You are on page 1of 22

COOLING TECHNOLOGY INSTITUTE

TEST CODE FOR


AIRCOOLED CONDENSERS

July 2011 ATC-107 (11)


FOREWORD
This Cooling Technology Institute (CTI) publication is published as an aid to cooling tower purchasers and designers.
It may be used by anyone desiring to do so, and efforts have been made by CTI to assure the accuracy and reliability
of the data contained herein. However, CTI makes NO WARRANTY OF FITNESS FOR PARTICULAR PURPOSE
OR MERCHANTABILITY nor any other warranty expressed, implied or statutory. In no event shall CTI be liable or
responsible for INCIDENTAL, CONSEQUENTIAL OR COMMERCIAL losses or damage of any kind resulting from
this publication’s use; or violation of any federal, state, or municipal regulation with which this publication may conflict
or for the infringement of any patent resulting from the use of this publication.

All CTI codes and standards are copyrighted with all rights reserved to CTI. The reproduction of any part of this or
any other CTI code or standard is a violation of Federal Law. One must recognize and appreciate commitment by a
number of volunteer members who donate their time to develop and update CTI codes and standards. The monies
spent for code development, administrative staff support and publication are essential and constitute a substantial
drain on CTI. The purchase price of these documents helps to offset these costs. Reproduction and distribution by
others, in addition to being unethical, undermines this system and constitutes a further financial drain on CTI. When
copies are needed, your are requested to call or write the Cooling Technology Institute, P.O. Box 73383, Houston,
Texas 77273, (281) 583-4087. Please request that your associates buy the required codes and standards rather
than copy them. Your cooperation in this matter is greatly appreciated.

Nothing contained herein is to be construed as granting any right for the manufacture, sale or use in connection with
any method, apparatus, or product covered by letters patent, nor as insuring anyone against liability for infringement
of letters patent.

This document summarizes the best current state of knowledge regarding the specific subject. It represents a
consensus of those individual members who have reviewed this document, its scope and provisions and is intended
to aid all users or potential users of evaporative vapor condensers.

Approved by the CTI Executive Board.

This document has been reviewed and approved


as part of CTI’s Five Year Review Cycle. This
document is again subject to review in 2016.

Copyright 2011
Approved by the by Cooling Technology Institute
CTI Executive Board Printed in U.S.A. ATC-107 (11)
TABLE OF CONTENTS

Page
1.0 Introduction........................................................................................................................................ 1
1.1 Scope ............................................................................................................................................. 1
1.2 Basis............................................................................................................................................... 1
1.3 Test Plan ........................................................................................................................................ 1
1.4 Definitions and Nomenclature ....................................................................................................... 1
2.0 Conditions of Test .............................................................................................................................. 2
2.1 Test Witnesses ............................................................................................................................... 2
2.2 Conditions of the Equipment ......................................................................................................... 2
2.3 Operating Condition....................................................................................................................... 2
2.4 Constancy of Test Conditions ........................................................................................................ 2
2.5 Duration of the Test ....................................................................................................................... 2
2.6 Frequency of Readings .................................................................................................................. 2
2.7 Number of Tests............................................................................................................................. 3
3.0 Test Measurements ............................................................................................................................ 3
3.1 Condenser Pressure ........................................................................................................................ 3
3.2 Steam Quality (Steam Content) ..................................................................................................... 4
3.3 Condensate Flow............................................................................................................................ 4
3.4 Inlet Air Temperature .................................................................................................................... 4
3.5 Barometric Pressure ....................................................................................................................... 5
3.6 Fan Motor Input Power .................................................................................................................. 5
3.7 Wind Speed .................................................................................................................................... 5
4.0 Evaluation of Test Data ..................................................................................................................... 5
4.1 Manufacturer’s Data ...................................................................................................................... 5
4.2 Calculation of Condenser Capability ............................................................................................. 6
5.0 Test Uncertainty................................................................................................................................. 7

Appendix A Basic Equations


Appendix B Calculation of Condenser Characteristic
Appendix C Example Calculation
Appendix D Uncertainty Analysis Example
Sensitivity Factors
Figure Cross Plot at Test Dry Bulb
Figure ACC Perf Curve
TEST CODE for AIRCOOLED CONDENSERS

