You are on page 1of 36

Power Circuit Breakers & Insulated Case Circuit Breakers

27.0-1
June 2006
Sheet 1091

Insulated Case Circuit Breakers


Power Circuit Breakers & Contents
Power Circuit Breakers & Insulated Case Circuit Breakers
22

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.0-2 23
Magnum Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . . . . . . . 27.1-1
Magnum DS Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . . . . 27.1-5 24
Magnum SB Insulated Case Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . 27.1-10
Magnum IEC Rated Air Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1-12
DSII Power Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.2-1
25
Specifications
See Eaton’s Cutler-Hammer Product Specification Guide on enclosed CD-ROM: 26
1995 CSI Format: Power Circuit Breakers — Magnum DS . . . . Section 16475
Power Circuit Breakers — DSII. . . . . . . . . . . Section 16475 27
Insulated Case Circuit Breakers
— Magnum SB . . . . . . . . . . . . . . . . . . . . . . Section 16475
Microprocessor Trip Units . . . . . . . . . . . . . . Section 16904
28
2004 CSI Format: Power Circuit Breakers — Magnum DS . . . . Section 26 28 11
Power Circuit Breakers — DSII. . . . . . . . . . . Section 26 28 11 29
Insulated Case Circuit Breakers
— Magnum SB . . . . . . . . . . . . . . . . . . . . . . Section 26 28 11 30
Microprocessor Trip Units . . . . . . . . . . . . . . Section 26 28 50

31

32

33

34

35

36

37

38

39

40

41

42

43
Low Voltage Circuit Breakers

CA08104001E For more information visit: www.EatonElectrical.com


27.0-2 Power Circuit Breakers & Insulated Case Circuit Breakers
Overview June 2006
Sheet 1092

22 Summary of Differences Between Low-Voltage Power Circuit Breakers,


Insulated-Case Circuit Breakers, and Molded-Case Circuit Breakers
23 Their are two main classifications of low-voltage circuit
breakers — molded-case circuit breakers and low-voltage
Molded-case circuit breakers and insulated-case circuit
breakers comply with the following standards:
power circuit breakers. All UL, NEMA, and ANSI standards
■ UL 489 — MCCB
24 are for molded-case circuit breakers and low-voltage
power circuit breakers. ■ UL 1087 — Molded Case Switches (MCS)
■ NEMA AB1 — MCCB & MCS
The industry recognizes three types of circuit breakers —
25 molded-case circuit breakers (MCCB), insulated-case circuit ■ NEMA AB3 — MCCB Application
breakers (ICCB), and low-voltage power circuit breakers Low-voltage power circuit breakers comply with the
LVPCB). Insulated-case circuit breakers are designed to following standards:
26 meet the standards for molded-case circuit breakers.
■ ANSI Std. C37.16 — Preferred Ratings
■ ANSI Std. C37.17 — Trip Devices for LVPCB
27
■ ANSI Std. C37.50 — Test Procedures
■ IEEE Std. C37.13 — LVPCB Used in Enclosures
28 ■ UL 1066 — LVPCB

Table 27.0-1. Breaker Comparison Chart


29 LVPCB ICCB MCCB
(C-H Type Magnum DS) (C-H Type Magnum SB) (C-H QUICKLAG/Series C/Series G)

30 Selective trip over full range of fault currents up


to interrupting rating.
Selective trip over partial range of fault currents Selective trip over a smaller range of fault currents
within the interrupting rating. Typically up to 35 kA. within the interrupting rating. Typically 10 – 13
times the frame size.

31 Types of operators: mechanically operated,


two-step, stored energy, and electrical two-step
Types of operators: mechanically operated,
two-step, stored energy, and electrical two-step
Types of operators: mechanically operated
over-center toggle or motor operator.
stored energy. stored energy.
5 cycle closing for electrically operated devices . 5 cycle closing for electrically operated devices. Greater than 5 cycle closing for electrically
32 operated devices.
Available in drawout construction permitting Available in drawout construction permitting Typically fixed-mounted but large frame sizes may
racking to a distinct “test position” and removal for racking to a distinct “test position” and removal for be available in drawout construction.
33 maintenance. maintenance.
Interrupting duty at 635 Vac: Interrupting duty at 508 Vac: Interrupting duty at 480 Vac:
42 – 100 kA and current limiting with or without 35 – 150 kA 22 – 100 kA without fuses and up to 200 kA with
34 fuses up to 200 kA. integral fuses or for current-limiting type.
Special current limiting types available with or Special current limiting types available without Current limiting available with and without fuses
without fuses up to 200 kA. fuses up to 150 kA. up to 200 kA.
35 Usually most costly. Slightly under LVPCB cost, but depends on the Usually least costly.
enclosure selected.
Small number of frame sizes available. Small number of frame sizes available. Large number of frame sizes available.
36 Typical 800 to 6000 A. Typical 800 to 6000 A. Typical 100 to 2500 A.
Extensive maintenance possible on all frame sizes. Limited maintenance possible on larger Very limited maintenance possible on larger
frame sizes. frame sizes.
37 Used in enclosures, switchboards, and switchgear. Used in enclosures, switchboards, and switchgear. Used in enclosures, panelboards, switchboards,
MCCs, and control panels.
Not available in series ratings. Not available in series ratings. Available in series ratings.
38 100% continuous current rated in its enclosure. 80% continuous-current rated, unless specifically 80% continuous-current rated, unless specifically
stated to be rated 100% in an enclosure. stated to be rated 100% in an enclosure.

39 UL 1066, IEEE Standard C37.13 UL 489, NEMA AB-1 UL 489, NEMA AB-1

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-1
June 2006 Power Circuit Breakers
Sheet 1093
Low Voltage Power Circuit Breakers — Magnum DS and SB

Contents Two Product Families


22
Magnum consists of two product families; each provides
Magnum Global Family
specific rating features and approvals to optimize perfor-
General Description . . . . . . . . . . . . . . . . . . . . . . . . . 27.1-1 mance when applied in power distribution equipment
and custom enclosures:
23
Magnum DS Power Circuit Breakers . . . . . . . . . . . 27.1-5
Magnum SB Insulated Case Circuit Breakers . . . . 27.1-10 Magnum DS Low Voltage Power Circuit Breakers for ANSI
Magnum IEC Rated Air Circuit Breakers . . . . . . . . 27.1-12 Rated Switchgear Applications 24
Breaker-Mounted Options . . . . . . . . . . . . . . . . . . . . 27.1-14 ■ Up to 635 Vac.
Trip Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1-16 ■ 200 to 6000 A continuous. 25
Accessories and Peripheral Devices. . . . . . . . . . . . 27.1-22 ■ 42 to 200 kA interrupting.

Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1-23 26


Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1-25

27
Magnum Low Voltage Power Circuit Breakers
for Global Application
28
Magnum Low Voltage Power Circuit Breakers enable
comprehensive solutions to meet and exceed the unique
and wide-ranging requirements of today’s global power 29
distribution systems. This powerful circuit breaker offering Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated
is designed for ultimate custom configuration and applica- for Switchgear Applications
tion flexibility, with the needs of the power distribution 30
equipment user and the electrical equipment manufacturer
in mind. Magnum SB Low Voltage Insulated Case Circuit Breakers for
Switchboard Applications 31
■ Up to 635 Vac.
■ 200 to 6000 A continuous. 32
■ 50 to 150 kA interrupting.

33

34

35

36
Magnum SB Low Voltage Insulated Case Circuit Breaker Family for
Switchboard Applications
37

38

39

40

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


27.1-2 Power Circuit Breakers & Insulated Case Circuit Breakers
Power Circuit Breakers June 2006
Sheet 1094
Low Voltage Power Circuit Breakers — Magnum DS and SB

22 All Magnum Breaker Types —


Features, Benefits and Functions
23 ■ 200 kA interruption ratings with current limiting perfor-
mance and low current let-through to reduce damaging
energy to downstream equipment at high fault levels.
24 ■ Withstand ratings up to 100 kA to maximize system
coordination and selectivity.
■ Three physical frame sizes (Narrow, Standard and
25 Double) to promote breaker application in compact
modular enclosures.
■ Continuous current ratings from 800 to 6000 A with 100%
26 rating at 40ºC and no derating on most ratings up to 50ºC.
■ Fixed breaker mounting configurations with horizontal
27 and optional vertical and front connected terminal
connections.
■ Drawout breaker mounting configurations with cassette
28 and optional safety shutters.
■ 3- and 4-pole breaker configurations.
■ Through-the-door design for human interface with the
29 breaker compartment door closed.
■ Two-step stored energy mechanism for manually and
electrically operated breakers.
30
■ Digitrip RMS Trip Unit family protection with four
models each providing increasing levels of protection
31 and feature options for coordination, information and
diagnostics:
❑ Microprocessor-based rms sensing
32 ❑ Basic to programmable overcurrent protection
and alarms Through-the-Door Design for Human Interface with the Breaker
❑ Local display for information, status and diagnostics Compartment Door Closed
33
❑ Ampere, voltage and power metering
❑ Power quality, harmonics and waveform capture
34 ❑ Communications with translators to common protocols
❑ Zone selective interlocking for improved coordination
35 ❑ ARMs Technologies for arc flash reduction
❑ Breaker health monitoring
36 ■ Field-installable accessories (UL listed) common across
the breaker frames and designed to be easily installed in
the field to service or modify the breaker at the point of use.
37 ■ Secondary terminal contacts mounted at the top front of
the breaker and away from the primary voltage areas for
improved safety and access. Finger-proof terminal blocks
38 accommodate ring-tongue or spade type terminals as
standard.
39

40

41

42

43
High Technology Microprocessor-Based Digitrip RMS 1150+ Trip
Units are Available With Advanced Features Like Programmable
Overcurrent Settings, Power Metering, Power Quality and
Communications

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-3
June 2006 Power Circuit Breakers
Sheet 1095
Low Voltage Power Circuit Breakers — Magnum DS and SB

Breaker Features on   
22
Front Cover
The controls and indicators are func- 23
tionally grouped on the breaker face-
plate to optimize the human interface,

visibility, and ease of use. For maxi- 24
mum safety, a modern, through-the- 
door design permits access to the

breaker levering system, trip unit, 25
controls and indicators with the 
door closed.
 Mechanical Trip Flag Pop-out 26

Indicator (Optional) — Red
 Accessory Viewing Windows for: 27
❑ Shunt Trip Attachment (STA)

❑ Spring Release Device (SR) 28



❑ Undervoltage Release (UVR)
Device or Second STA
29
 Digitrip RMS Trip Unit (Model 520M
Shown) Protected by Clear Cover
 Contact Status Indicators:
30
❑ OPEN — Green
❑ CLOSED — Red Magnum DS Drawout Breaker
31
 Spring Status Indicators:
32
❑ Charged — Yellow
❑ Discharged — White
33
 Push OFF (Open) Pushbutton —Red
 Push ON (Close) Pushbutton —
Green
34
Manual Spring Charging Handle for
Manually Charging the Stored 35
Energy Springs
Accessory Viewing Windows Visibly

Mechanical Operations Counter Confirm the Breaker Shunt Trip, Spring 36


(Optional) Release, and UVR Installation and Their
Control Voltage Rating
Key Off Lock (Optional)
Drawout Breaker Levering Can be 37
Padlockable Levering Device Accomplished With the Compartment
Shutter for Drawout Breakers Door Closed Without the Need for a
Color-Coded Position Indicator
Special Levering Tool 38
for Drawout Breakers:
❑ CONNECT — Red 39
❑ TEST — Yellow
❑ DISCONNECT — Green 40

41

42
Through-the-Door Design for Human
Interface with the Breaker Compartment
Door Closed, for Example, Manually
43
Charging the Stored Energy Springs

CA08104001E For more information visit: www.EatonElectrical.com


27.1-4 Power Circuit Breakers & Insulated Case Circuit Breakers
Power Circuit Breakers June 2006
Sheet 1096
Low Voltage Power Circuit Breakers — Magnum DS and SB

Breaker Internal Features  


22
Magnum circuit breakers are designed
for ease of access for inspection, mod- 
23 ification and maintenance at the point
of use. The breaker front cover is eas-
ily removed with four captive bolts,
24 revealing the modular internal breaker
features.
25  Secondary Terminal Points for
Internal Breaker Wiring
Connections
26  Breaker Accessory Mounting Deck
with Three Positions for Mounting:
27 ❑ Shunt Trip Attachment (STA)

❑ Spring Release Device (SR)
28 ❑ Undervoltage Release (UVR)
Device or Second STA
 Digitrip RMS Trip Unit (Model
29 1150+ Shown) 
 Spring Charging Motor (Optional) 
30 for Electrically Charging the Stored

Energy Springs

31  Manual Spring Charging Handle


for Manually Charging the Stored Magnum Drawout Breaker Front View With Front Cover Removed
Energy Springs Showing Easy Access to the Breaker Internal Devices
32  Padlockable Levering Device
Shutter for Drawout Breakers
33  Color-Coded Position Indicator for
Drawout Breakers:

34 ❑ CONNECT — Red
❑ TEST — Yellow
❑ DISCONNECT — Green
35

Secondary Contact Blocks for


Connection to External Cell
36 Control Wiring

Removable Arc Chute Covers for
37 Easy Access to Breaker Main
Contacts
Primary Finger Cluster Disconnect-
38 ing Contacts for Drawout Breaker
are Mounted on the Breaker
Element (Not in the Breaker
39 Compartment) for Ease of Access
for Inspection and Maintenance
40 Current Sensor Viewing Windows
to View and Confirm Breaker
Sensor Rating
41 Rigid Frame Housing (Thermoset
Composite Resin) Providing
42 Increased Strength and Durability


43 Magnum Drawout Breaker Rear View Showing Primary Disconnecting
Finger Clusters Mounted on the Breaker for Ease of Inspection

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-5
June 2006 Power Circuit Breakers
Sheet 1097
Magnum DS Low Voltage Power Circuit Breakers

Magnum DS Low Voltage UL and ANSI Test Comprehensive Enclosure 22


Power Circuit Breakers Certifications Solutions
Magnum DS is a true UL 1066 listed Magnum DS meets or exceeds the Magnum DS has proven performance
low voltage power circuit breaker applicable ANSI, NEMA, UL and CSA  in Eaton manufactured switchgear and 23
family, designed for the highest perfor- standards, including: switchboards with the following test
mance requirements of switchgear certifications:
and specialty enclosure applications. ■ ANSI C37.13 (Low Voltage ac 24
Power Circuit Breakers Used in ■ UL 1558 (Magnum DS Low Voltage
■ Magnum DS Low Voltage Power Enclosures). Metal-Enclosed
Circuit Breakers have short time ■ ANSI C37.16 (Preferred Ratings, Switchgear). 25
withstand and interruption ratings Related Requirements, and ■ UL 891 (Pow-R-Line C Low Voltage
up to 100 kA at 635 Vac with Application Recommendations for Switchboards).
continuous current ratings up to Low Voltage Power Circuit Breakers ■ UL 1008 Standard for Transfer
26
6000 amperes to maximize system and ac Power Circuit Breakers). Switch Equipment.
coordination and selectivity. ■ ANSI C37.17 (Trip Devices for ac and ■ UL, CSA 22.2.31 Low Voltage 27
■ Magnum MDSX Current Limiting General Purpose dc Low Assemblies.
Power Circuit Breakers have 200 kA Voltage Power Circuit Breakers).
interrupting ratings at 480 Vac with ■ Approvals
continuous current ratings up to
ANSI C37.50 (Test Procedures for 28
Low Voltage ac Power Circuit Break- ■ UL listed: Magnum DS Breaker UL
5000 amperes. ers Used in Enclosures).
■ Magnum MDSL Current Limiting File No. E52096 and Cassette UL File
Power Circuit Breakers have 200 kA
■ UL 1066 (Standard for Low Voltage No. E204565. 29
ac and dc Power Circuit Breakers ■ ABS (American Bureau of Shipping)
interrupting ratings at 600 Vac with Used in Enclosures).
continuous current ratings up to Type Listed Certificate Number
2000 amperes. ■ NEMA SG3 (This standard adopts 04-HS422844A-DUB. 30
ANSI C37.16 in its entirety).

