The foundation of TAMCO is built around innovation, technology, intelligence and flexibility, combined with the highest quality.
TAMCO products satisfies all the latest international standards. Your power needs are satisfied by our promise to optimum
results, enhanced safety, greater reliability, operating cost efficiencies, effective use of capital, and superior performance.
DESIGN – General Arrangement & Interlocks
1 LV Door
2 Circuit Breaker & Disconnector Door
3 Cable Door
4 LV Compartment
VCB & Disconnector Mechanism
1 4 5
6 Compartment
13
6 Bare busbar in SF6 gas/Plugin busbar
7
7 Busbar compartment in SF6 gas
VCB & Disconnector Compartment in SF6
8
tank
9 Current Transformer
10 Touch-proof Cable
2 5 14
11 Cable Compartment
12 Earthing Bar
13 Arc Duct
15
8 14 Voltage Transformer (VT)
15 VT Isolating switch
SF6 gas
9
10
1 4 3
12
11
GV series is designed to maximize safety in installation, operation and maintenance. It complies with the latest
IEC standards and fitted with all mandatory interlocks as recommended by the international standards.
• Disconnector can be operated only when VCB is in • Key can’t be removed in any position other than
“OFF” condition. when cables have been connected to “EARTH”.
• VCB can’t be operated, either mechanically or • Allows operation of Disconnector from “EARTH”
electrically, when Disconnector is accessed. to “OFF” only when key is trapped.
PERMISSIVE INTERLOCK*
CABLE ACCESS*
• Allows the operation of Disconnector to “EARTH”
only when key is trapped. • The opening of cable access cover is not possible
unless the cable have been connected to “EARTH”.
• The key can’t be removed when Disconnector is in
“EARTH” position. • Disconnector operation is not possible if the cable
access cover is “OPEN”
POINT OF ISOLATION*
2
4
Busbar connection plugged in at Inter-panel busbar connection with
1 one end plugin bushing
3
1
2
GENERAL GV1N GV3N
Rated voltage kV 12/15 36
Rated short time withstand current kA 25 31.5
Rated normal current A 800 1250 2000/2500* 800 1250 2000 2500
Rated frequency Hz 50/60
Rated duration of short time current sec 3
Rated short circuit making current kA 65 82
Rated symmetrical short time breaking current kA 25 31.5
kV-peak 95 170
Rated insulation level
kV-rms 38 70
Internal Arc kA/1sec 25 31.5
Insulation medium Sulphur Hexafluoride (SF6)
Rated gas pressure 0.135 MPa absolute
Alarm gas pressure 0.120 MPa absolute
*For 2500A GV3N shall be offered in combination with GV1N
DISCONNECTOR
Rated voltage kV 12/15 36
Rated short circuit current kA 25 31.5
Operation Manual / Motorised*
*Motorised option available on request
DESIGN CHARACTERISTIC
Width mm 500 800/900** 600 800 900
Depth* mm 1800 2165
Height* mm 2500 2450
Loss of service continuity LSC2B
Internal arc classification AFLR
Partition class PM
Ingress protection class IP65 (for tank) / IP4X (for cubicle)
Classification E2 C2 M2
*Depth & height may vary depending on the configurations/customer requirements
** 2500A GV3N in 900mm width
The information contained herein is correct at the time of printing, but as TAMCO’s products and manufacturing processes undergo continuous development, this information is subject
to change without notice. and the company cannot be held liable for any alleged misinterpretation howsoever arising.