You are on page 1of 14

Heat-Recovery Steam

Generators:
Understand the Basics

Gas turbines with heat-recovery - steam The HRSG generates steam utilizing the
generators(HRSGs) can be found in energy in the exhaust from the gas
By understanding virtually every chemical process turbine. However, some plants also have
industries (CPI) plant. They can be the capability of producing steam when
how gas-turbine operated in either the cogeneration mode the gas turbine is shutdown. This is done
or the combined-cycle mode (Figure 1). using a separate forced-draft fan along
heat-recovery steam with a burner to generate hot gases, which
In the cogeneration mode, steam produced
from the HRSG is mainly used for are then used to generate steam. An
generators differ isolating damper system (also called a
process applications, whereas in the
bypass damper) with seal air fans is re -
from conventional combined-cycle mode, power is generated
quired in these units to ensure that hot
via a steam turbine generator.
steam generators, Gas turbines have several advantages as a gases do not leak to the fan when the gas
power source: they can be started up turbine is running and that maintenance
engineers can quickly; they come in packaged modules, can be performed on the gas turbine when
with power outputs ranging from 3 MW the fresh air fan is operating. Bypass
design and operate to 100 MW, that can be easily assembled dampers are also used in some units to
and erected; they have high efficiencies of ensure that the gas flow to the HRSG can
HRSG systems that 25% to 35% (on a lower heating value be modulated in order to match steam
[LHV] basis); and they require little or no generation with steam demand. However,
produce steam cooling water. Recent developments in- if fresh air firing is not used, an isolating
clude large-capacity units of up to 250 damper is not required.
efficiently. MW, with low emission characteristics Recent trends in HRSG design include
(less than 10 ppmv NOx), as well as high multiple-pressure units for maximum en-
combustor operating temperatures (in the ergy recovery, the use of high-
range of 2,200°F), which results in effi- temperature superheaters or reheaters in
V. Ganapathy, ciencies higher than 35%; the exhaust gas combined cycle plants, and auxiliary
ABCO Industries temperature is also higher, which helps to firing for efficient steam generation. In
generate high-pressure/high-temperature addition, furnace firing is often employed
superheated steam, making the Rankine in small capacity units when the exhaust
cycle efficient. gas is raised to temperatures of 2,400-
The HRSG forms a major part of the 3,000°F to maximize steam generation
steam system. In the combined-cycle and thus improve fuel utilization.
mode, the efficiency of the combined gas- This article highlights some of the basic
turbine-plus-HRSG system can reach 55- facts about gas turbine HRSGs. This
60% (LHV basis) with today's advanced information can help plant engineers,
machines, while in the cogeneration consultants, and those planning co-
mode, system efficiency can be as high as generation projects make important deci-
75-85%. sions about the system and performance
related aspects.

32 • AUGUST 1996 • CHEMICAL ENGINEERING


HRSG temperature profiles and
steam generation
The starting point in the engineering of
a HRSG is the evaluation of its steam
generation capability and gas and steam
temperature profiles. For a
conventional fired steam generator, one
can assume a desired steam flow rate
and exit gas temperature and then fire
the necessary amount of fuel to meet
the steam demand. A HRSG behaves
differently due to the low inlet gas
temperature (900-1,050°F in the unfired
mode) and the large gas/steam ratio.
Arbitrarily assuming an exit gas
temperature or steam generation rate
can lead to "temperature cross situa-
tions" (discussed below).
Figure 2 shows the typical gas and
steam temperature profiles in a HRSG
consisting of a superheater, evaporator,
and economizer operating at a single
pressure. Because the gas temperature
entering the HRSG is low (900 -1,050°F
in unfired units), the steam generation
will also be lower than in conventional
steam gen erators for the same gas flow.
(Re

