List of Limit Values, PLC release: 2.50.04 CPU-P

Last revised on: 03.11.09


Docu-ID: GW_620_2020_2.50.04_EN_CPU-P

We reserve the right on necessary technical modification of the product, deviating from this document in order to improve the engines.
The reproduction, transmission or use of this document or its content is not permitted without express written authorization.
System Manual

This document applies to the following gas engines:

Series:
620, 2020

Impressum:
MWM GmbH
Service VS
Carl-Benz-Straße 1
D68167 Mannheim, Germany
Phone: +49 (0) 6 21 3 84-0
Fax: +49 (0) 6 21 3 84-88 41
www.mwm.net
Printed in Germany
All rights reserved

© GW_620_2020_2.50.04_EN_CPU-P
TEM Evolution System

Notes

1 Notes

1.1 Validity 1.2 Design of the List of Limit values


This list of limit values is only valid for gas engines disbributed by MWM
equipped with the TEM-Evo-System. It is only suitable for the engine type ind- Column Explanation
cated on the front page.
Identification
The list of limit values is valid for the following software release until a new list
of limit values will be published. Name of the limit value

• 2.50.04 CPU-P Sensor monitoring

Fault Event of type »Fault«


Please observe the following documents:


The genset is shut down immediately.
• Operating instructions MWM
• User's guide and system manual of the TEM-Evo systems, Fault. SC Event of type »Fault SC«
particularly the system manual “Operation log”« The genset is stopped by controlled shutdown.
See “Function Fault SC” page 5.

Alarm Event of type »Alarm«


The alarm is recorded as a note in the operation log.

Alarm (LR) Event of type »Alarms (LR)«


The admissible power is limited.
The alarm is recorded in the operation log.
See “Function Alarm (LR)” page 5.

Time of delay with Limit value for monitoring with delay time
unit

RA RA: Remote acknowledgement


10 h: Remote acknowledgement every 10 h possible
X: Fault that can be remotely acknowledged
(all alarms can be remotely acknowledged).

© GW_620_2020_2.50.04_EN_CPU-P Page 3
TEM Evolution System

Notes

Column Explanation Column Explanation

Monitoring RA see before

Monitoring of the measured value for observance of the NA X: Automatically acknowledgeable fault in case of
limit value mains fault.
In case of a mains fault under 30 s the
Undershooting of a limit value with fault TEM-Evo-System tries to re-establish the
readiness for start by automatic acknowledge of the
Undershooting of a limit value with alarm
marked faults.
Undershooting of a limit value with message
Comment Comment
Exceeding a limit value with fault

Exceeding a limit value with alarm

Exceeding a limit value with message

Limit value Limit value for monitoring with unit


For parameter depending limit values that value is
indicated which results from the default value of the
parameter.
The way to find the default value of the parameter is
described in column »Comment«.

Delay Time of delay with unit

© GW_620_2020_2.50.04_EN_CPU-P Page 4
TEM Evolution System

Notes

1.2.1 Function Fault SC


Load run
During load run (mains parallel mode) a fault of the type »Fault SC« causes the
controlled shutdown of the genset.
When a »Fault SC« appears the admissible power is immediately set to the
current actuall power. Thus a further increase of the power is prevented.
After expiration of the delay time (e.g. 5 minutes) the admissible power is re-
duced to 0.0 %. The set power follows the admissible power to a parameteris-
able ramp.
• Setting of the delay timet:
Parameter »10033 Delay time fault SC«
• Specification of the ramp for the set power: Figure 1: Controlled shutdown of the genset with »Fault SC«
Parameter »23007 Power control set ramp controlled shutdown«
In case that the value of the actual power is below 10 %, the genset is dese- 1.2.2 Function Alarm (LR)
lected. Events of type »Alarm (LR)« are intered in the operation log as an »alarm. Ad-
Note ditionallz, the admissible power is restricted to maximally 80 %. The power re-
duction is marked in the operation log by the alarm »Power reduction to safe
If all faults of type »Fault SC« can be acknowledge in the operation log during
power«.
the shut down process, the power is increased again to the externally demand-
ed power and the load run is continued.
Idle
If the genset is not operated in load run, every fault of type »Fault SC« causes
the immediate shutdown of the genset. With a pending »Fault SC« a start of
the genset or the idling operation are impossible.

