King Salman International Complex for Maritime
Industries and Services Project-KSIC
INSPECTION AND TEST PLAN
For Earthworks up to Formation Level
Document No.: 11083-QLT-ITP-001
Revision No.: 4, Date: 10 Dec 2017
Page 2 of 3
SHC
Noted and Rectified (MS)
SHC
Noted and Rectified (MS)
King Salman International Complex for Maritime
Industries and Services Project-KSIC
INSPECTION AND TEST PLAN
For Earthworks up to Formation Level
Document No.: 11083-QLT-ITP-001
Revision No.: 4, Date: 10 Dec 2017
Attachment
For
(ITP No.SAR-HTA-001_Rev.4)
Page 3 of 3
SAR-HTA ITP - REV. 4
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES AND SERVICES 25-00053-0003 SARCO-HUTA Consortium
INSPECTION RESPONSIBILITY
ITEM PROJECT PHASE / QUALITY QUALITY ASSIGNMENTS
TASK / ACTIVITY REMARKS
NO. ACTIVITY CODE PROCEDURE RECORD THIRD SARCO /
ARAMCO
PARTY HUTA
SHIC-Q-EW- SHIC-Q-EW-
1.1 Third Party Laboratory Testing Approval
0001 0001
N/A RH R
SHIC-Q-EW- SHIC-Q-EW-
2.1 Dredge Fill Material Receiving Inspection
0003 0003
N/A H W
3.0 CONSTRUCTION
SHIC-Q-EW- SHIC-Q-EW-
3.2 Backfilling and Compaction Inspection
0006 0006
N/A W W/S
SHIC-Q-EW- SHIC-Q-EW-
3.4 Compaction Test
0008 0008
N/A H W
SHIC-Q-EW- SHIC-Q-EW-
4.1 Final Fill Inspection
0009 0009
N/A H/R H
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES AND SERVICES 25-00053-0003 SARCO-HUTA Consortium
INSPECTION RESPONSIBILITY
ITEM PROJECT PHASE / QUALITY QUALITY ASSIGNMENTS
TASK / ACTIVITY REMARKS
NO. ACTIVITY CODE PROCEDURE RECORD THIRD SARCO /
ARAMCO
PARTY HUTA
2 Surveillance: QA/QC organization to monitor work in progress without notice from Construction Organization.
Witness: QA/QC organization shall be notified of the timing of Inspection or test in advance. However, the inspection or test shall be performed as scheduled if the QA/QC organization
3 representative is not present.
4 Hold: QA/QC organization shall be notified of the timing of inspection or test in advance. Inspection or test shall not be carried out without the QA/QC organization representative in attendance.
5 If the Main Contractor delegates the assigned responsibility to the Subcontractor, then the Main Contractor will have the same degree of responsibility as assigned to MYDP.
LEGEND
H Hold Point for QC Inspection/ Test R Review of Documents
W Witness Inspection/Test RH Review and Approval of Documents
S Surveillance I 100% Contractor Inspection/Test
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
SH ITP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 1.0 (1.1)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
R RH
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
All equipments to be used for testing shall have valid PB4784-1001-MA-SP-0049 Rev. 12
1.1b
calibration certificates and are in good operational condition. Sec. 1.9.10
PB4784-1001-MA-SP-0049 Rev. 12
1.1d Initial survey to be done for TPTL.
Sec. 1.8
Initial survey report submission to company along with all PB4784-1001-MA-SP-0049 Rev. 12
1.1e
mentioned documents in checklists. Sec. 1.10
REMARKS:
REFERENCE DOCUMENTS:
1- Schedule Q
2- Minutes of Meeting (M.O.M.)