Magnum DS, MDSX and MDSL Circuit Breakers


31

32

33

34

35

36

Magnum DS Low Voltage Power Magnum MDSX Current Limiting Magnum MDSL Current Limiting 37
Circuit Breakers have high withstand Power Circuit Breakers have fast open- Power Circuit Breakers have integral
ratings from 42 kA to 100 kA to ing contacts to provide interrupting current limiters to provide interrupting
provide for maximum system ratings up to 200 kA at 480 Vac ratings of 200 kA at 600 Vac. 38
coordination and selectivity. without fuses.
39

40

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-6
Power Circuit Breakers June 2006
Sheet 1098
Magnum DS Low Voltage Power Circuit Breakers

22 Selecting the Optimal Magnum Solution for System Coordination,


Interruption Performance and Arc Flash Reduction
23 Table 27.1-1. System Application Considerations
Magnum Breaker Type Withstand System Interruption Arc Flash Energy Operating System
(See Table 27.1-2) Coordination Convenience, and
24 Life Time Cost

MDS Up to 65 kA Up to 100 kA Up to 100 kA Highest Energy Inspect, Reset and


High Withstand — (Narrow Frame) at 635 Vac Close After Interruption
25 LS Trip Functions Up to 85 kA
with Trip Unit (Standard Frame)
Instantaneous Off
Up to 100 kA
26 (Double Frame)

MDSX 30 kA Up to the 200 kA Lower Energy at Inspect, Reset and


27 Current Limiting — (Standard Frame) Withstand Rating at 508 Vac Fault Levels in Current Close After Interruption
Fast Opening Reverse 50 kA Based on Trip Test Pending Limiting Range Above
Loop Contacts with (Double Frame) Unit Settings for 130 kA Withstand Rating
28 Trip Unit Instanta-
neous Off
at 635 Vac

29
MDSL Based on Current Based on Current Up to 200 kA Lower Energy at Fault Levels Blown Limiters Require
Current Limiting — Limiter Selected Limiter Selected at 600 Vac in the Current Limiting Replacement and Inventory
30 Integral Current
Limiters with Trip Unit
and Trip Unit
Settings
Range of Current Limiter Operating Watts Loss
is Higher than Fuse-less
Instantaneous Off Breakers
31 All Magnum Breakers Per Magnum Trip Unit Instanta- Per Magnum May be Reduced by Per Magnum Breaker
with Trip Unit Instantaneous On Breaker Type neous Settings Breaker Type Employing Trip Unit: Type Applied
Applied Affect System Applied Ground Fault Settings,
Coordination and
32 Continuity
Zone Selective Interlocking,
ARMs Technologies

33 Magnum MDS High Withstand Magnum MDSX Fuseless Magnum MDSL Interruption Up to
Breakers for Maximum Coordination Interruption Up to 200 kA Current 200 kA with Integral Current Limiters
34 Magnum MDS breakers are designed Limiting Performance Magnum MDSL breakers with integral
to hold in and carry their rated short Magnum MDSX breakers provide new current limiters provide interruption
time withstand current up to 0.5 fuseless technology with interruption ratings up to 200 kA at 600 Vac. MDSL
35 seconds, the maximum trip unit
short time delay setting. System
ratings up to 200 kA at 508 Vac. is especially effective in reducing
energy let-through and arc flash at the
The interruption performance
coordination is maximized when the is current limiting when the fault highest fault currents and those that
36 instantaneous trip unit settings are
either turned off or set high enough
currents exceeds the withstand rating. fall within the current limiting range
of the current limiter. Interruption is
The self-protecting fast opening
to facilitate coordination with other reverse loop contacts quickly open clean and efficient with most of the arc
37 protective devices on the circuit. clearing the fault in approximately display contained within the current
1/4 cycle, reducing energy let-through limiter. A wide array of current limiter
Energy let-through and arc flash
and arc flash energy before the ratings are available for selection and
energy to the downstream circuit can
38 be significantly reduced by employing breaker mechanism opens to reset application with the breaker current
the contacts. sensor ratings and trip unit settings
instantaneous trip unit settings as well
to provide for system coordination.
as ground fault and zone interlocking. Below their withstand rating, MDSX
39 However, the desire to reduce arc breakers coordinate like normal construc- When fault currents fall below the
flash may have to be balanced with tion MDS breakers. Arc flash levels to the current limiting range of the limiter,
the necessity to maintain system downstream circuit can be reduced by like those characteristic of arcing
40 coordination and continuity. This is employing the trip unit instantaneous faults, energy let thru and arc flash
especially true at the low fault levels settings as well as ground fault, zone energy can increase. In this range,
characteristic of arcing faults, because interlocking, and ARMs features. a lower rated current limiter may
41 the trip unit instantaneous trip setting be applied, but considerations must
may have to be set as low as the MDSX breakers have the same compact be given to nuisance blowing of the
minimum setting, which could footprint as standard MDS breakers to limiter and system coordination.
42 cause nuisance tripping. facilitate use in compact enclosures.
MDSL breakers can also employ trip
The ARMs Technologies Trip Unit MDSX improves overall operating sys- unit instantaneous settings as well as
43 Option can be employed to optimize tem continuity, convenience, and life ground fault, zone interlocking, and
arc flash reduction during system time costs by eliminating fuse trucks, ARMs Technologies features to reduce
start-up and maintenance operations. blown limiter change outs, replacement arc flash levels. Physically, they are 6
limiter inventories and the higher oper- inches (152.4 mm) deeper than stan-
ating watts loss associated with fuses. dard construction Magnum breakers.

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-7
June 2006 Power Circuit Breakers
Sheet 1099
Magnum DS Low Voltage Power Circuit Breakers

Magnum DS Switchgear Class UL 1066 22

23

24

25

26

27
Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications
Table 27.1-2. Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers
28
Frame Breaker Frame rms Symmetrical Current Ratings kA 50/60 Hz  Short Time Fixed Internal Available Current Sensor &
Amperes Type Type Interrupting at Interrupting at Interrupting at Withstand
Rating
Instantaneous
Trip
Rating Plugs for Digitrip
RMS Trip Unit (Establishes
29
254 Vac 508 Vac 635 Vac
Breaker In rating)

800 MDN-408 Narrow 42 42 42 42 — 200, 250, 300, 400, 600, 800 30


MDN-508 Narrow 50 50 50 50 —
MDN-608 Narrow 65 65 65 65 —
MDN-C08 Narrow 100 100 65 20 18 x In
MDS-408 Standard 42 42 42 42 —
31
MDS-608 Standard 65 65 65 65 —
MDS-808 Standard 85 85 85 85 —
MDS-C08 Standard 100 100 100 85 85 32
MDS-L08  Standard 200 200 200 — —
MDS-X08  Standard 200 200  30 30
1600 MDN-416 Narrow 42 42 42 42 — 200, 250, 300, 400, 600, 800, 33
MDN-516 Narrow 50 50 50 50 — 1000, 1200, 1600
MDN-616 Narrow 65 65 65 65 —
MDN-C16 Narrow 100 100 65 30 18 x In
34
MDS-616 Standard 65 65 65 65 —
MDS-816 Standard 85 85 85 85 —
MDS-C16 Standard 100 100 100 85 85
MDS-L16  Standard 200 200 200 — — 35
MDS-X16  Standard 200 200  30 30
2000 MDN-620 Narrow 65 65 65 65 — 200, 250, 300, 400, 600, 800,
MDN-C20 Narrow 100 100 65 35 18 x In 1000, 1200, 1600, 2000 36
MDS-620 Standard 65 65 65 65 —
MDS-820 Standard 85 85 85 85 —
MDS-C20 Standard 100 100 100 85 85 37
MDS-L20  Standard 200 200 200 — —
MDS-X20  Standard 200 200  30 30
3200 MDS-632 Standard 65 65 65 65 — 200, 250, 300, 400, 600, 800, 38
MDS-832 Standard 85 85 85 85 — 1000, 1200, 1600, 2000, 2500,
MDS-C32 Standard 100 100 100 85 85 3000, 3200
MDS-X32  Double 200 200  50 50 39
4000 MDS-840 Double 85 85 85 85 — 2000, 2500, 3200, 4000
MDS-C40 Double 100 100 100 100 —
MDS-X40  
Double 200 200 50 50
40
5000 MDS-850 Double 85 85 85 85 — 2500, 3200, 4000, 5000
MDS-C50 Double 100 100 100 100 —
MDS-X50  Double 200 200  50 50
6000 MDS-C60  Double 100 100 100 100 — 3200, 4000, 5000, 6000
41
 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are
equal to the published Short Time Withstand Rating. These interruption ratings are based on the standard duty cycle consisting of an open operation,
a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short
42
time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the
two periods.
 Magnum MDSL Current Limiting Power Circuit Breaker With Integral Current Limiters. Current Limiter selected determines short time and fixed instan- 43
taneous trip rating. Maximum voltage rating is 600 Vac.
 Magnum MDSX Current Limiting Power Circuit Breaker With Fast Opening Contacts.
 Product to be tested. Contact Eaton for product rating.
 Breaker applied in a tested fan-cooled enclosure.

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-8
Power Circuit Breakers June 2006
Sheet 1100
Magnum DS Low Voltage Power Circuit Breakers

22 Magnum MDSL previous paragraph does not intersect Limiter Selection


the limiter characteristic line, the avail-
Current Limiting Power able system fault current is below the The selection of a suitable limiter
rating for a given application is
23 Circuit Breakers “threshold” current of that limiter, and
generally governed by a choice of
it will offer no current limiting effect.
the following types of protection:
The following curves illustrate the ratings,
melting time-current characteristics The current limiting principle is
A. Maximum protection of “down-
24 and current limiting, or let-through illustrated below:
stream” components. Type MDSL
characteristics, of limiters for Magnum la = The Available Peak Fault Current breakers are often used for this
Low Voltage Power Circuit Breakers. purpose even when the maxi-
25 tm = The Melting Time mum available fault currents are
The let-through current for a given
Ip = The Peak Let-Through Current within the interrupting rating
limiter application is readily determined
of the corresponding unfused
26 by extending a vertical line from the
ta = The Arcing Time Magnum breakers.
applicable maximum available sym-
metrical fault amperes at the bottom tc = The Total Interrupting (Clearing) B. Protection of the circuit breaker only.
27 margin to the characteristic line for Time
Case A would tend to use the smallest
the particular limiter, and from this
intersection extending a horizontal line available limiter; Case B the largest.
28 to the left margin and reading the peak When downstream protection is
current. The withstand rating of any required, the selection is usually
circuit elements protected by the a compromise, since certain small
Ia
29 limiters should be at least equal to
Ip
limiters cannot be coordinated with
this peak current. the breaker to avoid nuisance blowing
on overloads or small and moderate
30 It will be noted that the let-through tm ta short circuits.
current increases with the limiter size tc
or ampere rating; in other words, the Minimum, recommended and
maximum current limiting effect is maximum limiter sizes for Magnum
31 obtained with the smallest size. This Figure 27.1-1. Current Limiting MDSL breakers are given in the table
effect is to be expected, since the below.
32 resistance decreases as the rating
increases. If the vertical line from the
bottom margin as described in the
33 Table 27.1-3. Magnum MDSL Ratings
Magnum MDSL Sensor MDSL Current Limiter Selection Chart 
Breaker Frame Rating  and Rating
34 800 A 1600 A 2000 A Plug In

MDSL08 MDSL16 200 MA250 MA300 MA400 MA600  MA800 MB1200 MB1600 MB2000 MD2500 MD3000
35 MDSL08 MDSL16 250 MA400 MA600 MA800  MB1200 MB1600 MB2000 MD2500 MD3000
MDSL08 MDSL16 300 MA400 MA600 MA800  MB1200 MB1600 MB2000 MD2500 MD3000

36 MDSL08 MDSL16 400 MA600 MA800 MB1200  MB1600 MB2000 MD2500 MD3000
MDSL08 MDSL16 600 MA800 MB1200 MB1600 MB2000  MD2500 MD3000
MDSL08 MDSL16 800 MB1200 MB1600 MB2000 MD2500  MD3000
37 MDSL16 1000 MB1600 MB2000 MD2500  MD3000
MDSL16 1200 MB2000 MD2500  MD3000
MDSL16 MDSL20 1600 MD3000 
38 MDSL20 2000 MD3000 
 Select the current limiter based on the Magnum breaker frame and current sensor and rating plug as shown.
39 

Refer to MDSL current limiter curves for let-through and time characteristics.
The recommended ratings shown provide for reduced current let-through and breaker coordination within the trip unit settings. Selection of
current limiters below the recommended ratings shown provides lower current let-through, however, trip unit settings must be considered to avoid
nuisance operation.
40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-9
June 2006 Power Circuit Breakers
Sheet 1101
Magnum DS Low Voltage Power Circuit Breakers

100
90
1000
900
800
22
80 700
70 600
60 500
50 400
23
Peak Instantaneous Let-Through Current in Kilo – Amperes X 10

40 300
30 200

20
MD3000
MD2500
100
90
80
24
MD2000 70
10 60
MD1600 50
9
8 MD1200 40 MA250
MA800
7
6
5 MA600
30 MA300 25
4 20 MA400
MA400 MA500
3 MA300
26