© GW_620_2020_2.50.04_EN_CPU-P Page 5
TEM Evolution System

Notes

1.3 Abbreviations Abbreviations Explanation

Abbreviations Explanation NA Handling of mains fault

AES Demand of external starting preparations NATL Monitoring of the exhaust gas temperature after exhaust
turbocharger
AKR Anti-knock governor
NAWT Exhaust gas temperature after exhaust heat exchanger
AVW Preheating air inlet
NFI Lube oil pressure after filter
AWG Exhaust wastegate
NK Emergency cooling circuit
BY Exhaust bypass
NKS Emergency cooler - dry cooler
CH4 Additional CH4 compensation
NKV Valve position NK valve
CH4K Extension of option CH4.
NKAT Monitoring of the exhaust gas temperature after catalyst
DK Leakage check
NMOT Monitoring of the exhaust gas temperature after engine
GK Intercooler circuit
QEÜ Acknowledgement of external monitorings
GKS Intercooler-dry cooler
REC Registration of receiver pressure
GKV Valve position of the GK valve
RL Control of cabin air temperature
GL Monitoring of the generator bearing temperatures
RL1 Cabin ventilation with admixture or frequency-controlled
GLU Generator air temperature coolers
GW Generator winding temperatures SATL Measuring and limitation of the exgaust turbocharger
speed
HK Heat utilization with heating circuit
VAWT Measuring of the heating water temperature before
HKV Valve position HK valve
exhaust gas heat exchanger
MK Jacket water control
VBP Compressor bypass

© GW_620_2020_2.50.04_EN_CPU-P Page 6
TEM Evolution System

Notes

Abbreviations Explanation

VKWT Jacket water temperature before jacket water heat


exchanger

VNK Heating water temperature before emergency cooler

VSWT Measuring of jacket/heating water before lube oil


exchanger

xM Parameterisable messages

xMW Parameterisable data

xPR Parameterisable control circuits

ZG Dual gas operation with change of the gas type only at a


standstill

ZGM Dual gas operation with composite mode

© GW_620_2020_2.50.04_EN_CPU-P Page 7
TEM Evolution System

List of Limit Values

2 List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


T202 Jacket water GK inlet Fault. SC 500 ms X [GK]
T206 Jacket water engine outlet Fault. SC 500 ms X
Alarm 98,0 °C 2s
Fault 99,0 °C 2s X X
Message 20,0 °C 240 min
T202 Jacket water GK inlet Fault. SC 500 ms X
Message 80,0 °C 5 min Power reduction; Limit value: Par.
13400; Island: Delay 30s
Fault 98,0 °C 2s X
Collective fault jacket water tempera-
tures Fault 0 ms T206 and T207 failed, automatically
acknowledgeable
P196 >Lube oil before filter Fault. SC 500 ms X
Alarm 3.00 bar 0 ms Operational oil pressure
Fault 0.30 bar 1 min Start prelubrication Delay at a stand-
still: 60s
Fault 2.80 bar 0 ms Operational oil pressure
P302 Lube oil after filter Fault. SC 500 ms X
Alarm 4.00 bar 500 ms Operational oil pressure 900rpm:
Limit value .5.0bar
Fault 0.30 bar 1 min
Fault 3.80 bar 500 ms Operational oil pressure 900rpm:
Limit value 4.8bar

© GW_620_2020_2.50.04_EN_CPU-P Page 8
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


