Correction The evaporator capacities used must be dividing the required evaporator capacity by the
for subcooling ∆tsub corrected if subcooling deviates from 4 K. correction factor below. Selections can then be
The corrected capacity can be obtained by made from the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.07 1.13 1.19 1.25 1.32 1.38 1.45 1.53 1.59
flash gas. factor
Example
Refrigerant = R 22 Correction factor from table = 1.07
Evaporator capacity Qe = 5 kW Corrected capacity = 5 ÷ 1.07 = 4.67 kW
Subcooling = 10 K
Correction The evaporator capacities used must be dividing the required evaporator capacity by the
for subcooling ∆tsub corrected if subcooling deviates from 4 K. correction factor below. Selections can then be
The corrected capacity can be obtained by made from the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.07 1.13 1.19 1.25 1.32 1.38 1.45 1.53 1.59
flash gas. factor
Example
Refrigerant = R 22 Correction factor from table = 1.07
Evaporator capacity Qe = 5 kW Corrected capacity = 5 ÷ 1.07 = 4.67 kW
Subcooling = 10 K
Correction The evaporator capacities used must be the required evaporator capacity by the
for subcooling ∆tsub corrected if subcooling deviates from 4 K. The correction factor below. Selections can then be
corrected capacity can be obtained by dividing made from the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.07 1.13 1.19 1.25 1.32 1.38 1.45 1.53 1.59
flash gas. factor
Correction The evaporator capacities used must be corrected required evaporator capacity by the correction
for subcooling ∆tsub if subcooling deviates from 4 K. The corrected factor below. Selections can then be made from
capacity can be obtained by dividing the the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.07 1.13 1.19 1.25 1.32 1.38 1.45 1.53 1.59
flash gas. factor
Capacity in kW
(continued) Range N: –40°C to +10°C R 134a
Orifice Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Valve type
no.
2 4 6 8 10 2 4 6 8 10
Correction The evaporator capacities used must be the required evaporator capacity by the
for subcooling ∆tsub corrected if subcooling deviates from 4 K. The correction factor below. Selections can then be
corrected capacity can be obtained by dividing made from the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.07 1.13 1.19 1.25 1.32 1.38 1.45 1.53 1.59
flash gas. factor
Correction The evaporator capacities used must be the required evaporator capacity by the
for subcooling ∆tsub corrected if subcooling deviates from 4 K. The correction factor next page. Selections can then
corrected capacity can be obtained by dividing be made from the tables above.
Correction The evaporator capacities used must be the required evaporator capacity by the
for subcooling ∆tsub corrected if subcooling deviates from 4 K. The correction factor below. Selections can then be
corrected capacity can be obtained by dividing made from the tables above.
Note: ∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Insufficient subcooling can produce
flash gas. Correction
1.00 1.07 1.13 1.19 1.25 1.32 1.38 1.45 1.53 1.59
factor