You are on page 1of 12

PT PEMBANGKITAN JAWA BALI SERVICES

SIAP INTEGRATED MANAGEMENT SYSTEM


MAJOR INSPECTION CTG 103
PT TRANS-PACIFIC PETROCHEMICAL INDOTAMA - 2020
Description STATIC CALIBRATION ( Before )
Equipment PRISMIC ROTOR EARTH FAULT R10
MEASUREMENT SHEET Document Number FU-TPPI-LIS-01.23
Issued 01 Juli 2019
Task No. : Revision : 00 Section : Listrik
WO No. : Page : 1 of 1 Date : 10 Januari 20
NAMA : Prismic REF R10
MANUFACTURER : Brush
Type : Infra Red
SERIAL NUMBER : HB959200700

No Deskripsi / Test Point Satuan Standart Hasil Keteran

A TRANSMITER

V dc ± 30 34
1 F1 - F2
mA 25 - 35 28.98
✘ IR 1 On
2 Infra Red On / Of On ✘ IR 2 On By Cam

B Aerial

1 Term 2 - 4 V dc 7,5 - 9,5 8.4

khz 20 22.32 Norm

t/div = 11,2µs
2 Term 1 - 2 ( Normal Condition ) div = 4 div
frek = 22,32 kH
V/div = 200 mV
div = 3,4 div
Volt = 6,8 Volt

khz < 20 0 Norm

Term 1 - 2 ( Fault Condition )


3 Simulasi gangguan d
menghubungkan te
dengan body transm

C Receiver

1 Term 1 - 2 khz 20 22.32

2 Term 2 - 4 V dc 7,5 - 9,5 8.4

3 Term 5 - 15 V dc 7,5 - 9,5 8.4

4 Term 10 - 12 V ac 220 220 With Slide re

5 Term TP1 - TP4 V dc 6 Na

6 Term TP1 - TP5 V dc 7.8 Na

LED 3 On < 0,5 1.671 Ubnorm


7 Term TP1 - TP13 V dc
LED 3 Of > 10
8 LED 1 (Supply inhibit released) On /Of On On

9 LED 2 ( Field voltage inhibit released ) On /Of On Of Ubnorm


10 LED 3 (Protection Operated) On /Of Of Of
11 LED 4 ( Supply present ) On /Of On On
LED 3 On, LED 3 On
Push On /Of Indicator On (±3 Indicator
secon )
Earth Fault Test On
12 Ubnorm
( Push Button ) ✘ Led 3 Of
LED 3 Of,
Release On /Of Indicator Of Indicator
✘ Of

Berdasarkan hasil pengukuran di atas, kondisi setting Receiver dalam kondisi tidak normal (pergeseran set ponit). untuk m
RECOMMENDATION mana kondisi receiver disarankan untuk dilakukan kalibrasi ulang ( ref : manual book atau IK REF R10 ).

Measuring Tool Multimeter , Oscilloscope


PT. TPPI PT. PJB SERVICES
Description
Approved by Checked by Insp

Signature

Name
Position
Approval Date
IC CALIBRATION ( Before )
MIC ROTOR EARTH FAULT R10
PPI-LIS-01.23
uli 2019
Listrik
10 Januari 2020

Keterangan

By Camera

Normal

t/div = 11,2µs
div = 4 div
frek = 22,32 kHz
V/div = 200 mV
div = 3,4 div
Volt = 6,8 Volt

Normal

Simulasi gangguan dengan


menghubungkan terminal F2(-Ve)
dengan body transmitter(Test)

With Slide regulator

Ubnormal
Ubnormal

Ubnormal

etting Receiver dalam kondisi tidak normal (pergeseran set ponit). untuk mengetahui sejauh
brasi ulang ( ref : manual book atau IK REF R10 ).

PT. PJB SERVICES


Inspected by
PT PEMBANGKITAN JAWA BALI SERVICES
SIAP INTEGRATED MANAGEMENT SYSTEM
MAJOR INSPECTION CTG 103
PT TRANS-PACIFIC PETROCHEMICAL INDOTAMA - 2020
Description STATIC CALIBRATION ( Before )
Equipment PRISMIC ROTOR EARTH FAULT R10
MEASUREMENT SHEET Document Number FU-TPPI-LIS-01.23
Issued 01 Juli 2019
Task No. : Revision : 00 Section : Listrik
WO No. : Page : 1 of 1 Date : 10 Januari 20
NAMA : Prismic REF R10
MANUFACTURER : Brush
Type : Infra Red
SERIAL NUMBER : HB959200700

No Deskripsi / Test Point Satuan Standart Hasil Keteran

A TRANSMITER

V dc ± 30 34
1 F1 - F2
mA 25 - 35 28.98
✘ IR 1 On
2 Infra Red On / Of On ✘ IR 2 On By Cam

B Aerial

1 Term 2 - 4 V dc 7,5 - 9,5 8.4

khz 20 22.32

t/div = 11,2µs
2 Term 1 - 2 ( Normal Condition ) div = 4 div
frek = 22,32 kH
V/div = 200 mV
div = 3,4 div
Volt = 6,8 Volt

khz < 20 0

Term 1 - 2 ( Fault Condition )