CHEMICAL ENGINEERING PROGRESS • AUGUST 1996 • 33


member that conventional steam gen-
erators start out at 3,200°F or so, the
adiabatic combustion temperature of
the fuels used.) Hence, the economiz-
er duty in the HRSG will also be low,
leading to a high exit gas tempera-
ture. Also (again unlike in a conven-
tional steam generator), the effect of
steam pressure is significant - the
higher the steam pressure, the higher
the exit gas temperature from the
evaporator and the lower the steam
generation rate, leading to a smaller
duty in the economizer and a higher
exit gas temperature. This is the rea-
son for considering multiple -pressure
units, as well as deaeration steam
coils and condensate heaters in
HRSGs operating at high pressures.
Two variables that directly affect
steam production and the gas and
steam temperature profiles are the
pinch point and the approach point
(Figure 2) (1). The pinch point is the
difference between the gas tempera-
ture leaving the evaporator and the
temperature of saturated steam. The
approach point is the difference be-
tween the temperature of saturated
steam and the temperature of the
water entering the evaporator.
Selection of these two variables also
entering the HRSG. Also, these pa- auxiliary fuel to generate a desired
affects the size of the superheater, the
rameters vary with ambient conditions, quantity of steam. There is only one
evaporator, and the economizer.
elevation, gas turbine load, and fuel design case, but several off-design
Based on the sizes of evaporators that
fired. Hence, the design case could be cases.
can be built and shipped eco-
60°F ambient condition at 100% load Prudent engineering calls for the
nomically, the pinch and approach
of the gas turbine, or any other pinch and approach points to be es -
points for unfired HRSGs are usually
accepted gas inlet parameters. tablished in the unfired mode (2, 3)
in the range of 15°F to 30°F. (If one
Using exhaust gas parameters at this rather than in the fired mode, for sev-
specifically wants to generate less
condition, one arrives at the design eral reasons:
steam, such as in a multiple-pressure
temperature profile, which forms the 1. Designs that can be physically and
HRSG generating more low-pressure
basis for sizing the HRSG. The HRSG economically shipped can be es-
steam than high-pressure steam, then
is then designed, or sized, once the tablished if pinch and approach points
a larger pinch and approach may be
pinch and approach points are selected are chosen in the range suggested
used.)
- that is, the surface areas are (Figure 2) in the unfired mode at the
Pinch and approach points are se-
determined indirectly. design ambient conditions.
lected for a particular case or exhaust
Once selected, the pinch and approach 2. A HRSG simulation approach is
gas condition called the "design
points will vary if gas flow and exhaust required to evaluate the pinch and
case." Unlike in a conventional steam
gas temperature vary. These cases are approach points at fired conditions or
generator, where the steam demand
called "off-design" cases. For example, at different ambient conditions (2, 3).
drives the design case, in a HRSG
at different ambient conditions and gas If the pinch and approach were se-
steam production is affected by the
turbine loads, one can have different lected in the fired mode (which is not
conditions of the exhaust gas leaving
exhaust gas parameters, or one may recommended), it is likely that the
the gas turbine (such as flow rate,
have to burn pinch point in the unfired mode could
temperature, and gas analysis) and