Section 1. Introduction 1.4 Definitions and Nomenclature


Capability - a measure of the thermal capacity of the
1.1 Scope This document details the measured test condenser expressed as a ratio between the design steam
parameters, instrumentation, test measurements and data flow and the predicted steam flow at test conditions.
reduction procedure required for determination of the
Condenser pressure - the steam pressure at the boundary of
thermal capability of a dry, air-cooled steam condenser
the condenser.
(ACC). The procedure focuses on contractual acceptance
testing of new units, but the same procedure may be used for Predicted steam flow - the steam flow rate predicted by the
performance testing of an existing unit. manufacturer for a given set of test conditions.
1.2 Basis Several resources have been used in the Nomenclature
preparation of this code. These are: A = area, m2 (ft2)
 VGB Guideline for Acceptance Test Measurement C = Condenser capability ()
and Operation Monitoring for Air Cooled Fc = correction factor from test to guarantee
Condensers (1997) conditions
 Code of Practice for Acceptance and Operating
NTU = number of heat transfer units
Tests of Air Cooled Steam Condensers (published
by the Association of German Electricity Supply P = pressure, Pa (in Hg, psia)
Authorities in 1965) Q = heat transfer rate, Watts (Btu/hr)
 ASME PTC 12.2 Steam Surface Condensers T = Temperature, C (F)
 CTI ATC-105 Acceptance Test Code for Water
Cooling Towers (2000) U = overall heat transfer coefficient, W/m2/C
 ASME PCT-23 Atmospheric Water Cooling (Btu/hr/ft2/F)
Equipment 
V = volumetric flow rate m3/s (ft3/min)
1.3 Test Plan A test plan is a convenient vehicle for W = power, Watts (hp)
specification of responsible test participants, required X = steam quality
preparations, measurement location, test instrumentation,
z = wind speed, m/s (mph)
required adjustments to plant operations, acceptable test
conditions, anticipated deviations from the test code, cp = heat capacity at constant pressure, kJ/kg/C
calculation procedures, and expected test uncertainty. As an (Btu/lbm/F)
example, the measurement of steam flow and the estimation h = specific enthalpy, kJ/kg (Btu/lbm)
of steam quality will require the use of plant instruments, mk = exponent for the correction of test fan motor
particularly flow elements. It is vital that such instruments power guarantee conditions
be identified prior to the test so that any necessary
calibrations can be performed. In addition, measurement of u = wind speed m/s (mph)
condensing pressure requires the installation of basket tips, Tlm = log mean temperature difference, C (F)
which may be different in number and location than those  = condenser effectiveness
used by the plant for monitoring purposes. The preparation
of a test plan, approved by manufacturer and the ACC prior  = condenser characteristic parameter
to the test, is highly recommended.  = film heat transfer coefficient, W/m2/C
(Btu/hr/ft2/F)
Impartial Testing Service - It is the intention of the Cooling
Technology Institute to provide independent third-party  = density, kg/m3 (lbm/ft3)
thermal performance testing. This means that any situation Subscripts
in which a testing agency has a material or other interest in G = guarantee
the outcome of the tests must be avoided. The CTI-licensed
Test agency referred to in this code shall have no P = predicted
connection, other than contractual, with the manufacturer, T = test
the purchaser or the Cooling Technology Institute. M = measured
System of Units - This standard is written in System i = inlet
International (SI) Units with secondary inch-pound (I-P) s = condensing steam
units. For conversion factors between I-P and SI units, refer
Superscripts
to CTI Bulletin STD-145.
c = corrected value

-1-
Section 2. Conditions of Test 2.3.4 Average wind velocity shall be less than or
equal to 4.5 m/s (10 miles per hour).
2.1 Test Witnesses For acceptance testing, representatives a) One minute duration velocity shall be less than 7
of the owner and condenser manufacturer shall be given m/s (15.6 miles per hour).
permission, opportunity and adequate notice to inspect the 2.3.4 The following variations from design conditions
ACC and prepare the ACC for the test. In no case shall any shall not be exceeded:
directly involved party be barred from the test site. a) Dry-bulb temperature-10C from design (18F)
but greater than 5C (41F).
2.2 Conditions of the Equipment b) Condensate Mass Flow-10% of the design value.
At the time of the test, the ACC shall be in good operating
c) Fan motor Input Power-10% of the design value
condition.
after the air density correction. (Eq. 4-7)
a) Steam duct and condensate piping systems shall be
essentially clear and free of foreign materials that may 2.3.4 Steam turbine exhaust steam shall be distributed
impede the normal flow of steam and condensate. to all modules as recommended by the manufacturer.
b) Mechanical equipment, including fans, gear boxes, For the purposes of the Code, a “module” is defined as
motors, pumps, air ejectors, etc., shall be clean and in good the smallest subdivision of the ACC, bound externally
working order. Fans shall be rotating in the correct by fin tube bundles and internally by partition walls,
direction, with proper orientation of the leading and trailing which can function as an independent unit. Each
edges. Fan blade pitch shall be set to a uniform angle that module generally has a single fan.
will yield within 10% of the guarantee fan driver input 2.3.5 There shall be no rain during the test period nor
power when corrected for the air density at the test in the one hour period preceding the test period.
condition. Variable frequency drives, if present, must be put 2.3.6 Steady state operation (constant condensate
into bypass (preferred), or set to 100% of rated speed. mass flow as defined in section 2.4.1) of the ACC shall
c) Air in-leakage must be such that the vacuum equipment be achieved at least one hour before and shall be
has at least 50% excess holding capacity during the test. maintained during the test periods.
d) ACC air inlet perimeter area and discharge area shall be
essentially clear and free from temporary obstructions that
2.4 Constancy of Test Conditions
may impede normal airflow.
For a valid test, variations in test conditions shall be within
e) The air side of the ACC fin tube bundles shall be
the following limits:
essentially free of foreign material, such as pollen, dust, oil,
scale, paper, animal droppings, etc. 2.4.1 Inlet dry-bulb temperature shall not vary by
f) Water level in the condensate hotwell tank shall be at more than 3C (5.4F) during the test. Variation is
the normal operating level. defined as the slope of the inlet dry-bulb temperature
g) Representatives of the ACC purchaser and with time the test run multiplied by the time period of
manufacturer shall agree prior to commencement of testing the test.
that the cleanliness and condition of the equipment is within 2.4.2 The initial temperature difference (ITD, defined
the tolerance specified by the manufacturer. Prior as the difference between the condensing steam
establishment of cleanliness and condition criteria are temperature, as calculated from the condenser pressure
strongly recommended. at the test boundary, and the inlet air temperature and
h) All emergency drain lines and all bypass lines which the condensing steam temperature) shall not vary by
have the potential for delivering superheated steam to the more than 5% of the ITD during the test period. The
condenser shall be isolated. A closed valve shall be variation between the maximum ITD and the minimum
considered adequate isolation. ITD shall not be more than 10% of the average ITD
during the test period.
2.3 Operating Condition
2.3.1 The test shall be conducted while operating as 2.5 Duration of the Test
close to the operation/guarantee point(s) as possible. In After reaching steady state conditions, the requirements for
any event, the test shall be conducted within the the test duration shall be at least one hour. Longer test
following limitations: intervals are acceptable provided the constancy of test
conditions is observed.
2 . 3 . 2 The test dry-bulb temperature shall be the inlet
value, measured in accordance with paragraph 3.4 of
2.6 Frequency of Readings
this test procedure.
Readings shall be taken at regular intervals and recorded
2 . 3 . 3 The wind velocity shall be measured in in the units and to the number of significant digits shown
accordance with paragraph 3.7 of this test procedure in Table 2.0.
and shall not exceed the following:

