test suite → Communica- Communication indications
tion module →

To read the indications with DIGSI 5 your PC must be connected via the USB user interface of the on-site
operation panel or via an Ethernet interface of the device. You can establish a direct connection to your PC
via the Ethernet interfaces. It is also possible to access all connected SIPROTEC 5 devices via a data network
from your DIGSI 5 PC.
² You reach the desired logs of the SIPROTEC 5 device using the project-tree window. If you have not
created the device within a project, you can also do this via the Online access menu item.
After selecting the desired log, you are shown the last state of the log loaded from the device. To update, it is
necessary to synchronize with the log in the device.
² Synchronize the log. For this purpose, click the appropriate button in the headline of the log (see the
ground-fault indications example in Figure 3-2 a)).

[scgrflmd-191012-01, 1, en_US]

Figure 3-2 DIGSI 5 Display of an Indication List (Example of Ground-Fault Log)

You will find additional information about deleting and saving logs in chapter 3.1.6 Saving and Deleting the
Logs.

68 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Which indications can be shown in the selected log depends on the assignments in the DIGSI 5 information
routing matrix or is predefined. You will find information about this in chapter 3.1.5.1 General.

Setting Relative Time Reference


² Reference the display of log entries, if needed, to the real time of a specific entry. In this way, you deter-
mine a relative time for all other indications. The real-time stamps of events remain unaffected.

3.1.4 Displaying Indications

Displayed indications are supplemented in DIGSI 5 and on the on-site operation panel with the following infor-
mation:

Table 3-1 Overview of Additional Information

Indications in DIGSI 5 Information Device Display Information


Log for operational indications and Time stamp (date and time), Time stamp (date and time),
log for user-defined indications Relative time, Function structure,
Entry number, Name,
Function structure, Value
Name,
Value,
Quality,
Cause,
Number
Log for fault indications Time stamp (date and time), Time stamp (date and time),
Relative time, Fault number,
Fault number, Value
Entry number,
Function structure,
Name,
Value,
Quality,
Cause,
Number
Log for motor-starting indications Time stamp (date and time), Time stamp (date and time),
Motor-starting time, Function structure,
Starting current, Name,
Starting voltage, Value
Starting duration
Log for ground-fault indications Time stamp (date and time), Time stamp (date and time),
Relative time, Fault number,
Fault number, Value
Entry number,
Function structure,
Name,
Value,
Indication number,
Quality,
Cause,
Number

SIPROTEC 5, 7SJ82/7SJ85, Manual 69


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Indications in DIGSI 5 Information Device Display Information


Log for parameter changes Time stamp (date and time), Time stamp (date and time),
Relative time, Function structure,
Entry number, Name,
Function structure, Value
Name,
Value,
Quality,
Cause,
Number
Spontaneous indication window Time stamp (date and time), Time stamp (date and time),
(DIGSI 5) Relative time, Fault number,
Indication, Value
Value,
Quality,
Additional Information
Log for safety indications1 Time stamp (date and time), Time stamp (date and time),
Indication number, Indication
Indication
Log for device-diagnostic indica- Time stamp (date and time), Time stamp (date and time),
tions1 Indication number, Indication
Indication
Log for communication indications1 Time stamp (date and time), Time stamp (date and time),
Indication number, Indication
Indication
Log for communication supervision Time stamp (date and time), Time stamp (date and time),
(GOOSE) Relative time, Function structure,
Entry number, Name,
Function structure, Value
Name,
Value,
Quality,
Cause,
Number

Overview of Displayed Quality Attributes


If values are shown on the device display or in DIGSI, the following quality attributes are different for meas-
ured values and metered values.

Table 3-2 Measured Values

IEC 61850 Device Display/ Description


Detail Quality Validity DIGSI
Good Invalid Questionable
– X Value The measured value is valid.
Failure X Fault The device is defective. Contact
Support.

1 Only online access

70 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

IEC 61850 Device Display/ Description


Detail Quality Validity DIGSI
Good Invalid Questionable
Inaccurate X --- The measured value was not
calculated (for example, the
angle between current and
voltage if 1 of the 2 variables is
missing).
Bad Reference X ≈ Value The measured value can be inac-
curate (for example, outside the
frequency-tracking range).
Out of Range X > Value The measured value exceeds the
measuring range.

Table 3-3 Metered Values

IEC 61850 Device Display/ Description


Validity DIGSI
Good Invalid Questionable
X Value The metered value is invalid.
X --- The metered value was not calcu-
lated.
X ≈ Value The metered value has no refer-
ence.

Indication Columns
The following table shows the meaning of the individual columns in the log:
Indication Column Meaning
Time stamp Time stamp of the indication in device time using the local time
zone of the device or the query time for the motor log
Relative time Relative time to a reference entry
Error number Number of the error that occurred in the device. This number incre-
ments continuously.
Entry number Entry identification of buffer entries. This identification displays the
sequence of buffer entries.
Indication number Number of the indication that occurred in the device. This number
increments continuously and is necessary for an analysis by
Siemens.
Indication Indication text
Function structure Path of the signal with the signal name
Name Signal name
Value Current state of the command. Also pay attention to the value
quality to check whether the value is up to date.
Quality The quality of the value shows the source of the value and whether
the value is up to date.
Cause Additional information such as the cause and validity
Number DIGSI address of the signal
Motor startup time Time of motor starting
Starting current Current needed by the motor to start up
Starting voltage Voltage needed by the motor to start up
Start duration Time needed by the motor to start up

SIPROTEC 5, 7SJ82/7SJ85, Manual 71


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

3.1.5 Logs

3.1.5.1 General
Indications are saved in logs inside the device and are available for later analyses. Different logs allow catego-
rization of indication logging based on operating states (for example, operational and fault logs) and based on
fields of application.

Table 3-4 Log Overview

Log Logging
Operational log Operational indications
Fault log Fault indications
Ground-fault log Ground-fault indications
Setting-history log Setting changes
User-defined log User-defined indication scope
Security log Access with safety relevance
Device-diagnosis log Error of the device (software, hardware) and the connection circuits
Communication log Status of communication interfaces
Motor-startup log Information on the motor startup
Communication-supervision log Communication supervision (GOOSE)

Log Management
Logs have a ring structure and are automatically managed. If the maximum capacity of a log is exhausted, the
oldest entries disappear before the newest entries. If the maximum capacity of the fault or ground-fault log is
reached, the number of the last fault is generated via the signal Fault log is full. You can route this signal in
the information routing. If indications in the information routing of DIGSI 5 are routed to a log, then they are
also saved. During a supply-voltage failure, recorded data are securely held by means of battery buffering or
storage in the flash memory. You can read and analyze the log from the device with DIGSI 5. The device
display and the navigation allow you to read and evaluate the logs on site using keys.

Configurability of Logs
The indication capacity to be recorded in configurable logs (for example, ground-fault log) is laid down in
columns of the information routing (matrix) of DIGSI 5 specifically defined for this purpose.

Procedure
To reach the information routing of your SIPROTEC 5 device, use the project-tree window. Access is only
through the project:

• Open the information routing.


Project → Device → Information routing

• Select the appropriate routing column.


Destination → Logs → Column Ground-fault log (G)
The routing of the selected indication is done via right click.

• Select one of the options in the list box shown:


– Routed (X)
– Unrouted

72 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

[scinfpuf-191012-01, 2, en_US]

Figure 3-3 Indication Configuration in DIGSI 5 (Example: Ground-Fault Log, Column G)

For non-configurable logs (for example, setting-history logs) scope and type of logged indications are
described separately (see following chapter about logs).

3.1.5.2 Operational Log


Operational indications are information that the device generates during operation. This includes information
about:

• State of device functions

• Measured data

• Power-system data
Exceeding or dropping below limiting values is output as an operational indication. Short circuits in the
network are indicated as an operational indication Fault with sequential fault number. For detailed informa-
tion about the recording of system incidents, please refer to the description of the fault log (chapter
3.1.5.3 Fault Log). Up to 2000 indications can be stored in the log.

Reading from the PC with DIGSI 5

• To reach the operational log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process Data → Log → Operational log

• The status of the operational log last loaded from the device is shown to you. To update (synchronization
with the device), click the button Read log entries in the headline of the indication list (Figure 3-4 a)).

SIPROTEC 5, 7SJ82/7SJ85, Manual 73


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

[scbetrmd-030211-01, 1, en_US]

Figure 3-4 Reading the Operational Log with DIGSI 5

Reading on the Device via the On-Site Operation Panel

• To reach the operational log via the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → Operational log

• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.

• Using the Info softkey, you can retrieve auxiliary information on the entry depending on the context.

74 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

[scoperlog1-081217-01, 1, en_US]

Figure 3-5 On-Site Display of an Indication List (Example: Operational Indications)

Deletability
The operational log of your SIPROTEC 5 device can be deleted. This is done usually after testing or commis-
sioning the device. To know more about this, read chapter 3.1.6 Saving and Deleting the Logs.

Configurability
The indication scope of the operational log is configured in a specifically defined column of the information
routing (matrix) of DIGSI 5:
Target → Log → Operational log column
Selected application templates and functions from the library bring with them a predefined set of operational
indications which you can adjust individually at any time.

3.1.5.3 Fault Log


Fault indications are events which arise during a fault. They are logged in the fault log with real-time stamp
and relative-time stamp (reference point: fault occurrence) . Faults are numbered consecutively in rising order.
With fault recording engaged, a corresponding fault record with the same number exists for every fault logged
in the fault log. A maximum of 128 fault logs can be stored. A maximum of 1000 indications can be recorded
in each fault log.

Fault Definition
In general, a fault is started by the raising pickup of a protection function and ends with the cleared pickup
after the trip command.
When using an automatic reclosing function, the complete reclosing cycle (successful or unsuccessful) is pref-
erably integrated into the fault. If evolving faults appear within reclosing cycles, the entire clearing process is
logged under one fault number even in multiple pickup cycles. Without automatic reclosing function every
pickup is also recorded as its own fault.
User-defined configuration of a fault is also possible.

NOTE

i The definition of the fault is done through settings of the fault recording (see Device manual). Events are
logged in the fault log even when fault recording is switched off.

SIPROTEC 5, 7SJ82/7SJ85, Manual 75


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Apart from the recording of fault indications in the fault log, spontaneous display of fault indications of the
last fault on the device display is also done. You will find details about this in chapter 3.1.8 Spontaneous Fault
Display on the On-Site Operation Panel.

Deletability
The fault log of your SIPROTEC 5 device can be deleted. You will find details about this in chapter 3.1.6 Saving
and Deleting the Logs.

Reading on the Device through the On-Site Operation Panel

• To reach the fault log from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → Fault logs

• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.

[scfaullg-090413-01.tif, 1, en_US]

Figure 3-6 Reading the Fault Log on the On-Site Operation Panel of the Device

Configurability
The indication scope of the fault log is configured in a specifically defined column of the information routing
(matrix) of DIGSI 5:
Target → Log → Fault log column
Selected application templates and functions from the library already bring a predefined set of operational
indications with them which you can adjust individually at any time.
The operational measured values and the measured values of the fundamental components and symmetrical
components (see Device Manual) are calculated every 9 cycles (at 50 Hz, this is every 180 ms). However, this
can mean that the data are not synchronized with the sampled values of the analog channels. The recording
of these measured values can be used to analyze the slowly changing processes.

3.1.5.4 Ground-Fault Log


Ground-fault indications are events which arise during a ground fault. They are logged in the ground-fault log
with real-time stamp and relative-time stamp (reference point: ground-fault occurrence) . Ground faults are
numbered consecutively in rising order. A maximum of 10 ground-fault logs are stored, and for each ground-
fault log it is guaranteed that at least 100 indications are recorded.
The following functions can start the logging of a ground fault with the raising ground-fault indication:

• Directional sensitive ground-fault protection for deleted and isolated systems (67Ns)

• Sensitive ground current protection with I0 (50Ns/51Ns)

• Intermittent ground-fault protection


The logging ends with the clearing ground-fault indication.

76 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Reading from the PC with DIGSI 5

• To reach the ground-fault log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Logs → Ground-fault log
The status of the device-diagnosis log last loaded from the ground-fault log is shown to you.

• To update (synchronization with the device) click the button Read log entries in the headline of the indi-
cation list (Figure 3-7 a)).

[scgrflmd-191012-01, 1, en_US]

Figure 3-7 Reading the Ground-Fault Log with DIGSI 5

Reading on the Device through the On-Site Operation Panel

• To reach the ground-fault log from the main menu, use the navigation keys of the on-site operation
panel.
Main menu → Indications → Ground-fault indication

• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.

[scgfllg1-191012-01.tif, 1, en_US]

Figure 3-8 Reading the Ground-Fault Log on the On-Site Operation Panel of the Device

SIPROTEC 5, 7SJ82/7SJ85, Manual 77


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Deletability
The ground-fault log of your SIPROTEC 5 device can be deleted. Read details about this in chapter 3.1.6 Saving
and Deleting the Logs.

Configurability
The indication scope of the ground-fault log is configured in a specifically defined column of the information
routing (matrix) of DIGSI 5:
Target → Log → Column Ground-fault log
Selected application templates and functions from the library already bring a predefined set of operational
indications with them which you can adjust individually at any time.

3.1.5.5 User Log


With the user-defined log (up to 2), you have the possibility of individual indication logging parallel to the
operational log. This is helpful, for example, in special monitoring tasks but also in the classification into
different areas of responsibility of the logs. Up to 200 indications can be stored in the user-defined log.

Reading from the PC with DIGSI 5

• To reach the user-defined log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process Data → Log → User log 1/2
The status of the user-defined log last loaded from the device is shown to you.

• To update (synchronization with the device) click the button Read log entries in the headline of the indi-
cation list (Figure 3-9 a)).

[scanwnmd-030211-01, 2, en_US]

Figure 3-9 Reading the User-Defined Log with DIGSI 5

Reading on the Device through the On-Site Operation Panel

• To reach user-specific logs from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → User-defined log 1/2

• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.

• Using the Info softkey, you can retrieve auxiliary information on the entry depending on the context.

78 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

[scuserrlog1-081217-01, 1, en_US]

Figure 3-10 Reading the User-Defined Log on the On-Site Operation Panel of the Device

Deletability
The user-defined log of your SIPROTEC 5 device can be deleted. You will find details about this in chapter
3.1.6 Saving and Deleting the Logs.

Configuration of a User-Defined Log


The indication capacity of a created user-defined log can be configured freely in the associated column of the
information routing (matrix) of DIGSI 5:
Target → Log → U1 or U2

[scdiu1u2-280415-01, 1, en_US]

Figure 3-11 Indication Configuration in DIGSI 5 (Example: User-Defined Log U1/2)

SIPROTEC 5, 7SJ82/7SJ85, Manual 79


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

3.1.5.6 Setting-History Log


All individual setting changes and the downloaded files of entire parameter sets are recorded in the log for
setting changes. This enables you to determine setting changes made are associated with events logged (for
example faults). On the other hand, it is possible to obtain verification with fault analyses, for example, that
the current status of all settings truly corresponds to their status at the time of the fault. Up to 200 indications
can be stored in the setting-history log.

Reading from the PC with DIGSI 5

• To reach the log for setting changes of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Log → Setting changes
The status of the setting-history log last loaded from the device is shown to you.

• To update (synchronization with the device), click the Read log entries button in the headline of the
indication list (Figure 3-12).

[scparamd-030211-01, 1, en_US]

Figure 3-12 Reading the Setting-History Log with DIGSI 5

Reading on the Device through the On-Site Operation Panel

• To reach the setting-history log from the main menu, use the navigation keys of the on-site operation
panel.
Main menu → Indications → Setting changes

• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.

[schislog-090413-01.tif, 1, en_US]

Figure 3-13 Reading the Setting-History Log on the On-Site Operation Panel of the Device

80 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Indication Categories in the Setting-History Log


For this log, there is selected information that is stored in case of successful as well as unsuccessful setting
changes. The following list gives you an overview of this information.

Table 3-5 Overview of Indication Types

Displayed Information Explanation


Selection edit+ Selection of settings group to be edited
Cancelation+ Cancelling of all changes successful
SG activation+ SG activation via command successful
SG activation- SG activation via command failed
Set+ Parameter value was changed
Confirmation+ Confirmation of change successful
Confirmation- Confirmation of change failed
DCF uploaded DCF loaded into device
SG 1 Settings group 1
SG 2 Settings group 2
SG 3 Settings group 3
SG 4 Settings group 4
SG 5 Settings group 5
SG 6 Settings group 6
SG 7 Settings group 7
SG 8 Settings group 8

NOTE

i • The logged indications are preconfigured and cannot be changed!

• The log, which is organized as a ring buffer, cannot be deleted by the user!

• If you want to archive security-relevant information of the device without loss of information, you
must regularly read this log.

• You cannot route additional indication objects to the setting-history log.

3.1.5.7 Communication Log


The logging of the respective status such as ensuing faults, test and diagnosis operation, and communication
capacity utilizations is done for all hardware-based configured communication interfaces. Up to 500 indica-
tions can be stored in the communication log. Logging occurs separately for each communication port of the
configured communication modules.

Reading from the PC with DIGSI 5

• Use the project-tree window to reach the communication logs of your SIPROTEC 5 device.
Online access → Device → Test suite → Communication module

• Then select:
J:Onboard Ethernet → Communication log
The communication log is shown to you in the state last loaded from the device.

• Before this, refresh the contents by clicking the update arrows in the headline.

SIPROTEC 5, 7SJ82/7SJ85, Manual 81


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

[sccompuf-140912-01, 2, en_US]

Figure 3-14 Reading the Communication Log with DIGSI 5

Reading on the Device through the On-Site Operation Panel

• To reach the communication log from the main menu, use the navigation keys on the on-site operation
panel.
Main Menu → Test & Diagnosis → Logs → Communication logs

• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.

[sccommlg-270618, 1, en_US]

Figure 3-15 Reading the Communication Log on the On-Site Operation Panel of the Device

Deletability
The communication logs of your SIPROTEC 5 device can be deleted. Read details about this in chapter
3.1.6 Saving and Deleting the Logs.

82 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Configurability
The communication logs are not freely configurable. The entries are preconfigured.

3.1.5.8 Communication-Supervision Log


The communication-supervision log is used to log communication events.
The following events are currently logged:

• Status for each GOOSE subscription (if configured)


A log is kept of whether the GOOSE subscription has received valid messages or not.

• Aggregated status for all GOOSE subscriptions


The status is TRUE if at least one GOOSE subscription does not receive any valid message.

• Subscriber in simulation mode


GOOSE messages are processed with a simulation flag. The status is TRUE if at least one GOOSE subscrip-
tion processes simulated messages.

Reading from the PC with DIGSI 5

• To reach the communication-supervision log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Logs → Com supervision log
The status of the communication-supervision log last loaded from the device is shown.

• To update (synchronization with the device), click the button Read log entries in the headline of the
indication list.

[sc_comsuperv, 1, en_US]

Figure 3-16 Reading the Communication-Supervision Log with DIGSI 5

Reading on the Device through the On-Site Operation Panel

• To reach the communication-supervision log from the main menu, use the navigation keys on the on-site
operation panel.
Main menu → Logs → Com supervision log

• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.

SIPROTEC 5, 7SJ82/7SJ85, Manual 83


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

[sc_comsupervlg, 1, en_US]

Figure 3-17 Reading the Communication-Supervision Log on the On-Site Operation Panel of the Device

Deletability
The communication-supervision log of your SIPROTEC 5 device can be deleted. Read details about this in
chapter 3.1.6 Saving and Deleting the Logs.

Configurability
The communication-supervision log cannot be freely configured. The entries are preconfigured.

3.1.5.9 Security Log


Access to areas of the device with restricted access rights is recorded in the security log. Unsuccessful and
unauthorized access attempts are also recorded. Up to 2048 indications can be stored in the security log.

Reading from the PC with DIGSI 5

• To reach the security log of your SIPROTEC 5 device, use the project-tree window. The device must be in
Online access.
Project → Online access → Device → Device Information → Logs tab → Security logs
The state of the security log last loaded from the device is displayed.

• Before this, refresh the contents by clicking the update arrows in the headline.

[scsecmld-180816-01, 2, en_US]

Figure 3-18 Reading the Security Indications with DIGSI 5

84 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Reading on the Device through the On-Site Operation Panel

• To reach the security log from the main menu, use the navigation keys of the on-site operation panel.
Main menu → Test & Diagnosis → Logs → Security log

• You can navigate on the on-site operation panel using the navigation keys (top/bottom) inside the
displayed indication list.

[scseclog-280618, 1, en_US]

Figure 3-19 Reading the Security Log on the On-Site Operation Panel of the Device

NOTE

i • The logged indications are preconfigured and cannot be changed!

• This log, which is organized as a ring buffer, cannot be deleted by the user!

• If you want to archive security-relevant information of the device without loss of information, you
must regularly read this log.

3.1.5.10 Device-Diagnosis Log


Concrete take-action instructions are logged and displayed in the device-diagnosis log for the following items:

• Required maintenance (for example, battery supervision)

• Identified hardware defects

• Compatibility problems
Up to 500 indications can be stored in the device-diagnosis log. In normal operation of the device, it is suffi-
cient for diagnostic purposes to follow the entries of the operational log. This specific significance is assumed
by the device-diagnosis log when the device is no longer ready for operation due to hardware defect or
compatibility problems and the fallback system is active.

Reading from the PC with DIGSI 5 in Normal Operation

• To reach the device-diagnosis log of your SIPROTEC 5 device, use the project-tree window.
Project → Online access → Device → Device information → Logs tab → Device-diagnosis log
The status of the device-diagnosis log last loaded from the device is shown to you.

• Before this, refresh the contents by clicking the update arrows in the headline.

SIPROTEC 5, 7SJ82/7SJ85, Manual 85


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

[scdevdia-180816-01, 1, en_US]

Figure 3-20 Reading the Device-Diagnosis Log with DIGSI 5

Reading on the Device through the On-Site Operation Panel in Normal Operation

• To reach the diagnosis log from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Test & Diagnosis → Logs → Device diagnosis

• You can navigate on the on-site operation panel using the navigation keys (top/bottom) inside the
displayed indication list.

[scdevdia-280618, 1, en_US]

Figure 3-21 Reading the Device-Diagnosis Log on the On-Site Operation Panel of the Device

NOTE

i • The device-diagnosis log cannot be deleted!

• The logged indications are preconfigured and cannot be changed!

3.1.6 Saving and Deleting the Logs

Deleting the logs of the device in the operating state is unnecessary. If storage capacity is no longer sufficient
for new indications, the oldest indications are automatically overwritten with new incoming events. In order
for the memory to contain information about the new faults in the future, for example, after a revision of the
system, a deletion of the log makes sense. Resetting the logs is done separately for the various logs.

NOTE

i Before you delete the content of a log on your SIPROTEC 5 device, save the log with DIGSI 5 on the hard
disk drive of your PC.

86 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

NOTE

i Not all logs of your SIPROTEC 5 device can be deleted. These limitations apply especially to logs with rele-
vance for security and after-sales (security log, device-diagnosis log, setting-history log).

NOTE

i Upon deletion of the fault log, the associated fault records are also deleted. In addition, the meters for fault
number and fault-record number are reset to 0. In contrast, if you delete fault records, the content of the
fault log, including the allocated fault numbers, remains.

NOTE

i If the device executes an initial start, for example after an update of the device software, the following logs
are automatically deleted:

• Operational log

• Fault log

• Ground-fault log

• Setting-history log

• User-defined log

• Motor-starting log

• Communication-supervision log
Back up the deletable logs using DIGSI 5.

NOTE

i If a ground fault is currently active, the ground-fault log cannot be deleted.

Deleting Logs on the On-Site Operation Panel

• To reach the selected log from the main menu, use the navigation keys of the on-site operation panel
(example operational log):
Main menu → Logs → Operational log

[scoprlog-090413-01.tif, 1, en_US]

Figure 3-22 Deleting the Operational Log on the On-Site Operation Panel

SIPROTEC 5, 7SJ82/7SJ85, Manual 87


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.

• The option to delete the entire log is offered to you in the footer of the display at the bottom left. Use the
softkeys below under the display to activate the command prompts. Confirm the request to Delete.

• After being requested, enter the password and confirm with Enter.

• After being requested, confirm the Deletion of all entries with Ok.

Deleting Logs from the PC with DIGSI 5

• To reach the selected log of your SIPROTEC 5 device, use the project-tree window (for example opera-
tional log).
Project → Device → Process data → Logs → Operational log

3.1.7 Spontaneous Indication Display in DIGSI 5

With DIGSI 5 you have the possibility of displaying all currently transmitted indications of the selected device
in a special indication window.

Procedure

• Call up the spontaneous indications of your selected device in the navigation window under Online
access.

• Click Indications in the path:


Online access → Interface → Device → Indications

• The raising indications appear immediately without you having to wait for a cyclical update or initiate the
manual update.

[scspnmld-230211-01, 2, en_US]

Figure 3-23 Displaying Spontaneous Device Indications in DIGSI 5

3.1.8 Spontaneous Fault Display on the On-Site Operation Panel

After a fault, the most important data of the last fault can be displayed automatically on the device display
without further operational measures. In SIPROTEC 5 devices, protected objects and even circuit breakers can
be freely created and configured depending on the application (even several instances). In DIGSI 5, several
spontaneous fault displays can be configured, depending on the application, with each individual one being
assigned a particular circuit breaker. These displays remain stored in the device until they are manually
confirmed or released by LED reset.

88 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Configuration of a Spontaneous Fault Display with DIGSI 5

• To reach the Fault-display configuration of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Display pages → Fault-display configuration

• In the main window, all configured circuit breakers are displayed. A list of a maximum of 6 configurable
display lines is offered for each circuit breaker. The activation of a spontaneous fault display occurs for
each circuit breaker by selection via checkmark in the column Display.

• With the parameter (_:139) Fault-display (under Device → Parameter → Device settings) you
determine whether spontaneous fault displays should be shown for each pickup or only pickups with the
trip command.

[sckonstf-230211-01, 2, en_US]

Figure 3-24 Configuration of the Spontaneous Fault Display on the Device

For every display line the following display options can be selected:

Table 3-6 Overview of Display Options

Displayed Information Explanation


Pickup indication Display of the first function stage picked up in a fault, as needed with auxiliary
information (phases, ground, direction)
PU time Display of the entire pickup duration of the fault
Operate indication Display of the first function stage triggered in a fault, as needed with auxiliary
information (phases)
Trip time Display of the operate time related to the beginning of the fault (pickup start)
Fault distance Display of the measured fault-location distance
Operate result indication Display of the control or switching device triggered in a fault, with auxiliary
information (phases) where necessary

Acknowledgment of the Spontaneous Fault Display on the Device


After faults, the last occurred fault is always displayed to you. In cases where more than one circuit breaker is
configured, several stored fault displays can be present after faults, with the latest being displayed. These
displays remain stored in the device until manual acknowledgment or release by LED reset.

SIPROTEC 5, 7SJ82/7SJ85, Manual 89


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

[scstfanz-090413-01.tif, 1, en_US]

Figure 3-25 Spontaneous Fault Display on the Device

Method 1: Manual acknowledgment

• Press the softkey button Quit in the base bar of the display. The display is irretrievably closed. Repeat this
step until no further spontaneous fault displays appear.

• After completion of all confirmations the last display view is showed before the faults.
Method 2: Acknowledgment via LED reset

• An LED reset (device) causes the reset of all stored LEDs and binary output contacts of the device and also
to the confirmation of all fault displays stored in the display.
You can find more details on the topic of LED reset in chapter 3.1.9 Stored Indications in the SIPROTEC 5
Device

3.1.9 Stored Indications in the SIPROTEC 5 Device

In your SIPROTEC 5 device, you can also configure indications as stored. This type of configuration can be
used for LEDs as well as for output contacts. The configured output (LED or contact) is activated until it is
acknowledged. Acknowledgment occurs via:

• On-site operation panel

• DIGSI 5

• Binary input

• Protocol of substation automation technology

Configuration of Stored Indications with DIGSI 5


In the Information Routing of each device set up in DIGSI 5, you can route binary signals, among others, to
LEDs and output contacts.

• To do this, proceed in the project tree to:


Project → Device → Information routing

• Right-click the routing field of your binary indication in the desired LED or binary output column in the
routing range of the targets.
You are offered the following options:

90 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.1 Indications

Table 3-7 Overview of Routing Options

Routing Options LEDs BOs BIs Description


H (active) X The signal is routed as active with voltage.
L (active) X The signal is routed as active without voltage.
V (unlatched) X X The signal is routed as unlatched. Activation and reset of
the output (LED, BA) occurs automatically via the binary-
signal value.
G (latched) X X The binary signal is latched when the output (LED) is acti-
vated. To reset, a targeted confirmation must occur.
NT (conditioned latching) X Fault indications are stored during control of the output
(LED) as a function of the parameter (_:91:139)
Fault-display. In the event of a new fault, the previ-
ously stored states are reset.

• If the fault gets terminated via a trip command from


the assigned circuit breaker, the status of an indication
remains as latched with the setting option with
trip. Without a trip command, the status is displayed
before the fault (if necessary, the status of the last
fault) is restored.
• With the setting option with pickup the current
indication image of a pickup gets stored. The image
comprises all indications of functions that are effective
in the event of tripping on the same circuit breaker,
like the picked up function.
TL (stored only with tripping) X Routing option TL (tripping stored) is only possible for the
switching object circuit breaker.
The output is saved with protection tripping. The contact
remains activated until acknowledged.
Control commands are not affected. A control command is
pending above the parameterized command period until
feedback has been successfully received.
Note:
You can realize the functionality of the Lockout (ANSI 86)
by storing the output relay with the routing option TL.

3.1.10 Resetting Stored Indications of the Function Group

You can configure indications of individual functions as "stored" in a function group. This type of configuration
can be used for LEDs as well as for output contacts. The configured output (LED or contact) is activated until it
is acknowledged.
The protection and the circuit-breaker function groups contain the block Reset LED FG. The block
Reset LED FG is visible only in the Information routing under the corresponding function group in DIGSI 5.
You use the binary input signal >Reset LED to reset the stored LEDs in the respective function group. The
configured outputs (contacts) are not reset.

3.1.11 Test Mode and Influence of Indications on Substation Automation Technology

If the test mode of the device or of individual functions is switched on, the SIPROTEC 5 device marks indica-
tions sent to substation automation technology station control system with an additional test bit. This test bit
makes it possible to determine that an indication was set during a test. Necessary reactions in normal opera-
tion on the basis of an indication can thus be suppressed.

SIPROTEC 5, 7SJ82/7SJ85, Manual 91


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.2 Measured-Value Acquisition

3.2 Measured-Value Acquisition


Basic Principle
SIPROTEC 5 devices are equipped with a powerful measured-value acquisition function. In addition to a high
sampling frequency, they have a high measurand resolution. This ensures a high degree of measuring accu-
racy across a wide dynamic range. The 24-bit sigma/delta analog-digital converter represents the core of
measured-value acquisition. In addition, the oversampling function supports the high measurand resolution.
Depending on the requirements of the individual method of measurement, the sampling frequency is reduced
(Downsampling).
In digital systems, deviations from the rated frequency lead to additional errors. In order to avoid this, 2 algo-
rithm-dependent processes are used in all SIPROTEC 5 devices:

• Sampling-frequency tracking:
The analog input channels are scanned for valid signals in cycles. The current power frequency is deter-
mined and the required sampling frequency is defined by using a resampling algorithm. The tracking is
effective in the frequency range between 10 Hz and 90 Hz.

• Fixed sampling frequency – correction of the filter coefficients:


This method operates in a limited frequency range (frated +/- 5 Hz). The power frequency is determined
and, depending on the degree of the frequency deviation, the filter coefficients are corrected.

The following figure shows the basics of dealing with sampled values (SAV) in the measured-value acquisition
chain. Figure 3-26 shows to whom the various sampling frequencies are made available. In order to limit the
bandwidth of the input signals, a low-pass filter (anti-aliasing filter to maintain the sampling theorem) is
installed downstream. After sampling, the current input channels are adjusted. This means the magnitude,
phase, as well as the transformer time constant are corrected. The compensation is designed to ensure that
the current transformer terminal blocks can be exchanged randomly between the devices.

[dwmeserf-250211-01.tif, 1, en_US]

Figure 3-26 Measured-Value Acquisition Chain

The internal sampling frequency of the SIPROTEC 5 devices is fixed at 16 kHz (sampling rate: 320 samplings
per 50-Hz cycle). All current and voltage inputs are sampled. If the magnitude, phase, and transformer time
constant are corrected, the sampling frequency is reduced to 8 kHz (160 samplings per 50-Hz cycle). This is
the basic sampling frequency to which various processes, such as fault recording, RMS measured values, refer.
For the RMS measurement, the measured-value window is adjusted on the basis of the power frequency. For
numerous measurement and protection applications , 20 samplings per cycle are sufficient (if frated = 50 Hz:
sampling every 1 ms, at frated = 60 Hz: sampling every 0.833 ms). This sampling rate is an adequate compro-
mise between accuracy and the parallel processing of the functions (multi-functionality).

92 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.2 Measured-Value Acquisition

The 20 samplings per cycle will be made available to the algorithms processed in the function groups, in
2 variants:

• Fixed (not resampled)

• Resampled (frequency range from 10 Hz to 90 Hz)


Depending on the algorithms (see function descriptions), the respective data flow is considered. A higher
sampling frequency is used for selected methods of measurement. Detailed information can be found in the
corresponding function description.

NOTE

i The measuring points for current and voltage are in the Power-system data (starting in chapter 6.1 Power-
System Data). Each measuring point has its own parameters.

SIPROTEC 5, 7SJ82/7SJ85, Manual 93


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

3.3.1 Overview

Starting from platform version V07.80, you can merge measuring points into Frequency tracking groups in
SIPROTEC 5 devices. The device operates with a maximum of 6 Frequency tracking groups..
The chapter 3.3.2 Sampling-Frequency Tracking provides the necessary hints on the operating principle of
sampling-frequency tracking and its application.
The chapter 3.3.3 Frequency Tracking Groups describes the principle and application of frequency tracking
groups.

3.3.2 Sampling-Frequency Tracking

SIPROTEC 5 devices are equipped with powerful sampling-frequency tracking as explained in the chapter
3.2 Measured-Value Acquisition. This ensures high measuring accuracy over a wide frequency operating range
(10 Hz to 90 Hz).
To determine the actual sampling frequency, the voltage and current measuring points are checked for valid
input signals, the actual power frequency is determined and the tracking frequency (sampling
frequency = 20 ⋅ tracking frequency) is adapted. The method is implemented in such a way that the number of
samplings per actual power frequency or the frequency of the system is always constant. The number of
samplings is 20 per cycle, as per chapter 3.2 Measured-Value Acquisition.
During engineering, you set the parameters specifying which measuring points are used for frequency
tracking. All 3-phase voltage and current measuring points and 1-phase voltage and current measuring points
are allowed.

NOTE

i The 1-phase measuring points, however, should only be used in exceptional cases.
Measuring points that measure zero-sequence voltages or zero-sequence currents must not be used for
frequency tracking.

The following figure shows where you set the parameters for the corresponding measuring point and activate
sampling-frequency tracking in the DIGSI 5 project tree under Settings → Power-system data.

[sc_MP_Powersys trackfreq, 1, en_US]

Figure 3-27 Using the Measuring Point to Determine the Sampling Frequency

94 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

If the parameter Tracking = active, the measuring point is used to determine the actual tracking
frequency. If the parameter Tracking is set to active for several measuring points, the ID of the measuring
point determines the sequence in which these are checked for valid input signals. The algorithm starts with
the lowest ID number, as follows:

• First, the 3-phase measuring points are scanned. If no valid voltage is found, the selected current meas-
uring points are next. In this case, the following sequence applies:
3-phase voltage measuring point → 3-phase current measuring point → 1-phase voltage measuring point
→ 1-phase current measuring point
If a trigger signal comes from a current measuring point, the voltage measuring points are still continu-
ously scanned for valid voltages and switched immediately if a voltage is found.

• If the true RMS value is greater than 2.5 % of the set secondary device rated value, a measuring point is
valid. For example, this is 2.5 V at 100 V, 25 mA at 1 A or 125 mA at 5 A.

• A 3-phase measuring point is scanned in the sequence of phase A → phase B → phase C.


In the case of the voltage measuring points, the phase-to-phase voltage VAB, VBC, and VCA is always used
for evaluation. The phase-to-phase voltage is calculated in the event of a phase-to-ground connection.

• The tracking frequency is tracked using different interval steps. If the tracking frequency deviates only
slightly from the measured frequency, the frequency is tracked using small steps of 0.010 Hz. In the case
of greater deviations, the interval is 1 Hz. To react faster in the event of larger deviations, for example in
switchover conditions, tracking occurs in 5-Hz steps. When switching on measurands immediately the
measured tracking frequency is used.

• If no tracking frequency can be determined, the appropriate rated frequency of the electrical power
system is used as the tracking frequency. This case occurs before the measurands are switched on, after
they are switched off or when the device is powered on. If the measurands are switched on, the starting
frequency is the set power frequency, for example 50 Hz or 60 Hz. Since rated-frequency input variables
can be assumed for most applications, the measuring algorithms start with the fixed sampling frequency,
for example, 1 kHz for 50 Hz and 1.2 kHz for 60 Hz.
Figure 3-28 shows the behavior of sampling-frequency tracking across the frequency band and at the
frequency limits.
The x-axis shows the actual power frequency (fsys) and the y-axis shows the set tracking frequency (ftrack).
Between 10 Hz and 90 Hz, the relationship is linear. If the actual power frequency is less than 10 Hz, the
tracking frequency is kept at 10 Hz. In this case, sampling occurs at 20 ⋅ 10 Hz = 200 Hz. If the power
frequency is greater than 90 Hz, the tracking frequency is kept constant at 90 Hz.
If the frequency is outside the frequency operating range (10 Hz to 90 Hz), frequency tracking generates the
indication Freq. out of range. The individual protection functions evaluate this indication. If an over-
function can occur, the protection functions are blocked internally to avoid a failure.
You can find more detailed information on the behavior of the protection functions in the chapter 12 Tech-
nical Data.

[dw_working-area_sampling-frequency-tracking, 2, en_US]

Figure 3-28 Operating Range of Sampling-Frequency Tracking

SIPROTEC 5, 7SJ82/7SJ85, Manual 95


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

Siemens recommends routing the calculated power frequency (fsys) and the determined tracking frequency
(ftrack) as a measured value trace in the fault record. In this way, you can document the behavior of the device
in transient conditions. The following figure shows that you find the both measured values in the information
routing under Power-system data → General:

[sc_Rout meas freq, 1, en_US]

Figure 3-29 Routing of the Frequency Measured Values

EXAMPLE:
Figure 3-30 shows the behavior of sampling-frequency tracking using an example.
The voltage was reduced linearly from 57.7 V (100 V phase-to-phase) to 35 V (60.6 V phase-to-phase) and, at
the same time, the frequency was reduced from 50 Hz to 35 Hz, for example motor coasting down. Then, an
abrupt switch to the rated values of 57.7 V at 50 Hz was made.
The upper trace shows the power-system voltage on 1 phase (A) as an example. The center trace is the calcu-
lated power frequency and the lower trace is the determined tracking frequency. If you multiply the deter-
mined tracking frequency of the lower trace by 20, you can determine the sampling frequency.

[sc_example freqtrack, 1, en_US]

Figure 3-30 Example of Frequency Tracking and Reaction to a Step Change in the Input Variable

96 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

3.3.3 Frequency Tracking Groups

In the SIPROTEC 5 devices before platform version V07.80, sampling-frequency tracking applies to the entire
device. This means that the 1st valid measuring point, for example a 3-phase voltage measuring point, deter-
mines the selected tracking frequency based on the detected frequency.
If all measuring points in a system are galvanically coupled to each other, the power frequency is identical for
all measuring points.
There are problems with electrical power system states or system states where galvanic separation is possible
and measuring points of the separated system parts are connected to the SIPROTEC 5 device. For these prob-
lematic electrical power system states or system states, different frequencies are possible for a limited time.
Depending on the measuring point set for tracking, the device selects which frequency to use. As a result,
measuring errors and a failure of protection functions are possible.
Starting with platform version V7.80, you can assign the measuring points to different frequency tracking
groups. This ensures high flexibility and high measuring accuracy for a variety of applications. In this case,
every frequency tracking group specifies its own sampling frequency. In the case of galvanic separation and
different system frequencies, different sampling frequencies arise as a result. This occurs temporarily in
systems with rotating machines, for example. A way to achieve galvanic separation is to use an open circuit
breaker.

NOTE

i In the measured-value acquisition chain in Figure 3-26 in the chapter 3.2 Measured-Value Acquisition, only
the data stream designated as tracked is adapted. The data stream represented as fixed derives its sampling
frequency exclusively from the set rated frequency. In this case, the constant sampling frequency of 1 kHz
at frated = 50 Hz and 1.2 kHz at frated = 60 Hz is used. This applies to every measuring point, regardless of the
frequency tracking group to which it is assigned.

EXAMPLE:
Figure 3-31 shows an example for the necessity of frequency tracking groups. The generator circuit breaker
(GCB) and the high-voltage circuit breaker (HVCB) are the galvanic disconnection points. In this way, different
switching states are possible. The device uses current measuring points (CTs 1 to 6) and voltage measuring
points (VTs 1 to 4) located on different sides of the circuit breakers. In addition, it is assumed that the gener-
ator is started using a starting-frequency converter. In a gas-turbine application, the starting-frequency
converter accelerates the generator from 0 Hz to about 70 % of the rated speed (roughly 35 Hz at
frated = 50 Hz). After this, the gas turbine is fired up and brings the generator to the rated speed. Then, the
voltage is built up to the rated voltage and synchronized. During this start-up operation, the GCB is open and
the HVCB is closed. As a result, the measuring points VT 1, CTs 1, 2, 4 have a frequency that deviates from the
other measuring points during start-up operation. The other measuring points are usually at the rated
frequency due of the connection to the power system.
Furthermore, protection tripping can result in a switching state where the HVCB is open and the GCB remains
closed. In this case, the generator and a generator transformer can assume a frequency that deviates from the
power frequency. In the event of load shedding, the generator accelerates before the speed controller inter-
venes. This is particularly pronounced in hydro generators.
An evaluation of the individual scenarios shows that different frequencies can occur at the different meas-
uring points for a limited time. For this reason, 3 frequency tracking groups are necessary in this example.
These groups are marked with different colors in the following figure.

NOTE

i The measuring point (CT 4) marked with 1) in the following figure will be discussed later.

SIPROTEC 5, 7SJ82/7SJ85, Manual 97


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

[dw_example_frequency-tracking-groups, 1, en_US]

Figure 3-31 Example of the Necessity of Frequency Tracking Groups

To strike a balance between application flexibility and the required computing power, the number of addi-
tional frequency tracking groups was limited to 5. Together with the basic functionality, a total of 6 frequency
tracking groups are possible.
If you wish to use frequency tracking groups, use the following engineering recommendations. Before starting
work, make sure you know how many frequency tracking groups are needed. Select only the required
number.
If you start with an application template that you have expanded by the necessary measuring points, you must
load the necessary number of additional frequency tracking groups from the Global DIGSI 5 Library into the
Power system folder.

98 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

[sc_loading freq group, 1, en_US]

Figure 3-32 Loading the Required Frequency Tracking Groups

If you instantiate an additional frequency tracking group, the system automatically assigns the ID of the
frequency tracking group in DIGSI using consecutive numbers. As the device already has 1 frequency tracking
group, the ID numbering for additional frequency tracking groups starts with 2.

[sc_ID freqgroup, 1, en_US]

Figure 3-33 ID of the Frequency Tracking Group

NOTE

i If you have activated several frequency tracking groups during engineering and you then delete a
frequency tracking group again later, the assigned ID is also deleted. All other frequency tracking groups
retain their assigned IDs.
Try to avoid discontinuities by deleting the frequency tracking group with the highest ID if possible.

You will find the frequency measured values and the indications of the corresponding frequency tracking
group in the routing matrix (see Figure 3-29).
Assign the measuring points to the frequency tracking groups in the Function-group connections Editor. As
soon as you have instantiated another frequency tracking group from the Global DIGSI 5 Library, the addi-
tional column Frequency tracking group ID appears in the routing matrix. In this column, you select the
number of the corresponding frequency tracking group for each measuring point using the list box.

[sc_Routing MP to freqgroup, 1, en_US]

Figure 3-34 Assignment of the Measuring Point to the Frequency Tracking Group

SIPROTEC 5, 7SJ82/7SJ85, Manual 99


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

NOTE

i Keep the following in mind when assigning the measuring points to the frequency tracking groups:

• The function groups (FGs) can operate only with 1 frequency tracking group.

• This applies also to interconnections between the function groups as for the Transformer differential
protection.
In the case of the Transformer differential protection, the Transformer side FG is interconnected
with the Transformer FG and all Transformer side FGs of one transformer must operate in the same
frequency tracking group.
The same applies when the neutral-point current is measured using a 1-phase function group.
There are also exceptions such as the FG Circuit breaker (see chapter 5.7 Function-Group Type Circuit
Breaker). The voltage measured values are processed by the Synchronization function which operates
only with a fixed sampling frequency. In this way, voltage measuring points from different frequency
tracking groups can be connected.
The cited rules are checked using scripts and infractions reported during engineering.

Now, you can select the measuring points to be used to determine the tracking frequency for the appropriate
frequency tracking group as explained in chapter 3.3.2 Sampling-Frequency Tracking. If possible, use at least
1 voltage measuring point and 1 current measuring point. Give preference to 3-phase measuring points.
When the tracking frequency has been determined, all measuring points of the frequency tracking group are
set to this frequency and the tracked sampling frequency is adapted.

NOTE

i As described in the chapter 3.2 Measured-Value Acquisition, the measured-value current with fixed
sampling frequency is unaffected by this.

To avoid errors, the ID of the measuring point and the ID of the assigned frequency tracking group are
displayed in the setting sheet of the measuring points in DIGSI 5 (see Figure 3-35).

[sc_MP additional setting freqgroup, 1, en_US]

Figure 3-35 Example: Settings of the 3-Phase Current Measuring Point; Additional Display of the ID for the
Frequency Tracking Group

In addition, the ID of the frequency tracking group is displayed in the function group in the General block (see
Figure 3-36). Here, you can also check the consistency.

100 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

[sc_MP additional setting FG, 1, en_US]

Figure 3-36 Display of the ID for the Frequency Tracking Group in the Block General of the Function Group

A special feature is explained using Figure 3-31 as an example.


The measuring point marked in Figure 3-31 with 1) uses a current transformer that is located on the generator
side but is used by the transformer differential protection. As a result, this current transformer must be
assigned to the frequency tracking group 2 in accordance with the rules above. Since the generator is started
using a starting-frequency converter in the application example, the frequency at this measuring point devi-
ates from the frequency at the other measuring points of group 2. For this reason, the measuring point with
CT 4 must not be used to determine the tracking frequency.
Depending on the application, the current of the CT 4 acts as a disturbance variable when forming the Kirch-
hoff's current law. As a rule, this current is not particularly strong (< 15 % of Irated) so that the disturbance
effect remains small. If required, you must set the differential protection to be less sensitive. Decide this for
the specific application.
The following table shows the possible assignment of measuring points used to determine the tracked
sampling frequency for the example. For this purpose, the parameter Tracking = active in the corre-
sponding measuring point:
Frequency Tracking 1 2 3
Group
Recommended measuring VT 4 VT 3 VT 1
points for tracking VT 2 CT 1
CT 5

3.3.4 Frequency Tracking Groups – Interpretation of Measured Values

If you use frequency tracking groups, you must keep in mind special features when interpreting the measured
values. The measuring points of a frequency tracking group are to be treated as decoupled for measurement
purposes. This means that the complex measured values of a single function group, like phasor measured
values, always match. Since phase A of the 1st measuring point is always assumed to be the reference value
when representing the measured value, the phasor measured values cannot be compared between frequency
tracking groups. This also applies if all measuring points are galvanically connected to one another.

NOTE

i When selecting the reference variable, a voltage measuring point always takes precedence over a current
measuring point. If the frequency tracking group does not contain a voltage measuring point, the 1st
current measuring point is used.

EXAMPLE:
Figure 3-37 shows an example of the phasor representation of the analog measured values of the measuring
points.
The phasor representation of the analog measured values of the measuring points can be found in the DIGSI 5
project tree under Online access → Device → Test suite → Analog inputs.

SIPROTEC 5, 7SJ82/7SJ85, Manual 101


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups

Each of the 2 frequency tracking groups contains one 3-phase voltage measuring point V-3ph and one 3-
phase current measuring point I-3ph.
Frequency tracking group 1 contains the measuring points V-3ph 1 and I-3ph 1, frequency tracking group 2
contains the measuring points V-3ph 2 and I-3ph 2. The frequencies between the frequency tracking groups
differ by 0.5 Hz. A phase displacement of -30° is set between the voltage and the current.
In Figure 3-37, you can see that the fundamental RMS measured values are identical. The phasor measured
angles are shown as decoupled (see Phase angle). In this case, VA is the reference value in the corresponding
frequency tracking group. With decoupled sampling-frequency tracking, the measurement of the measurands
is exact, even with a different system frequency.

[sc_measured_val_DIGSI, 1, en_US]

Figure 3-37 DIGSI Online Mode: Phasor Representation of the Measuring Points with 2 Frequency Tracking
Groups and a Different Frequency

If the circuit breaker in a system is closed, the measuring points are galvanically connected to one another. If
you want to compare the phasor variables of all measuring points to one another when using frequency
tracking groups, Siemens recommends starting a fault record. Evaluate the fault record using SIGRA in the
Phasor representation mode. The comparison is possible here because sampled values that are not
frequency-tracked are used in the fault record. If the frequency deviates from the rated frequency, the meas-
ured values differ slightly.

102 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

3.4 Processing Quality Attributes

3.4.1 Overview

The IEC 61850 standard defines certain quality attributes for data objects (DO), the so-called Quality. The
SIPROTEC 5 system automatically processes some of these quality attributes. In order to handle different appli-
cations, you can influence certain quality attributes and also the values of the data objects on the basis of
these quality attributes. This is how you can ensure the necessary functionality.
The following figure describes roughly the general data flow within a SIPROTEC 5 device. The following figure
also shows at which points the quality can be influenced. The building blocks presented in the figure are
described in more detail in the following.

[loquali1-090212-02.tif, 2, en_US]

Figure 3-38 Data Flow within a SIPROTEC 5 Device

Supported Quality Attributes


The following quality attributes are automatically processed within the SIPROTEC 5 system.

• Validity using the values good or invalid


The Validity quality attribute shows if an object transferred via a GOOSE message is received (valid,
invalid) or not received (invalid). The invalid state can be suppressed in the receiver device by also
setting a substitute value for the object that is not received (see 3.4.2 Quality Processing/Affected by the
User for Received GOOSE Values). The substitute value is forwarded to the functions.
If the device receives one of these values, it is replaced by the invalid value and thus processed further
as invalid.
If one of the detailed quality attributes (detailQual) has the value TRUE, then Validity is set to the
invalid value, unless this was already done at the transmitter end.
• Test using the values TRUE, FALSE
The Test quality attribute indicates to the receiver device that the object received via a GOOSE message
was created under test conditions and not operating conditions.

SIPROTEC 5, 7SJ82/7SJ85, Manual 103


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

• OperatorBlocked using the values TRUE, FALSE


The OperatorBlocked quality attribute indicates whether an object transferred via GOOSE message origi-
nates from a device that is in a functional logoff state. When the sending device is switched off,
the object is no longer being received and assumes the invalid state. However, since the Operator-
Blocked quality was previously identified on the receiver device, the object can be treated differently at
the receiving end (see chapter 3.4.2 Quality Processing/Affected by the User for Received GOOSE Values).
At the receiving end, the object may be treated like a dropped signal.

• Source using the values process, substituted


The Source quality attribute indicates whether the object was updated in the sending device.
You can find more detailed information in chapter 3.9.2 Acquisition Blocking and Manual Updating.

Influencing Quality by the Operating Modes


In addition to the normal operation, the device also supports further operating modes that influence quality:

• Test mode of the device


You can switch the entire device to test mode. In this case, all data objects generated in the device (state
values and measured values) receive the quality attribute Test = TRUE.
The CFC charts are also in test mode and all output data receive the quality attribute Test =TRUE.

• Test mode for individual functions, stages, or function blocks


You can switch individual functions, stages, or function blocks into test mode. In this case, all data
objects generated by the function, stage, or function block (state values and measured values) receive
the quality attribute Test = True.

• Functional logoff of the device


If you take the device out of operation and want to isolate it from the supply voltage, you can function-
ally log off the device ahead of time. Once you functionally log off the device, all data objects generated
in the device (state values and measured values) receive the quality attribute OperatorBlocked =TRUE.
This also applies to the output from CFC charts.
If objects are transferred via a GOOSE message, the receiver devices can assess the quality. The receiver
device detects a functional logoff of the transmitting device. After shutting down the sending device, the
receiver device identifies that the sending device has been logged off operationally and did not fail. Now
the receiving objects can automatically be set to defined states (see chapter 3.4.2 Quality Processing/
Affected by the User for Received GOOSE Values).

• Switching off individual functions, stages, or function blocks


You can switch off individual functions, stages, or function blocks. In this case, all data objects generated
by the function, stage, or function block (state values or measured values) receive the device-internal
quality attribute Off. The states of the inputs and measured values remain unchanged in this case; input
changes are not processed. As the quality attribute Off is not provided for in communication protocol
IEC 61850, the data objects are transferred with the quality attribute Invalid.

Influencing the Quality through Hardware Supervision


Supervision functions monitor the device hardware (see chapter 9.4 Supervision of the Device Hardware). If
the supervision functions identify failures in the data acquisition of the device, all recorded data will receive
the quality attribute Validity = invalid.

Influencing the Quality through Voltage-Transformer Circuit Breakers


If tripping of the voltage-transformer circuit breaker is detected (see chapter 9.3.4 Voltage-Transformer Circuit
Breaker), all recorded data will receive the quality attribute Validity = invalid.

104 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

Influencing the Quality by the User


You can influence the processing of data and their quality differently. In DIGSI 5, this is possible at the
following 3 locations:

• In the Information routing editor for external signals of GOOSE connections

• In the CFC chart

• In the Information routing editor for binary input signals of device-internal functions
The following chapters describe in more detail the options regarding this influence as well as the automatic
quality processing.
If a GOOSE connection is the data source of a binary input signal of a device-internal function, you can influ-
ence processing of the quality at 2 locations: at the GOOSE connection and at the input signal of the function.
This is based on the following: A GOOSE date can be distributed within the receiving device to several func-
tions. The GOOSE connection setting (influence) affects all functions. However, if different functions require
customized settings, these are then set directly at the binary input signal of the function.

3.4.2 Quality Processing/Affected by the User for Received GOOSE Values

The properties of quality processing have changed with the introduction of GOOSE Later Binding. You can find
information about the former quality processing in chapter Previous Quality Processing/Affected by the User
for Received GOOSE Values, Page 109.
In the Information Routing Editor, you can influence the data value and quality of all data types. The
following figure shows the possible influence using the example of a DPC data type. All setting options are
effective for the device receiving the data.

• In the DIGSI 5 project tree, double-click Information Routing.

• Select either the desired signal in the External Signals group or the signal of a function activated via the
GOOSE column.

• Open the Properties window and select the Processing Quality Attributes sheet.

SIPROTEC 5, 7SJ82/7SJ85, Manual 105


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

[sc_LB_GOOSE_2, 2, en_US]

Figure 3-39 Influence Option When Linking a DPC Type Data Object

Depending on the selected data type of the object, various selection options are offered to you for the Safe
state item in the Common settings section. At this point, you select the manually updated values that allow
a safe operating state as soon as the data access via the communication path is disturbed.

• Select the property for the selected data object.


You can also set the Advanced quality attributes of the data object for GOOSE Later Binding.
The following figure shows the advanced quality attributes using the example of a DPC data type.

• Open the Properties window and select the Advanced quality attributes sheet.

106 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

[sc_LB_GOOSE_1, 2, en_US]

Figure 3-40 Advanced Quality Attributes for GOOSE Later Binding

With the following advanced quality attributes, you can filter the transmitted GOOSE indications and check
and set their quality. The values that have been adapted, if necessary, are forwarded to the receiver.
For the tests, you can select from the following setting options depending on the data type.

Table 3-8 Value Definitions

Setting Value Description


Apply safe state value The value configured in the Safe state is forwarded as valid to the appli-
cation as soon as communication disturbance occurs.
Keep value The disturbed quality attribute is overwritten with good and the received
value is forwarded as valid to the application. If no value was received,
the output value is assumed being in safe state.
Keep last valid value If an invalid quality attribute is received, the last valid value is forwarded
to the application. If no value has yet been received, the output value is
assumed being in safe state.
Set value to "false" Applies only to Boolean communication objects. Every invalid quality
attribute causes the valid value false to be forwarded to the applica-
tion.
Set value to "true" Applies only to Boolean communication objects. Every invalid quality
attribute causes the valid value true to be forwarded to the application.

These settings of the Advanced quality attributes apply to the advanced quality attributes listed below. The
selection can vary depending on the data type.

SIPROTEC 5, 7SJ82/7SJ85, Manual 107


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

[sc_LB_GOOSE_3, 2, en_US]

Figure 3-41 Value Definition of a Data Object of the SPS Type

You can also forward the quality attributes unchanged. To do this, you must mark the Keep flag check box.

Functional Logoff by Operator Blocked


You have set the Operation mode to Device logoff = true in the transmitting device. As a result, every
indication issued from the functions and subject to Device logoff is transmitted with the quality informa-
tion operator blocked and Validity = good. The receiver recognizes this for this indication and reacts
according to the settings (Table 3-8). A different quality processing can take place only once you have set the
Operation mode to Device logoff = false in the transmitting device.

Communication Outage
There is communication disturbance (time allowed to live) between the transmitter and the receiver indicated
by the transmitter. The indication is set in accordance with the settings (Table 3-8).

Invalidity
The transmitting device sends this indication with the quality information Validity = invalid. The receiver
recognizes this for this indication and reacts according to the settings (Table 3-8).

Questionable
The transmitting device sends this indication with the quality information Validity = questionable. The
receiver recognizes this for this indication and reacts according to the settings (Table 3-8).

Test Mismatch
The transmitting device or the function in the transmitting device that issues this indication is in test mode. As
a result, the indication is transmitted with the quality information test. The receiving function block recog-
nizes this for this indication and reacts, depending on its own test-mode state (specified in IEC 61850-7-4
Annex A), according to the settings (Table 3-8).

NOTE

i Follow the sequence of tests. First, the Functional logoff by operator blocked is tested. Then comes
Communication outage and so on. If a case is recognized as active, the test chain is canceled with the
configured setting for the active case.

In the case of Invalidity, the tests are first performed for Functional logoff by operator blocked (not appli-
cable) and then for Communication outage (not applicable) and canceled with the configured action for
Invalidity.
If an indication is routed into the log, manual updating of a value is also logged based on the conditions listed
above and on the reason for the manual update. Manually updating a value based on the conditions listed
above causes a change in the Health Warning function block, inherited up to Device health (specified
in IEC 61850-7-4).

108 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

Keep Flag
The quality attributes and values indicated by the transmitter are accepted without change. Quality processing
must be performed by the user via a logic diagram. The outputs of the logic diagram following the user-
specific quality processing can be connected to the function-block inputs as before.

Data Substitute Values


Depending on the data type, different data substitute values must be used.
Data Type Possible Data Substitute Values
ACD, ACT general 0 (False), 1 (True)
(The directional information is always manually updated with
unknown.
PhsA, phsB, phsC, and neut are manually updated with the same
value just like how the general value is set.)
BAC, APC mxVal Floating-point range and range of values according to IEEE 754
(single precision)
BCR actVal –263 to 263 – 1
CMV mag, ang Floating-point range and range of values according to IEEE 754
(single precision)
DPC, DPS stVal 0, 1, 2, 3 (intermediate-state, off, on, bad-state)
INC stVal –2 147 483 648 to 2 147 483 647
INS stVal –2 147 483 648 to 2 147 483 647
ISC, BSC valWTr.posVal –64 to 64
valWTr.transInd 0 (False), 1 (True)
SPC, SPS stVal 0 (False), 1 (True)
MV mag Floating-point range and range of values according to IEEE 754
(single precision)

For controllable types, the following substitute values apply in addition to the settable state values or meas-
ured values:
ctlNum = 0
stSeld = False
origin.orIdent = Substituted by quality processing
origin.orCat = AUTOMATIC_BAY

Previous Quality Processing/Affected by the User for Received GOOSE Values


In the Information Routing editor, you can influence the data value and quality of all data types. The
following figure shows the possible influence using the example of a DPC data type.

• In the DIGSI 5 project tree, double-click Information Routing.

• Select the desired signal in the External Signals group.

• Open the Properties window and select the Processing Quality Attributes sheet.

SIPROTEC 5, 7SJ82/7SJ85, Manual 109


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

[sc_GOOSE values, 1, en_US]

Figure 3-42 Influence Option When Linking a DPC Type Data Object

The setting options work for the device receiving the data.
Quality Attribute: Validity
The validity values reserved and questionable are replaced at the receiving end by the invalid value.
• Check box is not set. The validity attribute and data value are forwarded
without change.
• Check box is set and receipt of Validity = good
Check box is set and receipt of Validity = invalid is • The validity attribute is set to good and
set (also applies to values reserved and ques- processed further using this value.
tionable). • The data value is set to the defined substitute
value and processed further using this substitute
value.

Quality Attribute: OperatorBlocked (opBlk)


• Check box is not set. The OperatorBlocked attribute and data value are
forwarded without change.
• Check box is set and received OperatorBlocked
= FALSE
Check box is set and received OperatorBlocked = • The OperatorBlocked attribute is set to FALSE
TRUE and processed further using this value.
• The data value is set to the defined substitute
value and processed further using this substitute
value.

110 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

Interaction of the Quality Attribute Validity and OperatorBlocked


OperatorBlocked check box is set and receipt of Oper- Regardless of whether the validity check box is set or
atorBlocked = TRUE not, and regardless of the current validity, the validity
attribute is set to good and the substitute value of
the OperatorBlocked data object is set. That is, the
OperatorBlocked settings overwrite the Validity
settings.
OperatorBlocked check box is not set and receipt of The OperatorBlocked attribute remains set and is
OperatorBlocked = TRUE forwarded.
If the Validity check box is set and the receipt of
validity = invalid is set, the respective data object
substitute value is used.
For continued signal processing and influence, it must
be taken into account that in this configuration the
data object substitute value for validity = invalid is
set, but the quality attribute OperatorBlocked is not
yet set.

3.4.3 Quality Processing/Affected by the User in CFC Charts

In DIGSI 5, you can control the quality processing of CFC charts. In the project tree, you can find the CFC
building block (see the following figure) under Device name →, Settings → Device settings in the editor:

[sc quali cfc, 1, en_US]

Figure 3-43 Influencing CFC Quality Handling in DIGSI 5

With the CFC chart quality handling parameter, you control whether you want to influence the
quality of CFC charts in a Manual or Automatic (default setting) manner.
If you select Manual, the quality attribute of the CFC chart is always valid regardless of the quality of indi-
vidual signals (Validity = good)!
Only the Test quality attribute of the CFC chart is processed. If the device is in test mode or the input TEST of
the CHART_STATE CFC building block is set, the quality attribute of the CFC chart is set to Test.
If you select Automatic, the quality processing of the CFC charts is influenced as follows:
In the case of CFC charts, a distinction has to be made between the general quality processing and certain CFC
building blocks that are specifically designed for quality processing.

SIPROTEC 5, 7SJ82/7SJ85, Manual 111


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

General Processing
Most of the CFC building blocks do not have an explicit quality processing. For these building blocks, the
following general mechanisms shall apply.
Quality Attribute: Validity
If one invalid signal is received in the case of CFC input data, then all CFC output data will also be set to
invalid if they originate from building blocks without explicit quality processing. In other words, the
quality is not processed sequentially from building block to building block but the output data are set glob-
ally.
This does not apply to CFC output data that originate from building blocks with explicit quality processing
(see next section).

Quality Attribute: Test


CFC chart is in normal state. CFC input data with the Test = TRUE attribute are ignored. When
the CFC chart is executed, then the data value that was used
before the Test = TRUE attribute is used. The quality of this old
value is also processed.
This means that on the output side, the attribute Test = FALSE.
CFC chart is in Test1) state. If the CFC chart is executed, then the attribute Test = TRUE is set
for all data leaving the CFC chart. This does not depend on
whether the data are formed via CFC building blocks with or
without quality processing.
1)ACFC chart can be switched to the test state by switching the entire device to test mode or the input TEST of
the CFC building block CHART_STATE is set.
Quality Attribute: OperatorBlocked
CFC chart is in normal state. In CFC charts for incoming data, the OperatorBlocked attribute
is ignored.
CFC chart is in functionally logged off1) In CFC charts for incoming data, the OperatorBlocked attribute
state . is ignored. All CFC output data are labeled as functionally logged
off.
1)This state only occurs if the device is functionally logged off. In this case, the quality attributes of all CFC
outputs are labeled as functionally logged off.

Quality Processing Building Blocks (Condition Processing)


The first 3 building blocks (x_SPS) process the quality automatically according to the stated logic. The other
building blocks are used to isolate the quality from a data object and add them back after separate logical
processing.

112 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

Building Blocks Description


OR_SPS The building blocks also process the supported quality attributes according to their logic.
The following tables describe the logic using input values in connection with the quality
AND_SPS attribute Validity. The input values are 0 or 1, the quality attribute Validity can have the
value good (=g) or invalid (=i).
NEG_SPS
x = placeholder for the input value and quality attribute Validity
OR_SPS
A (Value, Attribute) B (Value, Attribute) Q (Value, Attribute)
0, i 0, x 0, i
0, g 0, g 0, g
1, g x, x 1, g
1, i 0, x 1, i
1, i 1, i 1, i
The output thus has the logical value 1 with Validity = good as soon as at least 1 input has
the logical value 1 with Validity = good. Otherwise, the inputs are treated according to the
OR operation and the INVALID bit is OR-gated for the quality.
AND_SPS
A (Value, Attribute) B (Value, Attribute) Q (Value, Attribute)
0, g x, x 0, g
0, i 1, x 0, i
1, i 1, x 1, i
1, g 1, g 1, g
The output thus has the logical value 0 with Validity = good as soon as at least 1 input has
the logical value 0 with Validity = good. Otherwise, the inputs are treated according to the
AND operation and the INVALID bit is OR-gated for the quality.
NEG_SPS
A (Value, Attribute) Q (Value, Attribute)
0, i 1, i
0, g 1, g
1, i 0, i
1, g 0, g
SPLIT_SPS The building blocks isolate the data value and quality of a data object.
The requirement is that the quality is available from the input end. This is the case if the
SPLIT_DPS building block is interconnected with CFC input data, or is connected downstream with a
quality processing building block (x_SPS). In other cases, the CFC editor does not allow a
SPLI_XMV
connection.
SPLIT_Q The building block performs binary separation of the quality into good, bad (= invalid),
test, off and OperatorBlocked.
These 5 attributes can then be processed individually in a binary operation. The building
block must be connected downstream to a SPLIT_(DO) building block.
BUILD_Q The building block enters a binary value for good and bad (= invalid) in each quality
structure. Thus, with this building block the quality attributes good and bad (=invalid)
can be set explicitly, for example, as the result of a monitoring logic.
All other quality attributes are set to the default state, for instance, Test = FALSE. If, for
example, the entire CFC chart is in the test state (see Quality Attribute: Test Under General
Processing), this default status can again be overwritten on the CFC output side.
The building block is normally connected downstream to a BUILD_(DO) building block.

SIPROTEC 5, 7SJ82/7SJ85, Manual 113


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

Building Blocks Description


BUILD_ACD These building blocks merge data value and quality. The building-block output is generally
used as a CFC output.
BUILD_ACT Generally, the BUILD_Q building block is connected upstream from these building blocks.

BUILD_BSC

BUILD_DPS

BUILD_ENS

BUILD_SPS
BUILD_XMV

CFC charts have a standard behavior in the processing of signals. If an input signal of the CFC chart has the
quality invalid, all output signals of the CFC chart also get the quality invalid. This standard behavior is
not desirable in some applications. If you use the building blocks for quality processing, the quality attributes
of the input signals in the CFC chart are processed.

EXAMPLE: Switchgear Interlocking via GOOSE


The following conditions apply to the example:

• The interlocking condition for switchgear interlocking protection is stored in the device as a CFC chart.

• The removed device sends the release signal for the interlocking condition via a GOOSE telegram.
If the communication connection has been interrupted, the release signal (GOOSEStr) incoming via the
GOOSE telegram gets the quality invalid. If the CFC chart obtains an invalid input signal, there are the
following possibilities: The last signal valid before the communication interruption is used (quality = good) or
a substitute data value with the quality good is used (True, False).
To do this, you have to create a separate CFC chart in addition to the interlocking plan of the switchgear inter-
locking. Use the building blocks for quality processing in a separate CFC chart. With the SPLIT_SPS building
block, split the input signal (data type = SPS) into data value and quality information. You can then continue to
process these signals separately in the CFC chart. Use the quality information as an input signal for a
BUILD_SPS building block and assign the quality good to the signal. You obtain an SPS signal as a result, with
the quality good. You can use this to process release messages correctly. You can process the release
messages with the quality good in the CFC chart of the actual interlocking. Therefore, the release signal for a
switch illustrated in the interlocking logic is available as a valid result with the quality good. The following
figure shows an example of the CFC chart with the building blocks for quality processing:

[sccfcran-220415-01, 1, en_US]

Figure 3-44 CFC Chart with Building Blocks for Quality Processing (Switchgear Interlocking via GOOSE)

If you do not want to convert the invalid release signal to a valid signal, as described, during the communica-
tion interruption, you can also assign a defined data value to the release signal. Proceed as follows: With the

114 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

SPLIT_SPS building block, split the input signal (data type = SPS) into data value and quality information. Link
the VALID output of the SPLIT_SPS building block with the data value of the input signal (AND gate). This way,
you can set the value to a non-risk state with the valid input signals. In the example, the output of the CFC
chart is set to the value FALSE when the input signal is invalid.

3.4.4 Quality Processing/Affected by the User in Internal Device Functions

Figure 3-45 provides an overview for processing the quality of data objects within a device-internal function.
A function can receive internal data or input data that is routable by the user (binary input signal or double
commands). The respective quality attributes supported are evaluated by the function on the input side. The
attributes are not passed through the specific algorithm/the specific logic of the function. The output data are
supplied with a quality that is specified by the function state and device-operating mode.

NOTE

i Take into account that pickup of chatter blocking (see chapter 3.9.1 Signal Filtering and Chatter Blocking
for Input Signals) sets the corresponding Validity attribute to invalid.

[loquali3-100611-01.tif, 2, en_US]

Figure 3-45 Overview for Processing Quality within an Internal Function

Internal Input Data


The quality processing is automatic for internal input data.

SIPROTEC 5, 7SJ82/7SJ85, Manual 115


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

Supported Quality Attributes Description


Validity • At the receiving end, internal values can only be invalid
or good.
• If invalid, the function health is set to Alarm and the
function is reset.
Causes for invalid internal data are, for example:

• The frequency operating range of the device was left.


• The device is not calibrated.
• The A/D converter monitoring identified an error.

Routable Binary Input Signals (SPS Data Type)


Figure 3-46 shows the possible sources for connecting a binary input signal. Depending on the source,
different quality attributes can be set:

• CFC chart: See description in chapter 3.4.3 Quality Processing/Affected by the User in CFC Charts

• GOOSE connection: See description in chapter 3.4.2 Quality Processing/Affected by the User for Received
GOOSE Values

• Device hardware: No quality attributes are set and supported.

[loquali2-230212-01.tif, 2, en_US]

Figure 3-46 Sources for Connecting a Binary Input Signal

For this signal type (SPS), you can influence the processing of the quality, see overview in Figure 3-45.
The following figure shows the possible influence on a binary input signal of a protection stage.

• In the DIGSI 5 project tree, double-click Information routing.

• In the operating range, select the desired binary input signal.

• In the Properties window, select the Details entry. There, you will find the item Processing quality
attributes.

116 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

[sceinflu de, 1, en_US]

Figure 3-47 Influence Options for a Binary Input Signal (SPS Input Signal)

Quality Attribute: Validity


The Validity attribute can have the values good or invalid (reserved and questionable were already
replaced at the input end of the device by the value invalid).
The input signal source is invalid. The current data value of the source signal is ignored. You can
select between the following options:

• Further process last valid data value of the source signal


(this is the default setting with only a few exceptions)
• Set the binary value to be processed further to 0.
• Set the binary value to be processed further to 1.
This configuration option is necessary to satisfy different
applications.
The function health switches to Warning.
The input signal source is good. The source signal data value is processed further.

SIPROTEC 5, 7SJ82/7SJ85, Manual 117


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.4 Processing Quality Attributes

Quality Attribute: Test


• The input signal source and The source signal data value is processed further.
processed function are in test state.
• The input signal source is not in test
state and the function to be
processed is in test state.
The input signal source is in a test state The data value of the source signal is ignored. You can select
and the function to be processed is in between the following options:
normal state.
• Further processing of the last valid source signal data value,
before the source switches to the test state (that is the
default setting)
• The binary value to be processed further is set to 0.
• The binary value to be processed further is set to 1.
This configuration option is necessary to satisfy different applica-
tions.

Quality Attribute OperatorBlocked


The quality cannot be influenced at this position and does not lead to a response within the logic

Output Data
The quality is not processed through the actual algorithm/logic of the function. The following table displays
the conditions required to set the quality of output signals of a function.
Cause D0 Value Quality Attribute
After internal (to To the IEC 61850
the SIPROTEC 5 interface, in buffer
system, for example,
in the direction of a
CFC chart)
Functional state = Test Unchanged Test = TRUE Test = TRUE
(thus, result of device operating
mode = Test or function mode
= Test)
Functional state = Off Function-specific, corre- Validity = good Validity = invalid
(thus, result of device operating sponding to the definition for
mode = Off) switched off
Function health = Alarm Function-specific, corre- Validity = good Validity = invalid
(for example, result of invalid sponding to the definition for
receive data) reset
Device operating mode = func- Unchanged Validity = good Validity = good
tionally logged off OperatorBlocked = detailQual =
TRUE oldData
OperatorBlocked =
TRUE

118 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.5 Fault Recording

3.5 Fault Recording

3.5.1 Overview of Functions

All SIPROTEC 5 devices have a fault memory in which fault recordings are kept securely. Fault recording docu-
ments operations within the power system and the way in which protection devices respond to them. You can
read out fault recordings from the device and analyze them afterwards using evaluation tools such as SIGRA.
A fault record contains the following information:

• Sample values of the analog input channels

• Measured values calculated internally

• Any binary signals (for example, pickup signals and trip signals of protection functions)
You can individually configure the signals to be recorded. Furthermore, you can define the starting condition,
the record duration, and the saving criterion of a recording. Fault records saved in the device are also available
after a loss of auxiliary voltage.

3.5.2 Structure of the Function

The Fault recorder function is a central device function. Both the recording criterion and the measured-value
and binary channels to be recorded are functionally preconfigured through the application templates. You are
able to individually adapt the configuration in DIGSI 5. The fault recording and the fault log are subject to the
same control. This ensures that real time, relative time, and numbering of the fault data are synchronized.
This means that all fault recordings function on the same real-time and relative-time basis.
The data read out via the DIGSI-PC are saved in COMTRADE format. Fault recording data can be transferred to
the substation automation technology by request in accordance with the standards via existing communica-
tion connections (such as IEC 61850, IEC 60870-5-103). The central device analyzes the data using appro-
priate programs.

3.5.3 Function Description

The Fault recorder function records the sampled values, specific to each device, of all analog inputs, the inter-
nally calculated measured values and the binary signals. The configuration, which is predefined for each
device via an application template, can be adapted individually.

NOTE

i You can find detailed information about selecting and deleting fault records in the Operating Manual
(C53000-G5040-C003).

The fault memory of the device is automatically updated with every recording. When the fault memory is filled
completely, the oldest records are overwritten automatically. Thus, the most recent recordings are always
stored safely. The maximum number of recordings is 128.

Sampling Frequency
The analog measuring channels are sampled at a different sampling rate for fault recording. The Sampling
frequency parameter is used to set the desired sampling frequency. Possible setting values are 1 kHz, 2 kHz,
4 kHz, and 8 kHz . This setting value applies only to fault recording and does not affect protection functions or
calculated measured values.

SIPROTEC 5, 7SJ82/7SJ85, Manual 119


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.5 Fault Recording

Record Duration
The overall duration of a single fault recording comprises the total duration of the configurable recording
criterion, the Pre-trigger time and the Post-trigger time . You can set the parameters for these
components individually.

[dwsigrar-070813-01, 1, en_US]

Figure 3-48 Example of a Fault Recording

With the Fault recording parameter, you specify the start criterion of the recording.
You can set the following values:

• with pickup:
The fault recording records the complete fault until dropout. The resulting pickup signals of all function
groups are taken into account.

• with pickup & AR cyc.:


In connection with an active automatic reclosing function (internal/external), the fault recordings record
the fault including the short and long interruptions (automatic reclosing cycles).

• user-defined:
With this setting value, you can individually specify the recording criterion for the fault recording in
DIGSI 5. Function-specific recording criteria can be realized in this way.
If a recording criterion reoccurs during the pickup time and post-trigger time, the recording which is currently
active is extended to include a new post-trigger time.
For a sampling frequency of 8 kHz and 24 analog channels to be recorded, the duration of one individual fault
recording can be up to 20 s.
The maximum record duration can be limited by the Maximum record time parameter.
In addition to starting the fault recording via the pickup, the following alternatives are possible:

• Externally via binary input signal >External start (for example, from an external protection device
without fault recording by an object transferred via a GOOSE message)

• By way of a configurable input signal >Manual start, you can start fault records with a configurable
length (parameter Manual record time).

• From DIGSI 5, you can start test fault records with a fixed length of 1 s.

• With a command from a central device via an existing communication connection (IEC 61850,
IEC 60870-5-103)

NOTE

i If a pickup signal is present continuously, the fault record is closed after the Maximum record time
expires and the fault recording is not restarted!

120 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.5 Fault Recording

Saving the Recording


Not every fault recording that is started actually needs to be saved. With the Storage parameter, you specify
whether or not you want to save the fault recording that has started. You can also save only fault data for
which the pickup of a protection function also caused a tripping. With this setting, faults beyond the self-
protection range will not lead to replacing fault recordings that have already been saved.

Configuration of Signals to Be Recorded


All analog inputs of the device that have been configured (currents and voltages) are recorded as sampled
channels.
Function-specific binary signals (for example, pickup and trip signals) and measured value channels can be
configured individually for recording in the DIGSI Information-routing matrix. For this purpose, a separate
Recorder column is available.
You can rename the signals in the DIGSI Information-routing matrix. You can change the order of the binary
signals and measured-value channels to be recorded in DIGSI under Signal order. You can find more detailed
information on this in the DIGSI 5 Online Help, version V07.50 and higher (Order number: C53000-D5040-
C001-D).
The operational measured values and the measured values of the fundamental components and symmetrical
components (see the Device Manual, chapters 10.3 Operational Measured Values and 10.4 Fundamental and
Symmetrical Components) are calculated every 9 cycles (at 50 Hz, this is every 180 ms). However, this can
mean that the data are not synchronized with the sampled values of the analog channels. The recording of
these measured values can be used to analyze the slowly changing processes.

Numbering and Time Stamping


All fault recordings saved are automatically numbered in ascending order and assigned a real-time stamp for
the start time. The fault recording logs the fault with a relative time. The reference-time point is the start of
the recording. Every fault recording has a corresponding fault log with the same number. This ensures that the
fault recording can be uniquely assigned to the event log.

Fault Memory
The device manages its available fault memory dynamically, so that the maximum recording capacity is always
available. When exceeding the limits of the fault memory, the oldest recordings are automatically overwritten.
This means that the most recent recordings are always available. The sampling rate, type, and number of
measured value trends to be recorded are the crucial variables when it comes to restricting the length and
number of recordings possible. Parallel to the sampled tracks, up to 50 tracks with function-specific measured
values and up to 200 binary tracks can be recorded. The following table provides an overview of the maximum
storage capacities, in seconds, for different connection variations of the protection devices.

Table 3-9 Maximum Length of All Stored Recordings

Connection Examples Sampling Sampling Sampling Sampling


1 kHz 2 kHz 4 kHz 8 kHz
Feeder: 1365 s 819 s 455 s 241 s
4I, 6 measured values, 20 binary tracks
Feeder: 1125 s 566 s 284 s 142 s
4l, 4V, 20 binary tracks
Feeder: 890 s 500 s 266 s 137 s
4I, 4V, 6 measured values, 20 binary tracks
Feeder 1.5 CB: 525 s 281 s 145 s 74 s
8I, 8V, 6 measured values, 20 binary tracks

Input and Output Signals


The Fault recorder function provides several input signals that allow the precise starting, deleting of record-
ings. The output signals provide information about the function status.

SIPROTEC 5, 7SJ82/7SJ85, Manual 121


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.5 Fault Recording

In the following table, you can find input signals of the Fault recorder function:
Name Type Description
Control: Start recording SPC Start recording via the function key
Control: Reset memory SPC Delete all recording via the function key. The
error numbers are reset.
Control: Delete memory SPC Delete all recording via the function key. The
error numbers remain as is.
Control: >External start SPS Start recording with an external binary signal,
for example, by the trip command of an external
protection device. The set pre- and post-trigger
time are taken into account.
Control: >Manual start SPS Start a recording of fixed duration (parameter
Manual record time ) by way of an
external binary signal, for example, manually via
the function key or by an external binary signal.

In the following table, you can find output signals of the Fault recorder function:
Name Type Description
General: Mode ENC Status feedback of the fault recording according
General: State ENS to chapter 2.3 Function Control
General: Standby ENS
Control: Error number INS The indication of the current error number
allows a unique allocation of entries in the
message buffers for the recorded fault records.
Control: Recording started SPS Fault recording running

3.5.4 Application and Setting Notes

Parameter: Fault recording

• Recommended setting value (_:2761:130) Fault recording = with pickup


With the Fault recording parameter, you define the time interval at which faults are recorded. The total
record duration is defined as the duration of the fault plus the total of the parameters Pre-trigger time,
Post-trigger time and is limited by the maximum record duration.
Parameter Value Description
with pickup The fault recording time is determined by the total number of all protection
pickups. The resulting pickup signals of all function groups are taken into
account.
Note: When the post-trigger time has expired, the indications of an auto-
matic reclosing function are not recorded. Evolving faults after expiry of the
post-trigger time can result in the opening of a new fault with its own
recording.
with pickup & AR cyc. The fault recording time is determined by the total number of all protection
pickups including short and long interruptions (automatic reclosing cycles).
It includes the resulting pickup signals of all function groups and the
runtimes of initiated automatic reclosing cycles for all active automatic
reclosing functions.

122 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.5 Fault Recording

Parameter Value Description


user-defined The fault recording time is defined user-specific.
Note: You must specify all signals for individual definition of the fault
recording time in the DIGSI 5 information-routing matrix. In the information
routing matrix in the Fault record column, the fault recording has for this
purpose a separate column Trigger. The record duration is calculated from
the logical OR operation of all initiated, configured signals.

Parameter: Storage

• Recommended setting value (_:2761:131) Storage = always


With the Storage parameter, you define the storage criterion for a fault recording that has already started.
Parameter Value Description
always Each fault recording that has been started is saved.
with trip If at least one protection function issues an operate indication during the
record time, any fault recording that has been started will be saved.

Parameter: Maximum record time

• Default setting (_:2761:111) Maximum record time = 5.00 s


With the Maximum record time parameter, you configure the maximum record duration for an individual
fault recording. When the time configured expires, an ongoing fault recording is canceled. This parameter
merely limits the duration of the fault recording. It does not affect the logging of faults in the fault log.

Parameter: Pre-trigger time

• Recommended setting value (_:2761:112) Pre-trigger time = 0.50 s


With the Pre-trigger time parameter, you configure the pre-trigger time for an individual fault recording.
The set pre-trigger time is prepended to the actual recording criterion for the fault recording.

Parameter: Post-trigger time

• Recommended setting value (_:2761:113) Post-trigger time= 0.50 s


With the Post-trigger time parameter, you configure the post-trigger time for an individual fault
recording. The post-trigger time that has been configured is added to the actual recording criterion for the
fault recording after the dropout.
The following table shows how the setting range changes for the Post-trigger time parameter
depending on the Sampling frequency.
Sampling Frequency Setting Range for the Post-trigger time Parameter
8 kHz 0.05 s to 4 s
4 kHz 0.05 s to 8 s
2 kHz 0.05 s to 16 s
1 kHz 0.05 s to 24 s

Parameter: Manual record time

• Recommended setting value (_:2761:116) Manual record time = 0.50 s


With the Manual record time parameter, you set the length of a recording if the fault recording is acti-
vated dynamically (edge-triggered) via a separately configured input signal >Manual start.
In this case, pre-trigger and post-trigger times do not take effect.

Parameter: Sampling frequency

• Recommended setting value (_:2761:140) Sampling frequency = 8 kHz

SIPROTEC 5, 7SJ82/7SJ85, Manual 123


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.5 Fault Recording

With the Sampling frequency parameter, you define the sampling frequency of fault records that you
want to download via DIGSI 5. Possible setting values are 8 kHz, 4 kHz, 2 kHz, and 1 kHz.

Parameter: Sampl. freq. IEC61850 rec.

• Recommended setting value (_:2761:141) Sampl. freq. IEC61850 rec. = 8 kHz


With the Sampl. freq. IEC61850 rec. parameter, you define the sampling frequency of the fault record
that you want to download using the IEC 61850 communication protocol. Possible setting values are 8 kHz,
4 kHz, 2 kHz, and 1 kHz.
You cannot set the Sampl. freq. IEC61850 rec. parameter to be greater than the maximum setting
value of the Sampling frequency parameter.
If the size of the COMTRADE file exceeds the maximum permissible storage capacity of the device, the original
recording is truncated. The truncated data are discarded.

Parameter: COMTRADE revision year

• Recommended setting value (_:2761:151) COMTRADE revision year = COMTRADE 1999


With the COMTRADE revision year parameter, you select the version of the IEEE standard for the
COMTRADE format. Possible setting values are COMTRADE 1999 or COMTRADE 2013.

Parameter: Scaling COMTRADE

• Recommended setting value (_:2761:128) Scaling COMTRADE = Secondary values


With the Scaling COMTRADE parameter, you scale the fault record data for the COMTRADE format. Possible
setting values are Primary values or Secondary values.

Parameter: Cal.zero.seq.cur.channel

• Default setting (_:2761:129) Cal.zero.seq.cur.channel = no


With the Cal.zero.seq.cur.channel parameter, you determine whether the calculated zero-sequence
current 3I0 or -3I0 is recorded in a separate channel or not. The separate channel is visible in the DIGSI 5
Information routing under the I 3-phase measuring point.
The zero-sequence currents can be calculated only with the following current-transformer connection types:

• 3-phase + IN-separate

• 3-phase + IN

• 3-phase

Parameter Value Description


no The zero-sequence current calculated from the sampled values of the
currents is not recorded.
-3I0 The calculated zero-sequence current -3I0 is recorded for each I 3-phase
measuring point.
-3I0 is calculated from the sampled current values using the following
equation: -3I0 = - (IA + IB + IC).
3I0 The calculated zero-sequence current 3I0 is recorded for each I 3-phase
measuring point.
3I0 is calculated from the sampled current values using the following equa-
tion: 3I0 = (IA + IB + IC)

Parameter: Cal.zero seq.volt.channel

• Default setting (_:2761:132) Cal.zero seq.volt.channel = no

124 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.5 Fault Recording

With the Cal.zero seq.volt.channel parameter, you determine whether the calculated zero-sequence
voltage V0 or3V0 is recorded in a separate channel or not. The separate channel is visible in the DIGSI 5 Infor-
mation routing under the V 3-ph measuring point.
The zero-sequence voltages can be calculated only with the following current-transformer connection types:

• 3 ph-to-gnd volt. + VN

• 3 ph-to-gnd voltages

Parameter Value Description


no The zero-sequence voltage calculated from the sampled voltage values is
not recorded.
V0 The calculated zero-sequence voltage V0 is recorded for each V 3-ph meas-
uring point.
V0 is calculated from the sampled voltage values using the following equa-
tion: V0 = (VA + VB + VC)/3.
3V0 The calculated zero-sequence voltage 3V0 is recorded for each V 3-ph
measuring point.
3V0 is calculated from the sampled voltage values using the following
equation: 3V0 = (VA + VB + VC).

3.5.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2731:1 General:Mode • on on
• test
Control
_:2761:130 Control:Fault recording • with pickup with pickup
• with pickup & AR cyc.
• user-defined
_:2761:131 Control:Storage • always always
• with trip
_:2761:111 Control:Maximum record 0.20 s to 20.00 s 5.00 s
time
_:2761:112 Control:Pre-trigger time 0.05 s to 16.00 s 0.50 s
_:2761:113 Control:Post-trigger time 0.05 s to 16.00 s 0.50 s
_:2761:116 Control:Manual record 0.20 s to 20.00 s 0.50 s
time
_:2761:140 Control:Sampling • 8 kHz 2 kHz
frequency
• 4 kHz
• 2 kHz
• 1 kHz
_:2761:141 Control:Sampl. freq. • 8 kHz 1 kHz
IEC61850 rec.
• 4 kHz
• 2 kHz
• 1 kHz
_:2761:151 Control:COMTRADE revi- • COMTRADE 1999 COMTRADE
sion year 1999
• COMTRADE 2013

SIPROTEC 5, 7SJ82/7SJ85, Manual 125


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.5 Fault Recording

Addr. Parameter C Setting Options Default Setting


_:2761:128 Control:Scaling • Primary values Secondary
COMTRADE values
• Secondary values
_:2761:129 Control:Cal.zero.seq.cur. • no no
channel
• -3I0
• 3I0
_:2761:132 Control:Cal.zero • no no
seq.volt.channel
• V0
• 3V0

3.5.6 Information List

No. Information Data Class Type


(Type)
Binary IO
_:2731:51 General:Mode (controllable) ENC C
_:2731:52 General:Behavior ENS O
_:2731:53 General:Health ENS O
Binary IO
_:2761:300 Control:Start record SPC C
_:2761:305 Control:Reset memory SPC C
_:2761:306 Control:Clear memory SPC C
_:2761:502 Control:>External start SPS I
_:2761:503 Control:>Manual start SPS I
_:2761:310 Control:Fault number INS O
_:2761:311 Control:Recording started SPS O
_:2761:314 Control:Record made SPS O
_:2761:327 Control:Tmax reduced SPS O
_:2761:324 Control:Fault log is full INS O

126 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

3.6 Protection Communication

3.6.1 Overview

Protection communication includes all functionalities required to exchange data via the protection interface
(PI). It manages one or a maximum of 2 protection interfaces. The Protection communication is generated
with the configuration of the channels as a protocol.
You can find detailed information in the section Protection interface in chapter 3.6.3.1 Overview of Func-
tions.

3.6.2 Protection-Communication Structure

The following Protection communication functions are visible:

• Topology recognition

• Remote data
The following figure shows the structure of Protection communication:

[dwstrufg-171012-01.tif, 1, en_US]

Figure 3-49 Protection-Data Communication Structure

Interface to VI 3-Phase Function Group


Binary signals, measured values, and other data are automatically exchanged between the Protection-data
communication and the VI 3-phase protection function group.

Interface to Motor Function Group


Binary signals, measured values, and other data are automatically exchanged between the Protection-data
communication and the Motor protection function group.

Remote Data
The Remote data functionality is applied if you route a specific signal or a measured value to the protection
interfaces. The protection interface then attends to the transmitting and receiving of such signals. The
maximum amount of remote data is defined by the available bandwidth.

SIPROTEC 5, 7SJ82/7SJ85, Manual 127


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

3.6.3 Protection Interface and Protection Topology

3.6.3.1 Overview of Functions


The Protection topology and protection interface function enables data exchange between the devices via
synchronous serial point-to-point connections from 64 kBit/s to 2 MBit/s. These connections can be established
directly via optical fibers or via other communication media, for example via dedicated lines or via communi-
cation networks.
A protection topology consists of 2 to 6 devices which communicate via protection interfaces. It can be set up
either as a redundant ring or as a chain structure. Within a topology, the protection interfaces can have a
different bandwidth. Depending on the bandwidth, a certain amount of binary information and measured
values can be transmitted bi-directionally between the devices. The connection with the lowest bandwidth
defines this amount (of binary information and measured values).
The following information that is significant for the function of the protection interface is also transferred. You
cannot change this information:

• Topology data and values are exchanged for monitoring and testing the connection.
The results are displayed on the device or with DIGSI 5.

• Protection data, for example differential protection data or teleprotection scheme binary data, are trans-
ferred for distance protection and ground-fault protection.

• The devices can be synchronized in time via the connection, whereby a device of the protection topology
assumes the role of the timing master.
The connection is continuously monitored for data faults and outage, and the time delay of the data is meas-
ured.
The protection interfaces are typically used for differential protection and with the teleprotection scheme for
distance protection and ground-fault protection. In SIPROTEC 5, you can configure protection interfaces in all
devices and then use them for further protection applications. At the same time, any binary information and
measured values can be transferred between the devices.

3.6.3.2 Structure of the Function


The protection interfaces of a device are located in the Protection communication function group. A device
has 1 or 2 specifically parameterizable protection interfaces.
The protection topology is used for administration of that topology data relevant to the respective interfaces
and containing data from other devices in the protection topology.

[dwstruct-030211-01.tif, 1, en_US]

Figure 3-50 Structure of the Protection Interface in a Device

The protection communication runs physically via a serial optical communication module. This module can
have 1 or 2 channels. The protection communication can take place via various modules. This depends on the
type of interface and the application. DIGSI 5 is used to configure 1 or 2 channels of a serial optical module as
a protection interface. This enables communication with the values set at the protection interface via this
channel.

128 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

3.6.3.3 Function Description

Topology and Type of Protection Communication


The protection interfaces (PI) establish a direct point-to-point connection between devices via different
communication media. Data can be transferred within the switchgear or between switchgears.
Devices connected to one another with protection communication form a protection topology. Refer to
Figure 3-51.
The protection communication in a device can be either type 1 or type 2. In the case of devices with differen-
tial protection function (7SD and 7SL), a protection communication of type 1 is automatically created. Type 2
is created for other devices, and is used for other data transmission. A device can contain only the same types
of protection communication. Type 1 and type 2 protection communication do not work together in pairs via a
protection function.
Types Description
Type 1 With type 1, the differential protection function is the primary application.
This application requires the greatest portion of the bandwidth, so that with
Application using differential
type 1 the number of signals additionally available is lower. This becomes
protection
noticeable with a 64-kBit/s protection connection via a G703.1 or X21 inter-
face. If a multiple-end differential-protection application is realized, all
protection communications must be of type 1.
A maximum of 6 line ends is possible.
If the Differential protection and Teleprotection scheme functions are to
operate in parallel in the device, the bit rate must not be less than
512 kBit/s!
Type 2 Type 2 has a significantly higher amount of information that can be trans-
ferred as the differential-protection application is not used here. The trans-
Application without using
mission of protection data and other data, for example, measured values, is
differential protection
predominant here. Using type 2 protection communication, a maximum of
6 devices can be connected to one another and different device types (for
example, 6MD, 7VK, 7SA, and 7SJ) can exchange data.

[dwintert-030211-02.tif, 1, en_US]

Figure 3-51 Data Exchange between 4 Devices with Protection Communications of Type 1 or Type 2 in a
Protection Topology

2-Device Topology: Simple or Redundant Transfer


In the case of a simple 2-device topology, one protection communication per device is required (see next
figure).
The most frequent application is the point-to-point exchange of data between 2 devices (the protection
communication is of type 2), as performed by protection transmission devices.

SIPROTEC 5, 7SJ82/7SJ85, Manual 129


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[dwinterf-030211-01.tif, 1, en_US]

Figure 3-52 Data Exchange for 2 Devices, Each Having Protection Communication

NOTE

i The index describes the consecutive numbering of the devices in a protection topology (see parameter
Local device is device).

A maximum of 2 protection communications can be integrated in one device (see next figure). If 2 protection
communications of the same type are connected to one another, this results in 100 % redundancy regarding
the transmission route. The devices then search for the communication connection with the highest band-
width (for example, optical fiber). If this connection fails, the system switches over automatically to the 2nd
connection until the 1st connection is available again. As the connection with lower bandwidth defines the
maximum amount of transferable information, the same information is exchanged via both connections. Both
protection communications in the device are then of type 1.

[dwintera-030211-02.tif, 1, en_US]

Figure 3-53 Data Exchange for 2 Devices, Each Having 2 Protection Communications/Redundant Transmis-
sion Route

Protection-Interface Information Transfer


With the protection-interface information transfer, customer-specific indications and measured values can be
communicated via the protection interface with settable update cycles (priorities).
There are 3 different priorities when transferring protection-interface information:

• Priority 1: Use Priority 1 for the transmission of fast protection signals that are transferred and updated
at a maximum of every 20 ms in a telegram.

• Priority 2: Use Priority 2 for the transmission of fast single-point or double-point indications that are
transferred and updated at a maximum of every 40 ms.

• Priority 3: Use Priority 3 for all indications, measured, and metered values that are transferred and
updated a maximum of every 100 ms.
The number of customer-specific signals, indications, and measured values conform with the remaining band-
width. The remaining bandwidth is lower than with all other protection functions (type 2) when using a differ-
ential protection (type 1). Customer-specific measured values consume more bandwidth than single-point
indications.

Communication Media
The communication takes place via direct fiber-optic connections, via communication networks or via 2-wire
copper conductors. Siemens recommends a direct fiber-optic connection, as this offers the highest transmis-
sion rate of 2 MBit/s and is immune to failures in the communication route while offering the shortest trans-

130 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

mission time. This also enables the transmission of a large amount of additional information on differential
protection routes and the remote control of devices at the remote end with DIGSI 5.
The distance to be bridged and the transmission paths available determine the settings of the protection inter-
face. External communication converters are used for the connection to communication networks via
G703.1-, X21-, or G703.6 interfaces. The connection to 2-wire copper cores also takes place via a communica-
tion converter. The C37.94 interface, for example, with 2 MBit/s, offers a direct fiber-optic connection to a
multiplexer with the corresponding interface.
Table 3-10 to Table 3-11 show examples of communication connections.
In the case of a direct connection, the transmission distance depends on the fiber type of the optical fiber. This
distance can also be extended via external repeaters.
The modules in the device can be replaced from outside, so that adaptation to a transmission route is possible.
In the case of the 820-nm double module USART-AE-2FO with 2 channels, 2 protection interfaces can be oper-
ated on one module.
The modules can be located at slots E and F in the base device, and at slots N and P in the plug-in module
assembly with integrated power supply.
When using communication converters, the connection from the device to the communication converter by a
module is established via optical fibers.

Table 3-10 Plug-In Modules for Applications with the Protection Interface

Plug-In Modules

Module Type: USART-AH-1LDFO2

Module Type: USART-AX-2LDFO4

Module Type: USART-AY-2LDFO5


Module Type: USART-AW-2LDFO

Module Type: USART-AJ-1LDFO3


Module Type: USART-AG-1LDFO

Module Type: USART-AU-2LDFO

Module Type: USART-AK-1LDFO

Module Type: USART-AV-2LDFO


Module Type: USART-AF-1LDFO

Physical Connection
1 x optical serial, 1300 nm, duplex LC plug, 24 km via ●
9/125 μm singlemode optical fibers, 4 km via
62.5/125 μm multimode optical fibers
2 x optical serial, 1300 nm, duplex LC plug, 24 km via ●
9/125 μm singlemode optical fibers, 4 km via
62.5/125 μm multimode optical fibers
1 x optical serial, 1300 nm, duplex LC plug, 60 km via ●
9/125 μm singlemode optical fibers
2 x optical serial, 1300 nm, duplex LC plug, 60 km via ●
9/125 μm singlemode optical fibers
1 x optical serial, 1550 nm, duplex LC plug, 100 km ●
via 9/125 μm singlemode optical fibers
2 x optical serial, 1550 nm, duplex LC plug, 100 km ●
via 9/125 μm singlemode optical fibers
1 x optical serial, bi-directional via 1 optical fiber, ●
1300/1550 nm (Tx/Rx), simplex plug LC, 40 km via
9/125 μm singlemode optical fiber

2 USART-AH-1LDFO only pairs with USART-AJ-1LDFO or USART-AY-2LDFO on the opposite side


3 USART-AJ-1LDFO only pairs with USART-AH-1LDFO or USART-AX-2LDFO on the opposite side
4 USART-AX-2LDFO only pairs with USART-AJ-1LDFO or USART-AY-2LDFO on the opposite side
5 USART-AY-2LDFO only pairs with USART-AH-1LDFO or USART-AX-2LDFO on the opposite side

SIPROTEC 5, 7SJ82/7SJ85, Manual 131


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Plug-In Modules

Module Type: USART-AH-1LDFO2

Module Type: USART-AX-2LDFO4

Module Type: USART-AY-2LDFO5


Module Type: USART-AW-2LDFO

Module Type: USART-AJ-1LDFO3


Module Type: USART-AG-1LDFO

Module Type: USART-AU-2LDFO

Module Type: USART-AK-1LDFO

Module Type: USART-AV-2LDFO


Module Type: USART-AF-1LDFO
Physical Connection
1 x optical serial, bi-directional via 1 optical fiber, ●
1550/1300 nm (Tx/Rx), simplex plug LC, 40 km via
9/125 μm singlemode optical fiber
2 x optical serial, bi-directional via 1 optical fiber, ●
1300/1550 nm (Tx/Rx), 2 x simplex LC plug, 40 km via
9/125 μm singlemode optical fiber
2 x optical serial, bi-directional via 1 optical fiber, ●
1550/1300 nm (Tx/Rx), 2 x simplex LC plug, 40 km via
9/125 μm singlemode optical fiber

Table 3-11 Plug-In Modules USART-AD-1FO and USART-AE-2FO

Plug-In Module

USART-AD-1FO
USART-AE-2FO
Physical Connection
1 x optical serial, 820 nm, ST connector, 1.5 km via 62.5/125 μm multimode optical fibers ●
2 x optical serial, 820 nm, ST connector, 1.5 km via 62.5/125 μm multimode optical fibers ●
Application
Protection interface (Sync. HDLC, IEEE C37.94) X X

NOTE

i The USART plug-in module types can be used in slots E and F in the base module as well as in slots N and P
in the CB202 expansion module. They are not suitable for use in port M in the CB202 expansion module.

2 USART-AH-1LDFO only pairs with USART-AJ-1LDFO or USART-AY-2LDFO on the opposite side


3 USART-AJ-1LDFO only pairs with USART-AH-1LDFO or USART-AX-2LDFO on the opposite side
4 USART-AX-2LDFO only pairs with USART-AJ-1LDFO or USART-AY-2LDFO on the opposite side
5 USART-AY-2LDFO only pairs with USART-AH-1LDFO or USART-AX-2LDFO on the opposite side

132 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[dwmultim-070611-01.tif, 1, en_US]

Figure 3-54 Connection over Short Distances, 1.5 km to 2 km via Multimode Optical Fiber

[dwmultim-070611-02.tif, 1, en_US]

Figure 3-55 Connection over Maximum 4 km via Multimode Optical Fiber

[dwsingle-070611-03.tif, 1, en_US]

Figure 3-56 Connection via Different Distances via Singlemode Optical Fiber

NOTE

i In order to prevent optical overload of the receiver, a 7XV5107-0AA00 attenuator must be used on one side
in the fiber-optic modules USART-AF, USART-AG, USART-AU, USART-AK, and USART-AV for distances of less
than 25 km/50 km.

SIPROTEC 5, 7SJ82/7SJ85, Manual 133


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[dwsingle-020513-04.tif, 1, en_US]

Figure 3-57 Connection via Singlemode Optical Fiber

[dwmultim-070611-05.tif, 1, en_US]

Figure 3-58 Connection via Communication Network with a G703.1 Interface

The connection to the multiplexer is established via a communication converter with a G703.1 interface (64
kBit/s) or X21 interface (64 kBit/s to 512 kBit/s). You can set the bit rate for the KU-XG-512 (for X21), KU-
XG-256 (for X21), KU-XG-128 (for X21), and KU-XG-64 (for X21 or G703.1) with the parameter Connection
via.
You can find more detailed information in Table 3-12.

[dwmultim-070611-06.tif, 1, en_US]

Figure 3-59 Connection via Communication Network with a G703.6 Interface

The connection to the multiplexer is established with 512 kBit/s via a communication converter with a G703.6
interface (E1 with 2 MBit/s or T1 with 1.44 MBit/s). The communication converter offers a 2nd interface for
connecting an additional protection interface.
Make the setting for the bit rate with KU-2M-512 with 512 kBit/s in accordance with Table 3-12 with the
parameter Connection via.

134 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[dwmulti7-070611-01.tif, 1, en_US]

Figure 3-60 Connection via 2-Wire Copper Cables

The connection to a communication converter with an integrated 5-kV isolation voltage is established with
128 kBit/s (KU-KU-128 setting in accordance with Table 3-12). A 20 kV isolation of the 2-wire connection is
possible via an external 7XR9516 isolating transformer.

[dwrepeat-070611-10.tif, 1, en_US]

Figure 3-61 Direct Fiber-Optic Connection via an External Repeater

The repeater offers an interface for connecting an additional protection interface. The connection to a
repeater is established with 512 kBit/s (repeater 512 setting in accordance with Table 3-12) an einem
Repeater.

[dwmutip8-070611-01.tif, 1, en_US]

Figure 3-62 Direct Optical Connection to a Multiplexer with a C37.94 N * 64 kBit/s Interface (Time Slot N =
1; 2 or 8)

NOTE

i The redundancy of different communication connections (for the ring topology) requires rigorous separa-
tion of all devices involved in the communication. Therefore, avoid different communication routes via the
same multiplexer board, as no more substitute paths are possible if the board fails.

SIPROTEC 5, 7SJ82/7SJ85, Manual 135


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Supervision of the Communication


The communication is continuously monitored by the devices.
If a number of defective data telegrams, or no data telegrams at all, are received, this is regarded as a failure
in the communication as soon as a failure time of 100 ms (default setting can be changed) is exceeded. A list
of the measured values is shown in a window in DIGSI 5 (defective telegrams per minute/hour; transmitted
and received telegrams per minute/hour, percentage fault rate per minute/hour). A corresponding failure indi-
cation is always available. If no alternative communication route exists (as in the ring topology), the protec-
tion function operating with the protection interface is not operating and the remote signals are not updated
on the receiver side.
If the communication is interrupted for longer than an adjustable time Data-connection failure, this is
regarded as a communication failure. A corresponding failure indication is always available.

Time Synchronization via the Protection Interface


All devices of a topology can be time-synchronized with one another. Synchronization is carried out with milli-
second accuracy. The synchronization works independently of the protection function and is exclusively for
simultaneous time keeping in the devices of a protection topology.
The device you set in the parameter Address of device 1 is the device with index 1. This device functions
as the timing master in a protection topology. If the timing master is logged off and switched off, the device
with the next highest device index takes on the function of the timing master. The timing master synchronizes
the clocks of the other devices of this topology via the protection interfaces. The time of the timing master is
typically synchronized via a substation automation protocol (for example, Ethernet or SNTP) or via IRIG-B. For
this, these time sources must be set as the 1st time source and optionally as the 2nd time source in the timing
master. If available, the system switches over to the 2nd source upon outage of the 1st source in the timing
master. This time is communicated with millisecond accuracy to the other devices of the topology.
Set the protection interface as the 1st time source in the other devices of the topology. In this way, all events
in the devices of the protection topology are recorded with the same time and are time-synchronized even
across different switchgears. This simplifies fault analysis and the fault records are recorded with the same
time in all devices.

[dwtimesy-130212-01.tif, 1, en_US]

Figure 3-63 Time Synchronization in a Protection Topology

Figure 3-63 shows how device 1 with index 1 is synchronized with the devices 2, 3, and 4 via the protection
interface. Device 1 is synchronized externally from 2 sources (IRIG-B and SNTP via Ethernet).

136 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Time Synchronization of the Line Differential Protection Measured Values with Microsecond Accuracy
The measured values of the line differential protection for the various line ends are synchronized with each
other with microsecond accuracy via the mechanisms of the protection interface. The protection interface
displays this state with the RAISING indication Protection interface synchronized.
If communications problems occur, it is possible that the measured values may not be properly synchronized.
In this case, the protection interface generates the CLEARED indication Protection interface
synchronized. The line differential protection is blocked. This state can be corrected only by manual inter-
vention.

NOTE

i You can reset the synchronization of the protection interface directly in the device. Proceed as follows:
Device functions > x Device protection comm. > Protection interface y > Reset synchron.

Synchronization via GPS Second Pulse


Microsecond-accurate synchronization of the devices (1*10E-06 s), connected via protection interfaces, can
take place via a high-precision GPS second pulse at the time-synchronous port G for special differential protec-
tion applications or synchrophasor measuring devices. As a result, the transmission time of the communica-
tion route can be measured and displayed separately in the directions forward and reverse. This ensures that
the maximum responsivity can be obtained during differential protection, even if transmission times are
unbalanced in the communication networks. Different transmission times are insignificant for the transmis-
sion of protection data with a protection communication of type 2.

Log Off the Device


A device can be logged off for protection-function tests, system inspections, or disconnection of a feeder for
operational reasons. The device that is logged off no longer participates in the distributed functionality and is
therefore no longer a component of the topology. The protection functions are still in operation for the other
end or ends.
The following conditions are necessary for a successful logoff of the device from the point of view of protec-
tion communication:

• The protection topology is not in a transient state and is stable in operation without switchovers.

• The local device is one of the 2 token masters if there is a chain topology. The token masters are the
devices at the ends of the chain.

• The circuit breaker must be open and current must not be flowing.

NOTE

i If one of these conditions is not fulfilled, the device cannot be logged off.

You can find more detailed information in chapter 3.9.4 Device Logout.

SIPROTEC 5, 7SJ82/7SJ85, Manual 137


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

3.6.3.4 Initialization and Configuration of the Protection Interface in DIGSI 5


If the device is provided with modules, proceed as follows:

• Select the desired communication module in the rear view of the device.

• Use the Communication protocols text box to select the protection interface. A text box entitled Protec-
tion interface will then appear.

[scconfcp-241110-01.tif, 1, en_US]

Figure 3-64 Selection of the Communication Protocol

• Then select the Select constellation text box to select the number of devices (see next figure).

[scconfws-241110-01.tif, 1, en_US]

Figure 3-65 Selecting the Constellation

NOTE

i You have the option of changing the number of devices (for example 2 protection communication
devices) depending on the product code any way you like via the Select constellation text box.
If you change the number of devices via the Select constellation text box, all activated constellation
settings are lost.

138 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

If the module slot is not yet provided with modules, proceed as follows:

• Select the desired communication module in the rear view of the device.

• Select the module from the catalog and drag it to a channel. Thus is the channel configured with a
module. DIGSI 5 indicates whether the module can be used for protection communication under Device
Information.

• Use the Communication protocols text box to select the protection interface. A text box entitled Protec-
tion interface will then appear (see Figure 3-64).

• Then use the Select constellation text box to select the number of devices (for example 2 devices
protection com.) (see Figure 3-65).

3.6.3.5 Device-Combination Settings

[scconfig1, 1, en_US]

Make the device-combination settings and the settings for protection communication (see next figure).

SIPROTEC 5, 7SJ82/7SJ85, Manual 139


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[scconfig-181013-01, 3, en_US]

Figure 3-66 Protection Interface Initialization and Configuration

Changes in 1 channel are always visible on the other channel as well. All further parameters can be set sepa-
rately for individual channels.

Parameter: Address of Device x

• Default setting (_:5131:102) Address of device 1 = 101

• Default setting (_:5131:103) Address of device 2 = 102

• Default setting (_:5131:104) Address of device 3 = 103

• Default setting (_:5131:105) Address of device 4 = 104

• Default setting (_:5131:106) Address of device 5 = 105

• Default setting (_:5131:107) Address of device 6 = 106

140 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

The parameters Address of device 1 to Address of device 6 can be used to give an address to each
device. Set a unique and unambiguous address for each device.

Parameter: Local device is device

• Default setting (_:5131:101) Local device is device = 1


With the Local device is device parameter, you set the index (number) of your device in the topology.
A maximum of 6 devices can be available in a network topology.

APPLICATION EXAMPLE
You have a topology with 2 devices.
For example, in DIGSI 5, select the parameter setting Address of device 1 with the parameter value 101
for device 1 and the parameter setting Address of device 2 with the parameter value 102 for device 2.
Then, use the Local device is device parameter to set the index of the local device.
The addresses must be configured identically for all devices involved in the constellation. A functional protec-
tion communication requires that you also assign the same index in all devices of a constellation for a device
with a unique address.

Parameter: Lowest appearing bit rate

• Default setting (_:5131:122) Lowest appearing bit rate = 64 kBit/s


The Lowest appearing bit rate parameter is used to set the lowest bit rate occurring in the device
group. Set the lowest value in each device with a three-end constellation with 2 fiber-optic connections (2
MBit/s) and a 64 kBit/s connection with the lowest value (64 kBit/s). This value determines the maximum
signals and measured values within a constellation.
Apart from the default value, you can also set the following bit rates:

• 128 kBit/s

• 512 kBit/s

• 2048 kBit/s

NOTE

i If you use optical fibers for the connection between the devices, set the value to 2048 kBit/s.

Parameter: Number of devices

• Default setting (_:5131:125) Number of devices = 6


With the Number of devices parameter, you set the number of devices actually connected in the device
combination in one topology. This parameter is set by default to the maximum number of devices permitted
for the appropriate constellation.
The Number of devices parameter depends on the configuration of the protection interface. When config-
uring the protection interface, select the maximum number of devices present in the final phase of the system
in the Select constellation text box. If the current expansion phase of the system contains fewer devices at
this time, set the number of devices actually in the device combination using the Number of devices
parameter. In this procedure, all settings, for example, routing, you made for your constellation are retained.
If you wish to operate, for example, a 3-device protection communication as a 2-device protection communi-
cation, you must set the Number of devices parameter = 2.
If you expand the system later, change the Number of devices parameter to the number of devices
actually present.
You can find more detailed information regarding the configuration of the protection interface in chapter
3.6.3.4 Initialization and Configuration of the Protection Interface in DIGSI 5 .

SIPROTEC 5, 7SJ82/7SJ85, Manual 141


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

NOTE

i Set the same number of devices used in all devices that are part of the constellation.

Connection mode

• Default setting Connection mode = SIPROTEC 5


With the Connection mode parameter, you select the device type with which the SIPROTEC 5 device works
in the device combination via the protection interface.
Parameter Value Description
SIPROTEC 5 The SIPROTEC 5 device works with a SIPROTEC 5 device in the device combi-
nation.
SIPROTEC 4 7SD610 The SIPROTEC 5 device works with a SIPROTEC 4 differential protection
device 7SD610 with firmware version V4.74 and higher in the device combi-
nation.
SIPROTEC 4 7SD5 The SIPROTEC 5 device works with a SIPROTEC 4 differential protection
device 7SD5x with firmware version V4.74 and higher in the device combi-
nation.
SIPROTEC 4 7SA5/6 The SIPROTEC 5 device works with a SIPROTEC 4 distance protection 7SA522
and 7SA6x with firmware version V4.70 and higher in the device combina-
tion.

3.6.3.6 Selecting the Connection

• Default setting (_:105) Connection via = fiber optic


The Connection via parameter is used to set the bit rate required for the protection interface. Different
discrete values can be entered depending on the means of communication (see following table).

Table 3-12 Means of Communication

Means of Communication See Setting Value Bit Rate


Fiber-optic direct connection Figure 3-5 fiber optic 2 MBit/s
4 to
Figure 3-5
7
CC-XG-512 communication converter Figure 3-5 CCXG 512 kBit/s 512 kBit/s
8
CC-XG-128 communication converter Figure 3-5 CCXG 128 kBit/s 128 kBit/s
8
CC-XG-64 communication converter Figure 3-5 CCXG 64 kBit/s 64 kBit/s
8
Repeater 512 communication converter Figure 3-6 repeater 512 kBit/s 512 kBit/s
1
CC-CC-128 Communication converter Figure 3-6 CCPW 128 kBit/s 128 kBit/s
0
CC-2M-512 Communication converter Figure 3-5 CC2M 512 kBit/s 512 kBit/s
9
Multiplexer with C37.94 interface Figure 3-6 C37.94 1 * 64 kBit/s 64 kBit/s
2 C37.94 2 * 64 kBit/s 128 kBit/s
C37.94 8 * 64 kBit/s 512 kBit/s

142 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Means of Communication See Setting Value Bit Rate


Other (freely adjustable bit rates for a direct 64 kBit/s 64 kBit/s
connection for special applications) 128 kBit/s 128 kBit/s
512 kBit/s 512 kBit/s
2048 kBit/s 2048 kBit/s

3.6.3.7 Setting Notes for the Protection Interface

Parameter: Max. Error Rate/h

• Default setting (_:5161:105) Max. error rate per hour = 1.0 %


The Max. error rate per hour parameter allows you to receive an error message on the number of
faults per hour. An indication is then generated.

Parameter: Max. Error Rate/min

• Default setting (_:5161:106) Max. error rate per min = 1.0 %


The Max. error rate per min parameter allows you to receive an error message on the number of faults
per minute. An indication is then generated.

Parameter: Disturbance Alarm After

• Default setting (_:5161:107) Disturbance alarm after = 100 ms


The Disturbance alarm after parameter determines the time delay after which defective or missing
telegrams are signaled as faulty.

Parameter: Transm. Fail. Alarm After

• Default setting (_:5161:108) Transm. fail. alarm after = 6.0 s


The Transm. fail. alarm after parameter is used to set the time after which a failure of the communi-
cation is signaled.

NOTE

i If the setting values of the parameters Disturbance alarm after and Transm. fail. alarm
after are exceeded, then an indication is generated.

Parameter: Delay time threshold

• Default setting (_:5161:109) Delay time threshold = 30.0 ms


For the Delay time threshold, the default setting is selected such that it is not exceeded by normal
communication networks. If this time delay is exceeded during operation (for example, upon switchover to
another transmission route), the indication Time delay exceeded is issued.

Parameter: Difference Tx and Rx time

• Default setting (_:5161:110) Difference Tx and Rx time = 0.1 ms


The Difference Tx and Rx time parameter can be used to set a maximum time-delay difference
between the send and receive paths.
Set this value to 0 for a direct fiber-optic connection. A higher value is necessary for transmission via commu-
nication networks. Reference value: 0.1 ms (recommended setting value).

SIPROTEC 5, 7SJ82/7SJ85, Manual 143


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

NOTE

i Only if the Line differential protection function is instantiated, the Difference Tx and Rx time
parameter is displayed.

NOTE

i If the user employs a multiplexer with a C37.94 interface as a communication medium, Siemens recom-
mends a setting value of 0.25 ms to 0.6 ms.

Parameter: PPS Synchronization

• Default setting (_:5161:113) PPS synchronization=PPS sync. off


If the SIPROTEC device operates with PPS synchronization (PPS: pulse per second), use the PPS synchroni-
zation parameter to define how the protection is activated after restoration of the communication connec-
tion (basic state or after transmission fault).
Refer to Figure 3-67.

NOTE

i The PPS measurement is used to consider the time delay in the send and receive directions. If PPS fails due
to a reception fault or due to a short-term unfavorable satellite position, synchronization via conventional
communication media remains active.

The PPS synchronization parameter offers 3 different setting options:


Parameter Value Description
telegr. and PPS With this setting, the differential protection is only enabled upon renewed
establishment of the connection, if the communication section is synchron-
ized via PPS or if symmetrical time delays are signaled by an external opera-
tion (binary input).
This results in synchronization with the telegram measurement supported
by the PPS measurement.
telegr. or PPS In this setting, the differential protection is enabled immediately upon
renewed establishment of connection (data telegrams are received). The
conventional method is used up to synchronization.
This results in synchronization with the telegram measurement supported
by the PPS measurement.
PPS sync. off This setting means that no synchronization is performed via PPS at the
protection interface. This is typically the case if no time-delay differences
are expected.
The synchronization only takes place with the telegram measurement.

NOTE

i The synchronization mode can be set separately for both protection interfaces.

If no further PPS pulse is received within 2.1 s, the time-out supervision responds. If no new 2nd pulse occurs
after the expiry of the supervision time, the indication PPS pulse loss is issued.

144 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[loppssyn-100113-01.tif, 1, en_US]

Figure 3-67 Setting the PPS Synchronization

The binary input >PPS pulse loss can be used to signal an externally detected failure in the PPS signal (for
example, error message from the receiver). Setting this binary input also leads to the indication PPS pulse
loss.
If you are using a second pulse from a GPS receiver, you must ensure that a loss of reception or reception
disturbances do not generate a second pulse. The GPS receivers recommended by Siemens are set by default
so that a loss of reception or reception disturbances do not generate a second pulse. In the event of problems,
check the setting value for the second pulse.
Siemens recommends the Meinberg 164 GPS receiver. Check the default setting for the second pulse using
the GPSMON32 program. The program is available in the SIPROTEC download area. You can find the setting
value under Outputs →Enable Flags. The second pulse must be set to the value if Sync.

[scGPS_1, 2, --_--]

Figure 3-68 Checking the Setting Value for the 2nd Pulse Using the GPSMON32 Program, Step 1

SIPROTEC 5, 7SJ82/7SJ85, Manual 145


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[scGPS_2, 2, --_--]

Figure 3-69 Checking the Setting Value for the 2nd Pulse Using the GPSMON32 Program, Step 2

3.6.3.8 Routing Information in DIGSI 5


Protection communications of the same type form a topology.
For more information on this, see chapter 3.6.3.3 Function Description.
A data bar is exchanged between the devices of a topology connected via protection communication. This can
be written into or read from by the devices. This can be used for exchanging various signals between the
devices. In this case, each signal demands a certain number of data fields.

[dwdatenl-100113-01.tif, 1, en_US]

Figure 3-70 Data Bar Exchanged Between Devices

The data bar is divided into 3 priorities, which also have different transmission rates and data volumes.
The following basic principle applies for all messages: Only pure data contents are transmitted. The quality (for
example, Valid) is not automatically transmitted as well. If you want to transmit the quality as well (for
example, for further processing of GOOSE messages), the quality must be transmitted separately (for example,
by using CFC). If a signal that has a test flag is transmitted (because its function is in test mode, for example),
all signals are provided with a test flag on the receiving side. If the connection is broken, all received signals
are flagged with the quality Invalid. If desired, the value can also be set to a secure state after a selectable
dropout time, or the last value received can be retained (Hold setting). This can be configured separately for
each received signal (see Table 3-16).

NOTE

i For ACT type signals, only the phase information is transmitted.

Indications that are transferred data fields of priority 1 are sent with every telegram. They are preferably used
for the transmission of rapid signals, for example, release for circuit-breaker intertripping. A strictly determin-
istic, rapid transmission is required there.
Signals of priority 2 are transmitted with at least every 2nd telegram. For bit rates >256 kbit/s, there are no
differences between priority 1 and priority 2.
Priority 3 information is transmitted at least every 100 ms. This priority is used for transmission of measured
and metered values. Complex values must be routed separately as the real and the imaginary part for trans-
mission. Measured-value thresholds that lead to an updating of a measured value are set centrally as a prop-
erty of the measured value. These measured-value thresholds apply with the corresponding reporting, for
example, also for the transfer via IEC 61850 to a substation automation technology.
Indications which are written to a data area x under a priority on the data bar must be routed to an indication
of the same type in the device reading this information. Otherwise, they are processed incorrectly on the
receiving side. The data bar is organized in terms of bits. For information on the bit requirement of each signal
type, refer to Table 3-15.

146 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Table 3-13 and Table 3-14 show the number of data areas in the data bar in relation to the available baud
rate.

NOTE

i The Lowest appearing bit rate parameter, which has to be set in each device for the protection
interfaces of a topology, defines the number of data areas as well as the topology type.

If, for example, in a three-end constellation with a type 2 chain topology two devices are connected via direct
optical fibers and 2 devices via the 64-kbit/s weakest line, the 64-kbit/s section is the limiting factor for the
entire constellation.

Table 3-13 Available Bits - Minimum Constellation Baud Rate 64/128 kbit/s

Priority 1 Priority 2 Priority 3


Type 1 8 bits 24 bits 128 bits
Type 2 32 bits 64 bits 256 bits

Table 3-14 Available Bits - Minimum Constellation Baud Rate 512/2048 kbit/s

Priority 1 Priority 2 Priority 3


Type 1 48 bits 128 bits 384 bits
Type 2 96 bits 200 bits 1024 bits

Table 3-15 Requirement in Bits

Signal Type Size in Bits


SP (single-point indication) 1 bit
DP (double-point indication) 2 bits
IN (metered values) 32 bits
MW (measured values)6 32 bits
ACT 4 bits

Table 3-16 Possible Dropout Values

Signal Type Dropout Values


SP (single-point indication) Outgoing, Incoming, Hold
DP (double-point indication) On, Off, Intermediate Position, Disturbed Position,
Hold
IN (metered values) 0, Hold
MW (measured values) 0, Hold
ACT Hold

NOTE

i If the protection link fails, these values can be set on the receiver side.

EXAMPLE
2 devices are connected via a 64-kbits channel. This is a type 1 topology. 8 bits are freely available for priority
1. Now, for example, 4 SPS and 2 DPS can be routed:
4 x 1 bit + 2 x 2 bits = 8 bits

6 The complex phasors of a measuring point are pre-routed

SIPROTEC 5, 7SJ82/7SJ85, Manual 147


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

NOTE

i Measured values are transmitted as primary values.

EXAMPLE

For the rated current display in the receiving device


When Irated = 1000 A in the transmitting device and ILoad = 200 A, the number 200 is displayed in the receiving
device.

Remote Data Transmission: Routing of the Indications and Measured Values to the Protection Interface
The transmission is organized in the form of a data bar which is continuously exchanged between the devices.
For this, see Figure 3-70.
A device indication or measured value is allocated to a definite data area of the bar.
Figure 3-71 to Figure 3-74 show the routing for a communication topology of protection interface type 1.
To transmit signals to other devices, these signals must be routed in the communication matrix under
Transmit. Binary inputs 1 and 2 are single-point indications (SPS) and are routed to position 1 and position 2
of the transmission with the highest priority (priority 1). For 64 kbit/s, for example, only 8 of these data areas
are available for type 1; they are exchanged between the transmission routes with each telegram. Signals 3
and 4 are double-point indications (DPS), for example, a switch position that is transmitted by a device 1. A
double-point indication occupies 2 positions on the data bar. In addition, a measured and metered value are
communicated via priority 3.
As a measured or metered value uses 32 bits, value 2 starts at position 33. DIGSI 5 indicates the next available
position.

[scransps-021210-01.tif, 1, en_US]

Figure 3-71 Routing of Single-Point Indications to the Protection Interface in Device 1

148 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[scrangmw-021210-01.tif, 1, en_US]

Figure 3-72 Routing of Measured Values to the Protection Interface in Device 1

[scrangzw-021210-01.tif, 1, en_US]

Figure 3-73 Routing of Metered Values to the Protection Interface in Device 1

This device also receives information (in the matrix under Receive). This must have been routed as a target for
other devices (see next figure). The binary outputs 1 and 2 in device 1 receive their information via the protec-
tion interface. This is priority 1 information, which has been routed in another device to position 3 and 4 of
the data bar. The secure state is defined in the Fallback value column. If the data connection fails, the single-
point indication is reset to coming or going or its value is retained (hold). For data of the various priorities,
you can also set a dropout time after which the reset (see Figure 3-73) to the fallback value occurs, in order to
retain the original state for a short time in the event of brief interruptions. These 3 dropout times apply for all
data of one transmission priority and are set as parameters.

SIPROTEC 5, 7SJ82/7SJ85, Manual 149


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[scspsemp-021210-01.tif, 1, en_US]

Figure 3-74 Routing of Single-Point Indications (Receive) to the Protection Interface in Device 1

The following figure shows the routing in the 2nd device. Binary inputs 1 and 2 are routed with priority 1 to
positions 3 and 4 there. In device 1, positions 1 and 2 are already occupied (see Figure 3-71). If you also route
the signals to positions 1 and 2, the signals of the devices are then connected to the corresponding position
with a logical OR operation. If measured and metered values are routed in the same data areas, this results in
implausible values for the receivers that read the data. As a user, you are therefore responsible for the correct
routing.

[scbaspsr-021210-01.tif, 1, en_US]

Figure 3-75 Routing of Single-Point Indications to be Sent to the Protection Interface in Device 2

The binary outputs 1 and 2 (Receive) in the 2nd device are connected to priority 1 signals 1 and 2 from the
1st device. This takes place via the data areas at positions 1 and 2 of the data bar, which transfer the state of
the indications. Other devices can also read this information and link it to their internal signals. Here, too, the
secure state, which is assumed when the protection connection is interrupted, is entered. This state depends
on the information. In the case of single-point indications, the state is 0 or 1. In the case of double-point indi-
cations, the bit combinations 00, 01, 10, or 11 are possible, in order to directly signal a disturbed position
upon failure of the data connection, for example.
Hold is used to retain the state.

150 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[scbausps-021210-01.tif, 1, en_US]

Figure 3-76 Routing of Received Single-Point Indications to the Protection Interface in Device 2

[scbausmw-021210-01.tif, 1, en_US]

Figure 3-77 Routing of Received Measured Values to the Protection Interface in Device 2

[scbauszw-021210-01.tif, 1, en_US]

Figure 3-78 Routing of Metered Values to the Protection Interface in Device 2

3.6.3.9 Diagnostic Measured Values of the Protection Interface


The following diagnostic data is provided via the protection interfaces by the devices in the constellation:

• Address of the device in the constellation

• Circuit-breaker switch position (open/closed/undefined) (only for protection interfaces of type 1)

• Availability of protection-interface communication within the last minute, as percentage


Availability of protection-interface communication within the last hour, as percentage

• Time delay in the send and receive direction of the telegrams between local and neighboring device
You can find this diagnostic data in DIGSI under the following menu structure (see Figure 3-79):

SIPROTEC 5, 7SJ82/7SJ85, Manual 151


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[sc_diagnose_wskanäle_geräteadresse, 2, en_US]

Figure 3-79 Protection-Interface Channel Diagnostic Data – Device Address

NOTE

i You can use the following procedure to reset the measured values for the protection interface directly in
the device:
Device functions > x Device protection comm. > Protection interface y > Reset measured values.

Output Signals of the Protection Interface


Each individual protection interface provides the following indications for commissioning and diagnosing
communication:

152 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Indication Description
(_:5161:301) Status The output signal gives you information about the state of communication layers
of lay. 1 and 2 1 and 2 (1: Physical Layer, 2: Data Link Layer). The following indications values
are possible:

• initialized:
The protection interface is not connected and is in the Initial state.
• PI connected:
The protection interface is connected to the protection interface of a device.
• PI data fault:
The protection interface has not received any valid telegrams for the time
set in the parameter (_:5161:107) Disturbance alarm after.
• PI data failure:
The protection interface has not received any valid telegrams for the time
set in parameter (_:5161:108) Transm. fail. alarm after .

not existing:
The protection interface has not been assigned to a communication
channel.
(_:5161:302) Status The output signal gives you information about the state of communication layers
of lay. 3 and 4 3 and 4 (3: Network Layer, 4: Transport Layer). The following indications values
are possible:

• no error:
The protection interface is operating correctly.
• SW ver.incomp.:
The firmware versions of the connected devices are incompatible. Update
the firmware.
• wrong dev. ID:
The device address of the partner device is incorrect. Check the settings for
parameters Address of device 1 to address of device n
(_:5131:102 and following).
• const.sett.error:
Check that the same setting has been made for parameter (_:5131:122)
Lowest appearing bit rate in all devices.
• diff.sett error:
The line differential protection settings for the connected devices are incom-
patible. Check whether both devices are set to operate with or without line
differential protection.
The rated current of the line (parameter (_:9001:101) Rated
current) must be set equal at all ends of the line.
If a transformer is installed in the line, the rated apparent power
(_:9001:103) Rated apparent power must be set equal at all ends
of the line.
• Rec. own telegr.
The protection interface is receiving its own data. Check the wiring.
• wrong dev. idx.
The device index in the partner device is wrong. Check the setting of param-
eter (_:5131:101) Local device is device in the partner device.

In order to clarify faults, each individual protection interface provides the following binary signals:

SIPROTEC 5, 7SJ82/7SJ85, Manual 153


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Binary Output Signal Description


(_:5161:303) Signal Connection broken indicates that during a parameterized time (param-
Connection broken eter (_:5161:107) Disturbance alarm after) faulty or missing tele-
grams were continuously received. If the 'Connection interrupted' indication
occurs, the affected protection interface link will be terminated. This can cause
the blocking of an active differential protection or a ring topology can change to
a chain topology.
(_:5161:316) Error Signal Error rate / min exc. indicates that the set maximum error rate per
rate / min exc. minute (parameter (_:5161:106) Max. error rate per min) has been
exceeded.
(_:5161:317) Error Signal Error rate / hour exc. indicates that the set maximum error rate
rate / hour exc. per hour (parameter (_:5161:105) Max. error rate per hour) has
been exceeded.
(_:5161:318) Time Signal Time delay exceeded indicates that the threshold value for the set
delay exceeded signal-transit time (parameter (_:5161:109) Delay time threshold) has
been exceeded.
(_:5161:319) Time Signal Time delay different indicates that the threshold value for asym-
delay different metrical transit times has been exceeded. The setting value results from the
setting value of the parameter (_:5161:110) Difference Tx and Rx
time.
(_:5161:320) Time Signal Time delay jump indicates that the data transit times changed
delay jump abruptly. This is caused by switching the communication path in the communica-
tion network.
(_:5161:321) PI Signal PI synchronized indicates that the protection-interface connection is
synchronized synchronized with the opposite end.
(_:5161:340) Tele- Signal Telegram lost indicates that an expected telegram has failed to arrive
gram lost or a faulty telegram has been received.
If you would like to allocate the communications failures or faults to other events,
move the signal Telegram lost temporarily into the operational log. Such
events can be switching operations in the primary system or operations on the
components of the communication network.
Note: If the signal is constantly routed, the operational log can overflow. Siemens
recommends routing the signal only for clarification of faults.

Measured Values of the Protection Interface


The protection interface provides the following measured value to diagnose the protection interface commu-
nication:
Measured Value Description
(_:5161:308) Tx Telegrams sent during the last hour
tel/h
(_:5161:309) Rx Telegrams received during the last hour
tel/h
(_:5161:310) Tx Telegrams sent during the last minute
tel/min
(_:5161:311) Rx Telegrams received during the last minute
tel/min
(_:5161:312) Tx Transmission failure rate during the last hour
err/h
(_:5161:313) Rx Receive error rate during the last hour
err/h
(_:5161:314) Tx Transmission failure rate during the last minute
err/min

154 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Measured Value Description


(_:5161:315) Rx Receive error rate during the last minute
err/min
(_:5161:325) Mean signal-transit time (average value of the transit time in transmission and
Aver.Δt reception direction divided by 2, without GPS synchronization)
(_:5161:326) Rec. Signal-transit time in reception direction (with GPS synchronization)
Δt
(_:5161:327) Sen. Signal-transit time in transmission direction (with GPS synchronization)
Δt
(_:5161:334) Number of telegram failures within the last minute
Miss.tel/min
(_:5161:335) Number of telegram failures within the last hour
Miss.tel/h
(_:5161:336) Number of telegram failures within the last day
Miss.tel/d
(_:5161:337) Number of telegram failures within the last week
Miss.tel/w
(_:5161:338) M. Longest lasting telegram failure within the last day
loss/d
(_:5161:339) M. Longest lasting telegram failures within the last week
loss/w

NOTE

i You can reset the measured values of the protection interface directly in the device. Proceed as follows:
Device functions > x Device protection comm. > Protection interface y > Reset measured values.

3.6.3.10 Diagnostic Data for the Protection Interface

Diagnostic Data of the Channel in DIGSI 5


Different diagnostic data can be read with DIGSI 5.
For this, connect with the device via DIGSI 5 and query the device information. Diagnostic data for a module
whose channel is configured with the protection interface can be received by selecting the module slots (for
example, F) and the corresponding channel (1 or 2). The following figures show the extensive diagnostic data
for the protection interface. It is particularly helpful if data failures occur or other irregularities in a communi-
cation connection (for example, transmission time fluctuations).

NOTE

i The diagnostic data can also be read via the device control on the display of the device. The overview of
DIGSI 5 does not offer this option, however.

The following table describes the displays.

SIPROTEC 5, 7SJ82/7SJ85, Manual 155


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[scdiapin-140912-01, 1, en_US]

Figure 3-80 Diagnostic Data of a Channel Configured with the Protection Interface

Table 3-17 Description of the Diagnostic Data under Protection Interface

Channel Type Name Values Description - Diagnostic


Information for Log PI
Protection interfaces - log Status Initial, Running, Error Runtime status of the log
Protection interfaces - log Build Date/time Date and time of the log
version

Diagnostic Data of the Protection-Interface Log in DIGSI 5


The following figures and tables describe the displays of the protection-interface log.

[scdiamed-140912-01, 1, en_US]

Figure 3-81 Diagnostic Data of the Protection-Interface Log - Media Status

156 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Table 3-18 Description of Diagnostic Data under Media Status

Protection Interfaces - Log Name Values Description - Media Status


Type Interface (in Direction of
Outside Interface)
Media Status Baudrate 64 kbit/s; 128 kbit/s; HDLC baud rate:
512 kbit/s; 2048 kbit/s; FO: 64 kbit/s to 2048 kbit/s
30 Mbit/s; <unknown> for 820-Nm USART modules
LDFO: 30 Mbit/s for 1300-
Nm/1500-Nm long-distance
modules
Error case: <unknown>
Media Status LinkState N/A, UP, DOWN FO: N/A (always display N/A)
Media Status TransceiverDetection N/A, NO Transceiver FO: N/A (always N/A)
detected, Transceiver (NO Transceiver detected,
detected Transceiver detected),
Error case: N/A

[scdiacom-140912-01, 1, en_US]

Figure 3-82 Diagnostic Data of the Protection-Interface Log - HDLC (Log - Layer)

SIPROTEC 5, 7SJ82/7SJ85, Manual 157


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Table 3-19 Description of Diagnostic Data of the Protection-Interface Log - HDLC (Log - Layer)

Protection Interfaces - Log Name Values Description - HDLC Link


Type Layer Diagnostic Informa-
tion (in Direction of
Outside Interface)
HDLC RXHPFramesOK Number of corresponding Incoming telegrams, high
frames (16 bit counter) priority, OK
HDLC RXLPFramesOK Number of corresponding Incoming telegrams, low
frames (16 bit counter) priority, OK
HDLC RXHPFramesERR Number of corresponding Incoming telegrams, high
frames (16 bit counter) priority, faulty
HDLC RXLPFramesERR Number of corresponding Incoming telegrams, low
frames (16 bit counter) priority, faulty
HDLC TXHPFramesOK Number of corresponding Sending telegrams, high
frames (16 bit counter) priority, OK
HDLC TXLPFramesOK Number of corresponding Sending telegrams, low
frames (16 bit counter) priority, OK
HDLC TXHPFramesERR Number of corresponding Sending telegrams, high
frames (16 bit counter) priority, faulty
HDLC TXLPFramesERR Number of corresponding Sending telegrams, low
frames (16 bit counter) priority, faulty
HDLC Bridge Details Sub-nodes Sub-nodes Siemens-internal special
diagnostic for fault search

158 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

[scdiahdl-140912-01, 1, en_US]

Figure 3-83 Diagnostic Data of the Protection-Interface Log - COM Interface (Internal COM Link Interface
Between Module and Mainboard)

Table 3-20 Description of Diagnostic Data of the COM Interface (Internal COM Link Interface Between
Module and Mainboard)

Protection Interfaces - Log Name Values Description - COM Interface


Type Layer Diagnostic Informa-
tion
(Internal COM Link Inter-
face in Mainboard Direc-
tion)
COM interface RXHPFramesOK Number of corresponding Incoming telegrams, high
frames (16 bit counter) priority, OK
COM interface RXLPFramesOK Number of corresponding Incoming telegrams, low
frames (16 bit counter) priority, OK
COM interface RXHPFramesERR Number of corresponding Incoming telegrams, high
frames (16 bit counter) priority, faulty
COM interface RXLPFramesERR Number of corresponding Incoming telegrams, low
frames (16 bit counter) priority, faulty

SIPROTEC 5, 7SJ82/7SJ85, Manual 159


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Protection Interfaces - Log Name Values Description - COM Interface


Type Layer Diagnostic Informa-
tion
(Internal COM Link Inter-
face in Mainboard Direc-
tion)
COM interface TXHPFramesOK Number of corresponding Sending telegrams, high
frames (16 bit counter) priority, OK
COM interface TXLPFramesOK Number of corresponding Sending telegrams, low
frames (16 bit counter) priority, OK
COM interface TXHPFramesERR Number of corresponding Sending telegrams, high
frames (16 bit counter) priority, faulty
COM interface TXLPFramesERR Number of corresponding Sending telegrams, low
frames (16 bit counter) priority, faulty
COM interface Bridge Details Sub-nodes Sub-nodes Siemens-internal special
diagnostic for fault search

Table 3-21 Description of Diagnostic Data of some Setting Values of the Protection Interface

Protection Interfaces - Log Name Values Description - Protection


Type Interface Setting Values
Settings Connection via Integer number - display of Protection interface is
the internal coding of the Connection via
settings variant
Settings PDI bandwidth Bit-rate display Bit rate (bit/s) for protection
telegrams depending on the
parameter Connection
via
Settings PDI Telegram.Overhead Display of bits Overhead for every protec-
tion telegram in bit.

3.6.3.11 Settings

Addr. Parameter C Setting Options Default Setting


Device combin.
_:5131:102 Device combin.:Address 1 to 65534 101
of device 1
_:5131:103 Device combin.:Address 1 to 65534 102
of device 2
_:5131:104 Device combin.:Address 1 to 65534 103
of device 3
_:5131:105 Device combin.:Address 1 to 65534 104
of device 4
_:5131:106 Device combin.:Address 1 to 65534 105
of device 5
_:5131:107 Device combin.:Address 1 to 65534 106
of device 6
_:5131:101 Device combin.:Local 1 to 6 1
device is device
_:5131:122 Device combin.:Lowest • 64 kBit/s 64 kBit/s
appearing bit rate
• 128 kBit/s
• 512 kBit/s
• 2048 kBit/s

160 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

Addr. Parameter C Setting Options Default Setting


_:5131:125 Device combin.:Number 2 to 6 6
of devices
Prot. interf.1
_:5161:1 Prot. interf.1:Mode • off on
• on
_:5161:105 Prot. interf.1:Max. error 0.000 % to 100.000 % 1.000 %
rate per hour
_:5161:106 Prot. interf.1:Max. error 0.000 % to 100.000 % 1.000 %
rate per min
_:5161:107 Prot. interf.1:Distur- 0.05 s to 2.00 s 0.10 s
bance alarm after
_:5161:108 Prot. interf.1:Transm. 0.0 s to 6.0 s 6.0 s
fail. alarm after
_:5161:109 Prot. interf.1:Delay time 0.1 ms to 30.0 ms 30.0 ms
threshold
_:5161:110 Prot. interf.1:Difference 0.000 ms to 3.000 ms 0.100 ms
Tx and Rx time
_:5161:113 Prot. interf.1:PPS • telegr. and PPS PPS sync. off
synchronization
• telegr. or PPS
• PPS sync. off

3.6.3.12 Information List

No. Information Data Class Type


(Type)
Channel 1
_:307 Prot.interface:Health ENS O
_:304 Prot.interface:Channel Live SPS O
Device combin.
_:5131:52 Device combin.:Behavior ENS O
_:5131:53 Device combin.:Health ENS O
_:5131:301 Device combin.:Status of topo. recog. ENS O
_:5131:302 Device combin.:Topology is ENS O
_:5131:303 Device combin.:Devices form ENS O
_:5131:304 Device combin.:Number of detect. dev. INS O
_:5131:305 Device combin.:Fct. logout device 1 SPS O
_:5131:306 Device combin.:Fct. logout device 2 SPS O
_:5131:307 Device combin.:Fct. logout device 3 SPS O
_:5131:309 Device combin.:Fct. logout device 4 SPS O
_:5131:310 Device combin.:Fct. logout device 5 SPS O
_:5131:311 Device combin.:Fct. logout device 6 SPS O
_:5131:312 Device combin.:Device 1 available SPS O
_:5131:313 Device combin.:Device 2 available SPS O
_:5131:314 Device combin.:Device 3 available SPS O
_:5131:315 Device combin.:Device 4 available SPS O
_:5131:316 Device combin.:Device 5 available SPS O
_:5131:317 Device combin.:Device 6 available SPS O
Prot. interf.1
_:5161:81 Prot. interf.1:>Block stage SPS I

SIPROTEC 5, 7SJ82/7SJ85, Manual 161


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

No. Information Data Class Type


(Type)
_:5161:500 Prot. interf.1:>Sync reset SPS I
_:5161:341 Prot. interf.1:Reset synchronization SPC C
_:5161:342 Prot. interf.1:Reset measurements SPC C
_:5161:52 Prot. interf.1:Behavior ENS O
_:5161:53 Prot. interf.1:Health ENS O
_:5161:301 Prot. interf.1:Status of lay. 1 and 2 ENS O
_:5161:302 Prot. interf.1:Status of lay. 3 and 4 ENS O
_:5161:303 Prot. interf.1:Connection broken SPS O
_:5161:316 Prot. interf.1:Error rate / min exc. SPS O
_:5161:317 Prot. interf.1:Error rate / hour exc. SPS O
_:5161:318 Prot. interf.1:Time delay exceeded SPS O
_:5161:319 Prot. interf.1:Time delay different SPS O
_:5161:320 Prot. interf.1:Time delay jump SPS O
_:5161:321 Prot. interf.1:PI synchronized SPS O
_:5161:340 Prot. interf.1:Telegram lost SPS O
_:5161:308 Prot. interf.1:Tx tel/h MV O
_:5161:309 Prot. interf.1:Rx tel/h MV O
_:5161:310 Prot. interf.1:Tx tel/min MV O
_:5161:311 Prot. interf.1:Rx tel/min MV O
_:5161:312 Prot. interf.1:Tx err/h MV O
_:5161:313 Prot. interf.1:Rx err/h MV O
_:5161:314 Prot. interf.1:Tx err/min MV O
_:5161:315 Prot. interf.1:Rx err/min MV O
_:5161:334 Prot. interf.1:Miss.tel/min MV O
_:5161:335 Prot. interf.1:Miss.tel/h MV O
_:5161:336 Prot. interf.1:Miss.tel/d MV O
_:5161:337 Prot. interf.1:Miss.tel/w MV O
_:5161:338 Prot. interf.1:M. loss/d MV O
_:5161:339 Prot. interf.1:M. loss/w MV O
_:5161:331 Prot. interf.1:Recept. MV O
_:5161:323 Prot. interf.1:PPS: time del. unsym. SPS O
_:5161:324 Prot. interf.1:PI with PPS synchron. SPS O
_:5161:325 Prot. interf.1:Aver.Δt MV O
_:5161:326 Prot. interf.1:Rec. Δt MV O
_:5161:327 Prot. interf.1:Sen. Δt MV O
Ext. Synchron.
_:9181:500 Ext. Synchron.:>Block stage SPS I
_:9181:501 Ext. Synchron.:>PPS pulse loss SPS I
_:9181:301 Ext. Synchron.:PPS pulse loss SPS O
_:9181:302 Ext. Synchron.:PPS pulse SPS O
Meas.val.dev.1
_:1351:6811:300 Meas.val.dev.1:Dev.adr. INS O
_:1351:6811:301 Meas.val.dev.1:CB ENS O
_:1351:6811:302 Meas.val.dev.1:Vph WYE O
_:1351:6811:303 Meas.val.dev.1:Iph WYE O

162 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.6 Protection Communication

No. Information Data Class Type


(Type)
Meas.val.dev.2
_:1351:6841:300 Meas.val.dev.2:Dev.adr. INS O
_:1351:6841:301 Meas.val.dev.2:CB ENS O
_:1351:6841:302 Meas.val.dev.2:Vph WYE O
_:1351:6841:303 Meas.val.dev.2:Iph WYE O
Meas.val.dev.3
_:1351:6871:300 Meas.val.dev.3:Dev.adr. INS O
_:1351:6871:301 Meas.val.dev.3:CB ENS O
_:1351:6871:302 Meas.val.dev.3:Vph WYE O
_:1351:6871:303 Meas.val.dev.3:Iph WYE O
Meas.val.dev.4
_:1351:6901:300 Meas.val.dev.4:Dev.adr. INS O
_:1351:6901:301 Meas.val.dev.4:CB ENS O
_:1351:6901:302 Meas.val.dev.4:Vph WYE O
_:1351:6901:303 Meas.val.dev.4:Iph WYE O
Meas.val.dev.5
_:1351:6931:300 Meas val.dev.5:Dev.adr. INS O
_:1351:6931:301 Meas val.dev.5:CB ENS O
_:1351:6931:302 Meas val.dev.5:Vph WYE O
_:1351:6931:303 Meas val.dev.5:Iph WYE O
Meas.val.dev.6
_:1351:6961:300 Meas.val.dev.6:Dev.adr. INS O
_:1351:6961:301 Meas.val.dev.6:CB ENS O
_:1351:6961:302 Meas.val.dev.6:Vph WYE O
_:1351:6961:303 Meas.val.dev.6:Iph WYE O

SIPROTEC 5, 7SJ82/7SJ85, Manual 163


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.7 Date and Time Synchronization

3.7 Date and Time Synchronization

3.7.1 Overview of Functions

Timely recording of process data requires precise time synchronization of the devices. The integrated date/
time synchronization allows the exact chronological assignment of events to an internally managed device
time that is used to time stamp events in logs, which are then transmitted to a substation automation tech-
nology or transferred via the protection interface. A clock module internal to the device and having battery
backup is synchronized cyclically with the current device time so that the right device time is available and
used even in case of auxiliary-voltage failure. At the same time, this permits hardware-supported monitoring
of the device time.

3.7.2 Structure of the Function

The integrated date/time synchronization is a supervisory device function. Setting parameters and indications
can be found in the following menus for the DIGSI and the device:
Set date and time:

• DIGSI: Online access -> Interface -> Device -> Device Information -> Time Information

• Device: Main menu → Device functions → Date & Time


Parameter:

• DIGSI: Project -> Device -> Parameter -> Time Settings


Indications:

• DIGSI: Project -> Device -> Information routing ->Time keeping or Time Sync.

3.7.3 Function Description

Every SIPROTEC 5 device maintains an internal device time with date. The date and time can also be set on the
device via the on-site operation panel or via DIGSI 5. Within a system, or even beyond, it is usually necessary to
record the time of process data accurately and to have exact time synchronization of all devices. For SIPROTEC
5 devices, the sources of time and synchronization options can be configured.

Configurable Synchronization Options:

• None (default setting)


The device functions without any external time synchronization. The internal time synchronization
continues to work with the help of the back-up battery even when the auxiliary voltage is shut down
temporarily. The time can be adjusted manually.

• Telegram
The time is synchronized via a telegram with an appropriately configured communication interface in
accordance with the IEC 60870-5-103 or DNP3 protocol.

• Connection to a radio clock


The time synchronization takes place with the set time telegram from an external IRIG-B or DCF77
receiver via the time synchronization interface of the device.

• Ethernet
The time synchronization is done via Ethernet-based SNTP protocol (Simple Network Time Protocol), for
example with IEC 61850 stations or via IEEE 1588. If you enable both services during configuration of
Ethernet interfaces, these protocols are available as an option for the time synchronization.

164 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.7 Date and Time Synchronization

• Protection interface
The time synchronization takes place via the protection interfaces configured for your SIPROTEC 5 device.
Here, the timing master takes over the time management.

Configurable Time Sources:

• 2 time sources can be taken into consideration with the SIPROTEC 5 devices. For each time source, the
synchronization type may be selected based on the options provided.

• Time source 1 takes precedence over Time source 2, that is, Time source 2 will be effective for
the synchronization of the device time only if Time source 1 fails. If only one time source is available
and it fails, then only the internal clock continues unsynchronized. The status of the time sources is indi-
cated.

• For every time source, it is possible to define via the Time zone time source 1 parameter (or Time
zone time source 2) if this source transmits its time by UTC (universal time) or if the settings corre-
spond to the local time zone of the device.

NOTE

i Make sure that the settings for the time sources coincide with the actual hardware configuration of your
SIPROTEC 5 device. In any event, incorrect settings cause the status indications of time sources to pick up.

Configurable Date Format


Regardless of a feed time-synchronization source, a uniform format is maintained internally within the device.
The following options are available for the customary local representation of the date format:

• Day.Month.Year: 24.12.2009

• Month/Day/Year: 12/24/2009

• Year-Month-Day: 2009-12-24

Taking Local Time Zones into Account


The internal device time is maintained in universal time (UTC). To display time stamps in DIGSI and on the
device display, you can define the local time zone of the device (parameter Offset time zone for GMT),
including the applicable daylight saving times (start, end, and offset of daylight saving time) using parame-
ters. This allows the display of the local time.

NOTE

i • For time sources that transmit the status of the switch to daylight saving time, this will be taken into
account automatically when creating the internal device time in the UTC format. The differential time
of the daylight saving time set in the device (parameter Offset daylight saving time) is taken into
consideration. However, in contrast, the settings of the start of daylight saving time and end of the
daylight saving times are ignored when converting into the device internal UTC format.

• For active time sources, it is not possible to set the time via the device display or DIGSI 5. An exception
is setting the calendar year for active time protocol IRIG-B.

Status, Supervision, and Indications of Time Management


Your SIPROTEC 5 device generates status and monitoring indications that provide important information
regarding the correct configuration of the time source and the status of the internal time management during
start-up and device operation.
Internal time synchronization is monitored cyclically. Important synchronization processes, the status of the
time sources and errors detected are reported. A device time that has become invalid will be marked accord-
ingly so that affected functions can go to a safe state.

SIPROTEC 5, 7SJ82/7SJ85, Manual 165


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.7 Date and Time Synchronization

Indication Description
Device: This indication signals a high difference between the
Clock fail internally managed time and the time of the clock
module that is not permissible. The pickup of the indi-
cation can point to a defect in the clock module or to
an unacceptable high drift of the system quartz
crystal. The time maintained internally is marked as
invalid.
Time management: This indication signals whether daylight saving time
Daylight saving time has been enabled.
Time management: This indication signals that the device time has been
Clock set manually set manually via the on-site operation panel or via
DIGSI 5.
Time synchronization: These 2 indications signal whether the active time
Status time source 1 sources are recognized as valid and active from the
Status time source 2 device point of view. When the indications pick up, it
can also be an indication that an incorrect configura-
tion of the port or channel numbers was done at the
on-site operation panel.
Time synchronization: This indication signals after the parameterized time
Time sync. error Fault indication after that synchronization
using an external time source has failed.
Time synchronization: This indication signals that a Leap second has
Leap second occurred during time synchronization using an
external GPS receiver (protocol variant IRIG-B
005(004) with extension according to IEEE
C37.118-2005).
Time synchronization: This indication signals that the device is synchronized
High accuracy with an accuracy better than 1 μs The indication is
only of significance when the PMU function is used.

NOTE

i In case of a missing or discharged battery, the device starts without active external time synchronization
with the device time 2011-01-01 00:00:00 (UTC).

For the device, DIGSI 5 provides a compact overview of the status of the time synchronization of your
SIPROTEC 5 device in online mode. All displays are updated continuously. You can access the overview in the
project-tree window via Online access.
DIGSI: Online access -> Interface -> Device -> Device Information -> Time Information

166 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.7 Date and Time Synchronization

[sctimedg-220415, 1, en_US]

Figure 3-84 Time Information in DIGSI

For every time source, you see the following:

• Last received time (with date)

• Receipt time of the last received time telegram

• Configured type of timer

• Indication of timer outage or failure

• Whether the device time is currently synchronized from the time source
The lower section displays the device time, which is continuously updated. If the internal device time and the
infeed time source were synchronous at the time of telegram receipt, both displayed times are identical.

NOTE

i All times displayed (also the time source) take into consideration the local time settings (zone and daylight
saving time of the device) in the form of a numerical offset for UTC (universal time).

3.7.4 Application and Setting Notes

Parameter: Date Format

• Default setting Date format = YYYY-MM-DD


With the Date format parameter, you define the local customary format of the date display.
Parameter Value Description
YYYY-MM-DD Day.Month.Year: Typical European display
Example: 24.12.2010
YYYY-MM-DD Month/Day/Year: Typical US representation
Example: 12/24/2010
YYYY-MM-DD Year-Month-Day: Typical Chinese display
Example: 2010-12-24

Parameter: Time zone time source 1,Time zone time source 2

• Default setting Time zone time source 1 = local, Time zone time source 2 = local
With the Time zone time source 1 and Time zone time source 2 parameters, you define the
handling of time zones of the external timer.

SIPROTEC 5, 7SJ82/7SJ85, Manual 167


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.7 Date and Time Synchronization

Parameter Value Description


local Local time zone and daylight saving time are considered as time zone offsets to
GMT.
UTC Time format according to UTC (universal time)

Parameter: Time source 1,Time source 2

• Default setting Time source 1 = none, Time source 2 = none


With the Time source 1 and Time source 2 parameters, you can configure an external timer. The
prerequisite is to have the corresponding hardware configuration of the communication interfaces of your
SIPROTEC 5 device. This is listed as a prefix when making a selection in DIGSI 5.
Parameter Value Description
none The time source is not configured.
IRIG-B Time synchronization by an external GPS receiver:
SIPROTEC 5 devices support several protocol variants of the IRIG-B standards:

• IRIG-B 002(003)
The control function bits of the signal are not occupied. The missing year is
formed from the current device time. In this case, it is possible to set the
year via the online access in DIGSI 5.
• IRIG-B 006(007)
The bits for the calendar year are not equal to 00. The calendar year is set
automatically by the time protocol.
• IRIG-B 005(004) with extension according to IEEE C37.118-2005
If, in the time signal, other control function bits are occupied in addition to
the calendar year, then the device takes the additional information into
consideration for leap seconds, daylight saving time, time offset (zone,
daylight saving time) and time accuracy.
Time zone time source 1 or Time zone time source 2: The
value of this setting is not evaluated by the device, since this protocol
either transmits or in the case of local time, specifies the appropriate offset
to UTC in each set time telegram.
DCF77 Time synchronization by an external DCF 77 receiver
Time zone time source 1 or Time zone time source 2 = local
Please note: There are also clocks that generate a DCF 77 signal representing
UTC. In this case, UTC must be set.
PI The time synchronization takes place via the protection interfaces configured
for your SIPROTEC 5 device. Here, the timing master takes over the time
management. Signal-transit times of the protection interface communication
are calculated automatically.
Time zone time source 1 or Time zone time source 2 = UTC
A slave that receives a time or a SIPROTEC 5 master, receives its system time
kept in UTC.

168 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.7 Date and Time Synchronization

Parameter Value Description


SNTP The time synchronization is done via the Ethernet service SNTP (SNTP server or
via IEC 61850).
SIPROTEC 5 devices support both Edition1 and Edition2 in accordance with
IEC 61850-7-2. In Edition2, the logical attributes LeapSecondsKnown, ClockFai-
lure, ClockNotSynchronized, and the value TimeAccuracy are maintained in
each time stamp. For Edition1, these signals contain default settings. Thus, the
interoperability for substation automation technology is ensured for both
editions!
The SNTP service must be enabled during configuration of Ethernet interfaces
so that it is available as an option for the time synchronization.
Time zone time source 1 or Time zone time source 2 = UTC
IEC 60870-5-103 The time is synchronized via telegram with an appropriately configured
communication interface in accordance with the IEC 60870-5-103 protocol.
Time zone time source 1 or Time zone time source 2 = local
However, there are also T103 systems that send the UTC.
DNP3 The time is synchronized via telegram with the appropriately configured
communication interface in accordance with the DNP3 protocol.
Two characteristics are supported in the process:

• Time synchronization via UTC


• Time synchronization with local time
The daylight saving time status is not transmitted. The device assumes that
the DNP3 master follows the same rules for the start and end of the
daylight saving time as those that were set for the device.
Time zone time source 1 or Time zone time source 2 = UTC is
the current implementation, local concerns older implementations.
IEEE 1588 Time is synchronized via an IEEE 1588 timing master. In this case, SIPROTEC 5
devices operate as slave-only clocks. IEEE 1588 v2 is supported with P2P and
Ethernet Transport.
The IEEE 1588 service must be enabled during configuration of Ethernet inter-
faces so that it is available as an option for the time synchronization.
Time zone time source 1 or Time zone time source 2 = UTC.

Parameter: Fault indication after

• Default setting Fault indication after = 600 s


With the Fault indication after parameter, you set the time delay after which the unsuccessful
attempts of time synchronization with external time sources configured are indicated.

Parameter: Time Zone and Daylight Saving Time


This parameter block contains all the settings for the local time zone and daylight saving time of your
SIPROTEC 5 device. In addition to the individual parameters, configure the basic settings by preselecting via
the radio buttons or check box.

[sctimezo-210415, 1, en_US]

Figure 3-85 Settings for Time Zone and Daylight Saving Time in DIGSI

SIPROTEC 5, 7SJ82/7SJ85, Manual 169


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.7 Date and Time Synchronization

Selection Button Description


Manual settings (local time zone and daylight saving This setting must be selected if you want to select the
time regulation) local time zone and daylight saving time zone regula-
tions of your SIPROTEC 5 device regardless of the PC
settings.
Input: Offset time zone for GMT [min]
Selection: Switchover to daylight saving time
[yes/no] via check box

• Input: Start of daylight saving time [Day and


time]
• Input: End of daylight saving time [Day and
time]
• Input: Offset daylight saving time [min]
• Default settings as in the picture above

3.7.5 Settings

Addr. Parameter C Setting Options Default Setting


Time sync.
_:102 Time sync.:Time source • none none
1
• IRIG-B
• DCF77
• PI
• SNTP
• IEC 60870-5-103
• PROFIBUS DP
• Modbus
• DNP3
• IEEE 1588
• IEC 60870-5-104
_:103 Time sync.:Time source • port J
1 port
• port F
• port E
• port P
• port N
• port G
_:104 Time sync.:Time source • Ch1
1 channel
• Ch2

170 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.7 Date and Time Synchronization

Addr. Parameter C Setting Options Default Setting


_:105 Time sync.:Time source • none none
2
• IRIG-B
• DCF77
• PI
• SNTP
• IEC 60870-5-103
• PROFIBUS DP
• Modbus
• DNP3
• IEEE 1588
• IEC 60870-5-104
_:106 Time sync.:Time source • port J
2 port
• port F
• port E
• port P
• port N
• port G
_:107 Time sync.:Time source • Ch1
2 channel
• Ch2
_:108 Time sync.:Time zone • UTC local
time source 1
• local
_:109 Time sync.:Time zone • UTC local
time source 2
• local
_:101 Time sync.:Fault indica- 0 s to 3600 s 600 s
tion after

3.7.6 Information List

No. Information Data Class Type


(Type)
Time managem.
_:300 Time managem.:Daylight saving time SPS O
_:301 Time managem.:Clock set manually SPS O

No. Information Data Class Type


(Type)
Time sync.
_:303 Time sync.:Status time source 1 SPS O
_:304 Time sync.:Status time source 2 SPS O
_:305 Time sync.:Time sync. error SPS O
_:306 Time sync.:Leap second SPS O
_:307 Time sync.:High accuracy SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 171


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.8 User-Defined Objects

3.8 User-Defined Objects

3.8.1 Overview

With help from user-defined function groups and user-defined functions you can group user-defined objects,
for example user-defined function blocks. 2 user-defined function blocks are available (see following figure).

[scudef_lib, 1, en_US]

Figure 3-86 User-Defined Objects in the DIGSI 5 Library

The user-defined function block allows you to add (see following figure) single-point indications, pickup indi-
cations, operate indications (ADC, ACT), single and double commands, commands with a controllable whole
number as well as measured values. You can assign the group a superordinate name (for example process
indications for a group of single-point indications which are read via binary inputs). This function can be deac-
tivated using the mode. The standby mode is also analyzed or displayed.
The user-defined function blocks can be instantiated at the highest level (alongside other function groups) as
well as within function groups and functions.
In addition, there is a user-defined function block [control]. Alongside the aforementioned possibilities
presented by user-defined function blocks, this block offers additional tests for user-defined control signals,
for example SPC or DPC.
These are described in chapter 8.6.1 Overview of Functions.

[scbenutz-260912-01.tif, 1, en_US]

Figure 3-87 Information Routing with Incorporated User-Defined Function Block: Process Indications and
some Single-Point Indications

172 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.8 User-Defined Objects

3.8.2 Basic Data Types

The following data types are available for user-defined objects in the DIGSI 5 library under the heading User-
defined signals. Additionally, a folder for external signals is available (see chapter 3.8.5 External Signals).

User-Defined Signals

[sc_LB_userdefsig, 1, en_US]

Figure 3-88 User-Defined Signals

Single-Point Indication (Type SPS: Single-Point Status)


The status of a binary input can be registered in the form of a single-point indication or forwarded as the
binary result from a CFC chart.

EXAMPLE
Acquisition using binary input, further processing in a CFC and/or signaling using an LED.

Single-Point Indication (Type SPS unsaved: Single-Point Status Unsaved)


In contrast to SPS single-point indications, the state of the SPS unsaved indication is not maintained after the
device restarts.
For this purpose, go to Properties > Details > Initialization > Restart and set the Value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 173


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.8 User-Defined Objects

[scspsfas-140613-01.tif, 1, en_US]

Figure 3-89 Single-Point Indication SPS Unsaved (Example: 7KE85 Fault Recorder)

Double-Point Indication (Type DPS: Double-Point Status)


When using a double-point indication, the status of 2 binary inputs can be captured simultaneously and
mapped in an indication with 4 possible conditions (ON, Intermediate position, OFF, Disturbed
position).

EXAMPLE
Acquisition of a disconnector or circuit-breaker switch position.

Marker Command (Type SPC, Single-Point Controllable)


This data type can be used as a command without feedback for simple signaling or as an internal variable
(marker).

Integer Status Value (Type INS)


The data type INS is used to create a whole number that represents a CFC result.

174 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.8 User-Defined Objects

EXAMPLE
The output of the CFC block ADD_D can, for example, be connected with the data type INS. The result can be
shown on the display of the device.

State of an Enumeration Value (Type ENS)


The data type ENS is used to create an enumerated value that represents a CFC result.

Controllable Single-Point Indication (SPC, Single-Point Controllable)


This can be used to issue a command (to one or several relays, selectable under information routing) that is
monitored via a single feedback.

Command with Double-Point Feedback (DPC, Double Point Controllable)


This can be used to issue a command (to one or several relays, selectable under information routing) that is
monitored via double-point indication as feedback.

Command with a Whole Number (INC, Controllable Integer Status)


This can be used to issue a command (to one or more relays, selectable under information routing) that is
monitored via a whole number as feedback.

Complex Measured Values (CMV)


This data type provides a complex measured value that can be used as a CFC result, for example.

Measured Values (MV)


This data type provides a measured value that can be used as a CFC result, for instance.

NOTE

i Additional data types can be found under other headings in the DIGSI 5 library as well as in the corre-
sponding function blocks. This applies to the following data types:

• Pulse-metered values (see User-defined functions in the DIGSI 5 library)

• Transformer taps

• Metered values

Phase-to-Ground Measured Values (WYE)


This data type represents the phase-to-ground measured values of a 3-phase system.

Phase-to-Phase Measured Values (DEL, Delta)


This data type represents the phase-to-phase measured values of a 3-phase system.

Protection Activation Information (ACT)


This object type is used by the protection functions for Tripping. It is available in the library for receiving
protection information via the protection interface, which could also indicate Tripping.

Protection Activation Information with Direction (ACD)


This object type is used by the protection functions for Pickup. It is available in the library for receiving protec-
tion information via the protection interface, which could also indicate Pickup. In addition, both ACD and ACT
can be generated and processed by CFC charts.

SIPROTEC 5, 7SJ82/7SJ85, Manual 175


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.8 User-Defined Objects

3.8.3 Pulse and Energy Metered Values, Transformer Taps

Pulse-Metered Values
Pulse-metered values are available as data types BCR (Binary Counter Reading) in the DIGSI library under User-
defined Functions.
The functionality and the settings of the pulse-metered values can be found in chapter 10.8.1 Function
Description of Pulse-Metered Values.

Transformer Taps
Transformer taps are contained in the Transformer tap changers switching element. When the Transformer
tap changer switching element is created in the device, the transformer tap position is available as a data
object of type BSC (binary controlled tap changer with tap-position information).
You can find detailed information in 8.8.1 Function Description.

Energy-Metered Values
Energy-metered values no longer need to be created by the user separately. They are available as active and
reactive power in each Line function group for reference and output direction. The calculation is based on the
current and voltage transformers associated with the protected object.
You can find more detailed information in chapter 10.7.1 Function Description of Energy Values.

3.8.4 Additional Data Types

The following data types are also used in the system but are not available for general use as user-defined
signals in the library:

• ENC (Enumerated Setting Controllable)


The data type ENC models a command with which the user can set predefined values.

• SEQ (Sequence)

• BSC (Binary Controlled Step Position)


The data type BSC can, for example, be used to control a transformer tap changer. The commands up,
down can be given.

NOTE

i Transformer taps are included in the Transformer tap changer switching element. If this switching
element is created in the device, the transformer tap position is available as a data object of type BSC
(binary controlled step position information).

3.8.5 External Signals

User-defined signals of different types (see Figure 3-90) are available for GOOSE Later Binding. After instantia-
tion in a logical node, an external reference is generated during IID export and provided to a IEC 61850 system
tool (for example, System Configurator) for GOOSE Later Binding (according to the Later-Binding procedure
specified in IEC 61850-6).

176 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.8 User-Defined Objects

[sc_LB_extsign, 1, en_US]

Figure 3-90 External Signals

NOTE

i Consider the chapter on GOOSE Later Binding in the DIGSI Online Help. User-defined signals exist as
external signals and as preconfigured inputs that have been activated via the GOOSE column.

SIPROTEC 5, 7SJ82/7SJ85, Manual 177


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

3.9 Other Functions

3.9.1 Signal Filtering and Chatter Blocking for Input Signals

Input signals can be filtered to suppress brief changes at the binary input. Chatter blocking can be used to
prevent continuously changing indications from clogging the event list. After an adjustable number of
changes, the indication is blocked for a certain period.
The settings for indication filtering can be found at the individual signals. The next figure shows the settings
using the example of a controllable (circuit-breaker switch position).

NOTE

i The software filtering time is available only for the circuit breaker and disconnector in the controllable
Cmd. with feedback (control function block), as this is used for logging purposes. The controllable posi-
tion (circuit breaker or disconnector function block) is used for interlocking conditions and must always
show the unfiltered position of the switching object.

[sclposi-260116, 1, en_US]

Figure 3-91 Settings for Circuit-Breaker Switch Position

The setting range for the Software filter time parameter ranges from 0 ms to 100 000 ms in ms incre-
ments. The Retrigger filter check box can be used to select whether to restart the filtering time when-
ever a status change is performed within the software filtering time. When activated, the Indication
timestamp before filtering check box backdates the time stamp by the set software filtering time. In
this case, the time stamp corresponds to the actual status change of the signal. If you activate the Suppress
intermediate position check box, the intermediate position is suppressed for the duration of this soft-
ware filtering time.
If you leave the software filtering time at 0 ms, the time for the suppression of the intermediate position is
also 0 ms. The activated Suppress intermediate position check box then remains ineffective.

178 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

If you do not activate the Suppress intermediate position check box, the software filtering time
affects the on, off, intermediate, and disturbed positions of the circuit breaker or disconnector switch.
With the parameter Spontaneous position changes filtered by:, you set how such position
changes are to be filtered. Spontaneous position changes are caused by external switching commands, for
example. If you select the General software filter setting, the general settings for software filtering of
spontaneous position changes and for position changes caused by a switching command apply. The settings
for spontaneous position changes can then not be edited. A separate filtering for spontaneous position
changes is activated with the Spontaneous software filter setting and you can edit the settings for
this.
Chatter blocking can be activated or deactivated as an input parameter, for example as a parameter of the
position in the Circuit breaker or Disconnector function block.

[scflatte-180315, 1, en_US]

Figure 3-92 Setting Chatter Blocking

The settings for the chatter blocking function are set centrally for the entire device in DIGSI. They are acces-
sible as settings in the General function group (see the following figure).

SIPROTEC 5, 7SJ82/7SJ85, Manual 179


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

[scparafl-291110-01.tif, 2, en_US]

Figure 3-93 Chatter-Blocking Settings

The chatter-blocking settings have the following meaning (see also Figure 3-94 and Figure 3-95 in the exam-
ples shown in the following):

• No. permis.state changes


This number specifies how often the state of a signal may toggle within the chatter-test time and the
chatter-checking time. If this number is exceeded, the signal will be or remains blocked.
Enter a number from 0 to 65535 in this field. If the entry is 0, chatter blocking is essentially inactive.

• Initial test time


During this time, the number of times a signal changes its status is checked. This time is started if chatter
blocking is configured for at least one signal and this signal changes its status. If the configured number
of permissible status changes is exceeded during the initial test time, the signal is temporarily blocked
and the indication Chatter blocking is set.
Enter a number between 1 and 65535 in this field. The number entered corresponds to the time in
seconds. When the set time has expired, the timer restarts automatically (cycle time).

• No. of chatter tests


This number specifies the maximum number of test cycles to be run. If the number of permissible status
changes of the signal stays exceeded during the initial test time of the last test cycle, the signal is finally
blocked. In this case, the indication Group warning (Alarm handling group and Device group) is set
additionally to the Chatter blocking indication after expiry of the set number. Restarting the devices
removes this block again.
Enter a number from 0 to 32767 in this field. The value Infinite (∞) is also permissible here.
Enter this value as character string oo.

• Chatter idle time


If the number of permissible status changes for a signal is exceeded during the initial test time or the
subsequent test time, the Chatter idle time starts. Within this time, this signal is blocked tempora-
rily and the Chatter blocking indication is set. The blocked input signal is assigned the oscillatory
quality.
Enter a number between 1 and 65535 in this field. The number entered corresponds to the time in
minutes. An entry here is only considered if the number of chatter tests does not equal to 0.

180 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

• Subsequent test time


During this second test time, the number of times a signal changes its status is checked once again. The
time begins when the Chatter idle time expires. If the number of status changes is within the
permissible limits, the signal is released. Otherwise, an additional dead time begins, unless the maximum
number of chatter tests has been reached.
Enter a number between 2 and 65535 in this field. The number entered corresponds to the time in
seconds. An entry here is only considered if the number of chatter tests does not equal 0.

Example 1: Permanent Blocking


The chatter-blocking settings are set as follows:

• No. permis.state changes = 4

• No. of chatter tests = 2


After more than 4 state changes within the Initial test time, the input signal is set to the original state
by the chatter blocking and the oscillatory quality is assigned. Additionally, a corresponding indication is
added to the operational log. At the same time, the Chatter blocking indication is set. After expiry of the
settable Chatter idle time, during the following Subsequent test time, it is checked whether the
input signal is still chattering. This check is repeated, as the No. of chatter tests is set to 2 in this
example.
If, during the 2nd Subsequent test time, it has been detected that the number of status changes of the
input signal exceeds the set No. permis.state changes, the chatter blocking detects a persistent viola-
tion of the signal stability and sets the Group warning indication. The original state of the signal is perma-
nently frozen. Only a device restart removes the chatter blocking again.

[dw_chatter-block-01, 1, en_US]

Figure 3-94 Signal Change during Chatter Blocking with too Important Number of Signal State Changes
During 2nd Subsequent Test Time

(1) The input signal is permanently blocked starting from this point in time.

SIPROTEC 5, 7SJ82/7SJ85, Manual 181


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

Example 2: Temporary Blocking


The chatter-blocking settings are set as follows:

• No. permis.state changes = 4

• No. of chatter tests = 2


After more than 4 state changes within the Initial test time, the input signal is set to the original state
by the chatter blocking and the oscillatory quality is assigned. Additionally, a corresponding indication is
added to the operational log. At the same time, the Chatter blocking indication is set. After expiry of the
settable Chatter idle time, during the following Subsequent test time, it is checked whether the
input signal is still chattering. This check is repeated, as the No. of chatter tests is set to 2 in this
example.
If, during the 2nd Subsequent test time, it has been detected that the number of state changes of the
input signal is within the set No. permis.state changes, the temporary blocking of state changes of the
signal is removed and the actual signal state is released.
The quality bit oscillatory is removed and the Chatter blocking indication is reset. As the temporary
blocking of the signal is removed, the Group warning indication is not set. The chatter test starts again.

[dw_chatter-block-02, 1, en_US]

Figure 3-95 Signal Change during Chatter Blocking with Permissible Number of Signal State Changes
During 2nd Subsequent Test Time

3.9.2 Acquisition Blocking and Manual Updating

During commissioning, maintenance, or testing, a brief interruption of the connection between the logical
signals and binary inputs may be useful. It allows you to manually update the status of a switching device that
is not providing feedback correctly. Before this can take place, you must first set acquisition blocking.
To set the acquisition blocking, proceed as follows:

• Using the navigation keys, move in the main menu of the device display to
Commands→Equipment→Aq.blkman. update.

• Select the appropriate device (for example, a circuit breaker) from among the several switching devices
using the navigation keys.

• Press the Change softkey.

182 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

• Enter the confirmation ID (not relevant for active role-based access control (RBAC) in the device).

• Confirm the process with the softkey marked OK in the display.


After entering the confirmation ID (only with the RBAC inactive), acquisition blocking is switched on.

[scerfass-310816-01, 1, en_US]

Figure 3-96 Activating Acquisition Blocking

Manual updating of the switching device is possible from within the same menu.

• Select Manual update (Figure 3-97) using the navigation keys.

• Select the switching device setting to be updated manually using the navigation keys (for example, off,
Figure 3-98).

• Confirm the process with the softkey marked OK in the display.

[scstatus-310816-01, 1, en_US]

Figure 3-97 Activating Manual Update

[scstatu2-310816-01, 1, en_US]

Figure 3-98 Selecting Position

The manually updated position of the switching device will be displayed.

[scstatu3-310816-01, 1, en_US]

Figure 3-99 Position of the Switching Device

NOTE

i For security reasons, manual updating is possible only directly through the on-site operation panel of the
device and not through DIGSI 5.

SIPROTEC 5, 7SJ82/7SJ85, Manual 183


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

NOTE

i Setting acquisition blocking and the subsequent manual updating are also possible via the IEC 61850
system interface.

You can also set acquisition blocking via a binary input. If you want to put the feeder or the switching device
in revision, you can set the acquisition blocking for an individual or several switching devices with an external
toggle switch. For this purpose, every switching device in the Switch function block (circuit breaker or discon-
nector switch) has the input signal >Acquisition blocking. This signal can also be set from the CFC.

[scbeerfa-190215, 1, en_US]

Figure 3-100 Input Signals >Acquisition Block and >Release Acquisition Block & Manual
Updating on the Switching Device

NOTE

i Interlockings are carried out with the status changes of the switching device. Remove acquisition blocking
again manually. Otherwise, position changes of the switching device are not detected and interlockings are
ineffective.

If the acquisition blocking and the manually updated position are set using the operation panel of the device
or the system interface IEC 61850, these are retained until the acquisition blocking is manually deactivated.
When you initially start the device, the acquisition blocking is deactivated.
Except for a restart, the acquisition blocking and the manually updated position are retained.
If the acquisition blocking is activated via the input signal >Acquisition blocking, it is retained as long as
the binary input is active.
To set the acquisition blocking of a switching device, the following sources are possible:

• Operation panel of the device

• System interface IEC 61850

• Input signal >Acquisition blocking


All sources undergo OR operations, that is, the acquisition blocking remains set until all the sources are deacti-
vated.
After deactivation of the acquisition blocking, the actual position of the switching device is adopted and
displayed in the operation panel of the device.

NOTE

i When the acquisition blocking is activated or the switching device updated manually while the entire
device or the switching device is in test mode, these states are not saved. The acquisition blocking and the
manual updating are not retained after a restart.

The acquisition blocking and the manual update for the circuit breaker, the disconnector, and the tap changer
are reset by way of the >Reset AcqBlk&Subst binary input. Setting acquisition blocking and manual
update is blocked with the input activated.

184 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

3.9.3 Persistent Commands

In addition to the switching commands, which are issued as pulse commands, and stored for the standard
switching devices (circuit breaker, disconnector switch), persistent commands are also possible. In this case, a
distinction must be drawn between controllables with the Continuous output operating mode and a stored
signal output that is immune to reset.
You can change a controllable from pulse to persistent command with the Command output parameter.

[scbefehl-260912-01.tif, 1, en_US]

Figure 3-101 Setting the Command Type in DIGSI 5

Select Pulse output or Continuous output for the command output type. If a persistent command is
selected, the Pulse parameter is irrelevant.

3.9.4 Device Logout

3.9.4.1 Overview
In the case of multibay functions, a device uses information from one or more other devices. For some applica-
tions, it may be necessary for you to remove a device with all effective functions temporarily from the plant
and even to switch it off. These applications are, for example:

• Maintenance work

• System upgrades

• Testing the local protection functions


The Device logout functionality informs the receiver devices about the imminent disconnection of the
transmitter devices. To do this, the last valid received information is stored in the receiver devices and used for
the multibay functions.

SIPROTEC 5, 7SJ82/7SJ85, Manual 185


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

NOTE

i If you need to remove a device temporarily from the plant, you must log off the device.
Protection functions distributed to several devices operate in a healthy manner with the remaining devices
only if you have logged off the device.

You can log off the device as follows:

• Via the on-site operation panel

• Via a communication interface using the Device logout (_:319) controllable

• Via the binary inputs, general: >Dev. funct.logout on (_:507) or >Dev. funct.logout off
(_:508)
You can find the controllable and the binary inputs in the DIGSI 5 project tree under Name of the device →
Information routing in the working area in the General block.
During the log-off process, the device checks whether all conditions for a logoff have been met. If the condi-
tions for the log off have not been met, the logout is rejected.
The logout is rejected under the following conditions:

• The devices are communicating via the protection interface and switching off the device leads to an
interruption in protection-interface communication.

NOTE

i The option used to log the device off is stored in the operational log.
Even if you switch off the device after logoff, the Device logged off (_:315) state is stored.

If you want to establish the initial state again after logging off the device, you must log on the device again.
To log on the device, you must use the same option used for logoff. For example, if you have logged off the
device via binary inputs, you must log it on again via the binary inputs. This applies in similar manner if you
have logged off the device via DIGSI or via on-site operation.

3.9.4.2 Application and Setting Notes

Logoff Options for a Device


You can log off a device as follows:

• Via the on-site operation panel

• Via communication via the controllable Device logout (_:319)

• Via the binary inputs, general: >Dev. funct.logout on (_:507) or >Dev. funct.logout off
(_:508)

186 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

Conditions for Logging off the Device

[lo functional logoff device, 1, en_US]

Figure 3-102 Logic for Logging off the Device

The conditions for a successful logout of the device result from the conditions for every activated protection
function.

Logoff of a Device from a Device Combination with Communication via the IEC 61850-8-1 (GOOSE) Protocol
If devices are exchanging data via the IEC 61850-8-1 (GOOSE) protocol, for example, in the case of substation
interlocking, you can set in the receiver device for each received data point the value of this data point when
the transmitter device logs off. This value remains effective in the receiver device until the logout is canceled
by the transmitter device, even if the transmitter and/or the receiver are switched off in the meantime.

Logoff of a Device from a Device Combination using Protection Communication


If devices in a device combination communicate via the protection interface, you can only log off a device
under the following conditions:

• Logging off and switching off a device in a device combination must not result in an interruption of the
protection communication.

• For series-connected topologies, the device must be located at one end of the communication chain as
otherwise, the protection communication is interrupted when the device is logged off and switched off.
For this reason, devices that are not at one of the ends in series-connected topologies cannot be logged
off.

Logout via Binary Inputs


The following diagrams show potential variants on how to control binary inputs. If you want to use push-
buttons, switch them on as shown in the following figure. Use the push-button Key2 to log off the device; use
the push-button Key1 log on the device again.

[loextta logoff device, 1, en_US]

Figure 3-103 External Push-Button Wiring for Logging off the Device

If a switch is being used for control, route the binary input >Dev. funct.logout on as H (active with
voltage) and the binary input >Dev. funct.logout off as L (active without voltage). If the
switch S is closed, the device is logged off.

SIPROTEC 5, 7SJ82/7SJ85, Manual 187


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.9 Other Functions

[loextsx logoff device, 1, en_US]

Figure 3-104 External Switch Wiring for Logging off the Device

Indications
The logged-off device reports the status ((_:315) Device logged off) and the cause of the logout.
If you have logged off the device via binary inputs, the indication (_:313) Logged off via BI is issued.
If you have logged off the device via on-site operation, via DIGSI 5, or via the protection interface, the indica-
tion (_:314) Logged off via control is issued.
The indications are stored in the operational log.

3.9.4.3 Information List

No. Information Data Class Type


(Type)
General
_:507 General:>Dev. funct.logout on SPS I
_:508 General:>Dev. funct.logout off SPS I
_:319 General:Device logout SPC C
_:313 General:Logged off via BI SPS O
_:314 General:Logged off via control SPS O
_:315 General:Device logged off SPS O

188 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

3.10 General Notes for Setting the Threshold Value of Protection


Functions

3.10.1 Overview

You can set the threshold values of protection functions directly on the device or by using DIGSI 5.
An innovative design was implemented for the protection settings.
You can switchover the edit mode between the following setting views:

• Primary

• Secondary

• Percent
If you change settings in a setting view, DIGSI 5 calculates the settings of the 2 inactive views in the back-
ground. If you wish to save, for example, conversion to secondary values, then select the primary view.
Configure all the settings and switchover to the secondary view.

Edit Mode: Primary


The parameters are set as primary values and thus refer directly to the primary system. The manual conversion
on the secondary circuit omitted.

Edit Mode: Secondary


The settings refer to the secondary circuit of the transformer. This means that the settings must be converted.
The secondary setting is the customary setting view. For secondary tests, the pickup values can be read
directly.

Edit Mode: Percent


This setting type is beneficial for electric machines (generators, transformers, motors, and busbars). The
setting values can be standardized regardless of the machine size. The reference values for the percentage
settings are the rated values of the function groups, for example, rated voltage and rated current or rated
apparent power . The setting values are, thus, related exclusively to the primary settings. If other reference
values are used, then this is documented for the respective protection function in the application and setting
notes.
If parameters are selected it may happen that they are set only in percent in all 3 setting views.

Recommendation for Setting Sequence


When setting the protection function, Siemens recommends the following procedure:

• First set the transformation ratios of the transformers. You can find these under Power-system data.

• In addition, set the reference parameters for the percent setting. You will find these parameters in func-
tion group .

• Next, set the parameter of the protection functions.


If the transformer data have changed after completing the protection setting, remain in the setting sheet
(for example, primary setting) and change the transformer data. In the background, DIGSI 5 obtains the
new settings in the inactive setting views (for example, new secondary values).
The following section explains, by way of an example, how to modify the transformer ratios in DIGSI 5 using
the corresponding alternatives.

3.10.2 Modifying the Transformer Ratios in DIGSI 5

In the delivery setting, DIGSI 5 is set to the Secondary edit mode.

SIPROTEC 5, 7SJ82/7SJ85, Manual 189


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

The following setting example shows how you can change the transformer ratio in DIGSI 5, and what impact
this has on the settings in the setting views Primary and Secondary. The protection setting is observed in the
example of the Overcurrent protection function.
The following output data are assumed:
Current transformer: 1000 A/1 A
Protection pickup value: 1.5 A

The following figure shows the protection setting of the Overcurrent protection function in the secondary
view. The threshold value of the stage is set to 1.5 A.

[scmodsek_1, 1, en_US]

Figure 3-105 Protection Setting, Display of the Active Setting Sheet

When you click the green arrow in the setting sheet at the upper left, you get to the window for switching
over to the setting view (see the following figure). Select the setting view you prefer.

[scmodums_2, 1, en_US]

Figure 3-106 Switchover to the Desired Setting View

The following figures show the setting sequence in the Primary edit mode. Set the transformer data. In the
example, the current transformer has a transformation ratio of 1000 A/1 A.

190 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

[scpwandl_3, 1, en_US]

Figure 3-107 Setting Sheet: Transformer Data

In the function group Voltage/current 3-phase, you set the rated current and the rated voltage (see following
figure). Rated current, rated voltage are the reference variables for the percent setting.

[scui3phd, 1, en_US]

Figure 3-108 Reference Data for Percentage Settings

The following figure shows the threshold value of the Overcurrent protection function in the primary view at
1500 A.

SIPROTEC 5, 7SJ82/7SJ85, Manual 191


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

[scumzpri_5, 1, en_US]

Figure 3-109 Example of the Threshold Value of the Definite-Time Overcurrent Protection Stage (Edit Mode:
Primary)

When switching over to the percent view, the result should be the following value:
1500 A/1000 A · 100 % = 150 %

192 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

[scumzpro_6, 1, en_US]

Figure 3-110 Example of the Threshold Value of the Definite-Time Overcurrent Protection Stage (Edit Mode:
Percent)

When switching over to the secondary view, the result should be the following value:
1500 A/(1000 A/1 A) = 1.5 A

SIPROTEC 5, 7SJ82/7SJ85, Manual 193


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

[scumzsek_7, 1, en_US]

Figure 3-111 Example of the Threshold Value of the Definite-Time Overcurrent Protection Stage (Edit Mode:
Secondary)

If you only want to work in the secondary view, DIGSI 5 supports you if the transformer ratio changes during
the project phase.
In the example, the current-transformer ratio changes from 1000 A/1 A to 1000 A/5 A. Change the secondary
rated current of the current transformer in the setting sheet of the transformer data from 1 A to 5 A (Edit
mode: Secondary). If you change the transformer data, a window will appear (see the following figure) that
will ask you for the action desired.

194 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

[scfragew_8, 1, en_US]

Figure 3-112 Query after Changing the Transformer Data (Setting View: Secondary)

If you answer the question with Yes, then DIGSI 5 will recalculate the pickup values (threshold values) in the
active secondary view. For the new secondary transformer current 5 A, the new secondary threshold value
obtained is 7.5 A (1.5 A * 5 = 7.5 A). The primary and percent values remain unchanged.
The following figure shows the newly calculated threshold value in the secondary view.

SIPROTEC 5, 7SJ82/7SJ85, Manual 195


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

[scsekneu_9, 1, en_US]

Figure 3-113 Automatically Recalculated Secondary Values After Changes in the Transformer Data

If you have already set the settings in the secondary view by including the new transformation ratio of the
transformer in the calculation, then answer the question with No. In this case, the protection settings in the
secondary view remain unchanged. DIGSI 5 recalculates the settings (threshold values) of the primary view. In
the example, the primary threshold value is then 300 A (1.5 A * 1000 A/5 A = 300 A).
In the example, the current-transformer ratio changes from 1000 A/1 A to 1000 A/5 A. The following table
summarizes the pickup values that DIGSI 5 will recalculate in the setting view. The new values (in bold)
depend on the reply to your question (see Figure 3-112).
Reply to the Question
Yes No
Threshold value secondary (active setting view) 7.5 A 1.5 A
Threshold value primary (covered setting view) 1500 A 300 A

Changing the Transformer Ratio in the Single-Line Editor


If you want to change the primary or secondary rated currents of the current transformer in the Single-Line
Editor, select the current transformer. You can view and change the currents in the Properties tab of the
object bar.
If you change the rated currents, the corresponding field has a red border to indicate currents that differ
between the Single-Line Editor and the power-system data. During synchronization in the Single-Line Editor,
these rated currents are adopted into the power-system data.

3.10.3 Changing the Transformation Ratios of the Transformer on the Device

In the delivery setting, the device is preset to the secondary value. Only secondary values can be set directly
on the device.

196 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.10 General Notes for Setting the Threshold Value of Protection Functions

If you change transformer data directly on the device, it is not followed by a query, like in DIGSI 5 (see
Figure 3-112). Instead, the device assumes that all settings remain unchanged in the secondary view.

NOTE

i If the device works with IEC 61850 protocol, you change the transformer data only via DIGSI 5 and not
directly on the device. If you change the transformer data directly on the device, the IEC 61850 configura-
tion of the measurement and metered values can be faulty.

SIPROTEC 5, 7SJ82/7SJ85, Manual 197


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.11 Device Settings

3.11 Device Settings

3.11.1 General Device Settings

3.11.1.1 Overview
In Device settings in DIGSI 5, you find the following general settings.

[scDeSeDe1-310715-01, 1, en_US]

[scDeSeAl-310715-01, 3, en_US]

[scDeSeall-260815-01, 1, en_US]

Figure 3-114 General Device Settings

The following list shows you the chapters containing the desired information.

198 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.11 Device Settings

You can find more about:

• Chatter blocking in chapter 3.9.1 Signal Filtering and Chatter Blocking for Input Signals.

• Control in chapter 8.3 Control Functionality.

• Spontaneous indications in chapter 3.1.7 Spontaneous Indication Display in DIGSI 5.

• Continuous Function Chart Quality Treatment in chapter 3.4.3 Quality Processing/Affected by the User
in CFC Charts.
Under Device, you set the parameters for the device that are valid across functions.
With Test support, indications issued via communication interfaces are labeled with an additional test bit, if
this is supported by the protocol. With this test bit you can determine whether an indication is generated in a
test and whether all or individual functions of the device are in the test mode. In this manner the reactions
that are necessary in normal operation due to an indication can be suppressed in other devices that receive
these indications. You can also permit, for example, a trip command to close an energized binary output for
test purposes. Siemens recommends deactivating the Test support again after the test phase.

3.11.1.2 Application and Setting Notes


The major portion of the settings is described in the chapters cited above. Then, the parameters on the section
Device, Settings change, Spontaneous indication, and Test support are described.

Parameter: Rated frequency

• Default setting (_:101) Rated frequency = 50 Hz


With the parameter Rated frequency, you set the rated frequency of the electrical power system.

Parameter: Minimum operate time

• Default setting (_:102) Minimum operate time = 0.00 s


With the parameter Minimum operate time , you set the minimum duration for the trip command of the
functions. The trip command is maintained for the set duration.

Parameter: Block monitoring dir.

• Default setting (_:138) Block monitoring dir. = off


With the parameter Block monitoring dir., you set whether indications are output via the system inter-
face(s) of the SIPROTEC 5 device or not.
If transmission blocking is switched on, no indications are output via the system interface(s) of a SIPROTEC 5
device, except via the IEC 61850 interface(s).
To avoid receiving IEC 61850 data, the corresponding IEC 61850 Client must stop the reporting or freeze the
data. You can find more information in the Communication Protocols Manual (C53000-L1840-C055-3).

Parameter: Fault-display

• Default setting (_:139) Fault-display = with pickup


With the parameter Fault-display , you set whether spontaneous fault indications which are signed as NT
(conditioned latching) in the matrix, get stored with every pickup or only for one tripping.
Keep the DIGSI 5 routing options in chapters 3.1.7 Spontaneous Indication Display in DIGSI 5 and Table 3-7 in
mind.

Parameter: Activate device test mode

• Default setting (_:150) Activate device test mode = inactive


With the parameter Activate device test mode , you activate test mode that adds a test bit to the
output indications. If test mode is activated but the test mode of the relay outputs is not, no relay outputs are
activated by the protection functions.

SIPROTEC 5, 7SJ82/7SJ85, Manual 199


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.11 Device Settings

Parameter: Oper.bin.outp. under test

• Default setting (_:151) Oper.bin.outp. under test = inactive


If you activate the parameter Oper.bin.outp. under test , you can permit the closing of a binary
output for test purposes. In this way, indications are output during a device-wide test mode and the relay is
either activated or not. If an individual function is in test mode, only indications are output and the relays are
not activated.

NOTE

i The device remains in test mode during every startup until you intentionally set the device back into
process mode. You set process mode by switching the parameterActivate device test mode to inactive
again (removing the check mark).

Output Signal: Functions in Test mode


Normally, the output signal Functions in Test mode is prerouted to the last LED of the device base
module. If one or more functions are in test mode, the output signal Functions in Test mode is gener-
ated and the corresponding LED of the device lights up red.

3.11.1.3 Settings

Addr. Parameter C Setting Options Default Setting


Device
_:101 General:Rated frequency • 50 Hz 50 Hz
• 60 Hz
_:102 General:Minimum 0.00 s to 60.00 s 0.00 s
operate time
_:138 General:Block moni- • off off
toring dir.
• on
Setting change
_:163 General:Reserv.time for 0 s to 65535 s 120 s
com.prot.
Spontan.indic.
_:139 General:Fault-display • with pickup with pickup
• with trip
Test support
_:150 General:Activate device • 0 false
test mode
• 1
_:151 General:Oper.bin.outp. • 0 false
under test
• 1

3.11.1.4 Information List

No. Information Data Class Type


(Type)
General
_:510 General:>Test mode on SPS I
_:511 General:>Test mode off SPS I
_:507 General:>Dev. funct.logout on SPS I
_:508 General:>Dev. funct.logout off SPS I
_:512 General:>LED reset SPS I
_:52 General:Behavior ENS O

200 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.11 Device Settings

No. Information Data Class Type


(Type)
_:53 General:Health ENS O
_:51 General:Test mode ENC C
_:321 General:Protection on SPC C
_:54 General:Protection inactive SPS O
_:323 General:LED reset SPC C
_:320 General:LED have been reset SPS O
_:329 General:Functions in Test mode SPS O

3.11.2 Settings-Group Switching

3.11.2.1 Overview of Functions


For different applications you can save the respective function settings in so-called Settings groups, and if
necessary enable them quickly.
You can save up to 8 different settings groups in the device. In the process, only one settings group is active at
any given time. During operation, you can switch between settings groups. The source of the switchover can
be selected via a parameter.
You can switchover the settings groups via the following alternatives:

• Via the on-site operation panel directly on the device

• Via an online DIGSI connection to the device

• Via binary inputs

• Via a communication connection to the substation automation technology.


The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC 61850, DNP or Modbus TCP can be
used for switching the settings groups.
A settings group includes all switchable settings of the device. Except for a few exceptions (for example,
general device settings such as rated frequency), all device settings can be switched.
Detailed information about the settings groups can be found in the Operating Manual and DIGSI 5 Online
Help.

3.11.2.2 Structure of the Function


The function of the Settings group switching is a supervisory device function. Accordingly, the settings and
indications of the settings group switching can be found in DIGSI 5 and at the on-site operation panel of the
device, below the general device settings respectively.
If you want to switchover a settings group, navigate to DIGSI 5 or proceed on the on-site operation panel of
the device, as follows:

• Via the project tree in DIGSI 5:


Project -> Device -> Settings -> Device settings

• Via the on-site operation panel of the device:


Main menu → Settings → General → Group switchover
The indications for the settings group switching can be found in the DIGSI 5 project tree under:
Project → Device → Information routing → General

3.11.2.3 Function Description

Activation
If you want to use the Settings group switching function, you must first set at least 2 settings groups in DIGSI
5 (parameter Number of settings groups > 1). You can set up a maximum of 8 settings groups. The settings
groups set in DIGSI 5 are subsequently loaded into the device.

SIPROTEC 5, 7SJ82/7SJ85, Manual 201


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.11 Device Settings

Mechanism of the Switchover


When switching over from one settings group to another, the device operation is not interrupted. With the
Active settings group parameter, you are either specifying a certain settings group or you allow
switching via control (IEC 60870-5-103, IEC 61850) or via binary input.

Switching via Control


When using the Control function for switching, the settings groups can be switched via a communication
connection from the substation automation technology or via a CFC chart.
The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC 61850, DNP or Modbus TCP can be used
for switching the settings groups via a communication connection.
In order to use a CFC chart for switching, you must create a new CFC chart in DIGSI 5. Create the CFC chart in
the DIGSI 5 project tree under Name of the device → Charts → Add new chart. Link the signals that control
settings group switching in the CFC chart.

Switching via Binary Input


There are 3 appropriate input signals available for switching via binary inputs. These input signals allow selec-
tion of the settings group via a binary code. If one of the 3 signals changes, the signal image present will, after
100 ms (stabilization time), result in switching over to the appropriate settings group. If only 2 settings groups
must be switched over, only 1 binary input is required. The following table shows the possible binary codes
(BCD) and applicable settings groups (PG).

Table 3-22 Binary Codes of the Input Signals and Applicable Settings Groups

BCD Code via Binary Inputs PG 1 PG 2 PG 3 PG 4 PG 5 PG 6 PG 7 PG 8


>PG selection bit 3 0 0 0 0 1 1 1 1
>PG selection bit 2 0 0 1 1 0 0 1 1
>PG selection bit 1 0 1 0 1 0 1 0 1

Copying and Comparing Settings Groups


In DIGSI 5, you can copy or compare settings groups with each other.
If you want to copy settings groups, select a source and target parameter group in DIGSI 5 in the device
settings, and then start the copy process. The device settings can be found in the DIGSI 5 project tree under
Project → Device → Settings → Device settings.
If you want to compare settings groups, it is possible to do so in all setting sheets for settings. You will then
select in addition to the active settings group, a 2nd settings group for comparison. Active setting values and
the comparable values are displayed next to each other. For settings that cannot be switched over, no compa-
rable values are displayed.

Indication of Settings Group Switchings


Every settings group shows an applicable binary indication as well as its activation and deactivation. The
process of settings group switching is also logged in the log for settings changes.

3.11.2.4 Application and Setting Notes

Parameter: Number settings groups

• Default setting (_:113) Number settings groups = 1


With the Number settings groups parameter, you can set the number of available settings groups; you
can switch between these.

Parameter: Activat. of settings group

• Default setting (_:114) Activat. of settings group = settings group 1

202 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
System Functions
3.11 Device Settings

With the Activat. of settings group parameter, you specify the settings groups that you want to acti-
vate, or the mechanisms via which the switchover is allowed. You can switchover only between the settings
groups specified with the Number settings groups parameter. Parameter Value
Parameter Value Description
via control The switchover between the settings groups can only be initiated via a
communication connection from a substation automation technology or via
a CFC chart.
The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC
61850, DNP or Modbus TCP can be used for switching the settings groups
via a communication connection.
via binary input The switchover between the settings groups functions exclusively via the
binary input signals routed to the settings group switching.
settings group 1 They define the active settings groups. You can define the active settings
... groups in DIGSI 5, or directly on the device via the on-site operation.
settings group 8

3.11.2.5 Settings

Addr. Parameter C Setting Options Default Setting


Change group
_:113 General:Number settings 1 to 8 1
groups
_:114 General:Activat. of • via control settings group 1
settings group
• via binary input
• settings group 1
• settings group 2
• settings group 3
• settings group 4
• settings group 5
• settings group 6
• settings group 7
• settings group 8

3.11.2.6 Information List

No. Information Data Class Type


(Type)
General
_:500 General:>SG choice bit 1 SPS I
_:501 General:>SG choice bit 2 SPS I
_:502 General:>SG choice bit 3 SPS I
_:300 General:Act. settings group 1 SPC C
_:301 General:Act. settings group 2 SPC C
_:302 General:Act. settings group 3 SPC C
_:303 General:Act. settings group 4 SPC C
_:304 General:Act. settings group 5 SPC C
_:305 General:Act. settings group 6 SPC C
_:306 General:Act. settings group 7 SPC C
_:307 General:Act. settings group 8 SPC C

SIPROTEC 5, 7SJ82/7SJ85, Manual 203


C53000-G5040-C017-A, Edition 06.2019
204 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
4 Applications

4.1 Overview 206


4.2 Application Templates and Functional Scope for the Devices 7SJ82/7SJ85 207

SIPROTEC 5, 7SJ82/7SJ85, Manual 205


C53000-G5040-C017-A, Edition 06.2019
Applications
4.1 Overview

4.1 Overview
The Global DIGSI 5 library provides application templates for the applications of the devices. The application
template

• Supports the fast realization of complete protection solutions for applications

• Contains the basic configuration for the use case

• Contains functions and default settings for the use case

When using an application template, note the following:

• Adapt the application template to your specific use (check/adapt default settings, delete/add functions).
You can find more detailed information in the 2.1 Function Embedding in the Device.

• Check the routing of binary outputs with respect to fast and normal relays.

• Check the CFC charts for the group-warning indications and group-fault indications.
The following describes the application templates and maximum functional scope for the devices shown in
this manual.

NOTE

i The availability of certain settings and setting options depends on the device type and the functions avail-
able on the device!

206 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Applications
4.2 Application Templates and Functional Scope for the Devices 7SJ82/7SJ85

4.2 Application Templates and Functional Scope for the Devices


7SJ82/7SJ85
Application templates are available in DIGSI 5 for the applications of the non-modular device 7SJ82 and the
modular device 7SJ85. The application templates contain the basic configurations, required functions, and
default settings.
The following application templates are available for the device 7SJ82 and 7SJ85 in the DIGSI 5 function
library:

• Non-directional OC (4*I), 7SJ82 only

• Non-directional OC (4*I, 4*V)

• Directional OC, grounded system

• Directional OC, resonant-grounded/isol. system

• Capacitor bank H-bridge + 1*RLC, 7SJ85 only

• Capacitor bank MSCDN, 7SJ85 only

• Capacitor bank H-bridge, 7SJ82 only


For the application templates to function in the device, the following minimum requirements for the hardware
configuration must be met:
Application Template Hardware Configuration Minimum
Requirement
Template 1 Non-directional OC (4*I) 9 BI, 8 BO, 4 I
Template 2 Non-directional OC (4*I, 4*V) 9 BI, 8 BO, 4 I, 4 V
Template 3 Directional OC, grounded system
Template 4 Directional OC, resonant-grounded / isol.
system
Template 5 Capacitor bank: H-bridge + 1*RLC 2 BI, 2 BO, 12 I
Template 6 Capacitor bank: MSCDN 2 BI, 2 BO, 28 I, 4 V
Template 7 Capacitor bank: H-bridge 2 BI, 2 BO, 8 I

The following table shows the functional scope and the required function points of the application templates
for the device 7SJ82/7SJ85:

Table 4-1 Functional Scope of the Application Template for the Device 7SJ82/7SJ85

ANSI Function Abbr.


Available in 7SJ82

Available in 7SJ85

Template 1

Template 2

Template 3

Template 4

Template 5

Template 6

Template 7

Protection functions for 3-pole tripping 3-pole x x x x x x x x x


Hardware quantity structure expand- I/O x x x x x x
able
24 Overexcitation protection V/f x x
25 Synchrocheck, synchronization func- Sync x x
tion
27 Undervoltage protection, 3-phase V< x x
27 Undervoltage protection, positive- V1< x x
sequence system

SIPROTEC 5, 7SJ82/7SJ85, Manual 207


C53000-G5040-C017-A, Edition 06.2019
Applications
4.2 Application Templates and Functional Scope for the Devices 7SJ82/7SJ85

ANSI Function Abbr.

Available in 7SJ82

Available in 7SJ85

Template 1

Template 2

Template 3

Template 4

Template 5

Template 6

Template 7
27 Undervoltage protection, 3-phase, Vx< x x
universal, Vx
27 Undervoltage protection, 1-phase, Vx< x x
universal, Vx
27/Q Undervoltage-controlled reactive QU x x
power protection
32R Reverse-power protection -P< x x
32, 37 Power protection active/reactive power P<>, Q<> x x
37 Undercurrent protection I< x x x x x
38 Temperature supervision TmpUb x x
46 Negative-sequence system overcurrent I2> x x x x x
protection
46 Unbalanced-load protection (thermal) I22t> x x
46 Negative-sequence overcurrent protec- I2>, ∠ x x
tion with direction (V2, I2)
49 Thermal overload protection Θ, I2t x x 3 x
49 Thermal overload protection, user- Θ, I2t x x
defined characteristic
49 Thermal overload protection for RLC Θ, I2t x x x
filter elements of a capacitor bank
50TD/ Overcurrent protection, phases - I> x x x
51 advanced
50TD/ Overcurrent protection, phases - basic I> x x x x x x 3 x
51
50TD/ Positive-sequence overcurrent protec- x x
51 tion
50TD/ OC-3ph protection for RLC elements x x
51
50NTD/ Overcurrent protection, ground - IN> x x x
51N advanced
50NTD/ Overcurrent protection, ground - basic IN> x x x x x x x
51N
50N/ Overcurrent protection, 1-phase - I>1pA x x
51N advanced
50N/ Overcurrent protection, 1-phase - basic I>1pB x x
51N
50HS Instantaneous high-current tripping I>>> x x
50Ns/ Sensitive ground-current protection for INs> x x
51Ns systems with resonant or isolated
neutral
50BF Circuit-breaker failure protection x x x
RBRF Restrike protection x x
51V Overcurrent protection, voltage x x
dependent

208 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Applications
4.2 Application Templates and Functional Scope for the Devices 7SJ82/7SJ85

ANSI Function Abbr.

Available in 7SJ82

Available in 7SJ85

Template 1

Template 2

Template 3

Template 4

Template 5

Template 6

Template 7
59 Overvoltage protection, 3-phase V> x x x
59 Overvoltage protection, positive- V1> x x
sequence system
47 Overvoltage protection, negative- V2> x x
sequence system
47 Overvoltage protection, negative- V2/V1> x x
sequence/positive-sequence system
59N Overvoltage protection, zero-sequence V0> x x
system
59 Overvoltage protection, 3-phase or 1- Vx> x x
phase, universal, Vx
59C Peak overvoltage protection for capaci- x x x 2 x
tors
60 Voltage-comparison supervision x x
60C Current-unbalance protection for Iunbal> x x x 2 x
capacitor banks, 3-phase
60C Current-unbalance protection for Iunbal> x x
capacitor banks, 1-phase
67 Directional overcurrent protection, I>, ∠(V,I) x x
phases – advanced
67 Directional overcurrent protection, I>, ∠(V,I) x x x x
phases – basic
67N Directional overcurrent protection, IN>, ∠ x x
ground - advanced (V,I)
67N Directional overcurrent protection, IN>, ∠ x x x
ground - basic (V,I)
67Ns Directional sensitive ground-fault INs>, ∠ x x x
detection for systems with resonant or (V,I)
isolated neutral
67Ns Directional sensitive ground-fault G0>, B0> x x
detection via admittance measurement
for systems with resonant or isolated
neutral
67Ns Transient ground-fault function, for W0p,tr> x x
transient and permanent ground faults
in resonant-grounded or isolated
networks
67Ns Sensitive ground-fault detection for V0>, ∠ x x
systems with resonant or isolated (Uharm.,I
neutral with phasor measurement of harm.)
3rd or 5th harmonic
67Ns Sensitive ground-fault detection for IN-pulse x x
systems with resonant or isolated
neutral via 3I0 pulse pattern detection
74TC Trip-circuit supervision TCS x x
79 Automatic reclosing AREC x x
81O Overfrequency protection f> x x

SIPROTEC 5, 7SJ82/7SJ85, Manual 209


C53000-G5040-C017-A, Edition 06.2019
Applications
4.2 Application Templates and Functional Scope for the Devices 7SJ82/7SJ85

ANSI Function Abbr.

Available in 7SJ82

Available in 7SJ85

Template 1

Template 2

Template 3

Template 4

Template 5

Template 6

Template 7
81U Underfrequency protection f< x x
81U Underfrequency load shedding x x
81R Rate of frequency change protection df/dt x x
Vector-jump protection x x
86 Lockout x x 4 4 4 4 x x x
87C Differential protection, capacitor bank x x x
87V Voltage differential protection, capac- ΔV x
itor bank
87N Restricted ground-fault protection ΔIN x x
90V Voltage controller x x
Arc Arc protection x x
Prot
DIGFP Directional intermittent ground-fault x x
protection
IGFP Intermittent ground-fault protection x x
FL Fault locator, single-side FL-one x x
PMU Synchrophasor measurement PMU x x
SOTF Instantaneous tripping at switch onto SOTF x x x x x x
fault
Monit Circuit-breaker wear monitoring x x
VSEL Voltage measuring-point selection x x
20mA 20-mA unit Ethernet x x
MT
20mA 20-mA unit serial x x
MS
RTDMT RTD unit Ethernet x x
RTDMS RTD unit Serial x x
Signaling-voltage supervision x x
Measuring-voltage failure detection x x x x
CB Test x x x x x x x x x
Interlocking x x 4 4 4 4 x x x
I-jump detection x x
V-jump detection x x
Pulse metered value x x
Measured values, standard x x x x x x x 2 x
User-defined function block x x
Measured values, extended: Min, Max, x x
Avg
Switching statistic counters x x
CFC (Standard, control) x x x x x x x x x
CFC arithmetic x x
Switching sequences function x x
Inrush-current detection x x x x x x

210 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Applications
4.2 Application Templates and Functional Scope for the Devices 7SJ82/7SJ85

ANSI Function Abbr.

Available in 7SJ82

Available in 7SJ85

Template 1

Template 2

Template 3

Template 4

Template 5

Template 6

Template 7
External trip initiation x x
Control x x 4 4 4 4 x x x
Fault recording of analog and binary x x x x x x x x x
signals
Monitoring and supervision x x x x x x x x x
Protection interface, serial x x
Capacitor bank x x x 2 x
Circuit breaker x x x x x x x x x
Circuit breaker [control] x x
Circuit breaker [status only] x x
Disconnector x x 3 3 3 3
Disconnector [status only] x x
Tap changer x x
Analog unit x x
Communication modules x x x x x x x x x
Access control x x x x x x x x x
Security logging x x x x x x x x x
Temperature acquisition via communi- x x
cation protocol
Point-on-wave switching7 x
Function-points class: 0 0 30 45 90 295 80

7 You could find the description of this function in the Point-on-Wave Switching Function Manual.

SIPROTEC 5, 7SJ82/7SJ85, Manual 211


C53000-G5040-C017-A, Edition 06.2019
212 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
5 Function-Group Types

5.1 Function-Group Type Voltage/current 3-Phase 214


5.2 Function-Group Type Voltage/current 1-Phase 221
5.3 Function-Group Type Voltage 3-Phase 227
5.4 Function-Group Type Capacitor Bank 230
5.5 Function-Group Type Capacitor Bank Differential Protection 243
5.6 Function-Group Type Analog Units 256
5.7 Function-Group Type Circuit Breaker 319
5.8 Process Monitor 338

SIPROTEC 5, 7SJ82/7SJ85, Manual 213


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.1 Function-Group Type Voltage/current 3-Phase

5.1 Function-Group Type Voltage/current 3-Phase

5.1.1 Overview

In the Voltage-current 3-phase function group, you can use all the functions for protection and supervision
of a protected object or equipment that allows 3-phase current and voltage measurement. The function group
also contains the operational measurement for the protected object or equipment (on this topic, see chapter
10 Measured Values, Energy Values, and Supervision of the Primary System).
You will find the Voltage-current 3-phase function group under each device type in the Global DIGSI 5 library.
You will find all protection and supervision functions that you can use for this function-group type in the func-
tion group Voltage-current 3-phase. The functions are described in chapter 6 Protection and Automation
Functions.
You can find more information on the embedding of the functions in the device in chapter 2 Basic Structure of
the Function. You can find the function scope of the application templates for the various device types in
chapter 4 Applications.

5.1.2 Structure of the Function Group

The function group always contains the following blocks:

• Protected Object/Equipment Data (FB General)

• Operational measured values

• Process monitor

• Output logic of the function group

• Reset the LED group


These blocks are essential for the function group under all circumstances, so they cannot be loaded or deleted.
You can load the protection and supervision functions required for your application in the function group. The
functions are available in the Global DIGSI 5 library. Functions that are not needed can be deleted from the
function group.
The following figure shows the structure of the function group Voltage-current 3-phase.

[dwfgui3p-301112-01.tif, 4, en_US]

Figure 5-1 Structure of the Voltage-Current 3-Phase Function Group

214 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.1 Function-Group Type Voltage/current 3-Phase

The function group has interfaces with:

• The measuring points

• The Circuit-breaker function group

Interface with Measuring Points


The function group receives the required measured values via its interfaces with the measuring points. If you
are using an application template, the function group is already connected to the necessary measuring points.
If you add functions to the function group, they will automatically receive the measured values from the
correct measuring points. If you add protection functions to the function group but the necessary measuring
point is not connected, DIGSI 5 reports an inconsistency. Configure the measuring points in DIGSI 5 via the
Function group connections Editor. You can find more detailed information in chapter 2 Basic Structure of
the Function.
The function group has the following interfaces with the measuring points:

• 3-phase current
The measurands from the 3-phase current system are supplied via this interface. Depending on the
connection type of the transformers, these are, for example, IA, IB, IC, IN or 3I0. All values that can be
calculated from the measurands are also provided via this interface. The function group must always be
connected to the I-3ph measuring point.
You can connect the 3-phase current interface to a maximum of four 3-phase current measuring points
(for example, for 1 1/2 circuit-breaker layouts). If 2 current measuring points have been connected with
the 3-phase current interface, the total current is also determined from measured values from both
measuring points in the function group. All functions in the function group have access to these values.

• 3-phase voltage (optional)


The measurands from the 3-phase voltage system are supplied via this interface. There are various types
of transformer connections possible. All values that can be calculated from the measurands are also
provided via this interface. Connecting the function group to the V 3ph measuring point is optional.
You can connect multiple measuring points with this interface. You can find more information in chapter
6.53 Voltage Measuring-Point Selection.
If you want to test or change the connection between the voltages and the V-3ph measuring point,
double-click in the DIGSI 5 project tree → (Name of the device) Measuring point routing (Connection
type = 3 phase-to-ground voltage). For more information, please refer to the description of the power-
system data starting in chapter 6.1 Power-System Data.

Interface to the Circuit-Breaker Function Group


All required data is exchanged between the Voltage-current 3-phase function group and the Circuit-breaker
function group via the interface of the Circuit-breaker function group.
This data includes, for example, the pickup and operate indications of the protection functions sent in the
direction of the Circuit-breaker function group and, for example, the circuit-breaker position information in
the direction of the protection function groups.
The Voltage-current 3-phase function group is connected to one or more Circuit-breaker function groups.
This connection generally determines:

• Which circuit breaker(s) is/are activated by the protection functions of the protection function group

• Starting the Circuit-breaker failure protection function (if available in the Circuit-breaker function group)
through the protection functions of the connected protection function group

• Starting the Automatic reclosing function (AREC, if available in the Circuit-breaker function group)
through the protection functions of the connected Protection function group
Besides the general allocation of the protection function group to the Circuit-breaker function groups, you can
also configure the interface for certain functionalities in detail. Configure the details in DIGSI 5 using the
Circuit-breaker interaction Editor in the protection function group.

SIPROTEC 5, 7SJ82/7SJ85, Manual 215


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.1 Function-Group Type Voltage/current 3-Phase

In the detail configuration of the interface, you define:

• Which operate indications of the protection functions go into the generation of the trip command

• Which protection functions start the automatic reclosing function

• Which protection functions start the Circuit-breaker failure protection function


If you are using an application template, the function groups are already connected to each other, because
this connection is absolutely essential to ensure proper operation. You can modify the connection in DIGSI 5
via the Function-group connections Editor.
You can find more detailed information in chapter 2.1 Function Embedding in the Device.
If the connection is missing, DIGSI 5 reports an inconsistency.

Protected Object/Equipment Data (FB General)


The rated voltage and rated current as well as the neutral-point treatment of the protected object or the
equipment are defined here. These data apply to all functions in the Voltage-current 3-phase function group.

Resetting the LED Group


Using the Reset the LED group function, you can reset the stored LEDs of the functions in one specific func-
tion group while the activated, stored LEDs of other functions in other function groups remain activated.
You can find more detailed information in chapter 3.1.10 Resetting Stored Indications of the Function Group .

Process Monitor
The process monitor is always present in the Voltage-current 3-phase function group and cannot be
removed.
The process monitor provides the following information in the Voltage-current 3-phase function group:

• Current-flow criterion:
Detection of an open/activated protected object/equipment based on the flow of leakage current

• Closure detection:
Detection of the switching on of the protected object/equipment

• Cold-load pickup detection (optional, only for protection devices):


These data apply to all functions in the Voltage-current 3-phase function group.
The description of the process monitor begins in chapter 5.8 Process Monitor.

Operational Measured Values


The operational measured values are always present in the Voltage-current 3-phase function group and
cannot be removed.
The following table shows the operational measured values of the Voltage-current 3-phase function group:

Table 5-1 Operational Measured Values of the Voltage-Current 3-Phase Function Group

Measured Values Primary Secon- % Referenced to


dary
IA, IB, IC Phase currents A A Rated operating current of the primary values
3I0 Calculated zero-sequence A A Rated operating current of the primary values
current
IN Neutral-point phase current A A Rated operating current of the primary values
INS Sensitive ground current A mA Rated operating current of the primary values
VA, VB, VC Phase-to-ground voltages kV V Rated operating voltage of the primary values/
√3
VAB, VBC, VCA Phase-to-phase voltages kV V Rated operating voltage of the primary values

216 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.1 Function-Group Type Voltage/current 3-Phase

Measured Values Primary Secon- % Referenced to


dary
V0 Zero-sequence voltage kV V Rated operating voltage of the primary values/
√3
VNG Neutral-point displacement kV V Rated operating voltage of the primary values/
voltage √3
f Frequency Hz Hz Rated frequency
Ptotal Active power MW W Active power of the primary values
(total power) √3 · Vrated · Irated
Qtotal Reactive power Mvar var Reactive power of the primary values
(total power) √3 · Vrated · Irated
Stotal Apparent power MVA VA Apparent power of the primary values
(total power) √3 · Vrated · Irated
Cos φ Active factor (abs) (abs) 100 % corresponds to cos φ = 1
PA, PB, PC Phase-related active power MW W Active power of the phase
Vrated phsx · Irated phsx
QA, QB, QC Phase-related reactive power Mvar var Reactive power of the phase
Vrated phsx · Irated phsx
SA, SB, SC Phase-related apparent MVA VA Apparent power of the phase
power Vrated phsx · Irated phsx

The operational measured values are explained in more detail in chapter 10.3 Operational Measured Values.

Inversion of Power-Related Measured and Statistical Values (FB General)


The following directional values calculated in operational measured values are defined positively in the direc-
tion of the protected object.

• Power

• Active factor

• Energy

• Minimum, maximum values

• Average values
With the P, Q sign parameter, you can invert the sign of these operational measured values such that a
power flow from the line to the busbar is displayed positively.
You can find more information on this in chapter 10.1 Overview of Functions.

Output Logic
The output logic treats the pickup and trip signals of the protection and supervision functions that are avail-
able in the function group separately, in a pickup logic and a trip logic, respectively. The pickup and trip logic
generate the overreaching indications (group indications) of the function group. These group indications are
transferred via the Protection information interface to the Circuit-breaker function group and are processed
further there.
The pickup signals of the protection and supervision functions in the Voltage-current 3-phase function group
are combined in a phase-selective manner and output as a group indication.

SIPROTEC 5, 7SJ82/7SJ85, Manual 217


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.1 Function-Group Type Voltage/current 3-Phase

[lo_anrlin, 3, en_US]

Figure 5-2 Creation of the Pickup Indication of the Voltage-Current 3-Phase Function Group

The trip signals from the protection and supervision functions of the Voltage-current 3-phase function group
always result in 3-pole tripping of the device.

[loauslin-150211-01.tif, 3, en_US]

Figure 5-3 Creation of the Operate Indication of the Voltage-Current 3-Phase Function Group

5.1.3 Application and Setting Notes

Interface to the Circuit-Breaker Function Group


With this, you define which circuit breaker(s) is/are affected by the protection functions of the Protection func-
tion group. A feasible default setting has already been provided in the application templates. You can find
more information in chapter 2.

Protected Object/Equipment Data (FB General)


The set data applies to all functions in the function group.
Set the protected object/equipment data for your specific application.

Parameter: Rated current

• Default setting (_:9451:101) Rated current = 1000 A


With the Rated current parameter, you can set the primary rated current of the protected object or equip-
ment. The Rated current parameter is significant for protection functions if current values are set in
percentages. In this case it is the reference value. In addition it is the reference value for the measured values
in percent.
If the device works with the IEC 61850 protocol, then you change only the setting value of the parameter via
DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.

Parameter: Rated voltage

• Default setting (_:9451:102) Rated voltage = 400.00 kV


With the Rated voltage parameter, you can set the primary rated voltage of the protected object or equip-
ment. The Rated voltage parameter is significant for protection functions if current values are set in
percentages. In this case it is the reference value. In addition it is the reference value for the measured values
in percent.

218 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.1 Function-Group Type Voltage/current 3-Phase

If the device works with the IEC 61850 protocol, then you change only the setting value of the parameter via
DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.

Parameter: Power-sys. neutral point

• Default setting (_:9451:149) Power-sys. neutral point = grounded


With the Power-sys. neutral point parameter, you specify whether the system neutral is grounded,
isolated or suppress. coil grounded (grounded via arc-suppression coil). Currently, the parameter
does not affect any protection function; only if the Automatic reclosing function uses the voltage measure-
ment.
You can find more information in chapter 6.46.1 Overview of Functions.

Parameter: P, Q sign

• Default setting (_:9451:158) P, Q sign = not reversed


The power and energy values are defined by the manufacturer such that power in the direction of the
protected object is considered positive. You can also positively define the power output by the protected
object (for example, as seen by the consumer). With the P, Q sign parameter, you can invert the sign for
these components. This inversion does not influence any protection function.

5.1.4 Write-Protected Settings

The settings listed here are used primarily for understanding during configuration of the function groups. They
are calculated on the basis of other settings and cannot be directly changed.
Addr. Parameters C Range of Values Default Setting
Network data
_:103 General:rated apparent power 0.20 MVA to 5 000.00 MVA 692.82 MVA

NOTE

i You can find more detailed information on the Process monitor in chapter 5.8 Process Monitor.

5.1.5 Settings

Addr. Parameter C Setting Options Default Setting


Rated values
_:9451:101 General:Rated current 1 A to 100000 A 1000 A
_:9451:102 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Power-system data
_:9451:149 General:Power-sys. neutral • grounded grounded
point
• suppress. coil grounded
• isolated
Measurements
_:9451:158 General:P, Q sign • not reversed not reversed
• reversed

SIPROTEC 5, 7SJ82/7SJ85, Manual 219


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.1 Function-Group Type Voltage/current 3-Phase

5.1.6 Information List

No. Information Data Class Type


(Type)
General
_:9451:52 General:Behavior ENS O
_:9451:53 General:Health ENS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Reset LED Group
_:7381:500 Reset LED Group:>LED reset SPS I
_:7381:320 Reset LED Group:LED have been reset SPS O
Closure detec.
_:1131:4681:500 Closure detec.:>Disconnector open SPS I
_:1131:4681:300 Closure detec.:Closure SPS O

220 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.2 Function-Group Type Voltage/current 1-Phase

5.2 Function-Group Type Voltage/current 1-Phase

5.2.1 Overview

In the Voltage-current 1-phase function group, all functions can be used for protecting and for monitoring a
protection object or equipment that allow a 1-phase current and voltage measurement or a zero-sequence
voltage measurement via the 3-phase voltage measuring point. The function group also contains the opera-
tional measurement for the protected object or equipment (see chapter 10 Measured Values, Energy Values,
and Supervision of the Primary System).

5.2.2 Structure of the Function Group

The Voltage-current 1-phase function group has interfaces to the measuring points and the Circuit-breaker
function group.

[dw1spstr-040117-01.vsd, 1, en_US]

Figure 5-4 Structure of the Voltage-Current 1-Phase Function Group

Interface with Measuring Points


You connect the Voltage-current 1-phase function group to the current and voltage measuring points via the
interfaces to the measuring points. At least one measuring point has to be connected. The other is optional.
This assignment can only be made in DIGSI via Project tree → Function group connections. To connect the
interfaces, set a cross at the intersection between the row and column in the matrix.
The function group has the following interfaces to the measuring points:

• 1-phase current
The 1-phase current measured values are provided via this interface.
You can only connect a 1-phase current measuring point to the 1-phase current interface.

• Voltage 1-phase or Voltage 3-phase


You can connect the voltage interface of the Voltage-current 1-phase function group with a 1‑phase or
a 3-phase measuring point. The calculated zero-sequence voltage or the measured residual voltage are
available for connection with a 3-phase measuring point. The phase-to-ground voltages are not available
in the function group Voltage-current 1-phase. You can use both connection types at the same time.
You configure the 1-phase voltage measuring points via the voltage interface (see the following figure).

SIPROTEC 5, 7SJ82/7SJ85, Manual 221


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.2 Function-Group Type Voltage/current 1-Phase

[scVI1ph_V1ph, 1, en_US]

Figure 5-5 Connecting Measuring Points to the Voltage-Current 1-Phase Function Group

If you select the voltage type VN broken-delta for the 1-phase voltage measuring point in the measuring
point routing (see the following figure), the device measures the residual voltage VN at the broken-delta
winding. The residual voltage is converted into the voltage equivalent of the zero-sequence voltage. This
converted voltage is used as the voltage input for all functions in the Voltage-current 1-phase function
group.

[scvnopen, 1, en_US]

Figure 5-6 Selection of the VN broken-delta Voltage Type for the 1-Phase Voltage Measuring Point

The zero-sequence voltage calculated from the 3-phase voltage system or the measured residual voltage is
available via the voltage interface (see figure below).

[scVI1ph_V3ph, 1, en_US]

Figure 5-7 Connecting Measuring Points 3-Phase Voltage and 1-Phase Current to the 1-Phase Voltage-
Current Function Group

You can connect the voltage interface of the Voltage-current 1-phase function group with precisely one 3-
phase voltage measuring point. 3 types of 3-phase voltage measuring-point connection are supported. With
the different connection types, the type of voltage input for the functions in the Voltage-current 1-phase
function group also changes.

222 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.2 Function-Group Type Voltage/current 1-Phase

The following table shows the properties of the voltage input for the Voltage-current 1-phase function group
depending on the connection types.
Connection Type of the 3- Voltage Input
Phase Voltage Measuring
Point
3 ph-to-gnd voltages The zero-sequence voltage is calculated from the phase-to-ground voltages
and used as a voltage input for all functions.
3 ph-to-gnd volt. + VN The residual voltage VN is converted into the voltage equivalent of the zero-
3 ph-to-ph volt. + VN sequence voltage. This converted voltage is used as a voltage input for func-
tions.

Interface to the Circuit-Breaker Function Group


All required data is exchanged between the Voltage-current 1-phase function group and the Circuit-breaker
function group via the interface of the Circuit-breaker function group.
In this example, the pickup and operate indications of the protection functions are exchanged in the direction
of the Circuit-breaker function group.
You must connect the Voltage-current 1-phase function group with the Circuit-breaker function group. This
assignment can only be made in DIGSI via Project tree → Function group connections. To connect the inter-
faces, set a cross at the intersection between the row and column in the matrix. If the interface is not
connected, the functions operate as supervision functions in the Voltage-current 1-phase function group.

[sc1stspc-190214-01, 1, en_US]

Figure 5-8 Connecting Voltage-Current 1-Phase Function Group with Circuit-Breaker Function Group

Fundamental Components
The fundamental components are always present in the Voltage-current 1-phase function group and cannot
be deleted.
The following table shows the fundamental components of the Voltage-current 1-phase function group:

Table 5-2 Fundamental Components of the Voltage-Current 1-Phase Function Group

Measured Values Primary Secondary % Referring to


I 1-phase current A A Parameter Rated operating current
V8 1-phase voltage kV V Parameter Rated operating voltage
V0 9 Zero-sequence voltage kV V Parameter Rated operating
voltage /√3
VN10 Residual Voltage kV V Parameter Rated operating
voltage /√3

You can find the parameters Rated operating current and Rated operating voltage in the
General function block of the Voltage-current 1-phase function group.

8 The 1-phase voltage V is only visible if it is connected to a 1-phase voltage measuring point.
9 The zero-sequence voltage V0 is only visible if it is connected to a 3-phase voltage measuring point with the 3-phase phase-to-
ground voltage connection type.
10 The residual voltage VN is only visible if it is connected to a 3-phase voltage measuring point with the connection type 3-phase
phase-to-ground voltage + VN or 3-phase phase-to-phase voltage + VN.

SIPROTEC 5, 7SJ82/7SJ85, Manual 223


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.2 Function-Group Type Voltage/current 1-Phase

Operational Measured Values


The operational measured values are not preconfigured in the Voltage-current 1-phase function group. You
can instantiate them in the function group or delete them from the function group. You can find the opera-
tional measured values in the DIGSI library, in the folder FG Voltage-current 1-phase under Measurements
→ Operational values.

[scui1pom, 1, en_US]

Figure 5-9 Operational Measured Values

Table 5-3 Operational Measured Values of the Voltage-Current 1-Phase Function Group

Measured Values Primary Secondary % Referring to


I 1-phase current A A Parameter Rated operating current
V11 1-phase voltage kV V Parameter Rated operating voltage
VN 12 Residual voltage kV V Parameter Rated operating
voltage/√3
V013 Zero-sequence voltage kV V Parameter Rated operating
voltage/√3
f Frequency Hz Hz Parameter Rated frequency
P Active power MW W Parameter Rated apparent power
Q Reactive power Mvar var Parameter Rated apparent power

You can find the parameters Rated operating current, Rated operating voltage, and Rated
apparent power in the General function block of the Voltage-current 1-phase function group. You can
find the parameter Rated frequency in the General function block of the Device settings.

NOTE

i The frequency can be calculated from the voltage or current measured value.
The active and reactive power are only displayed if the voltage and the 1-phase current are connected to
the function group. If the connected voltage is a phase-to-ground voltage (VA, VB , VC) or any voltage Vx,
the specific power values are displayed. Otherwise the power is displayed as not available.

5.2.3 Application and Setting Notes

NOTE

i Prior to creation of the protection functions in the function group, these functions should first be
connected to the appropriateCircuit-breaker function group.

11 V is only visible if it is connected to a 1-phase voltage measuring point.


12 VN is only visible if it is connected to a 3-phase voltage measuring point of the type 3 ph-to-gnd volt. + VN or 3 ph-to-ph volt. + VN.
13 V0 is only visible if it is connected to a 3-phase voltage measuring point of the type 3 ph-to-gnd voltages.

224 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.2 Function-Group Type Voltage/current 1-Phase

Parameter: Rated current

• Default setting (_:9421:101) Rated current = 1000 A


The (_:9421:101) Rated current parameter is used to set the primary rated current of the protected
object. The (_:9421:101) Rated current specified here is the reference value for the percentage-meas-
ured values and setting values made in percentages.

Parameter: Rated voltage

• Default setting (_:9421:102) Rated voltage = 400.00 kV


With the Rated voltage parameter, you set the primary rated voltage of the protected object. The Rated
voltage set here is the reference value for all voltage-related percentage values in the Circuit-breaker func-
tion group.
If you connect the Voltage-current 1-phase function group with the 1-phase measuring point, the following
applies:

• With connection type VAB, VBC, VCB, or VN , you set the Rated voltage parameter as the phase-to-phase
voltage.

• With the connection type VA, VB, VC, or VN (broken-delta winding), you set the Rated voltage parameter as the
phase-to-ground voltage.

• With the connection type VX, you set the Rated voltage parameter as either the phase-to-phase
voltage or the phase-to-ground voltage

Parameter: P, Q sign

• Default setting (_:9421:150) P, Q sign = not reversed


The power values are set at the factory so that power in the direction of the protected object is considered
positive. You can also define the power output by the protected object as positive. With the P, Q sign
parameter, you can invert the signs of active and reactive power. This inversion has no effect on the protec-
tion functions.

5.2.4 Write-Protected Settings

The settings listed here are used primarily for understanding during configuration of the function groups. They
are calculated on the basis of other settings and cannot be directly changed.
Addr. Parameter C Setting Options Default Setting
Rated values
_:9421:103 General:Rated apparent -1.00 MVA to -1.00 MVA 0.00 MVA
power
Power-system data
_:9421:214 General:M I-1ph uses 0 to 100 0
MeasP with ID
_:9421:223 General:CT mismatch M 0.00 to 100.00 0.00
I-1ph

5.2.5 Settings

Addr. Parameter C Setting Options Default Setting


Rated values
_:9421:101 General:Rated current 1 A to 100 000 A 1000 A
_:9421:102 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV

SIPROTEC 5, 7SJ82/7SJ85, Manual 225


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.2 Function-Group Type Voltage/current 1-Phase

Addr. Parameter C Setting Options Default Setting


Measurements
_:9421:150 General:P, Q sign • not reversed not reversed
• reversed

5.2.6 Information List

No. Information Data Class Type


(Type)
General
_:9421:52 General:Behavior ENS O
_:9421:53 General:Health ENS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Reset LED Group
_:13381:500 Reset LED Group:>LED reset SPS I
_:13381:320 Reset LED Group:LED have been reset SPS O

226 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.3 Function-Group Type Voltage 3-Phase

5.3 Function-Group Type Voltage 3-Phase

5.3.1 Overview

In the Voltage 3-phase function group, all functions can be used for protecting and for monitoring a
protected object or equipment which allows a 3-phase voltage measurement. The function group also
contains the operational measurement for the protected object or equipment (on this topic, see chapter
10 Measured Values, Energy Values, and Supervision of the Primary System). Applicable functions are, for
example, Voltage protection or Frequency protection.

5.3.2 Structure of the Function Group

The Voltage 3-phase function group has interfaces to the measuring points and the Circuit-breaker function
group.

[dw3spann-300913, 1, en_US]

Figure 5-10 Structure of the Voltage 3-Phase Function Group

Interface with Measuring Points


You connect the Voltage 3-phase function group to the voltage measuring points via the interface to the
measuring points. This assignment can only be made in DIGSI via Project tree → Function group connec-
tions. To connect the interfaces, set a cross at the intersection between the row and column in the matrix.

[sc3span1-190214-01, 1, en_US]

Figure 5-11 Connecting Measuring Points to the Voltage 3-Phase Function Group

If you add functions to the Voltage 3-phase function group, these are connected to the measuring point auto-
matically.
You can connect multiple measuring points with this interface. You can find more information in chapter
6.53 Voltage Measuring-Point Selection.
The measurands from the 3-phase voltage system are supplied via the V 3-ph interface. Depending on the
connection type of the transformers, for example, VA, VB, VC, Vgnd. All values that can be calculated from the
measurands are also provided via this interface.

Interface to the Circuit-Breaker Function Group


All required data is exchanged between the Voltage 3-phase function group and the Circuit-breaker function
group via the interface of the Circuit-breaker function group.

SIPROTEC 5, 7SJ82/7SJ85, Manual 227


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.3 Function-Group Type Voltage 3-Phase

In this example, the pickup and operate indications of the protection functions are exchanged in the direction
of the Circuit-breaker function group.
You must connect the Voltage 3-phase function group with the Circuit-breaker function group. This assign-
ment can be made in DIGSI only via Project tree → Connect function group. To connect the interfaces, set a
cross at the intersection between the row and column in the matrix.

[sc3span2-190214-01, 1, en_US]

Figure 5-12 Connecting Voltage 3-Phase Function Group with Circuit-Breaker Function Group

Operational Measured Values


The operational measured values are always present in the Voltage 3-phase function group and cannot be
deleted.
The following table shows the operational measured values of the Voltage 3-phase function group:

Table 5-4 Operational Measured Values of the Voltage 3-Phase Function Group

Measured Values Primary Secondary % with respect to


VA, VB, VC Phase-to-ground voltages kV V Operating rated voltage of primary
values/√3
VAB, VBC, VCA Phase-to-phase voltage kV V Rated operating voltage of the
primary values
V0 Zero-sequence voltage kV V Operating rated voltage of primary
values/√3
VNG Neutral-point displacement kV V Operating rated voltage of primary
voltage values/√3
f Frequency Hz Hz Rated frequency

5.3.3 Application and Setting Notes

NOTE

i Before creating the protection functions in the function group, you should first connect these functions to
the appropriate Circuit-breaker function group.

Parameter: Rated voltage

• Default setting (_:9421:102) Rated voltage = 400.00 kV


With the Rated voltage parameter, you set the primary rated voltage. The Rated voltage set here is the
reference value for the percentage-measured values and setting values made in percentages.

5.3.4 Settings

Addr. Parameter C Setting Options Default Setting


Rated values
_:9421:102 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV

228 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.3 Function-Group Type Voltage 3-Phase

5.3.5 Information List

No. Information Data Class Type


(Type)
General
_:9421:52 General:Behavior ENS O
_:9421:53 General:Health ENS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Reset LED FG
_:4741:500 Reset LED Group:>LED reset SPS I
_:4741:320 Reset LED Group:LED have been reset SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 229


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

5.4 Function-Group Type Capacitor Bank

5.4.1 Overview

In the Capacitor bank function group, all the functions that are necessary for protecting and monitoring a
capacitor bank can be used.
You can find the Capacitor bank function group under 7SJ82/7SJ85 device types in the Global DIGSI 5 Library.
The Capacitor bank function group contains all of the protection and supervision functions that you can use
for this device type.
Some of these functions are exclusively used for protecting capacitor banks, and others are universal standard
functions which can be used for other protected objects as well. You find the exclusive protection functions in
the directory Capacitor-bank protection.

[scfgcapb-250314-01, 2, en_US]

Figure 5-13 Capacitor Bank Function Group - Functional Scope for Device Type 7SJ85

For more information about the embedding of the functions in the device, refer to chapter 2. For information
about the overall functional scope of the application templates for the various device types, refer to chapter 4.

230 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

5.4.2 Structure of the Function Group

The Capacitor bank function group always contains the following functionality:

• Protected object/equipment data (function block General)

• Operational measured values

• Capacitor bank device status and blocking of circuit-breaker closing during discharging (function block
General)

• Process monitor

• Global compensation (function block General)

• Output logic of the function group

• Reset LED group


This functionality is essential for the Capacitor bank function group, so it cannot be loaded or deleted.
You can load the protection functions and supervision functions required for your application in the Capacitor
bank function group. The functions are available from the Global DIGSI 5 Library. Functions that are not
needed can be deleted from the function group.

[Dwstrcap-20140619-01.vsd, 3, en_US]

Figure 5-14 Structure of the Capacitor Bank Function Group

The Capacitor bank function group has interfaces with the following parts:

• Measuring points

• Circuit-breaker function group

SIPROTEC 5, 7SJ82/7SJ85, Manual 231


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

Interfaces with the Measuring Points


The Capacitor bank function group receives the required measured values via the interfaces with the meas-
uring points. If you are using an application template, the Capacitor bank function group is already connected
to the specific measuring points.
You can find more detailed information in Chapter 2.
The Capacitor bank function group has the following 6 interfaces with the measuring points. The universal
standard functions only work with the standard interfaces 3-phase current and/or 3-phase voltage;
the other 4 interfaces are provided for the functions which are exclusively used for the capacitor banks. Please
also refer to the example given below.
The Capacitor bank function group has the following interfaces with the measuring points:

• 3-phase current:
The measurands from the 3-phase current system are supplied via this interface. Depending on the
connection type of the current transformers, the measurands can be for example IA, IB, IC, IN, or 3I0. All
values that can be calculated from the measurands are also provided via this interface.
The Capacitor bank function group must always be connected to the 3-phase current measuring point.
You can connect the 3-phase current measuring point interface to the maximum of two 3-phase
current measuring points. If 2 current measuring points have been connected to the 3-phase current
interface, the total current is determined by adding the measured values from both measuring points in
the function group. The functions in the Capacitor bank function group evaluate the total current.
For a 3-phase current measuring point connected to the 3-phase current interface of the Capac-
itor bank function group, the following connection types are not allowed:
– 3-phase, 2 primary CT
– 3ph,2prim.CT + IN-sep
– 2ph, 2p. CT + IN-sep

• 3-phase voltage (optional):


The measurands from the 3-phase voltage system are supplied via this interface. Depending on the
connection type of the voltage transformers, these can be for example VA, VB, VC, VN, or 3V0. All values
that can be calculated from the measurands are also provided via this interface.
The connection of the 3-phase voltage interface is optional. This connection is only required if protec-
tion functions or supervision functions are applied, which require voltage measurements.

• 3-phase voltage CB tap (optional):


The measurands of a 3-phase tap voltage within a capacitor bank are supplied via this interface.
The connection of the 3-phase voltage CB tap interface is optional. You can connect the 3-phase voltage
CB tap interface to a maximum of one 3-phase voltage measuring point.

• Voltage unbalance (optional):


The unbalanced-voltage measurands (for example, an isolated neutral point of the capacitor bank) are
supplied via this interface.
The connection of the voltage unbalance interface is optional. You can connect the voltage unbalance
interface to a maximum of one 1-phase voltage measuring points.

• Current unbalance (optional):


The unbalanced-current measurands are supplied via this interface.
The connection of the current unbalance interface is optional. You can connect the current unbalance
interface to a maximum of two 3-phase current measuring points and six 1-phase current measuring
points. The interface allows mixed connections to 3-phase current measuring point and 1-phase current
measuring point; however the sum of the connections is no more than 6.
For an overview which functions are applicable on this interface, please refer to Figure 1-5.

232 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

• 3-phase current RLC (optional)


The measurands from a tuning or filtering section (R, L, or C) of a capacitor bank are supplied via this
interface.
The connection of the 3-phase current RLC interface is optional. You can connect the 3-phase current
RLC interface to a maximum of nine 3-phase current measuring points.
For an overview which functions are applicable on this interface, please refer to Figure 5-15.

Example
The following figure shows an example of a capacitor in H-configuration and tuning section. In the single line,
the primary current and voltage measurement are shown. The required device measuring points and their
connections to the function group interfaces are shown as well. In addition, it is indicated which protection
function receives its measuring value from which measuring point.

[dwasscap-180713-01.tif, 2, en_US]

Figure 5-15 An Example of Assignment of Measuring Points to the Capacitor-Bank Functions

You can connect the Capacitor bank function group to the current and voltage measuring points via inter-
faces. You make this assignment in DIGSI via Project tree → Function group connections. To connect the
interfaces, set a cross at the intersection between the row and column in the matrix.

[scrconba-110314-03, 3, en_US]

Figure 5-16 Connecting Measuring Points to the Capacitor Bank Function Group

SIPROTEC 5, 7SJ82/7SJ85, Manual 233


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

For the protection functions applied on the interfaces 3-phase current and 3-phase voltage, if you add these
functions to the Capacitor bank function group, these functions will automatically receive the measured
values from the correct measuring points. If you add protection functions to the function group but the neces-
sary interface is not connected to any measuring point, DIGSI 5 reports an inconsistency. Configure the meas-
uring points in DIGSI 5 using the Function group connections editor.
For the protection functions applied on the interfaces Current unbalance and 3-phase current, you have to
select the desired measuring points via a setting MP selection, which offers a list of all measuring points
connected to the specific interface. The setting MP selection is located on the setting page of the protec-
tion function.
The following figure shows an overview of the protection functions and the interface assignment in the
Capacitor bank function group.

[DwCapBank-180713-01, 4, en_US]

Figure 5-17 Overview of the Protection Functions and Interface Assignment in the Capacitor Bank Function
Group

234 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

Interfaces with Circuit-Breaker Function Group


All required data are exchanged between the protection function group and the Circuit-breaker function
group via the interface with the Circuit-breaker function group. These data include, for example, the pickup
and operate indications of the protection functions sent in the direction of the Circuit-breaker function group
and, for another example, the information about the circuit-breaker condition sent in the direction of the
protection function group.
The Capacitor bank function group is connectable to a Circuit-breaker function group. This connection
generally determines:

• Which circuit breaker is activated by the protection functions of the Capacitor bank function group

• Starting of the Circuit-breaker failure protection function (if available in the Circuit-breaker function
group) through the protection functions of the connected Capacitor bank function group

• Starting of the Automatic reclosing function (if available in the Circuit-breaker function group) through
the protection functions of the connected Capacitor bank function group

NOTE

i For capacitor bank protection, the Automatic reclosing function is not applied in most cases. However,
due to flexibility and standardization, the respective interface is offered.

[scrconb1-180713-01.tif, 1, en_US]

Figure 5-18 Connecting Capacitor Bank Function Group with Circuit-Breaker Function Group

Besides the general assignment of the Capacitor bank function group to the Circuit-breaker function group,
you can also configure the interface for certain functionalities in detail. Configure the details in DIGSI 5 using
the Circuit breaker interaction editor in the Capacitor bank function group.
In the detailed configuration of the interface, define:

• Which operate indications of the protection functions go into the generation of the trip command

• Which protection functions start the Circuit-breaker failure protection function

• Which protection functions start the Automatic reclosing function

[scconcap-150713-01.tif, 2, en_US]

Figure 5-19 Connecting Protection Functions and Stage Using the Circuit-Breaker Interaction Editor

SIPROTEC 5, 7SJ82/7SJ85, Manual 235


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

If an application template is used, the function groups have already been connected to each other because
this link is essential to ensure proper operation. You can modify the link in DIGSI 5 using the Function-group
connections editor.
You can find more information in chapter 2.1 Function Embedding in the Device. If this link is missing, DIGSI 5
reports an inconsistency.

Protected Object/Equipment Data (FB General)


Capacitor-bank rated and reference data are defined as well as further protected object/equipment data. The
data applies for all functions in the Capacitor bank function group.
For further information, refer to chapter 5.4.3 Application and Setting Notes.

Capacitor Bank Device Status and Blocking of Circuit-breaker Closing during Discharging (FB General)
The functionality detects whether a capacitor bank is online or offline. When the status of the capacitor bank
changes from online to offline, the signal Discharge is issued during the capacitor-bank discharging time.

[Lo-CapZap-20140617-01, 1, en_US]

Figure 5-20 Logic Diagram of Capacitor Bank Device Status and Blocking of Circuit-breaker Closing during
Discharging

The device can block the closing of the circuit breaker automatically when a capacitor bank discharges. The
configuration is made with the parameter Blk.cls.cmd.dur.discharge. If the parameter
Blk.cls.cmd.dur.discharge is set to on, the device generates a trip/open command during the
discharge time and blocks closing commands additionally, see the following figure. This blocking condition is
signaled via the message Blocked by discharge.

236 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

[Lo-discharge-20140617-01, 1, en_US]

Figure 5-21 Logic Diagram of Processing the Blocked by Discharge Signal

Global Compensation (FB General)


The Global compensation function block provides the binary input signal >Compensate to carry out the
manual compensation for all functions in the FG using compensated measuring values.
In addition, the binary input signal >Reset comp. val. is provided to reset all compensation values for the
functions using compensated measuring values.

Process Monitor
The Process monitor detects the current state of the protected object. It is always present in the function
group and cannot be removed.
For detailed description of the Process monitor, refer to 5.8.1 Overview of Functions.

Reset LED Group


The Reset LED group function block allows you to reset only the stored LEDs of the functions contained in the
respective function group, while stored LEDs activated from functions in other function groups remain active.
For more information refer to chapter 3.1.10 Resetting Stored Indications of the Function Group .

Operational, Fundamental, Symmetrical Components Measurements


The operational fundamental, symmetrical components and functional measurements are always available in
the Capacitor bank function group and cannot be deleted.

Table 5-5 Operational Measured Values (True RMS) of the Function Group Capacitor Bank

Measured Values Primary Secondary % Referenced to


IA, IB, IC Phase currents A A Rated operating current of the primary
system
IN Neutral-point phase current A A Rated operating current of the primary
system
3I0 Residual current A A Rated operating current of the primary
system
VA, VB, VC Phase-to-ground voltages kV V Rated operating voltage of the primary
system/√3
VAB, VBC, VCA Phase-to-phase voltage kV V Rated operating voltage of the primary
system

SIPROTEC 5, 7SJ82/7SJ85, Manual 237


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

Measured Values Primary Secondary % Referenced to


V0 Zero-sequence voltage kV V Rated operating voltage of the primary
system/√3
VNG Neutral-point displacement kV V Rated operating voltage of the primary
voltage system/√3
f Frequency Hz Hz Rated frequency
Ptot Active power (total power) MW – Rated operating voltage and rated oper-
ating current of the primary system
√3 · Vrated · Irated
Qtot Reactive power (total power) MVAr – Rated operating voltage and rated oper-
ating current of the primary system
√3 ·Vrated · Irated
Stot Apparent power (total power) MVA – Rated operating voltage and rated oper-
ating current of the primary system
√3 ·Vrated · Irated
Cos φ Active factor (abs) (abs) 100 % corresponds to cos φ = 1
PA, PB, PC Phase-related active power MW – Apparent power of the phase Vrated Lx ·
Irated Lx
QA, QB, QC Phase-related reactive power MVAr – Apparent power of the phase Vrated Lx ·
Irated Lx
SA, SB, SC Phase-related apparent power MVA – Apparent power of the phase Vrated Lx ·
Irated Lx

Table 5-6 Fundamental and Symmetrical Components Measurement Values of the Function Group
Capacitor Bank

Measured Values Primary Secondary % Referenced to


IA, IB, IC Phase currents A A Rated operating current of the primary
system
IN Neutral-point phase current A A Rated operating current of the primary
system
Iseq:0 Zero-sequence current A A Rated operating current of the primary
system
Iseq:1 Positive-sequence current A A Rated operating current of the primary
system
Iseq:2 Negative-sequence current A A Rated operating voltage of the primary
system
VA, VB, VC Phase-to-ground voltages kV V Rated operating voltage of the primary
system/√3
VAB, VBC, VCA Phase-to-phase voltage kV V Rated operating voltage of the primary
system
VN Neutral-point phase voltage kV V Rated operating voltage of the primary
system/√3
Vseq:0 Zero-sequence voltage kV V Rated operating voltage of the primary
system/√3
Vseq:1 Positive-sequence voltage kV V Rated operating voltage of the primary
system/√3
Vseq:2 Negative-sequence voltage kV V Rated operating voltage of the primary
system/√3

Voltage and power measurements are only available if V-3ph measuring point connected to the Capacitor
bank function group.

238 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

The energy measurements are not predefined. If required, they must be loaded from the Global DIGSI 5
Library.

Inversion of Power-Related Measured and Statistical Values (FB General)


The following values calculated in operational measured values are defined positively in the direction of the
protected object.

• Power

• Power factor

• Energy

• Minimum, maximum values of the power

• Average values of the power


With the P, Q sign setting, you can invert the sign of these operational measured values such that a power
flow from the line to the busbar is displayed positively.
More information can be found in Chapter 10.1 Overview of Functions.

Output Logic
The output logic treats the pickup and operate indications of the protection functions and supervision func-
tions in the Capacitor bank function group separately, in a pickup logic and an output logic respectively. The
pickup and output logics generate the group indications of the function group. These group indications are
transferred to the Circuit-breaker function group via the protection-information interface and are processed
further there.
The pickup and operate indications of the protection functions and the supervision functions in the Capacitor
bank function group are combined according to the following figures of group indications.

[logepiin-230812-02.tif, 1, en_US]

Figure 5-22 Generation of the Pickup Indication of the Capacitor Bank Function Group

[logeopin-230812-02.tif, 1, en_US]

Figure 5-23 Generation of the Operate Indication of the Capacitor Bank Function Group

SIPROTEC 5, 7SJ82/7SJ85, Manual 239


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

5.4.3 Application and Setting Notes

Interface to Circuit-Breaker Function Group


The Capacitor bank protection function group is linked to one Circuit-breaker function group. This Circuit-
breaker function group is assigned to the circuit breaker of the capacitor bank.

Protected Object/Equipment Data (FB General)


The following application and setting notes apply for the general data. The data are configured in the function
block General of the Capacitor bank function group and apply for all functions in the function group.

Parameter: Capacitor reference curr.

• Default setting (_:14641:101) Capacitor reference curr. = 1000 A


With the Capacitor reference curr. parameter, you set the reference current for the capacitor bank to
be protected. This Capacitor reference curr. specified here is the reference value for the percentage-
measured values and setting values made in percentages.
Depending on the user philosophy, the reference value could be the capacitor-bank rated current, which
includes harmonics, or the capacitor-bank fundamental current.

Parameter: Capacitor reference volt.

• Default setting (_:14641:102) Capacitor reference volt. = 400.00 kV


With the parameter Capacitor reference volt., you set the reference voltage of the capacitor bank to
be protected. This Capacitor reference volt. specified here is the reference value for the percentage-
measured values and setting values made in percentages.
Depending on the user philosophy, the reference value could be the system rated voltage (bus voltage), or the
capacitor rated voltage

Parameter: Capacitor element type

• Default setting (_:14641:106) Capacitor element type = fused


With the parameter Capacitor element type, you set if the capacitor elements contain internal fuses or
not. This information is required in the current-unbalance protection for the fault position annunciation.

Parameter: Blk.cls.cmd.dur.discharge

• Default setting (_:14641:107) Blk.cls.cmd.dur.discharge = off


With the parameter Blk.cls.cmd.dur.discharge, you set whether closing of the circuit breaker is
blocked automatically or not when a capacitor bank discharges.

NOTE

i If the parameter Blk.cls.cmd.dur.discharge is set to on, the device generates a trip/open command
during the discharge time.

Parameter: Discharge time

• Default setting (_:14641:108) Discharge time = 300 s


With the parameter Discharge time, you define capacitor-bank discharging duration. You get the value
from the capacitor manufacturer.

Parameter: Cap.-bank neutral point

• Default setting (_:14641:109) Cap.-bank neutral point =isolated

240 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

With the parameter Cap.-bank neutral point, you can specify whether the neutral point of capacitor
bank is isolated or grounded. This information is required when applying the function 87V voltage differ-
ential protection.

Parameter: P, Q sign

• Default setting (_:14611:158) P, Q sign =not reversed


The power and energy values are defined by the manufacturer such that power in the direction of the
protected object is considered positive. You can also define the power output by the protected object as posi-
tive. With the P, Q sign parameter, you can invert the sign for these components. This inversion does not
influence any protection function.

5.4.4 Write-Protected Settings

The settings listed here are primarily to aid understanding when configuring the function groups. They are
calculated as a function of other settings and cannot be changed directly.
Addr. Parameter C Setting Options Default Setting
Rated values
_:14641:103 General:Rated apparent -1.00 MVA to -1.00 MVA 0.00 MVA
power

NOTE

i You can find more detailed information on the Process monitor in chapter 5.7.1 Overview.

5.4.5 Settings

Addr. Parameter C Setting Options Default Setting


Rated values
_:14641:101 General:Capacitor refer- 1 A to 100000 A 1000 A
ence curr.
_:14641:102 General:Capacitor refer- 0.20 kV to 1200.00 kV 400.00 kV
ence volt.
Cap.bank data
_:14641:106 General:Capacitor • fused fused
element type
• unfused
_:14641:107 General:Blk.cls.cmd.dur. • off off
discharge
• on
_:14641:108 General:Discharge time 1 s to 1200 s 300 s
_:14641:109 General:Cap.-bank • grounded isolated
neutral point
• isolated
Measurements
_:14611:158 Further settings:P, Q • not reversed not reversed
sign
• reversed

SIPROTEC 5, 7SJ82/7SJ85, Manual 241


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.4 Function-Group Type Capacitor Bank

5.4.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Reset LED Group
_:7381:500 Reset LED Group:>LED reset SPS I
_:7381:320 Reset LED Group:LED have been reset SPS O
General
_:14641:500 General:>Compensate SPS I
_:14641:501 General:>Reset comp. val. SPS I
_:14641:300 General:Blocked by discharge SPS O
_:14641:302 General:Discharge SPS O
_:14641:301 General:Cap.bank device status SPC C

242 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

5.5 Function-Group Type Capacitor Bank Differential Protection

5.5.1 Function-Group Types

In the following graphic, you can see the structural association of the function-group types to the Capacitor
bank differential protection.

[dwfgueca-120214-01, 2, en_US]

Figure 5-24 Function-Group Types Capacitor Bank Diff

The following function-group types are summarized in the Global DIGSI 5 library: Motor diff

• Capacitor bank diff

• Capacitor bank side


You can find the description of the function groupCapacitor bank in chapter 5.4.1 Overview.
The individual function-group types are stored in the Capacitor bank diff function group folder and can be
selected. In the protection function folders, you find all protection functions which are operational in each
function group. A Capacitor bank diff function group always includes the Capacitor bank and Capacitor
bank side function groups. In total, you can assign a maximum of 3 function groups Capacitor bank or
Capacitor bank side to the Capacitor bank diff function group.
The following table shows you the number of function-group types that can be instantiated for device 7SJ85.

Table 5-7 Function-Group Types in the Device

Function-Group Type
Device Capacitor Bank Diff Capacitor Bank Capacitor Bank Side
7SJ85 Max. 2 Max. 9 Max. 9

Interconnection of the function groups is necessary so that the capacitor bank differential protection functions
properly. The Circuit-breaker function group is not listed.

Table 5-8 Assignment of Protection Function Groups to Protection Function Groups

Capacitor Bank Diff 1


Side
(2 to 3)
Capacitor bank X
Capacitor bank side 1 X

SIPROTEC 5, 7SJ82/7SJ85, Manual 243


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

Capacitor Bank Diff 1


Side
(2 to 3)
Capacitor bank side 2 X

The individual function-group types are described in the following.

5.5.2 Function-Group Type Capacitor Bank Diff

5.5.2.1 Overview
The Capacitor bank diff. function group contains the differential protection function and protection-function-
relevant measured values.
You can find more information in the chapter 10 Measured Values, Energy Values, and Supervision of the
Primary System.
You will find the corresponding function groups and the folders with the usable protection functions in the
Global DIGSI library under each device type. In the Capacitor bank diff. function group, you can load only the
differential protection functions.

[scfgcadf-300414-01, 2, en_US]

Figure 5-25 Function Group Capacitor Bank Diff. - Functional Scope

244 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

For more information about the embedding of the functions in the device, refer to chapter 2 Basic Structure of
the Function. For application templates of the various device types, refer to chapter 4 Applications.

5.5.2.2 Structure of the Function Group


The Capacitor bank diff. function group, according to 5.5.2.1 Overview , has interfaces with the Capacitor
bank, the Capacitor bank side, and the Circuit-breaker function groups. The Capacitor bank diff. function
group contains the function blocks:

• Protection function (execution of the differential protection function)

• Trip logic (generation of forwarding of the operate indication)


In the Capacitor bank diff. function group, the differential protection function must always be available so
that the protection functionality can be ensured. If you do not use an application template, load the differen-
tial protection function from the Global DIGSI library.

[dwfgcadf-030314-01, 3, en_US]

Figure 5-26 Structure of the Capacitor Bank Diff. Function Group

The Capacitor bank diff. function group has interfaces to the following components:

• Function group Capacitor bank

• Function group Capacitor bank side

• Circuit-breaker function group

Interfaces with the Circuit-Breaker Function Group


The interface with the Circuit-breaker function group is used to exchange all required data between the
protection function group and the Circuit-breaker function group. The following data is required:

• Pickup and operate indications of the protection functions in the direction of the Circuit-breaker function
group

• Information on the circuit-breaker condition in the direction of the Protection function groups
You can connect the Capacitor bank diff. function group to one or more Circuit-breaker function groups.
This connection determines the following:

• Which circuit breakers are activated by the protection functions of the Capacitor bank diff. function
group

• Start of the Circuit-breaker failure protection function, if available in the Circuit-breaker function
group, through the protection functions of the connected Capacitor bank diff. function group
Besides the general assignment of the Capacitor bank diff. function group to the Circuit-breaker function
group, you can also configure the interface for specific functionalities in detail. Configure the details in DIGSI 5
via the Circuit-breaker interaction Editor in the Capacitor bank side diff. function group.

SIPROTEC 5, 7SJ82/7SJ85, Manual 245


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

For the detail configuration of the interface, define the following:

• Which operate indications of the protection functions are included when the trip command is generated

• Which protection functions activate the Circuit-breaker failure protection function


If an application template is used, the function groups are connected to each other because this link is abso-
lutely essential to ensure proper operation. You can modify the connection in DIGSI 5 via the Function-group
connections Editor. If the connection is missing, DIGSI 5 reports an inconsistency.
You can find more detailed information in chapter 2.1 Function Embedding in the Device.

Resetting the LED Group


Using the Reset the LED group function, you can reset the stored LEDs of the functions in one specific func-
tion group while the activated, stored LEDs of other functions in other function groups remain activated.

Interface with Protection Communication (optional)


All required data is exchanged between the protection function group and the protection communication via
the interface with Protection communication. These are for example:

• Binary signals

• Measured values

• Complex data
You can find more detailed information in chapter 3.6 Protection Communication.

Capacitor-Bank Data (General)


The capacitor-bank data characterizes the data of the capacitor bank to be protected. The data relevant for the
differential protection is shown. The Capacitor bank diff. function group takes the data from the coupled
function groups Capacitor bank and Capacitor bank side.

Output Logic
The output logic treats the pickup and trip signals of the protection and supervision functions in the function
group separately. Pickup logic and output logic are each assigned to the signals. The pickup and output logic
generate the overarching indications (group indications) of the function group. These group indications are
transferred via the Protection-information interface to the Circuit-breaker function group and are processed
further there.
The pickup and operate indications of the protection and supervision functions in the Capacitor bank diff.
function group are combined into one group indication using the following numbers and outputs.

[lo_anrlin, 3, en_US]

Figure 5-27 Generation of Pickup Indication of the Capacitor Bank Diff. Function Group

246 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

[lo_geopi1-231013-01, 2, en_US]

Figure 5-28 Generation of Operate Indication of the Capacitor Bank Diff. Function Group

5.5.2.3 Information List

No. Information Data Class Type


(Type)
General
_:91:52 General:Behavior ENS O
_:91:53 General:Health ENS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Reset LED Group
_:7381:500 Reset LED Group:>LED reset SPS I
_:7381:320 Reset LED Group:LED have been reset SPS O

5.5.3 Function-Group Type Capacitor-Bank Side

5.5.3.1 Overview
In the Capacitor bank side function group, all of the functions that are necessary for protecting and super-
vising a capacitor bank side can be used. The Capacitor bank side function group also contains the measuring
functions.
You can find more information in chapter 10 Measured Values, Energy Values, and Supervision of the Primary
System.
The Capacitor bank side function group must always have interfacing to the Capacitor bank diff. function
group.
You will find the corresponding function groups and the folders with the usable protection functions in the
Global DIGSI library under each device type. Depending on the connected measuring points, you can load the
respective protection and supervision functions in the Capacitor bank side function group. The functions are
described in chapter 6 Protection and Automation Functions.

SIPROTEC 5, 7SJ82/7SJ85, Manual 247


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

[scfgcasd-300414-01, 2, en_US]

Figure 5-29 Capacitor Bank Side Function Group - Functional Scope

For more information about the embedding of the functions in the device, refer to chapter 2 Basic Structure of
the Function. For application templates for the various device types, refer to chapter 4 Applications.

5.5.3.2 Structure of the Function Group


The Capacitor bank side function group always contains the following function blocks:

• Side-dependent capacitor-bank data

• Operational measured values

• Process monitor

• Output logic of the function group


These blocks are required for the Capacitor bank side function group and therefore cannot be loaded or
deleted.
You can load the protection and supervision functions required for your application in the Capacitor bank
side function group. The functions are available in the Global DIGSI 5 library. Functions that are not needed
can be deleted from the function group.

248 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

[dw_fgcabsi-201114-01, 2, en_US]

Figure 5-30 Structure of the Capacitor Bank Side Function Group

The Capacitor bank side function group has interfaces to the following components:

• Measuring points

• Capacitor bank diff. function group

• Circuit-breaker function group

Interfaces with Measuring Points


The Capacitor bank side function group receives the required measured values via its interfaces with the
measuring points. If you are using an application template, the Capacitor bank side function group is
connected to the necessary measuring points.
If you add functions to the Capacitor bank side function group, they will automatically receive the measured
values from the correct measuring points. If you add protection functions to the function group but the neces-
sary measuring point is not connected, DIGSI 5 reports an inconsistency. Configure the measuring points in
DIGSI 5 via the Function group connections Editor.
You can find more detailed information in chapter 2 Basic Structure of the Function.
The Capacitor bank side function group has the following interfaces with the measuring points:

• 3-phase current
The measurands from the 3-phase power system are supplied via this interface. Depending on the trans-
former connection type, these are for example: I A, I B, I C, I N or 3 I 0. All values that can be calculated
from the measurands are also provided via this interface. The Capacitor bank side function group must
always be linked to the I-3ph measuring point.
You can connect the 3-phase current interface with a maximum of two 3-phase current measuring
points. If 2 current measuring points have been connected to the 3-phase current interface, the total
current is also determined from measured values from both measuring points in the Capacitor bank side
function group. All functions in the Capacitor bank side function group have access to these values.

• 3-phase voltage (optional):


The measurands from the 3-phase voltage system are supplied via this interface. Different transformer
connection types are possible. All values that can be calculated from the measurands are also provided
via this interface.
The connection of the 3-phase voltage is optional. This connection is necessary only if protection or
supervision functions that require voltage measurements are used.

SIPROTEC 5, 7SJ82/7SJ85, Manual 249


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

Interfaces to the Circuit-Breaker Function Group


The interface with the Circuit-breaker function group is used to exchange all required data between the
protection function group and the Circuit-breaker function group. The following data is required:

• Pickup and operate indications of the protection functions in the direction of the Circuit-breaker function
group

• Information on the circuit-breaker condition in the direction of the Protection function groups
You can connect the Capacitor bank side function group to one or more Circuit-breaker function groups.
This connection determines the following:

• Which circuit breakers are activated by the protection functions of the Capacitor bank side function
group

• Start of the Circuit-breaker failure protection function, if available in the Circuit-breaker function
group, through the protection functions of the connected Capacitor bank side function group
Besides the general assignment of the Capacitor bank side function group to the Circuit-breaker function
group, you can also configure the interface for certain functionalities in detail. Configure the details in DIGSI 5
using the Circuit-breaker interaction Editor in the Capacitor bank side function group.
For the detail configuration of the interface, define the following:

• Which operate indications of the protection functions are included when the trip command is generated

• Which protection functions activate the Circuit-breaker failure protection function


If an application template is used, the function groups are connected to each other because this link is abso-
lutely essential to ensure proper operation. You can modify the connection in DIGSI 5 via the Function-group
connections Editor. If the connection is missing, DIGSI 5 reports an inconsistency.
You can find more detailed information in chapter 2.1 Function Embedding in the Device.

Interface with Protection Communication (optional)


All required data is exchanged between the protection function group and the protection communication via
the interface with Protection communication, for example:

• Binary signals

• Measured values

• Complex data
You can find more detailed information in chapter 3.6 Protection Communication.

Resetting the LED Group


Using the Reset the LED group function, you can reset the stored LEDs of the functions in one specific func-
tion group while the activated, stored LEDs of other functions in other function groups remain activated.

Process Monitor
The process monitor is always present in the Capacitor bank side function group and cannot be removed. The
process monitor provides the following information in the Capacitor bank side function group:

• Current-flow criterion:
Detection of an open/activated capacitor bank side based on the flow of leakage current

• Closure detection:
Detection of closure of the capacitor bank side

• Cold-load pickup detection (optional):


This information is in the Capacitor bank side function group and is available to all the functions in the func-
tion group.

250 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

Operational Measured Values


The operational measured values are always present in the Capacitor bank side function group and cannot be
deleted. If a 3-phase voltage measuring point is connected, the following table shows the total scope. If only
current is connected, only the first 3 lines apply.

Table 5-9 Possible Operational Measured Values of the Capacitor Bank Side Function Group

Measured Values Primary Secon- % Referenced to


dary
IA, IB, IC Phase currents A A Rated operating current of the primary system
3I0 Calculated residual current A A Rated operating current of the primary system
IN Measured residual current A A Rated operating current of the primary system
VA, VB, VC Phase-to-ground voltages kV V Rated operating current of the primary
system/√3
VAB, VBC, VCA Phase-to-phase voltages kV V Rated operating voltage of the primary
system
V0 Calculated zero-sequence voltage kV V Rated operating current of the primary
system/√3
Vr Measured neutral-point displace- kV V Rated operating current of the primary
ment voltage system/√3
f Frequency Hz Hz Rated frequency
P Active power MW – Rated operating voltage and rated operating
(total power) current of the primary system
√3 · Vrated · Irated
Q Reactive power MVAr – Rated operating voltage and rated operating
(total power) current of the primary system
√3 · Vrated · Irated
S Apparent power MVA – Rated operating voltage and rated operating
(total power) current of the primary system
√3 · Vrated · Irated
Cos φ Active factor (abs) (abs) 100 % corresponds to c
os φ = 1
PA, PB, PC Phase-related active power MW – Active power of the phase
Vrated phsx · Irated phsx
QA, QB, QC Phase-related reactive power MVAr – Reactive power of the phase
Vrated phsx · Irated phsx
SA, SB, SC Phase-related apparent power MVA – Apparent power of the phase
Vrated phsx · Irated phsx

If a V-3ph measuring point was connected to the Capacitor bank side function group, voltage and phase
measurements are available.
The energy measurements are not predefined. If necessary, you must load them from the Global DIGSI 5
library.
Depending on the protection and supervision functions used, additional function measurements may be avail-
able. The function values are listed in the information list of the appropriate protection or supervision func-
tion (see chapter 6 Protection and Automation Functions).

SIPROTEC 5, 7SJ82/7SJ85, Manual 251


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

NOTE

i With the P, Q sign parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see chapter 10.2 Structure of the Function Structure of
the Function, section Inversion of Power-Related Measured and Statistical Values):

• Active power (total): P total

• Active power (phase-related): PA, PB, PC

• Reactive power (total): Q total

• Reactive power (phase-related): QA, QB, QC

Capacitor-Bank Data (Side-Dependent)


The capacitor-bank data characterizes the data of the capacitor bank to be protected. The side-dependent
capacitor-bank data applies to all of the functions in the Capacitor bank side function group.

Output Logic
The output logic treats the pickup and trip signals of the protection and supervision functions in the function
group separately. Pickup logic and output logic are each assigned to the signals. The pickup and output logic
generate the overarching indications (group indications) of the function group. These group indications are
transferred via the Protection information interface to the Circuit-breaker function group and are processed
further there.
The pickup and operate indications of the protection and supervision functions in the Capacitor bank side
function group are combined into one group indication using the following numbers and outputs.

[lo_anrlin, 3, en_US]

Figure 5-31 Generation of Pickup Indication of the Capacitor Bank Side Function Group

[lo_geopi1-231013-01, 2, en_US]

Figure 5-32 Generation of Operate Indication of the Capacitor Bank Side Function Group

252 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

5.5.3.3 Application and Setting Notes

Interface to the Circuit-Breaker Function Group


The Capacitor bank side function group is usually connected to 1 Circuit-breaker function group. The
Circuit-breaker function group is assigned to the circuit breaker of the capacitor bank.

Parameter: Rated apparent power

• Default setting (_:1781:15571:103) Rated apparent power = 692.82 MVA.


The Rated apparent power parameter shows the primary rated apparent power of the capacitor
bank to be protected. The setting value is determined of the Capacitor reference volt. and the
Capacitor reference curr. parameters.

Parameter: Capacitor reference volt.

• Default setting (_:1781:15571:102) Capacitor reference volt. = 400.00 kV


You can use the Capacitor reference volt. parameter to set the reference voltage of the capacitor
bank to be protected. The reference voltage set here is the reference value for the percentage measured
values and setting values made in percent.
Depending on user philosophy you can use the system rated voltage (busbar voltage) or the capacitor rated
voltage as a reference value.

Parameter: Capacitor reference curr.

• Default setting (_:1781:15571:101) Capacitor reference curr. = 1000 A


You can use the Capacitor reference curr. parameter to set the reference current for the capacitor
bank to be protected. The capacitor reference current set here is the reference value for the percentage meas-
ured values and setting values in percent.
For Differential protection, these values are used for absolute-value correction (rated current of the protected
object).
If the capacitor bank is part of a delta connection, the value to be set here can differ from the capacitor refer-
ence current set in the Capacitor bank function group (by factor √3). Otherwise, set always the same values.
Depending on user philosophy, you can use the capacitor-bank rated current including the harmonics or the
capacitor-bank fundamental-component current as a reference value.

Parameter: Neutral point

• Default setting (_:1781:15571:149) Neutral point = isolated


With the Neutral point parameter, you specify whether the neutral point in the protection range of the
differential protection is grounded or isolated. If there is no neutral point in the protection zone, use the
parameter isolated. The neutral point of a capacitor bank is usually not in the protection zone. Therefore,
even if the neutral point is grounded, set isolated here.
You can find further information in the Device manual 7UT8 Chapter 6.2.3 function description neutral point-
current handling.

Parameter: Winding configuration

• Default setting (_:1781:15571:104) Winding configuration = Y (Wye)


You can use the Winding configuration parameter to set D (Delta) for a delta connection. Another
setting option is Y (Wye) for a star connection. The Winding configuration parameter is relevant for
the Differential protection function.

Parameter: Vector group numeral

• Default setting (_:1781:15571:100) Vector group numeral = 0


This parameter is used to account for phase-angle rotation, which is expressed by a numeral.

SIPROTEC 5, 7SJ82/7SJ85, Manual 253


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

Phase-angle rota- 0° 30° 60° 90° 120° 150° 180° 210° 240° 270° 300° 330°
tion
Vector group 0 1 2 3 4 5 6 7 8 9 10 11
numeral

In the function group, the following information is displayed additionally in the setting sheet:

• Side number

• Identification of the measuring points used

• Adaptation factor for the 3-phase measuring point (with reference to the side)
Each Vector group numeral can be set from 0 to 11 to the extent possible. Thus, for example, only even
numbers are possible for the vector group Yy and Dd and only odd numbers are possible for Yd and Dy.

Parameter: Side number

• Default setting (_:1781:14611:130) Side number = not assigned


The Side number parameter shows you which capacitor bank side is currently valid for the following param-
eters. The side number (Side 1 to Side 3) is automatically assigned with the connection to a capacitor bank
side.

Parameter: MI3ph1 usesMeasP with ID

• Default setting (_:1781:14611:210) MI3ph1 usesMeasP with ID = 0


The MI3ph1 usesMeasP with ID parameter shows you which 3-phase measuring point is connected to
the capacitor bank side. Every measuring point is assigned a unique ID.

Parameter: MI3ph2 usesMeasP with ID

• Default setting (_:1781:14611:211) MI3ph2 usesMeasP with ID = 0


The MI3ph2 usesMeasP with ID parameter shows you which 3-phase measuring point is connected to
the capacitor bank side. Every measuring point is assigned a unique ID.

Parameter: CT mismatch M I-3ph 1

• Default setting (_:1781:14611:215) CT mismatch M I-3ph 1 = 0.000


The CT mismatch M I-3ph 1 parameter shows you the magnitude adaptation of the phase currents of the
1st assigned measuring point. The numerical value results from the ratio of the primary rated current of the
current transformer to the rated current of the side.

Parameter: CT mismatch M I-3ph 2

• Default setting (_:1781:14611:217) CT mismatch M I-3ph 2 = 0.000


The CT mismatch M I-3ph 2 parameter shows you the magnitude adaptation of the phase currents of the
2nd assigned measuring point.

5.5.3.4 Write-Protected Settings


The settings listed here are used primarily for understanding during configuration of the function groups. They
are calculated on the basis of other settings and cannot be directly changed.
Addr. Parameter C Range of Values Default Setting
Rated values
_:1781:15571:103 Rated apparent power 0.20 MVA to 5000.00 MVA 692.82 MVA

254 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection

Addr. Parameter C Range of Values Default Setting


Side data
_:1781:14611:130 Side number • not assigned Side 2
• Side 1
• Side 2
• Side 3
_:1781:14611:210 MI3ph1 usesMeasP with ID 0 to 100 8
_:1781:14611:215 CT mismatch M I-3ph 1 0.010 to 100.000 1.000

5.5.3.5 Settings

Addr. Parameter C Setting Options Default Setting


Rated values
_:1781:15571:101 General:Capacitor reference 1 A to 100 000 A 1000A
curr.
_:1781:15571:102 General:Capacitor reference 0.20 kV to1200.00 kV 400.00 kV
volt.
Side data
_:1781:15571:149 General:Neutral point • grounded isolated
• isolated
_:1781:15571:104 General:Winding configuration • Y (Wye) Y (Wye)
• D (Delta)
_:1781:15571:100 General:Vector group numeral 0 to 11 0
Measurements
_:1781:14611:158 Further settings:P, Q sign • not reversed not reversed
• reversed

5.5.3.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Reset LED Group
_:7381:500 Reset LED Group:>LED reset SPS I
_:7381:320 Reset LED Group:LED have been reset SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 255


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

5.6 Function-Group Type Analog Units

5.6.1 Overview

The Analog units function group is used to map analog units and communicate with them. Analog units are
external devices, such as RTD units, analog plug-in modules, or measuring-transducer modules.
You will find the Analog units function group for many device types in the Global DIGSI 5 library.

[sc20maee-250816-01, 2, en_US]

Figure 5-33 Analog Unit Function Group in DIGSI

5.6.2 Structure of the Function Group

If the device has a measuring transducer, it is automatically mapped in the Analog units function group. If
one or more RTD units are connected to the device, you have to load one or more RTD unit Ether. or RTD unit
serial functions from the Global DIGSI 5 library in order to map the RTD units.
If the device is connected to a power-plant control system or another protection device, you must load one or
more Temperature acquisition via protocols functions from the Global DIGSI 5 library to form the protocols.
The following figure shows the structure of the function group.

256 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dwstrthe, 3, en_US]

Figure 5-34 Structure of the Analog Unit Function Group

Gray: Optionally wired, optionally available


White: Always wired, always available

The Analog units function group has interfaces to protection function groups. The Analog units function
group provides for example measured temperature values that come from an external RTD unit , a measuring
transducer or via protocols. These measured temperature values are available for all protection function
groups in which a temperature monitoring function works.
The RTD unit Ether. function is not preconfigured by the manufacturer. A maximum of 20 function instances
can operate simultaneously.
The structure of the function RTD unit serial is identical to the structure of the function RTD unit Ether..
The function 20-mA unit Ether. is not preconfigured by the manufacturer. A maximum of 4 function instances
can operate simultaneously. The structure of the function 20-mA unit serial is identical to the structure of the
function 20-mA unit Ether..

SIPROTEC 5, 7SJ82/7SJ85, Manual 257


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

The function Temperature acquisition via protocols has 2 stage types: The Temperature acquisition via
PROFINET IO or IEC 61850 and the Temperature acquisition via GOOSE. One instance of the Temperature
acquisition via PROFINET IO or IEC 61850 is preconfigured by the manufacturer. A maximum of 12 instances
can operate simultaneously for both stage types.

5.6.3 20-mA Unit Ethernet

5.6.3.1 Overview
The function 20-mA unit Ether.:

• Communicates in series with a 20-mA unit via the Slave Unit Protocol (SUP) and records the values meas-
ured by the 20-mA unit

• Transforms the measured 20-mA values into slowly changing process tags such as temperature or gas
pressure

• Makes the recorded process tags available to CFC, GOOSE, protocols and the device display

• Monitors communication with the 20-mA unit

5.6.3.2 Structure of the Function


The function 20-mA unit Ether. can work only in the function group Analog units. A maximum of 4 function
instances can work simultaneously. Each instance contains 12 preconfigured channel function blocks.
The function 20-mA unit Ether. contains input and output channels which can be configured independently
of one another.

[dwstrfn2-150113-01.tif, 2, en_US]

Figure 5-35 Structure/Embedding of the Function

258 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

5.6.3.3 Communication with 20-mA Unit Ethernet

Logic

[lo20mtcp-150113-01.tif, 1, en_US]

Figure 5-36 Logic of the Function 20-mA Unit Ethernet

Communication with 20-mA Unit


The function is used to communicate with a 20-mA unit connected via an Ethernet connection. When a
connection of the function to an external 20-mA unit via an Ethernet interface has successfully been estab-
lished, the 20-mA unit sends the measured values of all connected channels to the function 20-mA unit.
Ether.. For the connection to be established successfully, specific communication settings must be specified.
You can find more detailed information in Chapter 5.6.3.4 Application and Setting Notes.
The 20-mA measurement unit 7XV5674 is supported.

Error Responses
The following table lists the conditions under which the Health status transitions to the Alarm or Warning
state.

Table 5-10 Error Responses

Error Description Status Health


The function 20-mA unit Ether. cannot establish a Alarm
connection with a communication module.
The function 20-mA unit Ether. sends TCP settings to Alarm
the communication module, which evidently would
like to connect to the 20-mA unit via a serial protocol.
This communication module does not establish a
connection to the 20-mA unit.
The connection between the communication module Warning
and the 20-mA unit causes a time-out indication.

SIPROTEC 5, 7SJ82/7SJ85, Manual 259


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Error Description Status Health


A communication module has not received any more Warning
data from the 20-mA unit for 9 sec.

The Failure signal is set as soon as one of the channel function blocks reports a failure.

5.6.3.4 Application and Setting Notes

Parameter: Port

• Default setting (_:2311:103) Port = port J


Use the Port setting to define the port connecting the 20-mA unit to the SIPROTEC 5 device.

Parameter: IP address

• Default setting (_:2311:104) IP address = 10.16.60.1


With the IP address settings, you set the IP address of the 20-mA unit connected to the communication
module via the TCP protocol. You must assign each 20-mA unit an unambiguous IP address. The IP address to
be set depends on your network configuration. You can set any valid IPv4 address that does not cause conflicts
with other IP addresses in the network. First set an IP address for the 7XV5674 20-mA unit. Then specify the
IP address settings for the communication module to the same address.

Settings on the 20-mA Unit


The 7XV5674 20-mA unit is set with a web browser on the laptop computer via the latter's Ethernet interface.
Set Modbus TCP as bus protocol/operating mode.
You can find detailed notes on the settings in the 7XV5674 manual that accompanies the 20-mA unit. The
documents are also available in the SIPROTEC download area (http://www.energy.siemens.com).

5.6.3.5 20-mA Channel

Logic

[lo20mcha-160113-01.tif, 1, en_US]

Figure 5-37 Logic Diagram of the Function 20-mA Channel

260 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

(1) If the setting Range active is set to test , the setting Transformation ratio is not
displayed.
(2) If the setting Range active is set to false, the settings Upper limit, Transformation
ratio upper limit, Lower limit and Transformation ratio are not displayed.

Measured-Value Calculation
The function 20-mA channel processes a single 20-mA current signal supplied by the 20-mA unit of the corre-
sponding channel. The 20-mA current measured value is converted into the correct physical quantities such as
temperature or pressure. In each 20-mA functional unit (Ether. and serial) there are always 12 of the 20-mA
channel function blocks, even if fewer channels are connected with the 20-mA unit. The calculated values are
available for further processing via CFC, GOOSE, protocols, and the display image.

Measured-Value Processing
The 20-mA unit typically transmits a value which represents a physical quantity, such as a temperature or a
pressure. Therefore, the device must contain a characteristic curve that maps the physical quantity to the 20-
mA value. If you do not activate the Range active setting (no x in the check box), the function operates
over the range 0 mA to 20 mA. If a value smaller than 0 mA or greater than 20 mA is active at the input of the
20-mA unit, the measured value is identified as invalid. The setting of the range for the scaled value goes from
a usable range of 0 mA to 20 mA. The following figure shows an example.

[sckanumw-190214-01, 1, en_US]

Figure 5-38 Settings for Example 1

In this example, the measured value 0 mA means a temperature of 0 °C and the measured value 20 mA means
a temperature of 100 °C. So enter as Unit = °C and Conversion factor = 100. The resolution (decimal
place) of the temperature value can be chosen; for a decimal place, select Resolution = 0.1.

[dwknges3-020513-01.tif, 1, en_US]

Figure 5-39 Characteristic Curve of a 20-mA Input (Example 1)

SIPROTEC 5, 7SJ82/7SJ85, Manual 261


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

If you activate the Range active setting, then 4 additional parameters Upper limit, Lower limit,
Upper limit - Sensor, and Lower limit - Sensor appear. The parameters Upper limit and
Lower limit indicate the range of the input current in mA. The setting Upper limit - Sensor is the
calculated measured value if the input current corresponds to the value in the Upper limit setting. The
setting Lower limit - Sensor is the calculated measured value if the input current corresponds to the
value in the Lower limit setting. The setting of the range for the scaled value corresponds to the useable
range between Lower limit and Upper limit (see following figure).

[sckanumf-190214-01, 1, en_US]

Figure 5-40 Settings for Example 2

[dwknges2-020513-01.tif, 1, en_US]

Figure 5-41 Characteristic Curve of a 20-mA Unit (Example 2)

In this example, the Range active setting is selected. The setting Upper limit is at 20 mA, the setting
Lower limit is at 4 mA. The setting Upper limit - Sensor is at 55 and the setting Lower limit -
Sensor is at -33. If the input current is smaller than 4 mA or greater than 20 mA, the quality of the scaled
measured value in this example is invalid.
Each 20-mA channel makes available the scaled measured value in the information routing (these are the
temperature values in the examples) and the original current measured value in mA for further processing.
The 20-mA values can be displayed in the display page and processed with CFC charts.

Error Responses
If the current input value is determined to be incorrect, the quality attribute of the output value is set to
invalid That status for Health and the defect status assume the states displayed in the table.

262 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Table 5-11 Error Responses

Error Description Status Health Error Status


The input value lies outside the OK Yes
given limits
Channel not connected OK No

5.6.3.6 Application and Setting Notes

Parameter: Unit

• Default setting (_:13111:103) Unit = °C


With the Unit parameter, you set the physical unit of measurement the measured values. The possible setting
values are listed in the settings table.

Parameter: Conversion factor

• Default setting (_:13111:104) Conversion factor = 100


With the Conversion factor parameter, you set the conversion factor for the measuring transducer.

Parameter: Resolution

• Default setting (_:13111:108) Resolution = 0.1


With the Resolution parameter, you set the resolution of the scaled values.

Parameter: Range active

• Default setting (_:13111:107) Range active = false


If you do not activate the parameter Range active (no x in the check box), the function operates over the
range 0 mA to 20 mA. The setting of the range for the scaled value goes from a usable range of 0 mA to
20 mA.
If you activate the parameter Range active, the 4 additional parameters Upper limit, Upper limit -
Sensor, Lower limit, and Lower limit - Sensor appear.

Parameter: Upper limitLower limitUpper limit - Sensor and Lower limit - Sensor

• Default setting (_:13111:105) Upper limit = 20.000 mA

• Default setting (_:13111:109) Upper limit - Sensor = 100

• Default setting (_:13111:106) Lower limit = 4.000 mA

• Default setting (_:13111:110) Lower limit - Sensor = 100


If you activate the parameter Range active , the 4 additional parameters Upper limit, Lower limit,
Upper limit - Sensor, and Lower limit - Sensor appear. The parameter Upper limit -
Sensor is the calculated measured value if the input current corresponds to the value in the Upper limit
setting. The parameter Lower limit - Sensor is the calculated measured value if the input current corre-
sponds to the value in the Lower limit setting.
The following settings and information table shows only 1 of the 12 channels, as the setting possibilities of
the 12 channels do not differ.

SIPROTEC 5, 7SJ82/7SJ85, Manual 263


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

5.6.3.7 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:103 General:Port • port E port J
• port F
• port J
• port N
• port P

264 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Addr. Parameter C Setting Options Default Setting


Channel 1
_:13111:103 Channel 1:Unit • % m
• °
• °C
• °F
• Ω
• Ω/km
• Ω/mi
• 1/s
• A
• As
• cos φ
• cycles
• dB
• F/km
• F/mi
• h
• Hz
• Hz/s
• in
• J
• J/Wh
• K
• l/s
• m
• mi
• min
• p.u.
• Pa
• periods
• rad
• rad/s
• s
• V
• V/Hz
• VA
• VAh
• var
• varh
• Vs
• W

SIPROTEC 5, 7SJ82/7SJ85, Manual 265


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Addr. Parameter C Setting Options Default Setting


• W/s
• Wh
_:13111:108 Channel 1:Resolution • 1 0.1
• 0.1
• 0.01
• 0.001
_:13111:107 Channel 1:Range active • 0 false
• 1
_:13111:104 Channel 1:Conversion 1 to 1000000 100
factor
_:13111:105 Channel 1:Upper limit 0.00 mA to 20.00 mA 20.00 mA
_:13111:109 Channel 1:Upper limit - -1000000 to 1000000 100
Sensor
_:13111:106 Channel 1:Lower limit 0.00 mA to 20.00 mA 4.00 mA
_:13111:110 Channel 1:Lower limit - -1000000 to 1000000 100
Sensor

5.6.3.8 Information List

No. Information Data Class Type


(Type)
General
_:2311:53 General:Health ENS O
_:2311:56 General:Failure SPS O
Channel 1
_:13111:53 Channel 1:Health ENS O
_:13111:71 Channel 1:Failure SPS O
_:13111:301 Channel 1:20-mA output scale MV O
_:13111:302 Channel 1:20-mA output raw MV O

5.6.4 20-mA Unit Serial

5.6.4.1 Overview
The function 20-mA unit Serial:

• Provides serial communications with a 20-mA unit via the Modbus protocol and records the values meas-
ured by the 20-mA unit

• Transforms the measured 20-mA values into slowly changing process variables such as temperature or
gas pressure

• Makes the recorded process tags available to CFC, GOOSE, protocols and the device display

• Monitors communication with the 20-mA unit


The function 20-mA unit Serial is structured in the same way as the function 20-mA Unit Ether.. The mode of
operation is also identical. The only difference is that the measured values are transferred to the communica-
tion module via a serial connection instead of an Ethernet connection.
You can find more information in Chapter 5.6.3.2 Structure of the Function.

266 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

5.6.4.2 Application and Setting Notes

Parameter: Port

• Default setting (_:2311:103) Port = Port J


With the Port parameter, you specify the slot for the communication module that will be used for the
connection with an external 20-mA unit.

Parameter: Channel number

• Default setting (_:2311:105) Channel number = 1


A serial communication module optionally uses 2 channels. With the Channel number parameter, you
specify the channel number (1 or 2) used to connect the 20-mA unit to the device. The communication
module inputs are labeled with the channel numbers.

Parameter: Slave address

• Default setting (_:2311:106) Slave address = 1


With the Slave address parameter, you define the device address of the 20-mA unit. If only one 20-mA
unit is connected to the serial bus, the default value 1 can be used. Set the same device address as used with
the 20-mA unit. The device address is important for distinguishing several 20-mA units that are connected to a
serial bus. Set an unambiguous device address on every 20-mA unit, for example, 1, 2 and 3 when connecting
3 of the 20-mA units. On every 20-mA unit, set for the Slave address setting in the 3 functions 20-mA
Unit Serial.

Parameter: Unit

• Default setting (_:13111:103) Unit = °C


With the Unit parameter, you set the physical unit of measurement the measured values. The possible setting
values are listed in the settings table.

Parameter: Conversion factor

• Default setting (_:13111:104) Conversion factor = 100


With the Conversion factor parameter, you set the conversion factor for the measuring transducer.

Parameter: Resolution

• Default setting (_:13111:108) Resolution = 0.1


With the Resolution parameter, you set the resolution of the scaled values.

Parameter: Range active

• Default setting (_:13111:107) Range active = false


If you do not activate the Range active parameter (no x in the check box), the function operates over the
range 0 mA to 20 mA. The setting of the range for the scaled value goes from a usable range of 0 mA to
20 mA.
If you activate the Range active parameter, the 4 additional parameters Upper limit, Upper limit -
Sensor, Lower limit, and Lower limit - Sensor appear.

