Improvement the Reliability of HV – Power

Transmission Lines Protection by Means of Modern


Devices and Methods
Arif M. Gashimov Fakhraddin L.Khidirov
Azerbaijan Scientific-Research & Design-Prospecting Azerbaijan Scientific-Research & Design-Prospecting
Power Engineering Institute Power Engineering Institute
Baku, Azerbaijan Baku, Azerbaijan
ahashimov@azerenerji.gov.az fkhidirov@gmail.com

Aytek R. Babayeva Ahmet Nayir


Azerbaijan Scientific-Research & Design-Prospecting Fatih University
Power Engineering Institute Istanbul, Turkey
Baku, Azerbaijan ahmetnayir@gmail.com
sunlite10@gmail.com

Abstract— The increased voltage profile due to excess of voltage networks and their mission load flow control in
reactive power in low load operation mode in power grid is normal and transient mode of operation of power system and
observed. Because of HV overhead lines are distant from power consequently to increase power supply quality. To the moment
generating sources and variable load curve, the voltage profile there is a tendency to tighten requirements to power quality,
could grow over nominal level and at the same time power loss because of new high technological and continuous processes
would increase. The last is caused by changed reactive power on the consumer side.
distribution at the system.
Commutation process for open-phase mode taking in account There are a number of equipment in operation which has
residual voltages for 500kV, 300km length HV line is studied. an ability more or less to compensate reactive power (RP) and
Calculations, performed in presence of controlled shunt reactors, all of them has some advantages and drawbacks.
gain special importance. The evaluated parameters are the main
factors, which define a necessary number of used reactors. Such In extra high voltage networks reactive power
HV lines usually equipped with nonlinear overvoltage limiters compensation and voltage normalization are provided by
and therefore then switching line on it is necessary to keep in means of non-controlled shunt reactors (SR). Shunt and
mind line’s VA function and residual voltages at the points of current limitation reactors are widely used at power grids in
limiters locations. At the same time at the open-phase operation the world. Shunt reactors (SR) are used at high voltage
mode it is necessary to provide protection for overvoltage networks to compensate excess of high voltage lines reactive
limiters. power in low load operation mode.
At the next stages the protection of overvoltage limiters from
quasi-steady overvoltages would be considered. The scientific It is known that operation of non-controlled SR is
principles of protection from internal and external overvoltages connected with some technical difficulties.
for transmission of electrical energy through polyphase (multi- The main of them are:
wire) overhead HV lines, which having been passive before, with
help of controlled shunt reactors and selection of VA functions of • necessity of frequent commutation of SR during some
overvoltage limiters becomes active, are proposed. The selection changes in transmission of power.
of residual voltage at the overvoltage limiter and different control
functions of shunt reactors are considered. • there is a need to install circuit breakers to connect SR
to the lines.
Keywords — power transmission line, controlled shunt reactors,
overvoltage limiters. • reactor commutation lead to transient overvoltage’s
and as a result-deterioration of isolation of high voltage
equipment and shunt reactor itself.
I. INTRODUCTION
Outage in power supply system is a serious problem on • reduced circuit breaker operation life time.
now days not only for Azerbaijan, but also for other countries Therefore in high voltage network a series compensation
and this problem has to be solved immediately. The above of power lines inductance became popular. This measure lets
mentioned failures are connected with reactive power to increase a transmission capacity of line which none the less
compensation for transmission lines. Reactive power for lengthy lines is not exceed natural limit of transmission
compensation means are devices (equipment) installed at high capacity defined by natural power of line. Besides this

Modern Electric Power Systems 2015 – MEPS’15 Wroclaw, Poland – July 6-9, 2015
www.meps15.pwr.edu.pl

