You are on page 1of 6

Winding Ohmmeter RMO-TW

 Three resistance measurement channels


 One temperature measurement channel
 Accuracy (0,1% rdg + 0,1% F.S.)
 Lightweight
 On-load tap changer verification
 Automatic resistance measurement for the Heat Run test
 Rapid automatic demagnetization
 Automatic discharge circuit
 Resistance measurement of transformers, rotary machines and non-inductive objects
 Four models: RMO10TW, RMO20TW, RMO30TW, RMO50TW

Description
The Winding Ohmmeter of the RMO-TW series RMO-TW instrument can perform a simple,
is designed for winding resistance measurement quick and reliable transformer on-load tap
of inductive objects. The RMO-TW instrument is changer verification. This instrument enables
based on the state of the art technology, using measurements of a winding resistance in every
the most advanced switch mode technology tap position of an on-load tap changer without
available today. The RMO-TW instrument is discharging between the tests. Problems with
accurate (0,1% rdg + 0,1% F.S.), powerful (up to switching of the OLTC, such as interruption, can
50 A) and lightweight. It generates a true DC be detected with these measurements. The
ripple free current with automatically regulated results are displayed on a backlit LCD display.
measurement and discharging circuit.

Application
The list of the instrument application includes:

 Three-channel winding resistance measurement, which enables simultaneous winding resistance


measurement of up to three windings on a single phase

 Detection of interruptions during the operation of on-load tap changers (OLTC), performed on a
single phase

 Heat Run test, which enables obtaining the Hot Spot temperature along with resistance graph during
the cooling process
B-RXX0TW-311-EN, 2018-05-21

1
Connecting RMO-TW to Transformer Resistance Testing in Multiple Tap
Changer Positions
The RMO-TW has three separate resistance
measurement channels, which enable The winding resistance of all tap changer
simultaneous measurement of the primary, positions in one phase can be measured as part
secondary and tertiary winding on the same of a single test, without discharging between
phase, as presented in the figure above. This measurements. Different test modes are
significantly speeds up the measurement and provided for on-load tap changers (OLTC) and
reduces the total transformer testing time. At the de-energized tap changers (DETC). The
same time, by saturating the magnetic core instrument detects interruptions during the
through the HV and LV windings the stabilization operation of on-load tap changers and produces
time and subsequently the total testing time is a warning message to the operator.
reduced even more.
Automatic_Transformer
Simultaneous Three-Channel Winding Demagnetization
Resistance Measurement After a DC current test, such as a winding
The RMO-TW injects the current with a voltage resistance measurement, the magnetic core of
value as high as 55 V. This ensures that the a power or a measurement transformer may be
magnetic core is saturated quickly and duration magnetized. Also, when disconnecting a
of the test is as short as possible. The three transformer from a service, some amount of
independent channels enable simultaneous magnetic flux trapped in the core could be
testing of three windings in series – primary, present.
secondary and tertiary windings. There is The remnant magnetism can cause various
enough memory within the RMO-TW instrument problems such as erroneous measurements on
to store 5000 measurements. All measurements a transformer, or an inrush current at start-up
are time and date stamped. of a power transformer, or an incorrect
The instrument is equipped with thermal and operation of the protective relays due to the
overcurrent protection. The RMO-TW has very magnetized CT cores. To eliminate this source
high ability to cancel electrostatic and of potential problems, demagnetization should
electromagnetic interference that exists in HV be performed. When the discharging process
electric fields. It is achieved by a proprietary has been completed, the RMO-TW can perform
B-RXX0TW-311-EN, 2018-05-21

filtration solution applied to both, the hardware fully automatic demagnetization.


construction and the application software Demagnetizing the magnetic core of a
implementation. A special mode is provided for transformer requires alternating current applied
the resistance measurement in multiple de- with decreasing magnitude down to zero. The
energized tap changer (DETC) positions. RMO-TW provides this alternating current by
internally changing the polarity of a controlled
DC current.