-2-
Table 2.0 Measurement Frequency
Minimum
Readings per Recorded to
Measurement Unit
hour per Nearest
station
ACC Condensate Mass Flow 60 kg/h (lb/h) 0.1%
Condensate Hotwell Tank Level 5 M (ft) 0.01 (0.03)
0.005
Exhaust Steam Pressure 60 kPa (in.HgA)
(0.01)
Exhaust Steam Temperature (for
60 C (F) 0.05 (0.1)
comparison)
Inlet Air Dry-bulb Temperature 60 C (F) 0.01 (0.01)
Atmospheric Pressure 1 kPa (in. Hg) 0.2 (0.05)
Ambient Wind Velocity 60 m/s (mph) 0.1 (0.2)
Fan Power at Switchgear 1 kW (HP) 0.5%

2.7 Number of Tests total flow for an inlet is less than five percent of the total.
Even when tested under the guidelines specified in section 2.3, For inlet flows with less than 5 percent of the total steam
the apparent performance of air cooled condensers may vary flow, one pressure measurement is required. Steam inlets
with the following environmental conditions: with less than 1 per cent of the total steam flow need not
 wind speed be instrumented.
 wind direction 3.1.2 For air cooled condensers with multiple steam
 atmospheric stability inlets, the mass weighted average absolute pressure of the
To decrease the possibility of an anomalous test result, it is instrumented inlets shall be used as the condenser pressure
required that at least six tests be performed over a two day on lookup charts, tables, and curves.
period. The capability of the condenser shall be the average of 3.1.3 The pressure measurement points shall be located
the tests conducted with test conditions within the limits at positions 90 apart around the steam inlet. Pressure
specified in this Code. ports shall be bored holes in the wall of the steam inlet
connected to basket tips or baffle plates as illustrated in
Section 3.0. Test Measurements Figure 3.1 A and B. Separate pressure sensors shall be
The objective of the parameter measurements is to accurately connected to each port. Provisions should be made for
and reproducibly measure the thermal performance of the air purging all pressure connections to keep them free of
cooled condenser for comparison against the guarantee condensate.
provided by the manufacturer. The primary parameters to be 3.1.4 Pressure sensors shall have a calibrated accuracy
measured are: of 35 Pa (0.005 psia) or less. Steam temperature
 condenser pressure measurements should be taken in the thermal wells in the
 steam quality (content) vicinity of the pressure measurements.
 condensate flow rate
 condensate tank water level
 inlet air dry bulb temperature
 barometric pressure
 fan motor input power
 wind speed
It is recommended that the following parameters be acquired
for reference purposes:
 exhaust steam temperature
 condensate temperature
 air removal rate
 wind direction
3.1 Condenser Pressure
3.1.1 Condenser pressure should be measured at the
boundary of supply of the condenser manufacturer unless
another location is agreed upon by the parties to the test.
Four measurement points per inlet are required unless the

-3-
between the parties to the test. If used, the ultrasonic flow
meter shall be calibrated in a pipe corresponding to the
diameter and wall thickness of the pipe on which it will be
installed. The calibration range shall cover the Reynolds
number expected for the pipe at the design flow. The
installation location shall have at least 16 pipe diameters
of undisturbed length upstream of the meter and 4 pipe
diameters of undisturbed length downstream of the meter.
Readings shall be taken at 6 positions 30 apart around
the circumference of the pipe. These readings shall be
averaged to obtain the condensate flow. If the high and
low readings differ by more than 2 percent, the cause shall
be investigated. Use of an ultrasonic flow meter will
result in a higher uncertainty for the condensate flow
measurement than if an inline flow element is used.
3.2 Steam Quality (Steam Content) 3.3.3 Steam flow to the condenser shall be calculated by
Since the steam at the condenser inlet will be in the wet steam a mass balance around the condenser with consideration
range, measurement of the temperature and pressure is of any liquid flow streams upstream of the measurement
insufficient to determine is enthalpy. At present there is no point and the change in level of the condensate tank
acceptable method for measuring the quality directly, thus the during test. Design values may be used for those flow
parties to the test must agree on a method for calculating this streams representing less than 3 percent of the design
value. Some suggested methods are: steam flow.
a) Energy balance – If the temperature, pressure and flow
3.4 Inlet Air Temperature This code recommends the
rate of all steam flows into the steam turbine are
characterization of the performance of the air cooled condenser
measured, as well as turbine power output and generator
based on the inlet air temperature as opposed to the ambient
losses, it is possible to determine the enthalpy of the
air temperature. This recommendation is based on the
exhaust steam by an energy balance. This method
following considerations:
requires many measurements which are unlikely to be
 The results tend to be much more reproducible when
available unless a concurrent steam turbine test is being
the inlet air temperature is used as the basis for
performed. If this method is used, the values of the steam
thermal evaluation. Air cooled condensers are
flows should be verified performing a mass balance
subject to recirculation (the re-entrainment of he
around the condenser and steam turbine.
exhaust air into the air inlet) and interference from
b) Cycle Model-With sufficient information from the other heat sources in the area. Slight changes in the
steam turbine manufacturer, it is possible to construct a wind speed or direction can greatly affect the amount
cycle model for the steam turbine. Such a model can then of this recirculation and interference, which greatly
be used to construct correction curves for steam quality increases the scatter in the test results if performance
based on measured cycle variables. Such a cycle model is based on ambient air.
should be verified using the steam turbine manufacturer’s  The test result tends to be a fairer representation of
thermal kit. the performance of the condenser. While the amount
of recirculation is influenced by the condenser design
3.3 Condensate Flow chosen by the manufacturer, it is also governed by the
3.3.1 The condensate flow shall be measured sitting of the condenser. Other structures or uneven
downstream of the condensate pumps. The recommended topography in the vicinity can influence the amount
devices for measuring condensate flow are differential of recirculation.
pressure producers (orifice plates, flow nozzles, venturis).  Ambient temperature in a plant can be difficult to
The calibration records and construction details of the measure. It is difficult to find a location that is not
flow element shall be made available to the parties to the influenced by other heat sources. Inlet temperatures
test. The pressure transmitter reading the differential to other equipment such as turbines or broilers, are
pressure shall be calibrated prior to the test to an accuracy greatly influenced by heat sources in their
of not more than 0.25 percent of the expected differential surroundings. Temperature measurements at these
at the design flow. The installation of the flow element locations should never be used to characterize air
shall conform to the specifications of ASME PTC 19.5 cooled condenser performance.
Flow Measurement. The flow element, as installed, shall 3.4.1 Inlet dry bulb temperature shall be measured with a
have an accuracy of not more than 0.75 percent. four wire RTD with a calibrated accuracy of 0.05oC
3.3.2 A time-of-flight ultrasonic flow meter may be (0.1oF). These sensors shall be placed at the
used to measure the condensate flow rate by agreement

