You are on page 1of 4

COMPLIANCE SHEET FOR CABLE SCHEDULE

Da
S.NO. COMMENTS FROM NTPC REPLY OF HPIPL

CABLE DATA SHEET TO BE PROVIDED (FOR CABLE & MOTOR


CABLE DATA SHEETS WILL BE PROVIDED ONLY AFTER APPROVAL
1 TECHNICAL CLEARANCE WILL BE GIVEN ON THE BASIS OF OF CABLE SCHEDULE.
MANUFACTURER DATA SHEET W.R.T. OUR SPECIFICATION).

THE MAXIMUM ALLOWABLE VOLTAGE DROP DURING NORMAL RUNNING ALREADY TAKEN INTO CONSIDERATION. NOWHWERE IT IS
2 FROM MCC TO LOAD SHALL NOT EXCEED 3% OF 415 VOLTS UNDER FULL EXEEDING 3%.
LOAD CONDITION.

KINDLY CONFIRM THAT LENGTH OF CABLES ASSUMED IS SUBJECT TO


3 NOTED & CONFORM.
MODIFICATION IN VIEW OF SITE REQUIREMENT AND CIVIL CONSTRAINTS.

CABLE QUANTITY FROM MCC CONTRACTOR TO LPBS AND INCOMER


4 POWER SUPPLY CABLES (TECH SPEC CLAUSE NO-2.02.00), LIGHTING, NOTED & CONFORM.
INSTRUMENT CABLES ETC ARE NOT CONSIDERED (ALL CABLE SUPPLY AND
LAYING IS COVERED IN THE BIDDER'S SCOPE).
EFFICIENCY & POWER FACTOR FIGURES SPECIFIED FOR MOTORS AND
5 OTHER LOADS ARE AS PER VENDOR DATA SHEETS. ALREADY TAKEN AS PER DATA SHEETS.

THE FIGURES INDICATED IN THE DOCUMENT ARE BASED UPON VENDOR


6 DATA FOR ALL RELATED EQUIPMENT AND DATA SHEET TO BE PROVIDED BY NOTED & CONFORM.
THE VENDOR.

NECESSARY CARE SHALL BE TAKEN BY THE VENDOR IF REQUIRED FOR


SMOOTH OPERATION (TO REDUCES THE MECHANICAL AND ELECTRICAL
7 STRESS AND TO ACCELERATED THE EQUIPMENT SMOOTHLY) OF MOTOR (AS NOTED & CONFIRM
PER NTPC APPROVED TECHNICAL SPECIFICATION CLAUSE NO.-3.06.00, SUB-
SECTION A AND CLAUSE NO-6.00.00-(9), SUB SECTION A)
8 MAKE SHALL BE AS PER NTPC QA APPROVAL NO QA APPROVAL LIST IS THERE WITH TENDER.
9 CABLE SHALL BE AS PER TECH SPEC CLAUSE NO.-4.08.00 NOTED & CONFIRM.
Date: 14.06.2019