Parameter: Upper limitLower limitUpper limit - Sensor and Lower limit - Sensor

• Default setting (_:13111:105) Upper limit = 20 mA

• Default setting (_:13111:109) Upper limit - Sensor = 100

• Default setting (_:13111:106) Lower limit = 4 mA

• Default setting (_:13111:110) Lower limit - Sensor = 100

SIPROTEC 5, 7SJ82/7SJ85, Manual 267


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

If you activate the Range active parameter, the 4 additional parameters Upper limit, Lower limit,
Upper limit - Sensor, and Lower limit - Sensor appear. The parameter Upper limit -
Sensor is the calculated measured value if the input current corresponds to the value in the Upper limit
setting. The parameter Lower limit - Sensor is the calculated measured value if the input current corre-
sponds to the value in the Lower limit setting.
The following settings and information table shows only 1 of the 12 channels, as the setting possibilities of
the 12 channels do not differ.

5.6.4.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:103 General:Port • port E port J
• port F
• port J
• port N
• port P
_:2311:105 General:Channel number 1 to 2 1
_:2311:106 General:Slave address 1 to 247 1

268 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Addr. Parameter C Setting Options Default Setting


Channel 1
_:13111:103 Channel 1:Unit • % m
• °
• °C
• °F
• Ω
• Ω/km
• Ω/mi
• 1/s
• A
• As
• cos φ
• cycles
• dB
• F/km
• F/mi
• h
• Hz
• Hz/s
• in
• J
• J/Wh
• K
• l/s
• m
• mi
• min
• p.u.
• Pa
• periods
• rad
• rad/s
• s
• V
• V/Hz
• VA
• VAh
• var
• varh
• Vs
• W

SIPROTEC 5, 7SJ82/7SJ85, Manual 269


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Addr. Parameter C Setting Options Default Setting


• W/s
• Wh
_:13111:108 Channel 1:Resolution • 1 0.1
• 0.1
• 0.01
• 0.001
_:13111:107 Channel 1:Range active • 0 false
• 1
_:13111:104 Channel 1:Conversion 1 to 1000000 100
factor
_:13111:105 Channel 1:Upper limit 0.00 mA to 20.00 mA 20.00 mA
_:13111:109 Channel 1:Upper limit - -1000000 to 1000000 100
Sensor
_:13111:106 Channel 1:Lower limit 0.00 mA to 20.00 mA 4.00 mA
_:13111:110 Channel 1:Lower limit - -1000000 to 1000000 100
Sensor

5.6.4.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:53 General:Health ENS O
_:2311:56 General:Failure SPS O
Channel 1
_:13111:53 Channel 1:Health ENS O
_:13111:71 Channel 1:Failure SPS O
_:13111:301 Channel 1:20-mA output scale MV O
_:13111:302 Channel 1:20-mA output raw MV O

5.6.5 Communication with 20-mA Unit

5.6.5.1 Integration of a Serial 20-mA Unit

Connection of the Communication Lines


Figure 5-42 shows how to connect the 20-mA unit to the SIPROTEC 5 device. Note that Pin 1 of the RJ45 plug
is connected to RTD-B and Pin 2 is connected to RTD-A.

270 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dwve20au-150213-01.tif, 1, en_US]

Figure 5-42 Connection of the 20-mA Unit to the SIPROTEC 5 Device

Adding a USART Module


Add a USART-AB-1EL or a USART-AC-2EL USART module in DIGSI to the device. The USART module must be
inserted at one of the plug-in positions for communication modules in the base module or in the CB202
expansion module (refer to the following figure).

[sc20ser3-220114-01-DE, 1, en_US]

Figure 5-43 Insertion Position for a USART Module

Selecting the SUP Protocol


Select the Slave Unit Protocol (SUP). This protocol is responsible for the communication between the
SIPROTEC 5 device and the 20-mA unit.

SIPROTEC 5, 7SJ82/7SJ85, Manual 271


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[scauser4-301012-01.tif, 1, en_US]

Figure 5-44 Selecting the SUP Protocol

Communication Settings
Make the communications settings for the relevant serial channels. For this, use the default settings specified
by the 20-mA unit. Normally, you must adapt only the parameterization of the SIPROTEC 5 device to the
settings of the 20-mA unit. Make sure that the setting values in both devices are the same. The setting of the
parameter Non-flickering light (on/off): is not relevant for the RS485 interface.

NOTE

i The driver for the USART module for the SUP protocol is not preinstalled as standard for the initial use of
this interface (following the firmware update).

[scauser5-301012-01.tif, 1, en_US]

Figure 5-45 Making the Communication Settings

With the selection of the SUP protocol for the 20-mA unit DIGSI automatically adds the function group Analog
units to your device configuration. You can now instantiate the function 20-mA unit serial 1 (see the
following figure).

272 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc20ser6-220114-01-DE, 1, en_US]

Figure 5-46 Insertion of the Function 20-mA Unit Serial 1

Now, set the channel number over which the SUP protocol runs. In addition, set the slave address of the
20‑mA unit. This address must be set with the same value in the 20-mA unit (refer to the following figure).
For the first use of the 20-mA unit, the following device configuration must be set on the 20-mA unit:

• Bus protocol: mod

• Device address: 1

• Baud rate: 9600

• Parity: no

[scauser7-220114-01-DE, 1, en_US]

Figure 5-47 Setting the Port, Channel Number, and Device Address

Finally, load the configuration in the device.

5.6.5.2 Integration of a 20-mA Unit Ethernet

Device Configuration
In DIGSI, insert an Ethernet module into the provided slot, thus adding the module to the device configura-
tion. Figure 5-48 displays the available slots in the base module or on the expansion module CB 202. Alterna-
tively, you can also use the integrated Ethernet interface Port J.

SIPROTEC 5, 7SJ82/7SJ85, Manual 273


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[scautcp1-220114-01-DE, 1, en_US]

Figure 5-48 Inserting an Ethernet Module

Communication Settings
Activate the SUP Ethernet protocol for the Ethernet module.

[scautcp2-011112-01.tif, 1, en_US]

Figure 5-49 Activation of the Protocol

This protocol is also available for Port J of the integrated Ethernet interface of the base module (refer to
following figure).

[scautcp3-011112-01.tif, 1, en_US]

Figure 5-50 Selection of the Protocol

With the selection of the SUP protocol for the 20-mA unit, DIGSI automatically adds the Analog units function
group and the 20-mA unit Ether. 1 function to your device configuration (refer to the following figure).

274 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc20tcp4-220114-01-DE, 1, en_US]

Figure 5-51 Insertion of the Function 20-mA Unit Ether. 1

Now, set the port over which the SUP protocol runs. In addition, set the IP address of the 20-mA unit (refer to
the following figure). This address must be set with the same value in the 20-mA unit.

[scautcp5-301012-01.tif, 1, en_US]

Figure 5-52 Setting the Port and IP Address

Finally, load the configuration in the device.

5.6.6 V/I-Measuring-Transducer Unit with Fast Inputs

5.6.6.1 Overview
The fast analog measuring-transducer inputs process voltage values (DC -10 V to +10 V) as well as current
values (DC -20 mA to 20 mA).
The function MT fast input:

• Provides sampled values for recording in the fault record (the maximum sampling frequency is 8 kHz for
all other SIPROTEC 5 devices). The recorded sampling frequency results from the setting of the fault-
recorder function.

• Calculated measured values from the sampled values. These measured values have been deduced from
the arithmetic mean values. The measuring range for the mean-value calculation is adjustable in the
interval from 10 ms to 100 ms.

SIPROTEC 5, 7SJ82/7SJ85, Manual 275


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

• Converts the measured current or voltage values into process values, for example, temperature, gas pres-
sure, etc.

• Provides the recorded process variables for further processing by the fault recorder, the CFC, and in
GOOSE-applications for transmission via communication protocols, and for visualization
The fast measuring-transducer inputs are located on the IO212 module with 8 inputs (optionally current or
voltage inputs), and the IO210 module with 4 inputs (optionally current or voltage inputs).

5.6.6.2 Structure of the Function


The function MT fast input works in the function group Analog units and contains the number of available
measuring-transducer inputs, depending on the hardware configuration. You can configure these channels
independently from one another either as current or voltage inputs.

[dw_mu-structure, 1, en_US]

Figure 5-53 Structure/Embedding of the Function

5.6.6.3 Function Description


Once you have instantiated the MT fast input function, it will be visible in the project tree in the function
group Analog units. You can find the function group Analog units in DIGSI in the Settings folder.
If you open the subdirectory MT fast input, you reach the setting sheet for the respective input (for more
details, see Application and Setting Notes).
The hardware is designed in such a way that either a current or a voltage can be processed at each input. Use
the corresponding terminals (see Hardware manual). Configure the input in accordance with the selected
connection (Parameter TD input-signal type). With the parameter Measuring window, you set the
measuring range with which the arithmetic mean value is determined. With the parameter Measuring
window, you also determine measurement speed for the input. For example, a setting of 100 ms means that
the measured value is updated every 100 ms.

276 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[scmuio212, 1, en_US]

Figure 5-54 Parameters of the Measuring-Transducer Channels.

The fast measuring-transducer channels can be configured either as current or as voltage inputs. Apart from
this, their function corresponds to the basic function of the 20-mA-channels (see chapter 5.6.3.5 20-mA
Channel).

5.6.6.4 Application and Setting Notes

Parameter: TD input-signal type

• Default setting (_:101) TD input-signal type = Current input


With the TD input-signal type parameter, you determine whether the measuring-transducer input
channel works as a Current input or as a Voltage input.
Make sure that the selected channel has also been wired correctly (see Hardware manual, Input and Output
Module IO212).

Parameter: Unit

• Default setting (_:103) Unit = A


With the Unit parameter, you set the physical unit of measurement the measured values. The possible setting
values are listed in the settings table.

Parameter: Measuring window

• Default setting (_:142) Measuring window = 10 ms


With the Measuring window parameter, you set the measuring window that is used to determine the arith-
metic mean value from the sampled values. In case of slowly varying signals, Siemens recommends setting the
top value to 100 ms. With this value, a new, current measured value is provided every 100 ms for further
processing.

SIPROTEC 5, 7SJ82/7SJ85, Manual 277


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Parameter: Range active

• Default setting (_:107) Range active = false


If you do not activate the Range active parameter, the function then assumes a range of -20 mA to +20 mA
or -10 V to +10 V. The setting of the range for the scaled value then assumes a usable range of -20 mA to
+20 mA or -10 V to +10 V.
If you activate the Range active parameter, the 4 additional parameters Upper limit, Upper limit
- SensorLower limit and Lower limit - Sensor appear.
Note that this setting is activated by either placing, or not placing the relevant check mark in DIGSI (see
Figure 5-54).

Parameter: Conversion factor

• Default setting (_:104) Conversion factor = 1.00


With the Conversion factor parameter, you set the conversion factor for the measuring transducer.

Parameter: Upper limit, Upper limit - Sensor, Lower limit and Lower limit - Sensor
With the following parameters, you set the scaling of the measuring variables. By that, you can scale in an
application-specific way:

• Default setting Upper limit = 20.00 mA

• Default setting Upper limit - Sensor = 1.00

• Default setting Lower limit = -20.00 mA

• Default setting Lower limit - Sensor = 1.00


With these setting parameters, you set the operating range of the measuring transducer as well as the conver-
sion of the values transmitted to the sensor values. Harmonize the operating range of the measuring trans-
ducer with the transmitter of the sensor. Using the free scalability of the system, you can meet different
requirements. The following figure shows the setting parameters in general terms.

278 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dw_measured-value-scaling, 1, en_US]

Figure 5-55 Scaling Principle

Setting Example 1:
A measuring transducer transmitting a current signal of 4 mA to 20 mA is used as a transmitter. Currents well
below -25.6 mA or above +25.6 mA indicate a transmitter failure; currents around 0 mA indicate a broken
wire. A sensor detecting a temperature is attached to the transmitter. The upper value corresponds to 200 °C
and the lower value to -100 °C. This results in the following characteristic. In accordance with the set charac-
teristic curve, the function calculates the sensor value from the measured current. The coefficients of the
linear equation (gradient and foot point) are calculated from the set threshold and the sensor values are deter-
mined. A supplied current of 9.333 mA corresponds to a temperature of 0 °C.

SIPROTEC 5, 7SJ82/7SJ85, Manual 279


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dw_measuring-transducer-characteristic, 1, en_US]

Figure 5-56 Characteristic Curve of Setting Example 1

NOTE

i The hardware of the measuring transducer has been designed in such a way that measured values are
transmitted and analyzed using the setting range (Upper limit orLower limit). Therefore, special
applications are possible, if necessary. The limits are at approx. +20 mA and -20 mA or +10 V and -10 V.

Setting Example 2:
For special applications, the transmitter sends a maximum of ±12 V. This voltage shall be issued accordingly as
sensor voltage.
Set the parameters as follows:

• Upper limit = 10.00 V

• Upper limit - Sensor = 10.00 V

• Lower limit = -10.00 V

• Lower limit - Sensor = -10.00 V


With this setting, a signal of 12 V is issued as a 12-V measured value (see following figure).

280 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dw_measuring-transducer-setting, 1, en_US]

Figure 5-57 Parameter Settings and Representation of an Input Signal Greater than 10 V

5.6.6.5 Settings

Addr. Parameter C Setting Options Default Setting


MT fast #
_:101 MT in #:TD input-signal • Voltage input Current input
type
• Current input

SIPROTEC 5, 7SJ82/7SJ85, Manual 281


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Addr. Parameter C Setting Options Default Setting


_:103 MT in #:Unit • % A
• °
• °C
• °F
• Ω
• Ω/km
• Ω/mi
• 1/s
• A
• As
• cos φ
• cycles
• dB
• F/km
• F/mi
• h
• Hz
• Hz/s
• in
• J
• J/Wh
• K
• l/s
• m
• mi
• min
• p.u.
• Pa
• periods
• rad
• rad/s
• s
• V
• V/Hz
• VA
• VAh
• var
• varh
• Vs
• W
• W/s
• Wh

282 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Addr. Parameter C Setting Options Default Setting


_:142 MT in #:Measuring • 10 ms 10 ms
window
• 20 ms
• 40 ms
• 60 ms
• 80 ms
• 100 ms
_:107 MT in #:Range active • 0 false
• 1
_:104 MT in #:Conversion -1000000.00 to 1000000.00 1.00
factor
_:105 MT in #:Upper limit -20.00 m Ato 20.00 mA 5.00 mA
_:109 MT in #:Upper limit - -1000000.00 to 1000000.00 1.00
Sensor
_:106 MT in #:Lower limit -20.00 m Ato 20.00 mA 4.00 mA
_:110 MT in #:Lower limit - -1000000.00 to 1000000.00 1.00
Sensor

5.6.6.6 Information List

No. Information Data Class Type


(Type)
MT in #
_:302 MT in #:TD scale MV MV O
_:306 MT in #:TD scale SAV SAV O

5.6.7 RTD Unit Ethernet

5.6.7.1 Overview
The RTD unit Ether. function:

• Communicates with an external RTD unit via the Slave Unit Protocol (SUP) and records the measured
temperatures from the RTD unit

• Provides the captured temperatures to the temperature monitoring function

• Monitors communication with the RTD unit

5.6.7.2 Structure of the Function


The RTD unit Ether. function can only work in the Analog units function group. A maximum of 20 function
instances can work simultaneously. Each instance contains 12 preconfigured sensor function blocks.

SIPROTEC 5, 7SJ82/7SJ85, Manual 283


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dwstrfnc-291112-01.tif, 2, en_US]

Figure 5-58 Structure/Embedding of the Function

5.6.7.3 Communication with an RTD Unit

Logic

[lortdtcp-311012-01.tif, 1, en_US]

Figure 5-59 Logic of the RTD Unit Ether. Function

284 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Communication with an RTD Unit


The function is used to communicate with an RTD box connected via an Ethernet connection. If the connec-
tion of the function is successfully established to the external RTD box via the Ethernet interface, the RTD box
transmits the temperatures of all connected sensors to the RTD box Ether. function. For the connection to be
established successfully, specific communication settings must be set, see chapter 5.6.7.4 Application and
Setting Notes.
The RTD box Ziehl TR1200 IP supports only an Ethernet connection of 10 MBit/s. A direct connection to a 100-
Mbit communication module is therefore not possible. For this reason, you must connect the RTD box to the
communication module via a 10/100 MBit/s autosensing switch which automatically recognizes the transmis-
sion rates and adapts them accordingly. Further information can be found in the Application and setting
notes, see chapter 5.6.7.4 Application and Setting Notes.

Error Responses
The following table lists the conditions under which the Health status transitions to the Alarm or Warning
state.

Table 5-12 Error Responses

Error Description Status Health


The RTD unit Ether. function cannot establish a Alarm
connection with a communication module.
The connection between the communication module Warning
and the RTD unit causes a time-out.
A communication module has not received any more Warning
data from the RTD unit for 9 sec.

The Failure signal is set as soon as one of the sensor function blocks reports a failure.

5.6.7.4 Application and Setting Notes

Parameter: Port

• Default setting (_:2311:103) Port = port J


Use the Port parameter to define over which port the external RTD unit is connected to the SIPROTEC 5
device.
If you want to connect the external RTD unit to the integrated Ethernet interface, set the parameter Port =
Port J. If you want to connect the external RTD unit to an Ethernet plug-in module, set the parameter Port
= Port F, Port E, Port P, or Port N.
You can connect directly the RTD unit to the device via the internal 10-Mbit Ethernet port J. If you operate the
RTD unit on another port via a 100-Mbit communication module, you need an interconnected 10/100-Mbit
autosensing switch, which adapts transmission rates accordingly.

Parameter: IP address

• Default setting (_:2311:104) IP address = 10.16.60.1


With the IP address parameter, you set the IP address of the RTD unit connected to the communication
module via the SUP protocol. Every RTD unit has to be assigned a unique IP address. The IP address to be set
depends on your network configuration. You can set any valid IPv4 address that does not cause conflicts with
other IP addresses in the network. Set an appropriate IP address first at the Ziehl TR1200 IP RTD unit. Then
specify the IP address parameter for the communication module to the same address.

Settings on the RTD Unit


The Ziehl TR1200 IP RTD unit is set with the front keys or in a Web browser on a laptop computer via its
Ethernet interface. Set the connection type of the sensors (3-wire connection or resistance value for 2-wire
connection), the idle state of the fault-indication relay, as well as the IP interface setting.

SIPROTEC 5, 7SJ82/7SJ85, Manual 285


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

The code lock has to be switched off for parameterization. This is only possible using the front keys of the RTD
unit. The code lock is off (switched off) in as-delivered condition and has pin 504.
For detailed information on the settings, refer to the TR1200 IP manual that comes with the RTD unit. The
documents are also available in the SIPROTEC download area (http://www.siprotec.de) under Accessories ->
7XV5662-xAD.
For an Ethernet connection to a SIPROTEC 5 device communicating with the RTD unit TR1200 IP via the SUP
protocol (Slave Unit Protocol), the Modbus TCP setting must be activated in the RTD unit. You can activate
the Modbus TCP protocol using the function keys under the tcP. → Mod / on menu item or with the Web
browser in the TCP/UDP Config tab. The RTD (RTD protocol) and UDP Port settings have no effect here. The
Modbus TCP port is permanently set to 502 and cannot be changed.

5.6.7.5 Temperature Sensor

Logic

[lotmpval-311012-01.tif, 1, en_US]

Figure 5-60 Logic Diagram of the Temperature Sensor Function Block

Measured Temperature Value


The Temperature sensor function block processes one single measured temperature value delivered from the
RTD unit for the assigned sensor. 12 temperature sensor function blocks are always available in each RTD unit
function (both via Ethernet and serial), even if fewer sensors are connected to the RTD unit.
Various temperature sensor types are supported: Pt100, Ni100, and Ni120 sensors. The function block is noti-
fied regarding the selection of connected type via the Sensor type parameter.
The function block delivers a measured temperature value in °C or °F as an output variable. The measured
temperature value is available as an operational measured value and can be monitored by the Temperature
supervision function.

Error Responses
If the measured input value is determined to be incorrect, the quality attribute of the output measured
temperature value is set to invalid. The statuses for Health and Error take the statuses in accordance with
the following table:

Table 5-13 Error response

Error Description Health Status Error Status


Sensor or line short circuited Alarm Yes
Sensor or line interrupted Alarm Yes

286 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Error Description Health Status Error Status


Measured temperature value Alarm Yes
outside the valid measuring range
specified in the technical data. The
valid measuring range depends on
the sensor type.
Sensor not connected OK No

5.6.7.6 Application and Setting Notes

Parameter: Sensor type

• Default setting (_:11611:102) Sensor type = Pt 100


The Sensor type parameter is used to set the sensor element used. You can select between Pt 100, Ni
100 and Ni 120.

Parameter: Temperature unit


To change the display and evaluation of measured temperature values from °C to °F, adapt the DIGSI user
default settings accordingly.
Proceed as follows:

• In DIGSI select the menu item Extras --> Settings.

• In the Settings view select the menu item DIGSI 5 User preferences.

• Under Standard unit system change the setting value of the unit system used from SI units to US
units.

[scfahrht-190214-01, 1, en_US]

Figure 5-61 Change of the Display Between °C and °F

The following settings and information table shows only 1 of the 12 sensors, as the setting possibilities of the
12 sensors do not differ.

SIPROTEC 5, 7SJ82/7SJ85, Manual 287


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

5.6.7.7 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:103 General:Port • port E port J
• port F
• port J
• port N
• port P
Sensor 1
_:11611:102 Sensor 1:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120

5.6.7.8 Information List

No. Information Data Class Type


(Type)
General
_:2311:53 General:Health ENS O
_:2311:56 General:Failure SPS O
Sensor 1
_:11611:52 Sensor 1:Health ENS O
_:11611:60 Sensor 1:Failure SPS O
_:11611:80 Sensor 1:TmpOut MV O

5.6.8 RTD Unit, Serial

5.6.8.1 Overview
The RTD unit serial function:

• Communicates with an external RTD unit serial via the Slave Unit Protocol (SUP) and records the meas-
ured temperatures from the RTD unit

• Provides the captured temperatures to the temperature supervision function

• Monitors communication with the RTD unit


The RTD unit Serial function is set up structurally in the same manner as the RTD unit Ether. function. The
mode of operation is also identical (see 5.6.7.3 Communication with an RTD Unit ).

5.6.8.2 Application and Setting Notes

Parameter: Port

• Default setting (_:2311:103) Port = F


With the Port parameter, you set the slot for the communication module that will be used for the connection
with an external RTD unit.
If you want to connect the external RTD box to an Ethernet plug-in module, set the parameter Port = Port
F , Port E, Port P, or plug-in module position.

Parameter: Channel number

• Default setting (_:2311:105) Channel number = 1

288 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

A serial communication module optionally uses 2 channels. With the Channel number settings, you set the
channel number (1 or 2) through which the RTD unit is connected to the device. The communication module
inputs are labeled with the channel numbers.

Parameter: Slave address

• Default setting (_:2311:106) Slave address = 1


Use the Slave address parameter to define the device address of the RTD unit. If only one RTD unit is
connected to the serial bus, the default value 1 can be used. The same device address has to be set on the RTD
unit. The device address is important for distinguishing among several RTD units connected to a serial bus. Set
a unique device address (for example 1, 2 and 3 when connecting 3 RTD units) for each RTD unit and the same
device address for the parameter Slave address in the 3 RTD unit serial functions.
The following settings and information table shows only 1 of the 12 sensors, as the setting possibilities of the
12 sensors do not differ.

5.6.8.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:103 General:Port • port F port J
• port E
• port P
• port N
• port J
_:2311:105 General:Channel number 1 to 2 1
_:2311:106 General:Slave address 1 to 254 1
Sensor 1
_:11611:102 Sensor 1:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 2
_:11612:102 Sensor 2:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 3
_:11613:102 Sensor 3:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 4
_:11614:102 Sensor 4:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 5
_:11615:102 Sensor 5:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120

SIPROTEC 5, 7SJ82/7SJ85, Manual 289


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Addr. Parameter C Setting Options Default Setting


Sensor 6
_:11616:102 Sensor 6:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 7
_:11617:102 Sensor 7:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 8
_:11618:102 Sensor 8:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 9
_:11619:102 Sensor 9:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 10
_:11611:102 Sensor 10:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 11
_:11611:102 Sensor 11:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120
Sensor 12
_:11611:102 Sensor 12:Sensor type • Pt 100 Pt 100
• Ni 100
• Ni 120

5.6.8.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:53 General:Health ENS O
_:2311:56 General:Failure SPS O
Sensor 1
_:11611:52 Sensor 1:Health ENS O
_:11611:60 Sensor 1:Failure SPS O
_:11611:80 Sensor 1:TmpOut MV O
Sensor 2
_:11612:52 Sensor 2:Health ENS O
_:11612:60 Sensor 2:Failure SPS O
_:11612:80 Sensor 2:TmpOut MV O
Sensor 3
_:11613:52 Sensor 3:Health ENS O

290 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

No. Information Data Class Type


(Type)
_:11613:60 Sensor 3:Failure SPS O
_:11613:80 Sensor 3:TmpOut MV O
Sensor 4
_:11614:52 Sensor 4:Health ENS O
_:11614:60 Sensor 4:Failure SPS O
_:11614:80 Sensor 4:TmpOut MV O
Sensor 5
_:11615:52 Sensor 5:Health ENS O
_:11615:60 Sensor 5:Failure SPS O
_:11615:80 Sensor 5:TmpOut MV O
Sensor 6
_:11616:52 Sensor 6:Health ENS O
_:11616:60 Sensor 6:Failure SPS O
_:11616:80 Sensor 6:TmpOut MV O
Sensor 7
_:11617:52 Sensor 7:Health ENS O
_:11617:60 Sensor 7:Failure SPS O
_:11617:80 Sensor 7:TmpOut MV O
Sensor 8
_:11618:52 Sensor 8:Health ENS O
_:11618:60 Sensor 8:Failure SPS O
_:11618:80 Sensor 8:TmpOut MV O
Sensor 9
_:11619:52 Sensor 9:Health ENS O
_:11619:60 Sensor 9:Failure SPS O
_:11619:80 Sensor 9:TmpOut MV O
Sensor 10
_:11611:52 Sensor 10:Health ENS O
_:11611:60 Sensor 10:Failure SPS O
_:11611:80 Sensor 10:TmpOut MV O
Sensor 11
_:11611:52 Sensor 11:Health ENS O
_:11611:60 Sensor 11:Failure SPS O
_:11611:80 Sensor 11:TmpOut MV O
Sensor 12
_:11611:52 Sensor 12:Health ENS O
_:11611:60 Sensor 12:Failure SPS O
_:11611:80 Sensor 12:TmpOut MV O

5.6.9 Communication with RTD Unit

5.6.9.1 Integration of a Serial RTD Unit (Ziehl TR1200)

Connection of the Communication Lines


Figure 5-62 shows how you connect the RTD unit to the SIPROTEC 5 device. Note that Pin 1 of the RJ45 plug is
connected to RTD-B and Pin 2 is connected to RTD-A.

SIPROTEC 5, 7SJ82/7SJ85, Manual 291


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dwverbau-201112-01.tif, 1, en_US]

Figure 5-62 Connection of the RTD Unit to the SIPROTEC 5 Device

Adding a USART Module


Add a USART-AB-1EL or a USART-AC-2EL USART module in DIGSI to the device. The USART module must be
inserted at one of the plug-in positions for communication modules in the base module or in the CB202
expansion module (refer to the following figure).

[scauser3-190214-01, 1, en_US]

Figure 5-63 Insertion Position for a USART Module

Selecting the SUP Protocol


Select the Slave Unit Protocol (SUP). This protocol is responsible for the communication between the
SIPROTEC 5 device and the RTD Unit.

[scauser4-301012-01.tif, 1, en_US]

Figure 5-64 Selecting the SUP Protocol

292 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Communication Settings
Make the communications settings for the relevant serial channels. For this, use the default settings specified
by the RTD box. Normally, you must adapt only the parameterization of the SIPROTEC 5 device to the settings
of the RTD box. Make sure that the setting values in both devices are the same. The setting of the parameter
Non-flickering light (on/off): is not relevant for the RS485 interface.

NOTE

i The driver for the USART module for the SUP protocol is not preinstalled as standard for the initial use of
this interface (following the firmware update).

[scauser5-301012-01.tif, 1, en_US]

Figure 5-65 Making the Communication Settings

With the selection of the SUP protocol for the RTD box DIGSI automatically adds the function group Analog
units to your device configuration. You can now instantiate the function RTD unit serial 1 (refer to the
following figure).

[scauser6-190214-01, 1, en_US]

Figure 5-66 Analog-Unit Instance

Now, set the channel number over which the SUP protocol runs. In addition, set the slave address of the
RTD box. This address must be set with the same value in the RTD box (refer to the following figure).
The following device configuration must be set on the TR1200 RTD unit when the RTD unit is used for the first
time:

SIPROTEC 5, 7SJ82/7SJ85, Manual 293


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

• Bus protocol: mod

• Device address: 1

• Baud rate: 9600

• Parity: no

[scauser7-220114-01-DE, 1, en_US]

Figure 5-67 Setting the Port, Channel Number, and Slave Address

Finally, load the configuration in the device.

5.6.9.2 Integration of an RTD Unit Ethernet (TR1200 IP)

Device Configuration
In the DIGSI, insert an Ethernet module into the provided slot, thus adding the module to the device configura-
tion. Figure 5-68 displays the available slots in the base module or on the expansion module CB 202. Alterna-
tively, you can also use the integrated Ethernet interface port J.

[scautcp1-220114-01-DE, 1, en_US]

Figure 5-68 Inserting an Ethernet Module

Communication Settings
Activate the SUP Ethernet protocol for the Ethernet module.

294 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[scautcp2-011112-01.tif, 1, en_US]

Figure 5-69 SUP Ethernet Protocol Activation

This protocol is also available for Port J of the integrated Ethernet interface of the base module (refer to
following figure).

[scautcp3-011112-01.tif, 1, en_US]

Figure 5-70 SUP Ethernet Protocol Activation (Base Module)

With the selection of the SUP protocol for the RTD unit, DIGSI automatically adds the Analog units function
group and the RTD unit Ether. function to your device configuration (refer to the following figure).

[scauser6-190214-01, 1, en_US]

Figure 5-71 Analog Unit Instance

Now, set the port over which the SUP protocol runs. In addition, set the IP address of the RTD box (refer to the
following figure). This address must be set with the same value in the RTD box.

SIPROTEC 5, 7SJ82/7SJ85, Manual 295


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[scautcp5-301012-01.tif, 1, en_US]

Figure 5-72 Setting the Port and IP Address

Finally, load the configuration in the device.

5.6.9.3 Temperature Simulation without Sensors


Connect a resistor on the sensor terminals of the RTD unit. Using this resistor, simulate a constant tempera-
ture. The resistance value should be around 50 Ω to 200 Ω.
If you want to simulate a changeable temperature, connect an adjustable resistor of maximum 470 Ω instead
of a fixed resistor.

5.6.10 Temperature Acquisition via Protocols

5.6.10.1 Overview
The function Temperature acquisition via protocols:

• Obtains the temperature from a power-plant control system or from another protection device

• Processes the temperature, for example, supervises the temperature in the CFC

• Transfers the temperature to other protection devices

5.6.10.2 Structure of the Function


The function Temperature acquisition via protocols can work only in the function group Analog units. In
this function, the following stages can operate simultaneously:

• 12 stages Temperature acquisition via PROFINET IO or IEC 61850


The stage can obtain the temperature from a power-plant control system via PROFINET IO or via
IEC 61850.

• 12 stages Temperature acquisition via GOOSE


The stage can obtain the temperature from another SIPROTEC 5 protection device via GOOSE.
The function Temperature acquisition via protocols comes factory-set with 1 stage Temperature acquisi-
tion via PROFINET IO or IEC 61850.

296 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dw_structure_TmpviaProt, 1, en_US]

Figure 5-73 Structure/Embedding of the Function

5.6.10.3 Stage Temperature Acquisition via PROFINET IO or IEC 61850

Logic

[lo_tmpval, 1, en_US]

Figure 5-74 Logic Diagram of the Stage

The stage processes the transmitted temperature via PROFINET IO or via IEC 61850.

• Via PROFINET IO, only the analog value of the temperature is transmitted.

• Via IEC 61850, the analog value of the temperature, the quality of the temperature, and the time stamp
are transmitted.

Temperature-Failure Indication
If the received temperature is invalid, the failure indication Temperature failure is issued.

Stage Application
The following figure shows the application example. The temperature sensor measures, for example the cold-
gas temperature of the generator and feeds it to the power-plant control system. In the SIPROTEC 5 protection
device, the function Temperature acquisition via protocols acquires the cold-gas temperature from the

SIPROTEC 5, 7SJ82/7SJ85, Manual 297


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

power-plant control system and processes the cold-gas temperature in the function. The function Tempera-
ture acquisition via protocols can also send the processed temperature value to other functions for further
processing.

[dw_AppEXP_IEC, 1, en_US]

Figure 5-75 Application Example

The following table explains the data.


Data Name Description
Tmp The variable is used to acquire the temperature via the protocol PROFINET IO or via the
protocol IEC 61850.
In the stage Temperature acquisition via PROFINET IO or IEC 61850, the data type is
APC.
Unit The parameter is used to select the unit °F or °C for the temperature which is acquired
from the power-plant control system.

298 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Configuration Example
To acquire the temperature with the stage Temperature acquisition via PROFINET IO or IEC 61850, proceed
in DIGSI as follows:

• Via PROFINET IO
– In the project tree, select Device → Hardware and protocols.
– In the Device view, select an Ethernet port of the device.
If the device has no Ethernet port, select Hardware catalog → SIRPOTEC 5 → Communication to
add one to the device.
– In the Properties view of the Ethernet port, select General → Ethernet addresses.
– Under IP protocol, set the IP address for the port.

[sc_PROFINET IP, 1, en_US]

Figure 5-76 IP Configuration


– In the Properties view of the Ethernet port, select General → Ethernet-interface settings.
– Under Communication protocols, change the setting value of the parameter Selected protocol to
PROFINET IO.

[sc_PROFINET_IO, 1, en_US]

Figure 5-77 Protocol Selection


– In the project tree, select Device → Settings → Analog units.
– Instantiate the function Tmp.Acq.viaCom in the function group Analog units.
– In the project tree, select Device → Communication mapping.

SIPROTEC 5, 7SJ82/7SJ85, Manual 299


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

– In the Communication mapping window, set Show protocol to PROFINET IO.

[sc_PROFI_Filter, 1, en_US]

Figure 5-78 Protocol Filter


– In the column Signals, select Analog units → Tmp.Acq.viaCom 1 → Tmp.Ctl 1.
– Route the data Tmp in column R and set the value to 1.

[sc_PROFI_Setting, 1, en_US]

Figure 5-79 Signal Configuration


Now you can use the stage Temperature acquisition via PROFINET IO or IEC 61850 to acquire the cold-
gas temperature via PROFINET IO.

300 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

• Via IEC 61850


– In the project tree, select Device → Device information.
– In the Device information view, change the setting value of the parameter Edition to IEC 61850
Edition 2.
– In following dialog, click Yes.

[sc_PopupDialog, 1, en_US]

Figure 5-80 Confirmation of the IEC 61850 Edition Conversion

The IEC 61850 edition of the device changes to edition 2.

[sc_DeviceEdition, 1, en_US]

Figure 5-81 Converted IEC 61850 Edition


– In the project tree, select Device → Hardware and protocols.
– In the Device view, select the port that you want to communicate via IEC 61850.
– In the Properties view of the port, select General → Ethernet addresses.
– Under IP protocol, set the IP address for the port.

SIPROTEC 5, 7SJ82/7SJ85, Manual 301


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc_IEC61850_IP, 1, en_US]

Figure 5-82 IP Configuration


– Select General → Ethernet-interface settings.
– Under Communication protocols, check IEC 61850-8-1.

[sc_IEC61850Sel, 1, en_US]

Figure 5-83 Protocol Selection


– In the project tree, select Device → Settings → Analog units.
– Instantiate the function Tmp.Acq.viaCom in the function group Analog units.

302 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

– Instantiate the function which requires the cold-gas temperature in the corresponding function
group. The function 49R RotorTOLP is taken as an example in the following step.
– Under General of the function 49R RotorTOLP, change the setting values of the parameters
Temperature acquisition and Temperature via protocol to Protocol COM and
Tmp.Acq.viaCom 1.Tmp.Ctl 1 respectively.

[sc_IEC61850_3, 1, en_US]

Figure 5-84 Parameter Configuration


– In the project tree, select Device → IEC 61850 structure.
– In the column Name, select AnUn_TmpAcqCom 1 → VIAC_STMP1.
– Active the data CTmp.

[sc_IEC61850_CGT, 1, en_US]

Figure 5-85 Data Selection


Now you can use the stage Temperature acquisition via PROFINET IO or IEC 61850 to acquire the cold-
gas temperature via IEC 61850.

SIPROTEC 5, 7SJ82/7SJ85, Manual 303


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

5.6.10.4 Stage Temperature Acquisition via GOOSE

Logic

[lo_tmpval, 1, en_US]

Figure 5-86 Logic Diagram of the Stage

Temperature Failure Indication


If the received temperature is invalid, a failure indication Temperature failure is issued.

Stage Application
The following figure shows the application example. The temperature sensor measures, for example the cold-
gas temperature of the generator and feeds it to the SIPROTEC 5 device 2. In the SIPROTEC 5 protection device
1, the function Temperature acquisition via protocols acquires the cold-gas temperature from the
SIPROTEC 5 device 2 and processes the cold-gas temperature in the function. The function Temperature
acquisition via protocols can also send the processed temperature value to other functions for further
processing.

304 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[dw_AppEXP_GOOSE, 1, en_US]

Figure 5-87 Application Example

The following table shows the explanations of the data:


Data Name Description
Tmp The variable is used to acquire the temperature via GOOSE.
In the stage Temperature acquisition via GOOSE, the input measured value with a
COM template is designed to acquire the data from another protection device.
Unit The parameter is used to select the unit °F or °C for the temperature which is acquired
from another protection device.

SIPROTEC 5, 7SJ82/7SJ85, Manual 305


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

Configuration Example

• Configure the source device.


– In the project tree, select Project → Device information.
– In the Device information view, change the setting value of the parameter Edition to IEC 61850
Edition 2.
The following dialog shows up. To acquire the cold-gas temperature, click Yes.

[sc_PopupDialog, 1, en_US]

Figure 5-88 Confirmation of the IEC 61850 Edition Conversion


– Select Device → Hardware and protocols.
– In the Device view, select the port that you want to communicate with IEC 61850.
– In the Properties view of the port, select General → Ethernet addresses.
– Under IP protocol, set the IP address for the port.

[sc_IEC61850_IP, 1, en_US]

Figure 5-89 IP Configuration


– Select General → Ethernet-interface settings.
– Under Communication protocols, check IEC 61850-8-1.

306 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc_IEC61850Sel, 1, en_US]

Figure 5-90 Protocol Selection


– In the project tree, select Device → Settings → Analog units.
– Instantiate the function Tmp.Acq.viaCom in the function group Analog units.
– Select Device → IEC 61850 structure.
– In the column Name, select AnUn_TmpAcqCom 1 → VIAC_STMP1.
– Active the data CTmp.

[sc_IEC61850_CGT, 1, en_US]

Figure 5-91 Data Selection


Now the device can be used to send the cold-gas temperature to other devices.

SIPROTEC 5, 7SJ82/7SJ85, Manual 307


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

• Configure the destination device.


– In the project tree, select Device → Device information.
– In the Device information view, change the setting value of the parameter Edition to IEC 61850
Edition 2.
– In following dialog, click Yes.

[sc_PopupDialog, 1, en_US]

Figure 5-92 Confirmation of the IEC 61850 Edition Conversion

The IEC 61850 edition of the device changes to edition 2.

[sc_DeviceEdition, 1, en_US]

Figure 5-93 Converted IEC 61850 Edition


– In the project tree, select Device → Hardware and protocols.
– In the Device view, select the port that you want to communicate with via GOOSE.
– In the Properties view of the port, select General → Ethernet addresses.
– Under IP protocol, set the IP address for the port.

308 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc_IEC61850_IP, 1, en_US]

Figure 5-94 IP Configuration


– Select General → Ethernet-interface settings.
– Under Communication protocols, check IEC 61850-8-1.

[sc_IEC61850Sel, 1, en_US]

Figure 5-95 Protocol Selection


– In the project tree, select Device → Settings → Analog units.
– Instantiate the function Tmp.Acq.viaCom in the function group Analog units.
– Instantiate the stage Tmp.GOOSE in the function Tmp.Acq.viaCom.

SIPROTEC 5, 7SJ82/7SJ85, Manual 309


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

– Select Device → Information routing.


– In the column Signals, select Analog units → Tmp.Acq.viaCom 1 → Tmp.Goose 1.
– Enter 1 in the column GOOSE for the data Tmp.

[sc_Station10, 1, en_US]

Signal Configuration
– In the project tree, select Device → Settings.
– Instantiate the function which requires the cold-gas temperature in the corresponding function
group. The function 49R RotorTOLP is taken as an example in the following step.
– Under General of the function 49R RotorTOLP, change the setting values of the parameters
Temperature acquisition and Temperature via protocol to Protocol COM and
Tmp.Acq.viaCom 1.Tmp.Goose 1 respectively.

[sc_GOOSE_CGT, 1, en_US]

Figure 5-96 Parameter Configuration


Now the device can be used to receive the cold-gas temperature from another device.

310 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

• Connect the source device and the destination device.


– In the project tree, select IEC 61850 stations.
– Double-click Add new station and create a station.
– In the Properties view of the station, change the setting value of IEC Edition to IEC 61850
Edition 2.
– In following dialog, click Yes.

[sc_StationConfirmation, 1, en_US]

Figure 5-97 Confirmation of the IEC 61850 Edition Conversion

The IEC 61850 edition of the station changes to edition 2.

[sc_IECStation, 1, en_US]

Figure 5-98 Converted IEC 61850 Edition


– Assign the available devices to the IEC station.

SIPROTEC 5, 7SJ82/7SJ85, Manual 311


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc_DeviceAssign, 1, en_US]

Figure 5-99 Device Assignment


– Right-click the station and select Export changes to IEC 61850 System Configurator in the context
menu.

[sc_ExportIEC, 1, en_US]

Figure 5-100 Export Changes to IEC 61850 System Configurator


– In the following dialog, click OK and save the SCD file to a folder.

312 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc_IECConfim, 1, en_US]

Figure 5-101 SCD File Creation


– In the opened IEC 61850 System Configurator window, select GOOSE in the toolbar.

[sc_Station1, 1, en_US]

Figure 5-102 GOOSE Function Selection


– In the GOOSE messages view, right-click the IEC station and select GOOSE application in the
context menu.

SIPROTEC 5, 7SJ82/7SJ85, Manual 313


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc_Station2, 1, en_US]

Figure 5-103 GOOSE Application Creation


– In the Source catalog box, select Source device → AnUn_TmpAcqCom 1 → VIAC_STMP1.
– Drag the data CTmp and drop it to the GOOSE application.

[sc_Station3, 1, en_US]

Figure 5-104 Source Data Selection

314 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

You can see the assigned source data in the GOOSE messages view.

[sc_Station4, 1, en_US]

Figure 5-105 Source Data Assignment


– Unfold the assigned source data.
– In the Destination catalog box, select Destination device → AnUn_TmpAcqCom1.
– Drag the data RxTmp and drop it to the assigned source data.

[sc_Station6, 1, en_US]

Figure 5-106 Target Data Selection

Now the destination data is connected with the source data.

[sc_Station11, 1, en_US]

Figure 5-107 Target Data Assignment


– Save the configuration and close the IEC station.
– In the project tree, right-click the station and select Import changes from IEC 61850 System
Configurator in the context menu.

SIPROTEC 5, 7SJ82/7SJ85, Manual 315


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

[sc_Station8, 1, en_US]

Figure 5-108 Import Changes from IEC 61850 System Configurator

If the following dialog shows up, the source device and the destination device are successfully
connected.

[sc_End, 1, en_US]

Figure 5-109 Successful Devices Connection


– Click OK to finish the connection.
Now you can use the stage Temperature acquisition via GOOSE to acquire the cold-gas temperature via
GOOSE.

316 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

5.6.10.5 Application and Setting Notes

Change of the Temperature Unit


Commonly, the temperature unit °C is used in the display and evaluation of measured temperature values.

• To change the temperature unit from °C to °F for all devices in the current DIGSI project, proceed as
follows:
– In DIGSI, select the menu item Options → Settings.
– In the Settings view, select the menu item DIGSI 5 user preferences.
– Under Standard unit system, change the setting value of the unit system used from SI units to
US units.

[scfahrht-190214-01, 1, en_US]

Figure 5-110 Change of the Temperature Unit between °C and °F for all Devices

• To change the temperature unit from °C to °F for 1 device, proceed as follows:


– In the project tree, select Device → Settings → Device settings.
– In the Device settings view, select the menu item Localization.
– Under Unit system, change the setting value of the unit system used from SI to ANSI.

[sc_SITmp, 1, en_US]

Figure 5-111 Change of the Temperature Unit between °C and °F for 1 Device

SIPROTEC 5, 7SJ82/7SJ85, Manual 317


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.6 Function-Group Type Analog Units

NOTE

i If the parameter Unit system is set to ANSI, only the unit of the measuring values and parameters
changes to °F. The unit of the data used in the device and the thresholds in DCF is still °C.

Parameter: Unit

• Default setting (_:19801:101) Unit = °C


You use the setting Unit to specify which physical unit of the source data the measured values represent. The
possible setting values are listed in the settings table.

5.6.10.6 Settings

Addr. Parameter C Setting Options Default Setting


Tmp.Ctl 1
_:19801:101 Tmp.Ctl 1:Unit • °C °C
• °F

5.6.10.7 Information List

No. Information Data Class Type


(Type)
Tmp.Ctl 1
_:19801:300 Tmp.Ctl 1:Tmp APC C
_:19801:53 Tmp.Ctl 1:Health ENS O
_:19801:301 Tmp.Ctl 1:Failure SPS O
_:19801:302 Tmp.Ctl 1:TmpOut MV O

318 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

5.7 Function-Group Type Circuit Breaker

5.7.1 Overview

The Circuit-breaker function group combines all the user functions that relate to a circuit breaker.
You will find the Circuit-breaker function group under each device type in the Global DIGSI 5 function library.
The Circuit-breaker function group contains all of the protection, control, and supervision functions that you
can use for this device type. The following figure shows, for example, the functional scope of the Circuit-
breaker function group.

[scfgleis-200214-01, 1, en_US]

Figure 5-112 Circuit-Breaker Function Group – Example of the Functional Scope

The Circuit-breaker function group includes 3 different types of circuit breakers:

• Circuit breaker

• Circuit-breaker control

• Circuit breaker [status only]


The circuit-breaker type can accept additional basic function blocks for protection functions along with the
actual circuit-breaker control.

SIPROTEC 5, 7SJ82/7SJ85, Manual 319


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

The type circuit breaker [status only] is used only for acquiring the circuit-breaker switch position. This type
can be used to model switches that can only be read but not controlled by the SIPROTEC 5 device.
The available functions are described in the chapters 6 Protection and Automation Functions and 8 Control
Functions.

5.7.2 Structure of the Function Group

Besides the user functions, the Circuit-breaker function group contains certain functionalities that are essen-
tial for general purposes and therefore cannot be loaded or deleted:

• Trip logic

• Mapping the physical circuit breaker

• Circuit-breaker position recognition for protection functions

• Detection of manual closure

• General settings
The following figure shows the structure of the Circuit-breaker function group. The individual function blocks
in the image are described in the following chapters.

[dwfgstru-080812-01.tif, 1, en_US]

Figure 5-113 Structure of the Circuit-Breaker Function Group

The Circuit-breaker function group has interfaces with:

• Measuring points

• Protection function groups

Interfaces with Measuring Points


The function group contains the measured values needed from the measuring points associated with this
function group.

320 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

If an application template is used, the function group is connected to the measuring point of the 3-phase
current because this connection is essential. It can be necessary to connect additional measuring points to the
function group, depending on the nature of the user functions used. The configuration is carried out using the
Function-group connections editor in DIGSI 5. You can find more detailed information on this in chapter
2.1 Function Embedding in the Device.
If a user function, for example, synchronization, is used in the function group but the required measuring
point has not linked to it, DIGSI 5 reports an inconsistency. This inconsistency provides an indication of the
missing measuring-point connection.
The Circuit-breaker function group has interfaces with the following measuring points:

• 3-phase line current


The measurands from the 3-phase current system are supplied via this interface. The function group must
always be connected to this measuring point.

• Voltage
The measurands from the 3-phase voltage system are supplied via this interface. Depending on the
connection type of the transformers, in the 3-phase voltage system these are, for example, VA, VB, VC of
the line or feeder. The connection of the function group to this measuring point is optional.

• Sync. Voltage1, Sync. Voltage2


A 1-phase synchronization voltage (for example, voltage of the busbar with a 1-phase connection) or a 3-
phase synchronization voltage (for example, voltage of the busbar with a 3-phase connection) is supplied
via this interface.
The connection to the corresponding measuring point is necessary only if synchronization is used.

Interface with Protection-Function Groups


All required data is exchanged between the protection function groups and the Circuit-breaker function
group via the interfaces of the Circuit-breaker function group. This data includes, for example, the pickup and
operate indications of the protection functions sent in the direction of the Circuit-breaker function group and,
for example, the circuit-breaker position information in the direction of the protection function groups.
If an application template is used, the function groups are connected to each other because this connection is
essential to ensure proper operation. You can modify the connection using the Function-group connections
editor in DIGSI 5.
You can find more detailed information in chapter 2.1 Function Embedding in the Device.
If the connection is missing, DIGSI 5 reports an inconsistency.
Besides the general assignments of the protection function group or groups to the Circuit-breaker function
groups, you can also configure the interface for certain functionalities in detail:

• Which operate indications of the protection functions are included when the trip command is generated?

• Which protection functions activate the Automatic reclosing function?

• Which protection functions activate the Circuit-breaker failure protection function?


You can find more detailed information in chapter 2.1 Function Embedding in the Device.

5.7.3 Application and Setting Notes

Interface with Measuring Points


The interface with the 3-phase current system must have been configured. Otherwise, DIGSI 5 supplies an
inconsistency message.
If the Synchronization function is used, the measuring points that represent voltages V1 and V2 of the parts
of the electrical power system to be synchronized must be connected.
You can find more detailed information in chapter 8.4 Synchronization Function.
The Automatic reclosing function provides the auxiliary functions Dead-line check and Reduced dead time.
For these auxiliary functions, the 3-phase voltage system has to be measured. If you want to use these auxil-
iary functions, the measuring point of the 3-phase voltage system must be connected to the Voltage function

SIPROTEC 5, 7SJ82/7SJ85, Manual 321


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

group interface. This connection is also necessary if the Automatic reclosing function with adaptive dead
time function type is used.

Interface with Protection-Function Groups


The protection-function group is connected to 2 circuit breakers (2 Circuit-breaker function groups) for 1 1/2
circuit-breaker layouts.

Parameter: I Reference for % Values

• Default setting (_:2311:101) Rated normal current = 1000 A


With the Rated normal current parameter, you set the primary current which serves as a reference for all
current-related % values within the Circuit-breaker function group. This applies both for operational measured
values and for setting values in %.
Enter the primary rated current of the protected object here.
If the device works with the IEC 61850 protocol, then you change the setting value of the parameter only via
DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.

Parameter: V Reference for % Values

• Default setting (_:2311:102) Rated voltage = 400 kV


With the Rated voltage parameter, you set the primary voltage, which serves as a reference for all voltage-
related % values within the Circuit-breaker function group. This applies both for operational measured values
and for setting values in %.
Enter the primary rated voltage of the protected object (for example, the line) here.
If the device works with the IEC 61850 protocol, then you change the setting value of the parameter only via
DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.

Parameter: Current Threshold Circuit Breaker Open

• Default setting (_:2311:112) Current thresh. CB open = 0.10 A


With the Current thresh. CB open parameter, you specify the current threshold below which the circuit-
breaker pole or the circuit breaker is recognized as open.
Set the Current thresh. CB open parameter so that the current measured when the circuit-breaker pole
is open will certainly fall below the parameterized value. If parasitic currents (for example, due to induction)
are excluded with the line deactivated, you can make a secondary setting of the value with a high degree of
sensitivity, to 0.05 A for example.
If no special requirements exist, Siemens recommends retaining the setting value of 0.10 A for secondary
purposes.

5.7.4 Settings

Addr. Parameter C Setting Options Default Setting


Ref. for %-values
_:2311:101 General:Rated normal 0.20 A to 100000.00 A 1000.00 A
current
_:2311:102 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV

322 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

Addr. Parameter C Setting Options Default Setting


Breaker settings
_:2311:112 General:Current thresh. 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
CB open 5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2311:136 General:Op. mode BFP • unbalancing unbalancing
• I> query

5.7.5 Information List

No. Information Data Class Type


(Type)
Circuit break.
_:4261:500 Circuit break.:>Ready SPS I
_:4261:501 Circuit break.:>Acquisition blocking SPS I
_:4261:502 Circuit break.:>Reset switch statist. SPS I
_:4261:504 Circuit break.:>Reset AcqBlk&Subst SPS I
_:4261:503 Circuit break.:External health ENS I
_:4261:53 Circuit break.:Health ENS O
_:4261:58 Circuit break.:Position DPC C
_:4261:300 Circuit break.:Trip/open cmd. SPS O
_:4261:301 Circuit break.:Close command SPS O
_:4261:302 Circuit break.:Command active SPS O
_:4261:303 Circuit break.:Definitive trip SPS O
_:4261:304 Circuit break.:Alarm suppression SPS O
_:4261:306 Circuit break.:Op.ct. INS O
_:4261:307 Circuit break.:ΣI Brk. BCR O
_:4261:308 Circuit break.:ΣIA Brk. BCR O
_:4261:309 Circuit break.:ΣIB Brk. BCR O
_:4261:310 Circuit break.:ΣIC Brk. BCR O
_:4261:311 Circuit break.:Break.-current phs A MV O
_:4261:312 Circuit break.:Break.-current phs B MV O
_:4261:313 Circuit break.:Break.-current phs C MV O
_:4261:317 Circuit break.:Tripping current 3I0/IN MV O
_:4261:314 Circuit break.:Break. voltage phs A MV O
_:4261:315 Circuit break.:Break. voltage phs B MV O
_:4261:316 Circuit break.:Break. voltage phs C MV O
_:4261:322 Circuit break.:CB open hours INS O
_:4261:323 Circuit break.:Operating hours INS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 323


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

5.7.6 Trip Logic

5.7.6.1 Function Description


The Trip logic function block receives the group operate indication from the Protection function group or
Protection function groups and forms the protection trip command that is transmitted to the Circuit-breaker
function block.
The Circuit-breaker function block activates the device contact and thus causes the circuit breaker to open
(see 5.7.7 Circuit Breaker). The command output time is also effective here.
The trip logic also decides when the protection trip command is reset (see Figure 5-115).

[loausbef-140113-01.tif, 1, en_US]

Figure 5-114 Trip Command

Trip-Command Reset

[lobefe3p-140113-01.tif, 1, en_US]

Figure 5-115 Trip-Command Reset

Once a trip command is issued, it is stored (see Figure 5-114).


You determine the criteria for resetting a trip command that has been issued with the parameter Reset of
trip command. The following setting options are possible:

• with dropout
If the function that initiated tripping resets its operate indication the trip command is reset. This occurs
typically with dropout. Command reset of the trip command takes place regardless of verification of the
circuit-breaker condition.

• with I<

324 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

• with I< & aux.contact


For these criteria, the state of the circuit breaker is also taken into account as a further criterion in addi-
tion to the dropout of the tripping function (operate indication is reset by command). You can select
whether the state is determined by means of the current (with I<) or by means of the current in
conjunction with the circuit-breaker auxiliary contacts (with I< & aux.contact). The behavior of
these setting options only differs in one situation of the circuit-breaker state. If the circuit breaker is in
the opening state, the trip command is reset in the case of the option with I<, whereas it is not reset
yet in the case of the option with with I< & aux.contact. The opening state is detected if the auxil-
iary contacts still detect the circuit breaker as being closed and opening is detected via the decreasing
current flow.
As long as the circuit breaker is detected unambiguously as closed (fully closed), the trip command will
not be reset with these setting options.
The information about the condition of the circuit breaker and the determination of the various condi-
tions is supplied by the Circuit-breaker position recognition function block. You can find further infor-
mation in chapter 5.7.8 Circuit-Breaker Position Recognition for Protection-Related Auxiliary Functions.

5.7.6.2 Application and Setting Notes

Parameter: Reset of trip command

• Recommended setting value (_:5341:103) Reset of trip command = with I<

Parameter Value Description


with I< The trip command is reset under the following conditions:

• Dropout of the tripping function


• The current falls short of the value set in the parameter
(_:2311:112) Current thresh. CB open
with I< & aux.contact The trip command is reset under the following conditions:

• The current falls short of the value set in the parameter


(_:2311:112) Current thresh. CB open
• The circuit-breaker auxiliary contact reports that the circuit breaker is
open.
This setting assumes that the setting of the auxiliary contact has been
routed via a binary input (for more information, see 5.7.7.3 Acquisition
of Circuit-Breaker Auxiliary Contacts and Further Information).
with dropout If the load current in the system cannot be interrupted during the protec-
tion device test and the test current is fed in parallel with the load current
this setting is useful.
The setting can be selected for special applications in which the trip
command does not result in complete interruption of the current in every
case. In this case, the trip command is reset if the pickup of the tripping
protection function drops out.

5.7.6.3 Settings

Addr. Parameter C Setting Options Default Setting


Trip logic
_:103 Trip logic:Reset of trip • with I< with I<
command
• with I< & aux.contact
• with dropout

SIPROTEC 5, 7SJ82/7SJ85, Manual 325


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

5.7.6.4 Information List

No. Information Data Class Type


(Type)
Trip logic
_:300 Trip logic:Trip indication ACT O

5.7.7 Circuit Breaker

5.7.7.1 Overview
The Circuit-breaker function block represents the physical switch in the SIPROTEC 5 device.
The basic tasks of this function block are:

• Operation of the circuit breaker

• Acquisition of the circuit-breaker auxiliary contacts

• Acquistion of other circuit-breaker information


The Circuit-breaker function block provides the following information:

• Number of switching cycles

• Breaking current, breaking voltage, and breaking frequency

• Summation breaking current

5.7.7.2 Tripping, Opening, and Closing the Circuit Breaker


The circuit breaker is operated in the following situations:

• Tripping of the circuit breaker as a result of a protection trip command

• Opening of the circuit breaker as a result of control operations

• Closing of the circuit breaker as a result of automatic reclosing or control operations


Tripping is always the result of a protection function. The operate indications of the individual protection func-
tions are summarized in the Trip logic function block. The trip command that causes the tripping in the
Circuit-breaker function block is generated there.
To operate the circuit breaker, the Circuit-breaker function block provides the output signals that must be
routed to the corresponding binary outputs of the device (see Table 5-14).

326 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

[loausssc-090211-01.tif, 1, en_US]

Figure 5-116 Tripping, Opening, and Closing the Circuit Breaker

Table 5-14 Description of the Output Signals

Signal Description Routing Options


Trip/open cmd. This signal executes all tripping and opening opera- • Unlatched
tions.
• Only saved in
The Output time parameter affects the signal. the event of
The signal is pending for the duration of output time, protection trip-
with the following exceptions: ping (not when
opened)
• Only when switched off by the control:
If the auxiliary contacts report that the circuit
breaker is open before expiration of the period
the signal is canceled before expiration of the
period.
• Only in the event of protection tripping:
The signal remains active as long as the trip
command is still active after expiration of the
period (see also 5.7.6.1 Function Description).
• Only in the event of protection tripping:
With the routing option Only saved in the
event of protection tripping, the signal remains
pending until it is acknowledged manually. This
only applies for protection tripping.
Close command This signal executes all closing operations. Normal routing
The Output time parameter affects the signal.
The signal is pending for the duration of this period,
with the following exception: The signal is canceled
before expiration of the period if the auxiliary
contacts report that the circuit breaker is closed
before expiration of the period.

SIPROTEC 5, 7SJ82/7SJ85, Manual 327


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

Signal Description Routing Options


Command active This signal is active as long as one of the binary Normal routing
outputs is active:

• Trip/open cmd.
• Close command
The binary outputs are active while a switching
command is being executed by the control.

5.7.7.3 Acquisition of Circuit-Breaker Auxiliary Contacts and Further Information


To determine the circuit breaker position, the Circuit-breaker function block provides position signals. These
signals are of the Double-point indication (DPC) type. A double-point indication can be routed to 2 binary
inputs so that the open and closed circuit-breaker positions can be reliably acquired.

[loerfass-101210-01.tif, 1, en_US]

Figure 5-117 Acquisition of the Circuit-Breaker Information

Signal Type Description


Position DPC Acquisition of the circuit-breaker position
The position 3-pole circuit breaker open and/or the position 3-pole
circuit breaker closed can be acquired by routing to 1 or 2 binary inputs.

The signals must be routed to the binary input that is connected with the CB auxiliary contacts. The open and
closed signals do not necessarily have to be routed in parallel. The advantage of parallel routing is that it can
be used to determine an intermediate or disturbed position. If only one signal is routed (open or closed), you
cannot determine the intermediate or disturbed position.
In the monitoring direction, the position signals generate the following information when the open and
closed positions are acquired (see following table). This information is further processed by the Circuit-
breaker position recognition and Control function blocks.
Information Type Description
Open SPS The circuit-breaker position is open.
Closed SPS The circuit-breaker position is closed.
Intermediate position SPS The circuit-breaker position is in intermediate position.
Disturbed position SPS The circuit-breaker position is in disturbed position.
Not selected SPS The circuit breaker is not selected for a control operation.

328 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

The following table shows further input signals:


Signal Type Description
>Acquisition SPS This is used to activate acquisition blocking of the circuit-breaker auxil-
blocking iary contacts (see Other Functions 3.9.3 Persistent Commands for a
description of acquisition blocking).
>Reset SPS This is used to reset acquisition blocking and manual update of the
AcqBlk&Subst circuit breaker. When the signal is active, acquisition blocking and
tracking are reset.
>Ready SPS The active signal indicates that the circuit breaker is ready for an Open-
closed-open cycle.
The signal remains active as long as the circuit breaker is unable to trip.
The signal is used in the Automatic reclosing and Circuit-breaker test
functions.

The following table shows another output signal:


Signal Type Description
External health SPS This can be used to indicate the health of the physical circuit breaker.
For this, you must acquire any failure information for the circuit breaker
via a binary input. This failure information can be used to set the appro-
priate state of the External health signal with a CFC chart (using
the BUILD_ENS block).
The signal has no effect on the health of the function block.

5.7.7.4 Definitive Tripping, Circuit-Breaker Tripping Alarm Suppression

Definitive Tripping
Definitive tripping is always pending whenever the Automatic reclosing (AREC) function does not carry out
any reclosing after tripping. It follows that this is the case whenever an automatic reclosing is not present or
the AREC has been switched off.

Circuit-Breaker Tripping Alarm Suppression


In certain systems, the user may wish to actuate an alarm (for example, a horn) when tripping (circuit-breaker
tripping) occurs. This alarm should not be issued if it is to be reclosed automatically after tripping, or if it is to
be closed or opened via the control. The alarm is only to be issued in the event of definitive tripping.
Depending on how the alarm is generated (for example, triggered by a fleeting contact of the circuit breaker),
the Alarm suppression signal can be used to suppress the alarm.
If one of the following conditions is met, the Alarm suppression signal is generated:

• The definitive protection tripping is not present.

• The integrated automatic reclosing function executes a closure.

• The integrated control executes a closure or opening action.

• External closing is detected via the Manual close function.


For further information about its use, refer to 5.7.9.2 Application and Setting Notes.

SIPROTEC 5, 7SJ82/7SJ85, Manual 329


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

[lounterd-100611-01.tif, 2, en_US]

Figure 5-118 Definitive Tripping and Circuit-Breaker Tripping Alarm Suppression

5.7.7.5 Tripping and Opening Information


When a trip or opening command is issued, the breaking information shown in the next figure is saved in the
fault log.

[loausloe-081210-01.tif, 2, en_US]

Figure 5-119 Breaking Information

The following statistics information is saved for the circuit breaker:

• Number of switching cycles:


All tripping, opening, and closing operations are counted.

• Number of closing operations by the automatic reclosing function

• Total of breaking currents


The statistics information can be individually set and reset via the device control. It is also possible to reset all
values via the binary input signal >Reset switch statist..

[lo_statistics information circuit-breaker, 2, en_US]

Figure 5-120 Statistics Information About the Circuit Breaker

330 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

5.7.7.6 Application and Setting Notes

Routings for Activation of the Circuit Breaker


Figure 5-121 shows the necessary routings for the device:

• 3-pole tripping via the protection

• 3-pole opening via the control

• 3-pole closing via AREC or via the control

[loansteu-230311-01.tif, 2, en_US]

Figure 5-121 Activation of the Circuit Breaker

By routing the Trip/open cmd. signals to 1 or 2 binary outputs, you can carry out 1-pole, 1.5-pole, and 2-
pole activations of the circuit breaker. You can find a detailed description in chapter 8.2.2.3 Connection
Variants of the Circuit Breaker.

NOTE

i Do not confuse these 1-pole, 1.5-pole, and 2-pole activations of the circuit breaker with 1-pole or 3-pole
tripping of the circuit breaker.

Routings for Analysis of the Circuit-Breaker Switch Position


For certain functions of the device, it is useful to detect the circuit-breaker switch position via its auxiliary
contacts. In the following, you can find some examples:

• Circuit-breaker position recognition function block

• Circuit-breaker failure protection function

• Control function block


The operating principle of the auxiliary contacts is described in the individual functions.
Siemens recommends capturing the Circuit breaker is open in 3 poles and Circuit breaker
is closed in 3 poles information via auxiliary contacts. This is the optimal configuration for the control
functionality. For purely protection applications, it is also enough to capture just one of the 2 circuit-breaker
positions. When used as a protection and control device Siemens recommends the following analysis of the
circuit-breaker position:

SIPROTEC 5, 7SJ82/7SJ85, Manual 331


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

[loauswer-230311-01.tif, 1, en_US]

Figure 5-122 Recommended Analysis of the Circuit-Breaker Switch Position

The following diagram shows the recommended routing, in which OH stands for active with voltage.

[scpolg3p-230311-01.tif, 1, en_US]

Figure 5-123 Routing for Acquisition of the Circuit-Breaker Switch Position via 2 Auxiliary Contacts

The device can also function without the analysis from the circuit-breaker auxiliary contacts, that is, routing of
the auxiliary contacts is not absolutely necessary. However, this is a requirement for the control functions.

Parameter: Output Time

• Default setting (_:101) Output time = 0.10 s


The Output time parameter acts on the signals for tripping, opening, and closing of the circuit breaker.

! CAUTION
Do not set a time that is too short.
If you set a time that is too short, there is a danger that the device contacts will interrupt the control
circuit. If this happens, the device contacts will burn out.
² Set a time that is long enough to ensure that the circuit breaker reliably reaches its final position
(open or closed) after a control operation.

Parameter: Indicat. of breaking values

• Default setting (_:105) Indicat. of breaking values = always


With the Indicat. of breaking values parameter, you define whether the measured values are to be
indicated if the circuit breaker is opened by way of the control function.
Parameter Value Description
always With this setting, the measured values are reported if the circuit breaker is
opened either via the control function or the trip command of a protection
function.
with trip With this setting, the measured values are only reported if the circuit
breaker is opened via the trip command of a protection function.

332 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

Measured Values
If a protection function trips the circuit breaker, the following measured values are stored in the fault log:

• Break.-current phs A
• Break.-current phs B
• Break.-current phs C
• Break. current 3I0/IN
• Break. voltage phs A
• Break. voltage phs B
• Break. voltage phs C
The measured value Break. current 3I0/IN is the neutral-point current. Depending on the connection
type of the measuring point I-3ph connected with the Circuit-breaker function group, the neutral-point
current is differentiated as follows:
Connection Type of the Meas- Neutral-Point Current
uring Point I-3ph
3-phase Calculated zero-sequence current 3I0
3-phase + IN Measured neutral-point current IN
3-phase + IN-separate If, for sensitive current transformers, the secondary ground current exceeds
3ph,2prim.CT + IN-sep the linear range of the sensitive measuring input (1.6 Irated), the neutral-
2ph, 2p. CT + IN-sep point current of IN measured is switched to 3I0 calculated.
2ph, 2p. CT + 2 IN-sep

Output Signal: Indication Suppression


Whereas in the case of feeders without an automatic reclosing function every trip command is final due to a
protection function, the use of an automatic reclosing function should only cause the motion detector of the
circuit breaker (fleeting contact on the circuit breaker) to trigger an alarm if tripping of the circuit breaker is
definitive (see next figure for more details). Likewise, a tripping alarm should not be triggered for switching
operations by the control.
For this, the alarm activation circuit can be looped via a suitably routed output contact of the device (output
signal Alarm suppression). In the idle state and when the device is switched off, this contact is perma-
nently closed. For this, an output contact with a break contact must be routed. The contact opens whenever
the output signal Alarm suppression becomes active, so that tripping or a switching operation does not
cause an alarm.
You can find further information in the logic in chapter 5.7.7.3 Acquisition of Circuit-Breaker Auxiliary
Contacts and Further Information.

[loschalt-081210-01.tif, 2, en_US]

Figure 5-124 Circuit-Breaker Tripping Alarm Suppression

SIPROTEC 5, 7SJ82/7SJ85, Manual 333


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

5.7.7.7 Settings

Addr. Parameter C Setting Options Default Setting


Circuit break.
_:101 Circuit break.:Output 0.02 s to 1800.00 s 0.10 s
time
_:105 Circuit break.:Indicat. of • with trip always
breaking values
• always

5.7.7.8 Information List

No. Information Data Class Type


(Type)
Circuit break.
_:500 Circuit break.:>Ready SPS I
_:501 Circuit break.:>Acquisition blocking SPS I
_:502 Circuit break.:>Reset switch statist. SPS I
_:504 Circuit break.:>Reset AcqBlk&Subst SPS I
_:503 Circuit break.:External health ENS I
_:53 Circuit break.:Health ENS O
_:58 Circuit break.:Position DPC C
_:300 Circuit break.:Trip/open cmd. SPS O
_:301 Circuit break.:Close command SPS O
_:302 Circuit break.:Command active SPS O
_:303 Circuit break.:Definitive trip SPS O
_:304 Circuit break.:Alarm suppression SPS O
_:306 Circuit break.:Op.ct. INS O
_:307 Circuit break.:ΣI Brk. BCR O
_:308 Circuit break.:ΣIA Brk. BCR O
_:309 Circuit break.:ΣIB Brk. BCR O
_:310 Circuit break.:ΣIC Brk. BCR O
_:311 Circuit break.:Break.-current phs A MV O
_:312 Circuit break.:Break.-current phs B MV O
_:313 Circuit break.:Break.-current phs C MV O
_:317 Circuit break.:Break. current 3I0/IN MV O
_:314 Circuit break.:Break. voltage phs A MV O
_:315 Circuit break.:Break. voltage phs B MV O
_:316 Circuit break.:Break. voltage phs C MV O
_:322 Circuit break.:CB open hours INS O
_:323 Circuit break.:Operating hours INS O

5.7.8 Circuit-Breaker Position Recognition for Protection-Related Auxiliary


Functions

5.7.8.1 Overview
This function block calculates the position of the circuit breaker from the evaluation of the auxiliary contacts
and the current flow.

334 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

This information is needed in the following protection-related additional functions:

• Trip logic (see 5.7.6.1 Function Description)

• Detection of manual closing (see 5.7.9.1 Function Description)

• Process monitor (Standard V/I) 5.8 Process Monitor)


The specified chapters describe the way the protection-related additional functions are processing the infor-
mation of this function block.
The control does not use this information. The control evaluates the circuit-breaker auxiliary contacts.

[lozust3p-070611-01.tif, 1, en_US]

Figure 5-125 Overview of the Circuit-Breaker Condition Position Function

Based on the link between the information from the auxiliary contacts and the current flow, shown in
Figure 5-125, the circuit breaker can assume the following positions. The following table shows the possible
circuit-breaker conditions:
Circuit-Breaker Condition Description
Open The circuit-breaker pole is detected unambiguously as open according to
both criteria.
Closed The circuit-breaker pole is detected unambiguously as closed according to
both criteria.
Possibly open, possibly These conditions can occur if the information is incomplete due to the
closed routing of the auxiliary contacts and the condition can no longer be deter-
mined reliably. These uncertain conditions are evaluated differently
by certain functions.
Opening This is a dynamically occurring condition that results when, while a trip
command is active and the auxiliary contact is still closed, the current is
detected to have fallen below the threshold value. The reason for that is
that the current-flow criterion takes effect faster than the auxiliary contact
can open.

5.7.9 Detection Manual Closure (for AREC and Process Monitor)

5.7.9.1 Function Description

Detection of Manual Closure (for AREC and Process Monitor)


The Manual closure function block detects any closure carried out by hand. This information is used in func-
tion, the automatic reclosing (AREC) and Process monitor functions (within protection function groups).
You can find detailed information in the chapters Automatic reclosing function and Process monitor.
The following figure shows the logic for manual closure detection.

SIPROTEC 5, 7SJ82/7SJ85, Manual 335


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

[lohand3p-101210-01.tif, 3, en_US]

Figure 5-126 Logic for Manual Closure Detection

External Manual Closure


An external manual closure is communicated to the device via the input signal >Input. The input signal can
also be connected directly to the control circuit of the circuit-breaker closing coil. For this reason, detection is
suppressed in the event of a close command by the AREC function. Detection via the input signal >Input is
also blocked if the circuit breaker is closed or if a protection trip is active.

Internal Manual Closure


Manual closure is detected in all cases if a close command is transmitted by the internal control function of
the device. This is possible because the control carries out plausibility checks itself and is also subject to inter-
locking.

5.7.9.2 Application and Setting Notes

Input Signals: >Input, >Blocking of Manual Closure


In practice, the input signal >Input is connected directly to the control circuit of the circuit-breaker closing
coil (see following figure).

[losteuer-150113-01.tif, 1, en_US]

Figure 5-127 Connection of the Input Signal to the Control Circuit of the Circuit-Breaker Closing Coil

Every closure of the circuit breaker is recorded in the process. Therefore, detection is suppressed in the event
of a close command by the internal AREC function of the device.

336 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.7 Function-Group Type Circuit Breaker

If external close commands are possible (actuation of the circuit breaker by other devices), which are not
intended to prompt detection of a manual closure (for example, with an external reclosing device), this can be
ensured in 2 ways:

• The input signal is connected in such a way that it is not activated in the event of external close
commands.

• The external close command is connected to the blocking input >Block manual close for manual
closure detection.

Parameter: Action time

• Recommended setting value (_:101) Action time = 300 ms


In order to ensure independence from manual activation of the input signal, the detection function is
extended for a defined length of time using the parameter Action time.
Siemens recommends an action time of 300 ms.

Parameter: CB open dropout delay

• Default setting (_:102) CB open dropout delay = 0 ms


With the CB open dropout delay parameter, you can maintain the effectiveness of internal indication CB
open-circuited for the set time. If the input signal >Input becomes active after external delayed manual
closure, the indication (_:300) Detected is output as long as the dropout delay is active.

5.7.9.3 Settings

Addr. Parameter C Setting Options Default Setting


Manual close
_:101 Manual close:Action time 0.01 s to 60.00 s 0.30 s

5.7.9.4 Information List

No. Information Data Class Type


(Type)
Manual close
_:501 Manual close:>Block manual close SPS I
_:500 Manual close:>Input SPS I
_:300 Manual close:Detected SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 337


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.8 Process Monitor

5.8 Process Monitor

5.8.1 Overview of Functions

All function groups that have functions with dependencies on the state of the protected object contain a
process monitor. The process monitor detects the current state of the protected object.

5.8.2 Structure of the Function

The Process monitor function is used in the Standard V/I 3-phase protection function group.
The Process monitor function is provided by the manufacturer with the following function blocks:

• Cold-load pickup detection (optional)

• Current-flow criterion

• Circuit-breaker condition

• Closure detection

[dwpro3pt-061212-01.tif, 2, en_US]

Figure 5-128 Structure/Embedding of the Function

You can activate the cold-load pickup detection as needed. All other stages of the process monitor run perma-
nently in the background and are not displayed in DIGSI.
The following figure shows the relationships of the individual function blocks.

338 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.8 Process Monitor

[lopro3pt-171012-01.tif, 2, en_US]

Figure 5-129 Logic Diagram of the Overall Function Process Monitor

5.8.3 Current-Flow Criterion

[loproikr-011112-01.tif, 2, en_US]

Figure 5-130 Logic Diagram of the Current-Flow Criterion Function Block

The phase currents are provided via the interface to the protection function group.
The I open signal of one phase is generated if one of the following conditions is met:

• A phase current falls below the set threshold of the Current thresh. CB open parameter. The
hysteresis stabilizes the signal.

• The corresponding phase current, for example, I A, falls below 10 % of the phase current when the trip
command arrives. If the current does not drop until after a delay due to current transformer influences,
an open pole can therefore be detected quickly even after a high-current fault on the line.

SIPROTEC 5, 7SJ82/7SJ85, Manual 339


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.8 Process Monitor

With the Current thresh. CB open parameter, you define the minimum current as the criterion for a
deactivated line. The parameter lies in the Circuit-breaker function group. It acts both in the Circuit-breaker
function group, for example circuit-breaker position recognition, and also for the process monitor in the
protection function group.
If a protection function group with integrated process monitor is connected to several FG circuit-breakers, the
Current thresh. CB open parameter is present in each FG circuit-breaker. The smallest setting value of
the parameter Current thresh. CB open is used.

5.8.4 Application and Setting Notes (Current-Flow Criterion)

Parameter: Current thresh. CB open

• Recommended setting value (_:2311:112) Current thresh. CB open = 0.100 A


The Current thresh. CB open parameter is used to define the threshold for the leakage current as the
criterion for a deactivated line.
Set the Current thresh. CB open parameter so that the current measured when the feeder is deacti-
vated falls below the value of the Current thresh. CB open parameter with certainty. The hysteresis is
additionally active if the threshold is exceeded.
If parasitic currents, for example, due to induction, are ruled out when the feeder is deactivated, set the
Current thresh. CB open parameter sensitively.
Siemens recommends a setting value of 0.100 A.

5.8.5 Circuit-Breaker Condition for the Protected Object

Logic

[loprolsz-140611-01.tif, 2, en_US]

Figure 5-131 Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

The circuit-breaker position recognition in the Circuit-breaker (CB) function group provides the circuit-breaker
condition by way of the internal signal CB pos. recogn. prot. obj..
If a protected object is supplied via 2 circuit breakers (CBs), for example with the 1 1/2 circuit-breaker layout,
then the circuit-breaker switch position of the protected object must be determined with the aid of both circuit
breakers. In this case, the Circuit-breaker position recognition for the protected object function block
connects the individual CB states. The connection provides the internal CB pos. recogn. prot. obj.
signal to the other function blocks of the process monitor and to other functions, for example, Trip in the
event of weak infeed and Echo function for teleprotection method, within the same function group.
If one of the following 2 conditions is met, the CB pos. recogn. prot. obj. signal is in the Open state:

• All connected circuit breakers signal the Open state internally.

• The >Disconnector open input is active.

340 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.8 Process Monitor

If the following 2 conditions are met, the CB pos. recogn. prot. obj. signal is in the Closed state:

• At least one of the connected circuit breakers signals the Closed state internally.

• The >Disconnector open input is not active.

5.8.6 Closure Detection

The closure detection enables the immediate tripping of selected protection functions or protection stages
when switching to short circuit or the reduction of the responsivity. The closure detection determines whether
the protected object is switched on.

Logic

[loein6md-171012-01.tif, 1, en_US]

Figure 5-132 Logic Diagram of Closure Detection

For an applied binary input signal Detected (from Manual close function block), the indication Closure is
active.

5.8.7 Information List

No. Information Data Class Type


(Type)
Closure detec.
_:4681:500 Closure detec.:>Disconnector open SPS I
_:4681:300 Closure detec.:Closure SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 341


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.8 Process Monitor

5.8.8 Cold-Load Pickup Detection (Optional)

Logic

[loprocls-180912-01.tif, 1, en_US]

Figure 5-133 Logic Diagram of the Cold-Load Pickup Detection Function Block

The Cold-load pickup detection function block detects that a specific time has been exceeded after deactiva-
tion of the line or protected object. If you want to connect the protected object again, you must note that an
increased load-current requirement exists for a limited time after connection. This results from the nature of
the load.
The Cold-load pickup detection function block ensures that different parameters are used for an adjustable
time after connection. For example, for the time of the Min. CB-open time parameter, you can increase
the threshold value of a protection function or you can select a special characteristic curve.
If the Cold-load pickup detection function block detects an open feeder and the set time of the Min. CB-
open time parameter has expired, the indication >Activate cold-load is generated.
With the >Activate cold-load indication, you can activate a parameter set of the Cold-load pickup func-
tion. Via the binary input signal >Activate cold-load, you can also activate the >Activate cold-load
indication directly.
If the Cold-load pickup detection function block detects closure and the corresponding load current, it starts
the time set in the Dropout delay CB closed parameter. The >Activate cold-load indication and
the activated parameter set are deactivated after this time has elapsed.

342 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.8 Process Monitor

If, for the time set in the Dropout delay curr.crit. parameter, the maximum phase current falls below
the threshold value Dropout threshold current, the parameter set for the Cold-load pickup detection
function block is also deactivated. As a result, if the load current is very low, the action time Dropout delay
curr.crit. of the >Activate cold-load indication can be shortened.

5.8.9 Application and Setting Notes (Cold-Load Pickup Detection)

NOTE

i The settings and indications described in this chapter are only available when using the optional Cold-load
pickup detection function block.

Parameter: Operating mode

• Default setting (_:101) Operating mode = I open


With the Operating mode parameter, you set the criteria with which the Closure-detection function block
operates.
Parameter Value Description
I open When the Current-flow criterion function block detects a clearing open
condition, the decision is made for pickup. For this setting, make sure that
the Current thresh. CB open parameter is set lower than the
possible load current. If this is not the case, open is detected continuously
and each fault current that exceeds the Current thresh. CB open
parameter is interpreted as closure.
CB and I open Closure is detected if one of the following conditions is met:

• Analysis of the circuit-breaker auxiliary contact detects a clearing open


condition in at least one phase.
• The current-flow criterion detects a clearing open condition.

Parameter: Dropout threshold current

• Default setting (_:102) Dropout threshold current = 1.00 A


With the Dropout threshold current parameter, you set the threshold at which the output signal
Cold-load pickup is deactivated when the current in at least one phase falls below this threshold.

Parameter: Dropout delay current criterion

• Default setting (_:103) Dropout delay curr.crit. = 600 s


With the Dropout delay curr.crit. parameter, you set the time for which the actual value must be
below the Dropout threshold current threshold so that the output signal Cold-load pickup can be
deactivated prematurely.

Parameter: Dropout delay CB closed

• Default setting (_:104) Dropout delay CB closed = 3600 s


With the Dropout delay CB closed parameter, you set the action time for the dynamic parameter set
switching in the event of cold-load pickup detection.

Parameter: Min. CB open time

• Default setting (_:105) Min. CB-open time = 3600 s


With the Min. CB-open time parameter, you set the time after which the dynamic parameter set is acti-
vated in the event of cold-load pickup when the line is opened.

SIPROTEC 5, 7SJ82/7SJ85, Manual 343


C53000-G5040-C017-A, Edition 06.2019
Function-Group Types
5.8 Process Monitor

5.8.10 Settings

Addr. Parameter C Setting Options Default Setting


Cold-load PU
_:1 Cold-load PU:Mode • off off
• on
• test
_:101 Cold-load PU:Operating • I open I open
mode
• CB and I open
_:102 Cold-load PU:Dropout 1 A @ 100 Irated 0.030 A to 10.000 A 1.000 A
threshold current 5 A @ 100 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:103 Cold-load PU:Dropout 1 s to 600 s 600 s
delay curr.crit.
_:104 Cold-load PU:Dropout 1 s to 21600 s 3600 s
delay CB closed
_:105 Cold-load PU:Min. CB- 0 s to 21600 s 3600 s
open time

5.8.11 Information List

No. Information Data Class Type


(Type)
Cold-load PU
_:81 Cold-load PU:>Block stage SPS I
_:500 Cold-load PU:>Block fast dropout SPS I
_:501 Cold-load PU:>Activate cold-load SPS I
_:54 Cold-load PU:Inactive SPS O
_:52 Cold-load PU:Behavior ENS O
_:53 Cold-load PU:Health ENS O
_:300 Cold-load PU:Cold-load pickup SPS O

344 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
6 Protection and Automation Functions

6.1 Power-System Data 347


6.2 Group Indications of Overcurrent Protection Functions 369
6.3 Overcurrent Protection, Phases 370
6.4 Voltage-Dependent Overcurrent Protection, Phases 408
6.5 Overcurrent Protection, Ground 427
6.6 Directional Overcurrent Protection, Phases 458
6.7 Directional Overcurrent Protection, Ground 491
6.8 Inrush-Current Detection 537
6.9 Instantaneous High-Current Tripping 544
6.10 Arc Protection 551
6.11 Instantaneous Tripping at Switch onto Fault 570
6.12 Overcurrent Protection, 1-Phase 573
6.13 Positive-Sequence Overcurrent Protection 598
6.14 Non-Directional Intermittent Ground-Fault Protection 608
6.15 Directional Intermittent Ground-Fault Protection 616
6.16 Sensitive Ground-Fault Detection 627
6.17 Undercurrent Protection 703
6.18 Negative-Sequence Protection 708
6.19 Directional Negative-Sequence Protection 717
6.20 Thermal Overload Protection, 3-Phase - Advanced 727
6.21 Thermal Overload Protection, User-Defined Characteristic Curve 741
6.22 Thermal Overload Protection, 1-Phase 752
6.23 Unbalanced-Load Protection 762
6.24 Overvoltage Protection with 3-Phase Voltage 768
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage 780
6.26 Overvoltage Protection with Positive-Sequence Voltage 787
6.27 Overvoltage Protection with Negative-Sequence Voltage 791
6.28 Overvoltage Protection with Any Voltage 798
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage 804
6.30 Undervoltage Protection with 3-Phase Voltage 811
6.31 Undervoltage Protection with Positive-Sequence Voltage 829
6.32 Undervoltage Protection with Any Voltage 836
6.33 Overfrequency Protection 842
6.34 Underfrequency Protection 847

SIPROTEC 5, 7SJ82/7SJ85, Manual 345


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions

6.35 Underfrequency Load Shedding 853


6.36 Rate of Frequency Change Protection 865
6.37 Vector-Jump Protection 871
6.38 Power Protection (P,Q), 3-Phase 879
6.39 Reverse-Power Protection 889
6.40 Overexcitation Protection 897
6.41 Undervoltage-Controlled Reactive-Power Protection 907
6.42 Circuit-Breaker Failure Protection 916
6.43 Circuit-Breaker Restrike Protection 934
6.44 Restricted Ground-Fault Protection 943
6.45 External Trip Initiation 3-Pole 961
6.46 Automatic Reclosing Function 964
6.47 Fault Locator 1014
6.48 Fault Locator Plus 1027
6.49 Temperature Supervision 1040
6.50 Phase-Sequence Switchover 1050
6.51 Current-Jump Detection 1056
6.52 Voltage-Jump Detection 1059
6.53 Voltage Measuring-Point Selection 1062

346 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

6.1 Power-System Data

6.1.1 Overview

The Power-system data are provided with each SIPROTEC 5 device and cannot be deleted. You will find them
in DIGSI under Settings → Power-system data.

6.1.2 Structure of the Power-System Data

The Power-system data contain the block General and the Measuring points of the device. The following
figure shows the structure of the Power-system data:

[dwandata-180912-01.tif, 2, en_US]

Figure 6-1 Structure of the Power-System Data

In order to adjust its functions to the application, the device requires some data about the power system. The
necessary settings can be found in the Power-system data under General as well as in the Measuring points.

NOTE

i You can find information on the supervision-function parameters in chapter 9.3 Supervision of the Secon-
dary System.

Type and scope of the required measuring points depend on the application. Possible measuring points are:

• Voltage 3-phase (measuring point V 3-ph)

• Current 3-phase (measuring point I 3-ph)

• Voltage 1-phase (measuring point V 1-ph)

• Current 1-phase (measuring point I 1-ph)


The measuring points have interfaces to the function groups requiring voltage and/or current measured values
of the power system.

6.1.3 Application and Setting Notes – General Settings

Parameter: Phase sequence

• Recommended setting value (_:2311:101) Phase sequence= ABC


The parameter Phase sequence is used to set the phase sequence (ABC) or (ACB). The setting value applies
to the entire SIPROTEC 5 device.
Use the General function to set the settings in the power-system data.
You can find detailed information about phase-rotation reversal in chapter 6.50.1 Overview of Functions.

SIPROTEC 5, 7SJ82/7SJ85, Manual 347


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

6.1.4 Application and Setting Notes for Measuring-Point Current 3‑Phase (I 3-ph)

The supervision function settings are also located in the current measuring point. You can find the description
of these parameters in chapter 9 Supervision Functions.

Parameter: CT connection

• Default setting (_:8881:115) CT connection = 3-phase + IN-separate


The parameter CT connection shows the connection type of the current transformer for the 3‑phase
current measuring point. The parameter can be found in the DIGSI 5 project tree under Name of the device
→ Settings → Power system → Measuring point I 3-phase. You cannot change the connection type of the
current transformer in the Power system.
You can change the connection type of the current transformer only under measuring point routing in DIGSI 5.
Under Name of the device → Measuring point routing → Current measuring points, select the desired
connection type under Connection type. The following types of connections are possible:

• 3-phase + IN-separate

• 3-phase + IN

• 3-phase

• 3-phase, 2 primary CT

• 3ph,2prim.CT + IN-sep

• 2ph, 2p. CT + IN-sep

• 2ph, 2p. CT + 2 IN-sep

NOTE

i The following connection types are not allowed in the Capacitor bank function group:

• 3-phase, 2 primary CT

• 3ph,2prim.CT + IN-sep

• 2ph, 2p. CT + IN-sep

• 2ph, 2p. CT + 2 IN-sep

Depending on the connection type selected, you must route the measured values to the terminals of the
current measuring point in DIGSI 5. You can find connection examples for current transformers in chapter
A.7 Connection Examples for Current Transformers. The connection examples provide assistance when
selecting the type of connection.

Parameter: CT connection = 2ph, 2p. CT + 2 IN-sep


The ground current is measured both by way of an input of normal sensitivity (I2) and a sensitive input (I4)
with the connection type 2ph, 2p. CT + 2 IN-sep. The phase current IB is calculated via the ground
current IN2 measured with normal sensitivity.
The calculated phase current IB is not displayed in SIGRA. If you wish to display the current IB in SIGRA, you
must define the equation for calculating IB in SIGRA using the menu item Insert → Insert calculated signal.
Calculate IB in SIGRA using one of these 2 equations:

• IB = - IA - IC - IN2 or

• IB = - IC - IA - IN2

The currents in the equations are primary values.

348 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

NOTE

i • This connection type is possible only in the Voltage/current 3-phase and Circuit-breaker function
groups.

• This connection type is possible only with current terminals of the type Current, 3x protec-
tion, 1x sensitive and the following routing in the Measuring point I-3-ph:

[sc_ENEL_MP_route, 1, en_US]

As long as IN2 and INare connected to the same core balance current transformer, the parameters
Rated primary current and Rated secondary current of CT IN are also valid for the CT
IN2. You can find the parameter in the DIGSI 5 project tree under Name of the device → Settings →
Power system → Measuring point I-3-phase. You can find more information on this in chapter
6.1.4 Application and Setting Notes for Measuring-Point Current 3‑Phase (I 3-ph).
IN is used as the measured ground current for ground-fault protection functions.

Parameter: Tracking

• Default setting (_:8881:127) Tracking = active


With the parameter Tracking, you specify whether you would like to work with the sampling-frequency
tracking function.
Parameter Value Description
active If the parameter Tracking = active has been set, the measuring point
will be included when determining the sampling frequency. If possible, only
the 3-phase measuring points shall be considered.
Siemens recommends using the default setting.
Note: If the parameter Tracking = active, the determined sampling
frequency applies to all functions in the device not using fixed sampling
rates.
With platform version V07.80 and higher, you can merge measuring points
into Frequency tracking groups in SIPROTEC 5 devices. In this case, every
frequency tracking group specifies its own sampling frequency. You can
find more information on this in chapter 3.3 Sampling-Frequency Tracking
and Frequency Tracking Groups.
inactive If the channels of the measuring point are not to be considered for deter-
mining the sampling frequency, select the setting value inactive.

Parameter: Measuring-point ID

• Default setting (_:8881:130) Measuring-point ID = 1


The parameter Measuring-point ID is write-protected and displays the ID of the measuring point. If you
are using several measuring points, the Measuring-point ID is continuously incremented.
With platform version V07.80 and higher, you can merge measuring points into Frequency tracking groups
in SIPROTEC 5 devices. In this case, every frequency tracking group specifies its own sampling frequency. You

SIPROTEC 5, 7SJ82/7SJ85, Manual 349


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

can find more information on this in chapter 3.3 Sampling-Frequency Tracking and Frequency Tracking
Groups.

Parameter: Rated primary current

• Default setting (_:8881:101) Rated primary current = 1000 A


With the Rated primary current parameter, you set the active rated primary current of the current trans-
former

Parameter: Rated secondary current

• Default setting (_:8881:102) Rated secondary current = 1 A


With the Rated secondary current parameter, you set the active rated secondary current of the current
transformer.

Parameter: Current range

• Default setting 7SJ82 (_:8881:117) Current range = 50 x IR

• Default setting 7SJ85 (_:8881:117) Current range = 100 x IR


The Current range parameter allows you to set the dynamic range for the current input. Retain the default
setting for power-system protection applications. The current measuring range 1.6 x Irated applies for the
connection type 3-phase + IN-separate and the sensitive current input or for the measuring inputs.

Parameter: Neutr.point in dir.of ref.obj

• Default setting (_:8881:116) Neutr.point in dir.of ref.obj = yes


The Neutr.point in dir.of ref.obj parameter is used to set the direction of the neutral point of the
current transformer (see following figure). Often, the neutral point of the current transformer is determined
by the direction of the protected object (for example, in the direction of the line, cable, transformer). For this
reason, the default setting of the parameter was defined as yes.
When switching the parameter, the direction of the phase currents and of the ground current IN or IN-sepa-
rate is rotated device-internally.

[dwpolstromwdl-251013, 1, en_US]

Figure 6-2 Polarity of Current Transformers

Parameter: Inverted phases

• Default setting (_:8881:114) Inverted phases = none

350 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

The Inverted phases parameter is intended for special applications, for example, pumped-storage hydro-
power plants (see Chapter Phase-rotation reversal). This default setting may be retained for power-system
protection applications.

Parameter: Magnitude correction

• Default setting (_:3841:103) Magnitude correction = 1.000


When using the Magnitude correction parameter, you set the magnitude (magnitude correction) for the
current input. This allows you to correct the tolerances of the primary current transformer phase-selectively.
The magnitude correction may be required for highly precise measurements. Use a comparison measurement
to determine the setting value (for example, with a high-precision measuring-voltage transformer). If a
primary correction is not necessary, retain the default setting.

NOTE

i The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.

Note Regarding Routable Data


You can find indications for the current rotating field and the information pertaining to the sampling-
frequency tracking in Information routing under Power system → General in DIGSI 5. The indication
Freq.out of oper.range means that the frequency operating range has been exceeded. Either the
frequency is out of range (10 Hz to 90 Hz) or the input signals are too small for a manual update. Should this
state occur, the system switches the update frequency to a sampling rate that corresponds to the rated
frequency.
Furthermore, there are 2 additional measured frequency values available. The measured value f sys displays
the current system frequency, and the measured value f track displays the sampling frequency currently
set. Siemens recommends routing both measured values as fault-recording channel.

6.1.5 Application and Setting Notes for Measuring-Point Current 1-Phase (I-1ph)

If you insert a Measuring point I 1-ph in DIGSI 5, you must route a current to the measuring point under
Name of the device → Measuring-point routing → Current measuring points.
You can only route the current Ix.

Parameter: Rated primary current

• Default setting (_:2311:101) Rated primary current = 1000 A


With the Rated primary current parameter, you set the active primary rated current of the current trans-
former.

Parameter: Rated secondary current

• Default setting (_:2311:102) Rated secondary current = 1 A


With the Rated secondary current parameter, you set the active secondary rated current of the current
transformer.

Parameter: Current range

• Default setting (_:2311:103) Current range = 50 x IR


The Current range parameter allows you to set the dynamic range for the current input. Retain the default
setting for power-system protection applications.

SIPROTEC 5, 7SJ82/7SJ85, Manual 351


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Parameter: Term. 1,3,5,7 in dir. of obj.

• Default setting (_:2311:116) Term. 1,3,5,7 in dir. of obj. = yes


With the Term. 1,3,5,7 in dir. of obj. parameter, you define the direction of the current. If you set
the parameter Term. 1,3,5,7 in dir. of obj. = yes, the direction of the current to the protected
object is defined as forward.

Parameter: Magnitude correction

• Default setting (_:3841:103) Magnitude correction = 1.000


When using the Magnitude correction parameter, you set the magnitude (magnitude correction) for the
current input. This allows you to correct the tolerances of the primary current transformer phase-selectively.
The magnitude correction may be required for highly precise measurements. Use a comparison measurement
to determine the setting value (for example, a high-precision measuring-voltage transformer). If a primary
correction is not necessary, retain the default setting.

NOTE

i The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.

Parameter: Tracking

• Default setting (_:2311:105) Tracking = active


With the parameter Tracking, you specify whether you would like to work with the sampling-frequency
tracking function.
Parameter Value Description
active If the parameter Tracking = active has been set, the measuring point
will be included when determining the sampling frequency.
Note: If the parameter Tracking = active, the determined sampling
frequency applies to all functions in the device not using fixed sampling
rates.
With platform version V07.80 and higher, you can merge measuring points
into Frequency tracking groups in SIPROTEC 5 devices. In this case, every
frequency tracking group specifies its own sampling frequency. You can
find more information on this in chapter 3.3 Sampling-Frequency Tracking
and Frequency Tracking Groups.
inactive If the channels of the measuring point are not to be considered for deter-
mining the sampling frequency, select the setting value inactive.

Parameter: Measuring-point ID

• Default setting (_:2311:130) Measuring-point ID = 1


The parameter Measuring-point ID is write-protected and displays the ID of the measuring point. If you
are using several measuring points, the Measuring-point ID is continuously incremented.
With platform version V07.80 and higher, you can merge measuring points into Frequency tracking groups
in SIPROTEC 5 devices. In this case, every frequency tracking group specifies its own sampling frequency. You
can find more information on this in chapter 3.3 Sampling-Frequency Tracking and Frequency Tracking
Groups.

6.1.6 Application and Setting Notes for Measuring Point Voltage 3‑Phase (V-3ph)

Settings for the supervision functions are also located in the voltage measuring point. You can find the
description of these settings in chapter Supervision Functions.

352 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Parameter: Rated primary voltage

• Default setting (_:8911:101) Rated primary voltage = 400.000 kV


The Rated primary voltage parameter is used to set the primary rated voltage of the voltage trans-
former.

Parameter: Rated secondary voltage

• Default setting (_:8911:102) Rated secondary voltage = 100 V


The Rated secondary voltage parameter is used to set the secondary rated voltage of the voltage trans-
former.

Parameter: Matching ratio Vph / VN

• Default setting (_:8911:103) Matching ratio Vph / VN = 1.73


With the parameter Matching ratio Vph / VN, you set the deviation between the calculated zero-
sequence voltage and the residual voltage measured directly via a measuring input. The different transmission
ratio of the voltage transformers is the cause for the deviation (see Figure 6-3).
The Matching ratio Vph / VN is equal to the ratio 3V0 sec/VN sec
with
V0 sec Calculated zero-sequence voltage
VN sec Measured residual voltage

The zero-sequence voltage is calculated as phase-to-ground voltages. The residual voltage is measured on the
broken-delta winding of the voltage transformer. For 1-phase voltage transformers, the residual voltage is
measured in the generator or the transformer neutral point.

NOTE

i The measurement residual voltage VN sec is converted to a zero-sequence voltage in the device as follows:

SIPROTEC 5, 7SJ82/7SJ85, Manual 353


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

EXAMPLE 1:

[dw_bsp1uwdl_anpassfaktor, 2, en_US]

Figure 6-3 3-Phase Voltage Transformer: Connection = 3 Phase-to-Ground Voltage + VN

When the type of connection for the voltage transformer is 3 ph-to-gnd volt. + VN (parameter: VT
connection) and the voltage input V4 is connected to the broken-delta winding of the voltage transformer
(da/dn), the Matching ratio Vph / VN is as follows:
When changing the neutral point according to Figure 6-3, this results in the following values:

• The calculated secondary zero-sequence voltage V0 sec is equal to the secondary phase-to-ground voltage.
Expressed as secondary transformer rated voltage, then Vrated sec/√3.

• The measured residual voltage on the broken-delta winding is the sum of the voltage drops on the
3 sides. Expressed with the side ratio, the result is VN, sec = 3 Vrated sec /3.

Calculate the Matching ratio Vph / VN parameter as follows:

[fo_bsp1, 2, en_US]

Set Matching ratio Vph / VN = 1.73.

In example 1 Vrated sec, the phase-to-ground voltage and the secondary voltage on the broken-delta winding
were identical. If these voltages are different, use the actual numerical values in the calculation.

EXAMPLE 2:

Phase-to-ground voltage Vrated sec = 100 V


Broken-delta winding (for Vrated sec = 500 V
example, grounding trans- The voltage input of the device is designed for a continuous operation,
former in generator protection) using 230 V max. Therefore, the voltage on the broken-delta winding
(500 V) is reduced to a 5:2 ratio, using an ohmic divider. In order to calcu-
late the matching factor, the secondary voltage of 200 V will be applied.

Calculate the Matching ratio Vph / VN parameter as follows:

354 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

[fo_bsp2, 1, en_US]

Set Matching ratio Vph / VN = 0.866.


Interpretation of the result:
The zero-sequence voltage calculated from the phase-to-ground voltage is 57.73 V (= 100V/√3). The meas-
ured residual voltage is 200 V. The calculated adaptation factor is 0.866. The measured residual voltage is
converted to a zero-sequence voltage inside the device:

[fo_umrechnung2, 2, en_US]

NOTE

i During the ground-fault test, the set adaptation factor can be checked by comparing the operational meas-
ured values. The operational measured values contain the calculated zero-sequence voltage V0 sec and the
measured residual voltage VN sec. Proceed with the compilation as follows:

The Matching ratio Vph / VN parameter is significant for the following functions:

• Overvoltage protection with zero-sequence voltage/residual voltage

• Measured-value supervision

• Scaling of the faulty and measured values

Parameter: VT connection

• Default setting (_:8911:104) VT connection = 3 ph-to-gnd volt. + VN


The parameter VT connection shows the connection type of the voltage transformer for the 3-phase
voltage measuring point. You can find the parameter in the DIGSI 5 project tree under Name of the device →
Settings → Power-system data → Measuring point V 3-phase. You cannot change the connection type of
the voltage transformer in the power-system data.
You can change the connection type of the voltage transformer only under measuring point routing in
DIGSI 5. Under Name of the device → Measuring-points routing → Voltage measuring points, select the
desired connection type under Connection type. The following types of connections are possible:

• 3 ph-to-gnd volt. + VN

• 3 ph-to-gnd voltages

• 3 ph-to-ph volt. + VN

• 3 ph-to-ph voltages

• 2 ph-to-ph volt. + VN

• 2 ph-to-ph voltages

• 2 ph-to-gnd volt. + VN

• 2 ph-to-gnd voltages
Depending on the connection type selected, you must route the measured values to the terminals of the
voltage measuring point in DIGSI 5. You can find connection examples for voltage transformers in the chapters
A.9 Connection Examples of Voltage Transformers for Non-Modular Devices and A.8 Connection Examples of

SIPROTEC 5, 7SJ82/7SJ85, Manual 355


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Voltage Transformers for Modular Devices. The connection examples provide assistance when selecting the
type of connection.

Parameter: Inverted phases

• Default setting (_:8911:106) Inverted phases = none


The Inverted phases parameter is intended for special applications, for example pumped-storage hydro-
power plants (see chapter 6.50 Phase-Sequence Switchover). This default setting can be retained for power-
system protection applications.

Parameter: Tracking

• Default setting (_:8911:111) Tracking = active


The Tracking parameter is used to determine whether the measuring channels of this measuring point shall
be used to determine the sampling frequency.
The sampling frequency of the device is adjusted to the power frequency. The device selects a measuring
channel, through which the sampling frequency is determined. Preferably, this should be a voltage metering
channel. This validity of the signal is monitored (minimum level, frequency range). If these values are invalid,
the device switches to another channel (etc.). Once switched to a current channel, the system automatically
switches back to the voltage channel if a voltage channel is valid again.
Parameter Value Description
active If you set the parameter Tracking = active, the measuring point will be
included when determining the sampling frequency. If possible, only the
3‑phase measuring points shall be considered.
Siemens recommends using the default setting.
Note: If the parameter Tracking is active, the determined sampling
frequency applies to all functions in the device not using fixed sampling
rates.
With platform version V07.80 and higher, you can merge measuring points
into Frequency tracking groups in SIPROTEC 5 devices. In this case, every
frequency tracking group specifies its own sampling frequency. You can
find more information on this in chapter 3.3 Sampling-Frequency Tracking
and Frequency Tracking Groups.
inactive If the channels of the measuring point are not to be considered for deter-
mining the sampling frequency, select the setting value inactive.

Parameter: Measuring-point ID

• Default setting (_:8911:130) Measuring-point ID = 1


The parameter Measuring-point ID is write-protected and displays the ID of the measuring point. If you
are using several measuring points, the Measuring-point ID is continuously incremented.
With platform version V07.80 and higher, you can merge measuring points into Frequency tracking groups
in SIPROTEC 5 devices. In this case, every frequency tracking group specifies its own sampling frequency. You
can find more information on this in chapter 3.3 Sampling-Frequency Tracking and Frequency Tracking
Groups.

Parameter: Magnitude correction

• Default setting (_:3811:103) Magnitude correction = 1.000


When using the Magnitude correction parameter, the magnitude (magnitude correction) is adjusted for
the voltage input. This allows you to correct the tolerances of the primary current transformer phase-selec-
tively. The magnitude correction may be required for highly precise measurements. Use a comparison meas-
urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.

356 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

NOTE

i The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.

6.1.7 Application and Setting Notes for Measuring Point Voltage 1-Phase (V-1ph)

If you insert a Measuring point V 1-ph in DIGSI 5, you must route a voltage to the measuring point under
Name of the device → Measuring-points routing → Voltage measuring points.
You can route the following voltages:

• V A

• V B

• V C

• V AB

• V BC

• V CA

• VN14

• Vx

• VN broken-delta15

Parameter: Rated primary voltage

• Default setting (_:2311:101) Rated primary voltage = 400.000 kV


The Rated primary voltage parameter is used to set the primary rated voltage of the voltage trans-
former.

Parameter: Rated secondary voltage

• Default setting (_:2311:102) Rated secondary voltage = 100 V


The Rated secondary voltage parameter is used to set the secondary rated voltage of the voltage trans-
former.

Parameter: Matching ratio Vph / VN

• Default setting (_:2311:108) Matching ratio Vph / VN = 1.73


With the parameter Matching ratio Vph / VN you set the deviation between the calculated zero-
sequence voltage and the residual voltage measured directly via a measuring input.
You can find more detailed information in chapter 6.1.6 Application and Setting Notes for Measuring Point
Voltage 3‑Phase (V-3ph).

NOTE

i The Matching ratio Vph / VN parameter is only visible in the Measuring point V 1‑ph if the voltage
VN broken-delta has been routed.

14 If you route this voltage, the protection functions operate with the neutral-point displacement voltage.
15 If you route this voltage, the protection functions operate with the voltage measured directly at the broken-delta winding of the
voltage transformer.

SIPROTEC 5, 7SJ82/7SJ85, Manual 357


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Parameter: Tracking

• Default setting (_:2311:103) Tracking = inactive


The Tracking parameter is used to determine whether the measuring channels of this measuring point shall
be used to determine the sampling frequency.
The sampling frequency of the device is adjusted to the power frequency. The device selects a measuring
channel, through which the sampling frequency is determined. Preferably, this should be a voltage metering
channel. The validity of this signal is monitored (minimum level, frequency range). If these values are invalid,
the device switches to another channel (etc.). Once switched to a current channel, the system automatically
switches back to the voltage channel if a voltage channel is valid again.
Parameter Value Description
inactive If the channels of the measuring point are not to be considered for deter-
mining the sampling frequency, please select the setting value inactive.
active If you have set the parameter Tracking = active, the measuring point
will be included when determining the sampling frequency.
Note: If the parameter Tracking = active, the determined sampling
frequency applies to all functions in the device not using fixed sampling
rates.
With platform version V07.80 and higher, you can merge measuring points
into Frequency tracking groups in SIPROTEC 5 devices. In this case, every
frequency tracking group specifies its own sampling frequency. You can
find more information on this in chapter 3.3 Sampling-Frequency Tracking
and Frequency Tracking Groups.

Parameter: Measuring-point ID

• Default setting (_:2311:130) Measuring-point ID = 1


The parameter Measuring-point ID is write-protected and displays the ID of the measuring point. If you
are using several measuring points, the Measuring-point ID is continuously incremented.
With platform version V07.80 and higher, you can merge measuring points into Frequency tracking groups
in SIPROTEC 5 devices. In this case, every frequency tracking group specifies its own sampling frequency. You
can find more information on this in chapter 3.3 Sampling-Frequency Tracking and Frequency Tracking
Groups.

Parameter: Magnitude correction

• Default setting (_:3811:103) Magnitude correction = 1.000


When using the Magnitude correction parameter, the magnitude (magnitude correction) is adjusted for
the voltage input. This allows you to correct the tolerances of the primary current transformer phase-selec-
tively. The magnitude correction may be required for highly precise measurements. Use a comparison meas-
urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.

NOTE

i The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.

358 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

6.1.8 Settings

General

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Phase sequence • ABC ABC
• ACB

Measuring Point I-3ph

Addr. Parameter C Setting Options Default Setting


General
_:8881:115 CT 3-phase:CT connec- • not assigned 3-phase + IN
tion
• 3-phase + IN
• 3-phase
• 3-phase + IN-separate
• 3-phase, 2 primary CT
• 3ph,2prim.CT + IN-sep
• 2ph, 2p. CT + IN-sep
• 2ph, 2p. CT + 2 IN-sep
_:8881:127 CT 3-phase:Tracking • inactive active
• active
_:8881:130 CT 3-phase:Measuring- 0 to 100 0
point ID
CT phases
_:8881:101 CT 3-phase:Rated 1.0 A to 100 000.0 A 1000.0 A
primary current
_:8881:102 CT 3-phase:Rated secon- • 1A 1A
dary current
• 5A
_:8881:117 CT 3-phase:Current • 1.6 x IR 100 x IR
range
• 100 x IR
• 50 x IR
_:8881:118 CT 3-phase:Internal CT • CT protection CT protection
type
• CT measurement
• CT protection
• CT measurement
• CT Process bus
_:8881:116 CT 3-phase:Neutr.point • no yes
in dir.of ref.obj
• yes
_:8881:114 CT 3-phase:Inverted • none none
phases
• AC
• BC
• AB
_:8881:107 CT 3-phase:CT error 1.00 to 10.00 1.00
changeover
_:8881:108 CT 3-phase:CT error A 0.5 % to 50.0 % 5.0 %
_:8881:109 CT 3-phase:CT error B 0.5 % to 50.0 % 15.0 %

SIPROTEC 5, 7SJ82/7SJ85, Manual 359


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Addr. Parameter C Setting Options Default Setting


CT IN2
_:8881:140 CT 3-phase:Current • 1.6 x IR 100 x IR
range
• 100 x IR
• 50 x IR
_:8881:141 CT 3-phase:Internal CT • CT protection CT protection
type
• CT measurement
• CT protection
• CT measurement
• CT Process bus
CT IN
_:8881:104 CT 3-phase:Rated 1.0 A to 100 000.0 A 1000.0 A
primary current
_:8881:105 CT 3-phase:Rated secon- • 1A 1A
dary current
• 5A
_:8881:119 CT 3-phase:Current • 1.6 x IR 100 x IR
range
• 100 x IR
• 50 x IR
_:8881:120 CT 3-phase:Internal CT • CT protection CT protection
type
• CT measurement
• CT protection
• CT measurement
• CT Process bus
CT 1
_:3841:103 CT 1:Magnitude correc- 0.010 to 10.000 1.000
tion
_:3841:117 CT 1:Phase • IA
• IB
• IC
• IN
• INsens
• Ix
• IN2
CT 2
_:3842:103 CT 2:Magnitude correc- 0.010 to 10.000 1.000
tion
_:3842:117 CT 2:Phase • IA
• IB
• IC
• IN
• INsens
• Ix
• IN2
CT 3
_:3843:103 CT 3:Magnitude correc- 0.010 to 10.000 1.000
tion

360 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Addr. Parameter C Setting Options Default Setting


_:3843:117 CT 3:Phase • IA
• IB
• IC
• IN
• INsens
• Ix
• IN2
CT 4
_:3844:103 CT 4:Magnitude correc- 0.010 to 10.000 1.000
tion
_:3844:117 CT 4:Phase • IA
• IB
• IC
• IN
• INsens
• Ix
• IN2
Brk.wire det.
_:5581:1 Brk.wire det.:Mode • off off
• on
• test
Supv. balan. I
_:2491:1 Supv. balan. I:Mode • off off
• on
• test
_:2491:101 Supv. balan. I:Release 1 A @ 100 Irated 0.030 A to 35.000 A 0.500 A
threshold 5 A @ 100 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 2.500 A
_:2491:102 Supv. balan. I:Threshold 0.10 to 0.95 0.50
min/max
_:2491:6 Supv. balan. I:Delay 0.00 s to 100.00 s 5.00 s
failure indication
Supv. ph.seq.I
_:2551:1 Supv. ph.seq.I:Mode • off off
• on
• test
_:2551:6 Supv. ph.seq.I:Delay 0.00 s to 100.00 s 5.00 s
failure indication
Supv. sum I
_:2431:1 Supv. sum I:Mode • off off
• on
• test

SIPROTEC 5, 7SJ82/7SJ85, Manual 361


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Addr. Parameter C Setting Options Default Setting


_:2431:102 Supv. sum I:Threshold 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2431:101 Supv. sum I:Slope factor 0.00 to 0.95 0.10
_:2431:6 Supv. sum I:Delay failure 0.00 s to 100.00 s 5.00 s
indication
Supv.ADC sum I
_:2401:1 Supv.ADC sum I:Mode • off off
• on
• test

Measuring Point I-1ph

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Rated primary 1.0 A to 100 000.0 A 1000.0 A
current
_:2311:102 General:Rated secondary • 1A 1A
current
• 5A
_:2311:103 General:Current range • 1.6 x IR 100 x IR
• 100 x IR
• 50 x IR
_:2311:104 General:Internal CT type • CT protection CT protection
• CT measurement
• CT Process bus
_:2311:116 General:Term. 1,3,5,7 in • no yes
dir. of obj.
• yes
_:2311:105 General:Tracking • inactive inactive
• active
_:2311:130 General:Measuring-point 0 to 100 0
ID
CT 1
_:3841:103 CT 1:Magnitude correc- 0.010 to 10.000 1.000
tion
_:3841:117 CT 1:Phase • IA
• IB
• IC
• IN
• INsens
• Ix

362 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Measuring Point V-3ph

Addr. Parameter C Setting Options Default Setting


General
_:8911:101 VT 3-phase:Rated 0.200 kV to 1200.000 kV 400.000 kV
primary voltage
_:8911:102 VT 3-phase:Rated secon- 80 V to 230 V 100 V
dary voltage
_:8911:103 VT 3-phase:Matching 0.10 to 9.99 1.73
ratio Vph / VN
_:8911:104 VT 3-phase:VT connec- • not assigned 3 ph-to-gnd
tion volt. + VN
• 3 ph-to-gnd volt. + VN
• 3 ph-to-gnd voltages
• 3 ph-to-ph volt. + VN
• 3 ph-to-ph voltages
• 2 ph-to-ph volt. + VN
• 2 ph-to-ph voltages
_:8911:106 VT 3-phase:Inverted • none none
phases
• AC
• BC
• AB
_:8911:111 VT 3-phase:Tracking • inactive active
• active
_:8911:130 VT 3-phase:Measuring- 0 to 100 0
point ID
VT 1
_:3811:103 VT 1:Magnitude correc- 0.010 to 10.000 1.000
tion
_:3811:108 VT 1:Phase • VA
• VB
• VC
• V AB
• V BC
• V CA
• VN
• Vx
• VCB
VT 2
_:3812:103 VT 2:Magnitude correc- 0.010 to 10.000 1.000
tion

SIPROTEC 5, 7SJ82/7SJ85, Manual 363


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Addr. Parameter C Setting Options Default Setting


_:3812:108 VT 2:Phase • VA
• VB
• VC
• V AB
• V BC
• V CA
• VN
• Vx
• VCB
VT 3
_:3813:103 VT 3:Magnitude correc- 0.010 to 10.000 1.000
tion
_:3813:108 VT 3:Phase • VA
• VB
• VC
• V AB
• V BC
• V CA
• VN
• Vx
• VCB
VT 4
_:3814:103 VT 4:Magnitude correc- 0.010 to 10.000 1.000
tion
_:3814:108 VT 4:Phase • VA
• VB
• VC
• V AB
• V BC
• V CA
• VN
• Vx
• VCB
Supv. balan. V
_:2521:1 Supv. balan. V:Mode • off off
• on
• test
_:2521:101 Supv. balan. V:Release 0.300 V to 170.000 V 50.000 V
threshold
_:2521:102 Supv. balan. V:Threshold 0.58 to 0.95 0.75
min/max
_:2521:6 Supv. balan. V:Delay 0.00 s to 100.00 s 5.00 s
failure indication

364 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Addr. Parameter C Setting Options Default Setting


Supv. ph.seq.V
_:2581:1 Supv. ph.seq.V:Mode • off off
• on
• test
_:2581:6 Supv. ph.seq.V:Delay 0.00 s to 100.00 s 5.00 s
failure indication
Supv. sum V
_:2461:1 Supv. sum V:Mode • off off
• on
• test
_:2461:3 Supv. sum V:Threshold 0.300 V to 170.000 V 25.000 V
_:2461:6 Supv. sum V:Delay 0.00 s to 100.00 s 5.00 s
failure indication
VT miniatureCB
_:2641:101 VT minia- 0.00 s to 0.03 s 0.00 s
tureCB:Response time

Measuring Point V-1ph

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Rated primary 0.200 kV to 1200.000 kV 400.000 kV
voltage
_:2311:102 General:Rated secondary 80 V to 340 V 100 V
voltage
_:2311:108 General:Matching ratio 0.10 to 9.99 1.73
Vph / VN
_:2311:103 General:Tracking • inactive inactive
• active
_:2311:130 General:Measuring-point 0 to 100 0
ID
VT 1
_:3811:103 VT 1:Magnitude correc- 0.010 to 10.000 1.000
tion
_:3811:108 VT 1:Phase • VA
• VB
• VC
• V AB
• V BC
• V CA
• VN
• Vx
• VCB
• VN broken-delta
_:3811:107 VT 1:Sequence number 1 to 2147483647 2147483647
device

SIPROTEC 5, 7SJ82/7SJ85, Manual 365


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

Addr. Parameter C Setting Options Default Setting


VT miniatureCB
_:2641:101 VT minia- 0.00 s to 0.03 s 0.00 s
tureCB:Response time

6.1.9 Information List

General

No. Information Data Class Type


(Type)
General
_:2311:500 General:>Phs-rotation reversal SPS I
_:2311:501 General:>Invert Phases SPS I
General
_:2311:319 General:Phase sequence ABC SPS O
_:2311:320 General:Phase sequence ACB SPS O
_:2311:321 General:Freq.out of oper.range SPS O
_:2311:322 General:f sys MV O
_:2311:323 General:f track MV O

Measuring Point I-3ph

No. Information Data Class Type


(Type)
General
_:8881:319 CT 3-phase:Phases AB inverted SPS O
_:8881:320 CT 3-phase:Phases BC inverted SPS O
_:8881:321 CT 3-phase:Phases AC inverted SPS O
Meas.val.dist
_:8881:325 CT 3-phase:Meas.point mult.config. SPS O
CT 1
_:3841:300 CT 1:Sampled val. current SAV O
CT 2
_:3842:300 CT 2:Sampled val. current SAV O
CT 3
_:3843:300 CT 3:Sampled val. current SAV O
CT 4
_:3844:300 CT 4:Sampled val. current SAV O
Calc.IN
_:20191:300 Calc.IN:Sampled val. current SAV O
Brk.wire det.
_:5581:82 Brk.wire det.:>Block function SPS I
_:5581:54 Brk.wire det.:Inactive SPS O
_:5581:52 Brk.wire det.:Behavior ENS O
_:5581:53 Brk.wire det.:Health ENS O
_:5581:301 Brk.wire det.:Phs A BW suspected SPS O
_:5581:302 Brk.wire det.:Phs B BW suspected SPS O
_:5581:303 Brk.wire det.:Phs C BW suspected SPS O
_:5581:304 Brk.wire det.:Phase A broken wire SPS O

366 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

No. Information Data Class Type


(Type)
_:5581:305 Brk.wire det.:Phase B broken wire SPS O
_:5581:306 Brk.wire det.:Phase C broken wire SPS O
_:5581:307 Brk.wire det.:Broken wire suspected SPS O
_:5581:308 Brk.wire det.:Broken wire confirmed SPS O
Supv. balan. I
_:2491:82 Supv. balan. I:>Block function SPS I
_:2491:54 Supv. balan. I:Inactive SPS O
_:2491:52 Supv. balan. I:Behavior ENS O
_:2491:53 Supv. balan. I:Health ENS O
_:2491:71 Supv. balan. I:Failure SPS O
Supv. ph.seq.I
_:2551:82 Supv. ph.seq.I:>Block function SPS I
_:2551:54 Supv. ph.seq.I:Inactive SPS O
_:2551:52 Supv. ph.seq.I:Behavior ENS O
_:2551:53 Supv. ph.seq.I:Health ENS O
_:2551:71 Supv. ph.seq.I:Failure SPS O
Supv. sum I
_:2431:82 Supv. sum I:>Block function SPS I
_:2431:54 Supv. sum I:Inactive SPS O
_:2431:52 Supv. sum I:Behavior ENS O
_:2431:53 Supv. sum I:Health ENS O
_:2431:71 Supv. sum I:Failure SPS O
Supv.ADC sum I
_:2401:82 Supv.ADC sum I:>Block function SPS I
_:2401:54 Supv.ADC sum I:Inactive SPS O
_:2401:52 Supv.ADC sum I:Behavior ENS O
_:2401:53 Supv.ADC sum I:Health ENS O
_:2401:71 Supv.ADC sum I:Failure SPS O
Saturat. det.
_:17731:54 Saturat. det.:Inactive SPS O
_:17731:52 Saturat. det.:Behavior ENS O
_:17731:53 Saturat. det.:Health ENS O

Measuring Point I-1ph

No. Information Data Class Type


(Type)
CT 1
_:3841:300 CT 1:Sampled val. current SAV O

Measuring Point V-3ph

No. Information Data Class Type


(Type)
General
_:8911:315 VT 3-phase:Phases AB inverted SPS O
_:8911:316 VT 3-phase:Phases BC inverted SPS O
_:8911:317 VT 3-phase:Phases AC inverted SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 367


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.1 Power-System Data

No. Information Data Class Type


(Type)
VT 1
_:3811:300 VT 1:Sampled val. voltage SAV O
VT 2
_:3812:300 VT 2:Sampled val. voltage SAV O
VT 3
_:3813:300 VT 3:Sampled val. voltage SAV O
VT 4
_:3814:300 VT 4:Sampled val. voltage SAV O
Supv. balan. V
_:2521:82 Supv. balan. V:>Block function SPS I
_:2521:54 Supv. balan. V:Inactive SPS O
_:2521:52 Supv. balan. V:Behavior ENS O
_:2521:53 Supv. balan. V:Health ENS O
_:2521:71 Supv. balan. V:Failure SPS O
Supv. ph.seq.V
_:2581:82 Supv. ph.seq.V:>Block function SPS I
_:2581:54 Supv. ph.seq.V:Inactive SPS O
_:2581:52 Supv. ph.seq.V:Behavior ENS O
_:2581:53 Supv. ph.seq.V:Health ENS O
_:2581:71 Supv. ph.seq.V:Failure SPS O
Supv. sum V
_:2461:82 Supv. sum V:>Block function SPS I
_:2461:54 Supv. sum V:Inactive SPS O
_:2461:52 Supv. sum V:Behavior ENS O
_:2461:53 Supv. sum V:Health ENS O
_:2461:71 Supv. sum V:Failure SPS O
Definite-T 1
_:2641:500 VT miniatureCB:>Open SPS I
Calc.VN
_:20221:300 Calc.VN:Sampled val. voltage SAV O

Measuring Point V-1ph

No. Information Data Class Type


(Type)
VT 1
_:3811:300 VT 1:Sampled val. voltage SAV O
Definite-T 1
_:2641:500 VT miniatureCB:>Open SPS I

368 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.2 Group Indications of Overcurrent Protection Functions

6.2 Group Indications of Overcurrent Protection Functions

6.2.1 Description

The function block Group indications of the overcurrent protection functions uses the pickup and operate
indications of the following functions:

• Overcurrent Protection, Phases

• Overcurrent Protection, Ground

• Directional overcurrent protection, phases

• Directional Overcurrent Protection, Ground

• Instantaneous High-Current Tripping


The group indications of the overcurrent protection are generated by a logical OR of the stage-selective pickup
and operate indications of the functions listed above (see also Figure 6-4):

• Pickup

• Operate
The pickup and operate indications are output, where present, with direction information.

[loocgri2-271112-01.tif, 3, en_US]

Figure 6-4 Logic Diagram of the Overcurrent Protection Group Indications

SIPROTEC 5, 7SJ82/7SJ85, Manual 369


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

6.3 Overcurrent Protection, Phases

6.3.1 Overview of Functions

The Overcurrent protection, phases function (ANSI 50/51):

• Detects short circuits in electrical equipment

• Can be used as backup overcurrent protection in addition to the main protection

6.3.2 Structure of the Function

The Overcurrent protection, phases function is used in protection function groups. 2 kinds of functions are
available for the 3-phase overcurrent protection:

• Overcurrent protection, phases – advanced (50/51 OC-3ph-A)

• Overcurrent protection, phases – basic (50/51 OC-3ph-B)


The Basic function type is provided for standard applications. The Advanced function type offers more func-
tionality and is provided for more complex applications.
Both function types are preconfigured by the manufacturer with 2 Definite-time overcurrent protection
stages and with 1 Inverse-time overcurrent protection stage.
In the Overcurrent protection, phase – advanced function type, the following stages can be operated simul-
taneously:

• Maximum of 4 stages Definite-time overcurrent protection – advanced

• 2 stages Inverse-time overcurrent protection – advanced

• 2 stages User-defined overcurrent protection characteristic curve


In the Overcurrent protection, phases – basic function type, the following stages can be operated simulta-
neously:

• Maximum of 4 stages Definite-time overcurrent protection – basic

• 1 stage Inverse-time overcurrent protection – basic

Stages that are not preconfigured are shown in gray in the following figures. Apart from the tripping delay
characteristic, the stages are identical in structure.
The optional function block Filter offered in the advanced function allows to gain harmonics or to compensate
the amplitude attenuation for the RMS value.
The group-indication output logic generates the following group indications of the protection function by the
logical OR of the stage-selective indications:

• Pickup

• Operate

370 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

[dw_ocp_ad with Filter.tif, 2, en_US]

Figure 6-5 Structure/Embedding of the Function Overcurrent Protection, Phases – Advanced

[dwocpbp1-210113-01.tif, 3, en_US]

Figure 6-6 Structure/Embedding of the Function Overcurrent Protection, Phases – Basic

If the device-internal functions listed in the following are present in the device, these functions can influence
the pickup values and tripping delays of the stages or block the stages. The stage can also be affected by an
external source via a binary input signal.

• Automatic reclosing (AREC)

• Cold-load pickup detection

• Binary input signal


If the device is equipped with an Inrush-current detection function, the stages can be stabilized against trip-
ping due to transformer-inrush currents (available in both function types).

SIPROTEC 5, 7SJ82/7SJ85, Manual 371


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

6.3.3 Filter for RMS Value Gain

6.3.3.1 Description
The function block Filter can be used to adapt the RMS value for 2 means:

• To gain harmonics in a defined way. Higher harmonics can stress the protected object thermally more
than lower harmonics. This is the case for reactors applied in AC filters. In addition, the amplitude attenu-
ation of higher frequencies due to the anti-aliasing filter of the device is automatically compensated by
the filter

• To only compensate the amplitude attenuation of higher frequencies due to the anti-aliasing filter
The filter gain (amplitude response) is realized by a 9-order FIR filter.

Logic

[lo_TOLP_FilterStage, 1, en_US]

Figure 6-7 Logic Diagram of the Function Block Filter

The FIR filter gains the 8-kHz sampled values according to the set filter coefficients. Afterwards, the RMS value
is calculated. The symmetrical 9-order filter coefficients are set via the values of the respective parameters
h(0), h(1), h(2), h(3), and h(4).

NOTE

i A FIR-filter configuration tool is provided as an auxiliary PC tool. With this PC tool, the coefficients h(0),
h(1), h(2), h(3), h(4) of the FIR filter are generated according to the required gain factors (amplitude
response). The tool can be obtained from the SIPROTEC download area. For more information about the
tool, refer to the tool help function.

The gained RMS value is delivered to the protection stages only when the function block Filter is instantiated
and the parameter Enable filter is set as yes. Otherwise, the normal RMS value is used.

Functional Measured Values

Values Description Primary Secondary % Referenced to


Iph:A Gained RMS measured kA A Parameter Rated current
value of current A
Iph:B Gained RMS measured kA A Parameter Rated current
value of current B

372 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Values Description Primary Secondary % Referenced to


Iph:C Gained RMS measured kA A Parameter Rated current
value of current C

You can find the parameter Rated current in the FB General of function groups where the Overcurrent
protection, phases – advanced function is used.
If the parameter Enable filter is set to no, the functional measured values are shown as ---.

6.3.3.2 Application and Setting Notes

Parameter: Enable filter

• Default setting (_:1) Enable filter = no.


With the parameter Enable filter, you set whether the Filter is enabled.
Parameter Value Description
yes If gained RMS values should be used in one of the protection stages, set
parameter Enable filter = yes.
no If no gained RMS values are needed, set the parameter Enable filter =
no.

Parameter: h(0), h(1), h(2), h(3), h(4)

• Default setting (_:2) h(0) = 0.000

• Default setting (_:3) h(1) = 0.000

• Default setting (_:4) h(2) = 0.000

• Default setting (_:5) h(3) = 0.000

• Default setting (_:6) h(4) = 1.000


With the default value of the coefficients, the filter has no effect and no gain is applied.
If the filter shall be applied to adapt the RMS value calculation to a specific protection object such as a reactor,
the reactor manufacturer has to provide the required amplitude response (gain factors) for the reactor. To
determine the coefficients h(0) to h(4) for the FIR filter, you must enter the gain factors into the auxiliary PC
tool which is available in the SIPROTEC download area. The 5 required coefficients are generated by the tool.
They have to be entered manually as settings to configure the filter. The amplitude attenuation of higher
frequencies due to the anti aliasing filter of the device is automatically taken into account and compensated
by the filter.
To only compensate the attenuation of higher frequencies by the device, set the following coefficients in the
filter.
Rated Frequency Filter Coefficients for Only Compensating the Device Amplitude Attenu-
ation
50 Hz h(0) = -0.002
h(1) = -0.012
h(2) = 0.045
h(3) = -0.110
h(4) = 1.151
60 Hz h(0) = -0.005
h(1) = -0.020
h(2) = 0.058
h(3) = -0.128
h(4) = 1.170

SIPROTEC 5, 7SJ82/7SJ85, Manual 373


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

6.3.3.3 Settings

Addr. Parameter C Setting Options Default Setting


Filter
_:1 Filter:Enable filter • no no
• yes
_:2 Filter:h(0) -100.000 to 100.000 0.000
_:3 Filter:h(1) -100.000 to 100.000 0.000
_:4 Filter:h(2) -100.000 to 100.000 0.000
_:5 Filter:h(3) -100.000 to 100.000 0.000
_:6 Filter:h(4) -100.000 to 100.000 1.000

6.3.3.4 Information List

No. Information Data Class Type


(Type)
Filter
_:301 Filter:Iph:A MV O
_:302 Filter:Iph:B MV O
_:303 Filter:Iph:C MV O

374 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

6.3.4 Stage with Definite-Time Characteristic Curve

6.3.4.1 Description

Logic of the Basic Stage

[loocp3b1-280113-01.tif, 3, en_US]

Figure 6-8 Logic Diagram of the Definite-Time Overcurrent Protection (Phases) – Basic

SIPROTEC 5, 7SJ82/7SJ85, Manual 375


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Logic of the Advanced Stage

[lo_OCP_Adv_UMZ_StageControl, 1, en_US]

Figure 6-9 Logic Diagram of the Stage Control

376 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

[loocp3p1-310511-01.tif, 4, en_US]

Figure 6-10 Logic Diagram of the Definite-Time Overcurrent Protection (Phases) – Advanced

Method of measurement (Basic and Advanced Stage)


You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value.

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

RMS-Value Selection (Advanced Stage)


If RMS value is selected as the method of measurement, the protection function supports 2 kinds of RMS
measurement.

• Normal RMS value

• Gained RMS value from the function block Filter

SIPROTEC 5, 7SJ82/7SJ85, Manual 377


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

If the function block Filter is configured and if you have enabled the filter, the gained RMS value is automati-
cally used.

NOTE

i When the function block Filter is applied, only one 3-phase current measuring point is allowed to be
connected to the 3-phase current interface of the function group.

I0 Elimination (Advanced Stage)


In order to increase the sensitivity for the 2-phase short circuit on the transformer low-voltage side, use the
I0 elimination of the phase currents for the overcurrent-protection application on one transformer.
In order to determine the I0 elimination of the phase currents, the transformer neutral point current IY must be
measured.

[dwsgaocp-230414-01, 1, en_US]

Figure 6-11 I0 Elimination Principle

The transformer neutral point current IY is measured via a 1-phase current measuring point that is connected
to the Voltage/current 1-phase. The function group Voltage/current 1-phase must be connected to the func-
tion group Voltage/current 3-phase in which the function Overcurrent protection, phases is being used.

[sccpfoint-230414-01, 1, en_US]

Figure 6-12 Connection of the Voltage/Current 1-Phase Function Group with the Neutral Point Input of the
Voltage/Current 3-Phase Function Group

In case of an I0 elimination, the following calculations result:


IA-elim. = IA - 1/3 IY
IB-elim. = IB - 1/3 IY
IC-elim. = IC - 1/3 IY
The phase current Iphx-elim. is necessary for the following protection process.
If the Method of measurement parameter is set to fundamental comp., the I0 elimination is applied.
The currents Iphx-elim. are available as functional values.

Pickup delay (Advanced Stage)


If the current exceeds the threshold value, the pickup delay is generated. If the threshold remains exceeded
during the pickup delay time, the pickup signal is generated.

378 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Dropout Delay (Advanced Stage)


If the value falls below the dropout threshold, the dropout can be delayed. The pickup is maintained for the
specified time. The tripping delay continues to run. If the time delay expires while the pickup is still main-
tained, the stage operates.

Blocking of the Stage (Basic and Advanced Stage)


The following blockings reset the picked up stage completely:

• Via the binary input signal >Block stage from an external or internal source

• Via the functionality of the dynamic settings (only available in the Advanced function type, see
subtitle Influence of other functions via dynamic settings and chapter 6.3.8.1 Description ).

Blocking of the Time Delay (Basic and Advanced Stage)


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.

Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.3.7.1 Description .

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can influence the overcurrent-protection stages:

• Automatic reclosing

• Cold-load pickup detection

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.3.8.1 Description .

6.3.4.2 Application and Setting Notes

Parameter: Method of measurement

• Default setting (_:661:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

SIPROTEC 5, 7SJ82/7SJ85, Manual 379


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Parameter: Threshold, Operate delay

• Default setting (_:661:3) Threshold = 1.500 A (for the 1st stage)

• Default setting (_:661:6) Operate delay = 0.30 s (for the 1st stage)
Set the Threshold and Operate delay parameters for the specific application.
The following details apply to a 2-stage characteristic curve (1st stage = definite-time overcurrent protection
stage and 2nd stage = high-current stage).
1st stage (overcurrent stage):
The setting depends on the maximum occurring operating current. Pickup by overload must be excluded since
overcurrent protection operates with short tripping times as short-circuit protection and not as overload
protection. Therefore, set the Threshold parameter for lines to approx. 10 %, for transformers and motors to
approx. 20 % above the maximum load that is expected.

EXAMPLE
Overcurrent-protection stage: 110-kV overhead line, 150 mm2 cross-section
Maximum transmittable power
Pmax = 120 MVA
Correspondingly
Imax = 630 A
Current transformer = 600 A/5 A
Safety factor = 1.1

Settings in primary and secondary values result in the setting values:

[foocpph1-030311-01.tif, 2, en_US]

The Operate delay to be set is derived from the time-grading schedule that has been prepared for the
system.

2nd Stage (High-Current Stage):


This tripping stage can also be used for current grading. This applies in the case of very long lines with low
source impedance or ahead of high reactances (for example, transformers, shunt reactors). Set the
Threshold parameter to ensure that the stage does not pick up in case of a short circuit at the end of the
line.
Set the Operate delay parameter to 0 or to a low value.
Siemens recommends that the threshold values be determined with a system analysis. The following example
illustrates the principle of grading with a current threshold on a long line.

EXAMPLE
High-current stage: 110-kV overhead line, 150 mm2 cross-section
s (length) = 60 km
ZL/s = 0.46 Ω/km
Ratio of zero-sequence impedance and positive-sequence impedance of the line: ZL0/ZL1 = 4
Short-circuit power at the beginning of the line:
Ssc' = 2.5 GVA

380 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Ratio of zero-sequence impedance and positive-sequence impedance of the source impedance at the begin-
ning of the line: ZP0/ZP1 = 2
Current transformer = 600 A/5 A

Resulting in the following values for the line impedance ZL and the source impedance ZP:

[fo_OCP002_030311, 1, en_US]

[fo_OCP003_030311, 1, en_US]

The 3-phase short-circuit current at the end of the line is Isc end:

[fo_ocpph4_030311, 1, en_US]

The settings in primary and secondary values result in the following setting values which include a safety
margin of 10 %:

[foocp004-030311-01.tif, 2, en_US]

If short-circuit currents exceed 2365 A (primary) or 19.7 A (secondary), there is a short circuit on the line to be
protected. The overcurrent protection can cut off this short circuit immediately.
Note: The amounts in the calculation example are accurate enough for overhead lines. If the source impe-
dance and line impedance have different angles, you have to use complex numbers to calculate the
Threshold .

Parameter: I0 elimination

• Default setting (_:661:120) I0 elimination = no


This parameter is not visible in the basic stage.
The I0 elimination in phase currents for overcurrent-protection applications can be used in a transformer. This
increases the sensitivity for the 2-phase short circuit on the transformer low-voltage side. The following condi-
tions must be fulfilled:

• The transformer neutral point current IY is measured and is available for the protection function group.

• The parameter Method of measurement is set to fundamental comp. .


With the I0 elimination parameter, you can switch the I0 elimination function on or off.

Parameter: Pickup delay

• Default setting (_:661:102) Pickup delay = 0.00 s


This parameter is not visible in the basic stage.
For special applications, it is desirable that a short exceeding of the current threshold does not lead to the
pickup of the stage and start fault logging and recording. If this stage is used as a thermal overload function,
that is considered a special application.
When using the Pickup delay parameter, a time interval is defined during which a pickup is not triggered
if the current threshold is exceeded.

SIPROTEC 5, 7SJ82/7SJ85, Manual 381


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

For all short-circuit protection applications, this value is 0.00 s as a default.

Parameter: Dropout delay

• Default setting (_:661:101) Dropout delay = 0.00 s


This parameter is not visible in the basic stage.
Siemens recommends using the default setting 0 since the dropout of a protection stage must be done as fast
as possible.
You can use the Dropout delay parameter ≠ 0 to obtain a uniform dropout behavior if you use it together
with an electromechanical relay. This is required for time grading. The dropout time of the electromechanical
relay must be known for this purpose. Subtract the dropout time of your own device (see Technical Data) and
set the result.

Parameter: Dropout ratio

• Default setting (_:661:4) Dropout ratio = 0.95


This parameter is not visible in the basic stage.
The recommended set value of 0.95 is appropriate for most applications.
To achieve high-precision measurements, the setting value of the parameter Dropout ratio can be
reduced, for example, to 0.98. If you expect highly fluctuating measurands at the response threshold, you
can increase the setting value of the parameter Dropout ratio. This avoids chattering of the tripping stage.

Parameter: 1-pole operate allowed

• Default setting (_:661:11) 1-pole operate allowed = no


The parameter must be set for the specific application.
Parameter Value Description
no The stage always operates 3-pole.
yes The stage operates phase-selectively. However, tripping by the device (generated in
the trip logic of the Circuit-breaker function group) is always 3-pole because the
device does not support phase-selective tripping.

6.3.4.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:661:1 Definite-T 1:Mode • off off
• on
• test
_:661:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:661:11 Definite-T 1:1-pole • no no
operate allowed
• yes
_:661:26 Definite-T 1:Dynamic • no no
settings
• yes
_:661:27 Definite-T 1:Blk. w. • no no
inrush curr. detect.
• yes
_:661:8 Definite-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:661:120 Definite-T 1:I0 elimina- • no no
tion
• yes

382 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:661:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:4 Definite-T 1:Dropout 0.90 to 0.99 0.95
ratio
_:661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.00 s
_:661:101 Definite-T 1:Dropout 0.00 s to 60.00 s 0.00 s
delay
_:661:6 Definite-T 1:Operate 0.00 s to 100.00 s 0.30 s
delay
Dyn.s: AR off/n.rdy
_:661:28 Definite-T 1:Effect. by AR • no no
off/n.ready
• yes
_:661:35 Definite-T 1:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:661:29 Definite-T 1:Effected by • no no
AR cycle 1
• yes
_:661:36 Definite-T 1:Stage • no no
blocked
• yes
_:661:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:20 Definite-T 1:Operate 0.00 s to 100.00 s 0.30 s
delay
Dyn.set: AR cycle 2
_:661:30 Definite-T 1:Effected by • no no
AR cycle 2
• yes
_:661:37 Definite-T 1:Stage • no no
blocked
• yes
_:661:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:21 Definite-T 1:Operate 0.00 s to 100.00 s 0.30 s
delay
Dyn.set: AR cycle 3
_:661:31 Definite-T 1:Effected by • no no
AR cycle 3
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 383


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:661:38 Definite-T 1:Stage • no no
blocked
• yes
_:661:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:22 Definite-T 1:Operate 0.00 s to 100.00 s 0.30 s
delay
Dyn.s: AR cycle>3
_:661:32 Definite-T 1:Effected by • no no
AR cycle gr. 3
• yes
_:661:39 Definite-T 1:Stage • no no
blocked
• yes
_:661:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:23 Definite-T 1:Operate 0.00 s to 100.00 s 0.30 s
delay
Dyn.s: Cold load PU
_:661:33 Definite-T 1:Effect. b. • no no
cold-load pickup
• yes
_:661:40 Definite-T 1:Stage • no no
blocked
• yes
_:661:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:24 Definite-T 1:Operate 0.00 s to 100.00 s 0.30 s
delay
Dyn.set: bin.input
_:661:34 Definite-T 1:Effected by • no no
binary input
• yes
_:661:41 Definite-T 1:Stage • no no
blocked
• yes
_:661:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A

384 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:661:25 Definite-T 1:Operate 0.00 s to 100.00 s 0.30 s
delay

6.3.4.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:661:81 Definite-T 1:>Block stage SPS I
_:661:84 Definite-T 1:>Activ. dyn. settings SPS I
_:661:500 Definite-T 1:>Block delay & op. SPS I
_:661:54 Definite-T 1:Inactive SPS O
_:661:52 Definite-T 1:Behavior ENS O
_:661:53 Definite-T 1:Health ENS O
_:661:60 Definite-T 1:Inrush blocks operate ACT O
_:661:62 Definite-T 1:Dyn.set. AR cycle1act. SPS O
_:661:63 Definite-T 1:Dyn.set. AR cycle2act. SPS O
_:661:64 Definite-T 1:Dyn.set. AR cycle3act. SPS O
_:661:65 Definite-T 1:Dyn.set. ARcycl.>3act SPS O
_:661:66 Definite-T 1:Dyn.set. CLP active SPS O
_:661:67 Definite-T 1:Dyn.set. BI active SPS O
_:661:68 Definite-T 1:Dyn. set. blks. pickup SPS O
_:661:55 Definite-T 1:Pickup ACD O
_:661:56 Definite-T 1:Operate delay expired ACT O
_:661:57 Definite-T 1:Operate ACT O
_:661:302 Definite-T 1:I0el.Iph WYE O

SIPROTEC 5, 7SJ82/7SJ85, Manual 385


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

6.3.5 Stage with Inverse-Time Characteristic Curve

6.3.5.1 Description

Logic of the Basic Stage

[loocp3b2-280113-01.tif, 2, en_US]

Figure 6-13 Logic Diagram of the Inverse-Time Overcurrent Protection (Phases) – Basic

386 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Logic of the Advanced Stage

[lo_Stage Control, 1, en_US]

Figure 6-14 Logic Diagram of the Stage Control

[loocp3p2-310511-01.tif, 4, en_US]

Figure 6-15 Logic Diagram of the Inverse-Time Overcurrent Protection (Phases) – Advanced

SIPROTEC 5, 7SJ82/7SJ85, Manual 387


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

RMS-Value Selection (Advanced Stage)


If RMS value is selected as the method of measurement, the protection function supports 2 kinds of RMS
measurement.

• Normal RMS value

• Gained RMS value from the function block Filter


If the function block Filter is configured and if you have enabled the filter, the gained RMS value is automati-
cally used.

NOTE

i When the function block Filter is applied, only one 3-phase current measuring point is allowed to be
connected to the 3-phase current interface of the function group.

Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve according to IEC and ANSI (Basic and
Advanced Stage)

When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.

Minimum Time of the Curve (Advanced Stage)


With the parameter Min. time of the curve, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time.

[DwOcp3Mi_20140715-01, 1, en_US]

Figure 6-16 Minimum Operating Time of the Curve

388 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Additional Time Delay (Advanced Stage)


With the parameter Additional time delay, you define a definite-time delay in addition to the inverse-
time delay. With this setting, the whole curve is shifted on the time axis by this additional definite time.

Method of Measurement (Basic and Advanced Stage)


You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value.

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

I0 Elimination (Advanced Stage)


In order to increase the sensitivity for the 2-phase short circuit on the transformer low-voltage side, use the
I0 elimination of the phase currents for the overcurrent-protection applications on one transformer.
In order to determine the I0 elimination of the phase currents, the transformer neutral point current IY must be
measured.

[dwsgaocp-230414-01, 1, en_US]

Figure 6-17 I0 Elimination Principle

The transformer neutral point current IY is measured via a 1-phase current measuring point that is connected
to the Voltage/current 1-phase. The function group Voltage/current 1-phase must be connected to the func-
tion group Voltage/current 3-phase in which the function Overcurrent protection, phases is used.

[sccpfoint-230414-01, 1, en_US]

Figure 6-18 Connection of the Function Group Voltage/Current 1-Phase with the Neutral Point Input of the
Voltage/Current 3-Phase Function Group

In case of an I0 elimination, the following calculations must be considered:


IA-elim. = IA - 1/3 IY
IB-elim. = IB - 1/3 IY
IC-elim. = IC - 1/3 IY

SIPROTEC 5, 7SJ82/7SJ85, Manual 389


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

The phase current Iphx-elim. is necessary for the following protection process.
If the Method of measurement parameter is set to fundamental comp., the I0 elimination is operating.
The currents Iphx-elim. are available as functional values.

Pickup Delay (Advanced Stage)


If the current exceeds the threshold value, the pickup delay starts. If the threshold is exceeded during the
pickup delay time, the pickup signal is generated.

Blocking of the Stage (Basic and Advanced Stage)


The following blockings reset the picked up stage completely:

• Via the binary input signal >Block stage from an external or internal source

• Via the functionality of the dynamic settings (only available in the Advanced function type, see
subtitle Influence of other functions via dynamic settings and chapter 6.3.8.1 Description ).

Blocking of the Time Delay (Basic and Advanced Stage)


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.

Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.3.7.1 Description .

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can influence the overcurrent-protection stages:

• Automatic reclosing

• Cold-load pickup detection

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.3.8.1 Description .

6.3.5.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:691:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.

390 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Parameter Value Description


fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Type of character. curve

• Default setting (_:691:130) Type of character. curve = IEC normal inverse


The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application. For more information about the parameter
Type of character. curve, refer to chapter 12.5.2 Stage with Inverse-Time Characteristic Curve.

Parameter: Min. time of the curve

• Default setting (_:691:113) Min. time of the curve = 0.00 s


This parameter is only available in the advanced stage.
With the Min. time of the curve parameter, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time. If the
setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommends keeping the default setting of 0 s.

NOTE

i If the set value is smaller than the smallest possible time delay of the inverse-time characteristic curve, the
parameter has no influence on the delay time.

Parameter: Additional time delay

• Default setting (_:691:115) Additional time delay = 0.00 s


With the Additional time delay parameter, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic
time.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommends keeping the default setting of 0 s.

Parameter: Threshold

• Default setting (_:691:3) Threshold = 1.500 A


Set the Threshold and Type of character. curve parameters for the specific application.
The setting depends on the maximum occurring operating current. Pickup by overload must be excluded since
overcurrent protection operates with short tripping times as short-circuit protection and not as overload
protection. Set the Threshold parameter for lines to approx. 10 %, for transformers and motors to approx.
20 % above the maximum expected load.

SIPROTEC 5, 7SJ82/7SJ85, Manual 391


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Note that a safety margin is set between pickup value and threshold value. The stage only picks up at approx.
10 % above the Threshold.

EXAMPLE
Overcurrent-protection stage: 110-kV overhead line, 150 mm2 cross-section
Maximum transmittable power
Pmax = 120 MVA
Correspondingly
Imax = 630 A
Current transformer = 600 A/5 A

Settings in primary and secondary values result in the setting values:

[foocp005-030311-01.tif, 2, en_US]

Parameter: I0 elimination

• Default setting (_:661:120) I0 elimination = no


This parameter is not visible in the basic stage.
The I0 elimination in phase currents for overcurrent-protection applications can be used in a transformer. This
increases the sensitivity for the 2-phase short circuit on the low-voltage side of the transformer. The following
conditions must be fulfilled:

• The transformer neutral point current IY is measured and is available for the protection function group.

• The parameter Method of measurement is set to fundamental comp..


With the I0 elimination setting, you can switch the I0 elimination function on or off.

Parameter: Pickup delay

• Default setting (_:661:102) Pickup delay = 0.00 s


This parameter is not visible in the basic stage.
For special applications it is desirable if the current threshold is briefly exceeded, that this will not lead to the
pickup of the stage and starts fault logging or recording. If this stage is used as a thermal overload function,
that is considered a special application.
When using the Pickup delay parameter, a time interval is defined during which a pickup is not trigger if
the current threshold is exceeded.
For all short-circuit protection applications, this value is 0.00 s and is considered as a default.

Parameter: Time dial

• Default setting (_:691:101) Time dial = 1.00


With the Time dial parameter, you displace the characteristic curve in the time direction.
The set value for the Time dial parameter is derived from the time-grading schedule that has been prepared
for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the param-
eter Time dial at 1 (default setting).

392 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Parameter: Reset

• Default setting (_:691:131) Reset = disk emulation


With the Reset parameter, you define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Select this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.

Parameter: 1-pole operate allowed

• Default setting (_:691:11) 1-pole operate allowed = no


The parameter must be set for the specific application.
Parameter Value Description
no The stage always operates 3-pole.
yes The stage operates phase-selectively. However, tripping by the device
(generated in the trip logic of the Circuit-breaker function group) is always
3-pole because the device does not support phase-selective tripping.

6.3.5.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:691:1 Inverse-T 1:Mode • off off
• on
• test
_:691:2 Inverse-T 1:Operate & • no no
flt.rec. blocked
• yes
_:691:11 Inverse-T 1:1-pole • no no
operate allowed
• yes
_:691:26 Inverse-T 1:Dynamic • no no
settings
• yes
_:691:27 Inverse-T 1:Blk. w. inrush • no no
curr. detect.
• yes
_:691:8 Inverse-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:691:120 Inverse-T 1:I0 elimina- • no no
tion
• yes
_:691:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00 s
_:691:130 Inverse-T 1:Type of char-
acter. curve

SIPROTEC 5, 7SJ82/7SJ85, Manual 393


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:691:113 Inverse-T 1:Min. time of 0.00 s to 1.00 s 0.00 s
the curve
_:691:131 Inverse-T 1:Reset • instantaneous disk emulation
• disk emulation
_:691:101 Inverse-T 1:Time dial 0.00 to 15.00 1.00
_:691:115 Inverse-T 1:Additional 0.00 s to 60.00 s 0.00 s
time delay
Dyn.s: AR off/n.rdy
_:691:28 Inverse-T 1:Effect. by AR • no no
off/n.ready
• yes
_:691:35 Inverse-T 1:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:691:29 Inverse-T 1:Effected by • no no
AR cycle 1
• yes
_:691:36 Inverse-T 1:Stage • no no
blocked
• yes
_:691:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:102 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 2
_:691:30 Inverse-T 1:Effected by • no no
AR cycle 2
• yes
_:691:37 Inverse-T 1:Stage • no no
blocked
• yes
_:691:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:103 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 3
_:691:31 Inverse-T 1:Effected by • no no
AR cycle 3
• yes
_:691:38 Inverse-T 1:Stage • no no
blocked
• yes

394 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:691:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:104 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: AR cycle>3
_:691:32 Inverse-T 1:Effected by • no no
AR cycle gr. 3
• yes
_:691:39 Inverse-T 1:Stage • no no
blocked
• yes
_:691:17 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:105 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: Cold load PU
_:691:33 Inverse-T 1:Effect. b. • no no
cold-load pickup
• yes
_:691:40 Inverse-T 1:Stage • no no
blocked
• yes
_:691:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:106 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: bin.input
_:691:34 Inverse-T 1:Effected by • no no
binary input
• yes
_:691:41 Inverse-T 1:Stage • no no
blocked
• yes
_:691:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:107 Inverse-T 1:Time dial 0.00 to 15.00 1.00

SIPROTEC 5, 7SJ82/7SJ85, Manual 395


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

6.3.5.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:691:81 Inverse-T 1:>Block stage SPS I
_:691:500 Inverse-T 1:>Block delay & op. SPS I
_:691:54 Inverse-T 1:Inactive SPS O
_:691:52 Inverse-T 1:Behavior ENS O
_:691:53 Inverse-T 1:Health ENS O
_:691:60 Inverse-T 1:Inrush blocks operate ACT O
_:691:59 Inverse-T 1:Disk emulation running SPS O
_:691:55 Inverse-T 1:Pickup ACD O
_:691:56 Inverse-T 1:Operate delay expired ACT O
_:691:57 Inverse-T 1:Operate ACT O

6.3.6 Stage with User-Defined Characteristic Curve

6.3.6.1 Description
This stage is only available in the advanced function type.
This stage is structured the same way as the Inverse-time overcurrent protection – advanced stage (see
chapter 6.3.5.1 Description ). The only differences are as follows:

• You can define the characteristic curve as desired.

• The pickup and dropout behaviors of this stage are determined by the standard parameter Threshold
and, if necessary, by an additional parameter Threshold (absolute).

User-Defined Characteristic Curve


With the user-defined characteristic curve, you can define the operate curve point by point using up to 30
value pairs of current and time. The device uses linear interpolation to calculate the characteristic curve from
these values. You can also define a dropout characteristic curve if you wish.

Pickup and Dropout Behaviors with the User-Defined Characteristic Curve


When the input variable exceeds the Threshold value by 1.1 times, the characteristic curve is processed. An
integrating method of measurement totalizes the weighted time. The weighted time results from the charac-
teristic curve. For this, the time that is associated with the present current value is determined from the char-
acteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls short of the pickup value by a factor of 1.045 (0.95 x 1.1 x Threshold value),
the dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via
setting parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout
according to the characteristic curve (reduction of totalized time depending on the characteristic curve). The
dropout according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The
weighted reduction of the time is initiated from 0.9 of the set threshold value.

396 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

[dwocpken-140611-02.tif, 2, en_US]

Figure 6-19 Pickup Behavior and Dropout Behavior when Using a User-Defined Characteristic Curve

NOTE

i The currents that are lower than the current value of the smallest characteristic-curve point do not extend
the operate time. The pickup characteristic runs in parallel to the current axis up to the smallest character-
istic-curve point. Currents that are larger than the current value of the largest characteristic-curve point do
not reduce the operate time. The pickup characteristic runs in parallel to the current axis from the largest
characteristic-curve point.

If you want to change the pickup threshold of the stage without changing all points of the characteristic curve,
you can use the additional Threshold (absolute) parameter.
You can set the Threshold (absolute) parameter to be greater than 1.1 times the Threshold value.
Then the stage behaviors are as follows:

• The stage picks up when the measured current value exceeds the Threshold (absolute) value.

• The stage starts dropout when the measured current value falls short of the Threshold (absolute)
value by 0.95 times.

• For measured current values lower than the Threshold (absolute) value, no pickup takes place and
consequently the characteristic curve is not processed.
If you set the Threshold (absolute) parameter to be less than 1.1 times the Threshold value, the
pickup and dropout behaviors are not affected by the Threshold (absolute) parameter.

6.3.6.2 Application and Setting Notes


This stage is structured the same way as the Inverse-time overcurrent protection – advanced stage. The
only differences are described in chapter 6.3.6.1 Description . This chapter provides only the application and
setting notes for setting characteristic curves and for setting the Threshold (absolute) parameter. You
can find more information on the other parameters of the stage in chapter 6.3.5.2 Application and Setting
Notes .

Parameter: Current/time value pairs (from the operate curve)


With these settings, you define the characteristic curve. Set a current/time value pair for each characteristic-
curve point. The setting depends on the characteristic curve you want to realize.

SIPROTEC 5, 7SJ82/7SJ85, Manual 397


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to shift the characteristic curve.
Set the time value in seconds. The characteristic curve is shifted via the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

Parameter: Time dial

• Default setting (_:101) Time dial = 1


With the Time dial parameter, you displace the characteristic curve in the time direction.
The set value for the Time dial parameter is derived from the time-grading schedule that has been prepared
for the electrical power system. Where no time grading and therefore no displacement of the characteristic
curve is required, leave the Time dial parameter at 1.

Parameter: Reset

• Default setting (_:110) Reset = disk emulation


With the Reset parameter, you define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation In the case of this setting, a dropout characteristic curve has to be set in
addition to the operate curve.
Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Select this setting if the dropout is not to be performed after disk emulation
but an instantaneous dropout is desired.

Parameter: Current/time value pairs (of the dropout characteristic curve)


With these settings, you define the characteristic curve. Set a current/time value pair for each characteristic-
curve point. The setting depends on the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to shift the characteristic curve.
Set the time value in seconds. The characteristic curve is shifted via the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

Parameter: 1-pole operate allowed

• Default setting (_:11) 1-pole operate allowed = no


The parameter must be set for the specific application.
Parameter Value Description
no The stage always operates 3-pole.
yes The stage operates phase-selectively. However, tripping by the device (gener-
ated in the trip logic of the Circuit-breaker function group) is always 3-pole
because the device does not support phase-selective tripping.

398 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Parameter: Threshold (absolute)

• Default setting (_:113) Threshold (absolute) = 0.000 A


With the Threshold (absolute) parameter, you define and change the absolute pickup threshold of the
stage without changing all points of the characteristic curve.
The parameter is only used for special applications. With the default setting, this functionality is disabled. You
can find more information in Pickup and Dropout Behaviors with the User-Defined Characteristic Curve ,
Page 396.

6.3.6.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 User curve #:Mode • off off
• on
• test
_:2 User curve #:Operate & • no no
flt.rec. blocked
• yes
_:11 User curve #:1-pole • no no
operate allowed
• yes
_:26 User curve #:Dynamic • no no
settings
• yes
_:27 User curve #:Blk. w. • no no
inrush curr. detect.
• yes
_:8 User curve #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:120 User curve #:I0 elimina- • no no
tion
• yes
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:113 User curve #:Threshold 1 A @ 100 Irated 0.000 A to 35.000 A 0.000 A
(absolute) 5 A @ 100 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.000 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.000 A
_:111 User curve #:Pickup 0.00 s to 60.00 s 0.00 s
delay
_:110 User curve #:Reset • instantaneous disk emulation
• disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
_:115 User curve #:Additional 0.00 s to 60.00 s 0.00 s
time delay

SIPROTEC 5, 7SJ82/7SJ85, Manual 399


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by • no no
AR off/n.ready
• yes
_:35 User curve #:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:29 User curve #:Effected by • no no
AR cycle 1
• yes
_:36 User curve #:Stage • no no
blocked
• yes
_:14 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:102 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:30 User curve #:Effected by • no no
AR cycle 2
• yes
_:37 User curve #:Stage • no no
blocked
• yes
_:15 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:103 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by • no no
AR cycle 3
• yes
_:38 User curve #:Stage • no no
blocked
• yes
_:16 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:104 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:32 User curve #:Effected by • no no
AR cycle gr. 3
• yes
_:39 User curve #:Stage • no no
blocked
• yes

400 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:17 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:105 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:33 User curve #:Effect. b. • no no
cold-load pickup
• yes
_:40 User curve #:Stage • no no
blocked
• yes
_:18 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:106 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: bin.input
_:34 User curve #:Effected by • no no
binary input
• yes
_:41 User curve #:Stage • no no
blocked
• yes
_:19 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:107 User curve #:Time dial 0.05 to 15.00 1.00

6.3.6.4 Information List

No. Information Data Class Type


(Type)
User curve #
_:81 User curve #:>Block stage SPS I
_:84 User curve #:>Activ. dyn. settings SPS I
_:500 User curve #:>Block delay & op. SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:60 User curve #:Inrush blocks operate ACT O
_:62 User curve #:Dyn.set. AR cycle1act. SPS O
_:63 User curve #:Dyn.set. AR cycle2act. SPS O
_:64 User curve #:Dyn.set. AR cycle3act. SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 401


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

No. Information Data Class Type


(Type)
_:65 User curve #:Dyn.set. ARcycl.>3act SPS O
_:66 User curve #:Dyn.set. CLP active SPS O
_:67 User curve #:Dyn.set. BI active SPS O
_:68 User curve #:Dyn. set. blks. pickup SPS O
_:59 User curve #:Disk emulation running SPS O
_:55 User curve #:Pickup ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O

6.3.7 Blocking of the Tripping by Device-Internal Inrush-Current Detection

6.3.7.1 Description
The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.
The following figure only shows the part of the stage (exemplified by definite-time overcurrent protection
stage 1) that illustrates the influence of the blocking. Only if the central function Inrush-current detection
(see chapter 12.10 Inrush-Current Detection) is in effect can the blocking be set.

[loocp3pha-210812-01.vsd, 1, en_US]

Figure 6-20 Part-Logic Diagram on the Influence of Inrush-Current Detection Exemplified by the 1st Defi-
nite-Time Overcurrent Protection Stage

6.3.7.2 Application and Setting Notes

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:661:27) Blk. w. inrush curr. detect. = no

402 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Parameter Value Description


no The transformer inrush-current detection does not affect the stage.
Select this setting in the following cases:

• In cases where the device is not used on transformers.

• In cases where the device is used on transformers and the threshold


value of the stage is set above the maximum inrush current of the
transformer. This, for example, applies to the high-current stage that is
set such according to the short-circuit voltage Vsc of the transformer
that it only picks up on faults from the high-voltage side. The trans-
former inrush current cannot become larger than the maximum trans-
mittable short-circuit current.
yes When the transformer inrush current detection detects an inrush current
that would lead to a tripping of the stage, the start of the time delay and
tripping of the stage are blocked.
Select this setting if the device is used on transformers and the threshold
value of the stage is set below the maximum inrush current of the trans-
former. This applies to the overcurrent-protection stage, which is used as a
backup stage with grading time for faults on the undervoltage side of the
transformer.

6.3.8 Influence of Other Functions via Dynamic Settings

6.3.8.1 Description
The parameters Threshold and Operate delay used for tripping are so-called dynamic settings.
Depending on other functions, the settings of these parameters can be changed dynamically (see
Figure 6-21). Depending on other functions, the stage can also be blocked dynamically. This functionality is
only available in function type Advanced.

SIPROTEC 5, 7SJ82/7SJ85, Manual 403


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

[loocp3dpa-030311-01.vsd, 2, en_US]

Figure 6-21 Principle of the Dynamic Settings Exemplified by 1st Definite-Time Overcurrent Protection
Stage

If available in the device, the following functionalities can affect the overcurrent-protection stages:
Functionalities Priority
Automatic reclosing (AREC) Priority 1
Cold-load pickup detection Priority 2
Binary input signal Priority 3

These functionalities generate signals that change the settings of the dynamic settings of the overcurrent-
protection stage or block it, if required. In the latter case, the settings of the Threshold and Operate
delay parameters are of no relevance. Within the overcurrent-protection stage, each of these signals is
provided with a configuration parameter Influence of function ... and its own dynamic settings
(Operate delay and Threshold). The configuration settings are used to set whether the signal shall be
active or not, this means whether the dynamic settings shall be activated or not. If one of these signals (for
example, signal function x) becomes active and is to take effect, these settings become dynamic, that is,
instantly active. This means that the setting assigned to the signal replaces the standard setting. If the signal
becomes inactive, the standard settings apply again. The activation of the dynamic settings is reported.

404 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Where several signals are active in parallel, the priority specified above shall apply. This means that a signal
with priority 2 precedes that of priority 3. The settings assigned to signal 2 become active.
The functionality of the dynamic settings can be disabled. In this case, the settings assigned to the signals are
not visible and are without effect.

Link to the Device-Internal Function Automatic Reclosing (Advanced Stage)

[loocp3awe-040311-01, 1, en_US]

Figure 6-22 Influence of the AREC Signals on the Overcurrent-Protection Stage

SIPROTEC 5, 7SJ82/7SJ85, Manual 405


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

Several AREC signals can affect the setting for the Threshold and Operate delay parameters of the
protection stage and its blocking.

• AREC is ready for reclosing 1 (= Automatic reclosing cycle 1)

• AREC is ready for reclosing 2 (= Automatic reclosing cycle 2)

• AREC is ready for reclosing 3 (= Automatic reclosing cycle 3)

• AREC is ready for reclosing 4 (= Automatic reclosing cycle >3)


The following signal can only block the protection stage:

• AREC is not ready or switched off (= Automatic reclosing off / not ready)
This means that if the AREC is ready and the protection stage is in the idle state, the settings for
AREC cycle 1 are active and not the standard settings. The standard settings are active in the case of AREC
off/not ready.
The influence can be activated for each signal individually. You also have to set the Threshold and Operate
delay or Stage blocked parameters, which take effect when the signal is active.
The way AREC signals are generated is described in chapter 6.46.1 Overview of Functions.

Link to the Device-Internal Function Cold-Load Pickup Detection (Advanced Stage)

[loocp3kal-030311-01.vsd, 1, en_US]

Figure 6-23 Influence of the Cold-Load Pickup Detection on the Overcurrent-Protection Stage

In the case of cold-load pickup, you have the option to change the settings for the Threshold and Operate
delay parameters of the protection level. You can also block the level. To do so, you must activate the influ-
ence of the cold-load pickup. You also have to set the Threshold and Operate delay or assign settings to
Stage blocked, which take effect when the signal is active.
The way signals are generated Cold-load pickup is described in chapter 5.8.1 Overview of Functions.

Link to an External Function via a Binary Input Signal (Advanced Stage)

[loocp3bin-030311-01.vsd, 1, en_US]

Figure 6-24 Influence of the Binary Input on the Overcurrent-Protection Stage

You can use the binary input signal >Activ. dyn. settings to change the settings for the Threshold
and the Operate delay parameters of the protection stage. You can also block the level. To do so, you must
activate the influence of the binary input. You also have to set the Threshold and Operate delay or
assign settings to Stage blocked, which take effect when the signal is active.

406 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.3 Overcurrent Protection, Phases

6.3.8.2 Application and Setting Notes (Advanced Stage)

Parameter: Dynamic settings

• Default setting (_:661:26) Dynamic settings = no

Parameter Value Description


no The influence on the overcurrent-protection stage by device-internal or
external functions is not necessary.
yes If a device-internal function (automatic reclosing function or cold-load
pickup detection) or an external function should affect the overcurrent-
protection stage (such as change the setting of the threshold value or time
delay, blocking of the stage), the setting must be changed to yes.
This makes the configuration parameters Influence of function...
as well as the dynamic settings Threshold, Operate delay and Stage
blocked of the stage visible and enables the settings to be set for the
specific influence.

Influence of AREC
The example of how the overcurrent stage (1st stage) can be used as a fast stage before automatic reclosing
describes the influence exerted by AREC.
The setting of the overcurrent stage (1st stage) results from the time-grading schedule. Additionally, it is to be
used as fast stage before an automatic reclosing. Because a fast disconnection of the short-circuit current
takes priority over the selectivity prior to reclosing, the tripping delay can be set to 0 or a very small value. To
achieve the selectivity, the final disconnection must be done with the grading time.
AREC is set to 2 reclosings. A secondary Threshold of 1.5 A and a Operate delay of 600 ms are
assumed (according to the time-grading schedule) for the overcurrent-protection stage. The standard settings
of the stage are set to these values.
To realize the application, the configuration settings Effected by AR cycle 1 and Effected by AR
cycle 2 are changed in the example to yes (= influenced). This activates the AR cycle 1 and AR cycle
2 input signals within the stage. When they become active, they switch to the assigned dynamic settings.
The two dynamic settings Operate delay assigned to these input signals (sources of influence) are set to
the time delay 0 (instantaneous tripping). The two dynamic settings Threshold assigned to these input
signals are set to the normal threshold value of 1.5 A.
If the threshold value (1.5 A) is exceeded before AREC 1 and AREC 2, the overcurrent-protection stage trips
instantaneously. If the fault still exists after AREC 2 (unsuccessful AREC), the stage trips with the time delay of
600 ms according to the time-grading schedule.

Influence of External Devices


The influence of an external device can also be configured. The above is an example of how the overcurrent-
protection stage (1st stage) can be used as a fast stage before automatic reclosing, in which case the AREC
function is performed by an external device.
To realize the application, the configuration setting Effected by binary input must be changed to yes
(= influenced). This activates the >Activ. dyn. settings input signal within the stage. When the input
signal becomes active, it switches to the assigned dynamic settings. The external device must provide the
Cycle 1 and Cycle 2 signals or, alternatively, the AR ready signal. The signals must be connected with
the binary input signal >Activ. dyn. settings.
The dynamic setting Operate delay, which is assigned to the input signal (source of influence) >Activ.
dyn. settings, is set to the time delay 0 (instantaneous tripping). The dynamic setting Threshold
assigned to this input signal is set to the normal threshold value of 1.5 A.
If the threshold value (1.5 A) is exceeded before AREC 1 and AREC 2, the overcurrent-protection stage trips
instantaneously. If the fault still exists after AREC 2 (unsuccessful AREC), the stage trips with the time delay of
600 ms according to the time-grading schedule.

SIPROTEC 5, 7SJ82/7SJ85, Manual 407


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

6.4 Voltage-Dependent Overcurrent Protection, Phases

6.4.1 Overview of Functions

The Voltage-dependent overcurrent protection (ANSI 51V) function:

• Detects short circuits affecting electric equipment

• Can be used for special network conditions where the overcurrent pickup level should be decreased
depending on the fault voltage

• Can be used for generators where the excitation voltage is derived from the machine terminals and the
overcurrent pickup should be kept depending on the fault voltages

6.4.2 Structure of the Function

The Voltage-dependent overcurrent protection function is used in protection function groups with 3-phase
current and voltage measurement.
The function Voltage-dependent overcurrent protection comes with the following factory-set stages:

• Inverse-time overcurrent protection, voltage-dependent stage

• Definite-time overcurrent protection, undervoltage seal-in stage


In this function, the following stages can operate simultaneously:

• A maximum of 2 inverse-time overcurrent protection, voltage-dependent stages

• A maximum of 2 inverse-time overcurrent protection, voltage-released stages

• A maximum of 2 definite-time overcurrent protection, undervoltage seal-in stages

• A maximum of 2 definite-time overcurrent protection, voltage-released undervoltage seal-in stages

[dw_stuvol_release, 3, en_US]

Figure 6-25 Structure/Embedding of the Function

408 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

6.4.3 Stage with Inverse-Time Overcurrent Protection, Voltage-Dependent

6.4.3.1 Description

Logic of the Stage

[lovoldep-210713-01.tif, 2, en_US]

Figure 6-26 Logic Diagram of the Inverse-Time Overcurrent Protection, Voltage-Dependent

Method of Measurement
You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 409


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

• Measurement of the fundamental comp.:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Voltage-Dependent Pickup Threshold


The pickup threshold of the overcurrent stage depends on the voltage magnitude. A lower voltage decreases
the current pickup value (see Figure 6-27). In the range between V/Vrated = 1.00 to 0.25 a linear, directly
proportional dependence is realized.

[dwvolpic-220713-01.tif, 1, en_US]

Figure 6-27 Voltage Influence of the Pickup Threshold

With:
V = Measured phase-to-phase voltage
Vrated = Rated voltage (parameter Rated voltage in the function block General of the protec-
tion function group)
PU sett. = Pickup threshold setting (parameter address: _11491:3)
PU(V) = Applied pickup threshold according to the voltage influence

The minimum current pickup threshold value is 0.03 * Irated. This value cannot be decreased any further even
not by voltage-dependent pickup threshold factor.
Decreasing the pickup threshold is carried out phase-selectively. The assignment of voltages to current-
carrying phases is shown in Table 6-1.

Table 6-1 Controlling Voltages in Relation to the Fault Current

Current Controlling Voltage


IA VAB
IB VBC
IC VCA

Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI

When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results

410 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.

Influence On the Operate Curve


The current pickup threshold is decreased proportional to the voltage decrease. Consequently, for a constant
current I the I/Threshold-value ratio is increased and the operate time is reduced. Compared with the standard
curves represented in the Technical Data, the operate curve shifts to the left side as the voltage decreases.

Measuring-Voltage Failure Detection


In case of a measuring-voltage failure detection the input voltage value is automatically set to Vrated, so that
the pickup threshold factor will be 1.

Blocking of the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.

Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.3.7.1 Description .

6.4.3.2 Application and Setting Notes

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:11491:27) Blk. w. inrush curr. detect. = no

Parameter Value Description


no The transformer inrush-current detection does not affect the stage. Select
this setting in the following cases:

• In cases where the device is not used on transformers.


• In cases where the device is used on transformers and the threshold
value of the stage is set above the maximum inrush current of the
transformer. This applies, for example, to the high-current stage that is
set according to the short-circuit voltage uk of the transformer in such
a way that the stage only picks up on faults from the high-voltage side.
The transformer-inrush current cannot become larger than the
maximum transmittable short-circuit current.
yes When the transformer inrush-current detection detects an inrush current
that would lead to a tripping of the stage, the start of the time delay and
tripping of the stage are blocked.
Select this setting if the device is used on transformers and the threshold
value of the stage is set below the maximum inrush current of the trans-
former. This applies to the overcurrent-protection stage, which is used as a
backup stage with grading time for faults on the undervoltage side of the
transformer.

SIPROTEC 5, 7SJ82/7SJ85, Manual 411


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

Parameter: Method of measurement

• Recommended setting value (_:11491:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Threshold

• Default setting (_:11491:3) Threshold = 1.500 A


The recommended setting value of 1.500 A is suitable for most applications.
Set the Threshold and Type of character. curve parameters for the specific application.
The setting depends on the maximum occurring operating current. Pickup by overload must be excluded since
overcurrent protection operates with short tripping times as short-circuit protection and not as overload
protection.
Set the Threshold parameter for lines to approx.10 %, for transformers and motors to approx. 20 % above
the maximum expected load.
Note that a safety margin is set between pickup value and threshold value. The stage only picks up at approx.
10 % above the Threshold.

Parameter Type of character. curve

• Default setting (_:11491:101) Type of character. curve = IEC normal inverse


The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application.

Parameter: Reset

• Default setting (_:11491:102) Reset = disk emulation


The Reset parameter allows you to define whether the stage decreases according to the dropout character-
istic curve (behavior of a disk emulation = rotor disc) or instantaneously.
Parameter Value Description
disk emulation Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Select this setting if the dropout does not have to be performed after a disk
emulation and an instantaneous dropout is desired instead.

Parameter: Time dial

• Default setting (_:11491:103) Time dial = 1


You can use the Time dial parameter to displace the characteristic curve in the time direction.

412 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

The setting value for the Time dial parameter is derived from the time-grading chart that has been
prepared for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the param-
eter Time dial at 1 (default setting).

6.4.3.3 Settings

Addr. Parameter C Setting Options Default Setting


V-dependent 1
_:11491:1 V-dependent 1:Mode • off off
• on
• test
_:11491:2 V-dependent 1:Operate • no no
& flt.rec. blocked
• yes
_:11491:27 V-dependent 1:Blk. w. • no no
inrush curr. detect.
• yes
_:11491:8 V-dependent 1:Method • fundamental comp. fundamental
of measurement comp.
• RMS value
_:11491:3 V-dependent 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
1:Threshold 5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:11491:101 V-dependent 1:Type of
character. curve
_:11491:102 V-dependent 1:Reset • instantaneous disk emulation
• disk emulation
_:11491:103 V-dependent 1:Time dial 0.05 to 15.00 1.00

6.4.3.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
V-dependent 1
_:11491:81 V-dependent 1:>Block stage SPS I
_:11491:500 V-dependent 1:>Block delay & op. SPS I
_:11491:54 V-dependent 1:Inactive SPS O
_:11491:52 V-dependent 1:Behavior ENS O
_:11491:53 V-dependent 1:Health ENS O
_:11491:60 V-dependent 1:Inrush blocks operate ACT O
_:11491:59 V-dependent 1:Disk emulation running SPS O
_:11491:55 V-dependent 1:Pickup ACD O
_:11491:56 V-dependent 1:Operate delay expired ACT O
_:11491:57 V-dependent 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 413


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

6.4.4 Stage with Inverse-Time Overcurrent Protection, Voltage-Released

6.4.4.1 Description

Logic of the Stage

[lovolrel-210713-01.tif, 2, en_US]

Figure 6-28 Logic Diagram of the Inverse-Time Overcurrent Protection, Voltage-Released

This stage is structured in the same way as the Inverse-time overcurrent, voltage-dependent stage (see
chapter 6.4.3.1 Description). The only differences are the conditions for the pickup and the influence on the
operate curve.

414 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

Measuring-Element Release
When the controlling voltage drops below the setting Undervoltage threshold, the respective measuring
element is released.
The release of the measuring elements is carried out phase-selectively. The assignment of voltages to current-
carrying phases is shown in Figure 6-27.

Blocking of the Stage with Measuring-Voltage Failure


The stage can be blocked if a measuring-voltage failure occurs. In case of a blocking, the picked up stage is
reset. The following blocking options are available for the stage:

• From an internal source upon pickup of the Measuring-voltage failure detection function

• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker
The Blk. by meas.-volt. failure parameter can be set so that measuring-voltage failure detection
blocks the stage or does not block it.

6.4.4.2 Application and Setting Notes


This stage is structured in the same way as the Inverse-time overcurrent, voltage-dependent stage. The
only differences are the conditions for the pickup and the influence on the operate curve. This chapter only
provides the application and setting notes for the setting Blk. by meas.-volt. failure and Under-
voltage threshold. For guidance on the other parameters of this stage, refer to chapter 6.4.3.2 Applica-
tion and Setting Notes.

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:10) Blk. by meas.-volt. failure = yes


You can use the Blk. by meas.-volt. failure parameter to control the response of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal Measuring-voltage failure detection function is configured and switched on.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.

Parameter Value Description


no The overcurrent-protection stage is not blocked when a measuring-voltage
failure is detected.
yes The overcurrent-protection stage is blocked when a measuring-voltage
failure is detected. Siemens recommends using the default setting, as
correct operation of the stage cannot be guaranteed if a measuring-voltage
failure occurs.

Parameter: Undervoltage threshold

• Default setting (_:104) Undervoltage threshold = 75.0 V


When the controlling voltage is below the set value, the Inverse-time overcurrent protection stage is
released.
The parameter is set to a value just below the lowest phase-to-phase voltage admissible during operation, for
example, from 75 % to 80 % of Vrated.

SIPROTEC 5, 7SJ82/7SJ85, Manual 415


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

6.4.4.3 Settings

Addr. Parameter C Setting Options Default Setting


V-release #
_:1 V-release #:Mode • off off
• on
• test
_:2 V-release #:Operate & • no no
flt.rec. blocked
• yes
_:10 V-release #:Blk. by • no yes
meas.-volt. failure
• yes
_:27 V-release #:Blk. w. inrush • no no
curr. detect.
• yes
_:8 V-release #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:3 V-release #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:101 V-release #:Type of char- • ANSI long-time inv. IEC normal
acter. curve inverse
• ANSI short-time inv.
• ANSI extremely inv.
• ANSI very inverse
• ANSI normal inverse
• ANSI moderately inv.
• ANSI definite inverse
• IEC normal inverse
• IEC very inverse
• IEC extremely inv.
• IEC long-time inverse
_:102 V-release #:Reset • instantaneous disk emulation
• disk emulation
_:103 V-release #:Time dial 0.05 to 15.00 1.00
_:104 V-release #:Under- 0.300 V to 175.000 V 75.000 V
voltage threshold

6.4.4.4 Information List

No. Information Data Class Type


(Type)
V-release #
_:81 V-release #:>Block stage SPS I
_:500 V-release #:>Block delay & op. SPS I
_:54 V-release #:Inactive SPS O
_:52 V-release #:Behavior ENS O
_:53 V-release #:Health ENS O

416 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

No. Information Data Class Type


(Type)
_:60 V-release #:Inrush blocks operate ACT O
_:59 V-release #:Disk emulation running SPS O
_:55 V-release #:Pickup ACD O
_:56 V-release #:Operate delay expired ACT O
_:57 V-release #:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 417


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

6.4.5 Stage with Definite-Time Overcurrent Protection, Undervoltage Seal-In

6.4.5.1 Description

Logic of the Stage

[lo_Seal-in_20150215, 2, en_US]

Figure 6-29 Logic Diagram of the Definite-Time Overcurrent Protection, Undervoltage Seal-in

Undervoltage Seal-In
In generators where the excitation voltage is derived from the machine terminals, the short-circuit current
decreases quickly in the event of close-in faults (for example, in a generator or a generator-transformer
range). The current decreases to a value below the current threshold within a few seconds because of the
absence of the excitation voltage. To avoid a dropout of the relay, the positive-sequence voltages are used as
an additional criterion for detecting a short circuit.

418 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

The pickup signal is maintained for a settable seal-in time Duration of V-seal-in time, if the positive-
sequence voltage falls below a settable threshold V-seal-in threshold after an overcurrent pickup, even
if the current falls below the threshold again. If the voltage recovers before the seal-in time has elapsed, or if
the undervoltage seal-in is blocked via a binary input >Block V-seal-in, the signal Pickup I>+V-seal-
in drops out immediately.
You can switch off the undervoltage seal-in via the parameter State of V-seal-in.

Blocking of the Undervoltage Seal-in with Measuring-Voltage Failure


The Undervoltage seal-in can be blocked if a measuring-voltage failure occurs. In case of a blocking, the
pickup signal Pickup I>+V-seal-in drops out immediately. The following blocking options are available
for the Undervoltage seal-in:

• From an internal source upon pickup of the Measuring-voltage failure detection function.

• From an external source via the binary input signal >Open of the function block VT miniature CB, which
links in the tripping of the voltage-transformer circuit breaker.
The parameter Blk. by meas.-volt. failure can be used to control the measuring-voltage failure
detection. The Undervoltage seal-in remains unaffected if the parameter Blk. by meas.-volt.
failure is switched off.

6.4.5.2 Application and Setting Notes

Parameter: Operate & flt.rec. blocked

• Default setting (_:16951:2) Operate & flt.rec. blocked = no


With the parameter Operate & flt.rec. blocked, you can block the operate indication, the fault
recording, and the fault log.

Parameter: Threshold

• Default setting (_:16951:3) Threshold = 1.350 A


The setting is mainly determined by the maximum operating current.
Pickup by overload must be excluded since the protection may trip if a short operate delay time is set. Set the
Threshold parameter for generators to a value between 20 % and 30 %, for transformers and motors
approx. 40 % above the expected peak load.

Parameter: Operate delay

• Default setting (_:16951:6) Operate delay = 3.00 s


The parameter Operate delay must be coordinated with the time grading of the network protection to
guarantee the selectivity. Practical time delays are between 1 s to 2 s.

Parameter: Blk. by meas.-volt. failure

• Default setting (_:16951:10) Blk. by meas.-volt. failure = yes


With the parameter Blk. by meas.-volt. failure, you can activate (yes) or deactivate (no) the
blocking by the Measuring voltage failure detection function. The recommended setting is the default
setting.

Parameter: State of V-seal-in

• Default setting (_:16951:101) State of V-seal-in = off


With the parameter State of V-seal-in, the seal-in functionality can be activated (switched on). Siemens
recommends this setting if the excitation transformer is connected to the main lead of the generator.

SIPROTEC 5, 7SJ82/7SJ85, Manual 419


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

Parameter: V-seal-in threshold

• Default setting (_:16951:102) V-seal-in threshold = 46.2 V


The V-seal-in threshold (positive-sequence voltage) is set to a value below the lowest phase-to-phase
voltage admissible during an operation, for example 80 % of the rated voltage of a generator. The positive-
sequence voltage is evaluated. The practicable value for a voltage transformer with a rated secondary voltage
of 100 V is 46.2 V.
The following table shows an example of a specification:
Threshold 1.4 * Irated, Gen
Operate delay 3.00 s
Undervoltage seal-in 0.8 * Vrated, Gen
Duration of V-seal-in time 4.00 s
Dropout ratio 0.95
Rated current Irated, Gen 483 A Rated voltage Vrated, Gen 6.3 kV
Rated current Irated, VT, prim 500 A Rated voltage Vrated, VT, prim 6.3 kV
Rated current Irated, VT, sec 1A Rated voltage Vrated, VT, sec 100 V

The following secondary setting values result from this specification:

[fo_OCP_UVSI_threshold, 1, en_US]

[fo_OCP_UVSI_Seal-in, 1, en_US]

Parameter: Duration of V-seal-in time

• Default setting (_:16951:104) Duration of V-seal-in time = 4.00 s


The parameter Duration of V-seal-in time limits the pickup seal-in induced by an overcurrent or
undervoltage. The value must be set higher than the value of the parameter Operate delay. The difference
shall be greater than 0.5 s. In the default setting, a difference of 1 s is used.

6.4.5.3 Settings

Addr. Parameter C Setting Options Default Setting


V-seal-in 1
_:16951:1 V-seal-in 1:Mode • off off
• on
• test
_:16951:2 V-seal-in 1:Operate & • no no
flt.rec. blocked
• yes
_:16951:3 V-seal-in 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.350 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.75 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.350 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.75 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.350 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.750 A
_:16951:6 V-seal-in 1:Operate delay 0.00 s to 60.00 s 3.00 s

420 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:16951:10 V-seal-in 1:Blk. by meas.- • no yes
volt. failure
• yes
_:16951:101 V-seal-in 1:State of V- • off off
seal-in
• on
_:16951:102 V-seal-in 1:V-seal-in 0.300 V to 175.000 V 46.200 V
threshold
_:16951:104 V-seal-in 1:Duration of V- 0.10 s to 60.00 s 4.00 s
seal-in time

6.4.5.4 Information List

No. Information Data Class Type


(Type)
V-seal-in 1
_:16951:81 V-seal-in 1:>Block stage SPS I
_:16951:500 V-seal-in 1:>Block V-seal-in SPS I
_:16951:52 V-seal-in 1:Behavior ENS O
_:16951:53 V-seal-in 1:Health ENS O
_:16951:54 V-seal-in 1:Inactive SPS O
_:16951:55 V-seal-in 1:Pickup ACD O
_:16951:300 V-seal-in 1:Pickup I>+V-seal-in SPS O
_:16951:56 V-seal-in 1:Operate delay expired ACT O
_:16951:57 V-seal-in 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 421


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

6.4.6 Stage with Definite-Time Overcurrent Protection, Voltage-Released


Undervoltage Seal-In

6.4.6.1 Description

Logic of the Stage

[lo_Seal-in_Rel20150215, 2, en_US]

Figure 6-30 Logic Diagram of the Definite-Time Overcurrent Protection, Voltage-Released Undervoltage
Seal-in, Part 1

Signal 4 in the following figure refers to Figure 6-30.

422 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

[lo_Seal-in_Rel2, 1, en_US]

Figure 6-31 Logic Diagram of the Definite-Time Overcurrent Protection, Voltage-Released Undervoltage
Seal-in, Part 2

Voltage Release
In addition to the current criterion with undervoltage seal-in, a voltage-released logic must be present to issue
the indication Pickup. The voltage-released logic monitors the negative-sequence voltage and phase-to-
phase voltages respectively for detecting unsymmetrical faults and symmetrical faults. With the voltage-
released logic, the setting value of the parameter Threshold can be reduced in a certain range and the relia-
bility and sensibility of this function can be improved correspondingly.

Undervoltage Seal-In
In generators where the excitation voltage is derived from the machine terminals, the short-circuit current
decreases quickly in the event of close-in faults (for example, in a generator or a generator-transformer
range). The current decreases to a value below the current threshold within a few seconds because of the
absence of the excitation voltage. To avoid a dropout of the relay, the positive-sequence voltages are used as
an additional criterion for detecting a short circuit.
The pickup signal is maintained for a settable seal-in time Duration of V-seal-in time, if the positive-
sequence voltage falls below a settable threshold V-seal-in threshold after an overcurrent pickup, even
if the current falls below the threshold again. If the voltage recovers before the seal-in time has elapsed, or if
the undervoltage seal-in is blocked via a binary input >Block V-seal-in, the signal Pickup I>+V-seal-
in drops out immediately.
You can switch off the undervoltage seal-in via the parameter State of V-seal-in.

Blocking of the Undervoltage Seal-in with Measuring-Voltage Failure


The Undervoltage seal-in can be blocked if a measuring-voltage failure occurs. In case of a blocking, the
pickup signal Pickup I>+V-seal-in drops out immediately. The following blocking options are available
for the Undervoltage seal-in:

• From an internal source upon pickup of the Measuring-voltage failure detection function.

• From an external source via the binary input signal >Open of the function block VT miniature CB, which
links in the tripping of the voltage-transformer circuit breaker.
The parameter Blk. by meas.-volt. failure can be used to control the measuring-voltage failure
detection. The Undervoltage seal-in remains unaffected if the parameter Blk. by meas.-volt.
failure is switched off.

6.4.6.2 Application and Setting Notes

Parameter: Operate & flt.rec. blocked

• Default setting (_:2) Operate & flt.rec. blocked = no


With the parameter Operate & flt.rec. blocked, you can block the operate indication, the fault
recording, and the fault log.

SIPROTEC 5, 7SJ82/7SJ85, Manual 423


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

Parameter: Threshold

• Default setting (_:3) Threshold = 1.350 A


The setting is mainly determined by the maximum operating current.
Pickup by overload must be excluded since the protection may trip if a short operate delay time is set. Set the
Threshold parameter for generators to a value between 20 % and 30 %, for transformers and motors
approx. 40 % above the expected peak load.

Parameter: Operate delay

• Default setting (_:6) Operate delay = 3.00 s


The parameter Operate delay must be coordinated with the time grading of the network protection to
guarantee the selectivity. Practical time delays are between 1 s to 2 s.

Parameter: Blk. by meas.-volt. failure

• Default setting (_:10) Blk. by meas.-volt. failure = yes


With the parameter Blk. by meas.-volt. failure, you can activate (yes) or deactivate (no) the
blocking by the Measuring voltage failure detection function. The recommended setting is the default
setting.

Parameter: State of V-seal-in

• Default setting (_:101) State of V-seal-in = off


With the parameter State of V-seal-in, the seal-in functionality can be activated (switched on). Siemens
recommends this setting if the excitation transformer is connected to the main lead of the generator.

Parameter: V-seal-in threshold

• Default setting (_:102) V-seal-in threshold = 46.2 V


The V-seal-in threshold (positive-sequence voltage) is set to a value below the lowest phase-to-phase
voltage admissible during an operation, for example 80 % of the rated voltage of a generator. The positive-
sequence voltage is evaluated. The practicable value for a voltage transformer with a rated secondary voltage
of 100 V is 46.2 V.
The following table shows an example of a specification:
Threshold 1.4 * Irated, Gen
Operate delay 3.00 s
Undervoltage seal-in 0.8 * Vrated, Gen
Duration of V-seal-in time 4.00 s
Dropout ratio 0.95
Rated current Irated, Gen 483 A Rated voltage Vrated, Gen 6.3 kV
Rated current Irated, VT, prim 500 A Rated voltage Vrated, VT, prim 6.3 kV
Rated current Irated, VT, sec 1A Rated voltage Vrated, VT, sec 100 V

The following secondary setting values result from this specification:

[fo_OCP_UVSI_threshold, 1, en_US]

[fo_OCP_UVSI_Seal-in, 1, en_US]

424 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

Parameter: Duration of V-seal-in time

• Default setting (_:104) Duration of V-seal-in time = 4.00 s


The parameter Duration of V-seal-in time limits the pickup seal-in induced by an overcurrent or
undervoltage. The value must be set higher than the value of the parameter Operate delay. The difference
shall be greater than 0.5 s. In the default setting, a difference of 1 s is used.

Parameter: Vph-ph< threshold

• Default setting (_:105) Vph-ph< threshold = 60.000 V


With the parameter Vph-ph< threshold, you can set the threshold at which the output signal Voltage
release is activated when the minimum phase-to-phase voltage falls below this threshold.

Parameter: V2> threshold

• Default setting (_:106) V2> threshold = 4.600 V


With the parameter V2> threshold, you can set the threshold at which the output signal Voltage
release is issued when V2 exceeds the threshold.

6.4.6.3 Settings

Addr. Parameter C Setting Options Default Setting


Vseal-in+Vrel#
_:1 Vseal-in+Vrel#:Mode • off off
• on
• test
_:2 Vseal-in+Vrel#:Operate • no no
& flt.rec. blocked
• yes
_:3 Vseal-in+Vrel#:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.350 A
5 A @ 100 Irated 0.150 A to 175.000 A 6.750 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.350 A
5 A @ 50 Irated 0.150 A to 175.000 A 6.750 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.350 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.750 A
_:6 Vseal-in+Vrel#:Operate 0.00 s to 60.00 s 3.00 s
delay
_:10 Vseal-in+Vrel#:Blk. by • no yes
meas.-volt. failure
• yes
_:101 Vseal-in+Vrel#:State of • off off
V-seal-in
• on
_:102 Vseal-in+Vrel#:V-seal-in 0.300 V to 175.000 V 46.200 V
threshold
_:104 Vseal-in+Vrel#:Duration 0.10 s to 60.00 s 4.00 s
of V-seal-in time
_:105 Vseal-in+Vrel#:Vph-ph< 0.300 V to 175.000 V 60.000 V
threshold
_:106 Vseal-in+Vrel#:V2> 0.300 V to 200.000 V 4.600 V
threshold

SIPROTEC 5, 7SJ82/7SJ85, Manual 425


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases

6.4.6.4 Information List

No. Information Data Class Type


(Type)
Vseal-in+Vrel#
_:81 Vseal-in+Vrel#:>Block stage SPS I
_:500 Vseal-in+Vrel#:>Block V-seal-in SPS I
_:52 Vseal-in+Vrel#:Behavior ENS O
_:53 Vseal-in+Vrel#:Health ENS O
_:54 Vseal-in+Vrel#:Inactive SPS O
_:55 Vseal-in+Vrel#:Pickup ACD O
_:300 Vseal-in+Vrel#:Pickup I>+V-seal-in SPS O
_:301 Vseal-in+Vrel#:Voltage release SPS O
_:56 Vseal-in+Vrel#:Operate delay expired ACT O
_:57 Vseal-in+Vrel#:Operate ACT O

426 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

6.5 Overcurrent Protection, Ground

6.5.1 Overview of Functions

The Overcurrent protection, ground function (ANSI 50N/51N):

• Detects short circuits in electrical equipment

• Can be used as backup overcurrent protection in addition to the main protection

6.5.2 Structure of the Function

The Overcurrent protection, ground function is used in protection function groups. 2 kinds of functions are
available for the 3-phase overcurrent protection:

• Overcurrent protection, ground – advanced (50N/51N OC-gnd-A)

• Overcurrent protection, ground – basic (50N/51N OC-gnd-B)


The function type Basic is provided for standard applications. The function type Advanced offers more func-
tionality and is provided for more complex applications.
Both function types are pre-configured by the manufacturer with 2 Definite-time overcurrent protection
stages and with 1 Inverse-time overcurrent protection stage.
In the function type Overcurrent protection, ground – advanced the following stages can be operated
simultaneously:

• Maximum of 3 stages Definite-time overcurrent protection – advanced

• 1 stage Inverse-time overcurrent protection – advanced

• 1 stage User-defined characteristic curve overcurrent protection


In the function type Overcurrent protection, ground – basic the following stages can be operated simultane-
ously:

• Maximum of 3 stages Definite-time overcurrent protection – basic

• 1 stage Inverse-time overcurrent protection – basic


The non-preconfigured stages are shown in gray in the following figures. Apart from the tripping delay charac-
teristic, the stages are identical in structure.
The measured-value selection (only advanced stage) is general functionality and has a uniform effect on the
stages (see Figure 6-32 and chapter 6.5.3.1 Description). This ensures that all stages of the function receive
the same measured current value.
The group-indication output logic generates the following group indications of the protection function by the
logical OR of the stage-selective indications:

• Pickup

• Operate

SIPROTEC 5, 7SJ82/7SJ85, Manual 427


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

[dwocpga2-060213-01.tif, 5, en_US]

Figure 6-32 Structure/Embedding of the Function Overcurrent Protection, Ground – Advanced

[dwocpgb1-060213-01.tif, 4, en_US]

Figure 6-33 Structure/Embedding of the Function Overcurrent Protection, Ground – Basic

If the following listed, device-internal functions are present in the device, these functions can influence the
pickup values and tripping delays of the stages or block the stages. The stage can also be affected by an
external source via a binary input signal.

• Automatic reclosing (AREC)

• Cold-load pickup detection

• Binary input signal


If the device is equipped with an Inrush-current detection function, the stages can be stabilized against trip-
ping due to transformer-inrush currents (available in both function types).

6.5.3 General Functionality

6.5.3.1 Description

Measured-Value Selection
The function provides the option to select between the values IN measured or 3I0 calculated.

428 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

[loMasValue-201507-01.vsd, 1, en_US]

Figure 6-34 Logic Diagram of Measured-Value Selection

Both options are only available for the current-transformer connection types 3-phase + IN and 3-phase +
IN-separate. For other connection types respectively, only one option is possible. If you select an option
that is not allowed, an inconsistency message is given.
Depending on the CT secondary rated current, the CT connection type, and the selected setting, the secondary
threshold setting range varies according to the following table.

Table 6-2 Threshold Setting Range

Connec- Measured CT Threshold Setting Threshold Setting Threshold Setting Threshold Setting
tion Value Terminal Range (rated I-sec.: Range (rated I-sec.: Range (rated I-sec.: Range (rated I-sec.:
Type Type ph = 1 A, IN = 1 A) ph = 1 A, IN = 5 A) ph = 5 A, IN = 1 A) ph = 5 A, IN = 5 A)
3I0 calcu- 4 * Protec- 0.010 A to 35.000 A N/A N/A 0.050 A to 175.00 A
lated tion
4 * Meas- 0.001 A to 1.600 A N/A N/A 0.002 A to 8.000 A
3ph + IN

urement
IN meas- 4 * Protec- 0.010 A to 35.000 A N/A N/A 0.050 A to 175.00 A
ured tion
4 * Meas- 0.001 A to 1.600 A N/A N/A 0.002 A to 8.000 A
urement
3I0 calcu- 4 * Protec- 0.010 A to 35.000 A 0.010 A to 35.000 A 0.050 A to 175.00 A 0.050 A to 175.00 A
lated tion
3 * Protec- 0.010 A to 35.000 A 0.010 A to 35.000 A 0.050 A to 175.00 A 0.050 A to 175.00 A
tion, 1 *
sen.
3ph + IN-separate

4 * Meas- 0.001 A to 1.600 A 0.001 A to 1.600 A 0.002 A to 8.000 A 0.002 A to 8.000 A


urement
IN meas- 4 * Protec- 0.010 A to 35.000 A 0.050 A to 175.00 A 0.010 A to 35.000 A 0.050 A to 175.00 A
ured tion
3 * Protec- 0.001 A to 1.600 A 0.002 A to 8.000 A 0.001 A to 1.600 A 0.002 A to 8.000 A
tion, 1 *
sen.
4 * Meas- 0.001 A to 1.600 A 0.002 A to 8.000 A 0.001 A to 1.600 A 0.002 A to 8.000 A
urement

6.5.3.2 Application and Setting Notes

Parameter: Measured value

• Recommended setting value Measured value = IN Measured


This parameter is not available in the basic function.

SIPROTEC 5, 7SJ82/7SJ85, Manual 429


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Parameter Value Description


IN Measured The function operates with the measured ground current IN. This is the
recommended setting unless there is a specific reason to use the calculated
zero-sequence current 3I0.
3I0 Calculated The function operates with the calculated zero sequence current 3I0. This
setting option can be used when applying a redundant 50N/51N function for
safety reasons.

6.5.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:9 General:Measured • 3I0 calculated IN measured
value
• IN measured

430 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

6.5.4 Stage with Definite-Time Characteristic Curve

6.5.4.1 Description

Logic of the Basic Stage

[loocpgb1-060213-01.tif, 2, en_US]

Figure 6-35 Logic Diagram of the Definite-Time Overcurrent Protection (Ground) – Basic

SIPROTEC 5, 7SJ82/7SJ85, Manual 431


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Logic of the Advanced Stage

[loocpgn1-291112-01.tif, 2, en_US]

Figure 6-36 Logic Diagram of the Definite-Time Overcurrent Protection (Ground) – Advanced

Method of Measurement (Basic and Advanced Stage)


You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value.

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

432 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Dropout Delay (Advanced Stage)


If the value falls below the dropout threshold, the dropout can be delayed. The pickup is maintained for the
specified time. The tripping delay continues to run. If the time delay expires while the pickup is still main-
tained, the stage operates.

Blocking of the Stage (Basic and Advanced Stage)


The following blockings reset the picked up stage completely:

• Via the binary input signal >Block stage from an external or internal source

• Via the functionality of the dynamic settings (see chapter Influence of other functions via
dynamic settings and section 6.5.8.1 Description ).

Blocking of the Time Delay (Basic and Advanced Stage)


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.

Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.5.7.1 Description.

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can influence the overcurrent-protection stages:

• Automatic reclosing

• Cold-load pickup detection

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.5.8.1 Description .

6.5.4.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:751:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

SIPROTEC 5, 7SJ82/7SJ85, Manual 433


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Parameter: Threshold, Operate delay

• Default setting (_:751:3) Threshold = 1.20 A (for the first stage)

• Default setting (_:751:6) Operate delay = 0.300 s (for the first stage)
Set the Threshold and Operate delay parameters for the specific application.
The following details apply to a 2-stage characteristic curve (1st stage = definite-time overcurrent protection
stage and 2nd stage = high-current stage).

1st stage (overcurrent stage):


The setting depends on the minimal occurring ground-fault current. This must be determined.
The Operate delay to be set is derived from the time-grading schedule that has been prepared for the
system.

2nd stage (high-current stage):


This tripping stage can also be used for current grading. This applies in the case of very long lines with low
source impedance or ahead of high reactances (for example, transformers, shunt reactors). Set the
Threshold parameter to ensure that the stage does not pick up in case of a short-circuit at the end of the
line.
Set the Operate delay parameter to 0 or to a low value.
Siemens recommends that the threshold values be determined with a system analysis. The following example
illustrates the principle of grading with a current threshold on a long line.

EXAMPLE
High-current stage: 110-kV overhead line, 150 mm2 cross-section
s (length) = 60 km
ZL/s = 0.46 Ω/km
Ratio of zero-sequence impedance and positive-sequence impedance of the line: ZL0/ZL1 = 4
Short-circuit power at the beginning of the line:
Ssc' = 2.5 GVA
Ratio of zero-sequence impedance and positive-sequence impedance of the source impedance at the
beginning of the line: ZP0/ZP1 = 2
Current transformer = 600 A/5 A

Resulting in the following values for the line impedance ZL and the source impedance ZP:

[fo_OCP002_030311, 1, en_US]

[fo_OCP003_030311, 1, en_US]

The 1-pole short-circuit current at the end of the line is IscG end:

[fo_ocp005_030311, 1, en_US]

The settings in primary and secondary values result in the following setting values which include a safety
margin of 10 %:

434 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

[foocpgr4-030311-01.tif, 3, en_US]

In case of short-circuit currents exceeding 1246 A (primary) or 10.39 A (secondary) there is a short-circuit on
the line to be protected. The overcurrent protection can cut off this short circuit immediately.
Note: The amounts in the calculation example are accurate enough for overhead lines. If the source impe-
dance, line impedance and zero-sequence impedance have very different angles, you have use complex
numbers to calculate the Threshold.

Parameter: Dropout delay

• Recommended setting value (_:751:101) Dropout delay = 0


This parameter is not visible in the basic stage.
Siemens recommends using the default setting 0 since the dropout of a protection stage must be done as fast
as possible.
You can use the Dropout delay parameter ≠ 0 to obtain a uniform dropout behavior if you use it together
with an electromechanical relay. This is required for time grading. The dropout time of the electromechanical
relay must be known for this purpose. Subtract the dropout time of your own device (see Technical Data) and
set the result.

Parameter: Dropout ratio

• Recommended setting value (_:751:4) Dropout ratio = 0.95


This parameter is not visible in the basic stage.
The recommended set value of 0.95 is appropriate for most applications.
To achieve high-precision measurements, the setting value of the parameter Dropout ratio can be
reduced, for example, to 0.98. If you expect highly fluctuating measurands at the response threshold, you
can increase the setting value of the parameter Dropout ratio. This avoids chattering of the tripping stage.

6.5.4.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:751:1 Definite-T 1:Mode • off off
• on
• test
_:751:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:751:26 Definite-T 1:Dynamic • no no
settings
• yes
_:751:27 Definite-T 1:Blk. w. • no no
inrush curr. detect.
• yes
_:751:8 Definite-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value

SIPROTEC 5, 7SJ82/7SJ85, Manual 435


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:751:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:4 Definite-T 1:Dropout 0.90 to 0.99 0.95
ratio
_:751:101 Definite-T 1:Dropout 0.00 s to 60.00 s 0.00 s
delay
_:751:6 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.s: AR off/n.rdy
_:751:28 Definite-T 1:Effect. by AR • no no
off/n.ready
• yes
_:751:35 Definite-T 1:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:751:29 Definite-T 1:Effected by • no no
AR cycle 1
• yes
_:751:36 Definite-T 1:Stage • no no
blocked
• yes
_:751:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:20 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: AR cycle 2
_:751:30 Definite-T 1:Effected by • no no
AR cycle 2
• yes
_:751:37 Definite-T 1:Stage • no no
blocked
• yes
_:751:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:21 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: AR cycle 3
_:751:31 Definite-T 1:Effected by • no no
AR cycle 3
• yes

436 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:751:38 Definite-T 1:Stage • no no
blocked
• yes
_:751:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:22 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.s: AR cycle>3
_:751:32 Definite-T 1:Effected by • no no
AR cycle gr. 3
• yes
_:751:39 Definite-T 1:Stage • no no
blocked
• yes
_:751:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:23 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.s: Cold load PU
_:751:33 Definite-T 1:Effect. b. • no no
cold-load pickup
• yes
_:751:40 Definite-T 1:Stage • no no
blocked
• yes
_:751:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:24 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: bin.input
_:751:34 Definite-T 1:Effected by • no no
binary input
• yes
_:751:41 Definite-T 1:Stage • no no
blocked
• yes
_:751:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A

SIPROTEC 5, 7SJ82/7SJ85, Manual 437


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:751:25 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay

6.5.4.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:751:81 Definite-T 1:>Block stage SPS I
_:751:84 Definite-T 1:>Activ. dyn. settings SPS I
_:751:500 Definite-T 1:>Block delay & op. SPS I
_:751:54 Definite-T 1:Inactive SPS O
_:751:52 Definite-T 1:Behavior ENS O
_:751:53 Definite-T 1:Health ENS O
_:751:60 Definite-T 1:Inrush blocks operate ACT O
_:751:55 Definite-T 1:Pickup ACD O
_:751:56 Definite-T 1:Operate delay expired ACT O
_:751:57 Definite-T 1:Operate ACT O

438 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

6.5.5 Stage with Inverse-Time Characteristic Curve

6.5.5.1 Description

Logic of the Basic Stage

[lo_ocp_gr2, 4, en_US]

Figure 6-37 Logic Diagram of the Inverse-Time Overcurrent Protection (Ground) – Basic

SIPROTEC 5, 7SJ82/7SJ85, Manual 439


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Logic of the Advanced Stage

[loocpgn2-291112-01.tif, 3, en_US]

Figure 6-38 Logic Diagram of the Inverse-Time Overcurrent Protection (Ground) – Advanced

Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI (Basic and
Advanced Stage)

When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout

440 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.

Minimum Time of the Curve (Advanced Stage)


With the parameter Min. time of the curve, you define the minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time.

[Dwocpgr3Mi_20140716-01, 1, en_US]

Figure 6-39 Minimum Operating Time of the Curve

Additional Time Delay (Advanced Stage)


With the parameter Additional time delay, you define a definite-time delay in addition to the inverse-
time delay. With this setting, the whole curve is shifted on the time axis by this additional definite time.

Method of Measurement (Basic and Advanced Stage)


You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value.

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Blocking of the Stage (Basic and Advanced Stage)


The following blockings reset the picked up stage completely:

• Via the binary input signal >Block stage from an external or internal source

• Via the functionality of the dynamic settings (see subtitle Influence of other functions via dynamic
settings and chapter 6.5.8.1 Description ).

Blocking of the Time Delay (Basic and Advanced Stage)


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.

SIPROTEC 5, 7SJ82/7SJ85, Manual 441


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.5.7.1 Description.

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can influence the overcurrent-protection stages:

• Automatic reclosing

• Cold-load pickup detection

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.5.8.1 Description .

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can influence the overcurrent-protection stages:

• Automatic reclosing

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.5.8.1 Description .

6.5.5.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:781:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Type of character. curve

• Default setting (_:781:108) Type of character. curve = IEC normal inverse


The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application. For more information about the parameter
Type of character. curve, refer to chapter12.7.2 Stage with Inverse-Time Characteristic Curve.

Parameter: Min. time of the curve

• Default setting (_:781:113) Min. time of the curve = 0.00 s


This parameter is only available in the advanced stage.

442 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

With the Min. time of the curve parameter, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time. If the
setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommends keeping the default setting of 0 s.

NOTE

i If the set value is smaller than the smallest possible time delay of the inverse-time characteristic curve, the
parameter has no influence on the delay time.

Parameter: Additional time delay

• Recommended setting value (_:781:115) Additional time delay = 0.00 s


With the Additional time delay parameter, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic
curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommend keeping the default setting of 0 s.

Parameter: Threshold

• Default setting (_:781:3) Threshold = 1.20 A


The setting depends on the minimal occurring ground-fault current. This must be determined.

Parameter: Time dial

• Default setting (_:781:101) Time dial = 1


With the Time dial parameter, you displace the characteristic curve in the time direction.
The set value for the Time dial parameter is derived from the time-grading schedule that has been prepared
for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the Time
dial parameter at 1.

Parameter: Reset

• Default setting (_:781:109) Reset = disk emulation


With the Reset parameter, you define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Select this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.

6.5.5.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:781:1 Inverse-T 1:Mode • off off
• on
• test

SIPROTEC 5, 7SJ82/7SJ85, Manual 443


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:781:2 Inverse-T 1:Operate & • no no
flt.rec. blocked
• yes
_:781:26 Inverse-T 1:Dynamic • no no
settings
• yes
_:781:27 Inverse-T 1:Blk. w. inrush • no no
curr. detect.
• yes
_:781:8 Inverse-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:781:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:108 Inverse-T 1:Type of char-
acter. curve
_:781:113 Inverse-T 1:Min. time of 0.00 s to 1.00 s 0.00 s
the curve
_:781:109 Inverse-T 1:Reset • instantaneous disk emulation
• disk emulation
_:781:101 Inverse-T 1:Time dial 0.00 to 15.00 1.00
_:781:115 Inverse-T 1:Additional 0.00 s to 60.00 s 0.00 s
time delay
Dyn.s: AR off/n.rdy
_:781:28 Inverse-T 1:Effect. by AR • no no
off/n.ready
• yes
_:781:35 Inverse-T 1:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:781:29 Inverse-T 1:Effected by • no no
AR cycle 1
• yes
_:781:36 Inverse-T 1:Stage • no no
blocked
• yes
_:781:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:102 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 2
_:781:30 Inverse-T 1:Effected by • no no
AR cycle 2
• yes
_:781:37 Inverse-T 1:Stage • no no
blocked
• yes

444 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:781:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:103 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 3
_:781:31 Inverse-T 1:Effected by • no no
AR cycle 3
• yes
_:781:38 Inverse-T 1:Stage • no no
blocked
• yes
_:781:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:104 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: AR cycle>3
_:781:32 Inverse-T 1:Effected by • no no
AR cycle gr. 3
• yes
_:781:39 Inverse-T 1:Stage • no no
blocked
• yes
_:781:17 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:105 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: Cold load PU
_:781:33 Inverse-T 1:Effect. b. • no no
cold-load pickup
• yes
_:781:40 Inverse-T 1:Stage • no no
blocked
• yes
_:781:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:106 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: bin.input
_:781:34 Inverse-T 1:Effected by • no no
binary input
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 445


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:781:41 Inverse-T 1:Stage • no no
blocked
• yes
_:781:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:107 Inverse-T 1:Time dial 0.00 to 15.00 1.00

6.5.5.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:781:81 Inverse-T 1:>Block stage SPS I
_:781:500 Inverse-T 1:>Block delay & op. SPS I
_:781:54 Inverse-T 1:Inactive SPS O
_:781:52 Inverse-T 1:Behavior ENS O
_:781:53 Inverse-T 1:Health ENS O
_:781:60 Inverse-T 1:Inrush blocks operate ACT O
_:781:59 Inverse-T 1:Disk emulation running SPS O
_:781:55 Inverse-T 1:Pickup ACD O
_:781:56 Inverse-T 1:Operate delay expired ACT O
_:781:57 Inverse-T 1:Operate ACT O

6.5.6 Stage with User-Defined Characteristic Curve

6.5.6.1 Description
This stage is only available in the advanced function type.
This stage is structured the same way as the Inverse-time overcurrent protection – advanced stage (see
chapter 6.5.5.1 Description ). The only differences are as follows:

• You can define the characteristic curve as desired.

• The pickup and dropout behaviors of this stage are determined by the standard parameter Threshold
and, if necessary, by an additional parameter Threshold (absolute).

User-Defined Characteristic Curve


With the user-defined characteristic curve, you can define the operate curve point by point using up to 30
value pairs of current and time. The device uses linear interpolation to calculate the characteristic curve from
these values. You can also define a dropout characteristic curve if you wish.

Pickup and Dropout Behaviors with the User-Defined Characteristic Curve


When the input variable exceeds the Threshold value by 1.1 times, the characteristic curve is processed. An
integrating method of measurement totalizes the weighted time. The weighted time results from the charac-

446 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

teristic curve. For this, the time that is associated with the present current value is determined from the char-
acteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls short of the pickup value by a factor of 1.045 (0.95 x 1.1 x Threshold value),
the dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via
setting parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout
according to the characteristic curve (reduction of totalized time depending on the characteristic curve). The
dropout according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The
weighted reduction of the time is initiated from 0.9 of the set threshold value.

[dwocpken-140611-02.tif, 2, en_US]

Figure 6-40 Pickup Behavior and Dropout Behavior when Using a User-Defined Characteristic Curve

NOTE

i The currents that are lower than the current value of the smallest characteristic-curve point do not extend
the operate time. The pickup characteristic runs in parallel to the current axis up to the smallest character-
istic-curve point. Currents that are larger than the current value of the largest characteristic-curve point do
not reduce the operate time. The pickup characteristic runs in parallel to the current axis from the largest
characteristic-curve point.

If you want to change the pickup threshold of the stage without changing all points of the characteristic curve,
you can use the additional Threshold (absolute) parameter.
You can set the Threshold (absolute) parameter to be greater than 1.1 times the Threshold value.
Then the stage behaviors are as follows:

• The stage picks up when the measured current value exceeds the Threshold (absolute) value.

• The stage starts dropout when the measured current value falls short of the Threshold (absolute)
value by 0.95 times.

• For measured current values lower than the Threshold (absolute) value, no pickup takes place and
consequently the characteristic curve is not processed.
If you set the Threshold (absolute) parameter to be less than 1.1 times the Threshold value, the
pickup and dropout behaviors are not affected by the Threshold (absolute) parameter.

SIPROTEC 5, 7SJ82/7SJ85, Manual 447


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

6.5.6.2 Application and Setting Notes


This stage is structured the same way as the Inverse-time overcurrent protection – advanced stage. The
only differences are described in chapter 6.5.6.1 Description . This chapter provides only the application and
setting notes for setting characteristic curves and for setting the Threshold (absolute) parameter. You
can find more information on the other parameters of the stage in chapter 6.5.5.2 Application and Setting
Notes .

Parameter: Current/time value pairs (from the operate curve)


With these settings, you define the characteristic curve. Set a current/time value pair for each characteristic-
curve point. The setting depends on the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to shift the characteristic curve.
Set the time value in seconds. The characteristic curve is shifted via the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

Parameter: Time dial

• Default setting (_:101) Time dial = 1


With the Time dial parameter, you displace the characteristic curve in the time direction.
The set value for the Time dial parameter is derived from the time-grading schedule that has been prepared
for the electrical power system. Where no time grading and therefore no displacement of the characteristic
curve is required, leave the Time dial parameter at 1.

Parameter: Reset

• Default setting (_:110) Reset = disk emulation


With the Reset parameter, you define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation In the case of this setting, a dropout characteristic curve has to be set in
addition to the operate curve.
Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Select this setting if the dropout is not to be performed after disk emulation
but an instantaneous dropout is desired.

Parameter: Current/time value pairs (of the dropout characteristic curve)


With these settings, you define the characteristic curve. Set a current/time value pair for each characteristic-
curve point. The setting depends on the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to shift the characteristic curve.
Set the time value in seconds. The characteristic curve is shifted via the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

448 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Parameter: Threshold (absolute)

• Default setting (_:113) Threshold (absolute) = 0.000 A


With the Threshold (absolute) parameter, you define and change the absolute pickup threshold of the
stage without changing all points of the characteristic curve.
The parameter is only used for special applications. With the default setting, this functionality is disabled. You
can find more information in Pickup and Dropout Behaviors with the User-Defined Characteristic Curve ,
Page 446.

6.5.6.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 User curve #:Mode • off off
• on
• test
_:2 User curve #:Operate & • no no
flt.rec. blocked
• yes
_:26 User curve #:Dynamic • no no
settings
• yes
_:27 User curve #:Blk. w. • no no
inrush curr. detect.
• yes
_:8 User curve #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:3 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:113 User curve #:Threshold 1 A @ 100 Irated 0.000 A to 35.000 A 0.000 A
(absolute) 5 A @ 100 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.000 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.000 A
_:110 User curve #:Reset • instantaneous disk emulation
• disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
_:115 User curve #:Additional 0.00 s to 60.00 s 0.00 s
time delay
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by • no no
AR off/n.ready
• yes
_:35 User curve #:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:29 User curve #:Effected by • no no
AR cycle 1
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 449


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:36 User curve #:Stage • no no
blocked
• yes
_:14 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:102 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:30 User curve #:Effected by • no no
AR cycle 2
• yes
_:37 User curve #:Stage • no no
blocked
• yes
_:15 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:103 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by • no no
AR cycle 3
• yes
_:38 User curve #:Stage • no no
blocked
• yes
_:16 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:104 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:32 User curve #:Effected by • no no
AR cycle gr. 3
• yes
_:39 User curve #:Stage • no no
blocked
• yes
_:17 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:105 User curve #:Time dial 0.05 to 15.00 1.00

450 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


Dyn.s: Cold load PU
_:33 User curve #:Effect. b. • no no
cold-load pickup
• yes
_:40 User curve #:Stage • no no
blocked
• yes
_:18 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:106 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: bin.input
_:34 User curve #:Effected by • no no
binary input
• yes
_:41 User curve #:Stage • no no
blocked
• yes
_:19 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:107 User curve #:Time dial 0.05 to 15.00 1.00

6.5.6.4 Information List

No. Information Data Class Type


(Type)
User curve #
_:81 User curve #:>Block stage SPS I
_:500 User curve #:>Block delay & op. SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:60 User curve #:Inrush blocks operate ACT O
_:59 User curve #:Disk emulation running SPS O
_:55 User curve #:Pickup ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O

6.5.7 Blocking of the Tripping by Device-Internal Inrush-Current Detection

6.5.7.1 Description
The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are

SIPROTEC 5, 7SJ82/7SJ85, Manual 451


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.
The following figure only shows the part of the stage (exemplified by definite-time overcurrent protection
stage 1) that illustrates the influence of the inrush-current detection. Only if the central function Inrush-
current detection (see section 12.10 Inrush-Current Detection) is in effect can the blocking be set.

[loocpgrd-210812-01.tif, 1, en_US]

Figure 6-41 Part-Logic Diagram on the Influence of Inrush-Current Detection Exemplified by the 1st Defi-
nite-Time Overcurrent Protection Stage

6.5.7.2 Application and Setting Notes

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:751:27) Blk. w. inrush curr. detect. = no

Parameter Value Description


no The transformer inrush-current detection does not affect the stage.
Select this setting in the following cases:

• In cases where the device is not used on transformers.

• In cases where the device is used on transformers and the threshold


value of the stage is set above the maximum inrush current of the
transformer. This, for example, applies to the high-current stage that is
set such according to the short-circuit voltage Vsc of the transformer
that it only picks up on faults from the high-voltage side. The trans-
former inrush current cannot become larger than the maximum trans-
mittable short-circuit current.
yes When the transformer inrush-current detection detects an inrush current
that would lead to a tripping of the stage, the start of the time delay and
tripping of the stage are blocked.
Select this setting if the device is used on transformers and the threshold
value of the stage is set below the maximum inrush current of the trans-
former. This applies to the overcurrent-protection stage, which is used as a
backup stage with grading time for faults on the undervoltage side of the
transformer.

452 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

6.5.8 Influence of Other Functions via Dynamic Settings

6.5.8.1 Description
The Threshold and Operate delay settings used for tripping are so-called dynamic settings.
Depending on other functions, the settings of these parameters can be changed dynamically. Depending on
other functions, the stage can also be blocked dynamically. This functionality is only available in function type
Advanced.

[loocpgnd-030311-01.vsd, 2, en_US]

Figure 6-42 Principle of the Dynamic Settings in the Example of 1st Definite-Time Overcurrent Protection
Stage

If available in the device, the following functionalities can affect the overcurrent-protection stages:
Functionalities Priority
Automatic reclosing (AREC) Priority 1
Cold-load pickup detection Priority 2
Binary input signal Priority 3

SIPROTEC 5, 7SJ82/7SJ85, Manual 453


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

These functionalities generate signals that change the settings of the dynamic settings of the overcurrent-
protection stage or block it, if required. In the latter case, the settings for the Threshold and the Operate
delay are of no relevance. Within the overcurrent-protection stage, each of these signals is provided with a
configuration parameter Influence of function ... and its own dynamic settings (Operate delay
and Threshold). The configuration settings are used to set whether the signal shall be active or not, this
means whether the dynamic settings shall be activated or not. If one of these signals (for example, signal
function x) becomes active and is to take effect, these parameter settings become dynamic, that is, instantly
active. This means that the setting assigned to the signal replaces the standard setting. If the signal becomes
inactive, the standard settings apply again. The activation of the dynamic settings is reported.
Where several signals are active in parallel, the priority specified above shall apply. This means that a signal
with priority 2 precedes that of priority 3. The settings assigned to signal 2 become active.
The functionality of the dynamic settings can be disabled. In this case, the settings assigned to the signals are
not visible and are without effect.

454 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Link to the Device-Internal Function Automatic Reclosing (Advanced Stage)

[loocpgrnd-040311-01.vsd, 1, en_US]

Figure 6-43 Influence of the AREC Signals on the Overcurrent-Protection Stage

Several AREC signals can affect the setting for the Threshold and the Operate delay of the protection
stage and its blocking.

• AREC is ready for reclosing 1 (= Automatic reclosing cycle 1)

• AREC is ready for reclosing 2 (= Automatic reclosing cycle 2)

• AREC is ready for reclosing 3 (= Automatic reclosing cycle 3)

• AREC is ready for reclosing 4 (= Automatic reclosing cycle >3)

SIPROTEC 5, 7SJ82/7SJ85, Manual 455


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

The following signal can only block the protection stage:

• AREC is not ready or switched off (= Automatic reclosing off / not ready)
This means that if the AREC is ready and the protection stage is in the idle state, the settings for
AREC cycle 1 are active and not the standard settings. The standard settings are active in the case of AREC
off/not ready.
The influence can be activated for each signal individually. You also have to set the Threshold and Operate
delay or Stage blocked parameters, which take effect when the signal is active.
The way AREC signals are generated is described in chapter 6.46.1 Overview of Functions.

Link to the Device-Internal Function Cold-Load Pickup Detection (Advanced Stage)

[lo_ocp_kal_gnd, 1, en_US]

Figure 6-44 Influence of the Cold-Load Pickup Detection on the Overcurrent-Protection Stage

You have the option of changing the settings for the Threshold and the Operate delay of the protection
stage for a cold-load pickup. You can also block the stage. To do so, you must activate the influence of the
cold-load pickup. You also have to set the Threshold and Operate delay or assign settings to Stage
blocked, which take effect when the signal is active.
The way signals are generated Cold-load pickup is described in chapter 5.8.8 Cold-Load Pickup Detection
(Optional) .

Link to an External Function via a Binary Input Signal (Advanced Stage)

[loocpbingnd-030311-01.vsd, 1, en_US]

Figure 6-45 Influence of the Binary Input on the Overcurrent-Protection Stage

You can use the binary input signal >Activ. dyn. settings to change the settings for the Threshold
and the Operate delay of the protection stage. You can also block the stage. To do so, you must activate
the influence of the binary input. You also have to set the Threshold and Operate delay or assign
settings to Stage blocked, which take effect when the signal is active.

6.5.8.2 Application and Setting Notes (Advanced Stage)

Binary Input Signal: Dynamic settings

• Default setting (_:751:26) Dynamic settings = no

456 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.5 Overcurrent Protection, Ground

Parameter Value Description


no The influence on the overcurrent-protection stage by device-internal or
external functions is not necessary.
yes If a device-internal function (automatic reclosing function or cold-load
pickup detection) or an external function should affect the overcurrent-
protection stage (such as change the setting of the threshold value or time
delay, blocking of the stage), the setting must be changed to yes.
This makes the configuration parameters Influence of function...
as well as the dynamic settings Threshold, Operate delay and Stage
blocked of the stage visible and enables the settings to be set for the
specific influence.

Influence of AREC
The example of how the overcurrent-protection stage (1st stage) can be used as a fast stage before automatic
reclosing describes the influence exerted by AREC.
The setting of the overcurrent level (1st level) results from the time-grading schedule. It is to be used as fast
stage before an automatic reclosing. Because fast disconnection of the short-circuit current takes priority over
the selectivity prior to reclosing, the Operate delay parameter can be set to 0 or to a very low value. To
achieve the selectivity, the final disconnection must be done with the grading time.
AREC is set to 2 reclosings. A secondary Threshold of 1.5 A and a Operate delay of 600 ms are
assumed (according to the time-grading schedule) for the overcurrent-protection stage. The standard settings
of the stage are set to these values.
To realize the application, the configuration settings Effected by AR cycle 1 and Effected by AR
cycle 2 are changed in the example to yes (= influenced). This activates the AR cycle 1 and AR cycle
2 input signals within the stage. When they become active, they switch to the assigned dynamic settings.
The two dynamic settings Operate delay assigned to these input signals (sources of influence) are set to
the time delay 0 (instantaneous tripping). The two dynamic settings Threshold assigned to these input
signals are set to the normal threshold value of 1.5 A.
If the threshold value (1.5 A) is exceeded before AREC 1 and AREC 2, the overcurrent-protection stage trips
instantaneously. If the fault still exists after AREC 2 (unsuccessful AREC), the stage trips with the time delay of
600 ms according to the time-grading schedule.

Influence of External Devices


The influence of an external device can also be configured. The above is an example of how the overcurrent-
protection stage (1st stage) can be used as a fast stage before automatic reclosing, in which case the AREC
function is performed by an external device.
To realize the application, the configuration setting Effected by binary input must be changed to yes
(= influenced). This activates the >Activ. dyn. settings input signal within the stage. When the input
signal becomes active, it switches to the assigned dynamic settings. The external device must provide the
Cycle 1 and Cycle 2 signals or, alternatively, an AREC ready signal. The signals must be connected with
the binary input signal >Activ. dyn. settings.
The dynamic setting Operate delay, which is assigned to the input signal (source of influence) >Activ.
dyn. settings, is set to the time delay 0 (instantaneous tripping). The dynamic setting Threshold
assigned to this input signal is set to the normal threshold value of 1.5 A.
If the threshold value (1.5 A) is exceeded before AREC 1 and AREC 2, the overcurrent-protection stage trips
instantaneously. If the fault still exists after AREC 2 (unsuccessful AREC), the stage trips with the time delay of
600 ms according to the time-grading schedule.

SIPROTEC 5, 7SJ82/7SJ85, Manual 457


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

6.6 Directional Overcurrent Protection, Phases

6.6.1 Overview of Functions

The Directional overcurrent protection, phases function (ANSI 67):

• Detects short circuits at electrical equipment

• Can be used as backup overcurrent protection in addition to the main protection

• Ensures selective fault detection for parallel lines or transformers with infeed at one end

• Ensures selective fault detection in cable runs with infeed at both ends or in lines connected to form ring
topologies

6.6.2 Structure of the Function

The Directional overcurrent protection, phases function is used in protection function groups. 2 function
types are offered:

• Directional overcurrent protection, phases - advanced (67 Dir.OC-3ph-A)

• Directional overcurrent protection, phases - basic (67 Dir.OC-3ph-B)


The Basic function type is provided for standard applications. The Advanced function type offers more func-
tionality and is provided for more complex applications.
Both function types are preconfigured by the manufacturer with 2 directional, definite-time overcurrent
protection stages and with 1 directional inverse-time overcurrent protection stage.
In the advanced function type Directional overcurrent protection, phases – advanced the following stages
can be operated simultaneously:

• Maximum of 4 stages Definite-time overcurrent protection – advanced

• 1 stage Inverse-time overcurrent protection – advanced

• 1 stage User-defined overcurrent protection characteristic curve


In the Basic function type Directional overcurrent protection, phases – basic the following stages can be
operated simultaneously:

• Maximum of 4 stages Definite-time overcurrent protection – basic

• 1 stage Inverse-time overcurrent protection – basic


Stages that are not preconfigured are shown in gray in the following figures. Apart from the tripping delay
characteristic, the stages are identical in structure.
The direction determination occurs on function level and has the same effects in all stages (see following
figure and chapter 6.6.7.1 Description ). In this way, it is ensured that all stages of a function receive the same
direction result. Every stage can be set to the forward or reverse direction.
The group-indication output logic generates the following group indications of the protection function by the
logical OR of the stage-selective indications:

• Pickup

• Operate

458 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

[dwdiocan-050213-01.tif, 4, en_US]

Figure 6-46 Structure/Embedding the Function Directional Overcurrent Protection, Phases – Advanced

[dwdiocba-050213-01.tif, 5, en_US]

Figure 6-47 Structure/Embedding the Function Directional Overcurrent Protection, Phases – Basic

If the device-internal functions listed in the following are present in the device, these functions can influence
the pickup values and tripping delays of the stages or block the stages. The stage can also be affected by an
external source via a binary input signal.

• Automatic reclosing (AREC)

• Cold-load pickup detection

• Binary input signal


If the device is equipped with the Inrush-current detection function, the stages can be stabilized against trip-
ping due to transformer-inrush currents.

SIPROTEC 5, 7SJ82/7SJ85, Manual 459


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

6.6.3 Stage Control

6.6.3.1 Description

Logic
The following figure represents the stage control. It applies to all types of stages.

[lodocpn2-291112-01.tif, 1, en_US]

Figure 6-48 Stage-Control Logic Diagram

Blocking of the Stage with Measuring-Voltage Failure (Basic and Advanced Stage)
The stage can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset. The following blocking options are available for the stage:

• From inside on pickup of the Measuring-voltage failure detection function (see chapter 9.3.2.1 Over-
view of Functions)

• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker
The Blk. by meas.-volt. failure parameter can be set so that measuring-voltage failure detection
blocks the stage or does not block it.

6.6.3.2 Application and Setting Notes

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:8131:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following two conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


switched on.

• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 9.3.4.1 Overview of Functions).

460 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Parameter Value Description


yes The directional overcurrent-protection stage is blocked. Siemens recom-
mends that you retain the default setting, as correct direction determination
cannot be guaranteed if a measuring-voltage failure occurs.
no The directional overcurrent-protection stage is not blocked.

6.6.4 Stage with Definite-Time Characteristic Curve

6.6.4.1 Description

Logic of the Basic Stage

[lodocg6b-060213-01.tif, 2, en_US]

Figure 6-49 Logic Diagram of the Directional, Definite-Time Overcurrent Protection, Phases - Basic

SIPROTEC 5, 7SJ82/7SJ85, Manual 461


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Logic of the Advanced Stage

[lodocp31-141013, 1, en_US]

Figure 6-50 Logic Diagram of the Directional, Definite-Time Overcurrent Protection, Phases - Advanced

Directional Mode (Basic and Advanced Stage)


You use the Directional mode parameter to define whether the stage works in a forward or reverse direc-
tion.
Direction determination itself works across stages (see section 6.6.7.1 Description ).

Non-Directional Pickup, Voltage Memory (Basic and Advanced Stage)


If a 3-phase close-up fault occurs, all 3 phase-to-ground voltages drop to almost 0. If this happens, direction
determination can fall back on a voltage memory (see chapter 6.6.7.1 Description ). If no voltage measure-

462 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

ments which can be used to determine the direction are available in the voltage memory, the basic stage
generally picks up without direction determination, that is non-directionally. For the advanced stage, the
response can be defined via the Non-directional pickup parameter. With the at volt.< &
mem.empty setting, the function picks up in such a situation without direction determination. With the no
setting, the function does not pick up.

Directional Comparison Protection (Advanced Stage)


The stage can be used for directional comparison protection. This is set using the Directional compar-
ison parameter. With the yes setting, the function uses the threshold-value violation to determine the
direction (forward or reverse) and reports the indication Direction . The direction indicated is independent
of the directional mode set for the stage.
The Release via input signal setting and the >Release delay & op. input signal are available
with directional comparison protection. If the Release via input signal parameter is set to yes , the
start of the time delay, and therefore the tripping of the stage, are only enabled if the >Release delay &
op. input signal is active.

Method of Measurement (Basic and Advanced Stage)


You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value .

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Dropout Delay (Advanced Stage)


If the value falls below the dropout threshold, the dropout can be delayed. The pickup is maintained for the
specified time. The tripping delay continues to run. If the time delay expires while the pickup is still main-
tained, the stage operates.

Blocking of the Stage (Basic and Advanced Stage)


The following blockings reset the picked up stage completely:

• Externally or internally via the binary input signal >Block stage (see chapter 6.6.3.1 Description )

• Measuring-voltage failure (see chapter 6.6.3.1 Description )

• Via the dynamic settings function (only provided in the Advanced function type, see chapter Influence of
other functions via dynamic settings and chapter 6.3.8.1 Description )

Blocking of the Time Delay (Basic and Advanced Stage)


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.

Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.3.7.1 Description .

SIPROTEC 5, 7SJ82/7SJ85, Manual 463


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can influence the overcurrent-protection stages:

• Automatic reclosing

• Cold-load pickup detection

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.3.8.1 Description .

6.6.4.2 Application and Setting Notes

Parameter: Directional mode

• Default setting (_:8131:105) Directional mode = forward


You use the Directional mode parameter to define the directional mode of the stage.
Parameter Value Description
forward Select this setting if the stage is to work in a forward direction (in the direc-
tion of the line).
reverse Select this setting if the stage is to work in a reverse direction (in the direc-
tion of the busbar).

Parameter: Method of measurement

• Recommended setting value (_:8131:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Directional comparison, Release via input signal

• Default setting (_:8131:104) Directional comparison = no

• Default setting (_:8131:106) Release via input signal = no


These 2 parameters are not visible in the basic stage.
You use these parameters to define whether the stage is to be used for directional comparison protection.
Directional comparison protection is performed via the Direction and >Release delay & op. signals.

464 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Parameter Value Description


no The stage is not used for directional comparison protection.
yes If the Directional comparison parameter is set to yes, the Release
via input signal parameter, the Direction output signal, and the
>Release delay & op. input signal become available.
If the Release via input signal parameter is set to yes, the start of
the time delay, and therefore also the operate signal of the stage, are only
enabled if the >Release delay & op. input signal is active. The
>Release delay & op. input signal must be connected to the release
information from the opposite end (forward information from the Direc-
tion output signal); see also the application example in chapter
6.6.10 Application Notes for Directional Comparison Protection .

Parameter: Non-directional pickup

• Recommended setting value (_:8131:107) Non-directional pickup = at volt.< &


mem.empty
This parameter is not visible in the basic stage.
Parameter Value Description
at volt.< & mem.empty Select this setting if the stage is to pick up in a non-directional manner if the
voltage memory is empty and determining of direction has to be performed
at low voltages (3-phase close-up fault). An empty voltage memory may
exist, for example, if there is a voltage transformer at the line end and the
circuit breaker (CB) trips.
Siemens recommends using the default setting.
no Select this setting if determining of direction is required under all circum-
stances, that is, even in the event of pickup on a 3-phase close-up fault.

Parameter: Threshold

• Default setting (_:8131:3) Threshold = 1.50 A (for the first stage)


The same considerations apply to setting the threshold value as for non-directional overcurrent protection. For
further information, refer to section 6.3.4.2 Application and Setting Notes .

Parameter: Operate delay

• Default setting (_:8131:6) Operate delay = 0.300 s (for the 1st stage)
The Operate delay to be set is derived from the time-grading schedule that has been prepared for the system.
Typical examples of grading times are provided in the chapters 6.6.9 Application Notes for Parallel Lines and
Cable Runs with Infeed at Both Ends and 6.6.10 Application Notes for Directional Comparison Protection .

Parameter: Dropout ratio

• Recommended setting value (_:8131:4) Dropout ratio = 0.95


This parameter is not visible in the basic stage.
The recommended set value of 0.95 is appropriate for most applications.
For high-precision measurements, the setting value of the Dropout ratio parameter can be reduced, for
example to 0.98. If you expect heavily fluctuating measurands at the response threshold, you can increase the
setting value of the Dropout ratio parameter. This avoids chattering of the tripping stage.

Parameter: Dropout delay

• Recommended setting value (_:8131:101) Dropout delay = 0 s


This parameter is not visible in the basic stage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 465


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Siemens recommends using this setting value, since the dropout of a protection stage must be performed as
fast as possible.
You can use the Dropout delay parameter ≠ 0 s to obtain a uniform dropout behavior if you use it
together with an electromechanical relay. This is required for time grading. The dropout time of the electro-
mechanical relay must be known for this purpose. Subtract the dropout time of your own device (see Tech-
nical Data) and set the result.

6.6.4.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:102 General:Rotation angle -180 ° to 180 ° 45 °
of ref. volt.
General
_:8131:1 Definite-T 1:Mode • off off
• on
• test
_:8131:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:8131:105 Definite-T 1:Directional • forward forward
mode
• reverse
_:8131:8 Definite-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:8131:107 Definite-T 1:Non-direc- • no at volt.< &
tional pickup mem.empty
• at volt.< & mem.empty
_:8131:104 Definite-T 1:Directional • no no
comparison
• yes
_:8131:106 Definite-T 1:Release via • no no
input signal
• yes
_:8131:10 Definite-T 1:Blk. by • no yes
meas.-volt. failure
• yes
_:8131:26 Definite-T 1:Dynamic • no no
settings
• yes
_:8131:27 Definite-T 1:Blk. w. • no no
inrush curr. detect.
• yes
_:8131:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:4 Definite-T 1:Dropout 0.90 to 0.99 0.95
ratio
_:8131:101 Definite-T 1:Dropout 0.00 s to 60.00 s 0.00 s
delay
_:8131:6 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay

466 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


Dyn.s: AR off/n.rdy
_:8131:28 Definite-T 1:Effect. by AR • no no
off/n.ready
• yes
_:8131:35 Definite-T 1:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:8131:29 Definite-T 1:Effected by • no no
AR cycle 1
• yes
_:8131:36 Definite-T 1:Stage • no no
blocked
• yes
_:8131:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:20 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: AR cycle 2
_:8131:30 Definite-T 1:Effected by • no no
AR cycle 2
• yes
_:8131:37 Definite-T 1:Stage • no no
blocked
• yes
_:8131:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:21 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: AR cycle 3
_:8131:31 Definite-T 1:Effected by • no no
AR cycle 3
• yes
_:8131:38 Definite-T 1:Stage • no no
blocked
• yes
_:8131:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:22 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay

SIPROTEC 5, 7SJ82/7SJ85, Manual 467


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


Dyn.s: AR cycle>3
_:8131:32 Definite-T 1:Effected by • no no
AR cycle gr. 3
• yes
_:8131:39 Definite-T 1:Stage • no no
blocked
• yes
_:8131:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:23 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.s: Cold load PU
_:8131:33 Definite-T 1:Effect. b. • no no
cold-load pickup
• yes
_:8131:40 Definite-T 1:Stage • no no
blocked
• yes
_:8131:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:24 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: bin.input
_:8131:34 Definite-T 1:Effected by • no no
binary input
• yes
_:8131:41 Definite-T 1:Stage • no no
blocked
• yes
_:8131:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:25 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay

6.6.4.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:501 General:>Test of direction SPS I
_:2311:301 General:Test direction ACD O

468 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:8131:81 Definite-T 1:>Block stage SPS I
_:8131:501 Definite-T 1:>Release delay & op. SPS I
_:8131:84 Definite-T 1:>Activ. dyn. settings SPS I
_:8131:500 Definite-T 1:>Block delay & op. SPS I
_:8131:54 Definite-T 1:Inactive SPS O
_:8131:52 Definite-T 1:Behavior ENS O
_:8131:53 Definite-T 1:Health ENS O
_:8131:60 Definite-T 1:Inrush blocks operate ACT O
_:8131:62 Definite-T 1:Dyn.set. AR cycle1act. SPS O
_:8131:63 Definite-T 1:Dyn.set. AR cycle2act. SPS O
_:8131:64 Definite-T 1:Dyn.set. AR cycle3act. SPS O
_:8131:65 Definite-T 1:Dyn.set. ARcycl.>3act SPS O
_:8131:66 Definite-T 1:Dyn.set. CLP active SPS O
_:8131:67 Definite-T 1:Dyn.set. BI active SPS O
_:8131:68 Definite-T 1:Dyn. set. blks. pickup SPS O
_:8131:55 Definite-T 1:Pickup ACD O
_:8131:300 Definite-T 1:Direction ACD O
_:8131:56 Definite-T 1:Operate delay expired ACT O
_:8131:57 Definite-T 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 469


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

6.6.5 Stage with Inverse-Time Characteristic Curve

6.6.5.1 Description

Logic of the Basic Stage

[lodoci6b-060213-01.tif, 2, en_US]

Figure 6-51 Logic Diagram of the Directional, Inverse-Time Overcurrent Protection, Phases - Basic

470 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Logic of the Advanced Stage

[lodocp33-121013, 2, en_US]

Figure 6-52 Logic Diagram of the Directional, Inverse-Time Overcurrent Protection, Phases - Advanced

Directional Mode (Basic and Advanced Stage)


You use the Directional mode parameter to define whether the stage works in a forward or reverse direc-
tion.
The direction determination works across stages (see chapter 6.6.7.1 Description ).

Non-Directional Pickup, Voltage Memory (Basic and Advanced Stage)


If a 3-phase close-up fault occurs, all 3 phase-to-ground voltages drop to almost 0. If this happens, direction
determination can fall back on a voltage memory (see chapter 6.6.7.1 Description ). If no voltage measure-
ments which can be used to determine the direction are available in the voltage memory, the basic stage

SIPROTEC 5, 7SJ82/7SJ85, Manual 471


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

generally picks up without direction determination, that is non-directionally. For the advanced stage, the
response can be defined via the Non-directional pickup parameter. With the at volt.< &
mem.empty setting, the function picks up in such a situation without direction determination. With the no
setting, the function does not pick up.

Directional Comparison Protection (Advanced Stage)


The stage can be used for directional comparison protection. This is set using the Directional compar-
ison parameter. With the yes setting, the function uses the threshold-value violation to determine the direc-
tion (forward or reverse) and reports the indication Direction. The direction indicated is independent of the
directional mode set for the stage.
The Release via input signal setting and the >Release delay & op. input signal are available
with directional comparison protection. If the Release via input signal parameter is set to yes, the
start of the time delay, and therefore the tripping of the stage, are only enabled if the >Release delay &
op. input signal is active.

Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI (Basic and
Advanced Stage)

When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.

Minimum Time of the Curve (Advanced Stage)


With the parameter Min. time of the curve, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time.

[DwDocp01_040715-01.vsd, 1, en_US]

Figure 6-53 Minimum Operating Time of the Curve

472 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Additional Time Delay (Advanced Stage)


With the parameter Additional time delay, you define a definite-time delay in addition to the inverse-
time delay. With this setting, the whole curve is shifted on the time axis by this additional definite time.

Blocking of the Stage (Basic and Advanced Stage)


The following blockings reset the picked up stage completely:

• Externally or internally via the binary input signal >Block stage (see chapter 6.6.3.1 Description )

• Measuring-voltage failure (see chapter 6.6.3.1 Description )

• Via the functionality of the dynamic settings (only in the advanced function type, see subtitle Influ-
ence of other functions via dynamic settings and chapter 6.3.8.1 Description ).

Blocking of the Time Delay (Basic and Advanced Stage)


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and a fault record is opened.

Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.3.7.1 Description .

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can influence the overcurrent-protection stages:

• Automatic reclosing

• Cold-load pickup detection

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.3.8.1 Description .

6.6.5.2 Application and Setting Notes

Parameter: Directional mode

• Default setting (_:8161:111) Directional mode = forward


You use the Directional mode parameter to define the directional mode of the stage.
Parameter Value Description
forward Select this setting if the stage is to work in a forward direction (in the direc-
tion of the line).
reverse Select this setting if the stage is to work in a reverse direction (in the direc-
tion of the busbar).

Parameter: Method of measurement

• Recommended setting value (_:8161:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 473


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Parameter Value Description


fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Directional comparison, Release via input signal

• Default setting (_:8161:110) Directional comparison = no

• Default setting (_:8161:112) Release via input signal = no


These 2 parameters are not visible in the basic stage.
You use these parameters to define whether the stage is to be used for directional comparison protection.
Directional comparison protection is performed via the Direction and >Release delay & op. signals.
Parameter Value Description
no The stage is not used for directional comparison protection.
yes If the Directional comparison parameter is set to yes, the Release
via input signal parameter, the Direction output signal, and the
>Release delay & op. input signal become available.
If the Release via input signal parameter is set to yes, the start of
the time delay, and therefore also the operate signal of the stage, are only
enabled if the >Release delay & op. input signal is active. The
>Release delay & op. input signal must be connected to the release
information from the opposite end (forward information from the Direc-
tion output signal); see also the application example in chapter
6.6.10 Application Notes for Directional Comparison Protection .

Parameter: Non-directional pickup

• Recommended setting value (_:8161:113) Non-directional pickup = at volt.< &


mem.empty
This parameter is not visible in the basic stage.
Parameter Value Description
at volt.< & mem.empty Select this setting if the stage is to pick up in a non-directional manner if the
voltage memory is empty and determining of direction has to be performed
at low voltages (3-phase close-up fault). An empty voltage memory may
exist, for example, if there is a voltage transformer at the line end and the
CB trips.
Siemens recommends using the default setting.
no Select this setting if determining of direction is required under all circum-
stances, that is, even in the event of pickup on a 3-phase close-up fault.

Parameter: Type of character. curve

• Default setting (_:8161:130) Type of character. curve = IEC normal inverse

474 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application.

Parameter: Min. time of the curve

• Default setting (_:8161:114) Min. time of the curve = 0.00 s


This parameter is only available in the advanced stage.
With the parameter Min. time of the curve, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time. If the
setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommends keeping the default setting of 0 s.

NOTE

i If the set value is smaller than the smallest possible time delay of the inverse-time characteristic curve, the
parameter has no influence on the delay time.

Parameter: Additional time delay

• Default setting (_:8161:115) Additional time delay = 0.00 s


With the parameter Additional time delay, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic
curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommends keeping the default setting of 0 s.

Parameter: Threshold

• Default setting (_:8161:3) Threshold = 1.50 A


The same considerations apply to setting the threshold value as for non-directional overcurrent protection.
Therefore, refer to chapter 6.3.5.2 Application and Setting Notes for further information.

Parameter: Time dial

• Default setting (_:8161:101) Time dial = 1


Use the Time dial parameter to displace the characteristic curve in the time direction.
The set value for the Time dial parameter is derived from the time-grading chart that has been prepared for
the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the Time
dial parameter at 1 (default setting).

Parameter: Reset

• Default setting (_:8161:131) Reset = disk emulation


You use the Reset parameter to define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Use this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.

SIPROTEC 5, 7SJ82/7SJ85, Manual 475


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

6.6.5.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:102 General:Rotation angle -180 ° to 180 ° 45 °
of ref. volt.
General
_:8341:1 Inverse-T 1:Mode • off off
• on
• test
_:8341:2 Inverse-T 1:Operate & • no no
flt.rec. blocked
• yes
_:8341:111 Inverse-T 1:Directional • forward forward
mode
• reverse
_:8341:11 Inverse-T 1:1-pole • no no
operate allowed
• yes
_:8341:8 Inverse-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:8341:113 Inverse-T 1:Non-direc- • no at volt.< &
tional pickup mem.empty
• at volt.< & mem.empty
_:8341:110 Inverse-T 1:Directional • no no
comparison
• yes
_:8341:112 Inverse-T 1:Release via • no no
input signal
• yes
_:8341:10 Inverse-T 1:Blk. by • no yes
meas.-volt. failure
• yes
_:8341:26 Inverse-T 1:Dynamic • no no
settings
• yes
_:8341:27 Inverse-T 1:Blk. w. inrush • no no
curr. detect.
• yes
_:8341:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:130 Inverse-T 1:Type of char-
acter. curve
_:8341:114 Inverse-T 1:Min. time of 0.00 s to 1.00 s 0.00 s
the curve
_:8341:131 Inverse-T 1:Reset • instantaneous disk emulation
• disk emulation
_:8341:101 Inverse-T 1:Time dial 0.05 to 15.00 1.00
_:8341:115 Inverse-T 1:Additional 0.00 s to 60.00 s 0.00 s
time delay
Dyn.s: AR off/n.rdy
_:8341:28 Inverse-T 1:Effect. by AR • no no
off/n.ready
• yes

476 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:8341:35 Inverse-T 1:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:8341:29 Inverse-T 1:Effected by • no no
AR cycle 1
• yes
_:8341:36 Inverse-T 1:Stage • no no
blocked
• yes
_:8341:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:102 Inverse-T 1:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:8341:30 Inverse-T 1:Effected by • no no
AR cycle 2
• yes
_:8341:37 Inverse-T 1:Stage • no no
blocked
• yes
_:8341:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:103 Inverse-T 1:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:8341:31 Inverse-T 1:Effected by • no no
AR cycle 3
• yes
_:8341:38 Inverse-T 1:Stage • no no
blocked
• yes
_:8341:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:104 Inverse-T 1:Time dial 0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:8341:32 Inverse-T 1:Effected by • no no
AR cycle gr. 3
• yes
_:8341:39 Inverse-T 1:Stage • no no
blocked
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 477


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:8341:17 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:105 Inverse-T 1:Time dial 0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:8341:33 Inverse-T 1:Effect. b. • no no
cold-load pickup
• yes
_:8341:40 Inverse-T 1:Stage • no no
blocked
• yes
_:8341:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:106 Inverse-T 1:Time dial 0.05 to 15.00 1.00
Dyn.set: bin.input
_:8341:34 Inverse-T 1:Effected by • no no
binary input
• yes
_:8341:41 Inverse-T 1:Stage • no no
blocked
• yes
_:8341:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:107 Inverse-T 1:Time dial 0.05 to 15.00 1.00

6.6.5.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:501 General:>Test of direction SPS I
_:2311:301 General:Test direction ACD O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:8161:81 Inverse-T 1:>Block stage SPS I
_:8161:501 Inverse-T 1:>Release delay & op. SPS I
_:8161:84 Inverse-T 1:>Activ. dyn. settings SPS I
_:8161:500 Inverse-T 1:>Block delay & op. SPS I

478 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

No. Information Data Class Type


(Type)
_:8161:54 Inverse-T 1:Inactive SPS O
_:8161:52 Inverse-T 1:Behavior ENS O
_:8161:53 Inverse-T 1:Health ENS O
_:8161:60 Inverse-T 1:Inrush blocks operate ACT O
_:8161:62 Inverse-T 1:Dyn.set. AR cycle1act. SPS O
_:8161:63 Inverse-T 1:Dyn.set. AR cycle2act. SPS O
_:8161:64 Inverse-T 1:Dyn.set. AR cycle3act. SPS O
_:8161:65 Inverse-T 1:Dyn.set. ARcycl.>3act SPS O
_:8161:66 Inverse-T 1:Dyn.set. CLP active SPS O
_:8161:67 Inverse-T 1:Dyn.set. BI active SPS O
_:8161:68 Inverse-T 1:Dyn. set. blks. pickup SPS O
_:8161:59 Inverse-T 1:Disk emulation running SPS O
_:8161:55 Inverse-T 1:Pickup ACD O
_:8161:300 Inverse-T 1:Direction ACD O
_:8161:56 Inverse-T 1:Operate delay expired ACT O
_:8161:57 Inverse-T 1:Operate ACT O

6.6.6 Stage with User-Defined Characteristic Curve

6.6.6.1 Description
The structure of this stage is identical to that of the advanced stage with directional inverse-time characteristic
curve (6.6.4.1 Description ). The only difference is that you can define the characteristic curve as desired.

User-Defined Characteristic Curve


With the directional, user-defined characteristic curve, you can define the operate curve point by point using
up to 30 value pairs of current and time. The device uses linear interpolation to calculate the characteristic
curve from these values. You can also define a dropout characteristic curve if you wish.

Pickup and Dropout Behaviors with User-Defined Characteristic Curve


When the input variable exceeds the threshold value by 1.1 times, the characteristic curve is processed.
An integrating method of measurement totalizes the weighted time. The weighted time results from the char-
acteristic curve. For this, the time that is associated with the present current value is determined from the
characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls short of the pickup value by a factor of 1.045 (0.95 x 1.1 x threshold value),
the dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via
setting parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout
according to the characteristic curve (reduction of totalized time depending on the characteristic curve). The
dropout according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The
weighted reduction of the time is initiated from 0.9 of the set threshold value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 479


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

[dwocpken-140611-02.tif, 2, en_US]

Figure 6-54 Pickup and Dropout Behaviors when Using a Directional User-Defined Characteristic Curve

NOTE

i Note that the currents that are lower than the current value of the smallest characteristic-curve point do
not extend the operate time. The pickup characteristic runs in parallel to the current axis up to the smallest
characteristic-curve point. Currents that are larger than the current value of the largest characteristic-curve
point do not reduce the operate time. The pickup characteristic runs in parallel to the current axis from the
largest characteristic-curve point.

6.6.6.2 Application and Setting Notes


This stage is structured in the same way as the stage with a directional inverse-time characteristic curve. The
only difference is that you can define the characteristic curve as desired. This chapter only provides application
and setting notes for setting characteristic curves.

Parameter: Current/time value pairs (from the operate curve)


Use these settings to define the characteristic curve. Set a current/time value pair for each characteristic-curve
point. The setting depends on the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to displace the characteristic curve.
Set the time value in seconds. The characteristic curve is displaced using the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

Parameter: Time dial

• Default setting (_:101) Time dial = 1


Use the Time dial parameter to displace the characteristic curve in the time direction.

480 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

The set value for the Time dial parameter is derived from the time-grading chart that has been prepared for
the electrical power system. Where no time grading and therefore no displacement of the characteristic curve
is required, leave the Time dial parameter set to 1.

Parameter: Reset

• Default setting (_:115) Reset = disk emulation


You use the Reset parameter to define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation In the case of this setting, a dropout characteristic curve has to be set in
addition to the operate curve.
Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Use this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.

Parameter: Current/time value pairs (of the dropout characteristic curve)


Use these settings to define the characteristic curve. Set a current/time value pair for each characteristic-curve
point. The setting depends on the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to displace the characteristic curve.
Set the time value in seconds. The characteristic curve is displaced using the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

6.6.6.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 User curve #:Mode • off off
• on
• test
_:2 User curve #:Operate & • no no
flt.rec. blocked
• yes
_:110 User curve #:Directional • forward forward
mode
• reverse
_:8 User curve #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:112 User curve #:Non-direc- • no at volt.< &
tional pickup mem.empty
• at volt.< & mem.empty
_:109 User curve #:Directional • no no
comparison
• yes
_:111 User curve #:Release via • no no
input signal
• yes
_:10 User curve #:Blk. by • no yes
meas.-volt. failure
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 481


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:26 User curve #:Dynamic • no no
settings
• yes
_:27 User curve #:Blk. w. • no no
inrush curr. detect.
• yes
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:115 User curve #:Reset • instantaneous disk emulation
• disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by • no no
AR off/n.ready
• yes
_:35 User curve #:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:29 User curve #:Effected by • no no
AR cycle 1
• yes
_:36 User curve #:Stage • no no
blocked
• yes
_:14 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:102 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:30 User curve #:Effected by • no no
AR cycle 2
• yes
_:37 User curve #:Stage • no no
blocked
• yes
_:15 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:103 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by • no no
AR cycle 3
• yes

482 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Addr. Parameter C Setting Options Default Setting


_:38 User curve #:Stage • no no
blocked
• yes
_:16 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:104 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:32 User curve #:Effected by • no no
AR cycle gr. 3
• yes
_:39 User curve #:Stage • no no
blocked
• yes
_:17 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:105 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:33 User curve #:Effect. b. • no no
cold-load pickup
• yes
_:40 User curve #:Stage • no no
blocked
• yes
_:18 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:106 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: bin.input
_:34 User curve #:Effected by • no no
binary input
• yes
_:41 User curve #:Stage • no no
blocked
• yes
_:19 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:107 User curve #:Time dial 0.05 to 15.00 1.00

SIPROTEC 5, 7SJ82/7SJ85, Manual 483


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

6.6.6.4 Information List

No. Information Data Class Type


(Type)
User curve #
_:81 User curve #:>Block stage SPS I
_:501 User curve #:>Release delay & op. SPS I
_:84 User curve #:>Activ. dyn. settings SPS I
_:500 User curve #:>Block delay & op. SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:60 User curve #:Inrush blocks operate ACT O
_:62 User curve #:Dyn.set. AR cycle1act. SPS O
_:63 User curve #:Dyn.set. AR cycle2act. SPS O
_:64 User curve #:Dyn.set. AR cycle3act. SPS O
_:65 User curve #:Dyn.set. ARcycl.>3act SPS O
_:66 User curve #:Dyn.set. CLP active SPS O
_:67 User curve #:Dyn.set. BI active SPS O
_:68 User curve #:Dyn. set. blks. pickup SPS O
_:59 User curve #:Disk emulation running SPS O
_:55 User curve #:Pickup ACD O
_:309 User curve #:Direction ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O

6.6.7 Direction Determination

6.6.7.1 Description

General
Every phase has a separate direction-measuring element. If the threshold value in a phase is exceeded, the
direction determination is started for this phase. If there are multiphase short circuits, all measuring elements
involved perform direction determination independently. If one of the determined directions matches the set
direction, the stage picks up (see descriptions of the stage logic).
The direction is determined by calculating the phase angle between the short-circuit current and a reference
voltage.

Measurands for Direction Determining


The directional measuring element uses the short-circuit current of the phase concerned and the cross-polar-
ized phase-to-phase voltage (as the reference voltage) to determine the direction. This means that the direc-
tion can still be determined unambiguously and correctly, even if the short-circuit voltages collapse
completely when a 1-phase or 2-phase fault occurs (close-up fault).
The phase-to-phase voltages are calculated when phase-to-ground voltages are connected.
The cross-polarized voltage (reference voltage) is vertical in relation to the short-circuit voltages for 1-phase-
to-ground faults (Figure 6-55, left). For 2-phase short circuits, the position of the reference voltages changes
up to 30o, depending on the extent to which the short-circuit voltages collapse (Figure 6-55, right).

484 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

[dwdocp02-240611-01.tif, 1, en_US]

Figure 6-55 Cross-Polarized Voltages for Direction Determination

The following table shows how measurands are assigned for direction-determination purposes in the event of
different types of fault.

Table 6-3 Measurands for Direction Determining

Threshold- Measuring Element


Value A B C Ground
Exceeding Current Voltage Current Voltage Current Voltage Current Voltage
A IA VBC – – – – – –
B – – IB VCA – – – –
C – – – – IC VAB – –
Gnd – – – – – – Ir V0
A, Gnd – VBC – – – – Ir V0
B, Gnd – – IB VCA – – Ir V0
C, Gnd – – – – IC VAB Ir V0
A, B IA VBC IB VCA – – – –
B, C – – IB VCA IC VAB – –
A, C IA VBC – – IC VAB – –
A, B, Gnd IA VBC IB VCA – – Ir V0
B, C, Gnd – – IB VCA IC VAB Ir V0
A, C, Gnd IA VBC – – IC VAB Ir V0
A, B, C IA VBC IB VCA IC VAB – –
A, B, C, Gnd IA VBC IB VCA IC VAB Ir V0

Voltage Memory
Saved voltages are used if, when a 3-pole close-up fault occurs, the measuring voltages are not sufficient for
reliable direction determination. Insofar as and as long as no sufficient measuring voltage is available after the
storage time (2 s) has elapsed, the detected direction is retained. If the memory does not contain any voltages
(when closing onto a short circuit, for example), the behavior of the stage is defined using the Non-direc-
tional pickup parameter.

Direction Determination
As mentioned in the General section, the direction is determined by calculating the phase angle between
short-circuit current and reference voltage. To take different system conditions and applications into account,
the reference voltage can be rotated through an adjustable angle (Rotation angle of ref. volt.
parameter). This moves the vector of the rotated reference voltage close to the vector of the short-circuit

SIPROTEC 5, 7SJ82/7SJ85, Manual 485


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

current. Consequently, the result of direction determination is as reliable as possible. Figure 6-56 illustrates
the relationship based on a 1-phase ground fault in phase A. The short-circuit current IscA lags the short-circuit
voltage by the short-circuit angle φsc. The reference voltage, in this case VBC for measuring element A, is
rotated positively (counterclockwise) by the setting value of the Rotation angle of ref. volt. param-
eter. In the scenario illustrated here, the rotation is +45o.

[dwdocp33-070611-01.tif, 2, en_US]

Figure 6-56 Rotation of the Reference Voltage, Phase-Measuring Element

The rotated reference voltage defines the forward and reverse range, as shown in Figure 6-57. The forward
range is calculated as ±88o around the rotated reference voltage Vref,rot. If the short-circuit current vector is
located in this range, the device decides on the forward direction. In the mirrored range, the device decides on
the backward direction. In the intermediate range, the direction is undetermined.

[dwdocp34-240611-01.tif, 2, en_US]

Figure 6-57 Forward Characteristic of the Directional Function, Phase-Measuring Element

Direction Determination for Test Purposes


If you activate the binary input signal >Test of direction, the direction is determined and indicated even
without the current threshold being exceeded in one of the stages. The direction can be determined as soon
as current and voltage are greater than approx. 7 % of their secondary rated values.

486 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

6.6.7.2 Application and Setting Notes

Parameter: Rotation angle of ref. volt.

• Default setting (_:2311:102) Rotation angle of ref. volt.= 45o


The directional characteristic, that is, the position of the forward and reverse ranges, is set with the Rota-
tion angle of ref. volt. parameter. The short-circuit angle is typically to be found in a range from 30°
to 60° inductive. Therefore, in most cases, the default setting of +45o can be retained to position the reference
voltage, as it ensures a reliable directional result.
Some example settings for special applications appear in the following (Table 6-4). Please note that for phase-
to-ground faults (PG faults), the reference voltage (fault-free voltage) is vertical in relation to the short-circuit
voltage. This results in the following setting for the rotation angle:
Rotation angle of ref. volt. = 90 - φsh phase-measuring elements (PG faults)
Please also note that for phase-to-phase faults, the reference voltage is rotated between 0° (distant fault) and
30o (close-up fault) dependent upon the collapse of the faulted voltage (see Figure 6-56). You can take this
into account with an average value of 15°.
Rotation angle of ref. volt. = 90 - φsh - 15o phase-measuring elements (PP faults)

Table 6-4 Example settings

Application φsh typical Setting


Rotation angle of ref. volt.
60o Range 30o to 0o for PP faults
Selected: 15o

30o Range 60o to 30o for PP faults


Selected: 45o

30o Range 60o to 30o for PP faults


Selected: 45o

Input signal: >Test of direction


If you activate the binary input signal >Test of direction, the direction is determined and indicated even
without the current threshold being exceeded in one of the stages. This provides an easy means of checking
the direction during commissioning, without changing the threshold values of the stages.

SIPROTEC 5, 7SJ82/7SJ85, Manual 487


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

6.6.8 Influence of Other Functions via Dynamic Settings

The influence of these functions via dynamic settings is described in chapter 6.3.8.1 Description and chapter
6.3.8.2 Application and Setting Notes (Advanced Stage) .

6.6.9 Application Notes for Parallel Lines and Cable Runs with Infeed at Both Ends

Parallel Lines or Transformers


In parallel lines or transformers with infeed at one end (see Figure 6-58), if there is no directional measuring
element, a fault on feeder T1 will also trip the other feeder T2. In contrast, a directional measuring element in
the devices on busbar B prevents the tripping of the circuit breaker in the parallel feeder. Therefore, in
Figure 6-58, directional overcurrent protection is used in the places marked with direction arrows. Please note
that the forward direction of the protection device represents the direction towards the object to be protected.
This does not have to be the same as the power direction of normal power flow.
Set time grading in opposition to the power flow with increasing time. As load can only flow in one direction,
you can set the directional devices without time delay.

[dwdocp05-240611-01.tif, 1, en_US]

Figure 6-58 Parallel Line with Transformers

Legend for Figure 6-58


Stage ▶: Directional stage, forward direction set
Stage: Non-directional stage
T: Grading time

Cable Runs with Infeed at Both Ends


Cable runs with infeed at both ends and lines connected to form ring topologies also require that you supple-
ment overcurrent protection with the directional criterion. Figure 6-59 shows a ring system implementation,
with the 2 infeeds shown merging in the ring to form a single infeed. For the directional devices whose
forward direction matches the power-flow direction, set time grading in opposition to the power flow with
increasing time. As power flow from both ends is possible, grading has to be set at both ends.

[dwdocp06-240611-01.tif, 1, en_US]

Figure 6-59 Cable Runs with Infeed at Both Ends

488 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

Legend for Figure 6-59


Stage ▶: Directional stage, forward direction set
Stage: Non-directional stage
T: Grading time

6.6.10 Application Notes for Directional Comparison Protection

The direction determination of directional overcurrent protection can be used to implement directional
comparison protection for cable runs with infeed at both ends. Directional comparison protection is used for
the selective isolation of a faulted line section (for example, subsections of closed rings). Sections are isolated
in fast time, that is, they do not suffer the disadvantage of long grading times.
This technique requires that directional information can be exchanged between the individual protection
stations. You can implement this information exchange using a communication channel (protection interface
or IEC 61850 GOOSE) or with pilot wires for signal transmission via an auxiliary voltage loop.

Protection Principle
The protection principle is shown in Figure 6-60. 2 devices (one at the start of the line and the other at the
end of the line) work together in each line section. The information fault in forward direction is transferred
between them. A directional definite-time overcurrent protection level is in operation in both devices in the
forward direction (1st level). However, this level is not enabled in the idle state. The level is only released
when the information fault in forward direction is received from the opposite end. If the enabled level also
defines the fault in the forward direction, the fault must be on this line section and the level trips immediately.
As this protection principle works with an enable procedure (and not with a blocking procedure), there is no
need to delay the level.
A second directional definite-time overcurrent protection stage with standard time grading works in parallel
with the first stage as a selective backup stage. This ensures full selectivity of protection in the following situa-
tions:

• Infeed at one end or weak infeed at one end: In this case, no release signal is generated.

• Failure of the communication route: In this case, the release signal is not transmitted.
To provide selective protection in fast time for busbars between the line sections also, you can combine this
protection principle with the principle of reverse interlocking. This principle is not discussed in further detail in
this document.

[dwdocp07-240611-01.tif, 2, en_US]

Figure 6-60 Selectivity through Directional Comparison Protection

Legend for Figure 6-60


Stage ▶: Stage is set in the forward direction; stage 1 is instantaneous, stage 2 is graded
▶, ◀: If a threshold value is exceeded, the stage indicates the direction (forward or reverse)

If you are using a communication channel, the protocol-transmission methods detect if the channel is inter-
rupted. If you are using pilot wires, we recommend operation based on a closed-circuit connection. The device
uses a function chart to check and indicate if the binary input is dead for an unexpectedly long period. In

SIPROTEC 5, 7SJ82/7SJ85, Manual 489


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases

contrast with the blocking procedure, overfunction is not possible if communication is lost. Therefore, a loss of
communication is not critical where this procedure is concerned, although it must be detected and indicated.
Directional comparison protection can also be implemented as a blocking procedure. This procedure works
under all system switching states, i.e. also with infeed at one end (or weak infeed). However, to use it you
must delay the stage (typically by 100 ms) so that the blocking signal is received in time under all circum-
stances. It is also essential that you monitor the communication channel to avoid overfunction in the event of
failure followed by a system incident.

Configuration of the Stage, Function Chart


To configure the stage, proceed as follows:

• The Directional mode parameter of both stages must be set to forward

• The Directional comparison and Release via input signal parameters of the first stage
must be set to yes. This is so that the first stage is only released if the >Release delay & op. input
signal is active. Furthermore, the direction is indicated if a threshold value is exceeded.

• The first stage can be set without a time delay. The second stage has to be graded

• The information forward from the Direction signal in the first stage must be transmitted to the oppo-
site end. The routing is determined by the type of transmission

• A function chart has to be implemented at the receive end to link the received (forward information)
and release signals, dependent upon the type of transmission.

490 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7 Directional Overcurrent Protection, Ground

6.7.1 Overview of Functions

The Directional overcurrent protection, ground function (ANSI 67N):

• Detects short circuits to ground affecting electric equipment

• Ensures selective ground-fault detection for parallel lines or transformers with infeed at one end

• Ensures selective ground-fault detection in cable runs with infeed at both ends or in lines connected to
form ring topologies

6.7.2 Structure of the Function

The Directional overcurrent protection, ground function can be used in protection function groups which
provide zero-sequence current and zero-sequence voltage measurements. 2 function types are offered:

• Directional overcurrent protection, ground – advanced (67N Dir.OC-gnd-A)

• Directional overcurrent protection, ground – basic (67N Dir.OC-gnd-B)


The basic function type shall be used for standard applications. The advanced function type provides more
functionalities and is intended for more sophisticated applications.
Both function types are preconfigured by the manufacturer with 2 Definite-time overcurrent protection
stages and 1 Inverse-time overcurrent protection stage.
In the advanced function type Directional overcurrent protection, ground – advanced, the following stages
can operate simultaneously:

• A maximum of 4 Definite-time overcurrent protection – advanced stages

• 1 Inverse-time overcurrent protection – advanced stage

• 1 Logarithmic inverse-time overcurrent protection stage

• 1 Logarithmic inverse time with knee-point overcurrent protection stage

• 1 User-defined characteristic curve overcurrent protection stage


In the basic function type Directional overcurrent protection, ground – basic, the following stages can
operate simultaneously:

• A maximum of 4 Definite-time overcurrent protection – basic stages

• 1 Inverse-time overcurrent protection – basic stage


Referring to Figure 6-61 and Figure 6-62, the stages not preconfigured are shown in gray. Apart from the
operate-delay characteristic curve, the stages are similar in structure.
The general functionality includes the direction determination and the measured-value selection (only
advanced function). They take place on the functional level and have a uniform effect on the stages (see
Figure 6-61 and chapter 6.5.3 General Functionality). This ensures that all stages of the function receive the
same measured current value and the same direction result. Each stage can be set to work in forward or
reverse direction.
The group indication output logic generates the following group indications for the protection function by the
logic OR from the stage-selective indications:

• Pickup

• Operate

SIPROTEC 5, 7SJ82/7SJ85, Manual 491


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

[dwrdirad-300913, 3, en_US]

Figure 6-61 Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Advanced

[dwrdirba-300913, 2, en_US]

Figure 6-62 Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Basic

If the following listed device-internal functions are present in the device, these functions can influence the
pickup values and operate delays of the stages or block the stages. The stage can also be affected by an
external source via a binary input signal.

• Automatic reclosing (AREC)

• Cold-load pickup detection

• Binary input signal


If the device is equipped with the Inrush-current detection function, the stages can be stabilized against
operate due to transformer-inrush currents.

492 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.3 General Functionality

6.7.3.1 Measured-Value Selection

Logic
The function provides the option to select between the values IN measured or 3I0 calculated.

[loMasValue-201505-01.vsd, 1, en_US]

Figure 6-63 Logic Diagram of Measured-Value Selection

Both options are only available for the current-transformer connection types 3-phase + IN and 3-phase +
IN-separate. For other connection types respectively, only one option is possible. If you select an option
that is not allowed, an inconsistency message is given.
Depending on the CT secondary rated current, the CT connection type, and the selected setting, the secondary
threshold setting range varies according to the following table.

Table 6-5 Threshold Setting Range

Connec- Measured CT Terminal Type Threshold Threshold Threshold Threshold


tion Type Value Setting Range Setting Range Setting Range Setting Range
(rated I-sec.: (rated I-sec.: (rated I-sec.: (rated I-sec.:
ph = 1 A, IN = 1 ph = 1 A, IN = 5 ph = 5 A, IN = 1 ph = 5 A, IN = 5
A) A) A) A)
3I0 calculated 4 * Protection 0.030 A to N/A N/A 0.15 A to
35.000 A 175.00 A
4 * Measurement 0.001 A to N/A N/A 0.005 A to
3ph + IN

1.600 A 8.000 A
IN measured 4 * Protection 0.030 A to N/A N/A 0.15 A to
35.000 A 175.00 A
4 * Measurement 0.001 A to N/A N/A 0.005 A to
1.600 A 8.000 A
3I0 calculated 4 * Protection 0.030 A to 0.030 A to 0.15 A to 0.15 A to
35.000 A 35.000 A 175.00 A 175.00 A
3 * Protection, 1 * 0.030 A to 0.030 A to 0.15 A to 0.15 A to
sen. 35.000 A 35.000 A 175.00 A 175.00 A
3ph + IN-separate

4 * Measurement 0.001 A to 0.001 A to 0.005 A to 0.005 A to


1.600 A 1.600 A 8.000 A 8.000 A
IN measured 4 * Protection 0.030 A to 0.15 A to 0.030 A to 0.15 A to
35.000 A 175.00 A 35.000 A 175.00 A
3 * Protection, 1 * 0.001 A to 0.005 A to 0.001 A to 0.005 A to
sen. 1.600 A 8.000 A 1.600 A 8.000 A
4 * Measurement 0.001 A to 0.005 A to 0.001 A to 0.005 A to
1.600 A 8.000 A 1.600 A 8.000 A

SIPROTEC 5, 7SJ82/7SJ85, Manual 493


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.3.2 Direction Determination

Logic of Direction Determination


The following figure represents the logic of the direction determination. It applies to all types of stages.

[lodirdet-280812-01.tif, 1, en_US]

Figure 6-64 Logic Diagram of Direction Determination

Measurand for the Direction Determination


With the parameter Polarization with you define whether the direction determination is calculated with
the zero-sequence components 3I0 and V0 or with the negative-sequence components I2 and V2, which are
present during faults in the network.
The angle between IN (=-3I0) and V0 (respectively -I2 and V2) in case of using the negative-sequence compo-
nents is available as a functional measured value. This value is only present during faults in the network.

[DwUIkenn-240812-01.vsd, 1, en_US]

Figure 6-65 Measured-Value Definition

Start of the Direction Determination


If the zero-sequence current 3I0 exceeds the pickup threshold of a stage and the selected voltage (V0 or V2)
exceeds the parameter Min. voltage V0 or V2 as well, the direction determination is started.

Direction Determination with Zero-Sequence Values


The direction is determined by calculating the phase angle between the short-circuit current -3I0 and the
rotated reference voltage Vref, rot. Contrary to the Directional overcurrent protection, phase function, which
works with the healthy voltage as reference voltage, the fault voltage V0 itself is the reference voltage for the
Directional overcurrent protection, ground function. To take different system conditions and applications

494 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

into account, the reference voltage V0 can be rotated through an adjustable angle (parameter Rotation
angle of ref. volt. ). This moves the vector of the rotated reference voltage close to the vector of the
short-circuit current -3I0. Consequently, the result of direction determination is as reliable as possible.
Figure 6-66 illustrates the relationship based on a 1-phase-to-ground fault in phase A. The fault current has a
phase displacement of 180° to the fault current IscA and lags the fault voltage by the fault angle φsc. The
reference voltage V0 is rotated by φrot which is -45°.

[dwroreze-300913, 2, en_US]

Figure 6-66 Rotation of the Reference Voltage, Directional Overcurrent Protection, Ground Function with
Zero-Sequence Values

The rotated reference voltage Vref, rot and the parameter Forward section +/- define the forward and
reverse ranges, see Figure 6-67. The forward range is calculated as ± Δφ° around the rotated reference voltage
Vref, rot. Δφ is set with the parameter Forward section +/- . If the short-circuit current vector -3I0 is
located in this range, the device decides on the forward direction. In the mirrored range, the device decides on
the reverse direction. In the intermediate range, the direction is undetermined.

SIPROTEC 5, 7SJ82/7SJ85, Manual 495


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

[dwforrev-281013, 2, en_US]

Figure 6-67 Forward/Reverse Characteristic of the Directional Overcurrent Protection, Ground Function

Direction Determination with Negative-Sequence Values


The method works in the same way as for zero-sequence values. Instead of 3I0 and V0, the negative-sequence
values I2 and V2 are used for determining the direction.

Direction Determination for Test Purposes


If you activate the binary input signal >Test of direction , the direction is determined and indicated
even without the current threshold being exceeded in one of the stages. The direction can be determined as
soon as the zero-sequence current 3I0 and the zero-sequence voltage V0 exceeds approx. 7 % of the secon-
dary rated values of phase current and voltage.

6.7.3.3 Application and Setting Notes

Parameter: Measured value

• Recommended setting value (_:9) Measured value = IN Measured


This parameter is not available in the basic function.
Parameter Value Description
IN Measured The function operates with the measured ground current IN. This is the
recommended setting unless there is a specific reason to use the calculated
zero-sequence current 3I0.
3I0 Calculated The function operates with the calculated zero-sequence current 3I0. This
setting option can be used when applying a redundant 50N/51N function for
safety reasons.

Parameter: Min. voltage V0 or V2

• Recommended setting value (_:2311:101) Min. voltage V0 or V2 = 2 V

496 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

This parameter is not available in the basic function. The basic function uses a fixed value of 2 V.
You use the Min. voltage V0 or V2 parameter to define the minimum zero-sequence voltage or nega-
tive-sequence voltage for the direction determination. The minimum voltage must be set greater than the
maximum operational unbalance plus the voltage-transformer measuring errors.
As the measuring error of the individual voltage transformer is not added up, the critical measuring-error influ-
ence is the unbalance of the primary system.
Siemens recommends observing the operational zero-sequence voltage V0 of the protected object (for
example, the line) via the operational measured values of the device and providing the maximum value with a
certainty of 50 %.

EXAMPLE
Maximum operational measured value of zero-sequence voltage V0 = 0.5 Vsec
Min. voltage V0 or V2 = 1.5 ⋅ 0.5 V = 0.75 Vsec

If you have no information about maximum operational unbalance, Siemens recommends using the default
setting.

Parameter: Rotation angle of ref. volt. / Forward section +/-

• Recommended setting value (_:2311:102) Rotation angle of ref. volt.= -45°

• Recommended setting value (_:2311:103) Forward section +/- = 88°


The parameter Forward section +/- is not available in the basic function. The basic function uses a fixed
value of 88°.
The direction characteristic, that is, the area of the forward and reverse ranges, is set with the Rotation
angle of ref. volt. and the Forward section +/- parameters. The short-circuit angle is typically to
be found in a range from -30° to -60° inductively. Therefore, in most cases, the default setting of -45° can be
retained to position the reference voltage, as it ensures a reliable directional result.
Some example settings for special applications appear below Table 6-6. Note that for 1-phase-to-ground faults
(PG faults), the reference voltage is the zero-sequence voltage V0. This results in the following setting for the
rotation angle:
Rotation angle of ref. volt. = -φk ground-measuring elements (PG faults)

Table 6-6 Example Settings

Application φk Typical Setting


Rotation angle of ref. volt.
60° -60°

30° -30°

SIPROTEC 5, 7SJ82/7SJ85, Manual 497


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

30° -30°

Parameter: Polarization with

• Recommended setting value (_:2311:104) Polarization with = zero sequence


This parameter is not available in the basic function. The basic function uses always zero-sequence compo-
nents for the direction determination.
You use the parameter Polarization with to select the values for the direction determination.
Parameter Value Description
zero sequence Select zero sequence to determine the direction via the zero-sequence
components V0 and 3I0.
Siemens recommends using the zero-sequence components for the direction
determination.
negative sequence Select negative sequence to determine the direction via the negative-
sequence components V2 and I2.
The negative-sequence system can be used in case of danger that the zero-
sequence voltage is too small due to unfavorable zero-sequence impedance
conditions or that a parallel line influences the zero-sequence system.

Input Signal: >Test of direction


If you activate the binary input signal >Test of direction, the direction is determined and indicated even
without the current threshold being exceeded in one of the stages. This provides an easy means of checking
the direction during commissioning, without changing the threshold values of the stages.

6.7.3.4 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:9 General:Measured value • 3I0 calculated IN measured
• IN measured
_:2311:101 General:Min. voltage V0 0.150 V to 20.000 V 2.000 V
or V2
_:2311:102 General:Rotation angle -180 ° to 180 ° -45 °
of ref. volt.
_:2311:103 General:Forward section 0 ° to 90 ° 88 °
+/-
_:2311:104 General:Polarization • zero sequence zero sequence
with
• negative sequence

498 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.3.5 Information List

No. Information Data Class Type


(Type)
General
_:2311:501 General:>Test of direction I
_:2311:352 General:Test direction O
_:2311:351 General:Phi(I,V) O

6.7.4 Stage Control

6.7.4.1 Description

Logic
The following figure represents the stage control. It applies to all types of stages.

[lostacon-240812-01.tif, 1, en_US]

Figure 6-68 Logic Diagram of the Stage Control

Blocking of Stage in Case of Measuring-Voltage Failure


The stages can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset. The following blocking options are available for the stage:

• From an internal source on the pickup of the Measuring-voltage failure detection function

• From an external source via the binary input signal >Open of the function block Voltage-transformer
circuit breaker, which links to the trip of the voltage-transformer circuit breaker
The Blk. by meas.-volt. failure parameter can be set to either block or not block the stage when the
Measuring-voltage failure detection function picks up.

6.7.4.2 Application and Setting Notes

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:4861:10) Blk. by meas.-volt. failure = yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 499


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

You can use the Blk. by meas.-volt. failure parameter to control the response of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal Measuring-voltage failure detection function is configured and switched on.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.

Parameter Value Description


yes The directional overcurrent-protection stage is blocked when a measuring-
voltage failure is detected. Siemens recommends using the default setting,
as correct direction determination cannot be guaranteed if a measuring-
voltage failure occurs.
no The directional overcurrent-protection stage is not blocked when a meas-
uring-voltage failure is detected.

500 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.5 Stage with Definite-Time Characteristic Curve

6.7.5.1 Description

Logic of the Basic Stage

[lodirovb-280812-02.tif, 1, en_US]

Figure 6-69 Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Basic

SIPROTEC 5, 7SJ82/7SJ85, Manual 501


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Logic of the Advanced Stage

[lodirova-280812-02.tif, 1, en_US]

Figure 6-70 Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Advanced

Measurand (Basic and Advanced Stage)


The function uses the zero-sequence current (3I0) as a criterion for the ground fault.
Depending on the parameter setting connection type of the Measuring point I-3ph, the zero-sequence
current is measured or calculated. Depending on the applied CT terminal type, the 3I0 Threshold range
varies according to the following table.

502 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Table 6-7 Threshold Setting Range

Connection Type of the Ground Current CT Terminal Type Threshold Setting Range
Measuring Point (Secondary)
I-3ph
3-phase Calculated 4 * Protection 0.030 A to 35.000 A
3 * Protection, 1* sensitive 0.030 A to 35.000 A
4 * Measurement 0.001 A to 1.600 A
x + IN Measured 4 * Protection 0.030 A to 35.000 A
x + IN-separate 3 * Protection, 1* sensitive 0.001 A to 1.600 A
4 * Measurement 0.001 A to 1.600 A

Method of Measurement (Basic and Advanced Stage)


You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.

• Measurement of the fundamental component:


This measuring procedure processes the sampled current values and filters out the fundamental compo-
nents numerically.

• Measurement of the RMS value:


This measuring procedure determines the current amplitude from the sampled values according to the
defining equation of the RMS value. Harmonics are included in the analysis.

Directional Mode (Basic and Advanced Stage)


You can use the Directional mode parameter to define whether the stage works in a forward or reverse
direction.
The direction determination works across all stages (see chapter 6.7.3.2 Direction Determination).

Blocking of the Stage (Basic and Advanced Stage)


The following blockings reset the picked up stage completely:

• Externally or internally via the binary input signal >Block stage (see chapter 6.7.4.1 Description)

• Measuring-voltage failure (see chapter 6.7.4.1 Description)

• Via the dynamic settings functionality (only available in the advanced function type, see Influence of
Other Functions via Dynamic Settings and chapter 6.7.10 Influence of Other Functions via Dynamic
Settings)

Blocking of the Operate Delay (Basic and Advanced Stage)


You can use the binary input signal >Block delay & op. to prevent the start of the operate delay and thus
also the generation of the operate signal. A running operate delay is reset. The pickup is indicated. Fault
logging and fault recording take place.

Blocking of the Operate Delay and Operate Signal via the Device-Internal Inrush-Current Detection Function (Basic
and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.5.7.1 Description

Dropout Delay (Advanced Stage)


In case of undershooting of the dropout threshold, the dropout can be delayed. The pickup is maintained for
the specified time. The operate delay continues to run. If the operate delay expires while the pickup is still
maintained, the stage operates.

SIPROTEC 5, 7SJ82/7SJ85, Manual 503


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Directional Comparison Protection (Advanced Stage)


The stage can be used for directional comparison protection. This is set using the Directional compar-
ison parameter. With the yes setting, the direction indication Direction is released and the direction
(forward or reverse) is determined, if the current exceeds the threshold of the stage. The direction indicated is
independent of the directional mode set for the stage.
The Release via input signal parameter and the >Release delay & op. input signal are available
with directional comparison protection. If the Release via input signal parameter is set to yes, the
start of the operate delay, and therefore the operate signal of the stage, are only enabled when the
>Release delay & op. input signal is active.

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can exert an influence on the overcurrent-protection stage:

• Automatic reclosing

• Cold-load pickup detection

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.7.10 Influence of Other Func-
tions via Dynamic Settings.

6.7.5.2 Application and Setting Notes

Parameter: Directional mode

• Default setting (_:4861:105) Directional mode = forward


You can use the Directional mode parameter to define the directional mode of the stage.
Parameter Value Description
forward Select this setting if the stage is to work in forward direction (in the direction
of the line).
reverse Select this setting if the stage is to work in reverse direction (in the direction
of the busbar).

Parameter: Method of measurement

• Recommended setting value (_:4861:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

504 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Parameter: Directional comparison, Release via input signal

• Default setting (_:4861:104) Directional comparison = no

• Default setting (_:4861:106) Release via input signal= no


The parameters Directional comparison and Release via input signal are not visible for the
basic stage.
You can use these settings to define whether the stage is to be used for directional comparison protection.
Directional comparison protection is performed via the Direction and >Release delay & op. signals.
Parameter Value Description
no The stage is not used for directional comparison protection.
yes If the Directional comparison parameter is set to yes, the Release
via input signal parameter, the Direction output signal, and the
>Release delay & op. input signal become available.
If the Release via input signal parameter is set to yes, the starts of
the operate delay and operate signal are only enabled when the >Release
delay & op. input signal is active. The >Release delay & op. input
signal must be connected to the enable information from the opposite end
(forward information from the Direction output signal).
See also the application example in chapter 6.6.10 Application Notes for
Directional Comparison Protection

Parameter: Dynamic settings

• Default setting (_:4861:26) Dynamic settings = no


This parameter is not visible for the basic stage.
Parameter Value Description
no The influence on the overcurrent-protection stage by device-internal or
external functions is not necessary.
yes If a device-internal function (Automatic reclosing or Cold-load pickup
detection) or an external function should affect the overcurrent-protection
stage (such as change the setting of the threshold value or operate delay,
blocking of the stage), the setting must be changed to yes.
This makes the configuration parameters affected by Auto reclosing/Cold-
load PU/Binary input as well as the dynamic settings Threshold, Operate
delay, and Stage blocked of the stage visible and enables the settings to
be set for the specific influence.

For further setting notes, refer to chapter 6.5.8.2 Application and Setting Notes (Advanced Stage) of the func-
tion Overcurrent Protection, Ground.

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:4861:27) Blk. w. inrush curr. detect. = no

SIPROTEC 5, 7SJ82/7SJ85, Manual 505


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Parameter Value Description


no The transformer inrush-current detection does not affect the stage.
Select this setting in the following cases:

• In cases where the device is not used on transformers.


• In cases where the device is used on transformers and the threshold
value of the stage is set above the maximum inrush current of the trans-
former. This applies, for example, to the high-current stage that is set
according to the short-circuit voltage Vsc of the transformer in such a
way that the stage only picks up on faults from the high-voltage side.
The transformer inrush current cannot become larger than the
maximum transmittable short-circuit current.
yes When the transformer inrush-current detection detects an inrush current that
would lead to an operate of the stage, the start of the operate delay and
operate of the stage are blocked.
Select this setting if the device is used on transformers and the threshold
value of the stage is set below the maximum inrush current of the trans-
former. This applies to the overcurrent-protection stage, which is used as a
backup stage with grading time for faults on the undervoltage side of the
transformer.

Parameter: Threshold

• Default setting (_:4861:3) Threshold = 1.20 A


For setting the threshold value, the same considerations apply as for the non-directional overcurrent protec-
tion function.
For further information, refer to chapter 6.5.4.2 Application and Setting Notes .

Parameter: Dropout ratio

• Recommended setting value (_:4861:4) Dropout ratio = 0.95


This parameter is not visible for the basic stage.
The recommended setting value of 0.95 is appropriate for most applications.
For high-precision measurements, the setting value of the Dropout ratio parameter can be reduced, for
example to 0.98. If you expect highly fluctuating measurands at the pickup threshold, you can increase the
setting value of the Dropout ratio parameter. This avoids chattering of the stage.

Parameter: Dropout delay

• Recommended setting value (_:4861:101) Dropout delay = 0 s


This parameter is not visible for the basic stage.
Siemens recommends using the dropout delay of 0 s, since the dropout of a protection stage must be
performed as fast as possible.
You can use the Dropout delay parameter ≠ 0 s to obtain a uniform dropout behavior if you use it
together with an electromechanical relay. This is required for time grading. The dropout time of the electro-
mechanical relay must be known for this purpose. Subtract the dropout time of your own device (see Tech-
nical data) and set the result.

Parameter: Operate delay

• Default setting (_:4861:6) Operate delay = 0.300 s (for the 1st stage)
The Operate delay to be set is derived from the time-grading chart that has been prepared for the system.
Typical examples of grading times are provided in sections 6.6.9 Application Notes for Parallel Lines and Cable
Runs with Infeed at Both Ends and 6.6.10 Application Notes for Directional Comparison Protection .