34 • AUGUST 1996 • CHEMICAL ENGINEERING PROGRESS


be too low, resulting in a huge, un- of steam leaving the superheater (ts2), nents, such as the superheater, evapo-
wieldly, and uneconomical HRSG. and steam pressure (Ps). Assuming a rator, and economizer, are fixed once
Also, a low approach point in the reasonable pressure drop in the super- U is computed. (To calculate U one
fired mode could result in steaming heater, we can determine the saturation should have such mechanical data as
in the economizer under unfired temperature ( t s) at the evaporator. tube size, fin density, tube pitch, etc.)
conditions. Economizer steaming Once the pinch point is selected, we But if U is not known, US is, which
should be avoided, as it results in know the temperature of the gas leav- indirectly fixes the surface areas.
operational problems such as ing the evaporator ( t g3) and the ap- Now, if we want to know how the
vibration, water hammer, and proach point gives the temperature of HRSG behaves at different gas condi-
possible deposition of salts in the the water leaving the economizer (tw2), tions, we have to perform off-design
economizer tubes, with the ultimate since the saturation temperature is calculations and use the "surface areas"
result being reduced performance. known. The heat loss (hl) ranges from we have indirectly established. It may also
3. If a superheater is used, it is 2% in small HRSGs to about 0.5% in be noted that we are using a pinch point
not possible to estimate the degree large units. Methods of estimating heat of about 15-20°F, which results in a low
of oversizing if the pinch and losses are outlined elsewhere (2). AT in the evap orator and thus the need
approach are selected in the fired Considering the energy balance for large surface area. (The pinch point in
mode. If the steam temperature is to across the superheater and a con ventional steam generator could
be maintained over a wide load evaporator (Figure 2), the energy range from 150°F to 400°F, so the ∆T is
range, it is likely that the steam absorbed by the superheater and much higher and the required surface
temperature will be lower than evaporator is given by: area much less.) This is why extended
desired under unfired conditions. If Q1.2 = Wg C pg( tg1 - tg3 ) (hl) = surfaces are a must in HRSGs.
pinch and approach points along Don't select exit gas
with the desired steam temperature Wsd[(h s2 - h w2 )
+ (bd)(h f- h w 2)] (1) temperatures arbitrarily
are selected in the unfired mode,
Since t g 1 and t g3 are known, Q 1 2 can
then the steam temperature can The right way to evaluate the de-
be computed and the design steam
certainly be maintained under fired sign temperature profile is to assume
flow (Wsd ) can be determined. The
conditions and can be controlled pinch and approach points and per-
superheater duty is:
using attemperation or other means. form the calculations outlined above.
A HRSG simulation program Q1 = Wsd (h s2 - h v)
The exit gas temperature ( t g4 ) is deter-
(such as the one developed by the = W C
g p g ( tg l - tg2 ) (hl) (2) mined as shown above.
author (2)) may be used to simulate From above, the temperature of the gas What happens if we try to assume
the design and off-design leaving the superheater ( t g2 ) can be a value for t g 4 ? From Figure 2, con-
performance of single, multiple- determined, since all the other data are sidering the heat balance across the
pressure unfired and fired HRSGs known. superheater and evaporator and ne-
(/). Simulation gives a good idea The economizer energy balance glecting blowdown, we have:
of what the HRSG can do at gives: Wg Cp g( t g 1 - t g 3 ) (hl)
different gas inlet conditions, and
Q3 = Wsd (h w2 - h w1 )(1 + bd)
can help one optimize temperature = Ws d(h s2 - h w2 ) (4)
profiles and HRSG configurations = W g Cpg ( tg3 - tg4 ) (hl) (3)
and evaluate HRSG performance The gas temperature leaving the Also, considering the complete
with different gas turbines. economizer ( t g4) can be obtained from HRSG:
Simulation can also help one this. Thus, the complete gas/steam Wg Cpg (tg l - tg4 )(hl)
evaluate the effects of the exhaust profiles and steam generation rate for the = Wsd(h s2 – h w1 ) (5)
gas analysis, which is important in design case can be determined by
steam-injected gas turbines, because Dividing Eq. 4 by Eq. 5 and ne-
assuming the pinch and approach points.
gas specific heat and duty are In addition, once the pinch and glecting the effect of specific heat, we
impacted by gas analysis. approach points are selected, the log- have:
mean temperature differences ( ∆T) at (t g 1 - t g3 )/(tg 1 - t g4 )
Design temperature profile the various surfaces are fixed. Since = (h s2 - h w 2)/(hs 2 – h w1 )
calculatio ns from basic heat-transfer principles = K (6)
The starting point for determining surface area is given by S = QIUAT,
gas and steam temperature profiles and the surface areas of all the compo For steam generation to occur, two
steam generation is the assumption of conditions must be met:
pinch and approach points, as tg3 > ts
discussed above. The values that are
tg 4 >twl
known are gas flow rate (Wg, gas
temperature at HRSG inlet ( t g1 ), feed
water temperature (tw1), temperature
CHEMICAL ENGINEERING PROGRESS • AUGUST 1996 • 35
In simple terms, the factor US is obtained
using the equation Q/∆T for each
surface in the design case. Then in the
off-design case, the values of US are
corrected for the effects of gas flow,
temperature, and composition. Then, the
energy transferred across each surface is
obtained through an iterative process
using the following equation (after first
assuming a steam flow rate to begin):
Q = WgCpg(tgi - tgo)
= Ws(ho -hi)
= US∆T (7)
The total energy transferred across
each surface is computed, and the ac-
If either condition fails, a temperature cross (1,600 - 512)/(1,600 –tg4) = 0.7728,
tual steam generation rate (Ws) is ob-
situation results, meaning that the HRSG or tg4 = 192°F, which is below the
parameters are invalid and must be selected tained from the sum of ΣQ/(∆h) for
feed water temperature of 230°F.
again. This is why we cannot arbitrarily This, too, is an invalid temperature all the surfaces. This information is
select pinch and approach points and the profile. With a much higher pinch then used to correct the assumed
exit gas temperature. point we could have obtained tg4 steam flow.
Calculations for t have been carried out at
g4 above 230°F. This illustrates why The problem gets more complicated if
various steam conditions for a typical gas pinch and approach points are best there are several modules, and gets
turbine and the results are presented in selected in the unfired mode, having complicated further still if auxiliary firing
Table l. It may be seen that as the steam values in the range suggested in Fig- is used to generate the desired steam flow
pressure increases, the exit gas temperature ure 2, to ensure valid temperature rate in a particular module. Simulation
increases. Also, as the steam temperature profiles. Simulation can also help de- software, which performs these complex
increases at a given pressure, the amount of termine valid conditions. calculations in minutes, comes in handy
steam generated decreases for a given pinch in these s ituations.
point; this results in a decrease in the Evaluating HRSG design features
economizer duty, thus increasing the exit off-design performance
gas temperature. (The calculations are based The HRSG generates steam, the quality
We have seen how the "design
on a gas inlet temperature of 900°F, feed and quantity of which depend on the
temperature profile" is arrived at. Using
water temperature of 230°F, pinch point of simulation, one can predict HRSG flow and temperature of the exhaust gas
20°F, and approach of 15°F.) performance at any other gas inlet entering it. Large cogeneration and
Let us now see that an exit gas temperature conditions or steam parameters. This combined-cycle plants
of 300°F, at conditions of, say, 600 psig and approach is discussed elsewhere (1,2).
750°F, cannot be achieved. Using data from
the steam tables, K = 0.7728 at these condi-
tions. From Eq. 6, (900 –tg3)/(900 - 300) =
0.7728, or tg3 = 436°F. This is below the
saturation temperature of 492°F, which is
not a valid temperature profile - hence, we
say that temperature cross has occurred.
Now let us see what happens if we select the
pinch point in the fired mode with a gas
inlet temperature of 1,600°F. Let us assume
a 20°F pinch at the same pressure and
temperature conditions as above.
Using Eq. 6,