-4-
discharge of the fans, one-third of the distance from relative to grade corresponding to the smaller of:
the fan tip to the hub as measured from the fan tip. 1) 10m (33 ft),
3.4.2 At least 12 dry bulb sensors will be deployed. An 2) half the air inlet height
equal number of sensors will be deployed on all fans. The
If the wind speed is measured at a height other than half the air
number of inlet dry bulb sensors will be determined by the
inlet height, the measured wind speed shall be corrected to the
following schedule:
mid point of the air inlet height using the equation:
a) For single row condensers, at least 2 sensors will be z t 0. 2
deployed on axis perpendicular to the steam duct. u c  u( ) 3.2
b) For all other condensers, one sensor per fan will be zm
deployed on the side nearest the outside wall. where
uc =
wind speed corrected to the midpoint of the air
inlet
3.5 Barometric Pressure Barometric pressure will be u = measured wind speed
measured once per hour at grade level with a calibrated zm = vertical height of the wind speed station
accuracy of 200 Pa (0.03 psia). zt = vertical height of the midpoint of the air inlet
3.6 Fan Motor Input Power The fan motor input power
shall be determined by direct measurement of kilowatt input or Section 4.0. Evaluation of Test
by measurement of voltage, current, and power factor as Purpose - This section of code develops a method for
described in ASME PTC 19.6 Electrical Measurements in evaluation of the performance of an air cooled condenser from
Power Circuits. Measurement of the total input to all fan test data based on performance curves provided by the
motors is acceptable if a measurement location isolated from manufacturer.
other equipment can be established. The fan power 4.1 Manufacturer’s Data
measurement device shall have an accuracy of not more than
three percent. If the fan motor input power is not measured at 4.1.1 The manufacturer should submit a family of
the boundary of supply a correction shall be applied to account performance curves consisting of a minimum of 5 curves
for any line losses between the measurement point and the representing condenser pressure as function of dry bulb
boundary of supply. The variable frequency drive (VFD), if temperature for steam flow rates of 80, 90, 100, 110, and
present, should be taken out of service during the test. If the 120 percent of design steam flow rate. One curve shall be
VFD does not have a bypass or if the test must be conducted provided for each steam flow rate. Each curve shall be
with the VFD in service, the speed must be set to 100% and presented with dry bulb temperature as the abscissa versus
one of the following approaches must be taken for the condensing steam pressure as the ordinate. Graphical
evaluation of the fan motor power: scaling shall be incremented so as to provide a minimum
a) The power on the line side of the VFD is measured. resolution of 300 Pa (0.1 in. HgA) and not more than 3000
The VFD manufacturer’s guaranteed voltage drop across Pa/2.5 cm; (1.0 in. HgA/inch) for pressure and 0.2C
the unit used to calculate the power input into the motor. (0.5F) and 0.1C/mm (5F/inch) for dry bulb
temperature. The curves shall be based on constant fan
b) Some speed controllers display power delivered to the
pitch and steam quality. An example performance curve
motor. If agreeable to the test representatives, this may be
is presented in Figure 4.0.
used for the evaluation of the fan motor power.
c) The fan motor power is measured with a true RMS
wattmeter on the load size of the VFD and the motor
efficiency is evaluated at the reduced power loading. The
wattmeter must have a sampling frequency that is at least
twice the highest frequency component in the wave being
sampled. Switching frequencies of pulsed width
modulation drives can range from 2 kHz to 15 kHz. In
practice, a low-pass filter must be connected between the
measurement location (e.g. switch gear) and the meter.
The cut-off frequency of low pass filter should correspond
to the sampling frequency of the digital meter.
It should be noted that the use of the VFD will lower the
fan motor efficiency and, if the variable speed drive is not
inside the boundary of supply, a correction should be
made for the reduced efficiency of the motor.

