Capacity, m3
S.No Facilities Available or m3/hr
1 SOBCTF-FWT-03 (tank) 800
2 SOBCTF-FWP-01 (pump) 162
3 SOBCTF-FWP-02 (pump) 162
4 SOBCTF-FWP-03 (Diesel pump) 425
5 SOBCTF-FWP-04 (Elec. pump) 425
6 SOBCTF-FW-JOCKEY-01 15
7 SOBCTF-FW-JOCKEY-01 15
Note
1 Fire water storage shall be considered for 4 hours minimum
2 Therefore, the total firewater considered for storage shall be 2300 m3. Another tank is required to meet this demand
3 The existing fire water pumps are enough to meet the total fire demand if they are run parallelly (425+162=587 m3/hr)
4 Jockey Pump Capacity required shall be from 29 to 57 m3/hr as it is selected as 5 to 10% of the total design flow rate required
5 The existing fire water jockey pumps has to be replaced or another pump shall be operated in parallel to meet the jockey pump capacity required
Zone-1 Well Head Manifold
Reference
1 OISD-117
2 Alternative III is not considered as it is specific to an equipment to provide extinguishment of fire through spray s
Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
Manifold
Spray/ Exposure
Exposure Protection Hose
Water Water Stream Total Fire Water
Demand Demand Protection Demand
LPM/m2 LPM/m2 LPM LPM m3/hr
360 360 22
2754 2754 165
2754 165
1 Process Facilities
Design Flow Rate
Reference
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Alternative II is not considered as none of the equipments meet 4.2.5 of OISD-116
3 Alternative III is not considered as it is specific to an equipment to provide extinguishment of fire through spray s
acilities
Spray/ Exposure
Exposure Protection Hose
Water Water Stream Total Fire Water
Demand Demand Protection Demand
LPM/m2 LPM/m2 LPM LPM m3/hr
5850 5850 351
5850 351
Reference
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Alternative I is area protection as per OISD-116
3 Alternative II is process facility protection as per OISD-116
4 Alternative III is equipment Protection as per OISD-117 & 116
II
Spray/ Exposure
Exposure Protection Hose
Water Water Stream Total Fire Water
Demand Demand Protection Demand
LPM/m2 LPM/m2 LPM LPM m3/hr
535.82 2400 2400 144
1176.47 2400 3576 215
1176.47 1176 71
1176.47 1176 71
lternative II 5929 356
2352.94 2353 141
2352.94 2353 141
2352.94 2353 141
lternative III 7059 424
7059 424
Zone-4 Tank Farm
Oil
Equipment Height/L Shell Surface
S.No. Description type Diameter ength Area area
m m x m2 y m2
400 KL SOBCTF- Fixed Roof
1 TANK-01 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
2 TANK-02 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
3 TANK-03 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
4 TANK-04 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
5 TANK-05 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
6 TANK-05 Tank 8.25 7.8 202.1 53.43
Notes
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Since all tanks are considered with 3 LPM/m2, there is no need for exposure protection of 1 LPM/m2
3
ne-4 Tank Farm
Spray/ Exposure
Exposure Protection Hose
Water Water Foam Water Stream Total Fire Water
Demand Demand Demand Protection Demand
x*3 LPM/m2 1 LPM/m2 0.97*y*5 LPM/m2 LPM LPM m2/hr
tection of 1 LPM/m2
Zone-5 Test Tanks
Oil
Equipment Height/L Shell Surface
S.No. Description type Diameter ength Area area
m m x m2 y m2
50 KL SOBCTF- Fixed Roof
1 TEST-TANK-01 Tank 3 5.3 49.93 7.07
50 KL SOBCTF- Fixed Roof
2 TEST-TANK-02 Tank 3 5.3 49.93 7.07
Notes
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Since all tanks are considered with 3 LPM/m2, there is no need for exposure protection of 1 LPM/m2
ne-5 Test Tanks
Spray/ Exposure
Exposure Protection Hose
Water Water Foam Water Stream Total Fire Water
Demand Demand Demand Protection Demand
x*3 LPM/m2 1 LPM/m2 0.97*y*5 LPM/m2 LPM LPM m2/hr
tection of 1 LPM/m2
Zone-6 GCP I
Reference
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Alternative I is area protection as per OISD-116
3 Alternative II is process facility protection as per OISD-116
4 Alternative III is equipment Protection as per OISD-117 & 116
I
Spray/ Exposure
Exposure Protection Hose
Water Water Stream Total Fire Water
Demand Demand Protection Demand
LPM/m2 LPM/m2 LPM LPM m3/hr
535.82 2400 2936 176
1176.468 2400 3576 215
1176.468 1176 71
1176.468 1176 71
Alternative II 4753 285
2352.936 2353 141
2352.936 2353 141
2352.936 2353 141
Alternative III 7059 424
7059 424