5.1. Introduction
When the slab is supported on all four sides and the length is less than twice the width, the slab will deflect in two
directions, and the loads on the slab are transferred to all four supports. This slab is referred to as a two-way slab. The
bending moments and deflections in such slabs are less than those in one-way slabs; thus, the same slab can carry more
loads when supported on four sides. The load in this case is carried in two directions, and the bending moment in each
direction is much less than the bending moment in the slab if the load were carried in one direction only.
b. Flat plate
A flat-plate floor is a two-way slab system consisting of a uniform slab that rests directly on columns and does not
have beams or column capitals. In this case the column tends to punch through the slab, producing diagonal tensile
stresses. Therefore, a general increase in the slab thickness is required or special reinforcement is used.
31
c. Flat slab
A flat slab is a two-way slab reinforced in two directions that usually does not have beams or girders, and the
loads are transferred directly to the supporting columns. The column tends to punch through the slab, which can
be treated by three methods:
32
5.3. Design Methods
An exact analysis of forces and displacements in a two-way slab is complex, due to its highly indeterminate nature; this
is true even when the effects of creep and nonlinear behavior of the concrete are neglected. Numerical methods such as
finite elements can be used,but simplified methods such as those presented by the Code are more suitable for practical
design. The Code specifies two methods:
The systems that do not meet the requirements permitting analysis by the "direct design method" of the present code,
has led many engineers to continue to use the design method of the 1963 ACI Code (The coefficient method) for the
special case of two-way slabs supported on four sides of each slab panel by relatively deep, stiff, edge beams. It has
been used extensively here since 1963 for slabs supported at the edges by walls, steel beams, or monolithic concrete
beams having a total depth not less than about 3 times the slab thickness. While it was not a part of the 1977 or later
ACI Codes, its continued use is permissible under the current code provision (ACI Code 13.5.1) that a slab system may
be designed by any procedure satisfying conditions of equilibrium and geometric compatibility, if it is shown that the
design strength at every section is at least equal to the requiredstrength, and that serviceability requirements are met.
33
5.5. Minimum Thickness of Two-Way Slab
A. For slabs without interior beams spanning between the supports and having a ratio of long to short span not greater
than 2, the minimum thickness shall not be less than:
125 mm for slabs without drop panels
100 mm slabs with drop panel
B. For slabs with beams spanning between the supports on all sides, the minimum thickness shall be as follows:
For 0.2 fm 2 fy
ln 0.8 1400
h max , 125
36 5 fm 0.2
For fm 2 fy
ln 0.8 1400
h max , 90
36 9
fm 2 h minimum thickness without interior beams
34
Where:
ln clear span in the long direction measured face to face of columns (or face to face
of beams for slabs with beams)
the ratio of the long to the short clear spans
fm the average value of f for all beams on the sides of a panel
f the ratio of flexural stiffness of a beam section Ecb Ib to the flexural stiffness of
the slab Ecs I s bounded laterally by the centerlines of the panels on each side of
the beam
Ecb I b
=
Ecs I s
Ecb modulus of elasticity of concrete beam
Ecs modulus of elasticity of concrete slab
I b the gross moment of inertia of the beam section about the centroidal axis (the
beam section includes a slab length on each side of the beam equal to the
projection of the beam above or below the slab, whichever is greater, but not more
than four times the slab thickness)
I s the moment of inertia of the gross section of the slab
However, the thickness of any slab shall not be less than the following:
For slabs with fm 2 then thickness 125 mm
For slabs with fm 2 then thickness 90 mm
If no beams are used, as in the case of flat plates, then f 0 and fm 0 . The Code
equations for calculating slab thickness, h , take into account the effect of the span
length, the panel shape, the steel reinforcement yield stress, f y and the flexural stiffness
of beams. When very stiff beams are used,
fy
ln 0.8 1400
h max , 125
36 5 fm 0.2
may give a small slab thickness, and
fy
ln 0.8 1400
h max , 90
36 9
may control. For flat plates and flat slabs, when no interior beams are used, the
minimum slab thickness may be determined directly from the table for minimum
thickness of slabs without interior beam as shown above.
35
b) For slabs supported on beams having f 1 , the opposite is true, and the reinforcing pattern should be
reversed.
Problem Set 6:
1. Using the Code, determine the minimum permissible total thickness required for the slabs in panels 1 and 2 for the
floor system shown in the figure below. Edge beams are used around the building premeter, and they are 300mm
wide and extend vertically for 200 mm below the slab. They also extend 200 mmout onto the slab as required by
the Code. No drop panels are used, and the concrete in the slab is the same as that used for edge beams.
f y 420MPa
2. The two-way slab shown below has been assummed to have a thickness of 175 mm. Section A-A in the figure
shows the beam cross section. Check the Code equations to determine if the slab thickness is satisfactory for an
interior panel. f c 21MPa , f y 420MPa , and normal weight concrete.
'
36
Chapter 6
Design of Two-Way Slab by ACI Coefficient method
This method was provided in the American Concrete Institute (ACI) in 1963 to design two-way slabs carried by steel beams,
deep beam, or walls. Nonetheless, the coefficient method is not included in the current edition of the ACI code. This is
because it is considered to be too conservative and more precise approaches can be employed. However, it should be known
that the coefficient method is still applied for two-way slabs.
The coefficient method employs tables of moment coefficients for different slab edge conditions. The conditions are based
on elastic analysis but inelastic redistribution is accounted for as well.
As a result, the design moment on both directions is smaller by a specific amount than the ultimate elastic moment in that
exclusive direction.
According to the coefficient approach, the slab is divided into the middle strip and column strip in each direction. The width
of the latter is equal to the one-quarter of the panel width whereas the width of the former is one-half the panel width, as
illustrated in Fig.1.
The following equations can be used to estimate negative and positive moments in the two directions:
M a Ca wla2 Where:
Ca and Cb = tabulated moment coefficients
M b Cb wlb2
w = uniform load, kN/m
la , lb length of clear span in short and long directions
respectively.
The ACI Coefficient Tables are designed to give appropriate coefficients based on the edge conditions of the slab
Refer to the figure below for the different edge conditions:
37
The numbers correspond to the edge conditions in the following tables:
Case 4: 2 edges continuous, 2 edges discontinuous
Case 8: 3 edges continuous, 1 edge discontinuous
Case 2: 4 edges continuous
Note:
At continuous edges, moments are negative similar to continuous beams
at interior supports.
As expected in two-way slabs, the moments in both directions are larger in the center portion of the slab than the edges.
Therefore, the middle strip must be designed for the maximum tabulated moment. In the edge strips, the strips must be
designed for 1/3 of the maximum value of the calculated moment.
Problem Set:
A monolithic reinforced concrete floor is to be composed of rectangular bays measuring 6.5 m by 8 m, as shown. Beams of
width 300 mm and 600 mm depth are provided on all column lines. The floor is to be designed to carry a service live load
5 kPa and a dead load on the slab due to self-weight plus weight of:
Find the required slab thickness and reinforcement for the corner panel shown.
38
39
40
41
42
43