You are on page 1of 5

Multimeter measurements

on variable frequency
drives using the new
Fluke 289 DMM Application Note
Editor’s note: For similar instructions using the
Fluke 87V DMM, reference Fluke article 12345.
In the past, motor repair meant dealing
with traditional three-phase motor failures
that were largely the result of water, dust,
grease, failed bearings, misaligned motor
shafts, or just plain old age. But, motor
repair has changed in a big way with the
introduction of electronically controlled
motors, more commonly referred to as
variable frequency drives (VFD). Drives
present technicians with a unique set of
measurement problems that can vex the
most seasoned pro.
This application note describes the elec-
trical measurements you can make dur-
ing the installation and commissioning of
a drive, as well as other measurements
to aid in diagnosing bad components, and
other conditions that may lead to prema-
ture motor failure in VFDs.

Troubleshooting Next, take care to make incorporating the same selectable


philosophy accurate measurements. Nobody low pass filter found in the
makes inaccu­rate measurements successful 87V DMM. The filter
There are many different ways on purpose of course, but it’s allows the meter to make
to go about troubleshooting an easier to do than you may think, accurate drive
electrical circuit, and a good especially when working in a output
troubleshooter will always find high energy, noisy environment measure-
the problem—eventually. The like that of an VFD. Choosing the ments that
trick is to track down the problem right test tools for troubleshoot- will now
as quickly as possible, keeping ing, the drive, the motor, and agree with
downtime to a minimum. the connections is of the utmost the motor
The most efficient procedure importance. This is especially true drive controller
for troubleshooting is to begin at when making voltage, frequency display indica-
the motor, and then systemati- and current measurements on the tions. No longer
cally work back toward the elec- output side of the motor drive. does the technician have to
trical source, looking for the most Until now the only meter on guess whether the drive is
obvious problems first. A lot of the market able to make these operating correctly and deliv-
time and money can be wasted measurements accurately was ering the correct voltage, current,
replacing perfectly good parts the Fluke 87V Digital Multimeter. or frequency for a given control
when the problem is nothing Fluke has just introduced the next setting.
more than a simple loose con- generation of high performance
nection. Multimeter, the new Fluke 289, Drive measurements

From the Fluke Digital Library @ www.fluke.com/library


Input side measurements Safety ratings for
You can use any good quality electrical test equipment
true rms multimeter to verify
proper input power to the drive. ANSI and the International
The input voltage readings Electro­technical Commission (IEC)
should be within 2 % of one are the primary independent
another when measured phase organizations that define safety
to phase with no load. A sig- standards for test equipment
nificant unbalance may lead manufacturers. The IEC 61010
to erratic drive operation and second edition standard for test
should be corrected when dis- 289 dual display showing frequency
equipment safety states two
covered. and voltage basic parameters, a voltage rat­
ing and a measurement category
Output side measurements Fluke’s new 289 multimeter, rating. The voltage rating is the
Measurements on the output with it’s ¼ VGA dot matrix dis- maximum continuous working
side of a pulse width modulated play, has the ability to display voltage the instrument is capable
(pwm) motor drive have been multiple parameters at the same of measuring. The category rat-
difficult or impossible to make, time and utilize the selectable ings depict the measurement
especially accurate measure- low pass filter, giving the trou- environment expected for a given
ments, that would agree with bleshooter or engineer the ability category. Most three-phase VFD
the drive controller displayed make accurate voltage, current installations would be considered
values. The traditional true rms and frequency measurements a CAT III measurement environ-
multimeter will not provide accu- on the output side of the drive ment with power supplied from
rate answers. This is because either at the drive itself or at the either 480V or 600V distribution
the voltage applied to the motor motor terminals and also display systems. When using a digital
terminals by the VFD is a pulse the filtered output voltage and multimeter for measurements
width modulated non-sinusoidal frequency (motor speed) simulta- on these high energy systems,
voltage. neously. With the filter selected, insure that the
A true-rms DMM will give the 289 readings for both volt- multimeter is
an accurate reading of the heat- age and frequency (motor speed) rated at a mini-
ing effect of the non-sinusoidal should now agree with the mum for CAT III
voltage applied to the motor, but associated drive control display 600V and pref-
will not agree with the motor indications if they are available. erably for CAT
controller’s output voltage read- When measuring output current IV 600V/CAT
ing which is displaying the with a clamp accessory, the low III 1000V. The
rms value of the fundamental pass filter allows for accurate category rating and voltage limit
component only (typically from current measurements and fre- are typically found on the front
30 Hz to 60 Hz). The issues are quency measurements simultane- panel of the multimeter right at
bandwidth and shielding. Many ously when using the Hall-effect the input terminals.
of today’s true rms digital multi- type clamps. All of these mea-
meters have a wide bandwidth, surements are especially helpful
sometimes out as far as 20 kHz when making measurements
or more, which allows the meter at the motor location when the
to respond not only to the fun- drives displays are not in view.
damental component that the Making safe measurements The new Fluke 289 DMM
motor really responds to, but also Before making any electri- is dual rated CAT IV 600V
to all of the high frequency com- cal measure­ments, be sure you and CAT III 1000V.
ponents generated by the pwm understand how to make them
drive. safely. No test instrument is com- Refer to the ABC’s of DMM Safety
In addition, if the dmm is pletely safe if used improperly, from Fluke for additional information
not shielded for high frequency and you should be aware that on category ratings and making safe
noise, this can also lead to poor many test instruments on the measurements.
measurement performance due to market are not appropriate for
the high noise levels generated testing variable frequency drives.
by the drive controller. Because Also insure that the appropriate
of their higher bandwidth and personal protective equipment
shielding issues, many true rms (PPE) is used in accordance with
meters will display readings as the specific working environ-
much as 20 to 30 % higher than ment and the measurements to
the drive controller is indicating. be made. If at all possible, never
work alone.