P302.1 Differential pressure lube oil
Alarm 1.00 bar 2 min
Fault. SC 1.50 bar 2 min
Alarm -1.00 bar 2 min
T208 Lube oil Fault. SC 500 ms
Alarm 105,0 °C 2s
Fault. SC 110,0 °C 2s
L234 Lube oil level Fault. SC 500 ms
L234.1 Lube oil level Filtered value
Message 95,0 % 0 ms Enabling only during oil change
Fault 120,0 % 20 s 10 h With the engine at standstill delay 1s
Message 50,0 % 0 ms Enabling only during oil change
Fault 30,0 % 20 s 10 h With the engine at standstill delay 1s
Xxxx Number of pre-lube faults
Alarm 0 0 ms 1. Prelube fault
Fault 5 0 ms
T201 Receiver Fault. SC 500 ms X [GK]
Message 52,0 °C 5 min Power reduction; Limit value: Par.
13800; Island: Delay 30s
Message 55,0 °C 2s Limit value: Par. 13800 + 3,0K
Fault. SC 57,0 °C 2s 10 h Limit value: Par. 13800 + 5,0K
T378 Receiver B Fault. SC 500 ms X [GK]
Message 52,0 °C 5 min Power reduction; Limit value: Par.
13800; Island: Delay 30s
Message 55,0 °C 2s Limit value: Par. 13800 + 3,0K
Fault. SC 57,0 °C 2s 10 h Limit value: Par. 13800 + 5,0K

© GW_620_2020_2.50.04_EN_CPU-P Page 9
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


T203 Inlet air Alarm 500 ms
Message 30,0 °C 0 ms With [AVW] limit value: Par.
23230/23231 + 3.0K
Alarm 35,0 °C 2 min [RL without T404]; Limit value par.
13900 - 5.0K
Fault. SC 40,0 °C 2 min X [RL without T404]; Limit value par.
13900
Alarm 20,0 °C 30 s Enabling after 1 h engine running;
Limit value par. 23230 - 5.0K
T377 Intake air B Alarm 500 ms
Message 30,0 °C 0 ms With [AVW] limit value: Par.
23230/23231 + 3.0K
Alarm 20,0 °C 30 s par. 23230 - 5,0K
P232 Receiver Alarm 500 ms [REC]
P270 Receiver B Alarm 500 ms [REC]
P268 Boost pressure Alarm 500 ms [REC]
T461 Combustion chamber A1 Fault. SC 500 ms X For each cylinder individually
Fault 600 °C 6s 10 h
Alarm 240 °C 20 s Limit value 50K-120K below average
value
Fault. SC 240 °C 2 min 10 h Limit value 50K-120K below average
value; Island operation: Verz. 8 min;
Leistungsreduktion solange unter
Grenzwert

© GW_620_2020_2.50.04_EN_CPU-P Page 10
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


T471 Combustion chamber B1 Fault. SC 500 ms X For each cylinder individually
Fault 600 °C 6s 10 h
Alarm 240 °C 20 s Limit value 50K-120K below average
value
Fault. SC 240 °C 2 min 10 h Limit value 50K-120K below average
value; Island operation: Verz. 8 min;
Leistungsreduktion solange unter
Grenzwert
T204 Cold junction A Fault. SC 500 ms X
T205 Cold junction B Fault. SC 500 ms X
T46x.7 Combustion chamber Average value side A
average Fault 450 °C 500 ms 10 h Limit value 100K (mains) / 160K
(island) above set value
T47x.7 Comb. chamber aver. B Average value side B
Fault 450 °C 500 ms 10 h Limit value 100K (mains) / 160K
(island) above set value
T4xx.2 Act. combustion chamber Filtered value
Fault 0 ms More than 2 sensors failed automati-
cally acknowledgeable
Fault 150 °C 0 ms
Deviation comb. chamber control
Fault. SC 10 °C 5 min 10 h With a higher deviation less delay
time
Fault. SC -10 °C 5 min 10 h With a higher deviation less delay
time

© GW_620_2020_2.50.04_EN_CPU-P Page 11
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


