Professional Documents
Culture Documents
27.0-1
June 2006
Sheet 1091
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.0-2 23
Magnum Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . . . . . . . 27.1-1
Magnum DS Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . . . . 27.1-5 24
Magnum SB Insulated Case Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . 27.1-10
Magnum IEC Rated Air Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1-12
DSII Power Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.2-1
25
Specifications
See Eaton’s Cutler-Hammer Product Specification Guide on enclosed CD-ROM: 26
1995 CSI Format: Power Circuit Breakers — Magnum DS . . . . Section 16475
Power Circuit Breakers — DSII. . . . . . . . . . . Section 16475 27
Insulated Case Circuit Breakers
— Magnum SB . . . . . . . . . . . . . . . . . . . . . . Section 16475
Microprocessor Trip Units . . . . . . . . . . . . . . Section 16904
28
2004 CSI Format: Power Circuit Breakers — Magnum DS . . . . Section 26 28 11
Power Circuit Breakers — DSII. . . . . . . . . . . Section 26 28 11 29
Insulated Case Circuit Breakers
— Magnum SB . . . . . . . . . . . . . . . . . . . . . . Section 26 28 11 30
Microprocessor Trip Units . . . . . . . . . . . . . . Section 26 28 50
31
32
33
34
35
36
37
38
39
40
41
42
43
Low Voltage Circuit Breakers
39 UL 1066, IEEE Standard C37.13 UL 489, NEMA AB-1 UL 489, NEMA AB-1
40
41
42
43
27
Magnum Low Voltage Power Circuit Breakers
for Global Application
28
Magnum Low Voltage Power Circuit Breakers enable
comprehensive solutions to meet and exceed the unique
and wide-ranging requirements of today’s global power 29
distribution systems. This powerful circuit breaker offering Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated
is designed for ultimate custom configuration and applica- for Switchgear Applications
tion flexibility, with the needs of the power distribution 30
equipment user and the electrical equipment manufacturer
in mind. Magnum SB Low Voltage Insulated Case Circuit Breakers for
Switchboard Applications 31
■ Up to 635 Vac.
■ 200 to 6000 A continuous. 32
■ 50 to 150 kA interrupting.
33
34
35
36
Magnum SB Low Voltage Insulated Case Circuit Breaker Family for
Switchboard Applications
37
38
39
40
41
42
43
40
41
42
43
High Technology Microprocessor-Based Digitrip RMS 1150+ Trip
Units are Available With Advanced Features Like Programmable
Overcurrent Settings, Power Metering, Power Quality and
Communications
Breaker Features on
22
Front Cover
The controls and indicators are func- 23
tionally grouped on the breaker face-
plate to optimize the human interface,
visibility, and ease of use. For maxi- 24
mum safety, a modern, through-the-
door design permits access to the
breaker levering system, trip unit, 25
controls and indicators with the
door closed.
Mechanical Trip Flag Pop-out 26
Indicator (Optional) — Red
Accessory Viewing Windows for: 27
❑ Shunt Trip Attachment (STA)
41
42
Through-the-Door Design for Human
Interface with the Breaker Compartment
Door Closed, for Example, Manually
43
Charging the Stored Energy Springs
34 ❑ CONNECT — Red
❑ TEST — Yellow
❑ DISCONNECT — Green
35
43 Magnum Drawout Breaker Rear View Showing Primary Disconnecting
Finger Clusters Mounted on the Breaker for Ease of Inspection
32
33
34
35
36
Magnum DS Low Voltage Power Magnum MDSX Current Limiting Magnum MDSL Current Limiting 37
Circuit Breakers have high withstand Power Circuit Breakers have fast open- Power Circuit Breakers have integral
ratings from 42 kA to 100 kA to ing contacts to provide interrupting current limiters to provide interrupting
provide for maximum system ratings up to 200 kA at 480 Vac ratings of 200 kA at 600 Vac. 38
coordination and selectivity. without fuses.
39
40
41
42
43
29
MDSL Based on Current Based on Current Up to 200 kA Lower Energy at Fault Levels Blown Limiters Require
Current Limiting — Limiter Selected Limiter Selected at 600 Vac in the Current Limiting Replacement and Inventory
30 Integral Current
Limiters with Trip Unit
and Trip Unit
Settings
Range of Current Limiter Operating Watts Loss
is Higher than Fuse-less
Instantaneous Off Breakers
31 All Magnum Breakers Per Magnum Trip Unit Instanta- Per Magnum May be Reduced by Per Magnum Breaker
with Trip Unit Instantaneous On Breaker Type neous Settings Breaker Type Employing Trip Unit: Type Applied
Applied Affect System Applied Ground Fault Settings,
Coordination and
32 Continuity
Zone Selective Interlocking,
ARMs Technologies
33 Magnum MDS High Withstand Magnum MDSX Fuseless Magnum MDSL Interruption Up to
Breakers for Maximum Coordination Interruption Up to 200 kA Current 200 kA with Integral Current Limiters
34 Magnum MDS breakers are designed Limiting Performance Magnum MDSL breakers with integral
to hold in and carry their rated short Magnum MDSX breakers provide new current limiters provide interruption
time withstand current up to 0.5 fuseless technology with interruption ratings up to 200 kA at 600 Vac. MDSL
35 seconds, the maximum trip unit
short time delay setting. System
ratings up to 200 kA at 508 Vac. is especially effective in reducing
energy let-through and arc flash at the
The interruption performance
coordination is maximized when the is current limiting when the fault highest fault currents and those that
36 instantaneous trip unit settings are
either turned off or set high enough
currents exceeds the withstand rating. fall within the current limiting range
of the current limiter. Interruption is
The self-protecting fast opening
to facilitate coordination with other reverse loop contacts quickly open clean and efficient with most of the arc
37 protective devices on the circuit. clearing the fault in approximately display contained within the current
1/4 cycle, reducing energy let-through limiter. A wide array of current limiter
Energy let-through and arc flash
and arc flash energy before the ratings are available for selection and
energy to the downstream circuit can
38 be significantly reduced by employing breaker mechanism opens to reset application with the breaker current
the contacts. sensor ratings and trip unit settings
instantaneous trip unit settings as well
to provide for system coordination.
as ground fault and zone interlocking. Below their withstand rating, MDSX
39 However, the desire to reduce arc breakers coordinate like normal construc- When fault currents fall below the
flash may have to be balanced with tion MDS breakers. Arc flash levels to the current limiting range of the limiter,
the necessity to maintain system downstream circuit can be reduced by like those characteristic of arcing
40 coordination and continuity. This is employing the trip unit instantaneous faults, energy let thru and arc flash
especially true at the low fault levels settings as well as ground fault, zone energy can increase. In this range,
characteristic of arcing faults, because interlocking, and ARMs features. a lower rated current limiter may
41 the trip unit instantaneous trip setting be applied, but considerations must
may have to be set as low as the MDSX breakers have the same compact be given to nuisance blowing of the
minimum setting, which could footprint as standard MDS breakers to limiter and system coordination.
