TRANSMISSION MATERIALS STANDARD SPECIFICATION 01-TMSS-01, Rev.

03

Insulation Levels

Table 5 (Common Values)

69 110 115 132 230


11 13.8 33 34.5
G T O G T O G T O G T O G T O
BIL(kV * *
650/ 650/
peak) 110 110 200 200 325 350 350 550 650 650 550 650 650 650 1050 1050 1050
750 750
Power *
305/ *
Frequency 275/
275
Outdoors

withstand 50/ 50/ 95/ 95/ 140/ 160/ 160/ 230/ 305/ 275/ 230/ 305/ 275/ 275/ 275 460/ 505/ 460/
or
Voltage 45 45 80 80 140 140 140 230 275 275 230 275 275 275 or 325/ 460 460 460
355/
(Dry/Wet) 325
325
(kVrms)
Insulation Level

B B B
External

BSL (kVpeak) -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 750 750 750


* *
BIL(kV 550/ 550/
peak) 95 95 170 170 325 325 325 550 550 550 550 550 550 650 1050 950 950
650 650
Power
Frequency * *
Indoors

255/ 230/
Withstand 38 38 70 70 140 140 140 230 255 230 230 255 230 275 460 435 395
305 275
Voltage
(kVrms)
B B B
BSL (kVpeak) -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 750 650 650

BIL (kV peak) -- * * --


550/ 550/
Insulation Level

95 95 170 170 -- 325 325 -- 550 550 -- 550 550 950 950
650 650
Internal

Power
frequency * *
230/ 230/
withstand 38 38 70 70 -- 140 140 -- 230 230 -- 230 230 -- -- 435 395
275 275
voltage
(kV rms)
BSL (kVpeak)
-- -- -- -- -- -- -- -- 460 -- -- 460 -- -- 540 -- -- 750 --
* - Can be used in areas where the existing insulation level already proven for minimum 5 years subject to National Grid, Saudi Arabia review
and acceptance.

G - Values Applicable for GIS only.

T - Values Applicable for transformer bushing only(Indoor and outdoor).

O - Values applicable for Other Equipment

B - Values Applicable for GIS, transformer and other bushing

Table 6 (Across Isolating Distance)

System Nominal Voltage 69 110 115 132 230


11 13.8 33 34.5
(kVrms) G O G O G O G O G O
*
BIL(kV peak) 125 125 220 220 375 385 630 750 630 750 750 750/860 1200 1200
Outdoors

*
Power Frequency 315/315
55/ 55/ 105/ 105/ 160/ 176/ 265/
Insulation Level

withstand Voltage 315/315 265/265 315/315 315/315 or 530/530 530/530


50 50 88 88 160 154 265
(Dry/Wet) (kVrms) 375/375
External

*
BIL(kV peak) 110 110 195 195 375 375 630 630 630 630 750 630/750 1200 1050
Indoors

Power Frequency
*
withstand Voltage 45 45 80 80 160 160 265 265 265 265 315 265/315 530 460
(kVrms)

* - Can be used in areas where the existing insulation level already proven for minimum 5 years subject to National Grid, Saudi Arabia review and
acceptance.

G - Values Applicable for GIS only.

O - Values applicable for other equipment

01TMSS01R03/KSB Date of Approval: January 07, 2018 PAGE 11 OF 23