3 Simulasi gangguan d
menghubungkan te
dengan body transm

C Receiver

1 Term 1 - 2 khz 20 22.32

2 Term 2 - 4 V dc 7,5 - 9,5 8.4

3 Term 5 - 15 V dc 7,5 - 9,5 8.4

4 Term 10 - 12 V ac 220 220 With Slide re

5 Term TP1 - TP4 V dc 6 Na

6 Term TP1 - TP5 V dc 7.8 Na

LED 3 On < 0,5 0.034 Norm


7 Term TP1 - TP13 V dc
LED 3 Of > 10 13.03
8 LED 1 (Supply inhibit released) On /Of On On

9 LED 2 ( Field voltage inhibit released ) On /Of On On Norm


10 LED 3 (Protection Operated) On /Of Of Of
11 LED 4 ( Supply present ) On /Of On On
LED 3 On, ✘ LED 3 On
Push On /Of Indicator On (±3 Indicator
secon ) ✘ On
Earth Fault Test
12 Norm
( Push Button) ✘ Led 3 Of
LED 3 Of,
Release On /Of Indicator Of Indicator
✘ Of

ACCEPTED
RECOMMENDATION Setelah dilakukan kalibrasi ulang, kondisi receiver telah normal kembali( seeting RV2 dan RV3). Untuk langkah selanjutnya dilaku
pada saat kondisi fullspeed no no load untuk penganbilan data "minimum Voltage inhibited".

Measuring Tool Multimeter , Oscilloscope


PT. TPPI PT. PJB SERVICES
Description
Approved by Checked by Insp

Signature

Name
Position
Approval Date
IC CALIBRATION ( Before )
MIC ROTOR EARTH FAULT R10
TPPI-LIS-01.23
uli 2019
Listrik
10 Januari 2020

Keterangan

By Camera

t/div = 11,2µs
div = 4 div
frek = 22,32 kHz
V/div = 200 mV
div = 3,4 div
Volt = 6,8 Volt

Simulasi gangguan dengan


menghubungkan terminal F2(-Ve)
dengan body transmitter(Test)

With Slide regulator

Normal
Normal

Normal

h normal kembali( seeting RV2 dan RV3). Untuk langkah selanjutnya dilakukan kalibrasi
ilan data "minimum Voltage inhibited".

PT. PJB SERVICES


Inspected by
PT PEMBANGKITAN JAWA BALI SERVICES
SIAP INTEGRATED MANAGEMENT SYSTEM
MAJOR INSPECTION CTG 103
PT TRANS-PACIFIC PETROCHEMICAL INDOTAMA - 2020
Description FULL SPEED NO LOAD CALIBRATION
Equipment PRISMIC ROTOR EARTH FAULT R10
MEASUREMENT SHEET Document Number FU-TPPI-LIS-01.23
Issued 01 Juli 2019
Task No. : Revision : 00 Section : Listrik
WO No. : Page : 1 of 1 Date :
NAMA : Prismic REF R10
MANUFACTURER : Brush
Type : Infra Red
SERIAL NUMBER : HB959200700

No Deskripsi / Test Point Satuan Standart Hasil Keterangan

A TRANSMITER

1 Rotor Rotating rpm 1500

2 Full Speed No Load Yes/No Yes

B Aerial

1 Term 2 - 4 V dc 7,5 - 9,5

khz 20

2 Term 1 - 2 ( Normal Condition )

khz < 20

3 Term 1 - 2 ( Fault Condition)

C Receiver

1 Term 1 - 2 khz 20

2 Term 2 - 4 V dc 7,5 - 9,5

3 Term 5 - 15 V dc 7,5 - 47

4 Term 10 - 12 V ac 220

5 Term TP1 - TP4 V dc 6

6 Term TP1 - TP5 V dc 7.8

LED 3 On < 0,5


7 Term TP1 - TP13 V dc
LED 3 Of > 10
8 LED 1 (Supply inhibit released) On /Of On

9 LED 2 ( Field voltage inhibit released ) On /Of On


10 LED 3 (Protection Operated) On /Of Of
11 LED 4 ( Supply present ) On /Of On
LED 3 On, ✘ LED 3 On
Push On Indicator On (±3 Indicator
secon )
Earth Fault Test ✘ On
12 ( Push Button) ✘ Led 3 Of
LED 3 Of,
Release Of Indicator Of Indicator
✘ Of

ACCEPTED / REWORK / REPLACE


RECOMMENDATION (by Quality Control)
Measuring Tool Multimeter , Oscilloscope
PT. TPPI PT. PJB SERVICES
Description
Approved by Checked by Inspecte

Signature

Name
Position
Approval Date
FULL SPEED NO LOAD CALIBRATION
PRISMIC ROTOR EARTH FAULT R10
FU-TPPI-LIS-01.23
01 Juli 2019
Listrik

Keterangan
PT. PJB SERVICES
Inspected by

You might also like