978-1-5090-3101-6/15/$31.00 ©2015 IEEE


measure cause some other difficulties which diminish Where:
reliability of power transmission.
Lk , rk - Inductance and resistances of model which considers
This situation could be overcome by application of more skin effect;
effective controlled static reactive power compensators (SC),
reactors with excitation control (ECSR), transformer type υ - diagonal matrice of EM wave speed propagation along HV
controlled shunt reactors (CSRT). line;
The purpose of this paper selection and coordination of 0,5 - diagonal matrice;
main parameter of protection devices and right places for their
installation to provide efficient protection of equipment in τ - diagonal matrice of calculation step in time domain;
electrical network from overvoltage’s caused by lightning or
appeared due transients. U p ,U q , i p , iq − known values of voltage and current column
matrices in points p and q of HV line with coordinates;
At the same time the main solved problems are:
• selection and validation of models for calculation of
i f k - column matrice of known currents in k-branch of model
surge processes in multi-wire circuits, caused by which considers skin effect in the point of HV line with
internal and lightning surges. coordinates;
• search for more effective arrangement of protective id k - column matrice of new values for current in branch k of
devices location.
skin effect model at the same point of HV line with
coordinates.
II. MODELING OF ELECTROENERGETIC WAVE
PROCESSES IN MULTIWIRE ELECTRICAL NETWORK Matrice zn/ has the form:
k

The equations to calculate column matrix of voltages and


current Ud and id for multi-wire transmission line with
coordinates (x,t) known as [1]: zn11 χ k11 zn12 χ k12 zn13 χ k13
z = zn 21 χ k 21
/
nk zn22 χ k 22 zn23 χ k 23 ,
(1 + hzg )U d + ( z + zn )id = Ap ½° (1)
¾
− (1 + hzg )U d + ( z + zn )id = Aq °¿
zn31 χ k 31 zn32 χ k 32 zn33 χ k 33

here Where χ k = ( Lk − τrk )( Lk + τrk ) −1 , k = 1,2,3.

Diagonal matrices z S k , χ k , zn* , of 3-wire line for example


n
A p = U p + zi p + θ , Aq = −U q + zi q + θ , θ = ¦ z k i f k , (2) has a view:
k =1

3
0,5υ ( Lk11 + τrk11 ) 0 0
id k = z S−k1U S + χ k i f k , U S = z n* (id − ¦ χ k i f k ), (3)
k =1 zS k = 0 0,5υ ( Lk 22 + τrk 22 ) 0 ,
0 0 0,5υ ( Lk 33 + τrk 33 )
There coordinates of d, p, q, f consequently (x,t), (x-h,t-IJ) ɢ
(x, t-2IJ):
zn11 0 0 χk 11
0 0
h – diagonal matrix of step evaluation for distance; *
z = 0 zn22 0 , χk = 0 χk 0
n 22
g – square admittance matrix of transmission line along its 0 0 zn33 0 0 χk
length; 33

