Professional Documents
Culture Documents
Neutral Ground Resistor Calculation For Transformer PDF
Neutral Ground Resistor Calculation For Transformer PDF
During Earth fault voltage between Neutral & Earth = 6.6/√3 = 3.81 KV
(1) Solid grounding – The neutral point of the system is grounded without
any resistance. If the ground fault occurs, high ground current passes
through the fault. Its use is very common in low voltage system, where line
to neutral voltage is used for single phase loads.
(2) Low Resistance grounding (LRG) - This is used for limiting the ground
fault current to minimize the impact of the fault current to the system. In
this case, the system trips for the ground fault. In this system, the use of
line to neutral (single phase) is prohibited. The ground fault current is
limited to in the rage from 25A to 600A.
(3) High Resistance Grounding (HRG) - It is used where service continuity is
vital, such as process plant motors. With HRG, the neutral is grounded
through a high resistance so that very small current flows to the ground if
ground fault occurs. In the case of ground fault of one phase, the faulty
phase goes to the ground potential but the system doesn't trip. This system
must have a ground fault monitoring system. The use of line to neutral
(single phase) is prohibited (NEC, 250.36(3)) in HRG system, however,
phase to neutral is used with using the additional transformer having its
neutral grounded. When ground fault occurs in HRG system, the monitoring
systems gives alarm and the plant operators start the standby motor and
stop the faulty one for the maintenance. This way, the process plant is not
interrupted. The ground fault current is limited to 10A or less.
There are other two types such as Corner Grounding (for Delta system) and
Ungrounded system but they are not commonly used.
You have to select the resistance so that it can withstand 200A at least for
10 seconds.
Hope, it helps.
- MS