Time in Seconds
10
MA250 9
8
MA800
2 7
6 MB1200
5
4 MB1600
1
.9
.8
.7
3

2
MB2000 27
.6 MB2500
.5
1
MB3000
.4
.3
.9
.8
.7
28
.6
.5
.2 .4
.3

.1
.2
29
.09
.08
.07 .1
.06 .09
.05
.04
.08
.07
.06
30
.05
.03 .04
.03
.02
.02 31
.01

10000
8000

40
50

80

8000
80000

20

30

60
70
90

9000
50000
60000

32
7000

700
800

2000
10000

20000
3000

5000
6000

100

7000
40000

70000

100000
700

2000

9000

400
500
600

3000

5000
30000
400

4000

90000
1000

200

900

4000
500
200

600
300

800

300

1000

6000
100

900

1 2 3 4 5 6 7 8 9 10

Available Current, rms Symmetrical Amperes x 10 Scale x 100 = Current in Amperes


33
Figure 27.1-2. Type Magnum DSL Limiters, Peak Let-Through Current Figure 27.1-3. Type Magnum DSL Limiters Average Melting Time-
Characteristics Current Characteristics
34

35

36

37

38

39

40

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-10
Power Circuit Breakers June 2006
Sheet 1102
Magnum SB Insulated Case Circuit Breakers

22 Magnum SB Magnum SB is a Low Voltage Insulated UL and ANSI Test Certifications


Case Circuit breaker family designed
Low Voltage Insulated Case for the performance and economic Magnum SB meets or exceeds the

23 Circuit Breakers requirements of UL 891 switchboards. applicable ANSI, NEMA, UL and CSA
standards, including:
■ Magnum SB Insulated Case
Circuit Breakers have Interruption ■ ANSI C37.13 (Low Voltage ac Power
24 ratings up to 100 kA at 635 Vac with Circuit Breakers Used in Enclosures).
continuous current ratings up to ■ ANSI C37.16 (Preferred Ratings,
6000 amperes. Related Requirements, and
25 ■ Magnum SB Insulated Case Circuit Application Recommendations for
Breakers have lighter-duty Short Low Voltage Power Circuit Breakers
Time Withstand ratings and fixed and ac Power Circuit Breakers).
26 internal instantaneous trips on ■ ANSI C37.17 (Trip Devices for ac and
most ratings, which is characteristic General Purpose dc Low Voltage
of UL 489 molded case breakers Power Circuit Breakers).
27 commonly used in UL 891 switch-
■ ANSI C37.50 (Test Procedures
boards. This provides for greater
for Low Voltage ac Power Circuit
economy and excellent coordination
28 Breakers Used in Enclosures).
and selectivity for most commercial
applications. ■ UL 1066 (Standard for Low Voltage
ac and dc Power Circuit Breakers
■ Fixed internal instantaneous trips
29 will be phased in on all SB Insulated
Used in Enclosures).
Magnum SB Low Voltage Insulated Case ■ NEMA SG3 (This standard adopts
Circuit Breakers are Designed for the Case Circuit Breakers rated 3200
amperes and below to provide an ANSI C37.16 in its entirety).
Performance and Economic Requirements
30 of UL 891 Switchboards extra safety factor by reducing the
energy let-through to downstream Comprehensive
circuits at the maximum instanta-
31 neous trip point and to facilitate Enclosure Solutions
feeder circuit breaker protection
in UL 891 switchboards with Magnum DS has proven performance
32 3-cycle bus bracing. in Eaton manufactured switchgear and
switchboards with the following test
■ Magnum SBSE Current Limiting
certifications:
33 Power Circuit Breakers have 150 kA
Interrupting Ratings at 480 Vac ■ UL 1558 (Magnum DS Low Voltage
with continuous current ratings up Metal-Enclosed switchgear).
34 to 5000 amperes. The Short Time ■ UL 891 (Pow-R-Line C
Withstand Rating is 30 kA for Low Voltage Switchboards).
standard frame and 50 kA for ■ UL, CSA 22.2.31 Low Voltage
35 double frame breakers. Assemblies.

Approvals
36 ■ UL listed: Magnum DS Breaker
UL File E52096 and Cassette
UL File E204565.
37

38
Typical Magnum SB Low Voltage Insulated
Case Circuit Breaker Nameplate
39

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-11
June 2006 Power Circuit Breakers
Sheet 1103
Magnum SB Insulated Case Power Circuit Breakers

Magnum SB Switchboard Class UL 1066 Insulated Case 22

23

24

25

26

27
Magnum SB Low Voltage Insulated Case Circuit Breaker Family UL Rated for Switchboard Applications
Table 27.1-4. Magnum SB Switchboard Class UL 1066 Insulated Case Low Voltage Power Circuit Breaker
28
Frame Breaker Frame rms Symmetrical Current Ratings kA 50/60 Hz  Available Current Sensor & Rating
Amperes Type Type Plugs for Digitrip RMS Trip Unit
(Establishes Breaker In rating)
29
Interrupting Interrupting Interrupting Short Time Fixed Internal
at 254 Vac at 508 Vac at 635 Vac Withstand Rating Inst Trip

800 SBN-508 Narrow 50 50 35 20  200, 250, 300, 400, 600, 800 30


SBN-608 Narrow 65 65 42 20 
SBN-C08 Narrow 100 100 65 20 18 x In
SBS-608 Standard 65 65 65 20  31
SBS-C08 Standard 100 100 85 20 
SBS-E08  Standard 200 150  30 30
1200 SBN-512 Narrow 50 50 35 25 

200, 250, 300, 400, 600, 800, 32
SBN-612 Narrow 65 65 42 25 1000, 1200
SBN-C12 Narrow 100 100 65 25 18 x In
SBS-612
SBS-C12
Standard
Standard
65
100
65
100
65
85
25
25


33
SBS-E12  Standard 200 150  30 30

1600 SBN-516
SBN-616
Narrow
Narrow
50
65
50
65
35
42
30
30 
200, 250, 300, 400, 600, 800,
1000, 1200, 1600
34
SBN-C16 Narrow 100 100 65 30 18 x In

SBS-616
SBS-C16
Standard
Standard
65
100
65
100
65
85
30
30  35
SBS-E16  Standard 200 150  30 30
2000 SBN-620 Narrow 65 65 65 35  200, 250, 300, 400, 600, 800,
SBN-C20 Narrow 100 100 65 35 18 x In 1000, 1200, 1600, 2000 36
SBS-620 Standard 65 65 65 35 
SBS-C20 Standard 100 100 85 35 
SBS-E20  Standard 200 150  30 30 37
2500 SBS-625 Standard 65 65 65 45  200, 250, 300, 400, 600, 800,
SBS-C25 Standard 100 100 85 45  1000, 1200, 1600, 2000, 2500
SBS-E25  Double 200 150  50 50 38
3000 SBS-630 Standard 65 65 65 50  200, 250, 300, 400, 600, 800,
SBS-C30 Standard 100 100 85 50  1000, 1200, 1600, 2000, 2500, 3000
SBS-E30  Double 200 150  50 50
39
4000 SBS-840 Double 85 85 85 85 — 2000, 2500, 3000, 4000
SBS-C40 Double 100 100 100 100 —
SBS-E40  Double 200 150  50 50 40
5000 SBS-850 Double 85 85 85 85 — 2500, 3000, 4000, 5000
SBS-C50 Double 100 100 100 100 —
SBS-E50  Double 200 150  50 50 41
6000 SBS-C60  Double 100 100 100 100 — 3000, 4000, 5000, 6000
 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are
equal to the published Short Time Withstand Rating. These interruption ratings are based on the standard duty cycle consisting of an open operation,
42
a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short
time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the
two periods. 43
 Fixed Internal Instantaneous Trip set at approximately 18 x In symmetrical will be phased into the product.
 Product to be tested. Contact Eaton for product rating.
 Magnum SBSE Current Limiting Power Circuit Breaker With Fast Opening Contacts.
 Breaker applied in a tested fan-cooled enclosure.

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-12
Power Circuit Breakers June 2006
Sheet 1104
Magnum IEC Rated Air Circuit Breakers

22 Magnum IEC Rated Magnum Air Circuit Breakers are Comprehensive


designed to enable global power
Air Circuit Breakers distribution solutions in IEC switch- Enclosure Solutions
boards and other custom enclosures.
23 Magnum Air Circuit Breakers have
■ Magnum IEC Air Circuit Breakers proven performance in IEC switch-
have interruption ratings up to boards and custom enclosures manu-
24 100 kA at 690 Vac with continuous factured by Eaton and Low Voltage
current ratings up to 6300 amperes. Systems Builders (OEMs) to the
■ Magnum IEC Air Circuit Breaker following standards:
25 continuous current frames are ■ EN/IEC 60947-1.
100% rated. No thermal de-rating
■ EN/IEC 60439-1.
is required when applying the
26 breaker in the low voltage systems ■ Eaton manufactured IEC Low Volt-
enclosure at ambient temperatures age Switchboard solutions include:
of 40°C. ❑ Eaton MEM M-Form (UK)
27 ■ Magnum IEC Breakers carry the Low Voltage Switchboards
KEMA Keur Mark, which requires ❑ Eaton Holec Capitole 40 and
periodic follow-up testing, wit- Capitole 20 (Holland) Low Voltage
28 nessed by KEMA, to demonstrate Switchboards
our product performs to its pub- ❑ Eaton Tabula Low Voltage
lished nameplate ratings. This
29 differentiates Magnum Air Circuit
Switchboard Systems (Global) for
Low Voltage Systems Builders
Magnum Narrow Frame Drawout Breakers from competition, who
Air Circuit Breaker With Cassette generally self-tests their product ❑ Eaton Elatis (Germany) Low
30 when it is first introduced and is Voltage Switchboards
not bound to perform subsequent
follow-up third-party testing. Approvals and Marks
31 Magnum Air Circuit Breakers carry
IEC Test Certifications the following approvals and approval
marks:
32
Magnum Air Circuit Breakers meet or ■ CE.
exceed the applicable IEC standards,
■ KEMA Keur mark.
33 including:
■ ABS (American Bureau of Shipping)
■ EN/IEC 60947-2. Type Listed Certificate Number
The KEMA Keur Mark on the Magnum
■ KEMA third-party witness and 04-HS422844B-PDA-DUB.
34 ACB Label Confirms Third-Party Witness
and Follow-up Testing follow-up testing. ■ CCC (Certificate for China
Compulsory Product Certification)
35 to GB14048.2-2001, Certificate
Numbers:
❑ 2005010307139381
36 ❑ 2003010307094561
❑ 2003010307094558
37

38

39

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-13
June 2006 Power Circuit Breakers
Sheet 1105
Magnum IEC Rated Air Circuit Breakers

Magnum IEC 60947-2 Rated 22

23

24

25

26

27

Magnum IEC Low Voltage Air Circuit Breaker Family


28
Table 27.1-5. Magnum IEC 60947-2 Rated Air Circuit Breakers
Frame Breaker Frame rms Symmetrical Current Ratings kA  29
Amperes Type Type Interrupting Interrupting Interrupting Withstand Rating Fixed Available Current Sensor & Rating
at 240 Vac at 440 Vac at 690 Vac Icw Internal Plugs for Digitrip RMS Trip Unit
Icu = Ics Icu = Ics Icu = Ics 1-Sec / 3-Sec Inst. Trip (Establishes Breaker In Rating) 30
800 MWN-408 Narrow 40 40 40 40 / — — 200, 250, 300, 400, 630, 800
MWN-508
MWN-608
Narrow
Narrow
50
65
50
65
50
65
50 / —
65 / 40


31
MWI-608 Standard 65 65 65 65 / — —
MWI-808 Standard 85 85 85 85 / 65 —
MWI-C08 Standard 100 100 85 85 / 65 85
32
1000 MWN-410 Narrow 40 40 40 40 / — — 200, 250, 300, 400, 630, 800, 1000
MWN-510 Narrow 50 50 50 50 / — —
MWN-610 Narrow 65 65 65 65 / 40 — 33
MWI-610 Standard 65 65 65 65 / — —
MWI-810 Standard 85 85 85 85 / 65 —
MWI-C10 Standard 100 100 85 85 / 65 85 34
1250 MWN-412 Narrow 40 40 40 40 / — — 200, 250, 300, 400, 630, 800,
MWN-512 Narrow 50 50 50 50 / — — 1000, 1250
MWN-612 Narrow 65 65 65 65 / 40 — 35
MWI-612 Standard 65 65 65 65 / — —
MWI-812 Standard 85 85 85 85 / 65 —
MWI-C12 Standard 100 100 85 85 / 65 85 36
1600 MWN-516 Narrow 50 50 50 50 / — — 200, 250, 300, 400, 630, 800,
MWN-616 Narrow 65 65 65 65 / 40 — 1000, 1250, 1600
MWI-616 Standard 65 65 65 65 / — — 37
MWI-816 Standard 85 85 85 85 / 65 —
MWI-C16 Standard 100 100 85 85 / 65 85
2000 MWN-520 Narrow 50 50 50 50 / 30 — 200, 250, 300, 400, 630, 800, 38
MWN-620 Narrow 65 65 65 65 / 40 — 1000, 1250, 1600, 2000
MWI-620 Standard 65 65 65 65 / 50 —
MWI-820
MWI-C20
Standard
Standard
85
100
85
100
85
85
85 / 65
85 / 65

85
39
2500 MWI-625 Standard 65 65 65 65 / — — 200, 250, 300, 400, 630, 800,
MWI-825
MWI-C25
Standard
Standard
85
100
85
100
85
85
85 / 65
85 / 65

85
1000, 1250, 1600, 2000, 2500 40
3200 MWI-632 Standard 65 65 65 65 / 50 — 200, 250, 300, 400, 630, 800,
MWI-832 Standard 85 85 85 85 / 65 — 1000, 1250, 1600, 2000, 2500, 3200
MWI-C32 Standard 100 100 85 85 / 65 85 41
4000 MWI-64N Double 65 65 65 65 / — — 2000, 2500, 3200, 4000
MWI-84N Double 85 85 85 85 / — —
MWI-C4N Double 100 100 100 100 / — — 42
5000 MWI-85N Double 85 85 85 85 / — — 2500, 3200, 4000, 5000
MWI-C5N Double 100 100 100 100 / — —
6300 MWI-86N Double 85 85 85 85 / — — 3200, 4000, 5000, 6300
43
MWI-C6N Double 100 100 100 100 / — —
 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are equal
to the published breaker Icw Rating.

