You are on page 1of 14

TABLES 439

TABLE 7-1. Temperature and Enthalpy of Discharge Vapor after


Isentropic Compression
Condensing Temperature

Saturated 80° 90° 100°


Suction
Temperature / h t h t h

-40° 111.0° 91.6 121.0° 92.3 132.0° 93.9


-30° 105.0° 90.5 116.0° 92.0 127.5° 93.2
-20° 102.0° 90.2 112.5° 91.4 124.0° 92.6
-10° 97.5° 89.5 108.5° 90.7 119.9° 91.9
0° 95.0° 89.2 106.0° 90.3 117.0° 91.5
10° 92.0° 88.7 103.5° 89.9 114.0° 90.9
20° 90.0° 88.4 102.0° 89.6 112.0° 90.6
30° 88.0° 88.1 99.0° 89.1 110.8° 90.4
40° 86.0° 87.7 97.0° 88.8 109.5° 90.2
50° 84.0° 87.4 95.5° 88.6 107.0° 89.8

Condensing Temperature

Saturated 110° 120° 130°


Suction
Temperature / h t h / h

-40° 143.0° 95.1 155.0° 96.3 166.5° 97.3


-30° 138.0° 94.3 150.5° 95.5 161.5° 96.6
-20° 135.5° 93.7 147.0° 94.8 157.5° 95.8
-10° 131.6° 93.1 143.0° 94.2 154.0° 95.2
0° 128.5° 92.6 141.0° 93.7 152.0° 94.8
10° 126.5° 92.1 137.5° 93.2 148.5° 94.3
20° 124.0° 91.7 136.0° 92.8 147.2° 93.9
30° 122.0° 91.4 133.5° 92.5 146.0° 93.6
40° 120.0° 91.1 132.5° 92.2 143.5° 93.2
50° 118.0° 90.8 131.0° 92.0 142.0° 92.9
440 PRINCIPLES OF REFRIGERATION

TABLE 10-1. Heat Transmission Coefficients (U) for Cold Storage Rooms
Btu per hour per square foot per degree F difference between air on the two sides.
Wind velocity 15 mph.

t
Vapor seal on warm side Thickness of Insulation, V Inches
Wall Thickness
-Corkboard X Inches

Concrete block 8 0.12 0.085 0.066 0.054 0.046 0.040 0.035


Concrete block 12 0.12 0.083 0.065 0.053 0.045 0.039 0.035

Cinder block 8 0.11 0.081 0.064 0.052 0.045 0.039 0.034


Cinder block 12 0.11 0.079 0.063 0.052 0.044 0.039 0.034

(Vapor seal on warm side

Corkboard
Common brick 8 0.11 0.081 0.064 0.053 0.045 0.039 0,034

Common brick 12 0.10 0.076 0.061 0.050 0.043 0.038 0.034

, Vapor seal on warm side


Corkboard

Clay tile 4 0.12 0.085 0.066 0.054 0.046 0.040 0.035


Clay tile 6 0.11 0.081 0.064 0.053 0.045 0.039 0.035
Clay tile 8 0.11 0.081 0.064 0.052 0.045 0.039 0.034

,Vapor seal on warm side

Corkboard

.. . J:'<E-*!?I
Concrete 6 0.13 0.089 0.069 0.056 0.047 0.041 0.036
Concrete 8 0.12 0.087 0.068 0.055 0.047 0.040 0.036
:Sv£.*4*l^v.fl Concrete 10 0.12 0.086 0.067 0.055 0.046 0.040 0.035
Concrete 12 0.12 0.085 0.066 0.054 0.046 0.040 0.035

From Carrier Design Data. Reproduced by permission of Carrier Corporation.


TABLES 441

TABLE 10-2. Heat Transmission Coefficients (U) for Cold Storage Rooms
Btu per hour per square foot per degree F difference between the air on the two sides.
Outside wind velocity 15 mph.

Insulating
Thickness of Insulation (Inches)
Type of Construction
Material
3% 5%

Granulated
0.079 0.055
cork

Rock or
0.072 0.050
palco wool

Sawdust 0.097 0.069

1* board on
Corkboard ----- 0.11 0.084 0.067 0.055 0.047
both sides of studs*

Glass or rock
0.084 0.055 0.100 0.077 0.062 0.052
wool fill

Sheet steel on
"
both sides of studs

Thickness of Insulation
Insulating (Inches)
Material
8 10 12
Insulation

Granulated .040 0.033 0.027


cork

Palco or
0.036 0.029 0.025
rock wool

1- board _ b
both sides-2" x 4" studs-16" £ Sawdust 0.051 0.042 0.035

NOTES:
'Coefficients corrected for2x4or2x6 studs, on 16 in. centers.
b
Coefficients corrected for 2 x 4 studs
* Actual thickness *% in.

