List of Limit Values, PLC release: 2.50.09 CPU-P

Last revised on: 2011-03-09


Docu-ID: GW_620_2020_2.50.09_EN_CPU-P

We reserve the right on necessary technical modification of the product, deviating from this document in order to improve the engines.
The reproduction, transmission or use of this document or its content is not permitted without express written authorization.
This is the translation of the German original document. In case of dispute the German original version will be taken as a reference.
System Manual

This document applies to the following gas engines:

Series:
620, 2020

Imprint:
MWM GmbH
Service VS
Carl-Benz-Straße 1
D68167 Mannheim, Germany
Phone: +49 (0) 6 21 3 84-0
Fax: +49 (0) 6 21 3 84-88 41
www.mwm.net
Printed in Germany
All rights reserved

© GW_620_2020_2.50.09_EN_CPU-P
TEM Evolution System

Notes

1 Notes

1.1 Validity 1.2 Design of the List of Limit Values


This List of Limit Values is only valid for gas engines disbributed by MWM
equipped with the TEM-Evo System It is only suitable for the engine type ind- Column Explanation
cated on the front page.
Identification
The List of Limit Values is valid for the following software release until a new
List of Limit Values will be published. Name of the limit value

• 2.50.09 CPU-P Sensor monitoring

Fault Event of type »Fault«


Please observe the following documents: The genset is shut down immediately.
• Operating Instructions MWM
• User's Guide and System Manual of the TEM-Evo Systems, Fault. SC Event of type »Fault SC«
particularly the System Manual »Operation log« The genset is stopped by controlled shutdown.
See “Function Fault SC” page 5.

Alarm Event of type »Alarm«.


The alarm is recorded as a note in the operation log.

Alarm RP Event of type »Alarm RP«


The admissible power is limited.
The alarm is recorded in the operation log.
See “Function Alarm RP” page 5.

Time of delay with Limit value for monitoring with delay time
unit

RA RA: Remote acknowledgement


10 h: Remote acknowledgement is possible every 10 h
X: Fault that can be remotely acknowledged
(all alarms can be remotely acknowledged).

© GW_620_2020_2.50.09_EN_CPU-P Page 3
TEM Evolution System

Notes

Column Explanation

Monitoring

Monitoring of the measured value for observance of the


limit value

Undershooting of a limit value with a fault

Undershooting of a limit value with an alarm

Undershooting of a limit value with a message

Exceeding a limit value with a fault

Exceeding a limit value with an alarm

Exceeding a limit value with a message

Limit value Limit value for monitoring with a unit


For parameter-depending limit values that value is
indicated which results from the default value of the
parameter.
The way to find the default value of the parameter is
described in column »Comment«.

Delay Time of delay with unit

RA see before

Level Acknowledgement of the monitoring is only possible with


an USB Authorisation Dongle with the indicated authori-
sation level.

Comment Comment

© GW_620_2020_2.50.09_EN_CPU-P Page 4
TEM Evolution System

Notes

1.2.1 Function Fault SC


Load run
During load run (mains parallel mode) a fault of the type »Fault SC« causes the
controlled shutdown of the genset.
When a »Fault SC« appears the admissible power is immediately set to the
current actuall power. Thus a further increase of the power is prevented.
After expiration of the delay time (e.g. 5 minutes) the admissible power is re-
duced to 0.0 %. The set power follows the admissible power to a parameteris-
able ramp.
• Setting of the delay timet:
Parameter »10033 Delay time fault SC«
• Specification of the ramp for the set power: Figure 1: Controlled shutdown of the genset with a »Fault SC«
Parameter »23007 Power control set ramp controlled shutdown«
In case that the value of the actual power is below 10 %, the genset is dese- 1.2.2 Function Alarm RP
lected. Ereignisse des Typs »Warnung RP« werden im Betriebstagebuch als »War-
Note nung« eingetragen. Additionallz, the admissible power is restricted to maximal-
ly 80 %. The power reduction is marked in the operation log by the alarm
If all faults of type »Fault SC« can be acknowledge in the operation log during
»Power reduction to safe power«.
the shut down process, the power is increased again to the externally demand-
ed power and the load run is continued.
Idle
If the genset is not operated in load run, every fault of type »Fault SC« causes
the immediate shutdown of the genset. With a pending »Fault SC« a start of
the genset or the idling operation are impossible.