5• AUGUST 1996 • CHEMICAL ENGINEERING PROGRESS


generate high-pressure/high-tempera -
ture superheated steam (600-1,500 psig
at 650-950°F), while small ca pacity
plants (10-MW gas turbines and below)
may generate low-pres sure saturated
steam (100-300 psig). The superheated
steam temperature in a HRSG is
controlled using spray desuperheaters
as in conventional boilers. Steam
temperature varies with gas inlet
conditions, so performance should be
verified at various off-design cases.
Multiple-pressure steam generation is
employed in cases where the exit gas
temperature from single-pressure-level
generation would be considered too
high or uneconomical.
There are three types of HRSGs:
unfired, supplementary-fired, and ex-
haust-fired (Figures 3-5). This is not a
rigid classification, but it is widely used.
Table 2 shows the main features and
the typical steam outputs that can be
expected for each of the three types.
Figure 4b also shows a freshair-firing
system, where a supplemen tary-fired
HRSG is operated using air from a fan,
a situation that arises, for example,
when the gas turbine trips or is shut
down for maintenance. Fig ure 4c shows
a typical duct burner for a
supplementary-fired HRSG.

Unfired and supplementary-


fired HRSGs
The HRSG consists of single- or
multiple-pressure modules depending
upon the degree of energy recovery
desired. A simulation of the tempera -
ture profiles must be performed (I)
before designing the steam system for a
given application.
Unfired and supplementary-fired
HRSGs are similar in appearance and
constru ction, both being convective
designs. The units are internally insu-
lated with ceramic-fiber insulation with
an alloy steel liner to hold the insulation
in place. The insulation thickness
ranges from 4-6 in. inunfired units to 8-
10 in. in supplemen tary-fired units.
Roughly two-thirds of the HRSGs
purchased today are unfired due to their
low first cost.

