Professional Documents
Culture Documents
44.00
58.00
Dimensional 1.75
Quantity 9
Weight w/o Acc's (lb) 327 (14.00)
Performance
Requested Volume (CFM) 20,000
Actual Volume (CFM) 20,000
Total External SP (in. wg) 0.35
Fan RPM 524
Operating Power (hp) 5.32
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Drive Loss (%) 3.9
Tip Speed (ft/min) 5,800
Static Eff. (%) 22
Motor
Motor Mounted Yes
Size (hp) 5
Voltage/Cycle/Phase 460/60/3
Enclosure TEFC
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 7.6
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2014. Actual motor FLA may vary,
Sound Power by Octave Band for sizing thermal overload, consult factory.
Sound LwA - A weighted sound power level, based on ANSI S1.4
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA - A weighted sound pressure level, based on 11.5 dB
Data attenuation per Octave band at 5 ft - dBA levels are not
Inlet 88 94 87 79 74 72 68 61 84 72 23 licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
AMCA
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation
type A: Free inlet, Free outlet. Power rating (BHP/kW) includes transmission losses. Performance ratings include the
effects of birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free
field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels.
dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies to sone ratings only
PRODUCT DETAILS
Frame:
Frame Type:
2 in. x 0.063 in. Frame Thickness
Channel
Internal View
Blades: 0.063 in. Fixed Blade Thickness
Material: Aluminum
Sizing: Nominal
Shape: Rectangular
Construction: Mechanically Fastened
SUMMARY
Total Louver Qty: 54 Total Weight (lb): 1,604 Louver Area (ft2): 891
Total Ship Sect.: 54
**Weight shown is an estimate only based on the default base product configuration without options or accessories.
Larger openings may require field assembly of multiple louver panels to make up the overall opening size. Individual louver panels are designed to withstand windloads up to a maximum of 25
PSF (size and configuration dependent). Design, materials and installation of structural reinforcement required to adequately support large sections or multiple section assemblies within a large
opening are not provided by Greenheck. Options and accessories including, but not limited to, screens, filter racks, louver doors, and blankoff panels are not subject to structural analysis unless
indicated otherwise by Greenheck. Unless specifically indicated, the following are NOT included in the quote provided: structural steel, installation hardware (anchors, angle clips, continuous
angles, shims, fasteners, inserts, backer rod and sealant), field measuring and/or installation, miscellaneous flashing, trim or enclosures, blank off panels, mullion covers or mullion hardware,
hinged frames or removable subframes, custom bird/insect screen, 3-coat, metallic and/or exotic paint finishes, bituminous paints for unlike metals, any applicable taxes, stamped and sealed
structural calculations seismic calculations or job specific engineered submittal drawings.
The legal remedies described in this Limited Warranty are the sole exclusive remedy of Customer. This limited warranty will be void if payment from
Customer is not received within a commercially reasonable time frame. GREENHECK MAKES NO OTHER WARRANTY, EITHER EXPRESS OR
IMPLIED, REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH
BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This limited warranty is extended
solely to the Customer. It is nontransferable and non-assignable, and the Customer shall not permit or authorize its employees, agents, representatives
or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than the Customer.
In the event of material breach by the Customer of any of the conditions of this warranty, Greenheck shall have no liability for and product failure claims.
Failure to pay Greenheck in full for original services will automatically make this warranty null and void.
Greenheck will not be held liable for incidental or consequential damages of any kind. The limited warranty of product(s) replaced or repaired under this
limited warranty shall be limited to the remainder of the original warranty period. Greenheck reserves the right to reasonable field access to diagnose
and repair any product alleged to be defective. This limited warranty may not be modified by anyone and may not be changed by such things as
purchase order forms or acceptance forms, unless otherwise agreed upon by Greenheck.
This limited warranty is provided in lieu of any other warranty requirements or obligations, including, but not limited to, those within project specifications.
All notices and claims given under or pursuant to this agreement shall be in writing and sent by certified or registered mail, postage prepaid, return
receipt requested to: Greenheck, Attn: Louver Sales, 525 Western Road, Schofield, WI 54476.