3.7 Wind Speed Wind speed shall be measured with a


calibrated anemometer, in an unobstructed location at a height

-5-
4.2.1 Predicted Steam Mass Flow Rate-The predicted
Figure 4.0 ACC Performance Curve
condensing steam pressure at the measured inlet dry bulb
6.00
temperature shall be read from each of the performance
curves. The resulting values shall be used to generate a
5.50 plot of condensing steam pressure versus steam mass flow
rate. The curve so generated is used to read the steam
5.00
flow at the actual condensing steam pressure. This is the
ACC Condensing Pressure ("HgA)

4.50 predicted steam mass flow rate, ms,pred. This is illustrated


in Figure 4.1
4.00

3.50 Figure 4.1

3.00 Cross Plot at Test Dry Bulb

2.50 5.20

5.00
2.00
4.80

ACC Condensing Pressure ("HgA)


1.50
4.60
1.00
4.40
45 50 55 60 65 70 75 80 85
Inlet Air Dry Bulb Temperature (F) 4.20
120% Flow 110% Flow 100% Flow 90% Flow 80% Flow
4.00

3.80
4.1.2 A table of values defining the curves should also be
3.60
provided. The table of values shall be sufficient to allow
for the development of interpolation and curve fit 3.40
equations that can be used in place of reading values off 3.20
the curves during performance test. A curve fit may also
be used if the curves are provided in a different form than 3.00
80% 85% 90% 95% 100% 105% 110% 115% 120%
that specified in the previous paragraph. Use of either the
Predicted Steam Mass Flow Rate (% Design)
curve or the table of values should provide the same result
and either form of manufacturer provided data is
acceptable as the basis for capability calculations by the 4.2.2 Corrected Test Steam Mass Flow Rate-The
testing agent. corrected test steam mass flow rate is calculated by
m sc,T  m s ,T Fc 4-2
4.1.3 The design conditions including steam mass flow
rate, steam pressure, and steam quality, fan motor input where
power, barometric pressure and inlet dry bulb temperature m s ,T = the measured steam mass flow rate at test,
shall be printed on the curves. The effective area of the
condenser and the volumetric air flow at design conditions kg/s(lbm/hr)
shall also be included.
Fc = fxfpffp

4.2 Calculation of Condenser Capability - The condenser


capability will be calculated by: where
m sc,T fx = correction factor for steam quality,
C x 100 4-1 dimensionless
m s , P fp = correction factor for barometric pressure,
dimensionless
where ffp = correction for fan power, dimensionless
C = condenser capability, percent
m c s ,T = corrected test mass flow of steam, kg/s The correction factor for steam quality is calculated by
(lbm/hr)
XT
m s , P = predicted mass flow rate of steam at fx  4-3
XG
test conditions, kg/s (lbm/hr)
where

-6-
XT = steam quality at test conditions, kg/kg determine the accuracy of the test result. It is sometimes used
(lbm/lbm) as a test tolerance but this is a matter of contractual agreement
XG = steam quality at guarantee conditions, kg/kg between the parties to the test.
(lbm/lbm) The following major uncertainty components are addressed in
The correction factor for barometric pressure, fp, shall be the ASME PTC 19-1 Test Uncertainty (1988) test code:
calculated by: 1. Systematic Uncertainty
2. Random Uncertainty
1
P P mk  3. Spatial Uncertainty
f p   T (1  )  ( T )  4-4 4. Sensitivity Coefficients
 PG PG  An overview of the uncertainty components is provided below.
where Systematic Uncertainty. Systematic uncertainties are
PT = test barometric pressure, kPa (psia) approximations of the fixed errors inherent in a measurement.
PG = design barometric pressure, kPa (psia) These errors are also called bias errors. Systematic errors are
 = a constant condenser characteristic factor typically the largest source of error in a condenser performance
based on design information, this factor can be test. These uncertainties are primarily a result of the intrinsic
calculated based on the design information as accuracy of the instruments, and the calibration procedures
specified in Appendix B. employed. Systematic uncertainties are estimated from review
mk = 0.45, unless otherwise specified by the and analysis of the instrument manufacturer’s specifications,
manufacturer independent parameter measurement by additional means, and
examination of typical calibration data.
Spatial Systematic Uncertainty. Spatial systematic
The correction factor for fan power, ffp, can be calculated
uncertainty errors occur during the measurement of a spatially
by:
diverse sample. Spatial error is defined as the difference
1  m k 1  1
between the true average value of a parameter and the average
 WTc 3   WTc
 3  produced by an array of instruments used to measure the

f fp    (1   )     4-5
   parameter. Spatial errors for a condenser performance test
 WG    WG   occur in the measurement of inlet dry bulb temperature and
 
condenser pressure measured at single inlet. Spatial errors also
where
occur during the measurement of condensate flow if an
WTc = test fan motor input power corrected for inlet ultrasonic flow meter is used to measure the condensate flow.
Spatial uncertainties are calculated from the average of local
air conditions, kW
measurements in space. Thus they are treated as constant for a
WG = guarantee fan motor input power, kW given test period but may vary from one test period to another.
For example, the spatial variation of the dry bulb temperature
The corrected fan motor power can be calculated by:
change from test to test due to changes in the wind speed and
direction resulting in changes in recirculation and interference.
 
WTc   G WT 4-6 Random Uncertainty. Random uncertainty is also referred to
 T  as precision uncertainty. Random errors are evident by the
scatter of data that results from repeated measurements of
where transient data (e.g. the variability in a dry bulb temperature
T = density of inlet air at test conditions, reading at a specific location). Precision errors can be reduced
by increasing the number of measurement repetitions or by
kg/m3(lbm/ft3) selecting data intervals with greater stability. Although it is
G = density of inlet air at guarantee conditions, possible to evaluate random uncertainty for a given test
interval for each measured parameter, a more meaningful result
kg/m3(lbm/ft3) is obtained by basing the random uncertainty on the variation
of the condenser capability for the test periods.
The fan motor input power shall be corrected for any line
losses between the measurement point and the boundary Sensitivity Factors. Sensitivity factors relate a change in an
of supply for the condenser manufacturer. independent measured parameter to the resulting change in test
result. These sensitivities may be calculated as the partial
Section 5.0. TEST UNCERTAINTY derivative of the test result with respect to the parameter of
The purpose of the pretest uncertainty analysis is to predict the interest but it is usually more convenient to calculate the
uncertainty of the test result and to aid in the specification of sensitivity factor numerically as the ratio of the change in test
test instrumentation that will achieve the test objective. The result to the change in the test parameter. Sensitivity factors
pretest uncertainty analysis should be documented in the test are used to combine the uncertainties for each test parameter
plan. The purpose of a post-test uncertainty analysis is to into the uncertainty in the overall test results.