42 cause nuisance tripping. facilitate use in compact enclosures.
MDSL breakers can also employ trip
The ARMs Technologies Trip Unit MDSX improves overall operating sys- unit instantaneous settings as well as
43 Option can be employed to optimize tem continuity, convenience, and life ground fault, zone interlocking, and
arc flash reduction during system time costs by eliminating fuse trucks, ARMs Technologies features to reduce
start-up and maintenance operations. blown limiter change outs, replacement arc flash levels. Physically, they are 6
limiter inventories and the higher oper- inches (152.4 mm) deeper than stan-
ating watts loss associated with fuses. dard construction Magnum breakers.
23
24
25
26
27
Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications
Table 27.1-2. Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers
28
Frame Breaker Frame rms Symmetrical Current Ratings kA 50/60 Hz Short Time Fixed Internal Available Current Sensor &
Amperes Type Type Interrupting at Interrupting at Interrupting at Withstand
Rating
Instantaneous
Trip
Rating Plugs for Digitrip
RMS Trip Unit (Establishes
29
254 Vac 508 Vac 635 Vac
Breaker In rating)
MDSL08 MDSL16 200 MA250 MA300 MA400 MA600 MA800 MB1200 MB1600 MB2000 MD2500 MD3000
35 MDSL08 MDSL16 250 MA400 MA600 MA800 MB1200 MB1600 MB2000 MD2500 MD3000
MDSL08 MDSL16 300 MA400 MA600 MA800 MB1200 MB1600 MB2000 MD2500 MD3000
36 MDSL08 MDSL16 400 MA600 MA800 MB1200 MB1600 MB2000 MD2500 MD3000
MDSL08 MDSL16 600 MA800 MB1200 MB1600 MB2000 MD2500 MD3000
MDSL08 MDSL16 800 MB1200 MB1600 MB2000 MD2500 MD3000
37 MDSL16 1000 MB1600 MB2000 MD2500 MD3000
MDSL16 1200 MB2000 MD2500 MD3000
MDSL16 MDSL20 1600 MD3000
38 MDSL20 2000 MD3000
Select the current limiter based on the Magnum breaker frame and current sensor and rating plug as shown.
39
Refer to MDSL current limiter curves for let-through and time characteristics.
The recommended ratings shown provide for reduced current let-through and breaker coordination within the trip unit settings. Selection of
current limiters below the recommended ratings shown provides lower current let-through, however, trip unit settings must be considered to avoid
nuisance operation.
40
41
42
43
100
90
1000
900
800
22
80 700
70 600
60 500
50 400
23
Peak Instantaneous Let-Through Current in Kilo – Amperes X 10
40 300
30 200
20
MD3000
MD2500
100
90
80
24
MD2000 70
10 60
MD1600 50
9
8 MD1200 40 MA250
MA800
7
6
5 MA600
30 MA300 25
4 20 MA400
MA400 MA500
3 MA300
26
Time in Seconds
10
MA250 9
8
MA800
2 7
6 MB1200
5
4 MB1600
1
.9
.8
.7
3
2
MB2000 27
.6 MB2500
.5
1
MB3000
.4
.3
.9
.8
.7
28
.6
.5
.2 .4
.3
.1
.2
29
.09
.08
.07 .1
.06 .09
.05
.04
.08
.07
.06
30
.05
.03 .04
.03
.02
.02 31
.01
10000
8000
40
50
80
8000
80000
20
30
60
70
90
9000
50000
60000
32
7000
700
800
2000
10000
20000
3000
5000
6000
100
7000
40000
70000
100000
700
2000
9000
400
500
600
3000
5000
30000
400
4000
90000
1000
200
900
4000
500
200
600
300
800
300
1000
6000
100
900
1 2 3 4 5 6 7 8 9 10
35
36
37
38
39
40
41
42
43
23 Circuit Breakers requirements of UL 891 switchboards. applicable ANSI, NEMA, UL and CSA
standards, including:
■ Magnum SB Insulated Case
Circuit Breakers have Interruption ■ ANSI C37.13 (Low Voltage ac Power
24 ratings up to 100 kA at 635 Vac with Circuit Breakers Used in Enclosures).
continuous current ratings up to ■ ANSI C37.16 (Preferred Ratings,
6000 amperes. Related Requirements, and
25 ■ Magnum SB Insulated Case Circuit Application Recommendations for
Breakers have lighter-duty Short Low Voltage Power Circuit Breakers
Time Withstand ratings and fixed and ac Power Circuit Breakers).
26 internal instantaneous trips on ■ ANSI C37.17 (Trip Devices for ac and
most ratings, which is characteristic General Purpose dc Low Voltage
of UL 489 molded case breakers Power Circuit Breakers).
27 commonly used in UL 891 switch-
■ ANSI C37.50 (Test Procedures
boards. This provides for greater
for Low Voltage ac Power Circuit
economy and excellent coordination
28 Breakers Used in Enclosures).
and selectivity for most commercial
applications. ■ UL 1066 (Standard for Low Voltage
ac and dc Power Circuit Breakers
■ Fixed internal instantaneous trips
29 will be phased in on all SB Insulated
Used in Enclosures).