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-14
Power Circuit Breakers June 2006
Sheet 1106
Breaker-Mounted Options

Breaker-Mounted Options ■ Bell Alarm/Overcurrent Trip Switch


22 (OTS). Provides 2 Form C
Magnum breakers are available with (changeover) contacts that change
a comprehensive array of factory- state when the Digitrip RMS trip unit
23 installed breaker options to enable acts to trip the breaker on an over-
configured-to-order solutions for spec- current condition. The contacts are
ified customer requirements. Field available for external indication or
24 option kits are available to provide customer use and are manually
easy service, modification and reset by the Mechanical Trip
customization of the breaker at the Indicator.
25 point of use. ■ Padlockable Pushbutton Cover.
Permits padlocking hinged cover
■ Shunt Trip device (ST). Provides
plates to block access to the PUSH
26 for remote electrically controlled
ON and PUSH OFF buttons on the Auxiliary Switches Come in Modular 2a/2b
breaker opening when energized Contact Stages Providing up to 6a/6b
breaker faceplate.
by a rated voltage input. Dedicated Contacts
■ Mechanical Operations Counter.
27 ■ Spring Charge Motor (MOT).
Records mechanical operations of
Charges the breaker closing springs
the breaker over its installed life.
automatically, facilitating remote or
28 local closing. The motor assembly ■ Key Off Lock Provisions. Enables
includes its own cut-off switch mounting of a single cylinder Kirk,
that changes state at the end of the Castell, or Ronis Key Lock to lock the
29 charging cycle. This contact can be breaker in the OPEN position.
wired out for external indication. ■ Latch Check Switch. Provides 1
■ Spring Release device (SR). Form C (changeover contact) that
30 Provides for remote electrically changes state when the breaker is
controlled breaker closing when ready to close. Can be wired to the
its coils are energized by a rated Spring Release Device for fast
31 voltage input. transfer applications or wired for
external ready-to-close indication.
■ Undervoltage Release (UVR).
32 Trips the breaker when an existing
voltage signal is lost or falls
below an established threshold.
33 ■ Auxiliary Switch. Up to 6a/6b
auxiliary individual dedicated con-
tacts are available for customer use
34 to indicate if the breaker is in the
Mechanical Trip Indicator With Bell Alarm
OPEN or CLOSE position.
(OTS) Switches Mounted
■ Mechanical Trip Indicator Flag. The
35 red trip indicator flag pops out to
provide local visual indication when
the Digitrip RMS trip unit acts to trip
36 the breaker on an overcurrent
condition.
37

38 Shunt Trip, Spring Release and


Undervoltage Release Device Installed
on Accessory Deck
39

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-15
June 2006 Microprocessor Trip Units
Sheet 1107
General Description — Magnum DS and SB Trip Units

Digitrip RMS Trip Unit Family Digitrip RMS Trip Units are highly
accurate microprocessor-based
All Trip Units include three important
22
self-protecting safety features are
for Magnum Circuit Breakers protective devices that use a patented provided as standard:
sampling algorithm to compute
The Magnum family of Digitrip RMS true rms values for precise system Making Current Release (MCR): 23
Trip Units consists of four trip unit coordination and metering. The trip employs a fast acting analog instanta-
models, each providing increasing unit is completely self-contained and neous trip that prevents the breaker
levels of features and options to requires no external control power from closing and latching on a fault 24
enable the ultimate selection to to perform its overcurrent protective when the peak current exceeds 25 x
match application requirements for functions because the power to oper- the breaker In rating. This reduces arc
protection, coordination, information, ate the trip unit is derived from the flash energy during breaker closing for 25
diagnostics and communication: primary current passing through the faults within the self-protecting range.
current sensors. When the trip unit The MCR is enabled for the first 2
■ Digitrip RMS 520
■ Digitrip RMS 520M is operating, the green unit status cycles following the circuit breaker 26
LED begins to blink like a heartbeat closing operation and thereafter,
■ Digitrip RMS 520MC depending on the type of Magnum
to visibly confirm the microprocessor
■ Digitrip RMS 1150+ is powered up. breaker applied, becomes inactive. 27
The trip unit overcurrent protective Over-Temperature Protective Trip:
Common Trip Unit Features automatically trips the breaker when
A summary of the important features
pick-up settings are a function of the
the temperature inside the trip unit
28
breaker In rating, which is established
common to all Magnum Trip Units is by the rating plug and current sensors. exceeds 85 Degrees C, which indicates
as follows: that there are significantly higher
When preset conditions are exceeded,
temperatures within enclosure.
29
■ Microprocessor-based true the trip unit initiates a trip signal to
rms sensing. the trip actuator, tripping the circuit Thermal Memory: provides over-
■ Discrete rotary or programmable
breaker. Red cause of trip LEDs light temperature protection on load 30
up to indicate the cause of trip, pow- circuits against effects of repeated
settings.
ered by a easily replaceable back-up overload conditions. This feature is
■ Unit status LED (green). battery located behind the rating plug. defeatable for special applications 31
■ Cause of trip LEDs (red). The LED will flash to save power, until such as welding and primary
■ Battery check LED (green). the trip unit reset button is depressed. injection testing.
■ Reset/battery test pushbutton. 32
■ Making current release.
■ Thermal memory. 33
■ Over-temperature protective trip.
■ Zone selective interlocking (ZSI)
provisions. 34
■ Rating plug receptacle.
■ Back-up battery for cause of
trip LEDs.
35
■ Test kit receptacle with cover.
■ Plug-in mounting for easy 36
replacement.
■ Clear plastic cover (sealable).
37

38

39

40

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-16
Power Circuit Breakers June 2006
Sheet 1108
General Description — Magnum DS and SB Trip Units

22 Trip Units There are three ways to arm the Main-


tenance Mode Arc Flash Reduction
Eaton’s electrical business introduced setting. One method is locally at the
the first microprocessor based trip unit trip unit front panel. For the 520MC, the
23 and has advanced the technology into two-position switch in the Maintenance
a new family of UL and CSA listed Mode section of the trip unit is used.
Digitrip RMS Electronic and Program- Turning the switch to the ON position
24 mable Trip Units designed and engi- will arm the setting. For the 1150+,
neered exclusively for Magnum DS the local front keypad is used to enable
Breakers the Maintenance Mode setting. The set-
25 ting is located in the SYSTEM submenu
of programmable settings (PGM SET).
Electronic Trip Units
26 ■ Digitrip RMS 520 enables the user
For the second method of arming the
Maintenance Mode function, a remote
as many as nine phase and ground switch wired through the breaker
27 current protection settings for maxi-
mum flexibility in trip-curve shaping
secondary contacts can remotely
arm the Maintenace Mode setting. A
and multi-unit coordination and high quality gold plated or palladium
28 adds ground current protection contact is required in this application.
settings.
■ Digitrip RMS 520M adds phase, Magnum 520MC Trip Unit With ARMs A third method to arm that mainte-
Technologies Arc Flash Reduction, nance setting is via a communication
29 neutral and ground current
4 Digit LCD Display, and Ampere Based device. A Palm Pilot along with an IR
metering with a four-character Communications
LCD display window. Mint device can be employed to arm
the setting. By initiating the ENABLE,
30 ■ Digitrip RMS 520MC adds communi-
the Maintenance Mode selection in
cation of current values and breaker the control screen of the Palm, Mainte-
status (open, closed, tripped). nance Mode is set. There is a confir-
31 mation screen that verifies the arming.
Programmable Trip Units A BIM (Breaker Interface Module) or
32 PowerNet system is another commu-
■ Digitrip RMS 1150+ provides pro- nication method to arm the setting.
grammability for more sophisticated
distribution systems. The Arc Flash Reduction Maintenance
33 setting has five unique settings (2.5, 4.0,
❑ Increased protection and coordi-
6.0, 8.0, 10.0 x In). To adjust this setting,
nation capabilities. a rotary switch on the trip unit face is
34 ❑ Systems monitoring information provided for the 520MC while the 1150+
including power factor, voltage, trip unit uses its local keypad.
current, harmonic distortion
35 values and waveform capture For all three arming methods, the
with a bright three-line, (eight 520MC provides a blue LED to confirm
characters per line) LED display. the Maintenance Mode function is on.
36 ❑ Two programmable contacts for
In addition, there is also a normally
open breaker contact that allows the
customer use. user to wire in an external stacklight or
37 ❑ Time and date stamping of trip annunciator for remote indication. For
events for improved trouble- the 1150+, the message “Maintenance
shooting and diagnostics. Magnum 1150+ Trip Unit With ARMs
Mode Enabled” will be shown on its
Technologies Arc Flash Reduction,
38 ❑ Accuracy of 1% on current and 24-Digit LED Display, Programmable LED display. The 1150+ also has an
voltage values and 2% on energy Protection, Alarms and Relaying, Power alarm relay that can be programmed
and power. Metering, Power Quality and Alarms, to track the Maintenance Mode state.
39 ❑ Systems diagnostic information
Waveform Capture, Communications,
The Maintenance Mode function will
and Breaker Health Monitoring
and breaker Health menu. provide fast tripping even when the
40 ❑ PowerNet communications.
ARMs Technologies and
regular Instantaneous is set to OFF.
The Instantaneous LED position is
❑ ARMs Technologies for arc flash
reduction. Arc Flash Reduction also used to indicate a trip initiated
41 by the Maintenance Mode setting.
The ARMs Maintenance Mode func- The 520MC LCD display, if powered,
tion of the Digitrip 520MC and 1150+ will indicate with four dashes while
42 can reduce arc flash incident energy the 1150+ will display the message
that is generated on a fault condition. “Maintenance Mode Trip.”
This is accomplished by an analog trip
43 circuit which when armed provides a
fast-acting response to the fault. This
is separate from the normal system
protection setting of instantaneous.

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-17
June 2006 Microprocessor Trip Units
Sheet 1109
General Description — Magnum DS and SB Trip Units

Digitrip 520 Trip Unit Digitrip 520M Trip Unit Digitrip 520MC Trip Unit
22

23

24

25

26

27
Digitrip 520 Trip Unit with Digitrip 520M Trip Unit with 4 Digit LCD Digitrip 520MC Trip Unit With ARMs
Basic Overcurrent Protection Display and Ampere-based Metering, Technologies Arc Flash Reduction,
Alarms, and System Diagnostics 4 Digit LCD Display, and Ampere Based 28
The Digitrip 520 is a simple basic Communications
trip unit with three available types The Digitrip 520M is available with
of protection (LI, LSI and LSIG). three types of protection (LSI, LSIG The Digitrip 520MC is available in 29
Up to nine rotary-type current and and LSIA) and includes the following three types of protection (LSI, LSIG
time settings provide for maximum added features: and LSIA) and includes the following
flexibility in curve-shaping and enhancements: 30
■ 4 Digit LCD Display with a step
multi-unit coordination.
pushbutton to scroll through the ■ Communications of ampere based
■ The Instantaneous function (I) display data, including ampere- data, breaker status, and cause of
includes an off position setting based metering of phase, neutral, trip information using the INCOM 31
when Short Time (S) protection is and ground currents, plus opera- communications system. Each trip
provided to increase application tional, and cause-of-trip diagnostic unit has a unique hexadecimal
flexibility in the field. information. address (001 to 999) set by rotary 32
■ I2t Time Delay Settings for better ■ When specified, the Power Relay switches. A red Transmit LED is
provided to confirm communica-
curve shaping when Short Time (S) Module (PRM) is supplied to
tions activity. Peripheral translator 33
and Ground Fault (G) protective perform the following features:
functions are selected. devices are available to convert
❑ Power up the trip unit display
INCOM to other protocols like
■ Zone Selective Interlocking (ZSI) from an external customer sup- Modbus, Ethernet, etc. 34
provided when Short Time (S) plied source through the breaker
■ ARMs Technologies for arc flash
and/or Ground Fault (G) protective secondary contacts to retain the
functions are selected. ZSI provides cause of trip and magnitude of reduction allows the operator to 35
hard-wired positive system coordi- trip information. enable a special trip unit mainte-
nation, allowing the breaker closest nance mode with a preset acceler-
❑ Provide relay contact for remote ated instantaneous override trip that
to the fault to trip first, thus avoiding indication of overload (LSI) or can reduce Arc Flash Energy up to
36
unnecessary and costly system Ground Trip (LSIG), or Ground
downtime. ZSI is a useful method 30%. The arc flash reduction level
Alarm (LSIA). is preset at the trip unit using a 5
to reduce arc flash.
■ Type LSIA units alarm only when position switch which facilitates
37
ground fault settings are exceeded, the maximum arc flash reduction
which is quite useful in critical
power applications.
setting possible while avoiding nui-
sance tripping. Arms can be turned
38
■ Plug Receptacle for Auxiliary Power on locally at the trip unit or remotely
Module to power up the trip unit using peripheral devices like a PDA 39
display during bench testing remote with an IRMint, a logic level control
from the Switchgear. switch, or via communications. A
blue LED provides local indication 40
the trip unit is in the Maintenance
Mode. Remote indication can be
accomplished by a dedicated trip 41
unit contact for use with a stack light
or annunciator panel or via commu-
nications by a dedicated trip unit 42
contact for use with a stack light
or annunciator panel.
43

CA08104001E For more information visit: www.EatonElectrical.com


27.1-18 Power Circuit Breakers & Insulated Case Circuit Breakers
Microprocessor Trip Units June 2006
Sheet 1110
General Description — Magnum DS and SB Digitrip Trip Units

