ANNEXURE - WATER DEMAND CALCULATIONS FOR HVW SPRAY SYSTEM AS PER TAC

THEORETICAL
TOTAL AREA (IN DESIGN DENSITY WATER
SR. NO. TRANSFORMER AREA WITHOUT BOTTOM SIDE SQ.M) LPM/SQ. MTR REQUIREMENT
IN LPM

L W H A = AREA (IN SQ.M) A


1 3.5 3.5 3 54.25 54.25 10.2 553.35
3 NO OF HV WATER SPRAY NOZZLES : 20
4 PRESSURE REQUIREMENT FOR SYSTEM (IN KG/CM 2) 3.5 TO 10.5
5 CALCULATION FOR SELECTING 'K' FACTOR & ALSO INDICATE THE FLOW THROUGH EACH NOZZLES
EACH NOZZLE FLOW THEORTICAL (IN LPM) = 27.6675
K FACTOR = NOZZLE FLOW = √(PRESSURE)
K FACTOR = 27.67 / 3.5
K FACTOR = 27.67 / 1.87082869338697
K FACTOR = 14.788900821224
6 MVWS NOZZLE SELECTED K-FACTOR = 18
7 MVWS NOZZLE SELECTED SPRAY ANGLE = 80 Deg
8 ACTUAL WATER PROVIDED AS PER HYDRAULIC CALCULATIONS IN LPM = K-FACTOR x √(3.5) X HVWS NOZZLE QTY
9 ACTUAL WATER PROVIDED REQUIRED FLOW IN LPM 673.498329619309
10 ACTUAL WATER PROVIDED REQUIRED FLOW IN M 3/HR 40.4098997771586

DELUGE VALVE SELECTION:


150NB (FLOW RATE 170 TO 650 M3/HR)
11 100NB (FLOW RATE 50 TO 225 M3/HR) 80NB (FLOW RATE 30 TO 110 M3/HR)
80NB (FLOW RATE 30 TO 110 M3/HR)
50NB (FLOW RATE 10 TO 55 M3/HR)
AS PER TAC STANDARD FIRE PUMP
= (FLOW RATE FOR TWO HYDRANT VALVES (1750 LPM) + ACTUAL WATER PROVIDED REQUIRED FLOW ) 2423.49832961931
TOTAL WATER DEMAND IN LPM 145.41
FIRE FIGHING PUMP SELECTED 171 M3/HR AT 70 MWC