CALCULATION NOTE Date 10/11/10
Revision
Originator KBT
RO SIZING Checked by CSH
Approved by
2 CALCULATION OBJECTIVE
3 i. To estimate flowrate through RO, which is used for manual depressuring purpose.
4
15 The flow through RO will be based on upstream pressure up to design pressure of 113 barg at operating temperature of 27ºC (to be more
16 conservative) by ensuring the Mach Number of gas flow in piping downstream of RO is not exceeding 0.75 at 0 barg backpressure.
17
18 iii. Piping size of 2" and 3" are selected for the studies.
19 iv. Technip In-house spreadsheet, Calligne (Attachment -1 ) will be used to estimate the allowable flowrate to fulfill the criteria as mentioned above.
20 v. Technip In-house spreadsheet, RO sizing (Attachment -2 ) will be used to calculate the required orifice diameter. The calculated orifice diameter
21 shall be at least 5mm to avoid plugging. If the calculated orifice diameter is less than 5mm, a minimum 5mm orifice diameter will be selected to
22 estimate the flowrate through the RO. Piping size downstream of RO will be recalculated base on the new flowrate.
23
24
25 SUMMARY / RESULTS
26
42
43 ATTACHMENT
44 i. Calligne_v2.4
45 ii. Orifice_V1.3
46