You are on page 1of 3

822 J. SPACECRAFT VOL. 2, NO.

operating characteristics. The pressure data showed that THERMOMETER

the pump added additional compliance to the system through- BYPASS VALVE

out its operation. Cavitation at the pump inlet (confirmed


. r^h
by movies) lowered the resonant frequency of the oxidizer
system to the point that it coupled with the structure. The
test showed that the resonant frequency of the fuel system
L^l^i
also was within the frequency range in question, and, there-
fore, that both systems contributed to the Pogo phenomenon.

Manned Chamber Testing of the Apollo


Prototype Space Suit
G. FRANKEL,* G. ALBRIGHT^ AND I. AXELRODJ
Republic Aviation Corporation, Farmingdale, N. Y.

I N this note preliminary results on the ventilation efficiency


of the Apollo prototype space suit are reported. Two
tests were made with human subjects in the entry lock of
Downloaded by 121.200.6.58 on November 30, 2019 | http://arc.aiaa.org | DOI: 10.2514/3.28296

Republic's 13-ft-diam by 8-ft-long space chamber at a simu-


lated altitude of 35,000 ft. Chamber pressure was controlled
automatically by a pressure sensor and pneumatically oper-
ated throttling valve system. The suited subject was venti- • SUIT TEMPERATURE AND BIOMEDICAL READOUT
lated with oxygen supplied from an L02 source located out-
side the entry lock (Fig. 1). The oxygen was throttled, Fig. 1. Liquid oxygen ventilation system.
metered, and humidified. A manually operated bypass valve
controlled the rate of water vapor pickup from a wick in a respectively, and w3 is the theoretical water vapor flow rate
pressurized water reservoir. Inside the entry lock, the out at saturation, all in pounds per minute. For this cal-
humidity was adjusted by passing the stream through an culation to be meaningful, the water vapor flow rates used
ice-bath cooler and a centrifugal flow water trap. It then in the foregoing equation had to be chosen at a time when
passed through a manifold in which were mounted a mass the subject was generating the prescribed metabolic output,
spectrometer probe, a thermistor, one side of a mercury and when the water vapor flow rate resulting from this
manometer, and a barometer, and thence to the suit. exertion was stabilized. These data were validated by
The surface of the suit was instrumented with four therm- establishing a heat balance, i.e., accounting for all of the heat
istors, two of which were shielded from radiant heat. transfer both into and out of the space suit.
The walls of the chamber were heated externally by infrared As illustrated in Fig. 2, the sum of the heat generated
lamps, and the wall temperature was monitored by a therm- metabolically by the subject (Qmet) and the change in body
istor. The suit exhaust was connected to an exhaust manifold heat storage (QBtOT) is equated to the total heat removed from
in which were mounted a mass spectrometer probe, a therm- the subject by sensible, latent, radiant, and convective heat
istor, and the other leg of the mercury manometer that transfer, and the heat equivalent of mechanical work (Qs,
gave the pressure drop across the suit. The exhaust gases Qiy Qr, Qc, and Qm, respectively, all in British thermal units
then flowed into the space chamber, from which they were per hour)
exhausted by the pumping system. A bicycle ergometer
was calibrated to measure the mechanical work performed Qmet + Qstor = Qs + Ql + Qr + Qc + Qm (1)
by the subject. The subjects were Republic test pilots whose
respiratory quotients were determined in preliminary tests The calculation of Qmet was based on the rate of expiration
performed at sea-level conditions. Forehead, arm, thigh, of carbon dioxide. The flow of C02 was taken as the ratio
trunk, foot, and rectal temperatures, electrocardiogram, and of the partial pressure of C02 to the partial pressures of C02
heart rate were monitored. and oxygen times the ventilation flow of oxygen. The
The ventilation efficiency VE is defined as the ratio of the C02 flow, divided by the respiratory quotient RQ, is equal
actual increase in the water vapor content of the ventilation to the oxygen consumed. The product of the oxygen con-
stream to the theoretical increase if the stream were to reach sumed and its heat equivalent is equal to the metabolic heat
saturation output. The formula (adapted from Ref. 1) is
VE = 100 (w2 - Wi)/(w3 - t£>0 '02 0.36QRQ - 0.71)"
Qmet = 6230 L69 (2)
where Wi and w2 are the water vapor flow rates in and out> (Pco2 0.29
where P is partial pressure (torr), and 702 is the oxygen flow
Presented at the AIAA Space Simulation Testing Conference,
Pasadena, Calif., November 16-18, 1964 (no preprint number; (cfm at STP). Body heat storage was calculated from
published in bound volume of preprints of the meeting); revision = 60.1 Wcp dTMB/dt
received June 2, 1965. This study was performed under sub- (3)
contract to International Latex Corporation, Industrial Products where W is the weight of the subject (Ib), cp is the specific
Division, Dover, Del., under contract to Hamilton Standard
Division, United Aircraft Corporation, Windsor Locks, Conn., heat of the human body (cal/gm°C), TMB is .mean body
which has the prime contract for development of the Apollo space temperature (°R), t is time (min), and TMB was calculated
suit and related man support systems. from:2
* Chief, Space Environment Laboratory.
t Chief, Space Environment/Life Sciences. Member AIAA. 0.6777* + 0.33 [0.07!Tw + Q.27TA + 0.1977™ +
| Instrumentation Group Leader. 0.122V] (4)
SEPT.-OCT. 1965 ENGINEERING NOTES 823

