SYMBOLS & STANDARDS


1) INSTRUMENT ABBREVIATIONS

PRESSURE
 P : PRESSURE
 PI : PRESSURE INDICATOR

 PG : PRESSURE GAUGE

 PCV : PRESSURE CONTROL VALVE

 PT : PRESSURE TRANSMITTER
 PIT : PRESSURE INDICATING TRANSMITTER

 PIC : PRESSURE INDICATING CONTROLLER

 PDT : PRESSURE DIFFERENTIAL TRANSMITTER

 PRV : PRESSURE REDUCING VALVE


 PSV : PRESSURE SAFETY VALVE

 PS : PRESSURE SWITCH

 PSH : PRESSURE SWITCH HIGH


 PSL : PRESSURE SWITCH LOW

 PSHH : PRESSURE SWITCH HIGH HIGH

 PSLL : PRESSURE SWITCH LOW LOW

 PDS : PRESSURE DIFFERENTIAL SWITCH


 PDSH : PRESSURE DIFFERENTIAL SWITCH HIGH

 PDSL : PRESSURE DIFFERENTIAL SWITCH LOW

 PA : PRESSURE ALARM

TEMPERATURE
 T : TEMPERATURE
 TI : TEMPERATURE INDICATOR

 TW : THERMOWELL

 TM : THERMOMETER

 TE : TEMPERATURE ELEMENT
 RTD : RESISTANCE TEMPERATURE DETECTOR

 T/C : THERMOCOUPLE

 TT : TEMPERATURE TRANSMITTER
 TIC : TEMPERATURE INDICATING CONTROLLER

 TRC : TEMPERATURE RECORDER CONTROLLER

 TCV : TEMPERATURE CONTROL VALVE

 TS : TEMPERATURE SWITCH
 TSH : TEMPERATURE SWITCH HIGH

 TSL : TEMPERATURE SWITCH LOW


Automationforum.in Page 1 of 15
Automationforum.in

 TA : TEMPERATURE ALARM

FLOW
 F : FLOW

 FI : FLOW INDICATOR

 FG : FLOW GLASS / FLOW GAUGE


 FE : FLOW ELEMENT

 FIT : FLOW INDICATING TRANSMITTER

 FCV : FLOW CONTROL VALVE

 FIC : FLOW INDICATING CONTROLLER


 FS : FLOW SWITCH

 FY : FLOW CONVERTER

 FA : FLOW ALARM

 FR : FLOW RECORDER
 FRC : FLOW RECORDING CONTROLLER
LEVEL
 L : LEVEL

 LI : LEVEL INDICATOR
 LG : LEVEL GAUGE

 LIT : LEVEL INDICATING TRANSMITTER

 LCV : LEVEL CONTROL VALVE


 LDT : LEVEL DISPLACER TRANSMITTER

 LIC : LEVEL INDICATING CONTROLLER

 LRC : LEVEL RECORDING CONTROLLER

 LS : LEVEL SWITCH
 LSH : LEVEL SWITCH HIGH

 LSL : LEVEL SWITCH LOW

 LA : LEVEL ALARM

 RLT : RADAR LEVEL TRANSMITTER

Automationforum.in Page 2 of 15
Automationforum.in

GENERAL
 DCS : DISTRIBUTED CONTROL SYSTEM

 SCADA : SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM

 PLC : PROGRAMMABLE LOGIC CONTROLLER


 HART : HIGHWAY ADDRESSABLE REMOTE TRANSDUCER

 HHT : HAND HELD TERMINAL

 SFC : SMART FIELD CONFIGURATOR

 ESD : EMERGENCY SHUT DOWN


 AOV : AIR OPERATED VALVE

 MOV : MOTOR OPERATED VALVE

 SV : SOLENOID VALVE

 XVE : VIBRATION PROXIMITOR


 XVT : VIBRATION TRANSMITTER

 AE : ANALYZER

 JB : JUNCTION BOX
 ILD : INSTRUMENT LOOP DIAGRAM

 P&ID : PIPING AND INSTRUMENT DIAGRAM

 IIS : INSTRUMENT INSTALLATION SCHEDULE

 TDR : TIME DELAY RELAY


 SP : SET POINT

 NC : NORMALLY CLOSED

 NO : NORMALLY OPEN

 MCC : MOTOR CONTROL CENTRE


 IAS : INSTRUMENT AIR SUPPLY

 IGS : INSTRUMENT GAS SUPPLY

 ACFO : AIR TO CLOSE FAIL OPEN


 AOFC : AIR TO OPEN FAIL CLOSE

 FFA : FLAME FAILURE ALARM

 P/I – P to I : PNEUMATIC TO CURRENT CONVERTER

 I/P – I to P : CURRENT TO PNEUMATIC CONVERTER


 PB : PUSH BUTTON

 PID : PROPORTIONAL, INTEGRAL AND DERIVATIVE

 E/H : ELECTRO HYDRAULIC ACTUATOR

 BOV : BLOW DOWN VALVE


 A/M : AUTO / MANUAL – 2 POSITION SWITCH

 ZS : POSITION SWITCH

 HS : HAND SWITCH

Automationforum.in Page 3 of 15
Automationforum.in

2) INSTRUMENT LINE SYMBOLS

2.1) INSTRUMENT SUPPLY or CONNECTION TO PROCESS ___________________

2.2) PNEUMATIC SIGNAL ___________________

2.3) ELECTRICAL SIGNAL (ANALOG SIGNAL) (mA DC (OR) VDC) ------------------------

3.4) ELECTROMAGNETIC or SONIC SIGNAL ___________________

3.5) HYDRAULIC SIGNAL ___________________

2.6) CAPILLARY TUBE (FILLED SYSTEM) ___________________

2.7) PULSE TRAIN _ _ _ _ _ _ _

2.8) INTERNAL SYSTEM LINK


(SOFTWARE or DATA LINK)