CHEMICAL ENGINEERING PROGRESS 9 AUGUST 1996 • 37


Extended surfaces are widely used in the
superheater, evaporator, and
economizer. This is because a large
surface area is required in these systems
as a result of the low pinch and
approach points and the low logmean
temperature differences at the various
heating surfaces. Extended surfaces
make the HRSG design very compact.
And, lower gas pres sure drops can be
achieved with extended surfaces than
with bare tubes (Table 3) (2).
For evaporators and economizers with
clean gas streams, such as exhaust from
natural-gas -fired and dis tillate-oil-fired
gas turbines, fin densities of 4 to 5
fins/in. are reco mmended. Fin height
can vary from 0.5 to 1 in. Fin thickness
is typically from 0.05 to 0.075 in.
A low fin density is recommended for
superheaters due to their low tube-side
heat-transfer coefficient (3). Using a
high fin density when the tube-side peratures remain safely within limits. HRSG with surface area that is 100-
coefficient is low offers no added The first few rows of tubes near the 200% more than that of another design
benefit. The use of fins, in gen eral, high-gas-temperature zone use bare with a lower fin density can transfer the
increases the tube wall and fin tip tubes, and subsequent tube rows, same duty. Therefore, one should look
temperatures and the heat flux inside the where the gas is cooler, have extended at the product of overall heat -transfer
tubes. When the tube-side co efficient is surfaces. coefficient times surface area (US)
instead of surface area alone.
low, the temperature drop across the Surface areas can be misleading,
tube-side film is naturally high, resulting particularly when finned tubes are used. Table 4 illustrates the effects of fin
in high tube wall and fin tip The higher the fin density and the ratio geometry on superheater performance
temperatures even without fins. of external-to-internal tube surface (3, 4). For example, a superheater can
In fired units, a combination of bare and area, the lower the gas-side heat- transfer the same duty with signifi-
finned tubes is used to en sure that the transfer coefficient and hence the lower cantly different surface areas - the
tube wall and fin tip tem - the overall heat-transfer co efficient surface area in case 2 is more than
(Figure 6) (2, 4). Thus, a

7• AUGUST 1996 • CHEMICAL ENGINEERING PROGRESS


these cases, a small fan (called an
augmenting air fan) is also included
with the burner.
The duct burner raises the exhaust gas
temperature from about 1,000°F to a
maximum of 1,700°F in HRSGs with
insulated casings and up to 2,400°F in
HRSGs equipped with water-cooled
furnaces. The gas pressure drop across
the duct burner is low (on the order of
0.5 in. w.c.). This is important because
each additional 4 in. w.c. gas pressure
drop in the HRSG decreases the gas
turbine power output by about I %.
In large capacity units for combined-
cycle plants, reheaters are installed in
addition to superheaters to improve the
Rankine cycle efficiency. Unlike in a
Rankine cycle system based on a
conventional steam generator, where
the condensate is heated in external
steam-to-water heat exchangers using
steam extracted from the steam
turbine, in a gas turbine HRSG the
double the surface area in case l, yet condensate or make-up water is heated
(such as natural gas and distillate oil)
the duty (or energy transferred) is es- in the HRSG itself to improve the
into the exhaust gas stream.
sentially the same. This is because of efficiency of energy recovery.
Generally, no additional air is used,
the poor fin configuration in case 2 - Deaeration steam may also be gener-
except when the exhaust gas is
due to the higher heat flux inside the ated in the HRSG for the same reason.
injected with large quantities of
tubes with the higher fin density, the Thus, it is not unusual to see several
steam, which reduces the amount of
tube wall and fin tip temperatures in modules in a HRSG. Multiple pressure-
oxygen available for combustion. In
case 2 are much higher than in case 1. level steam generation,
Hence, the use of excess surface has
negative implications, too. Compar-
ing cases 2 and 3 illustrates how more
duty is transferred with a lower sur-
face area simply by selecting opti-
mum fin configuration. Thus, engi-
neers and purchasing managers
should not make decisions using a
spreadsheet that shows only the sur-
face areas of different designs.
Rather, a good evaluation should in-
clude the product of overall heat-
transfer coefficient (on an external
surface area basis) and surface area.
A supplementary-fired HRSG has a
duct burner (Figure 4c) located up-
stream. A duct burner typically has
a rectangular cross-section and fits
into the ductwork carrying the
exhaust gases. It consists of vertical
or horizontal grids with holes that
admit fuel