© GW_620_2020_2.50.09_EN_CPU-P Page 5
TEM Evolution System

Notes

1.3 Abbreviations Abbreviations Explanation

Abbreviations Explanation NA Handling of mains fault

AES Demand of external starting preparations NATL Monitoring of the exhaust gas temperature after exhaust
turbocharger
AKR Anti-knock governor
NAWT Exhaust gas temperature after exhaust heat exchanger
AVW Preheating air inlet
NFI Lube oil pressure after filter
AWG Exhaust wastegate
NK Emergency cooling circuit
BY Exhaust bypass
NKS Emergency cooler - dry cooler
CH4 Additional CH4 compensation
NKV Valve position NK valve
CH4K Extension of option CH4.
NKAT Monitoring of the exhaust gas temperature after catalyst
DK Leakage check
NMOT Monitoring of the exhaust gas temperature after engine
GK Intercooler circuit
QEÜ Acknowledgement of external monitorings
GKS Intercooler-dry cooler
REC Registration of receiver pressure
GKV Valve position of the GK valve
RL Control of cabin air temperature
GL Monitoring of the generator bearing temperatures
RL1 Cabin ventilation with admixture or frequency-controlled
GLU Generator air temperature coolers
GW Generator winding temperatures SATL Measuring and limitation of the exgaust turbocharger
speed
HK Heat utilization with heating circuit
VAWT Measuring of the heating water temperature before
HKV Valve position HK valve
exhaust gas heat exchanger
MK Jacket water control
VBP Compressor bypass

© GW_620_2020_2.50.09_EN_CPU-P Page 6
TEM Evolution System

Notes

Abbreviations Explanation

VKWT Jacket water temperature before jacket water heat


exchanger

VNK Heating water temperature before emergency cooler

VSWT Measuring of jacket/heating water before lube oil


exchanger

xM Parameterisable messages

xMW Parameterisable data

xPR Parameterisable control circuits

ZG Dual gas operation with change of the gas type only at a


standstill

ZGM Dual gas operation with composite mode

ZM Dual gas operation with composite mode and change of


the gas type under load

ZU Dual gas operation with change of the gas type under load

© GW_620_2020_2.50.09_EN_CPU-P Page 7
TEM Evolution System

List of Limit Values

2 List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


T202 Jacket water GK inlet Fault SC 500 ms X [GK]
T206 Jacket water engine outlet Fault SC 500 ms X
Alarm 98.0 °C 2s
(208.4 °F)
Fault 99.0 °C 2s X
(210.2 °F)
Message 20.0 °C 240 min
(68 °F)
T207 Jacket water engine inlet Fault SC 500 ms X
Message 80.0 °C 5 min Power reduction; Limit value: Par.
(176 °F) 13400; island: delay 30s
Fault 98.0 °C 2s X
(208.4 °F)
Collective fault jacket water tempera-
tures Fault 0 ms T206 and T207 failed, automatically
acknowledgeable
P196 Lube oil before filter Fault SC 500 ms X
Alarm 3.00 bar 0 ms Operational oil pressure
Fault ¹ 0.30 bar 1 min Start prelubrication; delay during at
a standstill: 60s
Fault ¹ 2.80 bar 0 ms Operational oil pressure

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 8


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


T208 Lube oil Fault SC 500 ms
Alarm 105.0 °C 2s
(221 °F)
Fault SC 110.0 °C 2s
(230 °F)
L234 Lube oil level Fault SC 500 ms
L234.1 Lube oil level Filtered value
Message 95.0 % 0 ms Enable only during oil change
Fault ¹ 120.0 % 20 s 10 h With the engine at a standstill delay
1s
Message 50.0 % 0 ms Enable only during oil change
Fault ¹ 30.0 % 20 s 10 h With the engine at a standstill delay
1s
Xxxx Number of prelube faults
Alarm 0 0 ms 1. Prelube fault
Fault 5 0 ms
T201 Receiver Fault SC 500 ms X [GK]
Message 52.0 °C 5 min Power reduction; Limit value: Par.
(125.6 °F) 13800; island: delay 30s
Message 55.0 °C 2s Limit value: Par. 13800 + 3.0K
(131 °F)
Fault SC 57.0 °C 2s 10 h Limit value: Par. 13800 + 5.0K
(134.6 °F)