Digitrip 1150+ Trip Unit ■ Health menu — The Health menu ■ Communications of comprehensive
22 on the Digitrip 1150+ front panel will access to trip unit capabilities
provide information on the Magnum including programmable settings,
Circuit Breaker’s Health, as well as breaker control, metering, alarm,
23 a history of the circuit breaker and status, relaying and diagnostic
circuit it is protecting. This data is information. Peripheral translator
useful for planning maintenance devices are available to convert
24 and inspection schedules. The type INCOM to other protocols like
of data includes the total number of Modbus, Ethernet, etc.
all Instantaneous and Short Delay ■ Accessory bus for use with periph-
25 trips seen by the circuit breaker. A eral digital relay modules, which
second counter shows the number can be programmed through the trip
of Overloads (LDT) and Ground unit keypad for additional auxiliary
26 Faults (GFT) encountered while in and various alarm contacts.
service. The OP count provides data ■ ARMs Technologies for arc flash
on the number of Close Operations reduction.
27 Digitrip 1150+ Trip Unit
experienced by the circuit breaker.
■ ARMs Technologies for arc flash
The last time the circuit breaker was
operated (open or closed or tripped) reduction allows the operator to
The Digitrip 1150+ Trip Unit is a highly
28 advanced programmable protective is viewable with time and date enable a special trip unit mainte-
displayed. Also included is the nance mode with a preset acceler-
device available in three types of
maximum temperature in degrees ated instantaneous override trip that
protection (LSI, LSIG and LSIA).
29 The following is a first level summary Centigrade as seen by the Digitrip can reduce Arc Flash Energy up to
microprocessor CHip. The capture 30%. The arc flash reduction level
of the special features and options:
of the data requires external is preset at the trip unit using a 5
30 ■ 24-character LED Digital Display Trip Unit power. This data, once position switch which facilitates
easily visible from 50 feet and ideal captured, is stored in non volatile the maximum arc flash reduction
for dark equipment environments. memory. These features are avail- setting possible while avoiding nui-
31 ■ Membrane type dust-resistant able for remote communications. sance tripping. Arms can be turned
keypad pushbuttons to facilitate on locally at the trip unit or remotely
■ Programmable alarm contacts or
local unit programming, including using peripheral devices like a PDA
trip contacts.
32 View Functions (Up, Down, ESCape, with an IRMint, a logic level control
■ Programmable relay functions switch, or via communications. A
SELect and Reset), Edit Values (Up,
including undervoltage, overvoltage, blue LED provides local indication
Down, and Save), and Battery Test.
33 ■ Programmable trip unit settings
underfrequency, overfrequency, the trip unit is in the Maintenance
reverse power, voltage unbalance, Mode. Remote indication can be
and curves including I2t and I4t and phase rotation. accomplished by a dedicated trip
curves, as well as IEEE Moderately
34 Inverse, Very Inverse, and Extremely
■ Breaker Health Monitoring with unit contact for use with a stack light
critical intelligence for planning or annunciator panel or via commu-
Inverse curves.
maintenance and inspection nications by a dedicated trip unit
35 ■ Voltage and power metering. schedules. contact for use with a stack light
■ Power quality monitoring and alarm or annunciator panel.
with THD and waveform capture.
36

37

38

39

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-19
June 2006 Microprocessor Trip Units
Sheet 1111
Selection Guide — Magnum DS and SB Digitrip Trip Units

Table 27.1-6. Digitrip Trip Units for Magnum DS and SB ANSI/UL Rated Power Circuit Breakers
22

23

24
Trip Unit Type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ 

Ampere Range 200 A – 6000 A 200 A – 6000 A 200 A – 6000 A 200 A – 6000 A 25
Interrupting Rating at 480 V 42 through 200 kA 42 through 200 kA 42 through 200 kA 42 through 200 kA
rms Sensing Yes Yes Yes Yes
Protection and Coordination 26
Protection Ordering Options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed Rating Plug (In) Yes Yes Yes Yes
Overtemperature Trip Yes Yes Yes Yes 27
Long Long Delay Pickup 0.4 – 1.0 x (In) 0.4 – 1.0 x (In) 0.4 – 1.0 x (In) 0.4 – 1.0 x (In)
Delay Long Delay Time I2t at 6 x Ir 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds
Protection Long Delay Time I4t No No No 1 – 5 Seconds 28
(L) IEEE Curves No No No Yes
Long Delay Thermal Memory Yes Yes Yes Yes
High Load Alarm No No No 0.5 – 1.0 x (Ir)
Short Short Delay Pickup 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1
29
Delay Short Delay Time I2t at 8 x Ir 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
Protection Short Delay Time Flat 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
(S) Short Delay Time ZSI Yes Yes Yes Yes 30
Instanta- Instantaneous Pickup 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1
neous Making Current Release Yes Yes Yes Yes
Protection Off Position LSI & LSIG Yes Yes Yes 31
(I)
Ground Ground Fault Alarm No Yes Yes Yes
Fault
Protection
Ground Fault Pickup 25 – 100% x (In)
Ground Fault Delay I2t at .625 x In 100 – 500 ms
25 – 100% x (In)
100 – 500 ms
25 – 100% x (In)
100 – 500 ms
24 – 100% x (In)
100 – 500 ms
32
(G)  Ground Fault Delay Flat 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
Ground Fault ZSI Yes Yes Yes Yes
Ground Fault Thermal Memory Yes Yes Yes Yes 33
Disable Ground Fault Protection No No No No
Neutral Protection (N) Model LSI Model LSI Model LSI Model LSI 34
System Diagnostics
Cause of Trip LEDs Yes Yes Yes Yes
Magnitude of Trip Information No Yes Yes Yes 35
Remote Signal Contacts No Yes Yes Yes
Programmable Contacts No No No Yes
System Monitoring 36
Digital Display No 4-Character LCD 4-Character LCD 24-Character LED
Current (% ) Full Scale Sensor No Yes +/- 2% Yes +/- 2% Yes +/- 1%
Voltage (%) L to L No No No Yes +/- 1% 37
Power and Energy (%) No No No Yes +/- 2%
Apparent Power kVA and Demand No No No Yes
Reactive Power kvar No No No Yes 38
Power Factor No No No Yes
Crest Factor No No No Yes
Power Quality — Harmonics No No No Yes 39
% THD, Waveform Capture No No No Yes
System Communications
Type No No INCOM/PowerNet INCOM/PowerNet/TripLink 40
Power Supply in Breaker N/A Optional Standard Standard
Additional Features
Trip Log (3 Events) No No No Yes 41
Electronic Operations Counter No No No Yes
Testing Method  Test Set Test Set Test Set Integral and Test Set
Waveform Capture No No No Yes 42
ARMs (Arc Flash Reduction Mode) No No Yes Yes 
Breaker Health Monitor No No No Yes
Programmable Relay Functions No No No Yes  43
 Over and Undervoltage Alarm or Trip, Over  1200 ampere maximum ground fault setting
and Underfrequency Alarm or Trip, Voltage per UL/NEC. Legend: In = Rating Plug and Sensor Rating.
Unbalance Alarm or Trip, Reverse Power  Test set for secondary injection. Ir = Long Delay Pickup setting.
Trip, and Phase Rotation Alarm are included.  Contact Eaton for availability.

CA08104001E For more information visit: www.EatonElectrical.com


27.1-20 Power Circuit Breakers & Insulated Case Circuit Breakers
Microprocessor Trip Units June 2006
Sheet 1112
Technical Data

Time-Current Curve Shaping Ground Fault (G) Zone Selective Interlocking


22 6. Ground Fault Pickup Zone selective interlocking provides
Determines the level of fault positive system coordination by allowing
current at which the ground fault the breaker closest to the fault to trip
23 trip delay countdown is actuated. without any preset time delays. This is
1
7. Ground Fault Delay achieved by setting up the distribution
system as shown in Figure 27.1-2.
24 2
2B Determines the amount of time
the breaker will carry a ground The hardwired connection between
2A
fault before tripping. the trip units sends a restraining signal
upstream allowing the breaker closest
25 3 a. Flat Response to the fault to act instantaneously. Zone
4B I2t out: For coordination with
Time

selective interlocking also reduces


other circuit breakers with stress on the distribution system by
26 6 4A
4
electronic ground fault settings.
isolating faults without time delays.
b. I2t Response
I2t in: For coordination with
27 5
zero sequence ground fault
7B
relays, fuses, and thermal-
7 magnetic breakers.
28 7A
Current in Multiples

29 Figure 27.1-4. Time-Current Curve Shaping


Note: See selection guide charts for avail-
ability of adjustments.
30 Ground Fault Setting:
Long Delay (L) 0.5 Seconds Time Delay
Zone 1
1. Long Delay Pickup Breaker
31 Determines the continuous
Number 1

ampere rating of the breaker. Fault 1

32 2. Long Delay Time Ground Fault Setting:


Determines the amount of time
the breaker will carry a low level Zone 2 0.3 Seconds Time Delay

33 overload before tripping.


a. I2t Response
I2t in: For coordination with other Breaker
34 circuit breakers with electronic Number 2

trip devices and for coordination Fault 2


Zone Selective
Interlocking Wiring
with thermal-magnetic
35 circuit breakers.
b. I4t Response Zone 3
I4t in: For coordination with Ground Fault Setting:
36 fuses and upstream trans-
300 A Pickup
No Time Delay
former damage curves. Breaker
Number 3

37 Short Delay (S)


Fault 3
3. Short Delay Pickup
Determine or set the level of fault
38 current at which the short time trip Load
delay countdown is actuated.
4. Short Delay
39 Sets the amount of time the breaker
Figure 27.1-5. Zone Selective Interlocking
will carry both a low level and high Fault 1 Fault 3
fault currents before tripping.
40 There are no interlocking signals. The branch breaker trip unit will initiate
a. Flat Response The main breaker trip unit will initiate the trip instantaneously to clear the fault;
I2t out: For coordination with the trip instantaneously. and Zone 3 will send an interlocking sig-
41 other circuit breakers with
Fault 2
nal to the Zone 2 trip unit; and Zone 2
will send an interlocking signal to Zone 1.
electronic trip devices.
The feeder breaker trip unit will initiate
b. I2t Response the trip instantaneously to clear the
Zone 1 and Zone 2 trip units will begin
42 I2t in: For coordination with fuses fault; and Zone 2 will send an inter-
to time out, and in the event that the
and thermal-magnetic breakers. branch breaker in Zone 3 would not
locking signal to the Zone 1 trip unit.
clear the fault, the feeder breaker in
The Zone 1 trip unit will begin to time
43 Instantaneous (I)
out, and in the event that the feeder
Zone 2 will clear the fault in 0.3 sec-
5. Instantaneous Pickup onds. Similarly, in the event that the
breaker in Zone 2 would not clear
Determines the level of fault feeder breaker in Zone 2 would not
the fault, the main breaker in Zone 1
current which will actuate a trip clear the fault, the main breaker in Zone
will clear the fault in 0.5 seconds.
with no time delay. 1 will clear the fault in 0.5 seconds.

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-21
June 2006 Power Circuit Breakers
Sheet 1113
Accessories

Magnum Peripheral Devices Time Delay Undervoltage (TDUVR) Digital Relay Accessory Module
22
(DRAM)
Modbus Translator Module (mMINT)
23

24

25

26

27

28
Time Delay Undervoltage
Digital Relay Accessory Module
Modbus Translator Module
The Magnum Time Delay Undervolt- 29
age is a DIN mounted accessory The DRAM is a DIN mounted
device applied in concert with a Mag- accessory device with four Form C
The mMINT (Modbus Master INCOM Net-
work Translator) is a DIN mounted acces-
num, Series C or Series G breaker contacts that can be programmed by 30
mounted instantaneous UVR to pro- the Digitrip 1150+ for indication of any
sory that facilitates communication with
vide an adjustable time delay ride combination of the following condi-
a Modbus RTU Network and as many as
32 Digitrip 520MC and 1150+ Trip Units
through on a temporary loss of volt- tions: auxiliary switch, INST, SDT, LDT, 31
age. Selectable time delay settings are GndT, GFAlm, HLAlm, DEADman, etc.
or other INCOM communications devices
0.1, 0.5, 1 and 2 seconds. Models are using the Trip Unit communications
by passing Modbus registers tranparently
between the two networks.
available for 120 Vac and 230 Vac bus function. 32
applications.
Wireless Transceiver (IRMINT) Other Protocol Translators
and PDA
BIM
To facilitate diverse communications
33
from INCOM to other protocols, Eaton
offers a host of translator devices
including MINTII (RS-232), EtherNet
34
(EMINT and NetLink), Modbus
(mMINT and ELINK), Wireless,
(IRMINT) etc. Contact Eaton for the
35
status of future product development,
including EtherNet Web-based server 36
and other communication
technologies.
37

38

39

BIM 40
Wireless Transceiver The Breaker Interface Module (BIMII)
is a panel mounted device that pro- 41
The wireless transceiver (IRMINT) is a vides a central monitor and display for
panel mounted device that facilitates as many as 50 Magnum 520MC and
central infrared wireless communica- 1150+ Trip Units or other INCOM com- 42
tions between a PDA and as many munications devices. The BIMII can be
as 64 Magnum 520MC and 1150+ Trip mounted directly on the switchgear or
Units or other INCOM communications may be located up to 10,000 feet away 43
devices. The IRMINT can be mounted using twisted pair shielded cable.
directly on the switchgear or may be
remotely located up to 10,000 feet away
using twisted pair shielded cable.

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-22
Power Circuit Breakers June 2006
Sheet 1114
Accessories

22 Accessories and Lifting Yoke and Hand-Held Test Kit


Peripheral Devices Floor Lifting Device
Magnum breakers include lifting ears
23 Levering Tool on each side to accept a lifting yoke
(or suitable sling) to facilitate lifting
using a skyhook from a top of gear
24 lifter, floor lifter or crane. Various lift-
ing yoke style numbers are available
for all Magnum frame types in both
25 3-pole and 4-pole configurations.
A roll-on-the-floor lifting device style
26 number 6727D63H20 is equipped with
a skyhook for use in conjunction
with a breaker lifting yoke or suitable
27 sling to lift the breaker from above.
Shelf-type roll-on-the-floor lifters can
also be used to lift the breaker from
28 Levering Tool
underneath without a lifting yoke.
Hand-Held Test Kit

Magnum drawout breakers are A hand-held test kit Catalog Number


29 designed for closed door manual lever- MTST120V or MTST240V is available
ing by use of a standard 3/8-inch (10 to functionally test Magnum and
mm) drive set, which is a commonly Series G breakers equipped with
30 available tool. This eliminates the need Digitrip Trip Units. The kit includes
for a unique levering device, which test cords and faceplate templates
tends to get lost if not properly stored. to match the breaker being tested,
31 and an auxiliary power module.
Remote Power Racking System
(Type RPR-2) Auxiliary Power Module
32 The auxiliary power module
Catalog Number PRTAAPM120V
or PRTAAPM240V plugs into the
33 receptacle located in the front of the
trip unit to power the display and/or
34 communications functions during
bench testing. An input power cord
is provided for connection to a
35 120 Vac or 230 Vac source.

Secondary Injection Test Kit


36 Floor Lifting Device and Adapter
Test Cabinet A test kit style number 8779C02G05
is available for secondary injection
37 The test cabinet is a separately testing of Magnum breakers with
mounted device with Open and Close Digitrip Trip units and includes the test
Pushbuttons that facilitates bench test- kit adapter Catalog Number MTADPTC.
38 Remote Power Racking System ing of electrically operated Magnum An input power cord is provided for
breakers. An input power cord is pro- connection to a 120 Vac, 15 A source.
For maximum safety during drawout vided for connection to a 120 Vac, 15 A
39 breaker levering operations, the RPR-2 plug receptacle. The test cabinet out- TripLink Cable
Universal Remote Power racking put power is matched to the breaker
System (RPR-2) can be employed on control voltage(s) and is connected to TripLink cable style number
40 Magnum, as well as other drawout the breaker via a cord, which plugs 5720B59G01 enables the downloading
low and medium voltage power circuit into the breaker secondary contacts. of the trip unit protection settings and
breakers that use rotation of a shaft for circuit data from one Digitrip 1150+
41 insertion or removal. Remote control is Trip Unit to another, which saves time
accomplished by an operator pendant during startup and maintenance.
with an INSERT and REMOVE pushbut-
42 ton station and a 25-foot connecting
cable. The RPR-2 requires 120 Vac, 15 A
power from a common plug receptacle.
43 Status indication and selectable torque
limitation matched to the breaker rack-
ing mechanism are also provided.