Deviation comb. chamber control B
Fault. SC 10 °C 5 min 10 h With a higher deviation less delay
time
Fault. SC -10 °C 5 min 10 h With a higher deviation less delay
time
Gas mixer limit stop lean
Message 4s Stop position not reached
Gas mixer start position OK
Message 0 ms Stop position not reached
Alarm 0 ms Start position not reached erreicht on
start abort
Gas mixer limit B stop lean
Message 4s Stop position not reached
Gas mixer B start position OK
Message 0 ms Stop position not reached
Alarm 0 ms Start position not reached erreicht on
start abort
T494 Exhaust after ATL A Alarm 500 ms [NATL]
Alarm 550 °C 15 min Limit value: par. 15111 / 15113
T495 Exhaust after ATL B Alarm 500 ms [NATL]
Alarm 550 °C 15 min Limit value: par. 15111 / 15113
T286 Exh. after engine Alarm 500 ms [NMOT]
Alarm 550 °C 2s Limit value: par. 15111 / 15113
T287 Exhaust after KAT Fault. SC 500 ms [NKAT]
Fault 550 °C 2s Limit value: par. 15111 / 15113
T496 Exhaust after CAT B Fault. SC 500 ms [NKAT]

© GW_620_2020_2.50.04_EN_CPU-P Page 12
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


T288 Exhaust after AWT Alarm 500 ms [NAWT]
Alarm 180 °C 2s Limit value: Par. 15112
S492 Speed ATL A Alarm 5s [SATL]
P157 Exhaust back press. too high Limit value switch
Alarm 50 mbar 2 min
Anti-knock governor available [AKR]
Alarm (LR) 0 ms AKR-card missing
AKR Speed signal [AKR] Error speed signal
Alarm (LR) 5s Enabling during load run
ZA maximum adjustment ignition [AKR] Sturdy ZZP-adjustment
point A side Alarm 0 ms Sturdy ZZP-adjustment; Limit value:
Par. 115036.0°; bit-coded display
ZA maximum adjustment ignition [AKR] Sturdy ZZP-adjustment
point B side Alarm 0 ms Sturdy ZZP-adjustment; Limit value:
Par. 115036.0°; bit-coded display
Critical fault! Engine test required! [AKR] Maximum ZZP-adjustment
Fault -9,0 ° 0 ms Limit value: Par. 11502 - 1,0 °; at
least -3.0 °
AKR Knock sensor fault bank A [AKR]
Alarm (LR) 10 s
AKR Knock sensor fault bank B [AKR]
Alarm (LR) 10 s
AKR Function block [AKR]
Alarm (LR) 0 ms
ZA Cabling of ignition coil bank A Cabling of ignition coi.
Message 0 ms
Alarm 1 min

© GW_620_2020_2.50.04_EN_CPU-P Page 13
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


ZA Cabling of ignition coil bank B Cabling of ignition coi.
Message 0 ms
Alarm 1 min
Ignition system ignites Feedback from ZA
Fault 3s 10 h Ignition does not ignite
Ignition system error code Fault message from ZA
Alarm 0 ms
Fault 3s 10 h
Ign. system capacitor discharge bank Error capacitor discharge
A Message 0 ms
Alarm 1 min
Ign. system capacitor discharge bank Error capacitor discharge
B Message 0 ms
Alarm 1 min
Ign. system condition serial Timeout ZA-communication
connection S Fault. SC 3s
Ign. system condition serial Error ZA-communication
connection W Message 0 ms
P145 Crank case Fault 0 ms
Fault 10,0 mbar 0 ms After start-up phase; limit value at
rated speed 1800 rpm: 20,0 mbar
Alarm -10,0 mbar 5 min with engine running
T501 Main bearing Alarm 500 ms [GLT]
xxxx Number of start attempts
Fault 3 0 ms 10 h X

© GW_620_2020_2.50.04_EN_CPU-P Page 14
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