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 9


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


T203 Inlet air Alarm 500 ms
Message 30.0 °C 0 ms With [AVW] limit value: Par.
(86 °F) 23230/23231 + 3.0K
Alarm 35.0 °C 2 min [RL without T404]; Limit value Par.
(95 °F) 13900 - 5.0K
Fault SC 40.0 °C 2 min X [RL without T404]; Limit value Par.
(104 °F) 13900
Alarm 20.0 °C 30 s Enable after 1 h engine running;
(68 °F) Limit value Par. 23230 - 5.0K
T461 Combustion chamber A1 Fault SC 500 ms X For each cylinder individually
Fault 600 °C 6s 10 h
(1112 °F)
Alarm 240 °C 20 s Limit value 50K-120K below
(464 °F) average value
Fault SC 240 °C 2 min 10 h Limit value 50K-120K below
(464 °F) average value; island operation:
delay. 8 min; During this time the
power reduction is under the limit
value
T471 Combustion chamber B1 Fault SC 500 ms X For each cylinder individually
Fault 600 °C 6s 10 h
(1112 °F)
Alarm 240 °C 20 s Limit value 50K-120K below
(464 °F) average value
Fault SC 240 °C 2 min 10 h Limit value 50K-120K below
(464 °F) average value; island operation:
delay. 8 min; During this time the
power reduction is under the limit
value

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 10


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


T204 Cold junction A Fault SC 500 ms X
T205 Cold junction B Fault SC 500 ms X
T46x.7 Combustion chamber Average value side A
average Fault 450 °C 500 ms 10 h Limit value 100K (mains) / 160K
(842 °F) (island) above set value
T47x.7 Comb. chamber aver. B Average value side B
Fault 450 °C 500 ms 10 h Limit value 100K (mains) / 160K
(842 °F) (island) above set value
T4xx.2 Act. combustion chamber Filtered value
Fault 0 ms More than 2 sensors failed automat-
ically acknowledgeable
Fault 150 °C 0 ms
(302 °F)
Deviation comb. chamber control
Fault SC 10 °C (50 °F) 5 min 10 h With a higher deviation less delay
time
Fault SC -10 °C 5 min 10 h With a higher deviation less delay
(14 °F) time
Gas mixer limit stop lean
Message 4s Stop position not reached
Gas mixer start position OK
Message 0 ms Stop position not reached
Alarm 0 ms Start position not reached on start
abort
T494 Exhaust after ATL A Alarm 500 ms [NATL]
Alarm 550 °C 15 min Limit value: Par. 15111 / 15113
(1022 °F)

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 11


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


T495 Exhaust after ATL B Alarm 500 ms [NATL]
Alarm 550 °C 15 min Limit value: Par. 15111 / 15113
(1022 °F)
T286 Exh. after engine Alarm 500 ms [NMOT]
Alarm 550 °C 2s Limit value: Par. 15111 / 15113
(1022 °F)
T287 Exhaust after KAT Fault SC 500 ms [NKAT]
Fault 550 °C 2s Limit value: Par. 15111 / 15113
(1022 °F)
T288 Exhaust after AWT Alarm 500 ms [NAWT]
Alarm 180 °C 2s Limit value: Par. 15112
(356 °F)
P157 Exhaust back press. too high Limit value switch
Alarm 50 mbar 2 min
Anti-knock governor available [AKR]
Alarm RP 0 ms AKR-card missing
AKR Speed signal [AKR] Error speed signal
Alarm RP 5s Enable during load run
ZA maximum adjustment ignition [AKR] Sturdy ignition p. adjustment
point A side Alarm 0 ms Sturdy ignition p. adjustment; Limit
value: Par. 115036.0°; bit-coded
display
ZA maximum adjustment ignition [AKR] Sturdy ignition p. adjustment
point B side Alarm 0 ms Sturdy ignition p. adjustment; Limit
value: Par. 115036.0°; bit-coded
display

