Description Modulating valves LMV are used in combustion processes that require linear adjustment of air
or gas flow. The flow varies proportionally to the opening angle of inner orifice, therefore
flowrate is very predictable. The valve can be operated with stage control (3-point, MZ3
servomotor) or with continuous modulation (analogue signals, MZ5 servomotor)..

Features Valve housing is made of aluminum alloy with connections from 3/4” to 3”.

Suitable for use with air and non-aggressive gases included in the 1st, 2nd and 3rd families (EN
437). Special versions for aggressive gases (Biogas or COG).
Linear ratio of opening angle to flow rate.
Working ratio till 25:1, low pressure drop and limited gas leakage when mechanism is in
minimum position.
Full gas orifice and reduced gas orifice are available for each size, to meet specific plant
requirements.
Maximum flow can be easily regulated.
Metal mesh in the inlet prevents contamination of the inner mechanism.

On request, an adjustable bypass can be installed to set up precisely the flow rate in minimum
position.
Suitable to be driven by servomotors MZ3 and MZ5.
Combined system LMV + MZ is designed to reduce overall dimensions.
MZ servomotors can be supplied in Ex-proof version, suitable for installation in Zone 2 and 22,
according to Directive 2014/34/UE (ATEX). Please refer to MZ tech data for further details.
All components are designed to withstand any mechanical, chemical and thermal condition
occurring during typical service. Effective impregnation and surface treatments have been used
to improve mechanical sturdiness, sealing and resistance to corrosion of the components.
Valves are 100% tested and fully warranted.

2-10
ELEKTROGAS – Scheda tecnica EE185 - 0322

Functioning and
application
LMV works by means of a double cylinder mechanism, allowing a linear variation of the flow
according to position, thanks to specifically shaped gas orifices. Outer cylinder is fixed while
inner cylinder can be rotated by the actuator, opening or closing the gas passage. Maximum
flow can be adjusted easily to set up the optimal working condition of the valve. Materials and
mechanical tolerances are designed to assure low leakage, repeatability of the performance
and reliability.

Flow restricting Flow modulating


cylinder cylinder
(fixed) (rotating)

Fig.1

Fig. 2 shows an example of installation with other Elektrogas devices.

VMM
automatic valve RAG
Air-gas
ratio
controller

VSG
Ball valve
FG
filter

LMV linear valve


MZ servomotor

Fig. 2

3-10
ELEKTROGAS – Scheda tecnica EE185 - 0322

Technical
specifications

Tab. 1

Connections Threaded f/f ISO 7-1 from Rp3/4 to Rp2½


Flanged PN16 ISO 7005 DN40 to DN80
On request:
ANSI-ASME B1.20 from 3/4”NPT to 2”½NPT
ANSI-ASA-ASME B16.5 class 150 from 2” to 3”

Control ratio 25:1

Ambient temperature -15°C... +60°C

Max working pressure 500 mbar (50 kPa)

Flow capacity See flow charts or tab. 2 - coefficient Kv


Complete opening

Leakage rate < 2% of Kv


Valve closed

Filtering element 600 µm

Materials in contact Aluminum alloy


with gas Brass
Stainless steel
Plated steel
Anaerobic adhesive
Nitrile rubber (NBR)
Fluoro elastomer (FPM)
Acetal resin (POM)

Voltage rate 230 VAC 50/60 Hz


Servomotor MZ 110 VAC 50/60 Hz
24 VAC/DC
(depending on servomotor type)

90° opening / closing time 7,5…60 sec (depending on servomotor type)

4-10
ELEKTROGAS – Scheda tecnica EE185 - 0322

Fig.3
Tab. 2

Overall dimensions [mm] Flow capacity Kv [m3/h]


Reduced Micro
Full
Conn. A B C(1) D Int h orifice orifice
orifice
(LMV..1..) (LMV..2..)
Rp 3/4 88 96 200 34 - - 8.06 4.35 1.58

Rp 1 88 96 200 34 - - 8.06 4.35 1.58

Rp 1¼ 120 153 235 43 - - 23.5 14.0 -

Rp 1½ 120 153 235 43 - - 23.5 14.0 -

Rp 2 106 156 240 47 - - 23.5 14.0 -

Rp 2½ 179 218 261 55 - - 56.6 28.5 -

DN 40 163 196 240 75 110 4x18 23.5 14.0 -

DN 50 163 196 240 75 125 4x18 23.5 14.0 -

DN 65 180 305 275 89.5 145 4x18 56.6 28.5 -

DN 80 180 305 275 89.5 160 8x18 56.6 28.5 -

(1) when a lever joint is installed (LMV..L), add 28mm

5-10
ELEKTROGAS – Scheda tecnica EE185 - 0322

Gas Flow Chart

Fig.4

Fig.5

6-10
ELEKTROGAS – Scheda tecnica EE185 - 0322

Fig.6

Valve selection: for optimal flow control, it is advisable to have a pressure drop p
between 20 and 30% of the inlet pressure p1.