By proceeding to use our products and services on your project, you accept the terms of these limited warranties.
AMCA
Greenheck Fan Corporation certifies that the louver shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and
water penetration ratings. The AMCA licensed performance data has been modified for installation, appurtenances,
accessories, etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to
aid in selection and applications of the air control device.
®
Downblast Centrifugal Roof Exhaust 1
Table of Contents Handling
Receiving, Unpacking, Handling . . . . . . . . . . . . . . 2-4
Belt and Direct Drive Units
Lift Direct Drive unit on to the roof utilizing hooks under
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
the lip of the shroud. Evenly space the hooks around
Inspection and Maintenance During Storage . . . . . .3 the shroud using a minimum of four lifting straps. Use
Removing from Storage . . . . . . . . . . . . . . . . . . . . . .3 a spreader bar to ensure the straps do not come in
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . .4 contact with the unit (see Figure 1).
Installation Typical Roof Mounting
and Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . .5
Figure 1
Pre-Starting Checks . . . . . . . . . . . . . . . . . . . . . . . 6-7
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . .8
Spreader
Tapered Bushing Hub Installation and Removal .8 Bar
Bushing Installation . . . . . . . . . . . . . . . . . . . . . . .9
Belt and Bearing Maintenance . . . . . . . . . . . . . . .9 Lifting
Strap
Bearing Lubrication Schedule . . . . . . . . . . . . . . .9
Fan Inlet Connections . . . . . . . . . . . . . . . . . . . . . . .10
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Mounting for Severe Duty . . . . . . . . . . . . . Backcover Hook Hook
Figure 2
Receiving Hook With
Upon receiving the product, check to ensure all Safety Latch
(Supplied by others)
items are accounted for by referencing the delivery
receipt or packing list. Inspect each crate or carton (2) Bearing Plate
for shipping damage before accepting delivery. Alert Lifting Points
the carrier of any damage detected. The customer will
make notification of damage (or shortage of items) on
the delivery receipt and all copies of the bill of lading
which is countersigned by the delivering carrier. If
damaged, immediately contact your representative. Any
physical damage to the unit after acceptance is not the (4) Drive Frame
Lifting Points
responsibility of the manufacturer.
Unpacking
Figure 3
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not Screws Screws
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
1¾ in.
(44 mm)
Curb Cap
®
Downblast Centrifugal Roof Exhaust 3
Dimensional Data
Disconnect Disconnect
Screws
Damper Damper
Recommended Duct Recommended Duct
1¼ in. and Damper Size 1¼ in. 1¼ in. and Damper Size 1¼ in.
(32 mm) (32 mm) (32 mm) (32 mm)
Recommended Roof Recommended Roof
Opening Opening
MOTOR MOTOR
Figure 4
Vari-Green Wiring
For Vari-Green wiring, refer to the Vari-Green Motor
and Controls Installation, Operation and Maintenance
Manual for complete wiring and operation instructions.
IMPORTANT
Installation, troubleshooting and parts replacement are
to be performed only by qualified personnel. Consult
and follow all applicable national, state and local
codes. They will supercede this document.
2. If unit is equipped with a backdraft damper, it
should be installed now.
3. Remove motor cover. Access to the motor
compartment is accomplished by removing the
screws as shown in Figure 3, page 2.
4. On belt drive fans, use the lifting lugs on the drive
frame or bearing plate to lift and place the unit on
top of roof curb. Refer to Figure 2, page 2.
5. On direct drive fans, lift and place the unit on top
of roof curb using hooks under the lip of the shroud.
Refer to Figure 1, page 2.
6. Secure fan to curb using a minimum of eight lag
screws, metal screws or the suitable fasteners.
Shims may be required depending upon curb
installation and roofing material.
7. Verify power line wiring is de-energized before
connecting fan motor to power source.
8. Connect power supply wiring to the motor as
indicated on the motor nameplate or terminal box
cover. Check the power source for compatibility
with the requirements of your equipment.