3- PB4784-1001-MA-SP-0049 Rev. 12 Technical Specification - Dredging and Reclamation Works
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 1 of 1
11083-QLT-CL-F001 Rev 0.0 26-SEP.-2017
SAIC NUMBER DATE APPROVED SHC-QR NUMBER
ARCHIRODON - HUTA Hegerfeld
SHIC-Q-EW-
Fill Material Sampling, Testing and Review of Test Reports 03-Dec-17 Civil
0002
PROJECT TITLE BI No. CONTRACTOR / SUBCONTRACTOR
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES
25-00053-0003 SARCO-HUTA Consortium
AND SERVICES
LOCATION
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
SH ITP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 1.0 (1.2)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
RH/H RH/H
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Plasticity Index test shall be conducted at a minimum of 5 tests for PB4784-1001-MA-SP-0049 Rev. 12
1.2a-1
each type of fill per source prior to use. Sec. 3.9 Table 3-1
Grading (PSD) test shall be conducted at a minimum of 5 tests for PB4784-1001-MA-SP-0049 Rev. 12
1.2a-2
each type of fill per source prior to use. Sec. 3.9 Table 3-1
Particle Density test shall be conducted at a minimum of 5 tests for PB4784-1001-MA-SP-0049 Rev. 12
1.2a-4
each type of fill per source prior to use. Sec. 3.9 Table 3-1
The Sand Dune fill material to be used shall be in compliance with SHIC-Q-EW-0002 (Checklist)
1.2b
the specification. 2.2.1a to 2.2.1g
Clarify the stockpile reference number of approved Sand Dune fill SHIC-Q-EW-0002 (Checklist)
1.2c
material to be in use. 2.2.1a to 2.2.1g
REMARKS:
REFERENCE DOCUMENTS:
1- SHIC-Q-EW-0004 (Checklist)
2- PB4784-1001-MA-SP-0049 Rev. 12 Technical Specification - Dredging and Reclamation Works
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 1 of 1
11083-QLT-CL-F001 Rev 0.0 26-SEP.-2017
SAIC NUMBER DATE APPROVED SHC-QR NUMBER
ARCHIRODON - HUTA Hegerfeld
Dredge Fill Material Receiving Inspection SHIC-Q-EW-0003 03-Dec-17 Civil
PROJECT TITLE BI No. CONTRACTOR / SUBCONTRACTOR
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES
25-00053-0003 SARCO-HUTA Consortium
AND SERVICES
LOCATION
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
SH ITP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 2.0 (2.1)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
W H
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Plasticity Index test shall be conducted at a minimum of 5 tests for PB4784-1001-MA-SP-0049 Rev. 12
2.1a-1
each type of fill per source prior to use. Sec. 3.9 Table 3-1
Grading (PSD) test shall be conducted at a minimum of 5 tests for PB4784-1001-MA-SP-0049 Rev. 12
2.1a-2
each type of fill per source prior to use. Sec. 3.9 Table 3-1
Particle Density test shall be conducted at a minimum of 5 tests for PB4784-1001-MA-SP-0049 Rev. 12
2.1a-4
each type of fill per source prior to use. Sec. 3.9 Table 3-1
The dredge fill material to be used shall be in compliance with the SHIC-Q-EW-0002 (Checklist)
2.1b
specification. 1.2.2a to 1.2.2g
Clarify the stockpile reference number of approved dredge fill SHIC-Q-EW-0002 (Checklist)
2.1c
material to be in use. 1.2.2a to 1.2.2g
REMARKS:
REFERENCE DOCUMENTS:
1- SHIC-Q-EW-0002 (Checklist)
2- PB4784-1001-MA-SP-0049 Rev. 12 Technical Specification - Dredging and Reclamation Works
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 1 of 1
11083-QLT-CL-F001 Rev 0.0 26-SEP.-2017
SHIC-Q-EW-
Sand Dune Fill Material Receiving Inspection 03-Dec-17 Civil
0004
PROJECT TITLE BI No. CONTRACTOR / SUBCONTRACTOR
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES
25-00053-0003 SARCO-HUTA Consortium
AND SERVICES
LOCATION
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
SH ITP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 2.0 (2.2)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
W H
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Fill Material used for Reclamation or for placement adjacent to PB4784-1001-MA-SP-0049 Rev. 12
2.2a
Marine Structures shall be inert, free draining granular material. Sec.3.9.
Fill Material shall not contain any material susceptible to volume PB4784-1001-MA-SP-0049 Rev. 12
2.2b
change, including marine mud, swelling clays and collapsible soils Sec.3.9.
Fill Material shall not contain peat, vegetation, timber, organic, PB4784-1001-MA-SP-0049 Rev. 12
2.2c
soluble or perishable material Sec.3.9.
