Question
1. Why am I getting Type 05 Code 01 error in the 440C-CR30-22BBB?
2. What is (Type 05) Internal Safety Synch Fault and (Code 01) Compare UART data during operation?
Environment
440C-CR30-22BBB
Answer
A Type 05 Code 01 fault code will occur if a SWS input is connected to terminal 10 or 11 of the CR30
relay and the SWS input is not used in the project.