You are on page 1of 3

1 2 3 4 5 6 7 8

=K01
+K01
=K02
+K02
=K03
+K03
RRT
=KZ01 =KZ02 =KZ03 R - Entrada/saída
A
T - Protecção Transformador por fusíve A

B B

-Q1

200 A
-Q1 -Q1 -F1

630 A 630 A
Copyright (C) SIEMENS AG 2016 All Rights Reserved

C C

-A51 -A51 -A51

D D
Typ C Typ C Typ C

E E

Entrada/Saída Entrada/Saída Protec. Traf.

F System/rated frequency Operating voltage Rated voltage Rated short-time withst. curr. Rated normal current F
3~50 Hz 15.0 kV 24.0 kV 20.0 kA (3 s) 630 A
Printout 23.10.2017 8DJH 1 =K00

Created by Nobre Siemens AG 8DJH +K00 B01


Checked by QMT- R-R-T (15kV) 8DJH-180922 Sh.No 01-
Issue Revision Date Name Standard Orig. / Repl. f. / Repl. by Single Line Diagram 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW
=K01 =K02 =K03
+K01 +K02 +K03
A =KZ01 =KZ02 =KZ03 A

B B

1400mm
Copyright (C) SIEMENS AG 2016 All Rights Reserved

C C

310mm 310mm 430mm

1050mm

T*1

D D

LOAD DATA AND MINIMUM DISTANCES

1.) PERMANENT LOADS


VERTICAL SINGLE LOAD GV
PANEL WIDTH 310 mm ≤ 1.8 kN
E PANEL WIDTH 430 mm ≤ 3.0 kN E
PANEL WIDTH 500 mm ≤ 4.0 kN
PANEL WIDTH 840 mm ≤ 3.5 kN

2.) NONPERMANENT LOADS


LIVE LOAD qk 6 kN/m²

3.) MINIMUM DISTANCES


WALL DISTANCE ON THE REAR ≥ 15 mm
WALL DISTANCE ON THE LEFT / RIGHT ≥ 50 mm
WITH EXTENSION ≥ 200 mm

4.) HEIGHT OF CEILING


SWITCHGEAR HEIGHT 1400 mm * ≥ 2000 mm
SWITCHGEAR HEIGHT 2000 mm / 2300 mm ≥ 2400 mm

5.) MINIMUM DOOR OPENING


SWITCHGEAR HEIGHT ≤ 1700 mm * 1000 mm x 2000 mm
SWITCHGEAR HEIGHT 2000 mm 1000 mm x 2200 mm THE LOCATION AND DETAIL DIAGRAMS
F SWITCHGEAR HEIGHT 2300 mm 1200 mm x 2500 mm DO HAVE SYMBOLIC CHARACTER AND System/rated frequency Operating voltage Rated voltage Rated short-time withst. curr. Rated normal current F
DO NOT SHOW THE ACTUAL SCOPE OF
* WITHOUT CABLE DUCT OR LV-CABINET
SUPPLY.
3~50 Hz 15.0 kV 24.0 kV 20.0 kA (3 s) 630 A
Printout 23.10.2017 8DJH 1 =K00

Created by Nobre Siemens AG 8DJH +K00 B01


Checked by QMT- R-R-T (15kV) 8DJH-180922 Sh.No 01-
Issue Revision Date Name Standard Orig. / Repl. f. / Repl. by Location diagram 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PLAN VIEW
=K01 =K02 =K03
+K01 +K02 +K03
A =KZ01 =KZ02 =KZ03 A

B B

714mm
775mm
Copyright (C) SIEMENS AG 2016 All Rights Reserved

WxD WxD WxD


C 230x610 270x610 390x610 C

310mm 310mm 430mm

1050mm

T*1

D D

LOAD DATA AND MINIMUM DISTANCES

1.) PERMANENT LOADS


VERTICAL SINGLE LOAD GV
PANEL WIDTH 310 mm ≤ 1.8 kN
E PANEL WIDTH 430 mm ≤ 3.0 kN E
PANEL WIDTH 500 mm ≤ 4.0 kN
PANEL WIDTH 840 mm ≤ 3.5 kN

2.) NONPERMANENT LOADS


LIVE LOAD qk 6 kN/m²

3.) MINIMUM DISTANCES


WALL DISTANCE ON THE REAR ≥ 15 mm
WALL DISTANCE ON THE LEFT / RIGHT ≥ 50 mm
WITH EXTENSION ≥ 200 mm

4.) HEIGHT OF CEILING THESE CONSTRUCTIONAL DATA OF


SWITCHGEAR HEIGHT 1400 mm * ≥ 2000 mm SIEMENS AG ARE NOT BINDING FOR
SWITCHGEAR HEIGHT 2000 mm / 2300 mm ≥ 2400 mm CONSTRUCTION. THEY ARE ONLY VALID
AS A BASE FOR PRODUCTION OF
5.) MINIMUM DOOR OPENING BINDING CONSTRUCTIONAL DRAWINGS.
SWITCHGEAR HEIGHT ≤ 1700 mm * 1000 mm x 2000 mm FURTHER INFORMATION ACCORDING
SWITCHGEAR HEIGHT 2000 mm 1000 mm x 2200 mm CONSTRUCTIONAL DATA CAN BE
F SWITCHGEAR HEIGHT 2300 mm 1200 mm x 2500 mm FOUND IN THE RELATED OPERATING System/rated frequency Operating voltage Rated voltage Rated short-time withst. curr. Rated normal current F
* WITHOUT CABLE DUCT OR LV-CABINET AND INSTRUCTION MANUAL. 3~50 Hz 15.0 kV 24.0 kV 20.0 kA (3 s) 630 A
Printout 23.10.2017 8DJH 1 =K00

Created by Nobre Siemens AG 8DJH +K00 B01


Checked by QMT- R-R-T (15kV) 8DJH-180922 Sh.No 01-
Issue Revision Date Name Standard Orig. / Repl. f. / Repl. by Constructional Data 1
1 2 3 4 5 6 7 8

You might also like