506 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.5.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:4861:1 Definite-T 1:Mode • off off
• on
• test
_:4861:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:4861:105 Definite-T 1:Directional • forward forward
mode
• reverse
_:4861:8 Definite-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:4861:104 Definite-T 1:Directional • no no
comparison
• yes
_:4861:106 Definite-T 1:Release via • no no
input signal
• yes
_:4861:10 Definite-T 1:Blk. by • no yes
meas.-volt. failure
• yes
_:4861:26 Definite-T 1:Dynamic • no no
settings
• yes
_:4861:27 Definite-T 1:Blk. w. • no no
inrush curr. detect.
• yes
_:4861:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:4 Definite-T 1:Dropout 0.90 to 0.99 0.95
ratio
_:4861:101 Definite-T 1:Dropout 0.00 s to 60.00 s 0.00 s
delay
_:4861:6 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.s: AR off/n.rdy
_:4861:28 Definite-T 1:Effect. by AR • no no
off/n.ready
• yes
_:4861:35 Definite-T 1:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:4861:29 Definite-T 1:Effected by • no no
AR cycle 1
• yes
_:4861:36 Definite-T 1:Stage • no no
blocked
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 507


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:4861:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:20 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: AR cycle 2
_:4861:30 Definite-T 1:Effected by • no no
AR cycle 2
• yes
_:4861:37 Definite-T 1:Stage • no no
blocked
• yes
_:4861:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:21 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: AR cycle 3
_:4861:31 Definite-T 1:Effected by • no no
AR cycle 3
• yes
_:4861:38 Definite-T 1:Stage • no no
blocked
• yes
_:4861:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:22 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.s: AR cycle>3
_:4861:32 Definite-T 1:Effected by • no no
AR cycle gr. 3
• yes
_:4861:39 Definite-T 1:Stage • no no
blocked
• yes
_:4861:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:23 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay

508 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


Dyn.s: Cold load PU
_:4861:33 Definite-T 1:Effect. b. • no no
cold-load pickup
• yes
_:4861:40 Definite-T 1:Stage • no no
blocked
• yes
_:4861:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:24 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
Dyn.set: bin.input
_:4861:34 Definite-T 1:Effected by • no no
binary input
• yes
_:4861:41 Definite-T 1:Stage • no no
blocked
• yes
_:4861:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:25 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay

6.7.5.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:501 General:>Test of direction SPS I
_:2311:352 General:Test direction ACD O
_:2311:351 General:Phi(I,V) MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:4861:81 Definite-T 1:>Block stage SPS I
_:4861:501 Definite-T 1:>Release delay & op. SPS I
_:4861:84 Definite-T 1:>Activ. dyn. settings SPS I
_:4861:500 Definite-T 1:>Block delay & op. SPS I
_:4861:54 Definite-T 1:Inactive SPS O
_:4861:52 Definite-T 1:Behavior ENS O
_:4861:53 Definite-T 1:Health ENS O
_:4861:60 Definite-T 1:Inrush blocks operate SPS O
_:4861:62 Definite-T 1:Dyn.set. AR cycle1act. SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 509


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

No. Information Data Class Type


(Type)
_:4861:63 Definite-T 1:Dyn.set. AR cycle2act. SPS O
_:4861:64 Definite-T 1:Dyn.set. AR cycle3act. SPS O
_:4861:65 Definite-T 1:Dyn.set. ARcycl.>3act SPS O
_:4861:66 Definite-T 1:Dyn.set. CLP active SPS O
_:4861:67 Definite-T 1:Dyn.set. BI active SPS O
_:4861:68 Definite-T 1:Dyn. set. blks. pickup SPS O
_:4861:55 Definite-T 1:Pickup ACD O
_:4861:300 Definite-T 1:Direction ACD O
_:4861:56 Definite-T 1:Operate delay expired ACT O
_:4861:57 Definite-T 1:Operate ACT O

6.7.6 Stage with Inverse-Time Characteristic Curve

6.7.6.1 Description

Logic of the Basic Stage

[lodiinvb-280812-02.tif, 2, en_US]

Figure 6-71 Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Basic

510 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Logic of the Advanced Stage

[lodiinva-280812-02.tif, 2, en_US]

Figure 6-72 Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Advanced

Measurand (Basic and Advanced Stage)


The function uses the zero-sequence current (3I0) as a criterion for the ground fault.
Depending on the parameter setting connection type of the Measuring point I-3ph, the zero-sequence
current is measured or calculated. Depending on the applied CT terminal type, the 3I0 Threshold range
varies according to the following table.

SIPROTEC 5, 7SJ82/7SJ85, Manual 511


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Table 6-8 Threshold Setting Range

Connection Type of the Ground Current CT Terminal Type Threshold Setting Range
Measuring Point I-3ph (Secondary)
3-phase Calculated 4 * Protection 0.030 A to 35.000 A
3 * Protection, 1* sensitive 0.030 A to 35.000 A
4 * Measurement 0.001 A to 1.600 A
x + IN Measured 4 * Protection 0.030 A to 35.000 A
x + IN-separate 3 * Protection, 1* sensitive 0.001 A to 1.600 A
4 * Measurement 0.001 A to 1.600 A

Method of Measurement (Basic and Advanced Stage)


You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.

• Measurement of the fundamental component:


This measuring procedure processes the sampled current values and filters out the fundamental compo-
nents numerically.

• Measurement of the RMS value:


This measuring procedure determines the current amplitude from the sampled values according to the
defining equation of the RMS value. Harmonics are included in the analysis.

Directional Mode (Basic and Advanced Stage)


You can use the Directional mode parameter to define whether the stage works in a forward or reverse
direction.
The direction determination works across all stages (see chapter 6.7.3.2 Direction Determination).

Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI (Basic and
Advanced Stage)

When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.

Minimum Time of the Curve (Advanced Stage)


With the parameter Min. time of the curve, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time.

512 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

[DwMinTime_20140708-01.vsd, 1, en_US]

Figure 6-73 Minimum Operating Time of the Curve

Additional Time Delay (Advanced Stage)


With the parameter Additional time delay, you define a definite-time delay in addition to the inverse-
time delay. With this setting, the whole curve is shifted on the time axis by this additional definite time.

Blocking of the Stage (Basic and Advanced Stage)


The following blockings reset the picked up stage completely:

• Externally or internally via the binary input signal >Block stage (see chapter 6.7.4.1 Description)

• Measuring-voltage failure (see chapter 6.7.4.1 Description)

• Via the dynamic settings functionality (only available in the advanced function type, see Influence of
Other Functions via Dynamic Settings and chapter 6.7.10 Influence of Other Functions via Dynamic
Settings)

Blocking of the Operate Delay (Basic and Advanced Stage)


You can use the binary input signal >Block delay & op. to prevent the start of the operate delay and thus
also the generation of the operate signal. A running operate delay is reset. The pickup is indicated. Fault
logging and fault recording take place.

Blocking of the Operate Delay and Operate Signal via the Device-Internal Inrush-Current Detection Function (Basic
and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter Blocking of the Tripping by Device-Internal Inrush-Current Detection
For more information, refer to 6.5.7.1 Description.

Directional Comparison Protection (Advanced Stage)


The stage can be used for directional comparison protection. This is set using the Directional compar-
ison parameter. With the yes setting, the direction indication Direction is released and the direction
(forward or reverse) is determined, if the current exceeds the threshold of the stage. The direction indicated is
independent of the directional mode set for the stage.
The Release via input signal parameter and the >Release delay & op. input signal are available
with directional comparison protection. If the Release via input signal parameter is set to yes, the
start of the operate delay, and therefore the operate signal of the stage, are only enabled when the
>Release delay & op. input signal is active.

SIPROTEC 5, 7SJ82/7SJ85, Manual 513


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Influence of Other Functions via Dynamic Settings (Advanced Stage)


If available in the device, the following functions can exert an influence on the overcurrent-protection stage:

• Automatic reclosing

• Cold-load pickup detection

• Binary input signal


The influence of these functions via dynamic settings is described in chapter 6.7.10 Influence of Other Func-
tions via Dynamic Settings.

6.7.6.2 Application and Setting Notes

Parameter: Directional mode

• Default setting (_:4891:111) Directional mode = forward


You can use the Directional mode parameter to define the directional mode of the stage.
Parameter Value Description
forward Select this setting if the stage is to work in forward direction (in the
direction of the line).
reverse Select this setting if the stage is to work in reverse direction (in the
direction of the busbar).

Parameter: Method of measurement

• Recommended setting value (_:4891:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Directional comparison, Release via input signal

• Default setting (_:4891:110) Directional comparison = no

• Default setting (_:4891:112) Release via input signal= no


The parameters Directional comparison and Release via input signal are not visible for the
basic stage.
You can use these settings to define whether the stage is to be used for directional comparison protection.
Directional comparison protection is performed via the Direction and >Release delay & op. signals.

514 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Parameter Value Description


no The stage is not used for directional comparison protection.
yes If the Directional comparison parameter is set to yes, the
Release via input signal parameter, the Direction output
signal, and the >Release delay & op. input signal become avail-
able.
If the Release via input signal parameter is set to yes, the
starts of the operate delay and operate signal are only enabled when
the >Release delay & op. input signal is active. The >Release
delay & op. input signal must be connected to the release informa-
tion from the opposite end (forward information from the Direc-
tion output signal).
See also the application example in chapter 6.6.10 Application Notes
for Directional Comparison Protection .

Parameter: Dynamic settings

• Default setting (_:4891:26) Dynamic settings = no


This parameter is not visible for the basic stage.
Parameter Value Description
no The influence on the overcurrent-protection stage by device-internal
or external functions is not necessary.
yes If a device-internal function (Automatic reclosing or Cold-load
pickup detection) or an external function should affect the overcur-
rent-protection stage (such as change the setting of the threshold
value or operate delay, blocking of the stage), the setting must be
changed to yes.
This makes the configuration parameters affected by Auto reclosing/
Cold-load PU/Binary input as well as the dynamic settings
Threshold, Time dial, and Stage blocked of the stage visible
and enables the settings to be set for the specific influence.

For further setting notes, refer to chapter 6.5.8.2 Application and Setting Notes (Advanced Stage) of the func-
tion Overcurrent Protection, Ground.

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:4891:27) Blk. w. inrush curr. detect. = no

SIPROTEC 5, 7SJ82/7SJ85, Manual 515


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Parameter Value Description


no The transformer inrush-current detection does not affect the stage.
Select this setting in the following cases:

• In cases where the device is not used on transformers.


• In cases where the device is used on transformers and the
threshold value of the stage is set above the maximum inrush
current of the transformer. This applies, for example, to the high-
current stage that is set according to the short-circuit voltage Vsc
of the transformer in such a way that the stage only picks up on
faults from the high-voltage side. The transformer inrush current
cannot become larger than the maximum transmittable shortcir-
cuit current.
yes When the transformer inrush-current detection detects an inrush
current that would lead to an operate of the stage, the start of the
operate delay and operate of the stage are blocked.
Select this setting if the device is used on transformers and the
threshold value of the stage is set below the maximum inrush current
of the transformer. This applies to the overcurrent-protection stage,
which is used as a backup stage with grading time for faults on the
undervoltage side of the transformer.

Parameter: Min. time of the curve

• Default setting (_:4891:114) Min. time of the curve = 0.00 s


This parameter is only available in the advanced stage.
With the parameter Min. time of the curve, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time. If the
setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommends keeping the default setting of 0 s.

NOTE

i If the set value is smaller than the smallest possible time delay of the inverse-time characteristic curve, the
parameter has no influence on the delay time.

Parameter: Additional time delay

• Default setting (_:4891:115) Additional time delay = 0.00 s


With the parameter Additional time delay, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic
curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommend keeping the default setting of 0 s.

Parameter: Threshold

• Default setting (_:4891:3) Threshold = 1.20 A


The setting depends on the minimal occurring ground-fault current. This must be detected.
Consider that a safety margin is set between pickup value and threshold value. The stage only picks up at
approx. 10 % above the Threshold.

516 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Parameter: Type of character. curve

• Default setting (_:4891:130) Type of character. curve = IEC normal inverse


The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application.

Parameter: Time dial

• Default setting (_:4891:101) Time dial = 1


You can use the Time dial parameter to displace the characteristic curve in the time direction.
The setting value for the Time dial parameter is derived from the time-grading chart that has been
prepared for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the Time
dial parameter at 1 (default setting).

Parameter: Reset

• Default setting (_:4891:131) Reset = disk emulation


You can use the Reset parameter setting to define whether the stage decreases according to the dropout
characteristic curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emula-
tion.
instantaneous Select this setting if the dropout does not have to be performed after a
disk emulation and an instantaneous dropout is desired instead.

6.7.6.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:4891:1 Inverse-T 1:Mode • off off
• on
• test
_:4891:2 Inverse-T 1:Operate & • no no
flt.rec. blocked
• yes
_:4891:111 Inverse-T 1:Directional • forward forward
mode
• reverse
_:4891:8 Inverse-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:4891:110 Inverse-T 1:Directional • no no
comparison
• yes
_:4891:112 Inverse-T 1:Release via • no no
input signal
• yes
_:4891:10 Inverse-T 1:Blk. by • no yes
meas.-volt. failure
• yes
_:4891:26 Inverse-T 1:Dynamic • no no
settings
• yes
_:4891:27 Inverse-T 1:Blk. w. inrush • no no
curr. detect.
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 517


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:4891:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:130 Inverse-T 1:Type of char-
acter. curve
_:4891:114 Inverse-T 1:Min. time of 0.00 s to 1.00 s 0.00 s
the curve
_:4891:131 Inverse-T 1:Reset • instantaneous disk emulation
• disk emulation
_:4891:101 Inverse-T 1:Time dial 0.00 to 15.00 1.00
_:4891:115 Inverse-T 1:Additional 0.00 s to 60.00 s 0.00 s
time delay
Dyn.s: AR off/n.rdy
_:4891:28 Inverse-T 1:Effect. by AR • no no
off/n.ready
• yes
_:4891:35 Inverse-T 1:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:4891:29 Inverse-T 1:Effected by • no no
AR cycle 1
• yes
_:4891:36 Inverse-T 1:Stage • no no
blocked
• yes
_:4891:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:102 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 2
_:4891:30 Inverse-T 1:Effected by • no no
AR cycle 2
• yes
_:4891:37 Inverse-T 1:Stage • no no
blocked
• yes
_:4891:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:103 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 3
_:4891:31 Inverse-T 1:Effected by • no no
AR cycle 3
• yes

518 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:4891:38 Inverse-T 1:Stage • no no
blocked
• yes
_:4891:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:104 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: AR cycle>3
_:4891:32 Inverse-T 1:Effected by • no no
AR cycle gr. 3
• yes
_:4891:39 Inverse-T 1:Stage • no no
blocked
• yes
_:4891:17 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:105 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: Cold load PU
_:4891:33 Inverse-T 1:Effect. b. • no no
cold-load pickup
• yes
_:4891:40 Inverse-T 1:Stage • no no
blocked
• yes
_:4891:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:106 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: bin.input
_:4891:34 Inverse-T 1:Effected by • no no
binary input
• yes
_:4891:41 Inverse-T 1:Stage • no no
blocked
• yes
_:4891:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:107 Inverse-T 1:Time dial 0.00 to 15.00 1.00

SIPROTEC 5, 7SJ82/7SJ85, Manual 519


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.6.4 Information List

No. Information Data Class Type


(Type)
Inverse-T 1
_:4891:81 Inverse-T 1:>Block stage SPS I
_:4891:501 Inverse-T 1:>Release delay & op. SPS I
_:4891:84 Inverse-T 1:>Activ. dyn. settings SPS I
_:4891:500 Inverse-T 1:>Block delay & op. SPS I
_:4891:54 Inverse-T 1:Inactive SPS O
_:4891:52 Inverse-T 1:Behavior ENS O
_:4891:53 Inverse-T 1:Health ENS O
_:4891:60 Inverse-T 1:Inrush blocks operate SPS O
_:4891:62 Inverse-T 1:Dyn.set. AR cycle1act. SPS O
_:4891:63 Inverse-T 1:Dyn.set. AR cycle2act. SPS O
_:4891:64 Inverse-T 1:Dyn.set. AR cycle3act. SPS O
_:4891:65 Inverse-T 1:Dyn.set. ARcycl.>3act SPS O
_:4891:66 Inverse-T 1:Dyn.set. CLP active SPS O
_:4891:67 Inverse-T 1:Dyn.set. BI active SPS O
_:4891:68 Inverse-T 1:Dyn. set. blks. pickup SPS O
_:4891:59 Inverse-T 1:Disk emulation running SPS O
_:4891:55 Inverse-T 1:Pickup ACD O
_:4891:300 Inverse-T 1:Direction ACD O
_:4891:56 Inverse-T 1:Operate delay expired ACT O
_:4891:57 Inverse-T 1:Operate ACT O

520 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.7 Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse


Characteristic Curve

6.7.7.1 Description

Logic of the Stage

[lodiloin-280812-02.tif, 3, en_US]

Figure 6-74 Logic Diagram of the Directional Logarithmic Inverse-Time Overcurrent Protection, Ground

Apart from the operate curve, this type of stage is identical to the Inverse-time overcurrent protection –
advanced stage (see chapter 6.7.6.1 Description).
This section will only discuss the nature of the operate curve. For further functionality, refer to chapter
6.7.6.1 Description.

SIPROTEC 5, 7SJ82/7SJ85, Manual 521


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Operate Curve
If the function picks up, the logarithmic inverse-time characteristic curve is processed. A time value Top is
calculated for every input value exceeding 95 % of the pickup value. An integrator accumulates the value 1/
Top. If the accumulated integral reaches the fixed value 1, the stage operates.
The curve used to calculate the time value Top is shown in the following figure. The Threshold multi-
plier parameter defines the beginning of the characteristic curve. The Max. time of the curve deter-
mines the initial value of the characteristic curve. The Time dial parameter changes the slope of the charac-
teristic curve. At high currents, the Min. time of the curve parameter indicates the lower time limit.

[dwloginv-300913, 3, en_US]

Figure 6-75 Operate Curve of Logarithmic Inverse-Time Characteristic

The time to operate is calculated with the following formula:

[fomula01-240812-01.tif, 1, en_US]

Where
Tmax Maximum time of the curve (parameter Max. time of the curve)
Td Time dial (parameter Time dial)
Top Operate time
3I0 Measured zero-sequence current
Ithresh Threshold value (parameter Threshold)
Imul Threshold multiplier (parameter Threshold multiplier)

If the calculated time is less than Tmin (parameter Min. time of the curve), Tmin is used.

522 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.7.2 Application and Setting Notes


Apart from the operate curve, this type of stage is identical to the ground-fault protection type with inverse-
time delay according to IEC and ANSI (advanced function type) (see chapter 6.7.6.1 Description).
This section only discusses the nature of the operate curve. For further functionality, refer to chapter
6.7.6.2 Application and Setting Notes.

Stage Type Selection


If the operate delay is to be dependent on the current level according to a logarithmic characteristic curve,
select this stage type.

Dynamic Settings: Threshold

• Default setting (_:3) Threshold = 1.20 A


Define the pickup value corresponding to the application. In doing so, for time-graded stages, the settings of
the superordinate and of the subordinate stages in the time-grading chart must be taken into consideration.

Parameter: Threshold multiplier

• Default setting (_:116) Threshold multiplier = 1.1


You can use the Threshold multiplier parameter to define the beginning of the characteristic curve on
the current axis (in relation to the threshold value).
General information cannot be provided. Define the value corresponding to the application.

EXAMPLE

Threshold (Secondary current) Ithresh = 1.2 A


Threshold multiplier Imul = 1.1
Pickup value (Secondary current) IPU = 1.2 A ×1.1 = 1.32 A

Dynamic Settings: Time dial

• Default setting (_:6) Time dial = 1.250 s


You can use the Time dial parameter to change the slope of the characteristic curve.
General information cannot be provided. Define the value corresponding to the application.

Parameter: Max. time of the curve

• Default setting (_:114) Max. time of the curve = 5.800 s


The parameter Max. time of the curve determines the initial value of the characteristic curve (for 3I0 =
Threshold).
General information cannot be provided. Define the value corresponding to the application.

Parameter: Min. time of the curve

• Default setting (_:113) Min. time of the curve = 1.200 s


The parameter Min. time of the curve determines the lower time limit (at high currents).
General information cannot be provided. Define the value corresponding to the application.

Parameter: Additional time delay

• Recommended setting value (_:115) Additional time delay = 0 s


You can set an additional current-independent time delay. This additional delay is intended for special applica-
tions.

SIPROTEC 5, 7SJ82/7SJ85, Manual 523


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Siemens recommends setting this time to 0 s so that it has no effect.

6.7.7.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 Log.-inv.-T #:Mode • off off
• on
• test
_:2 Log.-inv.-T #:Operate & • no no
flt.rec. blocked
• yes
_:119 Log.-inv.-T #:Directional • forward forward
mode
• reverse
_:8 Log.-inv.-T #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:118 Log.-inv.-T #:Directional • no no
comparison
• yes
_:120 Log.-inv.-T #:Release via • no no
input signal
• yes
_:10 Log.-inv.-T #:Blk. by • no yes
meas.-volt. failure
• yes
_:26 Log.-inv.-T #:Dynamic • no no
settings
• yes
_:27 Log.-inv.-T #:Blk. w. • no no
inrush curr. detect.
• yes
_:3 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:6 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
_:113 Log.-inv.-T #:Min. time 0.000 s to 60.000 s 1.200 s
of the curve
_:114 Log.-inv.-T #:Max. time 0.000 s to 60.000 s 5.800 s
of the curve
_:116 Log.-inv.-T #:Threshold 1.00 to 4.00 1.10
multiplier
_:115 Log.-inv.-T #:Additional 0.000 s to 60.000 s 0.000 s
time delay
Dyn.s: AR off/n.rdy
_:28 Log.-inv.-T #:Effect. by • no no
AR off/n.ready
• yes
_:35 Log.-inv.-T #:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:29 Log.-inv.-T #:Effected by • no no
AR cycle 1
• yes

524 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:36 Log.-inv.-T #:Stage • no no
blocked
• yes
_:14 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:107 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.set: AR cycle 2
_:30 Log.-inv.-T #:Effected by • no no
AR cycle 2
• yes
_:37 Log.-inv.-T #:Stage • no no
blocked
• yes
_:15 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:108 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.set: AR cycle 3
_:31 Log.-inv.-T #:Effected by • no no
AR cycle 3
• yes
_:38 Log.-inv.-T #:Stage • no no
blocked
• yes
_:16 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:109 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.s: AR cycle>3
_:32 Log.-inv.-T #:Effected by • no no
AR cycle gr. 3
• yes
_:39 Log.-inv.-T #:Stage • no no
blocked
• yes
_:17 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:110 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s

SIPROTEC 5, 7SJ82/7SJ85, Manual 525


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


Dyn.s: Cold load PU
_:33 Log.-inv.-T #:Effect. b. • no no
cold-load pickup
• yes
_:40 Log.-inv.-T #:Stage • no no
blocked
• yes
_:18 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:111 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.set: bin.input
_:34 Log.-inv.-T #:Effected by • no no
binary input
• yes
_:41 Log.-inv.-T #:Stage • no no
blocked
• yes
_:19 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:112 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s

6.7.7.4 Information List

No. Information Data Class Type


(Type)
Log.-inv.-T #
_:81 Log.-inv.-T #:>Block stage I
_:501 Log.-inv.-T #:>Release delay & op. I
_:84 Log.-inv.-T #:>Activ. dyn. settings I
_:500 Log.-inv.-T #:>Block delay & op. I
_:54 Log.-inv.-T #:Inactive O
_:52 Log.-inv.-T #:Behavior O
_:53 Log.-inv.-T #:Health O
_:60 Log.-inv.-T #:Inrush blocks operate O
_:62 Log.-inv.-T #:Dyn.set. AR cycle1act. O
_:63 Log.-inv.-T #:Dyn.set. AR cycle2act. O
_:64 Log.-inv.-T #:Dyn.set. AR cycle3act. O
_:65 Log.-inv.-T #:Dyn.set. ARcycl.>3act O
_:66 Log.-inv.-T #:Dyn.set. CLP active O
_:67 Log.-inv.-T #:Dyn.set. BI active O
_:68 Log.-inv.-T #:Dyn. set. blks. pickup O
_:55 Log.-inv.-T #:Pickup O
_:300 Log.-inv.-T #:Direction O

526 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

No. Information Data Class Type


(Type)
_:56 Log.-inv.-T #:Operate delay expired O
_:57 Log.-inv.-T #:Operate O

6.7.8 Stage with Knee-Point Characteristic Curve

6.7.8.1 Description

Logic of the Stage

[lodilokn-280812-02.tif, 3, en_US]

Figure 6-76 Logic Diagram of the Directional Logarithmic Inverse Time with Knee-Point Overcurrent Protec-
tion, Ground

SIPROTEC 5, 7SJ82/7SJ85, Manual 527


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Apart from the operate curve, this type of stage is almost identical to the Inverse-time overcurrent protec-
tion – advanced stage (see chapter 6.7.6.1 Description). The only difference is that the dynamic settings
change functionality is not available.
This section only discusses the nature of the operate curve. For further functionality, refer to chapter
6.7.6.1 Description.

Operate Curve
If the function picks up, the logarithmic inverse-time characteristic curve is processed. A time value Top is
calculated for every input value exceeding 95 % of the threshold value. An integrator accumulates the value
1/Top. If the accumulated integral reaches the fixed value 1, the stage operates.
The curve used to calculate the time value Top is shown in the following graphic. The curve is composed of 2
sections with different slops. 7 parameters are used to define the logarithmic inverse time with knee-point
characteristic curve. The parameter Max. time of the curve determines the initial time value of the
characteristic curve, and relates to the 3I0 Threshold value. The transition point is defined by parameter
Knee-point current and parameter Knee-point time. The parameter Min. time of the curve
indicates the lower time limit, and parameter Current at Min. time determines the current value at
Min. time of the curve. The parameter Time dial servers as a time factor to the operate time.

[dwloinkn-300913, 3, en_US]

Figure 6-77 Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In the Example
of Threshold = 0.004 A)

6.7.8.2 Application and Setting Notes


Apart from the operate curve, this type of stage is almost identical to the Inverse-time overcurrent protec-
tion – advanced stage (see chapter 6.7.6.1 Description). The only difference is that the dynamic settings
change functionality is not available.
This section only discusses the nature of the operate curve. For further functionality, refer to chapter
6.7.6.2 Application and Setting Notes.

528 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Parameter: Threshold

• Default setting (_:3) Threshold = 1.20 A


You can use the Threshold parameter to define the pickup value of the stage corresponding to the specific
application.

Parameter: Time dial

• Default setting (_:6) Time dial = 0.2


You can use the Time dial parameter to displace the operate curve in the time direction.
General information cannot be provided. Define the value corresponding to the application.

Parameter: Knee-point

• Default setting (_:101) Knee-point current = 1.300 A

• Default setting (_:105) Knee-point time = 23.60 s


You use the Knee-point current parameter and the Knee-point time parameter to define the knee-
point of the operate curve.
General information cannot be provided. Define the values corresponding to the application.

Parameter: Minimum Time of the Operate Curve

• Default setting (_:104) Min. time of the curve = 0.80 s

• Default setting (_:102) Current at Min. time = 1.500 A


Via the parameters Min. time of the curve and Current at Min. time, the point of the operate
curve is defined where higher currents do no longer cause shorter operate times.
General information cannot be provided. Define the value corresponding to the application.

Parameter: Maximum Time of the Operate Curve

• Default setting (_:103) Max. time of the curve = 93.00 s


You can use the parameter Max. time of the curve to determine the initial value of the operate curve
(for 3I0 = Threshold).
General information cannot be provided. Define the value corresponding to the application.

6.7.8.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 Log.inv.T KP #:Mode • off off
• on
• test
_:2 Log.inv.T KP #:Operate & • no no
flt.rec. blocked
• yes
_:108 Log.inv.T KP #:Direc- • forward forward
tional mode
• reverse
_:8 Log.inv.T KP #:Method • fundamental comp. fundamental
of measurement comp.
• RMS value
_:107 Log.inv.T KP #:Direc- • no no
tional comparison
• yes
_:106 Log.inv.T KP #:Release • no no
via input signal
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 529


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:10 Log.inv.T KP #:Blk. by • no yes
meas.-volt. failure
• yes
_:27 Log.inv.T KP #:Blk. w. • no no
inrush curr. detect.
• yes
_:3 Log.inv.T KP #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:109 Log.inv.T KP #:Time dial 0.05 to 1.50 0.20
_:101 Log.inv.T KP #:Knee- 1 A @ 100 Irated 0.030 A to 35.000 A 1.300 A
point current 5 A @ 100 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.500 A
_:105 Log.inv.T KP #:Knee- 0.00 s to 100.00 s 23.60 s
point time
_:102 Log.inv.T KP #:Current at 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
Min. time 5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:104 Log.inv.T KP #:Min. time 0.00 s to 30.00 s 0.80 s
of the curve
_:103 Log.inv.T KP #:Max. time 0.00 s to 200.00 s 93.00 s
of the curve

6.7.8.4 Information List

No. Information Data Class Type


(Type)
Stage #
_:81 Log.inv.T KP #:>Block stage SPS I
_:501 Log.inv.T KP #:>Release delay & op. SPS I
_:500 Log.inv.T KP #:>Block delay & op. SPS I
_:54 Log.inv.T KP #:Inactive SPS O
_:52 Log.inv.T KP #:Behavior ENS O
_:53 Log.inv.T KP #:Health ENS O
_:60 Log.inv.T KP #:Inrush blocks operate SPS O
_:55 Log.inv.T KP #:Pickup ACD O
_:300 Log.inv.T KP #:Direction ACD O
_:56 Log.inv.T KP #:Operate delay expired ACT O
_:57 Log.inv.T KP #:Operate ACT O

530 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

6.7.9 Stage with User-Defined Characteristic Curve

6.7.9.1 Description

Logic of the Stage

[lodirusr-280812-02.tif, 1, en_US]

Figure 6-78 Logic Diagram of the Directional User-Defined Characteristic Curve Overcurrent Protection,
Ground

This stage is structured in the same way as the Inverse-time overcurrent protection – advanced stage (see
chapter 6.7.6.1 Description). The only difference is that you can define the characteristic curve.
This section only discusses the nature of the operate curve. For further functionality, refer to chapter
6.7.6.1 Description.

SIPROTEC 5, 7SJ82/7SJ85, Manual 531


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

User-Defined Characteristic Curve


With the directional, user-defined characteristic curve, you can define the operate curve point by point using
up to 30 value pairs of current and time. The device uses linear interpolation to calculate the characteristic
curve from these values. You can also define a dropout characteristic curve if you wish.

Pickup and Dropout Behaviors with User-Defined Characteristic Curves


When the input variable exceeds the threshold value by 1.1 times, the characteristic curve is processed.
An integrating method of measurement totalizes the weighted time. The weighted time results from the char-
acteristic curve. For this, the time that is associated with the present current value is determined from the
characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls short of the threshold value by a factor of 1.045 (0.95 × 1.1× threshold value),
the dropout is started. The pickup will be indicated as outgoing. You can influence the dropout behavior via
setting parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout
according to the characteristic curve (reduction of totalized time depending on the characteristic curve). The
dropout according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The
weighted reduction of the time is started from 0.9 of the set threshold value.
The following figure shows the pickup behavior and dropout behavior when a directional user-defined charac-
teristic curve is used.

[dwpidrbe-300913, 1, en_US]

Figure 6-79 Pickup and Dropout Behaviors when Using a User-Defined Characteristic Curve

NOTE

i Note that the currents that are lower than the current value of the smallest characteristic-curve point do
not extend the operate time. The pickup characteristic runs in parallel to the current axis up to the smallest
characteristic-curve point. Currents that are larger than the current value of the largest characteristic-curve
point do not reduce the operate time. The pickup characteristic runs in parallel to the current axis from the
largest characteristic-curve point.

6.7.9.2 Application and Setting Notes


This stage is structured in the same way as the Inverse-time overcurrent protection – advanced stage. The
only difference is that you can define the characteristic curve as required. This section only provides applica-
tion and setting notes for setting the characteristic curves. For guidance on the other parameters of the stage,
see chapter 6.7.6.2 Application and Setting Notes.

532 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Parameter: Current/time value pairs (of the Operate Curve)


Use these settings to define the characteristic curve. Set a current/time value pair for each characteristic-curve
point. The setting follows the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold setting afterwards if you
want to displace the characteristic curve.
Specify the time value in seconds. The characteristic curve is displaced using the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

Parameter: Time dial

• Default setting (_:101) Time dial = 1


You can use the Time dial parameter to displace the characteristic curve in the time direction.
The setting value for the Time dial parameter is derived from the time-grading chart that has been
prepared for the system. Where no grading and therefore no displacement of the characteristic curve is
required, leave the Time dial set to 1.

Parameter: Reset

• Default setting (_:110) Reset = disk emulation


The Reset parameter is used to define whether the stage drops out according to the dropout characteristic
curve (behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation Both operate curve and a dropout characteristic curve have to be specified
with this setting.
Use this setting if the device is coordinated with electromechanical devices or
other devices performing dropout after disk emulation.
instantaneous Use this setting if the dropout is not to be performed after disk emulation,
that is, if instantaneous dropout is required.

Parameter: Current/time value pairs (of the Dropout Curve)


Use these settings to define the characteristic curve. Set a current/time value pair for each characteristic-curve
point. The setting is determined by the characteristic curve you want to achieve.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold setting afterwards if you
want to displace the characteristic curve.
Specify the time value in seconds. The characteristic curve is displaced using the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

6.7.9.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 User curve #:Mode • off off
• on
• test

SIPROTEC 5, 7SJ82/7SJ85, Manual 533


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:2 User curve #:Operate & • no no
flt.rec. blocked
• yes
_:113 User curve #:Directional • forward forward
mode
• reverse
_:8 User curve #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:112 User curve #:Directional • no no
comparison
• yes
_:114 User curve #:Release via • no no
input signal
• yes
_:10 User curve #:Blk. by • no yes
meas.-volt. failure
• yes
_:26 User curve #:Dynamic • no no
settings
• yes
_:27 User curve #:Blk. w. • no no
inrush curr. detect.
• yes
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:110 User curve #:Reset • instantaneous disk emulation
• disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by • no no
AR off/n.ready
• yes
_:35 User curve #:Stage • no no
blocked
• yes
Dyn.set: AR cycle 1
_:29 User curve #:Effected by • no no
AR cycle 1
• yes
_:36 User curve #:Stage • no no
blocked
• yes
_:14 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:102 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:30 User curve #:Effected by • no no
AR cycle 2
• yes

534 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


_:37 User curve #:Stage • no no
blocked
• yes
_:15 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:103 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by • no no
AR cycle 3
• yes
_:38 User curve #:Stage • no no
blocked
• yes
_:16 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:104 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:32 User curve #:Effected by • no no
AR cycle gr. 3
• yes
_:39 User curve #:Stage • no no
blocked
• yes
_:17 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:105 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:33 User curve #:Effect. b. • no no
cold-load pickup
• yes
_:40 User curve #:Stage • no no
blocked
• yes
_:18 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:106 User curve #:Time dial 0.05 to 15.00 1.00

SIPROTEC 5, 7SJ82/7SJ85, Manual 535


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground

Addr. Parameter C Setting Options Default Setting


Dyn.set: bin.input
_:34 User curve #:Effected by • no no
binary input
• yes
_:41 User curve #:Stage • no no
blocked
• yes
_:19 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:107 User curve #:Time dial 0.05 to 15.00 1.00

6.7.9.4 Information List

No. Information Data Class Type


(Type)
User curve #
_:81 User curve #:>Block stage SPS I
_:501 User curve #:>Release delay & op. SPS I
_:84 User curve #:>Activ. dyn. settings SPS I
_:500 User curve #:>Block delay & op. SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:60 User curve #:Inrush blocks operate SPS O
_:62 User curve #:Dyn.set. AR cycle1act. SPS O
_:63 User curve #:Dyn.set. AR cycle2act. SPS O
_:64 User curve #:Dyn.set. AR cycle3act. SPS O
_:65 User curve #:Dyn.set. ARcycl.>3act SPS O
_:66 User curve #:Dyn.set. CLP active SPS O
_:67 User curve #:Dyn.set. BI active SPS O
_:68 User curve #:Dyn. set. blks. pickup SPS O
_:59 User curve #:Disk emulation running SPS O
_:55 User curve #:Pickup ACD O
_:300 User curve #:Direction ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O

6.7.10 Influence of Other Functions via Dynamic Settings

6.5.8.1 Description and 6.5.8.2 Application and Setting Notes (Advanced Stage) describe the influence of
other functions on dynamic settings.

536 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.8 Inrush-Current Detection

6.8 Inrush-Current Detection

6.8.1 Overview of Functions

The function Inrush-current detection

• Recognizes an inrush process on transformers

• Generates a blocking signal for protection functions that protect the transformer (protected object) or for
protection functions that are affected in undesirable ways when transformers are switched on

• Allows a sensitive setting of the protection functions


The following protection functions evaluate the blocking signal

• Overcurrent protection with a pickup value below the maximum inrush current

• Negative-sequence protection as sensitive backup protection for transformers

6.8.2 Structure of the Function

The function Inrush-current detection is not an individual protection function. In the connection process of a
transformer, it transmits a blocking signal to other protection functions. For this reason, the inrush-current
detection must be in the same function group as the functions that are to be blocked.
The following figure shows the embedding of the function. The setting parameter Blk. w. inrush curr.
detect. establishes the connection between inrush-current detection and the functions that are to be
blocked. If the parameter is set to yes, the connection is effective.
A jump detection or the threshold value exceeding of the functions to be blocked is used as trigger signal for
synchronization of the internal measurement methods.
The jump detection reacts to changes in the current. The threshold value exceeding is recognized due to an
internal pickup of the protection function that is to be blocked.

[dwirsh01-070611-01.tif, 1, en_US]

Figure 6-80 Structure/Embedding of the Function

6.8.3 Function Description

The function Inrush-current detection analyzes the trigger signal of the jump detection or the threshold-
value violation of the function to be blocked in a start logic, and synchronizes the method of measurement. In
order to securely record the inrush processes, the function uses the Harmonic analysis method of measure-
ment and the CWA method (current wave shape analysis). Both methods work in parallel and link the results
through a logical OR.
If you wish to work with only one process, deactivate the other method by way of the parameters Blocking
with 2. harmonic or Blocking with CWA .

SIPROTEC 5, 7SJ82/7SJ85, Manual 537


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.8 Inrush-Current Detection

[loinru02-100611-01.tif, 2, en_US]

Figure 6-81 Basic Structure of the Inrush-Current Detection

Harmonic Analysis
For this method of measurement, the content of the 2nd harmonic and the fundamental component (1st
harmonic) are determined for each of the phase currents IA, IB, and IC and the quotient I2nd harm / I1st harm is
formed from this. If this quotient exceeds the set threshold value, a phase-selective signal is issued.
If 95 % of the set threshold value is exceeded, this leads to a pickup reset (dropout ratio = 0.95).

538 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.8 Inrush-Current Detection

[loinru10-040912-01.tif, 1, en_US]

Figure 6-82 Logic of the Harmonic Analysis Function (T = 1 Period)

CWA Method (Current Wave Shape Analysis)


The CWA method executes a wave shape analysis of the phase currents IA, IB, and IC. If all 3 phase currents
show flat areas at the same point in time, the inrush-current detection signal will be issued. This signal applies
for all 3 phases simultaneously. The following figure shows a typical inrush-current characteristic, with the
simultaneously occurring flat areas clearly recognizable.

[dwinru03-240211-01.tif, 1, en_US]

Figure 6-83 Inrush-Current Characteristic

The following figure shows the logic diagram of the CWA method.
From the present fundamental-component current (1st harmonic), the threshold value for identification of the
flat areas is derived via an internal factor.

SIPROTEC 5, 7SJ82/7SJ85, Manual 539


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.8 Inrush-Current Detection

[loinru05-240211-01.tif, 1, en_US]

Figure 6-84 Logic of the CWA-Method Function (T = 1 Period)

Logic of the Inrush-Current Detection


The following logic diagram shows the link of the 2 methods of measurement Harmonic Analysis and CWA
method.
The crossblock function influences the Harmonic Analysis process. If you have set the parameter Cross-
blocking to yes, you will receive in the event of threshold-value violation a blocking indication for all 3
phase currents and the measured or calculated zero-sequence current (l2nd harm / l1st harm). The crossblock func-
tion works via a timer. Set parameters for the time depending on the expected duration factor via the param-
eter Cross-blocking time.
If the phase current exceeds the maximum permissible current Operat.-range limit Imax, the inrush-
current detection will be blocked.

540 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.8 Inrush-Current Detection

[loinru12-060912-01.tif, 1, en_US]

Figure 6-85 Logic Diagram of the Inrush-Current Detection

6.8.4 Application and Setting Notes

Parameter: Operat.-range limit Imax

• Recommended setting value (_:106) Operat.-range limit Imax = 7.5 A


With the parameter Operat.-range limit Imax, you can specify at which current the inrush-current
detection is blocked internally. Set the value to be greater than the RMS value of the maximum inrush
current of the transformer. A practicable value is 7.5 times the transformer rated current.

Parameter: Blocking with CWA

• Recommended setting value = (_:111) Blocking with CWA = yes

Parameter Value Description


yes CWA process activated.
no CWA process deactivated.

Parameter: Blocking with 2. harmonic

• Recommended setting value (_:110) Blocking with 2. harmonic = yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 541


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.8 Inrush-Current Detection

Parameter Value Description


yes Harmonic analysis process activated.
no Harmonic analysis process deactivated.

NOTE

i Make sure that at least one process is activated. Siemens recommends retaining the advised setting values.

Parameter: 2nd harmonic content

• Recommended setting value (_:102) 2nd harmonic content = 15 %


With the parameter 2nd harmonic content, you can specify the pickup value of the harmonic anal-
ysis function. The setting value of 15 % is practicable for most transformers.

Parameter: Cross-blocking

• Recommended setting value (_:112) Cross-blocking = no

Parameter Value Description


no Through the CWA process working in parallel in the inrush-current detec-
tion, the function is not activated as standard.
yes If a subfunction of the inrush-current detection is identified in the course of
the closure trials during commissioning, set the parameter Cross-
blocking to yes.

Parameter: Cross-blocking time

• Default setting (_:109) Cross-blocking time = 0.06 s


You define the duration of this blocking with the Cross-blocking time parameter. The default
setting of 0.06 s (about 3 periods) has proven practicable. Set the time as short as possible and check
the value during the closure trials. The parameter Cross-blocking time is inactive at Cross-
blocking = no.

Parameter: Start flt.rec

• Default setting (_:114) Start flt.rec = yes


With the Start flt.rec parameter, you determine whether a fault record should be started upon
pickup of the inrush-current detection. The following settings are possible:

Parameter Value Description


no No fault recording starts with pickup.
yes The fault recording starts with pickup. When the protection function is
blocked by the inrush-current detection, a fault recording is started never-
theless.

6.8.5 Settings

Addr. Parameter C Setting Options Default Setting


Inrush detect.
_:1 Inrush detect.:Mode • off on
• on
• test

542 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.8 Inrush-Current Detection

Addr. Parameter C Setting Options Default Setting


_:106 Inrush detect.:Operat.- 1 A @ 100 Irated 0.030 A to 35.000 A 7.500 A
range limit Imax 5 A @ 100 Irated 0.15 A to 175.00 A 37.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 7.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 37.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 7.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 37.500 A
_:111 Inrush detect.:Blocking • no yes
with CWA
• yes
_:110 Inrush detect.:Blocking • no yes
with 2. harmonic
• yes
_:102 Inrush detect.:2nd 10 % to 45 % 15 %
harmonic content
_:112 Inrush detect.:Cross- • no no
blocking
• yes
_:109 Inrush detect.:Cross- 0.03 s to 200.00 s 0.06 s
blocking time
_:114 Inrush detect.:Start • no yes
flt.rec
• yes

6.8.6 Information List

No. Information Data Class Type


(Type)
Inrush detect.
_:81 Inrush detect.:>Block stage SPS I
_:54 Inrush detect.:Inactive SPS O
_:52 Inrush detect.:Behavior ENS O
_:53 Inrush detect.:Health ENS O
_:300 Inrush detect.:2.harmonic phase A SPS O
_:301 Inrush detect.:2.harmonic phase B SPS O
_:302 Inrush detect.:2.harmonic phase C SPS O
_:305 Inrush detect.:CWA SPS O
_:306 Inrush detect.:Cross-blocking SPS O
_:55 Inrush detect.:Pickup ACD O

SIPROTEC 5, 7SJ82/7SJ85, Manual 543


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.9 Instantaneous High-Current Tripping

6.9 Instantaneous High-Current Tripping

6.9.1 Overview of Functions

The Instantaneous high-current tripping function has the following tasks:

• Instantaneous tripping when switching onto an existing fault, for example, if a grounding switch is
closed.

• Instantaneous disconnection of high currents above the highest overcurrent-protection stage.

6.9.2 Structure of the Function

The Instantaneous high-current tripping function offers 2 different increment types:

• Stage with standard release method

• Stage with release method via protection interface (only applicable if the device is equipped with a
protection interface)
The function with the stage for the standard release procedure is factory-set.

[dwihcstr-230211-01.tif, 1, en_US]

Figure 6-86 Structure/Embedding of the Function

544 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.9 Instantaneous High-Current Tripping

6.9.3 Standard Release Procedure

Logic

[lo_hlore3, 2, en_US]

Figure 6-87 Logic Diagram of Instantaneous High-Current Tripping with Standard Release Method

Activation
Using the Activation parameter, you set the conditions under which the stage is released.

• on CB closure
With this procedure, the stage is released only if the circuit breaker is about to be closed (the CB is open)
or if the circuit breaker is being closed or if the binary input signal >release is active. The way signals
are generated Rel. by CB switch on is described in chapter 5.7.8 Circuit-Breaker Position Recogni-
tion for Protection-Related Auxiliary Functions.

• always active
The stage is always released and is thus independent of closing of the circuit breaker switch and of the
binary input signal >release.

SIPROTEC 5, 7SJ82/7SJ85, Manual 545


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.9 Instantaneous High-Current Tripping

• only with binary signal


The stage is released only if the binary input signal >release is active.

Method of Measurement, Threshold Value


The stage works with 2 different methods of measurement:

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically. A DC component is thus eliminated. The RMS value of the fundamental compo-
nent is compared with the set threshold.

• Evaluation of the unfiltered measurand:


The stage also works with unfiltered sampled values. Thus, very short operate times are possible. The
current sampling values are compared with a threshold value of 2 · √2 of the preset threshold value.

6.9.4 Application and Setting Notes

Parameter: Activation

• Default setting (_:3901:101) Activation = on CB closure


Using the parameter Activation, you define the conditions under which the stage is released.
Parameter Value Description
on CB closure Select this setting to activate the stage only when the circuit breaker is closed.
always active Select this setting to release the stage statically.
only with binary Select this setting to release the stage via an external signal.
signal

Parameter: Threshold

• Default setting (_:3901:3) Threshold = 10.0 A for Irated = 1 A or 50.0 A for Irated = 5 A

The stage works independently of the position of the remote circuit breakers. For this reason, set the
Threshold so that the fault current flowing through does not trigger the stage. Thus, use this stage only if
current grading over the protected object is possible, that is, for transformers, shunt reactors or long lines with
low source impedance. In other cases, deactivate the stage.

EXAMPLE
Calculation example for current grading of a 110 kV overhead line measuring 150 mm2
s (length) = 100 km;
R1/s = 0.21 Ω/km;
X1/s = 0.43 Ω/km
Since the stage is non-directional, the calculation must consider the maximum short-circuit power at the start
of the line or at the opposite end:
Ssc" = 3.5 GVA (subtransient, because the function can respond to the 1st peak value)
Current transformer: 600 A/5 A
The line impedance ZL and the minimum source impedance ZS are calculated on this basis:

[foglchzv-170309-01.tif, 1, en_US]

546 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.9 Instantaneous High-Current Tripping

The maximum 3-phase short-circuit current I"sc flowing through is (at a source voltage of 1.1 VN):

[foglchik-170309-01.tif, 1, en_US]

With a safety margin of 10 %, the following setting value results:

[foglnste-170309-01.tif, 1, en_US]

If short-circuit currents exceed 1496 A (primary) or 12.5 A (secondary), there is a short circuit on the line to be
protected. It can be disconnected immediately.

NOTE

i The calculation was performed with absolute values, which is accurate enough for overhead lines. A
complex calculation is required only if the source impedance and the line impedance have extremely
different angles.

Parameter: Dropout ratio

• Recommended setting value (_:3901:4) Dropout ratio = 0.90


The recommended setting value of 0.90 is sufficient for many applications. To obtain high-precision measure-
ments, the Dropout ratio can be reduced. If you expect highly fluctuating measurands at the pickup
threshold, you can increase the setting value of the parameter Dropout ratio. This avoids chattering of the
tripping stage.

6.9.5 Release Procedure via Protection Interface

This stage can be applied only if the device is equipped with a protection interface.

SIPROTEC 5, 7SJ82/7SJ85, Manual 547


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.9 Instantaneous High-Current Tripping

Logic

[lohinre3-160611-01.tif, 1, en_US]

Figure 6-88 Logic Diagram of Instantaneous High-Current Tripping with Release Procedure via Protection
Interface

Release
If one of the following conditions is fulfilled, the stage is released (the internal Release signal is present) (for
further information, see chapter 5.8 Process Monitor):

• No voltage has yet been applied to the protected object, which means that the remote circuit breakers
are open, or

• Switching to the local circuit breaker is imminent.


These conditions are recognized internally if a circuit breaker is open or just closed
Furthermore, the stage can be activated externally via the >release binary input signal.

NOTE

i To enable internal release of the stage, the devices at all ends of the protected object must be informed of
the circuit-breaker position (the circuit-breaker auxiliary contacts must be connected to the devices; the
respective binary input signals must be routed).

Method of Measurement, Threshold Value


The stage works with 2 different methods of measurement.

548 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.9 Instantaneous High-Current Tripping

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically. A DC component is thus eliminated. The RMS value of the fundamental compo-
nent is compared with the set threshold value.

• Evaluation of the unfiltered measurand:


If the current exceeds a preset threshold value by
current ≥ 2·√2·threshold value
this stage will use unfiltered measurands in addition. Thus, very short operate times are possible.

6.9.6 Application and Setting Notes

Parameter: Threshold

• Default setting (_:3901:3) Threshold = 2.5 A for Irated = 1 A or 12.5 A for Irated = 5 A

Select the value high enough for the protection not to pick up on the RMS value of the inrush current that
occurs when the local circuit breaker is closed. You do not have to consider short-circuit currents flowing
through, because the stage is released only if the circuit breakers are opened at all remote ends of the
protected object or the release was caused by the binary input >release.

Parameter: Dropout ratio

• Recommended setting value (_:3901:4) Dropout ratio = 0.90


The recommended setting value of 0.90 is sufficient for many applications. To obtain extremely accurate
measurements, the dropout ratio can be reduced. If you expect highly fluctuating measurands at the pickup
threshold, you can increase the dropout ratio. This avoids chattering of the tripping stage.

6.9.7 Settings

Addr. Parameter C Setting Options Default Setting


Standard 1
_:3901:1 Standard 1:Mode • off on
• on
• test
_:3901:101 Standard 1:Activation • on CB closure on CB closure
• only with binary signal
• always active
_:3901:3 Standard 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 10.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 50.000 A
_:3901:4 Standard 1:Dropout ratio 0.50 to 0.90 0.90

SIPROTEC 5, 7SJ82/7SJ85, Manual 549


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.9 Instantaneous High-Current Tripping

6.9.8 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Standard 1
_:3901:500 Standard 1:>release SPS I
_:3901:81 Standard 1:>Block stage SPS I
_:3901:54 Standard 1:Inactive SPS O
_:3901:52 Standard 1:Behavior ENS O
_:3901:53 Standard 1:Health ENS O
_:3901:300 Standard 1:Rel. by CB switch on ACT O
_:3901:55 Standard 1:Pickup ACD O
_:3901:57 Standard 1:Operate ACT O

550 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

6.10 Arc Protection

6.10.1 Overview of Function

The function Arc protection:

• Detects arcs in air-insulated switchgear parts without delay and in a fail-safe way

• Limits system damage through instantaneous high-speed tripping

• Protect systems from thermal overload

• Increases safety of personnel

• Trips in a 3-pole way

• Is suitable for use in all voltage levels

6.10.2 Structure of the Function

The Arc protection function can be added to function groups that provide current measured values.
The Arc protection function consists of the following blocks.

• General

• 3 stages

• Output logic 3-phase


The Arc protection function is preconfigured with 3 stages. A maximum of 17 tripping stages can be operated
simultaneously in the function. The tripping stages have an identical structure.
The following figure shows the basic structure of the Arc protection function.

[dw_structure_arcprot, 2, en_US]

Figure 6-89 Structure/Embedding of the Arc Protection Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 551


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

6.10.3 Function Description

General Logic of the Function Block

[lo_fb0_arcprot, 3, en_US]

Figure 6-90 General Logic Diagram of the Function Block

552 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

Logic of the Stage

[lo_stage_arcprotection, 1, en_US]

Figure 6-91 Logic Diagram of the Stage

TheArc protection function uses a locally connected optical arc sensor or an external trip initiation by other
devices in order to detect arcs.

NOTE

i Install the arc sensors inside the switchgear in such a way that they are not hidden behind other system
components!
Shadowing of the arc sensors must be avoided!

NOTE

i Once an optical sensor has detected an arc, you must replace the affected optical sensor!

Within the Arc protection function, you can use a fast current-flow criterion as an additional release criterion.
The parameters for the current-flow criterion can be found in the General block. For each stage, you can
select individually whether the current-flow criterion must be evaluated as well.

SIPROTEC 5, 7SJ82/7SJ85, Manual 553


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

Method of Measurement, Current-Flow Criterion


The current-flow criterion works with 2 different methods of measurement.

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically. A direct-current component is thus eliminated. The RMS value of the funda-
mental component is compared with the set threshold value.

• Evaluation of the unfiltered measurand:


If the current exceeds the threshold value set by the current amount ≥ 2 ⋅√2 ⋅threshold value, the stage
uses additional unfiltered measurands. Thus, very short operate times are possible.

NOTE

i If using the current-flow criterion in addition to the light, prevent a potential overfunction caused by the
suddenly occurring light signal.
If you use the current-flow criterion, arcs are typically detected in 4 ms!

Self Monitoring
The Arc protection function uses a self-monitoring circuit. This circuit monitors the optical arc sensors and the
fiber-optic cables. The arc-protection module uses the fiber-optic cable to send a cyclic test signal (light) to the
arc sensors. If the channel is operating properly, the test signal is sent back to the arc protection module. If the
test signal is not returned to the arc protection module, the indication channel # Sensor failure is
generated.
If the self-monitoring function detects a fault, the indication Health is set to Alarm and the stage/function is
blocked.

6.10.4 Application and Setting Notes – General Settings

Go to General under the function Arc protection and set the following parameters. The setting values apply
to all stages.

Parameter: Threshold I>

• Default setting (_:2311:3) Threshold I> = 2.000 A


Use the parameter Threshold I> to define the trigger threshold of the phase currents. The Threshold I>
is relevant for the current-flow criterion of the Arc protection function.
Set the Threshold I> of the function Arc protection in such a manner that the RMS value of the inrush
current does not exceed the Threshold I> when activating the local circuit breaker.
For more information about how to calculate the setting value, refer to 6.3.4.2 Application and Setting Notes .

Parameter: Threshold 3I0>

• Default setting (_:2311:4) Threshold 3I0> = 1.000 A


Use the parameter Threshold 3I0> to determine the tripping threshold for the zero-sequence current. The
Threshold 3I0> is relevant for the current-flow criterion of the Arc protection function.
Set the Threshold 3I0> of the function Arc protection in such a manner that the RMS value of the inrush
current does not exceed the Threshold 3I0> when activating the local circuit breaker.
For more information about how to calculate the setting value, refer to 6.5.4.2 Application and Setting Notes

NOTE

i If you set the parameter CT connection = 3-phase, 2 primary CT for the 3-phase current meas-
uring point, the parameter Threshold 3I0> has no effect.

554 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

6.10.5 Application and Setting Notes for the Stage

Parameter: External trip initiation

• Default setting (_:14551:9) External trip initiation = no


With the External trip initiation parameter, you set whether an external input signal is used to
trigger the stage.
Parameter Value Description
no The stage does not operate with an external input signal.
current The stage operates with an external input signal.
If the stage operates with an external input signal, the binary input signal
>External current must be routed in the DIGSI 5 information routing.
In this setting option, the binary input signal >External current is only
visible in the DIGSI 5 information routing
light The stage operates with an external input signal.
If the stage operates with an external input signal, the binary input signal
>External light must be routed in the DIGSI 5 information routing. In
this setting option, the binary input signal >External light is only
visible in the DIGSI 5 information routing
Note: When working with the light external trip initiation, do not select a
channel. If an additional channel is selected with this setting value, the
DIGSI 5 will signal an inconsistency.

Parameter: Operating mode

• Default setting (_:14551:8) Operating mode = current and light


With the Operating mode parameter, you define the basic functionality of the stage.
Parameter Value Description
current and light The stage operates with the input variables current and light.
The current-flow criterion ensures that the light signal originates from an
arc.
Siemens recommends using this setting value.
light only This stage operates only with the input signal 'light' and is triggered even if
current is not measured.
This operating mode can cause a overfunction if light is detected suddenly.
Use this setting value only if the effect caused by external light signals is
impossible.

Parameter: Sensor

• Default setting (_:14551:11) Sensor = point sensor


With the Sensor parameter, you set which sensor type is connected to the device.
Parameter Value Description
point sensor A point sensor is connected to the device.
line sensor A line sensor is connected to the device.
custom If you select this setting option, the parameter Threshold light is
visible.
Siemens recommends the default setting values point sensor or line
sensor. This allows arcs to be detected reliably regardless of diffused light.

Parameter: Threshold light

• Default setting (_:14551:7) Threshold light = -20.00 dB

SIPROTEC 5, 7SJ82/7SJ85, Manual 555


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

With the Threshold light parameter, you set the light sensitivity. If you set Threshold light to a
smaller value, the sensitivity increases. If you set Threshold light to a higher value, the sensitivity
decreases. If the sensors even pick up in case of a switching arc of the circuit breaker, set the Threshold
light parameter to a higher value.
Siemens recommends the default settings for point or line sensors.
Set the parameter Threshold light manually only if you have special default settings for light sensitivity.

Parameter: Channel

• Default setting (_:14551:10) Channel = No channel is selected


With the Channelparameter, you select which sensor channel the stage uses.
If the Arc protection function has several stages, a different channel must be selected for each stage.
For parameter Channel, the selection texts are identical to the name of the arc-protection module and its
channels.

6.10.6 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:3 General:Threshold I> 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 10.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 10.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:2311:4 General:Threshold 3I0> 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
Stage 1
_:14551:1 Stage 1:Mode • off off
• on
• test
_:14551:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:14551:9 Stage 1:External trip • no no
initiation
• current
• light
_:14551:8 Stage 1:Operating mode • light only current and light
• current and light
_:14551:11 Stage 1:Sensor • point sensor point sensor
• line sensor
• custom
_:14551:7 Stage 1:Threshold light -34.00 dB to -10.00 dB -20.00 dB
_:14551:10 Stage 1:Channel Setting options depend on
configuration

556 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

Addr. Parameter C Setting Options Default Setting


Stage 2
_:14552:1 Stage 2:Mode • off off
• on
• test
_:14552:2 Stage 2:Operate & • no no
flt.rec. blocked
• yes
_:14552:9 Stage 2:External trip • no no
initiation
• current
• light
_:14552:8 Stage 2:Operating mode • light only current and light
• current and light
_:14552:11 Stage 2:Sensor • point sensor point sensor
• line sensor
• custom
_:14552:7 Stage 2:Threshold light -34.00 dB to -10.00 dB -20.00 dB
_:14552:10 Stage 2:Channel Setting options depend on
configuration
Stage 3
_:14553:1 Stage 3:Mode • off off
• on
• test
_:14553:2 Stage 3:Operate & • no no
flt.rec. blocked
• yes
_:14553:9 Stage 3:External trip • no no
initiation
• current
• light
_:14553:8 Stage 3:Operating mode • light only current and light
• current and light
_:14553:11 Stage 3:Sensor • point sensor point sensor
• line sensor
• custom
_:14553:7 Stage 3:Threshold light -34.00 dB to -10.00 dB -20.00 dB
_:14553:10 Stage 3:Channel Setting options depend on
configuration

6.10.7 Information List

No. Information Data Class Type


(Type)
General
_:2311:82 General:>Block function SPS I
_:2311:53 General:Health ENS O
_:2311:301 General:Current detected SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O

SIPROTEC 5, 7SJ82/7SJ85, Manual 557


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

No. Information Data Class Type


(Type)
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:14551:81 Stage 1:>Block stage SPS I
_:14551:501 Stage 1:>External current SPS I
_:14551:502 Stage 1:>External light SPS I
_:14551:54 Stage 1:Inactive SPS O
_:14551:52 Stage 1:Behavior ENS O
_:14551:53 Stage 1:Health ENS O
_:14551:318 Stage 1:Fault arc counter INC C
_:14551:58 Stage 1:Arc detected SPS O
_:14551:301 Stage 1:Light detected SPS O
_:14551:55 Stage 1:Pickup ACD O
_:14551:57 Stage 1:Operate ACT O
Stage 2
_:14552:81 Stage 2:>Block stage SPS I
_:14552:501 Stage 2:>External current SPS I
_:14552:502 Stage 2:>External light SPS I
_:14552:54 Stage 2:Inactive SPS O
_:14552:52 Stage 2:Behavior ENS O
_:14552:53 Stage 2:Health ENS O
_:14552:318 Stage 2:Fault arc counter INC C
_:14552:58 Stage 2:Arc detected SPS O
_:14552:301 Stage 2:Light detected SPS O
_:14552:55 Stage 2:Pickup ACD O
_:14552:57 Stage 2:Operate ACT O
Stage 3
_:14553:81 Stage 3:>Block stage SPS I
_:14553:501 Stage 3:>External current SPS I
_:14553:502 Stage 3:>External light SPS I
_:14553:54 Stage 3:Inactive SPS O
_:14553:52 Stage 3:Behavior ENS O
_:14553:53 Stage 3:Health ENS O
_:14553:318 Stage 3:Fault arc counter INC C
_:14553:58 Stage 3:Arc detected SPS O
_:14553:301 Stage 3:Light detected SPS O
_:14553:55 Stage 3:Pickup ACD O
_:14553:57 Stage 3:Operate ACT O

Information about the self-monitoring function of the arc protection module

No. Information Data Class Type


(Type)
channel #
_:307 channel #:Sensor failure SPS O

558 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

6.10.8 Application Example for Arc Protection with Point Sensors in Operating Mode:
Light Only

6.10.8.1 Description

Overview
The example describes the Arc protection function in a medium-voltage switchgear with one infeed and
2 feeders. The Arc protection function operates with the Operating mode = light only.
The following items are considered in the example below:

• Positioning the optical point sensors in the switchgear

• Connecting the optical point sensors to the protection devices in the feeders and the infeed

• Number of necessary stages of the functions in the protection devices of the feeders and the infeed

• Setting notes about the selected parameters in the stages of the function
The following figure shows the arrangement and the connection of the optical point sensors:

[dw_arcprot-light-only, 2, en_US]

Figure 6-92 Layout and Connection of the Optical Point Sensors (Operating Mode = Light only)

For this example, the following is assumed:

• The circuit breaker of the infeed must be switched off. This ensures that the arcs in the busbar compart-
ments of the infeed and the feeders or in the circuit-breaker compartment of the feeders are off.
Install the optical point sensors in the busbar compartments (BB compartment) of the infeed and feeders.
Install additional optical point sensors in the circuit-breaker compartment (CB compartment) of the
feeders. Connect all optical point sensors to the protection device of the infeed.

SIPROTEC 5, 7SJ82/7SJ85, Manual 559


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

• The optical point sensors in the cable-connection compartment of the feeders detect arcs in this compart-
ment. Install one optical point sensor in the cable-connection compartment of the feeders and connect it
to the protection device of the feeder. This allows for the selective clearing of arcs inside the cable-
connection compartment.
Due to the pressure waves that occur during the formation of an arc, partitions can deform and cause
undesirable light influences in adjacent compartments. This can result in a non-selective tripping.

• If there is an arc in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device must switch off.

NOTE

i If the Arc protection function operates in Operating mode = light only, the effects of external light
can result in non-selective tripping.

NOTE

i It must be considered that the number of arc protection modules connected to the device depends on the
hardware configuration of the device.
When using modular devices, a maximum of 15 sensors can be connected. If using non-modular devices, a
maximum of 6 sensors (3 sensors per module) can be connected.

6.10.8.2 Application and Setting Notes

General Notes

• Connect one optical point sensor from the cable-connection compartment in feeder 1 to the protection
device in feeder 1. Arcs in the cable-connection compartment are cleared selectively by the circuit
breaker in feeder 1.

• Connect one optical point sensor from the cable-connection compartment in feeder 2 to the protection
device in feeder 2. Arcs in the cable-connection are cleared selectively by the circuit breaker in feeder 2.

• Connect optical point sensors from all busbar compartments and all circuit-breaker compartments of
feeders 1 and 2 to the protection device in the infeed. Arcs in these compartments are detected and
cleared by the device in the infeed.

Setting Notes for the Protection Device in Feeder 1


The Arc protection function operates with one stage.
Set the parameters of the stage as follows:

• Parameter: Operating mode = light only

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = no

• Parameter: Channel = Arc mod. 1 channel 1


The parameters in block General are not relevant since the Operating mode = light only.

Setting Notes for the Protection Device in Feeder 2


The Arc protection function operates with one stage.
Set the parameters of the stage as follows:

• Parameter: Operating mode = light only

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = no

• Parameter: Channel = Arc mod. 1 channel 1

560 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

The parameters in block General are not relevant since the Operating mode = light only.

Setting Notes for the Protection Device in the Infeed


The Arc protection function operates with 5 stages.
Set the parameters of the stages as follows:

• Parameter: Operating mode = light only (applies to all stages)

• Parameter: Sensor = point sensor (applies to all stages)

• Parameter: External trip initiation = no (applies to all stages)

• Parameter: Channel = Arc mod. 1 channel 1 (Stage 1) → Busbar compartment supervision in


feeder 1
Parameter: Channel = Arc mod. 1 channel 2 (Stage 2) → Circuit-breaker compartment supervision
in feeder 1
Parameter: Channel = Arc mod. 1 channel 3 (Stage 3) → Busbar compartment supervision in
feeder 2
Parameter: Channel = Arc mod. 2 channel 1 (Stage 4) → Circuit-breaker compartment supervision
in feeder 2
Parameter: Channel = Arc mod. 2 channel 2 (Stage 5) → Busbar compartment supervision in the
infeed
The parameters in block General are not relevant since the Operating mode = light only.

6.10.9 Application Example for Arc Protection with Point Sensors in Operating Mode:
Light and Current

6.10.9.1 Description

Overview
The example describes the Arc protection function in a medium-voltage switchgear with one infeed and 2
feeders. The Arc protection function operates with the Operating mode = current and light. In the
example, all arcs are detected by the protection device in the infeed.
The following items are considered in the example:

• Positioning the optical point sensors in the switchgear

• Connecting the optical point sensors to the protection devices in the feeders and the infeed

• Number of necessary stages of the functions in the protection devices of the feeders and the infeed

• Setting notes about selected parameters in the stages of the function

SIPROTEC 5, 7SJ82/7SJ85, Manual 561


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

[dw_light-and-current, 2, en_US]

Figure 6-93 Layout and Connection of the Optical Point Sensors (Operating Mode = Current and Light)

For this example, the following is assumed:

• The current-flow criterion offers additional security to prevent unwanted tripping caused by sudden light
influences.
Depending on the arc location in the cable-connection compartment of the feeder, it is not always
possible to measure the current. If an arc is detected in the cable-connection compartment of the feeder,
the current will therefore be evaluated in the infeed.

• Install the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the
cable-connection compartment of the feeders as well as the busbar compartment of the infeed. Connect
the optical point sensors to the protection device in the infeed.

• The protection device in the infeed clears all arcs in the busbar compartment, the circuit-breaker
compartment, and the cable-connection compartment of feeder 1 and 2. Furthermore, the protection
device clears arcs in the busbar compartment of the infeed.

• If the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the cable-
connection compartment of the feeders, or in the busbar compartment of the infeed detect an arc, the
protection device in the infeed evaluates the current as well.

• If an arc occurs in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device must trip.

NOTE

i If the Arc protection function operates with the Operating mode = current and light, the addi-
tional current-flow criterion prevents unwanted tripping caused by external light influences.

562 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

NOTE

i This application example requires the connection of several optical point sensors to a single protection
device. It must be considered that the number of arc-protection modules that are connected to the device
depends on the hardware configuration of the device.
When using modular devices, a maximum of 15 sensors can be connected. If you use non-modular devices,
a maximum of 6 sensors (3 sensors per module) can be connected.

6.10.9.2 Application and Setting Notes

General Notes

• Connect the optical point sensors from the busbar compartment, the circuit-breaker compartment, and
the cable-connection compartment of feeders 1 and 2 to the protection device in the infeed. Arcs in the
busbar compartment, the circuit-breaker compartment and the cable-connection compartment of
feeders 1 and 2 are detected and cleared by the device in the infeed.

• Connect an optical point sensor from the busbar compartment in the infeed to the protection device in
the infeed. Arcs in the busbar compartment of the infeed are cleared selectively by the circuit breaker in
the infeed.

Setting Notes for the Protection Device in the Infeed


The Arc protection function operates with 7 stages.
Set the parameters of the stages as follows:

• Parameter: Operating mode = current and light (applies to all stages)

• Parameter: Sensor = point sensor (applies to all stages)

• Parameter: External trip initiation = no (applies to all stages)

• Parameter: Channel = Arc mod. 1 channel 1 (Stage 1) → Busbar compartment supervision in


feeder 1
Parameter: Channel = Arc mod. 1 channel 2 (Stage 2) → Circuit-breaker compartment supervision
in feeder 1
Parameter: Channel = Arc mod. 1 channel 3 (Stage 3) → Cable-connection compartment supervi-
sion in feeder 1
Parameter: Channel = Arc mod. 2 channel 1 (Stage 4) → Busbar compartment supervision in
feeder 2
Parameter: Channel = Arc mod. 2 channel 2 (Stage 5) → Circuit-breaker compartment supervision
in feeder 2
Parameter: Channel = Arc mod. 2 channel 3 (Stage 6) → Cable-connection compartment supervi-
sion in feeder 2
Parameter: Channel = Arc mod. 3 channel 1 (Stage 7) → Busbar compartment supervision in the
infeed
You can find more information about the settings of the parameters Threshold I> and Threshold 3I0>
in chapter 6.10.4 Application and Setting Notes – General Settings.

6.10.10 Application Example for Arc Protection with Point Sensors via External Trip
Initiation

6.10.10.1 Description

Overview
The example describes the Arc protection function in a medium-voltage switchgear with one infeed and
2 feeders. The stages of the Arc protection function are triggered by External trip initiation.

SIPROTEC 5, 7SJ82/7SJ85, Manual 563


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

The following items are considered in the example below:

• Positioning the optical point sensors in the switchgear

• Connecting the optical point sensors to the protection devices in the feeders and the infeed

• Number of necessary stages of the functions in the protection devices of the feeders and the infeed

• Setting notes about the selected parameters in the stages of the function

[dw_arcprot-extern-input, 3, en_US]

Figure 6-94 Arc Protection with External Trip Initiation

For this example, the following is assumed:

• Install the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the
cable-connection compartment of the feeder and the infeed. Connect the optical point sensors to the
respective protection device in the feeder and infeed.

• If the optical point sensors detect an arc in the busbar compartment or the circuit-breaker compartment
of the feeders, the Light detected indication is sent via binary inputs/outputs, a protection interface,
or IEC 61850 GOOSE to the protection device in the infeed. Then, the protection device in the infeed
evaluates the current as well. If the measured current exceeds the thresholds Threshold I> and/or
Threshold 3I0>, the protection device in the infeed switches off the malfunction.
You can find detailed information in chapter 6.10.10.2 Application and Setting Notes

• Arcs in the cable-connection compartment of the feeders can also be switched off selectively by the
protection device of the affected feeder. To do this, the Current detected pickup indication from the
infeed unit must be sent to the appropriate protection device in the feeder.

• If an arc occurs in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device trips.

564 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

NOTE

i If the Arc protection function operates via the External trip initiation, only 3 optical point
sensors are required per feeder protection device in order to detect the arcs (only one arc-protection
module).
The number of GOOSE messages is not limited. Therefore, the number of feeders is not limited, and the
protection of complex systems is feasible.

6.10.10.2 Application and Setting Notes

General Notes:

• Install the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the
cable-connection compartment of the feeders and the infeed to the respective protection devices.

• Arcs in the busbar compartment and the circuit-breaker compartment of the feeders must be switched
off by the protection device in the infeed. To do this, the protection devices in the feeder device must
send the indication Light detected to the infeed device. Use the binary inputs/outputs, a protection
interface, or IEC 61850 GOOSE.
The protection device in the infeed evaluates the current. If the measured current exceeds the
Threshold I> and/or Threshold 3I0> threshold values, the protection device in the infeed switches
off faults on the busbar and the circuit-breaker compartment of the feeders.
Connect the signals over 4 stages, using the external trip initiation or a CFC chart.

• Arcs in the cable-connection compartment of the feeders are switched off locally. The protection device
in the infeed evaluates the current. If the measured current exceeds the threshold values Threshold
I> and/or Threshold 3I0>, the Current detected indication is sent to the protection devices in
the feeders. If, at the same time, an optical sensor in a cable-connection compartment detects light, the
protection device trips in the corresponding feeder.

Setting Notes for the Protection Device in Feeder 1


The Arc protection function operates with 3 stages.
Stage 1 and 2 (supervision of busbar compartment and circuit-breaker compartment):
Set the parameters of the stages as follows:

• Parameter: Operating mode = light only

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = no

• Parameter: Operate & flt.rec. blocked = yes

• Parameter: Channel = (Stage 1) → busbar-compartment supervision in feeder 1


Parameter: Channel = (Stage 2) → circuit-breaker compartment supervision in feeder 1
Stage 3 (supervision of cable-connection compartment):
Set the parameters of the stage as follows:

• Parameter: Operating mode = current and light

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = current


The protection device in the infeed evaluates the current. If the measured current exceeds the threshold
values Threshold I> and/or Threshold 3I0>, the protection device in the infeed returns the indica-
tion Current detected to the protection device in the feeder.
Only if the indication in the feeder device Current detected is connected with the signal >External
current an external trip initiation for this stage is effective.

SIPROTEC 5, 7SJ82/7SJ85, Manual 565


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

• Parameter: Operate & flt.rec. blocked = no

• Parameter: Channel =

Setting Notes for the Protection Device in Feeder 2


The Arc protection function operates with 3 stages.
Stage 1 and 2 (supervision of busbar compartment and circuit-breaker compartment):
Set the parameters of the stages as follows:

• Parameter: Operating mode = light only

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = no

• Parameter: Operate & flt.rec. blocked = yes

• Parameter: Channel = (Stage 1) → busbar-compartment supervision in feeder 2


Parameter: Channel = (Stage 2) → circuit-breaker compartment supervision in feeder 2
Stage 3 (supervision of cable-connection compartment):
Set the parameters of the stage as follows:

• Parameter: Operating mode = current and light

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = current


The protection device in the infeed evaluates the current. If the measured current exceeds the threshold
values Threshold I> and/or Threshold 3I0>, the protection device in the infeed returns the indica-
tion Current detected to the protection device in the feeder.
Only if the indication in the feeder device Current detected is connected with the signal >External
current an external trip initiation for this stage is effective.
• Parameter: Operate & flt.rec. blocked = no

• Parameter: Channel =

Setting Notes for the Protection Device in the Infeed


The Arc protection function operates with 7 stages.
Stage 1 (busbar-compartment supervision):

• Parameter: Operate & flt.rec. blocked = no


If an arc is detected in the busbar compartment of the infeed and the thresholds Threshold I> and/or
Threshold 3I0> are exceeded, an operate indication is generated immediately.

• Parameter: Channel =

• Parameter: Operating mode = current and light

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = no


Stage 2 (circuit-breaker compartment supervision):

• Parameter: Operate & flt.rec. blocked = yes


If an arc is detected in the circuit-breaker compartment of the infeed (light-gray point sensors in
Figure 6-94), a pickup indication is generated immediately. The arc is switched off by a superordinate
protection device.

• Parameter: Channel =

• Parameter: Operating mode = current and light

566 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = no


Stage 3 (cable-connection compartment supervision):

• Parameter: Operate & flt.rec. blocked = yes


If an arc is detected in the cable-connection compartment of the infeed (light-gray point sensors in
Figure 6-94), a pickup indication is generated immediately. The arc is switched off by a superordinate
protection device.
Depending where the arc is generated in the cable-connection compartment of the infeed, it is not
always possible to measure the current. If an arc is detected in the cable-connection compartment of the
infeed, the current must be evaluated by the superordinate protection device.

• Parameter: Channel =

• Parameter: Operating mode = light only

• Parameter: Sensor = point sensor

• Parameter: External trip initiation = no


Stage 4 to 7 (External trip initiation):

• Parameter: Operate & flt.rec. blocked = no

• Parameter: Operating mode = current and light

• Parameter: External trip initiation = light


If an arc is detected in the busbar compartment or the circuit-breaker compartment of the feeder, the
feeder device sends the Light detected indication to the infeed device. Only if the indication in the
infeed device Light detected is connected with the signal >External light, an external trip
initiation via these stages is effective.
The protection device in the infeed evaluates the current. If the measured current exceeds the
Threshold I> and/or Threshold 3I0> threshold values, the protection device in the infeed switches
off the arc.

6.10.11 Application Example for Arc Protection with a Line Sensor in Operating Mode:
Light and Current

6.10.11.1 Description

Overview
The example describes the Arc protection function in a medium-voltage switchgear with 1 infeed and
2 feeders. The Arc protection function operates with the Operating mode = current and light. In the
example, all arcs are detected by the protection device in the infeed.
The following items are considered in the example below:

• Optical line sensor placement in the switchgear

• Optical line sensor connection to the protection device in the infeed

• Number of necessary stages of the functions in the infeed protection device

• Setting notes about the selected parameters in the stages of the function

SIPROTEC 5, 7SJ82/7SJ85, Manual 567


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

[dw_Liniensensor, 1, en_US]

Figure 6-95 Layout and Connection of the Optical Line Sensors (Operating Mode = Current and Light)

For this example, the following is assumed:

• The current-flow criterion offers additional protection to prevent unwanted tripping caused by the
sudden effects of light.

• Figure 6-95 shows how the optical line sensors should be routed. Start in the infeed busbar compartment
and route the optical line sensor along the busbar and back again to the protection device in the infeed.
Connect the optical line sensor to the protection device in the infeed.

• Depending on the routing options in the control cabinet, you can also route the optical line sensor
through the circuit-breaker and cable-connection compartments of the feeders.
If this is not possible, you can detect arcs in these compartments using point sensors. For more detailed
information, see chapters 6.10.8 Application Example for Arc Protection with Point Sensors in Operating
Mode: Light Only and 6.10.9 Application Example for Arc Protection with Point Sensors in Operating
Mode: Light and Current.

• If an arc occurs in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device will shut off.

NOTE

i If the Arc protection function operates with the Operating mode = current and light, the addi-
tional current-flow criterion will prevent unwanted tripping caused by external light effects.

NOTE

i Note that the number of arc protection modules that are connected to the device depend on the hardware
configuration of the equipment.
When using modular equipment, a maximum of 15 sensors can be connected. If using non-modular equip-
ment, a maximum of 6 sensors (3 sensors per module) can be connected.
Depending on the use case, you can combine point and line sensors.

568 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.10 Arc Protection

6.10.11.2 Application and Setting Notes

Setting Notes for the Protection Device in the Infeed


The Arc protection function operates with 1 stage.
Set the parameters of the stage as follows:

• Parameter: Operating mode = current and light

• Parameter: Sensor = line sensor

• Parameter: External trip initiation = no

• Parameter: Channel = Arc mod. 1 channel 1 (Stage 1) → Busbar compartment supervision (infeed,
feeder 1, feeder 2)
You can find more information about the settings of the parameters Threshold I> and Threshold 3I0>
in chapter 6.10.4 Application and Setting Notes – General Settings.

SIPROTEC 5, 7SJ82/7SJ85, Manual 569


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.11 Instantaneous Tripping at Switch onto Fault

6.11 Instantaneous Tripping at Switch onto Fault

6.11.1 Overview of Functions

The Instantaneous tripping at switch onto fault function serves for immediate tripping when switching onto
a fault.
The function does not have its own measurement and must be linked to another protection function with the
pickup (measurement).

6.11.2 Structure of the Function

The function Instantaneous tripping at switch onto fault can be used in all protection function groups . The
function is preconfigured with 1 stage. A maximum of 2 tripping stages can be operated simultaneously
within the function. The tripping stages have an identical structure.

[dwstrsto-030211-01.tif, 1, en_US]

Figure 6-96 Structure/Embedding of the Function

570 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.11 Instantaneous Tripping at Switch onto Fault

6.11.3 Stage Description

Logic of the Stage

[logisotf-170312-01.tif, 1, en_US]

Figure 6-97 Logic Diagram of the Stage Instantaneous Tripping at Switch onto Fault

Connection of the Stage


The stage is intended to initiate instantaneous tripping when switching onto a fault. To do this, the stage must
be connected to one or more pickups from protection functions or protection stages, for example, to pickup of
an overcurrent-protection stage. That is, the stage of the Instantaneous tripping at switch onto fault func-
tion does not have its own measuring function but requires the pickup of another protection function or
protection stage to pick up.
The stage is active only if switching is pending or executed (for this, see chapter 6.3 Overcurrent Protection,
Phases).

NOTE

i If a protection stage picks up and tripping is blocked by the Inrush-current detection function, the Instan-
taneous tripping at switch onto fault function does not pick up. In this case there is no fault recording
either.
Despite this, if a fault recording is necessary, you can activate it with the parameter (_:114) Start
flt.rec of the Inrush-current detection function (see chapter 6.8 Inrush-Current Detection).

6.11.4 Application and Setting Notes

Parameter: Configuration

• Default setting (_:5941:102) Configuration = no stage

SIPROTEC 5, 7SJ82/7SJ85, Manual 571


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.11 Instantaneous Tripping at Switch onto Fault

The Configuration parameter is used to define the pickup of a protection function or protection stage that
the Instantaneous tripping at switch onto fault function uses to respond.
Normally, the pickups of protection functions and stages with high fault current are selected:

• Distance protection

• Overcurrent protection (phase and ground)

• Directional overcurrent protection (phase and ground)


A specific protection stage is generally used. This can be one of the protection stages provided for the protec-
tion application, which itself trips with a delay. An additional protection stage with settings optimized for this
use case, for example, increased threshold value and blocking of self-tripping, can also be used.

Parameter: Operate delay

• Recommended setting value (_:5941:6) Operate delay = 0.00 s


When switching onto a fault, the tripping should usually be instantaneous. The tripping delay is therefore set
to 0.

6.11.5 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:5941:1 Stage 1:Mode • off off
• on
• test
_:5941:2 Stage 1:Operate & flt.rec. • no no
blocked
• yes
_:5941:6 Stage 1:Operate delay 0.00 s to 60.00 s 0.00 s
_:5941:102 Stage 1:Configuration Setting options depend on
configuration

6.11.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:5941:81 Stage 1:>Block stage SPS I
_:5941:54 Stage 1:Inactive SPS O
_:5941:52 Stage 1:Behavior ENS O
_:5941:53 Stage 1:Health ENS O
_:5941:55 Stage 1:Pickup ACD O
_:5941:57 Stage 1:Operate ACT O

572 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

6.12 Overcurrent Protection, 1-Phase

6.12.1 Function Overview

The Overcurrent protection, 1-phase function (ANSI 50N/51N):

• Detects and monitors the current measured in a transformer neutral point grounding

• Can operate as sensitive tank leakage protection

• Detects and monitors the circulating current between the neutral points of 2 capacitor banks

• Switches off high-current faults instantaneously

6.12.2 Structure of the Function

The Overcurrent protection, 1-phase function is used in protection function groups with 1-phase current
measurement. 2 function types are available:

• Overcurrent protection, 1-phase – advanced (50N/51N OC-1ph-A)

• Overcurrent protection, 1-phase – basic (50N/51N OC-1ph-B)


The function type Basic is provided for standard applications. The function type Advanced offers more func-
tionality and is provided for more complex applications.
Both function types are pre-configured by the manufacturer with 2 Definite-time overcurrent protection
stages and with 1 Inverse-time overcurrent protection stage.
In the function type Overcurrent protection, 1-phase – advanced the following stages can be operated
simultaneously:

• Maximum of 3 stages Definite-time overcurrent protection (UMZ)

• 1 stage Inverse-time overcurrent protection (AMZ)

• 1 stage Logarithmic inverse-time overcurrent protection

• 1 stage User-defined characteristic curve overcurrent protection

• 1 Fast stage
In the function type Overcurrent protection, 1-phase – basic, the following stages can operate simultane-
ously:

• Maximum of 3 stages Definite-time overcurrent protection

• 1 stage Inverse-time overcurrent protection


The non-preconfigured stages in Figure 6-98 and Figure 6-99 are shown in gray. Apart from the operate-delay
characteristic curve, the Definite-time overcurrent protection stage, the Inverse-time overcurrent protec-
tion stage, the Logarithmic inverse-time overcurrent protection stage, and the User-defined characteristic
curve-time overcurrent protection stage are structured identically.
The Fast stage uses a fast tripping algorithm. It is therefore suited in particular for sensitive ground-fault
detection according to the high-impedance principle.

SIPROTEC 5, 7SJ82/7SJ85, Manual 573


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

[dwocp1pa-280113-01.tif, 4, en_US]

Figure 6-98 Structure/Embedding the Function Overcurrent Protection, 1-Phase – Advanced

[dwocp1pb-310113-01.tif, 3, en_US]

Figure 6-99 Structure/Embedding the Function Overcurrent Protection, 1-Phase – Basic

If the device is equipped with the Inrush-current detection function, you can stabilize the stages against
issuing of the operate indication due to transformer inrush-currents.

574 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

6.12.3 Stage with Definite-Time Characteristic Curve

6.12.3.1 Description

Logic of a Stage

[loinvocp-270612-01.tif, 1, en_US]

Figure 6-100 Logic Diagram of the Definite-Time Overcurrent Protection, 1-Phase

Method of measurement
You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value.

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

SIPROTEC 5, 7SJ82/7SJ85, Manual 575


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

Blocking of the Stage


The picked up stage can reset completely via the binary input signal >Block stage.

Blocking of the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also tripping. A running time delay is reset. The pickup is reported and a fault is opened.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.
Blocking of tripping with the Inrush-current detection function is possible only if the following conditions
have been met:

• The central Inrush-current detection function has to be available in another protection function group
with 3-phase current measurement.

• You have to connect the protection function group with 1-phase current measurement to the protection
function group with 3-phase current measurement. You connect protection function groups in the
DIGSI 5 Project Tree → Name of the device → Function group connections.

Related Topics
6.3.7.1 Description

6.12.3.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:12661:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Threshold, Operate delay

• Default setting (_:12661:3) Threshold = 1.200 A (for the first stage)

• Default setting (_:12661:6) Operate delay = 0.300 s (for the first stage)
Set the Threshold and Operate delay parameters for the specific application.

576 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

6.12.3.3 Settings

Addr. Parameter C Setting Options Default Setting


Definite-T 1
_:12661:1 Definite-T 1:Mode • off off
• on
• test
_:12661:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:12661:27 Definite-T 1:Blk. w. • no no
inrush curr. detect.
• yes
_:12661:8 Definite-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:12661:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:12661:6 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay

6.12.3.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:12661:81 Definite-T 1:>Block stage SPS I
_:12661:500 Definite-T 1:>Block delay & op. SPS I
_:12661:54 Definite-T 1:Inactive SPS O
_:12661:52 Definite-T 1:Behavior ENS O
_:12661:53 Definite-T 1:Health ENS O
_:12661:60 Definite-T 1:Inrush blocks operate ACT O
_:12661:55 Definite-T 1:Pickup ACD O
_:12661:56 Definite-T 1:Operate delay expired ACT O
_:12661:57 Definite-T 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 577


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

6.12.4 Stage with Inverse-Time Characteristic Curve

6.12.4.1 Description

Logic of the Stage

[lodefocp-270612-01.tif, 1, en_US]

Figure 6-101 Logic Diagram of the Inverse-Time Overcurrent Protection (1-Phase)

Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI

When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout

578 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.

Method of Measurement
You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value.

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Blocking of the Stage


The picked up stage can reset completely via the binary input signal >Block stage.

Blocking of the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also tripping. A running time delay is reset. The pickup is reported and a fault is opened.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.
Blocking of tripping with the Inrush-current detection function is possible only if the following conditions
have been met:

• The central Inrush-current detection function has to be available in another protection function group
with 3-phase current measurement.

• You have to connect the protection function group with 1-phase current measurement to the protection
function group with 3-phase current measurement. You connect protection function groups in the
DIGSI 5 Project Tree → Name of the device → Function group connections.

6.12.4.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:12691:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 579


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

Parameter Value Description


fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Type of character. curve

• Default setting (_:12691:108) Type of character. curve = IEC normal inverse


The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application.

Parameter: Threshold

• Default setting (_:12691:3) Threshold = 1.200 A


Set the Threshold and Type of character. curve parameters for the specific application.
Note that a safety margin is set between pickup value and threshold value. The stage only picks up at approx.
10 % above the Threshold.

Parameter: Time dial

• Default setting (_:12691:101) Time dial = 1


Use the Time dial parameter to displace the characteristic curve in the time direction.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the param-
eter Time dial at 1 (default setting).

Parameter: Reset

• Default setting (_:12691:109) Reset = disk emulation


You use the Reset parameter to define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Use this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.

6.12.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Inverse-T 1
_:12691:1 Inverse-T 1:Mode • off off
• on
• test

580 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

Addr. Parameter C Setting Options Default Setting


_:12691:2 Inverse-T 1:Operate & • no no
flt.rec. blocked
• yes
_:12691:27 Inverse-T 1:Blk. w. inrush • no no
curr. detect.
• yes
_:12691:8 Inverse-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:12691:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:12691:108 Inverse-T 1:Type of char-
acter. curve
_:12691:109 Inverse-T 1:Reset • instantaneous disk emulation
• disk emulation
_:12691:101 Inverse-T 1:Time dial 0.05 to 15.00 1.00

6.12.4.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:12691:81 Inverse-T 1:>Block stage SPS I
_:12691:500 Inverse-T 1:>Block delay & op. SPS I
_:12691:54 Inverse-T 1:Inactive SPS O
_:12691:52 Inverse-T 1:Behavior ENS O
_:12691:53 Inverse-T 1:Health ENS O
_:12691:60 Inverse-T 1:Inrush blocks operate ACT O
_:12691:59 Inverse-T 1:Disk emulation running SPS O
_:12691:55 Inverse-T 1:Pickup ACD O
_:12691:56 Inverse-T 1:Operate delay expired ACT O
_:12691:57 Inverse-T 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 581


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

6.12.5 Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse


Characteristic Curve

6.12.5.1 Description

Logic of the Stage

[lo_ocp 1phase logarithmic, 1, en_US]

Figure 6-102 Logic Diagram of the Logarithmic Inverse-Time Overcurrent Protection (1-Phase)

Apart from the operate curve, this type of stage is identical to the Inverse-time overcurrent protection stage
(see chapter 6.12.4.1 Description ).
This section will only discuss the nature of the operate curve. For further functionality, refer to chapter
6.12.4.1 Description .

582 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

Operate Curve
If the function picks up, the logarithmic inverse-time characteristic curve is processed. A time value Top is
calculated for every input value exceeding 95 % of the pickup value. An integrator accumulates the value 1/
Top. If the accumulated integral reaches the fixed value 1, the stage operates.
The curve used to calculate the time value Top is shown in the following figure. The Threshold multi-
plier parameter defines the beginning of the characteristic curve. The Max. time of the curve deter-
mines the initial value of the characteristic curve. The Time dial parameter changes the slope of the charac-
teristic curve. At high currents, the Min. time of the curve parameter indicates the lower time limit.

[dw_ocp 1phase logarithmic, 1, en_US]

Figure 6-103 Operate Curve of Logarithmic Inverse-Time Characteristic

The time to operate is calculated with the following formula:

[fo_ocp 1phase logarithmic, 1, en_US]

Where
Tmax Maximum time of the curve (parameter Max. time of the curve)
Td Time dial (parameter Time dial)
Top Operate time
I 1-phase current
Ithresh Threshold value (parameter Threshold)
Imul Threshold multiplier (parameter Threshold multiplier)

If the calculated time is less than Tmin (parameter Min. time of the curve), Tmin is used.

SIPROTEC 5, 7SJ82/7SJ85, Manual 583


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

6.12.5.2 Application and Setting Notes


Apart from the operate curve, this type of stage is identical to the ground-fault protection type with inverse-
time delay according to IEC and ANSI (see chapter 6.12.4.1 Description ).
This section only discusses the nature of the operate curve. For further functionality, refer to chapter
6.12.4.2 Application and Setting Notes .

Stage Type Selection


If the operate delay is to be dependent on the current level according to a logarithmic characteristic curve,
select this stage type.

Parameter: Threshold

• Default setting (_:3) Threshold = 1.20 A


With the parameter Threshold, you define the pickup value corresponding to the application. In doing so,
for the time-graded stages, the setting for the superordinate and subordinate stages must be taken into
account in the grading chart.

Parameter: Threshold multiplier

• Default setting (_:116) Threshold multiplier = 1.1


With the parameter Threshold multiplier, you define the beginning of the characteristic curve on the
current axis (in relation to the threshold value).
General information cannot be provided. Define the value corresponding to the application.

EXAMPLE

Threshold (Secondary current) Ithresh = 1.2 A


Threshold multiplier Imul = 1.1
Pickup value (Secondary current) IPU = 1.2 A ×1.1 = 1.32 A

Parameter: Time dial

• Default setting (_:6) Time dial = 1.250 s


With the parameter Time dial, you change the slope of the characteristic curve.
General information cannot be provided. Define the value corresponding to the application.

Parameter: Max. time of the curve

• Default setting (_:114) Max. time of the curve = 5.800 s


The parameter Max. time of the curve determines the initial value of the characteristic curve (for I =
Threshold).
General information cannot be provided. Define the value corresponding to the application.

Parameter: Min. time of the curve

• Default setting (_:113) Min. time of the curve = 1.200 s


The parameter Min. time of the curve determines the lower time limit (at high currents).
General information cannot be provided. Define the value corresponding to the application.

Parameter: Additional time delay

• Default setting (_:115) Additional time delay = 0 s

584 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

With the parameter Additional time delay, you set an additional current-independent time delay. This
additional delay is intended for special applications.
Siemens recommends setting this time to 0 s so that it has no effect.

6.12.5.3 Settings

Addr. Parameter C Setting Options Default Setting


Log.-inv.-T #
_:1 Log.-inv.-T #:Mode • off off
• on
• test
_:2 Log.-inv.-T #:Operate & • no no
flt.rec. blocked
• yes
_:27 Log.-inv.-T #:Blk. w. • no no
inrush curr. detect.
• yes
_:8 Log.-inv.-T #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:3 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:6 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
_:113 Log.-inv.-T #:Min. time 0.000 s to 60.000 s 1.200 s
of the curve
_:114 Log.-inv.-T #:Max. time 0.000 s to 60.000 s 5.800 s
of the curve
_:116 Log.-inv.-T #:Threshold 1.00 to 4.00 1.10
multiplier
_:115 Log.-inv.-T #:Additional 0.000 s to 60.000 s 0.000 s
time delay

6.12.5.4 Information List

No. Information Data Class Type


(Type)
Log.-inv.-T #
_:81 Log.-inv.-T #:>Block stage SPS I
_:500 Log.-inv.-T #:>Block delay & op. SPS I
_:54 Log.-inv.-T #:Inactive SPS O
_:52 Log.-inv.-T #:Behavior ENS O
_:53 Log.-inv.-T #:Health ENS O
_:60 Log.-inv.-T #:Inrush blocks operate ACT O
_:55 Log.-inv.-T #:Pickup ACD O
_:56 Log.-inv.-T #:Operate delay expired ACT O
_:57 Log.-inv.-T #:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 585


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

6.12.6 Stage with User-Defined Characteristic Curve

6.12.6.1 Description
The User-defined characteristic curve overcurrent protection stage is only available in the advanced func-
tion type.
This stage is structured the same way as the stage with the inverse-time characteristic curve. The only differ-
ence is that you can define the characteristic curve as desired.

User-Defined Characteristic Curve


With the user-defined characteristic curve, you can define the operate curve point by point using up to 30
value pairs of current and time. The device uses linear interpolation to calculate the characteristic curve from
these values. You can also define a dropout characteristic curve if you wish.

Pickup and Dropout Behaviors with the User-Defined Characteristic Curve


When the input variable exceeds the threshold value by 1.1 times, the characteristic curve is processed.
An integrating method of measurement totalizes the weighted time. The weighted time results from the char-
acteristic curve. For this, the time that is associated with the present current value is determined from the
characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls short of the pickup value by a factor of 1.045 (0.95 x 1.1 x threshold value),
the dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via
setting parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout
according to the characteristic curve (reduction of totalized time depending on the characteristic curve). The
dropout according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The
weighted reduction of the time is initiated from 0.9 of the set threshold value.

[dwocpken-140611-02.tif, 2, en_US]

Figure 6-104 Pickup Behavior and Dropout Behavior when Using a User-Defined Characteristic Curve

586 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

NOTE

i Note that the currents that are lower than the current value of the smallest characteristic-curve point do
not extend the operate time. The pickup characteristic runs in parallel to the current axis up to the smallest
characteristic-curve point. Currents that are larger than the current value of the largest characteristic-curve
point do not reduce the operate time. The pickup characteristic runs in parallel to the current axis from the
largest characteristic-curve point.

6.12.6.2 Application and Setting Notes


This stage is structured the same way as the stage with the inverse-time characteristic curve. The only differ-
ence is that you can define the characteristic curve as desired. This chapter only provides application and
setting notes for setting characteristic curves.

Parameter: Current/time value pairs (from the operate curve)


Use these settings to define the characteristic curve. Set a current/time value pair for each characteristic-curve
point. The setting depends on the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to displace the characteristic curve.
Set the time value in seconds. The characteristic curve is displaced using the Time dial parameter.

NOTE

i The value pairs must be entered in continuous order.

Parameter: Time dial

• Default setting (_:101) Time dial = 1


Use the Time dial parameter to displace the characteristic curve in the time direction.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the Time
dial parameter at 1.

Parameter: Reset

• Default setting Reset = disk emulation


You use the Reset parameter to define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation In the case of this setting, a dropout characteristic curve has to be set in
addition to the operate curve.
Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Use this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.

Parameter: Current/time value pairs (of the dropout characteristic curve)


Use these settings to define the characteristic curve. Set a current/time value pair for each characteristic-curve
point. The setting depends on the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to displace the characteristic curve.
Set the time value in seconds. The characteristic curve is displaced using the Time dial parameter.

SIPROTEC 5, 7SJ82/7SJ85, Manual 587


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

NOTE

i The value pairs must be entered in continuous order.

6.12.6.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 User curve #:Mode • off off
• on
• test
_:2 User curve #:Operate & • no no
flt.rec. blocked
• yes
_:27 User curve #:Blk. w. • no no
inrush curr. detect.
• yes
_:8 User curve #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:3 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:110 User curve #:Reset • instantaneous disk emulation
• disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00

6.12.6.4 Information List

No. Information Data Class Type


(Type)
User curve #
_:81 User curve #:>Block stage SPS I
_:500 User curve #:>Block delay & op. SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:60 User curve #:Inrush blocks operate ACT O
_:59 User curve #:Disk emulation running SPS O
_:55 User curve #:Pickup ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O

588 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

6.12.7 Fast Stage

6.12.7.1 Description

Logic of a Stage
The fast stage is only available in function type Advanced.

[loocp1hs-280113-01.tif, 2, en_US]

Figure 6-105 Logic Diagram of the Fast Stage, 1-Phase

Method of Measurement, Pickup and Dropout Behaviors of the Fast Stage


This stage evaluates the unfiltered measurands. Thus, very short response times are possible. When the abso-
lute values of 2 consecutive sampled values of the last half period exceed the Threshold, the stage picks up.
When all sampled values of the previous period are less than the dropout threshold, the stage drops out.

Blocking of the Stage


The picked up stage can reset completely via the binary input signal >Block stage.

6.12.7.2 Application and Setting Notes

Parameter: Threshold, Operate delay

• Default setting (_:3) Threshold = 10.00 A

• Default setting (_:6) Operate delay = 0.00 s


Set the Threshold and Operate delay parameters for the specific application.
Ensure that the sampled values are compared directly without an additional factor with the set threshold
value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 589


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

Parameter: Dropout ratio

• Recommended setting value (_:4) Dropout ratio = 0.90


The recommended setting value of 0.90 is sufficient for many applications. To obtain high-precision measure-
ments, the Dropout ratio can be reduced. If you expect highly fluctuating measurands at the pickup
threshold, you can increase the Dropout ratio setting. This avoids chattering of the tripping stage.

6.12.7.3 Settings

Addr. Parameter C Setting Options Default Setting


Fast stage #
_:1 Fast stage #:Mode • off off
• on
• test
_:2 Fast stage #:Operate & • no no
flt.rec. blocked
• yes
_:3 Fast stage #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 10.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 50.000 A
_:4 Fast stage #:Dropout 0.90 to 0.99 0.90
ratio
_:6 Fast stage #:Operate 0.00 s to 60.00 s 0.00 s
delay

6.12.7.4 Information List

No. Information Data Class Type


(Type)
Fast stage #
_:81 Fast stage #:>Block stage SPS I
_:54 Fast stage #:Inactive SPS O
_:52 Fast stage #:Behavior ENS O
_:53 Fast stage #:Health ENS O
_:55 Fast stage #:Pickup ACD O
_:56 Fast stage #:Operate delay expired ACT O
_:57 Fast stage #:Operate ACT O

6.12.8 Application Example: High-Impedance Restricted Ground-Fault Protection

6.12.8.1 Description
With the high-impedance method, all current transformers operate in parallel at the limits of the protection
range on a common, relatively high-impedance resistor R, the voltage of which is measured.
The current transformers must be of the same type of construction and have at least one core of their own for
the High-impedance restricted ground-fault protection. Furthermore, they must have the same transfer ratio
and approximately the same knee-point voltage.
The high-impedance principle is especially suited for ground-fault detection in grounded networks at trans-
formers, generators, motors, and shunt reactors.

590 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

The left part of Figure 6-106 shows an application example for a grounded transformer winding or a grounded
motor/generator. The example at the right shows an ungrounded transformer winding or an ungrounded
motor/generator. In this example, it is assumed that the network is grounded at a different point.

[dwhimpef-310113-01.tif, 2, en_US]

Figure 6-106 Restricted Ground-Fault Protection According to the High-Impedance Principle

Function of the High-Impedance Principle


The high-impedance principle is explained using the example of a grounded transformer winding.
In normal state, no residual currents flow, that is, in the transformer neutral point IY = 0 and in the phases
3I0 = IA + IB + IC = 0.
With an external ground fault (on the left in Figure 6-107), the short-circuit current of which is fed via a
grounded neutral point, the same current flows in the transformer neutral point and in the phases. The
respective secondary currents (with the same transfer ratio of all current transformers) draw each other off.
They are connected in series. At the resistor R, only a little voltage arises, which results from the internal resis-
tances of the transformers and those of the transformer connection lines. Even if a current transformer is
briefly saturated, it becomes a low-impedance during the time of the saturation and forms a low-impedance
shunt to the high-impedance resistor R. The high resistance of the resistor thus has a stabilizing effect (so-
called resistor stabilization).

[dwprhimp-310113-01.tif, 2, en_US]

Figure 6-107 Principle of the Restricted Ground-Fault Protection According to the High-Impedance Principle

With a ground-fault in the protection range (on the right in Figure 6-107), a neutral-point current IY flows in
any case. The magnitude of the residual current in the phase currents depends on the grounding conditions in
the rest of the network. A secondary current corresponding to the entire short-circuit current attempts to flow
via the resistor R. But since this resistor is high-impedance, a high voltage arises there which causes the satura-
tion of the current transformers. The effective voltage at the resistor therefore corresponds approximately to
the knee-point voltage of the current transformers.
The resistor R is thus dimensioned in such a way that even the smallest ground-fault current to be detected
leads to a secondary voltage that corresponds to half of the knee-point voltage of the current transformers
(see chapter 2.5.4).

SIPROTEC 5, 7SJ82/7SJ85, Manual 591


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

Further information can be found at Sensitivity view for high-impedance ground-fault differential protection in
chapter 6.12.8.2 Application and Setting Notes .

High-Impedance Restricted Ground-Fault Protection with a SIPROTEC 5 Device


Use the I4 measuring input of the SIPROTEC 5 device for the high-impedance restricted ground-fault protec-
tion. This input for this application is to be executed as a sensitive measuring input. Since this is a current
input, the current is detected by this resistor instead of the voltage at the resistor R.
Figure 6-108 shows the connection diagram. The protection device is connected in series with the resistor R
and thus measures its current.
The varistor V limits the voltage in case of an internal fault. The varistor cuts the high instantaneous voltage
peaks in the case of transformer saturation. Simultaneously, a smoothing of the voltage arises without any
relevant reduction of the average value.

[dwanedif-310113-01.tif, 2, en_US]

Figure 6-108 Connection Diagram of the Restricted Ground-Fault Protection According to the High-Impe-
dance Principle

As a protection against overvoltages, it is important that you connect the device directly at the grounded side
of the current transformer. The high voltage at the resistor is thus kept away from the device.
In a similar manner, the high-impedance restricted ground-fault protection for generators, motors, and shunt
reactors is used. With auto transformers, you must connect the upper-voltage side and low-voltage side
current transformers and neutral-point transformer in parallel.
The method can be realized for each protected object. As busbar protection, the device, for example, is
connected via the resistor to the parallel connection of the transformers of all feeders.

6.12.8.2 Application and Setting Notes


A prerequisite for the application of the high-impedance restricted ground-fault protection is that neutral-
point current detection is possible on the station side (see example in (Figure 6-108). Furthermore, a sensitive
input transformer must be available at device input I4. Set the pickup value for current at input I4 with the
function Overcurrent protection, 1-phase.
Observe the interaction between current-transformer characteristic curve, external resistor R, and the voltage
at R for the overall function of the high-impedance restricted ground-fault protection. Notes on this follow.

Current Transformer Data for High-Impedance Restricted Ground-Fault Protection


All affected current transformers must have the same ratio and approximately the same knee-point voltage.
This is normally the case when the current transformers are of the same type and have the same rated data.
You can calculate the knee-point voltage from the rated data as follows:

[foukniep-310113-01.tif, 1, en_US]

592 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

VKP Knee-point voltage


Ri Internal resistance of the current transformer
Prated Rated power of the current transformer
Irated Secondary rated current of the current transformer
n Rated overcurrent factor

Rated current, rated power, and overcurrent factor are found on the name plate of the transformer.

EXAMPLE
Current transformer with the following data on the name plate: 800/5; 5P10; 30 VA
You can read the following transformer data with this data:
Irated = 5 A (out of 800/5)
n = 10 (out of 5P10)
Prated = 30 VA

The internal resistance is frequently to be found in the test report of the transformer. If it is not known, it can
be approximately determined by a direct current measurement at the secondary winding.

EXAMPLE
Calculation of the knee-point voltage
Current transformer 800/5; 5P10; 30 VA with Ri = 0.3 Ω

[foukp5aw-310113-01.tif, 1, en_US]

Current transformer 800/1; 5P10; 30 VA with Ri = 5 Ω

[foukp1aw-310113-01.tif, 1, en_US]

Besides the current-transformer data, the resistance of the longest connection line between transformer and
device must be known.

Stability Consideration for High-Impedance Restricted Ground-Fault Protection


The stability condition is based on the simplified assumption that one current transformer is completely satu-
rated and the others transfer their partial currents proportionately in the case of an external fault. This is theo-
retically the worst case. A safety margin is automatically provided, since, in practice, even the saturated trans-
former still delivers some current.
Figure 6-109 shows an equivalent circuit of this simplification. CT1 and CT2 are assumed to be ideal trans-
formers with their internal resistances Ri1 and Ri2. Ra are the core resistances of the connection lines between
transformer and resistance R; they are used doubled (forward line and return line). Ra2 is the resistance of the
longest connection line.
CT1 transmits the current I1. CT2 is assumed to be saturated. This is indicated by the dotted short-circuit line.
The transformer thus represents a low-impedance shunt by its saturation.
A further prerequisite is R >> (2Ra2 + Ri2).

SIPROTEC 5, 7SJ82/7SJ85, Manual 593


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

[dwvebhdi-310113-01.tif, 2, en_US]

Figure 6-109 Simplified Connection Diagram of a Layout for High-Impedance Restricted Ground-Fault
Protection

The voltage at R is, then,


VR = I1· (2Ra2 + Ri2)
A further assumption is that the pickup value of the SIPROTEC 5 device corresponds to half of the knee-point
voltage of the current transformers. In the edge case,
VR = VKP/2
The stability limit ISL results, which means the through fault current up to which the arrangement remains
stable:

[foistabl-310113-01.tif, 1, en_US]

EXAMPLE
For the 5 A transformer as above with VKP = 75 V and Ri = 0.3 Ω
Longest connection line = 22 m with 4 mm2 cross-section; that corresponds to Ra = 0.1 Ω

[foisl5aw-310113-01.tif, 1, en_US]

In the example, the stability limit is 15 × rated current or 12 kA primary.


For the 1 A transformer as above with VKP = 350 V and Ri = 5 Ω
Longest connection line = 107 m with 2.5 mm2 cross-section; that corresponds to Ra = 0.75 Ω

[foisl1aw-310113-01.tif, 1, en_US]

In the example, the stability limit is 27 × rated current or 21.6 kA primary.

Sensitivity Consideration for High-Impedance Restricted Ground-Fault Protection


The voltage present at the set of current transformers is supplied to the protection device via a series resistor R
as proportional current for evaluation. For dimensioning of the resistor, the following must be taken into
account:
The high-impedance restricted ground-fault protection should pick up at approximately half of the knee-point
voltage of the current transformers. From this, you can calculate the resistor R.
Since the device measures the current through the resistor, the resistor and measuring input of the device
must be connected in series. Since the resistor still should be high-impedance (aforementioned condition R >>
2Ra2 + Ri2 ), the inherent resistance of the measuring input can be neglected. The resistance results thus from
the pickup current Ipick and half of the knee-point voltage:

594 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

[foberecr-310113-01.tif, 1, en_US]

EXAMPLE
For the 5 A transformer as above
Desired pickup value Ipick = 0.1 A (corresponds to 16 A primary)

[fober5aw-310113-01.tif, 1, en_US]

For the 1 A transformer as above


Desired pickup value Ipick = 0.05 A (corresponds to 40 A primary)

[fober1aw-310113-01.tif, 1, en_US]

The series resistor R must be designed for a minimum continuous load Pcontinuous.

[fopdau5a-310113-01.tif, 1, en_US]

[fopdau1a-310113-01.tif, 1, en_US]

Further, the series resistor R must be designed for a fault current lasting approximately 0.5 s. This time is
usually sufficient for fault clearing through backup protection.
The thermal stress of the series resistor depends on the voltage VRMS,stab that is present during an internal fault.
It is calculated according to the following equations:

[fousta5a-310113-01.tif, 1, en_US]

[fousta1a-310113-01.tif, 1, en_US]

IK,max,int corresponds to the maximum fault current here in the case of an internal fault.
5-A current transformer 800/5 with 40 kA primary corresponds to IK,max,int = 250 A secondary.
1-A current transformer 800/1 with 40 kA primary corresponds to IK,max,int = 50 A secondary.
This results in a temporary load for the series resistor over 0.5 s of:

[fop05s5a-310113-01.tif, 1, en_US]

[fop05s1a-310113-01.tif, 1, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 595


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

Observe that with the selection of a higher pickup value Ipick, the resistor value must be lowered and therefore
the dissipation rises sharply.
The varistor (see following figure) must be sized such that it remains high impedance up to the knee-point
voltage, for example:

• Approx. 100 V with 5 A transformer

• Approx. 500 V with 1 A transformer

[dwanedif-310113-01.tif, 2, en_US]

Figure 6-110 Connection Diagram of the Restricted Ground-Fault Protection According to the High-Impe-
dance Principle

Even with unfavorable wiring, the maximum occurring voltage peaks do not exceed 2 kV for safety reasons.
When for performance reasons, several varistors must be connected in parallel, give preference to types with
flat characteristic curves, in order to avoid an unbalanced load. Siemens therefore recommends the following
types by METROSIL:
600A/S1/S256 (k = 450, β = 0.25)
600A/S1/S1088 (k = 900, β = 0.25)
In the example, set the pickup value of the first Definite-time overcurrent protection stage (setting
Threshold) to 0.1 A for 5-A transformers or 0.05 A for 1-A transformers. No further protection stages are
needed. Delete these or switch them off. Set the Operate delay setting to 0 s.
If several current transformers are connected in series, for example, with use as busbar protection with several
feeders, the magnetization currents of the transformers switched in parallel can no longer be neglected. In
this case, add up the magnetization currents at half of the knee-point voltage (corresponds to the set
Threshold). These magnetization currents reduce the current through the resistor R. Thus, the actual pickup
value is correspondingly higher.

6.12.9 Application Example: Tank Leakage Protection

6.12.9.1 Description
Tank leakage protection records short-circuits to ground – including high-impedance ones – between a phase
and the tank of a transformer. The tank is thus insulated, or at least grounded with high impedance. The tank
must be connected with a line to ground. The current that flows through this line is fed to the protection
device. If a short-circuit to ground occurs in a tank, a fault current (tank current) flows to substation ground
via the ground connection.
The function Overcurrent protection, 1-phase detects the tank current. If the tank current exceeds the set
Threshold, the function Overcurrent protection, 1-phase generates an operate indication. Depending on
the set Operate delay, the transformer is tripped immediately or time-delayed on all sides.
For tank protection, a sensitive, 1-phase current measuring input is used.

596 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase

[dwprkess-310113-01.tif, 2, en_US]

Figure 6-111 Tank-Control Principle

6.12.9.2 Application and Setting Notes


A prerequisite for the application of tank protection is the availability of a sensitive input transformer at device
input I4.
If you connect Measuring point I 1-ph with the function group Voltage-current 1-phase, the function Over-
current protection, 1-phase works with the 1-phase current connected to input I4.
Use only the first definite-time overcurrent protection stage of function Overcurrent protection, 1-phase.
The Threshold setting is used to set the pickup value. No further protection stages are needed. Delete these
or switch them off. Set the Operate delay setting to 0 s.

SIPROTEC 5, 7SJ82/7SJ85, Manual 597


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

6.13 Positive-Sequence Overcurrent Protection

6.13.1 Overview of Functions

The Positive-sequence overcurrent protection function (ANSI 50/51):

• Detects short circuits in electric equipment

• Can be applied when the zero-sequence current or negative-sequence current should not influence the
tripping, for example, on the tertiary delta winding of an auto transformer
You can find a typical application scenario in the chapter 6.13.3.2 Application and Setting Notes.

6.13.2 Structure of the Function

The Positive-sequence overcurrent protection function is used in protection function groups with 3-phase
current measurement.
The function comes factory-set with 2 Definite-time positive-sequence overcurrent protection stages.
The following stages can be operated simultaneously within the function:

• 3 stages Definite-time positive-sequence overcurrent protection

• 2 stages Inverse-time positive-sequence overcurrent protection


Stages that are not preconfigured are shown in gray in the following figure. Apart from the tripping delay
characteristic, the stages are identical in structure.
The group-indication output logic generates the following group indications of the protection function by the
logical OR of the stage-selective indications:

• Pickup

• Operate

[dw_PSP_Structure, 1, en_US]

Figure 6-112 Structure/Embedding of the Function

If the device is equipped with an Inrush-current detection function, the stages can be stabilized against trip-
ping due to transformer-inrush currents.

598 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

6.13.3 Stage with Definite-Time Characteristic Curve

6.13.3.1 Description

Logic

[lo_PSP_definite, 1, en_US]

Figure 6-113 Logic Diagram of the Stage Definite-Time Positive-Sequence Overcurrent Protection

Method of Measurement
The fundamental phasors are calculated from the 3-phase phase currents. Based on this, the posi-
tive‑sequence current is calculated.

Blocking of the Stage


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage is reset.

Blocking of Tripping via the Device-Internal Inrush-Current Detection Function


If the device is equipped with the additional Inrush-current detection function, the stages can be stabilized
against tripping due to transformer inrush currents.
With the Blk. w. inrush curr. detect. parameter, you can define whether tripping of the stage
should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking, the
stage picks up. The start of the time delay and tripping are however blocked. The stage signals this by way of a
corresponding indication. If the blocking drops out and the threshold value of the stage is still exceeded, the
tripping delay (time delay) is started. After that time, the stage operates.

SIPROTEC 5, 7SJ82/7SJ85, Manual 599


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

6.13.3.2 Application and Setting Notes

Application Example
The Positive-sequence overcurrent protection function is applied to the tertiary delta winding of the auto
transformer as shown in the following figure.
Short circuits on the delta winding must be detected. The stage should be as sensitive as possible but must
not pick up in case of faults in the circuits connected to the low-voltage side of the auxiliary transformer. A
single Positive-sequence overcurrent protection stage without time delay is applied and is connected with
the CTs marked in the following figure. When the stage operates, both the high-voltage and low-voltage sides
of the auto transformer will trip.

[dw_PSP_application_example, 1, en_US]

Figure 6-114 Auto Transformer with Tertiary Delta Winding

During ground faults on the high-voltage side (220 kV) or low-voltage side (110 kV) of the auto transformer,
large currents circulate in the delta winding. This circulating current is a pure zero-sequence current. The
protection function applied to the delta winding must not respond to this zero-sequence current. For this
purpose, the Positive-sequence overcurrent protection function is applied.
In this application example, there is no circuit breaker on the delta winding, and the load on the delta winding
is directly connected via the 500-kVA auxiliary transformer.
The application data in this application example is as follows:
Application Data Value
Rated apparent power of the auto transformer 300 MVA
Rated apparent power of the auxiliary transformer (Srated, aux) 500 kVA
Short-circuit voltage of the auxiliary transformer (uk-aux) 12 %
Rated apparent power of the delta winding 30 MVA
Rated voltage of the delta winding (Vrated, delta) 22 kV
Connected load on the delta winding 500 kVA
Current transformer ratio in the delta winding (RatioI) 800 A/1 A

Generally, for the delta winding, the short-circuit current is substantially larger than the rated current, and the
expected maximum load current is substantially smaller than the rated current. Therefore, you only need to
consider the short-circuit current when determining the pickup threshold of the Positive-sequence overcur-
rent protection function.
As there is no circuit breaker between the delta winding and the connected auxiliary transformer, the pickup
threshold of the Positive-sequence overcurrent protection function is graded against the maximum short-
circuit current due to a short circuit on the low-voltage (400 V) side of the auxiliary transformer. The

600 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

maximum fault current for a fault on the low-voltage side of the auxiliary transformer must therefore be
determined to establish the pickup threshold.
To determine the pickup threshold (setting of the Threshold parameter) of the stage, the following calcula-
tions must be carried out:

• Maximum short-circuit current (ISC, max) on the high-voltage side of the auxiliary transformer due to a
short circuit on the low-voltage (400 V) side

[fo_max_fault_current, 1, en_US]

• Primary-current pickup threshold (I1stage1, prim)


In this example, a safety margin (kS) of 200 % is applied.

[fo_prim_threshold, 1, en_US]

• Secondary-current pickup threshold (I1stage1, sec), which is the setting of the Threshold parameter

[fo_sec_threshold, 1, en_US]

Parameter: Threshold, Operate delay

• Default setting (_:20581:3) Threshold = 1.200 A (for the 1st stage)

• Default setting (_:20581:6) Operate delay = 0.50 s (for the 1st stage)
Set the Threshold and Operate delay parameters for the specific application.
As time coordination with other protection functions is not required, you can set the Operate delay param-
eter to a rather small value of 0.03 s.

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:20581:104) Blk. w. inrush curr. detect. = no


With the Blk. w. inrush curr. detect. parameter, you stabilize the stage against tripping due to
transformer-inrush currents. If transformers are parts of the protection zones, set this parameter to yes.
When the pickup threshold is set to 2 times the maximum short-circuit current, the threshold value should be
above the current flowing during an inrush to the auxiliary transformer. Consequently, the setting of the Blk.
w. inrush curr. detect. can remain no. For more sensitive pickup thresholds, the Blk. w. inrush
curr. detect. should be set to yes.

Parameter: Operate & flt.rec. blocked

• Default setting (_:20581:2) Operate & flt.rec. blocked = no


With the Operate & flt.rec. blocked parameter, you block the operate indication, the fault recording,
and the fault log.

SIPROTEC 5, 7SJ82/7SJ85, Manual 601


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

6.13.3.3 Settings

Addr. Parameter C Setting Options Default Setting


Definite-T 1
_:20581:1 Definite-T 1:Mode • off off
• on
• test
_:20581:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:20581:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:20581:104 Definite-T 1:Blk. w. • no no
inrush curr. detect.
• yes
_:20581:6 Definite-T 1:Operate 0.00 s to 60.00 s 0.50 s
delay
Definite-T 2
_:20582:1 Definite-T 2:Mode • off off
• on
• test
_:20582:2 Definite-T 2:Operate & • no no
flt.rec. blocked
• yes
_:20582:3 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:20582:104 Definite-T 2:Blk. w. • no no
inrush curr. detect.
• yes
_:20582:6 Definite-T 2:Operate 0.00 s to 60.00 s 0.50 s
delay

6.13.3.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:20581:81 Definite-T 1:>Block stage SPS I
_:20581:52 Definite-T 1:Behavior ENS O
_:20581:53 Definite-T 1:Health ENS O
_:20581:54 Definite-T 1:Inactive SPS O
_:20581:56 Definite-T 1:Operate delay expired ACT O

602 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

No. Information Data Class Type


(Type)
_:20581:300 Definite-T 1:Inrush blocks operate ACT O
_:20581:55 Definite-T 1:Pickup ACD O
_:20581:57 Definite-T 1:Operate ACT O
Definite-T 2
_:20582:81 Definite-T 2:>Block stage SPS I
_:20582:52 Definite-T 2:Behavior ENS O
_:20582:53 Definite-T 2:Health ENS O
_:20582:54 Definite-T 2:Inactive SPS O
_:20582:56 Definite-T 2:Operate delay expired ACT O
_:20582:300 Definite-T 2:Inrush blocks operate ACT O
_:20582:55 Definite-T 2:Pickup ACD O
_:20582:57 Definite-T 2:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 603


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

6.13.4 Stage with Inverse-Time Characteristic Curve

6.13.4.1 Description

Logic

[lo_PSP_Inverse, 1, en_US]

Figure 6-115 Logic Diagram of the Inverse-Time Positive-Sequence Overcurrent Protection

Method of Measurement
The fundamental phasors are calculated from the 3-phase phase currents. Based on this, the posi-
tive‑sequence current is calculated.

Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI

When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout

604 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.

Blocking of the Stage


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage is reset.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.

6.13.4.2 Application and Setting Notes

Parameter: Type of character. curve

• Default setting (_:105) Type of character. curve = IEC normal inverse


The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application. For more information about the parameter
Type of character. curve, refer to chapter 12.16.2 Stage with Inverse-Time Characteristic Curve.

Parameter: Threshold

• Default setting (_:3) Threshold = 1.200 A


Set the Threshold and Type of character. curve parameters for the specific application.
Note that a safety margin is set between the pickup value and the threshold value. The stage only picks up at
approx. 10 % above the Threshold.

Parameter: Time dial

• Default setting (_:107) Time dial = 1.00


With the Time dial parameter, you displace the characteristic curve in the time direction.
The set value for the Time dial parameter is derived from the time-grading schedule that has been prepared
for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the param-
eter Time dial at 1.00 (default setting).

Parameter: Reset

• Default setting (_:106) Reset = disk emulation


With the Reset parameter, you define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value Description
disk emulation Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Select this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:104) Blk. w. inrush curr. detect. = no

SIPROTEC 5, 7SJ82/7SJ85, Manual 605


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

With the Blk. w. inrush curr. detect. parameter, you stabilize the stage against tripping due to
transformer-inrush currents. If transformers are parts of the protection zones, set this parameter to yes.

6.13.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Inverse-T #
_:1 Inverse-T #:Mode • off off
• on
• test
_:2 Inverse-T #:Operate & • no no
flt.rec. blocked
• yes
_:3 Inverse-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:104 Inverse-T #:Blk. w. inrush • no no
curr. detect.
• yes
_:105 Inverse-T #:Type of char- • ANSI long-time inv. IEC normal
acter. curve inverse
• ANSI short-time inv.
• ANSI extremely inv.
• ANSI very inverse
• ANSI normal inverse
• ANSI moderately inv.
• ANSI definite inverse
• IEC normal inverse
• IEC very inverse
• IEC extremely inv.
• IEC long-time inverse
_:106 Inverse-T #:Reset • instantaneous disk emulation
• disk emulation
_:107 Inverse-T #:Time dial 0.05 to 15.00 1.00

6.13.4.4 Information List

No. Information Data Class Type


(Type)
Inverse-T #
_:81 Inverse-T #:>Block stage SPS I
_:52 Inverse-T #:Behavior ENS O
_:53 Inverse-T #:Health ENS O
_:54 Inverse-T #:Inactive SPS O
_:56 Inverse-T #:Operate delay expired ACT O
_:60 Inverse-T #:Inrush blocks operate ACT O
_:59 Inverse-T #:Disk emulation running SPS O
_:55 Inverse-T #:Pickup ACD O

606 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.13 Positive-Sequence Overcurrent Protection

No. Information Data Class Type


(Type)
_:57 Inverse-T #:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 607


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.14 Non-Directional Intermittent Ground-Fault Protection

6.14 Non-Directional Intermittent Ground-Fault Protection

6.14.1 Overview of Functions

A typical characteristic of intermittent ground faults is that they often extinguish automatically and strike
again after some time. The fault duration can last between a few milliseconds and many seconds. Thus, such
faults are not detected at all or not selectively by the ordinary overcurrent protection. If pulse durations are
extremely short, not all protection devices in a short-circuit path can pick up. Thus, selective tripping is not
ensured.
Due to the time delay of the overcurrent protection function, such faults are too short to initiate switching off
the faulted cable. The short-circuit protection can clear such ground faults selectively only if the ground faults
have become permanent.
But such intermittent ground faults already bear the risk of damaging the equipment thermally. This is why
SIPROTEC 5 devices feature a protection function that is able to detect such intermittent ground faults and
accumulates their duration. If the sum reaches a configurable value within a certain time, the limit of the
thermal rating has been reached. If intermittent ground faults are distributed over a long period or if the
ground fault disappears and does not restrike after some time, the equipment under load is expected to cool
down. Tripping is not necessary in this case.
The Non-directional intermittent ground-fault protection function is used to protect against intermittent
ground faults which occur, for example, in cables due to poor insulation or water ingress in cable joints.

6.14.2 Structure of the Function

The Non-directional intermittent ground-fault protection function can be used in protection function
groups with current measurement. The function is preconfigured by the manufacturer with 1 stage, and a
maximum of 2 stages can be operated simultaneously. The non-preconfigured stages are shown in gray in the
following figure.

[DwIntGFP, 1, en_US]

Figure 6-116 Structure/Embedding of the Function

608 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.14 Non-Directional Intermittent Ground-Fault Protection

6.14.3 Stage Description

Logic

[LoIntnon, 1, en_US]

Figure 6-117 Logic of the Non-Directional Intermittent Ground-Fault Protection

Measured Value 3I0


The intermittent ground-fault current 3I0 can either be measured via the standard ground-current input IN or
via the sensitive ground-current input INS. It can also be calculated from the sum of the 3-phase currents. The
current value and its setting range depend on the parameter Connection type of the measuring point I-3ph.

SIPROTEC 5, 7SJ82/7SJ85, Manual 609


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.14 Non-Directional Intermittent Ground-Fault Protection

Table 6-9 Threshold Setting Range with Different Connection Types

Connection Type of Current Threshold 3I0/IN CT Terminal Type Threshold Setting


the Measuring Point Range
I-3ph (Secondary)16
3-phase Calculated 3I017 4 x Protection 0.030 A to 35.000 A
3 x Protection, 1 x sensitive 0.030 A to 35.000 A
4 x Measurement 0.001 A to 1.600 A
3-phase + IN Measured IN18 4 x Protection 0.030 A to 35.000 A
3-phase + IN-separate 4 x Measurement 0.001 A to 1.600 A
Measured IN and calculated 3 x Protection, 1 x sensitive 0.001 A to 35.000 A
3I0 when IN > 1.6 A

Method of Measurement
The stage calculates the RMS value of 3I0 since this value takes into account the higher-order harmonics
components and the direct component (DC). Both components contribute to the thermal load.

Maximum 3I0 of the Fault


The stage records the maximum RMS value of 3I0 during the intermittent ground fault. The statistic value 3I0
max. is a percentage value calculated through dividing the primary maximum RMS value by the rated current
value of the protected object. With the coming operate signal, this value is logged via the information 3I0
max..

Pickup and Intermittent Ground-Fault Indication


When 3I0 exceeds the threshold value, the pickup signals Pickup and Limited pickup (log) are issued.
The stage generates the Stabilized pickup signal by extending the Pickup for a defined time (param-
eter Pickup extension time).
The stage counts the Pickup signals. If the counted number reaches the configured No. pickups till
interm.GF, the Intermittent gnd.flt. signal is issued. The signal Limited pickup (log) is not
issued anymore after the issue of the Intermittent gnd.flt. signal.

[DwIntFaD, 2, en_US]

Figure 6-118 Fault Detection of the Intermittent Ground-Fault Protection

16 These values apply for a secondary rated current of 1 A. The values need to be multiplied by 5 when the secondary rated current is 5
A.
17 If the connection type is without IN, such as 3-phase, the current threshold value is a calculated 3I0 value.
18 If the connection type is with IN, such as 3-phase + IN, the current threshold value is a measured IN value.

610 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.14 Non-Directional Intermittent Ground-Fault Protection

Text. Defined time for extending the Pickup signal

Number of Pickups
The stage counts the number of Pickup signals during the intermittent ground fault. With the operate of the
stage this number is logged via the information No. of pickups.

Accumulation of the Intermittent Ground-Fault Current and Issuing the Operate Signal
An intermittent ground fault can result in thermal stress on the protected equipment. The magnitude and the
duration of the ground-fault current are decisive for the thermal stress. In order to calculate the thermal stress,
the stage sums up the duration of the stabilized pickups with an integrator. If the integration value reaches
the predefined Sum of extended PU times, the limit of the thermal load is reached. The stage issues the
signal Sum limit reached and operates when the signal Pickup is active.

Reset Timer for the Definition of the Interval between Independent Ground Faults
If there is a large interval between independent ground faults or if ground fault extinguishes and does not
restrike again within a larger time, the stressed equipment can cool down. In this case, an operation is not
necessary. The interval between ground faults is monitored with the reset timer. If a ground fault occurs, the
Timer T-reset with its setting Reset time is launched simultaneously with Integrator T-sum. Unlike the
integrator, each new ground fault restarts the reset timer with its initial value. If Timer T-reset expires, that is,
no new ground fault was detected during that period, all memories and the stage logics are reset. Timer T-
reset thus determines the time during which the next ground fault must occur to be processed yet as intermit-
tent ground fault in connection with the previous fault. A ground fault that occurs later is considered as a new
fault event.

Reset Conditions
Under one of the following 2 conditions, Timer T-reset is reset.

• The Intermittent ground-fault protection stage operates.

• The general operate indication is going.


Under one of the following conditions, Integrator T-sum and Counter are reset and the whole stage is reset
and returns to its idle state.

• Timer T-reset expires without an operate signal of this stage or another function was issued.

• The operate signal of the intermittent ground-fault protection stage is going.

• The general operate indication is going without the operate signal of the intermittent ground-fault
protection stage issued.

Fault Log and Fault Recording


You can select between the ground-fault log without fault recording or the normal fault log with fault
recording. If you set the parameter Operate & flt.rec. blocked to yes, the operate of the stage and
fault recording are blocked and the information automatically appears in the ground-fault log. Otherwise, the
operate and fault recording are not blocked and the information appears in the normal fault log.

Start & Stop of Fault Recording, Fault Logging, and General Pickup
The Stabilized pickup signal initiates the fault recording, fault logging, and the general pickup of the
function group. The fault recording starts according to the pre-trigger time before the Stabilized pickup
signal rises.
With the reset condition of this stage, the fault recording, fault logging, and the general pickup of the function
group are terminated.

Influence on Other Functions to Avoid a Burst of Signals


Intermittent ground faults may cause other functions, based on overcurrent measurement, to pick up, which
may result in a burst of signals. In order to avoid an overflow of the fault log, a special mechanism is applied to

SIPROTEC 5, 7SJ82/7SJ85, Manual 611


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.14 Non-Directional Intermittent Ground-Fault Protection

the signals of these functions after detection of an intermittent ground fault (signal Intermittent
gnd.flt.).
The special mechanism is applied for the following listed functions and other functions are not influenced:

• Overcurrent protection, phases

• Overcurrent protection, ground

• Directional overcurrent protection, phases

• Directional overcurrent protection, ground

• Overcurrent protection, 1-phase

• Negative-sequence protection with definite-time characteristic curve

• Directional negative-sequence protection with definite-time delay

• Directional overcurrent-protection stage with cos phi or sin phi measurement

• Directional overcurrent-protection stage with 3I0-phi (V,I) measurement

• Sensitive ground-current protection with 3I0


If a function picks up, normally its output signals are sent directly to the information targets, for example, the
pickup signal is written to the fault log. To avoid overflow of logs due to intermittent ground faults, a special
log buffer mechanism is used. If one of the preceding functions or stages picks up after an intermittent ground
fault has been detected (signal Intermittent gnd.flt. has been issued), its output signals are processed
as shown in the following 2 tables.

Table 6-10 Processing of the Signal Status Changes

Processing of Signal Status Changes Description


Special buffering mechanism The status changes of signals are written to a special
buffer. This buffer can store a maximum of 2 status
changes (the most recent ones) for each signal.
With the pickup signal as example, if one of the
preceding protection functions or stages picks up
during an active Intermittent gnd.flt. signal,
the pickup signal is not written in the fault log
anymore unless one of the preceding functions oper-
ates. After the operation, the buffered signals are
written to the information target with the original
time stamp. This measure ensures that a pickup
signal, although delayed, is always signaled in associ-
ation with each operate command.
Discard The signal status changes are discarded.
Pass through The signal is forwarded to the information target
without restriction.
Special buffering does not apply for specific informa-
tion targets as protection measure, for example,
reverse interlocking, need these signals for proper
operation.

612 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.14 Non-Directional Intermittent Ground-Fault Protection

Table 6-11 Information Target with Different Processing of Signal Status Changes

Information Target Processing of Signal Status Changes


Processing of Signal Status Operational log Special buffering mechanism
Changes Fault log
Ground-fault log
User-defined log
Communication interface IEC 61850-8-1 Client/Server Special buffering mechanism
IEC 60870-5-103/104
DNP V3.0
Protection interface PDI Pass through
IEC 61850-8-1 GOOSE Pass through
CFC Pass through
LEDs Pass through
Binary output Pass through
Fault recorder Pass through
Automatic reclosing function Discard
Circuit-breaker failure protection Discard
Group indications Discard

6.14.4 Application and Setting Notes

No Start of the Automatic Reclosing Function


Automatic reclosing is not an effective measure against intermittent ground faults as the protection function
only operates after repeated detection of a fault or after the integration value reaches the predefined Sum of
extended PU times. Besides this, its basic design is to prevent thermal overload. For these reasons, the
intermittent ground-fault protection function is not intended to start the automatic reclosing function.

Rooting of Pickup Signals


The signal Pickup is supposed to be routed to LED and relay. The signal Limited pickup (log) is only
reported to the fault log and communication interface before the signal Intermittent gnd.flt. is issued.
This scheme prevents a burst of messages.

NOTE

i To avoid a burst of messages, do not route the signal Pickup to the operational log and fault log.

Parameter: Threshold

• Default setting (_:11341:3) Threshold = 1.00 A


With the Threshold parameter, you set the threshold value of the ground current 3I0, measured as RMS
value.
A rather sensitive setting is possible to respond also to short ground faults since the pickup time shortens as
the ground-fault current increases.

Parameter: No. pickups till interm.GF

• Default setting (_:11341:101) No. pickups till interm.GF = 3


With the parameter No. pickups till interm.GF, you set the number of counted Pickup signals after
which the ground fault is considered as intermittent.

SIPROTEC 5, 7SJ82/7SJ85, Manual 613


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.14 Non-Directional Intermittent Ground-Fault Protection

Parameter: Pickup extension time

• Default setting (_:11341:102) Pickup extension time = 0.10 s


You can get a stabilized pickup signal with the Pickup extension time parameter. This stabilization is
especially important for the coordination with existing static or electromechanical overcurrent protections.

Parameter: Sum of extended PU times

• Default setting (_:11341:103) Sum of extended PU times = 20 s


With the Sum of extended PU times parameter, you set the threshold value for the integrator. If the
integration reaches Sum of extended PU times, the stage operates if the pickup state is present.
This Sum of extended PU times represents one of the 4 selectivity criteria (pickup threshold, pickup
extension time, reset time, and integrator threshold value) for coordination of the relays on adjacent feeders.
It is comparable to the time grading of the overcurrent protection. The protection in the radial system which is
closest to the intermittent fault and picks up, has the shortest summation time Sum of extended PU
times.

Parameter: Reset time

• Default setting (_:11341:104) Reset time = 300 s


With the parameter Reset time, you can define the maximum interval between 2 adjacent ground faults. If
the interval is larger than the Reset time, the counter and integrator are reset.
The Reset time parameter must be much higher than the operate value of the Sum of extended PU
times.

Parameter: Operate & flt.rec. blocked

• Default setting (_:11341:2) Operate & flt.rec. blocked = no


You can block the operate indication, the fault recording, and the fault log with the Operate & flt.rec.
blocked parameter. In this case, a ground-fault log is created instead of the fault log.

EXAMPLE

[TiExaInt, 1, en_US]

Figure 6-119 Example of Selectivity Criteria of the Intermittent Ground-Fault Protection

614 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.14 Non-Directional Intermittent Ground-Fault Protection

6.14.5 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:11341:1 Stage 1:Mode • off off
• on
• test
_:11341:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:11341:3 Stage 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:11341:101 Stage 1:No. pickups till 2 to 10 3
interm.GF
_:11341:102 Stage 1:Pickup extension 0.00 s to 10.00 s 0.10 s
time
_:11341:103 Stage 1:Sum of 0.00 s to 100.00 s 20.00 s
extended PU times
_:11341:104 Stage 1:Reset time 1.00 s to 600.00 s 300.00 s

6.14.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:11341:81 Stage 1:>Block stage SPS I
_:11341:54 Stage 1:Inactive SPS O
_:11341:52 Stage 1:Behavior ENS O
_:11341:53 Stage 1:Health ENS O
_:11341:55 Stage 1:Pickup ACD O
_:11341:302 Stage 1:Stabilized pickup ACD O
_:11341:303 Stage 1:Limited pickup (log) ACD O
_:11341:304 Stage 1:Intermittent gnd.flt. SPS O
_:11341:301 Stage 1:Sum limit reached SPS O
_:11341:305 Stage 1:Reset time running SPS O
_:11341:57 Stage 1:Operate ACT O
_:11341:306 Stage 1:3I0 max. MV O
_:11341:307 Stage 1:No. of pickups MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 615


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

6.15 Directional Intermittent Ground-Fault Protection

6.15.1 Overview of Functions

The function Directional intermittent ground-fault protection:

• Detects the intermittent ground faults in grounded, compensated, or isolated cable systems selectively

• Can be operated in 2 different modes:


– Operate only by counting directional ground-current pulses
– Operate by integration of the fault current in combination with a directional criterion by counting
directional ground-current pulses
The intermittent ground faults in cable systems are frequently caused by weak insulation or water ingress in
cable joints. The ground faults are characterized by the following properties:

• Intermittent ground faults show very short high ground-current pulses (up to several hundred amperes)
with a duration of less than 1 ms.

• Intermittent ground faults are self-extinguishing and reignite within one half period up to several
periods, depending on the power-system conditions and the fault type.

• Intermittent ground faults can persist over longer periods (several seconds to minutes) and develop to
static ground faults.

6.15.2 Structure of the Function

The function Directional intermittent ground-fault protection can be used in protection function groups
with current and voltage measurement. The function is preconfigured by the manufacturer with 1 stage, and
a maximum of 2 stages can be operated simultaneously.

[DwStrDirIGFP_20140618, 1, en_US]

Figure 6-120 Structure/Embedding of the Function

616 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

6.15.3 Stage Description

Overview

[LoOverview, 1, en_US]

Figure 6-121 Logic of the Directional Intermittent Ground-Fault Protection

Blocking of the Stage with Measuring-Voltage Failure


The stage can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset. The following blocking options are available for the stage:

• From an internal source upon pickup of the Measuring-voltage failure detection function

• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker
The Blk. by meas.-volt. failure parameter can be set so that the measuring-voltage failure detection
blocks the stage or does not block it.

SIPROTEC 5, 7SJ82/7SJ85, Manual 617


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

Logic for Direction Determination and Pulse Counting

[LoIntdir1, 2, en_US]

Figure 6-122 Logic Diagram of Direction Determination and Pulse Counting

(1) The input signal 3 is from Figure 6-123.

Measurement Values for Direction Determination


The function Directional intermittent ground-fault protection determines the direction of the ground-
current pulse by comparing the maximum 3I0 and the VN changing trend of the ground-current pulse.
The zero-sequence voltage v0(t) can either be measured via the voltage input VN or can be calculated from
the sum of 3 phase-to-ground voltages. The measured value depends on the parameter Connection type of
the measuring point V-3ph.
The intermittent ground-fault current 3i0(t) can either be measured via the ground-current input IN or via the
sensitive ground-current input INS. It can also be calculated from the sum of the 3 phase currents. The current
value and its setting range depend on the parameter Connection type of the measuring point I-3ph.

Table 6-12 Threshold Setting Range with Different Connection Types

Connection Type of Current Threshold 3I0/IN CT Terminal Type Threshold Setting


the Measuring Point Range
I-3ph (Secondary)19
3-phase Calculated 3I020 4 x Protection 0.030 A to 35.000 A
3 x Protection, 1 x sensitive 0.030 A to 35.000 A
4 x Measurement 0.001 A to 1.600 A
3-phase + IN Measured IN21 4 x Protection 0.030 A to 35.000 A
3-phase + IN-separate 4 x Measurement 0.001 A to 1.600 A
Measured IN and calculated 3 x Protection, 1 x sensitive 0.001 A to 35.000 A
3I0 when IN > 1.6 A

19 These values apply for a secondary rated current of 1 A. The values need to be multiplied by 5 when the secondary rated current is 5
A.
20 If the connection type is without IN, such as 3-phase, the current threshold value is a calculated 3I0 value.
21 If the connection type is with IN, such as 3-phase + IN, the current threshold value is a measured IN value.

618 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

Direction Determination and Pulse Counting


When the RMS value of 3I0 exceeds the set threshold value (signal no. 3 in Figure 6-122), the direction deter-
mination process is started and is continuously carried out until the function resets. At first, the current pulse
(current peak) detection takes place. If a current pulse is detected, the direction determination for this pulse is
carried out.
The direction is determined by the maximum 3I0 and the VN changing trend of the ground-current pulse. The
plus or minus sign of the maximum 3I0 is compared to the plus or minus sign of the VN changing trend,
resulting in the directional decision forward or reverse. If the VN changing trend is smaller than 0.03 Vrated
or if the maximum 3I0 is smaller than 0.1 Irated, the direction is undefined.
During the ongoing intermittent ground fault, the directional results for all current pulses are counted.

Directional Mode and Directional Pulse Counter Criterion


The parameter Directional mode defines whether the function operates in forward or in reverse direc-
tion. The pulses in the specified direction are counted. If the pulse counter reaches the threshold value set in
the parameter No. of pulses for operate, the signal Pulse no. reached is issued. Depending on
the operating mode (Counter or Integrator and counter) of the function, the signal can immediately
cause the operate of the function (Counter mode) or it is processed as directional release criteria (Inte-
grator and counter operating mode). Refer to the further description in the following sections.
The directional pulse counter is reset when a different direction than the set Directional mode is detected.
An undefined direction result does not reset the counter.

Operating Mode
2 different functional operating modes are available: Counter and Integrator and counter. You can
select the different operating modes using the parameter Operating mode.

• Operating mode Counter:


Many ground-current pulses of intermittent ground faults can result in a damage of the protected object.
In this mode, the criterion for operate is only the number of directional current pulses. This is similar to
the SIPROTEC 4 implementation.

• Operating mode Integrator and counter:


An intermittent ground fault can result in thermal stress on the protected object. The magnitude and the
duration of the ground-current pulses are decisive for the thermal stress. In order to calculate the thermal
stress, the stage sums up the duration of the stabilized pickups with an integrator. If the integration value
reaches the threshold value, one criterion for the operate is fulfilled. The 2nd criterion for the operate is
the ground-fault direction. The ground-fault direction is determined by counting the directional ground-
current pulses.

SIPROTEC 5, 7SJ82/7SJ85, Manual 619


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

Pickup, Operate, and Reset logic for the Counter Mode

[LoIntdir2, 3, en_US]

Figure 6-123 Pickup, Operate, and Reset Logic in Operating Mode Counter

(1) The internal signal 4 is from Figure 6-122.

620 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

Pickup, Operate, and Reset logic for the Integrator and Counter Mode

[LoIntdir3, 4, en_US]

Figure 6-124 Pickup, Operate, and Reset Logic in Operating Mode Integrator and Counter

(1) The internal signal 4 and 5 are from Figure 6-122.

Measurement Value for Pickup and Integration


The stage calculates the RMS value of 3I0 since this value takes into account the higher-order harmonic
components and the direct component (DC). Both components contribute to the thermal load.

Pickup, Limited Pickup, and Stabilized Pickup


Whenever 3I0 exceeds Threshold, the stage issues the signal Pickup. The signal is intended to be applied
for LED and relay output.
Stabilized pickup is formed by prolonging the pickup indication by a settable time Pickup extension
time. This stabilization is especially important for the coordination with the existing static or electromechan-
ical overcurrent protection.
The Limited pickup (log) signal is intend to be applied for logging and communication interface. The
Limited pickup (log) signal will be entered in the fault log and reported via the system interface unless
the Intermittent gnd.flt. indication is given. This behavior prevents a burst of indications.

SIPROTEC 5, 7SJ82/7SJ85, Manual 621


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

Intermittent Ground-Fault Indication


The stage counts the 3I0 pulses. If the sum of forward pulse counts, reverse counts, and directional undefined
counts is equal to or greater than No.of pulses for interm.GF, the signal Intermittent gnd.flt.
is issued.
If the signal Intermittent gnd.flt. is issued, the pickup indications of some protection functions will be
restraint to avoid an indication burst during an intermittent ground fault.

Operate
The conditions for issuing the signal Operate depend on the operating mode.
Operating Mode Conditions for Issuing the Operate Signal
Counter • The current-pulse counter reached the No. of pulses for
operate, which is signaled via the Pulse no. reached indication.
• The pickup is active, which is signaled via the Pickup indication.
Integrator and counter • The 3I0 current integration value reaches the predefined Sum of
extended PU times, which is signaled via the Sum limit
reached indication.
• The current-pulse counter reached the No. of pulses for
operate, which is signaled via the Pulse no. reached indication.
• The pickup is active, which is signaled via the Pickup indication.

When an opposite current pulse against the setting Directional mode is detected, the Integrator T-sum
and the Counter are reset.

Reset Time for the Definition of the Interval between Independent Ground Faults
If there is a large interval between independent ground faults or if the ground fault extinguishes and does not
restrike again within a larger time, the stressed equipment can cool down. In this case, no operate is neces-
sary. The interval between ground faults is monitored with the reset time. If a ground fault occurs, the Timer
T-reset with the setting Reset time and the Integrator T-sum are launched simultaneously. Unlike the inte-
grator, each new ground-current pulse restarts the reset time with its initial value. If the Timer T-reset
expires, that is, no new ground fault was detected during that period, all memories and the stage logics are
reset. The Timer T-reset thus determines the time during which the next ground fault must occur to be
processed yet as intermittent ground fault in connection with the previous fault. A ground fault that occurs
later is considered as a new ground-fault event.

Reset Conditions
Under one of the following 2 conditions, Timer T-reset is reset:

• The intermittent ground-fault protection stage operates.

• The general operate indication is going.


Under one of the following conditions, Integrator T-sum and Counter are reset and the whole stage is reset
and returns to its idle state:

• The Timer T-reset expires without an operate signal of this stage or another function was issued.

• The operate signal of the intermittent ground-fault protection stage is going.

• The general operate indication is going without the operate signal of the intermittent ground-fault
protection stage issued.

Maximum Value 3I0 of the Ground Fault


The stage records the maximum RMS value of 3I0 during the intermittent ground fault.The statistic value 3I0
max. is a percentage value calculated through dividing the primary maximum RMS value by the rated current
value of the protected object. If the function resets or operates, this value is logged via the signal 3I0 max..

622 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

Fault Log and Fault Recording


You can select between the ground-fault log without fault recording or the normal fault log with fault
recording. If you set the parameter Operate & flt.rec. blocked to yes, the operate of the stage and
fault recording are blocked and the information automatically appears in the ground-fault log. Otherwise, the
operate and fault recording are not blocked and the information appears in the normal fault log.

Start and Stop of Fault Recording, Fault Logging, and General Pickup
The Stabilized pickup signal initiates fault recording, fault logging, and the general pickup of the func-
tion group. The fault recording starts according to the pre-trigger time before the Stabilized pickup
signal rises.
With the reset condition of this stage, the fault recording, fault logging, and the general pickup of the function
group are terminated.

Influence on Other Functions to Avoid a Burst of Indications


In this case, the function uses the same mechanism as the Non-directional intermittent ground-fault
protection. For more information, refer to chapter Influence on Other Functions to Avoid a Burst of Signals,
Page 611.

6.15.4 Application and Setting Notes

No Start of the Automatic Reclosing Function


Automatic reclosing is not an effective measure against intermittent ground faults. For this reason, the Direc-
tional intermittent ground-fault protection function is not intended to start the Automatic reclosing func-
tion.

Routing of Pickup Signals


The signal Pickup is supposed to be routed to an LED and a relay. The signal Limited pickup (log) is
only reported to the fault log and communication interface until the signal Intermittent gnd.flt. is
issued. This scheme prevents a burst of indications.

NOTE

i To avoid a burst of indications, do not route the signal Pickup to the operational log and to the fault log.

Parameter: Threshold

• Default setting (_:16291:3) Threshold = 1.00 A


With the parameter Threshold, you set the threshold value of the ground current 3I0, measured as RMS
value.
A rather sensitive setting is possible to respond also to short ground faults since the pickup time shortens as
the ground-fault current increases.

Parameter: Directional mode

• Default setting (_:16291:101) Directional mode = forward


With the parameter Directional mode, you define if the function operates in forward or in reverse
direction.

Parameter: Pickup mode

• Default setting (_:16291:102) Pickup mode = with 3I0>

SIPROTEC 5, 7SJ82/7SJ85, Manual 623


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

With the parameter Pickup mode, you define under which conditions pickup is detected and fault logging
and recording start:

• When the parameter Pickup mode is set to with 3I0>, the signal Pickup is released without consid-
ering the ground fault direction. The signal Pickup is issued once the IN/3I0 exceeds the threshold
value.

• When the parameter Pickup mode is set to with direction, the signal Pickup is issued when at
least one pulse direction is the same as the direction specified by the set value of parameter Direc-
tional mode.

Parameter: Operating mode

• Default setting (_:16291:103) Operating mode = Counter


With the parameter Operating mode, you define if the function operates in Counter or in Integrator
and counter mode.
Operating Mode Application and Setting Notes
Counter The number of directional pulses is the determining operate criterion. This
is a simple method which is similar to the implementation in the 7SJ
SIPROTEC 4 devices. Siemens recommends using this method if no time
grading or only simple time grading between protection devices (time
grading of only 2 or 3 devices) is required.
Time grading is then carried out by increasing the parameter value No.
of pulses for operate towards the infeed.
Integrator and counter The integrator and the counter are the determining operate criteria while
the counter criterion is only used for the direction determination. The inte-
grator works in the same way as for the non-directional intermittent
ground fault function. This allows the same time-grading principles as for
the non-directional intermittent ground fault function. Refer to this func-
tion for more description.

Parameter: No.of pulses for interm.GF

• Default setting (_:16291:104) No.of pulses for interm.GF = 3


With the parameter No.of pulses for interm.GF, you set the total number of pulse counts (forward,
reverse and non-dir. pulses) at which the ground fault is considered to be intermittent. Siemens
recommends using the default setting.

Parameter: Pickup extension time

• Default setting (_:16291:105) Pickup extension time = 0.10 s


With the parameter Pickup extension time, you get a prolonged and thus stabilized pickup signal. This
stabilization is especially important for the coordination with existing static or electromechanical overcurrent
protections.

Parameter: No. of pulses for operate

• Default setting (_:16291:108) No. of pulses for operate = 5


The pulses in the specified direction from Directional mode are counted. If the pulse counter reaches the
set value of the parameter No. of pulses for operate, the directional counter criterion is fulfilled.
The setting of parameter No. of pulses for operate depends on the Operating mode.

624 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

Operating Mode Application and Setting Notes


Counter The number of directional pulses is the determining operate
criterion. Thus do not set the value for parameter No. of
pulses for operate too small. Consider that a permanent
intermittent ground fault will cause many current pulses. If no
time-grading considerations are required, Siemens recommends
using a value in the range of 10 to 20.
Integrator and counter The integrator and the counter are the determining operate
criteria while the counter criterion is only used for the direction
determination. The value for parameter No. of pulses for
operate to fulfill the directional criterion can be set to a rather
small value in the range of 3 to 5.

Parameter: Sum of extended PU times

• Default setting (_:16291:106) Sum of extended PU times = 20.00 s


This parameter is only relevant in the operating mode Integrator and counter.
With the parameter Sum of extended PU times, you set the threshold value for the integrator. If the
integration reaches Sum of extended PU times, the stage operates if the Pulse no. reached signal
and the pickup state is present.
The parameter Sum of extended PU times represents one of the 5 selectivity criteria (ground-fault direc-
tion, pickup threshold, pickup extension time, reset time, and integrator threshold value) for coordination of
the relays on subordinate devices. It is comparable to the time grading of the overcurrent protection.
The Sum of extended PU times has the shortest summation time in the radial system for the device that
is closest to the intermittent ground fault and that picks up.

Parameter: Reset time

• Default setting (_:16291:107) Reset time = 300 s


With the parameter Reset time, you can define the maximum interval between 2 adjacent ground faults. If
the interval is larger than the Reset time, the counter and integrator are reset.
The Reset time parameter must be much higher than the operate value of the Sum of extended PU
times.

Parameter: Operate & flt.rec. blocked

• Default setting (_:16291:2) Operate & flt.rec. blocked = no


With the parameter Operate & flt.rec. blocked, you can block the operate indication, the fault
recording, and the fault log. In this case, a ground-fault log is created instead of the fault log.

6.15.5 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:16291:1 Stage 1:Mode • off off
• on
• test
_:16291:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:16291:10 Stage 1:Blk. by meas.- • no yes
volt. failure
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 625


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.15 Directional Intermittent Ground-Fault Protection

Addr. Parameter C Setting Options Default Setting


_:16291:101 Stage 1:Directional • forward forward
mode
• reverse
_:16291:102 Stage 1:Pickup mode • with 3I0> with 3I0>
• with direction
_:16291:103 Stage 1:Operating mode • Counter Counter
• Integrator and counter
_:16291:3 Stage 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:16291:105 Stage 1:Pickup extension 0.00 s to 10.00 s 0.10 s
time
_:16291:104 Stage 1:No.of pulses for 2 to 10 3
interm.GF
_:16291:106 Stage 1:Sum of 0.00 s to 100.00 s 20.00 s
extended PU times
_:16291:107 Stage 1:Reset time 1.00 s to 600.00 s 300.00 s
_:16291:108 Stage 1:No. of pulses for 2 to 100 5
operate

6.15.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:16291:81 Stage 1:>Block stage SPS I
_:16291:54 Stage 1:Inactive SPS O
_:16291:52 Stage 1:Behavior ENS O
_:16291:53 Stage 1:Health ENS O
_:16291:55 Stage 1:Pickup ACD O
_:16291:302 Stage 1:Stabilized pickup ACD O
_:16291:303 Stage 1:Limited pickup (log) ACD O
_:16291:304 Stage 1:Intermittent gnd.flt. SPS O
_:16291:301 Stage 1:Sum limit reached SPS O
_:16291:308 Stage 1:Pulse no. reached SPS O
_:16291:305 Stage 1:Reset time running SPS O
_:16291:57 Stage 1:Operate ACT O
_:16291:306 Stage 1:3I0 max. MV O
_:16291:310 Stage 1:Forward pulses MV O
_:16291:311 Stage 1:Reverse pulses MV O
_:16291:312 Stage 1:Non-dir. pulses MV O

626 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16 Sensitive Ground-Fault Detection

6.16.1 Overview of Functions

2 functions are available for ground-fault detection: a directional one and a non-directional one.
The Directional sensitive ground-fault detection (ANSI 67Ns) serves:

• For directional detection of permanent ground faults in isolated or resonant-grounded systems

• For directional detection of fast extinguishing transient ground faults in isolated or resonant-grounded
systems

• For determination of the faulty phase

• For detection of high-impedance ground faults in effectively (solidly) or low-impedance (semi-solidly)


grounded systems
The Non-directional sensitive ground-fault detection (ANSI 51Ns) serves:

• For ground-fault detection in isolated or resonant-grounded systems

• For detection of high-impedance ground faults in effectively (solidly) or low-impedance (semi-solidly)


grounded systems

6.16.2 Structure of the Function

Directional Sensitive Ground-Fault Detection


The Directional sensitive ground-fault detection function can be used in protection function groups that
make current and voltage zero-sequence systems (3I0 and V0) available. The function comes factory-set with
a non-directional V0> stage with zero-sequence voltage/residual voltage, a directional 3I0> stage with cos
φ or sin φ measurement, and a directional transient ground-fault stage.
The following stages can be operated simultaneously within the function:

• 2 non-directional V0> stages with zero-sequence voltage/residual voltage

• 4 directional 3I0> stages with cos φ or sin φ measurement

• 2 directional transient ground-fault stages

• 4 directional 3I0> stages with φ(V0, 3I0) measurement

• 4 directional Y0> stages with G0 or B0 measurement (admittance method)

• 4 directional stages with phasor measurement of a harmonic

• 4 non-directional 3I0> stages

• 2 non-directional Y0> stages

• 2 non-directional pulse-pattern detection stages


The general functionality works across stages on the function level.
The group-indications output logic generates the following group indications of the entire function by the
logical OR from the stage-selective indications:

• Pickup

• Operate indication

SIPROTEC 5, 7SJ82/7SJ85, Manual 627


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[DwStrGFP-250113-01, 5, en_US]

Figure 6-125 Structure/Embedding of the Directional Function in Protection Function Groups

Non-Directional Sensitive Ground-Fault Detection


The Non-directional sensitive ground-fault detection function can be used in protection function groups
that only make the zero-sequence system (3I0) available. The function comes factory-set with a non-direc-
tional 3I0> stage.
The following stages can be operated simultaneously within the function:

• 4 non-directional 3I0> stages

• 2 non-directional Y0> stages

• 4 non-directional 3I0> harmonic stages

• 2 non-directional pulse-pattern detection stages


The general functionality works across stages on the function level.
The group-indications output logic generates the following group indications of the entire function by the
logical OR from the stage-selective indications:

• Pickup

• Operate indication

628 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[DwSGFPu4-230113-01, 5, en_US]

Figure 6-126 Structure/Embedding of the Non-Directional Function in Protection Function Groups

6.16.3 General Functionality

6.16.3.1 Description

Logic

[LoGFPger-280113-01, 7, en_US]

Figure 6-127 Logic Diagram of the Cross-Stage Functionality of the Directional Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 629


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[logfpnon-261012-01.tif, 5, en_US]

Figure 6-128 Logic Diagram of the Cross-Stage Functionality of the Non-Directional Function

Operational Measured Value φ(I,V)


The function block calculates the angle between IN and V0 and makes the angle available as function meas-
ured value Phi(I,V).

[DwPhINU0, 1, en_US]

Figure 6-129 Sign Definition for the Measured Value

Fault-Extinction Detection
The extinction of the fault is characterized by the fact that the zero-sequence voltage subsides. Depending on
the system conditions and fault characteristics, this process can last several 100 ms. If a continuously falling
zero-sequence voltage is detected during the set time Decay time V0, then the fault is considered extin-
guished. The signal Flt. extinction det. is issued.
Thus, the possibility exists, for example, to block the 3I0> stage with cos φ or sin φ measurement directly
after the fault extinction, in order to avoid an overfunction during the subsiding process with a very sensitive
setting of the stage.

Angle-Error Compensation
The high reactive power factor in the arc-suppression-coil-ground system and the unavoidable air-gap of the
core balance current transformer often make necessary a compensation of the angle error of the core balance
current transformer. Using the characteristic shown in the following figure, the device approaches the angle
error of the core balance current transformer with sufficient precision.

630 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[dwerdwdl-110512-01.tif, 1, en_US]

Figure 6-130 Correction of the Transmission Characteristic Curve of a Core Balance Current Transformer

Ground-Fault Indication, Stabilization at Intermittent Ground Fault


The indication Ground fault indicates the ground fault and manages the ground-fault log (see Ground-
Fault Log, Page 631). The corresponding information of the stages used is accessed for the generation of this
indication.
The indication Ground fault contains the direction information, independent of the parameterized
working direction of a stage. The indication is thus suited for transfer to a station.
To avoid a flood of indications in case of an intermittent ground fault, a maximum of 30 status changes of this
indication is logged per ground fault. An intermittent ground fault must be treated as a ground fault so that
the stabilization can take action. This is ensured with the parameter Dropout delay, by the dropout of the
indication Ground fault being delayed. If the next ignition of the ground fault takes place during the
dropout delay, the indication does not drop out and the log remains open.

NOTE

i The Ground fault indication in the general stage must be routed to the ground-fault log. If not, you can
meet an overflow of the ground-fault log when an intermittent ground fault occurs.

Ground-Fault Log
Ground faults can be recorded in a designated buffer, the ground-fault log. As long as the Operate &
flt.rec. blocked parameter is set to yes, all indications routed into the ground-fault log are written in
the ground-fault log.
The criterion for opening the ground-fault log is the raising of any indication which is routed to the ground-
fault log, for example, the indication Ground fault . The criterion for closing is the clearing of all routed
indications.

Related Topics
You can find general notes on the ground-fault login chapter Indications under 3.1.5.4 Ground-Fault Log.

Value Indications
If the following value indications can be calculated, they are written into the log (ground-fault log or fault log)
at the time of the 1st raising ground-fault indication and the 1st operate indication of any stage.

• 3I0 (value)

• 3I0 active component

• 3I0 reactive component

SIPROTEC 5, 7SJ82/7SJ85, Manual 631


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

• V0

• φ (IN, V0)

Group-Indication Blocking

[lo_SGFP block group ind., 1, en_US]

Figure 6-131 Logic Diagram of the Group-Indication Blocking of the Directional and Non-Directional Func-
tions

By setting the Block. group indications parameter to yes, the following indications are blocked:

• The group indications of the function and the corresponding group indications of the function group

• The trip command from the Sensitive ground-fault detection function to the FB Circuit breaker
Fault recording and logging are not affected by the setting.

6.16.3.2 Application and Setting Notes

Indication: Ground fault


To indicate the ground fault and its direction via the protocol, Siemens recommends using the indication
(_:2311:302) Ground fault. The indication contains the direction information, independent of the
parameterized working direction of a stage. And this indication is also stabilized against a flood of indications
in case of an intermittent ground fault.

Parameter: Decay time V0

• Recommended setting value (_:2311:101) Decay time V0 = 0.10 s


With the Decay time V0 parameter, you specify the time slot for the detection of a fault extinction. If V0
continuously falls within this time, fault extinction is detected and the indication Flt. extinction det. is
issued.
Siemens recommends using the default setting.

Parameter: Dropout delay

• Recommended setting value (_:2311:102) Dropout delay = 1.00 s


To avoid chattering of the indication Ground fault during an intermittent ground fault and thus a frequent
opening and closing of the ground-fault log, the dropout of the indication Ground fault (and thus the
closing of the log) can be delayed by the Dropout delay.
Siemens recommends using the default setting.
Using the default setting ensures that no flood of indications arises in case of an intermittent ground fault for
the indication Ground fault. The intermittent ground fault is then treated as a ground fault, and the stabili-
zation of the indication Ground fault can thus take action.

632 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Angle-Error Compensation of the Core Balance Current Transformer

• Default setting (_:2311:103) Core balance CT- current 1 = 0.050 A

• Default setting (_:2311:104) Core balance CT- current 2 = 1.000 A

• Default setting (_:2311:105) CT angle error at I1 = 0.0°

• Default setting (_:2311:106) CT angle error at I2 = 0.0°


The high reactive-power factor in the arc-suppression-coil-ground system and the unavoidable air gap of the
core balance current transformer often make necessary a compensation of the angle error of the core balance
current transformer. For the burden actually connected, the maximum angle error CT angle error at I1
and the corresponding secondary current Core balance CT- current 1 as well as a further operating
point CT angle error at I2/Core balance CT- current 2 are entered, from which point the angle
error no longer changes appreciably.
In the isolated or grounded system, angle compensation is not necessary.

Parameter: Block. group indications

• Default setting (_:2311:119) Block. group indications = no


The Block. group indications parameter supports in applying the Sensitive ground-fault detection
function as a supervision function. If you set this parameter to yes, the following indications are blocked:

• The group indications of the function and the corresponding group indications of the function group are
blocked.
Consequently, the group-indications of the function group are then related to short-circuit protection
functions and can be forwarded to a station controller in the meaning of short-circuit protection.

• The trip command from the Directional sensitive ground-fault detection function to the FB
Circuit breaker is blocked.
Fault recording and logging are not affected by the setting.

6.16.3.3 Settings

Directional sensitive ground-fault detection

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Decay time V0 0.03 s to 0.20 s 0.10 s
_:2311:102 General:Dropout delay 0.00 s to 60.00 s 1.00 s
_:2311:103 General:Core balance 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
CT- current 1 5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:2311:104 General:Core balance 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
CT- current 2 5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:2311:105 General:CT angle error at 0.0 ° to 5.0 ° 0.0 °
I1
_:2311:106 General:CT angle error at 0.0 ° to 5.0 ° 0.0 °
I2

SIPROTEC 5, 7SJ82/7SJ85, Manual 633


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Addr. Parameter C Setting Options Default Setting


_:2311:119 General:Block. group • no no
indications
• yes

Non-directional sensitive ground-fault detection

Addr. Parameter C Setting Options Default Setting


General
_:2311:102 General:Dropout delay 0.00 s to 60.00 s 1.00 s
_:2311:119 General:Block. group • no no
indications
• yes

6.16.3.4 Information List

Directional sensitive ground-fault detection

No. Information Data Class Type


(Type)
General
_:2311:302 General:Ground fault ACD O
_:2311:303 General:Flt. extinction det. SPS O
_:2311:309 General:Pos. measuring window SPS O
_:2311:301 General:Phi(I,V) MV O
_:2311:306 General:IN MV O
_:2311:307 General:V0 MV O
_:2311:304 General:IN active MV O
_:2311:305 General:IN reactive MV O

Non-directional sensitive ground-fault detection

No. Information Data Class Type


(Type)
General
_:2311:302 General:Ground fault ACD O

634 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.4 Directional 3I0 Stage with Cos φ or Sin φ Measurement

6.16.4.1 Description

Logic

[logfp3i0stufe-280314-01.vsd, 2, en_US]

Figure 6-132 Logic Diagram of the Stage Control

SIPROTEC 5, 7SJ82/7SJ85, Manual 635


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[logfp3i0f-280314-01, 5, en_US]

Figure 6-133 Logic Diagram of the Directional 3I0 Stage with Cos φ or Sin φ Measurement

Measured Value V0, Method of Measurement


The device can measure the residual voltage at the broken-delta winding. The measured voltage VN is
converted to a value with reference to the zero-sequence voltage V0. If the residual voltage is not available to
the device as a measurand, the zero-sequence voltage V0 is calculated from the measured phase-to-ground
voltages VA, VB, and VC using the defining equation.
This method of measurement processes the sampled voltage values and filters out the fundamental compo-
nent numerically.

Measured Value 3I0, Method of Measurement


The function usually evaluates the sensitively measured ground current 3I0 via a core balance current trans-
former. Since the linearity range of the sensitive measuring input ends at approx. 1.6 A, for larger secondary

636 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

ground currents, the function switches to the 3I0 current calculated from the phase currents. This results in a
very large linearity and settings range.
Depending on the setting of the Connection type parameter of the measuring point I-3ph as well as the
current terminal block used, the following different linearity and settings ranges result in addition to the
common application:
Connection Type of the Current Threshold 3I0/IN Current Terminal Block 3I0 Threshold Value
Measuring Point I-3ph Settings Range
(Secondary)22
3-phase Calculated 3I023 4 x protection 0.030 A to 35.000 A
3 x protection, 1 x sensitive 0.030 A to 35.000 A
4 x measurement 0.001 A to 1.600 A
3-phase + IN Measured IN24 4 x protection 0.030 A to 35.000 A
3-phase + IN-separate 4 x measurement 0.001 A to 1.600 A
2ph, 2p. CT + 2 IN-sep Measured IN and calculated 3 x protection, 1 x sensitive 0.001 A to 35.000 A
3I0 when IN > 1.6 A
3ph,2prim.CT + IN-sep Measured IN 4 x protection 0.030 A to 35.000 A
2ph, 2p. CT + IN-sep 4 x measurement 0.001 A to 1.600 A
3 x protection, 1 x sensitive 0.001 A to 1.600 A

With the use of the function within a 1-phase function group and therefore at a 1-phase measuring point
I-1ph, the following different linearity and settings ranges result:
Measuring Point Current Threshold Current Terminal Block 3I0 Threshold Value
I-1ph Settings Range
(Secondary) 25
Measured Sensitive 0.001 A to 1.600 A
Protection 0.030 A to 35.000 A

The method of measurement processes the sampled current values and filters out the fundamental compo-
nent numerically.
The methods of measurement are characterized by high accuracy and by insensitivity to harmonics, especially
the 3rd and 5th harmonics frequently present in the ground-fault (residual) current.

Ground-Fault Detection, Pickup


If the absolute value of the ground current 3I0 exceeds the threshold value 3I0> threshold value and
the absolute value of the zero-sequence voltage V0 exceeds the threshold value V0> threshold value,
the stage recognizes the ground fault. The direction determination (see the next paragraph) is started when
the V0 threshold value is exceeded. The direction result is indicated via the Ground fault signal (in the
General function block). If the direction result equals the parameterized direction (parameter Directional
mode), the stage picks up.

Direction Determination
Exceeding the threshold values by the zero-sequence voltage V0 is a criterion for the ground fault. The direc-
tion determination can be delayed from the occurrence of the zero-sequence voltage with the Dir. deter-
mination delay parameter to achieve steady-state measurands. The result form the direction determina-
tion is only valid if the absolute value of the ground current 3I0 has also exceeded its threshold value.

22 These values apply for a secondary rated current of 1 A. The values need to be multiplied by 5 when the secondary rated current is 5
A.
23 If the connection type is without IN, such as 3-phase, the current threshold value is a calculated 3I0 value.
24 If the connection type is with IN, such as 3-phase + IN, the current threshold value is a measured IN value.
25 These values apply for a secondary rated current of 1 A. The values need to be multiplied by 5 when the secondary rated current is 5
A.

SIPROTEC 5, 7SJ82/7SJ85, Manual 637


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

The following figure shows an example of the direction determination in the complex phasor diagram for the
cos-φ direction measurement method with a correction value of the direction straight lines from 0 (parameter
φ correction). The example is suitable for the determination of the ground-fault direction in an arc-
suppression-coil-ground system where the variable 3I0 ⋅ cos φ is decisive for the direction determination.

[dwcosphi-171012-01.tif, 3, en_US]

Figure 6-134 Direction-Characteristic Curve with Cos φ Measurement

The zero-sequence voltage V0 is basically the reference value for the real axis. The axis of symmetry of the
direction-characteristic curve coincides with the 3I0reactive axis for this example. For the direction determina-
tion, basically the portion of the current vertical to the set direction-characteristic curve (= axis of symmetry) is
decisive (3I0 dir.). In this example, this is the active portion 3l0active of the current 3l0. The current 3l0dir.
(here = 3I0active) is calculated and compared with the setting value Min.polar.3I0> for dir.det.. If
the current 3I0 dir. exceeds the positive setting value, the direction is forward. If the current 3I0 dir. exceeds
the negative setting value, the direction is backward. In the range in between, the direction is undetermined.
With the α1 reduction dir. area and α2 reduction dir. area parameters, you can limit the
forward and backward ranges as shown in the figure. With this, the direction determination is secured in case
of high currents in the direction of the axis of symmetry.
The symmetry axis can be turned via a correction angle φ correction parameter) in a range of ±45°.
Through this, it is possible, for example, to attain the greatest sensitivity in grounded systems in the resistive-
inductive range with a -45° turn. In the case of electric machines in busbar connection on the isolated system,
the greatest sensitivity in the resistive-capacitive range can be attained with a rotation of +45°.

638 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[dwphicor-171012-01.tif, 2, en_US]

Figure 6-135 Turning the Direction-Characteristic Curves with Cos φ Measurement with Angle Correction

If you set the Dir. measuring method parameter to sin φ and the φ correction parameter to 0, the
symmetry axis of the direction-characteristic curve coincides with the 3I0active axis and the V0 axis. Since the
portion of the current vertical to the direction-characteristic curve (= axis of symmetry) is decisive (3l0dir.),
here, the current 3l0reactive is included in the direction determination. If the current 3l0dir. (here = 3I0reac-
tive) exceeds the negative setting value Min.polar.3I0> for dir.det., the direction is forward. If the
current 3l0dir. exceeds the positive setting value, the direction is backward. In the range in between, the
direction is undetermined.
This direction measurement thus is appropriate for the determination of ground-fault direction in isolated
systems.

SIPROTEC 5, 7SJ82/7SJ85, Manual 639


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[dwsinphi-011112-01.tif, 4, en_US]

Figure 6-136 Direction-Characteristic Curve with Sin φ Measurement

Blocking the Stage via Binary Input Signal


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage will be reset.

Blocking the Stage in Case of Measuring-Voltage Failure


The stage can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset.
The following blocking options are available for the stage:

• From inside on pickup of the Measuring-voltage failure detection function

• From an external source via the binary input signal >Open of the function block Voltage-transformer
circuit breaker, which links in the tripping of the voltage-transformer circuit breaker.
The Blk. by meas.-volt. failure parameter can be set so that Measuring-voltage failure detection
blocks the stage or does not block it.

Blocking the Pickup with Detection of the Fault Extinction


Using the evaluation of the instantaneous value developing of the zero-sequence voltage, the fault extinction
can be recognized faster than via the dropout of the V0 fundamental-component value under the pickup
value. The pickup of the stage is blocked with the fast detection of the fault extinction. With this, the pickups
are avoided due to the decay procedure in the zero-sequence system after the fault extinction. With the Blk.
after fault extinction parameter, you enable or disable this accelerated detection of the fault extinc-
tion.

Blocking the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate indication. A running time delay is reset. The pickup is indicated and a fault record is opened.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

640 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.

6.16.4.2 Application and Setting Notes

Parameter: Operate & flt.rec. blocked

• Default setting (_:12601:2) Operate & flt.rec. blocked = no


You can block the operate indication, the fault recording, and the fault log with the Operate & flt.rec.
blocked parameter. In this case, a ground-fault log is created instead of the fault log.

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:12601:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


enabled.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is linked with
the voltage-transformer circuit breaker.

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

Parameter: Blk. w. inrush curr. detect.

• Recommended setting value (_:12601:27) Blk. w. inrush curr. detect. = no


With the Blk. w. inrush curr. detect.parameter, you specify whether the operate is blocked during
detection of an inrush current.
Siemens recommends disabling the blocking. The fundamental component of the zero-sequence voltage is a
reliable criterion for the ground fault and remains unaffected by an enabling procedure.

Parameter: Blk. after fault extinction

• Recommended setting value (_:12601:110) Blk. after fault extinction = yes


If the Blk. after fault extinction parameter is set to yes, the pickup is blocked after detection of
the fault extinction. With this, the pickups are avoided due to the decay procedure in the zero-sequence
system after the fault extinction. Siemens recommends using the default setting.

Parameter: Directional mode

• Default setting (_:12601:108) Directional mode = forward


When a fault is detected, the selection of the parameter Directional mode defines whether the pickup of
the stage occurs in forward or backward direction.

Parameter: Dir. measuring method, φ correction, Min.polar.3I0> for dir.det., 3I0> threshold
value

• Default setting (_:12601:109) Dir. measuring method = cos φ

• Default setting (_:12601:107) φ correction = 0.0°

SIPROTEC 5, 7SJ82/7SJ85, Manual 641


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

• Default setting (_:12601:102) Min.polar.3I0> for dir.det. = 0.030 A

• Default setting (_:12601:101) 3I0> threshold value = 0.050 A


These parameters are used to define the direction characteristic of the stage. The direction characteristic to
use is dependent on the neutral-point treatment of the system.
Note that, for the direction determination, basically only a portion of the current vertical to the set direction-
characteristic curve (3I0dir.) is decisive, refer to 6.16.4.1 Description. This portion of the current is compared
to the threshold value Min.polar.3I0> for dir.det.. In contrast, the absolute value of the current 3I0
is compared with the 3I0> threshold value parameter.
System Type/ Description
Neutral-Point Treat-
ment
Grounded In the arc-suppression-coil-ground system, the watt-metric residual current 3I0 · cos φ
of the arc-suppression coil is decisive for the direction determination.
To evaluate the watt-metric residual current, set the parameters as follows:

• Dir. measuring method = cos φ


• φ correction = 0.0°
The direction determination for a ground fault is made more difficult in that a much
larger capacitive or inductive reactive current is superimposed on the small watt-metric
residual current. Therefore, depending on the system configuration and the fault eval-
uation, the total ground current supplied to the device can vary considerably in its
values regarding the magnitude and the phase angle. However, the device should only
evaluate the active component of the ground-fault current.
This requires extremely high accuracy, particularly regarding the phase-angle measure-
ment of all the instrument transformers. Furthermore, the device must not be set to
operate too sensitively. A reliable direction measurement can only be expected with
connection to a core balance current transformer. For the setting of the
Min.polar.3I0> for dir.det. parameter, the rule of thumb is: Set the pickup
value only to half of the expected measuring current as only the watt-metric residual
current can be put into use.
The 3I0> threshold value parameter can also be set to half of the expected
measuring current, whereby here the entire zero-sequence current can be put to use.
Isolated In the isolated system, the capacitive ground reactive current 3I0 · sin φ is decisive for
the direction determination.
To evaluate the capacitive ground reactive current, set the parameters as follows:

• Dir. measuring method = sin φ


• φ correction = 0.0°
In an isolated system, the capacitive ground-fault currents of the entire electrically
connected system flow through the measuring point in case of a ground fault. The
ground current of the faulty feeder is compensated in the measuring point. As the
pickup value of the Min.polar.3I0> for dir.det. and 3I0> threshold
value parameters, select about half of this capacitive ground-fault current flowing via
the measuring point.
Resistance- In the resistance-grounded system, the ohmic-inductive ground-fault current is decisive
Grounded for the direction determination.
To evaluate this short-circuit current, set the parameters as follows:

• Dir. measuring method = cos φ


• φ correction = -45.0°
Set the Min.polar.3I0> for dir.det. and 3I0> threshold value parame-
ters to a value below the minimum ground-fault current to be expected.

642 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Parameter: α1 reduction dir. area, α2 reduction dir. area

• Recommended setting value (_:12601:105) α1 reduction dir. area = 2°

• Recommended setting value (_:12601:106) α2 reduction dir. area = 2°


With the α1 reduction dir. area and α2 reduction dir. area parameters, you specify the angle
for the limitation of the direction range. Siemens recommends using the default setting of 2°.
In an arc-suppression-coil-ground system in feeders with a very large reactive current, it can be practical to set
a somewhat larger angle α1 to avoid a false pickup based on transformer and algorithm tolerances.

Parameter: V0> threshold value

• Default setting (_:12601:103) V0> threshold value = 30.000 V


The V0> threshold value parameter allows you to set the zero-sequence voltage sensitivity of the stage.
Set the threshold value smaller than the minimum absolute value of the zero-sequence voltage V0 that must
still be detected.

Parameter: Dir. determination delay

• Default setting (_:12601:104) Dir. determination delay = 0.00 s


The start of the ground fault normally shows a significant transient behavior. This can lead to an incorrect
direction decision. The direction determination can be delayed from the occurrence of the zero-sequence
voltage with the Dir. determination delay parameter to achieve steady-state measurands. The dura-
tion of the transient cycle is determined from the system conditions and the respective fault characteristics. If
you have no knowledge of a suitable time delay, Siemens recommends keeping the default setting.

Parameter: Operate delay

• Default setting (_:12601:6) Operate delay = 2.0 s


The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.

6.16.4.3 Settings

Addr. Parameter C Setting Options Default Setting


3I0> cos/sinφ1
_:12601:1 3I0> cos/sinφ1:Mode • off off
• on
• test
_:12601:2 3I0> cos/sinφ1:Operate • no no
& flt.rec. blocked
• yes
_:12601:10 3I0> cos/sinφ1:Blk. by • no yes
meas.-volt. failure
• yes
_:12601:27 3I0> cos/sinφ1:Blk. w. • no no
inrush curr. detect.
• yes
_:12601:110 3I0> cos/sinφ1:Blk. after • no yes
fault extinction
• yes
_:12601:108 3I0> cos/sinφ1:Direc- • forward forward
tional mode
• reverse
_:12601:109 3I0> cos/sinφ1:Dir. • cos φ cos φ
measuring method
• sin φ
_:12601:107 3I0> cos/sinφ1:φ correc- -45 ° to 45 ° 0°
tion

SIPROTEC 5, 7SJ82/7SJ85, Manual 643


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Addr. Parameter C Setting Options Default Setting


_:12601:102 3I0> cos/ 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
sinφ1:Min.polar.3I0> for 5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
dir.det.
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.150 A
_:12601:105 3I0> cos/sinφ1:α1 reduc- 1 ° to 15 ° 2°
tion dir. area
_:12601:106 3I0> cos/sinφ1:α2 reduc- 1 ° to 15 ° 2°
tion dir. area
_:12601:101 3I0> cos/sinφ1:3I0> 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
threshold value 5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.250 A
_:12601:103 3I0> cos/sinφ1:V0> 0.300 V to 200.000 V 30.000 V
threshold value
_:12601:104 3I0> cos/sinφ1:Dir. 0.00 s to 60.00 s 0.10 s
determination delay
_:12601:6 3I0> cos/sinφ1:Operate 0.00 s to 60.00 s 2.00 s
delay

6.16.4.4 Information List

No. Information Data Class Type


(Type)
3I0> cos/sinφ1
_:12601:81 3I0> cos/sinφ1:>Block stage SPS I
_:12601:501 3I0> cos/sinφ1:>Block delay & op. SPS I
_:12601:54 3I0> cos/sinφ1:Inactive SPS O
_:12601:52 3I0> cos/sinφ1:Behavior ENS O
_:12601:53 3I0> cos/sinφ1:Health ENS O
_:12601:60 3I0> cos/sinφ1:Inrush blocks operate ACT O
_:12601:302 3I0> cos/sinφ1:Ground fault ACD O
_:12601:55 3I0> cos/sinφ1:Pickup ACD O
_:12601:56 3I0> cos/sinφ1:Operate delay expired ACT O
_:12601:57 3I0> cos/sinφ1:Operate ACT O

6.16.5 Directional Transient Ground-Fault Stage

6.16.5.1 Description

Overview
Ground faults occurring in arc-suppression-coil-ground systems often extinguish a short time after the igni-
tion, mostly within a few milliseconds. Such transient occurrences are called transient ground faults. In order
to detect the ground-fault direction, based on these transient occurrences, a special method of measurement
is required that can also capture high frequencies. Conventional methods based on phasor calculations are not
suitable. Even for ground faults lasting for a short time, usually, a high-frequency charging process occurs in
healthy phases. The transient charging process is evaluated by an energy-integrating method to determine the

644 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

ground-fault direction. This method ensures high sensitivity and positive stability against parasitic signals in
the zero-sequence system.
Since permanent ground faults also start with the transient charging process in healthy phases, those errors
will be detected as well.
This stage is most suitable for the use in closed loops or meshed systems. Operational, circulating zero-
sequence currents are eliminated and therefore, cannot affect the directional result.

Stage-Control Logic

[lostuwis-240113-01.tif, 2, en_US]

Figure 6-137 Logic Diagram of the Stage Control

Blocking the Stage via Binary Input Signal


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage will be reset.

Blocking the Stage in Case of Measuring-Voltage Failure


The stage can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset. The following blocking options are available for the stage:

• From inside on pickup of the Measuring-voltage failure detection function

• From an external source via the binary input signal >Open of the function block Volt.-transf. c. b., which
links in the tripping of the voltage-transformer circuit breaker.
The Blk. by meas.-volt. failure parameter can be set so that measuring-voltage failure detection
blocks the stage or not.

SIPROTEC 5, 7SJ82/7SJ85, Manual 645


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Logic of the Transient Ground-Fault Functionality

[lowisfut-240113-01.tif, 8, en_US]

Figure 6-138 Logic Diagram of the Directional Transient Ground-Fault Stage

Measured Values, Method of Measurement


The zero-sequence voltage and zero-sequence current are measured directly or calculated from the phase vari-
ables. When measuring directly, the following is detected:

• Zero-sequence voltage on the broken-delta winding

• Zero-sequence current via Holmgreen connection or via core balance current transformer
The voltage measured on the broken-delta winding will be converted to the zero-sequence voltage V0.
The instantaneous values of the zero-sequence voltage v0(t) that are sampled at a high frequency (8 kHz)
serve to determine the point in time of the ground fault occurrence T0.
The instantaneous values of the zero-sequence voltage v0(t) and the ground current 3i0(t), which are sampled
at a high frequency (8 kHz), are the basis for direction determination.
The fundamental-component values of the zero-sequence voltage V0 serve to release the directional result
and the pickup as well as a criterion for the stabilization against switching operations.
The positive-sequence system (if it exists as a measured value) serves as an additional criterion for the stabili-
zation against switching operations.
The fundamental-component value of V0 and the true RMS value of 3I0 will be used for the pickup and the
optional trip logic.

646 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Operational, meaning circulating zero-sequence currents, can occur in closed loops or meshed systems. This
type of zero-sequence current is also present in case of a failure and can falsify the directional result. There-
fore, an operational zero-sequence current is eliminated.

Determining the Time of the Ground-Fault Ignition


The algorithm uses the evaluation of the instantaneous values of the zero-sequence voltage to verify continu-
ously whether a ground fault occurred. This takes place regardless of whether the set threshold value for V0 is
exceeded. If a ground fault occurs, the measuring window for determining the direction is positioned and the
direction determination is performed. The position of the measuring window is logged via the indication Pos.
measuring window (in FB General). The precise identification of the time T0 at which the ground fault
occurs is decisive for the correct direction determination.

Determination of Direction, Method of Measurement


The active energy of the zero-sequence system is calculated for the direction determination. Once the ground-
fault occurrence has been detected, the active energy will be calculated across approximately 1 cycle
frequency. If the active energy of the zero-sequence system is negative, a forward fault is present; otherwise it
is a backward fault.

Directional Ground-Fault Signal, Pickup


Determining the time of the ground-fault ignition and the direction is always done with maximum sensitivity.
With the parameters V0> threshold value and 3I0> threshold value, you define the sensitivity for
the indication of the direction and the pickup of the stage.
If both of the following conditions are met, the direction result will be reported:

• The fundamental-component value of the zero-sequence voltage V0 exceeds the V0> threshold
value within 100 ms after detecting the ground-fault ignition.

• The true RMS value of the zero-sequence current 3I0 exceeds the 3I0> threshold value.
In this way, high-impedance ground faults are also reported in which the zero-sequence system values rise
only slowly, and, for this reason, the occurrence of the ground fault is detected noticeably earlier than the
exceedance of the parameterized threshold value.
The direction result will be reported to the function via the (_:2311:302) Ground fault of the function
block General information. This indication is reported irrespective of the parameterized direction of the func-
tion.
If the determined direction corresponds with the parameterized direction (parameter Directional mode), a
pickup occurs.

Reset of the Algorithm


To allow a new directional measurement, the algorithm needs to be reset. The normal reset takes place when
all the following conditions are met:

• The fundamental component of the zero-sequence voltage V0 drops below the V0 reset threshold. This
reset threshold is a small device-internal V0 threshold. It is also depending on an operational V0 and is
thus a dynamic threshold. The threshold value is 2.0 V secondary without dynamic influence.

• The duration of 120 ms after T0 has expired.

Stabilization against Switching Operations


Switching operations in the system to be protected can cause transient signals in the zero-sequence system.
The stage is stabilized against possible overfunction due to switching operations.

SIPROTEC 5, 7SJ82/7SJ85, Manual 647


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

The following mechanisms are applied:

• For reporting the direction result, the fundamental-component value of the zero-sequence voltage must
exceed the V0> threshold value in a time slot of 100 ms after the ground-fault ignition. This effec-
tively suppresses wrong indications as a result of switching operations.

• The fundamental-component value of the zero-sequence voltage V0 is not influenced by switching oper-
ations and is thus a good criterion for distinguishing the ground fault from a switching procedure. The
condition that the fundamental-component value must exceed the V0> threshold value for
reporting the direction result effectively suppresses the influence of switching operations.
For rare cases in which high zero-sequence voltages occur over longer time ranges after switching off the
feeder or line, a criterion based on the positive-sequence current is also effective. This criterion compares
the positive-sequence current before and after the transient event and thus detects a disconnection. In
case of disconnection, the direction result is not reported.
Through stabilization mechanisms, the direction result is reported 100 ms after the ground-fault ignition.
Thus a pickup occurs with a 100-ms delay.
If the stage is used in a 1-phase function group, the additional criterion via the positive-sequence current
is not effective.

• The function detects transient ground faults using the zero-sequence voltage. In systems with opera-
tional zero-sequence voltages, if the measuring voltage is switched on, the function can internally be
started. If the fundamental-component value of the zero-sequence voltage does not exceed the threshold
of the Maximum operational V0 parameter in a time slot of 100 ms after the function start, the func-
tion is reset internally.

Trip Logic

[loauswis-240113-01.tif, 4, en_US]

Figure 6-139 Trip Logic Diagram

648 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

In many applications, the transient ground-fault stage is used only to indicate the direction. In this case, the
trip logic is not required and remains disabled. However, this stage can also be used to disable a permanent
ground fault. For this, you enable the optional trip logic with the Operate functionality parameter. If
the fundamental-component value of V0 and the true RMS value of 3I0 exceed the set threshold values, the
tripping delay (Operate delay parameter) starts with the pickup. If the parameter Operate & flt.rec.
blocked is set to no, the stage operates when the tripping delay expires.
An intermittent ground fault has the characteristics of periodical extinction and reignition within one half
period up to several periods. You can find more information in chapter 6.15.1 Overview of Functions. Due to
the tripping delay and the too short fault durations (contact to ground), reliable tripping is not possible. To
ensure reliable tripping under such conditions, the parameter Dropout delay can be used. When the fault
extinguishes, the fundamental-component value of V0 and the true RMS value of 3I0 drop below the
threshold values. A dropout can be delayed for a time specified with the Dropout delay parameter. The
tripping delay continues to run. If the time delay expires within the dropout delay, the stage operates. You can
set the Dropout delay according to the application. The default setting is 0 s. The setting of the dropout
delay does not affect the direction determination. When the fault reignites, a new direction determination
takes place if the function has dropped out before. If the determined direction is opposite to the parameter-
ized direction or is unknown, the tripping delay is reset immediately.

Blocking the Tripping Delay with Detection of the Fault Extinction


Using the evaluation of the instantaneous value cycle of the zero-sequence voltage, the fault extinction of the
ground fault can be detected faster than via the dropout of the V0 fundamental-component value under the
pickup value. The fast detection of the fault extinction (see function block General information) blocks the
tripping delay after the dropout delay expires. With the parameter Blk. after fault extinction, this
accelerated blocking mechanism can be enabled or disabled.

6.16.5.2 Application and Setting Notes

Parameter: Operate functionality

• Default setting (_:13021:108) Operate functionality = no


If the transient ground-fault stage is used only to indicate the direction, this optional trip logic is not required
and remains disabled. If the transient ground-fault stage is used to disable permanent faults as well, this
optional trip logic is enabled. Pickup of the stage will initiate the tripping delay.

Parameter: Operate & flt.rec. blocked

• Default setting (_:13021:2) Operate & flt.rec. blocked = no


You can block the operate indication, the fault recording, and the fault log with the Operate & flt.rec.
blocked parameter. In this case, a ground-fault log is created instead of the fault log.

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:13021:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


enabled.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is linked with
the voltage-transformer circuit breaker.

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

SIPROTEC 5, 7SJ82/7SJ85, Manual 649


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Parameter: Blk. after fault extinction

• Recommended setting value (_:13021:107) Blk. after fault extinction = yes


If the Blk. after fault extinction parameter is set to yes, the tripping delay is reset after the detec-
tion of the fault extinction. Therefore, if the tripping delay is set for a short time, the possibility of an overfunc-
tion is avoided. The reason for an overfunction is a slower attenuation in the zero-sequence system following
the fault extinction. Siemens recommends keeping this default setting if the stage is used for tripping.
To protect against intermittent ground faults, the stage uses the parameter Dropout delay to delay a
dropout due to fault extinction. If you are using the stage for protection against intermittent ground faults,
disable the blocking.

Parameter: Directional mode

• Default setting (_:13021:106) Directional mode = forward


When a fault is detected, the selection of the parameter Directional mode defines whether the pickup of
the stage occurs in forward or backward direction.

Parameter: V0> threshold value

• Default setting (_:13021:103) V0> threshold value = 15.000 V


With the parameter V0> threshold value, you define the sensitivity for the indication of the direction and
the pickup of the stage.
Note that the sensitivity of the direction determination itself is not influenced. The direction determination
always works with maximum sensitivity.
If high-resistive ground faults must also be reported, very sensitive settings are possible, for example, V0>
threshold value = 5 V secondary.

Parameter: Maximum operational V0

• Recommended setting value (_:13021:105) Maximum operational V0 = 3.000 V


With the parameter Maximum operational V0, you define the maximum operational zero-sequence
voltage V0. If the fundamental-component value of the zero-sequence voltage V0 does not exceed the param-
eter Maximum operational V0 in a time slot of 100 ms after the function has started, the stage is reset.
The setting is made with reference to the zero-sequence voltage V0 according to its definition.

650 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Network Structure Description


Radial network In radial networks, operational zero-sequence voltages are rather small.
Siemens recommends using the default value of 3.000 V.
Ring network, meshed network Greater operational zero-sequence voltages can occur in ring or meshed
networks.
The secondary operational zero-sequence voltages can be determined by
reading the residual voltage VN sec or the zero-sequence voltage V0 sec under
the symmetrical components from the device or via DIGSI.
In case you read the secondary residual voltage VN sec, you convert it to V0 sec
with the Matching ratio Vph / VN parameter. You can find more
information in chapter 6.1.6 Application and Setting Notes for Measuring
Point Voltage 3‑Phase (V-3ph).
If V0 sec is greater than 2.5 V, the value of Maximum operational V0
shall be increased to V0 sec ⋅ 1.2.
Example:
VN sec = 5.000 V
Matching ratio Vph / VN = √3
V0 sec = 5.000 V ⋅ √3 / 3 = 2.887 V
Maximum operational V0 = 2.887 V ⋅ 1.2 = 3.464 V
In most cases, the operational zero-sequence voltages are smaller than
2.500 V. Siemens recommends using the default value of 3.000 V.

Parameter: 3I0> threshold value

• Default setting (_:13021:109) 3I0> threshold value = 0.000 A


With the parameter 3I0> threshold value, you define the sensitivity for the indication of the direction
and the pickup of the stage.
In ring or meshed systems, you can use this parameter to reduce the number of ground-fault reporting
devices. The parameter needs to be set according to the user experience on the specific network. For radial
systems, normally you can keep the default value of 0 A which sets this parameter to inactive.

Parameter: 3I0> threshold for operate

• Default setting (_:13021:104) 3I0> threshold for operate = 0.030 A


The setting is significant only for optional trip logic for switching off permanent ground faults. Select the
setting such that the static ground-fault current exceeds the threshold value. You can disable this criterion by
setting the value to 0 A.

Parameter: Dropout delay

• Default setting (_:13021:7) Dropout delay = 0.00 s


The parameter Dropout delay allows you to use the function also as a protection against intermittent
ground faults. With the parameter Dropout delay, the dropout of the pickup state after fault extinction is
delayed or held until the next ignition. Thus, the operate delay can go on and trip the fault.
Set the time to a value within which the new ignition can still be assigned to the previous fault. Typical values
are in a range between several hundred milliseconds and a few seconds.

Parameter: Operate delay

• Default setting (_:13021:6) Operate delay = 0.50 s


The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.
The setting of the Operate delay depends on the specific application. Ensure that the pickup is delayed by
100 ms regarding the time of the ground-fault ignition.

SIPROTEC 5, 7SJ82/7SJ85, Manual 651


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.5.3 Settings

Addr. Parameter C Setting Options Default Setting


Trans.Gnd.flt1
_:13021:1 Trans.Gnd.flt1:Mode • off off
• on
• test
_:13021:2 Trans.Gnd.flt1:Operate & • no no
flt.rec. blocked
• yes
_:13021:10 Trans.Gnd.flt1:Blk. by • no yes
meas.-volt. failure
• yes
_:13021:107 Trans.Gnd.flt1:Blk. after • no yes
fault extinction
• yes
_:13021:108 Trans.Gnd.flt1:Operate • no no
functionality
• yes
_:13021:106 Trans.Gnd.flt1:Direc- • forward forward
tional mode
• reverse
_:13021:103 Trans.Gnd.flt1:V0> 0.300 V to 200.000 V 15.000 V
threshold value
_:13021:105 Trans.Gnd.flt1:Maximum 0.300 V to 200.000 V 3.000 V
operational V0
_:13021:109 Trans.Gnd.flt1:3I0> 1 A @ 100 Irated 0.000 A to 35.000 A 0.000 A
threshold value 5 A @ 100 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.000 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.000 A
_:13021:104 Trans.Gnd.flt1:3I0> 1 A @ 100 Irated 0.000 A to 35.000 A 0.030 A
threshold for operate 5 A @ 100 Irated 0.00 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.150 A
_:13021:6 Trans.Gnd.flt1:Operate 0.00 s to 60.00 s 0.50 s
delay
_:13021:7 Trans.Gnd.flt1:Dropout 0.00 s to 60.00 s 0.00 s
delay

6.16.5.4 Information List

No. Information Data Class Type


(Type)
Trans.Gnd.flt1
_:13021:81 Trans.Gnd.flt1:>Block stage SPS I
_:13021:54 Trans.Gnd.flt1:Inactive SPS O
_:13021:52 Trans.Gnd.flt1:Behavior ENS O
_:13021:53 Trans.Gnd.flt1:Health ENS O
_:13021:302 Trans.Gnd.flt1:Ground fault ACD O
_:13021:55 Trans.Gnd.flt1:Pickup ACD O

652 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

No. Information Data Class Type


(Type)
_:13021:56 Trans.Gnd.flt1:Operate delay expired ACT O
_:13021:57 Trans.Gnd.flt1:Operate ACT O

6.16.6 Directional 3I0 Stage with φ(V0,3I0) Measurement

6.16.6.1 Description

Logic

[logfppvi-291112-02.vsd, 1, en_US]

Figure 6-140 Logic Diagram of the Stage Control

SIPROTEC 5, 7SJ82/7SJ85, Manual 653


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[lo_dir sensGFP 3I0 phi VI, 1, en_US]

Figure 6-141 Logic Diagram of the Directional 3I0 Stage with φ (V0,3I0) Measurement

Measured Value V0, Method of Measurement


The device can measure the residual voltage at the broken-delta winding. The measured voltage is converted
to a value with reference to the zero-sequence voltage V0. If the residual voltage is not available to the device
as a measurand, the zero-sequence voltage V0 is calculated from the measured phase-to-ground voltages VA,
VB, and VC using the defining equation.
This method of measurement processes the sampled voltage values and filters out the fundamental compo-
nent numerically.

Measured Value 3I0, Method of Measurement


The function usually evaluates the sensitively measured ground current 3I0 via a core balance current trans-
former. Since the linearity range of the sensitive measuring input ends at approx. 1.6 A, for larger secondary
ground currents, the function switches to the 3I0 current calculated from the phase currents. This results in a
very large linearity and settings range.
The method of measurement processes the sampled current values and filters out the fundamental compo-
nent numerically.

654 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Depending on the connection type of the measuring point and on the current terminal blocks used, different
linearity and setting ranges result. You can find more information in chapter Measured Value 3I0, Method of
Measurement , Page 636.

Ground-Fault Detection, Pickup


If the absolute value of the ground current 3I0 vector exceeds the threshold value 3I0> threshold value
and the absolute value of the zero-sequence voltage V0 vector exceeds the threshold value Min. V0> for
dir. determ., the stage detects the ground fault. The direction determination (see in the following para-
graph) is started when the zero-sequence voltage exceeds the threshold. The result from the direction deter-
mination is only valid if the absolute value of the ground current 3I0 vector has also exceeded its threshold
value. The direction result is indicated via the Ground fault signal (in the General function block).
As long as the direction result equals the parameterization direction (parameter Directional mode), the
stage picks up.

Direction Determination
Exceeding the threshold values by the zero-sequence voltage V0 is a criterion for the ground fault. The direc-
tion determination can be delayed from the occurrence of the zero-sequence voltage with the Dir. deter-
mination delay parameter to achieve steady-state measurands.
The direction is determined via the determination of the phase angle between the angle-error compensated
ground current 3I0com. and the rotated zero-sequence voltage V0, indicated in the following as reference
voltage Vref,rot. To take different system conditions and applications into account, the reference voltage can be
rotated through an adjustable angle (Rotation angle of ref. volt. parameter). This moves the vector
of the rotated reference voltage close to the vector ground current -3I0com. Consequently, the result of direc-
tion determination is as reliable as possible.
The rotated reference voltage Vref,rot and the Forward section +/- parameter define the forward and
reverse area. The forward area results as range ± Δφ around the rotated reference voltage Vref,rot. The value ±
Δφ is set with the Forward section +/- parameter. The remaining area besides the forward area is the
reverse area. Between the forward and reverse area, a hysteresis is defined, refer to Figure 6-142.

SIPROTEC 5, 7SJ82/7SJ85, Manual 655


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[dwdirrot-011112-02.vsd, 1, en_US]

Figure 6-142 Directional Characteristic in Forward Mode

Blocking the Stage via Binary Input Signal


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage will be reset.

Blocking the Stage in Case of Measuring-Voltage Failure


The stage can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset.
The following blocking options are available for the stage:

• From inside on pickup of the Measuring-voltage failure detection function

• From an external source via the binary input signal >open of the function block Voltage-transformer
circuit breaker, which links in the tripping of the voltage-transformer circuit breaker.
The Blk. by meas.-volt. failure parameter can be set so that measuring-voltage failure detection
blocks the stage or not.

Blocking the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate indication. A running time delay is reset. The pickup is indicated and a fault record is opened.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.

656 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.6.2 Application and Setting Notes

Parameter: Operate & flt.rec. blocked

• Default setting (_:2) Operate & flt.rec. blocked = no


You can block the operate indication, the fault recording, and the fault log with the Operate & flt.rec.
blocked parameter. In this case, a ground-fault log is created instead of the fault log.

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


enabled.

• The binary input signal >open of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

Parameter: Blk. w. inrush curr. detect.

• Recommended setting value (_:27) Blk. w. inrush curr. detect. = no


With the Blk. w. inrush curr. detect. parameter, you specify whether the operate is blocked during
detection of an inrush current.
Siemens recommends disabling the blocking. The fundamental component of the zero-sequence voltage is a
reliable criterion for the ground fault and remains unaffected by an enabling procedure.

Parameter: Directional mode

• Default setting (_:106) Directional mode = forward


When a fault is detected, the selection of the parameter Directional mode defines whether the pickup of
the stage occurs in forward or reverse direction.
When the parameter Directional mode is set as non-directional, the direction determination is not
considered. The pickup condition depends only on the absolute values 3I0 and V0 and the respective thresh-
olds. The forward direction is the direction towards the motor.

Parameter: Rotation angle of ref. volt.,Forward section +/-

• Default setting (_:104) Rotation angle of ref. volt. = -45°

• Default setting (_:103) Forward section +/- = 88°


With the Rotation angle of ref. volt. and Forward section +/- parameters, you set the direc-
tion characteristic, that is, the areas of forward and reverse. With this, you set the direction characteristic
according to the system conditions and the neutral-point treatment.
Typical settings for the Rotation angle of ref. volt.parameter are:

• Arc-suppression-coil-ground system: 0°

• Isolated system: +45°

• Grounded system: -45°

SIPROTEC 5, 7SJ82/7SJ85, Manual 657


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

The Forward section +/- parameter can normally be left at its default setting. A reduction of the forward
area by a few degrees is practical, for example, in an arc-suppression-coil-ground system with long cable
feeders, that generate high capacitive fault currents.

Parameter: Min. V0> for dir. determ.

• Default setting (_:102) Min. V0> for dir. determ. = 2.000 V


With the Min. V0> for dir. determ. parameter, you determine the minimum voltage V0 necessary for
the release of the direction determination that must be attained within the time delay Dir. determina-
tion delay.

Parameter: 3I0> threshold value

• Default setting (_:101) 3I0> threshold value = 0.050 A


The 3I0> threshold value parameter allows you to set the ground-current sensitivity of the stage. Set
the threshold value lower than the minimum absolute value of the ground-fault current 3I0 that must still be
detected.

Parameter: Dir. determination delay

• Default setting (_:105) Dir. determination delay = 0.10 s


The start of the ground fault normally shows a significant transient behavior. This can lead to an incorrect
direction decision. The direction determination can be delayed from the occurrence of the zero-sequence
voltage with the Dir. determination delay parameter to achieve steady-state measurands. The dura-
tion of the transient cycle is determined from the system conditions and the respective fault characteristics. If
you have no knowledge of a suitable time delay, Siemens recommends keeping the default setting.

Parameter: Operate delay

• Default setting (_:6) Operate delay = 0.50 s


The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.

6.16.6.3 Settings

Addr. Parameter C Setting Options Default Setting


3I0> φ(VI) #
_:1 3I0> φ(VI) #:Mode • off off
• on
• test
_:2 3I0> φ(VI) #:Operate & • no no
flt.rec. blocked
• yes
_:10 3I0> φ(VI) #:Blk. by • no yes
meas.-volt. failure
• yes
_:27 3I0> φ(VI) #:Blk. w. • no no
inrush curr. detect.
• yes
_:106 3I0> φ(VI) #:Directional • non-directional forward
mode
• forward
• reverse
_:104 3I0> φ(VI) #:Rotation -180 ° to 180 ° -45 °
angle of ref. volt.
_:103 3I0> φ(VI) #:Forward 0 ° to 180 ° 88 °
section +/-

658 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Addr. Parameter C Setting Options Default Setting


_:102 3I0> φ(VI) #:Min. V0> 0.300 V to 200.000 V 2.000 V
for dir. determ.
_:101 3I0> φ(VI) #:3I0> 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
threshold value 5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:105 3I0> φ(VI) #:Dir. deter- 0.00 s to 60.00 s 0.10 s
mination delay
_:6 3I0> φ(VI) #:Operate 0.00 s to 100.00 s 0.50 s
delay

6.16.6.4 Information List

No. Information Data Class Type


(Type)
3I0> φ(VI) #
_:81 3I0> φ(VI) #:>Block stage SPS I
_:501 3I0> φ(VI) #:>Block delay & op. SPS I
_:54 3I0> φ(VI) #:Inactive SPS O
_:52 3I0> φ(VI) #:Behavior ENS O
_:53 3I0> φ(VI) #:Health ENS O
_:301 3I0> φ(VI) #:Fault not in trip area SPS O
_:60 3I0> φ(VI) #:Inrush blocks operate ACT O
_:303 3I0> φ(VI) #:Ground fault ACD O
_:55 3I0> φ(VI) #:Pickup ACD O
_:56 3I0> φ(VI) #:Operate delay expired ACT O
_:57 3I0> φ(VI) #:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 659


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.7 Directional Y0 Stage with G0 or B0 Measurement

6.16.7.1 Description

Logic

[lo_stage_control_Y0G0B0, 1, en_US]

Figure 6-143 Logic Diagram of the Stage Control

660 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[LoY0G0B0-300713-01, 6, en_US]

Figure 6-144 Logic Diagram of the Directional Y0 Stage with G0 or B0 Measurement

Measured Value V0, Method of Measurement


The device can measure the residual voltage at the broken-delta winding. The measured voltage VN is
converted to a value with reference to the zero-sequence voltage V0. If the residual voltage is not available to
the device as a measurand, the zero-sequence voltage V0 is calculated from the measured phase-to-ground
voltages VA, VB, and VC using the definition equation.
The method of measurement processes the sampled voltage values and filters out the fundamental compo-
nent numerically.

Measured Value 3I0, Method of Measurement


The function usually evaluates the ground current 3I0 sensitively measured via a core balance current trans-
former. Since the linearity range of the sensitive measuring input ends at approx. 1.6 A, for larger secondary
ground currents, the function switches to the 3I0 calculated from the phase currents. This results in a very
large linearity and settings range.
The method of measurement processes the sampled current values and filters out the fundamental compo-
nent numerically. The methods of measurement are characterized by high accuracy and by insensitivity to
harmonics, especially the 3rd and 5th harmonics frequently present in the ground-fault (residual) current.

SIPROTEC 5, 7SJ82/7SJ85, Manual 661


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Depending on the connection type of the measuring point as well as the current terminal blocks used,
different linearity and setting ranges result. You can find more information in section Measured Value 3I0,
Method of Measurement , Page 636.

Y0, G0, B0
The fundamental-component values of V0 and 3I0 are used to calculate the admittance Y0 = G0 + jB0. You can
choose to use G0 or B0 to determine the direction.

Ground-Fault Detection, Pickup


If the absolute value of the ground current 3I0 exceeds the threshold value 3I0> release thresh.
value and the absolute value of the zero-sequence voltage V0 exceeds the threshold value V0> threshold
value, the stage recognizes the ground fault. The calculation of G0 or B0 is started with exceeding the
threshold values and then, the direction determination (see the following) is performed. The direction result is
indicated via the Ground fault signal (in the General function block). If the direction result equals the para-
meterized direction (parameter Directional mode), the stage picks up.

Direction Determination
Exceeding the threshold values by the zero-sequence voltage V0 is a criterion for the ground fault. The direc-
tion determination can be delayed from the occurrence of the zero-sequence voltage with the Dir. deter-
mination delay parameter to achieve steady-state measurands. The result from the direction determina-
tion is only valid if the absolute value of the ground current 3I0 has also exceeded its release threshold value.
The following figure shows an example of the direction determination in the complex phasor diagram for the
G0 direction measurement method with a correction value of the direction straight line from 0 (Parameter φ
correction). The example is suitable for the determination of the ground-fault direction in an arc-suppres-
sion-coil-ground system where the value G0 is decisive for the direction determination.

[DwY0Dire-171012-01, 1, en_US]

Figure 6-145 Direction-Characteristic Curve for the G0 Measurement

The zero-sequence voltage V0 is generally the reference value for the real axis and is identical to the G0 axis.
The axis of symmetry of the direction-characteristic curve coincides with the B0 (reactive) axis for this
example. For the direction determination, the component of the admittance perpendicular to the set direc-
tion-characteristic curve (= axis of symmetry) is decisive G0dir (=Y0dir). In this example, this is the active
component G0active of the admittance Y0. The conductance G0dir. (here = G0active) is calculated and
compared with the setting value Polarized G0/B0 threshold. If the conductance G0dir. exceeds the
positive setting value, the direction is forward. If the conductance G0dir. exceeds the negative setting value,
the direction is backward. In the range in between, the direction is undetermined.

662 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

With the α1 reduction dir. area and α2 reduction dir. area parameters, you can limit the
forward and backward ranges as shown in Figure 6-146. With this, the direction determination is secured in
case of high currents in the direction of the axis of symmetry.
The symmetry axis can be turned via a correction angle (φ correction parameter) in a range of ±45.
Through this, it is possible, for example, to attain the greatest sensitivity in grounded systems in the resistive-
inductive range with a -45° turn. In the case of electric machines in busbar connection on the isolated system,
the greatest sensitivity in the resistive-capacitive range can be attained with a turn of +45° (see following
figure).

[DwY0meas-171012-01, 1, en_US]

Figure 6-146 Turning the Direction-Characteristic Curves with G0 Measurement with Angle Correction

If you set the Dir. measuring method parameter to B0 and the φ correction parameter to 0, the axis
of symmetry of the direction-characteristic curve coincides with the G0 and V0 axes. Since the component of
the admittance Y0 perpendicular to the direction-characteristic curve (= axis of symmetry) is decisive (B0dir.
(=Y0dir.)), here, the susceptance B0 (reactive) is used in the direction determination. If the susceptance B0dir.
(B0reactive) exceeds the negative setting value Polarized G0/B0 threshold, the direction is forward. If
the susceptance B0dir. exceeds the positive setting value, the direction is backward. In the range in between,
the direction is undetermined.
This direction measurement thus is appropriate for the determination of ground-fault direction in isolated
systems.

SIPROTEC 5, 7SJ82/7SJ85, Manual 663


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[DwSiCoY0-011112-01, 1, en_US]

Figure 6-147 Direction-Characteristic Curve for the B0 Measurement

Blocking the Stage via Binary Input Signal


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage will be reset.

Blocking the Stage in Case of Measuring-Voltage Failure


The stage can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset.
The following blocking options are available for the stage:

• From inside on pickup of the Measuring-voltage failure detection function

• From an external source via the binary input signal >open of the function block Voltage-transformer
circuit breaker, which links in the tripping of the voltage-transformer circuit breaker.
The Blk. by meas.-volt. failure parameter can be set so that Measuring-voltage failure detection
blocks the stage or does not block it.

Blocking the Pickup with Detection of the Fault Extinction


Using the evaluation of the instantaneous value developing of the zero-sequence voltage, the fault extinction
can be recognized faster than via the dropout of the V0 fundamental-component value under the pickup
value. The pickup of the stage is blocked with the fast detection of the fault extinction. With this, the pickups
are avoided due to the decay procedure in the zero-sequence system after the fault extinction. With the Blk.
after fault extinction parameter, you enable or disable this accelerated detection of the fault extinc-
tion.

Blocking of the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate indication. A running time delay is reset. The pickup is indicated and a fault record is opened.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

664 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.

6.16.7.2 Application and Setting Notes

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


enabled.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is linked with
the voltage-transformer circuit breaker.

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

Parameter: Blk. w. inrush curr. detect.

• Recommended setting value (_:27) Blk. w. inrush curr. detect. = no


With the Blk. w. inrush curr. detect. parameter, you specify whether the operate is blocked during
detection of an inrush current.
Siemens recommends disabling the blocking. The fundamental component of the zero-sequence voltage is a
reliable criterion for the ground fault and remains untouched by an enabling procedure.

Parameter: Blk. after fault extinction

• Recommended setting value (_:110) Blk. after fault extinction = yes


If the Blk. after fault extinction parameter is set to yes, the pickup is blocked after detection of
the fault extinction. With this, the pickups are avoided due to the decay procedure in the zero-sequence
system after the fault extinction. Siemens recommends using the default setting.

Parameter: Directional mode

• Default setting (_:108) Directional mode = forward


When a fault is detected, the selection of the parameter Directional mode defines whether the pickup of
the stage occurs in forward or backward direction.

Parameter: Dir. measuring method, φ correction, Polarized G0/B0 threshold, 3I0> release
thresh. value

• Default setting (_:109) Dir. measuring method = G0

• Default setting (_:107) φ correction = 0.0°

• Default setting (_:102) Polarized G0/B0 threshold = 2.00 mS

• Default setting (_:101) 3I0> release thresh. value = 0.002 A


These parameters are used to define the direction characteristic of the stage. The direction characteristic to
use is dependent on the neutral-point treatment of the system.

SIPROTEC 5, 7SJ82/7SJ85, Manual 665


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Note that, for the direction determination, basically only the component of the admittance perpendicular to
the set direction-characteristic curve is decisive, see chapter 6.16.7.1 Description. This admittance component
is compared to the threshold value Polarized G0/B0 threshold. In contrast, the absolute value of the
current 3I0 is compared with the 3I0> release thresh. value parameter.

666 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

System Type/ Description


Neutral-Point Treat-
ment
Grounded In the arc-suppression-coil-ground system, the watt-metric residual current 3I0 · cos φ
of the arc-suppression coil is decisive for the direction determination.
To evaluate the watt-metric residual current, set the parameters as follows:

• Dir. measuring method = G0


• φ correction = 0.0°
The direction determination for a ground fault is made more difficult in that a much
larger reactive current of capacitive or inductive character is superimposed on the small
watt-metric residual current. Therefore, depending on the system configuration and
the fault evaluation, the total ground current supplied to the device can vary consider-
ably in its values regarding the magnitude and the phase angle. However, the device
should only evaluate the active component of the ground-fault current.
This requires extremely high accuracy, particularly regarding the phase-angle measure-
ment of all the instrument transformers. Furthermore, the device must not be set to
operate too sensitively. A reliable direction measurement can only be expected with
connection to a core balance current transformer. For the setting of the Polarized
G0/B0 threshold parameter, the following formula applies:

where:
ks: Safety margin, ks = 1.2 (cable networks), ks = 2.0 (overhead lines)
I0active: Active component of the ground-fault current (watt-metric residual current) of
the protected line
Vrated: Secondary rated voltage in the healthy case
I0min: Min. ground current in the healthy case, 5 mA to 10 mA (core balance current
transformer), 50 mA to 100 mA (Holmgreen transformer)
V0>: Pickup threshold of the residual voltage ≈ 0.1
If a parallel resistor Rp is used on the arc-suppression coil, the threshold value G0 must
also be smaller than:

where:
ks: Safety margin ≥ 1.5
IRp: Secondary rated current of the parallel resistor
Vrated: Secondary rated voltage in the healthy case
The 3I0> release thresh. value parameter can be set to half of the expected
measuring current and here, the entire zero-sequence current can be put to use.
Isolated In the isolated system, the capacitive ground reactive current 3I0 · sin φ is decisive for
the direction determination.
To evaluate the capacitive ground reactive current, set the parameters as follows:

• Dir. measuring method = B0


• φ correction = 0.0°
In isolated systems, a ground fault allows the capacitive ground-fault currents of the
entire electrically connected system, except for the ground current in the faulty cable
itself, to flow through the measuring point as the latter flows directly away from the

SIPROTEC 5, 7SJ82/7SJ85, Manual 667


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

System Type/ Description


Neutral-Point Treat-
ment
fault location (that is, not via the measuring point). The following formula can be used
to determine the pickup value of the Polarized G0/B0 threshold parameter.

where:
I0min: Ground current in the healthy case

V0>: Pickup threshold of the residual voltage ≈ 0.02


In healthy operation, B0 ≤ 0.
For the 3I0> release thresh. value parameter, select around half of this capac-
itive ground-fault current flowing via the measuring point.
Resistance- In the resistance-grounded system, the ohmic-inductive ground-fault current is decisive
Grounded for the direction determination.
To evaluate this short-circuit current, set the parameters as follows:

• Dir. measuring method = G0


• φ correction= -45.0°
For the setting of the Polarized G0/B0 threshold parameter, the rule of thumb
is: Set the pickup value according to the following formula where only the active
ground-fault current can be put into use.

where:
ks: Safety margin, ks = 1.2 (cable networks), ks = 2.0 (overhead lines)
I0active: Active component of the ground-fault current of the protected line
Vrated: Secondary rated voltage in the healthy case
I0min: Min. ground current in the healthy case, 5 mA to 10 mA (core balance current
transformer), 50 mA to 100 mA (Holmgreen transformer)
V0>: Pickup threshold of the residual voltage ≈ 0.02
The 3I0> release thresh. value parameter must be set to a value below the
minimum expected ground-fault current.

Parameter: α1 reduction dir. area, α2 reduction dir. area

• Recommended setting value (_:105) α1 reduction dir. area = 2°

• Recommended setting value (_:106) α2 reduction dir. area = 2°


With the α1 reduction dir. area and α2 reduction dir. area parameters, you specify the angle
for the limitation of the direction range. Siemens recommends using the default setting of 2°.
In an arc-suppression-coil-ground system in feeders with a very large reactive current, it can be practical to set
a somewhat larger angle α1 to avoid a false pickup based on transformer and algorithm tolerances.

Parameter: V0> threshold value

• Default setting (_:103) V0> threshold value = 30.000 V


The V0> threshold value parameter allows you to set the zero-sequence voltage sensitivity of the stage.
The threshold value must be smaller than the minimum amount of the zero-sequence voltage V0 which must
still be detected.

668 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Parameter: Dir. determination delay

• Default setting (_:104) Dir. determination delay = 0.10 s


The start of the ground fault normally indicates a significant transient behavior. This can lead to an incorrect
direction decision. The direction determination can be delayed for this reason from the occurrence of the zero-
sequence voltage with the Dir. determination delay parameter to achieve steady-state measurands.
The duration of the transient cycle is determined from the system conditions and the respective fault charac-
teristics. If you have no knowledge of a suitable time delay, Siemens recommends keeping the default setting.

Parameter: Operate delay

• Default setting (_:6) Operate delay = 2.0 s


The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.

6.16.7.3 Settings

Addr. Parameter C Setting Options Default Setting


Y0> G0/B0 #
_:1 Y0> G0/B0 #:Mode • off off
• on
• test
_:2 Y0> G0/B0 #:Operate & • no no
flt.rec. blocked
• yes
_:10 Y0> G0/B0 #:Blk. by • no yes
meas.-volt. failure
• yes
_:27 Y0> G0/B0 #:Blk. w. • no no
inrush curr. detect.
• yes
_:110 Y0> G0/B0 #:Blk. after • no yes
fault extinction
• yes
_:108 Y0> G0/B0 #:Directional • forward forward
mode
• reverse
_:109 Y0> G0/B0 #:Dir. meas- • G0 G0
uring method
• B0
_:107 Y0> G0/B0 #:φ correc- -45 ° to 45 ° 0°
tion
_:102 Y0> G0/B0 #:Polarized 0.10 mS to 100.00 mS 2.00 mS
G0/B0 threshold
_:105 Y0> G0/B0 #:α1 reduc- 1 ° to 15 ° 2°
tion dir. area
_:106 Y0> G0/B0 #:α2 reduc- 1 ° to 15 ° 2°
tion dir. area
_:101 Y0> G0/B0 #:3I0> 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
release thresh. value 5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.150 A
_:103 Y0> G0/B0 #:V0> 0.300 V to 200.000 V 30.000 V
threshold value

SIPROTEC 5, 7SJ82/7SJ85, Manual 669


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Addr. Parameter C Setting Options Default Setting


_:104 Y0> G0/B0 #:Dir. deter- 0.00 s to 60.00 s 0.10 s
mination delay
_:6 Y0> G0/B0 #:Operate 0.00 s to 60.00 s 2.00 s
delay

6.16.7.4 Information List

No. Information Data Class Type


(Type)
Y0> G0/B0 #
_:81 Y0> G0/B0 #:>Block stage SPS I
_:501 Y0> G0/B0 #:>Block delay & op. SPS I
_:54 Y0> G0/B0 #:Inactive SPS O
_:52 Y0> G0/B0 #:Behavior ENS O
_:53 Y0> G0/B0 #:Health ENS O
_:60 Y0> G0/B0 #:Inrush blocks operate ACT O
_:55 Y0> G0/B0 #:Pickup ACD O
_:56 Y0> G0/B0 #:Operate delay expired ACT O
_:57 Y0> G0/B0 #:Operate ACT O

6.16.8 Directional Stage with Phasor Measurement of a Harmonic

6.16.8.1 Description
The Directional stage with phasor measurement of a harmonic is based on a continuous measuring direc-
tion-determination method. The stage determines the direction via the 3rd, 5th, or 7th harmonic phasors of
the zero-sequence voltage V0 and current 3I0.

670 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Logic

[lo_sensGFP V0 dir harmonic, 1, en_US]

Figure 6-148 Logic Diagram of the Directional Stage with Phasor Measurement of a Harmonic

SIPROTEC 5, 7SJ82/7SJ85, Manual 671


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[lo_start condition and dir. determ, 1, en_US]

Figure 6-149 Logic Diagram of the Start Conditions and of the Direction Determination

Measured Values, Methods of Measurement


The device can measure the residual voltage at the broken-delta winding. The measured voltage is converted
to a value with reference to the zero-sequence voltage V0. If the residual voltage is not available to the device
as a measurand, the zero-sequence voltage V0 is calculated from the measured phase-to-ground voltages VA,
VB, and VC using the defining equation.
For the measured value 3I0 and the method of measurement, you can find more information in section Meas-
ured Value 3I0, Method of Measurement , Page 636.
The function uses the fundamental-component value of V0 and the 3rd, 5th, or 7th harmonic phasor of V0
and 3I0 for direction determination. The specific harmonic phasor to be used is determined by the Harmonic
selection setting.

Ground-Fault Detection, Pickup


If the fundamental-component value of the zero-sequence voltage V0 exceeds the threshold V0>
threshold value, the stage detects the ground fault and the timer Dir. determination delay starts.
If the following 2 conditions are met, the ground-fault signaling and direction determination start:

• The fundamental-component value of the zero-sequence voltage V0 keeps exceeding the threshold V0>
threshold value during the period of the timer Dir. determination delay.

• The absolute value of the zero-sequence harmonic current 3I0harm. exceeds the threshold Min. 3I0>
harmonic when the timer Dir. determination delay expires.

672 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

To carry out the direction determination, the following condition must also be met in addition to the
preceding 2 conditions:
The zero-sequence harmonic voltage V0harm. must exceed the threshold which is 0.02 % of the secondary
rated voltage of the voltage transformer. If this condition is not met, the direction result is unknown.
The direction result is indicated via the Ground fault signal.
The stage pickup depends on the direction result and on the Directional mode parameter:

• If the Directional mode parameter is set as forward or reverse, the stage picks up when the direc-
tion result equals the parameterized direction, and the Pickup is signaled with the determined direction.

• If the Directional mode parameter is set as non-directional, the stage picks up regardless of the
direction result, and the Pickup is signaled with the unknown information.

Direction Determination
With the Harmonic selection parameter, you can select the 3rd, 5th, or 7th harmonic phasor for direction
determination. The direction is determined via the calculation of the phase angle between the following
values:

• Zero-sequence harmonic current 3I0harm.

• Rotated zero-sequence harmonic voltage V0harm., indicated in the following as reference voltage Vref,rot

The reference voltage is rotated by the angle +90° in relation to V0. This provides the maximum security for
the direction determination assuming that 3I0harm. is a reactive current.
The rotated reference voltage Vref,rot and the Forward section +/- parameter define the forward and
reverse area. For details, refer to Figure 6-150.
The areas in the following figure are as follows:

• The forward area results as range ± Δφ around the rotated reference voltage Vref,rot. You can set the value
± Δφ with the Forward section +/- parameter. If the vector of the secondary ground current
-3I0harm. lies within this area, the direction result is forward.

• The mirror area of the forward area is the reverse area. If the vector of the secondary ground current
-3I0harm. lies within this area, the direction result is reverse.

• In the intermediate range, the direction is unknown.

[dw_sensGFP V0 dir harmonic, 1, en_US]

Figure 6-150 Direction Characteristic

SIPROTEC 5, 7SJ82/7SJ85, Manual 673


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Stabilization Counter
To determine a reliable direction result, the function uses a stabilization counter. For indicating a direction
result, the determined direction must be stable for 4 successive measuring cycles. The cycle time is 10 ms.

Direction-Result Extension
With the timer Dir.-result extension, you can extend the last determined direction result if the condi-
tions for a further direction determination are no longer met. The last direction result is held until the condi-
tions for a further direction determination are met again (timer is reset) or until the timer expires. The
behavior of the direction-result extension varies according to the setting of the Directional mode param-
eter:

• Directional mode = forward or reverse


As soon as the zero-sequence harmonic current 3I0harm. or the zero-sequence harmonic voltage
V0harm. falls below its respective dropout value, the timer Dir.-result extension starts. If the
direction result equals the setting of the Directional mode parameter, the last Pickup signal is also
extended.
If both 3I0harm. and V0harm. exceed their thresholds again, the timer Dir.-result extension is
reset immediately and the direction determination is carried out again.

• Directional mode = non-directional


As soon as the zero-sequence harmonic current 3I0harm. falls below its dropout value, the timer Dir.-
result extension starts.
In this directional mode, the Pickup is signaled only with the direction information unknown regardless
of the actual direction that is indicated via the Ground fault signal. Therefore, the Pickup signal with
the unknown information is extended.
If 3I0harm. exceeds its threshold again, the timer Dir.-result extension is reset immediately and
the direction determination is carried out again.

Measured Value Display


After the timer Dir. determination delay expires and the V0 fundamental-component value keeps
exceeding the V0> threshold value, the following measured values are issued:

• V0 harm.
• 3I0 harm.
• Phi(I,V) harm.
These measured values are displayed as --- if 3I0harm. or V0harm. is smaller than 0.005 % of the rated secon-
dary current or voltage.

Blocking the Stage via Binary Input Signal


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage will be reset.

Blocking the Stage in Case of Measuring-Voltage Failure


The stage can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset.
The following blocking options are available for the stage:

• From inside on pickup of the Measuring-voltage failure detection function

• From an external source via the binary input signal >Open of the function block Voltage-transformer
circuit breaker, which links in the tripping of the voltage-transformer circuit breaker
The Blk. by meas.-volt. failure parameter can be set so that the Measuring-voltage failure detec-
tion blocks the stage or not.

674 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.8.2 Application and Setting Notes

Parameter: V0> threshold value

• Default setting (_:102) V0> threshold value = 20.000 V


The V0> threshold value parameter allows you to set the zero-sequence (fundamental) voltage sensi-
tivity of the stage. Set the threshold value smaller than the minimum absolute value of the zero-sequence
voltage V0 that must still be detected. Typical values are in the range of 15 V to 25 V.

Parameter: Dir. determination delay

• Default setting (_:105) Dir. determination delay = 0.00 s


The start of the ground fault normally shows a significant transient behavior. This can lead to an incorrect
direction decision. The direction determination can be delayed from the occurrence of the zero-sequence
voltage with the Dir. determination delay parameter to achieve steady-state measurands. The dura-
tion of the transient cycle is determined from the system conditions and the respective fault characteristics. If
you have no knowledge of a suitable time delay, Siemens recommends keeping the default setting.

Parameter: Forward section +/-

• Default setting (_:103) Forward section +/- = 80°


With the Forward section +/- parameter, you set the direction characteristic, that is, the forward and
reverse areas.
The Forward section +/- parameter can normally be left at its default setting. With reducing the forward
area, you can provide more security for the direction result, but on the other hand, you increase the proba-
bility of an underfunction.

Parameter: Dir.-result extension

• Default setting (_:110) Dir.-result extension = 5.00 s


With the Dir.-result extension parameter, you define the time for extending the last determined direc-
tion result if the conditions for further direction determination are no longer met.
This timer can be used to generate a stable direction indication under fluctuating zero-sequence harmonics. A
stable direction indication again can be required for the implementation of a prioritization schema between
different parallel working detection methods (stages).

Parameter: Harmonic selection

• Default setting (_:201) Harmonic selection = 5th harmonic


With the Harmonic selection parameter, you select to use the 3rd, 5th, or 7th harmonic phasor of the
zero-sequence voltage V0 and of the zero-sequence current 3I0 for direction determination.

Parameter: Min. 3I0> harmonic

• Default setting (_:203) Min. 3I0> harmonic = 0.030 A


With the Min. 3I0> harmonic parameter, you define the threshold value of the zero-sequence harmonic
current 3I0harm. for detecting the ground fault and for starting direction determination. You can find more
information in the section Ground-Fault Detection, Pickup, Page 672.
This parameter needs to be set according to the experience from the specific network. This requires the anal-
ysis of permanent ground faults from the network. If such information is unavailable, Siemens recommends a
rather low setting in the area of 5 mA to 10 mA secondary.

Parameter: 3I0 harm. dropout ratio

• Default setting (_:204) 3I0 harm. dropout ratio = 0.60

SIPROTEC 5, 7SJ82/7SJ85, Manual 675


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

With the 3I0 harm. dropout ratio parameter, you define the dropout threshold for the Min. 3I0>
harmonic parameter.
Lowering this dropout threshold enlarges the range and the period of direction determination under fluctu-
ating zero-sequence harmonics. Siemens recommends using the default setting.

Parameter: Directional mode

• Default setting (_:106) Directional mode = forward


With the Directional mode parameter, you define for which direction result the function generates the
pickup state:

• If the Directional mode parameter is set as forward or reverse, the stage picks up when the direc-
tion result equals the parameterized direction, and the Pickup is signaled with the determined direction.

• If the Directional mode parameter is set as non-directional, the stage picks up regardless of the
direction result, and the Pickup is signaled with the unknown information.

Parameter: Operate delay

• Default setting (_:6) Operate delay = 1.00 s


The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.

NOTE

i When both the Operate delay and the Dir.-result extension are applied, the Operate delay
should usually be set to a considerably greater value than the Dir.-result extension. If the Operate
delay is less than the Dir.-result extension, the function will operate for each fault regardless of
the fault duration, as long as the fault direction equals the set direction.

Parameter: Operate & flt.rec. blocked

• Default setting (_:2) Operate & flt.rec. blocked = no


With the Operate & flt.rec. blocked parameter, you block the operate indication, the fault recording,
and the fault log. In this case, a ground-fault log is created instead of the fault log.

Parameter: Blk. by meas.-volt. failure

• Default setting (_:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


enabled.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

676 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.8.3 Settings

Addr. Parameter C Setting Options Default Setting


V0>dir.harm.#
_:1 V0>dir.harm.#:Mode • off off
• on
• test
_:2 V0>dir.harm.#:Operate • no no
& flt.rec. blocked
• yes
_:10 V0>dir.harm.#:Blk. by • no yes
meas.-volt. failure
• yes
_:106 V0>dir.harm.#:Direc- • non-directional forward
tional mode
• forward
• reverse
_:103 V0>dir.harm.#:Forward 0 ° to 90 ° 80 °
section +/-
_:102 V0>dir.harm.#:V0> 0.300 V to 200.000 V 20.000 V
threshold value
_:201 V0>dir.harm.#:Harmonic • 3rd harmonic 5th harmonic
selection
• 5th harmonic
• 7th harmonic
_:203 V0>dir.harm.#:Min. 3I0> 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
harmonic 5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.150 A
_:204 V0>dir.harm.#:3I0 harm. 0.10 to 0.95 0.60
dropout ratio
_:110 V0>dir.harm.#:Dir.-result 0.00 s to 60.00 s 5.00 s
extension
_:105 V0>dir.harm.#:Dir. 0.00 s to 60.00 s 0.00 s
determination delay
_:6 V0>dir.harm.#:Operate 0.00 s to 60.00 s 1.00 s
delay

6.16.8.4 Information List

No. Information Data Class Type


(Type)
V0>dir.harm.#
_:81 V0>dir.harm.#:>Block stage SPS I
_:501 V0>dir.harm.#:>Block delay & op. SPS I
_:54 V0>dir.harm.#:Inactive SPS O
_:52 V0>dir.harm.#:Behavior ENS O
_:53 V0>dir.harm.#:Health ENS O
_:303 V0>dir.harm.#:Ground fault ACD O
_:55 V0>dir.harm.#:Pickup ACD O
_:56 V0>dir.harm.#:Operate delay expired ACT O
_:57 V0>dir.harm.#:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 677


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

No. Information Data Class Type


(Type)
_:308 V0>dir.harm.#:Phi(I,V) harm. MV O
_:307 V0>dir.harm.#:V0 harm. MV O
_:306 V0>dir.harm.#:3I0 harm. MV O

678 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.9 Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage

6.16.9.1 Description

Logic

[lo_gfps v0, 4, en_US]

Figure 6-151 Logic Diagram of the Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage

Measured Value, Method of Measurement


The device can measure the residual voltage at the broken-delta winding. The measured voltage VN is
converted to a value with reference to the zero-sequence voltage V0. If the residual voltage is not available to
the device as a measurand, the zero-sequence voltage V0 is calculated from the measured phase-to-ground
voltages VA, VB, and VC using the defining equation.

SIPROTEC 5, 7SJ82/7SJ85, Manual 679


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Use the Method of measurement parameter to select the relevant method of measurement, depending on
the application:

• Measurement of the fundamental component (standard filter):


This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.

• Measurement of the RMS value (true RMS):


This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value.

• Measurement of the fundamental component over 2 cycle filters with triangular window:
This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically. The extended filter length compared to the standard filter and the use of the
triangular window results in a particularly strong attenuation of harmonics and transient faults. The
extended filter length causes the pickup time to increase slightly compared to the standard filter (see
12.19.7 Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage).

Pickup, Dropout
The stage compares the Threshold with the zero-sequence voltage V0. The Pickup delay parameter
allows you to delay the pickup of the stage depending on the residual voltage.
With the Dropout ratio parameter, you can define the ratio of the dropout value to the Threshold.

Determination of the Faulty Phase


With the Detection of faulty phase parameter, you can enable or disable the determination of the
ground-fault phase. Determining is released when the stage picks up. If 2 phases exceed the threshold value
V> healthy ph-to-gnd volt. and one phase falls below the threshold value V< faulty ph-to-gnd
volt., the last phase is determined to be faulty and is signaled as such.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. The following blocking options are available for the
stage:

• Via the binary input signal >Block stage from an external or internal source

• From inside on pickup of the measuring-voltage failure detection function. The Blk. by meas.-
volt. failure parameter can be set so that measuring-voltage failure detection blocks the stage or
does not block it.

• From an external source via the binary input signal >open of the function block Voltage-transformer
circuit breaker, which links in the tripping of the voltage-transformer circuit breaker. The Blk. by
meas.-volt. failure parameter can be set so that measuring-voltage failure detection blocks the
stage or not.

6.16.9.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:12391:8) Method of measurement = fundamental comp.


The Method of measurement parameter allows you to define whether the function works with the funda-
mental component or the calculated RMS value.
Parameter Value Description
fundamental comp. This method of measurement suppresses the harmonics or transient voltage
peaks.
Siemens recommends using this setting as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example at capacitor banks).

680 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Parameter Value Description


fund. comp. long filter To implement particularly strong damping of harmonics and transient
faults, select this method of measurement. At 2 periods, the length of the
filter is longer than that of the standard filter.
Note that in this case the pickup time of the stage increases slightly (see
12.19.7 Non-Directional V0 Stage with Zero-Sequence Voltage/Residual
Voltage).

Parameter: Pickup delay

• Recommended setting value (_:12391:107) Pickup delay = 0 ms


The Pickup delay parameter allows you to delay the analysis of the measurand (to generate the pickup)
depending on the occurrence of the residual voltage. A pickup delay can be necessary if high transients are
anticipated after fault inception due to high line and ground capacitances.
Siemens recommends using the default setting Pickup delay = 0 ms.

Parameter: Threshold

• Default setting (_:12391:3) Threshold = 30 V


The threshold value of the function is set as the zero-sequence voltage V0. The device calculates the zero-
sequence voltage V0 either from the residual voltage measured via the broken-delta winding or from the
3 phase-to-ground voltages.
The setting value depends on the system grounding:

• Since virtually the full residual voltage occurs during ground faults in isolated or arc-suppression-coil-
grounded systems, the setting value is uncritical there. Siemens recommends setting the value between
20 V and 40 V. A higher sensitivity (= lower threshold value) can be necessary for high fault resistances.

• Siemens recommends setting a more sensitive (smaller) value in grounded systems. This value must be
higher than the maximum residual voltage anticipated during operation caused by system unbalances.

EXAMPLE
For an isolated system
The residual voltage is measured via the broken-delta winding:

• If the ground fault is fully unbalanced, a residual voltage of 100 V is present at the device terminals.

• The threshold value should be set so that the stage picks up on 50 % of the full residual voltage.

• At full residual voltage, the zero-sequence voltage is 100 V/√3 = 57.7 V


Setting value: 0.5 ⋅ 57.7 V = 28.9 V ≈ 30 V

Parameter: Dropout ratio

• Recommended setting value (_:12391:4) Dropout ratio = 0.95


The recommended setting value of 0.95 is appropriate for most applications. To achieve high measurement
precision, the dropout ratio can be reduced to 0.98, for example.

Parameter: Operate delay

• Default setting (_:12391:6) Operate delay = 3.00 s


The Operate delay allows you to prevent transient residual voltages from initiating a trip. The setting
depends on the specific application.

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:12391:10) Blk. by meas.-volt. failure = yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 681


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


enabled.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is
linked with the voltage-transformer circuit breaker.

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

Parameter: Detection of faulty phase

• Default setting (_:12391:109) Detection of faulty phase = no


The Detection of faulty phase parameter controls how the stage responds to determine which phase
is affected by the ground fault.
Parameter Value Description
no The phase affected by the ground fault is not determined.
Select the default setting if you do not want to use the stage to detect
ground faults, for example for applications in grounded systems.
yes After a pickup by the residual voltage, the device tries to determine which
phase is affected by the ground fault.
Select this setting for applications in isolated or arc-suppression-coil-
grounded systems.

Parameter: V< faulty ph-to-gnd volt.

• Default setting (_:12391:104) V< faulty ph-to-gnd volt. = 30 V


Set the threshold value for determining which phase is affected by the ground fault in the V< faulty ph-
to-gnd volt. parameter. The setting value is a phase-to-ground quantity.
The set value must be smaller than the minimum phase-to-ground voltage occurring during operation.
Siemens recommends using the default setting V< faulty ph-to-gnd volt. = 30 V.

Parameter: V> healthy ph-to-gnd volt.

• Default setting (_:12391:101) V> healthy ph-to-gnd volt. = 70 V


Set the threshold value for the 2 healthy phases in the V> healthy ph-to-gnd volt. parameter. The
setting value is a phase-to-ground measurand.
The set value must be above the maximum phase-to-ground voltage occurring during operation, but below
the minimum phase-to-phase voltage present during operation. At Vrated = 100 V, the value has to be set to 70
V, for example. Siemens recommends using the default setting V> healthy ph-to-gnd volt. = 70 V.

Operation as Supervision Function


If you want the stage to have a reporting effect only, the generation of the operate indication and fault
logging can be disabled via the Operate & flt.rec. blocked parameter.

682 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.9.3 Settings

Addr. Parameter C Setting Options Default Setting


V0> 1
_:12391:1 V0> 1:Mode • off off
• on
• test
_:12391:2 V0> 1:Operate & flt.rec. • no no
blocked
• yes
_:12391:10 V0> 1:Blk. by meas.-volt. • no yes
failure
• yes
_:12391:109 V0> 1:Detection of faulty • no no
phase
• yes
_:12391:8 V0> 1:Method of meas- • fundamental comp. fundamental
urement comp.
• fund. comp. long filter
• RMS value
_:12391:3 V0> 1:Threshold 0.300 V to 200.000 V 30.000 V
_:12391:4 V0> 1:Dropout ratio 0.90 to 0.99 0.95
_:12391:107 V0> 1:Pickup delay 0.00 s to 60.00 s 0.00 s
_:12391:6 V0> 1:Operate delay 0.00 s to 100.00 s 3.00 s
_:12391:101 V0> 1:V> healthy ph-to- 0.300 V to 200.000 V 70.000 V
gnd volt.
_:12391:104 V0> 1:V< faulty ph-to- 0.300 V to 200.000 V 30.000 V
gnd volt.

6.16.9.4 Information List

No. Information Data Class Type


(Type)
V0> 1
_:12391:81 V0> 1:>Block stage SPS I
_:12391:54 V0> 1:Inactive SPS O
_:12391:52 V0> 1:Behavior ENS O
_:12391:53 V0> 1:Health ENS O
_:12391:300 V0> 1:Faulty phase ACT O
_:12391:55 V0> 1:Pickup ACD O
_:12391:56 V0> 1:Operate delay expired ACT O
_:12391:57 V0> 1:Operate ACT O

6.16.10 Non-Directional 3I0 Stage

6.16.10.1 Description
In the Directional sensitive ground-fault detection function, the Non-directional 3I0 stage also works on
demand.

SIPROTEC 5, 7SJ82/7SJ85, Manual 683


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Logic

[lo_sensitive ground-current protection 3I0, 2, en_US]

Figure 6-152 Logic Diagram of the Non-Directional 3I0 Stage

Measured Value 3I0


The function usually evaluates the sensitively measured ground current 3I0 via a core balance current trans-
former. Since the linearity range of the sensitive measuring input ends at approx. 1.6 A, for larger secondary
ground currents, the function switches to the 3I0 current calculated from the phase currents. This results in a
very large linearity and settings range.
Depending on the connection type of the measuring point as well as the current terminal blocks used,
different linearity and setting ranges result. You can find more information in section Measured Value 3I0,
Method of Measurement , Page 636.

Method of Measurement
You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value.

• Measurement of the fundamental component:


This method of measurement processes the sampled current values and filters out the fundamental
component numerically.

684 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

• Measurement of the RMS value:


This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Blocking the Stage via Binary Input Signal


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage will be reset.

Blocking the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate indication. A running time delay is reset. The pickup is indicated and a fault record is opened.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.

6.16.10.2 Application and Setting Notes

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:27) Blk. w. inrush curr. detect. = no


With the Blk. w. inrush curr. detect. parameter, you determine whether the tripping is blocked
during the detection of an inrush current.

Parameter: Method of measurement

• Recommended setting value (_:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Threshold

• Default setting (_:3) Threshold = 0.050 A


The Threshold parameter allows you to set the threshold value of the ground current 3I0.

Parameter: Pickup delay

• Default setting (_:102) Pickup delay = 0.00 s

SIPROTEC 5, 7SJ82/7SJ85, Manual 685


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

With the parameter Pickup delay you set whether pickup of the stage is to be delayed or not. If the tran-
sient cycle of the ground fault occurrence should not be evaluated, set a delay of 100 ms, for example.

Parameter: Operate delay

• Default setting (_:6) Operate delay = 0.30 s


The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.

6.16.10.3 Settings

Addr. Parameter C Setting Options Default Setting


3I0> #
_:1 3I0> #:Mode • off off
• on
• test
_:2 3I0> #:Operate & flt.rec. • no no
blocked
• yes
_:27 3I0> #:Blk. w. inrush • no no
curr. detect.
• yes
_:8 3I0> #:Method of meas- • fundamental comp. fundamental
urement comp.
• RMS value
_:3 3I0> #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:102 3I0> #:Pickup delay 0.00 s to 60.00 s 0.00 s
_:6 3I0> #:Operate delay 0.00 s to 100.00 s 0.30 s

6.16.10.4 Information List

No. Information Data Class Type


(Type)
3I0> #
_:81 3I0> #:>Block stage SPS I
_:500 3I0> #:>Block delay & op. SPS I
_:54 3I0> #:Inactive SPS O
_:52 3I0> #:Behavior ENS O
_:53 3I0> #:Health ENS O
_:60 3I0> #:Inrush blocks operate ACT O
_:55 3I0> #:Pickup ACD O
_:56 3I0> #:Operate delay expired ACT O
_:57 3I0> #:Operate ACT O

686 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.11 Non-Directional Y0 Stage

6.16.11.1 Description
In the Directional sensitive ground-fault detection function, the Non-directional Y0 stage also works on
demand.

Logic

[logfpsy0-240614-01.vsd, 2, en_US]

Figure 6-153 Logic Diagram of the Non-Directional Y0 Stage

Measured Value V0, Method of Measurement


The device can measure the residual voltage at the broken-delta winding. The measured voltage VN is
converted to a value with reference to the zero-sequence voltage V0. If the residual voltage is not available,

SIPROTEC 5, 7SJ82/7SJ85, Manual 687


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

the device calculates the zero-sequence voltage V0 from the measured phase-to-ground voltages VA, VB, and
VC using the defining equation.
The method of measurement processes the sampled voltage values and filters out the fundamental compo-
nent numerically.

Measured Value 3I0, Method of Measurement


The function usually evaluates the sensitively measured ground current 3I0 via a core balance current trans-
former. Since the linearity range of the sensitive measuring input ends at approx. 1.6 A, for larger secondary
ground currents, the function switches to the 3I0 current calculated from the phase currents. This results in a
very large linearity and settings range.
The method of measurement processes the sampled current values and filters out the fundamental compo-
nent numerically.
Depending on the connection type of the measuring point as well as the current terminal blocks used,
different linearity and setting ranges result. You can find more information in section Measured Value 3I0,
Method of Measurement , Page 636.

Y0
The fundamental-component values of V0 and 3I0 are used to calculate the admittance Y0 through the
formula Y0 = 3I0/V0. This stage uses Y0 as a condition to recognize the ground fault.

Minimum 3I0 Threshold


To start the Y0 calculation, the IN/3I0 value must exceed a minimum 3I0 threshold. For protection-class
current transformers, the threshold value is 30 mA (Irated, sec = 1 A) or 150 mA (Irated, sec = 5 A). For sensitive
current transformers, the threshold value is 1 mA (Irated, sec = 1 A) or 5 mA (Irated, sec = 5 A).

Ground-Fault Detection, Pickup


If the absolute value of the zero-sequence voltage V0 exceeds the threshold value V0> threshold value
and Y0 exceeds the threshold value Threshold Y0>, the stage recognizes the ground fault. If the threshold
values remain exceeded during the Pickup delay, the stage picks up.

Blocking the Stage via Binary Input Signal


Blocking of the stage is possible externally or internally via the binary input signal >Block stage. In the
event of blocking, the picked up stage will be reset.

Blocking the Stage in Case of Measuring-Voltage Failure


The stage can be blocked if a measuring-voltage failure occurs. In the event of blocking, the picked up stage
will be reset.
The following blocking options are available for the stage:

• From inside on pick up of the Measuring-voltage failure detection function

• From an external source via the binary input signal >open of the function block Voltage-transformer
circuit breaker, which links in the tripping of the voltage-transformer circuit breaker.
The Blk. by meas.-volt. failure parameter can be set so that measuring-voltage failure detection
blocks the stage or does not block it.

Blocking of the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate indication. A running time delay is reset. The pickup is indicated and a fault record is opened.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

688 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.

6.16.11.2 Application and Setting Notes

Parameter: Operate & flt.rec. blocked

• Default setting (_:2) Operate & flt.rec. blocked = no


You can block the operate indication, the fault recording, and the fault log with the Operate & flt.rec.
blocked parameter. In this case, a ground-fault log is created instead of the fault log.

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected. A measuring-voltage failure can only be detected if 1 of the following 2
conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


switched on.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.

Parameter Value Description


yes The protection stage is blocked (= default setting).
Siemens recommends using the default setting.
no The protection stage is not blocked.

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:27) Blk. w. inrush curr. detect. = no


With the Blk. w. inrush curr. detect. parameter, you determine whether the operate is blocked
during the detection of an inrush current.

Parameter: V0> threshold value

• Default setting (_:101) V0> threshold value = 5.000 V


The V0> threshold value parameter allows you to set the zero-sequence voltage sensitivity of the stage.
The threshold value must be smaller than the minimum amount of the zero-sequence voltage V0 which must
still be detected.

Parameter: Threshold Y0>

• Default setting (_:102) Threshold Y0> = 2.00 mS


With the parameter Threshold Y0>, you set the threshold value of the ground admittance Y0. If the ground
admittance for the setting value is unknown, you can assume the following relation:

[fo_SeGfY0-270614-01, 2, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 689


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

ks Factor, takes into account the ohmic components of the current


(1.2 for overhead lines, 1.0 to 1.05 for cable systems)
Ic,line Secondary capacitive ground-fault current for the protected line
Vph-gnd Secondary phase-to-ground voltage in the healthy case
3I0min Secondary ground current in the healthy case (resulting from transformer error),
5 mA to 10 mA (core balance current transformer), 50 mA to 100 mA (Holmgreen transformer)
V0> Secondary pickup threshold of the residual voltage

Parameter: Pickup delay

• Default setting (_:103) Pickup delay = 0.00 s


With the parameter Pickup delay, you set whether pickup of the stage is to be delayed or not. If the tran-
sient cycle of the ground fault occurrence should not be evaluated, set a delay of 100 ms, for example.

Parameter: Operate delay

• Default setting (_:6) Operate delay = 0.30 s


The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.

6.16.11.3 Settings

Addr. Parameter C Setting Options Default Setting


Y0> #
_:1 Y0> #:Mode • off off
• on
• test
_:2 Y0> #:Operate & flt.rec. • no no
blocked
• yes
_:10 Y0> #:Blk. by meas.-volt. • no yes
failure
• yes
_:27 Y0> #:Blk. w. inrush curr. • no no
detect.
• yes
_:101 Y0> #:V0> threshold 0.300 V to 200.000 V 5.000 V
value
_:102 Y0> #:Threshold Y0> 0.10 mS to 100.00 mS 2.00 mS
_:103 Y0> #:Pickup delay 0.00 s to 60.00 s 0.00 s
_:6 Y0> #:Operate delay 0.00 s to 60.00 s 0.30 s

6.16.11.4 Information List

No. Information Data Class Type


(Type)
Y0> #
_:81 Y0> #:>Block stage SPS I
_:501 Y0> #:>Block delay & op. SPS I
_:54 Y0> #:Inactive SPS O
_:52 Y0> #:Behavior ENS O
_:53 Y0> #:Health ENS O
_:60 Y0> #:Inrush blocks operate ACT O
_:55 Y0> #:Pickup ACD O

690 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

No. Information Data Class Type


(Type)
_:56 Y0> #:Operate delay expired ACT O
_:57 Y0> #:Operate ACT O

6.16.12 Non-Directional 3I0 Harmonic Stage

6.16.12.1 Description
The Non-directional 3I0 harmonic stage detects ground faults via the 3rd, 5th, or 7th harmonic component
of the zero-sequence current 3I0.

Logic

[lo_3I0_harmonic, 1, en_US]

Figure 6-154 Logic Diagram of the Non-Directional 3I0 Harmonic Stage

Measured Value 3I0, Method of Measurement


The function usually evaluates the sensitively measured ground current 3I0 via a core balance current trans-
former. Since the linearity range of the sensitive measuring input ends at approx. 1.6 A, for larger secondary

SIPROTEC 5, 7SJ82/7SJ85, Manual 691


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

ground currents, the function switches to the 3I0 current calculated from the phase currents. This results in a
very large linearity and settings range.
Depending on the connection type of the measuring point and on the current terminal blocks used, different
linearity and setting ranges result. You can find more information in chapter 6.16.4.1 Description.
The function uses the 3rd, 5th, or 7th harmonic component of the ground current 3I0 for detecting the
ground fault. The specific harmonic component to be used is determined by the Harmonic selection
setting.

Stabilization, Pickup
To avoid a wrong pickup in case of transient current peaks, the function uses the Stabilization counter
parameter. If the magnitude of the zero-sequence harmonic current 3I0harm. exceeds the 3I0 harm.
threshold, the stabilization counter starts. If the 3I0harm. current keeps exceeding the 3I0 harm.
threshold for a specified number of measuring cycles, the stage picks up. You can define the specified
number via the Stabilization counter parameter.

Pickup Extension
Considering the discontinuity of the 3I0harm. current, the Pickup signal does not drop out immediately after
the 3I0harm. current falls below the 3I0 harm. threshold.
When the 3I0harm. current falls below the 3I0 harm. threshold, the timer Pickup extension time
starts to hold the Pickup signal until the timer expires. The timer resets after the 3I0harm. current exceeds
the 3I0 harm. threshold again during the extension time.

Blocking the Stage via Binary Input Signal


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage will be reset.

Blocking the Time Delay


You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated. Fault logging and fault recording
take place.

Functional Measured Values

Values Description Primary Secondary % Referenced to


3I0 harm. 3rd, 5th, or 7th harmonic A A Parameter Rated current
component of the ground
current

You can find the parameter Rated current in the FB General of the function group where the Sensitive
ground-fault detection function is used. If the 3I0harm. current is smaller than 0.005 % of the rated secon-
dary current, the functional measured value is displayed as ---.

6.16.12.2 Application and Setting Notes

Parameter: Harmonic selection

• Default setting (_:201) Harmonic selection = 5th harmonic


With the Harmonic selection parameter, you select to use the 3rd, 5th, or 7th harmonic component of
the zero-sequence current 3I0 for detecting the ground fault.

Parameter: 3I0 harm. threshold

• Default setting (_:202) 3I0 harm. threshold = 0.030 A


With the 3I0 harm. threshold parameter, you define the threshold value of the zero-sequence harmonic
current 3I0harm. for detecting the ground fault.

692 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

This parameter needs to be set according to the experience from the specific network. The experience requires
the analysis of permanent ground faults from the network. If such information is unavailable, Siemens recom-
mends a rather low setting between 5 mA and 10 mA secondary.

Parameter: Stabilization counter

• Default setting (_:204) Stabilization counter = 4


With the Stabilization counter parameter, you define the number of measuring cycles in which the
3I0harm. current must keep exceeding the 3I0 harm. threshold to meet the pickup condition. With this
setting, you can optimize the pickup-condition reliability versus the pickup time.
For example, the Stabilization counter value is 4. Then, if the 3I0harm. current exceeds the 3I0
harm. threshold and keeps exceeding the threshold for 4 measuring cycles, the stage picks up. The meas-
uring cycle time is half of the network period. For 50 Hz, the cycle time is 10 ms. To avoid a false pickup due to
CB switching operations, Siemens recommends using the default setting.

Parameter: 3I0 harm. dropout ratio

• Default setting (_:203) 3I0 harm. dropout ratio = 0.60


With the 3I0 harm. dropout ratio parameter, you define the dropout threshold for the 3I0 harm.
threshold parameter. Siemens recommends using the default setting.

Parameter: Pickup extension time

• Default setting (_:110) Pickup extension time = 0.00 s


With the Pickup extension time parameter, you define the time for extending the Pickup signal if the
zero-sequence harmonic current 3I0harm. falls below the 3I0 harm. threshold.
This extension time can be used to generate a stable pickup indication under fluctuating zero-sequence
harmonics.

Parameter: Operate delay

• Default setting (_:6) Operate delay = 1.00 s


With the Operate delay parameter, you determine the time during which the pickup conditions must be
met to issue the operate indication. The operate indication is issued when this time expires.

Parameter: Operate & flt.rec. blocked

• Default setting (_:2) Operate & flt.rec. blocked = no


With the Operate & flt.rec. blocked parameter, you block the operate indication, the fault recording,
and the fault log. In this case, a ground-fault log is created instead of the fault log.

6.16.12.3 Settings

Addr. Parameter C Setting Options Default Setting


3I0> harmonic#
_:1 3I0> harmonic#:Mode • off off
• on
• test
_:2 3I0> harmonic#:Operate • no no
& flt.rec. blocked
• yes
_:201 3I0> • 3rd harmonic 5th harmonic
harmonic#:Harmonic
selection
• 5th harmonic
• 7th harmonic

SIPROTEC 5, 7SJ82/7SJ85, Manual 693


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Addr. Parameter C Setting Options Default Setting


_:202 3I0> harmonic#:3I0 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
harm. threshold 5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.150 A
_:203 3I0> harmonic#:3I0 0.10 to 0.95 0.60
harm. dropout ratio
_:204 3I0> harmonic#:Stabili- 1 to 10 4
zation counter
_:110 3I0> harmonic#:Pickup 0.00 s to 60.00 s 0.00 s
extension time
_:6 3I0> harmonic#:Operate 0.00 s to 60.00 s 1.00 s
delay

6.16.12.4 Information List

No. Information Data Class Type


(Type)
3I0> harmonic#
_:81 3I0> harmonic#:>Block stage SPS I
_:501 3I0> harmonic#:>Block delay & op. SPS I
_:54 3I0> harmonic#:Inactive SPS O
_:52 3I0> harmonic#:Behavior ENS O
_:53 3I0> harmonic#:Health ENS O
_:55 3I0> harmonic#:Pickup ACD O
_:56 3I0> harmonic#:Operate delay expired ACT O
_:57 3I0> harmonic#:Operate ACT O
_:306 3I0> harmonic#:3I0 harm. MV O

6.16.13 Pulse-Pattern Detection Stage

6.16.13.1 Description

Overview
The Pulse-pattern detection stage detects a faulty feeder during a permanent ground fault in overcompen-
sated systems. This method is not reliably applicable to undercompensated systems.
The following figure shows a simplified network that applies the pulse-pattern detection method.
The pulse pattern in the ground current 3I0 is generated by switching on and off a capacitor in parallel to the
arc-suppression coil:

• When the capacitor is switched on, an additional capacitive ground current is generated and the 3I0
compensation changes.

• When the capacitor is switched off, the additional capacitive ground current is vanished and the 3I0
compensation returns to the normal state.

694 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[dw_pulse detection network, 1, en_US]

Figure 6-155 Network that Uses the Pulse-Pattern Detection

Cs Capacitance of the switched capacitor


L Inductance of the arc-suppression coil

Pulse Pattern during a Ground Fault


The following figure shows the 3I0 pulse pattern in an overcompensated system for a low-impedance ground
fault and a high-impedance ground fault.

• For low-impedance ground faults, the 3I0 pulse pattern exists only in the faulty feeder.

• For high-impedance ground faults, the pulse pattern is also present in the healthy feeders with lower
amplitude but in phase opposition to the faulty feeder.
Applying a different switch-on/switch-off duration allows distinguishing between faulty and healthy
feeders in case of high-impedance ground faults.

SIPROTEC 5, 7SJ82/7SJ85, Manual 695


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

[dw_pulse pattern in overcompensation network, 1, en_US]

Figure 6-156 Current Pulse Pattern in the Overcompensated System

For the faulty feeder, the current pulse pattern is as follows:

• When the clocking pulse is on, the capacitor is switched on, the zero-sequence current 3I0 in the faulty
feeder is reduced, and the corresponding current pulse pattern is off.

• When the clocking pulse is off, the capacitor is switched off, 3I0 in the faulty feeder is increased, and the
current pulse pattern is on.

Clocking Pulse Capacitor 3I0 in the Faulty Feeder Current Pulse Pattern of the Faulty Feeder
On On Reduced Off
Off Off Increased On

696 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Logic

[lo_sensGFP pulse detection, 1, en_US]

Figure 6-157 Logic Diagram of the Pulse-Pattern Detection Stage

Measured Value V0, Method of Measurement


The device can measure the residual voltage at the broken-delta winding. The measured voltage VN is
converted to a value with reference to the zero-sequence voltage V0. If the residual voltage is not available to
the device as a measurand, the zero-sequence voltage V0 is calculated from the measured phase-to-ground
voltages VA, VB, and VC using the defining equation.
This method of measurement processes the sampled voltage values and filters out the fundamental compo-
nent numerically.

Measured Value 3I0, Method of Measurement


The function usually evaluates the ground current 3I0 sensitively measured via a core balance current trans-
former. Since the linearity range of the sensitive measuring input ends at approx. 1.6 A, for larger secondary
ground currents, the function switches to the 3I0 calculated from the phase currents. This results in a very
large linearity and settings range.

SIPROTEC 5, 7SJ82/7SJ85, Manual 697


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

The method of measurement processes the sampled current values and filters out the fundamental compo-
nent numerically.
Depending on the connection type of the measuring point as well as the current terminal blocks used,
different linearity and setting ranges result. You can find more information in section Measured Value 3I0,
Method of Measurement , Page 636.

Pulse Detection, Pulse Counter


For this stage, voltage routing is optional and current routing is mandatory.

• If VN or V0 is available, the voltage is the only criterion for starting the pulse-detection logic. When the
fundamental-component value of V0 exceeds the V0> threshold value, the pulse-detection logic is
started.

• If VN or V0 is not available, the current is the only criterion for starting the pulse-detection logic. When
the fundamental-component value of the zero-sequence current 3I0 exceeds the 3I0> threshold
value, the pulse-detection logic is started.
If the measured current pulse-off duration equals to the value of the Pulse-on duration parameter and
the measured current pulse-on duration equals to the value of the Pulse-off duration parameter, a valid
pulse is detected.
After the first valid pulse is detected, the pulse counter is started to count the number of pulses continuously
until the stage resets.

Pickup, Operate
After the first valid pulse is detected, the stage picks up.
If the number of detected pulses within the pulse monitoring time reaches the setting of the No. of
pulses for operate parameter, the stage operates. The pulse monitoring time is calculated via the
following formula:
Pulse monitoring time = Value Monitoring time(in pulses) ⋅ (Value Pulse-on duration + Value
Pulse-off duration)
For example, the value of the No. of pulses for operate parameter is 3, and the value of the Moni-
toring time(in pulses) is 5. Then the pickup and operate time diagram is as follows:

[dw_pulse pickup and operate, 1, en_US]

Figure 6-158 Pickup and Operate Time

• After the 3rd valid pulse is detected, the stage does not operate because the time between the 1st and
the 3rd valid pulses is greater than the pulse monitoring time which is 5 clocking pulses.

• After the 4th valid pulse is detected, the stage operates because the time between the 2nd and the 4th
valid pulses is within the pulse monitoring time which is 5 clocking pulses.

698 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

Dropout Delay
Switching on the capacitor usually causes 3I0 to decrease in the faulty feeder. This must not cause the stage to
drop out. For that reason, a dropout delay is active for the sum of the Pulse-on duration and Pulse-off
duration values.

Detected Pulses of the Ground Fault


The stage records the total number of detected pulses during the permanent ground fault. If the function
resets or the operate condition is met, this number is issued via the signal Detected pulses.

Blocking the Stage via Binary Input Signal


You can block the stage externally or internally via the binary input signal >Block stage. In the event of
blocking, the picked up stage will be reset.

6.16.13.2 Application and Setting Notes

Parameter: V0> threshold value

• Default setting (_:102) V0> threshold value = 30.000 V


The V0> threshold value parameter allows you to set the zero-sequence (fundamental) voltage sensi-
tivity of the stage. Set the threshold value smaller than the minimum absolute value of the zero-sequence
voltage V0 that must still be detected.
If VN or V0 is not available, the V0> threshold value parameter is hidden and the 3I0> threshold
value parameter is visible and used.

Parameter: 3I0> threshold value

• Default setting (_:101) 3I0> threshold value = 0.200 A


If VN or V0 is not available, the 3I0> threshold value parameter is visible and used.
The 3I0> threshold value parameter allows you to set the zero-sequence (fundamental) current sensi-
tivity of the stage. Set the threshold value smaller than the minimum absolute value of the zero-sequence
current 3I0 that must still be detected.

Parameter: Pulse-on duration, Pulse-off duration

• Default setting (_:104) Pulse-on duration = 1.00 s

• Default setting (_:105) Pulse-off duration = 1.50 s


With the Pulse-on duration and Pulse-off duration parameters, you define the switch-on and
switch-off duration of the capacitor.
These values must be set according to the operation of the clocking device that determines the switch-on and
switch-off duration of the capacitor. If you set these 2 parameters to the same or similar values, there is a risk
of failure because the stage cannot distinguish the healthy and faulty feeders by only evaluating the ground
current during a high-impedance ground fault.

Parameter: Max.tolera.pulse-on or off

• Default setting (_:109) Max.tolera.pulse-on or off = 0.15 s


With the Max.tolera.pulse-on or off parameter, you define the tolerance for the measured pulse-on/
pulse-off duration. The tolerance is the maximum deviation from the set values for the Pulse-on duration
and Pulse-off duration parameters.
The recommended setting for this parameter is the maximum tolerance of the clocking device plus 40 ms
(tolerance of the SIPROTEC 5 device). For the tolerance of the clocking device, you have to consider the toler-
ances of the pulse-on and pulse-off durations individually and select the larger tolerance of both.

SIPROTEC 5, 7SJ82/7SJ85, Manual 699


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

EXAMPLE

Clocking device:

Set pulse-on duration for the clocking device 1.00 s


Max. tolerance pulse-on duration of the clocking device 70 ms
Set pulse-off duration for the clocking device 1.50 s
Max. tolerance pulse-off duration of the clocking device 110 ms
Larger tolerance of both 110 ms

Tolerance to be set:

Tolerance of the SIPROTEC 5 device 40 ms


Total tolerance to be set 110 ms + 40 ms = 150 ms

Consequently, you must set the respective device settings as:

• Pulse-on duration = 1.00 s

• Pulse-off duration = 1.50 s

• Max.tolera.pulse-on or off = 0.15 s


The following figure shows the measured pulse durations which are within the maximum stated tolerances of
the example.

[dw_tolerance, 1, en_US]

If you have no information about the tolerance of the clocking device, you can carry out a test recording while
the clocking device is in operation. From the test recording, you can read the inaccuracy of the pulse-on/pulse-
off durations. Add a safety margin of 20 ms on the read inaccuracy and consider this as the maximum toler-
ance of the clocking device. For the setting, add another 40 ms for the tolerance of the SIPROTEC 5 device.

Parameter: 3I0 delta pulse off-on

• Default setting (_:103) 3I0 delta pulse off-on = 10 %


With the 3I0 delta pulse off-on parameter, you define the minimum percentage value of the ground-
current delta between the capacitor switched-on and capacitor switched-off states to detect the pulse pattern.
That is, to detect the pulse pattern, the following condition must be met:

[fo_delta ratio, 1, en_US]

700 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

To prevent minor current fluctuations from leading to a maloperation of the function, the setting of the 3I0
delta pulse off-on parameter cannot be less than 2 %.
The setting of the 3I0 delta pulse off-on parameter can be calculated with the following formula:

[fo_3I0_delta_pulse_off-on, 1, en_US]

Where
Kf Safety factor
Siemens recommends applying the factor 0.6 to also detect high-impedance ground faults.
Cs Capacitance of the switched capacitor
ω Angular frequency, which equals to 2πf, where f is the power frequency
L Inductance of the arc-suppression coil
C0Σ Zero-sequence capacitance of the whole network
C0i Zero-sequence capacitance of the protected feeder

EXAMPLE

Kf 0.6
Cs 1.1 ⋅ 10-6 F
ω 314 rad/s
L 0.577 H
C0Σ 5.4297 ⋅ 10-6 F
C0i 1.5502 ⋅ 10-6 F

Then the setting of the 3I0 delta pulse off-on parameter is calculated as follows:

[fo_delta calculate, 1, en_US]

If the network information for the setting calculation is not available, Siemens recommends using the default
setting of 10 %.

Parameter: No. of pulses for operate, Monitoring time(in pulses)

• Default setting (_:107) No. of pulses for operate = 3

• Default setting (_:108) Monitoring time(in pulses) = 5


With the No. of pulses for operate parameter, you determine the number of pulses to be detected
within the pulse monitoring time, so that the stage operates.
With the Monitoring time(in pulses) parameter, you define the pulse monitoring time, which is calcu-
lated via the following formula:
Pulse monitoring time = Value Monitoring time(in pulses) ⋅ (Value Pulse-on duration + Value
Pulse-off duration)

SIPROTEC 5, 7SJ82/7SJ85, Manual 701


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.16 Sensitive Ground-Fault Detection

6.16.13.3 Settings

Addr. Parameter C Setting Options Default Setting


Pulse detect.#
_:1 Pulse detect.#:Mode • off off
• on
• test
_:2 Pulse detect.#:Operate & • no no
flt.rec. blocked
• yes
_:102 Pulse detect.#:V0> 0.300 V to 200.000 V 30.000 V
threshold value
_:101 Pulse detect.#:3I0> 1 A @ 100 Irated 0.030 A to 35.000 A 0.200 A
threshold value 5 A @ 100 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.000 A
_:103 Pulse detect.#:3I0 delta 2 % to 50 % 10 %
pulse off-on
_:104 Pulse detect.#:Pulse-on 0.20 s to 10.00 s 1.00 s
duration
_:105 Pulse detect.#:Pulse-off 0.20 s to 10.00 s 1.50 s
duration
_:109 Pulse 0.02 s to 2.00 s 0.15 s
detect.#:Max.tolera.puls
e-on or off
_:107 Pulse detect.#:No. of 2 to 100 3
pulses for operate
_:108 Pulse detect.#:Moni- 2 to 100 5
toring time(in pulses)

6.16.13.4 Information List

No. Information Data Class Type


(Type)
Pulse detect.#
_:81 Pulse detect.#:>Block stage SPS I
_:54 Pulse detect.#:Inactive SPS O
_:52 Pulse detect.#:Behavior ENS O
_:53 Pulse detect.#:Health ENS O
_:302 Pulse detect.#:Detected pulses MV O
_:55 Pulse detect.#:Pickup ACD O
_:56 Pulse detect.#:Operate delay expired ACT O
_:57 Pulse detect.#:Operate ACT O

702 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.17 Undercurrent Protection

6.17 Undercurrent Protection

6.17.1 Overview of Functions

The Undercurrent protection function (ANSI 37):

• Detects the going current in a feeder after the opening of the infeed circuit breaker

• Detects the loss of loads

• Detects and protects pumps from running idle

6.17.2 Structure of the Function

The Undercurrent protection function is used in protection function groups with current measurement.
The Undercurrent protection function comes with 1 protection stage preconfigured at the factory. A
maximum of 2 protection stages can be operated simultaneously in this function. The protection stages are
structured identically.

[lostuundcu-150813, 2, en_US]

Figure 6-159 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 703


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.17 Undercurrent Protection

6.17.3 Stage Description

Logic of the Stage

[loundcur-200713-01.tif, 2, en_US]

Figure 6-160 Logic Diagram of the Undercurrent Protection

Method of Measurement
You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.

704 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.17 Undercurrent Protection

• Measurement of the fundamental comp.:


This measurement method processes the sampled current values and numerically filters out the funda-
mental component.

• Measurement of the parameter value RMS value:


This measurement method determines the current amplitude from the sampled values according to the
definition equation of the RMS value. Harmonics are included in the analysis.

Pickup Mode
The Pickup mode parameter defines whether the protection stage picks up if all 3 measuring elements
detect the undercurrent condition (3 out of 3) or if only 1 measuring element has to detect the undercur-
rent condition (1 out of 3).

Blocking the Stage


When blocked, the picked-up protection stage will drop out. Blocking the stage is possible externally or inter-
nally via the binary input signal >Block stage.

Activation and Blocking of the Stage Depending On the Circuit-Breaker Condition


With the parameter Activation, you define if the Undercurrent protection stage is always active or only
active if the circuit breaker is indicating closed.
If the parameter Activation is set to with CB closed and the local circuit breaker is not closed, the func-
tion Undercurrent protection is blocked and no pickup is generated.
The circuit-breaker position is detected as closed if one of the following conditions is met:

• The binary inputs are connected to the auxiliary contacts of the circuit breaker. The circuit-breaker switch
position is detected as closed via the related binary inputs of the Position indication. This is also true
under the condition that no phase current is flowing.

• The current-flow criterion indicates that the circuit breaker is closed. This is also true under the condition
that the auxiliary contacts indicate the circuit breaker as open.

6.17.4 Application and Setting Notes

Parameter: Activation

• Default setting (_:13051:103) Activation = with CB closed

Parameter Value Description


with CB closed The Undercurrent protection is active only when the circuit-breaker posi-
tion is detected as closed.
A precondition is, that the Position indication is routed to binary inputs to
obtain the CB position information via the CB auxiliary contacts. If this is not
the case, the function will always be inactive.
always active The Undercurrent protection stage is always active independent of the
position of the circuit breaker.

Parameter: Method of measurement

• Recommended setting value (_:13051:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 705


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.17 Undercurrent Protection

Parameter Value Description


fundamental comp. Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the threshold value of the
stage to less than 0.1 Irated,sec. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 Irated,sec multiplied by the number of
added currents.

Parameter: Pickup mode

• Default setting (_:13051:102) Pickup mode = 3 out of 3


Use the Pickup mode parameter to define whether the protection stage picks up if all 3 measuring elements
detect the undercurrent condition (3 out of 3) or if only 1 measuring element has to detect the undercur-
rent condition (1 out of 3).

Parameter: Pickup delay

• Default setting (_:13051:104) Pickup delay = 0.00 s


For special applications, it could be desirable that a short falling below the current threshold does not lead to
the pickup of the stage and to the start of fault logging and recording.
With the Pickup delay parameter, you define a time interval during which a pickup is not triggered if the
current falls below the threshold.

Parameter: Threshold

• Default setting (_:13051:3) Threshold = 0.050 A


Specify the Threshold (pickup threshold) for the specific application.

Parameter: Operate delay

• Default setting (_:13051:6) Operate delay = 0.05 s


Operate delay must be set according to the specific application. No general application notes can be given.

6.17.5 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:13051:1 Stage 1:Mode • off off
• on
• test
_:13051:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:13051:103 Stage 1:Activation • always active with CB closed
• with CB closed
_:13051:8 Stage 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value

706 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.17 Undercurrent Protection

Addr. Parameter C Setting Options Default Setting


_:13051:102 Stage 1:Pickup mode • 1 out of 3 3 out of 3
• 3 out of 3
_:13051:3 Stage 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:13051:104 Stage 1:Pickup delay 0.00 s to 60.00 s 0.00 s
_:13051:6 Stage 1:Operate delay 0.00 s to 60.00 s 0.50 s

6.17.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:13051:81 Stage 1:>Block stage SPS I
_:13051:54 Stage 1:Inactive SPS O
_:13051:52 Stage 1:Behavior ENS O
_:13051:53 Stage 1:Health ENS O
_:13051:55 Stage 1:Pickup ACD O
_:13051:56 Stage 1:Operate delay expired ACT O
_:13051:57 Stage 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 707


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

6.18 Negative-Sequence Protection

6.18.1 Overview of Functions

The function Negative-sequence protection (ANSI 46):

• Detects 1-phase or 2-phase short circuits in the electrical power system with clearly increased sensitivity
compared to the classical overcurrent protection

• Protects electric machines during excessive unbalanced load

• Reports unbalanced load conditions in the electricity supply system

• Detects phase interruptions in the primary system

• Locates short circuits or inversions in the connections to the current transformers

6.18.2 Structure of the Function

The Negative-sequence protection function is used in protection function groups with current measure-
ment.
The function is preconfigured by the manufacturer with 2 Definite-time negative-sequence protection
stages.
In the function Negative-sequence protection, the following stages can be operated simultaneously:

• 3 stages Definite-time negative-sequence protection

• 2 stages Inverse-time negative-sequence protection


The stages have an identical structure. Stages that are not preconfigured are shown in gray in the following
figure.

[dwnspstr-271112-01.tif, 3, en_US]

Figure 6-161 Structure/Embedding of the Function

If the device is equipped with the Inrush-current detection function, the stages can be stabilized against
operate due to transformer-inrush currents.

708 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

6.18.3 General Functionality

6.18.3.1 Description

Logic
The following figure represents the logic of the general functionality which applies across all configured
stages. It contains:

• Selection of the reference value

• Current-release criterion

[lo_General Functionality.vsd, 1, en_US]

Figure 6-162 Logic Diagram of the General Functionality

(1) Switchover to I1 with (_:2311:106) Reference value = pos. seq. current

Reference Value
With the parameter Reference value, the negative-sequence current I2 is normalized to the rated object
current Irated, obj or to the positive-sequence current I1. When I2 is normalized to I1, the sensitivity of the func-
tion for low short-circuit currents is increased.

Current Limitation and Maximum Phase Current


With the parameters Current limitation Imax and Maximum phase current, you restrict the oper-
ating range of the function. When the limiting is activated, pickup of the stages is blocked as soon as the
maximum phase-current threshold value is exceeded. For more information, refer to the stage description.

Release Current
The threshold value of the Release current serves to release the negative-sequence protection.

6.18.3.2 Application and Setting Notes

Parameter: Reference value

• Default setting (_:2311:106) Reference value = rated current


With the parameter Reference value, you define the normalization of the negative-sequence current I2 to
the rated object current Irated, obj (I2/Irated, obj) or to the positive-sequence current I1 (I2/I1).

SIPROTEC 5, 7SJ82/7SJ85, Manual 709


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

Parameter Value Description


I2/Irated, obj The negative-sequence current is referred to the rated current of the
protected object. This is a preferred normalization for electrical machines,
because the permissible limiting values are indicated exclusively referred to
the machine rated current. You can also use this normalization for other
applications.
I2/I1 The normalization of the negative-sequence system to the positive-
sequence system yields a higher sensitivity. Use this normalization when
detecting interruptions in the primary system.

Set the parameter depending on the application.

Parameter: Current limitation Imax, Maximum phase current

• Default setting (_:2311:107) Current limitation Imax = no

• Recommended setting value (_:2311:101) Maximum phase current = 10.0 A at 1 A


If the protection function needs a maximum current limitation, set the value of the Current limitation
Imax parameter from no to yes. With the parameter Maximum phase current, you set the upper limit of
the phase current. CT saturation will cause negative-sequence current in the secondary system. To avoid over-
function due to the CT saturation, a suitable phase-current limit value is 10 times of the rated protection-
object current.

Parameter: Release current

• Recommended setting value (_:2311:104) Release current = 0.05 A at 1 A


For the safe calculation of negative-sequence currents, the current in at least one phase must be greater than
5 % of the secondary rated device current. For a 1-A device, the value of Release current is 0.05 A (0.25 A
for a 5-A device).

710 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

6.18.4 Stage with Definite-Time Characteristic Curve

6.18.4.1 Stage Description

Logic of a Stage

[logiknsp-070312-01.tif, 2, en_US]

Figure 6-163 Logic Diagram of the Stage Negative-Sequence Protection with Definite-Time Characteristic
Curve

Method of Measurement
The fundamental phasors are calculated from the 3-phase phase currents. Based on this, the negative-
sequence system and the positive-sequence system are calculated. Following this, the negative-sequence
current is normalized to the reference current. The selection of the reference current is made in the FB
General.

Blocking of the Stage


When blocked, the picked-up protection stage will drop out.
Blocking the stage is possible externally or internally via the binary input signal >Block stage.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are

SIPROTEC 5, 7SJ82/7SJ85, Manual 711


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.

6.18.4.2 Application and Setting Notes

Parameter: Threshold

• Recommended setting value (_:1981:3) Threshold = 10 %


The setting of the parameter Threshold depends on the respective application. A threshold value of 10 % is
a practicable value for fault indications of electrical machines.

Parameter: Operate delay

• Recommended setting value (_:1981:6) Operate delay = 1500 ms


The setting of the Operate delay depends on the application. Observe the time grading in the power-
system protection and do not set the time for monitoring too short. The default setting is practicable. For
motors, the time depends on the permissible time period for the set unbalanced load.

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:1981:104) Blk. w. inrush curr. detect. = no


With the parameter Blk. w. inrush curr. detect., the stage can be stabilized against tripping on
transformer-inrush currents. If transformers are parts of the protection zones, set this parameter to yes.

6.18.4.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:106 General:Reference value • pos. seq. current rated current
• rated current
_:2311:107 General:Current limita- • no no
tion Imax
• yes
_:2311:101 General:Maximum phase 1 A @ 100 Irated 0.030 A to 35.000 A 10.000 A
current 5 A @ 100 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 10.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 50.000 A
_:2311:104 General:Release current 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
Definite-T 1
_:1981:1 Definite-T 1:Mode • off off
• on
• test
_:1981:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:1981:3 Definite-T 1:Threshold 5.0 % to 999.9 % 10.0 %

712 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

Addr. Parameter C Setting Options Default Setting


_:1981:4 Definite-T 1:Dropout 0.40 to 0.99 0.95
ratio
_:1981:104 Definite-T 1:Blk. w. • no no
inrush curr. detect.
• yes
_:1981:101 Definite-T 1:Dropout 0.00 s to 60.00 s 0.00 s
delay
_:1981:6 Definite-T 1:Operate 0.00 s to 60.00 s 1.50 s
delay
Definite-T 2
_:1982:1 Definite-T 2:Mode • off off
• on
• test
_:1982:2 Definite-T 2:Operate & • no no
flt.rec. blocked
• yes
_:1982:3 Definite-T 2:Threshold 5.0 % to 999.9 % 65.0 %
_:1982:4 Definite-T 2:Dropout 0.40 to 0.99 0.95
ratio
_:1982:104 Definite-T 2:Blk. w. • no no
inrush curr. detect.
• yes
_:1982:101 Definite-T 2:Dropout 0.00 s to 60.00 s 0.00 s
delay
_:1982:6 Definite-T 2:Operate 0.00 s to 60.00 s 0.50 s
delay

6.18.4.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:301 General:Overcurrent blocking SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:1981:81 Definite-T 1:>Block stage SPS I
_:1981:52 Definite-T 1:Behavior ENS O
_:1981:53 Definite-T 1:Health ENS O
_:1981:54 Definite-T 1:Inactive SPS O
_:1981:56 Definite-T 1:Operate delay expired ACT O
_:1981:300 Definite-T 1:Inrush blocks operate ACT O
_:1981:55 Definite-T 1:Pickup ACD O
_:1981:57 Definite-T 1:Operate ACT O
Definite-T 2
_:1982:81 Definite-T 2:>Block stage SPS I
_:1982:52 Definite-T 2:Behavior ENS O
_:1982:53 Definite-T 2:Health ENS O
_:1982:54 Definite-T 2:Inactive SPS O
_:1982:56 Definite-T 2:Operate delay expired ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 713


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

No. Information Data Class Type


(Type)
_:1982:300 Definite-T 2:Inrush blocks operate ACT O
_:1982:55 Definite-T 2:Pickup ACD O
_:1982:57 Definite-T 2:Operate ACT O

6.18.5 Stage with Inverse-Time Characteristic Curve

6.18.5.1 Description

Logic of a Stage

[lo_NSP_Inverse, 1, en_US]

Figure 6-164 Logic Diagram of the Negative-Sequence Protection with Inverse-Time Characteristic Curve

Method of Measurement
The fundamental phasors are calculated from the 3-phase phase currents. Based on this, the negative-
sequence system and the positive-sequence system are calculated. Following this, the negative-sequence
current is normalized to the reference current. The selection of the reference current is made in the FB
General.

Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI

714 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.

Blocking of the Stage


When blocked, the picked-up protection stage will drop out.
Blocking the stage is possible externally or internally via the binary input signal >Block stage.

Blocking of the Tripping by Device-Internal Inrush-Current Detection

The Blk. w. inrush curr. detect. parameter allows you to define whether the operate indication of
the stage should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking
and fulfilled pickup conditions, the stage picks up. The start of the time delay and the operate indication are
blocked. The function indicates this through a corresponding indication. If the blocking drops out and the
pickup conditions are still met, the time delay is started. After that time, the stage operates.

6.18.5.2 Application and Settings Notes

Parameter: Type of character. curve

• Default setting (_:105) Type of character. curve = IEC normal inverse


The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the Type
of character. curve required for your specific application. For more information about the parameter
Type of character. curve, refer to chapter 12.21.2 Stage with Inverse-Time Characteristic Curve.

Parameter: Threshold

• Recommended setting value (_:3) Threshold = 10.0 %


The setting of the parameter Threshold depends on the respective application. A threshold value of 10 % is
a practicable value for fault detection for different applications.

Parameter: Time dial

• Recommended setting value (_:107) Time dial = 1.00


With the parameter Time dial, you displace the characteristic curve in the time direction.
The set value for the parameter Time dial is derived from the time-grading schedule that has been prepared
for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the Time
dial parameter at 1.00 (default setting).

Parameter: Reset

• Default setting (_:106) Reset = disk emulation


With the parameter Reset, you define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.

SIPROTEC 5, 7SJ82/7SJ85, Manual 715


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.18 Negative-Sequence Protection

Parameter Value Description


disk emulation Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous Use this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:104) Blk. w. inrush curr. detect. = no


With the parameter Blk. w. inrush curr. detect., the stage can be stabilized against tripping on
transformer-inrush currents. If transformers are parts of the protection zones, set this parameter to yes.

6.18.5.3 Settings

Addr. Parameter C Setting Options Default Setting


Inverse-T #
_:1 Inverse-T #:Mode • off off
• on
• test
_:2 Inverse-T #:Operate & • no no
flt.rec. blocked
• yes
_:3 Inverse-T #:Threshold 5.0 % to 999.9 % 10.0 %
_:104 Inverse-T #:Blk. w. inrush • no no
curr. detect.
• yes
_:105 Inverse-T #:Type of char-
acter. curve
_:106 Inverse-T #:Reset • instantaneous disk emulation
• disk emulation
_:107 Inverse-T #:Time dial 0.05 to 15.00 1.00

6.18.5.4 Information List

No. Information Data Class Type


(Type)
Inverse-T #
_:81 Inverse-T #:>Block stage SPS I
_:52 Inverse-T #:Behavior ENS O
_:53 Inverse-T #:Health ENS O
_:54 Inverse-T #:Inactive SPS O
_:56 Inverse-T #:Operate delay expired ACT O
_:300 Inverse-T #:Inrush blocks operate ACT O
_:59 Inverse-T #:Disk emulation running SPS O
_:55 Inverse-T #:Pickup ACD O
_:57 Inverse-T #:Operate ACT O

716 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

6.19 Directional Negative-Sequence Protection

6.19.1 Overview of Functions

The function Directional negative-sequence protection with current-independent time delay (ANSI 46)
serves as the backup short-circuit protection for unbalanced faults.
With the negative-sequence system, various supervision and protection tasks can be realized, for example:

• Recording of 1 or 2-phase short circuits in the system with a higher sensitivity than in classic overcurrent
protection. The pickup value can be set under the rated object current.

• Recording of phase conductor interruptions in the primary system and in the current-transformer secon-
dary circuits

• Location of short circuits or reversals in the connections to the current transformers

• Indication of unbalanced states in the energy system

• Protection of electrical machines following unbalanced loads that are caused by unbalanced voltages or
conductor interruptions (for example, through a defective fuse)

6.19.2 Structure of the Function

The Directional negative-sequence protection with definite time delay function can be used in protection
function groups with 3-phase current and voltage measurement.
The function comes factory-set with 1 stage. A maximum of 6 tripping stages can be operated simultaneously
in the function.

[dwnspdir-271112-01.tif, 1, en_US]

Figure 6-165 Structure/Embedding of the Function

If the device is equipped with the Inrush-current detection function, the tripping stages can be stabilized
against tripping due to transformer-inrush currents.

6.19.3 Function Description

Stage Control
The following figure shows a stage control. It is available separately for each stage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 717


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

[lostensp-070611-01.tif, 1, en_US]

Figure 6-166 Stage Control of the Directional Negative-Sequence System Protection

In addition to the generally valid stage control, the stage is blocked in the event of a measuring voltage
failure, provided the stage is working directionally.

718 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

Logic of the Stage

[lonspdir-300112-01.tif, 1, en_US]

Figure 6-167 Logic Diagram of the Function Directional Negative-Sequence System Protection with Current-
Independen Time Delay

Measurand
The negative-sequence current I2 is used as a measurand. From the 3-phase currents, the fundamental
phasors are determined via a 1-cycle filter and, corresponding with the definition equation of the symmetrical
components, the negative-sequence system is calculated from this.

SIPROTEC 5, 7SJ82/7SJ85, Manual 719


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

Functioning
The stage picks up if the negative-sequence system current exceeds the set threshold value and the parame-
terized direction agrees with the measured direction. The pickup drops out if the negative-sequence system
current falls below 95 % of the set threshold.

Stabilization with Phase Current


Unbalance in operation and unbalanced transformer ratios can lead to spurious pickups and incorrect tripping.
In order to avoid this, the directional negative-sequence system stage is stabilized with the phase currents.
The threshold value increases with rising phase currents (see next image).
You can change the stabilization factor (= gradient) via the Stabiliz. w. phase current parameter.

[dwstabil-300112-01.tif, 1, en_US]

Figure 6-168 Stabilization with Phase Currents

Direction Determination
The direction determination takes place with the negative-sequence system measurements I2 and V2.
The forward and reverse region is defined through the parameters Angle forward α and Angle forward
β (see next figure). The reference for the 2 angles that must be set is the positive real axis. The angles are
positively defined in a mathematical sense (counter-clockwise). The region between the limit angle α and the
limit angle β - counted from the former in a positive direction - is the forward region. The remaining region is
the reverse region.
For determining of the direction, the function places the measuring current I2 on the real axis. If the phasor of
the negative-sequence system voltage V2 is located within the defined forward region, the function deter-
mines the direction as forward. In the other case, the function determines the direction as reverse.
The requirement for determining the direction is that the adjustable minimum variables have been exceeded
for the negative-sequence system current and negative-sequence system voltage (parameters Min. neg.-
seq. current I2 and Min. neg.-seq. voltage V2).

720 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

[dwphasor-140212-01.tif, 1, en_US]

Figure 6-169 Phasor Diagram for Direction Determination with Negative-Sequence System Values

If the device determines a fault in the voltage-transformer secondary circuit (through the binary input
voltage transformer circuit-breaker dropout or through measuring-voltage failure detec-
tion), direction determination will be disabled and every directionally set stage will be blocked. Non-direction-
ally set stages become active again if there are faults in the voltage-transformer secondary circuit.

[lorichtu-070611-01.tif, 1, en_US]

Figure 6-170 Logic of Direction Determination

Directional Mode
You use the Directional mode parameter to define whether the stage works in a forward or reverse direc-
tion. Non-directional operation is also possible.

SIPROTEC 5, 7SJ82/7SJ85, Manual 721


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

Blocking the Tripping by Pickup of the Main Protection Functions


The pickup and type of pickup for the main protection functions can block the tripping of the stage. You can
perform this setting via 2 parameters:

• Blocking by
This setting is used to select the zone or stage at which blocking is to occur in the event of pickup.

• Blocking by prot. pickup


The pickup type at which the blocking is to occur is defined with this parameter. The blocking can occur
at any pickup or only at 1-pole or only at multipole pickups.
This parameter is also used to set that no blocking should occur when the main protection has picked up.

Blocking of Tripping via the Device-Internal Inrush-Current Detection Function


If the device is equipped with the additional Inrush-current detection function, the stages can be stabilized
against tripping due to transformer inrush currents.
With the Blk. w. inrush curr. detect. parameter, you can define whether tripping of the stage
should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking, the
stage picks up. The start of the time delay and tripping are however blocked. The stage signals this by way of a
corresponding indication. If the blocking drops out and the threshold value of the stage is still exceeded, the
tripping delay (time delay) is started. After that time, the stage operates.

6.19.4 Application and Setting Notes for Direction Determination

Parameter: Limit Angle Region Forward

• Recommended setting value (_:2311:101) Angle forward α = 338°

• Recommended setting value (_:2311:102) Angle forward β = 122°


With the parameters Angle forward α and Angle forward β, you can change the location of the direc-
tional characteristic curve.
Siemens recommends using the defaults, because the function with these settings reliably determines the
direction.

Parameter: Minimum Negative-Sequence System Variables V2 and I2

• Default setting (_:2311:107) Min. neg.-seq. voltage V2 = 0.7 V

• Default setting (_:2311:106) Min. neg.-seq. current I2 = 0.05 A


With the parameters Min. neg.-seq. voltage V2 and Min. neg.-seq. current I2, you can
specify the minimum negative-sequence system values for direction determination with V2 and I2. The set
limiting values must not be exceeded by operational unbalances.

6.19.5 Application and Setting Notes for Stages

Parameter: Directional mode

• Default setting (_:8101:114) Directional mode = forward


You use the Directional mode parameter to define the directional mode of the stage.

