Pressure Regulator

WMR / NL
< For residential application Applications Description
< Compact angle design The WMR regulator is designed for The WMR regulator is a spring-loaded self
residential applications from low pressure operated meter regulator including an
< High capacity
service lines. excess flow protection which closes in case
< Ready for connection to gas meter It can be mounted directly to the meter inlet of high flow or low inlet pressure. It reverts
< Under-pressure cut-off pipe. Its compact angle design makes it automatically to open position when
specially adequate for installation in space conditions are back to normal. It is fitted an
saving meter boxes or in meter bars. inlet strainer.
It is fully preset from factory and ready to
be fitted on gas meter. All adjustments
screws are sealed and protected against
unauthorised use.

Technical features
Maximum inlet pressure 400 mbar
Outlet pressure 15 - 35 mbar
Accuracy and lockup pressure Up to AC 10 / up to SG 20
Operating temperature - 20°C to + 60°C
Acceptable gases Natural gas, propane, butane, air, nitrogen
Safety devices Gas loss protection

Sizes & Connections


Size DN 20
Connection Angle
Internal thread ISO 7 - Rp 3/4

Materials
Body Die cast aluminium with epoxy coating
Actuator Steel with epoxy coating
Seals Nitrile
Diaphragms Nitrile

Option designations
Indoors installation • WMR standard regulator
• WMR (G) regulator wih gas loss protection
• WMG gas loss protection valve
Outdoors installation • NL 25 regulator with gas loss protection
• NL 35 gas loss protection valve
Pressure Regulator WMR
Operating Principle
The pressure reduction takes place between Safety
seat and valve disc (1). The valve disc The safety plug (7) closes when outlet
position is controlled by the diaphragm (2) pressure drops, in the event of excessive
which senses, through the tube (3), the flow, i.e. (by high gas demand or broken
outlet pressure on one side and is loaded by outlet piping), or in case of low inlet pressure
the spring (4) on the other side. Spring load : this is the gas loss protection. Hovewer the
is adjustable by the nut (5). The cap (6) can valve plug design allows a limited gas flow (to
be sealed to avoid unauthorized intervention. creep to outlet pipe. In case of restored inlet
pressure and no gas demand, the outlet
The force on the valve disc (1) arising from
pressure builds up so as to re-open the
pressure differential is balanced by equivalent
safety plug without manual reset.
force from pressure differential on the
balancing diaphragm (7). A strainer - 100 µm - protects the
regulator on the inlet side.

WMR (G) Sectional View

2
Typical Performance Curve (24 mbar set point)
28

27

26
Outlet pressure - mbar

25

24

23 200 mbar

22
25 mbar
21
400 mbar
20

19

18
0 1 2 3 4 5 6 7
3
Rate of flow - m /h in standard conditions
Standard conditions:
0.6 SP.GR.GAS • Absolute pressure of 1.013 bar
• Temperature of 15°C

Gas Loss Protection Correction factor for


Switches at around 10 to 15 mbar.. non-natural gas applications:
The flow rates are indicated or a 0.6
specific gravity gas.
Flow Capacity
To determine the volumetric flow rate
WMR set at 25 mbar - models with and without gas loss protection for gases other than natural gas, the
Inlet Pressure Capacities (m3/h) in standard conditions values in the capacity tables should be
35 mbar 12 multiplied or calculated using the sizing
200 mbar 12
equations with a correction factor.
The table below lists the correction
factors for some common gases:
Gas type Specific Correction
gravity factor
Air 1.00 0.77
Butane 2.01 0.55
Carbon dioxide (dry) 1.52 0.63
Carbon monoxide (dry) 0.97 0.79
Natural gas 0.60 1.00
Nitrogen 0.97 0.79
Propane 1.53 0.63
Propane-Air mix 1.20 0.71

Specific gravity or relative density


(air = 1, non-dimensional value)
To calculate the correction factor for
gases not listed above, the specific
gravity (d) of the gas should be taken
and used in the following formula:

0.6
Correction factor =
d

3
Overall Dimensions & Fittings
Various options are available for inlet and the outlet connecions as shown in the table below.
Other possibilities can be provided on request..

Type Inlet connection Outlet connection A (mm) B (mm)


W-3/4 Rp 3/4 Gas meter union G 7/8 70 136
W-1 Rp 3/4 Gas meter union G 1 70 136
K-3/4 Rp 3/4 External thread R 3/4 75 141
B-3/4 Rp 3/4 Internal Rp 3/4 53 119

<Pressure Regulator WMR/NL


<Pressure Regulator WMR/NL
Ø 96

GA-0046.1-GB-01.04 - © Copyright 2004, Actaris, All Rights Reserved. - Actaris reserves the right to change these specifications without prior notice.
66

A
<Pressure Regulator WMR/(G)

53

Installation Information to be specified when


Gas must flow through the valve body in the
. ordering:
same direction as the arrow cast on the body.
• Regulator type code
The WMR regulator is usually installed
• Minimum and maximum inlet
directly on the inlet hub of a gas meter.
pressures
• Outlet presure range
• Outlet pressure setting
• Connection type
<Pressure Regulator WMR

Actaris Gaszählerbau GmbH


Hardeckstrasse 2
D-76185 Karlsruhe - Germany tel + 49-721 5981 0
For more information, www.actaris.com fax + 49-721 5981 189