P891

MiCOM Trip/Close Module

Technical Data Sheet


P891/EN TDS/A11
P R OT E C T I O N

MiCOM P891
Circuit Breaker
Trip / Close Module

P891 is suitable for application with protection relays where


relay independent tripping and closing functionality is
desired.

Independent circuit breaker indication is provided by two


LEDS allowing for direct wiring of the circuit breaker's 52A
and 52B contacts. With the wide voltage supply range
capability, integration into any battery supply system is
simple.

Configure the module to integrate with feeder management


relay functions such as autoreclosing and check
synchronizing and provide a secure CB control solution.

Pushbutton covers are provided to prevent inadvertent


operation of pushbutton switches. This safety feature allows
the module to be used under the most stringent operating
procedures. These covers can also be removed if not
required.

Customer Benefits
• Control to suit
customers' operational
procedures.
• Simple and robust
design
• Clear status indication

AREVA T&D
APPLICATION HARDWARE DESCRIPTION

The MiCOM P891 Trip/Close module can be applied to The module is housed in a 10TE Midos Case, suitable
directly control a circuit breaker or other plant such as for either rack or panel mounting. Pushbuttons can be
motorised line isolator switches requiring fitted with color coded push button covers and these
open(trip)/close control. can be locked by the user by means of a padlock or
other suitable locking device.
> Typical Application
> Features
The application shows the P891 combined with the
P14x and P991 to provide a complete feeder scheme • Close and Trip pushbuttons
solution. The P891 provides relay independent tripping • Red and Green LED indication for device open
and closing functionality. This functionality can also be and close indication
integrated with the protection relay to make use of relay • Universal power supply for LED indication circuit
functions such as check synchronising or
• Two N/O output contacts per pushbutton
autoreclosing.
• Removable Pushbutton covers(optional)
• ANSI Labelling

Fig.1 Typical scheme application

+ Close + Trip
52A 52B
T P991 P14x P891

2 1 2
Va
Close – – Trip 2 3 4
Vb
2 5 6
Vc Close PB
2 7 8
1 9 10 Trip
Input
1 11 12 CB Closed
+ Trip
8 13 14 A
9 15 16
8 17 18 B
Trip PB
9 19 20
8 21 22 C
9 23 24
Input
8 25 26 N CB Open
9
27 28

29 30 SEF

31 32
Shorting
Bars

Use MICOM P891


for secure control
of circuit breakers.
2
OUTPUT CONTACTS PRODUCT USE

> Standard Contacts The P891 output contacts are designed to be wired
directly into control circuits. However care should be
taken so that the Pushbutton output contact break
General purpose output contacts for signalling, tripping
capacity is not exceeded. In the case of circuit breaker
and alarming.
applications, the breaker's auxiliary contacts are used
to interrupt the trip/close circuit current once the
> Contact Ratings
breaker is operated.
• Make & Carry 3Amps for 3s
• Carry 250 A dc for 30ms
10 A continuous INSTALLATION
• Break DC: 50W resistive
DC: 62.5W inductive The generic safety guide SFTY/4L M/B11 should be
(L/R = 50ms) read before installing or using the P891 Trip/Close
AC: 2500VA Module.
AC: 2500VA inductive
(P.F. = 0.7)
EMC COMPLIANCE
• Maxima 10A and 300V
Compliance with the
• Loaded contact 10,000 operations minimum
89/336/EEC European Commission
• Unloaded contact 100,000 operations minimum
Directive on EMC

PRODUCT SAFETY Compliance with the


LED INPUTS
European Commission
73/23/EEC Low voltage directive
> Voltage Ratings

• DC operative range 19-300V dc P891 THIRD PARTY COMPLIANCES


• AC operative range 24-265V rms, 50/60Hz
File Number : E202519
C UL
fi US Original Issue Date : 18-01-2005
(Complies with Canadian and
US requirements)