From Carrier Design Data. Reproduced by permission of Carrier Corporation.


TABLE 10-3. Heat Transmission Coefficients (U) for Cold Storage Rooms
Btu per hour per square foot per degree F difference between air on the two sides.

Wind velocity 15 mph.

Wall, Floor or
Thickness of Insulation, Y Inches
Ceiling Thickness
X (Inches)
Self-supporting partition*

I
Vapor seal on warm side

• Corkboard
Cork partition 0.13 0.089 0.069 0.056 0.047 0.041 0.036

Cement plaster/
on both sides

Floor' Corkboard*
Slab 2 0.046 0.035
0.12 0.087 0.067 0.055 0.040
Finish 2
Slab 5
Finish concrete 0.12 0.084 0.066 0.054 0.046 0.040 0.035
Insulation Finish 3
Slab 6
0.11 0.083 0.065 0.054 0.045 0.039 0.035
Finish 4
a
Foamglas
Floors Slab 2
0.15 0.11 0.087 0.071 0.060 0.053 0.046
Finish 2
'
Vapor seal on warm side
Slab 5
0.15 0.11 0.084 0.070 0.059 0.052 0.046
Finish 3
Slab 6 0.14 0.10 0.083 0.069 0.059 0.051 0.045
Finish 4
Ceiling*
, Vapor seal on warm side

'Concrete slab
Concrete 4 0.12 0.089 0.069 0.056 0.048 0.042 0.036
Concrete 8 0.12 0.086 0.067 0.055 0.047 0.041 0.036

sleeper Corkboard

Ceiling*
>Ceiling joists or wall studs

_ /Sheathing
\
Wood
(actual)
% 0.11 0.082 0.064 0.053 0.045 0.039 0.035

iPaper and vapor ^-Corkboard


seal on warm side

Ceiling*

0.13 0.092 0.072 0.059 0.050 0.043 0.038

,Tee iron
construction
Corkboard

These values may also be used for floors on ground.


* Surface conductance for soil air, 1.65, used on both sides

From Carrier Design Data.. Reproduced by permission of Carrier Corporation.


442
TABLES 443

TABLE 10-4. Thermal Conductivity of Materials Used in Cold Storage Rooms


Practical*
Thermal Thermal Thermal
Conductivity Conductance Conductivity

*
(*) (Q (*)
(Btu per hour (Btu per hour (Btu per hour
per sq ft per sq ft Authority per sq ft

per°F per °F for per °F


per inch per test 2nd and 3rd per inch
Material thickness) thickness) Columns thickness)

Brick, common 5.0 — 1 —


Cement plaster 8.0 — 1 —
Concrete 12.0 — 1 —
Cinder aggregate block 8* — 0.60 1 —
Cinder aggregate block 12* — 0.53 1 —
Gravel aggregate block 8* — 1.0 1 —
Gravel aggregate block 12* — 0.80 1 —
Corkboard 0.28 — 2 0.30
Cork, granulated coarse 0.31 — 2 0.34
Foamglas 0.40 — 4 0.40
Glass wool, density 1 .5 lb per cu ft 0.27 — 1 0.30
Mineral wool board 0.33 — 3 0.36
Redwood bark, palco wool 0.26 — 1 0.29
Rock wool, density 10.0 lb per cu ft 0.27 — 1 0.30
Sawdust, various woods 0.41 — 2 0.45
Tile, hollow clay 4* — 1.0 1 —
Tile, hollow clay 6* — 0.64 1 —
Tile, hollow clay 8* — 0.60 1 —
Wood, yellow pine, or fir 0.80 — 1 —
Authorities: (X) ASHVE
Guide 1945. {2) AS RE
Data Book, Vol. 1—1943. (I) ASRE Data Book,
Vol. 2 —
1942. (4) Pittsburgh Corning Corporation.
* These conductivities were used for insulating materials in calculation of heat transmission
coefficients. %
Most of these values have been increased 10 above laboratory test values to allow for
the effect of moisture gain in the insulating material and for imperfect workmanship. This also
assumes adequate vapor sealing. When no vapor sealing is applied or where the workmanship is
poor the value of the insulation is largely destroyed. It is extremely difficult to get a good vapor seal
with loose fill type insulation.
Foamglas. If a combination of corkboard and Foamglas is used, 1 in. of Foamglas is equivalent
to | in. of corkboard.
Mineral Wool Board. For estimating purposes use heat transmission coefficients for corkboard
increased by 15%.
From Carrier Design Data. Reproduced by permission of Carrier Corporation.
TABLE 10-5 A. Surface Conductance (f)

