Professional Documents
Culture Documents
00
Printed in the U.S.A. ~ 1985 Pergamon Press Ltd.
167
168 A. I. KUDISH et al.
CONSTANTLEVEL
B
TOUT
h2 h3
TIN ~ - - F
h~
t
Fig. I. Schematic diagram of experimental simulated thermosiphon system.
most Israeli thermosiphon D H W systems. A some- flow rate. The rate of thermosiphon flow was meas-
what different application of such a single-pass ured periodically throughout the day during the
thermosiphon system has been reported re- sunshine hours.
cently[14]. The threshold AT (i.e. Tout - Ti,) values nec-
The direct measurement of the thermosiphon essary for the initiation of thermosiphon flow in the
flow rate was accomplished by simply collecting the morning, corresponding to the different thermo-
solar heated water effluent from the solar collector siphon heads studied, were also determined. This
in a graduated cylinder during a prescribed time in- was achieved by continuously monitoring the inlet
terval (usually 1 min.). The inlet and outlet water and outlet temperature to and from the solar col-
temperatures to and from the solar collector were lector. The threshold A T value corresponds to the
monitored continuously by means of type T (cop- instant when thermosiphon flow is initiated and is
per-constantan) thermocouples inserted into 4-mm evidenced graphically when the inlet temperature
copper tubing probes and connected to a multipoint drops to the main's water temperature and the out-
recorder (Chino) (see Fig. 1). The inlet and outlet let temperature rises rapidly (cf Fig. 2). The meas-
legs (viz. auxiliary plumbing) of the solar collector
were insulated with glass wool molded shells, which
were wrapped with aluminum laminate. The latter
I
efficiencies. Toui
The solar collector used in this study was a stan- v
-- b
90-
80-
Z
70-
..J 60-
ill •
v 50-
LU 40-
H-
<~ El • •
135 :.'50-
20~-
0 I0
_J
ii
0 I I I
55 65 75 85
Table 1. A v e r a g e t h e r m o s i p h o n flow rate v s (h3 - h2) days are not as clear and wind gusts are much more
during the time period 10:00-14:00 frequent).
180
160 .U
140
Ld
I-- 120
rY I00
8O
0 60
/
%
LL
4O
2O
0 I I I I I
20 SO 40 50 60 70
INSOLATION ( K J / M I N * M * ~2)
Fig. 5. T h e r m o s i p h o n flow rate vs global insolation rate for (h3 - h2) = 0.7 m.
Direct measurement and analysis of thermosiphon flow 171
EFFICIENCY VS TIME H =0 5 5 M
>.-
¢.D ,,,¢,, • . • • • ,~
Z
LLI 3 . /v \ . \
13_ 2 /~ ~..~
LL
LLI
0 I I I I I I, I
9 tO II 12 13 14 15 16
TIME (HR)
those for all cases. The instantaneous collector ef- ciency testing of solar collectors in the thermo-
ficiency increases with increasing thermosiphon siphon mode (in which they are intended to operate)
head [viz. ( h 3 -- hj)]. This is expected; since rh as opposed to the widely used forced circulation
increases more rapidly, then A T decreases with in- mode of testing. The results are presented graphi-
creasing thermosiphon head. Also the early morn- cally in Fig. 7 and the linear regression curve for
ing (<10:00) efficiency values are greater than the these data is
late afternoon (>14:00) values and that the latter
decrease quite rapidly. It is of interest to note that ( T i n - Tamb)
the maximum instantaneous efficiency (i.e. the "q = FR('ra)e - FRUL (2)
G
range) decreases with increasing values of Tm (see
Table 4). This is caused by the increased temper- where FR('ra)e = 0.79, FRUL = 22.4 W/m2'°C and
ature gradient (Tin - Tamb) and consequent faster the correlation factor = 0.95.
rate of heat loss.
Io[-
07!
0.50 , "~"
025-
0 I I I I 1
O[ 012 015 04 05
eqn (3), we arrive at factor (i.e. the sum of the individual section friction
factors adjusted by the continuity equation, p~ VIA~
hr = Ti, - Tout (2AT - B)(h3 - hl), (4) = p2V2A2). The fluid temperature does not vary in
2 transit between the Tou, probe position and the pipe
outlet (B) due to both the insulation and its rela-
where A = - 1.25 × 10 -6, B = 5.83 x 10 -5 and tively short residence time. Thus, the value of 9B
= (Tin + Tom)/2. (The temperature units for eqn corresponds to that at T = Tou t and the value of V8
(4) are °F as per the parabolic equation fit for the is the volumetric flow rate measured divided by the
specific gravity in [2]). outlet pipe cross-sectional area. We have utilized
The thermosiphon flow through the collector the continuity equation to calculate the linear flow
was analyzed by means of applying Bernoulli's rate within the various sections of the experimental
equation between A and B, on Fig. 1, i.e. system. The temperature (density) was assumed
constant within the inlet and outlet legs of the solar
collector. The temperature within the riser was as-
PA + gZAPA + - ~ DA sumed to increase linearly and the density as per
the parabolic relationship in [2]. The friction factor,
v~ _ v~ skin and fittings, was determined for each section
= PB Jr- gZBPB "~- T OB -~ E l~'i T Pi, (5)
of the system. The values for the thermosiphon
pressure head and overall system friction factor
where P is the pressure; Z, height above reference; were inserted into eqn (7) which was then solved
p, density; V, linear velocity; and F, friction factor. for VB. The agreement between the calculated and
In our system Pa = PB, ZA = ZB, and VA = 0 (i.e. experimental values was about 10%, which is quite
in the constant level device). Thus eqn (5) reduces satisfactory considering the lack of precision in de-
to termining friction factors for any particular system.