Figure2 P891 connection detail and rear terminal block detail

CASE EARTH
2

RED LED
4
AC or DC
VX Aux Supply
4

VAUX 6
RED LED
6

RED 1
8
8

RED RED 1
10
10

PUSHBUTTON

RED 2 12
12

RED 2
14
14
16

VAUX GREEN LED


16
GREEN LED AC or DC
18

VX Aux Supply
18
GREEN 1
20
22

20

GREEN 2 GREEN 1
24

22
GREEN
PUSHBUTTON
24
26

GREEN 2
26
28

MiCOM P891

Compact case size, for easy mounting alongside


MIDOS and MiCOM protection relays
TECHNICAL DATA Creepage Distances and Clearances
Per EN 61010-1: 2001
Pollution degree 2,
Mechanical Specification Overvoltage category III,
Impulse test voltage 5 kV.
Design
Modular MiCOM relay, P891 (10TE) case High Voltage (Dielectric) Withstand
Mounting is front of panel flush mounting. (i) Per IEC 60255-5: 2000, 2 kV rms
AC, 1 minute
Between all case terminals connected together,
Enclosure Protection and the case earth.
Per IEC 60529: 1989 Also, between all terminals of independent
IP 52 Protection (front panel) against dust and circuits.
dripping water, 1kV rms AC for 1 minute, across open contacts
IP 30 Protection for sides of the case, of changeover output relays.
IP 10 Protection for the rear. (ii) Per ANSI/IEEE C37.90-1989 (reaffirmed
1994):
Weight 1.5 kV rms AC for 1 minute, across open
Case 10TE: approx. 1.5kg contacts.

Impulse Voltage Withstand Test


Terminals Per IEC 60255-5: 2000
Front time: 1.2 µs, Time to half-value: 50 µs,
General Input/Output Terminals Peak value: 5 kV, 0.5J
For LED inputs and output contacts. Between all terminals, and all terminals and
Located on general purpose (black) blocks: case earth.
Threaded M4 terminals, for ring lug connection.
Electromagnetic Compatibility (EMC)
Case Protective Earth Connection
A single rear screw connections, threaded M4.
Must be earthed (grounded) for safety, minimum 1 MHz Burst High Frequency Disturbance Test
earth wire size 2.5mm2. Per IEC 60255-22-1: 1988, Class III,
Common-mode test voltage: 2.5 kV,
Differential test voltage: 1.0 kV,
Environmental Conditions
Test duration: 2 s, Source impedance: 200 Ω.
Ambient Temperature Range
Per IEC 60255-6: 1988 Immunity to Electrostatic Discharge
Operating temperature range: Per IEC 60255-22-2: 1996, Class 4,
-25°C to +55°C (or -13°F to +131°F). 15kV discharge in air to user interface, display,
Storage and transit: and exposed metalwork.
-25°C to +70°C (or -13°F to +158°F). Per IEC 60255-22-2: 1996, Class 4,
8kV point contact discharge to any part of the
front of the product.
Ambient Humidity Range
Per IEC 60068-2-3: 1969:
56 days at 93% relative humidity and +40 °C Electrical Fast Transient or Burst
Per IEC 60068-2-30: 1980: Requirements
Damp heat cyclic, six (12 + 12) hour cycles, Per IEC 60255-22-4: 2002. Test severity Class III
93% RH, +25 to +55 °C and IV:
Amplitude: 2 kV, burst frequency 5kHz (Class III),
Amplitude: 4 kV, burst frequency 2.5kHz (Class
Type Tests IV).
Applied directly to all inputs.
Insulation
Per IEC 60255-5: 2000,
Insulation resistance > 100MΩ at 500Vdc
(Using only electronic/brushless insulation tester).

P891 Technical Data Sheet 4


Surge Immunity Test Radiated Emissions
Per IEC 61000-4-5: 1995, Level 4, Per EN 55022: 1998:
Time to half-value: 1.2 / 50 µs, 30 - 230MHz, 40dBμV/m at 10m measurement
Amplitude: 4kV between all groups and case distance
earth, 230 - 1GHz, 47dBμV/m at 10m measurement
Amplitude: 2kV between terminals of each distance.
group.
Surge Withstand Capability
Immunity to Radiated Electromagnetic Energy Per ANSI/IEEE C37.90.1: 2002,
Per IEC 60255-22-3: 2000, Class III: Oscillatory SWC 2.5kV,
Test field strength, frequency band 80 to 1000 Fast Transient SWC 4kV.
MHz:
10 V/m,
Oscillatory Wave Immunity
Test using AM: 1 kHz / 80%,
Per EN61000-4-12: 1995, Level 3:
Spot tests at 80, 160, 450, 900 MHz
Amplitude: 4kV between independent circuits
Per IEEE/ANSI C37.90.2: 1995:
and case earth,
25MHz to 1000MHz, zero and 100% square wave
Amplitude: 1kV across terminals of the same
modulated.
circuits.
Field strength of 35V/m.