-7-
APPENDIX A

Basic Equations

Q  UATlm A-1 where


Xs,i = quality of inlet steam
where
hs = enthalpy of saturated steam at the condenser inlet
Q = heat duty
pressure
U = overall heat transfer coefficient
hl = enthalpy of saturated liquid at the condenser inlet
A = air side heat transfer area for the condenser
pressure
Tlm = log mean temperature difference

The mass flow rate of the inlet air can be calculated by:
The log mean temperature difference, Tlm, is defined as:
m a  Va ,i  a ,i A-5
(Ts  Ta,i )  (Ts  Ta,o ) Ta,o  Ta,i
Tlm  
 T  Ta,i   T  Ta,i  where
ln  s 
 ln  s 

T
 s  Ta, o  T
 s  Ta, o  Va , i = volumetric air flow
A-2
where a,I = air density at inlet conditions
Ts = condensing steam temperature
Ta,i = inlet dry-bulb temperature For constant pitch performance curves, the volumetric air flow
Ta,o = outlet dry-bulb temperature rate is assumed to be independent of air temperature and
pressure. The outlet air temperature is calculated by:
The heat duty for the condenser is:
A-3 Q
Ta , o  Ta , i  A-6
Q  m s (hs , i  hc , o )  m a c p , a (Ta , o  Ta , o ) m a c p , a
where

m s = mass flow rate of steam From equation A-1

hs,i = enthalpy of inlet steam


Q
hc,o = enthalpy of liquid condensate U A-7
ATlm
m a = mass flow rate of air

cp,a = heat capacity of air


and from equation A-1,A-2 and A-3;

The enthalpy of the inlet steam can be calculated by:


hs ,i  X s ,i hs  (1  X s ,i )hl A-4

-8-
 UA  NTU G
e ( ) 1  A-18
 m c  e NTU G  1
 a p,a 
Q  m a c p , a (Ts  Ta , i ) A-8
 UA  T NTU T
e ( ) 1   A-19
 m c  G NTU G
 a p , a 
The number of heat transfer units is defined as:
UA From equations A-4 and A-13,
NTU  A-9
m a c p , a QT T m a ,T
 A-20
and is equivalent to: QG  G m a ,G
Ta , o  Ta , i
NTU  A-10
Tlm From equation A-10
Therefore NTUT U T m a ,G
 A-21
e NTU  1 NTU G U G m a ,T
Q  m a c p , a (Ts  Ta , i ) NTU
e A-11

Since
The effectiveness of the condenser is defined as:
m a   aVa A-22
Ta , o  Ta ,i
 A-12 where
Ts  Ta ,i
Va = the volumetric flow rate of air
and is equivalent to
a = the density of air
Tlm
  NTU A-13 NTU T U T  a , i , GVa , i , G
Ts  Ta , i  A-23
NTU G U G  a , i ,T Va , i ,T
For the case of isothermal condensation:

  1  e  NTU A-14
The air side heat transfer coefficient, a, is a function of
The ratio of the test to guarantee effectiveness is: Reynolds number;

 a  Re m   qVa 
A-15 mk
k
A-24
 T  1  e  NTU T  1  e  ( NTU T  NTU G )
   1  Since the overall heat transfer resistance is dominated by the
 G  1  e  NTU G  e NTU G  1 air side resistance
For small values of (-0.15<<0.15) mk mk
U T  T   a ,i ,T   Va ,i ,T 
 
 
e   1  
A-25
A-16 U G  G   a ,i ,G   V 
 a , i , G 

Therefore, Therefore,
A-17 1 m k 1 m k
NTU T   a ,i ,G   Va ,i ,G 
 
 A-26
T
 1
NTU T  NTU G NTU NTU T
 1  NTU G
NTU
 NTU G NTU G   a ,i ,T  V
 a , i ,T 

G e NTU
1 e G
 1 NTU G e 1 G G

From equations A-19,A-20 and A-26:


Defining

-9-
A-27 From the ideal gas law

 V  
1mk 1mk
   Va ,i ,G  PM
QT
 a ,i ,T a ,i ,T 1     a ,i ,G      A-31
QG  a ,i ,G Va ,i ,G     V   RTA
  a ,i ,T   a ,i ,T  
where
From fan affinity laws
P = absolute pressure, Pa (psia)
1
VT  WTc  3 M = molecular weight of gas, 28.945 kg/kg-mole (lbm/lbm-
 
VG  WG 
A-28
mole)
R = universal gas constant,
Pa m3 psi ft 3
where 3
8.3143x10 kg  mole  K (10.73 )
WG = the fan power at guarantee conditions lbm  mole  R

WTc = the test fan power corrected to design temperature and TA = absolute temperature ,K (R)

pressure
The change in volumetric flow with inlet temperature is

Substituting in equation A-27 yields: included in the performance curves. Therefore, the correction

A-29 factor for barometric pressure is


1
m s ,G QG Pa ,G  
1 mk
1  1 m k
m k 1
 P 
QT  a ,i ,T  WTc  3    a ,i ,G   WT  3  f p 
c   1     a ,G   A-32
P 