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 12


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


Critical fault! Engine test required! [AKR] Maximum ZZP-adjustment
Fault ¹ -9.0 ° 0 ms Limit value: Par. 11502 - 1.0 °; at
least -3.0 °
AKR Knock sensor fault bank A [AKR]
Alarm RP 10 s
AKR Knock sensor fault bank B [AKR]
Alarm RP 10 s
AKR Function block [AKR]
Alarm RP 0 ms
ZA Cabling of ignition coil bank A Cabling of ignition coil
Message 0 ms
Alarm 1 min
ZA Cabling of ignition coil bank B Cabling of ignition coil
Message 0 ms
Alarm 1 min
Ignition system ignites Feedback from ZA
Fault 3s 10 h Ignition does not ignite
Ignition system error code Fault message from ZA
Alarm 0 ms
Fault 3s 10 h
Ign. system capacitor discharge bank Error capacitor discharge
A Message 0 ms
Alarm 1 min
Ign. system capacitor discharge bank Error capacitor discharge
B Message 0 ms
Alarm 1 min

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 13


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


Ign. system condition serial Timeout ZA communication
connection S Fault SC 3s
Ign. system condition serial Error ign. system communication
connection W Message 0 ms
P145 Crank case Fault 0 ms
Fault ¹ 10.0 mbar 0 ms After start-up phase; limit value at
rated speed 1800 rpm: 20.0 mbar
Alarm -10.0 mbar 5 min with engine running
xxxx Number of start attempts
Fault 3 0 ms 10 h
S200 Engine speed
Alarm 1725.0 rpm 0 ms Limit value: Par. 11108 + 15% (or
+20%), w. auto acknowledgement
Alarm 80.0 rpm 0 ms Speed bef. start
Fault ¹ 1725.0 rpm 200 ms Limit value: Par. 11108 + 15% (or
+20%)
Fault 1350.0 rpm 500 ms 10 h Limit value depending on condition
S110 Set value speed Fault 500 ms X only with analogue specification of
the set speed
G197.1 Throttle valve position Fault 500 ms Feedback voltage; sensor
monitoring: Current voltage is <
1.00 V or > 3.30 V. actual value 4.00
V: Line V- interrupted; Actual value
< 1.00 V: Line V- interrupted;
otherw.: line V+, V- or P interrupted
G197.Throttle valve position Fault 0 ms Position StG; sensor monitoring:
Current position is < -30.0 % or >
130.0 %

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 14


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


DZR Current derating
Alarm 5s Enable during load run
DZR Short circuit power stage
Fault 0 ms
DZR TDC sensor error TDC signal missing
Fault 2s 10 h Enable with the engine running
Alarm 0 ms Enable with the engine running,
auto acknowledgement
DZR Tooth number fault
Fault 2s 10 h Enable with the engine running
Alarm 0 ms Enable with the engine running,
auto acknowledgement
DZR TDC mixed up with gear ring
Fault 2s 10 h
Alarm 0 ms
E198 Actual power generator Fault 500 ms X
E198.2 Actual power Filtered value
Fault SC 105.0 % 2 min Overload; Limit value: Par. 13100 +
5%
Fault 120.0 % 5s Overload
Fault -5.0 % 12 s X Reverse power; delay Par. 13510
E198.8 Actual power in KW
Alarm 410 kW 45 min Minimum load; V12: 305kW, V16:
410kW
Fault 410 kW 60 min X Minimum load; V12: 305kW, V16:
410kW

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 15


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


Deviation power control
Fault SC 5.0 % 5 min During start and retrace of the
engine: limit value 20%
Alarm -5.0 % 5s Exceeding the admissible power in
island operation
Fault -5.0 % 30 s Exceeding the admissible power in
island operation
Fault SC -5.0 % 5 min
Power reduction due to jacket water
temperature Message 0.0 % 0 ms Enable with message T207
Power reduction due to receiver [GK]
temperature Message 0.0 % 0 ms Enable with message T201/T378
Power reduction due to throttle
Message 0.0 % 2 min island: delay 30s
Fault -40.0 % 0 ms
Power reduction due to CH4-value [CH4]
Message 0.0 % 0 ms Enable with message Q311
Power reduction due to AKR [AKR]
Message 0.0 % 2 min island: delay 30s
Alarm 0.0 % 2 min island: Delay. 30s, auto. acknowl-
edgeable, indicator of incorrect
parameterisation Par. 11502
Power reduction due to ATL speed [SATL]
Message 0.0 % 2 min island: delay 30s