Magnum SB Low Voltage Insulated Case ■ NEMA SG3 (This standard adopts
Circuit Breakers are Designed for the Case Circuit Breakers rated 3200
amperes and below to provide an ANSI C37.16 in its entirety).
Performance and Economic Requirements
30 of UL 891 Switchboards extra safety factor by reducing the
energy let-through to downstream Comprehensive
circuits at the maximum instanta-
31 neous trip point and to facilitate Enclosure Solutions
feeder circuit breaker protection
in UL 891 switchboards with Magnum DS has proven performance
32 3-cycle bus bracing. in Eaton manufactured switchgear and
switchboards with the following test
■ Magnum SBSE Current Limiting
certifications:
33 Power Circuit Breakers have 150 kA
Interrupting Ratings at 480 Vac ■ UL 1558 (Magnum DS Low Voltage
with continuous current ratings up Metal-Enclosed switchgear).
34 to 5000 amperes. The Short Time ■ UL 891 (Pow-R-Line C
Withstand Rating is 30 kA for Low Voltage Switchboards).
standard frame and 50 kA for ■ UL, CSA 22.2.31 Low Voltage
35 double frame breakers. Assemblies.
Approvals
36 ■ UL listed: Magnum DS Breaker
UL File E52096 and Cassette
UL File E204565.
37
38
Typical Magnum SB Low Voltage Insulated
Case Circuit Breaker Nameplate
39
40
41
42
43
23
24
25
26
27
Magnum SB Low Voltage Insulated Case Circuit Breaker Family UL Rated for Switchboard Applications
Table 27.1-4. Magnum SB Switchboard Class UL 1066 Insulated Case Low Voltage Power Circuit Breaker
28
Frame Breaker Frame rms Symmetrical Current Ratings kA 50/60 Hz Available Current Sensor & Rating
Amperes Type Type Plugs for Digitrip RMS Trip Unit
(Establishes Breaker In rating)
29
Interrupting Interrupting Interrupting Short Time Fixed Internal
at 254 Vac at 508 Vac at 635 Vac Withstand Rating Inst Trip
38
39
40
41
42
43
23
24
25
26
27
40
41
42
43
Digitrip RMS Trip Unit Family Digitrip RMS Trip Units are highly
accurate microprocessor-based
All Trip Units include three important
22
self-protecting safety features are
for Magnum Circuit Breakers protective devices that use a patented provided as standard:
sampling algorithm to compute
The Magnum family of Digitrip RMS true rms values for precise system Making Current Release (MCR): 23
Trip Units consists of four trip unit coordination and metering. The trip employs a fast acting analog instanta-
models, each providing increasing unit is completely self-contained and neous trip that prevents the breaker
levels of features and options to requires no external control power from closing and latching on a fault 24
enable the ultimate selection to to perform its overcurrent protective when the peak current exceeds 25 x
match application requirements for functions because the power to oper- the breaker In rating. This reduces arc
protection, coordination, information, ate the trip unit is derived from the flash energy during breaker closing for 25
diagnostics and communication: primary current passing through the faults within the self-protecting range.
current sensors. When the trip unit The MCR is enabled for the first 2
■ Digitrip RMS 520
■ Digitrip RMS 520M is operating, the green unit status cycles following the circuit breaker 26
LED begins to blink like a heartbeat closing operation and thereafter,
■ Digitrip RMS 520MC depending on the type of Magnum
to visibly confirm the microprocessor
■ Digitrip RMS 1150+ is powered up. breaker applied, becomes inactive. 27
The trip unit overcurrent protective Over-Temperature Protective Trip:
Common Trip Unit Features automatically trips the breaker when
A summary of the important features
pick-up settings are a function of the
the temperature inside the trip unit
28
breaker In rating, which is established
common to all Magnum Trip Units is by the rating plug and current sensors. exceeds 85 Degrees C, which indicates
as follows: that there are significantly higher
When preset conditions are exceeded,
temperatures within enclosure.
29
■ Microprocessor-based true the trip unit initiates a trip signal to
rms sensing. the trip actuator, tripping the circuit Thermal Memory: provides over-
■ Discrete rotary or programmable
breaker. Red cause of trip LEDs light temperature protection on load 30
up to indicate the cause of trip, pow- circuits against effects of repeated
settings.
ered by a easily replaceable back-up overload conditions. This feature is
■ Unit status LED (green). battery located behind the rating plug. defeatable for special applications 31
■ Cause of trip LEDs (red). The LED will flash to save power, until such as welding and primary
■ Battery check LED (green). the trip unit reset button is depressed. injection testing.
■ Reset/battery test pushbutton. 32
■ Making current release.
■ Thermal memory. 33
■ Over-temperature protective trip.
■ Zone selective interlocking (ZSI)
provisions. 34
■ Rating plug receptacle.
■ Back-up battery for cause of
trip LEDs.
35
■ Test kit receptacle with cover.
■ Plug-in mounting for easy 36
replacement.
■ Clear plastic cover (sealable).
37
38
39
40
41
42
43
Digitrip 520 Trip Unit Digitrip 520M Trip Unit Digitrip 520MC Trip Unit
22
23
24
25
26
27
Digitrip 520 Trip Unit with Digitrip 520M Trip Unit with 4 Digit LCD Digitrip 520MC Trip Unit With ARMs
Basic Overcurrent Protection Display and Ampere-based Metering, Technologies Arc Flash Reduction,
Alarms, and System Diagnostics 4 Digit LCD Display, and Ampere Based 28
The Digitrip 520 is a simple basic Communications
trip unit with three available types The Digitrip 520M is available with
of protection (LI, LSI and LSIG). three types of protection (LSI, LSIG The Digitrip 520MC is available in 29
Up to nine rotary-type current and and LSIA) and includes the following three types of protection (LSI, LSIG
time settings provide for maximum added features: and LSIA) and includes the following
flexibility in curve-shaping and enhancements: 30
■ 4 Digit LCD Display with a step
multi-unit coordination.