9. Check fan wheel for free rotation, recenter if
necessary. Check setscrew(s) for tightness.
10. Check all fasteners for tightness.
®
Downblast Centrifugal Roof Exhaust 5
Pre-Starting Checks WARNING
1. Check all fasteners and setscrews for tightness. Correct direction of wheel rotation is critical. Reversed
The wheel should rotate freely and be aligned as rotation will result in poor air performance, motor
shown in Figure 7. overloading and possible motor burnout.
AVERTISSEMENT
La turbine doit impérativement tourner dans le bon
Overlap Gap sens. Une rotation en sens inverse entraînerait de
mauvaises performances de soufflage, une surcharge
du moteur voire un grillage du moteur.
IMPORTANT
Figure 7
The fan has been checked for mechanical noises at
Model Type Overlap Gap the factory prior to shipment. If mechanical noise
Size
Direct Belt in. (mm) in. (mm) should develop, suggested corrective actions are
X — 060-095 — 3/32 (2) offered in the Troubleshooting section.
X — 097-163 1/4 (6) —
IMPORTANT
— X 071-161 1/4 (6) —
X — 183-243 3/8 (10) —
Over tightening belts will cause excessive bearing
wear and noise. Too little tension will cause slippage
— X 180-240 3/8 (10) —
at startup and uneven wear.
— X 260-540 1/2 (13) —
tachometer.
4. Check wheel rotation (viewing from the shaft side) by
momentarily energizing the unit. Rotation should be
clockwise as shown in Figure 8 and correspond to
rotation decal on the unit. Figure 10
If wheel rotation is incorrect,
reverse two of the wiring
leads or check motor wiring
for single phase. Fan RPM
should be checked and verified
with a tachometer.
Clockwise Rotation
Figure 8
®
Downblast Centrifugal Roof Exhaust 7
Maintenance Tapered Bushing Hub Installation
and Removal
DANGER For wheel hubs and shaft pulleys utilizing a tapered
Disconnect and secure to the “off” position all bushing interface, follow this procedure for installation
electrical power to the fan prior to inspection or and removal. There are two possible set ups for the
servicing. Failure to comply with this safety precaution tapered bushing, both have the same procedure, but
could result in serious injury or death. orientation of the hub varies.
DANGER Tapered Bushing Removal:
Pour écarter les risques de blessure grave ou de mort, 1. If present, loosen the setscrew holding the bushing
débrancher et verrouiller l’alimentation électrique en and shaft key in place.
position « Arrêt » avant tout contrôle ou entretien. 2. Loosen and remove the socket head cap screws
WARNING which fasten the bushing to the hub as shown in the
section views and examples of Figures 13-16.
This unit should be made non-functional when
cleaning the wheel or housing (fuses removed, Standard Mounting Reverse Mounting
disconnect locked off).
AVERTISSEMENT
L’appareil doit être rendu non opérationnel lors du
nettoyage de la turbine ou du caisson (fusibles retirés,
sectionneur verrouillé).
IMPORTANT
Uneven cleaning of the wheel will produce an out of
Figure 13 Figure 14
balance condition that will cause vibration in the fan.
Hub
Installation and maintenance are to be performed only Bushing
by qualified personnel who are familiar with local codes
Hub
and regulations and who are experienced with this type
of equipment.
Motor maintenance is generally limited to cleaning
and lubrication (where applicable). Cleaning should be Bushing
Washers
limited to exterior surfaces only. Removing dust buildup
Cap Screws
on motor housing ensures proper motor cooling. Washers
Cap Screws
Greasing of motors is only intended when fittings are
provided. Many fractional horsepower motors are
permanently lubricated and should not be lubricated
after installation. Motors supplied with grease fittings
should be greased in accordance with manufacturer’s
recommendations. Where motor temperatures do not
exceed 104ºF (40ºC), the grease should be replaced
after 2,000 hours of running time as a general rule.