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 16


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


T209 Generator winding U Fault SC 500 ms [GK]
Alarm 135.0 °C 10 s Limit value: Par. 13500 - 5.0K
(275 °F)
Fault ¹ 140.0 °C 10 s Limit value: Par. 13500
(284 °F)
T210 Generator winding V Fault SC 500 ms [GK]
Alarm 135.0 °C 10 s Limit value: Par. 13500 - 5.0K
(275 °F)
Fault ¹ 140.0 °C 10 s Limit value: Par. 13500
(284 °F)
T211 Generator winding W Fault SC 500 ms [GK]
Alarm 135.0 °C 10 s Limit value: Par. 13500 - 5.0K
(275 °F)
Fault ¹ 140.0 °C 10 s Limit value: Par. 13500
(284 °F)
T459 Generator bearing A Fault SC 500 ms [GL]
Alarm 55.0 °C 2s Limit value: Par. 13501 - 5.0K
(131 °F)
Fault ¹ 60.0 °C 2s Limit value: Par. 13501
(140 °F)
T460 Generator bearing B Fault SC 500 ms [GL]
Alarm 55.0 °C 2s Limit value: Par. 13501 - 5.0K
(131 °F)
Fault ¹ 60.0 °C 2s Limit value: Par. 13501
( 140 °F)

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 17


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


T487 Generator air inlet Fault SC 500 ms [GLU]
Alarm 75.0 °C 2s Limit value: Par. 13030 - 5.0K
(167 °F)
Fault 80.0 °C 2s Limit value: Par. 13030
(176 °F)
T488 Generator air outlet Fault SC 500 ms [GLU]
Alarm 75.0 °C 2s Limit value: Par. 13030 - 5.0K
(167 °F)
Fault 80.0 °C 2s Limit value: Par. 13030
(176 °F)
E121 Generator protection Input security chain
Fault 0 ms X
Synchronisation
Fault 10 min X Timeout synchronization
E104 mains fault [NA]
Fault 30 s
Alarm 0 ms
Mains fault sequencial failure [NA]
Fault 0 ms
E199 Analogous demand Alarm 500 ms only with demand 4..20mA,
deselection in case of a sensor
alarm
E199.7 demand active
Message 30.0 % 0 ms
T291 Heating water flow Fault SC 500 ms [HK] Enable with Par. 14008

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 18


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


T289 Heating water return Alarm 500 ms [HK] Enable with Par. 14009
Message 80.0 °C (176 10 s [NK]; Limit value: Par. 24510
°F)
T290 Heating water before KWT Alarm 500 ms [VKWT]
T385 Heating water before AWT Alarm 500 ms [VAWT]
T386 Heating water before SWT Alarm 500 ms [VSWT]
P281 Heating circuit pump [HK]
Fault 0 ms X
S397 HK Control valve position Alarm 500 ms [HKV]
T276 Overtemperature limiter 1 [HK] Input security chain
Fault 0 ms X
T277 Safety temperature monitor [HK] Input security chain
Fault 0 ms X
P278 Overpressure limiter [HK] Input security chain
Fault 0 ms X
P279 Overpressure limiter 1 [HK] Input security chain
Fault 0 ms X
L280 Low water heating circuit [HK] Input security chain
Fault 0 ms X
P457 Pump coupling circuit [HK] Input security chain
Fault 0 ms X
T435 Overtemperature limiter 2 [HK] Input security chain
Fault 0 ms X
P437 Overpressure limiter 2 [HK] Input security chain
Fault 0 ms X

