Professional Documents
Culture Documents
Joint cover
Contents
Description Page
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Unloading and Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Preparation and Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Joint Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Joint Cover Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Expansion Joint Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
End Cover Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Settlement Joint Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Horizontal Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Vertical Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wall Penetrations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Busduct Joint Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Tap-off Unit Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Attentions for Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Construction after Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Steps for Energizing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Maintenance Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Tap-off Unit Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Note. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Instruction Booklet IB XAP Series Busduct
Effective January 2017 Storage, Installation, and Maintenance
Unpack and inspect each piece for any signs of visible damage. Check
Storage the housing for dents or cracks caused by physical damage. Inspect
the XAP busduct joints to ensure they are clean and that the insulators
The Eaton XAP busduct should be stored in a covered, clean, dry space
are not cracked or broken.
which is climate controlled to prevent condensation. Do not allow the
busduct to come in contact with corrosive fumes, liquids, salts, or Consult the factory regarding any physical damage.
forms of concrete.
Perform an insulation resistance test on each busduct section by
Storing the busduct outdoors should be avoided at all possible. Megger testing at 1000 volts, phase-to-phase, phase-to-neutral, and
However, if it cannot be avoided, it must be stored off the ground and phase-to-ground ≥20MΩ to ensure system integrity.
securely covered to provide protection from dirt and moisture.
Temporary electrical heating must be provided and evenly distributed Record the readings of each item and of each installed run. Provide
beneath the cover to prevent condensation. At least 3 watts per cubic these readings as part of the permanent maintenance records.
foot is adequate for average environments. Failure to properly store Once inspected and tested, each busduct section is ready for installa-
and protect the busduct may cause damage and will void the warranty. tion.
Outdoor-rated busducts are not rated for outdoor applications until they
are completely and properly installed. They should be treated as indoor
busducts prior to complete installation.
Identification
PE
L3
L1
L2
N
Each piece of the Eaton XAP busduct has a nameplate label as shown in
Figure 1. This label identifies each piece and its ratings. It is recommend-
ed that each piece be installed sequentially, starting at the beginning
point of the run. This would typically be the cable tap box, transformer,
switchboard, or switchgear connection.
Compact Busway
Type: <XAP>
Figure 3. Joint Installation
Standard: IEC61439-1/-6
Ue = V In = A f =50/60Hz
Torque Indication Bolt
Ui = V Icw = kA IP65 When the two sections have been properly joined together, the joint
Name of contract: bolt may be tightened. This joint bolt is a special torque-indicating bolt
Contract No.: with two bolt heads to ensure that the proper installation torque is
achieved. Fall away instruction tags are provided between the upper
Installation No.:
and lower bolt heads. Torque should only be applied to the upper bolt
Manufacture Date:
head. When the proper torque is achieved, this bolt head will shear off,
Principal/Producers: Eaton Electrical Equipment Co.,LTD. allowing the tag to fall to the floor.
Production enterprise: Chongqing Yiwan Electric Co., LTD.
Orange
Figure 1. Nameplate Label
instruction Tag
Any joint bolt that is improperly tightened will retain the highly visible tag
and should be retightened. The lower bolt head remains intact for future
maintenance.
PE
L1
L2
L3
N
DANGER
FAILURE TO INSTALL THE BUSDUCT CORRECTLY MAY RESULT IN
DAMAGE TO THE BUSDUCT AS WELL AS PROPERTY DAMAGE, PHYSICAL
HARM, OR DEATH.
End cover
Joint cover
16-M6*25
Hexagon bolts
1. The mounting clearance for straight busduct should not be longer For individual and multiple runs of Eaton XAP busduct, thought must be
than 2m. Detailed clearance requirements shall be requested during given to horizontal and vertical clearances between runs, walls, and
routing design according to field conditions and loading situations, ceilings.
and shall be specified in installation drawing.
Busduct Busduct
2. Mounting supports shall be placed at both ends of the joint.
Maximum clearance is no longer than 1m. No load shall be burdened
at the joints.
Busduct Busduct
Note: When Lock Anchor A and B are in place, it means they are vertical
to the cover plate and in parallel to the side of the tap-off unit.
Note: Busduct joints on Indoor rated busducts should have a minimum Figure 16. Socket
of 8 in. (203.2 mm) clearance on either side of walls.
Lock
Anchor A
Lock
Anchor B
Note: Busduct joints on vertically mounted busduct should have a Figure 17. Tap-off Unit Installation
minimum of 8 in. (203.2 mm) clearance before ceilings and a minimum 1. After the Tap-off unit is installed onto the busduct, fasten the cable to
of 16 in. (406.4 mm) clearance above floors or curbs if used. its support in the case that the unit is connected to devices with
cable, to avoid movement.
2. Tap-off unit shall not be burdened with load directly. Loads at the rear
end shall be fastened onto the busduct or other fixed positions in
accordance with regulations.
WARNING
WHEN UNPLUGGING TAP-OFF UNITS, DISCONNECT LOADS. BEFORE
BUSDUCT SYSTEM POWERS ON, LEAD WIRES OF ALL TAP-OFF UNITS
SHALL BE CONNECTED TO ELECTRICAL DEVICES AND DISCONNECTED
OR PROTECTED. CABLES SHALL NOT BE EXPOSED.
3. Isolation for all living parts should be completed; 3. Perform a visual inspection on the busduct looking for stress or
damage and moisture intrusion;
4. No construction impacts installed busducts should be carried out;
4. Inspect the joint unit bolts for tightness;
5. Equipment for construction should be removed and the place should
be cleaned. 5. Check the insulation resistance and keep the record;
WARNING
ONLY THOSE TRAINED AND QUALIFIED IN RECOGNIZED SAFETY
PRACTICES SHOULD PERFORM MAINTENANCE ON THE BUSDUCT.
DANGER
HAZARD OF ELECTRICAL SHOCK OR BURN. TURN THE POWER TO THE
BUSDUCT OFF BEFORE INSTALLING, REMOVING, OR WORKING ON THIS
EQUIPMENT.
WARNING
RECOGNIZED SAFETY PROCEDURES MUST BE FOLLOWED PRIOR TO ANY
WORK OR MAINTENANCE BEING PERFORMED.
3. Using a multi-function meter, open the tap-off unit door and check to
ensure there is no voltage present on the line side of the unit;
4. For fusible units, check the fuse clip contact pressure and contact
means. If there are any sign of over-heating, replace fuse clips;
Note
These maintenance instructions and procedures do not represent an
exhaustive list of maintenance steps required to maintain safe
operation of the busduct and tap-off units under all applications.
Specific applications may require additional steps and procedures. For
additional information or assistance with issues not covered sufficiently
in this publication, contact the local Eaton sales office.