pushbutton to scroll through the ■ Communications of ampere based
■ The Instantaneous function (I) display data, including ampere- data, breaker status, and cause of
includes an off position setting based metering of phase, neutral, trip information using the INCOM 31
when Short Time (S) protection is and ground currents, plus opera- communications system. Each trip
provided to increase application tional, and cause-of-trip diagnostic unit has a unique hexadecimal
flexibility in the field. information. address (001 to 999) set by rotary 32
■ I2t Time Delay Settings for better ■ When specified, the Power Relay switches. A red Transmit LED is
provided to confirm communica-
curve shaping when Short Time (S) Module (PRM) is supplied to
tions activity. Peripheral translator 33
and Ground Fault (G) protective perform the following features:
functions are selected. devices are available to convert
❑ Power up the trip unit display
INCOM to other protocols like
■ Zone Selective Interlocking (ZSI) from an external customer sup- Modbus, Ethernet, etc. 34
provided when Short Time (S) plied source through the breaker
■ ARMs Technologies for arc flash
and/or Ground Fault (G) protective secondary contacts to retain the
functions are selected. ZSI provides cause of trip and magnitude of reduction allows the operator to 35
hard-wired positive system coordi- trip information. enable a special trip unit mainte-
nation, allowing the breaker closest nance mode with a preset acceler-
❑ Provide relay contact for remote ated instantaneous override trip that
to the fault to trip first, thus avoiding indication of overload (LSI) or can reduce Arc Flash Energy up to
36
unnecessary and costly system Ground Trip (LSIG), or Ground
downtime. ZSI is a useful method 30%. The arc flash reduction level
Alarm (LSIA). is preset at the trip unit using a 5
to reduce arc flash.
■ Type LSIA units alarm only when position switch which facilitates
37
ground fault settings are exceeded, the maximum arc flash reduction
which is quite useful in critical
power applications.
setting possible while avoiding nui-
sance tripping. Arms can be turned
38
■ Plug Receptacle for Auxiliary Power on locally at the trip unit or remotely
Module to power up the trip unit using peripheral devices like a PDA 39
display during bench testing remote with an IRMint, a logic level control
from the Switchgear. switch, or via communications. A
blue LED provides local indication 40
the trip unit is in the Maintenance
Mode. Remote indication can be
accomplished by a dedicated trip 41
unit contact for use with a stack light
or annunciator panel or via commu-
nications by a dedicated trip unit 42
contact for use with a stack light
or annunciator panel.
43
Digitrip 1150+ Trip Unit ■ Health menu — The Health menu ■ Communications of comprehensive
22 on the Digitrip 1150+ front panel will access to trip unit capabilities
provide information on the Magnum including programmable settings,
Circuit Breaker’s Health, as well as breaker control, metering, alarm,
23 a history of the circuit breaker and status, relaying and diagnostic
circuit it is protecting. This data is information. Peripheral translator
useful for planning maintenance devices are available to convert
24 and inspection schedules. The type INCOM to other protocols like
of data includes the total number of Modbus, Ethernet, etc.
all Instantaneous and Short Delay ■ Accessory bus for use with periph-
25 trips seen by the circuit breaker. A eral digital relay modules, which
second counter shows the number can be programmed through the trip
of Overloads (LDT) and Ground unit keypad for additional auxiliary
26 Faults (GFT) encountered while in and various alarm contacts.
service. The OP count provides data ■ ARMs Technologies for arc flash
on the number of Close Operations reduction.
27 Digitrip 1150+ Trip Unit
experienced by the circuit breaker.
■ ARMs Technologies for arc flash
The last time the circuit breaker was
operated (open or closed or tripped) reduction allows the operator to
The Digitrip 1150+ Trip Unit is a highly
28 advanced programmable protective is viewable with time and date enable a special trip unit mainte-
displayed. Also included is the nance mode with a preset acceler-
device available in three types of
maximum temperature in degrees ated instantaneous override trip that
protection (LSI, LSIG and LSIA).
29 The following is a first level summary Centigrade as seen by the Digitrip can reduce Arc Flash Energy up to
microprocessor CHip. The capture 30%. The arc flash reduction level
of the special features and options:
of the data requires external is preset at the trip unit using a 5
30 ■ 24-character LED Digital Display Trip Unit power. This data, once position switch which facilitates
easily visible from 50 feet and ideal captured, is stored in non volatile the maximum arc flash reduction
for dark equipment environments. memory. These features are avail- setting possible while avoiding nui-
31 ■ Membrane type dust-resistant able for remote communications. sance tripping. Arms can be turned
keypad pushbuttons to facilitate on locally at the trip unit or remotely
■ Programmable alarm contacts or
local unit programming, including using peripheral devices like a PDA
trip contacts.
32 View Functions (Up, Down, ESCape, with an IRMint, a logic level control
■ Programmable relay functions switch, or via communications. A
SELect and Reset), Edit Values (Up,
including undervoltage, overvoltage, blue LED provides local indication
Down, and Save), and Battery Test.
33 ■ Programmable trip unit settings
underfrequency, overfrequency, the trip unit is in the Maintenance
reverse power, voltage unbalance, Mode. Remote indication can be
and curves including I2t and I4t and phase rotation. accomplished by a dedicated trip
curves, as well as IEEE Moderately
34 Inverse, Very Inverse, and Extremely
■ Breaker Health Monitoring with unit contact for use with a stack light
critical intelligence for planning or annunciator panel or via commu-
Inverse curves.
maintenance and inspection nications by a dedicated trip unit
35 ■ Voltage and power metering. schedules. contact for use with a stack light
■ Power quality monitoring and alarm or annunciator panel.
with THD and waveform capture.
