Type of Test Connection Between Terminal Other Terminal: 2U-2V-2W & 3U-3V-3W Short
Type of Test Connection Between Terminal Other Terminal: 2U-2V-2W & 3U-3V-3W Short
a) First Resonance observed at Freq: 15KHZ and a) First Resonance observed at Freq: 12KHZ
Magnitude: -67dB and Magnitude: -51dB
b)2nd Resonance observed at Freq: 30KHZ and b)2nd Resonance observed at Freq: 16KHZ
Magnitude: -33dB and Magnitude: -42dB
c) )3rd Resonance observed at Freq: 40KHZ and c) 3rd Resonance observed at Freq: 22 KHZ
Magnitude: -55dB and Magnitude: -55dB
d) Next resonance observed at freq: 80kHZ & d) Next resonance observed at freq: 30kHZ
Magnitude: -33dB & Magnitude: -42dB
a)1st resonance at 11 kHZ & -84 DB a)1st resonance at 7kHZ & -56DB
b) 2nd resonance at 12kHZ & -45DB b) 2nd resonance at 12kHZ & -41DB
c)3rd resonance at 40kHZ & -55DB c)3rd resonance at 17kHZ & -53DB
d) 4th resonance at 80 kHZ & -32DB d) 4th resonance at 30kHZ & -44DB