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-23
June 2006 Power Circuit Breakers
Sheet 1115
Technical Data

Table 27.1-7. Magnum DS & SB Breaker Control Device Application Guide — Vdc
Breaker Control Device 24 Vdc 32 Vdc 48 Vdc 125 Vdc 250 Vdc 22
Nominal Voltage

Shunt Trip (ST)


Operational Voltage Range
Trip Circuit
70 to 110 % 17 – 26 Vdc

34 – 53 Vdc 77 – 138 Vdc 154 – 275 Vdc
23
Power Consumption (Inrush) (Required for 35 ms) 250 Watts 250 Watts 450 Watts 450 Watts
Opening Time Seconds 35 ms 35 ms 35 ms 35 ms
Spring Release (SR) Close Circuit —
24
Operational Voltage Range 70 to 110 % 17 – 26 Vdc 34 – 53 Vdc 77 – 138 Vdc 154 – 275 Vdc
Power Consumption (Inrush) (Required for 200 ms) 250 Watts 250 Watts 450 Watts 450 Watts
Closing Time Seconds 40 ms 40 ms 40 ms 40 ms 25
Spring Charge Motor (MOT) —
Operational Voltage Range 85 to 110% Voltage 20 – 26 Vdc 41 – 53 Vdc 94 – 138 Vdc 187 – 225 Vdc
Amps (Running) Running 12.0 Amps 5.0 Amps 2.0 Amps 1.0 Amp 26
Amps (Inrush) % of Running 300% 500% 600% 600%
Power Consumption 300 Watts 250 Watts 250 Watts 250 Watts
Charging Time Seconds 5 Sec 5 Sec 5 Sec 5 Sec
Undervoltage Release (UVR)
27
Operational Voltage Range 85 to 110 % Voltage 20 – 26 Vdc 27 – 35 Vdc 41 – 53 Vdc 94 – 138 Vdc 187 – 275 Vdc
Drop-out Voltage Range 30 to 60% Voltage 7 – 14 Vdc 10 – 19 Vdc 14 – 29 Vdc 33 – 75 Vdc 66 – 150 Vdc
Power Consumption (Inrush) Required for 200 ms 250 Watts 275 Watts 275 Watts 450 Watts 450 Watts 28
Power Consumption (Continuous) Required for 400 ms 18 Watts 15 Watts 18 Watts 10 Watts 10 Watts
Opening Time Seconds 70 ms 70 ms 70 ms 70 ms 70 ms
Auxiliary Switches — 29
Minimum Load
Contact Rating Inductive Load 0.5 Amps 0.5 Amps 0.5 Amps 0.25 Amps

Table 27.1-8. Magnum DS & SB Breaker Control Device Application Guide — Vac
30
Breaker Control Device 120 Vac 240 Vac 415 Vac 480 Vac 600 Vac
Nominal Voltage 31
Shunt Trip (ST) Trip Circuit — — —
Operational Voltage Range 70 to 110 % 77 – 140 Vac 146 – 264 Vac
Power Consumption (Inrush) (Required for 35 ms) 450 VA 450 VA 32
Opening Time Seconds 35 ms 35 ms
Spring Release (SR) Close Circuit — — —
Operational Voltage Range 70 to 110 % 77 – 140 Vac 146 – 264 Vac 33
Power Consumption (Inrush) (Required for 200 ms) 450 VA 450 VA
Closing Time Seconds 40 ms 40 ms
Spring Charge Motor (MOT)
Operational Voltage Range 85 to 110 % Voltage 93 – 140 Vdc
— — — 34
177 – 264 Vdc
Amps (Running) Running 2.0 Amps 1.0 Amp
Amps (Inrush) % of Running 600% 600%
Power Consumption 250 VA 250 VA 35
Charging Time Seconds 5 Sec 5 Sec
Undervoltage Release (UVR)
Operational Voltage Range 85 to 110 % Voltage 94 – 140 Vac 177 – 264 Vac 323 – 457 Vac 408 – 528 Vac 510 – 660 Vac 36
Drop-out Voltage Range 30 to 60% Voltage 33 – 76 Vac 62 – 144 Vac 114 – 249 Vac 144 – 288 Vac 180 – 360 Vac
Power Consumption (Inrush) Required for 200 ms 450 VA 400 VA 480 VA 400 VA 400 VA
Power Consumption (Continuous)
Opening Time
Required for 400 ms
Seconds
10 VA
70 ms
10 VA
70 ms
10 VA
70 ms
10 VA
70 ms
10 VA
70 ms
37
Auxiliary Switches — — —
Minimum Load
Contact Rating Inductive Load 10 Amps 10 Amps
38

39

40

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-24
Power Circuit Breakers June 2006
Sheet 1116
Technical Data

22
Legend:
LS Limit Switch for Closing Spring
23 MOT
ST
Motor for Spring Charging
Shunt Trip
SR Spring Release Close Open G Open R

24 UVR
OTS
Undervoltage Release
Overcurrent Trip Switch

Description of Operation: B12 B15 B26 B10 B24 A7 A1 A2 A3


25 1 — Motor is energized through
Lever
LS contact. in Door
2 — Motor runs and charges closing Switch
26 spring. (Draw- a.
3 — When closing spring is fully charged, Control out Only)
LS contacts change state. Power OTS 1*
27 4 — Close contacts energize SR coil. SR L.S. b. ST a. UVR OTS 2*
5 — When breaker closes, “b” opens.
6 — LS contacts change state and motor MOT

28 recharges closing springs.

B13 B14 B27 B11 B25 A8 A4 A5 A6


29
* Contacts shown for breaker open (not fully
charged), not tripped.
30
Dotted line denotes Magnum Breaker.

31
MDSEOBKR

32 Figure 27.1-6. Typical Magnum Breaker Control Circuit Diagram

33 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 C1 C2 C3 C4 C5 C6

ONO OC ONOONO OC ONO UVR UVR ALL ALC AL ICL ATR ATR IP IN NPW N2 N1 SGF ZC ZI ZO ST ST SR SR M M CNC CC CNO CNC CC CNO

34 COM IN OUT

OTS OTS UVR ATR INCOM ATR INCOM NEG NEUTRALSOURCE ZONE SHUNT SPRING MOTOR CELL SWITCH CONTACTS
CLOSE POWER SENSOR GROUND INTER- TRIP RELEASE (SHOWN WITH BREAKER IN WITHDRAWN POSITION)
35 INPUT INPUT INPUT INPUT LOCKING

A16 A17 A18 A19 A20 A21 A22 A23 A24 A25 A26 A27 A28 A29 A30 B16 B17 B18 B19 B20 B21 B22 B23 B24 B25 B26 B27 B28 B29 B30 C7 C8 C9 C10 C11 C12

36 MLS ACN ACP NO NO NC NC NO NO NC NC NO NO NC NC NO NO NC NC NO NO NC NC NO NO NC NC LCO LC LNC CNC CC CNO CNC CC CNO

37 SPRING ACCESSARY
CHARGE BUS
BREAKER AUXILIARY CONTACTS
(SHOWN WITH BREAKER IN OPEN POSITION)
BREAKER AUXILIARY CONTACTS
(SHOWN WITH BREAKER IN OPEN POSITION)
LATCH CELL SWITCH CONTACTS
CHECK (SHOWN WITH BREAKER IN WITHDRAWN POSITION)
STATUS COMMUN- SWITCH
ICATIONS

38
Figure 27.1-7. Typical Magnum Secondary Terminal Block Connection Diagram

39

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-25
June 2006 Power Circuit Breakers
Sheet 1117
Application Data

Applications Maximum capabilities of transformers Generator Breakers


22
of various types, can be found in
Section 14.0 It will be noted that the In most applications where generators
Transformer Main maximum ratings will often require the are connected through breakers to the
Secondary Breakers substitution of larger frame main break- secondary bus, they are used as emer- 23
ers than those listed in the tables. Even gency standby sources only, and are
Transformer secondary breakers are not synchronized or paralleled with the
required or recommended for one or if a self-cooled transformer only is
more of the following purposes: considered, it should be remembered unit substation transformers. Under 24
that with ratings of 750 kVA and higher, these conditions, the interrupting rating
1. To provide a one-step means provision for the future addition of of the generator breaker will be based
of removing all load from the cooling fans is automatically included. solely on the generator kVA and sub- 25
transformer. It is recommended that the main breaker transient reactance. This reactance varies
have sufficient capacity for the future with the generator type and rpm, from
2. To provide transformer overload
fan-cooled rating, plus an allowance for a minimum of approximately 9% for a 26
protection in the absence of an 2-pole 3600 rpm turbine driven gener a-
overloads, if possible, particularly since
individual primary breaker, and/or tor to 15% or 20% or more for a medium
load growth cannot always be predicted.
when primary fuses are used. or slow speed engine type generator. 27
The same considerations should be Thus the feeder breakers selected for the
3. To provide the fastest clearing of unit substation will usually be adequate
given to the main bus capacities and
a short circuit in the secondary
main bus.
main current transformer ratios. for a standby generator of the same 28
kVA as the transformer.
4. To provide a local disconnecting Bus Sectionalizing (Tie) Breakers Most generators have a 2-hour 25%
means, in the absence of a local The minimum recommended continu- overload rating, and the generator
29
primary switch or breaker, for ous current rating of bus sectionalizing breaker must be adequate for this
maintenance purposes. or tie breakers, as used in double-ended overload current. Selective type long
secondary selective unit sub-stations, and short delay trip protection only is
30
5. For automatic or manual transfer
of loads to alternate sources, as in or for connecting two single-ended usually recommended for coordination
substations, is one-half that of the with the feeder breakers, with the long
double-ended secondary selective
associated main breakers. The inter- delay elements set at 125% to 150% of
31
unit substations.
rupting rating should be at least equal to the maximum generator current rating
6. For simplifying key interlocking that of the feeder breakers. It is common for generator protection.
with primary interrupter switches. practice to select the tie breaker of the 32
next frame size below that of the main In the case of two or more paralleled
7. To satisfy NEC service entrance breakers. However, many users and generators, anti-motoring reverse power
requirements when more than engineers prefer that the tie breaker be relays (device 32) are recommended 33
six feeder breakers are required. identical to and interchangeable with for protection of the prime movers,
the main breakers, so that under normal particularly piston type engines. For
Main secondary breakers must have
conditions it will be available as a spare larger generators requiring a Magnum 34
adequate interrupting ratings, but
main breaker. MDS-632 or larger, voltage-restraint
not necessarily adequate continuous
type overcurrent relays (device 51V)
current ratings. They should be able In general, the tie breaker, like the are recommended. 35
to carry continuously not only the main breaker, trip unit should have
anticipated maximum continuous its instantaneous tripping defeated.
output of the transformer but also 36
any temporary overloads.
For a fully selective system, instanta-
neous protection on main breakers 37
should be defeated, as they typically
cannot be coordinated with down-
stream devices. 38

39

40

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


27.1-26 Power Circuit Breakers & Insulated Case Circuit Breakers
Power Circuit Breakers June 2006
Sheet 1118
Application Data

Standards Altitude 3. Salt spray, excessive moisture,


22 Eaton’s Cutler-Hammer Magnum DS The breakers are applicable at their
dripping, etc.
circuit breakers meet or exceed all full voltage and current ratings up Drip shields in equipment rooms and
23 applicable requirements of ANSI Stan- to a maximum altitude of 6,600 feet space heaters in indoor switchgear,
dards C37.13, C37.17, C37.50 and CSA. (2,012 m) above sea level. When or outdoor weatherproof enclosures,
installed at higher altitudes, the ratings may be indicated, depending upon
24 System Voltage and Frequency are subject to the following correction the severity of the conditions.
Magnum DS breakers are designed for factors in accordance with ANSI
C37.20.1: 4. Excessively high or low ambient
operation on ac systems only, 60 Hz or temperatures.
25 50 Hz, 635 volts maximum. Table 27.1-9. Altitude Derating Factors
For ambient temperatures exceeding
Altitude Voltage Current
Continuous Current Ratings Correction Correction
40°C, and based on a standard temper-
26 Unlike transformers, generators and
Feet Meters ature rise of 65°C, the continuous
6,600 2,012 1.000 1.000 current ratings of breaker frame sizes,
motors, circuit breakers are maximum-
7,000 2,134 .989 .998 and also buses, current transformers,
27 rated devices and have no built-in
7,500 2,286 .976 .995 etc., will be subject to a derating factor
temporary overload current ratings.
8,000 2,438 .963 .993 calculated from the following formula:
Consequently, it is vital that each
8,500 2,591 .950 .990
28 application takes into consideration 9,000 2,743 .933 .987 105°C ° Total – Special Ambient, °C
the maximum anticipated current -------------------------------------------------------------------------------------------------
-
9,500 2,896 .917 .983 105°C ° Total – 40°C ° Standard Ambient
demand, initial and future, including 10,000 3,048 .900 .980
29 temporary overloads. 10,500 3,200 .883 .977 Circuit breakers are not adversely
11,000 3,353 .867 .973 affected by very low outdoor ambient
The continuous rating of any Magnum temperatures, particularly when ener-
11,500 3,505 .850 .970
DS breaker is limited to the sensor gized and carrying load currents. The
30 rating, or the frame size current rating,
12,000 3,658 .833 .967
standard space heaters in weatherproof
12,500 3,810 .817 .963
whichever is the lesser. For instance, 13,000 3,962 .800 .960 switchgear will raise the temperature
an MDS-616 1600 ampere frame
31 breaker with 800 ampere sensors has
slightly and prevent condensation.
a maximum continuous rating of 800
Unusual Environmental and Electrical components such as relays
amperes, but the same breaker with Operating Conditions and instruments, however, must be
32 1600 ampere sensors is limited to 1600 Special attention should be given to applied within the manufacturer’s
amperes maximum. applications subject to the following specified limits.
33 All current ratings are based on a conditions: 5. Exposure to seismic shock.
maximum ambient air temperature 1. Damaging or hazardous fumes,
of 40°C (104°F). Magnum DS assemblies and breakers
vapors, etc. have been certified for applications
34 through UBC Zone 4 and for the
Ambient Temperature 2. Excessive or abrasive dust.
California Building Code. Assembly
The temperature of the air surround- For such conditions, it is generally
35 ing the enclosure should be within recommended that the switchgear
modifications are required, so such
conditions must be specified.
the limits of: be installed in a clean, dry room, with
filtered and/or pressurized clean air. 6. Abnormally high frequency
36 -30°C (-22°F) to +40°C (104°F).
This method permits the use of standard of operation.
indoor switchgear and avoids the de- In line with above, a lesser number
37 rating effect of non-ventilated enclosures. of operations between servicing, and
more frequent replacement of parts,
may be indicated.
38