722 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

Parameter Value Description


non-directional If the stage is to work in the forward and reverse direction (in the direction of
the line and busbar), then select this setting.
The stage will work with this setting even if no direction measurement is
possible, for example due to insufficient polarization voltage (or none at all), or
due to failure of the measuring voltage.
forward Select these settings if the stage is only to work in a forward direction (in direc-
tion of the line).
reverse Select this setting if the level is only to work in the reverse direction (in the
direction of the busbar).

Parameter: Blk. w. inrush curr. detect.


If the device is equipped with the additional Inrush-current detection function, the stages can be stabilized
against tripping due to transformer inrush currents.

• Default setting (_:8101:116) Blk. w. inrush curr. detect. = no

Parameter Value Description


no The transformer inrush current detection does not affect the stage.
Select this setting in the following cases:
1) In cases where the device is not used on transformers.
2) In cases where the device is used on transformers and the threshold value of
the stage is set above the maximum inrush current of the transformer.
yes When the transformer inrush current detection detects an inrush current that
can lead to a tripping of the stage, the start of the time delay and tripping of
the stage are blocked.
Select this setting if the device is used on transformers and the threshold value
of the stage is set below the maximum inrush current of the transformer.

Parameter: Blocking by the main Protection

• Recommended setting value (_:8101:140) Blocking by =


If you wish to give selective fault clarification through the main protection function precedence over tripping
through the directional negative-sequence protection, you can define this via the 2 parameters Blocking by
and Blocking by prot. pickup. The Blocking by parameter is used to select the zones or tripping
stages of the main protection function(s), upon whose pickup the negative-sequence protection is to be
blocked.

Parameter: Blocking by prot. pickup

• Default setting (_:8101:130) Blocking by prot. pickup = every pickup


The Blocking by prot. pickup parameter can be used to define the type of pickup, which leads to the
blocking.
Parameter Value Description
every pickup Blocking at every pickup
1-phase pickup Blocking only at 1-pole pickup
multi-phase pickup Blocking only at multipole pickup
no pickup If the pickup of the main protection function should not lead to blocking of the
negative-sequence protection, select this setting.

Parameter: Hold mode 1-p dead time

• Default setting (_:8101:112) Hold mode 1p dead time = 0.040 s

SIPROTEC 5, 7SJ82/7SJ85, Manual 723


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

The Hold mode 1p dead time setting is used to define the time by which the device-internal signal for the
1-pole interruption is extended after the end of the 1-pole interruption.
At all line ends, there is no simultaneous switch-in after a 1-pole dead time. Thus, the parameterized operating
mode for a 1-pole dead time must be retained for a certain time after the switch-in (end of the 1-pole dead
time) until the other end or ends have securely switched in. The time to be set here corresponds to the
maximum time between the switch-in of the 1st circuit breaker and the switch-in of the last circuit breaker at
all ends of the feeder after a 1-pole dead time.

NOTE

i The Hold mode 1p dead time setting is only available in devices with 1-/3-pole tripping. In devices
with 3-pole tripping, this setting does not apply.

Parameter: Stabiliz. w. phase current

• Recommended setting value (_:8101:111) Stabiliz. w. phase current = 10 %


In order to avoid unwanted pickups and tripping, the negative-sequence system current stage is stabilized
with the phase currents.
More information can be found in chapter 6.19.3 Function Description.
The threshold value increases as the phase currents increase.
You can change the stabilization factor (= gradient) via the Stabiliz. w. phase current parameter.
Siemens recommends a default setting of 10 % under normal operations.

Parameter: Threshold

• Default setting (_:8101:3) Threshold = 1.5 A


Define the pickup value corresponding to the application. In doing so, for the time-graded stages, the setting
for the superordinate and subordinate stages must be taken into account in the grading chart.
With a very sensitive setting, you must make sure that the negative-sequence system current does not lead to
undesired response of the stage due to unbalance (for example non-twisted line).

Parameter: Operate delay

• Default setting (_:8101:6) Operate delay = 0.30 s


The tripping delay (time delay) to be set is derived from the time-grading schedule that has been prepared for
the system.
When selecting the current and time setting, pay attention to whether the stage must work dependent on the
direction.

6.19.6 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Angle forward α 0 ° to 360 ° 338 °
_:2311:102 General:Angle forward β 0 ° to 360 ° 122 °
_:2311:107 General:Min. neg.-seq. 0.150 V to 34.000 V 1.213 V
voltage V2
_:2311:106 General:Min. neg.-seq. 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
current I2 5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A

724 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

Addr. Parameter C Setting Options Default Setting


Definite-T 1
_:8101:1 Definite-T 1:Mode • off off
• on
• test
_:8101:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:8101:114 Definite-T 1:Directional • non-directional forward
mode
• forward
• reverse
_:8101:111 Definite-T 1:Stabiliz. w. 0 % to 30 % 10 %
phase current
_:8101:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8101:6 Definite-T 1:Operate 0.00 s to 60.00 s 0.30 s
delay
_:8101:116 Definite-T 1:Blk. w. • no no
inrush curr. detect.
• yes
_:8101:130 Definite-T 1:Blocking by • every pickup every pickup
prot. pickup
• 1-phase pickup
• multi-phase pickup
• no pickup
_:8101:129 Definite-T 1:Op.mode at • blocked blocked
1p dead time
• non-directional
_:8101:112 Definite-T 1:Hold mode 0.000 s to 60.000 s 0.040 s
1p dead time
_:8101:140 Definite-T 1:Blocking by Setting options depend on
configuration

6.19.7 Information List

No. Information Data Class Type


(Type)
General
_:2311:500 General:>Test of direction SPS I
_:2311:300 General:Test direction ACD O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:8101:81 Definite-T 1:>Block stage SPS I
_:8101:54 Definite-T 1:Inactive SPS O
_:8101:52 Definite-T 1:Behavior ENS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 725


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.19 Directional Negative-Sequence Protection

No. Information Data Class Type


(Type)
_:8101:53 Definite-T 1:Health ENS O
_:8101:60 Definite-T 1:Inrush blocks operate ACT O
_:8101:302 Definite-T 1:Prot.PU blocks operate SPS O
_:8101:301 Definite-T 1:Mode1p dead-tm.active SPS O
_:8101:55 Definite-T 1:Pickup ACD O
_:8101:56 Definite-T 1:Operate delay expired ACT O
_:8101:57 Definite-T 1:Operate ACT O

726 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

6.20 Thermal Overload Protection, 3-Phase - Advanced

6.20.1 Overview of Functions

The Thermal overload protection, 3-phase – advanced function (ANSI 49) is used to:

• Protect the equipment (motors, generators, transformers, capacitors, overhead lines, and cables) against
thermal overloads

• Monitor the thermal state of motors, generators, transformers, capacitors, overhead lines, and cables

6.20.2 Structure of the Function

The Thermal overload protection, 3-phase – advanced function is used in protection function groups with
current measurement.
The function is preconfigured by the manufacturer with 1 Thermal overload protection, 3-phase –
advanced stage.
The non-preconfigured function block Filter can optionally be applied to gain the RMS value used by the
Thermal overload protection, 3-phase – advanced stage.

[dw_TOLP_with Filter stage, 2, en_US]

Figure 6-171 Structure/Embedding of the Function

6.20.3 Filter for RMS Value Gain

6.20.3.1 Description
The function block Filter can be used to adapt the RMS value for 2 means:

• To gain harmonics in a defined way. Higher harmonics can stress the protected object thermally more
than lower harmonics. This is the case for reactors applied in AC filters. In addition, the amplitude attenu-
ation of higher frequencies due to the anti-aliasing filter of the device is automatically compensated by
the filter

• To only compensate the amplitude attenuation of higher frequencies by the device (due to the anti-
aliasing filter)
The filter gain (amplitude response) is realized by a 9-order FIR filter.

SIPROTEC 5, 7SJ82/7SJ85, Manual 727


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

Logic

[lo_TOLP_FilterStage, 1, en_US]

Figure 6-172 Logic Diagram of the Function Block Filter

The FIR filter gains the 8-kHz sampled values according to the set filter coefficients. Afterwards the RMS value
is calculated. The symmetrical 9-order filter coefficients are set via the respective parameters h(0), h(1),
h(2), h(3) and h(4).

NOTE

i A FIR-filter configuration tool is provided as an auxiliary PC tool. With this PC tool, the coefficients h(0),
h(1), h(2), h(3), h(4) of the FIR filter are generated according to the required gain factors (amplitude
response). The tool can be obtained from the SIPROTEC download area. For more information about the
tool, refer to the tool help function.

The gained RMS value is delivered to the protection stages only when the function block Filter is instantiated
and the parameter Enable filter is set as yes . Otherwise, the normal RMS value is used.

Functional Measured Values

Values Description Primary Secon- % Referenced to


dary
Iph:A Filtered RMS measured kA A Parameter Rated current
value of current A
Iph:B Filtered RMS measured kA A Parameter Rated current
value of current B
Iph:C Filtered RMS measured kA A Parameter Rated current
value of current C

You can find the parameter Rated current in the FB General of function groups where the Thermal over-
load protection, 3-phase - advanced function is used.
If the parameter Enable filter is set to no, the function values are shown as ---.

6.20.3.2 Application and Setting Notes

Parameter: Enable filter

• Default setting (_:1) Enable filter = no.

728 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

With the parameter Enable filter, you set whether the Filter is enabled.
Parameter Value Description
yes If gained RMS values should be used in one of the protection stages, set
parameter Enable filter = yes.
no If no gained RMS values are needed, set the parameter Enable filter =
no.

Parameter: h(0), h(1), h(2), h(3), h(4)

• Default setting (_:2) h(0) = 0.000

• Default setting (_:3) h(1) = 0.000

• Default setting (_:4) h(2) = 0.000

• Default setting (_:5) h(3) = 0.000

• Default setting (_:6) h(4) = 1.000


With the default value of the coefficients, the filter has no effect and no gain is applied.
If the filter shall be applied to adapt the RMS value calculation to a specific protection object such as a reactor,
the reactor manufacturer has to provide the required amplitude response (gain factors) for the reactor. To
determine the coefficients h(0) to h(4) for the FIR filter, you must enter the gain factors into the auxiliary PC
tool which is available in the SIPROTEC download area. The 5 required coefficients are generated by the tool.
They have to be entered manually as settings to configure the filter. The amplitude attenuation of higher
frequencies due to the anti aliasing filter of the device is automatically taken into account and compensated
by the filter.
To only compensate the attenuation of higher frequencies by the device, set the following coefficients in the
filter.
Rated Frequency Filter Coefficients for Only Compensating the Device Amplitude Attenu-
ation
50 Hz h(0) = -0.002
h(1) = -0.012
h(2) = 0.045
h(3) = -0.110
h(4) = 1.151
60 Hz h(0) = -0.005
h(1) = -0.020
h(2) = 0.058
h(3) = -0.128
h(4) = 1.170

6.20.3.3 Settings

Addr. Parameter C Setting Options Default Setting


Filter
_:1 Filter:Enable filter • no no
• yes
_:2 Filter:h(0) -100.000 to 100.000 0.000
_:3 Filter:h(1) -100.000 to 100.000 0.000
_:4 Filter:h(2) -100.000 to 100.000 0.000
_:5 Filter:h(3) -100.000 to 100.000 0.000
_:6 Filter:h(4) -100.000 to 100.000 1.000

SIPROTEC 5, 7SJ82/7SJ85, Manual 729


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

6.20.3.4 Information List

No. Information Data Class Type


(Type)
Filter
_:301 Filter:Iph:A MV O
_:302 Filter:Iph:B MV O
_:303 Filter:Iph:C MV O

6.20.4 Stage with Thermal Overload Protection, 3-Phase - Advanced

6.20.4.1 Description

Logic

[lo_TOLP_withFilterstage, 2, en_US]

Figure 6-173 Logic Diagram of the Thermal Overload Protection, 3-Phase - Advanced Stage

730 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

[lo_Stage Control, 1, en_US]

Figure 6-174 Logic Diagram of the Stage Control

RMS-Value Selection
The protection function supports 2 kinds of RMS measurement:

• Normal RMS value

• Gained RMS value from the function block Filter


The gained RMS value is automatically used if the function block Filter is configured and the filter has been
enabled.

NOTE

i When the function block Filter is applied, only one current measuring point I-3ph is allowed to be
connected to the 3-phase current interface of the function group.

Thermal Replica
The protection function calculates the overtemperature from the phase currents based on a thermal single-
body model according to the thermal differential equation with

[fo_diffgl-170914, 2, en_US]

With the following standardization:

[fo_normie-170914, 3, en_US]

Θ Current overtemperature, in relation to the final temperature at a maximum permissible


phase current k Irated, obj
ΘAmb Standardized ambient temperature, where ϑAmbdescribes the coupled ambient temperature.
The coupled ambient temperature ϑAmb can be the measured ambient temperature or the
ambient temperature preset using the Default temperature parameter.
Δ ϑrated obj Overtemperature of the protected object set at rated current
τ th Thermal time constant (temperature rise/cooling) of the protected object

SIPROTEC 5, 7SJ82/7SJ85, Manual 731


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

k This factor indicates the maximum continuous permissible phase current. The factor refers
to the rated current of the protected object (k = Imax/Irated, obj)
Irated, obj Rated current of the protected object

At the same time, Irated, obj is the rated current of the assigned protected object side:

• In the case of transformers, the rated current of the winding to be protected, which the device calculates
from the set rated apparent power and rated voltage, is decisive.

• The uncontrolled winding forms the basis in the case of transformers with voltage control

• In the case of generators, motors and reactors, the rated current, which the device calculates from the
set rated apparent power and rated voltage, is decisive.

• In the case of lines, nodes and busbars, the rated current of the protected object is set directly
In a steady state, the solution to the thermal differential equation is an e-function whose asymptote repre-
sents the final overtemperature Θend. The time constant τth determines the rise. After reaching an initial adjust-
able overtemperature threshold Θwarn ( Threshold thermal warn. ), a warning indication is given.
If the overtemperature limit ΘOff (tripping overtemperature) is exceeded, an operate indication is immediately
issued and the equipment disconnected from the power supply. This threshold is specified at 100 % and corre-
sponds to the final temperature set at a flowing permissible continuous current (Imax).
Figure 6-175 shows the temperature rise at different overload currents and the supervision thresholds.

[dwtempve-030211-01.tif, 1, en_US]

Figure 6-175 Temperature History for Different Overload Currents ( K-factor = 1.1)

The overtemperature is calculated separately for each phase. The current overtemperature can be obtained
from the operational measured values. It is shown in percent. An indication of 100 % means that the thermal
threshold has been reached. The maximum overtemperature of the phases is regarded as the tripping temper-
ature. This means that the highest of the 3 phase currents is always assumed.
The analysis of the RMS values of the currents over a broad frequency band also includes the harmonic
components. These harmonic components contribute to the temperature rise of the equipment.
If the flowing current falls below an adjustable minimum current Imin cooling , the Cooling time
constant is activated.

732 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

Operate Curve
If the ambient temperature is not measured and set to 40°C, you can get the operate curve as following:

[foauslos-211010-01.tif, 1, en_US]

t Operate time
τth Time constant
I Measured load current
Ipreload Preload current
k Setting factor according to VDE 0435 part 3011 or IEC 60255-149 (K factor)
Irated, obj Rated current of the protected object

Ambient Temperature
This function can take the ambient temperature into consideration. The reference temperature of the thermal
model is 40°C. If the ambient temperature drops below the reference temperature, the thermal limit increases.
The equipment can be stressed more. If the ambient temperature is higher, the conditions change.
The Default temperature parameter can be used to fix or measure the ambient temperature. The
Minimal temperature parameter limits the coupled ambient temperature. If the measured ambient
temperature is lower than the minimum temperature, the minimum temperature is processed in the thermal
model.
The ambient temperature refers to the overtemperature of the protected object, which sets itself at the rated
current (parameter Temperature rise at Irated ).
The measured ambient temperature is measured by an external RTD unit (RTD = Resistance Temperature
Detector) or by an IO111 module and provided by the functions RTD unit Ether., RTD unit serial, or Tempera-
ture module IO111 of the function group Analog unit. When using the Temperature sensor parameter,
the respective temperature sensor can be selected.
If the temperature measurement is faulty, for example, due to an open circuit between the device and the RTD
unit, the health state of the Thermal overload protection, 3-phase – advanced function changes to
Warning. In this case, the process continues with either the temperature measured last or the value set under
the Default temperature parameter, depending on which value is the highest.

Current Influence
The thermal replica based on the single-body model applies with limitations to high overcurrent situations
(short circuits, motor startup currents). To avoid an overfunction of the overload protection, the thermal
replica must be influenced for overcurrents (exceeding l threshold). You can select between 2 strategies for this:

• Freezing of the thermal memory

• Limitation of the input current for the thermal replica to the set current. The temperature rise is thereby
retarded at high currents.

Warning Thresholds
The thermal warning threshold issues a warning indication before the tripping threshold (tripping tempera-
ture) is reached. In this way, for example, a load can be reduced in sufficient time and a disconnection
avoided. At a normal K-factor of 1.1, a thermal memory value of 83 % sets in at continuously flowing
rated current.

SIPROTEC 5, 7SJ82/7SJ85, Manual 733


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

Apart from the thermal warning threshold, the overload protection also has a current-warning threshold. This
current-warning threshold can signal an overload current in sufficient time before the overtemperature value
has reached the warning or tripping threshold.

Dropout of Tripping
Once the thermal memory has fallen below the setting value of the Dropout threshold operate , the
trip command is canceled upon tripping. In contrast, the current-warning threshold and the thermal warning
threshold are reduced at a fixed dropout threshold (see Technical Data).

Behavior in the Event of Auxiliary-Voltage Failure


The behavior of the thermal replica can be controlled upon auxiliary-voltage failure via the setting parameter
Storage of thermal replica . You can save the thermal state for a time of 500 min. Once the supply
voltage returns, the thermal replica continues to function with the saved thermal state.
If the thermal replica is not saved, it will be reset to 0 upon failure of the auxiliary voltage.

Resetting the Thermal Map


You can reset the thermal memory via the binary input indication >Reset thermal replica . The thermal
memory will then have a 0 value. A reparameterization will also lead to resetting the thermal memory.

Emergency Start
Depending on the operating conditions, tripping can be blocked or closure enabled despite the permissible
thermal limits being exceeded. Upon activation of the binary input signal >Emergency start , tripping is
blocked and closure enabled. This does not affect the state of the thermal memory. After the input >Emer-
gency start disappears, the blocking remains in effect for the set Emerg. start T overtravel .

Blocking the Function


Blocking will cause a picked up function to be reset. The tripping function can be blocked externally or inter-
nally by the binary input signal >Block stage .
All indications then drop out and the thermal memory is set to the value 0.

Blocking Closure
The signal Block close can be used to prevent closure of the protected object at a high thermal load. The
signal is set if the tripping overtemperature is exceeded, and canceled if the temperature falls below the
dropout threshold.

Functional Measured Values

Values Description Primary Secondary % Referenced to


(_:601:305) Time until trip Expected time until tripping s s s
(_:601:304) Time until close Time until close release s s s
(_:601:306) Overload phase A Thermal measured values of % % Tripping temperature
(_:601:307) Overload phase B the phases
(_:601:308) Overload phase C
(_:601:309) Overload Thermal measured value of the % % Tripping temperature
maximum overload protection
(_:601:310) Equival. current Current measured value which A A Rated operating current of
phs A serves as basis for the overload the primary values
(_:601:311) Equival. current measured value
phs B
(_:601:312) Equival. current
phs C

734 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

Values Description Primary Secondary % Referenced to


(_:601:313) Equival. current Maximum current measured A A Rated operating current of
max. value which serves as basis for the primary values
the overload measured value

6.20.4.2 Application and Setting Notes

Parameter: Threshold current warning

• Default setting (_:101) Threshold current warning = 1.000 A at Irated = 1 A

Set the threshold to the maximum permissible continuous current (Imax, perm). This results in the same setting
value as for the K-factor .

Parameter: Threshold thermal warn.

• Default setting (_:104) Threshold thermal warn. = 90 %


The default setting can be left at a K-factor , of 1.1, as the thermal memory results for 83 % at continu-
ously flowing rated current. The calculation uses the rule of three: 100 % corresponds to ( K-factor )2 and
x % corresponds to 12.

[fowarnsc-100810-01.tif, 2, en_US]

At a K-factor of 1.05, the thermal memory for rated current is already 91 % filled. Increase the Threshold
thermal warn. to 95 %.

Parameter: Dropout threshold operate

• Default setting (_:105) Dropout threshold operate = 90 %


The Dropout threshold operate parameter is used to drop out pickup and tripping when the value
drops below this threshold. A setting on the order of magnitude of the warning threshold is recommended.
You can select a lower setting value for special applications, desired additional cooling or longer blocking of
closing.
Note that the calculation of the operational measured value Time until close refers to this value.

Parameter: Emerg. start T overtravel

• Default setting (_:112) Emerg. start T overtravel = 300 s


This functionality is not required for protection of lines and cables. If the logical binary indication is not routed,
the Emerg. start T overtravel will be ineffective. The Emerg. start T overtravel presetting
can therefore be retained.

Parameter: K-factor

• Default setting (_:106) K-factor = 1.10


The K-factor parameter is used to describe the limiting value for the maximum permissible continuous load.
The rated current Irated, obj of the protected object (for example, cable) is the basic current for overload sensing.
You can determine the K-factor on the basis of the thermally permissible continuous current Imax, perm.:

[fotolpkf-100810-01.tif, 2, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 735


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

NOTE

i The thermally permissible continuous current for the protected object is known from relevant tables or
from the specifications of the manufacturer!

In the case of cables, the permissible continuous current depends on the cross-section, insulation material,
design type, and the manner in which the cables have been laid. In the case of overhead lines, an overload of
10 % is permissible.

EXAMPLE
For the Permissible Continuous Current
Cross-linked polyethylene cables (N2XS2Y): 10 kV 150 mm2 (Cu)
Current-carrying capacity (underground laying): Imax, perm = 406 A
Selected K factor of 1.1
This yields a rated current of Irated, obj= 369 A

Parameter: Thermal time constant

• Default setting (_:110) Thermal time constant = 900 s


The Thermal time constant parameter is used to define the tripping characteristics of the stage. If no
data on the Thermal time constant is available, you can determine this from the short-time current-
rating capacity of the cable, for example, from the 1-s current. The 1-s current is the maximum current permis-
sible for 1 s application time. The 1-s current can be found in the cable specifications. Calculate the Thermal
time constant according to the following formula:

[fo_perm_1.0-s-continuous-current, 1, en_US]

If the short-term current-rating capacity is specified for an application time other than 1 s, use the short-time
current instead of the 1-s current. Multiply the result by the specified application time.
For a given short-term current-carrying capacity of 0.5 s, use the following formula:

[fo_perm_0.5-s-continuous-current, 1, en_US]

EXAMPLE for a Cable


For a cable
Permissible continuous current: Imax, perm = 406 A
Maximum short-circuit current for 1 s: I1s = 21.4 kA
Therefore, for the Thermal time constant, it follows

[fokonsta-310510-01.tif, 2, en_US]

with 46.29 min = 2777 s

Parameter: Cooling time constant

• Default setting (_:111) Cooling time constant = 3600 s

736 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

The Cooling time constant parameter is used to define the dropout behavior of the stage. Cables and
overhead lines have the same time constant for both heating and cooling. Therefore, set the same value for
the Cooling time constant as for the parameter Thermal time constant.

Parameter: Imax thermal

• Default setting (_:107) Imax thermal = 2.5 A at Irated = 1 A

The Imax thermal parameter allows you to set the threshold current for the Behav. at I> Imax
therm. parameter. The selected threshold current of 2.5 Irated, obj is a practicable value.

Parameter: Imin cooling

• Default setting (_:108) Imin cooling = 0.500 A


If only the thermal time constant (parameter Thermal time constant ) must provide protection, set the
current parameter Imin cooling to 0 A.

Parameter: Temperature rise at Irated

• Default setting (_:109) Temperature rise at Irated = 70 K


As a value, set the overtemperature that is the result if the equipment is continuously operated with the rated
current and at an ambient temperature of 40°C. Here, the rated current refers to the protected object. You can
find the temperature value in the technical data of the equipment or measure it. If you use a temperature
sensor when measuring at the rated current, deduct the actual ambient temperature or the coolant tempera-
ture from the measured value.
When selecting the setting value, you can also use the specified temperature class for orientation. Usually, you
will find the overtemperature expressed in Kelvin (K), which can be accepted as is. If the absolute temperature
is given, the ambient temperature must be deducted. As a rule, this is 40°C.
The overtemperature at maximum permissible current (ϑmax) and the Temperature rise at Irated
(ϑrated,obj.) can be converted by using the following formula:

[fo_ueb_for_Irated, 3, en_US]

EXAMPLE:
Temperature class B for continuous operation: permissible overtemperature = 80 K
From this, a temperature for Irated of 120°C (80 K + 40°C) can be derived when using a temperature sensor for
the measurement.
Temperature class F as thermal limiting value: permissible overtemperature = 105 K.
From this, a maximum temperature of 155°C (105 K + 40°C) derives.
From these values, the K factor can be derived:

[fo_bsp_kfaktor, 3, en_US]

If you select a setting value of 1.1 for the K-factor, your selection can be considered as conservative.

NOTE

i For electrical machines, the limits can vary depending on the type of coolant.
Consult the machine manufacturer to agree on a setting value for the overtemperature.

SIPROTEC 5, 7SJ82/7SJ85, Manual 737


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

Parameter: Storage of thermal replica

• Default setting (_:113) Storage of thermal replica = no


If a continuous auxiliary voltage for the bay units is ensured, the bay default setting can be retained.

Parameter: Behav. at I> Imax therm.

• Default setting (_:114) Behav. at I> Imax therm. = current limiting


The Behav. at I> Imax therm. parameter is used to select the process by which the function reacts to
short-circuit currents. To prevent premature tripping of the overload protection at low time constants, high
preloading and high short-circuit currents, the thermal replica can be modified.
Parameter Value Description
freeze therm. rep. If input currents exceed the Imax thermal parameter, the thermal
replica will be frozen for the time the parameter is exceeded. This param-
eter value is provided to enable compatibility with older products!
current limiting The input currents are limited to the value set in the Imax thermal
parameter. If the measured current exceeds the set current value, the
limited current value is supplied to the thermal replica. An advisable current
threshold is approx. 2 to 2.5 Irated, obj.

Parameter: Temperature sensor

• Default setting (_:44) Temperature sensor = none


With the Temperature sensor parameter, you determine which temperature sensor to use to detect the
ambient temperature.
A temperature sensor is used to measure the ambient temperature of the protected object and to feed it to
the device via an RTD unit (RTD = Resistance Temperature Detector) or via an IO111 module. The Thermal
overload protection, 3-phase - advanced function receives the measured temperature value via the func-
tions RTD unit Ether., RTD unit Serial, or Temperature module IO111 from the function group Analog
units.

Parameter: Default temperature

• Default setting (_:118) Default temperature = 40°C


The Default temperature is set as ambient temperature under the following conditions:

• No temperature sensor for measuring the ambient temperature is connected.

• The temperature measurement is faulty and the last measured temperature value is less than the
Default temperature.
Siemens recommends using the default setting.

Parameter: Minimal temperature

• Default setting (_:117) Minimal temperature = -20°C


If the measured ambient temperature drops below the set value, the set value is assumed as the ambient
temperature. If the overload protection works with a prespecified outside temperature, and this temperature
drops below the value set in the Minimal temperature parameter, the Minimal temperature is also
used.

738 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

6.20.4.3 Settings

Addr. Parameter C Setting Options Default Setting


49 Th.overl. #
_:1 49 Th.overl. #:Mode • off off
• on
• test
_:2 49 Th.overl. #:Operate & • no no
flt.rec. blocked
• yes
_:101 49 Th.overl. #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
current warning 5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:104 49 Th.overl. #:Threshold 50 % to 100 % 90 %
thermal warn.
_:105 49 Th.overl. #:Dropout 50 % to 99 % 90 %
threshold operate
_:112 49 Th.overl. #:Emerg. 0 s to 15000 s 300 s
start T overtravel
_:106 49 Th.overl. #:K-factor 0.10 to 4.00 1.10
_:110 49 Th.overl. #:Thermal 10 s to 60000 s 900 s
time constant
_:111 49 Th.overl. #:Cooling 10 s to 60000 s 3600 s
time constant
_:107 49 Th.overl. #:Imax 1 A @ 100 Irated 0.030 A to 10.000 A 2.500 A
thermal 5 A @ 100 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 50 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 12.500 A
_:108 49 Th.overl. #:Imin 1 A @ 100 Irated 0.000 A to 10.000 A 0.500 A
cooling 5 A @ 100 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 50 Irated 0.000 A to 10.000 A 0.500 A
5 A @ 50 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 2.500 A
_:109 49 Th.overl. #:Tempera- 40 K to 200 K 70 K
ture rise at Irated
_:113 49 Th.overl. #:Storage of • no no
thermal replica
• yes
_:114 49 Th.overl. #:Behav. at • current limiting current limiting
I> Imax therm.
• freeze therm. rep.
_:118 49 Th.overl. #:Default -55°C to 55°C 40°C
temperature
_:117 49 Th.overl. #:Minimal -55°C to 40°C -20°C
temperature
_:44 49 Th.overl. #:Tempera- Setting options depend on
ture sensor configuration

SIPROTEC 5, 7SJ82/7SJ85, Manual 739


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.20 Thermal Overload Protection, 3-Phase - Advanced

6.20.4.4 Information List

No. Information Data Class Type


(Type)
49 Th.overl. #
_:500 49 Th.overl. #:>Block stage SPS I
_:501 49 Th.overl. #:>Reset thermal replica SPS I
_:502 49 Th.overl. #:>Emergency start SPS I
_:54 49 Th.overl. #:Inactive SPS O
_:52 49 Th.overl. #:Behavior ENS O
_:53 49 Th.overl. #:Health ENS O
_:301 49 Th.overl. #:Current warning SPS O
_:302 49 Th.overl. #:Thermal warning SPS O
_:303 49 Th.overl. #:Block close SPS O
_:55 49 Th.overl. #:Pickup ACD O
_:300 49 Th.overl. #:Operate alarm only ACT O
_:57 49 Th.overl. #:Operate ACT O
_:304 49 Th.overl. #:Time until close MV O
_:305 49 Th.overl. #:Time until trip MV O
_:306 49 Th.overl. #:Overload phase A MV O
_:307 49 Th.overl. #:Overload phase B MV O
_:308 49 Th.overl. #:Overload phase C MV O
_:309 49 Th.overl. #:Overload maximum MV O
_:310 49 Th.overl. #:Equival. current phs A MV O
_:311 49 Th.overl. #:Equival. current phs B MV O
_:312 49 Th.overl. #:Equival. current phs C MV O
_:313 49 Th.overl. #:Equival. current max. MV O

740 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

6.21 Thermal Overload Protection, User-Defined Characteristic Curve

6.21.1 Overview of Functions

The Thermal overload protection, user-defined characteristic curve function (ANSI 49) is used to:

• Protect the equipment (motors, generators, and transformers) against thermal overloads

• Realize a manufacturer specific overload characteristic curve for specific equipment, for example, shunt
reactors

• Monitor the thermal state of motors, generators, and transformers

6.21.2 Structure of the Function

The Thermal overload protection, user-defined characteristic curve function is used in protection function
groups with 3-phase current measurement.
The Thermal overload protection, user-defined characteristic curve function is steplessly preconfigured.

[dw_TOLP_UserCurveStr, 1, en_US]

Figure 6-176 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 741


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

6.21.3 Function Description

Logic

[lo_TOLP_UserCurve_stage, 1, en_US]

Figure 6-177 Logic Diagram of the Thermal Overload Protection, User-Defined Characteristic Curve Function

(1) The (_:101) Rated current parameter is from the protected object.
(2) The (_:104) Rated primary current parameter is from the used current transformer.

User-Defined Characteristic Curve


For specific equipment (for example, shunt reactors and transformers) or for special applications, the manu-
facturer specifies an overload characteristic curve. This curve cannot be described accurately with a single-

742 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

body model so that deviations can occur. The following figure shows an example of a predefined overload
characteristic curve and 2 standard characteristic curves based on the single-body model.

[dw_TOLP_UserCurve_characteristic, 1, en_US]

Figure 6-178 User-Defined Characteristic Curve with Replica of Standard Characteristics

The calculation is identical to the realization of the standard Thermal overload protection, 3-phase -
advanced function. You can find more information in the function description Thermal overload protection,
3-phase - advanced starting from chapter 6.20.1 Overview of Functions.
The main deviations are as follows:

• The thermal characteristic is set with a flexible characteristic (ttrip = f(I/Irated,obj)).

– The first point of the characteristic curve is important and is used to calculate the internal k-Factor.
– The point at I/Irated,obj = 1.5 is used to calculate the internal thermal time constant. If there is no point
at I/Irated,obj = 1.5, the point which is the closest to I/Irated,obj = 1.5 from I/Irated,obj = 1.1 is used to calcu-
late the internal thermal time.
– The points are set according to the maximum permissible load current.

• The Curve based on preload parameter describes for which thermal preload the user-defined char-
acteristic curve is valid. Normally, such a curve is given for protected objects under rated load.

• The Cool-down factor Tau parameter is used for the determination of the cooling time constant.
The set factor is multiplied with the internal calculated time constant.

• The thermal model is based on a constant ambient temperature of 40 °C. It cannot be corrected via the
external measurement.

SIPROTEC 5, 7SJ82/7SJ85, Manual 743


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

Thermal Replica
The protection function calculates the overtemperature from the phase currents on the basis of a thermal
single-body model according to the thermal differential equation with

[fo_TOLP_diffgl, 1, en_US]

With the following standardization:

[fo_TOLP_normie, 1, en_US]

Θ Current overtemperature, in relation to the final temperature at a maximum permis-


sible phase current k Irated, obj
Δ ϑrated obj Overtemperature of the protected object set at rated current
τ th Thermal time constant (temperature rise/cooling) of the protected object. The value is
calculated internally.
K This factor indicates the maximum continuous permissible phase current. The factor
refers to the rated current of the protected object (K = Imax/Irated, obj) and is calculated
internally.
Irated, obj Rated current of the protected object

[dw_TOLP_Temperature, 1, en_US]

Figure 6-179 Temperature History for Different Overload Currents ( K-factor = 1.1)

The overtemperature is calculated separately for each phase. The current overtemperature can be obtained
from the operational measured values. It is shown in percent. An indication of 100 % means that the thermal
threshold has been reached. The maximum overtemperature of the phases is regarded as the tripping temper-
ature. This means that the highest of the 3 phase currents is always assumed.

744 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

The analysis of the RMS values of the currents over a broad frequency band also includes the harmonic
components. These harmonic components contribute to the temperature rise of the equipment.

Current Influence
The thermal replica based on the single-body model applies only with limitations to high overcurrent situa-
tions (short circuits, motor startup currents). To avoid an overfunction of the overload protection, the thermal
replica must be influenced in case of overcurrents (exceeding Ithreshold). You can select between 2 strategies for
this:

• Freezing of the thermal memory

• Limitation of the input current for the thermal replica to the set current. The temperature rise is thereby
retarded at high currents.

Warning Thresholds
The thermal warning threshold issues a warning indication before the tripping threshold (tripping tempera-
ture) is reached. In this way, for example, a load can be reduced in sufficient time and a disconnection can be
avoided. If the first setting value of the user-defined characteristic curve is set to 1.1 of the rated current, a
thermal memory value of 83 % is set to the continuously flowing rated current.
Apart from the thermal warning threshold, the overload protection also has a current-warning threshold. This
current-warning threshold can signal an overload current in sufficient time before the overtemperature value
has reached the warning or tripping threshold.

Dropout of Tripping
Once the thermal memory has fallen below the setting value of the Dropout threshold operate, the trip
command is cancelled upon tripping. In contrast, the current-warning threshold and the thermal warning
threshold are reduced at a fixed dropout threshold (see Technical Data).

Behavior in the Event of Auxiliary-Voltage Failure


The behavior of the thermal replica can be controlled upon auxiliary-voltage failure via the setting parameter
Storage of thermal replica. You can save the thermal state for a time of 500 min. Once the supply
voltage returns, the thermal replica continues to function with the saved thermal state.
If the thermal replica is not saved, it will be reset to 0 upon failure of the auxiliary voltage.

Resetting the Thermal Memory


You can reset the thermal memory via the binary input indication >Reset thermal replica. The thermal
memory will then have a 0 value.

Emergency Start
Depending on the operating conditions, tripping can be blocked or closure enabled despite the permissible
thermal limits being exceeded. Upon activation of the binary input signal >Emergency start, tripping is
blocked and closure enabled. This does not affect the state of the thermal memory. After the input >Emer-
gency start disappears, the blocking remains in effect for the set Emerg. start T overtravel.

Blocking the Function


Blocking will cause a picked up function to be reset. The tripping function can be blocked externally or inter-
nally by the binary input signal >Block stage.
All indications then drop out and the thermal memory is not calculated.

Blocking Closure
The signal Block close can be used to prevent closure of the protected object at a high thermal load. The
signal is set if the tripping overtemperature is exceeded, and cancelled if the temperature falls below the
dropout threshold.

SIPROTEC 5, 7SJ82/7SJ85, Manual 745


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

Functional Measured Values

Values Description Primary Secondary % Referenced to


(_:601:305) Time until trip Expected time until tripping s s s
(_:601:304) Time until close Time until close release s s s
(_:601:306) Overload phase A Thermal measured values of % % Tripping temperature
(_:601:307) Overload phase B the phases
(_:601:308) Overload phase C
(_:601:309) Overload maximum Thermal measured value of the % % Tripping temperature
overload protection
(_:601:310) Equival. current phs Current measured value which A A Rated operating current
A serves as basis for the overload of the primary values
(_:601:311) Equival. current phs B measured value
(_:601:312) Equival. current phs C
(_:601:313) Equival. current max. Maximum current measured A A Rated operating current
value which serves as basis for of the primary values
the overload measured value

6.21.4 Application and Setting Notes

Motors and generators as well as transformers are at risk from long-lasting overloads. You can adapt the given
overload characteristic curve to the user-defined characteristic curve with the Thermal overload protection,
user-defined characteristic curve function. You can find the predefined characteristic curve in the chapter
12.24 Thermal Overload Protection, User-Defined Characteristic Curve.
When setting the parameters, consider the following:

• The settings for the used current transformer (primary values and secondary values) must be set correctly
in the power system.

• The rated values for the protected object must be correct in the used function group.

Parameter: Threshold current warning

• Recommended setting value (_:101) Threshold current warning = 1.1 A at Irated = 1 A

Set the threshold to the maximum permissible continuous current (Imax, perm). This results in the same setting
value as for the first value of the user-defined characteristic curve.

Parameter: Threshold thermal warn.

• Recommended setting value (_:104) Threshold thermal warn.= 90 %


If the first value of the user-defined characteristic curve is 1.1 of the rated current, the default setting can be
left. The thermal memory results for 83 % at continuously flowing rated object current.
If the first value of the user-defined characteristic curve is 1.05 of the rated object current, the thermal
memory for rated current is already 91 % filled. Increase the Threshold thermal warn. to 95 %.

Parameter: Dropout threshold operate

• Recommended setting value (_:105) Dropout threshold operate= 90 %


The Dropout threshold operate parameter is used to drop out pickup and tripping when the value
drops below this threshold. A setting on the order of magnitude of the warning threshold is recommended.
You can select a lower setting value for special applications, desired additional cooling or longer blocking of
closing.
Note that the calculation of the operational measured value Time until close refers to this value.

746 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

Parameter: Emerg. start T overtravel

• Default setting (_:112) Emerg. start T overtravel = 300 s


The Emerg. start T overtravel parameter is used to set the time for which blocking of the tripping has
to remain active after an outgoing binary input signal >Emergency start. With an outgoing input signal,
the load on the protected object is removed. The emergency start T-overtravel must be set long enough to
allow the thermal memory to fall below the dropout threshold after cooling. Select a time on the order of
magnitude of the Cooling time constant. In the example, 5 min (300 s) have been assumed.

Parameter: Imax thermal

• Recommended setting value (_:107) Imax thermal = 2.5 A at Irated = 1 A

The Imax thermal parameter allows you to set the threshold current for the Behav. at I> Imax
therm. parameter. If you calculate with relatively long start times for motors (longer than 25 s), the current
limiting must be reduced to 2 I/Irated, obj.

Parameter: Imin cooling

• Recommended setting value (_:108) Imin cooling = 0.5 A at Irated = 1 A

When defining the minimum current Imin cooling, you can use the no-load current for orientation. If no
data is available, set 0.5 I/Irated, obj. If the current falls below this value, the internal thermal time constant τ
automatically switches to the internal cooling time constant with the Cool-down factor Tau parameter.

Parameter: Storage of thermal replica

• Recommended setting value (_:113) Storage of thermal replica = no


If a continuous auxiliary voltage for the bay units is ensured, the default setting can be retained.

Parameter: Behav. at I> Imax therm.

• Recommended setting value (_:114) Behav. at I> Imax therm. = current limiting
The Behav. at I> Imax therm. parameter is used to select the process by which the function reacts to
short-circuit currents. To prevent premature tripping of the overload protection at low time constants, high
preloading and high short-circuit currents, the thermal replica can be modified. As overcurrent due to a
starting of the motor also leads to a certain heating of the stator winding, limiting the input current is recom-
mended for machines.
Parameter Value Description
current limiting The input currents are limited to the value set in the Imax thermal
parameter. If the measured current exceeds the set current value, the
limited current value is supplied to the thermal replica. An advisable current
threshold is approx. 2 to 2.5 Irated, obj.
freeze therm. rep. If input currents exceed the Imax thermal parameter, the thermal replica
will be frozen for the time the parameter is exceeded.

Parameter: Curve based on preload

• Default value (_:101) Curve based on preload = 100 %


The Curve based on preload parameter is used for a certain load case. In most cases, it applies for an
operation under rated conditions. For that, it is assumed that rated current is flowing permanently. This is
referred to as warm condition. In this case, the default setting 100 % is applied.
Thus, the thermal behavior is also correct for different preloads.
For cases without preload or cold condition, set the parameter to 0 %.

SIPROTEC 5, 7SJ82/7SJ85, Manual 747


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

Parameter: Cool-down factor Tau

• Default value (_:108) Cool-down factor Tau = 7.0


If the current becomes lower than the setting value of the Imin cooling parameter, you can set the Cool-
down factor Tau parameter to calculate the internal cooling time constant.

Parameter: Operate char. curve

• Default value Operate char. curve = 1.1 p.u., 600.00 s


With the Operate char. curve parameter, you define the characteristic curve in a tabular form with
ordered normalized current values and associated normalized time values.
When setting the parameter, consider the following:

• Set the current value as per-unit value with the rated current of the protected object as reference.

• Set the time value in seconds.

• Enter the values in continuous order.

EXAMPLE
With the following 12 points, you can get a user-defined characteristic curve as shown in the following figure.

Table 6-13 User-Defined Points

I / Iobj t (s)
1.16 120.00
1.21 96.00
1.25 76.00
1.28 62.00
1.35 48.00
1.42 37.50
1.48 33.50
1.58 27.50
1.84 20.50
2.09 14.00
2.25 9.85
8.00 9.85

748 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

[dw_TOLP_Predefined curve, 1, en_US]

Figure 6-180 Example of the User-Defined Characteristic Curve

6.21.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 User charact.#:Mode • off off
• on
• test
_:2 User charact.#:Operate • no no
& flt.rec. blocked
• yes
_:102 User charact.#:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
current warning 5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:104 User charact.#:Threshold 50 % to 100 % 90 %
thermal warn.
_:105 User charact.#:Dropout 50 % to 99 % 90 %
threshold operate
_:106 User charact.#:Emerg. 0 s to 15000 s 300 s
start T overtravel

SIPROTEC 5, 7SJ82/7SJ85, Manual 749


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

Addr. Parameter C Setting Options Default Setting


_:107 User charact.#:Imin 1 A @ 100 Irated 0.000 A to 10.000 A 0.500 A
cooling 5 A @ 100 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 50 Irated 0.000 A to 10.000 A 0.500 A
5 A @ 50 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 2.500 A
_:108 User charact.#:Cool- 0.5 to 20.0 7.0
down factor Tau
_:109 User charact.#:Storage • no no
of thermal replica
• yes
_:110 User charact.#:Imax 1 A @ 100 Irated 0.030 A to 10.000 A 2.500 A
thermal 5 A @ 100 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 50 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 12.500 A
_:111 User charact.#:Behav. at • current limiting current limiting
I> Imax therm.
• freeze therm. rep.
_:112 User charact.#:Operate Setting options depend on 1.1 p.u., 600 s
char. curve configuration
_:101 User charact.#:Curve 0 % to 100 % 100 %
based on preload

6.21.6 Information List

No. Information Data Class Type


(Type)
User charact.#
_:81 User charact.#:>Block stage SPS I
_:500 User charact.#:>Reset thermal replica SPS I
_:501 User charact.#:>Emergency start SPS I
_:54 User charact.#:Inactive SPS O
_:52 User charact.#:Behavior ENS O
_:53 User charact.#:Health ENS O
_:300 User charact.#:Current warning SPS O
_:301 User charact.#:Thermal warning SPS O
_:302 User charact.#:Block close SPS O
_:55 User charact.#:Pickup ACD O
_:303 User charact.#:Operate alarm only ACT O
_:57 User charact.#:Operate ACT O
_:304 User charact.#:Time until close MV O
_:305 User charact.#:Time until trip MV O
_:306 User charact.#:Overload phase A MV O
_:307 User charact.#:Overload phase B MV O
_:308 User charact.#:Overload phase C MV O
_:309 User charact.#:Overload maximum MV O
_:310 User charact.#:Equival. current phs A MV O

750 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.21 Thermal Overload Protection, User-Defined Characteristic Curve

No. Information Data Class Type


(Type)
_:311 User charact.#:Equival. current phs B MV O
_:312 User charact.#:Equival. current phs C MV O
_:313 User charact.#:Equival. current max. MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 751


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

6.22 Thermal Overload Protection, 1-Phase

6.22.1 Overview of Functions

The Thermal overload protection 1-phase function (ANSI 49) is used to:

• Protect the equipment (reactors or resistors in the neutral point of a transformer) from thermal overload

6.22.2 Structure of the Function

The Thermal overload protection 1-phase function is used in 1-phase protection function groups with
current measurement.
The Thermal overload protection, 1-phase function is steplessly preconfigured.

[dwtolp1p-270613-01.tif, 2, en_US]

Figure 6-181 Structure/Embedding of the Function

752 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

6.22.3 Function Description

Logic

[lotolp1p-250713-01.tif, 2, en_US]

Figure 6-182 Logic Diagram of the Thermal Overload Protection Function

Thermal Replica
The protection function calculates the overtemperature from the current flowing in the protected object (for
example, reactor or resistance in the transformer neutral point) on the basis of a thermal single-body model
according to the thermal differential equation with

[fodiffgl-310510-01.tif, 2, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 753


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

With the following standardization:

[fonormie-310510-01.tif, 2, en_US]

Θ Current overtemperature, in relation to the final temperature at a maximum permissible


current k Irated,obj
ΘV Standardized ambient temperature, where ϑAmb describes the coupled ambient tempera-
ture. The coupled ambient temperature ϑAmb can be the measured ambient temperature or
the ambient temperature preset using the Default temperature parameter.
Δ ϑrated,obj Overtemperature of the protected object set at rated current
τth Thermal time constant (temperature rise/cooling) of the protected object
k This factor indicates the maximum continuous permissible phase current. The factor refers
to the rated current of the protected object (k = Imax/Irated,obj)
Irated,obj Rated current of the protected object

At the same time, Irated,obj is the rated current of the protected object.
In a steady state, the solution to the thermal differential equation is an e-function whose asymptote repre-
sents the final overtemperature Θend. The time constant τth determines the rise. After reaching an initial adjust-
able overtemperature threshold Θwarn (Threshold thermal warn.), a warning indication is given.
If the overtemperature limit ΘOff (tripping overtemperature) is exceeded, an operate indication is immediately
issued and the equipment disconnected from the power supply. This threshold is specified at 100 % and corre-
sponds to the final temperature set at a flowing permissible continuous current (Imax).
Figure 6-183 shows the temperature rise at different overload currents and the supervision thresholds.

[dwtempve-030211-01.tif, 1, en_US]

Figure 6-183 Temperature History for Different Overload Currents (K-factor = 1.1)

754 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

The current overtemperature can be obtained from the operational measured values. It is shown in percent.
An indication of 100 % means that the thermal threshold has been reached.
The analysis of the RMS value of the current over a broad frequency band also includes the harmonic compo-
nents. These harmonic components contribute to the temperature rise of the equipment.

Operate Curve
If the ambient temperature is not measured and set to 40°C, you get the following operate curve:

[foauslos-211010-01.tif, 1, en_US]

t Operate time
τth Time constant
I Measured load current
Ipreload Preload current
k Setting factor according to VDE 0435 part 3011 or IEC 60255-149 (K factor)
Irated,obj Rated current of the protected object

Ambient Temperature
This function can take the ambient temperature into consideration The reference temperature of the thermal
model is 40 °C. If the ambient temperature drops below the reference temperature, the thermal limit
increases. The equipment can be stressed more. If the ambient temperature is higher, the conditions change.
The Default temperature parameter can be used to fix or measure the ambient temperature. The
Minimal temperature parameter limits the coupled ambient temperature. If the measured ambient
temperature is lower than the minimum temperature, the minimum temperature is processed in the thermal
model.
The ambient temperature refers to the overtemperature of the protected object, which sets itself at the rated
current (parameter Temperature rise at Irated).
The measured ambient temperature is recorded by an external RTD unit (RTD = Resistance Temperature
Detector) or by an IO111 module and provided by the functions RTD unit Ether., RTD unit serial, or Tempera-
ture module IO111 of the function group Analog units. When using the Temperature sensor parameter,
the respective temperature sensor can be selected.
If the temperature measurement is disrupted, for example, due to an open circuit between the device and the
RTD unit, the health state of the Thermal overload protection, 1-phase function changes to Warning. In this
case, the process continues with either the temperature measured last or the value set under the Default
temperature parameter, whichever value is the highest.

Current Influence
The thermal replica based on the single-body model applies with limitations to high overcurrent situations
(short circuits). To avoid an overfunction of the overload protection, the thermal replica must be influenced
for overcurrents (exceeding llimit). You can select between 2 strategies for this:

• Freezing of the thermal memory

• Limitation of the input current for the thermal replica to the set current. The temperature rise is thereby
retarded at high currents.

SIPROTEC 5, 7SJ82/7SJ85, Manual 755


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

Warning Thresholds
The thermal warning threshold issues a warning indication before the tripping threshold (tripping tempera-
ture) is reached. In this way, for example, a load can be reduced in sufficient time and a disconnection
avoided. At a normal K-factor of 1.1, a thermal memory value of 83 % sets in at continuously flowing rated
current.
Apart from the thermal warning threshold, the overload protection also has a current-warning threshold. This
current-warning threshold can signal an overload current in sufficient time before the overtemperature value
has reached the warning or tripping threshold.

Dropout of Tripping
Once the thermal memory has fallen below the setting value of the Dropout threshold operate, the trip
command is cancelled upon tripping. In contrast, the current-warning threshold and the thermal warning
threshold are reduced at a fixed dropout threshold (see technical data).

Behavior in the Event of Auxiliary-Voltage Failure


The behavior of the thermal replica can be controlled upon auxiliary-voltage failure via the Storage of
thermal replica parameter. You can save the thermal state for a down time of 500 min. If the supply
voltage returns, the thermal replica continues to function with the saved thermal state.
If the thermal replica is not saved, it will be reset to 0 upon failure of the auxiliary voltage.

Resetting the Thermal Map


You can reset the thermal memory via the binary input indication >Reset thermal replica. The thermal
memory will then have a 0 value. A reparameterization will also lead to resetting the thermal memory.

Blocking the Function


Blocking will cause a picked up function to be reset. The function can be blocked externally or internally by the
binary input signal >Block stage.
All indications then drop out and the thermal memory is set to the value 0.

Blocking Closure
The signal Block close can be used to prevent closure of the protected object at a high thermal load. The
signal is set if the tripping overtemperature is exceeded, and cancelled if the temperature falls below the
dropout threshold.

Functional Measured Values

Measured Value Description


(_:310) Equival. Besides the thermal measured values in percent, the equivalent current is
current also issued as a thermal current-measured value (A or kA). The current
equivalent is the primary current, which corresponds to the thermal meas-
ured value in percent, assuming steady-state conditions.
(_:304) Time until The Time until close is the expected time until it is possible for the
close protected object for reclosure. The calculation of this value is based on the
assumption of constant currents. The thermal replica has then fallen below
the setting value of the dropout threshold.
(_:305) Time until trip The Time until trip is the expected time until tripping (100 % value
exceeded) occurs. The calculation of this value is based on the assumption
of constant currents.
(_:306) Overload The value Overload indicates the current temperature of the protected
object in percent. Tripping occurs if 100 % is exceeded.

756 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

6.22.4 Application and Setting Notes

Parameter: Threshold current warning

• Recommended setting value (_:101) Threshold current warning = 1.1 A for lrated = 1 A

Set the threshold to the maximum permissible continuous current (Imax, perm). This results in the same setting
value as for K-factor.

Parameter: Threshold thermal warn.

• Recommended setting value (_:104) Threshold thermal warn. = 90 %


The default setting can be left at a K-factor of 1.1, because the thermal memory sets itself to 83 % at
continuously flowing rated current. The calculation uses the rule of three: 100 % corresponds to (K-factor)2
and x % corresponds to 12.

[fowarnsc-100810-01.tif, 2, en_US]

At a K-factor of 1.05, the thermal memory for rated current is 91% filled. Increase the Threshold
thermal warn. to 95%.

Parameter: Dropout threshold operate

• Recommended setting value (_:105) Dropout threshold operate = 90 %


The Dropout threshold operate parameter is used to cancel pickup and tripping when the value drops
below this threshold. A setting on the order of magnitude of the warning threshold is recommended. You can
select a lower setting value for special applications, desired additional cooling, or longer blocking of switching
on.
The calculation of the operational measured value Time until close refers to this value.

Parameter: K-factor

• Recommended setting value (_:106) K-factor = 1.1


The K-factor parameter is used to describe the limiting value for the maximum permissible continuous load.
The rated current Irated, obj of the protected object (for example, resistance) is the basic current for overload
sensing.
You can determine K-factor on the basis of the thermally permissible continuous current Imax, perm.:

[fotolpkf-100810-01.tif, 2, en_US]

NOTE

i The thermally permissible continuous current for the protected object is known from relevant tables or
from the specifications of the manufacturer!

Siemens recommends using the default value as it is a typical value for many applications.

Parameter: Thermal time constant

• Default value (_:110) Thermal time constant = 900 s (15 min)


The Thermal time constant parameter is used to define the operate curve of the stage. If no time
constant is given, you can derive it from other values.

SIPROTEC 5, 7SJ82/7SJ85, Manual 757


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

EXAMPLE

Protection of a current-limiting resistance


Rated current of the resistance: Irated = 100 A
Values for the overload capability:

• 1.1 Irated permanent (k-Factor = 1.1; k = 1.1)

• 1.5 Irated for 20 s for charge by cold

The following time constant results from these assumed values:

[fo_time_constance_11082015, 1, en_US]

For Thermal time constant, set 26 s.


The following time-dependent characteristic results from the data. In case of a current increase to 1.5 I rated,
the tripping occurs in 20 s.

[dwtime-dependent-110815-01.vsd, 1, en_US]

Parameter: Imax thermal

• Recommended setting value (_:107) Imax thermal= 2.5 A for lrated = 1 A

758 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

The Imax thermal parameter allows you to set the threshold current for the Behav. at I> Imax
therm. parameter. The selected current threshold of 2.5 Irated, obj is a practicable value.

Parameter: Temperature rise at Irated

• Default setting (_:109) Temperature rise at Irated = 70 K

NOTE

i For an application as a 1-phase overload protection, the ambient temperature measured via the tempera-
ture sensor is not taken into account. Therefore, the setting has no influence. You can keep the default
setting. If you take into account the temperature, note the following descriptions.

Set the overtemperature as the value that is the result if the equipment is continuously operated with the
rated current and at an ambient temperature of 40°C. Here, the rated current refers to the protected object.
You can find the temperature value in the Technical data of the equipment or you can measure the value. If
you use a temperature sensor when measuring at the rated current, deduct the actual ambient temperature or
the coolant temperature from the measured value.
When selecting the setting value, you can also use the specified temperature class for orientation. Usually, you
will find the overtemperature expressed in Kelvin (K), which can be accepted as is. If the absolute temperature
is given, the ambient temperature must be deducted. As a rule, this is 40 °C.
The overtemperature at maximum permissible current (ϑmax) and the Temperature rise at Irated
(ϑrated,obj.) can be converted by using the following formula:

[fo_ueb_for_Irated, 3, en_US]

EXAMPLE:
Temperature class B for continuous operation: permissible overtemperature = 80 K
From this, a temperature for Irated of 120 °C (80 K + 40 °C) can be derived when using a measuring element for
the measurement.
Temperature class F as thermal limiting value: permissible overtemperature = 105 K.
From this, a maximum temperature of 155 °C (105 K + 40 °C) derives.
From these values, the magnitude of the K factor can also be derived.

[fo_bsp_kfaktor, 3, en_US]

If selecting a setting value of 1.1 for the K-factor, your selection can be considered as conservative.

Parameter: Storage of thermal replica

• Recommended setting value (_:113) Storage of thermal replica = no


If a continuous auxiliary voltage of the bay units is ensured, the default setting can be retained.

Parameter: Behav. at I> Imax therm.

• Recommended setting value (_:114) Behav. at I> Imax therm. = current limiting
The Behav. at I> Imax therm. parameter is used to select the process by which the function reacts to
short-circuit currents. To prevent premature tripping of the overload protection at low time constants, high
preloading and high short-circuit currents, the thermal replica can be modified.
The default setting has been selected compatible with SIPROTEC 4 devices. If you wish to take further temper-
ature rise into consideration, the current limiting procedure is recommended.

SIPROTEC 5, 7SJ82/7SJ85, Manual 759


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

Parameter Value Description


current limiting The input current is limited to the value set in the Imax thermal parameter. If
the measured current exceeds the set current value, the limited current value is
supplied to the thermal replica. An advisable current threshold is approx. 2 to
2.5 Irated, obj.
freeze therm. rep. If the input current exceeds the Imax thermal parameter, the thermal replica
will be frozen for the time the parameter is exceeded. This parameter value is
provided to enable compatibility with older products!

Parameter: Temperature sensor

• Default setting (_:44) Temperature sensor = none


Use the Temperature sensor parameter to determine which temperature sensor to use to detect the
ambient temperature.
A temperature sensor is used to measure the ambient temperature of the protected object and to feed it to
the device via an RTD unit (RTD = Resistance Temperature Detector) or via an IO111 module. The function
Thermal overload protection receives the measured temperature value via the function RTD unit Ether., RTD
unit Serial, or Temperature module IO111 from the function group Analog units.

Parameter: Default temperature

• Recommended setting value (_:118) Default temperature = 40°C


Under the following conditions, the Default temperature will be set as ambient temperature:

• A temperature sensor for measuring the ambient temperature is not connected.

• The temperature measurement is interrupted and the measured temperature value is less than the
Default temperature.
Siemens recommends using the default setting.

Parameter: Minimal temperature

• Default setting (_:117) Minimal temperature = -20°C


If the measured ambient temperature drops below the preset value, the set value will be assumed as the
ambient temperature. If the overload protection works with a prespecified outside temperature, and this
temperature drops below the value set in the Minimal temperature parameter, the Minimal tempera-
ture can also be used.

6.22.5 Settings

Addr. Parameter C Setting Options Default Setting


49 Th.overl. #
_:1 49 Th.overl. #:Mode • off off
• on
• test
_:2 49 Th.overl. #:Operate & • no no
flt.rec. blocked
• yes
_:101 49 Th.overl. #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
current warning 5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A

760 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.22 Thermal Overload Protection, 1-Phase

Addr. Parameter C Setting Options Default Setting


_:104 49 Th.overl. #:Threshold 50 % to 100 % 90 %
thermal warn.
_:105 49 Th.overl. #:Dropout 50 % to 99 % 90 %
threshold operate
_:106 49 Th.overl. #:K-factor 0.10 to 4.00 1.10
_:110 49 Th.overl. #:Thermal 10 s to 60000 s 900 s
time constant
_:107 49 Th.overl. #:Imax 1 A @ 100 Irated 0.030 A to 10.000 A 2.500 A
thermal 5 A @ 100 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 50 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 12.500 A
_:109 49 Th.overl. #:Tempera- 40 K to 200 K 70 K
ture rise at Irated
_:113 49 Th.overl. #:Storage of • no no
thermal replica
• yes
_:114 49 Th.overl. #:Behav. at • current limiting current limiting
I> Imax therm.
• freeze therm. rep.
_:118 49 Th.overl. #:Default -55°C to 55°C 40°C
temperature
_:117 49 Th.overl. #:Minimal -55°C to 40°C -20°C
temperature
_:44 49 Th.overl. #:Tempera- Setting options depend on
ture sensor configuration

6.22.6 Information List

No. Information Data Class Type


(Type)
49 Th.overl. #
_:500 49 Th.overl. #:>Block stage SPS I
_:501 49 Th.overl. #:>Reset thermal replica SPS I
_:54 49 Th.overl. #:Inactive SPS O
_:52 49 Th.overl. #:Behavior ENS O
_:53 49 Th.overl. #:Health ENS O
_:301 49 Th.overl. #:Current warning SPS O
_:302 49 Th.overl. #:Thermal warning SPS O
_:303 49 Th.overl. #:Block close SPS O
_:55 49 Th.overl. #:Pickup ACD O
_:300 49 Th.overl. #:Operate alarm only ACT O
_:57 49 Th.overl. #:Operate ACT O
_:304 49 Th.overl. #:Time until close MV O
_:305 49 Th.overl. #:Time until trip MV O
_:306 49 Th.overl. #:Overload MV O
_:310 49 Th.overl. #:Equival. current MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 761


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.23 Unbalanced-Load Protection

6.23 Unbalanced-Load Protection

6.23.1 Overview of Functions

The Unbalanced-load protection function detects unbalanced loads or line interruptions of electrical
machines (generators and motors). Unbalanced loads create a counter-rotating magnetic field at double
frequency in the rotor. The skin effect leads to local overheating on the surface of the rotor bars in the transi-
tion between the slot wedges and the winding bundles. Another effect of unbalanced loads is the overheating
of the damper winding.

6.23.2 Structure of the Function

The Unbalanced-load protection function is used in the protection function group. The Unbalanced-load
protection function is preconfigured with 1 stage. A maximum of 2 stages can operate simultaneously in the
function.

[dwunbla-240913, 1, en_US]

Figure 6-184 Structure/Embedding of the Function

762 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.23 Unbalanced-Load Protection

6.23.3 Function Description

Logic of the Stage

[lounbala-090812-03.tif, 1, en_US]

Figure 6-185 Logic Diagram of the Unbalanced-Load Protection Function

Method of Measurement
The stage uses the negative-sequence current I2 as a measurand. The negative-sequence current is calculated
from the measured 3-phase currents according to the defining equation of symmetrical components.

Warning Stage
If the negative-sequence current I2 continuously exceeds the parameter Max. continuously perm. I2,
the Warning indication is given after expiry of a set time Warning delay.

Thermal Characteristic Stage


The machine manufacturers indicate the permissible unbalanced load using the following formula:

SIPROTEC 5, 7SJ82/7SJ85, Manual 763


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.23 Unbalanced-Load Protection

[forbanl1-030812-02.tif, 1, en_US]

With:
tI2Perm Permissible time of the negative-sequence current
K Unbalanced-load factor of the machine (parameter Unbalanced load factor K)
I2/Irated,machine Actual unbalanced-load current as a per unit value(negative-sequence current/rated
current of the machine)

[dwunbalo-230913, 2, en_US]

Figure 6-186 Operate Curve of the Unbalanced-Load Protection

The parameter Unbalanced load factor K depends on the machine. It also represents the time in
seconds during which the machine can be loaded with a 100 % unbalanced load. This factor is typical in a
range from 5 s to 40 s. The heating of the protected object starts to calculate as soon as the negative-
sequence current I2 exceeds the parameter Max. continuously perm. I2. The operate time is calculated
from the flowing negative-sequence current I2 with an integrating method of measurement depending on the
thermal characteristic. As soon as the integrate result reaches the parameter Unbalanced load factor K,
the thermal characteristic stage operates.

Limitation of Operate Curve


To avoid an overfunction of the thermal characteristic stage in the situation of unbalanced short circuits (for
example, 2-phase short circuit), the input current I2 is restricted to an upper limit. The limiting value is 10
times of Max. continuously perm. I2. If I2 exceeds the limit, the operate time of the function is
constant.
In addition, the thermal memory is limited to 200 % of Unbalanced load factor K. The limitation avoids
a too long cooling after a delayed short-circuit tripping (for example, of external power-system faults).

764 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.23 Unbalanced-Load Protection

Cooling Time Thermal Replica


The thermal replica starts to cool down as soon as the negative-sequence current I2 is lower than Max.
continuously perm. I2. The thermal replica decreases according to the parameter Cooling time
therm.replica. The parameter Cooling time therm.replica is the time required by the thermal
replica to cool down from 100 % to 0 %. If the parameter Cooling time therm.replica is set to 0, the
thermal replica is reset immediately.
The parameter Cooling time therm.replica depends on the construction type of the machine, espe-
cially of the damper winding. Preloading is considered when unbalanced loading occurs again during the
cooling time. The protection device thus operates in a shorter time.

Functional Measured Values


The following formula is used to calculate the functional measured value ΘI2/Θop:

[forunbl2-030812-02.tif, 1, en_US]

With
ΘI2/Θop Functional measured value indicating the thermal replica of the unbalanced
load
Integrating method of measurement of the thermal replica of the negative-
sequence system

K Unbalanced-load factor of the machine (parameter Unbalanced load


factor K)
I2/Irated,machine Unbalanced-load as a per unit value (negative-sequence current/rated current
of the machine)

If the functional measured value reaches 100 %, the operate of the function is initiated.

6.23.4 Application and Setting Notes

The function is used in the applications of machines. You can get the necessary settings from the technical
data of the synchronous generators and motors. The setting example is applied for a generator application.

Parameter: Max. continuously perm. I2, Warning delay

• Default setting (_:11011:101) Max. continuously perm. I2 = 10.0 %

• Default setting (_:11011:104) Warning delay = 15 s


If the negative-sequence current I2 exceeds Max. continuously perm. I2 , the stage picks up and a
warning indication is given after the set time delay Warning delay .
The parameter Max. continuously perm. I2 is given in percentage of the rated current of the
protected object.
The setting value of the parameter Max. continuously perm. I2 depends on following parts:

• Design of the machine (salient pole or non-salient pole rotor synchronous machine)

• Cooling system (directly or indirectly cooled)

• Size of the machine


Depending on the standards IEEE C50.12 and IEC 60034-1, the parameter is given in the range between 5 %
and 12 %. To set the parameter Max. continuously perm. I2 , technical data of the machine is

SIPROTEC 5, 7SJ82/7SJ85, Manual 765


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.23 Unbalanced-Load Protection

required. The technical data of the machine is provided in the Technical Data Sheet of the machine manufac-
turer.

EXAMPLE
The following example shows the setting of the parameter Max. continuously perm. I2 . The value 10
% is selected in the example.
To avoid issuing the Warning indication too fast, Siemens recommends a longer delay. Setting the param-
eter Warning delay in the range of 10 s to 20 s is practicable. 15 s is selected in the example.

[dwunbloc-030812, 1, en_US]

Figure 6-187 Example of an Unbalanced-Load Characteristic Specified by the Machine Manufacturer

Parameter: Unbalanced load factor K

• Default setting (_:11011:102) Unbalanced load factor K = 15 s


Unbalanced load factor K can be derived from the unbalanced-load characteristic according to
Figure 6-187. You can read the time corresponding to Unbalanced load factor K at the point I2 /
Irated,machine= 1. In the example, this is the p.u. value 10° which corresponds to a time of 15 s. As the example
shows, the time is often written directly on the characteristic curve.

Parameter: Cooling time therm.replica

• Default setting (_:11011:103) Cooling time therm.replica = 1500 s


The parameter Cooling time therm.replica establishes the time required by the protected object to
cool down the thermal replica to the initial value. If the machine manufacturer does not provide this informa-
tion, the setting value of Cooling time therm.replica can be calculated from the setting values of
Unbalanced load factor K and Max. continuously perm. I2 by the formula in the following
example.

766 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.23 Unbalanced-Load Protection

EXAMPLE

[forbala2-290812-02.tif, 1, en_US]

Max. continuously perm. I2 = 10.0 % (corresponds to 0.1)


Unbalanced load factor K = 15 s
Cooling time therm. replica = 1500 s

6.23.5 Settings

Addr. Parameter C Setting Options Default Setting


Therm. Stage 1
_:11011:1 Therm. Stage 1:Mode • off off
• on
• test
_:11011:2 Therm. Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:11011:101 Therm. Stage 1:Max. 3.0 % to 30.0 % 10.0 %
continuously perm. I2
_:11011:102 Therm. Stage 1:Unbalanced 1.0 s to 100.0 s 15.0 s
load factor K
_:11011:103 Therm. Stage 1:Cooling 0 s to 50000 s 1500 s
time therm.replica
_:11011:104 Therm. Stage 1:Warning 0.0 s to 60.0 s;∞ 15.0 s
delay

6.23.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Therm. Stage 1
_:11011:81 Therm. Stage 1:>Block stage SPS I
_:11011:501 Therm. Stage 1:>Reset thermal replica SPS I
_:11011:53 Therm. Stage 1:Health ENS O
_:11011:54 Therm. Stage 1:Inactive SPS O
_:11011:52 Therm. Stage 1:Behavior ENS O
_:11011:302 Therm. Stage 1:Thermal replica reset SPS O
_:11011:301 Therm. Stage 1:Warning ACD O
_:11011:55 Therm. Stage 1:Pickup ACD O
_:11011:56 Therm. Stage 1:Operate delay expired ACT O
_:11011:57 Therm. Stage 1:Operate ACT O
_:11011:303 Therm. Stage 1:ΘI2/Θop MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 767


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

6.24 Overvoltage Protection with 3-Phase Voltage

6.24.1 Overview of Functions

The function Overvoltage protection with 3-phase voltage (ANSI 59) is used to:

• Monitor the permissible voltage range

• Protect equipment (for example, plant components, machines, etc.) against damages caused by over-
voltage

• Decouple systems (for example, wind power supply)


Abnormally high voltages in power systems are caused by voltage controller failure at the transformer or on
long transmission lines under low-load conditions.
When using common-mode reactors in the protected power system, the device must shut down the line
quickly if the reactors fail (for example, due to fault clearance). The insulation is endangered by the over-
voltage condition.
Overvoltages at capacitor banks can be caused by resonances with line or transformer inductances.
In power plants increased voltage levels can be due to one of these factors:

• Incorrect operation when controlling the excitation system manually

• Failure of the automatic voltage controller

• After full load shedding of a generator

• Generators which are disconnected from the network or in island mode

6.24.2 Structure of the Function

The Overvoltage protection with 3-phase voltage function is used in protection function groups with
voltage measurement.
The Overvoltage protection with 3-phase voltage function comes factory-set with 2 Definite-time over-
voltage protection stages. In this function, the following stages can operate simultaneously:

• 3 stages Definite-time overvoltage protection

• 2 stages Inverse-time overvoltage protection


Stages that are not preconfigured are shown in gray in the following figure.

[dw3phovp-030211-01.tif, 5, en_US]

Figure 6-188 Structure/Embedding of the Function

768 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

6.24.3 Stage with Definite-Time Characteristic Curve

6.24.3.1 Description

Logic of the Stage

[lo3phasi-090611-01.tif, 4, en_US]

Figure 6-189 Logic Diagram of the Definite-Time Overvoltage Protection with 3-Phase Voltage

Method of Measurement
Use the Method of measurement parameter to define whether the stage uses the fundamental comp.
or the RMS value.

• Measurement fundamental comp.:


This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.

SIPROTEC 5, 7SJ82/7SJ85, Manual 769


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

• Measurement RMS value:


This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Pickup Stabilization
To enable the pickup stabilization, you set the Stabilization counter parameter to a value other than
zero. Then, if the input voltage keeps exceeding the Threshold for a specified number (1 + Stabiliza-
tion counter value) of successive measuring cycles, the stage picks up. For 50 Hz, the measuring cycle
time is 10 ms.
If you set this parameter to 0 (default value), the stabilization is not applied. The pickup signal is issued imme-
diately after the input voltage exceeds the Threshold.

Pickup Mode
The Pickup mode parameter defines whether the protection stage picks up if all 3 measuring elements
detect the overvoltage condition (3 out of 3) or if only 1 measuring element detects the overvoltage
condition (1 out of 3).

Measured Value
Use the Measured value parameter to define whether the tripping stage analyzes the phase-to-phase
voltages VAB, VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. Blocking is possible externally or internally via the
binary input signal >Block stage.

6.24.3.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:181:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental
component (standard method = default setting) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement to suppress harmonics or transient
voltage peaks.
Siemens recommends this method of measurement as the default setting.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Do not set the threshold
value of the stage under 10 V for this method of measurement.

Parameter: Measured value

• Default setting (_:181:9) Measured value = phase-to-phase


With the Measured value parameter, you define whether the stage monitors the phase-to-phase voltages
VAB, VBC, and VCA or the phase-to-ground voltages VA, VB, and VC.

770 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

Parameter Value Description


phase-to-phase If you want to monitor the voltage range, keep phase-to-phase as the
default setting. In this case, the function will not pick up on ground faults.
Siemens recommends the measured value phase-to-phase as the
default setting.
phase-to-ground Select the phase-to-ground setting if you want to detect voltage unbal-
ances and overvoltage conditions caused by ground faults.

Parameter: Threshold

• Default setting (_:181:3) Threshold = 110 V


Depending on the Measured value , the Threshold is set either as phase-to-phase quantity or as phase-
to-ground quantity. The default setting assumes that the voltage range is monitored on long-distance trans-
mission lines under low-load conditions.
Specify the Threshold (pickup threshold) for the specific application.

Parameter: Stabilization counter

• Default setting (_:2311:101) Stabilization counter = 0


You can configure the Stabilization counter parameter in the function block General.
For special applications, it could be desirable that a short exceeding of the input voltage above the pickup
value does not lead to the pickup of the stage, which starts fault logging and recording. This is achieved by
setting the Stabilization counter parameter to a value other than zero.
For example, if you set this parameter to 1, the pickup signal is issued when the voltage keeps exceeding the
Threshold for 2 successive measuring cycles. For 50 Hz, the measuring cycle time is 10 ms.

Parameter: Operate delay

• Default setting (_:181:6) Operate delay = 3 s


The Operate delay must be set for the specific application.

Parameter: Dropout ratio

• Recommended setting value (_:181:4) Dropout ratio = 0.95


The recommended set value of 0.95 is appropriate for most applications. To achieve high measurement preci-
sion, the Dropout ratio can be reduced, to 0.98, for example.

Parameter: Pickup mode

• Recommended setting value (_:181:101) Pickup mode = 1 out of 3


With the Pickup mode parameter, you define whether the protection stage picks up if all 3 measuring
elements detect the overvoltage condition (3 out of 3) or if only 1 measuring element detects the over-
voltage condition (1 out of 3).
Parameter Value Description
1 out of 3 Select the setting for protection applications or for monitoring the voltage
range.
Siemens recommends 1 out of 3 as the default setting. This reflects how
the function behaved in previous generations (SIPROTEC 4, SIPROTEC 3).
3 out of 3 Select this setting when using the stage to disconnect from the power
system (in the case of wind farms, for example).

Operation as Supervision Function


If you want the stage to have a reporting effect only, generation of the operate indication and fault logging
can be disabled via the Operate & flt.rec. blocked parameter.

SIPROTEC 5, 7SJ82/7SJ85, Manual 771


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

EXAMPLE
Example for 2-stage overvoltage protection
The example describes the possible settings for a 2-stage overvoltage protection function. We will look at the
settings of the parameters Threshold and Operate delay.

• 1. Stage:
To detect stationary overvoltages, set the threshold value of the first overvoltage-protection element at
least 10 % above the max. stationary phase-to-phase voltage anticipated during normal operation. When
setting the parameter Measured value to phase-to-phase voltage and a secondary rated voltage of
100 V, the secondary setting value of the first overvoltage-protection element is calculated as follows:

Threshold value: 10 % above Vrated

Vthreshold, sec = 1.1 Vrated, sec = 1.1 × 100 V = 110 V


This requires that the primary rated voltages of protected object and voltage transformer are identical. If they
are different, you have to adjust the pickup value.
For the Operate delay set a value of 3 s.

• 2. Stage:
The second overvoltage-protection stage is intended for high overvoltages with short duration. A high
pickup value is selected here, for example, 1.5 times the rated voltage. A time delay setting of 0.1 s to
0.2 s is sufficient then.

Stage Setting Values


Threshold value Time delay
1 1.1 Vrated 3s
2 1.5 Vrated 0.1 s to 0.2 s

6.24.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Stabilization 0 to 10 0
counter
Definite-T 1
_:181:1 Definite-T 1:Mode • off off
• on
• test
_:181:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:181:9 Definite-T 1:Measured • phase-to-ground phase-to-phase
value
• phase-to-phase
_:181:8 Definite-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:181:101 Definite-T 1:Pickup mode • 1 out of 3 1 out of 3
• 3 out of 3
_:181:3 Definite-T 1:Threshold 0.300 V to 340.000 V 110.000 V
_:181:4 Definite-T 1:Dropout 0.90 to 0.99 0.95
ratio
_:181:6 Definite-T 1:Operate 0.00 s to 300.00 s 3.00 s
delay

772 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

Addr. Parameter C Setting Options Default Setting


Definite-T 2
_:182:1 Definite-T 2:Mode • off off
• on
• test
_:182:2 Definite-T 2:Operate & • no no
flt.rec. blocked
• yes
_:182:9 Definite-T 2:Measured • phase-to-ground phase-to-phase
value
• phase-to-phase
_:182:8 Definite-T 2:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:182:101 Definite-T 2:Pickup mode • 1 out of 3 1 out of 3
• 3 out of 3
_:182:3 Definite-T 2:Threshold 0.300 V to 340.000 V 130.000 V
_:182:4 Definite-T 2:Dropout 0.90 to 0.99 0.95
ratio
_:182:6 Definite-T 2:Operate 0.00 s to 300.00 s 0.50 s
delay

6.24.3.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:181:81 Definite-T 1:>Block stage SPS I
_:181:54 Definite-T 1:Inactive SPS O
_:181:52 Definite-T 1:Behavior ENS O
_:181:53 Definite-T 1:Health ENS O
_:181:55 Definite-T 1:Pickup ACD O
_:181:300 Definite-T 1:Pickup loop AB SPS O
_:181:301 Definite-T 1:Pickup loop BC SPS O
_:181:302 Definite-T 1:Pickup loop CA SPS O
_:181:56 Definite-T 1:Operate delay expired ACT O
_:181:57 Definite-T 1:Operate ACT O
Definite-T 2
_:182:81 Definite-T 2:>Block stage SPS I
_:182:54 Definite-T 2:Inactive SPS O
_:182:52 Definite-T 2:Behavior ENS O
_:182:53 Definite-T 2:Health ENS O
_:182:55 Definite-T 2:Pickup ACD O
_:182:300 Definite-T 2:Pickup loop AB SPS O
_:182:301 Definite-T 2:Pickup loop BC SPS O
_:182:302 Definite-T 2:Pickup loop CA SPS O
_:182:56 Definite-T 2:Operate delay expired ACT O
_:182:57 Definite-T 2:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 773


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

6.24.4 Stage with Inverse-Time Characteristic Curve

6.24.4.1 Description

Logic of the Stage

[lo3phinv, 3, en_US]

Figure 6-190 Logic Diagram of the Inverse-Time Overvoltage Protection with 3-Phase Voltage

Method of Measurement
Use the Method of measurement parameter to define whether the stage uses the fundamental comp.
or the RMS value .

• Measurement fundamental comp. :


This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.

774 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

• Measurement RMS value :


This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Pickup Stabilization
To enable the pickup stabilization, you set the Stabilization counter parameter to a value other than
zero. Then, if the input voltage keeps exceeding the pickup value for a specified number (1 + Stabiliza-
tion counter value) of successive measuring cycles, the stage picks up. For 50 Hz, the measuring cycle
time is 10 ms.
If you set this parameter to 0 (default value), the stabilization is not applied. The pickup signal is issued imme-
diately after the input voltage exceeds the pickup value.

Pickup Mode
With the Pickup mode parameter, you define whether the protection stage picks up if all 3 measuring
elements detect the overvoltage condition ( 3 out of 3 ) or if only 1 measuring element detects the over-
voltage condition ( 1 out of 3 ).

Measured Value
Use the Measured value parameter to define whether the stage analyzes the phase-to-phase voltages VAB,
VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.

Pickup and Operate Curve


When the input voltage exceeds the threshold value by a settable value Pickup factor , the stage picks up
and the inverse-time characteristic curve is processed. Operate delay starts. The operate delay is the sum of
inverse-time delay and additional time delay.

Where
Top Operate delay
Tinv Inverse-time delay
Tadd Additional time delay (parameter Additional time delay )

After pickup, the time value Tinv is calculated for every input voltage that exceeds the threshold. An integrator
accumulates the value 1/Tinv. Once the accumulated integral reaches the fixed value 1, the inverse-time delay
expires. The additional time delay Tadd starts. The stage operates after the additional time delay expires.

SIPROTEC 5, 7SJ82/7SJ85, Manual 775


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

The inverse-time characteristic is shown in the following figure.

[dwovpinv, 2, en_US]

Figure 6-191 Operate Curve of Inverse-Time Characteristic

The inverse-time delay is calculated with the following formula:

Where
Tinv Inverse-time delay
Tp Time multiplier (parameter Time dial )
V Measured voltage
Vthresh Threshold value (parameter Threshold )
k Curve constant k (parameter Charact. constant k )
α Curve constant α (parameter Charact. constant α )
c Curve constant c (parameter Charact. constant c )

When V/Vthresh is equal to or greater than 20, the inverse-time delay does not decrease any further.

Dropout Behavior
When the voltage falls below the dropout threshold (0.95 × pickup factor × threshold value), the pickup signal
is going and the dropout is started. You can define the dropout behavior via parameter Reset time . Instan-
taneous reset takes place by setting Reset time to 0 s. A delayed reset takes place by setting the desired
delay time.
During the Reset time (> 0 s), the elapsed operate delay is frozen. If the pickup value is exceeded again
within this period, the stage operates when the rest of operate delay expires.

776 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

Blocking the Stage


In the event of blocking, the picked up stage will be reset. Blocking is possible externally or internally via the
binary input signal >Block stage .

6.24.4.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the tripping stage uses the fundamental
component (standard method = default setting) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement to suppress harmonics or transient
voltage peaks.
Siemens recommends this method of measurement as the default setting.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Do not set the threshold
value of the tripping stage under 10 V for this method of measurement.

Parameter: Measured value

• Default setting (_:9) Measured value = phase-to-phase


With the Measured value parameter, you define whether the tripping stage monitors the phase-to-phase
voltages VAB, VBC, and VCA or the phase-to-ground voltages VA, VB, and VC.

Parameter Value Description


phase-to-phase If you want to monitor the voltage range, keep phase-to-phase as the
default setting. In this case, the function will not pick up on ground faults.
Siemens recommends the measured value phase-to-phase as the
default setting.
phase-to-ground Select the phase-to-ground setting if you want to detect voltage unbal-
ances and overvoltage conditions caused by ground faults.

Parameter: Threshold, Pickup factor

• Default setting (_:3) Threshold = 110.000 V

• Default setting (_:101) Pickup factor = 1.10


The stage picks up when the measured voltage value exceeds the pickup value Threshold × Pickup
factor.
Depending on the Measured value, the Threshold is set either as phase-to-phase quantity or as phase-to-
ground quantity.
With the Pickup factor parameter, you modify the pickup value. To avoid a long-time operate delay after
pickup when the measured value is slightly over the threshold, Siemens recommends using the default
setting.
Specify the Threshold (pickup threshold) and Pickup factor for the specific application.

Parameter: Stabilization counter

• Default setting (_:2311:101) Stabilization counter = 0


You can configure the Stabilization counter parameter in the function block General.
For special applications, it could be desirable that a short exceeding of the input voltage above the pickup
value does not lead to the pickup of the stage, which starts fault logging and recording. This is achieved by
setting the Stabilization counter parameter to a value other than zero.

SIPROTEC 5, 7SJ82/7SJ85, Manual 777


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

For example, if you set this parameter to 1, the pickup signal is issued when the voltage keeps exceeding the
pickup value for 2 successive measuring cycles. For 50 Hz, the measuring cycle time is 10 ms.

Parameter: Pickup mode

• Recommended setting value (_:182:101) Pickup mode = 1 out of 3


With the Pickup mode parameter, you define whether the protection stage picks up if all 3 measuring
elements detect the overvoltage condition (3 out of 3) or if only 1 measuring element detects the over-
voltage condition (1 out of 3).
Parameter Value Description
1 out of 3 Select the setting for protection applications or for monitoring the voltage
range.
Siemens recommends 1 out of 3 as the default setting. This reflects how
the function behaved in previous generations (SIPROTEC 4, SIPROTEC 3).
3 out of 3 Select this setting when using the stage to disconnect from the power
system (in the case of wind farms, for example).

Parameter: Charact. constant k, Charact. constant α, Charact. constant c

• Default setting (_:102) Charact. constant k = 1.00

• Default setting (_:103) Charact. constant α = 1.000

• Default setting (_:104) Charact. constant c = 0.000


With the parameters Charact. constant k, Charact. constant α, and Charact. constant c,
you define the required inverse-time characteristic curve.

Parameter: Time dial

• Default setting (_:105) Time dial = 1.00


With the Time dial parameter, you displace the characteristic curve in the time direction.
As usually, there is no time grading for voltage protection and therefore no displacement of the characteristic
curve, Siemens recommends leaving the Time dial parameter at 1.00 (default setting).

Parameter: Additional time delay

• Default setting (_:106) Additional time delay = 0.00 s


With the Additional time delay parameter, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, only the inverse-time delay is operative.

Parameter: Reset time

• Default setting (_:107) Reset time = 0.00 s


With the Reset time parameter, you define the reset time delay which is started when the voltage falls
below the dropout threshold. Set the parameter Reset time to 0 s when instantaneous reset is desired.
Under network conditions of intermittent faults or faults which occur in rapid succession, Siemens recom-
mends setting the Reset time to an appropriate value (> 0 s) to ensure the operation. Otherwise Siemens
recommends keeping the default value to ensure a fast reset of the function.

778 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.24 Overvoltage Protection with 3-Phase Voltage

6.24.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Inverse-T #
_:1 Inverse-T #:Mode • off off
• on
• test
_:2 Inverse-T #:Operate & • no no
flt.rec. blocked
• yes
_:9 Inverse-T #:Measured • phase-to-ground phase-to-phase
value
• phase-to-phase
_:8 Inverse-T #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:108 Inverse-T #:Pickup mode • 1 out of 3 1 out of 3
• 3 out of 3
_:3 Inverse-T #:Threshold 0.300 V to 340.000 V 110.000 V
_:101 Inverse-T #:Pickup factor 1.00 to 1.20 1.10
_:102 Inverse-T #:Charact. 0.00 to 300.00 1.00
constant k
_:103 Inverse-T #:Charact. 0.010 to 5.000 1.000
constant α
_:104 Inverse-T #:Charact. 0.000 to 5.000 0.000
constant c
_:105 Inverse-T #:Time dial 0.05 to 15.00 1.00
_:106 Inverse-T #:Additional 0.00 s to 60.00 s 0.00 s
time delay
_:107 Inverse-T #:Reset time 0.00 s to 60.00 s 0.00 s

6.24.4.4 Information List

No. Information Data Class Type


(Type)
Inverse-T #
_:81 Inverse-T #:>Block stage SPS I
_:54 Inverse-T #:Inactive SPS O
_:52 Inverse-T #:Behavior ENS O
_:53 Inverse-T #:Health ENS O
_:55 Inverse-T #:Pickup ACD O
_:300 Inverse-T #:Pickup loop AB SPS O
_:301 Inverse-T #:Pickup loop BC SPS O
_:302 Inverse-T #:Pickup loop CA SPS O
_:56 Inverse-T #:Operate delay expired ACT O
_:57 Inverse-T #:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 779


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual


Voltage

6.25.1 Overview of Functions

The Overvoltage protection with zero-sequence voltage/residual voltage function (ANSI 59N):

• Detects ground faults in isolated or arc-suppression-coil-grounded systems

• Determines the phase affected by the ground fault

• Works with electrical machines to detect ground faults in the stator winding

6.25.2 Structure of the Function

The Overvoltage protection with zero-sequence voltage/residual voltage function is used in protection
function groups with voltage measurement.
The Overvoltage protection with zero-sequence voltage/residual voltage function comes factory-set with
1 stage. A maximum of 3 stages can be operated simultaneously in the function.
The stages have an identical structure.

[dwu0ovps-030211-01.tif, 2, en_US]

Figure 6-192 Structure/Embedding of the Function

780 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

6.25.3 Stage Description

Logic of a Stage

[loovpu03-090611-01.tif, 2, en_US]

Figure 6-193 Logic Diagram of an Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage
Stage

Measured Value, Method of Measurement


The device measures the residual voltage at the broken-delta winding. The measured voltage is converted to
the zero-sequence voltage V0. If the residual voltage is not available to the device as a measurand, the zero-
sequence voltage V0 is calculated from the measured phase-to-ground voltages VA, VB, and VC using the
defining equation.

SIPROTEC 5, 7SJ82/7SJ85, Manual 781


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

Use the Method of measurement parameter to select the relevant method of measurement, depending on
the application.

• Measurement of the fundamental comp. (standard filter):


This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.

• Measurement of the RMS value parameter value (true RMS):


This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value.

• fund. comp. long filter (fundamental component over 2 cycle filters with triangular window):
This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically. The extended filter length compared to the standard filter and the use of the
triangular window results in a particularly strong attenuation of harmonics and transient faults. The
extended filter length causes the pickup time to increase slightly compared to the standard filter (see
Technical Data).

Pickup, Dropout
The stage compares the Threshold with the zero-sequence voltage V0. The Pickup delay parameter
allows you to delay the pickup of the stage depending on the residual voltage.
With the Dropout ratio parameter you can define the ratio of the dropout value to the Threshold.

Determination of the Faulty Phase


You can use the Detection of faulty phase parameter to enable or disable the determining of the
phase affected by the ground fault. Determining is released when the stage picks up. If 2 phases exceed the
threshold value V> healthy ph-to-gnd volt. and 1 phase falls below the threshold value V< faulty
ph-to-gnd volt., the last phase is considered to be affected by the ground fault and is signaled as such.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. The following blocking options are available for the
stage:

• Via the binary input signal >Block stage from an external or internal source

• From inside on pick up of the measuring-voltage failure detection function (see chapter 9.3.2.1 Over-
view of Functions). The Blk. by meas.-volt. failure parameter can be set so that measuring-
voltage failure detection blocks the stage or does not block it.

• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker. The Blk. by meas.-volt.
failure parameter can be set so that measuring-voltage failure detection blocks the stage or does not
block it.

6.25.4 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:331:8) Method of measurement = fundamental comp.


The Method of measurement parameter allows you to define whether the function works with the funda-
mental component or the calculated RMS value.

782 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

Parameter Value Description


fundamental comp. This method of measurement suppresses the harmonics or transient voltage
peaks.
Siemens recommends using this setting as the standard method.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Do not set the threshold
value of the tripping stage under 10 V for this method of measurement.
fund. comp. long filter To implement particularly strong damping of harmonics and transient
disturbances, select this method of measurement. At 2 periods, the length
of the filter is longer than that of the standard filter.
Please note that in this case the pickup time of the stage increases slightly
(see Technical Data).

Parameter: Pickup delay

• Recommended setting value (_:331:107) Pickup delay = 0.00 ms


The Pickup delay parameter allows you to delay the analysis of the measurand (to generate the pickup)
depending on the occurrence of the residual voltage. A pickup delay can be necessary if high transients are
anticipated after fault inception due to high line and ground capacitances.
Siemens recommends using the default setting Pickup delay = 0.00 ms.

Parameter: Threshold

• Default setting (_:331:3) Threshold = 30.000 V 26


The threshold value of the function is set as the zero-sequence voltage V0. The device calculates the zero-
sequence voltage V0 either from the residual voltage measured via the broken-delta winding or from the
3 phase-to-ground voltages.
The setting value depends on the system grounding:

• Since virtually the full residual voltage occurs during ground faults in isolated or arc-suppression-coil-
grounded systems, the setting value is uncritical there. It should range between 20 V and 40 V. A higher
sensitivity (= lower threshold value) can be necessary for high fault resistances.

• You should select a more sensitive (smaller) value in a grounded system. This value must be higher than
the maximum residual voltage anticipated during operation caused by system unbalances.

EXAMPLE
For an isolated system
The residual voltage is measured via the broken-delta winding:

• If the ground fault is fully unbalanced, a residual voltage of 100 V is present at the device terminals.

• The threshold value should be set so that the stage picks up on 50 % of the full residual voltage.

• At full residual voltage, the zero-sequence voltage is 100 V/√3 = 57.7 V


Setting value: 0.5 ⋅ 57.7 V = 28.9 V ≈ 30 V

Parameter: Dropout ratio

• Recommended setting value (_:331:4) Dropout ratio = 0.95


The recommended set value of 0.95 is appropriate for most applications. The dropout ratio can be reduced
for example, to 0.98 to achieve a high measurement precision.

26 The specific setting limits depend on the transformer data and transformer connections set.

SIPROTEC 5, 7SJ82/7SJ85, Manual 783


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

Parameter: Operate delay

• Default setting (_:331:6) Operate delay = 3.00 s


The Operate delay allows you to prevent transient residual voltages from initiating a trip. The setting
depends on the specific application.

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:331:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following two conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


switched on.

• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see Chapter 9.3.4.1 Overview of Functions).

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

Parameter: Detection of faulty phase

• Default setting (_:331:109) Detection of faulty phase = no


The Detection of faulty phase parameter controls how the stage responds to determine which phase
is affected by the ground fault.
Parameter Value Description
no The phase affected by the ground fault is not determined.
Select the default setting if you do not want to use the stage to detect
ground faults. For example, applications in grounded systems.
yes After a pickup by the residual voltage the device tries to determine, which
phase is affected by the ground fault.
Select this setting for applications in isolated or arc-suppression-coil-
grounded systems.

Parameter: V< faulty ph-to-gnd volt.

• Default setting (_:331:104) V< faulty ph-to-gnd volt. = 40.000 V 27


Set the threshold value for determining which phase is affected by the ground fault in the V< faulty ph-
to-gnd volt. parameter. The setting value is a phase-to-ground quantity.
The set value must be smaller than the minimum phase-to-ground voltage occurring during operation.
Siemens recommends using the default setting V< faulty ph-to-gnd volt. = 40.000 V.

Parameter: V> healthy ph-to-gnd volt.

• Default setting (_:331:101) V> healthy ph-to-gnd volt. = 75.000 V 28


Set the threshold value for the two healthy phases in the V> healthy ph-to-gnd volt. parameter. The
setting value is a phase-to-ground quantity.
The set value must lie above the maximum phase-to-ground voltage occurring during operation, but below
the minimum phase-to-phase voltage present during operation. At Vrated = 100 V, the value has to be set to

27 The specific setting limits depend on the transformer data and transformer connections set.
28 The specific setting limits depend on the transformer data and transformer connections set.

784 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

75 V, for example. Siemens recommends using the default setting V> healthy ph-to-gnd volt. =
75.000 V.

Operation as Supervision Function


If you want the stage to have a reporting effect only, generation of the operate indication and fault logging
can be disabled via the Operate & flt.rec. blocked parameter.

6.25.5 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:331:1 Stage 1:Mode • off off
• on
• test
_:331:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:331:10 Stage 1:Blk. by meas.- • no yes
volt. failure
• yes
_:331:109 Stage 1:Detection of • no no
faulty phase
• yes
_:331:8 Stage 1:Method of • fundamental comp. fundamental
measurement comp.
• fund. comp. long filter
• RMS value
_:331:3 Stage 1:Threshold 0.300 V to 340.000 V 30.000 V
_:331:4 Stage 1:Dropout ratio 0.90 to 0.99 0.95
_:331:107 Stage 1:Pickup delay 0.00 s to 320.00 s 0.00 s
_:331:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
_:331:101 Stage 1:V> healthy ph- 0.300 V to 200.000 V 75.000 V
to-gnd volt.
_:331:104 Stage 1:V< faulty ph-to- 0.300 V to 200.000 V 40.000 V
gnd volt.

6.25.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:331:81 Stage 1:>Block stage SPS I
_:331:54 Stage 1:Inactive SPS O
_:331:52 Stage 1:Behavior ENS O
_:331:53 Stage 1:Health ENS O
_:331:300 Stage 1:Faulty phase ACT O
_:331:55 Stage 1:Pickup ACD O
_:331:56 Stage 1:Operate delay expired ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 785


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.25 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

No. Information Data Class Type


(Type)
_:331:57 Stage 1:Operate ACT O

786 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.26 Overvoltage Protection with Positive-Sequence Voltage

6.26 Overvoltage Protection with Positive-Sequence Voltage

6.26.1 Overview of Functions

The function Overvoltage protection with positive-sequence voltage (ANSI 59) is used to:

• Detect symmetric stationary overvoltages

• Supervise the voltage range if the positive-sequence voltage is the decisive quantity
Unbalanced overvoltages, for example, caused by ground faults and unbalanced faults, are not detected due
to the evaluation of the positive-sequence voltage.

6.26.2 Structure of the Function

The Overvoltage protection with positive-sequence voltage function is used in protection function groups,
which are based on voltage measurement.
The function Overvoltage protection with positive-sequence voltage comes factory-set with 2 stages. A
maximum of 3 tripping stages can be operated simultaneously in the function. The tripping stages have an
identical structure.

[dwovpu1s-030211-01.tif, 1, en_US]

Figure 6-194 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 787


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.26 Overvoltage Protection with Positive-Sequence Voltage

6.26.3 Stage Description

Logic of a Stage

[logovpu1-090611-01.tif, 1, en_US]

Figure 6-195 Logic Diagram of a Stage: Overvoltage Protection with Positive-Sequence Voltage

Method of Measurement
The stage uses the positive-sequence voltage. The positive-sequence voltage is calculated from the measured
phase-to-ground voltages according to the defining equation.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. Blocking is possible externally or internally via the
binary input signal >Block stage.

6.26.4 Application and Setting Notes

Parameter: Threshold

• Default setting (_:211:3) Threshold = 65 V


The Threshold is set according to the definition of the positive-sequence system.
Specify the Threshold (pickup threshold) for the specific application.

Parameter: Operate delay

• Default (_:211:6) Operate delay = 3 s


The Operate delay must be set for the specific application.

788 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.26 Overvoltage Protection with Positive-Sequence Voltage

Parameter: Dropout ratio

• Recommended setting value (_:211:4) Dropout ratio = 0.95


The default value of 0.95 is appropriate for most applications. To achieve high measurement precision, the
Dropout ratio can be reduced, to 0.98, for example.

General Notes
If the overvoltage is high, the first stage can trip with a short time delay. If overvoltages are lower, the second
stage can either only signal the threshold value violation (see Operation as monitoring function) or trip with a
longer delay to allow the voltage controller to regulate the voltage back into the nominal range.

Operation as Supervision Function


If you want the tripping stage to have a reporting effect only, generation of the operate indication and fault
logging can be disabled via the Operate & flt.rec. blocked parameter.

6.26.5 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:211:1 Stage 1:Mode • off off
• on
• test
_:211:2 Stage 1:Operate & flt.rec. • no no
blocked
• yes
_:211:3 Stage 1:Threshold 0.300 V to 200.000 V 65.000 V
_:211:4 Stage 1:Dropout ratio 0.90 to 0.99 0.95
_:211:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
Stage 2
_:212:1 Stage 2:Mode • off off
• on
• test
_:212:2 Stage 2:Operate & flt.rec. • no no
blocked
• yes
_:212:3 Stage 2:Threshold 0.300 V to 200.000 V 75.000 V
_:212:4 Stage 2:Dropout ratio 0.90 to 0.99 0.95
_:212:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s

6.26.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:211:81 Stage 1:>Block stage SPS I
_:211:54 Stage 1:Inactive SPS O
_:211:52 Stage 1:Behavior ENS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 789


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.26 Overvoltage Protection with Positive-Sequence Voltage

No. Information Data Class Type


(Type)
_:211:53 Stage 1:Health ENS O
_:211:55 Stage 1:Pickup ACD O
_:211:56 Stage 1:Operate delay expired ACT O
_:211:57 Stage 1:Operate ACT O
Stage 2
_:212:81 Stage 2:>Block stage SPS I
_:212:54 Stage 2:Inactive SPS O
_:212:52 Stage 2:Behavior ENS O
_:212:53 Stage 2:Health ENS O
_:212:55 Stage 2:Pickup ACD O
_:212:56 Stage 2:Operate delay expired ACT O
_:212:57 Stage 2:Operate ACT O

790 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.27 Overvoltage Protection with Negative-Sequence Voltage

6.27 Overvoltage Protection with Negative-Sequence Voltage

6.27.1 Overview of Functions

The function Overvoltage protection with negative-sequence voltage (ANSI 47) is used to:

• Monitor the power system and electric machines for voltage unbalances

• Establish a release criterion of overcurrent protection for unbalanced faults


Voltage unbalances can be caused by various factors:

• The most common cause is unbalanced load, caused by different consumers in the individual phases, for
example.

• Voltage unbalance can also be caused by phase failure, for example due to a tripped 1-phase fuse, a
broken conductor, etc.

• Other causes can include faults in the primary system, for example, at the transformer or in installations
for reactive-power compensation.

6.27.2 Structure of the Function

The Overvoltage protection with negative-sequence voltage function is used in protection function groups,
which are based on voltage measurement.
The Overvoltage protection with negative-sequence voltage function comes factory-set with 2 stages.
A maximum of 3 stages can be operated simultaneously in the function.
The stages have an identical structure.

[dwu2ovpsExt.vsd, 2, en_US]

Figure 6-196 Structure/Embedding of the Function

6.27.3 General Functionality

6.27.3.1 Description

Logic
The following figure represents the logic of the average-value calculation of the negative-sequence voltage.
The average value is forwarded to all subordinate stages.

SIPROTEC 5, 7SJ82/7SJ85, Manual 791


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.27 Overvoltage Protection with Negative-Sequence Voltage

[lo_GeneralFunctionality_20150323, 1, en_US]

Figure 6-197 Logic Diagram of the General Functionality

Measurand
The average value of negative-sequence voltage is determined by a settable time interval (parameter: Meas-
uring window). With the parameter Measuring window, you can adapt this function to all power-system
conditions.
You can set the parameter Measuring window with a large value to get a more accurate calculated result,
which leads to a longer pickup time however.

Blocking the Function with Measuring-Voltage Failure Detection


In case of blocking, the picked up function is reset. The following blocking options is available for the function:

• From inside on pick up of the Measuring-voltage failure detection function (see section 9.3.2.1 Over-
view of Functions).

• From an external source via the binary input signal >Open of the function block Volt.-transf. c. b., which
links in the tripping of the voltage-transformer circuit breaker.
The parameter Blk. by meas.-volt. failure can be set so that the measuring-voltage failure detection
blocks the function or does not block it.

6.27.3.2 Application and Setting Notes

Parameter: Measuring window

• Default setting (_:2311:101) Measuring window = 1 cycle


With the parameter Measuring window, you can optimize the measuring accuracy or the pickup time
of this function.
For sensitive settings of the parameter Threshold, for example, lower than 10 % of the rated voltage,
Siemens recommends using a higher number of cycles. Siemens recommends 10 cycles, and in this
case, the pickup time is increased.
For further information, refer to chapter 12.35 Overvoltage Protection with Negative-Sequence Voltage .

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:2311:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the function when a
measuring-voltage failure is detected.

792 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.27 Overvoltage Protection with Negative-Sequence Voltage

A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


switched on.

• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 9.3.4.1 Overview of Functions).

Parameter Value Description


yes The protection function is blocked (= default setting). Siemens recommends
using the default setting.
no The protection function is not blocked.

6.27.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:10 General:Blk. by meas.- • no yes
volt. failure
• yes
_:2311:101 General:Measuring 1 cycles to 10 cycles 1 cycles
window

6.27.3.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:301 General:V2 average MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 793


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.27 Overvoltage Protection with Negative-Sequence Voltage

6.27.4 Stage with Negative-Sequence Voltage

6.27.4.1 Description

Logic of a Stage

[lou23pol-090611-01.tif, 3, en_US]

Figure 6-198 Logic Diagram of the Stage: Overvoltage Protection with Negative-Sequence Voltage

Method of Measurement
The stage uses the average value of the negative-sequence voltage, which is calculated from the function
block General Functionality. For more information, refer to chapter 6.27.3.1 Description.

Blocking the Stage


In case of blocking, the picked up function is reset. The following blocking option is available for the function:

• From an external or internal source via the binary input signal >Block stage

6.27.4.2 Application and Setting Notes

Parameter: Threshold

• Default setting (_:271:3) Threshold = 5.800 V


The parameter Threshold is set according to the definition of the negative-sequence system.
Specify the Threshold (pickup threshold) for the specific application.
The secondary voltage of the voltage transformer can be used if the voltage transformer is adapted to the
rated voltage. The value of the 10 % negative-sequence voltage at a 100 V rated secondary voltage is:
100 V / 1.73 * 0.1 = 5.77 V

794 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.27 Overvoltage Protection with Negative-Sequence Voltage

Parameter: Dropout ratio

• Default setting (_:271:4) Dropout ratio = 0.95


The default setting of 0.95 is appropriate for most applications.
You can decrease the dropout ratio to avoid chattering of the stage if the threshold value is low. For example,
for the stage with a 2 % setting, you can use a dropout ratio of 0.90.

Parameter: Operate delay

• Default setting (_:271:6) Operate delay = 3.00 s


Specify the Operate delay for the specific application. 3.00 s is a practicable value.
For a higher threshold value, a shorter tripping delay is required.

Operation as Supervision Function


If you want the stage to have a reporting effect only, generation of the operate indication and fault logging
can be disabled via the Operate & flt.rec. blocked parameter.

Example 1:
Releasing an overcurrent protection stage for unbalanced faults
The following section describes how to set the function to release an Overcurrent-protection stage when
unbalanced faults occur. Set the Overcurrent-protection stage only slightly higher than the load current, that
is very sensitive. To prevent the Overcurrent-protection stage from picking up inadvertently, the Overcur-
rent-protection stage is released when the Negative-sequence voltage stage picks up. The Overcurrent-
protection stage remains blocked as long as the Negative-sequence voltage stage has not picked up.
Figure 6-199 shows the voltage phasors during a 2-phase local fault between phases B and C. The phase-to-
phase voltage VBC is virtually 0.

[dwuazeig-020412-01.tif, 1, en_US]

Figure 6-199 Voltage Phasors during a 2-Phase Local Fault

A 2-phase local fault generates a relatively large negative-sequence voltage of up to 50 % referred to the
phase-to-ground voltage. The portion of the negative-sequence decreases in case of a remote fault. The lower
setting limit results from the possible unbalance at full load. If you assume for example 5 % negative-
sequence voltage, the pickup value must be higher. A setting value of 10 % warrants sufficient stability during
unbalanced operating states and sufficient sensitivity to release the Overcurrent-protection stage when a
fault occurs.
For a secondary rated voltage of 100 V, set the following secondary threshold value:

[fo_OVP_V2_Secondary Threshold, 1, en_US]

You can keep the default setting of 0.95 for the dropout ratio. This avoids chattering of the stage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 795


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.27 Overvoltage Protection with Negative-Sequence Voltage

Set the Negative-sequence voltage stage so that it does not generate a fault when it picks up and does not
initiate tripping. The Overcurrent-protection stage generates a fault indication. The pickup of the Negative-
sequence voltage stage is used as the release criterion because the Short-circuit function must be released
immediately when the Negative-sequence voltage stage has picked up. The time delay is thus not relevant
and can be left at the default setting.
You implement the release of the Overcurrent-protection stage using a logic block chart. An inverter links
the pickup of the Negative-sequence voltage stage with the Overcurrent-protection stage blocking.

[loinvert-020412-01.tif, 1, en_US]

Figure 6-200 Linking the Pickup of the Negative-Sequence Voltage Stage

Stage Setting Values


Secondary Threshold Value Time Delay Dropout Ratio
1 5.800 V 3.00 s 0.95

The second stage is not needed. It is deleted or remains off.

Example 2:
A negative-sequence voltage in the auxiliary system of the power plant causes negative-sequence currents on
motors. This leads to a thermal overload of the rotors. The following estimation can be used as a basis: 1 %
negative-sequence voltage can lead to approximately 5 % or 6 % negative-sequence current.
A negative-sequence voltage can be caused by a broken conductor on the high-voltage side. If a negative-
sequence voltage occurs, this can, for example, initiate a switching of the infeed in order to prevent a protec-
tion trip of an unbalanced-load protection of the motors.
Siemens recommends using multiple stages for a better grading, whereby a sensitive setting of the threshold
permits an increased tripping delay.
For a reference, only 2 stages are discussed.
The first stage has a pickup threshold of 10 % with a time delay of 1.5 s. The second stage has a pickup
threshold of 3 % with a time delay of 8 s, see Table 6-14. Further, it is assumed that the voltage transformer is
well adapted to the rated voltage.

[fo_OVP_V2_SecondaryThreshold2, 1, en_US]

Table 6-14 Recommended Settings

Stage Threshold Operate Delay


Stage 1 5.800 V 1.50 s
Stage 2 1.730 V 8.00 s

6.27.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:271:1 Stage 1:Mode • off off
• on
• test
_:271:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes

796 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.27 Overvoltage Protection with Negative-Sequence Voltage

Addr. Parameter C Setting Options Default Setting


_:271:3 Stage 1:Threshold 0.300 V to 200.000 V 5.800 V
_:271:4 Stage 1:Dropout ratio 0.90 to 0.99 0.95
_:271:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
Stage 2
_:272:1 Stage 2:Mode • off off
• on
• test
_:272:2 Stage 2:Operate & • no no
flt.rec. blocked
• yes
_:272:3 Stage 2:Threshold 0.300 V to 200.000 V 9.000 V
_:272:4 Stage 2:Dropout ratio 0.90 to 0.99 0.95
_:272:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s

6.27.4.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:301 General:V2 average MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:271:81 Stage 1:>Block stage SPS I
_:271:54 Stage 1:Inactive SPS O
_:271:52 Stage 1:Behavior ENS O
_:271:53 Stage 1:Health ENS O
_:271:55 Stage 1:Pickup ACD O
_:271:56 Stage 1:Operate delay expired ACT O
_:271:57 Stage 1:Operate ACT O
Stage 2
_:272:81 Stage 2:>Block stage SPS I
_:272:54 Stage 2:Inactive SPS O
_:272:52 Stage 2:Behavior ENS O
_:272:53 Stage 2:Health ENS O
_:272:55 Stage 2:Pickup ACD O
_:272:56 Stage 2:Operate delay expired ACT O
_:272:57 Stage 2:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 797


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.28 Overvoltage Protection with Any Voltage

6.28 Overvoltage Protection with Any Voltage

6.28.1 Overview of Functions

The function Overvoltage protection with any voltage (ANSI 59) detects any 1-phase overvoltages and is
intended for special applications.

6.28.2 Structure of the Function

The Overvoltage protection with any voltage function is used in protection function groups, which are
based on voltage measurement.
The function Overvoltage protection with any voltage comes factory-set with 2 stages. A maximum of 3
tripping stages can be operated simultaneously in the function. The tripping stages have an identical struc-
ture.

[dwovpuxs-030211-01.tif, 1, en_US]

Figure 6-201 Structure/Embedding of the Function

798 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.28 Overvoltage Protection with Any Voltage

6.28.3 Stage Description

Logic of a Stage

[louxovpr-211212-01.tif, 1, en_US]

Figure 6-202 Logic Diagram of a Stage: Overvoltage Protection with Any Voltage

NOTE

i If the function Overvoltage protection with any voltage is used in a 1-phase function group, the param-
eter Measured value is not visible.

Method of Measurement
The Method of measurement parameter allows you to define whether the function works with the funda-
mental component or the calculated RMS value.

• Measurement of the fundamental comp.:


This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.

• Measurement of the parameter value RMS value:


This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Measured Value
The parameter Measured value allows you to select whether the stage uses a measured (directly
connected) voltage or a calculated phase-to-phase voltage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 799


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.28 Overvoltage Protection with Any Voltage

If the function Overvoltage protection with any voltage is used in a 1-phase function group, the parameter
Measured value is not visible.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. Blocking is possible externally or internally via the
binary input signal >Block stage.

6.28.4 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:391:8) Method of measurement = fundamental comp.


Use the Method of measurement parameter to define whether the tripping stage uses the fundamental
component (standard method = default setting) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement to suppress harmonics or transient
voltage peaks.
Siemens recommends this method of measurement as the default setting.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example at capacitor banks). Do not set the threshold
value of the tripping stage under 10 V for this method of measurement.

Parameter: Measured value

• Default setting (_:391:9) Measured value = VA measured


The Measured value parameter is used to specify which voltage is monitored by the stage.
The scope of setting options depends on the connection type for the voltage transformers and the routing of
the measured values to the terminals of the voltage measuring point. You can find connection examples for
voltage transformers in the Appendix.
The following setting options can be available:

• Measured phase-to-ground voltage VA (VA measured)

• Measured phase-to-ground voltage VB (VB measured)

• Measured phase-to-ground voltage VC (VC measured)

• Measured phase-to-phase voltage VAB (VAB measured)

• Measured phase-to-phase voltage VBC (VBC measured)

• Measured phase-to-phase voltage VCA (VCA measured)

• Calculated phase-to-phase voltage VAB (VAB calculated)

• Calculated phase-to-phase voltage VBC (VBC calculated)

• Calculated phase-to-phase voltage VCA (VCA calculated)

• Calculated voltage V0 (V0 calculated)


The selection depends on the corresponding application.

800 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.28 Overvoltage Protection with Any Voltage

NOTE

i From V7.30 on, the value VN measured is no longer provided. If you have selected this value in earlier
versions, you can use either the following methods instead after upgrading the configuration to V7.30 or a
later version:

• Select the value V0 calculated for the Measured value parameter in the function Overvoltage
protection with any voltage.

• Use the function Overvoltage protection with zero-sequence voltage/residual voltage.


If the function Overvoltage protection with any voltage is used in a 1-phase function group, the param-
eter Measured value is not visible.

Parameter: Threshold

• Default setting (_:391:3) Threshold = 110 V


Specify the Threshold (pickup threshold) for the specific application.
Depending on the measured value, the Threshold is set either as Measured voltage or as Phase-to-
phase quantity.

NOTE

i If the function is used in a Voltage-current 1-phase function group connected to the 1-phase voltage
measuring point with the voltage type VN broken-delta, you set the threshold value based on the
equivalent zero-sequence voltage.
Calculate the equivalent zero-sequence voltage V0 equiv. sec from the measured voltage VN sec with the
following formula:

You can find more information about the Matching ratio Vph / VN parameter in chapter 6.1.6 Appli-
cation and Setting Notes for Measuring Point Voltage 3‑Phase (V-3ph).

Parameter: Operate delay

• Default setting (_:391:6) Operate delay = 3 s


The Operate delay must be set for the specific application.

Parameter: Dropout ratio

• Recommended setting value (_:391:4) Dropout ratio = 0.95


The recommended set value of 0.95 is appropriate for most applications. To achieve high measurement preci-
sion, the Dropout ratio can be reduced, to 0.98, for example.

Operation as Supervision Function


If you want the tripping stage to have a reporting effect only, generation of the operate indication and fault
logging can be disabled via the Operate & flt.rec. blocked parameter.

SIPROTEC 5, 7SJ82/7SJ85, Manual 801


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.28 Overvoltage Protection with Any Voltage

6.28.5 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:391:1 Stage 1:Mode • off off
• on
• test
_:391:2 Stage 1:Operate & flt.rec. • no no
blocked
• yes
_:391:9 Stage 1:Measured value • VA measured VA measured
• VB measured
• VC measured
• VAB calculated
• VBC calculated
• VCA calculated
• V0 calculated
_:391:8 Stage 1:Method of measure- • fundamental comp. fundamental
ment comp.
• RMS value
_:391:3 Stage 1:Threshold 0.300 V to 340.000 V 110.000 V
_:391:4 Stage 1:Dropout ratio 0.90 to 0.99 0.95
_:391:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
Stage 2
_:392:1 Stage 2:Mode • off off
• on
• test
_:392:2 Stage 2:Operate & flt.rec. • no no
blocked
• yes
_:392:9 Stage 2:Measured value • VA measured VA measured
• VB measured
• VC measured
• VAB measured
• VBC measured
• VCA measured
• VAB calculated
• VBC calculated
• VCA calculated
• V0 calculated
_:392:8 Stage 2:Method of measure- • fundamental comp. fundamental
ment comp.
• RMS value
_:392:3 Stage 2:Threshold 0.300 V to 340.000 V 130.000 V
_:392:4 Stage 2:Dropout ratio 0.90 to 0.99 0.95
_:392:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s

802 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.28 Overvoltage Protection with Any Voltage

6.28.6 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:391:81 Stage 1:>Block stage SPS I
_:391:54 Stage 1:Inactive SPS O
_:391:52 Stage 1:Behavior ENS O
_:391:53 Stage 1:Health ENS O
_:391:55 Stage 1:Pickup ACD O
_:391:56 Stage 1:Operate delay expired ACT O
_:391:57 Stage 1:Operate ACT O
Stage 2
_:392:81 Stage 2:>Block stage SPS I
_:392:54 Stage 2:Inactive SPS O
_:392:52 Stage 2:Behavior ENS O
_:392:53 Stage 2:Health ENS O
_:392:55 Stage 2:Pickup ACD O
_:392:56 Stage 2:Operate delay expired ACT O
_:392:57 Stage 2:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 803


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage

6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-


Sequence Voltage

6.29.1 Overview of Functions

The function Overvoltage protection with negative-sequence voltage/positive-sequence voltage is used


to:

• Monitor the power system and electric machines for voltage unbalances

• Establish a release criterion of overcurrent protection for unbalanced faults


Voltage unbalances can be caused by various factors:

• The most common cause is unbalanced load, caused by different consumers in the individual phases, for
example.

• Voltage unbalance can also be caused by phase failure, for example due to a tripped 1-phase fuse, a
broken conductor, etc.

• Other causes can include faults in the primary system, for example, at the transformer or in installations
for reactive-power compensation.

6.29.2 Structure of the Function

The Overvoltage protection with negative-sequence voltage/positive-sequence voltage function is used


in protection function groups, which are based on voltage measurement.
The Overvoltage protection with negative-sequence voltage/positive-sequence voltage function comes
factory-set with 2 stages. A maximum of 3 stages can be operated simultaneously in the function. The stages
have an identical structure.

[Structure-V2/V1_20150521, 2, en_US]

Figure 6-203 Structure/Embedding of the Function

6.29.3 General Functionality

6.29.3.1 Description

Logic
The following figure represents the logic of the average-value calculation of the ratio of negative-sequence
voltage to positive-sequence voltage. The average value is forwarded to all subordinate stages.

804 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage

[lo_V2toV1_FB General_20150326, 1, en_US]

Figure 6-204 Logic Diagram of the General Functionality

Measurand
The average value of the ratio of negative-sequence voltage to positive-sequence voltage is determined by a
settable time interval (parameter: Measuring window). With the parameter Measuring window, you can
adapt this function to all power-system conditions.
You can set the parameter Measuring window with a large value to get a more accurate calculated result,
which leads to a longer pickup time however.

Blocking the Function with Measuring-Voltage Failure Detection


In case of blocking, the picked up function is reset. The following blocking options is available for the function:

• From inside on pick up of the Measuring-voltage failure detection function (see section 9.3.2.1 Over-
view of Functions).

• From an external source via the binary input signal >Open of the function block Volt.-transf. c. b., which
links in the tripping of the voltage-transformer circuit breaker.
The parameter Blk. by meas.-volt. failure can be set so that the measuring-voltage failure detection
blocks the function or does not block it.

6.29.3.2 Application and Setting Notes

Parameter: Measuring window

• Default setting (_:2311:102) Measuring window = 1 cycle


With the parameter Measuring window, you can optimize the measuring accuracy or the pickup time
of this function.
For sensitive settings of the parameter Threshold, for example, lower than 10 % of the rated voltage,
Siemens recommends using a higher number of cycles. Siemens recommends 10 cycles, and in this
case, the pickup time is increased.
For further information, refer to chapter 12.38 Overvoltage Protection with Negative-Sequence Voltage/
Positive-Sequence Voltage .

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:2311:10) Blk. by meas.-volt. failure = yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 805


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage

You use the Blk. by meas.-volt. failure parameter to control the behavior of the function when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


switched on.

• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 9.3.4.1 Overview of Functions).

Parameter Value Description


yes The protection function is blocked (= default setting). Siemens recommends
using the default setting.
no The protection function is not blocked.

6.29.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:10 General:Blk. by meas.- • no yes
volt. failure
• yes
_:2311:102 General:Measuring 1 cycles to 10 cycles 1 cycles
window
_:2311:101 General:Minimum 0.300 V to 60.000 V 5.000 V
voltage V1

6.29.3.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:300 General:Undervoltage blocking SPS O
_:2311:301 General:V2/V1 MV O

806 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage

6.29.4 Stage with Negative-Sequence Voltage/Positive-Sequence Voltage

6.29.4.1 Description

Logic of a Stage

[lo_V2V1_PROV_20150326, 1, en_US]

Figure 6-205 Logic Diagram of the Stage: Overvoltage Protection with Negative-Sequence Voltage/Positive-
Sequence Voltage

Method of Measurement
The stage uses the average value of the negative-sequence voltage/positive-sequence voltage, which is calcu-
lated from the function block General Functionality. For more information, refer to chapter 6.29.3.1 Descrip-
tion.

Blocking the Stage


In case of blocking, the picked up function is reset. The following blocking option is available for the function:

• From an external or internal source via the binary input signal >Block stage

6.29.4.2 Application and Setting Notes

Parameter: Threshold

• Default setting (_:17071:3) Threshold = 10.00 %


The parameter Threshold is set in percentage according to the definition of the symmetrical compents. It is
the ratio of the negative-sequence voltage to positive-sequence voltage.
Specify the Threshold (pickup threshold) for the specific application.

SIPROTEC 5, 7SJ82/7SJ85, Manual 807


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage

In the application with a lower threshold setting of about 2.00 %, there is a risk of an overfunction due to the
measuring errors with small values as well as an influence via disturbances.

Parameter: Dropout ratio

• Default setting (_:17071:4) Dropout ratio = 0.95


The default setting of 0.95 is appropriate for most applications if a higher threshold is used.
You can decrease the dropout ratio to avoid chattering of the stage if the threshold value is low. For example,
for the stage with a 2 % setting, you can use a dropout ratio of 0.90.

Parameter: Operate delay

• Default setting (_:17071:6) Operate delay = 3.00 s


Specify the Operate delay for the specific application. When using the sensitive setting of the threshold
value that is described in this chapter, the function can be delayed by 3.00 s.
For a higher threshold value, a shorter tripping delay is required.

Operation as Supervision Function


If you want the stage to have a reporting effect only, generation of the operate indication and fault logging
can be disabled via the Operate & flt.rec. blocked parameter.

Example 1:
Releasing an overcurrent protection stage for unbalanced faults
The following section describes how to set the function to release an Overcurrent-protection stage when
unbalanced faults occur. Set the Overcurrent-protection stage only slightly higher than the load current, that
is very sensitive. To prevent the Overcurrent-protection stage from picking up inadvertently, the Overcur-
rent-protection stage is released when the Negative-sequence voltage stage picks up. The Overcurrent-
Protection stage remains blocked as long as the Negative-sequence voltage stage has not picked up.
Figure 6-206 shows the voltage phasors during a 2-phase local fault between phases B and C. The phase-to-
phase voltage VBC is virtually 0.

[dwuazeig-020412-01.tif, 1, en_US]

Figure 6-206 Voltage Phasors during a 2-Phase Local Fault

A 2-phase local fault generates a relatively large negative-sequence voltage of up to 100 % referred to the
positive-sequence voltage. The portion of the negative-sequence decreases in case of a remote fault. The
lower setting limit results from the possible unbalance at full load. If you assume for example 5 % of the nega-
tive-sequence voltage to positive-sequence voltage, the pickup value must be higher. A setting value of 10 %
warrants sufficient stability during unbalanced operating states and sufficient sensitivity to release the Over-
current-protection stage when a fault occurs.
You can keep the default setting of 0.95 for the dropout ratio. This avoids chattering of the stage.
Set the Negative-sequence voltage stage so that it does not generate a fault when it picks up and does not
initiate tripping. The Overcurrent-protection stage generates a fault indication. The pickup of the Negative-
sequence voltage stage is used as the release criterion because the Short-circuit function must be released

808 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage

immediately when the Negative-sequence voltage stage has picked up. The time delay is thus not relevant
and can be left at the default setting.
You implement the release of the Overcurrent-protection stage using a logic block chart. An inverter links
the pickup of the Negative-sequence voltage stage with the Overcurrent-protection stage blocking.

[lo_Pickup of V2_20150507, 1, en_US]

Figure 6-207 Linking the Pickup of the Negative-Sequence Voltage Stage

Stage Setting Values


Percentage of the Negative- Time Delay Dropout Ratio
Sequence Voltage to Positive-
Sequence Voltage
1 10.00 % 3.00 s 0.95

The second stage is not needed. It is deleted or remains off.

Example 2:
A negative-sequence voltage in the auxiliary system of the power plant causes negative-sequence currents on
motors. This leads to a thermal overload of the rotors. The following estimation can be used as a basis: 1 %
negative-sequence voltage can lead to approximately 5 % or 6 % negative-sequence current.
A negative-sequence voltage can be caused by a broken conductor on the high-voltage side. If a negative-
sequence voltage occurs, this can, for example, initiate a switching of the infeed in order to prevent a protec-
tion trip of an unbalanced-load protection of the motors.
Siemens recommends using multiple stages for a better grading, whereby a sensitive setting of the threshold
permits an increased tripping delay.
For a reference, only 2 stages are discussed.
The first stage has a pickup threshold of 10 % with a time delay of 1.5 s. The second stage has a pickup
threshold of 3 % with a time delay of 8 s, seeTable 6-15.

Table 6-15 Recommended Settings

Stage Threshold Operate Delay


Stage 1 10.00 % 1.50 s
Stage 2 3.00 % 8.00 s

6.29.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:17071:1 Stage 1:Mode • off off
• on
• test
_:17071:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:17071:3 Stage 1:Threshold 0.50 % to 100.00 % 10.00 %
_:17071:4 Stage 1:Dropout ratio 0.90 to 0.99 0.95
_:17071:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s

SIPROTEC 5, 7SJ82/7SJ85, Manual 809


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.29 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage

Addr. Parameter C Setting Options Default Setting


Stage 2
_:17072:1 Stage 2:Mode • off off
• on
• test
_:17072:2 Stage 2:Operate & • no no
flt.rec. blocked
• yes
_:17072:3 Stage 2:Threshold 0.50 % to 100.00 % 15.00 %
_:17072:4 Stage 2:Dropout ratio 0.90 to 0.99 0.95
_:17072:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s

6.29.4.4 Information List

No. Information Data Class Type


(Type)
Stage 1
_:17071:81 Stage 1:>Block stage SPS I
_:17071:54 Stage 1:Inactive SPS O
_:17071:52 Stage 1:Behavior ENS O
_:17071:53 Stage 1:Health ENS O
_:17071:55 Stage 1:Pickup ACD O
_:17071:56 Stage 1:Operate delay expired ACT O
_:17071:57 Stage 1:Operate ACT O
Stage 2
_:17072:81 Stage 2:>Block stage SPS I
_:17072:54 Stage 2:Inactive SPS O
_:17072:52 Stage 2:Behavior ENS O
_:17072:53 Stage 2:Health ENS O
_:17072:55 Stage 2:Pickup ACD O
_:17072:56 Stage 2:Operate delay expired ACT O
_:17072:57 Stage 2:Operate ACT O

810 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

6.30 Undervoltage Protection with 3-Phase Voltage

6.30.1 Overview of Functions

The function Undervoltage protection with 3-phase voltage (ANSI 27):

• Monitors the permissible voltage range

• Protects equipment (for example, plant components and machines) against damages caused by under-
voltage

• Handles disconnection or load shedding tasks in a system

6.30.2 Structure of the Function

The function Undervoltage protection with 3-phase voltage is used in protection function groups with
voltage measurement.
The function Undervoltage protection with 3-phase voltage comes factory-set with 2 Definite-time under-
voltage protection stages.
In the function Undervoltage protection with 3-phase voltage, the following stages can be operated simul-
taneously:

• 3 stages Definite-time undervoltage protection

• 2 stages Inverse-time undervoltage protection


Stages that are not preconfigured are shown in gray in the following figure.
The protection function is structured such that one current-flow criterion can act on all undervoltage protec-
tion stages (see Figure 6-208). If the protection function group used has no current measurement, you can
only set the current-flow criterion as fulfilled via the corresponding binary input signal.

[dwstru3p-110211-01.tif, 5, en_US]

Figure 6-208 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 811


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

6.30.3 Stage with Definite-Time Characteristic Curve

6.30.3.1 Description

Logic of the Stage

[louvp3ph-140611-01_stagecontrol.vsd, 3, en_US]

Figure 6-209 Logic Diagram of the Stage Control

812 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

[louvp3ph-140611-01.tif, 3, en_US]

Figure 6-210 Logic Diagram of the Definite-Time Undervoltage Protection with 3-Phase Voltage

Method of Measurement
With the Method of measurement parameter, you select the relevant method of measurement, depending
on the application.

• Measurement fundamental component:


This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.

• Measurement RMS value:


This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Measured Value
With the Measured value parameter, you define whether the stage analyzes the phase-to-phase voltages
VAB, VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.

Pickup Stabilization
To enable the pickup stabilization, you set the Stabilization counter parameter to a value other than
zero. Then, if the input voltage keeps being below the Threshold for a specified number (1 + Stabiliza-

SIPROTEC 5, 7SJ82/7SJ85, Manual 813


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

tion counter value) of successive measuring cycles, the stage picks up. For 50 Hz, the measuring cycle
time is 10 ms.
If you set this parameter to 0 (default value), the stabilization is not applied. The pickup signal is issued after
the input voltage falls below the Threshold.

Pickup Mode
With the Pickup mode parameter, you define whether the stage picks up when there is a lower threshold-
value violation in one measuring element (1 out of 3) or when there is a lower threshold-value violation in
all 3 measuring elements (3 out of 3).

Pickup Delay
The Pickup delay parameter is only available and of relevance if you are using the current-flow criterion of
the function (parameter Current-flow criterion = on).
If the circuit breaker opens when the current-flow criterion is being used, the undervoltage detection and
current-flow dropout functions conflict with one another. Depending on the threshold value settings for
undervoltage detection and current-flow criterion, it is possible that the undervoltage is detected before the
current-flow criterion has dropped out. In this case, the stage picks up briefly. Use the Pickup delay param-
eter to prevent the stage from briefly picking up in this way when the circuit breaker opens. This is achieved
by delaying the pickup by approximately 40 ms.

Current-Flow Criterion
The undervoltage protection stages work optionally with a current-flow criterion. The Current-flow
criterion works across all tripping stages.
When the Current-flow criterion parameter is activated, the undervoltage protection stages only pick
up if a settable minimum current (Threshold I>) is exceeded. A current below the minimum current blocks
the stages.
The current-flow criterion can also be set to fulfilled with the binary input signal >Current flow-crite-
rion. The function reports when the current-flow criterion is fulfilled.
Figure 6-210 illustrates the influence of the current-flow criterion.

NOTE

i If the (_:2311:104) Current-flow criterion parameter is deactivated, the device picks up imme-
diately if a missing measuring voltage is detected while the undervoltage protection is active. The param-
eter setting can be changed even when the device has picked up.

Blocking the Stage


In the event of blocking, the picked-up stage will be reset. The following blocking options are available for the
stage:

• Via the binary input signal >Block stage from an external or internal source

• From inside on pickup of the Measuring-voltage failure detection function (see section 9.3.2.1 Over-
view of Functions). The Blk. by meas.-volt. failure parameter can be set so that measuring-
voltage failure detection blocks the stage or does not block it.

• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker. The Blk. by meas.-volt.
failure parameter can be set so that measuring-voltage failure detection blocks the stage or does not
block it.

6.30.3.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:421:8) Method of measurement = fundamental comp.

814 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

With the Method of measurement parameter, you define whether the stage uses the fundamental compo-
nent (standard method = default setting) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement to suppress harmonics or transient
voltage peaks.
Siemens recommends using this parameter value as the default setting.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example at capacitor banks). Do not set the threshold
value of the stage under 10 V for this method of measurement.

Parameter: Measured value

• Recommended setting value (_:421:9) Measured value = phase-to-phase


With the Measured value parameter, you define whether the stage monitors the phase-to-phase voltages
VAB, VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC. Parameter Value

Parameter Value Description


phase-to-phase If you want to detect voltage dips caused by multiphase short circuits, or
generally monitor the voltage range, keep phase-to-phase as the default
setting. The function will not pick up on ground faults.
Siemens recommends the measured value phase-to-phase as the
default setting.
phase-to-ground Select the phase-to-ground setting if you want to detect voltage unbal-
ances or overvoltage conditions caused by ground faults.

Parameter: Threshold

• Default setting (_:421:3) Threshold = 80 V


The Threshold is set in accordance with the Measured value as either a phase-to-phase or phase-
to-ground variable.
Specify the Threshold (pickup threshold) for the specific application.
For the default setting, the lower limit of the voltage range to be monitored is assumed to be 80 % of the
rated voltage of the protected object.

EXAMPLE:

Rated voltage of the protected object: Vrated, obj.= 10 kV


Voltage transformer:

Threshold value: 80 % of Vrated, obj.

The secondary setting value is calculated as follows:

[foschwlw-190309-01.tif, 2, en_US]

Parameter: Stabilization counter

• Default setting (_:2311:103) Stabilization counter = 0


You can configure the Stabilization counter parameter in the function block General.
For special applications, it could be desirable that a short falling of the input voltage below the pickup value
does not lead to the pickup of the stage, which starts fault logging and recording. This is achieved by setting
the Stabilization counter parameter to a value other than zero.

SIPROTEC 5, 7SJ82/7SJ85, Manual 815


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

For example, if you set this parameter to 1, the pickup signal is issued when the voltage keeps being below
the Threshold for 2 successive measuring cycles. For 50 Hz, the measuring cycle time is 10 ms.

Parameter: Pickup mode

• Recommended setting value (_:421:101) Pickup mode = 1 out of 3


With the Pickup mode parameter, you specify whether the stage picks up when there is a lower threshold-
value violation in one measuring element (1 out of 3) or when there is a lower threshold-value violation in
all 3 measuring elements (3 out of 3).
Parameter Value Description
1 out of 3 Use this setting for protection applications or for monitoring the voltage
range.
Siemens recommends 1 out of 3 as the default setting. This reflects how
the function behaved in previous generations (SIPROTEC 4, SIPROTEC 3).
3 out of 3 Select this setting when using the stage to disconnect from the power
system (in the case of wind farms, for example).

Parameter: Pickup delay

• Default setting (_:421:102) Pickup delay = no


The Pickup delay parameter is only available if you are using the current-flow criterion of the function
(parameter Current-flow criterion = on). If the current-flow criterion is deactivated, no pickup delay is
required.
With the Pickup delay parameter, you set whether pickup of the stage is to be delayed by approximately
40 ms or not. The delay avoids possible brief pickup of the stage when the circuit breaker opens.
When applied in parallel, the pickup delay and the delay through pickup stabilization add up.
Parameter Value Description
no Use this setting if you definitely do not want stage pickup to be subject to a
time delay in the event of a fault. This setting results in pickup and, where
applicable, tripping being performed as quickly as possible.
Note that switching procedures (opening of the CB) can result in brief
pickup of the stage, depending on the threshold-value settings for under-
voltage pickup and the current-flow criterion. To prevent unwanted trip-
ping, you must set a minimum tripping delay of 50 ms.
yes Use this setting when switching procedures (opening of the CB) are not
permitted to result in stage pickup.
Note that pickup is delayed by approximately 40 ms. This delay is added to
the operate time.

Parameter: Operate delay

• Default (_:421:6) Operate delay = 3 s


The Operate delay must be set for the specific application.

Parameter: Dropout ratio

• Recommended setting value (_:421:4) Dropout ratio = 1.05


The recommended setting value of 1.05 is appropriate for most applications. To achieve high-precision meas-
urements, the Dropout ratio can be reduced (to 1.02, for example).

Parameter: Blk. by meas.-volt. failure

• Default setting (_:421:10) Blk. by meas.-volt. failure = yes

816 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

With the Blk. by meas.-volt. failure parameter, you control the behavior of the stage when a meas-
uring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following two conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


switched on.

• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see Chapter 9.3.4.1 Overview of Functions).

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

Parameter: Current-flow criterion

• Recommended setting value (_:2311:104) Current-flow criterion = on


Depending on the system, the voltage transformers are arranged on either the supply side or the junction side.
These 2 possible voltage transformer locations induce a different behavior of the function after tripping and
opening of the circuit breaker:

• If they are located on the supply side, the voltage still exists.

• If they are located on the junction side, the voltage does not exist.

Parameter Value Description


on If the voltage transformers are located on the junction side, you can use the
current-flow criterion to make the pickup drops out when the current falls
below a minimum value (parameter Threshold I>).
off In the case of undervoltage, the pickup of the undervoltage protection
stage persists when the current-flow criterion is not used.

Parameter: Threshold I>

• Recommended setting value (_:2311:101) Threshold I> = 0.05 A


The Threshold I> parameter makes it possible to detect when the circuit breaker is closed. Siemens recom-
mends setting the Threshold I> parameter to 5% of the rated current. With a secondary rated transformer
current of 1 A, the secondary setting value for Threshold I> would be 0.05 A.
If the sensitivity of the Threshold I> parameter is set too high, compensation processes in the secondary
circuit of the current transformer extend the dropout time when breaking extremely high currents. To speed
up dropout, increase the default setting.

Operation as Supervision Function


If you want the stage to have a reporting effect only, generation of the operate indication and fault logging
can be disabled via the Operate & flt.rec. blocked parameter.

6.30.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:104 General:Current-flow • off on
criterion
• on

SIPROTEC 5, 7SJ82/7SJ85, Manual 817


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

Addr. Parameter C Setting Options Default Setting


_:2311:101 General:Threshold I> 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:2311:103 General:Stabilization 0 to 10 0
counter
Definite-T 1
_:421:1 Definite-T 1:Mode • off off
• on
• test
_:421:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:421:10 Definite-T 1:Blk. by • no yes
meas.-volt. failure
• yes
_:421:9 Definite-T 1:Measured • phase-to-ground phase-to-phase
value
• phase-to-phase
_:421:8 Definite-T 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:421:101 Definite-T 1:Pickup mode • 1 out of 3 1 out of 3
• 3 out of 3
_:421:102 Definite-T 1:Pickup delay • no no
• yes
_:421:3 Definite-T 1:Threshold 0.300 V to 175.000 V 80.000 V
_:421:4 Definite-T 1:Dropout 1.01 to 1.20 1.05
ratio
_:421:6 Definite-T 1:Operate 0.00 s to 60.00 s 3.00 s
delay
Definite-T 2
_:422:1 Definite-T 2:Mode • off off
• on
• test
_:422:2 Definite-T 2:Operate & • no no
flt.rec. blocked
• yes
_:422:10 Definite-T 2:Blk. by • no yes
meas.-volt. failure
• yes
_:422:9 Definite-T 2:Measured • phase-to-ground phase-to-phase
value
• phase-to-phase
_:422:8 Definite-T 2:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:422:101 Definite-T 2:Pickup mode • 1 out of 3 1 out of 3
• 3 out of 3
_:422:102 Definite-T 2:Pickup delay • no no
• yes
_:422:3 Definite-T 2:Threshold 0.300 V to 175.000 V 65.000 V

818 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

Addr. Parameter C Setting Options Default Setting


_:422:4 Definite-T 2:Dropout 1.01 to 1.20 1.05
ratio
_:422:6 Definite-T 2:Operate 0.00 s to 60.00 s 0.50 s
delay

6.30.3.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:500 General:>Current flow-criterion SPS I
_:2311:300 General:Current crit. fulf. SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:421:81 Definite-T 1:>Block stage SPS I
_:421:54 Definite-T 1:Inactive SPS O
_:421:52 Definite-T 1:Behavior ENS O
_:421:53 Definite-T 1:Health ENS O
_:421:55 Definite-T 1:Pickup ACD O
_:421:300 Definite-T 1:Pickup loop AB SPS O
_:421:301 Definite-T 1:Pickup loop BC SPS O
_:421:302 Definite-T 1:Pickup loop CA SPS O
_:421:56 Definite-T 1:Operate delay expired ACT O
_:421:57 Definite-T 1:Operate ACT O
Definite-T 2
_:422:81 Definite-T 2:>Block stage SPS I
_:422:54 Definite-T 2:Inactive SPS O
_:422:52 Definite-T 2:Behavior ENS O
_:422:53 Definite-T 2:Health ENS O
_:422:55 Definite-T 2:Pickup ACD O
_:422:300 Definite-T 2:Pickup loop AB SPS O
_:422:301 Definite-T 2:Pickup loop BC SPS O
_:422:302 Definite-T 2:Pickup loop CA SPS O
_:422:56 Definite-T 2:Operate delay expired ACT O
_:422:57 Definite-T 2:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 819


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

6.30.4 Stage with Inverse-Time Characteristic Curve

6.30.4.1 Description

Logic of the Stage

[lo_UVP3ph_In_StageControl, 3, en_US]

Figure 6-211 Logic Diagram of the Stage Control

820 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

[lo_UVP3ph_In, 5, en_US]

Figure 6-212 Logic Diagram of the Inverse-Time Undervoltage Protection with 3-Phase Voltage

Method of Measurement
With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. or the RMS value.

• Measurement fundamental comp.:


This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.

• Measurement RMS value:


This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

Measured Value
With the Measured value parameter, you define whether the stage analyzes the phase-to-phase voltages
VAB, VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.

SIPROTEC 5, 7SJ82/7SJ85, Manual 821


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

Pickup Stabilization
To enable the pickup stabilization, you set the Stabilization counter parameter to a value other than
zero. Then, if the input voltage keeps being below the pickup value for a specified number (1 + Stabiliza-
tion counter value) of successive measuring cycles, the stage picks up. For 50 Hz, the measuring cycle
time is 10 ms.
If you set this parameter to 0 (default value), the stabilization is not applied. The pickup signal is issued after
the input voltage falls below the pickup value.

Pickup Mode
With the Pickup mode parameter, you define whether the stage picks up when there is a lower threshold-
value violation in one measuring element (1 out of 3) or when there is a lower threshold-value violation in
all 3 measuring elements (3 out of 3).

Pickup and Operate Curve


When the input voltage falls below the threshold value by a settable value Pickup factor, the stage picks
up and the inverse-time characteristic curve is processed. The operate delay starts. The operate delay is the
sum of inverse-time delay and additional time delay.
Top=TInv+ Tadd
Where:
Top Operate delay
TInv Inverse-time delay
Tadd Additional time delay (Parameter Additional time delay)

After pickup the time value TInv is calculated for every input voltage less than the dropout value. An integrator
accumulates the value 1/TInv. Once the accumulated integral reaches the fixed value 1, the inverse-time delay
expires. The stage operates after the additional time delay.
The inverse-time delay is calculated with the following formula:

[fo_UVP3ph_inverse, 2, en_US]

Where
TInv Inverse-time delay
Tp Time multiplier (Parameter Time dial)
V Measured undervoltage
VThresh Threshold value (Parameter Threshold)
k Curve constant k (Parameter Charact. constant k)
α Curve constant α (Parameter Charact. constant α)
c Curve constant c (Parameter Charact. constant c)

822 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

The inverse-time characteristic is shown in the following figure:

[dwUVP3ph_inverse, 1, en_US]

Figure 6-213 Inverse-Time Characteristics for Undervoltage Protection

Pickup Delay
The Pickup delay parameter is only available and of relevance if you are using the current-flow criterion of
the function (parameter Current-flow criterion = on).
If the circuit breaker opens when the current-flow criterion is being used, the undervoltage detection and
current-flow dropout functions conflict with one another. Depending on the threshold value settings for
undervoltage detection and current-flow criterion, it is possible that the undervoltage is detected before the
current-flow criterion has dropped out. In this case, the stage picks up briefly. Use the Pickup delay
parameter to prevent the stage from briefly picking up in this way when the circuit breaker opens. This is
achieved by delaying the pickup by approximately 40 ms.

Dropout Behavior
When the voltage exceeds the dropout value (1.05 x pickup factor x threshold value), the pickup signal is
going and the dropout is started. You can define the dropout behavior via parameter Reset time. Instanta-
neous reset takes place by setting Reset time to 0 s. A delayed reset takes place by setting the desired delay
time.
During the Reset time (> 0 s), the elapsed operate delay is frozen. If the stage picks up again within this
period, the stage operates when the rest of operate delay expires.

Current-Flow Criterion
The undervoltage protection stages work optionally with a current-flow criterion. The Current-flow
criterion works across all tripping stages.
When the Current-flow criterion parameter is activated, the undervoltage-protection stages only pick
up if a settable minimum current (Threshold I>) is exceeded. A current below the minimum current blocks
the stages.
The current-flow criterion can also be set to fulfilled with the binary input signal >Current flow-crite-
rion. The function reports when the current-flow criterion is fulfilled.
Figure 6-210 illustrates the influence of the current-flow criterion.

SIPROTEC 5, 7SJ82/7SJ85, Manual 823


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

NOTE

i If the (_:2311:104) Current-flow criterion parameter is deactivated, the device picks up imme-
diately if a missing measuring voltage is detected while the undervoltage protection is active. The param-
eter setting can be changed even when the device has picked up.

Blocking the Stage


In the event of blocking, the picked-up stage is reset. The following blocking options are available for the
stage:

• Via the binary input signal >Block stage from an external or internal source

• From inside on pickup of the Measuring-voltage failure detection function (see chapter 9.3.2.1 Over-
view of Functions) . The Blk. by meas.-volt. failure parameter can be set so that measuring-
voltage failure detection blocks the stage or does not block it.

• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker. The Blk. by meas.-volt.
failure parameter can be set so that measuring-voltage failure detection blocks the stage or does not
block it.

6.30.4.2 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:8) Method of measurement = fundamental comp.


With the Method of measurement parameter, you define whether the stage uses the fundamental compo-
nent (standard method = default setting) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement to suppress harmonics or transient
voltage peaks.
Siemens recommends using this parameter value as the default setting.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Do not set the threshold
value of the stage under 10 V for this method of measurement.

Parameter: Measured value

• Recommended setting value (_:9) Measured value = phase-to-phase


With the Measured value parameter, you define whether the stage monitors the phase-to-phase voltages
VAB, VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.

Parameter Value Description


phase-to-phase If you want to detect voltage dips caused by multiphase short circuits, or
generally monitor the voltage range, keep phase-to-phase as the default
setting. The function will not pick up on ground faults.
Siemens recommends the measured value phase-to-phase as the
default setting.
phase-to-ground Select the phase-to-ground setting if you want to detect voltage unbal-
ances or overvoltage conditions caused by ground faults.

Parameter: Threshold, Pickup factor

• Default setting (_:3) Threshold = 80.000 V

• Default setting (_:109) Pickup factor = 0.90

824 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

The stage picks up when the measured voltage value falls below the pickup value Threshold × Pickup
factor.
Depending on the Measured value, the Threshold is set either as phase-to-phase quantity or as
phase-to-ground quantity.
With the Pickup factor parameter, you modify the pickup value. To avoid a long operate delay time after
pickup, Siemens recommends using the default value of Pickup factor.
Specify the Threshold (pickup threshold) and Pickup factor for the specific application.

Parameter: Stabilization counter

• Default setting (_:2311:103) Stabilization counter = 0


You can configure the Stabilization counter parameter in the function block General.
For special applications, it could be desirable that a short falling of the input voltage below the pickup value
does not lead to the pickup of the stage, which starts fault logging and recording. This is achieved by setting
the Stabilization counter parameter to a value other than zero.
For example, if you set this parameter to 1, the pickup signal is issued when the voltage keeps being below
the pickup value for 2 successive measuring cycles. For 50 Hz, the measuring cycle time is 10 ms.

Parameter: Pickup mode

• Recommended setting value (_:101) Pickup mode = 1 out of 3


With the Pickup mode parameter, you specify whether the stage picks up when there is a lower threshold-
value violation in one measuring element (1 out of 3) or when there is a lower threshold-value violation in
all 3 measuring elements (3 out of 3).
Parameter Value Description
1 out of 3 Use this setting for protection applications or for monitoring the voltage
range.
Siemens recommends 1 out of 3 as the default setting. This reflects how
the function behaved in previous generations (SIPROTEC 4, SIPROTEC 3).
3 out of 3 Select this setting when using the stage to disconnect from the power
system (in the case of wind farms, for example).

Parameter: Pickup delay

• Default setting (_:102) Pickup delay = no


The Pickup delay parameter is only available if you are using the current-flow criterion of the function
(parameter Current-flow criterion = on). If the current-flow criterion is deactivated, no pickup delay is
required.
With the Pickup delay parameter, you set whether pickup of the stage is to be delayed by approximately
40 ms or not. The delay avoids possible brief pickup of the stage when the circuit breaker opens.
When applied in parallel, the pickup delay and the delay through pickup stabilization add up.
Parameter Value Description
no Use this setting if you definitely do not want stage pickup to be subject to a
time delay in the event of a fault. This setting results in pickup and, where
applicable, tripping being performed as quickly as possible.
Note that switching procedures (opening of the CB) can result in brief
pickup of the stage, depending on the threshold-value settings for under-
voltage pickup and the current-flow criterion. To prevent unwanted trip-
ping, you must set a minimum tripping delay of 50 ms.
yes Use this setting when switching procedures (opening of the CB) are not
permitted to result in stage pickup.
Note that pickup is delayed by approximately 40 ms. This delay is added to
the operate time.

SIPROTEC 5, 7SJ82/7SJ85, Manual 825


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

Parameter: Charact. constant k, Charact. constant α, Charact. constant c

• Default setting (_:103) Charact. constant k = 1.00

• Default setting (_:104) Charact. constant α = 1.000

• Default setting (_:105) Charact. constant c = 0.000


With the Charact. constant k, Charact. constant α, and Charact. constant c parameters,
you define the required inverse-time characteristic.

Parameter: Time dial

• Default setting (_:106) Time dial = 1.00


With the Time dial parameter, you displace the characteristic curve in the time direction.
As usually, there is no time grading for voltage protection and therefore no displacement of the characteristic
curve, Siemens recommends leaving the Time dial parameter at 1.00 (default setting).

Parameter: Reset time

• Default setting (_:108) Reset time = 0.00 s


With the Reset time parameter, you define the reset time delay which is started when the voltage exceeds
the dropout value. Set the parameter Reset time to 0 s when instantaneous reset is desired.
Under network conditions of intermittent faults or faults which occur in rapid succession, Siemens recom-
mends setting the Reset time to an appropriate value > 0 s to ensure the operation. Otherwise, Siemens
recommends keeping the default value to ensure a fast reset of the function.

Parameter: Additional time delay

• Default setting (_:107) Additional time delay = 0.00 s


With the Additional time delay parameter, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, only the inverse-time delay is operative.

Parameter: Blk. by meas.-volt. failure

• Default setting (_:10) Blk. by meas.-volt. failure = yes


With the Blk. by meas.-volt. failure parameter, you control the behavior of the stage when a meas-
uring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


switched on.

• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 9.3.4.1 Overview of Functions).

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

Parameter: Current-flow criterion

• Recommended setting value (_:2311:104) Current-flow criterion = on


Depending on the system, the voltage transformers are arranged on either the supply side or the junction side.
These 2 possible voltage-transformer locations induce a different behavior of the function after tripping and
opening of the circuit breaker:

826 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

• If they are located on the supply side, the voltage still exists.

• If they are located on the junction side, the voltage does not exist.

Parameter Value Description


on If the voltage transformers are located on the junction side, you can use the
current-flow criterion to make the pickup drops out when the current falls
below a minimum value (parameter Threshold I>).
off In the case of undervoltage, the pickup of the undervoltage protection
stage persists when the current-flow criterion is not used.

6.30.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Inverse-T #
_:1 Inverse-T #:Mode • off off
• on
• test
_:2 Inverse-T #:Operate & • no no
flt.rec. blocked
• yes
_:10 Inverse-T #:Blk. by • no yes
meas.-volt. failure
• yes
_:9 Inverse-T #:Measured • phase-to-ground phase-to-phase
value
• phase-to-phase
_:8 Inverse-T #:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:101 Inverse-T #:Pickup mode • 1 out of 3 1 out of 3
• 3 out of 3
_:102 Inverse-T #:Pickup delay • no no
• yes
_:3 Inverse-T #:Threshold 0.300 V to 175.000 V 80.000 V
_:109 Inverse-T #:Pickup factor 0.80 to 1.00 0.90
_:103 Inverse-T #:Charact. 0.00 to 300.00 1.00
constant k
_:104 Inverse-T #:Charact. 0.010 to 5.000 1.000
constant α
_:105 Inverse-T #:Charact. 0.000 to 5.000 0.000
constant c
_:106 Inverse-T #:Time dial 0.05 to 15.00 1.00
_:107 Inverse-T #:Additional 0.00 s to 60.00 s 0.00 s
time delay
_:108 Inverse-T #:Reset time 0.00 s to 60.00 s 0.00 s

6.30.4.4 Information List

No. Information Data Class Type


(Type)
Inverse-T #
_:81 Inverse-T #:>Block stage SPS I
_:54 Inverse-T #:Inactive SPS O
_:52 Inverse-T #:Behavior ENS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 827


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.30 Undervoltage Protection with 3-Phase Voltage

No. Information Data Class Type


(Type)
_:53 Inverse-T #:Health ENS O
_:55 Inverse-T #:Pickup ACD O
_:300 Inverse-T #:Pickup loop AB SPS O
_:301 Inverse-T #:Pickup loop BC SPS O
_:302 Inverse-T #:Pickup loop CA SPS O
_:56 Inverse-T #:Operate delay expired ACT O
_:57 Inverse-T #:Operate ACT O

828 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.31 Undervoltage Protection with Positive-Sequence Voltage

6.31 Undervoltage Protection with Positive-Sequence Voltage

6.31.1 Overview of Functions

The Undervoltage protection with positive-sequence voltage function (ANSI 27):

• Monitors the permissible voltage range

• Protects equipment (for example, plant components and machines) from damages caused by under-
voltage

• Protects motors and generators from inadmissible operating states and a possible loss of stability in the
event of voltage dips
2-phase short circuits or ground faults lead to an unbalanced voltage collapse. In comparison to three 1-phase
measuring systems, such events have no noticeable impact on the positive-sequence voltage. This makes this
function particularly suitable for the assessment of stability problems.

6.31.2 Structure of the Function

The Undervoltage protection with positive-sequence voltage function is used in protection function
groups, which are based on voltage measurement.
The Undervoltage protection with positive-sequence voltage function comes factory-set with 2 tripping
stages. A maximum of 3 tripping stages can be operated simultaneously in the function. The tripping stages
have an identical structure.
The protection function is structured such that one current-flow criterion can act on all undervoltage protec-
tion stages (see Figure 6-214). If the protection function group used has no current measurement, you can
only set the current-flow criterion as fulfilled via the corresponding binary input signal.

[dwstuvu1-110211-01.tif, 3, en_US]

Figure 6-214 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 829


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.31 Undervoltage Protection with Positive-Sequence Voltage

6.31.3 Stage Description

Logic of the Stage

[louv3pu1-021012-01.tif, 1, en_US]

Figure 6-215 Logic Diagram of the Stage Undervoltage Protection with Positive-Sequence Voltage

Method of Measurement
The stage uses the positive-sequence voltage. The positive-sequence voltage is calculated from the measured
phase-to-ground voltages according to the defining equation.

830 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.31 Undervoltage Protection with Positive-Sequence Voltage

Pickup Delay
The Pickup delay parameter is only available and of relevance if you are using the current-flow criterion of
the function (parameter Current-flow criterion = on).
If the circuit breaker opens when the current-flow criterion is being used, the undervoltage detection and
current-flow dropout functions conflict with one another. Depending on the threshold value settings for
undervoltage detection and current-flow criterion, it is possible that the undervoltage is detected before the
current-flow criterion has dropped out. In this case, the tripping stage picks up briefly. Use the Pickup
delay parameter to prevent the tripping stage from briefly picking up in this way when the circuit breaker
opens. This is achieved by delaying pickup by approximately 40 ms.

Current-Flow Criterion
The undervoltage-protection stages work optionally with a current-flow criterion. The current-flow criterion
works across all stages.
When the Current-flow criterion parameter is switched on, the undervoltage protection stages only
pick up if a settable minimum current (Threshold I>) is exceeded in at least one phase. A current below the
minimum current blocks the tripping stages.
The current-flow criterion can also be set to fulfilled via the binary input signal >Current flow-crite-
rion. The function reports when the current-flow criterion is fulfilled.
Figure 6-215 illustrates the influence of the current-flow criterion.

NOTE

i If the Current-flow criterion parameter is switched off, the device picks up immediately if a missing
measuring voltage is detected while the undervoltage protection is active. The parameter setting can be
changed even when the device has picked up.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. The following blocking options are available for the
stage:

• Via the binary input signal >Block stage from an external or internal source

• From inside on pickup of the Measuring-voltage failure detection function (see chapter 9.3.2.1 Over-
view of Functions). The Blk. by meas.-volt. failure parameter can be set to either block or not
block the tripping stage when the measuring-voltage failure detection picks up.

• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker. The Blk. by meas.-volt.
failure parameter can be set so that measuring-voltage failure detection blocks the stage or does not
block it.

6.31.4 Application and Setting Notes

Parameter: Threshold

• Default setting (_:481:3) Threshold = 46 V


Specify the Threshold (pickup threshold) for the specific application. For the default setting, the lower limit
of the voltage range to be monitored is assumed to be 80 % of the rated voltage of the protected object.

Parameter: Pickup delay

• Default setting (_:481:101) Pickup delay = no


The Pickup delay parameter is only available if you are using the current-flow criterion of the function
(parameter Current-flow criterion = on). If the current-flow criterion is deactivated, no pickup delay is
required.

SIPROTEC 5, 7SJ82/7SJ85, Manual 831


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.31 Undervoltage Protection with Positive-Sequence Voltage

With the parameter Pickup delay you set whether pickup of the stage is to be delayed by approximately
40 ms or not. The delay avoids possible brief pickup of the stage when the circuit breaker opens.
Parameter Value Description
no Use this setting if you definitely do not want tripping-stage pickup to be
subject to a time delay in the event of a fault. This setting results in pickup
and, where applicable, tripping being performed as quickly as possible.
Note that switching procedures (opening of the CB) can result in brief
pickup of the tripping stage, depending on the threshold-value settings for
undervoltage pickup and the current-flow criterion. To prevent unwanted
tripping, you must set a minimum tripping delay of 50 ms.
yes Use this setting when switching procedures (opening of the CB) are not
permitted to result in tripping-stage pickup.
Note that pickup is delayed by approximately 40 ms. This delay is added to
the operate time.

Parameter: Operate delay

• Default setting (_:481:6) Operate delay = 3 s


The Operate delay must be set for the specific application.

Parameter: Dropout ratio

• Recommended setting value (_:481:4) Dropout ratio = 1.05


The recommended setting value of 1.05 is sufficient for many applications. To obtain extremely accurate indi-
cations, the Dropout ratio can be reduced.

Parameter: Blk. by meas.-volt. failure

• Default setting (_:481:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the behavior of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal supervision function Measuring-voltage failure detection is configured and


switched on.

• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 9.3.4.1 Overview of Functions).

Parameter Value Description


yes The protection stage is blocked (= default setting). Siemens recommends
using the default setting.
no The protection stage is not blocked.

Parameter: Current-flow criterion

• Recommended setting value (_:2311:104) Current-flow criterion = on


Depending on the system, the voltage transformers can be located on the supply or the output side. These 2
possible voltage transformer locations induce a different behavior of the function after tripping and opening
of the circuit breaker:

• If they are located on the supply side, the voltage still exists.

• If they are located on the output side, the voltage does not exist.

832 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.31 Undervoltage Protection with Positive-Sequence Voltage

Parameter Value Description


on If the voltage transformers are located on the output side, you can use the
current-flow criterion to make the pickup drops out when the current falls
below a minimum value (parameter Threshold value I>).
off In the case of undervoltage, the pickup of the undervoltage-protection
stage persists when the current-flow criterion is not used.

Parameter: Threshold I>

• Recommended setting value (_:2311:101) Threshold I> = 0.05 A


The Threshold I> parameter makes it possible to detect when the circuit breaker is closed. Siemens recom-
mends setting the Threshold I> parameter to 5% of the rated current. With a secondary rated transformer
current of 1 A, the secondary setting value for Threshold I> would be 0.05 A.
If the sensitivity of the Threshold I> parameter is set too high, compensation processes in the secondary
circuit of the current transformer extend the dropout time when breaking extremely high currents. To speed
up dropout, increase the default setting.

Operation as Supervision Function


If you want the tripping stage to have a reporting effect only, generation of the operate indication and fault
logging can be disabled via the Operate & flt.rec. blocked parameter.

EXAMPLE of a 2-stage undervoltage protection


The undervoltage protection can be used for the protection of motors within the power plant's own power
system. The example describes the possible settings for a two-stage undervoltage-protection function. We will
look at the settings of the parameters Threshold and Operate delay.
1. Stage:
Set the Threshold to approx. 80 % of the rated voltage. In the case of voltage dips down to that value, the
motors can still start up. Depending on the machine characteristic, the Threshold can also be set somewhat
lower.
The following data apply:
Rated motor voltage: Vrated,M = 6 kV
Minimum startup voltage: 80 % of rated motor voltage
Voltage-transformer ratio:

When setting the threshold value, make sure that the positive-sequence voltage as defined is equal to the
value of one phase-to-ground voltage. Taking into account the rated primary voltage of the motor, the
primary setting value of the first stage is calculated as follows:

[fobglei1-190309-01.tif, 2, en_US]

When setting secondary values, you calculate the secondary setting value as follows, taking into account the
voltage-transformer ratio:

[fobglei3-190309-01.tif, 2, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 833


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.31 Undervoltage Protection with Positive-Sequence Voltage

Set a value of 3 s for the Operate delay.


2. Stage:
Undervoltage causes excessive torques and current surges which place inadmissible strains on the motor. The
voltage at which motors do no longer start up is in the range of (0.55 … 0.70) Vrated,M. If no data are available,
use the empirical value of approx. 70% of the rated voltage for setting the parameter Threshold. Set the
Operate delay so that it slightly overlaps the tripping time of the overcurrent protection for the power-
plant auxiliary power. Unless otherwise required by the motor manufacturer, set an Operate delay
between 0.5 s and 3 s. The shorter time should be preferred.
Stage Setting Values
Threshold value Time delay
1 0.70 to 0.85 Vrated,M Approx. 3 to 5 s
(for example, 0.80 Vrated,M)
2 0.55 to 0.70 Vrated,M 0.5 s to 3 s
(for example, 0.70 Vrated,M)

6.31.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:104 General:Current-flow • off on
criterion
• on
_:2311:101 General:Threshold I> 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
Stage 1
_:481:1 Stage 1:Mode • off off
• on
• test
_:481:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:481:10 Stage 1:Blk. by meas.- • no yes
volt. failure
• yes
_:481:101 Stage 1:Pickup delay • no no
• yes
_:481:3 Stage 1:Threshold 0.300 V to 200.000V 46.000V
_:481:4 Stage 1:Dropout ratio 1.01 to 1.20 1.05
_:481:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
Stage 2
_:482:1 Stage 2:Mode • off off
• on
• test
_:482:2 Stage 2:Operate & • no no
flt.rec. blocked
• yes

834 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.31 Undervoltage Protection with Positive-Sequence Voltage

Addr. Parameter C Setting Options Default Setting


_:482:10 Stage 2:Blk. by meas.- • no yes
volt. failure
• yes
_:482:101 Stage 2:Pickup delay • no no
• yes
_:482:3 Stage 2:Threshold 0.300 V to 200.000 V 40.000V
_:482:4 Stage 2:Dropout ratio 1.01 to 1.20 1.05
_:482:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s

6.31.6 Information List

No. Information Data Class Type


(Type)
General
_:2311:500 General:>Current flow-criterion SPS I
_:2311:300 General:Current crit. fulf. SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:481:81 Stage 1:>Block stage SPS I
_:481:54 Stage 1:Inactive SPS O
_:481:52 Stage 1:Behavior ENS O
_:481:53 Stage 1:Health ENS O
_:481:55 Stage 1:Pickup ACD O
_:481:56 Stage 1:Operate delay expired ACT O
_:481:57 Stage 1:Operate ACT O
Stage 2
_:482:81 Stage 2:>Block stage SPS I
_:482:54 Stage 2:Inactive SPS O
_:482:52 Stage 2:Behavior ENS O
_:482:53 Stage 2:Health ENS O
_:482:55 Stage 2:Pickup ACD O
_:482:56 Stage 2:Operate delay expired ACT O
_:482:57 Stage 2:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 835


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.32 Undervoltage Protection with Any Voltage

6.32 Undervoltage Protection with Any Voltage

6.32.1 Overview of Functions

The function Undervoltage protection with any voltage (ANSI 27) detects any 1-phase undervoltage and is
intended for special applications.

6.32.2 Structure of the Function

The Undervoltage protection with any voltage function is used in protection function groups, which are
based on voltage measurement.
The function Undervoltage protection with any voltage comes factory-set with 2 stages. A maximum of 3
tripping stages can be operated simultaneously in the function. The tripping stages have an identical struc-
ture.
The protection function is structured such that one current-flow criterion can act on all undervoltage protec-
tion stages (see Figure 6-216).

[dwstuvux-110211-01.tif, 1, en_US]

Figure 6-216 Structure/Embedding of the Function

836 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.32 Undervoltage Protection with Any Voltage

6.32.3 Stage Description

Logic of a Stage

[louvpuxx-100611-01.tif, 1, en_US]

Figure 6-217 Logic Diagram of a Stage: Undervoltage Protection with Any Voltage

NOTE

i If the function Undervoltage protection with any voltage is used in a 1-phase function group, the param-
eter Measured value is not visible.

Method of Measurement
The Method of measurement parameter allows you to define whether the function works with the funda-
mental component or the calculated RMS value.

• Measurement of the fundamental component:


This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.

• Measurement of the RMS value:


This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.

SIPROTEC 5, 7SJ82/7SJ85, Manual 837


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.32 Undervoltage Protection with Any Voltage

Measured Value
The parameter Measured value allows you to select whether the stage uses a measured (directly
connected) voltage or a calculated phase-to-phase voltage.
If the function Undervoltage protection with any voltage is used in a 1-phase function group, the parameter
Measured value is not visible.

Current-Flow Criterion
The undervoltage-protection stages work optionally with a current-flow criterion. The current-flow criterion
works across all stages.
When the Current-flow criterion parameter is switched on, the undervoltage protection stages only
pick up when the current-flow criterion has been set to fulfilled via the binary input signal >Current flow-
criterion. The function reports when the current-flow criterion is fulfilled.
Figure 6-217 illustrates the influence of the current-flow criterion.

NOTE

i If the (_:2311:101) Current-flow criterion parameter is deactivated, the device picks up imme-
diately if a missing measuring voltage is detected while the undervoltage protection is active. The param-
eter setting can be changed even when the device has picked up.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. Blocking the stage is possible externally or internally
via the binary input signal >Block stage.

6.32.4 Application and Setting Notes

Parameter: Method of measurement

• Recommended setting value (_:571:8) Method of measurement = fundamental comp.


Use the Method of measurement parameter to define whether the tripping stage uses the fundamental
component (standard method = default setting) or the calculated RMS value.
Parameter Value Description
fundamental comp. Select this method of measurement to suppress harmonics or transient
voltage peaks.
Siemens recommends using this parameter value as the default setting.
RMS value Select this method of measurement if you want the stage to take harmonics
into account (for example at capacitor banks). Do not set the threshold
value of the tripping stage under 10 V for this method of measurement.

Parameter: Measured value

• Default setting (_:571:9) Measured value = VA measured


The Measured value parameter is used to specify which voltage is monitored by the stage.
The scope of setting options depends on the connection type for the voltage transformers and the routing of
the measured values to the terminals of the voltage measuring point. You can find connection examples for
voltage transformers in the Appendix.
The following setting options can be available:

• Measured phase-to-ground voltage VA (VA measured)

• Measured phase-to-ground voltage VB (VB measured)

• Measured phase-to-ground voltage VC VC measured)

838 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.32 Undervoltage Protection with Any Voltage

• Measured phase-to-phase voltage VAB (VAB measured)

• Measured phase-to-phase voltage VBC (VBC measured)

• Measured phase-to-phase voltage VCA (VCA measured)

• Calculated phase-to-phase voltage VAB (VAB calculated)

• Calculated phase-to-phase voltage VBC (VBC calculated)

• Calculated phase-to-phase voltage VCA (VCA calculated)

• Calculated voltage V0 (V0 calculated)


The selection depends on the corresponding application.

NOTE

i From V7.30 on, the value VN measured is no longer provided. If you have selected this value in earlier
versions, you can select the value V0 calculated instead after upgrading the configuration to V7.30 or a
later version.
If the function Undervoltage protection with any voltage is used in a 1-phase function group, the param-
eter Measured value is not visible.

Parameter: Threshold

• Default setting (_:571:3) Threshold = 80 V


Specify the Threshold (pickup threshold) for the specific application.
Depending on the Measured value, the Threshold is set either as measured voltage or as a phase-
to-phase variable.

NOTE

i If the function is used in a Voltage-current 1-phase function group connected to the 1-phase voltage
measuring point with the voltage type VN broken-delta, you set the threshold value based on the
equivalent zero-sequence voltage.
Calculate the equivalent zero-sequence voltage V0 equiv. sec from the measured voltage VN sec with the
following formula:

You can find more information about the Matching ratio Vph / VN parameter in chapter 6.1.6 Appli-
cation and Setting Notes for Measuring Point Voltage 3‑Phase (V-3ph).

Parameter: Operate delay

• Default setting (_:571:6) Operate delay = 3 s


The Operate delay must be set for the specific application.

Parameter: Dropout ratio

• Recommended setting value (_:571:4) Dropout ratio = 1.05


The recommended set value of 1.05 is appropriate for most applications. To achieve high measurement preci-
sion, the Dropout ratio can be reduced to 1.02, for example.

Parameter: Current-flow criterion

• Recommended setting value (_:2311:101) Current-flow criterion = on

SIPROTEC 5, 7SJ82/7SJ85, Manual 839


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.32 Undervoltage Protection with Any Voltage

Parameter Value Description


on Because of the application, it makes sense that the stage is only active (that
is, not blocked) when a certain current flow is present (see note).
off Current flow monitoring does not make sense for the application.

NOTE

i Because of the flexible setting options of the voltage measurand, the function itself does not determine the
current associated with the voltage. A suitable current-flow monitoring function must be created by the
user with the Continuous Function Chart (CFC), and connected to the binary input signal >Current
flow-criterion.

Operation as Supervision Function


If you want the tripping stage to have a reporting effect only, generation of the operate indication and fault
logging can be disabled via the Operate & flt.rec. blocked parameter.

6.32.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Current-flow • off on
criterion
• on
Stage 1
_:571:1 Stage 1:Mode • off off
• on
• test
_:571:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:571:9 Stage 1:Measured value • VA measured VA measured
• VB measured
• VC measured
• VAB measured
• VBC measured
• VCA measured
• VAB calculated
• VBC calculated
• VCA calculated
• V0 calculated
_:571:8 Stage 1:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:571:3 Stage 1:Threshold 0.300 V to 340.000 V 80.000 V
_:571:4 Stage 1:Dropout ratio 1.01 to 1.20 1.05
_:571:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
Stage 2
_:572:1 Stage 2:Mode • off off
• on
• test

840 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.32 Undervoltage Protection with Any Voltage

Addr. Parameter C Setting Options Default Setting


_:572:2 Stage 2:Operate & • no no
flt.rec. blocked
• yes
_:572:9 Stage 2:Measured value • VA measured VA measured
• VB measured
• VC measured
• VAB measured
• VBC measured
• VCA measured
• VAB calculated
• VBC calculated
• VCA calculated
• V0 calculated
_:572:8 Stage 2:Method of • fundamental comp. fundamental
measurement comp.
• RMS value
_:572:3 Stage 2:Threshold 0.300 V to 340.000 V 65.000 V
_:572:4 Stage 2:Dropout ratio 1.01 to 1.20 1.05
_:572:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s

6.32.6 Information List

No. Information Data Class Type


(Type)
General
_:2311:500 General:>Current flow-criterion SPS I
_:2311:300 General:Current crit. fulf. SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:571:81 Stage 1:>Block stage SPS I
_:571:54 Stage 1:Inactive SPS O
_:571:52 Stage 1:Behavior ENS O
_:571:53 Stage 1:Health ENS O
_:571:55 Stage 1:Pickup ACD O
_:571:56 Stage 1:Operate delay expired ACT O
_:571:57 Stage 1:Operate ACT O
Stage 2
_:572:81 Stage 2:>Block stage SPS I
_:572:54 Stage 2:Inactive SPS O
_:572:52 Stage 2:Behavior ENS O
_:572:53 Stage 2:Health ENS O
_:572:55 Stage 2:Pickup ACD O
_:572:56 Stage 2:Operate delay expired ACT O
_:572:57 Stage 2:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 841


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.33 Overfrequency Protection

6.33 Overfrequency Protection

6.33.1 Overview of Functions

The Overfrequency protection function (ANSI 81O):

• Detect overfrequencies in electrical power systems or machines

• Monitor the frequency band and output failure indications

• Disconnect generating units when the power frequency is critical

• Provide additional turbine protection if the speed limiter fails


Frequency deviations are caused by an unbalance between the active power generated and consumed. Over-
frequency is caused by load shedding (island network), power system disconnection or disturbances of the
frequency controller. Overfrequency implies a risk of self excitation of machines which are connected to long
lines without load.
Overfrequency protection is available in two functional configurations (selectable from the DIGSI functions
library). The functional configurations differ in the frequency measurement method they use.

6.33.2 Structure of the Function

The Overfrequency protection function is used in protection function groups, which are based on voltage
measurement.
The overfrequency protection function comes with 2 factory-set stages. A maximum of 3 tripping stages can
be operated simultaneously in the function. The tripping stages have an identical structure.
The parameters Dropout differential and Minimum voltage are set for all stages.

[dwstofqp-090211-01.tif, 1, en_US]

Figure 6-218 Structure/Embedding of the Function

842 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.33 Overfrequency Protection

6.33.3 Overfrequency-Protection Stage

Logic of a Stage

[lostofqp-040411-01.tif, 1, en_US]

Figure 6-219 Logic Diagram of the Overfrequency-Protection Stage

Frequency-Measurement Method
Overfrequency protection is available in 2 functional configurations. These work with different frequency-
measurement methods. You select the frequency-measurement method in dependence of the application.

• Angle-difference method (method A):


The angle-difference method determines the phasor of the positive-sequence voltage in multiphase
systems. In the case of 1-phase connection, it always processes the phasor of the connected voltage.
Since the change of angle of the voltage phasor over a given time interval is proportional to the
frequency change, the current frequency can be derived from it.

• Filtering method (method B):


The filtering method processes the instantaneous voltage values and determines the current frequency
using a suitable combination of filters. The frequency-protection function selects automatically the
largest voltage as the measurand. In a multiphase connection, the phase-to-phase voltage is always the
largest. If in a multiphase connection the selected voltage is no longer available, the function changes
over automatically to the next maximum voltage. The function can even operate with just one voltage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 843


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.33 Overfrequency Protection

Both methods of measurement are characterized by a high measuring accuracy combined with a short pickup
time. Disturbance values such as harmonics, high frequency disturbances, phase-angle jumps during
switching operations and compensation processes due to power swings are effectively suppressed.

Functional Measured Value


The angle-difference method provides the following measured value:
Measured Value Description
f Frequency calculated with the angle-difference method

Behavior on Leaving the Operating Range


The sampling-frequency tracking makes a wide frequency operating range possible. If the stage has picked up
before leaving the frequency operating range and the measuring voltage is higher than the set minimum
voltage, the pickup is maintained. A dropout of the pickup is only possible by means of a blocking.

Blocking the Stage


In the event of blocking, a picked-up stage will be reset. The following blocking options are available for the
stage:

• Externally or internally via the logical binary input >Block stage

• Internally when the voltage drops below the Minimum voltage

6.33.4 Application and Setting Notes

Frequency-Measurement Method
The frequency measurement method is selected with the functional configuration from the DIGSI functions
library. The letter at the end of the function name describes the method of measurement.
Redundant solutions can be implemented by combining 2 different methods of frequency measurement. You
can implement a 2-out-of-2 decision by connecting the operate indications of both functions in a CFC with a
logical AND gate. This increases the reliability of protection.
Frequency-Measurement Description
Method
Angle difference method Select this method of measurement if the frequency protection stage is
(method A) used for the protection of machines.
Filtering method (method B) Select this method of measurement if the frequency protection stage is
used in an electrical power system.

Parameter: Threshold

• Recommended setting value (_:31:3) Threshold = 50.20 Hz for frated = 50 Hz

The Threshold parameter is used to define the pickup threshold of the overfrequency protection stage in
dependence of the application. 50.20 Hz is a typical warning threshold in 50-Hz systems.

Parameter: Operate delay

• Recommended setting value (_:31:6) Operate delay = 10 s


The Operate delay parameter is used to set the stage so that overfunctions due to disturbing influences
(for example, switching operations) are avoided. Fairly high time delays are sufficient for warning indications.

Parameter: Minimum voltage

• Recommended setting value (_:2311:101) Minimum voltage = 37.5 V


For the Undervoltage blocking, 65 % of the rated voltage of the protected object is recommended.

844 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.33 Overfrequency Protection

When determining the setting value, please keep in mind the measurement method and the measuring
connection that you have selected. If you work with the positive-sequence voltage, remember that the
maximum voltage is equal to the phase-to-ground voltage. The default setting is referred to this value.

Parameter: Dropout differential

• Recommended setting value (_:2311:109) Dropout differential = 20 mHz


Due to the high-precision frequency measurement, the recommended setting value for the Dropout
differential can remain at 20 mHz. If in your application you wish a subsequent dropout of the tripping
stage, then increase the setting value of the dropout differential. For example, if the pickup value (parameter
Threshold) of the tripping stage is set to 50.20 Hz and the Dropout differential to 100 mHz, the
stage will drop out at 50.10 Hz.

Application example of the overfrequency protection


Overfrequency protection can be used for monitoring the frequency range. If the frequency deviates from the
rated frequency by for example, 0.2 Hz, an alarm indication is generated. The trip command is delayed to
avoid overfunction due to disturbing influences (for example, switching operations). A delay of a few seconds
(for example, 10 s) is deemed to be a good value. You can leave the Dropout differential at the default
value of 20 mHz. The following table shows a setting recommendation.
For this application, 1 stage of the overfrequency protection is used. The following table shows a setting
suggestion.
Stage Caused by Setting Values
At frated = 50 Hz At frated = 60 Hz Delay
f1> Warning 50.20 Hz 60.20 Hz 10.00 s
f2> Not used (OFF) - - -

NOTE

i This table shows one example of a possible frequency protection setting. The setting values can differ
depending on the application.

6.33.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Minimum voltage 3.000 V to 175.000 V 37.500 V
_:2311:109 General:Dropout differential 20 mHz to 2000 mHz 20 mHz
Stage 1
_:31:1 Stage 1:Mode • off off
• on
• test
_:31:2 Stage 1:Operate & flt.rec. • no no
blocked
• yes
_:31:3 Stage 1:Threshold 40.00 Hz to 70.00 Hz 51.50 Hz
_:31:6 Stage 1:Operate delay 0.00 s to 600.00 s 10.00 s
Stage 2
_:32:1 Stage 2:Mode • off off
• on
• test

SIPROTEC 5, 7SJ82/7SJ85, Manual 845


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.33 Overfrequency Protection

Addr. Parameter C Setting Options Default Setting


_:32:2 Stage 2:Operate & flt.rec. • no no
blocked
• yes
_:32:3 Stage 2:Threshold 40.00 Hz to 70.00 Hz 54.00 Hz
_:32:6 Stage 2:Operate delay 0.00 s to 600.00 s 5.00 s

6.33.6 Information List

No. Information Data Class Type


(Type)
General
_:2311:300 General:Undervoltage blocking SPS O
_:2311:301 General:f MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:31:81 Stage 1:>Block stage SPS I
_:31:54 Stage 1:Inactive SPS O
_:31:52 Stage 1:Behavior ENS O
_:31:53 Stage 1:Health ENS O
_:31:55 Stage 1:Pickup ACD O
_:31:56 Stage 1:Operate delay expired ACT O
_:31:57 Stage 1:Operate ACT O
Stage 2
_:32:81 Stage 2:>Block stage SPS I
_:32:54 Stage 2:Inactive SPS O
_:32:52 Stage 2:Behavior ENS O
_:32:53 Stage 2:Health ENS O
_:32:55 Stage 2:Pickup ACD O
_:32:56 Stage 2:Operate delay expired ACT O
_:32:57 Stage 2:Operate ACT O

846 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.34 Underfrequency Protection

6.34 Underfrequency Protection

6.34.1 Overview of Functions

The Underfrequency protection function (ANSI 81U) is used to:

• Detect underfrequencies in electrical power systems or machines

• Monitor the frequency band and output failure indications

• Decouple power systems

• Load shedding to ensure power system stability and protect motors

• Disconnect generating units when the power system frequency is critical (for example, f < 0.95 frated)

Frequency deviations are caused by an unbalance between the active power generated and consumed. Under-
frequency is caused by an increase of the consumers' active power demand or by a decrease of the power
generated. These conditions occur in the case of power system disconnection, generator failure, or distur-
bances of the power and frequency controller.
Underfrequency protection is available in 2 functional configurations (selectable from the DIGSI functions
library). The functional configurations differ in the frequency measurement method they use.

6.34.2 Structure of the Function

The Underfrequency protection function is used in protection function groups, which are based on voltage
measurement.
The Underfrequency protection function comes with 3 factory-set stages. A maximum of 5 tripping stages
can be operated simultaneously in the function. The tripping stages have an identical structure.
The parameters Dropout differential and Minimum voltage are set for all stages.

[dwstufqp-090211-01.tif, 1, en_US]

Figure 6-220 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 847


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.34 Underfrequency Protection

6.34.3 Underfrequency-Protection Stage

Logic of a Stage

[lostufqp-040411-01.tif, 2, en_US]

Figure 6-221 Logic Diagram of the Underfrequency-Protection Stage

Frequency-Measurement Method
Underfrequency protection is available in 2 functional configurations. These work with different frequency-
measurement methods. You select the frequency-measurement method in dependence of the application.

• Angle-difference method (method A):


The angle-difference method determines the phasor of the positive-sequence voltage in multiphase
systems. In the case of 1-phase connection, it always processes the phasor of the connected voltage.
Since the change of angle of the voltage phasor over a given time interval is proportional to the
frequency change, the current frequency can be derived from it.

• Filtering method (method B):


The filtering method processes the instantaneous voltage values and determines the current frequency
using a suitable combination of filters. The frequency-protection function selects automatically the
largest voltage as the measurand. In a multiphase connection, the phase-to-phase voltage is always the
largest. If in a multiphase connection the selected voltage is no longer available, the function changes
over automatically to the next maximum voltage. The function can even operate with just one voltage.

848 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.34 Underfrequency Protection

Both methods of measurement are characterized by a high measuring accuracy combined with a short
response time. Disturbance values such as harmonics, high frequency disturbances, phase-angle jumps during
switching operations and compensation processes due to power swings are effectively suppressed.

Behavior on Leaving the Operating Range


The sampling-frequency tracking makes a wide frequency operating range possible. If the stage has picked up
before leaving the frequency operating range and the measuring voltage is higher than the set minimum
voltage, the pickup is maintained. A dropout of the pickup is only possible by means of a blocking.

Blocking the Stage


In the event of blocking, a picked-up stage will be reset. The following blocking options are available for the
stage:

• Via the binary input signal >Block stage from an external or internal source

• Internally when the voltage drops below the Minimum voltage

6.34.4 Application and Setting Notes

Frequency-Measurement Method
The frequency measurement method is selected with the functional configuration from the DIGSI functions
library. The letter at the end of the function name describes the method of measurement.
Redundant solutions can be implemented by combining 2 different methods of frequency measurement. You
can implement a 2-out-of-2 decision by connecting the operate indications of both functions in a CFC with a
logical AND gate. This increases the security of protection.
Method of Measurement Description
Angle-difference method Select this method of measurement if the frequency protection stage is
(method A) used for the protection of machines.
Filtering method (method B) Select this method of measurement if the frequency protection stage is
used in an electrical power system.

Parameter: Threshold

• Recommended setting value (_:61:3) Threshold = 49.80 Hz for frated = 50 Hz

The Threshold parameter is used to define the pickup threshold of the underfrequency protection stage in
dependence of the application. 49.8 Hz is a typical warning threshold in 50-Hz systems.

Parameter: Operate delay

• Recommended setting value (_:61:6) Operate delay = 10.00 s


The Operate delay parameter is used to set the stage so that overfunctions due to disturbing influences
(for example switching operations) are avoided. Fairly high time delays are sufficient for warning indications.

Parameter: Minimum voltage

• Recommended setting value (_:2311:101) Minimum voltage = 37 500 V


For the Undervoltage blocking, 65 % of the rated voltage of the protected object is recommended.
When determining the setting value, please keep in mind the measurement method and the measuring
connection that you have selected. If you work with the positive-sequence voltage, remember that the
maximum voltage is equal to the phase-to-ground voltage. The default setting is referred to this value.

Parameter: Dropout differential

• Recommended setting value (_:2311:109) Dropout differential = 20 mHz

SIPROTEC 5, 7SJ82/7SJ85, Manual 849


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.34 Underfrequency Protection

Due to the high-precision frequency measurement, the recommended setting value for the Dropout
differential can remain at 20 mHz. If in your application you wish a subsequent dropout of the tripping
stage, then increase the setting value of the dropout differential. For example, if the pickup value (parameter
Threshold) of the tripping stage is set to 49.8 Hz and the Dropout differential to 100 mHz, the stage
will drop out at 49.9 Hz.

Application Example of Underfrequency Protection


Frequency protection can be used for load shedding. The UCTE has defined a 5-stage plan for the Western
European power grid. The setting values of the stages are based on that plan (see table below).

Table 6-16 Stage Plan

Frequency Activity
49.80 Hz Alarm and activation of reserves following an established plan
49.00 Hz Undelayed disconnection of 10 % to 15 % of the power system load
48.70 Hz Undelayed disconnection of another 10 % to 15 % of the power system load
48.40 Hz 3rd load-shedding stage. Another 15 % to 20 % of the power system load is
disconnected.
47.50 Hz Power plants are decoupled from the electrical power system

For this application, 3 stages of the underfrequency protection are used. 2 of these stages are used for load
shedding. The following table shows a setting suggestion.
Stage Caused by Setting Values
At frated = 50 Hz At frated = 60 Hz Delay
f1< Warning 49.80 Hz 59.80 Hz 10.00 s
f2< 1st load shedding 49.00 Hz 59.00 Hz 0.00 s
f3< 2nd load shedding 48.70 Hz 58.70 Hz 0.00 s

NOTE

i This table shows one example of a possible frequency protection setting. The setting values can differ
depending on the application.

6.34.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Minimum voltage 3.000 V to 175.000 V 37.500 V
_:2311:109 General:Dropout differential 20 mHz to 2000 mHz 20 mHz
Stage 1
_:61:1 Stage 1:Mode • off off
• on
• test
_:61:2 Stage 1:Operate & flt.rec. • no no
blocked
• yes
_:61:3 Stage 1:Threshold 40.00 Hz to 70.00 Hz 49.80 Hz
_:61:6 Stage 1:Operate delay 0.00 s to 600.00 s 10.00 s

850 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.34 Underfrequency Protection

Addr. Parameter C Setting Options Default Setting


Stage 2
_:62:1 Stage 2:Mode • off off
• on
• test
_:62:2 Stage 2:Operate & flt.rec. • no no
blocked
• yes
_:62:3 Stage 2:Threshold 40.00 Hz to 70.00 Hz 47.50 Hz
_:62:6 Stage 2:Operate delay 0.00 s to 600.00 s 10.00 s
Stage 3
_:63:1 Stage 3:Mode • off off
• on
• test
_:63:2 Stage 3:Operate & flt.rec. • no no
blocked
• yes
_:63:3 Stage 3:Threshold 40.00 Hz to 70.00 Hz 47.00 Hz
_:63:6 Stage 3:Operate delay 0.00 s to 600.00 s 10.00 s

6.34.6 Information List

No. Information Data Class Type


(Type)
General
_:2311:300 General:Undervoltage blocking SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:61:81 Stage 1:>Block stage SPS I
_:61:54 Stage 1:Inactive SPS O
_:61:52 Stage 1:Behavior ENS O
_:61:53 Stage 1:Health ENS O
_:61:55 Stage 1:Pickup ACD O
_:61:56 Stage 1:Operate delay expired ACT O
_:61:57 Stage 1:Operate ACT O
Stage 2
_:62:81 Stage 2:>Block stage SPS I
_:62:54 Stage 2:Inactive SPS O
_:62:52 Stage 2:Behavior ENS O
_:62:53 Stage 2:Health ENS O
_:62:55 Stage 2:Pickup ACD O
_:62:56 Stage 2:Operate delay expired ACT O
_:62:57 Stage 2:Operate ACT O
Stage 3
_:63:81 Stage 3:>Block stage SPS I
_:63:54 Stage 3:Inactive SPS O
_:63:52 Stage 3:Behavior ENS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 851


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.34 Underfrequency Protection

No. Information Data Class Type


(Type)
_:63:53 Stage 3:Health ENS O
_:63:55 Stage 3:Pickup ACD O
_:63:56 Stage 3:Operate delay expired ACT O
_:63:57 Stage 3:Operate ACT O

852 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

6.35 Underfrequency Load Shedding

6.35.1 Overview of Functions

The Underfrequency load shedding function:

• Detects underfrequencies in the electrical power systems

• Switches off the medium-voltage busbar or feeders that consume active power to stabilize the frequency

• Maintains operations for the medium-voltage busbar or feeders that generate active power

6.35.2 Structure of the Function

The Underfrequency load shedding function can be used in the Voltage/Current 3-phase function group
and in the Line function group.
The Underfrequency load shedding function comes factory-set with 8 stages. A maximum of 12 stages can
be operated simultaneously within the function. These stages are identical in structure.

[dw_load shedding_Structure, 1, en_US]

Figure 6-222 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 853


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

6.35.3 General Functionality

6.35.3.1 Description

Logic

[lo_UFLS_General functionality, 1, en_US]

Figure 6-223 Logic Diagram of the General Functionality

(1) n means the number of the protection stage.

854 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

Measurands
The general functionality requires the following input measurands:

• Positive-sequence voltage V1

• Positive-sequence current I1

• Positive-sequence system apparent power S1

• Positive-sequence system active power P1

• Frequency
S1 and P1 are both calculated from V1 and I1. The frequency is calculated from V1.
The frequency and the frequency change rate df/dt are calculated via the angle difference algorithm. You can
find more information in chapter 6.33.3 Overfrequency-Protection Stage.

Undervoltage Blocking
The frequency of the Underfrequency load shedding function is calculated from the positive-sequence
voltage V1. In order to obtain a reliable and accurate frequency calculation result, the magnitude of V1 is
monitored. If the magnitude of V1 is smaller than the Minimum voltage, all the protection stages are
blocked and the V1< block indication is issued.

Power Criterion
If a feeder delivers active power towards the busbar, or if the medium-voltage busbar delivers active power to
the high-voltage busbar, it is meaningless to switch off this feeder or the medium-voltage busbar during the
load-shedding process. The power criterion determines the power-flow direction and includes this information
as a blocking criterion into the load-shedding decision of all protection stages.
The Positive power direction parameter defines the positive active-power flow direction of the func-
tion in relation to the standard forward direction of the protection functionality. You can find more informa-
tion in chapter 6.35.3.2 Application and Setting Notes.
In the following figures, if the power flow is located in the release area which is marked in gray, the protection
stages are released. In the remaining area, the protection stages are blocked.
The release area is configured via the following parameters:

• The parameter Phi (power criterion) defines the area which limits the range of the power angle.

• The parameter Min. current (power crit.) defines the minimum positive-sequence current that
must be present to calculate the active power in a reliable way. In the following figures, the minimum
current is indicated as the circle whose center is the origin of the coordinates.
The power criterion is checked only when the following 2 conditions are fulfilled:

• The positive-sequence current I1 exceeds the threshold Min. current (power crit.), that is, I1 is
out of the circle in the following figures.

• The undervoltage blocking is not fulfilled, that is, the magnitude of V1 is not smaller than the Minimum
voltage.
The dashed lines in the figures show the dropout characteristics. The dropout differential of the power angle is
1°.
The symbol φ in the following figures represents the setting value of the parameter Phi (power crite-
rion).

SIPROTEC 5, 7SJ82/7SJ85, Manual 855


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

[dw_load shedding_Power crit.<0, 1, en_US]

Figure 6-224 Power-Criterion Checking at Phi (power criterion) ≤ 0

[dw_load shedding_Power crit.>0, 1, en_US]

Figure 6-225 Power-Criterion Checking at Phi (power criterion) > 0

The power criterion contains the check of the current criterion and of the power-angle criterion.
You can determine whether to check the power criterion or not by setting the Power criterion parameter.
The power criterion is carried out only when the Power criterion parameter is set to yes.
The working method of the current criterion and of the power-angle criterion differ at Phi (power crite-
rion) ≤ 0 and Phi (power criterion) > 0.

856 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

For Phi (power criterion) ≤ 0, the power criterion is checked as follows:

• When the positive-sequence current I1 falls below the Min. current (power crit.), the current
criterion is not fulfilled and the I1< blocking indication is issued. Therefore, all the protection stages
are blocked and the power-angle criterion is not considered.

• When I1 exceeds the Min. current (power crit.) and the power angle is out of the release area,
the Power crit. blocking indication is issued and all the protection stages are blocked.
For Phi (power criterion) > 0, the power criterion is checked as follows:

• When I1 falls below the Min. current (power crit.), all the protection stages are released and
the power-angle criterion is not considered.

• When I1 exceeds the Min. current (power crit.) and the power angle is out of the release area,
the Power crit. blocking indication is issued and all the protection stages are blocked.

df/dt Blocking
If the change rate of df/dt is too high, the Underfrequency load shedding function may not be applicable
anymore.
The df/dt blocking comprises the df/dt-rising blocking and the df/dt-falling blocking.
The df/dt-rising criterion and the df/dt-falling criterion can be individually switched on or off. These 2 df/dt
criteria are operative only when the magnitude of the positive-sequence voltage V1 is greater than the
Minimum voltage:

• The df/dt-rising blocking takes place when the df/dt-rising value exceeds the setting value of the param-
eter df/dt-rising blk. threshold. It is signaled via the indication df/dt-rising blocking.

• The df/dt-falling blocking takes place when the df/dt-falling value exceeds the setting value of the param-
eter df/dt-falling blk. threshold. It is signaled via the indication df/dt-falling
blocking.

Activating/Deactivating Protection Stages


The mechanism of exclusive stage activation is described in section Exclusive Stage Activation, Page 861.

Functional Measured Value

Value Description
df/dt Calculated rate of frequency change

6.35.3.2 Application and Setting Notes

Parameter: Minimum voltage

• Default setting (_:18121:101) Minimum voltage = 0.700 p.u.


If the magnitude of V1 is smaller than the Minimum voltage, all protection stages are blocked.
The Minimum voltage parameter is set as a per-unit value related to the rated voltage of the connected
voltage measuring point. Siemens recommends using the default setting.

Parameter: Positive power direction

• Default setting (_:18121:115) Positive power direction = inv. to CT neu.pnt sett.


With the Positive power direction parameter, you define the positive active-power flow direction of
the function in relation to the standard forward direction of the protection functionality.

SIPROTEC 5, 7SJ82/7SJ85, Manual 857


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

The following figure shows 2 application scenarios of protection devices with the Underfrequency load shed-
ding function.

[dw_UFLS_positive power direction, 1, en_US]

Figure 6-226 Application Scenarios

Dotted arrow: Standard forward direction of the protection functionality


Solid arrow: Positive active-power flow direction

The standard forward direction of the protection functionality is from the busbar to the protected object which
is the transformer for device 1 or the feeder for device 2. The standard forward direction of the protection
functionality is configured via the (_:8881:116) Neutr.point in dir.of ref.obj parameter of the
measuring point I-3ph (see chapter 6.1.4 Application and Setting Notes for Measuring-Point Current 3‑Phase (I
3-ph)). For the load-shedding function, the positive active-power flow direction can differ from the standard
forward direction of the protection functionality, such as for device 1. To adapt the function to this condition,
the Positive power direction parameter is used. With the Positive power direction parameter,
you can set the positive active-power flow direction either to the same as or to the inverse of the standard
forward direction.

• For device 1, set the Positive power direction parameter to inv. to CT neu.pnt sett..
Then, the positive active-power flow direction of the power criterion is opposite to the standard forward
direction of the protection functionality. Consequently, the Underfrequency load shedding function
sheds the medium-voltage busbar when the positive power-flow direction is from the high-voltage
busbar to the medium-voltage busbar.

• For device 2, set the Positive power direction parameter to acc. to CT neu.pnt sett..
Then, the positive active-power flow direction of the power criterion is the same as the standard forward
direction of the protection functionality. Consequently, the Underfrequency load shedding function
sheds the feeder when the positive power-flow direction is from the medium-voltage busbar to the
feeder.

858 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

Parameter: Power criterion, Phi (power criterion), Min. current (power crit.)

• Default setting (_:18121:103) Power criterion = yes

• Default setting (_:18121:106) Phi (power criterion) = -5°

• Default setting (_:18121:104) Min. current (power crit.) = 0.050 p.u.


The power criterion evaluates the power-flow direction as a blocking criterion for the protection stages.

• With the Power criterion parameter, you configure whether to apply the power criterion or not.
If a feeder can deliver active power towards the busbar, or if the medium-voltage busbar can deliver
active power to the high-voltage busbar, Siemens recommends using the power criterion to exclude the
feeder or the medium-voltage busbar from being shed under this condition. If a feeder or the medium-
voltage busbar is always consuming active power, the power criterion is not required.

• With the Phi (power criterion) parameter, you decide whether the protection stage is blocked or
released in the case of low active-power flow. If the active-power flow is low, the determined active
power-flow direction is not always reliable.
For Phi (power criterion) ≤ 0, the protection stage is released for a clear forward active power-
flow direction. If the active power-flow direction is not reliable, the protection stages are blocked. For
Phi (power criterion) > 0, the behavior is the contrary.
The Phi (power criterion) parameter can be set depending on your philosophy.

• With the Min. current (power crit.) parameter, you set the minimum positive-sequence current
threshold to achieve a reliable active-power criterion result. The Min. current (power crit.)
parameter is set as a per-unit value related to the rated current of the connected current measuring
point. Siemens recommends using the default setting.

Parameter: df/dt-rising blk. criterion, df/dt-rising blk. threshold, df/dt-falling blk.


criterion, df/dt-falling blk. threshold

• Default setting (_:18121:107) df/dt-rising blk. criterion = no

• Default setting (_:18121:108) df/dt-rising blk. threshold = 1.0 Hz/s

• Default setting (_:18121:109) df/dt-falling blk. criterion = no

• Default setting (_:18121:110) df/dt-falling blk. threshold = 3.0 Hz/s


If the change rate of df/dt is too high, the Underfrequency load shedding function may not be applicable
anymore.
With the parameters df/dt-rising blk. criterion and df/dt-falling blk. criterion, you
determine whether to check the df/dt-rising blocking and the df/dt-falling blocking.
With the parameters df/dt-rising blk. threshold and df/dt-falling blk. threshold, you set
the threshold rates of df/dt-rising and df/dt-falling.

Parameter: df/dt measuring window

• Default setting (_:18121:111) df/dt measuring window = 5 periods


With the df/dt measuring window parameter, you optimize the measuring accuracy or the pickup time of
the function.
The default setting provides the maximum measuring accuracy. If you do not have specific requirements for a
decreased pickup time, Siemens recommends using the default setting.
For a non-sensitive setting (high threshold value), you can set the df/dt measuring window parameter to
a value which is smaller than 5 periods.

Parameter: df/dt dropout differential

• Default setting (_:18121:112) df/dt dropout differential = 0.1 Hz/s


With the df/dt dropout differential parameter, you define the dropout threshold of the parameters
df/dt-rising blk. threshold and df/dt-falling blk. threshold.

SIPROTEC 5, 7SJ82/7SJ85, Manual 859


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

The default setting is a reasonable value. Siemens recommends using the default setting.

6.35.4 Stage Description

6.35.4.1 Description

Logic of the Stage

[lo_load shedding_stage, 1, en_US]

Figure 6-227 Logic Diagram of the Underfrequency Load Shedding Stage

Pickup and Operate


If the following 3 conditions are all fulfilled, a Pickup indication is issued:

• The frequency value drops below the Threshold.

• The Blocking input from the function block General is inactive.

• The preceding 2 conditions are fulfilled during the configured number of frequency measurement cycles
(cycle time = 10 ms). You can set the number with the parameter f< stabilization counter.

860 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

If the Pickup signal is maintained during the Operate delay time, an Operate indication is issued.

Exclusive Stage Activation


A load-shedding schema defines in which order feeders (power consumers) are disconnected. To not discrimi-
nate power consumers, this order is changed regularly. The mechanism of exclusive stage activation supports
this order change efficiently.
Even though multiple protection stages are instantiated and their Mode parameters are set to on, you can only
activate one stage at a time via the exclusive stage activation in an Underfrequency load shedding function.
The exclusive stage activation comprises the following input signals:

• The SPS signal >Exclusive activation which is offered in the protection stage.

• The SPC signal Exclusive activation which is offered in the protection stage.
This SPC signal allows the exclusive stage activation from a station controller.

• The SPS signal >Activate all stages which is offered in the function block General.
The protection stage which receives the newest SPS signal >Exclusive activation or SPC signal Exclu-
sive activation remains active and all other stages are deactivated. If 2 or more protection stages simul-
taneously receive the SPS signals >Exclusive activation and/or the SPC signals Exclusive activa-
tion, only the protection stage with the largest stage number is activated.
If the SPS signal >Activate all stages is activated, the exclusive stage activation is reset, that is, all
protection stages whose Mode parameters are set to on become active again.
After a normal device restart (reset), the statuses of the protection stages which were influenced by the SPS
signal >Exclusive activation or the SPC signal Exclusive activation are still maintained.
After an initial startup, the exclusive stage activation is reset.

EXAMPLE
Configured protection stages: Protection stages 1 to 8
Protection stages whose Mode parameters are set to on: Protection stages 1 to 8

The following cases occur in sequence:

• Case 1:
Scenario: In the protection stage 1, the SPS signal >Exclusive activation or the SPC signal
Exclusive activation is activated.
Result: The protection stage 1 remains active and stages 2 to 8 are deactivated.

• Case 2:
Scenario: In the protection stage 2, the SPS signal >Exclusive activation or the SPC signal
Exclusive activation is activated.
Result: The protection stage 2 is activated, the stage 1 is deactivated, and stages 3 to 8 remain deacti-
vated.

• Case 3:
Scenario: The SPS signal >Activate all stages is activated.
Result: The protection stages 1 to 8 are activated.

• Case 4:
Scenario: In the protection stages 2 to 4, the SPS signal >Exclusive activation or the SPC signal
Exclusive activation is activated simultaneously.
Result: The protection stage 4 is activated and the other stages are deactivated.

• Case 5:
Scenario: A normal device restart (reset) occurs.
Result: After the device restart, the protection stage 4 remains activated and the other stages remain
deactivated.

SIPROTEC 5, 7SJ82/7SJ85, Manual 861


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

Blocking the Stage


In the event of blocking, the picked up stage will be reset. The following blocking options are available for the
stage:

• Via the binary input signal >Block stage from an external or internal source

• Via the Inactive input from the function block General

Behavior on Leaving the Operating Range


The sampling frequency tracking makes a wide frequency-operating range possible. If the stage has picked up
before leaving the frequency-operating range, the pickup is maintained. The Pickup signal is reset when a
blocking condition becomes active.

6.35.4.2 Application and Setting Notes

Parameter: Threshold

• Default setting (_:18151:3) Threshold = 49.00 Hz for frated = 50 Hz

With the Threshold parameter, you define the underfrequency pickup value of the stage. The specific value
depends on the application and the total number of the stages applied in parallel.

Parameter: Operate delay

• Default setting (_:18151:6) Operate delay = 0.10 s


Set the Operate delay parameter for the specific application.

Parameter: Dropout differential

• Default setting(_:18151:5) Dropout differential = 20 mHz


With the Dropout differential parameter, you define the dropout threshold. For example, if you set the
Threshold to 49.00 Hz and the dropout differential to 20 mHz, the stage drops out at 49.02 Hz.
Due to the high-precision frequency measurement, the setting value can remain at the default value of
20 mHz.

Parameter: Operate & flt.rec. blocked

• Default setting (_:18151:2) Operate & flt.rec. blocked = no


With the Operate & flt.rec. blocked parameter, you can block the operate indication, the fault
recording, and the fault log.

Parameter: f< stabilization counter

• Default setting(_:18121:113) f< stabilization counter = 6


You can configure the f< stabilization counter parameter in the function block General.
With the f< stabilization counter parameter, you set the number of measurement cycles in which the
measured frequency value must be lower than the frequency threshold to meet the pickup condition. With
this setting, you can optimize the pickup-condition reliability versus the pickup time.
The measuring cycle time is 10 ms. With the default setting of 6, the pickup time is the sum of the inherent
frequency measuring time (approx. 10 ms to 30 ms) plus the 6 times measuring repetition of 60 ms, which is
70 ms to 90 ms in total.
In order to avoid a wrong pickup in case of a phase jump, Siemens recommends setting the value of the f<
stabilization counter parameter not below 5.

862 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

6.35.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:18121:101 General:Minimum 0.300 p.u. to 0.900 p.u. 0.700 p.u.
voltage
_:18121:103 General:Power criterion • no yes
• yes
_:18121:104 General:Min. current 0.020 p.u. to 0.200 p.u. 0.050 p.u.
(power crit.)
_:18121:115 General:Positive power • inv. to CT neu.pnt sett. inv. to CT
direction neu.pnt sett.
• acc. to CT neu.pnt sett.
_:18121:106 General:Phi (power crite- -30° to 30° -5°
rion)
_:18121:107 General:df/dt-rising blk. • no no
criterion
• yes
_:18121:108 General:df/dt-rising blk. 0.1 Hz/s to 20.0 Hz/s 1.0 Hz/s
threshold
_:18121:109 General:df/dt-falling blk. • no no
criterion
• yes
_:18121:110 General:df/dt-falling blk. 0.1 Hz/s to 20.0 Hz/s 3.0 Hz/s
threshold
_:18121:111 General:df/dt measuring 2 periods to 5 periods 5 periods
window
_:18121:112 General:df/dt dropout 0.02 Hz/s to 0.99 Hz/s 0.10 Hz/s
differential
_:18121:113 General:f< stabilization 1 to 20 6
counter
Stage 1
_:18151:1 Stage 1:Mode • off off
• on
• test
_:18151:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:18151:3 Stage 1:Threshold 40.00 Hz to 70.00 Hz 49.00 Hz
_:18151:5 Stage 1:Dropout differ- 20 mHz to 2000 mHz 20 mHz
ential
_:18151:6 Stage 1:Operate delay 0.00 s to 60.00 s 0.10 s

6.35.6 Information List

No. Information Data Class Type


(Type)
General
_:18121:501 General:>Activate all stages SPS I
_:18121:300 General:V1< block SPS O
_:18121:301 General:Power crit. blocking SPS O
_:18121:302 General:I1< blocking SPS O
_:18121:303 General:df/dt-rising blocking SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 863


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.35 Underfrequency Load Shedding

No. Information Data Class Type


(Type)
_:18121:304 General:df/dt-falling blocking SPS O
_:18121:305 General:df/dt MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:18151:81 Stage 1:>Block stage SPS I
_:18151:500 Stage 1:>Block delay & op. SPS I
_:18151:502 Stage 1:>Exclusive activation SPS I
_:18151:347 Stage 1:Exclusive activation SPC C
_:18151:54 Stage 1:Inactive SPS O
_:18151:52 Stage 1:Behavior ENS O
_:18151:53 Stage 1:Health ENS O
_:18151:55 Stage 1:Pickup ACD O
_:18151:56 Stage 1:Operate delay expired ACT O
_:18151:57 Stage 1:Operate ACT O

864 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.36 Rate of Frequency Change Protection

6.36 Rate of Frequency Change Protection

6.36.1 Overview of Functions

The function Rate of frequency change protection is used to:

• Detect a frequency change quickly

• Prevent the system from not secure states caused by unbalance between the generated and consumed
active power

• Network decoupling

• Load shedding

6.36.2 Structure of the Function

The function Rate of frequency change protection can be used in protection function groups containing a
3‑phase voltage measurement.
2 function block types are available:

• df/dt rising

• df/dt falling
The function Rate of frequency change protection is preconfigured by the manufacturer with 1 df/dt rising
stage and 1 df/dt falling stage. A maximum of 5 df/dt rising stages and 5 df/dt falling stages can operate simul-
taneously within the function. Both of the function block types are similar in structure.
Undervoltage check and df/dt calculation are general functionalities and take place on the function level. All
stages use these general functionalities.

[dwdfdt01-160113-01.tif, 1, en_US]

Figure 6-228 Structure/Embedding of the Function

6.36.3 General Functions (Undervoltage Test, df/dt Calculation)

6.36.3.1 Description

Logic
The following figure represents the logic of undervoltage check and df/dt calculation. It applies to all types of
stages.

SIPROTEC 5, 7SJ82/7SJ85, Manual 865


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.36 Rate of Frequency Change Protection

[lodfdtgf-160113-01.tif, 1, en_US]

Figure 6-229 Logic Diagram of General Functionality

Measurand
This function uses the frequency calculated via the angle difference algorithm.
For more information, refer to chapter 6.33.3 Overfrequency-Protection Stage.
The frequency difference is calculated over a settable time interval (default setting: 5 periods).
The ratio between the frequency difference and the time difference reflects the frequency change which can
be positive or negative.
A stabilization counter works to avoid overfunction. This counter is increased if the set threshold value is
exceeded. If the value drops below the threshold value, the counter is reset immediately. The counter is set to
8 internally and is activated at each half system cycle.

Undervoltage Blocking
If the measuring voltage drops below the Minimum voltage, the Rate of frequency change protection is
blocked because precise frequency values cannot be calculated anymore.

Functional Measured Value

Value Description
df/dt Calculated rate of frequency change

6.36.3.2 Application and Setting Notes

Parameter: Minimum voltage

• Recommended setting value (_:13171:101) Minimum voltage = 37.500 V


For the Undervoltage blocking, 65 % of the rated voltage of the protected object is recommended.
The method of measurement uses the phasor of the positive-sequence voltage. When determining the setting
value, keep in mind that the absolute value of the sound positive-sequence voltage is equal to the absolute
value of the phase-to-ground voltage. The default setting is referred to this value.

Parameter: Measuring window

• Default setting (_:13171:137) Measuring window = 5 periods


You can use the Measuring window parameter to optimize the measuring accuracy or the pickup time of
the function. For information regarding pickup time and measuring accuracy, refer to the technical data.
The default setting provides maximum measuring accuracy. If you do not have specific requirements for a
decreased pickup time, Siemens recommends using the default setting.

866 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.36 Rate of Frequency Change Protection

The default setting is a reasonable compromise between measuring accuracy and pickup time. For a non-
sensitive setting (high threshold value), you can set the parameter Measuring window to a smaller value.

6.36.4 Stage Description

6.36.4.1 Description

Logic of the Stage

[lodfdtst-160113-01.tif, 1, en_US]

Figure 6-230 Logic Diagram of Rate of Frequency Change Protection

(1) For the stage type df/dt rising, the value df/dt rising is used.

Frequency Rising/Falling
The stage df/dt falling is used to detect frequency falling and the stage df/dt rising is used to detect
frequency rising.
You set the threshold value as an absolute value. You define the frequency-change direction via the selected
stage type.

Blocking of the Stage


The following blockings reset the picked up stage completely:

• Via the binary input signal >Block stage

• Via the undervoltage blocking when the voltage drops below the Minimum voltage

SIPROTEC 5, 7SJ82/7SJ85, Manual 867


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.36 Rate of Frequency Change Protection

6.36.4.2 Application and Setting Notes

Parameter: Threshold

• Default setting (_:13231:3) Threshold = 3.000 Hz/s


The pickup value depends on the application and is determined by power-system conditions. In most cases, a
network analysis will be necessary. A sudden disconnection of loads leads to a surplus of active power. The
frequency rises and causes a positive frequency change. On the other hand, a failure of generators leads to a
deficit of active power. The frequency drops and results in a negative frequency change.
The following relations can be used as an example for estimation. They apply for the change rate at the begin-
ning of a frequency change (approximate 1 s).

Where:
frated Rated frequency
ΔP Active power change
ΔP = PConsumption - PGeneration
Srated Rated apparent power of the machines
H Inertia constant

Typical data for H:


For hydro generators (salient-pole machines) H = 1.5 s to 6 s
For turbine-driven generators (non-salient pole rotors) H = 2 s to 10 s
For industrial turbine-driven generators H = 3 s to 4 s

EXAMPLE

frated = 50 Hz
H=3s
Case 1: ΔP/Srated = 0.12
Case 2: ΔP/Srated = 0.48
Case 1: df/dt = -1 Hz/s
Case 2: df/dt = -4 Hz/s

Parameter: Operate delay

• Default setting (_:13231:6) Operate delay = 1.00 s


You can use the Operate delay parameter to avoid overfunction due to disturbing influences (for example,
switching operations). If the protection function is supposed to respond quickly, set the Operate delay
parameter to 0 s.
For monitoring small changes (< 1 Hz/s), a small time delay is useful to avoid overfunctioning.

Parameter: Dropout differential

• Recommended setting value (_:13231:4) Dropout differential = 0.10 Hz/s


You can use the Dropout differential parameter to define the dropout value. The recommended value
is 0.10 Hz/s.

868 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.36 Rate of Frequency Change Protection

NOTE

i In case of power-system incidents, especially in case of transmission incidents and influence of voltage-
stabilizing measures via power-electronic components (reactive-power compensation through SVC), the
magnitude and the phase angle of the voltage can change. Sensitive settings can lead to overfunction.
Therefore, it is reasonable to block the Rate of Frequency Change Protection if other protection func-
tions, for example, residual voltage or negative-sequence voltage, pick up. To do this, use the blocking
input >Block stage and connect it via CFC.

6.36.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:13171:101 General:Minimum 3.000 V to 175.000 V 37.500 V
voltage
_:13171:137 General:Measuring 2 periods to 5 periods 5 periods
window
df/dt falling1
_:13231:1 df/dt falling1:Mode • off off
• on
• test
_:13231:2 df/dt falling1:Operate & • no no
flt.rec. blocked
• yes
_:13231:3 df/dt falling1:Threshold 0.100 Hz/s to 20.000 Hz/s 3.000 Hz/s
_:13231:4 df/dt falling1:Dropout 0.02 Hz/s to 0.99 Hz/s 0.10 Hz/s
differential
_:13231:6 df/dt falling1:Operate 0.00 s to 60.00 s 1.00 s
delay
df/dt rising1
_:13201:1 df/dt rising1:Mode • off off
• on
• test
_:13201:2 df/dt rising1:Operate & • no no
flt.rec. blocked
• yes
_:13201:3 df/dt rising1:Threshold 0.100 Hz/s to 20.000 Hz/s 3.000 Hz/s
_:13201:4 df/dt rising1:Dropout 0.02 Hz/s to 0.99 Hz/s 0.10 Hz/s
differential
_:13201:6 df/dt rising1:Operate 0.00 s to 60.00 s 1.00 s
delay

6.36.6 Information List

No. Information Data Class Type


(Type)
General
_:13171:300 General:Undervoltage blocking SPS O
_:13171:301 General:df/dt MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O

SIPROTEC 5, 7SJ82/7SJ85, Manual 869


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.36 Rate of Frequency Change Protection

No. Information Data Class Type


(Type)
_:4501:57 Group indicat.:Operate ACT O
df/dt falling1
_:13231:81 df/dt falling1:>Block stage SPS I
_:13231:54 df/dt falling1:Inactive SPS O
_:13231:52 df/dt falling1:Behavior ENS O
_:13231:53 df/dt falling1:Health ENS O
_:13231:55 df/dt falling1:Pickup ACD O
_:13231:56 df/dt falling1:Operate delay expired ACT O
_:13231:57 df/dt falling1:Operate ACT O
df/dt rising1
_:13201:81 df/dt rising1:>Block stage SPS I
_:13201:54 df/dt rising1:Inactive SPS O
_:13201:52 df/dt rising1:Behavior ENS O
_:13201:53 df/dt rising1:Health ENS O
_:13201:55 df/dt rising1:Pickup ACD O
_:13201:56 df/dt rising1:Operate delay expired ACT O
_:13201:57 df/dt rising1:Operate ACT O

870 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.37 Vector-Jump Protection

6.37 Vector-Jump Protection

6.37.1 Overview of Functions

The Vector-jump protection function:

• Is used for network decoupling of the power generating unit in case of a load loss

• Evaluates the phase-angle jump of the voltage phasors

6.37.2 Structure of the Function

The Vector-jump protection function can be used in the following function groups:

• Voltage-current 3-phase

• Voltage 3-phase
The Vector-jump protection function comes factory-set with a Δφ stage.
The following stages can operate simultaneously within the function:

• 1 Δφ stage

• 1 I1 < Release stage

[dw_VJP_Structure, 1, en_US]

Figure 6-231 Structure/Embedding of the Function

6.37.3 General Functionality

6.37.3.1 Description

Basic Principle of Vector-Jump Protection


The following 2 figures show the basic principle of the Vector-jump protection function.
The following figure shows the voltage vector of the steady state condition. The load current causes a voltage
drop between the internal voltage Vp and the generator terminal voltage V.
If the load is switched off, the following situations occur:

• The current is reduced.

• A smaller voltage drop is caused.

SIPROTEC 5, 7SJ82/7SJ85, Manual 871


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.37 Vector-Jump Protection

[dw_load loss, 1, en_US]

Figure 6-232 Voltage Vector of the Steady State

The following figure shows the situations after the load is switched off:

• The terminal voltage V changes to V'.

• An additional phase-angle jump occurs.


A phase-angle jump occurs with load loss and is the evaluation criterion for the Vector-jump protection func-
tion. If the phase-angle differential exceeds a set threshold, the generator circuit breaker or the circuit breaker
of the system switch opens. Therefore, the generator unit can be protected against unacceptable stress.

[dw_vector change, 1, en_US]

Figure 6-233 Vector Change after the Load Shedding

Table 6-17 Vector Description

Vector Description
Vp Vector of the generator internal voltage (rotor voltage)
V Vector of the generator terminal voltage
ΔV Vector of the voltage differential
V' Vector of the terminal voltage after the load shedding
ΔV' Vector of the voltage differential after the load shedding

872 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.37 Vector-Jump Protection

The following measures are applied to avoid unwanted tripping:

• Correction of steady-state deviations from rated frequency

• Frequency operating range limited to frated ± 3 Hz

• High measuring accuracy by using frequency-tracked measured values and evaluation of the positive-
sequence phasor

• Enabling the minimum voltage for the Vector-jump protection function

• Blocking the function when the primary voltage is switched on or off as switching can lead to a phase-
angle jump

Logic

[lo_VJP_General, 1, en_US]

[lo_VJP_General_2, 1, en_US]

Figure 6-234 Logic Diagram of the General Functionality

Phase-Angle Calculation
The phase-angle differential is calculated at different time intervals (t-T, t-2T, t-3T) from the vector of the posi-
tive-sequence voltage via a delta-interval measurement. With the current measured power frequency, the
measuring errors of the angle measurement caused by frequency deviations are compensated.

Range
If the measured frequency or voltage is below the set threshold, the Vector-jump protection is blocked.
The voltage and frequency bands have the following limits:

• The threshold of the voltage band is configurable.

• The frequency band ranges is fixed from frated - 3 Hz to frated + 3 Hz.

Measurand
The general functionality calculates the phase-angle displacement Δφ and sends it to the Δφ stage. Δφ is used
for comparison with the parameter Threshold Δφ. Δφ is displayed in the functional measured value and can
be routed in a fault record and displayed in the fault log.

SIPROTEC 5, 7SJ82/7SJ85, Manual 873


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.37 Vector-Jump Protection

The functional measured values of Δφ in HMI are displayed differently in the following situations:

• If the Vector-jump protection function is inactive, the function value of Δφ is displayed as “---”

• If the Vector-jump protection function is active and has not picked up, the functional measured value of
Δφ is displayed as 0.0°

• If the Vector-jump protection function is active and has picked up, the functional measured value of Δφ
is displayed as a calculated value (for example, 12.0°) and remains unchanged until the next pickup of
the Vector-jump protection function.

6.37.3.2 Application and Setting Notes

Parameter: Threshold V1 min

• Default setting (_:2311:102) Threshold V1 min = 46.189 V


With the parameter Threshold V1 min, you can define the minimum threshold of the voltage band.
The setting value is closed to the allowed lower limit of the voltage band. The default setting is 80 % of the
rated positive-sequence voltage. The value of the rated positive-sequence voltage is 100 V/√3.

Parameter: Threshold V1 max

• Default setting (_:2311:101) Threshold V1 max = 75.058 V


With the parameter Threshold V1 max, you can define the maximum threshold of the voltage band.
The setting value is closed to the allowed higher limit of the voltage band. The default setting is 130 % of the
rated positive-sequence voltage. The value of the rated positive-sequence voltage is 100 V/√3.

Parameter: T Block

• Default setting (_:2311:6) T Block = 0.10 s


With the parameter T Block, you set the dropout delay of the Δφ stage.
When voltages are connected or disconnected, the overfunction can be avoided with the timer T Block.
Siemens recommends to use the default setting of the parameter T Block. Keep in mind that the parameter
T Block has always to be set to 2 cycles more than the measuring window for vector-jump measurement.

6.37.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:102 General:Threshold V1 0.300 V to 175.000 V 46.189 V
min
_:2311:101 General:Threshold V1 0.300 V to 175.000 V 75.058 V
max
_:2311:6 General:T Block 0.00 s to 60.00 s 0.10 s

6.37.3.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:301 General:Δφ MV O
_:2311:300 General:Δφ out of meas. range SPS O

874 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.37 Vector-Jump Protection

6.37.4 Δφ Stage

6.37.4.1 Description

Logic

[lo_DeltaPhi_Stage, 1, en_US]

Figure 6-235 Logic Diagram of the Δφ Stage

In the logic diagram, the I1 < Release stage is instantiated. You can find more information in chapter
6.37.5.1 Description.
If the I1 < Release stage is not instantiated, the AND operation has no influence. The Operate indication is
issued under the following conditions:

• The parameter Operate & flt.rec. blocked is set to no.

• The operate delay expires.

• The phase-angle differential exceeds the parameter Threshold Δφ.

Measurand
The Δφ stage gets the measured value Δφ from the general functionality.

Pickup
The Δφ stage compares the value of the vector jump Δφ with the Threshold Δφ.
If the value of the Threshold Δφ is exceeded, the pickup delay starts.

SIPROTEC 5, 7SJ82/7SJ85, Manual 875


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.37 Vector-Jump Protection

The vector jump Δφ is stored in an RS flip-flop. Trippings can be delayed by the associated time delay.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. The following blocking options are available for the
stage:

• The parameter Mode is in the state off.

• The binary input signal >Block stage is active.

• The signal Δφ out of meas. range is active.

6.37.4.2 Application and Setting Notes

Parameter: Operate & flt.rec. blocked

• Default setting (_:19261:2) Operate & flt.rec. blocked = no


With the parameter Operate & flt.rec. blocked, you can block the operate indication, the fault
recording, and the fault log. If you want the stage to have a warning indication only, set the parameter
Operate & flt.rec. blocked to yes.

Parameter: Threshold Δφ

• Default setting (_:19261:101) Threshold Δφ = 10°


With the parameter Threshold Δφ, you can set the pickup value of the Δφ stage.
The parameter value to be set for the vector jump depends on the supply and load conditions. Load changes
cause a jump of the voltage vector. The value to be set must be established in accordance with the particular
power system. An estimation can be done based on the system equivalent circuit in Figure 6-233. A network
calculation considering the relevant source and load situations will be more precise.
If the setting for the parameter Threshold Δφ is too sensitive, every time loads are connected or discon-
nected, the protection function performs a network decoupling. Therefore, If no other calculated value is
applicable to the setting of this parameter, Siemens recommends using the default setting.

Parameter: Operate delay

• Default setting (_:19261:6) Operate delay = 0.00 s


With the parameter Operate delay, you can set the operate delay of the Δφ stage. For the tripping stage,
set the operate delay between 0.00 s and 60.00 s.
Siemens recommends the default setting.
The following requirements can necessitate a change of the parameter Operate delay with respect to the
default setting:

• The operate indication should be transmitted with delay to a programmable logic.

• There shall be enough time for an external blocking to take effect.

Parameter: T Reset

• Default setting T Reset = 5.00 s


With the parameter T Reset, you can set the reset time for the Pickup indication stored in the RS flip-flop.
When the timer T Reset expires, the protection function is reset automatically.
The reset time meets the following conditions:

• The reset time depends on the decoupling requirements

• The reset time must expire before the circuit breaker is reclosed

876 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.37 Vector-Jump Protection

6.37.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Stage Δφ 1
_:19261:1 Stage Δφ 1:Mode • off off
• on
• test
_:19261:2 Stage Δφ 1:Operate & • no no
flt.rec. blocked
• yes
_:19261:101 Stage Δφ 1:Threshold 2.0° to 30.0° 10.0°
Δφ
_:19261:6 Stage Δφ 1:Operate 0.00 s to 60.00 s 0.00 s
delay
_:19261:7 Stage Δφ 1:T Reset 0.00 s to 60.00 s 5.00 s

6.37.4.4 Information List

No. Information Data Class Type


(Type)
Stage Δφ 1
_:19261:81 Stage Δφ 1:>Block stage SPS I
_:19261:54 Stage Δφ 1:Inactive SPS O
_:19261:52 Stage Δφ 1:Behavior ENS O
_:19261:53 Stage Δφ 1:Health ENS O
_:19261:55 Stage Δφ 1:Pickup ACD O
_:19261:56 Stage Δφ 1:Operate delay expired ACT O
_:19261:57 Stage Δφ 1:Operate ACT O

6.37.5 I1 < Release Stage

6.37.5.1 Description

Logic

[lo_UndercurrentRelease_Stage, 1, en_US]

Figure 6-236 Logic Diagram of the I1 < Release Stage

The I1 < Release stage is an optional stage and is used to reduce the risk of overfunction.
The indication Undercurrent release is an additional safety criterion to avoid an unexpected trip. It indi-
cates a load loss of the connected line to the system and the phase-angle criterion is released. If any load in
the network is switched on or off, an unexpected trip can occur.
If the I1 < Release stage is not instantiated, the Δφ stage works without current-flow criterion. You can find
more information in chapter 6.37.4.1 Description.
If the positive-sequence current falls below the parameter I< Threshold, the message Undercurrent
release is issued and is forwarded to the Δφ stage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 877


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.37 Vector-Jump Protection

6.37.5.2 Application and Setting Notes

Parameter: I< Threshold

• Default setting (_:101) I< Threshold = 0.100 A


With the parameter I< Threshold, you can set the pickup value of the I < Release stage corresponding to
the specific application. Consider that the current measuring point must be on the line side. The parameter I<
Threshold depends on the load situation.

6.37.5.3 Settings

Addr. Parameter C Setting Options Default Setting


I1 < Release #
_:101 I1 < Release #:I< 1 A @ 100 Irated 0.030 A to 35.000 A 0.100 A
Threshold 5 A @ 100 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A

6.37.5.4 Information List

No. Information Data Class Type


(Type)
I1 < Release #
_:300 I1 < Release #:Undercurrent release SPS O

878 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

6.38 Power Protection (P,Q), 3-Phase

6.38.1 Overview of Functions

The 3-phase power protection (P, Q) function (ANSI 32) is used to:

• Detect whether the active or reactive power rises above or drops below a set threshold

• Monitor agreed power limits and output warning indications

• Detect both active and reactive power feedback in the power systems or on electric machines

• Detect machines (motors, generators) running without load and output an indication to shut them down.

• Be integrated into any automation solution, for example, to monitor very specific power limits (further
logical processing in CFC)

6.38.2 Structure of the Function

The 3-phase power protection (P, Q) function can be integrated in function groups, which provide measured
voltages and currents of the 3-phases for calculation of the power.
The 3-phase power protection (P,Q) function comes with one factory-set stage each for the active and the
reactive power. The following stages are preconfigured:

• Power P>

• Power Q>

• Power P<

• Power Q<
A maximum of 4 active power stages and 4 reactive power stages can be operated simultaneously in the func-
tion. The tripping stages have an identical structure.

[dw_GPP 3-phase structure, 2, en_US]

Figure 6-237 Structure/Embedding of the Function

Logical Combination of Output Signals


The operate indications of the active and reactive power stage(s) can be logically combined in CFC. When an
operate indication is present in both the active and the reactive power stage, an alarm indication is generated.

SIPROTEC 5, 7SJ82/7SJ85, Manual 879


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

[lo_GPP operate indication logical comb, 2, en_US]

Figure 6-238 Logical Combination of Operate Indications in CFC

6.38.3 Active Power Stage

Logic of a Stage

[lo_3-phase active power, 2, en_US]

Figure 6-239 Logic Diagram of the Active Power Stage (Stage Type: Power P<)

Measured Value
The Measured value parameter is used to specify which measured power value is analyzed by the tripping
stage. Possible settings are positive seq. power and the phase-selective powers power of phase A,
power of phase B or power of phase C.

Pickup Characteristic
With the stage type you specify if the stage work as a greater stage (stage type: Power P>) or as a smaller
stage (stage type: Power P<).

880 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

The Threshold parameter is used to define the pickup threshold of the stage. The Tilt power charac-
teristic parameter is used to define the tilt of the pickup characteristic. The figure below shows the defini-
tion of the signs.

[dw_tilt-power active power, 2, en_US]

Figure 6-240 Tilt-Power Characteristic

Pickup
The stage compares the selected power value with the set Threshold. Depending on the stage type (Power
P> or Power P<) being above or falling below the threshold value will lead to a pickup.

Dropout Delay
A delay can be set for the dropout when the measured value falls below the dropout threshold. The pickup is
maintained for the specified time. The time delay of the tripping (parameter Operate delay) continues to
run. Once the Operate delay has elapsed, the stage trips.

Blocking the Stage


In the event of blocking, a picked-up stage is reset. The following blocking options are available for the stage:

• Internally or externally via the binary input signal >Block stage

• The frequency is less than or equal to 10 Hz.

SIPROTEC 5, 7SJ82/7SJ85, Manual 881


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

6.38.4 Reactive Power Stage

Logic of a Stage

[lo_3phase reactive power, 2, en_US]

Figure 6-241 Logic Diagram of the Reactive Power Stage (Stage Type: Power Q<)

Measured Value
The Measured value parameter is used to specify which measured power value is processed by the tripping
stage. Possible settings are positive seq. power and the phase-selective powers power of phase A,
power of phase B or power of phase C.

Pickup Characteristic
With the stage type you specify if the stage work as a greater stage (stage type: Power Q>) or as a smaller
stage (stage type: Power Q<).
The Threshold parameter is used to define the pickup threshold of the stage. The Tilt power charac-
teristic parameter is used to define the tilt of the pickup characteristic. The figure below shows the defini-
tion of the signs.

882 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

[dw_tilt-power reactive power, 2, en_US]

Figure 6-242 Tilt-Power Characteristic

Pickup
The stage compares the selected power value with the set Threshold. Depending on the stage type (Power
Q> or Power Q<) being above or falling below the threshold value will lead to a pickup.

Dropout Delay
A delay can be set for the dropout when the measured value falls below the dropout threshold. The pickup is
maintained for the specified time. The time delay of the tripping (parameter Operate delay) continues to
run. Once the Operate delay has elapsed, the stage trips.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. Blocking the stage is possible externally or internally
via the binary input signal >Block stage.

6.38.5 Application Example

The setting of the function will be explained using an active/reactive power range as an example. If the appa-
rent power phasor is within the power range (in Figure 6-243 tripping zone defined by characteristics), an
alarm indication is generated. For this purpose, you have to make an AND operation of the stage indications of
the active and reactive power stage in CFC. The function used is 3-phase power measurement. Figure 6-243
shows the threshold values and the location of the characteristics in the PQ diagram.

SIPROTEC 5, 7SJ82/7SJ85, Manual 883


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

[dw_GPP PQ diagram, 2, en_US]

Figure 6-243 Pickup Values and Characteristic Curves

6.38.6 Setting Notes for the Active Power Stage

Stage Type
In the following example, a drop of the active power below a threshold is to be monitored. In the 3-phase
circuit breaker (P, Q) function, work with the stage type Power P<.

Parameter: Measured value

• Recommended setting value (_:6271:105) Measured value = positive seq. power


The Measured value parameter is used to specify which measured power value is evaluated. For 3-phase
measurement, Siemens recommends to evaluate the positive-sequence system power.

Parameter: Threshold

• Recommended setting value (_:6271:3) Threshold = 0 %


The Threshold parameter is used to define the pickup threshold of the active power stage. In the example,
the pickup characteristic runs across the point of origin of the coordinates. Set the parameter Threshold to
0 %.

NOTE

i If you use several settings groups, consider the following:

• The dropout value of a stage must have the same sign in all settings groups.

• Switching from a positive dropout value to a negative dropout value or vice versa is not allowed. As a
result, DIGSI reports an inconsistency.

• If you want to change the sign of the dropout value of a stage in an additional settings group, instan-
tiate a new stage and enable it. If the new stage should not be effective in another settings group,
disable the stage there.

Parameter: Dropout ratio

• Recommended setting value (_:6271:101) Dropout ratio = 1.05


A hysteresis of 5 % is sufficient for most applications. The setting value for the lower stage is therefore 1.05.

884 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

Parameter: Tilt power characteristic

• Recommended setting value (_:6271:103) Tilt power characteristic = +70°


The Tilt power characteristic parameter is used to incline the pickup characteristic. In the above
example, an inclination is required. The setting value is +70° (for a definition of the sign, see Figure 6-240).

Parameter: Dropout delay

• Recommended setting value (_:6271:7) Dropout delay = 20 ms


The Dropout delay parameter maintains the pickup even if the measured value drops momentarily below
the threshold value. A delay is required for very low pickup values to prevent a so-called chattering of the
function. In the example, the setting value is 20 ms.

Parameter: Operate delay

• Recommended setting value (_:6271:6) Operate delay = 100 ms


The Operate delay must be set for the specific application. In the example, a setting value of 100 ms has
been selected.

6.38.7 Setting Notes for the Reactive Power Stage

Stage Type
In the example, the reactive power is to be monitored if it falls below the threshold. In the 3-phase circuit
breaker (P, Q) function, work with the stage type Power Q<.

Parameter: Measured value

• Recommended setting value (_:6331:105) Measured value = positive seq. power


The Measured value parameter is used to specify which measured power value is evaluated. For 3-phase
measurement, Siemens recommends to evaluate the positive-sequence system power.

Parameter: Threshold

• Recommended setting value (_:6331:3) Threshold = 0 %


The Threshold parameter is used to define the pickup threshold of the reactive power stage. In the example,
the pickup characteristic runs across the point of origin of the coordinates. Set the parameter Threshold to 0
%.

NOTE

i If you use several settings groups, consider the following:

• The threshold value of a stage must have the same sign in all settings groups.

• Switching from a positive threshold value to a negative threshold value or vice versa is not allowed. As
a result, DIGSI reports an inconsistency.

• If you want to change the sign of the threshold value of a stage in an additional settings group, instan-
tiate a new stage and enable it. If the new stage should not be effective in another settings group,
disable the stage there.

Parameter: Dropout ratio

• Recommended setting value (_:6331:101) Dropout ratio = 0.95


A hysteresis of 5 % is sufficient for most applications. The setting value for the lower stage is therefore 0.95.

SIPROTEC 5, 7SJ82/7SJ85, Manual 885


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

Parameter: Tilt power characteristic

• Recommended setting value (_:6331:103) Tilt power characteristic = +20°


The Tilt power characteristic parameter is used to incline the pickup characteristic. In the example
(see Figure 6-243), the power characteristic has a tilt of 20°. Set the Tilt power characteristic param-
eter to +20° (for a definition of the sign, see Figure 6-242).

Parameter: Dropout delay

• Recommended setting value (_:6331:7) Dropout delay = 20 ms


The Dropout delay parameter maintains the pickup even if the measured value drops momentarily below
the threshold value. A delay is required for very low pickup values to prevent a so-called chattering of the
function. In the example, the setting value is 20 ms.

Parameter: Operate delay

• Recommended setting value (_:6331:6) Operate delay = 100 ms


The Operate delay must be set for the specific application. In the example, a setting value of 100 ms has
been selected.

6.38.8 Settings

Addr. Parameter C Setting Options Default Setting


Power P> 1
_:6241:1 Power P> 1:Mode • off off
• on
• test
_:6241:2 Power P> 1:Operate & • no no
flt.rec. blocked
• yes
_:6241:104 Power P> 1:Measured value • power of phase A positive seq.
power
• power of phase B
• power of phase C
• positive seq. power
_:6241:3 Power P> 1:Threshold -200.0 % to 200.0 % 80.0 %
_:6241:101 Power P> 1:Dropout ratio 0.90 to 0.99 0.95
_:6241:103 Power P> 1:Tilt power char- -89.0 ° to 89.0 ° 0.0 °
acteristic
_:6241:7 Power P> 1:Dropout delay 0.00 s to 60.00 s 0.00 s
_:6241:6 Power P> 1:Operate delay 0.00 s to 60.00 s 1.00 s
Power P< 1
_:6271:1 Power P< 1:Mode • off off
• on
• test
_:6271:2 Power P< 1:Operate & • no no
flt.rec. blocked
• yes
_:6271:105 Power P< 1:Measured value • power of phase A positive seq.
power
• power of phase B
• power of phase C
• positive seq. power

886 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

Addr. Parameter C Setting Options Default Setting


_:6271:3 Power P< 1:Threshold -200.0 % to 200.0 % 5.0 %
_:6271:101 Power P< 1:Dropout ratio 1.01 to 1.10 1.05
_:6271:103 Power P< 1:Tilt power char- -89.0 ° to 89.0 ° 0.0 °
acteristic
_:6271:7 Power P< 1:Dropout delay 0.00 s to 60.00 s 0.00 s
_:6271:6 Power P< 1:Operate delay 0.00 s to 60.00 s 1.00 s
Power Q> 1
_:6301:1 Power Q> 1:Mode • off off
• on
• test
_:6301:2 Power Q> 1:Operate & • no no
flt.rec. blocked
• yes
_:6301:105 Power Q> 1:Measured • power of phase A positive seq.
value power
• power of phase B
• power of phase C
• positive seq. power
_:6301:3 Power Q> 1:Threshold -200.0 % to 200.0 % 70.0 %
_:6301:101 Power Q> 1:Dropout ratio 0.90 to 0.99 0.95
_:6301:103 Power Q> 1:Tilt power -89.0 ° to 89.0 ° 0.0 °
characteristic
_:6301:7 Power Q> 1:Dropout delay 0.00 s to 60.00 s 0.00 s
_:6301:6 Power Q> 1:Operate delay 0.00 s to 60.00 s 1.00 s
Power Q< 1
_:6331:1 Power Q< 1:Mode • off off
• on
• test
_:6331:2 Power Q< 1:Operate & • no no
flt.rec. blocked
• yes
_:6331:105 Power Q< 1:Measured • power of phase A positive seq.
value power
• power of phase B
• power of phase C
• positive seq. power
_:6331:3 Power Q< 1:Threshold -200.0 % to 200.0 % -30.0 %
_:6331:101 Power Q< 1:Dropout ratio 0.90 to 0.99 0.95
_:6331:103 Power Q< 1:Tilt power -89.0 ° to 89.0 ° 0.0 °
characteristic
_:6331:7 Power Q< 1:Dropout delay 0.00 s to 60.00 s 0.00 s
_:6331:6 Power Q< 1:Operate delay 0.00 s to 60.00 s 1.00 s

6.38.9 Information List

No. Information Data Class Type


(Type)
Power P> 1
_:6241:81 Power P> 1:>Block stage SPS I
_:6241:54 Power P> 1:Inactive SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 887


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.38 Power Protection (P,Q), 3-Phase

No. Information Data Class Type


(Type)
_:6241:52 Power P> 1:Behavior ENS O
_:6241:53 Power P> 1:Health ENS O
_:6241:55 Power P> 1:Pickup ACD O
_:6241:56 Power P> 1:Operate delay expired ACT O
_:6241:57 Power P> 1:Operate ACT O
Power P< 1
_:6271:81 Power P< 1:>Block stage SPS I
_:6271:54 Power P< 1:Inactive SPS O
_:6271:52 Power P< 1:Behavior ENS O
_:6271:53 Power P< 1:Health ENS O
_:6271:55 Power P< 1:Pickup ACD O
_:6271:56 Power P< 1:Operate delay expired ACT O
_:6271:57 Power P< 1:Operate ACT O
Power Q> 1
_:6301:81 Power Q> 1:>Block stage SPS I
_:6301:54 Power Q> 1:Inactive SPS O
_:6301:52 Power Q> 1:Behavior ENS O
_:6301:53 Power Q> 1:Health ENS O
_:6301:55 Power Q> 1:Pickup ACD O
_:6301:56 Power Q> 1:Operate delay expired ACT O
_:6301:57 Power Q> 1:Operate ACT O
Power Q< 1
_:6331:81 Power Q< 1:>Block stage SPS I
_:6331:54 Power Q< 1:Inactive SPS O
_:6331:52 Power Q< 1:Behavior ENS O
_:6331:53 Power Q< 1:Health ENS O
_:6331:55 Power Q< 1:Pickup ACD O
_:6331:56 Power Q< 1:Operate delay expired ACT O
_:6331:57 Power Q< 1:Operate ACT O

888 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.39 Reverse-Power Protection

6.39 Reverse-Power Protection

6.39.1 Overview of Functions

The Reverse-power protection function (ANSI 32R):

• Monitors the motor operation of generators and thus detects driving-power failure

• Prevents endangering the turbine (e.g. the turbine-blade damage due to overheating) by opening the
circuit breaker of the system

• Protects a turbo-generator set


For the generator, there is a danger that the turbo-generator set accelerates and reaches overspeed in case of
an incorrect residual-steam passage (quick-stop valves defective) after the circuit breaker has opened. Conse-
quently, disconnecting the system (opening the circuit breaker of the system) shall only occur after reverse
power (active-power consumption) has been detected.

6.39.2 Structure of the Function

The Reverse-power protection function comes factory-set with 1 stage. A maximum of 2 stages can be oper-
ated simultaneously within the function.
In all function groups, the function works with a 3-phase voltage and current interface.

[dw_RPP structure, 3, en_US]

Figure 6-244 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 889


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.39 Reverse-Power Protection

6.39.3 General Functionality

6.39.3.1 Description

Logic of the Function

[lo_RPP general functionality, 2, en_US]

Figure 6-245 Logic Diagram of the Cross-Stage Functionality

Calculating the Reverse Power


The reverse-power protection calculates the active power from the symmetrical components of the funda-
mental components of the voltages and currents. It generates the average value of the active power over a
fixed number of cycles. Since positive-sequence variables are used for evaluation, the reverse power is deter-
mined independently of unbalance in currents or voltages. The frequency-tracking sampled values are used for
calculation. The determined reverse power corresponds to the load on the driving-power side. The calculated
active-power value corresponds to the total active power.
Taking the phase-displacement angle of the voltage and current transformers into account, the function calcu-
lates the exact active power even with a high apparent power and a small cos φ. A constant correction angle
φcorr makes correction possible. The influence of the current-transformer angle error is predominant here.
Determine this constant correction angle when you commission the protection device in the plant and adjust
it as specified in the table (see Table 11-1).

Power Calculation and Angle Correction


To satisfy the high measuring-accuracy requirements, the power measured value is additionally averaged over
16 cycles before it is supplied to the protection function. The active power is calculated from the symmetrical-
component vectors of voltage V1 and current I1. The total power is evaluated as power. The complex apparent
power results from the following relationship. The real component is the active power:
S = 3V 1 ⋅ I 1 * = 3V1 ejϕV ⋅ I1 e-jϕI = 3V1 I1 ej(ϕV-ϕI)
P = 3V1 I1 cos(φ V-φ I)

890 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.39 Reverse-Power Protection

The angle error between voltage transformer and current transformer has a strong influence on the measuring
accuracy. With the parameter (_:2311:101) Angle correction , you can correct the angle error. The
following 2 methods are possible here:

• Determine the angle error from the transformer test report data. Ask the transformer manufacturer for
these values when you order the transformer.

• While the generator is connected to the power system, measure to determine the angle error (see
chapter 11.14.2 Primary Test).
The influence on the power-system voltage makes it very difficult to test high-power generators with a meas-
urement while the generator is connected to the power system. In this case, you must determine the angle
error from the transformer test report data (see chapter 6.39.3.2 Application and Setting Notes). Alternatively,
you can use instrument transformers with small angle errors. This is ensured with class 0.2 instrument trans-
formers (voltage and current). The following equation describes the influence of the angle error:
P = 3V1 I1 cos(φ V + φ V,F - (φ I + φ I,F)) = 3V1 I1 cos(φ U - φ I + (φ V,F - φ I,F))
The angle error to be corrected results as:
ϕ Corr = φ V,F - φ I,F
To rotate in the correct direction, the correction angle is considered with inverted sign inside the unit.

Functional Measured Values


You can use the following functional measured values to check the behavior of the protection function and to
support commissioning. The total power is represented as the measured value.
Measured Value Description
P1fast Positive-sequence system active power Angle correction influences the measured
calculated per cycle value
Q1fast Positive-sequence system reactive power Angle correction influences the measured
calculated per cycle value
P1avg Positive-sequence system active power Input value for Reverse-power protection
calculated from P1fast over 16 cycles
Q1avg Positive-sequence system reactive power –
calculated from Q1fast over 16 cycles

6.39.3.2 Application and Setting Notes


In the general functionality, you can adjust the parameter (_:2311:101) Angle correction. The param-
eter results from the angle error of the primary transformer. In SIPROTEC 5, the input transformers are cali-
brated so that the angle error is negligible. You can assume an error of < 0.1°. There is no difference between
a protection input and an instrument-transformer input.

NOTE

i If you use class 0.2 instrument transformers on the primary side to avoid the influence of the angle, you
can connect a protection device with a protection current transformer without any problems.
Class 0.2 voltage transformers have a maximum admissible angle error of 10 min (0.17°). The angle error
of a class 0.2 measuring current transformer at rated current is approximately 10 min, at 0.2 Irated = 15 min,
and at 0.05 Irated = 30 min.

Parameter: Angle correction

• Default setting (_:2311:101) Angle correction = 0°


To determine the correction angle via measurement with the primary system, follow the instructions in
chapter 11.14.2 Primary Test.
You can use the method that is explained in the following section to derive the necessary correction angle
from the transformer measuring reports.

SIPROTEC 5, 7SJ82/7SJ85, Manual 891


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.39 Reverse-Power Protection

Example
This example uses a class 0.2 voltage transformer with a rated burden of 45 VA. The following data was taken
from the measuring report.

Table 6-18 For Phase A

V/Vn Sb = Sbr Sb = Sbr/4


ε v [%] δ v [min] ε v [%] δ v [min]
0.8 -0.14 0.31 0.16 -0.34
1 -0.15 0.43 0.15 -0.24
1.2 -0.16 0.68 0.14 -0.06

The values resulting for the phases B and C are almost identical.
Furthermore, a termination with a rated burden (other measuring devices are still connected) is assumed so
that an angle error of +0.43 min (rated-voltage value) is used as the calculation variable.
A current transformer of type 5PR is used here. This current transformer features a gap that limits the rema-
nence to 10 %. However, this gap results in larger angle errors. The following tables show excerpts from the
test reports.

Table 6-19 Phase A

I/In [%] Sb = Sbr (cos β = 0.8)


ε i [%] δ i [min]
100 0.314 46.40

Table 6-20 Phase B

I/In [%] Sb = Sbr (cos β = 0.8)


ε i [%] δ i [min]
100 0.247 35.10

Table 6-21 Phase C

I/In [%] Sb = Sbr (cos β = 0.8)


ε i [%] δ i [min]
100 0.702 41.10

Since the positive-sequence system power is evaluated in the device, take the sign into account when you add
the angle errors per phase, and divide the result by 3.
The following value results in this example:

The resulting correction angle is:

Set the parameter (_:2311:101) Angle correction = -0.67 °.

892 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.39 Reverse-Power Protection

Parameter: Minimum voltage V1

• Default setting (_:2311:102) Minimum voltage V1 = 5.000 V


With the parameter Minimum voltage V1, you can limit the operating range of the reverse-power protec-
tion. If the positive-sequence voltage falls below the set value, the reverse-power protection is deactivated. If
no other restrictions are known, Siemens recommends using the default setting.

6.39.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Angle correction -10.00 ° to 10.00 ° 0.00 °
_:2311:102 General:Minimum 0.300 V to 60.000 V 5.000 V
voltage V1

6.39.3.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:300 General:Undervoltage blocking SPS O
_:2311:301 General:P1avg MV O
_:2311:302 General:Q1avg MV O
_:2311:303 General:P1fast MV O
_:2311:304 General:Q1fast MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 893


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.39 Reverse-Power Protection

6.39.4 Stage Description

6.39.4.1 Description

Logic of the Stage

[lo_RPP stage, 2, en_US]

Figure 6-246 Logic Diagram of the Reverse-Power Protection Stage

Trip Command
To bridge brief power consumption during synchronization or during power swings caused by system inci-
dents, tripping (shutdown of the generator via reverse power) is delayed by a settable time (for example, 10
s).
A brief delay is enough when the quick-stop valve is closed. Couple the position of the quick-stop valve via the
binary input signal >Stop valve closed . When quick stop is tripped, the short Operate delay thus
becomes effective.

Blocking the Stage


In the event of blocking, the picked up stage will be reset. Blocking of the stage is possible externally or inter-
nally via the binary input signal >Block stage .

894 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.39 Reverse-Power Protection

6.39.4.2 Application and Setting Notes


If reverse power occurs in a power plant, the turbo-generator set must be disconnected from the electrical
power system. Operating the turbine without the minimum steam flow (cooling effect) is dangerous. For a
gas turbine cogeneration unit, the motor load can also be too great for the electrical power system.

Parameter: Threshold

• Recommended setting value (_:991:3) Threshold = -1.00 %


The friction losses that have to be overcome mainly determine the active power consumed by a turbo-gener-
ator set. Depending on the plant, the consumed active power is of the following ranges:
Steam turbines Preverse/Srated = 1.00 % to 3.00 %
Diesel drives Preverse/Srated> 5.00 %
Gas turbines Preverse/Srated = up to 30.00 %

You can measure the reverse power of the turbo-generator set yourself in a primary test by using the protec-
tion function. Set the setting value P reverse, for example, to 0.5 times the value of the measured reverse
power. This power is shown additionally in the functional measured values in the Reverse-power protection
function (P1avg). For large machines with very small reverse power, you must use the angle-error correction
option of the current and voltage transformers.

NOTE

i In the current-input selection, you can select protection current transformers or instrument transformers
on the device side. Since the transformers are calibrated at the factory, there are hardly any differences
between the transformers for the Reverse-power protection function. You can thus always select device
inputs with a protection current transformer.
In contrast, a primary current transformer significantly influences the measuring accuracy via its angle
error. The angle error of a class 0.2 instrument transformer is significantly smaller than the angle error of a
class 5P protection current transformer. A separate function group is necessary for the connection to an
instrument transformer. Use a Voltage/current 3-phase function group and load the Reverse-power
protection function from the library.
Do not connect the Reverse-power protection function to a linear core-type transformer (for example, a
TPZ type), as these transformers have a large angle error (for example, approx. 180 min).

6.39.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:991:1 Stage 1:Mode • off off
• on
• test
_:991:2 Stage 1:Operate & • no no
flt.rec. blocked
• yes
_:991:3 Stage 1:Threshold -30.00 % to -0.30 % -1.00 %
_:991:4 Stage 1:Dropout ratio 0.40 to 0.99 0.60
_:991:102 Stage 1:Dropout delay 0.00 s to 60.00 s 0.00 s
_:991:6 Stage 1:Operate delay 0.00 s to 60.00 s 10.00 s
_:991:103 Stage 1:Operate delay 0.00 s to 60.00 s 1.00 s
stop valve

SIPROTEC 5, 7SJ82/7SJ85, Manual 895


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.39 Reverse-Power Protection

6.39.4.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:991:81 Stage 1:>Block stage SPS I
_:991:500 Stage 1:>Stop valve closed SPS I
_:991:54 Stage 1:Inactive SPS O
_:991:52 Stage 1:Behavior ENS O
_:991:53 Stage 1:Health ENS O
_:991:55 Stage 1:Pickup ACD O
_:991:56 Stage 1:Operate delay expired ACT O
_:991:57 Stage 1:Operate ACT O
_:991:300 Stage 1:Operate del. stop val. ACT O
_:991:301 Stage 1:Operate w. stop valve ACT O

896 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

6.40 Overexcitation Protection

6.40.1 Overview of Functions

The Overexcitation protection (ANSI 24) is used for detecting high induction values in generators and trans-
formers. It protects the equipment from excessive thermal loads.
The induction is recorded indirectly by analyzing the V/f ratio (also referred to as Volt per Hertz protection).
Overvoltage leads to excessive magnetizing currents, while underfrequency leads to higher losses when reset-
ting the magnetization.
If the power system is disconnected and the voltage and frequency control function in the remaining system
does not react quickly or the power imbalance is excessive, there is a risk of overexcitation.

6.40.2 Structure of the Function

The Overexcitation protection function is used within protection function groups that have a 3-phase
voltage input. The function comes with the following factory-set stages:

• Thermal stage adjustable with a user-defined characteristic curve

• Definite-time stage which can be delayed using a time component


Within this function, the following maximum number of stages can be operated simultaneously: one stage
with a user-defined characteristic curve and 2 definite-time stages.
The group-indication output logic (see following figure) uses the logical OR function from the stage-selective
indications to generate the following group indications of the entire Overexcitation protection function:

• Pickup

• Operate Indication

[dwovexuf-080513-01.tif, 3, en_US]

Figure 6-247 Structure/Embedding of the Function

Function Measured Value

Measured Value Description


(_:2311:322) V/f Value calculated by the voltage and the frequency

SIPROTEC 5, 7SJ82/7SJ85, Manual 897


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

6.40.3 Stage with Dependent Characteristic Curve (Thermal Stage)

6.40.3.1 Function Description

Logic

[lothchuf-080513-01.tif, 1, en_US]

Figure 6-248 Logic of the Overexcitation Protection with Thermal Characteristic Curve

(1) Heating
(2) Cooling

V/f Method of Measurement


The input values of the protection function are the continuously measured voltage and the frequency. The
phase-to-phase voltage is used to process the voltage. The angle difference method (see 6.33 Overfrequency
Protection) is used to determine the frequency. Both values form the V/f ratio. In order to arrive at an absolute
value, standardized data is applied.
Thus, the ratio is derived from:

[foverufn-080523-01.tif, 1, en_US]

with

898 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

V Measured voltage (maximum phase-to-phase voltage)


Vrated, obj. Adjusted rated voltage of the protected object
f Measured frequency
frated Adjusted rated frequency

Based on the definition above, the protection function refers exclusively to primary values of the protected
object. A deviation between the primary rated voltage of the voltage transformer and the protected object is
corrected automatically.

NOTE

i This fact must be considered during a secondary test.


More information can be found in chapter 11.16 Functional Test for Overexcitation Protection .

The function compares the calculated value of the measured V/f ratio with the threshold value and the user-
defined thermal characteristic curve.
Depending on the characteristic curve, a thermal trip signal is triggered after a pre-determined duration.

Characteristic Curve
You can freely configure the thermal characteristic curve with the user-defined values. This provides a flexible
adjustment to the specified characteristics of the protected object. If the set threshold value (parameter
(_:13591:3) Threshold) is exceeded, the evaluation of the characteristic curve is initiated. Exceeding the
threshold value triggers an indication ((_:13591:55) Pickup). In addition, a definite-time stage may be
used to generate a delayed indication output as ((_:13591:301) Warning).
The pickup is used to start the integration process (weighted counting) of the thermal characteristic curve. If
the time as a factor of V/f is reached, the pickup is triggered. Based on the replica of the thermal behavior, the
trigger value is always 100 % (see Thermal Behavior, Page 900).
If the value drops below the pickup threshold, the trip command is rescinded and the internal counter of the
parameterized cooling time (parameter (_:13591:102) Cooling time therm.replica) is reduced.
The dropout threshold of the pickup threshold is fixed to 0.98 * Threshold.
A maximum of 30 overexcitation value pairs V/f (referring to the rated values) and operate time t can be set.
The default characteristic curve refers to a standard transformer.

[scaulskn-200214-01, 1, en_US]

Figure 6-249 Data Sheet for Adjustment of Thermal Characteristic Curve

The parameter Threshold (pickup threshold) affects the evaluation of the characteristic curve as follows:
If the Threshold is smaller than the first characteristic pair, the set time will be extended (see Figure 6-250).

SIPROTEC 5, 7SJ82/7SJ85, Manual 899


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

[dwovexak-210313-01.tif, 1, en_US]

Figure 6-250 Tripping Zone of the Thermal Characteristic Curve (I)

If the Threshold is greater, then a cutoff occurs (see Figure 6-251).

[dwovexab-210313-01.tif, 1, en_US]

Figure 6-251 Tripping Zone of the Thermal Characteristic Curve (II)

Warning Threshold
If the Threshold is exceeded, the time delay (parameter (_:13591:101) Warning delay) is started. If
the time delay has elapsed, the indication ((_:13591:301) Warning) will be displayed.

Thermal Behavior
The time derived from the characteristic curve and associated with the V/f value is set to 100 %. With each
function call, the time will be increased according to the respective weighted invocation interval. If the 100 %
value is exceeded, tripping is initiated. If the V/f value is changed, the associated time from the characteristic
curve is added as a new 100 % value.
In order to prevent excessive cooling times, the thermal storage has been limited internally to 150 %. The
fill level of the thermal storage will be provided as functional measured value.

900 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

Measured Value Description


(_:13591:321) V/f th. Thermal tripping of the overexcitation protection. If
the value reaches 100 %, the tripping occurs.

Cooling Time
If the value drops below the threshold ((_:13591:3) Threshold), tripping of the thermal characteristic
curve (dependent characteristic curve) is reverted. However, the parameterized cooling time (Cooling time
therm.replica) reduces the thermal storage (counter content) to 0. This parameter is defined as time. It is
required by the thermal replica in order to cool down from 100 % to 0 %.

Resetting the Thermal Map


The binary input indication (_:13591:501) >Reset thermal replica can be applied to reset the
thermal replica. The thermal replica will then have a value of 0. A reparameterization will also lead to resetting
the thermal replica.

Blocking the Stage


The function can be blocked externally or internally by the binary input signal (_:13591:81) >Block
stage. Blocking will cause a picked up function to be reset.

6.40.3.2 Application and Setting Notes


Thermal overloads extended over a longer period will jeopardize electric equipment, for example, synchro-
nous motors, generators, or transformers and may cause damage. When using the thermal, user-defined char-
acteristic curve, the overexcitation protection lends itself perfectly for adjustment to the specified limits of the
protection equipment.
The following provides the recommended settings:

NOTE

i It must be noted that one requirement for the correct mode of operation of the function is based on the
proper setting of the power-system data.
You can find more detailed information on this in chapter 6.1 Power-System Data.

For additional setting recommendations, verity the following parameter in the power-system data:

• Adjusted rated frequency

• Adjusted rated voltage of the protected object

• Adjusted rated voltage of the voltage transformer of the applicable measuring point

Parameter: Threshold Value

• Default setting (_:13591:3) Threshold = 1.10


The Threshold parameter is used to describe the value for the permissible continuous overexcitation.
The default value is a practical value used for transformers. The value may be less for generator applica-
tions. These values can be found in the manufacturer's information.

Parameter: Time Delayed Warning

• Default setting (_:13591:101) Warning delay = 10.00 s


When using the Warning delay parameter, the time can be determined by which the warning indica-
tion of the stage should be delayed after the pickup. This time delay depends on the specific application.
This time must clearly exceed the reaction time of the regulators. 10 seconds is a feasible value.

Parameter: Cooling Time Therm. Replica

• Default setting (_:13591:102) Cooling time therm.replica = 3600 s

SIPROTEC 5, 7SJ82/7SJ85, Manual 901


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

The Cooling time therm.replica parameter is used to define the cooling characteristics of the thermal
replica. If concrete specifications are not given, the default value can be maintained.

Parameter: V/f/time value pairs (operate curve)


With this parameter, the number of potting points along the thermal operate curve are defined. This is
required for the calculation. The number of points defines the accuracy of the image of the specified charac-
teristic curve. Adjust the value individually.
Set a V/f/time value pair for each characteristic-curve point. The setting depends on the characteristic curve
you want to realize. The default settings refer to a Siemens standard transformer.

NOTE

i The value pairs must be entered in continuous order.

NOTE

i Note that the V/f values that are lower than the V/f values of the smallest characteristic-curve point do not
extend the operate time. Up to the smallest characteristic-curve point, the characteristic curves runs
parallel to the V/f axis. V/f values that are larger than the V/f value of the largest characteristic-curve point
do not reduce the operate time. From the largest characteristic-curve point, the pickup characteristic runs
parallel to the V/f axis (seeCharacteristic Curve, Page 899).

6.40.3.3 Settings

Addr. Parameter C Setting Options Default Setting


Definite-T 1
_:13621:1 Definite-T 1:Mode • off off
• on
• test
_:13621:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:13621:3 Definite-T 1:Threshold 1.00 to 1.40 1.40
_:13621:6 Definite-T 1:Operate delay 0.00 s to 60.00 s 1.00 s
General
_:13591:1 Therm.charact.:Mode • off off
• on
• test
_:13591:2 Therm.charact.:Operate & • no no
flt.rec. blocked
• yes
_:13591:3 Therm.charact.:Threshold 1.00 to 1.20 1.10
_:13591:101 Therm.charact.:Warning 0.00 s to 60.00 s 10.00 s
delay
_:13591:102 Therm.charact.:Cooling 0 s to 100000 s 3600 s
time therm.replica

6.40.3.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:322 General:V/f MV O

902 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:13621:81 Definite-T 1:>Block stage SPS I
_:13621:54 Definite-T 1:Inactive SPS O
_:13621:52 Definite-T 1:Behavior ENS O
_:13621:53 Definite-T 1:Health ENS O
_:13621:55 Definite-T 1:Pickup ACD O
_:13621:56 Definite-T 1:Operate delay expired ACT O
_:13621:57 Definite-T 1:Operate ACT O
Therm.charact.
_:13591:81 Therm.charact.:>Block stage SPS I
_:13591:501 Therm.charact.:>Reset thermal replica SPS I
_:13591:54 Therm.charact.:Inactive SPS O
_:13591:52 Therm.charact.:Behavior ENS O
_:13591:53 Therm.charact.:Health ENS O
_:13591:55 Therm.charact.:Pickup ACD O
_:13591:301 Therm.charact.:Warning ACT O
_:13591:57 Therm.charact.:Operate ACT O
_:13591:321 Therm.charact.:V/f th. MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 903


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

6.40.4 Stage with Independent Characteristic Curve

6.40.4.1 Function Description

Logic

[lodtchuf-080513-01.tif, 1, en_US]

Figure 6-252 Logic of the Overexcitation Protection with Inpendent Characteristic Curve (Definite-Time
Stage)

Method of Measurement
This stage evaluates also the V/f value that is identical to the input value of the thermal stage.
Measurement-relevant details can be found in chapter 6.40.3 Stage with Dependent Characteristic Curve
(Thermal Stage).

How the Definite-Time Stage Works


The stage comprises a threshold and a time-delay stage. If the V/f value is greater than the set threshold value
((_:13621:3) Threshold), then the stage is tripped after an adjustable time delay has elapsed. You can
set the time delay with the parameter (_:13621:6) Operate delay.
The dropout ratio for the Threshold is fixed to 98 %.

6.40.4.2 Application and Setting Notes


The definite-time stage can be applied when fast tripping is required in the presence of high V/f values. In this
case, the stage acts superimposed on the thermal, dependent stage.

Parameter: Threshold Value

• Default setting (_:13621:3) Threshold = 1.40


The Threshold parameter is used to describe the overexcitation value that causes the tripping function.
The default value matches a feasible upper limit.

904 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

Parameter: Tripping delay

• Default setting (_:13621:6) Operate delay = 1.00 s


The Operate delay parameter is used to determine the time by which the stage is delayed after the
pickup. This time delay depends on the specific application. The default value is practical for the applica-
tion described in the previous chapter.

6.40.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Definite-T 1
_:13621:1 Definite-T 1:Mode • off off
• on
• test
_:13621:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:13621:3 Definite-T 1:Threshold 1.00 to 1.40 1.40
_:13621:6 Definite-T 1:Operate 0.00 s to 60.00 s 1.00 s
delay
Therm.charact.
_:13591:1 Therm.charact.:Mode • off off
• on
• test
_:13591:2 Therm.charact.:Operate • no no
& flt.rec. blocked
• yes
_:13591:3 Therm.charact.:Threshol 1.00 to 1.20 1.10
d
_:13591:101 Therm.charact.:Warning 0.00 s to 60.00 s 10.00 s
delay
_:13591:102 Therm.charact.:Cooling 0 s to 100 000 s 3600 s
time therm.replica

6.40.4.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:322 General:V/f MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
df/dt falling1
_:13621:81 Definite-T 1:>Block stage SPS I
_:13621:54 Definite-T 1:Inactive SPS O
_:13621:52 Definite-T 1:Behavior ENS O
_:13621:53 Definite-T 1:Health ENS O
_:13621:55 Definite-T 1:Pickup ACD O
_:13621:56 Definite-T 1:Operate delay expired ACT O
_:13621:57 Definite-T 1:Operate ACT O
Therm.charact.
_:13591:81 Therm.charact.:>Block stage SPS I

SIPROTEC 5, 7SJ82/7SJ85, Manual 905


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.40 Overexcitation Protection

No. Information Data Class Type


(Type)
_:13591:501 Therm.charact.:>Reset thermal replica SPS I
_:13591:54 Therm.charact.:Inactive SPS O
_:13591:52 Therm.charact.:Behavior ENS O
_:13591:53 Therm.charact.:Health ENS O
_:13591:55 Therm.charact.:Pickup ACD O
_:13591:301 Therm.charact.:Warning ACT O
_:13591:57 Therm.charact.:Operate ACT O
_:13591:321 Therm.charact.:V/f th. MV O

906 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

6.41 Undervoltage-Controlled Reactive-Power Protection

6.41.1 Overview of Functions

The Undervoltage-controlled reactive-power protection function (ANSI 27/Q):

• Detects critical power-system situations, mainly in case of regenerative generation

• Prevents a voltage collapse in power system by disconnecting the power-generation facility from the
main power systems

• Ensures reconnection under stable power-system conditions

6.41.2 Structure of the Function

The Undervoltage-controlled reactive-power protection function can be used in protection function groups
containing 3-phase voltage and current measurement. Depending on the device, it is preconfigured by the
manufacturer with 1 Protection stage and 1 Reclosure stage. A maximum of 2 Protection stages and 1
Reclosure stage can operate simultaneously within the function.

[dwqvprot-110713-01.tif, 1, en_US]

Figure 6-253 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 907


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

6.41.3 Protection Stage

6.41.3.1 Description

Logic of the Stage

[loqvprst-110713-01.tif, 1, en_US]

Figure 6-254 Logic Diagram of the Protection Stage of the Undervoltage-Controlled Reactive-Power Protec-
tion

908 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

Measurand
To detect critical power-system situations, the Undervoltage-controlled reactive-power protection function
uses the fundamental values of the phase-to-phase voltages, the positive-sequence current, and the reactive
power.

Q-Measurement Direction
The default directions of the positive reactive-power flow Q and the forward direction of the short-circuit
protection are identical, in the direction of the protected object. Via parameter Q sign, the direction of the
positive reactive-power flow Q can be changed by inverting the sign of the reactive power Q.

Pickup
The protection stage picks up under the following conditions:

• All 3 phase-to-phase voltages are below the parameterized threshold value.

• The positive-sequence current I1 is above the parameterized threshold value.

• The power-generation facility requires more than the parameterized reactive power (Q is above the para-
meterized threshold value).

Trip Interface
The stage provides 2 operate signals, the Operate (generator) and the Operate (grid). Depending
on the parameter Trip interface contains, one or none of them will be forwarded to the trip interface
of the circuit-breaker interaction.

Blocking of the Stage


The following blockings reset the picked up stage completely:

• Externally or internally via the binary input signal >Block stage

• Measuring-voltage failure
For further information, refer to chapter 6.7.4.1 Description.

Blocking of the Operate Delay and Operate Signal via the Device-Internal Inrush-Current Detection Function
The Blk. w. inrush curr. detect. parameter permits you to define whether the operate delay should
be blocked by a threshod-value violation due to an inrush current.
For further information about device-internal Inrush-current detection function, refer to chapter
6.3.7.1 Description .

6.41.3.2 Application and Setting Notes

Parameter: Blk. by meas.-volt. failure

• Recommended setting value (_:13921:10) Blk. by meas.-volt. failure = yes


You use the Blk. by meas.-volt. failure parameter to control the response of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal Measuring-voltage failure detection function is configured and switched on.

• The binary input signal >Open of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.

SIPROTEC 5, 7SJ82/7SJ85, Manual 909


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

Parameter Value Description


yes The Protection stage is blocked when a measuring-voltage failure is
detected. Siemens recommends using the default setting, as there is
no assurance that the Protection stage will function correctly if the
measuring voltage fails.
no The Protection stage is not blocked when a measuring-voltage failure
is detected.

Parameter: Blk. w. inrush curr. detect.

• Default setting (_:13921:27) Blk. w. inrush curr. detect. = no


You use the Blk. w. inrush curr. detect. parameter to determine whether the operate delay and
operate signal are blocked during the detection of an inrush current.

Parameter: I> release threshold

• Recommended setting value (_:13921:105) I> release threshold = 0.100 A


You use the I> release threshold parameter to define a precondition that the stage can pick up. The
default setting is at 10 % of the rated current. Siemens recommends using the default setting.

Parameter: V< threshold value

• Recommended setting value (_:13921:103) V< threshold value = 85.000 V


You use the V< threshold value parameter to define one of the 2 pickup criteria. If all 3 phase-to-phase
voltages drop below the parameterized undervoltage threshold value, the pickup criterion is fulfilled.
The setting should be set below the lower value of the permissible voltage range, according to the national
transmission code. In Germany, the recommended undervoltage threshold is 85 % of the rated voltage. There-
fore Siemens recommends using the default setting.

Parameter: Q> threshold value

• Default setting (_:13921:3) Q> threshold value = 5 %


You use the Q> threshold value parameter to define the second of the 2 pickup criteria. If the positive
reactive power exceeds the parameterized Q> threshold value, the pickup criterion is fulfilled.
In the following example, the pickup takes place if Q exceeds 5 % of the power-supply system rated power.

EXAMPLE
The following example is given for settings in secondary values.
Rated voltage: Vrated, sec = 100 V
Rated current: Irated, sec = 1 A
Threshold value: 5 % of the power-supply system rated power
You can calculate the setting value as follows:

[foqvprot-110713-01.tif, 1, en_US]

Parameter: Operate delay

• Default setting (_:13921:6) Operate delay grid CB = 1.50 s

• Default setting (_:13921:108) Oper. delay generator CB = 0.50 s


You can set the Operate delay grid CB for the circuit breaker at the power-supply system connection
point, or set the Oper. delay generator CB for the circuit breaker of the facility, for example, the gener-
ator.

910 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

The time of the Operate delay grid CB should always be set longer than the time of the Oper. delay
generator CB.

Parameter: Trip interface contains

• Default setting (_:13921:101) Trip interface contains = operate (grid)


The stage provides 2 operate signals, the Operate (generator) and the Operate (grid).
You use the Trip interface contains parameter to define whether one or none of them will be
forwarded to the trip interface of the circuit-breaker interaction. The selected operate signal will trip the circuit
breaker that has been connected to the protection function group.
The setting depends on the specific application.

Parameter: Q sign

• Default setting (_:13921:102) Q sign = not reversed


The default directions of the positive reactive-power flow Q and the forward direction of the short-circuit
protection are identical, in the direction of the main protected object (for example, a feeder). You use the Q
sign parameter to reverse the sign and therefore the direction of the reactive-power flow Q. This reversal
may be required for specific application, where the main protected object (for example, a line towards the
main power systems) is in different direction to the power-generation facility.
Parameter Value Description
not reversed The protected object is in the same direction as the power-gener-
ation facility.
reversed The protected object is not in the same direction as the power-
generation facility.

6.41.3.3 Settings

Addr. Parameter C Setting Options Default Setting


Prot. stage 1
_:13921:1 Prot. stage 1:Mode • off off
• on
• test
_:13921:2 Prot. stage 1:Operate & • no no
flt.rec. blocked
• yes
_:13921:10 Prot. stage 1:Blk. by • no yes
meas.-volt. failure
• yes
_:13921:27 Prot. stage 1:Blk. w. • no no
inrush curr. detect.
• yes
_:13921:101 Prot. stage 1:Trip inter- • no operate operate (grid)
face contains
• operate (generator)
• operate (grid)
_:13921:102 Prot. stage 1:Q sign • not reversed not reversed
• reversed
_:13921:3 Prot. stage 1:Q> 1.00 % to 200.00 % 5.00 %
threshold value
_:13921:103 Prot. stage 1:V< 3.000 V to 175.000 V 85.000 V
threshold value

SIPROTEC 5, 7SJ82/7SJ85, Manual 911


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

Addr. Parameter C Setting Options Default Setting


_:13921:105 Prot. stage 1:I> release 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
threshold 5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:13921:108 Prot. stage 1:Oper. delay 0.00 s to 60.00 s 0.50 s
generator CB
_:13921:6 Prot. stage 1:Operate 0.00 s to 60.00 s 1.50 s
delay grid CB

6.41.3.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Prot. stage 1
_:13921:81 Prot. stage 1:>Block stage SPS I
_:13921:54 Prot. stage 1:Inactive SPS O
_:13921:52 Prot. stage 1:Behavior ENS O
_:13921:53 Prot. stage 1:Health ENS O
_:13921:60 Prot. stage 1:Inrush blocks operate ACT O
_:13921:55 Prot. stage 1:Pickup ACD O
_:13921:301 Prot. stage 1:Op.delay expir.(gen.) ACT O
_:13921:302 Prot. stage 1:Operate (generator) ACT O
_:13921:56 Prot. stage 1:Op.delay expir.(grid) ACT O
_:13921:57 Prot. stage 1:Operate (grid) ACT O

912 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

6.41.4 Reclosure Stage

6.41.4.1 Description

Logic of the Stage

[loqvclst-110713-01.tif, 3, en_US]

Figure 6-255 Logic Diagram of Reclosure Stage in Undervoltage-Controlled Reactive-Power Protection

Measurand
The stage works with fundamental values of voltage and current.

Release for Reconnecting


The release for reconnecting the power-generation facility is given under the following conditions:

SIPROTEC 5, 7SJ82/7SJ85, Manual 913


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

• All 3 phase-to-phase voltages are above the threshold value.

• The power frequency is within a specified range.

• The reclosure time delay, started by the operate of specific protection functions, has elapsed. The time
delay is started by the first operate signal of the protection stages configured via the Configuration
parameter. All protection stages of the voltage protection, the frequency protection, and the QV protec-
tion are available for configuration.

External Start of Reclosure Time Delay


Reclosure time delay can be started via the binary input signal >V, f trip, which can be connected to
external voltage and frequency protection trip signals.

Blocking of the Stage


The stage can be blocked via the binary input signal >Block stage.

6.41.4.2 Application and Setting Notes

Parameter: Configuration

• Default setting (_:13951:102) Configuration = no stage


You use the Configuration parameter to define which operate signal of specific protection functions starts
the release time delay of the Reclosure stage:

• Overfrequency protection

• Underfrequency protection

• Overvoltage protection

• Undervoltage protection

• Protection stage of undervoltage-controlled reactive-power protection


When the protection stage of undervoltage-controlled reactive-power protection is selected, only the signal
Operate (generator) can start the release time delay of this stage. The signal Operate (grid) cannot
start the release time delay.
The configuration depends on the specific application.

Parameter: I> release threshold

• Recommended setting value (_:13951:106) I> release threshold = 0.100 A


You use the I> release threshold parameter to define a precondition that the stage can work.
The default setting is at 10 % of the rated current. Siemens recommends using the default setting.

Parameter: V> threshold value

• Recommended setting value (_:13951:101) V> threshold value = 95.000 V


You use the V> threshold value parameter to set one of the 2 release criteria. The setting should be set
above the lower value of the allowed voltage range, according to the national transmission code. In Germany,
the recommended overvoltage threshold is 95 % of the rated voltage. Therefore Siemens recommends using
the default setting.

Parameter: Frequency range

• Recommended setting value (_:13951:104) f difference positive = 0.05 Hz

• Recommended setting value (_:13951:105) f difference negative = -2.50 Hz

914 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.41 Undervoltage-Controlled Reactive-Power Protection

You use these 2 parameters to define the admitted frequency deviation from the rated frequency. f differ-
ence positive defines the upper frequency range limit. f difference negative defines the lower
frequency range limit.
Siemens recommends using the default settings, which reflect common practice in Germany. Other national
transmission codes may require a slightly different range.

Parameter: Time delay

• Default setting (_:13951:108) Time delay = 0.00 s


You use the Time delay parameter to specify the minimum time delay for releasing the reconnection of the
power-generation facility after tripping by protection.
The setting depends on the specific application.

6.41.4.3 Settings

Addr. Parameter C Setting Options Default Setting


Reclos. stage
_:13951:1 Reclos. stage:Mode • off off
• on
• test
_:13951:101 Reclos. stage:V> 3.000 V to 340.000 V 95.000 V
threshold value
_:13951:104 Reclos. stage:f difference 0.01 Hz to 5.00 Hz 0.05 Hz
positive
_:13951:105 Reclos. stage:f difference -5.00 Hz to -0.01 Hz -2.50 Hz
negative
_:13951:106 Reclos. stage:I> release 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
threshold 5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:13951:108 Reclos. stage:Time delay 0.00 s to 3600.00 s 0.00 s
_:13951:102 Reclos. stage:Configura- Setting options depend on
tion configuration

6.41.4.4 Information List

No. Information Data Class Type


(Type)
Reclos. stage
_:13951:81 Reclos. stage:>Block stage SPS I
_:13951:501 Reclos. stage:>V, f trip SPS I
_:13951:54 Reclos. stage:Inactive SPS O
_:13951:52 Reclos. stage:Behavior ENS O
_:13951:53 Reclos. stage:Health ENS O
_:13951:301 Reclos. stage:Release closure ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 915


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

6.42 Circuit-Breaker Failure Protection

6.42.1 Overview of Functions

The Circuit-breaker failure protection function (ANSI 50BF) monitors the tripping of the associated circuit-
breaker (CB) and generates a backup trip signal if the circuit-breaker fails.
Starting with version V7.50, the previous function CB failure has been replaced with the new Circuit-breaker
failure protection with an adaptive algorithm Adaptive CB failure protection. In this way, you achieve a
faster, more reliable detection of the opening of the circuit breaker in the event of complex signal histories.
The 2 functions are identical, with the exception of a slightly increased processor load, in terms of setting
options, logic and indications. Siemens recommends using the adaptive circuit-breaker failure protection and
avoiding mixing the protection types in one device. You can find additional information on the processor load
in DIGSI for each device under Device information in the Resource consumption tab.

6.42.2 Structure of the Function

The function Circuit-breaker failure protection (CBFP) can be used in the Circuit-breaker function group.

[dwstrbfp-260213-01.tif, 1, en_US]

Figure 6-256 Structure/Embedding of the Function

Figure 6-257 shows the functionalities and the function control of the function.
The start is initiated by the device-internal protection function or by an external protection. Along with the
start, the current-flow criterion or the circuit-breaker auxiliary contact criterion is used to check whether the
circuit breaker is closed. If the circuit breaker is closed, the function picks up and starts the time delay. During
the time delay, the system checks continuously whether the circuit breaker has opened. If this is the case, the
function drops out. If the circuit breaker is not opened, the function trips upon expiration of the time delay.
The following description elaborates on the detailed functionality of the individual function blocks.

916 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

[losvsbfp-090712-01.tif, 2, en_US]

Figure 6-257 Function Logic Overview

6.42.3 Function Description

The Circuit-breaker failure protection function is started by device-internal protection functions and/or exter-
nally (via a binary input or an interface, such as GOOSE). Figure 6-258 and Figure 6-259 show the function-
ality.

Internal Start
By default, each device-internal protection stage that has to control the local circuit breaker starts the circuit-
breaker failure protection. The function is started by the tripping of the protection stage. In the default setting,
the starting signal Internal start (see Figure 6-258) is held when the pickup signal has a falling edge or
the protection function has tripped. The Circuit-breaker failure protection function can in this case only drop
out if the circuit breaker is detected to be open. This is detected using the current flow or circuit-breaker auxil-
iary contact criterion. If necessary, the Circuit-breaker failure protection function can also drop out when the
pickup signal has a falling edge or the protection function trips (internal starting signal is not held).
Using routing, you can specify whether individual protection stages or protection functions are used as a
starting source or whether starting happens only externally.
The internal starting sources are routed in the protection function groups via the Circuit-breaker interaction
entry (for this, see 2.1 Function Embedding in the Device Figure 2-6).

SIPROTEC 5, 7SJ82/7SJ85, Manual 917


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

[loanwint-160611-01.tif, 2, en_US]

Figure 6-258 Internal Start of the Circuit-Breaker Failure Protection Function

External Start
The parameter Start via binary input is used to set whether the external start is initiated by a 1-
channel or 2-channel signal. The required routing of the input signals is compared with the setting. If a
routing is missing, an error message is generated. The Health signal changes to the state Warning.

[loanwext-030211-01.tif, 1, en_US]

Figure 6-259 Configuration of the External Start of the Circuit-Breaker Failure Protection Function

In 1-channel operation, the start is initiated with the binary input signal >Start only.
In 2-channel operation, the binary input signal >Release must also be activated to initiate the start. In the
default setting, the starting signal External start drops out immediately when the input signals have a
falling edge (see Figure 6-260). If necessary, the starting signal can be held. In this case the start remains
active when the binary input signals have a falling edge.
The input signals are monitored to avoid an unwanted pickup of the function.
If either of the signals >Start or >Release is active for more than the set supervision time of the corre-
sponding signal without the function picking up, an error in the binary input circuit is assumed. The corre-
sponding signal is blocked to exclude an external pickup of the function. An indication to this effect is output,
and the Health signal changes to the state Warning. The blocking is reset as soon as the binary input signal
drops out.

918 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

Supervision is disabled in the following cases:

• On pickup of the Circuit-breaker failure protection function (only in the case of an external start). This
prevents an unwanted pickup of the supervision if the external protection that starts the Circuit-breaker
failure protection function uses a lockout functionality. When the starting signal drops out, supervision is
enabled again.

• As long as the function or the device is in test mode. This allows to check the function without the super-
vision blocking the function.
If the >Start signal is active and no release signal is present after elapse of the settable supervision time for
the starting signal, the pickup is blocked and an indication to this effect is output. The Health signal changes
to the state Warning. The blocking is reset with the dropout of the starting signal.
The binary input signals only take effect if the binary inputs are activated for at least 10 ms (SW filter, see
Figure 6-260).

[logikext-070611-02.tif, 2, en_US]

Figure 6-260 External Start of the Circuit-Breaker Failure Protection Function, Logic

Current-Flow Criterion
The current-flow criterion is the primary criterion for determining the circuit-breaker switch position. A circuit-
breaker pole is supposed to be closed, and the current-flow criterion fulfilled, as soon as one of the phase
currents exceeds the phase-current threshold value, and at the same time a plausibility current exceeds the
associated threshold value. The plausibility current can be either a 2nd phase current (to compare with the
threshold value for phase currents) or the zero-sequence or negative-sequence current (to compare with the
sensitive threshold value). The additional evaluation of the plausibility current increases the safety of the crite-
rion.
If you are using the transformer connection type 3-phase, 2prim.trans., the ground current is neither meas-
ured nor calculated. The plausibility check via the ground current is therefore not possible. The setting
Direct release via the ground current does not lead to a pickup of the circuit-breaker failure protection.

SIPROTEC 5, 7SJ82/7SJ85, Manual 919


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

In the case of ground faults, the sensitive threshold value can be dynamically applied to the phase currents as
well. The current-flow criterion is fulfilled when the currents exceed the sensitive threshold value. The phase-
current threshold value is then ineffective. The binary signal >Threshold sensitive is used for the switch-
over.
If you set the 3I0 criterion parameter to Direct release, you prevent the plausibility check of the
zero-sequence current. In this way, a pickup only by way of this current can be achieved. With the Threshold
3I0 dir. release parameter, you set the threshold value to be exceeded.
If you set the I2 criterion parameter to Direct release, you also switch off the plausibility check of
the negative-sequence current. With the Threshold I2 dir. release parameter, you set the threshold
value to be exceeded.
If you set the I2 criterion parameter to Direct release, a plausibility check is performed via the phase
currents with 1/3 * Threshold I2 dir. release.
The measuring algorithm is optimized for fast dropout when the value drops below the threshold value.

920 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

[lostrom1-030211-01.tif, 4, en_US]

Figure 6-261 Current-Flow Criterion

Circuit-Breaker Auxiliary Contact Criterion


Settings allow you to specify whether the circuit-breaker auxiliary contacts are permitted for determining the
circuit-breaker position.
The double-point indication 3-pole position (from the Circuit-breaker function block) is used to deter-
mine whether all 3 poles of the circuit breaker are closed. If the double-point indication is not routed, the
output is an error message. Furthermore, the Health signal changes to the state Warning.
The detection of a static disturbed position (not an intermediate position) has the effect that the circuit-
breaker auxiliary contact criterion is not used (the internal signal Aux.co.crit.: CB Clsd is disabled).

SIPROTEC 5, 7SJ82/7SJ85, Manual 921


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

[lokriter-140611-01.tif, 1, en_US]

Figure 6-262 Circuit-Breaker Auxiliary Contact Criterion

Pickup/Dropout
After the start, a check is performed whether the circuit breaker is closed. The current-flow criterion and the
circuit-breaker auxiliary contact criterion are available for this purpose.
Even if the circuit-breaker auxiliary contact criterion is permitted, preference is given to the fulfilled current-
flow criterion because the current-flow criterion is the most reliable criterion for detecting whether the circuit
breaker is closed. This means that the circuit breaker is deemed to be closed if it is closed according to the
current-flow criterion but at the same time open according to the circuit-breaker auxiliary contact criterion.
If no current is flowing at the start time, the function can only pick up on the basis of the circuit-breaker auxil-
iary contact criterion. For this purpose, the circuit-breaker auxiliary contacts must be permitted as criterion.
When the current begins to flow after the start, the function switches over to the current-flow criterion.
If the circuit breaker is detected as closed and the starting condition is present, the function picks up.
The pickup starts a time delay (see Delay/Tripping). While the delay is running, the system checks continuously
whether the circuit breaker has opened. In the default setting, the opening of the circuit breaker is checked on
the basis of the currently valid criterion, which is normally the current-flow criterion because it is preferred. If
until expiration of the time delay, no current flow above the set threshold values has been detected, the
circuit-breaker auxiliary contact criterion becomes effective.
The function has also a setting in which dropout is only possible if both criteria detect in parallel the circuit
breaker to be open (dropout with auxiliary contact and current-flow criterion).
In the default setting, the internal starting signal is held (see Figure 6-258 and Figure 6-260). This means that
dropout is controlled solely by the current or the circuit-breaker auxiliary contact criterion. If dropout is also to
occur on the falling edge of the starting signal (that is, when the pickup signal has a falling edge or the protec-
tion function trips), holding of the start signal must be disabled.

922 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

[loanreg1-030211-01.tif, 4, en_US]

Figure 6-263 Pickup/Dropout of the Circuit-Breaker Failure Protection Function

Delay/Tripping
In a first step, tripping at the local circuit breaker can be repeated. Tripping is repeated after expiration of the
settable delay T1. If the local CB was not yet tripped, for example, in the event of an external start of the
circuit-breaker failure protection, the trip logic of the circuit breaker itself is activated when the time delay T1
elapses.
Time delay T2 (backup tripping) can commence in parallel either with the start of time T1 or after expiration of
time T1.
If time delay T2 expires without a dropout of the function, a circuit-breaker failure is assumed and the backup
tripping signal Tripping T2 is output. If there is a protection interface in the device, if needed a transfer-trip
signal can be sent to the opposite end.
You can find detailed information in the chapter 3.6.3 Protection Interface and Protection Topology.
If the >CB defect input signal is valid, any repetition of the trip signal is suppressed, and the backup tripping
signal T2 is generated immediately (without delay). The binary input of the >CB defect input signal must be
activated for at least 20 ms before the signal becomes valid.
With help of the CB failure pole indication, you can determine the phase currents that are above the
threshold value at the tripping time T2.
The Minimum operate time parameter defines the minimum duration for tripping the function. In contrast
to other protection functions, the parameter is set within its own function. As a result, the setting is inde-
pendent of the identically named global parameter that is set in the Device settings.

SIPROTEC 5, 7SJ82/7SJ85, Manual 923


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

[lo-bbp-verza-3ph.vsd, 5, en_US]

Figure 6-264 Delay/Tripping of the Circuit-Breaker Failure Protection Function

6.42.4 Application and Setting Notes

Figure 6-265 gives an overview of the functions involved in an external start of the CBFP function. In the case
of an internal start, there is no external protection device and the protection functionality is located in the
CBFP device.

924 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

[loextpol-021112-01.tif, 2, en_US]

Figure 6-265 Circuit-Breaker Failure Protection with External Start, Tripping Repetition, and 3-‑Pole Tripping
(T2)

Routing: Configuration of Internal Starting Sources (Internal Protection Function)


Configuration of the internal starting sources takes place in the protection function groups via the Circuit-
breaker interaction entry (for this, see 2.1 Function Embedding in the Device, Figure 2-2).
By default, the function can be started by any tripping of the internal protection functions that control the
local circuit breaker. Depending on the specific application, it can be necessary to exclude certain device-
internal protection functions from starting the CBFP. For instance, busbar disconnection following a local
circuit-breaker failure can be undesirable in the case of load-shedding applications or ground faults in isolated/
resonant-grounded systems.
Where a start exclusively from external sources is required, all internal protection functions must be routed so
that they are excluded as a starting source.

Parameter: Start via binary input

• Default setting (_:107) Start via binary input = no

SIPROTEC 5, 7SJ82/7SJ85, Manual 925


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

Parameter Value Description


no If no external start is intended, the parameter is set to no.
2 channel 2-channel start is used if there is a risk that the circuit-breaker failure protec-
tion causes a tripping due to a faulty activation of the start binary input.
This is the case in the following situations:
a) The CBFP pickup value (threshold value) is set to less than the load
current.
b) There can be operating conditions under which the current flow is higher
than the pickup value.
To avoid a possible overfunction, Siemens recommends using the 2-channel
start.
1 channel The 1-channel start must be used where only one control circuit of a binary
input is available for starting the CBFP.

Input Signals: >Start, >Release


The start and release input signals have a filtering time of 10 ms as default setting. If a transient control signal
to the binary inputs is to be expected due to the design of the external binary-input control circuits and due to
environmental conditions, the filtering time can be extended. This delays the start of the CBFP function.
Input Signals Description
>Start The start input signal is linked with the tripping of the external protection
device (see Figure 6-265).
>Release The release input signal is normally linked with the pickup of the external
protection device (see Figure 6-265). Another common configuration is the
parallel wiring of the external trip initiation to both binary inputs (start and
release).

Parameter: Supervision time release signal

• Default setting (_:111) Sup.time f. release signal = 0.06 s


The setting depends on the external function which generates the release signal. If the pickup or tripping of
the external protection is used as release signal, the default setting can be kept. If it is ensured that the release
signal is always present before the starting signal, the time can be set to 0.

Parameter: Holding internal start signal

• Recommended setting value (_:105) Holding int. start signal = yes

Parameter Value Description


yes For an internal start, the starting signal is hold. The dropout of the CBFP
depends exclusively on the determination of the circuit-breaker position.
This setting must be selected if it is not ensured that all 3 poles of the CB
have opened when the pickup signal of the protection function has a falling
edge.
Siemens recommends using this method as the standard method.
no Holding of the starting signal can be disabled if it is ensured by the applica-
tion that the CB has reliably opened when the starting signal has a falling
edge, or if the CBFP is explicitly required to drop out when the starting
signal has a falling edge.

926 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

EXAMPLE

Holding internal starting signal (setting value: Yes)


In the event of a 2-pole fault, only one contact of the CB opens. The fault current is thus reduced, and the
starting phase short-circuit protection drops out.

Parameter: Holding external start signal

• Recommended setting value (_:106) Holding ext. start signal = no

Parameter Value Description


no The CBFP drops out when the external starting signal has a falling edge. This
setting prevents the CBFP from generating a tripping signal when an
unwanted pulse is received at the binary input and the current flow is high
enough.
Siemens recommends using this method as the standard method.
yes You can hold the starting signal if it is not ensured that the circuit breaker is
open when the external starting signal has a falling edge.

EXAMPLE

Holding external starting signal (setting value: Yes)


The function is started from the opposite end via an auxiliary device for command transmission. This device
generates only a signal pulse.

NOTE

i Siemens would like to point out that, with a hold signal, the CBFP generates a trip signal each time a
starting pulse is received and the current flow is high enough. Remember this particularly in the case of an
external start.

Parameter: Threshold phase current/Threshold sensitive

• Recommended setting value (_:102) Threshold phase current = approx. 0.50 Isc, min

• Recommended setting value (_:101) Threshold sensitive = approx. 0.50 Isc,min

In order to ensure that the disconnection of the fault is promptly detected and the function can drop out
quickly, Siemens recommends setting both thresholds to half the minimum short-circuit current (Isc, min).
If – depending on the neutral-point treatment and/or load conditions – ground faults lead to relatively low
fault currents, a sensitive setting of the parameter Threshold sensitive must be selected according to
the rule (0.5 Isc, min). There can also be values which are noticeably below the rated or load current.