Wheels require very little attention when moving clean
air. Occasionally, oil and dust may accumulate causing
imbalance. When this occurs, the wheel and housing
should be cleaned to ensure smooth and safe operation. Figure 15 Figure 16
Standard Bushing Orientation Reverse Bushing Orientation
All fasteners should be checked for tightness each
time maintenance checks are performed prior to
3. Standard Mounting: Take the two socket head cap
restarting unit.
screws that were removed and install them into the
A proper maintenance program will help these units visibly threaded holes on the wheel hub.
deliver years of dependable service. Reverse Mounting: Install the two socket head cap
screws into the visibly threaded holes of the bushing
flange.
4. Once both socket head cap screws are installed,
tighten them an eighth of a turn at a time, alternating
between the two until the hub comes loose from
the bushing.
®
Downblast Centrifugal Roof Exhaust 9
Fan Inlet Connections
In order to ensure proper fan performance, caution must be exercised in fan placement and connection to the
ventilation system. Obstructions, transitions, poorly designed elbows, improperly selected dampers, etc., can cause
reduced performance, excessive noise and increased mechanical stress. For performance to be as published, the
system must provide uniform and stable airflow into the fan.
Good
Poor Poor Good
Dampers must open fully. Avoid sharp turns or Provide uniform airflow at Provide uniform airflow at
Use motorized dampers in entrance conditions which fan inlet and through the fan inlet to ensure optimum
low airflow applications to cause uneven flow. Use damper to ensure optimum performance.
reduce losses. turning vanes in elbows to performance. Curb cap
reduce adverse effects. should be three wheel
diameters from the radius.
Use turning vanes in duct
when possible.
Parts List
Each fan bears a manufacturer’s nameplate with model
CAUTION
number and serial number embossed. This information
will assist the local representative and the factory in A fan manufactured with an explosion resistant motor
providing service and replacement parts. Before taking does not certify the entire unit to be explosion proof.
any corrective action, make certain unit is not capable Refer to UL Listing mark for the fans approved usage.
of operation during repairs. CAUTION
La présence d’un moteur antidéflagrant sur un
ventilateur ne garantit pas que tout l’appareil est
antidéflagrant. Pour connaître les emplois autorisés de
l’appareil, voir son marquage de conformité UL.
Belt
Shaft Pulley
Motor
Motor Pulley
Vibration Bearings
Isolators
Drive Frame Motor
Shroud Hood Clip Assembly
Vibration
Isolators Fan Shaft
Birdguard Shroud Brace
Shroud
®
Downblast Centrifugal Roof Exhaust 11
Mounting for Severe Duty Installations
Fan to Curb Mounting: 5/16-inch self-drilling fasteners Curb to Deck Mounting: Fasteners need to be located
are to be installed on each side of fan with one fastener on all four sides of the curb.
4 inches from each edge and one fastener in the center. Roof Curb Roof Curb
Fasteners are to be equally spaced. 3/8 in. (10 mm) S.S. Hilti Kwik Bolt
Three Expansion Anchors 1/4 in. - 14 Self-Drilling Screw
Min. 2-1/2 in. (64 mm) Engagement Min. 1/2 in. (13 mm) of Threads Through
Fasteners
Fan Size
Per Side
Roof Truss
≤ 163 3 1/8 in. (3 mm) Thick
or 12 ga. Min.
180 to 240 5 2500 Min. PSI
Concrete
≥ 260 9
Concrete Steel
Deck Anchoring Deck Anchoring
1¼ in.
(32 mm)
Roof Curb
1¼ in. 3/8 in. (10 mm) Lag Bolt (Zinc Plated)
(32 mm)
Min. 3 in. (76 mm) Thread Engagement
Curb Corner
Anchor Detail
Wood Timber
Min. 4 in. (102 mm)
Roof Curb Nominal Thickness
Model GPF, GPFHL, GPFHD or Equivalent Min. G = 0.42
18 ga. min. G: Specific Gravity
High wind ratings – 42 in. Tall Max of Lumber
Seismic ratings – 24 in. Tall Max
Steel Welded Construction
Timber Anchoring
Seismic
High Wind Ratings NOTE: Installation instructions for seismic
Ratings
Fasteners Fasteners ratings are only recommendations.