Radiated Immunity from Digital EU Directives


Communications
Per EN61000-4-3: 2002, Level 4: EMC Compliance
Test field strength, frequency band 800 to 960 Per 89/336/EEC:
MHz, and 1.4 to 2.0 GHz: Compliance to the European Commission
30 V/m, Directive on EMC is claimed via the Self
Test using AM: 1 kHz / 80%. Certification route. Product Specific Standards
were used to establish conformity:
Radiated Immunity from Digital Radio EN50263: 2000
Telephones
Per ENV 50204: 1995 Product Safety
10 V/m, 900MHz and 1.89GHz. Per 73/23/EEC:
Compliance with European Commission Low
Immunity to Conducted Disturbances Induced Voltage Directive. Compliance is demonstrated
by Radio Frequency Fields by reference to generic safety standards:
Per IEC 61000-4-6: 1996, Level 3, EN61010-1: 2001
EN60950-1: 2002
Disturbing test voltage: 10 V
Mechanical Robustness
Power Frequency Magnetic Field Immunity
Per IEC 61000-4-8: 1994, Level 5,
Vibration Test
100A/m applied continuously,
Per IEC 60255-21-1: 1996
1000A/m applied for 3s.
Response Class 2
Per IEC 61000-4-9: 1993, Level 5,
Endurance Class 2
1000A/m applied in all planes.
Per IEC 61000-4-10: 1993, Level 5,
100A/m applied in all planes at 100kHz/1MHz Shock and Bump
with a burst duration of 2s. Per IEC 60255-21-2: 1995
Shock response Class 2
Shock withstand Class 1
Conducted Emissions
Bump Class 1
Per EN 55022: 1998:
0.15 - 0.5MHz, 79dBμV (quasi peak) 66dBμV
(average) Seismic Test
0.5 - 30MHz, 73dBμV (quasi peak) 60dBμV Per IEC 60255-21-3: 1995
(average). class 2

P891 Technical Data Sheet 5


Ordering Information
Type Trip/Close Module P891

Push Button Guard Option


With Push Button Guard 01
Without Push Button Guard 02
Hardware Suffix
Original A

Case Dimensions

P891 Technical Data Sheet 6


Connection Diagram

A
CASE
EARTH B

RED LED 4
RED INDICATION
6 19V - 300V AC / DC
SWITCH GEAR

8 52 52
TC CC
RED 1
10
TRIP +
RED
PUSHBUTTON 12
RED 2 FOR REMOTE INDICATION (i.e. P145)
14 TRIP - CLOSE -

GREEN LED 16
GREEN INDICATION
18 19V - 300V AC / DC

20
GREEN 1
22
CLOSE +
GREEN
PUSHBUTTON 24
GREEN 2 FOR REMOTE INDICATION (i.e. P145)
26

PUSHBUTTON NORMALLY
MiCOM P891 OPEN CONTACT (REF)

P891 Technical Data Sheet 7


DEVICE TRACK RECORD-SWITCH MODULES
>> MMLZ - Auxiliary modules used in multiple hardwired scheme
applications since 1989.
>> Complements MIDOS and MiCOM relays, plus MMLG and
P99x test blocks.

MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-P891-BR-03.05-0847-GB - © - AREVA - 2005. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.

AREVA T&D Worldwide Contact Centre: Our policy is one of continuous development. Accordingly the
http://www.areva-td.com/contactcentre/ design of our products may change at any time. Whilst every
effort is made to produce up to date literature, this brochure
Tel.: +44 (0) 1785 250 070 should only be regarded as a guide and is intended for
information purposes only. Its contents do not constitute an offer
for sale or advise on the application of any product referred to in
www.areva-td.com it. We cannot be held responsible for any reliance on any
decisions taken on its contents without specific advice.
www.areva-td.com/protectionrelays