Input Signal: >Threshold sensitive


In order to ensure that the function picks up reliably in all switch positions of the power-supply system (exam-
ples: opposite end of line open, switching onto a ground fault), the setting of the parameter Threshold
sensitive can be applied dynamically to all currents – including phase currents – in the presence of ground
faults. For this purpose, the binary signal >Threshold sensitive must be activated. This can be done via a
device-internal function for ground-fault detection (if provided in the device), for example, using Overvoltage
protection with zero-sequence voltage. In this case, the pickup of the V0> function must be linked with the
binary signal. Alternatively, the signal can be coupled from a separate device for sensitive ground-fault detec-
tion via a binary input.

SIPROTEC 5, 7SJ82/7SJ85, Manual 927


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

Parameter: Circuit-breaker auxiliary contact criterion allowed for protection

• Recommended setting value (_:103) CB aux.cont. crit. allowed = no

Parameter Value Description


no If sufficient current flow is ensured under all conditions with the CB closed,
Siemens recommends not to permit the auxiliary contacts as a further crite-
rion for determining the CB position, because measurement based on the
current flow is the most reliable criterion.
w. 'CB pos. closed 3p.' The auxiliary contacts must be permitted as a further criterion in applica-
tions (see the following examples) where the current is no reliable criterion
for determining the circuit-breaker position.

Parameter: 3I0 criterion

• Recommended setting value (_:120) 3I0 criterion = Plausibility check

Parameter Value Description


Plausibility check The ground current serves only for the plausibility check of the phase
currents. The threshold for the ground current uses the value set in the
Threshold sensitive parameter.
Direct release The current-flow criterion can be fulfilled only by the ground current
without the phase currents exceeding their set threshold value. The
threshold for the ground current uses the value set in the Threshold 3I0
dir. release parameter in this case.

If you have set the Threshold phase current to be larger than the maximum load current, overfunction
because of a false start is impossible. To ensure a Circuit-breaker failure protection for smaller ground faults
also with this setting, you can set the 3I0 criterion to Direct release and set the Threshold 3I0
dir. release to be appropriately smaller than the Threshold phase current.

Parameter: I2 criterion

• Recommended setting value (_:121) I2 criterion = Plausibility check

Parameter Value Description


Plausibility check The negative-sequence current serves only for the plausibility check of the
phase currents. The threshold for the negative-sequence current uses the
value set in the Threshold sensitive parameter.
Direct release If a phase current exceeds 1/3 of the Threshold I2 dir. release, the
current-flow criterion can be fulfilled just by the negative-sequence current
without the phase currents exceeding their set threshold value. The
threshold for the negative-sequence current uses the value set in the
Threshold I2 dir. release parameter in this case.

If you have set the Threshold phase current to be larger than the maximum load current, overfunction
because of a false start is impossible. To have a Circuit-breaker failure protection function for smaller unbal-
anced faults also with this setting, you can set the I2 criterion to Direct release and set the
Threshold 3I0 dir. release to be appropriately smaller than the Threshold phase current.

Parameter: Threshold 3I0 dir. release


Recommended setting value (_:122) Threshold 3I0 dir. release = approx. 0.5 Iscmin
This parameter is effective only if the 3I0 criterionparameter is set to Direct release. Siemens
recommends setting the threshold to half the minimum short-circuit current (Iscmin) to ensure that the discon-
nection of the fault is promptly detected and the function can drop out quickly.

928 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

Parameter: Threshold I2 dir. release


Recommended setting value (_:123) Threshold I2 dir. release = approx. 0.5 I2min
This parameter is effective only if the I2 criterion parameter is set to Direct release. Siemens recom-
mends setting the parameter to half the permissible negative-sequence current (I2min) to achieve a fast fault
clearing in case of an undesired negative-sequence system component.

Parameter: Monit. time for BI ">Start"/Monit.tm. f.BI ">Release"

• Default setting (_:124) Monit. time for BI ">Start" = 15 s

• Default setting (_:125) Monit.tm. f.BI ">Release" = 15 s


With these parameters, you set the monitoring time of the binary inputs >Start/>Release. If the Circuit-
breaker failure protection does not pick up during this monitoring time, a failure in the binary-input circuit is
assumed. Siemens recommends retaining the default setting of 15 s.

EXAMPLES

Applications which require you to permit the circuit-breaker auxiliary contact criterion:

• Tripping of the high and low-voltage side CB on the transformer. If only one of the 2 CBs trips, there is no
more current flow.

• Tripping of protection functions whose tripping decision is not based on a current measurement in
combination with voltage or frequency protection functions

• Injection of the tripping signal from Buchholz protection

Parameter: Dropout

• Recommended setting value (_:104) Dropout = with effective criterion


The parameter Dropout is available if the circuit-breaker auxiliary contact criterion is permitted (see param-
eter CB aux.cont. crit. allowed).
Parameter Value Description
with effective crite- Siemens recommends keeping the default setting, because it prefers the
rion current as a reliable criterion for detection of an open CB and thus for
dropout of the CBFP function.
w. aux.c. and Select this setting for applications on transformers or generators (see the
curr.crit. preceding examples) in which the current flow is such that the current is no
longer a reliable criterion for detecting the opening of the CB.

Parameter: Retrip after T1

• Default setting (_:108) Retrip after T1 = no

Parameter Value Description


no Where no redundant CB control is provided, a repetition of the trip signal to
the local CB is not required.
start T2 after T1 Where a redundant CB control (2nd trip coil with 2 trip circuits) is provided,
a repetition of the trip signal to the local CB makes sense.
Siemens recommends the setting start T2 after T1 because it
provides a clear chronological separation of the processes for trip repeat
and backup tripping. Remember here that the overall fault-clearance time in
case of a failure of the local CB is the sum of T1 and T2.
parallel start T2, T1 As an alternative to the setting start T2 after T1, the user can start T2
and T1 in parallel.

SIPROTEC 5, 7SJ82/7SJ85, Manual 929


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

Parameter: Delay T1 for 3-pole retrip

• Default setting (_:109) Delay T1 for 3-pole retrip = 0.05 s


The parameter is visible only when retripping is set.
The setting depends on the user's philosophy.
The following settings make sense:

• If the minimum fault-clearing time has top priority, Siemens recommends setting the time to 0. This
setting causes initiation of the retrip immediately upon the start. The drawback is that a defect of the 1st
trip circuit is not detected.

• With a small time delay of, for instance, 50 ms, the defect of the 1st trip circuit can be detected based on
the evaluation of the fault record.

• With a long time delay, which reliably ensures the dropout of the CBFP with the CB open, the rising edge
indication of the trip repeat Retrip T1 is a sure signal for a fault in the 1st trip circuit. The following
example shows how this time is determined.

EXAMPLE

Determining the T1 Time that Reliably Ensures the Dropout of the CBFP with the CB Open:

Time of binary device output 5 ms


(when tripping is caused by device-internal protec-
tion)
CB inherent time up to current interruption 2 periods (assumed rated frequency = 50 Hz)
Dropout time of CBFP function 1 period
Subtotal 65 ms
Security Factor 2
Total (time T1) 130 ms

Parameter: Delay T2 for 3-pole trip

• Default setting (_:110) Delay T2 for 3-pole trip = 0.13 s


This setting has to ensure that after opening of the local CB the function drops out reliably and that backup
tripping is avoided under all circumstances. The setting depends on the parameter Retrip after T1.
If T2 is started after T1, there is no need to consider the time T1 for the setting of T2.

EXAMPLE

Determining the T2 Time that Reliably Ensures the Dropout of the CBFP with the CB Open:

Time of binary device output 5 ms


(when tripping is caused by device-internal protec-
tion)
CB inherent time up to current interruption 2 periods (assumed rated frequency = 50 Hz)
Dropout time of CBFP function 1 period
Subtotal 65 ms
Security Factor 2
Total (time T2) 130 ms

If T1 and T2 are started in parallel, take into account the time T1 for the setting of T2.

930 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

EXAMPLE

Simultaneous start of T2 and T1

Time for a reliable dropout after the local CB has 130 ms


opened
Setting of T1 50 ms
Total (= T2) 180 ms

Parameter: Minimum operate time

• Default setting (_:112) Minimum operate time = -


The Minimum operate time parameter is used to set the minimum duration for tripping the function.

! CAUTION
Do not set a time that is too short.
If you set a time that is too short, there is a danger (dropout of the function without the current-flow
criterion) that the device contacts will interrupt the control circuit. If this happens, the device
contacts will burn out.
² Set a duration that is long enough to ensure that the circuit breaker reaches its final position open
reliably after a control operation.

Input Signal: >CB defect


The input signal >CB defect has a default filtering time of 20 ms. This filtering time prevents the input
signal from becoming effective in the case of a transient activation of the physical binary input, which can be
caused by the pressure change when the CB opens.
This time can be set to 0 if such a transient pickup of the physical binary input can be excluded due to the CB
design.

Output Signal: Retrip T1


If only 1 control circuit is available for the local circuit breaker, it is not mandatory to route the output signal
because the signal also controls the circuit-breaker trip logic.
If a 2nd Control circuit is present, the Retrip T1 output signal must be routed to the associated binary
output.

Output Signal: Trip T2


In order to operate the adjacent circuit breakers, the backup tripping (indication Trip T2) must be routed to
a binary output; andif necessary, to an interface (intertripping to opposite end).

6.42.5 Settings

Addr. Parameter C Setting Options Default Setting


50BF Ad.CBF #
_:1 50BF Ad.CBF #:Mode • off on
• on
• test
_:105 50BF Ad.CBF #:Holding • no yes
int. start signal
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 931


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

Addr. Parameter C Setting Options Default Setting


_:107 50BF Ad.CBF #:Start via • no no
binary input
• 2 channel
• 1 channel
_:106 50BF Ad.CBF #:Holding • no no
ext. start signal
• yes
_:111 50BF Ad.CBF #:Sup.time 0.00 s to 1.00 s 0.06 s
f. release signal
_:103 50BF Ad.CBF #:CB • no no
aux.cont. crit. allowed
• w. 'CB pos. closed 3p.'
_:104 50BF Ad.CBF #:Dropout • with effective criterion with effective
criterion
• w. aux.c. and curr.crit.
_:108 50BF Ad.CBF #:Retrip • no no
after T1
• start T2 after T1
• parallel start T2, T1
_:102 50BF Ad.CBF #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.500 A
phase current 5 A @ 100 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 2.500 A
_:101 50BF Ad.CBF #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
sensitive 5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.250 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.250 A
_:109 50BF Ad.CBF #:Delay T1 0.000 s to 60.000 s 0.050 s
for 3-pole retrip
_:110 50BF Ad.CBF #:Delay T2 0.050 s to 60.000 s 0.130 s
for 3-pole trip
_:112 50BF Ad.CBF #:Minimum 0.00 s to 60.00 s 0.10 s
operate time
_:120 50BF Ad.CBF #:3I0 crite- • Direct release Plausibility
rion check
• Plausibility check
_:121 50BF Ad.CBF #:I2 crite- • Direct release Plausibility
rion check
• Plausibility check
_:122 50BF Ad.CBF #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
3I0 dir. release 5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.250 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.250 A
_:123 50BF Ad.CBF #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
I2 dir. release 5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.250 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.250 A
_:124 50BF Ad.CBF #:Monit. 0.05 s to 60.00 s 15.00 s
time for BI ">Start"
_:125 50BF Ad.CBF 0.05 s to 60.00 s 15.00 s
#:Monit.tm. f.BI
">Release"

932 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.42 Circuit-Breaker Failure Protection

6.42.6 Information List

No. Information Data Class Type


(Type)
50BF Ad.CBF #
_:501 50BF Ad.CBF #:>Start SPS I
_:502 50BF Ad.CBF #:>Release SPS I
_:82 50BF Ad.CBF #:>Block function SPS I
_:503 50BF Ad.CBF #:>CB defect SPS I
_:500 50BF Ad.CBF #:>Threshold sensitive SPS I
_:54 50BF Ad.CBF #:Inactive SPS O
_:52 50BF Ad.CBF #:Behavior ENS O
_:53 50BF Ad.CBF #:Health ENS O
_:55 50BF Ad.CBF #:Pickup ACD O
_:305 50BF Ad.CBF #:Retrip T1 ACT O
_:306 50BF Ad.CBF #:Trip T2 ACT O
_:302 50BF Ad.CBF #:BI start routing miss. SPS O
_:304 50BF Ad.CBF #:BI aux.ct. rout. miss. SPS O
_:300 50BF Ad.CBF #:Fail. BI 'start' SPS O
_:307 50BF Ad.CBF #:Fail. no BI release SPS O
_:301 50BF Ad.CBF #:Fail. BI 'release' SPS O
_:315 50BF Ad.CBF #:Immediate Operate SPS O
_:316 50BF Ad.CBF #:CB failure pole ACD O

SIPROTEC 5, 7SJ82/7SJ85, Manual 933


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

6.43 Circuit-Breaker Restrike Protection

6.43.1 Overview of Function

The Circuit-breaker restrike protection function:

• Monitors the circuit breaker against restriking, for example, caused by an overvoltage over the circuit-
breaker poles after switching off a capacitor bank

• Generates a backup operate signal in case of a circuit-breaker restriking

6.43.2 Structure of the Function

The Circuit-breaker restrike protection function is used in the Circuit-breaker function group. A maximum
of 2 functions can operate simultaneously within the function group.

[lo_strrestrike_2014-03-05.vsd, 2, en_US]

Figure 6-266 Structure/Embedding of the Function

The function logic is grouped into the parts shown in Figure 6-267. In the following chapter, these logic parts
are described in detail.

[lo_respro-210113-01.vsd, 1, en_US]

Figure 6-267 Logic Overview of the Function

6.43.3 Function Description

Plausibility Release
The function Circuit-breaker restrike protection issues a trip command to a superordinated circuit breaker,
usually the infeed circuit breaker of a busbar. Overfunction of this protection can cause extreme problems for
the whole application.
The logic of plausibility release strongly reduces the risk of a false start of the function by adding an extra
release criteria for a function start.

934 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

Each criterion can be switched on or off individually.

[lo_paus-210113-01.vsd, 1, en_US]

Figure 6-268 Logic Diagram for the Plausibility Release of the Circuit-Breaker Restrike Protection

The plausibility-release logic checks the following conditions:

• When the parameter Plausibility via 50BF fct. is set to yes, the pickup signal of the Circuit-
breaker failure protection is monitored. The plausibility release is given if the Circuit-breaker failure
protection has picked up.

• When the parameter Plaus. via open/trip cmd is set to yes, the trip/open command is moni-
tored. The plausibility release is given if the trip/open command has been generated.

• When the parameter Plaus. via binary input is set to yes, the >release signal is monitored.
The plausibility release is given if the >release signal has been received.
If one of the conditions is fulfilled, the plausibility release is given for 5 s. The 5-s timer ensures that the
release criterion and start condition relate to the same circuit-breaker opening/tripping process.
If all the 3 plausibility settings are set to no, the start/stop-monitoring logic considers the release as fulfilled.
For safety reasons, the input signal >release has a preset software filtering time of 20 ms.

Start/Stop Monitoring
Via the start/stop monitoring logic, the monitoring duration of the current signal regarding restriking is deter-
mined.

SIPROTEC 5, 7SJ82/7SJ85, Manual 935


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

[lo_starstop-210113-01.vsd, 2, en_US]

Figure 6-269 Logic Diagram for Start/Stop Monitoring of the Circuit-Breaker Restrike Protection

The monitoring is started if one of the following conditions is met:

• The circuit-breaker position is detected as open via the circuit-breaker auxiliary contacts during the time
set with the parameter Position recognition delay.
The Position recognition delay time is used for safety means to ensure that the circuit breaker is
definitely open when the monitoring starts. This parameter allows to adapt this start criterion to all kinds
of auxiliary-contact configurations.

• The binary input signal >Start is activated.


For safety reasons, the input signal has a preset software filtering time of 20 ms.
In addition to the active start criterion, the plausibility release (refer to the Plausibility Release, Page 934)
must be present to start the monitoring duration.
With the fulfilled start condition, the Monitoring duration timer is started. This timer defines how long
the current signal is monitored regarding restriking. If the time expires, the monitoring is terminated.
The monitoring is also terminated immediately if one of the following conditions is met:

• The circuit-breaker position is detected no longer as open.

• A close command is given by the device.

• The binary input signal >Stop is activated.


For safety reasons, the input signal has a preset software filtering time of 20 ms.

Measuring Value, Pickup/Dropout


During the Monitoring duration, the current signal is monitored phase-selectively regarding restriking.
As a measuring value, the fundamental component of the current is used.

• On one hand, current peaks are damped but still detected reliably by the fundamental-component value.

• On the other hand, a DC (Direct Current) component is suppressed. A DC component can occur after
switching off the circuit breaker.
Thus, the fundamental-component value is a good choice for a reliable restrike detection.
If any phase current exceeds the set current threshold value, the function picks up. The coming pickup indi-
cates the first restrike current pulse. With the pickup, the operate delay timers are started, see also the
following description Delay/Tripping, Page 937.

936 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

[lo_pickdrop-210113-01.vsd, 1, en_US]

Figure 6-270 Logic Diagram for Measuring Value, Pickup/Dropout of the Circuit-Breaker Restrike Protection

If restriking occurs, the current signal drops below the current threshold if the time between restrike pulses is
long enough. In this case, the operate delay must not be reset. During the dropout delay, the pickup is
extended to ensure that the operate delay timers are not reset. However, if the dropout delay time expires (no
new current peak occurred), the function drops out and the operate delay timers are reset.

Delay/Tripping
In the first step, tripping of the local circuit breaker can be repeated. Tripping is repeated after expiration of
the settable delay T1. The retrip on the local circuit breaker is as a safety mechanism as well. In the event of a
wrong start and pickup, only the local circuit breaker is opened instead of the superordinated circuit breaker.
Time delay T2 (backup tripping) can start in parallel either with the start of time T1 or after expiration of time
T1.
If time delay T2 expires, circuit-breaker restriking takes place and the backup-tripping signal Trip T2 is
generated.
If the >CB defect input signal is valid, any repetition of the trip signal is suppressed and the backup-trip-
ping signal Trip T2 is generated immediately (without delay). For safety reasons, a default software filter
time of 20 ms is preset (configurable in DIGSI) for the binary input signal >CB defect.
The Minimum operate time parameter defines the minimum duration for the trip command of the func-
tion. In contrast to other protection functions, the parameter is set within its own function. As a result, the
setting is independent of the identically named comprehensive parameter that is set in the Device settings.

[lo_deltrip-030211-01.vsd, 2, en_US]

Figure 6-271 Logic Diagram for Delay/Tripping of the Circuit-Breaker Restrike Protection

SIPROTEC 5, 7SJ82/7SJ85, Manual 937


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

6.43.4 Application and Setting Notes

Parameter: Switch On or Off Additional Plausibility Release Criteria

• Default setting (_:101) Plausibility via 50BF fct. = no

• Default setting (_:102) Plaus. via open/trip cmd = no

• Default setting (_:103) Plaus. via binary input = no


When using the plausibility release, the start condition and the release condition instead of only the start
condition must be present to start the current monitoring regarding restriking. Since the current threshold
value is set below the operating current, a false start would directly cause tripping. Thus, the plausibility
release strongly reduces the risk that a falsely given start criterion leads to a wrong tripping of the superordi-
nated circuit breaker.
3 different release criteria are available. You can use one or more than one or none of them. The selection
depends on the application.

NOTE

i When using release criteria, it must be ensured that the criteria are given under all the conditions where
the Circuit-breaker restrike protection shall be started. If you choose no release criteria, the release is
permanently given.

• Open/trip command by the device


Use this criterion in case that all control or trip commands are given by the protection device.

NOTE

i Opening the circuit breaker manually without using the device will not release the start of the Circuit-
breaker restrike protection.

• Pickup of the Circuit-breaker failure protection


Use this criterion if the Circuit-breaker restrike protection should only be started in case that the Circuit-
breaker failure protection was started (picked up) before.

NOTE

i Opening the circuit breaker by control or manually will not trigger the Circuit-breaker failure protection.
Consequently the Circuit-breaker restrike protection cannot be released either.

• Binary input signal


Use this option if neither of the above 2 release criteria fit the application and you want to define your own
release criterion.

Input signals: >Start, >release, >Stop

Input Signals Description


>Start This input signal allows to start the monitoring, for example, via
protocol commands from a master (by use of a CFC chart) or by other
specific conditions.
>release This input signal allows to define specific release conditions by use of a
CFC chart. Also refer to Parameter: Switch On or Off Additional Plausi-
bility Release Criteria , Page 938.
>Stop This input signal allows to stop the monitoring, for example, via
protocol commands from a master (by use of a CFC chart) or by other
specific conditions.

938 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

The input signals >Start , >release , and >Stop have a filtering time of 20 ms as default setting. If a
transient spurious signal to the binary inputs is expected due to the design of the external binary-input control
circuits and environmental conditions, the filtering time can be extended.

Parameter: Position recognition delay

• Default setting (_:105) Position recognition delay = 0.02 s


With the parameter Position recognition delay, you define how long the circuit breaker must be
detected as open (via the circuit-breaker auxiliary contacts) before the monitoring time is started. This defini-
tion is a safety feature to ensure that the monitoring is not started too early. For example, in case that due to a
non-standard auxiliary-contacts configuration, the circuit-breaker is already detected as open while current
flow is still present.
The setting depends on the circuit-breaker auxiliary-contacts configuration. If it can be ensured that the auxil-
iary contacts announce the circuit breaker as open after the current flow is interrupted, the time can be set to
zero.

Parameter: Monitoring duration

• Default setting (_:104) Monitoring duration = 200.00 s


With the parameter Monitoring duration , you define how long the current signal is monitored regarding
restriking after the circuit breaker has been opened.
With ongoing discharging of the capacitor bank, the probability of restriking is decreasing. There is no need to
set the monitoring time longer than the discharging time. Siemens recommends setting the monitoring time
in the range of 0.5 * discharging time to 1 * discharging time.

Parameter: Threshold

• Default setting (_:3) Threshold = 0.250 A


After opening of the circuit breaker, the phase currents are compared with the threshold value. If no restriking
takes place, the current is zero. Consequently the threshold for detecting restriking can be set much smaller
than the operating current. A typical value is 25 % of the operating current.
With a threshold below the operating current, a falsely-given start directly cause tripping. For minimizing this
risk, Siemens recommends applying a release criterion additionally. Refer to Parameter: Switch On or Off Addi-
tional Plausibility Release Criteria , Page 938.

Parameter: Dropout delay

• Default setting (_:7) Dropout delay = 0.05 s


The parameter Dropout delay ensures that a short dropping below the current threshold does not cause
the operate delay timers to be reset.
Since restriking is normally a periodical effect, the dropout delay can be set to a rather small time. Siemens
recommends applying the default value of 50 ms.

Input signal: >CB defect


The input signal >CB defect has a preset filtering time of 20 ms. This filtering time prevents the input
signal from becoming effective in the case of a transient activation of the physical binary input, which can be
caused by the pressure change when the circuit breaker opens.
This time can be set to 0 if such a transient response of the physical binary input can be excluded due to the
circuit-breaker design.

Parameter: Retrip after T1

• Default setting (_:106) Retrip after T1 = start T2 after T1

SIPROTEC 5, 7SJ82/7SJ85, Manual 939


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

Parameter Value Description


start T2 after T1 The retrip on the local circuit breaker is a safety mechanism to avoid
false tripping of the superordinated circuit breaker. With generating a
retrip, only the local circuit breaker is tripped in the event of a false
start. Afterwards the Circuit-breaker restrike protection function drops
out during the T2 delay time.
Siemens recommends applying a retrip on the local circuit breaker.
Siemens also recommends applying the parameter value start T2
after T1. The parameter value provides a clear chronological separa-
tion of the processes for trip repeat and backup tripping. Remember that
the overall fault-clearance time in case of circuit-breaker restriking is the
sum of T1 and T2.
no No retrip is given
parallel start T2, T1 As an alternative to the setting parallel start T2, T1 the
customer can start T2 and T1 in parallel.

Parameter: Delay T1 for 3-pole retrip

• Default setting (_:109) Delay T1 for 3-pole retrip = 0.00 s


The parameter is visible only when the parameter Retrip after T1 is set to start T2 after T1 or
parallel start T2, T1 .
The retrip on the local circuit breaker is as a safety mechanism to avoid false tripping of the superordinated
circuit breaker. In the event of a false start, only the local circuit breaker is tripped by the retrip. Afterwards the
Circuit-breaker restrike protection function will drop out during the T2 delay time.
Siemens recommends applying a retrip on the local circuit breaker. Since the retrip is a safety mechanism, it
can be given without a delay time. Siemens recommends setting the delay time to 0 s.

Parameter: Delay T2 for 3-pole trip

• Default setting (_:110) Delay T2 for 3-pole trip = 0.15 s


This parameter defines the duration of restriking after the backup tripping is sent. The following should be
considered:

• When using the retrip functionality, this delay time must ensure a safe function dropout after giving the
retrip on the local circuit breaker.
Siemens recommends applying a delay time of 150 ms which is the default setting.

Parameter: Minimum operate time

• Default setting (_:109) Minimum operate time = 0.15 s


The Minimum operate time parameter is used to set the minimum duration for the trip command of the
function.

! CAUTION
Do not set a time that is too short.
If you set a time that is too short, there is a danger (dropout of the function without the current-flow
criterion) that the device contacts interrupt the control circuit. If this happens, the device contacts
burn out.
² Set a duration that is long enough to ensure that the circuit breaker reliably reaches its final position
(open) after a control operation.

940 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

Output signal: Retrip T1


The output signal Retrip T1 must be routed to a binary output.
If only one control circuit is available for the local circuit breaker, the output signal must be routed to the
binary output to which the general circuit breaker trip command (command Position) is routed.
If a second control circuit is present, the Retrip T1 output signal can be routed to the associated binary
output.

Output signal: Trip T2


In order to trip the adjacent circuit breakers, the backup tripping (indication Trip T2 ) must be routed to a
binary output and if necessary, to an interface (intertripping to the opposite end). Thus, the circuit breaker on
the opposite end can be tripped without delay.

6.43.5 Settings

Addr. Parameter C Setting Options Default Setting


Restrike prt.#
_:1 Restrike prt.#:Mode • off off
• on
• test
_:101 Restrike prt.#:Plausibility • no no
via 50BF fct.
• yes
_:102 Restrike prt.#:Plaus. via • no no
open/trip cmd
• yes
_:103 Restrike prt.#:Plaus. via • no no
binary input
• yes
_:106 Restrike prt.#:Retrip after • no start T2 after T1
T1
• start T2 after T1
• parallel start T2, T1
_:104 Restrike prt.#:Monitoring 1.00 s to 600.00 s 200.00 s
duration
_:105 Restrike prt.#:Position 0.00 s to 60.00 s 0.02 s
recognition delay
_:3 Restrike prt.#:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 50 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.250 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.250 A
_:7 Restrike prt.#:Dropout 0.00 s to 60.00 s 0.05 s
delay
_:107 Restrike prt.#:Delay T1 0.00 s to 60.00 s 0.00 s
for 3-pole retrip
_:108 Restrike prt.#:Delay T2 0.05 s to 60.00 s 0.15 s
for 3-pole trip
_:109 Restrike prt.#:Minimum 0.00 s to 60.00 s 0.15 s
operate time

SIPROTEC 5, 7SJ82/7SJ85, Manual 941


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.43 Circuit-Breaker Restrike Protection

6.43.6 Information List

No. Information Data Class Type


(Type)
Restrike prt.#
_:500 Restrike prt.#:>Start SPS I
_:501 Restrike prt.#:>Stop SPS I
_:502 Restrike prt.#:>release SPS I
_:82 Restrike prt.#:>Block function SPS I
_:503 Restrike prt.#:>CB defect SPS I
_:54 Restrike prt.#:Inactive SPS O
_:52 Restrike prt.#:Behavior ENS O
_:53 Restrike prt.#:Health ENS O
_:304 Restrike prt.#:Release by plausibility SPS O
_:303 Restrike prt.#:Monitoring running SPS O
_:55 Restrike prt.#:Pickup ACD O
_:301 Restrike prt.#:Retrip T1 ACT O
_:302 Restrike prt.#:Trip T2 ACT O

942 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

6.44 Restricted Ground-Fault Protection

6.44.1 Overview of Functions

The Restricted ground-fault protection function (ANSI 87N):

• Detects ground faults in transformers, shunt reactors, neutral reactors or rotating machinery in which the
neutral point is grounded.

• Has high sensitivity to ground faults near the neutral point.

• Is supplemental main protection to longitudinal differential protection.

• Protects grounding transformers in the protection range. It is required that a current transformer be used
in the case of neutral point feed, that is, between neutral point and grounding conductor. The neutral
point transformer and the phase current transformer define the protection range.

• Adapts itself to the highest-amperage side with auto transformers and thereby prevents overfunction in
the event of external ground faults.

6.44.2 Structure of the Function

The Restricted ground-fault protection function is used in the Transformer side or Auto transformer
protection function group. Furthermore, you can use the function in the stabilizing winding of the auto trans-
former or also in the Standard UI function. The function depends upon application in the corresponding appli-
cation template preconfigured by the manufacturer or can be copied during the engineering into the corre-
sponding function group.
The Restricted ground-fault protection function is stepless.

[dwstrupt-170712-01.tif, 2, en_US]

Figure 6-272 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 943


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

6.44.3 Function Description

Logic of the Function

[loreffkt-170712-01.tif, 1, en_US]

Figure 6-273 Logic Diagram of the Restricted Ground-Fault Protection Function

The protection function processes the neutral-point current I0* (exactly 3I0) and the calculated zero-sequence
current I0** (exactly 3I0) from the phase currents (see following figure). The protection range extends exclu-
sively over the transformer winding, including current transformer. The amount-adapted (compensated)
currents are described by the * symbol. They are normalized to the rated object current of the respective side.
In case of an internal ground fault, the residual currents flow to the fault location. With an external ground
fault, the fault current inverts itself in the phase current transformers. In this way, the direction of current flow
serves as the decisive criterion for an internal fault.

944 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

[dwgrdpri-170712-01.tif, 1, en_US]

Figure 6-274 Basic Principle of the Function

In accordance with the logic diagram, Figure 6-273 the protection function consists of 3 parts:

Effect of Pickup Value


The differential current and the restraint current are calculated from the residual currents. The reference
arrows are defined as positive when pointing to the protected object (see Figure 6-274). Consider that the
ground current in the fault record and in the DIGSI 5 Test Suite are displayed as positive if the current flows to
ground from the protected object.

NOTE

i The following calculation applies to the configurations with a current transformer for the side. In a special
case of several current transformers per side, the calculation of the restraint current must be performed in
greater detail.

I0* = km · 3I0'
I0** = km · 3I0'' → 3I0'' = IA + IB + IC
with km = IN,transformer/IN,side
IDiff,REF = |I0* + I0**|
IRest,REF = |I0*| + |IA| + |IB| + |IC|
where:
3I0' Measured zero-sequence current at neutral point
3I0'' Zero-sequence current calculated from the phase currents
km Factor for magnitude adaptation
Irated,transformer Primary transformer rated current
Irated,side Primary rated current of the transformer side
IDiff,REF Differential current
IRest,REF Restraint current

Using the calculated restraint current, a current Ichar. curve which represents the pickup value for the tripping is
determined from the characteristic curve (Figure 6-275). In this way, the protection function is stabilized in
the event of external, multiphase ground faults, for example, a 2-pole ground fault. This means that the
protection function becomes less sensitive.
If the Slope = 0 is set here, the set Threshold of the operate curve is delivered independent of the restraint
current.

SIPROTEC 5, 7SJ82/7SJ85, Manual 945


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

[dwstabke-170712-01.tif, 1, en_US]

Figure 6-275 Stabilized Characteristic Curve

Processing a Ground Side for Auto Transformer


Instead of a 1-phase neutral point, with an auto transformer, a 3-phase ground side can also be used.

[dwautraf-201112-01.tif, 1, en_US]

Figure 6-276 Connecting a Ground Side on the Auto Transformer

In this case, the neutral-point current calculates as sum of the phase currents of the ground side:
I0* = km · 3I0' → 3I0' = Ignd,A + Ignd,B + Ignd, C
with km = IN,transformer/IN,side

946 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

The following applies for the restraint current:


IRest,REF = |Ignd,A| + |Ignd,B| + |Ignd,C| + |IA| + |IB| + |IC|

NOTE

i If both 1-phase neutral point and 3-phase ground side are connected, only the 1-phase neutral point is
used by the restricted ground-fault protection. The 3-phase ground side is not considered.

Pickup
If the IDiff,REF calculated differential current exceeds the calculated current Ichar. (see Figure 6-273), pickup
occurs and the internal processing is enabled. The pickup is indicated.

Operate Curve
The operate curve represented in the following figure consists of 2 parts. In the right part of the characteristic
curve, you will find a case of an internal ground fault. Under ideal conditions, the angle between the two
residual currents (∠(I0*, I0**)) equals 0. With current-transformer saturation, angle errors can result. The right
part of the characteristic curve is valid for angles ≤ 90°. The tripping current is the current flowing at the
neutral point (I0*). It is compared to the set or increased threshold value.

[dwausken-170712-01.tif, 1, en_US]

Figure 6-277 Operate Curve Depending on the Phase Angle between l0* and I0** at |I0*| = |I0**| (180° =
External Fault)

In case of an external ground fault, the zero-sequence current calculated from the phase currents reverses by
180°. The phase angle between the residual currents thus (∠(I0*, I0**)) equals 180°. They are located in the
left part of the operate curve and recognize a clearly increased pickup value. Angle deviations of 180° are
caused by transformer saturation in conjunction with external short-circuits.
The current IAngle,REF for the Angle Decision is determined from the following subtraction and summation:
IAngle,REF = |I0* - I0**| - |I0* + I0**|
The resulting current IAngle,REF results from the respective fault conditions, which are illustrated in the following
figure. With an internal fault (angle = 0°), a current results that has a negative sign. If angle errors occur, the
sign remains negative. The amount of the current decreases.

SIPROTEC 5, 7SJ82/7SJ85, Manual 947


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

In an external short circuit (180°), the current becomes positive. At a smaller angle (<180°) due to transformer
saturation, the angle remains positive. The amount also decreases.

[dwwinken-011112-01.tif, 1, en_US]

Figure 6-278 Angle Decision in Internal and External Faults

For tripping to occur, the neutral-point current I0* must reach the value IREF,off. The characteristic curve in the
left part of the figure can be determined from the following relationship:
IREF,off = Ichar + k · IAngle,REF
where:
Ichar. curve Pickup value resulting from the pickup value increase
k Factor (permanently set to 4.05657. With this value, the limit angle at |I0*| = |I0**| is
precisely 100°. No tripping is possible from this angle on.)

Processing of Several Measuring Points on One Side


If several measuring points are present on one side of a star winding, as with a 1 1/2 circuit-breaker layout, the
angle decision occurs separately for each measuring point. The maximum current IAngle,REF is used to establish
the tripping decision.

NOTE

i With an external fault, the current IAngle,REF is always > 0.

The following figure shows the behavior under different fault conditions.
Also observe that the restraint current (IRest.,REF) always results from the sum of all currents (phase currents of
the measuring points and the neutral-point current). For pickup, the differential current IDiff,REF is necessary.
This differential current results from the geometric sum of all adapted residual currents. The residual currents
of the measuring points on the outgoing side and of the neutral-point current are meant here.

948 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

[dwfehler-291112-01.tif, 1, en_US]

Figure 6-279 Behavior under Different Fault Conditions

Functional Measured Values

Measured Value Description


(_:306) I REF,operate Operate quantity of the restricted ground-fault protection from
the angle criterion
(_:307) I Angle,REF Stabilizing value (angle) of the restricted ground-fault protection
from the angle criterion
(_:311) I REF,Trip operate Operate quantity of the restricted ground-fault protection when
OFF
(_:312) I angle,REF operate Stabilizing value of the restricted ground-fault protection when
OFF
(_:301) I diff. Differential current
(_:302) I restr. Restraint current

You will find the measured values for the Restricted ground-fault protection under the following device
menu entries:

• Main menu → Measurements → function → Function values → 87N REF

6.44.4 Application and Setting Notes

NOTE

i The following conditions must be observed when setting the threshold values:
Threshold value ≥ max {0.05 I/Irated,S ; 0.05 I/Irated,S * Iprim transf. max / Irated, protected object}
Threshold value ≤ min {2.00 I/Irated,S ; 100.00 I/Irated,S * Iprim transf. max / Irated, protected object}
The value 0.05 I/Irated,S is the minimum possible setting value and 2.00 I/Irated,S the
maximum possible. Iprim,transf. max is the largest transformer current and Irated,protected object the protected object
rated current. 100.00 I/Irated,S is the upper measurement limit.
If otherwise, it could happen that there is chattering of the pickup indication, the minimum threshold limit
is lifted. The maximum limit on the other hand is corrected downward, if the exceeding current otherwise
through the magnitude scaling must be so large, that it would already be outside of the measuring range
of the transformer.
The adaptation of the setting limits is done automatically. In addition, a setting is prevented outside of
these limits.

SIPROTEC 5, 7SJ82/7SJ85, Manual 949


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

In the following, typical applications are described for the restricted ground-fault protection.

Protection of a Solidly Grounded Star Winding (Y Side)

[dwanster-170712-01.tif, 1, en_US]

Figure 6-280 Application Star Side

This application is a standard application. Here the phase currents of one side and the neutral-point current
are processed. The function is located in the Transformer Side function group.
The following figure show the structural division of the function. The restricted ground-fault protection gets
its measurands from the current transformers, which are connected to the Transformer side function group.
The neutral-point current is guided via the Transformer neutral point function group to the Transformer
side function group. To be compatible with SIPROTEC 4 (including reference arrow definition of the restricted
ground-fault protection), in addition to the magnitude scaling of the neutral-point current, a rotation of the
polarity (phase rotation by 180°) is also done in the Transformer neutral point function group.

NOTE

i The fault record indicates the analog traces according to the connection. For this reason, the neutral-point
current is shown rotated by 180° in comparison to SIPROTEC 4.

[dw2wtyde-201112-01.tif, 2, en_US]

Figure 6-281 Function Group Structure of the Restricted Ground-Fault Protection

950 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

Explanations on the Connection and Current-Direction Definition


Uniform reference arrows and transformer burdens are defined for the SIPROTEC 5 device series. These agree-
ments also apply to the transformer protection devices. The special handling of the neutral-point current
described previously is a result of this.
The current definition states that the sum of the currents flowing into the protected object is equal to 0 (IA + IB
+ IC + IN = 0 or IA + IB + IC = -IN). The protected object is located to the right or left of the transformer set. The
following basic connections result from this.

[tileite2-070211-01.tif, 3, en_US]

Figure 6-282 Current-Transformer Connection (1) According to Definition

or

[tileite4-260313-01.tif, 3, en_US]

Figure 6-283 Current-Transformer Connection (2) According to Definition

The following connection is defined for the transformer according to Figure 6-284. The current flow for an
external ground fault is entered at the same time. It is recognized that the secondary currents each flow from
the device. From this, a differential current (IDiff,REF = |IY + IA + IB + IC| = | -I4 - I3|) results, according to the refer-
ence arrow definition for the restricted ground-fault protection (positive to the protected object) with an

SIPROTEC 5, 7SJ82/7SJ85, Manual 951


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

external ground fault. To prevent that, the neutral-point current is rotated in the Transformer neutral-point
function group. It follows that: IDiff, REF = |I4 – I3| = 0.

NOTE

i If the neutral-point current is included in the protection function (zero-sequence current correction), this
rotation also has an effect for the differential protection.

[dwstwnas-281112-01.tif, 1, en_US]

Figure 6-284 Current-Transformer Connection on the Transformer

The setting of the 1-phase measuring point based on the definition is done as follows:

[scedsall-200214-01, 1, en_US]

Figure 6-285 DIGSI 5 Setting

The point in Figure 6-284 describes the polarity of the current transformer. At the same time, the current
terminal is designed so that this side is fed out on an odd number terminal point. Since in the SIPROTEC 5
system each current transformer can be assigned a 1-phase measuring point, the odd number terminal points
are named in the setting parameters. According to Figure 6-284, the setting must be yes.

952 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

• Default setting (_:115) terminal 1,3,5,7 in dir.obj.= yes


The following view can be used to derive the threshold value. The transformer is supplied, for example, via the
delta winding and a 1-pole ground fault occurs on the star side.

NOTE

i For estimation of the short-circuit current, note that the inductance changes quadratically with the winding
and linearly with the voltage.

The right part in the following figure represents the fault current as a function of the fault location. The fault
current curve IF1 shows that the longitudinal differential protection with faults near the neutral point has
sensitivity problems due to the sinking current. On the other hand, the neutral-point current IF2 is sufficiently
large. There is therefore no need to set the Threshold (current through the neutral point transformer) to
sensitive.

[dwf1pole-170712-01.tif, 1, en_US]

Figure 6-286 Principal Fault Current Curves with a 1-Pole Ground Fault

• Recommended setting value (_:103) Threshold = 0.2 I/Irated,S


The previously mentioned condition must be maintained during the setting.

[foschwe1-170712-01.tif, 1, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 953


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

The following lower limiting value results from the data from Figure 6-280:

[foschwe2-041012-01.tif, 1, en_US]

The recommended setting value of 0.2 I/Irated,S lies above it.

• Recommended setting value (_:105) Slope = 0.07


You can stabilize the protection function (less sensitive setting) with external multiphase short-circuits to
ground with the parameter Slope. To determine the setting value, no pickup value increase can occur up to
the rated current. After this, the gradient must be active. To derive the gradient, it is assumed that continua-
tion of the straight line must go through the coordinate origin (see Figure 6-287). Determine the intersection
from the threshold value and the restraint current at rated current. Calculate the gradient as follows:

[fostbref-231012-01.tif, 1, en_US]

[dwsteiga-221012-01.tif, 2, en_US]

Figure 6-287 Derivation of the Setting Value for the Gradient

If you have several measuring points on an outgoing side (see Figure 6-279), Siemens recommends using the
value 3 I/Irated,S in the intersection calculation for the restraint current. In the load case, the maximum trans-
former rated current flows on one side.
If, however, several measuring points are on the supply side (for example, breaker-and-a-half layout), Siemens
recommends including all phase currents in the intersection calculation, in order to avoid too strong a stabili-
zation. With 2 measuring points, a value of 6 I/Irated,S results as intersection with the threshold value. The
slope becomes flatter (0.2 I/Irated,S/6 I/Irated,S = 0.03).

954 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

Protection of an Auto Transformer

[dwsptran-170712-01.tif, 1, en_US]

Figure 6-288 Activation and Application Example of an Auto Transformer (500 MVA: 400 kV, 230 kV;
125 MVA: 34.5 kV)

Use the highest side rated current with the auto transformer for normalization. In the example (Figure 6-288),
the measuring point is M2 (230 kV side). For this side, a rated current of 500 MVA/(√(3) · 230 kV) = 1255 A
results. The primary transformer rated current is 1500 A. With this, you can estimate the minimum permissible
pickup value.

[foscwe01-170712-01.tif, 1, en_US]

Siemens recommends a setting value of 0.2 I/Irated,S.

• Recommended setting value (_:103) Threshold = 0.2 I/Irated,S

SIPROTEC 5, 7SJ82/7SJ85, Manual 955


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

To determine the Slope, the restraint current of both sides (400 kV and 230 kV) must be used. The rated
current is used as starting value for the gradient. Since side 2 (230 kV) is the reference side for the normaliza-
tion, the value of the 400 kV side must be adapted to this rated current. The adaptation factor results from the
inverse ratio (230 kV/400 kV). The following restraint current goes into the calculation:

[fostbrst-231012-01.tif, 1, en_US]

Siemens recommends using the setting value 0.07.

• Recommended setting value (_:105) Slope = 0.07

Protection of a Resistance-Grounded Star Winding (Y Side)

[dwrefspa-170712-01.tif, 1, en_US]

Figure 6-289 Application with Resistance-Grounded Neutral Point

To also capture faults in the resistance to ground, a current transformer must be installed at the neutral point
of the protected object (see Figure 6-289). The pickup values can be derived from the data in the example. As
side rated value, the following results:
140 MVA/(√3 · 20 kV) = 4042 A
The following threshold value results as lower limit:

956 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

[foschwe3-170712-01.tif, 1, en_US]

So that the function is responsive, select a setting value of 0.08 I/Irated,S.

• Recommended setting value (_:103) Threshold = 0.08 I/Irated,S


As gradient, the following results:

[fosteig1-170712-01.tif, 1, en_US]

• Recommended setting value (_:105) Slope = 0.03


Because of the grounding resistance RE reduced protection range results. This can be estimated as follows: The
grounding resistance is much larger than the winding reactance, thus the following maximum ground current
results:
IGnd max = 20 kV/(√3 · 12 Ω) = 962 A
You can determine the minimum tripping current from the setting value:
IGnd min = side rated current * threshold value = 4042 A · 0.08 = 323 A
Thus, the following protection range results:

[foschwe4-170712-01.tif, 1, en_US]

The attainable protection range amounts to approx. 66.4 %. In order to capture ground faults near the neutral
point, it is also recommended to connect a sensitive ground current protection to the neutral point trans-
former. You must coordinate its operate time with the line protection.

NOTE

i Ensure that the protection range further limits itself with larger neutral-point resistances, or the restricted
ground-fault protection can no longer be used.

Protection with Neutral Reactors on the Delta Side


To produce ground currents on the delta side of a transformer, neutral reactors (zigzag reactors) are used. A
resistance for ground current limitation can also be present. In this case, the resistance is much greater than
the reactor and delta reactance of the transformer. The following figure shows a typical implementation. The
restricted ground-fault protection works between output-sided phase current transformers and the current
transformer in the neutral point of the neutral reactor.
In the example, the fault current curve with the ground fault in a delta winding is also represented. The fault
location in which the lowest fault current flows can also be seen. This current influences the protection setting
set close.

SIPROTEC 5, 7SJ82/7SJ85, Manual 957


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

[dwstrpkt-170712-01.tif, 1, en_US]

Figure 6-290 Application with Neutral Reactor

As side rated value, the following results:


140 MVA/(√3 · 34.4 kV) = 2343 A
You can thus define the lower limit for the threshold value:

[foschwe5-170712-01.tif, 1, en_US]

If the fault is in the middle of the winding, the minimum ground current will arise, as shown in Figure 6-290.
The driving voltage is:
VGnd min = Vrated,S2/(2 √3) = 34.5 kV/(2 √3) = 9.96 kV
The following minimum ground current results:
IGnd min = VGnd min/RGnd = 9.96 kV/19.05 Ω = 523 A
With reference to the side rated current, the relationship is:
IGnd min/Irated,S = 523 A/2343 A = 0.223
With a safety margin of 2, 0.223/2 = 0.1115 results. Select this value as threshold value (rounded: 0.12 I/
Irated,S).

• Recommended setting value (_:103) Threshold = 0.12 I/Irated,S


As gradient, the following results:

958 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

[fosteig2-170712-01.tif, 1, en_US]

• Recommended setting value (_:105) Slope = 0.04

Protection of a Shunt Reactor

[dwanquer-170712-01.tif, 1, en_US]

Figure 6-291 Application with Neutral Reactor

As side rated value, the following results:


10 MVA/(√3 · 132 kV) = 43.7 A
You can thus define the lower limit for the threshold value:

[foschwe6-170712-01.tif, 1, en_US]

Select 0.35 I/Irated,S as threshold value.

• Recommended setting value (_:103) Threshold = 0.35 I/Irated,S


For the shunt reactor, there is no external fault that can lead to overfunction. Siemens recommends a
minimum rise (0.05).

• Recommended setting value (_:105) Slope = 0.05

6.44.5 Settings

Addr. Parameter C Setting Options Default Setting


87N REF #
_:1 87N REF #:Mode • off off
• on
• test

SIPROTEC 5, 7SJ82/7SJ85, Manual 959


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.44 Restricted Ground-Fault Protection

Addr. Parameter C Setting Options Default Setting


_:2 87N REF #:Operate & flt.rec. • no no
blocked
• yes
_:103 87N REF #:Threshold 0.05 I/IrObj to 2.00 I/IrObj 0.20 I/IrObj
_:105 87N REF #:Slope 0.00 to 0.95 0.07
_:109 87N REF #:Operate delay 0.00 s to 60.00 s; ∞ 0.00 s
_:191 87N REF #:Reference side is • not assigned not assigned
• Side 1
• Side 2
• Side 3
• Side 4
• Side 5

6.44.6 Information List

No. Information Data Class Type


(Type)
87N REF #
_:82 87N REF #:>Block function SPS I
_:54 87N REF #:Inactive SPS O
_:52 87N REF #:Behavior ENS O
_:53 87N REF #:Health ENS O
_:55 87N REF #:Pickup ACD O
_:57 87N REF #:Operate ACT O
_:303 87N REF #:Operate delay expired ACT O
_:305 87N REF #:Block by direct. det. SPS O
_:306 87N REF #:I REF,operate MV O
_:307 87N REF #:I Angle,REF MV O
_:311 87N REF #:I REF,Trip operate MV O
_:312 87N REF #:I angle,REF operate MV O
_:301 87N REF #:I diff. MV O
_:302 87N REF #:I restr. MV O

960 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.45 External Trip Initiation 3-Pole

6.45 External Trip Initiation 3-Pole

6.45.1 Overview of Functions

The External trip initiation function:

• Processes any signals from external protection or supervision devices

• Enables the integration of any signals from external protection equipment in the indication and tripping
processing, for example from transient ground-fault relays or Buchholz protection

• Enables direct tripping of the circuit breaker in conjunction with busbar-protection applications

• Enables direct tripping of the circuit breaker in the case of circuit-breaker failure at the other line end

6.45.2 Structure of the Function

The External trip initiation function contains one stage. You can instantiate the External trip initiation func-
tion in DIGSI 5 multiple times.

[dwstrext-030211-01.tif, 1, en_US]

Figure 6-292 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 961


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.45 External Trip Initiation 3-Pole

6.45.3 Stage Description

Logic of the Stage

[lotrip3p-070611-01.tif, 1, en_US]

Figure 6-293 Logic Diagram for the External Trip-Initiation Stage

Binary Input Signal >External Trip


The binary input signal >External trip starts the Pickup and the Operate delay.

Blocking the Stage


The stage can be switched to ineffective via a number of signals. If the stage is in the pickup state at the time
of blocking, it will be immediately reset. However, the operate indication remains stopped for the minimum
operating time (_:102) Minimum operate time.

6.45.4 Application and Setting Notes

Parameter: Operate delay

• Recommended setting value (_:901:6) Operate delay = 0.05 s


The Operate delay parameter must be set for the specific application. After expiry of the Operate delay
the time-out and tripping are signaled. The duration of the initiation signal as well as the adjustable minimum
command time determine the signal duration of the Operate.

962 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.45 External Trip Initiation 3-Pole

6.45.5 Settings

Addr. Parameter C Setting Options Default Setting


Stage 1
_:901:1 Stage 1:Mode • off off
• on
• test
_:901:2 Stage 1:Operate & flt.rec. • no no
blocked
• yes
_:901:6 Stage 1:Operate delay 0.00 s to 60.00 s 0.05 s

6.45.6 Information List

No. Information Data Class Type


(Type)
Stage 1
_:901:82 Stage 1:>Block function SPS I
_:901:501 Stage 1:>External trip SPS I
_:901:54 Stage 1:Inactive SPS O
_:901:52 Stage 1:Behavior ENS O
_:901:53 Stage 1:Health ENS O
_:901:55 Stage 1:Pickup ACD O
_:901:56 Stage 1:Operate delay expired ACT O
_:901:57 Stage 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 963


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

6.46 Automatic Reclosing Function

6.46.1 Overview of Functions

The Automatic reclosing function:

• Automatically closes overhead lines after arc short-circuits

• Is only permissible for overhead lines, because only the possibility of self-activated extinguishing of an
arc short-circuit exists here

• Can be controlled by integrated protection functions and by external protection devices

• The automatic reclosing can occur through an external automatic reclosing function via binary inputs.
The automatic reclosing after switching off through a short-circuit protection is taken over by the automatic
reclosing function (AREC). The following figure shows an example for the normal procedure with a two-time
automatic reclosing where the second automatic reclosing attempt is successful.

[dw2awewz-090210-01.tif, 1, en_US]

Figure 6-294 Process Diagram of a Two-Time Reclosing With Action Time (2nd Reclosing Successful)

The integrated Automatic reclosing function allows for up to 8 reclosing attempts. Each of the 8 disruption
cycles can work with different parameters.

6.46.2 Structure of the Function

The Automatic reclosing function is used in function groups for circuit breakers. In a function group for circuit
breakers, one of the 3 types of functions illustrated in the following figures can be used. The Automatic
reclosing function has a central function control.

[dwfktawe-100611-01.tif, 1, en_US]

Figure 6-295 Structure/Embedding of the Function

Cyclic Automatic Reclosing Function


The Cyclic automatic reclosing function (Figure 6-296) allows up to 8 reclosing attempts. Here each disruption
cycle can work with different settings.

964 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

For the Cyclic automatic reclosing function, 1 cycle is preset. The preset cycle cannot be deleted. You can add
and delete additional cycles from the function library in DIGSI 5.

[dwzykawe-100611-01.tif, 1, en_US]

Figure 6-296 Structure/Embedding of the Cyclic Automatic Reclosing Function

Automatic Reclosing Function with Adaptive Dead Time


The Automatic reclosing function with adaptive dead time (ADT) works without fixed disruption cycles
(Figure 6-297). The requirement for the usage of ADT is that voltage transformers on the line-side are
connected or there is a possibility to transfer a close command to a remote line end. With the ADT, the Auto-
matic reclosing function decides independently if and when an automatic reclosing is reasonable and permis-
sible and when it is not. The criteria is the phase-to-ground voltage, which is switched through after reclosing
from the opposite line end. The Automatic reclosing function with ADT occurs as soon as it is known that the
line from the opposite end has been placed back under voltage.

[dwaweasp-100611-01.tif, 1, en_US]

Figure 6-297 Structure/Embedding of the Automatic Reclosing Function With Adaptive Dead Time (ADT)

Operation with External Automatic Reclosing Function


The cooperation of an external reclosing device with the SIPROTEC protection device occurs via the function
mode Operation with external automatic reclosing function (Figure 6-298). The function only provides
binary inputs for the influence of the protection functions in the SIPROTEC protection device. The external
reclosing device delivers the close command. The SIPROTEC protection functions then provide for the trip
commands.

[dwextawe-100611-01.tif, 1, en_US]

Figure 6-298 Structure/Embedding of the Operating Function With External Automatic Reclosing Function

Function Control
The Automatic reclosing function contains a central function control, see the following figure. You can find
detailed information on the function control in the chapter Function/Stage Control.

SIPROTEC 5, 7SJ82/7SJ85, Manual 965


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[loarcfkt-090211-01.tif, 1, en_US]

Figure 6-299 Function Control for the Automatic Reclosing Function

6.46.3 Cooperation of the Automatic Reclosing Function and Protection Functions

The Automatic reclosing function (AREC) can be influenced by the protection functions in the following way:

• The AREC is started through pickup indications and operate indications by the selected protection func-
tions or protection stages. The start is independent of the set operating mode for the AREC.

• Individual protection functions or protection stages can be configured so that their operate indication
blocks the AREC. If such a blocking exists, the AREC cannot be started. If the AREC is already started, the
blocking will lead to the cancellation of the AREC.
The automatic reclosing device can thus have an influence on the effects of the protection functions. The
following influence possibilities exist:

• The AREC provides signals that can be used by protection functions for the blocking or release of special
stages or zones. An example is the release of overreaching zones with distance protection.

966 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[loawesig-190912-01.tif, 1, en_US]

Figure 6-300 Signals between Protection Functions and Automatic Reclosing Functions

The configuration of the interaction between internal protection functions and automatic reclosing functions
can be set separately for each protection function, see Figure 6-300. The configuration occurs in a matrix view
in DIGSI, see the following figure..

SIPROTEC 5, 7SJ82/7SJ85, Manual 967


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[scdigsia-080311-01.tif, 1, en_US]

Figure 6-301 Configuration of the Protection Functions for Starting and Blocking the Automatic Reclosing
Function in DIGSI 5

If a protection function or the stage of a protection function is connected with the AREC through the matrix,
this means that the respective pickup and operate indications are forwarded to the AREC.
The links can be conducted separately

• For starting the automatic reclosing function and

• For the blocking of the automatic reclosing function


The Automatic reclosing function also has the corresponding binary inputs and binary outputs through which
the external protection devices can be connected to the internal Automatic reclosing function.

6.46.4 Cyclic Automatic Reclosing Function

6.46.4.1 Operating Modes for Cyclic Automatic Reclosing Function


For the cyclic automatic reclosing function, there are 4 operating modes, from which one can be selected for
the parameterization (parameter (_:6601:101) 79 operating mode).
The selection of the operating mode is dependent on the tripping behavior of the protection functions and the
circuit breaker.
For applications with 3-pole tripping, all 4 operating modes are available.

• Operating mode 1: with op., with act. time

• Operating mode 2: w.pickup, w. action time

• Operating mode 3: with op., w/o act. time

• Operating mode 4: w.pickup, w/o act. time

968 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Operating Mode 1: with op., with act. time


The operating mode with op., with act. time allows different automatic reclosing cycles depending
on the tripping type and operate time of the protection function(s). With this operating mode, the automatic
reclosing must be started with the operate indications. Additionally, the general pickup must also be consid-
ered.
With raising general pickup, the action times of the configured automatic reclosing cycles start. The general
pickup is in this connection the group indication of all internal protection functions configured for starting the
automatic reclosing and the external binary input for general pickup >Gen. pickup for start.
Through the time between the raising general pickup and clearing operate indication, the automatic reclosing
cycle to be started will be determined. Here for multiple automatic reclosing cycles, the sequence of the
expiring automatic reclosing cycles is not fixed, like the operating modes without action time.
The following example in Figure 6-302 shows a tripping that comes after expiration of the action time of cycle
1, but still before the expiration of the action times from cycle 2 and cycle 3. Cycle 2 is now active.
Within the following reclaim time, there will be another pickup and tripping. Since cycle 2 is already complete,
these and all lower cycles are no longer able to expire. The 2nd operate indication comes during the running
action time of cycle 3. Thus, cycle 3 is now active.

[dwarce1d-190912-01.tif, 1, en_US]

Figure 6-302 Operating-Mode Signal Examples: With Tripping/With Action Time

Through the action time, there is a direct influence on the dead time behavior of the automatic reclosing func-
tion. With faults with short operate times, other dead times can be realized than for removed faults with
longer tripping time. With faults with short operate time, an automatic reclosing is executed, with removed
faults this does not occur with longer operate time. The operating mode with op., with act. time
allows for different automatic reclosing cycles depending on the operate time of the protection function(s).

Operating Mode 2: w.pickup, w. action time


The operating mode w.pickup, w. action time allows different automatic reclosing cycles depending
on the operate time and type of fault. It is only suitable and applicable for applications with 3-pole tripping.
With this operating mode, the automatic reclosing must be started with the operate indications from the
protection functions. Additionally, the pickup sample from the conductor pickups and the general pickup are
considered:

• With 1-phase pickup, the automatic reclosing cycles set for 1-phase dead times are activated. 1-phase
pickup includes both pickup samples phase-to-ground and only grounding.

• With 2-phase pickup, the automatic reclosing cycles set for 2-phase dead times are activated.

• With 3-phase pickup, the automatic reclosing cycles set for 3-phase dead times are activated.
With each automatic reclosing cycle, it is checked to see if it is a 1-phase, 2-phase or 3-phase pickup.

SIPROTEC 5, 7SJ82/7SJ85, Manual 969


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

With raising general pickup, the action times of the configured automatic reclosing cycles start. The general
pickup is in this connection the group indication of all internal protection functions configured for starting the
automatic reclosing and the external binary input for general pickup >Gen. pickup for start.
Through the time between the raising general pickup and raising trip command, the automatic reclosing cycle
to be started will be determined. Here for multiple automatic reclosing cycles, the sequence of the expiring
automatic reclosing cycles is not fixed, like the operating modes without action time.
The following example shows a tripping that comes after expiration of the action time of cycle 1, but still
before the expiration of the action times from cycle 2 and cycle 3. Since it is a 2-phase pickup, cycle 2 is active
with the dead-time setting for 2-phase faults.
After reclosing, there will be another, this time 3-phase, pickup and tripping within the following reclaim time.
Since cycle 2 is already complete, these and all lower cycles are no longer able to expire. The trip command
comes during the current action time of cycle 3. Thus, cycle 3 is active, with the dead time setting for 3-phase
faults.

[dwarcbm2-190912-01.tif, 1, en_US]

Figure 6-303 Operating-Mode Signal Examples: With Pickup/With Action Time

Operating Mode 3: with op., w/o act. time


With the operating mode with op., w/o act. time, the respective dead time is started after each trip
command. The pickups are not considered. If more than one automatic reclosing cycle is configured, the
sequence of the expiring automatic reclosing cycles is identical with the cycle number (1, 2, and 3.).

[dwaweb3d-240810-01.tif, 1, en_US]

Figure 6-304 Operating-Mode Signal Examples: With Tripping/Without Action Time

Operating Mode 4: w.pickup, w/o act. time


With the operating mode w.pickup, w/o act. time, the automatic reclosing must be started with the
operate indications from the protection functions. It is only suitable and applicable for applications with 3-pole
tripping.

970 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

The start of the dead time occurs after each trip command. Additionally, the pickup sample from the
conductor pickups is considered:

• With 1-phase pickup, the automatic reclosing cycles set for 1-phase dead times are activated. 1-phase
pickup includes both pickup samples phase-to-ground and only grounding.

• With 2-phase pickup, the automatic reclosing cycles set for 2-phase dead times are activated.

• With 3-phase pickup, the automatic reclosing cycles set for 3-phase dead times are activated.
With each automatic reclosing cycle, it is checked to see if it is a 1-phase, 2-phase or 3-phase pickup. If more
than one automatic reclosing cycle is configured, the sequence of the expiring automatic reclosing cycles is
identical with the cycle number (1, 2, 3, etc.).

[dwarcbs4-170311-01.tif, 1, en_US]

Figure 6-305 Operating-Mode Signal Examples: With Pickup/Without Action Time

6.46.4.2 Structure of the Cyclic Automatic Reclosing Function


In Figure 6-306, the functional structure of the cyclic automatic reclosing function is illustrated as a block
diagram. The figure displays the important signals, coming from outside of the cyclic automatic reclosing
function, and the most important signals between the individual function blocks.
The automatic reclosing function works as a state machine. From the idle state AREC ready, the automatic
reclosing function gets through the tripping or pickup indications of the protection functions to the Dead time
state. After expiration of the dead time, the subsequent state is reached with the closing indication. The
reclaim time is also started together with the closing indication. If the reclaim time can expire without further
operate or pickup indications, the automatic reclosing is successful and the automatic reclosing function turns
back to idle state.
If the automatic reclosing function is restarted during the current reclaim time, there will be either a dynamic
blocking or other reclosing cycles will be executed. If other reclosing cycles are possible, there will be a dead
time start and the described process starts again.
After the end of a dynamic blocking, the automatic reclosing function switches back to idle state or it goes
into the state Static Blocking if the blocking condition is permanently present. In the following sections, the
individual function blocks are described in detail.

SIPROTEC 5, 7SJ82/7SJ85, Manual 971


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[lozykawe-310511-01.tif, 1, en_US]

Figure 6-306 Cyclic Reclosing Function: Block Diagram of Automatic Reclosing

6.46.4.3 Input Logic for Operating Modes with Tripping


The operate indications are used as starting signals. For operating modes with action time, the start of the
action time(s) occurs with the pickup messages. During all operating modes, the pickup indications are also
required during the processing of faults and for supervision during the reclaim time.

972 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Applications with 3-Pole Tripping


For applications with only 3-pole tripping options, the internal operate indications are always 3-pole. For
external starts, there is a binary input, which signalizes a 3-pole tripping of the external protection device.
The outputs of the input logic signalize that the reclosing start has occurred through a 3-pole operate indica-
tion.

[lobtaaus-100611-01.tif, 2, en_US]

Figure 6-307 Input Logic for Operating Modes: With Tripping

6.46.4.4 Input Logic for Operating Modes with Pickup


The operate indications and the pickup indications are used as starting signals. The internal pickup indications
are processed selective to the phase. Through binary inputs, the pickup information can also be coupled by
external protection devices (>Pickup A for start, >Pickup B for start and >Pickup C for
start). Optionally, the pickup information can be externally captured as a pickup sample, thus, as a 1-phase,
2-phase and 3-phase pickup.
The outputs of the input logic signalize if the automatic reclosing start occurs through a 1-phase, 2-phase, or
3-phase pickup:

• On Start with 3-phase pickup, it is recognized if all 3 phases were picked up in the period from the first
raising pickup indication up to the last clearing outgoing pickup indication.

• On Start with 2-phase pickup, it is recognized if all 2 phases were picked up in the period from the first
raising pickup indication up to the last clearing pickup indication and at no time 3 phases.

• On Start with 1-phase pickup, it is recognized if only 1 phase was picked up in the period from the first
raising pickup indication up to the last clearing pickup indication.

SIPROTEC 5, 7SJ82/7SJ85, Manual 973


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

For operating modes with action time, the start of the action time(s) occurs with the pickup indications.
During operating modes with pickup, the pickup indications affect the selection of the dead times. During all
operating modes, the pickup indications are also required during the processing of faults and for supervision
during the reclaim time.
The automatic reclosing operating modes with pickup are only ideal for applications with 3-pole tripping.
Therefore, the outputs of the input logic always signal 3-pole operate indications.

[lobtaanr-010611-01.tif, 1, en_US]

Figure 6-308 Input Logic for Operating Modes: With Pickup

6.46.4.5 Start
In the Start function block, the automatic reclosing function is switched from the idle state AREC ready to the
state Dead time, see Figure 6-309. The length of the starting signals is controlled with a supervision time.

Start-Signal Supervision Time


The start-signal supervision stops the automatic reclosing if the short circuit is not switched off within the
normal time; for example, in the case of a circuit-breaker failure.
With the first raising operate indication, the start-signal supervision time is initiated, parameter Start
signal supervis.time. The time is stopped as soon as no operate indication is active.
The automatic reclosing function is blocked if there is an expiration of the start-signal supervision time
through a long operate indication. The blocking lasts until the operate indication stops, extended by a further
0.5 s.

974 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Transition to the Dead-Time State


The transition of the automatic reclosing function to the dead-time state occurs for:

• Clearing operate indications if none of the signal inputs for operate indications are active

• or if the circuit breaker can no longer be recognized as 3-pole

• and the start-signal supervision time is not expired


Additionally, the following conditions must be fulfilled:

• The circuit breaker signalizes the readiness for automatic reclosing typically through a binary input. If the
circuit breaker is not ready, the automatic reclosing function can be statically blocked. In this situation,
the automatic closing function is not in idle state automatic closing function ready. The control of the
circuit-breaker readiness is optional and can be turned off through settings, see also chapter
6.46.4.16 Circuit-Breaker Readiness and 6.46.4.17 Blockings.

• The circuit breaker must be closed before the 3-pole trip command. This condition is not considered if the
circuit-breaker auxiliary contacts are not connected to the protection device.
You can delay the transition to the dead time state through the binary input >Dead time start delay.
As long the corresponding binary signal is present, the dead time of the automatic reclosing function will not
be started. The maximum duration of this binary signal is monitored through a time stage that can be set,
parameter Max. dead-time delay. Upon expiration of this time stage, that is, if the binary signal is
present longer than permitted, the automatic reclosing function will be blocked until the end of the binary
signal, additionally extended by another 0.5 s. See also chapter 6.46.4.17 Blockings.

[logistar-140611-01.tif, 1, en_US]

Figure 6-309 Logic for Function Block Start

6.46.4.6 Cycle Control with Operating Mode 1: With Tripping/With Action Time
The cycle control checks the readiness for each automatic reclosing cycle and controls the process of the
action time(s). In Figure 6-310, the cycle control is illustrated.

Cycle Availability
The cycle availability is influenced through the parameterization of the dead time and through a binary input.
In this way, setting the parameter Dead time aft. 3-pole trip to invalid avoids an automatic
reclosing after 3-pole tripping. Correspondingly, there is no automatic reclosing function if the Dead time

SIPROTEC 5, 7SJ82/7SJ85, Manual 975


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

aft. 1-pole trip 29 is set to invalid. If both dead times are set to invalid, the respective automatic
reclosing cycle will be completely blocked. With the binary input >Block 79 cycle, you can block the asso-
ciated automatic reclosing cycle.
For applications with 1-pole tripping, the cycle control provides a signal, based on which the protection func-
tions can recognize that the automatic reclosing function only occurs after 1-pole tripping (AR only after
1p. trip). The approval or switch over of special protection stages only occurs for types of fauts that lead to
1-pole tripping.

Action Time
If the automatic reclosing function is in the idle state automatic reclosing function ready, an incoming
general pickup will affect the start of the action time. This applies for the reclosing function cycles that are
released through the parameter Start from idle state allow. and not blocked.
During one of the started action times, the corresponding reclosing cycle is blocked and the reclosing cycle is
assigned the next highest cycle number, whose action time is running and is not blocked.
With raising trip commands, the action times are stopped and reset. The process state of the action times
existing at this moment determines the automatic reclosing cycle that should be started.
If all initiated action times expire without capturing a tripping, the automatic reclosing function does not take
place. However, if a tripping function is initiated after expiry of the action time, the automatic closing function
is blocked for 3 seconds. A new start of the reclosing function is only possible if the general pickup is no longer
active.

29 is not available for devices with only 3-pole tripping

976 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[loauswir-140611-01.tif, 1, en_US]

Figure 6-310 Cycle Control with Operating Mode: With Tripping/With Action Time

6.46.4.7 Cycle Control with Operating Mode 2: With Pickup/With Action Time
The cycle control checks the readiness for each automatic reclosing cycle and controls the process of the
action time(s). In Figure 6-311, the cycle control is illustrated.

Cycle Availability
The cycle availability is influenced through the parameterization of the dead time and through a binary input.
In this way, setting the parameter Dead time aft.1ph. pickup to invalid avoids an automatic
reclosing after 3-pole tripping due to 1-phase short circuits. This also applies to Dead time aft.2ph.
pickup and Dead time aft.3ph. pickup. If all 3 dead times are set to invalid, the respective
reclosing cycle will be completely blocked. With the binary input >Block 79 cycle, you can block the asso-
ciated automatic reclosing cycle.

SIPROTEC 5, 7SJ82/7SJ85, Manual 977


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Action Time
If the automatic reclosing function is in the idle state automatic reclosing function ready, an incoming
general pickup will affect the start of the action time. This applies for the reclosing function cycles that are
released through the parameter Start from idle state allow. and not blocked.
During one of the started action times, the corresponding reclosing cycle is blocked and the reclosing cycle is
assigned the next highest cycle number, whose action time is running and is not blocked.
With raising trip commands, the action times are stopped and reset. The process state of the action times
existing at this moment determines the automatic reclosing cycle that should be started.
If all initiated action times expire without capturing a tripping, the automatic reclosing function does not take
place. However, if a tripping function is initiated after expiry of the action time, the automatic closing function
is blocked for 3 seconds. A new start of the reclosing function is only possible if the general pickup is no longer
active.

978 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[loanrwir-140611-01.tif, 1, en_US]

Figure 6-311 Cycle Control with Operating Mode: With Pickup/With Action Time

6.46.4.8 Cycle Control with Operating Mode 3: With Tripping/Without Action Time
The cycle control checks the availability for each automatic reclosing cycle. In Figure 6-312, the cycle control
for the 1st automatic reclosing cycle and other reclosing cycles is illustrated. The further automatic reclosing
cycles are generally described with the cycle number n and apply for all other configured automatic reclosing
cycles.
The cycle availability is influenced through the parameterization of the dead time and through a binary input.
In this way, setting the parameter Dead time aft. 3-pole trip to invalid avoids an automatic
reclosing after 3-pole tripping. Correspondingly, there is no automatic reclosing function after 1-pole tripping
if the Dead time aft. 1-pole trip 30 to invalid. If both dead times are set to invalid, the respec-

30 is not available for devices with only 3-pole tripping

SIPROTEC 5, 7SJ82/7SJ85, Manual 979


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

tive automatic reclosing cycle will be completely blocked. With the binary input >Block 79 cycle, you can
block the associated automatic reclosing cycle.
For applications with 1-pole tripping, the cycle control provides a signal, based on which the protection func-
tions can recognize that the automatic reclosing function only occurs after 1-pole tripping (AR only after
1p. trip). The approval or switch over of special protection stages only occurs for types of faults that lead to
1-pole tripping.

[loauowrk-210311-01.tif, 1, en_US]

Figure 6-312 Cycle Control with Operating Mode: With Tripping/Without Action Time

6.46.4.9 Cycle Control with Operating Mode 4: With Pickup/Without Action Time
The cycle control checks the availability for each automatic reclosing cycle. In Figure 6-313, the cycle control
for the 1st automatic reclosing cycle and other reclosing cycles is illustrated. The further automatic reclosing
cycles are generally described with the cycle number n and apply for all other configured automatic reclosing
cycles.

980 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

The cycle availability is influenced through the parameterization of the dead time and through a binary input.
In this way, setting the parameter Dead time aft.1ph. pickup to invalid avoids an automatic
reclosing after 3-pole tripping due to 1-phase short circuits. This also applies to Dead time aft.2ph.
pickup and Dead time aft.3ph. pickup. If all 3 dead times are set to invalid, the respective
reclosing cycle will be completely blocked. With the binary input >Block 79 cycle, you can block the asso-
ciated automatic reclosing cycle.

[loanowrk-100611-01.tif, 1, en_US]

Figure 6-313 Cycle Control with Operating Mode: With Pickup/Without Action Time

6.46.4.10 Stage Release


The function block Stage release creates output indications for the release or switching over of special stages
for protection functions (stage release in the 1st cycle or stage release in the n. cycle). Examples for this are
the release of overreaching zones with distance protection and the dynamic adjustment of delays or threshold
values with overcurrent protection.

SIPROTEC 5, 7SJ82/7SJ85, Manual 981


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Figure 6-314 shows the tripping stage release for the 1st automatic reclosing cycle. With available automatic
reclosing functions, the tripping stage release typically occurs up to the expiration of the dead time. The cycle
number in this state is on 1. However, if the automatic reclosing cycle is set only for 1-phase 31, the tripping
stage release will be reset to the beginning of the 1-phase dead time. This is necessary, since every additional
evolving fault that occurs within the dead time causes a 3-pole cut-off, and subsequently, the automatic
reclosing function can no longer take place.

[lo1awezk-170912-01.tif, 1, en_US]

Figure 6-314 Stage Release for Protection Functions in the 1st Automatic Reclosing Cycle

The tripping stage release for higher automatic reclosing cycles is set to the beginning of the reclaim time for
rising edge close commands. Simultaneously, the cycle number is increased. The reset condition is identical to
the condition for the 1st automatic reclosing cycle. If the reduced dead time (RDT) mode is selected and no
additional reduced dead time occurs, the release of the 2nd cycle will be maintained, since it can be assumed
that the opposite end is open.

[lo2awezk-170912-01.tif, 1, en_US]

Figure 6-315 Stage Release for Protection Functions Starting With the 2nd Automatic Reclosing Cycle

6.46.4.11 Dead Time for Operating Modes With Tripping


In the Dead time function block, that dead time which corresponds with the previous trip command is started.
After expiration of the dead time, the automatic reclosing function changes to the status Switch on.
Figure 6-316shows the dead time logic.
There are the following time stages that can be set differently:

• Dead time after 3-pole tripping

• Dead time after evolving fault


Setting the parameter Dead time aft. 3-pole trip to ∞ (= invalid) avoids an automatic reclosing after
3-pole tripping.

31 not for devices with only 3-phase tripping

982 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

As soon as an evolving fault is recognized (see chapter 6.46.4.13 Evolving-Fault Detection During Dead Time),
switching to an automatic reclosing cycle for 3-pole interruption occurs. With the 3-pole cut-off of the
evolving fault, a separate adjustable dead time for the evolving fault begins. The total dead time is composed
of the part of the dead time that expired until the evolving fault was stopped for the first disruption plus the
dead time for the evolving fault. With the setting of the parameter Dead time aft. evolv. fault to ∞
(= invalid), no other automatic reclosing cycle is executed after tripping by the evolving fault. The tripping
through evolving faults is then finished.

[lopausjk-021212-01.tif, 1, en_US]

Figure 6-316 Cyclic Automatic Reclosing Function - Logic of the Dead Time for the Operating Modes: With
Tripping

6.46.4.12 Dead Time for Operating Modes with Pickup


In the dead time function block, the dead time corresponding to the type of short circuit that led to the trip
command is started. The automatic reclosing operating modes with pickup are only ideal for applications with
3-pole tripping. After expiration of the dead time, the automatic reclosing function changes to the status
Switch on. Figure 6-317 shows the dead time logic.
There are 4 time stages that can be set differently:

• Dead time after 1-phase short circuits

• Dead time after 2-phase short circuits

• Dead time after 3-phase short circuits

• Dead time for evolving faults

SIPROTEC 5, 7SJ82/7SJ85, Manual 983


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

In this way, setting the parameter Dead time aft.1ph. pickup to invalid avoids an automatic
reclosing after 3-pole tripping due to 1-phase short circuits. This also applies to Dead time aft.2ph.
pickup and Dead time aft.3ph. pickup .
As soon as an evolving fault is recognized (see chapter 6.46.4.13 Evolving-Fault Detection During Dead Time),
a separate dead time for faults begins with the stopping of the fault. The total dead time is composed of the
part of the dead time that expired until the evolving fault was stopped for the 1st disruption plus the dead
time for the evolving fault. With the setting of the Dead time aft. evolv. fault to invalid, no
other automatic reclosing cycle is executed after tripping through the evolving fault. The tripping through
evolving faults is then finished.

[lopauare-010611-01.tif, 1, en_US]

Figure 6-317 Cyclic Automatic Reclosing Function - Logic of the Dead Time for the Operating Modes: With
Pickup

6.46.4.13 Evolving-Fault Detection During Dead Time


Evolving faults are short circuits, which occur after switching off a short circuit during dead time. This may be
the case during 1-pole tripping and there is a short circuit in the non-switched conductors after this.
After 3-pole tripping there may also be evolving faults if the line is fed through a second (non-3-pole) opened
circuit breaker, for example, for systems with a 1 1/2 circuit breaker layout.

984 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

The evolving-fault detection is divided into components:

• Detection of Evolving Faults

• Evolving-Faults Processing

• 3-pole circuit-breaker intertripping during evolving faults


The procedure during evolving faults is illustrated in Figure 6-318.

Detection of Evolving Faults


For the detection of an evolving fault, the following criteria can be selected through parameters:

• Parameter Evolving-fault detection = with trip


For this setting, any tripping during the dead time leads to evolving-fault detection. At any tripping it is
decided if an internal protection function is tripped or if the tripping is signaled through a binary input.
Thus, it does not matter if the tripping-protection function is configured for the start of the Automatic
reclosing function or not.

• Parameter Evolving-fault detection = with pickup


Evolving faults are detected if during the dead time a protection function configured for the Automatic
reclosing function start is picked up or if an external pickup is recognized through a binary input.

• Binary input >Evolving fault start


The evolving-fault detection can also be introduced through a binary input without an internal protection
pickup being available.

Reaction to Evolving Faults


After a recognized evolving fault, the Automatic reclosing function can be influenced in 2 ways.

• Parameter Response to evolv. faults = blocks 79


As soon as an evolving fault is recognized, the reclosing function will be blocked. There are no other
reclosing attempts and the Automatic reclosing function is blocked until the pickup and operate indica-
tions causing the evolving fault disappear.

• Parameter Response to evolv. faults = strt. evol.flt.dead time


As soon as an evolving fault is recognized, an automatic reclosing cycle for 3-pole interruption is
switched to. The Automatic reclosing function does not allow any 1-pole tripping until the fault is solved
or there is a final switch off; thus, every following trip command will be 3-pole. When the evolving fault is
fixed, the separate dead time for faults will start, see also chapter Dead time. The further process is as by
3-pole cycles.

[dwbspffe-100611-01.tif, 1, en_US]

Figure 6-318 Cyclic Automatic Reclosing Function - Example for an Evolving Fault

For tripping through evolving faults, the entire dead time consists of the part of the dead time expired until
disconnecting the evolving fault for the 1-pole interruption plus the dead time for the fault together, see
Figure 6-319.
The dead time for evolving faults is started with the return of the operate indication or with the opening of all
3 circuit-breaker poles, provided the circuit-breaker auxiliary contacts are connected.

SIPROTEC 5, 7SJ82/7SJ85, Manual 985


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[lofolsjk-021212-01.tif, 1, en_US]

Figure 6-319 Cyclic Automatic Reclosing Function - Logic of Evolving-Fault Detection

6.46.4.14 Closing Indication and Close Command


After the expiration of the dead time, the Automatic reclosing function is in the closing state.
The closing state can depend on the following influences, see Figure 6-320:

• Through a synchrocheck if the circuit breaker was opened during the 3-pole dead time

• Through the readiness of the circuit breaker signaled through the binary input

• Through a binary input for delaying the close command (>Delay close cmd.)
The Close cmd. indication is a requirement for the assignment of the actual close command to the
circuit breaker.
The mentioned criteria must not be fulfilled directly after expiration of the dead time. If a dead-time prolonga-
tion is set, the mentioned criteria will be checked during the prolongation. With the release of the closing indi-
cation, the Automatic reclosing function switches to the reclaim time state.

986 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[loeinsha-141111-01.tif, 1, en_US]

Figure 6-320 Cyclic Reclosing Function: Logic for the Closing Indication

Testing the Circuit-Breaker Readiness Directly before Closing


For each of the automatic reclosing cycles, you can set if a test of the circuit-breaker readiness should occur
directly before closing (parameter CB ready check bef.close, Figure 6-321). Independent of this, a test
of the circuit-breaker readiness before the start of the 1st automatic reclosing cycle can be set, see
6.46.4.5 Start and chapter 6.46.4.16 Circuit-Breaker Readiness .

SIPROTEC 5, 7SJ82/7SJ85, Manual 987


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[lolsvoei-130511-01.tif, 1, en_US]

Figure 6-321 Cyclic Reclosing Function: Logic for the Query of the Circuit-Breaker Readiness Directly before
Closing

Synchrocheck
For each of the configured automatic reclosing cycles, you can set if a synchrocheck should be executed and
which functionality should be used here, see Figure 6-322. You can use the internal synchrocheck only if the
device is connected to a voltage transformer.
Alternatively, you can also connect an external device with synchrocheck through a binary input.
The measuring request for the synchrocheck is placed if the optional test of the circuit-breaker readiness was
positive. The measuring request for the synchrocheck exists until the synchrocheck assigns the allowance for
the closure. If the allowance is not given within the set maximum dead time extension, the closure will be
cancelled through the blocking of the Automatic reclosing function. The minimum duration of the measuring
request is 50 ms.

[losyncro-130511-01.tif, 1, en_US]

Figure 6-322 Cyclic Reclosing Function: Logic for the Inquiry of the Synchronism

Close Command
As soon as the test of the circuit-breaker readiness and the synchrocheck deliver a positive result, the closing
indication will be created. It will be assigned for 100 ms. The actual close command is not created by the Auto-
matic reclosing function, but rather from the circuit-breaker function block outside of the Automatic reclosing
function. Here the set maximum duration of the close command is also considered.

988 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

In addition to the closing indication, additional indications will be created that describe the type of closure.
These include:

• Close command after 3-pole tripping in the 1st cycle (Cls.cmd after 3p.1.cyc

• Close command after 1-pole or 3-pole tripping starting with the 2nd cycle (CloseCmd >=2nd.cyc)

Creation of the Signal Remote close signal


The cyclic automatic reclosing function can create information Remote close signal. This information
can be transferred to the protection device as a binary signal on the line that is to be protected on the oppo-
site end and processed by the AREC function there in the operating mode Adaptive dead time (ADT). Further-
more, the binary signal may be arranged as information for transmission via an existing protection interface.
The information Remote close signal is generated by the closing logic. It can be delayed by a set time
over the local close indication. With this delay, you can make sure that information is only set if the automatic
reclosing was successful and there was no further tripping. The pulse duration of the inter-close signal has a
fixed length of 500 ms.

6.46.4.15 Reclaim Time


With the assignment of the close command, the automatic reclosing function goes into the reclaim time
state. During this time, it is decided if the current reclosing cycle was successful or not.

• If during the reclaim time no further tripping occurs, the currently running automatic reclosing cycle, and
thus the entire automatic reclosing, was successful.

• If during the reclaim time another tripping occurred, the currently running automatic reclosing cycle was
not successful. If other automatic reclosing cycles are permitted, one of these cycles will be used to
continue the process. If, in contrast, the currently executed cycle was the last permissible cycle, the auto-
matic reclosing process will end and be reported as unsuccessful.
In both cases, the automatic reclosing function switches back to the idle state automatic reclosing function
ready.

Short Circuits during Running Reclaim Time


A trip command that occurs during a reclaim time leads to a cancellation of the reclaim time. If further auto-
matic reclosing cycles are allowed, the regulation of the cycle depends on if the automatic reclosing function
is executed in an operating mode with action times or without action times, see Figure 6-323.

• With operating modes with action time, the action times of all higher cycles are started with the begin-
ning of the new general pickup if these are not blocked. The cycle with the lowest cycle number is
selected, whose action time is not yet expired with the incoming trip indication. If no further cycles are
possible or if the action times of all possible cycles are expired before the operate indication, there will be
no further reclosing.

• With the operating modes without action time, the cycle following the current cycle will always be
selected in the set cycle. If this is blocked, the cycle following this one will be selected, etc. If no higher
cycles exist or if they are all blocked, there will be no further automatic reclosing.

SIPROTEC 5, 7SJ82/7SJ85, Manual 989


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[losperre-140611-01.tif, 1, en_US]

Figure 6-323 Cyclic Reclosing Function: Logic for the reclaim time

6.46.4.16 Circuit-Breaker Readiness


The Automatic reclosing function requires the circuit-breaker readiness for the following purposes, see
Figure 6-324:

• Recognition of the circuit-breaker readiness from the beginning:


In idle state of the Automatic reclosing function, an unavailable circuit breaker leads to the blocking of
the Automatic reclosing function. This monitoring is optional and must be switched off through settings
if the readiness signal is not available for the protection device.

• Analysis of the circuit-breaker readiness directly before the close command:


For each of the configured automatic reclosing cycles, it can be set whether the circuit-breaker readiness
is a requirement for the assignment of the close command. This monitoring is also optional.

990 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[lolsbere-130511-01.tif, 1, en_US]

Figure 6-324 Cyclic Automatic Reclosing: Logic for the Circuit-Breaker Readiness

6.46.4.17 Blockings
The Automatic reclosing function differentiates between 2 types of blockings, see Figure 6-325:

• Static blocking

• Dynamic blocking

Static Blocking
The Automatic reclosing function is statically blocked if the function is switched on, but is not ready for
reclosing and also cannot be started as long as this blocking is present. The dynamic blocking is signaled with
the indication Inactive.
The following conditions lead to the static blocking:
Condition Indication
Manual closing of the circuit breaker, recognition through binary Inactive
input or internal device control.
The blocking is temporary, the duration can be set with the
parameter Block. time aft. man.close.
Circuit breaker not available for automatic reclosing function, Inactive
recognition through binary input. This cause can be switched on
or off through the parameter CB ready check bef.close.
Circuit breaker of non-closed 3-pole, recognition through binary Inactive
input.
This criteria is used if the circuit-breaker auxiliary contacts are
connected.

SIPROTEC 5, 7SJ82/7SJ85, Manual 991


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Condition Indication
No reclosing cycle possible Inactive
Recognition due to the following causes:

• Automatic reclosing cycle is not set.


• Automatic reclosing cycles are set, but all are blocked, for
example, via binary input.
• There is no internal device function and no binary input
configured for starting the automatic reclosing function.
• With operating modes with tripping:
– both 1-pole and 3-pole cycles are blocked via binary
inputs
• With operating modes with pickup:
– 1-phase, 2-phase and 3-phase automatic reclosing
cycles, the blocking is done through binary inputs.
• With operating modes without action time:
– the first automatic reclosing cycle is blocked via binary
input.
• With the dead-line check functionality:
– if the voltage measurement is not available or is
disrupted.

Dynamic Blocking
The automatic reclosing function is blocked dynamically if a blocking condition occurs while an automatic
reclosing function is running. The dynamic blocking is signalized with the indication Not ready.
After the occurrence of a dynamic blocking, it is checked in intervals of 0.5 s to see if the blocking can be
removed. If the blocking condition remains or if a different blocking condition occurs in the meantime, the
blocking will remain. If, in contrast, the cause of the blocking disappears, the dynamic blocking will be
removed if no general pickup or no tripping configured for the automatic reclosing function start is available.
A separate indication for logging exists for each individual blocking cause.
The following conditions lead to the dynamic blocking:
Condition Indication
If no reclosing cycle fitting the fault type is released: Not ready
Block. by no cycle
• With operating modes with tripping:
If a 1-pole or 3-pole operate indication occurs during the
automatic reclosing function start input, however, the auto-
matic reclosing function does not start in accordance with
the parameterization for this type of tripping, the respective
dead time will be set to invalid.
• With operating modes with pickup:
If a 1-phase, 2-phase or 3-phase pickup indication occurs
during the automatic reclosing function starting process,
but the automatic reclosing function may not be started in
accordance with the parameterization for this type of
pickup.
If a protection function causes the automatic reclosing function Not ready
to be blocked in accordance with the configuration Block. by protection

992 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Condition Indication
If the maximum set waiting time for the delay of the start of the Not ready
dead time through the binary input >Dead time start Blk.by max. d.t. delay
delay expires without the binary input becoming inactive
during this time lapse
If the synchrocheck is set and the synchronism conditions after Not ready
the expiration of the maximum dead-time prolongation are not Blk.by max.d.t. expiry
fulfilled before the assignment of the close command
If the inquiry of the circuit-breaker readiness is switched on Not ready
directly before the close command through the parameter and Blk.by CB ready sup.
the maximum dead-time prolongation expires Blk.by max.d.t. expiry
If the closing indication is delayed through the binary input Not ready
>Delay close cmd. for so long until the maximum dead time Blk.by max.d.t. expiry
extension is exceeded before the assignment of the close
command
If an evolving fault occurs and the parameter Response to Not ready
evolv. faults is set to blocks 79 Blk. by evolving fault
If the start-signal supervision time for the operate indication Not ready
starting from the automatic reclosing function or the starting Blk.by strtsig.superv.
binary input expires.
In this case, a circuit-breaker failure is assumed.
If after the start of the automatic reclosing function a dead time Not ready
is already running and a blocking binary input is active, with the Block. by binary input
following binary inputs:
>Blk. 1-pole AR, >Blk. 3-pole AR, >Blk. with 1-ph
pickup, >Blk. with 2-ph pickup, >Blk. with 3-ph pickup
If the maximum number of automatic reclosing attempts is Not ready
reached and there is a trip command within the reclaim time Block. by max. cycles
With operating modes with action time: Not ready
If the action times of all released automatic reclosing cycles Blk.by action time exp
expire without a trip command
For applications with voltage measurement and switched on Not ready
functionalities with dead-line check: Blk.by dead-line check
If during the dead time the required voltage criteria is not
fulfilled
For applications with voltage measurement and switched on Not ready
functionalities with dead-line check: Blk.by loss of voltage
If during a running automatic reclosing cycle a failure of the
measuring voltage is determined.
After the completion of the automatic reclosing cycle, the
dynamic blocking becomes static blocking if there is a continued
failure of the measuring voltage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 993


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[lobloawe-100611-01.tif, 3, en_US]

Figure 6-325 Cyclic Reclosing Function: Blocking Logic in the Example for a 1-Pole Cycle (Static and Dynamic
Blocking)

6.46.4.18 Dead-Line Checking (DLC) and Reduced Dead Time (RDT)


The additional functions Dead-line check (DLC) and Reduced dead time (RDT), are only possible for applica-
tions with a voltage-transformer connection. Another requirement is that the voltage of the line being
switched on can be correctly measured with an open circuit breaker. This is only possible if the voltage trans-
former is aligned on the line-side - seen from the circuit breaker.

994 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Both additional functions DLC and RDT are mutually exclusive, because the DLC checks if the value falls below
a voltage threshold, while the RDT checks if the value exceeds the voltage threshold.
The respectively selected additional function runs in the automatic reclosing state dead time.

Reduced Dead Time (RDT)


With the Reduced dead time, a close command can be assigned before the expiration of the set dead times if
the line to switch on is recognized as fault-free through the measurement of the line voltage.
The voltage measurement occurs with the 3 phase-to-phase-voltages.
In systems with a grounded neutral point, the 3 phase-to-ground voltages are additionally observed.
In systems with compensated or with isolated neutral points, the largest 2 of the 3 phase-to-ground voltages
are additionally considered. Through this, a RDT can also be executed with 1-phase ground connections.
For the approval of the close command with RDT, the following conditions apply:

• The automatic reclosing function is in the state dead time.

• Each measured voltage is above the set threshold values Volt. thres.f. live line/bus
The phase-to-phase voltages are divided by √3 prior to comparing the threshold value. Thus, the phase-
to-ground voltage UN√3 applies as the reference size for the parameterization.

• Exceeding the threshold is fulfilled for the set duration Voltage supervision time.

Dead-Line Check (DLC)


If after switching off a short-circuit the voltage on the switched off line does not disappear, the automatic
reclosing function can be avoided with the dead-line check (DLC).
The voltage measurement occurs with the 3 phase-to-ground voltages.
For the release of the close command with DLC, the following conditions apply:

• The automatic reclosing function is in the state dead time.

• All measured voltages for the set duration Voltage supervision time are below the set threshold
Volt. thres.f. live line/bus.

• The set dead time is expired.


As soon as the voltages fall below the threshold value for the set duration, the allowance for automatic
reclosing with DLC is assigned. This also applies if the values are not below the voltage threshold until the
expiration of the set dead time. In this way, an automatic reclosing is executed if the automatic reclosing func-
tion is first switched to at the end of the protected line and thus, the line is exposed to voltage again.
The automatic reclosing function is blocked by the DLC under the following conditions:

• The automatic reclosing function is in the Closure state, the dead time has expired

• All measured voltages were not simultaneously below the set threshold values Volt.thres. f. dead
line/bus for the set duration Voltage supervision time during the dead time.

SIPROTEC 5, 7SJ82/7SJ85, Manual 995


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[lovrkarc-130511-01.tif, 1, en_US]

Figure 6-326 Cyclic Reclosing Function: Logic for the Functions of Reduced Dead Time and Dead-Line Check

6.46.4.19 Settings

Addr. Parameter C Setting Options Default Setting


General
_:6601:1 General:Mode • off on
• on
• test

996 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Addr. Parameter C Setting Options Default Setting


_:6601:101 General:79 operating • with op., w/o act. time with op., with
mode act. time
• with op., with act. time
• w.pickup, w/o act. time
• w.pickup, w. action time
_:6601:102 General:CB ready check • no no
bef. start
• yes
_:6601:103 General:Reclai. time 0.50 s to 300.00 s 3.00 s
aft.succ.cyc.
_:6601:104 General:Block. time aft. 0.00 s to 300.00 s 1.00 s
man.close
_:6601:105 General:Start signal 0.01 s to 300.00 s 0.13 s
supervis.time
_:6601:106 General:CB ready superv. 0.01 s to 300.00 s 3.00 s
time
_:6601:107 General:3-pole operate • no yes
by 79
• yes
_:6601:108 General:Evolving-fault • with trip with trip
detection
• with pickup
_:6601:109 General:Response to • strt. evol.flt.dead time blocks 79
evolv. faults
• blocks 79
_:6601:110 General:Max. dead-time 0.01 s to 300.00 s 0.50 s
delay
_:6601:111 General:Max. dead-time 0.00 s to 300.00 s; ∞ 1.20 s
extension
_:6601:112 General:Send delay f. 0.00 s to 300.00 s; ∞ ∞
remot. close
DLC, RDT
_:6601:113 General:Dead-line check/ • without without
reduc.d.t
• Reduced dead t. RDT
• Dead-line check DLC
_:6601:114 General:Voltage supervi- 0.10 s to 30.00 s 0.10 s
sion time
_:6601:115 General:Volt. thres.f. live 0.300 V to 340.000 V 48.000 V
line/bus
_:6601:116 General:Volt.thres. f. 0.300 V to 340.000 V 30.000 V
dead line/bus
Cycle 1
_:6571:102 Cycle 1:Start from idle • no yes
state allow.
• yes
_:6571:103 Cycle 1:Action time 0.00 s to 300.00 s; ∞ 0.20 s
_:6571:108 Cycle 1:Dead time aft. 3- 0.00 s to 1800.00 s; ∞ 0.50 s
pole trip
_:6571:107 Cycle 1:Dead time aft. 1- 0.00 s to 1800.00 s; ∞ 1.20 s
pole trip
_:6571:104 Cycle 1:Dead time 0.00 s to 1800.00 s; ∞ 1.20 s
aft.1ph. pickup
_:6571:105 Cycle 1:Dead time 0.00 s to 1800.00 s; ∞ 1.20 s
aft.2ph. pickup

SIPROTEC 5, 7SJ82/7SJ85, Manual 997


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Addr. Parameter C Setting Options Default Setting


_:6571:106 Cycle 1:Dead time 0.00 s to 1800.00 s; ∞ 0.50 s
aft.3ph. pickup
_:6571:109 Cycle 1:Dead time aft. 0.01 s to 1800.00 s 1.20 s
evolv. fault
_:6571:111 Cycle 1:CB ready check • no no
bef.close
• yes
_:6571:110 Cycle 1:Synchroch. aft. • none none
3-pole d.t.
• internal
• external
_:6571:112 Cycle 1:Intern. synchro- Setting options depend on
check with configuration

6.46.4.20 Information List

No. Information Data Class Type


(Type)
General
_:6601:51 General:Mode (controllable) ENC C
_:6601:87 General:>Function off SPS I
_:6601:524 General:>Function on SPS I
_:6601:347 General:Function on SPC C
_:6601:82 General:>Block function SPS I
_:6601:501 General:>Release by ext.sync. SPS I
_:6601:502 General:>Blk. with 1-ph pickup SPS I
_:6601:503 General:>Blk. with 2-ph pickup SPS I
_:6601:504 General:>Blk. with 3-ph pickup SPS I
_:6601:505 General:>Blk. 1-pole AR SPS I
_:6601:506 General:>Blk. 3-pole AR SPS I
_:6601:507 General:>Pickup A for start SPS I
_:6601:508 General:>Pickup B for start SPS I
_:6601:509 General:>Pickup C for start SPS I
_:6601:510 General:>Pickup 1ph for start SPS I
_:6601:511 General:>Pickup 2ph for start SPS I
_:6601:512 General:>Pickup 3ph for start SPS I
_:6601:513 General:>Gen. pickup for start SPS I
_:6601:514 General:>General trip for start SPS I
_:6601:515 General:>Trip pole A for start SPS I
_:6601:516 General:>Trip pole B for start SPS I
_:6601:517 General:>Trip pole C for start SPS I
_:6601:518 General:>Trip 1-pole for start SPS I
_:6601:519 General:>Trip 3-pole for start SPS I
_:6601:520 General:>Evolving fault start SPS I
_:6601:521 General:>Dead time start delay SPS I
_:6601:522 General:>Delay close cmd. SPS I
_:6601:52 General:Behavior ENS O
_:6601:53 General:Health ENS O
_:6601:54 General:Inactive SPS O
_:6601:301 General:79 state ENS O

998 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

No. Information Data Class Type


(Type)
_:6601:302 General:Actual reclose cycle INS O
_:6601:303 General:Not ready SPS O
_:6601:304 General:79 successful SPS O
_:6601:305 General:CB ready superv.expir SPS O
_:6601:306 General:CB is not ready SPS O
_:6601:307 General:79 permits 1-pole trip SPS O
_:6601:308 General:AR only after 1p. trip SPS O
_:6601:309 General:In progress SPS O
_:6601:310 General:Reclaim time running SPS O
_:6601:311 General:Start sig. superv.exp. SPS O
_:6601:313 General:Evolv.-fault detected SPS O
_:6601:314 General:RDT CloseCmd indicat. SPS O
_:6601:315 General:Dead t. aft.1pole trip SPS O
_:6601:316 General:Dead t. aft.3pole trip SPS O
_:6601:317 General:Dead t. aft.1ph pickup SPS O
_:6601:318 General:Dead t. aft.2ph pickup SPS O
_:6601:319 General:Dead t. aft.3ph pickup SPS O
_:6601:320 General:Dead t. aft.evolv.flt. SPS O
_:6601:321 General:Close cmd. indication ACT O
_:6601:322 General:Cls.cmd after 1p.1.cyc SPS O
_:6601:323 General:Cls.cmd after 3p.1.cyc SPS O
_:6601:324 General:CloseCmd >=2nd.cyc SPS O
_:6601:325 General:3-pole operate by 79 SPS O
_:6601:326 General:Remote close signal SPS O
_:6601:327 General:Block. by binary input SPS O
_:6601:328 General:Blk.by CB ready sup. SPS O
_:6601:329 General:Blk.by strtsig.superv. SPS O
_:6601:330 General:Blk.by action time exp SPS O
_:6601:331 General:Blk.by max.d.t. expiry SPS O
_:6601:332 General:Blk.by max. d.t. delay SPS O
_:6601:333 General:Blk. by evolving fault SPS O
_:6601:337 General:Block. by no cycle SPS O
_:6601:338 General:Block. by protection SPS O
_:6601:334 General:Blk.by dead-line check SPS O
_:6601:335 General:Blk.by loss of voltage SPS O
_:6601:336 General:Block. by max. cycles SPS O
_:6601:339 General:Cyc1 1p AR INS O
_:6601:340 General:Cyc1 3p AR INS O
_:6601:341 General:Cyc2+ 1p AR INS O
_:6601:342 General:Cyc2+ 3p AR INS O
Cycle 1
_:6571:51 Cycle 1:Mode (controllable) ENC C
_:6571:500 Cycle 1:>Block 79 cycle SPS I
_:6571:52 Cycle 1:Behavior ENS O
_:6571:53 Cycle 1:Health ENS O
_:6571:301 Cycle 1:Cycle running SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 999


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

No. Information Data Class Type


(Type)
_:6571:302 Cycle 1:Stage release prot. SPS O
_:6571:303 Cycle 1:Synchrocheck request SPS O

6.46.5 Automatic Reclosing Function with Adaptive Dead Time (ADT)

6.46.5.1 Description
Description
It is also possible to set the dead times only at one line end and to configure the adaptive dead time at the
other end or ends. The requirements for this is that the voltage transformer aligned on the line side or a possi-
bility to transfer a close command to a remote line end exists.
Figure 6-327 shows an example with a voltage measurement. It is assumed that device I works with defined
dead times, while the adaptive dead time is configured in device II. It is important that the line is at least fed
from busbar A, so from the side with the defined dead times.
With the adaptive dead time, the automatic reclosing function at the line end II decides independently if and
when a reclosing is reasonable and permissible and when it is not. The criteria is the voltage of the line at the
end II, which is switched through after reclosing from end I. The reclosing at end II occurs, as soon as it exists,
so that the line from end I is set back under voltage. Basically, all phase-to-phase and phase-to-ground
voltages are monitored.
With an implied short-circuit, the lines at the positions I, II, and III in the example are switched off. Position I is
switched on again after the dead time set there. At position III the reduced dead time (RDT) can be executed
with the appropriate configuration (see chapter ) if an infeed is also available on busbar B.
If the short circuit has been cleared after successful reclosing, the line A-B from the busbar A will be set under
voltage through the position I. Device II recognizes this voltage and switches on to warrant adequate voltage
measurement time after a short delay The system incident is thus successfully cleared.
If the short circuit is not cleared after closure at position I, I will be switched to the fault again. At line end II,
now no healthy voltage will appear. The device here recognizes this and does not close again.
With multiple reclosing, the process may repeat if the reclosing is unsuccessful until one of the reclosings is
successful or a final disconnection occurs.

[dwarcasp-100611-01.tif, 1, en_US]

Figure 6-327 Example for Adaptive Dead Time (ADT)

As the example shows, the adaptive dead time brings along the following advantages:

• The circuit breaker at position II does not switch off again with a remaining fault and is protected through
this.

• With non-selective tripping by overreach at position III, no further disruption cycles may occur here
because the short-circuit path via busbar B and the position II remains disrupted even with multiple
reclosing.

• At position I, with multiple reclosing and even with a final tripping, an overlapping is allowed, because
the line at position II remains open and thus, no actual overreaching can occur at position I.

1000 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

The adaptive dead time also contains the reduced dead time (RDT), because the criteria are the same. A
special setting of the reduced dead time (RDT) is unnecessary if the automatic reclosing function is used with
adaptive dead time (ADT).

6.46.5.2 Settings

Addr. Parameter C Setting Options Default Setting


General
_:6601:1 General:Mode • off on
• on
• test
_:6601:101 General:79 operating mode • with op., w/o act. time with op., with
act. time
• with op., with act. time
• w.pickup, w/o act. time
• w.pickup, w. action time
_:6601:102 General:CB ready check bef. • no no
start
• yes
_:6601:103 General:Reclai. time 0.50 s to 300.00 s 3.00 s
aft.succ.cyc.
_:6601:104 General:Block. time aft. 0.00 s to 300.00 s 1.00 s
man.close
_:6601:105 General:Start signal 0.01 s to 300.00 s 0.13 s
supervis.time
_:6601:106 General:CB ready superv. 0.01 s to 300.00 s 3.00 s
time
_:6601:107 General:3-pole operate by • no yes
79
• yes
_:6601:111 General:Max. dead-time 0.00 s to 300.00 s; ∞ 1.20 s
extension
_:6601:114 General:Voltage supervi- 0.10 s to 30.00 s 0.10 s
sion time
_:6601:115 General:Volt. thres.f. live 0.300 V to 340.000 V 48.000 V
line/bus
ADT
_:6631:101 ADT:1-pole trip allowed • no no
• yes
_:6631:104 ADT:Action time 0.00 s to 300.00 s; ∞ 0.20 s
_:6631:105 ADT:Maximum dead time 0.50 s to 3000.00 s 5.00 s
_:6631:102 ADT:CB ready check • no no
bef.close
• yes
_:6631:103 ADT:Synchroch. aft. 3-pole • none none
d.t.
• internal
• external
_:6631:106 ADT:Intern. synchrocheck Setting options depend on
with configuration

SIPROTEC 5, 7SJ82/7SJ85, Manual 1001


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

6.46.5.3 Information List

No. Information Data Class Type


(Type)
General
_:6601:51 General:Mode (controllable) ENC C
_:6601:87 General:>Function off SPS I
_:6601:524 General:>Function on SPS I
_:6601:347 General:Function on SPC C
_:6601:82 General:>Block function SPS I
_:6601:501 General:>Release by ext.sync. SPS I
_:6601:502 General:>Blk. with 1-ph pickup SPS I
_:6601:503 General:>Blk. with 2-ph pickup SPS I
_:6601:504 General:>Blk. with 3-ph pickup SPS I
_:6601:505 General:>Blk. 1-pole AR SPS I
_:6601:506 General:>Blk. 3-pole AR SPS I
_:6601:507 General:>Pickup A for start SPS I
_:6601:508 General:>Pickup B for start SPS I
_:6601:509 General:>Pickup C for start SPS I
_:6601:510 General:>Pickup 1ph for start SPS I
_:6601:511 General:>Pickup 2ph for start SPS I
_:6601:512 General:>Pickup 3ph for start SPS I
_:6601:513 General:>Gen. pickup for start SPS I
_:6601:514 General:>General trip for start SPS I
_:6601:515 General:>Trip pole A for start SPS I
_:6601:516 General:>Trip pole B for start SPS I
_:6601:517 General:>Trip pole C for start SPS I
_:6601:518 General:>Trip 1-pole for start SPS I
_:6601:519 General:>Trip 3-pole for start SPS I
_:6601:522 General:>Delay close cmd. SPS I
_:6601:52 General:Behavior ENS O
_:6601:53 General:Health ENS O
_:6601:54 General:Inactive SPS O
_:6601:301 General:79 state ENS O
_:6601:302 General:Actual reclose cycle INS O
_:6601:303 General:Not ready SPS O
_:6601:304 General:79 successful SPS O
_:6601:305 General:CB ready superv.expir SPS O
_:6601:306 General:CB is not ready SPS O
_:6601:307 General:79 permits 1-pole trip SPS O
_:6601:308 General:AR only after 1p. trip SPS O
_:6601:309 General:In progress SPS O
_:6601:310 General:Reclaim time running SPS O
_:6601:311 General:Start sig. superv.exp. SPS O
_:6601:312 General:Max. dead time expired SPS O
_:6601:315 General:Dead t. aft.1pole trip SPS O
_:6601:316 General:Dead t. aft.3pole trip SPS O
_:6601:317 General:Dead t. aft.1ph pickup SPS O
_:6601:318 General:Dead t. aft.2ph pickup SPS O

1002 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

No. Information Data Class Type


(Type)
_:6601:319 General:Dead t. aft.3ph pickup SPS O
_:6601:321 General:Close cmd. indication ACT O
_:6601:322 General:Cls.cmd after 1p.1.cyc SPS O
_:6601:323 General:Cls.cmd after 3p.1.cyc SPS O
_:6601:325 General:3-pole operate by 79 SPS O
_:6601:327 General:Block. by binary input SPS O
_:6601:328 General:Blk.by CB ready sup. SPS O
_:6601:329 General:Blk.by strtsig.superv. SPS O
_:6601:330 General:Blk.by action time exp SPS O
_:6601:331 General:Blk.by max.d.t. expiry SPS O
_:6601:337 General:Block. by no cycle SPS O
_:6601:338 General:Block. by protection SPS O
_:6601:335 General:Blk.by loss of voltage SPS O
_:6601:336 General:Block. by max. cycles SPS O
_:6601:339 General:Cyc1 1p AR INS O
_:6601:340 General:Cyc1 3p AR INS O
ADT
_:6631:51 ADT:Mode (controllable) ENC C
_:6631:501 ADT:>Remote close signal SPS I
_:6631:52 ADT:Behavior ENS O
_:6631:53 ADT:Health ENS O
_:6631:301 ADT:ADT is running SPS O
_:6631:302 ADT:Stage release prot. SPS O
_:6631:303 ADT:Synchrocheck request SPS O

6.46.6 Cooperation with External Automatic Reclosing Function

6.46.6.1 Description
The operation of an external reclosing device with the SIPROTEC protection device occurs through the function
mode Operation with external automatic reclosing function. In this function mode, the SIPROTEC protec-
tion functions create the trip command and the external reclosing device creates the close command.
The following figure shows the interaction of an external reclosing device with the functions of the SIPROTEC
5 device.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1003


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

[loaweext-140212-01.tif, 1, en_US]

Figure 6-328 Connection of an External Automatic Reclosing Function

There are no setting parameters for operation with external automatic reclosing functions. The function
provides exclusively the following described binary inputs. The external reclosing device can thus have an
influence on the effects of the internal protection functions.
The following connection possibilities exist:

• From the external reclosing function, the signal >Release stages can be coupled so that the protec-
tion functions use special stages or zones for release. An example is the release of an overreaching zone
with a distance protection or the non-delayed tripping of an overcurrent protection stage in the 1st
reclosing cycle.

• For applications with 1-pole tripping, the external reclosing can provide the signal >1-pole trip
permitted, based on which the protection functions can switch off the 1-pole circuit breaker.
• For applications with reclosing functions only with 1-pole faults and stage or zone releases through the
reclosing function can the signal >1-pole AR only be connected. The protection functions use this
information to allow the stage or zone release only affect 1-pole faults.

6.46.6.2 Information List

No. Information Data Class Type


(Type)
Ext
_:6661:51 Ext:Mode (controllable) C
_:6661:501 Ext:>Release stages I
_:6661:502 Ext:>1-pole trip permitted I
_:6661:503 Ext:>1-pole AR only I
_:6661:52 Ext:Behavior O
_:6661:53 Ext:Health O
_:6661:54 Ext:Inactive O

1004 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

6.46.7 Application and Setting Notes for General Settings

For the Automatic reclosing function, 3 functions are available in the function library of the device. In each
circuit-breaker function group, a function from the Automatic reclosing function can be used.
Configure one of the 3 following function specifications:

• Cyclic Automatic reclosing function

• Automatic reclosing function with adaptive dead time (ADT)

• Operation with External Automatic Reclosing Function

Starting the Automatic Reclosing Function


The configuration of the interaction between internal protection functions and the Automatic reclosing func-
tion can be set separately for each protection function. The configuration occurs in a matrix view in DIGSI. The
Automatic reclosing function also has the corresponding binary inputs and binary outputs through which the
external protection devices can be connected to the internal Automatic reclosing function.
Configure the starting and blocking condition for the Automatic reclosing function at the position shown in
Figure 6-329 in DIGSI (for example, a protection function group Line is shown here) or route the corre-
sponding binary inputs.

[scdigsia-080311-01.tif, 1, en_US]

Figure 6-329 Configuration of the Protection Functions for Starting and Blocking the Automatic Reclosing
Function in DIGSI

General Settings
If you use the Cyclic automatic reclosing function or Automatic reclosing function with adaptive dead
time (ADT) function, set the following settings under General.
There are no settings for the function Operation with external automatic reclosing function. The control
occurs exclusively through binary inputs and binary outputs.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1005


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Parameter: 79 operating mode

• Default setting (_:6601:101) 79 operating mode = with op., with act. time
With the 79 operating mode parameter, you can determine which start criteria the Automatic reclosing
function works with.
Parameter Value Description
with op., with act. The Automatic reclosing function cycles are dependent on the operate time of
time the protection function(s). The start occurs with all protection function(s) or
protection stages that are configured through the Automatic reclosing function
start matrix.
Siemens generally recommends this setting for applications with 1/3-pole trip-
ping and for applications with 3-pole tripping if a single dead time, independent
of the type of connection working, is required in the Automatic reclosing func-
tion cycle.
You can find detailed information in chapter 6.46.4.1 Operating Modes for
Cyclic Automatic Reclosing Function, in the section Operating Mode 1.
w.pickup, w. action The Automatic reclosing function cycles are dependent on the operate time of
time the protection function(s) and the type of fault. The start occurs with all protec-
tion function(s) or protection stages that are configured through the Automatic
reclosing function start matrix.
For applications with 3-pole tripping and dead time dependent on the circuit
type, Siemens recommends this setting.
You can find detailed information in chapter 6.46.4.1 Operating Modes for
Cyclic Automatic Reclosing Function, in the section Operating Mode 2
with op., w/o act. Each operate indication starts the Automatic reclosing function. The start
time occurs with all protection function(s) or protection stages that are configured
through the Automatic reclosing function start matrix.
The Automatic reclosing function start must be configured so that it only occurs
from the protection stages/zones for which an Automatic reclosing should
occur after tripping.
You can find detailed information in chapter 6.46.4.1 Operating Modes for
Cyclic Automatic Reclosing Function, in the section Operating Mode 3
w.pickup, w/o act. Each operate indication starts the Automatic reclosing function. The Automatic
time reclosing function cycles are dependent on the type of fault. The start occurs
with all protection function(s) or protection stages that are configured through
the Automatic reclosing function start matrix.
The Automatic reclosing function start must be configured so that it only occurs
from the protection stages/zones for which an Automatic reclosing should
occur after tripping.
You can find detailed information in chapter 6.46.4.1 Operating Modes for
Cyclic Automatic Reclosing Function, in the section Operating Mode 4

Parameter: CB ready check bef. start

• Default setting (_:6601:102) CB ready check bef. start = no


With the CB ready check bef. start parameter, you can determine if the readiness of the circuit
breaker should be tested before starting the Automatic reclosing function.
Additionally or alternatively, it is possible to check the readiness of the circuit breaker after the expiration of
the dead time, directly before the assignment of the close command. There is another parameter described in
chapter 6.46.8 Application and Setting Notes for 1 Cycle of the Cyclic Automatic Reclosing Function for this
function.

1006 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Parameter Value Description


yes The Automatic reclosing function checks the readiness of the circuit breaker for
a switching cycle, consisting of a tripping-reclosing-switching.
If the circuit breaker is ready - signaled through a binary input - the startup of
the Automatic reclosing function can occur. If the circuit breaker is not ready,
the Automatic reclosing function reports the static blocking.
Siemens recommends using this setting.
Note: The default setting of this parameter does not correspond to the recom-
mended setting value for operation. The Automatic reclosing function would
otherwise be blocked with a non-available circuit breaker-ready-signal. Please
set the parameter as recommended.
no The readiness of the circuit breaker is not checked before starting the Auto-
matic reclosing function. The test also does not occur if the readiness signal
from the circuit breaker is connected to a binary input on the device.

Parameter: Reclai. time aft.succ.cyc.

• Default setting (_:6601:103) Reclai. time aft.succ.cyc. = 3.00 s


With the Reclai. time aft.succ.cyc. parameter, you can decide if the currently running reclosing
cycle was successful or not. You can find more detailed information on the function of the reclaim time in
chapter 6.46.4.15 Reclaim Time.
The default setting for the reclaim time can be frequently maintained. In regions where thunderstorms and
storms often occur, a shorter reclaim time makes sense in order to minimize the danger of the final disconnec-
tion due to sequential lightning strikes or cable spark over.
Select a long reclaim time if there is no possibility for circuit-breaker supervision with multiple automatic
reclosing, for example, due to missing auxiliary contacts or lacking circuit-breaker-ready-information. In this
case, the reclaim time must be longer than the recovery time of the circuit breaker.

Parameter: Block. time aft. man.close

• Default setting (_:6601:104) Block. time aft. man.close = 1.00 s


With the Block. time aft. man.close parameter, the time is determined for which the automatic
reclosing should be blocked after a manual connection.
Set the time so that the circuit breaker can be safely switched on and off during connection to a short circuit
without the Automatic reclosing function being automatically closed.

Parameter: Start signal supervis.time

• Default setting (_:6601:105) Start signal supervis.time = 0.25 s


With the Start signal supervis.time parameter, set the maximum time after which a circuit breaker
must be opened after a trip command. If the time expires, a failure of the circuit breaker is assumed and the
Automatic reclosing function is dynamically blocked.
You can find detailed information about the start supervision time function in chapter 6.46.4.5 Start.

NOTE

i With the use of an internal or external circuit-breaker failure protection at the same line branch, observe
the following:
The start supervision time should be the same as the circuit-breaker failure protection time delay. With this,
you can make sure that in the case of a circuit-breaker failure followed by the tripping of the busbar, no
Automatic reclosing will be executed.
(Note: An exception to this recommendation is described below.)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1007


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Parameter: CB ready superv. time


The setting of this parameter is only important if the cycle-specific parameter CB ready check bef.close
is set to yes. Otherwise, this parameter has no effect.

• Default setting (_:6601:106) CB ready superv. time = 3.00 s


With the CB ready superv. time parameter, you can determine after which maximum time after the trip-
ping the circuit breaker must be ready for the reclosing function.
Set the time somewhat longer than the regeneration time of the circuit breaker after an OFF-ON-OFF cycle.
You can find detailed information on this function in the chapters 6.46.4.16 Circuit-Breaker Readiness and
6.46.4.14 Closing Indication and Close Command.

Parameter: Evolving-fault detection


This parameter is not important and cannot be set if you use the ADT function (Automatic reclosing function
with adaptive dead time).

• Default setting (_:6601:108) Evolving-fault detection = with trip


With the Evolving-fault detection parameter, you can determine which criteria is used to recognize an
evolving fault. The actual effect of the recognized evolving fault on the Automatic reclosing function can be
set with the parameter described below Response to evolv. faults.
Evolving faults are short circuits, which occur after switching off a short circuit during dead time.
You can find detailed information about evolving-fault detection in chapter 6.46.4.13 Evolving-Fault Detec-
tion During Dead Time.
Parameter Value Description
with trip Evolving faults are recognized if an operate indication occurs during the dead
time. Thus, it does not matter if the tripping-protection function is configured
for the start of the Automatic reclosing function or not.
The pickup of a protection function without an operate indication does not lead
to evolving-fault detection.
with pickup Evolving faults are detected if during the dead time a protection function
configured for the Automatic reclosing function start is picked up or if an
external pickup is detected through a binary input.

For applications with 1-/3-pole tripping, Siemens recommends the setting with trip if the system is
adequately interconnected.
If multiple individual lines in a row form a total transmission path, the setting with pickup may be better
suitable. With this setting, you can prevent 2 lines following each other from switching to 1-pole in different
conductors during evolving faults. The consequence of this fault would be the remainder of a single conductor
in the dead time for the overall transmission path. This is particularly important if power plants are coupled
through the overall transmission path.

Parameter: Response to evolv. faults


This parameter is not important and cannot be set if you use the ADT function (Automatic reclosing function
with adaptive dead time).

• Default setting (_:6601:109) Response to evolv. faults = blocks 79


With the Response to evolv. faults parameter, you can determine how the Automatic reclosing func-
tion reacts to recognized faults.
You can find detailed information about the Automatic reclosing function for faults in chapter
6.46.4.13 Evolving-Fault Detection During Dead Time.

1008 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Parameter Value Description


blocks 79 The Automatic reclosing function is immediately blocked until the disconnec-
tion of the fault.
For blockings through faults during the 1-pole dead times, you can force a 3-
pole trip command through the Automatic reclosing function if the you set the
parameter 3-pole operate by 79 to yes.
strt. evol.flt.dead After the 3-pole trip command to clear up the fault, the Automatic reclosing
time function starts a new 3-pole Automatic reclosing function cycle with the set
Dead time aft. evolv. fault.

Parameter: Max. dead-time delay


This parameter is not important and cannot be set if you use the ADT function (Automatic reclosing function
with adaptive dead time).

• Default setting (_:6601:110) Max. dead-time delay = 0.5 s


With the Max. dead-time delay parameter, you determine at which time the starting of the dead time
may be delayed before the Automatic reclosing function is dynamically blocked.
The delay of the start of the dead time is possible with the binary input >Dead time start delay.
You can find detailed information about the functionality in chapter 6.46.4.5 Start.

Parameter: Max. dead-time extension

• Default setting (_:6601:111) Max. dead-time extension = 1.2 s


With the Max. dead-time extension parameter, you determine the time by which the dead time may be
extended before the Automatic reclosing function is dynamically blocked.
With the setting oo (invalid), the extension is unlimited.
An extension of the dead time can be required under the following conditions:

• Waiting for the readiness of the circuit breaker

• Inquiry of a synchronous test

• Delay through binary input in order e.g. to give the leading Automatic reclosing function priority in a
system with 1 1/2 circuit breaker layout.
Remember that longer dead times after 3-pole disconnection are only permissible if no stability problems
occur or if a synchronous test occurs before the reclosing.
You can find detailed information about the functionality in chapter 6.46.4.14 Closing Indication and Close
Command.

Parameter: Voltage supervision time


This parameter is only important if you use the subfunctions RDT, DLC, or the ADT function. If you do not use
any of these functions, the setting of this parameter is free to select.

• Default setting (_:6601:114) Voltage supervision time = 0.1 s


With the Voltage supervision time parameter, you can determine the measuring time that is available
as a criteria for the voltage decision. It should be longer than all transient oscillations through switching oper-
ations.
For the subfunctions Reduced dead time and Reclosing function with adaptive dead time, this measuring
time applies for the determination of the surpassing of a voltage threshold. For the subfunction Dead-line
check, the surpassing of a voltage threshold is checked.
Siemens recommends the setting 0.10 s.
You can find detailed information on the functionality in the following parameters, and in the chapters
6.46.4.18 Dead-Line Checking (DLC) and Reduced Dead Time (RDT) and 6.46.5.1 Description.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1009


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Parameter: Volt. thres.f. live line/bus


This parameter is only important if you use the subfunction RDT or the function ADT. If you do not use any of
these functions, the setting of this parameter is free to select.

• Default setting (_:6601:115) Volt. thres.f. live line/bus = 48 V


With the Volt. thres.f. live line/bus parameter, you can determine the limit voltage above which
the line should be seen as fault-free. It must be lower than the smallest expected operating voltage. The
phase-to-ground voltage applies as the reference value.
You can find detailed information on the functionality in the following parameters and in the chapters
6.46.4.18 Dead-Line Checking (DLC) and Reduced Dead Time (RDT) and 6.46.5.1 Description.

Parameter: Dead-line check/reduc.d.t


This parameter is not important and cannot be set if you use the ADT function (Automatic reclosing function
with adaptive dead time).

• Default setting (_:6601:113) Dead-line check/reduc.d.t = without


With the Dead-line check/reduc.d.t parameter, you can determine if the Automatic reclosing function
should work with one of the additional functions Dead-line check DLC or Reduced dead t. RDT.
Parameter Value Description
without The Automatic reclosing function occurs after the expiration of the parameter-
ized dead times. DLC or RDT are not activated.
Reduced dead t. RDT The Automatic reclosing function works with a reduced dead time (RDT).
Dead-line check DLC The Automatic reclosing functions works with dead-line check. The closing indi-
cation is only assigned if the line was really de-energized during the dead time.

You can find detailed information about the functionality in chapter 6.46.4.18 Dead-Line Checking (DLC) and
Reduced Dead Time (RDT).

NOTE

i Use RDT or DLC only if the voltages of the line can be correctly measured with an open circuit breaker. This
is only possible if the voltage transformer is aligned on the line-side - seen from the circuit breaker.

Parameter: Volt.thres. f. dead line/bus


This parameter is only important if you use the Dead-line check subfunction. If you do not use any of this
subfunction, the setting value of this parameter is free to select.

• Default setting (_:6601:116) Volt.thres. f. dead line/bus = 30 V


With the Volt.thres. f. dead line/bus parameter, you can determine the limit voltage below which
the line should be seen with certainty as idle or switched off. The threshold value is used by the Dead-line
check subfunction (dead-line check). The reference size is the phase-to-ground voltage.
You can find detailed information about the functionality in chapter 6.46.4.18 Dead-Line Checking (DLC) and
Reduced Dead Time (RDT).

Parameter: Send delay f. remot. close


With the Send delay f. remot. close parameter, you can determine after which time after the Auto-
matic reclosing function the information is sent to the remote closing.

• Default setting (_:6601:112) Send delay f. remot. close = oo (invalid)


The transmission delay prevents the device operating in the adaptive dead time mode on the opposite side
from closing unnecessarily if the local reclosing function remains unsuccessful. On the other hand, it must be
remembered that the line is not available for transporting energy as long as the opposite end is also closed.
Thus, the Send delay f. remot. closemust be added to the dead time in order to determine the
system stability.

1010 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

You can find detailed information about this functionality in chapter 6.46.4.14 Closing Indication and Close
Command.

6.46.8 Application and Setting Notes for 1 Cycle of the Cyclic Automatic Reclosing
Function

For the function of the cyclic automatic reclosing function, 1 cycle is preset. The preset cycle cannot be
deleted. You can add and delete more cycles from the function library in DIGSI 5.

Parameter: Start from idle state allow.


This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode with action time.

• Default setting (_:6571:102) Start from idle state allow. = yes


With the parameter Start from idle state allow. you can determine whether the action time of this
automatic reclosing cycle is started, if the automatic reclosing function is in idle state during with incoming
general pickup. Please set the parameter always to yes , if the automatic reclosing function is configured for
only 1 cycle. If several cycles are configured, you can control the effectiveness of the automatic reclosing
cycles with this parameter and various action times.
Detailed information about the functionality can be found in Chapters 6.46.4.6 Cycle Control with Operating
Mode 1: With Tripping/With Action Time und 6.46.4.7 Cycle Control with Operating Mode 2: With Pickup/With
Action Time.

Parameter: Action time


This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode with action time.

• Default setting (_:6571:103) Action time = 0.2 s


With this parameter Action time you can determine, within which time frame the trip command must
appear, in order to start the automatic reclosing function. If the trip command occurs only after the action
time has expired, automatic reclosing does not occur within the active automatic reclosing cycle.
You can find detailed information about the functionality in
Chapters 6.46.4.6 Cycle Control with Operating Mode 1: With Tripping/With Action Time and 6.46.4.7 Cycle
Control with Operating Mode 2: With Pickup/With Action Time.

Parameter: Dead time aft. 3-pole trip


This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode with tripping.

• Default setting (_:6571:108) Dead time aft. 3-pole trip = 0.5 s


With this parameter Dead time aft. 3-pole trip , you can determine after which dead time the auto-
matic reclosing function will be executed. After a 3-pole trip of the circuit breaker, the system stability is
priority. Since the switched off line cannot develop synchronizing forces, only a short dead time is permitted in
most cases. The usual duration is 0.3 s to 0.6 s. A longer period can be tolerated if a synchrocheck is carried
out prior to reclosing. Longer 3-pole dead times are also possible in radial systems.

Parameter: Dead time aft.1ph. pickup, Dead time aft.2ph. pickup, Dead time aft.3ph. pickup
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode with pickup.

• Default setting (_:6571:104) Dead time aft.1ph. pickup = 1.2 s

• Default setting (_:6571:105) Dead time aft.2ph. pickup = 1.2 s

• Default setting (_:6571:106) Dead time aft.3ph. pickup = 0.5 s

SIPROTEC 5, 7SJ82/7SJ85, Manual 1011


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

With the 3 dead-time parameters, you can determine after which dead time the automatic reclosing function
will be executed. Please set the times as desired for the respective type of short circuit.

• The parameter Dead time aft.1ph. pickup applies to dead times after 1-phase short circuits and
the following protection tripping: A, B, C, or A-Gnd, B-Gnd, C-Gnd

• The parameter Dead time aft.2ph. pickup applies to dead times after 2-phase short circuits and
the following protection tripping: A-B, B-C, C-A, or A-B-gnd, B-C-gnd, C-A-gnd

• The parameter Dead time aft.3ph. pickup applies to dead times after 3-phase short circuits and
the following protection tripping: A-B-C or A-B-C-Gnd

NOTE

i If you would like to avoid automatic reclosing during individual short-circuit types, please set the respective
dead times to oo (invalid).

Example:
After 1-phase short-circuits, the automatic reclosing function should occur after 1.2 s. The automatic reclosing
function should not occur for 2-phase and 3-phase short circuits.
For this application, the parameters should be set as follows:

• Dead time aft.1ph. pickup = 1.2 s

• Dead time aft.2ph. pickup = oo (invalid)

• Dead time aft.3ph. pickup = oo (invalid)

Parameter: Dead time aft. evolv. fault


These parameters are only significant if the parameter (_:6601:109) Response to evolv. faults is
set to strt. evol.flt.dead time .

• Default setting (_:6571:109) Dead time aft. evolv. fault = 1.2 s


With the parameter Dead time aft. evolv. fault , you can determine after which dead time the auto-
matic reclosing function should be executed, if based on an evolving fault during the current dead time, a 3-
pole trip has occurred. For this 3-pole dead time, stability concerns for the system are also important. Often,
this dead time as well as the parameter (_:6571:108) Dead time aft. 3-pole trip can be set.
Detailed information about the function during evolving faults during dead time are described in Chapter
6.46.4.13 Evolving-Fault Detection During Dead Time.

Parameter: CB ready check bef.close

• Default setting (_:6571:111) CB ready check bef.close = no


With the parameter CB ready check bef.close you can determine if after the expiration of the dead
time (meaning, directly prior to assigning the close command) readiness of the circuit breaker should be
queried.

1012 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.46 Automatic Reclosing Function

Parameter Value Description


no With the setting no , the automatic reclosing function does not check again
the readiness of the circuit breaker prior to assigning the close demand.
Siemens recommends this setting, if it is sufficient to check the readiness of the
circuit breaker for the entire switching cycle once before the start of a reclosing
function, consisting of tripping-reclosing-tripping. The setting for checking the
readiness of the circuit breaker prior to the start of the automatic reclosing
function is done using the parameter (_:6601:102) CB ready check
bef. start .
yes With the setting yes , the dead time can be extended if after the expiration of
the dead time the circuit breaker is not ready for the next ON-OFF cycle. The
maximum delay of the dead time can be set with the parameter
(_:6601:111) Max. dead-time extension .
Siemens recommends this setting, if it can be assumed that the circuit breaker
becomes available to switch on the reclosing function only after an additional
waiting period.

Detailed information about the function can be found in Chapters 6.46.4.16 Circuit-Breaker Readiness and
6.46.4.14 Closing Indication and Close Command.

Parameter: Synchroch. aft. 3-pole d.t.

• Default setting (_:6571:110) Synchroch. aft. 3-pole d.t. = none


With the parameter Synchroch. aft. 3-pole d.t. you can determine if a synchrocheck must be
carried out for the configured automatic reclosing cycle.
If during a 3-pole interruption in the system stability problems may be a concern, the synchrocheck should be
carried out. If only 1-pole reclosure cycles are possible or stability problems are not to be expected during the
3-pole dead time, for example, due to a highly intermeshed system or radial system, please select the param-
eter none .
Parameter Value Description
none During the automatic reclosing cycle a synchrocheck is not executed.
internal In the configured automatic reclosing cycle, a synchrocheck is executed after a
3-pole dead time prior to the close command of the circuit breaker.
For the synchrocheck a synchrocheck stage of the internal synchronization
function is used, which is contained in the same function group as the circuit
breaker and the automatic reclosing function. The selection of the synchro-
check stage that is used in the automatic reclosing cycle occurs through the
following described parameter Internal synchrocheck.
external In the configured automatic reclosing cycle, a synchrocheck is executed after a
3-pole dead time prior to the close command of the circuit breaker.
An external synchrocheck device initiates the synchrocheck. The external
synchrocheck device is connected with the binary signals Synchrocheck
request and >Release by ext.sync. . Detailed information about the
function can be found in Chapter 6.46.4.14 Closing Indication and Close
Command under the section Synchrocheck.

Parameter: Internal Synchrocheck


These parameters are only significant if the previously described parameter (_:6571:110) Synchroch.
aft. 3-pole d.t. is set to internal .
With the parameter Internal Synchrocheck, you can determine which function block of the synchroniza-
tion function for the automatic reclosing function is used after a 3-pole dead time. This selection is only
possible for function blocks of the synchronization function, and which are included in the same circuit-
breaker function group as the automatic reclosing function. The setting options of the parameter will be
generated dynamically, according to the actual parameterization.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1013


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

6.47 Fault Locator

6.47.1 Overview of Functions

The Fault locator function is used to determine the distance to the fault location.
Quick determination of fault location and the associated rapid troubleshooting increase the availability of the
line for the power transmission in the electrical power system. Fault-location determination is based on the
determination of the reactance of the short-circuited measuring loops.

6.47.2 Structure of the Function

The Fault locator function can be used in protection function groups with 3-phase current and voltage meas-
urement.

[dwstbafo-090812-01.tif, 1, en_US]

Figure 6-330 Structure/Embedding of the Function

The fault location is calculated based on the line parameter. The fault-location determination is always carried
out with going pickup of the short-circuit protection. There is an option to limit the fault-location deter-
mination to cases with tripping (setting value for parameter Start = with operate).
The fault locator can be started as follows:

• Via the phase-segregated binary inputs >Fault detected phs A, >Fault detected phs B and
>Fault detected phs C

• Via the directional overcurrent protection, phases or ground

• Via the overcurrent protection, phases or ground

• Via the non-phase segregated binary input >Flt. det. w/o phs.&gnd.
If multiple protection functions are operating in parallel, the fault locator is only started by the protection-
function pickup with the highest priority. The functions are listed in decreasing priority.
The Fault locator function only works with the following current and voltage-transformer connection types
(see parameter value).
Parameter Parameter Value
CT connection • 3-phase + IN-separate
• 3-phase + IN
• 3-phase
• 2ph, 2p. CT + 2 IN-sep
VT connection • 3 ph-to-gnd volt. + VN
• 3 ph-to-gnd voltages

1014 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

NOTE

i The Fault locator function does not work with all possible current and voltage transformer connection
types. An error message is displayed in DIGSI 5 if the Fault locator function cannot work with the set
connection types. In this case check the current and voltage transformer connection type. You will find the
CT connection or VT connection parameters in DIGSI 5 under Power system → Meas.point I-3ph or
Power system → Meas.point V-3ph.

6.47.3 Function Description

Starting Conditions
Each protection function that can start the fault locator also provides the fault locator with information on
the pickup and tripping times. If several protection functions pick up at the same time, the fault locator is
started only by the function with the highest priority. The pickup pattern for the other protection functions is
discarded.
The fault locator uses the pickup and tripping information for the protection function being started to form its
own measurand memory for the following calculations. Depending on the pickup duration of the protection
function, the measurand memory is positioned in such a way that it contains prefault processes, short-circuit
processes, and switch-off processes. If the pickup lasts for a longer time, only the short-circuit processes and
switch-off processes are recorded by the measurand memory. The fault-location determination always starts
only after the dropout of the pickup.
Fault-location determination is also possible via the starting condition with going pickup, if the protec-
tion device only picks up and does not trigger. Fault-location determination is performed via the starting
condition with operate only if the protection device has reported the tripping and if the pickup has
dropped out.
Alternatively, the fault locator can be started via one or more binary inputs. If the phase-segregated indica-
tions >Fault detected phs A, >Fault detected phs B, and >Fault detected phs C are routed
in the DIGSI 5 Information routing, the fault locator interprets the binary inputs as a phase-segregated
external protection function and treats them with the highest priority.
If the binary input >Flt. det. w/o phs.&gnd. is routed, the binary input is interpreted as a non-segre-
gated external protection function and is treated with the lowest priority. The fault locator starts when the
binary input drops out.
If with operate is set and the fault locator is started via the binary input, the fault-location determination
is started only if a device-internal protection function generates an operate indication or if the binary input
>Fault locator start is activated.

[sc_rout_BE, 1, en_US]

Figure 6-331 Routing Matrix for the Triggering of the Fault Locator via Binary Input

Determining the Fault Location


The recorded sampled values of the short-circuit currents and voltages are transferred to an own measurand
memory. The pickup indications are used to determine the short-circuited loops. The measurand memory is
searched for an optimal measurement window. The largest possible measurement window is selected. If
possible, the measurement window is positioned at the end of the short-circuit process. This means that the
steady-state process and the decay process have the least possible impact on the measuring result.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1015


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

[dw_sigra_flo, 1, en_US]

Figure 6-332 Determining the Measurement Window

The impedances of the short-circuit loops are calculated using the measurement-window data. If there are
several short-circuited loops, a selection process is used to select a loop and the results are then issued.
If it is not possible to determine a sufficient data window with usable measured values or a plausible short-
circuited loop, the indication FLO invalid signals the invalid measuring result.

Output of the Fault Location


The following results for the fault location are output:

• The fault reactance X in Ω primary

• The fault resistance R in Ω primary

• The fault distance d of the line proportional to the reactance in kilometers or miles, converted on the
basis of the parameterized reactance per unit length of the line

• The fault distance d as a percentage of the line length, calculated on the basis of the parameterized reac-
tance per unit length and the parameterized line length

• The selected fault loop for calculation of the fault location

NOTE

i Specification of distance in kilometers, miles, or percent is relevant only for homogenous line sections. If
the line comprises parts which exhibit different reactances per unit of length (for example, overhead-line-
cable sections), you can then analyze the reactance determined from the fault location for separate calcula-
tion of the fault distance. Alternatively, you can use the Fault locator plus function, with which the non-
homogeneous lines can be parameterized in line sections.

1016 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

Impedance-Based Fault Location


The determination of the fault distance is based on the evaluation of the imaginary part of the calculated
short-circuit impedance. The fault distance is determined by dividing the calculated reactance X with the
parameterizable reactance per unit length (parameter X per length unit). Both the impedance up to the
fault location and the fault distance are issued by the fault locator.
An impedance measuring element is available for each of the 6 possible short-circuit loops A-gnd, B-gnd, C-
gnd, A-B, B-C, C-A. The loop to be measured is selected depending on the fault type.
For 2‑phase short circuits with grounding, the phase-to-phase loop is preferred for fault location. For 3‑phase
short circuits, the average reactance, determined from the reactance of the 3 phase-to-phase loops is used.
A 2-phase short circuit B-C, for example, is used for the calculation of the phase-to-phase loop.

[dw_llschleife_flo, 1, en_US]

Figure 6-333 Short Circuit of a Phase-to-Phase Loop

The loop equation for the calculation of the short-circuit impedance of the phase-to-phase loop B-C is:

[fo_L2-L3_schl, 1, en_US]

where:
VB, VC Short-circuit voltage phasor for phases B and C
IB, IC Short-circuit current phasor phases B and C
m Proportionate distance to the fault
mZL = m ⋅ (RL + jXL) Line impedance up to fault location

The line impedance is calculated as follows:

[fo_R_L2-L3_schl, 1, en_US]

[fo_X_L2-L3_schl, 1, en_US]

In case of a phase-to-ground short circuit, for example, A-gnd, for the calculation of a phase-to-ground loop, it
must be considered that the impedance of the ground-return path does not match the impedance of the
phases.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1017


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

[dw_leschleife_flo, 1, en_US]

Figure 6-334 Short Circuit of a Phase-to-Ground Loop

In case of A-gnd short circuit, the phase-to-ground voltage VA, the phase current IA, and the ground current Ignd
are measured.

[fo_L1-E_schl, 1, en_US]

The impedance to the fault location is calculated as:

[fo_R_L1-E_schl, 1, en_US]

and

[fo_X_L1-E_schl, 1, en_US]

where:
VA Short-circuit voltage phasor
IA Short-circuit current phasor phase A
Ignd Ground-fault current phasor
IR = IA - kr⋅Ignd Auxiliary quantity
Ix = IA - kx⋅Ignd Auxiliary quantity

The factors kr = Rgnd/RL and kx = Xgnd/XL depend only on the line constants and not on the distance to the fault.

Measured-Value Correction at Load Current on Lines Fed on Both Sides


In the case of faults on lines fed on both sides and with load transport and contact resistance (see
Figure 6-335), the fault voltage VA is influenced not only by the voltage source on side A, but also by the
voltage source on side B if both voltage sources feed to the fault location. Without special measures, this leads
to measuring errors in the impedance, since the current portion IB cannot be recorded at measuring point A.
For long and highly loaded lines, this measuring error in the X portion of the fault impedance can be consider-
able. This X component is critical for the distance calculation.
The X component can be corrected when using load compensation. When using load compensation, the calcu-
lated R component comprises the combination of the fault resistance to be determined and the resistance of
the line up to the fault location. This form of impedance calculation corresponds to the distance-protection
measurement protocol using the reactance method. The load compensation impacts both the 1-pole short
circuit and the 2-pole short circuit. You can activate and deactivate the load compensation via the Load
compensation parameter. If the distance protection operates with the reactance method, Siemens recom-
mends switching on the load compensation for the fault locator, too.

1018 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

The following figure serves as an example of the description of the impedance calculation:

[dw ueb impedanzber, 2, en_US]

Figure 6-335 Fault Currents and Voltages of a Line Fed on Both Sides (1-Pole Display)

A Measuring point
VA, VB Voltage source
IA, IB Partial fault currents
IF Total fault current
VA Fault voltage at measuring point A
RF Common fault resistance
Z L, (1-m) ZL Fault impedances
ZA, ZB Source impedances
m Proportionate distance to the fault

Impedance Calculation for Phase-to-Ground Loops


For calculation of a phase-to-ground loop, it must be considered that the impedance of the ground-return
path generally does not match the impedance of the phases. This is the case, for example, for an A-gnd short
circuit.

[dw_leschleife_rmd, 2, en_US]

Figure 6-336 Short Circuit of a Phase-to-Ground Loop

The loop equation for calculating the impedance is:

[fo schl le ohne icomp, 3, en_US]

The loop equation is extended with the equivalent current I Subst. on both sides and converted according to the
impedance.

[fo schl le mit icomp, 4, en_US]

The following applies:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1019


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

[fo x impber, 1, en_US]

The reactance X of the phase-to-ground loop is calculated as follows:

[fo xf impber, 2, en_US]

where:
A Measuring point
VA, Fault voltage at measuring point A (phase-to-ground voltage)
IA, IGnd Partial fault currents
IF Total fault current
RF Common fault resistance
ZL, ZB Line impedance
m Proportionate distance to the fault
ISubst. Equivalent current
k0 Ground-fault factor
δComp Compensation angle

You can select the equivalent current ISubst. in such a way that the impact of the fault current IB is compensated
at the fault resistance RF. This prevents the measuring error in the reactance.
The resulting measuring error in R can be compensated only partially.
R is calculated as follows:

[fo rf impber, 3, en_US]

The protection device cannot measure the fault current IF directly. Therefore, either 3I0 or 3I2 is used as an
equivalent for IF. In order to achieve the best result, the procedure uses the larger one of the 2 equivalent
currents. If the angles of the source impedances and the line impedance are not equal, you can compensate
the inhomogeneity using the compensation angles.
The compensation angles δ comp depend on the network conditions and can be calculated for the zero and
negative-sequence system using the following formulas:

[fo kompwi nullsys impber, 1, en_US]

[fo kompwi gegensys impber, 1, en_US]

where:
ZA,0, ZB,0 Source impedances in the zero-sequence system
ZL,0 Line impedance in the zero-sequence system
m Proportionate distance to the fault

1020 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

δcomp,0 Compensation angle in the zero-sequence system


ZA,2, ZB,2 Source impedances in the negative-sequence system
ZL,2 Line impedance in the negative-sequence system
δcomp,2 Compensation angle in the negative-sequence system

Impedance Calculation for Phase-to-Phase Loops


A 2-phase short circuit B-C is assumed as an example for the calculation:

[dw_llschleife_rmd, 3, en_US]

Figure 6-337 Short Circuit of a Phase-to-Phase Loop

The loop equation for the calculation of the phase-to-phase loop is:

[fo schl ll ohne icomp, 2, en_US]

Thus, X is calculated as follows:

[fo xf impber LLschl, 2, en_US]

Whereby the following applies for the B-C loop: Isubst = (a - a2)⋅I2 and a = e j120°.
The negative-sequence system rotation, which depends on the fault loop, performs the fault-locator algorithm
internally.
R is calculated as follows:

[fo rf impber LLschl, 3, en_US]

6.47.4 Application and Setting Notes

The function requires the following key line data to calculate fault distance:

• Reactance per unit length of the line per kilometer or per mile

• Line length for the correct output of the fault distance as a percentage of the line length

• Residual-compensation factors in the setting format Kr and Kx

Parameter: Start

• Recommended setting value (_:101) Start = with going pickup


The Start parameter is used to define the criterion for starting the fault location.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1021


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

Parameter Value Description


with going pickup If a pickup signal of the protection functions designated for the start has
dropped out, the fault-location determination starts.
with operate If one of the protection functions designated for start has reported the trip-
ping and the pickup has dropped out, the fault-location determination
starts.

As an alternative, the fault locator can be started using external binary input.

Parameter: Load Compensation

• Default setting (_:103) Load compensation = no


With the Load compensation parameter, you can correct measuring errors for 1-phase and 2-phase short
circuits on lines fed on both sides.
Parameter Value Description
no The load compensation does not become effective with this setting.
yes The load compensation becomes effective with this setting.
If you use the load compensation, the following parameters are relevant
and are shown automatically:

• (_:104) Substitute for IF


• (_:106) Comp. angle zero seq.
• (_:107) Comp. angle neg. seq.

Parameter: Substitute for IF

• Default setting (_:104) Substitute for IF = 3I0


The parameter Substitute for IF is only visible and relevant if you use the load compensation.
With the Substitute for IF parameter, for ground-impedance loops, you define which substitute value to
use at the fault location for the fault current IF that cannot be measured due to the fault resistance.
First, calculate the compensation angles for the zero-sequence system and the negative-sequence system. Set
the parameter Substitute for IF according to the smaller compensation angle. The smaller compensa-
tion angle indicates that the associated system (zero-sequence or negative-sequence system) is more homo-
geneous and that the fault current can be approximated in a better way through the fault resistance at the
fault location.

Parameter: Compensation Angle for Zero-Sequence System/Negative-Sequence System

• Default setting (_:106) Comp. angle zero seq. = 0.00°

• Default setting (_:107) Comp. angle neg. seq. = 0.00°


The parameters Comp. angle zero seq. and Comp. angle neg. seq. are only visible and relevant if
you use the load compensation.
If you have determined an angle difference between the measured 3I0 or 3I2 and IF based on network model
tests or calculations, you can compensate this with the parameters Comp. angle zero seq. or Comp.
angle neg. seq..
A setting of the compensation angle deviating from 0 is only relevant for non-homogeneous systems.
With the Comp. angle zero seq. parameter, you compensate the angle difference between the 3I0 calcu-
lated by the device and the fault current IF.
With the Comp. angle neg. seq. parameter, you compensate the angle difference between the 3I2 calcu-
lated by the device and the fault current IF.

Parameter: X per length unit

• Default setting (_:113) X per length unit = 0.210 Ω/km

1022 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

With the X per length unit parameter, you set the reactance per unit length for the line to be protected.
You set the X per length unit parameter as a relative value in Ω/km or Ω/miles.

Parameter: Line length

• Default setting (_:114) Line length = 60 km


With the Line length parameter, you can set the length of the line to be protected as a unit of length in km
or miles.

Parameter: Line angle

• Default setting (_:108) Line angle = 85.00°


Calculate the setting value for the parameter Line angle from the line constants for the line to be protected
as follows:

[folwinkl-050509-01.tif, 1, en_US]

where:
RL Resistance of the line to be protected
XL Reactance of the line to be protected

EXAMPLE

110-kV overhead line, 150 mm2 with the data


R´1 = 0.19 Ω/km
X´1 = 0.42 Ω/km
You calculate the setting value for the line angle as follows:

[fo tan phi, 1, en_US]

[fo arctan phi, 1, en_US]

Parameter: Kr and Kx

• Default setting (_:104) Kr = 1.00

• Default setting (_:105) Kx = 1.00


The Kr and Kx parameters are used to set the residual compensation factors as scalar values. The Kr and Kx
parameters are relevant for the Fault locator function.
Calculate the setting values for the parameters Kr and Kx from the line data as follows:
Resistance ratio Reactance ratio

where:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1023


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

R0 Zero-sequence system resistance of the line


X0 Zero-sequence system reactance of the line
R1 Positive-sequence system resistance of the line
X1 Positive-sequence system reactance of the line

This data can either be used for the entire line or as length-related values, since the quotients are length-inde-
pendent. You can calculate the data both from the primary values and from the secondary values.

EXAMPLE

110-kV overhead line, 150 mm2 with the data:

R1/s 0.19 Ω/km positive-sequence system resistance


X1/s 0.42 Ω/km positive-sequence system reactance
R0/s 0.53 Ω/km zero-sequence system resistance
X0/s 1.19 Ω/km zero-sequence system reactance
s Line length

You receive the following setting values for the parameters Kr and Kx:

[fo kr, 1, en_US]

[fo kx, 1, en_US]

Parameter: K0 and Angle (K0)

• Default setting K0 = 1.000

• Default setting Angle (K0) = 0.00°

NOTE

i The visibility of the K0 and Angle (K0) parameters depends on the selected setting format of the residual
compensation factors. The parameters K0 and Angle (K0) are only visible if you have set the parameter
Set. format residu. comp. = K0 for the device. The Set. format residu. comp. parameter
can be found in the DIGSI 5 project tree under Name of the device → Parameter → Device settings.

The K0 and Angle (K0) parameters are used to set the complex grounding-resistance factor.
Make sure that the line angle is set correctly because the device needs the line angle for calculation of the
compensation components from the K0 factor. The complex grounding-resistance factor is defined by the
value and the angle. You can calculate the complex grounding-resistance factor from the line data as follows:

[fo K01, 1, en_US]

where:
Z0 (Complex) zero-sequence impedance
Z1 (Complex) positive-sequence impedance

1024 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

This data can either be used for the entire line or as length-related values, since the quotients are length-inde-
pendent. You can calculate the data both from the primary values and from the secondary values.
For overhead lines, you can use the values for the calculation because the angles of the zero-sequence system
and the positive-sequence system differ only slightly. For cables, however, significant angular differences can
occur, as the following example illustrates.

EXAMPLE

110-kV single-conductor liquid-filled cable 3 · 185 mm2 Cu with the data:

Z1/s 0.408 · ej73° Ω/km positive-sequence impedance


Z0/s 0.632 · ej18.4° Ω/km zero-sequence impedance
s Line length

The values for calculation of the grounding-resistance factor K0 are:

[fo1 k0, 1, en_US]

[fo2 k0, 1, en_US]

The setting value of the parameter K0 is calculated from:

[fo3 k0, 1, en_US]

When determining the angle, take note of the quadrant of the result. The following table lists the quadrants
and the angle range obtained from the operational signs of the real and imaginary parts of K0.
Real Part Imaginary Part tan Phi (K0) Quadrant/Range Calculation Method
+ + + I 0° to 90° arc tan (|Im| / |Re|)
+ - - IV -90° to 0° –arc tan (|Im| / |Re|)
- - + III -90° to -180° arc tan (|Im| / |Re|) –180°
- + - II +90° to +180° –arc tan (|Im| / |Re|) +180°

In this example, the following setting value for the Angle (K0) parameter is obtained:

[fo phi K0, 1, en_US]

6.47.5 Settings

Addr. Parameter C Setting Options Default Setting


Fault locator
_:1 Fault locator:Mode • off off
• on
• test

SIPROTEC 5, 7SJ82/7SJ85, Manual 1025


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.47 Fault Locator

Addr. Parameter C Setting Options Default Setting


_:101 Fault locator:Start • with operate with going
pickup
• with going pickup
_:103 Fault locator:Load compen- • no no
sation
• yes
_:113 Fault locator:X per length 1A 0.0001 Ω/km to 9.5000 Ω/km Ω/km
unit 5A 0.0000 Ω/km to 1.9000 Ω/km 0.0000 Ω/km
_:114 Fault locator:Line length 0.10 km to 1000.00 km 60.00 km
_:108 Fault locator:Line angle 10.00 ° to 89.00 ° 85.00 °
_:104 Fault locator:Kr -0.33 to 11.00 1.00
_:105 Fault locator:Kx -0.33 to 11.00 1.00
_:118 Fault locator:K0 0.000 to 11.000 1.000
_:150 Fault locator:Angle (K0) -180.00 ° to 180.00 ° 0.00 °

6.47.6 Information List

No. Information Data Class Type


(Type)
Fault locator
_:54 Fault locator:Inactive SPS O
_:52 Fault locator:Behavior ENS O
_:53 Fault locator:Health ENS O
_:302 Fault locator:Fault resistance prim. MV O
_:303 Fault locator:Fault reactance prim. MV O
_:308 Fault locator:Fault resistance sec. MV O
_:309 Fault locator:Fault reactance sec. MV O
_:304 Fault locator:Fault distance MV O
_:305 Fault locator:Fault distance in % MV O
_:306 Fault locator:Fault loop ENS O
_:307 Fault locator:FLO invalid ENS O

1026 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

6.48 Fault Locator Plus

6.48.1 Overview of Functions

The Fault locator plus function

• Is used for 2-sided measurement of the distance to the fault location

• Also reliably detects the fault location in case of 2-sided infeed, ground faults, and in case of fault resis-
tances

• Can be used for fault-location determination in case of non-homogeneous lines


The Fault locator plus function calculates the fault location with the measured values of both line ends. For
the transmission of the measured values between the line ends, a communication connection via the protec-
tion interface must be available.
If 2-sided fault-location determination is not possible, alternatively, the 1-sided method with a calculation of
the reactance of the short-circuited measurement loops is used.
Fast determination of the fault location and the associated fast fault clearance increase the availability of the
line for power transmission in the electrical power system.

6.48.2 Structure of the Function

The Fault locator plus function can be used in protection function groups with 3-phase current and voltage
measurement.

[dwst fo_double, 1, en_US]

Figure 6-338 Structure/Embedding of the Function

The fault location is calculated based on the line parameters. The fault-location determination is always carried
out with going pickup of the short-circuit protection. As an option, the fault-location determination can
be limited to cases with tripping (setting value of the parameter Start = with operate).
For non-homogeneous lines, for example, cable/overhead line routes, you can configure parameters for sepa-
rate line sections with dedicated line data. You can instantiate a maximum of 9 line sections.
For 2-sided fault-location determination, the measured values of both line ends must be available at each line
end. For this purpose, a SIPROTEC 5 device with a protection interface must be installed at each end of the
area to be protected. The devices exchange their measurands via the protection interface. The measurands are
encrypted in digital telegrams and transmitted via the protection communication. The current and voltage
transformers selectively delimit the protection range.
The 2-sided fault-location determination is not possible with the Fault locator plus function under the
following conditions, for example:

• The fault is not located on the line.

• The devices at the line ends have no protection interface.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1027


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

• The protection communication is disturbed.

• For a 1-sided infeed, a metallic fault occurs.

NOTE

i If 2-sided fault-location determination is not possible, the Fault locator plus function alternatively works
with the 1-sided method for fault-location determination.

[dw_example_WS, 1, en_US]

Figure 6-339 Data Exchange for 2 Devices, Each With Protection Communication

The Fault locator plus can be started as follows:

• Via the phase-segregated binary inputs >Fault detected phs A, >Fault detected phs B, and
>Fault detected phs C

• Via the Directional overcurrent protection, phases or ground

• Via the Overcurrent protection, phases or ground

• Via the non-phase segregated binary input >Flt. det. w/o phs.&gnd.
If several protection functions are working in parallel, the fault locator is only started by the pickup of the
function with the highest priority. The functions are listed in decreasing order of priority.

Connection Types of the Current and Voltage Transformers

NOTE

i The Fault locator plus function does not work with all possible current-transformer and voltage-trans-
former connection types.
If the function cannot work with the set connection type, an error message is displayed in DIGSI 5. In this
case, check the current-transformer and voltage-transformer connection type.
You can find the CT connection or VT connection settings in DIGSI 5 under Power system →
Meas.point I-3ph or System data → Meas.point V-3ph.

The Fault locator plus function only works with the following current-transformer and voltage-transformer
connection types (see parameter value).
Parameter Parameter Value
CT connection • 3-phase + IN-separate
• 3-phase + IN
• 3-phase
VT connection • 3 ph-to-gnd volt. + VN
• 3 ph-to-gnd voltages

1028 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

6.48.3 Function Description

Starting Conditions
Each protection function that can start the fault locator also provides the Fault locator plus with information
on the pickup and tripping times. If several protection functions pick up at the same time, the Fault locator
plus is started only by the function with the highest priority.
The fault locator uses the pickup and tripping information of the protection function being started to form its
own measurand memory for the following calculations. Depending on the pickup duration of the protection
function, the measurand memory is positioned such that it contains prefault processes, short-circuit processes,
and switch-off processes. If the pickup lasts for a longer time, the measurand memory only records the short-
circuit processes and switch-off processes. The fault-location determination always starts only after the
dropout of the pickup.
Via the starting condition with going pickup, the fault-location determination is also possible if the
protection device only picks up and does not trigger. Via the starting condition with operate, the fault-loca-
tion determination is only performed if the protection device has reported the tripping and the pickup has
dropped out.
Alternatively, the Fault locator can be started via one or more binary inputs. If the phase-segregated indica-
tions >Fault detected phs A, >Fault detected phs B, and >Fault detected phs C are routed
in the DIGSI 5 Information routing, the Fault locator interprets the binary inputs as a phase-segregated
external protection function and treats them with the highest priority.
When routing the binary input >Flt. det. w/o phs.&gnd., the binary input is interpreted as a non-
segregated external protection function and is treated with the lowest priority. The fault locator starts when
the binary input drops out.
If the setting with operate is active and the Fault locator is started via the binary input, the fault-location
determination only starts if a device-internal protection function generates an operate indication or if the
binary input >Fault locator start is activated.

[scRang_FOplus, 1, en_US]

Figure 6-340 Routing Matrix for the Triggering of the Fault Locator via Binary Input

Definition of the Line Sections


For non-homogeneous lines, for example, cable/overhead line routes, you can define several line sections and
set the line parameters separately for each line section.

NOTE

i If you have an non-homogeneous line with several line sections, you must enter the line sections in the
device at the opposite end inversely. The function checks the correct parameterization and issues the
inconsistency message (_:2311:310) Line sect. setting err. in case of a fault.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1029


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

EXAMPLE:
The line between line ends A and B consists of the line sections Cable A – overhead line – Cable B. Consider
the following for the parameterization of the function:

• Instantiate 3 line sections in the device at line end A and at line end B respectively and enter the line data
for each section.

• Ensure that you enter the data for the line sections in device B inversely to device A.

[dw def line sections, 1, en_US]

Figure 6-341 Line with 3 Line Sections

Installation Site Definition of the Line Sections


Device A Define the line sections at device A as follows:

• Line section 1: Line data from cable A


• Line section 2: Line data from the overhead line
• Line section 3: Line data from cable B
Device B Define the line sections at device B as follows:

• Line section 1: Line data from cable B


• Line section 2: Line data from the overhead line
• Line section 3: Line data from cable A

You can rename the instantiated line sections.

Algorithm for 2-Sided Fault-Location Determination


For an unbranched line with known current and known voltage on the line ends, the voltage can be calculated
at any position x of the line. The algorithm calculates the voltage of both sides of the line. At the fault location
itself, the voltage calculated from both line ends must match. If both voltage curves are displayed graphically,
their intersection is the position of the fault location dFL. Figure 6-342 illustrates the basic principle of 2-sided
fault-location determination. The algorithm calculates the voltage curves with the measured data of the
protection devices of both line ends A and B. The voltage curve is not linear and is calculated as follows with
the telegraph equation:

[fo telegraph equation line, 1, en_US]

with

Wave propagation constant

Wave impedance

d Distance

1030 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

V, I Measured values on the line ends

[dw fault locator voltage char, 1, en_US]

Figure 6-342 Voltage Curve, Calculated from Both Sides of the Line

with:
1 Voltage curve calculated with the measured values at line end A
2 Voltage curve calculated with the measured values at line end B
dFL Fault location

The algorithm of the 2-sided fault-location determination offers the following advantages compared to the 1-
sided method:

• The correct fault-location determination is also possible with power flow, 2-sided infeed, and fault resis-
tances.

• The algorithm is independent from the zero-sequence system and therefore also from its influencing vari-
ables, such as inductive couplings of parallel lines.

• An inaccurate setting of the residual compensation factors has no influence on the accuracy of the fault
location.

Output of the Fault Location


The following results for the fault location are issued:

• The fault resistance in Ω primary and secondary

• The fault contact resistance in Ω primary and secondary


This value is only issued, if the 2-sided fault-location determination is possible.

• The fault reactance up to the fault location in Ω primary and secondary

• The fault distance d in km or miles

SIPROTEC 5, 7SJ82/7SJ85, Manual 1031


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

• The fault distance d in percentage of the line length

• The number of the line section in which the fault was localized

• The selected fault loop for calculation of the fault location


The indication of distance in kilometers, miles, or percent is also applicable for non-homogeneous line routes
(for example, overhead line cable routes). If you have defined several line sections for an non-homogeneous
line, the Fault locator plus function issues the number of the faulty line section.

NOTE

i If the 2-sided fault-location determination is not possible via the Fault locator plus function, the function
works automatically with the algorithm for the 1-sided fault-location determination.
You can find the description for the 1-sided fault locator in the sections starting at chapter 6.47.1 Overview
of Functions.

6.48.4 Application and Setting Notes

The following line data is relevant for the 2-sided fault-location determination:

• The reactance per unit length of the line per kilometer or per mile

• The line length for the correct output of the fault distance in percent of the line length
The following parameters are only relevant for the 1-sided fault-location determination:

• Load compensation

• The residual compensation factors in the setting format Kr and Kx or K0 and Angle (K0).

NOTE

i load compensation isonly possible with homogeneous lines.


If you define more than one line section and set the parameter Load compensation = yes, DIGSI reports
an inconsistency.

Parameter: Start

• Recommended setting value (_:2311:101) Start = with going pickup


With the Start parameter, you define the criterion for starting the fault location.
Parameter Value Description
with going pickup If a pickup signal of the protection functions designated for the startup has
dropped out, the fault-location determination starts.
with operate If one of the protection functions designated for startup has reported the
tripping and the pickup has dropped out, the fault-location determination
starts.

As an alternative, the fault locator can be started via an external binary input.

Parameter: Load compensation

• Default setting (_:2311:103) Load compensation = no


This parameter is only relevant for the 1-sided fault-location determination.
With the Load compensation parameter, you can correct the measuring error for 1-phase short circuits on
lines fed on both sides. This is the case for overhead lines without grounding cable or in case of unfavorable
grounding conditions of the towers, if high contact resistances can occur in case of 1-phase short circuits.

1032 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

Parameter Value Description


no With this setting, the load compensation is not effective.
yes With this setting, the load compensation is effective.
If you operate using the load compensation, the following parameters are
relevant and are shown automatically:

• Substitute for IF
• Comp. angle zero seq.
• Comp. angle neg. seq.

Parameter: Substitute for IF

• Default setting (_:2311:104) Substitute for IF = 3I0


The parameter Substitute for IF is only visible and relevant if you operate using the load compensation.
With the Substitute for IF parameter, you define which substitute value can be used in ground-impe-
dance loops for the unmeasurable fault current IF and replace it with the fault resistance at the fault location.
First, calculate the compensation angle for the zero-sequence system and the negative-sequence system. Set
the parameter Substitute for IF for the relatively smaller compensation angle. The relatively smaller
compensation angle indicates that the associated system (zero-sequence and negative-sequence system) is
more homogeneous and the fault current can be approximated better through the fault resistance at the fault
location.

Parameter: Compensation Angle for Zero-Sequence System/Negative-Sequence System

• Default setting (_:2311:106) Comp. angle zero seq. = 0.00°

• Default setting (_:2311:107) Comp. angle neg. seq. = 0.00°


The parameters Comp. angle zero seq. and Comp. angle neg. seq. are only visible and relevant if
you operate using load compensation.
If, based on network model tests or calculations, an angle difference between the measured 3I0 or 3I2 and IF
was determined, this can be compensated for with the parameter Comp. angle zero seq. or the param-
eter Comp. angle neg. seq..
A setting of the compensation angle deviating from 0 is only relevant for non-homogeneous systems.
When using the Comp. angle zero seq. parameter, the angle difference between the 3I0 calculated by
the device and the fault current IF is being compensated.
When using the Comp. angle neg. seq. parameter, the angle difference between the 3I2 calculated by
the device and the fault current IF is being compensated.

NOTE

i For non-homogeneous lines, for example, cable/overhead line routes, you can define several line sections
and set the line parameters separately for each line section.
You can find further information on the line parameters in the chapter 6.47.4 Application and Setting
Notes.

Parameter: C1 per length unit

• Default setting (_:16921:112) C1 per length unit = 0.010 μF/km


With the C1 per length unit parameter, you specify the capacitance per unit length in the positive-
sequence system for the line to be protected. You set the C1 per length unit parameter as a relative
value in μF/km or μF/miles. The capacitance per unit length in the positive-sequence system is identical to the
operating capacitance cb´.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1033


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

Parameter: C0 per length unit

• Default setting (_:16921:148) C0 per length unit = 0.010 μF/km


With the C0 per length unit parameter, you specify the capacitance per unit length in the zero-sequence
system for the line to be protected. You set the C0 per length unit parameter as a relative value in
μF/km or μF/miles. The capacitance per unit length in the zero-sequence system is identical to the ground
capacitance cgnd´.

Parameter: X per length unit

• Default setting (_:16921:113) X per length unit = 0.210 Ω/km


With the X per length unit parameter, you set the reactance per unit length for the line to be protected.
You set the X per length unit parameter as a relative value in Ω/km or Ω/miles.

Parameter: Line length

• Default setting (_:16921:114) Line length = 60 km


With the Line length parameter, you can set the length of the line to be protected as a unit of length in km
or miles.

Parameter: Line angle

• Default setting (_:16921:108) Line angle = 85.00°


Calculate the setting value for the parameter Line angle from the line constants for the line to be protected
as follows:

[folwinkl-050509-01.tif, 1, en_US]

where:
RL Resistance of the line to be protected
XL Reactance of the line to be protected

EXAMPLE

110-kV overhead line 150 mm2 with the data


R´1 = 0.19 Ω/km
X´1 = 0.42 Ω/km
You calculate the setting value for the line angle as follows:

[fo tan phi, 1, en_US]

[fo arctan phi, 1, en_US]

Parameter: Kr and Kx

• Default setting (_:16921:104) Kr = 1.00

• Default setting (_:16921:105) Kx = 1.00

1034 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

The Kr and Kx parameters are used to set the residual compensation factors as scalar values. The Kr and Kx
parameters are relevant for the Fault locator function.
Calculate the setting values for the parameters Kr and Kx from the line data as follows:
Resistance ratio Reactance ratio

where:
R0 Zero-sequence system resistance of the line
X0 Zero-sequence system reactance of the line
R1 Positive-sequence system resistance of the line
X1 Positive-sequence system reactance of the line

This data can either be used for the entire line or as length-related values, since the quotients are length-inde-
pendent. You can calculate the data both from the primary values and from the secondary values.

EXAMPLE

110-kV overhead line 150 mm2 with the data:

R1/s 0.19 Ω/km positive-sequence system resistance


X1/s 0.42 Ω/km positive-sequence system reactance
R0/s 0.53 Ω/km zero-sequence system resistance
X0/s 1.19 Ω/km zero-sequence system reactance
s Line length

You receive the following setting values for the parameters Kr and Kx:

[fo kr, 1, en_US]

[fo kx, 1, en_US]

Parameter: K0 and Angle (K0)

• Default setting (_:16921:118) K0 = 1.000

• Default setting (_:16921:150) Angle (K0) = 0.00°

NOTE

i The visibility of the K0 and Angle (K0) parameters depends on the selected setting format of the residual
compensation factors. The parameters K0 and Angle (K0) only become visible after you have set the
parameter Set. format residu. comp. = K0 for the device. You can find the Set. format
residu. comp. parameter in the DIGSI 5 project tree under Name of the device → Settings → Device
settings.

The K0 and Angle (K0) parameters are used to set the complex grounding-resistance factor.
Make sure that the line angle is set correctly because the device needs the line angle for calculation of the
compensation components from the K0 factor. The complex grounding-resistance factor is defined by the

SIPROTEC 5, 7SJ82/7SJ85, Manual 1035


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

absolute value and the angle. You can calculate the complex grounding-resistance factor from the line data as
follows:

[fo K01, 1, en_US]

where:
Z0 (Complex) zero-sequence impedance
Z1 (Complex) positive-sequence impedance

This data can either be used for the entire line or as length-related values, since the quotients are length-inde-
pendent. You can calculate the data both from the primary values and from the secondary values.
For overhead lines, you can use the values for the calculation because the angles of the zero-sequence system
and the positive-sequence system differ only slightly. For cables, however, significant angular differences can
occur, as the following example illustrates.

EXAMPLE

110-kV single-conductor liquid filled cable 3 · 185 mm2 Cu with the data:

Z1/s 0.408 · ej73° Ω/km positive-sequence impedance


Z0/s 0.632 · ej18.4° Ω/km zero-sequence impedance
s Line length

The values for calculation of the grounding-resistance factor K0 are:

[fo1 k0, 1, en_US]

[fo2 k0, 1, en_US]

The setting value of the parameter K0 is calculated from:

[fo3 k0, 1, en_US]

When determining the angle, take note of the quadrant of the result. The following table lists the quadrants
and the angle range obtained from the operational signs of the real and imaginary parts of K0.
Real Part Imaginary Part tan Phi (K0) Quadrant/Range Calculation Method
+ + + I 0° to 90° arc tan (|Im| / |Re|)
+ - - IV -90° to 0° –arc tan (|Im| / |Re|)
- - + III -90° to -180° arc tan (|Im| / |Re|) –180°
- + - II +90° to +180° –arc tan (|Im| / |Re|) +180°

In this example, the following setting value for the Angle (K0) parameter is obtained:

[fo phi K0, 1, en_US]

1036 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

Parameter: Blocking of the auto. recl.

• Default setting Blocking of the auto. recl. = no


With the parameter Blocking of the auto. recl., you can block the automatic restart for faults on
individual line sections for non-homogeneous lines, for example, on cable sections.

NOTE

i The parameter Blocking of the auto. recl. is only visible, if you have instantiated the function
block Blk by FtLc. # in the Automatic reclosing function.

You can find the function block Blk by FtLc. # in the DIGSI 5 library in the FG Circuit breaker → Automatic
reclosing → Blocking by Fault Locator.
Parameter Value Description
no The Fault locator plus function has no impact on the Automatic reclosing
function.
yes The Fault locator plus function blocks the Automatic reclosing function.
The blocking only functions if the function block (FB) Blk by FtLc. # is
instantiated in the Automatic reclosing function. The parameter (_:102)
Min. dead time of blocking is in the FB. Set the parameter Min.
dead time of blocking to the smallest dead time of all instantiated
AREC cycles.

6.48.5 Settings

Addr. Parameter C Setting Options Default Setting


Control
_:2311:1 General:Mode • off off
• on
• test
_:2311:101 General:Start • with operate with going
pickup
• with going pickup
Compensation
_:2311:103 General:Load compensa- • no no
tion
• yes
_:2311:104 General:Substitute for IF • 3I2 3I0
• 3I0
_:2311:106 General:Comp. angle -40.00 ° to 40.00 ° 0.00 °
zero seq.
_:2311:107 General:Comp. angle -40.00 ° to 40.00 ° 0.00 °
neg. seq.
Line data 1
_:16921:112 Line section 1:C1 per 1A 0.000 µF/km to 100000.000 0.010 µF/km
length unit µF/km
5A 0.000 µF/km to 500000.000 0.050 µF/km
µF/km
_:16921:148 Line section 1:C0 per 1A 0.000 µF/km to 100000.000 0.010 µF/km
length unit µF/km
5A 0.000 µF/km to 500000.000 0.050 µF/km
µF/km

SIPROTEC 5, 7SJ82/7SJ85, Manual 1037


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

Addr. Parameter C Setting Options Default Setting


_:16921:113 Line section 1:X per 1A 0.0005 Ω/km to 9.5000 Ω/km 0.0525 Ω/km
length unit 5A 0.0001 Ω/km to 1.9000 Ω/km 0.0105 Ω/km
_:16921:114 Line section 1:Line 0.10 km to 1000.00 km 60.00 km
length
_:16921:108 Line section 1:Line angle 10.00 ° to 89.00 ° 85.00 °
_:16921:104 Line section 1:Kr -0.33 to 11.00 1.00
_:16921:105 Line section 1:Kx -0.33 to 11.00 1.00
_:16921:118 Line section 1:K0 0.000 to 11.000 1.000
_:16921:150 Line section 1:Angle (K0) -180.00 ° to 180.00 ° 1.00 °
_:16921:106 Line section 1:KmR 0.00 to 8.00 1.00
_:16921:107 Line section 1:KmX 0.00 to 8.00 1.00
_:16921:124 Line section 1:Km0 0.000 to 8.000 1.000
_:16921:125 Line section 1:Angle -180.00 ° to 180.00 ° 0.00 °
(Km0)
_:16921:120 Line section 1:Blocking • no no
of the auto. recl.
• yes

Settings in the AWE

Addr. Parameter C Setting Options Default Setting


Blk by FtLc. #
_:102 Blk by FtLc. #:Min. dead 0.00 s to 1800.00 s 0.50 s
time of blocking

6.48.6 Information List

No. Information Data Class Type


(Type)
General
_:2311:81 General:>Block function SPS I
_:2311:501 General:>Fault detected phs A SPS I
_:2311:502 General:>Fault detected phs B SPS I
_:2311:503 General:>Fault detected phs C SPS I
_:2311:504 General:>Fault detected gnd. SPS I
_:2311:505 General:>Flt. det. w/o phs.&gnd. SPS I
_:2311:506 General:>Fault locator start SPS I
_:2311:52 General:Behavior ENS O
_:2311:53 General:Health ENS O
_:2311:54 General:Inactive SPS O
_:2311:302 General:Fault resistance prim. MV O
_:2311:321 General:Fault trans. resis. prim. MV O
_:2311:303 General:Fault reactance prim. MV O
_:2311:308 General:Fault resistance sec. MV O
_:2311:322 General:Fault trans. resis. sec. MV O
_:2311:309 General:Fault reactance sec. MV O
_:2311:304 General:Fault distance MV O
_:2311:305 General:Fault distance in % MV O
_:2311:306 General:Fault loop ENS O

1038 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.48 Fault Locator Plus

No. Information Data Class Type


(Type)
_:2311:307 General:State ENS O
_:2311:310 General:Line sect. setting err. SPS O
Line section 1
_:16921:52 Line section 1:Behavior ENS O
_:16921:53 Line section 1:Health ENS O
_:16921:301 Line section 1:Fault on section SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1039


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

6.49 Temperature Supervision

6.49.1 Overview of Functions

The Temperature supervision function checks the thermal state of:

• Motors

• Generators

• Transformers
In rotating machines, it also checks bearing temperatures for a limit violation.
The temperatures are measured at various locations of the protected object using temperature sensors (RTD =
Resistance Temperature Detector) and are sent to the device via one or more RTD units.
The Temperature supervision function receives its measured temperature values via the RTD unit Ether. or
RTD unit serial functions from the Analog units function group.

6.49.2 Structure of the Function

The Temperature supervision function can work in all protection function groups. A maximum of 48 tempera-
ture supervision locations can operate simultaneously in the Temperature supervision function function.
Each temperature supervision location has 2 threshold stages.

[dwstrtmp-170712-01.tif, 1, en_US]

Figure 6-343 Structure/Embedding of the Function

1040 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

6.49.3 Function Description

Logic

[lotmpsup-170712-01.tif, 2, en_US]

Figure 6-344 Logic Diagram for a Temperature Supervision Location

The Temperature supervision location function block (Location FB) receives a measured temperature value
in °C or °F as an input variable delivered from the temperature sensor function blocks of the Analog units
function group. The Sensor number parameter is used to select the temperature sensor.
2 threshold value decisions can be performed for each measuring point. If the measured temperature value is
greater than or equal to the set threshold values, the stages generate a pickup indication independent of one
another and, after a set tripping time delay, an operate indication.
The indications from the supervision locations remain available for further processing.

NOTE

i The pickup of the stages does not result in fault logging. The operate indications of the stages do not go
into the trip logic of the device.

6.49.4 Application and Setting Notes

If you use an external RTD unit, connect the RTD unit via an interface (Ethernet or serial) to the SIPROTEC 5
device. Observe the setting notes for configuration of the interfaces in chapter Analog Transformer Function
Group Type under 5.6.7.3 Communication with an RTD Unit .

SIPROTEC 5, 7SJ82/7SJ85, Manual 1041


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

Parameter: Sensor location

• Default setting (_:11101:46) Sensor location = Other


You inform the device of the sensor installation location using the Sensor location parameter. Oil,
Ambient, Turn, Bearing and Other are available for selection. The selection is not evaluated in the device,
it only serves an informational purpose in the medium in which the temperature measurement takes place.

Parameter: Sensor number

• Default setting(_:11101:44) sensor number = no function block selected


With the sensor number parameter, you assign a specific sensor whose temperature is to be monitored to
the Location function block. You perform the assignment in DIGSI using a list box that contains all connected
RTD units and their sensors.

Parameter: Threshold stage 1

• Default setting (_:11101:40) Threshold stage 1 = 100°C


With the Threshold stage 1 parameter you establish the temperature value whose exceedance causes a
pickup of the 1st tripping stage.

Parameter: Operate delay of stage 1

• Default setting (_:11101:41) Operate delay of stage 1 = 5 s


With the Operate delay of stage 1 parameter you establish the time the operate indication of the 1st
tripping stage should be delayed after the pickup. This time delay depends on the specific application. If you
set the time delay to ∞ the operate indication is blocked.

Parameter: Threshold stage 2

• Default setting (_:11101:42) Threshold stage 2 = 120°C


With the Threshold stage 2 parameter you establish the temperature value whose exceedance causes a
pickup of the 2nd tripping stage.

Parameter: Operate delay of stage 2

• Default setting (_:11101:43) Operate delay of stage 2 = 0 s


With the Operate delay of stage 2 parameter you establish the time the operate indication of the 2nd
tripping stage should be delayed after the pickup. This time delay depends on the specific application. If you
set the time delay to ∞ the operate indication is blocked.

Temperature Unit
Temperature Unit To change the display and evaluation of measured temperature values from °C to °F, adapt
the DIGSI user default settings accordingly (see 5.6.7.5 Temperature Sensor).

6.49.5 Settings

Addr. Parameter C Setting Options Default Setting


Point 1
_:11101:46 Point 1:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other

1042 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

Addr. Parameter C Setting Options Default Setting


_:11101:1 Point 1:Mode • off off
• on
• test
_:11101:40 Point 1:Threshold stage 1 -50°C to 250°C 100°C
_:11101:41 Point 1:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11101:42 Point 1:Threshold stage 2 -50°C to 250°C 120°C
_:11101:43 Point 1:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11101:44 Point 1:Sensor Setting options depend on config-
uration
Point 2
_:11102:46 Point 2:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11102:1 Point 2:Mode • off off
• on
• test
_:11102:40 Point 2:Threshold stage 1 -50°C to 250°C 100°C
_:11102:41 Point 2:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11102:42 Point 2:Threshold stage 2 -50°C to 250°C 120°C
_:11102:43 Point 2:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11102:44 Point 2:Sensor Setting options depend on config-
uration
Point 3
_:11103:46 Point 3:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11103:1 Point 3:Mode • off off
• on
• test
_:11103:40 Point 3:Threshold stage 1 -50°C to 250°C 100°C
_:11103:41 Point 3:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11103:42 Point 3:Threshold stage 2 -50°C to 250°C 120°C
_:11103:43 Point 3:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11103:44 Point 3:Sensor Setting options depend on config-
uration

SIPROTEC 5, 7SJ82/7SJ85, Manual 1043


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

Addr. Parameter C Setting Options Default Setting


Point 4
_:11104:46 Point 4:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11104:1 Point 4:Mode • off off
• on
• test
_:11104:40 Point 4:Threshold stage 1 -50°C to 250°C 100°C
_:11104:41 Point 4:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11104:42 Point 4:Threshold stage 2 -50°C to 250°C 120°C
_:11104:43 Point 4:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11104:44 Point 4:Sensor Setting options depend on config-
uration
Point 5
_:11105:46 Point 5:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11105:1 Point 5:Mode • off off
• on
• test
_:11105:40 Point 5:Threshold stage 1 -50°C to 250°C 100°C
_:11105:41 Point 5:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11105:42 Point 5:Threshold stage 2 -50°C to 250°C 120°C
_:11105:43 Point 5:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11105:44 Point 5:Sensor Setting options depend on config-
uration
Point 6
_:11106:46 Point 6:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11106:1 Point 6:Mode • off off
• on
• test
_:11106:40 Point 6:Threshold stage 1 -50°C to 250°C 100°C
_:11106:41 Point 6:Operate delay of 0 s to 60 s; ∞ 5s
stage 1

1044 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

Addr. Parameter C Setting Options Default Setting


_:11106:42 Point 6:Threshold stage 2 -50°C to 250°C 120°C
_:11106:43 Point 6:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11106:44 Point 6:Sensor Setting options depend on config-
uration
Point 7
_:11107:46 Point 7:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11107:1 Point 7:Mode • off off
• on
• test
_:11107:40 Point 7:Threshold stage 1 -50°C to 250°C 100°C
_:11107:41 Point 7:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11107:42 Point 7:Threshold stage 2 -50°C to 250°C 120°C
_:11107:43 Point 7:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11107:44 Point 7:Sensor Setting options depend on config-
uration
Point 8
_:11108:46 Point 8:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11108:1 Point 8:Mode • off off
• on
• test
_:11108:40 Point 8:Threshold stage 1 -50°C to 250°C 100°C
_:11108:41 Point 8:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11108:42 Point 8:Threshold stage 2 -50°C to 250°C 120°C
_:11108:43 Point 8:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11108:44 Point 8:Sensor Setting options depend on config-
uration
Point 9
_:11109:46 Point 9:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other

SIPROTEC 5, 7SJ82/7SJ85, Manual 1045


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

Addr. Parameter C Setting Options Default Setting


_:11109:1 Point 9:Mode • off off
• on
• test
_:11109:40 Point 9:Threshold stage 1 -50°C to 250°C 100°C
_:11109:41 Point 9:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11109:42 Point 9:Threshold stage 2 -50°C to 250°C 120°C
_:11109:43 Point 9:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11109:44 Point 9:Sensor Setting options depend on config-
uration
Point 10
_:11110:46 Point 10:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11110:1 Point 10:Mode • off off
• on
• test
_:11110:40 Point 10:Threshold stage 1 -50°C to 250°C 100°C
_:11110:41 Point 10:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11110:42 Point 10:Threshold stage 2 -50°C to 250°C 120°C
_:11110:43 Point 10:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11110:44 Point 10:Sensor Setting options depend on config-
uration
Point 11
_:11111:46 Point 11:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11111:1 Point 11:Mode • off off
• on
• test
_:11111:40 Point 11:Threshold stage 1 -50°C to 250°C 100°C
_:11111:41 Point 11:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11111:42 Point 11:Threshold stage 2 -50°C to 250°C 120°C
_:11111:43 Point 11:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11111:44 Point 11:Sensor Setting options depend on config-
uration

1046 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

Addr. Parameter C Setting Options Default Setting


Point 12
_:11112:46 Point 12:Sensor location • Oil Other
• Ambient
• Turn
• Bearing
• Other
_:11112:1 Point 12:Mode • off off
• on
• test
_:11112:40 Point 12:Threshold stage 1 -50°C to 250°C 100°C
_:11112:41 Point 12:Operate delay of 0 s to 60 s; ∞ 5s
stage 1
_:11112:42 Point 12:Threshold stage 2 -50°C to 250°C 120°C
_:11112:43 Point 12:Operate delay of 0 s to 60 s; ∞ 0s
stage 2
_:11112:44 Point 12:Sensor Setting options depend on config-
uration

6.49.6 Information List

No. Information Data Class Type


(Type)
Point 1
_:11101:81 Point 1:>Block stage SPS I
_:11101:54 Point 1:Inactive SPS O
_:11101:52 Point 1:Behavior ENS O
_:11101:53 Point 1:Health ENS O
_:11101:61 Point 1:Pickup stage 1 SPS O
_:11101:62 Point 1:Operate stage 1 SPS O
_:11101:63 Point 1:Pickup stage 2 SPS O
_:11101:64 Point 1:Operate stage 2 SPS O
Point 2
_:11102:81 Point 2:>Block stage SPS I
_:11102:54 Point 2:Inactive SPS O
_:11102:52 Point 2:Behavior ENS O
_:11102:53 Point 2:Health ENS O
_:11102:61 Point 2:Pickup stage 1 SPS O
_:11102:62 Point 2:Operate stage 1 SPS O
_:11102:63 Point 2:Pickup stage 2 SPS O
_:11102:64 Point 2:Operate stage 2 SPS O
Point 3
_:11103:81 Point 3:>Block stage SPS I
_:11103:54 Point 3:Inactive SPS O
_:11103:52 Point 3:Behavior ENS O
_:11103:53 Point 3:Health ENS O
_:11103:61 Point 3:Pickup stage 1 SPS O
_:11103:62 Point 3:Operate stage 1 SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1047


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

No. Information Data Class Type


(Type)
_:11103:63 Point 3:Pickup stage 2 SPS O
_:11103:64 Point 3:Operate stage 2 SPS O
Point 4
_:11104:81 Point 4:>Block stage SPS I
_:11104:54 Point 4:Inactive SPS O
_:11104:52 Point 4:Behavior ENS O
_:11104:53 Point 4:Health ENS O
_:11104:61 Point 4:Pickup stage 1 SPS O
_:11104:62 Point 4:Operate stage 1 SPS O
_:11104:63 Point 4:Pickup stage 2 SPS O
_:11104:64 Point 4:Operate stage 2 SPS O
Point 5
_:11105:81 Point 5:>Block stage SPS I
_:11105:54 Point 5:Inactive SPS O
_:11105:52 Point 5:Behavior ENS O
_:11105:53 Point 5:Health ENS O
_:11105:61 Point 5:Pickup stage 1 SPS O
_:11105:62 Point 5:Operate stage 1 SPS O
_:11105:63 Point 5:Pickup stage 2 SPS O
_:11105:64 Point 5:Operate stage 2 SPS O
Point 6
_:11106:81 Point 6:>Block stage SPS I
_:11106:54 Point 6:Inactive SPS O
_:11106:52 Point 6:Behavior ENS O
_:11106:53 Point 6:Health ENS O
_:11106:61 Point 6:Pickup stage 1 SPS O
_:11106:62 Point 6:Operate stage 1 SPS O
_:11106:63 Point 6:Pickup stage 2 SPS O
_:11106:64 Point 6:Operate stage 2 SPS O
Point 7
_:11107:81 Point 7:>Block stage SPS I
_:11107:54 Point 7:Inactive SPS O
_:11107:52 Point 7:Behavior ENS O
_:11107:53 Point 7:Health ENS O
_:11107:61 Point 7:Pickup stage 1 SPS O
_:11107:62 Point 7:Operate stage 1 SPS O
_:11107:63 Point 7:Pickup stage 2 SPS O
_:11107:64 Point 7:Operate stage 2 SPS O
Point 8
_:11108:81 Point 8:>Block stage SPS I
_:11108:54 Point 8:Inactive SPS O
_:11108:52 Point 8:Behavior ENS O
_:11108:53 Point 8:Health ENS O
_:11108:61 Point 8:Pickup stage 1 SPS O
_:11108:62 Point 8:Operate stage 1 SPS O
_:11108:63 Point 8:Pickup stage 2 SPS O

1048 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.49 Temperature Supervision

No. Information Data Class Type


(Type)
_:11108:64 Point 8:Operate stage 2 SPS O
Point 9
_:11109:81 Point 9:>Block stage SPS I
_:11109:54 Point 9:Inactive SPS O
_:11109:52 Point 9:Behavior ENS O
_:11109:53 Point 9:Health ENS O
_:11109:61 Point 9:Pickup stage 1 SPS O
_:11109:62 Point 9:Operate stage 1 SPS O
_:11109:63 Point 9:Pickup stage 2 SPS O
_:11109:64 Point 9:Operate stage 2 SPS O
Point 10
_:11110:81 Point 10:>Block stage SPS I
_:11110:54 Point 10:Inactive SPS O
_:11110:52 Point 10:Behavior ENS O
_:11110:53 Point 10:Health ENS O
_:11110:61 Point 10:Pickup stage 1 SPS O
_:11110:62 Point 10:Operate stage 1 SPS O
_:11110:63 Point 10:Pickup stage 2 SPS O
_:11110:64 Point 10:Operate stage 2 SPS O
Point 11
_:11111:81 Point 11:>Block stage SPS I
_:11111:54 Point 11:Inactive SPS O
_:11111:52 Point 11:Behavior ENS O
_:11111:53 Point 11:Health ENS O
_:11111:61 Point 11:Pickup stage 1 SPS O
_:11111:62 Point 11:Operate stage 1 SPS O
_:11111:63 Point 11:Pickup stage 2 SPS O
_:11111:64 Point 11:Operate stage 2 SPS O
Point 12
_:11112:81 Point 12:>Block stage SPS I
_:11112:54 Point 12:Inactive SPS O
_:11112:52 Point 12:Behavior ENS O
_:11112:53 Point 12:Health ENS O
_:11112:61 Point 12:Pickup stage 1 SPS O
_:11112:62 Point 12:Operate stage 1 SPS O
_:11112:63 Point 12:Pickup stage 2 SPS O
_:11112:64 Point 12:Operate stage 2 SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1049


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.50 Phase-Sequence Switchover

6.50 Phase-Sequence Switchover

6.50.1 Overview of Functions

The Phase-sequence reversal function enables correct execution of the protection of the device and supervi-
sion functions, independently of the phase sequence of the phases in a system or system section.
The phase sequence is set via parameters. You can select between the phase sequences ABC or ACB.
Binary inputs also provide the option of switching over the phase sequence with respect to the parameter
setting. For example, in pumped-storage hydropower plants with motor or motor/generator operation you
temporarily change the direction of rotation by changing over the phase sequence.
The phase sequence has an effect on calculation of the positive-sequence system and negative-sequence
system values and on calculation of phase-to-phase values. A phase-rotation reversal therefore has an effect
on all protection and supervision functions that use these values.
You can change the phase sequence in 2 ways via binary inputs.

• Change over the phase sequence for the entire device.


In doing so, all 3-phase measuring points are switched over. All analog inputs are therefore affected (for
example current and voltage inputs simultaneously).

• Change over the phase sequence per measuring point.


In doing so, only the activated measuring points are switched over. The other measuring points remain
unaffected.

6.50.2 Structure of the Function

The Phase-sequence switchover function is integrated in the Power-system data. You will find the signals in
the DIGSI 5 project tree under Name of the device → Settings. There you will find the parameter for setting
the phase sequence and the binary inputs via which you can influence a change in the phase sequence.

[dwphrein-240211-01.tif, 1, en_US]

Figure 6-345 Structure/Embedding of the Function

6.50.3 Function Description

General
The phase sequence of the system is set in the device via the Phase sequence parameter. You will find the
signals in the DIGSI 5 project tree under Name of the device → Settings → Power-system data → General.
There are 3 methods to change the phase sequence for different operational requirements.

• Changing the phase sequence via the setting parameter.


– Note: With version V7.50 and higher, this setting parameter is a reset parameter. If the parameter is
changed and transmitted to the device, the device performs a startup. The parameter change affects
all 3-phase measuring points. If the device is in operation and if measurands are present at the
measuring points, perform a parameter change carefully since this affects all measuring points.

1050 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.50 Phase-Sequence Switchover

• With the binary signal >Phs-rotation reversal, you change over the phase sequence of all meas-
uring points.

• With the binary signal >Invert Phases, you change over the phase sequence per measuring point.
The Inverted phases parameter available for each measuring point is used to set which phases at the
measuring point must be swapped. The parameter can be found at each 3‑phase measuring point.
The 2 binary-signal mechanisms are explained separately below.

Switchover of the Phase Sequence of All Measuring Points


The direction of rotation of the currents and voltages depends on the phase sequence. The following drawing
shows the vector definitions for the 2 phase sequences.

[dwphrdrf-240211-01.tif, 1, en_US]

Figure 6-346 Vector with Different Phase Sequences

The phase sequence of a system or a system section is defined when parameterizing via the Phase
sequence parameter. The setting parameter acts on all measuring points.
The operationally induced switchover between the phase sequence ABC and the phase sequence ACB is initi-
ated via the binary input >Phs-rotation reversal. This switches over the phase sequence simultane-
ously at all 3-phase measuring points.
The following image shows a logic diagram for determining the current phase assignment and switchover.
The indications shown on the right show the present phase sequence. If the phase sequence is set via the
Phase sequence parameter to ABC, activation of the binary input will result in a switchover to the phase
sequence ACB.

NOTE

i The switchover of the phase sequence is only authorized for a time at which no measured values are
pending. The switchover command must be present for at least 200 ms. The change of phase sequence is
only permissible when the machine is at standstill. If the current and voltage values of all 3-phase meas-
uring points are below 5 % of the rated variables, this is recognized as machine standstill.

A renewed machine standstill must be detected for a resetting of the phase sequence to the set preferred posi-
tion.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1051


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.50 Phase-Sequence Switchover

[dwphrpsys1-151013, 2, en_US]

Figure 6-347 Phase Sequence Switchover

Changing Over the Phase Sequence per Measuring Point


A switchover of the phase sequence per measuring point can also be necessary for operational reasons. This
switchover enables proper behavior of the protection equipment, for example at the transition from generator
operation to motor operation (pump operation).
The following example shows an application in a pumped storage plant. The switchover of the phase
sequence (change in rotational direction) realizes the transition there from generator operation to motor oper-
ation. Which phases and measuring points are changed over depends on the conditions in the system.

[dwphrapp-240211-01.tif, 2, en_US]

Figure 6-348 Application Example for Phase-Rotation Reversal in a Pump Station

The example shows 2 differential protection devices (IED1 and IED2) and an impedance protection (IED3) with
the connected measuring points.
The phase sequence is insignificant for the differential protection of IED1, as the protected object is not
affected by the switchover option of the phase sequence.
The phase sequence is also relevant to the differential protection of IED2, as the protected object extends
beyond the switchover option.
The phase sequence is also relevant to the impedance protection (IED3). Depending on the switch position,
the voltage measured values 1 and the current measured values 3 have a different phase sequence.

1052 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.50 Phase-Sequence Switchover

The phase sequence of the system is set in the device via the Phase sequence parameter for generator
operation. The Inverted phases parameter is used to set which phase is swapped for the relevant meas-
uring point. The swap is communicated to the measuring point via the binary input signal >Invert Phases.
The changed phase sequence is then included for calculation of the measurands at the measuring point.
In accordance with Figure 6-348 the phase sequence is set to ABC. A is swapped with C in motor operation.
The Inverted phases parameter must be set to AC for the measuring points of current measured values 2
and current measured values 3. As a result, the phase assignment for the differential protection IED2 and the
impedance protection IED3 is correct. The positive-sequence and negative-sequence current is calculated
correctly.
The following logic diagram shows the principle for determining the present phase assignment and measured
variables with the example of currents.
The switchover of the phase sequence is only authorized for a time at which no measured values are pending
at the selected measuring points. The switchover command must be present for at least 200 ms. The change
in the phase sequence is only implemented if the measurands at the measuring points that are to be switched
are under 5 % of the rated variables. If the currents of the measuring points of current measured values 2 and
current measured values 3 of the example fall below 5 % of their rated variables, the switchover is released
and the set phases are switched with active binary input.

[lophrgph-190517-01.vsd, 1, en_US]

Figure 6-349 Measured Values for Changed-Over Phases

6.50.4 Application and Setting Notes

Parameter: Phase sequence

• Default setting (_:101) Phase sequence = ABC

ABC Phase sequence A, B, C


ACB Phase sequence A, B, C

Parameter: Inverted phases

• Default setting (_:106) Inverted phases = none

none No phase exchange


AC Phase A changed over with phase C
BC Phase B changed over with phase C

SIPROTEC 5, 7SJ82/7SJ85, Manual 1053


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.50 Phase-Sequence Switchover

AB Phase C changed over with phase B

NOTE

i If you change the setting value of the parameter Inverted phases, consider the following:
The device can take the new setting value only if the binary input signal >Invert Phases is not active.

Input signal: >Phs-rotation reversal


The >Phs-rotation reversal binary input is used to switch between the ABC phase sequence and the
ACB phase sequence. The switchover direction depends on the setting of the Phase sequence parameter. In
doing so, the phase sequence of all 3-phase measuring points is changed. Changing of the phase-rotation
reversal via the binary input is only possible if no measurands (< 5 % of the rated variables) are present at all 3-
phase measuring points.

Input signal: >Invert Phases


The binary input >Invert Phases is used to activate the setting of the parameter Inverted phases. In
doing so, the phase sequence of the selected measuring point is changed. Changing of the phase sequence
via the binary input is only possible if no measurand (< 5 % of the rated variables) is present at the respective
3-phase measuring point.

6.50.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:101 General:Phase sequence • ABC ABC
• ACB
General
_:101 VT 3-phase:Rated primary 0.20 kV to 1200.00 kV 400.00 kV
voltage
_:102 VT 3-phase:Rated secon- 80 V to 230 V 100 V
dary voltage
_:103 VT 3-phase:Matching ratio 0.10 to 9.99 1.73
Vph / VN
_:104 VT 3-phase:VT connection • 3 ph-to-gnd volt. + VN 3 ph-to-gnd
volt. + VN
• 3 ph-to-gnd voltages
• 3 ph-to-ph volt. + VN
• 3 ph-to-ph voltages
_:106 VT 3-phase:Inverted phases • none none
• AC
• BC
• AB
_:111 VT 3-phase:Tracking • inactive active
• active
_:107 VT 3-phase:Measuring- 0 to 100 0
point ID

1054 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.50 Phase-Sequence Switchover

6.50.6 Information List

No. Information Data Class Type


(Type)
General
_:500 General:>Phs-rotation reversal SPS I
_:501 General:>Invert Phases SPS I
General
_:319 General:Phase sequence ABC SPS O
_:320 General:Phase sequence ACB SPS O
_:321 General:Freq.out of oper.range SPS O
_:322 General:f sys MV O
_:323 General:f track MV O
General
_:315 VT 3-phase:Phases AB inverted SPS O
_:316 VT 3-phase:Phases BC inverted SPS O
_:317 VT 3-phase:Phases AC inverted SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1055


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.51 Current-Jump Detection

6.51 Current-Jump Detection

6.51.1 Overview of Functions

The Current jump detection function has the following tasks:

• Detection of jumps in the phase or zero-sequence current (ΔI)

• Generation of an indication when the measurands change by more than a configured threshold value
from one system period to the next.
The function for detecting jumps in the phase or zero-sequence current is an additional function used for indi-
cation purposes or for further processing in user-specific CFC logics. Pick up of the function therefore neither
opens a separate fault in the fault log nor generates an operate indication.

6.51.2 Structure of the Function

The Current-jump detection function is used in protection function groups based on current measurement. It
can be instantiated multiple times.

[dwstruki-111026-01.tif, 1, en_US]

Figure 6-350 Structure/Embedding of the Function

6.51.3 Function Description

Current-jump detection operates directly with the sampled values without numeric filtering. This provides very
short response times to sudden changes in the current. The method used is not sensitive to slow changes of
amplitude or frequency.
Using a configurable selection of measured values, you can select from 3 line currents or the residual current.
Current-jump detection is phase-selective for the line current A, B and C.
The difference from the previous sampled value of the first system cycle is calculated for each sampled value.
The rectified average is then determined for a ½ system cycle from this differential signal Δi(t). The rectified
average for sinusoidal measurands is then converted to a RMS value ΔI by subsequent multiplication by 1.11.
The resultant measurand ΔI is then compared with the threshold value.
If the parameter (_:101) Threshold is exceeded, the output indication Jump is generated. If you have
selected the phase currents for measurement, the output indication data type used includes the separate
phase information. If you have selected the residual current for measurement, the output indication data type
used includes the NI information. If the current-jump detection responds (ΔILimit), the general information is
generated in the output indication in all cases.
Dropout occurs with a dynamically increased threshold value (ΔILimit) in accordance with the logic in
Figure 6-351. Dynamic increase of the dropout threshold value achieves optimally short dropout times.
The output indication Pulse is formed with the configurable timer (_:102) Minimum pulse length. As
a consequence this output indication has a consistent minimum size. If you activate the binary input >Pulse
extension, you can prolong the pulse duration even further. If the binary input >Pulse extension has
been activated, the indication Pulse drops off when the configured time has elapsed and the falling edge of
the binary input is detected.

1056 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.51 Current-Jump Detection

Logic

[lojumpii-271011-01.tif, 1, en_US]

Figure 6-351 Current-Jump Detection Logic

6.51.4 Application and Setting Notes

Parameter: Measured value

• Default setting (_:9) Measured value = phase currents


With the parameter Measured value, you set whether the line current(s) or the residual current is to be
used for jump detection.
Parameter Value Description
phase currents The tripping stage evaluates the line currents IL1, IL2
and IL3 phase-selectively to detect a jump.
zero-sequence current The tripping stage evaluates the residual current
IN/3I0 to detect a jump.

Parameter: Threshold

• Default setting (_:101) Threshold = 0.10 A for Irated = 1A or 0.50 A for Irated = 5 A

With the parameter Threshold, you set the threshold value for the measurand which, when exceeded,
generates the output indication Jump.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1057


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.51 Current-Jump Detection

Parameter: Minimum pulse length

• Default setting (_:102) Minimum pulse length = 0.10 s


With the parameter Minimum pulse length, you specify a consistent minimum size for the output indica-
tion Pulse.

6.51.5 Settings

Addr. Parameter C Setting Options Default Setting


I-jump det. #
_:1 I-jump det. #:Mode • off off
• on
• test
_:9 I-jump det. #:Measured • phase currents phase currents
value
• zero-sequence current
_:101 I-jump det. #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:102 I-jump det. #:Minimum 0.01 s to 60.00 s 0.10 s
pulse length

6.51.6 Information List

No. Information Data Class Type


(Type)
I-jump det. #
_:81 I-jump det. #:>Block stage SPS I
_:501 I-jump det. #:>Pulse extension SPS I
_:54 I-jump det. #:Inactive SPS O
_:52 I-jump det. #:Behavior ENS O
_:53 I-jump det. #:Health ENS O
_:301 I-jump det. #:Jump ACT O
_:302 I-jump det. #:Pulse ACT O

1058 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.52 Voltage-Jump Detection

6.52 Voltage-Jump Detection

6.52.1 Overview of Functions

The Voltage-jump detection function has the following tasks:

• Recognition of jumps in the phase or zero-sequence voltage (ΔV)

• Generation of an indication when the measurands change by more than a configured threshold value
from one system cycle to the next.
The function for detecting jumps in the phase or zero-sequence voltage is an additional function used for indi-
cation purposes or for further processing in user-specific CFC logics. Pick up of the function therefore neither
opens a separate fault in the fault log nor generates an operate indication.

6.52.2 Structure of the Function

The Voltage-jump detection function is used in protection function groups based on voltage measurement. It
can be instantiated multiple times.

[dwstruku-011211-01.tif, 1, en_US]

Figure 6-352 Structure/Embedding of the Function

6.52.3 Function Description

Voltage-jump detection operates directly with the sampled values without numeric filtering. This provides very
short response times to sudden changes in the voltage. The method used is not sensitive to slow changes of
amplitude or frequency.
By using a configurable selection of measured values, you can select from phase-to-ground voltages, phase-to-
phase voltages or the zero-sequence voltage. Voltage-jump detection is phase-selective.
The difference from the previous sampled value of 1 system cycle is calculated for each sampled value. The
rectified average is then determined for a ½ system cycle from this differential signal Δv(t). The rectified
average for sinusoidal measurands is then converted to a RMS value ΔV by subsequent multiplication by 1.11.
The resultant measurand ΔV is then compared with the threshold value.
If the parameter (_:101) Threshold is exceeded, the output indication Jump is generated. If the measured
value is set to phase-to-phase, the sudden change in voltage is signaled selectively for the individual meas-
uring elements that have picked up (Jump VAB, Jump VBC or Jump VCA). If you have selected the phase-to-
phase or phase-to-ground voltages for measurement, the output indication data type used included the sepa-
rate phase information. If you have selected the zero-sequence voltage for measurement, the output indica-
tion data type used includes the N information. If the voltage-jump detection responds (ΔVLimit), the general
information is generated in the output indication in all cases.
Dropout occurs with a dynamically increased threshold value ΔULimit in accordance with the information in
Figure 6-353. Dynamic increase of the dropout threshold value achieves optimally short dropout times.
A timing element is added to the indication Jump. The element generates a pulse from this. The length of this
pulse can be set using the parameter (_:102) Minimum pulse length. This gives the output indication
Pulse a reliable minimum size. If you activate the binary input >Pulse extension, you can prolong the
pulse duration even further. If the binary input >Pulse extension has been activated, the indication
Pulse drops off when the configured time has elapsed and the falling edge of the binary input is detected. If

SIPROTEC 5, 7SJ82/7SJ85, Manual 1059


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.52 Voltage-Jump Detection

the measured value is set to phase-to-phase, the pulse duration is signaled selectively for the individual meas-
uring elements that have picked up (Pulse VAB, Pulse VBC or Pulse VCA).

Logic

[lojumpuu-011211-01.tif, 2, en_US]

Figure 6-353 Voltage-Jump Detection Logic

6.52.4 Application and Setting Notes

Parameter: Measured value

• Default setting (_:9) Measured value = phase-to-ground


With the parameter Measured value , you specify which measured values of voltage are to be used for
determining the voltage jumps.
Parameter Value Description
phase-to-ground The tripping stage evaluates the phase-to-ground
voltages VA, VB and VC.
phase-to-phase The tripping stage evaluates the phase-to-phase
voltages VAB, VBC and VCA.
zero-sequence voltage The tripping stage evaluates the zero-sequence
voltage VN/V0.

1060 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.52 Voltage-Jump Detection

Parameter: Threshold

• Default setting (_:101) Threshold = 5.000 V


With the parameter Threshold , you set the threshold value for the measurand which, when exceeded,
generates the output indication Jump .

Parameter: Minimum pulse length

• Default setting (_:102) Minimum pulse length = 0.10 s


With the parameter Minimum pulse length , you specify a consistent minimum size for the output indica-
tion Pulse .

6.52.5 Settings

Addr. Parameter C Setting Options Default Setting


V-jump det. #
_:1 V-jump det. #:Mode • off off
• on
• test
_:9 V-jump det. #:Measured • phase-to-ground phase-to-ground
value
• phase-to-phase
• zero-sequence voltage
_:101 V-jump det. #:Threshold 0.300 V to 340.000 V 5.000 V
_:102 V-jump det. #:Minimum 0.01 s to 60.00 s 0.10 s
pulse length

6.52.6 Information List

No. Information Data Class Type


(Type)
V-jump det. #
_:81 V-jump det. #:>Block stage SPS I
_:501 V-jump det. #:>Pulse extension SPS I
_:54 V-jump det. #:Inactive SPS O
_:52 V-jump det. #:Behavior ENS O
_:53 V-jump det. #:Health ENS O
_:301 V-jump det. #:Jump ACT O
_:302 V-jump det. #:Jump VAB SPS O
_:303 V-jump det. #:Jump VBC SPS O
_:304 V-jump det. #:Jump VCA SPS O
_:305 V-jump det. #:Pulse ACT O
_:306 V-jump det. #:Pulse VAB SPS O
_:307 V-jump det. #:Pulse VBC SPS O
_:308 V-jump det. #:Pulse VCA SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1061


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.53 Voltage Measuring-Point Selection

6.53 Voltage Measuring-Point Selection

6.53.1 Overview of Functions

The function block Voltage measuring-point selection can:

• Provide the ability to switchover the voltage measuring points to be applied, if various voltage measuring
points are connected to the voltage interface of the function group

• Select the correct voltage based on the switch position of the plant
If more than one voltage measuring points are connected to the same voltage interface of the function group,
use the Voltage measuring-point selection function block in the function group to select the correct voltage
based on the switch position of the plant.
The Voltage measuring-point selection is a common functionality for the function groups of the protected
objects.

6.53.2 Function Description

The Voltage measuring-point selection function block realizes the selection of 1-phase voltage measuring
points or of 3-phase voltage measuring points by a logic block chart. The logic block chart controls the input
>MP-ID selection depending on the switch positions of disconnectors.

Example
Figure 6-354 shows an example of voltage measuring points selection for the function group Capacitor bank
in a double busbar application.

[dwbusbardouble.vsd, 2, en_US]

Figure 6-354 Double Busbar with Capacitor Bank

Connecting Measuring Points to Capacitor Bank Function Group


Figure 6-355 shows the connection of the function group Capacitor bank with several measuring points in
DIGSI. The ID of each measuring point appears in the bracket after the name.

1062 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.53 Voltage Measuring-Point Selection

[scconnection, 1, en_US]

Figure 6-355 Connecting the Measuring Points with the Capacitor Bank Function Group

There are consistency checks that validate the connections of voltage measuring points to the function group:

• The connection type must be identical for all measuring points connected to the same interface of the
function group.

• The rated voltage (primary and secondary) must be identical for all measuring points connected to the
same interface.

• If more than 1 measuring point is connected to one voltage interface, a function block must be added to
enable the selection of the voltage measuring points.

6.53.3 Application and Setting Notes

CFC Control
The voltage measuring point is selected by logic block chart on basis of the measuring point IDs. If more than
one measuring point is connected to the interface of the function group, instantiate the function block
Voltage measuring-point selection from the library in the corresponding function group.
In order to ensure the correct measuring-point connection for the function group, a logic block chart has to
define the actual valid IDs for the input >MP-ID selection of the function block.
The following logic block chart implementation is based on the example given in Figure 6-354.
If the Disconnector 1 (QB1) is closed and no matter what the position the Disconnector 2 (QB2) is, the value 2
is the output of CFC block mux_d_1 and transferred to the input >MP-ID selection. Then, the Meas.point
V-3ph with ID 2 is selected as the reference voltage. Similarly, the Meas.point V-3ph with ID 3 is selected as
the reference voltage if the Disconnector 1 (QB1) is not closed (open or in intermediate position) while
Disconnector 2 (QB2) is closed.

[sc_lo-cfcVP, 1, en_US]

Figure 6-356 Logic Block Chart: Voltage Selection Using Measuring Point ID

However, the disconnectors might be both open or in a transient state. In this case, the input IN3 of the block
bool_int_1 becomes true, the value 0 is used as the ID for voltage selection input ( >MP-ID selection). If
ID 0 is selected, then all voltage values of the respective function-group interface are set to 0 V immediately.
An alarm indication Selection invalid is issued and the indication Health is issued as OK. In case you
want to supply the function group with voltage values under the condition that both disconnectors are open
or in transient state from one or the other busbar, you can alter the CFC chart respectively.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1063


C53000-G5040-C017-A, Edition 06.2019
Protection and Automation Functions
6.53 Voltage Measuring-Point Selection

NOTE

i An invalid measuring-point selection (ID < 0 or an ID of a unconnected measuring point) for input >MP-ID
selection results in the following:
• The voltage measured values are displayed as failure.

• The validity of the voltage measured values is set to invalid.

• The indication Health is set to Alarm.

• The indication Selection invalid becomes true.

6.53.4 Information List

No. Information Data Class Type


(Type)
V-MP selection
_:501 V-MP selection:>MP-ID selection INS I
_:53 V-MP selection:Health ENS O
_:301 V-MP selection:Selection invalid SPS O

1064 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
7 Capacitor Bank Protection

7.1 Introduction 1066


7.2 Overcurrent Protection for Capacitor Banks 1067
7.3 Thermal Overload Protection for Capacitor Banks 1071
7.4 Current-Unbalance Protection for Capacitors, 3-Phase 1075
7.5 Current-Unbalance Protection for Capacitors, 1-Phase 1100
7.6 Peak Overvoltage Protection for Capacitors 1119
7.7 Voltage Differential Protection for Capacitors 1131
7.8 Differential Protection for Capacitor Banks 1143
7.9 Detuning Supervision for Capacitor Banks 1171

SIPROTEC 5, 7SJ82/7SJ85, Manual 1065


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.1 Introduction

7.1 Introduction
Capacitors and capacitor banks are used for various applications. Examples are:

• Reactive-power compensation for voltage stabilization

• Fast voltage- and reactive-power control

• Filter circuits for the elimination of certain frequencies


Capacitor banks for transmission systems are complex systems customized for the special application. The
design depends much on the used switching technology (for example, mechanically or via thyristor). In detail
hardly one capacitor bank resembles another. However, a capacitor bank consists always of the same compo-
nents (C, R, L, and switches). A capacitor bank often consists of several subcomponents which are connected
to the capacitor-bank busbar via the circuit breakers.
The modularity of hardware and protection functionality allows to tailor the protection device exactly to the
needs of the capacitor bank or the subcomponent of the capacitor bank and to realize the complete protection
of the whole capacitor bank or the capacitor- bank subcomponent with only one 7SJ8 device.
Capacitor banks require the use of extensive protection functionality. The protection consists of standard
protection functions and specific capacitor protection functions. The following topics are described in the next
chapters:

• Extensions on standard protection functions for optimal utilization in a capacitor bank

• Specific capacitor protection functions

• Application of standard protection functions for specific protection tasks within a capacitor bank

1066 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.2 Overcurrent Protection for Capacitor Banks

7.2 Overcurrent Protection for Capacitor Banks

7.2.1 Overview

You can use the following overcurrent protection function types in the Capacitor bank function group:

• Overcurrent protection, phases with phase-segregated operate indications for short-circuit protection
in the area between the busbar and the capacitor and for protecting against overload of a subbank.

• Overcurrent protection, phases for protection against overload of RLC filter circuit elements (Over-
curr. -3ph RLC)

• Overcurrent protection, ground as protection or backup protection in the event of ground faults
Figure 5-17 in chapter 5.4.2 Structure of the Function Group shows

• The standard protection functions you can use in the Capacitor bank function group.

• The specific protection functions that are available for protecting a capacitor bank.

• The assignment of protection functions to the interfaces of the function group.


Figure 5-15 in chapter 5.4.2 Structure of the Function Group shows the assignment of the interfaces in the
Capacitor bank function group to the measuring points of the device with reference to an example.

NOTE

i Starting from V07.30, the function type 50/51 OC-3ph 1p is no longer offered in the DIGSI 5 global library
in the function group Capacitor bank. Instead you can use now the standard overcurrent protection func-
tion Overcurrent protection, phases – advanced to apply phase-segregated operate indications.

7.2.2 Overcurrent Protection, Phases for Protection of RLC Filter-Circuit Elements

7.2.2.1 Structure of the Function


In the Capacitor bank function group, the Overcurr. -3ph RLC function is based on the standard overcurrent
protection function Overcurrent protection, phases – advanced.
The Overcurr. -3ph RLC function differs from the standard protection function as follows:

• Superordinate measuring-point selection

• Selecting whether the rated current of the capacitor bank or of the protected object (for example, reactor
or resistor) is taken as reference value

• Setting the rated current of the protected object (for example, reactor or resistor) within the function if
necessary

• Functional measured values of connected phase currents

SIPROTEC 5, 7SJ82/7SJ85, Manual 1067


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.2 Overcurrent Protection for Capacitor Banks

[dwocpRLC-190813-01.vsd, 3, en_US]

Figure 7-1 Structure/Embedding of the Overcurr. -3ph RLC Function

7.2.2.2 Function Description


A feature of the Overcurr. -3ph RLC function is the selection of measuring points. A capacitor bank can
include multiple filter circuits. Each filter can include, for example, a 3-phase current measuring device, each
of which is assigned a measuring point. In order to protect the filter circuits, multiple instances of the Over-
curr. -3ph RLC function can be created. Each instance of the function is assigned to a measuring point via the
Measuring-point selection.
The function is structured such that the Measuring-point selection is superordinate to the advanced overcur-
rent-protection stages.

Measuring-Point Selection
With the MP selection parameter, you can select from a list of measuring points a measuring point that is
connected to the I 3ph RLC interface in the Capacitor bank function group. The Overcurr. -3ph RLC function
processes the current that is connected to the measuring point.
For more information, refer to the description of the Capacitor bank function group starting from chapter
5.4.1 Overview.

Selection and Setting of the Rated Current


With the parameter Rated-current selection, you define whether this function uses the rated current
of the whole capacitor bank or the individual rated current of the protected object (for example, reactor or
resistor branch within the capacitor-bank installation) as the reference value for percentage-measured values
and for thresholds set in percentages.
If you select the individual rated current of the protected object as the reference value, set the individual rated
current in the FB General of the Overcurr. -3ph RLC function.

Functional Measured Values


The function provides the connected phase currents as functional measured values for display, further
processing, or transmission to a station.

1068 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.2 Overcurrent Protection for Capacitor Banks

Measured Values Description Primary Secondary % Referenced to


(_:13501:301) Iph 3 phase currents of the meas- kA A Parameter Capacitor
uring point reference curr. or RLC
rated current depending
on the setting of parameter
Rated-current selec-
tion

You can find the parameter Capacitor reference curr. in the FB General of the Capacitor bank func-
tion group, and the parameter RLC rated current in the FB General of the Overcurr. -3ph RLC function.

7.2.2.3 Application and Setting Notes

Parameter: MP selection

• Default setting (_:13501:81) MP selection = None


With the MP selection parameter, you can select a measuring point that is connected to the I 3ph RLC
interface in the Capacitor bank function group.
The selection list displays the measuring points that are connected to the I 3ph RLC interface of the Capacitor
bank function group:

[scmpselection_ocp_rlc, 1, en_US]

Figure 7-2 Example of Measuring-Point Selection

The MP selection parameter is set for all stages. The setting applies equally to all stages of the function.
In the default setting, a measuring point is not selected. You must select a measuring point. If you do not
select a measuring point, an inconsistency is indicated via the read-only parameter Consistency failure:

[scinconsistency_ocp_rlc, 1, en_US]

Figure 7-3 Function Inconsistency Indication

Parameter: Rated-current selection

• Default setting (_:2311:101) Rated-current selection = prim. rated curr.of MP


With the parameter Rated-current selection, you define the reference value for percentage-measured
values and for thresholds set in percentages.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1069


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.2 Overcurrent Protection for Capacitor Banks

Parameter Value Description


prim. rated curr.of MP Select this setting if you want to use the rated current of the whole capac-
itor bank as the reference value.
RLC rated current Select this setting if you want to use the individual rated current of the RLC
object to be proteced (for example, a resistor or reactor) as the reference
value.

Parameter: RLC rated current

• Default setting (_:2311:102) RLC rated current = 1000 A


With the parameter RLC rated current, you set the primary rated current of the respective protected
object which is usually a reactor or resistor branch within the capacitor-bank installation.

7.2.2.4 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Rated-current • prim. rated curr.of MP prim. rated
selection curr.of MP
• RLC rated current
_:2311:102 General:RLC rated 1 A to 10 0000 A 1 000 A
current
MP selection
_:13501:100 MP selection:Consistency • no MP configured no MP config-
failure ured
• no Sensor configured
_:13501:81 MP selection:MP selec- Setting options depend on
tion configuration

7.2.2.5 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
MP selection
_:13501:301 MP selection:Iph WYE O

1070 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.3 Thermal Overload Protection for Capacitor Banks

7.3 Thermal Overload Protection for Capacitor Banks

7.3.1 Overview of Functions

The function Thermal overload protection for capacitor banks (Overload RLC) protects RLC filter circuit
elements in a capacitor bank from thermal overload.

NOTE

i The structure of the function Overload RLC differs only slightly from that of the standard Thermal over-
load protection, 3-phase – advanced function. In this chapter, only the differences between these and
the standard function are described.
For more information, refer to the function description Thermal overload protection, 3-phase –
advanced starting from chapter 6.20.1 Overview of Functions.

7.3.2 Structure of the Function

The function Overload RLC is used in the Capacitor bank function group.
The General functionality differs from the standard Thermal overload protection, 3-phase – advanced
function and consists of:

• Measuring-point selection

• Selecting whether the rated current of the capacitor bank or of the protected object (for example, reactor
or resistor) is taken as reference value

• Setting the rated current of the protected object (for example, reactor or resistor) within the function if
necessary

[dwtolp_rlc-200813, 3, en_US]

Figure 7-4 Structure/Embedding of the Function

7.3.3 Function Description

A feature of the function Overload RLC is the Measuring-point selection. A capacitor bank can include
multiple filter circuits. Each filter circuit can include, for example, a 3-phase current transformer, each of
which is assigned a measuring point. In order to protect all filter circuits, multiple instances of the function
Overload RLC can be created. Each instance of the function is assigned to a measuring point via the Meas-
uring-point selection.
The function is structured such that the Measuring-point selection is superordinate to the Thermal overload
protection stage.

Measuring-Point Selection
With the parameter MP selection, you can select from a list of measuring points a measuring point that is
connected to the I 3ph RLC interface in the Capacitor bank function group. The function Overload RLC
processes the current that is connected to the measuring point.
For more information, refer to the description of the Capacitor bank function group starting from Chapter
5.4.1 Overview.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1071


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.3 Thermal Overload Protection for Capacitor Banks

Selection and Setting of the Rated Current


With the parameter Rated-current selection, you define whether this function uses the rated current
of the whole capacitor bank or the individual rated current of the protected object (for example, reactor or
resistor branch within the capacitor-bank installation) as the reference value. This function uses the reference
value for current normalization in thermal-replica calculation, for percentage-measured values, and for thresh-
olds set in percentages.
If you select the individual rated current of the protected object as the reference value, set the individual rated
current in the FB General of the Overload RLC function.

Functional Measured Values

Measured Values Description Primary Secondary % Referenced to


(_:13501:301) Iph 3-phase currents of the meas- A A Parameter Capacitor
uring point reference curr. or RLC
rated current depending
on the setting of parameter
Rated-current selec-
tion
(_:601:304) Time Time until close release s s s
until close
(_:601:305) Time Estimated time until tripping s s s
until trip
(_:601:306) Over- Thermal measured values of % % Trip temperature
load phase A phases
(_:601:307) Over-
load phase B
(_:601:308) Over-
load phase C
(_:601:309) Over- Thermal measured values of % % Trip temperature
load maximum overload protection
(_:601:310) Current measured value as A A Parameter Capacitor
Equival. current base for overload measured reference curr. or RLC
phs A value rated current depending
(_:601:311) on the setting of parameter
Equival. current Rated-current selec-
phs B tion
(_:601:312)
Equival. current
phs C
(_:601:313) Maximum current measured A A Parameter Capacitor
Equival. current value as base for overload reference curr. or RLC
max. value rated current depending
on the setting of parameter
Rated-current selec-
tion

7.3.4 Application and Setting Notes

Parameter: MP selection

• Default setting (_:13501:81) MP selection = no MP configured


With the MP selection parameter, you can select a measuring point that is connected to the I 3ph RLC
interface in the Capacitor bank function group.

1072 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.3 Thermal Overload Protection for Capacitor Banks

The selection list displays the measuring points that are connected to the I 3ph RLC interface of the Capacitor
bank function group:

[scmpselection_tolp_rlc, 1, en_US]

Figure 7-5 Example of Measuring-Point Selection

The MP selection parameter is set for all stages. The setting applies equally to all stages of the function.
In the default setting, a measuring point is not selected. You must select a measuring point. If you do not
select a measuring point, an inconsistency is indicated via the read-only parameter Consistency
failure :

[scinconsistency_tolp_rlc, 1, en_US]

Figure 7-6 Function Inconsistency Indication

Parameter: Rated-current selection

• Default setting (_:2311:101) Rated-current selection = prim. rated curr.of MP


With the parameter Rated-current selection, you define the reference value for current normalization
in thermal-replica calculation, for percentage-measured values, and for thresholds set in percentages.
Parameter Value Description
prim. rated curr.of MP Select this setting if you want to use the rated current of the whole capac-
itor bank as the reference value.
RLC rated current Select this setting if you want to use the individual rated current of the RLC
object to be proteced (for example, a resistor or reactor) as the reference
value.

Parameter: RLC rated current

• Default setting (_:2311:102) RLC rated current = 1000 A


With the parameter RLC rated current, you set the primary rated current of the respective protected
object which is usually a reactor or resistor branch within the capacitor-bank installation.

7.3.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Rated-current • prim. rated curr.of MP prim. rated
selection curr.of MP
• RLC rated current

SIPROTEC 5, 7SJ82/7SJ85, Manual 1073


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.3 Thermal Overload Protection for Capacitor Banks

Addr. Parameter C Setting Options Default Setting


_:2311:102 General:RLC rated 1 A to 100 000 A 1 000 A
current
MP selection
_:13501:100 MP selection:Consistency • no MP configured no MP config-
failure ured
• no Sensor configured
_:13501:81 MP selection:MP selec- Setting options depend on
tion configuration

7.3.6 Information List

No. Information Data Class Type


(Type)
MP selection
_:13501:301 MP selection:Iph WYE O

1074 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

7.4 Current-Unbalance Protection for Capacitors, 3-Phase

7.4.1 Overview of Functions

The Current-unbalance protection for capacitors, 3-phase function (ANSI 60C):

• Protects in case of capacitor elements (C-elements) faults of a capacitor bank in H connection

• Provides very sensitive supervision of the unbalanced current between the 2-star points

• Allows counting of individual faulty C-elements

7.4.2 Structure of the Function

The Current-unbalance protection for capacitors, 3-phase function is used in the Capacitor bank function
group. It is preconfigured at the factory with 2 overcurrent-protection stages I> and one stage of the type
Counter. A maximum of 3 overcurrent-protection stages and 4 counter stages can be operated simultaneously
in the function.
The function is designed so that the General functionality (including compensation) and the Measuring-
point selection can work across the stages.

[dwocpIunbalanced-300813, 4, en_US]

Figure 7-7 Structure/Embedding of the Function

7.4.3 General Functions and Measuring-Point Selection

7.4.3.1 Description

The General functionality is structured in the following functional parts:

• Compensation of the unbalance

• Normalization of the unbalanced current with the current Ic

• Counting faulty C-elements (the stage type Counter is used to monitor the counter status)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1075


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

Logic for Compensation and Normalization

[lo_FBallg_iunbal-020913.tif, 3, en_US]

Figure 7-8 Cross-Stage Functionality

Measuring-Point Selection
With the MP selection parameter, you can select from a list of measuring points a measuring point that is
connected to the I Unbalanced interface in the Capacitor bank function group. The Current-unbalance
protection for capacitors, 3-phase function processes the current that is connected to the measuring point.
For more information, refer to the description of the Capacitor bank function group starting from chapter
5.4.1 Overview.

Measurands, Method of Measurement


The function receives its measurands via the I Unbalanced interface of the Capacitor bank function group.

1076 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

The compensated and non-compensated unbalanced currents are provided for the overcurrent-protection
stage. Within the protection stage, one of the 2 values is selected in the protection stage via the parameter
Measured value. Both values are available as functional measured values (see Figure 7-8).
Configure across the stages whether the unbalanced current must be normalized with the current Ic that flows
into the capacitor bank. You can find more information in this chapter under Normalization with Ic ,
Page 1078.
The method of measurement used processes the sampled unbalanced-current values and filters out the funda-
mental component numerically. The protection stages evaluate the fundamental component of the unbal-
anced current.

General Notes on the Compensation


An operational unbalanced current is added to an unbalanced current resulting from faulty capacitor
elements. This corrupts the measuring result.
Operational unbalanced currents can result from the following causes:

• Manufacturing tolerances of the capacitor

• Aging of the capacitor

• Environmental influences, for example, temperature


The compensation eliminates operational unbalanced currents by calculation. For this purpose, the phasor of
the operational unbalanced current I unbal.,op. is stored at specific times. The stored phasor (compensation
phasor), is subtracted from the actually measured unbalanced-current phasor:

[fo_compensatied unbal., 1, en_US]

The following indications describe the status of the compensation:


Indication Description
Alg. not The algorithm is not compensated. The compensated values are not available under
compensated the following conditions:

• After initial startup of the device before any compensation is carried out
• After activating the binary input >Reset comp. val.
• After change of Irated,obj
Protection stages that are working with compensated values are inactive.
Compens. This indication is issued (as transient indication with a pulse duration of 10 ms) if the
succeeded existing unbalance has been compensated manually or automatically. In case of auto-
matic compensation, the signal is issued at each event-based situation where full
compensation is carried out.
Comp. via BI If a manual compensation has been initiated and the current Ic (current flowing into
blk.(Ic<) the capacitor bank) at this time is less than the threshold Current threshold CB
open, the manual compensation is not executed. This is signaled via the Comp. via
BI blk.(Ic<) indication.

2 different methods are available for the compensation:

• Manual compensation via binary input signals

• Automatic compensation

Manual Compensation via Binary Input Signal


If the binary input signal >Compensate is activated, the manual compensation starts. This will fully compen-
sate any unbalance that exists at this time. This means the value Iunbal.,comp. will then become 0. You can also
use the manual compensation in parallel with the automatic compensation.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1077


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

For the reliability of manual compensation, the binary input signal >Compensate has a preset software
filtering time (configurable in DIGIS) of 20 ms.

Automatic Compensation
When using the parameter Automatic compensation , this automatic compensation function can be
enabled or disabled.
The automatic compensation consists of 2 different mechanisms:

• The event-based compensation of any existing unbalance.


This compensation is performed in the following situations:
– After energizing the capacitor bank or a phase of the bank (phase-selective compensation)
– After counting a faulty C-element (phase-selective compensation)
– After each startup of the device
– After specific parameter changes:
– Switching on the automatic compensation
– Changing the rated current of the capacitor bank
In order to avoid transient inrush-current effects, the compensation is delayed by 250 ms after energizing
has been detected.
Full compensation after bank energization can be avoided in case of only short de-energization by means
of parameter De-energ.time w/o comp.. If the de-energized duration is less than the setting of
parameter De-energ.time w/o comp., the full compensation is not carried out after energizing a
phase or the whole bank.

• Cyclic, slow and thus gradual compensation of an existing unbalance in small increments.
This permits, for example, the automatic compensation of environmental influences.

Resetting the Compensation


The algorithm can be reset to the non-compensated status. Compensated values are not available in this case.
Protection stages that work with compensated values are rendered inactive. The binary input signal >Reset
comp. val. of the function or function group resets the compensation (see also Figure 7-8).
For the reliability of manual compensation, the binary input signal >Reset comp. val. has a preset soft-
ware filtering time (configurable in DIGIS) of 20 ms.

NOTE

i When operating with manual compensation, changing the value of parameter capacitor reference
current will reset the compensation values.

Normalization with Ic

The threshold for the unbalanced current is usually set by assuming the rated capacitor current Ic,rated. The
current Ic flowing into the capacitor bank determines the amount of the unbalanced current. A lower Ic also
means a lower unbalanced current. If Ic < Ic,rated, the protection becomes less sensitive. This influence can be
compensated via the normalization. Normalization keeps the sensitivity of the protection function constant by
normalizing the unbalance value with the current Ic. When using the parameter Normalization with Ic ,
normalization is enabled or disabled.

Ic Lower than Current Thresh.CB Open

If the current Ic is lower than the threshold Current Thresh.CB Open, the compensated value can no
longer be computed with sufficient accuracy. To avoid a malfunction, the compensated unbalanced value
Iunbal.,comp. is set to 0 A in a phase-segregated way (see Figure 7-8). This deactivates the affected phase meas-
uring components of the protection stages that work with compensated values.

1078 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

This condition will be indicated in a phase-segregated manner (indication I>-stage(cmp) blk.(Ic<) ).


In this case, normalization with current Ic will no longer work properly either. The normalization is canceled in
a phase-segregated manner. This means that the non-normalized value is used in place of the normalized
value (see Figure 7-8).

Charging/Energizing the Capacitor Bank or a Phase of the Bank


Charging of the bank takes place when the discharged bank is switched on to the network. Charging of a
phase can occur in case of network faults. If a phase-to-ground voltage drops to 0 V due to a network fault,
the respective phase is discharged and the return of the phase-to-ground (after the fault has been cleared) will
charge the phase.
Charging the bank or a phase of the bank causes inrush currents in the respective phases. To avoid overfunc-
tion in case of sensitive threshold settings, the stages using compensated unbalanced values are blocked in a
phase-selective way by setting Iunbal.,comp. to 0 A. These stages are:

• Counter stage

• I> stage, if set to operate with compensated unbalanced values


The blocking (Iunbal.,comp. set to 0 A) lasts for 250 ms after energizing detection. Afterwards, the calculated
Iunbal.,comp. is processed again.
Energizing detection takes place in a phase-selective way by monitoring the phase current Ic flowing into the
bank. If a phase current exceeds the threshold Current Thresh.CB Open, energizing in this phase is
detected.

Logic for Counting Faulty C-Elements


This part of the General functionality is only important if counter stages are used.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1079


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

[lo-cnt-EF-260314-01, 3, en_US]

Figure 7-9 Counting Faulty C-Elements

Activation/Blocking Counting
If at least one counter stage is enabled, the counter function is active. Furthermore, the counter function
works only if the automatic compensation is enabled.
In order to prevent counting as a consequence of the charging process, the counter function is implicitly
blocked for 250 ms by setting Iunbal.,comp. to 0 A, after the capacitor energizing has been detected.

Measurands, Counting
The measurand is the phase-selective compensated unbalanced current Iunbal.,comp.. If a single C-element is
faulty, an unbalance occurs in the H connection. This unbalance causes an unbalanced current; this means, a
small current jump is generated in the unbalanced current. Set the parameter Thresh. defective C-
elem., so that the current jump can be detected (refer also to 7.4.3.2 Application and Setting Notes). The
unbalanced current that was caused by the fault must exceed the threshold for 100 ms before the affected
group is determined and counting (incrementing the counter) takes place. There is one counter for each phase
and group. After the counting, the existing unbalance is compensated; this means, the unbalance is reset to
0 A. If the faulty group cannot be determined, the unbalance is also compensated.

1080 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

Resetting/Setting the Counters


You can reset or set the counters of group 1 and group 2 via:

• On-site operation panel directly on the device

• Online DIGSI connection to the device

• Binary input >Reset all counters (only reset of all counters)

• Communication connection with the control center


You can directly set or reset the counters via IEC 61850 by setting the counter values to the desired value. If
you want to reset the counters via DNP3, IEC 60870-5-103, Modbus, or IEC 60870-5-104, an additional config-
uration with CFC is necessary. For more information, refer to chapter 7.4.3.2 Application and Setting Notes.

Functional Measured Values

Values Description Primary Secondary % Referenced to


(_:2311:300) Iunbl.cp Compensated unbalanced kA A Parameter Rated primary
current Iunbal.,comp. current
(_:2311:301) Iunbl. Non-compensated unbal- kA A Parameter Rated primary
anced current Iunbal. current
(_:2311:323) Cp.vect. Compensation vector kA A Parameter Rated primary
Icomp.,vect. current

You can find the value of the parameter Rated primary current of the preceding table in the chapter
6.1.8 Settings according to the specified parameter MP selection.
Icomp.,vect. is normalized with Ic. The normalization is carried out no matter if the parameter Normalization
with Ic is set to yes or no. Icomp.,vect. keeps its value unchanged until the next compensation occurs.

[fo_compensation vector, 1, en_US]

Where:
I unbal.op. Operational unbalanced current at the moment the compensation is carried
out
Ic,rated Rated current of the capacitor bank
Ic Current of the capacitor bank at the moment the compensation is carried
out

Definition of the Group and Fault Location with the Capacitor in H Connection
If the capacitor is designed in an H connection, the following definition is assumed:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1081


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

[dwfehlerortinf_iunsy-020913, 1, en_US]

Figure 7-10 Definition of the Fault-Location Information

The black dot indicates the orientation of the current transformer. For the connection of the current trans-
former shown in the previous figure, the following definition applies:

• Group 1: C1 and C4

• Group 2: C2 and C3
In order to determine the fault location (group 1 or 2) correctly, use the parameter Capacitor element
type (in FB General of the Capacitor bank function group) to tell the device whether the elements of the
capacitor bank have internal fuses or not.
The angle reference of the unbalanced-current phasor to the reference current Ic is used to determine the
direction of the unbalanced current and, thus, the affected group is determined. If the direction cannot be
determined with confidence, an appropriate indication will be generated.

7.4.3.2 Application and Setting Notes

Parameter: MP selection

• Default setting (_:13501:81) MP selection = None


With the MP selection parameter, you can select from a list the measuring point that is connected to the
I Unbalanced interface of the Capacitor bank function group.
The setting applies equally to all stages of the function.
In the default setting, a measuring point is not selected. You must select a measuring point. If you do not
select a measuring point, an inconsistency is indicated via the read-only parameter Consistency failure.

Parameter: Automatic compensation

• Default setting (_:2311:101) Automatic compensation = no


The parameter applies equally to all stages of the function that work with compensated measurands.

1082 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

If no counter stages are applied, Siemens recommends switching the automatic compensation off and using
the manual compensation. You can find more information on this recommendation in chapter 7.4.4.2 Appli-
cation and Setting Notes (setting notes for the operate delay of the I> stage).
If the counter stages are applied, the automatic compensation must be switched on, otherwise the counting
function will not work.

Parameter: De-energ.time w/o comp.

• Default setting (_:2311:104) De-energ.time w/o comp. = 2.00 s


In case of networks faults, the faulty phases are discharged. With the returning voltage after fault clearance,
charging takes place. For such conditions, Siemens recommends that no automatic full compensation takes
place in the affected phases. Otherwise, C-element defects occurring in this period (for example, because of
discharging stress due to network-fault inception) will not be detected.
With the parameter De-energ.time w/o comp., you define the duration of short de-energization after
which no automatic compensation takes place. The parameter must be set to a value larger than the slowest
fault-clearing time in your network plus a safety margin.
If the setting is set to 0 s, an automatic full compensation is carried out after each energizing detection.

Parameter: Normalization with Ic

• Default setting (_:2311:100) Normalization with Ic = no


This parameter applies equally to all stages of the function.
Parameter Value Description
no Select this setting if you can safely assume that Ic will not change for opera-
tional reasons or if you do not desire normalization of the unbalanced
current with Ic.
Please consider that the protection sensitivity will decrease with decreasing
Ic.
yes Select this setting if you want to keep the sensitivity of the protection
stages constant during changes of Ic.

Parameter: Thresh. defective C-elem.

• Default (_:2311:102) Thresh. defective C-elem. = 0.030 A


Set the parameter Thresh. defective C-elem. to ensure that the jump in the unbalanced current
caused by the faulty C-element is detected. Information about occurring unbalanced current as a consequence
of single faulty C-elements will be provided by the manufacturer of the capacitor bank. Siemens recommends
to set the threshold value to approx. 75 % of the unbalanced current that occurs after the fault of the 1st C-
element.

Example 1: Information about the Unbalanced Current Available from the Manufacturer of the Capacitor Bank

Table 7-1 Unbalanced Current, Depending on the Number of Faulty C-Elements

Number of Faulty C-Elements Primary Unbalanced Current


0 0.00 A
1 0.71 A
2 1.47 A
3 2.29 A
... ...

Assumed current transformer ratio: 10 A/1 A


Primary unbalanced current if 1st C-element fails: 0.71 A
Secondary unbalanced current if 1st C-element fails: 0.071 A

SIPROTEC 5, 7SJ82/7SJ85, Manual 1083


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

Secondary setting value: 0.75 ⋅ 0.071 A = 0.053 A

NOTE

i Use sensitive device current inputs in order to apply secondary thresholds of < 30 mA.

If no information is provided by the manufacturer of the capacitor bank, the following example can be used as
a basis in order to determine the value.

Example 2 (a to h): Unbalanced-Current Information Not Available from the Manufacturer of the Capacitor Bank,
External Capacitor-Bank Structure with Cross-Linked Cans
The following consideration applies to one phase.

2a) External Structure of the Capacitor Bank


The external structure of the capacitor bank must be known or must be determined. This information can be
requested from the manufacturer of the capacitor bank.
This example assumes the following external structure of the capacitor bank:
- 28 levels (cans) in series
- 4 cans per level
- H transformer between levels 13 and 14, counting from top to bottom
- 2 parallel cans are always cross-linked, refer to the following diagram

[dwexaufbcb-120314-01, 1, en_US]

Figure 7-11 External Structure of the Capacitor Bank

1084 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

2b) Internal Structure of a Can


The internal structure of a can must be known or must be determined. This information can be requested
from the manufacturer of the capacitor bank.
This example assumes the following internal structure of the can:
- 14 parallel capacitances
- Internal fuses (one internal fuse per capacitance)
- 7 capacitance levels in series

[dwintauka-120314-01, 2, en_US]

Figure 7-12 Internal Structure of a Can

2c) Capacitance of a Can


The capacitance of a can must be known or must be determined. This information can be requested from the
manufacturer of the capacitor bank.

• Capacitance per can: CK = 19.67 μF

2d) Current per Phase


The unbalanced current is derived under the assumption of a certain phase current.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1085


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

In this example, the phase current is determined using the following assumptions and data:

• 1-phase rated capacitance of the capacitor bank: 2.81 μF

• Phase-to-ground voltage of the fundamental component of the capacitor bank: 249.1 kV

• Current per phase: IC = VPh. fund. ⋅ ωC = 249.1 kV ⋅ 2π ⋅ 50 Hz ⋅ 2.81 μF = 219.9 A

2e) Capacitance of a Can during an Element Fault


To do this, the capacitance of an individual C-element will be determined first:

• Capacitance of a C-element:

• Capacitance of a can during an element fault:

CK,1EF = 19.456 μF

2f) Capacitance in the Quarter of the H Connection during an Element Fault


Consider 2 special conditions:

• Cross-linking and therefore the parallel connection of 2 cans, refer to Figure 7-11

• Current transformer is not in the center of the levels


Therefore, the following calculation must be performed for the upper (C1) and lower quarter (C3).

[dw4tlkbnk-120314-01, 1, en_US]

Figure 7-13 Quarters of the Capacitor Bank

Based on the cross-linking of the cans, in case of an element fault, the capacitance of the parallel cans must be
determined first:

• Capacitance of 2 parallel cans in case of an element fault:


C2K,1EF = 19.456 μF + 19.67 μF = 39.126 μF
Capacitance in the quarter of C1 in case of an element fault:

C11EF = 3.0249 μF

1086 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

• Capacitance in the quarter of C3 in case of an element fault:

C31EF = 2.6217 μF

2g) Capacitance in the Quarters of the H Connection without Element Fault

• Capacitance in the quarters of C1 and C3 without element fault:

2h) Unbalanced Current and Threshold-Value Setting in Case of a C-Element Fault

• Unbalanced current:

• Unbalanced current in case of an element fault in C1:

• Unbalanced current in case of an element fault in C3:

The lesser of both values is relevant for the setting of the threshold value. For instance, set the threshold to
75 % of this value:

• Threshold value (primary): 0.75 ⋅ 20.0 mA = 15.0 mA


The threshold is a primary value. In order to detect this, a 1:1 transformer is required. Under this assumption,
the secondary setting value is equal to the primary value.

NOTE

i Use sensitive device current inputs in order to apply secondary thresholds of < 30 mA.

Example 3 (a to d): Unbalanced-Current Information Not Available from the Manufacturer of the Capacitor Bank,
External Capacitor-Bank Structure without Cross-Linked Cans
Example 3 is almost identical to example 2. The only difference is that the cans are not cross-linked. Here, only
the calculation part is discussed that is a result of the different external structure. Information for additional
calculations can be found in example 2.

3a) External Structure of the Capacitor Bank


The external structure of the capacitor bank must be known or must be determined. This information can be
requested from the manufacturer of the capacitor bank.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1087


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

This example assumes the following external structure of the capacitor bank:
- 28 levels (cans) in series
- 4 cans per level
- H transformer between levels 13 and 14, counting from top to bottom
- Parallel cans are not cross-linked, refer to the following diagram

[dwexafbocb-260314-01, 1, en_US]

Figure 7-14 External Structure of the Capacitor Bank

3b) Capacitance in the Quarter of the H Connection during an Element Fault


The current transformer is not located in the center of the levels; therefore, the following calculation for the
upper (C1) and the lower quarter (C3) must be performed.

[dw4tlkbnk-120314-01, 1, en_US]

Figure 7-15 Quarters of the Capacitor Bank

1088 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

• Capacitance in the quarter of C1 in case of an element fault (C11EF):


Capacitance in the row without element fault:

C1RoEF = 1.5130 μF

• Capacitance in the row with element fault:

C1RmEF = 1.5118 μF
C11EF = C1RoEF + C1RmEF = 1.5130 μF + 1.5118 μF = 3.0248 μF

• Capacitance in the quarter of C3 in case of an element fault (C31EF):


Capacitance in the row without element fault:

C3RoEF = 1.3113 μF

• Capacitance in the row with element fault:

C3RmEF = 1.3104 μF
C31EF = C3RoEF + C3RmEF = 1.3113 μF + 1.3104 μF = 2.6217 μF

3c) Capacitance in the Quarters of the H Connection without Element Fault


The values are identical to those values in the example 2g) Capacitance in the Quarters of the H Connection
without Element Fault, Page 1087.

3d) Unbalanced Current and Threshold-Value Setting in Case of a C-Element Fault


Use the values determined under 3b) for those formula listed in example 2h) Unbalanced Current and
Threshold-Value Setting in Case of a C-Element Fault, Page 1087.

Resetting the Counters via Protocols IEC 60870-5-103, IEC 60870-5-104, DNP3, or Modbus
The following example shows how to use a function chart (CFC) to reset the counters with the protocols
IEC 60870-5-103, IEC 60870-5-104, DNP3, or Modbus.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1089


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

EXAMPLE

• Add a Marker command (SPC) signal to the information list.

[sc_add_SPC_signal, 1, en_US]

Figure 7-16 Adding Marker Command (SPC) Signal to Information List

• Set up the following CFC. Connect the SPC signal as input, and the signal >Reset all counters as
output.

[sc_CFC_60C_3ph, 1, en_US]

Figure 7-17 Function Chart (CFC): Activating the Binary Input Signal

• Send a single-point control command from the control center to the SPC signal to activate the signal
>Reset all counters. Then the counters are reset.

7.4.3.3 Settings

Addr. Parameter C Setting Options Default Setting


MP selection
_:13501:100 MP selection:Consistency • no MP configured no MP config-
failure ured
• no Sensor configured

1090 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

Addr. Parameter C Setting Options Default Setting


_:13501:81 MP selection:MP selec- Setting options depend on
tion configuration
General
_:2311:101 General:Automatic • no no
compensation
• yes
_:2311:100 General:Normalization • no no
with Ic
• yes
_:2311:102 General:Thresh. defec- 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
tive C-elem. 5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.150 A
_:2311:104 General:De-energ.time 0.00 s to 60.00 s 2.00 s
w/o comp.

7.4.3.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
General
_:2311:500 General:>Compensate SPS I
_:2311:501 General:>Reset comp. val. SPS I
_:2311:502 General:>Reset all counters SPS I
_:2311:302 General:Alg. not compensated SPS O
_:2311:303 General:Compens. succeeded SPS O
_:2311:304 General:Comp. via BI blk.(Ic<) SPS O
_:2311:305 General:I>-stage(cmp) blk.(Ic<) ACT O
_:2311:306 General:No auto. comp. config. SPS O
_:2311:307 General:C defect counted SPS O
_:2311:308 General:Unknown dir. phase A SPS O
_:2311:309 General:Unknown dir. phase B SPS O
_:2311:310 General:Unknown dir. phase C SPS O
_:2311:311 General:Df. G1 A INS O
_:2311:312 General:Df. G1 B INS O
_:2311:313 General:Df. G1 C INS O
_:2311:314 General:Df. G2 A INS O
_:2311:315 General:Df. G2 B INS O
_:2311:316 General:Df. G2 C INS O
_:2311:300 General:Iunbl.cp WYE O
_:2311:301 General:Iunbl. WYE O
_:2311:323 General:Cp.vect. WYE O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1091


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

7.4.4 Overcurrent-Protection Stage I>

7.4.4.1 Description

Logic of a Stage

[lounbalstufe-020913, 1, en_US]

Figure 7-18 Logic Diagram of the Overcurrent-Protection Stage I>

Measurands
Within the protection stage, the compensated and the non-compensated unbalanced currents are available.
Use the parameter Measured value to select one of the 2 values. Both values are displayed as measured
values of the function at the function stage.

1092 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

Pickup, Tripping Delay


If the selected measurand in one of the phase measuring element exceeds the threshold, the stage picks up.
The pickup starts a tripping time delay, and a fault-location information is issued. More information can be
found in this chapter under Fault-Location Information, Page 1093. If the threshold is exceeded during the
entire tripping delay, a phase-selective operate indication is issued.
Please note that, when using the compensated measurands as well as the automatic compensation, the
currently measured current unbalance (that resulted in the threshold being exceeded) is gradually compen-
sated. This means that even in case of a constantly existing unbalance in the primary system, the compen-
sated measurand becomes gradually lower and may therefore fall below the threshold again at some time.
The timing depends on by how much the threshold is exceeded.
For this reason and under those conditions, long time delays must not be set, see also chapter 7.4.4.2 Applica-
tion and Setting Notes.
This effect does not occur if manual compensation or the non-compensated measurand is used.

Blocking While Charging


In order to prevent pickup as a consequence of the charging process, the I> stage is implicitly blocked in a
phase-selective way for 250 ms by setting Iunbal.,comp. to 0 A, after capacitor energizing has been detected.
Blocking only takes place if the stage operates with compensated unbalanced values.

Fault-Location Information
When picking up, the stage provides information about the faulty group of the capacitor bank. If the location
can be safely determined, the corresponding indication Fault position group 1 or Fault position
group 2 is issued.
Both indications also contain the information about the faulty phase. If the capacitor is implemented as an H
connection, the following definition is assumed:

[dwfehlerortinf_iunsy-020913, 1, en_US]

Figure 7-19 Definition for the Fault-Location Information

SIPROTEC 5, 7SJ82/7SJ85, Manual 1093


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

The black dot indicates the orientation of the current transformer. For the connection of the current trans-
former shown in the previous figure, the following definition applies:

• Group 1: C1 and C4

• Group 2: C2 and C3
In order to determine the fault location (group 1 or 2) correctly, use the parameter Capacitor element
type (in FB General of the Capacitor bank function group) to tell the device whether the elements of the
capacitor bank have internal fuses or not.

Non-Compensated Status
If no compensated values are available and the stage has been set to use such values, the stage will be
blocked. The readiness of the stage turns to Warning. This condition will be reported on the function stage
(indication Alg. not compensated ).

7.4.4.2 Application and Setting Notes

Parameter: Measured value

• Default setting (_:13801:100) Measured value = no


With the parameter, you set the Measured value.
Parameter Value Description
compensated The stage uses compensated unbalanced values. This means an operational
current unbalance will be eliminated. This allows you to significantly
increase the sensitivity of the measurement.
Note the following: If the current Ic is lower than the threshold Current
threshold CB open, the affected phase measuring elements are
rendered inactive by setting Iunbal.,comp. to 0 A. This condition is held for
250 ms after energizing has been detected in order to avoid a pickup as a
consequence of the charging process.
Siemens recommends using compensated unbalanced values. In case that
automatic compensation is applied, please consider the setting notes for
the operate delay.
non-compensated The stage works with non-compensated unbalanced values. This means the
measurand may contain an existing operational current unbalance.

Parameter: Threshold

• Default setting (_:13801:3) Threshold = 0.2 A


Set the parameter Threshold for the specific application.
When using compensated unbalanced values, very sensitive settings are possible. When using non-compen-
sated unbalanced values, the threshold must be higher than the maximum operational unbalanced current.

Parameter: Operate delay

• Default setting (_:13801:6) Operate delay = 0.08 s (for the 1st stage)
Set the parameter Operate delay for the specific application.

NOTE

i If the function has been set to automatic compensation and the stage works with compensated values, the
maximum permitted operate delay is 80 ms. If the operate delay is set to longer than 80 ms, the automatic
compensation might cause dropout of the picked-up stage. This risk does not exist when manual compen-
sation or non-compensated values are used.

1094 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

7.4.4.3 Settings

Addr. Parameter C Setting Options Default Setting


I> 1
_:13801:1 I> 1:Mode • off off
• on
• test
_:13801:2 I> 1:Operate & flt.rec. • no no
blocked
• yes
_:13801:100 I> 1:Measured value • compensated compensated
• non-compensated
_:13801:3 I> 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.000 A
_:13801:6 I> 1:Operate delay 0.00 s to 60.00 s 0.08 s
I> 2
_:13802:1 I> 2:Mode • off off
• on
• test
_:13802:2 I> 2:Operate & flt.rec. • no no
blocked
• yes
_:13802:100 I> 2:Measured value • compensated non-compen-
sated
• non-compensated
_:13802:3 I> 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:13802:6 I> 2:Operate delay 0.00 s to 60.00 s 0.00 s

7.4.4.4 Information List

No. Information Data Class Type


(Type)
I> 1
_:13801:81 I> 1:>Block stage SPS I
_:13801:54 I> 1:Inactive SPS O
_:13801:52 I> 1:Behavior ENS O
_:13801:53 I> 1:Health ENS O
_:13801:55 I> 1:Pickup ACD O
_:13801:56 I> 1:Operate delay expired ACT O
_:13801:57 I> 1:Operate ACT O
_:13801:301 I> 1:Fault position group 1 ACT O
_:13801:302 I> 1:Fault position group 2 ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1095


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

No. Information Data Class Type


(Type)
I> 2
_:13802:81 I> 2:>Block stage SPS I
_:13802:54 I> 2:Inactive SPS O
_:13802:52 I> 2:Behavior ENS O
_:13802:53 I> 2:Health ENS O
_:13802:60 I> 2:Inrush blocks operate ACT O
_:13802:55 I> 2:Pickup ACD O
_:13802:56 I> 2:Operate delay expired ACT O
_:13802:57 I> 2:Operate ACT O
_:13802:301 I> 2:Fault position group 1 ACT O
_:13802:302 I> 2:Fault position group 2 ACT O

1096 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

7.4.5 Counter Stage

7.4.5.1 Description

Logic of a Stage

[lo-cnt-stage-260314-01, 2, en_US]

Figure 7-20 Logic Diagram of the Counter Stage

Measurands/Input Values
The measurand/input values of the counter stage are the phase- and group-segregated counter contents that
are determined in the General FB.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1097


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

Pickup, Tripping Delay


Supervision of the counter contents is phase-segregated. If a counter reaches the preset threshold (parameter
Max. no. of def. elem. phs A , Max. no. of def. elem. phs B , Max. no. of def.
elem. phs C), the stage picks up. When using the parameter Type of counting groups , a selection is
made whether the supervision function occurs group-segregated or with the sum value of both groups. The
pickup starts the time delay. If the time delay has elapsed, the operate indication will be issued.

Automatic Compensation
If the automatic compensation function is enabled, the counter stage is working. If this is not the case, the
readiness status of the stage changes to the state Warning.

7.4.5.2 Application and Setting Notes

General Notes

• The setting notes for the current-threshold value for counting faulty C-elements are provided in chapter
7.4.3.2 Application and Setting Notes as you must set this parameter across all stages.

• In order to react quickly to the simultaneous fault of many C-elements, always use an overcurrent-protec-
tion stage I> with a short tripping delay (< 100 ms) in addition to the counter stage. This is necessary as
the counter function counts each current jump only once, regardless of its height.

Parameter: Type of counting groups

• Default setting (_:13651:104) Type of counting groups = segregated


When using the parameter Type of counting groups, you specify whether the group-segregated
counter status or the sum of both group counters are compared to the threshold.

Parameter: Maximum Number of Faulty Elements, Operate delay

• Default setting (_:13651:101) Max. no. of def. elem. phs A = 10

• Default setting (_:13651:102) Max. no. of def. elem. phs B = 10

• Default setting (_:13651:103) Max. no. of def. elem. phs C = 10

• Default setting(_:13651:6) Operate delay = 0.00 s


Set the parameters for the specific application.
It is possible to configure several stages for different tasks:

• Reporting only (with or without fault record)


Use this stage to report 1 or 2 faulty C-elements. To do this, set the 3 parameters Max. no. of def.
elem. phs A, Max. no. of def. elem. phs B and Max. no. of def. elem. phs C to a
small value (1 or 2). The parameter Operate delay can be set to 0.
If you would like to prevent the operate (tripping) and fault logging (fault log and fault record), set the
parameter Operate & flt.rec. blocked to yes.
If you would like to prevent only the operate (tripping) and the fault logging must occur, remove this
stage from the interface Trip to the circuit breaker (see also 5.4.2 Structure of the Function Group, Inter-
faces with Circuit-Breaker Function Group).

• Indication with delayed operate


Use this stage to report in case of some faulty C-elements and set a relatively long time delay of the
operate, for example, 2 hours. During this time, the fault of the C-elements can be clarified. If it is
possible to find a solution, the counter status can be reset manually. This way, the stage drops out. If a
solution cannot be found within 2 hours, the stage trips and disconnects the capacitor bank.

• Immediate operate
The stage is used to initiate the operate immediately after a larger number of C-elements became faulty.

1098 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase

7.4.5.3 Settings

Addr. Parameter C Setting Options Default Setting


Counter 1
_:13651:1 Counter 1:Mode • off off
• on
• test
_:13651:2 Counter 1:Operate & • no no
flt.rec. blocked
• yes
_:13651:104 Counter 1:Type of • segregated segregated
counting groups
• sum
_:13651:101 Counter 1:Max. no. of 1 to 1000 10
def. elem. phs A
_:13651:102 Counter 1:Max. no. of 1 to 1000 10
def. elem. phs B
_:13651:103 Counter 1:Max. no. of 1 to 1000 10
def. elem. phs C
_:13651:6 Counter 1:Operate delay 0.00 s to 10000.00 s 0.00 s

7.4.5.4 Information List

No. Information Data Class Type


(Type)
Counter 1
_:13651:81 Counter 1:>Block stage SPS I
_:13651:54 Counter 1:Inactive SPS O
_:13651:52 Counter 1:Behavior ENS O
_:13651:53 Counter 1:Health ENS O
_:13651:55 Counter 1:Pickup ACD O
_:13651:56 Counter 1:Operate delay expired ACT O
_:13651:57 Counter 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1099


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

7.5 Current-Unbalance Protection for Capacitors, 1-Phase

7.5.1 Overview of Functions

The Current-unbalance protection for capacitors, 1-phase function (ANSI 60C):

• Protects in case of faults in capacitor elements (C-elements) of a double neutral point capacitor bank

• Provides very sensitive supervision of the unbalanced current between the 2 neutral points

• Allows counting individual faulty C-elements

7.5.2 Structure of the Function

The Current-unbalance protection for capacitors, 1-phase function is used in the Capacitor bank function
group. It is preconfigured at the factory with 2 overcurrent-protection stages I> and 1 stage of the type
Counter. A maximum of 3 overcurrent-protection stages and 4 counter stages can be operated simultaneously
in the function.
The function is designed so that the General functionality (including adjustment) and the Measuring-point
selection can work across the stages.

[dwocpIunb1ph-020714, 3, en_US]

Figure 7-21 Structure/Embedding of the Function

7.5.3 General Functions and Measuring-Point Selection

7.5.3.1 Description

The General functionality is structured in the following functional parts:

• Compensation of the unbalance

• Normalization of the unbalanced current with the current Ic

• Counting faulty C-elements (the stage type Counter is used to monitor the counter status)

1100 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

Logic for Compensation and Normalization

[lo_FBallgiunb1ph-070714-01, 3, en_US]

Figure 7-22 Cross-Stage Functionality

Measuring-Point Selection
With the MP selection parameter, you can select from a list of measuring points a 1-phase measuring point
that is connected to the I Unbalanced interface in the Capacitor bank function group. The Current-unbal-
ance protection for capacitors, 1-phase function processes the 1-phase current that is connected to the
measuring point.
For more information, refer to the description of the Capacitor bank function group starting from chapter
5.4.1 Overview.

Measurands, Method of Measurement


The function receives its measurands via the I Unbalanced interface of the Capacitor bank function group.
The compensated and non-compensated unbalanced currents are provided for the overcurrent-protection
stage. Within the protection stage, one of the 2 values is selected in the protection stage via the parameter
Measured value. Both values are available as functional measured values (see Figure 7-22).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1101


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

Configure across the stages whether the unbalanced current must be normalized with the current Ic that flows
into the capacitor bank. Phase A component of the current Ic flowing into the capacitor bank is used as the
reference for the normalization. You can find more information in this chapter under Normalization with Ic ,
Page 1103.
The method of measurement used processes the sampled unbalanced-current values and filters out the funda-
mental component numerically. The protection stages evaluate the fundamental component of the unbal-
anced current.

General Notes on the Compensation


An operational unbalanced current is added to an unbalanced current resulting from faulty capacitor
elements. This corrupts the measuring result.
Operational unbalanced currents can result from the following causes:

• Manufacturing tolerances of the capacitor

• Aging of the capacitor

• Environmental influences, for example, temperature


The compensation eliminates operational unbalanced currents by calculation. For this purpose, the phasor of
the operational unbalanced current I unbal.,op. is stored at specific times. The stored phasor (compensation
phasor), is subtracted from the actually measured unbalanced-current phasor:

[fo_compensatied unbal., 1, en_US]

The following indications describe the status of the compensation:


Indication Description
Alg. not The algorithm is not compensated. The compensated values are not available under
compensated the following conditions:

• After initial startup of the device before any compensation is carried out
• After activating the binary input >Reset comp. val.
• After change of Irated,obj
Protection stages that are working with compensated values are inactive.
Compens. This indication is issued (as transient indication with a pulse duration of 10 ms) if the
succeeded existing unbalance has been compensated manually or automatically. In case of auto-
matic compensation, the signal is issued at each event-based situation where full
compensation is carried out.
Comp. via BI If a manual compensation has been initiated and the current Ic (current flowing into
blk.(Ic<) the capacitor bank) at this time is less than the threshold Current threshold CB
open, the manual compensation is not executed. This is signaled via the Comp. via
BI blk.(Ic<) indication.

2 different methods are available for the compensation:

• Manual compensation via binary input signals

• Automatic compensation

Manual Compensation via Binary Input Signal


If the binary input signal >Compensate is activated, the manual compensation starts. This will fully compen-
sate any unbalance that exists at this time. This means, the value Iunbal.,comp. will then become 0. You can also
use the manual compensation in parallel with the automatic compensation.
For the reliability of manual compensation, the binary input signal >Compensate has a preset software
filtering time (configurable in DIGIS) of 20 ms.

1102 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

Automatic Compensation
When using the parameter Automatic compensation, this automatic compensation function can be
enabled or disabled.
The automatic compensation consists of 2 different mechanisms:

• Event-based compensation of any existing unbalance


This compensation is performed in the following situations:
– After energizing the capacitor bank or a phase of the bank
– After counting a faulty C-element
– After each startup of the device
– After specific parameter changes:
– Switching on the automatic compensation
– Changing the rated current of the capacitor bank
In order to avoid transient inrush-current effects, the compensation is delayed by 250 ms after energizing
has been detected.
Full compensation after bank energization can be avoided in case of only short de-energization by means
of parameter De-energ.time w/o comp.. If the de-energized duration is less than the setting of
parameter De-energ.time w/o comp., the full compensation is not carried out after energizing a
phase or the whole bank.

• Cyclic, slow and thus gradual compensation of an existing unbalance in small increments
This permits, for example, the automatic compensation of environmental influences.

Resetting the Compensation


The algorithm can be reset to the non-compensated status. Compensated values are not available in this case.
Protection stages that work with compensated values are rendered inactive. The binary input signal >Reset
comp. val. of the function or function group resets the compensation (see also Figure 7-22).
For the reliability of manual compensation, the binary input signal >Reset comp. val. has a preset soft-
ware filtering time (configurable in DIGIS) of 20 ms.

Normalization with Ic

The threshold for the unbalanced current is usually set by assuming the rated capacitor current Ic,rated. The
current Ic flowing into the capacitor bank determines the amount of the unbalanced current. A lower Ic also
means a lower unbalanced current. If Ic < Ic,rated, the protection becomes less sensitive. This influence can be
compensated via the normalization. Normalization keeps the sensitivity of the protection function constant by
normalizing the unbalance value with the current Ic. Phase A component of the current Ic flowing into the
capacitor bank is used as the reference for the normalization. When using the parameter Normalization
with Ic, normalization is enabled or disabled.

Ic Lower than Current Thresh. CB Open

If any phase current of Ic is lower than the threshold Current thresh. CB open, the compensated value
can no longer be computed with sufficient accuracy. To avoid a malfunction, the compensated unbalanced
value Iunbal.,comp. is set to 0 A (see Figure 7-22). This deactivates the protection stages that work with compen-
sated values.
This condition will be indicated (indication I>-stage(cmp) blk.(Ic<)).
In this case, normalization with current Ic will no longer work properly either. Normalization is canceled. This
means that the non-normalized value will be used instead of the normalized value (see Figure 7-22).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1103


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

Charging/Energizing the Capacitor Bank or a Phase of the Bank


Charging of the bank takes place when the discharged bank is switched on to the network. Charging of a
phase can occur in case of network faults. If a phase-to-ground voltage drops to 0 V due to a network fault,
the respective phase is discharged and the return of the phase-to-ground voltage (after the fault has been
cleared) will charge the phase.
Charging the bank causes inrush currents in the respective phases. To avoid overfunction in case of sensitive
threshold settings, the stages using compensated unbalanced values are blocked by setting Iunbal.,comp. to 0 A.
These stages are:

• Counter stage

• I> stage, if set to operate with compensated unbalanced values


The blocking (Iunbal.,comp. set to 0 A) lasts for 250 ms after energizing detection. Afterwards, the calculated
Iunbal.,comp. is processed again.
Energizing detection takes place by monitoring the phases currents Ic flowing into the bank. If all three phase
currents exceed the threshold Current Thresh.CB Open, energizing is detected.

Logic for Counting Faulty C-Elements


This part of the General functionality is only important if counter stages are used.

1104 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

[locntEF1ph-070714-01, 3, en_US]

Figure 7-23 Counting Faulty C-Elements

Activation/Blocking Counting
If at least one counter stage is enabled, the counting function is active. Furthermore, the counting function
works only if the automatic compensation is enabled.
In order to prevent counting as a consequence of the charging process, the counter function is implicitly
blocked for 250 ms by setting Iunbal.,comp. to 0 A, after the capacitor energizing has been detected.

Measurands, Counting
The measurand is the 1-phase compensated unbalanced current Iunbal.,comp.. If a single C-element is faulty, an
unbalance occurs between the neutral points of the 2 capacitor banks. This unbalance causes an unbalanced
current; this means, a small current jump occurs in the unbalanced current. Set the parameter Thresh.
defective C-elem., so that this current jump can be detected (see also 7.5.3.2 Application and Setting
Notes). The unbalanced current that was caused by the fault must exceed the threshold for 100 ms before the
affected phase and the affected group are determined and counting (incrementing the counter) takes place.
The angle reference of the unbalanced-current phasor to the reference current Ic,A is used to determine the
phase of the faulty C element. Thus, phase-segregated counting is possible. There is one counter for each

SIPROTEC 5, 7SJ82/7SJ85, Manual 1105


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

phase and group. After the counting, the existing unbalance is compensated; this means, the unbalance is
reset to 0 A. If the faulty group cannot be determined, the unbalance is also compensated.

Resetting/Setting the Counters


You can reset or set the counters of group 1 and group 2 via:

• On-site operation panel directly on the device

• Online DIGSI connection to the device

• Binary input >Reset all counters (only reset of all counters)

• Communication connection with the control center


You can directly set or reset the counters via IEC 61850 by setting the counter values to the desired value. If
you want to reset the counters via DNP3, IEC 60870-5-103, Modbus, or IEC 60870-5-104, an additional config-
uration with CFC is necessary. For more information, refer to chapter 7.5.3.2 Application and Setting Notes.

Functional Measured Values

Values Description Primary Secondary % Referenced to


(_:2311:300) Iunbl.cp Compensated unbalanced kA A Parameter Rated primary
current Iunbal.,comp. current
(_:2311:301) Iunbl. Non-compensated unbal- kA A Parameter Rated primary
anced current Iunbal. current
(_:2311:323) Cp.vect. Compensation vector Icomp.,vect. kA A Parameter Rated primary
current

You can find the value of the parameter Rated primary current of the preceding table in the chapter
6.1.8 Settings according to the specified parameter MP selection.
Icomp.,vect. is normalized with Ic. The normalization is carried out no matter if the parameter Normalization
with Ic is set to yes or no. Icomp.,vect. keeps its value unchanged until the next compensation occurs.

[fo_compensation vector, 1, en_US]

Where:
I unbal.op. Operational unbalanced current at the moment the compensation is carried out
Ic,rated Rated current of the capacitor bank
Ic Current of the capacitor bank at the moment the compensation is carried out

Definition of the Group and Fault Location in Case of a Capacitor Dual Switching
If the capacitor is designed with dual switching function, the following definition is assumed:

1106 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

[dwfehlerortinf_iunsy1ph-070714-01, 1, en_US]

Figure 7-24 Definition of the Fault-Location Information

The black dot indicates the orientation of the current transformer. For the connection of the current trans-
former shown in the previous figure, the following definition applies:

• Group 1: C1

• Group 2: C2
In order to determine the fault location (group 1 or 2) correctly, use the parameter Capacitor element
type (in FB General of the Capacitor bank function group) to tell the device whether the elements of the
capacitor bank have internal fuses or not.
The angle reference of the unbalanced-current phasor to the reference current Ic is used to determine the
direction of the unbalanced current and, thus, the affected group is determined. If the direction cannot be
determined with confidence, an appropriate indication will be generated.

7.5.3.2 Application and Setting Notes

Parameter: MP selection

• Default setting (_:13501:81) MP selection = None


With the MP selection parameter, you can select from a list the measuring point that is connected to the
I Unbalanced interface of the Capacitor bank function group.
The setting applies equally to all stages of the function.
In the default setting, a measuring point is not selected. You must select a measuring point. If you do not
select a measuring point, an inconsistency is indicated via the read-only parameter Consistency failure.

Parameter: Automatic compensation

• Default setting (_:2311:101) Automatic compensation = no


The parameter applies equally to all stages of the function that work with compensated measurands.
If no counter stages are applied, Siemens recommends to switch the automatic compensation off and use the
manual compensation. You can find more information on this recommendation in chapter 7.5.4.2 Application
and Setting Notes (setting notes for the operate delay of the I> stage).
If the counter stages are applied, the automatic compensation must be switched on, otherwise the counting
function will not work.

Parameter: De-energ.time w/o comp.

• Default setting (_:2311:104) De-energ.time w/o comp. = 2.00 s


In case of networks faults, the faulty phases are discharged. With the returning voltage after fault clearance,
charging takes place. For such conditions, Siemens recommends that no automatic full compensation takes
place in the affected phases. Otherwise, C-element defects occurring in this period (for example, because of
discharging stress due to network-fault inception) will not be detected.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1107


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

With the parameter De-energ.time w/o comp., you define the duration of short de-energization after
which no automatic compensation takes place. The parameter must be set to a value larger than the slowest
fault clearing time in your network plus a safety margin.
If the setting is set to 0 s, an automatic full compensation is carried out after each energizing detection.

Parameter: Normalization with Ic

• Default setting (_:2311:100) Normalization with Ic = no


This parameter applies equally to all stages of the function.
Parameter Value Description
no Select this setting if you can safely assume that Ic will not change for opera-
tional reasons or if you do not desire normalization of the unbalanced
current with Ic.
Please consider that the protection sensitivity will decrease with decreasing
Ic.
yes Select this setting if you want to keep the sensitivity of the protection
stages constant during changes of Ic.

Parameter: Thresh. defective C-elem.

• Default setting (_:2311:102) Thresh. defective C-elem.= 0.030 A


Set the parameter Thresh. defective C-elem. to ensure that the jump in the unbalanced current
caused by the faulty C-element is detected. Information about occurring unbalanced current as a consequence
of single faulty C-elements will be provided by the manufacturer of the capacitor bank. Siemens recommends
to set the threshold value to approx. 75 % of the unbalanced current that occurs after the fault of the 1st C-
element.

Example 1: Information about the Unbalanced Current Available from the Manufacturer of the Capacitor Bank

Table 7-2 Unbalanced Current, Depending on the Number of Faulty C-Elements

Number of Faulty C-Elements Primary Unbalanced Current


0 0.00 A
1 0.71 A
2 1.47 A
3 2.29 A
... ...

Assumed current transformer ratio: 10 A/1 A


Primary unbalanced current if 1st C-element fails: 0.71 A
Secondary unbalanced current if 1st C-element fails: 0.071 A
Secondary setting value: 0.75 ⋅ 0.071 A = 0.053 A

NOTE

i Use senstive device current inputs in order to apply secondary thresholds of < 30 mA.

Resetting the Counters via Protocols IEC 60870-5-103, IEC 60870-5-104, DNP3, or Modbus
The following example shows how to use a function chart (CFC) to reset the counters with the protocols
IEC 60870-5-103, IEC 60870-5-104, DNP3, or Modbus.

1108 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

EXAMPLE

• Add a Marker command (SPC) signal to the information list.

[sc_add_SPC_signal_1ph, 1, en_US]

Figure 7-25 Adding Marker Command (SPC) Signal to Information List

• Set up the following CFC. Connect the SPC signal as input, and the signal >Reset all counters as
output.

[sc_CFC_60C_1ph, 1, en_US]

Figure 7-26 Function Chart (CFC): Activating the Binary Input Signal

• Send a single-point control command from the control center to the SPC signal to activate the signal
>Reset all counters. Then the counters are reset.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1109


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

7.5.3.3 Settings

Addr. Parameter C Setting Options Default Setting


MP selection
_:13501:100 MP selection:Consistency • no MP configured no MP config-
failure ured
• no Sensor configured
_:13501:81 MP selection:MP selec- Setting options depend on
tion configuration
General
_:2311:101 General:Automatic • no no
compensation
• yes
_:2311:100 General:Normalization • no no
with Ic
• yes
_:2311:102 General:Thresh. defec- 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
tive C-elem. 5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.150 A
_:2311:104 General:De-energ.time 0.00 s to 60.00 s 2.00 s
w/o comp.

7.5.3.4 Information List

No. Information Data Class Type


(Type)
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
General
_:2311:500 General:>Compensate SPS I
_:2311:501 General:>Reset comp. val. SPS I
_:2311:502 General:>Reset all counters SPS I
_:2311:302 General:Alg. not compensated SPS O
_:2311:303 General:Compens. succeeded SPS O
_:2311:304 General:Comp. via BI blk.(Ic<) SPS O
_:2311:305 General:I>-stage(cmp) blk.(Ic<) SPS O
_:2311:306 General:No auto. comp. config. SPS O
_:2311:307 General:C defect counted SPS O
_:2311:308 General:Unknown dir. phase A SPS O
_:2311:309 General:Unknown dir. phase B SPS O
_:2311:310 General:Unknown dir. phase C SPS O
_:2311:311 General:Df. G1 A INS O
_:2311:312 General:Df. G1 B INS O
_:2311:313 General:Df. G1 C INS O
_:2311:314 General:Df. G2 A INS O
_:2311:315 General:Df. G2 B INS O
_:2311:316 General:Df. G2 C INS O
_:2311:300 General:Iunbl.cp CMV O
_:2311:301 General:Iunbl. CMV O

1110 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

No. Information Data Class Type


(Type)
_:2311:323 General:Cp.vect. CMV O

7.5.4 Overcurrent-Protection Stage I>

7.5.4.1 Description

Logic of a Stage

[lounbalstu1ph-080714-01, 1, en_US]

Figure 7-27 Logic Diagram of the Overcurrent-Protection Stage I>

Measurands
Within the protection stage, the compensated and the non-compensated unbalanced currents are available.
Use parameter Measured value to select one of the 2 values. Both values are displayed as measured values
of the function at the function stage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1111


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

Pickup, Operate Delay


If the selected measurand exceeds the threshold, the stage picks up. The pickup starts the operate delay, and a
fault-location information is issued. More information can be found in this chapter under Fault-Location Infor-
mation, Page 1112. If the threshold is exceeded during the entire operate delay, the operate indication is
issued.
Please note that, when using the compensated measurands as well as the automatic compensation, the
currently measured current unbalance (that resulted in the threshold being exceeded) is gradually compen-
sated. This means that even in case of a constantly existing unbalance in the primary system, the compen-
sated measurand becomes gradually lower and may therefore fall below the threshold again at some time.
The timing depends on by how much the threshold is exceeded.
For this reason and under those conditions, long time delays must not be set, see also chapter 7.5.4.2 Applica-
tion and Setting Notes.
This effect does not occur if manual compensation or the non-compensated measurand is used.

Blocking While Charging


In order to prevent pickup as a consequence of the charging process, the I> stage is implicitly blocked for
250 ms by setting Iunbal.,comp. to 0 A, after capacitor energizing has been detected. Blocking only takes place if
the stage operates with compensated unbalanced values.

Fault-Location Information
When picking up, the stage provides information about the faulty group of the capacitor bank. If the location
can be safely determined, the corresponding indication Fault position group 1 or Fault position
group 2 is issued.
Both indications also contain the information about the faulty phase. If the capacitor is implemented with
2 neutral points, the following definition is assumed:

[dwfehlerortinf_iunsy1ph-070714-01, 1, en_US]

Figure 7-28 Definition for the Fault-Location Information

The black dot indicates the orientation of the current transformer. For the connection of the current trans-
former shown in the previous figure, the following definition applies:

• Group 1: C1

• Group 2: C2
In order to determine the fault location (group 1 or 2) correctly, use the parameter Capacitor element
type (in FB General of the Capacitor bank function group) to tell the device whether the elements of the
capacitor bank have internal fuses or not.

Non-Compensated Status
If no compensated values are available and the stage has been set to use such values, the stage will be
blocked. The readiness of the stage turns to Warning. This condition will be reported on the function stage
(indication Alg. not compensated ).

1112 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

7.5.4.2 Application and Setting Notes

Parameter: Measured value

• Default setting (_:16231:100) Measured value = compensated


With this parameter you set the Measured value .
Parameter Value Description
compensated The stage uses compensated unbalanced values. This means an operational
current unbalance will be eliminated. This allows you to increase signifi-
cantly the sensitivity of the measurement.
Note: If any phase current Ic is lower than the threshold Current
threshold CB open, the stage is rendered inactive by setting Iunbal.,comp.
to 0 A. This condition is held for 250 ms after energizing has been detected
in order to avoid a pickup as a consequence of the charging process.
Siemens recommends using compensated unbalanced values. In case that
automatic compensation is applied, consider the setting notes for the
operate delay.
non-compensated The stage works with non-compensated unbalanced values. This means the
measurand may contain an existing operational current unbalance.

Parameter: Threshold

• Default setting (_:16231:3) Threshold = 1.500 A


Set the parameter Threshold for the specific application.
When using compensated unbalanced values, very sensitive settings are possible. When using non-compen-
sated unbalanced values, the threshold must be higher than the maximum operational unbalanced current.

Parameter: Operate delay

• Default setting (_:16231:6) Operate delay = 0.30 s (for the 1st stage)
Set the parameter Operate delay for the specific application.

NOTE

i If the function has been set to automatic compensation and the stage works with compensated values, the
maximum permitted operate delay is 80 ms. If the operate delay is set to longer than 80 ms the automatic
compensation might cause dropout of the picked-up stage. This risk does not exist when manual compen-
sation or non-compensated values are used.

7.5.4.3 Settings

Addr. Parameter C Setting Options Default Setting


I> 1
_:16231:1 I> 1:Mode • off off
• on
• test
_:16231:2 I> 1:Operate & flt.rec. • no no
blocked
• yes
_:16231:100 I> 1:Measured value • compensated compensated
• non-compensated

SIPROTEC 5, 7SJ82/7SJ85, Manual 1113


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

Addr. Parameter C Setting Options Default Setting


_:16231:3 I> 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.000 A
_:16231:6 I> 1:Operate delay 0.00 s to 60.00 s 0.08 s

7.5.4.4 Information List

No. Information Data Class Type


(Type)
I> 1
_:16231:81 I> 1:>Block stage SPS I
_:16231:54 I> 1:Inactive SPS O
_:16231:52 I> 1:Behavior ENS O
_:16231:53 I> 1:Health ENS O
_:16231:55 I> 1:Pickup ACD O
_:16231:56 I> 1:Operate delay expired ACT O
_:16231:57 I> 1:Operate ACT O
_:16231:301 I> 1:Fault position group 1 ACT O
_:16231:302 I> 1:Fault position group 2 ACT O

1114 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

7.5.5 Counter Stage

7.5.5.1 Description

Logic of a Stage

[lo-cnt-stage1ph-080714-01, 2, en_US]

Figure 7-29 Logic Diagram of the Counter Stage

SIPROTEC 5, 7SJ82/7SJ85, Manual 1115


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

Measurands/Input Values
The measurand/input values of the counter stage are phase-segregated and group-segregated counter
contents that are determined in the General FB.

Pickup, Operate Delay


With the parameter Type of counting phases, a selection is made whether the supervision function
occurs in a phase-segregated way or with the sum value of the phases. With the parameter Type of
counting groups, a selection is made whether the supervision function occurs in a group-segregated way
or with the sum value of both groups. If a counter reaches the set threshold, the stage picks up. The pickup
starts the time delay. If the time delay has elapsed, the operate indication will be issued.

Automatic Compensation
If the automatic compensation function is enabled, the counter stage is working. If this is not the case, the
readiness status of the stage changes to the state Warning.

7.5.5.2 Application and Setting Notes

General Notes

• The setting notes for the current-threshold value for counting faulty C-elements are provided in chapter
7.5.3.2 Application and Setting Notes as you must set this parameter across all stages.

• In order to react quickly to the simultaneous fault of many C-elements, always use an overcurrent-protec-
tion stage I> with a short operate delay (< 100 ms) in addition to the counter stage. This is necessary as
the counter function counts each current jump only once, regardless of its height.

Parameter: Type of counting groups

• Default setting (_:16261:101) Type of counting groups = segregated


With the parameter Type of counting groups, you specify whether the group-segregated counter status
or the sum value of both group counters are compared to the threshold.

Parameter: Type of counting phases

• Default setting (_:16261:102) Type of counting phases = segregated


With the parameter Type of counting phases, you specify whether the supervision function occurs in a
phase-segregated way or with the sum value of the phases.

Parameter: Maximum Number of Faulty Elements, Operate delay

• Default setting (_:16261:103) Max. no. of def. elem. phs A = 10

• Default setting (_:16261:104) Max. no. of def. elem. phs B = 10

• Default setting (_:16261:105) Max. no. of def. elem. phs C = 10

• Default setting (_:16261:106) Max. no. of def. elem. = 10

• Default setting (_:16261:6) Operate delay = 0.00 s


Set the parameters for the specific application.

1116 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

It is possible to configure several stages for different tasks:

• Reporting only (with or without fault record)


Use this stage to report 1 or 2 faulty C-elements. To do this, set the parameters Max. no. of def.
elem. phs A, Max. no. of def. elem. phs B , Max. no. of def. elem. phs C , or
Max. no. of def. elem. to a small value (1 or 2). The parameter Operate delay can be set to 0.
If you would like to prevent the operate (tripping) and fault logging (fault log and fault record), set the
parameter Operate & flt.rec. blocked to yes.
If you would like to prevent only the operate (tripping) and the fault logging must occur, remove this
stage from the interface Trip to the circuit breaker (see also 5.4.2 Structure of the Function Group Inter-
faces with Circuit-Breaker Function Group).

• Indication with delayed operate


Use this stage to report in case of some faulty C-elements and to set a relatively long time delay of the
operate, for example, 2 hours. During this time, the fault of the C-elements can be clarified. If it is
possible to find a solution, the counter status can be reset manually. This way, the stage drops out. If a
solution cannot be found within 2 hours, the stage trips and disconnects the capacitor bank.

• Immediate operate
The stage is used to initiate the operate immediately after a larger number of C-elements became faulty.

7.5.5.3 Settings

Addr. Parameter C Setting Options Default Setting


Counter 1
_:16261:1 Counter 1:Mode • off off
• on
• test
_:16261:2 Counter 1:Operate & • no no
flt.rec. blocked
• yes
_:16261:101 Counter 1:Type of • segregated segregated
counting groups
• sum
_:16261:102 Counter 1:Type of • segregated segregated
counting phases
• sum
_:16261:103 Counter 1:Max. no. of 1 to 1000 10
def. elem. phs A
_:16261:104 Counter 1:Max. no. of 1 to 1000 10
def. elem. phs B
_:16261:105 Counter 1:Max. no. of 1 to 1000 10
def. elem. phs C
_:16261:106 Counter 1:Max. no. of 1 to 1000 10
def. elem.
_:16261:6 Counter 1:Operate delay 0.00 s to 10000.00 s 0.00 s

7.5.5.4 Information List

No. Information Data Class Type


(Type)
Counter 1
_:16261:81 Counter 1:>Block stage SPS I
_:16261:54 Counter 1:Inactive SPS O
_:16261:52 Counter 1:Behavior ENS O
_:16261:53 Counter 1:Health ENS O
_:16261:55 Counter 1:Pickup ACD O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1117


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase

No. Information Data Class Type


(Type)
_:16261:56 Counter 1:Operate delay expired ACT O
_:16261:57 Counter 1:Operate ACT O

1118 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

7.6 Peak Overvoltage Protection for Capacitors

7.6.1 Overview of Functions

The Peak overvoltage protection for capacitors (ANSI 59C) function protects capacitors against:

• Peak overvoltages that stress the dielectric medium in the capacitor causing accelerated aging

• Peak overvoltages that in extreme cases can destroy the dielectric medium in the capacitor

7.6.2 Structure of the Function

The Peak overvoltage protection for capacitors function can be applied in the Capacitor bank function
group.
3 types of stages are available:

• Stage with inverse-time characteristic curve according to IEC and IEEE Standards

• Stage with definite-time characteristic curve

• Stage with user-defined characteristic curve


The function is preconfigured at the factory with a stage having an inverse-time characteristic curve and a
stage having a definite-time characteristic curve.
Within the function, the following maximum number of stages can be operated simultaneously:

• 1 stage with an inverse-time characteristic curve

• 4 stages with a definite-time characteristic curve

• 1 stage with a user-defined characteristic curve

[dw_strpea-230813, 3, en_US]

Figure 7-30 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 1119


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

7.6.3 Stage with Inverse-Time Characteristic Curve

7.6.3.1 Description

Logic of the Stage

[lo_peainv-230813, 2, en_US]

Figure 7-31 Logic Diagram of the Stage with Inverse-Time Characteristic Curve

1120 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

(1) With down integration time


(2) With dropout delay

Measurand, Method of Measurement


The function calculates the peak voltage in a phase-segregated way from the fundamental component and
superimposed harmonics. Integration of the phase currents then yields the voltage. This approach captures
the higher harmonics considerably better since they are transferred better by current transformers than by
voltage transformers.
The peak voltage determined is then set with reference to the rated voltage of the capacitor. The resulting
measurand is Û/VC-rated(t). The threshold value for the stage is thus set as a referenced quantity.
The phase-selective peak overvoltages Û/VC-rated(t) are available as measured values for display or further
processing.

Pickup, Tripping and Dropout Behavior with the Inverse-Time Characteristic Curve
If the measurand Û/VC-rated(t) exceeds 1.045 times the set threshold value (for example, 1.045 × 1.1 ≈ 1.15),
pickup occurs and the inverse-time characteristic curve is then followed. For each input value that exceeds the
pickup value (1.045 × threshold value), the time value Ttrip is calculated. An integrator accumulates the value
1/ Ttrip. When the accumulated integral reaches the fixed value of 1, the stage trips.
If the measurand falls below 1.045 times the set threshold value (pickup value), processing of the character-
istic (accumulation of the time values) stops. In the hysteresis region between the pickup value and dropout
value (95 % of the pickup value, for example, 0.95 × 1.15 = 1.0925), the integral value remains unchanged.
The stage, however, remains in the picked-up state.
Use the parameter Dropout principle to select the method for the dropout of the stage:

• Method with down integration time:


If the measurand falls below the dropout threshold, the pickup drops out immediately. If the value drops
below the pickup threshold, the internal integral value that depends on the selected Down integra-
tion time is slowly reduced. The Down integration time defines the duration in order to reduce
the internal integral value linear from 100 % to 0 %. The internal integral value is limited to 100 % and is
reached with the tripping function.

• Method with dropout delay:


If the measurand falls below the dropout threshold, the pickup drops not out immediately. The pickup
remains for the duration of the set Dropout principle . The integral value remains frozen during
this time. If the pickup value is not exceeded again during this time, a dropout occurs and the integral
value is reset to 0. If the pickup value is exceeded during this time again, the integrator continues with
the integration of frozen values. The pickup remains active and the Dropout principle is reset.

Inverse-Time Characteristic Curve


The characteristic curve is defined by the Standards IEC 60871-1:2005 and IEEE Std 1036-2010, see
Figure 7-32.
The points on the characteristic curve defined in the standards result from a threshold setting of 1.1.
Threshold values differing from this value shift the characteristic as shown in Figure 7-32.
Straight-line segments are implemented between the defined points on semi-logarithmic coordinates.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1121


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

[dw_pecinv-230813, 2, en_US]

Figure 7-32 Inverse-Time Characteristic Curve

Phase-Segregated Operate Indications


In contrast to what normally occurs in a 3-phase protection device, the function generates phase-segregated
operate indications. These indications are needed for supervision applications.

Function Values

Values Description Primary Secondary % Referenced to


(_:2311:301) VpeakA Peak voltage phase A kV V Parameter Capacitor
reference volt./√3
(_:2311:302) VpeakB Peak voltage phase B kV V Parameter Capacitor
reference volt./√3
(_:2311:303) VpeakC Peak voltage phase C kV V Parameter Capacitor
reference volt./√3

You can find the parameter Capacitor reference volt. of the preceding table in the function block
General of the function group Capacitor bank.

7.6.3.2 Application and Setting Notes

Parameter: Capacitor rated current

• Default setting (_:2311:101) Capacitor rated current = 1000.0 A


With the Capacitor rated current parameter, you set the primary rated current IC-rated of the capacitor
or the capacitor bank.
Keep in mind that the rated current of the capacitor considers harmonics in addition to the fundamental
component.

1122 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

The rated current IC-rated is determined from the rated capacity and the rated voltage across the bank. Both
values are listed in the Technical Data for the capacitor. Take note of the following:

• The rated voltage for the capacitor also takes harmonics into account. This is not the rated voltage of the
system.

• The rated voltage to be used is the voltage applied across the capacitor; depending on the application,
this can be a phase-to-phase or phase-to-ground voltage.

Example: Determining the Capacitor Rated Current for a Capacitor in a Star Connection

[dw_UC-Y-Schalt-110813, 1, en_US]

Figure 7-33 Capacitor in Star Connection

Rated voltage of the system 220 kV


Rated capacity per phase 5.233 µF
Capacitor rated voltage VC-rated 192.30 kVrms
Rated frequency f 50 Hz

IC-rated = ωC × UC-rated = 2πf × C × UC-rated = 2 π 50 × 5.233 10-6 × 192.3 103 [Hz × F × U] = 316.1 [A]

Parameter: Threshold

• Default setting (_:13861:3) Threshold = 1.10


The peak voltage determined is then set with reference to the rated voltage of the capacitor. The threshold
value is thus set as a referenced quantity.
The points on the characteristic curve defined in the Standards IEC 60871-1:2005 and IEEE Std 1036-2010
result from a threshold setting of 1.10 (see Figure 7-32). Threshold values differing from this shift the charac-
teristic as shown in Figure 7-32.
Siemens recommends using the default setting.

Parameter: Dropout principle

• Default setting (_:13861:103) Dropout principle = with down integration


Use the parameter Dropout principle to select the method for the dropout of the stage:
Parameter Value Description
with down integra- If the measurand for the dropout threshold falls below the limit, the pickup
tion drops out immediately.
If the value drops below the pickup threshold, the internal integral value that
depends on the selected down integration time is reduced from 100 % to 0 %
with dropout delay If the measurand falls below the dropout threshold, the measurand remains
active for the duration of the preset dropout delay. The integral value remains
frozen during this time.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1123


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

Parameter: Down integration time

• Default setting (_:13861:102) Down integration time = 3.00 min


Use the parameter Down integration time in order to determine the duration until the internal integra-
tion value is linearly reduced from 100 % to 0 %.
For example, if the integration value is 52 %, a duration of 52 % × down integration time is required until the
integration value 0 % is reached. When using this parameter, the preloading of a capacitor can be considered
and therefore released quicker.
If you are knowledgeable about recovery time of stressed capacitors, they can be considered with this param-
eter.

Parameter: Dropout delay

• Default setting (_:13861:7) Dropout delay = 1.00 s


The parameter Dropout delay can be used to prevent resetting of the integral value in the event that the
measured value briefly falls below the dropout threshold.