for Building Structures


TABLE 10-5. V Factors for Glass
Surface Conductance
Number of (Btu per hour per
Panes Btu/hr/sq ft/° F square foot per ° F)

1 1.13 Surface Exposure Winter Summer


2 0.46
3 0.29 Ceilings Inside 1.65 1.20
4 0.21 Roofs Outside 6.00* 4.00f
Walls Inside 1.65 1.65
From ASRE Data Book, Design Volume, Walls Outside 6.00* 4.00t
1949 Edition, by permission of the American
Society of Heating, Refrigerating, and Air- * Average wind velocity 15 mph.
Conditioning Engineers. t Average wind velocity 8 mph.
From Carrier Design Data. Reproduced
by permission of Carrier Corporation.

TABLE 10-6. Refrigeration Design Ambient Temperature Guide*


Average Maximum Average Maximum
Ambient Ambient Ambient Ambient
Location Temp. Temp. Location Temp. Temp.

Alabama Delaware
Birmingham 88 99 Dover 87 96
Mobile 88 97 Milford 87 98
Arizona Wilmington 87 94
Flagstaff 75 90
113
Columbia
District of
Phoenix 100
Washington 89 98
Tucson 84 98
Arkansas Florida
Fort Smith 91 103
Jacksonville 88 96
Little Rock 90 100
Miami 88 90
California Orlando 88 97
Bakersfield 96 114 Tallahassee 88 100
Fresno 94 111 Tampa 88 95
Los Angeles 83 94
Oakland 75 89 Georgia
Sacramento 90 108 Atlanta 87 95
San Diego 75 80 Savannah 89 99
San Francisco 75 83
Idaho
Colorado
Boise 89 105
Colorado Springs 83 94
Pocatello 83 100
Denver 83 98
Grand Junction 88 102 Illinois
Pueblo 83 100 Cairo 89 101
Connecticut Chicago 87 98
Hartford 83 94 Peoria 88 100
New Haven 83 95 Quincy 90 103
New London 83 93 Rockford -87 101
Norwalk 83 96 Springfield 90 102
TABLE 10-6 (Continued)

Average Maximum Average Maximum


Ambient Ambient Ambient Ambient
Location Temp. Temp. Location Temp. Temp.
Indiana Minnesota
Evansville 90 100 Duluth 79 92
Fort Wayne 87 100 Minneapolis 90 102
Indianapolis 89 99 St. Cloud 88 101
South Bend 87 101
Mississippi
Terre Haute 90 100
Jackson 90 99
Iowa
Vicksburg 9P 96
Burlington 90 101
Davenport 90 100 Missouri
Des Moines 90 102 Hannibal 90 102
Dubuque 90 99 Kansas City 92 103
Keokuk 90 101 St. Joseph 92 103
Mason City 86 97 St. Louis 92 103
Sioux City 90 102 Springfield 88 98
Kansas Montana
Concordia 93 108 Billings 85 104
Dodge City 92 106 Butte 75 96
Hutchinson 92 108 Havre 82 99
Salina 95 111
Helena 82 102
Topeka 92 105
Wichita 91 104 Nebraska
Kentucky Lincoln 94 106
Lexington 86 North Platte 89 103
98
Louisville 88 99
Omaha 92 104

Louisiana Nevada
Baton Rouge 88 98 Reno 84 101
New Orleans 89 98 Tonopah 84 96
Shreveport 92 102
New Hampshire
Maine Concord 81 92
Eastport 70 81
Portland 81 93
New Jersey
Atlantic City 83 92
Maryland
Paterson 85 95
Baltimore 89 99
Trenton 85 96
Cumberland 87 102
Massachusetts New Mexico
Boston 84 94 Albuquerque 83 99
Fall River 81 90 Santa Fe 81 90
Lawrence 81 94 New York
Worcester 81 92 Albany 83 96
Michigan Binghamton 83 94
Alpena 82 95 Buffalo 80 89
Detroit 86 99 Elmira 83 97
Grand Rapids 86 98 New York 85 93
Jackson 86 99 Poughkeepsie 83 95
Lansing 86 96 Rochester 83 95
Marquette 81 96 Syracuse 83 96
Saginaw 88 101 Watertown 83 93
•445
446 PRINCIPLES OF REFRIGERATION