they should be inversely proportional if the ther- 3. The correlation between thermosiphon flow
mosiphon pressure head is, indeed, invariable. This and global insolation rate was observed to be
was verified by calculating the corresponding ther- linear for all cases studied.
mosiphon pressure heads, using the left-hand side 4. The thermosiphon pressure head required to in-
of eqn (7), and the results are presented in Table 4, itiate flow in the morning was shown to be
column 4. The standard deviation (-3.2%) is quite constant.
small considering the uncertainty involved in de- 5. The friction factor analysis of the system ver-
termining the threshold temperatures (cf. Fig. 2). ified the experimental technique.
The constant thermosiphon pressure head is evi-
dence of the accuracy of our technique of insuring
that the fluid levels (inlet and outlet) were equal (i.e. Acknowledgement--The authors wish to express their
zero hydrostatic pressure head) prior to measuring gratitude to the International Association for the Ex-
the thermosiphon flow rate. change of Students for Technical Experience (IAESTE)
for enabling two of us (P.S. and P.B.) to participate in this
research project.
C. Solar collector efficiency
The increase in efficiency with increasing ther-
mosiphon head is an important consideration when
dealing with single-pass systems. In practice, while REFERENCES
there is a minimum thermosiphon head necessary
to prevent reverse thermosiphon flow during the 1. Y. Nowarski, Israel Ministry of Energy and Infra-
structure, Department of Energy Conservation, pri-
night, the thermosiphon head is generally deter- vate communication. 1984.
mined by where the system is positioned and its 2. D. J. Close, Performance of solar water heaters with
aesthetic and architectural interaction with its sur- natural circulation. Solar Energy 6, 33 (1962).
roundings. 3. G. L. Gupta and H. P. Garg, System design in solar
water heaters with natural circulation. Solar Energy
The commencement of thermosiphonic flow is 12, 163 (1968).
also a function of thermosiphon head, in that the 4. K. S. Ong, A finite-difference method ot evaluate the
greater (other parameters being constant) the ear- thermal performance of a solar water heater. Solar
lier the onset of thermosiphon flow and consequent Energy 16, 137 (1974).
5. K. S. Ong, An improved computer program for the
solar energy conversion. This is because the greater
thermal performance of a solar water heater. Solar
the thermosiphon head the lower the threshold A T Energy 18, 183 (1976).
value required to overcome system inertia. Thus, 6. Y. Zvirin, A. Shitzer and H. Grossman, The natural
both system efficiency and total daily hours of op- circulation solar heater models with linear and non-
eration are proportional to the thermosiphon head. linear temperature distribution. Int. J. Heat Mass
Transfer 20, 999 (1977).
This explains why the onset of flow in the case of 7. A. Shitzer, D. Kalmanoviz, Y. Zvirin and G. Gross-
(h3 - h2) = 0 was relatively late, i.e. after 10:00. man, Experiments with a fiat plate solar water heating
system in thermosiphone flow. Solar Energy 22, 27
(1979).
5. CONCLUSIONS 8. G. L. Morrison and D. B. J. Ranatunga, Transient
response of thermosiphon solar collectors. Solar En-
1. We have shown how a very simple and well- ergy 24, 55 (1980).
known laboratory technique can be adapted to 9. G. L. Morrison and D. B. J. Ranatunga, Thermo-
measure the rate of thermosiphon flow directly siphon circulation in solar collectors. Solar Energy
and thereby be used to perform standard effi- 24, 191 (1980).
10. B. J. Huang, Similarity theory of solar water heater
ciency tests on solar collectors operating in the with natural circulation. Solar Energy 25, 105 (1984).
thermosiphon mode. 11. M. S. Sodha and G. N. Tiwari, Analysis of natural
2. The thermosiphon flow rate was found to sta- circulations solar water heating systems. Energy Con-
bilize during the mid-day hours as did the A T version and Management 21, 288 ( 1981).
values across the solar collector. The exception 12. M. F. Young and J. B. Bergquam, Performance char-
acteristics ofa thermosiphon solar domestic hot water
to this observation was in the case of (h3 - h2) system. ASME J. Solar Energy Engng. 103, 193
= 0, where the correlation between thermo- (1981).
siphon flow and A T was linear, independent of 13. B. Norton and S. D. Probert, Natural circulation
Ti, values. The latter may be a result of the solar-energy stimulated systems for heating water.
Applied Energy 11, 167 (1982).
greater sensitivity of the thermosiphon flow to 14. Y. F. Wang, Z. L. Liand and X. L. Sun. A "'once-
A T since the thermosiphon pressure head is rel- through" solar water heating system. Solar Energy 29,
atively low. 541 ~1982).