where the subscript R = rectal, Fd = forehead, A = arm,


Th = thigh, T = trunk, and F = foot. The sensible and II
latent heats removed by the ventilation stream were calcu-
lated by
in
Qs = 60 Vo2pcp02(T2 - T,) Qi = 60 hi(w2 - (5)
where subscripts 1 and 2 again represent in and out, respec-
tively, p is density of 02 (lb/ft 3 ), and hi is the latent heat of
vaporization of water (~1040 Btu/lb at the body tempera-
ture involved).
The water flow rates Wi and w2 were determined from par-
tial pressures by the mass spectrometer and the total flow M
rate. The ideal gas equation was used with an appropriate
conversion factor: w = 0.0325 Pn2o Vo2/T, where w = Fig. 3. Carbon dioxide partial pressure curve.
water vapor flow rate (Ib/min), P = partial pressure of water
vapor (torr), 7o2 = oxygen flow rate (ft 3 /rain), and T =
temperature (°R). during a representative number of respiratory cycles was
Radiant heat exchange between the suit and the walls was divided by the time interval for these cycles to determine the
calculated from average partial pressure of C02 during the interval. The
water vapor levels measured were relatively steady. As the
= FgFeAv(Tw* - TV) (6) subject approached a state of equilibrium at a given Qmet,
Pn2o increased to a plateau and remained constant, except
Downloaded by 121.200.6.58 on November 30, 2019 | http://arc.aiaa.org | DOI: 10.2514/3.28296

where Fg — geometry factor, Fe = emissivity factor, A = for occasional momentary fluctuations.