TABLE 10-6 (Continued)

Average Maximum Average Maximum


Ambient Ambient Ambient Ambient
Location Temp. Temp. Location Temp. Temp,

North Carolina Tennessee


Asheville 81 93 Chattanooga 87 98
Charlotte 86 98 Knoxville 87 98
Raleigh 86 98 Memphis 89 99
Wilmington 86 95 Nashville 87 98
Winston-Salem 86 97
Texas
North Dakota Dallas 92 102
Bismarck 87 103 El Paso 92 102
Devils Lake 84 100 Fort Worth 92 104
Houston 92 99
Ohio
San Antonio 92 102
Akron 86 98
Canton 86 97 Utah
Cincinnati 88 100 Modena 80 97
Cleveland 83 95 Salt Lake City 88 101
Columbus 88 98
Vermont
Dayton 88 99
Burlington 80 91
Toledo 87 99
Virginia
Youngstown 86 97
Lynchburg 87 99
Oklahoma Norfolk 87 95
Oklahoma City 92 104
Richmond 87 98
Tulsa 92 105
Washington
Oregon Olympia 75 90
Portland 81 95
Seattle 75 86
Pennsylvania Spokane 75 102
Altoona 82 96 Walla Walla 87 105
Erie 83 92
West Virginia
Harrisburg 85 97 87 102
Charleston
Philadelphia 87 97 Clarksburg 84 97
Pittsburgh 85 96 87
Huntington 100
Scranton 82 95
Parkersburg 86 98
Rhode Island Wheeling 86 101
Providence 83 94
Wisconsin
South Carolina Green Bay 85 97
Charleston 88 98 La Crosse 87 99
Columbia 88 99 Madison 87 96
Milwaukee 87 99
South Dakota
Huron 93 107 Wyoming
Pierre 94 110 Cheyenne 79 94
Rapid City 87 103 Lander 80 98
Sioux Falls 88. 102 Sheridan 86 102

* Do not use these temperatures for air conditioning design.


From ASRE Data Book, Design Volume, 1949 Edition, by permission of the American Society
of Heating, Refrigerating, and Air-Conditioning Engineers.
TABLES 447

TABLE 10-6 A. Design Ground Temperatures


Ground Ground
Location Temperature Location Temperature

Alabama Idaho
Birmingham 70° F Boise 60°
Mobile 75 Pocatello 60
Arizona Illinois 60
Flagstaff 60 Cairo
Phoenix 80 Chicago 60
Tucson 80 Peoria 60
Arkansas Quincy 60
Fort Smith 70 Rockford 60
Little Rock 70 Springfield 60

California Indiana
Bakersfield Evansville 65
75
Fresno 80
Fort Wayne 60
Los Angeles Indianapolis 60
75
Oakland South Bend 60
65
Sacramento Terre Haute 65
80
San Diego 65 Iowa
San Francisco 65 Burlington 60
Colorado Davenport 60
Colorado Springs 60
Des Moines 60
Denver 60
Bubuque 60
Grand Junction 60 Keokuk 60
Pueblo 55
Mason City 60
Sioux City 60
Connecticut
Hartford 65
Kansas
New Haven 65
Concordia 60
New London 65
Dodge City 60
Norwalk Hutchinson 60
65
Salina 60
Delaware Topeka 60
Dover 65 Wichita 60
Milford 65
Wilmington 65
Kentucky
Lexington 65
Columbia
District of Louisville 65
Washington 65
Louisiana
Florida Baton Rouge 75
Jacksonville 80 New Orleans 75
Miami 80 Shreveport 70
Orlando 80
Tallahassee
Maine
80
Eastport 60
Tampa 80
Portland 60
Georgia Maryland
Atlanta 70 Baltimore 65
Savannah 75 Cumberland 65
448 PRINCIPLES OF REFRIGERATION
TABLE I0-6A (Continued)
Ground Ground
Location Temperature Location Temperature