S200 Engine speed
Alarm 1725,0 rpm 0 ms Limit value: Par. 11108 + 15% (bzw.
+20%), w. auto acknowledgement
Alarm 80,0 rpm 0 ms Speed bef. start
Fault 1725,0 rpm 200 ms Limit value: Par. 11108 + 15% (or.
+20%)
Fault 1350,0 rpm 500 ms 10 h Limit value depending on condition
S110 Set value speed Fault 500 ms X only with analogue specification of
the set speed
G197.1 Throttle valve position Fault 500 ms Feedback voltage; sensor monitoring:
Current voltage is < 1.00 V or > 3.30
V. actual value 4.00 V: Line V- inter-
rupted; Actual value < .1.00 V: Line
V- interrupted; otherw.: line V+, V- or
P interrupted
G197.Throttle valve position Fault 0 ms Position StG; sensor monitoring:
Current position is < -30.0 % or >
130.0 %
DZR Current derating
Alarm 5s Enabling during load run
DZR Short circuit power stage
Fault 0 ms
DZR TDC sensor error TDC-signal missing
Fault 2s 10 h Enabling with the engine running
Alarm 0 ms Enabling with the engine running,
auto acknowledgement

© GW_620_2020_2.50.04_EN_CPU-P Page 15
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


DZR Tooth number fault
Fault 2s 10 h Enabling with the engine running
Alarm 0 ms Enabling with the engine running,
auto acknowledgement
DZR TDC mixed up with gear ring
Fault 2s 10 h
Alarm 0 ms
E198 Actual power generator Fault 500 ms X
E198.2 Actual power Filtered value
Fault. SC 105,0 % 2 min Overload; Limit value: Par. 13100 +
5%
Fault 120,0 % 5s Overload
Fault -5,0 % 12 s X X Reverse power; Delay Par. 13510
E198.8 Actual power in KW
Alarm 410 kW 45 min Minimum load 620, 2020, 2020K;
V12: 305kW, V16: 410kW, 2020 V20:
585kW
Fault 410 kW 60 min X X Minimum load 620, 2020, 2020K;
V12: 305kW, V16: 410kW, 2020 V20:
585kW
Deviation power control
Fault. SC 5,0 % 5 min On start and retrace of the engine:
limit value 20%
Alarm -5,0 % 5s Exceeding the admissible power in
island operation
Fault -5,0 % 30 s Exceeding the admissible power in
island operation
Fault. SC -5,0 % 5 min

© GW_620_2020_2.50.04_EN_CPU-P Page 16
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


Power reduction due to jacket water
temperature Message 0,0 % 0 ms Enabling with message T207
Power reduction due to receiver [GK]
temperature Message 0,0 % 0 ms Enabling with message T201/T378
Power reduction due to throttle
Message 0,0 % 2 min Island: Delay 30s
Fault -40,0 % 0 ms
Power reduction due to CH4-value [CH4]
Message 0,0 % 0 ms Enabling with message Q311
Power reduction due to AKR [AKR]
Message 0,0 % 2 min Island: Delay 30s
Alarm 0,0 % 2 min Island: Delay. 30s, auto. acknowl-
edgeable, indicator of incorrect
parameterisation Par. 11502
Power reduction due to ATL speed [SATL]
Message 0,0 % 2 min Island: Delay 30s
Wastegate position (%) Fault. SC 0 ms [AWG] Position StG; sensor
monitoring: Current position is < -
30.0 % or > 130.0 %
Wastegate position (V) Fault. SC 500 ms [AWG] Feedback voltage sensor
monitoring: Current voltage is < 1.00
V or > 3.30 V. actual value 4.00 V:
Line V- interrupted; Actual value <
.1.00 V: Line V- interrupted; otherw.:
line V+, V- or P interrupted
Wastegate power decrease [AWG]
Alarm 2 min

© GW_620_2020_2.50.04_EN_CPU-P Page 17
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


