REFRIGERATION AND AIR-CONDITIONING

Actual Vapour Compression Cycle-1

Prof. RAVI KUMAR


MECHANICAL & INDUSTRIAL ENGINEERING
• Depiction of actual refrigeration cycle on T-s diagram
• Depiction of actual refrigeration cycle on P-h diagram
• Worked Example

Prof. RAVI KUMAR Department of Mechanical &


2
Industrial Engineering
In a R-134a based refrigeration system the cycle operates
in the temperature range of 40 oC and -20 oC Find COP of
the system if the vapour is dry and saturated while
entering the compressor. Assume mass flow rate of
refrigerant is 1 kg/s.

Prof. RAVI KUMAR


3
Department of Mechanical & Industrial Engineering
© ASHRAE, www.ashrae.org. (2013) ASHRAE Handbook- (Fundamentals)
Prof. RAVI KUMAR
Department of Mechanical & Industrial 4
Engineering
Prof. RAVI KUMAR
Department of Mechanical & Industrial 5
Engineering
THE END

Prof. RAVI KUMAR


6
Department of Mechanical & Industrial Engineering