1) Customer, UPS and battery details
1.1 Customer Details
Customer Name :
Customer Address
Contact Person :
Contact No :
Email ID :
1.2 UPS Details
Hipulse -
UPS Model & Capacity 7200 7400M Hipulse Hipulse -E
EX
UPS Sr. No
MSDA
LBS Model Supplied Single Parallel LBS ELBS
panel
Page 2
Battery racks Earthing Grounded Ungrounded
Page 3
3) Methods of physical connection checks
Sr. No Power Section tightness checks UPS 1 UPS 2
3.1 Rectifier Section
3.2 Inverter Section
3.3 Static Switch Section
3.4 DC Filter Section
3.5 AC Filter Section
3.6 Transformer Terminal Connection
3.7 Transformer Bases & Core
3.8 Series chokes & other wire compound
3.9 Other power cables
3.10 Input termination (R, Y, B, N, PE)
3.11 Output Termination (R, Y, B, N, NE)
3.12 Bypass termination (R, Y, B, N)
3.13 Battery termination (+ve & -Ve)
3.14 All isolator termination
Page 4
4) Sizing of cable used & its observations
Sr. No Cables size & runs UPS 1 UPS 2
4.1 Input conductors
Neutral Earthing
4.6
conductors
4.7 PE Conductors
Page 5
5) PCB Jumper settings checks
Rectifier Logic Board
Plug Position Function UPS 1 UPS 2
1-2 Disable Battery Temperature/Voltage Compensation (Standard) Ok
X5
2-3 Enable Battery Temperature/Voltage Compensation
1-2 Fast DC Regulation Speed for ALL UNITS Ok
X6
2-3 Decreased DC Regulation Speed- NOT USED
1-2 Fast Walk-In
X7
2-3 Slow Walk-In: 10 Seconds+ (Standard) Ok
1-2 Disable Temperature Monitor (6P Rectifier)
X9
2-3 Enable Temperature Monitor (12P Rectifier) Ok
1-2 Enable Rectifier Temperature Monitor (12P Rectifier)
X10
2-3 Disable Rectifier Temperature Monitor (6P Rectifier) Ok
Page 6
UPS Logic Board
Plug Position Function UPS 1 UPS 2
Open for Parallel Operation
1-2
X12 Closed for Single-Module Operation
3-4 Open (Standard)
1-2 EPROM Enabled
X13
2-3 RAM Enabled (Standard) Closed
1-2 Open
3-4 Open
X14 Not Required; PCB Testing Only; Normally Open
5-6 Open
7-8 Open
Page 7
Inverter Bad Voltage for 10 Seconds Closed
3-4 OFF Latch Enabled = Closed (Standard)
OFF Latch Disabled = Open
5-6 Not Required
Security Password Override Closed
7-8 Closed = Override Security Password
Open = Enable Security Password (Standard)
Open Internal Battery Disabled
X31
1-2 Internal Battery Installed and Charger Enabled (Standard) Closed
Open RS485 Port Disabled
X32
1-2 RS485 Port Enabled (Standard) Closed
1-2 Calendar IC Supply from VRAM (Standard) Closed
X33
2-3 Calendar IC Supply from Internal Battery
1-2 G.V.C.O. to Inverter Logic (Parallel Module Operation) Closed
X34
2-3 Micro V.C.O. to Inverter Logic (Single Module Operation)
1-2 Manual Reset Output Buffers Closed
X35
2-3 Micro Reset Output Buffers (Standard)
1-2 Separate Battery Per Module (1 for each Rectifier) Closed
X36
2-3 Common Battery (Parallel Rectifiers)
1-2 No Function
X37
2-3 No Function (Standard) Closed
1-2 Close for 7200 (30 kVA–60 kVA)
X38
2-3 Close for Hipulse (80 kVA) Closed
Page 8
Operator Logic Board
Plug Position Function UPS 1 UPS 2
Open +5V Enable Main CPU (Standard)
X11
Closed ALE Enable Main CPU
0-1 Enable INV ON-OFF Push Button
0-2
0-3
0-4
X12
0-5 Open (Standard)
0-6
0-7
0-8
1-2 Inhibit Buzzer
X23
2-3 Enable Buzzer (Standard)
1-2 CAN bus Terminated (Standard)
X24
2-3 CAN bus not Terminated
1-2 RS232 Terminated (Standard)
X25
2-3 RS232 not Terminated
1-2 RS485 GND Connected to Board 0V
X26
2-3 RS485 GND not Connected to Board 0V (Standard)
X27 Open Standard (Test Only)
Page 9
Static Switch Driver Board
Plug Position Function UPS 1 UPS 2
0-1 Inhibit Temp Sensor (Standard)
X15 0-2 Open
0-3 Close