Wastegate short-circuit output stage [AWG]
Fault 0 ms
Compressor bypass position (%) Fault. SC 0 ms [VBP] position StG; sensor
monitoring: Current position is < -
30.0 % or > 130.0 %
Compressor bypass position (V) Fault. SC 500 ms [VPB] Feedback voltage sensor
monitoring: Current voltage is < 1.00
V or > 3.30 V. actual value 4.00 V:
Line V- interrupted; Actual value <
.1.00 V: Line V- interrupted; otherw.:
line V+, V- or P interrupted
Compressor bypass power decrease [VBP]
Alarm 2 min
Compressor bypass short-circuit [VBP]
output stage Fault 0 ms
T209 Generator-winding U Fault. SC 500 ms [GK]
Alarm 135,0 °C 10 s Limit value: Par. 13500 - 5,0K
Fault 140,0 °C 10 s Limit value: Par. 13500
T210 Generator-winding V Fault. SC 500 ms [GK]
Alarm 135,0 °C 10 s Limit value: Par. 13500 - 5,0K
Fault 140,0 °C 10 s Limit value: Par. 13500
T211 Generator-winding W Fault. SC 500 ms [GK]
Alarm 135,0 °C 10 s Limit value: Par. 13500 - 5,0K
Fault 140,0 °C 10 s Limit value: Par. 13500
T459 Generator bearing A Fault. SC 500 ms [GL]
Alarm 55,0 °C 2s Limit value: Par. 13501 - 5.0K
Fault 60,0 °C 2s Limit value: Par. 13501

© GW_620_2020_2.50.04_EN_CPU-P Page 18
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


T460 Generator bearing B Fault. SC 500 ms [GL]
Alarm 55,0 °C 2s Limit value: Par. 13501 - 5.0K
Fault 60,0 °C 2s Limit value: Par. 13501
T487 Generator air inlet Fault. SC 500 ms [GLU]
Alarm 75,0 °C 2s Limit value: par. 13030 - 5,0K
Fault 80,0 °C 2s Limit value: par. 13030
T488 Generator air outlet Fault. SC 500 ms [GLU]
Alarm 75,0 °C 2s Limit value: par. 13030 - 5,0K
Fault 80,0 °C 2s Limit value: par. 13030
E121 Generator protection Input security chain
Fault 0 ms X X
Synchronization
Fault 10 min X X Timeout synchronization
E104 mains fault [NA]
Fault 30 s
Alarm 0 ms
Mains fault sequencial failure [NA]
Fault 0 ms
E199 Analogous demand Alarm 500 ms only with demand 4..20mA, Abwahl
bei Sensorwarnung
E199.7 demand active
Message 30,0 % 0 ms
T291 Heating water flow Fault. SC 500 ms [HK] Enabling with par. 14008
T289 Heating water-return Alarm 500 ms [HK] Enabling with par. 14009
Message 80,0 °C 10 s [NK]; Limit value: par. 24510
T290 Heating water before KWT Alarm 500 ms [VKWT]

© GW_620_2020_2.50.04_EN_CPU-P Page 19
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


T385 Heating water before AWT Alarm 500 ms [VAWT]
T386 Heating water before SWT Alarm 500 ms [VSWT]
P281 Heating circuit pump [HK]
Fault 0 ms X X
S397 HK Control valve position Alarm 500 ms [HKV]
T276 Overtemperature limiter 1 [HK] Input security chain
Fault 0 ms X X
T277 Safety temperature monitor [HK] Input security chain
Fault 0 ms X X
P278 Overpressure limiter [HK] Input security chain
Fault 0 ms X X
P279 Overpressure limiter 1 [HK] Input security chain
Fault 0 ms X X
L280 Low water heating circuit [HK] Input security chain
Fault 0 ms X X
P457 Pump coupling circuit [HK] Input security chain
Fault 0 ms X X
T435 Overtemperature limiter 2 [HK] Input security chain
Fault 0 ms X X
P437 Overpressure limiter 2 [HK] Input security chain
Fault 0 ms X X
Exhaust bypass AWT limit stop [HK+BY]
Closed Message 500 ms
P126 Flow monitoring engine cooling
circuit Fault 0 ms X X

© GW_620_2020_2.50.04_EN_CPU-P Page 20
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


