Perhitungan Balok Baja Luffing Crane
Loading Analysis
*Collar load = 2.1 ton each = 20.6 kN
I) In Service
Slew torque and horizontal force happened
Safety factor =2
Slew Torque (MD) = 200 kN × 2 = 400 kN
T = MD / b = 400 kNm / 3.06 m = 131 kN
2 section = T/2 = 131 kN / 2 = 65.5 kN
Horizontal force (R1) = 248 kN × 2 = 496 kN
R1 = 496 kN / 4 = 124 Kn
5
III) Jacking Condition
Only Axial force happened
Safety factor =2
Axial force (P) = 700 kN ×2 = 1400 kN
= 1400 kN /4 = 350 kN
H Beam Analysis
H Beam
Use H beam : 250 × 250 × 9 × 14
Weight = 36.2 kg/m’
Web depth = 250 mm
Flange width = 250 mm
Web thck. = 9 mm
Flange thck. = 14 mm
Sec. Area = 46.09 cm2
Inertia, Ix = 412 cm4
Inertia, Iy = 1,820 cm4
Gyration, ix = 2.99 cm
Gyration, iy = 6.29 cm
Wx = 39.5 cm3
Wy = 146 cm3
Steel quality (BJ41)
fu = 4900 kg/cm2
fy = 2800 kg/cm2
Collar in service
Slew Torque (MD) = 200 kN × 2 = 400 kN
T = MD / b = 400 kNm / 3.06 m = 131 kN
2 section = T/2 = 131 kN / 2 = 65.5 kN
Horizontal force (R1) = 248 kN × 2 = 496 kN
R1 = 496 kN / 4 = 124 kN
6
Gambar 5. Diagram Kombinasi Beban
Reaksi (terbesar)
VZ = 19.58 kN
HX = 505.59 kN
HY = 374.585 kN
7
Gambar 7. Moment X-Y direction dan Moment Z direction Diagram
8
Gambar 8. Steel Beam ratio
Gambar di atas menunjukkan rasio Balok Baja, jika rasio lebih dari 1, itu berarti Steel Beam tidak
cukup kuat untuk menahan semua beban, dari diagram diatas Rasio terbesar yang berwarna hijau
dengan rasio 0,7 oleh karena itu HB 250x250x9x14 aman untuk menahan semua beban
9
Main H beam Control
( SNI 03-1729-2002, Number 7.6.4 Table 7.5-1 )
bf 250
Flange : = = 8.92
2tf 2∗14
250 250
λR = = = 16.14
√fy √250
bf
< λR
2tf
h 250
Web : = = 27.78
tw 9
665 665
λR = = = 42.93
√fy √240
h
> λR , then Mmax = W × fy
tw
10
Kontrol Lendutan
A B
C D
11
Angkur menggunakan HTB M20, dengan sepesifikasi:
Steel quality: fu = 4100 kg/cm2
fy = 2500 kg/cm2
Bolt sectional area = ¼ × π × D2
= ¼ × π × 2.02
= 3.14 cm2
Jumlah Angkur:
u =√𝑉𝑧 2 + 𝐻𝑦 2
= √19.582 + 374.592
= 375.10 kN
Jumlah Angkur = u / max
= 375.10 kN / 126.13 kN = 2.97 buah
Minimum mengunakan 4 buah angkur
12
Geser Pons / Kontrol kekuatan Beton
Gambar 11. Area beton untuk menahan beban geser (lihat baut PERI)
u = 1.3 × (fc)1/2
= 1.3 × (38.5)1/2
= 8.067 kg/cm2
max = u / (2(a+b+2ht)ht)
= 38,236.49 kg / (2(12+12+2×40)40) cm2
= 4.595 kg/cm2
Control : u > max
8.067 kg/cm2 > 4.595 kg/cm2 ( OK )
13
Sambungan Balok Baja dan braket
14
Jumlah Baut Diameter 12 mm
u =√𝐻𝑥 2 + 𝐻𝑦 2
= √19.582 + 374.592
= 375.10 kN
Jumlah Baut = u / Vd
= 38,236.49 kg / 4,829 kg = 7.91 buah
Minimum menggunakan baut 8 buah .
15