Page 10
Parallel Logic Board
Plug Position Function UPS 1 UPS 2
0-1
0-2
X4 0-3 Links are Closed to give a Fixed Ref Voltage to the Circuit
0-4
0-5
All Open
X5 No Links
Ref Signal is o_n_inv from the Parallel Connectors Board
Open Common Battery for all UPS Modules
0-2 Closed Separate Battery for each UPS Module
(Standard)
Open (Standard)
0-3
Closed Disable Open Parallel Cable Shutdown
X6
0-5 Open No Function
0-6 Open No Function
0-7 Open No Function
Open Normal Operation (Standard)
0-8
Closed Test Mode Active
1-2 60 Hz
X7
2-3 50 Hz (Standard)
X11 1-2 Board Test Only (Open = Standard)
1-2 Parallel Cable Screen Earthed
X13
2-3 Parallel Cable Screen NOT Earthed (Standard)
0-1, 0-2 Open Slow Slew Rate (0.1 Hz/Sec) Selected
X14
0-1, 0-2 Closed Fast Slew Rate (0.5 Hz/Sec) Selected
0-3
Page 11
High Voltage Interface Board (7200 / 7400M)
Shunt Plug Link Position Function UPS 1 UPS 2
- 0-1 30 kVA CT burden
selection
x31 0-2
x31 : x32 : x33 : x34 : x35 : x37 : x38 : x39 : x40 0-3
- 0-1 40 kVA CT burden
selection
x31 : x32 : x33 : x34 0-2
x35 : x36 : x37 : x38 : x39 : x40 0-3
- 0-1 60 kVA CT burden
selection
- 0-2
x31: x32 : x33 : x34 : x35 : x36 : x37 : x38 : x39 : 0-3
x40
Page 12
6) Control Parameters & windows checks
CARD SETTINGS
TEST
SI.NO CHECK MIN MAX UPS 1 UPS 2
POINT
1 CPS +12V V46 - K +12.95 +13.10
2 CPS --12V V45 - A -13.00 -13.05
3 DC Voltage reference X8 - 6 3.3 3.3
4 Rectifier Current Limit X8 - 7 -1.6 -1.6
Battery Current Limit.
5 X8 - 8 59mV / A 59mV / A
Ref. as per battery .Ah
Page 13
Parallel Logic Board – (GND – X10)
SOFTWARE SETTINGS
SI.NO CHECK UPS 3 UPS 4
1 Configuration
2 UPS capacity
3 NUM. OF. INVERTER OK Selection
4 Rated Output Voltage
5 Voltage Window (Upper / Lower – Input & Output)
6 Sync. Window
7 Slew Rate
8 Battery Capacity
9 No. Of Cell
10 Date and Time Set
11 Communication - Local / Remote / IGMNET / JBUS
Page 14
7) Power parameters & windows checks
Output Parameters
Sr. No Parameters
R phase Y phase B Phase
Voltage
Current
kW
UPS 1
kVA
PF
Frequency
Output Parameters
Sr. No Parameters
R phase Y phase B Phase
Voltage
Current
kW
UPS 2
kVA
PF
Frequency
TRF. Primary DC
TRF. Primary AC TRF. Secondary AC
Current Output Load Current
Current current
(Including Polarity)
Sr. No
R Y B R Y B R Y B R Y B
Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase
UPS 1
UPS 2
UPS 3
Page 15
8) AC / DC Capacitor health checkups
AC and DC Capacitors Bank
Sr. DC Capacitors AC Capacitors
Parameters
No
1 Capacitor Voltage
2 Capacitor Current
3 Any Leakage
5 Ambient Temp.
6 Capacitor Temp.
7 Physical Condition
8 DC Voltage Sharing
Charging current
9
with Battery
10 Ripple Current
Page 16
9) Battery health checks & cleaning
UPS 1 UPS 2
Sr. No Float Discharge Float Discharge
Batch Code Batch Code
Voltage Voltage Voltage Voltage
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Page 17
Battery health checkups
Sr. No Activity UPS 1 UPS 2
1 Cleaning of battery container
2 Terminal Tightness
3 Leakage on container
4 Physical damages if any
Inverter Transformer (Max 100 Deg Centigrade) AC Capacitors (Max 50 Deg Centigrade)
Page 18
Rectifier Heatsink (Max 60 Deg Centigrade) IGBT Heatsink (Max 70 Deg Centigrade)
Page 19
12) Important Note:
a) Do not connect OC web card in online.
b) Do not connect AS400 card in online.
c) Do not disconnect PLB in online.
d) Do not disconnect PLB until DC voltage drop completely Zero.
e) Do not disconnect PLB without convert it to single mode.
f) Do not forget to change the setup in the display when disconnected PLB.
Page 20