7.6.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Capacitor rated 1.0 A to 100000.0 A 1000.0 A
current
Inverse-T 1
_:13861:1 Inverse-T 1:Mode • off off
• on
• test
_:13861:2 Inverse-T 1:Operate & • no no
flt.rec. blocked
• yes
_:13861:103 Inverse-T 1:Dropout prin- • with dropout delay with down inte-
ciple gration
• with down integration
_:13861:3 Inverse-T 1:Threshold 0.80 p.u. to 3.00 p.u. 1.10 p.u.
_:13861:102 Inverse-T 1:Down inte- 1 min to 1500 min 3 min
gration time
_:13861:7 Inverse-T 1:Dropout 0.00 s to 3600.00 s 1.00 s
delay

7.6.3.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:301 General:VpeakA MV O
_:2311:302 General:VpeakB MV O
_:2311:303 General:VpeakC MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:13861:81 Inverse-T 1:>Block stage SPS I
_:13861:54 Inverse-T 1:Inactive SPS O
_:13861:52 Inverse-T 1:Behavior ENS O

1124 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

No. Information Data Class Type


(Type)
_:13861:53 Inverse-T 1:Health ENS O
_:13861:55 Inverse-T 1:Pickup ACD O
_:13861:301 Inverse-T 1:Down integr. running SPS O
_:13861:56 Inverse-T 1:Operate delay expired ACT O
_:13861:57 Inverse-T 1:Operate ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1125


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

7.6.4 Stage with Definite-Time Characteristic Curve

7.6.4.1 Description

Logic of the Stage

[lo_peadef-230813, 1, en_US]

Figure 7-34 Logic Diagram of the Stage with Definite-Time Characteristic Curve

Measurand, Method of Measurement


The function calculates the peak voltage in a phase-segregated way from the fundamental component and
superimposed harmonics. Integration of the phase currents then yields the voltage. This approach captures

1126 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

the higher harmonics considerably better since they are transferred better by current transformers than by
voltage transformers.
The peak voltage determined is then set with reference to the rated voltage of the capacitor. The resulting
measurand is Û/VC-rated(t). The threshold value for the stage is thus set as a referenced quantity.
The phase-segregated peak overvoltages Û/VC-rated(t) are available as measured values for display or further
processing.

Pickup, Tripping and Dropout Behavior with the Definite-Time Characteristic Curve
If the measurand Û/VC-rated(t) exceeds the set threshold value, pickup occurs and the tripping delay starts. If the
measurand remains above the dropout value (95 % of the threshold value) during the tripping delay, the stage
trips.

Phase-Segregated Operate Indications


In contrast to what normally occurs in a 3-phase protection device, the function generates phase-segregated
operate indications. These indications are needed for supervision applications.

Function Values
For the detailed information of the function values, refer to Function Values, Page 1122.

7.6.4.2 Application and Setting Notes

Parameter: Capacitor rated current

• Default setting (_:2311:101) Capacitor rated current = 1000.0 A


You can find the setting notes for the parameter Capacitor rated current under Parameter: Capac-
itor rated current, Page 1122.

Parameter: Threshold

• Default setting (_:13831:3) Threshold = 1.10


The peak voltage determined is then set with reference to the rated voltage of the capacitor. The Threshold
is thus set as a referenced quantity.
The setting depends on the application of the stage. If this stage is intended to operate as a warning stage, a
very sensitive setting of approx. 1.05 can be selected. If the stage is used for instantaneous tripping in addi-
tion to the stage with inverse-time characteristic curve, Siemens recommends a setting of ≥ 3.00.

Parameter: Operate delay

• Default setting (_:13831:6) Operate delay = 3.00 s


The setting depends on the application of the stage. If this stage is intended to operate as a warning stage, the
time delay can be selected in a range of seconds. If the stage is used for instantaneous tripping in addition to
the stage with inverse-time characteristic curve, the Operate delay can be set to 0.00 s.

7.6.4.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:Capacitor rated 1.0 A to 100000.0 A 1000.0 A
current
Definite-T 1
_:13831:1 Definite-T 1:Mode • off off
• on
• test

SIPROTEC 5, 7SJ82/7SJ85, Manual 1127


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

Addr. Parameter C Setting Options Default Setting


_:13831:2 Definite-T 1:Operate & • no no
flt.rec. blocked
• yes
_:13831:3 Definite-T 1:Threshold 0.80 p.u. to 10.00 p.u. 5.00 p.u.
_:13831:6 Definite-T 1:Operate 0.01 s to 3600.00 s 0.03 s
delay

7.6.4.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:301 General:VpeakA MV O
_:2311:302 General:VpeakB MV O
_:2311:303 General:VpeakC MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:13831:81 Definite-T 1:>Block stage SPS I
_:13831:54 Definite-T 1:Inactive SPS O
_:13831:52 Definite-T 1:Behavior ENS O
_:13831:53 Definite-T 1:Health ENS O
_:13831:55 Definite-T 1:Pickup ACD O
_:13831:56 Definite-T 1:Operate delay expired ACT O
_:13831:57 Definite-T 1:Operate ACT O

7.6.5 Stage with User-Defined Characteristic Curve

7.6.5.1 Description
This stage is structured the same way as the stage with a voltage-dependent characteristic (see chapter
7.6.3.1 Description). The only difference is that you can define the characteristic curve as desired. This means
that you can also define a dropout characteristic curve. This makes the dropout delay parameter superfluous
and unneeded.

User-Defined Characteristic Curve


With the user-defined characteristic curve, you can define the operate curve point by point using up to 30
value pairs of voltage and time. The device uses linear interpolation to calculate the characteristic curve from
these values. You can also define a dropout characteristic curve if you wish.

Pickup and Dropout Behavior with the User-Defined Characteristic Curve


If the measurand Û/VC-rated(t) exceeds the threshold value, the characteristic is followed. An integrating
method of measurement summarizes the weighted time. The weighted time results from the characteristic
curve. This means that the time associated with the present measured value is determined from the character-
istic curve. Once the weighted time exceeds the value 1, the stage operates.
If the measured value falls below 95 % of the set threshold value, the dropout is initiated. The pickup will be
indicated as clearing. The weighted time results from the dropout characteristic curve. The integral value is
reduced until it reaches 0.

1128 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

[dw_pecuse-230813, 2, en_US]

Figure 7-35 Pickup Behavior and Dropout Behavior when Using a User-Defined Characteristic Curve

7.6.5.2 Application and Setting Notes


This stage is structured the same way as the stage with a inverse-time characteristic (see chapter
7.6.3.2 Application and Setting Notes). The only difference is that you can define the characteristic curve as
desired. This chapter provides only application and setting notes for setting characteristic curves.

Parameter: Voltage/Time Value Pairs (from the Operate Curve)


Use these settings to define the characteristic curve. Set a voltage/time value pair for each point on the charac-
teristic curve. The setting depends on the characteristic curve you want to realize.
Set the voltage to a multiple of the threshold value. In order to obtain a simple relation, Siemens recommends
setting the Threshold parameter to 1.00. You can change the threshold value setting afterwards if you
want to shift the characteristic curve.
Set the time value in seconds. The characteristic curve is shifted via the Time dial parameter.
Set the number of value pairs to be used with DIGSI. You can define a maximum of 30 value pairs.

NOTE

i The value pairs must be entered in continuous order.

Parameter: Time dial

• Default setting (_:101) Time dial = 1


Use the Time dial parameter to displace the characteristic curve in the time direction.
Where no time grading of tripping and thus no shifting of the characteristic curve is required, leave the param-
eter Time dial at 1.

Parameter: Voltage/Time Value Pairs (from the Dropout Characteristic Curve)


Use these settings to define the characteristic curve. Set a voltage/time value pair for each point on the charac-
teristic curve. The setting depends on the characteristic curve you want to realize.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1129


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors

Set the voltage to a multiple of the threshold value. Siemens recommends setting the Threshold parameter
to 1.00 in order to obtain a simple relation. You can change the threshold value afterwards if you want to
shift the characteristic curve.
Set the time value in seconds. The characteristic curve is shifted via the Time dial parameter.
Set the number of value pairs to be used with DIGSI. You can define a maximum of 30 value pairs.

NOTE

i The value pairs must be entered in continuous order.

7.6.5.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 User curve #:Mode • off off
• on
• test
_:2 User curve #:Operate & • no no
flt.rec. blocked
• yes
_:3 User curve #:Threshold 0.80 p.u. to 3.00 p.u. 1.10 p.u.
_:101 User curve #:Time dial 0.05 to 15.00 1.00

7.6.5.4 Information List

No. Information Data Class Type


(Type)
User curve #
_:81 User curve #:>Block stage SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:55 User curve #:Pickup ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O
_:301 User curve #:Down integr. running SPS O

1130 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

7.7 Voltage Differential Protection for Capacitors

7.7.1 Overview of Functions

The Voltage differential protection function (ANSI 87V) can be applied if the capacitor offers a voltage tap to
measure the 3-phase voltage within the capacitor installation. The function:

• Calculates the differential voltage between busbar and tap voltage by applying a matching factor

• Works as a capacitor unbalance function for protection of faults in capacitor elements (C elements)

7.7.2 Structure of the Function

The Voltage differential protection function is used in the Capacitor bank function group. The function is
preconfigured at the factory with one protection stage Vdiff>.
A maximum of 4 protection stages Vdiff> can be operated simultaneously in the function.
The General functionality (including compensation) works across all stages.

[dw_strucVoldi-060213-01.vsd, 1, en_US]

Figure 7-36 Structure of the Voltage Differential Protection Function

7.7.3 General Functionality

7.7.3.1 Description
The General functionality is structured in the following parts:

• Calculation of the differential voltage Vdiff.

• Compensation of an operational differential voltage Vdiff.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1131


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

Logic for Calculation and Compensation

[Lo_voltdiffgeneral_20140714.vsd, 4, en_US]

Figure 7-37 Logic Diagram of the General Functionality

Measurands, Method of Measurement


The function receives the 3-phase busbar and tap voltage measurands (see also VBB and Vtap in Figure 7-37) via
the 3-phase voltage and 3-phase voltage CB tap interfaces of the Capacitor bank function group. For an
isolated capacitor-bank system, the function receives the capacitor-bank neutral-point displacement voltage
VN via the Voltage unbalance interface. The method of measurement used processes the sampled voltage
values and filters out the fundamental component numerically.

1132 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

Based on the grounding type of the capacitor-bank neutral point, different values of voltage measurands are
used for calculating the differential voltages and for calculating the voltage matching factors at the compensa-
tion moment:

• For a grounded capacitor-bank system, absolute values such as VBB and Vtap are used.

• For an isolated capacitor-bank system, vector values such as VBB and Vtap are used.

The compensated or non-compensated differential voltages are provided to the protection stage for evalua-
tion.

Voltage Matching Factor, Setting of the Matching Factor


The voltage matching factor k is used as a multiplier for the tap voltage to obtain an equivalent voltage value
compared to the busbar voltage. With the parameter Matching-factor setting, you can select to set the
matching factor phase-selectively using the parameters Volt. match. factor phs A, Volt. match.
factor phs B, and Volt. match. factor phs C, or to set it for all phases together using the param-
eter Voltage matching factor. If the compensation is carried out, the function obtains the matching
factors from the compensation functionality instead of applying the setting values. In case the compensation
is reset, the setting values are applied again.

Calculation of the Differential Voltage


The calculation of the differential voltage depends on the way the capacitor-bank neutral point is grounded.
With the parameter Cap.-bank neutral point, you can set the grounding type.
2 ways of capacitor-bank neutral-point grounding are possible:

• Grounded capacitor-bank system

[dw_voltage_measurement_grounded, 1, en_US]

Figure 7-38 Voltage Measurement for a Grounded Capacitor-Bank System

The following formula is used to calculate the differential voltage Vdiff. of phase A from the absolute values of
the busbar and tap voltage:
Vdiff,A = |VBB,A - kA ⋅ Vtap,A|

VBB,A Absolute value of the busbar voltage, phase A


Vtap,A Absolute value of the tap voltage, phase A
kA Absolute value of the voltage matching factor, phase A

This calculation also applies to the calculation of the Vdiff. of phase B and phase C.
The voltage measuring-points are connected to the corresponding function-group interfaces.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1133


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

[Sc_grounded_ground, 1, en_US]

Figure 7-39 Connecting Measuring Points to the Capacitor Bank Function Group for the Grounded Capac-
itor-Bank System

• Isolated capacitor-bank system

[dw_voltage_measurement_isolated, 2, en_US]

Figure 7-40 Voltage Measurement for an Isolated Capacitor-Bank System

The following formula is used to calculate the differential voltage Vdiff. of phase A from the vector values of the
busbar and tap voltage:
Vdiff,A = |(VBB,A - VN) - kA ⋅ (Vtap,A - VN)|

VBB,A Vector value of the busbar voltage, phase A


Vtap,A Vector value of the tap voltage, phase A
kA Vector value of the voltage matching factor, phase A
VN Vector value of the neutral-point-to-ground voltage

This calculation also applies to the calculation of the Vdiff. of phase B and phase C.
The voltage VN is measured via a 1-phase measuring point V-1ph. The measuring point V-1ph must be
connected with the Vunbalance (voltage unbalance) interface of the function group.

[Sc_isolate_ground, 1, en_US]

Figure 7-41 Connecting Measuring Points to the Capacitor Bank Function Group for the Isolated Capacitor-
Bank System

1134 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

Both the capacitor-bank tap voltage and the calculated differential voltage are displayed as measured values of
the function.

General Notes on the Compensation


An operational differential voltage is added to a differential voltage resulting from faulty capacitor elements.
This corrupts the measuring result.
The operational differential voltages can result from the following factors:

• Manufacturing tolerances of the capacitor

• Aging of the capacitor

• Environmental influences, for example, temperature


The compensation eliminates the operational differential voltage by adjusting the voltage matching factors.
The adjusted phasors of the matching factor are calculated at the compensation moment, with the following
formula (for phase A):

• Grounded capacitor-bank system (absolute values are used for calculation)


kcp,A = VBB,A / Vtap,A

• Isolated capacitor-bank system (vector values are used for calculation)


kcp,A = (VBB,A - VN) / (Vtap,A - VN)

With
VBB,A and VBB,A Busbar voltage, phase A
Vtap,A and Vtap,A Tap voltage, phase A
kcp,A and kcp,A Calculated matching factor at the compensation moment, phase A
VN Neutral-point-to-ground voltage

The calculation also applies to the calculation of the voltage matching factors of phase B and phase C.
The phasors of the calculated voltage matching factors kcp are stored and used for calculation of the differen-
tial voltage until the next compensation is applied or until the compensation is reset.
The phasors of the calculated voltage matching factors kcp are displayed as functional measured values after
the compensation is applied. In addition, the compensated differential voltage Vdiff.cp is available as a
functional measured value. Vdiff.cp is the differential voltage at the moment of the compensation
compared to the not compensated status. The compensated differential voltage Vdiff.cp is calculated with
the following formula (for phase A):

• Grounded capacitor-bank system (absolute values are used for calculation)


Vdiff.cp,A = | VBB,A - kcp,A ⋅ Vtap,A|

• Isolated capacitor-bank system (vector values are used for calculation)


Vdiff.cp,A = | (VBB,A - VN) - kcp,A ⋅ (Vtap,A - VN)|

With
kcp,A and kcp,A Calculated matching factor at the compensation moment, phase A
VBB,A and VBB,A Busbar voltage, phase A
Vtap,A and Vtap,A Tap voltage, phase A
VN Neutral-point-to-ground voltage

This calculation also applies to the calculation of the compensated differential voltages of phase B and phase
C.

Manual Compensation via Binary Input Signal


Manual compensation via binary input signals is available.
The following indications describe the status of the compensation:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1135


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

Indication Description
Alg. not compensated The algorithm is not compensated. Compensated values are not available.
Compens. succeeded If the existing unbalance has been compensated manually, this indication is
issued (as transient indication).

By activation of the binary input signal >Compensate, the manual compensation is started and the differen-
tial voltage that exists at that moment is compensated to 0. The value of Vdiff. becomes 0.
For the reliability of manual compensation, the binary input signal >Compensate has a preset software
filtering time (configurable in DIGSI) of 20 ms.

NOTE

i If the measured busbar voltage or tap voltage is too low, the manual compensation cannot be performed.
No manual compensation is carried out under the following conditions:

• In the grounded system:


VBB < 10 % ⋅ VBB,rated or Vtap,sec < 1 V

• In the isolated system:

[fo_isolated-system, 2, en_US]

Resetting the Compensation


If one of the following conditions is met, the function works in the non-compensated status:

• Initial startup of the device before any compensation has been carried out

• Activation of the binary input >Reset comp. val.

• Change of the parameter Cap.-bank neutral point in the Capacitor bank function group (refer to
chapter 5.4.3 Application and Setting Notes)
The non-compensated status is indicated via the signal Alg. not compensated.
For the reliability of manual compensation, the binary input signal >Reset comp. val. has a preset soft-
ware filtering time (configurable in DIGSI) of 20 ms.

Functional Measured Values

Values Description Primary Secondary % Referenced to


(_:15781:300) Vtap Tap voltage kV V Parameter Capacitor refer-
ence volt./√3
(_:15781:304) Neutral-point displacement kV V Parameter Capacitor refer-
Vunbal. voltage ence volt.
(_:15781:301) Differential voltage kV V Parameter Capacitor refer-
Vdiff. ence volt./√3
(_:15781:306) Compensated differential voltage kV V Parameter Capacitor refer-
Vdiff.cp at the compensation moment ence volt./√3
(_:15781:305) Voltage matching factor – – –
Mat.fac.

You can find the parameter Capacitor reference volt. in the General function block of the Capacitor
bank function group.

1136 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

NOTE

i If the function works in the non-compensated status, the settings of the voltage matching factors are
displayed as functional measured values, and the functional measured values of Vdiff.cp are shown as
---.

7.7.3.2 Application and Setting Notes

Parameter: Matching-factor setting

• Default setting (_:15781:102) Matching-factor setting = not phase-selective


With the parameter Matching-factor setting, you select to set the voltage matching factor in a phase-
selective way or not.
Parameter Value Description
not phase-selective Select this setting if you want to apply the same voltage matching factor for
all 3 phases.
phase-selective Select this setting if you want to apply different voltage matching factors for
all 3 phases.

Parameter: Voltage matching factor, Volt. match. factor phs A, Volt. match. factor phs B,
Volt. match. factor phs C

• Default setting (_:15781:101) Voltage matching factor = 2.0000

• Default setting (_:15781:103) Volt. match. factor phs A = 2.0000

• Default setting (_:15781:104) Volt. match. factor phs B = 2.0000

• Default setting (_:15781:105) Volt. match. factor phs C = 2.0000


The voltage matching factors are applied as multipliers for the primary tap voltage to calculate the differential
voltage. It depends on the position of the tap-voltage measurement in the specific capacitor installation. The
setting is defined as the ratio of the capacitor-bank reference voltage to the tap voltage.

EXAMPLE
The application consists of:

• Capacitor-bank busbar, with a rated voltage of 345 kV

• Capacitor bank, consisting of 15 can levels in series

• Capacitor-bank tap-voltage measurement between levels 14 and 15

SIPROTEC 5, 7SJ82/7SJ85, Manual 1137


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

[lo_application example, 2, en_US]

Figure 7-42 Application Example for Setting the Voltage Matching Factor

Capacitor-bank busbar voltage as phase-to-phase voltage: 345 kV


(it equals to a phase-to-ground voltage of 199.2 kV)
Capacitor-bank tap voltage as phase-to-phase voltage: 23 kV
(it equals to a phase-to-ground voltage of 13.28 kV)
Voltage matching factors are set as: 345 kV/23 kV = 15

The voltage measuring points must be set as indicated in the figure:


Busbar transformer, rated primary voltage: 345 kV
Busbar transformer, rated secondary voltage: 110 V
Transformer to tap the voltage, rated primary voltage: 22 kV
Transformer to tap the voltage, rated secondary voltage: 110 V

Under normal operation, these settings result in a differential voltage of approximately 0 V and in the primary
and secondary measured voltage values as indicated in the 7.7.3.1 Description.

NOTE

i The sound secondary tap voltage must not be smaller than 1 V. Otherwise the function cannot work prop-
erly. Fulfill this condition by applying an appropriate voltage transformer for the tap voltage. Siemens
recommends applying a tap voltage transformer which provides under normal operation a secondary
voltage in the area of the rated secondary voltage.

EXAMPLE

In the grounded system:


Ratio of the capacitor-bank busbar voltage to the tap voltage (matching 400 kV/400 V = 1000
factor k):
Busbar transformer, rated primary voltage: 400 kV
Busbar transformer, rated secondary voltage: 100 V

To ensure an optimal tap-voltage measurement, the following transformer ratio is recommended:


Transformer to tap the voltage, rated primary voltage: 400 kV
Transformer to tap the voltage, rated secondary voltage: 100 V

1138 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

7.7.4 Protection Stage

7.7.4.1 Description

Logic of the Stage Vdiff>

[Lo_voltdiffstage_20140715, 2, en_US]

Figure 7-43 Logic of the Protection Stage Vdiff>

Measurand, Pickup and Operate


In the protection stage, the differential-voltage value is converted to a p.u. value in relation to the capacitor-
bank reference voltage.
If the converted value exceeds the Threshold value, a Pickup indication is issued. If the threshold is
exceeded continuously during the operate delay, an Operate signal is issued.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1139


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

Blocking the Stage


In the event of blocking, the picked up stage will be reset. The following blocking options are available for the
stage:

• Via the binary input signal >Block stage from an external or internal source.

• From inside on pickup of the Measuring-voltage failure detection function (see section 9.3.2.1 Over-
view of Functions). The parameter Blk. by meas.-volt. failure can be set so that the meas-
uring-voltage failure detection blocks the stage or does not block it.

• From an external source via the binary input signal >Open of the Volt.-transf. c. b. function block, which
links in the tripping of the voltage-transformer circuit breaker. The parameter Blk. by meas.-volt.
failure can be set so that the measuring-voltage failure detection blocks the stage or does not block it.

7.7.4.2 Application and Setting Notes

Stage Blocking during Bank Switch-off


After the bank is switched off (the bank CB is opened), the tap voltage begins to decrease while the bus
voltage remains its normal value. If no measure is taken, the protection stage will pick up and also operate
after the operate delay expires. To avoid this, the stage can be blocked via the binary input >Block stage.
The stage must be blocked during the entire bank switch-off period and until the device is measuring the
complete tap voltage after the bank is energized again.
Different blocking schemes can be selected depending on user philosophy and experience:

• Starting of the blocking with detection of the CB position "not closed" (with leaving the CB position
"closed")
In rare cases this scheme could result in a racing condition depending on the time delay of the respective
CB auxiliary contact. Stage pickup might occur in case of a long delay (> 20 ms) of auxiliary contacts.
Stage operate is avoided due to the operate delay.
The blocking should be maintained for an additional time delay of 100 ms after the CB position is
detected as “closed” again.

• Starting of the blocking with issue of the CB-open command and in parallel with detection of the CB posi-
tion "not closed"
In case of a long delay (> 20 ms) of auxiliary contacts, blocking can be initiated with the CB-open
command and be held with the CB position "not closed". This scheme safely avoids a stage pickup.
The blocking should be maintained for an additional time delay of 100 ms after the CB position is
detected as “closed” again.

• Blocking with detection of the phase currents dropping below a low set CB-open threshold, for example,
by applying the Undercurrent protection function
This scheme will result in a racing condition. Stage pickup possibly occurs but stage operate is avoided
due to the operate delay.
The blocking should be maintained for an additional time delay of 100 ms after the Undercurrent
protection function drops out.

Parameter: Threshold

• Default setting (_:15811:3) Threshold = 0.200 p.u.


The parameter Threshold is set as a p.u. value related to the parameter Capacitor reference
voltage in the Capacitor bank function group. The parameter Capacitor reference voltage is
defined as a rated voltage and therefore is set in relation to a phase-to-phase voltage.
The setting of the parameter Threshold depends on the differential voltage that occurs with the number of
defective C elements for which a warning indication or a trip command shall be generated. Determine this
differential voltage and set the Threshold slightly lower, for example, to 80 % of the value.

1140 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

Example of the relationship between the p.u. value and the absolute primary and secondary values of the pickup
threshold
For example, the setting values are as follows:
Setting value of Capacitor reference voltage, primary value related to a 69 kV
phase‑to‑phase voltage
Setting value of Threshold 0.05 p.u.
Voltage transformer ratio (Setting value of Rated primary voltage divided 1000
by setting value of Rated secondary voltage)

Then, the absolute primary and secondary values of the pickup threshold are as follows:
Primary pickup threshold, related to a phase-to-phase voltage 69 kV ⋅ 0.05 = 3.45 kV
Secondary pickup threshold, related to a phase-to-phase voltage 3.45 kV/1000 = 3.45 V
Secondary pickup threshold, related to a phase-to-ground voltage 3.45 V/√3 = 2.00 V

Parameter: Operate delay

• Default setting (_:15811:6) Operate delay = 1.00 s


Set the parameter Operate delay for the specific application.

Parameter: Blk. by meas.-volt. failure

• Default setting (_:15811:10) Blk. by meas.-volt. failure = yes


You can use the parameter Blk. by meas.-volt. failure to control the response of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:

• The device-internal Measuring-voltage failure detection function is configured and switched on.

• The binary input signal >Open of the Voltage-transformer circuit breaker function block is connected to
the voltage-transformer circuit breaker. This binary input is available in the voltage transformers
connected to the bus voltage and capacitor-bank tap voltage. The binary input is also available in the
voltage transformer connected to the VN voltage in case of an isolated capacitor bank.

Parameter Value Description


no The stage Vdiff> is not blocked when a measuring-voltage failure is detected.
yes The stage Vdiff> is blocked when a measuring-voltage failure is detected.
Siemens recommends using the default setting, as correct operation of the
stage cannot be guaranteed if a measuring-voltage failure occurs.

7.7.4.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:15781:102 General:Matching-factor • not phase-selective not phase-selec-
setting tive
• phase-selective
_:15781:101 General:Voltage 0.5000 to 2000.0000 2.0000
matching factor
_:15781:103 General:Volt. match. 0.5000 to 2000.0000 2.0000
factor phs A
_:15781:104 General:Volt. match. 0.5000 to 2000.0000 2.0000
factor phs B
_:15781:105 General:Volt. match. 0.5000 to 2000.0000 2.0000
factor phs C

SIPROTEC 5, 7SJ82/7SJ85, Manual 1141


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors

Addr. Parameter C Setting Options Default Setting


Vdiff> 1
_:15811:1 Vdiff> 1:Mode • off off
• on
• test
_:15811:2 Vdiff> 1:Operate & • no no
flt.rec. blocked
• yes
_:15811:10 Vdiff> 1:Blk. by meas.- • no yes
volt. failure
• yes
_:15811:3 Vdiff> 1:Threshold 0.005 p.u. to 1.000 p.u. 0.200 p.u.
_:15811:6 Vdiff> 1:Operate delay 0.00 s to 60.00 s 1.00 s

7.7.4.4 Information List

No. Information Data Class Type


(Type)
General
_:15781:500 General:>Compensate SPS I
_:15781:501 General:>Reset comp. val. SPS I
_:15781:302 General:Alg. not compensated SPS O
_:15781:303 General:Compens. succeeded SPS O
_:15781:300 General:Vtap WYE O
_:15781:304 General:Vunbal. CMV O
_:15781:301 General:Vdiff. WYE O
_:15781:306 General:Vdiff.cp WYE O
_:15781:305 General:Mat.fac. WYE O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Vdiff> 1
_:15811:81 Vdiff> 1:>Block stage SPS I
_:15811:54 Vdiff> 1:Inactive SPS O
_:15811:52 Vdiff> 1:Behavior ENS O
_:15811:53 Vdiff> 1:Health ENS O
_:15811:55 Vdiff> 1:Pickup ACD O
_:15811:56 Vdiff> 1:Operate delay expired ACT O
_:15811:57 Vdiff> 1:Operate ACT O

1142 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

7.8 Differential Protection for Capacitor Banks

7.8.1 Overview of Functions

The function Differential protection for capacitor banks (ANSI 87C):

• Detects ground faults and multiphase short circuits at capacitor banks

• Detects ground faults during the operation of capacitors in systems with a grounded neutral point

• Uses the necessary stabilization procedures during energizing operations

• Trips safely and very fast in the case of internal high-current faults through an additional high-current
stage

7.8.2 Structure of the Function

The Differential capacitor bank protection function is used in the Capacitor bank diff protection function
group. The function depends upon application in the corresponding application template preconfigured by the
manufacturer and can be copied during the engineering into the corresponding function group.
The Capacitor bank diff function consists of the 2 tripping stages I-DIFF and I-DIFF fast. In addition, the trip-
ping stage I-DIFF unrestrained is available. You can select this tripping stage from the function catalog and
copy it into the Capacitor bank diff protection function group. The stages can be blocked, in addition you can
switch the stages on and off.
The Capacitor bank side function group has the following characteristics:

• The side-related protection settings are performed

• The side-related calculations are performed

• All data (setting values, detected currents) are relayed to the Capacitor bank diff function group
The side-related protection functions can run in the Capacitor bank side function group, for example over-
load protection, overcurrent protection, etc.

[dweimcapbk-030314-01, 3, en_US]

Figure 7-44 Structure/Embedding of the Function

7.8.3 Function Description

Basic Principle of Differential Protection


Differential protection is based on a comparison of currents (Kirchhoff current law). When comparing the
current, use is made of the fact that a protected object uses the same current I in a non-faulty operating state
on both sides (dotted in Figure 7-45). This current flows into the range being observed on one side and leaves
it again on the other side. A current differential is a sure indication of a fault within the protected object. The

SIPROTEC 5, 7SJ82/7SJ85, Manual 1143


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

calculation of the difference is determined through the current-direction definition. The current direction is
defined as positive to the protected object. The current difference results from the vector addition of the
currents.

[dwprin2s-170712-01.tif, 1, en_US]

Figure 7-45 Basic Principle of Differential Protection Using the Example of 2 Sides

For safe operation, additional functions are required. The implementation of these additional functions is
described in chapter I-DIFF Differential Protection Function, Page 1149.

Current Stabilization
If very large currents flow through the protection range in the case of external faults, with different transmis-
sion behavior of the transformers T1 and T2 (Figure 7-45), a corresponding differential current Idiff occurs.
When this is larger than the corresponding pickup threshold, the device can issue a trip command, even
though no fault is present in the protection range. Such a malfunction of the protection is avoided by the
restraint current (Irest) and is implemented in the form of a characteristic curve Idiff = f(Irest).
The largest current of 2 or more measuring points of the protected object is used for stabilization.
The definition for 2 measuring points is:
A trip or differential current is
Idiff = (I1 + I2)
as well as a restraint current of
Irest = Max (|I1| ; |I2|)
For more than 2 measuring points, this definition is expanded. This restraint method allows a reliable trip deci-
sion for more than 2 measuring points and different feeding behavior for internal short circuits.
Irest = Max (|I1| ; |I2| ; ... |In|)
To clarify the effect, 3 important operating states are observed with ideal and adapted measurands.

• Through fault current in healthy operation or externally caused error:


I1 flows into the protection range, I2 flows out of the protection range, that is, negative compared with
the prefix definition, thus I2 = -I1;
in addition |I2| = |I1|
Idiff = |I1 + I2| = |I1 - I1| = 0
Irest = Max (|I1| ; |I2|) = |I1| = |I2|
No tripping quantity (Idiff = 0); the stabilization (Irest) corresponds to the flowing current.

• Internal short circuit, feed from both sides with equal amount of currents, for example:
Then I2 = I1; In addition |I2| = |I1|;
Idiff = |I1 + I2| = |I1 + I1| = 2 · |I1|
Irest = Max (|I1| ; |I2|) = |I1| = |I2|
The tripping quantity (Idiff) is twice as large as the short-circuit current and the restraining quantity (Irest).

1144 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

• Internal short circuit, feed only from one side:


Then I2 = 0
Idiff = |I1 + I2| = |I1 + 0| = |I1|
Irest = Max (|I1| ; |I2|) = |I1|
The tripping quantity (Idiff) and the restraining quantity (Irest) are of the same size and correspond to the
short-circuit current.

Additional Stabilization with External Short Circuits


In case of an external short circuit, high short-circuit currents flowing through can lead to current-transformer
saturation. This saturation can be more or less strongly pronounced at the measuring points, and in this way
simulate a differential current. The differential current can lie in the tripping range of the characteristic curve
for a certain time and lead to unwanted tripping without any particular measures. In accordance with
Figure 7-46, there are 2 typical scenarios:

• High-current, external short circuit


First, the current on both sides is transferred and leads to a large restraint current. After this, a trans-
former becomes saturated, resulting in a differential current Idiff that can exceed the operate curve.
Simultaneously, the restraint current Irest drops. Once the transformer is no longer saturated, the differen-
tial current decreases and falls below the characteristic curve.

• Low-current, external short circuit


Current transformers can also become saturated through the large direct-current time constant
(switching of transformers, motors), but small currents flowing through. This manifests itself as a phase-
angle rotation of the current. Exceeding the characteristic curve in a non-stabilized area is possible.
Intelligent saturation-detection methods capture this state and lead to a temporally limited blocking of the
Differential protection function.

[dwislauf-170712-01.tif, 1, en_US]

Figure 7-46 Principle Current Course in External Short Circuit and Temporary Current-Transformer Satura-
tion on One Side

Inrush-Current Detection
The inrush-current detection evaluates the calculated instantaneous values of the differential current. The
inrush current develops with Sympathetic Inrush – connection of a parallel transformer or Recovery Inrush –
inrush current subsequent to returning voltage after fault in the system considerably higher than in the side
currents. An assignment to the corresponding blocking phases is possible only in the differential current due
to the vector-group correction.
The inrush-current detection is activated when the pickup characteristic is exceeded. It is deactivated when it
is blocked by an external fault.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1145


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

For inrush-current detection, 2 methods working in parallel are used:

• Component of the 2nd harmonic relative to the fundamental component in the differential current
(I2nd harm/I1st harm)
As Figure 7-47 also shows, the 2nd harmonic is clearly pronounced in the inrush current. If the share of
the 2nd harmonic exceeds the set threshold value (parameter: 2nd harmonic content), a phase-
segregated blocking occurs. The harmonics develop differently in the different phases. If exceeding of
the 2nd harmonic is detected in a phase, it may be necessary to block all phases simultaneously. This
blocking must be limited with regard to time and is controlled by the parameter Crossblock. time
2nd har.. The correct positioning of the filter windows is controlled by the internal pickup.
If you want only one method to be active, the other method can be changed to inactive. For this, parameter
Blocking with 2. harmonic = no is used.

[scinrush-120120-01.tif, 1, en_US]

Figure 7-47 Inrush Current with Pronounced Flat Areas

Figure 7-48 shows the logical input and output signals.

[loblkcap-290414-01, 1, en_US]

Figure 7-48 Logic Inrush-Current Detection

1146 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

Logic of the Function

[lomesmgr-190713-01.tif, 2, en_US]

Figure 7-49 Logic Diagram of the Differential Protection Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 1147


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

The interaction of the I-DIFF, I-DIFF fast, and I-DIFF unrestrained tripping stages is shown in the following
operate curve.

[dw_charac_function_trans-dif, 1, en_US]

Figure 7-50 Operate Curve of the Differential Protection Function

Measurand Processing

Amount Correction
Since the current transformers cannot be adapted exactly to the rated currents of the protected object with
regard to their primary rated data, a standardization to the nominal sizes of the protected object takes place.
The conversion occurs every sampling time (thus, for instantaneous values). The differential protection func-
tion processes 20 sampled values per period. In addition, the sampled values tracked are used. A high degree
of accuracy can be attained over the entire tracking range (from 10 Hz to 90 Hz).
The Idiff-fast tripping stage works on non-frequency tracked values and thus, implements fast operate times
with low frequencies.
The amount is adapted via the following formula:

[fobetr07-170712-01.tif, 1, en_US]

iphsx* Adapted instantaneous value per phase (x = A, B, C)


iphsx Instantaneous value per phase (x = A, B, C)
k Correction value per measuring point
Irated prim,Sx Primary transformer rated current per measuring point
Irated obj,Sx Primary rated current of the protected object
Srated,ref Reference power (maximum rated apparent power of the protected object)
Vrated,Sx Rated voltage of the respective side (measuring point) of the protected object

NOTE

i For more than 2 capacitor bank sides (teed feeder), , the winding with the highest power is used as the
reference winding. If several sides have the same highest amount of power, then the highest current side is
selected as reference side. The amount of the neutral-point transformer is also adapted according to the
previous formula. In this case, the amount should be adapted to the side with the greatest power.

1148 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

Vector-Group Correction
The vector groups of the capacitor bank sides occur due to couplings that are different on each side. There-
fore, the measured currents cannot be used directly for summation. The vector-group correction replicates the
coupling of the capacitors and makes the measured currents comparable. The correction occurs such that each
side is converted to vector group 0. Since you are in the 3-phase system, the conversion occurs via matrices
which are stored for the respective vector-group type. The general description is given in the following
formula. In the same calculation step, the absolute value is corrected:

[foscha08-170712-01.tif, 1, en_US]

with
iphsx* Adapted instantaneous value per phase (x = A, B, C)
iphsx Instantaneous value per phase (x = A, B, C)
k Absolute-value correction per measuring point
MSG Correction matrix

I-DIFF Differential Protection Function


A differential current per phase based on the instantaneous value variables is calculated from the processed
currents (see section Measurand Processing). The direction of current flow is defined as to the protected
object as positive. The fundamental component contribution to the differential current (Idiff) is calculated via
a Fourier filter (filter length = 1 period (20 sampled values)).
The currents of that measuring point whose RMS value is the largest are used as restraint current. If, for
example, the current collapses at a measuring point as a consequence of current-transformer saturation, the
measuring point that has the largest current is automatically switched to at the point in time of the calcula-
tion.

NOTE

i Differential protection does not work with sensitive ground-current transformers. Since sensitive trans-
formers can go into saturation too quickly, false differential currents arise.

[fogrds16-170712-01.tif, 1, en_US]

with
x Variable (1, 2, 3) for the phase currents (A, B, C)
m Variable (1, 2, ..., N) for the measuring points
N Number of measuring points
n Number of samples per period (n = 20)
FIR Fourier filter
MAX Maximum value determination

SIPROTEC 5, 7SJ82/7SJ85, Manual 1149


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

Pickup Characteristic
Figure 7-51 shows the pickup characteristic of the differential protection. The characteristic curve branch a
represents the sensitivity threshold of the differential protection (parameter Threshold) and considers
constant fault currents like magnetizing currents.
The characteristic branch b (parameter Intersection 1 Irest and Slope 1) considers current-propor-
tional faults under normal operating conditions.
These faults can occur for the following reasons:

• Transformation errors in the current transformer and the input transformer of the device

• Adaptation deviations
The characteristic curve branch c (parameter Intersection 2 Irest and Slope 2) protects the differen-
tial protection against overfunction in case of high-current external faults and transformer saturation. In this
range, transformer saturation can arise due to high short-circuit currents, and because of this, a higher differ-
ential current results.
In order to avoid overfunction in the event of external faults with current-transformer saturation, a logic is
implemented that uses the characteristic curve Additional stabilization of external faults. If the operating
point is located in the additional stabilization range and exceeds the operate curve from there, then the logic
becomes active and blocks the differential protection.
The additional stabilization range is derived from the Threshold add-on stabiliz. and Slope 1
parameters.

[dwdifaus-030912-01.tif, 2, en_US]

Figure 7-51 Pickup Characteristic of the Differential Protection

1150 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

If the differential current multiplied by the dropout ratio of 0.7 does not reach the pickup characteristic, the
pickup drops out.

Detection of External Faults


To detect external faults with transformer saturation in a reliable way, the measurand curve is evaluated in the
Diff.-Rest level by means of a detector.
The detector has 2 essential tasks:

• Blocking in the case of a definite high-current external fault


The differential current and the restraint current are monitored on a phase basis in the Diff/Restr level
immediately after fault inception. To ensure the stability of the saturation detection for low saturation-
free times of the primary current transformer, estimated values based on the difference quotients of the
instantaneous values are used.
If the estimated restraint current exceeds the Threshold add-on stabiliz. parameter and the
expected value of the differential current of all phases is in the additional stabilization range (parameter
Slope 1) (Figure 7-51) at the same time, the detector is active and the indication Blocked by ext.
fault phsx appears. The tripping of the Differential protection function is blocked.
If an external fault arises and is cleared by the protection responsible for it, the additional stabilization
drops out. If the dropout ratio (0.7) of the RMS value of the restraint current does not reach the
Threshold add-on stabiliz. parameter (Figure 7-51), the additional stabilization drops out. The
indication Blocked by ext. fault phsx is reset.
If the differential current exceeds Slope 1 as a result of transformer saturation, that is, there is a pickup
phsx, the blocking is limited in time (parameter: Time of add-on stabiliz.).
Starting with the indication Blocked by ext. fault phsx, the other phases can be blocked with it
via the Crossblk. time add-on st. parameter. If differential currents due to transformer satura-
tion spread to the other phases through the vector-group correction or residual current elimination, this
blocking is necessary.

• Removal of the blocking with a change in fault location from external to internal
An internal fault can arise as a consequence of an external fault. This fault change must be recognized
and the blocking must be removed. The critical case is a short-circuit with current-transformer saturation.
The saturation detection examines here the instantaneous values of the differential current. With trans-
former saturation, the instantaneous values fall below an internal threshold in the saturation-free time. If
this threshold is permanently exceeded and a pickup is present in the corresponding phase, an internal
error is assumed. The other phases are also examined during the parameterization with crossblock.
The blocking of the tripping is removed and the indication Blocked by ext. fault phsx is reset.

DC-Component Detection
Low-current external faults with large DC components can also lead to exceeding of the operate curve. The
additional stabilization range is not attained, however.
To avoid an overfunction, the following steps are taken:

• The restraint current Irest.;phsx is monitored for a jump.

• If the jump occurs, the DC component is calculated, with a temporal delay (1 period), from the instanta-
neous value of the restraint current (current at the measuring point with the largest current) irest.,phsx =
iphsx,Mm. The result is Irest.DC,phsx. This current is compared to the restraint current Irest., phsx and is checked for
exceeding of the internal threshold.

• The differential current Idiff,phsx must lie below the dropout characteristic curve (characteristic curve · 0.7)
in all 3 phases.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1151


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

• If the first 3 points lead to positive results, then the operate curve is raised by the parameter Factor
increasing char. with a default setting of 2.3. Here, only the threshold value and the slope 1 are
raised (see Figure 7-52). The indication Increase of char. (DC) is output. If the product of param-
eter Factor increasing char. and Slope 1 exceeds 0.85, the maximum increase of the raised
Slope 1 is limited to 0.85.

• As additional criterion, the pickup indication Pickup (internal fault is present) or the indication of the
additional stabilization Blocked by ext. fault phsx (high-current external fault) is interrogated. If
one of the 2 conditions is present, the characteristic-curve increase is stopped. A retroactive pickup no
longer resets the characteristic-curve increase. A pickup with DC-component detection occurs only if the
raised operate curve is exceeded.
If the DC component Irest.DC,phsx falls below the internal dropout threshold, the dropout delay is determined as
follows:
It is assumed that the de- and re-magnetization of the transformer last equally long. The magnetization is at
the highest at the point in time in which the internal dropout threshold is attained. The time is measured from
the start of the DC-component detection until the internal dropout threshold is reached. Added to this time
are 5 periods and from this, the dropout delay is derived. Following this, the characteristic-curve increase is
reset to the original value. Figure 7-53 shows the overall logic.

[dwdcerkn-201112-01.tif, 2, en_US]

Figure 7-52 Increasing the Characteristic Curve after DC Detection

1152 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

[lodcerkn-170712-01.tif, 3, en_US]

Figure 7-53 Logic DC Detection

Startup Detection
The startup detection is particularly useful in the case of motors. In contrast to transformers, the inrush
current with motors is a flowing current. Differential currents can arise, however, by the current transformers
having different residual magnetization and being supplied with current at different operating points of their
hysteresis. These differential currents are low in fact, but they can lead to overfunction with sensitive setting
of the differential protection.
As additional security against overfunction when switching in a previously protected object that carries no
current, you can use the pickup-value increase at startup. If the restraint current falls below a settable value
Thresh. startup detection in all phases, the pickup-value increase is activated. The pickup value
Threshold and Slope 1 are raised by the set value in accordance with parameter Factor increasing
char.. As a rule here, Slope 1 cannot exceed a value of 0.85.
If the parameter Thresh. startup detection is exceeded, dropout occurs and a timing element (param-
eter: Max. perm. Start. time) is activated. Once this time has elapsed, the characteristic curve that was
increased in all phases is reset to its original value. Figure 7-54 shows the logic diagram of the startup detec-
tion and Figure 7-55 the increased characteristic curve.

[loanlauf-170712-01.tif, 3, en_US]

Figure 7-54 Logic Startup Detection

SIPROTEC 5, 7SJ82/7SJ85, Manual 1153


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

[dwanlken-201112-01.tif, 1, en_US]

Figure 7-55 Characteristic-Curve Increase at Startup

Trip Logic of the Differential Protection Function I-DIFF


Figure 7-56 shows the trip logic. If the characteristic curve is exceeded (see Figure 7-51) a pickup occurs. Redi-
rection of the information for tripping can be blocked by the additional functions.
Blocking is possible through use of the following influencing variables:

• Recognition of external faults that can simulate an internal fault through transformer saturation

• Recognition of the connection process (2nd harmonic)


In addition, in case of blocking due to an external error, a Crossblock mechanism comes into effect.

1154 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

[loauscod-290414-01, 1, en_US]

Figure 7-56 Trip Logic of I-DIFF

I-DIFF Fast Differential Protection Function


As a supplement to the I-DIFF differential protection function, the function I-DIFF fast is available. The main
task consists in switching off high-current internal faults in the shortest amount of time. The method controls
current-transformer saturation and is stable in the event of external transverse faults (integration in breaker-
and-a-half arrangements).
Metrologically, 2 methods are combined:

• Instantaneous-value method

• Filter-based method

Instantaneous-Value Method
Through the instantaneous-values method, an immediate evaluation of the sampled values of the differential
iDiff(t) and restraint current irest(t) occurs. The absolute-value and vector-group adapted currents (i*) are also
the basis. The currents are defined positively to the node. The restraint current is the maximum current of all
measuring points.

[fomome27-170712-01.tif, 1, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 1155


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

where
x Variable (1, 2, 3) for the phase currents (A, B, C)
m Variable (1, 2, ..., N) for the measuring points
N Number of measuring points

The evaluation of the restraint current is used to recognize saturated, high-current external faults.
Figure 7-57 shows the operate curve. The parameter Threshold is set here such that it lies over the
maximum fault current flowing. The slope of the characteristic curve is fixed at 0.8.
In the algorithm, the following conditions are processed:

• Condition 1: The increase of the restraint current direst(t)/dt is determined continuously and compared
with an internal threshold value.

• Condition 2: After that, a comparison determines whether the differential current is larger than the
restraint current (characteristic curve Slope in Figure 7-57): idiff(t) > 0.8 · irest(t).

• Condition 3: After that, a comparison determines whether the differential current exceeds the parameter
Threshold.
When all conditions are met, tripping occurs immediately. If the 1st condition is recognized and not the 2nd
condition, then the function is blocked for 300 ms.

[dwidfast-300114-01.tif, 1, en_US]

Figure 7-57 I-DIFF Fast Characteristic Curve

The following figures show the behavior during an internal and an external fault. It is typical for the internal
fault (Figure 7-58) that the differential current rises more quickly than the restraint current. After a few
sampled values, the trip signal is issued. In case of an external fault, a differential current arises only after
transformer saturation occurs. You can always assume, however, that the current is transferred a few millisec-
onds after occurrence of the fault. In accordance with Figure 7-60, the restraint current is larger than the
differential current after occurrence of the fault, but condition 2 is not met and the function is therefore
blocked.

1156 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

[dwinnfel-201112-01.tif, 1, en_US]

Figure 7-58 Curve Plot for Internal Fault with Transformer Saturation (k= 0.65)

[dwextfel-170712-01.tif, 1, en_US]

Figure 7-59 Curve Plot for External Fault with Transformer Saturation (k= 0.65)

Fundamental-Component Method
Parallel to the instantaneous-value method, the fundamental component works with a temporal delay. Here,
the same measured values are processed as with the I-DIFF method. The fundamental component of the
differential current Idiff and the stabilization value (maximum current of a measuring point) Irest. are ordered in
the operate curve according to Figure 7-57 and the trip decision is made.
Figure 7-60 shows the overall logic.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1157


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

[loidfast-151012-01.tif, 3, en_US]

Figure 7-60 Logic of the I-DIFF Fast Differential Protection Function

I-DIFF Unrestrained Differential Protection Function


In addition to the I-DIFF and I-DIFF fast differential protection function, the function I-DIFF unrestrained is
available. The main task of this function consists in switching off high-current internal short circuits in the
shortest amount of time. The method controls current-transformer saturation.
High-current faults in the protection range can always be switched off immediately without consideration of
the restraint currents if, due to the current magnitude, it is determined that an external fault is not involved. In
the case of protected objects with a large intrinsic longitudinal impedance (transformer, generator, reactor), a
current can be found that is never exceeded by a flowing short-circuit current.

1158 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

For a transformer, for example, the (primary) value is:

[fo_Idiff-error, 1, en_US]

The I-DIFF unrestrained stage also acts if, for example, due to current-transformer saturation because of a
DC component in the short-circuit current, a 2nd harmonic occurs. The inrush-current detection could inter-
pret this as the closed-circuit current.
The I-DIFF unrestrained protection stage operates both with the fundamental component of the differential
protection and with the instantaneous value.
Metrologically, 2 methods are combined:

• Instantaneous-value method

• Filter-based method

Instantaneous-Value Method
With the instantaneous-values method, an immediate evaluation of the sampled values of the differential
current iDiff(t) occurs. The absolute-value and vector-group adapted currents (i*) are also the basis.

Fundamental-Component Method
Parallel to the instantaneous-value method, the fundamental component works with a temporal delay. Here,
the same measured values are processed as with the I-DIFF method. The fundamental component of the
differential current Idiff is ordered in the operate curve Figure 7-61 and the trip decision is made.

[dwidffunres-100117-01, 1, en_US]

Figure 7-61 I-DIFF Unrestrained Characteristic Curve

Figure 7-62 shows the overall logic.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1159


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

[loidffunres-100117-01, 1, en_US]

Figure 7-62 Logic of the I-DIFF Unrestrained Differential Protection Function

Trip Logic of the Differential Protection


A common trip signal is formed from the subfunctions I-DIFF, I-DIFF fast, and I-DIFF unrestrained. Figure 7-63
shows the corresponding logic.

1160 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

[logesamt-170712-01.tif, 2, en_US]

Figure 7-63 Overall Trip Logic

Fault Logging and Fault Recording


A fault is opened with every protection pickup. This means that a fault log and a fault recording are started.
Saving of the fault record depends on the setting (see 3.5.3 Function Description). Since pickup and tripping
are the same in differential protection, the recording setting can be used with the pickup function. To enable
fault recording even with external errors, along with the exceedance of the characteristic curve, a fault record
is opened in case of a blocking by an external error or in case of a characteristic-curve increase through a DC-
component detection. This has the advantage that you can evaluate the transformer transfer method of the
current transformers very well in case of a fault.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1161


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

7.8.4 Application and Setting Notes

Figure 7-64 shows the application of the differential protection using a capacitor bank with a simplified
example.

[dwanslbca-130514-01, 3, en_US]

Figure 7-64 Connection Example

The measuring points must be interconnected with the corresponding function groups.
Figure 7-65 shows the corresponding screenshot from DIGSI 5.

[sccapbak-130514-01, 1, en_US]

Figure 7-65 Internal Interconnection in DIGSI 5

1162 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

Function Group Capacitor Bank


Only the parameters important for the application of the differential protection function are discussed here.
You can find setting notes for more parameters in chapter 5.4.3 Application and Setting Notes (Capacitor
bank function group).

Parameter: Capacitor reference curr.

• Default setting (_:14641:101) Capacitor reference curr. = 1000 A


With the parameter Capacitor reference curr., you determine the reference current of the capacitor
bank to be protected. The capacitor reference current set here is the reference value for the percentage meas-
ured values and setting values in percent.
For differential protection these values are added to the correction amount (rated current of the protected
object).
Depending on user philosophy you use the rated current of the capacitor bank as a reference value including
the harmonic or the fundamental component current.

Function Group Capacitor Bank Side


Make the following settings in the Capacitor bank side function group:

Parameter: Capacitor reference curr.

• Default setting (_:1781:15571:101) Capacitor reference curr. = 1000 A


With the parameter Capacitor reference curr., you determine the reference current of the capacitor
bank to be protected. The capacitor reference current set here is the reference value for the percentage meas-
ured values and setting values in percent.
For differential protection these values are added to the correction amount (rated current of the protected
object).
If the capacitor bank is in a delta connection, the value to be set can differ from the capacitor-bank reference
current set in the function group Capacitor bank (by a factor √3). Otherwise always use the same value
settings.
Depending on user philosophy you use the rated current of the capacitor bank as a reference value including
the harmonic or the fundamental component current.

Parameter: Capacitor reference volt.

• Default setting (_:1781:15571:102) Capacitor reference volt. = 400.00 kV


With the parameter Capacitor reference volt., you set the reference voltage of the capacitor bank to
be protected. The reference voltage set here is the reference value for the percentage measured values and
setting values in percent.
Depending on user philosophy you can set the system reference value of the system voltage (busbar voltage)
or the capacitor rated voltage as a reference.

Parameter: Neutral point

• Default setting (_:1781:15571:149) Neutral point = isolated


With the parameter Neutral point, you specify whether the the neutral point in the protection range of
the differential protection is grounded or isolated. As this is not the case for the example application
described, use the default setting isolated.
You can find further information in the device manual 7UT8, chapter 6.2.3 Function Description Neutral-Point
Current Treatment.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1163


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

NOTE

i You do not need to change the parameters Winding configuration and Vector group numeral
for the example application described. You must establish the phase reference by way of the vector group
if the capacitor bank is in a delta connection.
You can find further information in the device manual 7UT8, chapter 6.2.3 Description Vector-Group
Correction.

Parameter: Winding configuration

• Default setting (_:1781:15571:104) Winding configuration = Y (Wye)


With the parameter Winding configuration, you set D (Delta) for a delta connection. A further star-
connection setting option is Y (Wye). The parameter Winding configuration is relevant for the differen-
tial protection function. You do not need to change this setting for the example application described.

Parameter: Vector group numeral

• Default setting (_:1781:15571:100) Vector group numeral = 0


This parameter is used to account for phase-angle rotation, which is expressed by a number.
Phase-angle rotation 0° 30° 60° 90° 120° 150° 180° 210° 240° 270° 300° 330°
Vector group 0 1 2 3 4 5 6 7 8 9 10 11
numeral

In the function group, the following information is displayed additionally in the setting sheet:

• Side number

• Identification of the measuring points used

• Adaptation factor for the 3-phase measuring point (with reference to the side)
You can set each Vector group numeral from 0 to 11 to the extent possible. Thus, for example, only even
numbers are possible for the vector groups Yy and Dd and only odd numbers are possible for Yd and Dy.
You do not need to change this setting for the example application described.

Function Group Capacitor Bank diff


Proceed with the following settings in the Capacitor bank diff function group for the I-DIFF function:

Parameter: Threshold (Setting the Characteristic-Curve Parameters)

• Default setting (_:11041:3) Threshold = 0.20 I/Irated,obj


You set the pickup threshold for the differential current with this parameter. This is the total current flowing
into the protection range during a short circuit, regardless of how it is distributed on the sides of the protected
object. The pickup value is relative to the rated current of the protected object. The default setting of 0.20
I/Irated,obj is a practical value between sensitivity and possible disturbing influence.

Parameter: Intersection 1 Irest

• Default setting (_:11041:101) Intersection 1 Irest = 0.67 I/Irated,obj


The maximum current of the measuring point is used as restraint current. If you have to expect dynamic trans-
mission faults of the current transformer even with small currents, half of the rated current is an appropriate
setting value.

Parameter: Slope 1

• Default setting (_:11041:100) Slope 1 = 0.30

1164 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

With the Slope 1, you avoid an overfunction of the differential protection with low-current external faults as
a consequence of current-transformer transmission faults (stationary and dynamic faults). The default setting
of 0.30 is sufficient for many applications.

Parameter: Intersection 2 Irest

• Default setting (_:11041:103) Intersection 2 Irest = 2.50 I/Irated,obj

NOTE

i If excessive current flows are cause to expect transmission problems for the current transformer, set Slope
2 to a higher value.

The parameter Intersection 2 Irest determines from which restraint current the Slope 2 begins. The
default setting 2.50 I/Irated,obj is a practical value.

Parameter: Slope 2

• Default setting (_:11041:102) Slope 2 = 0.70


With the parameter Slope 2, an overfunction of the differential protection is avoided with high-current
external faults as a consequence of current-transformer transmission faults (for example, due to saturation). A
value greater than or equal to double the value of Slope 1 is practical. As the default setting, 0.70 was
selected.

[dwdifaus-030912-01.tif, 2, en_US]

Figure 7-66 Characteristic Curve with the Default Settings

SIPROTEC 5, 7SJ82/7SJ85, Manual 1165


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

Parameter: Starting detection

• Default setting (_:11041:106) Starting detection = yes


To avoid an overfunction when connecting the capacitor banks, you can set the parameter Starting
detection = yes. Siemens recommends using the setting Starting detection = yes.

Parameter: Thresh. startup detection

• Default setting (_:11041:107) Thresh. startup detection = 0.1 I/Irated,obj


If the restraint current falls below this threshold value, the subsequently set characteristic-curve increase
becomes effective with activated function. The default setting value of 0.1 I/Irated,obj is recommended
for the application.

Parameter: Factor increasing char.

• Default setting (_:11041:108) Factor increasing char. = 2.0


An increase to the value 2.0 has proven itself to be sufficient for many applications.

Parameter: Max. perm. Start. time

• Default setting (_:11041:109) Max. perm. Start. time = 5.0 s


The setting value must lie above the maximum permissible starting time of the connected capacitor bank. To
ensure tripping by the capacitor-bank protection (make time/starting time supervision) and avoid overfunc-
tions, select a somewhat longer time (factor of 1.2 or higher).

Parameter: Factor increasing char. DC (DC-Component Detection)

• Default setting (_:11041:110) Factor increasing char. DC = 2.3


DC-component detection is always active. As a result of the DC components, transmission problems can arise
(for example, phase-angle rotations) in current transformers with small currents flowing. For this reason, the
Threshold and the Slope 1 are raised by the set factor. The default setting of 2.3 has proven itself with
numerous applications.

Parameter: Blocking with 2. harmonic (Inrush-Current Detection)

• Default setting (_:11041:115) Blocking with 2. harmonic = no


The inrush-current detection is not necessary for the capacitor-bank applications.

Parameter: 2nd harmonic content

• Default setting (_:11041:116) 2nd harmonic content = 15 %


For many practical applications, the default setting value of 15 % has proven useful. In exceptional cases, the
setting value can be decreased with a small proportion of 2nd harmonic. Avoid a setting under 10 %, however.
With an internal fault and current-transformer saturation, some proportion of 2nd harmonic also arises. Too
sensitive of a setting leads to a blocking of the protection function.

Parameter: Crossblock. time 2nd har.

• Default setting (_:11041:117) Crossblock. time 2nd har. = 0.00 s


Since the inrush currents develop differently in the 3 phases, the pickup value, for example, is not attained in
a phase, but the differential current exceeds the characteristic curve. Corrective action creates a mutual
blocking. If a time unequal to 0 s is set, the crossblock function works. If an overfunction arises, the setting
cannot be made until commissioning takes place. Do not set the duration for an excessive amount of time.
Practical values showed a setting between 3 and 5 periods.

1166 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

Detection of External Faults


In Figure 7-66, the range Add-on stabilization of external faults is represented. The range is described by
the parameters Threshold add-on stabiliz. and Slope 1. With an external short circuit, the differen-
tial currents can increase beyond this range and reach into the tripping area. With the following parameters,
time-limited blocking can be performed.

Parameter: Threshold add-on stabiliz.

• Default setting (_:11041:128) Threshold add-on stabiliz. = 2.00


The Threshold add-on stabiliz. parameter allows you to set the pickup value for the additional stabili-
zation. Due to the selected method of measurement, a setting value of 2.00 is practical. The additional stabili-
zation range is limited by the parameters Threshold add-on stabiliz. and Slope 1.

Parameter: Time of add-on stabiliz.

• Default setting (_:11041:129) Time of add-on stabiliz. = 0.30 s


As orientation for the setting value, you can use the operate time of the external feeder protection. Addition-
ally, take into account the break time of the circuit breaker. Thus, the following calculation rule results:
tZ rest ≥ tTrip,ext protection + tTrip,circuit breaker
The default value is a practical value. You must adapt the value appropriately to use. The value 0 deactivates
the detection of external faults.

Parameter: Crossblk. time add-on st.

• Default setting (_:11041:130) Crossblk. time add-on st. = 0.30 s


The additional stabilization acts separately on each phase. However, it can be extended to block all phases.
Siemens recommends the activation of the crossblock function with a corresponding setting of the time. The
set time must be identical to the time that is set for the duration of the additional stabilization.

Protection Stage I-DIFF Fast


The task of this protection stage is the fast detection of high-current internal short circuits (see also I-DIFF Fast
Differential Protection Function, Page 1155). For this reason, the protection stage must always be activated.

Parameter: Threshold

• Default setting (_:11071:3) Threshold = 7.5 I/Irated,obj


Siemens recommends that the threshold value is set greater or equal to the starting current.

Protection Stage I-DIFF Unrestrained


The task of this protection stage is the fast detection of high-current internal faults (see also I-DIFF Unre-
strained Differential Protection Function, Page 1158).

Parameter: Threshold

• Default setting (_:18002:3)Threshold = 10.0 I/Irated,obj


Use the description of the protection stage I-DIFF fast (Protection Stage I-DIFF Fast, Page 1167) to set the
threshold value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1167


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

7.8.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:11041:1 I-DIFF:Mode • off off
• on
• test
_:11041:2 I-DIFF:Operate & flt.rec. • no no
blocked
• yes
_:11041:6 I-DIFF:Operate delay 0.00 s to 60.00 s 0.00 s
Operate curve
_:11041:3 I-DIFF:Threshold 0.05 I/IrObj to 2.00 I/IrObj 0.20 I/IrObj
_:11041:100 I-DIFF:Slope 1 0.00 to 0.80 0.30
_:11041:101 I-DIFF:Intersection 1 Irest 0.00 I/IrObj to 5.00 I/IrObj 0.67 I/IrObj
_:11041:102 I-DIFF:Slope 2 0.25 to 0.95 0.70
_:11041:103 I-DIFF:Intersection 2 Irest 1.00 I/IrObj to 20.00 I/IrObj 2.50 I/IrObj
Starting detection
_:11041:106 I-DIFF:Starting detection • no no
• yes
_:11041:107 I-DIFF:Thresh. startup 0.1 I/IrObj to 2.0 I/IrObj 0.1 I/IrObj
detection
_:11041:108 I-DIFF:Factor increasing 1.0 to 5.0 2.0
char.
_:11041:109 I-DIFF:Max. perm. Start. 0.1 s to 180.0 s 5.0 s
time
DC offset detection
_:11041:110 I-DIFF:Factor increasing 1.0 to 5.0 2.3
char. DC
Inrush blocking
_:11041:115 I-DIFF:Blocking with 2. • no no
harmonic
• yes
_:11041:116 I-DIFF:2nd harmonic 10% to 45% 15%
content
_:11041:117 I-DIFF:Crossblock. time 0.00 s to 200.00 s; ∞ 0.00 s
2nd har.
Ext. fault detection
_:11041:128 I-DIFF:Threshold add-on 1.00 I/IrObj to 20.00 I/IrObj 2.00 I/IrObj
stabiliz.
_:11041:129 I-DIFF:Time of add-on 0.00 s to 5.00 s; ∞ 0.30 s
stabiliz.
_:11041:130 I-DIFF:Crossblk. time 0.00 s to 2.00 s; ∞ 0.30 s
add-on st.
I-DIFF fast
_:11071:1 I-DIFF fast:Mode • off off
• on
• test
_:11071:3 I-DIFF fast:Threshold 0.5 I/IrObj to 35.0 I/IrObj 7.5 I/IrObj
_:11071:6 I-DIFF fast:Operate delay 0.00 s to 60.00 s 0.00 s

1168 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

Addr. Parameter C Setting Options Default Setting


_:11071:100 I-DIFF fast:Operate & • no no
flt.rec. blocked
• yes
I-DIFF unrestr
_:1 I-DIFF unrestr:Mode • off off
• on
• test
_:3 I-DIFF unrestr:Threshold 0.5 I/IrObj to 35.0 I/IrObj 10.0 I/IrObj
_:6 I-DIFF unrestr:Operate 0.00 s to 60.00 s 0.00 s
delay
_:100 I-DIFF unrestr:Operate & • no no
flt.rec. blocked
• yes

7.8.6 Information List

No. Information Data Class Type


(Type)
General
_:2311:300 General:I diff. WYE O
_:2311:301 General:I restr. WYE O
_:2311:311 General:I diff. operate phA MV O
_:2311:312 General:I diff. operate phB MV O
_:2311:313 General:I diff. operate phC MV O
_:2311:314 General:I restr. operate phA MV O
_:2311:315 General:I restr. operate phB MV O
_:2311:316 General:I restr. operate phC MV O
_:2311:317 General:Adapt. adjustm. inact. SPS O
I-DIFF
_:11041:81 I-DIFF:>Block stage SPS I
_:11041:54 I-DIFF:Inactive SPS O
_:11041:52 I-DIFF:Behavior ENS O
_:11041:53 I-DIFF:Health ENS O
_:11041:55 I-DIFF:Pickup ACD O
_:11041:56 I-DIFF:Operate delay expired ACT O
_:11041:57 I-DIFF:Operate ACT O
_:11041:301 I-DIFF:Slope 1 MV O
_:11041:302 I-DIFF:Incr. of char. (Start) SPS O
_:11041:303 I-DIFF:Increase of char. (DC) SPS O
_:11041:304 I-DIFF:Blocked by inrush SPS O
_:11041:305 I-DIFF:Blocked by 2.Harmon. ACT O
_:11041:306 I-DIFF:Crossblock by 2.Harm. SPS O
_:11041:312 I-DIFF:Blocked by ext. fault ACT O
_:11041:313 I-DIFF:Crossbl. by ext. fault SPS O
_:11041:316 I-DIFF:CWA int. fault detected SPS O
I-DIFF fast
_:11071:81 I-DIFF fast:>Block stage SPS I
_:11071:54 I-DIFF fast:Inactive SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1169


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks

No. Information Data Class Type


(Type)
_:11071:52 I-DIFF fast:Behavior ENS O
_:11071:53 I-DIFF fast:Health ENS O
_:11071:55 I-DIFF fast:Pickup ACD O
_:11071:57 I-DIFF fast:Operate ACT O
_:11071:56 I-DIFF fast:Operate delay expired ACT O
I-DIFF unrestr
_:18002:81 I-DIFF unrestr:>Block stage SPS I
_:18002:54 I-DIFF unrestr:Inactive SPS O
_:18002:52 I-DIFF unrestr:Behavior ENS O
_:18002:53 I-DIFF unrestr:Health ENS O
_:18002:55 I-DIFF unrestr:Pickup ACD O
_:18002:57 I-DIFF unrestr:Operate ACT O
_:18002:56 I-DIFF unrestr:Operate delay expired ACT O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O

1170 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.9 Detuning Supervision for Capacitor Banks

7.9 Detuning Supervision for Capacitor Banks

7.9.1 AC-Filter Detuning Supervision

Tuned AC filters serve to provide reactive power and to absorb specific frequencies from the busbar. They
usually consist of the upper-voltage side capacitor (for providing reactive power) and the tuning section (for
tuning to the frequencies to be absorbed). The tuning section consists of primary C, L and, if required, R
elements, refer also to Figure 7-67.
Under normal operation, the RLC characteristics of the filter – the impedances – are identical per phase. A
change in the impedance of one phase indicates that the filter characteristic of this phase has changed. This
situation (a detuned filter) is not wanted and shall be detected.
The primary elements of the AC filter shall be subject of regular maintenance intervals where the compliance
with the tolerances of the rated values specified in the design need to be checked. For the detection of
detuning between the maintenance intervals, the protection device can be applied. Detuning supervision for
the upper-voltage side voltage capacitor can be achieved by applying the phase-selective Current unbalance
function (ANSI 60C), especially by using the counter function.
A criterion for the supervision of the primary elements of the tuning section is the ground or zero-sequence
current (3I0) of the AC filter. The fundamental phase current of the AC filter is determined by the phase capac-
itance of the upper-voltage side capacitor. Consequently, a difference in the phase capacitances of the upper-
voltage side capacitor will cause a fundamental ground current. Therefore it is not sufficient for the tuning-
section supervision to evaluate only the fundamental ground current. Under normal operation and symmet-
rical network conditions, the fundamental ground current will be 0. An unbalance in the phase impedances
(detuning) will cause a ground current. A detuning of the tuning section will mainly cause harmonics in the
ground current. Thus, the RMS value of the ground current needs to be evaluated. For a detuning supervision
of the tuning section, the function OCP, ground (ANSI 50N) with the measuring method RMS value is applied.
This allows detecting harmonics up to the 50th harmonic with high precision (refer also to Technical data).
When selecting the settings (pickup value, operate delay and function mode) for the function OCP, ground
(ANSI 50N) the present network connecting conditions must be considered! Otherwise short-term power-
system unbalances (for example, 1-pole fast auto reclosing) or statically present harmonics in the zero-
sequence system may cause an overfunction. Since the primary elements of the AC filter are directly or inher-
ently protected by other protection functions and due to the possible influence of the network conditions on
the function OCP, ground (ANSI 50N), this function should be configured only as alarm function and not as
tripping function.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1171


C53000-G5040-C017-A, Edition 06.2019
Capacitor Bank Protection
7.9 Detuning Supervision for Capacitor Banks

[dw_AC-Filter_detuning-supervision, 1, en_US]

Figure 7-67 Application Overview

1172 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
8 Control Functions

8.1 Introduction 1174


8.2 Switching Devices 1177
8.3 Control Functionality 1205
8.4 Synchronization Function 1227
8.5 Switching Sequences 1290
8.6 User-Defined Function Block [Control] 1297
8.7 CFC-Chart Settings 1302
8.8 Transformer Tap Changers 1304
8.9 Voltage Controller 1316
8.10 Point-on-Wave Switching 1383

SIPROTEC 5, 7SJ82/7SJ85, Manual 1173


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.1 Introduction

8.1 Introduction

8.1.1 Overview

The SIPROTEC 5 series of devices offers powerful command processing capability as well as additional func-
tions that are needed when serving as bay controllers for the substation automation technology or when
providing combi-protection. The object model for the devices is based on the IEC 61850 standard, making the
SIPROTEC 5 series of devices ideally suited for use in systems employing the IEC 61850 communication
protocol. In view of the function blocks necessary for the control functions, other logs are also used.

8.1.2 Concept of Controllables

The concept of so-called controllables is based on the data model described in IEC 61850. Controllables are
objects that can be controlled, such as a switch with feedback. The model of a transformer tap changer, for
example, contains controllables. The controllables are identifiable by their last letter C of the data type (for
example, DPC = Double Point Controllable/Double Command with feedback or BSC = Binary-Controlled Step
Position Indication / transformer tap command with feedback).

1174 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.1 Introduction

[sc_control, 1, en_US]

(1) Position (connect with binary inputs)


(2) Signalization of the current condition
(3) Command output (connect with relay)

The trip, opening and the close commands are connected to the relays. For the trip command, a choice
between saved and unsaved output is possible. The position is connected with 2 binary inputs (double-point
indication). In addition, signals are available that display the current state of the switch (not selected, off, on,
intermediate position, disturbed position). These signals can be queried in CFC for example, in order to
build interlocking conditions.

Control Models
You can set the operating mode of the controllables by selecting the control model.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1175


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.1 Introduction

4 different control models are available:

• Direct without feedback monitoring (direct w. normal secur.)

• With reservation (SBO)32 without feedback monitoring (SBO w. normal secur.)

• Direct with feedback monitoring (direct w. enh. security)

• With SBO with feedback monitoring (SBO w. enh. security)


The next figure shows the command sources, command types, and control models.

[dwsteuer-190912-01.tif, 1, en_US]

Figure 8-1 Command Sources, Command Types and Control Models

The figure shows the control models (right) with the respective control mechanisms (center). The standard
control model for a switching command in an IEC 61850 compliant system is SBO with feedback monitoring
(SBO w. enh. security). This control model is the default setting for newly created switching devices.

32 SBO: Select Before Operate

1176 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

8.2 Switching Devices

8.2.1 General Overview

The following switching devices can be found in the DIGSI 5 library in the Circuit-breaker and Switching-
devices function groups (see following figures).

[sccbausw, 1, en_US]

Figure 8-2 Selecting the Circuit-Breaker Switching Device Using the DIGSI Circuit-Breaker Function Group
Menu

[scswausw, 1, en_US]

Figure 8-3 Selecting the Remaining Switching Devices Using the DIGSI Switching-Devices Menu

8.2.2 Switching Device Circuit Breaker

8.2.2.1 Structure of the Circuit-Breaker Switching Device


This chapter describes the control properties of the Circuit-breaker switching device.
The Circuit-breaker switching device contains the following function blocks that are needed for control:

• Function block Circuit breaker

• Function block Control

• Function block Interlocking


This corresponds to the logical nodes XCBR, CSWI, and CILO in IEC 61850.
In the case of protection devices or combined protection and control devices, additional functions can be
contained in the Circuit-breaker switching device, for example, Synchrocheck, the Automatic reclosing
(AREC), the Trip logic or Manual On function. However, these are not relevant for the control function. The
description of these functions can be found in the chapter Protection and Automatic Functions. In addition,
other functions can be initialized. The description of these functions can be found in the chapter Protection
Functions.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1177


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

[dwbreake-220512-01.tif, 1, en_US]

Figure 8-4 Control Function Blocks of the Circuit-Breaker Switching Device

The circuit breaker in DIGSI 5 is linked with the binary inputs that acquire the switch position via information
routing. The circuit breaker in DIGSI 5 is also linked with the binary outputs that issue the switching
commands.

NOTE

i When setting the parameters of a device, you will find 2 circuit-breaker types in the Global DIGSI 5 library:
- 3-pole circuit breaker or 1-pole circuit breaker, depending on the device type selected (3-pole or 1-pole
tripping)
- Circuit breaker (status only)

1178 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Function Blocks of the Circuit Breaker

Table 8-1 Function Blocks of the Circuit-Breaker Function Group

Function Description Parameter Function


Block
Circuit The Circuit-breaker function Output time The circuit breaker forms the
breaker block in the SIPROTEC 5 switch position from the posi-
device represents the physical tions of the binary inputs and
switch. also outputs the command via
the binary outputs.
Control Command processing Control model Command check, communica-
SBO time-out tion with the command
Feedback monitoring time source and with the function
block Circuit breaker
Check switching
authority
Check if pos. is reached
Check double activat.
blk.
Check blk. by protection
Inter- Switchgear interlocking Interlocking condition (depos- The Interlocking functionality
locking protection ited in CFC) generates the releases for
switchgear interlocking
protection.

The setting values of the parameter can be found in the chapter 8.2.2.2 Application and Setting Notes.

Additional Setting Options of the Circuit-Breaker Switching Element


The setting options of the circuit breaker are assigned to the function blocks on the basis of their relevance.
Additional setting options of the circuit breakers that cannot be directly assigned to one of the 3 function
blocks are nevertheless available:

Table 8-2 Setting Options of the Controllable Command with Feedback in the Control Function
Block of the Circuit Breaker.

Properties Function To Be Found in


Software filtering time Software filtering time for position Position of the Control function
detection block 33
Retrigger filter (yes/no) Switching retriggering of the Position of the Control function
filtering time on/off by changing block33
the position
Message time before Consideration of the hardware Position of the Control function
filtering (yes/no) filtering time for position-detection block33
time stamp
Suppress intermediate When activated, only the inter- Position of the Control function
position (yes/no) mediate position is suppressed by block33
the duration of the software
filtering time.

33 First click Position and then click the Details button in the Properties window (below).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1179


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Properties Function To Be Found in


Treatment of spontaneous If you select the General soft- Position of the Control function
position changes (Gen. Soft- ware filter setting, the general block33
ware Filt./Spont. Software Filt.) settings for software filtering of
spontaneous position changes and
for position changes caused by a
switching command apply. By
selecting Spontaneous soft-
ware filter, a separate filtering
is activated for spontaneous posi-
tion changes.
Spontaneous software Software filtering time for sponta- Position of the Control function
filtering time neous position changes block33
Spontaneous retrigger Switching on/off retriggering of the Position of the Control function
filter (yes/no) filtering time by spontaneous posi- block33
tion change
Spontaneous indication Consideration of the hardware Position of the Control function
timestamp before filtering filtering time for position-detection block33
(yes/no) time stamp in case of a sponta-
neous change
Inhibit intermediate posi- When activated, only the sponta- Position of the Control function
tion for a spontaneous neous change to the intermediate block33
chng. (yes/no) position is suppressed by the dura-
tion of the software filtering time.

Table 8-3 Setting Options of the Controllable Position in the Circuit-Breaker Function Block (Chatter
Blocking)

Properties Function To Be Found in


Chatter blocking (yes/no) Switching chatter blocking on/off Position of the Circuit-breaker
function block33

Table 8-4 Additional Settings in the Device Settings having Effects on the Circuit Breaker

Properties Function To Be Found in


Number of permissible Chatter-blocking setting value: Device settings (to be found under
status changes Once for the entire device Settings)
Chatter test time
Number of chatter tests
Chatter idle time
Chatter check time

The inputs and outputs as well as the setting options of the Circuit-breaker and Control function blocks are
described in the next section (see 8.2.2.3 Connection Variants of the Circuit Breaker).

Interlocking
The Interlocking function block generates the releases for switchgear interlocking protection. The actual
interlocking conditions are deposited in CFC. For more information on this, see the general chapter
8.3.1 Command Checks and Switchgear Interlocking Protection.

8.2.2.2 Application and Setting Notes

Circuit Breaker
The Circuit-breaker function block in the SIPROTEC 5 device represents the physical switch device. The task of
the circuit breaker is to replicate the switch position from the status of the binary inputs.

1180 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

The following figure shows the logical inputs and outputs of the Circuit-breaker function block.

[dwfuncls-140212-01.tif, 2, en_US]

Figure 8-5 Logical Inputs and Outputs of the Circuit-Breaker Function Blocks

Table 8-5 and Table 8-6 list the inputs and outputs with a description of their function and type. For inputs,
the effect of Quality = invalid on the value of the signal is described.

EXAMPLE
If the signal >Ready has the Quality = invalid, then the value is set to cleared. In problematic operating
states, the circuit breaker should signal that it is not ready for an Off-On-Off cycle.

Table 8-5 Inputs of the Circuit-Breaker Function Block

Signal Name Description Type Default Value if


Signal Quality =
invalid
>Ready The signal >Ready indicates that the OFF-ON-OFF SPS Going
cycle is possible with the circuit breaker.
This signal is used for the AREC standby status.
>Acquisition The binary input activates acquisition blocking. You SPS Unchanged
blocking can also set this binary input with an external toggle
switch.
>Reset Acquisition blocking and the substitution of the circuit SPS Unchanged
AcqBlk&Subst breaker are reset with this input. If the input is acti-
vated, setting the acquisition blocking and the substi-
tution is blocked.
>Reset switch Among other things, the binary input sets the opera- SPS Unchanged
statist. tion counter for the switch to the value 0.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1181


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Signal Name Description Type Default Value if


Signal Quality =
invalid
External health The binary input External health reflects the ENS Unchanged
circuit-breaker status (EHealth).
This input will be set by the CFC using the BUILD_ENS
block. In turn, BUILD_ENS can query binary inputs that
represent the conditions OK, Warning, or Alarm (as
a result of the function Trip-circuit supervision).
Position The signal Position can be used to read the circuit- DPC Unchanged
breaker position with double-point indication.

If the quality of the input signal assumes the status Quality = invalid, then the standby status (EHealth) of the
Circuit-breaker function block is set to Warning.

Table 8-6 Outputs of the Circuit-Breaker Function Block

Signal Name Description Type


Definitive trip Protection has finally been tripped. SPS
Alarm suppression The signaling contact for external alarm inhibition is suppressed during SPS
the runtime of automatic reclosing (optional) as well as during the
command output of switching commands.
Op.ct. The information counts the number of switching cycles of the circuit INS
breaker.
Trip/open cmd. This logic output is responsible for the command output Off. SPS
Close command This logic output is responsible for the command output On. SPS
Command active The binary output Command active is responsible for signaling a SPS
running command (relay active or selected switching device (SEL)).
CB open hours The statistical value counts the hours the circuit breaker is open. INS
Operating hours The statistical value counts the hours where at least one phase current is INS
greater than the Current thresh. CB open parameter.

Control
It is the task of the controls to execute command checks and establish communication between the command
source and the circuit breaker. Using the control settings, you specify how the commands are to be processed
(see also chapter 8.3.1 Command Checks and Switchgear Interlocking Protection).
Through the function SBO (Select Before Operate, reservation34), the switching device is reserved prior to the
actual switching operation, thus it remains locked for additional commands. Feedback monitoring provides
information about the initiator of the command while the command is in process, that means, informing
whether or not the command was implemented successfully. These 2 options can be selected individually in
the selection of the control model, so that 4 combinations in total are available (see the following table).
The control makes the following settings available (see next table).
Parameters Default Setting Possible Parameter Values
(_:4201:101) Control model SBO w. enh. direct w. normal secur.
security35 SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
(_:4201:102) SBO time-out 30.00 s 0.01 s to 1800 s
(Increment: 0.01 s)

34 In the IEC 61850 standard, reservation is described as Select before Operate (SBO).
35 This default setting is the standard control model for a switching command in an IEC 61850-compliant system.

1182 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Parameters Default Setting Possible Parameter Values


(_:4201:103) Feedback monitoring time 1.00 s 0.01 s to 1800 s
(Increment: 0.01 s)
(_:4201:104) Check switching authority yes no
yes
advanced
(_:4201:105) Check if pos. is reached yes no
yes
(_:4201:106) Check double activat. blk. yes no
yes
(_:4201:107) Check blk. by protection yes no
yes

The following figure shows the logical inputs and outputs of the Control function block.

[dwsteue1-100611-01.tif, 1, en_US]

Figure 8-6 Logical Inputs and Outputs of the Control Function Block

Table 8-7 Control Function Block Input and Output

Signal Description Type Value if Signal


Name Quality=Invalid
Cmd. with With the Cmd. with feedback signal, the circuit- Controllable Unchanged
feedback breaker position is accepted via the double-point indi- (DPC)
cation of the Circuit-breaker function block and the Unchanged
command is issued.

In the information routing of DIGSI 5, you may select a function key as a possible command source. In addi-
tion, it is displayed here if the command is activated by CFC. The logging is routed here.

8.2.2.3 Connection Variants of the Circuit Breaker


For each switching device, you can establish the number of poles (for example, 1-pole, 1.5-pole or 2-pole)
that are switched with or without feedback. This results in the necessary amount of information to be
processed, thus establishing the command type.
Whether the circuit breaker is triggered 1-, 1.5-, or 2-pole, depends on the design of the auxiliary and control-
voltage system. In most cases, the activation of the opening coil of the circuit breaker is 1-pole.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1183


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Table 8-8 Meaning of the Abbreviations of the Connection Variants

Abbreviation Meaning of the Abbreviation of the Connection Variants


BO Binary output
L+; L- Control voltage
A Trip command
Gnd Close command

Table 8-9 Meaning of the Abbreviations in DIGSI

Abbreviation Description of the Input in DIGSI


V Unsaved trip command
Click the right mouse button and enter V.
X Close Command
Click the right mouse button and enter X for the respective binary output.
OH The switching-device feedback is in the position OFF, if there is voltage present at the
routed binary input (H).
Click the right mouse button and enter OH.
OL The switching-device feedback is in the position OFF, if there is no voltage present at
the routed binary input (L).
Click the right mouse button and enter OL.
GH The switching-device feedback is in the position ON, if there is voltage present at the
routed binary input (H).
Click the right mouse button and enter CH.
CL The switching-device feedback is in the position ON, if there is no voltage present at
the routed binary input (H).
Click the right mouse button and enter CL.
TL Trip command stored
Click the right mouse button and enter TL.

Connection Variant: 3-Pole Circuit Breaker


This is the standard type for the control function. All 3 individual poles of the circuit breaker are triggered
together by a double command.

[dw3polls-070611-01.tif, 1, en_US]

Figure 8-7 3-Pole Circuit Breaker

1184 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

1-Pole Triggering

[dw1polig-020211-01.tif, 1, en_US]

Figure 8-8 1-Pole Triggering

[scrang1pLS1p, 1, en_US]

Figure 8-9 1-Pole Triggering, Routing in DIGSI

You can select the contacts for On and Off as desired. They need not necessarily be next to one another. The
letter U represents an unlatched command. Alternatively, TL (latched tripping) can be selected.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1185


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

1.5-Pole Triggering

[dw5polig-020211-01.tif, 1, en_US]

Figure 8-10 1.5-Pole Triggering

[scrang1pLS15p, 1, en_US]

Figure 8-11 1.5-Pole Triggering, Routing in DIGSI

1186 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

2-Pole Triggering

[dw2polan-020211-01.tif, 1, en_US]

Figure 8-12 2-Pole Triggering

[scrang1pLS13p, 1, en_US]

Figure 8-13 2-Pole Triggering, Routing in DIGSI

Connection Variant: 1-Pole Circuit Breaker


The 1-pole circuit breaker is used for separate activation and acquisition of the individual poles of a circuit
breaker. It is intended for common use by 1-pole protection and control functions.

NOTE

i The wiring of the Circuit-breaker function group with binary inputs and binary outputs occurs once per
device.

The control function in this type switches all 3 poles on or off simultaneously.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1187


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

The protection functions can switch off 1-pole. The close command is always 3-pole. Optionally, only the open
poles are closed.

[dw1polls-020211-01.tif, 1, en_US]

Figure 8-14 Circuit Breaker with 1-Pole Triggering

For the circuit breaker with 1-pole triggering, triggering takes place via one relay per phase for the trip
command and via a 4th relay for the close command (see next figure).

[dw1panls-020211-01.tif, 1, en_US]

Figure 8-15 1-Pole Connection of a Circuit Breaker

1188 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

[scrang1pLS13pz, 1, en_US]

Figure 8-16 Routing in DIGSI

In the previous figure, the switch is connected 1-pole. The protection trip command is routed individually for
the 3 phases ( Trip only pole A to Trip only pole C ). The protection trip command is routed for
the 3 phases ( Trip/open cmd. 3-pole ). The control always switches off the 3 poles of the switch. In
addition, the 3 U (Unlatched) routings of the trip and open command are set to 3-pole. This routing is also
used by protection functions that trip 3 poles. The close command is issued simultaneously for all 3 phases.

Example: Trip Command during Transition from 1-Pole to 3-Pole


During a transition from 1-pole to 3-pole tripping, Trip only pole A remains active. To inform, for
example, an external AREC whether it is a 1-pole or 3-pole trip, you can use the indication Trip
logic:Trip indication:1-pole and Trip logic:Trip indication:3-pole.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1189


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

[dw_trip-command_between_1p-3p, 1, en_US]

Acquisition of the Circuit-Breaker Position


The binary inputs for feedback of the switch position are routed as shown in the previous figure (also see
chapter 5.7.7.3 Acquisition of Circuit-Breaker Auxiliary Contacts and Further Information ).

1190 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

[scrang1pLSHk, 1, en_US]

Figure 8-17 Routing of the 1-Pole in DIGSI

The meaning of abbreviations can be found in Table 8-8 and Table 8-9.
The indication Command active can also be routed to a binary output. This binary output is always active if
either a close or trip command is pending, or the switching device was selected by the command control.

8.2.2.4 Settings

Addr. Parameter C Setting Options Default Setting


Ref. for %-values
_:2311:101 General:Rated 0.20 A to 100000.00 A 1000.00 A
normal current
_:2311:102 General:Rated 0.20 kV to 1200.00 kV 400.00 kV
voltage
Breaker settings
_:2311:112 General:Current 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
thresh. CB open 5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2311:136 General:Op. mode • unbalancing unbalancing
BFP
• I> query

SIPROTEC 5, 7SJ82/7SJ85, Manual 1191


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Addr. Parameter C Setting Options Default Setting


Trip logic
_:5341:103 Trip logic:Reset of • with I< with I<
trip command
• with I< & aux.contact
• with dropout
Circuit break.
_:4261:101 Circuit 0.02 s to 1800.00 s 0.10 s
break.:Output time
_:4261:105 Circuit • with trip always
break.:Indicat. of
breaking values
• always

Manual close
_:6541:101 Manual 0.01 s to 60.00 s 0.30 s
close:Action time
_:6541:102 Manual close:CB 0.00 s to 60.00 s 0.00 s
open dropout delay
Control
_:4201:101 Control:Control • status only SBO w. enh.
model security
• direct w. normal secur.
• SBO w. normal secur.
• direct w. enh. security
• SBO w. enh. security
_:4201:102 Control:SBO time- 0.01 s to 1800.00 s 30.00 s
out
_:4201:103 Control:Feedback 0.01 s to 1800.00 s 1.00 s
monitoring time
_:4201:104 Control:Check • no yes
switching authority
• yes
• advanced
_:4201:105 Control:Check if • no yes
pos. is reached
• yes
_:4201:106 Control:Check • no yes
double activat. blk.
• yes
_:4201:107 Control:Check blk. • no yes
by protection
• yes
Switching authority
_:4201:151 Control:Swi.dev. • 0 false
related sw.auth.
• 1
_:4201:152 Control:Specific sw. • 0 true
authorities
• 1
_:4201:115 Control:Specific • station station/remote
sw.auth. valid for
• station/remote
• remote
_:4201:153 Control:Num. of 2 to 5 2
specific sw.auth.
_:4201:155 Control:Ident. Freely editable text
sw.auth. 1

1192 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Addr. Parameter C Setting Options Default Setting


_:4201:156 Control:Ident. Freely editable text
sw.auth. 2
_:4201:157 Control:Ident. Freely editable text
sw.auth. 3
_:4201:158 Control:Ident. Freely editable text
sw.auth. 4
_:4201:159 Control:Ident. Freely editable text
sw.auth. 5
_:4201:154 Control:Multiple • 0 false
specific sw.auth.
• 1
CB test
_:6151:101 CB test:Dead time 0.00 s to 60.00 s 0.10 s
_:6151:102 CB test:Trip only • 0 false
• 1
_:6151:103 CB test:Consider • 0 false
current criterion
• 1
_:6151:104 CB test:Current 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
threshold 5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A

8.2.2.5 Information List

No. Information Data Class Type


(Type)
Trip logic
_:5341:300 Trip logic:Trip indication ACT O
Circuit break.
_:4261:500 Circuit break.:>Ready SPS I
_:4261:501 Circuit break.:>Acquisition blocking SPS I
_:4261:502 Circuit break.:>Reset switch statist. SPS I
_:4261:504 Circuit break.:>Reset AcqBlk&Subst SPS I
_:4261:503 Circuit break.:External health ENS I
_:4261:53 Circuit break.:Health ENS O
_:4261:58 Circuit break.:Position 3-pole DPC C
_:4261:300 Circuit break.:Trip/open cmd. 3-pole SPS O
_:4261:301 Circuit break.:Close command SPS O
_:4261:302 Circuit break.:Command active SPS O
_:4261:303 Circuit break.:Definitive trip SPS O
_:4261:304 Circuit break.:Alarm suppression SPS O
_:4261:306 Circuit break.:Op.ct. INS O
_:4261:307 Circuit break.:ΣI Brk. BCR O
_:4261:308 Circuit break.:ΣIA Brk. BCR O
_:4261:309 Circuit break.:ΣIB Brk. BCR O
_:4261:310 Circuit break.:ΣIC Brk. BCR O
_:4261:311 Circuit break.:Break.-current phs A MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1193


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

No. Information Data Class Type


(Type)
_:4261:312 Circuit break.:Break.-current phs B MV O
_:4261:313 Circuit break.:Break.-current phs C MV O
_:4261:317 Circuit break.:Break. current 3I0/IN MV O
_:4261:314 Circuit break.:Break. voltage phs A MV O
_:4261:315 Circuit break.:Break. voltage phs B MV O
_:4261:316 Circuit break.:Break. voltage phs C MV O
_:4261:322 Circuit break.:CB open hours INS O
_:4261:323 Circuit break.:Operating hours INS O
Manual close
_:6541:501 Manual close:>Block manual close SPS I
_:6541:500 Manual close:>Input SPS I
_:6541:300 Manual close:Detected SPS O
Reset LED Group
_:13381:500 Reset LED Group:>LED reset SPS I
_:13381:320 Reset LED Group:LED have been reset SPS O
Control
_:4201:503 Control:>Sw. authority local SPS I
_:4201:504 Control:>Sw. authority remote SPS I
_:4201:505 Control:>Sw. mode interlocked SPS I
_:4201:506 Control:>Sw. mode non-interl. SPS I
_:4201:53 Control:Health ENS O
_:4201:58 Control:Cmd. with feedback DPC C
_:4201:302 Control:Switching auth. station SPC C
_:4201:308 Control:Enable sw. auth. 1 SPC C
_:4201:309 Control:Enable sw. auth. 2 SPC C
_:4201:310 Control:Enable sw. auth. 3 SPC C
_:4201:311 Control:Enable sw. auth. 4 SPC C
_:4201:312 Control:Enable sw. auth. 5 SPC C
_:4201:313 Control:Switching authority ENS O
_:4201:314 Control:Switching mode ENS O
Interlocking
_:4231:500 Interlocking:>Enable opening SPS I
_:4231:501 Interlocking:>Enable closing SPS I
_:4231:502 Interlocking:>Enable opening(fixed) SPS I
_:4231:503 Interlocking:>Enable closing (fixed) SPS I
_:4231:53 Interlocking:Health ENS O
CB test
_:6151:53 CB test:Health ENS O
_:6151:301 CB test:Test execution ENS O
_:6151:302 CB test:Trip command issued ENS O
_:6151:303 CB test:Close command issued ENS O
_:6151:304 CB test:Test canceled ENS O
_:6151:311 CB test:3-pole open-close SPC C

1194 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

8.2.3 Disconnector Switching Device

8.2.3.1 Structure of the Disconnector Switching Device


Like the circuit breaker, the Disconnector switching device contains the following 3 function blocks:

• Function block Disconnector

• Function block Control

• Function block Interlocking


This corresponds to the logical nodes XSWI, CSWI, and CILO in IEC 61850.

NOTE

i In contrast to the Circuit-breaker switching device, the Disconnector switching device cannot contain any
additional functions because protection functions or synchronization can have no effect on the discon-
nector.

The following figure shows the structure of the Disconnector switching element:

[dwdiscon-190612-01.tif, 2, en_US]

Figure 8-18 Control-Relevant Function Blocks of the Disconnector Switching Device

SIPROTEC 5, 7SJ82/7SJ85, Manual 1195


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

The Disconnector switching device behaves like the Circuit-breaker switching device. The only difference is
the designation of the function block that the physical switch provides (disconnector instead of circuit
breaker). Blocking by protection is not provided in the analysis of the Control function block.
The Disconnector switching device is available in the DIGSI 5 library in 2 different variants:

• Disconnector with 3-pole connection


The device switches all 3 poles of the disconnector on or off simultaneously.

• Disconnector without triggering (only status detection, no control)


This variant is rarely encountered. It is encountered with grounding switches that frequently cannot be
controlled, but only provide their current position. In addition, the position of a disconnector in a neigh-
boring bay can be acquired.

Function Blocks of the Disconnector

Table 8-10 Function Blocks of the Disconnector Function Group

Function Description Parameter Function


Block
Discon- The disconnector represents Maximum output time The disconnector replicates
nector the physical switch in the Seal-in time the switch position from the
SIPROTEC 5 device. Switching-device type status of the binary inputs
and also transmits the
command via the binary
outputs.
Control Command processing Control model Command checks, commu-
SBO time-out nication with the command
Feedback monitoring time source and with the func-
tion block Disconnector
Check switching authority
Check if pos. is reached
Check double activat.
blk.
Inter- Switchgear interlocking Interlocking condition (deposited The Interlocking function-
locking protection in CFC) ality generates the releases
for switchgear interlocking
protection.

The setting values of the parameter can be found in the chapter 8.2.3.2 Application and Setting Notes.

Additional Settings of Disconnector Switching Element


The settings of the disconnector are assigned to the function blocks on the basis of their relevance. Additional
disconnector settings that cannot be directly assigned to one of the 3 function blocks and are identical to the
circuit-breaker settings are available:

Table 8-11 Setting Options of the Controllable Command with Feedback in the Control Function
Block of the Circuit Breaker

Characteristics Function To Be Found in


Software filtering time Software filtering time for position Position of the Control(1) function
detection block
Retrigger filter (yes/no) Switching retriggering of the Position of the Control(1) function
filtering time on/off by changing block
the position
Message time before Consideration of the hardware Position of the Control(1) function
filtering (yes/no) filtering time for position-detection block
time stamp

1196 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Characteristics Function To Be Found in


Suppress intermediate When activated, only the inter- Position of the Control(1) function
position (yes/no) mediate position is suppressed by block
the duration of the software
filtering time.
Spontaneous position If the General software Position of the Control(1) function
changes filtered by (Gen. filter setting is selected, the block
Software Filt./Spont. Software Filt.) general settings for software
filtering of spontaneous position
changes and for position changes
caused by a switching command
apply. By selecting Spontaneous
software filter, a separate
filtering is activated for sponta-
neous position changes.
Spontaneous software Software filtering time for sponta- Position of the Control(1) function
filter time neous position changes block
Spontaneous retrigger Switching on/off retriggering of the Position of the Control(1) function
filter (yes/no) filtering time by spontaneous posi- block
tion change
Spontaneous indication Consideration of the hardware Position of the Control(1) function
timestamp before filtering filtering time for position-detection block
(yes/no) time stamp in case of a sponta-
neous change
Spontaneous suppress When activated, only the sponta- Position of the Control(1) function
intermediate position neous change to the intermediate block
(yes/no) position is suppressed by the dura-
tion of the software filtering time.
(1) First click Position and then click the Details button in the Properties window (below).

Table 8-12 Setting Options of the Controllable Position in the Disconnector Function Block (Chatter
Blocking)

Characteristics Function To Be Found in


Chatter blocking (yes/no) Switching chatter blocking on/off Position of the Disconnector (1)
function block
(1) First click Position and then click the Details button in the Properties window (below).

Table 8-13 Additional Settings in the Device Settings with Effects on the Disconnector

Characteristics Function To Be Found in


Number of permissible Chatter-blocking setting value: Device settings (to be found under
state changes Once for the entire device Settings)
Chatter test time
Number of chatter tests
Chatter dead time
Chatter test time

The inputs and outputs as well as the setting options of the Disconnector switch function block will be
described in the next chapter (see 8.2.3.3 Trigger Variants of the Disconnector). The Control function block is
described identically as the Circuit-breaker function block, with the exception that the command check
blocking is available through protection only with the circuit breaker.
More information on this is can be found in chapter 8.2.2.2 Application and Setting Notes.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1197


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Interlocking
The Interlocking function block generates the releases for switchgear interlocking protection. The actual
interlocking conditions are deposited in CFC. For more information on this, see the general chapter
8.3.1 Command Checks and Switchgear Interlocking Protection.

8.2.3.2 Application and Setting Notes

Disconnector
The disconnector represents the physical switch in the SIPROTEC 5 device. The task of the disconnector is to
replicate the switch position from the status of the binary inputs.
The Disconnector function block is linked automatically via the information matrix with the binary inputs that
register the switch position and with the binary outputs that issue the switching commands.
The Disconnector function block makes the following settings available (see next table).
Parameters Default Setting Possible Parameter Values
(_:5401:101) Maximum output time 10.00 s 0.02 s to 1800 s
The Maximum output time specifies the duration (Increment: 0.01 s)
of the output pulse created by the switching
command.
(_:5401:102) Seal-in time 0.00 s 0 s to 60 s
If the target actuating position is not yet attained
although feedback has already been received, the
output time is extended by the Seal-in time. The
Seal-in time is relevant for equipment that sends
feedback before the switching operation is
completely performed. The Seal-in time is only
considered for control models with feedback moni-
toring.
(_:5401:103) Switching-device type disconnector switch-disconnector
The Switching-device type specifies the type of disconnector
the switching device. grounding switch
fast grounding switch

NOTE

i The parameter Switching-device type is effective only on the IEC 61850 interface. This parameter is
used to set the disconnector switching device type for communication via IEC 61850. It is a mandatory data
object in the IEC 61850 standard.

The following figure shows the logical inputs and outputs of the Disconnector function block.

1198 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

[dwoutinp-150212-01.tif, 2, en_US]

Figure 8-19 Logical Inputs and Outputs of the Disconnector Function Block

Table 8-14 and Table 8-15 list the inputs and outputs with a description of their function and type. For inputs,
the effect of Quality = invalid on the value of the signal is described.

Table 8-14 Inputs of the Disconnector Function Block

Signal Name Description Type Value if Signal


Quality=Invalid
>Acquisition The binary input activates acquisition blocking. You SPS Unchanged
blocking can also set this binary input with an external toggle
switch.
>Reset Acquisition blocking and the substitution of the circuit SPS Unchanged
AcqBlk&Subst breaker are reset with this input. If the input is acti-
vated, setting of the acquisition blocking and of the
substitution is blocked.
>Reset switch The binary input sets the operation counter for the SPS Unchanged
statist. switch to the value 0.
Position The binary input Position can be used to read the DPC Unchanged
disconnector position with double-point indication.

If the quality of the input signal assumes the status Quality = invalid, then the standby status (Health) of the
Disconnector function block is set to Warning.

Table 8-15 Outputs of the Disconnector Function Block

Signal Name Description Type


Open command This binary output is responsible for the command SPS
output Off.
Close command This binary output is responsible for the command SPS
output On.
Command active The binary output Command active is a running SPS
command for the signalization (command active or
selected switching device). During Command active
either an On or Off command is active.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1199


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

Signal Name Description Type


Op.ct. The information counts the number of disconnector INS
switching cycles.

Control
It is the task of the controls to execute command checks and establish communication between the command
source and the disconnector. Using the control settings, you specify how the commands are to be processed
(see also chapter 8.3.1 Command Checks and Switchgear Interlocking Protection).
Through the function SBO (Select Before Operate, reservation36), the switching device is reserved prior to the
actual switching operation, thus it remains locked for additional commands. Feedback monitoring provides
information about the initiator of the command while the command is in process, that means, informing
whether or not the command was implemented successfully. These two options can be selected individually in
the selection of the control model, so that 4 combinations in total are available (see the following table).
The control makes the following settings available (see next table).
Parameters Default Setting Possible Parameter Values
(_:4201:101) Control model SBO w. enh. direct w. normal secur.
security37 SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
(_:4201:102) SBO time-out 30.00 s -
(_:4201:103) Feedback monitoring time 10.00 s -
(_:4201:104) Check switching authority yes no
yes
advanced
(_:4201:105) Check if pos. is reached yes no
yes
(_:4201:106) Check double activat. blk. yes no
yes

8.2.3.3 Trigger Variants of the Disconnector


The activation types are identical to those for the circuit breaker. The meaning of abbreviations can be found
in 8.2.2.3 Connection Variants of the Circuit Breaker and 8.2.2.3 Connection Variants of the Circuit Breaker.
Whether the disconnector is triggered for 1-, 1.5-, or 2-phases depends on the design of the auxiliary and
control voltage system.

1-Pole Triggering

[dw1ptren-030211-01.tif, 1, en_US]

Figure 8-20 1-Pole Triggering

36 In the IEC 61850 standard, Reservation is described as Select before Operate (SBO).
37 This default setting is the standard control model for a switching command in an IEC 61850-compliant system.

1200 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

[scrangtrenn1p, 1, en_US]

Figure 8-21 1-Pole Triggering, Routing in DIGSI

You can select the contacts for On and Off as desired. They need not necessarily be next to one another.

1.5-Pole Triggering

[dw5polig-020211-01.tif, 1, en_US]

Figure 8-22 1.5-Pole Triggering

SIPROTEC 5, 7SJ82/7SJ85, Manual 1201


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

[scrangtrenn15p, 1, en_US]

Figure 8-23 1.5-Pole Triggering, Routing in DIGSI

2-Pole Triggering

[dw2polan-020211-01.tif, 1, en_US]

Figure 8-24 2-Pole Triggering

1202 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

[scrangtrenn2p, 1, en_US]

Figure 8-25 2-Pole Triggering, Routing in DIGSI

The feedback is routed via the position with the disconnector.

8.2.3.4 Settings

Addr. Parameter C Setting Options Default Setting


Control
_:4201:101 Control:Control model • status only SBO w. enh.
security
• direct w. normal secur.
• SBO w. normal secur.
• direct w. enh. security
• SBO w. enh. security
_:4201:102 Control:SBO time-out 0.01 s to 1800.00 s 30.00 s
_:4201:103 Control:Feedback moni- 0.01 s to 1800.00 s 10.00 s
toring time
_:4201:104 Control:Check switching • no yes
authority
• yes
_:4201:105 Control:Check if pos. is • no yes
reached
• yes
_:4201:106 Control:Check double • no yes
activat. blk.
• yes
Disconnector
_:5401:101 Disconnector:Maximum 0.01 s to 1800.00 s 10.00 s
output time
_:5401:102 Disconnector:Seal-in time 0.00 s to 60.00 s 0.00 s
_:5401:103 Disconnector:Switching- • switch-disconnector disconnector
device type
• disconnector
• grounding switch
• fast grounding switch

SIPROTEC 5, 7SJ82/7SJ85, Manual 1203


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.2 Switching Devices

8.2.3.5 Information List

No. Information Data Class Type


(Type)
Control
_:4201:503 Control:>Sw. authority local SPS I
_:4201:504 Control:>Sw. authority remote SPS I
_:4201:505 Control:>Sw. mode interlocked SPS I
_:4201:506 Control:>Sw. mode non-interl. SPS I
_:4201:53 Control:Health ENS O
_:4201:58 Control:Cmd. with feedback DPC C
_:4201:302 Control:Switching auth. station SPC C
_:4201:308 Control:Enable sw. auth. 1 SPC C
_:4201:309 Control:Enable sw. auth. 2 SPC C
_:4201:310 Control:Enable sw. auth. 3 SPC C
_:4201:311 Control:Enable sw. auth. 4 SPC C
_:4201:312 Control:Enable sw. auth. 5 SPC C
_:4201:313 Control:Switching authority ENS O
_:4201:314 Control:Switching mode ENS O
Interlocking
_:4231:500 Interlocking:>Enable opening SPS I
_:4231:501 Interlocking:>Enable closing SPS I
_:4231:502 Interlocking:>Enable opening(fixed) SPS I
_:4231:503 Interlocking:>Enable closing (fixed) SPS I
_:4231:53 Interlocking:Health ENS O
Disconnector
_:5401:500 Disconnector:>Acquisition blocking SPS I
_:5401:501 Disconnector:>Reset switch statist. SPS I
_:5401:53 Disconnector:Health ENS O
_:5401:58 Disconnector:Position DPC C
_:5401:300 Disconnector:Open command SPS O
_:5401:301 Disconnector:Close command SPS O
_:5401:302 Disconnector:Command active SPS O
_:5401:305 Disconnector:Op.ct. INS O

1204 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

8.3 Control Functionality

8.3.1 Command Checks and Switchgear Interlocking Protection

Before switching commands can be issued by the SIPROTEC 5 device, several steps are used to check the
command:

• Switching mode (interlocked/non-interlocked)

• Switching authority (local/DIGSI/station/remote)

• Switching direction (set=actual)

• Bay interlocking and substation interlocking

• 1-out-of-n check (double-activation blocking)

• Blocking by protection function

Confirmation IDs (with Inactive RBAC)


SIPROTEC 5 devices can operate using role-based access control (RBAC). If RBAC is active in the device, the
authorizations to execute various actions are linked directly to the role concept.
If RBAC is inactive in the device, various actions are secured using the confirmation IDs. The following confir-
mation IDs from the Safety menu apply to the control functions:

[scconf89-061016-01, 1, en_US]

Figure 8-26 Confirmation IDs in DIGSI 5: Settings Menu

The following table identifies the meanings of the confirmation IDs:

Table 8-16 Relevant Confirmation IDs for Controls

Confirmation ID Meaning Description


Set/operate Changing settings The confirmation ID is requested before device
parameters can be changed.
Operation (function Process data access via Access to process data is possible with the help of
buttons) function buttons push-buttons and function buttons. The confirma-
tion ID of Set/operation is requested.
Control (process) General release for control The confirmation ID is usually not needed for bay
of switching devices controllers. In the case of protection devices, this
confirmation ID can be used to safeguard control
of switching devices.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1205


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

Confirmation ID Meaning Description


Control (non-interlocked) Switching non-interlocked Switching mode:
Release for switching without querying the inter-
locking conditions (S1 operation). The fixed
interlocking conditions (for example, >Enable
opening(fixed) and >Enable closing
(fixed)) are still queried if this is set in the
parameters.
The confirmation ID is queried only for devices
without a key switch; otherwise it is replaced with
the key switch position.
Switching authority Release for switching The confirmation ID is queried only for devices
authority Local without a key switch; otherwise it is replaced with
the key switch position.

The confirmation IDs are preset with the following values:

• Set/operate 222222

• Control (process, interlocked) 333333

• Control (not-interlocked) 444444

• Switching authority local 666666


If you have configured a device with key switches, the confirmation IDs for non-interlocked switching and
switching authority are not displayed or editable in DIGSI; the function is handled by the position of the key
switch.
To increase security, change these codes with DIGSI.

Switching Mode (Interlocked/Non-Interlocked)


The switching mode determines whether or not the switchgear interlocking that has been configured in the
CFC is checked before the command is output.
You can change the switching mode with the key switch S1 (interlocking off/normal). For devices without a
key switch, you can change the switching mode with a corresponding menu item on the display (after
entering a confirmation ID). You can also set the switching mode for switching commands from the sources
DIGSI, station or remote.

! DANGER
If the switching mode = non-interlocked, the switchgear interlocking protection is shut off.
Erroneous switching operations can lead to severe or fatal injuries.
² Ensure manually that all checks have been implemented.

In addition, you can set the switching mode directly with a binary input or CFC. Use the General function
block (see next figure).

1206 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[scmoscha-260511-01.tif, 1, en_US]

Figure 8-27 Switching Mode in Function Block General

The following table shows the effects of changing the switching mode to use command checks.

Table 8-17 Relationship Between Switching Mode and Command Checks

Command Check Switching Mode


Interlocked Non-Interlocked
Switching authority Checked Checked
Switching direction (set=actual) Checked Checked
Fixed interlocking conditions Checked Checked
Interlocking conditions Checked Not checked
1-out-of-n check (double-activation blocking) Checked Not checked
Blocking by protection function Checked Not checked

Switching Authority
The switching authority determines which command source is allowed. The following command sources are
possible:

• Local:
A switching command from the local control (cause-of-error source Local) is possible only if the
switching authority is set to Local and the device is capable of on-site operation. Setting the switching
authority to Local is typically accomplished with key switch S5 (Local/Remote). In this case, commands
from all other sources are rejected. If the switching authority is set to Local, the setting cannot be
changed remotely.

• DIGSI:
A switching command from DIGSI (connected via USB or Ethernet, cause-of-error source Maintenance) is
accepted only if the switching authority in the device is set to Remote. Once DIGSI has signed on the
device for command output, no commands from other command sources or a different DIGSI PC will be
executed.

• Station:
This switching authority level can be activated via a parameter in the General function block. A switching
command from the station level (cause-of-error source Station or Automatic station) is accepted if the
switching authority is set to Remote and the controllable Station switching authority is set. This is
accomplished by a command from the substation automation technology. Switching commands from the
device or from outside the station (cause-of-error source Local, Remote or Automatic remote) are
rejected.
Full support of the this switching authority level is assured only when using the IEC 61850 protocol.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1207


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

• Remote:
This switching authority level stands from remote control directly from the network control center or (if
the switching authority level Station is not activated) generally for Remote control. The cause-of-error
source is Automatic remote. Commands from this level are accepted if the switching authority is set to
Remote and the controllable Station switching authority is not set. Switching commands from the
device or from the station (cause-of-error source Local, Station or Automatic station) are rejected.

[schoheit-260511-01.tif, 1, en_US]

Figure 8-28 Display of Switching Authority and Switching Mode in Information Routing (in Function Block
General)

Sw. authority key/set and Sw.mode key/set indicate the current state of the key switch or parameter for
switching authority or switching mode and provide this information for further processing in the CFC. In the
CFC, for example, it is possible to set up an automatic routine to ensure that the switching authority is auto-
matically set to Local when the key switch is set to non-interlocked.
The following table shows the dependency of the switching mode on the key-switch position and the
switching authority. In the case of switching commands from Remote, the information on whether a locked
or non-interlocked switching should take place is also sent. For this reason, the position of the key switch is
irrelevant for the switching mode in these cases. The information in the table assumes that, in the case of
remote switching commands or those from the station, the switching mode is interlocked in each case.

Table 8-18 Dependency of the Switching Mode on the Key-Switch Position and Switching Authority

Switching Authority
Key Switch for Switching Mode Local Remote Station
Interlocked Interlocked Interlocked Interlocked
Non-interlocked Non-interlocked Interlocked Interlocked

1208 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

The signals shown in Figure 8-28 in DIGSI 5 information routing have the following relationship:

• In terms of switching authority and switching mode, the respective key switch position serves as the
input signal and the input signals in the matrix.

• The state of the switching authority and switching mode is indicated by corresponding output signals.

• The Switching authority and Switching mode functions link the input signals and in this way establish
the output signals (see Figure 8-29 and Figure 8-30).

[dwhoheit-260511-01.tif, 1, en_US]

Figure 8-29 Establishing Switching Authority

[dwmodsch-020513-01.tif, 1, en_US]

Figure 8-30 Establishing Switching Mode

In the case of both functions, the input signals overwrite the state of the key switch. This allows external
inputs to also set the switching authority or switching mode, if desired (for instance, by querying an external
key switch).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1209


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

The following additional settings are available for the switching authority:

• Activation of Switching Authority Station (defined in IEC 61850 Edition 2):


If you would like to use this switching authority, set the check mark General/Control.

• Multiple Switching Authority Levels:


This option permits switching commands from several command sources in the device if the switching
authority Remote is selected. Subsequently, a distinction between these command sources can also be
made. You can find more details in the following table. Activate this option by setting the check mark
General/Control.

• Specific sw. authorities:


You can enable additional options for the switching authority check. You can find more information
about these options in section Specific Switching Authority, Page 1211. By default, these are not used.

[scakthoh-161014, 1, en_US]

Figure 8-31 How to Activate the Station Switching Authority and to Enable Several Switching-Authority
Levels

Table 8-19 Effect on Switching Authority when Several Switching-Authority Levels Are Enabled with/
without Activation of the Station Switching Authority

Release Several Switching Status of DIGSI Station State of the Resulting


Switching Authority in the in the Device Switching Station Switching
Authority Device Authority Acti- Switching Authority
Levels vated Authority
Local – – – Local

No Signed on – – DIGSI

Remote No – Station and


Not signed on
remote
Yes Set Station
Not set Remote
Local – – – Local

Yes Signed on – – DIGSI

Remote No – Local and station


Not signed on
and remote
Yes Set Local and station
Not set Local and station
and remote

1210 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

The following table shows the result of the switching-authority check, based on the set switching authority
and the cause of the command. This overview represents a simplified normal case (no multiple command
sources when using Station and Remote).

Table 8-20 Result of a Switching-Authority Check

Cause Source Switching Authority


Local DIGSI Station Remote
Local Release Blocked Blocked Blocked
Station Blocked Blocked Release Blocked
Remote Blocked Blocked Blocked Release
Local automatic Release Release Release Release
operation
Station automatic Blocked Blocked Release Blocked
operation
Remote automatic Blocked Blocked Blocked Release
operation
DIGSI Blocked Release Blocked Blocked

Specific Switching Authority


Special switching authorities can be configured as extension of the switching-authority check. This makes it
possible to differentiate the Remote command sources at the bay level. Switching authority can be routed to
or revoked from different control centers that can, for example, belong to different companies. Thus, precisely
one of these command sources can switch at a certain time. This function is based on extending the
switching-authority check by verifying the identifier of the command source (field Originator/orIdent of
switching command). In order to turn on the function, go to General/Control and set the check mark for the
parameter Specific sw. authorities. More settings for the configuration of the identifiers and the
behavior of the function as well as additional signals appear (see Figure 8-33). In order to permit an additional
command source to switch, you must activate this specific switching authority. In order to do this, set the
controllable Enable sw. auth. 1 to Enable sw. auth. 5.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1211


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[sc_act additional options sw authority, 3, en_US]

Figure 8-32 Activating Additional Options of the Switching Authority

The additional parameters allow you to set the following options:

• Specific sw.auth. valid for (for station/remote, only remote or only station):
With this parameter, you determine for which command source the extended switching-authority check
is used.

Table 8-21 Result Derived from the Combination of the Parameter Value Specific sw.auth. valid
for and the Level of the Command Source (Field Originator/orCat of the Switching
Command)

Command Source Specific sw.auth. valid for


station station/remote remote
Local, local automatic No check No check No check
Station, station automatic Check Check No check
Remote, remote auto- No check Check Check
matic
DIGSI No check No check No check

1212 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

• Num. of specific sw.auth.:


With this parameter, you determine how many specific switching authorities are available. This deter-
mines the number of parameters Identifier switching authority as well as the controllable
Active. Sw. auth..

• Identifier switching authority 1 to Identifier switching authority 5:


The number of names that appear corresponds to the number set in the previous parameter. You can
select the names as you wish, 1 to 64 characters are allowed. The command check verifies whether these
titles correspond with those sent by the command source. This applies to the switching commands as
well as to the activation of a specific switching authority. The requirement for this is the system interface
IEC 61850. The field Originator/orIdent is used.

• Multiple specific sw.auth. ensures the simultaneous validity of the various command sources.
The following table shows how to determine the resulting specific switching authority when activating
the command sources of Remote or Station. If this parameter is activated, all parameterized command
sources get permissible automatically (see last row in the table) and they cannot be deactivated via the
controllable Enable sw. auth. 1 to Enable sw. auth. 5. Otherwise, the enabled command
source with the lowest number has always the highest priority and prevails against the other numbers.

Table 8-22 Determining Switching Authority if Multiple Command Sources Are Available

Multiple Enable sw. Enable sw. Enable sw. Enable sw. Enable sw. Resulting
specific auth. 1 auth. 2 auth. 3 auth. 4 auth. 5 Specific
sw.auth. Switching
Authority
No On * * * * Switch. auth. 1
No Off On * * * Switch. auth. 2
No Off Off On * * Switch. auth. 3
No Off Off Off On * Switch. auth. 4
No Off Off Off Off On Switch. auth. 5
No Off Off Off Off Off None
Yes On On On On On All

The * symbol in the previous table refers to any value.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1213


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[sc_sw authority and mode in info routing, 1, en_US]

Figure 8-33 Display of Switching Authority and Switching Mode in the Information Routing (in Function
Block General), Example of 2 Activated Remote Switching Authorities

Individual Switching Authority and Switching Mode for the Switching Devices
In a standard case, the functionalities switching authority, switching mode, and specific switching authority as
described in the previous sections, are applicable to the entire bay unit and, therefore, are valid for all
switching devices that are controlled by this bay unit. In addition, you can configure an individual switching
authority and specific switching authority as well as individual switching modes for single switching devices.
Therefore, individual switching devices can accept various switching authorities and switching modes simulta-
neously.
This is offered for the following function groups and function blocks:

• Circuit-breaker function group

• Disconnector function group

• Transformer tap changer function group

• Switching sequence function block


This allows to select individual settings for each switching device. This is useful if, for example, switching
devices of different utilities are managed within a single bay.
In order to activate this option, go to the function block Control of a switching device and set the parameter
Check switching authority to advanced. An additional table containing initially 2 parameters is
displayed.

1214 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[sc_add parameters sw authority sw device, 1, en_US]

Figure 8-34 Additional Parameters for Switching Authorities in the Parameters of a Switching Device

When activating the parameter Swi.dev. related sw.auth., an individual switching authority as well as
an individual switching mode for this switching device are configured. Additional signals are displayed in the
Control function block of the corresponding switching device.

[sc_extended parameters sw authority sw device, 1, en_US]

Figure 8-35 Expanded Parameters for the Switching Authority in the Switching Device

[sc_switching auth sw mode changeable, 1, en_US]

Figure 8-36 Individually Modifiable Switching Authority and Switching Mode for Switching Devices

The new input signals that are displayed allow you to set the individual switching authority and switching
mode for the switching devices. For this switching device, these inputs overwrite the central switching

SIPROTEC 5, 7SJ82/7SJ85, Manual 1215


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

authority and the switching mode. The outputs Switching authority and Switching mode indicate the
states only for this switching device.
When activating Specific sw. authorities, an individual specific switching authority for this switching
device is configured. Additional parameters are displayed.

[sc_Parameters FB control all additional options, 1, en_US]

Figure 8-37 Parameters of the FB Control with All Additional Options

The functionality of the specific switching authority for the individual switching device and the significance of
the additional parameters is identical to the operating mode of the central specific switching authority. Addi-
tional signals are displayed in the Control function block.

[sc_Specific sw authority changeable per sw device, 1, en_US]

Figure 8-38 Specific Switching Authority, Modifiable for Each Switching Device

Switching Direction (Set = Actual)


With this check, you avoid switching a switching device into a state that has already been achieved. For
instance, before a trip command is issued to a circuit breaker, its current position is determined. If this circuit
breaker is already in the Off position, no command is issued. This is logged accordingly.

Switchgear Interlocking Protection


Switchgear interlocking protection means avoiding maloperation by checking the bay and substation inter-
locking and thus preventing equipment damage and personal injury. The interlocking conditions are always
system-specific and for this reason are stored as CFC charts in the devices.
SIPROTEC 5 devices recognize 2 different types of interlocking conditions:

• Normal interlocking conditions:


These can be revoked by changing the switching mode to non-interlocked.

1216 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

• Non-revocable (fixed) interlocking conditions:


These are still checked even if the switching mode is set to non-interlocked.
Application: Replacing mechanical interlocking, for example, that prevent actuation of a medium-
voltage switch.
Each of the 2 categories has 2 release signals (for the On and Off switching directions) that represent the
result of the interlocking plan, so that interlocking is in effect during the command check (see the figure
below). The default setting for all release signals is TRUE, so that no switchgear interlocking checks take place
if no CFC charts have been prepared.

[scverrie-260912-01.tif, 1, en_US]

Figure 8-39 Interlocking Signals in Function Block Interlocking

EXAMPLE

For interlocking
For the making direction of the circuit breaker QA in bay E01 (see the figure below), it is necessary to check
whether the disconnectors QB1, QB2, and QB9 are in the defined position, that is, either On or Off. Opening
the circuit breaker QA should be possible at any time.
The interlocking equations are: QA_On = ((QB1 = On) or (QB1 = Off)) and ((QB2 = On) or (QB2 = Off)) and
((QB9 = On) or (QB9 = Off)). There is no condition for opening.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1217


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[ScAbgang-270410-deDE-01, 1, en_US]

Figure 8-40 Feeder Bay for a Double Busbar System

The CFC chart that is required to implement the interlocking equation is shown in the next figure.

[scverpla-270511-01.tif, 1, en_US]

Figure 8-41 Interlocking Chart for Bay Interlocking

Since the Disconnector function block provides the defined position On or Off, the exclusive OR gate XOR is
not necessary for the linkage. A simple OR suffices.

1218 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

As can be seen in the CFC chart, the result of the check is connected to the >Release on signal in the
Interlocking function block in the Circuit breaker QA function group (see Figure 8-41).

EXAMPLE

For system interlocking


This example considers the feeder = E01 from the previous example (bay interlocking) and additionally the
coupler bay = E02 (see the figure below).

[ScAnlage-270410-deDE-01, 1, en_US]

Figure 8-42 System with Feeder and Coupler Bays

The circuit breaker QA in coupler bay = E02 will be considered next. As the multibay interlocking condition,
you must provide the bus-coupler circuit-breaker command block at the end:
If the 2 busbars in bay = E01 are connected, that is, if the 2 disconnectors QB1 and QB2 in bay =E01 are
closed, the circuit breaker QA in bay = E02 is not allowed to be switched off. Accordingly, bay = E01 in the CFC
of the device generates the indication Bus coupler closed from the positions of the switches QB1 and
QB2 and, using IEC 61850-GOOSE, transmits it to bay = E02 in the device. You must then store the following
interlocking condition in bay = E02:
QA_Off = NOT (= E01/Bus coupler closed)
In the CFC chart for the coupling device = E02, you must create the following CFC chart (see the figure below).

[scplanve-241013, 1, en_US]

Figure 8-43 Interlocking Chart for Substation Interlocking

SIPROTEC 5, 7SJ82/7SJ85, Manual 1219


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

1-Out-of-n Check (Double-Activation Blocking)


The double-activation blocking prevents 2 commands from being executed in the device simultaneously. You
can set the device-internal check for each switching device as a parameter in the Control function block.
The default setting is Yes, that is, double-activation blocking is active (see the figure below).

[scdoppel-260912-01.tif, 1, en_US]

Figure 8-44 Activating the Double-Activation Blocking

With SIPROTEC 5, it is also possible to achieve multibay double-activation blocking.


In this case, send the signal not selected to other devices for analysis using IEC 61850-GOOSE. This signal
is available under Position in every Circuit-breaker or Disconnector function block in the switching device
function groups (see figure below).

[scnotselected-090315_de, 1, en_US]

Figure 8-45 Signal Not selected in the Circuit-Breaker Function Block

The signal is then queried in the CFC interlocking conditions for the associated switching devices and is used
to generate the release signal (for example, >Release on).

Blocking by Protection Function

• Default setting (_:107) Check blk. by protection = yes


In devices with protection and control functions, Siemens recommends that no switching commands can be
issued while protection functions have picked up.

1220 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

This applies to automatic reclosing as well. Switching commands must be prevented as long as automatic
reclosing is active.
The default setting for blocking by the protection function is therefore yes. If necessary, you can disable this
blocking. You can find the settings on the same page as the double-activation blocking (see Figure 8-44).

NOTE

i Remember, for instance, that pickup of the thermal overload protection can create a fault as well and thus
prevent switching commands.

NOTE

i The command check Blocking by protection function is only available for controlling circuit breakers,
because in this case a unique relationship with protection functions and automatic reclosing has been
configured. In disconnectors, this relationship is not always unique, precisely with regard to the 1 1/2
circuit-breaker layout, and it must be mapped for each system using CFC charts.
To carry out the command check Blocking by protection function for disconnectors, use the following
indications (if present) in your interlocking conditions:

• Group indication: Pickup (Function group Line)

• Circuit-breaker failure protection: Pickup (Circuit-breaker failure protection)

• General: In progress (Automatic reclosing function)

8.3.2 Command Logging

All commands in the sequence are logged. The command log contains:

• Date and time

• Name of the switching device (or function group)

• Reason for the transmission (SEL = Selected, OPR = Operate, CMT = Command execution end, SPN =
Spontaneous)

• Status or switching direction

EXAMPLE
The following example illustrates control of a disconnector QB1 for various cases.

• Successful command output

• Interrupted command

• Command interrupted by switchgear interlocking

• Command ended due to missing feedback

• Spontaneous change of switch position without command output


Figure 8-46 to Figure 8-52 indicates command logging for various scenarios of the standard control model
SBO with feedback monitoring.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1221


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[scposcas-070411-01.tif, 1, en_US]

Figure 8-46 Positive Case (Display 1)

[scposca2-070411-01.tif, 1, en_US]

Figure 8-47 Positive Case (Display 2)

1222 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[scposcan-070411-01.tif, 1, en_US]

Figure 8-48 Positive Case with Command Cancellation

[scnegint-070411-01.tif, 1, en_US]

Figure 8-49 Negative Case (Blocked by Switchgear Interlocking)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1223


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[scnegtim-070411-01.tif, 1, en_US]

Figure 8-50 Negative Case (Expiration of Feedback Supervision Time) (Display 1)

[scnegti2-070411-01.tif, 1, en_US]

Figure 8-51 Negative Case (Expiration of Feedback Supervision Time) (Display 2)

1224 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

[scsponta-070411-01.tif, 1, en_US]

Figure 8-52 Spontaneous Status Change

Depending on the transmission reason, the desired control value or the actual state value of the controllable
and the switching device can be contained in the log.
The following table shows the relationship.

Table 8-23 Relationship between the Reason for Transmission and the Value Logged

Reason for Transmission Value


Selected (SEL) Desired value
Operate (OPR) Desired value
Command cancellation (CNC) Desired value
Command execution and termination (CMT) Actual value
Spontaneous change (SPN) Actual value

8.3.3 Settings

Addr. Parameter C Setting Options Default Setting


Control
_:101 Control:Control model • status only SBO w. enh.
security
• direct w. normal secur.
• SBO w. normal secur.
• direct w. enh. security
• SBO w. enh. security
_:102 Control:SBO time-out 0.01 s to 1800.00 s 30.00 s
_:103 Control:Feedback moni- 0.01 s to 1800.00 s 1.00 s
toring time
_:104 Control:Check switching • no yes
authority
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 1225


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.3 Control Functionality

Addr. Parameter C Setting Options Default Setting


_:105 Control:Check if pos. is • no yes
reached
• yes
_:106 Control:Check double • no yes
activat. blk.
• yes
_:107 Control:Check blk. by • no yes
protection
• yes

8.3.4 Information List

No. Information Data Class Type


(Type)
Control
_:53 Control:Health ENS O
_:58 Control:Cmd. with feedback DPC C

1226 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4 Synchronization Function

8.4.1 Overview of Functions

The 1-channel Synchronization function (ANSI 25) checks whether the activation is permissible without a risk
to the stability of the system when interconnecting 2 parts of an electrical power system.
Typical applications are as follows:

• Synchronization of a line and a busbar

• Synchronization of 2 busbars via a cross-coupling

• Synchronization of a generator and a busbar


A power transformer between the 2 measuring points can also be taken into consideration.
The following operating modes are covered:

• Synchrocheck

• Switching synchronous power systems

• Switching asynchronous power systems

• Switching to dead line/busbar

8.4.2 Structure of the Function

The Synchronization function is used in the Circuit-breaker function group.


The following stage types can be used within the function:

• Synchrocheck stage

• Synchronous/asynchronous stage

• Synchronous/asynchronous stage with balancing commands


The Synchrocheck and Synchronous/Asynchronous (Sychr./Asycr.) stage types are preconfigured at the
factory.
In addition, the stage types Extended delta-f options and Synchronous/asynchronous with balancing
commands (Syn./Asy.bal.) are available in the function library. These have not been preconfigured.
You can operate a maximum of 2 stages of the Synchrocheck stage type or 6 stages of the Synchronous/
asynchronous or Synchronous/asynchronous with balancing commands in parallel.
As soon as the function is available in the device, the functional measured values are calculated and displayed.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1227


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dw_syn-asyn-stage_with_adjusting_com, 1, en_US]

Figure 8-53 Structure/Embedding of the Function

8.4.3 Connection and Definition

Connection
You can find examples for the synchronization of line and busbar in the following 2 figures. Figure 8-56 shows
an example for the synchronization of 2 busbars via bus coupler.
The synchronization function uses 2 voltages to check the connecting conditions: a voltage of the reference
side 1 (V1) as well as a voltage to be used as a reference on side 2 (V2). The reference voltage of side 1 is
designated in the synchronization function as V138. This is always the voltage of the measuring point that is
connected to the Sync. voltage 1 interface of the Circuit-breaker function group. The voltage to be set as
reference is designated with V238. This is always the voltage of the measuring point that is connected to the
Sync. voltage 2 interface of the Circuit-breaker function group. The assignment of the measuring points to
the interfaces of the Circuit-breaker function group can be configured, see chapter 2.1 Function Embedding
in the Device.
The selection of the voltages used for the synchronization depends on the device connection to the primary
system:

• Connection of the primary system via 4 voltage inputs and hence use of a 1-phase and a 3-phase meas-
uring point (Figure 8-54 and Figure 8-56):
The voltage connected to the 1-phase measuring point is definitive here. If. for example, this is the
phase-to-ground voltage VA, the voltage VA is also used by the other side of the 3-phase measuring point.

• Connection of the primary system via 6 voltage inputs and hence use of two 3-phase measuring points
(Figure 8-55):
The phase-to-phase voltage VAB of both sides is always used for the test.

You can connect both the phase-to-ground voltages and the phase-to-phase voltages to the device. The
possible interface connections are listed in the Appendix.

38 Do not confuse the designations V1 and V2 with the numbering of the voltage inputs V1 to V4 (Figure 8-54) and V1 to V8
(Figure 8-55).

1228 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dwsyns01-210912-01.tif, 1, en_US]

Figure 8-54 Synchronization of Line and Busbar, Connection via 4 Voltage Inputs

[dwsyns02-210912-01.tif, 1, en_US]

Figure 8-55 Synchronization of Line and Busbar, Connection via 6 Voltage Inputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1229


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dwsyns03-210912-01.tif, 1, en_US]

Figure 8-56 Synchronization of 2 Busbars via Cross-Coupling, Connection via 4 Voltage Inputs

Definition of the Variables


The definition of the variables is important for understanding the following implementation. The reference
side 1 indicates the function with 1. This yields the reference values voltageV1, frequencyf1, and phase angle
α1. The side to be synchronized indicates the function with 2. The electrical variables of side 2 are then the
voltageV2, frequencyf2, and phase angle α2.
When forming the differential variables, the function is oriented to the definition of the absolute measuring
error (Δ x = measured value – real value). The reference value and hence the real value is side 1. This results in
the following calculation specifications:
Differential voltage dV = V2 – V1
A positive sign means that the voltage V2 is greater than the voltage V1. In other cases, the sign is negative.
Differential frequency df = f2 – f1
A positive result means that according to the example from Figure 8-54 the busbar frequency is greater than
the line frequency.
Phase-angle difference dα = α2 – α1
The representation is limited to ±180o. A positive result means that α2 leads by a maximum of 180o. In the
case of a negative value, α2 lags by a maximum of 180o. Figure 8-57 shows the circumstances. The phase
angle α1 was added to the zero axis as a reference system.
If asynchronous systems are present and the frequency f2 is greater than f1, the angle dα then changes from
the negative value to 0 and then to the positive value. As shown in Figure 8-57, the direction of rotation is
counterclockwise (mathematically positive). At f2 < f1, the direction of rotation is clockwise.

1230 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dw_synp_04, 1, en_US]

Figure 8-57 Phase-Angle Difference Representation dα

Only positive values are permissible for the setting parameters. Inequalities are used to characterize the
setting parameters uniquely. The representation is explained with the example of differential voltage. 2
setting values are necessary to allow unbalanced settings.
The inequality V2 > V1 yields a positive value for dV. The associated parameter is Max. voltage diff.
V2>V1. For the 2nd setting parameter Max. voltage diff. V2<V1, the inequality V2 < V1 applies. It
corresponds to a negative dV.
The procedure is the same for the differential frequency and differential phase angle.

8.4.4 General Functionality

8.4.4.1 Description

Overview of a Synchronization Stage (Sync Stage)


A synchronization stage can be integrated in the following blocks (see Figure 8-58):

• Stage control with mode, state control, standby and blocking (description in this chapter)

• Supervision (description in this chapter)

• Functional sequence for issuing the closing release (see chapter 8.4.6 Sequence of Functions)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1231


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[losyn001-100611-01.tif, 3, en_US]

Figure 8-58 Overview of the Stage Logic

Stage Control
The normal stage control is used for a synchronization stage (see Figure 8-58).
Note the following special features:

• As soon as there is a synchronization function available in the device, the measured values are calculated
and displayed. One stage must be activated for calculating all Delta settings. It is not necessary to start
the stage for this purpose.

• If all synchronization stages are deactivated within the function, closure via the control will no longer be
possible, as none of the stages can generate a closing release. If the synchronization function is deleted,
the circuit breaker is no longer regarded as subject to compulsory synchronization. In this case, it is
possible to activate via the control without synchronization.

• If more than one synchronization stage is activated, the >Selection signal must be active for exactly
one stage, so that it can be activated via the controls.
You can block the entire synchronization stage via the binary signal >Block stage. A started process is
completed and the entire stage reset after blocking. The stage must be restarted to initiate a new switching
procedure. The blocking only affects the test process for the closing conditions. The measured values are still
calculated and displayed.

1232 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Operating Range

[losyn002-160311-01.tif, 1, en_US]

Figure 8-59 Logic of the Operating Ranges

The operating range of the synchronization function is defined by the configurable voltage limits Min.
operating limit Vmin and Max. operat. limit Vmax, as well as by the specified frequency band
frated ±4 Hz.
If one or both voltages are outside the permitted operating range when the measurement is started or a
voltage leaves the range, this is displayed via corresponding indications Frequency f1 > fmax,
Frequency f1 < fmin, Voltage V1 > Vmax, Voltage V1 < Vmin etc. The closing conditions are
then not checked.

Supervision
The supervisions listed below are executed in a function-specific manner. If one of the supervisions picks up,
the Health goes to alarm. The stage is indicated as Inactive. A closing release or direct close command is
not possible in this case.

• For consistency of settings of specific parameters


Definite threshold-value settings are checked after a parameter change. If there is an inconsistency, the
error message Setting error is issued.

• For multiple selection of the stage at the start time of the synchronization
If there is a simultaneous selection of multiple closed synchronization stages at the start time, the error
message Multiple selection is issued.

Measuring-Voltage Failure
If a voltage-transformer fault (measuring-voltage failure) is recorded via the binary input signal >Open of one
of the voltage-measuring points, then the closing conditions of the synchronization stage are no longer
tested. This means that a release of the closure based on the measurement is no longer possible. The readi-
ness of the stage turns to warning. Direct close command is still possible.
The device-internal supervision function measuring-voltage failure detection (Fuse Failure Monitor) does not
have any effect on the synchronization stage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1233


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Function Measured Values


The function measured values for the Synchronization function are displayed in their own primary, secondary
and percentage measured value windows. Voltage measurements are always displayed as ph-ph voltages,
even if the associated measuring point records phase-to-ground voltages. The function measured values are
determined and displayed as soon as the device is functional. The difference values are calculated as soon as
the stage is activated.

Table 8-24 Protection-Specific Values of the Synchronization

Values Primary Secon- % Referenced to


dary
V1 Reference voltage V1 kV V Rated operating voltage of the
primary values
V2 Voltage to be synchronized V2 kV V Rated operating voltage of the
primary values
f1 Frequency of the voltage V1 Hz Hz Rated frequency
f2 Frequency of the voltage V2 Hz Hz Rated frequency
dV Voltage difference V2-V1 kV V –
df Frequency difference f2–f1 Hz Hz –
dα Angle difference α2–α1 o – –

Multiple Synchronization Points


The synchronization function can only be used within a Circuit-breaker function group. It always operates on
the circuit breaker that is linked to the Circuit-breaker function group. The reference to the circuit breaker is
therefore unique. If you wish to switch several circuit breakers (synchronization points) with the device, you
must create several Circuit-breaker function groups.

Different Synchronization Conditions per Synchronization Point


Within the synchronization function, you can operate maximum 2 stages of the stage type Synchrocheck and
maximum 6 stages of the type Synchronous/asynchronous in parallel. All setting parameters for a synchroni-
zation point are included in each synchronization stage.
If you have to synchronize with different synchronization conditions (parameter settings), several synchroniza-
tion stages are used for a synchronization point/circuit breaker. In this case, you must define which of the
synchronization stages is currently active via the binary signal >Selection (synchronization stage x). The
closing conditions are checked if the respective stage is activated via the >Selection binary signal and the
stage is activated.
The fault indication Multiple selection is issued upon simultaneous selection of different synchroniza-
tion stages. If several synchronization stages are activated and the input signal >Selection (synchronization
stage x) is missing at the starting time, a valid selection is awaited during the supervision time Max.durat.
sync.process. If this does not come, the process is terminated.

Different Voltage-Transformer Ratios of Both Parts of the Electrical Power System


The settings of the rated parameters of the transformer for the measuring points automatically takes the
different voltage-transformer transformation ratios of both parts of the electrical power system into account.
The Voltage adjustment parameter is not needed for this purpose.

Synchronization via a Transformer


There are systems in which a power transformer is located between the voltage measuring points of the circuit
breaker to be synchronized. The device automatically considers the different voltage stages by setting the
transformer ratios (within the measuring points).
A phase displacement must be taken into account based on the transformer vector group, via the Angle
adjust. (transform.) parameter.

1234 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

The parameter is defined as -Δα = –(α2 – α1).


To calculate the Delta parameters, the voltage of side 2 is converted to the voltage of side 1 using to the
settings of both parameters.
In the Application and Setting Notes, several examples are provided for using both parameters.

Different Connection Types on Both Sides


If both the measuring points used by the synchronization functions record different voltages of the 3-phase
system, the calculation of the phase-angle difference is automatically taken into consideration.

EXAMPLE:
The 1-phase measuring point connected with Sync-voltage 1 records the phase-to-phase voltage VAB. The 1-
phase measuring point connected with Sync-voltage 2 records VA. In this case the phase angle between VAB
and VA takes into consideration the delta variable Δα during calculation..
This automation guarantees that several voltage sources can be switched between during running operation,
each of which records different voltages.

8.4.4.2 Application and Setting Notes

Stage-Type Selection
The following 2 types of stage are available:
Stage Type Application
Synchrocheck stage Select this type of stage to issue, for example, an additional release
during an automatic reclosing or a manual reclosing for safety reasons.
With this type, the variables ΔV, Δf, and Δα are checked before
connecting the 2 parts of the power system.
Synchronous/asynchronous stage Select this type of stage if it is necessary to differentiate between
synchronous and asynchronous systems, depending on the switch posi-
tion.
If galvanically coupled systems are switched in parallel, synchronous
systems are present. A typical characteristic of synchronous systems is
equality of frequency (Δf ≈ 0). In this state, the conditions Δα and ΔV
are checked.
If the systems are galvanically isolated, asynchronous systems can be
present. At the same time, compliance with the voltage difference ΔV
and frequency difference Δf conditions is checked. The time of the
direct close command is calculated taking into account the angle differ-
ence Δα and the closing time of the circuit breaker. The time of the
direct close command is calculated such that the voltages are equal at
the moment of pole contact of the circuit breaker (ΔV ≈ 0, Δα ≈ 0).

Configuration of the Voltages V1 (Reference Side) and V2


The voltages V1 and V2 are established via the connection of the measuring points to the interface of the
function groups (refer to chapter 8.4.3 Connection and Definition). The measuring point connected to the
interface Voltage is the reference side 1 with the reference voltage V1. The measuring point connected to the
interface Sync. voltage is the side 2 with V2. The definition of the Delta parameters that can be derived from
this is also described in chapter 8.4.3 Connection and Definition.

Parameter: Min. operating limit Vmin, Max. operat. limit Vmax

• Recommended setting value (_:5071:101) Min. operating limit Vmin = 90 V

• Recommended setting value (_:5071:102) Max. operat. limit Vmax = 110 V


The values define the voltage operating range of the synchronization stage. A normal setting is approx. ±10 %
of the rated voltage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1235


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

NOTE

i All voltages connected according to the parameterized measuring-point connection type are subjected to
the appropriate Vmin/Vmax test. Therefore, connected phase-to-ground voltages are multiplied by √3 as
the threshold values with reference to the rated voltage (phase-to-phase voltage) must be set.

[lohyster-010415-01.vsd, 1, en_US]

If the Synchronization function is started within the hysteresis, no switching is performed as a result of the
minimum and maximum operating limit (parameters Min. operating limit Vmin and Max. operat.
limit Vmax). If the Synchronization function is started within the voltage operating range and the voltage
exceeds the minimum or maximum operating limit during the synchronization process, selecting can occur in
the area of the hysteresis.

Parameter: Max.durat. sync.process

• Default setting (_:5071:110) Max.durat. sync.process = 30 s


The parameterized conditions must be fulfilled within this time. If the conditions are not fulfilled, no further
closing release takes place and the synchronization stage is stopped. If this time is set to ∞, the conditions are
checked until they are fulfilled. This is also the default setting. Observe the operating conditions when
defining the time limitation. This must be defined specifically for each system. If 0 or 0.01 s is set, then all
conditions are checked once at the starting time point. Thereafter the process is stopped immediately.

Parameter: Voltage adjustment

• Default setting (_:5071:126) Voltage adjustment = 1.00


The parameter can be used for correction of amplitude errors, for example, due to indirect measurement (for
example, tap changer).
To apply a transformer between measuring points, the Voltage adjustment parameter is not needed. The
transformer ratios are set for the measuring points and the function will take them into account automatically.

Parameter: Angle adjust. (transform.)

• Default setting (_:2311:127) Angle adjust. (transform.) = 0 o

1236 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

The parameter can be applied under the following conditions:

• 1. Phase-angle rotation by power transformer between the measuring points

• 2. Correction of phase-angle errors


1. Phase-angle rotation by power transformer between the measuring points:

[losynae1-160311-01.tif, 1, en_US]

Figure 8-60 Transformer Between the Measuring Points

If there is a power transformer between the voltage transformers of the circuit breaker to be synchronized,
you then have to correct the phase-angle rotation for a vector group deviating from 0. Figure 8-60 shows such
an application. The Angle adjust. (transform.) parameter is used to save the phase-angle rotation.
The vector group of the transformer is defined by the upper-voltage side to the lower-voltage side. If the refer-
ence voltage transformer V1 is connected on the upper-voltage side of the transformer (as in Figure 8-60),
enter the phase-angle rotation directly according to the vector group. A vector-group figure of 5, for example,
means an angular rotation of 5 ⋅ 30o = 150o. Set this value for the Angle adjust. (transform.) param-
eter.
If the voltage connection V1 is on the lower-voltage side due to the system, you then have to apply the exten-
sion angle with 360o. A transformer with vector group 5 yields an angular adjustment of 360o –
(5 ⋅ 30o) = 210o.
2. Correction of phase-angle errors:
You can correct a phase-angle error between the voltage transformers in increments. Ascertain a possible
correction value during commissioning.

Parameter: CB make time

• Default setting (_:5041:113) CB make time = 0.06 s


If you are to interconnect under asynchronous system conditions with the device as well, the closing time of
the circuit breaker must be taken into account. The device uses this to calculate the time of the direct close
command, so that the voltages are in phase at the moment of closure of the switch poles. Note that apart
from the operating time of the switch, this also includes the pickup time of an auxiliary relay that may be
upstream. You can determine the closing time using the protection device (see commissioning notes in
chapter 11.12 Primary and Secondary Testing of the Synchronization Function).
This parameter only occurs for the stage type Synchronous/asynchronous.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1237


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.4.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:127 General:Angle adjust. -179.0 ° to 180.0 ° 0.0 °
(transform.)
General
_:5071:1 Synchrocheck 1:Mode • off off
• on
• test
_:5071:101 Synchrocheck 1:Min. 0.300 V to 340.000 V 90.000 V
operating limit Vmin
_:5071:102 Synchrocheck 1:Max. 0.300 V to 340.000 V 110.000 V
operat. limit Vmax
_:5071:110 Synchrocheck 0.00 s to 3600.00 s; ∞ 30.00 s
1:Max.durat.
sync.process
_:5071:108 Synchrocheck 1:Direct • no no
close command
• yes
_:5071:126 Synchrocheck 1:Voltage 0.500 to 2.000 1.000
adjustment
General
_:5041:1 Sychr./Asycr.1:Mode • off off
• on
• test
_:5041:101 Sychr./Asycr.1:Min. oper- 0.300 V to 340.000 V 90.000 V
ating limit Vmin
_:5041:102 Sychr./Asycr.1:Max. 0.300 V to 340.000 V 110.000 V
operat. limit Vmax
_:5041:110 Sychr./ 0.00 s to 3600.00 s; ∞ 30.00 s
Asycr.1:Max.durat.
sync.process
_:5041:108 Sychr./Asycr.1:Direct • no no
close command
• yes
_:5041:126 Sychr./Asycr.1:Voltage 0.500 to 2.000 1.000
adjustment

8.4.5 Dynamic Measuring-Point Switching

Dynamic measuring-point switching provides the capability to connect the voltages used in the Synchro-
check function to various measuring points. In this way, for example, it is possible to use the correct voltage
on the basis of the switch position on the switching devices. If more than 1 measuring point is connected to V
sync1 or V sync2, you must create the V sync select. function block in the Circuit-breaker function
group.
Selection of the desired voltage measuring points (V sync1 and V sync2) for the Circuit-breaker function
group is controlled via Continuous Function Chart.

Connecting Measuring Points to Circuit-Breaker Function Group


The following figure shows the connection of the Circuit-breaker function group with several measuring
points in DIGSI. The ID of each measuring point appears in parentheses after the name.

1238 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[scdynms2-211212-01.tif, 1, en_US]

Figure 8-61 Connecting the Measuring Points with the Circuit-Breaker Function Group

There are consistency checks that validate the connections of voltage measuring points to the function group:

• The connection type must be identical for all measuring points connected to the same interface.

• It is not permitted to route a measuring point to the function group using the option VN.

• The rated voltage (primary and secondary) must be identical for all measuring points connected to the
same interface.

• If more than 1 measuring point is connected to 1 voltage interface, a function block must be expanded to
enable selection of the synchronization voltage.

CFC Control
The voltages are selected by CFC logic on the basis of the measuring point IDs. If more than one measuring
point is connected to interfaces Vsync1 or Vsync2 of the Circuit-breaker function group, theV sync select.
function block has to be removed from the library in the Circuit-breaker function group. A CFC logic (see
following example) has to define IDs for the V sync1 or V sync2 inputs of this function block in order to
ensure the correct measuring point connection for the Synchrocheck function.

[scdynmsx-160212-01.tif, 1, en_US]

Figure 8-62 CFC Logic: Voltage Selection Using Measuring Point ID

If no measuring point can be selected because of the switch or disconnector positions, the ID0 is used. If ID0 is
selected, the indication (_:2311:304) Blocked no V selected is set. The synchrocheck is blocked. If
you have activated the parameter (_:5071:108) Direct close command, unsynchronized switching is
still possible.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1239


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.6 Sequence of Functions

[losynf01-100611-01.tif, 3, en_US]

Figure 8-63 Sequence of Functions

Start
The synchronization stage must be started to check the closing conditions. The synchronization stage can be
started device-internally by the control and the reclosing, or externally via binary input signals, for example, by
an external automatic reclosing (AREC), (see chapter 8.4.13 Interaction with Control, Automatic Reclosing
(AREC), and External Triggering).
At the start, the system checks whether there is a multiple selection of the synchronization stage (see chapter
Supervision in chapter 8.4.4.1 Description). If this is the case, the process is terminated. After a successful
start, the indication In progress is cleared and the supervision time for the maximum duration of the
synchronization process (parameter Max.durat. sync.process) is started. The system also checks
whether the voltages and frequencies are in the operating range (see chapter 8.4.4.1 Description). If this is
not the case, the closing conditions are not checked.

Checking the Closing Conditions, Closure


After starting, the parameterized closing conditions are checked, depending on the selected operating mode
(see chapter 8.4.8.1 Description to 8.4.12 Direct Close Command ). Every condition fulfilled is explicitly indi-
cated here. Conditions not fulfilled are also indicated. If all conditions are fulfilled, the synchronization stage
sets the indication All sync. conditio. OK. The indication is active until all conditions are fulfilled. The
further behavior for issuing the release for closing depends on the type of the stage (see chapters
8.4.7.1 Description and 8.4.8.1 Description). The release is signaled via the Release close cmd. indica-
tion. This indication is active for 100 ms. With an internal start, the control or the AREC performs the actual
closure, depending on the internal starting source.

1240 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Switching to Dead Line/Busbar


If operating modes for switching to dead parts of an electrical power system are configured, the associated
conditions are also checked after the start (see chapter 8.4.11.1 Description). The fulfilled conditions are
signaled. An adjustable supervision time is started after the closure conditions are fulfilled (parameter CB
make time). If the conditions remain valid until expiry of the time, the function gives the release for closure
after expiry of the time.

Direct Close Command


If the Direct close command operation is active, the function instantaneously initiates the release for closure
after the successful start (see chapter 8.4.12 Direct Close Command ). A combination of direct close command
with other release conditions is not advisable, as these conditions are bypassed by the direct close command.

End of the Process


If the function is started via the device-internal control or AREC, these functions also terminate the synchroni-
zation process upon closure. The process is terminated via the corresponding binary signals in case of external
starting.
If the supervision time (Max.durat. sync.process parameter) has expired, the process is also completed
and the indication Max. time exceeded is issued. A renewed synchronization is only possible if the stage is
restarted.

Blocking Closure
You can use the input signal >Block close command to block the release signal for the closure (signal
Release close cmd.) as well as the closure itself. The measurement continues to operate during the
blocking. If the blocking is revoked and the release conditions are still fulfilled, the release is given for closure.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1241


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.7 Stage Synchrocheck

8.4.7.1 Description

Checking Closing Conditions

[losynche-160311-01.tif, 1, en_US]

Figure 8-64 Closing Conditions for the Synchrocheck Function

With this operating mode, the values ΔV, Δf, and Δα are checked before connecting the 2 parts of the elec-
trical power system. The indication All sync. conditio. OK signals that the setting values (conditions)
have been reached and that the release for closure has been given (see section Checking the Closing Condi-
tions, Closure in chapter 8.4.6 Sequence of Functions).
Every fulfilled condition is signaled individually via the indications Voltage difference OK, Frequency
diff. OK, and Angle difference OK.
If a condition is not fulfilled, detailed information on why the condition is not fulfilled is provided via indica-
tions. If the differential voltage is outside the setting limits, for example, the indication V dif.too
large(V2<V1) is issued. The indication indirectly contains information that the voltage V2 has to be
increased for a successful synchronization.
With the Expanded delta-f options stage type configured and an activated (_:140) Limit dfdiff/dt
for sync. op parameter, the frequency difference rate of change is also checked. If the permissible
frequency change rate (parameter (_:141) Max. value dfdiff/dt syn) is exceeded, the indication
(_:329) dfdiff/dt too large is issued.

1242 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.7.2 Application and Setting Notes

Parameter: Maximum Differential Values of Voltage, Frequency and Angle

• Default setting (_:5071:122) Max. voltage diff. V2>V1 = 5.0 V

• Default setting (_:5071:123) Max. voltage diff. V2<V1 = 5.0 V

• Default setting (_:5071:117) Max. frequency diff. f2>f1 = 0.10 Hz

• Default setting (_:5071:118) Max. frequency diff. f2<f1 = 0.10 Hz

• Default setting (_:5071:124) Max. angle diff. α2>α1 = 10o

• Default setting (_:5071:125) Max. angle diff. α2<α1 = 10o


2 parameters are available for the differential values voltage, frequency, and angle. Unbalanced closing ranges
can be set with this, if required.
The permissible differential values must ensure that no protection tripping or damage occurs in the system
owing to compensation processes (circulating current) and power swings after interconnection of the parts of
the power system. The settings must not be configured too closely on the other side so that necessary
closures are not blocked.
Typical differential values are selected in the default setting. Depending on the system, the settings must be
checked and adjusted, if necessary.

8.4.7.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:5071:1 Synchrocheck 1:Mode • off off
• on
• test
_:5071:101 Synchrocheck 1:Min. 0.300 V to 340.000 V 90.000 V
operating limit Vmin
_:5071:102 Synchrocheck 1:Max. 0.300 V to 340.000 V 110.000 V
operat. limit Vmax
_:5071:110 Synchrocheck 0.00 s to 3600.00 s; ∞ 30.00 s
1:Max.durat.
sync.process
_:5071:108 Synchrocheck 1:Direct • no no
close command
• yes
_:5071:126 Synchrocheck 1:Voltage 0.500 to 2.000 1.000
adjustment
De-en.gized switch.
_:5071:105 Synchrocheck 1:Close • no no
cmd. at V1< & V2>
• yes
_:5071:106 Synchrocheck 1:Close • no no
cmd. at V1> & V2<
• yes
_:5071:107 Synchrocheck 1:Close • no no
cmd. at V1< & V2<
• yes
_:5071:103 Synchrocheck 1:V1, V2 0.300 V to 170.000 V 5.000 V
without voltage
_:5071:104 Synchrocheck 1:V1, V2 0.300 V to 340.000 V 80.000 V
with voltage
_:5071:109 Synchrocheck 1:Supervi- 0.00 s to 60.00 s 0.10 s
sion time

SIPROTEC 5, 7SJ82/7SJ85, Manual 1243


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Addr. Parameter C Setting Options Default Setting


Synchr. conditions
_:5071:122 Synchrocheck 1:Max. 0.000 V to 170.000 V 5.000 V
voltage diff. V2>V1
_:5071:123 Synchrocheck 1:Max. 0.000 V to 170.000 V 5.000 V
voltage diff. V2<V1
_:5071:117 Synchrocheck 1:Max. 0.000 Hz to 2.000 Hz 0.100 Hz
frequency diff. f2>f1
_:5071:118 Synchrocheck 1:Max. 0.000 Hz to 2.000 Hz 0.100 Hz
frequency diff. f2<f1
_:5071:124 Synchrocheck 1:Max. 0 ° to 90 ° 10 °
angle diff. α2>α1
_:5071:125 Synchrocheck 1:Max. 0 ° to 90 ° 10 °
angle diff. α2<α1

8.4.7.4 Information List

No. Information Data Class Type


(Type)
Synchrocheck 1
_:5071:81 Synchrocheck 1:>Block stage SPS I
_:5071:500 Synchrocheck 1:>Selection SPS I
_:5071:502 Synchrocheck 1:>Start / stop syn.proc. SPS I
_:5071:503 Synchrocheck 1:>Start syn. process SPS I
_:5071:504 Synchrocheck 1:>Stop syn. process SPS I
_:5071:506 Synchrocheck 1:>Op. mode 'V1<V2>' SPS I
_:5071:505 Synchrocheck 1:>Op. mode 'V1>V2<' SPS I
_:5071:507 Synchrocheck 1:>Op. mode 'V1<V2<' SPS I
_:5071:508 Synchrocheck 1:>Op. mode 'dir.cls.cmd' SPS I
_:5071:501 Synchrocheck 1:>Block close command SPS I
_:5071:54 Synchrocheck 1:Inactive SPS O
_:5071:52 Synchrocheck 1:Behavior ENS O
_:5071:53 Synchrocheck 1:Health ENS O
_:5071:328 Synchrocheck 1:In progress SPS O
_:5071:324 Synchrocheck 1:Release close cmd. SPS O
_:5071:305 Synchrocheck 1:All sync. conditio. OK SPS O
_:5071:325 Synchrocheck 1:Voltage difference OK SPS O
_:5071:326 Synchrocheck 1:Angle difference OK SPS O
_:5071:327 Synchrocheck 1:Frequency diff. OK SPS O
_:5071:307 Synchrocheck 1:Cond. V1<V2> fulfilled SPS O
_:5071:306 Synchrocheck 1:Cond. V1>V2< fulfilled SPS O
_:5071:308 Synchrocheck 1:Cond. V1<V2< fulfilled SPS O
_:5071:309 Synchrocheck 1:Frequency f1 > fmax SPS O
_:5071:310 Synchrocheck 1:Frequency f1 < fmin SPS O
_:5071:311 Synchrocheck 1:Frequency f2 > fmax SPS O
_:5071:312 Synchrocheck 1:Frequency f2 < fmin SPS O
_:5071:313 Synchrocheck 1:Voltage V1 > Vmax SPS O
_:5071:314 Synchrocheck 1:Voltage V1 < Vmin SPS O
_:5071:315 Synchrocheck 1:Voltage V2 > Vmax SPS O
_:5071:316 Synchrocheck 1:Voltage V2 < Vmin SPS O

1244 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

No. Information Data Class Type


(Type)
_:5071:317 Synchrocheck 1:V dif.too large(V2>V1) SPS O
_:5071:318 Synchrocheck 1:V dif.too large(V2<V1) SPS O
_:5071:319 Synchrocheck 1:f dif.too large(f2>f1) SPS O
_:5071:320 Synchrocheck 1:f dif.too large(f2<f1) SPS O
_:5071:329 Synchrocheck 1:dfdiff/dt too large SPS O
_:5071:321 Synchrocheck 1:α dif.too large(α2>α1) SPS O
_:5071:322 Synchrocheck 1:α dif.too large(α2<α1) SPS O
_:5071:304 Synchrocheck 1:Max. time exceeded SPS O
_:5071:323 Synchrocheck 1:Setting error SPS O

8.4.8 Stage Synchronous/Asynchronous

8.4.8.1 Description
A distinction according to synchronous and asynchronous systems can be made with this type of stage.
If galvanically coupled systems are switched in parallel, synchronous systems are present. A typical character-
istic for synchronous systems is equality of frequency (Δf ≈ 0). If the frequency difference falls below the
setting value of the f-threshold ASYN<->SYN parameter, synchronous systems are to be assumed. If the
frequency difference exceeds the setting value of the f-threshold ASYN<->SYN parameter, asynchronous
systems are to be assumed. This status occurs in galvanically isolated systems, for example.
Both states have their own operating mode with its own closing conditions. Both operating modes can be
switched on and off separately (parameter Sync. operating mode and Async. operating mode). The
following combinations result from this:
Sync. operating mode Async. operating Functionality
mode
on on If the frequency difference is below the set
threshold value f-threshold ASYN<->SYN,,
the operating mode synchronous is active. In other
cases, the operating mode asynchronous is active.
off on Regardless of the frequency difference and the
threshold value f-threshold ASYN<->SYN, the
operating mode is exclusively active asynchro-
nously.
on off If the frequency difference is below the set
threshold value f-threshold ASYN<->SYN,,
the operating mode synchronous is active. In other
cases, the stage is inactive, that is, a switching
release cannot be issued.
off off Both operating modes are deactivated. No activa-
tion release can be be given via these operating
modes either.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1245


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Checking the Closing Conditions in Synchronous Systems

[losynsyn-100611-01.tif, 1, en_US]

Figure 8-65 Closing Conditions when Switching Synchronous Systems

The frequency difference is very low in the synchronous systems operating mode. It is below the threshold
value f-threshold ASYN<->SYN. The status is signaled via the State f-synchronous indication.
The parameters ΔV and Δα are checked for issuing an activation release (see Figure 8-66). The indication All
sync. conditio. OK signals that both setting values (conditions) are reached. If the conditions remain
fulfilled over the set time delay (parameter Delay close command), the release for closing is given (see
also chapter 8.4.7.1 Description).
Every condition fulfilled is signaled individually via the indications Voltage difference OK and Angle
difference OK.
If a condition is not fulfilled, detailed information on why the condition is not fulfilled is provided via indica-
tions. If the differential voltage is outside the setting limits, for example, the indication V dif.too
large(V2<V1) is issued. The indication indirectly contains information that the voltage V2 has to be
increased for a successful synchronization.
With the Expanded delta-f options stage type configured and an activated (_:142) Limit dfdiff/dt
for asyn. op parameter, the frequency difference rate of change is also checked. If the permissible
frequency change rate (parameter (_:143) Max. value dfdiff/dt asyn) is exceeded, the indication
(_:329) dfdiff/dt too large is generated.

1246 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[losynzus-110211-01.tif, 1, en_US]

Figure 8-66 Connecting Under Synchronous System Conditions

SIPROTEC 5, 7SJ82/7SJ85, Manual 1247


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Checking Closing Conditions in Asynchronous Systems

[losynasy-210912-01.tif, 1, en_US]

Figure 8-67 Closing Conditions when Switching Asynchronous Systems

In this operating mode, compliance with the voltage difference ΔV and frequency difference Δf conditions is
checked. The function calculates the time point of the close command taking into account the angular differ-
ence Δα and the closing time of the circuit breaker. This is calculated so that the voltage phasors are equal at
the moment of pole contact by the circuit breaker (ΔV ≈ 0, Δα ≈ 0).

Ranges in the Voltage-Frequency Diagram (V-f Diagram)


Figure 8-68 shows the setting parameters for synchronous and asynchronous conditions in the V-f diagram.
The frequency band is very narrow owing to the functional principle in the case of synchronous systems.

1248 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[losynarb-080211-01.tif, 1, en_US]

Figure 8-68 Operating Range under Synchronous and Asynchronous Conditions for Voltage (V) and
Frequency (f)

8.4.8.2 Application and Setting Notes

Parameter: Synchronous operating mode, Asynchronous operating mode

• Default setting (_:5041:119) Sync. operating mode = off

• Default setting (_:5041:114) Async. operating mode= off


The operating modes of the stages can be activated or deactivated via the parameters. The operating modes
are deactivated in the default setting for safety reasons.
The following combination options are possible:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1249


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Sync. operating mode Async. operating mode Description


on on If the frequency difference is below the set threshold
value f-threshold ASYN<->SYN, the operating
mode synchronous is active. In other cases, the oper-
ating mode asynchronous is active.
If you wish to interconnect galvanically isolated
systems, then select this operating mode.
off on Regardless of the frequency difference and the
threshold value f-threshold ASYN<->SYN, the
asynchronous operating mode is exclusively active.
The closing time of the circuit breaker is this always
taken into account for determining the connecting
point.
Select this operating mode if you wish to activate
machines, for example generators or asynchronous
motors.
However, if synchronous conditions with a low Δf are
present, a close command is generated in this oper-
ating mode without a kick pulse.
on off Use this operating mode for galvanically connected
systems.
Closure is only possible with synchronous systems
(with low Δf).
off off Both operating modes are deactivated. No closing
release can be therefore be given via this operating
mode.
This configuration is only advisable for special applica-
tions. Select this operating mode if you only wish to
switch, for example de-energized parts of the power
system.

Parameter for asynchronous operation: Max. voltage diff. of voltage and frequency

• Default setting (_:5041:115) Max. voltage diff. V2>V1 = 2.0 V

• Default setting (_:5041:116) Max. voltage diff. V2<V1 = 2.0 V

• Default setting (_:5041:117) Max. frequency diff. f2>f1 = 0.10 Hz

• Default setting (_:5041:118) Max. frequency diff. f2<f1 = 0.10 Hz


For information, see Parameter for synchronous operation

Parameter for synchronous operation: Maximum voltage diff. of voltage and angle

• Default setting (_:5041:122) Max. voltage diff. V2>V1 = 5.0 V

• Default setting (_:5041:123) Max. voltage diff. V2<V1 = 5.0 V

• Default setting (_:5041:124) Max. angle diff. α2>α1 = 10o

• Default setting (_:5041:125) Max. angle diff. α2<α1 = 10o


2 parameters are available for the differential values voltage, frequency, and angle. Unbalanced closing ranges
can be set with this, if required.
The permissible differential values must ensure that no protection tripping or damage occurs in the system
owing to compensation processes (circulating current) and power swings after interconnection of the parts of
the power system. The settings must not be configured too closely on the other side so that necessary
closures are not blocked.

1250 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Typical differential values are selected in the default setting. Depending on the system, the settings must be
checked and adjusted, if necessary.

Parameter: Switchover between synchronous and asynchronous operation

• Recommended setting value (_:5041:120) f-threshold ASYN<->SYN = 0.01 Hz


This parameter is used to set the frequency difference for switching over between synchronous and asynchro-
nous operation.
Siemens recommends using the default setting of 0.01 Hz.

8.4.8.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:5041:1 Sychr./Asycr.1:Mode • off off
• on
• test
_:5041:101 Sychr./Asycr.1:Min. oper- 0.300 V to 340.000 V 90.000 V
ating limit Vmin
_:5041:102 Sychr./Asycr.1:Max. 0.300 V to 340.000 V 110.000 V
operat. limit Vmax
_:5041:110 Sychr./ 0.00 s to 3600.00 s; ∞ 30.00 s
Asycr.1:Max.durat.
sync.process
_:5041:108 Sychr./Asycr.1:Direct • no no
close command
• yes
_:5041:126 Sychr./Asycr.1:Voltage 0.500 to 2.000 1.000
adjustment
De-en.gized switch.
_:5041:105 Sychr./Asycr.1:Close • no no
cmd. at V1< & V2>
• yes
_:5041:106 Sychr./Asycr.1:Close • no no
cmd. at V1> & V2<
• yes
_:5041:107 Sychr./Asycr.1:Close • no no
cmd. at V1< & V2<
• yes
_:5041:103 Sychr./Asycr.1:V1, V2 0.300 V to 170.000 V 5.000 V
without voltage
_:5041:104 Sychr./Asycr.1:V1, V2 0.300 V to 340.000 V 80.000 V
with voltage
_:5041:109 Sychr./Asycr.1:Supervi- 0.00 s to 60.00 s 0.10 s
sion time
Asynchr. op.mode
_:5041:114 Sychr./Asycr.1:Async. • off on
operating mode
• on
_:5041:113 Sychr./Asycr.1:CB make 0.01 s to 0.60 s 0.06 s
time
_:5041:115 Sychr./Asycr.1:Max. 0.000 V to 170.000 V 5.000 V
voltage diff. V2>V1
_:5041:116 Sychr./Asycr.1:Max. 0.000 V to 170.000 V 5.000 V
voltage diff. V2<V1

SIPROTEC 5, 7SJ82/7SJ85, Manual 1251


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Addr. Parameter C Setting Options Default Setting


_:5041:117 Sychr./Asycr.1:Max. 0.000 Hz to 4.000 Hz 0.100 Hz
frequency diff. f2>f1
_:5041:118 Sychr./Asycr.1:Max. 0.000 Hz to 4.000 Hz 0.100 Hz
frequency diff. f2<f1
Synchr. op.mode
_:5041:119 Sychr./Asycr.1:Sync. • off on
operating mode
• on
_:5041:120 Sychr./Asycr.1:f- 0.010 Hz to 0.200 Hz 0.010 Hz
threshold ASYN<->SYN
_:5041:122 Sychr./Asycr.1:Max. 0.000 V to 170.000 V 5.000 V
voltage diff. V2>V1
_:5041:123 Sychr./Asycr.1:Max. 0.000 V to 170.000 V 5.000 V
voltage diff. V2<V1
_:5041:124 Sychr./Asycr.1:Max. 0 ° to 90 ° 10 °
angle diff. α2>α1
_:5041:125 Sychr./Asycr.1:Max. 0 ° to 90 ° 10 °
angle diff. α2<α1
_:5041:121 Sychr./Asycr.1:Delay 0.00 s to 60.00 s 0.00 s
close command

8.4.8.4 Information List

No. Information Data Class Type


(Type)
Sychr./Asycr.1
_:5041:81 Sychr./Asycr.1:>Block stage SPS I
_:5041:500 Sychr./Asycr.1:>Selection SPS I
_:5041:502 Sychr./Asycr.1:>Start / stop syn.proc. SPS I
_:5041:503 Sychr./Asycr.1:>Start syn. process SPS I
_:5041:504 Sychr./Asycr.1:>Stop syn. process SPS I
_:5041:506 Sychr./Asycr.1:>Op. mode 'V1<V2>' SPS I
_:5041:505 Sychr./Asycr.1:>Op. mode 'V1>V2<' SPS I
_:5041:507 Sychr./Asycr.1:>Op. mode 'V1<V2<' SPS I
_:5041:508 Sychr./Asycr.1:>Op. mode 'dir.cls.cmd' SPS I
_:5041:501 Sychr./Asycr.1:>Block close command SPS I
_:5041:54 Sychr./Asycr.1:Inactive SPS O
_:5041:52 Sychr./Asycr.1:Behavior ENS O
_:5041:53 Sychr./Asycr.1:Health ENS O
_:5041:328 Sychr./Asycr.1:In progress SPS O
_:5041:324 Sychr./Asycr.1:Release close cmd. SPS O
_:5041:305 Sychr./Asycr.1:All sync. conditio. OK SPS O
_:5041:303 Sychr./Asycr.1:State f-synchronous SPS O
_:5041:325 Sychr./Asycr.1:Voltage difference OK SPS O
_:5041:326 Sychr./Asycr.1:Angle difference OK SPS O
_:5041:327 Sychr./Asycr.1:Frequency diff. OK SPS O
_:5041:307 Sychr./Asycr.1:Cond. V1<V2> fulfilled SPS O
_:5041:306 Sychr./Asycr.1:Cond. V1>V2< fulfilled SPS O
_:5041:308 Sychr./Asycr.1:Cond. V1<V2< fulfilled SPS O
_:5041:309 Sychr./Asycr.1:Frequency f1 > fmax SPS O

1252 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

No. Information Data Class Type


(Type)
_:5041:310 Sychr./Asycr.1:Frequency f1 < fmin SPS O
_:5041:311 Sychr./Asycr.1:Frequency f2 > fmax SPS O
_:5041:312 Sychr./Asycr.1:Frequency f2 < fmin SPS O
_:5041:313 Sychr./Asycr.1:Voltage V1 > Vmax SPS O
_:5041:314 Sychr./Asycr.1:Voltage V1 < Vmin SPS O
_:5041:315 Sychr./Asycr.1:Voltage V2 > Vmax SPS O
_:5041:316 Sychr./Asycr.1:Voltage V2 < Vmin SPS O
_:5041:317 Sychr./Asycr.1:V dif.too large(V2>V1) SPS O
_:5041:318 Sychr./Asycr.1:V dif.too large(V2<V1) SPS O
_:5041:319 Sychr./Asycr.1:f dif.too large(f2>f1) SPS O
_:5041:320 Sychr./Asycr.1:f dif.too large(f2<f1) SPS O
_:5041:329 Sychr./Asycr.1:dfdiff/dt too large SPS O
_:5041:321 Sychr./Asycr.1:α dif.too large(α2>α1) SPS O
_:5041:322 Sychr./Asycr.1:α dif.too large(α2<α1) SPS O
_:5041:304 Sychr./Asycr.1:Max. time exceeded SPS O
_:5041:323 Sychr./Asycr.1:Setting error SPS O

8.4.9 Stage Synchronous/Asynchronous with Balancing Commands

8.4.9.1 Description
With this stage type, a distinction by synchronous and asynchronous systems can be made.
Additionally, the stage provides the balancing commands for adjustment of the voltage and frequency (speed)
to the target conditions. The stage is used for automatic synchronization of generators. The stage has the
functionality of a 1-channel parallel switching function.
If galvanically coupled systems are switched in parallel, synchronous systems are present. A typical feature for
synchronous systems is equality of frequency (Δf ≈ 0). If the frequency difference falls below the setting value
of the f-threshold ASYN<->SYN parameter, synchronous systems are to be assumed. If the frequency
difference exceeds the setting value of the f-threshold ASYN<->SYN parameter, asynchronous systems
are to be assumed. This status occurs in galvanically separated systems, for example.
Both states have their own operating mode with own closing conditions. You can switch both operating
modes on and off separately (parameters Sync. operating mode and Async. operating mode). The
following combinations result from this:
Sync. operating mode Async. operating Functionality
mode
on on If the frequency difference is below the set
threshold value f-threshold ASYN<->SYN, the
synchronous operating mode is active. In other
cases, the asynchronous operating mode is active.
off on Regardless of the frequency difference and the
threshold value f-threshold ASYN<->SYN, the
asynchronous operating mode is exclusively
active.
on off If the frequency difference is below the set
threshold value f-threshold ASYN<->SYN, the
synchronous operating mode is active. In other
cases, the stage is inactive, that is, a switching
release cannot be issued.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1253


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

off off Both operating modes are deactivated. No closure


release can be given via these operating modes
either.

Checking Closing Conditions of Synchronous Systems

[losynsyn_adj_comm, 1, en_US]

Figure 8-69 Closing Conditions when Switching Synchronous Systems

The frequency difference is very low in the synchronous systems operating mode. It is below the threshold
value f-threshold ASYN<->SYN. The status is signaled via the State f-synchronous indication.
The parameters ΔV and Δα are checked for issuing a closure release (see Figure 8-70). The indication All
sync. conditio. OK signals that both setting values (conditions) are reached. If the conditions remain
fulfilled over the set time delay (parameter Delay close command), the release for closing is issued (see
also chapter 8.4.7.1 Description).
Every fulfilled condition is signaled individually via the indications Voltage difference OK and Angle
difference OK.
If a condition is not fulfilled, detailed information on why the condition is not fulfilled is provided via indica-
tions. If, for example, the differential voltage is outside the setting limits, the indication V dif.too
large(V2>V1) is issued. The indication indirectly contains information that the voltage V2 must be
increased for successful synchronization.

1254 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

If the Expanded delta-f options stage type is configured and the parameter (_:142) Limit dfdiff/dt
for asyn. op is activated, the rate of change of the differential frequency is also checked. If the permissible
frequency change rate (parameter (_:143) Max. value dfdiff/dt asyn) is exceeded, the indication
(_:329) dfdiff/dt too large is generated.

[losynzus_adj_comm, 1, en_US]

Figure 8-70 Connecting Under Synchronous System Conditions

SIPROTEC 5, 7SJ82/7SJ85, Manual 1255


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Checking Closing Conditions of Asynchronous Systems

[losynasy_adj_comm, 1, en_US]

Figure 8-71 Closing Conditions when Switching Asynchronous Systems

In this operating mode, compliance with the voltage difference ΔV and frequency difference Δf conditions is
checked. The function calculates the time of the close command taking into account the angle difference Δα
and the closing time of the circuit breaker. This is calculated in such a way that the voltage phasors are equal
at the moment of closing the circuit-breaker poles (ΔU ≈ 0, Δα ≈ 0).

Ranges in the Voltage-Frequency Diagram (V-f Diagram)


The following figure shows the setting parameters for synchronous and asynchronous conditions in the V-f
diagram. For synchronous systems, the frequency band is very narrow owing to the functional principle.

1256 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[losynarb_adj_comm, 1, en_US]

Figure 8-72 Operating Range under Synchronous and Asynchronous Conditions for Voltage (V) and
Frequency (f)

Balancing Commands for Voltage and Frequency


The stage has 2 separate blocks, split according to balancing commands for the voltage and the frequency.
The balancing pulses for increasing or decreasing the voltage and the frequency are generated in each block.
The following values affect the pulse width of the balancing command:

• Current measured values for differential voltage

• Current measured values for differential frequency

• Set gradients dV/dt and df/dt


In addition, the minimum pulse duration (T V pulse min, T f pulse min) and the maximum pulse dura-
tion (T V pulse max, T f pulse max) are defined. The minimum pulse duration allows for a safe reac-
tion of the controllers while the maximum pulse duration prevents an overreaction, that is an exceedance of
the desired target value. A settable dead time intercepts transient states.
The balancing commands are active once the synchronization function has been started.

Balancing Commands for Voltage


The parameters Max. voltage diff. V2>V1 and Max. voltage diff. V2<V1 are used to determine
the voltage range that defines the admissible voltage difference for asynchronous parallel switching. The
middle of the voltage range is defined as the set point value for the balancing commands.
The parameters T V pulse min and T V pulse max define the minimum and maximum duration of the
balancing pulse.
The parameter dV per second defines the speed for the set point value change of the voltage control. The
functionality uses the measured current voltage difference and the setting value of the parameter to deter-
mine the actuating time. The following equation applies:

[fo_voltage-adujsting-command, 1, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 1257


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

with:
dVMeasured value Measured differential voltage
dV per second Parameter for default speed of set point value change

The following figure shows the effect of the functionality. When the voltage range limits fall short by approxi-
mately 1/8 of the voltage range, the stage no longer issues any voltage balancing commands.

[dw_build_voltage-adjusting-com, 1, en_US]

Figure 8-73 Generation of Balancing Commands for Voltage

Balancing Commands for Frequency


The parameters Max. frequency diff. f2>f1 and Max. frequency diff. f2<f1 are used to deter-
mine the frequency band that defines the admissible frequency difference for asynchronous parallel
switching. The set point value for the balancing commands is not the middle of the frequency band, but the
value defined with the parameter Δf set point for balancing. If you specify a positive value, the
generators are supersynchronously switched in parallel to the network and can immediately transmit active
power to the network.
The parameters T f pulse min and T f pulse max define the minimum and maximum duration of the
balancing pulse. The parameter df/dt of the controller defines the speed for the set point value
change of the frequency control. The functionality uses the measured current frequency difference and the
setting value of the parameter to determine the actuating time. The following equation applies:

[fo_frequency-adujsting-command, 1, en_US]

with:
dfMeasured value Measured differential frequency
Δf set point for Parameter for default set point value for the frequency balancing
balancing commands
df/dt of the controller Parameter for default speed of set point value change

The following figure shows the effect of the functionality.

1258 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dw_build_frequency-adjusting-com, 1, en_US]

Figure 8-74 Generation of Balancing Commands for Frequency

If the speed (frequency) was adjusted in such a way that the differential frequency df ≈ is 0, the voltage
phasors of V1 and V2 are practically standing still. This can result in an angle difference that does not allow
any switching. A certain frequency difference is required for safe switching. A kick pulse is emitted to attain
this state. With the parameter Release for the kick pulse, you can control the generation of a kick
pulse. A kick pulse is only emitted if the frequency difference falls below the setting value for the parameter
f-threshold ASYN<->SYN. You can find the parameter f-threshold ASYN<->SYN in the entry block
Synchr. op.mode. The actuating time of the kick pulse is defined with the parameter Δf for the kick
pulse. The following equation applies:

[fo_frequency-adujsting-command_01, 1, en_US]

with:
tfact Pulse duration
Δf for the kick pulse Parameter for default set point value for the kick pulse
df/dt of the controller Parameter for adapting the balancing commands to the controller

The following figure shows the overall effect of the balancing commands:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1259


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dw_kick-pulse_freq-adj-com, 1, en_US]

Figure 8-75 Kick Pulse and Frequency Adjustment Ranges

Stabilization and Supervision Actions


The parameter Smoothing causes a smoothing of the relevant measuring signal (dV and df) via a recursive
filter. The smoothing of the signals prevents wrong balancing commands from being issued to control the
voltage and frequency in case of a strong fluctuation of the signals. The smoothing has a low-pass behavior
corresponding to a delay element of the 1st order (for PT1 behavior, see also Figure 8-82).
When the voltage and the frequency are adjusted simultaneously, you must ensure that the admissible over-
excitation limit for the generator is not exceeded. The overexcitation is determined by monitoring the (V/
Vrated)/(f/frated) ratio and compared to the admissible threshold value (parameter (V/Vrated)/(f/frated)).
When the threshold value is exceeded, a voltage balancing command is issued. In this way, the generator
returns to the admissible operating range. The maximum admissible voltage threshold (V2max) for V2 is deter-
mined using the overexcitation parameter and the f2/frated ratio.
A generator can only be synchronized with a system when there is a certain amount of slip. The frequency
difference is a measure for the slip within the functionality. A practically constant frequency difference is
assumed when determining the switching point. When adjusting the frequency, take care that no frequency
balancing commands are issued near a potential switching point. When the frequency is in the admissible
band (parameters Max. frequency diff. f2>f1 and Max. frequency diff. f2<f1; see also
Figure 8-75), the currently determined angle difference of the voltage (dα) is used to calculate the speed of
change (dα/dt). This can be used to calculate the remaining time up to the synchronized point (dα → 0)
continuously. If the determined time reaches of the value for the parameter T close without balancing
or falls below it, a frequency balancing command will no longer be issued and any active frequency adjust-
ment will be discontinued.

8.4.9.2 Application and Setting Notes


Use the Synchronous/asynchronous stage type with balancing commands (Syn./Asy.bal.) for synchro-
nizing generators automatically.
You can find the Syn./Asy.bal. stage in the DIGSI 5 library under FG Circuit Breaker → Synchronization →
Function extensions.

1260 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[sc_FBadjcomm, 1, en_US]

Figure 8-76 Extract from the DIGSI Library

Delete the stages of the synchronization function that are not used.

Routing the Voltage Transformers to the Measuring Points

NOTE

i Ensure that the transformer connections available in the specific application are routed to the correct meas-
uring point!
You can find the routing in the DIGSI 5 project tree under Function-group connections → Connect meas-
uring points to function group.

• Route the system-side transformer connections in the FG Circuit breaker to the input V Sync 1.

• Route the generator-side transformer connections in the FG Circuit breaker to the input V Sync 2.

The following figures show possible connection variants for the voltage transformers:

[dw_dim_two_3ph-voltage-trans, 1, en_US]

Figure 8-77 Connection of Two 3-Phase Voltage Transformers

SIPROTEC 5, 7SJ82/7SJ85, Manual 1261


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dw_dim_3ph_and_1ph-voltage-trans, 1, en_US]

Figure 8-78 Connection of a 3-Phase and a 1-Phase Voltage Transformer (Phase-to-Phase Voltage)

[dw_dim_two_1ph-voltage-trans, 1, en_US]

Figure 8-79 Connection of Two 1-Phase Voltage Transformers (Phase-to-Phase Voltage)

If you have routed the voltage transformers to the measuring points, set the corresponding transformer data
in the System data.
In the FG Circuit breaker, under General, set the rated voltage that is used as a reference for percentage-
value scaling.
Siemens recommends routing the functional measured values into the fault record in addition to the logical
signals. Route at least the functional measured values (_:2311:300) dV, (_:2311:301) df, and
(_:2311:302) dα into the fault record. This allows you to document the commissioning and subsequently
the quality of synchronization.
The asynchronous operating mode defines the automatic synchronization of generators. For this reason, the
parameters for this operating mode are described in the following sections.
You can find the basic parameters in the setting sheet for the Syn./Asy.bal. stage in the General block. The
default settings for the parameters are typical values. You can use the default settings if the transformer has a
secondary rated voltage of 100 V.

1262 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[sc_FB0_adj_comm, 1, en_US]

Figure 8-80 General Block for Syn./Asy.Bal. Stage in the DIGSI Setting Sheet

If you want to switch the generator to a dead busbar (black start), Siemens recommends keeping the default
values and controlling the release via the binary input signal (_:506) >Op. mode 'V1<V2>'.
The preset voltage ranges V1 < 5 V (dead busbar) and V2 > 80 V (live generator) are tested only once the
binary input signal (_:506) >Op. mode 'V1<V2>' is active. Siemens recommends this procedure.
If you set the parameter (_:105) Close cmd. at V1< & V2> = yes, on the other hand, the voltage
ranges are tested automatically once synchronization has started. The condition V1 < 5 V is met if the voltage
is really 0 V or in case of an interruption.
In case of an interruption, the current voltage state of the busbar is unknown and there is a risk of wrong
synchronization. In this case, you can increase safety with the following measures:

• The operational crew deliberately releases synchronization.

• Alternatively, you can control release via a redundant 2nd channel. If V1 < 5 V (dead busbar), the binary
input signal (_:506) >Op. mode 'V1<V2>' is active.

[sc_FB_spglos_sch, 1, en_US]

Figure 8-81 De-en.gized Switch. Block for Syn./Asy.Bal. Stage in the DIGSI Setting Sheet

NOTE

i In the black-start application, a 3-phase voltage connection provides the advantage that all voltages are
monitored. This increases the safety of this application.

Parameters: Sync. operating mode, Async. operating mode

• Default setting (_:119) Sync. operating mode = off

• Default setting (_:114) Async. operating mode = off


With these parameters, you can switch the operating mode of the stage on or off individually. The operating
modes are deactivated in the default setting for safety reasons. Switch the Async. operating mode = on.
You can find possible combinations of operating modes in chapter 8.4.8.2 Application and Setting Notes.

Parameter for Asynchronous Operation: Maximum Differential Values for Voltage and Frequency

• Default setting (_:113) CB make time = 0.06 s

• Default setting (_:115) Max. voltage diff. V2>V1 = 2.0 V

• Default setting (_:116) Max. voltage diff. V2<V1 = 2.0 V

SIPROTEC 5, 7SJ82/7SJ85, Manual 1263


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

• Default setting (_:117) Max. frequency diff. f2>f1 = 0.10 Hz

• Default setting (_:118) Max. frequency diff. f2<f1 = 0.10 Hz


The default settings are typical values you can use to synchronize generators. For example, if you only want to
connect to the network supersynchronously, set the parameter (_:118) Max. frequency diff. f2<f1
= 0 Hz.
With the parameter (_:113) CB make time, you set the make time of the closing circuit (circuit-breaker
operating time + times of auxiliary relay, where applicable). You must measure this time during commis-
sioning.

Parameter: f-threshold ASYN<->SYN

• Recommended setting value (_:120) f-threshold ASYN<->SYN = 0.01 Hz


With the parameter f-threshold ASYN<->SYN, you set the frequency difference for switching over
between synchronous and asynchronous operation. You can find this parameter in the Synchr. op.mode
block.
Siemens recommends keeping the default setting value of 0.01 Hz.
This parameter is also taken into account when the kick pulse has been activated (see Figure 8-75).

Parameters for Balancing Commands used to Control the Voltage


The following parameters are used as balancing commands to control the voltage:

• (_:131) Balancing voltage V2

• (_:132) T V pulse min

• (_:133) T V pulse max

• (_:134) dV per second

• (_:135) T pause V

• (_:136) Smoothing

• (_:137) (V/Vrated)/(f/frated)

Parameter: Balancing voltage V2

• Default setting (_:131) Balancing voltage V2 = off


With the parameter Balancing voltage V2, you specify whether you wish to issue balancing commands
for the voltage V2 on the generator side or not. If you wish to issue balancing commands for the voltage, 2
alternatives are available for voltage control.
Parameter Value Description
off If you select this setting value, no balancing commands are issued for the
voltage V2 on the generator side.
transformer tap If you select this setting value, the balancing commands are issued to the
voltage controller. The balancing commands control the voltage via the tap
changer on the transformer with the pulse duration T V pulse max.
balancing pulses If you select this setting value, balancing commands are issued for the
voltage V2 to the voltage controller of the generator.

Parameter: T V pulse min

• Default setting (_:132) T V pulse min = 0.10 s


With the parameter T V pulse min, you set the minimum time of the control pulse. It corresponds to the
minimum time to which the voltage controller responds. Set the parameter T V pulse min to this limiting
value. The default setting is a practicable value.

1264 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Parameter: T V pulse max

• Default setting (_:133) T V pulse max = 1.00 s


With the parameter T V pulse max, you set the maximum time of the control pulse. The default setting is a
practicable value. This allows you to avoid overadjustment of the voltage in case of major voltage differences.

Parameter: dV per second

• Default setting (_:134) dV per second = 2.00 V/s


With the parameter dV per second, you adjust the balancing commands to the controller. You can thus
correctly define the set point value. The duration of the control pulse is derived from the measured differential
voltage and from the setting value of the parameter. The default setting is a practicable value. Use the
following equation to estimate the actuating time.

[fo_voltage-adujsting-command, 1, en_US]

with:
dVMeasured value Measured differential voltage
dV per second Parameter for specifying the speed of set point value change

EXAMPLE:
The following values apply to the example:
Measured differential voltage dV = 4 V
Parameter setting value dV per second = 2 V/s

Use the following equation to estimate the duration of the balancing pulse:

[fo_du-dt_2v-s, 1, en_US]

The calculated duration of the setting pulse is 2 s. The setting value of the parameter (_:133) T V pulse
max limits the maximum duration of the setting pulse to 1 s. In this case, the value of 1 s applies.

Parameter: T pause V

• Default setting (_:135) T pause V = 5.00 s


With the parameter T pause V, you set the dead time between the balancing commands. This allows the
controller or generator to respond to the control pulse. Determine the final setting value during commis-
sioning.

Parameter: Smoothing

• Default setting (_:136) Smoothing = 1


The parameter Smoothing is used for additional smoothing of the dV voltage measured values.
If the measured differential voltage dV fluctuates during commissioning, increase the default setting. The
smoothing has low-pass behavior (PT1 behavior).
Figure 8-82 allows you to estimate the effect of the setting value of the parameter. The following figure
shows the step response. The longer the delay, the greater the smoothing effect.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1265


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dw_characteristic-adjusting-com, 1, en_US]

Figure 8-82 Effect of Smoothing Depending on the Set Parameter

Parameter: (V/Vrated)/(f/frated)

• Default setting (_:137) (V/Vrated)/(f/frated) = 1.10


With the parameter (V/Vrated)/(f/frated), you specify the overexcitation threshold.
The default setting is a typical value. Note that the thresholds refer to primary voltages. You can also easily
calculate with secondary values, as the voltage transformers are usually exactly adjusted to the rated voltage
of the plant. In case of deviations, you must correct the default setting.

EXAMPLE:

Permissible value (V/Vrated)/(f/frated) 1.1


Primary rated voltage of the generator Vprim = 10.5 kV
Primary voltage of the voltage transformer Vprim, trans. = 10 kV

This results in the following secondary setting value:

[fo_v-rated_the_generator, 1, en_US]

Parameters for Balancing Commands used to Control the Frequency


The following parameters are used as balancing commands to control the frequency:

• Balancing frequency f2

• T f pulse min

• T f pulse max

• df/dt of the controller

• T pause f

1266 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

• Δf set point for balancing

• Smoothing

• T close without balancing

• Release for the kick pulse

• Δf for the kick pulse

• Stabilization

Parameter: Balancing frequency f2

• Default setting (_:141) Balancing frequency f2 = off


With the parameter Balancing frequency f2, you specify whether you wish to issue balancing
commands for the frequency f2 on the generator side or not.
Parameter Value Description
off If you select this setting value, no balancing commands are issued for the
frequency f2 on the generator side.
balancing pulses If you select this setting value, balancing commands are issued for the
frequency f2 on the generator side.

Parameter: T f pulse min

• Default setting (_:142) T f pulse min = 0.10 s


With the parameter T f pulse min, you set the minimum time of the control pulse. It corresponds to the
minimum time to which the frequency controller responds. Set the time to this limiting value. The default
setting is a practicable value.

Parameter: T f pulse max

• Default setting (_:143) T f pulse max = 1.00 s


With the parameter T f pulse max, you set the maximum time of the control pulse. The default setting is a
practicable value. This allows you to avoid overadjustment of the speed in case of major frequency differ-
ences.

Parameter: df/dt of the controller

• Default setting (_:144) df/dt of the controller = 1.00 Hz/s


With the parameter df/dt of the controller, you adjust the balancing commands to the controller.
This allows the set point value to be specified correctly. The control pulse is derived from the measured differ-
ential frequency, the setting value of the parameter df/dt of the controller, and the set point value
Δf set point for balancing. The default setting is a practicable value.
Use the following equation to estimate the duration of the balancing pulse:

[fo_frequency-adujsting-command, 1, en_US]

with:
dfMeasured value Measured differential frequency
Δf set point for Parameter for specifying the set point value for the frequency balancing
balancing commands
df/dt of the controller Parameter for specifying the speed of set point value change

SIPROTEC 5, 7SJ82/7SJ85, Manual 1267


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Parameter: T pause f

• Default setting (_:145) T pause f = 10.00 s


With the parameter T pause f, you set the dead time between the balancing commands. This allows the
controller and the generator to respond to the control pulse. Determine the final setting value during commis-
sioning.

Parameter: Δf set point for balancing

• Default setting (_:146) Δf set point for balancing = 0.04 Hz


With the parameter Δf set point for balancing, you define the set point value for the frequency
adjustment. The default setting is a practicable value.

EXAMPLE:

Measured differential frequency df = 0.5 Hz


Parameter setting value df/dt of the controller = 1 Hz/s
Set point value Δf set point for balancing = 0.04 Hz

Use the following equation to calculate the duration of the balancing pulse:

[fo_df-dt_1hz-s, 1, en_US]

Parameter: Smoothing

• Default setting (_:147) Smoothing = 1


The parameter Smoothing is used for additional smoothing of the df frequency measured values. If the meas-
ured differential frequency df fluctuates during commissioning, increase the default setting. For hydropower
plants, in particular, the generator speed may fluctuate, necessitating corresponding adjustment.
Smoothing results in proportional transmission behavior with a delay of the 1st order (PT1 behavior).
Figure 8-82 allows you to estimate the effect of the setting value of the parameter.

Parameter: T close without balancing

• Default setting (_:148) T close without balancing = 5.00 s


With the parameter T close without balancing, you set the time within which no balancing commands
are to be issued. This avoids having the frequency change at the moment of switching. The time is thus the
remaining duration up to a possible switching. The parameter T close without balancing is active if
the frequency difference is within the set band (see Figure 8-75).
Proceed as follows to estimate the time:
Use the set frequency difference to calculate the period duration. The phasors are in phase opposition after
half of that time. Do not adjust the frequency within the range from approximately 120° to a maximum of
180° before switching.

EXAMPLE:
The set frequency band in the example is df = 0.1 Hz.
At this threshold, the period duration is as follows:

[fo_Tdf, 1, en_US]

Assuming a constant differential frequency of 0.1 Hz, dα changes by 360° in 10 s.

1268 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

The rule of three may be used to estimate the minimum dead time as follows:
360° = 10 s
120° = tmin

[fo_frequenzband, 1, en_US]

Set the parameter T close without balancing to a higher value, as in a practical case, the current
differential frequency is less than 0.1 Hz (for example, set point value 0.04 s).
At a differential frequency of 0.04 Hz, a 360° rotation takes 25 s and this leads to a minimum dead time of
approximately 8 s.
The example shows that the default setting of 5.00 s is a practicable value.

Parameter: Release for the kick pulse

• Default setting (_:149) Release for the kick pulse = off


With the parameter Release for the kick pulse, you can activate the kick pulse.
If you need a kick pulse for your application, change the default setting.

Parameter: Δf for the kick pulse

• Default setting (_:150) Δf for the kick pulse = 0.04 Hz


With the parameter Δf for the kick pulse, you define the set point value for the kick pulse. The pulse
duration is derived from this.
Set the parameter Δf for the kick pulse to the same value as the parameter Δf set point for
balancing.
The setting value of 0.04 Hz leads to the following duration for the kick pulse:

[fo_frequency-adujsting-command_02, 1, en_US]

If the controller does not respond to this brief pulse (tfact < t pulse min), the minimum pulse T f pulse
min applies.

Parameter: Stabilization

• Default setting (_:151) Stabilization = no


If the dead time is too short, the parameter Stabilization results in a faster compensation of the speed
controller.
Parameter Value Description
no The default setting no is a practicable value for typical synchronization
applications.
yes If the dead time is short, the transition process has not yet been completed
after a control pulse for the frequency. The frequency can fluctuate around
its set point value.
If you set the parameter Stabilization = yes, the transient status is
attenuated by canceling the control pulse or by issuing a control pulse in
the reverse direction in time.
Siemens only recommends this setting value if you wish to achieve fast
synchronization by means of short dead times or for special applications.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1269


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.9.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 Syn./Asy.bal.#:Mode • off off
• on
• test
_:101 Syn./Asy.bal.#:Min. oper- 0.300 V to 340.000 V 90.000 V
ating limit Vmin
_:102 Syn./Asy.bal.#:Max. 0.300 V to 340.000 V 110.000 V
operat. limit Vmax
_:110 Syn./ 0.00 s to 3600.00 s; ∞ 30.00 s
Asy.bal.#:Max.durat.
sync.process
_:108 Syn./Asy.bal.#:Direct • no no
close command
• yes
_:126 Syn./Asy.bal.#:Voltage 0.500 to 2.000 1.000
adjustment
De-en.gized switch.
_:105 Syn./Asy.bal.#:Close • no no
cmd. at V1< & V2>
• yes
_:106 Syn./Asy.bal.#:Close • no no
cmd. at V1> & V2<
• yes
_:107 Syn./Asy.bal.#:Close • no no
cmd. at V1< & V2<
• yes
_:103 Syn./Asy.bal.#:V1, V2 0.300 V to 170.000 V 5.000 V
without voltage
_:104 Syn./Asy.bal.#:V1, V2 0.300 V to 340.000 V 80.000 V
with voltage
_:109 Syn./Asy.bal.#:Supervi- 0.00 s to 60.00 s 0.10 s
sion time
Asynchr. op.mode
_:114 Syn./Asy.bal.#:Async. • off off
operating mode
• on
_:113 Syn./Asy.bal.#:CB make 0.01 s to 0.60 s 0.06 s
time
_:115 Syn./Asy.bal.#:Max. 0.000 V to 170.000 V 2.000 V
voltage diff. V2>V1
_:116 Syn./Asy.bal.#:Max. 0.000 V to 170.000 V 2.000 V
voltage diff. V2<V1
_:117 Syn./Asy.bal.#:Max. 0.000 Hz to 4.000 Hz 0.100 Hz
frequency diff. f2>f1
_:118 Syn./Asy.bal.#:Max. 0.000 Hz to 4.000 Hz 0.100 Hz
frequency diff. f2<f1
Synchr. op.mode
_:119 Syn./Asy.bal.#:Sync. • off off
operating mode
• on
_:120 Syn./Asy.bal.#:f- 0.010 Hz to 0.200 Hz 0.010 Hz
threshold ASYN<->SYN

1270 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Addr. Parameter C Setting Options Default Setting


_:122 Syn./Asy.bal.#:Max. 0.000 V to 170.000 V 2.000 V
voltage diff. V2>V1
_:123 Syn./Asy.bal.#:Max. 0.000 V to 170.000 V 2.000 V
voltage diff. V2<V1
_:124 Syn./Asy.bal.#:Max. 0 ° to 90 ° 10 °
angle diff. α2>α1
_:125 Syn./Asy.bal.#:Max. 0 ° to 90 ° 10 °
angle diff. α2<α1
_:121 Syn./Asy.bal.#:Delay 0.00 s to 60.00 s 0.00 s
close command
Balancing V
_:131 Syn./Asy.bal.#:Balancing • off off
voltage V2
• transformer tap
• balancing pulses
_:132 Syn./Asy.bal.#:T V pulse 0.01 s to 1.00 s 0.10 s
min
_:133 Syn./Asy.bal.#:T V pulse 0.01 s to 60.00 s 1.00 s
max
_:134 Syn./Asy.bal.#:dV per 0.100 V/s to 50.000 V/s 2.000 V/s
second
_:135 Syn./Asy.bal.#:T pause V 0.10 s to 60.00 s 5.00 s
_:136 Syn./ 1 to 100 1
Asy.bal.#:Smoothing
_:137 Syn./Asy.bal.#:(V/ 1.00 to 1.40 1.10
Vrated)/(f/frated)
Balancing f
_:141 Syn./Asy.bal.#:Balancing • off off
frequency f2
• balancing pulses
_:142 Syn./Asy.bal.#:T f pulse 0.01 s to 1.00 s 0.10 s
min
_:143 Syn./Asy.bal.#:T f pulse 0.01 s to 60.00 s 1.00 s
max
_:144 Syn./Asy.bal.#:df/dt of 0.05 Hz/s to 5.00 Hz/s 1.00 Hz/s
the controller
_:145 Syn./Asy.bal.#:T pause f 0.10 s to 60.00 s 10.00 s
_:146 Syn./Asy.bal.#:Δf set -1.00 Hz to 1.00 Hz 0.04 Hz
point for balancing
_:147 Syn./ 1 to 100 1
Asy.bal.#:Smoothing
_:148 Syn./Asy.bal.#:T close 1.00 s to 100.00 s 5.00 s
without balancing
_:149 Syn./Asy.bal.#:Release • off off
for the kick pulse
• on
_:150 Syn./Asy.bal.#:Δf for the -1.00 Hz to 1.00 Hz 0.04 Hz
kick pulse
_:151 Syn./Asy.bal.#:Stabiliza- • no no
tion
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 1271


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.9.4 Information List

No. Information Data Class Type


(Type)
Syn./Asy.bal.#
_:81 Syn./Asy.bal.#:>Block stage SPS I
_:500 Syn./Asy.bal.#:>Selection SPS I
_:502 Syn./Asy.bal.#:>Start / stop syn.proc. SPS I
_:503 Syn./Asy.bal.#:>Start syn. process SPS I
_:504 Syn./Asy.bal.#:>Stop syn. process SPS I
_:506 Syn./Asy.bal.#:>Op. mode 'V1<V2>' SPS I
_:505 Syn./Asy.bal.#:>Op. mode 'V1>V2<' SPS I
_:507 Syn./Asy.bal.#:>Op. mode 'V1<V2<' SPS I
_:508 Syn./Asy.bal.#:>Op. mode 'dir.cls.cmd' SPS I
_:501 Syn./Asy.bal.#:>Block close command SPS I
_:511 Syn./Asy.bal.#:>Block balancing SPS I
_:513 Syn./Asy.bal.#:>Block V2 balancing SPS I
_:514 Syn./Asy.bal.#:>Block f2 balancing SPS I
_:54 Syn./Asy.bal.#:Inactive SPS O
_:52 Syn./Asy.bal.#:Behavior ENS O
_:53 Syn./Asy.bal.#:Health ENS O
_:328 Syn./Asy.bal.#:In progress SPS O
_:324 Syn./Asy.bal.#:Release close cmd. SPS O
_:305 Syn./Asy.bal.#:All sync. conditio. OK SPS O
_:303 Syn./Asy.bal.#:State f-synchronous SPS O
_:325 Syn./Asy.bal.#:Voltage difference OK SPS O
_:326 Syn./Asy.bal.#:Angle difference OK SPS O
_:327 Syn./Asy.bal.#:Frequency diff. OK SPS O
_:307 Syn./Asy.bal.#:Cond. V1<V2> fulfilled SPS O
_:306 Syn./Asy.bal.#:Cond. V1>V2< fulfilled SPS O
_:308 Syn./Asy.bal.#:Cond. V1<V2< fulfilled SPS O
_:309 Syn./Asy.bal.#:Frequency f1 > fmax SPS O
_:310 Syn./Asy.bal.#:Frequency f1 < fmin SPS O
_:311 Syn./Asy.bal.#:Frequency f2 > fmax SPS O
_:312 Syn./Asy.bal.#:Frequency f2 < fmin SPS O
_:313 Syn./Asy.bal.#:Voltage V1 > Vmax SPS O
_:314 Syn./Asy.bal.#:Voltage V1 < Vmin SPS O
_:315 Syn./Asy.bal.#:Voltage V2 > Vmax SPS O
_:316 Syn./Asy.bal.#:Voltage V2 < Vmin SPS O
_:317 Syn./Asy.bal.#:V dif.too large(V2>V1) SPS O
_:318 Syn./Asy.bal.#:V dif.too large(V2<V1) SPS O
_:319 Syn./Asy.bal.#:f dif.too large(f2>f1) SPS O
_:320 Syn./Asy.bal.#:f dif.too large(f2<f1) SPS O
_:329 Syn./Asy.bal.#:dfdiff/dt too large SPS O
_:321 Syn./Asy.bal.#:α dif.too large(α2>α1) SPS O
_:322 Syn./Asy.bal.#:α dif.too large(α2<α1) SPS O
_:304 Syn./Asy.bal.#:Max. time exceeded SPS O
_:323 Syn./Asy.bal.#:Setting error SPS O
_:332 Syn./Asy.bal.#:V2 control pulse higher SPS O

1272 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

No. Information Data Class Type


(Type)
_:331 Syn./Asy.bal.#:V2 control pulse lower SPS O
_:334 Syn./Asy.bal.#:f2 control pulse higher SPS O
_:333 Syn./Asy.bal.#:f2 control pulse lower SPS O

8.4.10 Expanded Checks (df/dt and Smoothing of Oscillations)

When configuring the Expanded delta-f options function block, you can expand the synchronization checks
to include the following aspects:

• Limitation of the frequency change rate


With this option, you can define additional upper limits for the rate of permissible requency difference
change. The release checks for both stage types take these additional upper limits into consideration.
Both activation (parameters (_:140) Limit dfdiff/dt for sync. op and (_:142) Limit
dfdiff/dt for asyn. op) and the upper limits (parameters (_:141) Max. value dfdiff/dt
syn and (_:143) Max. value dfdiff/dt asyn) for the frequency change rate are adjustable
selectively for synchronous and asynchronous conditions. Both stage types consider the frequency
change rate when issuing the release for switching and indicate when the rate is exceeded.
If you also activate the option to compensate for low-frequency oscillations (parameter (_:150)
Suppr. frequ. oscillations), the frequency change rate is stabilized in the presence of such oscil-
lations. Stabilization is in effect for asynchronous as well as synchronous operating modes.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1273


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

• Compensation for low-frequency oscillations


If you activate this option (parameter (_:150) Suppr. frequ. oscillations), low-frequency
oscillations, for example, as a consequence of power swings in the range of 0.8 Hz to 1.6 Hz are detected
and smoothed. This stabilizes the release checks in the presence of frequently changing violations of
upper and lower limits for the specified frequency threshold values. The option affects the frequency
check of the Synchrocheck stage types and the synchronous operating mode of the Synchronous/Asyn-
chronous stage type. It does not affect the asynchronous operating mode.
In the example of the following figure, the synchrocheck function would initiate energization, if the
allowed frequency difference was set to 10 mHz without the parameter Suppr. frequ. oscilla-
tions as soon as the frequency f2 enters the 10-mHz band. If the parameter Suppr. frequ. oscil-
lations is activated, energization is not initiated, since the average value of f2 is outside the band.

[dwsynfre-101013-01.vsd, 1, en_US]

Figure 8-83 Example: Frequency Difference between the Constant Frequency f1 and the Sinusoidal
Oscillating Frequency f2

With this option active, the range of function measured values is expanded by the smoothed frequency.
Release of switching in synchronous networks occurs after one second at the earliest. This time is needed
to smooth the frequency measured values.
The actual frequency can be larger or smaller than the smoothed value at any instant. The Max. diff.
"f threshold" parameter makes it possible to limit the increase in instantaneous frequency value in
relation to the respective frequency threshold value.

8.4.11 Closing at De-Energized Line/Busbar

8.4.11.1 Description
If at least one of 2 parts of an electrical power system is de-energized, the parts of the electrical power system
can be connected together via the following operating modes.
If the measured voltage is less than the threshold V1, V2 without voltage, the zero potential of the part
of the electrical power system is detected. In this case, all phases are compared to the parameter V1, V2
without voltage. The energized side must be in the defined operating range with respect to voltage and
frequency (see chapter 8.4.4.1 Description) and all phases must exceed the threshold V1, V2 with
voltage.
The following additional closing conditions can be selected, which are then applied next to the closing condi-
tions for the synchronism:

1274 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Settings Description
Close cmd. at V1> & V2< Closing release under the condition that the part V1 of the power
system is energized and the part of the electrical power system
U2 is de-energized.
Close cmd. at V1< & V2> Closing release under the condition that the part V1 of the power
system is de-energized and the part of the electrical power
system U2 is energized.
Close cmd. at V1< & V2< Closing release provided mains adapters V 1 and V2 are de-ener-
gized.

Each of these conditions can be made effective individually via parameters or binary input. You can also set
parameters for combinations, for example a release for closure, if Close cmd. at V1> & V2< or Close
cmd. at V1< & V2> has been fulfilled.

[losyn003-160311-01.tif, 1, en_US]

Figure 8-84 Release Conditions for Switching to De-Energized Line/Busbar

The indications Cond. V1>V2< fulfilled, Cond. V1<V2> fulfilled and Cond. V1<V2<
fulfilled indicate that the relevant conditions are fulfilled.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1275


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

You can use the Supervision time parameter to set a supervision time for which the closing conditions
must at least be fulfilled with de-energized connection, before closing is allowed.

8.4.11.2 Application and Setting Notes


If at least one of 2 parts of an electrical power system is de-energized, the parts of the electrical power system
can be connected together via the following operating modes. The above potential release conditions are
independent of one another and can also be combined.

NOTE

i For reasons of safety, the releases have been deactivated in the default setting and are therefore at no.
Even if you wish to apply one of these operating modes, Siemens recommends leaving the setting at no for
reasons of safety. Set the operating mode only dynamically via the assigned binary input signal (for
example >Operating mode 'U1>U2<') (see also Figure 8-84). This prevents one of these operating
modes from being incorrectly activated statically thereby resulting in an incorrect switching.

Parameter: Close cmd. at V1< & V2>

• Recommended setting value (_:5071:105) Close cmd. at V1< & V2> = no

Settings Description
no No release for closing is possible via this operating mode.
yes If part V1of the power system is de-energized and part V2 of the power
system is energized, the release for closure is given upon starting the
synchronization stage after the supervision time has passed.
The setting depends on the operational requirements. Note the above
information.

Parameter: Close cmd. at V1> & V2<

• Recommended setting value (_:5071:106) Close cmd. at V1> & V2< = no

Settings Description
no No release for closing is possible via this operating mode.
yes If part V1of the power system is energized and part V2 of the power
system is de-energized, the release for closure is given upon starting the
synchronization stage after the supervision time has passed.
The setting depends on the operational requirements. Note the above
information.

Parameter: Close cmd. at V1< & V2<

• Recommended setting value (_:5071:107) Close cmd. at V1< & V2< = no

Settings Description
no No release for closing is possible via this operating mode.
yes If the parts V1 and V2 of the power system are de-energized, the release
for closure is given upon starting the synchronization stage after the
supervision time has passed.
The setting depends on the operational requirements. Note the above
information.

Parameter: V1, V2 with voltage

• Recommended setting value (_:5071:104) V1, V2 with voltage = 80 V


The setting value indicates the voltage above which a part of the power system (feeder or busbar) can be
regarded as activated with certainty.

1276 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

You must set the value below the minimum expected operational undervoltage. Siemens therefore recom-
mends a setting value of approx. 80 % of the rated voltage. All voltages connected according to the parame-
terized measuring-point connection type are subjected to the appropriate Vmin/Vmax test.

Parameter: V1, V2 without voltage

• Recommended setting value (_:5071:103) V1, V2 without voltage = 5 V


The setting value indicates the voltage below which a part of the power system (feeder or busbar) can be
regarded as deactivated with certainty.
Siemens recommends a setting value of approx. 5 % of the rated voltage for this. All voltages connected
according to the parameterized measuring-point connection type are subjected to the appropriate Vmin/Vmax
test.

Parameter: Supervision time

• Recommended setting value (_:5071:109) Supervision time = 0.1 s


The parameter defines a supervision time for which the above additional closing conditions have to be at least
fulfilled at de-energized switching, before the release for closing is given. In order to include transient
phenomena, Siemens recommends a value of 0.1 s.

Parameter: Direct close command

• Recommended setting value (_:5071:108) Direct close command = no


In this operating mode, the function initiates a closing release without any testing upon start of the synchroni-
zation stage. The closure occurs immediately.

NOTE

i For safety reasons, Siemens recommends leaving the setting atno. If a direct close command is necessary,
Siemens recommends only using this operating mode dynamically via the binary input signal >Op. mode
'dir.cls.cmd' (see also Figure 8-86). This prevents this operating mode from being incorrectly acti-
vated statically thereby resulting in an incorrect switching.

8.4.12 Direct Close Command

You can activate the operating mode direct close command statically via the Direct close command
parameter or dynamically with the binary input signal >Op. mode 'dir.cls.cmd' (see Figure 8-85).

[losyndir-140611-01.tif, 1, en_US]

Figure 8-85 Activation of the Operating Mode Direct Close Command

The operating mode Direct close command function initiates a closure release without any testing upon start
of the synchronization stage. The closure occurs immediately.
The combination Direct close command with other operating modes is not recommended, as the other oper-
ating data is bypassed.
If the synchronization function is defective (standby of the sync stage = alarm or warning), a direct close
command is executed or not executed, depending on the type of fault (see also supervisions in chapter
8.4.4.1 Description).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1277


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.13 Interaction with Control, Automatic Reclosing (AREC), and External Triggering

With Control
The control and synchronization functions are always located in a Circuit-breaker function group. The control
and also the synchronization function always operate with the circuit breaker, which is linked to the Circuit-
breaker function group.
As soon as the synchronization function is in the Circuit-breaker function group, the circuit breaker is subject
to compulsory synchronization. If all synchronization stages are deactivated, the circuit breaker cannot be acti-
vated via the control, as no release can be generated for the closure. The circuit breaker is no longer subject to
compulsory synchronization after deletion of the synchronization function. Closure without synchronization is
then possible via the control.
If closure is to be synchronized via the control, the control automatically generates an internal signal which
starts the synchronization function. The functional sequence is described in chapter 8.4.6 Sequence of Func-
tions. After fulfilling all closing conditions, the synchronization sends a release signal to the control, which
closes the circuit breaker and then stops and synchronization function.

[losynaw1-310111-01.tif, 2, en_US]

Figure 8-86 Interaction of the Control with the Synchronization Function

With Automatic Reclosing


The automatic reclosing mechanism (AREC) can also work with the synchronization function. Both functions
are always located in a Circuit-breaker function group. Consequently the AREC and synchronization function
always work with the circuit breaker that is linked to the Circuit-breaker function group.
You must select a synchronization stage via settings within the AREC so that closure is synchronized by the
AREC. The tests for the synchronization stage are used for the closure by the AREC. If no synchronization stage
is selected, the AREC then activates without synchronization.
If closure is to be synchronized via the AREC, the AREC automatically generates an internal signal which starts
the synchronization function. The functional sequence is described in chapter 8.4.6 Sequence of Functions.
After fulfilling all closing conditions, the synchronization sends a release signal to the AREC, which closes the
circuit breaker and then stops and synchronization function.

1278 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[losynaw2-100611-01.tif, 2, en_US]

Figure 8-87 Connection of the AREC to the Synchronization Function

With External Control


You have the option of controlling the synchronization function externally via binary input signals. This can be
done as follows:

• Edge-controlled

• Via the signals >Start syn. process and >Stop syn. process

• State-controlled, via the signal >Start / stop syn.proc. (see also chapter 8.4.6 Sequence of Func-
tions).
The start is followed by the functional sequence (see chapter 8.4.6 Sequence of Functions). If the conditions
are fulfilled, the output signal Release close cmd. is issued. The switched object QAx of the Circuit-
breaker function group is not closed. The output signal Release close cmd. must be explicitly routed to
the binary output in order to close the circuit breaker.

[losynaw3-160311-01.tif, 2, en_US]

Figure 8-88 Interaction of the Synchronization Function with External Control

SIPROTEC 5, 7SJ82/7SJ85, Manual 1279


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.14 External Synchronization

8.4.14.1 Description
The purpose of the External synchronization function is to control an external synchronization device.

[dw_ctrl_ext_sync_device, 1, en_US]

Figure 8-89 Triggering an External Synchronization Device

The bay controller in bay x should switch the circuit breaker in bay x in synchrony. The synchronization check
is carried out in the central paralleling device 7VE6. In addition to the paralleling device, another central bay
controller ensures the switching of the correct measuring voltages and the routing of the CB close command
from the 7VE6 to the correct circuit breaker in bay x. The bay controller x provides the information to the
central bay controller via IEC61850-GOOSE.
The External synchronization is designed as a function block which can be used in the Circuit-breaker func-
tion group. The additional External synchronization function block integrates the external synchronization
into command processing, so that the corresponding feedback can be forwarded to the command source.
If a circuit-breaker close command with a synchronization requirement is present, the external synchroniza-
tion device is started. After successfully checking the synchronization conditions, the close command is issued
from the external synchronization device to the circuit breaker. If a circuit-breaker close command without
synchronization requirement is present, the circuit-breaker close command is issued directly from the Circuit-
breaker function group to the circuit breaker. Also, each circuit-breaker trip command is issued directly to the
circuit breaker.
In case of a failure of the external synchronization device, you can also close the circuit breaker directly
without considering the synchronization conditions.

1280 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

[dwextsyn-02, 1, en_US]

Figure 8-90 Interaction between Control and External Synchronization

Parameterization with DIGSI


In the DIGSI library, the function is visible inside the Circuit-breaker function group as the External synchro-
nization function block. You can instantiate the function block in the Circuit-breaker function group and the
Circuit-breaker (control) function group. You can instantiate only 1 External synchronization function block
within these function groups at a time.

[scextsyn-041116-01, 1, en_US]

Figure 8-91 Instantiating the External Synchronization Function Block in the Circuit-Breaker Function
Group

It is not possible to jointly instantiate the External synchronization function block with the 25 synchroniza-
tion function in the same Circuit-breaker function group.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1281


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Notes for Optional Input Interconnections


You have the option of connecting the input signals >Close cmd. released and >In progress. If you
omit these interconnections, observe the following instructions:
Input >Close cmd. released:
If you do not interconnect the input signal >Close cmd. released, the execution of a circuit-breaker close
command with synchronization requirement is confirmed directly (execution successful: OPR+), as soon as the
output signal Start syn. process is set. In this case, the (_:109) Max.durat. sync.process
setting has no meaning. If you use a control model with feedback monitoring, consider that the feedback
monitoring will start immediately when the Start syn. process signal is tripped. The (_:4201:103)
Feedback monitoring time setting must therefore be set higher than the maximum synchronization
time of the external synchronization device plus the circuit-breaker closing time. If >Close cmd. released
is not routed, the output Start/stop syn. proc. is not set.
Input >In progress:
The interconnection of the input signal >In progress is intended to check whether the synchronization
device has received the Start syn. process signal. If you do not interconnect this input signal and the
external synchronization device rejects a start command, the negative acknowledgment of the circuit-breaker
close command does not occur until the maximum synchronization time (parameter (_:109) Max.durat.
sync.process) has expired.
Input >Op. mode 'dir.cls.cmd':
In case of a failure of the external synchronization device, you can also close the circuit breaker directly
without considering the synchronization conditions. To do this, activate the input signal >Op. mode
'dir.cls.cmd' or the parameter (_:110) Direct close command. The close command is then issued
directly by the bay controller.

8.4.14.2 Application and Setting Notes (External Synchronization)

Parameter: Mode

• Default setting (_:1) Mode = on


With the Mode parameter, you switch the external synchronization function on or off. If you set the Mode
parameter to off, a circuit-breaker close command with synchronization requirement is rejected.

Parameter: Max.durat. sync.process

• Default setting (_:109) Max.durat. sync.process = 30 s


The Max.durat. sync.process parameter defines the maximum synchronization time. The time starts
when the External synchronization function block sends a close command to the external synchronization
device. The command must be executed within this time. If the close command is not executed within this
time, the External synchronization function block sends a command to cancel closing to the external
synchronization device.

Parameter: Direct close command

• Default setting (_:110) Direct close command = no


In case of a failure of the external synchronization device the Direct close command parameter is used to
close the circuit breaker directly without considering the synchronization conditions. If the parameter is acti-
vated a close command with synchronization requirement will not be transmitted to the external synchroniza-
tion device, but directly carried out by the bay controller.

1282 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.14.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 Syn./Asy.bal.#:Mode • off off
• on
• test
_:101 Syn./Asy.bal.#:Min. oper- 0.300 V to 340.000 V 90.000 V
ating limit Vmin
_:102 Syn./Asy.bal.#:Max. 0.300 V to 340.000 V 110.000 V
operat. limit Vmax
_:110 Syn./ 0.00 s to 3600.00 s; ∞ 30.00 s
Asy.bal.#:Max.durat.
sync.process
_:108 Syn./Asy.bal.#:Direct • no no
close command
• yes
_:126 Syn./Asy.bal.#:Voltage 0.500 to 2.000 1.000
adjustment
De-en.gized switch.
_:105 Syn./Asy.bal.#:Close • no no
cmd. at V1< & V2>
• yes
_:106 Syn./Asy.bal.#:Close • no no
cmd. at V1> & V2<
• yes
_:107 Syn./Asy.bal.#:Close • no no
cmd. at V1< & V2<
• yes
_:103 Syn./Asy.bal.#:V1, V2 0.300 V to 170.000 V 5.000 V
without voltage
_:104 Syn./Asy.bal.#:V1, V2 0.300 V to 340.000 V 80.000 V
with voltage
_:109 Syn./Asy.bal.#:Supervi- 0.00 s to 60.00 s 0.10 s
sion time
Asynchr. op.mode
_:114 Syn./Asy.bal.#:Async. • off off
operating mode
• on
_:113 Syn./Asy.bal.#:CB make 0.01 s to 0.60 s 0.06 s
time
_:115 Syn./Asy.bal.#:Max. 0.000 V to 170.000 V 2.000 V
voltage diff. V2>V1
_:116 Syn./Asy.bal.#:Max. 0.000 V to 170.000 V 2.000 V
voltage diff. V2<V1
_:117 Syn./Asy.bal.#:Max. 0.000 Hz to 4.000 Hz 0.100 Hz
frequency diff. f2>f1
_:118 Syn./Asy.bal.#:Max. 0.000 Hz to 4.000 Hz 0.100 Hz
frequency diff. f2<f1
Synchr. op.mode
_:119 Syn./Asy.bal.#:Sync. • off off
operating mode
• on
_:120 Syn./Asy.bal.#:f- 0.010 Hz to 0.200 Hz 0.010 Hz
threshold ASYN<->SYN

SIPROTEC 5, 7SJ82/7SJ85, Manual 1283


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Addr. Parameter C Setting Options Default Setting


_:122 Syn./Asy.bal.#:Max. 0.000 V to 170.000 V 2.000 V
voltage diff. V2>V1
_:123 Syn./Asy.bal.#:Max. 0.000 V to 170.000 V 2.000 V
voltage diff. V2<V1
_:124 Syn./Asy.bal.#:Max. 0 ° to 90 ° 10 °
angle diff. α2>α1
_:125 Syn./Asy.bal.#:Max. 0 ° to 90 ° 10 °
angle diff. α2<α1
_:121 Syn./Asy.bal.#:Delay 0.00 s to 60.00 s 0.00 s
close command
Balancing V
_:131 Syn./Asy.bal.#:Balancing • off off
voltage V2
• transformer tap
• balancing pulses
_:132 Syn./Asy.bal.#:T V pulse 0.01 s to 1.00 s 0.10 s
min
_:133 Syn./Asy.bal.#:T V pulse 0.01 s to 60.00 s 1.00 s
max
_:134 Syn./Asy.bal.#:dV per 0 V/s to 0 V/s 0 V/s
second
_:135 Syn./Asy.bal.#:T pause V 0.10 s to 60.00 s 5.00 s
_:136 Syn./ 1 to 100 1
Asy.bal.#:Smoothing
_:137 Syn./Asy.bal.#:(V/ 1.00 to 1.40 1.10
Vrated)/(f/frated)
Balancing f
_:141 Syn./Asy.bal.#:Balancing • off off
frequency f2
• balancing pulses
_:142 Syn./Asy.bal.#:T f pulse 0.01 s to 1.00 s 0.10 s
min
_:143 Syn./Asy.bal.#:T f pulse 0.01 s to 60.00 s 1.00 s
max
_:144 Syn./Asy.bal.#:df/dt of 0.05 Hz/s to 5.00 Hz/s 1.00 Hz/s
the controller
_:145 Syn./Asy.bal.#:T pause f 0.10 s to 60.00 s 5.00 s
_:146 Syn./Asy.bal.#:Δf set -1.00 Hz to 1.00 Hz 0.04 Hz
point for balancing
_:147 Syn./ 1 to 100 1
Asy.bal.#:Smoothing
_:148 Syn./Asy.bal.#:T close 1.00 s to 100.00 s 5.00 s
without balancing
_:149 Syn./Asy.bal.#:Release • off off
for the kick pulse
• on
_:150 Syn./Asy.bal.#:Δf for the -1.00 Hz to 1.00 Hz 0.04 Hz
kick pulse
_:151 Syn./Asy.bal.#:Stabiliza- 0 to 1000 0
tion

1284 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Addr. Parameter C Setting Options Default Setting


External sync.
_:1 External sync.:Mode • off on
• on
• test
_:109 External 0.00 s to 3600.00 s; ∞ 30.00 s
sync.:Max.durat.
sync.process
_:110 External sync.:Direct • 0 false
close command
• 1

8.4.14.4 Information List

No. Information Data Class Type


(Type)
External sync.
_:506 External sync.:>Synch. device ready SPS I
_:508 External sync.:>In progress SPS I
_:507 External sync.:>Close cmd. released SPS I
_:509 External sync.:>Op. mode 'dir.cls.cmd' SPS I
_:52 External sync.:Behavior ENS O
_:54 External sync.:Health ENS O
_:55 External sync.:Start syn. process SPS O
_:56 External sync.:Stop syn. process SPS O
_:57 External sync.:Start/stop syn. proc. SPS O

8.4.15 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:127 General:Angle adjust. -179.0 ° to 180.0 ° 0.0 °
(transform.)
General
_:5071:1 Synchrocheck 1:Mode • off off
• on
• test
_:5071:101 Synchrocheck 1:Min. oper- 0.300 V to 340.000 V 90.000 V
ating limit Vmin
_:5071:102 Synchrocheck 1:Max. 0.300 V to 340.000 V 110.000 V
operat. limit Vmax
_:5071:110 Synchrocheck 1:Max.durat. 0.00 s to 3600.00 s; ∞ 30.00 s
sync.process
_:5071:108 Synchrocheck 1:Direct close • no no
command
• yes
_:5071:126 Synchrocheck 1:Voltage 0.500 to 2.000 1.000
adjustment
De-en.gized switch.
_:5071:105 Synchrocheck 1:Close cmd. • no no
at V1< & V2>
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 1285


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Addr. Parameter C Setting Options Default Setting


_:5071:106 Synchrocheck 1:Close cmd. • no no
at V1> & V2<
• yes
_:5071:107 Synchrocheck 1:Close cmd. • no no
at V1< & V2<
• yes
_:5071:103 Synchrocheck 1:V1, V2 0.300 V to 170.000 V 5.000 V
without voltage
_:5071:104 Synchrocheck 1:V1, V2 0.300 V to 340.000 V 80.000 V
with voltage
_:5071:109 Synchrocheck 1:Supervi- 0.00 s to 60.00 s 0.1 s
sion time
Synchr. conditions
_:5071:122 Synchrocheck 1:Max. 0.000 V to 170.000 V 5.000 V
voltage diff. V2>V1
_:5071:123 Synchrocheck 1:Max. 0.000 V to 170.000 V 5.000 V
voltage diff. V2<V1
_:5071:117 Synchrocheck 1:Max. 0.000 Hz to 2.000 Hz 0.100 Hz
frequency diff. f2>f1
_:5071:118 Synchrocheck 1:Max. 0.000 Hz to 2.000 Hz 0.100 Hz
frequency diff. f2<f1
_:5071:124 Synchrocheck 1:Max. angle 0 ° to 90 ° 10 °
diff. α2>α1
_:5071:125 Synchrocheck 1:Max. angle 0 ° to 90 ° 10 °
diff. α2<α1
General
_:5041:1 Sychr./Asycr.1:Mode • off off
• on
• test
_:5041:101 Sychr./Asycr.1:Min. oper- 0.300 V to 340.000 V 90.000 V
ating limit Vmin
_:5041:102 Sychr./Asycr.1:Max. operat. 0.300 V to 340.000 V 110.000 V
limit Vmax
_:5041:110 Sychr./Asycr.1:Max.durat. 0.00 s to 3600.00 s; ∞ 30.00 s
sync.process
_:5041:108 Sychr./Asycr.1:Direct close • no no
command
• yes
_:5041:126 Sychr./Asycr.1:Voltage 0.500 to 2.000 1.000
adjustment
De-en.gized switch.
_:5041:105 Sychr./Asycr.1:Close cmd. • no no
at V1< & V2>
• yes
_:5041:106 Sychr./Asycr.1:Close cmd. • no no
at V1> & V2<
• yes
_:5041:107 Sychr./Asycr.1:Close cmd. • no no
at V1< & V2<
• yes
_:5041:103 Sychr./Asycr.1:V1, V2 0.300 V to 170.000 V 5.000 V
without voltage
_:5041:104 Sychr./Asycr.1:V1, V2 with 0.300 V to 340.000 V 80.000 V
voltage

1286 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

Addr. Parameter C Setting Options Default Setting


_:5041:109 Sychr./Asycr.1:Supervision 0.00 s to 60.00 s 0.1 s
time
Asynchr. op.mode
_:5041:114 Sychr./Asycr.1:Async. oper- • off on
ating mode
• on
_:5041:113 Sychr./Asycr.1:CB make 0.01 s to 0.60 s 0.06 s
time
_:5041:115 Sychr./Asycr.1:Max. voltage 0.000 V to 170.000 V 5.000 V
diff. V2>V1
_:5041:116 Sychr./Asycr.1:Max. voltage 0.000 V to 170.000 V 5.000 V
diff. V2<V1
_:5041:117 Sychr./Asycr.1:Max. 0.000 Hz to 4.000 Hz 0.100 Hz
frequency diff. f2>f1
_:5041:118 Sychr./Asycr.1:Max. 0.000 Hz to 4.000 Hz 0.100 Hz
frequency diff. f2<f1
Synchr. op.mode
_:5041:119 Sychr./Asycr.1:Sync. oper- • off on
ating mode
• on
_:5041:120 Sychr./Asycr.1:f-threshold 0.010 Hz to 0.200 Hz 0.010 Hz
ASYN<->SYN
_:5041:122 Sychr./Asycr.1:Max. voltage 0.000 V to 170.000 V 5.000 V
diff. V2>V1
_:5041:123 Sychr./Asycr.1:Max. voltage 0.000 V to 170.000 V 5.000 V
diff. V2<V1
_:5041:124 Sychr./Asycr.1:Max. angle 0 ° to 90 ° 10 °
diff. α2>α1
_:5041:125 Sychr./Asycr.1:Max. angle 0 ° to 90 ° 10 °
diff. α2<α1
_:5041:121 Sychr./Asycr.1:Delay close 0.00 s to 60.00 s 0.00 s
command
dfdiff/dt limitation
_:140 Adv. options:Limit dfdiff/dt • 0 false
for sync. op
• 1
_:141 Adv. options:Max. value 0.010 Hz/s to 0.025 Hz/s 0.010 Hz/s
dfdiff/dt syn
_:142 Adv. options:Limit dfdiff/dt • 0 false
for asyn. op
• 1
_:143 Adv. options:Max. value 0.050 Hz/s to 0.500 Hz/s 0.050 Hz/s
dfdiff/dt asyn
Frequ. oscillations
_:150 Adv. options:Suppr. frequ. • 0 false
oscillations
• 1
_:151 Adv. options:Max. diff. "f 0.000 Hz to 0.100 Hz 0.000 Hz
threshold"

SIPROTEC 5, 7SJ82/7SJ85, Manual 1287


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

8.4.16 Information List

No. Information Data Class Type


(Type)
Measurements
_:2311:303 General:Multiple selection SPS O
_:2311:304 General:Blocked no V selected SPS O
_:2311:329 General:V1 MV O
_:2311:330 General:f1 MV O
_:2311:331 General:V2 MV O
_:2311:332 General:f2 MV O
_:2311:300 General:dV MV O
_:2311:301 General:df MV O
_:2311:302 General:dα MV O
Synchrocheck 1
_:5071:81 Synchrocheck 1:>Block stage SPS I
_:5071:500 Synchrocheck 1:>Selection SPS I
_:5071:502 Synchrocheck 1:>Start / stop syn.proc. SPS I
_:5071:503 Synchrocheck 1:>Start syn. process SPS I
_:5071:504 Synchrocheck 1:>Stop syn. process SPS I
_:5071:506 Synchrocheck 1:>Op. mode 'V1<V2>' SPS I
_:5071:505 Synchrocheck 1:>Op. mode 'V1>V2<' SPS I
_:5071:507 Synchrocheck 1:>Op. mode 'V1<V2<' SPS I
_:5071:508 Synchrocheck 1:>Op. mode 'dir.cls.cmd' SPS I
_:5071:501 Synchrocheck 1:>Block close command SPS I
_:5071:54 Synchrocheck 1:Inactive SPS O
_:5071:52 Synchrocheck 1:Behavior ENS O
_:5071:53 Synchrocheck 1:Health ENS O
_:5071:328 Synchrocheck 1:In progress SPS O
_:5071:324 Synchrocheck 1:Release close cmd. SPS O
_:5071:305 Synchrocheck 1:All sync. conditio. OK SPS O
_:5071:325 Synchrocheck 1:Voltage difference OK SPS O
_:5071:326 Synchrocheck 1:Angle difference OK SPS O
_:5071:327 Synchrocheck 1:Frequency diff. OK SPS O
_:5071:307 Synchrocheck 1:Cond. V1<V2> fulfilled SPS O
_:5071:306 Synchrocheck 1:Cond. V1>V2< fulfilled SPS O
_:5071:308 Synchrocheck 1:Cond. V1<V2< fulfilled SPS O
_:5071:309 Synchrocheck 1:Frequency f1 > fmax SPS O
_:5071:310 Synchrocheck 1:Frequency f1 < fmin SPS O
_:5071:311 Synchrocheck 1:Frequency f2 > fmax SPS O
_:5071:312 Synchrocheck 1:Frequency f2 < fmin SPS O
_:5071:313 Synchrocheck 1:Voltage V1 > Vmax SPS O
_:5071:314 Synchrocheck 1:Voltage V1 < Vmin SPS O
_:5071:315 Synchrocheck 1:Voltage V2 > Vmax SPS O
_:5071:316 Synchrocheck 1:Voltage V2 < Vmin SPS O
_:5071:317 Synchrocheck 1:V dif.too large(V2>V1) SPS O
_:5071:318 Synchrocheck 1:V dif.too large(V2<V1) SPS O
_:5071:319 Synchrocheck 1:f dif.too large(f2>f1) SPS O

1288 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.4 Synchronization Function

No. Information Data Class Type


(Type)
_:5071:320 Synchrocheck 1:f dif.too large(f2<f1) SPS O
_:5071:321 Synchrocheck 1:α dif.too large(α2>α1) SPS O
_:5071:322 Synchrocheck 1:α dif.too large(α2<α1) SPS O
_:5071:304 Synchrocheck 1:Max. time exceeded SPS O
_:5071:323 Synchrocheck 1:Setting error SPS O
Sychr./Asycr.1
_:5041:81 Sychr./Asycr.1:>Block stage SPS I
_:5041:500 Sychr./Asycr.1:>Selection SPS I
_:5041:502 Sychr./Asycr.1:>Start / stop syn.proc. SPS I
_:5041:503 Sychr./Asycr.1:>Start syn. process SPS I
_:5041:504 Sychr./Asycr.1:>Stop syn. process SPS I
_:5041:506 Sychr./Asycr.1:>Op. mode 'V1<V2>' SPS I
_:5041:505 Sychr./Asycr.1:>Op. mode 'V1>V2<' SPS I
_:5041:507 Sychr./Asycr.1:>Op. mode 'V1<V2<' SPS I
_:5041:508 Sychr./Asycr.1:>Op. mode 'dir.cls.cmd' SPS I
_:5041:501 Sychr./Asycr.1:>Block close command SPS I
_:5041:54 Sychr./Asycr.1:Inactive SPS O
_:5041:52 Sychr./Asycr.1:Behavior ENS O
_:5041:53 Sychr./Asycr.1:Health ENS O
_:5041:328 Sychr./Asycr.1:In progress SPS O
_:5041:324 Sychr./Asycr.1:Release close cmd. SPS O
_:5041:305 Sychr./Asycr.1:All sync. conditio. OK SPS O
_:5041:303 Sychr./Asycr.1:State f-synchronous SPS O
_:5041:325 Sychr./Asycr.1:Voltage difference OK SPS O
_:5041:326 Sychr./Asycr.1:Angle difference OK SPS O
_:5041:327 Sychr./Asycr.1:Frequency diff. OK SPS O
_:5041:307 Sychr./Asycr.1:Cond. V1<V2> fulfilled SPS O
_:5041:306 Sychr./Asycr.1:Cond. V1>V2< fulfilled SPS O
_:5041:308 Sychr./Asycr.1:Cond. V1<V2< fulfilled SPS O
_:5041:309 Sychr./Asycr.1:Frequency f1 > fmax SPS O
_:5041:310 Sychr./Asycr.1:Frequency f1 < fmin SPS O
_:5041:311 Sychr./Asycr.1:Frequency f2 > fmax SPS O
_:5041:312 Sychr./Asycr.1:Frequency f2 < fmin SPS O
_:5041:313 Sychr./Asycr.1:Voltage V1 > Vmax SPS O
_:5041:314 Sychr./Asycr.1:Voltage V1 < Vmin SPS O
_:5041:315 Sychr./Asycr.1:Voltage V2 > Vmax SPS O
_:5041:316 Sychr./Asycr.1:Voltage V2 < Vmin SPS O
_:5041:317 Sychr./Asycr.1:V dif.too large(V2>V1) SPS O
_:5041:318 Sychr./Asycr.1:V dif.too large(V2<V1) SPS O
_:5041:319 Sychr./Asycr.1:f dif.too large(f2>f1) SPS O
_:5041:320 Sychr./Asycr.1:f dif.too large(f2<f1) SPS O
_:5041:321 Sychr./Asycr.1:α dif.too large(α2>α1) SPS O
_:5041:322 Sychr./Asycr.1:α dif.too large(α2<α1) SPS O
_:5041:304 Sychr./Asycr.1:Max. time exceeded SPS O
_:5041:323 Sychr./Asycr.1:Setting error SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1289


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.5 Switching Sequences

8.5 Switching Sequences

8.5.1 Overview of Functions

Switching sequences may be running inside the device that switch the switchgear automatically in a prespeci-
fied sequence.
A switching sequence consists of a special function block Switching sequence (Swi. seq.) from the DIGSI 5
Library and the project-specific list of the switching commands that are generated in the CFC.

8.5.2 Function Description

The function block Switching sequence is located in folder User-defined functions in the DIGSI 5 Library.

[scudeffb-150816-01, 1, en_US]

Figure 8-92 Function block Switching Sequence in the Library

These function blocks can be used in the information matrix on the highest level (level of the function groups)
or in a user-defined function group.
One Switching sequence function block is used per switching sequence. The function block is the interface
for controlling and monitoring the condition of the CFC switching sequence. The task of the function block is
to verify the relative conditions for control commands, for example, switching authority, interlocking condi-
tions, etc. You can connect the signals of the function block with the CFC chart. They start and stop the
switching sequence and provide data about the status of the switching sequence (see Figure 8-93). The CFC
chart is used to activate the switching device that must be switched. The CFC blocks define, among other
things, the switching devices that must be switched.

1290 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.5 Switching Sequences

[dwswseq1-110913-01.vsd, 1, en_US]

Figure 8-93 Switching Sequence Function Block

Starting and Canceling a Switching Sequence


One of the following methods can be used to start a switching sequence:

• On-site operation: menu or display page

• Input >Start during rising edge, for example, via binary input

• Controllable Start for the start via a communication protocol, for example, IEC 61850, T103, or DNP

• Input >Start via a function key

• Controllable Start via a function key


One of the following methods can be used to cancel a switching sequence:

• On-site operation: menu or display page

• Input >Cancel during rising edge, for example, via binary input

• Controllable Cancel for the cancelation via a communication protocol, for example, IEC 61850, T103, or
DNP

• Input >Cancel via a function key

• Controllable Cancel via a function key

On-Site Operation
If at least one Switching sequence function block is used in the device, a new Switching sequences entry is
shown in the first line of the Control menu. If this menu item is selected, an overview of all switching
sequences and the current status will be displayed (see Figure 8-94, example with 2 switching sequences).
You can start or cancel the switching sequences from this menu.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1291


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.5 Switching Sequences

Figure 8-94
Overview of the Switching Sequences on the Device Display

8.5.3 Application and Setting Notes

The function block offers similar settings to the Control function block of a circuit breaker or disconnector (see
chapter 8.2.1 General Overview).

[scccs4pa-13112014_DE, 1, en_US]

Figure 8-95 Settings of the Switching Sequence Function Block

Parameter: Check switching authority

• Default setting (_:101) Check switching authority = yes


With the Check switching authority parameter, you can determine whether the switching authority
should be checked before the execution of the switching sequence.
Parameter: Check double activat. blk.

• Default setting (_:102) Check double activat. blk. = yes


With the Check double activat. blk. parameter, you can determine whether the double activation of
switching devices should be checked. The setting value yes indicates that a switching sequence will be
started only if no switching commands for a circuit breaker and disconnector are active, provided that double-
activation blocking was activated for those switching devices.
Parameter: Time-out monitoring
With the Time-out monitoring parameter, you can determine whether the feedback from the process
should be evaluated. The feedback is gathered via the inputs >Successful and >Failed.
Parameter: Monitoring time

• Default setting (_:104) Monitoring time = 30.00 s


With the Monitoring time parameter, you can determine the duration of the monitoring time.

1292 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.5 Switching Sequences

Parameter: Control model

• Default setting (_:105) Control model = SBO w. normal secur.


With the Control model parameter, you select between direct w. normal secur. or SBO w.
normal secur. to start the switching sequence.
It is not possible to set a control model for cancelation of the switching sequence. The control model direct
w. normal secur. is always used to cancel the function.

Information
The Switching sequence function block provides the following data:

[scinfof1-13112014, 1, en_US]

Figure 8-96 Data Provided by the Switching Sequence Function Block

In the Switching sequence function block, the interlocking is analog to the Interlocking function block and it
is possible to use it in the switching sequence:

• >Enable start: Connection to interlocking conditions (CFC) for the start of the entire switching
sequence. Not in effect in the non-interlocked switching mode.

• >Enable start (fixed): Non-revocable interlocking conditions for the start of the entire switching
sequence. In effect regardless of the switching mode.
If the time-out monitoring is activated (parameter Time-out monitoring), the process feedback must take
place via the inputs >Successful and >Failed. If the last switching command of the switching sequence
was executed successfully, the input >Successful usually is set. To do this, connect the feedback of the last
switching command from the CFC with this input of the function block during the device parameterization.
If a switching command fails, this feedback can be captured by the input >Failed. The active switching
sequence will be ended immediately and does not have to wait for a time-out.
The indication Execution signals the current state of the switching sequence. The events running,
canceled, failed, and successful are generated only while the time-out monitoring is activated. The
event Start Trigger is used to start the switching sequence in the CFC chart.

Example for a Switching Sequence with CFC


The following figure shows a single-line diagram for a substation with 4 bays: Busbar grounding, infeed, bus-
coupler circuit-breaker, and feeder bay.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1293


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.5 Switching Sequences

[dwbspunt-120913-01.vsd, 1, en_US]

Figure 8-97 Example of a Substation

The switching sequence C4 Off (Figure 8-98) should switch off feeder bay C4. The circuit breaker is opened;
followed by opening of one of the 2 busbar disconnectors.

[Scssc4as-110913-01, 1, en_US]

Figure 8-98 CFC Switching Sequence C4 Off

1294 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.5 Switching Sequences

Command Execution
As described in section Starting and Canceling a Switching Sequence, Page 1291, the display page or the
Control menu can be used to start the switching sequence. The Start Trigger signal for indication
Execution is used to recognize the start and initiates the switching sequence by pickup of TRIG in the DPC-
DEF building block of circuit breaker QA1. Building blocks DPC-DEF and DPC-EXE are always used in pairs. The
DEF building block controls the type and nature of the command

• VAL = Switching direction (0 = Off, 1 = On)

• SELECT = Select switching device (2 = Select with a value suitable for the preset control model SBO w.
enh. security)

• OPERATE = Switch switching device (1 = Switching device is switched on or off)


Using the connected DPC-EXE building block, the command checks can be deactivated (REL_...). In the appli-
cation example, all inputs are set to 0 and therefore, all checks are activated.
After the open command of circuit breaker QA1 is acknowledged via the auxiliary contacts, the OK output of
the CFC block DPC_EXE becomes active and triggers the next switching object. With the input PT the signal for
the OK output is time-delayed (in the example by 10 ms) and creates a dead time between individual
switching commands and the switching sequence. This dead time is important for the updating of the inter-
locking conditions.
If QB1 is closed, QB1 will be opened. If QB2 is closed, QB2 will be opened. In order to implement this logic, the
OK output signal of QA1 is linked with the respective positions of circuit breakers QB1 and QB2 via the logical
AND function. This signal serves as a trigger for the trip command of QB1 or QB2.
Because in this example the time-out monitoring is activated, the feedback about the successful or unsuc-
cessful execution of the switching sequence must be parameterized. The Switching sequence function block
provides the inputs >Successful and >Failed. In order to acknowledge the entire switching sequence
positively, the OR operation of the OK outputs for the disconnectors QB1 and QB2 is sufficient. The feedback
of all failed executions takes place via the OR operation of all ERR outputs of the switching devices. The
benefit of such assessment is the fact that, in case of a failure, waiting for the time-out is not necessary, but
the active switching sequence can be ended immediately.
In this example, the use of the EN_I input of building block DPC-DEF fulfills 2 tasks:

• Cancelation of the entire switching sequence

• Resetting of the outputs OK and ERR on building block DPC-EXE


By linking all EN_I inputs and EN_O outputs of building blocks DPC-DEF and DPC-EXE, the execution of the
switching sequence can be controlled centrally since the value is transmitted between the building blocks.
Only if input EN_I on the DPC-EXE is set to 1, a switching command is issued. If the input drops back to 0 while
a command is being processed, this command will be canceled. With this behavior, cancelation of an entire
switching sequence can be achieved. As recognition of a cancelation, the canceled signal of the indication
Execution is used in the CFC chart and connected with the input EN_I of the first switching device, in this
example, with the DPC-DEF building block of circuit breaker QA1.
Since the OK and ERR outputs of the DPC-EXE building block maintain their value until execution of the next
command, it is necessary to reset the continuous output after each execution of the switching sequence for
correct execution of the entire CFC switching sequence multiple times. In this case, the use of the EN_I input
is also helpful. In the input drops back to 0, the OK and ERR outputs are also reset to 0. The triggers for ending
the switching sequence are the events failed and successful. For this reason, in the above example, the
signals failed and successful of the indication Execution were connected with EN_I of the DPC-DEF
building block.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1295


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.5 Switching Sequences

8.5.4 Settings

Addr. Parameter C Setting Options Default Setting


Swi. seq. #
_:101 Swi. seq. #:Check • no yes
switching authority
• yes
• advanced
_:102 Swi. seq. #:Check double • no yes
activat. blk.
• yes
_:103 Swi. seq. #:Time-out • 0 true
monitoring
• 1
_:104 Swi. seq. #:Monitoring 0.02 s to 3600.00 s 30.00 s
time
_:105 Swi. seq. #:Control • direct w. normal secur. SBO w. normal
model secur.
• SBO w. normal secur.
_:106 Swi. seq. #:SBO time-out 0.01 s to 1800.00 s 30.00 s
Switching authority
_:151 Swi. seq. #:Swi.dev. • 0 false
related sw.auth.
• 1
_:152 Swi. seq. #:Specific sw. • 0 true
authorities
• 1
_:115 Swi. seq. #:Specific • station station/remote
sw.auth. valid for
• station/remote
• remote
_:153 Swi. seq. #:Num. of 2 to 5 2
specific sw.auth.
_:154 Swi. seq. #:Multiple • 0 false
specific sw.auth.
• 1

8.5.5 Information List

No. Information Data Class Type


(Type)
Swi. seq. #
_:501 Swi. seq. #:>Enable start SPS I
_:502 Swi. seq. #:>Enable start (fixed) SPS I
_:503 Swi. seq. #:>Start SPS I
_:504 Swi. seq. #:>Cancel SPS I
_:505 Swi. seq. #:>Successful SPS I
_:506 Swi. seq. #:>Failed SPS I
_:53 Swi. seq. #:Health ENS O
_:302 Swi. seq. #:Execution ENS O
_:304 Swi. seq. #:Start SPC C
_:305 Swi. seq. #:Cancel SPC C

1296 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.6 User-Defined Function Block [Control]

8.6 User-Defined Function Block [Control]

8.6.1 Overview of Functions

The User-defined function block [control] allows the switching-authority check of a control command, the
check of whether the position has been reached, a double-activation blocking, and the definition of inter-
locking conditions for user-defined controllables.

8.6.2 Function Description

The User-defined function block [control] is located in the folder User-defined functions in the DIGSI 5
Library.
You can instantiate the user-defined function blocks on the top level (in parallel to other function groups) as
well as within function groups and functions.
The task of the function block is to check the switching authority and the interlocking conditions for the user-
defined control commands instantiated within it. For these control commands, the function block checks
whether the required switch position is equal to the current switch position (actual/set point comparison). If
you activate the double-activation blocking, commands from switching objects and user-defined control
signals will be rejected as long as a command is still being performed for one of the other switching objects
for which double-activation blocking has also been set.
With the binary release signals, you can determine a switchgear interlocking protection for all the user-defined
control signals instantiated in the function block. Unlike the switching devices (circuit breaker, disconnector),
there is only one release input here, since there is only one switching direction for the signal types INC and
APC. The signal types DPC, SPC, and BSC have 2 switching directions, but still only one release input. This
release input can be operated based on the result of a logic created in the CFC, or can be directly connected to
a binary input or a variable. If the input >Enable is activated, the switching command can be performed. If it
is not activated, the switching command is rejected, with the reason Interlocking violation.
This applies in a similar way to the input >Enable (fixed), although with this input, the interlocking
cannot be revoked by key switch S1 or an unlocked switching authority.
The following table shows the reaction of the function to the assignment of its inputs.
Input >Enable Input >Enable (fixed) Effect on control command
1 0 Rejected
0 1 Successful if device mode = unlocked
Rejected if device mode = locked
1 1 Successful
0 0 Rejected

NOTE

i The default setting for the state of the inputs is 1, that is, the switching commands are not locked.

You can instantiate every user-defined signal (for example, SPS, DPC, INC) in the function block and route the
corresponding indications (see following figure).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1297


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.6 User-Defined Function Block [Control]

[scuser01, 1, en_US]

Figure 8-99 Information Routing with Inserted User-Defined Function Block [Control]: Process Indications
and Some Single-Point Indications

8.6.3 Application and Setting Notes

The function block contains the parameters (_:104) Check switching authority, (_:105) Check
if pos. is reached, (_:106) Check double activat. blk., and (_:150) Check swi.auth.
for Mode. The parameter settings Check switching authority and Check if pos. is reached
affect all controllables instantiated in the function block. Other signal types are not affected by these parame-
ters and objects.
On the other hand, the parameter setting Check swi.auth. for Mode affects the controllable Mode
(controllable) of the function block.

1298 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.6 User-Defined Function Block [Control]

[scuser02, 1, en_US]

Figure 8-100 Parameterization Options of the User-Defined Function Block [Control]

Parameter: Check switching authority

• Default setting (_:104) Check switching authority = yes


With the Check switching authority parameter, you determine whether the command source of
switching commands must be checked (see chapter 8.3.1 Command Checks and Switchgear Interlocking
Protection).
Parameter: Check if pos. is reached

• Default setting (_:105) Check if pos. is reached = yes


With the Check if pos. is reached parameter, you check at a switching command whether the
switching direction equals the current position.
Parameter: Check double activat. blk.

• Default setting (_:106) Check double activat. blk. = no


With the Check double activat. blk. parameter, you check whether commands from switching
objects and user-defined control signals should be rejected, as long as a command is still being executed for
one of the other objects.
Parameter: Check swi.auth. for Mode

• Default setting (_:150) Check swi.auth. for Mode = no


With the Check swi.auth. for Mode parameter, you specify whether the switching authority for the
command source must be checked when switching the controllable Mode (controllable) to the mode
On, Off, or Test. If you set the parameter Check swi.auth. for Mode to yes, the switching command
is only executed with the appropriate switching authority (see chapter 8.3.1 Command Checks and Switch-
gear Interlocking Protection).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1299


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.6 User-Defined Function Block [Control]

8.6.4 Settings

Addr. Parameter C Setting Options Default Setting


U-def.FB ctl.#
_:104 U-def.FB ctl.#:Check • no yes
switching authority
• yes
• advanced
_:105 U-def.FB ctl.#:Check if • no yes
pos. is reached
• yes
_:106 U-def.FB ctl.#:Check • no no
double activat. blk.
• yes
Switching authority
_:150 U-def.FB ctl.#:Check • no no
swi.auth. for Mode
• yes
_:151 U-def.FB ctl.#:Swi.dev. • 0 false
related sw.auth.
• 1
_:152 U-def.FB ctl.#:Specific • 0 true
sw. authorities
• 1
_:115 U-def.FB ctl.#:Specific • station station/remote
sw.auth. valid for
• station/remote
• remote
_:153 U-def.FB ctl.#:Num. of 2 to 5 2
specific sw.auth.
_:155 U-def.FB ctl.#:Ident. Freely editable text
sw.auth. 1
_:156 U-def.FB ctl.#:Ident. Freely editable text
sw.auth. 2
_:157 U-def.FB ctl.#:Ident. Freely editable text
sw.auth. 3
_:158 U-def.FB ctl.#:Ident. Freely editable text
sw.auth. 4
_:159 U-def.FB ctl.#:Ident. Freely editable text
sw.auth. 5
_:154 U-def.FB ctl.#:Multiple • 0 false
specific sw.auth.
• 1

8.6.5 Information List

No. Information Data Class Type


(Type)
U-def.FB ctl.#
_:501 U-def.FB ctl.#:>Enable SPS I
_:502 U-def.FB ctl.#:>Enable (fixed) SPS I
_:503 U-def.FB ctl.#:>Sw. authority local SPS I
_:504 U-def.FB ctl.#:>Sw. authority remote SPS I
_:505 U-def.FB ctl.#:>Sw. mode interlocked SPS I
_:506 U-def.FB ctl.#:>Sw. mode non-interl. SPS I
_:51 U-def.FB ctl.#:Mode (controllable) ENC C

1300 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.6 User-Defined Function Block [Control]

No. Information Data Class Type


(Type)
_:52 U-def.FB ctl.#:Behavior ENS O
_:53 U-def.FB ctl.#:Health ENS O
_:302 U-def.FB ctl.#:Switching auth. station SPC C
_:308 U-def.FB ctl.#:Enable sw. auth. 1 SPC C
_:309 U-def.FB ctl.#:Enable sw. auth. 2 SPC C
_:310 U-def.FB ctl.#:Enable sw. auth. 3 SPC C
_:311 U-def.FB ctl.#:Enable sw. auth. 4 SPC C
_:312 U-def.FB ctl.#:Enable sw. auth. 5 SPC C
_:313 U-def.FB ctl.#:Switching authority ENS O
_:314 U-def.FB ctl.#:Switching mode ENS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1301


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.7 CFC-Chart Settings

8.7 CFC-Chart Settings

8.7.1 Overview of Functions

If you want to process a parameter in a CFC chart and this parameter is to be changeable during runtime using
DIGSI or HMI, you can use the function blocks CFC chart of Boolean parameters, the CFC chart of integer
parameters and the CFC chart of floating-point parameters. Instantiate the appropriate function block
depending on the parameter value needed (logical, integer, or floating point). In this way, the current value of
the parameter can then be used in the CFC chart at runtime.

8.7.2 Function Description

You can find the CFC-chart parameters Chrt sett.Bool , Chart setting Int , and Chrt sett.real
in the DIGSI library in the User-defined functions folder. Drag and drop the desired function block into a func-
tion group or a function. Set the appropriate parameter value of the function block in DIGSI using the param-
eter editor or via HMI under the Settings menu item. You can then use the parameter as an input signal in CFC
charts.

NOTE

i The user-defined function groups and the user-defined functions can be used to group the CFC-chart
parameters. You can rename for the function block and change the parameter value in the DIGSI Informa-
tion routing matrix to suit your specific application.

[sccfcparam, 1, en_US]

Figure 8-101 CFC-Chart Parameters within Information Routing

8.7.3 Application and Setting Notes

Parameter: Chrt sett.Bool

• Default setting Chrt sett.Bool = False

1302 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.7 CFC-Chart Settings

You can use the parameter Chrt sett.Bool in a CFC chart as an input signal with a Boolean value. This
input value can then be changed during the runtime of the CFC chart.

Parameter: Chart setting Int

• Default setting Chart setting Int = 10


You can use the parameter Chart setting Int in a CFC chart as an input signal with an integer value.
This input value can then be changed during the runtime of the CFC chart.

Parameter: Chrt sett.real

• Default setting Chrt sett.real = 100.000


You can use the parameter Chrt sett.real in a CFC chart as an input signal with a floating-point number.
This input value can then be changed during the runtime of the CFC chart.

8.7.4 Settings

Addr. Parameter C Setting Options Default Setting


Chrt sett.Bool
_:105 Chrt sett.Bool:Value • 0 false
• 1

Addr. Parameter C Setting Options Default Setting


Chart setting Int
_:105 Chart setting Int:Value -2147483648 to 2147483647 10

Addr. Parameter C Setting Options Default Setting


Chrt sett.real
_:105 Chrt sett.real:Value -10000000000.000 % to 100.000 %
10000000000.000 %

8.7.5 Information List

No. Information Data Class Type


(Type)
Chrt sett.Bool
_:305 Chrt sett.Bool:Setting value SPS O

No. Information Data Class Type


(Type)
Chart setting Int
_:305 Chart setting Int:Setting value INS O

No. Information Data Class Type


(Type)
Chrt sett.real
_:305 Chrt sett.real:Setting value MV O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1303


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

8.8 Transformer Tap Changers

8.8.1 Function Description

With the device control function, you can change a transformer tap by moving it higher or lower and monitor
the proper execution of the adjusting commands.
The function has built-in comprehensive options for measuring the tap changer position as well as supervision
and monitoring functions. The supervision and monitoring functions are used to check the voltage and supply
information about the tap position for adaptive matching of the transformer differential protection
The following options are provided for control:

• Direct user commands via the device keypad or routed binary inputs

• User-defined conditions via the CFC


If the tap changer reaches the end positions, the control function issues the (_:301) End higher
pos.reached or (_:302) End lower pos.reached indication.
The transformer tap controller is controlled by the function group Tap changer, which you can select from the
DIGSI library (group Switching devices).

[sc_tssdig, 1, en_US]

Figure 8-102 Tap Changer Functionality in the DIGSI Information Matrix

The central element is the Controllable Position of type BSC (Binary Controlled Step Position Information,
based on IEC 61850). You connect this Controllable in the matrix to the desired number of binary inputs that
indicate the current tap position.
You can find more information in chapter 8.8.2 Application and Setting Notes.
The Position Controllable also contains parameters. If you wish to change the settings, you must select the
Controllable in the DIGSI information matrix and change the settings by way of the Properties dialog. The taps
are controlled via the commands Higher command and Lower command, each of which must be connected
to one binary output.

1304 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

Example
The following 2 figures show a CFC chart as an example for transformer tap control with the routing of the
function keys for stepping up or stepping down.

[schilocd-280316-01, 2, en_US]

Figure 8-103 Routing of the Function Keys and CFC Signals

To use the function keys, you create 2 user-defined single-point indications (SPS). These are used for the func-
tion keys (for example, <F1>, Higher function key and <F2>, Lower function key) and as the input signals for
the appropriate CFC blocks. In addition, you must use the controllable Cmd. with feedback for the CFC
chart and set the control model to direct w. enh. security.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1305


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

You can select the control direction using the following values at the Val input of the BSC_DEF building block:

• 1 means step up

• 0 means step down

[scbivctv-280715-01, 3, en_US]

Figure 8-104 CFC Chart

Pressing the function keys to step up or down incrementally can be displayed using this simple CFC chart.

Motor Supervision Time


The runtime of the motor-drive mechanism can be monitored from the device. This function is used to identify
failures of the motor-drive mechanism during the switching procedure and to trip actions if necessary. To use
the Motor supervision time, you must route the motor sliding contact (most significant binary input)
and set the proper motor runtime.
The motor sliding contact is active until the tap changer has reached the new position. This time is compared
to the Motor supervision time. If the new tap position is not reached within the motor runtime, the
Motor sup. time expired indication is set. The Trigger motor prot. sw. indication with which
the motor can be switched off is output for a duration of 1.5 s.

Adjusting-Command Supervision
Adjusting-command supervision is used for checking the proper operation of the tap-changer mechanism. The
Tap changer function calculates the next logical tap position as a result of the higher/lower tap command.
The time of position detection is determined as a function of the availability of the motor sliding contact. After
resetting the active motor sliding contact, the Tap changer function reads the new tap position value. If the
value for the calculated tap position could not be received within the parameterized time Motor supervi-
sion time, the error message Position failure is output.
The following position errors of the tap changer are taken into consideration during this:

• Invalid tap position: The tap position is outside the predefined range of minimum value and maximum
value

• Adjusting command in the wrong direction (for example, if a higher tap was commanded and the tap
changer responds with a lower position and vice versa)

• No operation of the tap changer (for example, if the tap-changer motor is defective or the position indi-
cation is not functioning)

• Illogical tap-change operation (for example, if no logical tap position following the previous position is
indicated)

1306 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

The value of 0 during an unexpected interruption of the auxiliary voltage represents a special case. An invalid
tap-changer position without a corresponding adjusting command is signaled in the Position controllable
only as an invalid tap position.

[lotcmoue-090713-01.tif, 3, en_US]

Figure 8-105 Position and Motor Supervision Logic

The user-defined signals Higher command and Lower command are provided via a CFC chart (see
Figure 8-104).

Supervision Behavior
Depending on the setting of the Supervision behavior parameter, the function reaches a health state of
Alarm or Warning. You can set the parameter Supervision behavior to off, alarm block, or
warning.
In the alarm block mode, the function is set to the health state Alarm. All tap-changer commands are
blocked.
In the warning mode, the function is set to the health state Warning. Executing tap-changer commands is
still possible.
You can manually reset the health state of alarm block or warning using the controllable Reset errors
(Main menu → Device functions → Reset functions → Tap changer). As an alternative to this, you can also
switch off the supervision function and then switch it on again.

Operating Counter
The device counts the number of successfully completed adjusting commands with the Op.ct. switching
cycle counting value. The counting and memory levels are protected against an auxiliary-voltage failure. The
switching cycle counting value can be set to 0 or to any other starting value.
You can access the statistical values via the operation panel on the device (measured values/statistics), via
DIGSI, or using various communication protocols.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1307


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

8.8.2 Application and Setting Notes

Parameters of the Tap Changer Function Group

[scstuslt-100713-01.tif, 2, en_US]

Figure 8-106 Parameters of the Tap Changer

NOTE

i If run positions, this means internal tap changer positions without voltage changes, are available, the
following must be observed:
If these tap changer positions contain a suffix a and c or + and -, and additional switching pulses are not
required, adjust the parameter for the feedback and motor supervision time to the actual motor runtime
when passing through a run position. Siemens recommends parameterization with capturing of the motor
sliding contact.

Parameter: Check switching authority

• Default setting (_:104) Check switching authority = yes


With the Check switching authority parameter, you specify whether the switching authority (on site,
remote) is checked in the case of an adjusting command (see also chapter 8.3.1 Command Checks and
Switchgear Interlocking Protection).

Parameter: Control model

• Default setting (_:108) Control model = SBO w. enh. security


Use the Control model parameter to specify the control model according to IEC 61850-7-2. The following
selection options are available:

• direct w. normal secur.

• SBO w. normal secur.

• direct w. enh. security

• SBO w. enh. security

• status only

1308 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

Parameter: SBO time-out

• Default setting (_:109) SBO time-out = 30 s


With this setting, you specify the time for detecting the time-out of the SBO command. The range of values
extends from 0.01 s to 1800.00 s. This is the time that can elapse between command acceptance and
command execution (command model as per IEC 61850-7-2).

Parameter: Feedback monitoring time

• Default setting (_:110) Feedback monitoring time = 10 s


Reaching a new tap position after the switching command is monitored. If a new tap position is not reached,
you specify with this setting the time when the command is canceled. The range of values extends from 0.01 s
to 1800.00 s.

Parameter: Maximum output time

• Default setting (_:111) Maximum output time = 1.50 s


This parameter specifies the maximum output time. The range of values extends from 0.01 s to 1800.00 s. For
activating motors to change the tap position, a time of 1.50 s is practical.

Parameter: Supervision behavior

• Default setting (_:112) Supervision behavior = alarm block


You can select whether the supervision is switched off (off) or if only a warning is indicated (warning). With
the alarm block setting, an alarm indication is generated and the function is blocked.

Parameter: Motor supervision time

• Default setting (_:113) Motor supervision time = 10 s


After the motor supervision time has elapsed, the indication Motor sup. time expired is displayed. You
can find additional information in section Motor Supervision Time, Page 1306. The range of values extends
from 5 s to 100 s.

Parameter: Highest tap changer pos.

• Default setting (_:116) Highest tap changer pos. = Lowest voltage tap
With the Highest tap changer pos. parameter, you specify whether the lowest or highest voltage is
present at the highest tap changer position.

Additional Settings (Properties Dialog Position)


Additional settings are assigned to the controllable Position. To display and adjust the settings, select
Position in the DIGSI information matrix and select the Properties dialog. To do this, click the Properties
tab.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1309


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

[scdeegts-170216-01, 1, en_US]

Figure 8-107 Properties Dialog

Parameter: Minimum value

• Default setting Minimum value = 1

Parameter: Maximum value

• Default setting Maximum value = 15


The parameters Minimum value and Maximum value are initially calculated by DIGSI 5 on the basis of the
tap coding, the Number of tap positions and the Tap-display offset. They represent the allowed
control area of the position value. Positions outside this area are defined as invalid. This control area can be
further restricted within the initially set physical range (see Number of tap positions and Tap-
display offset).

Parameter: Tap-display offset

• Default setting Tap-display offset = 0


If you want to move the height of the displayed value in a positive or the negative direction with respect to
the height of the actual value, enter the value for this in the Tap-display offset field.

Parameter: Number of bits f. tap code

• Default setting Number of bits f. tap code = 4


With the Number of bits f. tap code parameter, you set the number of bits you need for encoding the
transformer taps. The number is dependent on the selected Encoding and on the Moving contact. For
example, you need 3 bits for 7 binary-encoded transformer taps. The range of values extends from 2 to 32.

1310 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

Parameter: Number of tap positions

• Default setting Number of tap positions = 15


With the Number of tap positions parameter, you set the number of transformer taps. The range of
values extends from 2 to 127. The output of the tap position is limited from -63 to +63. If the number of taps
is > 63, set the Tap-display offset parameter so that the output of the tap position is within the range of
-63 to +63.

Parameter: Tap-coding type

• Default setting Tap-coding type = binary


In the Tap-coding type list box, select the interpretation type of the indication pending at the binary input.
You can select from the following options:

• binary

• 1-of-n

• BCD

• table

• BCD signed

• gray
The tap changer position can also be routed via a GOOSE signal (BSC) or a 20-mA measuring transducer input.
You can find more information on this in the document Measuring the transformer tap changer using an
analog measuring transducer input in SIPROTEC 5 in the Download area under SIPROTEC 5 and DIGSI
5 downloads → SIPROTEC 5 General → Application Notes → Control.
A selection of tap-coding types is described in greater detail using examples in the following text.

Routing of the Binary Inputs (Tap-Coding Type binary)


The following table shows the routing of 3 binary inputs (BI 1 to BI 3) with 4 transformer tap positions desig-
nated 3 to 6. BI4 is the moving contact. The encoding is in binary.

Table 8-25 Routing of the Binary Inputs (Tap-Coding Type binary)

Example
BI1 BI2 BI3 BI4 BI5 BI6
Tap changer X X X X – –
Meaning Bit 1 Bit 2 Bit 3 Moving – –
contact
Tap = 1 1 0 0 – –

With 3 binary inputs, a maximum of 23 -1 = 7 tap positions can be mapped in binary code. If all routed binary
inputs indicate 0, this is interpreted as a connection error and is reported by Position --- or -64 with quality
invalid. The representation of transformer taps should start with the metered value 3. You must configure the
information properties as follows for the example:
Tap-coding type: binary
Number of tap positions: 7
Number of bits f. tap code: 4
Tap-display offset: 2
Moving contact (highest binary input): Yes

The 3 binary inputs must be numbered sequentially, for example, BI 1, BI 2, BI 3, and BI 4 for the moving
contact.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1311


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

Routing of the Binary Inputs (Tap-Coding Type BCD)


The following table shows the routing of 6 binary inputs (BI 1 to BI 6) with 39 transformer tap positions desig-
nated 1 to 39. The encoding is in BCD. BI 7 is the moving contact.

Table 8-26 Routing of the Binary Inputs (Tap-Coding Type BCD)

Example
BI1 BI2 BI3 BI4 BI5 BI6 BI7
Tap changer X X X X X X X
Meaning BCD 1 BCD 2 BCD 4 BCD 8 BCD 10 BCD 20 Moving
contact
Tap = 21 1 0 0 0 0 1 –

With 6 binary inputs, a maximum of 39 tap positions can be mapped with the tap-coding type of BCD. This
yields the number of tap positions from 1 to 39. If all routed binary inputs indicate 0, this is detected as tap 0.
The 7 binary inputs must be numbered sequentially, for example, BI 1, BI 2, BI 3, BI 4, BI 5, BI 6, and BI 7 for
the moving contact.
Tap-coding type: BCD
Number of tap positions: 39
Number of bits f. tap code: 7
Tap-display offset: 0
Moving contact (highest binary input): Yes

Individual Tap-Coding Type (table)


With the table parameter setting, you can specify an individual Tap-coding type.
In the Representation of encoding section, select the number system in which your code table entries
will take place, alternatively:

• Binary (2 characters)

• Octal (8 characters)

• Decimal (10 characters)

• Hexadecimal (16 characters)


The selected option is valid for all inputs in the Encoding column.
If you change the number system and there are already entries in this column, these will be converted to the
new number system. The selection area becomes visible as soon as you have selected the setting table in the
Tap-coding type list box.

1312 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

[sccotabi-111016-01, 1, en_US]

Figure 8-108 Code Table for the Tap-Coding Type table

NOTE

i If the binary inputs used for encoding are all inactive, this indicates an invalid tap position (regardless of
the display offset). For an invalid tap position, the display shows the position --- or -64 with quality invalid,
exception BCD signed, see Routing of the Binary Inputs (Tap-Coding Type BCD signed), Page 1313.

Enter the encoding for the tap in the Encoding column in the Code table. Enter the value according to the
number system previously selected. Select the desired number of taps and number of bits for tap coding. Taps
with the same encoding and taps with 0 coding are not permitted.

Routing of the Binary Inputs (Tap-Coding Type BCD signed)


The following table shows the routing of 3 binary inputs (BI 1 to BI -3) with 7 transformer tap positions desig-
nated 3 to 3. The encoding uses BCD signed.

Table 8-27 Routing of the Binary Inputs (Tap-Coding Type BCD signed)

Example
BI1 BI2 BI3 BI4 BI5 BI6
Tap changer X X X – – –
Meaning BCD 1 BCD 2 Sign – – –
Tap = 1 1 0 1 – – –

Using 3 binary inputs, a maximum of 7 tap positions can be mapped with the tap coding type of BCD signed.
This yields the number of tap positions from -3 to 3. If all routed binary inputs indicate 0, this is recognized as
tap 0. The 3 binary inputs must be numbered sequentially.
Tap-coding type: BCD signed
Number of tap positions: 7
Number of bits f. tap code: 3
Tap-display offset: 0
Moving contact (highest binary input): No

SIPROTEC 5, 7SJ82/7SJ85, Manual 1313


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

Routing the Tap Position to Binary Outputs


For the output of the adjusting commands, route the information step up and step down on one relay each,
see following figure.

[sc_trass7, 1, en_US]

Figure 8-109 Routing the Tap Setting Commands

Parameter: Moving contact (highest binary input)

• Default setting Moving contact (highest binary input) = no


If the tap position is only to be recognized as valid and implemented when the motor sliding contact signals
that it has reached the taps, then activate the Moving contact (highest binary input) option. If this
parameter is set, the new position is only labeled with an * when the moving contact drops out.

Parameter: Software filter time

• Default setting Software filter time = 1000 ms


With this parameter, you set the Software filter time for capturing the tap position. The range of
values extends from 0 ms to 100 000 ms. Within this time, brief changes on the binary inputs are suppressed.

Parameter: Retrigger filter

• Default setting Retrigger filter = Yes


With this parameter, you switch retriggering of the filtering time by a position change on or off.

Parameter: Indication timestamp before filtering

• Default setting Indication timestamp before filtering = no


With this parameter, you specify whether the hardware filtering time is accounted for in the time stamp of
position capture.

Parameter: Chatter blocking

• Default setting Chatter blocking = no


With this parameter, you switch Chatter blocking on or off.

1314 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.8 Transformer Tap Changers

8.8.3 Settings

Addr. Parameter C Setting Options Default Setting


Tap changer
_:104 Tap changer:Check • no yes
switching authority
• yes
_:108 Tap changer:Control model • status only SBO w. enh.
security
• direct w. normal secur.
• SBO w. normal secur.
• direct w. enh. security
• SBO w. enh. security
_:109 Tap changer:SBO time-out 0.01 s to 1800.00 s 30.00 s
_:110 Tap changer:Feedback 0.01 s to 1800.00 s 10.00 s
monitoring time
Tap changer
_:111 Tap changer:Maximum 0.02 s to 1800.00 s 1.50 s
output time
_:112 Tap changer:Supervision • off alarm block
behavior
• warning
• alarm block
_:113 Tap changer:Motor supervi- 5 s to 100 s 10 s
sion time

8.8.4 Information List

No. Information Data Class Type


(Type)
Tap changer
_:500 Tap changer:>Acquisition blocking SPS I
_:501 Tap changer:>Enable SPS I
_:53 Tap changer:Health ENS O
_:301 Tap changer:End higher pos.reached SPS O
_:302 Tap changer:End lower pos.reached SPS O
_:308 Tap changer:Position BSC C
_:305 Tap changer:Higher command SPS O
_:306 Tap changer:Lower command SPS O
_:307 Tap changer:Command active SPS O
_:309 Tap changer:Motor sup. time expired SPS O
_:310 Tap changer:Trigger motor prot. sw. SPS O
_:311 Tap changer:Position failure SPS O
_:312 Tap changer:Op.ct. INS O
_:319 Tap changer:Reset failure SPC C

SIPROTEC 5, 7SJ82/7SJ85, Manual 1315


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

8.9 Voltage Controller

8.9.1 Overview of Functions

The transformer voltage controller functionality (ANSI 90V) is used to control power transformers (two-
winding transformers, three-winding transformers, grid coupling transformers) and auto transformers using a
motor-operated tap changer. In addition, the voltage control can be used for two-winding transformers
connected in parallel.
The function provides automatic voltage control within a specified voltage range on the secondary side of the
transformers or, as an alternative, at a remote load point (Z compensation or R/X compensation) in the
network. In order to compensate for the voltage variations in the meshed system, use the LDC-Z procedure (Z
compensation). For voltage drops on the line, use the LDC-XandR procedure (R/X compensation).
The control principle is based on the fact that a higher or lower adjusting command to the tap changer, as a
function of the voltage change (ΔV) per tap, causes a voltage increase or decrease.
The voltage control operates on a tap-for-tap basis and compares the measured actual voltage (Vact) with the
specified target voltage (Vtarget). If the voltage difference is greater than the set bandwidth (B), a higher or
lower adjusting command is sent to the tap changer once the set time delay (T1) has elapsed. Specifying the
time delay (T1) depends on the set controller response (inverse or linear), so as to avoid unnecessary adjusting
commands during brief voltage deviations from the target value and for coordination with other automatic
voltage controllers in the system.
The voltage controller function also monitors the currents on the upper-voltage side and the low-voltage side
of the transformer to block the voltage controller during impermissible operating states (overcurrent/under-
current/undervoltage). The voltage controller function also has limiting values that, in special operating cases,
suppress higher adjusting commands in the case of overvoltage and lower adjusting commands in the case of
undervoltage.
You can also use the voltage controller function for parallel control of up to 8 two-winding transformers in
different groups. You can carry out parallel control based on the Master-Follower method or using circulating
reactive current minimization method.

8.9.2 Structure of the Function

The Two-winding transformer voltage controller , Three-winding transformer voltage controller, and
Grid coupling transformer voltage controller function groups consist of 5 function blocks. Depending on
the application, the function groups are preconfigured in the relevant application template by the manufac-
turer or can be copied into the corresponding device project during engineering.
The following figure shows, for example, the functional scope of the Two-winding transformer voltage
controller function group.

[dwvolctl-060913-01.vsd, 3, en_US]

Figure 8-110 Structure/Embedding of the Function Group

1316 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

The functions General (GAPC), Tap changer (YLTC), and Voltage controller (ATCC) are logical node points in
IEC 61850-8-1.
The tap changer (YLTC) is the interface between the voltage controller (ATCC) and the motor-operated tap
changer of the transformer (OLTC). This means that the voltage controller (ATCC) sends higher and lower
adjusting commands to the tap changer. This tap changer issues command pulses to the motor-operated tap
changer of the transformer (OLTC). The tap changer (YLTC) measures the tap positions and monitors the
action of the motor-operated tap changer (OLTC).
The Parallel control function is needed for the parallel operation of 2 to 8 transformers. The Parallel control
function can only be instantiated in the Voltage controller function group.
The function group has interfaces to the following measuring points:

• Two-winding transformer:
– Voltage, 3-phase
– Current, 3-phase (optional)

• Three-winding transformer:
– 2 x voltage, 3-phase
– 2 x current, 3-phase (optional)

• Grid coupling transformer:


– 2 x voltage, 3-phase
– 2 x current, 3-phase
Figure 8-111 shows these interfaces as a block structure.

[dwvocnti-060913-01.vsd, 3, en_US]

Figure 8-111 Structure of the Voltage Control Function Group

You can find the information and function measured values of the voltage controller in the DIGSI routing
matrix.

8.9.3 Function Description

8.9.3.1 General
If the load is increased in an electricity-supply system, the voltage is reduced and vice versa. The power trans-
formers are usually equipped with transformer tap changers (OLTC) so as to keep the power-system voltage at
a constant level.
As a result, the transformer ratio is changed in predefined steps. Changes to the transformer taps cause the
voltage to change.
The Voltage control function is intended to control transformers with motor-operated transformer tap
changers.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1317


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

This function is designed to control the following:

• For two-winding transformers (2W): the voltage on the secondary circuit of the power transformer and
parallel control of several transformers feeding the same busbar or a nodal point of a system

• For three-winding transformers (3W): the voltage of the secondary winding 1 or winding 2

• For grid coupling transformers (GC): voltage of winding 1 or winding 2, selectively depending on the
power direction
Control operation is based on a step-by-step principle. To move the tap changer one position higher or lower,
a single control pulse is issued to the motor-drive mechanism of the tap changer. The length of the control
pulse can be set over a large range so as to handle the different types of tap-changer drives. The control pulse
is issued if the measured voltage deviates from the set reference value by more than the preset voltage range
for more than a given time period.
The voltage can be controlled at the voltage measuring point or at the load point in the electrical power
system. In this case, the load-point voltage is calculated on the basis of the measured load current and the
known impedance between the voltage measuring point and the load point.
The following figures show possible configurations of the voltage controller for two-winding transformers
with and without current measurement.

[dwkonlst-060913.vsd, 1, en_US]

Figure 8-112 Voltage-Controller Constellation for Two-Winding Transformers with Current Measurement for
Load Compensation at the End of the Line

(1) Only if a transformer side is present

1318 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[dwkonlsK-060913.vsd, 1, en_US]

Figure 8-113 Voltage-Controller Constellation for Two-Winding Transformers without Current Measurement

Three-Winding Transformers
Three-winding transformers are special power transformers that have 2 separate windings on the secondary
circuit and typically supply 2 different busbars. The voltage levels on the secondary circuit of the power trans-
formers can either be the same or different. In addition to designs with 2 tap changers on the secondary
circuits, in most cases, three-winding transformers are equipped with only one tap changer or on-load tap
changer on the primary side. It is therefore necessary to feed both voltages of the secondary windings to the
voltage measuring inputs (V1, V2) and to specify one of them, depending on the busbar situation, to the
voltage controller as the control variable.
The voltages of side 1 and 2 of the three-winding transformer are simultaneously monitored. In the process,
the voltage to be controlled can be automatically selected via the load current of both sides or by using one
parameter. This parameter is the settings group switching via binary input, protocol, or function keys. The
uncontrolled voltage can be monitored in parallel to ensure that it remains within the defined voltage limits.
If a current measuring point is assigned to a function group, the voltage to be controlled can be automatically
selected dependent on the load.
For automatic on-load tap changing, the voltage of the transformer side into which the larger load current
flows is controlled. The respective uncontrolled voltage is monitored for undervoltage and overvoltage.
In contrast to overvoltage on the controlled side, for overvoltage on the uncontrolled side, the higher
adjusting command is blocked and no fast step down to a lower tap occurs. In case of undervoltage on the
uncontrolled side, the lower adjusting commands are blocked if this behavior is activated for undervoltage
supervision.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1319


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[dw_V-constell-3wind-with-imeas.vsd, 2, en_US]

Figure 8-114 Voltage-Controller Constellation for Three-Winding Transformers with Current Measurement
for Load Compensation at the End of the Line

(1) Only if a transformer side is available

1320 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[dw_V-constell-3wind-without-imeas-091014.vsd, 2, en_US]

Figure 8-115 Voltage-Controller Constellation for Three-Winding Transformers without Current Measure-
ment

Grid Coupling Transformers


Grid coupling transformers are special power transformers that connect 2 electrical power systems to one
another. The load-side voltage is controlled. The power flow can change during operation. That is why both
voltages and currents, winding 1 and winding 2, voltage measuring inputs (V1, V2) and current measuring
inputs (I1 and I2) must be fed. A voltage must be specified as a function of the load situation to the voltage
controller as the control variable.
The voltages of the windings 1 and 2 of the grid coupling transformers are simultaneously monitored. In the
process, you can select the voltage to be controlled using one parameter. This parameter can be changed
using the settings group switching via the binary input, protocol, or function keys.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1321


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[dw_V-constell-2wind-coupl-transf.vsd, 1, en_US]

Figure 8-116 Voltage-Controller Constellation for Grid Coupling Transformers

On-Load Tap Changer


On-load tap changers are used to set the desired tap of a stepped winding of the transformer while under
load. During switchover, the desired tap of the stepped winding is first selected by means of the tap selector.
Next, the on-load tap changer switches over from the current-carrying tap to the selected tap. During this
switchover, one tap of the stepped winding is briefly bridged by an ohmic resistor so that the load switchover
takes place without current interruption. Physically, the tap changer is installed in the transformer tank or in a
separate tank.

Tap Changer
The Tap changer function issues the adjusting commands to the on-load tap changer and receives the corre-
sponding feedback. The function of the tap changer inside the voltage controller corresponds to that of the
separate tap changer. The higher and lower adjusting commands are generated by the voltage controller. The
Check switching authority, Control model, SBO time-out, and Feedback monitoring time
parameters are set only in the voltage controller.
You can find more information in chapter 8.9.4.1 General.

Voltage Controller
The Voltage controller function controls the voltage within the bandwidth and within the set voltage limits.
Using the Mode parameter, you can turn the voltage controller on or off or set it for test mode.
With the Number of target voltage parameter, you can specify up to 4 target voltages. You can only
activate one of these target voltages at a time using function key, communication, or a binary input. Use the
Set point mode active parameter to specify a valid target voltage via a communication network.
If the voltage controller is switched off, adjusting commands cannot be given to the tap changer in automatic
operation or in manual operation. The set on-site or remote switching authority is independent of this.

1322 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

You can set the voltage controller operating mode using the Operating mode parameter or the Operating
mode command to automatic operation or manual operation. In automatic operation, the voltage is
controlled automatically in accordance with the set parameters.

Three-Winding Transformer Voltage Controller


For the two-winding transformer voltage controller, the measurands that are used to manage the feedback
control are permanently defined.
With the voltage controller for the three-winding transformer, these measurands can be specified using one
parameter (parameter Winding selection = Winding 1 or Winding 2) or they can be automatically
selected (Winding selection = WithMaxLoad).
The winding is automatically selected by evaluating the load current in the windings. If the load current in one
of the two windings is greater than the load current in the other winding by 5 % of the rated current for 10 s,
then the winding voltage is controlled using the larger load current.

Grid Coupling Transformer Voltage Controller


For the two-winding transformer voltage controller, the measurands that are used to manage the feedback
control are permanently defined.
With the grid coupling transformer voltage controller, these measurands can be selected using a parameter
(parameter Winding selection = Winding 1 or Winding 2).
You can change the winding selection during operation using the settings group switching.
You can monitor the power-flow direction. If the difference in the power of Winding 1 and Winding 2 is
greater than 10 % of the rated power on the control side, the indication Power-flow superv. appears and
the function switches to alarm status.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1323


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

8.9.3.2 Logic of the Function

[lovoltco-060913-01.vsd, 5, en_US]

Figure 8-117 Superordinate Logic of the Voltage Controller

1) Manual operation
2) Automatic operation
3) Controllable
4) Command
5) Position and motor supervision (Figure 8-105)

1324 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

In accordance with the IEC 61850 standard, DOI LTCBlk (Block automatic operation command), automatic
control can be blocked with a command.
The voltage controller measures the actual voltage (Vact) and compares it to the target voltage (Vtarget). If
the difference between the measured voltage (control deviation D) is greater than the set bandwidth (B), a
higher or lower adjusting command is sent to the tap changer once the set time delay (T1) has elapsed.
You can change the settings for control during operation with the settings group switching.
You can switchover the settings groups via the following alternatives:

• Via the on-site operation panel directly on the device

• Via an online DIGSI connection to the device

• Via binary inputs

• Via a communication connection to substation automation technology (IEC 60870-5-103, IEC 61850)
You can find more information on this in chapter 3.11.2 Settings-Group Switching.

8.9.3.3 Control Response

Control Deviation
The control deviation is calculated from the present actual voltage and the target voltage in relation to the
rated voltage.

[fokonisk-211013, 2, en_US]

D = Control deviation

Bandwidth
To minimize the number of switching operations by the tap changer, a permitted bandwidth is defined. If the
actual voltage is within the bandwidth, no adjusting control commands are issued to the tap changer. If the
actual voltage exceeds the defined bandwidth, an adjusting command is issued after the set time delay T1
delay. If the actual voltage returns to the voltage range of the bandwidth before T1 delay elapses, no
adjusting control command is issued.
If the actual voltage returns to the voltage range of the bandwidth within the time delay T1, the running time
delay T1 continues to count down, starting at the already elapsed time. If the actual voltage returns again to
the set bandwidth while the time is counting down, the time delay T1 is started at the remaining time. In this
way, the time delay is reduced in the event of frequent violations of the lower limit of the bandwidth.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1325


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[dwistspn-060913-01.vsd, 1, en_US]

Figure 8-118 Actual-Voltage Curve during Control Deviation

(a) Actual voltage outside the bandwidth


(b) Actual voltage before T1 elapses within the bandwidth - no switching
(c) Actual voltage outside the bandwidth, T1 begins to elapse
(d) Actual voltage outside the bandwidth after T1, switching procedure initiated
(e) Switching procedure concluded, actual voltage within the bandwidth

Linear, Inverse
With linear control response, the voltage controller reacts independently of the control deviation after the set
time T1 delay. If more than one tap-position change is required to bring the actual voltage back within the
bandwidth, the set time T2 delay takes effect.
With inverse control response, the time T1 delay depends on the magnitude of the control deviation. Small
deviations are tolerated for longer than larger ones. If the time delay is very small in accordance with the set
characteristic curve, the time T1 Inverse Min takes effect.
The set inverse characteristic curve is a function of the parameter T1 delay. The characteristic curves arising
for different settings of the time T1 delay are shown in chapter 8.9.4.1 General, margin title Parameter: T1
characteristic.

Zero Potential or Voltage Recovery


If the actual voltage is not within the defined bandwidth after a voltage recovery, it can be necessary for the
voltage controller to send the 1st adjusting command with the T2 time. For this purpose, the parameter
Regulate with T2 at start must be activated.

1326 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[dw_istgro-130215, 1, en_US]

Figure 8-119 Actual-Voltage Curve during Control with T2

(1) Actual voltage below the minimum voltage


(2) After switching on, the change to a higher tap occurs with time T2
(3) After the voltage recovery, the actual voltage is above the bandwidth
(4) Actual voltage outside the bandwidth. A fast step down mode is carried out with the time T2 until
the bandwidth is reached.

Larger Voltage Deviations

[dwistgro-060913-01.vsd, 2, en_US]

Figure 8-120 Actual-Voltage Curve During Larger Control Deviations

(1) Actual voltage outside the bandwidth


(2) The change to a higher tap occurs after T1 and then T2
(3) Actual voltage inside the bandwidth
(4) Actual voltage outside the limit for a fast step down. A fast step down mode is carried out until
the bandwidth is reached.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1327


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Fast Step Up Mode and Fast Step Down Mode


The fast step down mode and the fast step up mode allow a quick reaction to abnormal voltage situations.
Figure 8-120 shows such a situation at point (4). A fast step down mode occurs until the bandwidth has been
reached. The tap-position time between 2 consecutive lower adjusting commands results from the following 2
conditions:

• The completion of a tap change command after the new valid position was detected

• The measurement time for capturing the new actual voltage


The activity of the fast step down mode and the fast step up mode is displayed with the indications
(_:14011:308) Fast Step Down active and (_:14011:307) Fast Step Up active.

[losnlruk-090913-01.vsd, 2, en_US]

Figure 8-121 Logic of the Fast Step Down Mode

The fast step up mode works in a similar fashion.

8.9.3.4 Function Supervision

Automatic Operation
If the actual voltage exceeds or falls below the set bandwidth for longer than the set time delay, this situation
is shown by the indication (_:14011:309) Auto Monitor. If the actual voltage returns to the voltage
range, the indication is reset. You can switch off the function monitor with a time delay = 0 min.

[lofktueb-090913-01.vsd, 1, en_US]

Figure 8-122 Logic of the Function Supervision for Automatic Operation

8.9.3.5 Line Compensation


When using line compensation, the voltage drop of a phase that is connected to a transformer can be
included. In this case, 2 processes are available:

• Z compensation (LDC-Z)

• X and R compensation (LDC-XandR)

1328 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

NOTE

i Line compensation is only active if power is flowing in the direction of the line.

Z Compensation (LDC-Z)
Z compensation allows you to include the voltage drop of a line connected to the transformer. You can switch
the Z compensation on or off. If cos φ is roughly constant, you can use the Z compensation. Setting the
parameters requires the calculation of the voltage increase (Target voltage rising) taking into consid-
eration the load current (Max load current).
The parameter Target voltage rising represents the voltage drop across the line as a % under rated
load.
You can find more information and the calculation in chapter 8.9.4.1 General.
In case of active Z compensation, you must limit the maximum permitted voltage increase in relation to the
target voltage to avoid too high voltage at the transformer. To do this, set the parameter Max load
current. In addition, the parameter Vmax threshold is active. If the actual voltage exceeds this threshold
value, no more higher adjusting commands are issued.

[dwregchr-090913-01.vsd, 3, en_US]

Figure 8-123 Control Characteristic with Z Compensation

X and R Compensation (LDC-XandR)


During the application of the X and R compensation, you need the phase data. With this data, it is possible to
precisely compensate the voltage drop of the transmission lines. This method of line compensation also oper-
ates with negative active-power values. The following figure shows the effect of this compensation type.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1329


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[dw-line-drop-kompensation-250214-01.vsd, 2, en_US]

Figure 8-124 Phasor Diagram of the X and R Compensation

Vtransf Voltage on the transformer, voltage to be controlled


Vload Voltage of load point (target voltage, Vload = Vtransf - Vdrop)
Vdrop Voltage drop of the phase
IR, IX Voltage drop due to R and X of the line
Iload Load current
φ Rotor angle

You can also use X and R compensation for parallel control of transformers. If the X value is positive, the
voltage losses of the phase are compensated. If you are implementing parallel control with X and R compen-
sation, then the X value is negative and considers the voltage increase from the busbar to the transformer.
If the X and R compensation you must limit the maximum permitted voltage increase in relation to the target
voltage in order to avoid a voltage at the transformer that is too high. To do this, set the parameter Vmax
threshold. If the actual voltage exceeds this threshold value, no more higher adjusting commands are
issued.

8.9.3.6 Limiting Values


The limiting values cause no higher or lower adjusting commands to be given to the tap changer in the event
of an upper limit violation (Vmax threshold) or lower limit violation (Vmin threshold). In this way,
changing taps under abnormal voltage conditions and changing taps in the incorrect direction (for example, in
the event of wiring errors) is prevented.
The lower and upper tap changer limits are included in the limiting values. The parameters Lower tap-
position limit and Higher tap-position limit cause an additional restriction of the control range.