39

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.1-27
June 2006 Power Circuit Breakers
Sheet 1119
Application Data

Feeder Breakers — General For motor starting duty, with closing During fault conditions, each trip
Circuit breakers for feeder circuit
starting currents up to 600% and opening unit which senses the fault sends a 22
running currents up to 100% of the restraining signal to all upstream trip
protection may be manually or breaker frame size, at 80% power units. This restraining signal results in
electrically operated, with long and factor or higher, the endurance or causing the upstream trip to continue 23
short delay or long delay and instanta- total operations (not requiring parts timing as it is set. In the absence of a
neous type trip devices, and trip replacement) will be as follows: restraining signal, the trip unit trips the
settings, as required for the specific associated breaker with no intentional 24
circuit and load requirements. 800 A Frame: 1400 operations time delay, minimizing damage to the
1600 A Frame: 400 operations fault point. This restraining signal is
General purpose feeder breakers, such as
for lighting circuits, are usually equipped The frequency of operation should not a very low level. To minimize the 25
with long delay and instantaneous trip exceed 20 starts in 10 minutes or 30 in potential for induced noise, and
devices, with the long delay pickup set one hour. provide a low impedance interface
for the maximum load demand in the between trip units, twisted pair con- 26
circuit. Where arcing fault protection is Group Motor Feeder Breakers ductors are utilized for interconnection.
required, the instantaneous trip setting
should be as low as practicable consis-
Typical loads for such circuits are motor Ground fault and short delay pickup 27
control centers. The feeder breakers on Digitrip Trip Units have zone
tent with inrush requirements. selective interlocking.
may be either manually or electrically
Motor Starting Feeder Breakers operated as preferred, and are usually
Zone selective interlocking may be
28
equipped with long and short delay trip
These breakers are usually electrically protection only for coordination with applied as a type of bus differential
protection. It must be recognized,
operated, with long delay and instan- the individual motor circuit devices.
however, that one must accept the
29
taneous tripping characteristics for The minimum long delay pickup setting
motor running, locked rotor and fault should be 115% of the running current minimum pickup of the trip unit for
sensitivity.
protection. The breaker sensor rating of the largest motor in the group, plus 30
should be chosen so that the long delay the sum of the running circuits of all It must also be recognized that not
pickup can be set at 125% of motor full other motors. all systems may be equipped with
load current for motors with a 1.15 zone selective interlocking. Systems 31
service factor, or at 115% for all other Zone Selective Interlocking containing multiple sources, or where
motors. Contactors are recommended the direction of power flow varies,
By definition, a selectively coordinated
for this application when there are a
system is one where by adjusting trip require special considerations, or may 32
number of daily operations involved. not be suitable for this feature. Digitrip
unit pickup and time delay settings, the
When system short circuits are less circuit breaker closest to the fault trips zone interlocking has been tested with
than 40 times the motor full load first. The upstream breaker serves two up to three levels with up to 20 trip 33
current, the motor breaker tripping functions: (1) back-up protection to the units per level.
characteristic should include a short downstream breaker and (2) protection
delay characteristic for greater fault of the conductors between the upstream
34
protection. and downstream breakers. These
elements are provided for on Digitrip
Repetitive Duty trip units.
35
Repetitive breaker opening and clos- For faults which occur on the conduc-
ing, such as in frequent motor starting tors between the upstream and down- 36
and stopping, are covered by ANSI stream breakers it is ideally desirable
standards C37.13 and C37.16. These for the upstream breaker to trip with
standards list the number of opera- no time delay. This is the feature pro- 37
tions between servicing (adjusting, vided by zone selective interlocking.
cleaning, lubrication, tightening, etc.) Digitrip trip units include this option.
and the total numbers of operations 38
under various conditions without Zone selective interlocking is a com-
requiring replacement of parts, for munication signal between trip units
the various breaker frame sizes. applied on upstream and downstream 39
breakers. Each trip unit must be applied
as if zone selective interlocking were
not employed, and set for selective 40
coordination.

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


27.1-28 Power Circuit Breakers & Insulated Case Circuit Breakers
Power Circuit Breakers June 2006
Sheet 1120
Application Data

Sensor Rating, Resistance Welding


22 Amperes The application of Eaton’s Cutler-
15000 Hammer Magnum DS circuit breakers
40 50
00 to resistance welding circuits is shown
23 00
in Figure 27.1-8 of the Sensor Selection
32
10000 00
Guide. Sensor ratings only are given;
24 25 the breaker frame must be selected as
00
required for interrupting ratings.
20
00
The Magnum DS microprocessor-based
25 5000 16
00 true rms sensing devices have a ther-
mal memory and are well suited for this
During-Weld Amperes (rms)

12 service. The thermal memory functions


00
26 10 prevent exceeding the breaker and
00 cable maximum permissible thermal
80 energy level. The circuit also replicates
27 0
time dissipation of thermal energy.
2000 60
0 The size of the thermal memory is
28 30 T (In / In)2 unit Amperes2 seconds. It
40
0 fills at a rate of (iw / In)2 unit Amperes2
seconds/second, trips at 30T seconds,
29 30
0 and empties at the rate of (In / In)2 unit
Amperes2 seconds/second, where:
25
0
30 T = Long Time Delay Setting in
20
0 seconds (range is 2 – 24 seconds)
500 iw = rms value of the welding
31 current in amperes
In = Rating plug current value
32 200 in amperes
The memory is filled during the weld
33 and empties during the non-welding
period of the duty cycle.
These welding applications are based
34 on long delay and instantaneous trip
100 devices with the following settings.
The long time delay setting is based
35 3 4 5 6 7 8 9 10 20
Percent Duty Cycle
30 40 50 60
on the weld amperes and duty cycle.
Instantaneous trip setting is two times
Figure 27.1-8. Magnum DS Breaker Sensor Selection Guide for Resistance Welding Applications the average weld amperes (weld
36 amperes times percent duty cycle)
or higher.
37 Note: Making Current Release (MCR)
may prevent closing the breaker during
a welding cycle.
38

39

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.2-1
June 2006 Power Circuit Breakers — DSII
Sheet 1121
General Description

Type DSII Low Voltage Sizes and Arrangements the circuit breaker current sensors
22
and initiating trip signals to the circuit
Power Circuit Breakers Types DSLII-308 (800 ampere), breaker trip unit when preset current
DSLII-516 (1600 ampere), and DSLII- levels and time delay settings are
620 (2000 ampere) frame breakers exceeded. By sampling the current 23
include the limiters integrally mounted waveform at various points on the
on the drawout breaker elements in wave and calculating true rms current,
series with the upper terminals. the Digitrip is able to reduce nuisance 24
Current limiters used in Types tripping events due to non-sinusoidal
DSLII-632 and DSLII-840 combinations wave shapes.
are mounted on separate drawout 25
Electronic trip units are applied to
trucks in an additional equal size distribution systems when high stan-
compartment. dards of protection and coordination 26
are called for. In addition, electronic
Electronic Trip Units trip units can provide further enhanced
Eaton offers the most comprehensive features such as alarming, diagnostics, 27
range of electronic trip units in the system monitoring and communications.
industry for power circuit breakers.
Cutler-Hammer rms sensing trip
DSII with 910 Trip Unit Digitrip electronic trip units are ac units for power breakers fall into two
28
devices that employ microprocessor- main categories:
Type DSII Low Voltage Power Circuit based technology that provides a true
Breakers provide: rms current sensing means for proper ■ Front adjustable trip units: 29
correlation with thermal characteristics Digitrip RMS 510, 610, 810, 910.
■ 100% rated, fully selective protection. ■ Programmable trip units:
of conductors and equipment. The pri-
■ Integral microprocessor-based mary function of the Digitrip electronic Digitrip OPTIM 750, 1050. 30
breaker tripping systems. trip unit is to provide circuit protection.
For additional information on trip units
■ Two-step stored-energy breaker This is achieved by analyzing the sec-
closing. ondary current signals received from
see Section 28.1. 31
And many other features for coordi-
nated, safe, convenient, trouble-free 32
Legend
and economical control and protection LS — Limit Switch for Closing Spring CS (or PB) CS (or PB)
of low voltage distribution systems. MOT — Motor for Spring Charging Close Ind. G Trip
SH TR — Shunt Trip Lts.
R 33
Maximum Ratings SR — Spring Release
Y — Anti-Pump Relay
■ 600 Vac.
Description of Operation 34
■ 5000 amperes continuous. 1 — Motor is energized through LS contact. SR MOT SHTR
■ 200,000 amperes short circuit capacity. 2 — Motor runs and charges Closing Spring.
3 — When Closing Spring fully charged, LS
contacts reverse.
35
Application 4 — CIosing CS-C contact energizes SR Coil Y
Eaton’s Cutler-Hammer Type DSLII through Y, LS & “b” contacts.
breakers are coordinated combina- 5 — When Breaker closes, “b” opens and Y Y LS LS 36
Coil is energized in series with SR Coil.
tions of Type DSII breakers and series 6 — Y contact opens to open SR Coil circuit b b a
connected current limiters. They are & prevent pumping should breaker 37
intended for applications requiring open while CS-C is held closed. Y Coil
the overload protection and switching has very low drop-out voltage.
7 — LS contacts reverse and motor
functions of air circuit breakers on
systems whose available fault currents
recharges closing springs. 38
exceed the interrupting rating of the
Figure 27.2-1. Standard Control Diagram for Type DSII Electrically Operated Breaker,
breakers alone, and/or the withstand
in DSII Switchgear, for ac or dc Control Source 39
ratings of “downstream” circuit
components.
40

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


27.2-2 Power Circuit Breakers & Insulated Case Circuit Breakers
Power Circuit Breakers — DSII June 2006
Sheet 1122
Technical Data

22 DSII Ratings Maximum voltages at which the inter-


rupting ratings in Table 27.2-1 apply are:
Table 27.2-1. Interrupting Ratings of Type DSII Breakers
Table 27.2-6. Maximum Voltage Rating
Breaker Frame Ratings, rms Symmetrical Amperes
23 Type Size, Interrupting Rating Short Time Rating 
System Maximum
Amperes Voltage Voltage
208-240 V 480 V 600 V 208-240 V 480 V 600 V
208 or 240 254
24 DSII-308 800 42,000 30,000 30,000 30,000 30,000 30,000 480 508
DSII-508 800 65,000 50,000 42,000 50,000 50,000 42,000 600 635
DSII-608 800 65,000 65,000 50,000 65,000 65,000 50,000
25 DSII-516 1600 65,000 50,000 42,000 50,000 50,000 42,000 These interrupting ratings are based
DSII-616 1600 65,000 65,000 50,000 65,000 65,000 50,000 on the standard duty cycle consisting
DSII-620 2000 65,000 65,000 50,000 65,000 65,000 50,000 of an opening operation, a 15-second
26 DSII-632 3200 85,000 65,000 65,000 65,000 65,000 65,000 interval and a close-open operation,
DSII-840 4000 130,000 85,000 85,000 85,000 85,000 85,000 in succession, with delayed tripping
DSII-850 5000 130,000 85,000 85,000 85,000 85,000 85,000 in case of short-delay devices.
27  Short circuit ratings of non-automatic breakers except the DSII-840 and DSII-850 which are 65,000.
The standard duty cycle for short-time
Table 27.2-2. Digitrip RMS Adjustable Trip Settings ratings consists of maintaining the rated
28 Time/Current Pickup Pickup Point Time Band,
current for two periods of 1/2 second
Characteristic Setting (see note) Seconds each, with a 15-second interval of zero
current between the two periods.
29 Long Delay 0.5, 0.6, 0.7, 0.8,
0.85, 0.9, 0.95, 1.0
In Times
Long Delay Setting
2, 4, 7, 10, 12, 15, 20, 24
(at 6 times pickup value) Table 27.2-7. Available Sensor Ratings for
Instantaneous 2, 2.5, 3, 4, 5, 6 In Times — Digitrip RMS
M1=8, M2=12 Instantaneous Setting
30 Short Delay 2, 2.5, 3, 4, 5, 6 Ir Times 0.1, 0.2, 0.3, 0.4, 0.5
Breaker
Type
Frame
Size,
Sensor
Ratings,
S1=8, S2=10 Short Delay Setting (Flat Response) Amperes Amperes
0.1 , 0.3 , 6.5 
31 Ground Fault A (.25), B (.3), C (.35), In Times 0.1, 0.2, 0.3, 0.4, 0.5
DSII-308, DSLII-308, 800 200, 300, 400,
DSII-508 or 600, 800
D (.4), E (.5), F (.6), Ground Fault Setting (Flat Response) DSII-608
H (.75), K (1.0) 0.1 , 0.3 , 0.5
32 (1200A Maximum) DSII-516, DSLII-516
or DSII-616
1600 200, 300, 400,
600, 800, 1200,
 I2t Response.
1600
Note: In = Rating Plug Value
33 Ir = Long Delay Pickup Setting x In.
DSII-620 2000 200, 300, 400,
600, 800, 1200,
1600, 2000
Table 27.2-3. Interrupting Ratings of Type DSLII Breakers
34 Type DSLII-308 DSLII-516 DSLII-620 DSLII-632 DSLII-840
DSLII-620
DSII-632, DSLII-632
2000
3200
2000
2400, 3200
DSII-840, DSLII-840 4000 3200, 4000
Frame Size, Amperes 800 1600 2000 3200 4000 DSII-850 5000 5000
35 Maximum Interrupting Rating, 200,000 200,000 200,000 200,000 200,000
rms Symmetrical Amperes, Table 27.2-8. Available Digitrip RMS Rating
System Voltage 600 or Below Plugs Marked 50/60 Hertz
36 Sensor Ratings, Plug Rating
Table 27.2-4. Control Voltages and Currents Amperes in Amperes (In)
Control 48 dc 125 dc 250 dc 120 ac 240 ac
37 Voltage 200
300
100, 200
200, 250, 300
Close current (SR), ampere 5.0 2.0 1.0 3.0 2.0 400 200, 250, 300, 400
Shunt trip current, ampere 5.0 2.0 1.0 2.0 1.0
38 Spring charge motor ampere 7.5 3.0 1.5 3.0 1.5
600
800
300, 400, 600
400, 600, 800
Control voltage range: 1200 600, 800, 1000, 1200
Close — 38 – 56 100 – 140 200 – 280 104 – 127 208 – 254 1600 800, 1000, 1200, 1600
39 Trip — 28 – 56 70 – 140 140 – 280 60 – 127 208 – 254 2000 1000, 1200, 1600, 2000 
2400 1600, 2000, 2400
Note: Motor currents are running currents; inrush is approximately 400%. Motor running time 3200 1600, 2000, 2400, 3000, 3200
40 to charge spring approximately 5 seconds. 4000 2000, 2400, 3200, 4000
5000 3200, 4000, 5000
Table 27.2-5. Estimated Heat Loss Per Breaker  2000 ampere is the only plug available for
41 Breaker Type Watts DSLII-620.
Note: The rating plug is for 50 and 60 Hz
DSII-308 (DSLII-308) 400 (600) applications. Rating plugs are not inter-
42 DSII-516 (DSLII-516)
DSII-620 (DSLII-620)
1000 (1500)
1500 (2250)
changeable with 60 Hz or 50 Hz only
rating plugs.
DSII-632 2400
DSII-840 3000
43 DSII-850 4700
DSII-FT32 3600
DSII-FT40 4500

