General purpose current function (over and under) for
• phase fault protection
• back-up protection
B. Features
• insensitive to DC component
• insensitive to harmonics
• single or three-phase measurement
• maximum respectively minimum value detection in the three-
phase mode
• detection of inrush currents.
I. C.t./v.t. inputs:
• Current
IV. Measurements:
• current amplitude.
1
ABB Power Automation Ltd REC 316*4 1MRB520044-Uen / Rev. F
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
Delay
Time between the function picking up and tripping.
I-Setting
Pick-up current setting.
Forbidden settings:
• > 1.6 IN when supplied from metering cores
• < 0.2 IN when supplied from protection cores.
MaxMin
defines operation as overcurrent or undercurrent or with
inrush blocking. Settings:
• MIN (3ph): Undercurrent.
Three-phase functions detect the highest
phase current.
Not permitted for single-phase functions.
• MIN (1ph): Undercurrent.
Three-phase functions detect the lowest
phase current.
2
REC 316*4 1MRB520044-Uen / Rev. F ABB Power Automation Ltd
3
ABB Power Automation Ltd REC 316*4 1MRB520044-Uen / Rev. F
E. Setting instructions
Settings:
Setting I-Setting
Delay Delay
Over or undercurrent MaxMin
Number of phases NrOfPhases
Setting I-Setting
The current setting ‘I-Setting’ must be sufficiently high on the one
hand to avoid any risk of false tripping or false signals under
normal load conditions, but should be low enough on the other to
detect the lowest fault current that can occur. The margin which
has to be allowed between the maximum short-time load current
and the setting must take account of:
• the tolerance on the current setting
• the reset ratio.
The maximum short-time load current has to be determined ac-
cording to the power system conditions and must take switching
operations and load surges into account.
I-Setting
IN
Delay
4
REC 316*4 1MRB520044-Uen / Rev. F ABB Power Automation Ltd
IGN 800 A
1 .5 = 1 .5 = 1. 2
IN1 1000 A
CurrentInp
An interposing c.t. in the input is essential for current settings
lower than < 0.2 IN.
Delay
The delay is used to achieve discrimination of the overcurrent
function. It is set according to the grading table for all the over-
current units on the power system. The zone of protection of our
overcurrent function extends to the location of the next down-
stream overcurrent relay.
Should the downstream relay fail to clear a fault, the overcurrent
function trips slightly later as a back-up protection.
Setting MaxMin
This parameter enables the following operating modes to be
selected:
• MIN (3ph): Pick-up when the highest phase current also
falls below the setting. This setting is not per-
mitted for single-phase measurement.
• MIN (1ph): Pick-up when the lowest phase current falls
below the setting.
• MAX (3ph): Pick-up when the lowest phase current also
exceeds the setting. This setting is not permit-
ted for single-phase measurement.
• MAX (1ph): Pick-up when the highest phase current ex-
ceeds the setting.
• MAX-Inrush: Blocking of inrush currents when a phase
current exceeds the setting.
5
ABB Power Automation Ltd REC 316*4 1MRB520044-Uen / Rev. F