Professional Documents
Culture Documents
Iec 909 Short Circuit Analysis PDF
Iec 909 Short Circuit Analysis PDF
This tutorial exercise will serve as a validation and verification test for the EDSA IEC 909 short circuit
program. The tutorial will be based on two examples documented in the IEC 909 “Short circuit current
calculation in three-phase AC systems”. These examples are:
Each example will first be solved by longhand calculations, and then the corresponding pre-created EDSA
file will be used to re-calculate the short circuit results. Once both analyses have been completed, a table of
comparison will be presented. It is assumed, for this exercise, that the user is familiar with building EDSA
job files using the ECAD interface. If not, please refer to sections 1.0 and 2.0 of the EDSA User’s Guide to
review the process. The program options used in this tutorial are as follows:
250 MVA
(cq = 1.1) 0.00438 + j0.04378
X/R = 10
15 kV 15 kV
F1 F1
C4 1.1575 + j0.92813
18.52 + j14.85
F3 F3
Page 1
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
Figure 1 shows the system under study for the IEC example 1. The diagram shown in this figure is given,
both in ohms and per unit. The calculation, however, will be done in per unit.
Original data for the example had the following cable info.
C1 – 2-240mm2, 10 meter length and 0.077 + j 0.079 ohms/meter/ph = 0.77 + j 0.79 milliohms.
C2 – 2-150mm2, 4 meter length and 0.208 + j 0.068 ohms/meter/ph = 0.832 + j 0.272 milliohms.
C3 – 2-70mm2, 20 meter length and 0.271 + j 0.087 ohms/meter/ph = 5.420 + j 1.740 milliohms.
C4 – 2-50mm2, 50 meter length and 0.3704+ j 0.297 ohms/meter/ph = 18.52 + j 14.85 milliohms.
Utility source - The source is <35 kV, therefore the X/R = 10 per IEC-60909 (X = 0.995*Z, R = 0.1 X).
Cables are converted from ohms to per-unit on 10 MVA and 0.4-kV bases
Page 2
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
Fault at F1, the impedance network is reduced by having the impedance of T1 in parallel with sum of the
impedances of T2 +C2 +C1.
C1 = 0.02406 + j0.02469 PU
C2 = 0.02600 + j0.00850 PU
T2 = 0.28750 + j0.95750
Sum 0.33756 + j0.99069 = 1.04662 @71.184 deg
To determine the circuit X/R ratio to be used to determine the peak current all reactances are multiplied
0.40 and the system then reduced. The new per-unit impedances are:
C1 = 0.02406 + j0.00988 PU
C2 = 0.02600 + j0.00340 PU
T2 = 0.28750 + j0.38300
Sum 0.33756 + j0.39628 = 0.52056 @49.5749 deg
X/RADJ = 2.5 * (X/R0.4) = 2.5*1.4693 = 3.67. This compares with X/R = 3.64 for the 50 Hz system.
The X/R = 3.67 is used to calculate the peak current from iPEAK = √2 I”k (1.02 + 0.98 e-3(R/X)).
Page 3
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
Fault at F2, the impedance network is reduced by having the impedance of T1 and C1 in parallel with the
impedances of T2 +C2.
C1 = 0.02406 + j0.02469 PU
T1 = 0.16375 + j0.24550 PU
Sum 0.18781 + j0.27019 = 0.32905@55.197 deg
C2 = 0.02600 + j0.00340 PU
T2 = 0.28750 + j0.38300PU
Sum 0.31350 + j0.38640 = 0.49758 @50.946 deg
C1 = 0.02406 + j0.00988 PU
T1 = 0.16375 + j0.24550PU
Sum 0.18781 + j0.25538 = 0.31700 @53.6669 deg
C2 = 0.02600 + j0.0034 PU
T2 = 0.28750 + j0.38300
Sum 0.31350 + j0.38640 = 0.49758 @50.9464 deg
X/RADJ = 2.5 * (X/R0.4) = 2.5*1.4049 = 3.5123. This compares with X/R = 3.508 for the 50 Hz system.
The X/R = 3.51 is used to calculate the peak current from iPEAK = √2 I”k (1.02 + 0.98 e-3(R/X)).
Fault at F3, the impedance network was reduced for fault F2 to the common point. Cables C3 and C4 are
added to that impedance.