Fan Size Curb Cap Size Self-Drilling Per Total Fan Size Per Total Final design must be determined by
Screw Size Side Side Structural Engineer of Record (SEOR) including
17x17 to 22x22 requirements for curb construction, mounting
≤ 141 3 12 060-300 2 8
Concrete
1/4” - 14
26x26 to 40x40
> 141 4 16 330-540 3 12
(660x660 to 1016x1016 mm)
17x17 to 22x22
≤ 141 3 12 060-300 2 8
(432x432 to 559x559 mm)
Timber
3/8”
26x26 to 40x40
> 141 4 16 330-540 3 12
(660x660 to 1016x1016 mm)
All dimensions are in inches (millimeters).
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck Centrifugal Roof Downblast Exhaust Fans catalog AMCA Publication 410-96, Safety Practices for Users and
provides additional information describing the equipment, fan Installers of Industrial and Commercial Fans, provides
performance, available accessories, and specification data. additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
12 471558 • G and GB, Rev. 7, March 2018 Copyright 2018 © Greenheck Fan Corporation
ESJ-202
Stationary Louver
J Blade
Application and Design
ESJ-202 is a weather louver designed to protect air intake and
exhaust openings in building exterior walls. Design incorporates J style
blades, sloped sill and high free area to provide maximum resistance
to rain and weather while providing minimum resistance to airflow.
The ESJ-202 is an extremely efficient louver with AMCA LICENSED
PERFORMANCE DATA enabling designers to select and apply with
confidence.
Standard Construction
Frame ���������������Heavy gauge extruded 6063-T5 aluminum,
2 in. x 0.063 in. nominal wall thickness
Blades ���������������J style, heavy gauge extruded 6063-T5 aluminum,
0.063 in. nominal wall thickness, positioned at 45º
angles on approximately 3 in. centers
Construction �����Mechanically fastened
Birdscreen ���������3/4 in. x 0.051 in. flattened expanded aluminum in
removable frame, inside mount (rear)
Finish �����������������Mill
Minimum Size ���6 in. W x 6 in. H
Maximum Single
Section Size ������120 in. W or 120 in. H. (limited to 70 ft. sq.)
102 0.95 2.72 4.48 6.24 8.00 9.77 11.53 13.29 15.05 16.82 18.58 20.34 22.10 23.87 25.63 27.39 29.15 30.92 32.68 34.44
108 0.98 2.79 4.59 6.40 8.21 10.01 11.82 13.63 15.43 17.24 19.05 20.85 22.66 24.47 26.28 28.08 29.89 31.70 33.50 35.31
114 1.07 3.03 5.00 6.96 8.93 10.90 12.86 14.83 16.80 18.76 20.73 22.70 24.66 26.63 28.60 30.56 32.53 34.50 36.46 38.43
120 1.11 3.16 5.20 7.25 9.30 11.35 13.39 15.44 17.49 19.54 21.58 23.63 25.68 27.73 29.77 31.82 33.87 35.92 37.96 40.01
Airflow Resistance (Standard Air - .075 lb/ft3) Water Penetration (Standard Air - .075 lb/ft3)
Pa in. wg Test size 48 in. x 48 in. Test duration of 15 min.
1 ml/m2 oz/ft2
0.9
200 0.8 Test Size 48 in. x 48 in. 0.30
3
0.7 Standard Air - .075 lb/ft Test Size 48 in. x 48 in.
0.6 Test Period 15 minutes
0.5 80 0.25 Standard Air - .075 lb/ft
3
100 0.4
Water Penetration per Unit Free Area
90
80
0.3 0.20
70 60
60
Static Pressure Drop
50 0.2
0.15
40
40
30
0.10
0.1
0.09
t
aus
20 0.08 20
Exh
ke
0.07 0.05
Inta
0.06
0.05
10
0 0.00
0.04
9 ft/min: 600 650 700 750 800 850 900
8
0.03
7 m/s: 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5
6
Free Area Velocity
5 0.02
ft/min 200 300 400 500 600 700 800 900 1000 2000 3000 The AMCA Water Penetration Test provides a method for comparing
various louver models and designs as to their efficiency in resisting
m/s 2 3 4 5 6 7 8 9 10
the penetration of rainfall under specific laboratory test conditions. The
Free Air Velocity beginning point of water penetration is defined as that velocity where the
water penetration curve projects through .01 oz. of water (penetration)
Model ESJ-202 resistance to airflow (pressure drop) varies per sq. ft. of louver free area. *The beginning point of water
depending on louver application (air intake or air exhaust). penetration for Model ESJ-202 is 668 fpm free area velocity.