Massachusetts New Mexico


Boston 65° F Albuquerque 70° F
Fall River 60 Santa Fe 65
Lawrence 60 New York
Worcester 60 Albany 60
Michigan Binghamton 60
Alpena 60 Buffalo 65
Detroit 60 Elmira 60
Grand Rapids 60 New York 65
Jackson 60 Poughkeepsie 60
Lansing 60 Rochester 60
Marquette 60 Syracuse 60
Saginaw 60 Watertown 60

Minnesota North Carolina


Duluth 50 Asheville 70
Minneapolis 55 Charlotte 70
St. Cloud 55 Raleigh 70
Wilmington 75
Mississippi
Winston-Salem 75
Jackson 75
Vicksburg 75 North Dakota
Bismarck 50
Missouri
Devils Lake 50
Hannibal 60
Kansas City 60 Ohio
St. Joseph 60 Akron 65
St. Louis 60 Canton 65
Springfield 60 Cincinnati 65
Cleveland 65
Montana
Columbus 60
Billings 55
Dayton 65
Butte 55
Toledo 60
Havre 50
Youngstown 60
Helena 55
Oklahoma
Nebraska Oklahoma City 65
Lincoln 60 Tulsa 65
North Platte 55
Omaha 60 Oregon
Portland 70
Nevada
Pennsylvania
Reno 65
Altoona 65
Tonopah 70
Erie 65
New Hampshire Harrisburg 70
Qoncord 55 Philadelphia 70
New Jersey Pittsburgh 65
Atlantic City 70 Scranton 65
Paterson 70 Rhode Island
Trenton 70 Providence 65
TABLES 449

TABLE I0-6A (Continued)


Ground Ground
Location Temperature Location Temperature

South Carolina Virginia


Charleston 75° F Lynchburg 75'
Columbia 75 Norfork 75
South Dakota Richmond 70
Huron 55 Washington
Pierre 55 Olympia 60
Rapid City 55 Seattle 75
Sioux Falls 55 Spokane 60
Tennessee Walla Walla 60
Chattanooga 70 West Virginia
Knoxville 70 Charleston 65
Memphis 70 Clarksburg 65
Nashville 70 Huntington 65
Texas Parkersburg 65
Dallas 70 Wheeling 65
El Paso 70 Wisconsin
Fort Worth 70 Green Bay 55
Houston 75 La Crosse 55
San Antonio 75 Madison 55
Utah Milwaukee 55
Modena 60
Wyoming
Salt Lake City 60 Cheyenne 55
Vermont Lander 55
Burlington 60 Sheridan 55
:

450 PRINCIPLES OF REFRIGERATION

TABLE 10-7. Allowance for Solar


Radiation
(Degrees Fahrenheit to be added to the normal
temperature difference for heat leakage calcu-

lations to compensate for sun effect not to be
used for air-conditioning design)

East South West Flat


Type of Surface Wall Wall Wall Roof

Dark-colored sur-
faces such as
Slate roofing
Tar roofing 8 5 8 20
Black paints
Medium-colored sui
faces, such as:
Unpainted wood
Brick
Red tile 6 4 6 15
Dark cement
Red, gray, or
green paint
Light-colored sur-
faces, such as:
White stone
Light-colored
cement 4 2 4 9
White paint

From ASRE Data Book, Design Volume,


1957-1958 Edition, by permission of the Ameri-
can-Society of Heating, Refrigerating, and Air-
Coriditioning Engineers.
TABLES 451

TABLE 1 0-8 A. Btu per Cubic Foot of Air Removed in Cooling to


Storage Conditions above 30°
Inlet Air Temperature, ° F
Storage 85 90 95 100

Temp., Inter. Air Relative Humidity, %


°F 50 60 70 50 60 70 50 60 50 60

65 0.65 0.85 1.12 0.93 1.17 1.44 1.24 1.54 1.58 1.95
60 0.85 1.03 1.26 1.13 1.37 1.64 1.44 1.74 1.78 2.15
55 1.12 1.34 1.57 1.41 1.66 1.93 1.72 2.01 2.06 2.44
50 1.32 1.54 1.78 1.62 1.87 2.15 1.93 2.22 2.28 2.65
45 1.50 1.73 1.97 1.80 2.06 2.34 2.12 .2.42 2.47 2.85
40 1.69 1.92 2.16 2.00 2.26 2.54 2.31 2.62 2.67 3.06
35 1.86 2.09 2.34 2.17 2.43 2.72 2.49 2.79 2.85 3.24
30 2.00 2.24 2.49 2.26 2.53 2.82 2.64 2.94 2.95 3.35

Reprinted from Refrigeration Engineering Data Book by courtesy of American Society of


Refrigerating Engineers.