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.2-3
June 2006 Power Circuit Breakers — DSII
Sheet 1123
Technical Data

The following curves illustrate the ratings, Limiter Selection Case A would tend to use the smallest
melting time-current characteristics
The selection of a suitable limiter
available limiter; Case B the largest. 22
and current limiting, or let-through When downstream protection is
characteristics, of limiters for Eaton’s rating for a given application is required, the selection is usually
Cutler-Hammer Type DSLII breakers. generally governed by a choice of a compromise, since certain small 23
the following types of protection: limiters cannot be coordinated with
The let-through current for a given the breaker to avoid nuisance blowing
A. Maximum protection of “down-
limiter application is readily determined
stream” components. Type DSLII on overloads or small and moderate 24
by extending a vertical line from the short circuits.
applicable maximum available sym- breakers are often used for this
purpose even when the maxi-
metrical fault amperes at the bottom
mum available fault currents are
Minimum, recommended, and maxi- 25
margin to the characteristic line for mum limiter sizes for Eaton’s Cutler-
the particular limiter, and from this within the interrupting rating of Hammer Types DSLII-308, DSLII-516,
the corresponding Type DSII
intersection extending a horizontal line
unfused breakers.
and DSLII-620 breakers are given 26
to the left margin and reading the peak in table.
current. The withstand rating of any B. Protection of the circuit breaker only.
circuit elements protected by the
Table 27.2-10. DSLII Limiter Selection
27
limiters should be at least equal to
this peak current. Breaker Sensor Rating, Limiter Rating, Amperes

It will be noted that the let-through


Type Amperes Minimum  Recommended  Maximum  28
current increases with the limiter size DSLII-308 200 250 1200 2000
or ampere rating; in other words, the
maximum current limiting effect is
DSLII-308
DSLII-308
300
400
400
600
1200
1200
2000
2000
29
obtained with the smallest size. This DSLII-308 600 800 1200 2000
effect is to be expected, since the DSLII-308 800 1200 1600 2000
resistance decreases as the rating DSLII-516 600 800 2000 3000 30
increases. If the vertical line from the DSLII-516 800 1000 2000 3000
bottom margin as described in the DSLII-516 1200 2000 2500 3000
previous paragraph does not intersect DSLII-516 1600 — 3000 — 31
DSLII-620 2000 — 3000 —
the limiter characteristic line, it is  For use only when protection of downstream equipment is required. Not completely coordinated
indicated that the available system 32
with breaker to avoid nuisance blowing.
fault current is below the “threshold”  Lowest rating which can be coordinated with breaker to minimize nuisance blowing.
current of that limiter, and it will offer  Highest available ratings, for protection of breaker only.
no current limiting effect. 33
The current limiting principle is Table 27.2-11. Sensor, Plug and Limiter Selection
illustrated below: DSII Sensor Rating, Plug Rating, Limiter Rating, Amperes
Breakers Amperes Amperes (Applicable only to DSLII Breakers) 34
la = The Available Peak Fault Current
308, 508, 200 100, 200 250, 300, 400, 600, 800, 1200, 1600, 2000
tm = The Melting Time 608 300 200, 250, 300 400, 600, 800, 1200, 1600, 2000
400 200, 250, 300, 400 600, 800, 1200, 1600, 2000 35
Ip = The Peak Let-Through Current 600 300, 400, 600 800, 1200, 1600, 2000
800 400, 600, 800 1200, 1600, 2000
ta = The Arcing Time 516, 616 200 100, 200 800, 1000, 1200, 1600, 2000, 2500, 3000 36
300 200, 250, 300 800, 1000, 1200, 1600, 2000, 2500, 3000
tc = The Total Interrupting (Clearing) 400 200, 250, 300, 400 800, 1000, 1200, 1600, 2000, 2500, 3000
Time 600
800
300, 400, 600
400, 600, 800
800, 1000, 1200, 1600, 2000, 2500, 3000
1000, 1200, 1600, 2000, 2500, 3000
37
1200 600, 800, 1000, 1200 2000, 2500, 3000
1600 800, 1000, 1200, 1600 3000
620 200 100, 200 Not Applicable
38
300 200, 250, 300 Not Applicable
Ia 400 200, 250, 300, 400 Not Applicable
Ip 600 300, 400, 600 Not Applicable 39
800 400, 600, 800 Not Applicable
1200 600, 800, 1000, 1200 Not Applicable
tm ta 1600 800, 1000, 1200, 1600 Not Applicable
tc 2000 1000, 1200, 1600, 2000  3000  40
632 2400 1600, 2000, 2400 2500, 3000, 4000
3200 1600, 2000, 2400, 3000, 3200 2500, 3000, 4000
Figure 27.2-2. Current Limiting
840 3200 1600, 2000, 2400, 3200 2500, 3000, 4000, 5000
41
4000 2000, 2400, 3200, 4000 2500, 3000, 4000, 5000
Table 27.2-9. DSLII-632 and DSLII-840
Available Limiters

850 5000 3200, 4000, 5000 Not Applicable
42
2000 ampere is the only plug available for DSLII-620.
Breaker Available Limiters, 
Type Amperes 3000 ampere is the only limiter available for DSLII-620.

DSLII-632 2500, 3000, 4000


43
DSLII-840 2500, 3000, 4000, 5000

CA08104001E For more information visit: www.EatonElectrical.com


27.2-4 Power Circuit Breakers & Insulated Case Circuit Breakers
Power Circuit Breakers — DSII June 2006
Sheet 1124
Technical Data

22
SCALE X 100 = CURRENT IN AMPERES

10,000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
400,000

70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
800 800
700 700 300,000
600 600
500 500

23
400 400
200,000
300 300

200 Limiter Ampere Rating 200


AMPERE
RATING
250
300
400
600

800
1200
1600
2000 2000
100

24
100 100,000
90 90 1600
80 80 90,000
70 70 1200
60 60
80,000
800
50 50 70,000

MAXIMUM PEAK LET-THROUGH CURRENT, AMPS


40 40
60,000
30 30 600
50,000

ce
25

du
TIME IN SECONDS
TIME IN SECONDS

o
20 20 40,000

Pr
an
400

tc
ui
30,000

irc
10 10 300

C
9 9

nt
8 8 250

re
7 7

ur
26 6 6

C
20,000

ak
5 5

Pe
4 4

um
im
3 3

ax
M
2 2

27 1
.9
1
.9
10,000
9000
8000
.8 .8 7000
.7 .7
.6 .6 6000
.5 .5
5000

28
.4 .4

.3 .3 4000

.2 .2
3000

29
.1 .1
.09 .09
.08 .08 2000
.07 .07
.06 .06
.05 .05
.04 .04

.03 .03

30 1000

1000

2000

3000

4000

5000

6000
7000
8000
9000
10,000

20,000

30,000

40,000

50,000

60,000
70,000
80,000
90,000
100,000

200,000
.02 .02

AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES


.01 .01
10,000
1000

2000

3000

4000
5000
6000
7000
8000
9000
300
100

200

400
500
600
700
800
900
70
80
90

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60

31 SCALE X 100 = CURRENT IN AMPERES


Ref. Curve No. 639771
Supersedes AD 36-783
dated April 1990
Ref. Curve No. 639772
Supersedes AD 36-783
dated April 1990
Type DSL-206 Limiters — For DSL-206 and DSLII-308 Breakers Type DSL-206 Limiters — For DSL-206 and DSLII-308 Breakers
January 1997 January 1997

32 Figure 27.2-3. DSLII-308 Average Melting Time-Current Characteristics Figure 27.2-5. DSLII-308 Let-Through Characteristics

33
SCALE X 100 = CURRENT IN AMPERES
10,000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
70
80
90

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
800 800 400,000
700 700
600 600
500 500
300,000

34
400 400

300 300
AMPERE
200,000 RATING
200 Limiter Ampere Rating 200
3000
800
1000
1200
1600
2000
2500
3000

2500

35 100
90
80
70
60
100
90
80
70
60
100,000
90,000
2000
1600
1200
50 50 80,000 1000
40 40 70,000
800
MAXIMUM PEAK LET-THROUGH CURRENT, AMPS

30 30

36
60,000
50,000
e
TIME IN SECONDS

20 20
TIME IN SECONDS

uc
od

40,000
Pr
an
tc

10 10
ui

9 9 30,000
irc

8 8

37
C

7 7
nt

6 6
re
ur

5 5
C

20,000
ak

4 4
Pe

3 3
um
im
ax

38
2 2
M

10,000
9000
1 1
.9 .9 8000
.8 .8
.7 .7 7000
.6 .6

39
6000
.5 .5

.4 .4 5000
.3 .3
4000

.2 .2

3000

40 .1
.09
.08
.1
.09
.08 2000
.07 .07
.06 .06
.05 .05

41
.04 .04

.03 .03
1000
1000

2000

3000

4000

5000

6000
7000
8000
9000
10,000

20,000

30,000

40,000

50,000

60,000
70,000
80,000
90,000
100,000

200,000

.02 .02

AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES

42 .01 .01
300
70
80
90
100

1000

2000

3000

4000
5000
6000
7000
8000
9000
200

400
500
600
700
800
900

10,000

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60

SCALE X 100 = CURRENT IN AMPERES

Type DSL-416 Limiters — For DSL-416, DSLII-516, DSL-420  Ref. Curve No. 639431 Type DSL-416 Limiters — For DSL-416, DSLII-516, DSL-420  Ref. Curve No. 639432
Supersedes AD 36-783
and DSLII-620  Breakers
Supersedes AD 36-783
dated April 1990 and DSLII-620  Breakers
43 January 1997
dated April 1990
January 1997

Figure 27.2-4. DSLII-516 and DSLII-620 Average Melting Figure 27.2-6. DSLII-516 and DSLII-620 Let-Through Characteristics
Time-Current Characteristics  DSL-420 and DSLII-620 — use only 3000 limiter.
 DSL-420 and DSLII-620 — use only 3000 limiter.

For more information visit: www.EatonElectrical.com CA08104001E


Power Circuit Breakers & Insulated Case Circuit Breakers
27.2-5
June 2006 Power Circuit Breakers — DSII
Sheet 1125
Technical Data

SCALE X 100 = CURRENT IN AMPERES

22

10,000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
70
80
90
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
100 100 400,000
90
80
Ampere Rating Limiter 90
80
AMPERE
RATING

2500

3000

4000
5000
70 70
60 60 300,000
50 50 5000
40

30
40

30 200,000
4000
23
3000
20 20
2500

10
90
80
10
90
80 100,000
24
70 70 90,000
60 60
50 50
80,000
40 40 70,000

25

MAXIMUM PEAK LET-THROUGH CURRENT, AMPS


30 30 60,000
50,000

e
TIME IN SECONDS
TIME IN SECONDS

uc
20 20

od
40,000

Pr
an
tc
10 10
26

ui
9 9 30,000

rc
8 8

Ci
7 7

t
en
6 6

rr
5 5

Cu
20,000

ak
4 4

Pe
3 3

27

um
im
ax
2 2

M
10,000
1 1 9000
.9 .9
.8
.7
.6
.5
.8
.7
.6
.5
8000
7000
28
6000
.4 .4

.3 .3
5000

.2 .2
4000
29
3000
.1 .1
.09 .09
.08 .08
.07
.06
.05
.04
.07
.06
.05
.04
2000
30
.03 .03

31
.02 .02
1000
1000

2000

3000

4000

5000

6000
7000
8000
9000
10,000

20,000

30,000

40,000

50,000

60,000
70,000
80,000
90,000
100,000

200,000
.01 .01
70
90

1000

2000

3000

4000
5000
6000
7000
8000
9000
10,000
80

300
100

200

400
500
600
700
800
900

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
AVAILABLE CURRENT, RMS SYMMETRICAL AMPERES
SCALE X 100 = CURRENT IN AMPERES

Type DSL-632 Limiters — For DSL-632, and DSLII-632 Breakers Ref. Curve No. 705503
Supersedes AD 36-783
Type DSL-632 Limiters — For DSL-632, and DSLII-632 Breakers
Type DSL-840 Limiters — For DSL-840, and DSLII-840 Breakers
Ref. Curve No.
705504Supercedes AD
36-783
32
Type DSL-840 Limiters — For DSL-840, and DSLII-840 Breakers dated April 1990 dated April 1990
January 1997 January 1997

Figure 27.2-7. DSLII-632 and DSLII-840 Average Melting Figure 27.2-8. DSLII-632 and DSLII-840 Let-Through Characteristics 33
Time-Current Characteristics

CSA is a registered trademark of the Canadian Standards Association. Cutler-Hammer 34


is a federally registered trademark of Eaton Corporation. NEMA is the registered
trademark and service mark of the National Electrical Manufacturers Association.
National Electrical Safety Code is a registered trademark and service mark of the
Institute of Electrical and Electronics Engineers, Inc. UL is a federally registered 35
trademark of Underwriters Laboratories Inc. Uniform Building Code (UBC) is
a trademark of the International Conference of Building Officials (ICBO).

36

37

38

39

40

41

42

43

CA08104001E For more information visit: www.EatonElectrical.com


Power Circuit Breakers & Insulated Case Circuit Breakers
27.2-6
June 2006
Sheet 1126

This page intentionally left blank.


22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

For more information visit: www.EatonElectrical.com CA08104001E

You might also like