QG  a ,i ,G
  1       

   m s ,T QT Pa ,T 
  a ,T  

 G
W
  a , i ,T   WG 

  where
The correction factor for fan power is: Pa,G = atmospheric pressure at guarantee
A-30 Pa,T = atmospheric pressure at test condition
1
1
 m k 1

m s , G QG  WTc  3   WTc  3 
f fp     1     
m s ,T QT  WG    WG  
 

-10-
APPENDIX B

Calculation of Condenser Characteristics

1. Calculate guarantee heat transfer rate using 5. Calculate log mean temperature difference using
equation A-4 equation A-2
Q  m s (hs , i  hc , o ) B-1 Ta ,o  Ta ,i
Tlm  B-5
 Ts  Ta ,i 
ln 
2. Calculate the inlet air density at guarantee

conditions using equation A-30  Ts  Ta ,o 
PM 6. Calculate NTU using equation A-11
 B-2
RTA Ta , o  Ta , i
NTU  B-6
3. Calculate the air mass flow rate using equation A-5 Tlm
m a  Va , i  a , i B-3 7. Calculate the heat transfer characteristic using

4. Calculate outlet air temperature using equation A-7 equation A-18


NTU G
Ta , o  Ta , i 
Q
B-4  B-7

ma c p , a e NTU G  1

-11-
APPENDIX C

Example Calculations

Design and Test Data


Design and test conditions for the air cooled condenser are presented in Table C.1

Parameter Units Design Test


Steam flow lbm/hr 1,250,000 1,250,834
Steam quality % 94 94.6
Condenser pressure inHg 3.00 3.86
Inlet air temperature ºF 65.0 75.49
Atmospheric pressure inHg 28.85 28.56
Fan power hp 6115 5634
Wind speed mph 10.0 8.6
Condensate outlet temperature ºF 113.0 121.2
7
Volumetric air flow acfm 3.775x10 ----
Calculated Values
Condensing steam temperature ºF 115.0 124.1
Enthalpy of vapor at condenser pressure Btu/lbm 1111.1 1114.9
Enthalpy of liquid at condenser pressure Btu/lbm 83.0 92.1
Enthalpy of condensing steam Btu/lbm 1049.8 1060.0
Enthalpy of condensate at outlet temperature Btu/lbm 81.0 89.2

In this example, the change in the level of the condensate did not change during the test period. Therefore, the steam flow
to the condenser is equivalent the condensate flow. Condensing steam temperature and specific enthalpy values for steam
and liquid water were calculated by using steam table software.

-12-
Performance Curves
The performance curves supplied by the manufacturer are presented in Figure C.1 and Table C.2

Table C.2 Performance Curves


Condensing Pressure InHgA
120% 110% 100% 90% 80%
Air Temp Flow Flow Flow Flow Flow
85.0 6.39 5.68 5.05 4.48 3.96
80.0 5.65 5.02 4.44 3.92 3.48
75.0 4.98 4.42 3.90 3.44 3.03
70.0 4.39 3.89 3.42 3.02 2.62
65.0 3.87 3.41 3.00 2.63 2.30
60.0 3.40 2.98 2.63 2.30 2.01
55.0 2.99 2.62 2.30 2.01 1.74
50.0 2.63 2.31 2.02 1.75 1.51
45.0 2.31 2.02 1.77 1.53 1.32
75.5 5.05 4.48 3.95 3.49 3.07

Digital data for condenser pressure as function of dry bulb temperature for steam flow rates between 80 and 120 percent of the design
flow rate was provided by the manufacturer. The predicted condenser pressure at the test inlet air temperature of 75.5ºF for each flow
rate was calculated by nonlinear interpolation.

Predicted Steam Flow at Test Conditions


The data required for calculation of the predicted flow at test conditions are summarized in Table C.3 illustrated in Figure C.1.

Table C.3 Condenser Pressure at Test Conditions

Steam Flow Condenser Pressure

% of Guarantee inHg
80% 3.07
90% 3.49
100% 3.95
110% 4.48
120% 5.05
98.01% 3.86

-13-
Figure C.1 Cross Plot at Test Dry Bulb Temperature

Cross Plot at Test Dry Bulb

ACC Condensing Pressure ("HgA) 5.5

5.0

4.5

4.0

3.5

3.0
80% 90% 100% 110% 120%
Predicted Steam Mass Flow Rate (% Design)

The predicted percentage steam flow rate at test pressure was calculated of 3.86 inHg was calculated by nonlinear interpolation of
from the data in Table C.3. The predicted steam flow rate at test conditions is
m s , P  0.9801 x1,250,000  1,225,069 lbm / hr .

Corrections to Guarantee Conditions


Calculation of Condenser Characteristic

1. Calculate guarantee heat transfer rate using equation B-1


Q  m s (hs , i  hc , o )

Q  1.25x106 (1049.8  83.0)  1.208 x109 Btu / hr


2. Calculate the inlet air density at guarantee conditions using equation B-2
PM

RTA
28.85 x.0.491x 28.945
 G   a ,i   0.0729lbm / ft 3
10.73x (65.0  459.7)
3. Calculate the air mass flow rate using equation B-3

m a  Va , i  a , i

m a  3.775 x10 7 x 0.0729 x 60  1.6508 x108 lbm / hr

-14-
4. Calculate outlet air temperature using equation B-4
Q
Ta , o  Ta , i 
m a c p , a

1.208 x109
Ta ,o  65.0   95.5
1.65 x108 x 0.24
5. Calculate log mean temperature difference using equation B-5

Ta,o  Ta ,i
Tlm 
 T T 
ln s a,i 
 Ts  Ta,o 

95.5  65.0
Tlm   32.4
 115.0  65.0 
ln 
 115.0  95.5 

6. Calculate NTU using equation B-6


Ta , o  Ta , i
NTU 
Tlm
95.5  65.5
NTU   0.9420
32.4

7. Calculate the heat transfer characteristic using equation B-7


NTU G

e NTU G  1
0.942
  0.6019
e 0.942  1

Correction to Guarantee Conditions


1. Calculate correction for steam quality using equation 4.4
XT
fx 
XG
94.6
fx   1.007
94.0
2. Calculate correction for barometric pressure using equation 4.5
1
P P mk 
f p   T (1   )   ( T ) 
 PG PG 

