Product Bulletin
62.1:846 846 Transducer
September 2017 D102127X012
Specifications
Input Signal Multirange Performance: 9.7 m3/hr (360 scfh) at
4-20 mA DC, field adjustable split ranging. 2.5 bar (35 psi) supply pressure
2
Product Bulletin
846 Transducer 62.1:846
D102127X012 September 2017
Specifications (Continued)
Adjustments Other Classifications/Certifications
Zero and Span: Screwdriver adjustments located in CUTR— Customs Union Technical Regulations
terminal compartment. (Russian, Kazakhstan, and Belarus)
INMETRO—National Institute of Metrology, Quality,
Remote Pressure Reading (optional) and Technology (Brazil)
ON or OFF; jumper selectable KGS—Korea Gas Safety Corporation (South Korea)
Frequency Range: 0-10,000 Hz NEPSI— National Supervision and Inspection Centre
Amplitude: 0.4-1.0 Vp-p for Explosion Protection and Safety of
Instrumentation (China)
Required Operating Voltage Contact your Emerson sales office or Local Business
Min. 6.0 V (at 4 mA) Partner for classification/certification specific
Max. 7.2 V (at 20 mA) information
with Remote Pressure Reading ON
Min. 6.4 V (at 4 mA) Construction Materials
Max. 8.2 V (at 20 mA)
Housing
J ASTM: A03600 material composition alloy or
Electrical Classification
J CF8M
Hazardous Area O-Rings
see Bulletin 9.2:001 (D103222X012) Nitrile, except silicone for sensor O-rings.
CSA C/US—Intrinsically Safe, Explosion-proof,
Non-Incendive Mounting
FM—Intrinsically Safe, Explosion-proof, J Actuator, J pipestand, or J surface
Non-Incendive
ATEX—Intrinsically Safe, Flameproof, Type n
Weight
IECEx—Intrinsically Safe, Flameproof
Aluminum: 2.9 kg (6.5 lb) excluding options
Electrical Housing Stainless Steel: 6.7 kg (14.8 lb) excluding options
Tropicalization (Fungus test per MIL-STD-810)
CSA C/US—Type 4X Options
FM—Type 4X J Fisher 67CFR filter regulator, J supply and output
ATEX—IP66(3) gauges, J remote pressure reading, or J stainless
IECEx—IP66(3) steel mounting bracket
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology
1. Normal m3/hr: normal cubic meters per hour (m3/hr, 0_C and 1.01325 bar, absolute). Scfm: standard cubic feet per minute (ft3/min, 60_F and 14.7 psig).
2. Performance values are obtained using a transducer with a 4 to 20 mA dc input signal, a 3 to 15 psig output, and 20 psig supply pressure.
3. ATEX and IECEx Flameproof — IP66 per CSA Letter of Attestation.
3
Product Bulletin
62.1:846 846 Transducer
September 2017 D102127X012
4
Product Bulletin
846 Transducer 62.1:846
D102127X012 September 2017
TERMINAL COVER
TRANSDUCER HOUSING
MASTER MODULE
A6326
MODULE COVER
STROKE PORT
846 TRANSDUCER
4 TO 20 mA 6 VDC
INPUT
50
OHMS
ELECTRONIC CIRCUIT
MAGNETIC ACTUATOR
POWER
SOLID-STATE SUPPLY
PILOT STAGE PRESSURE
SENSOR
BOOSTER STAGE
Note:
The 846 is not a constant resistor in series with an inductor. It is better
modeled in the loop as a 50 ohm resistor in series with a 6 volt DC voltage drop
with negligible inductance.
3 TO 15 PSI
OUTPUT, TYPICAL A6325
A6324
5
Product Bulletin
62.1:846 846 Transducer
September 2017 D102127X012
6
Product Bulletin
846 Transducer 62.1:846
D102127X012 September 2017
Figure 5. Dimensions
67 COVER REMOVAL
(2.62) CLEARANCE
68 1/4-18 NPT
(2.69) SUPPLY CONN
59
(2.31)
78
(3.08)
156
(6.15)
29
(1.13)
119
(4.68)
168
(6.60)
137 MODULE COVER
(5.38) REMOVAL CLEARANCE 5/16-18
3 PLACES
1/4-18 NPT
OUTLET CONN
PLUGGED WHEN
GAUGE NOT
FURNISHED
7
Product Bulletin
62.1:846 846 Transducer
September 2017 D102127X012
67
COVER REMOVAL
(2.62)
CLEARANCE
13
(0.50)
191
6
(7.51)
(0.25)
78 FOR PROPER MOISTURE 1
(3.08) DRAINAGE THIS END
MUST BE UP
CENTERLINE OF ACTUATOR
MODULE 137
COVER (5.38)
REMOVAL
CLEARANCE
YOKE MOUNTED
mm
(INCH)
Note:
1 The mounting positions shown allow any moisture buildup in the terminal compartment to drain to the signal wire conduit
entrance. Do not mount the transducer with the terminal compartment cover on the bottom; moisture may accumulate in the
terminal compartment or pilot stage, preventing proper transducer operation. The vertical mount is most effective for moisture
drainage in wet applications.
14B7361-D
8
Product Bulletin
846 Transducer 62.1:846
D102127X012 September 2017
67
(2.62) COVER REMOVAL
CLEARANCE
222
(8.76)
89 FOR PROPER MOISTURE
(3.50) DRAINAGE THIS END
19 MUST BE UP 1
(0.76)
13
(0.50) 89
(3.50)
SURFACE/WALL MOUNTED
mm
(INCH)
Note:
1 The mounting positions shown allow any moisture buildup in the terminal compartment to drain to the signal wire conduit
entrance. Do not mount the transducer with the terminal compartment cover on the bottom; moisture may accumulate in the
terminal compartment or pilot stage, preventing proper transducer operation. The vertical mount is most effective for moisture
drainage in wet applications.
14B7332-D
9
Product Bulletin
62.1:846 846 Transducer
September 2017 D102127X012
Figure 8. Dimensions with Optional Fisher 67CFR Filter-Regulator (Pipe Stand Mounted)
210
(8.27)
1/2-14 NPT
148 CONDUIT CONN
(5.82)
67 COVER REMOVAL
(2.62) CLEARANCE
13
(0.50)
156
(6.15)
54
(2.51)
67CFR
1/4-18 NPT
SUPPLY CONN
262
(10.31)
MODULE
137 COVER
(5.38) REMOVAL
CLEARANCE
mm
PIPE STAND MOUNTED (INCH)
Notes:
1 The mounting positions shown allow any moisture buildup in the terminal compartment to drain to the signal wire conduit
entrance. Do not mount the transducer with the terminal compartment cover on the bottom; moisture may accumulate in the
terminal compartment or pilot stage, preventing proper transducer operation. The vertical mount is most effective for moisture
drainage in wet applications.
2 If mounted on horizontal pipe, the I/P must be on top of the pipe for proper moisture drainage.
14B7363-D
10
Product Bulletin
846 Transducer 62.1:846
D102127X012 September 2017
11
Product Bulletin
62.1:846 846 Transducer
September 2017 D102127X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions,
Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
E
121995, 2017 Fisher Controls International LLC. All rights reserved.