2
DV-Win Software Heat Run Test Application

The DV-Win application software enables The DV-Win application software has an
control and observation of the test process, as additional Heat Run temperature/resistance
well as saving and analyzing the results on a extrapolation feature. After the transformer
PC. It provides a test report, arranged in a heating is switched off, the RMO-TW is
selectable form as an Excel spreadsheet, PDF, immediately connected to up to three
or Word. The software provides additional transformer windings and the timer is started.
OLTC (tap changer) verification option by The winding resistance is measured at regular
recording the test current during the transition. time intervals. This information is used to
The standard interface is USB. RS232 is automatically extrapolate the values of
optional. temperature and resistance at the moment when
the transformer was switched off.
B-RXX0TW-311-EN, 2018-05-21

3
Technical Data
Winding Resistance Measurement Computer Interface
 Test currents:  USB
5 mA – 10 A DC for RMO10TW  Optional: RS232
5 mA – 20 A DC for RMO20TW
5 mA – 30 A DC for RMO30TW Warranty
5 mA – 50 A DC for RMO50TW  3 years
 Output voltage: up to 55 V DC
 Measurement range: 0,1 μΩ - 10 kΩ Environmental Conditions
 Typical accuracy:  Operating temperature:
±(0,1% rdg + 0,1% F.S.) for 0,1 μΩ-1,999 kΩ range - 10 ºC to + 55 ºC / + 14 ºF to + 131 ºF
±(0,2% rdg + 0,1% F.S.) for 2 kΩ - 10 kΩ range  Storage & transportation:
- 40 ºC to + 70 ºC / - 40 ºF to + 158 ºF
Resolution  Humidity 5 % - 95 % relative humidity,
 0,1 μΩ – 999,9 μΩ: 0,1 μΩ non condensing
 1,000 mΩ – 9,999 mΩ: 1 μΩ
 10,00 mΩ – 99,99 mΩ: 10 μΩ Dimensions and Weight
 100,0 mΩ – 999,9 mΩ: 0,1 mΩ Device Weight Dimensions (WxHxD)
 1,000 Ω – 9,999 Ω: 1 mΩ RMO10TW 8 kg / 205 x 287 x 410 mm
 10,00 Ω - 99,99 Ω: 10 mΩ RMO20TW 17.6 lbs 8.1 x 11.3 x 16.4 in
RMO30TW 8.5 kg / 205 x 287 x 410 mm
 100,0 Ω – 999,9 Ω: 0,1 Ω
RMO50TW 18.7 lbs 8.1 x 11.3 x 16.4 in
 1,000 kΩ – 9,999 kΩ: 1 Ω
Mains Power Supply
Data Storage
 5000 internal memory positions  Connection according to IEC/EN60320-1;
UL498, CSA 22.2
Printer (optional)  Mains supply: 90 V - 264 V AC
 Thermal printer  Frequency: 50 / 60 Hz
 Paper width 80 mm  Input power: 2 250 VA
 Fuse 15 A / 250 V, type F, not user replaceable
OLTC Dynamic Resistance Measurement
 Sampling rate: 4 ms Applicable Standards
 Automatic open circuit detection and warning  Installation/overvoltage: category II
 Transition current ripple measurement  Pollution: degree 2
 Transition time measurement using DV-Win
software  Low voltage directive: Directive 2014/35/EU
(CE conform); Applicable standards, for a
 Timing measurement of different transition class I instrument, pollution degree 2,
changes using DV-Win graph analysis tool
installation category II: IEC EN61010-1

Temperature Measurement  EMC: Directive 2014/30/EU (CE Conform)

 One temperature measurement channel Applicable standard EN 61326-1


B-RXX0TW-311-EN, 2018-05-21

Thermometer Pt100
 Safety: CAN/CSA-C22.2 No. 61010-1, 2nd
-50 ºC +180 ºC / -58 ºF +356 ºF
edition, including Amendment 1
50 mm x 6 mm
All specifications herein are valid at ambient temperature of + 25 °C and recommended accessories.
Specifications are subject to change without notice.
Specifications are valid if the instrument is used with the recommended set of accessories.