Fill Material shall not contain dangerous or toxic material or PB4784-1001-MA-SP-0049 Rev. 12
2.2d
material susceptible to combustion. Sec.3.9.
Fill Material shall not contain metal, rubber, plastic or synthetic PB4784-1001-MA-SP-0049 Rev. 12
2.2e
material. Sec.3.9.
Check unsuitable soil move at Disposal Area maximum thickness PB4784-1001-MA-SP-0049 Rev. 12
2.2f
0.60m Sec.3.5.8
Uniformity coefficient >3 when tested in accordance with BS 1377: PB4784-1001-MA-SP-0049 Rev. 12
2.2.1c
Part 2. Sampling every 12500 m3 Sec.3.9.
Particle Density (BS EN13383-2) >2.3 Mg/m3 when tested in PB4784-1001-MA-SP-0049 Rev. 12
2.2.1e
accordance with BS 1377: Part 2. Sampling every 20000 m 3 Sec.3.9.
Plasticity Index <6% when tested in accordance with BS 1377: Part PB4784-1001-MA-SP-0049 Rev. 12
2.2.1f
2. Sampling every 12500 m3 Sec.3.9.
Page 1 of 2
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Uniformity coefficient >3 when tested in accordance with BS 1377: PB4784-1001-MA-SP-0049 Rev. 12
2.2.2c
Part 2. Sampling every 12500 m3 Sec.3.9.
Water Absorption (BS EN13383-2) <6% when tested in accordance PB4784-1001-MA-SP-0049 Rev. 12
2.2.2d
with BS 1377: Part 2. Sampling every 20000 m3 Sec.3.9.
Particle Density (BS EN13383-2) >2.3 Mg/m 3 when tested in PB4784-1001-MA-SP-0049 Rev. 12
2.2.2e
accordance with BS 1377: Part 2. Sampling every 20000 m 3 Sec.3.9.
Plasticity Index <6% when tested in accordance with BS 1377: Part PB4784-1001-MA-SP-0049 Rev. 12
2.2.2f
2. Sampling every 12500 m3 Sec.3.9.
REFERENCE DOCUMENTS:
1- PB4784-1001-MA-SP-0049 Rev. 12, Technical Specification - Dredging and Reclamation Works
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 2 of 2
11083-QLT-CL-F001 Rev 0.0 26-SEP.-2017
SAIC NUMBER DATE APPROVED SHC-QR NUMBER
ARCHIRODON - HUTA Hegerfeld
Pre Reclamation CPT Test 100m X 100m (Excluding Tuxedo Area) SHIC-Q-EW-0005 03-Dec-17 Civil
PROJECT TITLE BI No. CONTRACTOR / SUBCONTRACTOR
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES
25-00053-0003 SARCO-HUTA Consortium
AND SERVICES
LOCATION
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
SH ITP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 3.0 (3.1)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
W H
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
At depth below top of formation level 0.60m the CPTu cone PB4784-1001-MA-SP-0049 Rev.
3.1d
resistance qc shall be ≥ 5 Mpa 12 Sec. 3.14.1 Table 3-3
From 6.50 to depth of CPTu refusal, the CPTu cone resistance q c PB4784-1001-MA-SP-0049 Rev.
3.1e
shall be 8 Mpa 12 Sec. 3.14.1 Table 3-3
REMARKS:
REFERENCE DOCUMENTS:
1- PB4784-1001-MA-SP-0049 Rev. 12, Technical Specification - Dredging and Reclamation Works
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 1 of 1
11083-QLT-CL-F001 Rev 0.0 26-SEP.-2017
SAIC NUMBER DATE APPROVED SHC-QR NUMBER
ARCHIRODON - HUTA Hegerfeld
Backfilling and Compaction Inspection SHIC-Q-EW-0006 03-Dec-17 Civil
PROJECT TITLE BI No. CONTRACTOR / SUBCONTRACTOR
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES
25-00053-0003 SARCO-HUTA Consortium
AND SERVICES
LOCATION
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
SH ITP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 3.0 (3.2)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
W/S W
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Demonstration with trials for effectiveness of the approved method PB4784-1001-MA-SP-0049 Rev.
