Zone No.

Description Design Flow Rate


LPM m3/hr
1 Wellhead Manifold 2754 165
2 Process Facilities 5850 351
3 GCP-II 7059 424
4 Tank Farm 7592 456
5 Test Tank 2768 166
6 GCP-I 7059 424

Design Flow Rate considering all 7592 456


zones

Capacity, m3
S.No Facilities Available or m3/hr
1 SOBCTF-FWT-03 (tank) 800
2 SOBCTF-FWP-01 (pump) 162
3 SOBCTF-FWP-02 (pump) 162
4 SOBCTF-FWP-03 (Diesel pump) 425
5 SOBCTF-FWP-04 (Elec. pump) 425
6 SOBCTF-FW-JOCKEY-01 15
7 SOBCTF-FW-JOCKEY-01 15

Note
1 Fire water storage shall be considered for 4 hours minimum
2 Therefore, the total firewater considered for storage shall be 2300 m3. Another tank is required to meet this demand
3 The existing fire water pumps are enough to meet the total fire demand if they are run parallelly (425+162=587 m3/hr)
4 Jockey Pump Capacity required shall be from 29 to 57 m3/hr as it is selected as 5 to 10% of the total design flow rate required
5 The existing fire water jockey pumps has to be replaced or another pump shall be operated in parallel to meet the jockey pump capacity required
Zone-1 Well Head Manifold

Equipment Total Area


S.No. Description type Method Length Breath Covered
m m m2
Alternative I 40 9 360
Alternative II 30 9 270
1 Well Head Manifold
Design Flow Rate

Reference
1 OISD-117
2 Alternative III is not considered as it is specific to an equipment to provide extinguishment of fire through spray s
Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
Manifold
Spray/ Exposure
Exposure Protection Hose
Water Water Stream Total Fire Water
Demand Demand Protection Demand
LPM/m2 LPM/m2 LPM LPM m3/hr
360 360 22
2754 2754 165

2754 165

ment of fire through spray system


Zone-2 Process Facilities

Equipment Total Area


S.No. Description type Method Length Breath Covered
m m m2
Alternative I 45 130 5850

1 Process Facilities
Design Flow Rate

Reference
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Alternative II is not considered as none of the equipments meet 4.2.5 of OISD-116
3 Alternative III is not considered as it is specific to an equipment to provide extinguishment of fire through spray s
acilities
Spray/ Exposure
Exposure Protection Hose
Water Water Stream Total Fire Water
Demand Demand Protection Demand
LPM/m2 LPM/m2 LPM LPM m3/hr
5850 5850 351

5850 351

ment of fire through spray system


Zone-3 GCP II

Equipment Total Area


S.No. Description type Method Length Breath Covered
m m m2
Alternative I 14.6 36.7 535.82
Alternative IIA 14.6 7.9 115.34
Alternative IIB 14.6 7.9 115.34
Alternative IIC 14.6 7.9 115.34
Alternative II
Alternative IIIA 14.6 7.9 115.34
Alternative IIIB 14.6 7.9 115.34
Alternative IIIC 14.6 7.9 115.34
1 GCP-II Alternative III
Design Rate

Reference
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Alternative I is area protection as per OISD-116
3 Alternative II is process facility protection as per OISD-116
4 Alternative III is equipment Protection as per OISD-117 & 116
II
Spray/ Exposure
Exposure Protection Hose
Water Water Stream Total Fire Water
Demand Demand Protection Demand
LPM/m2 LPM/m2 LPM LPM m3/hr
535.82 2400 2400 144
1176.47 2400 3576 215
1176.47 1176 71
1176.47 1176 71
lternative II 5929 356
2352.94 2353 141
2352.94 2353 141
2352.94 2353 141
lternative III 7059 424
7059 424
Zone-4 Tank Farm

Oil
Equipment Height/L Shell Surface
S.No. Description type Diameter ength Area area
m m x m2 y m2
400 KL SOBCTF- Fixed Roof
1 TANK-01 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
2 TANK-02 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
3 TANK-03 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
4 TANK-04 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
5 TANK-05 Tank 8.25 7.8 202.1 53.43
400 KL SOBCTF- Fixed Roof
6 TANK-05 Tank 8.25 7.8 202.1 53.43

Design Flow Rate

Notes
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Since all tanks are considered with 3 LPM/m2, there is no need for exposure protection of 1 LPM/m2
3
ne-4 Tank Farm
Spray/ Exposure
Exposure Protection Hose
Water Water Foam Water Stream Total Fire Water
Demand Demand Demand Protection Demand
x*3 LPM/m2 1 LPM/m2 0.97*y*5 LPM/m2 LPM LPM m2/hr

606.18 0.00 259.13 2400 3265 196

606.18 0.00 259.13 865 52

606.18 0.00 259.13 865 52

606.18 0.00 259.13 865 52

606.18 0.00 259.13 865 52

606.18 0.00 259.13 865 52

w Rate 7592 456

tection of 1 LPM/m2
Zone-5 Test Tanks

Oil
Equipment Height/L Shell Surface
S.No. Description type Diameter ength Area area
m m x m2 y m2
50 KL SOBCTF- Fixed Roof
1 TEST-TANK-01 Tank 3 5.3 49.93 7.07
50 KL SOBCTF- Fixed Roof
2 TEST-TANK-02 Tank 3 5.3 49.93 7.07

Design Flow Rate

Notes
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Since all tanks are considered with 3 LPM/m2, there is no need for exposure protection of 1 LPM/m2
ne-5 Test Tanks
Spray/ Exposure
Exposure Protection Hose
Water Water Foam Water Stream Total Fire Water
Demand Demand Demand Protection Demand
x*3 LPM/m2 1 LPM/m2 0.97*y*5 LPM/m2 LPM LPM m2/hr

149.78 0.00 34.27 2400 2584 155

149.78 0.00 34.27 184 11

w Rate 2768 166

tection of 1 LPM/m2
Zone-6 GCP I

Equipment Total Area


S.No. Description type Method Length Breath Covered
m m m2
Alternative I 14.6 36.7 535.82
Alternative IIA 14.6 7.9 115.34
Alternative IIB 14.6 7.9 115.34
Alternative IIB 14.6 7.9 115.34
Alternative II
Alternative IIIA 14.6 7.9 115.34
Alternative IIIB 14.6 7.9 115.34
Alternative IIIC 14.6 7.9 115.34
1 GCP-I Alternative III
Design Flow Rate

Reference
1 Supplementary Hose Flow considered per zone = 144 m3/hr as per OISD-117
2 Alternative I is area protection as per OISD-116
3 Alternative II is process facility protection as per OISD-116
4 Alternative III is equipment Protection as per OISD-117 & 116
I
Spray/ Exposure
Exposure Protection Hose
Water Water Stream Total Fire Water
Demand Demand Protection Demand
LPM/m2 LPM/m2 LPM LPM m3/hr
535.82 2400 2936 176
1176.468 2400 3576 215
1176.468 1176 71
1176.468 1176 71
Alternative II 4753 285
2352.936 2353 141
2352.936 2353 141
2352.936 2353 141
Alternative III 7059 424
7059 424