Example:
Select a valve for natural gas flow
Qn= 40 Nm3/h and a pressure p2
= 70 mbar.
With p equal to 30% of P1:
 0.3 
p =   p 2 = 30 mbar
1 − 0.3 

From the gas flow charts of LMV


valves, the size that can
guarantee the required flow rate is
the 3/4 "-1" with full passage,
because the working point is
between MAX and MIN position of
flow regulation.

Fig. 7

7-10
ELEKTROGAS – Scheda tecnica EE185 - 0322

Tab. 3

Actuator connection:

LMV.. LMV..C LMV..L LMV..R


Without joint compact joint joint with lever: valve is Lever for remote actuator:
actuated by servomotor valve is actuated by a
8 square shaft
above and a second valve servomotor installed in
can be controlled by lever another position by lever
and angular joints (DIN and angular joints (DIN
71802 – not provided) 71802 – not provided)

Example of LMV..C+MZ:

Fig. 8

8-10
ELEKTROGAS – Scheda tecnica EE185 - 0322

Order Information Tab. 4

LMV 3 1 M C
Model Tab. 3
LMV Linear valve (actuator not included)
Connection
2 3/4"
3 1"
35 1" 1/4
4 1" 1/2
6 2"
7T 2” 1/2
4F DN40
6F DN50
7 DN65
8 DN80
Variants
_ Rp internal thread / ISO flange
N NPT thread / ANSI flange (on request)
Gas orifice
_ Full gas orifice
1 Reduced gas orifice
2 Micro gas orifice (only ¾”-1”)
Pressure test points and bypass
_ Pressure test point at the inlet
A Additional pressure points at the outlet (only 1”¼-2”)
M Adjustable bypass (only 3/4”-2”)
Actuator connection
_ without joint (8 square shaft)
C compact joint (standard)
L joint with lever
R joint with special lever to connect remote actuators or manual lever
Special version
J Biogas

When LMV is coupled to a servomotor, complete product code adding model of servomotor (see MZ tech sheets).

Special versions and options


▪ Adjustable by-pass suitable for setting up a very low minimum flow rate, only for ¾”-2”.
▪ Joint with lever to connect multiple LMV to the same servomotor (Notice: C dimension
must be increased of 28 mm).
▪ Joint to connect remote actuator.
▪ Test points G1/4 at the outlet: on request for models 1”¼-1”½-2”, always present in valves
2”½-3”.
▪ Special versions for aggressive gas (J version), manufactured without brass and with
special sealing.

Elettromeccanica Delta Spa reserves the right to update or make any technical changes without
prior notice.

9-10
ELEKTROGAS – Scheda tecnica EE185 - 0322

Design,
installation
and servicing To assure a proper and safe operation, as well as a long service life of the valve, consider the
following recommendations during the design of the system where the valve will be installed:

✓ Ensure that all the features of your system comply with the specifications of the valve (gas
type, operating pressure, flow rate, ambient temperature, electrical voltage, etc.).
✓ Valve may be mounted with actuator in horizontal or vertical position, not upside down.
✓ In the event of vertical pipe, the flow direction should be from bottom to top.
✓ After removing the end caps make sure no foreign body will enter into the valve during
handling or installation (e.g. swarf or excessive sealing agent).
✓ A gas filter should be always installed upstream the valve.
✓ Gas transiting through the valve must be clean and dry.
✓ Ensure that installing area is protected from rain and water splashes or drops.
✓ Perform leak and functional tests after mounting (max pressure test 1,5 Pmax).
✓ Never install the valve close to walls or other equipment. To improve actuator cooling,
install the valve allowing free air circulation.
✓ Perform maintenance according to service instructions at least once a year (most often for
aggressive gases).
✓ Due to seals aging, to ensure safe operation, we recommend valve replacement after 10
years from the date of manufacture stamped on the product. Frequent cycle operation may
reduce the expected lifetime.
✓ This control must be installed in compliance with the rules in force.
✓ Make sure all works are performed by qualified technicians only and in compliance with
local and national codes.
✓ To prevent product damage and dangerous situations, read carefully the instructions
supplied with the product before use.

Standards and
approvals LMV valves are designed according to EN13611.

Quality Management System is certified according to UNI EN


ISO 9001 and the monitoring is carried out by the notified body
Kiwa Cermet Italia S.p.a.

Elektrogas® is a brand name of

Elettromeccanica Delta S.p.A.


Via Trieste 132
31030 Arcade (TV) - ITALY
tel +39 0422 874068
fax +39 0422 874048
www.delta-elektrogas.com Copyright © 2022
info@delta-elektrogas.com All rights reserved

10-10

You might also like