36
37
38
39
40
41
42
43
Table 27.1-6. Digitrip Trip Units for Magnum DS and SB ANSI/UL Rated Power Circuit Breakers
22
23
24
Trip Unit Type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+
Ampere Range 200 A – 6000 A 200 A – 6000 A 200 A – 6000 A 200 A – 6000 A 25
Interrupting Rating at 480 V 42 through 200 kA 42 through 200 kA 42 through 200 kA 42 through 200 kA
rms Sensing Yes Yes Yes Yes
Protection and Coordination 26
Protection Ordering Options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed Rating Plug (In) Yes Yes Yes Yes
Overtemperature Trip Yes Yes Yes Yes 27
Long Long Delay Pickup 0.4 – 1.0 x (In) 0.4 – 1.0 x (In) 0.4 – 1.0 x (In) 0.4 – 1.0 x (In)
Delay Long Delay Time I2t at 6 x Ir 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds
Protection Long Delay Time I4t No No No 1 – 5 Seconds 28
(L) IEEE Curves No No No Yes
Long Delay Thermal Memory Yes Yes Yes Yes
High Load Alarm No No No 0.5 – 1.0 x (Ir)
Short Short Delay Pickup 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1
29
Delay Short Delay Time I2t at 8 x Ir 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
Protection Short Delay Time Flat 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
(S) Short Delay Time ZSI Yes Yes Yes Yes 30
Instanta- Instantaneous Pickup 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1
neous Making Current Release Yes Yes Yes Yes
Protection Off Position LSI & LSIG Yes Yes Yes 31
(I)
Ground Ground Fault Alarm No Yes Yes Yes
Fault
Protection
Ground Fault Pickup 25 – 100% x (In)
Ground Fault Delay I2t at .625 x In 100 – 500 ms
25 – 100% x (In)
100 – 500 ms
25 – 100% x (In)
100 – 500 ms
24 – 100% x (In)
100 – 500 ms
32
(G) Ground Fault Delay Flat 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
Ground Fault ZSI Yes Yes Yes Yes
Ground Fault Thermal Memory Yes Yes Yes Yes 33
Disable Ground Fault Protection No No No No
Neutral Protection (N) Model LSI Model LSI Model LSI Model LSI 34
System Diagnostics
Cause of Trip LEDs Yes Yes Yes Yes
Magnitude of Trip Information No Yes Yes Yes 35
Remote Signal Contacts No Yes Yes Yes
Programmable Contacts No No No Yes
System Monitoring 36
Digital Display No 4-Character LCD 4-Character LCD 24-Character LED
Current (% ) Full Scale Sensor No Yes +/- 2% Yes +/- 2% Yes +/- 1%
Voltage (%) L to L No No No Yes +/- 1% 37
Power and Energy (%) No No No Yes +/- 2%
Apparent Power kVA and Demand No No No Yes
Reactive Power kvar No No No Yes 38
Power Factor No No No Yes
Crest Factor No No No Yes
Power Quality — Harmonics No No No Yes 39
% THD, Waveform Capture No No No Yes
System Communications
Type No No INCOM/PowerNet INCOM/PowerNet/TripLink 40
Power Supply in Breaker N/A Optional Standard Standard
Additional Features
Trip Log (3 Events) No No No Yes 41
Electronic Operations Counter No No No Yes
Testing Method Test Set Test Set Test Set Integral and Test Set
Waveform Capture No No No Yes 42
ARMs (Arc Flash Reduction Mode) No No Yes Yes
Breaker Health Monitor No No No Yes
Programmable Relay Functions No No No Yes 43
Over and Undervoltage Alarm or Trip, Over 1200 ampere maximum ground fault setting
and Underfrequency Alarm or Trip, Voltage per UL/NEC. Legend: In = Rating Plug and Sensor Rating.
Unbalance Alarm or Trip, Reverse Power Test set for secondary injection. Ir = Long Delay Pickup setting.
Trip, and Phase Rotation Alarm are included. Contact Eaton for availability.
Magnum Peripheral Devices Time Delay Undervoltage (TDUVR) Digital Relay Accessory Module
22
(DRAM)
Modbus Translator Module (mMINT)
23
24
25
26
27
28
Time Delay Undervoltage
Digital Relay Accessory Module
Modbus Translator Module
The Magnum Time Delay Undervolt- 29
age is a DIN mounted accessory The DRAM is a DIN mounted
device applied in concert with a Mag- accessory device with four Form C
The mMINT (Modbus Master INCOM Net-
work Translator) is a DIN mounted acces-
num, Series C or Series G breaker contacts that can be programmed by 30
mounted instantaneous UVR to pro- the Digitrip 1150+ for indication of any
sory that facilitates communication with
vide an adjustable time delay ride combination of the following condi-
a Modbus RTU Network and as many as
32 Digitrip 520MC and 1150+ Trip Units
through on a temporary loss of volt- tions: auxiliary switch, INST, SDT, LDT, 31
age. Selectable time delay settings are GndT, GFAlm, HLAlm, DEADman, etc.
or other INCOM communications devices
0.1, 0.5, 1 and 2 seconds. Models are using the Trip Unit communications
by passing Modbus registers tranparently
between the two networks.
available for 120 Vac and 230 Vac bus function. 32
applications.
Wireless Transceiver (IRMINT) Other Protocol Translators
and PDA
BIM
To facilitate diverse communications
33
from INCOM to other protocols, Eaton
offers a host of translator devices
including MINTII (RS-232), EtherNet
34
(EMINT and NetLink), Modbus
(mMINT and ELINK), Wireless,
(IRMINT) etc. Contact Eaton for the
35
status of future product development,
including EtherNet Web-based server 36
and other communication
technologies.
37
38
39
BIM 40
Wireless Transceiver The Breaker Interface Module (BIMII)
is a panel mounted device that pro- 41
The wireless transceiver (IRMINT) is a vides a central monitor and display for
panel mounted device that facilitates as many as 50 Magnum 520MC and
central infrared wireless communica- 1150+ Trip Units or other INCOM com- 42
tions between a PDA and as many munications devices. The BIMII can be
as 64 Magnum 520MC and 1150+ Trip mounted directly on the switchgear or
Units or other INCOM communications may be located up to 10,000 feet away 43
devices. The IRMINT can be mounted using twisted pair shielded cable.
directly on the switchgear or may be
remotely located up to 10,000 feet away
using twisted pair shielded cable.