CHEMICAL ENGINEERING PROGRESS AUGUST 1996 • 39


which increases the efficiency of en ergy pressure unit in these systems, as the and natural gas or fuel oil input is (3):
recovery, is common in unfired and exit gas temperature can be brought Q = 58.4W gO (8)
supplementary-fired HRSGs. down to a low level (on the order of
300°F), unlike in an unfired or sup- where W g is the exhaust gas flow in
Exhaust-fired HRSGsThe exhaust- lb/h, O is the oxygen consumed in
plementary-fired HRSG, which has a
fired HRSG (Figure 5), in which the %vol., and Q is the burner heat input in
high exit gas temperature if a single-
firing temperature ranges from 1,700°F Btu/h (LHV basis).
pressure system is used.
to 3,000°F, uses a completely water- For example, if the exhaust gas
Due to the high gas temperature
cooled furnace to contain the flame, conditions are 150,000 lb/h at 1,000°F
entering the HRSG, the design is likely
since the temperature could approach with 15% oxygen, the energy required
to consist of more bare tubes than
the adiabatic combustion temperature. to raise the gas to 1,700°F is
finned tubes. A radiant furnace is
The burner used is typically a register approximately Q = (150,000)(0.3) x
required to cool the gases before they
burner with a windbox, although a duct (1,700 - 1,000) = 31.5 MM Btu/h; the
enter the superheater or convective
burner may be used up to 2,400°F. The sections. oxygen consumed during com bustion
gas turbine exhaust is used as hot air will be: O = 31,500,000
for combustion. In certain plants Auxiliary firing and [(150,000)(58.4)] = 3.6%. Thus, the
overseas, even solid fuels such as coal system efficiency exhaust gas still contains more than
have been fired in these boilers using Typical gas turbine exhaust contains 13- 11.4% oxygen.
register burners. 15% oxygen by volume. This is A HRSG simulation program has been
The gas pressure drop across the adequate to fire additional fuel in the used to evaluate the efficiency of
register burner is high (about 4-6 in. burner to raise the exhaust gas supplementary firing on HRSG per -
w.c.). The HRSG is typically a single temperature to about 3,000°F. The re- formance, and the results are present ed
lationship between oxygen availability in Table 5 and Figures 7 and 8. As

9• AUGUST 1996 • CHEMICAL ENGINEERING PROGRESS


the amount of firing increases, the ef-
ficiency of the system (as defined by
ASME PTC 4.4 (S)) also increases.
Note that the fuel utilization in the
HRSG is nearly 100%. The additional
boiler duty to generate 60,000 lb/h of
steam is 59.90 - 22.67 = 37.23 MM
Btu/h and the fuel added is 37.60 MM
Btu/h (LHV basis). Thus, all of the fuel
energy goes into generating steam,
making the fuel utilization 100%,
compared to the efficiency of a
conventional steam generator of about
90%. There are two reasons for this:
l. We know from basic combustion
principles that in a conventional steam
generator, as the excess air increases,
the efficiency decreases. This