4
Current and Sense cables with TTA clamps Voltage Sense cables with TTA clamps

Current connection cable with TTA clamps Transport case

Cable plastic case Cable bag


B-RXX0TW-311-EN, 2018-05-21

Device bag Test shunt

5
Order Info
Instrument with Included accessories Article No
Winding Ohmmeter RMO-TW
DV-Win PC software including USB cable
RMOXXTW-N-00
Mains Power cable
Ground (PE) cable

Recommended Article No
Current cables 2 x 10 m 10 mm2 (32.8 ft, 7 AWG) and Sense cables 2 x 10 m
CS-10-10LMWC
(32.8 ft) with TTA clamps*
Current cables 2 x 10 m 2,5 mm2 (32.8 ft, 13 AWG) and Sense cables 2 x 10 m
CS-10-02BPWC
(32.8 ft) with TTA clamps**
Sense cables 2 x 10 m (32.8 ft) with TTA clamps S2-10-02BPWC
Current connection cable 1 x 5 m 10 mm2 (16.4 ft, 7 AWG) with TTA clamps* CX-05-102XWC
Current connection cable 1 x 5 m 6 mm2 (16.4 ft, 9 AWG) with TTA clamps** CX-05-062XWC
Transport case HARD-CASE-ME
*Recommended for RMO30TW and RMO50TW
** Recommended for RMO10TW and RMO20TW

Optional Article No
Test shunt 150 A / 150 mV SHUNT-150-MK
Thermal printer 80 mm (3.15 in) (built-in) PRINT-080-00
Cable plastic case – small size CABLE-CAS-01
Cable plastic case – medium size CABLE-CAS-02
Cable bag CABLE-BAG-00
Current cables 2 x 15 m 10 mm2 (49.2 ft, 7 AWG) and Sense cables 2 x 15 m
CS-15-10LMXC
(49.2 ft) with TTA clamps*
Current cables 2 x 15 m 2,5 mm2 (49.2 ft, 13 AWG) and Sense cables 2 x 15 m
CS-15-02BPWC
(49.2 ft) with TTA clamps**
Current cables 2 x 20 m 16 mm2 (65.6 ft, 5 AWG) and Sense cables 2 x 20 m
CS-20-10LMXC
(65.6 ft) with TTA clamps*
Current cables 2 x 20 m 2,5 mm2 (65.6 ft, 13 AWG) and Sense cables 2 x 20 m
CS-20-02BPWC
(65.6 ft) with TTA clamps**
Sense cables 2 x 15 m (49.2 ft) with TTA clamps S2-15-02BPWC
Sense cables 2 x 20 m (65.6 ft) with TTA clamps S2-20-02BPWC
Current connection cable 1 x 12 m 10 mm2 (39.4 ft, 5 AWG) with TTA clamps* CX-12-102XWC
Current connection cable 1 x 12 m 6 mm2 (39.4.4 ft, 9 AWG) with TTA clamps** CX-12-062XWC
Temperature sensor 1 x 50 mm (1.97 in) + 5 m (16.4 ft) cable TEMP1-050-05
Temperature sensor 1 x 50 mm (1.97 in) + 10 m (32.8 ft) cable TEMP1-050-10
Temperature sensor 1 x 50 mm (1.97 in) + 15 m (49.2 ft) cable TEMP1-050-15
* For RMO30TW and RMO50TW
** For RMO10TW and RMO20TW
B-RXX0TW-311-EN, 2018-05-21

IBEKO Power AB Contact


Stockholmsvägen 18 Phone: +46 70 0925 000
181 50 Lidingö, Sweden E-mail: sales@dv-power.com

You might also like