Table 27.1-7. Magnum DS & SB Breaker Control Device Application Guide — Vdc
Breaker Control Device 24 Vdc 32 Vdc 48 Vdc 125 Vdc 250 Vdc 22
Nominal Voltage
Table 27.1-8. Magnum DS & SB Breaker Control Device Application Guide — Vac
30
Breaker Control Device 120 Vac 240 Vac 415 Vac 480 Vac 600 Vac
Nominal Voltage 31
Shunt Trip (ST) Trip Circuit — — —
Operational Voltage Range 70 to 110 % 77 – 140 Vac 146 – 264 Vac
Power Consumption (Inrush) (Required for 35 ms) 450 VA 450 VA 32
Opening Time Seconds 35 ms 35 ms
Spring Release (SR) Close Circuit — — —
Operational Voltage Range 70 to 110 % 77 – 140 Vac 146 – 264 Vac 33
Power Consumption (Inrush) (Required for 200 ms) 450 VA 450 VA
Closing Time Seconds 40 ms 40 ms
Spring Charge Motor (MOT)
Operational Voltage Range 85 to 110 % Voltage 93 – 140 Vdc
— — — 34
177 – 264 Vdc
Amps (Running) Running 2.0 Amps 1.0 Amp
Amps (Inrush) % of Running 600% 600%
Power Consumption 250 VA 250 VA 35
Charging Time Seconds 5 Sec 5 Sec
Undervoltage Release (UVR)
Operational Voltage Range 85 to 110 % Voltage 94 – 140 Vac 177 – 264 Vac 323 – 457 Vac 408 – 528 Vac 510 – 660 Vac 36
Drop-out Voltage Range 30 to 60% Voltage 33 – 76 Vac 62 – 144 Vac 114 – 249 Vac 144 – 288 Vac 180 – 360 Vac
Power Consumption (Inrush) Required for 200 ms 450 VA 400 VA 480 VA 400 VA 400 VA
Power Consumption (Continuous)
Opening Time
Required for 400 ms
Seconds
10 VA
70 ms
10 VA
70 ms
10 VA
70 ms
10 VA
70 ms
10 VA
70 ms
37
Auxiliary Switches — — —
Minimum Load
Contact Rating Inductive Load 10 Amps 10 Amps
38
39
40
41
42
43
22
Legend:
LS Limit Switch for Closing Spring
23 MOT
ST
Motor for Spring Charging
Shunt Trip
SR Spring Release Close Open G Open R
24 UVR
OTS
Undervoltage Release
Overcurrent Trip Switch
31
MDSEOBKR
33 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 C1 C2 C3 C4 C5 C6
ONO OC ONOONO OC ONO UVR UVR ALL ALC AL ICL ATR ATR IP IN NPW N2 N1 SGF ZC ZI ZO ST ST SR SR M M CNC CC CNO CNC CC CNO
34 COM IN OUT
OTS OTS UVR ATR INCOM ATR INCOM NEG NEUTRALSOURCE ZONE SHUNT SPRING MOTOR CELL SWITCH CONTACTS
CLOSE POWER SENSOR GROUND INTER- TRIP RELEASE (SHOWN WITH BREAKER IN WITHDRAWN POSITION)
35 INPUT INPUT INPUT INPUT LOCKING
A16 A17 A18 A19 A20 A21 A22 A23 A24 A25 A26 A27 A28 A29 A30 B16 B17 B18 B19 B20 B21 B22 B23 B24 B25 B26 B27 B28 B29 B30 C7 C8 C9 C10 C11 C12
37 SPRING ACCESSARY
CHARGE BUS
BREAKER AUXILIARY CONTACTS
(SHOWN WITH BREAKER IN OPEN POSITION)
BREAKER AUXILIARY CONTACTS
(SHOWN WITH BREAKER IN OPEN POSITION)
LATCH CELL SWITCH CONTACTS
CHECK (SHOWN WITH BREAKER IN WITHDRAWN POSITION)
STATUS COMMUN- SWITCH
ICATIONS
38
Figure 27.1-7. Typical Magnum Secondary Terminal Block Connection Diagram
39
40
41
42
43
39
40
41
42
43
39
40
41
42
43
Feeder Breakers — General For motor starting duty, with closing During fault conditions, each trip
Circuit breakers for feeder circuit
starting currents up to 600% and opening unit which senses the fault sends a 22
running currents up to 100% of the restraining signal to all upstream trip
protection may be manually or breaker frame size, at 80% power units. This restraining signal results in
electrically operated, with long and factor or higher, the endurance or causing the upstream trip to continue 23
short delay or long delay and instanta- total operations (not requiring parts timing as it is set. In the absence of a
neous type trip devices, and trip replacement) will be as follows: restraining signal, the trip unit trips the
settings, as required for the specific associated breaker with no intentional 24
circuit and load requirements. 800 A Frame: 1400 operations time delay, minimizing damage to the
1600 A Frame: 400 operations fault point. This restraining signal is
General purpose feeder breakers, such as
for lighting circuits, are usually equipped The frequency of operation should not a very low level. To minimize the 25
with long delay and instantaneous trip exceed 20 starts in 10 minutes or 30 in potential for induced noise, and
devices, with the long delay pickup set one hour. provide a low impedance interface
for the maximum load demand in the between trip units, twisted pair con- 26
circuit. Where arcing fault protection is Group Motor Feeder Breakers ductors are utilized for interconnection.
required, the instantaneous trip setting
should be as low as practicable consis-
Typical loads for such circuits are motor Ground fault and short delay pickup 27
control centers. The feeder breakers on Digitrip Trip Units have zone
tent with inrush requirements. selective interlocking.
may be either manually or electrically
Motor Starting Feeder Breakers operated as preferred, and are usually
Zone selective interlocking may be
28
equipped with long and short delay trip
These breakers are usually electrically protection only for coordination with applied as a type of bus differential
protection. It must be recognized,
operated, with long delay and instan- the individual motor circuit devices.
however, that one must accept the
29
taneous tripping characteristics for The minimum long delay pickup setting
motor running, locked rotor and fault should be 115% of the running current minimum pickup of the trip unit for
sensitivity.
protection. The breaker sensor rating of the largest motor in the group, plus 30
should be chosen so that the long delay the sum of the running circuits of all It must also be recognized that not
pickup can be set at 125% of motor full other motors. all systems may be equipped with
load current for motors with a 1.15 zone selective interlocking. Systems 31
service factor, or at 115% for all other Zone Selective Interlocking containing multiple sources, or where
motors. Contactors are recommended the direction of power flow varies,
By definition, a selectively coordinated
for this application when there are a
system is one where by adjusting trip require special considerations, or may 32
number of daily operations involved. not be suitable for this feature. Digitrip
unit pickup and time delay settings, the
When system short circuits are less circuit breaker closest to the fault trips zone interlocking has been tested with
than 40 times the motor full load first. The upstream breaker serves two up to three levels with up to 20 trip 33
current, the motor breaker tripping functions: (1) back-up protection to the units per level.
characteristic should include a short downstream breaker and (2) protection
delay characteristic for greater fault of the conductors between the upstream
34
protection. and downstream breakers. These
elements are provided for on Digitrip
Repetitive Duty trip units.