L123 Low water engine cooling circuit Input security chain
Fault 0 ms X X
T156 Preheating genset
Alarm 2s
T419 Emergency cooler-dry cooler- Alarm 500 ms [NKS] Enabling with par. 14055
outlet
S000 NK Control valve position Alarm 500 ms [NKV] position feedback
P309 Flow monitoring intercooler [GK]
circuit Fault. SC 3s X X
L308 Low water intercooler circuit [GK] input security chain
Fault 0 ms X X
S000 Intercooler-control valve Alarm 500 ms [GKV] Position feedback
position
T405 Intercooler-dry cooler outlet Alarm 500 ms [GKS] enabling with par. 13085
T404 Cabin air Alarm 500 ms [RL1x] enabling with par. 13092
Message 32,0 °C 2s Limit value: par. 13900 - 8,0K
Alarm 35,0 °C 2s Limit value: par. 13900 - 5,0K
Fault. SC 40,0 °C 2s X Limit value: par. 13900
Cabin ventilation [RL]
Fault. SC 3s X Delay during start 60s
P124 Gas pressure gas control
system Fault 0 ms X X [CH4] Auto acknowledgement (par.
12900)
P125 Leakage check gas control [DK]
system A Fault 1 min Timeout leakage check
T147 Temperature monitor gas
control system Fault 0 ms

© GW_620_2020_2.50.04_EN_CPU-P Page 21
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


P127 Gas pressure gas control [ZG ZGM]
system B Fault 0 ms X X [CH4] Auto acknowledgement (par.
12900)
P128 Leakage check gas control [ZG+DK]
system B Fault 1 min Timeout leakage check
T131 Temperature monitor gas [ZG]
control system B Fault 0 ms
Q311 CH4-value Fault. SC 2 s [CH4]
Message 0,0 % 30 s [ZGM] Deselection; enabling/limit
value: par. 12810, par. 12811
Message 30,0 % 0 ms [ZGM] Gas type change; Limit value:
par. 12806 - 8.0%
Message 38,0 % 0 ms Limit value: Par. 12806
Message 50,0 % 5 min Power reduction; Limit value: par.
12803; Island: Delay 30s
Fault. SC 38,0 % 5 min X Limit value: Par. 12806
Stop due to CH4 calibration [CH4K]
Fault. SC 75 min X Timeout calibration, manual
Alarm 75 min Timeout calibration, auto
G602.0 Throttle valve gas type A Alarm 500 ms X [ZGM]
actual
G602.6 Control deviation throttle [ZGM]
valve gas type A Alarm 10,0 % 1s
Alarm -10,0 % 1s
G603.0 Throttle valve gas type B Alarm 500 ms X [ZGM]
actual

© GW_620_2020_2.50.04_EN_CPU-P Page 22
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


G603.6 Control deviation throttle [ZGM]
valve gas type B Alarm 10,0 % 1s
Alarm -10,0 % 1s
E149 Voltage supply
Alarm 30,0 V 0 ms
Alarm 20,0 V 0 ms
Exxx Earth leakage monitor switching
cabinet Alarm 10 kOhm 5s
Voltage back-up battery
Alarm 3,30 V 1 min
Alarm 2,00 V 1 min
H141 Internal quick stop Input security chain
Fault 0 ms
H117 Ext. quick stop without heat Input security chain
removal Fault 0 ms
H116 Ext. quick stop with heat Input security chain
removal Fault 0 ms X X
Security chain Security chain open
Fault 0 ms X X
G143 Circuit breaker TEM swtiching
cabinet Fault 0 ms
Parameterisable message 01 [xM] par. message; free text
Message 0 ms X X Limit value, delay, type, enabling
parameterisable

© GW_620_2020_2.50.04_EN_CPU-P Page 23
TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA NA Comment


Parameterisable measured value 01 Alarm 500 ms [xMW] Par. measured value; free text
Message 0 0 ms X X Limit value, delay, type, enabling
parameterisable
Message 0 0 ms X X Limit value, delay, type, enabling
parameterisable
Control deviation parameterisable [xPR] control deviation par. governor;
controllers 1 XX=1..3
Message 10 0 ms X X Limit value, delay, type, enabling
parameterisable
H108.2 ZGM analogue external Alarm 500 ms X [ZGM]
demand gas type B