8.9.3.7 Blockings
The blockings prevent tap positions under abnormal network conditions. The following blocking functions are
available:

• Undervoltage

• Overcurrent, load current

• Undercurrent

• External blocking (binary input)

• Blocking command LTCBlock IEC 61850

• Blocking in the event of pickup of the transformer differential protection


Using the parameter Blocking behavior, you specify whether the blockings are to take effect only in auto-
matic operation (Auto) or in both automatic and manual operation (Auto-Manual).

1330 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Overcurrent blocking prevents tap-change operations in the event of an overload. For the current blockings,
the positive-sequence system of the load current and of the current on the upper-voltage side of transformers
is calculated.
By assigning the tap changer to the transformer side, you also arrange the current of the upper-voltage side.
Perform this assignment in the appropriate Transformer side function group. Here, you must use the tap
changer of the voltage controller.
Undervoltage blocking prevents tap-change operations in the event of a network collapse. The output signals
of the voltage controller are blocked and, depending on the operating mode, the indication Auto Blocking
and/or Manual Blocking is issued.

[loblokir-090913-01.vsd, 2, en_US]

Figure 8-125 Logic Blockings

1) If transformer differential protection is available


2) If a current measurement is available
3) If parallel proxys are available (max. 7)

If assignment of the tap changer for the transformer side is available, the current of the upper-voltage side is
also monitored and the differential-protection pickup automatically blocks the voltage controller.

Additional Blockings for the Three-Winding Transformer Voltage Controller


The blockings described in the above sections also apply to the controlled winding of the three-winding trans-
former. In addition, the blockings for undervoltage, minimum voltage, and overcurrent are used for the meas-
urands of the uncontrolled side.

Additional Blockings for the Grid Coupling Transformer Voltage Controller


For voltage control in grid coupling transformers, the voltages and currents of both windings are always used
for the blockings.

8.9.3.8 Parallel Operation

General
The parallel operation of 2 or more power transformers is intended to increase the electrical throughput or
short-circuit power at a power-system node. An additional reason for the parallel operation of transformers is
a reserve in case of a failure of a transformer.
If power peaks are to be expected in the power system, multiple transformers can be connected in parallel on
different busbars. This allows several feeders to be supplied simultaneously. You can control up to 8 trans-
formers in parallel in one group. The evaluation of the measured and status values takes place via the IEC
61850 GOOSE communication.
If for the transformers used the tap positions differ, thus creating a different transformation ratio, the no-load
voltages on the low-voltage side are different. A circulating reactive current flows via the transformers. Since

SIPROTEC 5, 7SJ82/7SJ85, Manual 1331


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

the transformer impedance consists mainly of leakage inductance, the current is inductive. These currents can
result in an overload of the transformer.
The parallel operation is intended for two-winding transformers. For this application case, additionally instan-
tiate the function Parallel operation. For each of the transformers connected in parallel you need an addi-
tional function block ParallelProxy. The 1st ParallelProxy is preinstantiated. For a configuration with
8 transformers working in parallel, you can instantiate a maximum of 7 ParallelProxy. The exchange of
the necessary information takes place via this proxy. 8 transformers can be configured to a maximum of
4 groups.
For the Parallel operation, the following 2 methods are available:

• Master-follower method

• Method of minimizing circulating reactive current

Table 8-28 Conditions for the Use of Both Methods

Requirements for the Transformers Requirement for the Voltage Method


Controller
Voltage change Rated power Short-circuit Current meas- Tap position
per tap voltage devia- urement
tion
Same Same or <10 % Optional Necessary Master/Follower
different
Different Same or Different Necessary Recommended Minimizing circu-
different lating reactive
current

As the preceding table shows, before selecting the method, you must check whether the corresponding
requirements are met. If you place transformers in parallel, whose short-circuit voltages differ by more than
10 % from each other, then Siemens recommends the Method of minimizing circulating reactive current.

Control of the Function


You can control the Parallel operation function using setting values or commands.
Parameters Values
With setting values Parallel mode Master, No mode, Follower, Circulat. react
current
Parallel mode changeable by setting, controllable
Force master changeable by setting, controllable
With command Parallel operation (ParOp) independent, parallel
Set master (ForceMast) off, on
Parallel groups (ParGrp) 1 to 4

The state of the control is reported as:

• No mode

• Independent

• Master

• Follower

• Circulating reactive current


If the Parallel operation is connected to further transformers via the communication, the state is checked for
correctness. If this is not the case, an inconsistency indication is output. The communication to the trans-
formers of a group is also monitored. If a fault is present, this is reported.

1332 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[sc_infogroup, 1, en_US]

Figure 8-126 Assigned Control Modules in Information Routing

Grouping
Each transformer in the parallel operation is assigned to a group. The group number can be set by a superordi-
nate control system or locally using a CFC logic. Once the group assignment is fixed, enter a value for the
initial start via the Properties tab of the command Parallel group in the information routing of DIGSI 5.

[sccfcgrouprel, 1, en_US]

Figure 8-127 CFC Chart for Group Assignment and Group Display

SIPROTEC 5, 7SJ82/7SJ85, Manual 1333


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[sc_para_grouping_vc, 1, en_US]

Figure 8-128 Properties Tab of the Parallel Group

During operation you can change this assignment by command, depending on the switching state of the
transformers.

Logic of the Function

[lo_proxy-logic-part_01, 1, en_US]

Figure 8-129 Grouping Logic

Parallel-Operation Detection via Group Inputs


You can control up to 8 transformers in parallel in one group or in 4 groups without detecting the system
topology. The devices in parallel operation use exclusively the information transmitted from devices of the

1334 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

same parallel-operation group via GOOSE. The groups of the transformers to be controlled in parallel are set
and changed using the control Parallel group. Thus, you assign the device to a parallel-operation group.
You can do this remote or locally on the device. If No mode is set for the parallel operation, no group
assignment takes place.

Parallel-Operation Detection via Topology


In addition, you have the option to detect the group assignment in parallel operation based on the position of
the disconnectors and circuit breakers. To report its status, every disconnector and circuit breaker is equipped
with a circuit-breaker auxiliary contact. These binary signals can be processed in a CFC chart and can be
dynamically adapted to the switching state of the system.
The signals Parallel group, Remote parallel mode, and Parallel mode active are transmitted
via the GOOSE communication between the other transformers in the group.

[lo_proxy-logic-part_03, 1, en_US]

Figure 8-130 Logic of the Blocking of Automatic Operation in the ParallelProxy

1) Only applies to the Master-follower method

The signals automatic operation, automatic-block. local, Health, and Remote parallel
mode are transmitted via the GOOSE communication between the other transformers in the group.
If the other voltage controllers in the group are set to the mode No mode or if the communication is
disturbed, the automatic operation is blocked. The blocking is reported. If a fault in the tap position is detected
via the difference in the tap positions of the transformers, the indication Error tap difference is issued.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1335


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[lo_proxy-logic-part_02, 1, en_US]

Figure 8-131 Logic of the Parallel-Operation State Detection

Controlling Locally/Remote
The parallel operation can be done with a parameter or via the control. With the parameter setting control-
lable, with a CFC block, you can also use a binary input and the status signal of a circuit breaker
(Figure 8-134).
First, for the control of the Parallel operation, set the parameters Parallel mode changeable and
Force master changeable.
You can select one of the 2 options:

• by setting

• controllable

[sc_para_oper_change, 1, en_US]

Figure 8-132 Selection for Parallel Operation

1336 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

If you set Parallel mode changeable to controllable, you can read and change the settings for the
parallel operation on the device under the following path:

• Main menu → Commands → Functionality → Voltage cont. 2w1 → Operation

[sc_para_hmi_oper, 1, en_US]

Figure 8-133 Menu Item for Parallel Operation on the Device Display

Figure 8-134 shows an example of a CFC chart for switching to parallel mode via the binary input of the circuit
breaker.

[sc_switchparop_cfc, 1, en_US]

Figure 8-134 CFC Chart

Master-Follower Method
As a prerequisite for the application of this method, the following values must be almost equal:

• Transformation ratios of the transformers used

• Number of the taps

• Voltage differential between the taps


The Master-Follower method regulates the Follower devices to the same tap position as the Master trans-
former. One voltage controller takes the lead (Master device), whilst the other voltage controllers (Follower
devices) follow its tap position (Master-Follower method). The Master device controls the busbar voltage auto-
matically according to the same principles of the available voltage-controller functionality for a two-winding
transformer. Compared with the Master-Slave method, this method has the advantage that losing a higher/
lower adjusting command (for example due to communication loss or auxiliary-voltage failure of the Follower
device) does not result in asynchrony of the transformers.
The Master-Follower method is suitable for transformers of the same design. If transformers of different
power are controlled with the Master-Follower method, you must make sure that the same tap positions

SIPROTEC 5, 7SJ82/7SJ85, Manual 1337


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

result in the same ratios. The relative short-circuit voltages of the transformers must not deviate significantly
from each other (max. 10 %).

Logic of the Master-Follower Method

[lo_parallel_voltage_contrl-master-follower, 1, en_US]

Figure 8-135 Logic of the Master-Follower Method

The Master-Follower method can be blocked using the automatic function in the systems control. In case of a
communication failure the function is also blocked.
The Master device controls the voltage of the transformer. The Follower device updates its tap position
according to the Master device. When doing so, the maximum tap-position difference between the trans-
formers is taken into account. If the tap-position difference is exceeded for a predefined time, an error is
reported (Error tap difference). If the supervision of a group detects that there is more than one
Master device, this is reported and the automatic operation is blocked.

1338 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Manual Operation Master-Follower


Changing the tap of the tap changer using the Master device leads to an adjustment of the taps by all Follower
devices within the group.
In case of a communication error, a tap change can be done by the Follower device by switching to manual
operation. In the Master device and all Follower devices the Automatic mode is blocked.

Method of Minimizing Circulating Reactive Current


If the ratios of the transformers connected in parallel are different (>10 %), Siemens recommends the method
of Minimizing circulating reactive current. The prerequisite for the method of Minimizing circulating reac-
tive current is a data exchange between the ATCC function blocks (one ATCC function for each transformer in
the parallel group). The data exchange for ATCC functions in different devices occurs via the GOOSE communi-
cation of the IEC 61850 protocol. All data of the devices in a group is exchanged cyclically via GOOSE; both
analog and binary signals are exchanged.
The following advantages can be achieved with the method of Minimizing circulating reactive current for
parallel voltage control:

• Setting the load voltage to a preset value

• Minimizing circulating reactive current for transformers operated in parallel

Calculation of the Circulating Reactive Current


To calculate the circulating reactive current, the measured values of the individual transformers must be trans-
mitted between the affected voltage controllers. The suitable reference variable for all transformers in a
parallel group is the bus voltage. With this, there is a common reference between all devices within one
parallel transformer group. The measured bus voltage is the reference value of the devices used.

[dw_CCM_01, 1, en_US]

Figure 8-136 Detection of the Circulating Reactive Current of a Parallel Group

The following formulas are used to calculate the circulating reactive current.
For each device, a direct-axis reactance relating to the control side of the transformer is calculated from the
following 3 parameters:

• Rated apparent power Srated of the transformer

• Rated voltage Vrated of the transformer

• Short-circuit voltage of the transformer VSC in percent

SIPROTEC 5, 7SJ82/7SJ85, Manual 1339


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

If the ohmic longitudinal resistance is neglected, the direct-axis reactance of the transformer Tk (k = 1,2,3 ... n
in the example) relating to the control side results in:

[fo_reakccm, 1, en_US]

This direct-axis resistance is transferred to the other voltage controllers as a measured value via GOOSE. This
value is displayed as a check. To determine the total load current, from each voltage controller the measured
current with magnitude and phase angle is transferred as a GOOSE CMV measured value.
The total load current results in:

[fo_summccm, 1, en_US]

The total inductive susceptance, the total susceptance of all transformers results in:

[fo_suszccm, 1, en_US]

The partial load current value of the individual transformers results from the ratio between susceptance and
total susceptance multiplied with the total load current. Only the inductive value, that is, the imaginary part
Im(IA) of the calculated total load current is used.

[fo_loadcurccm, 1, en_US]

The circulating reactive current at transformer k is the difference of the current measured at the transformer
and the calculated partial load current ILkImag. This is multiplied with -1 so that its positive no-load voltage
difference results in a positive circulating reactive current:

[fo_ccmtrafo, 1, en_US]

where:
ILkImag Calculated inductive part (imaginary part) of the partial load current of transformer k
IKBSk Circulating reactive current
IkImag Measured inductive part of the current at transformer k
ISC Measured current at the transformer
X Reactance of the transformer
k 1, 2, 3, ... 8 (number of the transformer)

Calculation of the Control Deviation


The control deviation DKBSk is calculated from the calculated circulating reactive current IKBSk:

[fo_regelabwdcc, 1, en_US]

1340 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

where:
Xk Reactance of the transformer
Bp Total susceptance (total susceptance value) of all parallel transformers (sum of the reciprocals
of the transformer reactance)
Bk Susceptance of the transformer (reciprocal of the reactance)
Vrated Rated voltage of the transformer

With the parameter Reactive I control factor, you can adjust the control deviation DKBSk so that the
circulating reactive current caused by a tap difference results in exceeding the control bandwidth. A Reac-
tive I control factor which is set too high can affect the control stability. In most cases, control
quality and control stability are available with the default setting of 1.
The sum of the control deviation resulting from voltage deviation DV and the control deviation DKBSk, caused by
the circulating reactive current, results in:
Dk = DKBSk + DV
and is compared with the set bandwidth. The following 2 diagrams explain the summations of the control
deviation at negative and positive voltage deviation. A possible control deviation initiated by the circulating
reactive current, is on transformer T1 in contrast to transformer T2. This results for both voltage controllers in a
different total deviation.

Negative voltage deviation -DV Positive voltage deviation DV


Changing to higher tap of T2 with DV + DKBS2 < -B Changing to lower tap of T1 with DV + DKBS1 > B

For the calculation of the voltage deviation, the voltages of all voltage controllers are transferred with GOOSE
as a measured value and an average value is calculated. The voltage can be monitored. If the data are not
plausible the voltage controller is blocked after a time delay which can be set.

Error Behavior
If the value of the circulating reactive current exceeds the set time delay Circul. current time delay
for a longer time than the threshold value Circul. current threshold, the indication Circul.
current blocking is issued and the voltage control blocked.
If the circulating reactive current value drops below the preset value, the signal is automatically reset. You can
achieve this by manually controlling the tap changer.

Blocking the Tap Changer in Case of a Fault


To activate the supervision functions in Follower mode when used with the transformer differential protec-
tion, you must set the parameter Blocking in the voltage controller function to Auto-Manual.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1341


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[scblockVC-240117-01, 1, en_US]

Figure 8-137 Parameter in the Voltage Controller

The blockings prevent tap positions under abnormal network conditions.

[loblokir-090913-01.vsd, 2, en_US]

Figure 8-138 Blocking Logic

1) If transformer differential protection is available


2) If a current measurement is available
3) If parallel proxies are available (max. 7)

In addition to present blockings a parallel operation of the number of proxies used is taken into account.

Maintenance of Transformers Connected in Parallel


If you want to take the device out of service and disconnect it from the power supply, you must first function-
ally log off the device. If you functionally log off the device, all data objects generated in the device (state and
measured values) receive the quality attribute OperatorBlocked = TRUE. This also applies to the output
from CFC charts.
If objects are transferred via a GOOSE message, the receiver devices can analyze the quality. After a switch off
of the transmitting device, the receiver devices detect that the transmitting device has been functionally
logged off and did not fail. Now the receiving objects can automatically be set to defined states.

Table 8-29 Decommissioning

Binary input

Controllable/device display

NOTE

i Decommissioning the device is only allowed if the Parallel mode of the voltage controller is set to No
mode. After the decommissioning you must commission the voltage controller again.

The decommissioning can be done with binary input indications or via the control.

1342 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Supervision of the Communication


A communication fault can occur in the following cases:

• The connection between 2 SIPROTEC 5 devices is interrupted.

• A hard- or software error is present in the device.

• The supply voltage of one or more devices is not present.


If the receipt of GOOSE messages is disturbed, a GOOSE time-out is signaled and all GOOSE messages arriving
are signaled as invalid. If No mode is set in one of the devices, then the parallel operation is not blocked. If
a communication error is present, the parallel mode in the Master and Follower device cannot be determined.
In this case the operating mode automatic operation in the Master and Follower device is blocked for security
reasons. Once the communication error has been cleared, the blocking is removed.
You can find more information about setting a GOOSE connection between the devices in the following
chapter.

8.9.3.9 Creating a GOOSE Later Binding for Parallel Control


To create the GOOSE later binding between the devices for parallel control, proceed as described in the
following example:

[dw_overview_sys-config_and_iec61850-goose, 1, en_US]

Figure 8-139 Example of a Parallel Control

Step 1

• Create the 1st device for parallel control in the DIGSI 5 project.

• Create the configurations and make the necessary settings for the IEC 61850 structure.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1343


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[sc_para_dev_set, 1, en_US]

Figure 8-140 IEC 61850 Structure Settings

For using Port J for the GOOSE communication:

• Activate the device functionality for Port J.

[sc_para_dev_func, 1, en_US]

Figure 8-141 Setting for the Integrated Ethernet Interface

• Instantiate the voltage controller function for the two-winding transformer and the Parallel control
function and the proxies that are necessary for parallel operation. One ParallelProxy is required for
each transformer to be controlled in parallel, that is, for 3 transformers in the project, it must be addition-
ally instantiate 2 ParallelProxies.

1344 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[sc_para_instanz, 1, en_US]

Figure 8-142 Selecting Parallel Control

• Make the necessary communication settings.

[sc_para_com_prot, 1, en_US]

Figure 8-143 Ethernet-interface settings

NOTE

i Note that you must assign a separate IP address for each device.

NOTE

i Note the hardware equipment of the device and the settings for the IEC 61850 communication (IEC 61850
Edition 2 required).

• Under Device Information in DIGSI, change IEC 61850 Edition 1 to Edition 2.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1345


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[sc_change_edition, 1, en_US]

Figure 8-144 Changing the IEC 61850 Edition

• Confirm the conversion to IEC 61850 Edition 2 with Yes.


Step 2

• Copy the 1st device as many times as are needed for the parallel transformers. The copied devices
contain the same settings.

• Adapt the IP addresses of the copied devices in the project tree under Hardware and protocols.

1346 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[sc_para_ether_portj, 1, en_US]

Figure 8-145 Adapting the IP Address

• Adapt the entries of the copied devices for the other transformers (device name and IEC 61850 name).

[sc_lbnametrafo, 1, en_US]

Figure 8-146 Adapting the Devices in DIGSI

• Assign a unique transformer ID for the other transformers in the copied devices.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1347


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

NOTE

i Note that in the Master-Follower method, you must configure one device as the Master device and the
additional devices as Follower devices.

[sc_par_trafo_id, 1, en_US]

Figure 8-147 Adapting the Parallel Transformer ID in DIGSI

Step 3

• Double-click Add new station.

• Double-click the first IEC 61850 station.

• Change the IEC 61850 station name for example in parallel operation.

• Change IEC 61850 Edition 1 to Edition 2.

[sc_par_stat_iec_edi, 1, en_US]

Figure 8-148 Selecting the IEC 61850 Edition

• Confirm the conversion to IEC 61850 Edition 2 with Yes.

• Use >> to assign the devices to the IEC 61850 station.

[sc_par_assign_syscon, 1, en_US]

Figure 8-149 Assigning the Devices

• Export the IEC 61850 station as an ICD file to the IEC 61850 System Configurator.

1348 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[sc_par_exp_syscon, 1, en_US]

Figure 8-150 Export to the IEC 61850 System Configurator

If the following dialog appears, confirm with OK and specify a storage location for the SCD file.

[sc_para_assinged, 1, en_US]

Figure 8-151 Export dialog

Step 4

• Import the ICD files into the system configurator. After the export to the system configurator, the config-
urator starts automatically.

• Create a single-line configuration in the system configurator.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1349


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[sc_para_single_line_konfig, 1, en_US]

Figure 8-152 Creating a Single-Line Configuration in the System Configurator

• Create a substation. Right-click Parallel operation and select Substation.

• Create the individual bays (bays 1-3) and instantiate for each a function and subfunction.

• Rename the function to VoltageControlParallel.

• Rename the subfunction to Proxies.

NOTE

i If you use the specified function and subfunction names, the GOOSE application will be created without
faults.

1350 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

• Connect the LN Trafo1\VCtrl1\ATCC1 of the device to the function and the other LN
Trafo2\Ctrl_90VParallelOperation\ProxyATCC1 to the proxies according to Figure 8-152.
Step 5

• Create a new GOOSE application and subsequently perform the GOOSE later binding using the applica-
tion template. With the GOOSE application template, all the links between the devices and the proxies
are automatically connected.

• Set all the settings for GOOSE communication between the Master and the Follower devices in the
IEC 61850 System Configurator.

• If you have done all the links and settings in the IEC 61850 System Configurator, save the project and
close the IEC 61850 System Configurator.

[sc_parasyscon_goose, 1, en_US]

Figure 8-153 Creating the GOOSE Application

Step 6

• Import the SCD file generated and stored in the IEC 61850 System Configurator back to DIGSI.

[sc_para_import, 1, en_US]

Figure 8-154 Import from the IEC 61850 System Configurator into DIGSI

• Load the created configuration to the devices.

8.9.3.10 Functional Measured Values


You can read the current status of the measured values for the two-winding transformer, the parallel control/
proxy, the three-winding and grid coupling transformer at any time. The following tables show you the avail-
able measured values.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1351


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Measured Values, Two-Winding Transformer

Measured Value Description Primary Secondary % Referenced to


V act. Current, measured positive- kV V Target voltage of the primary
sequence voltage (referenced system referenced to the rated
to phase-to-phase) voltage
ΔV act. Voltage difference between % % Voltage difference referenced
the target voltage and the to the rated voltage of the
actual voltage controlled winding
I load Current measured load current A A Load current referenced to the
(positive-sequence system) rated value of the function
V max Maximum positive-sequence kV V Maximum voltage of the
voltage ever measured (refer- winding referenced to the
enced to phase-to-phase) rated voltage of the winding
V min Minimum positive-sequence kV V Minimum voltage of the
voltage ever measured (refer- winding referenced to the
ence to phase-to-phase) rated voltage of the winding
V target Calculated target voltage with kV V Target voltage of the winding
consideration of Z compensa- referenced to the rated voltage
tion of the winding
PhAng Phase angle of the currently ° ° -
measured load current
I load Σ Sum of the currently measured A A Load current referenced to the
load currents. Active when line rated current of the function
compensation is activated.
I circul. Currently measured circulating A A Circulating reactive current
reactive current
Vact.m Currently measured control kV V Current voltage of the control
voltage referenced to the rated voltage
of the function
ΔVactV Voltage difference % % Voltage difference referenced
to the rated voltage of the
function
ΔVactC Voltage difference % % Voltage difference referenced
to the rated voltage of the
function

The function measured values V max and V min can be reset with the input indication >Reset min./max..
For the two-winding transformer, you can find the measured values under the following menu entries of the
device:

• Main menu → Measurements → Voltage control 2w → 90V V.contr.2w

• Main menu → Measurements → Voltage control 2w → Statistics → 90V V.contr.2w

Measured Values for Parallel Control, Proxy

Measured Value Description Primary Secondary % Referenced to


V act. Actual voltage of winding kV V Target voltage of the primary
system referenced to the rated
voltage of the function
1/X trf. Susceptance, internal value for 1/Ω
GOOSE transmission
I load Load current A - Load current referenced to the
rated current of the function

1352 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Measured Value Description Primary Secondary % Referenced to


PhAng Phase angle of the load current ° ° Phase angle of the load current
relative to the voltage with a 100 % = 180°
power factor of 1.0

For the parallel control, you can find the measured values under the following menu entries of the device:

• Main menu → Measurements → Voltage control 2w → Functional measured values → Parallel operation

Measured Values, Three-Winding Transformer

Measured Value Description Primary Secondary % Referenced to


Vact.w1 Actual voltage of winding 1 kV V Target voltage of the primary
system referenced to the rated
voltage
Vact.w2 Actual voltage of winding 2 kV V Target voltage of the primary
system referenced to the rated
voltage
ΔV act. Voltage difference between % % Voltage difference referenced
the target voltage and the to the rated voltage of the
actual voltage controlled winding
I load w1 Load current of winding 1 A A Load current referenced to the
rated current of winding 1
I load w2 Load current of winding 2 A A Load current referenced to the
rated current of winding 2
Vmax 1 Maximum voltage of winding 1 kV V Maximum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmax 2 Maximum voltage of winding 2 kV V Maximum voltage of winding 2
referenced to the rated voltage
of winding 2
Vmin 1 Minimum voltage of winding 1 kV V Minimum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmin 2 Minimum voltage of winding 2 kV V Minimum voltage of winding 2
referenced to the rated voltage
of winding 2
V tar.w1 Target voltage of winding 1 kV V Target voltage of winding 1
referenced to the rated voltage
of winding 1
V tar.w2 Target voltage of winding 2 kV V Target voltage of winding 2
referenced to the rated voltage
of winding 2

The function measured values Vmax 1, Vmax 2, Vmin 1, and Vmin 2 can be reset with the input indication
>Reset min./max..
For the three-winding transformer, you can find the measured values under the following menu entries of
the device:

• Main menu → Measurements → Voltage control 3w → 90V V.contr.3w

• Main menu → Measurements → Voltage control 3w → Statistics → 90V V.contr.3w

SIPROTEC 5, 7SJ82/7SJ85, Manual 1353


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Measured Values Grid Coupling Transformer

Measured Value Description Primary Secondary % Referenced to


Vact.w1 Actual voltage of winding 1 kV V Target voltage of the primary
system referenced to the rated
voltage
Vact.w2 Actual voltage of winding 2 kV V Target voltage of the primary
system referenced to the rated
voltage
ΔV act. Voltage difference between % % Voltage difference referenced
the target voltage and the to the rated voltage of the
actual voltage controlled winding
I load w1 Load current of winding 1 A A Load current referenced to the
rated current of winding 1
I load w2 Load current of winding 2 A A Load current referenced to the
rated current of winding 2
Vmax 1 Maximum voltage of winding 1 kV V Maximum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmax 2 Maximum voltage of winding 2 kV V Maximum voltage of winding 2
referenced to the rated voltage
of winding 2
Vmin 1 Minimum voltage of winding 1 kV V Minimum voltage of winding 1
referenced to rated voltage of
winding 1
Vmin 2 Minimum voltage of winding 2 kV V Minimum voltage of winding 2
referenced to rated voltage of
winding 2
V tar.w1 Target voltage of winding 1 kV V Target voltage of winding 1
referenced to the rated voltage
of winding 1
V tar.w2 Target voltage of winding 2 kV V Target voltage of winding 2
referenced to the rated voltage
of winding 2

The function measured values Vmax 1, Vmax 2, Vmin 1, and Vmin 2 can be reset with the input indication
>Reset min./max..
For the grid coupling transformer, you can find the measured values under the following menu entries of the
device:

• Main menu → Measurements → Voltage control gc → 90V V.contr.gc

• Main menu → Measurements → Voltage control gc → Statistics → 90V V.contr.gc

Fundamental-Component Values and Power Measured Values


The fundamental-component values and power measured values are always present in the Two-winding
transformer voltage controller, Three-winding transformer voltage controller, and Grid coupling trans-
former voltage controller function groups. Furthermore, you can find the fundamental-component values
and power measured values for winding 1 and winding 2 in the Three-winding transformer voltage
controller and Grid coupling transformer voltage controller function groups. These values cannot be
deleted.
The following tables show Table 8-30 and Table 8-31 the total scope for the case in which a 3-phase voltage
measuring point is also connected.

1354 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Table 8-30 Possible Fundamental Values for the Voltage Controller Function Group

Fundamental-Component Values Primar Secon- % Referenced to


y dary
IA, IB, IC Phase currents A A Rated operating current of the
primary system
IN Zero-sequence current A A Rated operating current of the
primary system
VA, VB,VC Phase-to-ground voltages kV V Rated operating voltage of the
primary system/√3
VAB, VBC, VCA Phase-to-phase voltages kV V Rated operating voltage of the
primary system
VN Measured neutral-point displace- kV V Rated operating voltage of the
ment voltage primary system/√3

Table 8-31 Possible Power Measured Values of the Voltage Controller Function Group

Power Measured Value Primar Secon- % Referenced to


y dary
Ptotal Active power MW W Active power of the primary system
(total power) √3 ⋅ Vrated ⋅ Irated
Qtotal Reactive power Mvar var Reactive power of the primary
(total power) system
√3 ⋅ Vrated ⋅ Irated
Stotal Apparent power MVA VA Apparent power of the primary
(total power) system
√3 ⋅ Vrated ⋅ Irated
Cos φ Active power factor (abs) (abs) 100 % corresponds to cos φ = 1

8.9.4 Application and Setting Notes

8.9.4.1 General
The following application and setting notes refer to a two-winding transformer. The additional parameters for
a three-winding transformer or for a grid coupling transformer are marked correspondingly.
Parameter: Rated current

• Default setting (_:2311:101) Rated current= 1000.00 A


Parameter: Rated voltage

• Default setting (_:2311:102) Rated voltage = 400.00 kV


The measured values of the voltage controller can be displayed as primary values, secondary values, or in
percent. With the Rated current and Rated voltage parameters, you set the reference value for the
percentage values.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1355


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Additional Parameters for the Three-Winding Transformer and Grid Coupling Transformer
Winding 1
Parameter: Rated current

• Default setting (_:2311:101) Rated current= 1000.00 A


Parameter: Rated voltage

• Default setting (_:2311:103) Rated voltage = 400.00 kV

Winding 2
Parameter: Rated current

• Default setting (_:2311:102) Rated current= 1000.00 A


Parameter: Rated voltage

• Default setting (_:2311:104) Rated voltage = 400.00 kV


The measured values of the voltage controller can be displayed as primary values, secondary values, or in
percent. With the Rated current and Rated voltage parameters, you set the reference value for the
percentage values.

Tap Changer
The parameters of the tap changer inside the voltage controller correspond to those of the tap changer in
chapter 8.8.2 Application and Setting Notes.
For the tap changer inside the voltage controller, the parameters for the control model are copies of those
from the voltage controller. This concerns the parameters:

• Checking the switching authority

• Control model

• SBO39 Time-out

• Feedback.monitor.time

General
Parameter: Mode

• Default setting (_:14011:1) Mode = on


With the Mode parameter, you switch the voltage controller in on, off, or in test operation.
Parameter: Operating mode

• Default setting (_:14011:101) Operating mode = Manual


With the Operating mode parameter, you specify whether the voltage controller is operating in Auto or in
Manual mode.
Parameter: Minimal voltage

• Default setting (_:14011:104) Minimal voltage = 5%


With the Minimal voltage parameter, you specify the threshold value at which the voltage controller oper-
ates. If the value is below the set threshold value, the entire measurement is not displayed and the binary
output Auto inactive is activated.

39 In the IEC 61850 standard, reservation is known as Select Before Operate (SBO).

1356 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Three-Winding Transformer only:


Parameter: Winding selection

• Default setting (_:15601:157) Winding selection = Winding 1


With the Winding selection parameter, you specify whether the voltage controller controls the voltage
of Winding 1 or Winding 2. With the WithMaxLoad parameter, the voltage to be controlled is selected
automatically depending on the load current. With this method, you can toggle using the parameter
Winding selection or the controllable Automatic winding selection.
If the controllable Automatic winding selection is set to Off or is not set, you can influence the
winding to be controlled using the following 2 options:

• Using the Winding selection parameter


• Using the Manual winding selection controllable
The function value Active winding shows the winding selection.

Grid Coupling Transformer only:


Parameter: Winding selection

• Default setting (_:16351:161) Winding selection = Winding 1


With the Winding selection parameter, you specify whether the voltage controller controls the voltage
of Winding 1 or Winding 2.
You may select the winding to be controlled using the Winding selection parameter or the Manual
winding selection controllable. The function value Active winding shows the winding selection.

8.9.4.2 Controlling
Parameter: Check switching authority

• Default setting (_:107) Check switching authority = yes


With the Check switching authority parameter, you specify whether the switching authority (On-site,
Remote) is checked during an adjusting command.
Parameter: Control model

• Default setting (_:109) Control model = SBO w. enh. security


This parameter Control model specifies the control model according to IEC 61850-7-2 that corresponds to
the behavior of the data (SBO – Select Before Operate).
You can select one of the following settings:

• direct w. normal secur.

• SBO w. normal secur.

• direct w. enh. security

• SBO w. enh. security


Parameter: SBO time-out

• Default setting (_:110) SBO time-out = 30.00 s


This parameter specifies the time for detecting the time-out of the SBO command. The range of values
extends from 0.01 s to 1800.00 s. This is the time that can elapse between command acceptance and
command execution (command model as per IEC 61850-7-2).
Parameter: Feedback monitoring time

• Default setting (_:111) Feedback monitoring time = 10.00 s


Reaching a new tap position after the adjusting command is monitored via the feedback-monitoring time. If a
new tap position is not reached, the command is canceled after this time.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1357


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

8.9.4.3 Voltage Controller


Parameter: Number of target voltage

• Default setting (_:14011:156) Number of target voltage = 1


With this parameter, you specify the number of available target voltages (1 to 4). You can select a target
voltage from the available ones using the function key, communication, or binary input.

NOTE

i Keep in mind that the parameter Number of target voltage cannot be influenced by way of the
settings group switching.
You can specify the target voltages (1 to 4) in primary, secondary, or in percent.
For the activation of the target voltage 1 to 4 via a binary input, you need a CFC chart.

Parameter: Target voltage 1

• Default setting (_:14011:112) Target voltage 1 = 110.000 V


With the Target voltage 1 parameter, you specify the voltage that the voltage controller is supposed to
reach.
Parameter: Target voltage 2

• Default setting (_:14011:157) Target voltage 2 = 110.000 V


With the Target voltage 2 parameter, you specify the 2nd voltage that the voltage controller is supposed
to reach.
Parameter: Target voltage 3

• Default setting (_:14011:158) Target voltage 3 = 110.000 V


With the Target voltage 3 parameter, you specify the 3rd voltage that the voltage controller is supposed
to reach.
Parameter: Target voltage 4

• Default setting (_:14011:159) Target voltage 4 = 110.000 V


With the Target voltage 4 parameter, you specify the 4th voltage that the voltage controller is supposed
to reach.

1358 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Three-Winding Transformer only:


Parameter: Number of target voltage

• Default setting (_:15601:164) Number of target voltage = 1


With this parameter, you specify the number of available target voltages (1 W1/2 to 4 W1/2). You can
select a target voltage from the available ones using the function key, communication, or binary input.

Note:
Keep in mind that the parameter Number of target voltage cannot be influenced by way of the
settings group switching.
You can specify the target voltages (1 W1/2 to 4 W1/2) in primary, secondary, or in percent.
For the activation of the target voltage 1 to 4 via a binary input, you need a CFC chart.
Parameter: Target voltage 1 w1

• Default setting (_:15601:112) Target voltage 1 w1 = 110.000 V


Parameter: Target voltage 1 w2

• Default setting (_:15601:146) Target voltage 1 w2 = 110.000 V


Parameter: Target voltage 2 w1

• Default setting (_:15601:165) Target voltage 2 w1 = 110.000 V


Parameter: Target voltage 2 w2

• Default setting (_:15601:168) Target voltage 2 w2 = 110.000 V


Parameter: Target voltage 3 w1

• Default setting (_:15601:166) Target voltage 3 w1 = 110.000 V


Parameter: Target voltage 3 w2

• Default setting (_:15601:169) Target voltage 3 w2 = 110.000 V


Parameter: Target voltage 4 w1

• Default setting (_:15601:167) Target voltage 4 w1 = 110.000 V


Parameter: Target voltage 4 w2

• Default setting (_:15601:170) Target voltage 4 w2 = 110.000 V

SIPROTEC 5, 7SJ82/7SJ85, Manual 1359


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Grid Coupling Transformer only:


Parameter: Number of target voltage

• Default setting (_:16351:164) Number of target voltage = 1


With this parameter, you specify the number of available target voltages (1 W1/2 to 4 W1/2). You can
select a target voltage from the available ones using the function key, communication, or binary input.

Note:
Keep in mind that the parameter Number of target voltage cannot be influenced by way of the
settings group switching.
You can specify the target voltages (1 W1/2 to 4 W1/2) in primary, secondary, or in percent.
For the activation of the target voltage 1 to 4 via a binary input, you need a CFC chart.
Parameter: Target voltage 1 w1

• Default setting (_:16351:112) Target voltage 1 w1 = 110.000 V


Parameter: Target voltage 1 w2

• Default setting (_:16351:146) Target voltage 1 w2 = 110.000 V


Parameter: Target voltage 2 w1

• Default setting (_:16351:165) Target voltage 2 w1 = 110.000 V


Parameter: Target voltage 2 w2

• Default setting (_:16351:168) Target voltage 2 w2 = 110.000 V


Parameter: Target voltage 3 w1

• Default setting (_:16351:166) Target voltage 3 w1 = 110.000 V


Parameter: Target voltage 3 w2

• Default setting (_:16351:169) Target voltage 3 w2 = 110.000 V


Parameter: Target voltage 4 w1

• Default setting (_:16351:167) Target voltage 4 w1 = 110.000 V


Parameter: Target voltage 4 w2

• Default setting (_:16351:170) Target voltage 4 w2 = 110.000 V

Parameter: Bandwidth

• Default setting (_:113) Bandwidth = 1.0 %


With the Bandwidth parameter, you specify the voltage range where no control action higher or lower is to
occur at the Target voltage 1. If the actual voltage is outside the bandwidth referenced to the Target
voltage 1, no correction takes place.
Calculation of the Bandwidth:

NOTE

i When calculating the Bandwidth B, keep the maximum accepted voltage deviation in the electrical power
system and the tap voltage of the tap changer on the secondary side of the transformer in mind. Select the
bandwidths so that it is not passed through within an increment.

1360 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

NOTE

i Instable Controlling (Hunting)


The tolerance band is defined by the double bandwidth. If you select the bandwidth – and thus the admis-
sible control deviation D – in such a way that the tolerance band is smaller than the step adjustment of the
transformer, then, with the next step adjustment operation, the voltage controller adjusts over the other
side of the band after exceeding the tolerance band. In this case, no stable controlling is possible. This
operation is also called Hunting. Keep also in mind that the load of the tap changer, that is the amount of
operated tap changes, increases with lower bandwidth.

On the secondary side, the increment ∆Vsec is not linear. The largest ∆Vmax,sec in an increment results with the
increment to the highest stage (smallest ratio) and with maximum power-system voltage on the primary side.

[fobdnvrz-150816, 1, en_US]

If the control deviation and the bandwidth are thus correlated, this results in a minimal bandwidth that is to be
set:

[fospnvrz-150816, 1, en_US]

Vrated,sec Secondary rated voltage of the transformer


VN,prim Primary tap voltage of the transformer of tap N
V(N-1),prim Primary tap voltage of the transformer of tap N-1
Vmax,prim Maximum primary voltage of the transformer
Vmax,sec Maximum secondary voltage of the transformer

Parameter: T1 characteristic

• Default setting (_:114) T1 characteristic = Linear


Parameter: T1 delay

• Default setting (_:115) T1 delay = 40 s


You can adjust the control action so that the smallest number of adjusting commands possible is necessary. To
do so, use T1 characteristic to set the control response and T1 delay to set a time delay.
In the Linear setting (linear control response), the control response is independent of the voltage deviation.
A constant time delay applies here.
In the Inverse setting (inverse control response), the time delay is a function of the voltage deviation refer-
enced to Target voltage 1. The greater the control deviation, the faster the control response. The control
quality improves, but the switching frequency increases. If the voltage control is blocked during the time
delay, the accumulated time delay T1 delay is reset.
The effective time delay is the result from:

[fovrzzet-211013, 2, en_US]

T1 – Parameter T1 delay

[fokonisk-211013, 2, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 1361


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

D = Control deviation

[dwrglchr-160913-01.vsd, 2, en_US]

Figure 8-155 Inverse Control Characteristic

Parameter: T1 Inverse Min

• Default setting (_:116) T1 Inverse Min= 5 s


With the T1 Inverse Min parameter, you define the minimum time delay for the control action. This time
applies only to the control response Inverse and the response cannot be shorter.
Parameter: T2 delay

• Default setting (_:117) T2 delay= 5 s


With the T2 delay parameter, you set the time the tap changer has to wait from one tap position to the
next. During this time, several adjusting commands can be sent to the tap changer in one direction, which
permits a correction of the actual voltage. The time delay T2 has an independent characteristic. The time T2 is
generally set shorter than the time T1. If the time T2 is switched off by a setting equal to 0, the delay T1 is
always active. If the voltage control is blocked during the time delay, the accumulated time delays T1 delay
and T2 delay are reset.
Parameter: Fast step up

• Default setting (_:118) Fast step up = off


Parameter: Fast step up limit

• Default setting (_:119) Fast step up limit = –6.0 %


Parameter: Fast step up T delay

• Default setting (_:120) Fast step up T delay = 2.0 s


With this parameter, you specify the time delay of the fast step up mode. If the actual voltage is less than the
value of the limit for the fast step up mode (_:119), the fast step up mode is activated. A fast step up mode is
not activated if the value drops below the voltage limit for only a brief period within the time delay. If the
voltage control is blocked during the time delay, the accumulated time delay Fast step up T delay is
reset.
Parameter: Fast step down

1362 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

• Default setting (_:121) Fast step down = on


Parameter: Fast step down limit

• Default setting (_:122) Fast step down limit = 6.0%


Parameter: Fast step down T delay

• Default setting (_:123) Fast step down T delay = 0.0 s


With this parameter, you specify the time delay of the fast step down mode. If the actual voltage is greater
than the value of the limit for the fast step down mode (_:122), the fast step down mode is activated. A fast
step down mode is not activated if the voltage limit is exceeded for only a brief period within the time delay. If
the voltage control is blocked during the time delay, the accumulated time delay Fast step down T
delay is reset.
Parameter: Function monitoring

• Default setting (_:124) Function monitoring = 15 min


You can delay the pickup of the function monitor. With the setting Function monitoring = 0 min, the
function monitor is switched off.
Grid Coupling Transformer Only:
Parameter: Power-flow supervision

• Default setting (_:16351:162) Power-flow supervision = on


With the Power-flow supervision parameter, you monitor the power flow. You can switch the param-
eter on or off.

Parameter: Regulate with T2 at start

• Default setting (_:14011:155) Regulate with T2 at start = on


With the Regulate with T2 at start parameter, you can activate a shorter time than T1. This can be
necessary for controlling a voltage recovery or after switching on a transformer. If voltage was not present
beforehand, this setting controls with the shorter time T2 when starting the control action. You can switch
this functionality on or off. If you always want to use the time T2 for control, you must set the Block T1
controllable to On.
For the three-winding transformer, the address of the Regulate with T2 at start parameter is
_:15601:163, for the grid coupling transformer, it is _:16351:163.
Parameter: Set point mode active

• Default setting (_:14011:160) Set point mode active = on


With th Set point mode active = on parameter, you can send a target voltage to the controller via a
communication network. The voltage controller uses the specified voltage value as target voltage. If the
controller does not receive any valid voltage values, it uses the original target voltage. You can enable or
disable the parameter.
For the three-winding transformer, the address of the parameter Set point mode active is
_:15601:171, for the grid coupling transformer, it is _:16351:171

8.9.4.4 Line Compensation


Parameter: Line drop compensation

• Default setting (_:14011:125) Line drop compensation = off


You can use the Line drop compensation parameter to select the correction procedure of the load-
dependent line voltage drop. There are 2 procedures available for selection: LDC-Z and LDC-XandR. The
setting of the parameter Set point mode active is also taken into account here.
For setting the parameter Line drop compensation = LDC-Z, consider the following parameter:
Parameter: Target voltage rising

• Default setting (_:14011:126) Target voltage rising = 4.0 %

SIPROTEC 5, 7SJ82/7SJ85, Manual 1363


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

With the Target voltage rising parameter, you set the voltage drop across the line. The value repre-
sents the voltage rising in % of the Target voltage 1 that occurs at rated load. Only the magnitude of the
current is considered. The set value is added to Target voltage 1.

Target voltage rising [%] = ΔVload [%], if Iload = 100 %

[foschlst-211013, 2, en_US]

where:
VSetComp Target voltage at the end of the line
VSet Target voltage
Iload Load current in %

With the following equation, you can determine the percentage of the primary load current of the line from
the rated current of the transformer k (k = 1, 2, …, 8).

[fo_ibs_load_cur_perc, 1, en_US]

where:
Iload Primary load current
Irated Rated current of the transformer

Example
Application example of the LDC-Z line compensation for the voltage control of 2 transformers connected in
parallel.

[dw_target_voltage_2exam, 1, en_US]

Figure 8-156 LDC-Z Line Compensation with 2 Parallel Transformers

1364 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

In the example, a load current of Iload = 1430 A results in a voltage drop of Vload = 500 V.

Value Transformer T1 Transformer T2

Iload(%) 100 % 50 %

Target voltage rising ΔVload(%) 4.8 % 9.6 %

NOTE

i Make sure that you configure the parameter Max load current on the voltage controller on the trans-
former T1 to 200 %, as this summation load current is used for the line compensation.

Parameter: LDC is calculated

• Default setting (_:14011:172) LDC is calculated = on target voltage


For the parameter LDC is calculated, you can select between the settings on target voltage and on
measured voltage. The voltage compensation is added to the target voltage with the setting on target
voltage and to the measured voltage with the setting on measured voltage.
Parameter: Max load current

• Default setting (_:14011:127) Max load current = 100.0 %


With the setting of the parameter Max load current, you can prevent the voltage at the transformer from
becoming too high in the event of extraordinarily high load current. If the load current exceeds the set value,
no additional load-current compensation is calculated.
For setting the parameter Line drop compensation = LDC-XandR, consider the following parameters:
Parameter: R line

• Default setting (_:14011:153) R line = 0.00 Ω


With the R line, you to set the ohmic resistance of the line.
Parameter: X line

• Default setting (_:14011:154) X line = 0.00 Ω


With the X line parameter, you set the reactance for the line to be protected.
In order to determine the voltage drop by the line, entering the parameters R line and X line is necessary
for the procedure Line drop compensation = LDC-XandR. If the primary values are known and you
would like to set the secondary values, use the following formula for the calculation:

[fo-I-V-Ratio-250214, 1, en_US]

As an example, calculate Xsec with the following parameters:

Current transformer ratio : 1000 A/1 A


Voltage transformer ratio : 380 kV/0.1 kV
Xprim : 21 Ω

Therefore, the result for Xsec is:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1365


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

[fo-I-V-Ratio_Value-250214, 1, en_US]

If you are implementing a parallel control with the X and R compensation, then the X value is negative and
considers the voltage rising from the busbar to the transformer.

Additional Parameters for the Three-Winding Transformer and for the Grid Coupling Transformer
Parameter: Line drop compensation

• Default setting (_:125) Line drop compensation = off


For setting the parameter Line drop compensation = LDC-Z, consider the following parameters:
Parameter: Target voltage rising w1

• Default setting (_:126) Target voltage rising w1 = 4.0%


Parameter: Target voltage rising w2

• Default setting (_:147) Target voltage rising w2 = 4.0%


Parameter: Max load current

• Default setting (_:127) Max load current = 100.0 %


For setting the parameter Line drop compensation = LDC-XandR, consider the following parameters:
Parameter: R line w1

• Default setting (_:153) R line w1 = 0.0 Ω


Parameter: R line w2

• Default setting (_:155) R line w2 = 0.0 Ω


Parameter: X line w1

• Default setting (_:154) X line w1 = 0.0 Ω


Parameter: X line w2

• Default setting (_:156) X line w2 = 0.0 Ω

8.9.4.5 Limiting Values


Parameter: Lower tap-position limit

• Default setting (_:14011:102) Lower tap-position limit = 1


Parameter: Higher tap-position limit

• Default setting (_:14011:103) Higher tap-position limit = 1


With the parameters Lower tap-position limit and Higher tap-position limit, you can restrict
the taps available in automatic operation. For example, using the parameter Higher tap-position
limit, changes to higher taps to excessive ratios that would result in overvoltages in the event of a sudden
loss of load are blocked.
Parameter: Vmin limiting

• Default setting (_:14011:128) Vmin limiting = on


Parameter: Vmin threshold

• Default setting (_:14011:129) Vmin threshold = 105.000 V


Parameter: Vmin time delay

• Default setting (_:14011:130) Vmin time delay = 10 s


Parameter: Vmax limiting

• Default setting (_:14011:131) Vmax limiting = on

1366 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Parameter: Vmax threshold

• Default setting (_:14011:132) Vmax threshold = 115.000 V


Parameter: Vmax time delay

• Default setting (_:14011:133) Vmax time delay = 10 s


The voltage limits are necessary only for special control situations. The overvoltage limit prevents a change to
a higher tap by the voltage controller if the limiting value Vmax threshold is exceeded. The undervoltage
limit prevents a change to a lower tap by the voltage controller if the voltage drops below the limiting value
Vmin threshold.
Additional Parameters for the Three-Winding Transformer and for the Grid Coupling Transformer
Parameter: Vmin threshold w1

• Default setting (_:129) Vmin threshold w1 = 105.000 V


Parameter: Vmin threshold w2

• Default setting (_:148) Vmin threshold w2 = 105.000 V

Parameter: Vmax threshold w1

• Default setting (_:132) Vmax threshold w1 = 115.000 V


Parameter: Vmax threshold w2

• Default setting (_:149) Vmax threshold w2 = 115.000 V

8.9.4.6 Blockings
Parameter: Blocking behavior

• Default setting (_:14011:134) Blocking behavior = Auto-Manual


If the corresponding voltage limits are exceeded in either direction, the blockings prevent a change to a lower
or higher tap. On the one hand, this prevents excessive wear of the contacts of the tap changer and, on the
other hand, it prevents a system incident. With the parameter Blocking behavior, you set whether these
blockings are effective only in automatic operation or in both automatic and manual operation.
Parameter: V< Blocking

• Default setting (_:14011:135) V< Blocking = on


Parameter: V< Threshold

• Default setting (_:14011:136) V< Threshold = 90.000 V


Parameter: V< Time delay

• Default setting (_:14011:137) V< Time delay = 0 s


Parameter: I> Blocking

• Default setting (_:14011:138) I> Blocking = on


Parameter: I> Threshold

• Default setting (_:14011:139) I> Threshold = 150 %


Parameter: I> Time delay

• Default setting (_:14011:140) I> Time delay = 0 s


If the load current exceeds the threshold value I> Threshold for the time I> Time delay, the overcur-
rent blocking prevents changing to a higher or lower tap. Set the threshold value I> Threshold in % in rela-
tion to the rated current. To do this, set the parameter I reference for % values.
Parameter: I< Blocking

• Default setting (_:14011:141) I< Blocking = off

SIPROTEC 5, 7SJ82/7SJ85, Manual 1367


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Parameter: I< Threshold

• Default setting (_:14011:142) I< Threshold = 10 %


Parameter: I< Time delay

• Default setting (_:14011:143) I< Time delay = 10 s


If the load current drops below the threshold value I< Threshold for the time I< Time delay, the under-
current blocking prevents changing to a higher or lower tap. Set the threshold value I< Threshold in % in
relation to the rated current. To do this, set the parameter I reference for % values.
Additional Pararmeters for Three-Winding Transformers and for Grid Coupling Transformers
Parameter: V< Threshold w1

• Default setting (_:136) V< Threshold w1 = 90.000 V


Parameter: V< Threshold w2

• Default setting (_:150) V< Threshold w2 = 90.000 V

You can find the parameter and information lists in chapter 8.9.5 Settings.

8.9.4.7 Parallel Control


Parameter: Parallel mode

• Default setting (_:14011:161) Parallel mode = No mode


With the Parallel mode parameter, you can switch the voltage controller into one of the following modes:
No mode
Master
Follower
Circulat. react current
Parameter: Parallel-transfomer id

• Default setting (_:14011:168) Parallel-transfomer id = 1


The Parallel-transfomer id parameter indicates the ID of the transformer.
With this parameter, you identify individual transformers in a parallel group. Transformers belonging to the
same parallel group must be uniquely identifiable based on the ID. The unique identification applies to all
transformers which communicate via GOOSE.
Parameter: Parallel mode changeable

• Default setting (_:14011:164) Parallel mode changeable = by setting


With the Parallel mode changeable parameter, you can influence the parallel control by setting or
via the setting controllable.
Parameter: Force master changeable

• Default setting (_:14011:165) Force master changeable = by setting


With the Force master changeable parameter, you can determine by setting or via the setting
controllable which device is the Master in the parallel operation. In a group of transformers working in
parallel, only one device can be the Master. The presence of a Master is monitored.
Parameter: Maximal tap difference

• Default setting (_:14011:166) Maximal tap difference = 2


With the Maximal tap difference parameter, you set the maximum permissible difference of the tap-
changer positions between the transformers of a group.
Parameter: Reactive I control factor

• Default setting (_:14011:169) Reactive I control factor = 1.00

1368 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

The voltage deviation between the transformers is influenced with the parameter Reactive I control
factor. This means that a deviation from one stage exceeds the bandwidth of the voltage controller. This
allows the control deviation DCRC, initiated by the circulating reactive current, to be adjusted individually for
every parallel operation.
Parameter: VT supervision

• Default setting (_:14011:146) VT supervision = on


With the VT supervision parameter, you switch the voltage supervision on or off.
Parameter: VT supervision threshold

• Default setting (_:14011:147) VT supervision threshold = 10.0 %


With the VT supervision threshold parameter, you set the threshold value for the voltage supervision.
Parameter: VT supervision time delay

• Default setting (_:14011:148) VT supervision time delay = 10 s


With the VT supervision time delay parameter, you set the time for which exceeding the voltage
supervision threshold does not lead to a blocking.
Parameter: Circul. current blocking

• Default setting (_:14011:149) Circul. current blocking = on


With the Circul. current blocking parameter, you switch the supervision of the circulating reactive
current off or on.
Parameter: Circul. current threshold

• Default setting (_:14011:150) Circul. current threshold = 50 %


With the Circul. current threshold parameter, you set the level at which the supervision must be acti-
vated.
Parameter: Circul. current time delay

• Default setting (_:14011:151) Circul. current time delay = 60 s


With the Circul. current time delay parameter, you set the time for which exceeding the threshold
value of the circulating reactive current supervision does not lead to a blocking.

8.9.5 Settings

Two-Winding Transformer and Parallel Control

Addr. Parameter C Setting Options Default Setting


Ref. for %-values
_:2311:101 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:102 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
_:2311:106 General:Rated app. 0.20 MVA to 5000.00 MVA 692.82 MVA
power transf.
_:2311:108 General:Imp(Z): short 1.00 % to 20.00 % 10.00 %
circuit imp.
_:2311:124 General:Freq tracking 1 to 100 1
group ID
General
_:14011:1 90V V.contr.2w:Mode • off on
• on
• test
_:14011:101 90V V.contr.2w:Oper- • Manual Manual
ating mode
• Auto

SIPROTEC 5, 7SJ82/7SJ85, Manual 1369


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


_:14011:104 90V V.contr.2w:Minimal 0 % to 100 % 5%
voltage
Control tap changer
_:14011:107 90V V.contr.2w:Check • no yes
switching authority
• yes
_:14011:109 90V V.contr.2w:Control • direct w. normal secur. SBO w. enh.
model security
• SBO w. normal secur.
• direct w. enh. security
• SBO w. enh. security
_:14011:110 90V V.contr.2w:SBO 0.01 s to 1800.00 s 30.00 s
time-out
_:14011:111 90V V.contr.2w:Feed- 0.01 s to 1800.00 s 10.00 s
back monitoring time
Voltage Control
_:14011:156 90V V.contr.2w:Number • 1 1
of target voltage
• 2
• 3
• 4
_:14011:112 90V V.contr.2w:Target 10.000 V to 340.000 V 110.000 V
voltage 1
_:14011:157 90V V.contr.2w:Target 10.000 V to 340.000 V 110.000 V
voltage 2
_:14011:158 90V V.contr.2w:Target 10.000 V to 340.000 V 110.000 V
voltage 3
_:14011:159 90V V.contr.2w:Target 10.000 V to 340.000 V 110.000 V
voltage 4
_:14011:113 90V V.contr.2w:Band- 0.2 % to 10.0 % 1.0 %
width
_:14011:114 90V V.contr.2w:T1 char- • Linear Linear
acteristic
• Inverse
_:14011:115 90V V.contr.2w:T1 delay 5 s to 600 s 40 s
_:14011:116 90V V.contr.2w:T1 5 s to 100 s 5s
Inverse Min
_:14011:117 90V V.contr.2w:T2 delay 0 s to 100 s 5s
_:14011:118 90V V.contr.2w:Fast step • off off
up
• on
_:14011:119 90V V.contr.2w:Fast step -50.0 % to 0.0 % -6.0 %
up limit
_:14011:120 90V V.contr.2w:Fast step 0.0 s to 10.0 s 2.0 s
up T delay
_:14011:121 90V V.contr.2w:Fast step • off on
down
• on
_:14011:122 90V V.contr.2w:Fast step 0.0 % to 50.0 % 6.0 %
down limit
_:14011:123 90V V.contr.2w:Fast step 0.0 s to 10.0 s 0.0 s
down T delay
_:14011:124 90V V.contr.2w:Function 0 min to 120 min 15 min
monitoring

1370 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


_:14011:155 90V V.contr.2w:Regulate • off on
with T2 at start
• on
_:14011:160 90V V.contr.2w:Set • off on
point mode active
• on
Parallel operation
_:14011:161 90V V.contr.2w:Parallel • No mode No mode
mode
• Master
• Follower
• Circulat. react current
_:14011:168 90V V.contr.2w:Parallel- 1 to 8 1
transfomer id
_:14011:164 90V V.contr.2w:Parallel • by setting by setting
mode changeable
• controllable
_:14011:165 90V V.contr.2w:Force • by setting by setting
master changeable
• controllable
_:14011:166 90V V.contr.2w:Maximal 1 to 9 2
tap difference
_:14011:169 90V V.contr.2w:Reactive 0.01 to 100.00 1.00
I control factor
_:14011:146 90V V.contr.2w:VT • off on
supervision
• on
_:14011:147 90V V.contr.2w:VT 0.5 % to 10.0 % 10.0 %
supervision threshold
_:14011:148 90V V.contr.2w:VT 1 s to 600 s 10 s
supervision time delay
_:14011:149 90V V.contr.2w:Circul. • off on
current blocking
• on
_:14011:150 90V V.contr.2w:Circul. 10 % to 500 % 50 %
current threshold
_:14011:151 90V V.contr.2w:Circul. 0 s to 1000 s 60 s
current time delay
Line drop comp.
_:14011:125 90V V.contr.2w:Line • off off
drop compensation
• LDC-Z
• LDC-XandR
_:14011:172 90V V.contr.2w:LDC is • on target voltage on target
calculated voltage
• on measured voltage
_:14011:126 90V V.contr.2w:Target 0.0 % to 20.0 % 4.0 %
voltage rising
_:14011:127 90V V.contr.2w:Max 0.0 % to 500.0 % 100.0 %
load current
_:14011:153 90V V.contr.2w:R line 0.00 Ω to 30.00 Ω 0.00 Ω
_:14011:154 90V V.contr.2w:X line -30.00 Ω to 30.00 Ω 0.00 Ω
Limiting
_:14011:102 90V V.contr.2w:Lower -128 to 127 1
tap-position limit
_:14011:103 90V V.contr.2w:Higher -128 to 127 15
tap-position limit

SIPROTEC 5, 7SJ82/7SJ85, Manual 1371


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


_:14011:128 90V V.contr.2w:Vmin • off on
limiting
• on
_:14011:129 90V V.contr.2w:Vmin 10.000 V to 340.000 V 105.000 V
threshold
_:14011:130 90V V.contr.2w:Vmin 0 s to 20 s 10 s
time delay
_:14011:131 90V V.contr.2w:Vmax • off on
limiting
• on
_:14011:132 90V V.contr.2w:Vmax 10.000 V to 340.000 V 115.000 V
threshold
_:14011:133 90V V.contr.2w:Vmax 0 s to 20 s 10 s
time delay
Blocking
_:14011:134 90V V.contr.2w:Blocking • Auto Auto-Manual
behavior
• Auto-Manual
_:14011:135 90V V.contr.2w:V< • off on
Blocking
• on
_:14011:136 90V V.contr.2w:V< 10.000 V to 340.000 V 90.000 V
Threshold
_:14011:137 90V V.contr.2w:V< Time 0 s to 20 s 0s
delay
_:14011:138 90V V.contr.2w:I> • off on
Blocking
• on
_:14011:139 90V V.contr.2w:I> 10 % to 500 % 150 %
Threshold
_:14011:140 90V V.contr.2w:I> Time 0 s to 20 s 0s
delay
_:14011:141 90V V.contr.2w:I< • off off
Blocking
• on
_:14011:142 90V V.contr.2w:I< 3 % to 100 % 10 %
Threshold
_:14011:143 90V V.contr.2w:I< Time 0 s to 20 s 10 s
delay

Three-Winding Transformer

Addr. Parameter C Setting Options Default Setting


Winding 1
_:2311:101 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:103 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Winding 2
_:2311:102 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:104 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Rated values
_:2311:137 General:Freq tracking 1 to 100 1
group ID

1372 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


General
_:15601:1 90V V.contr.3w:Mode • off on
• on
• test
_:15601:101 90V V.contr.3w:Oper- • Manual Manual
ating mode
• Auto
_:15601:104 90V V.contr.3w:Minimal 0 % to 100 % 5%
voltage
_:15601:157 90V V.contr.3w:Winding • Winding 1 Winding 1
selection
• Winding 2
• WithMaxLoad
_:15601:161 90V V.contr.3w:Winding • Winding 1 Winding 1
selection
• Winding 2
Control tap changer
_:15601:107 90V V.contr.3w:Check • no yes
switching authority
• yes
_:15601:109 90V V.contr.3w:Control • direct w. normal secur. SBO w. enh.
model security
• SBO w. normal secur.
• direct w. enh. security
• SBO w. enh. security
_:15601:110 90V V.contr.3w:SBO 0.01 s to 1800.00 s 30.00 s
time-out
_:15601:111 90V V.contr.3w:Feed- 0.01 s to 1800.00 s 10.00 s
back monitoring time
Voltage Control
_:15601:164 90V V.contr.3w:Number • 1 1
of target voltage
• 2
• 3
• 4
_:15601:112 90V V.contr.3w:Target 10.000 V to 340.000 V 110.000 V
voltage 1 w1
_:15601:165 90V V.contr.3w:Target 10.000 V to 340.000 V 110.000 V
voltage 2 w1
_:15601:166 90V V.contr.3w:Target 10.000 V to 340.000 V 110.000 V
voltage 3 w1
_:15601:167 90V V.contr.3w:Target 10.000 V to 340.000 V 110.000 V
voltage 4 w1
_:15601:146 90V V.contr.3w:Target 10.000 V to 340.000 V 110.000 V
voltage 1 w2
_:15601:168 90V V.contr.3w:Target 10.000 V to 340.000 V 110.000 V
voltage 2 w2
_:15601:169 90V V.contr.3w:Target 10.000 V to 340.000 V 110.000 V
voltage 3 w2
_:15601:170 90V V.contr.3w:Target 10.000 V to 340.000 V 110.000 V
voltage 4 w2
_:15601:113 90V V.contr.3w:Band- 0.2 % to 10.0 % 1.0 %
width

SIPROTEC 5, 7SJ82/7SJ85, Manual 1373


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


_:15601:114 90V V.contr.3w:T1 char- • Linear Linear
acteristic
• Inverse
_:15601:115 90V V.contr.3w:T1 delay 5 s to 600 s 40 s
_:15601:116 90V V.contr.3w:T1 5 s to 100 s 5s
Inverse Min
_:15601:117 90V V.contr.3w:T2 delay 0 s to 100 s 5s
_:15601:118 90V V.contr.3w:Fast step • off off
up
• on
_:15601:119 90V V.contr.3w:Fast step -50.0 % to 0.0 % -6.0 %
up limit
_:15601:120 90V V.contr.3w:Fast step 0.0 s to 10.0 s 2.0 s
up T delay
_:15601:121 90V V.contr.3w:Fast step • off on
down
• on
_:15601:122 90V V.contr.3w:Fast step 0.0 % to 50.0 % 6.0 %
down limit
_:15601:123 90V V.contr.3w:Fast step 0.0 s to 10.0 s 0.0 s
down T delay
_:15601:124 90V V.contr.3w:Function 0 min to 120 min 15 min
monitoring
_:15601:162 90V V.contr.3w:Power- • off on
flow supervision
• on
_:15601:163 90V V.contr.3w:Regulate • off on
with T2 at start
• on
_:15601:171 90V V.contr.3w:Set • off on
point mode active
• on
Line drop comp.
_:15601:125 90V V.contr.3w:Line • off off
drop compensation
• LDC-Z
• LDC-XandR
_:15601:172 90V V.contr.3w:LDC is • on target voltage on target
calculated voltage
• on measured voltage
_:15601:126 90V V.contr.3w:Target 0.0 % to 20.0 % 4.0 %
voltage rising w1
_:15601:147 90V V.contr.3w:Target 0.0 % to 20.0 % 4.0 %
voltage rising w2
_:15601:127 90V V.contr.3w:Max 0.0 % to 500.0 % 100.0 %
load current
_:15601:153 90V V.contr.3w:R line 0.0 Ω to 30.0 Ω 0.0 Ω
w1
_:15601:154 90V V.contr.3w:X line -30.0 Ω to 30.0 Ω 0.0 Ω
w1
_:15601:155 90V V.contr.3w:R line 0.0 Ω to 30.0 Ω 0.0 Ω
w2
_:15601:156 90V V.contr.3w:X line -30.0 Ω to 30.0 Ω 0.0 Ω
w2

1374 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


Limiting
_:15601:102 90V V.contr.3w:Lower -128 to 127 1
tap-position limit
_:15601:103 90V V.contr.3w:Higher -128 to 127 15
tap-position limit
_:15601:128 90V V.contr.3w:Vmin • off on
limiting
• on
_:15601:129 90V V.contr.3w:Vmin 10.000 V to 340.000 V 105.000 V
threshold w1
_:15601:148 90V V.contr.3w:Vmin 10.000 V to 340.000 V 105.000 V
threshold w2
_:15601:130 90V V.contr.3w:Vmin 0 s to 20 s 10 s
time delay
_:15601:131 90V V.contr.3w:Vmax • off on
limiting
• on
_:15601:132 90V V.contr.3w:Vmax 10.000 V to 340.000 V 115.000 V
threshold w1
_:15601:149 90V V.contr.3w:Vmax 10.000 V to 340.000 V 115.000 V
threshold w2
_:15601:133 90V V.contr.3w:Vmax 0 s to 20 s 10 s
time delay
Blocking
_:15601:134 90V V.contr.3w:Blocking • Auto Auto-Manual
behavior
• Auto-Manual
_:15601:135 90V V.contr.3w:V< • off on
Blocking
• on
_:15601:136 90V V.contr.3w:V< 10.000 V to 340.000 V 90.000 V
Threshold w1
_:15601:150 90V V.contr.3w:V< 10.000 V to 340.000 V 90.000 V
Threshold w2
_:15601:137 90V V.contr.3w:V< Time 0 s to 20 s 0s
delay
_:15601:138 90V V.contr.3w:I> • off on
Blocking
• on
_:15601:139 90V V.contr.3w:I> 10 % to 500 % 150 %
Threshold
_:15601:140 90V V.contr.3w:I> Time 0 s to 20 s 0s
delay
_:15601:141 90V V.contr.3w:I< • off off
Blocking
• on
_:15601:142 90V V.contr.3w:I< 3 % to 100 % 10 %
Threshold
_:15601:143 90V V.contr.3w:I< Time 0 s to 20 s 10 s
delay

Grid Coupling Transformer

Addr. Parameter C Setting Options Default Setting


Winding 1
_:2311:101 General:Rated current 0.20 A to 100000.00 A 1000.00 A

SIPROTEC 5, 7SJ82/7SJ85, Manual 1375


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


_:2311:103 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Winding 2
_:2311:102 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:104 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Rated values
_:2311:137 General:Freq tracking 1 to 100 1
group ID
General
_:16351:1 90V V.contr.gc:Mode • off on
• on
• test
_:16351:101 90V V.contr.gc:Oper- • Manual Manual
ating mode
• Auto
_:16351:104 90V V.contr.gc:Minimal 0 % to 100 % 5%
voltage
_:16351:157 90V V.contr.gc:Winding • Winding 1 Winding 1
selection
• Winding 2
• WithMaxLoad
_:16351:161 90V V.contr.gc:Winding • Winding 1 Winding 1
selection
• Winding 2
Control tap changer
_:16351:107 90V V.contr.gc:Check • no yes
switching authority
• yes
_:16351:109 90V V.contr.gc:Control • direct w. normal secur. SBO w. enh.
model security
• SBO w. normal secur.
• direct w. enh. security
• SBO w. enh. security
_:16351:110 90V V.contr.gc:SBO 0.01 s to 1800.00 s 30.00 s
time-out
_:16351:111 90V V.contr.gc:Feedback 0.01 s to 1800.00 s 10.00 s
monitoring time
Voltage Control
_:16351:164 90V V.contr.gc:Number • 1 1
of target voltage
• 2
• 3
• 4
_:16351:112 90V V.contr.gc:Target 10.000 V to 340.000 V 110.000 V
voltage 1 w1
_:16351:165 90V V.contr.gc:Target 10.000 V to 340.000 V 110.000 V
voltage 2 w1
_:16351:166 90V V.contr.gc:Target 10.000 V to 340.000 V 110.000 V
voltage 3 w1
_:16351:167 90V V.contr.gc:Target 10.000 V to 340.000 V 110.000 V
voltage 4 w1
_:16351:146 90V V.contr.gc:Target 10.000 V to 340.000 V 110.000 V
voltage 1 w2

1376 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


_:16351:168 90V V.contr.gc:Target 10.000 V to 340.000 V 110.000 V
voltage 2 w2
_:16351:169 90V V.contr.gc:Target 10.000 V to 340.000 V 110.000 V
voltage 3 w2
_:16351:170 90V V.contr.gc:Target 10.000 V to 340.000 V 110.000 V
voltage 4 w2
_:16351:113 90V V.contr.gc:Band- 0.2 % to 10.0 % 1.0 %
width
_:16351:114 90V V.contr.gc:T1 char- • Linear Linear
acteristic
• Inverse
_:16351:115 90V V.contr.gc:T1 delay 5 s to 600 s 40 s
_:16351:116 90V V.contr.gc:T1 5 s to 100 s 5s
Inverse Min
_:16351:117 90V V.contr.gc:T2 delay 0 s to 100 s 5s
_:16351:118 90V V.contr.gc:Fast step • off off
up
• on
_:16351:119 90V V.contr.gc:Fast step -50.0 % to 0.0 % -6.0 %
up limit
_:16351:120 90V V.contr.gc:Fast step 0.0 s to 10.0 s 2.0 s
up T delay
_:16351:121 90V V.contr.gc:Fast step • off on
down
• on
_:16351:122 90V V.contr.gc:Fast step 0.0 % to 50.0 % 6.0 %
down limit
_:16351:123 90V V.contr.gc:Fast step 0.0 s to 10.0 s 0.0 s
down T delay
_:16351:124 90V V.contr.gc:Function 0 min to 120 min 15 min
monitoring
_:16351:162 90V V.contr.gc:Power- • off on
flow supervision
• on
_:16351:163 90V V.contr.gc:Regulate • off on
with T2 at start
• on
_:16351:171 90V V.contr.gc:Set point • off on
mode active
• on
Line drop comp.
_:16351:125 90V V.contr.gc:Line drop • off off
compensation
• LDC-Z
• LDC-XandR
_:16351:172 90V V.contr.gc:LDC is • on target voltage on target
calculated voltage
• on measured voltage
_:16351:126 90V V.contr.gc:Target 0.0 % to 20.0 % 4.0 %
voltage rising w1
_:16351:147 90V V.contr.gc:Target 0.0 % to 20.0 % 4.0 %
voltage rising w2
_:16351:127 90V V.contr.gc:Max load 0.0 % to 500.0 % 100.0 %
current
_:16351:153 90V V.contr.gc:R line w1 0.0 Ω to 30.0 Ω 0.0 Ω
_:16351:154 90V V.contr.gc:X line w1 -30.0 Ω to 30.0 Ω 0.0 Ω

SIPROTEC 5, 7SJ82/7SJ85, Manual 1377


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

Addr. Parameter C Setting Options Default Setting


_:16351:155 90V V.contr.gc:R line w2 0.0 Ω to 30.0 Ω 0.0 Ω
_:16351:156 90V V.contr.gc:X line w2 -30.0 Ω to 30.0 Ω 0.0 Ω
Limiting
_:16351:102 90V V.contr.gc:Lower -128 to 127 1
tap-position limit
_:16351:103 90V V.contr.gc:Higher -128 to 127 15
tap-position limit
_:16351:128 90V V.contr.gc:Vmin • off on
limiting
• on
_:16351:129 90V V.contr.gc:Vmin 10.000 V to 340.000 V 105.000 V
threshold w1
_:16351:148 90V V.contr.gc:Vmin 10.000 V to 340.000 V 105.000 V
threshold w2
_:16351:130 90V V.contr.gc:Vmin 0 s to 20 s 10 s
time delay
_:16351:131 90V V.contr.gc:Vmax • off on
limiting
• on
_:16351:132 90V V.contr.gc:Vmax 10.000 V to 340.000 V 115.000 V
threshold w1
_:16351:149 90V V.contr.gc:Vmax 10.000 V to 340.000 V 115.000 V
threshold w2
_:16351:133 90V V.contr.gc:Vmax 0 s to 20 s 10 s
time delay
Blocking
_:16351:134 90V V.contr.gc:Blocking • Auto Auto-Manual
behavior
• Auto-Manual
_:16351:135 90V V.contr.gc:V< • off on
Blocking
• on
_:16351:136 90V V.contr.gc:V< 10.000 V to 340.000 V 90.000 V
Threshold w1
_:16351:150 90V V.contr.gc:V< 10.000 V to 340.000 V 90.000 V
Threshold w2
_:16351:137 90V V.contr.gc:V< Time 0 s to 20 s 0s
delay
_:16351:138 90V V.contr.gc:I> • off on
Blocking
• on
_:16351:139 90V V.contr.gc:I> 10 % to 500 % 150 %
Threshold
_:16351:140 90V V.contr.gc:I> Time 0 s to 20 s 0s
delay
_:16351:141 90V V.contr.gc:I< • off off
Blocking
• on
_:16351:142 90V V.contr.gc:I< 3 % to 100 % 10 %
Threshold
_:16351:143 90V V.contr.gc:I< Time 0 s to 20 s 10 s
delay

1378 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

8.9.6 Information List

Two-Winding Transformer and Parallel Control

No. Information Data Class Type


(Type)
General
_:2311:52 General:Behavior ENS O
_:2311:53 General:Health ENS O
90V V.contr.2w
_:14011:81 90V V.contr.2w:>Block SPS I
_:14011:85 90V V.contr.2w:>Reset min./max. SPS I
_:14011:53 90V V.contr.2w:Health ENS O
_:14011:54 90V V.contr.2w:Inactive SPS O
_:14011:339 90V V.contr.2w:Auto inactive SPS O
_:14011:52 90V V.contr.2w:Behavior ENS O
_:14011:301 90V V.contr.2w:End Higher pos. Auto SPS O
_:14011:302 90V V.contr.2w:End Lower pos. Auto SPS O
_:14011:326 90V V.contr.2w:Cmd. with feedback BSC C
_:14011:329 90V V.contr.2w:Block auto SPC C
_:14011:312 90V V.contr.2w:Operating mode SPC C
_:14011:305 90V V.contr.2w:Bandwidth > SPS O
_:14011:306 90V V.contr.2w:Bandwidth < SPS O
_:14011:307 90V V.contr.2w:Fast Step Up active SPS O
_:14011:308 90V V.contr.2w:Fast Step Down active SPS O
_:14011:309 90V V.contr.2w:Auto Monitor SPS O
_:14011:310 90V V.contr.2w:Vmin Limiting SPS O
_:14011:311 90V V.contr.2w:Vmax Limiting SPS O
_:14011:315 90V V.contr.2w:Auto Blocking SPS O
_:14011:316 90V V.contr.2w:Manual Blocking SPS O
_:14011:317 90V V.contr.2w:V< Blocking SPS O
_:14011:318 90V V.contr.2w:I> Blocking SPS O
_:14011:319 90V V.contr.2w:I< Blocking SPS O
_:14011:366 90V V.contr.2w:VT supervision SPS O
_:14011:367 90V V.contr.2w:Circul. current blocking SPS O
_:14011:320 90V V.contr.2w:V act. MV O
_:14011:333 90V V.contr.2w:Vact.m MV O
_:14011:321 90V V.contr.2w:ΔV act. MV O
_:14011:334 90V V.contr.2w:ΔVactV MV O
_:14011:335 90V V.contr.2w:ΔVactC MV O
_:14011:322 90V V.contr.2w:I load MV O
_:14011:364 90V V.contr.2w:PhAng MV O
_:14011:336 90V V.contr.2w:I load Σ MV O
_:14011:365 90V V.contr.2w:I circul. MV O
_:14011:323 90V V.contr.2w:V max MV O
_:14011:324 90V V.contr.2w:V min MV O
_:14011:325 90V V.contr.2w:V target MV O
_:14011:354 90V V.contr.2w:Target voltage 1 SPC C
_:14011:355 90V V.contr.2w:Target voltage 2 SPC C

SIPROTEC 5, 7SJ82/7SJ85, Manual 1379


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

No. Information Data Class Type


(Type)
_:14011:356 90V V.contr.2w:Target voltage 3 SPC C
_:14011:357 90V V.contr.2w:Target voltage 4 SPC C
_:14011:358 90V V.contr.2w:Set target voltage APC C
_:14011:359 90V V.contr.2w:Block T1 SPC C
_:14011:337 90V V.contr.2w:No. of master is not 1 SPS O
_:14011:338 90V V.contr.2w:Automatic block. local SPS O
_:14011:328 90V V.contr.2w:Parallel operation SPC C
_:14011:331 90V V.contr.2w:Parallel group INC C
_:14011:332 90V V.contr.2w:Force master SPC C
_:14011:360 90V V.contr.2w:Local parallel mode ENS O
_:14011:363 90V V.contr.2w:Local para. transf. id INS O
_:14011:361 90V V.contr.2w:Cause of par.op. error ENS O
_:14011:362 90V V.contr.2w:Parallel-operation error SPS O

Three-Winding Transformer

No. Information Data Class Type


(Type)
General
_:2311:52 General:Behavior ENS O
_:2311:53 General:Health ENS O
90V V.contr.3w
_:15601:81 90V V.contr.3w:>Block SPS I
_:15601:85 90V V.contr.3w:>Reset min./max. SPS I
_:15601:53 90V V.contr.3w:Health ENS O
_:15601:54 90V V.contr.3w:Inactive SPS O
_:15601:371 90V V.contr.3w:Auto inactive SPS O
_:15601:52 90V V.contr.3w:Behavior ENS O
_:15601:301 90V V.contr.3w:End Higher pos. Auto SPS O
_:15601:302 90V V.contr.3w:End Lower pos. Auto SPS O
_:15601:332 90V V.contr.3w:Cmd. with feedback BSC C
_:15601:335 90V V.contr.3w:Block auto SPC C
_:15601:336 90V V.contr.3w:Operating mode SPC C
_:15601:305 90V V.contr.3w:Bandwidth > SPS O
_:15601:306 90V V.contr.3w:Bandwidth < SPS O
_:15601:307 90V V.contr.3w:Fast Step Up active SPS O
_:15601:308 90V V.contr.3w:Fast Step Down active SPS O
_:15601:309 90V V.contr.3w:Auto Monitor SPS O
_:15601:357 90V V.contr.3w:Power-flow superv. SPS O
_:15601:310 90V V.contr.3w:Vmin Limiting w1 SPS O
_:15601:311 90V V.contr.3w:Vmin Limiting w2 SPS O
_:15601:312 90V V.contr.3w:Vmax Limiting w1 SPS O
_:15601:313 90V V.contr.3w:Vmax Limiting w2 SPS O
_:15601:314 90V V.contr.3w:Auto Blocking SPS O
_:15601:315 90V V.contr.3w:Manual Blocking SPS O
_:15601:316 90V V.contr.3w:V< Blocking w1 SPS O
_:15601:317 90V V.contr.3w:V< Blocking w2 SPS O

1380 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

No. Information Data Class Type


(Type)
_:15601:318 90V V.contr.3w:I> Blocking SPS O
_:15601:319 90V V.contr.3w:I< Blocking SPS O
_:15601:320 90V V.contr.3w:Vact.w1 MV O
_:15601:321 90V V.contr.3w:Vact.w2 MV O
_:15601:322 90V V.contr.3w:ΔV act. MV O
_:15601:323 90V V.contr.3w:I load w1 MV O
_:15601:324 90V V.contr.3w:I load w2 MV O
_:15601:325 90V V.contr.3w:Vmax 1 MV O
_:15601:326 90V V.contr.3w:Vmax 2 MV O
_:15601:327 90V V.contr.3w:Vmin 1 MV O
_:15601:328 90V V.contr.3w:Vmin 2 MV O
_:15601:329 90V V.contr.3w:V tar.w1 MV O
_:15601:330 90V V.contr.3w:V tar.w2 MV O
_:15601:358 90V V.contr.3w:Target voltage 1 w1 SPC C
_:15601:359 90V V.contr.3w:Target voltage 2 w1 SPC C
_:15601:360 90V V.contr.3w:Target voltage 3 w1 SPC C
_:15601:361 90V V.contr.3w:Target voltage 4 w1 SPC C
_:15601:362 90V V.contr.3w:Target voltage 1 w2 SPC C
_:15601:363 90V V.contr.3w:Target voltage 2 w2 SPC C
_:15601:364 90V V.contr.3w:Target voltage 3 w2 SPC C
_:15601:365 90V V.contr.3w:Target voltage 4 w2 SPC C
_:15601:366 90V V.contr.3w:Set target voltage w1 APC C
_:15601:367 90V V.contr.3w:Set target voltage w2 APC C
_:15601:368 90V V.contr.3w:Block T1 SPC C
_:15601:356 90V V.contr.3w:Winding act. INS O
_:15601:369 90V V.contr.3w:Winding selec. manual SPC C
_:15601:370 90V V.contr.3w:Winding selec. auto SPC C

Grid Coupling Transformer

No. Information Data Class Type


(Type)
General
_:2311:52 General:Behavior ENS O
_:2311:53 General:Health ENS O
90V V.contr.gc
_:16351:81 90V V.contr.gc:>Block SPS I
_:16351:85 90V V.contr.gc:>Reset min./max. SPS I
_:16351:53 90V V.contr.gc:Health ENS O
_:16351:54 90V V.contr.gc:Inactive SPS O
_:16351:371 90V V.contr.gc:Auto inactive SPS O
_:16351:52 90V V.contr.gc:Behavior ENS O
_:16351:301 90V V.contr.gc:End Higher pos. Auto SPS O
_:16351:302 90V V.contr.gc:End Lower pos. Auto SPS O
_:16351:332 90V V.contr.gc:Cmd. with feedback BSC C
_:16351:335 90V V.contr.gc:Block auto SPC C
_:16351:336 90V V.contr.gc:Operating mode SPC C

SIPROTEC 5, 7SJ82/7SJ85, Manual 1381


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.9 Voltage Controller

No. Information Data Class Type


(Type)
_:16351:305 90V V.contr.gc:Bandwidth > SPS O
_:16351:306 90V V.contr.gc:Bandwidth < SPS O
_:16351:307 90V V.contr.gc:Fast Step Up active SPS O
_:16351:308 90V V.contr.gc:Fast Step Down active SPS O
_:16351:309 90V V.contr.gc:Auto Monitor SPS O
_:16351:357 90V V.contr.gc:Power-flow superv. SPS O
_:16351:310 90V V.contr.gc:Vmin Limiting w1 SPS O
_:16351:311 90V V.contr.gc:Vmin Limiting w2 SPS O
_:16351:312 90V V.contr.gc:Vmax Limiting w1 SPS O
_:16351:313 90V V.contr.gc:Vmax Limiting w2 SPS O
_:16351:314 90V V.contr.gc:Auto Blocking SPS O
_:16351:315 90V V.contr.gc:Manual Blocking SPS O
_:16351:316 90V V.contr.gc:V< Blocking w1 SPS O
_:16351:317 90V V.contr.gc:V< Blocking w2 SPS O
_:16351:318 90V V.contr.gc:I> Blocking SPS O
_:16351:319 90V V.contr.gc:I< Blocking SPS O
_:16351:320 90V V.contr.gc:Vact.w1 MV O
_:16351:321 90V V.contr.gc:Vact.w2 MV O
_:16351:322 90V V.contr.gc:ΔV act. MV O
_:16351:323 90V V.contr.gc:I load w1 MV O
_:16351:324 90V V.contr.gc:I load w2 MV O
_:16351:325 90V V.contr.gc:Vmax 1 MV O
_:16351:326 90V V.contr.gc:Vmax 2 MV O
_:16351:327 90V V.contr.gc:Vmin 1 MV O
_:16351:328 90V V.contr.gc:Vmin 2 MV O
_:16351:329 90V V.contr.gc:V tar.w1 MV O
_:16351:330 90V V.contr.gc:V tar.w2 MV O
_:16351:358 90V V.contr.gc:Target voltage 1 w1 SPC C
_:16351:359 90V V.contr.gc:Target voltage 2 w1 SPC C
_:16351:360 90V V.contr.gc:Target voltage 3 w1 SPC C
_:16351:361 90V V.contr.gc:Target voltage 4 w1 SPC C
_:16351:362 90V V.contr.gc:Target voltage 1 w2 SPC C
_:16351:363 90V V.contr.gc:Target voltage 2 w2 SPC C
_:16351:364 90V V.contr.gc:Target voltage 3 w2 SPC C
_:16351:365 90V V.contr.gc:Target voltage 4 w2 SPC C
_:16351:366 90V V.contr.gc:Set target voltage w1 APC C
_:16351:367 90V V.contr.gc:Set target voltage w2 APC C
_:16351:368 90V V.contr.gc:Block T1 SPC C
_:16351:356 90V V.contr.gc:Winding act. INS O
_:16351:369 90V V.contr.gc:Winding selec. manual SPC C
_:16351:370 90V V.contr.gc:Winding selec. auto SPC C

1382 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Control Functions
8.10 Point-on-Wave Switching

8.10 Point-on-Wave Switching


The Point-on-wave switching function in SIPROTEC 5 is used to reduce increased electrodynamic and dielec-
tric loads which are caused by non-optimal switching of circuit breakers in the network. In extreme cases,
these loads reduce the reliability and life of the equipment installed in the network or lead to unnecessary
opening operations by the protection device. To avoid effects such as overvoltages and inrush currents, this
function can control the closing and opening instants of circuit breakers.

Table 8-32 Avoided Effects in Different Load Types

Load Type Switching Operation Avoided Effect


Inductive load: Opening Restriking, overvoltage
Transformer, reactance coil Closing Inrush current
Capacitive load: Opening Restriking, overvoltage
Capacitor bank, unloaded lines/cables, filter Closing Overvoltage, inrush current

The Point-on-wave switching function is always started via a control command, either from the device
internal control or from an external control function. Protection functions generally directly trip the circuit
breaker and have no interaction with the Point-on-wave switching function.
You can find more information about this function in the Point-on-Wave Switching Function Manual.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1383


C53000-G5040-C017-A, Edition 06.2019
1384 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
9 Supervision Functions

9.1 Overview 1386


9.2 Resource-Consumption Supervision 1387
9.3 Supervision of the Secondary System 1392
9.4 Supervision of the Device Hardware 1443
9.5 Supervision of Device Firmware 1448
9.6 Supervision of Hardware Configuration 1449
9.7 Supervision of Communication Connections 1450
9.8 Error Responses and Corrective Measures 1451
9.9 Group Indications 1460

SIPROTEC 5, 7SJ82/7SJ85, Manual 1385


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.1 Overview

9.1 Overview
SIPROTEC 5 devices are equipped with an extensive and integrated supervision concept. Continuous supervi-
sion:

• Ensures the availability of the technology used

• Avoids subfunction and overfunction of the device

• Protects persons and primary technical devices

• Offers effective assistance during commissioning and testing


The following areas are monitored:

• Supervision the resource consumption of the application

• Supervision of the secondary system, including the external auxiliary power supply

• Supervision of device hardware

• Supervision of device firmware

• Supervision of hardware configuration

• Supervision of communication connections


When the supervision functions pick up, that will be displayed and also indicated. Error responses are defined
for the device. The error responses are grouped in defect severities.
The supervision functions work selectively. When the supervision functions pick up - as far as possible - only
the affected parts of the hardware and firmware are blocked. If this is not possible, the device goes out of
operation into a secure state (fallback mode). In addition to safety, this warrants a high degree of availability.

1386 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.2 Resource-Consumption Supervision

9.2 Resource-Consumption Supervision

9.2.1 Load Model

SIPROTEC 5 devices are freely configurable. A load model is integrated in DIGSI 5. The load model prevents you
from overloading the device with an excessively large application.
The load model shows the device utilization and the response times for device functions. If it determines that
an application created is likely to overload the device, DIGSI prevents the application from being loaded into
the device.
In this rare case, you must then reduce the application in order to be able to load it into the device.
The load model can be found in the DIGSI 5 project tree under Name of the device → Device information. In
the operating range, select the Resource consumption setting sheet. The following figure shows an example
of the view of the load model in DIGSI 5:

[sclasjsk-291112-01.tif, 1, en_US]

Figure 9-1 Visualization of the Load Model in DIGSI

A green total display for the processor response time indicates that the device is not overloaded by the present
application. On the other hand, if you see a red exclamation mark, the planned application is overloading the
device.
The list below the total display shows the individual functional areas. These areas combine functions with the
same real-time requirements in groups. A green display in front of an area (see Figure 9-1) indicates that the
response times of the functions grouped in this area can be maintained. A red exclamation point indicates that
functions may have longer response times than are specified in the Technical data for the device. In such a
case, loading of the application into the device is blocked.
The following table provides an overview of the functional areas and the most important influencing quanti-
ties on device utilization:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1387


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.2 Resource-Consumption Supervision

Functional Brief Description Change in Load


Area
CFC event-trig- CFC charts that must be Adding or removing CFC charts in the fast event-triggered
gered, fast processed especially fast (for process range
example, to invoke interlock-
ings between protection func-
• Create CFC chart
tions) • Delete CFC chart
• Change the process range in the properties of the CFC
chart
Add to or remove from CFC charts in the fast event-trig-
gered process area
Measuring Provision of measured values Adding or removing
points for protection, control, and
measurement functions
• Measuring points (in the Measuring-points routing
Editor)
• Function groups that provide measured-value prepro-
cessing for insertable functions (for example, Line
function group and Circuit-breaker function group)
• FG • Interaction between indi- Adding or removing
connec- vidual function groups, for
tions example, between the
• Protection functions and their stages
• Fast Line function group and • Circuit-breaker function groups
GOOSE the Circuit-breaker func- • Fast GOOSE connections
tion group
• Fast GOOSE communica-
tion
Protection Signal transmission via protec- Adding or removing
Communica- tion communication and differ-
tion ential protection communica-
• Communication modules for the protection interface
(in the DIGSI 5 Hardware and logs view)
tion
• Routings to the protection interface
Function Function Groups Adding or removing function groups such as:
Groups
• FG V/I 3-phase
Overcurrent Overcurrent protection Adding or removing
protection
• Overcurrent protection, phases
• Overcurrent protection, ground
Measuring • Measuring-point supervi- Adding or removing measuring points or individual super-
point super- sion functions vising functions, such as
vising func-
tion, protec-
• Scope of the data trans- • 3-phase current measuring point
mission via the protection
tion communi- communication
• 3-phase voltage measuring point
cation • Measuring-voltage failure detection
Add to or remove from transmission values via the protec-
tion communication

• Single-point indications
• Measured values
Other protec- Protection functions with low Adding or removing
tion requirements for fast operate
times
• Overload protection functions
• Functions and stages of voltage protection
• All functions not listed previously

1388 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.2 Resource-Consumption Supervision

Functional Brief Description Change in Load


Area
CFC event-trig- CFC charts with a maximum Adding or removing CFC charts in the event-triggered
gered, processing time of 40 ms process range
standard
GOOSE
• Create CFC chart
• Delete CFC chart
• Change the process range in the properties of the CFC
chart
Add to or remove from CFC charts in the event-triggered
process area
• Control • Control and interlocking Adding or removing
• Other • CFC charts in the area of • Function blocks for control and interlocking
contin- control, measured-value
uous preprocessing, and event-
• CFC charts in the control area
function controlled • Switching devices (except circuit breakers), for
chart example, Disconnector function groups
• Operational measured
• Opera- values • Operational measured values
tional • CFC charts in the measured values area
measured
values

If the load model displays a warning, bear in mind the following general instructions:
The areas named in the table are listed in descending order of real time requirements. If a warning appears to
the effect that the guaranteed response times may be exceeded in an area, you can return to the permitted
area by taking the following measures:

• Reduce the functional scope in the marked area (red exclamation mark)

• Reduce the functional scope in another area with higher real time requirements
When you have reduced the application, check the display in resource consumption! If a function or stage has
been switched off, it will continue to represent a load for the area. If you do not need the function or stage,
delete it rather than switching it off.
Use the general Circuit-breaker function group only in the following cases:

• Interaction with a protection-function group is essential.


That is, operate indications of protection functions cause the circuit breaker assigned to the Circuit-
breaker function group to be switched off.

• You want to use functions such as the automatic reclosing function or circuit-breaker failure protection in
the Circuit-breaker function group.
If a circuit breaker is only to be modeled for control purposes, use the Circuit breaker [state only] function
group.

9.2.2 Function Points

When you order a SIPROTEC 5 device, you are also ordering a function-points account for use of additional
functions.
The following figure illustrates consumption of function points in the current application with respect to the
existing function-points account.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1389


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.2 Resource-Consumption Supervision

[scfpunkt-141210-01, 1, en_US]

Figure 9-2 Resource Overview: Function-Points Consumption

The remaining white bar shows the function points that have not yet been used up by your configuration. The
number of function points available in a device depends on the device purchase order (position 20 of the
product code). You can also order function points subsequently, and so increase the function-points account
for the device.

NOTE

i Find out the function-points requirement for the desired application before ordering the device. For this,
you can use the device configurator.

9.2.3 CFC Resources

Task Levels of the CFC Function


A CFC chart, and thus the configured CFC function, runs in the SIPROTEC 5 device on exactly one of the 4 task
levels. The individual task levels differ, on the one hand, in the priority of processing tasks and, on the other,
in the cyclic or event-triggered processing of the CFC charts.
You can select between the following task levels:
Task Level Description
Fast Event-Triggered Use the Fast Event-Triggered task level for time-critical tasks, for
example, if a signal should block a protection function within 2 ms to 3 ms.
Functions on this task level are processed in an event-triggered way with
the highest priority. Each change to a logical input signal is immediately
processed. Processing can interrupt the execution of protection functions
and functions on the Event-Triggered task level.
Event-Triggered Use the Event-Triggered task level preferably for logic functions that
need not be executed with highest priority. Each change to a logical input
signal is immediately processed. Protection functions or functions on the
Fast event-triggered task level can disrupt processing.
Functions on the Event-Triggered task level are typically processed
within a maximum of 5 ms in all devices. For busbar protection or line
protection, the functions on the Event-Triggered task level are
processed within a maximum of 10 ms.
Measurement Use the Measurement task level for processing measured values. Functions
on this task level are processed cyclically every 500 ms.
Interlocking Use the Interlocking task level preferably for logic functions that should
be executed with lower priority than functions in the Event-Triggered
task level. If the available ticks of the Event-Triggered task level shown
in the following figure are sufficient for the required CFC functionality, you
do not need to use the Interlocking task level.

All CFC function blocks can be assigned to all the task levels. There are no device-specific function blocks. If
enough ticks are available, all CFC charts can be created in the same task level. A tick is the measure of the
performance requirement of CFC blocks.
The number of available ticks for each task is calculated depending on the created device configuration. This
calculation is based on the previously described load model. In this process, it is recommended to create all

1390 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.2 Resource-Consumption Supervision

selected functions and objects first followed by configuration of the CFC charts so that a realistic information
about the remaining system capacitance for CFC charts is available. Significantly exceeding the typical
response time is prevented by the load model by limiting the number of CFC function blocks in the corre-
sponding task level via the number of ticks available.
The typical response times for CFC tasks are listed in the Technical Data.
The following figure shows an example of the CFC chart capacitances in DIGSI calculated by the load model.
The ticks available for each task are shown here. The green bars represent the ticks used in the task levels. You
reach this dialog with the following call: Device → Device information → Resource consumption.

[sc-cfc-statistic, 1, en_US]

Figure 9-3 CFC Statistics

NOTE

i The fast-event-triggered CFC charts have the highest priority and are processed before all other tasks. At
this level, a considerable smaller number of ticks are available than at all other tasks. It is recommended to
configure only very-high-priority logic functions at this task and to configure the other logic functions in
any other level.

NOTE

i Empty CFC charts also consume system resources. Empty charts that are not required any more should be
deleted.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1391


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3 Supervision of the Secondary System

9.3.1 Overview

The secondary circuits establish a connection to the power system from the point of view of the device. The
measuring-input circuit (currents, voltages) as well as the command circuits to the circuit breakers are moni-
tored for the correct function of the device. The connection to the station battery is ensured with the supervi-
sion of the external auxiliary voltage. The secondary system has the following supervision systems:
Measuring circuits (voltage):

• Measuring-voltage failure

• Voltage-transformer circuit breaker

• Voltage balance

• Voltage sum

• Voltage rotating field


Measuring circuits (current):

• Broken conductor of the current circuits

• Current balance

• Current sum

• Current rotating field

Trip circuits
When the supervisions listed in the previous section pick up, corresponding warning indications are output.
Some supervisions lead directly to the blocking of affected protection functions or to the marking of meas-
uring points that have become invalid, so that affected protection functions can go into a secure state.
A detailed description of the supervision mechanisms and their error responses can be found in the respective
function descriptions.

External auxiliary voltage


The supervision of the external auxiliary voltage is described in the subchapter Error Responses and Corrective
Measures starting at 9.8.1 Overview.

9.3.2 Measuring-Voltage Failure

9.3.2.1 Overview of Functions


The Measuring-voltage failure detection function monitors the voltage transformer secondary circuits:

• Non-connected transformers

• Pickup of the voltage transformer circuit breaker (in the event of short circuits in the secondary circuit)

• Broken conductor in one or more measuring loops


All these events cause a voltage of 0 in the voltage transformer secondary circuits which can lead to failures of
the protection functions.
Each of the following protection functions has the parameter Blk. by meas.-volt. failure. With the
setting value of the parameter, you can specify whether the protection functions react to a measuring-voltage
failure or not (block/not block).

• Directional Overcurrent Protection, Phases

• Overvoltage Protection with Negative-Sequence Voltage

1392 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

• Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

• Undervoltage Protection with 3-Phase Voltage

• Overvoltage Protection with Positive-Sequence Voltage

• Voltage-Dependent Overcurrent Protection, Phases

• Overvoltage Protection with Negative-Sequence Voltage

• Overvoltage Protection with Positive-Sequence Voltage

• Undervoltage-Controlled Reactive-Power Protection


The following protection functions are automatically blocked in the case of a measuring-voltage failure:

• Distance protection

• Directional Negative-Sequence Protection

• Ground-Fault Protection for High-Resistance Ground Faults in Grounded Systems

9.3.2.2 Structure of the Function


The function is part of protection function groups which are connected with a 3-phase voltage and current
measurement point.

[dwstrffm-210113-01.tif, 1, en_US]

Figure 9-4 Structure/Embedding of the Function

The function is broken down into 3 subfunctions (see Figure 9-5):

• Supervision for unbalanced measuring-voltage failure

• Supervision for 3-phase measuring-voltage failure

• Supervision for switching onto a 3-phase measuring-voltage failure

SIPROTEC 5, 7SJ82/7SJ85, Manual 1393


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

[lozusamm-100611-01.tif, 2, en_US]

Figure 9-5 Breakdown of the Measuring-Voltage Failure Detection Function

Each subfunction creates its own monitoring indication. The function summarizes these indications via the
group indication Alarm.
The response to the detection of a measuring-voltage failure is explained in the specific protection-function
descriptions.

1394 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.2.3 Unbalanced Measuring-Voltage Failure

Logic

[looppode-200812-05.tif, 3, en_US]

Figure 9-6 Logic Diagram Unbalanced Measuring-Voltage Failure Detection

The criterion for detection of an unbalanced measuring-voltage failure is the voltage unbalance. This unbal-
ance is determined based on the ratio between negative and positive-sequence voltage. If the threshold value
is exceeded and the monitoring is released and not blocked, the monitoring picks up (see Figure 9-6). The
indication Asym.fail.-inst.alarm is output.
The monitoring is released as soon as a certain minimum voltage is exceeded. This prevents a spurious
response in the presence of low voltage measurands or a measurand of 0 (for example, circuit breaker open).
Instantaneous monitoring also requires the presence of a minimum current. This prevents a spurious instanta-
neous pick up of the monitoring in the presence of a weak infeed (current < 10 % of rated current) combined
with a power-system incident.
If the voltage unbalance is blocked by unbalanced faults in the primary system, the supervision is blocked. The
device detects an unbalanced fault based on the ratio between negative-sequence and positive-sequence
current.

Delay/Seal-In
In the presence of a weak infeed (current < 10 % of rated current), certain protection functions require more
time for detection of a system incident. For this purpose, the monitoring can be delayed using the
Asym.fail. - time delay parameter.
If a system incident is detected during the time delay, the supervision drops off. This is because the function
assumes that the unbalance - and consequently the pickup of the supervision - is due to the system incident.
After the time delay has elapsed, it definitely assumes a measuring-voltage failure. The monitoring seals in
and the Asym.fail.-alarm indication is output. The dropout does not happen until the voltage unbalance
has disappeared after a seal-in time of 10 s. In the presence of 3-pole close-in faults outside the protection
zone, this seal-in time prevents the monitoring from dropping off too quickly and thus releasing the protection
functions.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1395


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

The sealing-in function can be deactivated using the Asym.fail.-DO on netw.flt. parameter. As soon
as a system incident is detected, the monitoring drops off instantaneously.

9.3.2.4 3-Phase Measuring-Voltage Failure

Logic

[losymmet-190912-01.tif, 1, en_US]

Figure 9-7 Logic Diagram 3-Phase Measuring-Voltage Failure

Balanced Fault – VA, VB, VC <


A 3-phase measuring-voltage failure is detected if the following criteria are fulfilled simultaneously:

• All 3 phase-to-ground voltages drop below the threshold value 3ph.fail. - VA,VB,VC <

• A jump of the voltage (signal Jump V)


If these criteria are fulfilled and the monitoring is released and not blocked, the 3ph.failure-alarm indica-
tion is output. When the voltage returns (even as 1-phase), the monitoring drops out.

Release by Phase Current


When all phase currents exceed the threshold value 3ph.fail. - phs.curr.release the monitoring is
released.

1396 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Blocking in the Case of a System Incident


In the case of a 3-phase system incident, supervision must be blocked. The device detects a 3-phase system
incident with a jump in the current. This change is detected via the internal signal Jump I or when the
change in current of a phase current exceeds the threshold value 3ph.fail. - phs.curr. jump. The
change in current of phase currents is formed from the difference between the present current phasor and the
current phasor of the previous period. This allows to take into account a jump of the current phase.

NOTE

i If a voltage-transformer circuit breaker is installed in the secondary circuit of the voltage transformers, its
position is communicated to the device via a binary input (see chapter 9.3.4.1 Overview of Functions).

9.3.2.5 Switching onto a 3-Phase Measuring-Voltage Failure, Low Load

Logic

[lozuscha-100611-01.tif, 1, en_US]

Figure 9-8 Logic Diagram Switching to 3-Phase Measuring-Voltage Failure

Switching onto a 3-phase measuring-voltage failure is detected if the following criteria are fulfilled simultane-
ously:

• All 3 phase-to-ground voltages have dropped below the threshold value 3ph.fail. - VA,VB,VC <.

• The circuit breaker is detected to be in closed position. The detection takes place either via the phase
currents or via the ≥1-pole closed signal, which is generated via the circuit-breaker auxiliary contacts.
You can find more detailed information in chapter 5.8.5 Circuit-Breaker Condition for the Protected
Object.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1397


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

A voltage jump – such as in a 3-phase measuring-voltage failure with closed circuit breaker (see chapter
9.3.2.4 3-Phase Measuring-Voltage Failure) – does not occur in the case of switching to a 3-phase measuring-
voltage failure. If the monitoring is not blocked, the time delay SO 3ph.fail. - time delay is started.
After the time has elapsed, the indication SO 3ph.failure-alarm is displayed. A dropout of the moni-
toring is only possible by a recovery of the voltage.
The supervision is blocked as soon as a pickup of a protection function is detected within a protection function
group and the time delay of the supervision has not yet elapsed.
This subfunction also covers the situation of a low load with 3-phase measuring-voltage failure and closed
circuit breaker, because the circuit-breaker condition is also determined from the circuit-breaker auxiliary
contacts. The subfunction for detecting a 3-phase measuring-voltage failure (see chapter 9.3.2.4 3-Phase
Measuring-Voltage Failure) is not released in this situation, for example, because the current flow is too low.
This subfunction can be switched on or off separately using the Switch-on 3ph. failure parameter.

9.3.2.6 Application and Setting Notes

Parameter: Asym.fail. - time delay

• Recommended setting value (_:113) Asym.fail. - time delay = 10.00 s


The Asym.fail. - time delay parameter allows you to set the time during which a system incident
detected after the occurrence of the unbalance resets the monitoring. This setting is important in the case of
weak infeed (current < 10 % of rated current) in order to give certain protection functions (such as distance
protection) more time for detecting system incidents. As long as the time delay runs, it is assumed that the
unbalance is due to a system incident.
As soon as the time has elapsed, the supervision assumes a measuring-voltage failure and seals in.
Siemens recommends using the default setting.
If you want the seal-in function to operate sooner or at once, you can reduce the time.

Parameter: Asym.fail.-DO on netw.flt.

• Recommended setting value (_:115) Asym.fail.-DO on netw.flt. = No

Parameter Value Description


no After elapse of the time delay the supervision function seals in. Even if the
system incident criterion is fulfilled, the protection functions concerned will
remain blocked.
This avoids an unselective tripping of the protection functions due to an
absence of the measuring voltage in the case of an unbalanced system inci-
dent.
This is the default setting.
yes The seal-in function is switched off. The supervision drops out immediately
when a system incident is detected. With this setting, the unbalanced meas-
uring-voltage failure is only reported, and in the event of a double failure
(measuring-voltage failure and system incident in parallel), unselective trip-
ping is preferred.

Parameter: 3ph.fail. - VA,VB,VC <

• Recommended setting value (_:101) 3ph.fail. - VA,VB,VC < = 5 V


The 3ph.fail. - VA,VB,VC < parameter allows you to set the pickup value of the monitoring.
Siemens recommends using the default setting.
If you expect major disturbances acting upon the voltage inputs, you can increase this value. Increasing the
values makes the supervision more sensitive to 3-phase system incidents.

1398 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Parameter: 3ph.fail. - phs.curr.release

• Recommended setting value (_:102) 3ph.fail. - phs.curr.release = 0.1 A for Irated = 1 A or


0.5 A for Irated = 5 A

The 3ph.fail. - phs.curr.release parameter is used to define the phase current threshold above
which the monitoring is released.
Siemens recommends using the default setting.

Parameter: 3ph.fail. - phs.curr. jump

• Recommended setting value (_:103) 3ph.fail. - phs.curr. jump = 0.1 A for Irated = 1 A or
0.5 A for Irated = 5 A

The 3ph.fail. - phs.curr. jump parameter is used to set the differential current between the present
current phasor and the stored phasor (from the previous period). If the value is exceeded, the function detects
a system incident and blocks the monitoring.
Siemens recommends using the default setting.

Parameter: SO 3ph.fail. - time delay

• Recommended setting value (_:106) SO 3ph.fail. - time delay = 3.00 s


The SO 3ph.fail. - time delay parameter allows you to set the delay of the monitoring.
Siemens recommends using the default setting.

NOTE

i Adapt the SO 3ph.fail. - time delay parameter to the inherent time of protection functions which
are intended to block the monitoring function.
Note that with parameter values 0 s blocking of the monitoring function via a protection stimulation will
not be possible any more.

Parameter: Switch-on 3ph. failure

• Recommended setting value (_:107) Switch-on 3ph. failure = on

Parameter Value Description


on The subfunction Switching to a 3-phase measuring-voltage failure is
active.
In the case of low loads, the subfunction for detection of a 3-phase meas-
uring-voltage failure is not released, for example, because the current flow
is too low. In this situation, the subfunction Switching to a 3-phase meas-
uring-voltage failure can perform the monitoring task.
Siemens recommends to switch that subfunction on.
off With the setting off the subfunction Switching to a 3-phase measuring-
voltage failure is not active.

9.3.2.7 Settings

Addr. Parameter C Setting Options Default Setting


Mes.v.fail.det
_:1 Mes.v.fail.det:Mode • off on
• on
• test
_:115 Mes.v.fail.det:Asym.fail.- • no yes
DO on netw.flt.
• yes

SIPROTEC 5, 7SJ82/7SJ85, Manual 1399


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Addr. Parameter C Setting Options Default Setting


_:113 Mes.v.fail.det:Asym.fail. 0.00 s to 30.00 s 10.00 s
- time delay
_:102 Mes.v.fail.det:3ph.fail. - 1 A @ 100 Irated 0.030 A to 35.000 A 0.100 A
phs.curr.release 5 A @ 100 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:103 Mes.v.fail.det:3ph.fail. - 1 A @ 100 Irated 0.030 A to 35.000 A 0.100 A
phs.curr. jump 5 A @ 100 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:101 Mes.v.fail.det:3ph.fail. - 0.300 V to 340.000 V 5.000 V
VA,VB,VC <
_:107 Mes.v.fail.det:Switch-on • off on
3ph. failure
• on
_:106 Mes.v.fail.det:SO 0.01 s to 30.00 s 3.00 s
3ph.fail. - time delay

9.3.2.8 Information List

No. Information Data Class Type


(Type)
Mes.v.fail.det
_:82 Mes.v.fail.det:>Block function SPS I
_:54 Mes.v.fail.det:Inactive SPS O
_:52 Mes.v.fail.det:Behavior ENS O
_:53 Mes.v.fail.det:Health ENS O
_:300 Mes.v.fail.det:Alarm SPS O
_:304 Mes.v.fail.det:Asym.fail.-inst.alarm SPS O
_:303 Mes.v.fail.det:Asym.fail.-alarm SPS O
_:301 Mes.v.fail.det:3ph.failure-alarm SPS O
_:302 Mes.v.fail.det:SO 3ph.failure-alarm SPS O

9.3.3 Signaling-Voltage Supervision

9.3.3.1 Overview of Functions


Signaling-voltage supervision is used to evaluate the validity of binary signals connected to the SIPROTEC
device via binary inputs. For this purpose, one binary input is used to monitor the signaling voltage. If the
signaling voltage fails, the associated binary signals are marked as invalid and a Signaling-voltage malfunc-
tion indication is issued.
Several signaling-voltage supervision groups can be created in one SIPROTEC device. Each of these groups
monitors an adjustable area with binary inputs.

9.3.3.2 Structure of the Function


The Signaling-voltage supervision function group contains, besides the general functionality, one preinstan-
tiated Supervision group stage. The Supervision group stage can be instantiated in DIGSI 5 multiple times.

1400 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

[dwivsstr-060214-01.vsd, 1, en_US]

Figure 9-9 Structure/Embedding of the Function Group

9.3.3.3 Function Description


You can instantiate the Signaling-voltage supervision function group in the Global DIGSI 5 library. It
contains 1 pre-instantiated Superv.Grp. function block (see the following figure). You can instantiate a
maximum of 25 supervision groups.

[sc_ivslib, 1, en_US]

Figure 9-10 Entry in the Global Library

Following the instantiation of the function group in the DIGSI project tree, it appears in the information
routing of DIGSI (see the following figure). The status indications of the supervision groups can be routed
here, for example, to existing binary outputs and/or logs.

[sc_ivsrou, 1, en_US]

Figure 9-11 Information Routing

Set the binary input used for signaling-voltage supervision within one input/output module using the setting
option (see the following figure). This binary input monitors the presence of the signaling voltage. If the
signaling voltage fails, this sets the quality attribute for all other binary inputs of the parameterized input/
output module to invalid. The signal status of each of these binary inputs is frozen with its last valid value
prior to the occurrence of the fault. The quality attribute of the binary inputs for other input/output modules
are not taken into consideration by this.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1401


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

If the signaling voltage again exceeds the binary threshold, the quality attribute of the binary inputs is reset to
valid.

[sc_ivsgrp, 2, en_US]

Figure 9-12 Parameterization Menu of the Supervision Group (I)

NOTE

i Each status change of the monitored binary inputs is delayed by 3 ms.

You can also combine binary inputs across modules in one Superv.Grp. function block and define any
binary input within this group for supervision of the signaling voltage. For this purpose, place a check mark at
the parameter (_:102) Enable variable group when configuring the supervision group. This extends
the parameterization menu by the sections Supervis. grp. start and Supervis. grp. end (see the
following figure).

[sc_gruppe_de, 2, en_US]

Figure 9-13 Parameterization Menu of the Supervision Group (II)

There, for example, you are able to combine 1 to n different binary inputs into one supervision group. When
doing so, the binary inputs on the input/output modules assignable to a supervision group must be related
logically. With 3 input/output modules, for example, this allows only consecutive binary inputs to be grouped
on the modules 1 and 2 or 2 and 3, but no binary inputs on modules 1 and 3. The binary inputs used for super-
vision can be located on any input/output module within the group defined in this manner.

1402 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

If you have to monitor several binary inputs that, for example, work with different signaling voltages from
different sources, then you can also instantiate and configure several Superv.Grp. function blocks within
the Signaling-voltage supervision function group accordingly.
Within different supervision groups, only those consecutive binary inputs that are not already assigned to
another supervision group can be grouped. The overlapping of binary inputs in different supervision groups is
not permitted.
Error parameters are displayed to you by inconsistency indications in DIGSI.

Example
There are 4 input/output modules available.
Binary inputs of input/output modules 1 and 2 are already combined in supervision group 1. The 2 last binary
inputs on module 2 are not included in the grouping.
In supervision group 2, only these 2 binary inputs of the input/output module 2 not used in supervision group
1 as well as further consecutive binary inputs of the input/output modules 3 and 4 can be combined.

9.3.3.4 Application and Setting Notes

Parameter (General): Mode

• Default setting (_:1) Mode = on


With the Mode parameter, you specify whether you want to activate, deactivate, or test the supervision of the
signaling voltage for the appropriate group. If you put the group into test mode, the Sig. volt.
disturbed indication is given a test flag. If the supervision input drops out in test mode, the assigned inputs
retain their status without their quality attribute being set to invalid.

Parameter (Supervision Signal): I/O module ID

• Default setting (_:104) I/O module ID = I/O module 1


Using the I/O module ID parameter, you specify the I/O module for which you want to activate signaling-
voltage supervision. Counting of the I/O modules starts in increasing order with the binary inputs of the base
module. The binary inputs of the PS201 power-supply module permanently installed in the base module count
as the 2nd I/O module followed by additional I/O modules (3 to n) in the expansion boards of the device.

Parameter (Supervision Signal): Binary input

• Default setting (_:105) Binary input = 1


Using the Binary input parameter, you specify the binary input responsible for the supervision of the
signaling voltage for the parameterized I/O module. The quality attribute of all other binary inputs for this
module are set to valid or invalid depending on the presence of the signaling voltage at the parameterized
binary input.

Parameter (Supervision Signal): Enable variable group

• Default setting (_:102) Enable variable group = untrue


You can activate the parameter Enable variable group by placing the check mark. If you have not set
the check mark (default setting), only these 2 parameters are available for the configuration of the supervision
signal. If you have set the check mark, the parameter menu is extended by the areas Start supervision group
and End supervision group. You can then use that to carry out the grouping of binary inputs for supervision
groups explained in the function description.

Parameter (Start Supervision Group): I/O module ID

• Default setting (_:106) I/O module ID = I/O module 1

SIPROTEC 5, 7SJ82/7SJ85, Manual 1403


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Parameter I/O module ID is used to define the first I/O module that you want to assign to a supervision
group. As the counting of the I/O module starts in ascending order with the binary inputs of the base module,
this is the module with the lowest counter number that you can use for carrying out a grouping.

Parameter (Start Supervision Group): Binary input

• Default setting (_:107) Binary input = 1


Parameter Binary input is used to define the lowest binary input for the first I/O module (see (_:106)
I/O module ID) that you want to assign to a supervision group.

Parameter (End Supervision Group): I/O module ID

• Default setting (_:108) I/O module ID = I/O module 1


Parameter I/O module ID is used to define the last I/O module that you want to assign to a supervision
group. As the counting of the I/O module starts in ascending order with the binary inputs of the base module,
this is the module with the highest counter number that you can use for carrying out a grouping.

Parameter (End Supervision Group): Binary input

• Default setting (_:109) Binary input = 1


Parameter Binary input is used to define the highest binary input for the last I/O module (see (_:108)
I/O module ID) that you want to assign to a supervision group.

9.3.3.5 Settings

Addr. Parameter C Setting Options Default Setting


General
_:1 Superv.Grp.#:Mode • off on
• on
• test
Superv. signal
_:104 Superv.Grp.#:I/O module • I/O module 1 I/O module 1
ID
• I/O module 2
• I/O module 3
• I/O module 4
• I/O module 5
• I/O module 6
• I/O module 7
• I/O module 8
• I/O module 9
• I/O module 10
• I/O module 11
• I/O module 12
• I/O module 13
• I/O module 14
• I/O module 15
_:105 Superv.Grp.#:Binary 1 to 256 1
input
_:102 Superv.Grp.#:Enable • 0 false
variable group
• 1

1404 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Addr. Parameter C Setting Options Default Setting


Supervis. grp. start
_:106 Superv.Grp.#:I/O module • I/O module 1 I/O module 1
ID
• I/O module 2
• I/O module 3
• I/O module 4
• I/O module 5
• I/O module 6
• I/O module 7
• I/O module 8
• I/O module 9
• I/O module 10
• I/O module 11
• I/O module 12
• I/O module 13
• I/O module 14
• I/O module 15
_:107 Superv.Grp.#:Binary 1 to 256 1
input
Supervis. grp. end
_:108 Superv.Grp.#:I/O module • I/O module 1 I/O module 1
ID
• I/O module 2
• I/O module 3
• I/O module 4
• I/O module 5
• I/O module 6
• I/O module 7
• I/O module 8
• I/O module 9
• I/O module 10
• I/O module 11
• I/O module 12
• I/O module 13
• I/O module 14
• I/O module 15
_:109 Superv.Grp.#:Binary 1 to 256 1
input

9.3.3.6 Information List

No. Information Data Class Type


(Type)
Superv.Grp.#
_:52 Superv.Grp.#:Behavior ENS O
_:55 Superv.Grp.#:Sig. volt. disturbed SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1405


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.4 Voltage-Transformer Circuit Breaker

9.3.4.1 Overview of Functions


The Voltage-transformer circuit breaker function detects the tripping of the voltage-transformer circuit
breaker due to short circuits in the voltage-transformer secondary circuits.
The Voltage-transformer circuit breaker function works independently of Measuring-voltage failure detec-
tion and should be used – if possible – in parallel to it.
The tripping of the voltage-transformer circuit breaker has an impact on the quality of the recorded measured-
value data (see chapter 3.4 Processing Quality Attributes).
The following protection function is automatically blocked if the voltage-transformer circuit breaker trips:

• Directional negative-sequence protection


For the following functions the reaction (block/not block) can be set within the function in cases of a tripping
of the voltage-transformer circuit breaker:

• Directional overcurrent protection, phases

• Directional overcurrent protection, ground

• Directional sensitive ground-fault detection

• Overvoltage protection with negative-sequence voltage

• Overvoltage protection with zero-sequence voltage/residual voltage

• Undervoltage protection with 3-phase voltage

• Undervoltage protection with positive-sequence voltage

9.3.4.2 Structure of the Function


The Figure 9-14 shows the position of the function in the device. Every voltage measuring point contains the
Voltage-transformer circuit breaker function.

[dwmcbstr-040211-01.tif, 1, en_US]

Figure 9-14 Structure/Embedding of the Function

9.3.4.3 Function Description


The tripping of the voltage-transformer circuit breaker is captured via the binary input signal >Open. With an
active input signal the information about the measuring-voltage failure is relayed to the affected functions
(see 9.3.4.1 Overview of Functions). The response to the detection of a measuring-voltage failure is explained
in the specific protection-function descriptions.

Response Time of the Voltage-Transformer Circuit Breaker


The response time of the voltage-transformer circuit breaker can be slower than the pickup time of the
distance protection. This bears the risk of an overfunction. The response time is communicated to the device
with the Response time parameter. For a timely detection of the tripping of the voltage-transformer circuit
breaker, the pickup of the distance protection is delayed by that response time.

9.3.4.4 Application and Setting Notes


The function is always active and need not be switched on.

1406 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Input Signal: >Open

• Input signal: (_:500) >Open


The input signal >Open must be connected to the tripping of the voltage-transformer circuit breaker. As a rule,
this occurs via the routing to a binary input.

Parameter: Response time of the voltage-transformer circuit breaker

• Recommended setting value (_:101) Response time = 0 ms


When the voltage-transformer circuit breaker drops out, the device must block the distance protection imme-
diately to prevent an unwanted tripping of the distance protection due to the absence of the measuring
voltage while the load current is flowing.
The blocking must be faster than the 1st stage of the distance protection. This requires an extremely short
response time of the miniature circuit breaker (≤ 4 ms at 50 Hz, ≤ 3 ms at 60 Hz rated frequency). If the circuit-
breaker auxiliary contact does not fulfill this requirement, you have to set the response time accordingly.

9.3.4.5 Settings

Addr. Parameter C Setting Options Default Setting


VT miniatureCB
_:101 VT miniatureCB:Response 0.00 s to 0.03 s 0.00 s
time

9.3.4.6 Information List

No. Information Data Class Type


(Type)
Definite-T #
_:500 VT miniatureCB:>Open SPS I

9.3.5 Voltage-Balance Supervision

9.3.5.1 Overview of Functions


In healthy system operation, a certain balance between voltages can be assumed.
The Voltage-balance supervision function detects the following errors:

• Unbalance of phase-to-phase voltages in the secondary circuit

• Connection errors during commissioning or short circuits and interruptions in the secondary circuit
The voltage measurement is based on the RMS values of the fundamental component.

9.3.5.2 Structure of the Function


The Voltage-balance supervision function is located in the Power-system data of each 3-phase voltage
measuring point.

[dwstrusy-300913, 2, en_US]

Figure 9-15 Structure/Embedding of the Function

SIPROTEC 5, 7SJ82/7SJ85, Manual 1407


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.5.3 Function Description


The voltage balance is checked by a magnitude supervision function. This function relates the smallest phase-
to-phase voltage to the largest phase phase-to-phase voltage. Unbalance is detected if
|Vmin| / |Vmax| < Threshold min/max, as long as Vmax > Release threshold

[lokenuns-040211-01.tif, 1, en_US]

Figure 9-16 Characteristic of the Voltage-Balance Supervision

Logic

[lospasym-100611-01.tif, 4, en_US]

Figure 9-17 Logic Diagram of the Voltage-Balance Supervision

1408 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

The Threshold min/max parameter is the criterion by which a phase-to-phase voltage unbalance is meas-
ured. The device calculates the ratio between the minimum (Vmin) and the maximum (Vmax) phase-to-phase
voltage.
Enter the lower limit of the maximum phase-to-phase voltage (Vmax) with the parameter Release
threshold. This specifies the lower limit of the operating range of this function.

Delay failure indication


If it falls below the balance factor Threshold min/max and at the same time the maximum phase-to-phase
voltage exceeds the Release threshold, the delay of the failure indication begins, (parameter: Delay
failure indication). If both conditions persist during this time, the indication Failure is generated.

Blocking the Function


The following blockings reset the picked up function completely:

• Externally or internally via the binary input signal >Block function

• A protection pickup
The pickup signal of a protection function blocks the Failure indication.

9.3.5.4 Application and Setting Notes

Parameter: Threshold min/max

• Recommended setting value (_:102) Threshold min/max = 0.75


The Threshold min/max parameter is used to set the ratio between the minimum (Vmin) and the maximum
(Vmax) phase-to-phase voltage. Siemens recommends using the default setting.

Parameter: Release threshold

• Recommended setting value (_:101) Release threshold = 50 V


With the Release threshold parameter you set the lower limit of the maximum phase-to-phase voltage
(Vmax). Siemens recommends using the default setting.

Parameter: Delay failure indication

• Recommended setting value (_:6) Delay failure indication = 5.00 s


Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.

9.3.5.5 Settings

Addr. Parameter C Setting Options Default Setting


Supv. balan. V
_:1 Supv. balan. V:Mode • off off
• on
• test
_:101 Supv. balan. V:Release 0.300 V to 170.000 V 50.000 V
threshold
_:102 Supv. balan. V:Threshold 0.58 to 0.95 0.75
min/max
_:6 Supv. balan. V:Delay 0.00 sto 100.00 s 5.00 s
failure indication

SIPROTEC 5, 7SJ82/7SJ85, Manual 1409


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.5.6 Information List

No. Information Data Class Type


(Type)
Supv. balan. V
_:82 Supv. balan. V:>Block function SPS I
_:54 Supv. balan. V:Inactive SPS O
_:52 Supv. balan. V:Behavior ENS O
_:53 Supv. balan. V:Health ENS O
_:71 Supv. balan. V:Failure SPS O

9.3.6 Voltage-Sum Supervision

9.3.6.1 Overview of Functions


In healthy system operation, the sum of all voltages at one measuring point must be approximately 0. The
Voltage-sum supervision monitors the sum of all voltages of one measuring point in the secondary circuit. It
detects connection errors during commissioning or short circuits and interruptions in the secondary circuit. For
summation of the voltages, the 3 phase-to-ground voltages and the residual voltage (da-dn - voltage of an
open-circuited delta winding) are required.
The voltage measurement is based on the RMS values of the fundamental component.

NOTE

i For the Voltage-sum supervision, the externally generated residual voltage must be connected to the 4th
voltage measuring input.
For the Voltage-sum supervision to work correctly, the Matching ratio Vph / VN parameter must be
set accordingly.

9.3.6.2 Structure of the Function


The Voltage-sum supervision function is located in the Power-system data function group of each 3-phase
voltage measuring point.

[dwstrvss-100611-01.tif, 2, en_US]

Figure 9-18 Structure/Embedding of the Function

9.3.6.3 Function Description


The voltage sum is generated by addition of the voltage phasors. Errors in the voltage circuits are detected if
VF = |VA + VB + VC - Vph/VN • VN| > Threshold, where Vph/VN forms the Matching ratio Vph / VN
parameter.

1410 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

[lo_kenvss-01.tif, 1, en_US]

Figure 9-19 Characteristic of the Voltage-Sum Supervision

Logic

[lovssumm-140611-01.tif, 4, en_US]

Figure 9-20 Logic Diagram of the Voltage-Sum Supervision

The device measures the phase-to-ground voltage and the ground voltage of the lines to be protected. The
sum of the 4 voltages must be 0.

Threshold
If the calculated fault voltage (VF) exceeds the Threshold the parameter Delay failure indication
triggers the indication Failure.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1411


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

The device calculates the fault voltage (VF) with the formula:
VF = |VA + VB + VC - Vph/UN • UN|, where Vph/VN forms the Matching ratio Vph / VN parameter.
The Matching ratio Vph / VN parameter takes into account the differing transformation ratios between
the residual voltage input and the phase-voltage inputs.
You can find more information in this respect in chapter 9.3.6.1 Overview of Functions ).

Delay failure indication


When the threshold value for the delay of the failure indication (parameter: Delay failure indication)
is exceeded, the indication Failure is generated.

Blocking the Function


The following blockings reset the picked up function completely:

• Externally or internally via the binary input signal >Block function

• A protection pickup
The pickup signal of a protection function blocks the Failure indication.

9.3.6.4 Application and Setting Notes

Parameter: Threshold

• Recommended setting value (_:3) Threshold = 25 V


The Threshold parameter is used to set the voltage which the device uses to recognize the calculated fault
voltage (VF) as a failure of the voltage sums. Siemens recommends using the default setting.

Parameter: Delay failure indication

• Recommended setting value (_:6) Delay failure indication = 5.00 s


Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.

9.3.6.5 Settings

Addr. Parameter C Setting Options Default Setting


Supv. sum V
_:1 Supv. sum V:Mode • off off
• on
• test
_:3 Supv. sum V:Threshold 0.300 V to 170.000 V 43.300 V
_:6 Supv. sum V:Delay 0.00 sto 100.00 s 5.00 s
failure indication

9.3.6.6 Information List

No. Information Data Class Type


(Type)
Supv. sum V
_:82 Supv. sum V:>Block function SPS I
_:54 Supv. sum V:Inactive SPS O
_:52 Supv. sum V:Behavior ENS O
_:53 Supv. sum V:Health ENS O
_:71 Supv. sum V:Failure SPS O

1412 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.7 Voltage Phase-Rotation Supervision

9.3.7.1 Overview of Functions


The Voltage phase-rotation supervision function monitors the phase sequence of the secondary-circuit
voltages by monitoring the sequence of the zero crossings (with same sign) of the voltages. This enables the
device to detect connections that were inverted during commissioning. The criterion for the check is the
setting of the Phase sequence parameter.

9.3.7.2 Structure of the Function


The Voltage phase-rotation supervision function is located in the Power-system data of each 3-phase
voltage measuring point.

[dwstrvrs-060611-01.tif, 3, en_US]

Figure 9-21 Structure/Embedding of the Function

9.3.7.3 Function Description

Logic

[lovrsymm-100611-01.tif, 4, en_US]

Figure 9-22 Logic Diagram of the Voltage Phase-Rotation Supervision

SIPROTEC 5, 7SJ82/7SJ85, Manual 1413


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

The phase rotation is important for protection functions which process phase, loop, and directional informa-
tion. You can set the phase sequence with the Phase sequence parameter in the function block General of
the power-system data (see chapter 6.1 Power-System Data).
To supervise the phase rotation, the device compares the measured phase sequence with the set phase
sequence. For abnormal phase sequences, the indication Failure is generated.
The connection of the voltages to the device does not depend on the selected phase sequence. The connec-
tion diagrams are shown in chapter A Appendix.

Release Condition
The supervision of the voltage phase rotation is carried out when all measured phase-to-phase voltages are
greater than 40 V.

Blocking of the Function


The following blockings reset the function completely:

• Via the binary input signal >Block function from an external or internal source

• Via a protection pickup


The pickup signal from a protection function blocks the indication Failure.

Delay failure indication


When the device detects an inverted phase-rotation direction for the duration of the Delay failure indi-
cation, the indication Failure is generated.

9.3.7.4 Application and Setting Notes

Parameter: Delay failure indication

• Recommended setting value (_:6) Delay failure indication = 5.00 s


Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.

9.3.7.5 Settings

Addr. Parameter C Setting Options Default Setting


Supv. ph.seq.V
_:1 Supv. ph.seq.V:Mode • off off
• on
• test
_:6 Supv. ph.seq.V:Delay 0.00 s to 100.00 s 5.00 s
failure indication

9.3.7.6 Information List

No. Information Data Class Type


(Type)
Supv. ph.seq.V
_:82 Supv. ph.seq.V:>Block function SPS I
_:54 Supv. ph.seq.V:Inactive SPS O
_:52 Supv. ph.seq.V:Behavior ENS O
_:53 Supv. ph.seq.V:Health ENS O
_:71 Supv. ph.seq.V:Failure SPS O

1414 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.8 Voltage-Comparison Supervision

9.3.8.1 Overview of Functions


The Voltage-comparison supervision function (ANSI 60):

• Monitors the voltage-transformer circuits by comparing the voltages from 2 voltage transformers
If failures in the voltage circuits are detected, voltage-related protection functions can be blocked.

• Requires the connection of 2 voltage measuring points to the voltage interface of the function group
You can take one of the voltages as the reference voltage and then the other becomes the main voltage.
The reference voltage is used for comparison.

NOTE

i The voltage selection for the protection function in the FGs works independent of the status of the
Voltage-comparison supervision function.

9.3.8.2 Structure of the Function


The Voltage-comparison supervision function can be used in the following function groups:

• Generator stator

• Generator side

• Voltage-current 3-phase (VI 3ph)

• Transformer side

• Auto transformer autoside (Auto trf. autoside)


The Voltage-comparison supervision function supports only 1 stage. The stage is preconfigured at the
factory.

[dw_structure_VBP, 1, en_US]

Figure 9-23 Structure/Embedding of the Function

9.3.8.3 Description

Function Application
The following figure shows an application example.

[dw_VBP application, 1, en_US]

Figure 9-24 Application Example

SIPROTEC 5, 7SJ82/7SJ85, Manual 1415


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Connecting Measuring Points to a Function Group


The following figure shows the connection of the function group Generator stator with several measuring
points in DIGSI. The ID of each measuring point appears in the brackets after the name.

[sc_VBStoFG, 1, en_US]

Figure 9-25 Connecting the Measuring Points to the Generator Stator Function Group

There are consistency checks that validate the connections of voltage measuring points to the function group:

• The connection type must be identical for all measuring points connected to the same interface of the
function group.

• The rated voltage (primary and secondary) must be identical for all measuring points connected to the
same interface.

• 2 voltage measuring points must be connected to one voltage interface.

• Either the Voltage-comparison supervision function or the Voltage measuring-point selection func-
tion must be instantiated. They must not be instantiated at the same time.
About the Voltage measuring-point selection function, you can find more information in chapter
6.53 Voltage Measuring-Point Selection.

Voltage Selection
2 voltage measuring points are connected to a voltage interface of a function group. In the Voltage-compar-
ison supervision function, you can set one of the voltages as the reference voltage via the parameter Refer-
ence voltage, and the other voltage becomes the main voltage.

• The reference voltage is used for voltage comparison.

• The main voltage is used for all voltage-related functions in the FGs that contain the Voltage-compar-
ison supervision function.
If the main voltage transformer is disconnected, the Voltage-comparison supervision function issues
the blocking signal Meas.-volt failure. The signal is transmitted to all voltage-related protection
functions which are used in the same FGs as the Voltage-comparison supervision.

1416 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Logic of the Stage

[lo_stage VBP, 2, en_US]

Figure 9-26 Logic Diagram of the Supervision Stage

The voltage inputs in the preceding figure are calculated with the following equations:
ΔV1 = |v(n)ref.| - |v(n)main|
ΔV2 = |v(n)main| - |v(n)ref.|
ΔV3 = |Vref. - Vmain|
ΔV4 = Max. (V1ref., V1main)

The following table shows the description of the voltages.

Table 9-1 Voltage Description

Voltages Description
v(n)ref. Sampled value of the reference voltage
v(n)main Sampled value of the main voltage
Vref. Fundamental value of the reference voltage
Vmain Fundamental value of the main voltage
V1ref. Positive-sequence value of the reference voltage

SIPROTEC 5, 7SJ82/7SJ85, Manual 1417


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Voltages Description
V1main Positive-sequence value of the main voltage

Pickup
If the voltage difference between each 2 of 3 continuous sampling points is over 8 % Vrated of the plant, the
supervision stage picks up.

Voltage Supervision
For the Voltage-comparison supervision function, the following 2 connection types are allowed:

• Phase-to-ground
The phase-to-ground voltages are used for the voltage-difference comparison.

• Phase-to-phase
The phase-to-phase voltages are used for the voltage-difference comparison.

NOTE

i The 2 ph-to-ph volt. + VN and 2 ph-to-ph voltages connection types are not allowed.

Voltage-Failure Indication
For different connection types, the indications are different.

• Phase-to-ground
You can get the voltage-failure information from the output signals Main-voltage failure and
Ref.-voltage failure.
• Phase-to-phase
– If one phase is influenced, the phase information is indicated.
– If more than one phase is influenced, the phase-to-phase information is indicated.
Take the main voltage transformer for example. You can determine the faulty phase with the
following table.

Determination Criteria Calculated Result


(|vAB(n)ref.| - |vAB(n)main|) - 8 % Vrated >0 >0 <0
(|vBC(n)ref.| - |vBC(n)main|) - 8 % Vrated <0 >0 >0
(|vAC(n)ref.| - |vAC(n)main|) - 8 % Vrated >0 <0 >0
Failure Information Phase A is failed. Phase B is failed. Phase C is failed.

Release Voltage
If the main positive-sequence voltage or the reference positive-sequence voltage is between 50 % Vrated and
130 % Vrated, the function is released.

Selection Invalid
An invalid measuring-point selection results in the following:

• The voltage measured values are displayed as Failure.

• The validity of the voltage measured values is set to Invalid.

• The indication Health is set to Alarm.

• The indication Selection invalid becomes true.

1418 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Blocking of the Stage


In the event of blocking, the picked up function is reset. Blocking is possible externally or internally via the
binary input signal >Block stage.

9.3.8.4 Application and Setting Notes

Parameter: Reference voltage

• Default setting Reference voltage = None


With the parameter Reference voltage, you can set a measured voltage as the reference voltage.

NOTE

i You must assign a voltage measuring point to the parameter Reference voltage. The assignment influ-
ences the voltage-related protection functions which are used in the same FGs as the Voltage-comparison
supervision function. These voltage-related protection functions use the unassigned voltage measuring
point, which is defined as the main voltage in the Voltage-comparison supervision function. You can find
more information in section Voltage Selection, Page 1416.

EXAMPLE
Meas.point V-3ph 1 and Meas.point V-3ph 2 are connected to the Voltage-comparison supervision func-
tion. Then you have 2 more setting options, as shown in the following figure. You must select one of these
setting options for the parameter Reference voltage.

[sc_VBS_ref.voltage, 1, en_US]

Parameter: Mode

• Default setting (_:2311:1) Mode = off


With the parameter Mode, you can activate and deactivate the Voltage-comparison supervision function. If
you switch to test mode, the Voltage-comparison supervision function is marked as invalid.

9.3.8.5 Settings

Addr. Parameter C Setting Options Default Setting


VolCmpSup 1
_:2311:1 General:Mode • off off
• on
• test
_:2311:101 General:Reference Setting options depend on None
voltage configuration

SIPROTEC 5, 7SJ82/7SJ85, Manual 1419


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.8.6 Information List

No. Information Data Class Type


(Type)
VolCmpSup 1
_:2311:81 General:>Block stage SPS I
_:2311:501 General:>MP-ID selection INS I
_:2311:54 General:Inactive SPS O
_:2311:52 General:Behavior ENS O
_:2311:53 General:Health ENS O
_:2311:307 General:Main-voltage failure ACD O
_:2311:308 General:Ref.-voltage failure ACD O
_:2311:309 General:Selection invalid SPS O

9.3.9 Broken-Wire Detection

9.3.9.1 Overview of Functions


The purpose of the Broken-wire detection is to detect interruptions in the secondary circuit of the current
transformers during steady-state operation.
The Broken-wire detection is unavailable for the connection type 2ph, 2p. CT + IN-sep and the
connection type 2ph, 2p. CT + 2 IN-sep.

9.3.9.2 Structure of the Function


The Broken-wire detection function is located in the power-system data of each 3-phase measuring point.

[dwbwsjsk-301112-01.tif, 3, en_US]

Figure 9-27 Structure/Embedding of the Function

The tasks of Broken-wire detection are:

• The instantaneous values of all current measuring points are checked on a phase-selective basis for
implausible values.

• The affected phases are marked with wire-break suspected.

• Depending on the supervision mode, you can add a marker for blocking protection functions for the
affected phases.

• After 10 ms of broken-wire check, a detected wire break is signaled.

9.3.9.3 Function Description

Broken Wire Suspected


The Broken-wire detection function monitors the dynamic behavior of the currents of each phase and of all
measuring points. For this purpose, the instantaneous values of the currents are checked for their plausibility.
Each expected violation must be confirmed by additional criteria before a wire break can be detected and
signaled with assurance.
The detection of the local broken wire suspected is performed on each 3-phase current measuring point of the
device selectively for each phase.

1420 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Detection:
A wire break initially manifests itself as a sudden decrease of the current below the minimum threshold of
0.06 I/I rated. A plausibility test on one period of past instantaneous values confirms this condition. If the criteria
for the local wire break are satisfied, the affected phase is marked with Broken wire suspected.

Resetting:
The broken wire suspected is reset by phase current flowing again or by a binary input signal. Binary resetting
can be useful during laboratory tests among other applications.

Indication
If the broken-wire detection has not been reset within 10 ms, it will be indicated. The indication is held stable
for the duration of at least 3 periods.
When using the fast measuring transducer inputs as 4 mA to 20 mA inputs, broken-wire detection is active.
With a < 2 mA current, wire breaks are detected and the wire break indication is set. The measured values
display remains unaffected.

9.3.9.4 Application and Setting Notes

Parameter: Mode

• Recommended setting value (_:1) Mode = off


The Mode parameter is used to switch the broken-wire detection to on, off and test.

9.3.9.5 Settings

Addr. Parameter C Setting Options Default Setting


Brk.wire det.
_:1 Brk.wire det.:Mode • off off
• on
• test

9.3.9.6 Information List

No. Information Data Class Type


(Type)
Brk.wire det.
_:82 Brk.wire det.:>Block function SPS I
_:54 Brk.wire det.:Inactive SPS O
_:52 Brk.wire det.:Behavior ENS O
_:53 Brk.wire det.:Health ENS O
_:301 Brk.wire det.:Phs A BW suspected SPS O
_:302 Brk.wire det.:Phs B BW suspected SPS O
_:303 Brk.wire det.:Phs C BW suspected SPS O
_:304 Brk.wire det.:Phase A broken wire SPS O
_:305 Brk.wire det.:Phase B broken wire SPS O
_:306 Brk.wire det.:Phase C broken wire SPS O
_:307 Brk.wire det.:Broken wire suspected SPS O
_:308 Brk.wire det.:Broken wire confirmed SPS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1421


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.10 Current-Balance Supervision

9.3.10.1 Overview of Functions


In healthy network operation, a certain balance between currents can be assumed.
The Current-balance supervision function detects the following errors:

• Unbalance of phase currents in the secondary circuit

• Connection errors during commissioning or short circuits and interruptions in the secondary circuit
The current measurement is based on the RMS values of the fundamental component.

9.3.10.2 Structure of the Function


The Current-balance supervision function is located in the Power-system data of each 3-phase current
measuring point.

[dwstrsym-060611-01.tif, 3, en_US]

Figure 9-28 Structure/Embedding of the Function

9.3.10.3 Function Description


The current balance is checked by a magnitude monitoring function. This function relates the smallest phase
current to the largest phase current. Unbalance is detected if
|Imin| / |Imax| < Threshold min/max, as long as Imax > Release threshold.

[losymmke-040211-01.tif, 1, en_US]

Figure 9-29 Characteristic of the Current-Balance Supervision

1422 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Logic

[locbsymm-100611-01.tif, 3, en_US]

Figure 9-30 Logic Diagram of the Current-Balance Supervision

The Threshold min/max parameter is the criterion by which unbalance in the phase currents is measured.
The device calculates the ratio between the minimum (Imin) and the maximum (Imax) phase current.
Enter the lower limit of the maximum phase current (Imax) with the parameter Release threshold. This
specifies the lower limit of the operating range of this function.

Delay failure indication


If it falls below the balance factor Threshold min/max and at the same time the maximum phase current
exceeds the Release threshold, the operate delay of the failure indication (parameter Delay failure
indication) begins. If both conditions persist during this time, the indication Failure is generated.

Blocking the Function


The following blockings reset the picked up function completely:

• Externally or internally via the binary input signal >Block function

• A protection pickup
The pickup signal of a protection function blocks the indication Failure.

9.3.10.4 Application and Setting Notes

Parameter: Threshold min/max

• Recommended setting value (_:102) Threshold min/max = 0.5


The Threshold min/max parameter is used to set the ratio between the minimum (Imin) and the maximum
(Imax) phase current.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1423


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Parameter: Release threshold

• Recommended setting value (_:101) Release threshold = 0.5 A for Irated = 1 A or 2.5 A for Irated
=5A
The Release threshold parameter is used to set the lower limit of the maximum phase current (Imax).

Parameter: Delay failure indication

• Recommended setting value (_:6) Delay failure indication = 5.00 s


Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided.

9.3.10.5 Settings

Addr. Parameter C Setting Options Default Setting


Supv. balan. I
_:1 Supv. balan. I:Mode • off off
• on
• test
_:101 Supv. balan. I:Release 1 A @ 100 Irated 0.030 A to 35.000 A 0.500 A
threshold 5 A @ 100 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 2.500 A
_:102 Supv. balan. I:Threshold 0.10 to 0.95 0.50
min/max
_:6 Supv. balan. I:Delay 0.00 s to 100.00 s 5.00 s
failure indication

9.3.10.6 Information List

No. Information Data Class Type


(Type)
Supv. balan. I
_:82 Supv. balan. I:>Block function SPS I
_:54 Supv. balan. I:Inactive SPS O
_:52 Supv. balan. I:Behavior ENS O
_:53 Supv. balan. I:Health ENS O
_:71 Supv. balan. I:Failure SPS O

9.3.11 Current-Sum Supervision

9.3.11.1 Overview of Functions


In healthy system operation, the sum of all currents at one measuring point must be approximately 0. The
Current-sum supervision function monitors the sum of all currents of one measuring point in the secondary
circuit. It detects connection errors during commissioning or short circuits and interruptions in the secondary
circuit.

1424 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

For summation of the currents, the device requires the phase currents and the ground current of the current
transformer neutral point or of a separate ground-current transformer at this measuring point. Select the
following connection variant:

• Current-transformer connections connected to 3 current transformers and the neutral point (see
Figure A-12 in the Attachment)

NOTE

i For current-sum supervision, the ground current of the line to be protected must be connected to the 4th
current measurement input (IN).

9.3.11.2 Structure of the Function


The Current-sum supervision function is located in the Power-system data of each 3-phase current meas-
urement point.

[dwstrcss-300913, 3, en_US]

Figure 9-31 Structure/Embedding of the Function

9.3.11.3 Function Description


The current sum is generated by addition of the current phasors. Errors in the current circuits are detected if
IF = |IA + IB + IC + kl• IN| > Threshold + Slope factor •Σ | I |.

[lokensum-300311-01.tif, 1, en_US]

Figure 9-32 Characteristic of the Current-Sum Supervision

SIPROTEC 5, 7SJ82/7SJ85, Manual 1425


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Logic

[locssumm-140611-01.tif, 3, en_US]

Figure 9-33 Logic Diagram of the Current-Sum Supervision

Slope of the Characteristic Curve


The Slope factor • Σ | I | part takes into account permissible current-proportional transformation errors of
the transformer, which can occur in the case of high short-circuit currents.
The Slope factor and Threshold parameters are used to set the fault-current limit (IFmax) for the current-
sum supervision. The device calculates this fault current limit with the formula:
IFmax = Threshold + Slope factor • Σ| I |
The device uses the current inputs (IA, IB, IC and IN) to calculate:

• The fault current IF = |IA + IB + IC + kl• IN|

• The maximum current Σ| I | = | IA| + |IB| +| IC| + |kl• IN|


with kI taking into account a possible difference from the transformation ratio of a separated ground-current
transformer (IN), for example, cable type current transformer.

• Transformation ratio of residual-current converter: RatioN

• Transformation ratio of phase-current converter: Ratioph

1426 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

[foglchki-040211-01.tif, 1, en_US]

Threshold
The Threshold parameter is the lower limit of the operating range of the Current-sum supervision func-
tion.

Delay failure indication


When the calculated fault current (IF) exceeds the calculated fault current limit (IFmax), the delay of the failure
indication (parameter: Delay failure indication) starts. If the threshold-value violation persists for
that time, the Failure indication is generated.

Blocking the Function


The following blockings reset the picked up function completely:

• Externally or internally via the binary input signal >Block function

• A protection pickup
The pickup signal of a protection function blocks the indication Failure.

9.3.11.4 Application and Setting Notes

Parameter: Slope factor

• Recommended setting value (_:101) Slope factor = 0.1


The Slope factor parameter is used to set the ratio between the minimum (Imin) and the maximum (Imax)
phase current. This function calculates the RMS values.

Parameter: Threshold

• Recommended setting value (_:102) Threshold = 0.1 A for Irated = 1 A or 0.5 A for Irated = 5 A

The Threshold parameter is used to set the maximum phase current (Imax).

Parameter: Delay failure indication

• Recommended setting value (_:6) Delay failure indication = 5.00 s


Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided.

9.3.11.5 Settings

Addr. Parameter C Setting Options Default Setting


Supv. sum I
_:1 Supv. sum I:Mode • off off
• on
• test
_:102 Supv. sum I:Threshold 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A

SIPROTEC 5, 7SJ82/7SJ85, Manual 1427


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Addr. Parameter C Setting Options Default Setting


_:101 Supv. sum I:Slope factor 0.00 to 0.95 0.10
_:6 Supv. sum I:Delay failure 0.00 s to 100.00 s 5.00 s
indication

9.3.11.6 Information List

No. Information Data Class Type


(Type)
Supv. sum I
_:82 Supv. sum I:>Block function SPS I
_:54 Supv. sum I:Inactive SPS O
_:52 Supv. sum I:Behavior ENS O
_:53 Supv. sum I:Health ENS O
_:71 Supv. sum I:Failure SPS O

9.3.12 Current Phase-Rotation Supervision

9.3.12.1 Overview of Functions


The Current phase-rotation supervision function monitors the phase sequence of the secondary-circuit
currents by monitoring the sequence of the zero crossings (with same sign) of the currents. This enables the
device to detect connections that were inverted during commissioning. The criterion for the check is the
setting of the Phase sequence parameter.
The current measurement is based on the RMS values of the fundamental component.

9.3.12.2 Structure of the Function


The Current phase-rotation supervision function is located in the Power-system data of each 3-phase
current measurement point.

[dwstrcrs-040211-01.tif, 4, en_US]

Figure 9-34 Structure/Embedding of the Function

1428 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.12.3 Function Description

Logic

[locrsymm-100611-01.tif, 4, en_US]

Figure 9-35 Logic Diagram of the Current Phase-Rotation Supervision

The phase rotation is important for protection functions which process phase, loop, and directional informa-
tion. You can set the phase sequence with the Phase sequence parameter in the function block General of
the power-system data (see chapter 6.1 Power-System Data).
To supervise the phase rotation, the device compares the measured phase sequence with the set phase
sequence. For abnormal phase sequences, the indication Failure is generated.
The connection of the currents to the device does not depend on the selected phase sequence. The connec-
tion diagrams are shown in the chapter A Appendix.

Release Condition
The supervision of the current phase rotation is carried out when all measured phase currents are greater than
0.5 Irated.

Blocking of the Function


The following blockings reset the function completely:

• Via the binary input signal >Block function from an external or internal source

• Via a protection pickup


The pickup signal from a protection function blocks the indication Failure.

Delay failure indication


When the device detects an inverted phase sequence for the duration of the Delay failure indication,
the indication Failure is generated.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1429


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.12.4 Application and Setting Notes

Parameter: Delay failure indication

• Recommended setting value (_:6) Delay failure indication = 5.00 s


Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.

9.3.12.5 Settings

Addr. Parameter C Setting Options Default Setting


Supv. ph.seq.I
_:1 Supv. ph.seq.I:Mode • off off
• on
• test
_:6 Supv. ph.seq.I:Delay 0.00 s to 100.00 s 5.00 s
failure indication

9.3.12.6 Information List

No. Information Data Class Type


(Type)
Supv. ph.seq.I
_:82 Supv. ph.seq.I:>Block function SPS I
_:54 Supv. ph.seq.I:Inactive SPS O
_:52 Supv. ph.seq.I:Behavior ENS O
_:53 Supv. ph.seq.I:Health ENS O
_:71 Supv. ph.seq.I:Failure SPS O

9.3.13 Trip-Circuit Supervision

9.3.13.1 Overview of Functions


The Trip-circuit supervision function recognizes disruptions in the trip circuit. When 2 binary inputs are used,
the function recognizes all disruptions in the trip circuit. If only 1 binary input is available, it will not recognize
disruptions at the circuit breaker.
The control voltage for the circuit breaker must be greater than the sum of the minimum voltage drops at the
binary inputs VCtrl > 2 VBImin. At least 19 V are required for each binary input. This makes the supervision usable
only with a system-side control voltage of > 38 V.

9.3.13.2 Structure of the Function


The trip-circuit supervision is integrated into the Circuit-breaker function group. Depending on the number of
available binary inputs, it works with 1 or 2 binary inputs.

[dwtcsueb-010313-01.tif, 1, en_US]

Figure 9-36 Structure/Embedding of the Function

1430 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.13.3 Trip-Circuit Supervision with 2 Binary Inputs


In order to recognize disruptions in the trip circuit for each switch position, you need 2 binary inputs. One
input is connected parallel to the respective command relay of the protection, the other parallel to the circuit-
breaker auxiliary contact.
The following figure shows the principle of the trip-circuit supervision with 2 binary inputs.

[dwtcs2be-110611-01.tif, 3, en_US]

Figure 9-37 Principle of Trip-Circuit Supervision with 2 Binary Inputs

CR Command relay
CB Circuit breaker (open)
CB coil Circuit-breaker coil
AuxCon1 Circuit-breaker auxiliary contact (make contact)
AuxCon2 Circuit-breaker auxiliary contact (break contact)
V-Ctrl Control voltage (tripping voltage)
V-BI1 Input voltage for binary input 1
V-BI2 Input voltage for binary input 2

Supervision with 2 binary inputs identifies disruptions in the trip circuit and the outage of the control voltage.
It also monitors the reaction of the circuit breaker by way of the position of the circuit-breaker auxiliary
contacts.
Depending on the switch position of the command relay and circuit breaker, the binary inputs are either acti-
vated (H) or not (L). If both binary inputs are not activated, there is a fault. The fault can be a disruption or a
short circuit in the trip circuit, an outage of the battery voltage or a fault in the mechanics of the circuit
breaker. With intact trip circuits, this state will occur only briefly while the command relay is closed and the
circuit breaker has not yet been opened.
No. Command CB AuxCon1 AuxCon2 BI 1 BI 2 Dynamic State Static State
Relay
(CR)
1 Open ON Closed Open H L Normal operation with closed circuit
breaker
2 Open OFF Open Closed H H Normal operation with open circuit
breaker
3 Closed ON Closed Open L L Transmission or fault Fault

SIPROTEC 5, 7SJ82/7SJ85, Manual 1431


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

No. Command CB AuxCon1 AuxCon2 BI 1 BI 2 Dynamic State Static State


Relay
(CR)
4 Closed OFF Open Closed L H CR successfully activated the circuit
breaker

With the Alarm delay parameter, you can set the time delay. After fixing the fault in the trip circuit, the
failure indication will automatically expire after the same time.
If the binary input signals >Trip relay or >CB auxiliary contact are not routed on the binary inputs
of the device, then the Input sig. not routed indication is generated and the Trip-circuit supervision
function is ineffective.
The following figure shows the logic diagram of the trip-circuit supervision with 2 binary inputs.

[lotcs2be-260912-01.tif, 1, en_US]

Figure 9-38 Logic Diagram of Trip-Circuit Supervision with 2 Binary Inputs

9.3.13.4 Trip-Circuit Supervision with 1 Binary Input


When using 1 binary input, you will not identify any disruptions on the circuit breaker. The binary input is
connected in parallel with the respective command relay of the protection device. The circuit-breaker auxiliary
contact is bridged with a high-resistance equivalent resistance R.
The following figure shows the principle of the trip-circuit supervision with 1 binary input.

1432 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

[dwtcs1be-110611-01.tif, 3, en_US]

Figure 9-39 Principle of Trip-Circuit Supervision with 1 Binary Input

CR Command relay
CB Circuit breaker (open)
CB coil Circuit-breaker coil
AuxCon1 Circuit-breaker auxiliary contact (make contact)
AuxCon2 Circuit-breaker auxiliary contact (break contact)
V-Ctrl Control voltage (tripping voltage)
V-BI Input voltage for binary input
R Equivalent resistance

Supervision with 1 binary input identifies disruptions in the trip circuit and the outage of the control voltage.
In normal operation, the binary input is activated with the command relay open and the trip circuit intact (H).
The supervision circuit is closed with the equivalent resistance R or with the auxiliary contact AuxCon1 of the
closed circuit breaker. The binary input is not activated while the command relay is closed (L). If the binary
input is not activated for a prolonged time, there is a disruption in the trip circuit or the control voltage has
failed.
No. Command CB AuxCon1 AuxCon2 BI Dynamic State Static State
Relay
1 Open ON Closed Open H Normal operation with closed circuit
breaker
2 Open OFF Open Closed H Normal operation with open circuit
breaker
3 Closed ON Closed Open L Transmission or fault Fault
4 Closed OFF Open Closed L CR successfully activated the circuit
breaker

Use the parameter Blk.by trip/open cmd from to set the conditions under which the trip-circuit super-
vision is blocked. The following conditions can cause a blocking of the trip-circuit supervision function:

• The Trip/open cmd. of the circuit breaker is activated.

• One of the trip commands of the circuit-breaker failure protection is activated.


As long as the trip-circuit supervision function is blocked, the closed contact of the command relay does not
cause a failure indication.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1433


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

If the command contacts of other devices work in parallel on the trip circuit, the failure indication must be
delayed. With the Alarm delay parameter, you can set the time delay. After fixing the fault in the trip
circuit, the failure indication will automatically expire after the same time.
If the binary input signal >Trip relay is not routed to a binary input of the device (information routing in
DIGSI 5), then the Input sig. not routed indication is generated and Trip-circuit supervision is no
longer in effect.
The following figure shows the logic diagram of the trip-circuit supervision with 1 binary input.

[lotcs1be-260912-01.tif, 1, en_US]

Figure 9-40 Logic Diagram of Trip-Circuit Supervision with 1 Binary Input

Equivalent Resistance R
The equivalent resistance R must be dimensioned such that the circuit-breaker coil is no longer activated when
the circuit breaker is open. Simultaneously, the binary input must still be activated when the command relay is
open.
In order to ensure the minimum voltage for activating the binary input, Rmax results in:

[fofr1b02-090330-01.tif, 1, en_US]

So that the circuit-breaker coil does not remain activated, Rmin results in:

1434 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

[fofr1b03-090330-01.tif, 1, en_US]

You can calculate the optimal value for the equivalent resistance R from the 2 values Rmin and Rmax:

[fofr1b01-090330-01.tif, 1, en_US]

The following applies for the power consumption of the equivalent resistance R:

[fofr1b04-090330-01.tif, 1, en_US]

9.3.13.5 Application and Setting Notes

Parameter: Alarm delay

• Recommended setting value (_:100) Alarm delay = 2 s (Trip-circuit supervision with 2 binary
inputs)

• Recommended setting value (_:100) Alarm delay = 300 s (Trip-circuit supervision with 1 binary
input)
With the parameter Alarm delay, you can set the time for the delayed output of the indication Trip-
circuit failure.
For Trip-circuit supervision with 2 binary inputs, you set the Alarm delay parameter so that the short-
term transient states do not cause the function to activate.
For the Trip-circuit supervision with 1 binary input, you set the Alarm delay so that the longest duration
of a trip command is bridged without fail. This ensures that the indication is emitted only if the trip circuit is
actually interrupted.

Parameter: Blk.by trip/open cmd from

• Possible settings, application-dependent


The parameter works only with the trip-circuit supervision with 1 binary input.
Use the parameter Blk.by trip/open cmd from to set the conditions under which the trip-circuit super-
vision is blocked. The following conditions can cause a blocking of the trip-circuit supervision function:

• The Trip/open cmd. of the circuit breaker is activated.

• One of the trip commands of the circuit-breaker failure protection is activated.

• One of the trip commands of the circuit-breaker reignition protection is activated.


The circuit-breaker failure protection is set to protect a different trip circuit than the local circuit breaker. Using
the configuration options of the Blk.by trip/open cmd from parameter, multiple trip-circuit supervision
functions can be operated in parallel. For instance, a trip-circuit supervision function dedicated to a local
circuit breaker can also be operated parallel to a higher-level circuit breaker upon which the circuit-breaker
failure protection acts.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1435


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

9.3.13.6 Settings

Addr. Parameter C Setting Options Default Setting


74TC sup.1BI #
_:1 74TC sup.1BI #:Mode • off on
• on
• test
_:100 74TC sup.1BI #:Alarm delay 1.00 s to 600.00 s 300.00 s
_:102 74TC sup.1BI #:Blk.by trip/ Setting options depend on
open cmd from configuration
74TC sup.2BI #
_:1 74TC sup.2BI #:Mode • off on
• on
• test
_:100 74TC sup.2BI #:Alarm delay 1.00 s to 30.00 s 2.00 s

9.3.13.7 Information List

No. Information Data Class Type


(Type)
74TC sup.1BI #
_:82 74TC sup.1BI #:>Block function SPS I
_:500 74TC sup.1BI #:>Trip relay SPS I
_:54 74TC sup.1BI #:Inactive SPS O
_:52 74TC sup.1BI #:Behavior ENS O
_:53 74TC sup.1BI #:Health ENS O
_:71 74TC sup.1BI #:Trip-circuit failure SPS O
_:301 74TC sup.1BI #:Input sig. not routed SPS O
74TC sup.2BI #
_:82 74TC sup.2BI #:>Block function SPS I
_:500 74TC sup.2BI #:>Trip relay SPS I
_:503 74TC sup.2BI #:>CB auxiliary contact SPS I
_:54 74TC sup.2BI #:Inactive SPS O
_:52 74TC sup.2BI #:Behavior ENS O
_:53 74TC sup.2BI #:Health ENS O
_:71 74TC sup.2BI #:Trip-circuit failure SPS O
_:301 74TC sup.2BI #:Input sig. not routed SPS O

9.3.14 Closing-Circuit Supervision

9.3.14.1 Overview of Functions


The Closing-circuit supervision function detects disruptions in the closed circuit of the circuit breaker.
The control voltage for the closed circuit must be greater than the sum of the minimum voltage drops at the
binary inputs, that is, VCtrl > 2 ⋅ VBImin.

9.3.14.2 Structure of the Function


The Closing-circuit supervision function is integrated into the Circuit-breaker function group. Depending on
the available number of the binary inputs, the function works with 2 binary inputs or with 1 binary input.

1436 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

The following stages can be operated simultaneously in the Circuit-breaker function group:

• Maximum of 3 stages Closing-circuit supervision with 2 binary inputs

• Maximum of 3 stages Closing-circuit supervision with 1 binary input

[dw_CCS_structure, 1, en_US]

Figure 9-41 Structure/Embedding of the Function

9.3.14.3 Closing-Circuit Supervision with 2 Binary Inputs

Principle
In order to detect disruptions in the closed circuit for each switch position, 2 binary inputs are necessary:

• One binary input is connected in parallel to the close-command relay.

• Another binary input is connected in series with the circuit‑breaker auxiliary contact.

[dw_CCS_2BI, 1, en_US]

Figure 9-42 Principle of the Closing-Circuit Supervision with 2 Binary Inputs

CCR Close-command relay


CB Circuit breaker
CB closing coil Circuit-breaker closing coil
AuxCon1 Circuit-breaker auxiliary contact 1 (open if the CB is closed)
AuxCon2 Circuit-breaker auxiliary contact 2 (closed if the CB is closed)
V-Ctrl Control voltage for the closed circuit
V-BI1 Input voltage for binary input 1
V-BI2 Input voltage for binary input 2

SIPROTEC 5, 7SJ82/7SJ85, Manual 1437


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

The stage Closing-circuit supervision with 2 binary inputs detects disruptions in the closed circuit. It also
monitors the reaction of the circuit breaker via the position of the circuit-breaker auxiliary contacts.
Depending on the switch position of the close-command relay and the circuit breaker, the binary inputs are
either activated (H) or deactivated (L). If both binary inputs are deactivated, a fault occurs. The fault can be
one of the following conditions:

• A disruption

• An outage of the battery voltage

• An adhesion present on the contact surface of the CCR


The following table shows all the states of the closed circuit:
CCR CB AuxCon1 AuxCon2 >Closed >CB auxil- Dynamic Static State
contact iary contact State
Open Open Closed Open H L Normal operation with an
open circuit breaker
Open Closed Open Closed H H Normal operation with a
closed circuit breaker
Closed Open Closed Open L L Transient Fault
Closed Closed Open Closed L H Transient, CCR is activated

Logic

[lo_CCS_2BI, 1, en_US]

Figure 9-43 Logic Diagram of the Stage Closing-Circuit Supervision with 2 Binary Inputs

The indication Closing-circuit failure is generated when the following 2 conditions are met:

• The binary inputs >Closed contact and >CB auxiliary contact are both deactivated.

• The Alarm delay has elapsed.

9.3.14.4 Closing-Circuit Supervision with 1 Binary Input

Principle
In the stage Closing-circuit supervision with 1 binary input, 1 binary input is used to detect the disruption in
the closed circuit. The binary input is connected parallel to the close-command relay. The circuit-breaker auxil-
iary contact is bridged with an equivalent resistance R.

1438 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

[dw_CCS_1BI, 1, en_US]

Figure 9-44 Principle of the Closing-Circuit Supervision with 1 Binary Input

CCR Close-command relay


CB Circuit breaker
CB closing coil Circuit-breaker closing coil
AuxCon1 Circuit-breaker auxiliary contact 1 (open if the CB is closed)
AuxCon2 Circuit-breaker auxiliary contact 2 (closed if the CB is closed)
V-Ctrl Control voltage for the closed circuit
V-BI Input voltage for binary input
R Equivalent resistance

Depending on the switch position of the close-command relay, the binary input is either activated (H) or deac-
tivated (L). If the binary input is deactivated, a fault occurs. The fault can be one of the following conditions:

• A disruption

• An outage of the battery voltage

• An adhesion present on the contact surface of the CCR


The following table shows all the states of the closed circuit:
CCR CB AuxCon1 AuxCon2 >Closed Dynamic State Static State
contact
Open Open Closed Open H Normal operation with an open
circuit breaker
Open Closed Open Closed H Normal operation with a closed
circuit breaker
Closed Open Closed Open L Transient Fault
Closed Closed Open Closed L Transient, CCR is activated

SIPROTEC 5, 7SJ82/7SJ85, Manual 1439


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

Logic

[lo_CCS_1BI, 1, en_US]

Figure 9-45 Logic Diagram of the Stage Closing-Circuit Supervision with 1 Binary Input

The indication Closing-circuit failure is generated when the following 2 conditions are met:

• The binary input >Closed contact is deactivated.

• The Alarm delay has elapsed.

Equivalent Resistance R
The equivalent resistance R must be dimensioned such that the circuit-breaker closing coil is no longer acti-
vated when the circuit breaker is open. Simultaneously, the binary input must still be activated when the
command relay is open.
In order to ensure the minimum voltage for activating the binary input, Rmax results in:

[fo_CCS_general_Rmax, 1, en_US]

Because the circuit-breaker closing coil does not remain activated, Rmin results in:

[fo_CCS_general_Rmin, 1, en_US]

You can calculate the optimal value for the equivalent resistance R from the 2 values Rmin and Rmax:

[fo_CCS_general_R, 1, en_US]

1440 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

The following equation applies for the power consumption of the equivalent resistance R:

[fo_CCS_general_P, 1, en_US]

With:
VCtrl Control voltage for the closed circuit
VBImin The minimum voltage to activate the binary input
IBImax The maximum current to activate the binary input
RCBC The resistance of the circuit-breaker closing coil
VCBC(Lowmax) The maximum voltage flow through the circuit-breaker closing coil, which does not result in
the closing of the circuit breaker

9.3.14.5 Application and Setting Notes

Parameter: Alarm delay

• Default setting (_:100) Alarm delay = 2 s (Closing-circuit supervision with 2 binary inputs)

• Default setting (_:100) Alarm delay = 300 s (Closing-circuit supervision with 1 binary input)
With the parameter Alarm delay, you can set the time for the delayed output of the indication Closing-
circuit failure.
For the stage Closing-circuit supervision with 2 binary inputs, set the parameter Alarm delay so that the
short-term transient states do not cause the function to activate.
For the stage Closing-circuit supervision with 1 binary input, set the parameter Alarm delay so that the
longest duration of a close command is bridged without fail. This setting ensures that the function is activated
only when the closed circuit is disrupted.

9.3.14.6 Settings

Addr. Parameter C Setting Options Default Setting


74CC sup.1BI #
_:1 74CC sup.1BI #:Mode • off on
• on
• test
_:100 74CC sup.1BI #:Alarm 1.00 s to 600.00 s 300.00 s
delay
74CC sup.2BI #
_:1 74CC sup.2BI #:Mode • off on
• on
• test
_:100 74CC sup.2BI #:Alarm 1.00 s to 30.00 s 2.00 s
delay

9.3.14.7 Information List

No. Information Data Class Type


(Type)
74CC sup.1BI #
_:82 74CC sup.1BI #:>Block function SPS I
_:500 74CC sup.1BI #:>Closed contact SPS I

SIPROTEC 5, 7SJ82/7SJ85, Manual 1441


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.3 Supervision of the Secondary System

No. Information Data Class Type


(Type)
_:54 74CC sup.1BI #:Inactive SPS O
_:52 74CC sup.1BI #:Behavior ENS O
_:53 74CC sup.1BI #:Health ENS O
_:71 74CC sup.1BI #:Closing-circuit failure SPS O
74CC sup.2BI #
_:82 74CC sup.2BI #:>Block function SPS I
_:500 74CC sup.2BI #:>Closed contact SPS I
_:503 74CC sup.2BI #:>CB auxiliary contact SPS I
_:54 74CC sup.2BI #:Inactive SPS O
_:52 74CC sup.2BI #:Behavior ENS O
_:53 74CC sup.2BI #:Health ENS O
_:71 74CC sup.2BI #:Closing-circuit failure SPS O

1442 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.4 Supervision of the Device Hardware

9.4 Supervision of the Device Hardware

9.4.1 Overview

The correct state of the device hardware is a requirement for the correct functioning of the device. The failure
or erroneous function of a hardware component leads to device malfunctions.
The following modules of the device hardware are monitored:

• Base module

• Expansion modules

• Plug-in modules on the interface locations


The error responses result, depending on type and degree of the error, as follows:
Hardware errors where the device remains in operation.
The error is indicated. The signals/data affected by the failure are marked as invalid. In this way, the affected
protection functions can switch into a secure state. Such errors are, for example:

• Communication-module failure (module x)

• Measuring-transducer module failure (module x)

• USB interface

• Integrated Ethernet interface

• Real-time clock device

• A/D converter (fast current sum)

• Battery voltage

• Faulty or missing compensation values (magnitude/phase)


Failures which can partially be corrected by a restart of the device. The device goes briefly out of opera-
tion.
Such errors are, for example:

• Memory error (RAM) in the base module

• Defective module

• Module-connection error (PCB Link)

• Control circuit error binary output

• Outage of an internal auxiliary voltage

NOTE

i If the error has not be rectified after 3 unsuccessful attempts, the system automatically recognizes it as a
severe device malfunction. The device goes permanently out of operation into a secure state (fallback
mode).

Fatal device errors with outage of central components: The device goes permanently out of operation
into a secure state (fallback mode).
Such errors are, for example:

• Memory error (flash) in the base module

• CPU/Controller/FPGA error in the base module

• 3 unsuccessful restarts in a row


You can find the detailed description of the error responses in table form at the end of this chapter. You will
find corresponding corrective measures there.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1443


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.4 Supervision of the Device Hardware

Device Operating Hours


The Device operating hours statistical value counts the operating hours of the physical device. The
starting time and the time in Fallback mode are not considered.
You can neither reset nor change the statistical value.

9.4.2 Analog-Channel Supervision via Fast Current-Sum

9.4.2.1 Overview of Functions


The function Supervision of the device-internal analog-digital converters it performs the following tasks:

• Supervision of the correct functioning of the device-internal analog-digital converters, based on the sum
of all currents of one measuring point in the secondary circuit.

• Detection of failures in the device-internal measuring circuits (for example, analog-digital converter)

• Blocking of protection and control functions that process the measured values from this current meas-
uring point (for example, differential protection). This avoids an overfunction of the device.
The supervision principle is based on fast current sum supervision with connection of the neutral-point current
to the 4th current measurement input. In order to ensure that even the fast tripping stages of the protection
functions can be blocked in time before a spurious pickup, the fast current measurement is based on instanta-
neous values.
For Analog-digital converter supervision, the neutral-point current of the line to be protected must be
connected to the 4th current measuring input (IN). The 4th current measuring input must be routed via the
current-transformer neutral point (IN neutral point) (see next figure).

[tileite2-070211-01.tif, 3, en_US]

Figure 9-46 Connection to a 3-Phase Current Transformer and Measured Zero-Sequence Current (Current
in Common Return Path)

NOTE

i The analog channel supervision via fast current sum is only available when the 4th current input is a
protection-class current transformer. In the DIGSI 5 project tree, under Device → Measuring-point
routing, set the connection type 3-phase + IN for the current measuring point.

9.4.2.2 Structure of the Function


The Supervision of the device-internal analog-digital converters function is located in the Power-system
data function group of each 3-phase current measuring point.

1444 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.4 Supervision of the Device Hardware

[dwschstr-040211-01.tif, 1, en_US]

Figure 9-47 Structure/Embedding of the Function

9.4.2.3 Function Description


Errors in the current circuits are detected if
IF = |iA + iB + iC + iN| > Threshold value + Slope of the characteristic 1 •Σ| i | and
IF > Slope of the characteristic 2 • (Σ| i | - Base point 2)
With the current inputs (iA, iB, iC, and iN), the device calculates:

• Fault current IF = |iA + iB + iC + iN|

• Maximum current Σ| i | = |iA|+|iB|+|iC|+ |iN|

[lokenisu-240413-01.tif, 2, en_US]

Figure 9-48 Characteristic Curve of the Supervision of the Device-Internal Analog-Digital Converters

SIPROTEC 5, 7SJ82/7SJ85, Manual 1445


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.4 Supervision of the Device Hardware

Logic

[losumsch-240413-01.tif, 3, en_US]

Figure 9-49 Logic Diagram of the Supervision of the Device-Internal Analog-Digital Converters

When the output signal A/D converter monit. is active, certain protection functions are blocked to avoid
failures (see 12.72 Analog Channel Supervision via Fast Current Sum ).

NOTE

i The parameters are fixed in the device and cannot be changed.


It is not necessary to change the parameters depending on the application.

Threshold Value
The threshold value is the lower limit of the operating range of the Supervision of the device-internal
analog-digital converters function.
The threshold value is permanently set to 10 % of the device rated current.

Slope of the Characteristic 1


The component Slope of the characteristic 1 • Σ | i | takes into account permissible errors of the current input
that can occur in the case of small overcurrents.
The Slope of the characteristic 1 is permanently set to 0.1.

Slope of the Characteristic 2


The component Slope of the characteristic 2 takes into account permissible errors of the current input that
can occur in the case of high overcurrents (high short-circuit currents).

1446 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.4 Supervision of the Device Hardware

The Slope of the characteristic 2 is permanently set to 0.95. The base point of the Slope of the character-
istic 2 is permanently set to 10.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1447


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.5 Supervision of Device Firmware

9.5 Supervision of Device Firmware


The device firmware determines essentially the functionality of the device.
The following supervisions ensure the stable function of the device:

• Supervisions of the data and version consistency

• Supervision of the undisturbed sequential activity of the device firmware

• Supervision of the available processor performance


When you start the device, load data via the interfaces and these supervisions of the device firmware will be in
effect during the continuous operation. Depending on the type and severity of error, the following error
responses will result:

Firmware failures where the device remains in operation.


The error is indicated. The signals/data affected by the failure are marked as invalid. In this way, the affected
protection functions can go into a secure state. Such errors are, for example, errors in time synchronization
(loss and errors).

Failures which can partially be corrected by a restart of the device. The device goes briefly out of
operation.
Such errors are, for example:

• Device startup with faulty new parameter set. The old parameter set is still present.

• Overloading of the processor

• Program-sequence error

Fatal firmware error. The device goes permanently out of operation into a secure state (fallback mode).
Such errors are, for example:

• Device startup with faulty new parameter set. No usable parameter set is present.

• Device startup with version error

• CFC-runtime error

• 3 unsuccessful restarts in a row


You can find the detailed description, in table form, of the fault responses at the end of chapter 9.8 Error
Responses and Corrective Measures. You will find corresponding corrective measures there.

1448 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.6 Supervision of Hardware Configuration

9.6 Supervision of Hardware Configuration


The modular hardware concept requires adherence to some rules within the product family and the modular
system. Configuration errors show that the hardware configuration saved in the device does not agree with
the hardware actually detected. Impermissible components and unallowed combinations must be detected
just as missing configured components are.
Depending on the type and severity of error, the following error responses will result: The identified hardware
configuration errors are assigned to the defect severities as follows:

Configuration errors for which the device remains in operation.


The failure is indicated. The signals/data affected by the failure are marked as invalid. In this way, the affected
protection functions can go into a secure state. Such errors are, for example, errors in the IE converter config-
uration (normal/sensitive).

Fatal configuration error: The device goes permanently out of operation into a secure state (fallback
mode).
Such errors are, for example:

• Missing hardware module (module x)

• Incorrect hardware module (module x)

• Incorrect hardware combination

• Incorrect plug-in module (module x)


You can find the detailed description of the error responses in table form at the end of this chapter. You will
find corresponding corrective measures there. You can resolve configuration errors through another synchro-
nization with DIGSI.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1449


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.7 Supervision of Communication Connections

9.7 Supervision of Communication Connections


SIPROTEC 5 devices offer extensive communication possibilities via fixed and optional interfaces. Beyond the
hardware supervision of the communication plug-in modules the transferred data must be monitored with
respect to their consistency, failure, or outage.

Supervision
With the supervision of the communication connections, every communication port is monitored selectively.

• Failures are detected and indicated via the operational log. The device remains in operation!

• Each port additionally is equipped with a separate communication log, with which details of the failures
(for example, error rate) are displayed.

Marking Fault Signals/Data


The signals/data affected by the failure are marked as invalid. In this way, the affected protection functions
can go into a secure state. In the following, some examples are named:

• GOOSE signals can automatically be set to defined values in case of disturbed IEC 61850 communication.

• Disturbed protection interfaces set phasor values, both analog measured values and binary information
to invalid (for example, for differential protection). Binary signal traces can be set to defined values in
cases of failures.

• Disturbed time-synchronization signals can lead to an automatic change of the source of time synchroni-
zation.
Normally, you can correct communication failures by checking the external connections or by replacing the
affected communication modules. In chapter 9.8.2 Defect Severity 1 to 9.8.4 Defect Severity 3 you will find
the detailed description, in tabular form, of the error responses. Corresponding corrective measures can also
be found there.

1450 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

9.8 Error Responses and Corrective Measures

9.8.1 Overview

When device errors occur and the corresponding supervision functions pick up, this is displayed on the device
and also indicated. Device errors can lead to corruption of data and signals. These data and signals are marked
and tagged as invalid, so that affected functions automatically go into a secure state. If the supervision func-
tions pick up, this will lead to defined error responses.

How Do Device Errors Make Themselves Noticeable


In case of a device error the supervision functions of the device pickup. The device responds according to the
type and severity of the error. To report an error, supervision functions use outputs on the device and indica-
tions.
Run LED (green) The external auxiliary voltage is present. The device is ready for operation.
Error LED (red) The device is not ready for operation. The life contact is open.
Life contact Signaling of device readiness following successful device startup.
Group-warning indication The device remains in operation and signals an error via the prerouted LED
Group warning and the log.
Log of the device Indications of causes for defects and corrective measures

Determination of Causes for Defects and Corrective Measures


To determine the cause for defect and the corresponding corrective measure, proceed step by step.
Step 1: Pick up of supervisions leads to one of the following defect severities in all cases.

• Defect severity 1:
Internal or external device error that is reported. The device remains in operation.
• Defect severity 2:
Severe device failure, the device restarts (reset) to correct the cause for defect.
• Defect severity 3:
Severe device failure, the device goes to a safe condition (fallback mode), as the
correction of defects cannot be implemented by a restart. In fallback mode, the
protection and automated functions are inactive. The device is out of operation.
• Defect severity 4:
Severe device-external failure, the device switches the protection and automatic
functions to inactive for safety, but remains in operation. Normally, the user can
correct the fault by himself.
Step 2: For every defect severity, you will find detailed tables with information about causes
for defects, error responses, and corrective measures in the following chapters.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1451


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

Table 9-2 Error Responses

All Protection and Automation Functions


Group-Warning Indication

Device-Diagnosis Log

Indication of the
Operational Log
Group Warning

Fallback Mode
Device restart
Indication in

Indication in

Life Contact

are inactive

(Reset)
Defect Severity 1 x x x – – – –
Defect Severity 2 – – x x During the x –
starting time of
the device
Defect Severity 3 – – x x x – x
Defect Severity 4 – x – x x – –

9.8.2 Defect Severity 1

Defect severity 1 faults allow the continued safe operation of the device. Defect severity 1 faults are indicated.
The device remains in operation.
When the supervision functions pick up, corrupted data and signals are marked as invalid. In this way, the
affected functions can go into a secure state. Whether functions are blocked is decided in the appropriate
function itself. For more detailed information, refer to the function descriptions.
Live status contact Remains activated
Red error LED Is not activated

Log
For every device fault, a corresponding supervision indication is generated. The device records these indica-
tions with a real-time stamp in the operational log. In this way they are available for further analyses. If super-
visions in the communication interfaces area of the device pick up, there is a separate communication log
available for each port. Extended diagnostic indications and measured values are available there. The device-
diagnosis log contains expanded fault descriptions. There you also receive recommendations of corresponding
corrective measures for each detected device error.
There is further information on handling the logs in chapter 3.1 Indications.

Group-Warning Indication Group Warning


In delivery condition, all supervision indications of Defect Severity 1 are routed to the signal (_:301) Group
warning. In this way, a device error can be indicated with only one indication. The majority of supervision
indications are permanently connected to the Group warning (Group warning column = fixed). However,
some supervision indications are routed flexibly to the Group warning via a CFC chart (Group warning
column = CFC). If necessary, you can remove again the routings via a CFC chart from the group indication.
In delivery condition, the Group warning is prerouted to an LED.
The following logic diagram shows the context.

1452 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

[lo_warning_indication, 1, en_US]

Figure 9-50 Forming the Group-Warning Indication Group Warning

Overview of Errors

Indication Type Group Explanation


Warning
General:
(_:53) Health ENS CFC If the Health of an individual function block, for example
(_:53) Health = Warning SPS a protection stage or an individual function, goes to the
Warning or Alarm state, this state is processed via the
(_:53) Health = Alarm SPS
associated function group up to the general group indica-
tion Health (_:53).
Check from the operational log from which function or
function block the error originates. In the associated func-
tion description, there is additional information as to why
the Health of the function or a function block can change.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1453


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

Indication Type Group Explanation


Warning
Device:
_:320 Auxiliary Power Fail SPS Fixed Fault with the auxiliary power supply:
Check the external power supply.
If the device has a redundant PS204 power-supply module,
this indication is not provided and is replaced by the indica-
tions for a device with PS204 that are described in the
following.
(_:305) Battery failure SPS Battery fault:
Replace the device battery.
To avoid data losses, Siemens recommends replacing the
device battery with the device supply voltage switched on.
You can find more detailed information about the disposal
of the battery in the Hardware Manual, version V07.80 and
higher (Order number: C53000-G5040-C002-D).
_:312 Compensation error x ENS Calibration error on module x:
Contact the Customer Support Center.
Quality: Measured values are marked with the quality
attribute questionable (measured-value display with ≈).
_:314 Offset error x ENS Offset error on module x:
If this indication persists after the device start, contact the
Customer Support Center.
Quality: Measured values are marked with the quality
attribute questionable (measured-value display with ≈).
_:306 Clock fail SPS Internal time failure

• Check the time settings first.


• Then replace the device battery.
• If the fault is not remedied, contact the Customer
Support Center.
Quality: The internal time is marked with the quality
attribute Clock Failure.
(_:319) Error memory SPS Checksum (CRC) error in monitored memory areas of the
device
Measuring-transducer error ENS Hardware error on the measuring-transducer module on
(x) plug-in module position E/F/M/N/P:
Contact the Customer Support Center.

1454 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

Indication Type Group Explanation


Warning
Device with redundant PS204 power-supply module:
_:330 Power sup. Module INS CFC Device-internal error on the power-supply module at posi-
fail. x tion x40:

• As the deice has a redundant PS204 power-supply


module, the device remains in operation as long as
this module is OK.
• Exchange the defective power-supply module so that
redundancy is re-established!
_:331 Power sup. Module OK x INS No device-internal error on the power-supply module at
position x40.
_:332 Pow. sup. aux. pow. INS Error on the external auxiliary power supply of the power-
fail. x supply module at position x40:

• As the deice has a redundant PS204 power-supply


module, the device remains in operation as long as
this module is OK.
• Check the auxiliary power supply of the device-
internal power-supply module.
_:333 Power sup.aux.pow.OK x INS The external auxiliary power supply of the power-supply
module at position x40 is OK.
Handling an alarm:
(_:504) >Group Warning SPS Fixed Input signal for user-defined generation of group warning
Time sync.:
(_:305) Time sync. error SPS Fixed Time synchronization error, the timing master is faulty:

• Check the external time source first.


• Check the external connections.
• If the fault is not remedied, contact the Customer
Support Center.
Quality: The internal time is marked with the quality
attribute Clock not synchronized.
Power-system data:meas. point Failure of the current balance (see chapter 9.3.10.1 Over-
SPS CFC
I-3ph:superv. bal. I: view of Functions )
(_:71) Failure
Power-system data:meas. point Failure of current phase-rotation supervision (see chapter
SPS CFC
I-3ph:superv. Phsseq.I: 9.3.12.1 Overview of Functions )
(_:71) Failure
Power-system data:meas. point Failure of the current sum (see chapter 9.3.11.1 Overview
SPS CFC
I-3ph:superv. Sum I of Functions )
(_:71) Failure

40 x means the mounting position of the module (x = 1,2,3,...)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1455


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

Indication Type Group Explanation


Warning
Power-system data:meas. point Failure of the quick current sum (see chapter 9.4.2.1 Over-
SPS CFC
I-3ph:superv.ADC sum.I: view of Functions)
(_:71) Failure The failure indication indicates a fault in the analog-digital
converter at the power input.

• Check the exterior wiring.


• If the fault is not remedied, contact the Customer
Support Center.
Quality: The internally managed current measured values
are marked with the quality attribute invalid.
Blocking: The protection functions based on current meas-
urement are blocked.
Power-system data:meas. point V-3ph: Voltage-transformer circuit breaker is open.
SPS CFC
Volt.Trans.Cir.B: Blocking: Appropriate functions are either blocked defi-
(_:500) >Open nitely or the blocking can be set individually.
Power-system data:meas. point V-3ph: Failure of the voltage balance (see chapter 9.3.5.1 Over-
SPS CFC
Superv. of Bal. V: view of Functions )
(_:71) Failure
Power-system data:meas. point V-3ph: Failure of voltage phase-rotation supervision (see chapter
SPS CFC
Superv. Phsseq.V: 9.3.7.1 Overview of Functions )
(_:71) Failure
Power-system data:meas. point V-3ph: Failure of the voltage sum (see chapter 9.3.6.1 Overview
SPS CFC
Superv. of Sum V: of Functions )
(_:71) Failure
2 devices prot. comm.: Protection inter- Protection interface connection defective:
face #:
• Check the connections and the external communica-
(_:303) Connection broken SPS CFC 41 tion infrastructure.
SPS
(_:316) Error rate / min
exc.
• If the fault is not remedied, contact the Customer
Support Center.
(_:317) Error rate / hour SPS
Transferred signals: Faulty or not received telegrams are
exc.
detected at the receive end and discarded. They do not
(_:318) Time delay exceeded SPS result in failure of the applications. Configured binary
(_:320) Time delay jump SPS signals are reset after a time that can be set.
VI-3ph: Mess.Volt.Fail detected: Measuring-voltage failure detected:
SPS CFC
(_:300) Failure Check the exterior wiring.
Blocking: Appropriate functions are either blocked defi-
nitely or the blocking can be set individually.

9.8.3 Defect Severity 2

Faults of defect severity 2 are fatal device faults that lead to an immediate restart of the device (reset).
This occurs when the device data is corrupted (for example, RAM memory), if a restart prevents restoration of
data consistency. The device goes briefly out of operation, a failure is avoided.
Life contact Is terminated during the restart
Red error LED Is activated during the restart

41 The indications are not prerouted in the CFC. The indications must be added to by the user in the CFC!

1456 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

NOTE

i If the fault of defect severity 2 has not be been removed after 3 unsuccessful restarts (reset), the fault is
automatically assigned to defect severity 3. The device will automatically turn to the fallback mode.

Log
For every device error with a subsequent restart (reset), only the restart can be detected in the operational log.
The actual supervision indication is entered in the device-diagnosis log at the point in time of the fault detec-
tion and before the restart. These indications are recorded with a real-time stamp and are thus available for
later analyses. The device-diagnosis log contains expanded fault descriptions. There you also receive recom-
mendations of corresponding corrective measures for each detected device error.
You can find further information on handling the logs in chapter 3.

Overview of Errors

Number Device-Diagnosis Log


826 Processor error on the base module:
If the fault occurs numerous times, contact the Customer Support Center.
830 FPGA hardware error on the base module:
Contact the Customer Support Center.
834 Memory error (short term):
Reset initiated.
3823 Program run error:
If the fault occurs numerous times, contact the Customer Support Center.
826 CPU overload:
If the fault occurs numerous times, contact the Customer Support Center.
Miscellaneous Internal firmware error:
If the fault occurs numerous times, contact the Customer Support Center.

9.8.4 Defect Severity 3

Faults of defect severity 3 are fatal device faults that lead to device immediately going into the fallback mode.
The signal (_:301) Device status goes to the Alarm state. The Warning state is not supported for this
signal.
Fatal device errors are errors that cannot be resolved by a restart of the device. In this case, contact the
Customer Support Center. The device goes permanently out of operation, a failure is avoided. In the fallback
mode, minimal operation of the device via the on-site operation panel and DIGSI is possible. In this way, for
example, you can still read out information from the device-diagnosis log.
Life contact Is terminated in the fallback mode
Red error LED Is activated in the fallback mode

Log
For every device error that immediately leads to entry into the fallback mode, entries from supervision
messages and from the signal (_:301) Device status into the operational log are not possible. The
actual supervision indication is entered in the device-diagnosis log at the point in time of the fault detection,
that is, before entry into the fallback mode. These indications are recorded with a real-time stamp and are thus
available for later analyses. The device-diagnosis log contains expanded fault descriptions. There, you are
offered recommendations of corresponding corrective measures for each detected device error.
You can find further information on handling the logs in chapter 3.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1457


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

Overview of Errors

Number Device-Diagnosis Log


2822 Memory error (continuous)
Contact the Customer Support Center.
4727, 5018-5028 Hardware failure at module 1-12:
Contact the Customer Support Center.
4729 Device bus error (repeated):

• Check the module configuration and the module connections.


• Contact the Customer Support Center.
4733 Incorrect hardware configuration:
Synchronize the hardware configuration of the device with DIGSI.
5037-5048 Wrong module 1-12 detected:
Synchronize the hardware configuration of the device with DIGSI.
5031-5035 Identified wrong plug-in module on plug-in module position E/F/M/N/P:
Synchronize the hardware configuration of the device with DIGSI.
Wrong application configuration:
Search for the cause in the operational log and load a valid configuration to the device.
3640, 4514 Data-structure error:
Contact the Customer Support Center.
956 Firmware-version error:
Contact the Customer Support Center.
2013, 2025 Signature error:
Contact the Customer Support Center.
CFC error:
In DIGSI, check your CFC chart for the cause.
5050-5061 Binary-output error in module 1 - 12:
Contact the Customer Support Center.
5088, 5089 A missing display configuration was established:
Synchronize the hardware configuration of the device with DIGSI.

9.8.5 Defect Severity 4 (Group Alarm)

Errors of defect severity 4 are not device failures in the classical meaning. These errors do not affect the device
hardware and are not detected or reported by internal device supervision functions. The condition of the
defect severity 4 – the group alarm – is set user-specifically by the binary input signal (_:503) >Group
alarm. If the binary input signal is reset, the device is no longer in the Group alarm condition and all func-
tions return to the normal operating state.
If the group alarm is generated, the device reacts as follows:

• The group indication (_:300) Group alarm is generated and recorded in the operational log.

• The life contact is terminated.

• The red Error LED is activated.

• All protection and automation functions are blocked.

• The device remains in operation, does not carry out any restart (reset), and does not switch to the safe
condition (Fallback mode).

• The signals managed internally are marked with the invalid quality attribute. Signals managed inter-
nally are, for example, measured values, binary input and output signals, GOOSE and CFC signals.

1458 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.8 Error Responses and Corrective Measures

In the delivery condition, every device has the CFC chart Process mode inactive, that initiates the Group
alarm (see chapter 9.9 Group Indications).
Life contact Is terminated in case of Group alarm
Red error LED Is initiated in case of Group alarm

Log
The group indication (_:300) Group alarm is recorded in the operational log. Depending on the cause of
the initiation, further information can be found in the operational log.
You can find further information on handling the logs in chapter 3.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1459


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.9 Group Indications

9.9 Group Indications


The following group indications are available:

• (_:300) Group alarm


• (_:301) Group warning
• (_:302) Group indication
You can find the signals in the DIGSI 5 project tree under Name of the device → Information routing. In the
operating range, you can find the signals under Alarm handling (see the following figure).

[scgrwarn-010313-01, 1, en_US]

Figure 9-51 Group Monitoring Indication in the DIGSI 5 Information Routing Matrix

Group Indication Group Alarm


The indication (_:300) Group alarm is the group indication for defect severity 4 monitoring. This moni-
toring has a special purpose, as it is set user-specifically by a binary input signal and not by internal device
supervision. Nevertheless, the response of the device is serious, such as blocking all protection and automatic
functions (see chapter 9.8.5 Defect Severity 4 (Group Alarm)).
If the binary input signal (_:503) >Group Alarm is set, the group indication (_:300) Group alarm
becomes active. If the binary input signal (_:503) >Group Alarm is reset, the signal (_:300) Group
alarm is also reset and the device returns to the normal operating state.
In the delivery condition, every device has the CFC chart Process mode inactive, that initiates the >Group
Alarm. This CFC chart checks whether the device is still accidentally in the simulation or commissioning
mode.
You can adapt the CFC chart as needed. You can find the CFC chart in the DIGSI 5 project tree under Name of
the device → Charts.

Group Indication Group Warning


The indication (_:301) Group warning is the group indication for defect severity 1 monitoring. Some
error messages of defect severity 1 are firmly linked to the signal (_:301) Group warning, others are
connected flexibly in the device delivery condition via a CFC chart. This assignment is described in chapter
9.8.2 Defect Severity 1.
In the delivery condition, every device has the CFC chart Group warning, that initiates the Group warning.

1460 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Supervision Functions
9.9 Group Indications

You can adapt the CFC chart as needed. You can find the CFC chart in the DIGSI 5 project tree under Name of
the device → Charts.
The group-warning indication (_:301) Group warning is prerouted to an LED of the base module.

Group Indication
The Group indication is exclusively for user-specific purposes. There is no internal device supervision
function that activates this indication. If the binary input signal (_:505) >Group indication is set, the
indication (_:302) Group indication becomes active and is recorded in the operational log. This
warning indication does not result in blocking a protection function. If the binary input signal is reset, the
signal (_:302) Group indication drops out. Using a CFC chart, you can define when the binary input
signal (_:505) >Group indication is to be set.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1461


C53000-G5040-C017-A, Edition 06.2019
1462 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
10 Measured Values, Energy Values, and Supervision
of the Primary System

10.1 Overview of Functions 1464


10.2 Structure of the Function 1465
10.3 Operational Measured Values 1467
10.4 Fundamental and Symmetrical Components 1469
10.5 Average Values 1470
10.6 Minimum/Maximum Values 1473
10.7 Energy Values 1475
10.8 User-Defined Metered Values 1478
10.9 Phasor Measurement Unit (PMU) 1482
10.10 Measuring Transducers 1502
10.11 Statistical Values of the Primary System 1509
10.12 Circuit-Breaker Wear Monitoring 1510

SIPROTEC 5, 7SJ82/7SJ85, Manual 1463


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.1 Overview of Functions

10.1 Overview of Functions


The measurands are recorded at the measuring points and forwarded to the function groups.
Within the function groups, further measurands are calculated from these measured values, which are
required for the functions of this function group. This is how, for example, the electric power is calculated
from the voltage and current measurands.
Measuring transducers are an exception as they already form various calculation parameters from the analog
current and voltage inputs themselves.
Basic instructions for recording and editing process data can be found in the chapter 2.1 Function Embedding
in the Device.

[dwomverf-010212-01.tif, 1, en_US]

Figure 10-1 Structure of Measured-Value Acquisition and Processing

For the display, the measured values of a SIPROTEC 5 device are summed up in the following groups:

• Operational measured values

• Fundamental and symmetrical components

• Function-specific measured values

• Minimum values, maximum values, average values

• Energy metered values

• User-defined measured and metered values

• Statistical values

1464 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.2 Structure of the Function

10.2 Structure of the Function


Depending on the interconnection of the function groups, these can contain different measured-value groups.
2 typical function groups are displayed below.

Voltage/Current 3-Phase Function Group


In the simplest version, the Voltage/current 3-phase function group obtains the measured values of the 3-
phase voltage and current system and contains the following measured-value groups:

[dwstrciv-011012-01.tif, 1, en_US]

The Minimum values/Maximum values/Average values and User-defined values can be inserted from the
library into the Voltage/Current 3-phase function group.
Details regarding the individual measured value groups can be found in the tables in the following chapters.

Circuit-Breaker Function Group


The Circuit-breaker function group may contain the following measured values:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1465


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.2 Structure of the Function

[dwomvls1-250211-01.tif, 1, en_US]

Inversion of Output-Related Measured and Statistical Values


The calculated, directional values in the operational measured values (power, power factor, energy and
minimum, maximum, and average values based on these) are normally defined as positive in the direction of
the protected object. This requires that the connection polarity for the used measuring points be correctly set
(see also parameter (_:8881:116) Neutr.point in dir.of ref.obj of the measuring point current,
3-phase). It is, however, possible, to set the "forward" direction for the protection functions and the positive
direction for the powers, etc., differently, for example, such that the active power consumption (from the line
to the busbar) is displayed positively. Then set the option reversed in the affected function groups at the
parameter P, Q sign. With the setting not reversed (default setting), the positive direction for the
powers etc. corresponds to the "forward" direction for the protection functions.
The affected values are given in detail in the chapters 10.3 Operational Measured Values - 10.11 Statistical
Values of the Primary System.

1466 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.3 Operational Measured Values

10.3 Operational Measured Values


Operational measured values are assigned to different function groups.
The values can be displayed as primary and secondary values and as percentage values.
The operational measured values are calculated according to the following definition equations:
RMS values

Active power

Apparent power

Reactive power

n Harmonic order
φn The angle difference between the voltage and current of the nth harmonic
Power factor

Active factor

Voltage/Current 3-Phase Function Group


The following table describes the operational measured values of the Voltage/current 3-Phase function group.
All protection functions have access to the values.

Table 10-1 Operational Measured Values of the Voltage/Current 3-Phase Function Group

Measured Values Primary Secon- % Referenced to


dary
IA, IB, IC Phase currents A A Rated operating current of the primary values
3I0 Calculated zero-sequence A A Rated operating current of the primary values
current
IN Neutral-point phase current A A Rated operating current of the primary values
VA, VB, VC Phase-to-ground voltages kV V Rated operating voltage of the primary values/
√3
VAB, VBC, VCA Phase-to-phase voltage kV V Rated operating voltage of the primary values
V0 Calculated zero-sequence kV V Rated operating voltage of the primary values/
voltage √3
VN Measured neutral-point kV V Rated operating voltage of the primary values/
displacement voltage √3
f Frequency Hz Hz Rated frequency
P Active power MW – Active power of the primary values
(total power) √3 · Vrated · Irated
Q Reactive power Mvar – Reactive power of the primary values
(total power) √3 · Vrated · Irated
S Apparent power MVA – Apparent power of the primary values
(total power) √3 · Vrated · Irated

SIPROTEC 5, 7SJ82/7SJ85, Manual 1467


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.3 Operational Measured Values

Measured Values Primary Secon- % Referenced to


dary
Cos φ Active factor (abs) (abs) 100 % corresponds to cos φ = 1
PA, PB, PC Phase-related active power MW – Active power of the phase
Vrated phsx · Irated phsx
QA, QB, QC Phase-related reactive power Mvar – Reactive power of the phase
Vrated phsx · Irated phsx
SA, SB, SC Phase-related apparent MVA – Apparent power of the phase
power Vrated phsx · Irated phsx

NOTE

i With the parameter P, Q sign in the function block General of the respective function group, the sign of
the following measured values can be inverted:

• Active power (total): P total

• Active power (phase-related): PA, PB, PC

• Reactive power (total): Q total

• Reactive power (phase-related): QA, QB and QC

1468 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.4 Fundamental and Symmetrical Components

10.4 Fundamental and Symmetrical Components


The fundamental components are calculated from the frequency-tracked instantaneous values through a
Fourier filter (integration interval: one period). The results are phasor values that are described by way of the
amount and phase angle.
In accordance with the transformation matrix, the symmetrical components are calculated from the voltage
and current phasors. These are also phasor quantities.

Fundamental Components

Table 10-2 Fundamental Components

Values Primary Secon- Phase % Referenced to


dary Angle
V A, V B, V C Phase-to-ground voltage kV V ° Rated operating voltage of primary
values/√3
VN Measured neutral-point displace- kV V ° Rated operating voltage of primary
ment voltage values/√3
V 12, V 23, Phase-to-phase voltage kV V ° Rated operating voltage of the
V 31 primary values

I A, I B, I C Phase currents A A ° Rated operating current of the


primary values
IN Neutral-point phase current A A ° Rated operating current of the
primary values

Symmetrical Components

Table 10-3 Symmetrical Components

Values Primary Secon- Phase % Referenced to


dary Angle
V0 Zero-sequence component of the kV V ° Rated operating voltage of primary
voltage values/√3
V1 Positive-sequence component of kV V ° Rated operating voltage of primary
the voltage values/√3
V2 Negative-sequence component of kV V ° Rated operating voltage of primary
the voltage values/√3
I0 Zero-sequence component of the A A ° Rated operating current of the
current primary values
I1 Positive-sequence component of A A ° Rated operating current of the
the current primary values
I2 Negative-sequence component of A A ° Rated operating current of the
the current primary values

SIPROTEC 5, 7SJ82/7SJ85, Manual 1469


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.5 Average Values

10.5 Average Values

10.5.1 Function Description of Average Values

Average values can be formed based on different measurands:

• Operational measured values

• Symmetrical components
Through the settings, you can set how and when the average values are formed. The settings describe:

• Time slot over which the average value is formed


(Parameter: Average calc. interval )

• Update interval for the display of the average values


(Parameter: Average update interval )

• Synchronization time for establishing the date of commencement updating information, for example, at
the top of the hour (hh:00) or at one of the other times (hh:15, hh:30, hh:45).
(Parameter: Average synchroniz. time )
Average values are formed through the following measurands:

• Operational measured values except for phase-related ratings

• Amounts of the symmetrical components


You reset the average value formation via the

• Binary input >Reset average value

• DIGSI

• The integrated operation panel

NOTE

i With the P, Q sign parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see Chapter 10.2 Structure of the Function Structure of
the Function, section Inversion of Output-Related Measured and Statistical Values):

• Active power (total): P total

• Reactive power (total): Q total

10.5.2 Application and Setting Notes for Average Values

The average value formation functionality is not preconfigured with the devices in the function group. If you
use the functionality, you must load it from the library into the respective function group.
The following settings listed for the calculation of the average values can be set with DIGSI and at the device.
You find the setting parameters in DIGSI in the project tree under Settings > Device settings.

Parameter: Average calc. interval

• Default setting: (_:104) Average calc. interval = 60 min

Parameter Value Description


1 min to 60 min Time slot for averaging, for example 60 minutes

Parameter: Average update interval

• Default setting: (_:105) Average update interval = 60 min

1470 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.5 Average Values

Parameter Value Description


1 min to 60 min Update interval for displaying the average value, for example 60 minutes

Parameter: Average synchroniz. time

• Default setting: (_:106) Average synchroniz. time = hh:00


The parameter describes the synchronization time for average value formation.

Parameter Value Description


hh:00 The parameter Average update interval will be
effective on the full hour
hh:15 The parameter Average update interval will be
effective 15 minutes after the full hour
hh:30 The parameter Average update interval will be
effective 30 minutes after the full hour
hh:45 The parameter Average update interval will be
effective 45 minutes after the full hour

NOTE

i The average value calculation restarts after

• Changing one of the 3 settings for the average-value calculation

• Resetting the device (initial or normal reset)

• Changing the time

• Resetting the average values


The average values are reset immediately. The display changes to "---".

The following examples explain how to set parameters and to make a change.

Average calc. interval = 60 min


Average update interval = 30 min
Average synchroniz. time = hh:15.

A new average value is formed every 30 min, at hh:15 (15 min after the top of the hour) and hh:45 (15 min
before the top of the hour). All measured values obtained during the last 60 min are used for average value
formation.
If these settings are changed to 11:03:25, for instance, the average values are first reset and "---" appears in
the display. The 1st average value is then formed at 12:15:00.
In this example, the Average synchroniz. time = hh:45 acts as described above for = hh:15.

Average calc. interval = 60 min


Average update interval = 60 min
Average synchroniz. time = hh:15.

A new average value is formed every 60 min at hh:15 (15 min after the top of the hour). All measured values
obtained during the last 60 min are used for average value formation.
If these settings are changed to 11:03:25, for instance, the average values are first reset and "---" appears in
the display. The 1st average value is then formed at 12:15:00.

Average calc. interval = 5 min


Average update interval = 10 min
Average synchroniz. time = hh:00.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1471


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.5 Average Values

A new average value is formed every 10 min at hh:00, hh:10, hh:20, hh:30, hh:40, hh:50. All measured
values obtained during the last 5 min are used to form the average value.
If these settings are changed to 11:03:25, for instance, the average values are first reset and "---" appears in
the display. The 1st average value is then formed at 11:10:00.

1472 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.6 Minimum/Maximum Values

10.6 Minimum/Maximum Values

10.6.1 Function Description of Minimum/Maximum Values

Minimum and maximum values can be formed based on different measured or calculated measurands:

• Operational measured values

• Symmetrical components

• Selected values
You can set which measurand will be used. The measurands for the minimum/maximum formation are loaded
from DIGSI.
Calculation and resetting of the minimum and maximum values are controlled through settings. The settings
describe the following points:

• Memories of the minimum/maximum values are reset to 0 cyclically or not at all.


(Setting Min/Max cyclic reset )

• Point in time when the memories of the minimum/maximum values are reset to 0.
(Setting Min/Max reset each and setting Min/Max reset minute )

• Point in time at which the cyclical reset procedure of the minimum/maximum values begins (after the
parameterization)
(Setting Min/Max days until start )
The following figure shows the effect of the settings.

[dwminmax-100611-01.tif, 1, en_US]

Figure 10-2 Minimum and Maximum-Value Formation

Minimum and maximum values are time-stamped.


Minimum/maximum values are formed through:

• Operational measured values except for phase-related ratings

• Amounts of the symmetrical components

• Average values
The minimum and maximum values are reset on a regular basis or via the

• Binary input >Reset min/max

• DIGSI

• The integrated operation panel

SIPROTEC 5, 7SJ82/7SJ85, Manual 1473


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.6 Minimum/Maximum Values

NOTE

i With the P, Q sign parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see Chapter 10.2 Structure of the Function Structure of
the Function, section Inversion of Output-Related Measured and Statistical Values):

• Minimum/maximum values of the active and reactive power:


Min:Ptotal, Max:Ptotal, Min:Qtotal, Max:Qtotal

• Minimum/maximum values of the average values of the active and reactive power:
AverageMin:Ptotal, AverageMax:Ptotal, AverageMin:Qtotal, AverageMax:Qtotal

10.6.2 Application and Setting Notes for Minimum/Maximum Values

The minimum/maximum values functionality is not preconfigured. If you want to use the functionality, you
must load it from the library into the respective function group.
The following settings listed for the calculation of the minimum/maximum values can be set with DIGSI or at
the device. You find the setting parameters in DIGSI in the project tree under Settings > Device settings.

Parameter: Min/Max cyclic reset

• Default setting: (_:107) Min/Max cyclic reset = yes

Parameter Value Description


Yes Cyclical resetting of the minimum and maximum value memories is acti-
vated
No Cyclical resetting of the minimum and maximum value memories is deacti-
vated
None of the following parameters are visible

Parameter: Min/Max reset each

• Default setting: (_:108) Min/Max reset each = 1 day

Parameter Value Description


1 day to 365 days Resetting of the minimum value and the maximum value, cyclically on all
specified days, for example each day (1 day)

Parameter: Min/Max reset minute

• Default setting: (_:109) Min/Max reset minute = 0 min

Parameter Value Description


0 min to 1439 min Resetting the minimum value and the maximum value at the specified
minute of the day, which is stated in the parameter Min/Max Reset
takes place every, for example 0 min 0 min (= 00.00)

Parameter: Min/Max days until start

• Default setting: (_:110) Min/Max days until start = 1 day

Parameter Value Description


1 day to 365 days Indication of when the cyclical reset procedure of the minimum values and
maximum values begins, for example in 1 day (after the parameterization)

1474 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.7 Energy Values

10.7 Energy Values

10.7.1 Function Description of Energy Values

The device continually determines the values for the active and reactive energy from the power-measured
values. It calculates the exported and imported electrical energy. The calculation (summation over time)
begins immediately after the device startup. You can read the present energy values on the device display or
through DIGSI, delete the energy value (set to 0), or set it to any initial value. After input, the energy-value
calculation will continue with the new setting values.
Energy values can be transferred to a control center through an interface. The energy values are converted
into energy metered values. Here the following applies:

[foomverg-020311-01.tif, 1, en_US]

Through the settings, you set how the metered values are processed. The setting parameters apply for all
energy metered values of the device, and do not have a function-group specific effect. You determine the
following points:

• Parameter Energy restore time


Hour-related point in time; at this point in time, the device will provide a metered value at the communi-
cation interface for transmission. After this, it will be transferred in accordance with the selected log.
Note: If the parameter is activated through a time setting, the parameter Energy restore interval
will be deactivated automatically.

• Parameter Energy restore interval


Adjustable period in minutes until the first and every further transfer of the metered value to the commu-
nication interface of the device. After this, it will be transferred in accordance with the selected log.
Note: The transfer interval is used alternatively to the transfer time, and deactivates the set transfer time.
The display of the device is always up to date.
You will find these parameters in the device settings under measured values.
In addition, restoring can be triggered via a routable binary input (>Restoring). The rising edge of the binary
input leads to restoring, that is, provision of the energy-metered value at the communication interface.
The metered-value memory and the energy values can be set to 0 via a binary input (>Resetting) if there is
a rising edge.
Note: The binary inputs affect all energy/energy metered values simultaneously.
The following energy values are available:
Energy Values Primary
Wp+ Active energy, output kWh, MWh, GWh
Wp- Active energy, input kWh, MWh, GWh
Wq+ Reactive energy, output kvarh, Mvarh, Gvarh
Wq- Reactive energy, input kvarh, Mvarh, Gvarh

In compliance with IEC 61850, when individually measured values are missing, the quality of the energy-
metered values changes to the state Questionable.
This quality state is retained until a new meter content is specified for the energy value by:
- Confirmation of the current meter content via Set
- Setting a new counter status
- Resetting the counter status to 0

SIPROTEC 5, 7SJ82/7SJ85, Manual 1475


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.7 Energy Values

NOTE

i With the P, Q sign parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see chapter 10.2 Structure of the Function, section on the
Inversion of Output-Related Measured and Statistical Values):

• Active energy, output: Wp+

• Active energy, input: Wp-

• Reactive energy, output: Wq+

• Reactive energy, input: Wq-

10.7.2 Application and Setting Notes for Energy Values

The set parameters apply for all electricity meters of the device. You find the setting parameters in DIGSI in the
project tree under Settings > Device settings.

Parameter: Energy restore interval

• Default setting: (_:111) Energy restore interval = 10 min

Parameter Value Description


0 min Restoring deactivated
60 min Cyclical restoring after the set time 1 minute to 60 minutes

Note: If the parameter is activated through a time setting, the parameter Energy restore time is not in
effect and will be deactivated automatically.

Parameter: Energy restore time

• Default setting: (_:112) Energy restore time = none

Parameter Value Description


none Deactivated
hh:00 Restoring on the full hour
hh:15 Restoring 15 minutes after the full hour
hh:30 Restoring 30 minutes after the full hour
hh:45 Restoring 45 minutes after the full hour

Note: If the parameter is activated through a time setting, the parameter Energy restore interval is
not in effect and will be deactivated automatically.

Parameter: Energy restore

• Default setting: (_:120) Energy restore = latest value

Parameter Value Description


latest value Restoring of the current energy value
delta value Restoring the difference value between the current energy value and the
energy value of the last restoring operation

Parameter: Energy restore by A.time

• Default setting: (_:121) Energy restore by A.time = false

1476 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.7 Energy Values

Parameter Value Description


False Restoring deactivated
True The cyclic restoring after the set time of the parameter (_:111) Energy
restore intervalwill also be synchronized with the system time.
Example: Energy restore interval = 30 min; current system time:
12:10 o'clock First restore: 12:30 o'clock; next restore: 13:00 o'clock etc.

Note: When the parameter is activated, the following setting values are possible for the parameter (_:111)
Energy restore interval: 1 min; 2 min; 3 min; 4 min; 5 min; 6 min; 10 min; 12 min; 15 min; 20 min;
30 min; 60 min.

Input Signals: >Restoring and >Resetting

Binary Inputs Description


>Restoring The restoring of the metered values is initiated via a binary input.
>Reset The metered value memory is set to 0 through the binary input.

You route these logical signals in the DIGSI routing matrix. Open the function group, for example, Line, where
you created the energy value. There, under the tab Measured values you will find the tab Energy, 3-phase.
In this tab, you will find the logical signals in addition to the measured values.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1477


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.8 User-Defined Metered Values

10.8 User-Defined Metered Values

10.8.1 Function Description of Pulse-Metered Values

NOTE

i You can define additional metered values through DIGSI for user-specific applications.

Use pulse meters; then you can define the respective metered values through DIGSI and set parameters for
them analogously to the energy values. You can read out the metered values on the display of the device or
via DIGSI.
Through settings, you can individually set how each pulse-metered value is processed:

• Parameter Restore time


Hour-related point in time when the device will provide a metered value at the communication interface
for transmission. After this, the transfer takes place in accordance with the selected protocol.
Note: If the parameter is activated through a time setting, the parameter Restore interval will
automatically be deactivated.

• Parameter Restore interval


Adjustable period in minutes until the first and every further transfer of the metered value to the commu-
nication interface of the device. After this, it will be transferred in accordance with the selected log.
Note: If the parameter is activated through a time setting, the parameter Restore time will automati-
cally be deactivated.
In addition, restoring can be triggered via a routable binary input ( >Restore trigger ) or via a logical
internal binary input. The rising edge of the binary input leads to restoring and thus to provision of the
metered value at the communication interface.
The counter pulse of any external/internal pulse generator is connected to the device via a routable binary
input ( >Pulse input ). If this does not deliver any plausible values, this can be signaled to the device via
another routable binary input ( >External error ).
In compliance with IEC 61850, in the event of an external error, the quality of the pulse-metered value
changes to the state Questionable. No more pulses are added as long as the external error persists. Once the
external fault condition has been cleared, pulses are added again.
The quality of the pulse-metered value remains Questionable until a new meter content is specified for the
pulse-metered value by:
- Confirmation of the current meter content via Setting
- Setting a new meter content
- Resetting the meter content to 0

• Parameter Edge trigger


Through settings, you can select between counting only with a rising edge or with rising and falling
edges on the pulse input.
The pulse counter can be reset to 0. You can perform this resetting via the rising edge of a routable binary
input ( >Reset ) or via operation on the device.
To display the counting amount at the device display, use DIGSI to set the desired weighting of the counter
pulses, the unit of the metered value and a multiplication factor for every pulse generator. You can also assign
a user-specific name.
To do this, open the functional area Pulse-metered value in DIGSI information routing. (see Figure 10-3).
Select the metered value and enter the settings under Properties.

1478 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.8 User-Defined Metered Values

[scomvimp-010313-01.tif, 2, en_US]

Figure 10-3 Setting with DIGSI, General Settings, Pulse-Metered Values

10.8.2 Application and Setting Notes for Pulse-Metered Values

The functionality Pulse-metered values is not preconfigured. If you want to use the functionality, you must
load it from the library into the respective function group.
The parameters can be set individually for every pulse counter. You will find the setting parameters in DIGSI in
the project tree under Parameter > Function group
For pulse-metered values, the following described settings and binary inputs are available.

Parameter: Restore time

• Default setting: (_:101) Restore time = none

Parameter Value Description


none Deactivated
hh:00 Transfer on the full hour
hh:15 Transfer 15 minutes after the full hour Note:
hh:30 Transfer 30 minutes after the full hour Note:
hh:45 Transfer 45 minutes after the full hour Note:

Note: If the parameter is activated through a time setting, the parameter Restore interval is not in effect
and will be deactivated automatically.

Parameter: Restore interval

• Default setting: (_:102) Restore interval = 0 min

SIPROTEC 5, 7SJ82/7SJ85, Manual 1479


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.8 User-Defined Metered Values

Parameter Value Description


0 min Deactivated
1 min to 60 min Cyclical transfer after the set time 1 minute to 60 minutes

Note: If the parameter is activated through a time setting, the parameter Restore time is not in effect and
will be deactivated automatically.

Parameter: Edge trigger

• Default setting: (_:103) Edge trigger = rising edge

Parameter Value Description


rising edge Counting with rising edge at the pulse input
rising & falling edge Counting with rising and falling edge at the pulse input

Parameter: Restore by absolute time

• Default setting: (_:104) Restore by absolute time= False

Parameter Value Description


False Deactivated
True The cyclic restoring of setting Restore interval after the set time is also
synchronized with the system time. Example: Restore interval = 30
min; current system time: 12:10 o'clock. First restoring operation: 12:30
o'clock; next restoring operation: 13:00 o'clock, etc.

Input Signals: >Pulse input, >External error, >Restore trigger, >Reset

Binary inputs Description


>Pulse input Input for the counting pulses of an external pulse generator
>External error Indication that the counter pulses of the external pulse generator are faulty.
The indication has an effect on the quality identifier of the pulse value.
>Restore trigger The transfer of the metered values is initiated via a binary input.
>Reset The rising edge at the binary input resets the pulse counter to 0.

The amount of energy indicated by a pulse generator is to be displayed as a measured value.


1 pulse corresponds to 100 Wh.
The pulse weighting, the SI unit, and the factor must be adjusted to one another.
Display value = Calculated metered value * Pulse weighting * Factor * SI unit.
If the check box Restore delta value is activated, the differential value is transferred at the restore time set
via the communication interface. The difference value is formed by subtracting the counter content of the last
restoring operation from the current counter content.
You route the logical signal >Pulse input to a binary input to which the pulse generator is connected.
Set the following values:
Name Active Power Meter
Pulse weighting 100
Restore differential value Activated
SI unit Wh
Factor 1

The factor is used for adaptation to larger units (for instance, 1000 for kWh). It is adjustable in powers of ten
(1, 10, 100, 1000, etc.). The following figure shows the signals that can be arranged in the DIGSI information
matrix. Open the function group where you created the pulse-metered value, for example, Line 1. There, you
will find the function area Pulse-metered value. Here you will also find the logical signals next to the
metered value. Select the metered value and enter the settings under Properties.

1480 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.8 User-Defined Metered Values

[scimpzwe-260912-01.tif, 1, en_US]

Figure 10-4 Setting with DIGSI

SIPROTEC 5, 7SJ82/7SJ85, Manual 1481


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

10.9 Phasor Measurement Unit (PMU)

10.9.1 Overview of Functions

A Phasor Measurement Unit (PMU) measures the phasor values of current and voltage. These values get a high
precision time stamp and together with the values of power frequency, power frequency change rate and
optional binary data that are also time stamped are transmitted to a central analysis station. The standardized
transmission protocol IEEEC 37.118 is used to do this.

10.9.2 Structure of the Function Group

The PMU function group is activated by selecting the protocol IEEE C37.118PMU on an Ethernet module
(electrical or optical). The PMU obtains the measured values from the measuring points and the precise time
from time synchronization. The time-stamped synchrophasors for current and voltage are formed from this
and transferred together with additional values via the communication module to a server (PDC, Phasor Data
Concentrator).

[dwstrpmu-250613-01.tif, 2, en_US]

Figure 10-5 Structure/Embedding of the Function

10.9.3 Function Description

The synchrophasors, sent from the PMU in a continuous data stream to a PDC, are provided with time stamps
and thus are comparable with the measured values of other PMUs. The power frequency, the power frequency
change rate and optional binary information are also transmitted as time-stamped measured values. There-
fore, you receive an overview of the transient processes in a distributed energy transfer system, for example
network fluctuations and compensating processes.
The following table shows the differences between the PMU measured values and the remaining measured
values of the device.

1482 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

Table 10-4 Comparison of Synchrophasors and Conventional Measured Values

Synchrophasors of the PMU Measured Values from the Measuring Points


Continuous updating (measured value of current) Slow updating (typically every 5 seconds)
with, for example, 10 values per second (reporting
rate)
Every measured value has a time stamp No time stamp for the measured values
Phasor values of current and voltage (amplitude and RMS values without phase angle
phase angle)

The following figure shows the structure of such a Wide Area Monitoring System. The data delivered from the
PMUs on the PDC are transmitted via the Inter-Control Center Communications Protocol (ICCP) according to
DIN EN 60870-6 to the network control center.

[dwstrwam-120124-01.tif, 1, en_US]

Figure 10-6 Structure of a Wide-Area Monitoring System with Phasor Measurement Units

The phasor measurement units each have 2 communication interfaces: an Ethernet module for synchrophasor
communication via IEEE C37.118 and another module for communication with the substation automation
technology, for example, through the IEC 61850 protocol.
The central evaluation system, for example SIGUARD PDP Phasor Data Processor, receives the data, files,
archives them and graphically displays them on a User Interface. In this system, a self-checking function may
also be performed, for example, on undamped power swings. The further distribution of information to other
PDCs or to a control center is done here.
To maintain the required maximum errors (TVE) required in the standard IEEE C37.118, the time tolerance
relative to the UTC time reference (UTC = Universal Time Coordinated) may be maximum 10 μs. Therefore, the
device must be directly synchronized with a GPS precise time signal for the correct function of the PMU.

Phasors
A phasor u(t) = Uejωt can be displayed as a phasor that moves counterclockwise in the complex plane at the
angular frequency ω. Therefore, the voltage function u(t) = Re{u(t)} is obtained as a projection of the phasor
u(t) on the real axis.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1483


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

[dwgeopdc-061011-01.tif, 1, en_US]

Figure 10-7 Geometric Representation of a Phasor

Reference Point for Determining the Angle


The phase angle of a measuring signal Xm is determined relative to a cosine function having a rated frequency,
which is synchronized with the UTC time reference (see Figure 10-8).

[dwutcphi-260112-01.tif, 1, en_US]

Figure 10-8 Determination of Phase Angle ρ of Measuring Signal Xm Relative to the Cosine Function

1484 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

The number of phasors that are transmitted per second is configurable. The transmission rate is defined
according to IEEE C37.118 as the reporting rate. The reporting rate defines the number of phasors that are
transmitted per second. Extremely precise time synchronization via GPS is essential so that phasor measure-
ment can be carried out to enable phasors from different sites to be compared.

Reporting Rate
You use the configurable reporting rate (parameter (_:10621:102) Reporting rate) to specify the
number of telegrams that are compiled and sent to the PDC per second. It is adjustable, depending on the
rated frequency, and applies to all currents and voltages of the relevant PMU function group. If several PMU
function groups are created on the device, these can work with different reporting rates.

Total Vector Error (TVE)


The TVE describes the error between the actual and the measured values of the input signal. The Synchro-
phasor Standard IEEE 37.118 defines upper limiting values of 120 % VN and 200 % IN, among other things. Up
to these limiting values, the TVE of 1 % must not be exceeded for stationary signals. The standard defines the
2 performance classes, Class P and Class M, as ranges within which influencing variables are acceptable and
the TVE of ≤1 % must be maintained. The SIPROTEC 5 devices support Class P and Class M, which specify the
following influencing variables for a TVE of 1 %:

• Signal frequency (relative to fN)

• Signal magnitude (relative to 100 % nominal magnitude) for voltage and current

• Phase angle (relative to 0°)

• Harmonic distortions (relative to < 0.2 % (THD) up to the 50th harmonic


The following figure graphically represents the total vector error. As well as the amplitude, the TVE also enters
into the angle error.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1485


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

[dwklatve-120124-01.tif, 1, en_US]

Figure 10-9 Representation of the Total Vector Error

The TVE is defined as follows:

[fo_utcphi_new, 1, en_US]

where:

• Xr(n) = Real part of measured signal

• Xi(n) = Imaginary part of measured signal

• Xr = Real part of input signal

• Xi = Imaginary part of input signal

Variables that influence the TVE are:

• Amplitude errors

• Phase errors

• Synchronization accuracy (deviation from the UTC)


Synchronization accuracy is affected by a GPS timer and the precise correction of the time delay within the
GPS receiver module, as well as by the optimal setup of the GPS antenna.

1486 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

10.9.4 Transmitted Data

The following data is transmitted from the PMU to the PDC:

• Current and voltage phasors

• Frequency

• Frequency rate of change

• Binary information
The current and voltage channels transferred from a PMU function group are selected through the Function
group connections editor in DIGSI 5. The frequency and frequency change rate are determined once per
PMU. In this case, only the current and voltage channels selected via the Function group connections editor
for this PMU are taken into consideration. You may route the binary information in the information routing
matrix of DIGSI 5.
The channel used for specifying the frequency is selected dynamically during the device runtime. Each
channel is checked for the presence of a signal in the following order:
1st 3-phase voltage measuring points
2nd 1-phase voltage measuring points
3rd 3-phase current measuring points
4th 1-phase current measuring points

The 1st measuring point found with a valid signal is used for specifying the frequency in the PMU function
group.
In the case of 3-phase measuring points, the positive-sequence system can also be transmitted instead of
3 individual synchrophasors. This setting can be made via the parameter (_:10621:103) Only positive
sequence.

10.9.5 PMU Communication (IEEE C37.118)

PMU communication according to standard IEEE C37.118 is a client-server communication format in which the
PDC (Phasor Data Concentrator) functions as both the client and the server.
Once the PDC has been successfully connected to the device PMU and the PMU configuration data has been
queried, the PDC initiates transmission of the synchrophasor data by sending a close command to the PMU. If
you use the method of spontaneous transmission via UDP, data output starts immediately after the device
boots without a close command to the PMU.
In addition to the phasors, the channel names of the routed measuring points and the binary information are
transferred. Per default, these are automatically generated by the respective PMU function groups.
Where applicable, you can also edit the channel names of the measuring point and assign a designation of its
own for this purpose. For more information, see chapter 10.9.6 Parameterizing the PMU with DIGSI. The
names for the binary information carried out are however, generally automatically generated by the respec-
tive PMU function group and cannot be edited.
As an example, the names (generated) for measuring points or binary information may be as follows:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1487


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

Table 10-5 Possible Measuring-Point Names

Name Displayed in the DIGSI Function Depending on the Connection Type, Name Transferred to the
Group Connections PDC (in case it cannot be assigned automatically)
Measuring point U-3ph 1[ID 1] MP-V3ph VAB ID01
MP-V3ph VBC ID01
MP-V3ph VCA ID01
MP-V3ph VA ID01
MP-V3ph VB ID01
MP-V3ph VC ID01
MP-V3ph V1 ID01
Measuring point I-3ph 1[ID 2] MP-I3ph IA ID02
MP-I3ph IB ID02
MP-I3ph IC ID02
MP-I3ph I1 ID02
Measuring point I-1ph 1[ID 3] MP-I1ph ID03
Measuring point U-1ph 1[ID 4] MP-V1ph ID03

Table 10-6 Possible Binary Information Names

Path Displayed in DIGSI 5 Name Transferred to the PDC


(Can Be Edited) (Cannot be Edited)
PMU 1: BIN-01-INFO-6
Transf.bin.1:
>BinaryInfo.6
PMU 1: BIN-02-INFO-8
Transf.bin.2:
>BinaryInfo.8
PMU 1: BIN-10-INFO-3
Transf.bin.10:
>BinaryInfo.3

Data is transmitted continuously from the PMU to the PDC at the configured reporting rate. The transmission is
terminated by a corresponding trip command from the PDC or when the connection between the PDC and the
PMU is interrupted.
Communication between the PMU and the PDC can be passed via TCP or UDP protocols.
The following ports are used for data transmission:

• TCP: Port 4712

• UDP: Port 4713


The ports must be configured on the PDC.
If you are using the UDP protocol for communication between the PMU and the PDC, you can set either
command mode or asynchronous response mode as the communication mode. In asynchronous
response mode, data can be transmitted continuously to preset PDC destination addresses in IEEE C37.118
format without a PDC having to request transmission of the synchrophasor data via a close command to the
PMU.
Up to 3 different PDCs can be connected to one device PMU at the same time. The IP addresses of the
maximum 3 PDCs are set in the PMU function group. If 4 device PMUs are configured, this enables support for
up to 12 PDCs.

1488 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

10.9.6 Parameterizing the PMU with DIGSI

You configure and parameterize the Phasor Measurement Unit with DIGSI. After a device has been added in a
DIGSI project, one or more communication modules that support synchrophasors can be configured as PMUs.
The device module supports a maximum of 2 communication modules that can be configured as PMUs. If
more than 2 PMUs are needed, the device must be expanded with a CB202 plug-in module assembly (expan-
sion module), which can accommodate 2 more communication modules.
The following communication modules support synchrophasors:

• ETH-BA-2EL (2 x Ethernet electric, RJ45)

• ETH-BB-2FO ( 2 x Ethernet optical, 2 km, LC duplex)


These modules are then freely assignable to ports E, F, N, or P of the device, see Figure 10-10. You can view
the selected port in the (_:10621:104) Port. This parameter is automatically managed by DIGSI and
cannot be changed.

[sccommod-140213-01.tif, 1, en_US]

Figure 10-10 Placement of Communication Modules

NOTE

i Port M of the CB202 plug-in module assembly is used to accommodate measuring-transducer modules and
cannot be used for the installation of communication modules.

Addressing
You must configure the respective Ethernet address (IP address, subnet mask, etc.) for each communication
module in DIGSI. This is done in the DIGSI General settings properties dialog of the communication module in
item Ethernet addresses and so forms the IP address for the respective PMU.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1489


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

[scethern-210415, 1, en_US]

Figure 10-11 Ethernet Address Configuration

In the Protocols – Communication menu, select the synchrophasor protocol, see the following figure.

[scprotoc-100419, 1, en_US]

Figure 10-12 Protocol Selection

After you have selected the synchrophasor protocol for the communication module, a settings dialog for PMU-
specific configuration opens in the Settings item, see the following figure.

1490 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

[scwildcard-100419, 1, en_US]

Figure 10-13 PMU-Specific Configuration

You configure the specific settings for the communication protocol in the top section of this settings dialog. In
the bottom section, you specify the corresponding PMU-specific settings.
In order to permit a better configuration of larger wide-area supervision systems, changes have been imple-
mented in the IEEE C37.118 communication configuration that permit a flexible IP configuration without the
loss of safety aspects in the systems administered.
Configurable placeholders are permitted for each PDC/IP address with the TCP PMU transmission protocol in
general and with UDP in the Communication mode commanded operation. These placeholders allow you
to define a range of IP addresses where they are accepted within these accesses. The purpose of this is to
permit each individual device or system access within the respective system without limits with regard to their
hierarchy level. Therefore, with regard to security aspects, the limitation to individual IP addresses is elimi-
nated. You are thus allowed to configure complete sections of IP addresses in each PMU and, as a result, very
flexible when making changes to the configuration of the entire system, for example. The placeholder char-
acter must follow consecutively at the bit level, starting with the bit with the lowest value.

EXAMPLE of Placeholder Characters:


Example 1:

• binary 00000000.00000000.00000000.00101011 is not permitted

• binary 00000000.00000000.00000000.00111111 is permitted


Example 2:

• The PDC IP address is: 192.172.16.1

• Placeholder: 0.0.0.127
The device accepts requests within the IP address range of 192.172.16.1 to 192.172.16.127.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1491


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

Example 3:

• The PDC IP address is: 192.172.16.100

• Placeholder: 0.0.0.3
The device accepts requests within the IP address range of 192.172.16.100 to 192.172.16.103.

If a PDC attempts to establish a connection to the device, the PDC IP addresses and corresponding place-
holders are checked in the same order as they had been configured (IP address PDC1, IP address PDC2,
IP address PDC3). Running through the list is stopped with the first match of the IP address, placeholder and
requested IP address range and the connection is built-up. If there are no matches, the attempt to connect is
rejected.
If you have configured IP address 0.0.0.0 and the placeholder 255.255.255.255, every IP address received is
accepted as valid. This could be of use in the course of commissioning measures.

NOTE

i You must have configured at least 1 IP address in order to establish a connection between the device and
PDC.

If you use the asynchronous data transmission method, set the PMU transfer parameter to UDP and the
Communication mode parameter to Spontaneous operation. The PMU data are then sent cyclically via
UDP to each PDC/IP address permanently configured in DIGSI. You may not configure placeholders for PDC/IP
address ranges in this communication mode.
Data output starts immediately after the device has booted. In this way, no starting signal from the PDC is
necessary to start data transmission.

[scspontan-100419, 1, en_US]

Figure 10-14 PMU Configuration for Spontaneous Transmission

The configuration dataset is transmitted 1x per minute. With the Reporting Rate parameter, you set the
number of cyclic repetitions of the data packages. As UDP is a connectionless protocol, a preconfigured desti-
nation device with its PDC/IP address is not required to be physically present and/or connected. This allows
uninterrupted provision of the data without bidirectional communication.

NOTE

i If you have not configured valid PDC/IP addresses and still activate option for spontaneous data transmis-
sion, no cyclic data telegrams are sent.

NOTE

i It is possible to configure IP addresses for various PDCs that are not in the same subnetwork as the COM
module. Such configurations are considered valid and may be loaded into the device. However, if the
device transmits spontaneous data and configuration packages to these IP addresses, the PDC with the
deviating subnetwork destination address cannot be reached.

1492 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

EXAMPLE
COM-Module Address Configuration

• IP address: 192.168.100.1

• Subnet mask: 255.255.255.0


PDC Address Configuration

• IP address for PDC1: 192.168.100.160

• IP address for PDC2: 86.168.100.161


Only PDC1 receives the data because the IP address is in the same subnetwork as that of the COM module.
PDC2 cannot be reached because the subnetwork address (86.x) differs from the subnetwork address of the
COM module (192.x). The PMU cannot transmit data to this address.

Measuring-Point Assignment
After adding measuring points to the device, you can assign these measuring points to each configured PMU.
Figure 10-15 shows an example expansion of the device configuration by 2 additional input/output modules.
You connect the current and voltage inputs of these I/O modules to measuring points via the DIGSI routing
matrix, see example in Figure 10-16.

[scaddios-140213-01.tif, 1, en_US]

Figure 10-15 Adding Additional Input/Output Modules

SIPROTEC 5, 7SJ82/7SJ85, Manual 1493


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

[scroutin-210415, 1, en_US]

Figure 10-16 Assignment of the Current and Voltage Inputs of the Added Input/Output Modules on Meas-
uring Points

The maximum numbers of measuring points that can be routed for one PMU are:

• 20 x 3-phase voltage measuring points

• 20 x 3-phase current measuring points

• 40 x 1-phase voltage measuring points

• 40 x 1-phase current measuring points


You can assign all supported measuring points to any PMU, see the following figure. Each PMU must be
connected to at least one measuring point and the total number of phasors (3-phase measuring point = 4
phasors) must not exceed 80 per PMU. The limitation of the load model must also be considered, depending
on the device configuration.

[scfgconn-210415, 1, en_US]

Figure 10-17 Connecting Measuring Points to the Configured PMU Function Groups

When these setting steps have been completed, the PMUs are fully configured. The PMU is a function group
that functions independently of all the other function groups instantiated in the device.

Changing the Channel Names of Phasors


You can edit the names of the individual phasor channels for voltage and current in DIGSI. The clearly struc-
tured channel designations assist with when testing and commissioning PMU systems. Furthermore, only the
names visible in the IEEE C37.118 interface can be changed. The function block designations themselves
cannot.
The IEEE C37.118 defines the ASCII character set for changing the channel names. Due to the protocol, the
designation length is limited to 255 ASCII characters per channel for CFG3 and to 16 ASCII characters per
channel for CFG2. The renaming of binary channels is not supported in the current implementation.
In order to define your own channel names, instantiate the required number of Phasor names function blocks
in the PMU function group first. Assign the corresponding measuring points via the Measuring point selec-

1494 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

tion. For this purpose, DIGSI shows all measuring points routed to the PMU in the function group connections
(see following figure).

[scphasoredit-100419, 1, en_US]

Figure 10-18 Options for Editing the Names of the Individual Phasors

NOTE

i You can only rename each individual phasor when you set the parameter Positive-sequence system
only to No in the functional settings. Otherwise you will only be offered one single phasor for each 3-
phase measuring point for renaming.

Routing Binary Signals


You can connect binary inputs with binary channels of the PMU via DIGSI information routing. Alternatively,
you can also route the binary inputs via a function chart (CFC). You will find, in the Phasor Measurement
Unit (PMU) folder, the Binary information transmission function block in the DIGSI function library (see the
following figure). You can instantiate this function block up to 10 times in one PMU function group. Each of
these function blocks contains 8 options for routing binary channels.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1495


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

[scpmubif-210415, 1, en_US]

Figure 10-19 Information Routing in DIGSI 5

Routing Indications
The routable indication ChannelLive of the PMU log

• raises when the PMU is connected to the PDC

• clears when the connection to the PDC is interrupted.

[scparami-260912-01.tif, 1, en_US]

Figure 10-20 Log Indication for Display of the PMU/PDC Connection

10.9.7 Parameterizing the PMU on the Device

You can also change the PMU settings directly on the device. To do this, select the desired PMU instance on
the device display. By selecting menu item Settings you then access the editable setting values (see
Figure 10-21). Note that the parameter Port cannot be changed, because this corresponds to the physical
slot position of the communication module in question.

1496 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

[scdevpmu-210415, 1, en_US]

Figure 10-21 Changing the PMU Setting Values via the Device Display

You can also change the communication settings in the same way. To do this, select the corresponding
communication port in the Communication menu on the device display. From the Channel 1 menu item, you
can then access the detailed setting options for the IP or PMU communication settings (see Figure 10-22).

[sccompmu, 1, en_US]

Figure 10-22 Changing the Communication Setting Values Via the Device Display

SIPROTEC 5, 7SJ82/7SJ85, Manual 1497


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

10.9.8 Application and Setting Notes

Time Synchronization
In order to ensure the time accuracy of the PMU, you must select IRIG B as protocol for the GPS clock, see the
following figure. With other settings, the PMU function function group indicates that it is not time synchron-
ized.

[sc_setting time source_2014-09-09, 1, en_US]

Figure 10-23 Setting Time Synchronization

To detect a lack of synchronization quickly, also set the waiting time for the failure indication of the loss of
time synchronization to the smallest possible value, thus to 1 s.

Parameter: Mode

• Default setting (_:10621:1) Mode = on


Activate and deactivate the PMU or switch to Test mode via the parameter Mode. The possible setting values
are on, off and test. In Test mode, the PMU data is marked as invalid.

Parameter: Reporting rate

• Default setting (_:10621:102) Reporting rate = 10 frames/s


With the parameter Reporting rate, you specify the number of telegrams that are compiled and sent to
the PDC per second.

NOTE

i Different setting values are shown or hidden, depending on the rated frequency set.

1498 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

Parameter: Only positive sequence

• Default setting (_:10621:103) Only positive sequence = no


With the parameter Only positive sequence, you set whether the positive-sequence system is to be
transmitted instead of 3 individual synchrophasors in the case of 3-phase measuring points. The setting you
make here is then valid for all PMUs with 3-phase measuring points.

Parameter: Class

• Default setting (_:10621:101) Class = Class P


With the parameter Class, you set which performance class is used for the calculation of the measured
values. Class P is the standard case for PMUs. In this case, filters are used that are suitable for a short
response time and therefore are well suited for recording dynamic processes. Class M is conceived for appli-
cations that are unfavorably affected by alias effects and in which short response times are not relevant.

Parameter: Global PMU ID

• Default setting (_:10621:142) Global PMU ID = Freely editable text


With the parameter Global PMU ID, you enter a global ID for the PMU, which can contain up to 16 charac-
ters.

Parameter: PMU Latitude

• Default setting (_:10621:143) PMU Latitude = 0.00000000 °


With the parameter PMU Latitude, you set the latitude to a value between -90.00000000 ° and
+90.00000000 °.

Parameter: PMU Longitude

• Default setting (_:10621:144) PMU Longitude = 0.00000000 °


With the parameter PMU Longitude, you set the current longitude to a value between -180.00000000 ° and
+180.00000000 °.

Parameter: PMU Elevation

• Default setting (_:10621:145) PMU Elevation = 0.00 m


With the parameter PMU Elevation, you set the current height above sea level to a value between -50
000.00 m and +50 000.00 m.

Parameter: Port
This parameter cannot be set, because the Port results from the physical position where the corresponding
communication module is inserted.

10.9.9 Settings

Addr. Parameter C Setting Options Default Setting


Func. settings
_:10621:1 Func. settings:Mode • off on
• on
• test
_:10621:101 Func. settings:Class • Class P Class P
• Class M
_:10621:142 Func. settings:Global Freely editable text
PMU ID

SIPROTEC 5, 7SJ82/7SJ85, Manual 1499


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

Addr. Parameter C Setting Options Default Setting


_:10621:143 Func. settings:PMU Lati- -90.00000000 ° to 0.00000000 °
tude 90.00000000 °
_:10621:144 Func. settings:PMU -180.00000000 ° to 0.00000000 °
Longitude 180.00000000 °
_:10621:145 Func. settings:PMU -50000.00 m to 50000.00 m 0.00 m
Elevation
_:10621:102 Func. settings:Reporting • 1 frame/s 10 frames/s
rate
• 5 frames/s
• 6 frames/s
• 10 frames/s
• 12 frames/s
• 15 frames/s
• 20 frames/s
• 25 frames/s
• 30 frames/s
• 50 frames/s
• 60 frames/s
• 100 frames/s
• 120 frames/s
_:10621:103 Func. settings:Only posi- • no no
tive sequence
• yes
_:10621:104 Func. settings:Port • port J port F
• port F
• port E
• port P
• port N
• port G

_:10621:141 Func. settings:Freq 1 to 100 1
tracking group ID
Ph.names I-3ph
_:131 Ph.names I-3ph:Phasor 1 Freely editable text
_:132 Ph.names I-3ph:Phasor 2 Freely editable text
_:133 Ph.names I-3ph:Phasor 3 Freely editable text
_:134 Ph.names I-3ph:Phasor Freely editable text
_:81 Ph.names I-3ph:Meas- Setting options depend on
uring point configuration
Ph.names I-1ph
_:131 Ph.names I-1ph:Phasor Freely editable text
_:81 Ph.names I-1ph:Meas- Setting options depend on
uring point configuration
Ph.names V-3ph
_:131 Ph.names V-3ph:Phasor Freely editable text
1
_:132 Ph.names V-3ph:Phasor Freely editable text
2

1500 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)

Addr. Parameter C Setting Options Default Setting


_:133 Ph.names V-3ph:Phasor Freely editable text
3
_:134 Ph.names V-3ph:Phasor Freely editable text
_:81 Ph.names V-3ph:Meas- Setting options depend on
uring point configuration
Ph.names V-1ph
_:131 Ph.names V-1ph:Phasor Freely editable text
_:81 Ph.names V-1ph:Meas- Setting options depend on
uring point configuration

10.9.10 Information List

No. Information Data Class Type


(Type)
General
_:10621:52 Func. settings:Behavior ENS O
_:10621:53 Func. settings:Health ENS O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1501


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.10 Measuring Transducers

10.10 Measuring Transducers

10.10.1 Overview of Functions

Measuring transducers with an input rated at 20 mA can be used in the devices. 4 such inputs are available as
module ANAI-CA-4EL, which can be plugged into a communication module slot (for instance, port E or F). Up
to 4 such modules can be plugged in. Typically, slowly changing process variable such as temperature or gas
pressure are recorded with such 20-mA measured values and reported to the substation automation tech-
nology.

10.10.2 Structure of the Function

The measuring-transducer blocks are embedded in the Analog units function group and contain input and
output channels that are configurable independently of each other.

[dwstrumu-050313-01.tif, 1, en_US]

Figure 10-24 Structure/Embedding of the Function

10.10.3 Function Description

The 20-mA inputs typically transmit a value which represents a physical quantity such as a temperature or a
pressure. Therefore, the device must contain a characteristic curve that assigns the physical quantity to the
20-mA value. If the parameter Range active is not activated (no x in the check box), the function operates
over the range -25.6 mA to +25.6 mA. The setting of the range for the scaled value goes from a usable range
of -25.6 mA to +25.6 mA. The following figure shows an example.

1502 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.10 Measuring Transducers

[dwklbsp1-120124-01.tif, 3, en_US]

Figure 10-25 Characteristic Curve of a 20-mA Input (Example 1)

In this example, the measured value 0 mA means a temperature of 0 degrees Celsius and the measured value
20 mA means a temperature of 100 degrees Celsius. Thus, Unit = °C and Conversion factor = 100 are
entered. The resolution (decimal place) of the temperature value can be selected; for one decimal place, select
Resolution = 0.1.

[sctransd-210415, 1, en_US]

Figure 10-26 Parameter Settings for Example 1

If a value smaller than -25.6 mA or larger than +25.6 mA is applied to the measuring-transducer input, the
measured value is marked as outside the range of values. If the parameter Range active is activated, the 2
additional parameters Upper limit and Lower limit appear. Both limiting values indicate the input
currents in mA, for which the value set by the Conversion factor (Upper limit) and the value 0
(Lower limit) of the calculated measurand are valid (see following figure).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1503


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.10 Measuring Transducers

[dwklbsp2-120124-01.tif, 1, en_US]

Figure 10-27 Characteristic Curve of a 20-mA Input (Example 2)

In this example, Range active is selected. The Upper limit is at 15 mA, the Lower limit is at 5 mA
and the Conversion factor remains at 100. Overall, this results in a characteristic curve as shown in the
following figure, taking into account all possible valid measured values from -25.6 mA to +25.6 mA. The
parameter Upper limit - Sensor is the calculated measured value if the input current corresponds to the
value in the Upper limit setting. The parameter Lower limit - Sensor is the calculated measured
value if the input current corresponds to the value in the Lower limit setting.

[dwklges2-120124-01.tif, 3, en_US]

Figure 10-28 Total Characteristic Curve in Example 2

1504 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.10 Measuring Transducers

[sctrans2-210415, 2, en_US]

Figure 10-29 Parameter Setting for Example 2

Each measuring-transducer input provides the scaled measured value (these are the temperature values in the
examples) and the original current measured value in mA in the information routing for further processing.

Table 10-7 Measuring-Transducer Measured Values

Measured Value Display


TD scale MV (_:301)
Primary Measured value converted to the sensor
Secondary –
Percent 100 % ≙ parameter (_:104) Conversion factor
(for (_:107) Range active = false)
100 % ≙ max. absolute value of the parameter (_:109) Upper limit - Sensor
or of the parameter (_:110) Lower limit - Sensor
(for (_:107) Range active = true)
TD direct MV (_:302)
Primary –
Secondary -20.000 mA to +20.000 mA or -10 V to +10 V
Percent 100 % ≙ 20 mA or 10 V

The measuring-transducer values can be displayed in the display image and processed with CFC charts.

10.10.4 Application and Setting Notes

Parameter: Unit

• Recommended setting value (_:103) Unit = °C


With the Unit parameter, you set the physical unit of measurement the measured values. The possible setting
values are listed in the settings table.

Parameter: Conversion factor


With the (_:104) Conversion factor parameter, you set the conversion factor for the measuring trans-
ducer.

Parameter: Resolution

• Default setting (_:108) Resolution = 0.1


With the Resolution parameter, you set the resolution of the scaled values.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1505


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.10 Measuring Transducers

Parameter: Range active

• Default setting (_:107) Range active = false


If you do not activate the parameter Range active (no x in the check box), the function operates over the
range -25.6 mA to +25.6 mA. The setting of the range for the scaled value goes from a usable range of
-25.6 mA to +25.6 mA.
If you activate the parameter Range active, the 4 additional parameters Upper limit, Upper limit -
Sensor, Lower limit, and Lower limit - Sensor appear.

Parameter: Upper limitLower limitUpper limit - Sensor and Lower limit - Sensor

• Default setting (_:105) Upper limit = 20000 mA

• Default setting (_:109) Upper limit - Sensor = 100

• Default setting (_:106) Lower limit = 4000 mA

• Default setting (_:110) Lower limit - Sensor = 100


If you activate the parameter Range active, the 4 additional parameters Upper limit, Lower limit,
Upper limit - Sensor, and Lower limit - Sensor appear. The parameter Upper limit -
Sensor is the calculated measured value if the input current corresponds to the value in the Upper limit
setting. The parameter Lower limit - Sensor is the calculated measured value if the input current corre-
sponds to the value in the Lower limit setting.

10.10.5 Settings

Addr. Parameter C Setting Options Default Setting


MT in #
_:101 MT in #:Meas. transduc. • Voltage input Current input
I/O type
• Current input
• Voltage output
• Current output
• Temperature input

1506 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.10 Measuring Transducers

Addr. Parameter C Setting Options Default Setting


_:103 MT in #:Unit • % m
• °
• °C
• °F
• Ω
• Ω/km
• Ω/mi
• 1/s
• A
• As
• cos φ
• cycles
• dB
• F/km
• F/mi
• h
• Hz
• Hz/s
• in
• J
• J/Wh
• K
• l/s
• m
• mi
• min
• p.u.
• Pa
• periods
• rad
• rad/s
• s
• V
• V/Hz
• VA
• VAh
• var
• varh
• Vs
• W
• W/s
• Wh

SIPROTEC 5, 7SJ82/7SJ85, Manual 1507


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.10 Measuring Transducers

Addr. Parameter C Setting Options Default Setting


_:108 MT in #:Resolution • 1 0.1
• 0.1
• 0.01
• 0.001
_:107 MT in #:Range active • 0 false
• 1
_:104 MT in #:Conversion 1 to 10000 100
factor
_:105 MT in #:Upper limit -20.00 mA to 20.00 mA 20.00 mA
_:109 MT in #:Upper limit - -10000 to 10000 100
Sensor
_:106 MT in #:Lower limit -20.00 mA to 20.00 mA 4.00 mA
_:110 MT in #:Lower limit - -10000 to 10000 100
Sensor

10.10.6 Information List

No. Information Data Class Type


(Type)
MT in #
_:301 MT in #:TD scale MV MV O
_:302 MT in #:TD direct MV MV O

1508 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.11 Statistical Values of the Primary System

10.11 Statistical Values of the Primary System


The device has statistical values for circuit breakers and disconnectors.
The following values are available for each circuit breaker:

• Total number of trippings of the circuit breaker initiated by the device.

• Number of trippings of the circuit breaker initiated by the device, separately for each circuit breaker pole
(if 1-pole tripping is possible)

• Total sum of primary breaking currents

• Sum of the primary breaking currents, separately for each breaker pole

• Hours with open circuit breaker

• Hours under load


The following values are available for each disconnector switch:

• Total number of switching operations of the disconnector switch initiated by the device

• Number of switching operations of the disconnector switch initiated by the device, separately for each
switch pole (if 1-pole switching is possible)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1509


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12 Circuit-Breaker Wear Monitoring

10.12.1 Overview of Functions

The Circuit-breaker wear monitoring function:

• Records the wear of circuit breakers

• Allows maintenance intervals of the CB poles to be carried out when their actual degree of wear makes it
necessary

• Sends a warning signal when the wear of a circuit breaker reaches a specified degree

• Allows the supervision of the circuit-breaker make time


Savings on maintenance and servicing costs is one of the main benefits this functionality offers.

10.12.2 Structure of the Function

The Circuit-breaker wear monitoring function can be used in the Circuit-breaker function group.
The function offers 4 independent operating stages with different measuring methods:

• ΣIx-method stage
Sum of tripping current powers

• 2P-method stage
2 points method for calculating the remaining switching cycles

• I2t-method stage
Sum of all squared fault-current integrals

• Supv.CB make time stage


Supervision of the circuit-breaker make time
The function is preconfigured by the manufacturer with 1 ΣIx-method stage. A maximum of 1 ΣIx-method
stage, 1 2P-method stage, 1 I2t-method stage, and 1 Supv.CB make time stage can be operated simultane-
ously within this function.
The general functionality is available across stages and provides a uniform start criterion for the stages.

[DwCBWear, 2, en_US]

Figure 10-30 Structure/Embedding of the Function

1510 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12.3 General Functionality

10.12.3.1 Description

Logic
As the wear on the circuit breaker depends on the current amplitude and duration of the actual switching
action, including arc deletion, determination of the start and end criteria is important. The following general
functionality provides starting and further timing information to the different stages (methods).
The general functionality operates phase-selectively. The following figure shows the logic of the functionality
across stages.

[LoCBWear, 3, en_US]

Figure 10-31 Logic Diagram of the Functionality Across Stages of the Circuit-Breaker Wear Monitoring Func-
tion

Start Criterion for the Circuit-Breaker Wear Monitoring Function


The Circuit-breaker wear monitoring function starts when any of the following criteria is fulfilled:

• Internal protection-function tripping signal from the function block Trip logic is received

• Open command signal from the internal Control function is received.

• Binary input signal >Start calculation is initiated, for example, from external.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1511


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

• Closed position signal of circuit breaker is going


This signal is derived form the circuit-breaker auxiliary contacts. In this way, opening the circuit-breaker
manually is detected.

Logic Input Signals for Stages


As soon as the start criterion has been fulfilled, the timers of the parameterized opening time and break time
are started. With the parameter CB opening time, the time when the circuit-breaker pole begins to open is
defined. With the parameter CB break time, the time of the pole being open including the arc extinction is
defined. The following figure shows the relationship between these circuit-breaker times.

[DwCBTime, 2, en_US]

Figure 10-32 Circuit-Breaker Times

In order to prevent an incorrect calculation in case of a circuit-breaker failure, the parameter Current
thresh. CB open is used to verify whether the current actually returns to 0 after 2 additional cycles. Funda-
mental components are used for comparing the threshold values. When the current criterion fulfills the
requirement of the phase-selective logic release, the calculation and evaluation of the respective methods are
initiated.

End Criterion for the Circuit-Breaker Wear Monitoring Function


After calculation and evaluation have been completed, the end criterion of the circuit-breaker maintenance is
fulfilled. The Circuit-breaker wear monitoring function is ready for a new initiation.

10.12.3.2 Application and Setting Notes

Parameter: CB opening time

• Default setting value (_:2311:101) CB opening time = 0.065 s


You use the CB opening time parameter to define the time span from energizing the shunt release of the
circuit breaker until the start of opening of switching poles.
You can find the information on the setting value in the technical data of the used circuit breaker. Also refer to
Figure 10-32.

1512 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

Parameter: CB break time

• Default setting (_:2311:102) CB break time = 0.080 s


You use the CB break time parameter to define the time span from energizing the shunt release of the
circuit breaker to the instant of arc extinction (and switching pole open).
You can find the information on the setting value in the technical data of the used circuit breaker. Also refer to
Figure 10-32.

Parameter: CB make time

• Default setting (_:2311:103) CB make time = 0.080 s


With the parameter CB make time, you define the typical time interval between the activation of the closing
procedure for the circuit breaker and the point in time when the first current flows.
You can find more information on the setting value in the technical data of the used circuit breaker.

10.12.3.3 Settings

Addr. Parameter C Setting Options Default Setting


General
_:2311:101 General:CB opening time 0.001 s to 0.500 s 0.065 s
_:2311:102 General:CB break time 0.001 s to 0.600 s 0.080 s
_:2311:103 General:CB make time 0.001 s to 0.600 s 0.080 s

10.12.3.4 Information List

No. Information Data Class Type


(Type)
General
_:2311:500 General:>Start calculation SPS I

SIPROTEC 5, 7SJ82/7SJ85, Manual 1513


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12.4 ΣI*-Method Stage

10.12.4.1 Description

Logic of the Stage

[LoCBWIxS, 3, en_US]

Figure 10-33 Logic of the ΣIx-Method Stage

Determination of the Tripping/Opening Current Value


RMS values of the fundamental components are stored for each phase in a buffer during the time between the
start criterion and the pole-opening-starts criterion. With the coming pole-opening-starts criterion, the latest
value in the buffer is searched for whose value is above the setting of parameter Current thresh. CB
open. The 20 ms prior value is used as tripping/opening current for further calculation.
If no value within the buffer is above the setting value, this circuit-breaker opening affects only the mechan-
ical lifetime of the circuit breaker and is consequently not considered by this method.

1514 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

[LoCBWIxF, 1, en_US]

Figure 10-34 Logic of the Determination of the Tripping Current Value

(1) Current-flow criterion fulfilled


(2) 20 ms prior value

Calculation of the Wear


If the ΣIx-method stage receives the logic release signal, the determined tripping current is used in the calcula-
tion of wear. The calculation results are then added to the existing statistic values of the ΣIx method as
follows, with phase A as example.

[FoCBWIxA-301012-01.tif, 1, en_US]

Where:
x Parameter exponent
q No. of circuit-breaker switching cycle
Tripping/opening current of phase A to the power of x in the qth circuit-
breaker operation
Rated normal current to the power of x

Statistic value of current phase A calculated with the ∑Ix method

m Total number of switching cycles

The phase-selective ΣIx value is available as statistical value. You can reset or preset the statistics according to
the specific application.
To simplify the interpretation of the sum of the tripping current powers, the values are set in relation to the
exponentiated rated normal current Irated of the circuit-breaker (see also Setting notes).

Circuit-Breaker Maintenance Warning


If the summated ΣIx value of any phase is greater than the threshold, a phase-selective warning signal is
generated.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1515


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12.4.2 Application and Setting Notes

Parameter: Exponent

• Default setting (_:11371:101) Exponent = 2.0

You use the Exponent parameter to specify the exponent for the ΣIx method.
A typical value is the default setting of 2. However, due to practical experiences with individual circuit
breakers, slightly different values may be requested.

Parameter: Threshold

• Default setting (_:11371:102) Threshold = 10 000.00


You use the parameter Threshold to define the threshold of the statistic value.
The relation of the tripping current powers to the exponentiated rated normal current Irated allows the limiting
value of the ΣIx method to correspond to the maximum number of make-break operations. For a circuit
breaker, whose contacts have not yet been worn, the maximum number of make-break operations can be
entered directly as limiting value.

10.12.4.3 Settings

Addr. Parameter C Setting Options Default Setting


ΣIx-method
_:11371:1 ΣIx-method:Mode • off off
• on
• test
_:11371:101 ΣIx-method:Exponent 1.0 to 3.0 2.0
_:11371:102 ΣIx-method:Threshold 0 to 10000000 10000

10.12.4.4 Information List

No. Information Data Class Type


(Type)
ΣIx-method
_:11371:54 ΣIx-method:Inactive SPS O
_:11371:52 ΣIx-method:Behavior ENS O
_:11371:53 ΣIx-method:Health ENS O
_:11371:301 ΣIx-method:ΣIx A BCR O
_:11371:302 ΣIx-method:ΣIx B BCR O
_:11371:303 ΣIx-method:ΣIx C BCR O
_:11371:304 ΣIx-method:Warning ACT O

1516 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12.5 2P-Method Stage

10.12.5.1 Description

Logic of the Stage

[LoCBW2PS, 2, en_US]

Figure 10-35 Logic of the 2P-Method Stage

Determination of the Tripping/Opening Current Value


For the description to determine the tripping/opening current value, refer to chapter 10.12.4.1 Description.

Calculation of Remaining Switching Cycles


A double-logarithmic diagram provided by the circuit-breaker manufacturer illustrates the relationship of
permitted switching cycles and the tripping/opening current, see the following figure. According to the
example, this circuit breaker can operate approximately 1000 times at a tripping current of 10 kA.
2 points and their connecting line determine the relationship of switching cycles and tripping current. Point P1
is determined by the number of permitted switching cycles at rated normal current Irated. Point P2 is deter-

SIPROTEC 5, 7SJ82/7SJ85, Manual 1517


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

mined by the maximum number of switching cycles at rated short-circuit breaking current Isc. The 4 associated
values can be configured with the parameters Rated normal current, Switching cycles at Ir,
Rated short-circ.cur. Isc, and Switching cycles at Isc.

[DwCBWOpC, 1, en_US]

Figure 10-36 Diagram of Switching Cycles for the 2P Method

As shown in the preceding figure, a double-logarithmic diagram, the straight line between P1 and P2 can be
expressed by the following exponential function:

[FoCBW2P1-301012-01.tif, 1, en_US]

Where:
Itrip Tripping/opening current
Irated Rated normal current
m Slope coefficient
b Switching cycles at rated normal current
n Number of switching cycles

The general line equation for the double-logarithmic representation can be derived from the exponential func-
tion and leads to the coefficients b and m.

1518 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

NOTE

i Since a slope coefficient of m < -4 is technically irrelevant, but could theoretically be the result of incorrect
settings, the slope coefficient is limited to -4. If a coefficient is smaller than -4, the exponential function in
the switching-cycles diagram is deactivated. The maximum number of switching cycles with Isc is used
instead as the calculation result for the current number of switching cycles, as the dashed line with m =
-4.48 shows in following figure.

[DwCBWSlo, 1, en_US]

Figure 10-37 Value Limitation of Slope Coefficient

(1) Applied function from m < -4


(2) Parameterized function with m = -4.48
(3) Parameterized function with m = -1.77

If the 2P-method stage receives the logic release signal, the current number of used up switching cycles (in
relation to the number of switching cycles at rated normal current) is calculated based on the determined trip-
ping current. This value is subtracted from the the remaining lifetime (switching cycles). The remaining life-
time is available as statistic value. For better understanding, refer to the example below.
You can reset or preset the statistical values according to the specific application. The reset operation changes
the statistic values to 0, and not to their default values of 10 000.
The statistic value of the residual switching cycles is calculated according to the following formula:

[FoCBW2P2-301012-01.tif, 1, en_US]

SIPROTEC 5, 7SJ82/7SJ85, Manual 1519


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

Where:
i No. of latest circuit-breaker switching cycle
Endur.i Residual switching cycles with rated normal current, after the ith
switching cycle
nrated Overall permissible switching cycles at rated normal current
ntrip Overall permissible switching cycles at tripping current Itrip
nrated/ntrip Lost switching cycles referring to rated normal current

EXAMPLE
For calculating the residual switching cycles of a circuit breaker, the following is assumed:
P1 (2.5 kA, 10 000)
P2 (50.0 kA, 50)
The circuit breaker has made 100 opening operations with rated normal current, 2 tripping operations with
rated short-circuit breaking current, and 3 tripping operations with 10 kA tripping current. Then, the residual
switching cycles with rated normal current are:

[FoCBW2P3-301012-01.tif, 1, en_US]

There are still 9465 possible break operations at rated normal current.

Circuit-Breaker Maintenance Warning


If the residual switching cycles of any phase lie below the threshold, a phase-selective warning signal is gener-
ated.

10.12.5.2 Application and Setting Notes

Parameter: Switching cycles at Ir

• Default setting (_:101) Switching cycles at Ir = 10 000


You use the Switching cycles at Ir parameter to define the number of permitted switching cycles at
rated normal current.
You can find the information on the setting value in the technical data of the used circuit breaker.

Parameter: Rated short-circ.cur. Isc

• Default setting (_:102) Rated short-circ.cur. Isc = 25 000 A


You use the Rated short-circ.cur. Isc parameter to define the rated short-circuit breaking current.
You can find the information on the setting value in the technical data of the used circuit breaker.

Parameter: Switching cycles at Isc

• Default setting (_:103) Switching cycles at Isc = 50


You use the Switching cycles at Isc parameter to define the number of permitted switching cycles at
rated short-circuit breaking current.
You can find the information on the setting value in the technical data of the used circuit breaker.

1520 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

Parameter: Threshold

• Default setting (_:104) Threshold = 1000


You use the Threshold parameter to define the threshold of residual switching cycles with rated normal
current. A warning signal is generated when the statistic is less than the Threshold.

Example
Here is an example that shows you how to set the Threshold parameter. Assuming a circuit breaker with the
same technical data as provided in the example for residual switching cycles, 50 breaking operations with
rated short-circuit breaking current are permitted.
A warning signal should be issued when the number of possible breaking operations with rated short-circuit
breaking current is less than 3. For that condition, you set the Threshold value based on the following calcu-
lation:

[FoCBW2P4-301012-01.tif, 1, en_US]

10.12.5.3 Settings

Addr. Parameter C Setting Options Default Setting


2P-method
_:1 2P-method:Mode • off off
• on
• test
_:101 2P-method:Switching 100 to 1000000 10000
cycles at Ir
_:102 2P-method:Rated short- 10 A to 100000 A 25000 A
circ.cur. Isc
_:103 2P-method:Switching 1 to 1000 50
cycles at Isc
_:104 2P-method:Threshold 0 to 10000000 100

10.12.5.4 Information List

No. Information Data Class Type


(Type)
2P-method
_:54 2P-method:Inactive SPS O
_:52 2P-method:Behavior ENS O
_:53 2P-method:Health ENS O
_:301 2P-method:Endur.A INS O
_:302 2P-method:Endur.B INS O
_:303 2P-method:Endur.C INS O
_:304 2P-method:Warning ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1521


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12.6 I2t-Method Stage

10.12.6.1 Description

Logic of the Stage

[LoCBWI2t, 1, en_US]

Figure 10-38 Logic of the I2t-Method Stage

Calculation of the Wear


The I2t method evaluates the wear of a circuit breaker based the sampled measuring values of the phase
currents during the arc time. The duration of the arc time is defined by the difference between the 2 settings
of parameters CB break time and CB opening time (see also Figure 10-32). The stage determines the
ending point of the arc time by searching backward the zero-crossing point of the phase currents after it
receives the logic release signal. Then, the squared fault currents during the arc time are integrated phase-

1522 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

selectively. The integrals are referred to the squared rated normal current of the circuit breaker as shown in
the following formula, with phase A as example.

[FoCBWI2T-301012-01.tif, 1, en_US]

Where:
Irated Rated normal current
iA(t) Sampled measured current value of phase A

The calculated squared tripping current integrals are added to the existing statistic values.You can reset or
preset the statistic value according to the specific application.

Circuit-Breaker Maintenance Warning


If the statistic value of any phase lies above the threshold, a phase-selective warning signal is generated.

10.12.6.2 Application and Setting Notes

Parameter: Threshold

• Default setting (_:101) Threshold = 10 000.00 I/Ir*s


You use the Threshold parameter to specify the maximum permitted integral of squared sampled measured
values of the phase currents.

10.12.6.3 Settings

Addr. Parameter C Setting Options Default Setting


I2t-method
_:1 I2t-method:Mode • off off
• on
• test
_:101 I2t-method:Threshold 0.00 I/Ir*s to 21400000.00 I/Ir*s 10000.00 I/Ir*s

10.12.6.4 Information List

No. Information Data Class Type


(Type)
I2t-method
_:54 I2t-method:Inactive SPS O
_:52 I2t-method:Behavior ENS O
_:53 I2t-method:Health ENS O
_:301 I2t-method:ΣI²t A BCR O
_:302 I2t-method:ΣI²t B BCR O
_:303 I2t-method:ΣI²t C BCR O
_:304 I2t-method:Warning ACT O

SIPROTEC 5, 7SJ82/7SJ85, Manual 1523


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12.7 Supervision CB Make Time Stage

10.12.7.1 Description

Logic of the Stage

[Lo_sup-cb-make-time, 1, en_US]

Figure 10-39 Logic of the Supv.CB Make Time Stage

Operating Mode
The stage for the supervision of the circuit-breaker make time calculates the time between the circuit-breaker
closing command and the point in time when the current from at least one phase exceeds the
Oper.current threshold. If this threshold has not been exceeded after 2.5 times the value of the param-
eter CB make time, the measurement is canceled and the output value Make time is set to 0 and marked
with the quality invalid.
If at least one phase of the current has exceeded the parameter Oper.current threshold or the param-
eter Current thresh. CB open at the time of the circuit-breaker closing command, the measurement is
canceled and the output value Make time is marked with the quality invalid.
You can define 2 independent thresholds for the supervision of the measured make time. When these thresh-
olds are exceeded, the corresponding outputs Warning 1 and Warning 2 are activated for 100 ms. These
can be routed in the log.

1524 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12.7.2 Application and Setting Notes

Parameter: Level of warning 1

• Default setting (_:101) Level of warning 1 = 5 %


With the parameter Level of warning 1, you define the percentage the measured value is allowed to
exceed the parameter CB make time at the output Make time, before the output Warning 1 is set. The
output Warning 1 then drops out after 100 ms.

Parameter: Level of warning 2

• Default setting (_:102) Level of warning 2 = 10 %


With the parameter Level of warning 2, you define the percentage the measured value is allowed to
exceed the parameter CB make time at the output Make time, before the output Warning 2 is set. The
output Warning 2 then drops out after 100 ms.

Parameter: Oper.current threshold

• Default setting (_:103) Oper.current threshold = 0.100 A


With the parameter Oper.current threshold, you define the current threshold. If the measured value
exceeds this threshold, the measured value is detected as flowing operating current. As soon as an operating
current flows, the end of the time interval Make time is detected.

Parameter: Delay correction time

• Default setting (_:104) Delay correction time = 0.000 s


With the parameter Delay correction time, you define a correction value which will be subtracted from
the Make time during calculation. This allows you to compensate delays caused by the system, for example,
relay residual times, if necessary.

10.12.7.3 Settings

Addr. Parameter C Setting Options Default Setting


Supv.CB mak.t.
_:1 Supv.CB mak.t.:Mode • off off
• on
• test
_:101 Supv.CB mak.t.:Level of 1 % to 100 % 5%
warning 1
_:102 Supv.CB mak.t.:Level of 1 % to 100 % 10 %
warning 2
_:103 Supv.CB 1 A @ 100 Irated 0.030 A to 35.000 A 0.100 A
mak.t.:Oper.current 5 A @ 100 Irated 0.15 A to 175.00 A 0.50 A
threshold
1 A @ 50 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:104 Supv.CB mak.t.:Delay -0.050 s to 0.050 s 0.000 s
correction time

SIPROTEC 5, 7SJ82/7SJ85, Manual 1525


C53000-G5040-C017-A, Edition 06.2019
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring

10.12.7.4 Information List

No. Information Data Class Type


(Type)
Supv.CB mak.t.
_:54 Supv.CB mak.t.:Inactive SPS O
_:52 Supv.CB mak.t.:Behavior ENS O
_:53 Supv.CB mak.t.:Health ENS O
_:301 Supv.CB mak.t.:Make time MV O
_:302 Supv.CB mak.t.:Warning 1 SPS O
_:303 Supv.CB mak.t.:Warning 2 SPS O

1526 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
11 Functional Tests

11.1 General Notes 1528


11.2 Direction Test of the Phase Quantities (Current and Voltage Connection) 1529
11.3 Direction Test of Ground Quantities for Directional Ground-Fault Functions 1530
11.4 Functional Test of Thermal Overload Protection 1534
11.5 Primary and Secondary Tests of the Circuit-Breaker Failure Protection 1536
11.6 Circuit-Breaker Test 1539
11.7 Functional Test of the Inrush-Current Detection 1542
11.8 Functional Test of Transient Ground-Fault Protection 1543
11.9 Functional Test of the Trip-Circuit Supervision 1544
11.10 Functional Test for the Phase-Rotation Reversal 1545
11.11 Functional Test for Overvoltage Protection with Zero-Sequence Voltage/Residual 1546
Voltage
11.12 Primary and Secondary Testing of the Synchronization Function 1548
11.13 Testing the Negative-Sequence Current 1552
11.14 Reverse-Power Protection 1553
11.15 Functional Test Protection Communication 1556
11.16 Functional Test for Overexcitation Protection 1558
11.17 Functional Test Differential Protection for Capacitor Banks 1559
11.18 Commissioning Hints for Voltage Control 1561

SIPROTEC 5, 7SJ82/7SJ85, Manual 1527


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.1 General Notes

11.1 General Notes


Various tests have to be performed for commissioning to warrant the correct function of the device.
For tests using secondary test equipment, make sure that no other measurands are locked in and trip and
close commands to the circuit breakers are interrupted, unless otherwise indicated.
Secondary tests can never replace primary tests because they cannot include connection faults. They provide a
theoretical check of the setting values only.
Primary tests may be done only by qualified personnel who are familiar with the commissioning of protection
systems, with the operation of the system, and with safety regulations and provisions (switching, grounding,
etc.).
Switching operations also have to be performed for the commissioning. The described tests require that these
be capable of being performed safely. They were not conceived for operational checks.

1528 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.2 Direction Test of the Phase Quantities (Current and Voltage Connection)

11.2 Direction Test of the Phase Quantities (Current and Voltage


Connection)
The proper connection of the current and voltage transformer is checked with load current over the line to be
protected. For this, the line must be switched on. A load current of at least 0.1 Irated has to flow over the line; it
should be ohmic to ohmic inductive. The direction of the load current has to be known. In case of doubt,
meshed and ring systems should be unraveled. The line remains switched on the for the duration of the meas-
urements.
The direction can be derived directly from the operational measured value. First make sure that the power
measured values correspond to the power direction. Normally, it can be assumed that the forward direction
(measuring direction) goes from the busbar toward the line.
Using the power measured values at the device or DIGSI 5, make sure that it corresponds to the power direc-
tion:

• P is positive if the active power flows in the line or protected object.

• P is negative if the active power flows to the busbar or out of the protected object.

• Q is positive if the inductive reactive power flows in the line or protected object.

• Q is negative if the inductive reactive power flows to the busbar or out of the protected object.
If the power measured values have a different sign than expected, then the power flow is opposite the
current-direction definition. This can be the case, for example, at the opposite end of the line . The current-
transformer neutral point then points in the direction of the protected object (for example line).
If the values are not as expected, it may be due to a polarity reversal at the voltage connection.
As a final step, switch off the system.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1529


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.3 Direction Test of Ground Quantities for Directional Ground-Fault Functions

11.3 Direction Test of Ground Quantities for Directional Ground-Fault


Functions

11.3.1 Overview

If the CT and VT connections are in the way that the ground quantities (3I0 and V0) are calculated by the
device from the phase quantities, then, no additional directional test is required. Testing according to
11.2 Direction Test of the Phase Quantities (Current and Voltage Connection) is sufficient.
If the ground current IN or the ground voltage VN is directly measured via a device input (usually I4 or V4), the
correct polarity of the ground current and the ground voltage path must be checked.

! DANGER
Live system parts! Capacitive coupled voltages on dead parts!
Noncompliance with the following measures can lead to death, serious physical injury, or consider-
able material damage.
² Primary measures may be performed only on dead and grounded system parts.

11.3.2 Directional Testing for Solid or Resistive-Grounded Systems

Primary Test
The primary test is used for the evaluation of the correct polarity of the transformer connections for the deter-
mination of the ground-fault direction.
To generate a zero-sequence voltage V0, the e-n winding of one phase in the voltage-transformer set (for
example, phase A) is bypassed, see Figure 11-1. If no connection on the e–n windings of the voltage trans-
former is provided, the corresponding phase is disconnected on the secondary side, see Figure 11-2. Only the
current of the transformer in the phase of which the voltage is missing is transferred via the current circuit. If
the line carries resistive-inductive load, the protection is subject to the same conditions as existing during a
ground fault in line direction.
For directional testing, the Directional ground-fault protection function (67N) is configured and at least one
stage is switched on. The pickup threshold of the stage must be below the load current of the line. If not, the
binary input signal (_:2311:501) >Test of direction can be activated to lower the threshold tempo-
rarily for testing means without changing the respective parameter.
After switching the line on and off again, you can check the pickup signal of the directional protection stage in
the fault log. A forward information must be logged. If no pickup information is logged at all, the 3I0 or U0
threshold is not exceeded.
If a wrong direction is logged, one of the following conditions may have occurred:

• The direction of the load flow is from the line towards the busbar.

• The ground-current connection is incorrect.

• The voltage connection is incorrect.

NOTE

i Siemens recommends not to change parameter settings for the test. However, if parameters were changed
for this test, they must be returned to their original state after completing the test!

1530 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.3 Direction Test of Ground Quantities for Directional Ground-Fault Functions

[ConnPolarit1_diagram, 1, en_US]

Figure 11-1 Polarity Testing, Example with Current Transformers Configured in a Holmgreen-Connection
and VTs with Broken-Delta Connection

[ConnPolarit2_201507, 1, en_US]

Figure 11-2 Polarity Testing, Example with Current Transformers Configured in a Holmgreen-Connection
and VTs with Star Connection

SIPROTEC 5, 7SJ82/7SJ85, Manual 1531


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.3 Direction Test of Ground Quantities for Directional Ground-Fault Functions

11.3.3 Directional Testing for Isolated or Resonant-Grounded Systems

Secondary Test with Core Balance Current Transformer


The secondary test is used for the evaluation of the correct ground-fault direction of the directional ground-
fault protection functions. With this test, a core balance current transformer that is incorrectly connected can
also be found.

[dw_secondary_test_SGFP, 1, en_US]

Figure 11-3 Connection with Primary Current Injection

In the preceding figure, the red pilot wire must be wired only for the testing purpose through the core balance
current transformer.
² Make the connections of the test equipment according to Figure 11-3.
² Route the pilot wire through the core balance current transformer in the direction towards the protection
object (towards the feeder).
² To achieve a higher measured ground current, route the pilot wire multiple times through the core
balance current transformer.
² The equivalent primary test current is the test current of the test device multiplied by the number of pilot-
wire windings.
² Inject the test quantities according to the following table. Select the quantities according to the
networking grounding and direction to be tested.

1532 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.3 Direction Test of Ground Quantities for Directional Ground-Fault Functions

Neutral Point Isolated Resonant-Grounded


Direction Forward Reverse Forward Non-faulty
VA (V1) 0V 0° 0V 0° 0V 0° 0V 0°
VB (V2) 100 V ‑150° 100 V ‑150° 100 V ‑150° 100 V ‑150°
VC (V3) 100 V +150° 100 V +150° 100 V +150° 100 V +150°
Vda/dn (V4) 100 V +180° 100 V +180° 100 V +180° 100 V +180°
IA = 3I0 (I142) 2A +90° 2A ‑90° 1A 0° 2A ‑90°

² You can check the test result by the direction information from the log.

Primary Test
The primary test is used for the evaluation of the correct polarity of the transformer connections for the deter-
mination of the ground-fault direction.
For directional testing, the Directional sensitive ground-fault detection function (67Ns) is configured and a
directional stage is switched on. For example, the directional 3I0> stage with cos φ or sin φ measurement.
The most reliable test is the one with a primary ground fault. Proceed as follows:
² Isolate the line and ground it on both sides; on the farthest line end it must remain open during the
entire test.
² Place a 1-phase ground fault bridge on the line. For overhead lines, this can be done at an arbitrary loca-
tion, in any case behind the current transformer (as seen from the busbar of the feeder to be tested). For
cables, the grounding is done on the farthest end (sealing end).
² Remove the protective grounding from the line.
² Switch on the circuit breaker on the line to be tested.
² Check direction indicator (LED if routed).
² Check the indication (_:302) Ground fault in the ground-fault log or fault log with regard to its
direction. The indication (_:302) Ground fault forward must be logged as direction information.
If backward is determined as the direction, either with the current connections or the voltage connec-
tions, there is an inversion in the neutral path. For the display unknown, the ground current is probably
too low.
² Switch the line off and ground it.
This completes the test.

42 Refers to I1 of the test equipment in Figure 11-3.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1533


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.4 Functional Test of Thermal Overload Protection

11.4 Functional Test of Thermal Overload Protection


Secondary Test
For the secondary test for the overload protection, note that all setting parameters refer to primary variables
of the protected object. The protection device extracts the current transformer ratio from the power-system
data and internally performs the adjustments to device nominal variables. Take these characteristics into
account for the test.
² Reset the thermal memory before you repeat the test. This is possible, for instance, via the binary input
indication >Reset thermal replica. If the function is reparameterized or is switched off, the
thermal replica will also be reset.

Test without Previous Load


² Test the operate time at 1.5 I/Irated, obj.
In the example, the following power-system data are assumed:
Irated, obj = 483 A
Irated, transf.prim = 750 A
Irated, transf.sec = 1 A

The primary test current is 1.5 * 483 A = 724.5 A. This results in a secondary current of 724.5 A *1A/750A =
0.966 A. A secondary current of 0.966 A must therefore be supplied.
² Calculate the operate time with the following formula. Enter only primary variables here.
² Set Iprevious load = 0. The setting parameters reveal the K-factor (for example, 1.1) and the Thermal
time constant (for example, 600 s or 10 min).
² Test from the cold state.

[foauslpr-190309-01.tif, 2, en_US]

² At a current of 0.966 A supplied on the secondary side, the protection function must trip after 463 s.

Test with Previous Load


² The object rated current (Iprevious load= Irated, obj) flows at a previous load of 1 (100 %).

² Supply 483 A *1 A/750 A = 0.644 A in this case.


After a finite time (greater than 5 τth), the stationary previous load sets in.
K-factor
² If you abruptly increase the supplied secondary current from 0.644 A to 0.966 A (1.5 I/Irated, obj), the over-
load protection will trip in the following time.

[foauslpr-190309-02.tif, 2, en_US]

1534 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.4 Functional Test of Thermal Overload Protection

NOTE

i Owing to the relatively large time constants in practice, the tests are carried out with significantly reduced
time constants. Reset the original setting value after completing the tests.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1535


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.5 Primary and Secondary Tests of the Circuit-Breaker Failure Protection

11.5 Primary and Secondary Tests of the Circuit-Breaker Failure


Protection
Integration of the Protection Function into the Station
The integration of the protection function into the station must be tested in the real-life application. Because
of the multitude of possible applications and possible system configurations, the required tests cannot be
described here in detail.

NOTE

i Always keep the local conditions, the station plans, and protection plans in mind.

NOTE

i Siemens recommends isolating the circuit breaker of the tested feeder at both ends before starting the
tests. Line disconnector switches and busbar disconnector switches must be open so that the circuit
breaker can be operated without risk.

General Precautions

! CAUTION
Tests on the local circuit breaker of the feeder cause a trip command to the output to the adjacent (busbar)
circuit breakers.
Noncompliance with the following measure can result in minor personal injury or physical damage.
² In a first step, interrupt the trip commands to the adjacent (busbar) circuit breakers, for example, by
disconnection of the corresponding control voltages.

For testing the circuit-breaker failure protection, it must be ensured that the protection (external protection
device or device-internal protection functions) cannot operate the circuit breaker. The corresponding trip
command must be interrupted.
Although the following list does not claim to be complete, it can also contain points, which have to be ignored
in the current application.

Test Modes
The device and the function can be switched to test mode. These test modes support the test of the function
in different ways:
Test Modes Explanation
Device in test mode This operating mode is relevant for the following tests:
1. Approach of current thresholds in the case of an external start: Supervi-
sion of the binary input signals in the case of an external start is disabled.
This setting allows a static activation of the starting signals in order to
approach the current threshold.
2. Check whether the issued trip commands actuate the corresponding
circuit breakers, because the device contacts are also actuated in the device
test mode.
CBFP function in test mode This operating mode is important for function tests in which the generated
(device is NOT in test mode) operate indications are NOT supposed to actuate the binary outputs.

1536 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.5 Primary and Secondary Tests of the Circuit-Breaker Failure Protection

NOTE

i When the function or device is in test mode, all indications are given a test bit.

NOTE

i In the mode Device in test mode, the operate indications generated by the function operate the binary
outputs.

The function must also be tested in its normal, switched-on condition.


Consider the following in this case:
² The device contacts are actuated.
² Binary input signal supervision (in the case of an external start) is enabled and blocks the function.
² All indications generated are generated without test bit.

Circuit-Breaker Auxiliary Contacts


When circuit-breaker auxiliary contacts are connected to the device, they make an essential contribution to the
reliability of the circuit-breaker failure protection, provided that their settings are set accordingly.
² Make sure that the correct assignment has been checked.

Internal Starting Conditions (Trip Command from Internal Protection Function)


The internal start can be tested by means of tripping a protection function, for example, the main protection
function of the device.
² Check the settings for circuit-breaker failure protection. See also chapter 6.42.4 Application and Setting
Notes.
² For the circuit-breaker failure protection to be able to pick up, a phase current (see current-flow criterion)
must be present. This can be generated by a device-internal test sequence (see description in the Oper-
ating manual). It can also be a secondary test current.
² Generate the trip for the protection function. This can be generated within the device by a test sequence
(see description in the Operating manual) or by creating corresponding secondary test values.
² The trip command(s) and their time delay compared to the pickup, depending on the parameterization.

External Starting Conditions (Trip Command from External Protection Function)


If external protection devices are also able to start the circuit-breaker failure protection, the external starting
conditions require checking.
² Check the settings for circuit-breaker failure protection.
See also chapter 6.42.4 Application and Setting Notes.
² For the circuit-breaker failure protection to be able to pick up, a phase current (see current-flow criterion)
must be present. This can be generated by a device-internal test sequence (see description in the Oper-
ating manual). It can also be a secondary test current.
² Activate the binary input or inputs to which the start signal and possibly also the release signal for the
CBFP function are routed. This can be done in 2 ways:
– Via internal test sequences
– By controlling the binary input or inputs via an auxiliary voltage
² Check the start input signal, and if available, check the enable input signal in the spontaneous or fault
messages.
² Check the pickup indication in spontaneous or fault indications.
² The trip command(s) and their time delay compared to the pickup, depending on the parameterization.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1537


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.5 Primary and Secondary Tests of the Circuit-Breaker Failure Protection

Start by Trip Command from the External Protection


² Check the static and - in case of 2-channel operation - also the dynamic supervision of the binary input
signals. For this purpose, induce pickup of the supervision and check the supervision indications and the
ready signal in the event log buffer.

Start by Trip Command from the External Protection without Current Flow
² If start is possible without current flow: (see Start by trip command from the external protection).

Repetition of the Local Tripping (T1)


² Make sure that the trip repeat signal controls a 2nd circuit (2nd coil) for switching off the circuit breaker.

Backup Tripping in the Case of a Circuit-Breaker Failure (T2)


For tests in the station, it is important to check that the distribution of trip commands to the adjacent circuit
breakers in the case of a circuit-breaker failure is correct. The adjacent circuit breakers are all circuit breakers,
which must be tripped in order to ensure interruption of the short-circuit current if the feeder circuit-breaker
fails. They are therefore the circuit breakers of all feeders which feed the busbar or busbar section to which
the feeder with the fault is connected.
A general detailed test guide cannot be specified because the layout of the adjacent circuit breakers depends
largely on the system topology.
² With multiple busbars, the trip distribution logic for the adjacent circuit breakers must be checked.
The test has to check for every busbar section that, in case of a failure of the feeder circuit-breaker under
observation, only those circuit breakers which are connected to the same busbar section are tripped.

Backup Tripping on Circuit-Breaker Failure (T2), Tripping of the Opposite End


If the trip command of the circuit-breaker failure protection must also trip the circuit breaker at the opposite
end of the tested feeder, the communication channel for this remote trip has to be tested as well.
² It is practical to test the communication channel for the remote trip while transmitting other signals in
accordance with 11.15.1 Checking the Protection-Data Communication.

Termination
² All temporary measures taken for testing must be undone, such as special switch positions, interrupted
trip commands, changes to setting values, or individually switched off protection functions.

1538 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.6 Circuit-Breaker Test

11.6 Circuit-Breaker Test


The Circuit-breaker test function enables you to easily perform a complete test of the trip circuit, the closing
circuit, and the circuit breaker. For this, the circuit-breaker test carries out an automatic opening and closing
cycle or an only-open cycle of the circuit breaker during operation. You can also include a current-flow crite-
rion in the test. The effect of the current-flow criterion is to ensure the circuit-breaker test is only carried out if
the current flow across the circuit breaker is below the parametrizable threshold.

NOTE

i If the circuit-breaker auxiliary contacts are not connected, a circuit breaker that has been opened can be
permanently closed.

The following test program is available for you to carry out the circuit-breaker test.
No. Test Program
1 3-phase open/closed cycle

Structure of the Function


The Circuit-breaker test function is used in protection function groups for circuit breakers.

[dwcbch01-240217, 1, en_US]

Figure 11-4 Embedding of the Function

[dwzecbc3p2-030217, 2, en_US]

Figure 11-5 Structure of the Function

Test Procedure
The following conditions must be satisfied before the circuit-breaker test can start:
² If a circuit-breaker auxiliary contact signals the position of the breaker pole to the device via the binary
inputs of the signal Position, the test cycle is not initiated unless the circuit breaker is closed.
² If the circuit-breaker auxiliary contact has not been routed, you must ensure that the circuit breaker is
closed.
² The circuit breaker must be ready for an open-closed-open or only-open cycle (indication >Ready).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1539


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.6 Circuit-Breaker Test

² A protection function must not have been picked up in the circuit-breaker protection function group
responsible for the circuit breaker.

[scCBTest3p, 1, en_US]

Figure 11-6 Settings for the Circuit-Breaker Test

Figure 11-7 shows the progression over time of an open-close cycle. If you activated the (_:6151:102)
Trip only option, the close command will not be executed and the dead time will not be taken into
account.
If a circuit-breaker auxiliary contact is connected, the function waits for the indication circuit breaker Posi-
tion = open after the trip command is generated. When the indication Position = open is received, the
close command is transmitted after a dead time (parameter (_:6151:101) Dead time) for an open-close
cycle. If the feedback from the circuit-breaker positions is not received within the maximum transmission time
(Dead time + 2 · Output time + 5 s), the circuit-breaker test is aborted and considered to be failed. The
proper functioning of the circuit breaker is monitored via the feedback on the circuit-breaker positions.

[dwcbch03-300913, 1, en_US]

Figure 11-7 Progress over Time of a Circuit-Breaker Test Cycle

Use the (_:6151:103) Consider current criterion parameter to ensure the circuit-breaker test is
only carried out when the current flowing through the circuit breaker does not exceed a specific current
threshold (parameter (_:6151:104) Current threshold). Otherwise, the circuit-breaker test is not
started.
² If the current-flowcriterion is deactivated, the current threshold is not evaluated. The circuit-breaker test
is performed irrespective of the current-flow level through the circuit breaker.

NOTE

i The circuit-breaker test does not perform a synchrocheck even if the synchrocheck has been configured in
the protection-function groups for circuit breakers. This can cause stability problems in the system during a
3-pole interruption. Therefore, a 3-pole circuit-breaker test should be very short, or not performed at all
under load.

You can start the test program as follows:

• Via the device-control panel

• Via DIGSI

• Via communication protocols

• Via control commands, which you can also connect in the CFC

1540 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.6 Circuit-Breaker Test

The following figure illustrates operation of the circuit-breaker test in DIGSI.

[sccb_3pol, 1, en_US]

Figure 11-8 Circuit-Breaker Test in the Test Suite in DIGSI

² Select the function in the project tree on the left in the online access.
² Start the desired test program in the upper portion of the working area.
² The corresponding feedback is displayed in the bottom portion of the working area. Additional informa-
tion about the behavior of other functions while the circuit-breaker test is being performed can be read in
the operational log.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1541


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.7 Functional Test of the Inrush-Current Detection

11.7 Functional Test of the Inrush-Current Detection


General
² For the test, make sure that the test current reflects the typical inrush current.
² Perform the test with transient signals. These can be recorded inrush currents or simulated currents from
a transient system model.
² When using synthetic signals, observe the notes on the individual measuring principles.

Harmonic Analysis
² Superimpose on the fundamental-component current a test current of double frequency (2nd harmonic)
and test the pickup behavior with this.
² Cause a threshold value excess (internal pickup) for one of the protection functions that you want to
block.
- or -
² Apply a test current with a load current as lead (current step).
The inrush current detection creates a blocking signal.

CWA Process
² Create a test current that has flat ranges of a minimum width of 3 ms simultaneously in all 3 phase
currents.
The inrush current detection creates a blocking signal.

1542 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.8 Functional Test of Transient Ground-Fault Protection

11.8 Functional Test of Transient Ground-Fault Protection


General
This function requires the correct polarity of the ground current IN and the neutral-point displacement voltage
VN respectively the zero-sequence voltage V0. For the direction test of these quantities, refer to chapter
11.3 Direction Test of Ground Quantities for Directional Ground-Fault Functions.
The function is based on the evaluation of the transient in the zero-sequence system after the ground-fault
ignition.
For issuing the signal (_:13021:302) Ground fault, the following 2 conditions must be met:

• There is a transient in the ground quantities.

• The fundamental compoment of the zero-sequence voltage V0 exceeds the threshold (_:13021:103)
V0> threshold value.
The following 2 methods are available for testing of the signal (_:13021:302) Ground fault:

• Replaying real transient ground-fault recordings to the device

• Using secondary test equipment which allows to simulate transients ground faults
However, the setting of parameter (_:13021:103) V0> threshold value cannot be tested precisely
with the mentioned 2 methods, since this test requires a static V0. An easy way to test the setting is described
in the following.

Secondary Test
This test must be carried out by injecting static secondary quantities. The test equipment needs to be config-
ured in a way that it generates zero-sequence current 3I0 and zero-sequence voltage V0, which are injected to
the SIPROTEC 5 device. By carrying out a shot, for example, a status change from zero-sequence values of 0 A
and 0 V to the values not equal to zero, a transient is generated. The signal (_:13021:302) Ground
fault is issued as long as the static zero-sequence voltage of the 2nd state is greater than the set threshold.
As amplitude for the secondary 3I0, 100 mA is a suitable value. In this test, the directional result contained in
the signal (_:13021:302) Ground fault is not defined and relevant, since the task is to test the setting
of parameter (_:13021:103) V0> threshold value only.
For testing the threshold, shots must be carried out with a static V0 slightly below the threshold and slightly
above the threshold, for example, to 98 % and 102 % of the threshold value or to a threshold value of -0.2 V
and +0.2 V (the greater absolute deviation of the threshold value must be selected) .
Consider that the V0 threshold is defined according to the definition of the symmetrical components. A full
neutral-point displacement voltage VN of 100 V causes V0 = 57.7 V.

Example

• (_:13021:103) V0> threshold value = 15 V

• 3 shots from 0 to V0 = 14.7 V and 3I0 = 100 mA


No signal (_:13021:302) Ground fault is issued.