CHEMICAL ENGINEERING PROGRESS • AUGUST 1996 • 41


is because the additional air must be files, casing design, use of extended
heated from ambient conditions to the surfaces, and surface area require -
exit conditions. In a HRSG, on the ments are similar between natural-
other hand, the amount of excess air is and forced-circulation units.
reduced by firing only fuel in the
exhaust gas without adding air. Improving HRSG efficiency
2. The exit gas temperature in a Several options for improving energy
single-pressure HRSG decreases as recovery, even in a single-pressure
the firing temperature increases. In a steam system, are illustrated in Figure
conventional steam generator, the 10.
gas/steam ratio remains nearly con- Make-up water or condensate can be
stant at about unity at all loads, heated in the HRSG itself (Figure
where as in a gas turbine HRSG, it 10a). This reduces the amount of
decreases as steam generation steam required for deaeration, im-
increases. This results in a larger heat proving the overall efficiency. If sul-
sink at the economizer and hence a furic acid vapor is present in the ex-
lower exit gas temperature. Note that haust gases, the condensate tempera-
in a HRSG, the gas flow remains ture should be no lower than the acid
nearly the same at all steam vapor's dew point to prevent conden-
generation levels. sation of the corrosive vapors on the
Therefore, engineers should first plan separation occurs. Saturated steam is tube (4). This condensate heater op-
to generate additional steam in the then taken to the superheater. tion is generally used in natural-gas-
HRSG before using conventional In forced-circulation HRSGs, the tubes fired systems that do not contain acid
steam generators (6, 7). As discussed are horizontal and gas flow is vertical. vapors. Still, the water temperature
earlier, unfired and supplementary- This configuration minimizes the use entering the exchanger should be
fired HRSGs do not differ much ex- of land space. The cross-sectional area, above the water vapor's dew point to
cept for changes in steam drum size, though, is the same as in natural- prevent water condensation on the
insulation thickness, valve sizes, and circulation systems. tubes.
so on. Hence, it may be economical to Pumps maintain circulation of the The second option is to generate low-
consider these designs for firing up to water/steam mixture through the pressure saturated steam or deaeration
1,300-1,500°F to maximize steam evaporator tubes, which results in an steam in the HRSG itself using a low-
generation at a high efficiency. The additional operational expense. Failure pressure evaporator (Figure 10b). This
furnace-fired HRSG requires a of the pumps can cause shutdown and type of system is recommended if
completely different design with possibly evaporator tube failure. there is a possibility of acid vapor
completely water-cooled membrane- Keep in mind that the heat flux in side condensation, since the steam
wall furnaces, so a detailed cost finned tubes is several times that in a saturation temperature can be
evaluation is needed to determine the comparable bare tube. Thus, fired maintained above the acid's dew point.
economic viability of this type of HRSGs must be designed with care to However, it is more expensive than
HRSG. prevent overheating of the tubes. In the condensate heater option due to
general, horizontal tubes cannot higher surface area requirements and
Natural vs. forced circulation tolerate heat fluxes as high as vertical the need for a drum, instrumentation,
Natural-circulation HRSGs (as shown evaporator tubes can because in the and controls. The exit gas temperature
in Figures 3-5) are common in the latter gravity assists in providing good from the HRSG will naturally be
U.S. In Europe, forced-circulation wetting of tube periphery. In addition, higher than the saturation temperature
units (Figure 9) are more prevalent. In steam bubbles formed during boiling of steam, whereas in the pre vious
natural-circulation HRSGs, the tubes tend to concentrate on the top portion option, it could be much lower.
are vertical and gas flows hori- of the horizontal tubes, while water The third option is to preheat the
zontally. The widths of the various occupies the lower portion. This results make-up water in a heat exchanger
modules are limited by shipping in a varying temperature profile across before it enters the deaerator, while
considerations. Thus, large HRSGs the tube periphery due to the different simultaneously cooling the feed water
may have modules 12 ft wide and 30- heat-transfer coefficients of water and before it enters the economizer (Fig-
50 ft tall. Downcomer pipes carry the steam, which leads to higher thermal ure 10c). The economizer requires a
hot saturated water to the bottom of stresses. larger surface area, but this is an eco-
the evaporator modules and riser pipes Other aspects of HRSG design, such nomical option compared to the
carry the steam/water mixture to the as gas/steam temperature pro deaerator.
external steam drum, where

42 • AUGUST 199 6 • CHEMICAL ENGINEERING PROGRESS


Condensing heat exchangers have circulate more water than necessary Evaluating operating data
also been used in some projects. through the economizer and HRSGs often operate under different
Polytetrafluoroethylene (PTFE; e.g., recirculate the excess to the deaerator exhaust gas conditions and steam
Teflon) or similar corrosion-resistant in order to reduce the deaeration parameters than the design conditions
material is used as a coating on the steam requirements (Figure 1Od). - for example, if the ambient
tubes to prevent corrosion from acid Some plants, depending upon the temperature or gas turbine load is
condensation. In such cases, the steam system and the quantity and different from what was selected for
make -up water can enter the heater as temperature of make-up water re - design of the HRSG. The questions
cool as 60-80°F. quired, may use a combination of then arise as to whether the HRSG is
Another option for lowering the these methods. operating satisfactorily or not, and
exhaust gas temperature is to how the operating data

CHEMICAL ENGINEERING PROGRESS 9 AUGUST 1996 • 43


range of 2-4 in. w.c., which must be
considered in the overall design and
performance evaluation.