2 Fluke Corporation Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
Making the measurements The new Fluke 289 also contains
Measurements for this procedure internal memory for saving 1.  Connect the clamp to the 289’s common and
will be made on a 480 V three specific individual measurements 400 mA input jacks.
phase drive control at the control that can be recalled on screen or
2.  Select the mA/A ac function.
panel terminal strips using the downloaded to reports generated
new Fluke 289 digital multimeter. by Fluke View Forms® software. 3.  Place the clamp around each of the input supply
phase cables in succession, recording or saving
These procedures would also be Input Current to internal memory each of the readings as they
valid for lower voltage 3 phase Measuring the input current are taken. Since these clamps output 1 milliamp
drives powered by either single requires using a current clamp per amp, the milliamp readings shown on the
or 3 phase supply voltages. For accessory. This is because it is 289 display are the actual phase current read-
these tests the motor is running not practical to “break the circuit” ing in amps.
at 30 Hz. to make an in-line series current
Input Voltage measurement. Regardless of the Hall Effect type (AC/DC) clamp (i410, i-1010)
To measure the ac voltage supply type of clamp used, check to 1.  Connect the clamp to the 289’s common and
to the input side of the drive at insure that all readings are V/Ω input jacks.
the drive: within 5 % of each other for 2.  Select the 289’s mVac voltage function for cur-
1.  Select the 289’s ac voltage proper balance. rent measurements up to 500 amps.
function. Transformer type clamp 3.  Since the lowest range on the 289 is
2.  Connect the black probe to (Fluke models i200, i400, 50.000 mVac push the range button once to
one of the three phase input place the meter in the 500.00 mVac range if
80i-400, 80i-600A, i800)
terminals. This will be the the drive current will exceed 50 amps for the
reference phase. measurement.
3.  Connect the red probe to one 4.  Place the clamp around each of the input supply
of the other two phase input phase cables in succession, recording each of
terminals and record the the readings as they are taken or again save to
reading or save it to the the 289’s internal memory. Since these clamps
289’s internal memory. output 1 millivolt per amp, the millivolt readings
4.  Leaving the black probe on shown on the 289 display are the actual phase
the reference phase now current reading in amps.
move the red probe to the
third phase input and record
or save this reading to the
289’s internal memory.
5.  Check to make sure that
there is no more than a 2 %
difference between these
two readings.