• 3 shots from 0 to V0 = 15.3 V and 3I0 = 100 mA


Signal (_:13021:302) Ground fault is issued
If the test result is not as expected, check the injected static V0 voltage via the operational measurement of
the device which contains the zero-sequence components.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1543


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.9 Functional Test of the Trip-Circuit Supervision

11.9 Functional Test of the Trip-Circuit Supervision


General
² For the test, make sure that the switching threshold of the binary inputs is clearly below half the rated
value of the control voltage.

2 Binary Inputs
² Make sure that the binary inputs used are isolated.

1 Binary Input
² Make sure that, in the circuit of the 2nd circuit-breaker auxiliary contact, an equivalent resistance R is
connected.
² Observe the dimensioning notes under the section Equivalent resistance R.

1544 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.10 Functional Test for the Phase-Rotation Reversal

11.10 Functional Test for the Phase-Rotation Reversal


² Check the phase sequence (direction of rotating field) at the device terminals. It must correspond to the
setting of the Phase sequence parameter.
² The output indication Phase sequence ABC or Phase sequence ACB displays the determined
phase sequence. This must correspond to the phase sequence that was set.
² You can also determine the phase sequence via the Symmetrical components measured values. If you
obtain negative-sequence system variables (V2, I2) and no positive-sequence system variables (V1, I1) with
symmetrical 3-phase infeed, the setting parameter Phase sequence does not correspond to the
connection.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1545


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.11 Functional Test for Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

11.11 Functional Test for Overvoltage Protection with Zero-Sequence


Voltage/Residual Voltage
Checking the Stator Ground-Fault Protection with the Machine
You have to check whether the protection function and the protection ranges are functioning correctly. The
following tests are intended for the unit connection.
You can check the protection range by performing a test with a ground fault at the generator terminals. The
ground fault test in the power system enables you to verify the noise suppression of the load resistor.

Checking the Protection Range with a Machine Ground Fault

! DANGER
Do not touch live parts or reach into rotating machines.
Touching live parts or reaching into rotating machines will result in death or serious injury.
² Perform primary measures only when the machine is at standstill and the system components are de-
energized and grounded.

² Insert a 1-phase-to-ground jumper into the terminal circuit of the machine.


² Set the Mode parameter in the protection stage to test. This prevents the trip command from being
generated for the stage.
² Start the machine and excite it slowly up to approx. 20 % of the rated machine voltage.
² From the operational measured values, check the plausibility of the zero-sequence voltage V0 and the
input voltage at the connected input.
² Determine the protection range from the pickup voltage.
The following applies for the protection range S:

[foschzbe-130309-01.tif, 2, en_US]

Example: Measurement with secondary voltages


VNG: Generator voltage transformed to the transformer secondary side = 100 V
V0, pickup value: Measured zero-sequence voltage at pickup = 5.68 V
S: Resulting protection range = 90 %
² Check the messages in the message buffer. If the Detection of faulty phase parameter is set to
yes, check the display of the phase affected by the fault.
² Shut the machine down and remove the ground fault bridge.
² Set the Mode protection stage parameter to on.

1546 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.11 Functional Test for Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

Checking Disturbance-Voltage Suppression in the Load Resistor with a System Ground Fault

! DANGER
Do not touch live parts or reach into rotating machines.
Touching live parts or reaching into rotating machines will result in death or serious injury.
² Perform primary measures only when the machine is at standstill and the system components are de-
energized and grounded.

² With the primary system de-energized and grounded, insert a 1-pole ground fault bridge on the high-
voltage side of the unit transformer.

! CAUTION
If there is a neutral-point grounding at the transformer and simultaneously a grounding on the high-
voltage side, do not perform the test.
Material can be damaged during the test if there is a neutral-point grounding at the transformer and
simultaneously a grounding on the high-voltage side.
² Neutral grounding at the transformer must be interrupted during the test.

² Start the machine and excite it slowly up to 30 % of the rated machine voltage.
² Read the zero-sequence voltage V0, measured value from the operational measured values.

² Extrapolate the zero-sequence voltage to 100 % of the machine voltage (V0, fault).

² Calculate the safety margin by dividing the calculated fault value by the set threshold value.
If the result is less than 0.5, the safety margin is sufficient. If the fault voltage is lower, you can increase the
sensitivity of the protection function.

EXAMPLE:
V0, meas. = 0.75 V
Vthreshold value = 5.68 V
V0, fault = 0.75 V * 100 % / 30 % = 2.5 V
Safety margin = 2.5 V / 5.68 V = 0.44
The calculated safety margin of 0.44 is sufficient because it is below 0.5.
² Shut the machine down and de-excite it. Remove the ground-fault bridge.
² Restore neutral-point grounding if you require grounded operation of the neutral on the high-voltage
side of the unit transformer.
When using the function for startup ground-fault protection on a busbar connection, carry out the same check
as for the unit connection, but only the part Test during machine ground fault.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1547


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.12 Primary and Secondary Testing of the Synchronization Function

11.12 Primary and Secondary Testing of the Synchronization Function


Measuring the Circuit-Breaker Make Time
Under asynchronous system conditions, the circuit-breaker make time must be measured and set correctly.
This achieves an exact parallel switching with a phase angle 0o. If switching occurs only in synchronous system
conditions, this section can be skipped.
The make time can be determined via the following 2 methods:

• By reading from a fault record (recommended method)

• With external timer


1. A simple option for determining the make time involves reading the time between the close command and
closure of the switch pole via the fault record. The time determined here is the real make time and not the
operating time of the circuit breaker. You do not have to add any further time.
Siemens recommends the following procedure:
² Establish a condition in which the circuit breaker can be closed without hazard.
² If V2 is switched through, activate the operating mode Close cmd. at V1< & V2> for the synchroni-
zation stage by setting to yes.
If V1 is switched through, activate the operating mode Close cmd. at V1> & V2<.
² Make sure that the fault recorder is turned on. Via a temporary CFC chart, link the signal Release
close cmd. of the active synchronization stage to the binary input signal >Manual start (of the
fault recorder). With the release of closure, a fault record of the parameterized duration is set up (the
default setting of 500 ms is more than adequate for this).
² Starting the synchronization stage. The device activates immediately.
² Read the fault record and determine the make time via SIGRA (see Figure 11-9).
Use the 2 cursors and the time-measuring function for this. Position the first cursor on the raising close
command. The occurrence of the 2nd voltage signals the closed power-switching poles. Place the 2nd
cursor on the raising 2nd voltage.
² Set the determined time with the CB make time parameter. Round off to the next lower adjustable
value. Proceed in the same way for all other sync stages.
² Set the parameter Close cmd. at V1< & V2> or parameter Close cmd. at V1< & V2< back to
its source value.
² Delete the CFC chart.

1548 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.12 Primary and Secondary Testing of the Synchronization Function

[scsyn001-170510-01.tif, 1, en_US]

Figure 11-9 Measurement of the Circuit-Breaker Make Time

2. The configuration in Figure 11-10 is suitable for measuring the circuit-breaker operating time with an
external timer. Set the timer to the range 1 s or a tripping of 1 ms.
Connect the circuit breaker manually. The timer is started simultaneously by this. After the poles of the circuit
breaker close, the voltage VLine appears. The timer is then stopped.
If the timer is not stopped owing to an unfavorable closing moment, repeat the attempt.
Siemens recommends calculating the average value from several (3 to 5) successful switching attempts.

NOTE

i Add the command output time of the protected device to measured time. This exclusively depends in good
approximation on the binary output used for the close command. You can find the switching times for the
different binary outputs in the Technical data. Set the total time with the parameter CB make time.
Round off to the next lower adjustable value. Proceed in the same way for all other synchronization stages
used.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1549


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.12 Primary and Secondary Testing of the Synchronization Function

[dwsynae6-080211-01.tif, 1, en_US]

Figure 11-10 Measurement of the Circuit-Breaker Make Time

Checking the Measurement Chain


The measurement chain for the voltage measurement must be checked. As soon as one of the synchronization
stages to be used is closed, all the necessary functional measured values are calculated. The synchronization
stage, thus, does not have to be started for this check.
Proceed as follows when checking the measurement chain as a primary or secondary test:
a) As primary test
² Establish a synchronous state by closing the circuit breaker, if possible.
² Check the functional measured values within the synchronization function:
– The delta values must be 0.
– Check the voltages V1 and V2 for plausible values in comparison with the operational measured values
for the voltage.
– Check the frequencies f1 and f2 for plausible values in comparison with the operational measured
value for the frequency.

b) As secondary test
² Establish a synchronous state by applying synchronous voltage values at both measuring points.
² Check the functional measured values within the synchronization function:
– The delta values must be 0.
– Check the voltages V1 and V2 for plausible values in comparison with the operational measured values
for the voltage.
– Check the frequencies f1 and f2 for plausible values in comparison with the operational measured
value for the frequency.

Blind Switching Attempts when Used in Machines


Perform blind switching attempts when using the function in machines.
Requirement:
² You have checked the setting values again.
² The circuit breaker is switched off. The close command for the circuit breaker is interrupted (discon-
necting the close command). The system voltage is switched through for the measurement.

a) Attempt with asynchronous systems:


² Via manual control, set the generator to a speed slightly below the permitted frequency difference
according to the setting values Max. frequency diff. f2>f1 and Max. frequency diff.
f2<f1. The generator is excited to line voltage. You can read out the values in the operational measured
values.

1550 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.12 Primary and Secondary Testing of the Synchronization Function

² Start the synchronization stage, for example, externally with binary input signal or via the integrated
controller. You can use a synchronoscope to trigger the start at synchronism, that is, at 12 o'clock. The
duration until the close command then corresponds to a cycle with the duration 1/Δf. At a frequency
difference of 0.1 Hz, the duration is thus 10 s.
² Insofar as permissible, perform this attempt several time for oversynchronous switching and subsynchro-
nous switching.
² The switching performance can be checked with an external recorder or the integrated fault recording
function. You have to start the fault recording explicitly.
² You can repeat the blind switching attempts at the limits of the permissible voltage difference.

b) Attempt with synchronous systems:


² Start the synchronization stage, for example, externally with binary input signal or via the integrated
controller.
² Check the proper release for activation with the message log or via a fault record. You have to start the
fault recording explicitly. All activation conditions have to be fulfilled within the time Delay close
command.
If you observe the change between synchronous and asynchronous operation, raise the changeover
threshold f-threshold ASYN<->SYN slightly.

c) Attempt with synchrocheck:


² If you use this function in conjunction with the manual synchronization, check the proper release for
closure.
² Synchronize the generator manually. Start the synchronization stage externally via a binary input. Check
the proper release for closure with the indication log or via the fault record. You have to start the fault
recording explicitly.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1551


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.13 Testing the Negative-Sequence Current

11.13 Testing the Negative-Sequence Current


When testing, keep in mind that the measured values are standardized. In the setting I2/Irated, obj., they are
standardized to the rated current of the protected object. The conversion to secondary transformer values is
accomplished in the device.

EXAMPLE:
The threshold value is set to 10 % of the protected object.
Transformer: 100 A/1 A
Rated current of the protected object: 80 A

Action Steps
² At a setting of 10 %, the primary negative-sequence current is 80 A • 10 %/100 % = 8 A.
For a current transformer ratio of 100, test with a secondary current of 0.08 A.
² With a transformer of 100 A/5 A, the test current is higher by the factor 5. Test with 0.4 A. The pickup
value is at 1.1 • 0.4 A = 0.44 A.
² If deviations occur during the testing, you must check whether the power-system data were entered
correctly.

NOTE

i Keep in mind that the function works starting from the set minimum current.

1552 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.14 Reverse-Power Protection

11.14 Reverse-Power Protection

11.14.1 Secondary Test

When performing the secondary test, note that the setting value for the reverse power refers to the machine
variables. Due to the mismatching of the current transformer, you must check with reduced currents. You can
deduce the reduction from the ratio Irated, generator/ Irated, CT. Check the reverse-power protection at rated voltage.
If the voltage transformer is not adjusted to the rated generator voltage, correct the secondary voltage, too.
Use the following ratio:
Vrated, generator/Vrated, VT

11.14.2 Primary Test

For measurements on the protection current transformers and with sensitive setting of the reverse-power
protection, Siemens recommends determining the reverse power and the angle-correction values. Regardless
of the generator excitation, that is regardless of the reactive power Q, the reverse power P as a pure active
power is constant. The resulting characteristic curve is a straight line that runs parallel to the Q axis. Due to
possible angle errors of current transformers and voltage transformers, the protection device does not
measure a constant active power. The current flowing at this time, which can be assumed as being propor-
tional to the reactive power, has a substantial influence.
The deviations are determined with 3 measurements and the correcting quantity φcorr is determined from the
results.
To calculate the correction angle, enter the active power and reactive power measured with the device in the
following table.
Use the functional measured values P1avg and Q1avg (type averaged).

Table 11-1 Value Table for Angle Correction

State Reverse Power Reactive Power


Reactive power near zero P0 = Q0 =
Overexcited P1 = Q1 =
Underexcited P2 = Q2 =

[dw_RPP correction angle, 2, en_US]

Figure 11-11 Determining the Correction Angle φcorr

! CAUTION
Be careful if you operate the turbine without a certain minimum steam flow (cooling effect).
Operating the turbine without a certain minimum steam flow (cooling effect) can overheat the
turbine blades!
² The consumption of reverse power for a turbo-generator set is only allowed for a short time!

SIPROTEC 5, 7SJ82/7SJ85, Manual 1553


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.14 Reverse-Power Protection

! CAUTION
If the generator is underexcited, there is the risk of an out-of-step condition!
Non-observance of the following measures can result in minor personal injury or material damage.
² The following measures prevent the risk of an out-of-step condition.

² Regulate the driving power to 0 by closing the control valves. The generator draws its reverse power from
the electrical power system.
² Change the excitation until the reactive power Q = 0. As a control measurement, read the active power P0
and the reactive power Q0 with the sign, and enter the values in Table 11-1.

² Increase the excitation slowly until reaching approx. 30 % of the rated apparent power of the generator
(overexcited).
Read the reverse power P1 with the sign (negative) and the reactive power Q1 with the sign (positive) in
the functional measured values and note these 2 values in the values table.
² Reduce the excitation slowly until reaching approx. 30 % of the rated apparent power of the generator
(underexcited).
Read the reverse power P2 with the sign (negative) and the reactive power Q2 with the sign (negative) in
the functional measured values and note these 2 values in the values table.
² Run the generator again at no-load excitation and select the desired operating state.
² With the measured value pairs (P1, Q1 and P2, Q2), calculate the correction angle ϕ corr with the following
formula:

[fo_RPP correction angle, 2, en_US]

NOTE

i Insert the power values with the signs that you read previously!

² Enter this angle φcorr with the same sign as the new correction angle (parameter (_:2311:101) Angle
correction ):
Setting value (_:2311:101) Angle correction = φcorr
² You can determine the pickup value of the reverse-power protection from the measured values P1 and
P2.
Use the following formula: Ppickup = (P1+P2)/4
Set the value as pickup value: Parameter (_:991:3) Threshold = Ppickup

Check of the Reverse-Power Protection


With a generator that is connected to the power system, the reverse power results from closing the control
valves or from closing the quick stop.
² In both cases, check the consumed active power (reverse power). The valves could be leaking.
² Repeat the reverse-power measurement to confirm that the settings are correct.

1554 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.14 Reverse-Power Protection

² To check the efficiency of the reverse-power protection on the basis of the indications, use the parameter
(_:991:1) Mode to switch the reverse-power protection to test .
Proceed as follows:
² Start the generator and synchronize it with the power system.
² Close the control valves.
² From the functional measured value, take the reverse power that was measured by the protection device
as the active power. Use 50 % of the functional measured value as setting value for the reverse-power
protection.
² Increase the driving power up to normal operation.
² Check the quick-stop criterion.
Proceed as follows:

NOTE

i Make sure that the binary input >Stop valve closed is properly routed. The quick-stop criterion (the
pressure-operated switch or the limit switch on the quick-stop valve) must control this binary input.

² Close the quick-stop valve.


² From the functional measured value P1avg , take the reverse power that was measured by the protec-
tion device as the active power.
² If – contrary to expectations – this value is smaller than the reverse power when the control valves are
closed, take 50 % of this value as the setting value for the reverse-power protection.
² Shut down the machine by activating the reverse-power protection. Set the parameter (_:991:1)
Mode to on .

SIPROTEC 5, 7SJ82/7SJ85, Manual 1555


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.15 Functional Test Protection Communication

11.15 Functional Test Protection Communication

11.15.1 Checking the Protection-Data Communication

Checking the Protection-Data Communication


If the devices are connected to one another via the protection interface and switched on, they contact each
other automatically. If, for example, device 1 recognizes device 2, the successful connection is indicated (see
next figure). Accordingly, each device signals to all devices that aProtection-data communication is available.

[scprotec, 1, en_US]

Figure 11-12 Connection Establishment in DIGSI 5

Proper communication of the devices among each other can be supervised during operation.
² Check the connections for each protection interface in DIGSI 5.
If a connection is successfully established, the Status of topo recog. field shows the indication valid in DIGSI
5 (see Figure 11-12).
If 2 devices are parameterized incorrectly, the Status of topo recog. field shows the indication invalid (see
Figure 11-12).
In Figure 11-13 there is no protection-data communication between device 1 and device 2, that is, the protec-
tion interfaces 1 and 2 of device 1 do not receive data. The transmission of protection data is interrupted and
differential protection is ineffective. One reason for this can be a remote control with DIGSI via the protection
interface. In this case, the protection connection is interrupted and the connection is used exclusively for
DIGSI.

1556 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.15 Functional Test Protection Communication

[scprotco-061210-01.tif, 1, en_US]

Figure 11-13 Protection-Data CommunicationDeactivated

11.15.2 Directional Test

In the case of protection interfaces of type 1 and type 2, the complex phasors of the voltage and current meas-
uring point are exchanged between devices of one communication topology in order to be able to carry out a
directional test during commissioning, for example. DIGSI 5 depicts this in the form of a phasor diagram. You
can only route the measuring point to the protection interface. For 1 1/2 circuit-breaker layouts, a measuring
point can therefore be transferred and checked optionally. You can also check and test the 2nd measuring
point by rerouting. Furthermore, communication with DIGSI 5 can take place via the protection interface to
other devices of the constellation. For this purpose, the protection-interface connection is interrupted and
DIGSI 5 uses this connection for communication with the remote device.
² After completing the remote connection by DIGSI 5, the system switches back over to protection commu-
nication.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1557


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.16 Functional Test for Overexcitation Protection

11.16 Functional Test for Overexcitation Protection


Secondary Test

NOTE

i While performing the secondary test, ensure that the data of the protected object refer to the protection
function.

This means that a mismatch between the voltage transformer and the protected object will be corrected auto-
matically. For instance, when applying the secondary rated voltage and the rated frequency, this must not
result in a V/f value of 1.
The mismatch of the voltage transformer must be taken into consideration when selecting the test voltage.
Multiply the secondary test voltage with the following 'k' factor.

[fokfakuf-070513-01.tif, 1, en_US]

Example
Vrated,obj = 110 kV; Vrated, transf. = 100 kV
It follows from the above that k = 1.1. For example, when verifying the nominal conditions if the secondary
rated voltage is 100 V, a voltage of 1.1 * 100 V = 110 V must be supplied. The measured value of the function
Measured value V/f must display 1.0000.

NOTE

i When checking the dependent stage, ensure it is associated with a thermal replica. When repeating a test,
always reset the replica, using the binary input indication >Reset therm. replica(_:13951:501).

Primary Test
The plausibility check between instantaneous overexcitation and the displayed operational measured value is
used to verify the functionality of overexcitation.
Instantaneous overexcitation is a result of the following function:

[fomoweuf-070513-01.tif, 1, en_US]

where:
V Instantaneous voltage
Vrated Primary rated voltage of the protected object
f Instantaneous frequency in f
frated Rated frequency

1558 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.17 Functional Test Differential Protection for Capacitor Banks

11.17 Functional Test Differential Protection for Capacitor Banks

11.17.1 Secondary Tests

Secondary tests can never replace the primary tests described in the following chapter 11.17.2 Primary Tests,
because they cannot include connection faults.
Secondary tests are used to check the following:

• Checking the setting values

• Proper reaction of the protection function

• Engineering (for example, routing the respective logic signals, display images with measured values,
logics in CFC, and much more)
If you want to perform secondary tests, observe the following instructions.

NOTE

i For tests with secondary test equipment, ensure that no other measurands are connected and the trip
commands to the circuit breakers are interrupted, otherwise, the circuit breakers could be activated.

Perform the tests with the current setting values for the device. If these values are not (yet) present, check
with the default values.

NOTE

i The measuring accuracy to be attained depends on the electrical data of the test sources. The accuracies
stated in the Technical Data can be expected only if the reference conditions stipulated in VDE 0435/
part 303 and IEC 60255 are ensured and precision instruments are used. The stated tolerances refer to the
default data for the protected objects. If the rated current of the protected object in relation to the rated
current of the current transformer deviates considerably from the rated current of the device, you must
assume higher response tolerances.

For differential protection, you can check each side separately. This corresponds to the simulation of a fault
supplied from one side. If a side has several measuring points, the measuring inputs not included in the test
carry no current. The pickup value is tested by increasing the test current slowly.

NOTE

i Tests of currents via quadruple device-rated current (or a maximum of 20 A) lead to an overload of the
input circuits and may be performed only briefly. You can find more information in chapter 12.31 Differen-
tial Protection for Capacitor Banks. Interrupt testing to allow cool-down!

The set pickup values refer to symmetrical 3-phase current in the case of 3-phase protected objects.
If you are testing parameters set during operation, you must ensure that the setting value for the differential
protection refers to the rated current of the protected object.
If you wish to check the characteristic curve, Siemens recommends using the standard testing programs of
digital test equipment. For the manual checking of points on the characteristic curve, feed in a through-
flowing current which corresponds to a current value on the stabilization axis. Then change the phase angle
of the test current on one side, so that the necessary differential current is achieved. Check a value with a
tolerance of 5 % above and below the point on the characteristic curve which is to be tested.
For capacitor banks, the actual pickup values for 2-phase testing also depend on the vector group of the
capacitor bank.
To obtain the actual pickup value, multiply the setting value by a vector-group factor kSG according to the
following formula:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1559


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.17 Functional Test Differential Protection for Capacitor Banks

[foscgrfa-170712-01.tif, 1, en_US]

The following table shows this factor kSG in dependence of the vector group and the fault type.

Table 11-2 Correction Factor kSG for the Vector Group (SG) and Fault Type

Fault Type Reference Winding Even SG Number Odd SG Number (1, 3,


(High Voltage) (0, 2, 4, 6, 8, 10) 5, 7, 9, 11)
3-phase 1 1 1
2-phase 1 1 √3/2 ≈ 0.866
1-phase with I0 elimination 3/2 = 1.5 3/2 = 1.5 √3 ≈ 1.73
1-phase without I0 elimination 1 1 3/(1+√3) ≈ 1.1

11.17.2 Primary Tests

Restricted primary testing is possible for capacitor-bank applications. A wiring fault in the connection to the
system could be a possible cause of the fault. With the system at a standstill, you can apply a test current of
approx. 10 % to 20 % of the rated current directly to the transformer terminals and connected transformer
with a primary testing device. Simulate a load (through-flowing current). The differential current must be 0
and the restraint current is the current which is fed in.
To rule out overfunction on initial switch-on, for example, due to the incorrect installation of a transformer,
Siemens recommends switching the differential protection to test mode. The protection function operates,
but does not issue a trip command. With the protection measurement values in the fault log, check the differ-
ential and the restraint current. The differential current must be 0 and the restraint current must correspond
to the actual capacitor current.
If the differential protection is functioning correctly, switch the protection function ON.

NOTE

i If the differential protection is disabled (for example, function in test mode), an overcurrent protection
must be active as short-circuit protection (without delay and set via the starting current).

1560 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

11.18 Commissioning Hints for Voltage Control

11.18.1 Secondary Tests

11.18.1.1 General
Secondary tests can never replace the primary tests described in the following (11.18.2 Primary Tests),
because you cannot exclude connection faults.
Secondary tests are used for the following purposes:

• Checking the setting values

• Checking the correct reaction of the protection function, limits, indications, blocking, and voltage control
functions

• Checking the engineering (for example, routing of the respective logic signals, display images with meas-
ured values and CFC logics)

• With parallel control check of the communication


Note the following information during the secondary tests:

NOTE

i For tests with secondary test equipment, make sure that no other measurands are connected and that the
trip commands to the circuit breakers are interrupted. Otherwise, the circuit breaker may be activated.

If the tap-changer position is not updated manually during the secondary test, you must deactivate the tap-
changer supervision. Otherwise, the voltage control is blocked after every switching procedure.

NOTE

i Once you have completed the secondary test, you must activate the tap-changer supervision again.

11.18.1.2 Checking the Transformer Tap Position

General
For this test, the transformer must be de-energized, that is, circuit breakers and disconnectors are switched
off/opened, protected against re-energizing and the maintenance grounding switch should be closed.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1561


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

During the functional test of the on-load tap changer, the most important setting parameters for the tap-
changer supervision such as Motor supervision time, Highest tap changer pos., and Maximum
output time must be checked and adjusted.

[scstuslt-100713-01.tif, 2, en_US]

Figure 11-14 Parameters of the Tap Changer

Tap-Position Display
You can route the current tap position as a position indication on a display page or into the operating indica-
tions. If no signal is present or the function is blocked, the device reports a position error. The display then
indicates an invalid tap position with --- (Figure 11-15). You can find information on which conditions lead to
an invalid tap position in the section Adjusting-Command Supervision, Page 1306.

[sc_osop_valid_position, 1, en_US]

Figure 11-15 Invalid Tap-Changer Position in the Device Display

Parameterize BCD Code


If the tap position of the tap changer is transmitted to the SIPROTEC 5 device via BCD code with prefix, then it
is sufficient to assign the binary inputs with the corresponding functions according to the routing. Corre-
sponding functions are for example:

• BCD1

• BCD2

• BCD4

1562 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

• BCD8

• BCD10

• BCD20

• BCD40

• BCDminus

• Sliding contact
You can find a short introduction into parameter setting and routing of the binary inputs for the tap position in
chapter 8.8.2 Application and Setting Notes.
Besides the tap-position display via BCD with prefix, the SIPROTEC 5 device offers the option to code the
tap position as follows:

• Binary

• 1-of-n

• BCD

• Table

• Gray Code

• IEC 61850 GOOSE indication (Type BSC)


Optionally, you can also use an mA signal or a resistance-coded tap-position display. An ANAI module must be
installed for the analog integration of the tap-position signal.

Checking the Tap Position


The active binary input is marked with a cross in the device menu under the entry Binary IO. Siemens recom-
mends driving through all positions of the tap changer completely, if possible, thereby testing the correct tap-
changer position indication once the parameterization of the tap position detection is finished and the tap-
position display is activated.
You can carry out the tap-position check from the on-site operation panel or from the DIGSI Online-Editor. If
you are using the DIGSI Online-Editor, set the switching authority of the device to Remote and the operating
mode of the voltage controller to Manual.

[sc_ibs_contr_func, 1, en_US]

Figure 11-16 DIGSI Online-Editor

SIPROTEC 5, 7SJ82/7SJ85, Manual 1563


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

Checking Sliding Contact


The device can monitor the runtime of the motor drive. This function is used to identify failures of the motor-
drive mechanism during the switching procedure and to initiate actions (for example, blocking) if required. If
you want to use the motor supervision time, you must route the motor run signal (most significant binary
input) and set the motor runtime.
The maximum motor runtime can be calculated by measuring – during commissioning – how long the tap
changer needs from the time point of the incremental command until completion of the tap changing. The tap
changer needs approx. 7 s to 10 s for one tap-position change. Select the runtime to be 2 s to 3 s longer than
the measured time. This takes into account a tolerance for the aging of the tap changer. If the tap changer has
a run-through setting, select the motor lead time based on the run-through time of the switching tap (+ toler-
ance time).
If the tap-changer position is not manually updated during the secondary test, you must deactivate the tap-
changer supervision. Otherwise, the voltage control is blocked after every switching procedure.

NOTE

i Once you have completed the secondary test, you must activate the tap-changer supervision again.

11.18.1.3 Check of the Voltage-Control Function


The measured control deviation D results from the following formula:

[fo_ibs_regelab, 1, en_US]

where:
Vact-prim Actual voltage, primary
Vtarget-prim 90V V.contr.2w → Target voltage primary
Vrated 90V V.contr.2w → General:Rated voltage

If you set the 3-phase measuring point voltage to VT connection = 3 ph-to-gnd volt. + VN, the
measured voltage primary Vact-prim results from the ratio of the voltage transformer parameters Rated
secondary voltage VCT-sec and Rated primary voltage VCT-prim .

[fo_ibs_prim_measur_volt, 1, en_US]

This results in the secondary voltage Vact-sec to be fed in depending on the control deviation D to be achieved
with the connection type VT connection = 3 ph-to-gnd volt. + VN / 3 ph-to-gnd voltages
being:

[fo_ibs_prim_measur_volt_2, 1, en_US]

This results in the secondary voltage Vact-sec to be fed in depending on the control deviation D to be achieved
with the connection type VT connection = 3 ph-to-ph voltages being:

[fo_ibs_prim_measur_volt_3, 1, en_US]

1564 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

Table 11-3 Example Settings for the System Data

Parameters Value
Power system → VT 3-phase:Rated primary voltage VCT-prim 15 kV
Power system → VT 3-phase:Rated secondary voltage VCT-sec 110 kV
Voltage cont. 2w → General:Rated voltage Vrated 10.5 kV
Target voltage 1 Vtarget 11 kV

This results in the secondary voltage Vact-sec with a phase-to-ground connection being:

[fo_ibs_prim_measur_volt_4, 1, en_US]

11.18.1.4 Further Tests

Control Deviation

• Check the control deviation D = 0 % at set point value infeed.

• Check the measured value of the control deviation D online in DIGSI or on the on-site operation panel of
the device.
Secondary infeed values for the example:
Voltage-transformer connection phase-to-ground: Vact-sec = 46.6 V
Voltage-transformer connection phase-to-phase: Vact-sec = 46.6 V ⋅√3 = 80.7 V

Command Outputs

• Check the output of the Lower adjusting command after the parameterizable time T1.
With a set bandwidth B of 1 %, this results in the secondary pickup value:
Voltage-transformer connection phase-to-ground: Vact-sec > 47.1 V
Voltage-transformer connection phase-to-phase: Vact-sec > 47.1 V ⋅√3 = 81.5 V

• Check the output of the Higher adjusting command after the parameterizable time T1.
With a set bandwidth B of 1 %, this results in the secondary pickup value:
Voltage-transformer connection phase-to-ground: Vact-sec < 46.1 V
Voltage-transformer connection phase-to-phase: Vact-sec < 46.1 V ⋅√3 = 79.8 V

• Check the output of the Lower adjusting command after the parameterized time Fast step down T
delay.
For the set parameter Fast step down limit = 6 %, the following secondary pickup values result:
Voltage-transformer connection phase-to-ground: Vact-sec > 49.3 V
Voltage-transformer connection phase-to-phase: Vact-sec > 49.3 V ⋅√3 = 85.3 V

• Check the output of the Higher adjusting command after the parameterized time Fast step up T
delay.
For the set parameter Fast step up limit = -6 %, the following secondary pickup values result:
Voltage-transformer connection phase-to-ground: Vact-sec < 49.3 V
Voltage-transformer connection phase-to-phase: Vact-sec < 49.3 V ⋅√3 = 85.3 V

Blockings

• Check the undervoltage blocking V< Blocking.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1565


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

For the set parameter V< Blocking = 8 kV, the following secondary pickup values result:
Voltage-transformer connection phase-to-ground: Vact-sec < 58.7 V
Voltage-transformer connection phase-to-phase: Vact-sec < 58.7 V ⋅√3 = 101.6 V

• Check the overcurrent blocking.

NOTE

i The overcurrent blocking works with the maximum current of all phases, for this reason, check the phases
A, B, and C separately.

Example

Parameters Value
Power system → CT 3-phase:Rated primary current ICT-prim 7500 A
Power system → CT 3-phase:Rated secondary current ICT-sec 1A
Voltage cont. 2w → General:Rated current Irated 5500 A

[fo_ibs_overcur_block, 1, en_US]

If you set the parameter I> Threshold to 150 %, this results in an infeed current secondary of Iact-sec > 1.1 A
for the example.

Line Compensation

• Check the Z Compensation.


The parameter Target voltage rising represents the voltage drop across the line as a % at rated load. In
case of a voltage drop primary of 504 V across the line at rated current, according to the setting notes in
8.9.4.4 Line Compensation, this results in a setting value of 4.8 %.
The secondary current to be fed in at a load current for the 100 % load case results in:

[fo_ibs_load_current, 1, en_US]

where:
ICT-prim Power system → CT 3-phase:Rated primary current
ICT-sec Power system → CT 3-phase:Rated secondary current
Irated Voltage cont. 2w → General:Rated current

The secondary voltage to be fed in for the 100 % load case with a control deviation D [%] to be tested for the
voltage-transformer connection phase-to-ground results in:

[fo_ibs_sec_volt, 1, en_US]

For the voltage-transformer connection phase-to-phase, the reference must be multiplied with the factor √3.
For a control deviation of D = 0 % to be tested and a setting value Target voltage rising of 4.8 %, in
the example, for voltage-transformer connection phase-to-ground, this results in a secondary infeed voltage
of:

1566 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

[fo_ibs_sec_volt_values, 1, en_US]

The infeed current for the 100 % load case is Iact-sec = 0.733 A.

• Check the XandR compensation.


The control deviation results from the difference of the measured voltage Vact-prim and a calculated compen-
sated target voltage Vtarget-comp.

[fo_ibs_target_comp, 1, en_US]

The calculated compensated target voltage is calculated from a numerically determined voltage Vload at the
end of the line:
Vtarget-comp = (Vact-prim - Vload) + Vtarget
This numerically determined voltage Vload at the end of the line is determined form the parameters X line, R
line, the flowing current Iact-prim, and the rotor angle φ.
The measured voltage at the voltage controller results as follows from the dependency to the numerically
determined voltage Vload and the flowing current Iact-prim:

[fo_ibs_volt_prim_calcul, 1, en_US]

with IΔVI = Iact-prim ⋅ (cosφ ⋅ R + sinφ ⋅ X)


If you insert the target voltage Vtarget in the formula instead of Vload, for the resulting control deviation this
results in D = 0 %.

• Check whether the operational measured value ΔV has the value 0 via the on-site operation panel or in
DIGSI.
If you set the previous example values and if you set the values 0.10 Ω for parameter R line and 0.15 Ω
for the parameter X line, then this results in the following secondary infeed values at a rated load current of
5500 A and a cosφ = 0.707:
With a phase-to-ground connection

[fo_ibs_input_values_LE, 1, en_US]

with Iact-sec = 734 mA and φload = -45°


With a phase-to-phase connection

[fo_ibs_input_values_LL, 1, en_US]

with Iact-sec = 734 mA and φload = -75°

SIPROTEC 5, 7SJ82/7SJ85, Manual 1567


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

11.18.1.5 Voltage-Control Function for Parallel Transformers

Checking the Settings of the Voltage Controller within a Group and of the GOOSE Communication

• For the functional test of Voltage cont.2w, route the indications Health, Remote parallel mode,
Parallel-operation error, and Auto Blocking to an LED.
• Check this routing.

• Route the GOOSE input indication Cmd. with feedback under


Voltage reg.2w → Parallel control → ParallelProxy on one display page.
The tap positions received from the other voltage controllers are shown under:
Voltage reg.2w → Parallel control → ParallelProxy

• Switch all affected voltage controllers to the parallel mode.

[sc_ibs_tap_changer_pos, 1, en_US]

Figure 11-17 Example of a User-Defined Display Page

If the indication Parallel-operation error is reported, the following causes are possible:

• Communication error

• Parallel-mode error - inconsistent setting Parallel mode

• Parameter Parallel-transfomer id inconsistent or identical for 2 voltage controllers

• Master error (number of Masters in the group ≠ 1), only with the Master-Follower method

• Measured value invalid (for example, with line compensation no current transformer assigned in the
remote voltage controller)

• Mode error (inconsistent test mode of the voltage controllers)


You can find the reason for the indication in the operational log of the indication Cause of par.op.
error.

NOTE

i If the indication Auto Blocking is reported and if the indication Parallel Auto Blocking is
reported in the ParallelProxy, the possible cause is that the remote voltage controller is blocked or the
Follower device is in the Manual in case of the Master-Follower method.

Checking Remote Measured Values


You can check the measured values received via GOOSE in the DIGSI-Online-Editor or on the on-site operation
panel of the device under the following path:
Main menu → Measured Values → Voltage cont.2w → Function values. → Parallel operat. → Parallel-
Proxy

1568 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

[sc_ibs_func_value, 1, en_US]

Figure 11-18 Functional Measured Values in DIGSI

Checking the Voltage-Control Function for Parallel Transformers


First you must check the manual update of the transformer taps in the operating mode Manual. Proceed as
follows:

• Switch the Master device to the operating mode Manual.

• Switch the Follower devices to the operating mode Auto.

• On the Master device, start a Higher adjusting command for the tap changer.
The voltage controllers in Follower mode of the same group must also change to a higher tap once the new
tap-changer position is reached.

• Check the tap position of the Follower devices on the device display of the on-site operation panel.

• Repeat the test with a Lower adjusting command.

Checking the Voltage-Control Function of the Master-Follower Method

• Carry out the test items of the voltage-controller function in the chapter 11.18.1.1 General in the Master
device.

NOTE

i During this test, note that the measured control voltage Vact.m is averaged from the measured voltages
of all parallel voltage controllers and therefore the secondary voltage must be fed in for all voltage control-
lers.

Checking the Line Compensation


To check the Z Compensation (LDC-Z), proceed as follows:
The parameter Target voltage rising represents the voltage drop across the line as a % at rated load.
Since the rated load current in the Master and Follower devices can be different, you must calculate the
parameter Target voltage rising separately for each voltage controller.

• First, based on the following ratio, determine the percentage of the primary load current of the line
compared with the rated current of a transformer k (k = 1, 2, …, 8).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1569


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

[fo_ibs_load_cur_perc, 1, en_US]

[fo_ibs_prim_load_voltage, 1, en_US]

The following calculation values result from the Example, Page 1364, which is shown in the setting notes in
the chapter Z Compensation.
Parameters Transformer T1 Transformer T2
Power system → 11 kV 11 kV
VT 3-phase:Rated primary voltage VCT-prim
Power system → 110 V 100 V
VT 3-phase:Rated secondary voltage VCT-sec
Power system → 1500 A 3000 A
CT 3-phase:Rated primary current ICT-prim
Power system → 1A 5A
CT 3-phase:Rated secondary current ICT-sec
Voltage cont. 2w → 10.5 kV 10.5 kV
General:Rated voltage Vrated
Voltage cont. 2w → 26 MVA 52 MVA
General:Rated app. power transf. Srated
Voltage cont. 2w → 1430 A 2859 A
General:Rated current Irated
Target voltage Vtarget 11 kV 11 kV
Target voltage rising 4.8% 9.6%

• Based on the following table check the input currents and voltages for each voltage controller:

Transformer T1 Transformer T2 Transformer T1 Master


Independent Independent Transformer T2 Follower
T2 = off T1 = off
(I2 = 0) (I1 = 0)
Input values, secondary
Isec 0.953 A 2.383 A 0.635 A 3.1833 A
Phase-to-ground Vsec 33.198 V 60.359 V 34.641 V 62.984 V
Phase-to-phase Vsec 57.501 V 104.54 V 60 V 109.1 V
Functional measured values
Vact 11.5 kV 11.5 kV 12.0 kV 12.0 kV
Iload 1430 A 1430 A 953 A 1910 A
Iload∑ - - 2860 A 2860 A
ΔVactual 0% 0% 0% 0%
Vtarget 11.5 kV 11.5 kV 12.0 kV 12.0 kV

You can find more information in chapter 8.9.4.4 Line Compensation.

1570 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

Checking the Voltage-Control Function with the Method of Minimizing the Circulating Reactive Current
The following secondary test is used to check the setting values. The current is fed into one voltage controller
respectively and this current has a phase angle of -90° to the voltage.

• Check also the functional measured values for the circulating reactive current for the voltage controllers
where no current is being fed in.
The following simplification results:
The current on one voltage controller is the total load current (Iload= Ik) and therefore the measured circulating
reactive current depends on the primary load current on a transformer:

[fo_ibs_ccm_trafo, 1, en_US]

where:

Total susceptance value

Xk Transformer reactance on transformer k

The control deviation DCRCk resulting from the circulating reactive current is determined in the voltage
controller numerically according to the following formula:

[fo_regelabwdcc, 1, en_US]

The primary current to be fed in at a desired control deviation DCRCk results as follows:

[fo_ibs_regelabwd_ccm, 1, en_US]

The current to be fed in is calculated from the following ratio, with the phase angle to voltage being ∠Iact-sec =
-90°

[fo_ibs_load_cur_prim, 1, en_US]

Example

Table 11-4 Example Values

Parameters Transformer T1 Transformer T2


Power system → 22 kV 11 kV
VT 3-phase:Rated primary voltage VCT-prim
Power system → 110 V 100 V
VT 3-phase:Rated secondary voltage VCT-sec

SIPROTEC 5, 7SJ82/7SJ85, Manual 1571


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

Parameters Transformer T1 Transformer T2


Power system → 1500 A 3000 A
CT 3-phase:Rated primary current ICT-prim
Power system → 1A 5A
CT 3-phase:Rated secondary current ICT-sec
Voltage cont. 2w → 10.5 kV 10.5 kV
General:Rated voltage Vrated
Voltage cont. 2w → 26 MVA 52 MVA
General:Rated app. power transf. Srated
Voltage cont. 2w → 1430 A 2859 A
General:Rated current Irated
Target voltage Vtarget 11 kV 11 kV

For the transformer T1, with a desired control deviation of 1 % and the parameter Reactive I control
factor = 1, the primary current is as follows:

[fo_ibs_regelabwd_ccm_values, 1, en_US]

• Check the function values in all voltage controllers according to the following table:

Secondary Test Secondary Test


Infeed Transformer T1 Infeed Transformer T2
for D = 1 % for D = 1 %
Input values, secon- T1 T2 T1 T2
dary
Isec 0.09622 A 0A 0A 0.4041 A
-90° ph-gnd -90° ph-gnd
-150° ph-ph -150° ph-ph
Phase-to-ground Vsec 31.754 V 57.735 V 31.754 V 57.735 V
Phase-to-phase Vsec 55 V 100 V 55 V 100 V
Functional measured values
Vact 11.0 kV 11.0 kV 11.0 kV 11.0 kV
Iload 144 A 0A 0A 243 A
Phase angle 90° - - 0°
Iload∑ 144 A 144 A 243 A 243 A
ICRC 90 A -90 A -91 A 91 A
ΔVact 1% -1 % -1 % 1%
ΔVact u 0% 0% 0% 0%
ΔVact k 1% -1 % -1 % 1%

Checking the Pickup Value of the Circulating Reactive Current Blocking


If the value of the circulating reactive current exceeds the threshold value Circul. current threshold
for a longer time than the set time delay Circul. current time delay, the indication Circul.
current blocking is issued and the voltage control is blocked.

1572 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

[fo_ibs_ccm_cur_thresh, 1, en_US]

Thus. the secondary infeed current results as follows with a phase angle to the voltage ∠Iact-sec = -90°:

[fo_ibs_ccm_cur_inp, 1, en_US]

The calculation from the values of the Table 11-4 with a pickup value of 50 % results in the following for the
transformer T1:

[fo_ibs_ccm_cur_inp_value, 1, en_US]

With Isec > 0.76 mA and ∠act-sec = -90°

11.18.2 Primary Tests

If secondary test equipment is connected to the device, remove it or switch the test switch to the operating
position.

• To be able to control the on-load tap changer manually, switch the voltage controller to the Manual
operating mode.

NOTE

i Be aware that a trip occurs in case of incorrect connections.

Checking the Polarity of the Voltage Transformer and Current Transformer


The correct connection of the current and voltage transformers is tested using the load current via the feeder
to be controlled. For this, you must switch on the line or the protected object. A load current of at least 0.1 ⋅
Irated must flow through the line or the protected object. The load current should be ohmic to ohmic inductive.
The direction of the load current must be known. If there is a doubt, open meshed or ring systems.
The line or the protected object remains switched on for the duration of the measurements. You can derive
the direction directly from the operational measured values.

• Make sure in DIGSI 5 or on the device with the following path that the power measured values corre-
spond to the power direction:
Main menu → Measured Values → Voltage cont.2w → Power values.
If active power flows in the line or the protected object, the power direction for P must be positive. If inductive
reactive power flows in the line or the protected object, the power direction for Q must be positive. If the
power measured values have a different sign than expected, then the power flow is opposite the current-
direction definition. This can be the case, for example, at the opposite end of the low-voltage side of a trans-
former. The current-transformer neutral point then points in the direction of the protected object (for
example, transformer). In this case, you must connect the Measuring point I-3ph in an inverted way to the
function group Voltage controller in the function-group assignment (see chapter Interface Between Function
Group and Measuring Point, Page 50).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1573


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

Checking the Tap Direction and the Set Bandwidth

• Set the bandwidth according to the formula in chapter 8.9.4.3 Voltage Controller.
The tap direction and the set bandwidth are checked with the following functional test.
With the correct tap direction, there will be a voltage increase when changing to a higher tap or a voltage
reduction when changing to a lower tap.

• First switch the voltage controller to the Manual operating mode.

• Switch the tap changer to a higher or lower tap on the on-site operation panel or in the DIGSI Online-
Editor until the voltage set point value is reached.

• Keep switching the tap changer higher until the bandwidth is exceeded.
The difference in the control deviation ∣ΔV(n+1) - ΔV(n)∣ at a tap setting must be smaller than double the
bandwidth.

• Switch the voltage controller to the Auto operating mode.


After the parameterized time T1, the voltage controller should change to lower taps until the control
deviation drops below the bandwidth.

• Switch the voltage controller back to the Manual operating mode.


Keep switching the tap changer lower until the value drops below the bandwidth. The difference in the
control deviation ∣ΔV(n-1) - ΔV(n)∣ at a tap setting must be smaller than double the bandwidth.

• Switch the voltage controller to the Auto operating mode.


After the parameterized time T1, the voltage controller must change to higher taps until the control devi-
ation drops below the bandwidth.

Checking the Circulating Reactive Current Sensitivity in Parallel Operation


The prerequisites for correct function of the parallel operation are the commissioning of the voltage controller
in single operation and that the secondary tests have been completed.
For the functional test, the voltage controllers must be in the same parallel group according to the topology
and the Manual mode as well as the Method of minimizing the circulating reactive current must be acti-
vated. In most cases, the default setting of the parameter Reactive I control factor is sufficient, since
an optimal adjustment to the configuration takes place because of the entry of the parameter
General:Imp(Z): short circuit imp. of the transformer.
If the control deviation is still larger than double the bandwidth due to the circulating reactive current at a tap-
position difference of 1, alternating tap changing may take place. In this case, reduce the parameter Reac-
tive I control factor.

NOTE

i Carry out the following tests only at low load current.

• With all voltage controllers, approach one tap position which corresponds to the same no-load voltage to
keep the circulating reactive current as low as possible and to reach the voltage set point value.

• Set one of the tap changers to a higher or lower tap. This results in a circulating reactive current.
– If the difference of the circulating reactive current control deviation ∣ΔVactK(n+1) - ΔVactK(n)∣ is
smaller than the set bandwidth, increase the parameter Reactive I control factor.
– If the difference of the circulating reactive current control deviation ∣ΔVactK(n+1) - ΔVactK(n)∣ is larger
than double the bandwidth, reduce the parameter Reactive I control factor.

• Repeat this test for all voltage controllers.

1574 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

• With all voltage controllers, approach a minimum tap position where the same no-load voltages result
everywhere, and repeat the following tests.
– If the difference of the circulating reactive current control deviation ∣ΔVactK(n+1) - ΔVactK(n)∣ is
smaller than the set bandwidth, increase the parameter Reactive I control factor.
– If the difference of the circulating reactive current control deviation∣ΔVactK(n+1) - ΔVactK(n)∣ is larger
than double the bandwidth, reduce the parameter Reactive I control factor.

• Repeat this test for all voltage controllers.

• With all voltage controllers, approach a maximum tap position where the same no-load voltages result
everywhere, and repeat the following tests.
– If the difference of the circulating reactive current control deviation∣ΔVactK(n+1) - ΔVactK(n)∣ is
smaller than the set bandwidth, increase the parameter Reactive I control factor.
– If the difference of the circulating reactive current control deviation∣ΔVactK(n+1) - ΔVactK(n)∣ is larger
than double the bandwidth, reduce the parameter Reactive I control factor.

• Repeat this test for all voltage controllers.


Since the transformer reactance can change slightly with the tap position, the points with maximum and
minimum tap position mentioned in the preceding section are used to check the stable control.

Checking the Tap Direction and the Set Bandwidth in Parallel Operation with the Master-Follower Method
The following prerequisites apply for the following test:

• All transformers are switched on.

• All transformers feed to the same busbar.

• All voltage controllers are in parallel mode.

• The Master device is in the Manual operating mode.

• The Follower devices are in the Auto operating mode.

NOTE

i Carry out these tests only at low load current.

The test sequence corresponds to the sequence under Checking the Tap Direction and the Set Bandwidth,
Page 1574.

• In addition, test the manually updated tap position of the Follower devices.
If the current is measured on the involved voltage controllers, the line compensation or the circulating reactive
current blocking is activated, you must check the currents.

NOTE

i If a circulating reactive current forms despite the same tap position, there is an error in the tap-position
assignment.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1575


C53000-G5040-C017-A, Edition 06.2019
Functional Tests
11.18 Commissioning Hints for Voltage Control

Performance of Current Tests

! DANGER
Live system parts! Capacitive coupled voltages on dead parts!
Non-observance of the safety notes will result in death, severe injury, or considerable material
damage.
² Primary measures may be performed only on dead and grounded system parts.

NOTE

i These tests cannot replace a visual check of the correct current-transformer connections. Therefore,
completed checks of the system connections are a prerequisite.

The SIPROTEC 5 device provides operational measured values. With these operational measured values, a fast
commissioning without external instrumentation is possible.
The following procedure is intended for 3-phase protected objects, that is, for measuring point 1 against
measuring point 2. For transformers, it is assumed that side 1 is the upper-voltage side of the transformer. The
other possible current circuits are tested in an analog way.

• Read out the differential and restraint currents under:


Main menu → Measured values.

• Check the direction information of the (_:302) Ground fault indication in the fault log or in the
ground-fault log. The direction information forward must be logged for the (_:302) Ground fault
indication.
If backward is determined as the direction, there is an inversion in the neutral path either for the current
connections or for the voltage connections. If unknown is displayed, the ground current is probably too
low.

• Switch off the line and ground it.


This completes the test.

1576 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
12 Technical Data

12.1 General Device Data 1580


12.2 Protection Interface and Protection Topology 1591
12.3 Date and Time Synchronization 1593
12.4 Analog-Units Function Group 1594
12.5 Overcurrent Protection, Phases 1595
12.6 Voltage-Dependent Overcurrent Protection, Phases 1607
12.7 Overcurrent Protection, Ground 1610
12.8 Directional Overcurrent Protection, Phases 1620
12.9 Directional Overcurrent Protection, Ground 1626
12.10 Inrush-Current Detection 1636
12.11 Arc Protection 1637
12.12 Instantaneous High-Current Tripping 1638
12.13 Instantaneous Tripping at Switch onto Fault 1639
12.14 Overcurrent Protection, 1-Phase 1640
12.15 Overcurrent Protection, 1-Phase (Fast Stage) 1647
12.16 Positive-Sequence Overcurrent Protection 1648
12.17 Non-Directional Intermittent Ground-Fault Protection 1651
12.18 Directional Intermittent Ground-Fault Protection 1653
12.19 Sensitive Ground-Fault Detection 1655
12.20 Undercurrent Protection 1666
12.21 Negative-Sequence Protection 1668
12.22 Directional Negative-Sequence Protection with Definite-Time Delay 1672
12.23 Thermal Overload Protection, 3-Phase – Advanced 1674
12.24 Thermal Overload Protection, User-Defined Characteristic Curve 1678
12.25 Thermal Overload Protection, 1-Phase 1679
12.26 Unbalanced-Load Protection 1682
12.27 Overcurrent Protection for Capacitor Banks 1684
12.28 Current-Unbalance Protection for Capacitors, 3-Phase 1696
12.29 Current-Unbalance Protection for Capacitors, 1-Phase 1698
12.30 Voltage-Differential Protection for Capacitors 1700
12.31 Differential Protection for Capacitor Banks 1701
12.32 Overvoltage Protection with 3-Phase Voltage 1704
12.33 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage 1706
12.34 Overvoltage Protection with Positive-Sequence Voltage 1708

SIPROTEC 5, 7SJ82/7SJ85, Manual 1577


C53000-G5040-C017-A, Edition 06.2019
Technical Data

12.35 Overvoltage Protection with Negative-Sequence Voltage 1709


12.36 Overvoltage Protection with Any Voltage 1710
12.37 Peak Overvoltage Protection for Capacitors 1712
12.38 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage 1714
12.39 Undervoltage Protection with 3-Phase Voltage 1715
12.40 Undervoltage Protection with Positive-Sequence Voltage 1718
12.41 Undervoltage Protection with Any Voltage 1720
12.42 Overfrequency Protection 1722
12.43 Underfrequency Protection 1723
12.44 Underfrequency Load Shedding 1724
12.45 Rate of Frequency Change Protection 1726
12.46 Vector-Jump Protection 1728
12.47 Power Protection (P,Q), 3-Phase 1729
12.48 Reverse-Power Protection 1730
12.49 Overexcitation Protection 1731
12.50 Undervoltage-Controlled Reactive-Power Protection 1733
12.51 Circuit-Breaker Failure Protection 1735
12.52 Circuit-Breaker Restrike Protection 1737
12.53 Restricted Ground-Fault Protection 1738
12.54 External Trip Initiation 1740
12.55 Automatic Reclosing 1741
12.56 Fault Locator 1742
12.57 Fault Locator Plus 1743
12.58 Temperature Supervision 1744
12.59 Current-Jump Detection 1745
12.60 Voltage-Jump Detection 1746
12.61 Synchronization Function 1747
12.62 Voltage Controller 1750
12.63 Current-Balance Supervision 1754
12.64 Voltage-Balance Supervision 1755
12.65 Current-Sum Supervision 1756
12.66 Voltage-Sum Supervision 1757
12.67 Current Phase-Rotation Supervision 1758
12.68 Voltage Phase-Rotation Supervision 1759
12.69 Voltage-Comparison Supervision 1760
12.70 Trip-Circuit Supervision 1761
12.71 Closing-Circuit Supervision 1762
12.72 Analog Channel Supervision via Fast Current Sum 1763
12.73 Measuring-Voltage Failure Detection 1764
12.74 Voltage-Transformer Circuit Breaker 1766
12.75 Operational Measured Values and Statistical Values 1767
12.76 Energy Values 1771

1578 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data

12.77 Phasor Measurement Unit 1772


12.78 Circuit-Breaker Wear Monitoring 1773
12.79 CFC 1774
12.80 Point-on-Wave Switching 1778

SIPROTEC 5, 7SJ82/7SJ85, Manual 1579


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

12.1 General Device Data

12.1.1 Analog Inputs

Current Inputs

All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Protection-class current trans- Rated current Irated Measuring range of Measuring range of the
formers the modular devices non-modular devices
5A 0 A to 500 A 0 A to 250 A
1A 0 A to 100 A 0 A to 50 A
Instrument transformers 5A 0 A to 8 A 0 A to 8 A
1A 0 A to 1.6 A 0 A to 1.6 A
Burden for rated current Approx. 0.1 VA
Thermal rating 20 A continuously
(protection and instrument trans- 25 A for 3 min
formers) 30 A for 2 min
150 A for 10 s
500 A for 1 s
Dynamic load-carrying capacity 1250 A one half wave

Voltage Input

All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Input and output modules IO102, IO202, IO208, IO211, IO215
IO214
Measuring range 0 V to 200 V 0 V to 7.07 V
Burden < 0.1 VA < 0.01 VA
Thermal rating 230 V continuously 20 V continuously

Measuring-Transducer Inputs (via Module ANAI-CA-4EL)

Insulation class SELV (Safety Extra Low Voltage) (according to IEC 60255-27)
Connector type 8-pin terminal spring
Differential current input channels 4
Measuring range DC -25.6 mA to +25.6 mA
Fault < 0.5 % of the measuring range
Input impedance 140 Ω
Conversion principle Delta-sigma (16 bit)
Permissible potential difference DC 20 V
between channels
Galvanic separation from ground/ DC 700 V
housing
Permissible overload DC 100 mA continuously
Measured-value repetition 200 ms

1580 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

Inputs for Optical Sensors for Arc Protection (via Module ARC-CD-3FO)

Connector type AVAGO AFBR-4526Z


Number of transceivers 3
Fiber type Polymer Optical Fiber (POF) 1 mm
Receiver
Maximum -10 dBm ± 2 dBm
Minimum -40 dBm ± 2 dBm
Spectrum 400 nm to 1100 nm
Attenuation In the case of plastic optical fibers, you can expect a path attenuation of
0.2 dB/m. Additional attenuation comes from the plug and sensor head.
Optical budget43 Minimal 25 dB
Analog sampling rate 16 kHz
ADC type 10-bit successive approximation
Transmitter
Type LED
Wavelength λ = 650 nm
Transmitter power Minimum 0 dBm
Maximum 2 dBm
Numerical aperture 0.5 44
Signal rate connection test 1 pulse per second
Pulse duration connection test 11 μs

High-Speed Measuring-Transducer Inputs, Voltage/Current (via IO210, IO212)

NOTE

i Current and voltage must not be connected at the same time to one measuring-transducer input. Instead,
only connect either current or voltage. For EMC reasons, do not connect a line to an unused input (current
or voltage).
Use shielded cables.

Table 12-1 High-Speed Measuring-Transducer Inputs, Voltage

Differential voltage input channels IO210: 445


IO212: 846
Measuring range DC -10 V to +10 V
Fault < 0.5 % of the measuring range
Input impedance 48 kΩ
Max. permissible voltage with 300 V
respect to ground on the meas-
uring inputs
Permissible overload DC 20 V continuously
DC 60 V continuously (IO210 MT3 terminal point C9)

43 All values in combination with sensors approved by Siemens.


44 Numerical aperture (NA = sin θ (launch angle))
45 The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
46 The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1581


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

Table 12-2 High-Speed Measuring-Transducer Inputs, Current

Differential current input channels IO210: 447


IO212: 848
Measuring range DC -20 mA to +20 mA
Fault < 0.5 % of the measuring range
Input impedance, current 12 Ω
Permissible potential difference DC 3.5 kV
between channels
Galvanic separation with respect to DC 3.5 kV
ground/housing
Permissible current overload DC 100 mA continuously

Table 12-3 Common Data for the Fast Measuring-Transducer Inputs, Voltage/Current

Conversion principle Delta-sigma (16 bit)


Insulation test voltage between the DC 3.5 kV
channels
Insulation test voltage with respect DC 3.5 kV
to ground/housing
Measured-value repetition 62.5 μs
Insulation class IO210 ELV (Extra Low Voltage) (as per IEC 60255-27)
Insulation class IO212 SELV (as per IEC 60255-27)

Temperature Inputs

Settings Value Note


Insulation class PELV (Protective Extra Low Voltage) –
(acc. to IEC 60255-27)
Measurement mode • Pt 100 Ω –
• Ni 100 Ω
• Ni 120 Ω
3-wire connection, shielded cables
Connector type 16-pin, 17-pin terminal spring –
Temperature measuring range -65 °C to +710 °C For PT100
-50 °C to +250 °C For NI100
-50 °C to +250 °C For NI120

47 The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
48 The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.

1582 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

12.1.2 Supply Voltage

Integrated Power Supply


For modular devices, the following modules contain a power supply:
PS201 – Power supply of the base module and of the 1st device row
PS203 – Power supply of the 2nd device row
CB202 – Plug-in module assembly with integrated power supply, for example, to accommodate communica-
tion modules
Permissible voltage DC 19 V to DC 60 V DC 48 V to DC 300 V
ranges AC 80 V to AC 265 V, 50 Hz/60 Hz
(PS201, PS203, CB202)
Auxiliary rated voltage VH DC 24 V/DC 48 V DC 60 V/DC 110 V/DC 125 V/DC 220 V/
(PS201, PS203, CB202) DC 250 V or
AC 100 V/AC 115 V/AC 230 V, 50 Hz/60 Hz
Permissible voltage DC 19 V to DC 60 V DC 48 V to 150 V DC 88 V to DC 300 V
ranges (PS101) AC 80 V to AC 265 V,
Only for non-modular 50 Hz/60 Hz
devices
Auxiliary rated voltage VH DC 24 V/DC 48 V DC 60 V/DC 110 V/ DC 110 V/ DC 125 V/
(PS101) DC 125 V DC 220 V/DC 250 V
Only for non-modular or
devices AC 100 V/AC 115 V/
AC 230 V, 50 Hz/60 Hz
Superimposed alternating ≤ 15 % of the DC auxiliary rated voltage (applies only to direct voltage)
voltage, peak-to-peak,
IEC 60255-11,
IEC 61000-4-17
Inrush current ≤ 18 A
Recommended external Miniature circuit breaker 6 A, characteristic C according to IEC 60898
protection
Internal fuse
– DC 24 V to DC 48 V DC 60 V to DC 125 V DC 24 V to DC 48 V
AC 100 V to AC 230 V
PS101 4 A inert, AC 250 V, 2 A time-lag, AC 250 V, DC 300 V, UL recognized
Only for non-modular DC 150 V, SIBA type 179200 or Schurter type SPT 5x20
devices UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
PS201, PS203, CB202 2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
Power consumption (life relay active)
– DC AC 230 V/50 Hz AC 115 V/50 Hz
1/3 base module, non- 7W 16 VA 12.5 VA
modular
Without plug-in modules
1/3 base module, modular 13 W 33 VA 24 VA
Without plug-in modules
1/6 expansion module 3W 6 VA 6 VA
1/6 plug-in module 3.5 W 14 VA 7 VA
assembly without plug-in
modules (modules CB202)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1583


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

Integrated Power Supply


Plug-in module for base <5W < 6 VA < 6 VA
module or plug-in module
assembly (for example,
communication module)
Stored-energy time for auxiliary voltage outage or For V ≥ DC 24 V ≥ 50 ms
short circuit, modular devices For V ≥ DC 110 V ≥ 50 ms
IEC 61000-4-11 For V ≥ AC 115 V ≥ 50 ms
IEC 61000-4-29
Stored-energy time for auxiliary voltage outage or For V ≥ DC 24 V ≥ 20 ms
short circuit, non-modular devices For V ≥ DC 60 V ≥ 50 ms
IEC 61000-4-11 For V ≥ AC 115 V ≥ 200 ms
IEC 61000-4-29

12.1.3 Binary Inputs

Standard Binary Input

Rated voltage range DC 24 V to 250 V


The binary inputs of SIPROTEC 5 are bipolar, with the exception of the
binary inputs on the modules IO230, IO231, and IO233.
Current consumption, excited Approx. DC 0.6 mA to 2.5 mA (independent of the control voltage)
Power consumption, max. 0.6 W
Pickup time Approx. 3 ms
Dropout time49 Capacitive load (supply-line capaci- Dropout time
tance)
< 5 nF < 4 ms
< 10 nF < 6 ms
< 50 nF < 10 ms
< 220 nF < 35 ms
Control voltage for all modules Adapt the binary-input threshold to be set in the device to the control
with binary inputs, except voltage.
module IO233 Range 1 for 24 V, 48 V, and 60 V Vlow ≤ DC 10 V
Control voltage Vhigh ≥ DC 19 V
Range 2 for 110 V and 125 V Vlow ≤ DC 44 V
Control voltage Vhigh ≥ DC 88 V
Range 3 for 220 V and 250 V Vlow ≤ DC 88 V
Control voltage Vhigh ≥ DC 176 V
Control voltage for binary inputs of Range for 125 V Vlow ≤ DC 85 V
the IO233 module Control voltage Vhigh ≥ DC 105 V
Maximum permitted voltage DC 300 V
The binary inputs contain interference suppression capacitors. To ensure EMC immunity, use the terminals
shown in the terminal diagrams/connection diagrams to connect the binary inputs to the common potential.

49 For time-critical applications with low-active signals, consider the specified dropout times. If necessary, provide for active discharge
of the binary input (for example, a resistor in parallel to the binary input or using a change-over contact).

1584 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

Special Binary Input with Maximized Robustness against Electrical Disturbances and Failures (IO216)

Rated voltage range DC 24 V to 250 V


The special binary inputs of the SIPROTEC 5 with maximized robustness
against electrical disturbances and failures are bipolar and available only
on the module IO216.
Rejection pulse charge > 200 µC
Current consumption, excited Approx. DC 0.6 mA to 2.5 mA (independent of the control voltage)
Power consumption, max. 1.5 W at DC 242 V
Pickup time Approx. 3 ms
Dropout time50 Capacitive load (supply-line capaci- Dropout time
tance)
< 5 nF < 4 ms
< 10 nF < 6 ms
< 50 nF < 10 ms
< 220 nF < 35 ms
Control voltage for the module Range for 220 V and 250 V control voltage
IO216 Threshold pickup 158 V to 170 V
Threshold dropout 132 V to 154 V
Maximum permitted voltage DC 300 V
The binary inputs contain interference suppression capacitors. To ensure EMC immunity, use the terminals
shown in the terminal diagrams/connection diagrams to connect the binary inputs to the common potential.

12.1.4 Relay Outputs

Standard Relay (Type S)

Making capacity Max. 1000 W (L/R = 40 ms)


Max. 3600 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Breaking capacity Max. 30 W (L/R = 40 ms)
Max. 360 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
AC and DC contact voltage 250 V
Permissible current per contact (continuous) 5A
Permissible current per contact (switching on and 30 A for 1 s (make contact)
holding)
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to 5A
common potential
Switching time OOT (Output Operating Time) Make time: typical: 8 ms; maximum: 10 ms
Additional delay of the output medium used Break time: typical: 2 ms; maximum: 5 ms
Max. rated data of the output contacts in accordance DC 24 V, 5 A, General Purpose
with UL certification DC 48 V, 0.8 A, General Purpose
DC 240 V, 0.1 A, General Purpose
AC 240 V, 5 A, General Purpose
AC 120 V, 1/6 hp
AC 250 V, 1/2 hp
B300
R300

50 For time-critical applications with low-active signals, consider the specified dropout times. If necessary, provide for active discharge
of the binary input (for example, a resistor in parallel to the binary input or using a change-over contact).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1585


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

Interference suppression capacitors across the 4.7 nF, ± 20 %, AC 250 V


contacts

Fast Relay (Type F)

Making capacity Max. 1000 W (L/R = 40 ms)


Max. 3600 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Breaking capacity Max. 30 W (L/R = 40 ms)
Max. 360 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
AC and DC contact voltage 250 V
Permissible current per contact (continuous) 5A
Permissible current per contact (switching on and 30 A for 1 s (make contact)
holding)
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to 5A
common potential
Switching time OOT (Output Operating Time) Make time: typical: 4 ms; maximum: 5 ms
Additional delay of the output medium used Break time: typical: 2 ms; maximum: 5 ms
Rated data of the output contacts in accordance with DC 24 V, 5 A, General Purpose
UL certification DC 48 V, 0.8 A, General Purpose
DC 240 V, 0.1 A, General Purpose
AC 120 V, 5 A, General Purpose
AC 250 V, 5 A, General Purpose
AC 250 V, 0.5 hp
B300
R300
Interference suppression capacitors across the 4.7 nF, ± 20 %, AC 250 V
contacts
Supervision 2-channel activation with cyclic testing (only for make
contact)

High-Speed Relay with Semiconductor Acceleration (Type HS)

Making capacity Max. 2500 W (L/R = 40 ms)


Max. 3600 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Breaking capacity Max. 2500 W (L/R = 40 ms)
Max. 360 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Contact voltage AC 200 V, DC 250 V
Permissible current per contact (continuous) 5 A (according to UL certification)
10 A (no UL certification; AWG 14 / 2.5-mm2 (0.0039-
in2) copper conductors necessary)
Permissible current per contact (switching on and 30 A for 1 s (make contact)
holding)
Short-time current across closed contact 250 A for 30 ms
Switching time OOT (Output Operating Time) Make time, typical: 0.2 ms; maximum: 0.2 ms
Additional delay of the output medium used Break time, typical: 9 ms; maximum: 9 ms
Rated data of the output contacts in accordance with B150
UL certification Q300

1586 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

Power Relay (for Direct Control of Motor Switches)

Switching power for permanent and periodic operation


250 V/4.0 A 1000 W In order to prevent any damage, the external protec-
220 V/4.5 A 1000 W tion circuit must switch off the motor in case the rotor
110 V/5.0 A 550 W is blocked.
60 V/5.0 A 300 W
48 V/5.0 A 240 W
24 V/5.0 A 120 W
Turn on switching power for 30 s, recovery time until switching on again is 15 minutes.
For short-term switching operations, an impulse/pause ratio of 3 % must be considered.
100 V/9.0 A 1000 W Continuous and inching operation is not permitted.
60 V/10.0 A 600 W In order to prevent any damage, the external protec-
48 V/10.0 A 480 W tion circuit must switch off the motor in case the rotor
24 V/10.0 A 240 W is blocked.
AC and DC contact voltage 250 V
Permissible continuous current per contact 5A
Permissible current per contact (switching on and 30 A for 1 s
holding)
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to 5A
common potential
Switching time OOT (Output Operating Time) ≤ 16 ms
Additional delay of the output medium used
Rated data of the output contacts in accordance with DC 300 V, 4.5 A - 30 s ON, 15 min OFF
UL certification DC 250 V, 1 hp motor - 30 s ON, 15 min OFF
DC 110 V, 3/4 hp motor - 30 s ON, 15 min OFF
DC 60 V, 10 A, 1/2 hp motor - 30 s ON, 15 min OFF
DC 48 V, 10 A, 1/3 hp motor - 30 s ON, 15 min OFF
DC 24 V, 10 A, 1/6 hp motor - 30 s ON, 15 min OFF
Interference suppression capacitors across the 4.7 nF, ± 20 %, AC 250 V
contacts
The power relays operate in interlocked mode, that is, only one relay of each switching pair picks up at a time
thereby avoiding a power-supply short circuit.

12.1.5 Design Data

Masses

Device Size
Weight of the Modular Devices
Type of construction 1/3 1/2 2/3 5/6 1/1
Flush-mounting device 4.4 kg 7.2 kg 9.9 kg 12.7 kg 15.5 kg
Surface-mounted device with inte- 7.4 kg 11.7 kg 15.9 kg 20.2 kg 24.5 kg
grated on-site operation panel
Surface-mounted device with 4.7 kg 7.8 kg 10.8 kg 13.9 kg 17.0 kg
detached on-site operation panel

Size Weight
Detached on-site operation panel 1/3 1.9 kg
Detached on-site operation panel 1/6 1.1 kg

SIPROTEC 5, 7SJ82/7SJ85, Manual 1587


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

Device Size
Weight of the Non-Modular Devices 7xx81, 7xx82
Type of construction 1/3
Flush-mounting device 3.6 kg
Bracket for non-modular surface- 1.9 kg
mounted variant

Dimensions of the Base and 1/3 Modules

Type of Construction (Maximum Dimensions) Width over all x Height over all x Depth (incl.
Current Terminal), Width and Depth Each Rounded
up to the Next Full mm (in Inches)
Flush-mounting device 150 mm x 266 mm x 229 mm
(5.91 x 10.47 x 9.02)
Surface-mounted device with integrated on-site oper- 150 mm x 314 mm x 337 mm
ation panel (5.91 x 12.36 x 13.27)
Surface-mounted device with detached on-site opera- 150 mm x 314 mm x 230 mm
tion panel (5.91 x 12.36 x 9.06)

Dimensions of the Device Rows

Type of Width over all x Height over all x Depth (incl. Current Terminal), Width and Depth
Construction Each Rounded up to the Next Full mm (in Inches)
(Maximum
Dimensions)
Type of construc- 1/3 1/2 2/3 5/6 1/1
tion
Flush-mounting 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
device 266 mm x 266 mm x 266 mm x 266 mm x 266 mm x
229 mm 229 mm 229 mm 229 mm 229 mm
(5.91 x 10.47 x (8.86 x 10.47 x (11.81 x 10.47 x (14.76 x 10.47 x (17.72 x 10.47 x
9.02) 9.02) 9.02) 9.02) 9.02)
Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
mounted device 314 mm x 314 mm x 314 mm x 314 mm x 314 mm x
with integrated 337 mm 337 mm 337 mm 337 mm 337 mm
on-site operation (5.91 x 12.36 x (8.86 x 12.36 x (11.81 x 12.36 x (14.76 x 12.36 x (17.72 x 12.36 x
panel 13.27) 13.27) 13.27) 13.27) 13.27)
Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
mounted device 314 mm x 314 mm x 314 mm x 314 mm x 314 mm x
with detached 230 mm 230 mm 230 mm 230 mm 230 mm
on-site operation (5.91 x 12.36 x (8.86 x 12.36 x (11.81 x 12.36 x (14.76 x 12.36 x (17.72 x 12.36 x
panel 9.06) 9.06) 9.06) 9.06) 9.06)

Expansion Module Dimensions

Type of Construction (Maximum Dimensions) Width x Height x Depth, Width and Depth Each
Rounded up to the Next Full mm (in Inches)
Flush-mounting device 75 mm x 266 mm x 229 mm
(2.95 x 10.47 x 9.02)
Surface-mounted device with integrated on-site oper- 75 mm x 314 mm x 337 mm
ation panel (2.95 x 12.36 x 13.27)
Surface-mounted device with detached on-site opera- 75 mm x 314 mm x 230 mm
tion panel (2.95 x 12.36 x 9.06)

1588 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

Plug-In Module Dimensions

Type of Construction (Maximum Dimensions) Width x Height x Depth (in Inches)


USART-Ax-xEL, ETH-Bx-xEL 61 mm x 45 mm x 120.5 mm
(2.4 x 1.77 x 4.74)
USART-Ax-xFO, ETH-Bx-xFO (without protection 61 mm x 45 mm x 132.5 mm
cover) (2.4 x 1.77 x 5.22)
ANAI-CA-4EL 61 mm x 45 mm x 119.5 mm
(2.4 x 1.77 x 4.7)
ARC-CD-3FO 61 mm x 45 mm x 120.5 mm
(2.4 x 1.77 x 4.74)

Minimum Bending Radii of the Connecting Cables Between the On-Site Operation Panel and the Base Module

Fiber-optic cable R = 50 mm
Pay attention to the length of the cable protection
sleeve, which you must also include in calculations.
D-Sub cable R = 50 mm (minimum bending radius)

Degree of Protection According to IEC 60529

For equipment in the surface-mounted housing IP5451 for front


For equipment in the flush-mounting housing IP5451 for front
For operator protection (back side) IP2x for current terminal (installed)
IP2x for voltage terminal (installed)
Degree of pollution, IEC 60255-27 2
Maximum operating altitude above sea level 2000 m (6561.68 ft)

UL Note

Type 1 if mounted into a door or front cover of an enclosure.


When expanding the device with the 2nd device row, then they must be mounted completely inside an
enclosure.

Tightening Torques for Terminal Screws

Type of Line Current Terminal Voltage Terminal with Voltage Terminal with
Spring-Loaded Terminals Screw Connection
Stranded wires with ring- 2.7 Nm No ring-type lug No ring-type lug
type lug
Stranded wires with boot- 2.7 Nm 1.0 Nm 0.6 Nm
lace ferrules or pin-type
lugs
Solid conductor, bare 2.0 Nm 1.0 Nm –
(2 mm2)
Bare stranded wire Not permitted 1 Nm 0.6 Nm

NOTE

i For current and voltage terminals, the maximum speed of the tool must not exceed 640 rpm.

51 The provided plug-in label must be used for expansion modules with LEDs.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1589


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.1 General Device Data

NOTE

i Use copper cables only.

Torques for Other Screw Types

Screw Type Torque


M4 x 20 1.2 Nm
M4 x 8 1.2 Nm
M2.5 x 6 0.39 Nm
Countersunk screw, M2.5 x 6 0.39 Nm
Countersunk screw, M2.5 x 8 0.39 Nm
Collar screw, M4 x 20 0.7 Nm

1590 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.2 Protection Interface and Protection Topology

12.2 Protection Interface and Protection Topology


Setting Values

Mode On
Off
PPS Synchronization Telegr. and PPS
Telegr. or PPS
PPS synchronization off
Blocking of the unbalanced Yes
runtimes No
Maximum signal runtime threshold 0.1 ms to 30.0 ms Increments of 0.1 ms
Maximum runtime difference 0.000 ms to 3.000 ms Increments of 0.001 ms
Failure indication after 0.05 s to 2.00 s Increments of 0.01 s
Transm. fail. alarm after 0.0 s to 6.0 s Increments of 0.1 s
Max. error rate/h 0.000 % to 100.000 % Increments of 0.001 %
Max. error rate/min 0.000 % to 100.000 % Increments of 0.001 %
PPS failure indication after 0.5 s to 60.0 s Increments of 0.1 s

Transmission Rate

Direct connection:
Transmission rate 2048 kbit/s
Connection via communication networks:
Supported network interfaces G703.1 with 64 kbit/s
G703-T1 with 1.455 Mbit/s
G703-E1 with 2.048 Mbit/s
X.21 with 64 kbit/s or 128 kbit/s or 512 kbit/s
Pilot wires with 128 kbit/s
Transmission rate 64 kbit/s at G703.1
1.455 Mbit/s at G703-T1
2.048 Mbit/s at G703-E1
512 kbit/s or 128 kbit/s or 64 kbit/s at X.21
128 kbit/s for pilot wires

Transmission Times

Priority 1:
Response time, total approx.
For 2 ends Minimum 8 ms
Typical 10 ms
For 3 ends Minimum 10 ms
Typical 14 ms
For 6 ends Minimum 15 ms
Typical 18 ms
Dropout times, total approx.
For 2 ends Typical 20 ms
For 3 ends Typical 20 ms
For 6 ends Typical 26 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1591


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.2 Protection Interface and Protection Topology

Priority 2:
Response time, total approx.
For 2 ends Minimum 9 ms
Typical 16 ms
For 3 ends Minimum 12 ms
Typical 18 ms
For 6 ends Minimum 17 ms
Typical 23 ms
Dropout times, total approx.
For 2 ends Typical 24 ms
For 3 ends Typical 25 ms
For 6 ends Typical 32 ms

Priority 352
Response time, total approx.
For 2 ends Minimum
Typical 100 ms
For 3 ends Minimum
Typical 150 ms
For 6 ends Minimum
Typical 200 ms
Dropout times, total approx.
For 2 ends Typical 100 ms
For 3 ends Typical 150 ms
For 6 ends Typical 200 ms

52 Times cannot be determined because the signals are transmitted in fragments.

1592 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.3 Date and Time Synchronization

12.3 Date and Time Synchronization


Date format DD.MM.YYYY (Europe)
MM/DD/YYYY (USA)
YYYY-MM-DD (China)
Time source 1, time source 2 None
IRIG-B 002(003)
IRIG-B 006(007)
IRIG-B 005(004) with extension according to
IEEE C37.118-2005
DCF77
PI (protection interface) 53
SNTP
IEC 60870-5-103
DNP3
IEEE 1588
T104
Time zone 1, time zone 2 Local
UTC
Failure indication after 0 s to 3600 s
Time zone and daylight saving time Manually setting the time zones
Time zone offset with respect to GMT -720 min to 840 min
Switching over to daylight saving time Active
Inactive
Beginning of daylight saving time Input: day and time
End of daylight saving time Input: day and time
Offset daylight saving time 0 min to 120 min [steps of 15]

53 If provided

SIPROTEC 5, 7SJ82/7SJ85, Manual 1593


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.4 Analog-Units Function Group

12.4 Analog-Units Function Group


20-mA Unit Ether. 7XV5674-0KK00-1AA1

Max. number of connected 20-mA units 4


Max. number of channels per 20-mA unit 12

20-mA Unit Serial 7XV5674-0KK30-1AA1 (RS485) and 7XV5674-0KK40-1AA1 (Fiberglass)

Max. number of connected 20-mA units 4


Max. number of channels per 20-mA unit 12

RTD Unit (Ziehl TR1200) 7XV5662-6AD10

Max. number of connected RTD units 4


Max. number of sensors per RTD unit 12
Sensor type Pt 100 to EN 60751; connection of Ni 100 and Ni 120
sensors possible. The measured values must be
converted in the evaluation unit.

RTD Unit (Ziehl TR1200 IP) 7XV5662-8AD10

Max. number of connected RTD units 4


Max. number of sensors per RTD unit 12
Sensor type Pt 100 to EN 60751; connection of Ni 100 and Ni 120
sensors possible. The measured values must be
converted in the evaluation unit.

Temperature Measured Values

Unit of measurement for temperature °C or °F, adjustable


Pt 100 -199 °C to 800 °C (-326 °F to 1472 °F)
Ni 100 -54 °C to 278 °C (-65 °F to 532 °F)
Ni 120 -52 °C to 263 °C (-62 °F to 505 °F)
Resolution 1 °C or 1 °F
Tolerance ±0.5 % of the measured value ±1 K

1594 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

12.5 Overcurrent Protection, Phases

12.5.1 Stage with Definite-Time Characteristic Curve

Setting Value for the Function Block Filter

h(0) -100.000 to 100.000 Increments of 0.001


h(1) -100.000 to 100.000 Increments of 0.001
h(2) -100.000 to 100.000 Increments of 0.001
h(3) -100.000 to 100.000 Increments of 0.001
h(4) -100.000 to 100.000 Increments of 0.001

Setting Values for Protection Stage

Method of measurement Fundamental component –


RMS value
Threshold value54 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout ratio 0.90 to 0.99 Increments of 0.01
Operate delay 0.00 s to 100.00 s Increments of 0.01 s
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s
Pickup delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT 55 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 20 ms + OOT

54 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
55 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1595


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value, no filter applied
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the compensation of the amplitude attenuation due to the anti-aliasing filter
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 2 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the gain of harmonics (including compensation of the amplitude attenuation56
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1.5 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %) 57
Up to 50th harmonic, frated = 50 Hz 3% of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 58
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 59
Time delays 1 % of the setting value or 10 ms

56 In case that the filter response exactly matches the user-defined gain factors
57 In case that the user-defined gain factor is set below 3. The tolerance increases, if the gain factor is larger.
58 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
59 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.

1596 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.5.2 Stage with Inverse-Time Characteristic Curve

Setting Value for the Function Block Filter

h(0) -100.000 to 100.000 Increments of 0.001


h(1) -100.000 to 100.000 Increments of 0.001
h(2) -100.000 to 100.000 Increments of 0.001
h(3) -100.000 to 100.000 Increments of 0.001
h(4) -100.000 to 100.000 Increments of 0.001

Setting Values for Protection Stage

Method of measurement Fundamental component –


RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.00 to 15.00 Increments of 0.01
Pickup delay 0.00 s to 60.00 s Increments of 0.01 s
Minimum time of the curve 0.00 s to 1.00 s Increments of 0.01 s
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Operate Curves and Dropout-Time Characteristic Curves according to IEC

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

SIPROTEC 5, 7SJ82/7SJ85, Manual 1597


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

[dwocpki1-080213-01.tif, 1, en_US]

Figure 12-1 Operate Curves and Dropout-Time Characteristic Curves According to IEC

1598 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

[dwocpki2-080213-01.tif, 1, en_US]

Figure 12-2 Operate Curves and Dropout-Time Characteristic Curves According to IEC

SIPROTEC 5, 7SJ82/7SJ85, Manual 1599


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

[dwocpka1-080213-01.tif, 2, en_US]

Figure 12-3 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

1600 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

[dwocpka2-080213-01.tif, 2, en_US]

Figure 12-4 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

SIPROTEC 5, 7SJ82/7SJ85, Manual 1601


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

[dwocpka3-080213-01.tif, 2, en_US]

Figure 12-5 Tripping Characteristic Curves and Dropout Characteristic Curves According to ANSI/IEEE

1602 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

[dwocpka4-080213-01.tif, 2, en_US]

Figure 12-6 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value, no filter applied
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the compensation of the amplitude attenuation due to the anti-aliasing filter
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1603


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

Up to 50th harmonic, frated = 50 Hz 2 % of the setting value or 10 mA (Irated = 1 A)


or 50 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the gain of harmonics (including compensation of the amplitude attenuation60
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1.5 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %) 61
Up to 50th harmonic, frated = 50 Hz 3% of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 62
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 63
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.5.3 Stage with User-Defined Characteristic Curve

Setting Value for the Function Block Filter

h(0) -100.000 to 100.000 Increments of 0.001


h(1) -100.000 to 100.000 Increments of 0.001
h(2) -100.000 to 100.000 Increments of 0.001
h(3) -100.000 to 100.000 Increments of 0.001
h(4) -100.000 to 100.000 Increments of 0.001

Setting Values for Protection Stage

Method of measurement Fundamental component –


RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

60 In case that the filter response exactly matches the user-defined gain factors
61 In case that the user-defined gain factor is set below 3. The tolerance increases, if the gain factor is larger.
62 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
63 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.

1604 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

Absolute pickup value 1 A @ 50 and 100 Irated 0.000 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.00 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.000 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.000 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
Number of value pairs for the operate curve 2 to 30 Increments of 1
X values of the operate curve 1.00 p.u. to 20.00 p.u. Increments of 0.01 p.u.
Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 s
Number of value pairs for the dropout characteristic 2 to 30 Increments of 1
curve
X values of the dropout characteristic curve 0.05 p.u. to 0.95 p.u. Increments of 0.01 p.u.
Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value or 95 % of the absolute
pickup value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value, no filter applied
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1605


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.5 Overcurrent Protection, Phases

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)


or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the compensation of the amplitude attenuation due to the anti-aliasing filter
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 2 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the gain of harmonics (including compensation of the amplitude attenuation64
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1.5 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %) 65
Up to 50th harmonic, frated = 50 Hz 3% of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 66
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 67
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

64 In case that the filter response exactly matches the user-defined gain factors
65 In case that the user-defined gain factor is set below 3. The tolerance increases, if the gain factor is larger.
66 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
67 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.

1606 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.6 Voltage-Dependent Overcurrent Protection, Phases

12.6 Voltage-Dependent Overcurrent Protection, Phases


Setting Values for All Stage Types

Method of measurement Fundamental component –


RMS value
Overcurrent threshold For Irated = 1 A 0.030 A to 35.000 A Increments of 0.001 A
value
For Irated = 5 A 0.15 A to 175.00 A Increments of 0.01 A
Time delay 0.10 s to 60.00 s Increments of 0.01 s

Setting Values for Inverse-Time Overcurrent Protection Stages

Method of measurement Fundamental component –


RMS value
Dropout ratio of undervoltage68 1.01 to 1.20 Increments of 0.01
Undervoltage threshold value68 0.300 V to 175.000 V Increments of 0.001 V
Dropout Disk emulation –
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01

Setting Values for Definite-Time Overcurrent Protection Stages

Seal-in voltage 0.300 V to 175.000 V Increments of 0.001 V


Phase-to-phase voltage 0.300 V to 175.000 V Increments of 0.001 V
Negative-sequence voltage V2 0.300 V to 200.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Duration of V-seal-in time 0.10 s to 60.00 s Increments of 0.01 s

Dropout for Inverse-Time Overcurrent Protection Stages


The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout
Current 95 % of 1.1 ⋅ threshold value
Voltage68 105 % of threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 68 150 mV sec.

Reset of the Integration Timer for Inverse-Time Overcurrent Protection Stages

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

68 The value is for the inverse-time overcurrent voltage-released stage.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1607


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.6 Voltage-Dependent Overcurrent Protection, Phases

Dropout for Definite-Time Overcurrent Protection Stages

Dropout differential derived from the parameter Dropout ratio


If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.

Operate Curves and Dropout Characteristic Curves According to IEC

Extension of the operate time during operation with Approx. 10 ms


inrush-current detection

The operate curves and dropout characteristic curves according to IEC can be found in the chapter Technical
Data under Inverse-Time Overcurrent Protection.

Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE


The operate curves and dropout characteristic curves according to IEC can be found in the chapter Technical
Data under Inverse-Time Overcurrent Protection.

Times for Definite-Time Overcurrent Protection Stages

Operate time with time delay = 0 ms, typical Approx. 25 ms + OOT69 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Operate time with time delay = 0 ms, maximum Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
(33 % part of harmonic in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)

69 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

1608 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.6 Voltage-Dependent Overcurrent Protection, Phases

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)


or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Voltage 0.5 % of the setting value or 0.05 V
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1609


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

12.7 Overcurrent Protection, Ground

12.7.1 Stage with Definite-Time Characteristic Curve

Setting Values

Method of measurement Fundamental component –


RMS value
Threshold value70 1 A @ 50 and 100 Irated 0.010 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.05 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.002 A to 8.000 A Increments of 0.001 A
Dropout ratio 0.90 to 0.99 Increments of 0.01
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT71 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

70 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
71 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

1610 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

Tolerances

3I0 measured via I472, method of measurement = 1 % of the setting value or 5 mA (Irated = 1 A)
fundamental component or 25 mA (Irated = 5 A), (frated ± 10 %)
3I0 measured via I473, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.7.2 Stage with Inverse-Time Characteristic Curve

Setting Values

Method of measurement Fundamental component –


RMS value
Threshold value74 1 A @ 50 and 100 Irated 0.010 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.05 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.002 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.00 to 15.00 Increments of 0.01
Minimum time of the curve 0.00 s to 1.00 s Increments of 0.01 s
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

72 Slightly expanded tolerances will occur during the calculation of 3I0, maximum factor of 2
73 Slightly expanded tolerances will occur during the calculation of 3I0, maximum factor of 2
74 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 l
rated,sec.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1611


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Operate Curves and Dropout Characteristic Curves According to IEC

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

[dwocpki1-080213-01.tif, 1, en_US]

Figure 12-7 Operate Curves and Dropout Characteristic Curves According to IEC

1612 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

[dwocpki2-080213-01.tif, 1, en_US]

Figure 12-8 Operate Curves and Dropout Characteristic Curves According to IEC

SIPROTEC 5, 7SJ82/7SJ85, Manual 1613


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE

[dwocpka1-080213-01.tif, 2, en_US]

Figure 12-9 Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE

1614 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

[dwocpka2-080213-01.tif, 2, en_US]

Figure 12-10 Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE

SIPROTEC 5, 7SJ82/7SJ85, Manual 1615


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

[dwocpka3-080213-01.tif, 2, en_US]

Figure 12-11 Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE

1616 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

[dwocpka4-080213-01.tif, 2, en_US]

Figure 12-12 Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

3I0 measured via I475, method of measurement = 1 % of the setting value or 5 mA (Irated = 1 A)
fundamental component or 25 mA (Irated = 5 A), (frated ± 10 %)
3I0 measured via I476, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms

75 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
76 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2

SIPROTEC 5, 7SJ82/7SJ85, Manual 1617


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

Dropout time for 2 ≤ I/threshold value I ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.7.3 Stage with User-Defined Characteristic Curve

Setting Values

Method of measurement Fundamental component –


RMS value
Threshold value 1 A @ 50 and 100 Irated 0.010 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.05 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.002 A to 8.000 A Increments of 0.001 A
Absolute pickup value 1 A @ 50 and 100 Irated 0.000 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.00 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.000 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.000 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
Number of value pairs for the operate curve 2 to 30 Increments of 1
X values of the operate curve 1.00 p.u. to 20.00 p. u. Increments of 0.01 p.u.
Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 s
Number of value pairs for the dropout characteristic 2 to 30 Increments of 1
curve
X values of the dropout characteristic curve 0.05 p.u. to 0.95 p. u. Increments of 0.01 p.u.
Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value or 95 % of the absolute
pickup value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

1618 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.7 Overcurrent Protection, Ground

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

3I0 measured via I477, method of measurement = 1 % of the setting value or 5 mA (Irated = 1 A)
fundamental component or 25 mA (Irated = 5 A), (frated ± 10 %)
3I0 measured via I478,
method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

77 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
78 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2

SIPROTEC 5, 7SJ82/7SJ85, Manual 1619


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.8 Directional Overcurrent Protection, Phases

12.8 Directional Overcurrent Protection, Phases

12.8.1 Stage with Definite-Time Characteristic Curve

Setting Values

Rotation angle of the reference voltage -180° to +180° Increments of 1°


Directional mode Forward –
Reverse
Method of measurement Fundamental component –
RMS value
Threshold value79 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout ratio 0.90 to 0.99 Increments of 0.01
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Direction Determination

Type With healthy voltages


With voltage memory 2 s
Forward range Vref,rot ±88°
Dropout differential forward/reverse range 1°
Directional sensitivity Unlimited for 1 and 2-phase short circuits
Dynamically unlimited, stationary for 3-phase short
circuits
Approx. 13 V phase-to-phase

79 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.

1620 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.8 Directional Overcurrent Protection, Phases

Times

Operate time with time delay = 0 ms Approx. 37 ms + OOT 80 at 50 Hz


Approx. 31 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Time delay 1 % of the setting value or 10 ms
Direction-determination angle error 1°

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.8.2 Stage with Inverse-Time Characteristic Curve

Setting Values

Rotation angle of the reference voltage -180° to +180° Increments of 1°


Directional mode Forward –
Backward
Method of measurement Fundamental component –
RMS value

80 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1621


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.8 Directional Overcurrent Protection, Phases

Threshold value81 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.00 to 15.00 Increments of 0.01
Minimum time of the curve 0.00 s to 1.00 s Increments of 0.01 s
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Operate Curves and Dropout-Time Characteristic Curves according to IEC

Normal inverse: type A See chapter 12.5.2 Stage with Inverse-Time Charac-
Very inverse: type B teristic Curve, Figure 12-1
Extremely inverse: type C See chapter 12.5.2 Stage with Inverse-Time Charac-
Long-time inverse: type B teristic Curve, Figure 12-2

Operate Curves and Dropout-Time Characteristic Curves according to ANSI/IEEE

Inverse: type C See chapter 12.5.2 Stage with Inverse-Time Charac-


Short inverse teristic Curve, Figure 12-3
Long inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
Moderately inverse teristic Curve, Figure 12-4
Very inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
Extremely inverse teristic Curve, Figure 12-5
Definite inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
teristic Curve, Figure 12-6

Direction Determination

Type With healthy voltages


With voltage memory 2 s
Forward range Vref,rot ±88°
Dropout differential forward/reverse range 1°

81 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.

1622 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.8 Directional Overcurrent Protection, Phases

Directional sensitivity Unlimited for 1 and 2-phase short circuits


Dynamically unlimited, stationary for 3-phase short
circuits
Approx. 13 V phase-to-phase

Times

Operate time with time delay = 0 ms Approx. 37 ms + OOT 82 at 50 Hz


Approx. 31 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/threshold value I ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 10 ms
Dropout time for I/threshold value I ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 10 ms
Direction-determination angle error 1°

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

82 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1623


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.8 Directional Overcurrent Protection, Phases

12.8.3 Stage with User-Defined Characteristic Curve

Setting Values

Rotation angle of the reference voltage -180° to +180° Increments of 1°


Directional mode Forward –
Reverse
Method of measurement Fundamental component –
RMS value
Threshold value83 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation -
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
Number of value pairs for the operate characteristic 2 to 30 Increments of 1
curve
X values of the operate curve 1.00 p.u. to 66.67 p.u. Increments of 0.01 p.u.
Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 s
Number of value pairs for the dropout characteristic 2 to 30 Increments of 1
curve
X values of the dropout characteristic curve 0.05 p.u. to 0.95 p.u. Increments of 0.01 p.u.
Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Direction Determination

Type With healthy voltages


With voltage memory 2 s
Forward range Vref,rot ±88°
Dropout differential forward/reverse range 1°

83 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.

1624 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.8 Directional Overcurrent Protection, Phases

Directional sensitivity Unlimited for 1-phase and 2-phase short circuits


Dynamically unlimited, stationary for 3-phase short
circuits
Approx. 13 V phase-to-phase

Times

Operate time with time delay = 0 ms Approx. 37 ms + OOT 84 at 50 Hz


Approx. 31 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/threshold value I≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 10 ms
Dropout time for I/threshold value I ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 10 ms
Direction-determination angle error 1°

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

84 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1625


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

12.9 Directional Overcurrent Protection, Ground

12.9.1 Stage with Definite-Time Characteristic Curve

Setting Values for the Function Direction Determination

Method for direction determination Zero sequence –


Negative sequence
Minimum V0 or V2 threshold 0.150 V to 20.000 V 0.001 V
Rotation angle of the reference voltage -180° to 180° 1°
Forward range 0° to 180° 1°

Setting Values

Direction mode Forward –


Reverse
Method of measurement Fundamental component –
RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout ratio 0.90 to 0.99 Increments of 0.01
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

The maximum pickup time with operate delay = 0 ms Approx. 30 ms + OOT at 50 Hz


Approx. 25 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
inrush-current detection
Dropout time Approx. 20 ms + OOT

1626 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with reduced sensitivity
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A)
Currents, method of measurement = RMS value
(33 % part of harmonic, referring to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Time delays 1 % of the setting value or 10 ms
Direction-determination angle error 1º

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.9.2 Stage with Inverse-Time Characteristic Curve

Setting Values for the Function Direction Determination

Method for direction determination Zero sequence –


Negative sequence
Minimum V0 or V2 threshold 0.150 V to 20.000 V 0.001 V
Rotation angle of the reference voltage -180° to 180° 1°
Forward range 0° to 180° 1°

Setting Values

Direction mode Forward –


Reverse
Method of measurement Fundamental component –
RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Type of characteristic curve Characteristic curves according to IEC and ANSI

SIPROTEC 5, 7SJ82/7SJ85, Manual 1627


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

Dropout Disk emulation –


Instantaneous
Time multiplier 0.00 to 15.00 Increments of 0.01
Minimum time of the curve 0.00 s to 1.00 s Increments of 0.01 s
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Operate Curves and Dropout-Time Characteristic Curves according to IEC

Normal inverse: type A Refer to the respective figure of the technical data for
Very inverse: type B the non-dir-OC-ground function 12.7.2 Stage with
Inverse-Time Characteristic Curve
Extremely inverse: type C
Long-time inverse: type B

Operate Curves and Dropout-Time Characteristic Curves according to ANSI/IEEE

Inverse: type C Refer to the respective figure of the technical data for
Short inverse the non-dir-OC-ground function 12.7.2 Stage with
Inverse-Time Characteristic Curve
Long inverse
Moderately inverse
Very inverse
Extremely inverse
Definite inverse

Times

The maximum pickup time with operate delay = 0 ms Approx. 30 ms + OOT at 50 Hz


Approx. 25 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
inrush-current detection
Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz

1628 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

f < 10 Hz Active with reduced sensitivity


f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A)
Currents, method of measurement = RMS value
(33 % part of harmonic, referring to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Direction-determination angle error 1º

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.9.3 Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse


Characteristic Curve

Setting Values for the Function Direction Determination

Method for direction determination Zero sequence –


Negative sequence
Minimum V0 or V2 threshold 0.150 V to 20.000 V 0.001 V
Rotation angle of the reference voltage -180° to 180° 1°
Forward range 0° to 180° 1°

Setting Values

Direction mode Forward –


Reverse
Method of measurement Fundamental component –
RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Characteristic curve: see Figure 12-13
Threshold value multiplier 1.00 to 4.00 Increments of 0.01

SIPROTEC 5, 7SJ82/7SJ85, Manual 1629


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

Time multiplier 0.000 s to 60.000 s Increments of 0.001 s


Minimum time of the characteristic curve 0.000 s to 60.000 s Increments of 0.001 s
Maximum time of the characteristic curve 0.000 s to 60.000 s Increments of 0.001 s
Additional time delay 0.000 s to 60.000 s Increments of 0.001 s

[dwloginv-300913, 3, en_US]

Figure 12-13 Operate Curve of Logarithmic Inverse-Time Characteristic

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

The maximum pickup time with operate delay = 0 ms Approx. 30 ms + OOT at 50 Hz


Approx. 25 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
inrush-current detection
Dropout time Approx. 20 ms + OOT

1630 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with reduced sensitivity
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A)
Currents, method of measurement = RMS value
(33 % part of harmonic, referring to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Inverse-time operate time to logarithmic inverse-time 5 % of the reference (calculated) value
characteristic + 2 % current tolerance or 30 ms
Inverse-time dropout time to logarithmic inverse-time 5 % of the reference (calculated) value
characteristic + 2 % current tolerance or 30 ms
Direction-determination angle error 1º

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.9.4 Stage with Knee-Point Characteristic Curve

Setting Values for the Function Direction Determination

Method for direction determination Zero sequence –


Negative sequence
Minimum V0 or V2 threshold 0.150 V to 20.000 V 0.001 V
Rotation angle of the reference voltage -180° to 180° 1°
Forward range 0° to 180° 1°

Setting Values

Direction mode Forward –


Reverse
Method of measurement Fundamental component –
RMS value

SIPROTEC 5, 7SJ82/7SJ85, Manual 1631


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Characteristic curve: see Figure 12-14
Minimum time of the characteristic curve 0.00 s to 30.00 s Increments of 0.01 s
Knee-point time of the curve 0.00 s to 100.00 s Increments of 0.01 s
Maximum time of the characteristic curve 0.00 s to 200.00 s Increments of 0.01 s
Knee-point value 0.030 A to 35.000 A Increments of 0.001 A
Current at minimum time of the curve 0.030 A to 35.000 A Increments of 0.001 A
Time multiplier 0.05 to 1.50 Increments of 0.01

[dwdrloinkn-171013, 1, en_US]

Figure 12-14 Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In the Example
of Threshold = 0.004 A)

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)

1632 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or


2.5 mA sec. (Irated = 5 A)

Times

The maximum pickup time with operate delay = 0 ms Approx. 30 ms + OOT at 50 Hz


Approx. 25 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
inrush-current detection
Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with reduced sensitivity
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A)
Currents, method of measurement = RMS value
(33 % part of harmonic, referring to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Inverse-time operate time to logarithmic inverse time 5 % of the reference (calculated) value
with knee-point characteristic + 2 % current tolerance or 30 ms
Inverse-time dropout time to logarithmic inverse time 5 % of the reference (calculated) value
with knee-point characteristic + 2 % current tolerance or 30 ms
Direction-determination angle error 1º

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.9.5 Stage with User-Defined Characteristic Curve

Setting Values for the Function Direction Determination

Method for direction determination Zero sequence –


Negative sequence
Minimum V0 or V2 threshold 0.150 V to 20.000 V 0.001 V

SIPROTEC 5, 7SJ82/7SJ85, Manual 1633


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

Rotation angle of the reference voltage -180° to 180° 1°


Forward range 0° to 180° 1°

Setting Values

Direction mode Forward –


Reverse
Method of measurement Fundamental component –
RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
X values of the operate curve 1.00 p. u. to 66.67 p. u. Increments of 0.01 p. u.
Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 s
Number of value pairs for the dropout characteristic 2 to 30 Increments of 1
curve
X values of the dropout characteristic curve 0.05 p. u. to 0.95 p. u. Increments of 0.01 p. u.
Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Times

The maximum pickup time with operate delay = 0 ms Approx. 30 ms + OOT at 50 Hz


Approx. 25 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
inrush-current detection
Dropout time Approx. 20 ms + OOT

1634 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.9 Directional Overcurrent Protection, Ground

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with reduced sensitivity
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A)
Currents, method of measurement = RMS value
(33 % part of harmonic, referring to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Direction-determination angle error 1º

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1635


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.10 Inrush-Current Detection

12.10 Inrush-Current Detection


Setting Values

Operat.-range limit Imax 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Content 2nd harmonic 10 % to 45 % Increments of 1 %
Duration of the crossblock function 0.03 s to 200.00 s Increments of 0.01 s

Times

Pre-arcing times Approx. 29 ms

Dropout Ratios

Harmonic: I2nd harm/I1st harm 0.95

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Current measurement Imax 1 % of the setting value or 5 mA


Harmonic: I2nd harm/I1st harm 1 % of the setting value with setting values
of I2nd harm/I1st harm
Time delays 1 % of the setting value or 10 ms

1636 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.11 Arc Protection

12.11 Arc Protection


Setting Values

Threshold I> 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold 3I0>> 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
External trip initiation no
current
light
Operating mode light only
current and light
Sensor point sensor
line sensor
custom
Threshold light -28.00 dB to 0.00 dB Increments of 0.01
Channel Possible settings, application-dependent

Dropout
The larger dropout differential (= | pickup threshold – dropout threshold |) of the following
2 criteria is used:
Dropout differential derived from the Dropout ratio parameter
If this parameter is not available, a dropout ratio of 95 % applies to the overcurrent protection and a dropout
ratio of 105 % applies to the undercurrent protection.
Minimum absolute dropout differential
Protection-class current transformers 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument transformers 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Shortest operate time Approx. 2.6 ms + OOT 85


Operating mode = light only
Shortest operate time
Approx. 4.0 ms + OOT at 50 Hz
Operating mode = Current and light
Approx. 3.8 ms + OOT at 60 Hz

85 OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relay, see chapter
12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1637


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.12 Instantaneous High-Current Tripping

12.12 Instantaneous High-Current Tripping


Setting Values

Threshold value 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


5 A @ 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 50 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout ratio 0.50 to 0.90 Increments of 0.01

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time for current > 2 · √2 · threshold value Approx. 8 ms + OOT86

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Response tolerance, current 5 % of setting value or 10 mA


at Irated = 1 A
5 % of setting value or 50 mA
at Irated = 5 A
Time delays 1 % of the setting value or 10 ms

86 OOT (Output Operating Time) Additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

1638 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.13 Instantaneous Tripping at Switch onto Fault

12.13 Instantaneous Tripping at Switch onto Fault


Setting Values

Tripping delay 0.00 s to 60.00 s Increments of


0.01 s

Tolerances

Times < 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1639


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.14 Overcurrent Protection, 1-Phase

12.14 Overcurrent Protection, 1-Phase

12.14.1 Stage with Definite-Time Characteristic Curve

Setting Values

Method of measurement Fundamental component –


RMS value
Threshold value87 1 A @ 50 and 100 Irated 0.010 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.05 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.002 A to 8.000 A Increments of 0.001 A
Dropout ratio (fixed) 0.95 –
Time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 15 ms + OOT88 at 50 Hz


Approx. 14 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 20 ms + OOT at 50 Hz
Approx. 17 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

87 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
88 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

1640 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.14 Overcurrent Protection, 1-Phase

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.14.2 Stage with Inverse-Time Characteristic Curve

Setting Values

Method of measurement Fundamental component –


RMS value
Threshold value89 1 A @ 50 and 100 Irated 0.010 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.05 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.002 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

89 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1641


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.14 Overcurrent Protection, 1-Phase

Operate Curves and Dropout Characteristic Curves According to IEC

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

The operate curves and dropout characteristic curves according to IEC can be found in the Technical Data
chapter under Inverse-Time Overcurrent Protection.

Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE


The operate curves and dropout characteristic curves according to ANSI/IEEE can be found in the Technical
Data chapter under Inverse-Time Overcurrent Protection.

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

1642 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.14 Overcurrent Protection, 1-Phase

12.14.3 Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse


Characteristic Curve

Setting Values

Method of measurement Fundamental component –


RMS value
Threshold value 1 A @ 50 and 100 Irated 0.010 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.050 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.002 A to 8.000 A Increments of 0.001 A
Characteristic curve: see Figure 12-15
Threshold value multiplier 1.00 to 4.00 Increments of 0.01
Time dial 0.000 s to 60.000 s Increments of 0.001 s
Minimum time of the characteristic curve 0.000 s to 60.000 s Increments of 0.001 s
Maximum time of the characteristic curve 0.000 s to 60.000 s Increments of 0.001 s
Additional time delay 0.000 s to 60.000 s Increments of 0.001 s

[dw_ocp 1phase logarithmic, 1, en_US]

Figure 12-15 Operate Curve of Logarithmic Inverse-Time Characteristic

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:

SIPROTEC 5, 7SJ82/7SJ85, Manual 1643


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.14 Overcurrent Protection, 1-Phase

Dropout differential derived from the parameter Dropout ratio


If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

The maximum pickup time with operate delay = 0 ms Approx. 30 ms + OOT at 50 Hz


Approx. 25 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
inrush-current detection
Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with reduced sensitivity
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A)
Currents, method of measurement = RMS value
(33 % part of harmonic, referring to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Inverse-time operate time to logarithmic inverse-time 5 % of the reference (calculated) value
characteristic + 2 % current tolerance or 30 ms
Inverse-time dropout time to logarithmic inverse-time 5 % of the reference (calculated) value
characteristic + 2 % current tolerance or 30 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

1644 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.14 Overcurrent Protection, 1-Phase

12.14.4 Stage with User-Defined Characteristic Curve

Setting Values

Method of measurement Fundamental component –


RMS value
Threshold value 1 A @ 50 and 100 Irated 0.010 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.05 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.002 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
Number of value pairs for the operate curve 2 to 30 Increments of 1
X values of the operate curve 1.00 p.u. to 66.67 p. u. Increments of 0.01 p.u.
Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 s
Number of value pairs for the dropout characteristic 2 to 30 Increments of 1
curve
X values of the dropout characteristic curve 0.05 p.u. to 0.95 p. u. Increments of 0.01 p.u.
Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with reduced sensitivity
f > 90 Hz

SIPROTEC 5, 7SJ82/7SJ85, Manual 1645


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.14 Overcurrent Protection, 1-Phase

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

1646 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.15 Overcurrent Protection, 1-Phase (Fast Stage)

12.15 Overcurrent Protection, 1-Phase (Fast Stage)


Setting Values

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout ratio (fixed) 0.90 to 0.99 Increments of 0.01
Time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 8 ms + OOT90


Dropout time Approx. 25 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Pickup tolerance, current 5 % of the setting value or 10 mA (Irated = 1 A)


or 50 mA (Irated = 5 A)
Time delays 1 % of the setting value or 10 ms

90 OOT (Output Operating Time): additional time delay of the output medium used, for example, 5 ms with fast relay

SIPROTEC 5, 7SJ82/7SJ85, Manual 1647


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.16 Positive-Sequence Overcurrent Protection

12.16 Positive-Sequence Overcurrent Protection

12.16.1 Stage with Definite-Time Characteristic Curve

Setting Values for Protection Stage

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Operate delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT 91 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Current 1 % of the setting value or 5 mA (Irated = 1 A)


or 25 mA (Irated = 5 A), (frated ± 10 %)
Time delays 1 % of the setting value or 10 ms

91 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

1648 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.16 Positive-Sequence Overcurrent Protection

12.16.2 Stage with Inverse-Time Characteristic Curve

Setting Values for Protection Stage

Threshold 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Reset instantaneous –
disk emulation
Time dial 0.00 to 15.00 Increments of 0.01

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Operate and Dropout Characteristic Curves


You can select from the following operate and dropout characteristic curves:

Table 12-4 Standard Characteristic Curves according to IEC

Normal inverse: type A See chapter 12.5.2 Stage with Inverse-Time Charac-
Very inverse: type B teristic Curve, Figure 12-1
Extremely inverse: type C See chapter 12.5.2 Stage with Inverse-Time Charac-
Long-time inverse: type B teristic Curve, Figure 12-2

Table 12-5 Standard Characteristic Curves according to ANSI

Inverse: type C See chapter 12.5.2 Stage with Inverse-Time Charac-


Short inverse teristic Curve, Figure 12-3
Long inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
Moderately inverse teristic Curve, Figure 12-4
Very inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
Extremely inverse teristic Curve, Figure 12-5
Definite inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
teristic Curve, Figure 12-6

SIPROTEC 5, 7SJ82/7SJ85, Manual 1649


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.16 Positive-Sequence Overcurrent Protection

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT 92 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Current 1 % of the setting value or 5 mA (Irated = 1 A)


or 25 mA (Irated = 5 A), (frated ± 10 %)
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Time delays 1 % of the setting value or 10 ms

92 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

1650 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.17 Non-Directional Intermittent Ground-Fault Protection

12.17 Non-Directional Intermittent Ground-Fault Protection


Setting Values

Threshold For current transformer type protection 0.030 A to 35.000 A Increments of 0.001 A
value 3I0> and Irated = 1 A
interm.
For current transformer type protection 0.15 A to 175.00 A Increments of 0.01 A
and Irated = 5 A
For IN transformer For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A
type sensitive and For I
ph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A
IN-rated = 1 A
For IN transformer For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A
type sensitive and For I
ph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A
IN-rated = 5 A
Number of pickups until intermittent ground fault 2 to 10 Increments of 1
Pickup extension time 0.00 s to 10.00 s Increments of 0.01 s
Sum of extended pickup times 0.00 s to 100.00 s Increments of 0.01 s
Reset time 1.00 s to 600.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT93 at 50 Hz


Approx. 23 ms + OOT at 60 Hz
Dropout time Approx. 25 ms + OOT at 50 Hz
Approx. 22 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with reduced sensitivity
f > 90 Hz

93 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1651


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.17 Non-Directional Intermittent Ground-Fault Protection

Tolerances

Currents -3I0 via protection-class current transformers:


1 % of setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A)
-3I0 via sensitive current transformer:
1 % of setting value or 0.1 mA (Irated = 1.6 A)
or 0.5 mA (Irated = 8 A)
Times 1 % of the setting value or ± 10 ms

1652 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.18 Directional Intermittent Ground-Fault Protection

12.18 Directional Intermittent Ground-Fault Protection


Setting Values

Threshold For current transformer type 0.030 A to 35.000 A Increments of 0.001 A


value 3I0> protection and Irated = 1 A
For current transformer type 0.15 A to 175.00 A Increments of 0.01 A
protection and Irated = 5 A
For IN transformer For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A
type sensitive and For I
ph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A
IN-rated = 1 A
For IN transformer For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A
type sensitive and For I
ph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A
IN-rated = 5 A
Number of pulses until intermit- 2 to 10 Increments of 1
tent ground fault
Pickup extension time 0.00 s to 10.00 s Increments of 0.01 s
Sum of extended pickup times 0.00 s to 100.00 s Increments of 0.01 s
Reset time 1.00 s to 600.00 s Increments of 0.01 s
Number of pulses for operate 2 to 100 Increments of 1

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Pickup time Approx. 30 ms + OOT94 at 50 Hz


Approx. 23 ms + OOT at 60 Hz
Dropout time Approx. 25 ms + OOT at 50 Hz
Approx. 22 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with reduced sensitivity
f > 90 Hz

94 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1653


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.18 Directional Intermittent Ground-Fault Protection

Tolerances

Currents 3I0 via protection-class current transformers:


1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A)
3I0 via sensitive current transformer:
1 % of the setting value or 0.1 mA (Irated = 1.6 A)
or 0.5 mA (Irated = 8 A)
Times 1 % of the setting value or ± 10 ms

1654 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

12.19 Sensitive Ground-Fault Detection

12.19.1 General

Setting Values

Decay time V0 0.03 s to 0.20 s Increments of 0.01 s


Dropout delay 0.00 s to 60.00 s Increments of 0.01 s
Core balance Protection-class For Iph-rated = 1 A 0.030 A to Increments of 0.001 A
current transformer current trans- 35.000 A
current 1 formers For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A
Core balance
For IN transformer For Iph-rated = 1 A 0.001 A to Increments of 0.001 A
current transformer
type sensitive 35.000 A
current 2
and IN-rated = 1 A For Iph-rated = 5 A 0.001 A to Increments of 0.001 A
175.000 A
For IN transformer For Iph-rated = 1 A 0.005 A to Increments of 0.001 A
type sensitive 35.000 A
and IN-rated = 5 A For Iph-rated = 5 A 0.005 A to Increments of 0.001 A
175.000 A
Core balance current transformer angle correction F1 0.0° to 5.0° Increments of 0.1°
Core balance current transformer angle correction F2

Times

Pickup times Approx. 25 ms + OOT95 at 50 Hz


Approx. 23 ms + OOT at 60 Hz
Dropout times Approx. 25 ms + OOT at 50 Hz
Approx. 22 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances 96
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active with less sensitivity 97
f > 90 Hz

Tolerances

Currents -3I0 via sensitive current transformer:


1 % of the setting value or 0.1 mA (Irated = 1.6 A)
or 0.5 mA (Irated = 8 A, frated ± 10 %)
-3I0 via protection-class current transformers:
1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A, frated ± 10 %)
Voltages 1 % of the setting value or 0.05 V
Times 1 % of the setting value or ±10 ms

95 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
96 Transient ground-fault stage is inactive
97 Transient ground-fault stage is inactive

SIPROTEC 5, 7SJ82/7SJ85, Manual 1655


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

Direction-calculation angle error98 ≤ 1° at 3I0 > 5 mA, V0 = 0.6 V


≤ 2° at 3I0 ≤ 5 mA, V0 = 0.6 V

12.19.2 Directional 3I0 Stage with Cos φ or Sin φ Measurement

Setting Values

Direction method of measurement cos φ –


sin φ
Threshold value Protection-class For Iph-rated = 0.030 A to 35.000 A Increments of 0.001 A
3I0> current trans- 1A
Minimum direc- formers
For Iph-rated = 0.15 A to 175.00 A Increments of 0.01 A
tional 3I0> for
5A
direction determi-
nation For IN transformer For Iph-rated = 0.001 A to 35.000 A Increments of 0.001 A
type sensitive 1A
and IN-rated = 1 A For Iph-rated = 0.001 A to 175.000 A Increments of 0.001 A
5A
For IN transformer For Iph-rated = 0.005 A to 35.000 A Increments of 0.001 A
type sensitive 1A
and IN-rated = 5 A For Iph-rated = 0.005 A to 175.000 A Increments of 0.001 A
5A
Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 V
Time delay of the direction determination 0.00 s to 60.00 s Increments of 0.01 s
α1 constraint of the direction range 1° to 15° Increments of 1°
α2 constraint of the direction range
Angle correction φ -45° to 45° Increments of 1°
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.

98 Not applicable to 12.19.4 Directional 3I0 Stage with φ(V0,3I0) Measurement

1656 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT99 at 50 Hz


Approx. 29 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 32 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz

12.19.3 Directional Transient Ground-Fault Stage

Setting Values

3I0> threshold Protection-class For Iph-rated = 0.000 A to 35.000 A Increments of 0.001 A


value current transformers 1 A
3I0> threshold For Iph-rated = 0.00 A to 175.00 A Increments of 0.01 A
for operate
5A
Sensitive current IN-rated = 1 A 0.000 A to 1.600 A Increments of 0.001 A
transformer for IN
IN-rated = 5 A 0.000 A to 8.000 A Increments of 0.001 A
Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 V
Maximum operational V0 0.300 V to 200.000 V Increments of 0.001 V
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 115 ms + OOT100 at 50 Hz


Approx. 112 ms + OOT at 60 Hz
Dropout time Approx. 20 ms + OOT at 50 Hz
Approx. 15 ms + OOT at 60 Hz

99 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
100 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1657


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

12.19.4 Directional 3I0 Stage with φ(V0,3I0) Measurement

Setting Values

Threshold value Protection-class For Iph-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A


3I0> current transformers
For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A
For IN transformer type For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A
sensitive For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A
and IN-rated = 1 A
For IN transformer type For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A
sensitive For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A
and IN-rated = 5 A
Min. V0> for direction determination 0.300 V to 200.000 V Increments of 0.001 V
Time delay of the direction determination 0.00 s to 60.00 s Increments of 0.01 s
Rotation angle of the reference voltage -180° to 180° Increments of 1°
Forward range +/- 0° to 180° Increments of 1°
Tripping delay 0.00 s to 100.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 23 ms + OOT101 at 50 Hz


Approx. 21 ms + OOT at 60 Hz
Extension of operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 21 ms + OOT at 50 Hz
Approx. 20 ms + OOT at 60 Hz

Tolerances

Direction-calculation angle error ≤ 1° at 3I0 ≥ 10 mA, V0 = 0.6 V


≤ 2° at 2 mA < 3I0 < 10 mA, V0 = 0.6 V
≤ 3° at 3I0 ≤ 2 mA, V0 = 0.6 V

101 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

1658 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

12.19.5 Directional Y0 Stage with G0 or B0 Measurement (Admittance)

Setting Values

Direction method of measurement B0 –


G0
Release Protection-class For Iph-rated = 0.030 A to 35.000 A Increments of 0.001 A
Threshold current transformers 1 A
value 3I0> For Iph-rated = 0.15 A to 175.00 A Increments of 0.01 A
5A
For IN transformer For Iph-rated = 0.001 A to 35.000 A Increments of 0.001 A
type sensitive and 1A
IN-rated = 1 A For Iph-rated = 0.001 A to 175.000 A Increments of 0.001 A
5A
For IN transformer For Iph-rated = 0.005 A to 35.000 A Increments of 0.001 A
type sensitive and 1A
IN-rated = 5 A For Iph-rated = 0.005 A to 175.000 A Increments of 0.001 A
5A
Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 V
Threshold value Y0> 0.10 mS to 100.00 mS Increments of 0.01 mS
Time delay of direction determination 0.00 s to 60.00 s Increments of 0.01 s
α1 constraint of direction range 1° to 15° Increments of 1°
α2 constraint of direction range
Angle correction φ -45° to 45° Increments of 1°
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT102 at 50 Hz


Approx. 29 ms + OOT at 60 Hz
Extension of operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 32 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz

102 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1659


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

Tolerances

Admittance 1 % of the setting value or 0.05 mS (Irated = 1.6 A) or


0.25 mS (Irated = 8 A), (frated ± 10 %)

12.19.6 Directional Stage with Phasor Measurement of a Harmonic

Setting Values

Min. 3I0> of the Protection-class For Iph-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A
selected current transformers
For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A
harmonic phasor
For IN transformer type For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A
sensitive For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A
and IN-rated = 1 A
For IN transformer type For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A
sensitive For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A
and IN-rated = 5 A
Dropout ratio of the direction determination in terms of the 0.10 to 0.95 Increments of 0.01
zero-sequence harmonic current
Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 V
Time delay of the direction determination 0.00 s to 60.00 s Increments of 0.01 s
Extension of the direction result 0.00 s to 60.00 s Increments of 0.01 s
Forward range +/- 0° to 90° Increments of 1°
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 70 ms + OOT103 at 50 Hz


Approx. 60 ms + OOT at 60 Hz
Dropout time Approx. 30 ms + OOT at 50 Hz
Approx. 20 ms + OOT at 60 Hz

103 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

1660 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

Tolerances

Zero-sequence harmonic current 3I0harm. -3I0harm. via sensitive current transformer:


1 % of the setting value or 0.1 mA (Irated = 1.6 A)
or 0.5 mA (Irated = 8 A, frated ± 10 %)
-3I0harm. via protection-class current transformers:
1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A, frated ± 10 %)
V0 fundamental-component value 1 % of the setting value or 0.05 V
Direction-calculation angle error of the 3rd, 5th, or ≤ 1° at 3I0harm. > 5 mA
7th harmonic phasor ≤ 2° at 3I0harm. ≤ 5 mA

12.19.7 Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage

Setting Values

Threshold value104 0.300 V to 200.000 V Increments of 0.001 V


Time delay 0.00 s to 100.00 s Increments of 0.01 s
Pickup delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01
V< faulty ph-gnd vltg. 0.300 V to 200.000 V Increments of 0.001 V
V> healthy ph-gnd. vltg. 0.300 V to 200.000 V Increments of 0.001 V

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms


Standard filter, true RMS Approx. 25 ms + OOT105 at 50 Hz
Approx. 22 ms + OOT at 60 Hz
2 cycle filters Approx. 45 ms + OOT at 50 Hz
Approx. 39 ms + OOT at 60 Hz
Dropout time
Standard filter, true RMS Approx. 20 ms + OOT at 50 Hz
Approx. 16.6 ms + OOT at 60 Hz
2 cycle filters Approx. 31.06 ms + OOT at 50 Hz
Approx. 27.06 ms + OOT at 60 Hz

Tolerances

Voltages 0.5 % of the setting value or 0.05 V


Time delays 1 % of the setting value or 10 ms

104 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
105 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1661


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

12.19.8 Non-Directional 3I0 Stage

Setting Values

Method of Measurement Fundamental component


RMS value
Threshold Protection-class For Iph-rated = 0.030 A to 35.000 A Increments of 0.001 A
value 3I0> current transformers 1 A
For Iph-rated = 0.15 A to 175.00 A Increments of 0.01 A
5A
For transformer type For Iph-rated = 0.001 A to 35.000 A Increments of 0.001 A
I-sensitive and 1A
IN-rated = 1 A For Iph-rated = 0.001 A to 175.000 A Increments of 0.001 A
5A
For transformer type For Iph-rated = 0.005 A to 35.000 A Increments of 0.001 A
I-sensitive and 1A
IN-rated = 5 A For Iph-rated = 0.005 A to 175.000 A Increments of 0.001 A
5A
Pickup delay 0.00 s to 60.00 s Increments of 0.01 s
Tripping delay 0.00 s to 100.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT106 at 50 Hz


Approx. 23 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 25 ms + OOT at 50 Hz
Approx. 22 ms + OOT at 60 Hz

12.19.9 Non-Directional Y0 Stage

Setting Values

V0> threshold value 0.300 V to 200.000 V Increments of 0.001 V


Threshold Y0> 0.10 mS to 100.00 mS Increments of 0.01 mS

106 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

1662 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

Pickup delay 0.00 s to 60.00 s Increments of 0.01 s


Operate delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT107 at 50 Hz


Approx. 29 ms + OOT at 60 Hz
Extension of operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 32 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz

Current Operating Range

Minimum 3I0 threshold Protection-class current 30 mA sec. (Irated = 1 A)


for Y0 calculation transformers
150 mA sec. (Irated = 5 A)
Sensitive current trans- 1 mA sec. (Irated = 1 A)
former
5 mA sec. (Irated = 5 A)

Tolerances

Admittance 1 % of the setting value or 0.05 mS (Irated = 1.6 A) or


0.25 mS (Irated = 8 A), (frated ± 10 %)

12.19.10Non-Directional 3I0 Harmonic Stage

Setting Values

3I0 harm. Protection-class For Iph-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A


threshold current transformers
For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A
For IN transformer type For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A
sensitive For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A
and IN-rated = 1 A
For IN transformer type For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A
sensitive For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A
and IN-rated = 5 A
3I0 harm. dropout ratio 0.10 to 0.95 Increments of 0.01
Pickup extension time 0.00 s to 60.00 s Increments of 0.01 s
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Stabilization counter 1 to 10 Increments of 1

107 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1663


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms and stabilization Approx. 70 ms + OOT108 at 50 Hz


counter = 4 Approx. 60 ms + OOT at 60 Hz
Dropout time Approx. 40 ms + OOT at 50 Hz
Approx. 30 ms + OOT at 60 Hz

Tolerances

Zero-sequence harmonic current 3I0harm. -3I0harm. via sensitive current transformer:


1 % of the setting value or 0.1 mA (Irated = 1.6 A)
or 0.5 mA (Irated = 8 A, frated ± 10 %)
-3I0harm. via protection-class current transformers:
1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A, frated ± 10 %)

12.19.11Pulse-Pattern Detection Stage

Setting Values

V0> threshold value 0.300 V to Increments of 0.001 V


200.000 V
3I0> threshold Protection-class For Iph-rated = 1 A 0.030 A to Increments of 0.001 A
value current trans- 35.000 A
formers For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A
For IN transformer For Iph-rated = 1 A 0.001 A to Increments of 0.001 A
type sensitive and 35.000 A
IN-rated = 1 A For Iph-rated = 5 A 0.001 A to Increments of 0.001 A
175.000 A
For IN transformer For Iph-rated = 1 A 0.005 A to Increments of 0.001 A
type sensitive and 35.000 A
IN-rated = 5 A For Iph-rated = 5 A 0.005 A to Increments of 0.001 A
175.000 A
3I0 delta pulse off-on 2 % to 50% Increments of 1 %
Pulse-on duration 0.20 s to 10.00 s Increments of 0.01 s
Pulse-off duration

108 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

1664 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.19 Sensitive Ground-Fault Detection

No. of pulses for operate 2 to 100 Increments of 1


Monitoring time(in pulses)
Max.tolera.pulse-on or off 0.02 s to 2.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.

Times

Operate delay = 0 ms Approx. 2.5 s + 0.3 s + OOT109 at 50 Hz and 60 Hz110


Dropout time Approx. 32 ms + OOT at 50 Hz and 60 Hz

109 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
110 After the first valid pulse is detected, the function picks up. For the typical settings 1.00 s of Pulse-on duration, 1.50 s of Pulse-off
duration, and 0.15 s of Max.tolera.pulse-on or off, the inherent pickup time is approx. 1 s + 1.5 s + 2 ⋅ 0.15 s + OOT

SIPROTEC 5, 7SJ82/7SJ85, Manual 1665


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.20 Undercurrent Protection

12.20 Undercurrent Protection


Setting Values

Method of measurement Fundamental component –


RMS value
Threshold value I< 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Pickup delay 0.00 s to 60.00 s Increments of 0.01 s
Operate delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time Approx. 25 ms + OOT111 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Dropout time Approx. 25 ms + OOT at 50 Hz
Approx. 22 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

111 OOT (Output Operating Time): additional delay of the output medium used, for example, 5 ms with fast relays, see chapter Relay
Outputs

1666 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.20 Undercurrent Protection

Tolerances

Currents, method of measurement = fundamental 1 % of setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
(33 % portion harmonic, referring to fundamental component)
Up to 30th harmonic 1 % of setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Time delays 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1667


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.21 Negative-Sequence Protection

12.21 Negative-Sequence Protection

12.21.1 Stage with Definite-Time Characteristic Curve

Setting Values

Reference value for I2 (Iref) Rated object current Irated, obj.


Positive-sequence current I1
Pickup value 5.0 % to 999.9 % l2/lref Increments of 0.1
Dropout ratio 0.40 to 0.99 Increments of 0.01
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Release current (minimum 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
current release) 5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Maximum phase current 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
(maximum current 5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
limiting)
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:

• Dropout differential derived from the parameter Dropout ratio

• Dropout differential of 3 % of the object rated current

Times

Pickup time Approx. 40 ms + OOT112 at 50 Hz


Approx. 35 ms + OOT at 60 Hz
Dropout time Approx. 35 ms + OOT

Current Operating Range

Current range At least one phase current ≥ setting value Irelease


All phase currents ≤ setting value Iph, max

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

112 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

1668 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.21 Negative-Sequence Protection

Tolerances

Pickup value
I2/Irated, obj Approx. 2 % of the setting value
or 0.8 % of the absolute value
I2/I1 Approx. 2 % of the setting value
or 4 % of the absolute value (I1 > 50 mA
(Irated = 1 A) or 250 mA (Irated = 5 A))
Time delays 1 % of the setting value or 10 ms

12.21.2 Stage with Inverse-Time Characteristic Curve

Setting Values

Reference value for I2 (Iref) Rated object current Irated,obj.


Positive-sequence current I1
Pickup value 5.0 % to 999.9 % l2/lref Increments of 0.1
Dropout Disk emulation
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
Release current (minimum 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
current release) 5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Maximum phase current 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
(maximum current 5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
limiting)
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:

• Dropout differential derived from the parameter Dropout ratio

• Dropout differential of 3 % of the object rated current

Times

Pickup time Approx. 40 ms + OOT113 at 50 Hz


Approx. 35 ms + OOT at 60 Hz
Dropout time Approx. 35 ms + OOT

Dropout Ratio

Disk emulation Approx. 0.90 ⋅ threshold value


Instantaneous Approx. 1.05 ⋅ threshold value
Approx. 0.95 ⋅ pickup value

113 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1669


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.21 Negative-Sequence Protection

Operate and Dropout Characteristic Curves


You can select from the following operate and dropout characteristic curves:

Table 12-6 Standard Characteristic Curves to IEC

Normal inverse: type A See chapter 12.5.2 Stage with Inverse-Time Charac-
Very inverse: type B teristic Curve, Figure 12-1
Extremely inverse: type C See chapter 12.5.2 Stage with Inverse-Time Charac-
Long-time inverse: type B teristic Curve, Figure 12-2

Table 12-7 Standard Characteristic Curves to ANSI

Inverse: type C See chapter 12.5.2 Stage with Inverse-Time Charac-


Short inverse teristic Curve, Figure 12-3
Long inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
Moderately inverse teristic Curve, Figure 12-4
Very inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
Extremely inverse teristic Curve, Figure 12-5
Definite inverse See chapter 12.5.2 Stage with Inverse-Time Charac-
teristic Curve, Figure 12-6

Extension of the Operating Time

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

Current Operating Range

Current range At least one phase current ≥ setting value Irelease


All phase currents ≤ setting value Iph, max

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Reference value = rated current


Pickup value Approx. 2 % of the setting value or
0.8 % of the absolute value
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the setting value or
+ 2 % of the current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the setting value or
+ 2 % of the current tolerance or 30 ms
Reference value = pos. seq. current
Pickup value Approx. 2 % of the setting value
or 4 % of the absolute value
(I1 > 50 mA (Irated = 1 A) or 250 mA (Irated = 5 A))

1670 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.21 Negative-Sequence Protection

Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+ 2 % current tolerance or 30 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1671


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.22 Directional Negative-Sequence Protection with Definite-Time Delay

12.22 Directional Negative-Sequence Protection with Definite-Time


Delay
Setting Values

Directional mode Forward, backward, non-directional


Stabilization with phase currents 0 % to 30 % Increments of 1 %

Threshold value (pickup value) at IN-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A


Threshold value (pickup value) at IN-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

Extension time of the blocking after a 1-pole pause 0.00 s to 60.00 s Increments of 0.01 s

Setting Values for Direction Determination

Minimum negative-sequence system voltage V2 0.150 V to 20.000 V Increments of 0.001 V


Minimum negative-sequence system For Irated = 1 A 0.030 A to 10.000 A Increments of 0.001 A
current I2
For Irated = 5 A 0.15 A to 50.00 A Increments of 0.01 A
Upper limit angle forward, β 0o to 360o Increments of 1o
Lower limit angle forward, α 0o to 360o Increments of 1o

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:

• Dropout differential derived from the parameter Dropout ratio

• Dropout differential of 3 % of the object rated current

Times

Operate time with time delay = 0 ms Approx. 40 ms + OOT114 at 50 Hz


Approx. 40 ms + OOT at 60 Hz
Dropout time Approx. 39 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Threshold values:
Negative-sequence voltage V2 1 % of the setting value or 0.5 V
Negative-sequence current I2 2 % of the setting value or 10 mA at Irated = 1 A
1 % of the setting value or 5 mA at Irated = 5 A
Times:
Independent time delays 1 % of the setting value or 10 ms

114 OOT (Output Operating Time) Additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

1672 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.22 Directional Negative-Sequence Protection with Definite-Time Delay

Limit angle in determining the direction 5o

SIPROTEC 5, 7SJ82/7SJ85, Manual 1673


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.23 Thermal Overload Protection, 3-Phase – Advanced

12.23 Thermal Overload Protection, 3-Phase – Advanced


Setting Value for the Function Block Filter

h(0) -100.000 to 100.000 Increments of 0.001


h(1) -100.000 to 100.000 Increments of 0.001
h(2) -100.000 to 100.000 Increments of 0.001
h(3) -100.000 to 100.000 Increments of 0.001
h(4) -100.000 to 100.000 Increments of 0.001

Setting Values/Increments for the Protection Stage

Threshold current 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


warning 5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold thermal warn. 50 % to 100 % Increments of 1 %
Dropout threshold operate 50 % to 99 % Increments of 1 %
Emerg. start T overtravel 0 s to 15 000 s Increments of 10 s
K-factor acc. to IEC 60225-149 0.10 to 4.00 Increments of 0.01
Thermal time constant 10 s to 60 000 s Increments of 1 s
Cooling time constant 10 s to 60 000 s Increments of 1 s
Imax thermal 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Imin cooling 1 A @ 50 and 100 Irated 0.000 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.00 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.000 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.000 A to 8.000 A Increments of 0.001 A
Temperature rise at Irated 40 K to 200 K Increments of 1 K
Default temperature -55°C to 55°C Increments of 1°C
Minimal temperature -55°C to 40°C Increments of 1°C

Dropout Ratios

Tripping threshold (fixed at 100 %) Dropout if value drops below operate indication
dropout threshold
Thermal warning threshold About 0.99 of the setting value
Current warning threshold About 0.95 of the setting value

Frequency Range of the Input Signals


The function captures input signals up to the 50th harmonic.

1674 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.23 Thermal Overload Protection, 3-Phase – Advanced

Tolerances

No filter applied
(33 % harmonics, in relation to the fundamental component)
With reference to k ⋅ Irated Up to 30th harmonic 2 % or 10 mA ( Irated = 1 A)
or 50 mA ( Irated = 5 A),
2 % class acc. to IEC 60255-149
Up to 50th harmonic, 4 % or 20 mA ( Irated = 1 A)
frated = 50 Hz or 100 mA ( Irated = 5 A),
4 % class acc. to IEC 60255-149
Up to 50th harmonic, 5 % or 25 mA ( Irated = 1 A)
frated = 60 Hz or 125 mA ( Irated = 5 A),
5 % class acc. to IEC 60255-149
With the filter for compensation of the amplitude attenuation due to the anti-aliasing filter
(33 % harmonics, in relation to the fundamental component)
With reference to k ⋅ Irated Up to 30th harmonic 2 % or 10 mA ( Irated = 1 A)
or 50 mA ( Irated = 5 A),
2 % class acc. to IEC 60255-149
Up to 50th harmonic, 3 % or 20 mA ( Irated = 1 A)
frated = 50 Hz or 100 mA ( Irated = 5 A),
3 % class acc. to IEC 60255-149
Up to 50th harmonic, 4 % or 20 mA ( Irated = 1 A)
frated = 60 Hz or 100 mA ( Irated = 5 A),
4 % class acc. to IEC 60255-149
With the filter for gain of harmonics including compensation of the amplitude attenuation115
(33 % harmonics, in relation to the fundamental component)
With reference to k ⋅ Irated Up to 30th harmonic 2 % or 10 mA ( Irated = 1 A)
or 50 mA ( Irated = 5 A),
2 % class acc. to IEC 60255-149116
Up to 50th harmonic, 4 % or 20 mA ( Irated = 1 A)
frated = 50 Hz or 100 mA ( Irated = 5 A),
4 % class acc. to IEC 60255-149117
Up to 50th harmonic, 5 % or 25 mA ( Irated = 1 A)
frated = 60 Hz or 125 mA ( Irated = 5 A),
5 % class acc. to IEC 60255-149117
With reference to the Up to 30th harmonic 3 % or 1 s for I/(k ⋅ Irated) > 1.25,
operate time 3 % class acc. to IEC 60255-149

115 In case that the filter response exactly matches the user-defined gain factor.
116 In case that the user-defined gain factor is set below 3. The tolerance is increased if the gain factor is larger.
117 In case that the user-defined gain factor is set below 7. The tolerance is increased if the gain factor is larger.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1675


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.23 Thermal Overload Protection, 3-Phase – Advanced

Operate Curve

Operate curve

Where t Operate time


τth Time constant
I Current load current
Ipreload Preload current
k Setting factor according to VDE 0435 part 3011 or
IEC 60255-149 (K factor)
Irated, obj Rated current of the protected object

1676 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.23 Thermal Overload Protection, 3-Phase – Advanced

[dwauslke-100611-01.tif, 1, en_US]

Figure 12-16 Operate Curve of Overload Protection

SIPROTEC 5, 7SJ82/7SJ85, Manual 1677


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.24 Thermal Overload Protection, User-Defined Characteristic Curve

12.24 Thermal Overload Protection, User-Defined Characteristic Curve


Setting Values

Threshold current 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


warning 5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold thermal warn. 50 % to 100 % Increments of 1 %
Dropout threshold operate 50 % to 99 % Increments of 1 %
Emerg. start T overtravel 0 s to 15 000 s Increments of 10 s
Imax thermal 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Imin cooling 1 A @ 50 and 100 Irated 0.000 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.00 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.000 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.000 A to 8.000 A Increments of 0.001 A
Curve based on preload 1 % to 100 % Increments of 1 %
Number of value pairs for the operate curve 2 to 30 Increments of 1
X values of the operate curve 1.10 p.u. to 20.00 p. u. Increments of 0.0 p.u.
Y values of the operate curve 1.00 s to 20 000.00 s Increments of 0.01 s

Dropout Ratios

Tripping threshold (fixed at 100 %) Dropout if value drops below operate indication
dropout threshold
Thermal warning threshold About 0.99 of the setting value
Current warning threshold About 0.95 of the setting value

Frequency Range of the Input Signals


The function captures input signals up to the 50th harmonic.

Tolerances

With reference to k ⋅ Irated For Irated = 1 A 2 % or 10 mA, class 2 % acc. to IEC 60255-149
For Irated = 5 A 2 % or 50 mA, class 2 % acc. to IEC 60255-149
With reference to operate time 3 % or 1 s, class 3 % acc. to IEC 60255-149
for I/(k ⋅ Irated) > 1.25

1678 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.25 Thermal Overload Protection, 1-Phase

12.25 Thermal Overload Protection, 1-Phase


Setting Values/Increments for the Protection Stage

Threshold current 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


warning 5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold thermal warn. 50 % to 100 % Increments of 1 %
Dropout threshold operate 50 % to 99 % Increments of 1 %
K-factor acc. to IEC 60225-149 0.10 to 4.00 Increments of 0.01
Thermal time constant 10 s to 60 000 s Increments of 1 s
Imax thermal 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Temperature rise at Irated 40 K to 200 K Increments of 1 K
Default temperature -55°C to 55°C Increments of 1°C
Minimal temperature -55°C to 40°C Increments of 1°C

Dropout Ratios

Tripping threshold (fixed at 100 %) Dropout if value drops below operate indication
dropout threshold
Thermal warning threshold About 0.99 of the setting value
Current warning threshold About 0.95 of the setting value

Frequency Range of the Input Signals


The function captures input signals up to the 50th harmonic.

Tolerances

With reference to k ⋅ Irated Up to 30th harmonic 2 % or 10 mA ( Irated = 1 A)


or 50 mA ( Irated = 5 A),
2 % class acc. to IEC 60255-149
Up to 50th harmonic, 4 % or 20 mA ( Irated = 1 A)
frated = 50 Hz or 100 mA ( Irated = 5 A),
4 % class acc. to IEC 60255-149
Up to 50th harmonic, 5 % or 25 mA ( Irated = 1 A)
frated = 60 Hz or 125 mA ( Irated = 5 A),
5 % class acc. to IEC 60255-149
With reference to the Up to 30th harmonic 3 % or 1 s for I/(k ⋅ Irated) > 1.25,
operate time 3 % class acc. to IEC 60255-149

SIPROTEC 5, 7SJ82/7SJ85, Manual 1679


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.25 Thermal Overload Protection, 1-Phase

Operate Curve

Operate curve

Where t Operate time


τth Time constant
I Current load current
Ipreload Preload current
k Setting factor according to VDE 0435 part 3011 or
IEC 60255-8 (K factor)
Irated, obj Rated current of the protected object

1680 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.25 Thermal Overload Protection, 1-Phase

[dwauslke-100611-01.tif, 1, en_US]

Figure 12-17 Operate Curve of Overload Protection

SIPROTEC 5, 7SJ82/7SJ85, Manual 1681


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.26 Unbalanced-Load Protection

12.26 Unbalanced-Load Protection


Setting Values

Maximum continuously perm. I2 3.0 % to 30.0 % l2/ Increments of 0.1 %


lrated,machine
Unbalanced load factor K 1.0 s to 100.0 s Increments of 0.1 s
Warning delay 0.0 s to 60.0 s; ∞ Increments of 0.1 s
Cooling time thermal replica 0 s to 50 000 s Increments of 1 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:

• Dropout differential derived from a dropout ratio of 95 %

• Dropout differential of 3 % of the object rated current

Operate Characteristics

Characteristic of the
thermal replica

Where: tI2Perm Permissible application time of the negative-sequence


current
K Unbalanced load factor K
I2/Irated,machine Unbalanced load (negative-sequence current/rated
current of the machine)

[dwunbaop-300913, 1, en_US]

Figure 12-18 Thermal Characteristic for Unbalanced Load Protection

1682 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.26 Unbalanced-Load Protection

Times

Pickup time of the warning stage Approx. 60 ms + OOT118 at 50 Hz


Approx. 50 ms + OOT at 60 Hz
Dropout time Approx. 50 ms or better

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Negative-sequence current I2 Approx. 3 % of setting value or 0.030 A at Irated = 1 A


Approx. 3 % of setting value or 0.150 A at Irated = 5 A
Warning delay 1 % of the setting value or 10 ms
Time for 2 ≤ I2/I2Perm ≤ 20 5 % of reference (calculated) value or 100 ms ±
(1 % current tolerance or 10 mA) at Irated = 1 A
5 % of reference (calculated) value or 100 ms ±
(1 % current tolerance or 50 mA) at Irated = 5 A

Influencing Variables for the Thresholds

Harmonics
– Up to 10 % 3rd harmonic ≤1%
– Up to 10 % 5th harmonic ≤1%

118 OOT (Output Operating Time): additional delay of the output medium used, for example, 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1683


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

12.27 Overcurrent Protection for Capacitor Banks

12.27.1 Stage with Definite-Time Characteristic Curve

Setting Value for the Function Block Filter

h(0) -100.000 to 100.000 Increments of 0.001


h(1) -100.000 to 100.000 Increments of 0.001
h(2) -100.000 to 100.000 Increments of 0.001
h(3) -100.000 to 100.000 Increments of 0.001
h(4) -100.000 to 100.000 Increments of 0.001

Setting Values for Protection Stage

Method of measurement Fundamental component –


RMS value
Threshold value119 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout ratio 0.90 to 0.99 Increments of 0.01
Operate delay 0.00 s to 100.00 s Increments of 0.01 s
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s
Pickup delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT 120 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Extension of the operate time during operation with Approx. 10 ms
transformer inrush-current detection
Dropout time Approx. 20 ms + OOT

119 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
120 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

1684 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value, no filter applied
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the compensation of the amplitude attenuation due to the anti-aliasing filter
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 2 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the gain of harmonics (including compensation of the amplitude attenuation121
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1.5 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %) 122
Up to 50th harmonic, frated = 50 Hz 3% of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 123
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 124
Time delays 1 % of the setting value or 10 ms

121 In case that the filter response exactly matches the user-defined gain factors
122 In case that the user-defined gain factor is set below 3. The tolerance increases, if the gain factor is larger.
123 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
124 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1685


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.27.2 Stage with Inverse-Time Characteristic Curve

Setting Value for the Function Block Filter

h(0) -100.000 to 100.000 Increments of 0.001


h(1) -100.000 to 100.000 Increments of 0.001
h(2) -100.000 to 100.000 Increments of 0.001
h(3) -100.000 to 100.000 Increments of 0.001
h(4) -100.000 to 100.000 Increments of 0.001

Setting Values for Protection Stage

Method of measurement Fundamental component –


RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.00 to 15.00 Increments of 0.01
Pickup delay 0.00 s to 60.00 s Increments of 0.01 s
Minimum time of the curve 0.00 s to 1.00 s Increments of 0.01 s
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Operate Curves and Dropout-Time Characteristic Curves according to IEC

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

1686 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

[dwocpki1-080213-01.tif, 1, en_US]

Figure 12-19 Operate Curves and Dropout-Time Characteristic Curves According to IEC

SIPROTEC 5, 7SJ82/7SJ85, Manual 1687


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

[dwocpki2-080213-01.tif, 1, en_US]

Figure 12-20 Operate Curves and Dropout-Time Characteristic Curves According to IEC

1688 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

[dwocpka1-080213-01.tif, 2, en_US]

Figure 12-21 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

SIPROTEC 5, 7SJ82/7SJ85, Manual 1689


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

[dwocpka2-080213-01.tif, 2, en_US]

Figure 12-22 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

1690 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

[dwocpka3-080213-01.tif, 2, en_US]

Figure 12-23 Tripping Characteristic Curves and Dropout Characteristic Curves According to ANSI/IEEE

SIPROTEC 5, 7SJ82/7SJ85, Manual 1691


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

[dwocpka4-080213-01.tif, 2, en_US]

Figure 12-24 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value, no filter applied
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the compensation of the amplitude attenuation due to the anti-aliasing filter
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)

1692 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

Up to 50th harmonic, frated = 50 Hz 2 % of the setting value or 10 mA (Irated = 1 A)


or 50 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the gain of harmonics (including compensation of the amplitude attenuation125
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1.5 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %) 126
Up to 50th harmonic, frated = 50 Hz 3% of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 127
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 128
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

12.27.3 Stage with User-Defined Characteristic Curve

Setting Value for the Function Block Filter

h(0) -100.000 to 100.000 Increments of 0.001


h(1) -100.000 to 100.000 Increments of 0.001
h(2) -100.000 to 100.000 Increments of 0.001
h(3) -100.000 to 100.000 Increments of 0.001
h(4) -100.000 to 100.000 Increments of 0.001

Setting Values for Protection Stage

Method of measurement Fundamental component –


RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

125 In case that the filter response exactly matches the user-defined gain factors
126 In case that the user-defined gain factor is set below 3. The tolerance increases, if the gain factor is larger.
127 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
128 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1693


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

Absolute pickup value 1 A @ 50 and 100 Irated 0.000 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.00 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.000 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.000 A to 8.000 A Increments of 0.001 A
Dropout Disk emulation –
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
Number of value pairs for the operate curve 2 to 30 Increments of 1
X values of the operate curve 1.00 p.u. to 20.00 p.u. Increments of 0.01 p.u.
Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 s
Number of value pairs for the dropout characteristic 2 to 30 Increments of 1
curve
X values of the dropout characteristic curve 0.05 p.u. to 0.95 p.u. Increments of 0.01 p.u.
Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value or 95 % of the absolute
pickup value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Reset of the Integration Timer

Instantaneous With dropout


Disk emulation Approx. < 0.90 ⋅ threshold value

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents, method of measurement = fundamental 1 % of the setting value or 5 mA (Irated = 1 A)


component or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value, no filter applied
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)

1694 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.27 Overcurrent Protection for Capacitor Banks

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)


or 100 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the compensation of the amplitude attenuation due to the anti-aliasing filter
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 50 Hz 2 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %)
Up to 50th harmonic, frated = 60 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %)
Currents, method of measurement = RMS value
with filter for the gain of harmonics (including compensation of the amplitude attenuation129
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1.5 % of the setting value or 10 mA (Irated = 1 A)
or 50 mA (Irated = 5 A), (frated ± 10 %) 130
Up to 50th harmonic, frated = 50 Hz 3% of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 131
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated ± 10 %) 132
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = < 5 %


fundamental component, for τ > 100 ms (with
complete unbalance)

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation with Approx. 10 ms


transformer inrush-current detection

129 In case that the filter response exactly matches the user-defined gain factors
130 In case that the user-defined gain factor is set below 3. The tolerance increases, if the gain factor is larger.
131 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
132 In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1695


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.28 Current-Unbalance Protection for Capacitors, 3-Phase

12.28 Current-Unbalance Protection for Capacitors, 3-Phase


Setting Values for the Function

Automatic compensation Yes


No
Time between switch off and switch on 0.00 s to 60.00 s Increments of 0.01 s
Normalization with Ic Yes
No
Threshold of defective C- 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
element 5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Setting Values (Overcurrent-Protection Stage I>)

Measured value compensated


non-compensated
Iunbal. 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
Iunbal. 1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Operate delay 0.00 s to 60.00 s Increments of 0.01 s

Setting Values (Counter Stage)

Type of counting groups segregated


sum
Max. no. of def. elem. phs A 1 to 1000 Increments of 1
Max. no. of def. elem. phs B 1 to 1000 Increments of 1
Max. no. of def. elem. phs C 1 to 1000 Increments of 1
Operate delay 0.00 s to 10000.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

1696 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.28 Current-Unbalance Protection for Capacitors, 3-Phase

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT133 at 50 Hz


Approx. 29 ms + OOT at 60 Hz
Dropout time Approx. 32 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents Ic, Iunbal. 1 % of the setting value or 5 mA (Irated = 1 A)


Protection-class current transformers or 25 mA (Irated = 5 A), (frated ± 10 %)
Currents Iunbal. 1 % of the setting value or 0.1 mA (Irated = 1.6 A)
Sensitive current transformer or 0.5 mA (Irated = 8 A), (frated ± 10 %)
Time delays 1 % of the setting value or 10 ms

133 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1697


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.29 Current-Unbalance Protection for Capacitors, 1-Phase

12.29 Current-Unbalance Protection for Capacitors, 1-Phase


Setting Values for the Function

Automatic compensation Yes


No
Time between switch off and switch on 0.00 s to 60.00 s Increments of 0.01 s
Normalization with Ic Yes
No
Threshold of defective C- 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
element 5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Setting Values (Overcurrent-Protection Stage I>)

Current threshold Iunbal. 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.150 A to 175.000 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.005 A
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Measured value compensated
non-compensated

Setting Values (Counter Stage)

Type of counting groups segregated


sum
Type of counting phases segregated
sum
Max. no. of def. elem. phs A 1 to 1000 Increments of 1
Max. no. of def. elem. phs B 1 to 1000 Increments of 1
Max. no. of def. elem. phs C 1 to 1000 Increments of 1
Max. no. of def. elem. 1 to 1000 Increments of 1
Operate delay 0.00 s to 10000.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

1698 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.29 Current-Unbalance Protection for Capacitors, 1-Phase

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT134 at 50 Hz


Approx. 29 ms + OOT at 60 Hz
Dropout time Approx. 32 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Currents Ic, Iunbal. 1 % of the setting value or 5 mA (Irated = 1 A)


Protection-class current transformers or 25 mA (Irated = 5 A), (frated ± 10%)
Currents Iunbal. 1 % of the setting value or 0.1 mA (Irated = 1.6 A)
Sensitive current transformer or 0.5 mA (Irated = 8 A), (frated ± 10%)
Time delays 1 % of the setting value or 10 ms

134 OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1699


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.30 Voltage-Differential Protection for Capacitors

12.30 Voltage-Differential Protection for Capacitors


Setting Values (General Functionality)

Matching-factor setting not phase-selective


phase-selective
Voltage matching factor k 0.5000 to 2000.0000 Increments of 0.0001

Setting Values (Protection Stage Vdiff>)

Threshold 0.005 p.u. to 1.000 Increments of 0.001 p.u.


p.u.135
Operate delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

Dropout ratio for sec. threshold > 3 V 95 %


Dropout differential for sec. threshold 0.3 V to 3 V 150 mV
Dropout ratio for sec. threshold 0.2 V to 0.3 V 50 %

Times

Operate time with time delay = 0 ms Approx. 30 ms + OOT (Output Operating Time)
at 50 Hz
Approx. 27 ms + OOT (Output Operating Time)
at 60 Hz
Dropout time Approx. 20 ms + OOT (Output Operating Time)
at 50 Hz
Approx. 18 ms + OOT (Output Operating Time)
at 60 Hz

Tolerances

Threshold ≥ 0.2 V 1 % of the setting value or 0.05 V (compensated)


Time delays 1 % of the setting value or 10 ms

Operating Range of the Secondary Differential Voltage

Operating Range of the secondary differential voltage ≥ 0.1 V (compensated)

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

135 Minimum secondary setting threshold = 0.2 V

1700 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.31 Differential Protection for Capacitor Banks

12.31 Differential Protection for Capacitor Banks


Setting Values

Operate curve
Threshold value I/Irated,obj 0.05 to 2.00 Increments of 0.01
Slope 1 0.00 to 0.80 Increments of 0.01
Intersection 1 Irest I/Irated,obj 0.00 to 5.00 Increments of 0.01
Slope 2 0.25 to 0.95 Increments of 0.01
Intersection 2 Irest I/Irated,obj 1.00 to 20.00 Increments of 0.01
Startup detection
Startup detection I/Irated,obj 0.1 to 2.0 Increments of 0.1
threshold value
Characteristic curve increase factor 1.0 to 5.0 Increments of 0.1
Maximum starting time 0.1 s to 180.0 s Increments of 0.1 s
DC-component detection
Characteristic curve increase factor 1.0 to 5.0 Increments of 0.1
DC
Inrush-current detection
2nd harmonic content 10 % to 45 % Increments of 1 %
Crossblk. time 2nd har. 0.00 s to 200.00 s or ∞ Increments of 0.01 s
Detection of external faults
Add-on stabilization threshold value I/Irated,obj 1.00 to 20.00 Increments of 0.01
Add-on stabilization time 0.00 s to 5.00 s or ∞ Increments of 0.01 s
Crossblk. time additional stabilization 0.00 s to 2.00 s or ∞ Increments of 0.01 s
Operate curve See figure Figure 12-25

I-DIFF Fast

Threshold value I/Irated,obj 0.5 to 35.0 Increments of 0.1


Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

I-DIFF Unrestrained

Threshold value I/Irated,obj 0.5 to 35.0 Increments of 0.1


Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout Ratio

I-DIFF stage Approx. 0.7


I-DIFF fast stage Approx. 0.8
I-DIFF unrestrained stage Approx. 0.7

Response Tolerance

For preset characteristic curve parameters; for 2 sides with 1 measuring point each
I-DIFF stage and characteristic curve 2 % of the setting value
I-DIFF fast stage 2 % of the setting value

SIPROTEC 5, 7SJ82/7SJ85, Manual 1701


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.31 Differential Protection for Capacitor Banks

Time Delays

I-DIFF stage 0.00 s to 60.00 s Increments of 0.01 s


I-DIFF fast stage 0.00 s to 60.00 s Increments of 0.01 s
Timer tolerance 1 % of the setting value or 10 ms

[dwdifaus-030912-01.tif, 2, en_US]

Figure 12-25 Operate Curve of the Differential Protection

Operate Times

Operate times for one-sided supply


I-DIFF stage, min 50 Hz 23 ms + OOT136
60 Hz 20 ms + OOT1)
I-DIFF fast stage, min 50 Hz 8 ms + OOT1)
60 Hz 8 ms + OOT1)
I-DIFF unrestrained stage, min 50 Hz 8 ms + OOT1)
60 Hz 8 ms + OOT1)
Dropout time, approx. 50 Hz 29 ms
60 Hz 26 ms

136 Refer to protection functions, for example overcurrent protection

1702 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.31 Differential Protection for Capacitor Banks

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

SIPROTEC 5, 7SJ82/7SJ85, Manual 1703


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.32 Overvoltage Protection with 3-Phase Voltage

12.32 Overvoltage Protection with 3-Phase Voltage


Setting Values for the Function

Stabilization counter 0 to 10 Increments of 1

Setting Values for Stage Type Definite-Time Overvoltage Protection

Measured value Phase-to-phase


Phase-to-ground
Method of measurement Fundamental component
RMS value
Pickup mode 1 out of 3
3 out of 3
Pickup value137 0.300 V to 340.000 V Increments of 0.001 V
Time delay 0.00 s to 300.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01

Setting Values for Stage Type Inverse-Time Overvoltage Protection

Measured value Phase-to-phase


Phase-to-ground
Method of measurement Fundamental component
RMS value
Pickup mode 1 out of 3
3 out of 3
Pickup value 0.300 V to 340.000 V Increments of 0.001 V
Pickup factor 1.00 to 1.20 Increments of 0.01
Characteristic constant k 0.00 to 300.00 Increments of 0.01
Characteristic constant α 0.010 to 5.000 Increments of 0.001
Characteristic constant c 0.000 to 5.000 Increments of 0.001
Time multiplier 0.05 to 15.00 Increments of 0.01
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s
Reset time 0.00 s to 60.00 s Increments of 0.01 s

Operate Curve for Stage Type Inverse-Time Overvoltage Protection

Where
Top Operate delay
Tinv Inverse-time delay
Tadd Additional time delay (parameter Additional time delay)

137 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.

1704 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.32 Overvoltage Protection with 3-Phase Voltage

Where
Tinv Inverse-time delay
Tp Time multiplier (parameter Time dial)
V Measured voltage
Vthresh Threshold value (parameter Threshold)
k Curve constant k (parameter Charact. constant k)
α Curve constant α (parameter Charact. constant α)
c Curve constant c (parameter Charact. constant c)

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms, typical Approx. 25 ms + OOT138 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Operate time with time delay = 0 ms, maximum Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances for Stage Type Definite-Time Overvoltage Protection

Voltages 0.5 % of the setting value or 0.05 V


Time delays 1 % of the setting value or 10 ms

Tolerances for Stage Type Inverse-Time Overvoltage Protection

Voltages 0.5 % of the setting value or 0.05 V


Operate time for 5 % of the setting value or 30 ms
1.2 ≤ V/V threshold value ≤ 20
Reset time delay 1 % of the setting value or 10 ms

138 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1705


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.33 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

12.33 Overvoltage Protection with Zero-Sequence Voltage/Residual


Voltage
Setting Values

Method of measurement RMS value


Fundamental component
Fundamental component
over 2 cycle filters
Block. on measuring-voltage outage Yes
No
Determ. ph. aff. by grd. flt. Yes
No
Threshold value139 0.300 V to 340.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Pickup delay 0.00 s to 320.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01
V< faulty ph-gnd vltg. 0.300 V to 200.000 V Increments of 0.001 V
V> healthy ph-gnd. vltg. 0.300 V to 200.000 V Increments of 0.001 V

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms


Standard filter, true RMS, typical Approx. 25 ms + OOT140 at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Standard filter, true RMS, maximum Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
2 cycle filters, typical Approx. 40 ms + OOT at 50 Hz
Approx. 35 ms + OOT at 60 Hz
2 cycle filters, maximum Approx. 45 ms + OOT at 50 Hz
Approx. 40 ms + OOT at 60 Hz
Dropout time
Standard filter, true RMS, typical Approx. 20 ms + OOT at 50 Hz
Approx. 17 ms + OOT at 60 Hz
Standard filter, true RMS, maximum Approx. 25 ms + OOT at 50 Hz
Approx. 20 ms + OOT at 60 Hz
2 cycle filters, typical Approx. 30 ms + OOT at 50 Hz
Approx. 25 ms + OOT at 60 Hz

139 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
140 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

1706 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.33 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

2 cycle filters, maximum Approx. 35 ms + OOT at 50 Hz


Approx. 30 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Voltages 0.5 % of the setting value or 0.05 V


Time delays 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1707


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.34 Overvoltage Protection with Positive-Sequence Voltage

12.34 Overvoltage Protection with Positive-Sequence Voltage


Setting Values

Pickup value 0.300 V to 200.000 V Increments of 0.001 V


Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms, typical Approx. 25 ms + OOT141 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Operate time with time delay = 0 ms, maximum Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Voltages 0.5 % of the setting value or 0.05 V


Time delays 1 % of the setting value or 10 ms

141 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

1708 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.35 Overvoltage Protection with Negative-Sequence Voltage

12.35 Overvoltage Protection with Negative-Sequence Voltage


Setting Values for the Function

Measuring window 1 cycle to 10 cycles Increments of 1 cycle

Setting Values

Pickup value of V2 0.300 V to 200.000 V Increments of 0.001 V


Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Pickup times 55 ms to 210 ms + OOT 142


(depends on the measuring-window length) at 50 Hz
48 ms to 185 ms + OOT
(depends on the measuring-window length) at 60 Hz
Dropout time 20 ms to 70 ms + OOT
(depends on the measuring-window length)

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Voltages 0.50 % of the setting value or 0.050 V


Time delays 1.00 % of the setting value or 10 ms

142 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1709


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.36 Overvoltage Protection with Any Voltage

12.36 Overvoltage Protection with Any Voltage


Setting Values

Measured value143 Measured phase-to-ground voltage VA


Measured phase-to-ground voltage VB
Measured phase-to-ground voltage VC
Measured phase-to-phase voltage VAB
Measured phase-to-phase voltage VBC
Measured phase-to-phase voltage VCA
Measured phase-to-phase voltage VAB
Measured phase-to-phase voltage VBC
Measured phase-to-phase voltage VCA
Calculated voltage V0
Method of measurement Fundamental component
RMS value
Pickup value144 0.300 V to 340.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms, typical Approx. 25 ms + OOT145 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Operate time with time delay = 0 ms, maximum Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

143 If the function Overvoltage protection with any voltage is used in a 1-phase function group, the measured-value parameter is not
visible.
144 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
145 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

1710 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.36 Overvoltage Protection with Any Voltage

Tolerances

Voltages 0.5 % of the setting value or 0.05 V


Time delays 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1711


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.37 Peak Overvoltage Protection for Capacitors

12.37 Peak Overvoltage Protection for Capacitors


Setting Values

Threshold value
Inverse-time stage 0.80 to 3.00 p.u. Increments of 0.01
Definite-time stage 0.80 to 10.00 p.u. Increments of 0.01
User-defined characteristic curve 0.80 to 3.00 p.u. Increments of 0.01
Tripping delay 0.01 s to 3600.00 s Increments of 0.01 s
Dropout delay 0.00 s to 3600.00 s Increments of 1.00 s
Down integration time 1 min to 1500 min Increments of 1 min
Time multiplier 0.05 to 15.00 Increments of 0.01
Number of value pairs for the operate curve 30 Increments of 1
X values of the operate curve 1.00 p.u. to 4.00 p.u. Increments of 0.01 p.u.
Y values of the operate curve 0.00 s to 9999.99 s Increments of 0.01 s
Number of value pairs for the dropout characteristic 30 Increments of 1
curve
X values of the dropout characteristic curve 0.01 p.u. to 0.95 p.u. Increments of 0.01 p.u.
Y values of the dropout characteristic curve 0.00 s to 9999.99 s Increments of 0.01 s

Inverse-Time Characteristic Curve (IEC/IEEE)

[dw_pecinv-230813, 2, en_US]

Figure 12-26 Inverse-Time Characteristic Curve

The points on the characteristic curve defined in the standards result from a threshold setting of 1.1. These
single points are connected via semi-logarithmic line segments.

1712 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.37 Peak Overvoltage Protection for Capacitors

Table 12-8 Peak Overvoltage Inverse-Time Characteristic (for Threshold Setting 1.1)

Measurand Û/Vc,rated Time Delay Curve Point According to


<1.15 ∞ (no pickup) Siemens definition
1.15 1800.00 s IEC 60871-1:2005
1.2 300.00 s IEC 60871-1:2005
1.3 60.00 s IEC 60871-1:2005, IEEE Std 1036-2010
1.4 15.00 s IEEE Std 1036-2010
1.7 1.00 s IEEE Std 1036-2010
2 0.25 s IEEE Std 1036-2010
2.2 0.1 s IEEE Std 1036-2010
>2.2 0.01 s IEEE Std 1036-2010

Times

Pickup time Approx. 35 ms + OOT at 50 Hz1


Approx. 25 ms + OOT at 60 Hz1
Dropout Time Depending on settings
1 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast
relays

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Peak overvoltage
(33 % harmonics, with reference to fundamental component)
Up to 30th harmonic 1 % of the setting value or 0.005 p.u. (frated ± 10%)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 0.02 p.u. (frated ± 10%)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 0.02 p.u. (frated ± 10%)
Time delays
Measured value of definite-time stage 1 % of the setting value or 10 ms
Measured value of inverse-time stage and stage with 5 % of the setting value +1 % of the measured value
user-defined characteristic curve or 30 ms
Down integration time 5 % of the setting value or 30 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1713


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.38 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage

12.38 Overvoltage Protection with Negative-Sequence Voltage/Positive-


Sequence Voltage
Setting Values for the Function

Measuring window 1 cycle to 10 cycles Increments of 1 cycle


Minimum voltage V1 0.300 V to 60.000 V Increments of 0.001 V

Setting Values for Stage Types

Pickup value of V2/V1 0.50 % to 100.00 % Increments of 0.01 %


Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Pickup times 55 ms to 210 ms + OOT146


(depends on the measuring-window length) at 50 Hz
48 ms to 190 ms + OOT
(depends on the measuring-window length) at 60 Hz
Dropout times 22 ms to 55 ms + OOT
(depends on the measuring-window length) at 50 Hz
18 ms to 45 ms + OOT
(depends on the measuring-window length) at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Voltages 0.50 % of the setting value or 0.050 V


Time delays 1.00 % of the setting value or 10 ms

146 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

1714 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.39 Undervoltage Protection with 3-Phase Voltage

12.39 Undervoltage Protection with 3-Phase Voltage


Setting Values for the Function

Stabilization counter 0 to 10 Increments of 1

Setting Values for Stage Type Definite-Time Undervoltage Protection

Measured value Phase-to-phase


Phase-to-ground
Method of measurement Fundamental component
RMS value
Current-flow criterion On
Off
Threshold value I> 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold value147 0.300 V to 175.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 1.01 to 1.20 Increments of 0.01

Setting Values for Stage Type Inverse-Time Undervoltage Protection

Measured value Phase-to-phase


Phase-to-ground
Method of measurement Fundamental component
RMS value
Current-flow criterion On
Off
Threshold value I> 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold 0.300 V to 175.000 V Increments of 0.001 V
Pickup factor 0.80 to 1.00 Increments of 0.01
Characteristic constant k 0.00 to 300.00 Increments of 0.01
Characteristic constant α 0.010 to 5.000 Increments of 0.001
Characteristic constant c 0.000 to 5.000 Increments of 0.001
Time multiplier 0.05 to 15.00 Increments of 0.01
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s
Reset time 0.00 s to 60.00 s Increments of 0.01 s

Operate Curve

Top=TInv+Tadd
Where:
Top Operate delay
TInv Inverse-time delay

147 If you have selected the Method of measurement = RMS value, do not set the threshold value under 10 V.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1715


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.39 Undervoltage Protection with 3-Phase Voltage

Tadd Additional time delay (parameter Additional time delay)

[fo_UVP3ph_inverse, 2, en_US]

Where
TInv Inverse-time delay
Tp Time multiplier (parameter Time dial)
V Measured undervoltage
VThresh Threshold value (parameter Threshold)
k Curve constant k (parameter Charact. constant k)
α Curve constant α (parameter Charact. constant α)
c Curve constant c (parameter Charact. constant c)

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms, typical Approx. 25 ms + OOT148 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Operate time with time delay = 0 ms, maximum Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive, maintained;
f > 90 Hz Dropout of the pickup induced by blocking or by
increasing the measurand beyond the dropout
threshold

148 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

1716 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.39 Undervoltage Protection with 3-Phase Voltage

Tolerances for Stage Type Definite-Time Undervoltage Protection

Voltages 0.5 % of the setting value or 0.05 V


Currents 1 % of the setting value or 5 mA (Irated = 1 A) or 25 mA
(Irated = 5 A, frated ± 10 %), valid for protection-class
current transformers
1 % of the setting value or 0.1 mA (Irated = 1.6 A) or
0.5 mA (Irated = 8 A, frated ± 10 %), valid for instrument
transformers
Time delays 1 % of the setting value or 10 ms

Tolerances for Stage Type Inverse-Time Undervoltage Protection

Voltages 0.5 % of the setting value or 0.05 V


Currents 1 % of the setting value or 5 mA (Irated = 1 A) or 25 mA
(Irated = 5 A, frated ± 10 %), valid for protection-class
current transformers
1 % of the setting value or 0.1 mA (Irated = 1.6 A) or
0.5 mA (Irated = 8 A, frated ± 10 %), valid for instrument
transformers
Operate time for 0 < V/VThresh < 0.9 5 % of the setting value or 30 ms
Reset time delay 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1717


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.40 Undervoltage Protection with Positive-Sequence Voltage

12.40 Undervoltage Protection with Positive-Sequence Voltage


Setting Values

Threshold value 0.300 V to 200.000 V Increments of 0.001 V


Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 1.01 to 1.20 Increments of 0.01
Current-flow criterion On
Off
Threshold value I> 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms, typical Approx. 25 ms + OOT149 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Operate time with time delay = 0 ms, maximum Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive, maintained;
f > 90 Hz Dropout of the pickup induced by blocking or by
increasing the measurand beyond the dropout
threshold

149 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

1718 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.40 Undervoltage Protection with Positive-Sequence Voltage

Tolerances

Voltages 0.5 % of the setting value or 0.05 V


Currents 1 % of the setting value or 5 mA (Irated = 1 A) or
25 mA (Irated = 5 A, frated ± 10 %),
valid for protection-class current transformers
1 % of the setting value or 0.1 mA (Irated = 1.6 A) or
0.5 mA (Irated = 8 A, frated ± 10 %),
valid for instrument transformers
Time delays 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1719


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.41 Undervoltage Protection with Any Voltage

12.41 Undervoltage Protection with Any Voltage


Setting Values

Measured value Measured phase-to-ground voltage VA


Measured phase-to-ground voltage VB
Measured phase-to-ground voltage VC
Measured phase-to-phase voltage VAB
Measured phase-to-phase voltage VBC
Measured phase-to-phase voltage VCA
Calculated phase-to-phase voltage VAB
Calculated phase-to-phase voltage VBC
Calculated phase-to-phase voltage VCA
Calculated voltage V0
Method of measurement Fundamental component
RMS value
Threshold value150 0.300 V to 340.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 1.01 to 1.20 Increments of 0.01

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.

Times

Operate time with time delay = 0 ms, typical Approx. 25 ms + OOT151 at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Operate time with time delay = 0 ms, maximum Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive, maintained;
f > 90 Hz Dropout of the pickup induced by blocking or by increasing the
measurand beyond the dropout threshold

150 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
151 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

1720 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.41 Undervoltage Protection with Any Voltage

Tolerances

Voltages 0.5 % of the setting value or 0.05 V


Time delays 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1721


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.42 Overfrequency Protection

12.42 Overfrequency Protection


Setting Values

Pickup values f> 40.00 Hz to 70.00 Hz Increments of 0.01 Hz


Dropout differential 20 mHz to 2 000 mHz Increments of 10 mHz
Time delay T 0.00 s to 600.00 s Increments of 0.01 s
Minimum voltage 3.000 V to 175.000 V Increments of 0.001 V

Times

Pickup times f> Angle difference method


50 Hz Approx. 70 ms + OOT152
60 Hz Approx. 60 ms + OOT
Filtering method
50 Hz Approx. 79 ms + OOT
60 Hz Approx. 65 ms + OOT
Dropout times f> 60 ms to 80 ms

Dropout

Frequency Parameterizable dropout differential


Minimum voltage
The larger dropout differential (= | pickup value – dropout threshold |) of the following
2 criteria is used:
Dropout differential derived from Dropout ratio 105 % for the Minimum voltage parameter
Minimum absolute dropout differential 150 mV secondary

Operating Ranges

Voltage range 5 V to 230 V (phase-phase)


Frequency range Angle difference method 10 Hz to 90 Hz
Filtering method 25 Hz to 80 Hz

Tolerances

Frequency f>
frated - 0.20 Hz < f < frated + 0.20 Hz ± 5 mHz at V = Vrated
frated - 3.0 Hz < f < frated + 3.0 Hz ± 10 mHz at V = Vrated
Time delay T(f>) 1 % of the setting value or 10 ms
Minimum voltage 1 % of the setting value or 0.5 V

152 OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relays, see chapter
12.1.4 Relay Outputs

1722 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.43 Underfrequency Protection

12.43 Underfrequency Protection


Setting Values

Pickup values f< 40.00 Hz to 70.00 Hz Increments of 0.01 Hz


Dropout differential 20 mHz to 2 000 mHz Increments of 10 mHz
Time delay T 0.00 s to 600.00 s Increments of 0.01 s
Minimum voltage 3.000 V to 175.000 V Increments of 0.001 V

Times

Pickup times f< Angle difference method


50 Hz Approx. 70 ms + OOT153
60 Hz Approx. 60 ms + OOT
Filtering method
50 Hz Approx. 75 ms + OOT
60 Hz Approx. 64 ms + OOT
Dropout times f< 60 ms to 80 ms

Dropout

Frequency Parameterizable dropout differential


Minimum voltage
The larger dropout differential (= | pickup value – dropout threshold |) of the following
2 criteria is used:
Dropout differential derived from Dropout ratio 105 % for the Minimum voltage parameter
Minimum absolute dropout differential 150 mV secondary

Operating Ranges

Voltage range 5 V to 230 V (phase-phase)


Frequency range Angle difference method 10 Hz to 90 Hz
Filtering method 25 Hz to 80 Hz

Tolerances

Frequency f<
frated - 0.20 Hz < f < frated + 0.20 Hz ± 5 mHz at V = Vrated
frated - 3.0 Hz < f < frated + 3.0 Hz ± 10 mHz at V = Vrated
Time delay T(f<) 1 % of the setting value or 10 ms
Minimum voltage 1 % of the setting value or 0.5 V

153 OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relays, see chapter
12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1723


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.44 Underfrequency Load Shedding

12.44 Underfrequency Load Shedding


Setting Values for the Function

Minimum voltage 0.300 p.u. to 0.900 p.u. Increments of 0.001 p.u.


Minimum current 0.020 p.u. to 0.200 p.u. Increments of 0.001 p.u.
Power angle -30° to 30° Increments of 1°
Positive power direction inv. to CT neu.pnt sett.
acc. to CT neu.pnt sett.
Threshold value for the df/dt-rising 0.1 Hz/s to 20.0 Hz/s Increments of 0.1 Hz/s
rate or df/dt-falling rate
df/dt measuring window 2 periods to 5 periods Increments of 1 period
df/dt dropout differential 0.02 Hz/s to 0.99 Hz/s Increments of 0.10 Hz/s
f < stabilization counter 1 to 20 Increments of 1

Setting Values for the Stage

Pickup threshold 40.00 Hz to 70.00 Hz Increments of 0.01 Hz


Dropout differential 20 mHz to 2000 mHz Increments of 10 mHz
Time delay 0.00 s to 60.00 s Increments of 0.01 s

Times

Pickup times with stabilization counter = 6 Approx. 85 ms + OOT154 at 50 Hz


Approx. 80 ms + OOT at 60 Hz
Dropout time Approx. 80 ms + OOT at 50 Hz
Approx. 75 ms + OOT at 60 Hz

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout
Frequency 0.01 Hz
df/dt-rising rate and df/dt-falling rate 0.1 Hz/s
Voltage V1 105 % of the threshold value
Current I1 105 % of the threshold value at φ ≤ 0
95.23 % of the threshold value at φ > 0
Power angle 1°
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.

Tolerances

Frequency f<
frated - 0.20 Hz < f < frated + 0.20 Hz ± 5 mHz at V = Vrated

154 OOT (Output Operating Time): additional time delay of the output medium used, for example, 5 ms with fast relay

1724 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.44 Underfrequency Load Shedding

frated - 3.0 Hz < f < frated + 3.0 Hz ± 10 mHz at V = Vrated


df/dt, measuring window > 3 periods Approx. 3 % or 0.06 Hz/s
df/dt, measuring window ≤ 3 periods Approx. 5 % or 0.06 Hz/s
Minimum voltage 0.5 % of the setting value or 0.05 V
Minimum current 1 % of the setting value or 5 mA (Irated = 1 A) or 25 mA
(Irated = 5 A), (frated ± 10 %)
Power angle 1°
Time delays 1 % of the setting value or 10 ms

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

SIPROTEC 5, 7SJ82/7SJ85, Manual 1725


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.45 Rate of Frequency Change Protection

12.45 Rate of Frequency Change Protection


Setting Values for the Function

Minimum voltage 3.000 V to 175.000 V Increments of 0.001 V


Measuring window 2 periods to 5 periods Increments of 1 period

Setting Values for Stage Types

Threshold 0.100 Hz/s to 20.000 Hz/s Increments of 0.025 Hz/s


Dropout differential 0.02 Hz/s to 0.99 Hz/s Increments of 0.01 Hz/s
Operate delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

Frequency Parameterizable dropout differential


Minimum voltage
The larger dropout differential (= | pickup value – dropout threshold |) of the following
2 criteria is used:
Dropout differential derived from Dropout ratio 105 % for the Minimum voltage parameter
Minimum absolute dropout differential 150 mV secondary

Times

Pickup time Approx. 160 ms + OOT155 to 220 ms + OOT (depends on measuring


window length)
at 50 Hz
Approx. 140 ms + OOT to 200 ms + OOT (depends on measuring
window length)
at 60 Hz
Dropout time Approx. 160 ms + OOT to 220 ms + OOT (depends on measuring
window length)
at 50 Hz
Approx. 140 ms + OOT to 200 ms + OOT (depends on measuring
window length)
at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Threshold, Approx. 3 % or 0.060 Hz/s


measuring window > 3 periods
Threshold, Approx. 5 % or 0.060 Hz/s
measuring window ≤ 3 periods

155 OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relays, see chapter
12.1.4 Relay Outputs

1726 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.45 Rate of Frequency Change Protection

Minimum voltage 1 % of the setting value or 0.5 V


Time delays 1 % of the setting value or 10 ms

Functional Measured Value

Value Description
df/dt Calculated rate of frequency change

SIPROTEC 5, 7SJ82/7SJ85, Manual 1727


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.46 Vector-Jump Protection

12.46 Vector-Jump Protection


Setting Values

Threshold V1 min 0.300 V to 175.000 V Increments of 0.001 V


Threshold V1 max 0.300 V to 175.000 V Increments of 0.001 V
Threshold Δφ 2.0° to 30.0° Increments of 0.1°
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
T Reset 0.00 s to 60.00 s Increments of 0.01 s
T Block 0.00 s to 60.00 s Increments of 0.01 s
I< Threshold 0.030 A to 35.000 A at 1 A Increments of 0.001 A
0.150 A to 175.000 A at 5 A

Times

Pickup times Approx. 80 ms + OOT 156at 50 Hz


Approx. 66.8 ms + OOT at 60 Hz
Dropout times Approx. 80 ms + OOT at 50 Hz
Approx. 66.8 ms + OOT at 60 Hz

Frequency Operating Range

frated - 3 Hz ≤ f or frated ≤ frated + 3 Hz According to specified tolerances


f < frated - 3 Hz or f > frated + 3 Hz Inactive

Tolerances

Angle jump 0.5° at V > 0.5 Vrated


Voltage blocking 1 % of the setting value or 0.500 V
Undercurrent release For Irated = 1 A: 1 % of the setting value or 10 mA
For Irated = 5 A: 1 % of the setting value or 50 mA
Time delay T 1 % or 10 ms

156 OOT (Output Operating Time): additional delay of the output medium used. You can find more information in chapter 12.1.4 Relay
Outputs.

1728 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.47 Power Protection (P,Q), 3-Phase

12.47 Power Protection (P,Q), 3-Phase


Setting Values

Measured value Positive sequence power


Power of phase A
Power of phase B
Power of phase C
Threshold value -200.0 % to +200.0 % Increments of 0.1
Tilt-power characteristic -89.0° to +89.0° Increments of 0.1°
Dropout delay time 0.00 s to 60.00 s Increments of 0.01 s
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio Upper stage: 0.90 to 0.99 Increments of 0.01
Lower stage: 1.01 to 1.10 Increments of 0.01

Times

Pickup times Approx. 55 ms + OOT157 at 50 Hz


Approx. 45 ms + OOT at 60 Hz
Dropout times Approx. 55 ms + OOT at 50-Hz
Approx. 45 ms + OOT at 60 Hz

Tolerances

Power 0.5 % Srated ± 3 % of setting value


(Srated: rated apparent power)
Time delays 1 % of the setting value or 10 ms

Variables That Influence Pickup Values

Auxiliary DC voltage in the range 0.8 ≤ Vaux./ ≤1%


Vaux.,rated ≤ 1.15
Frequency in the range 0.95 ≤ f/frated ≤ 1.05 ≤1%
Harmonics
≤1%
- Up to 10 % of 3rd harmonics
≤1%
- Up to 10 % of 5th harmonics

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz < f < 0.9 frated Slightly expanded tolerances
1.1 frated < f
f ≤ 10 Hz Inactive

157 OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1729


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.48 Reverse-Power Protection

12.48 Reverse-Power Protection


Setting Values

Reverse power Preverse (p.u.) -0.30 % to -30.00 % Increments of 0.01 %


Angle correction -10.00 ° to 10.00 ° Increments of 0.01 °
Minimum voltage V1 0.300 V to 60.000 V Increments of 0.001 V
Tripping delay 0.00 s to 60.00 s 0.00 s to 60.00 s
Tripping delay with quick stop 0.00 s to 60.00 s 0.00 s to 60.00 s
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 0.40 to 0.99 Increments of 0.01

Times

Pickup times Approx. 360 ms at f = 50 Hz


Approx. 300 ms at f = 60 Hz
Dropout times Approx. 360 ms at f = 50 Hz
Approx. 300 ms at f = 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Reverse power 0.15 % Srated or 5 % of the setting value


when Q < 0.5 Srated
Time delays 1 % or 10 ms

1730 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.49 Overexcitation Protection

12.49 Overexcitation Protection


Setting Values

Threshold value 1.00 to 1.20 Increments of 0.01


(Inverse-time characteristic curve
pickup)
Threshold value 1.00 to 1.40 Increments of 0.01
(Definite-time characteristic curve
pickup)
Time delay (warning delay and tripping delay) 0.00 s to 60.00 s Increments of 0.01 s
Characteristic value pairs 2 to 30
Ranges of values V/f 1.00 p.u. to 10.00 p.u. Increments of 0.01 p.u.
t 0 s to 100 000 s Increments of 1 s
Cooling time therm. replica 0 s to 100 000 s Increments of 1 s

Functional Measured Values

Measured Value Description


(_:2311:322) V/f Value calculated from voltage and frequency.
(_:13591) Therm.charact. Thermal tripping of the overexcitation protection. If the value reaches
100 %, tripping occurs.

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Operating Times

Operate times/dropout times


Operate time at frequency 50 Hz 60 Hz
Minimum 33 ms + OOT1 30 ms + OOT158
Dropout time 10 ms + OOT1 10 ms + OOT1

Dropout Ratios

Warning, tripping (independent stage) Approx. 0.98

Operate Curve

Thermal replica For default setting refer to the following characteristic


curve Figure 12-27

Tolerances

V/f pickup 2 % of the setting value


Time delays 1 % of the setting value or 10 ms (min. 1.5 periods)
Thermal replica 5 % based on V/f ± 600 ms

158 Refer to protection functions, for example overcurrent protection

SIPROTEC 5, 7SJ82/7SJ85, Manual 1731


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.49 Overexcitation Protection

Voltage measurement accuracy 0.5 % of the setting value or 0.5 V in the range
fn ± 10 %
Frequency measurement accuracy 1.0 % of the setting value or 1.0 Hz in the frequency
range 10 Hz to 90 Hz

Influencing Quantities

Auxiliary direct voltage in the 0.8 range ≤1%


Time delays ≤ 0.5 %/10 K
Thermal replica ≤1%
Harmonics
up to 10 % of 3rd harmonics ≤1%
up to 10 % of 5th harmonics ≤1%

[dwrsasuf-070513-01.tif, 1, en_US]

Figure 12-27 Operate Curve from the Thermal Replica of the Overexcitation Protection (Default Setting)

1732 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.50 Undervoltage-Controlled Reactive-Power Protection

12.50 Undervoltage-Controlled Reactive-Power Protection


Setting Values

Threshold value Power Q 1.00 % to 200.00 % Increments of 0.01 %


Voltage of protection 3.000 to 175.000 Increments of 0.001 V
stage
Voltage of reclosure 3.000 V to 340.000 V Increments of 0.001 V
stage
Current I1 release threshold 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Release time delay of reclosure stage 0.00 s to 3600.00 s Increments of 0.01 s

Dropout Ratio

Protection stage
Reactive-power flow Q Approx. 0.95
Voltage Approx. 1.02
Release current Approx. 0.95

Reclosure stage
Voltage Approx. 0.98
Release current Approx. 0.95

Times

Pickup time Approx. 55 ms + OOT159 at 50 Hz


Approx. 45 ms + OOT at 60 Hz
Dropout time Approx. 55 ms + OOT at 50 Hz
Approx. 45 ms + OOT at 60 Hz

Tolerances

Current I1 1 % of the setting value or 5 mA (Irated = 1 A)


or 25 mA (Irated = 5 A)
Voltage 0.5 % of the setting value or 0.05 V
Power Q 0.5 % Srated ± 3 % of the setting value
(Srated: rated apparent power)
Time delays 1 % of the setting value or 10 ms
Reclosure time delay 1 % of the setting value or 10 ms

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz

159 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1733


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.50 Undervoltage-Controlled Reactive-Power Protection

f < 10 Hz Active
f > 90 Hz

1734 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.51 Circuit-Breaker Failure Protection

12.51 Circuit-Breaker Failure Protection


Starting Conditions

For circuit-breaker failure protection 3-pole tripping internal or external160

Setting Values

Phase-current threshold 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


values 1 A @ 50 Irated
5 A @ 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
5 A @ 50 Irated
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Sensitive threshold value 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
1 A @ 50 Irated
5 A @ 100 Irated 0.15 A to 175.00A Increments of 0.01 A
5 A @ 50 Irated
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Supervision time of release signal 0.00 s to 1.00 s Increments of 0.01 s
Time delays T1 0.000 s to 60.000 s Increments of 0.001 s
Time delays T2 0.050 s to 60.000 s Increments of 0.001 s
Supervision times of binary inputs 0.05 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup threshold – dropout threshold |) of the following 2
criteria applies:
Dropout differential 95 % of the pickup value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated= 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated= 1 A) or
2.5 mA sec. (Irated = 5 A)

Circuit-Breaker Supervision

Position supervision via circuit-breaker auxiliary contacts


For 3-pole CB tripping 1 input each for make contact and break contact

NOTE

i The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated.
Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).

160 Via binary inputs

SIPROTEC 5, 7SJ82/7SJ85, Manual 1735


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.51 Circuit-Breaker Failure Protection

Times

Pickup time, in the case of an internal start < 1 ms


Pickup time, in the case of an external start < 5 ms
Typical dropout time < 15 ms
Dropout time, via circuit-breaker auxiliary contact < 5 ms
criterion161

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the setting value or 10 ms

161 The use of the transformer connection types 2ph, 2p. CT + IN-sep result in slightly increased tolerances

1736 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.52 Circuit-Breaker Restrike Protection

12.52 Circuit-Breaker Restrike Protection


Setting Values

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Monitoring duration 1.00 s to 600.00 s Increments of 0.01 s
Position recognition delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s
Trip delay time 0.05 s to 60.00 s Increments of 0.01 s
Retrip delay time 0.00 s to 60.00 s Increments of 0.01 s
Minimum operate (trip) time 0.00 s to 60.00 s Increments of 0.01 s

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT at 50 Hz


Approx. 22 ms + OOT at 60 Hz
Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Active
f > 90 Hz

Tolerances

Threshold 1 % of the setting value or 5 mA (Irated = 1 A) or 25 mA


(Irated = 5 A)
Time delays 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1737


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.53 Restricted Ground-Fault Protection

12.53 Restricted Ground-Fault Protection


Setting Values

Threshold value162 0.05 A to 2.00 A Increments of 0.01 A


Gradient 0.00 to 0.95 Increments of 0.01
Operate curve See figure
Pickup tolerance 2%
(for preset characteristic curve parameters; for 2 sides
with 1 measuring point each)
Tripping delay 0.00 s to 60.00 s or ∞ Increments of 0.01 s
(no tripping)
Timer tolerance 1 % of the setting value or 10 ms

Functional Measured Values

Measured Value Description


(_:306) I REF,operate Operate quantity of the restricted ground-fault protection from
the angle criterion and can be displayed in the fault record
(_:307) I Angle,REF Stabilizing value (angle) of the restricted ground-fault protection
from the angle criterion and can be displayed in the fault record
(_:311) I REF,Trip operate Operate quantity of the restricted ground-fault protection when
OFF; will be issued in the log
(_:312) I angle,REF operate Stabilizing value of the restricted ground-fault protection when
OFF; will be issued in the log
(_:301) I diff. Differential current; can be displayed in the fault record
(_:302) I restr. Restraint current; can be displayed in the fault record

Dropout Ratio

Threshold value 0.7

Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)

Times

7UT82/7UT85/7UT86/7UT87
Frequency 50 Hz 60 Hz
Operate time Operate time

162 The specified setting limit can be dynamically further limited, depending on the transformer adaptation factor, (for this refer to
chapter 6.44.4 Application and Setting Notes).

1738 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.53 Restricted Ground-Fault Protection

At 1.5 · setting value threshold value 33 ms + OOT 32 ms + OOT


At 2.5 · setting value threshold value 27 ms + OOT 26 ms + OOT
Dropout time approx. 80 ms 67 ms

[dwausken-170712-01.tif, 2, en_US]

Figure 12-28 Restricted Ground-Fault Protection Operate Curve Depending on the Phase Angle between IY*
and 3I0* with Extended Operate Range.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1739


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.54 External Trip Initiation

12.54 External Trip Initiation


Setting Values

Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Times

Operate time with time delay = 0 ms


Approx. 10 ms + OOT 163.
- At initiation via binary input signal

Tolerance

Sequence tolerance for delay times 1 % of the setting value or 10 ms

163 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs

1740 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.55 Automatic Reclosing

12.55 Automatic Reclosing


Function specifications Cyclic automatic reclosing function
Automatic reclosing function with adaptive dead time (ADT)
Operation with External Automatic Reclosing Function
Number of reclosings Max. 8, per individual settings
Type (depending on the order 1-pole, 3-pole, or 1-/3-pole
variation)
Operating mode of the automatic With trip command, without action time
reclosing function With trip command, with action time
With pickup, without action time
With pickup, with action time
Reclaim time after reclosing 0.50 s to 300.00 s Increments of 0.01 s
Blocking time after dynamic 0.5 s -
blocking
Blocking time after manual closure 0.00 s to 300.00 s Increments of 0.01 s
Start supervision time 0.01 s to 300.00 s Increments of 0.01 s
Circuit-breaker supervision time 0.01 s to 300.00 s Increments of 0.01 s
Evolving-fault detection With trip command
With Pickup
Reaction to evolving faults Blocks Automatic reclosing function
Start, evolving fault, dead time
Action times (separated for all 0.00 s to 300.00 s or oo (ineffec- Increments of 0.01 s
cycles) tive)
Dead times after trip command 0.00 s to 1 800.00 s or oo (ineffec- Increments of 0.01 s
(separated for all types and all tive)
cycles)
Dead time after evolving-fault 0.00 s to 1 800.00 s Increments of 0.01 s
detection (separated for all cycles)
Synchrocheck after 3-pole dead None
time Internal
External
Transmission delay, inter close 0.00 s to 300.00 s or oo (ineffec- Increments of 0.01 s
command tive)
Dead-line check/reduced dead time Without
Reduced dead time (VWE)
Dead line checking
Voltage supervision warning time 0.10 s to 30.00 s Increments of 0.01 s
Limiting value for fault-free line 0.3 V to 340.0 V Increments of 0.1 V
Limiting value for zero potential 0.3 V to 340.0 V Increments of 0.1 V

SIPROTEC 5, 7SJ82/7SJ85, Manual 1741


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.56 Fault Locator

12.56 Fault Locator


Setting Values

Reactance per unit length of the line per kilometer or per mile
Line length for the correct output of the fault distance as a percentage of the line length
The residual compensation factors in the setting format Kr and Kx or K0 and angle (K0)
Consideration of the load current for 1-pole ground Correction of the X value, for connection and discon-
faults nection

Fault Distance

Output of the fault distance (line length) In Ω primary and secondary


In km, miles or in percent. 164

Tolerances

Measuring tolerances during sinusoidal measurands 1.5 % from fault location at VK/Vrated ≥ 0.01 and one of
and error duration the following scenarios:
> 25 ms at 60 Hz or
> 30 ms at 50 Hz
• Metal fault
• Non-metallic fault for one-side infeed without
load

164 The output of the fault distance in km, miles and percent presupposes a homogenous line.

1742 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.57 Fault Locator Plus

12.57 Fault Locator Plus


Setting Values

• Cb per length unit, C0 per length unit, and X per length unit of the line per kilometer or per mile
• Line angle in °
• Line length for the correct output of the fault distance in km or miles and percent of the line length
• The residual compensation factors in the setting format Kr and Kx or K0 and angle (K0)
Consideration of the load current in the case of 1- Correction of the X value, for connection and discon-
phase ground faults nection

Output Values

Output of the fault distance (line length), for non- In km, miles, or percent. 165
homogeneous lines with indication of the line section
Output of the fault resistance, fault contact resis- In Ω primary and secondary
tance, and fault reactance

Tolerances

Measuring tolerances during sinusoidal measurands 1.5 % from fault location with VK/Vrated ≥ 0.01 and IF/
and fault duration Irated ≥ 0.1
> 25 ms at 60 Hz or
> 30 ms at 50 Hz

165 Output of the fault distance in km, miles, and percent presupposes a homogeneous line.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1743


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.58 Temperature Supervision

12.58 Temperature Supervision


Setting Values

Pickup value -50 °C to 250 °C Increments of 1°C


-58 °F to 482 °F Increments of 1°F
Time delay 0 s to 60 s Increments of 1 s
or ∞

Dropout Conditions

Dropout differential 3 °C or 6 °F

Tolerances

Tripping delay ±1 % of the setting value or ±10 ms


Measured temperature value ±0.5 % of the setting value or ±1 °C or ±2 °F

1744 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.59 Current-Jump Detection

12.59 Current-Jump Detection


Times

Pickup time Approx. 10 ms + OOT166 at 50 Hz


Approx. 8 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Currents 3 % of setting value or 10 mA (Irated = 1 A) or


50 mA (Irated = 5 A), (frated ± 10 %)
for amplitude changes of sinusoidal measurands
Pulse time 1 % of the setting value or 10 ms

166 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

SIPROTEC 5, 7SJ82/7SJ85, Manual 1745


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.60 Voltage-Jump Detection

12.60 Voltage-Jump Detection


Times

Pickup time Approx. 10 ms + OOT167 at 50 Hz


Approx. 8 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz
f < 10 Hz Inactive
f > 90 Hz

Tolerances

Voltages 2 % of the setting value or 0.100 V


for amplitude changes of sinusoidal measurands
Pulse time 1 % of the setting value or 10 ms

167 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

1746 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.61 Synchronization Function

12.61 Synchronization Function


Operating Modes

Synchrocheck
Switching synchronous systems
Switching asynchronous systems
Switching synchronous/asynchronous systems with balancing commands
De-energized switching
Direct closing command
Balancing Voltage
Balancing Frequency

Setting Values

Supervision/Delay/Pulse times:
Max.durat. sync.process 0.00 s to 3 600.00 s or ∞ (ineffec- Increments of 0.01 s
tive)
Supervision time de-energized 0.00 s to 60.00 s Increments of 0.01 s
switching
Closure delay 0.00 s to 60.00 s Increments of 0.01 s
T V pulse min/T f pulse min 0.01 s to 1.00 s Increments of 0.01 s
T V pulse max/T f pulse max 0.01 s to 60.00 s Increments of 0.01 s
T pause V/T pause f 0.01 s to 60.00 s Increments of 0.01 s
T close without balancing 1.00 s to 100.00 s Increments of 0.01 s
Voltage threshold values:
Upper voltage limit Vmax 0.300 V to 340.000 V (phase-to- Increments of 0.001 V
phase)
Lower voltage limit Vmin 0.300 V to 340.000 V (phase-to- Increments of 0.001 V
phase)
V<, for off-circuit conditions 0.300 V to 170.000 V (phase-to- Increments of 0.001 V
V>, for voltage present phase) Increments of 0.001 V
0.300 V to 340.000 V (phase-to-
phase)
Differential values, changeover thresholds asynchronous/synchronous/balancing/adjusting commands:
Voltage differences 0.000 V to 170.000 V Increments of 0.001 V
V2 > V1; V2 < V1
Frequency difference f2 > f1; 0.000 Hz to 2.000 Hz (synchro- Increments of 0.001 Hz
f2 < f1 nous)
0.000 Hz to 4.000 Hz (asynchro-
nous)
Angle difference α2 > α1; α2 < α1 0o to 90o Increments of 1o
Δf threshold ASYN <-> SYN 0.010 Hz to 0.200 Hz Increments of 0.001 Hz
Δf set point for balancing -1.00 Hz to 1.00 Hz Increments of 0.01 Hz
Δf for the kick pulse -1.00 Hz to 1.00 Hz Increments of 0.01 Hz
Adjustments of the sides:
Angle adjustment 0.0o to 360.0o Increments of 0.1o
Voltage adjustment 0.500 to 2.000 Increments of 0.001
Circuit breaker
Closing time of the circuit breaker 0.01 s to 0.60 s Increments of 0.01 s

SIPROTEC 5, 7SJ82/7SJ85, Manual 1747


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.61 Synchronization Function

Dropout Ratio

Min./max. operating limit 1 % of the setting value


Voltage differential 10 % of the setting value or 0.5 V
De-energized/energized 5 % of the setting value
Frequency difference 3 mHz
Angle difference 0.1o

Measured Values of the Synchronization Function

Reference voltage V1 In kV primary, in V secondary or in % Vrated


Display always as phase-to-phase voltage
• Range 10 % to 120 % of Vrated

• Tolerance at rated frequency ≤ 1 % of the measured value or 0.5 % Vrated


Voltage to be synchronized V2 In kV primary, in V secondary or in % Vrated
Display always as phase-to-phase voltage
• Range 10 % to 120 % of Vrated

• Tolerance at rated frequency ≤ 1 % of the measured value or 0.5 % Vrated


Frequency of the voltage V1f1 f1 in Hz
25 Hz ≤ f ≤ 70 Hz
• Range
1 mHz
• Tolerance at rated frequency
Frequency of the voltage V1f2 f2 in Hz
25 Hz ≤ f ≤ 70 Hz
• Range
1 mHz
• Tolerance at rated frequency
Voltage difference V2-V1 In kV primary, in V secondary or in % Vrated
Display always as phase-to-phase voltage in relation
to side 1
10 % to 120 % of Vrated
• Range
≤ 1 % of the measured value or 0.5 % Vrated
• Tolerance at rated frequency
Frequency difference f2-f1 In mHz
frated ± 10 %
• Range
1 mHz
• Tolerance at rated frequency
Angle difference λ2-λ1 In o
• Range -180o to +180o
0.5o
• Tolerance at rated frequency

Times

Measuring time, after switching on the variables Approx. 80 ms

Operating Range

Voltage 20 V to 340 V
Frequency frated - 4 Hz ≤ frated ≤ frated + 4 Hz

Tolerances

Tolerances of the voltage settings 2 % of the pickup value or 1 V


Voltage difference V2>V1; V2<V1 1V

1748 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.61 Synchronization Function

Frequency difference f2>f1; f2<f1 10 mHz


Angle difference α2>α1; α2<α1 1o
Pulse time 1 % of the calculated impulse or
10 ms
Tolerance of all time settings 10 ms
Max. phase displacement angle 5o for Δf ≤ 1 Hz
10o for Δf > 1 Hz

SIPROTEC 5, 7SJ82/7SJ85, Manual 1749


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.62 Voltage Controller

12.62 Voltage Controller


Setting Values

General Information
I reference for % values168 0.20 A to 100000.00 A Increments of 0.01 A
V reference for % values169 0.20 kV to 1200.00 kV Increments of 0.01 kV
Rated app. power transf.170 0.20 MVA to 5000.00 MVA Increments of 0.01 MVA
Volt. cont. 2W
Target voltage 1
Target voltage 2
10.000 V to 340.000 V Increments of 0.001 V
Target voltage 3
Target voltage 4
Volt. cont. 3W and GC
Target voltage 1 w1
Target voltage 2 w1
Target voltage 3 w1
Target voltage 4 w1
10.000 V to 340.000 V Increments of 0.001 V
Target voltage 1 w2
Target voltage 2 w2
Target voltage 3 w2
Target voltage 4 w2
Volt. cont. 2W, 3W, and GC
Bandwidth 0.2 % to 10.0 % Increments of 0.1 %
T1 delay 5 s to 600 s Increments of 1 s
T1 Inverse Min 5 s to 100 s Increments of 1 s
T2 delay 0 s to 100 s Increments of 1 s
Fast step down limit 0.0 % to 50.0 % Increments of 0.1 %
Fast step down T delay 0.0 s to 10.0 s Increments of 0.1 s
Fast step up limit -50.0 % to 0.0 % Increments of 0.1 %
Fast step up T delay 0.0 s to 10.0 s Increments of 0.1 s
Function monitoring 0 min to 120 min Increments of 1 min
Line compensation LDC-Z
Target voltage rising 0.0 % to 20.0 % Increments of 0.1 %
Max load current 0.0 % to 500.0 % Increments of 0.1 %
Line compensation LDC-XandR (two-winding transformer)
R line 0.00 Ω to 30.00 Ω Increments of 0.01 Ω
X line -30.00 Ω to 30.00 Ω Increments of 0.01 Ω
Line compensation LDC-XandR
R line 0.0 Ω to 30.0 Ω Increments of 0.1 Ω
X line -30.0 Ω to 30.0 Ω Increments of 0.1 Ω
Limiting values
Vmin threshold 10.000 V to 340.000 V Increments of 0.001 V
Vmin time delay 0 s to 20 s Increments of 1 s
Vmax threshold 10.000 V to 340.000 V Increments of 0.001 V

168 Only visible in the voltage-control operation without parallel operation


169 Only visible in the voltage-control operation without parallel operation
170 Only visible in the voltage-control operation without parallel operation

1750 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.62 Voltage Controller

Vmax time delay 0 s to 20 s Increments of 1 s


Blockings
V< Threshold 10.000 V to 340.000 V Increments of 0.001 V
V< Time delay 0 s to 20 s Increments of 1 s
I> Threshold 10 % to 500 % Increments of 1 %
I> Time delay 0 s to 20 s Increments of 1 s
I< Threshold 3 % to 100 % Increments of 1 %
I< Time delay 0 s to 20 s Increments of 1 s
Parallel control
Parallel-transfomer id 0 to 8 Increments of 1
Maximal tap difference 1 to 9 Increments of 1
Reactive I control factor 0.01 to 100.00 Increments of 0.01
VT supervision threshold 0.5 % to 10.0 % Increments of 0.1 %
VT supervision time delay 1 s to 600 s Increments of 1 s
Circul. current threshold 10 % to 500 % Increments of 1 %
Circul. current time delay 0 s to 1000 s Increments of 1 s

Measured Values, Two-Winding Transformer

Measured Value Description Primary Secondary % Referenced to


V act. Current, measured positive- kV V Target voltage of the primary
sequence voltage (referenced system referenced to the rated
to phase-to-phase) voltage
ΔV act. Voltage difference between % % Voltage difference referenced
the target voltage and the to the rated voltage of the
actual voltage controlled winding
I load Current measured load current A A Load current referenced to the
(positive-sequence system) rated value of the function
V max Maximum positive-sequence kV V Maximum voltage of the
voltage ever measured (refer- winding referenced to the
enced to phase-to-phase) rated voltage of the winding
V min Minimum positive-sequence kV V Minimum voltage of the
voltage ever measured (refer- winding referenced to the
ence to phase-to-phase) rated voltage of the winding
V target Calculated target voltage with kV V Target voltage of the winding
consideration of Z compensa- referenced to the rated voltage
tion of the winding
PhAng Phase angle of the currently ° ° -
measured load current
I load Σ Sum of the currently measured A A Load current referenced to the
load currents. Active when line rated current of the function
compensation is activated.
I circul. Currently measured circulating A A Circulating reactive current
reactive current
Vact.m Currently measured control kV V Current voltage of the control
voltage referenced to the rated voltage
of the function
ΔVactV Voltage difference % % Voltage difference referenced
to the rated voltage of the
function

SIPROTEC 5, 7SJ82/7SJ85, Manual 1751


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.62 Voltage Controller

Measured Value Description Primary Secondary % Referenced to


ΔVactC Voltage difference % % Voltage difference referenced
to the rated voltage of the
function

Measured Values for Parallel Control, Proxy

Measured Value Description Primary Secondary % Referenced to


V act. Actual voltage of winding kV V Target voltage of the primary
system referenced to the rated
voltage of the function
1/X trf. Susceptance, internal value for 1/Ω
GOOSE transmission
I load Load current A - Load current referenced to the
rated current of the function
PhAng Phase angle of the load current ° ° Phase angle of the load current
relative to the voltage with a 100 % = 180°
power factor of 1.0

Measured Values, Three-Winding Transformer

Measured Value Description Primary Secondary % Referenced to


Vact.w1 Actual voltage of winding 1 kV V Target voltage of the primary
system referenced to the rated
voltage
Vact.w2 Actual voltage of winding 2 kV V Target voltage of the primary
system referenced to the rated
voltage
ΔV act. Voltage difference between % % Voltage difference referenced
the target voltage and the to the rated voltage of the
actual voltage controlled winding
I load w1 Load current of winding 1 A A Load current referenced to the
rated current of winding 1
I load w2 Load current of winding 2 A A Load current referenced to the
rated current of winding 2
Vmax 1 Maximum voltage of winding 1 kV V Maximum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmax 2 Maximum voltage of winding 2 kV V Maximum voltage of winding 2
referenced to the rated voltage
of winding 2
Vmin 1 Minimum voltage of winding 1 kV V Minimum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmin 2 Minimum voltage of winding 2 kV V Minimum voltage of winding 2
referenced to the rated voltage
of winding 2
V tar.w1 Target voltage of winding 1 kV V Target voltage of winding 1
referenced to the rated voltage
of winding 1
V tar.w2 Target voltage of winding 2 kV V Target voltage of winding 2
referenced to the rated voltage
of winding 2

1752 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.62 Voltage Controller

Measured Values Grid Coupling Transformer

Measured Value Description Primary Secondary % Referenced to


Vact.w1 Actual voltage of winding 1 kV V Target voltage of the primary
system referenced to the rated
voltage
Vact.w2 Actual voltage of winding 2 kV V Target voltage of the primary
system referenced to the rated
voltage
ΔV act. Voltage difference between % % Voltage difference referenced
the target voltage and the to the rated voltage of the
actual voltage controlled winding
I load w1 Load current of winding 1 A A Load current referenced to the
rated current of winding 1
I load w2 Load current of winding 2 A A Load current referenced to the
rated current of winding 2
Vmax 1 Maximum voltage of winding 1 kV V Maximum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmax 2 Maximum voltage of winding 2 kV V Maximum voltage of winding 2
referenced to the rated voltage
of winding 2
Vmin 1 Minimum voltage of winding 1 kV V Minimum voltage of winding 1
referenced to rated voltage of
winding 1
Vmin 2 Minimum voltage of winding 2 kV V Minimum voltage of winding 2
referenced to rated voltage of
winding 2
V tar.w1 Target voltage of winding 1 kV V Target voltage of winding 1
referenced to the rated voltage
of winding 1
V tar.w2 Target voltage of winding 2 kV V Target voltage of winding 2
referenced to the rated voltage
of winding 2

Dropout Ratio

Threshold of the voltage limit About 0.98 of the setting value


Threshold of the current limit About 0.95 of the setting value

SIPROTEC 5, 7SJ82/7SJ85, Manual 1753


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.63 Current-Balance Supervision

12.63 Current-Balance Supervision


Setting Values

Release threshold 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A


1 A @ 50 Irated
5 A @ 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
5 A @ 50 Irated
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold min/max 0.10 to 0.95 Increments of 0.01
Delay failure indication 0.00 s to 100.00 s Increments of 0.01 s

Dropout Ratio

Overcurrent dropout ratio Approx. 0.97


Undercurrent dropout ratio Approx. 1.05

Times

Tripping time Approx. 500 ms


Dropout time Approx. 500 ms

1754 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.64 Voltage-Balance Supervision

12.64 Voltage-Balance Supervision


Setting Values

Release threshold 0.300 V to 170.000 V Increments of 0.001 V


Threshold min/max 0.58 to 0.95 Increments of 0.01
Delay failure indication 0.00 s to 100.00 s Increments of 0.01 s

Dropout Ratio

Overvoltage dropout ratio Approx. 0.97


Undervoltage dropout ratio Approx. 1.05

Times

Tripping time Approx. 500 ms


Dropout time Approx. 500 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1755


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.65 Current-Sum Supervision

12.65 Current-Sum Supervision


Setting Values

Slope factor 0.00 to 0.95 Increments of 0.01


Threshold 1 A @ 50 0.030 A to 10.000 A Increments of 0.001 A
and100 Irated
5 A @ 50 0.15 A to 50.00 A Increments 0.01 A
and100 Irated
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Delay failure indication 0.00 s to 100.00 s Increments of 0.01 s

Dropout Ratio

Dropout ratio Approx. 0.97

Times

Tripping time Approx. 500 ms


Dropout time Approx. 500 ms

1756 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.66 Voltage-Sum Supervision

12.66 Voltage-Sum Supervision


Setting Values

Threshold 0.300 V to 170.000 V Increments of 0.001 V


Delay failure indication 0.00 s to 100.00 s Increments of 0.01 s

Dropout Ratio

Dropout ratio Approx. 0.97

Times

Tripping time Approx. 500 ms


Dropout time Approx. 500 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1757


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.67 Current Phase-Rotation Supervision

12.67 Current Phase-Rotation Supervision


Setting Values

Tripping delay 0.00 s to 100.00 s Increments of 0.01 s


Phase-rotation direction ABC
ACB

Times

Tripping time Approx. 500 ms


Dropout time Approx. 500 ms

1758 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.68 Voltage Phase-Rotation Supervision

12.68 Voltage Phase-Rotation Supervision


Setting Values

Tripping delay 0.00 s to 100.00 s Increments of 0.01 s


Phase-rotation direction ABC
ACB

Times

Tripping time Approx. 500 ms


Dropout time Approx. 500 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1759


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.69 Voltage-Comparison Supervision

12.69 Voltage-Comparison Supervision


Times

Alarm times Approx. 3 ms to 12 ms + OOT 171at 50 Hz


Approx. 2.5 ms to 10 ms + OOT at 60 Hz
Dropout time 20 ms

Frequency Operating Range

10 Hz ≤ f ≤ 90 Hz According to specified tolerances


f < 10 Hz Inactive
f > 90 Hz

Tolerances

Pickup threshold
Voltage 0.5 % of the setting value or 0.05 V

171 OOT (Output Operating Time): extra delay of the output medium used

1760 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.70 Trip-Circuit Supervision

12.70 Trip-Circuit Supervision


Setting Values

Number of monitored circuits per circuit-breaker function group 1 to 3


Operating mode per circuit With 1 binary input
With 2 binary inputs
Pickup and dropout time About 1 s to 2 s
Adjustable indication delay with 1 binary input 1.00 s to 600.00 s Increments of 0.01 s
Adjustable indication delay with 2 binary inputs 1.00 s to 600.00 s Increments of 0.01 s

SIPROTEC 5, 7SJ82/7SJ85, Manual 1761


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.71 Closing-Circuit Supervision

12.71 Closing-Circuit Supervision


Setting Values

Operating mode per circuit With 1 binary input


With 2 binary inputs
Adjustable indication delay with 1 binary input 1.00 s to 600.00 s Increments of 0.01 s
Adjustable indication delay with 2 binary inputs 1.00 s to 30.00 s Increments of 0.01 s

1762 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.72 Analog Channel Supervision via Fast Current Sum

12.72 Analog Channel Supervision via Fast Current Sum


Times

Pickup times Approx. 2 ms (faster than the fastest protection function)


Dropout time Approx. 100 ms

Blockings

Blocked functions All functions that process the measured values from this current meas-
uring point (for example, differential protection).

SIPROTEC 5, 7SJ82/7SJ85, Manual 1763


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.73 Measuring-Voltage Failure Detection

12.73 Measuring-Voltage Failure Detection


Setting Values

3ph.fail. - VA,VB,VC < 0.300 V to 340 000 V Increments of 0.001 V


3ph.fail. - phs.curr.release 1 A @ 50 and100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
3ph.fail. - phs.curr. jump 1 A @ 50 and100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Asym.fail. - time delay 0.00 s to 30.00 s Increments of 0.01 s
SO 3ph.fail. - time delay 0.00 s to 30.00 s Increments of 0.01 s

Dropout
The larger dropout differential (= | pickup value – dropout threshold |) of the following 2 criteria
is used:
Dropout differential derived from the Dropout ratio parameter
If this parameter is not available, a dropout ratio of 95 % applies to the overvoltage protection and a dropout
ratio of 105 % applies to the undervoltage protection.
Minimum absolute dropout differential 150 mV sec.

Times

Pickup time Approx. 10 ms + OOT172 at 50 Hz


Approx. 10 ms + OOT at 60 Hz
Dropout time Approx. 20 ms + OOT

Times

Use in function group Line


Pickup time Approx. 10 ms + OOT173 at 50 Hz
Approx. 9 ms + OOT at 60 Hz

Use in other function group types


Pickup time Approx. 20 ms + OOT174 at 50 Hz
Approx. 18 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances


10 Hz ≤ f < 0.9 frated Slightly expanded tolerances
1.1 frated < f ≤ 90 Hz

172 OOT (Output Operating Time) Additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
173 OOT (Output Operating Time) Additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
174 OOT (Output Operating Time) Additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs

1764 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.73 Measuring-Voltage Failure Detection

f < 10 Hz Active
f > 90 Hz

Tolerances

Currents 1 % of the setting value or 5 mA (Irated = 1 A)


or 25 mA (Irated = 5 A), (frated ± 10 %)
Voltages 0.5 % of the setting value or 0.5 V
Time delays 1 % of the setting value or 10 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1765


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.74 Voltage-Transformer Circuit Breaker

12.74 Voltage-Transformer Circuit Breaker


Setting Values

Response time 0.000 s to 0.030 s Increments of 0.001 s

1766 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.75 Operational Measured Values and Statistical Values

12.75 Operational Measured Values and Statistical Values


The following applies to the tolerances of currents and voltages:

• The values apply both to the RMS values and the absolute value and phase angle of the fundamental
components.

• The values were determined for pure sinusoidal signals – without harmonics.

• All measured values have an additional tolerance of 1 DIGIT.

Voltages

VA, VB, VC V secondary


Voltage range < 200 V secondary
Secondary rated voltage 100 V to 125 V
Measuring range (0.1 to 2) · Vrated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.2 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above-mentioned
measuring range
VAB, VBC, VCA V secondary
Voltage range < 200 V
Secondary rated voltage 100 V to 125 V
Measuring range (0.1 to 2) · Vrated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.2 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above-mentioned
measuring range

Currents, Instrument Transformers

IA, IB, IC, 3I0 A secondary


Current range < 1.6 Irated
Rated currents 1 A, 5 A
Measuring range (0.1 to 1.6) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.1 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz

SIPROTEC 5, 7SJ82/7SJ85, Manual 1767


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.75 Operational Measured Values and Statistical Values

Tolerance 0.3 % of the measured value in the above-mentioned


measuring range

Currents, Protection-Class Current Transformer

IA, IB, IC, 3I0 A secondary


Current range < 100 Irated
Rated currents 1 A, 5 A
Measuring range (0.1 to 5) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.2 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above-mentioned
measuring range

Currents, Protection-Class Current Transformer

IA, IB, IC, 3I0 A secondary


Current range < 50 Irated
Rated currents 1 A, 5 A
Measuring range (0.1 to 5) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.2 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above-mentioned
measuring range

Currents, Sensitive Ground-Current Transformer

3I0 A secondary
Current range < 1.6 Irated
Rated currents 1 A, 5 A
Measuring range (0.1 to 1.6) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.1 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above-mentioned
measuring range

1768 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.75 Operational Measured Values and Statistical Values

Phase Angle

ΦV °
Frequency range 47.5 Hz to 52.5 Hz at frated = 50 Hz
57.5 Hz to 62.5 Hz at frated = 60 Hz
Tolerance ΦV 0.2° at rated voltage
ΦI °
Frequency range 47.5 Hz to 52.5 Hz at frated = 50 Hz
57.5 Hz to 62.5 Hz at frated = 60 Hz
Tolerance ΦI 0.2° at rated current

Power Values

Active power P W secondary


Voltage range (0.8 to 1.2) · Vrated
Current range (0.1 to 2) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 0.5 % of the measured value in the above-mentioned
measuring range
Reactive power Q var secondary
Voltage range (0.8 to 1.2) · Vrated
Current range (0.1 to 2) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 1.0 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 1.5 % of the measured value in the above-mentioned
measuring range
Apparent power S VA secondary
Measuring range (0.01 to 2) · Srated
Voltage range (0.8 to 1.2) · Vrated
Current range (0.01 to 2) · Irated
Frequency range
49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 0.5 % of the measured value in the above-mentioned
measuring range

SIPROTEC 5, 7SJ82/7SJ85, Manual 1769


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.75 Operational Measured Values and Statistical Values

Power Factor

Measuring range |cosφ| ≥ 0.01


Voltage range (0.8 to 1.2) · Vrated
Current range (0.1 to 2) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above-mentioned
measuring range
Frequency range (expanded) 45 Hz to 55 Hz at frated = 50 Hz
55 Hz to 65 Hz at frated = 60 Hz
Tolerance 0.5 % of the measured value in the above-mentioned
measuring range

Frequency

Frequency f Hz
Range frated - 0.20 Hz ≤ f ≤ frated + 0.20 Hz
Tolerance ± 2 mHz at V = Vrated or at I = Irated
Range frated - 3.00 Hz ≤ f < frated + 3.00 Hz
Tolerance ± 5 mHz at V = Vrated or at I = Irated
Range 25 Hz to 80 Hz; operational measured values
10 Hz to 90 Hz; functional measured values, system
frequency
Tolerance ± 10 mHz at V = Vrated or at I = Irated

Statistical Values of the Device

Device operating hours h


Range 0 to 9999999 h
Tolerance 1h

Statistical Values of the Circuit Breaker

Op.cnt. (operation counter)


Range 0 to 999999999
Tolerance None
∑I Off (sum of the primary currents switched off) A, kA, MA, GA, TA, PA primary
Range 0 to 9.2e+15
Operating hours h
Range 0 to 9999999 h
Tolerance 1h
Circuit breaker open hours h
Range 0 to 9999999 h
Tolerance 1h

Statistical Values of the Disconnector

Op.cnt. (operation counter)


Range 0 to 999999999
Tolerance None

1770 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.76 Energy Values

12.76 Energy Values


Setting Values

Active energy Wp kWh, MWh, GWh


Measuring range |cosφ| ≥ 0.01
Voltage range (0.8 to 1.2) · Vrated
Current range (0.1 to 2) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above mentioned measuring
range
Frequency range (expanded) 40 Hz to 69 Hz at frated = 50 Hz
50 Hz to 70 Hz at frted = 60 Hz
Tolerance 0.5 % of the measured value in the above mentioned measuring
range

Reactive energy Wq kvarh, Mvarh, Gvarh


Measuring range |cosφ| ≤ 0,984
Voltage range (0.8 to 1.2) · Vrated
Current range (0.1 to 2) · Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 1.0 % of the measured value in the above mentioned measuring
range
Frequency range (expanded) 40 Hz to 69 Hz at frated = 50 Hz
50 Hz to 70 Hz at frated = 60 Hz
Tolerance 1.5 % of the measured value in the above mentioned measuring
range

SIPROTEC 5, 7SJ82/7SJ85, Manual 1771


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.77 Phasor Measurement Unit

12.77 Phasor Measurement Unit


Accuracy
IEEE Standard for Synchrophasor
Measurements
IEEE Std C37.118.1aTM-2014

Data Transfer
IEEE Standard for Synchrophasor
Data transfer
IEEE Std C37.118.2TM-2011

1772 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.78 Circuit-Breaker Wear Monitoring

12.78 Circuit-Breaker Wear Monitoring


Setting Values

Threshold value ΣIx-method stage 0 to 10 000 000 Increments of 1


2P-method stage 0 to 10 000 000 Increments of 1
I2t-method stage 0.00 I/Ir*s to 21 400 000.00 I/Ir*s Increments of 0.01
CB opening time 0.001 s to 0.500 s Increments of 0.001 s
CB break time 0.001 s to 0.600 s Increments of 0.001 s
CB make time 0.001 s to 0.600 s Increments of 0.001 s
Exponent for the ΣIx method 1.0 to 3.0 Increments of 0.1
Switching cycles at Irated 100 to 1 000 000 Increments of 1
Rated short-circuit breaking current Isc 10 to 100 000 Increments of 1
Switching cycles at Isc 1 to 1000 Increments of 1
Level of warning 1 1 % to 100 % Increments of 1 %
Level of warning 2 1 % to 100 % Increments of 1 %
Operating 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
current threshold 5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Delay correction time -0.050 s to 0.050 s Increments of 0.001 s

Tolerances

Tolerance of the measured value make time ± 2 ms

SIPROTEC 5, 7SJ82/7SJ85, Manual 1773


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.79 CFC

12.79 CFC
Typical response times and maximum number of ticks of the CFC task levels:
Task Level Time (in ms) Ticks for Non- Ticks for Modular Ticks for Modular
Modular Devices Devices with CP200 Devices with CP300
with CP100
Fast Event- <1 500 500 1000
Triggered
Event-Triggered <10 12 367 12 757 14 702
Interlocking <10 117 564 in total 121 537 in total 141 398 in total
Measurement 250

The times describe the response time of a typical CFC chart at the respective task level. The maximum number
of ticks applies to a typical load for the device based on the application template Directional overcurrent
protection, grounded system. The maximum number can be lower in case of extensive protection applica-
tions.
The task level Measurement runs in cycles every 500 ms. All other task levels are event-triggered.
In order to estimate the tick consumption of a CFC chart, you can use the following formula:
TChart = 5 ∙ nInp + 5 ∙ nOutp + TTLev + ∑i Tint + ∑j TBlock

where:
nInp Number of indications routed as input in the CFC chart
nOutp Number of indications routed as output in the CFC chart
TTLev 101 Ticks in Fast Event-Triggered level
104 Ticks in Event-Triggered level
54 Ticks in Measurement level
74 Ticks in Interlocking level
Tint Number of internal connections between 2 CFC blocks in one chart
TBlock Used ticks per CFC block (see Table 12-9)

Table 12-9 Ticks of the Individual CFC Blocks

Element Ticks
ABS_D 2.3
ABS_R 1.5
ACOS_R 6.9
ADD_D4 3.4
ADD_R4 3.3
ADD_XMV 6.4
ALARM 1.8
AND_SPS 1.1
AND10 2.9
APC_DEF 1.2
APC_EXE 1.0
APC_INFO 3.9
ASIN_R 1.3
ATAN_R 1.2
BLINK 1.3
BOOL_CNT 2.0
BOOL_INT 1.5

1774 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.79 CFC

Element Ticks
BSC_DEF 1.3
BSC_EXE 1.1
BSC_INFO 2.7
BUILD_ACD 2.9
BUILD_ACT 2.2
BUILD_BSC 1.2
BUILD_CMV 2.3
BUILD_DEL 2.1
BUILD_DPS 1.4
BUILD_ENS 1.3
BUILD_INS 0.5
BUILD_Q 0.8
BUILD_SPS 0.6
BUILD_WYE 3.2
BUILD_XMV 2.9
BUILDC_Q 3.0
CHART_STATE 5.9
CMP_DPS 1.5
CON_ACD 0.7
CON_ACT 0.5
CONNECT 0.4
COS_R 2.5
CTD 1.8
CTU 1.6
CTUD 2.3
DINT_REAL 3.0
DINT_UINT 3.0
DIV_D 2.9
DIV_R 1.6
DIV_XMV 2.2
DPC_DEF 0.4
DPC_EXE 0.4
DPC_INFO 1.1
DPC_OUT 1.3
DPS_SPS 1.0
DRAGI_R 1.7
ENC_DEF 3.6
ENC_EXE 3.8
EQ_D 1.0
EQ_R 1.9
EXP_R 1.5
EXPT_R 2.7
F_TRGM 0.3
F_TRIG 0.3
FF_D 0.9
FF_D_MEM 1.4
FF_RS 0.7

SIPROTEC 5, 7SJ82/7SJ85, Manual 1775


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.79 CFC

Element Ticks
FF_RS_MEM 1.2
FF_SR 0.8
FF_SR_MEM 1.1
GE_D 0.9
GE_R 1.1
GT_D 0.9
GT_R 1.2
HOLD_D 1.1
HOLD_R 1.0
INC_INFO 0.9
LE_D 1.1
LE_R 1.1
LIML_R 1.5
LIMU_R 1.5
LN_R 3.3
LOG_R 1.2
LOOP 1.5
LT_D 0.9
LT_R 0.9
MAX_D 0.9
MAX_R 1.4
MEMORY_D 0.9
MEMORY_R 1.1
MIN_D 0.7
MIN_R 1.3
MOD_D 1.5
MUL_D4 2.5
MUL_R4 2.7
MUL_XMV 2.8
MUX_D 1.2
MUX_R 0.9
NAND10 3.5
NE_D 0.9
NE_R 0.9
NEG 1.2
NEG_SPS 0.8
NL_LZ 3.8
NL_MV 5.6
NL_ZP 2.7
NOR10 3.2
OR_DYN 1.1
OR_SPS 1.3
OR10 2.6
R_TRGM 0.4
R_TRIG 0.4
REAL_DINT 3.0
REAL_SXMV 3.0

1776 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.79 CFC

Element Ticks
SIN_R 0.8
SPC_DEF 0.4
SPC_EXE 0.4
SPC_INFO 0.4
SPC_OUT 0.4
SPLIT_ACD 3.4
SPLIT_ACT 1.0
SPLIT_BSC 1.3
SPLIT_CMV 2.2
SPLIT_DEL 2.0
SPLIT_DPS 1.0
SPLIT_INS 0.5
SPLIT_Q 0.7
SPLIT_SPS 0.8
SPLIT_WYE 2.6
SPLIT_XMV 2.1
SQRT_R 0.6
SUB_D 1.3
SUB_R 1.6
SUB_XMV 2.4
SUBST_B 1.0
SUBST_BQ 1.5
SUBST_D 1.0
SUBST_R 1.0
SUBST_XQ 1.4
SXMV_REAL 3.0
TAN_R 1.1
TLONG 2.2
TOF 1.0
TON 1.1
TP 2.5
TSHORT 1.9
UINT_DINT 3.0
XOR2 2.6

SIPROTEC 5, 7SJ82/7SJ85, Manual 1777


C53000-G5040-C017-A, Edition 06.2019
Technical Data
12.80 Point-on-Wave Switching

12.80 Point-on-Wave Switching


You can find more information about the technical data of the Point-on-wave switching function in the
Point-on-Wave Switching Function Manual.

1778 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
A Appendix

A.1 Order Configurator and Order Options 1780


A.2 Ordering Accessories 1781
A.3 Typographic and Symbol Conventions 1783
A.4 Standard Variants for 7SJ82 1786
A.5 Standard Variants for 7SJ85 1789
A.6 Current Transformer Requirements 1793
A.7 Connection Examples for Current Transformers 1796
A.8 Connection Examples of Voltage Transformers for Modular Devices 1803
A.9 Connection Examples of Voltage Transformers for Non-Modular Devices 1809
A.10 Prerouting 7SJ82/85 General 1813
A.11 Prerouting 7SJ82/85 Capacitor Bank Applications 1815

SIPROTEC 5, 7SJ82/7SJ85, Manual 1779


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.1 Order Configurator and Order Options

A.1 Order Configurator and Order Options


Order Configurator
The order configurator assists you in the selection of SIPROTEC 5 products. The order configurator is a Web
application that can be used with any browser. The order configurator can be used to configure complete
devices or individual components, such as communication modules, expansion modules, or other accessories.
At the end of the configuration process, the product code and a detailed presentation of the configuration
result are provided. The product code unambiguously describes the selected product and also serves as an
order number.

Ordering Options
The following ordering options are possible for SIPROTEC 5 products:

• Device

• Single part

• DIGSI 5

• Functional enhancement

NOTE

i To order single parts in the order configurator, use the Single part link.

Individual parts are:

• Expansion module

• Plug-in module

• Sensors for arc protection

• Operation panel

• Terminal

• Accessories

1780 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.2 Ordering Accessories

A.2 Ordering Accessories

NOTE

i To order terminals, terminal accessories, and mechanical accessories in the order configurator, use the
Single part link.

Table A-1 Accessories

Group Accessories
Terminal Voltage terminal, terminal block, 14-pole
Terminal Voltage input (power supply)
Terminal block, 2-pole175
Terminal Type A current terminal, 4 x protection
(for modular devices)
Terminal Type A current terminal, 3 x protection and 1 x measurement
(for modular devices)
Terminal Type A current terminal, 4 x measurement
(for modular devices)
Terminal Type B current terminal, 4 x protection
(for non-modular devices)
Terminal Type B current terminal, 3 x protection and 1 x measurement
(for non-modular devices)
Terminal 2-pole cross connector for current terminal
Terminal Terminals for IO110, IO112, IO113175
Terminal Terminals and shielding for IO111175,176,177
Terminal Terminal kit only for IO23x175 only
Terminal 2-pole cross connector for voltage terminal
Terminal Cover for current terminal block
Terminal Cover for voltage terminal block
Terminal Transport safety, current terminal
Terminal Transport safety, voltage terminal
Terminal Terminals for low-voltage applications
Terminal 8 x voltage terminal, 14-pole
Terminal 2 x voltage terminal, 2-pole
Accessories USB covers (10 pieces each for CP 100, 200, 300)
Accessories Cable, integrated operation panel, 0.43 m
Accessories Cable, detached operation panel, 2.50 m
Accessories Cable, detached operation panel, 5.00 m
Accessories Cable set, COM link cable
Accessories Cover plate for plug-in modules
Accessories Set of angle rails
Accessories 10 x labeling strip, LEDs/function keys
Accessories 5 x labeling strips, push-buttons
Accessories Set of parts, mounting bracket 1/2

175 Recommended tightening torque when screwing down the terminal on the rear plate: 0.3 Nm
176 The set consists of terminals and shielding for the IO111 for the terminal positions M and N.
177 Only for non-modular devices 7xx82

SIPROTEC 5, 7SJ82/7SJ85, Manual 1781


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.2 Ordering Accessories

Group Accessories
Accessories Set of parts, mounting bracket 2/3
Accessories Set of parts, mounting bracket 5/6
Accessories Set of parts, mounting bracket 1/1
Accessories 4 x screw cover 1/3, type C11
Accessories 4 x screw cover 1/3, type C22
Accessories 4 x screw cover 1/6, type C21
Accessories 2 x bus termination plate
Accessories Assembly frame for panel surface mounting for non-modular
devices 7xx81 and 7xx82 devices
Accessories SDHC memory card for 7KE85
Accessories 10 x battery holder
Accessories Connecting cable for 2nd row
Accessories DIGSI 5 USB cable 2.0
Sensors for arc protection Point sensor with line length of 3 m
Sensors for arc protection Point sensor with line length of 4 m
Sensors for arc protection Point sensor with line length of 5 m
Sensors for arc protection Point sensor with line length of 7 m
Sensors for arc protection Point sensor with line length of 10 m
Sensors for arc protection Point sensor with line length of 15 m
Sensors for arc protection Point sensor with line length of 20 m
Sensors for arc protection Point sensor with line length of 35 m
Sensors for arc protection Line sensor, length 3 m
Sensors for arc protection Line sensor, length 10 m
Sensors for arc protection Line sensor, length 20 m
Sensors for arc protection Line sensor, length 30 m
Sensors for arc protection Line sensor, length 40 m
Sensors for arc protection Supply line for line sensors, length 3 m
Sensors for arc protection Supply line for line sensors, length 5 m
Sensors for arc protection Supply line for line sensors, length 10 m

1782 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.3 Typographic and Symbol Conventions

A.3 Typographic and Symbol Conventions


The following typefaces are used to characterize parameters in the text:
Mode Parameter name
_:661:1 Parameter address
_ stands for the address combination from function
group:function
661, for example, stands for the address of the
setting parameter
from Parameter state

The following symbols are used in drawings:


Icon Description
Parameter

Parameters with setting values


The default setting is in the 1st position and displayed
in italics

Parameters with application-dependent setting values

Dynamic settings:

State logic

Health of a function, stage, or function block

External binary input signal with indication number

External output signal with indication number and


additional information

External output signal without indication number

Measured output value

SIPROTEC 5, 7SJ82/7SJ85, Manual 1783


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.3 Typographic and Symbol Conventions

Icon Description
Binary input signal derived from an external output
signal

Internal input signal

Internal output signal

Analog input signal

Reset/Block a logic element

AND gate

OR gate

XOR gate

Negation

Threshold stage exceeded

Threshold stage exceeded with


reset of input

Threshold stage shortfall

Threshold stage shortfall with


reset of input

Threshold stage exceeded with


dropout delay
Threshold stage exceeded with
dropout delay and reset of input

Threshold stage shortfall with


Dropout delay
Threshold stage shortfall with
dropout delay and reset of input

Comparators

Pickup delay

Dropout delay

Pickup and dropout delay

1784 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.3 Typographic and Symbol Conventions

Icon Description
Trigger the pulse of duration T with a positive signal
edge

Trigger the pulse of duration T with a negative signal


edge

SR-Flip-Flop, RS-Flip-Flop, D-Flip-Flop

Characteristic curve

Minimum operate time

SIPROTEC 5, 7SJ82/7SJ85, Manual 1785


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.4 Standard Variants for 7SJ82

A.4 Standard Variants for 7SJ82

[sv82typ01-120913-01.tif, 1, en_US]

Figure A-1 Standard Variant Type U1

[sv82typ02-120913-01.tif, 1, en_US]

Figure A-2 Standard Variant Type U2

1786 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.4 Standard Variants for 7SJ82

[sv82typ03-120913-01.tif, 1, en_US]

Figure A-3 Standard Variant Type U3

[sv82typ04-120913-01.tif, 1, en_US]

Figure A-4 Standard Variant Type U4

SIPROTEC 5, 7SJ82/7SJ85, Manual 1787


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.4 Standard Variants for 7SJ82

[svut82typ01-210114-01, 1, en_US]

Figure A-5 Standard Variant Type U5

1788 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.5 Standard Variants for 7SJ85

A.5 Standard Variants for 7SJ85

[svstyp01-191112-01.tif, 1, en_US]

Figure A-6 Standard Variant Type S1

[svstyp02-191112-01.tif, 1, en_US]

Figure A-7 Standard Variant Type S2

SIPROTEC 5, 7SJ82/7SJ85, Manual 1789


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.5 Standard Variants for 7SJ85

[svstyp03-191112-01.tif, 1, en_US]

Figure A-8 Standard Variant Type S3

1790 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.5 Standard Variants for 7SJ85

[svstyp04-191112-01.tif, 1, en_US]

Figure A-9 Standard Variant Type S4

SIPROTEC 5, 7SJ82/7SJ85, Manual 1791


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.5 Standard Variants for 7SJ85

[svstyp05-191112-01.tif, 1, en_US]

Figure A-10 Standard Variant Type S5

1792 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.6 Current Transformer Requirements

A.6 Current Transformer Requirements


The requirements for phase current transformers are usually determined by the overcurrent protection, partic-
ularly by the high-current element settings. Besides, there is a minimum requirement based on experience.
The recommendations are given according to the standard IEC 60044-1.
The standards IEC 60044-6, BS 3938 and ANSI/IEEE C 57.13 are referred to for converting the requirement into
the knee-point voltage and other transformer classes.

Accuracy Limiting Factors

Table A-2 Effective and Rated Accuracy Limiting Factor

Required minimum effective accu-


racy limiting factor

but at least 20
with
KALF' Minimum effective accuracy limiting factor
I>>PU Primary pickup value of the high-current
element
Irated,prim Primary rated transformer current
Resulting rated accuracy limiting
factor

with
KALF Rated accuracy limiting factor
RBC Connected burden (device and cables)
RBN Rated burden
RCt Internal burden

Table A-3 Calculation Example According to IEC 60044–1

Irated,sec = 1 A
KALF' = 20
RBC = 0.6 Ω (device and cables)
KALF set to 10,
RCt = 3 Ω
so that: 5P10, 5 VA
RBN = 5 Ω (5 VA)
with
Irated,sec = Secondary rated transformer current

Class Conversion

Table A-4 Conversion into Other Classes

British Standard BS 3938

ANSI/IEEE C 57.13, class C

Irated,sec = 5 A (typical value)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1793


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.6 Current Transformer Requirements

IEC 60044-6 (transient response),


class TPS

K≈ 1
KSSC≈ KALF
Classes TPX, TPY, TPZ
You can find a calculation example in the above section Accuracy
Limiting Factors with: KSSC≈ KALF
TP depending on power system and specified closing sequence
with
Vk Knee-point voltage
RCt Internal burden
RBN Rated burden
Irated,sec Secondary rated transformer current
KALF Rated accuracy limiting factor
Vs.t.max Secondary terminal voltage at 20 Irated,prim
Val Secondary magnetization limit voltage
K Dimensioning factor
KSSC Factor symmetric rated fault current
TP Primary time constant

Cable Core Balance Current Transformer


The requirements to the cable core balance current transformer are determined by the function Sensitive
ground-fault detection.
The recommendations are given according to the standards IEC 60044-1 and IEC 61869-2.

Table A-5 Requirements to the cable core balance current transformer according to IEC 60044-1 and
IEC 61869-2

Transformation ratio, typical 60 / 1


It may be necessary to select a different transforma-
tion ratio to suit the specific power system and thus
the corresponding amount of the maximum ground
fault current.
Accuracy limiting factor FS = 10
Power 1 to 4 times the connected burden (device input plus
infeeds)
Notes concerning the power:
The burden of the sensitive ground-current input is very low (0.05 VA or 0.1 VA). Thus, an underburden of
more than factor 4 is probable. In this case, clarify the suitability of the class accuracy concerning an impor-
tant underburden with the transformer manufacturer. If necessary, request the accuracy for the range from 0
VA to the rated burden. This specification is then outside the standard, but in practice, it is possible in most
cases.
(Relevant standard: IEC 61869-2, Chapter 5.6.201.4 Extended burden range. There, the range 1 VA to rated
burden is specified for rated burdens smaller than 15 VA.)

Table A-6 Minimum Required Class Accuracy Depending on Neutral Grounding and Function Operating
Principle

Neutral Point Isolated Resonant-Grounded High-Resistance


Grounded
Function directional Class 1 Class 1 Class 1

1794 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.6 Current Transformer Requirements

Function non-directional Class 3 Class 1 Class 3

NOTE

i The class accuracy according to IEC 61869-2 below 5% Irated (< 50 mA secondary) is not defined in general.
For very sensitive directional measurements, Siemens recommends the classes 0.5S or 0.1S that define the
class accuracy via an extended current range (up to 1% Irated) (see chapter 5.6.201.5, IEC 61869-2).
Another possibility is to correct the phase-angle error of the transformer on the device, if this error is
known (see function description Sensitive ground-fault detection.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1795


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.7 Connection Examples for Current Transformers

A.7 Connection Examples for Current Transformers

[ti3leit1-070211-01.tif, 3, en_US]

Figure A-11 Connection to 3 Phase Current Transformers (Zero-Sequence Current to be Calculated)

[tileite2-070211-01.tif, 3, en_US]

Figure A-12 Connection to 3 Phase Current Transformers and a Measured Zero-Sequence Current (Current
in Common Return Conductor)

NOTE

i The switchover of the current polarity at the 3-phase current transformer causes a rotation in the direction
of electric current for current input I4 (IN)!

1796 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.7 Connection Examples for Current Transformers

[tileite3-260313-01.tif, 3, en_US]

Figure A-13 Connection to 3 Phase Current Transformers and a Cable Type Current Transformer for Sensi-
tive Ground-Fault Detection

NOTE

i The switchover of the current polarity at the 3-phase current transformer causes a rotation in the direction
of electric current for current input I4 (IN-sep)!

[tileite4-260313-01.tif, 3, en_US]

Figure A-14 Connection to 3 Phase Current Transformers and a Measured Ground Current from a Complete
Holmgreen Connection

SIPROTEC 5, 7SJ82/7SJ85, Manual 1797


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.7 Connection Examples for Current Transformers

NOTE

i The switchover of the current polarity at the 3-phase current transformer causes a rotation in the direction
of electric current for current input I4 (IN-sep)!

[tileite6-060313-01.tif, 3, en_US]

Figure A-15 Connection to 3 Phase Current Transformers and a Measured Ground Current via the Neutral-
Point Current Transformer of a Grounded Power Transformer

[tileite7-070211-01.tif, 3, en_US]

Figure A-16 Connection to a 2 Phase Current Transformers – for Isolated or Resonant-Grounded Systems
Only

1798 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.7 Connection Examples for Current Transformers

[tileite8-260313-01.tif, 3, en_US]

Figure A-17 Connection to 2 Phase Current Transformers and a Cable Type Current Transformer for Sensi-
tive Ground-Fault Detection – for Isolated or Resonant-Grounded Systems Only

NOTE

i The switchover of the current polarity at the 3-phase current transformer causes a rotation in the direction
of electric current for current input I4 (IN-sep)!

[tileite9-260313-01.tif, 3, en_US]

Figure A-18 Connection to 3 Phase Current Transformers and an Additional Current Transformer in the
Neutral Point of a Grounded Power Transformer

SIPROTEC 5, 7SJ82/7SJ85, Manual 1799


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.7 Connection Examples for Current Transformers

[tileit10-260313-01.tif, 3, en_US]

Figure A-19 Current Transformer Connection for High-Impedance Differential Protection (for Example, a
Power Transformer, in Preparation)

1800 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.7 Connection Examples for Current Transformers

[tileit14-260313-10.tif, 4, en_US]

Figure A-20 Connection to 2 Phase Current Transformers and a Cable Type Current Transformer for Sensi-
tive Ground-Fault Detection of the Line and Additional Sensitive Ground-Fault Detection via
the Neutral-Point Current Transformer of a Grounded Power Transformer

NOTE

i The switchover of the current polarity at the 3-phase current transformer causes a rotation in the direction
of electric current for current input I3 (IN-sep)!

SIPROTEC 5, 7SJ82/7SJ85, Manual 1801


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.7 Connection Examples for Current Transformers

[ti_leite_15, 1, en_US]

Figure A-21 Connection to 2 Phase Current Transformers and an Additional Cable Type Current Trans-
former for Sensitive Ground-Fault Detection via a Sensitive Input (I4) and an Input of Normal
Sensitivity (I2; IN2 and IN)

NOTE

i The switchover of the current polarity at the 3-phase current transformer causes a rotation in the direction
of electric current for current inputs I2 and I4 (IN-sep)!

1802 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.8 Connection Examples of Voltage Transformers for Modular Devices

A.8 Connection Examples of Voltage Transformers for Modular Devices

[tvvolta1-260313-01.tif, 1, en_US]

Figure A-22 Connection to 3 Star-Connected Voltage Transformers

[tvvolta2-260313-01.tif, 1, en_US]

Figure A-23 Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding

SIPROTEC 5, 7SJ82/7SJ85, Manual 1803


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.8 Connection Examples of Voltage Transformers for Modular Devices

[tvvolta3-260313-01.tif, 1, en_US]

Figure A-24 Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding of a
Separate Voltage Transformer (for Example Busbar)

1804 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.8 Connection Examples of Voltage Transformers for Modular Devices

[tvvolta4-260313-01.tif, 2, en_US]

Figure A-25 Connection to 3 Star-Connected Voltage Transformers and to the Phase-to-Phase Voltage of a
Busbar Voltage Transformer (for Example for Synchrocheck Applications)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1805


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.8 Connection Examples of Voltage Transformers for Modular Devices

[tvvolta5-260313-01.tif, 1, en_US]

Figure A-26 Connection to V-Connected Voltage Transformer (Delta-Connected Device Input Transformer)
and Connection to the Phase-to-Phase Voltage of a Busbar Voltage Transformer

NOTE

i When using the connection type 3-phase-to-phase voltage, the zero-sequence voltage cannot be detected.

1806 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.8 Connection Examples of Voltage Transformers for Modular Devices

[tvvolta6-260313-01.tif, 1, en_US]

Figure A-27 Connection to V-Connected Voltage Transformer (Delta-Connected Device Input Transformer)
and Connection to the Broken-Delta Winding of a Busbar Voltage Transformer

[tvvol2ll-260313-01.tif, 2, en_US]

Figure A-28 Connection to V-Connected Voltage Transformer (Measurement of 2 Phase-to-Phase Voltages)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1807


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.8 Connection Examples of Voltage Transformers for Modular Devices

[tvl2lluu-260313-01.tif, 2, en_US]

Figure A-29 Connection to V-Connected Voltage Transformer (Measurement of 2 Phase-to-Phase Voltages)


and Connection to the Broken-Delta Winding of a Busbar Voltage Transformer

[tvvolta7-260313-01.tif, 1, en_US]

Figure A-30 Connection to a 1-Pole Insulated Voltage Transformer (Phase-to-Ground Voltage)

1808 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.9 Connection Examples of Voltage Transformers for Non-Modular Devices

A.9 Connection Examples of Voltage Transformers for Non-Modular


Devices

[tvvolta1-260313-01.tif, 1, en_US]

Figure A-31 Connection to 3 Star-Connected Voltage Transformers

[tvvolta3-260313-01.tif, 1, en_US]

Figure A-32 Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding of a
Separate Voltage Transformer (for Example, Busbar)

SIPROTEC 5, 7SJ82/7SJ85, Manual 1809


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.9 Connection Examples of Voltage Transformers for Non-Modular Devices

[tvvolta4-260313-01.tif, 2, en_US]

Figure A-33 Connection to 3 Star-Connected Voltage Transformers and to the Phase-to-Phase Voltage of a
Busbar Voltage Transformer (for Example, for Synchrocheck Applications)

[tvvol2ll82-260313-01.vsd, 1, en_US]

Figure A-34 Connection to V-Connected Voltage Transformer (Measurement of 2 Phase-to-Phase Voltages)

1810 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.9 Connection Examples of Voltage Transformers for Non-Modular Devices

[tvl2lluu82-260313-01.vsd, 1, en_US]

Figure A-35 Connection to V-Connected Voltage Transformer (Measurement of 2 Phase-to-Phase Voltages)


and Connection to the Broken-Delta Winding of a Busbar Voltage Transformer

SIPROTEC 5, 7SJ82/7SJ85, Manual 1811


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.9 Connection Examples of Voltage Transformers for Non-Modular Devices

[tvvolta5SJ82-260313-01.vsd, 2, en_US]

Figure A-36 Connection to V-Connected Voltage Transformer (Measurement of 2 Phase-to-Phase Voltages)


and Connection to the Broken-Delta Winding of a Busbar Voltage Transformer (for Example,
for Synchrocheck Applications)

[tvvolta7SJ82-260313-01.vsd, 1, en_US]

Figure A-37 Connection to a 1-Pole Insulated Voltage Transformer (Phase-to-Ground Voltage)

1812 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.10 Prerouting 7SJ82/85 General

A.10 Prerouting 7SJ82/85 General


Meaning of the abbreviations in DIGSI, see 8.2.2.3 Connection Variants of the Circuit Breaker.

Binary Inputs

Table A-7 Default Binary Inputs, Using the Example of Overcurrent Protection

Binary Signal Number Signal Type Configura-


Input tion
BI1 Circuit breaker 1:Circuit break.:Position 201.4261.58 DPC OH
BI2 Circuit breaker 1:Circuit break.:Position 201.4261.58 DPC CH
BI3 Disconnector 1:Circuit break.:Position 601.5401.58 DPC OH
BI4 Disconnector 1:Circuit break.:Position 601.5401.58 DPC CH
BI5 Disconnector 2:Circuit break.:Position 602.5401.58 DPC OH
BI6 Disconnector 2:Circuit break.:Position 602.5401.58 DPC CH
BI7 Disconnector 3:Circuit break.:Position 603.5401.58 DPC OH
BI8 Disconnector 3:Circuit break.:Position 603.5401.58 DPC CH
BI9 Power system:Meas. point V-3ph 1:VT- 11.941.2641.500 SPS H
miniature CB:>Open

Binary Outputs

Table A-8 Default Output Relays, Using the Example of Overcurrent Protection

Binary Signal Number Signal Type Configura-


Output tion
BO1 Circuit breaker 1:Circuit break.:Trip/open 201.4261.300 SPS U
cmd.
BO2 Circuit breaker 1:Circuit break.:Close 201.4261.301 SPS X
command
BO3 Disconnector 1:Disconnector:Open 601.5401.300 SPS X
command
BO4 Disconnector 1:Disconnector:Close 601.5401.301 SPS X
command
BO5 Disconnector 2:Disconnector:Open 602.5401.300 SPS X
command
BO6 Disconnector 2:Disconnector:Close 602.5401.301 SPS X
command
BO7 Disconnector 3:Disconnector:Open 603.5401.300 SPS X
command
BO8 Disconnector 3:Disconnector:Close 603.5401.301 SPS X
command

Function Keys

Table A-9 Default Setting Function Key Using the Example of Overcurrent Protection

Function Signal Number Signal Type Configura-


Key tion
F-key1 Main menu:Logs:Operational log X
F-key2 Main menu:Measurements:VI 3ph X
1:Operational values
F-key3 Main menu:Logs:Fault log X

SIPROTEC 5, 7SJ82/7SJ85, Manual 1813


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.10 Prerouting 7SJ82/85 General

Light-Emitting Diodes

Table A-10 Default LED Displays, Using the Example of Overcurrent Protection

LEDs Signal Number Signal Type Configura-


tion
LED1 VI 3ph 1:Group indicat.:Pickup:phs A SPS NT
LED2 VI 3ph 1:Group indicat.:Pickup:phs B SPS NT
LED3 VI 3ph 1:Group indicat.:Pickup:phs C SPS NT
LED4 VI 3ph 1:Group indicat.:Pickup:phs gnd SPS NT
LED5 Circuit breaker 1:Circuit break.:Trip/ 201.4261.300 SPS L
open cmd.
LED15 Alarm handling:Group warning 5971.301 SPS U
LED16 Device:Process mode inactive SPS U
General:Functions in Test mode 91.329 SPS U

1814 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.11 Prerouting 7SJ82/85 Capacitor Bank Applications

A.11 Prerouting 7SJ82/85 Capacitor Bank Applications


Meaning of the abbreviations in DIGSI, see8.2.2.3 Connection Variants of the Circuit Breaker

Binary Inputs

Table A-11 Default Binary Inputs, Using the Example of Overcurrent Protection

Binary input Signal Number Signal type Configuration


BI1 Circuit breaker 201.4261.58 DPC OH
1:Circuit
break.:Position
BI2 Circuit breaker 201.4261.58 DPC CH
1:Circuit
break.:Position

Binary Outputs

Table A-12 Default Output Relays, Using the Example of Overcurrent Protection

Binary output Signal Number Signal type Configuration


BO1 Circuit breaker 201.4261.300 SPS U
1:Circuit
break.:Trip/open
cmd.
BO2 Circuit breaker 201.4261.301 SPS X
1:Circuit
break.:Close
command

Function Keys

Table A-13 Default Setting Function Key Using the Example of Overcurrent Protection

Function key Signal Number Signal type Configu-ration


F-key1 Main X
menu:Logs:Opera-
tional log
F-key2 Main menu:Meas- X
urements :Capacitor
bank 1:Operational
values
F-key3 Main X
menu:Logs:Fault log

Light-Emitting Diodes

Table A-14 Default LED Displays, Using the Example of Overcurrent Protection

LEDs Signal Number Signal type Configura-tion


LED1 Capacitor bank 1:Group SPS NT
indicat.:Pickup:phs A
LED2 Capacitor bank 1:Group SPS NT
indicat.:Pickup:phs B

SIPROTEC 5, 7SJ82/7SJ85, Manual 1815


C53000-G5040-C017-A, Edition 06.2019
Appendix
A.11 Prerouting 7SJ82/85 Capacitor Bank Applications

LEDs Signal Number Signal type Configura-tion


LED3 Capacitor bank 1:Group SPS NT
indicat.:Pickup:phs C
LED4 Capacitor bank 1:Group SPS NT
indicat.:Pickup:phs gnd
LED5 Circuit breaker 1:Circuit 201.4261.300 SPS L
break.:Trip/open cmd.
LED15 Alarm handling:Group 5971.301 SPS U
warning
LED16 Device:Process mode inac- SPS U
tive
General:Functions in Test 91.329 SPS U
mode

1816 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

ACD
IEC 61850 data type: Directional protection activation information

ACK
Data transfer acknowledgment

ACT
IEC 61850 data type: Protection activation information

APC
Controllable analog set point information

ASDU
ASDU stands for Application Service Data Unit. An ASDU can consist of one or more identical information
objects. A sequence of the same information elements, for example measured values, is identified by the
address of the information object. The address of the information object defines the associated address of the
first information element of the sequence. A consecutive number identifies the subsequent information
elements. The number builds on this address in integral increments (+1).

BAC
Binary Controlled Analog Process Value

Back-up battery
The back-up battery ensures that specified data areas, flags, times and counters are kept retentive.

Bay controller
Bay controllers are devices with control and monitoring functions without protection functions.

BCR
IEC 61850 data type: Binary Counter Reading

Best master clock algorithm


A PTP network contains communicating clocks. With the best master clock algorithm (BMC), the device indi-
cating the most precise time is determined. This device is used as a reference clock and is designated as grand-
master. If the network topology is changed, the BMC algorithm is executed again on network segments that
are possibly disconnected from the grandmaster. If a participating device is a master and a slave, it is called a
boundary clock.

Big-endian
Big-endian and little-endian describe the order in which a sequence of bytes is stored. In big-endian systems,
the most significant byte is stored at the lowest storage address. In little-endian systems, the most significant
byte is stored at the highest storage address.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1817


C53000-G5040-C017-A, Edition 06.2019
Glossary

Binary Controlled Analog Process Value


The data type BAC represents a command with or without feedback. The BAC is used for example for the
control of an arc suppression coil. The commands Higher, Lower, and Stop are possible. The feedback from
the process is an analog value.

Binary Controlled Step Position


The data type BSC can, for example, be used to control a transformer tap changer. The commands up, down
can be given.

Bit pattern indication


A bit pattern indication is a processing function, with the help of which adjacent numerical process informa-
tion can be logged coherently and processed further in parallel via multiple inputs. The bit pattern indication
can be selected as 1, 2, 3 or 4 bytes.

BMC
Best Master Clock Algorithm

Boundary clock
The Precision Time Protocol knows different types of clocks: an ordinary clock (abbreviation: OC), a boundary
clock (BC), and a transparent clock (TC). The boundary clock transports time information over a network limit,
for example, in a router connecting different switched networks: As a slave, the clock of the router receives
the time information and transmits this further on as a master.

BRCB
Buffered Report Control Block

BSC
Binary Controlled Step Position

Buffered Report Control Block


Buffered Report Control Block (BRCB) is a form of report controlling. Internal events trigger the immediate
sending of reports or saving of events for the transfer. Data values cannot therefore be lost on account of
transport flow control conditions or connection interruptions. BRCB provides the functionality SOE (see
Sequence of Events).

CB
Circuit breaker

CDC
Common Data Class

CFC
Continuous Function Chart

Chatter blocking
A rapidly intermittent input (for example, owing to a relay contact fault) is disconnected after a parameteriz-
able monitoring time and therefore cannot generate any more signal changes. The function prevents the
system from overloading in the event of an error.

CID
Configured IED Description

1818 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

CMV
Complex measured value

Combination device
Combination devices are bay units with protection functions and with feeder mimic diagram.

Common Data Class


Generic term for a data class according the IEC 61850 model.

Communication branch
A communication branch corresponds to the configuration of 1 to n participants communicating via a joint
bus.

Configured IED Description


A Configured IED Description (CID) is a file for data exchange between the IED Configuration Tool and the IED
itself.

Container
If an object contains other objects, this is referred to as a container. The object Folder is an example of such a
container.

Continuous Function Chart


The Continuous Function Chart (CFC) is a programming language. It is used for programmable logic control-
lers. The programming language Continuous Function Chart is not defined in the standard IEC 61131-3, but
represents a current extension of IEC programming environments. CFC is a graphic programming language.
Function blocks are linked to one another. This represents an essential difference from conventional program-
ming languages, where sequences of commands are entered.

Control display
The control display becomes visible for devices with a large display after pressing the Control key. The diagram
contains the switching devices to be controlled in the feeder. The control display serves for implementing
switching operations. Specification of this diagram forms part of configuring.

Controllable Integer Status


The data type INC can be used to issue a command (to one or more relays, selectable under information
routing) that is monitored via a whole number as feedback.

Controller
The controller initiates the IO data communication.

CRC
Cyclic redundancy check

Data type
The data type is a value set of a data object, together with the operations allowed on this value set. A data
type contains a classification of a data element, such as the determination whether it consists of integers,
letters, or similar.

Data unit
Information item with a joint transmission source. Abbreviation: DU – Data Unit

SIPROTEC 5, 7SJ82/7SJ85, Manual 1819


C53000-G5040-C017-A, Edition 06.2019
Glossary

Data window
The right area of the project window visualizes the content of the area selected in the navigation window. The
data window contains for example, indications or measured values of the information lists or the function
selection for parameterization of the device.

DCF
Device Configuration File

DCF77
The precise official time is determined in Germany by the Physikalisch-Technische Bundesanstalt PTB in Bruns-
wick. The atomic clock unit of the PTB transmits this time via the long-wave time signal transmitter in Main-
flingen near Frankfurt/Main. The emitted time signal can be received within a radius of approx. 1500 km from
Frankfurt/Main.

DCP
Discovery and Basic Configuration Protocol

DDD
DIGSI 5 Device Driver – SIPROTEC 5 device driver which must be loaded in DIGSI.

DEL
Phase-to-phase related measurements of a 3-phase system

Device 5 Export Format


DEX5

DEX5
Device 5 Export Format
You can archive the data from an individual SIPROTEC 5 device in DEX5 format.

DHCP
Dynamic Host Configuration Protocol

DIGDNP
DIGSI 5 protocol settings for DNP3
File extension for a file generated by DIGSI for exporting the protocol configuration from DIGSI 5.

DIGMOD
DIGSI 5 protocol settings for Modbus TCP
File extension for a file generated by DIGSI for exporting the protocol configuration from DIGSI 5.

DIGSI
Configuration software for SIPROTEC

DIGSI 5 Display Pages


You can archive individual or all display pages of a SIPROTEC 5 device in DSP5 format. You can also use this
format to exchange display pages between SIPROTEC 5 devices. The DSP5 format is based on XML.

1820 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

DIGSI 5 protocol settings for DNP3


If the DNP3 protocol is configured for a system interface, you can export the protocol settings in DIGDNP
format. The DIGDNP format is specially designed to transmit interface data from DIGSI 5 into the SICAM PAS
substation automation system.

DIGSI 5 protocol settings for IEC 60870-5-103


If the IEC 60870-5-103 protocol is configured for a system interface, you can export the protocol settings in
DIGT103 format. The DIGT103 format is specially designed to transmit interface data from DIGSI 5 into the
SICAM PAS substation automation system.

DIGSI 5 protocol settings for IEC 60870-5-104


If the IEC 60870-5-104 protocol is configured for a system interface, you can export the protocol settings in
DIGT104 format. The DIGT104 format is specially designed to transmit interface data from DIGSI 5 into the
SICAM PAS substation automation system.

DIGSI 5 protocol settings for Modbus TCP


If the Modbus TCP protocol is configured for a system interface, you can export the protocol settings in
DIGMOD format. The DIGMOD format is specially designed to transmit interface data from DIGSI 5 into the
SICAM PAS substation automation system.

DIGSI 5 Test Sequences


You can archive individual or all test sequences of a SIPROTEC 5 device in SEQ5 format. You can also use this
format to exchange test sequences between SIPROTEC 5 devices. The SEQ5 format is based on XML.

DIGT103
DIGSI 5 protocol settings for IEC 60870-5-103
File extension for a file generated by DIGSI for exporting the protocol configuration from DIGSI 5.

DIGT104
DIGSI 5 protocol settings for IEC 60870-5-104
File extension for a file generated by DIGSI for exporting the protocol configuration from DIGSI 5.

Discovery and Basic Configuration Protocol


The DCP protocol is used to detect devices without IP addresses and to assign addresses to these devices.

DNP3
DNP3 is a communications standard for telecontrol engineering. DNP3 is used as a general transmission
protocol between control systems and substations and between bay devices and the systems control.

Double command
Double commands (DPC – Double Point Control) are process outputs which visualize 4 process states at 2
outputs: 2 defined states (for example, On/Off) and 2 undefined states (for example, disturbed positions).

Double-point indication
Double commands (DPS – Double Point Status) are process indications which visualize 4 process states at 2
inputs: 3 defined states (for example, On/Off and disturbed position) and 1 undefined state (00).

DPC
IEC 61850 data type: Double Point Control

SIPROTEC 5, 7SJ82/7SJ85, Manual 1821


C53000-G5040-C017-A, Edition 06.2019
Glossary

DPS
IEC 61850 data type: Double Point Status

Drag and drop


Copying, moving, and linking function, used in graphic user interfaces. The mouse is used to highlight and
hold objects and then move them from one data area to another.

DSP5
DIGSI 5 Display Pages

DU
Data Unit

Dynamic Host Configuration Protocol


In order to configure PCs automatically, centralized and uniformly in a TCP/IP network, a dynamic assignment
of IP addresses is used. DHCP is used. The system administrator determines how the IP addresses are to be
assigned and specifies the time lapse over which they are assigned. DHCP is defined in the Internet standards
RFC 2131 (03/97) and RFC 2241 (11/97).
For SIPROTEC 5, a device can also be assigned an IP address via DIGSI via DHCP.

ELCAD
Electrical CAD

Electrical CAD
You can import the topology information contained in an ELCAD file into a project and use it as the basis for a
single-line configuration. The other information contained in the ELCAD file is not included in this process.

Electromagnetic compatibility
Electromagnetic compatibility (EMC) means that an item of electrical equipment functions without error in a
specified environment. The environment is not influenced in any impermissible way here.

ENC
Enumerated Status Controllable

ENS
Enumerated Status

ESD protection
The ESD protection is the entirety of all means and measures for the protection of electrostatic-sensitive
devices.

Far End Fault Indication


Far End Fault Indication (FEFI) is a special setting of switches. It is always only possible to log a line interrup-
tion on the receive line. If a line interruption is detected, the link status of the line is changed. The status
change leads to deletion of the MAC address assigned to the port in the switch. However, outage of the
receive line from the aspect of the switch can only be detected in the receiver, that is, by the switch. The
receiver then immediately blocks the transmit line and signals the connection failure to the other device. The
FEFI setting in the switch triggers detection of the error on the receive line of the switch.

FEFI
Far End Fault Indication

1822 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

FG
Function group

Fleeting indication
Fleeting indications are single-point indications present for a very short time, in which only the coming of the
process signal is logged and further processed time-correctly.

Floating
Floating means that a free potential not connected to ground is generated. Therefore no current flows
through the body to ground in the event of touching.

Folder
This object type helps when structuring a project hierarchically.

Function group
Functions are brought together into function groups (FG). The assignment of functions to current and/or
voltage transformers (assignment of functions to measuring points), the information exchange between the
function groups via interfaces as well as the generation of group indications are important for this bringing
together.

General interrogation
The state of all process inputs, of the status, and of the error image are scanned on system startup. This infor-
mation is used to update the system-side process image. Likewise, the current process state can be interro-
gated after data loss with a general interrogation (GI).

General Station Description Mark-up Language


GSDML is an XML-based description language for creating a GSD file.

Generic Object-Oriented Substation Event


GOOSE. Protocol of IEC 61850 for communication between bay units.

GI
General Interrogation

GIN
Generic Identification Number

GOOSE
Generic Object-Oriented Substation Event

Ground
The conductive ground whose electric potential can be set equal to 0 at every point. In the area of grounding
conductors, the ground can have a potential diverging from 0. The term reference ground is also used for
this situation.

Grounding
The grounding is the entirety of all means and measuring for grounding.

GSDML
General Station Description Mark-up Language

SIPROTEC 5, 7SJ82/7SJ85, Manual 1823


C53000-G5040-C017-A, Edition 06.2019
Glossary

Hierarchy level
In a structure with superordinate and subordinate objects, a hierarchy level is a level of equal-ranking objects.

High Availability Seamless Redundancy Protocol


Like PRP (Parallel Redundancy Protocol), HSR (High Availability Seamless Redundancy Protocol) is specified in
IEC 62439-3. Both protocols offer redundancy without switching time.
The principal function can be found in the definition of PRP. With PRP, the same indication is sent via 2 sepa-
rated networks. In contrast to this, in the case of HSR the indication is sent twice in the 2 directions of the ring.
The recipient receives it correspondingly via 2 paths in the ring, takes the 1st message and discards the 2nd
(see PRP).
Whereas NO indications are forwarded in the end device in the case of PRP, a switch function is installed in the
HSR node. Thus, the HSR node forwards indication in the ring that are not directed at it.
In order to avoid circular messages in the ring, corresponding mechanisms are defined in the case of HSR.
SAN (Single Attached Node) end devices can only be connected with the aid of a REDBOX in the case of HSR.
PRP systems and HSR systems can be coupled redundantly with 2 REDBOXES.

HMI
Human-Machine Interface (HMI)

HSR
High Availability Seamless Redundancy Protocol

HV bay description
The HV project description file contains data concerning which bays are present within a ModPara project. The
actual bay information is saved for each bay in an HV bay description file. Within the HV project description
file, each bay receives an HV bay description file through a reference to the file name.

HV project description
If the configuring and parameterization of PCUs and submodules is completed with ModPara, all the data will
be exported. The data is distributed to several files during this process. A file contains data on the basic project
structure. This typically includes information on which bays are present within this project. This file is desig-
nated as an HV project description file.

ICD
IED Capability Description

IEC
International Electrotechnical Commission - International electrotechnical standardization body

IEC 60870-5-103
International standard protocol for communication with IEDs (especially protective equipment). Many protec-
tive relays, bay devices, bay controllers and measurement acquisition devices use the IEC 60870-5-103
protocol to communicate with the SICAM system.

IEC 60870-5-104
Internationally standardized telecontrol protocol. Transmission protocol based on IEC 60870-5-101 for the
connection of the substation control level to the telecontrol center using TCP/IP via a Wide Area Network
(WAN) connection.
IEC 60870-5-104 is also used for the communication with IEDs.

1824 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

IEC 61850
IEC 61850 is an international standard for consistent communication in substations. This standard defines the
communication amongst devices in substations and the related system requirements. All substation automa-
tion functions as well as engineering functions are supported. IEC 61850 can also be transferred to automa-
tion systems in other applications, for example, for the control and monitoring of distributed power genera-
tion.

IEC address
A unique IEC address must be assigned to each SIPROTEC device within an IEC bus. A total of 254 IEC
addresses per IEC bus are available.

IEC communication branch


Within an IEC communication branch, the participants communicate on the basis of the protocol IEC
60870-5-103 via an IEC bus.

IED Capability Description


Data exchange from the IED configuration software (DIGSI) to the system configurator. This file describes the
performance properties of an IED.

IEEE 1588
Time-synchronization protocol according to IEEE Std 1588-2008: Precision Clock Synchronization Protocol for
Networked Measurement and Control Systems (IEEE 1588 v2) and IEEE Std C37.238-2011: IEEE Standard
Profile for Use of IEEE 1588 Precision Time Protocol in Power System Applications (Power Profile).

IID
Instantiated IED Description

INC
Controllable Integer Status

Input data/input direction


Data is sent from the protocol slave to the protocol master.

INS
Integer Status

Instantiated IED Description


Files in IID format are ICD files adapted for the concrete application in the project. This format is mainly suit-
able for exchanging data between DIGSI 5 and an external system configurator or also a substation automa-
tion system such as SICAM PAS. The ICD format uses SCL as the description language for this purpose.

International Electrotechnical Commission


IEC

Internet Protocol
An Internet protocol (IP) enables the connection of participants which are positioned in different networks.

IO
Input-Output

SIPROTEC 5, 7SJ82/7SJ85, Manual 1825


C53000-G5040-C017-A, Edition 06.2019
Glossary

IO Provider Status
The provider (sender) of an IO data element uses this to signal the status (good/bad with error location).

IOPS
IO Provider Status

IP
Internet Protocol

IPv4
Internet-Protocol Version 4

ISC
Integer Step Controlled Position Information

LAN
Local Area Network

Link address
The link address indicates the address of a SIPROTEC device.

Link Layer Discovery Protocol


The Link Layer Discovery Protocol supplies the basis for topology detection and for determination of the
configuration.

List view
The right area of the project window displays the names and symbols of the objects which are within a
container selected in the tree view. As the visualization is in the form of a list, this area is also referred to as list
view.

LLDP
Link Layer Discovery Protocol

Local Area Network


A Local Area Network (LAN) is a regional, local PC network. The PCs are all equipped with a network interface
card and work with one another via data exchange. The LAN requires an operating system on each PC and
standardized data transport software. The operating systems can be different, as can the data transport soft-
ware, but both must support a common transmission protocol (= TCP/IP protocols), so that all PCs can
exchange data with one another.

LSB
Least Significant Bit

MAC address
The MAC address (Media Access Control) is the hardware address of each single system adaptor. With the MAC
address, the device can be identified unambiguously in the system.

Management Information Base


A Management Information Base (MIB) is a database which saves information and statistics concerning each
device in a network continuously. The performance of each device can be monitored with this information and

1826 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

statistics. In this way, it can also be ensured that all devices in the network function properly. MIBs are used
with SNMP.

Manufacturing Message Specification


The standard Manufacturing Message Specification (MMS) serves for data exchange. The standard is used for
the transmission protocols IEC 61850 and IEC 60870-6 TASE.2.

Measured Value
This data type provides a measured value that can be used as a CFC result, for instance.

Metered value
Metered values are a processing function, used to determine the total number of discrete similar events
(counting pulses), for example, as integral over a time span. In the power supply utility field, electrical energy
is often recorded as a metered value (energy import/delivery, energy transport).

MIB
Management Information Base

MICS
Model Implementation Conformance Statement

MMS
Manufacturing Message Specification

Modbus
The Modbus protocol is a communication protocol. It is based on a Master/Slave or Client/Server architecture.

Model Implementation Conformance Statement


Model Implementation Conformance Statement (see MICS)
The Model Implementation Conformance Statement describes in detail the standard data object models that
are supported by the system or by the device.

Module
Self-contained unit at the device level. This can be a real module or a functional unit of the device.

MSB
Most Significant Bit

MV
Data type Measured Value

NACK
Negative acknowledgment

Navigation window
Left area of the project window, which visualizes the names and symbols of all containers of a project in the
form of a hierarchical tree structure.

Object
Each element of a project structure is designated as an object in DIGSI 5.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1827


C53000-G5040-C017-A, Edition 06.2019
Glossary

Object property
Each object has properties. These can on the one hand be general properties that are common to several
objects. Otherwise, an object can also have object-specific properties.

Offline
If there is no communication connection between a PC program (for example, configuration program) and a
runtime application (for example, a PC application), the PC program is offline. The PC program executes in
Offline mode.

Online
If there is a communication connection between a PC program (for example, configuration program) and a
runtime application (for example, a PC application), the PC program is online. The PC program executes in
Online mode.

Optical Switch Module


An Optical Switch Module (OSM) is a process for switching over switches in Ethernet networks that are ring-
shaped in structure. OSM is a proprietary process from Siemens, which later became standard under the term
MRP. OSM is integrated in the optical Ethernet module EN100-O. OSM is hardly used in IEC 61850 networks.
RSTP is used there, this having become established as an international standard.

OSM
Optical Switch Module

Output data/output direction


Data is sent from the protocol master to the protocol slave.

Parallel Redundancy Protocol


Parallel Redundancy Protocol (PRP) is a redundancy protocol for Ethernet networks that is specified in IEC
62439-3. Unlike conventional redundancy procedures, such as RSTP (Rapid Spanning Tree Protocol, IEEE
802.1D-2004), PRP offers uninterruptible switching, which avoids any down time in the event of a fault, and
thus the highest availability.
PRP is based on the following approach: The redundancy procedure is generated in the end device itself. The
principle is simple: The redundant end device has 2 Ethernet interfaces with the same address (DAN, Double
Attached Node). Now, the same indication is sent twice, in the case of PRP (parallel) to 2 separate networks,
and uniquely marks both with a sequence number. The recipient takes the information that it receives first,
stores its ID based on the source address and the sequence number in a duplicate filter and thus recognizes
the 2nd, redundant information. This redundant information is then discarded. If the 1st indication is missing,
the 2nd indication with the same content comes via the other network. This redundancy avoids a switching
procedure in the network and is thus interruption-free. The end device forwards no messages to the other
network. Since the process is realized in the Ethernet layer (same MAC address), it is transparent and usable
for all Ethernet payload protocols (IEC 61850, DNP, other TCP/IP based protocols). In addition, it is possible to
use one of the 2 networks for the transmission of non-redundant messages.
There are 2 versions of PRP: PRP-0 and its successor PRP-1. Siemens implements PRP-1.

Parameterization
Comprehensive term for all setting work on the device. You can parameterize the protection functions with
DIGSI 5 or sometimes also directly on the device.

Parameter set
The parameter set is the entirety of all parameters that can be set for a SIPROTEC device.

1828 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

Participant address
A participant address consists of the name of the participant, the international dialing code, the local dialing
code and the participant-specific telephone number.

PICS
Protocol Implementation Conformance Statement

PLC
Programmable Logic Controller

PLC
Programmable Logic Controller

PROFIBUS
PROcess FIeld BUS, German Process and Fieldbus standard (EN 50170). The standard specifies the functional,
electrical and mechanical characteristics for a bit-serial fieldbus.

PROFIBUS address
A unique PROFIBUS address must be assigned to each SIPROTEC device within a PROFIBUS network. A total of
254 PROFIBUS addresses per PROFIBUS network are available.

Profile_ID
A Profile_ID in combination with an API uniquely identifies the access and the behavior of an application.

PROFINET IO
PROFINET is an open Industrial Ethernet Standard from PROFIBUS for the automation.

Programmable Logic
The programmable logic is a function in Siemens devices or station controllers, enabling user-specific func-
tionality in the form of a program. This logic component can be programmed by various methods: CFC (=
Continuous Function Chart) is one of these. SFC (Sequential Function Chart) and ST (Structured Text) are
others.

Programmable Logic Controller


Programmable logic controllers (PLC) are electronic controllers whose function is saved as a program in the
control unit. The construction and wiring of the device do not therefore depend on the function of the control.
The programmable logic controller has the structure of a computer; it consists of CPU with memory, installa-
tion/extension groups (for example, DI, AI, CO, CR), power supply (PS) and racPrk (with bus system). The
peripherals and programming language are oriented towards the circumstances of the control system.

Programmable Logic Module


Modules are parts of the user program delimited by their function, structure and intended use.

Project
In terms of content, a project is the replication of a real energy supply system. In graphic terms, a project is
represented as a number of objects which are incorporated in a hierarchical structure. Physically, a project
consists of a series of directories and files containing project data.

Project tree
The Project tree is used to display a data structure. This data structure represents the content of the project
and is created by a Generic Browser.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1829


C53000-G5040-C017-A, Edition 06.2019
Glossary

Protection communication
Protection communication includes all functionalities necessary for data exchange via the protection interface.
Protection communication is created automatically during configuration of communication channels.

Protection device
A protection device detects erroneous states in distribution networks, taking into account various criteria, such
as error distance, error direction or fault direction, triggering a disconnection of the defective network section.

Protocol Implementation Conformance Statement


The performance properties of the system to be tested are summarized in the report on the conformity of
implementation of a protocol (PICS = Protocol Implementation Conformance Statement).

PRP
Parallel Redundancy Protocol

Rapid Spanning Tree Protocol


The Rapid Spanning Tree Protocol (RSTP) is a standardized redundancy process with a short response time. In
the Spanning Tree Protocol (STP protocol), structuring times in the multidigit second range apply in the case of
a reorganization of the network structure. These times are reduced to several 100 milliseconds for RSTP.

Real Time
Real time

RedBox
Reduncancy box
The RedBox is used for the redundant connection of devices with only one interface to both the LAN A and the
LAN B PRP network. The RedBox is a DAN (Double Attached Node) and operates as a proxy for the devices
connected to it (VDANs). The RedBox has its own IP address in order to be able to configure, manage, and
monitor it.

Relay Information by OMICRON


Files in RIO format can be used to exchange data between test systems from the OMICRON company and any
other project-protection planning system. With DIGSI 5, you can export different settings from protection
functions in RIO format, which the OMICRON test equipment 7VP15 can then continue to process. The rele-
vant settings are described in the Test equipment manual.

RIO
Data format Relay Information by OMICRON

RSTP
Rapid Spanning Tree Protocol

SAN
Single Attached Node
A SAN is a non-redundant node in the PRP network. It is only connected with one port to one network (LAN A
or LAN B). It can only communicate with nodes in the connected network. Via a RedBox, devices with only one
connection can be redundantly connected to the 2 LAN A and LAN B networks. In order to obtain symmetrical
LAN A and LAN B networks, Siemens recommends avoiding SANs and to connect the devices either via a
RedBox or in a separate network without PRP support.

1830 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

SBO
Select before operate

SC
Single command

SCD
Ssubstation Configuration Description

SCL
Substation Configuration Description Language

SED
System Exchange Description

SEQ
Data type Sequence

SEQ5
DIGSI 5 Test Sequences

Sequence of Events
Acronym: SOE. An ordered, time-stamped log of status changes at binary inputs (also referred to as state
inputs). SOE is used to restore or analyze the performance, or an electrical power system itself, over a certain
period of time.

Service interface
Device interface for interfacing DIGSI 5 (for example, through a modem)

SICAM SAS
Substation Automation System – Modularly structured station control system, based on the substation
controller SICAM SC and the SICAM WinCC operator control and monitoring system.

SICAM WinCC
The operator control and monitoring system SICAM WinCC graphically displays the state of your network.
SICAM WinCC visualizes alarms and messages, archives the network data, provides the option of intervening
manually in the process and manages the system rights of the individual employees.

SIM
Simulation data format for single/multiple devices

Simple Network Management Protocol


The Simple Network Management Protocol (SNMP) is an Internet standard protocol and serves for the admin-
istration of nodes in an IP network.

Simple Network Time Protocol


The Simple Network Time Protocol (SNTP) is a protocol for the synchronization of clocks via the Internet. With
SNTP, client computers can synchronize their clocks via the Internet with a time server.

SIPROTEC 5, 7SJ82/7SJ85, Manual 1831


C53000-G5040-C017-A, Edition 06.2019
Glossary

Simulation data format for single/multiple devices


You can export the simulation-related files of a SIPROTEC 5 device in the SIM format. This new functionality in
DIGSI 5 provides the ability to export the simulation data and simulate all the devices in the DIGSI 5 project for
test and commissioning needs. The simulation is achieved by importing the simulation file into a signal
processing and automation system which will then simulate the device/devices with the process data as in a
real-time system. This feature also ensures the testing of a device for various real-time system conditions.

Single command
Single commands (SPC – Single Point Control) are process outputs which visualize 2 process states (for
example, On/Off) at an output.

Single-line diagram
A single-line diagram (SLD) is a simplified electric overview of the switchgear. Only 1 phase is shown instead
of all 3 phases of a line. Therefore, the diagram is called single-line.

Single-Line Editor
A Single-Line Editor contains a catalog of topological components to create a single-line diagram. The
customer may use the single-line elements to configure the topological view of his substation.

Single-point indication
Single-point indications (Single Ppoint Status) are process indications which visualize 2 process states (for
example, On/Off) at an

SIPROTEC
The registered trademark SIPROTEC designates the product family of protection devices and fault recorders.

SIPROTEC 5 device
This object type represents a real SIPROTEC device with all the contained setting values and process data.

Slave device
A slave may only exchange data with a master after its has been requested to do so by this master. SIPROTEC
devices work as slaves. A master computer controls a slave computer. A master computer can also control a
peripheral device.

SLD
Single-Line Diagram

SLE
Single-Line Editor

SNMP
Simple Network Management Protocol

SNTP
Simple Network Time Protocol

SOE
Sequence of Events

1832 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

SP
Single-point status

SP
Single-Point Indication

SPC
IEC 61850 data type: Single Point Control

SPS
IEC 61850 data type: Single Point Status

SSD
System Specification Description

ST
Structured Text file

Station description
A station description is an IEC 61850-compliant file for data exchange between the system configurator and
the IED configurator. The station description contains information on the network structure of a substation.
The station description contains for example, information on the assignment of the devices to the primary
equipment, as well as on the station-internal communication.

Structured Text file


You can import function charts (CFC) from DIGSI 4 in ST format. First, however, export your function charts
from DIGSI 4.83 or higher.

Substation Configuration Description Language


A description language standardized in IEC 61850, SCL is based on XML. This description language allows all
information relevant to an IEC 61850 substation to be documented consistently. This format is therefore suit-
able for exchanging IEC 61850-specific data between different applications, even if these come from different
manufacturers. The described import checks are basically done for all SCL formats, not only for SCD imports.

System Exchange Description


Files in SED format can be used to exchange interface information between DIGSI 5 projects and thus between
substations. To do this, the project extracts the data for the other projects from the file during import and
writes its own data in the same file during export. The contents of an SED file are formulated in SCL.

System Specification Description


Files in SSD format contain the complete specification of a station automation system, including a single-line
configuration of the station. The assignment of logical nodes from IEC 61850 to primary equipment can also
be described in SSD files. This allows device requirements to be defined in the SSD file so that the devices can
be used in the substation. The contents of an SED file are formulated in SCL.

TAI
Temps Atomique International - International Atomic Time

TC
Tap-position command

SIPROTEC 5, 7SJ82/7SJ85, Manual 1833


C53000-G5040-C017-A, Edition 06.2019
Glossary

TCP
Transmission Control Protocol

TEA-X
You can archive the data from individual SIPROTEC 5 devices or whole projects in TEA-X format. This format is
also suitable for data exchange between different applications, such as DIGSI 5 and Engineering Base (EB). The
TEA-X format is based on XML.

Time stamp
A time stamp is a value in a defined format. The time stamp assigns a time point to an event, for example, in a
log file. Time stamps ensure that events can be found again.

Topological view
The Topological View is oriented to the objects of a system (for example, switch gear) and their relation to one
another. The Topological View describes the structured layout of the system in hierarchical form. The Topolog-
ical View does not assign the objects to the devices.

Transmission Control Protocol


The Transmission Control Protocol (TCP) is a transmission protocol for transport services in the Internet. TCP is
based on IP and ensures connection of the participants during the data transmission. TCP ensures the correct-
ness of the data and the correct sequence of the data packages.

Transparent clock
The Precision Time Protocol knows different types of clocks: an ordinary clock (abbreviation: OC), a boundary
clock (BC), and a transparent clock (TC). The transparent clock was added to the specification in 2008 and
improves the time-information transmission within a network by receiving PTP messages and transmitting
them after modification (correction).

Tree view
The left area of the project window visualizes the names and symbols of all containers of a project in the form
of a hierarchical tree structure. This area is referred to as a tree view.

Tunneling
Technology for connecting two networks via a third network, whereby the through traffic is completely
isolated from the traffic of the third network.

UDP
User Datagram Protocol

Unbuffered Report Control Block


Unbuffered Report Control Block (URCB) is a form of report controlling. Internal events trigger the immediate
sending of reports based on best effort. If no association exists or if the transport data flow is not fast
enough, events can be lost.

URCB
Unbuffered Report Control Block

USART
Universal Synchronous/Asynchronous Receiver/Transmitter

1834 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Glossary

User Datagram Protocol (UDP)


UDP is a protocol. The protocol is based on IP as TCP. In contrast to this, however, UDP works without a
connection and does not have any safety mechanisms. The advantage of UDP in comparison to IP is the higher
transmission rate.

UTC
Universal Time Coordinated

Vendor ID
Manufacturer-specific part of the device identification for PROFINET.

Virtual device
A VD (virtual device) comprises all communication objects, as well as their properties and states, which a
communication user can utilize in the form of services. A VD can be a physical device, a module of a device or
a software module.

WYE
Phase-to-ground related measurements of a 3-phase system

SIPROTEC 5, 7SJ82/7SJ85, Manual 1835


C53000-G5040-C017-A, Edition 06.2019
1836 SIPROTEC 5, 7SJ82/7SJ85, Manual
C53000-G5040-C017-A, Edition 06.2019
Index

A C
ACD 175 Check of the voltage control function 1564
Acknowledgment Checking the transformer tap position 1561
Spontaneous fault display 89 Circuit breaker
Acquisition blocking 182 Circuit-breaker failure protection 319
ACT 175 Circuit-breaker test 319
Application templates Trip logic 324
7SJ85 207 Trip-circuit supervision 319
Arc protection 551 Trip-command reset 324
Automatic reclosing function Circuit-breaker failure protection
Structure of the function 964 CBFP 916
Automatic Reclosing Function Circulating reactive current 1339
Overview of Functions 964 Communication log 81
Automatic reclosing function, cyclic Communication-supervision log 83
Blockings 991 Control functions
Circuit-breaker readiness, circuit-breaker posi- Command checks 1205
tion 990 Command logging 1221
Closing indication, close command 986 Controllables 1174
Cycle control, Operating mode 1 975 User-defined objects 172
Cycle control, Operating mode 2 977 Current jump detection
Cycle control, Operating mode 3 979 Overview of functions 1056
Cycle control, Operating mode 4 980 Current-jump detection
Dead time, Operating modes with pickup 983 Function structure 1056
Dead time, Operating modes with tripping 982
Dead-line checking, reduced dead time 994
Evolving-fault detection 984
Input logic, Operating modes with pickup 973 D
Input logic, Operating modes with tripping 972
Operating modes 968 Device-diagnosis log 85
Reclaim time 989 Differential protection for capacitor banks
Stage release 981 Overview of functions 1143
Start 974 Structure of the function 1143
Structure 971 Dimensions 1588
Directional intermittent ground-fault protection 617
Directional mode 721
Directional negative-sequence protection
B Inrush-current detection 717
Directional overcurrent protection, phases 458
Battery fault 1454 Directional sensitive ground-fault detection
Broken-wire detection Sensitive ground current with 3I0 683
Application and setting notes 1421 Directional test 1557
Broken wire suspected 1420 DPC 175
Overview of functions 1420 DPS 174
Structure of the function 1420

SIPROTEC 5, 7SJ82/7SJ85, Manual 1837


C53000-G5040-C017-A, Edition 06.2019
Index

E I
External trip initiation 961 IEC 60529 1589
INC 175
Indication display
Spontaneous 88
F Indications 66
Displays 69
Fault display Read out 66
Configuration 89 Reading 66
Spontaneous 88 Reading with DIGSI 68
Fault locator INS 174, 175
Parallel-line compensation 1014 Instantaneous high-current tripping
Plus, 2-sided fault-location determination 1027 Function structure 544
Fault log 75 Overview of functions 544
FG Analog Transformers Release via protection interface 547
Overview 20-mA Unit Serial 266 Standard release 545
FG Analog units Instantaneous tripping at switch onto fault 570
20-mA Unit. Ether. 260 IO212 275, 277
Application and setting notes for the RTD unit
serial 288
Application and setting notes for the RTD-Unit
Ether. 285 L
Application and setting notes MT fast input 277
Communication with 20-mA Unit. Ether. 259 Lockout 91
Communication with an RTD unit 284 Log 72
Function-group structure 256 Configuring 72
Measuring transducer with fast inputs 275 Deleting 86
Overview 256 Logs 86
Overview 20-mA Unit Ether. 258 Management 72
Overview of RTD Unit Ether. 283 Logic of the Capacitance Bank Differential Protec-
Overview RTD unit serial 288 tion 1147
Technical data 1594
Temperature sensor 286
FG Analog Units
Application and Setting Notes 20 mA Unit. M
Serial 267
Function group Manual updating 182
Capacitor bank side 247 Master-follower method 1337
Function group VI 3-phase Method of minimizing circulating reactive current 1339
Overview 214
Structure of the function group 214
Function groups
Capacitor bank diff. 244
N
Negative-sequence protection 708
Non-directional intermittent ground-fault protec-
G tion 609

General Functionalities (Undervoltage Check, df/dt Calcu-


lation) 865
Ground-fault log 76
O
Group Indications
Time Overcurrent Protection Functions 369 Operational log 73
Grouping 1333 Operational measured values 1467
Optical fiber
Multimode 130
Multiplexer 130
Repeater 130

1838 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019
Index

Singlemode 130 Q
Order configurator 1780
Ordering Quality attributes 70
Accessories 1781 Quality processing for GOOSE Later Binding 105
Individual components 1780
Other Functions
Acquisition Blocking 178
Chatter Blocking 178 R
Manual Updating 178
Persistent Commands 178 Restricted ground-fault protection 943, 944
Stored Outputs 178 Reverse-power protection
Overcurrent protection General functionality 890
Dynamic settings 403, 453 Stage description 894
Overcurrent Protection
AREC 405, 455
Overcurrent protection, 1-phase 573
stage with definite-time characteristic curve (defi- S
nite time-overcurrent protection) 575
Structure of the function 573 Security log 84
Overcurrent Protection, 1-Phase Sensitive ground-fault detection
Application Example: High-Impedance Restricted Directional overcurrent protection stage with 3I0-
Ground-Fault Protection 590 φ(V,I) measurement 653
Application Example: Tank Leakage Protection 596 Directional overcurrent-protection stage with cos φ
Fast stage 589 or sin φ measurement 635
Stage with Inverse-Time Characteristic Curve Directional overcurrent-protection stage with G0 or
(Inverse Time-Overcurrent Protection) 578 B0 measurement 660
Overcurrent protection, ground 427 Overvoltage protection stage with zero-sequence
Inrush-current detection 451 voltage/residual voltage 679
Structure of the function 427 Sensitive ground current with Y0 687
User-defined characteristic curve 446 Sensitive Ground-Fault Detection
Overcurrent protection, phases 370 Function Structure 627
Inrush-current detection 402 Overview of Functions 627
Structure of the function 370, 598 Transient Ground-Fault Stage 644
User-defined characteristic curve 396, 586 Setting-history log 80
Overexcitation protection SIPROTEC 5 device
Function structure 897 Application templates/Adaptation of functional
Overview of functions 897 scope 55
Overload protection 727, 752 Reference number for parameters and indica-
tions 61
SIPROTEC 5 Device
Function Control 57
P Function Embedding 48
SPC 174, 175
Parallel operation 1331 SPS 173
Parallel-operation detection 1334 SPS unsaved 173
Positive-sequence overcurrent protection 598 Stage Control 499
Protection communication 127, 129 Stage Description 867
Remote data 127 Stage Description of the Reclosure Stage 913
Protection interface Stage description of the stage 908
Checking the protection-data communication 1556 Stored indications 90
Data bar 146 Synchrocheck 1242
Diagnosis data 155 Synchronization function
Diagnostic measured values of the protection inter- Dynamic measuring-point switching 1238
face 151 Synchronization of asynchronous systems 1248, 1256
Protocol 155 Synchronization of synchronous systems 1246, 1254
Time synchronization 139, 143 Synchronization stage 1231

SIPROTEC 5, 7SJ82/7SJ85, Manual 1839


C53000-G5040-C017-A, Edition 06.2019
Index

T
Temperature Monitoring
Application and Setting Notes 1041
Technical Data 1744
Temperature supervision
Function description 1041
Function structure 1040
Overview of functions 1040
Test of the line compensation 1569
Thermal overload protection
Functional measured values 730, 753
Thermal replica 730, 753
Topology
Chain topology 129
Ring topology 129

U
User log 78

V
Voltage jump detection
Function structure 1059
Voltage protection
Overvoltage protection with 3-phase voltage 768
Overvoltage protection with any voltage 798
Overvoltage protection with positive-sequence
voltage 787
Overvoltage protection with zero-sequence voltage/
residual voltage 780
Undervoltage protection with 3-phase voltage 811
Undervoltage protection with any voltage 836
Undervoltage protection with positive-sequence
voltage 829
Voltage-jump detection
Overview of functions 1059

1840 SIPROTEC 5, 7SJ82/7SJ85, Manual


C53000-G5040-C017-A, Edition 06.2019

You might also like