Turbine exhaust
characteristics
Two important variables that affect flow
rate and temperature of the gas turbine
exhaust are ambient temperature and
load, as mentioned earlier. These
parameters, in turn, affect HRSG
performance. At higher ambi ent
temperatures, the exhaust gas flow is
lower and the exhaust gas temperature is
higher, and vice versa. As the gas turbine
load decreases, the exhaust gas
temperature also decreases but the mass
flow does not vary much.
As a result of the variations in exhaust
gas flow and temperature, the HRSG
steam flow and temperature will also be
affected (Figure 12). Therefore, engineers
should analyze HRSG performance at
various cases and ensure that the plant
performance is not impacted by the
varying steam production in the HRSG.
Supplemen tary firing of the HRSG, as
well as steam and water injection in the
gas turbine, may have to be considered to
ensure steady steam production.
can be reconciled with any performance further to 9-15 ppm. Catalysts, in the Steam injection is becoming more
guarantees. form of selective catalytic reduction widespread. In addition to controlling
One way to answer these questions (SCR) systems (9), can be used in the NO, emissions from the gas turbine
is through HRSG simulation. One can HRSG to achieve this lower emission combustor, it also increases the gas
use the operating data to simulate the level. turbine power output as well as the
design pinch and approach points, and Catalyst performance is affected by gas HRSG output. This is due to the high er
then use this information to predict the temperature at the catalyst. Catalysts mass flow as well as the higher specific
HRSG off-design performance at the operate efficiently over a narrow range heat of the gas. In the Cheng cycle (3),
conditions specified in the proposal or of gas temperatures. For NOx catalysts, for example, steam injection is significant,
guarantee. A comparison between the the gas temperature range is typically raising the amount of water vapor from
two sets of data can confirm whether 600-750°F; for CO catalysts it is 900- 7% in uninjected units to 25%, with a
or not the HRSG original design is 1,200°F. The catalyst supplier specifies corresponding increase in the gas turbine
adequate (8). this temperature window, which power output from 3.5 to about 5.5 MW.
depends on the materials used. In order In summer months the gas turbine
Use of catalysts to achieve temperatures within this power output drops off, which may not
With stringent environmental reg- window at all loads of the HRSG, the be tolerable in some plants. Evaporative
ulations for carbon monoxide and ni- heat-transfer surfaces may have to be cooling or some other form of air cool-
trogen oxides, the use of catalysts for split to find a good location for the ing can be used in these plants to main-
controlling emissions is becoming SCR (Figure 11). tain a low and steady inlet air tempera-
commonplace. Steam and water in- Provision should be made for an ture to the compressor throughout the
jection and modifications to the gas ammonia injection grid upstream of the year. This results in a constant power
turbine combustor can reduce NOx NOx catalyst. The catalyst also has a output and steam generation, and
levels to 30-40 ppm. However, some high gas pressure drop, in the
states require that NO, be reduced

13 • AUGUST 1996 • CHEMICAL ENGINEERING PROGRESS


HRSG performance in such units does generator). While evaluating HRSG
not vary much with ambient tempera- steam flow, pinch and approach points HRSG simulation can help one evalu-
tures. However, this option is should be selected in the un fired mode. ate plant operating data and compare it
economical only in large gas turbines - Fired HRSGs are more efficient than with design data.
exceeding, say, 50 MW capacity. unfired; hence, cogeneration plants are
Closing
Closing thoughts more efficient in the fired mode.
Gas turbine HRSGs have different Several options for im proving energy
performance characteristics and con- recovery in the HRSG should be
struction features than conventional evaluated. Multiple-pres sure steam
steam generators. By understanding generation should be considered to
these and relating them to conven tional optimize energy recovery, particularly if
steam generators, engineers can generate high-pressure steam is generated. Since
steam efficiently. extended surfaces are widely used, an
The key points to remember are as understanding of heat-transfer
follows. To determine steam generation characteristics with finned tubes is
from a given gas turbine, a HRSG desirable. Engineers often make the
simulation should be performed, mistake of selecting a HRSG based on
because the HRSG exit gas temperature surface area alone, which can be
cannot be arbitrarily selected (as in a misleading - more surface area does not
conventional steam always mean more heat transferred.
And finally,
CHEMICAL ENGINEERING PROGRESS AUGUST 1996 • 14

You might also like