z – matrix of line impedance without losses (square matrix) Where k=1, 2, 3 - a number of parallel branches in a model
considering skin effect.
−1 −1 −1
ª 3 −1 º ª 3 −1 º ª 3 −1 º
«¦ (Lk + τrk )11 » «¦ (Lk + τrk )12 » «¦ (Lk + τrk )13 » III. ESTIMATION OF OVL APPLICATION
¬ k =1 ¼ ¬ k =1 ¼ ¬ k =1 ¼ EFFICIENCY TO INCREASE LIGHTNING PROOFNESS
−1 −1 −1
ª 3 −1 º ª 3 −1 º ª 3 −1 º
zn = 0,5υ «¦ (Lk + τrk )21 » «¦ k ( L + τr )
k 22 » «¦ k ( L + τr )
k 23 » ,
OF OVERHEAD POWER LINES
¬ k =1 ¼ ¬ k =1 ¼ ¬ k =1 ¼
ª 3 −1 º
−1
ª 3 −1 º
−1
ª 3 −1 º
−1 To estimate an efficiency of OVL in different transient
«¦ (Lk + τrk )31 » «¦ (Lk + τrk )32 » «¦ (Lk + τrk )33 » modes of operation the efforts were continued in direction to
¬ k =1 ¼ ¬ k =1 ¼ ¬ k =1 ¼
increase the accuracy of mathematical modeling. For this
purpose besides of IEEE model there was used the
mathematical description of nonlinear resistor using interpola-
tion method.
Considering volt-ampere function in the certain intervals During operation of HV line there could occur regular or
and using spline interpolation certain mathematical extraordinary open-phase mode with resonance circuits
expressions were written. including phase and interphase capacitances of HV line and
inductances of powerful reactors. In these modes there could
On the base of these expressions equations for multi wire appear increased voltages on line itself as well as on connected
system are recorded in form of matrices. For studied multi equipment (non-linear voltage limiters) which could lead to
wire systems (multi-wire overhead transmission lines) the isolation electrical durability failure and possible destruction.
conducted researches pointed out that the used algorithm has We have to note that protective devices as OVL could not
to be improved. Therefore the above mentioned numerical withstand against resonance overvoltages because of limited
equations have to be expressed as matrices with equal rates. power of their varistors [4].
To evaluate the system of non-linear equations the As an example take a look on failure development on
iteration rule and Vegstain accuracy method are used [2]. 500kV, 470km overhead transmission line. Then it was
Taking in account that surges caused by lightening is high switched on after repair there took place a short circuit
frequency process and non-interruptible operation of shunt because of OVL external isolation flash over (it may be caused
reactor, the variation of its parameters as a function of voltage by humidity and moistening of sand filling internal cavity of
is demanding the acceleration of iteration, because reduction OVL if a repair took a long time and therefore OVL was not
of calculation step may increase the calculation period and under the voltage). In the studied case transmission line was
reduce the accuracy. The various mathematical methods were equipped by one phase automatic reclosure units, so if short
studied and tested. Obtained preliminary results may us to circuit (SC) takes place on one phase this phase is switched off
believe that better decision is resulted then using Aitken. from both ends. Similar process may take place on the
Samoukh – Gardabany line (Fig.2). Taking all this in account
Taking in consideration the above mentioned methods the we have done a series of evaluation for automatic reclosure in
evaluation of efficient protection of OVL from lightning using presence of OVL.
developed algorithm is made. It is known that together with
OVL protection from lightning and surges caused by
commutation in grid it is necessary to protect OVL from
resonance condition. To perform such function research is
conducted with help of above mentioned algorithm and this
permit to evaluate overvoltages with different action time.
Study results provide OVL protection for different transients
in case of shunt reactors installed (Fig.1).