289 with i1010


AC/DC Clamp accessory

3 Fluke Corporation Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
Output voltage and motor speed using the low pass filter Output voltage reading with low pass filter enabled

Output voltage and motor speed


(Output frequency using voltage as a reference)
An important new feature on the 289 multimeter is its’ ability
to simultaneously display both the filtered output voltage and
frequency (motor speed) at the same time without having to push
additional buttons or change functions.
To measure the ac output voltage and motor speed, either at the
drive or at the motor disconnect:
1.  Plug the black test lead into the common jack and the red test
Output voltage and frequency (motor speed)
lead into the V/Ω jack. without the low pass filter (incorrect readings)
2.  Select the 289’s ac voltage function.
3.  Select MENU then (LPF+Hz)
to enable the low pass filter
and the Hz function.
4.  Connect the black probe to one of the three phase output voltage
or motor terminals. This will be the reference phase.
5.  Connect the red probe to one of the other two phase output
voltage or motor terminals and record the reading or save to the
289’s internal memory.
6.  Leaving the black probe on the reference phase now move the
red probe to the third phase output voltage or motor terminal and
record or save this reading.
Output voltage and frequency (motor speed)
7.  Check to make sure that there is no more than a 2 % difference using the low pass filter (correct readings)
between these two readings. These readings should also agree
within these limits with the controller display panel if available.
8.  If the low pass filter is not enabled the output voltage readings
may be between 10-30 % higher than what is expected and the
frequency readings will be inaccurate and unstable.

4 Fluke Corporation Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
Output current and frequency 3.  Select MENU then (LPF+Hz)
(motor speed) to enable the low pass filter
and the Hz function. This will allow the
With the large dot matrix display on the 289 meter to reject all of the high frequency noise
multimeter, it is possible to display both the ac generated by the drive controller. Once the low
current reading and its’ associated frequency pass filter has been enabled the meter is now
simultaneously, allowing the technician or installer in manual range mode.
to see both the load current and motor speed at
4.  Since the lowest range on the 289 is 50.000
the same time, in the same display.
mVac push the range button once to place
Transformer type clamp (i200, i400, the meter in the 500.00 mVac range if the
80i-400, 80i-600A, i800) drive current will exceed 50 amps for the
1.  Regardless of the type of clamp used, check measurement.
to insure that all phase current readings are 5.  Place the clamp around each of the output
within 5% of each other for proper balance supply phase cables in succession, recording
2.  Connect the clamp to the 289’s common and each of the readings as they are taken or again
400 mA input jacks. save to the 289’s internal memory. Since these
3.  Select the mA/A ac function. If you want to take clamps output 1 millivolt per amp, the millivolt
advantage of the 289’s dual display, then select readings shown on the 289
MENU then Hz. display are the actual phase Caption?
4.  Place the clamp around each of the output current reading in amps.
phase cables in succession, recording each of
the readings as they are taken or save them to
internal memory for later use.
Since these clamps output 1
milliamp per amp, the milliamp
readings shown on the 289
display are the actual phase
current reading in amps as
well as the frequency of the ac
current signal.
Hall Effect type (AC/DC) clamp
(i410, i-1010)
1.  Connect the clamp to the 289’s
common and V/Ω input jacks.
2.  Select the 289’s mVac
voltage function for current
measurements up to 500 amps.

Phase current reading + motor speed using i1010 clamp


Fluke. Keeping your world
up and running.®
DC Bus measurements To measure the dc bus voltage:
A healthy dc bus is a must for a 1.  Select the 289’s dc voltage
Fluke Corporation
properly operating motor drive. If function. PO Box 9090, Everett, WA USA 98206
the bus voltage is not correct or 2.  Connect the black probe to Fluke Europe B.V.
unstable it may be an indication either the DC- or B- terminal. PO Box 1186, 5602 BD
that the converter diodes or 3.  Connect the red probe to the Eindhoven, The Netherlands

capacitors may be starting to fail. DC+ or B+ terminal. For more information call:
The bus voltage should agree In the U.S.A. (800) 443-5853 or
The dc bus voltage should be Fax (425) 446-5116
approximately 1.414 times the with the example mentioned In Europe/M-East/Africa +31 (0) 40 2675 200
phase to phase input voltage. above and be relatively stable. or Fax +31 (0) 40 2675 222
You can also check the amount In Canada (800)-36-FLUKE or
For a 480 volt input, the dc bus Fax (905) 890-6866
should be approximately 679 of ac ripple on the bus by simply From other countries +1 (425) 446-5500 or
V dc. The DC Bus is typically switching the 289’s function Fax +1 (425) 446-5116

labeled as DC+, DC- or B+, B- on switch to the vac function. Web access: http://www.fluke.com
©2008 Fluke Corporation. Specifications subject
the drive terminal strip. to change without notice. Printed in U.S.A.
7/2008 3291974 A-EN-N Rev A

5 Fluke Corporation Multimeter measurements on variable frequency drives using the new Fluke 289 DMM

You might also like