Pump Performance:According to ISO9906-2012,Grade 2B

Pump Performance Datasheet


Customer Quote number
Customer Reference Pump size LS200-150-508B
Item number Stages 1
Service Based on curve number 1
Quantity of pumps Data last saved 2019-8-20
Operating Conditions Liquid
Flow 110 l/s Liquid type Water
Head(requested) 60 m Additional liquid description
Head(actual) 60 m Solids diameter,max 0 mm
Suction pressure,rated/max Temperature 20 C
NPSH available,rated Ample m Fluid density,rated/max 1000.00 kg/m3
Frequency 50 HZ Viscosity,rated 1.0 cst
Performance Material
Pump speed,rated 1485 rpm Casing Material CI
Impeller diameter,rated 407.8 mm Impeller Material SS
Impeller diameter,maximum 508.0 mm Pressure Data
Impeller diameter,minimum 355.6 mm Flange Rating PN16
Efficiency 81.03 % Maximum working pressure 0.64 MPa
NPSH 3.6 m Maximum allowable working requested 1.60 MPa
- - Maximum allowable suction pressure limit 0.96 MPa
MCSF 58.85 l/s Casing hydrostatic test pressure 2.40 MPa
Head Maximum,rated diameter 65.3 m
Driver&Power Data
Head rise to shut off 93.87 %
Driver sizing specification 280M
Flow,best eff.Point(BEP) 116.30 l/s Margin over specification 1.13
Flow ratio(rated/BEP) 94.58 % Service factor
Head ratio(rated/Max Diameter) 61.33 % Power,hydraulic 64.68 kW
Diameter ratio(ratio/max) 80.28 % Power,rated 79.82 kW
Viscous coefficients(CQ/CH/CE) 1.0/1.0/1.0 Power,maximum 95.90 kW
Selection status Acceptable Min recommended driver 90.00 kW

P(kW)
125

100

75

50

25
0
0 25 50 75 100 125 150 175 200 225 250

H(m) Eff(%)
120 100

108

96 80

84
508.00mm
72 60

60

48 407.84mm 40

36
355.60mm
24 20

12

0 0
0 25 50 75 100 125 150 175 200 225 250

NPSH(m) Q(l/s)
12.5
10.0
7.5
5.0
2.5
0.0
0 25 50 75 100 125 150 175 200 225 250

Printed from Grundfos Selector [V2.0.2019-6-30] Motor Sizing Method:ISO 5199


1/3
Printed from Grundfos Selector [V2.0.2019-6-30]
2/3
Note:

1.The pump may be exposed to forces and moments:


(the pipeline connection is tension-free)
Fx=Fy=Fz=2000N Mx=My=Mz=750Nm
Other forces and torque are inadmissible
2.Pump parameter Weight
Pump:640kg Motor:685kg
Water:/kg Baseplate:48kg
3.Pump rotational inertia: YY X HZ HS HD HE HA CP LM W HM HR HP n
Without water:2.45kgm2
483 432 651 371 371 525 595 994 1196 448 1151 23 200 6 Pump model LS200-150-508B(CW)
With water:/kgm2
M HL HB Ls d3 HF h Motor series MMG-W(Low voltage)
4.Foundation static load
Pump unit:13.5kN M20x500 755 1910 260 150 560 12 Motor brand MMG IE3

5.Direction of rotation:Clockwise Ds D1/D1* K1 T1/T1* n1 d1 Dd D2/D2* K2 T2/T2* n2 d2 Speed(rpm) 1485


(Pump direction of rotation as seen from motor end) 200 381/343 295 41/29 12 23 150 318/285 240 37/25 8 23 Power(kW) 90
6.Packaging:Complete package for motor and pump. Flange rating PN16
7.All units are in [mm] unless others are stated. Total weight(kg) 1373
8.Dimensions with * is only for stainless steel pump housing.
Disclaimer:Figure only for reference,main dimensions data table will prevail.

2019-8-20
DIMENSIONS
Split Case Pumps

LS200-150-508B(CW) Outline Drawing

YY X HZ SH DH AE A CP W N
483 432 651 171 171 260 318 994 546 95
D G U BP WS B WB H n b
451 25 53.975 305 394 356 724.5 19 4 12.7
h Ls
59.51 260

SUCTION FLANGE DIMENSION


DN T/T* n d K D/D*
200 41/29 12 23 295 381/343
DISCHARGE FLANGE DIMENSION
DN T/T* n d K D/D*
150 37/25 8 23 240 318/285

Explanation:
1.Flange drilled to:PN16;
2.Weight:640kg.
3.Dimensions with * is only for stainless steel pump housing.

Note:All units are in [mm] unless others are stated. 2019-8-20


Printed from Grundfos Selector [V2.0.2019-6-30]