Fig.2. Communication of Azerbaijan power system with the Georgian energy


system

Then using CSR it is advisable to study not only normal


operation mode but pay attention on various kinds of regular
and non-regular open-phase commutation which take place
during operation and may be a reason for appearing of quasi-
stationary resonances occurred in commutation leading to
serious failure.
Fig.1. Interpolation current-voltage characteristics of the OVL
To estimate operation of CSR which let us to carry out a
smooth control in normal mode of operation of transmission
IV. APPLICATION OF CONTROLLED SHUNT line with variable load and also optimal control of quasi-
REACTORS. POSSIBLE PROBLEMS AND HOW TO stationary open-phase and non-symmetrical regimes to provide
SOLVE THEM a reliable operation of equipment connected to the
It is known that controlled reactor in automatic mode transmission line it is necessary to continue researches on live
without commutation by switch is compensating reactive line as well as on computer model.
power especially in lengthy 500, 230 and 110kV overhead The mathematical model to study electro-magnetic
transmission lines. transients in complex multi-wire lines and appropriate
The necessity for application of controlled shunt reactors algorithm were developed for open-phase and non-
(CSR) depends only from lines voltage, length and symmetrical mode of operation.
capacitances of reactive power components. CSR provides The next problems were defined and solved:
both – a smooth automatic control of consumed power and
optimal regime concerning of voltage and reactive power 1. Expressions to evaluate currents and voltages in
without commutation and service personnel interference [3]. intermediate points of multi-wire network.
2. Parameters of multi-wire overhead transmission lines The obtained results could be seen on Fig.4.
(OTL).
3. Parameters of model to take in account skin effect in
wires and ground.
4. Parameters of model to take in account corona effect for
multi-wire OTL.
5. Parameters of matrices for OTL evaluation expressions.
Application of CSR on transit transmission lines lets in
addition to solve a problem of premature deterioration of
switching equipment.
Other important moment is provision of necessary quality
of electrical energy transferred through interstate transmission a. - The voltage at the Samukh (without line reactor and OVL)
lines in accordance with international standards. In these
circumstances the using of CSR to normalize voltage level and
OTL operation improvement is necessity [5].
Operation speed of CSR is also very important parameter.
There is a wrong opinion that CSR is very sluggish device.
Provision of necessary regime in grid (phase-by-phase
power control, provision of ALR and repeated ALR, arc
interruption in ALR interval, etc.) all problems of impact of
occurred in grid overvoltages caused either by lightning or
switching procedure (impact of voltage surges on controlled
reactive power sources or vice versa, impact of sources on grid
in presence of overvoltages) are solved equally with slight
b. The voltage at the Gardabany (without line reactor and OVL)
time difference. With no load the time which is necessary for
CSR to reach nominal power level according to some
information sources is equal to 5 seconds [6].
There was formulated the task to define the action time for
CSR installed on OTL Samoukh-Gardabany.
The design scheme of transmission could be seen on Fig.3.

c. The voltage at the Samukh (availability reactor Mingechaur and Samukh)

d. The voltage at the Gardabany (availability reactor Mingechaur and


b Samukh)
Fig.3. Design scheme of power transmission: a - Presence in Mingechaur and
Samukh reactor: 1 - Mingechaur, 2- Samukh, 3- Gardabany; b. Presence in Fig.4. The obtained results
Mingechaur reactor, in Samukh reactor and OVL
As seen from the curves the presence of OVL and reactor then line transforms from passive to active element of the grid
stabilizes the voltage on line despite the absence of the reactor and the nature of this transformation is controlled shunt
at the node 3. This is due to the parallel connection of the reactor consuming extra reactive power and non-linear over-
reactor at the node 2 of the OVL. voltage limiter with characteristics which are in good
compliance with residual voltages of OVL and this helps to
CONCLUSION get various regulation characteristics of CSR.

1. Algorithm for evaluation of HV-line commutation in


REFERENCES
presence of controlled shunt reactor and surge limiter is
developed. [1] Gashimov A.M., Dmitriyev E.V., Pivchik I.R. Numerical analysis of
wave processes in electric networks, Novosibirsk: Science, 2003, p.153
2. Algorithm for evaluation of multi-circuit HV-line [in Russian].
commutation in presence of controlled shunt reactor and surge [2] G.N.Lance, Numerical methods for high speed computers, Moscow:
limiter is developed. 1962, pp. 171-192 [in Russian].
[3] O.Matveev, Shunt reactors. Electrical news, #3(75), 2012, pp.1-3. [in
3. Evaluation algorithm and estimation of line isolation Russian].
protection from lightning in presence of controlled shunt [4] K.Kadomskaya, Efficiency and manageability of shunt reactors.
reactor and surge limiter. Electrical news, #6(78), 2012 [in Russian].
[5] S.V.Jatukova, Controlled shunt reactors to compensate reactive power
4. Evaluation algorithm and estimation of multi-circuit and regulate voltage in the power grids of single power system of
line isolation protection from lightning in presence of Kazakhstan. Electrical engineering, #1, 2003, pp.18-22 [in Russian].
controlled shunt reactor and surge limiter. [6] A.M.Bransev, A.G.Dolqopalov, Three-phase shunt reactor is controlled
by the capacity of 100 MVA. Electrical engineering, #1, 2003, pp.22-30
5. Scientific basis of multi-wire line protection from [in Russian].
internal surges and those caused by lightning under conditions