3.2a
of compaction in grid not less than 50m x 50m in plan dimensions. 12 Sec. 3.14.5.2 and Sec. 3.17
REMARKS:
REFERENCE DOCUMENTS:
1- PB4784-1001-MA-SP-0049 Rev. 12, Technical Specification - Dredging and Reclamation Works
2- IFC Drawings
3- SHIC-Q-EW-0007 (Checklist)
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 1 of 1
11083-QLT-CL-F001 Rev 0.0 26-SEP.-2017
SAIC NUMBER DATE APPROVED SHC-QR NUMBER
ARCHIRODON - HUTA Hegerfeld
Post Reclamation CPT Test 30m X 30m
SHIC-Q-EW-0007 03-Dec-17 Civil
(Excluding Tuxedo Area)
PROJECT TITLE BI No. CONTRACTOR / SUBCONTRACTOR
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES
25-00053-0003 SARCO-HUTA Consortium
AND SERVICES
LOCATION
Reclamation Area
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
MYDO TIP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 3.0 (3.3)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
W H
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
CPTu’s shall be carried out on a 30m x 30m grid across the site
after placement of the Reclamation Fill and execution of the PB4784-1001-MA-SP-0049 Rev.
3.3a
Earthworks to form the Reclamation but prior to any ground 12 Sec. 3.12.2
improvement or placement of crushed rock fill.
For a depth below top of formation level 0.60m the minimum CPTu PB4784-1001-MA-SP-0049 Rev.
3.3c cone resistance value qc ≥ 5 Mpa 12 Sec. 3.14.1 Table 3-3
From 6.50 to depth of CPTu refusal, the CPTu cone reasistance PB4784-1001-MA-SP-0049 Rev.
3.3d value qc shall be not less thant 8 Mpa 12 Sec. 3.14.1 Table 3-3
REMARKS:
REFERENCE DOCUMENTS:
1- PB4784-1001-MA-SP-0049 Rev. 12, Technical Specification - Dredging and Reclamation Works
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 1 of 1
11083-QLT-CL-F001 Rev 1.0 3-Dec-17
SAIC NUMBER DATE APPROVED SHC-QR NUMBER
ARCHIRODON - HUTA Hegerfeld
Compaction Test SHIC-Q-EW-0008 03-Dec-17 Civil
PROJECT TITLE BI No. CONTRACTOR / SUBCONTRACTOR
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES
25-00053-0003 SARCO-HUTA Consortium
AND SERVICES
LOCATION
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
SH ITP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 3.0 (3.4)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
W H
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
REMARKS:
REFERENCE DOCUMENTS:
3- PB4784-1001-MA-SP-0049 Rev. 12 - Dredging and Reclamation Works
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 1 of 1
11083-QLT-CL-F001 Rev 0.0 26-SEP.-2017
SAIC NUMBER DATE APPROVED SHC-QR NUMBER
ARCHIRODON - HUTA Hegerfeld
Final Fill Inspection SHIC-Q-EW-0009 03-Dec-17 Civil
PROJECT TITLE BI No. CONTRACTOR / SUBCONTRACTOR
KING SALMAN INTERNATIONAL COMPLEX FOR MARITIME INDUSTRIES
25-00053-0003 SARCO-HUTA Consortium
AND SERVICES
LOCATION
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PB4784-1001-MA-DR-0036 7.0 6600040118 N/A
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME DOC. REF. NO.
11083-QLT-ITP-001
SH ITP NUMBER SEQUENCE NO. WORK PERMIT REQUIRED?
SAR-HTA-001 4.0 (4.1)
MYDP INSPECTION LEVEL SARCO-HUTA INSPECTION LEVEL NO
W H/R
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
The levels of the Final Surface of the reclamation shall be within a PB4784-1001-MA-SP-0049 Rev. 12
4.1a
tolerance of ± 25mm above the specified level in the AFC Drawing Sec. 3.19
REMARKS:
REFERENCE DOCUMENTS:
1- IFC Drawings
2- SHIC-Q-EW-0001 to 0008 Checklists
3- PB4784-1001-MA-SP-0049 Rev. 12 Technical Specification - Dredging and Reclamation Works
SARCO-HUTA Consortium MYDP
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test SHC=SARCO-HUTA Consortium, Y = YES N = NO F = FAILED
Page 1 of 1