Free area velocities (shown) are higher than average These performance ratings do not guarantee a louver to be weatherproof
velocity through the overall louver size. See louver selection or stormproof and should be used in combination with other factors
information. including good engineering judgement in selecting louvers.
PRODUCT DETAILS ESJ-202
Stationary Louver J Blade
Maximum Size and Installation Information Extruded Aluminum
Maximum single section size for model ESJ-202 is 120 in. W x 84 in. H or 84 in. W x 120 in. H (70 sq. ft). Larger openings require
field assembly of multiple louver sections to make up the overall opening size. Individual louver sections are designed to withstand
a 25 PSF wind load (please consult Greenheck if the louvers must withstand higher wind-loads). Structural reinforcing members
may be required to adequately support and install multiple louver sections within a large opening. Structural reinforcing members
along with any associated installation hardware is not provided by Greenheck unless indicated otherwise by Greenheck. Options
and accessories including, but not limited to, screens, filter racks, louver doors, and blank off panels are not subject to structural
analysis unless indicated otherwise by Greenheck. Additional information on louver installation may be found in AMCA Publication
#501, Louver Application Manual.
FINISHES
Standard Warranty
Finish Type Description/Application Color Selection
(Aluminum)
Standard Colors: Any of the 24
“Best.” The premier finish for extruded aluminum. Tough, 10 Years
2-coat 70% KYNAR 500®/HYLAR 5000® AAMA 2605 – standard colors shown can be
long-lasting coating has superior color retention and (Consult Greenheck for
Dry film thickness 1.2 mil. (AKA: Duranar®, Fluoropon®, furnished in 70% or 50% KYNAR
abrasive properties. Resists chalking, fading, chemical availability of extended
Trinar®, Flouropolymer, Polyvinylidene Fluoride, PVDF2) 500®/HYLAR 5000® or Baked Enamel.
abrasion and weathering. warranty)
2-Coat Mica:
“Better.” Tough, long-lasting coating has excellent color Greenheck offers 9 standard 2-
2-coat 50% KYNAR 500®/HYLAR 5000® AAMA 2604
retention and abrasive properties. Resists chalking, fading, coat Mica colors. Other colors are 5 Years
– Dry film thickness 1.2 mil. (AKA: Acroflur®, Acrynar®)
chemical abrasion and weathering. available. Consult Greenheck for
possible extra cost when selecting
Baked Enamel AAMA 2603 – Dry film thickness 0.8 mil. “Good.” Provides good adhesion and resistance to non-standard colors or special
1 Year
(AKA: Acrabond Plus®, Duracron®) weathering, corrosion and chemical stain. finishes.
“Two-step” anodizing is produced by following the normal Light, Medium or Dark Bronze;
Integral Color Anodize AA-M10C22A42 (>0.7 mil) 5 years
anodizing step with a second, colorfast process. Champagne; Black
Greenheck offers a number of industrial coatings such as Hi-Pro Polyester, Epoxy, and Permatector®.
Industrial coatings Consult Greenheck
Consult a Greenheck Product Specialist for complete color and application information.
Materials may be supplied in natural aluminum or galvanized steel finish when normal weathering is
Mill n/a
acceptable and there is no concern for color or color change.
Finishes meet or exceed AAMA 2605, AAMA 2604, and AAMA 2603 requirements. Please consult www.greenheck.com for complete information on standard and
extended paint warranties. Paint finish warranties are not applicable to steel products.
ESJ-202
September 2018
Copyright © 2018 Greenheck Fan Corporation