01/10/2019 931004 - Studio 5000: CodeMeter runtime server service is not running - Error 200

Rockwell Automation Home  Support Center  Search Knowledgebase

Studio 5000: CodeMeter runtime server service is not running -


Error 200
931004 | Date Created: 09/28/2016 | Last Updated: 05/02/2019
 Print
Access Level: TechConnect

Problem
When launching Studio 5000 Logix Designer the following error code occurs:

Codemeter runtime server service is not running. Error 200.

When trying to open any ACD file the following error code occurs:

CmActLicense runtime system is not installed!

Environment
Studio 5000 Logix Designer v23.00 or higher

Solution 1
Follow the steps below:

1. Go to Control Panel > Program and Features and uninstall CodeMeter Runtime
Kit and Rockwell Automation CM Runtime if existed
2. Launch CodeMeterRuntime.exe or Rockwell Automation CM.msi from the following
folder of Studio 5000 installation package:
23.00.00-Studio5000-Web\Studio5000\System
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/931004 1/2
01/10/2019 931004 - Studio 5000: CodeMeter runtime server service is not running - Error 200

24.00.00-Studio5000-Web\Redist\CodeMeter_5.20.1
26.01.00-Studio5000-Web\Redist\CodeMeter_5.21.0
27.00.00-Studio5000-Web\Redist\CodeMeter_5.21.3799
28.00.00-Studio5000-Web\Redist\CodeMeter_5.21.3875
29.00.01-Studio5000-Web\Redist\CodeMeter_6.20
30.01.01-Studio5000-Web\Redist\CodeMeter_6.30
31.00.01-Studio5000-DVD\Redist\CodeMeter_6.50c
32.00.00-Studio5000-Web\Redist\CodeMeter_6.70.3152 

Solution 2
If solution 1 is not working while FactoryTalk Activation Manager v4.03.03 or higher is installed,
reinstall FactoryTalk Activation Manager.

 
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a
particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly,
the information in this web site is not intended to constitute application, design, software or
other professional engineering advice or services. Before making any decision or taking any
action, which might affect your equipment, you should consult a qualified professional advisor.
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR
ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES
THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL
INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL
ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT,
INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION
HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN
RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE
IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND
NON-INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of
implied warranties; thus, this disclaimer may not apply to you.

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/931004 2/2

You might also like