Page 4
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
X/RADJ = 2.5 * (X/R0.4) = 2.5*0.3622 = 0.9055. This compares with X/R = 0.9053 for the 50 Hz
system.
The X/R = 0.9055 is used to calculate the peak current from iPEAK = √2 I”k (1.02 + 0.98 e-3(R/X)).
Step 1.
Select “File”.
Step 2.
Select “Open”.
Step 3.
Select “IEC1.EDS”.
Step 4.
Select “Open”.
3.1 Invoke the ECAD interface, and proceed to load the pre-formatted file for IEC example 1. The
file is called “IEC1.eds”, and it can be loaded according to the procedure shown in the above
screen capture.
Page 5
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
Step 1.
Click here to invoke
the Short Circuit
program.
3.2 Next, proceed to invoke the short circuit program, as indicated in the above screen capture.
Page 6
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
Step 6
Select “OK”.
Step 1
Select the
“Options” icon.
Step 2
Fill out the
“Options” screen
exactly as indicated
here.
Step 3
Select “IEC”.
Step 4 Step 5
Fill out the “IEC 909 Select “OK”.
Calculation Control”
screen exactly as
indicated here.
3.3 Once the Short Circuit interface appears, proceed to specify the required short circuit components,
the calculation methodology, and the specific IEC calculation controls. Follow the methodology
outlined in the screen-capture shown above.
Page 7
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
Step 1
Select “Update
Answer File”
Step 2 Step 3
Select “Faults Select “OK”.
at all busses”
3.4 Finally, run the analysis by following the procedure shown in the screen-capture above.
Page 8
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
3.5 The IEC 909 report, showing the selected sections, is now presented in the output screen. At this
point, the report can be printed out, copied to the clipboard or saved as a text file for third party
software customisation. To exit, select “Done” from the menu.
Page 9
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
The following table shows a comparison between the results obtained using longhand calculations, EDSA
and the results documented in the IEC 909 standard.
All variances with Hand Calculations and IEC 909 documents are attributed to round off on input data or
results.
7 5 0 M VA
( c q = 1 .1 ) 0 .0 0 1 4 6 + j0.0 1 4 5 9
X/R = 1 0
33 kV 33 kV
C1 C2 C1 C2
0 .4 8 5 + j 0.4 8 5 o h m 0 .4 8 5 + j 0 .4 8 5 o h m 0.0 0 4 4 5 + j0 .0 0 4 4 5 0.00445 + j0.00445
T1 T2 T1 T2
1 5 M VA 15 MVA 0 .0 0 4 0 + j0.0 9 9 9 0 .0 0 4 0 + j0 .0 9 9 9
3 3 /6 .3 k V 1 5% 3 3 /6 .3 k V 1 5 %
X/R = 2 5 X/R = 2 5
Un = 6 kV F1 6 kV F1
M1 M2 M3 M4 M1 M2 M3 M4
M1 M2, M3, M4 M1 M2, M3, M4
5 MW , UM = 6 k V 1 MW , UM = 6k V 0.0374 + j 0.3742 1st Cy (IEC) 0.1920 + j1.9200 1st Cy (IEC)
p f= 0 .8 6 , e ff = 0 .9 7 p f= 0 .8 3 , e ff = 0 .9 4 0.0489 + j 0.4891 Int (IEC) 0.2001 + j2.0006 Int (IEC)
I L R/ I M= 4 , 4 p o le I L R/ I M= 5 .5 , 2 p o le
X/R = 1 0 X/R = 1 0
Page 10
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
Figure 2 shows the system under study for the IEC example 2. The diagram shown in this figure is given
both, in ohms and per unit. The calculation, however, will be done in per unit.
The following table shows the data that corresponds to the motors.
The standard provides both curves and equations to determine the currents from motors at breaking time.
The interrupting time impedances are determined by using the factors : and q. Factor : accounts currents in
both synchronous and asynchronous (induction motors) decaying from substransient to transient
Page 11
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
impedance. Factor q is a second correction for asynchronous machines that accounts for different decay
rates based on the motor size. The IEC example used 0.10 seconds for the breaking time.