35
Repetitive breaker opening and clos- For faults which occur on the conduc-
ing, such as in frequent motor starting tors between the upstream and down- 36
and stopping, are covered by ANSI stream breakers it is ideally desirable
standards C37.13 and C37.16. These for the upstream breaker to trip with
standards list the number of opera- no time delay. This is the feature pro- 37
tions between servicing (adjusting, vided by zone selective interlocking.
cleaning, lubrication, tightening, etc.) Digitrip trip units include this option.
and the total numbers of operations 38
under various conditions without Zone selective interlocking is a com-
requiring replacement of parts, for munication signal between trip units
the various breaker frame sizes. applied on upstream and downstream 39
breakers. Each trip unit must be applied
as if zone selective interlocking were
not employed, and set for selective 40
coordination.
41
42
43
39
40
41
42
43
Type DSII Low Voltage Sizes and Arrangements the circuit breaker current sensors
22
and initiating trip signals to the circuit
Power Circuit Breakers Types DSLII-308 (800 ampere), breaker trip unit when preset current
DSLII-516 (1600 ampere), and DSLII- levels and time delay settings are
620 (2000 ampere) frame breakers exceeded. By sampling the current 23
include the limiters integrally mounted waveform at various points on the
on the drawout breaker elements in wave and calculating true rms current,
series with the upper terminals. the Digitrip is able to reduce nuisance 24
Current limiters used in Types tripping events due to non-sinusoidal
DSLII-632 and DSLII-840 combinations wave shapes.
are mounted on separate drawout 25
Electronic trip units are applied to
trucks in an additional equal size distribution systems when high stan-
compartment. dards of protection and coordination 26
are called for. In addition, electronic
Electronic Trip Units trip units can provide further enhanced
Eaton offers the most comprehensive features such as alarming, diagnostics, 27
range of electronic trip units in the system monitoring and communications.
industry for power circuit breakers.
Cutler-Hammer rms sensing trip
DSII with 910 Trip Unit Digitrip electronic trip units are ac units for power breakers fall into two
28
devices that employ microprocessor- main categories:
Type DSII Low Voltage Power Circuit based technology that provides a true
Breakers provide: rms current sensing means for proper ■ Front adjustable trip units: 29
correlation with thermal characteristics Digitrip RMS 510, 610, 810, 910.
■ 100% rated, fully selective protection. ■ Programmable trip units:
of conductors and equipment. The pri-
■ Integral microprocessor-based mary function of the Digitrip electronic Digitrip OPTIM 750, 1050. 30
breaker tripping systems. trip unit is to provide circuit protection.
For additional information on trip units
■ Two-step stored-energy breaker This is achieved by analyzing the sec-
closing. ondary current signals received from
see Section 28.1. 31
And many other features for coordi-
nated, safe, convenient, trouble-free 32
Legend
and economical control and protection LS — Limit Switch for Closing Spring CS (or PB) CS (or PB)
of low voltage distribution systems. MOT — Motor for Spring Charging Close Ind. G Trip
SH TR — Shunt Trip Lts.
R 33
Maximum Ratings SR — Spring Release
Y — Anti-Pump Relay
■ 600 Vac.
Description of Operation 34
■ 5000 amperes continuous. 1 — Motor is energized through LS contact. SR MOT SHTR
■ 200,000 amperes short circuit capacity. 2 — Motor runs and charges Closing Spring.
3 — When Closing Spring fully charged, LS
contacts reverse.
35
Application 4 — CIosing CS-C contact energizes SR Coil Y
Eaton’s Cutler-Hammer Type DSLII through Y, LS & “b” contacts.
breakers are coordinated combina- 5 — When Breaker closes, “b” opens and Y Y LS LS 36
Coil is energized in series with SR Coil.
tions of Type DSII breakers and series 6 — Y contact opens to open SR Coil circuit b b a
connected current limiters. They are & prevent pumping should breaker 37
intended for applications requiring open while CS-C is held closed. Y Coil
the overload protection and switching has very low drop-out voltage.
7 — LS contacts reverse and motor
functions of air circuit breakers on
systems whose available fault currents
recharges closing springs. 38
exceed the interrupting rating of the
Figure 27.2-1. Standard Control Diagram for Type DSII Electrically Operated Breaker,
breakers alone, and/or the withstand
in DSII Switchgear, for ac or dc Control Source 39
ratings of “downstream” circuit
components.
40
41
42
43
The following curves illustrate the ratings, Limiter Selection Case A would tend to use the smallest
melting time-current characteristics
The selection of a suitable limiter
available limiter; Case B the largest. 22
and current limiting, or let-through When downstream protection is
characteristics, of limiters for Eaton’s rating for a given application is required, the selection is usually
Cutler-Hammer Type DSLII breakers. generally governed by a choice of a compromise, since certain small 23
the following types of protection: limiters cannot be coordinated with
The let-through current for a given the breaker to avoid nuisance blowing
A. Maximum protection of “down-
limiter application is readily determined
stream” components. Type DSLII on overloads or small and moderate 24
by extending a vertical line from the short circuits.
applicable maximum available sym- breakers are often used for this
purpose even when the maxi-
metrical fault amperes at the bottom
mum available fault currents are
Minimum, recommended, and maxi- 25
margin to the characteristic line for mum limiter sizes for Eaton’s Cutler-
the particular limiter, and from this within the interrupting rating of Hammer Types DSLII-308, DSLII-516,
the corresponding Type DSII
intersection extending a horizontal line
unfused breakers.