area (ft 3 ), a = Stefan-Boltzmann constant, Tw = wall Prior to the test, the subject was assisted by two tech-
temperature (°R), and Ts = suit surface temperature (°R). nicians, his inside observer and the chamber operator.
Convective heat flow from the suit to the ambient environ- After instrumentation and dressing were completed and
ment was determined by base-line data were recorded, the subject and his inside ob-
server entered the chamber and were placed on 100% oxygen
Qc = 4AMV/2(0.952 2 - TS)/3X (7) for 2 to 2^- hr before actual flight. During this period all
2 of the instrumentation connections were completed, and
where A = area (ft ), k = thermal conductivity of oxygen operation of each component was verified. Ascent to ex-
(Btu/hr-ft2-F/ft), Pr = Prandtl number of oxygen, Gr = perimental altitude was then accomplished at a rate of ap-
Grashof number of oxygen, T^ = temperature of oxygen proximately 1500 fpm. At experimental altitude, the
(°R), and X — characteristic dimension of suit (assumed to chamber was placed on automatic altitude control and care-
be unity). fully monitored. The excursions on automatic control were
It was also necessary to convert the mechanical work per- less than ±50 ft from the experimental altitude. Descent
formed on the ergometer into its heat equivalent. This was to ground level after the run was accomplished manually at
calculated by multiplying the pedal speed (co, rpm) by the ^2000 fpm. When ground level was reached, final data
tangential force exerted (Kp, kg) and correcting for the units were taken. All of the preflight measurements were then
to give the heat equivalent rate (Btu/hr) repeated.
Qm = 3.34 E> (8) The results of the first test are plotted as four points on a
curve of oxygen flow vs total heat removed by the stream
A time-of-flight mass spectrometer continuously sampled (Fig. 4). Curve A represents the theoretical maximum
and analyzed the gas from the exhaust manifold. Figure amount of heat (both sensible and latent) that could be
3 shows a typical strip-chart record for C02. The lower trace carried by the stream at various flow rates if the stream were
is the partial pressure of C02 generated by the subject. It to enter at 43 °F carrying water equivalent to saturation at
has a regular, cyclic pattern except for an interval A during 32 °F and were to leave saturated at T2 (varied from 88° to
which the subject was speaking. The upper trace is the 91 °F). Curve B represents the theoretical heat-carrying
integration of the lower trace; each vertical excursion repre- capacity of the stream taken at inlet conditions of 43°F
sents a constant time-pressure product (torr-sec) of C02 saturated and outlet conditions of 93 °F saturated with an
partial pressure output. The sum of the vertical excursions inlet pressure of 3.73 psia. The temperature of 93°F was

THEORETICAL LINES
_____
INLET OUTLET FLOW
43°FH 2 Oot32°F ACT. ACT. 35 K
43°F SAT 93°FSAT 15 cf m 3.73 psia
INTERPOLATED DATA LINE — — — —
TEST DATA POINTS ,

OXYGEN FLOW-CFM-STP

Fig. 2. Heat exchanges of space suit ventilation tests. Fig. 4. Oxygen flow vs heat removed, test 1.
824 J. SPACECRAFT VOL. 2, NO. 5

Table 1 Thermal balances from second test Analytical Model to Determine Aft-End
Ergometer setting, Kp Igniter Design Parameters
Heat load 175 T7o
Heat generated (Btu/hr): ARNOLD G. PLUMLEY*
Metabolic output (Q me t) 1655 1080 Aerojet General Corporation, Sacramento, Calif.
Body heat loss (Qstor) 0 167
1655 1247 Nomenclature
Heat removed (Btu/hr):
Sensible (Q s ) 149 121 A — area, in.2
Latent (Qi) 1292 956 a* = sonic velocity of igniter gas, fps
Loss to ambient (Qr + Qc) -50 -50 Cw = flow coefficient - (yg/RT)Q-5[2/(y + 1)] X
Mechanical work (Q mec h) 250 167 exp(7 + l)/2(y — 1), sec"1
1641 g = earth gravitational acceleration, ft/sec2
1194 M = Mach number
m = igniter mass flow rate, slugs/sec
P = pressure, psia
chosen as a realistic theoretical outlet temperature based on fPdA = integrated pressure, area force of chamber gas on
experimental data. Curve C represents the test data; the converging portion of motor exhaust nozzle, Ibf
vertical line through each data point represents the estimated R = gas constant, ft/°R
error range. Comparison of Curve C to Curve A at 4 cfm T = igniter gas total temperature, °R
indicates a ventilation efficiency of 58%. The thermal V = volume, ft 3
balances in Table 1 were established during the second test. v = velocity, fps
Downloaded by 121.200.6.58 on November 30, 2019 | http://arc.aiaa.org | DOI: 10.2514/3.28296