TABLE I0-8B. Btu per Cubic Foot Removed in Cooling to


Storage Conditions below 30°
Inlet Air Temperature, ° F
Storage 40 50 80 90 100

Temp., Inter.Air Relative Humidity, %


°F 70 80 70 80 50 60 50 60 50 60

30 0.24 0.29 0.58 0.66 1.69 1.87 2.26 2.53 2.95 3.35
25. 0.41 0.45 0.75 0.83 1.86 2.05 2.44 2.71 3.14 3.54
20 0.56 0.61 0.91 0.99 2.04 2.22 2.62 2.90 3.33 3.73
15 0.71 0.75 1.06 1.14 2.20 2.39 2.80 3.07 3.51 3.92
10 0.85 0.89 1.19 1.27 2.38 2.52 2.93 3.20 3.64 4.04
5 0.98 1.03 1.34 1.42 2.51 2.71 3.12 3.40 3.84 4.27
1.12 1.17 1.48 1.56 2.68 2.86 3.28 3.56 4.01 4.43
-5 1.23 1.28 1.59 1.67 2.79 2.98 3.41 3.69 4.15 4.57
-10 1.35 1.41 1.73 1.81 2.93 3.13 3.56 3.85 4.31 4.74
-15 1.50 1.53 1.85 1.93 3.05 3.25 3.67 3.96 4.42 4.86
-20 1.63 1.68 2.01 2.09 3.24 3.44 3.88 4.18 4.66 5.10
-25 1.77 1.80 2.12 2.21 3.38 3.56 4.00 4.30 4.78 5.21
-30 1.90 1.95 2.29 2.38 3.55 3.76 4.21 4.51 5.00 5.44

Reprinted from Refrigeration Engineering Data Book by courtesy of American Society of


Refrigerating Engineers.
452 PRINCIPLES OF REFRIGERATION

TABLE 1 0-9 A. Average Air Changes per 24 Hours for Storage Rooms above 32° F
due to Door Opening and Infiltration
(Does not apply to rooms using ventilating ducts or grilles)

Air Air Air Air


Volume Changes Volume Changes Volume Changes Volume Changes
cuft per 24 hr cuft per 24 hr cuft per 24 hr cuft per 24 hr

250 38.0 1,000 17.5 6,000 6.5 30,000 2.7


300 34.5 1,500 14.0 8,000 5.5 40,000 2.3
400 29.5 2,000 12.0 10,000 4.9 50,000 2.0
500 26.0 3,000 9.5 15,000 3.9 75,000 1.6
600 23.0 4,000 8.2 20,000 3.5 100,000 1.4
800 20.0 5,000 7.2 25,000 3,0

Note: For storage room with anterooms, reduce air changes to 50% of values in table.
For heavy duty usage, add 50% to values given in table.
From ASRE Data Book, Design Volume, 1949 Edition, by permission of the American Society of
Heating,. Refrigerating, and Air-Conditioning Engineers.

TABLE I0-9B. Average Air Changes per 24 Hours for Storage RoOms below 32° F
due to Door Opening and Infiltration
(Does not apply to rooms using ventilating ducts or grilles)

Air Air Air Air


Volume Changes Volume Changes Volume Changes Volume Changes
cuft per 24 hr cuft per 24 hr cuft per 24 hr cuft per 24 hr

250 29.0 1,000 13.5 5,000 5.6 25,000 2.3


300 26.2 1,500 11.0 6,000 5.0 30,000 2.1
400 22.5 2,000 9.3 8,000 4.3 40,000 1.8
500 20.0 2,500 8.1 10,000 3.8 50,000 1.6
600 18.0 3,000 7.4 15,000 3.0 75,000 1.3
800 15.3 4,000 6.3 20,000 2.6 100,000 1.1

Note: For storage rooms with anterooms, reduce air changes to 50% of values in table.
(1)
For heavy duty usage, add 50% to values given in table.
(2) For locker plant rooms, double the above table values.
From ASRE Data Book, Design Volume, 1949 Edition, by permission of the American Society
of Heating, Refrigerating, and Air-Conditioning Engineers.

You might also like