-----------------------------------------------------------------------------------------------------------------

3) TYPES OF SUPPLY

3.1) AS - AIR SUPPLY IA – INSTRUMENT AIR


Options
PA – PLANT AIR

3.2) ES – ELECTRICAL SUPPLY

3.3) GS – GAS SUPPLY

3.4) HS – HYDRAULIC SUPPLY

3.5) NS – NITROGEN SUPPLY

3.6) SS – STEAM SUPPLY

3.7) WS – WATER SUPPLY

The “ES” or “AS” symbol is to be used only for Field Devices requiring supply. For
panel mounted instruments power supplies are not shown on flow sheet.

ES 24 V DC

IAS 130 kPa

Automationforum.in Page 4 of 15
Automationforum.in

4) GENERAL INSTRUMENT SYMBOLS

Automationforum.in Page 5 of 15
Automationforum.in

Automationforum.in Page 6 of 15
Automationforum.in

5) IDENTIFICATION LETTERS

TABLE – 1

FIRST LETTER (4) SUCCEEDING LETTER (3)


MEASURED / INITIATING MODIFIER READOUT / OUTPUT MODIFIER
VARIABLE PASSIVE FUNCTION
FUNCTION
A ANALYSIS (5, 19) ALARM

B BURNER, COMBUSTION USER’S CHOICE (1) USER’S CHOICE (1) USER’S CHOICE (1)

C USER’S CHOICE (1) CONTROL (13)

D USER’S CHOICE (1) DIFFERENTIAL


(4)
E VOLTAGE SENSOR (PRIMARY
ELEMENT)
F FLOW RATE RATIO
(FRACTION) (4)
G USER’S CHOICE (1) GLASS, VIEWING
DEVICE (9)
H HAND HIGH (7,15,16)

I CURRENT (ELECTRICAL) INDICATE (10)

J POWER SCAN (7)

K TIME, TIME SCHEDULE TIME, RATE OF CONTROL STATION


CHANGE (4, 21) (22)
L LEVEL LIGHT (11) LOW (7, 15, 16)

M USER’S CHOICE (1) MOMENTARY MIDDLE,


(4) INTERMEDIATE (7,
15)
N USER’S CHOICE (1) USER’S CHOICE (1) USER’S CHOICE (1) USER’S CHOICE (1)

O USER’S CHOICE (1) ORIFICE,


RESTRICTION
P PRESSURE, VACUUM POINT (TEST)
CONNECTION
Q QUANTITY INTEGRATE,
TOTALIZE (4)
R RADIATION RECORD (17)

S SPEED, FREQUENCY SAFETY (8) SWITCH (13)

T TEMPERATURE TRANSMIT (18)

U MULTIVARIABLE (6) MULTIFUNCTION (12) MULTIFUNCTION (12) MULTIFUNCTION (12)

V VIBRATION, MECHANICAL VALVE, DAMPER,


ANALYSIS (19) LOUVER (13)
W WEIGHT, FORCE WELL

X UNCLASSIFIED (2) X AXIS UNCLASSIFIED (2) UNCLASSIFIED (2) UNCLASSIFIED (2)

Y EVENT, STATE / Y AXIS RELAY, COMPUTE,


PRESENCE (20) CONVERT(13,14,18)
Z POSITION, DIMENSION Z AXIS DRIVER,
ACTUATOR,
UNCLASSIFIED
FINAL CONTROL
ELEMENT

NOTE: Numbers in parentheses refer to specific explanatory notes.

Automationforum.in Page 7 of 15
Automationforum.in

6) TYPICAL LETTER COMBINATIONS


TABLE – 2

Automationforum.in Page 8 of 15
Automationforum.in

7) FUNCTIONAL BLOCKS – FUNCTIONAL DESIGNATIONS

THE FUNCTION DESIGNATIONS ASSOCIATED WITH CONTROLLERS, COMPUTING DEVICES,


CONVERTERS AND RELAYS MAY BE USED INDIVIDUALLY OR IN COMBINATION (ALSO SEE TABLE 1,
NOTE 14). THE USE OF A BOX AVOIDS CONFUSION BY SETTING OFF THE SYMBOL FROM OTHER
MARKINGS ON A DIAGRAM AND PERMITS THE FUNCTION TO BE USED AS A STAND ALONE BLOCK ON
CONCEPTUAL DESIGNS.
TABLE -3

Automationforum.in Page 9 of 15
Automationforum.in

Automationforum.in Page 10 of 15
Automationforum.in

Automationforum.in Page 11 of 15
Automationforum.in

Automationforum.in Page 12 of 15
Automationforum.in

Automationforum.in Page 13 of 15
Automationforum.in

Automationforum.in Page 14 of 15
Automationforum.in

8. APPLICATION EXERCISE

Automationforum.in Page 15 of 15