-15-
1
 28.56 28.56 0.45 
fp   (1  0.6019)  0.6019( )   1.007
 28.85 28.85 
3. Calculate air inlet density at test conditions using equation B-4
PM

RTA
28.56 x.0.491x 28.945
T   0.0707lbm / ft 3
10.73x (75.5  459.7)
4. Calculate corrected fan power using equation 4.7
T
WTc  W
G T
0.0707
WTc  5634  5464 hp
0.729
5. Calculate fan power correction using equation 4.6

1  m k 1  1
 WT  3 
c  WTc  3 
f fp   (1   )     
 W 
 G 
W  G 
 
1
1
 0.451

 5464  3   5464  3 
f fp    (1  0 . 6019 )  0 . 6019     1.012
 6115    6115  
6. Calculate test steam flow correction factor using equation 4.3
Fc  f x f p f fp

Fc  1.007 x1.007 x1.012  1.025


7. Calculation of corrected condenser steam flow using equation 4.2

m sc,T  m s ,T Fc

m sc,T  1,250,834 x1.025  1,263,931 lbm / hr

Calculation of Condenser Capability

Calculate condenser capability using equation 4.1

m sc,T
C x 100
m s , P

1,263,931
C x100  103.2%
1,225,069

-16-
APPENDIX D

Uncertainty Analysis Example


Sensitivity Factors

Using the data in the example in Appendix C, the sensitivity


factors for each of the test parameters were calculated by The systematic uncertainty calculations are summarized in
incrementally changing the test parameters about average Table D-2.
test result.
Condenser pressure and inlet air temperature are measured
Cap Cap x 1 / 2 x  Cap x 1 / 2 x
 par   by an array of instruments which are averaged. The average
x x value for such parameters is subject to spatial bias. The
spatial systematic for condenser pressure is calculated by:
where tn 1S Pcond , spatial
BPcond , spatial 
par = sensitivity factor of capability to n
parameter, par
where
X = average value for a test parameter, par
tn-1 = Student’s t value for 95% confidence
Cap = condenser capability
and n-1 degrees of freedom
x = incremental change in a test SPcond,spatial = Standard deviation of the time averaged
parameter, par condenser pressure readings
 Cap = incremental change in condenser n = number of measurement stations
capability
Cap x 1 / 2 x = capability with test parameter, par, set The standard deviation of the condenser pressure
to x +1/2x measurements is calculated by:
Cap x 1 / 2 x = capability with test parameter, par, set

i 1, n
( Pcond , avg  Pcond ,i )2
to x -1/2par S Pcond, spatial 
A data reduction spreadsheet was used to generate capability n
values at the incremented test parameter values. Table D-1
summarizes the result of the sensitivity analysis. where
Pcond,avg = average condenser pressure for the test
The systematic uncertainty, in terms of condenser capability, Pcond,i = average condenser pressure at
is calculated by multiplying the parameter uncertainty by the measurement station i
sensitivity factor :

B Cpar   par B par For four condenser pressure measurements, n=4 and
t3=3.182. The standard deviation of the condenser pressure
where measurements was 0.020 inHg.

3.182 * 0.020
B Cpar = parameter uncertainty in terms of BPcond , spatial   0.032 inHg
condenser capability 4
Bpar = parameter uncertainty, parameter units
The total systematic uncertainty for condenser pressure was
The overall systematic uncertainty for the test is calculated calculated by the square root of the sum of the squares of the
the square root of the sum of the squares of the parameter systematic uncertainty of the pressure transmitter and the
uncertainties: spatial systematic uncertainty.

0.0152  0.0322
 BPcond  BPcond ,inst  BPcond   0.04inHg
2 2
B par 1, m
B Cpar

-17-
Table D-1 Sensitivity Factors
Increment Capability@ Capability@ Delta Sensitivity
Parameter Units Average ½ x x+1/2x x=1/2x Capability par
Steam Flow 1bm/hr 1,252,834 10000 104.57 102.91 1.66 8.30E-05
Steam Enthalpy Btu/hr 1,049.8 10 104.82 102.66 2.15 0.108
Condenser Pressure InHg 3.86 0.1 101.49 106.11 -4.62 23.100
Inlet Air Temperature F 75.49 1 106.99 101.54 5.45 2.725
Barometric Pressure InHg 28.56 0.1 103.58 103.9 -0.32 -1.600
Fan Motor Power Hp 5,634 100 103.34 104.16 -0.82 -4.10E-03

The spatial systematic uncertainty and the total where


systematic uncertainty for inlet air temperature was
calculated in a similar manner. S = the standard deviation of the test capability of the
t n 1STair , spatial tests
BTair , spatial  m = number of tests.
n
The total uncertainty for the series of tests is calculated For this series of tests, the standard deviation of the
by: capability for six tests was 2.32 percent. The overall
uncertainty in the capability for the test series is:
2S
U  B2 
m 2( 2.32)
U  ( 2.70) 2   3.29 percent
6

Table D-2 Systematic Uncertainty Table


Instrumental Spatial Systematic Capability
Parameter Units Average Uncertainty Uncertainty Uncertainty Sensitivity Uncertainty
Steam Flow 1bm/hr 1,252,834 9647 0 9647 8.300E-05 0.80
Steam Enthalpy Btu/hr 1,049.8 NA NA NA 0.108
Condenser Pressure InHg 3.86 0.015 0.032 0.04 -23.100 0.82
Inlet Air Temperature F 75.49 0.5 0.70 0.86 2.725 2.35
Barometric Pressure InHg 28.56 0.03 0 0.03 -1.600 0.05
Fan Motor Power Hp 5,634 169.0 0 169.02 -4.100E-03 0.69

Capability % 103.74 2.70

-18-
COOLING TECHNOLOGY INSTITUTE
P.O. Box 73383 Houston, Texas 77273 281.583. 4087 FAX 281.537.1721
Printed in U.S.A.

-19-

You might also like