and DSLII-620 breakers are given 26
to the left margin and reading the peak in table.
current. The withstand rating of any B. Protection of the circuit breaker only.
circuit elements protected by the
Table 27.2-10. DSLII Limiter Selection
27
limiters should be at least equal to
this peak current. Breaker Sensor Rating, Limiter Rating, Amperes
22
SCALE X 100 = CURRENT IN AMPERES
10,000
1000
2000
3000
4000
5000
6000
7000
8000
9000
100
200
300
400
500
600
700
800
900
400,000
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
800 800
700 700 300,000
600 600
500 500
23
400 400
200,000
300 300
800
1200
1600
2000 2000
100
24
100 100,000
90 90 1600
80 80 90,000
70 70 1200
60 60
80,000
800
50 50 70,000
ce
25
du
TIME IN SECONDS
TIME IN SECONDS
o
20 20 40,000
Pr
an
400
tc
ui
30,000
irc
10 10 300
C
9 9
nt
8 8 250
re
7 7
ur
26 6 6
C
20,000
ak
5 5
Pe
4 4
um
im
3 3
ax
M
2 2
27 1
.9
1
.9
10,000
9000
8000
.8 .8 7000
.7 .7
.6 .6 6000
.5 .5
5000
28
.4 .4
.3 .3 4000
.2 .2
3000
29
.1 .1
.09 .09
.08 .08 2000
.07 .07
.06 .06
.05 .05
.04 .04
.03 .03
30 1000
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
200,000
.02 .02
2000
3000
4000
5000
6000
7000
8000
9000
300
100
200
400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
32 Figure 27.2-3. DSLII-308 Average Melting Time-Current Characteristics Figure 27.2-5. DSLII-308 Let-Through Characteristics
33
SCALE X 100 = CURRENT IN AMPERES
10,000
1000
2000
3000
4000
5000
6000
7000
8000
9000
100
200
300
400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
800 800 400,000
700 700
600 600
500 500
300,000
34
400 400
300 300
AMPERE
200,000 RATING
200 Limiter Ampere Rating 200
3000
800
1000
1200
1600
2000
2500
3000
2500
35 100
90
80
70
60
100
90
80
70
60
100,000
90,000
2000
1600
1200
50 50 80,000 1000
40 40 70,000
800
MAXIMUM PEAK LET-THROUGH CURRENT, AMPS
30 30
36
60,000
50,000
e
TIME IN SECONDS
20 20
TIME IN SECONDS
uc
od
40,000
Pr
an
tc
10 10
ui
9 9 30,000
irc
8 8
37
C
7 7
nt
6 6
re
ur
5 5
C
20,000
ak
4 4
Pe
3 3
um
im
ax
38
2 2
M
10,000
9000
1 1
.9 .9 8000
.8 .8
.7 .7 7000
.6 .6
39
6000
.5 .5
.4 .4 5000
.3 .3
4000
.2 .2
3000
40 .1
.09
.08
.1
.09
.08 2000
.07 .07
.06 .06
.05 .05
41
.04 .04
.03 .03
1000
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
200,000
.02 .02
42 .01 .01
300
70
80
90
100
1000
2000
3000
4000
5000
6000
7000
8000
9000
200
400
500
600
700
800
900
10,000
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
Type DSL-416 Limiters — For DSL-416, DSLII-516, DSL-420 Ref. Curve No. 639431 Type DSL-416 Limiters — For DSL-416, DSLII-516, DSL-420 Ref. Curve No. 639432
Supersedes AD 36-783
and DSLII-620 Breakers
Supersedes AD 36-783
dated April 1990 and DSLII-620 Breakers
43 January 1997
dated April 1990
January 1997
Figure 27.2-4. DSLII-516 and DSLII-620 Average Melting Figure 27.2-6. DSLII-516 and DSLII-620 Let-Through Characteristics
Time-Current Characteristics DSL-420 and DSLII-620 — use only 3000 limiter.
DSL-420 and DSLII-620 — use only 3000 limiter.
22
10,000
1000
2000
3000
4000
5000
6000
7000
8000
9000
100
200
300
400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
100 100 400,000
90
80
Ampere Rating Limiter 90
80
AMPERE
RATING
2500
3000
4000
5000
70 70
60 60 300,000
50 50 5000
40
30
40
30 200,000
4000
23
3000
20 20
2500
10
90
80
10
90
80 100,000
24
70 70 90,000
60 60
50 50
80,000
40 40 70,000
25
e
TIME IN SECONDS
TIME IN SECONDS
uc
20 20
od
40,000
Pr
an
tc
10 10
26
ui
9 9 30,000
rc
8 8
Ci
7 7
t
en
6 6
rr
5 5
Cu
20,000
ak
4 4
Pe
3 3
27
um
im
ax
2 2
M
10,000
1 1 9000
.9 .9
.8
.7
.6
.5
.8
.7
.6
.5
8000
7000
28
6000
.4 .4
.3 .3
5000
.2 .2
4000
29
3000
.1 .1
.09 .09
.08 .08
.07
.06
.05
.04
.07
.06
.05
.04
2000
30
.03 .03
31
.02 .02
1000
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
200,000
.01 .01
70
90
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
80
300
100
200
400
500
600
700
800
900
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES
SCALE X 100 = CURRENT IN AMPERES
Type DSL-632 Limiters — For DSL-632, and DSLII-632 Breakers Ref. Curve No. 705503
Supersedes AD 36-783
Type DSL-632 Limiters — For DSL-632, and DSLII-632 Breakers
Type DSL-840 Limiters — For DSL-840, and DSLII-840 Breakers
Ref. Curve No.
705504Supercedes AD
36-783
32
Type DSL-840 Limiters — For DSL-840, and DSLII-840 Breakers dated April 1990 dated April 1990
January 1997 January 1997
Figure 27.2-7. DSLII-632 and DSLII-840 Average Melting Figure 27.2-8. DSLII-632 and DSLII-840 Let-Through Characteristics 33
Time-Current Characteristics
36
37
38
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43