Motor M1, has 4 times inrush current at rated voltage. The inrush current is adjusted by the voltage factor
‘c’ and is 4*1.1 = 4.4 and the motor has 2.5 MW per pole. Motors M2, M3, and M4 have 5.5 * 1.1 inrush
current of 6.05 and 1 MW per pole. For motors => 1.0 MW per pole pair, the Standard specifies a X/R
ratio of 10. The : and q values at 0.10 seconds are:
The standard uses these multipliers to adjust the first cycle currents. The same total current will be
calculated if the inverse multiplies are applied to the impedances.
MW HP per R” PU X” PU
Motor KV RPM Poles %X” MVA X/R
Rating pole-pair Resistance Reactance
Motor Impedance for 1st Cy. and Interrupting Time (10 MVA Base)
Factors : and q for Rotating Equipment (Decay of Symmetrical Current)
Following the procedure given in IEC-60909, the non-decaying ac fault current is first calculated on the 6
kV bus, then the motor contributions are added to it.
Page 12
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
The equivalent impedance is determined by adding impedances C1 to T1 and C2 to T2 then paralleling the
two and adding the remote source impedance.
Since the bus is operated at 6.0 kV, I”k = 15.046*6.0/6.3 = 14.33 = 1.219 + j14.278 kA
The peak currents are added for each contribution separately. Using the equation for peak current I”k PEAK
=I”k *[1.02 + 0.98 , -3/(X/R)]*/2
To calculate the breaking time current at 0.10 seconds, the motor breaking currents are added to the non-
decaying ac source current
Page 13
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
Ik = 0.0308 + j 0.308 kA
IDC =(0.0745 + j 0.745kA)/2,_(2Β 50*0.1 /10) = 0.00455+j 0.0455 kA = 0.0457 kA
IbASYM = [0.04572 + 0.31112]1/2 = 0.313 kA
Since the sources having decaying ac current components are greater than 5% (>15% in this system) the
fault currents are referred to as ‘near to generator’.
This problem was redone using Method C for the first cycle peak. The motor impedances were included in
the network reduction. Computer software was used reduce the network with reactances at 40% the 50Hz
values. The final solution is given below with the Method C X/RAJD being used for both the peak and dc
component.
IbASYM = 16.73 kA
The solution for Example 2 followed the procedure given in IEC-60909. To me it has several questionable
items.
1. Why isn’t method A, B, or C used in this example. It appears to present a 4th method. Therefore, if
this example is given to several engineers, a number of different correct answers can be obtained.
Why not include the motors in the impedance reduction and let the math take care of the contribution?
Including motor impedances would be more acceptable to computer programs.
2. From the IEC examples given, it is not clear how to handle a network in which the cable impedances to
the motors are represented. If the fault currents at the terminal of the motors are to be calculated, and
if the motors currents are added after the ‘far from generator’ network is reduced, it appears that ohms
law can be violated for some system configuration. Network action will affect the currents coming
Page 14
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
from adjacent motors due to their cable impedances. To me, to motor current should not be added
directly as if it does not make a difference.
3 The procedure shows that the first cycle network impedance from remote sources is assumed not to
change for breaking time currents. While in example 2 this is correct, but in Example 3 ( not worked
out here) the motor contribution from Busbar B and C have an influence on each other which was not
taken into account during breaking time sample calculations. To me this again violates ohms law.
4 While I agree that a complex network reduction X/R ratio may not accurately represent the X/R ratio
needed to obtain the peak current, IEC-60909 indicate that Method C is more accurate. But, the
examples only use it on the first example. The Standard gives no references to support method C or
several other procedures used in the Standard.
6.1 Following the instructions outlined in steps 3.1 and 3.2, proceed to load the file “IEC2.eds”, and
launch the short circuit program interface.
Page 15
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
6.2 Following the same instructions outlined in step 3.3, proceed to select the options, and calculation
control settings for this example. The above screen capture shows the what is needed. Notice that
in IEC example 2, the 6 cycle X/R and AC component have been included in the calculation.
Next, run the analysis according to the procedure explained in step 3.4.
Page 16
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
6.3 Once again, the IEC 909 output screen, presents the selected output sections. At this point, the
report can be printed out, copied to the clipboard or saved as a text file for third party software
customisation. To exit, select “Done” from the menu.
Page 17
EDSA
IEC 909 SHORT CIRCUIT ANALYSIS
The following table shows a comparison between the results obtained using longhand calculations, EDSA
and the results documented in the IEC 909 standard.
All variances with Hand Calculations and IEC 909 documents are attributed to round off on input data or
results.
Page 18