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 19


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


Exhaust bypass AWT limit stop [HK+BY]
Closed Message 500 ms
P126 Flow monitoring engine cooling
circuit Fault 0 ms X
L123 Low water engine cooling circuit Input security chain
Fault 0 ms X
T419 Emergency cooler-dry cooler- Alarm 500 ms [NKS] Enable with Par. 14055
outlet
S000 NK Control valve position Alarm 500 ms [NKV] position feedback
P309 Flow monitoring intercooler [GK]
circuit Fault SC 3s X
L308 Low water intercooler circuit [GK] Input security chain
Fault 0 ms X
S000 Intercooler-control valve Alarm 500 ms [GKV] Position feedback
position
T405 Intercooler-dry cooler outlet Alarm 500 ms [GKS] Enable with Par. 13085
T404 Cabin air Alarm 500 ms [RL1x] Enable with Par. 13092
Message 32.0 °C 2s Limit value: Par. 13900 - 8.0K
(89.6 °F)
Alarm 35.0 °C 2s Limit value: Par. 13900 - 5.0K
(95 °F)
Fault SC 40.0 °C 2s X Limit value: Par. 13900
(104 °F)
Cabin ventilation [RL]
Fault SC 3s X delay during start 60s

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 20


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


P124 Gas pressure gas control
system Fault 0 ms X [CH4] Auto acknowledgement (Par.
12900)
P125 Leakage check gas control [DK]
system A Fault 1 min Timeout leakage check
T147 Temperature monitor gas
control system Fault 0 ms
P127 Gas pressure gas control [ZG ZGM]
system B Fault 0 ms X [CH4] Auto acknowledgement (Par.
12900)
P128 Leakage check gas control [ZG+DK]
system B Fault 1 min Timeout leakage check
T131 Temperature monitor gas [ZG]
control system B Fault 0 ms
Q311 CH4-value Fault SC 2s [CH4]
Message 0.0 % 30 s Deselection; enabling/limit value:
Par. 12810, Par. 12811
Message 30.0 % 0 ms [ZGM] Gas type change; Limit
value: Par. 12806 - 8.0%
Message 38.0 % 0 ms Limit value: Par. 12806
Message 50.0 % 5 min Power reduction; Limit value: Par.
12803; island: delay 30s
Fault SC 38.0 % 5 min X Limit value: Par. 12806
Stop due to CH4 calibration [CH4K]
Fault SC 75 min X Timeout calibration, manual
Alarm 75 min Timeout calibration, auto

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 21


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


G602.0 Throttle valve gas type A Alarm 500 ms X [ZGM]
actual
G602.6 Control deviation throttle [ZGM]
valve gas type A Alarm 10.0 % 5s delay during the start and engine
running 50 x Par. 12522, otherwise
600 x Par. 12522
Alarm -10.0 % 5s delay during the start and engine
running 50 x Par. 12522, otherwise
600 x Par. 12522
G603.0 Throttle valve gas type B Alarm 500 ms X [ZGM]
actual
G603.6 Control deviation throttle [ZGM]
valve gas type B Alarm 10.0 % 5s delay during the start and engine
running 50 x Par. 12522, otherwise
600 x Par. 12522
Alarm -10.0 % 5s delay during the start and engine
running 50 x Par. 12522, otherwise
600 x Par. 12522
E149 Voltage supply
Alarm 30.0 V 0 ms
Alarm 20.0 V 0 ms
Exxx Earth leakage monitor switching
cabinet Alarm 10 kOhm 5s
Voltage back-up battery
Alarm 3.30 V 1 min
Alarm 2.00 V 1 min
H141 Internal quick stop Input security chain
Fault 0 ms

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 22


TEM Evolution System

List of Limit Values

Identification Sensor monitoring RA Monitoring Limit value Delay RA Level Comment


H117 Ext. quick stop without heat Input security chain
removal Fault 0 ms
H116 Ext. quick stop with heat Input security chain
removal Fault 0 ms X
Security chain Security chain open
Fault 0 ms X
G143 Circuit breaker TEM swtiching
cabinet Fault 0 ms
Parameterisable message 01 [xM] Par. message; free text
Message 0 ms X Limit value, delay, type, enabling
parameterisable
Parameterisable measured value 01 Alarm 500 ms [xMW] Par. measured value; free
text
Message 0 0 ms X Limit value, delay, type, enabling
parameterisable
Message 0 0 ms X Limit value, delay, type, enabling
parameterisable
Control deviation parameterisable [xPR] control deviation par.
controllers 1 governor; XX=1..3
Message 10 0 ms X Limit value, delay, type, enabling
parameterisable
H108.2 ZGM analogue external Alarm 500 ms X [ZGM]
demand gas type B

¹ Monitoring must be acknowledged individually © GW_620_2020_2.50.09_EN_CPU-P Page 23