The ventilation flow rate remained constant at 4.1 cfm at w = igniter flow rate, Ib/sec
2
STP. The heat loads removed by the stream (Qs + Qi) at
r = i + ( T - i)/2 M
7 = ratio of specific heats
1.5 Kp work load and 1.0 Kp work load were 1441 and 1077 e* = ratio of minimum annular flow area between igniter
Btu/hr, respectively. The mean body temperature was and motor exit cone to the motor throat area
1.2°F higher at stabilization during the 1.5 Kp work load
than during stabilization at 1.0 Kp work load. Excessive Subscripts
sweat, during the 1.5 Kp work-load period, "pooled" in the e = at motor throat plane for gas leaving motor chamber
lower sections of the space suit and was relatively unavailable i = at motor throat plane for igniter gas entering motor
to the ventilation flow. The mean body temperature was chamber
steady during the stabilization period at 1.5 Kp work load ign = igniter
and continued to decrease during the 1.0 Kp work load. p = motor port
From these limited results, it appears that the subject would t = motor throat
have maintained an acceptable mean body temperature to = total conditions
0 = at motor plane entering nozzle converging section for
(within the physiological limitations of dehydration and fa- gas leaving motor chamber
tigue) indefinitely when working at a 1.0 Kp load with a 4- 1 = initial or ambient conditions
cfm-at-STP ventilation flow rate, and that this flow rate 2 = pressurized conditions
probably is adequate for a 1.5 Kp work load. However, s = static conditions
it must be noted that the Qi's measured correspond to the
evaporation of approximately 0.9 to 1.3 Ib/hr of body water, Introduction
so that dehydration will result with prolonged work in the
space suit. Hence, means for replacing lost water and elec-
trolytes must be provided in the final design and included in
T HE conventional igniter for a solid-propellant rocket
motor generates hot gas, which impinges on the motor
propellant and raises the motor chamber pressure. It is
the space suit's operational requirements. normally positioned in the forward end of the motor. An
Conclusion aft-end igniter is positioned near the motor throat and dis-
charges its gas through the motor throat into the motor
Suited subjects at 35,000-ft simulated altitude, instru- chamber. Design values for mass flow rate and operating
mented for electrocardiograms and rectal and skin tempera- pressure of the conventional igniter have been determined
tures, performed work satisfactorily on a bicycle ergometer largely through testing. Such a trial-and-error procedure
at a constant metabolic rate (1500 Btu/hr) while the ventila- would be very costly on the 260-in.-diam motor. The
tion rate was successively increased from 2.5 to 5.8 cfm STP analytical model described herein permits the sizing of aft-
and at different metabolic rates (1080 and 1655 Btu/hr) while end igniters to obtain desired motor chamber pressure and
the ventilation rate was held constant at 4.1 cfm at STP. igniter-gas penetration prior to propellant ignition. These
At a work load of 1.5 Kp on the ergometer, the total heat design criteria are presented as functions of the pertinent
leaving the subject was calculated to be 1641 Btu/hr (sensible, motor and igniter parameters, and the equations are pre-
149; latent, 1292; mechanical, 250; convective and radiant, sented graphically for an igniter operating at 1000 psia. The
— 50) compared to a metabolic generation rate (as indicated analysis does not allow prediction of the over-all ignition
by C02 production) of 1655 Btu/hr. Results of the first test transient, which will require more comprehensive treatment.
(Fig. 4) suggest that the heat removed by the ventilation
stream would not be significantly increased by a flow rate Analytical Model
greater than 4 cfm at STP, at which the ventilation efficiency
was 58% for Qmet = 1500 Btu/hr. These limited data sug- The analytical model is based on the following two ele-
gest that the suit ventilation is adequate for continuous work mentary concepts: 1) the incoming igniter gas expands to
at the levels investigated, but that body dehydration would the static pressure in the motor throat and requires a portion
result from prolonged work in the suit. of the throat flow area; the remaining flow area must be
sufficient to allow the same flow out of the motor at the same
static pressure at sonic velocity; and 2) the incoming flow
References must be turned around in order to flow out the motor; since
1
Bard, P., Medical Physiology (C. V. Mosby and Co., St.
Louis, Mo., 1956), p. 580. Received January 6, 1954; revision received March 30, 1965.
2
Benjamin, F., personal communication, Office of Space Medi- * Development Engineer; now with Chrysler Corp., Highland
cine, NASA Headquarters, Washington, D. C. (July 1964.) Park, Mich.

You might also like